- No category
advertisement
User Manual
Installation and Operation Instructions
Lubrication System QLS 301
4197a99
Form 403013
6093b03
U.S. Patent-No. 6,244,387, German Registration Design No. 29923765.6
810-55230-1
2.1A-38006-E05
User Manual
Installation and Operation Instructions
All rights reserved.
Any duplication of this User Manual, in its entirety or in part, by whatever means is prohibited without the prior consent in writing of Lincoln GmbH & CO. KG.
Subject to modifications without prior notification.
© 2005 by
LINCOLN GmbH & Co. KG
Postfach 1263
D-69183 Walldorf
Phone: +49 (6227) 33-0
Fax: +49 (6227) 33-259
Page 2 of 48 2.1A-38006-E05 Form 403013
User Manual
Installation and Operation Instructions
Table of Contents
Page
Introduction ..................................................................... 4
Explanation of Symbols Used ............................................ 4
User’s Responsibility ......................................................... 4
Environmental Protection .................................................. 4
Service .............................................................................. 4
Glossary ............................................................................ 4
Safety Instructions .......................................................... 5
Appropriate Use ................................................................ 5
Misuse ............................................................................... 5
General Safety Instructions ................................................ 5
Regulations for Prevention of Accidents ............................ 5
Operation, Maintenance and Repair .................................. 5
Operation/Maintenance ................................................ 6
Exclusion Liability .................................................... 6
Installation ......................................................................... 6
Installation Instructions .................................................. 7
Pump ................................................................................. 7
SSV-Lubricant Metering Device ........................................ 7
Adjusting the output by Crossporting of outlets .................. 7
Single Output ............................................................... 7
Double Multiple Outputs .......................................... 7
Check valves ............................................................... 7
Returning of lubricant quantities ........................................ 8
Lubrication points .............................................................. 9
Installing Zerk-Locks onto Grease Fittings ........................ 9
Connection of Feed Lines ................................................ 10
Filling of Reservoir............................................................ 10
Identification Code
VDC ................................................................................. 11
VAC ................................................................................. 12
Electrical Connecting Diagrams ................................... 13
VAC ................................................................................. 13
VDC ................................................................................. 15
Description
QLS 301 with back position of the SSV divider block ...... 17
QLS 301 with bottom position of the SSV divider block ... 17
QLS 301 with external SSV divider block ........................ 18
Page
Operation ........................................................................ 19
Pump ............................................................................... 19
Pressure Relief Valve ...................................................... 19
Display of the Membrane Keypad .................................... 19
Monitoring time/ malfunction ............................................ 20
Operator keys of the keypad ............................................ 21
Setting the pause time................................................. 21
Display of information regarding the set pause time.... 22
Changing to the different programming levels ............ 22
Monitoring Relay .............................................................. 22
Setting and Operation ..................................................... 23
Factory Settings ............................................................... 23
Operator Keys .................................................................. 23
Display mode ................................................................... 24
Programming mode ......................................................... 25
Operating mode ............................................................... 30
Maintenance, Repair and Tests
Maintenance .................................................................... 33
To fill reservoir ............................................................ 33
Repair .............................................................................. 34
Functional Test ................................................................ 34
Troubleshooting
Pump of the QLS 301 system ........................................... 35
SSV Metering Device ....................................................... 37
Technical Data ................................................................ 39
QLS 301, General ...................................................... 39
Electrical Data ............................................................ 39
Time Setting ............................................................... 39
Relay for Malfunction .................................................. 39
Accessory Kits ............................................................ 39
Dimensions ...................................................................... 40
SSV Divider Blocks ..................................................... 40
Service Parts .................................................................. 41
Version with bayonet plug ................................................ 41
QLS 301 with bottom mounted SSV divider block and square-type plug ....................................................... 42
QLS 301 with back mounted SSV divider block and square-type plug ....................................................... 44
Option for Metrical Fittings ........................................... 46
EC Declaration of Conformity ....................................... 47
Form 403013 2.1A-38006-E05 Page 3 of 48
User Manual
Installation and Operation Instructions
Introduction
Explanation of Symbols Used
The following description standards are used in this manual:
Safety Instructions
Structure of safety instructions:
Pictogram
Furthermore, you will find the following text symbols in this manual:
Listing of applicable statements
- Subpoint of applicable statements
1. Determination of the number or sequence of contents
 Procedural instruction
- Danger note
- How to avoid danger
The following pictograms are used in this manual and are combined with the corresponding signal words:
1013A94 4273a00 6001a02
- ATTENTION
- CAUTION
- WARNING
- ATTENTION
- CAUTION
- WARNING
- NOTE
- IMPORTANT
The signal words give the seriousness of danger if the following text is not observed:
ATTENTION refers to faults or damages on
CAUTION
machines. refers to bad damages and possible injuries.
WARNING
NOTE
IMPORTANT
refers to possible dangerous injuries. indicates improved operation of the device. indicates special operating features of the device.
Example:
ATTENTION!
1013A94
When making use of other than the tested spare parts, serious damage may affect your device.
Therefore, for the operation of your device always use original spare parts made by
Lincoln GmbH & Co. KG.
User's Responsibility
To ensure the safe operation of the unit, the user is responsible for the following:
1. The pump / system shall be operated only for the intended use (see next chapter "Safety Instructions") and its design shall neither be modified nor transformed.
2. The pump / system shall be operated only if it is in a proper functioning condition and if it is operated in accordance with the maintenance requirements.
3. The operating personnel must be familiar with this Owner
Manual and the safety instructions mentioned within and observe these carefully.
The correct installation and connection of tubes and hoses, if not specified by Lincoln GmbH & Co. KG, is the user's responsibility. Lincoln GmbH & Co. KG will gladly assist you with any questions pertaining to the installation.
Environmental Protection
Waste (e.g. used oil, detergents, lubricants) must be disposed of in accordance with relevant environmental regulations.
Service
The personnel responsible for the handling of the pump / system must be suitably qualified. If required, Lincoln GmbH
& Co. KG offers you full service in the form of advice, on-site installation assistance, training, etc. We will be pleased to inform you about our possibilities to support you purposefully.
In the event of inquiries pertaining to maintenance, repairs and spare parts, we require model specific data to enable us to clearly identify the components of your pump / system.
Therefore, always indicate the part, model and series number of your pump / system.
Glossary
Lubricating time
Operating cycle
=
=
Operating time
Lubrication cycle
Page 4 of 48 2.1A-38006-E05 Form 403013
User Manual
Installation and Operation Instructions
Safety Instructions
Appropriate Use
The lubrication system QLS 301 has been designed for initial and retrofit installation. It has been designed for:
1. the automatic lubrication of machines and systems
2. the automatic lubrication of commercial vehicles and construction machines
3. the automatic lubrication of hydraulically driven units and devices.
The lubrication system QLS 301 is able to deliver greases up to NLGI grade 2 or fluid greases of NLGI grade 000 or 00.
Use the QLS 301 exclusively to supply lubricants.
The QLS 301 is adequate for intermittent operation only.
The QLS 301 is adequate for feeding max. 18 lube points per operating cycle.
Do not use QLS 301 with bottom-mounted SSV metering device for mobile applications. Do not install the system with machines exposed to shock.
Misuse
Any use of the QLS 301 that is not expressly mentioned in this User Manual will be regarded as misuse.
If the QLS 301 is used or operated in a different manner other than specified, any claim for warranty or liability will be null and void.
NOTE
6001a02
If personal injury or material damage occurs as a result of inappropriate operation, e.g. if the safety instructions are ignored or resulting from an incorrect installation of the QLS 301, no claims or legal actions may be taken against
Lincoln GmbH & Co. KG.
General Safety Instructions
Lubrication systems QLS 301
- are designed state-of-the-art.
- can be assembled for safe operation.
- must be regularly refilled with clean lubricant.
Incorrect use may result in bearing damage caused by poor or over-lubrication.
Do not over-pressurize reservoir when filling the pump.
Refill QLS 301 pump with clean lubricant.
Each outlet needed must be equipped with an appropriate check valve.
IMPORTANT
Do not paint the pump. Before painting a machine or commercial vehicle, remove or cover the pump completely.
6001a02
Unauthorized modifications or changes to an installed system are not recommended and will void warranty. Any modifications must be subject to prior consultation with the manufacturer of the QLS 301.
Regulations for Prevention of Accidents
To prevent accidents, observe all city, state and federal safety regulation of the country in which the product will be used.
Operation, Repair and Maintenance
1013A94
ATTENTION!
Malfunction because of dirt!
When executing any maintenance or repair works on the QLS 301, ensure absolute cleanliness.
CAUTION!
Switch off the power supply before beginning maintenance or repair work.
4273a00
Repair
Repairs should only be performed by authorized personnel who are familiar with the instructions.
Form 403013 2.1A-38006-E05 Page 5 of 48
User Manual
Installation and Operation Instructions
Safety Instructions, continuation
Operation, Repair and Maintenance, continuation
Operation/Maintenance
Lubrication systems QLS 301
must operate with mounted pressure relief valve, only.
must operate only with mounted or connected SSV divider blocks.
must be regularly filled with clean and air-free lubricant.
operates automatically. However, a regular check (approximately every 2 weeks) should be made to ensure that lubricant is being dispensed from all lubricant points.
Operation with bayonet plug
CAUTION!
If the protective-conductor terminal is not connected or interrupted, dangerous touch voltages may occur on the equipment!
4273a00
Protective measures to be applied for the appropriate operation with bayonet plugs:
"Functional extra-low voltage with safe isolation" /
"Protective Extra-Low Voltage" (PELV)
Standards: EN60204 Part1:1992 / IEC 204-1:1992, modified
DIN VDE 0100 Part 410 / IEC 364-4-41:1992
(see pages 15 to 19)
Disposal
Used or contaminated lubricants must be disposed of in accordance with local environmental regulations, see technical data sheets of lubricants.
Exclusion of Liability
The manufacturer of the centralized lubrication system will not accept any liability for:
damage caused by insufficient lubricant and irregular refilling of pump
damage due to the use of greases which are not or are only conditionally pumpable in centralized lubrication systems
damage caused by the use of contaminated lubricants
damage caused by inadequate disposal of used or contaminated lubricants
damage caused by unauthorized modification of system components
damage caused by the use of unapproved parts (voids the pump warranty)
Installation
IMPORTANT
Do not remove, modify or alter any safety equipment already installed on the machine, the construction machine or the commercial vehicle.
6001a02
If necessary, these devices may be removed temporarily during the installation of the pump.
The devices must be properly put back in place after the installation of the pump.
Use only original spare parts or spare parts authorized by
Lincoln.
Keep pump QLS 301 away from sources of heat (see
Operating Temperature Specification, Technical Data).
Provide access to fill, clean and visually monitor the pump operation.
IMPORTANT
6001a02
Adhere to the installation instructions of the vehicle or machine manufacturer as regards all drilling and welding procedures. Observe the specified minimum distances between bores and upper/lower rim of the frame or between the bores.
4273a00
4273a00
CAUTION!
The QLS 301 may only be installed by qualified personnel. The connection
(N/L/PE) of the supply voltage must be made according to VDE 0100 and VDE
0160.
Install a protective and lockout device for isolating and disconnecting the QLS
301. Before beginning the installation work, disconnect the electrical supply.
WARNING!
Failure to observe the safety instructions, e. g. touching electrically charged parts when the system is opened, or improper handling of the
QLS 301 may cause serious injury or
death.
If the values specified in the Technical
Data are exceeded, the device may overheat. It may damage the QLS 301 and thus impair the electric safety.
Page 6 of 48 2.1A-38006-E05 Form 403013
User Manual
Installation and Operation Instructions
R
Pump
SSV Metering Device
1014b00
Fig. 1 Single double and triple lubricant output, on back-mounted metering devices
0x-3x Output (single, double, etc.)
A Clamping ring of the check valve
Return to reservoir
Fig. 3 Check valve, push-in type
A Clamping ring (brass)
Installation Instructions
Use drilling template to mark and drill mounting holes of the
QLS 301. Drilling template and mounting bolts are included in the package.
Fig. 2 Closure plug, also provided in the accessory kits
4163a98
4180a02
Adjusting the output by cross-porting of outlets
Single Output
A single output is the lubricant quantity fed to the lube point by a piston per stroke and outlet port. It amounts to ap-
proximately 0.2 cm³, see outlet 6, fig. 1.
Double or Multiple Outputs
Outputs can be increased by simply plugging the unused outlet ports with closure plugs (fig. 2, provided in the accessory kit).
Lubricant from a plugged outlet is redirected to the next outlet on the same side of the SSV divider block in descending numerical order (see fig.1).
Example, see fig. 1:
By closing
- of outlet 4, outlet 2 receives the double quantity.
- of outlets 5 and 3, outlet 1 receives the triple amount of lubricant. The connecting conduit from outlet line 1 to outlet line 2 and to the return line (R) is closed by clamping rings (A) of the check valve.
Unused lubricant can be internally fed back to the reservoir, see paragraph ‘’direct internal feed back feature”.
6001a02
NOTE
Do not plug outlets number 1 or 2
(horizontally positioned outlets) on bottom-mounted lubricant metering devices SSV 8, 12 and 18.
Do not plug outlets number 1 or 2 on externally mounted metering devices.
Closure plugs
 Install a closure plug in each outlet port that is not required, see fig. 1 or 4.
Closure plugs are used in fig. 1 and 4 as follows:
- Fig. 1 outlets 3, 4 and 5
- Fig. 4 (page 8) outlets 1, 2, 4 and 5
Check valves
 For feed lines (diameter 6x1.5 mm, 1/4” I.D., provided in the accessory kits) use check valves with standard collar and knurled flange.
 Install a check valve in each outlet port that is required, see fig. 1 or 4. Observe paragraph “Direct (internal) feedback feature” (see page 8).
Check valves are used in fig. 1 and 4 as follows:
- Fig. 1
- Fig. 4 (page 8) outlets 1, 2 and 6 outlets 3 and 6
Form 403013 2.1A-38006-E05 Page 7 of 48
User Manual
Installation and Operation Instructions
Installation Instructions, continuation
Fig. 4 Internal feedback of supplied lubricant, only on backmounted SSV metering devices
0x-2x Output (single, double, etc.)
4188b99
A Clamping ring of the check valve
6001a02
NOTE
Maximum internal combination of outlets:
SSV 6 = 3
SSV 12 = 6
SSV 18 = 9
Further combinations are possible outside the metering device by means of a tee-piece only.
Direct (internal) feedback feature
All pumps with back-mounted SSV metering device have the capability to feed back unused lubricant internally from closed outlets directly to the reservoir (see pos.
R fig. 1, 4).
This procedure will start automatically, if outlet port 2 is plugged with a closure plug. All pumps have capability to feed back the lubricant directly to the reservoir from even
and odd outlets via the passage from outlet 1 to outlet 2.
When feeding back, always start with plugging the outlets
with the smallest outlet numbers, e.g. 2, 4, 6... or 1, 3,
5... plus outlet 2. In fig. 4 the outputs of outlets 1, 2 and 4
(3xR) are fed back to the reservoir.
The remaining outlets are to be used for the connection to the lube point or for increasing the lubricant output (double or triple), see fig.1.
CAUTION!
If outlet 2 is connected to a lube point, then never close outlet 1, see clamping ring (A) in outlet 2, fig. 1.
1013A94
6001a02
NOTE
To feed back unneeded lubricant quantities from bottom-mounted metering
devices to the reservoir, connect unneeded outlet via the feed line to plug
(pos. R, Fig 20, page 19) for external return line.
Page 8 of 48 2.1A-38006-E05 Form 403013
User Manual
Installation and Operation Instructions
Installation Instructions, continuation
Lubrication Points
Installing Quicklinc fittings into lube points
Remove lubrication fitting from lube point and install appropriate Quicklinc fitting into the bore of the lube point.
Installing Zerk-Lock onto Lube Fitting
4200a99
Fig. 5 Place the Zerk-Lock body over the filler fitting
4201a99
Fig. 6 Installation of Zerk-
Locks with staking tool
Fig. 7 Screwing Quicklinc fitting into the Zerk-Lock body
4202a99
The Zerk-Lock fitting consists of the Zerk-Lock body, insert and a Quicklinc fitting.
 Place the Zerk-Lock body over the lube fitting and place the staking tool firmly against the Zerk-Lock insert. (Staking tool is included in the accessory kits).
 Strike the tool sharply with a hammer until the Zerk-Lock insert partially crimps onto the grease fitting.
 Screw the Quicklinc fitting into the Zerk-Lock body and tighten until parts resist further tightening (about 1-1/2 turns).
NOTE
Quicklinc hex. is 12 mm. Zerk-Lock body hex is 1/2 ’’.
6001a02
 Move the Zerk-Lock and tube fitting from side to side on the lubrication fitting to insure the Zerk-Lock is firmly seated.
Form 403013 2.1A-38006-E05 Page 9 of 48
User Manual
Installation and Operation Instructions
Installation Instructions, continuation
Connection of Feed Lines
Fig. 8 Feed line installed in the Quicklinc fitting
4203a99
4157a98
Fig. 9 Feed line insert into the fitting up to the next white mark
Filling of reservoir
 Measure, cut and route the feed lines included in the accessory kit.
NOTE
6001a02
Avoid sharp bends of the plastic tubing and the moving parts of the machine that could damage the lubrication lines. Minimum bending radius is 50 mm (2 in).
 Secure the lubrication lines to the machine using nylon ties, clamps or straps provided in the accessory kit.
 If the feed lines are not primed, prime all lubrication feed lines before connecting them to the lube point (by triggering additional lubrications or via the filler fitting, pos. 4, fig.
17 and 18, page 17).
 Connect the feed lines directly to the check valves of the metering device and to the Quicklinc fittings of the lube point.
NOTE
6001a02
Push the ends of the feed line firmly into the Quicklinc fitting until it is fully seated in the body of the fitting. The primed feed lines are marked with white lines (fig. 9,
10) to facilitate installation.
 Cut the pressure plastic tube off at one of the white lines before it is mounted.
 Then insert the plastic pressure tube into the fitting up to the next white mark.
This will ensure a correct installation of the pressure plastic tube in the threaded tube fitting.
Fig. 10 Vent hole on reservoir
4204a99
 Fill the reservoir with suitable clean lubricant without air pockets.
WARNING!
Risk of bursting if the reservoir is
overfilled. When filling the reservoir by
means of pumps with a large delivery volume do not exceed the max. filling
mark.
1013A94
CAUTION!
Avoid inclusions of air in the lubricant below the follower plate. When filling the reservoir, the follower plate sealing lip overlaps the vent hole (see fig. 10) to ensure that all air pockets can be vented.
Page 10 of 48 2.1A-38006-E05 Form 403013
User Manual
Installation and Operation Instructions
Selection Guide VDC
Pump models
Examples of part numbers
Pump 301 for grease .......................................................... P301
P30100210113
P30162410153
P301 6 2 4 1 0 1 5 3
SSV Metering Device
External, SSV 6, SSV 8
1)
.....................................................
External, SSV 12, SSV 18
1)
................................................. .
SSV 6 (back) ........................................................................
0
1
3
SSV 8 (bottom) .....................................................................
SSV 12 .................................................................................
4
6
SSV 18 ................................................................................. 9
1)
Note: For external metering device application only use specific SSV metering devices... KNQLS.
SSV Metering Device Position, arrangement of the outlets
Without / external metering device ........................................ 0
Back (vertical order of lines) .................................................
Bottom
2)
1
(horizontal order of lines) ....................................... 2
2)
Note: Do not use QLS 301 with SSV metering device in bottom-mounting position for mobile applications. Do not install the pump in areas exposed to shock (see chapter “Safety Instruc-
Operating Voltage
12 VDC
24 VDC
3)
3)
...............................................................................
...............................................................................
2
4
3)
Note: Standard 12 and 24 VDC pump models for mobile applications can be supplied with 10-meter (30’) cable.
Reservoir
1 liter reservoir with low-level control ..................................... 1
Possible connections
- 1A = 1 connector (square plug), left, power supply ............
- 2A = 2 connectors (square plugs)
1 connector, left, power supply
1 connector, right, fault indication ..............................
- 1A = 1 connector (bayonet plug), left, power supply;
Fault indication ...........................................................
0
1
2
Type of Plug Connector
* Square-type plug, acc. to DIN 43650 type of construction A
(industrial application)
** Bayonet plug, DIN 72585-1, 4-core (mobile application, VDC)
1
5
Electrical Connectors
With socket without cable * ...................................................
With socket and 10 m cable * ...............................................
With socket and 10 m cable ADR * .......................................
With socket and 10 m cable **...............................................
With socket and 6 m cable, ADR ** ......................................
1
5
6
7
8
Control p. c. b.
Terminal board without time control.......................................
Control p.c.b. S3:
NC contact or NO contact (programmable), monitored:
- 1-5 cycles ...........................................................................
0
3
(Accessory kits see ”Technical Data”)
Form 403013 2.1A-38006-E05 Page 11 of 48
User Manual
Installation and Operation Instructions
Selection Guide VAC
Pump models
Examples of part numbers
Pump 301 for grease ........................................................... P301
P30100810113
P30162610113
P301 6 2 6 1 0 1 1 3
SSV Metering Device
External, SSV 6, SSV 8
1)
.....................................................
External, SSV 12, SSV 18
1)
................................................. .
SSV 6 (back) ........................................................................
0
1
3
SSV 8 (bottom) .....................................................................
SSV 12 .................................................................................
4
6
SSV 18 ................................................................................. 9
1)
Note: For external metering device application, use the specific metering device SSV ... KNQLS.
SSV Metering Device Position, arrangement of the outlets
External metering device ....................................................... 0
Back (vertical order of the lines) ...........................................
Bottom
2)
1
(horizontal order of the lines) ................................. 2
2)
Note: Do not use QLS 301 with SSV metering device in bottom-mounting position for mobile applications. Do not install pump in areas exposed to shock (see “Safety Instructions“).
Operating Voltage
120 VAC
3)
230 VAC
3)
(only with control p.c.b.) .....................................
(only with control p.c.b.) .....................................
6
8
3)
Note: Standard 120 and 230 VAC pump models for industry are supplied without electrical cable.
Reservoir
1 liter reservoir with low-level control .................................... 1
Possibilities of connection
- 1A = 1 connector (square plug), left, power supply
- 2A = 2 connectors (square plug)
1 connector, left, power supply
1 connector, right, fault indication ...............................
0
1
Type of Plug Connector
* Square-type plug, acc. to DIN 43650 type of construction A 1
Electrical Connectors
With socket, without cable * .................................................. 1
Control p.c.b.
Control p.c.b. S3:
NC or NO contact (programmable), monitored
- 1 cycle with SSV 12, SSV 18
- 1 to 3 cycles with SSV 6, SSV 8 ......................................... 3
(Accessory kits, see ”Technical Data”)
Page 12 of 48 2.1A-38006-E05 Form 403013
User Manual
Installation and Operation Instructions
Electrical Connecting Diagrams
Electrical connection
4273a00
CAUTION!
Before starting, make sure that the electrical supply is off. The device may not be connected or disconnected when the power is on. The protective conductor must always be connected. Take care that this line section is undamaged and conforms to standards and the contacts are safe.
 Verify the connection and the type of construction of your
QLS.
 Verify the configuration of your QLS 301:
- Type of voltage (VDC / VAC)
- Low-level control
- Connection (square-type/ bayonet plug)
- Metering device (internal/ external cycle switch)
 Connect the electrical wires according to the following electrical connecting diagrams (page 13 to 16).
Operation with bayonet plug
4273a00
ATTENTION!
Consider residual ripple of max.
±
5 % to connect pumps with direct current version
(in relation to the operating voltage acc. to
DIN 41755).
ATTENTION!
If the protective-conductor terminal is not connected or interrupted, dangerous touch voltages may occur on the equipment!
6001a02
NOTE
The protection IP6K9K is guaranteed when the socket (X1:, X2:, see fig. 6 ff) is tightened on housing cover with flat packing.
4273a00
Protective measures to be applied for the appropriate operation with bayonet plugs:
"Functional extra-low voltage with safe isolation" /
"Protective Extra-Low Voltage" (PELV)
Standards: EN60204 Part1:1992 / IEC 204-1:1992, modified
DIN VDE 0100 Part 410 / IEC 364-4-41:1992
(see pages 15 and 16)
Alternate current (AC)
with integrated control p.c.b. and attached metering device, alarm contact as normally open or normally closed contact (programmable):
4334a04
Fig. 11 Electrical connecting diagram for alternate current VAC with square-type plug, alarm contact as normally closed contact
Form 403013 2.1A-38006-E05 Page 13 of 48
User Manual
Installation and Operation Instructions
Electrical Connecting Diagrams, continuation
Alternate current (AC)
with integrated control p.c.b. and external metering device, alarm contact as normally open or normally closed contact (programmable):
Fig. 12 Electrical connecting diagram for alternate current VAC with square-type plug, alarm contact as normally closed contact
4335b02
Page 14 of 48 2.1A-38006-E05 Form 403013
User Manual
Installation and Operation Instructions
Electrical Connecting Diagrams, continuation
Direct current (DC), square-type plug
with integrated control p.c.b. and attached metering device, alarm contact as normally open or normally closed contact (programmable):
4337a02
Fig. 13 Electrical connecting diagram for direct current VDC with square-type plug, alarm contact as normally closed contact
Direct current (DC), square-type plug
with integrated control p.c.b. and external metering device, alarm contact as normally open or normally closed contact (programmable):
Fig. 14 Electrical connecting diagram for direct current VDC with square-type plug, alarm contact as normally closed contact
4336a02
Form 403013 2.1A-38006-E05 Page 15 of 48
User Manual
Installation and Operation Instructions
Electrical Connecting Diagrams, continuation
Direct Current (DC), bayonet plug
with integrated control p.c.b. and attached metering device, alarm contact as normally open or normally closed contact (programmable):
6298a04
Fig. 15 Electrical connecting diagram for direct current VDC with bayonet plug, alarm contact as normally open contact
Direct Current (DC), bayonet plug
with integrated control p.c.b. and external metering device, alarm contact as normally open or normally closed contact (programmable):
6300a04
Fig. 16 Electrical connecting diagram for direct current VDC with bayonet plug, alarm contact as normally open contact
Page 16 of 48 2.1A-38006-E05 Form 403013
User Manual
Installation and Operation Instructions
Description
4198a99
Fig. 17 QLS 301 with back position of the SSV metering device
1
2
3
4
Proximity switch
Control pin
SSV metering device
Nipple for external manual lubrication (1/8’’)
4199b02
Fig. 18 QLS 301 with bottom position of the SSV metering device
2
3
4
5
The QLS 301 is a complete compact lubrication system for a maximum of 18 lubrication points per operating
cycle.
The pump has three basic configurations:
- SSV metering device back-mounted (see Fig. 19)
- SSV metering device bottom-mounted (see Fig. 20)
- Pump without SSV metering device attached respectively with external metering device KNQLS (see fig. 21)
The pump with bottom-mounted SSV metering device has the capability of using steel tubing as lubrication lines if necessary.
Standard lubrication lines are high-pressure plastic hoses included in the pump installation kit for pumps with attached SSV metering device.
NOTE
The function of the pump is independent of the SSV metering device's mounting position.
6001a02
A signal from the pump timer starts the electric motor and the pumping element starts pumping the lubricant to the
SSV metering device.
When all lubrication points have received lubricant, an internal proximity switch (pos. 1, fig. 19, initiator) turns the motor off, completing one operating cycle.
NOTE
6001a02
If the QLS 301 is not provided with an attached SSV metering device but with an external SSV KNQLS (see Fig. 19, page
18), the proximity switch (of the SSV
KNQLS) switches the motor off.
If the operating cycle is not completed within the maxi-
mum permissible time, the flashing fault indication ‘’ Er ‘’ appears on the display of the membrane keypad (see
Fig. 24, page 20). The QLS 301 does not start automatically anymore.
Max. cycle time of the VDC-version ................ 25 minutes
Max. cycle time of the VAC-version ................ 15 minutes
Manifold
SSV metering device
Nipple for external manual lubrication (1/8’’)
Plug (1/8’’) for
P
R external pressure line external return line
Form 403013 2.1A-38006-E05 Page 17 of 48
User Manual
Installation and Operation Instructions
Description, continuation
An externally connected lubricant metering device SSV
KN QLS is equipped with the same proximity switch as the normal QLS 301.
The proximity switch is provided with a connecting cable of 2 m lengths and a connecting plug that must be connected to the socket of the QLS 301.
The socket is integrated in the housing instead of the proximity switch and is connected to the control p.c.b.
NOTE
The function of the QLS 301 is independent of the mounting position of the proximity switch.
6001a02
There are available the following externally connectable metering devices SSV KN QLS:
- SSV 6 KN QLS 619-28945-1
- SSV 8 KN QLS 619-28946-1
- SSV 10 KN QLS
- SSV 12 KN QLS
- SSV 14 KN QLS
- SSV 16 KN QLS
- SSV 18 KN QLS
619-28949-1
619-28950-1
619-28951-1
619-28952-1
619-28953-1
4199b02kopie
Fig. 19 QLS 301 without mounted SSV metering device with connection for external SSV metering device KN QLS
1
2
3
4
P
R
Connecting block
Closure plug
Nipple for emergency lubrication, R 1/8’
Connecting socket for SSV KN QLS
For feed line to external SSV KN QLS
Relief line connection
Page 18 of 48 2.1A-38006-E05 Form 403013
User Manual
Installation and Operation Instructions
Operation
Pump
4205a99
1
2
3
4
The QLS 301 operates according to operating cycles
(pause and lubricating times).
The pause time begins the cycle, and then the lubricating time occurs.
A division of the lube points (option) via sub-metering devices and one main metering device (SSV 6, SSV 8) is possible only up to max. 18 points per operating cycle.
In this case, set the number of cycles of the main metering device according to the number of lube points or the lubricant need to 1, 2, 3 or max. 5 cycles; see P3 on page
27.
Low-level control
Proximity switch
Keypad with display
Control unit
6 SSV 6, 8, 12, 18
Fig. 20 QLS 301, schematic
Pressure Relief Valve
Fig. 21 Pressure relief valve (cartridge) in housing
Pump Display Window
4304a00
The QLS 301 is protected with a pressure relief valve
(cartridge).
The pressure relief valve limits the pressure build-up in the QLS 301. It opens at an overpressure of 205 bar
(3000 psi).
If the pressure relief valve is actuated, this indicates that the system is malfunctioning. The lubricant flows back into the reservoir (hardly visible from outside).
When the monitoring time of 15 minutes (VAC version) respectively 25 minutes (VDC version) has elapsed, the pump switches off. On the display of the membrane keypad appears the flashing fault indication * Er *, see display mode below Setting and Operation of the QLS.
When switching the pump on, the segment in the display window is lit (pause time starts).
4208a04
Fig. 22 Green segment display, pause time
4209a99
Fig. 23 Green rotating display, lubricating time
Pump ”running” is indicated on the display by a rotating light movement of the green display (lubricating time).
If the voltage supply is interrupted during the lubricating time, the times already expired are stored. When the power supply is switched on again, the lubricating time continues operating from the point where it had been interrupted.
Form 403013 2.1A-38006-E05 Page 19 of 48
User Manual
Installation and Operation Instructions
Operation, continuation
Monitoring time/ malfunction
Fig. 24 Display of a fault indication
4210a99
4228a02
Fig. 25 Membrane keypad with fault indication and operator keys
1
2
3
Display window
Operator key
– operating mode: trigger additional lubrication
– programming mode: setting of times and metering
device cycles – terminate programming
Operator key
– display mode: acknowledge receipt of flashing
functional fault
- Operating mode: display of the set pause time and
residual pause time
– programming mode: change to the different
programming levels
If the proximity switch (pos. 1, fig. 17, page 17) does not give any feedback after the pause time has elapsed or after triggering additional operating cycles within 15 min-
utes (AC monitoring time) or 25 minutes (DC monitoring time), the pump switches off immediately. The flashing fault indication * Er * (Error) appears on the display.
IMPORTANT
If a malfunction is present, the pump does not switch on automatically any longer.
6001a02
 In this case, switch on the pump by pressing the button for additional operating cycle (pos. 2, fig. 31).
 The fault can be confirmed (see pos. 3, Fig. 25). However, this is not obligatory.
IMPORTANT
When confirming a fault indication, the flashing light changes into a permanent light or a signal horn can be temporarily switched off.
6001a02
When a malfunction is present, it can be cancelled only by initiating an additional operating cycle and if a proper operating cycle has been executed afterward.
If the fault is still present after an additional operating cycle has been initiated, the fault indication ”Er” is displayed again.
The monitoring time starts in parallel to the lubricating time. It is firmly adjusted and amounts to 15 respectively
25 minutes.
If the voltage supply is interrupted during the monitoring time (lubricating time), the monitoring time starts from the beginning after the pump is switched on again.
Low-level indication
Low-level indication
6262b04 6263b04
Fig. 26 Announcement of a low-level indication
6264b04
* L6 *, … * L1 * announces a low-level indication.
Right at the end appears the flashing display * LL * to indicate an unconfirmed low-level indication (see page 21,
Fig. 27).
Page 20 of 48 2.1A-38006-E05 Form 403013
User Manual
Installation and Operation Instructions
Operation, continuation
Low-level indication, continuation
Fig. 27 Display of a low-level indication
4211a99
1
2
3
The follower plate (3) (Fig. 28) of the reservoir moves the pin (pos. 2) with the solenoid (pos. 1) ahead of the sensor on the printed circuit board and initiates the low-level signal.
In this case, the pump is not switched off immediately.
The current operating cycle is completed. Upon expiration of the pause time, the pump cannot be started again automatically. The flashing display ”LL” appears, see Fig.
27.
 Fill reservoir.
As soon as the lubricant reservoir is filled up, the ”LL” display is cancelled. The operating cycle resumes.
Solenoid
Pin
Follower plate
Fig. 28 Parts of the low-level indication
Operator keys of the keypad
Operator keys of the keypad in the operating mode
4222a99
Fig. 29 Pushbutton for additional operating cycle
4229a99
Malfunction/low-level indication
If both indications (fig. 24 and 27) occur at the same time, then both displays * Er * and * LL* will flash.
Additional operating cycle
 is triggered via the button (Fig. 30). Press the button for
2 seconds.
 can be initiated at any time, provided that the power supply is applied.
If a fault signal (malfunction) is present, it will be cancelled as soon as the system is operating properly, again.
NOTE
6001a02
An existing fault indication (flashing display) can be confirmed before triggering additional operating cycles. However, this
is not obligatory (see Fig. 29).
Operator keys of the keypad in the programming mode
Fig. 30 Key for resetting the pause time
4222a99
Reset of the pause time
 Setting of the pause time by
- single key activation for one hour/minute
- permanent activation for quick run
Setting of the monitoring relay
Setting of the metering device circulations:
The monitoring relay signalizes a functional fault on an external lamp via the optional connection “X2“ (see connecting diagrams).
In case of the standard setting “normally open contact” the fault is indicated by a lamp with permanent light.
In case of the setting “normally closed contact” the fault is indicated by a lamp gone out.
Form 403013 2.1A-38006-E05 Page 21 of 48
User Manual
Installation and Operation Instructions
Operation, continuation
Operator keys of the keypad, continuation
Operator keys of the keypad in the programming mode, continuation
Continuation of fig. 30:
4222a99
Key for resetting the pause time
 For VDC version ……………………………. 1 to 5 cycles
For VAC version
- SSV 6 / SSV 8 ……………………………... 1 to 3 cycles
- SSV 12 / SSV 18 ….……………………….......... 1 cycle
Start settings
 Set: SP (Start with pause time)
SO (Start with lubricating time)
 Termination of the programming mode.
Operator keys of the keypad in the display mode
4214a99
Acknowledging receipt of a malfunction
 By pressing the key (fig. 31) the flashing *Er* changes into a permanent light.
Acknowledging receipt of the low-level indication
 By pressing the key (fig. 31) the flashing *LL* changes into a permanent light.
Fig. 31 Acknowledging receipt of a flashing fault indication
Operator keys of the keypad in the operating mode
Display of information regarding the set pause time
and residual pause time
 Press key >2 seconds.
4214a99
Fig. 32 Information regarding the set pause time and residual pause time
Operator keys of the keypad in the programming mode
4214a99
4222a99
Changing to the different programming levels
 Press keys to access the programming mode.
 Set parameters.
Â
 Setting: hours ….……………………………. P1 minutes P2 metering device cycles …………. P3 outlet potential-free contact ….... P4 external display for functional faults of
(NO) or (NC) contacts ................. P5 start with pause time or lubricating time …………………….. P6 termination of programming
4214a99
Fig. 33 Changing to the different programming levels
Monitoring relay
The monitoring relay signals a low-level indication or a malfunction (only in combination with optional connector
X2, see electrical connection diagrams).
In the first case the relay picks up (normally open contact).
In the second case the relay releases (normally closed contact, broken-wire interlock).
The signal is available via a potential-free contact.
The monitoring relay is released upon acknowledgement of the fault.
Page 22 of 48 2.1A-38006-E05 Form 403013
User Manual
Installation and Operation Instructions
Setting and Operation
6001a02
NOTE
The following technical description includes information on the centralized lubrication systems QLS 301 after upgrading them with the following control printed circuit boards:
- for 12/24 VDC … 236-14212-7
- for 120 VAC …… 236-10298-6
- for 230 VAC …… 236-10298-1
Factory Settings
Programming steps Factory setting Description
6 h
6 hours Pause time
4215a99
0 min
4217a99
4218a99
6252b04
6255b04
1 cycle no
– –
SP
Page
7
0 minutes Pause time
Operating cycles:
1 cycle (metering device cycle)
7
8
Signal output of the fault relay: no (normally open) Signalizing during the failure, 8
Differentiation fault indication (ER) / low-Level control (LL):
– – Permanent signal (no differentiation
between ER and LL)
Start phase:
SP Start with pause time
9
10
4299a00
Tab. 1 Programming steps P1 to P6
Operator Keys
Fig. 34
4222a99
Key for modifying the parameters in the programming step
Fig. 35
4214a99
Key for switching to the next programming step
Form 403013 2.1A-38006-E05 Page 23 of 48
User Manual
Installation and Operation Instructions
Setting and Operation, continuation
Three possible modes of operation and settings can be selected on the keypad.
Display mode
Programming mode (page 26 ff)
Operating mode (page 30 ff)
Display Mode
In the display mode the user receives information on functions and malfunctions of the QLS 301.
As soon as voltage is applied to the pump, the keypad is automatically in display mode. The segment is illuminated on the display.
Normally, the display is dark. Only the functions (segment, rotating segment display) or malfunctions (* Er *, * LL *) are displayed.
4206a04
Display press
A test display is made when the voltage is applied, all segments and decimal points are illuminated for 2 seconds.
NOTE
2 sec.
4207a99
6001a02
If *EP* is displayed after the display test, there is a malfunction of the operating keys (see page 20).
If *EE* is displayed, this indicates an electromagnetic interference. In this case, individually set times are set back to the factory setting and must be programmed newly
4227a99 6574b05
In the display mode during the pause time there appears the right segment display (On). It is to display the readiness for operation (voltage supply). As soon as another message is displayed, the segment turns off.
4208a04
The lubricating time is displayed as a rotating segment.
4209a99
Fig. 36 Display Mode (continuation next page)
Page 24 of 48 2.1A-38006-E05 Form 403013
User Manual
Installation and Operation Instructions
Setting and Operation, continuation
Display Mode, continuation
Display press
* Er * is shown to indicate a malfunction.
4210a99
6262b04 6263b04 6264b04
In the display mode, a low level is announced by an intermittent display of * L8 *, * L7 *, * L6 *, … * L1 *.
Finally appears the intermittent display * LL * for a lowlevel indication that had not been confirmed.
4210a99
Fig. 36 Display Mode
4214a99
< 2 sec.
To acknowledge malfunctions
The flashing display is changed into a continuous light by pressing the button (acknowledging). To acknowledge, press the button only briefly (< 2 sec.).
Messages which have been acknowledged but have not yet been remedied flash again after the pump is switched off and on again.
Form 403013 2.1A-38006-E05 Page 25 of 48
User Manual
Installation and Operation Instructions
Setting and Operation, continuation
Programming Mode
Display
4215a99
4222a99
press
4214a99
> 4 sec.
Setting Pause Time P1 and P2
 To access the programming mode, press both buttons at the same time > 4 seconds, so that “P1” appears in the display.
Programming options: Pause time:
Min. pause time DC 4 minutes
Min. pause time AC 20 minutes
Max. pause time DC/AC 59 hours 59 minutes
P1: Setting hours
When releasing the two buttons, the currently set value appears (here the factory-set value: 6 hours).
The field “hour“ is indicated by a decimal point on the right-
hand side.
4281a00
4220a99
4217a99
6270b04
4222a99
4214a99
4222a99
4220a99
Fig. 37 Programming Mode (continuation next page)
 Press button.
 Settings are made in one direction: 0, 1, 2, 3,....59 h
Button pressed once …............. increases by 1 hour
Button pressed continuously ........... quick sequence
P2: Setting minutes
 Press button, so that “P2“ appears in the display.
When releasing the button, the currently set value appears
(her the factory-set value: 0 minutes).
The field “minute“ is indicated by a decimal point on the left-
hand side.
 Press button.
 Settings are made in one direction: 0, 1, 2, 3, 4, .... 59 min
Button pressed once ….......... increases by 1 minute
Button pressed continuously ........... quick sequence
6001a02
NOTE
The minimum pause time is 4 respectively
20 minutes. For settings < 4 respectively
< 20 minutes (without input of hours) there automatically appears “. 04“ respectively
“. 20“ in the display provided the programming sequence has been carried out completely.
Page 26 of 48 2.1A-38006-E05 Form 403013
User Manual
Installation and Operation Instructions
Setting and Operation, continuation
Programming Mode, continuation
P3: Setting number of cycles
If lube points are divided via sub-metering devices (SSV 6) and a main metering device (SSV 6, SSV 8), never exceed a
maximum of 18 (24) lube points.
4218a99
4219a04
4219a99
4214a99
4222a99
IMPORTANT
Settings are only possible in connection with progressive metering device SSV 6 or SSV 8 KNQLS (connected as a main metering device) and a jumper attached at the p.c.b
 Press button, so that “P3“ appears in the display.
Max. cycle time VDC …………………………………… 1 to 5
Max. cycle time VAC …………………………………… 1 to 3
When releasing the button, the currently set value appears
(here the factory-set value: 1 cycle)
 Press button.
 Settings are made in one direction: 1, 2, 3, 4, 5
6001a02
NOTE
For the VDC version all metering device cycle numbers are possible with SSV 6,
SSV 8, SSV 12 and SSV 18.
For the VAC version depending on the type of SSV metering device the following cycle numbers are possible:
- with SSV 6 and SSV 8 .…………... 1 to 3
- with SSV 12 and SSV 18 ......……..….. 1
6252b04
6254b04
4214a99
4222a99
6253b04
Fig. 37 Programming Mode (continuation next page)
P4: Programming of the output signal on the monitoring relay for external fault indication (external fault contact)
 Press button, so that “P4“ appears in the display.
When releasing the button, the currently set value appears in the display (here the factory-set value “no“, normally open contact).
 Press button.
The external fault contact is modified by programming it as an “nc“ normally closed contact.
Form 403013 2.1A-38006-E05 Page 27 of 48
User Manual
Installation and Operation Instructions
Setting and Operation, continuation
Programming Mode, continuation
P5: Program external display for empty reservoir or fault indications
 Press button, so that “P5“ appears in the display.
4214a99
6255b04
6256b04 factory setting
When releasing the button, the display symbol “- -“ for permanent signal appears in the display.
NOTE
In this setting, a differentiation between low-level indication and fault indication is not possible.
6001a02
6257b04
4222a99
The output signal on the monitoring relay for the external fault indication “P4“ is set as a normally open contact (no) (see page 30).
 Press key to change the external signal into an intermittent signal.
Then low-level indications appear as intermittent signals and malfunctions as permanent signals (On).
On
Off intermittent signal
On
Off
Permanent signal
6258b04
4222a99
On
Off
On
Off intermittent signal Permanent signal
Fig. 37 Programming Mode (continuation next page)
The output signal on the monitoring relay for the external fault indication “P4“ is set as a normally closed contact (nc) (see page 30).
 Press key to change the external signal into an intermittent signal.
Then low-level indications appear as intermittent signals and malfunctions as permanent signals (Off).
Page 28 of 48 2.1A-38006-E05 Form 403013
User Manual
Installation and Operation Instructions
Setting and Operation, continuation
Programming Mode, continuation
4299a00
6259b04
4214a99
P6: Program start phase
 Press button, so that “P6“ appears in the display.
The pump is set as a standard with starting pause time SP
(Start Pause time).
 Press button.
The pump then starts after each switching on with the lubricating time SO (Start Operation). After the first lubricating time the preset pause time is valid.
6260b04
4222a99
4221a99
4214a99
4222a99
Completing the programming
 Press button. „ P -“ is displayed.
IMPORTANT
6001a02
In order to avoid a wrong program, make sure to always carry out the programming order completely, i. e. setting of P1
(hours), P2 (minutes), P3 (number of cycles), P4 (external contact), P5 (external display), P6 (start phase) and P- (Programming end).
Press this key (additional lubrication) to complete the programming and to save the entered parameters.
6001a02
NOTE
If the button “additional lubrication” is not pressed within 30 seconds, the changed parameters are not saved and the previous programming remains valid.
IMPORTANT
After completion of the programming, check the parameter settings in the operating mode once again (see pages 33 ff).
4208a99
Fig. 37 Programming Mode
Form 403013 2.1A-38006-E05 Page 29 of 48
User Manual
Installation and Operation Instructions
Setting and Operation, continuation
Operating Mode
Display press
IMPORTANT
The operating mode is accessible only during the pause time, and cannot be operated during the running time (pump lubricating time).
6001a02
Precondition: When the voltage supply is applied, the segment (On) is lit.
4208a04
Operating option: Initiating an additional operating cycle
 Press the button (> 2 sec.). The elapsed pause time is reset. The lubricating time starts. A rotating segment is visible on the display during the whole lubricating time.
> 2 sec.
4209a99 4222a99
Operating option: Calling up of set parameters and data determined
4208a04
4123a99
4216a99
4220a99
4214a99 after two sec. after two sec. after two sec.
 Press the button.
PP (set pause time)
NOTE
6001a02
The following display sequence is shown
once and is cancelled after 40 seconds.
The change of display occurs every two seconds. Example:
PP
rP
= 12h 30 min
= 5h 10 min
12 . (hours)
. 30 (minutes)
rP (remaining pause time)
4224a99
Fig. 38 Operating Mode (continuation next page)
Page 30 of 48 2.1A-38006-E05 Form 403013
User Manual
Installation and Operation Instructions
Setting and Operation, continuation
Operating Mode, continuation
after two sec.
5 . (hours)
4225a99 after two sec.
4226a99 after two sec.
4277a00 after two sec.
4281a00 after two sec.
4280a00 after two sec.
4278a00 after two sec.
4297a00 after two sec.
4226a99
Fig. 38 Operating Mode (continuation next page)
. 10 (minutes)
AC number of the automatically triggered operating cycles, countable up to 9999 cycles.
Then counting starts from the beginning again.
Example 0625 cycles:
06. Display for thousands and hundreds
06 as 600
.25 Display for tens and ones
UC Number of the manually triggered
(by the user) additional operating cycles, countable up to 9999 cycles.
Then counting starts from the beginning again.
Example 0110 cycles:
01. Display for thousands and hundreds
01 as 100
.10 Display for tens and ones
Form 403013 2.1A-38006-E05 Page 31 of 48
User Manual
Installation and Operation Instructions
Setting and Operation, continuation
Operating Mode, continuation
after two sec.
4218a99
4219a99
6252b04
6253b04
6255b04
6256b04
4299a00
6260b04 after two sec. after two sec. after two sec. after two sec. after two sec. after two sec. after two sec. after approx. 40 sec.
P3: Number of metering device cycles
Display of the metering device cycles
P4: Programming of the output signal
Display of the output signal “normally closed“ (nc) or “normally open“ (no)
P5: Differentiation between low-level indication and fault indication (only external indication)
Differentiation inactive
P6: Programming of the start phase
Display of the start phase with “start lubricating time“ (SO) or
“start pause time“ (SP)
Termination of the operating mode
4208a04
Fig. 38 Operating Mode
Page 32 of 48 2.1A-38006-E05 Form 403013
User Manual
Installation and Operation Instructions
Maintenance, Repair and Tests
Maintenance
Maintenance is essentially limited to refilling the reservoir with clean lubricant as necessary. However, check regularly whether the lubricant is being dispensed to all the lubrication points.
Also check the feed lines for damage and replace them, if necessary.
4273a00
CAUTION!
Turn off the voltage supply for pumps
120 VAC and 230 VAC before servicing the pump.
6001a02
NOTE
Whenever work is performed on the centralized lubrication system, special attention should be paid to cleanness.
Dirt will cause failure of the system.
IMPORTANT
To clean the system use petroleum spirit or petroleum. Do not use Tri, Per or similar solvents or polar or organic solvents such as alcohol, methanol, acetone, etc.
To fill reservoir
4231a99
Fig. 39 Filling nipple for filling reservoir
1 Filling nipple
3 Follower plate
Filling of the empty reservoir
Make sure that all air has been expelled from under the follower plate after refilling the empty reservoir.
The follower plate seal should contact the hole located on the top of the reservoir. Small amount of grease should be refilled to ensure expelling of air from under the follower plate.
Fill the reservoir up to the ”Max.” mark via the filling nipple, see fig. 38.
IMPORTANT
6001a02
The grease must be free from impurities and must not be liable to change its consistency over the course of time.
NOTE
If the reservoir has been completely emptied, the pump may require priming and a longer running time to reach the full lubricant output. Therefore, trigger additional operating cycles manually.
1013A94
CAUTION!
Risk of bursting if the reservoir is overfilled!
When filling the reservoir by means of pumps with a large delivery volume, do not exceed the max. filling mark.
Form 403013 2.1A-38006-E05 Page 33 of 48
User Manual
Installation and Operation Instructions
Maintenance, Repair and Tests, continuation
Repair
For repair work on the QLS 301 use only original Lincoln spare parts.
CAUTION!
Switch off the voltage supply for pumps 120 VAC and 230 VAC before servicing the pump.
4273a00
CAUTION!
By operating the drive motor without the reservoir installed, there is a risk of
injury by the eccentric gear.
Never use the lubrication system QLS
301 without installing the reservoir!
1013A94
Functional Test
 Press pushbutton > 2 sec. to trigger an operating cycle.
4222a99
Fig. 40 Pushbutton for additional operating cycle
Page 34 of 48 2.1A-38006-E05 Form 403013
User Manual
Installation and Operation Instructions
Pump of the QLS 301 system
Troubleshooting
The green rotating display indicates that the pump operates properly.
4209a99
Fig. 41 Green rotating segment, lubricating time
Fault: Pump motor doesn’t run
Cause: Remedy:
Power supply interrupted. Green decimal point On/h on display is not lit.
Warning!
Disconnect the power supply before starting any maintenance or repair works.
Power supply from printed circuit board to motor interrupted. Electric motor defective.
4273a00
 Check the voltage supply to the pump/fuses. If necessary, eliminate the fault or replace the fuses.
 Check the feedline from the fuses to the plug of the pump and then to the printed circuit board.
 Trigger an additional operating cycle. Check voltage supply from the printed circuit board to the motor.
 Replace printed circuit board.
 Replace housing with keypad.
Printed circuit board defective
Keypad or button is defective. ”EP” display at the keypad flashes.
Fault: Pump does not deliver lubricant
Cause: Remedy:
Reservoir is almost empty. ”LL” display at the keypad is flashing.
Pump lost prime and ”Er” display at the keypad is flashing.
 Fill up the reservoir with clean grease. Let the pump run
(initiate an additional operating cycle) until lubricant shows at all lube points.
NOte
Air pockets in lubricant.
Improper lubricant has been used.
Suction hole of pump element clogged.
Pump piston is worn.
Check valve in pump element defective or clogged.
6001a02
Dependent on the ambient temperature and/or sort of lubricant output. Therefore, trigger several additional operating cycles.
 Trigger an additional operating cycle. Lubricant must dispense without air bubbles.
 Change the lubricant.
 Remove pump element. Check suction hole for foreign particles. If there are any, remove them.
 Replace pump element.
 Replace pump element.
Form 403013 2.1A-38006-E05 Page 35 of 48
User Manual
Installation and Operation Instructions
Troubleshooting, continuation
Fault: Pump either does not switch off at all or only after the monitoring time of 15 min.
Cause: Remedy:
Proximity switch is not dampened, i.e. the control pin does not move within the switching range of the initiator, or the distance between the control pin and the initiator surface is more than 0.5 mm (0.02 in.).
 Trigger additional lubrication. Check whether the control pin moves centrically over the switching surface of the initiator. In case the adjustments do not correspond to the indications, the fixing position of the metering device has to be corrected.
 Check the distance.
- Between the control pin and the switching surface of the initiator (max. 0.5 mm; 0.02 in.)
In case the adjustments do not correspond to the indications, the fixing position of the proximity switch has to be corrected.
- Distances between the switching surface of the initiator and the upper edge of the fixing nut:
When the metering device is mounted at the back: 16+ /
–0.2 mm (0.62+/-0.08 in.)
When the metering device is mounted at the bottom:
12.7 +/-0.1 mm (0.5 +/-0.004 in.).
 Tightening torque of the nut: 1.5 NM (1.10 ft-lb.).
Fault: Pump runs continuously
Cause: Remedy:
Programming of pause time in step P1 was set to‘’00”.
Programming of further steps P2, P3, P4, P5, P6 and P- was not carried out.
Pump starts running immediately. The proximity switch switches off the cycle for two minutes. Then, pump runs continuously.
 Switch off pump (power supply) by removing left-hand side socket from plug.
 Press both buttons of keypad:
4222a99 4214a99
> 5 sec.
 Switch on pump (power supply) by replugging left-hand side socket.
 Release both pushbuttons after approx. 5 seconds.
 The factory-set pause time of 6 hours is automatically reset.
 Afterwards new setting of pause time is possible.
Fault: Fault indication * EE *
Cause: Remedy:
Electromagnetic interferences have modified the customer’s time setting. All values have been set back to the factory setting.
 Eliminate electromagnetic interferences.
 Repeat individual programming (see as of page 26).
Page 36 of 48 2.1A-38006-E05 Form 403013
User Manual
Installation and Operation Instructions
Troubleshooting, continuation
SSV metering device
Fault: Blockage in the downstream progressive system
Cause: Remedy:
Bearings, lines or metering device clogged Determine the cause of the blockage as described in the following example and eliminate it.
Mounting position of metering device: bottom
- In the case of metering devices SSV 8,12 and 18, the outlets 1 and/or 2 are closed.
 Let the pump run (refer to ”trigger additional operating cycles”).
Mounting position of metering device: back
- In the case of metering devices SSV 6, 12 and SSV
18, outlet 1 is closed and outlet 2 is connected to a lube point.
The fault can be identified as follows: a) Fault indication ”Er” flashing on the keypad display. b) The indicator pin at the metering device piston does
not move.
 Disconnect all feed lines (pos. D) of the metering device one after the other. If grease shows under pressure the blockage is located in the line of outlet 3 or in the connected bearing point.
 Pump through the blocked line or bearing point using a hand pump.
NOTE
6001a02
To check the individual outlets, leave all outlets disconnected for a while, since only one piston stroke is executed with each motor revolution. Several strokes are required for a full cycle of all metering devices.
 Check pressure relief valve (fig. 21, page 19). Replace it, if necessary.
Fig. 43 Example of a QLS 301
B pump
C
D
R
SSV 12 metering device feed lines return line
4232b02
Form 403013 2.1A-38006-E05 Page 37 of 48
User Manual
Installation and Operation Instructions
Troubleshooting, continuation
Fault: Blockage in the downstream progressive system, continuation
Cause: Remedy:
Metering device is blocked
Fault: Differing lubricant amounts at the lubrication point
 Replace the metering device or clean it as follows:
- Remove all threaded tube fittings.
- Unscrew the piston closure plugs.
- Remove the piston, if possible, with a soft mandrel
(smaller than ø 6 mm, 0.24 in).
IMPORTANT
6001a02
The pistons are individually fit in the bores of the metering device. After removing the pistons, mark them in order to reinstall them in the right direction and position. They may not be interchanged.
- Thoroughly clean the metering device body in a greasedissolving detergent and dry it with compressed air.
- Clean through the material passages (ø 1.5 mm, 0.59 in) at the thread ends of the piston bores using a pin.
- Clean the metering device once more and dry it thoroughly.
- Reassemble the metering device.
Cause: Remedy:
Lubricant metering not correct.
Setting of the pause time incorrect.
 Check the lubricant metering acc. to the lubrication chart.
 Check time setting.
Page 38 of 48 2.1A-38006-E05 Form 403013
User Manual
Installation and Operation Instructions
Technical Data
QLS 301, GENERAL
Operating temperature........ -25° C to 70° C (-10° F to 160° F)
Maximum operating pressure of pump model without metering device...... 205 bar (3,000 psig)
Number of outlets................................................... 6, 8, 12, 18
Output per outlet and cycle ............................. approx. 0.2 cm²
Reservoir capacity ...............................................................1 l
Lubricant .................................................. up to NLGI 2 grease
Weight (average) ......................................... 5.7 kg. (12.5 lbs.)
Protection................................. IP6K 9K acc. to DIN 40050 T9
Reverse polarity protection:
The operating voltage inlets are protected against reverse polarity.
ELECTRICAL DATA AC (ALTERNATE CURRENT)
Operating voltage.............................. 120 VAC/60 Hz +/- 10 %
Operating current .............................................................1,0 A
Operating voltage........................ 230 VAC; 50/60 Hz +/- 10 %
Operating current .............................................................0.5 A
ELECTRICAL DATA DC (DIRECT CURRENT)
Operating voltage...................................... 12 V, - 20%/+ 30 %
Operating current .............................................................2,0 A
Operating voltage...................................... 24 V, - 20%/+ 30 %
Operating current ............................................................1.0 A
Residual ripple in relation to the operating voltage ...................... ± 5% acc. to DIN41755
NOTE
The pump motor is suitable for intermittent operation only.
6001a02
In addition to the EMV directive, DC systems also comply with the following guidelines and standards:
- vehicle guideline 95/245/EC
- EMV regulation for on-road vehicles acc. EN 40839 parts 1, 3 and 4
TIME SETTING
Range of pause time ................................ increment 1 minute
- VDC ................................................... 4 minutes to 60 hours
- VAC ................................................. 20 minutes to 60 hours
Factory setting
Pause time .......................................................... 6 hours/cycle
Numbers of operating cycles
- VDC ................................................................. 1 to 5 cycles
- VAC SSV 6 / SSV 8 .......................................... 1 to 3 cycles
SSV 12 / SSV 18 ............................................... 1 cycle
Timer memory................................ indefinite over EEPROM
RELAY FOR MALFUNCTION AC (OPTION)
Potential-free outlet for malfunction/low-level option
Switching voltage.............................. max. 230 VAC/ 125 VDC
Switching current ....................................... max. (resistive) 2 A
Switching capacity ......................................max. 100 VA/80 W
RELAY FOR MALFUNCTION DC (OPTION)
Potential-free outlet for malfunction/low level option
Switching voltage....................................... max. 48 VAC/ VDC
Switching current ....................................... max. (resistive) 2 A
Switching capacity ......................................max. 100 VA/80 W
NOTE
All data depends on operating voltage, ambient temperature and max. operating pressure.
6001a02
LINES
Plastic tube (ø 6x1,5 mm;1/4 in.)
Min. bending radius . .............................................50 cm (2 in.)
Bursting pressure at 20° C ( 70°F) .............................approx. 210 bar (3050 psi )
Min. temperature ................................................-25° C (-10°F)
TIGHTENING TORQUES
Pump
Electric motor to housing..................................3 NM (2.5 lb.-ft)
Pump element in housing............................25 NM ( 19.0 lb.-ft)
Metering device, accessories
Closure plug (piston) in metering device .....18 NM (13.5 lb.-ft)
Closure plug (outlets) in metering device ....15 NM (11.0 lb.-ft)
Outlet fitting in metering device
- screw-type ..............................................17 NM (12.5 lb.-ft)
- push-in type..............................................12 NM (9.0 lb.-ft)
Compression nut onto outlet fitting, screw-type:
- plastic tube ...............................................10 NM (7.5 lb.-ft)
- steel tube..................................................11 NM (8.0 lb.-ft)
Indicator pin in metering device ...................18 NM (13.5 lb.-ft)
Mounting of the metering device....................10 NM (8.0 lb.-ft)
ACCESSORY KITS:
Inch-Size Kits:
SSV 6/8 part no. 550-36971-1
SSV 12 part no. 550-36971-2
SSV 18 part no. 550-36971-3
Metric Size Kits:
SSV 6/8 part no. 550-36970-1***
SSV 12 part no. 550-36970-2***
SSV 18 part no. 550-36970-3***
***
Lube fittings must be ordered separately
Form 403013 2.1A-38006-E05 Page 39 of 48
User Manual
Installation and Operation Instructions
Pump and SSV metering devices
Dimensions
Fig. 44 Dimension of QLS 301
4233a99
Fig. 45 Dimensions of back-mounted SSV metering device
Number of outlets Dimension A in mm
4234b04
Number of outlets Dimension A in mm
2012b95
Fig. 46 Dimension of bottom-mounted SSV metering device
Page 40 of 48 2.1A-38006-E05 Form 403013
User Manual
Installation and Operation Instructions
Service Parts
Version with bayonet plug
(VDC application only)
6302b04
Fig. 47 QLS 301 housing with bottom-mounted SSV metering device and bayonet plug (replacement of pos. 11, Fig. 49)
6303b04
Fig. 48 QLS 301 housing with back-mounted SSV metering device and bayonet plug (replacement of pos. 11, Fig. 50)
Parts list for bottom-mounted and back-mounted SSV lubricant metering devices with bayonet plug
Pos. Description Kit Single
Part
Qty Part No.
11 Housing cover for
VDC, plug 1A1
11.1 Socket with 6 m cable for bayonet plug or
Socket with 6 m cable for bayonet plug ADR
11.2 Bayonet plug x 1 664-34045-2 x 1 550-36980-1
Tab. 2 Parts list, QLS 301 with bayonet plug to table 3 and 4
(instead of square-type plug, pages 43 and 45)
Form 403013 2.1A-38006-E05 Page 41 of 48
User Manual
Installation and Operation Instructions
Service Parts, continuation
QLS 301 with bottom-mounted SSV metering device and square-type plug
Fig. 49 QLS 301 with bottom-mounted SSV metering device and square-type plug
Page 42 of 48 2.1A-38006-E05
4193b02
Form 403013
User Manual
Installation and Operation Instructions
Service Parts, continuation
Parts list for bottom-mounted SSV metering device and square-type plug
Pos. Description Kit Single part
Qty Part No. Pos. Description Kit Single part
Qty Part No.
1 Reservoir
2 Spring
DA 28x1,6x106 x 1 550-36979-2
13 p.c.b. for 1-5 cycles x 1 550-36980-1 x 1 550-36983-7
4 Intermediate x 1 550-36979-3
1 450-24749-1 p.c.b. for 1 cycle x 1 550-34199-1
6 Shaft
7 Pressure relief valve, cartridge
11.3 Flat packing
11.4 Appliance plug 2 , for remote control, VDC
Appliance plug 2 , for remote control, VAC
11.5 Appliance plug 1, for power supply, VDC
Appliance plug 1, for power supply, VAC
11.6 Socket 1 with 10 m cable, for power supply
11.7 Screw with washer assy. x 1 550-36979-4 x 1 550-36979-1 x 2 236-13294-3 p.c.b. for 3 cycles
ø 6 mm assy. x 1 control
15 Motor, 12 VDC pump element
10 Housing with low level control
With square-type plug (pos. 11, fig. 49, page 42):
Motor, 24 VDC
Motor, 120 VAC
11 Housing cover with low level control and VDC, plug 1A1 x 1 550-34179-3
Motor, 230 VAC
15.1 Motor connection
VDC
15.2 Motor connection
VAC or VDC, plug 2A1
Housing cover with low level control x and VAC, plug 1A1 x or VAC, plug 2A1
11.1 Socket 2 with 10 m cable, for remote control x
1 550-36984-2
1 550-36984-3
1 550-36984-4
16 Hydraulic lube fitting,
ST AR 1/8
17 Adapter M 22x1,5 (a) x G 1/8 in.(i)
18 O-Ring ø 5 x1,
5 mm
11.2 Socket, black
GMD-3011
20 Sealing ring aluminum
21 Manifold
22 Connecting
23 Hydraulic lube fitting,
ST AR 1/8
SSV 8 - K
SSV 12 - K
SSV 18 - K
25 Piston plug with sealing for control pin
Sealing kit for
QLS 301 x 1 550-34199-3 x 1 550-34199-2 x 1 550-34199-4 x x x x x x x x x x x
1 550-36979-9
1
1
1
1 550-36982-4
1 226-13777-2
1 550-36979-6
1 550-36979-7
1
1
1
550-36982-1
550-36982-2
550-36982-3
619-37586-1
619-37587-1
619-37588-1
Form 403013 2.1A-38006-E05 Page 43 of 48
User Manual
Installation and Operation Instructions
Service Parts, continuation
QLS 301 with back-mounted SSV metering device and square-type plug
Fig. 50 QLS 301 with back-mounted SSV metering device and square-type plug
Page 44 of 48 2.1A-38006-E05
4194b02
Form 403013
User Manual
Installation and Operation Instructions
Service Parts, continuation
Parts List for back-mounted SSV metering device and square-type plug
Pos. Description Kit Single
Part
Qty Part No. Pos. Description Kit Single
Part
Qty Part No.
1 Reservoir
2 Spring
DA 28x1,6x106 x 1 550-36979-2 x 1 550-36979-3
4 Intermediate bottom
5 Eccentric x 1 550-36979-4
6 Shaft x 1 550-36979-1
11.6 Socket 1 with 10 m cable, for power supply assy.
13 p.c.b. for 1-5 cycles valve, cartridge p.c.b. for 1 cycle assy. ø 6 mm pump element
10 Housing with lowlevel control
With square-type plug (pos. 11, fig. 50, page 44):
11 Housing cover with low level control and VDC, plug 1A1 or VDC, plug 2A1 x
Housing cover with low level control x and VAC, plug 1A1 x or VAC, plug 2A1 x
11.1 Socket 2 with 10 m cable, for remote control
1 550-34179-3
1 550-36984-2
1
1
550-36984-3
550-36984-4
GMD-3011 x 2 236-13294-3 p.c.b. for 3 cycles
14 Low-level 1 550-36979-9
15 Motor, 12 VDC x 1 550-36982-1
Motor, 24 VDC
Motor, 120 VAC
Motor, 230 VAC x x x
1
1
1
550-36982-2
550-36982-3
550-36982-4
VDC
VAC fitting, ST AR 1/8
17 Adapter M 22x1,5
(a) x G 1/8 in.(i)
18 O-Ring ø 5 x1,
5 mm
11.4 Appliance plug 2, for remote control,
VDC
Appliance plug 2, for remote control,
VAC
11.5 Appliance plug 1, for power supply,
VDC
Appliance plug 1, for power supply,
VAC device
SSV 6 - K
SSV 12 - K
SSV 18 - K fitting, ST AR 1/8
21 Piston plug with sealing for control pin
Sealing kit for
QLS 301 x x x
1 619-37589-1
1 619-37590-1
1 619-37591-1
Form 403013 2.1A-38006-E05 Page 45 of 48
User Manual
Installation and Operation Instructions
Option for metric fittings
(not included in the accessory kits)
SSV Connecting tube fitting, screw-type and push-in type
4239a99
1
2
3
Ferrule nut
Cutting ring
Valve body with sealing and ferrule
Fig. 51 Screw-type check valve
Connection of the pressure plastic tube or the high-pressure hose
1009a98
A
B
1a
2a
For high-pressure hose (ø 4.1 x 2.3 mm) use check valve
A, fig. 52, with reinforced collets 1a and smooth flange
(part no. 226-14091-4)
For pressure plastic tube (ø 6 x 1.5 mm) use check valve
B, fig. 52, with standard collets 2a and knurled flange (part no. 226-14091-2)
Check valve with reinforced collets
Check valve with standard collets
Smooth flange
Knurled flange
Fig. 52 Different types of check valves
NOTE
6001a02
On construction machines or agricultural machines use high-pressure hoses as feed lines. In such cases, the check valves of the sub-metering devices must have a reinforced collets and a smooth flange.
6001a02
IMPORTANT
Connect only high-pressure hoses
(ø 4.1 x 2.3 mm) with threaded sleeve and hose stud to the check valves with reinforced collets.
4156a98
Fig. 53 Check valve with reinforced collets and high-pressure hose
Page 46 of 48 2.1A-38006-E05 Form 403013
User Manual
Installation and Operation Instructions
Option for metric fittings
(not included in the accessory kits), continuation
Mounting of the threaded sleeves and hose studs onto the high-pressure hose
Screw threaded sleeve (1, fig. 54) counterclockwise onto the high-pressure hose (2) until the illustrated dimension of 11mm is reached. Then screw the hose stud (3) into the threaded sleeve (1).
IMPORTANT
Oil parts 1 and 3 well before screwing them together.
6001a02
1028a96
Fig. 54 Pre-assembly of the threaded sleeves and hose studs onto the main line
2
3
Main line
Hose stud
EC Declaration of Conformity as defined by Machinery Directive
98/37/EC, Annex II A
This is to declare that the design of the
QLS 301 lubrication system
in the version supplied by us, complies with the provisions of the directive 98/37/EC – including all modifications of this directive valid at the time of the declaration.
Applied harmonized standards in particular:
EN 12100-1
Safety of machinery part 1
EN 12100-2
Safety of machinery part 2
EN 809
Pumps and pump units for liquids
Safety requirements
Part 1: General requirements
EC Declaration of Conformity according
EMC Directive 2004/108/EC
We declare that the model of the
QLS 301 lubrication system
in the version supplied by us, complies with the provisions of above-mentioned directive.
Applied harmonized standards in particular:
EN 55011
Specifications, limits and methods of measurement of radio disturbance and medial (ISM) radio-frequency
equipment
EN 50081-1
Electromagnetic compatibility
Part 1: residential, commercial and light
industry
Generic immunity standard
Part 2: industrial environment
Walldorf, 10.08.2004, Dr. Ing. Z. Paluncic Walldorf, 10.08.2004, Dr. Ing. Z. Paluncic
U.S. Patent-No. 6,244,387, German Registration Design No. 29923765.6
Form 403013 2.1A-38006-E05 Page 47 of 48
User Manual
Installation and Operation Instructions
Lincoln Industrial
One Lincoln Way
St. Louis, MO 63120-1578
USA
Phone: (+1) 314 679 4200
Fax: (+1) 800 424 5359
Lincoln GmbH & Co. KG
Heinrich-Hertz Straße 2-8
69190 Walldorf, Germany
Tel: (+49) 6227 33-0
Fax: (+49) 6227 33-259
Lincoln Industrial Corporation
51 Changi Business Park Central 2
# 09-06 The Signature
Singapore 486066
Phone: (+65) 6588-0188
Fax: (+65) 6588-3438
Email: [email protected]
© Copyright 2005
Printed in Germany
Web site: www.lincolnindustrial.com
Page 48 of 48 2.1A-38006-E05 Form 403013
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 1 Title
- 2 Imprint
- 3 Inhaltsverzeichnis
- 4 Introduction
- 4 Explanation of Symbols Used
- 4 User's Responsibility
- 4 Environmental Protection
- 4 Service
- 4 Glossary
- 5 Safety Instructions
- 5 Appropriate Use
- 5 Misuse
- 5 General Safety Instructions
- 5 Regulations for Prevention of Accidents
- 5 Operation, Repair and Mai
- 5 Repair
- 6 Operation/Maintenance
- 6 Operation with bayonet plug
- 6 Disposal
- 6 Exclusion of Liability
- 6 Installation
- 7 Installation Instructions
- 7 Pump
- 7 SSV Metering Device
- 7 Adjusting the output by cross-porting of outlets
- 7 Single Output
- 7 Double or Multiple Outputs
- 7 Closure plugs
- 7 Check valves
- 8 Direct (internal) feedback feature
- 9 Lubrication Points
- 9 Installing Quicklinc fittings into lube points
- 9 Installing Zerk-Lock onto Lube Fitting
- 10 Connection of Feed Lines
- 10 Filling of reservoir
- 11 Selection Guide
- 11 VDC
- 12 VAC
- 13 Electrical Connecting Diagrams
- 13 Electrical connection
- 13 Alternate current (AC)
- 15 Direct current (DC), square-type plug
- 16 Direct Current (DC), bayonet plug
- 17 Description
- 17 QLS 301 with back position of the SSV metering device
- 17 QLS 301 with bottom position of the SSV metering d
- 18 QLS 301 without mounted SSV metering device with connection for external SSV metering device KN QLS
- 19 Operation
- 19 Pump
- 19 Pressure Relief Valve
- 19 Pump Display Window
- 20 Monitoring time/ malfunction
- 20 Low-level indication
- 21 Malfunction/low-level indication
- 21 Operator keys of the keypad
- 21 Additional operating cycle
- 21 Reset of the pause time
- 21 Setting of the monitoring rel
- 22 Acknowledging receipt of a malfunction
- 22 Acknowledging receipt of the low-level indication
- 22 Display of information regarding the set pause time and residual pause time
- 22 Changing to the different programming levels
- 22 Monitoring relay
- 23 Setting and Operation
- 23 Factory Settings
- 23 Operator Keys
- 24 Display Mode
- 26 Programming Mode
- 30 Operating Mode
- 33 Maintenance, Repair and Tests
- 33 Maintenance
- 33 To fill reservoir
- 33 Filling of the empty reservoir
- 34 Repair
- 34 Functional Test
- 35 Troubleshooting
- 35 Pump of the QLS 301 system
- 35 Pump motor doesn’t run
- 35 Pump does not deliver lubricant
- 36 Pump either does not switch off at all or only after the monitoring time of 15 min.
- 36 Pump runs continuously
- 36 Fault indication * EE *
- 37 SSV metering device
- 37 Blockage in the downstream progressive system
- 38 Differing lubricant amounts at the lubrication point
- 39 Technical Data
- 39 QLS 301, GENERAL
- 39 ELECTRICAL DATA AC (ALTERNATE CURRENT)
- 39 ELECTRICAL DATA DC (DIRECT CURRENT)
- 39 TIME SETTING
- 39 RELAY FOR MALFUNCTION AC (OPTION)
- 39 RELAY FOR MALFUNCTION DC (OPTION)
- 39 LINES
- 39 TIGHTENING TORQUES
- 39 ACCESSORY KITS
- 40 Dimensions
- 40 Pump and SSV metering devices
- 41 Service Parts
- 41 Version with bayonet plug
- 41 Parts list for bottom-mounted and back-mounted SSV lubricant metering devices with bayonet plug
- 42 QLS 301 with bottom-mounted SSV metering device and square-type plug
- 43 Parts list for bottom-mounted SSV metering device and square-type plug
- 44 QLS 301 with back-mounted SSV metering device and square-type plug
- 45 Parts List for back-mounted SSV metering device and square-type plug
- 46 Option for metric fittings
- 46 SSV Connecting tube fitting, screw-type and push-in type
- 46 Connection of the pressure plastic tube or the high-pressure hose
- 47 Mounting of the threaded sleeves and hose studs onto the high-pressure hose
- 47 EC Declaration of conformity
- 48 Lincoln worldwide