Relion® product family
Grid Automation
Recloser Protection and Control RER615
Modbus Point List Manual
Document ID: 1MRS757822
Issued: 2015-03-06
Revision: B
Product version: 1.1
© Copyright 2015 ABB. All rights reserved
Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third
party, nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license
and may be used, copied, or disclosed only in accordance with the terms of such
license.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
http://www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.
This product has been designed to be connected and communicate data and
information via a network interface which should be connected to a secure
network. It is the sole responsibility of the person or entity responsible for network
administration to ensure a secure connection to the network and to take the
necessary measures (such as, but not limited to, installation of firewalls, application
of authentication measures, encryption of data, installation of anti virus programs,
etc.) to protect the product and the network, its system and interface included,
against any kind of security breaches, unauthorized access, interference, intrusion,
leakage and/or theft of data or information. ABB is not liable for any such damages
and/or losses.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standards EN 50263 and EN 60255-26 for the EMC
directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The product is designed in accordance with the international
standards of the IEC 60255 series.
Table of contents
Table of contents
Section 1
Introduction.......................................................................7
This manual........................................................................................7
Intended audience..............................................................................7
Product documentation.......................................................................8
Product documentation set............................................................8
Document revision history.............................................................8
Related documentation..................................................................9
Symbols and conventions...................................................................9
Symbols.........................................................................................9
Document conventions..................................................................9
Functions, codes and symbols....................................................10
Section 2
Modbus data mappings..................................................15
Overview...........................................................................................15
Supported functions in RER615.......................................................15
Indications........................................................................................17
Common data 1...........................................................................18
LD0.FPHLPTOC1 Three-phase non-directional overcurrent
protection, low stage (1)..............................................................18
LD0.PHHPTOC1 Phase overcurrent protection, high stage
(1)................................................................................................19
LD0.PHIPTOC1 Phase overcurrent protection,
instantaneous stage (1)...............................................................19
LD0.FDPHLPDOC1 Three-phase directional overcurrent
protection, low stage (1)..............................................................20
LD0.FPDHLPDOC2 Three-phase directional overcurrent
protection, low stage (2)..............................................................20
LD0.DPHHPDOC1 Three-phase directional overcurrent
protection, high stage (1).............................................................21
LD0.FEFLPTOC1 Non-directional earth-fault protection,
low stage (1)................................................................................21
LD0.EFHPTOC1 Non-directional earth-fault protection, high
stage (1)......................................................................................21
LD0.EFIPTOC1 Non-directional earth-fault protection,
instantaneous stage (1)...............................................................22
LD0.FDEFLPDEF1 Directional earth-fault protection, low
stage (1)......................................................................................22
LD0.FDEFLPDEF2 Directional earth-fault protection, low
stage (2)......................................................................................22
LD0.DEFHPDEF1 Directional earth-fault protection, high
stage (1)......................................................................................23
Recloser Protection and Control RER615
Point List Manual
1
Table of contents
LD0.INTRPTEF1 Intermittent earth fault protection (1)...............23
LD0.EFPADM1 Admittance-based earth-fault protection
(1)................................................................................................23
LD0.EFPADM2 Admittance-based earth-fault protection
(2)................................................................................................23
LD0.EFPADM3 Admittance-based earth-fault protection
(3)................................................................................................24
LD0.WPWDE1 Wattmetric-based earth-fault protection (1)........24
LD0.WPWDE2 Wattmetric-based earth-fault protection (2)........24
LD0.WPWDE3 Wattmetric-based earth-fault protection (3)........24
LD0.HAEFPTOC1 Harmonics-based earth-fault protection
(1)................................................................................................25
LD0.NSPTOC1 Negative-sequence overcurrent protection
(1)................................................................................................25
LD0.NSPTOC2 Negative-sequence overcurrent protection
(2)................................................................................................25
LD0.PDNSPTOC1 Phase discontinuity protection (1).................26
LD0.ROVPTOV1 Residual overvoltage protection (1).................26
LD0.ROVPTOV2 Residual overvoltage protection (2).................26
LD0.PHPTUV1 Phase undervoltage protection (1).....................26
LD0.PHPTUV2 Phase undervoltage protection (2).....................27
LD0.PHPTUV3 Phase undervoltage protection (3).....................27
LD0.PHPTOV1 Phase overvoltage protection (1).......................28
LD0.PHPTOV2 Phase overvoltage protection (2).......................28
LD0.PHPTOV3 Phase overvoltage protection (3).......................28
LD0.PSPTUV1 Positive-sequence undervoltage protection
(1)................................................................................................29
LD0.NSPTOV1 Negative-sequence overvoltage protection
(1)................................................................................................29
LD0.FRPFRQ1 Frequency protection (1)....................................30
LD0.FRPFRQ2 Frequency protection (2)....................................30
LD0.T1PTTR1 Thermal overload protection (1)..........................31
CTRL.CCBRBRF1 Circuit breaker (1) failure protection.............31
LD0.INRPHAR1 Three-phase inrush detection (1)......................31
LD0.TRPPTRC1 Protection trip conditioning (1).........................32
LD0.TRPPTRC2 Protection trip conditioning (2).........................32
LD0.MAPGAPC1 Multipurpose analog protection function
(1)................................................................................................32
LD0.MAPGAPC2 Multipurpose analog protection function
(2)................................................................................................33
LD0.MAPGAPC3 Multipurpose analog protection function
(3)................................................................................................33
LD0.MAPGAPC4 Multipurpose analog protection function
(4)................................................................................................33
2
Recloser Protection and Control RER615
Point List Manual
Table of contents
LD0.MAPGAPC5 Multipurpose analog protection function
(5)................................................................................................34
LD0.MAPGAPC6 Multipurpose analog protection function
(6)................................................................................................34
LD0.CMHAI1 Current total demand distortion (1)........................34
LD0.VMHAI1 Voltage total demand distortion (1)........................34
LD0.PHQVVR1 PQ - Voltage variation signals (1)......................35
LD0.VSQVUB1 Voltage unbalance (1)........................................35
CTRL.CBXCBR1 Circuit breaker (1) blocking signals.................35
CTRL.DCSXSWI1 Disconnector position indication (1) .............36
CTRL.DCSXSWI2 Disconnector position indication (2)..............36
CTRL.ESSXSWI1 Earthing switch indication (1) ........................36
CTRL.ESSXSWI2 Earthing switch indication (2) ........................36
LD0.DARREC1 AR state (1)........................................................37
LD0.DARREC1 Autorecloser (1).................................................37
LD0.SECRSYN1 Synchrocheck (1).............................................38
LD0.SSCBR1 Circuit breaker (1) condition monitoring................38
LD0.TCSSCBR1 Trip circuit supervision (1)................................39
LD0.TCSSCBR2 Trip circuit supervision (2)................................39
LD0.SEQRFUF1 Fuse failure protection (1)................................39
LD0.MDSOPT1 Generic operation time supervision (1)..............40
LD0.PHSVPR1 Voltage presence supervision (1).......................40
LD0.CMMXU1 Phase current limit supervision (1)......................41
LD0.RESCMMXU1 Residual current limit supervision (1)...........41
LD0.VMMXU1 Phase voltage limit supervision (1)......................41
LD0.VMMXU2 Phase voltage limit supervision (2)......................42
LD0.MVGAPC1 Multipurpose binary inputs (1)...........................42
LD0.MVGAPC2 Multipurpose binary inputs (2)...........................43
LD0.SPCGGIO1 Multipurpose binary output states (1)...............43
LD0.SPCGGIO2 Multipurpose binary output states (2)...............44
LD0.SPCRGGIO1 Multipurpose binary output states (1)............45
LD0.SPCLGGIO1 Multipurpose binary output states (1).............46
LD0.GSEGGIO1 Goose supervision (1)......................................47
LD0.LEDPTRC1 Global conditioning (1).....................................47
LD0.LEDGGIO1 Indication LED states OFF/ColorX...................47
LD0.LEDGGIO1 Indication LED states Color1/Color2................48
CTRL.CBCSWI1 Circuit breaker (1) mom. position.....................50
CTRL.CBCSWI1 Circuit breaker (1) mom+mcd position.............50
CTRL.CBCILO1 Circuit breaker (1) enable signals.....................50
LD0.XGGIO130 Physical I/O states (BIO card X130) ................50
LD0.XGGIO120 Physical I/O states (AIM card X120).................51
LD0.XGGIO110 Physical I/O states (BIO card X110).................51
LD0.XGGIO100 Physical I/O states (PSM card X100)................52
LD0.XAGGIO130 Physical I/O states (AIM card XA130)............53
Recloser Protection and Control RER615
Point List Manual
3
Table of contents
Registers..........................................................................................53
User definable registers [Alt.1], visible on 3x and 4x...................53
User definable bits [Alt.2], visible on 0x,1x,3x and 4x.................54
SSR1 System status register (1) device health...........................54
SSR2 System status register (2) IED mode and state................55
SSR3 System status register (3) data available 1 (clientdependent)..................................................................................55
SSR4 System status register (4) data available 2 (clientdependent - user-definable)........................................................56
SSR5 System status register (5) device alive register................56
SSR6 System status register (6) control command status
(client-dependent)........................................................................57
LD0.T1PTTR1 Thermal protection values (1)..............................57
LD0.CMHAI1 Current total demand distortion (1)........................58
LD0.VMHAI1 Voltage total demand distortion (1)........................58
LD0.PHQVVR1 Short duration voltage variations (1)..................59
LD0.DARREC1 Autorecloser values (1)......................................59
LD0.DARREC1 Autorecloser counters (1)..................................60
LD0.SECRSYN1 Synchrocheck (1).............................................60
LD0.SSCBR1 Circuit-breaker condition monitoring values
(1)................................................................................................60
LD0.MDSOPT1 Generic operation time supervision ..................61
LD0.CMMXU1 Phase current measurements (1) .......................61
LD0.CMSQI1 Sequence of current measurements (1) ...............61
LD0.RESCMMXU1 Residual current measurement (1) .............61
LD0.VMMXU1 Voltage measurements (1) .................................62
LD0.VMMXU2 Voltage measurements (2)..................................62
LD0.VMSQI1 Sequence of voltage measurements (1) ..............63
LD0.VSMSQI2 Sequence of voltage measurements (2).............63
LD0.PEMMXU1 Three-phase power measurements (1).............63
LD0.FMMXU1 Frequency measurement (1)...............................64
Indication bits mirrored in registers..............................................64
LD0.VMSTA1 Voltage demand values (1) ..................................64
LD0.VMSTA2 Voltage demand values (2)...................................65
LD0.PEMSTA1 Power measurement demand values (1) ..........65
LD0.RESCMSTA1 Residual current demand value (1) ..............66
LD0.CMSTA1 Phase current demand values (1) .......................66
CTRL.CBCSWI1 Circuit breaker operation counter (1) ..............67
LD0.PEMMTR1 Three-phase energy measurements (1)............68
System diagnostic values............................................................68
Control structure 1.......................................................................69
Control structure 2.......................................................................69
Control structure 3.......................................................................69
Control structure 4.......................................................................69
4
Recloser Protection and Control RER615
Point List Manual
Table of contents
Control structure 5.......................................................................70
Control structure 6.......................................................................70
Control structure 7.......................................................................70
Control structure 8.......................................................................70
Device ID string...........................................................................71
IED Real-time clock (in local time mode) - read and write
(synchronize)...............................................................................71
IED real-time clock (in UTC time mode) - read and write
(synchronize)...............................................................................71
Time and reason for latest IED reset...........................................72
Active parameter setting group - read and write..........................72
Event record structure.................................................................72
Fault record structure header......................................................76
Fault record data.........................................................................77
Controls............................................................................................78
Reset, acknowledge and trigger points (A)..................................78
LD0.LPHD1 IED warm reset (1)..................................................79
CTRL.CBCSWI1 Circuit breaker (1) control................................79
LD0.SRGAPC1 Reset SRGAPC1 generic flip-flops....................80
LD0.SRGAPC2 Reset SRGAPC2 generic flip-flops....................80
LD0.SPCGGIO1 Multipurpose binary outputs (1) .......................80
LD0.SPCGGIO2 Multipurpose binary outputs (2) .......................81
LD0.SPCRGGIO1 Multipurpose binary outputs (1).....................82
Section 3
Recloser Protection and Control RER615
Point List Manual
Glossary.........................................................................83
5
6
Section 1
Introduction
1MRS757822 B
Section 1
Introduction
1.1
This manual
The point list manual describes the outlook and properties of the data points
specific to the IED. The manual should be used in conjunction with the
corresponding communication protocol manual.
1.2
Intended audience
This manual addresses the communication system engineer or system integrator
responsible for pre-engineering and engineering for communication setup in a
substation from an IED perspective.
The system engineer or system integrator must have a basic knowledge of
communication in protection and control systems and thorough knowledge of the
specific communication protocol.
Recloser Protection and Control RER615
Point List Manual
7
Section 1
Introduction
Decommissioning,
deinstallation & disposal
Maintenance
Operation
Product documentation set
Commissioning
1.3.1
Engineering
Product documentation
Planning &
purchase
1.3
Installation
1MRS757822 B
Quick start guide
Quick installation guide
Brochure
Product guide
Operation manual
Installation manual
Connection diagram
Engineering manual
Technical manual
Application Engineering Guide
Communication protocol manual
IEC 61850 Engineering guide
Point list manual
GUID-7414985D-2433-46E4-B77B-CCE64F6FC8D0 V1 EN
Figure 1:
The intended use of documents during the product life cycle
Product series- and product-specific manuals can be downloaded
from the ABB Website http://www.abb.com/relion.
1.3.2
Document revision history
Document revision/date
Product version
History
A/2013-09-17
1.0
First release
B/2015-03-06
1.1
Content updated to correspond to the
product version
Download the latest documents from the ABB Website
http://www.abb.com/substationautomation.
8
Recloser Protection and Control RER615
Point List Manual
Section 1
Introduction
1MRS757822 B
1.3.3
Related documentation
Name of the document
Modbus Communication Protocol Manual
1.4
Symbols and conventions
1.4.1
Symbols
Document ID
1MRS757819
The caution icon indicates important information or warning related
to the concept discussed in the text. It might indicate the presence
of a hazard which could result in corruption of software or damage
to equipment or property.
The information icon alerts the reader of important facts and
conditions.
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
Although warning hazards are related to personal injury, it is necessary to
understand that under certain operational conditions, operation of damaged
equipment may result in degraded process performance leading to personal injury
or death. Therefore, comply fully with all warning and caution notices.
1.4.2
Document conventions
A particular convention may not be used in this manual.
•
•
•
•
•
•
•
Recloser Protection and Control RER615
Point List Manual
Abbreviations and acronyms are spelled out in the glossary. The glossary also
contains definitions of important terms.
The example figures illustrate the IEC display variant.
Menu paths are presented in bold.
Select Main menu/Settings.
LHMI messages are shown in Courier font.
To save the changes in non-volatile memory, select Yes and press
.
Parameter names are shown in italics.
The function can be enabled and disabled with the Operation setting.
Parameter values are indicated with quotation marks.
The corresponding parameter values are "On" and "Off".
IED input/output messages and monitored data names are shown in Courier font.
When the function starts, the START output is set to TRUE.
9
Section 1
Introduction
1.4.3
1MRS757822 B
Functions, codes and symbols
All available functions are listed in the table. All of them may not be applicable to
all products.
Table 1:
Functions included in the relay
Function
IEC 61850
IEC 60617
IEC-ANSI
Protection
Three-phase non-directional
overcurrent protection, low stage,
instance 1
FPHLPTOC1
3I> (1)
51P-1 (1)
Three-phase non-directional
overcurrent protection, high stage,
instance 1
PHHPTOC1
3I>> (1)
51P-2 (1)
Three-phase non-directional
overcurrent protection,
instantaneous stage, instance 1
PHIPTOC1
3I>>> (1)
50P/51P (1)
Three-phase directional overcurrent
protection, low stage, instance 1
FDPHLPDOC1
3I> -> (1)
67-1 (1)
Three-phase directional overcurrent
protection, low stage, instance 2
FDPHLPDOC2
3I> -> (2)
67-1 (2)
Three-phase directional overcurrent
protection, high stage, instance 1
DPHHPDOC1
3I>> -> (1)
67-2 (1)
Non-directional earth-fault
protection, low stage, instance 1
FEFLPTOC1
Io> (1)
51N-1 (1)
Non-directional earth-fault
protection, high stage, instance 1
EFHPTOC1
Io>> (1)
51N-2 (1)
Non-directional earth-fault
protection, instantaneous stage,
instance 1
EFIPTOC1
Io>>> (1)
50N/51N (1)
Directional earth-fault protection, low
stage, instance 1
FDEFLPDEF1
Io> -> (1)
67N-1 (1)
Directional earth-fault protection, low
stage, instance 2
FDEFLPDEF2
Io> -> (2)
67N-1 (2)
Directional earth-fault protection,
high stage, instance 1
DEFHPDEF1
Io>> -> (1)
67N-2 (1)
Transient/intermittent earth-fault
protection, instance 1
INTRPTEF1
Io> -> IEF (1)
67NIEF (1)
Admittance based earth-fault
protection, instance 1
EFPADM1
Yo> -> (1)
21YN (1)
Admittance based earth-fault
protection, instance 2
EFPADM2
Yo> -> (2)
21YN (2)
Admittance based earth-fault
protection, instance 3
EFPADM3
Yo> -> (3)
21YN (3)
Wattmetric based earth-fault
protection, instance 1
WPWDE1
Po> -> (1)
32N (1)
Wattmetric based earth-fault
protection, instance 2
WPWDE2
Po> -> (2)
32N (2)
Wattmetric based earth-fault
protection, instance 3
WPWDE3
Po> -> (3)
32N (3)
Table continues on next page
10
Recloser Protection and Control RER615
Point List Manual
Section 1
Introduction
1MRS757822 B
Function
IEC 61850
IEC 60617
IEC-ANSI
Harmonics based earth-fault
protection, instance 1
HAEFPTOC1
Io>HA (1)
51NHA (1)
Negative-sequence overcurrent
protection, instance 1
NSPTOC1
I2> (1)
46 (1)
Negative-sequence overcurrent
protection, instance 2
NSPTOC2
I2> (2)
46 (2)
Phase discontinuity protection,
instance 1
PDNSPTOC1
I2/I1> (1)
46PD (1)
Residual overvoltage protection,
instance 1
ROVPTOV1
Uo> (1)
59G (1)
Residual overvoltage protection,
instance 2
ROVPTOV2
Uo> (2)
59G (2)
Three-phase undervoltage
protection, instance 1
PHPTUV1
3U< (1)
27 (1)
Three-phase undervoltage
protection, instance 2
PHPTUV2
3U< (2)
27 (2)
Three-phase undervoltage
protection, instance 3
PHPTUV3
3U< (3)
27 (3)
Three-phase overvoltage protection,
instance 1
PHPTOV1
3U> (1)
59 (1)
Three-phase overvoltage protection,
instance 2
PHPTOV2
3U> (2)
59 (2)
Three-phase overvoltage protection,
instance 3
PHPTOV3
3U> (3)
59 (3)
Positive-sequence undervoltage
protection, instance 1
PSPTUV1
U1< (1)
47U+ (1)
Negative-sequence overvoltage
protection, instance 1
NSPTOV1
U2> (1)
47O- (1)
Frequency protection, instance 1
FRPFRQ1
f>/f<,df/dt (1)
81 (1)
Frequency protection, instance 2
FRPFRQ2
f>/f<,df/dt (2)
81 (2)
Three-phase thermal protection for
feeders, cables and distribution
transformers, instance 1
T1PTTR1
3Ith>F (1)
49F (1)
Circuit breaker failure protection,
instance 1
CCBRBRF1
3I>/Io>BF (1)
51BF/51NBF (1)
Three-phase inrush detector,
instance 1
INRPHAR1
3I2f> (1)
68 (1)
Master trip, instance 1
TRPPTRC1
Master Trip (1)
94/86 (1)
Master trip, instance 2
TRPPTRC2
Master Trip (2)
94/86 (2)
Multi-purpose protection, instance 1
MAPGAPC1
MAP (1)
MAP (1)
Multi-purpose protection, instance 2
MAPGAPC2
MAP (2)
MAP (2)
Multi-purpose protection, instance 3
MAPGAPC3
MAP (3)
MAP (3)
Multi-purpose protection, instance 4
MAPGAPC4
MAP (4)
MAP (4)
Multi-purpose protection, instance 5
MAPGAPC5
MAP (5)
MAP (5)
Multi-purpose protection, instance 6
MAPGAPC6
MAP (6)
MAP (6)
Fault locator, instance 1
SCEFRFLO1
FLOC (1)
21FL (1)
Table continues on next page
Recloser Protection and Control RER615
Point List Manual
11
Section 1
Introduction
1MRS757822 B
Function
IEC 61850
IEC 60617
IEC-ANSI
Current total demand distortion,
instance 1
CMHAI1
PQM3I (1)
PQM3I (1)
Voltage total harmonic distortion,
instance 1
VMHAI1
PQM3U (1)
PQM3V (1)
Voltage variation, instance 1
PHQVVR1
PQMU (1)
PQMV (1)
Voltage unbalance, instance 1
VSQVUB1
PQUUB (1)
PQVUB (1)
Circuit-breaker control, instance 1
CBXCBR1
I <-> O CB (1)
I <-> O CB (1)
Disconnector position indication,
instance 1
DCSXSWI1
I <-> O DC (1)
I <-> O DC (1)
Disconnector position indication,
instance 2
DCSXSWI2
I <-> O DC (2)
I <-> O DC (2)
Earthing switch indication, instance 1
ESSXSWI1
I <-> O ES (1)
I <-> O ES (1)
Earthing switch indication, instance 2
ESSXSWI2
I <-> O ES (2)
I <-> O ES (2)
Autoreclosing, instance 1
DARREC1
O -> I (1)
79 (1)
Synchronism and energizing check,
instance 1
SECRSYN1
SYNC (1)
25 (1)
Circuit-breaker condition monitoring,
instance 1
SSCBR1
CBCM (1)
CBCM (1)
Trip circuit supervision, instance 1
TCSSCBR1
TCS (1)
TCM (1)
Trip circuit supervision, instance 2
TCSSCBR2
TCS (2)
TCM (2)
Fuse failure supervision, instance 1
SEQRFUF1
FUSEF (1)
60 (1)
Runtime counter for machines and
devices, instance 1
MDSOPT1
OPTS (1)
OPTM (1)
Voltage presence, instance 1
PHSVPR1
PHSVPR(1)
PHSVPR(1)
Disturbance recorder, instance 1
RDRE1
DR (1)
DFR (1)
Three-phase current measurement,
instance 1
CMMXU1
3I (1)
3I (1)
Sequence current measurement,
instance 1
CSMSQI1
I1, I2, I0 (1)
I1, I2, I0 (1)
Residual current measurement,
instance 1
RESCMMXU1
Io (1)
In (1)
Three-phase voltage measurement,
instance 1
VMMXU1
3U (1)
3V (1)
Three-phase voltage measurement,
instance 2
VMMXU2
3U (B) (1)
3V (B) (1)
Sequence voltage measurement,
instance 1
VSMSQI1
U1, U2, U0 (1)
V1, V2, V0 (1)
Sequence voltage measurement,
instance 2
VSMSQI2
U1, U2, U0 (B)
(1)
V1, V2, V0 (B) (1)
Three-phase power and energy
measurement, instance 1
PEMMXU1
P, E (1)
P, E (1)
Power quality
Control
Condition monitoring and supervision
Measurement
Table continues on next page
12
Recloser Protection and Control RER615
Point List Manual
Section 1
Introduction
1MRS757822 B
Function
IEC 61850
IEC 60617
IEC-ANSI
Frequency measurement, instance 1
FMMXU1
f (1)
f (1)
Load profile, instance 1
LDPMSTA1
LOADPROF (1)
LOADPROF (1)
TP (1)
TP (1)
TP (2)
TP (2)
TPS (1)
TPS (1)
TPM (1)
TPM (1)
Other
Minimum pulse timer (2 pcs),
instance 1
TPGAPC1
Minimum pulse timer (2 pcs),
instance 2
TPGAPC2
Minimum pulse timer (2 pcs, second
resolution), instance 1
TPSGAPC1
Minimum pulse timer (2 pcs, minute
resolution), instance 1
TPMGAPC1
Pulse timer (8 pcs), instance 1
PTGAPC1
PT (1)
PT (1)
Pulse timer (8 pcs), instance 2
PTGAPC2
PT (2)
PT (2)
Time delay off (8 pcs), instance 1
TOFGAPC1
TOF (1)
TOF (1)
Time delay off (8 pcs), instance 2
TOFGAPC2
TOF (2)
TOF (2)
Time delay on (8 pcs), instance 1
TONGAPC1
TON (1)
TON (1)
Time delay on (8 pcs), instance 2
TONGAPC2
TON (2)
TON (2)
Set reset (8 pcs), instance 1
SRGAPC1
SR (1)
SR (1)
Set reset (8 pcs), instance 2
SRGAPC2
SR (2)
SR (2)
Move (8 pcs), instance 1
MVGAPC1
MV (1)
MV (1)
Move (8 pcs), instance 2
MVGAPC2
MV (2)
MV (2)
Generic control point (16 pcs),
instance 1
SPCGGIO1
SPCGGIO (1)
SPCGGIO (1)
Generic control point (16 pcs),
instance 2
SPCGGIO2
SPCGGIO (2)
SPCGGIO (2)
Remote generic control points,
instance 1
SPCRGGIO1
SPCRGGIO (1)
SPCRGGIO (1)
Local generic control points,
instance 1
SPCLGGIO1
SPCLGGIO (1)
SPCLGGIO (1)
Generic up-down counters, instance 1
UDFCNT1
UDCNT (1)
UDCNT (1)
Generic up-down counters, instance 2
UDFCNT2
UDCNT (2)
UDCNT (2)
Generic up-down counters, instance 3
UDFCNT3
UDCNT (3)
UDCNT (3)
Recloser Protection and Control RER615
Point List Manual
13
14
Section 2
Modbus data mappings
1MRS757822 B
Section 2
Modbus data mappings
2.1
Overview
This document describes the Modbus data points and structures available in the
IED. The point lists describe a superset of all data available through the standard
configuration/s including the optional functionalities.
The majority of the Modbus data points are valid for all standard configurations.
Some data points are standard configuration-dependent or optional applicationdependent and thus not available in each IED. The unavailable, that means, unused,
data points always return value 0 when they are read. The configuration-dependent
and optional data do not overlap.
2.2
Table 2:
Supported functions in RER615
Supported functions
Function
IEC 61850
A
RE01
D
RE02
Protection1)2)
Three-phase non-directional overcurrent protection, low stage
FPHLPTOC
(1)3)
(1)3)
Three-phase non-directional overcurrent protection, high stage
PHHPTOC
(1)3)
(1)3)
Three-phase non-directional overcurrent protection, instantaneous stage
PHIPTOC
1
1
Three-phase directional overcurrent protection, low stage
FDPHLPDOC
(2)3)
(2)3)
Three-phase directional overcurrent protection, high stage
DPHHPDOC
(1)3)
(1)3)
Non-directional earth-fault protection, low stage
FEFLPTOC
(1)4)5)
(1)4)5)
Non-directional earth-fault protection, high stage
EFHPTOC
(1)4)5)
(1)4)5)
Non-directional earth-fault protection, instantaneous stage
EFIPTOC
15)
15)
Directional earth-fault protection, low stage
FDEFLPDEF
(2)5)6)7)
(2)5)6)7)
Directional earth-fault protection, high stage
DEFHPDEF
(1)5)6)7)
(1)5)6)7)
Transient / intermittent earth-fault protection
INTRPTEF
(1)5)6)7)
(1)5)6)7)
Admittance based earth-fault protection
EFPADM
(3)5)7)8)
(3)5)7)8)
Wattmetric based earth-fault protection
WPWDE
(3)5)7)8)
(3)5)7)8)
Harmonics based earth-fault protection
HAEFPTOC
(1)5)8)
(1)5)8)
Negative-sequence overcurrent protection
NSPTOC
2
2
Phase discontinuity protection
PDNSPTOC
1
1
(1)7)
(2)9)10)
Residual overvoltage protection
ROVPTOV
Table continues on next page
Recloser Protection and Control RER615
Point List Manual
15
Section 2
Modbus data mappings
Function
1MRS757822 B
IEC 61850
A
RE01
D
RE02
Three-phase undervoltage protection
PHPTUV
(3)
(3)11)
Three-phase overvoltage protection
PHPTOV
(3)
(3)11)
Positive-sequence undervoltage protection
PSPTUV
(1)
(1)
Negative-sequence overvoltage protection
NSPTOV
(1)
(1)
Frequency protection
FRPFRQ
(2)
(2)
Three-phase thermal protection for feeders, cables and distribution transformers
T1PTTR
1
1
Circuit breaker failure protection
CCBRBRF
1
1
Three-phase inrush detector
INRPHAR
1
1
Master trip
TRPPTRC
2
2
Multi-purpose protection
MAPGAPC
6
6
Fault locator
SCEFRFLO
(1)
(1)
Current total demand distortion
CMHAI
(1)
(1)
Voltage total harmonic distortion
VMHAI
(1)
(1)
Voltage variation
PHQVVR
(1)
(1)
Voltage unbalance
VSQVUB
(1)
(1)
Circuit-breaker control
CBXCBR
1
1
Disconnector position indication
DCSXSWI
2
2
Earthing switch indication
ESSXSWI
2
2
Autoreclosing
DARREC
1
1
Synchronism and energizing check
SECRSYN
Power quality
Control
1
Condition monitoring and supervision
Circuit-breaker condition monitoring
SSCBR
1
1
Trip circuit supervision
TCSSCBR
2
2
Fuse failure supervision
SEQRFUF
1
1
Runtime counter for machines and devices
MDSOPT
1
1
Voltage presence
PHSVPR
1
1
Disturbance recorder
RDRE
1
1
Three-phase current measurement
CMMXU
1
1
Sequence current measurement
CSMSQI
1
1
Residual current measurement
RESCMMXU
1
1
Three-phase voltage measurement
VMMXU
1
1(2)12)
Sequence voltage measurement
VSMSQI
1
1(2)12)
Three-phase power and energy measurement
PEMMXU
1
1
Frequency measurement
FMMXU
1
1
Load profile
LDPMSTA
1
1
Measurement
Other
Table continues on next page
16
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
Function
IEC 61850
A
RE01
D
RE02
Minimum pulse timer (2 pcs)
TPGAPC
2
2
Minimum pulse timer (2 pcs, second resolution)
TPSGAPC
1
1
Minimum pulse timer (2 pcs, minute resolution)
TPMGAPC
1
1
Pulse timer (8 pcs)
PTGAPC
2
2
Time delay off (8 pcs)
TOFGAPC
2
2
Time delay on (8 pcs)
TONGAPC
2
2
Set reset (8 pcs)
SRGAPC
2
2
Move (8 pcs)
MVGAPC
2
2
Generic control point (16 pcs)
SPCGGIO
2
2
Remote generic control points
SPCRGGIO
1
1
Local generic control points
SPCLGGIO
1
1
Generic up-down counters
UDFCNT
3
3
1, 2, ... = number of included instances
() = optional
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
11)
12)
All directional protection functions can also be used in the non-directional mode
The instances of a protection function represent the number of identical protection function blocks available in the standard configuration
Only one can be ordered as an option at a time with OC or directional OC
Can be ordered as an option when OC is also chosen
Io selectable by parameter, Io measured by default
Can be ordered as an option when OC or directional OC is also chosen
Uo calculated is always used
One of the three can be ordered as an option when directional OC and directional EF are chosen: Admittance based EF, Wattmetric
based EF or Harmonics based EF
Uo calculated is always used with the first instance
UoB calculated is always used with the second instance
Voltage group B is always used with the third instance
Voltage group B is always used with the second instance
2.3
Indications
Table 3:
Column name
Explanations of the indications table columns
Description
BitA
Default 0X and 1X bit address for the data.
RegA
Default 3X and 4X register.bit (00-15) address for the data.
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name
The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description
Short description of the signal. See the technical manual for more information.
Value
Meaning of the value states.
Recloser Protection and Control RER615
Point List Manual
17
Section 2
Modbus data mappings
2.3.1
Table 4:
BitA
1MRS757822 B
Common data 1
Common data 1
RegA
IEC 61850 name
SA name
Description
Values
CTRL.LLN0
2720
170.00
.Loc.stVal
-
Remote/Local state
0/1=Rem/Loc
2721
170.01
.LocRem.stVal.Station
-
Station state
1=Station
-
DR recording made
1=Made
Settings reserved
1=Reserved
Settings changed
1=Changed
DR.RDRE1
2722
170.02
.RcdMade.stVal
2723
170.03
.mcd
LD0.LLN0
2726
170.06
.SetSeld.stVal
2727
170.07
.mcd
2728
170.08
.SetChg.stVal
2729
170.09
.mcd
2.3.2
Table 5:
BitA
LD0.FPHLPTOC1 Three-phase non-directional overcurrent
protection, low stage (1)
LD0.FPHLPTOC1 Three-phase non-directional overcurrent protection, low stage (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.FPHLPTOC1
18
3936
246.00
.Str.general
3937
246.01
.mcd
3938
246.02
.Str.phsA
3939
246.03
.mcd
3940
246.04
.Str.phsB
3941
246.05
.mcd
3942
246.06
.Str.phsC
3943
246.07
.mcd
3944
246.08
.Op.general
3945
246.09
.mcd
START
OPERATE
General start
1=Start
phsA start
1=Start
phsB start
1=Start
phsC start
1=Start
General operate
1=Operate
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
2.3.3
Table 6:
BitA
LD0.PHHPTOC1 Phase overcurrent protection, high stage
(1)
LD0.PHHPTOC1 Phase overcurrent protection, high stage (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.PHHPTOC1
2890
180.10
.Str.general
2891
180.11
.mcd
2892
180.12
.Str.phsA
2893
180.13
.mcd
2894
180.14
.Str.phsB
2895
180.15
.mcd
2896
181.00
.Str.phsC
2897
181.01
.mcd
2898
181.02
.Op.general
2899
181.03
.mcd
2.3.4
Table 7:
BitA
START
OPERATE
General start
1=Start
phsA start
1=Start
phsB start
1=Start
phsC start
1=Start
General operate
1=Operate
LD0.PHIPTOC1 Phase overcurrent protection,
instantaneous stage (1)
LD0.PHIPTOC1 Phase overcurrent protection, instantaneous stage (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.PHIPTOC1
2910
181.14
.Str.general
2911
181.15
.mcd
2912
182.00
.Str.phsA
2913
182.01
.mcd
2914
182.02
.Str.phsB
2915
182.03
.mcd
2916
182.04
.Str.phsC
2917
182.05
.mcd
2918
182.06
.Op.general
2919
182.07
.mcd
Recloser Protection and Control RER615
Point List Manual
START
OPERATE
General start
1=Start
phsA start
1=Start
phsB start
1=Start
phsC start
1=Start
General operate
1=Operate
19
Section 2
Modbus data mappings
2.3.5
Table 8:
BitA
1MRS757822 B
LD0.FDPHLPDOC1 Three-phase directional overcurrent
protection, low stage (1)
LD0.FDPHLPDOC1 Three-phase directional overcurrent protection, low stage (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.FDPHLPTOC1
3006
187.14
.Str.general
3007
187.15
.mcd
3008
188.00
.Str.phsA
3009
188.01
.mcd
3010
188.02
.Str.phsB
3011
188.03
.mcd
3012
188.04
.Str.phsC
3013
188.05
.mcd
3014
188.06
.Op.general
3015
188.07
.mcd
2.3.6
Table 9:
BitA
START
OPERATE
General start
1=Start
phsA start
1=Start
phsB start
1=Start
phsC start
1=Start
General operate
1=Operate
LD0.FPDHLPDOC2 Three-phase directional overcurrent
protection, low stage (2)
LD0.FPDHLPDOC2 Three-phase directional overcurrent protection, low stage (2)
RegA
IEC 61850 name
SA name
Description
Values
LD0.FDPHLPTOC2
20
3016
188.08
.Str.general
3017
188.09
.mcd
3018
188.10
.Str.phsA
3019
188.11
.mcd
3020
188.12
.Str.phsB
3021
188.13
.mcd
3022
188.14
.Str.phsC
3023
188.15
.mcd
3024
189.00
.Op.general
3025
189.01
.mcd
START
OPERATE
General start
1=Start
phsA start
1=Start
phsB start
1=Start
phsC start
1=Start
General operate
1=Operate
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
2.3.7
Table 10:
BitA
LD0.DPHHPDOC1 Three-phase directional overcurrent
protection, high stage (1)
LD0.DPHHPDOC1 Three-phase directional overcurrent protection, high stage (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.DPHHPTOC1
3026
189.02
.Str.general
3027
189.03
.mcd
3028
189.04
.Str.phsA
3029
189.05
.mcd
3030
189.06
.Str.phsB
3031
189.07
.mcd
3032
189.08
.Str.phsC
3033
189.09
.mcd
3034
189.10
.Op.general
3035
189.11
.mcd
2.3.8
Table 11:
START
OPERATE
General start
1=Start
phsA start
1=Start
phsB start
1=Start
phsC start
1=Start
General operate
1=Operate
LD0.FEFLPTOC1 Non-directional earth-fault protection,
low stage (1)
LD0.FEFLPTOC1 Non-directional earth-fault protection, low stage (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
START
Stage start
1=Start
OPERATE
Stage operate
1=Operate
LD0.FEFLPTOC1
3966
247.14
.Str.general
3967
247.15
.mcd
3968
248.00
.Opr.general
3969
248.01
.mcd
2.3.9
Table 12:
BitA
LD0.EFHPTOC1 Non-directional earth-fault protection,
high stage (1)
LD0.EFHPTOC1 Non-directional earth-fault protection, high stage (1)
RegA
IEC 61850 name
SA name
Description
Values
START
Stage start
1=Start
OPERATE
Stage operate
1=Operate
LD0.EFHPTOC1
2940
183.12
.Str.general
2941
183.13
.mcd
2942
183.14
.Op.general
2943
183.15
.mcd
Recloser Protection and Control RER615
Point List Manual
21
Section 2
Modbus data mappings
2.3.10
Table 13:
BitA
1MRS757822 B
LD0.EFIPTOC1 Non-directional earth-fault protection,
instantaneous stage (1)
LD0.EFIPTOC1 Non-directional earth-fault protection, instantaneous stage (1)
RegA
IEC 61850 name
SA name
Description
Values
START
Stage start
1=Start
OPERATE
Stage operate
1=Operate
LD0.EFIPTOC1
2944
184.00
.Str.general
2945
184.01
.mcd
2946
184.02
.Op.general
2947
184.03
.mcd
2.3.11
Table 14:
BitA
LD0.FDEFLPDEF1 Directional earth-fault protection, low
stage (1)
LD0.FDEFLPDEF1 Directional earth-fault protection, low stage (1)
RegA
IEC 61850 name
SA name
Description
Values
START
Stage start
1=Start
OPERATE
Stage operate
1=Operate
LD0.FDEFLPTOC1
2920
182.08
.Str.general
2921
182.09
.mcd
2922
182.10
.Op.general
2923
182.11
.mcd
2.3.12
Table 15:
BitA
LD0.FDEFLPDEF2 Directional earth-fault protection, low
stage (2)
LD0.FDEFLPDEF2 Directional earth-fault protection, low stage (2)
RegA
IEC 61850 name
SA name
Description
Values
START
Stage start
1=Start
OPERATE
Stage operate
1=Operate
LD0.FDEFLPTOC2
22
2924
182.12
.Str.general
2925
182.13
.mcd
2926
182.14
.Op.general
2927
182.15
.mcd
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
2.3.13
Table 16:
BitA
LD0.DEFHPDEF1 Directional earth-fault protection, high
stage (1)
LD0.DEFHPDEF1 Directional earth-fault protection, high stage (1)
RegA
IEC 61850 name
SA name
Description
Values
START
Stage start
1=Start
OPERATE
Stage operate
1=Operate
LD0.DEFHPTOC1
2928
183.00
.Str.general
2929
183.01
.mcd
2930
183.02
.Op.general
2931
183.03
.mcd
2.3.14
Table 17:
BitA
LD0.INTRPTEF1 Intermittent earth fault protection (1)
LD0.INTRPTEF1 Intermittent earth fault protection (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.INTRPTEF1
3176
198.08
.Str.general
3177
198.09
.mcd
3178
198.10
.Op.general
3179
198.11
.mcd
2.3.15
Table 18:
BitA
START
General Start
1=Start
OPERATE
General Operate
2=Operate
LD0.EFPADM1 Admittance-based earth-fault protection (1)
LD0.EFPADM1 Admittance-based earth-fault protection (1)
RegA
IEC 61850 name
SA name
Description
Values
START
Stage start
1=Start
OPERATE
Stage operate
1=Operate
LD0.EFPADM1
2840
177.08
.Str.general
2841
177.09
.mcd
2842
177.10
.Op.general
2843
177.11
.mcd
2.3.16
Table 19:
BitA
LD0.EFPADM2 Admittance-based earth-fault protection (2)
LD0.EFPADM2 Admittance-based earth-fault protection (2)
RegA
IEC 61850 name
SA name
Description
Values
START
Stage start
1=Start
OPERATE
Stage operate
1=Operate
LD0.EFPADM2
2844
177.12
.Str.general
2845
177.13
.mcd
2846
177.14
.Op.general
2847
177.15
.mcd
Recloser Protection and Control RER615
Point List Manual
23
Section 2
Modbus data mappings
2.3.17
Table 20:
BitA
1MRS757822 B
LD0.EFPADM3 Admittance-based earth-fault protection (3)
LD0.EFPADM3 Admittance-based earth-fault protection (3)
RegA
IEC 61850 name
SA name
Description
Values
START
Stage start
1=Start
OPERATE
Stage operate
1=Operate
LD0.EFPADM3
2860
178.12
.Str.general
2861
178.13
.mcd
2862
178.14
.Op.general
2863
178.15
.mcd
2.3.18
Table 21:
BitA
LD0.WPWDE1 Wattmetric-based earth-fault protection (1)
LD0.WPWDE1 Wattmetric-based earth-fault protection (1)
RegA
IEC 61850 name
SA name
Description
Values
START
Stage start
1=Start
OPERATE
Stage operate
1=Operate
LD0.WPSDE1
3296
206.00
.Str.general
3297
206.01
.mcd
3298
206.02
.Op.general
3299
206.03
.mcd
2.3.19
Table 22:
BitA
LD0.WPWDE2 Wattmetric-based earth-fault protection (2)
LD0.WPWDE2 Wattmetric-based earth-fault protection (2)
RegA
IEC 61850 name
SA name
Description
Values
START
Stage start
1=Start
OPERATE
Stage operate
1=Operate
LD0.WPSDE2
3300
206.04
.Str.general
3301
206.05
.mcd
3302
206.06
.Op.general
3303
206.07
.mcd
2.3.20
Table 23:
BitA
LD0.WPWDE3 Wattmetric-based earth-fault protection (3)
LD0.WPWDE3 Wattmetric-based earth-fault protection (3)
RegA
IEC 61850 name
SA name
Description
Values
START
Stage start
1=Start
OPERATE
Stage operate
1=Operate
LD0.WPSDE3
3304
206.08
.Str.general
3305
206.09
.mcd
3306
206.10
.Op.general
3307
206.11
.mcd
24
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
2.3.21
Table 24:
BitA
LD0.HAEFPTOC1 Harmonics-based earth-fault protection
(1)
LD0.HAEFPTOC1 Harmonics-based earth-fault protection (1)
RegA
IEC 61850 name
SA name
Description
Values
START
Stage start
1=Start
OPERATE
Stage operate
1=Operate
LD0.HAEFPTOC1
3312
207.00
.Str.general
3313
207.01
.mcd
3314
207.02
.Op.general
3315
207.03
.mcd
2.3.22
Table 25:
BitA
LD0.NSPTOC1 Negative-sequence overcurrent protection
(1)
LD0.NSPTOC1 Negative-sequence overcurrent protection (1)
RegA
IEC 61850 name
SA name
Description
Values
START
Stage start
1=Start
OPERATE
Stage operate
1=Operate
LD0.NSPTOC1
2956
184.12
.Str.general
2957
184.13
.mcd
2958
184.14
.Op.general
2959
184.15
.mcd
2.3.23
Table 26:
BitA
LD0.NSPTOC2 Negative-sequence overcurrent protection
(2)
LD0.NSPTOC2 Negative-sequence overcurrent protection (2)
RegA
IEC 61850 name
SA name
Description
Values
START
Stage start
1=Start
OPERATE
Stage operate
1=Operate
LD0.NSPTOC2
2960
185.00
.Str.general
2961
185.01
.mcd
2962
185.02
.Op.general
2963
185.03
.mcd
Recloser Protection and Control RER615
Point List Manual
25
Section 2
Modbus data mappings
2.3.24
Table 27:
BitA
1MRS757822 B
LD0.PDNSPTOC1 Phase discontinuity protection (1)
LD0.PDNSPTOC1 Phase discontinuity protection (1)
RegA
IEC 61850 name
SA name
Description
Values
START
Stage start
1=Start
OPERATE
Stage operate
1=Operate
LD0.PDNSPTOC1
2952
184.08
.Str.general
2953
184.09
.mcd
2954
184.10
.Op.general
2955
184.11
.mcd
2.3.25
Table 28:
BitA
LD0.ROVPTOV1 Residual overvoltage protection (1)
LD0.ROVPTOV1 Residual overvoltage protection (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.ROVPTOV1
3168
198.00
.Str.general
3169
198.01
.mcd
3170
198.02
.Op.general
3171
198.03
.mcd
2.3.26
Table 29:
BitA
START
General start
1=Start
OPERATE
General operate
1=Operate
LD0.ROVPTOV2 Residual overvoltage protection (2)
LD0.ROVPTOV2 Residual overvoltage protection (2)
RegA
IEC 61850 name
SA name
Description
Values
LD0.ROVPTOV2
3172
198.04
.Str.general
3173
198.05
.mcd
3174
198.06
.Op.general
3175
198.07
.mcd
2.3.27
Table 30:
BitA
START
General start
1=Start
OPERATE
General operate
1=Operate
LD0.PHPTUV1 Phase undervoltage protection (1)
LD0.PHPTUV1 Phase undervoltage protection (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.PHPTUV1
3138
196.02
.Str.general
3139
196.03
.mcd
3140
196.04
.Str.phsA
3141
196.05
.mcd
START
General start
1=Start
phsA start
1=Start
Table continues on next page
26
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
BitA
RegA
IEC 61850 name
3142
196.06
.Str.phsB
3143
196.07
.mcd
3144
196.08
.Str.phsC
3145
196.09
.mcd
3146
196.10
.Op.general
3147
196.11
.mcd
2.3.28
Table 31:
BitA
SA name
OPERATE
Description
Values
phsB start
1=Start
phsC start
1=Start
General operate
1=Operate
LD0.PHPTUV2 Phase undervoltage protection (2)
LD0.PHPTUV2 Phase undervoltage protection (2)
RegA
IEC 61850 name
SA name
Description
Values
LD0.PHPTUV2
3148
196.12
.Str.general
3149
196.13
.mcd
3150
196.14
.Str.phsA
3151
196.15
.mcd
3152
197.00
.Str.phsB
3153
197.01
.mcd
3154
197.02
.Str.phsC
3155
197.03
.mcd
3156
197.04
.Op.general
3157
197.05
.mcd
2.3.29
Table 32:
BitA
START
OPERATE
General start
1=Start
phsA start
1=Start
phsB start
1=Start
phsC start
1=Start
General operate
1=Operate
LD0.PHPTUV3 Phase undervoltage protection (3)
LD0.PHPTUV3 Phase undervoltage protection (3)
RegA
IEC 61850 name
SA name
Description
Values
LD0.PHPTUV3
3158
197.06
.Str.general
3159
197.07
.mcd
3160
197.08
.Str.phsA
3161
197.09
.mcd
3162
197.10
.Str.phsB
3163
197.11
.mcd
3164
197.12
.Str.phsC
3165
197.13
.mcd
3166
197.14
.Op.general
3167
197.15
.mcd
Recloser Protection and Control RER615
Point List Manual
START
OPERATE
General start
1=Start
phsA start
1=Start
phsB start
1=Start
phsC start
1=Start
General operate
1=Operate
27
Section 2
Modbus data mappings
2.3.30
Table 33:
BitA
1MRS757822 B
LD0.PHPTOV1 Phase overvoltage protection (1)
LD0.PHPTOV1 Phase overvoltage protection (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.PHPTOV1
3088
193.00
.Str.general
3089
193.01
.mcd
3090
193.02
.Str.phsA
3091
193.03
.mcd
3092
193.04
.Str.phsB
3093
193.05
.mcd
3094
193.06
.Str.phsC
3095
193.07
.mcd
3096
193.08
.Op.general
3097
193.09
.mcd
2.3.31
Table 34:
BitA
START
OPERATE
General start
1=Start
phsA start
1=Start
phsB start
1=Start
phsC start
1=Start
General operate
1=Operate
LD0.PHPTOV2 Phase overvoltage protection (2)
LD0.PHPTOV2 Phase overvoltage protection (2)
RegA
IEC 61850 name
SA name
Description
Values
LD0.PHPTOV2
3098
193.10
.Str.general
3099
193.11
.mcd
3100
193.12
.Str.phsA
3101
193.13
.mcd
3102
193.14
.Str.phsB
3103
193.15
.mcd
3104
194.00
.Str.phsC
3105
194.01
.mcd
3106
194.02
.Op.general
3107
194.03
.mcd
2.3.32
Table 35:
BitA
START
OPERATE
General start
1=Start
phsA start
1=Start
phsB start
1=Start
phsC start
1=Start
General operate
1=Operate
LD0.PHPTOV3 Phase overvoltage protection (3)
LD0.PHPTOV3 Phase overvoltage protection (3)
RegA
IEC 61850 name
SA name
Description
Values
LD0.PHPTOV3
3108
194.04
.Str.general
3109
194.05
.mcd
3110
194.06
.Str.phsA
START
General start
1=Start
phsA start
1=Start
Table continues on next page
28
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
BitA
RegA
IEC 61850 name
3111
194.07
.mcd
3112
194.08
.Str.phsB
3113
194.09
.mcd
3114
194.10
.Str.phsC
3115
194.11
.mcd
3116
194.12
.Op.general
3117
194.13
.mcd
2.3.33
Table 36:
BitA
SA name
OPERATE
Description
Values
phsB start
1=Start
phsC start
1=Start
General operate
1=Operate
LD0.PSPTUV1 Positive-sequence undervoltage protection
(1)
LD0.PSPTUV1 Positive-sequence undervoltage protection (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.PSPTUV1
3118
194.14
.Str.general
3119
194.15
.mcd
3120
195.00
.Str.phsA
3121
195.01
.mcd
3122
195.02
.Str.phsB
3123
195.03
.mcd
3124
195.04
.Str.phsC
3125
195.05
.mcd
3126
195.06
.Op.general
3127
195.07
.mcd
2.3.34
Table 37:
BitA
START
OPERATE
General start
1=Start
phsA start
1=Start
phsB start
1=Start
phsC start
1=Start
General operate
1=Operate
LD0.NSPTOV1 Negative-sequence overvoltage protection
(1)
LD0.NSPTOV1 Negative-sequence overvoltage protection (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.NSPTOV1
3128
195.08
.Str.general
3129
195.09
.mcd
3130
195.10
.Str.phsA
3131
195.11
.mcd
3132
195.12
.Str.phsB
3133
195.13
.mcd
3134
195.14
.Str.phsC
START
General start
1=Start
phsA start
1=Start
phsB start
1=Start
phsC start
1=Start
Table continues on next page
Recloser Protection and Control RER615
Point List Manual
29
Section 2
Modbus data mappings
BitA
RegA
IEC 61850 name
3135
195.15
.mcd
3136
196.00
.Op.general
3137
196.01
.mcd
2.3.35
Table 38:
BitA
1MRS757822 B
SA name
OPERATE
Description
Values
General operate
1=Operate
LD0.FRPFRQ1 Frequency protection (1)
LD0.FRPFRQ1 Frequency protection (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.FRPTRC1
4000
250.00
.Str.general
4001
250.01
.mcd
START
LD0.FRPTOF1
4002
250.02
.Op.general
4003
250.03
.mcd
250.04
.Op.general
4005
250.05
.mcd
4006
250.06
.Op.general
4007
250.07
.mcd
OPR_OFRQ
Table 39:
BitA
Operate
1=Operate
Underfrequency
OPR_UFRQ
LD0.FRPFRC1
2.3.36
1=Start
Overfrequency
LD0.FRPTUF1
4004
Stage 1 start
Operate
1=Operate
Frequency gradient
OPR_FRG
Operate
1=Operate
LD0.FRPFRQ2 Frequency protection (2)
LD0.FRPFRQ2 Frequency protection (2)
RegA
IEC 61850 name
SA name
Description
Values
LD0.FRPTRC2
4008
250.08
.Str.general
4009
250.09
.mcd
START
LD0.FRPTOF2
4010
250.10
.Op.general
4011
250.11
.mcd
250.12
.Op.general
4013
250.13
.mcd
OPR_OFRQ
250.14
.Op.general
4015
250.15
.mcd
30
Operate
1=Operate
Underfrequency
OPR_UFRQ
LD0.FRPFRC2
4014
1=Start
Overfrequency
LD0.FRPTUF2
4012
Stage 2 start
Operate
1=Operate
Frequency gradient
OPR_FRG
Operate
1=Operate
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
2.3.37
Table 40:
BitA
LD0.T1PTTR1 Thermal overload protection (1)
LD0.T1PTTR1 Thermal overload protection (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.T1PTTR1
2972
185.12
.Str.general
2973
185.13
.mcd
2974
185.14
.AlmThm.general
2975
185.15
.mcd
2976
186.00
.Op.general
2977
186.01
.mcd
2.3.38
Table 41:
BitA
START
General start
1=Start
ALARM
Thermal alarm
1=Alarm
OPERATE
General operate
1=Operate
CTRL.CCBRBRF1 Circuit breaker (1) failure protection
CTRL.CCBRBRF1 Circuit breaker (1) failure protection
RegA
IEC 61850 name
SA name
Description
Values
CTRL.CCBRBRF1
2826
176.10
.InStr.stVal
2827
170.11
.mcd
2828
176.12
.Str.general
2829
176.13
.mcd
2830
176.14
.OpEx.general
2831
176.15
.mcd
2832
177.00
.OpIn.general
2833
177.01
.mcd
2.3.39
Table 42:
BitA
START
CBFP start command
1=Start
CB_FAULT_AL
Timer running
1=Running
TRBU
Fail, external trip
1=Ext.trip
TRRET
Internal re-trip
1=Re-trip
LD0.INRPHAR1 Three-phase inrush detection (1)
LD0.INRPHAR1 Three-phase inrush detection (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.INRPHAR1
2964
185.04
.Str.general
2965
185.05
.mcd
2966
185.06
.Str.phsA
2967
185.07
.mcd
2968
185.08
.Str.phsB
2969
185.09
.mcd
2970
185.10
.Str.phsC
2971
185.11
.mcd
Recloser Protection and Control RER615
Point List Manual
BLK2H
General start
1=Start
phsA start
1=Start
phsB start
1=Start
phsC start
1=Start
31
Section 2
Modbus data mappings
2.3.40
Table 43:
BitA
1MRS757822 B
LD0.TRPPTRC1 Protection trip conditioning (1)
LD0.TRPPTRC1 Protection trip conditioning (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.TRPPTRC1
2740
171.04
.Op.general
2741
171.05
.mcd
2742
171.06
.Tr.general
2743
171.07
.mcd
2.3.41
Table 44:
BitA
-
Op.Input signal
1=Operate
-
Trip output signal
1=Trip
LD0.TRPPTRC2 Protection trip conditioning (2)
LD0.TRPPTRC2 Protection trip conditioning (2)
RegA
IEC 61850 name
SA name
Description
Values
LD0.TRPPTRC2
2744
171.08
.Op.general
2745
171.09
.mcd
2746
171.10
.Tr.general
2747
171.11
.mcd
2.3.42
Table 45:
BitA
-
Op.Input signal
1=Operate
-
Trip output signal
1=Trip
LD0.MAPGAPC1 Multipurpose analog protection function
(1)
LD0.MAPGAPC1 Multipurpose analog protection function (1)
RegA
IEC 61850 name
SA name
Description
Values
START
Stage start
1 = Start
OPERATE
Stage operate
1 = Operate
LD0.MAPGAPC1
3696
231.00
.Str.general
3697
231.01
.mcd
3698
231.02
.Op.general
3699
231.03
.mcd
32
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
2.3.43
Table 46:
BitA
LD0.MAPGAPC2 Multipurpose analog protection function
(2)
LD0.MAPGAPC2 Multipurpose analog protection function (2)
RegA
IEC 61850 name
SA name
Description
Values
START
Stage start
1 = Start
OPERATE
Stage operate
1 = Operate
LD0.MAPGAPC2
3700
231.04
.Str.general
3701
231.05
.mcd
3702
231.06
.Op.general
3703
231.07
.mcd
2.3.44
Table 47:
BitA
LD0.MAPGAPC3 Multipurpose analog protection function
(3)
LD0.MAPGAPC3 Multipurpose analog protection function (3)
RegA
IEC 61850 name
SA name
Description
Values
START
Stage start
1 = Start
OPERATE
Stage operate
1 = Operate
LD0.MAPGAPC3
3704
231.08
.Str.general
3705
231.09
.mcd
3706
231.10
.Op.general
3707
231.11
.mcd
2.3.45
Table 48:
BitA
LD0.MAPGAPC4 Multipurpose analog protection function
(4)
LD0.MAPGAPC4 Multipurpose analog protection function (4)
RegA
IEC 61850 name
SA name
Description
Values
LD0.MAPGAPC4
3708
231.12
.Str.general
3709
231.13
.mcd
3700
231.14
.Op.general
3711
231.15
.mcd
Recloser Protection and Control RER615
Point List Manual
START
Start
1 = Start
OPERATE
Operate
1 = Operate
33
Section 2
Modbus data mappings
2.3.46
Table 49:
BitA
1MRS757822 B
LD0.MAPGAPC5 Multipurpose analog protection function
(5)
LD0.MAPGAPC5 Multipurpose analog protection function (5)
RegA
IEC 61850 name
SA name
Description
Values
START
Stage start
1 = Start
OPERATE
Stage operate
1 = Operate
LD0.MAPGAPC5
3712
232.00
.Str.general
3713
232.01
.mcd
3714
232.02
.Op.general
3715
232.03
.mcd
2.3.47
Table 50:
BitA
LD0.MAPGAPC6 Multipurpose analog protection function
(6)
LD0.MAPGAPC6 Multipurpose analog protection function (6)
RegA
IEC 61850 name
SA name
Description
Values
START
Stage start
1 = Start
OPERATE
Stage operate
1 = Operate
LD0.MAPGAPC6
3716
232.04
.Str.general
3717
232.05
.mcd
3718
232.06
.Op.general
3719
232.07
.mcd
2.3.48
Table 51:
BitA
LD0.CMHAI1 Current total demand distortion (1)
LD0.CMHAI1 Current total demand distortion (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.CMHAI1
3316
207.04
.Alm.stVal
3317
207.05
.mcd
2.3.49
Table 52:
BitA
ALARM
1=Alarm
LD0.VMHAI1 Voltage total demand distortion (1)
LD0.VMHAI1 Voltage total demand distortion (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.VMHAI1
3318
207.06
.Alm.stVal
3319
207.07
.mcd
34
ALARM
1=Alarm
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
2.3.50
Table 53:
BitA
LD0.PHQVVR1 PQ - Voltage variation signals (1)
LD0.PHQVVR1 PQ - Voltage variation signals (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.PH1QVVR1
3328
208.00
.VarStrGen.stVal
3329
208.01
.mcd
3330
208.02
.VarEnd.stVal
3331
208.03
.mcd
3332
208.04
.SwlOp.stVal
3333
208.05
.mcd
3334
208.06
.DipOp.stVal
3335
208.07
.mcd
3336
208.08
.IntrOp.stVal
3337
208.09
.mcd
2.3.51
Table 54:
-
Variation event detected
1=Detected
-
Variation event ended
1=Ended
-
Swell event detected
1=Detected
-
Dip event detected
1=Detected
-
Interruption event detected
1=Detected
LD0.VSQVUB1 Voltage unbalance (1)
LD0.VSQVUB1 Voltage unbalance (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.VSQVUB1
3984
249.00
.VarStr.stVal
3985
249.01
.mcd
3986
249.02
.HiPctVUnb.stVal
3987
249.03
.mcd
2.3.52
Table 55:
BitA
Start of the event
1=Start
Unbalance limit exceed
1=Alarm
CTRL.CBXCBR1 Circuit breaker (1) blocking signals
CTRL.CBXCBR1 Circuit breaker (1) blocking signals
RegA
IEC 61850 name
SA name
Description
Values
CTRL.CBXCBR1
2834
177.02
.ItlByPss.stVal
2835
177.03
.mcd
2836
177.04
.BlkOpn.stVal
2837
177.05
.mcd
2838
177.06
.BlkCls.stVal
2839
177.07
.mcd
Recloser Protection and Control RER615
Point List Manual
ITL_BYPASS
Interlock bypass
1=Bypass
BLK_OPEN
Open blocked
1=Blocked
BLK_CLOSE
Close blocked
1=Blocked
35
Section 2
Modbus data mappings
2.3.53
Table 56:
BitA
1MRS757822 B
CTRL.DCSXSWI1 Disconnector position indication (1)
CTRL.DCSXSWI1 Disconnector position indication (1)
RegA
IEC 61850 name
SA name
CTRL.DCSXSWI1
POSITION
Description
Values
2792
174.08
.Pos.stVal.Close
-
Close bit
1=Close
2793
174.09
.Pos.stVal.Open
-
Open bit
1=Open
2794
174.10
.Pos.stVal.Fault
-
Fault bit
1=Pos(00/11)
2.3.54
Table 57:
BitA
CTRL.DCSXSWI2 Disconnector position indication (2)
CTRL.DCSXSWI2 Disconnector position indication (2)
RegA
IEC 61850 name
SA name
CTRL.DCSXSWI2
POSITION
Description
Values
2795
174.11
.Pos.stVal.Close
-
Close bit
1=Close
2796
174.12
.Pos.stVal.Open
-
Open bit
1=Open
2797
174.13
.Pos.stVal.Fault
-
Fault bit
1=Pos(00/11)
2.3.55
Table 58:
BitA
CTRL.ESSXSWI1 Earthing switch indication (1)
CTRL.ESSXSWI1 Earthing switch indication (1)
RegA
IEC 61850 name
SA name
CTRL.ESSXSWI1
POSITION
Description
Values
2801
175.01
.Pos.stVal.Close
-
Close bit
1=Close
2802
175.02
.Pos.stVal.Open
-
Open bit
1=Open
2803
175.03
.Pos.stVal.Fault
-
Fault bit
1=Pos(00/11)
2.3.56
Table 59:
BitA
CTRL.ESSXSWI2 Earthing switch indication (2)
CTRL.ESSXSWI2 Earthing switch indication (2)
RegA
IEC 61850 name
SA name
CTRL.ESSXSWI2
POSITION
Description
Values
2807
175.07
.Pos.stVal.Close
-
Close bit
1=Close
2808
175.08
.Pos.stVal.Open
-
Open bit
1=Open
2809
175.09
.Pos.stVal.Fault
-
Fault bit
1=Pos(00/11)
36
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
2.3.57
Table 60:
BitA
LD0.DARREC1 AR state (1)
LD0.DARREC1 AR state (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.DARREC1
2724
170.04
2.3.58
Table 61:
BitA
.AROn.stVal
AR_ON
AutoRecloser state
0/1=Off/On
LD0.DARREC1 Autorecloser (1)
LD0.DARREC1 Autorecloser (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.DARREC1
3040
190.00
.PrgRec.stVal
3041
190.01
.mcd
3042
190.02
.PrgRec1.stVal
3043
190.03
.mcd
3044
190.04
.PrgRec2.stVal
3045
190.05
.mcd
3046
190.06
.PrgRec3.stVal
3047
190.07
.mcd
3048
190.08
.PrgRec4.stVal
3049
190.09
.mcd
3050
190.10
.PrgRec5.stVal
3051
190.11
.mcd
3052
190.12
.SucRec.stVal
3053
190.13
.mcd
3054
190.14
.UnsRec.stVal
3055
190.15
.mcd
3056
191.00
< reserved >
3057
191.01
< reserved >
3058
191.02
< reserved >
3059
191.03
< reserved >
3060
191.04
.LO.stVal
3061
191.05
.mcd
3062
191.06
.RdyRec.stVal
3063
191.07
.mcd
3064
191.08
.ActRec.stVal
3065
191.09
.mcd
3066
191.10
.PrgDsr.stVal
3067
191.11
.mcd
INPRO
AR in progess
1=In progress
INPRO_1
1st shot in progess
1=In progress
INPRO_2
2nd shot in progess
1=In progress
INPRO_3
3rd shot in progess
1=In progress
INPRO_4
4th shot in progess
1=In progress
INPRO_5
5th shot in progess
1=In progress
SUC_RECL
Successful AR
1=Success
UNSUC_RECL
Unsuccessful AR
1=Unsuccess
LOCKED
Lockout status
1=Lockout
READY
Reclose ready
1=Ready
ACTIVE
Reclose active
1=Active
DISCR_INPRO
Discr.time in progress
1=In progress
Table continues on next page
Recloser Protection and Control RER615
Point List Manual
37
Section 2
Modbus data mappings
BitA
RegA
IEC 61850 name
3068
191.12
.PrgCutOut.stVal
3069
191.13
.mcd
3070
191.14
.FrqOpAlm.stVal
3071
191.15
.mcd
3072
192.00
.RclTmStr.stVal
3073
192.01
.mcd
3074
192.02
.ProCrd.stVal
3075
192.03
.mcd
3076
192.04
.CBManCls.stVal
3077
192.05
.mcd
3078
192.06
.Op.general
3079
192.07
.mcd
3080
192.08
.OpOpn.general
3081
192.09
.mcd
3082
192.10
.UnsCBCls.stVal
3083
192.11
.mcd
3084
192.12
.WtMstr.stVal
3085
192.13
.mcd
2.3.59
Table 62:
1MRS757822 B
SA name
Description
Values
CUTOUT_INPRO
Cutout time in progress
1=In progress
FRQ_OP_ALM
Frequent op. Alarm
1=Alarm
Reclaim time started
Protection coordination
1=In progress
MAN_CB_CL
CB manually closed
1=CB closed
CLOSE_CB
Operate (close XCBR)
1=Close CB
OPEN_CB
Operate (open XCBR)
1=Open CB
UNSUC_CB
CB closing failed
1=Failed
CMD_WAIT
Master signal to follower
1=Signal
LD0.SECRSYN1 Synchrocheck (1)
LD0.SECRSYN1 Synchrocheck (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.SECRSYN1
3882
242.10
.SynPrg
3883
242.11
.mcd
3884
242.12
.FailCmd
3885
242.13
.mcd
3886
242.14
.FailSyn
3887
242.15
.mcd
2.3.60
Table 63:
BitA
SYNC_INPRO
Synch. in progress
1=In progress
CMD_FAIL_AL
Close request fail
1=Failed
CL_FAIL_AL
Close cmd fail
1=Failed
LD0.SSCBR1 Circuit breaker (1) condition monitoring
LD0.SSCBR1 Circuit breaker (1) condition monitoring
RegA
IEC 61850 name
SA name
Description
Values
LD0.SSCBR1
2848
178.00
.OpnAlm.stVal
TRV_T_OP_ALM
Opn travel time alarm
1=Alarm
2849
178.01
.ClsAlm.stVal
TRV_T_CL_ALM
Cls travel time alarm
1=Alarm
2850
178.02
.SprChaAlm.stVal
SPR_CHR_ALM
Spring charge alarm
1=Alarm
Table continues on next page
38
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
BitA
RegA
IEC 61850 name
SA name
Description
Values
2851
178.03
.OpNumAlm.stVal
OPR_ALM
CB operations alarm
1=Alarm
2852
178.04
.OpNumLO.stVal
OPR_LO
CB operations lockout
1=Lockout
2853
178.05
.LonTmAlm.stVal
MON_ALM
CB inactive alarm
1=Alarm
2854
178.06
.PresAlm.stVal
PRES_ALM
Low pressure alarm
1=Alarm
2855
178.07
.PresLO.stVal
PRES_LO
Low pressure lockout
1=Lockout
2856
178.08
.APwrAlm.stVal
IPOW_ALM
Lyt alarm
1=Alarm
2857
178.09
.APwrLO.stVal
IPOW_LO
Lyt lockout
1=Lockout
2858
178.10
.CBLifAlm.stVal
CB_LIFE_ALM
CB lifetime alarm
1=Alarm
2.3.61
Table 64:
BitA
LD0.TCSSCBR1 Trip circuit supervision (1)
LD0.TCSSCBR1 Trip circuit supervision (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.TCSSCBR1
2780
173.12
.CirAlm.stVal
2781
173.13
.mcd
2.3.62
Table 65:
BitA
ALARM
Supervision alarm
1=Alarm
LD0.TCSSCBR2 Trip circuit supervision (2)
LD0.TCSSCBR2 Trip circuit supervision (2)
RegA
IEC 61850 name
SA name
Description
Values
LD0.TCSSCBR2
2782
173.14
.CirAlm.stVal
2783
173.15
.mcd
2.3.63
Table 66:
BitA
ALARM
Supervision alarm
1=Alarm
LD0.SEQRFUF1 Fuse failure protection (1)
LD0.SEQRFUF1 Fuse failure protection (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.SEQRFUF1
2996
187.04
.Str.general
2997
187.05
.mcd
2998
187.06
.Str3Ph.general
2999
187.07
.mcd
Recloser Protection and Control RER615
Point List Manual
FUSEF_U
Start
1=Start
FUSEF_3PH
3-phase start
1=Start
39
Section 2
Modbus data mappings
2.3.64
1MRS757822 B
LD0.MDSOPT1 Generic operation time supervision (1)
Since the register size is 16 bits, the value saturates at 65535 hours (approximately
7.5 years). Alternatively, a 32-bit user-definable register can be made of this data to
cover the whole 300 000 hours (34 years) range. The value can also, for example,
be rescaled to show “total operation days” instead by changing the scale factor
from 1 to 1/24 = 0.0417.
Table 67:
BitA
LD0.MDSOPT1 Generic operation time supervision (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.MDSOPT1
3308
205.12
OpTmWrn.stVal
3309
205.13
.mcd
3310
205.14
OpTmAlm.stVal
3311
205.15
.mcd
2.3.65
Table 68:
BitA
WARNING
Op. time warning
1=Warning
ALARM
Op. time alarm
1=Alarm
LD0.PHSVPR1 Voltage presence supervision (1)
LD0.PHSVPR1 Voltage presence supervision (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.PHSVPR1
3960
247.08
.VLiv.stVal
3961
247.09
.mcd
3962
247.10
.VLivPhsA.stVal
3963
247.11
.mcd
3964
247.12
.VLivPhsB.stVal
3965
247.13
.mcd
3966
247.14
.VLivPhsC.stVal
3967
247.15
.mcd
3968
248.00
.VDea.stVal
3969
248.01
.mcd
3970
248.02
.VDeaPhsA.stVal
3971
248.03
.mcd
3972
248.04
.VDeaPhsB.stVal
3973
248.05
.mcd
3974
248.06
.VDeaPhsC.stVal
3975
248.07
.mcd
40
U_LIVE
High voltage presence
1=High voltage
U_A_AB_LIVE
High phsA or phsAB voltage
1=High voltage
U_B_BC_LIVE
High phsB or phsBC voltage
1=High voltage
U_C_CA_LIVE
High phsC or phsCA voltage
1=High voltage
U_DEAD
Low voltage presence
1=Low voltage
U_A_AB_DEAD
Low phsA or phsAB voltage
1=Low voltage
U_B_BC_DEAD
Low phsB or phsBC voltage
1=Low voltage
U_C_CA_DEAD
Low phsC or phsCA voltage
1=Low voltage
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
2.3.66
Table 69:
BitA
LD0.CMMXU1 Phase current limit supervision (1)
LD0.CMMXU1 Phase current limit supervision (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.CMMXU1
2752
172.00
.HiAlm.stVal
2753
172.01
.mcd
2754
172.02
.HiWrn.stVal
2755
172.03
.mcd
2756
172.04
.LoWrn.stVal
2757
172.05
.mcd
2758
172.06
.LoAlm.stVal
2759
172.07
.mcd
2.3.67
Table 70:
BitA
HIGH_ALARM
High alarm
1=Alarm
HIGH_WARN
High warning
1=Warning
LOW_WARN
Low warning
1=Warning
LOW_ALARM
Low alarm
1=Alarm
LD0.RESCMMXU1 Residual current limit supervision (1)
LD0.RESCMMXU1 Residual current limit supervision (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.RESCMMXU1
2760
172.08
.HiAlm.stVal
2761
172.09
.mcd
2762
172.10
.HiWrn.stVal
2763
172.11
.mcd
2.3.68
Table 71:
BitA
HIGH_ALARM
High alarm
1=Alarm
HIGH_WARN
High warning
1=Warning
LD0.VMMXU1 Phase voltage limit supervision (1)
LD0.VMMXU1 Phase voltage limit supervision (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.VMMXU1
2784
174.00
.HiAlm.stVal
2785
174.01
.mcd
2786
174.02
.HiWrn.stVal
2787
174.03
.mcd
2788
174.04
.LoWrn.stVal
2789
174.05
.mcd
2790
174.06
.LoAlm.stVal
2791
174.07
.mcd
Recloser Protection and Control RER615
Point List Manual
HIGH_ALARM
High alarm
1=Alarm
HIGH_WARN
High warning
1=Warning
LOW_WARN
Low warning
1=Warning
LOW_ALARM
Low alarm
1=Alarm
41
Section 2
Modbus data mappings
2.3.69
Table 72:
BitA
1MRS757822 B
LD0.VMMXU2 Phase voltage limit supervision (2)
LD0.VMMXU2 Phase voltage limit supervision (2)
RegA
IEC 61850 name
SA name
Description
Values
LD0.VMMXU2
3360
210.00
.HiAlm.stVal
3361
210.01
.mcd
3362
210.02
.HiWrn.stVal
3363
210.03
.mcd
3364
210.04
.LoWrn.stVal
3365
210.05
.mcd
3366
210.06
.LoAlm.stVal
3367
210.07
.mcd
2.3.70
Table 73:
BitA
HIGH_ALARM
High alarm
1=Alarm
HIGH_WARN
High warning
1=Warning
LOW_WARN
Low warning
1=Warning
LOW_ALARM
Low alarm
1=Alarm
LD0.MVGAPC1 Multipurpose binary inputs (1)
LD0.MVGAPC1 Multipurpose binary inputs (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.MVGAPC1
3536
221.00
.Q1.stVal
3537
221.01
.mcd
3538
221.02
.Q2.stVal
3539
221.03
.mcd
3540
221.04
.Q3.stVal
3541
221.05
.mcd
3542
221.06
.Q4.stVal
3543
221.07
.mcd
3544
221.08
.Q5.stVal
3545
221.09
.mcd
3546
221.10
.Q6.stVal
3547
221.11
.mcd
3548
221.12
.Q7.stVal
3549
221.13
.mcd
3550
221.14
.Q8.stVal
3551
221.15
.mcd
42
Input 1
0/1=Off/On
Input 2
0/1=Off/On
Input 3
0/1=Off/On
Input 4
0/1=Off/On
Input 5
0/1=Off/On
Input 6
0/1=Off/On
Input 7
0/1=Off/On
Input 8
0/1=Off/On
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
2.3.71
Table 74:
BitA
LD0.MVGAPC2 Multipurpose binary inputs (2)
LD0.MVGAPC2 Multipurpose binary inputs (2)
RegA
IEC 61850 name
SA name
Description
Values
LD0.MVGAPC2
3552
222.00
.Q1.stVal
3553
222.01
.mcd
3554
222.02
.Q2.stVal
3555
222.03
.mcd
3556
222.04
.Q3.stVal
3557
222.05
.mcd
3558
222.06
.Q4.stVal
3559
222.07
.mcd
3560
222.08
.Q5.stVal
3561
222.09
.mcd
3562
222.10
.Q6.stVal
3563
222.11
.mcd
3564
222.12
.Q7.stVal
3565
222.13
.mcd
3566
222.14
.Q8.stVal
3567
222.15
.mcd
2.3.72
Table 75:
BitA
Input 1
0/1=Off/On
Input 2
0/1=Off/On
Input 3
0/1=Off/On
Input 4
0/1=Off/On
Input 5
0/1=Off/On
Input 6
0/1=Off/On
Input 7
0/1=Off/On
Input 8
0/1=Off/On
LD0.SPCGGIO1 Multipurpose binary output states (1)
LD0.SPCGGIO1 Multipurpose binary output states (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.SPCGGIO1
3600
225.00
.SPCS01.stVal
3601
225.01
.mcd
3602
225.02
.SPCS02.stVal
3603
225.03
.mcd
3604
225.04
.SPCS03.stVal
3605
225.05
.mcd
3606
225.06
.SPCS04.stVal
3607
225.07
.mcd
3608
225.08
.SPCS05.stVal
3609
225.09
.mcd
3610
225.10
.SPCS06.stVal
3611
225.11
.mcd
3612
225.12
.SPCS07.stVal
Ouput state 1
0/1=Off/On
Ouput state 2
0/1=Off/On
Ouput state 3
0/1=Off/On
Ouput state 4
0/1=Off/On
Ouput state 5
0/1=Off/On
Ouput state 6
0/1=Off/On
Ouput state 7
0/1=Off/On
Table continues on next page
Recloser Protection and Control RER615
Point List Manual
43
Section 2
Modbus data mappings
BitA
RegA
IEC 61850 name
3613
225.13
.mcd
3614
225.14
.SPCS08.stVal
3615
225.15
.mcd
3616
226.00
.SPCS09.stVal
3617
226.01
.mcd
3618
226.02
.SPCS10.stVal
3619
226.03
.mcd
3620
226.04
.SPCS11.stVal
3621
226.05
.mcd
3622
226.06
.SPCS12.stVal
3623
226.07
.mcd
3624
226.08
.SPCS13.stVal
3625
226.09
.mcd
3626
226.10
.SPCS14.stVal
3627
226.11
.mcd
3628
226.12
.SPCS15.stVal
3629
226.13
.mcd
3630
226.14
.SPCS16.stVal
3631
226.15
.mcd
2.3.73
Table 76:
BitA
1MRS757822 B
SA name
Description
Values
Ouput state 8
0/1=Off/On
Ouput state 9
0/1=Off/On
Ouput state 10
0/1=Off/On
Ouput state 11
0/1=Off/On
Ouput state 12
0/1=Off/On
Ouput state 13
0/1=Off/On
Ouput state 14
0/1=Off/On
Ouput state 15
0/1=Off/On
Ouput state 16
0/1=Off/On
LD0.SPCGGIO2 Multipurpose binary output states (2)
LD0.SPCGGIO2 Multipurpose binary output states (2)
RegA
IEC 61850 name
SA name
Description
Values
LD0.SPCGGIO2
3632
227.00
.SPCS01.stVal
3633
227.01
.mcd
3634
227.02
.SPCS02.stVal
3635
227.03
.mcd
3636
227.04
.SPCS03.stVal
3637
227.05
.mcd
3638
227.06
.SPCS04.stVal
3639
227.07
.mcd
3640
227.08
.SPCS05.stVal
3641
227.09
.mcd
3642
227.10
.SPCS06.stVal
3643
227.11
.mcd
3644
227.12
.SPCS07.stVal
3645
227.13
.mcd
Ouput state 1
0/1=Off/On
Ouput state 2
0/1=Off/On
Ouput state 3
0/1=Off/On
Ouput state 4
0/1=Off/On
Ouput state 5
0/1=Off/On
Ouput state 6
0/1=Off/On
Ouput state 7
0/1=Off/On
Table continues on next page
44
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
BitA
RegA
IEC 61850 name
3646
227.14
.SPCS08.stVal
3647
227.15
.mcd
3648
228.00
.SPCS09.stVal
3649
228.01
.mcd
3650
228.02
.SPCS10.stVal
3651
228.03
.mcd
3652
228.04
.SPCS11.stVal
3653
228.05
.mcd
3654
228.06
.SPCS12.stVal
3655
228.07
.mcd
3656
228.08
.SPCS13.stVal
3657
228.09
.mcd
3658
228.10
.SPCS14.stVal
3659
228.11
.mcd
3660
228.12
.SPCS15.stVal
3661
228.13
.mcd
3662
228.14
.SPCS16.stVal
3663
228.15
.mcd
2.3.74
Table 77:
BitA
SA name
Description
Values
Ouput state 8
0/1=Off/On
Ouput state 9
0/1=Off/On
Ouput state 10
0/1=Off/On
Ouput state 11
0/1=Off/On
Ouput state 12
0/1=Off/On
Ouput state 13
0/1=Off/On
Ouput state 14
0/1=Off/On
Ouput state 15
0/1=Off/On
Ouput state 16
0/1=Off/On
LD0.SPCRGGIO1 Multipurpose binary output states (1)
LD0.SPCRGGIO1 Multipurpose binary output states (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.SPCRGGIO1
4080
255.00
.SPCS01.stVal
4081
255.01
.mcd
4082
255.02
.SPCS02.stVal
4083
255.03
.mcd
4084
255.04
.SPCS03.stVal
4085
255.05
.mcd
4086
255.06
.SPCS04.stVal
4087
255.07
.mcd
4088
255.08
.SPCS05.stVal
4089
255.09
.mcd
4090
255.10
.SPCS06.stVal
4091
255.11
.mcd
4092
255.12
.SPCS07.stVal
4093
255.13
.mcd
4094
255.14
.SPCS08.stVal
Ouput state 1
0/1=Off/On
Ouput state 2
0/1=Off/On
Ouput state 3
0/1=Off/On
Ouput state 4
0/1=Off/On
Ouput state 5
0/1=Off/On
Ouput state 6
0/1=Off/On
Ouput state 7
0/1=Off/On
Ouput state 8
0/1=Off/On
Table continues on next page
Recloser Protection and Control RER615
Point List Manual
45
Section 2
Modbus data mappings
BitA
RegA
IEC 61850 name
4095
255.15
.mcd
4096
256.00
.SPCS09.stVal
4097
256.01
.mcd
4098
256.02
.SPCS10.stVal
4099
256.03
.mcd
4100
256.04
.SPCS11.stVal
4101
256.05
.mcd
4102
256.06
.SPCS12.stVal
4103
256.07
.mcd
4104
256.08
.SPCS13.stVal
4105
256.09
.mcd
4106
256.10
.SPCS14.stVal
4107
256.11
.mcd
4108
256.12
.SPCS15.stVal
4109
256.13
.mcd
4110
256.14
.SPCS16.stVal
4111
256.15
.mcd
2.3.75
Table 78:
BitA
1MRS757822 B
SA name
Description
Values
Ouput state 9
0/1=Off/On
Ouput state 10
0/1=Off/On
Ouput state 11
0/1=Off/On
Ouput state 12
0/1=Off/On
Ouput state 13
0/1=Off/On
Ouput state 14
0/1=Off/On
Ouput state 15
0/1=Off/On
Ouput state 16
0/1=Off/On
LD0.SPCLGGIO1 Multipurpose binary output states (1)
LD0.SPCLGGIO1 Multipurpose binary output states (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.SPCLGGIO1
4048
253.00
.SPCS01.stVal
4049
253.01
.mcd
4050
253.02
.SPCS02.stVal
4051
253.03
.mcd
4052
253.04
.SPCS03.stVal
4053
253.05
.mcd
4054
253.06
.SPCS04.stVal
4055
253.07
.mcd
4056
253.08
.SPCS05.stVal
4057
253.09
.mcd
4058
253.10
.SPCS06.stVal
4059
253.11
.mcd
4060
253.12
.SPCS07.stVal
4061
253.13
.mcd
4062
253.14
.SPCS08.stVal
4063
253.15
.mcd
Ouput state 1
0/1=Off/On
Ouput state 2
0/1=Off/On
Ouput state 3
0/1=Off/On
Ouput state 4
0/1=Off/On
Ouput state 5
0/1=Off/On
Ouput state 6
0/1=Off/On
Ouput state 7
0/1=Off/On
Ouput state 8
0/1=Off/On
Table continues on next page
46
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
BitA
RegA
IEC 61850 name
4064
254.00
.SPCS09.stVal
4065
254.01
.mcd
4066
254.02
.SPCS10.stVal
4067
254.03
.mcd
4068
254.04
.SPCS11.stVal
4069
254.05
.mcd
4070
254.06
.SPCS12.stVal
4071
254.07
.mcd
4072
254.08
.SPCS13.stVal
4073
254.09
.mcd
4074
254.10
.SPCS14.stVal
4075
254.11
.mcd
4076
254.12
.SPCS15.stVal
4077
254.13
.mcd
4078
254.14
.SPCS16.stVal
4079
254.15
.mcd
2.3.76
Table 79:
BitA
SA name
Description
Values
Ouput state 9
0/1=Off/On
Ouput state 10
0/1=Off/On
Ouput state 11
0/1=Off/On
Ouput state 12
0/1=Off/On
Ouput state 13
0/1=Off/On
Ouput state 14
0/1=Off/On
Ouput state 15
0/1=Off/On
Ouput state 16
0/1=Off/On
LD0.GSEGGIO1 Goose supervision (1)
LD0.GSEGGIO1 Goose supervision (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.GSEGGIO1
2734
170.14
2.3.77
Table 80:
BitA
.Alm.stVal
ALARM
General alarm
0/1=Off/On
LD0.LEDPTRC1 Global conditioning (1)
LD0.LEDPTRC1 Global conditioning (1)
RegA
IEC 61850 name
SA name
Description
Values
LD0.LEDPTRC1
2736
171.00
.Str.general
2737
171.01
.mcd
2738
171.02
.Op.general
2739
171.03
.mcd
2.3.78
-
Global start
1=Start
-
Global operate
1=Operate
LD0.LEDGGIO1 Indication LED states OFF/ColorX
These LED indication points interpret the case when an indication signal is wired
to either the OK or ALARM input of the LED function block. The default color for
Recloser Protection and Control RER615
Point List Manual
47
Section 2
Modbus data mappings
1MRS757822 B
ALARM is red and green for OK. Colors can, however, be reconfigured with a
setting parameter.
LEDx
Signal
OK
ALARM
RESET
LEDx
Signal
OK
ALARM
RESET
GUID-775477F8-C2DE-4138-B2C0-6B7C2774D4D2 V1 EN
Figure 2:
Table 81:
BitA
Signal wired to either OK or Alarm input
LD0.LEDGGIO1 Indication LED states OFF/ColorX
RegA
IEC 61850 name
SA name
Description
Values
LD0.LEDGGIO1
2768
173.00
.ISCSO1.stVal
-
LED 1 state
0/1=Off/Color
2769
173.01
.ISCSO2.stVal
-
LED 2 state
0/1=Off/Color
2770
173.02
.ISCSO3.stVal
-
LED 3 state
0/1=Off/Color
2771
173.03
.ISCSO4.stVal
-
LED 4 state
0/1=Off/Color
2772
173.04
.ISCSO5.stVal
-
LED 5 state
0/1=Off/Color
2773
173.05
.ISCSO6.stVal
-
LED 6 state
0/1=Off/Color
2774
173.06
.ISCSO7.stVal
-
LED 7 state
0/1=Off/Color
2775
173.07
.ISCSO8.stVal
-
LED 8 state
0/1=Off/Color
2776
173.08
.ISCSO9.stVal
-
LED 9 state
0/1=Off/Color
2777
173.09
.ISCSO10.stVal
-
LED 10 state
0/1=Off/Color
2778
173.10
.ISCSO11.stVal
-
LED 11 state
0/1=Off/Color
2779
173.11
<reserved>
2.3.79
0
LD0.LEDGGIO1 Indication LED states Color1/Color2
These LED indication points interpret the case when a signal is wired to both the
OK and ALARM inputs, but inverted to the other. This means that the LED toggles
between red and green colors. The default color for ALARM is red and green for
OK. Colors can, however, be reconfigured with a setting parameter.
48
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
LEDx
Signal
OK
ALARM
RESET
NOT
GUID-2AE4D47A-2BBD-4422-A81C-CF2EB7473379 V1 EN
Figure 3:
Signal wired to both OK and ALARM inputs – inverted to the other
If the OK and ALARM inputs are wired to separate indication
signals, the LED will have three legal states and cannot be
expressed with one bit only. In this case, it is possible to combine
this LED bit interpretation with the corresponding value from the
other LED state interpretation.
LEDx
Signal 1
Signal 2
OK
ALARM
RESET
GUID-051741E8-4D66-412C-BA0A-0B849B5E58F2 V1 EN
Figure 4:
Table 82:
BitA
Separate signals wired to OK and ALARM inputs
LD0.LEDGGIO1 Indication LED states Color1/Color2
RegA
IEC 61850 name
SA name
Description
Values
LD0.LEDGGIO1
3520
220.00
.ISCSO1.stVal
-
LED 1 state
0/1=Color1/2
3521
220.01
.ISCSO2.stVal
-
LED 2 state
0/1=Color1/2
3522
220.02
.ISCSO3.stVal
-
LED 3 state
0/1=Color1/2
3523
220.03
.ISCSO4.stVal
-
LED 4 state
0/1=Color1/2
3524
220.04
.ISCSO5.stVal
-
LED 5 state
0/1=Color1/2
3525
220.05
.ISCSO6.stVal
-
LED 6 state
0/1=Color1/2
3526
220.06
.ISCSO7.stVal
-
LED 7 state
0/1=Color1/2
3527
220.07
.ISCSO8.stVal
-
LED 8 state
0/1=Color1/2
3528
220.08
.ISCSO9.stVal
-
LED 9 state
0/1=Color1/2
3529
220.09
.ISCSO10.stVal
-
LED 10 state
0/1=Color1/2
3530
220.10
.ISCSO11.stVal
-
LED 11 state
0/1=Color1/2
3531
220.11
<reserved>
Recloser Protection and Control RER615
Point List Manual
0
49
Section 2
Modbus data mappings
2.3.80
Table 83:
BitA
1MRS757822 B
CTRL.CBCSWI1 Circuit breaker (1) mom. position
CTRL.CBCSWI1 Circuit breaker (1) mom. position
RegA
IEC 61850 name
SA name
CTRL.CBCSWI1
POSITION
Description
Values
2804
175.04
.Pos.stVal.Close
-
Close bit
1=Close
2805
175.05
.Pos.stVal.Open
-
Open bit
1=Open
2806
175.06
.Pos.stVal.Fault
-
Fault bit
1=Pos(00/11)
2.3.81
Table 84:
BitA
CTRL.CBCSWI1 Circuit breaker (1) mom+mcd position
CTRL.CBCSWI1 Circuit breaker (1) mom+mcd position
RegA
IEC 61850 name
CTRL.CBCSWI1
2816
176.00
.Pos.stVal.Close
2817
176.01
.mcd
2818
176.02
.Pos.stVal.Open
2819
176.03
.mcd
2820
176.04
< reserved >
2821
176.05
< reserved >
2822
176.06
.Pos.stSeld
2823
176.07
.mcd
2.3.82
Table 85:
BitA
SA name
Description
Values
POSITION
SELECTED
Close bit
1=Close
Open bit
1=Open
CB selected for control
1=Selected
CTRL.CBCILO1 Circuit breaker (1) enable signals
CTRL.CBCILO1 Circuit breaker (1) enable signals
RegA
IEC 61850 name
SA name
Description
Values
CTRL.CBCILO1
2824
176.08
.EnaOpn.stVal
ENA_OPEN
Open enabled
1=Enabled
2825
176.09
.EnaCls.stVal
ENA_CLOSE
Close enabled
1=Enabled
2.3.83
Table 86:
BitA
LD0.XGGIO130 Physical I/O states (BIO card X130)
LD0.XGGIO130 Physical I/O states (BIO card X130)
RegA
IEC 61850 name
SA name
Description
Values
LD0.XGGIO130
3184
199.00
.Ind1.stVal
3185
199.01
.mcd
3186
199.02
.Ind2.stVal
X130-Input 1 State
0/1=Off/On
X130-Input 2 State
0/1=Off/On
Table continues on next page
50
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
BitA
RegA
IEC 61850 name
3187
199.03
.mcd
3188
199.04
.Ind3.stVal
3189
199.05
.mcd
3190
199.06
.Ind4.stVal
3191
199.07
.mcd
3192
199.08
.Ind5.stVal
3193
199.09
.mcd
3194
199.10
.Ind6.stVal
3195
199.11
.mcd
3264
204.00
.SPCSO1.stVal
3265
204.01
.mcd
3266
204.02
.SPCSO2.stVal
3267
204.03
.mcd
3268
204.04
.SPCSO3.stVal
3269
204.05
.mcd
2.3.84
Table 87:
BitA
SA name
Description
Values
X130-Input 3 State
0/1=Off/On
X130-Input 4 State
0/1=Off/On
X130-Input 5 State
0/1=Off/On
X130-Input 6 State
0/1=Off/On
X130-Output 1 State
0/1=Off/On
X130-Output 2 State
0/1=Off/On
X130-Output 3 State
0/1=Off/On
LD0.XGGIO120 Physical I/O states (AIM card X120)
LD0.XGGIO120 Physical I/O states (AIM card X120)
RegA
IEC 61850 name
SA name
Description
Values
LD0.XGGIO120
3200
200.00
.Ind1.stVal
3201
200.01
.mcd
3202
200.02
.Ind2.stVal
3203
200.03
.mcd
3204
200.04
.Ind3.stVal
3205
200.05
.mcd
3206
200.06
.Ind4.stVal
3207
200.07
.mcd
2.3.85
Table 88:
BitA
X120-Input 1 State
0/1=Off/On
X120-Input 2 State
0/1=Off/On
X120-Input 3 State
0/1=Off/On
X120-Input 4 State
0/1=Off/On
LD0.XGGIO110 Physical I/O states (BIO card X110)
LD0.XGGIO110 Physical I/O states (BIO card X110)
RegA
IEC 61850 name
SA name
Description
Values
LD0.XGGIO110
3216
201.00
.Ind1.stVal
3217
201.01
.mcd
3218
201.02
.Ind2.stVal
3219
201.03
.mcd
X110-Input 1 State
0/1=Off/On
X110-Input 2 State
0/1=Off/On
Table continues on next page
Recloser Protection and Control RER615
Point List Manual
51
Section 2
Modbus data mappings
BitA
RegA
IEC 61850 name
3220
201.04
.Ind3.stVal
3221
201.05
.mcd
3222
201.06
.Ind4.stVal
3223
201.07
.mcd
3224
201.08
.Ind5.stVal
3225
201.09
.mcd
3226
201.10
.Ind6.stVal
3227
201.11
.mcd
3228
201.12
.Ind7.stVal
3229
201.13
.mcd
3230
201.14
.Ind8.stVal
3231
201.15
.mcd
3232
202.00
.SPCSO1.stVal
3233
202.01
.mcd
3234
202.02
.SPCSO2.stVal
3235
202.03
.mcd
3236
202.04
.SPCSO3.stVal
3237
202.05
.mcd
3238
202.06
.SPCSO4.stVal
3239
202.07
.mcd
2.3.86
Table 89:
BitA
1MRS757822 B
SA name
Description
Values
X110-Input 3 State
0/1=Off/On
X110-Input 4 State
0/1=Off/On
X110-Input 5 State
0/1=Off/On
X110-Input 6 State
0/1=Off/On
X110-Input 7 State
0/1=Off/On
X110-Input 8 State
0/1=Off/On
X110-Output 1 State
0/1=Off/On
X110-Output 2 State
0/1=Off/On
X110-Output 3 State
0/1=Off/On
X110-Output 4 State
0/1=Off/On
LD0.XGGIO100 Physical I/O states (PSM card X100)
LD0.XGGIO100 Physical I/O states (PSM card X100)
RegA
IEC 61850 name
SA name
Description
Values
LD0.XGGIO100
3248
203.00
.SPCSO1.stVal
3249
203.01
.mcd
3250
203.02
.SPCSO2.stVal
3251
203.03
.mcd
3252
203.04
.SPCSO3.stVal
3253
203.05
.mcd
3254
203.06
.SPCSO4.stVal
3255
203.07
.mcd
3256
203.08
.SPCSO5.stVal
3257
203.09
.mcd
3258
203.10
.SPCSO6.stVal
3259
203.11
.mcd
52
X100-Output 1 State
0/1=Off/On
X100-Output 2 State
0/1=Off/On
X100-Output 3 State
0/1=Off/On
X100-Output 4 State
0/1=Off/On
X100-Output 5 State
0/1=Off/On
X100-Output 6 State
0/1=Off/On
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
2.3.87
LD0.XAGGIO130 Physical I/O states (AIM card XA130)
Table 90:
BitA
LD0.XAGGIO130 Physical I/O states (AIM card XA130)
RegA
IEC 61850 name
SA name
Description
Values
LD0.XAGGIO130
3280
205.00
.Ind1.stVal
3281
205.01
.mcd
3282
205.02
.Ind2.stVal
3283
205.03
.mcd
3284
205.04
.Ind3.stVal
3285
205.05
.mcd
3286
205.06
.Ind4.stVal
3287
205.07
.mcd
2.4
XA130-Input 1 State
0/1=Off/On
XA130-Input 2 State
0/1=Off/On
XA130-Input 3 State
0/1=Off/On
XA130-Input 4 State
0/1=Off/On
Registers
Table 91:
Column name
2.4.1
Explanations of columns in register tables
Description
RegA
Default 3X and 4X register address for the data.
Type
Type of the register. The alternatives are u16, u32 (unsigned 16 and 32 bits
integer) or i16, i32 (signed 16 and 32 bit integer).
Scale
Scale factor as default. Also, an adjustable offset value exists that is set to 0 by
default.
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name
The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description
Short description of the signal. See the technical manual for more information.
Also, if a register is writable, it is stated here.
Values
The value range of the original IEC 61850 value, that is, before scaling.
User definable registers [Alt.1], visible on 3x and 4x
Table 92:
User definable registers [Alt.1], visible on 3x and 4x
RegA
Type
(0)
Reg
< not mappable- not visible >
1
Reg
User Register 1
2
Reg
User Register 2
3
:
:
Scale
IEC 61850 name
SA name
Description
Values
Table continues on next page
Recloser Protection and Control RER615
Point List Manual
53
Section 2
Modbus data mappings
RegA
Type
Scale
IEC 61850 name
1MRS757822 B
SA name
Description
:
:
:
:
:
:
127
Reg
User Register 127
2.4.2
User definable bits [Alt.2], visible on 0x,1x,3x and 4x
Table 93:
User definable bits [Alt.2], visible on 0x,1x,3x and 4x
BitA
Type
(0)
Bit
< not mappable - not visible >
1
Bit
Usr Reg 1.Bit 01
2
Bit
Usr Reg 1.Bit 02
3
Bit
Usr Reg 1.Bit 03
:
:
:
:
:
:
15
Bit
Usr Reg 1.Bit 15
16
Bit
Usr Reg 2.Bit 00
17
Bit
Usr Reg 2.Bit 01
:
:
:
:
:
:
2046
Bit
Usr Reg 127.Bit 14
2047
Bit
Usr Reg 127.Bit 15
Scale
2.4.3
IEC 61850 name
SA name
Description
Values
SSR1 System status register (1) device health
Table 94:
RegA
Values
SSR1 System status register (1) device health
Type
Scale
IEC 61850 name
SA name
Description
Values
128.00
Bit
Device global error
1=Error
128.01
Bit
Device global warning
1=Warning
128.02
Bit
< reserved >
0
128.03
Bit
< reserved >
0
128.04
Bit
< reserved >
0
128.05
Bit
< reserved >
0
128.06
Bit
< reserved >
0
128.07
Bit
< reserved >
0
128.08
Bit
< reserved >
0
128.09
Bit
< reserved >
0
128.10
Bit
< reserved >
0
128.11
Bit
< reserved >
0
128.12
Bit
< reserved >
0
Table continues on next page
54
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
128.13
Bit
< reserved >
0
128.14
Bit
< reserved >
0
128.15
Bit
< reserved >
0
2.4.4
SSR2 System status register (2) IED mode and state
Table 95:
RegA
SSR2 System status register (2) IED mode and state
Type
Scale
IEC 61850 name
SA name
Description
Values
129.00
Bit
Device test mode
1=Test mode
129.01
Bit
< reserved >
0
129.02
Bit
Remote/Local state
0/1=Rem/Loc
Active setting group
SG=1...6
129.03
Bit
- bit 0
129.04
Bit
- bit 1
129.05
Bit
- bit 2
129.06
Bit
IED timesynch failure
1=Failure
129.07
Bit
< reserved >
0
129.08
Bit
Last reset cause a
1=Cold start
129.09
Bit
Last reset cause b
1=Watchdog
129.10
Bit
Last reset cause c
1=Warm start
129.11
Bit
< reserved >
0
129.12
Bit
< reserved >
0
129.13
Bit
< reserved >
0
129.14
Bit
< reserved >
0
129.15
Bit
< reserved >
0
2.4.5
SSR3 System status register (3) data available 1 (clientdependent)
Table 96:
RegA
SSR3 System status register (3) data available 1 (client-dependent)
Type
Scale
IEC 61850 name
SA name
Description
Values
130.00
Bit
Unread event records available
1=Available
130.01
Bit
Unread fault records available
1=Available
130.02
Bit
< reserved >
0
130.03
Bit
< reserved >
0
130.04
Bit
Any momentary bit updated
1=Updated
130.05
Bit
Any mcd bit set
1=Set
130.06
Bit
Device restart bit
1=IED restart
130.07
Bit
< reserved >
0
Table continues on next page
Recloser Protection and Control RER615
Point List Manual
55
Section 2
Modbus data mappings
RegA
Type
Scale
IEC 61850 name
1MRS757822 B
SA name
Description
Values
130.08
Bit
Event record selected
1=Selected
130.09
Bit
Fault record selected
1=Selected
130.10
Bit
< reserved >
0
130.11
Bit
< reserved >
0
130.12
Bit
< reserved >
0
130.13
Bit
< reserved >
0
130.14
Bit
< reserved >
0
130.15
Bit
< reserved >
0
2.4.6
SSR4 System status register (4) data available 2 (clientdependent - user-definable)
Table 97:
RegA
SSR4 System status register (4) data available 2 (client-dependent - user-definable)
Type
Scale
IEC 61850 name
SA name
Description
Values
131.00
Bit
Data category 1 has changed
1=Changed
131.01
Bit
Data category 2 has changed
1=Changed
131.02
Bit
Data category 3 has changed
1=Changed
131.03
Bit
Data category 4 has changed
1=Changed
131.04
Bit
Data category 5 has changed
1=Changed
131.05
Bit
Data category 6 has changed
1=Changed
131.06
Bit
Data category 7 has changed
1=Changed
131.07
Bit
Data category 8 has changed
1=Changed
131.08
Bit
Data category 9 has changed
1=Changed
131.09
Bit
Data category 10 has changed
1=Changed
131.10
Bit
Data category 11 has changed
1=Changed
131.11
Bit
Data category 12 has changed
1=Changed
131.12
Bit
Data category 13 has changed
1=Changed
131.13
Bit
Data category 14 has changed
1=Changed
131.14
Bit
Data category 15 has changed
1=Changed
131.15
Bit
Data category 16 has changed
1=Changed
2.4.7
SSR5 System status register (5) device alive register
Table 98:
SSR5 System status register (5) device alive register
RegA
Type
132
u16
56
Scale
1
IEC 61850 name
SA name
Description
Device alive counter
Values
0...65535
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
2.4.8
SSR6 System status register (6) control command status
(client-dependent)
Table 99:
RegA
SSR6 System status register (6) control command status (client-dependent)
Type
Scale
IEC 61850 name
SA name
Description
Last cmd result code
133.00
Bit
- bit 0
133.01
Bit
- bit 1
133.02
Bit
- bit 2
133.03
Bit
- bit 3
133.04
Bit
- bit 4
133.05
Bit
- bit 5
133.06
Bit
- bit 6
133.07
Bit
- bit 7
Response Type
133.08
Bit
- bit 0
133.09
Bit
- bit 1
Command state
133.10
Bit
- bit 0
133.11
Bit
- bit 1
Cmd sequence number
133.12
Bit
- bit 0
133.13
Bit
- bit 1
133.14
Bit
- bit 2
133.15
Bit
- bit 3
Values
1)
1)
1)
0...15
1) See the technical manual.
2.4.9
LD0.T1PTTR1 Thermal protection values (1)
Table 100:
RegA
LD0.T1PTTR1 Thermal protection values (1)
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.T1PTTR1
146
i16
1
.Tmp.mag
TEMP
Object temperature
-100.0…
9999.9 [C]
147
u16
1
.TmpRl.mag
TEMP_RL
Relative temperature
0.00…99.99
[C]
148
i16
1
.TmpUsed.mag
TEMP_AMB
Ambient temperature
-99…999.99
[C]
149
u16
.001
.TmmsOp.stVal
THERMLEV_ST
Est. time to operate
0…600,000
[ms]
150
u16
.001
.TmmsRecEna.stVal
THERMLEV_END
Est. time to deactivate block
0…600,000
[ms]
Recloser Protection and Control RER615
Point List Manual
57
Section 2
Modbus data mappings
2.4.10
LD0.CMHAI1 Current total demand distortion (1)
Table 101:
RegA
1MRS757822 B
LD0.CMHAI1 Current total demand distortion (1)
Type
Scale
IEC 61850 name
SA name
LD0.CMHAI1
Description
Values
3-second mean value:
2150
u16
100
.TddA.phsA.cVal.mag
3SMHTDD_A
- phsA
0...500.00 [%]
2151
u16
100
.TddA.phsB.cVal.mag
3SMHTDD_B
- phsB
0...500.00 [%]
2152
u16
100
.TddA.phsC.cVal.mag
3SMHTDD_C
- phsC
0...500.00 [%]
Demand value:
2153
u16
100
.DmdTddA.phsA.cVal.m
ag
DMD_TDD_A
- phsA
0...500.00 [%]
2154
u16
100
.DmdTddA.phsB.cVal.m
ag
DMD_TDD_B
- phsB
0...500.00 [%]
2155
u16
100
.DmdTddA.phsC.cVal.m
ag
DMD_TDD_C
- phsC
0...500.00 [%]
Max demand value:
2156
u16
100
.MaxDmdTddA.phsA.cV
al.mag
-
- phsA
0...500.00 [%]
2157
u16
100
.MaxDmdTddA.phsB.cV
al.mag
-
- phsB
0...500.00 [%]
2158
u16
100
.MaxDmdTddA.phsB.cV
al.mag
-
- phsC
0...500.00 [%]
2.4.11
LD0.VMHAI1 Voltage total demand distortion (1)
Table 102:
RegA
LD0.VMHAI1 Voltage total demand distortion (1)
Type
Scale
IEC 61850 name
SA name
LD0.VMHAI1
Description
Values
3-second mean value:
2170
u16
100
.ThdPhV.phsA.cVal.mag
3SMHTHD_A
- phsA
0...500.00 [%]
2171
u16
100
.ThdPhV.phsB.cVal.mag
3SMHTDD_B
- phsB
0...500.00 [%]
2172
u16
100
.ThdPhV.phsC.cVal.mag
3SMHTDD_C
- phsC
0...500.00 [%]
Demand value:
2173
u16
100
.DmdThdPhV.phsA.cVal.
mag
DMD_TDD_A
- phsA
0...500.00 [%]
DMD_TDD_B
- phsB
0...500.00 [%]
DMD_TDD_C
- phsC
0...500.00 [%]
2174
u16
100
.DmdThdPhV.phsB.cVal.
mag
2175
u16
100
.DmdThdPhV.phsC.cVal.
mag
Max demand value:
2176
u16
100
.MaxDmdThdV.phsA.cV
al.mag
-
- phsA
0...500.00 [%]
2177
u16
100
.MaxDmdThdV.phsB.cV
al.mag
-
- phsB
0...500.00 [%]
2178
u16
100
.MaxDmdThdV.phsC.cV
al.mag
-
- phsC
0...500.00 [%]
58
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
2.4.12
LD0.PHQVVR1 Short duration voltage variations (1)
Table 103:
RegA
LD0.PHQVVR1 Short duration voltage variations (1)
Type
Scale
IEC 61850 name
SA name
LD0.PH1QVVR1
2100
u32
1
.SwlInstCnt.stVal
INSTSWELLCNT
u32
1
.SwlMomCnt.stVal
MOMSWELLCNT
2103
2104
u32
1
.SwlTmpCnt.stVal
TEMPSWELLCNT
2105
2106
u32
1
.SwlMaxCnt.stVal
Values
Voltage swell:
2101
2102
Description
MAXDURSWELLC
NT
2107
- Inst counter (high)
0…
- (low word)
2147483647
- Mom counter (high)
0…
- (low word)
2147483647
- Temp counter (high)
0…
- (low word)
2147483647
- Max duration.counter (high)
0…
- (low word)
2147483647
Voltage dip:
2108
u32
1
.DipInstCnt.stVal
INSTDIPCNT
2109
2110
u32
1
.DipMomCnt.stVal
MOMDIPCNT
2111
2112
u32
1
.DipTmpCnt.stVal
TEMPDIPCNT
2113
2114
u32
1
.DipMaxCnt.stVal
MAXDURDIPCNT
2115
- Inst counter (high)
0…
- (low word)
2147483647
- Mom counter (high)
0…
- (low word)
2147483647
- Temp counter (high)
0…
- (low word)
2147483647
- Max duration.counter (high)
0…
- (low word)
2147483647
Voltage interrupts:
2116
u32
1
.IntrMomCnt.stVal
MOMINTCNT
2117
2118
u32
1
.IntrTmpCnt.stVal
TEMPINTCNT
2119
2120
u32
1
.IntrSstCnt.stVal
SUSTINTCNT
2121
2122
u32
1
2.4.13
MAXDURINTCNT
0…
- (low word)
2147483647
- Temp counter (high)
0…
- (low word)
2147483647
- Sustain counter (high)
0…
- (low word)
2147483647
- Max duration.counter (high)
0…
LD0.DARREC1 Autorecloser values (1)
Table 104:
RegA
.IntrMaxCnt.stVal
- Mom counter (high)
LD0.DARREC1 Autorecloser values (1)
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.DARREC1
135
i16
1
.AutoRecSt.stVal
STATUS
AR state
-2...41)
136
u16
1
.ShotPntr.stVal
SHOT_PTR
AR shot pointer value
0...6
137
u16
1
.OpCntRs.stVal
COUNTER
AR operation counter
0...65535
1) See the technical manual.
Recloser Protection and Control RER615
Point List Manual
59
Section 2
Modbus data mappings
2.4.14
LD0.DARREC1 Autorecloser counters (1)
Table 105:
RegA
1MRS757822 B
LD0.DARREC1 Autorecloser counters (1)
Typw
Scale
IEC 61850 name
SA name
Description
Values
LD0.DARREC1
2031
u16
1
.OpCnt1.stVal
CNT_SHOT1
AR 1st shot counter
0…65535
2032
u16
1
.OpCnt2.stVal
CNT_SHOT2
AR 1st shot counter
0…65535
2033
u16
1
.OpCnt3.stVal
CNT_SHOT3
AR 1st shot counter
0…65535
2034
u16
1
.OpCnt4.stVal
CNT_SHOT4
AR 1st shot counter
0…65535
2035
u16
1
.OpCnt5.stVal
CNT_SHOT5
AR 1st shot counter
0…65535
2036
u16
1
.FrqOpCnt.stVal
FRQ_OPR_CNT
AP freq.op. counter
0…65535
2.4.15
LD0.SECRSYN1 Synchrocheck (1)
Table 106:
RegA
LD0.SECRSYN1 Synchrocheck (1)
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.SECRSYN1
169
u16
1
.EnSt.stVal
ENERG_STATE
Energ. state of line and bus
0...41)
1) See the technical manual.
2.4.16
LD0.SSCBR1 Circuit-breaker condition monitoring values
(1)
Table 107:
RegA
LD0.SSCBR1 Circuit-breaker condition monitoring values (1)
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.SSCBR1
2060
u16
1
.InaTmdCnt.stVal
INA_DAYS
CB inactive days
0...65535
2061
u16
1
.TmmsOpn.mag
T_TRV_OP
Open travel time
0...60000
[ms]
2062
u16
1
.TmmsCls.mag
T_TRV_CL
Close travel time
0...60000
[ms]
2063
u16
100
.TmsSprCha.mag
T_SPR_CHR
Spring charge time
0.00…99.99
[s]
2064
i16
1
.RmnLifPhA.stVal
CB_LIFE_A
Remain.life phsA
-/+ 9999
2065
i16
1
.RmnLifPhB.stVal
CB_LIFE_B
Remain.life phsB
-/+ 9999
2066
i16
1
.RmnLifPhC.stVal
CB_LIFE_C
Remain.life phsC
-/+ 9999
2067
u16
1
.AccAPwrPhA.mag
IPOW_A
Iyt phsA
0...1E6
2068
u16
1
.AccAPwrPhB.mag
IPOW_B
Iyt phsB
0...1E6
2069
u16
1
.AccAPwrPhC.mag
IPOW_C
Iyt phsC
0...1E6
60
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
2.4.17
LD0.MDSOPT1 Generic operation time supervision
Since the register size is 16 bits, the value saturates at 65535 hours (approximately
7.5 years). Alternatively, a 32-bit user-definable register can be made of this data to
cover the whole 300 000 hours (34 years) range. The value can also, for example,
be rescaled to show “total operation days” instead by changing the scale factor
from 1 to 1/24 = 0.0417.
Table 108:
LD0.MDSOPT1 Generic operation time supervision
RegA
Type
2048
u16
Scale
1
2.4.18
.stVal
SA name
OPR_TIME
Description
Operating hours
Values
0…299999
[hours]
LD0.CMMXU1 Phase current measurements (1)
Table 109:
RegA
IEC 61850 name
LD0.CMMXU1 Phase current measurements (1)
Type
Scale
IEC 61850 name
SA name
LD0.CMMXU1
Description
Values
Phase current (1)
138
u16
1000
.A.phsA.instCVal.mag
I_INST_A
- phsA amplitude
0.00...40.0
[xIn]
139
u16
1000
.A.phsB.instCVal.mag
I_INST_B
- phsB amplitude
0.00...40.0
[xIn]
140
u16
1000
.A.phsC.instCVal.mag
I_INST_C
- phsC amplitude
0.00...40.0
[xIn]
2.4.19
LD0.CMSQI1 Sequence of current measurements (1)
Table 110:
RegA
LD0.CMSQI1 Sequence of current measurements (1)
Type
Scale
IEC 61850 name
SA name
LD0.CMSQI1
Description
Values
Sequence of currents
143
u16
1000
.SeqA.c1.instCVal.mag
I1_INST
- positive amplitude
0.00...40.0
[xIn]
144
u16
1000
.SeqA.c2.instCVal.mag
I2_INST
- negative amplitude
0.00...40.0
[xIn]
145
u16
1000
.SeqA.c2.instCVal.mag
I3_INST
- zero amplitude
0.00...40.0
[xIn]
2.4.20
LD0.RESCMMXU1 Residual current measurement (1)
Table 111:
RegA
LD0.RESCMMXU1 Residual current measurement (1)
Type
Scale
IEC 61850 name
SA name
LD0.RESCMMXU1
141
u16
1000
Recloser Protection and Control RER615
Point List Manual
.A.res.instCVal.mag
Description
Values
Residual current (1)
I0_INST
- amplitude
0.00...40.0
[xIn]
61
Section 2
Modbus data mappings
2.4.21
LD0.VMMXU1 Voltage measurements (1)
Table 112:
RegA
1MRS757822 B
LD0.VMMXU1 Voltage measurements (1)
Type
Scale
IEC 61850 name
SA name
LD0.VMMXU1
Description
Values
Phase-ground voltage (1)
152
u16
1000
.phV.phsA.cVal.mag
U_DB_A
- phsA amplitude
0.00...4.00
[xUn]
153
u16
1000
.phV.phsB.cVal.mag
U_DB_B
- phsB amplitude
0.00...4.00
[xUn]
154
u16
1000
.phV.phsC.cVal.mag
U_DB_C
- phsC amplitude
0.00...4.00
[xUn]
LD0.VMMXU1
Phase-phase voltage (1)
155
u16
1000
.PPV.phsAB.cVal.mag
U_DB_AB
- phsAB amplitude
0.00...4.00
[xUn]
156
u16
1000
.PPV.phsBC.cVal.mag
U_DB_BC
- phsBC amplitude
0.00...4.00
[xUn]
157
u16
1000
.PPV.phsCA.cVal.mag
U_DB_CA
- phsCA amplitude
0.00...4.00
[xUn]
2.4.22
LD0.VMMXU2 Voltage measurements (2)
Table 113:
RegA
LD0.VMMXU2 Voltage measurements (2)
Type
Scale
IEC 61850 name
SA name
LD0.VMMXU2
Description
Values
Phase-ground voltage (2)
1001
u16
1000
.phV.phsA.cVal.mag
U_DB_A
- phsA amplitude
0.00...4.00
[xUn]
1002
u16
1000
.phV.phsB.cVal.mag
U_DB_B
- phsB amplitude
0.00...4.00
[xUn]
1003
u16
1000
.phV.phsC.cVal.mag
U_DB_C
- phsC amplitude
0.00...4.00
[xUn]
LD0.VMMXU2
Phase-phase voltage (2)
1004
u16
1000
.PPV.phsAB.cVal.mag
U_DB_AB
- phsAB amplitude
0.00...4.00
[xUn]
1005
u16
1000
.PPV.phsBC.cVal.mag
U_DB_BC
- phsBC amplitude
0.00...4.00
[xUn]
1006
u16
1000
.PPV.phsCA.cVal.mag
U_DB_CA
- phsCA amplitude
0.00...4.00
[xUn]
62
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
2.4.23
LD0.VMSQI1 Sequence of voltage measurements (1)
Table 114:
RegA
LD0.VMSQI1 Sequence of voltage measurements (1)
Type
Scale
IEC 61850 name
SA name
LD0.VMSQI1
Description
Values
Sequence of voltages
158
u16
1000
.SeqA.c1.instCVal.mag
U1_INST
- positive amplitude
0.00...4.00
[xUn]
159
u16
1000
.SeqA.c2.instCVal.mag
U2_INST
- negative amplitude
0.00...4.00
[xUn]
160
u16
1000
.SeqA.c2.instCVal.mag
U3_INST
- zero amplitude
0.00...4.00
[xUn]
2.4.24
LD0.VSMSQI2 Sequence of voltage measurements (2)
Table 115:
RegA
LD0.VSMSQI2 Sequence of voltage measurements (2)
Type
Scale
IEC 61850 name
SA name
LD0.VSMSQI2
Description
Values
Sequence of voltages
1007
u16
1000
.SeqA.c1.instCVal.mag
U1_INST
- positive amplitude
0.00...4.00
[xUn]
1008
u16
1000
.SeqB.c2.instCVal.mag
U2_INST
- negative amplitude
0.00...4.00
[xUn]
1009
u16
1000
.SeqC.c2.instCVal.mag
U3_INST
- zero amplitude
0.00...4.00
[xUn]
2.4.25
LD0.PEMMXU1 Three-phase power measurements (1)
Table 116:
RegA
LD0.PEMMXU1 Three-phase power measurements (1)
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.PEMMXU1
161
i32
1
162
163
i32
1
.TotVAr.instMag
i32
1
.TotVA.instMag
Q_INST
1000
Recloser Protection and Control RER615
Point List Manual
.TotPF.instMag
-/+ 999,999
Total reactive power Q (high)
-/+ 999,999
(low word)
S_INST
.TotVA.instMag
i16
Total active power P (high)
(low word)
.TotVAr.instMag
166
167
P_INST
.TotW.instMag
164
165
.TotW.instMag
Total apparent power S (high)
-/+ 999,999
(low word)
PF_INST
Average power factor
-1...1
63
Section 2
Modbus data mappings
2.4.26
LD0.FMMXU1 Frequency measurement (1)
Table 117:
RegA
1MRS757822 B
LD0.FMMXU1 Frequency measurement (1)
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.FMMXU1
168
u16
100
2.4.27
F_DB
Frequency
Indication bits mirrored in registers
Type
Scale
IEC 61850 name
SA name
Description
170.00
Bit
Indication bit 2720 (0x1700)
170.01
Bit
Indication bit 2721 (0x1701)
:
:
:
170.14
Bit
Indication bit 2734 (0x170E)
170.15
Bit
Indication bit 2735 (0x170F)
171.00
Bit
Indication bit 2736 (0x1710)
2.4.28
Values
LD0.VMSTA1 Voltage demand values (1)
Table 119:
RegA
35.00...75.00
[Hz]
Indication bits mirrored in registers
Table 118:
RegA
.Hz.mag
LD0.VMSTA1 Voltage demand values (1)
Type
Scale
IEC 61850 name
SA name
LD0.VMSTA1
Description
Values
Demand phase-to-ground
1954
u16
1000
.AvVPhsA.mag
U_DMD_A
- phsA amplitude
0...4.0 [xUn]
1955
u16
1000
.AvVPhsB.mag
U_DMD_B
- phsB amplitude
0...4.0 [xUn]
1956
u16
1000
.AvVPhsC.mag
U_DMD_C
- phsC amplitude
0...4.0 [xUn]
Demand phase-to-phase
1957
u16
1000
.AvVPhsAB.mag
U_DMD_AB
- phsAB amplitude
0...4.0 [xUn]
1958
u16
1000
.AvVPhsBC.mag
U_DMD_BC
- phsBC amplitude
0...4.0 [xUn]
1959
u16
1000
.AvVPhsCA.mag
U_DMD_CA
- phsCA amplitude
0...4.0 [xUn]
Update time stamp
1)
1960
u16
-
- Year - month
1961
u16
-
- Day - hour
1962
u16
-
- Minute - second
1963
u16
-
- Milliseconds
1964
u16
-
- Time quality
1) See the technical manual.
64
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
2.4.29
LD0.VMSTA2 Voltage demand values (2)
Table 120:
RegA
LD0.VMSTA2 Voltage demand values (2)
Type
Scale
IEC 61850 name
SA name
LD0.VMSTA
Description
Values
Demand phase-to-ground
1928
u16
1000
.AvVPhsA.mag
U_DMD_A
- phsA amplitude
0...4.0 [xUn]
1929
u16
1000
.AvVPhsB.mag
U_DMD_B
- phsB amplitude
0...4.0 [xUn]
1930
u16
1000
.AvVPhsC.mag
U_DMD_C
- phsC amplitude
0...4.0 [xUn]
.
Demand phase-to-phase
1931
u16
1000
.AvVPhsAB.mag
U_DMD_AB
- phsAB amplitude
0...4.0 [xUn]
1932
u16
1000
.AvVPhsBC.mag
U_DMD_BC
- phsBC amplitude
0...4.0 [xUn]
1933
u16
1000
.AvVPhsCA.mag
U_DMD_CA
- phsCA amplitude
0...4.0 [xUn]
Update timestamp
1)
1934
u16
-
- Year - Month
1935
u16
-
- Day - Hour
1936
u16
-
- Minute - Second
1937
u16
-
- Millisecond
1938
u16
-
- Time quality
1) See the technical manual.
2.4.30
LD0.PEMSTA1 Power measurement demand values (1)
Table 121:
RegA
1939
LD0.PEMSTA1 Power measurement demand values (1)
Type
i32
Scale
IEC 61850 name
1
.AvW.mag
- Active power P (high)
i32
1
.AvVAr.mag
-/+ 999,999
- Reactive power Q (high)
-/+ 999,999
- (low word)
i32
1
.AvVA.mag
1944
1945
Values
- (low word)
1942
1943
Description
Demand
1940
1941
SA name
LD0.PEMSTA1
- Apparent power S (high)
-/+ 999,999
- (low word)
i16
1000
.AvPF.mag
1946
- Power factor
-1...1
< reserved >
0
Max values:
1947
i32
1
.MaxW.mag
1948
1949
-/+ 999,999
- (low word)
i32
1
.MaxVAr.mag
1950
1951
- Active power P (high)
- Reactive power Q (high)
-/+ 999,999
- (low word)
i32
1
.MaxVA.mag
- Apparent power S (high)
1952
- (low word)
1953
< reserved >
Recloser Protection and Control RER615
Point List Manual
-/+ 999,999
0
65
Section 2
Modbus data mappings
2.4.31
LD0.RESCMSTA1 Residual current demand value (1)
Table 122:
RegA
1MRS757822 B
LD0.RESCMSTA1 Residual current demand value (1)
Type
Scale
IEC 61850 name
SA name
LD0.RESCMSTA1
1989
u16
1000
.AvAmps.mag
Description
Demand value
I_DMD_RES
- residual amplitude
Update time stamp
1990
u16
-
- Year - month
1991
u16
-
- Day - hour
1992
u16
-
- Minute - second
1993
u16
-
- Milliseconds
1994
u16
-
- Time quality
1995
u16
1000
.MaxAmps.mag
Values
Max demand Io
- Max Io demand
Update time stamp
1996
u16
-
- Year - month
1997
u16
-
- Day - hour
1998
u16
-
- Minute - second
1999
u16
-
- Milliseconds
2000
u16
-
- Time quality
0.00...40.0
[xIn]
1)
0.00...40.0
[xIn]
1)
1) See the technical manual.
2.4.32
LD0.CMSTA1 Phase current demand values (1)
Table 123:
RegA
LD0.CMSTA1 Phase current demand values (1)
Type
Scale
IEC 61850 name
SA name
LD0.CMSTA1
Description
Values
Demand value
2001
u16
1000
.AvAmpsA.mag
I_DMD_A
- phsA amplitude
0.00...40.0
[xIn]
2002
u16
1000
.AvAmpsB.mag
I_DMD_B
- phsB amplitude
0.00...40.0
[xIn]
2003
u16
1000
.AvAmpsC.mag
I_DMD_C
- phsC amplitude
0.00...40.0
[xIn]
Update time stamp
2004
u16
-
- Year - month
2005
u16
-
- Day - hour
2006
u16
-
- Minute - second
2007
u16
-
- Milliseconds
2008
u16
-
- Time quality
1)
Table continues on next page
66
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
RegA
Type
Scale
2009
u16
1000
IEC 61850 name
.MaxAmpsA.mag
SA name
Max demand IL1
Description
- Max phsA demand
Update time stamp
2010
u16
-
- Year - month
2011
u16
-
- Day - hour
2012
u16
-
- Minute - second
2013
u16
-
- Milliseconds
2014
u16
-
- Time quality
2015
u16
1000
.MaxAmpsB.mag
Max demand IL2
- Max phsB demand
Update time stamp
2016
u16
-
- Year - month
2017
u16
-
- Day - hour
2018
u16
-
- Minute - second
2019
u16
-
- Milliseconds
2020
u16
-
- Time quality
2021
u16
1000
.MaxAmpsC.mag
Max demand IL3
- Max phsC demand
Update time stamp
2022
u16
-
- Year - month
2023
u16
-
- Day - hour
2024
u16
-
- Minute - second
2025
u16
-
- Milliseconds
2026
u16
-
- Time quality
Values
0.00...40.0
[xIn]
1)
0.00...40.0
[xIn]
1)
0.00...40.0
[xIn]
1)
1) See the technical manual.
2.4.33
CTRL.CBCSWI1 Circuit breaker operation counter (1)
Table 124:
RegA
CTRL.CBCSWI1 Circuit breaker operation counter (1)
Type
Scale
IEC 61850 name
SA name
Description
Values
CTRL.CBCSWI1
2027
u16
1
Recloser Protection and Control RER615
Point List Manual
.OpCntRs.stVal
Operation counter
Operation counter
0…65535
67
Section 2
Modbus data mappings
2.4.34
LD0.PEMMTR1 Three-phase energy measurements (1)
Table 125:
RegA
1MRS757822 B
LD0.PEMMTR1 Three-phase energy measurements (1)
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.PEMMTR1
2037
u32
1
2038
2039
u32
1
2040
2041
u32
1
2042
2043
u32
1
2044
2.4.35
Reverse active energy (high)
.SupWh.actVal
(low word)
.SupVArh.actVal
Reverse reactive energy (high)
.SupVArh.actVal
(low word)
.DemWh.actVal
Forward active energy (high)
.DemWh.actVal
(low word)
.DemVArh.actVal
Forward reactive energy (high)
.DemVArh.actVal
(low word)
0...1E10
[kWh]
0...1E10
[kVAr]
0...1E10
[kWh]
0...1E10
[kVAr]
System diagnostic values
Table 126:
RegA
.SupWh.actVal
System diagnostic values
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.LPHD1
2050
u16
1
.PhyHealth1.stVal
Warning
Last warning code
1)
2051
u16
1
.PhyHealth2.stVal
Internal fault
Last internal fault code
1)
DR.RDRE1
2052
u16
1
.FltNum.stVal
Num.of DR recordings
0...N
2053
u16
1
.MemUsed.stVal
DR memory used
0...100 [%]
LD0.LPHD1
2054
u16
1
.NumPwrUp.stVal
Num of cold starts
0...65535
2055
u16
1
.WrmStr.stVal
Num of warm starts
0...65535
2056
u16
1
.WacTrg.stVal
Num of watchdog resets
0...65535
2057
u16
1
.NumCmpChg.stVal
Num of conf. changes
0...65535
1) See the technical manual.
68
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
2.4.36
Control structure 1
Table 127:
RegA
Control structure 1
Type
Scale
IEC 61850 name
SA name
Description
Values
8001
Execute register
1
8002
Password reg 1
acc to setting
8003
Password reg 2
acc to setting
8004
Control register
< single bit >
8005
Confirm register
< single bit >
2.4.37
Control structure 2
Table 128:
RegA
Control structure 2
Type
Scale
IEC 61850 name
SA name
Description
Values
8006
Execute register
1
8007
Password reg 1
acc to setting
8008
Password reg 2
acc to setting
8009
Control register
< single bit >
8010
Confirm register
< single bit >
2.4.38
Control structure 3
Table 129:
RegA
Control structure 3
Type
Scale
IEC 61850 name
SA name
Description
Values
8011
Execute register
1
8012
Password reg 1
acc to setting
8013
Password reg 2
acc to setting
8014
Control register
< single bit >
8015
Confirm register
< single bit >
2.4.39
Control structure 4
Table 130:
RegA
Control structure 4
Type
Scale
IEC 61850 name
SA name
Description
Values
8016
Execute register
1
8017
Password reg 1
acc to setting
8018
Password reg 2
acc to setting
8019
Control register
< single bit >
8020
Confirm register
< single bit >
Recloser Protection and Control RER615
Point List Manual
69
Section 2
Modbus data mappings
2.4.40
Control structure 5
Table 131:
RegA
1MRS757822 B
Control structure 5
Type
Scale
IEC 61850 name
SA name
Description
Values
8021
Execute register
1
8022
Password reg 1
acc to setting
8023
Password reg 2
acc to setting
8024
Control register
< single bit >
8025
Confirm register
< single bit >
2.4.41
Control structure 6
Table 132:
RegA
Control structure 6
Type
Scale
IEC 61850 name
SA name
Description
Values
8026
Execute register
1
8027
Password reg 1
acc to setting
8028
Password reg 2
acc to setting
8029
Control register
< single bit >
8030
Confirm register
< single bit >
2.4.42
Control structure 7
Table 133:
RegA
Control structure 7
Type
Scale
IEC 61850 name
SA name
Description
Values
8031
Execute register
1
8032
Password reg 1
acc to setting
8033
Password reg 2
acc to setting
8034
Control register
< single bit >
8035
Confirm register
< single bit >
2.4.43
Control structure 8
Table 134:
RegA
Control structure 8
Type
Scale
IEC 61850 name
SA name
Description
Values
8036
Execute register
1
8037
Password reg 1
acc to setting
8038
Password reg 2
acc to setting
8039
Control register
< single bit >
8040
Confirm register
< single bit >
70
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
2.4.44
Device ID string
Table 135:
Device ID string
RegA
Type
9000
u16
Scale
IEC 61850 name
SA name
Description
ASCII coded string
Values
1)
...
9120
u16
1) See the technical manual.
2.4.45
IED Real-time clock (in local time mode) - read and write
(synchronize)
Table 136:
RegA
IED Real-time clock (in local time mode) - read and write (synchronize)
Type
Scale
IEC 61850 name
SA name
Description
Values
9201
Control register
0...21)
9202
Year
2000...2999
9203
Month
1...12
9204
Day
1...31
9205
Hour
0...23
9206
Minute
0...59
9207
Second
0...59
9208
Millisecond
0…999
1) See the technical manual.
2.4.46
IED real-time clock (in UTC time mode) - read and write
(synchronize)
Table 137:
RegA
IED real-time clock (in UTC time mode) - read and write (synchronize)
Type
Scale
IEC 61850 name
SA name
Description
Values
9211
Control register
0...21)
9212
Year
2000...2999
9213
Month
1...12
9214
Day
1...31
9215
Hour
0...23
9216
Minute
0...59
9217
Second
0...59
9218
Millisecond
0…999
1) See the technical manual.
Recloser Protection and Control RER615
Point List Manual
71
Section 2
Modbus data mappings
2.4.47
1MRS757822 B
Time and reason for latest IED reset
Table 138:
Time and reason for latest IED reset
RegA
Type
Scale
9221
u16
1
Year
2000...2999
9222
u16
1
Month
1...12
9223
u16
1
Day
1...31
9224
u16
1
Hour
0...23
9225
u16
1
Minute
0...59
9226
u16
1
Second
0...59
9227
u16
1
Millisecond
0…999
9228
u16
1
Reset reason
9228.0
Bit
- bit 0
1=Cold start
9228.1
Bit
- bit 1
1=Watchdog
9228.2
Bit
- bit 2
1=Warm start
2.4.48
SA name
Description
Values
Active parameter setting group - read and write
Table 139:
Active parameter setting group - read and write
RegA
Type
9231
u16
Scale
IEC 61850 name
SA name
1
2.4.49
Description
Active setting group
Values
1...6
Event record structure
Table 140:
RegA
IEC 61850 name
Event record structure
Type
Scale
IEC 61850 name
SA name
Description
Values
Selection write:
9250
u16
1
- Num of multiple records
1...10
9251
i16
1
- Read selection
-499…3
Record 1 data to read:
9252
u16
1
- Record sequence num
1...9999
9253
u16
1
- Unread records left
0...499
Timestamp of record
9254
u16
1
- Year, Month
Year/Month
9255
u16
1
- Day, Hour
Day/Hour
9256
u16
1
- Minute, Second
Min/Sec
9257
u16
1
- Millisecond
Millisecond
9258
u16
1
Event identification
1)
9259
u16
1
Data object ID1
1)
Table continues on next page
72
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
RegA
Type
9260
u16
Scale
1
IEC 61850 name
SA name
Description
Data object ID2
Values
1)
9261
u16
1
Event data value 1
1)
9262
u16
1
Event data value 2
1)
Record 2 data to read:
If selected
9263
u16
1
- Record sequence num
1..9999
9264
u16
1
- Unread records left
0..499
Timestamp of record
9265
u16
1
- Year, Month
Year/Month
9266
u16
1
- Day, Hour
Day/Hour
9267
u16
1
- Minute, Second
Min/Sec
9268
u16
1
- Millisecond
Millisecond
9269
u16
1
Event identification
1)
9270
u16
1
Data object ID1
1)
9271
u16
1
Data object ID2
1)
9272
u16
1
Event data value 1
1)
9273
u16
1
Event data value 2
1)
Record 3 data to read:
If selected
9274
u16
1
- Record sequence num
1...9999
9275
u16
1
- Unread records left
0...499
Timestamp of record
9276
u16
1
- Year, Month
Year/Month
9277
u16
1
- Day, Hour
Day/Hour
9278
u16
1
- Minute, Second
Min/Sec
9279
u16
1
- Millisecond
Millisecond
9280
u16
1
Event identification
1)
9281
u16
1
Data object ID1
1)
9282
u16
1
Data object ID2
1)
9283
u16
1
Event data value 1
1)
9284
u16
1
Event data value 2
1)
Record 4 data to read:
If selected
9285
u16
1
- Record sequence num
1...9999
9286
u16
1
- Unread records left
0...499
Timestamp of record
9287
u16
1
- Year, Month
Year/Month
9288
u16
1
- Day, Hour
Day/Hour
9289
u16
1
- Minute, Second
Min/Sec
Table continues on next page
Recloser Protection and Control RER615
Point List Manual
73
Section 2
Modbus data mappings
Scale
IEC 61850 name
1MRS757822 B
RegA
Type
9290
u16
1
SA name
Description
- Millisecond
Values
Millisecond
9291
u16
1
Event identification
1)
9292
u16
1
Data object ID1
1)
9293
u16
1
Data object ID2
1)
9294
u16
1
Event data value 1
1)
9295
u16
1
Event data value 2
1)
Record 5 data to read:
If selected
9296
u16
1
- Record sequence num
1...9999
9297
u16
1
- Unread records left
0...499
Timestamp of record
9298
u16
1
- Year, Month
Year/Month
9299
u16
1
- Day, Hour
Day/Hour
9300
u16
1
- Minute, Second
Min/Sec
9301
u16
1
- Millisecond
Millisecond
9302
u16
1
Event identification
1)
9303
u16
1
Data object ID1
1)
9304
u16
1
Data object ID2
1)
9305
u16
1
Event data value 1
1)
9306
u16
1
Event data value 2
1)
Record 6 data to read:
If selected
9307
u16
1
- Record sequence num
1...9999
9308
u16
1
- Unread records left
0...499
Timestamp of record
9309
u16
1
- Year, Month
Year/Month
9310
u16
1
- Day, Hour
Day/Hour
9311
u16
1
- Minute, Second
Min/Sec
9312
u16
1
- Millisecond
Millisecond
9313
u16
1
Event identification
1)
9314
u16
1
Data object ID1
1)
9315
u16
1
Data object ID2
1)
9316
u16
1
Event data value 1
1)
9317
u16
1
Event data value 2
1)
Record 7 data to read:
If selected
9318
u16
1
- Record sequence num
1...9999
9319
u16
1
- Unread records left
0...499
Timestamp of record
Table continues on next page
74
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
RegA
Type
9320
u16
Scale
1
IEC 61850 name
SA name
Description
- Year, Month
Values
Year/Month
9321
u16
1
- Day, Hour
Day/Hour
9322
u16
1
- Minute, Second
Min/Sec
9323
u16
1
- Millisecond
Millisecond
9324
u16
1
Event identification
1)
9325
u16
1
Data object ID1
1)
9326
u16
1
Data object ID2
1)
9327
u16
1
Event data value 1
1)
9328
u16
1
Event data value 2
1)
Record 8 data to read:
If selected
9329
u16
1
- Record sequence num
1...9999
9330
u16
1
- Unread records left
0...499
9331
u16
1
- Year, Month
Year/Month
9332
u16
1
- Day, Hour
Day/Hour
9333
u16
1
- Minute, Second
Min/Sec
9334
u16
1
- Millisecond
Millisecond
9335
u16
1
Event identification
1)
9336
u16
1
Data object ID1
1)
9337
u16
1
Data object ID2
1)
9338
u16
1
Event data value 1
1)
9339
u16
1
Event data value 2
1)
Record 9 data to read:
If selected
Timestamp of record
9340
u16
1
- Record sequence num
1...9999
9341
u16
1
- Unread records left
0...499
Timestamp of record
9342
u16
1
- Year, Month
Year/Month
9343
u16
1
- Day, Hour
Day/Hour
9344
u16
1
- Minute, Second
Min/Sec
9345
u16
1
- Millisecond
Millisecond
9346
u16
1
Event identification
1)
9347
u16
1
Data object ID1
1)
9348
u16
1
Data object ID2
1)
9349
u16
1
Event data value 1
1)
9350
u16
1
Event data value 2
1)
Table continues on next page
Recloser Protection and Control RER615
Point List Manual
75
Section 2
Modbus data mappings
RegA
Type
Scale
1MRS757822 B
IEC 61850 name
SA name
Description
Values
Record 10 data to read:
If selected
9351
u16
1
- Record sequence num
1...9999
9352
u16
1
- Unread records left
0...499
Timestamp of record
9353
u16
1
- Year, Month
Year/Month
9354
u16
1
- Day, Hour
Day/Hour
9355
u16
1
- Minute, Second
Min/Sec
9356
u16
1
- Millisecond
Millisecond
9357
u16
1
Event identification
1)
9358
u16
1
Data object ID1
1)
9359
u16
1
Data object ID2
1)
9360
u16
1
Event data value 1
1)
9361
u16
1
Event data value 2
1)
1) See the technical manual.
2.4.50
Fault record structure header
Table 141:
RegA
Fault record structure header
Type
Scale
IEC 61850 name
SA name
Description
Values
Selection write:
9401
u16
- Read selection
-99...3
Record data header:
9402
u16
- Record sequence num
0...65535
9403
u16
- Unread records left
0...99
Timestamp of record:
9404
u16
- Year, month
Year/Month
9405
u16
- Day, hour
Day/Hour
9406
u16
- Minute, second
Min/Sec
9407
u16
- Millisecond
Millisecond
9408
u16
- Timestamp quality
1)
LD0.FLTMSTA1
9409
u16
100
.StrDur.mag
- Start duration
0...100.00 [%]
9410
u16
1
.ActSG.stVal
- Active setting group
1...6
9411
u16
100
.FltDiskm.mag
- Fault distance
0...9999.99
[pu]
9412
u16
< reserved >
0
9413
u16
< reserved >
0
9414
u16
< reserved >
0
9415
u16
< reserved >
0
Table continues on next page
76
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
RegA
Type
9416
u16
Scale
IEC 61850 name
SA name
Description
< reserved >
Values
0
9417
u16
< reserved >
0
9418
u16
< reserved >
0
9419
u16
< reserved >
0
9420
u16
< reserved >
0
9421
u16
< reserved >
0
1) See the technical manual.
2.4.51
Fault record data
Table 142:
RegA
Fault record data
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.FLTMSTA1
9422
u16
1000
.MaxAmpsA.mag
-
Max phsA current
0...50.0 [xIn]
9423
u16
1000
.MaxAmpsB.mag
-
Max phsB current
0...50.0 [xIn]
9424
u16
1000
.MaxAmpsC.mag
-
Max phsC current
0...50.0 [xIn]
9425
u16
1000
.MaxAmpsN.mag
-
Max residual current
0...50.0 [xIn]
9426
u16
1000
.AmpsA.mag
-
PhsA current
0...50.0 [xIn]
9427
u16
1000
.AmpsB.mag
-
PhsB current
0...50.0 [xIn]
9428
u16
1000
.AmpsC.mag
-
PhsC current
0...50.0 [xIn]
9429
u16
1000
.AmpsN.mag
-
Residual current
0...50.0 [xIn]
9430
u16
1000
.AmpsNClc.mag
-
Residual current (calc)
0...50.0 [xIn]
9431
u16
1000
.AmpsPsSeq.mag
-
Positive seq. current
0...50.0 [xIn]
9432
u16
1000
.AmpsNgSeq.mag
-
Negative seq. current
0...50.0 [xIn]
9433
u16
1000
.VoltsA.mag
-
PhsA voltage
0...4.00 [xUn]
9434
u16
1000
.VoltsB.mag
-
PhsB voltage
0...4.00 [xUn]
9435
u16
1000
.VoltsC.mag
-
PhsC voltage
0...4.00 [xUn]
9436
u16
1000
.VoltsAB.mag
-
PhsAB voltage
0...4.00 [xUn]
9437
u16
1000
.VoltsBC.mag
-
PhsBC voltage
0...4.00 [xUn]
9438
u16
1000
.VoltsCA.mag
-
PhsCA voltage
0...4.00 [xUn]
9439
u16
1000
.VoltsN.mag
-
Residual voltage
0...4.00 [xUn]
9440
u16
1000
.VZroSeq.mag
-
Zero seq. voltage
0...4.00 [xUn]
9441
u16
1000
.VPsSeq.mag
-
Positive seq. voltage
0...4.00 [xUn]
9442
u16
1000
.VNgSeq.mag
-
Negative seq. voltage
0...4.00 [xUn]
9443
u16
1000
.VoltsAb.mag
-
PhsAb voltage
0...4.00 [xUn]
9444
u16
1000
.VoltsBb.mag
-
PhsBb voltage
0...4.00 [xUn]
9445
u16
1000
.VoltsCb.mag
-
PhsCb voltage
0...4.00 [xUn]
9446
u16
1000
.VoltsABb.mag
-
PhsABb voltage
0...4.00 [xUn]
9447
u16
1000
.VoltsBCb.mag
-
PhsBCb voltage
0...4.00 [xUn]
Table continues on next page
Recloser Protection and Control RER615
Point List Manual
77
Section 2
Modbus data mappings
1MRS757822 B
RegA
Type
Scale
IEC 61850 name
9448
u16
1000
.VoltsCAb.mag
-
PhsCAb voltage
0...4.00 [xUn]
9449
u16
1000
.VZroSeqb.mag
-
Zero seq. voltage b
0...4.00 [xUn]
9450
u16
1000
.VPsSeqb.mag
-
Positive seq. voltage b
0...4.00 [xUn]
9451
u16
1000
.VNgSeqb.mag
-
Negative seq. voltage b
0...4.00 [xUn]
9452
i16
10
.DifAAngBC.mag
-
PhsB-C angle
-/+ 180 deg
9453
i17
10
.DifBAngCA.mag
-
PhsC-A angle
-/+ 180 deg
9454
i18
10
.DifCAngAB.mag
-
PhsA-B angle
-/+ 180 deg
9455
u16
100
.MaxTmpRl.mag
-
Relative temperature
0...99.99
9456
u16
10
.PDNS1MxRat.mag
-
PDNSPTOC1 ratio I2/I1
0...999.99 [%]
9457
u16
100
.Hz.mag
-
Frequency
30...80.00
[Hz]
9458
i16
100
.HzS.mag
-
Frequency gradient
-/+10.00 [Hz/
s]
9459
i16
10
.CondN.mag
-
Coductance
-/+-1000 [mS]
9460
i16
10
.SusN.mag
-
Susceptance
-/+-1000 [mS]
2.5
Column name
2.5.1
0xA
Description
Values
Controls
Table 143:
Table 144:
SA name
Explanations of the controls table columns
Description
0xA
Coil (0X) address for control value.
CS
Control structure and bit within the structure for control value.
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name
The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description
Short description of the signal. See the technical manual for more information.
Value
Meaning of the written value.
Reset, acknowledge and trigger points (A)
Reset, acknowledge and trigger points (A)
CS
IEC 61850 name
SA name
Description
Values
LD0.LLN0
2060
2.00
.LEDRs1.Oper.ctlVal
Reset indications and LEDs
1=Reset
2061
2.01
.LEDRs2.Oper.ctlVal
Reset Alarm LEDs
1=Reset
Reset Power max demands
1=Reset
LD0.PEMSTA1
2062
2.02
.RecRs.Oper.ctlVal
LD0.DARREC1
Table continues on next page
78
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
0xA
CS
IEC 61850 name
SA name
Description
Values
2063
2.03
.RsRec.Oper.ctlVal
Reset reclosing
1=Reset
2064
2.04
.RsCnt.ctlVal
Reset reclosing counters
1=Reset
LD0.SSCBR1
2065
2.05
.RsAccAPwr.Oper.ctlVal
Reset CB accum. energy
1=Reset
2066
2.06
.RsCBWear.Oper.ctlVal
Reset CB wear data
1=Reset
DR.RDRE1
2067
2.07
.RcdTrg.Oper.ctlVal
Trig DR recording
1=Trig
2068
2.08
.MemClr.Oper.ctlVal
Clear DR memory
1=Clear
Reset Max current1 demands
1=Reset
Reset energy values
1=Reset
LD0.CMSTA1
2069
2.09
.RecRs.Oper.ctlVal
LD0.PEMMXU1
2070
2.10
.SupDmdRs.Oper.ctlVal
LD0.SCCBR1
2071
2.11
.RsTrvTm.Oper.ctlVal
Reset CB travel time
1=Reset
2072
2.12
.RsSprChaTm.Oper.ctlV
al
Reset CB spring charge time
1=Reset
Reset Io (1) max demands
1=Reset
Reset Uo (1) max demands
1=Reset
LD0.RESCMSTA1
2073
2.13
.RecRs.Oper.ctlVal
LD0.RESVMSTA1
2074
2.14
2.5.2
Table 145:
0xA
.RecRs.Oper.ctlVal
LD0.LPHD1 IED warm reset (1)
LD0.LPHD1 IED warm reset (1)
CS
IEC 61850 name
SA name
Description
Values
LD0.LPHD1
2080
3.00
2.5.3
Table 146:
0xA
.RsDev.Oper.ctlVal
Warm reboot of IED
1=Reboot
CTRL.CBCSWI1 Circuit breaker (1) control
CTRL.CBCSWI1 Circuit breaker (1) control
CS
IEC 61850 name
SA name
Description
Values
CTRL.CBCSWI1
2048
1.00
.Pos.Oper.ctlVal
Select open
1=Select
2049
1.01
.Pos.Oper.ctlVal
Select close
1=Select
2050
1.02
.Pos.Oper.ctlVal
Cancel selection
1=Cancel
2051
1.03
.Pos.Oper.ctlVal
Execute selection
1=Execute
2052
1.04
.Pos.Oper.ctlVal
Direct open
1=Open
2053
1.05
.Pos.Oper.ctlVal
Direct close
1=Close
Recloser Protection and Control RER615
Point List Manual
79
Section 2
Modbus data mappings
2.5.4
Table 147:
0xA
1MRS757822 B
LD0.SRGAPC1 Reset SRGAPC1 generic flip-flops
LD0.SRGAPC1 Reset SRGAPC1 generic flip-flops
CS
IEC 61850 name
SA name
Description
Values
LD0.SRGAPC1
2096
4.00
.Rs1.Oper.ctlVal
Reset flip-flop 1
1=Reset
2097
4.01
.Rs2.Oper.ctlVal
Reset flip-flop 2
1=Reset
2098
4.02
.Rs3.Oper.ctlVal
Reset flip-flop 3
1=Reset
2099
4.03
.Rs4.Oper.ctlVal
Reset flip-flop 4
1=Reset
2100
4.04
.Rs5.Oper.ctlVal
Reset flip-flop 5
1=Reset
2101
4.05
.Rs6.Oper.ctlVal
Reset flip-flop 6
1=Reset
2102
4.06
.Rs7.Oper.ctlVal
Reset flip-flop 7
1=Reset
2103
4.07
.Rs8.Oper.ctlVal
Reset flip-flop 8
1=Reset
2.5.5
Table 148:
0xA
LD0.SRGAPC2 Reset SRGAPC2 generic flip-flops
LD0.SRGAPC2 Reset SRGAPC2 generic flip-flops
CS
IEC 61850 name
SA name
Description
Values
LD0.SRGAPC2
2104
4.08
.Rs1.Oper.ctlVal
Reset flip-flop 1
1=Reset
2105
4.09
.Rs2.Oper.ctlVal
Reset flip-flop 2
1=Reset
2106
4.10
.Rs3.Oper.ctlVal
Reset flip-flop 3
1=Reset
2107
4.11
.Rs4.Oper.ctlVal
Reset flip-flop 4
1=Reset
2108
4.12
.Rs5.Oper.ctlVal
Reset flip-flop 5
1=Reset
2109
4.13
.Rs6.Oper.ctlVal
Reset flip-flop 6
1=Reset
2110
4.14
.Rs7.Oper.ctlVal
Reset flip-flop 7
1=Reset
2111
4.15
.Rs8.Oper.ctlVal
Reset flip-flop 8
1=Reset
2.5.6
LD0.SPCGGIO1 Multipurpose binary outputs (1)
The binary outputs can be configured either as pulse- or persistent-type outputs. Pulsetype outputs are triggered with the write value "1". Persistent-type outputs can be
written with both values "1" and "0". The setting mode "toggled" for local
operation corresponds to "persistent" for remote operation.
Table 149:
0xA
LD0.SPCGGIO1 Multipurpose binary outputs (1)
CS
IEC 61850 name
SA name
Description
Values
LD0.SPCGGIO1
2112
5.00
.SPCS01.ctlVal
Output 1 control
0/1=Off/On
2113
5.01
.SPCS02.ctlVal
Output 2 control
0/1=Off/On
2114
5.02
.SPCS03.ctlVal
Output 3 control
0/1=Off/On
Table continues on next page
80
Recloser Protection and Control RER615
Point List Manual
Section 2
Modbus data mappings
1MRS757822 B
0xA
CS
IEC 61850 name
SA name
Description
Values
2115
5.03
.SPCS04.ctlVal
Output 4 control
0/1=Off/On
2116
5.04
.SPCS05.ctlVal
Output 5 control
0/1=Off/On
2117
5.05
.SPCS06.ctlVal
Output 6 control
0/1=Off/On
2118
5.06
.SPCS07.ctlVal
Output 7 control
0/1=Off/On
2119
5.07
.SPCS08.ctlVal
Output 8 control
0/1=Off/On
2120
5.08
.SPCS09.ctlVal
Output 9 control
0/1=Off/On
2121
5.09
.SPCS10.ctlVal
Output 10 control
0/1=Off/On
2122
5.10
.SPCS11.ctlVal
Output 11 control
0/1=Off/On
2123
5.11
.SPCS12.ctlVal
Output 12 control
0/1=Off/On
2124
5.12
.SPCS13.ctlVal
Output 13 control
0/1=Off/On
2125
5.13
.SPCS14.ctlVal
Output 14 control
0/1=Off/On
2126
5.14
.SPCS15.ctlVal
Output 15 control
0/1=Off/On
2127
5.15
.SPCS16.ctlVal
Output 16 control
0/1=Off/On
2.5.7
LD0.SPCGGIO2 Multipurpose binary outputs (2)
The binary outputs can be configured either as pulse- or persistent-type outputs. Pulsetype outputs are triggered with the write value "1". Persistent-type outputs can be
written with both values "1" and "0". The setting mode "toggled" for local
operation corresponds to "persistent" for remote operation.
Table 150:
0xA
LD0.SPCGGIO2 Multipurpose binary outputs (2)
CS
IEC 61850 name
SA name
Description
Values
LD0.SPCGGIO2
2128
6.00
.SPCS01.ctlVal
Output 1 control
0/1=Off/On
2129
6.01
.SPCS02.ctlVal
Output 2 control
0/1=Off/On
2130
6.02
.SPCS03.ctlVal
Output 3 control
0/1=Off/On
2131
6.03
.SPCS04.ctlVal
Output 4 control
0/1=Off/On
2132
6.04
.SPCS05.ctlVal
Output 5 control
0/1=Off/On
2133
6.05
.SPCS06.ctlVal
Output 6 control
0/1=Off/On
2134
6.06
.SPCS07.ctlVal
Output 7 control
0/1=Off/On
2135
6.07
.SPCS08.ctlVal
Output 8 control
0/1=Off/On
2136
6.08
.SPCS09.ctlVal
Output 9 control
0/1=Off/On
2137
6.09
.SPCS10.ctlVal
Output 10 control
0/1=Off/On
2138
6.10
.SPCS11.ctlVal
Output 11 control
0/1=Off/On
2139
6.11
.SPCS12.ctlVal
Output 12 control
0/1=Off/On
2140
6.12
.SPCS13.ctlVal
Output 13 control
0/1=Off/On
2141
6.13
.SPCS14.ctlVal
Output 14 control
0/1=Off/On
2142
6.14
.SPCS15.ctlVal
Output 15 control
0/1=Off/On
2143
6.15
.SPCS16.ctlVal
Output 16 control
0/1=Off/On
Recloser Protection and Control RER615
Point List Manual
81
Section 2
Modbus data mappings
2.5.8
1MRS757822 B
LD0.SPCRGGIO1 Multipurpose binary outputs (1)
The binary outputs can be configured either as pulse- or persistent-type outputs. Pulsetype outputs are triggered with the write value "1". Persistent-type outputs can be
written with both values "1" and "0". The setting mode "toggled" for local
operation corresponds to "persistent" for remote operation.
Table 151:
0xA
LD0.SPCRGGIO1 Multipurpose binary outputs (1)
CS
IEC 61850 name
SA name
Description
Values
LD0.SPCRGGIO1
2416
-
.SPCS01.ctlVal
Output 1 control
0/1=Off/On
2417
-
.SPCS02.ctlVal
Output 2 control
0/1=Off/On
2418
-
.SPCS03.ctlVal
Output 3 control
0/1=Off/On
2419
-
.SPCS04.ctlVal
Output 4 control
0/1=Off/On
2420
-
.SPCS05.ctlVal
Output 5 control
0/1=Off/On
2421
-
.SPCS06.ctlVal
Output 6 control
0/1=Off/On
2422
-
.SPCS07.ctlVal
Output 7 control
0/1=Off/On
2423
-
.SPCS08.ctlVal
Output 8 control
0/1=Off/On
2424
-
.SPCS09.ctlVal
Output 9 control
0/1=Off/On
2425
-
.SPCS10.ctlVal
Output 10 control
0/1=Off/On
2426
-
.SPCS11.ctlVal
Output 11 control
0/1=Off/On
2427
-
.SPCS12.ctlVal
Output 12 control
0/1=Off/On
2428
-
.SPCS13.ctlVal
Output 13 control
0/1=Off/On
2429
-
.SPCS14.ctlVal
Output 14 control
0/1=Off/On
2430
-
.SPCS15.ctlVal
Output 15 control
0/1=Off/On
2431
-
.SPCS16.ctlVal
Output 16 control
0/1=Off/On
82
Recloser Protection and Control RER615
Point List Manual
Section 3
Glossary
1MRS757822 B
Section 3
Glossary
EF
Earth fault
EMC
Electromagnetic compatibility
IEC
International Electrotechnical Commission
IEC 61850 International standard for substation communication and
modeling
IED
Intelligent electronic device
LHMI
Local human-machine interface
Modbus
A serial communication protocol developed by the Modicon
company in 1979. Originally used for communication in PLCs
and RTU devices.
OC
Overcurrent
PCM600
Protection and Control IED Manager
Recloser Protection and Control RER615
Point List Manual
83
84
85
ABB Oy
Medium Voltage Products,
Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone
+358 10 22 11
Fax
+358 10 22 41094
www.abb.com/substationautomation
1MRS757822 B © Copyright 2015 ABB. All rights reserved.