Politec ADEBUS Installation And Wiring Manual

Add to My manuals
32 Pages

advertisement

Politec ADEBUS Installation And Wiring Manual | Manualzz
PRODUCT
ADEBUS
Product code ADEBUS
ADEBUS
MONITORING CONTROL UNIT
INSTALLATION AND WIRING MANUAL VERSION 2.1
1
Table of contents
1.Introduction…………………………………………………………………………………………........................................4
2.Product description…………………..………………………………………………………….………………………….…..4
3.General warnings…………………………………………………………………………………………………………………...….5
3.1 Additional warnings for devices powered by mains voltage
3.2 Installation warnings
4.List of main components………….………………………………………………………………………………………………..6
4.1 The control unit
5.Description of the boards ………………………………………………………………………………………………………… 7
5.1 ADEBUS SC - Adebus motherboard
5.2 ADEBUS ESP - Expansion board with 16 relay outputs for Adebus
5.3 ALPO2B
6.Preparation for installation ………………………………………………..…………………………………………………....10
6.1 Preparing the components before installation
6.2 It is advisable to carry out
7.Connections……………………………………………………………………………..…................................................12
7.1 Adebus internal connections
7.2 Barrier connections - Adebus
7.3 Examples of cable connections
8.Installation and first access - DEFAULT STATIC IP 192.168.1.222 …………..…………………………….....13
8.1 Access via Ethernet port
8.2 Factory settings
8.3 Adebus Explorer software installation and start-up
8.4 Main screen
8.5 Working Path
8.6 Site Creation
8.7 Configuration Mode
8.8 Address Setup
8.9 System Configuration
8.10 Adding or replacing barrier
8.11 Popup
9.Access to the columns - Adebus Explorer ……………………………....………..……………………………........ 18
9.1 Key
9.2 Column Detail
9.3 New Configuration
9.4 Input/Output Associations
9.5 Polarity
10.Events archive …………………....……………………………………………………..............................................21
ADEBUS
2
POLITEC | INSTALLATION MANUAL - VER.2.1
Table of contents
11.Appendix A - WEB page .………………………. ………………………. ………… ..… .. .22
11.1 Column Detail
11.2 Column Status
11.3 Output Configuration / Output Polarity
11.4 Network Configuration
12.Appendix B - configuration and barrier statuses ……………………………….… .. …… .24
12.1 Status
12.2 Analogue Values
12.3 Configuration
13.Appendix C - Special Input …………………………………………………… ..…………………………………………… ..... 27
13.1 Connection in barrier
13.2 Enabling and software status
13.3 Output configuration
14.Appendix D - Sectioning ….…………… .. ……………………………………………… ..... 29
14.1 Enabling in pairs - Sectioning
14.2 Area configuration - Sectioning
14.3 Software configuration - Sectioning
15.Technical characteristics …………….……………………………………………. ………… .30
16.Product disposal ………….………………. …………………………………. ……….….…. ..31
ADEBUS
3
POLITEC | INSTALLATION MANUAL - VER.2.1
1.Introduction
Congratulations on having purchased the Politec monitoring control unit.This appliance
guarantees long-lasting and reliable operation if installed correctly.For correct and effective use,
it is necessary to read this instruction manual carefully.
The barriers and the monitoring control unit have been designed to detect intrusions
and activate the alarm; it is not a device that prevents intrusion.Politec is not
responsible for damage, injury or loss caused by accidents, theft, force majeure
(including momentary lightning-induced overcurrent), abuse, improper or incorrect
use, faulty installation or inadequate maintenance.
2. Product description
ADEBUS is a monitoring control unit
for the management of up to 32
columns (MANA SMA, PARVIS MES
SMA, SANDOR PLUS SMA) divided
arbitrarily
into
2
branches
(expandable) using both the serial
ports Com0 and Com1.Adebus
manages, supervises and configures
every individual column reachable
through a TCP/IP connection.
MAX 32 Columns
MAX 1 Km
This system is ideal for managing
the perimeter protection of large
areas.
The main features of this system
are:
• Each column and beam can be
configured and verified in real
time: all operations can be
performed locally or remotely via
WEB;
• Configuration of each relay
output associated with any
event.
• Storing and downloading up to
32000 events on a PC.
MAX 1 Km
Warnings
Mounting, installation of the barrier and connection to the mains must be carried out
by expert and qualified personnel, in compliance with rules and regulations applicable
to electrical systems.
ADEBUS
4
POLITEC | INSTALLATION MANUAL - VER.2.1
3.General warnings
This installation manual contains important information regarding safety for installation: it is
necessary to read all the instructions before proceeding with the installation.
Keep this manual for future use.
• If you have any questions or doubts during installation, do not carry out any operations and contact
the support service.
• Use of these products for purposes other than those specified in these instructions is prohibited.
• You must not make any change to the components of the product unless stated in the manual in
order not to void the warranty; such operations can only lead to malfunctions; Politec assumes no
liability for malfunctions or damage due to modified products.
• Depending on the specific situation of use, check for the need for additional devices: detectors or
signalling devices.
• During installation, mounting and use of the product, make sure no foreign objects (solids, metals
or liquids) are able to penetrate inside the open devices.
• Manufacturer's liability:Politec assumes no liability for failures resulting from incorrect installation;
lack of maintenance, incorrect assembly or use.
• Politec is also not liable for incorrect or incomplete operation of the product or failure to detect
intrusion.
• Warranty (summary of conditions):Politec guarantees its products for a period of 2 years from the
production date.The warranty is applied to those purchasing directly from Politec; there is no
warranty for the end user who, in the event of breakdowns or faults, must contact the installer or
dealer.
• The warranty excludes aesthetic parts as well as parts subject to normal wear and parts subject to
normal consumption such as batteries and accumulators.
3.1 Additional warnings for devices powered by mains voltage
This manual is intended only for technical personnel qualified to install such devices.
• Assessing the hazards that may occur during installation and use of the system, in order to achieve
complete safety, it is necessary that installation takes place in full compliance with applicable laws,
methods, rules and regulations.
• Before accessing the internal terminals of the product, it is necessary to disconnect all the power
circuits.
• If automatic circuit breakers or fuses trip, before resetting them it is necessary to identify the fault
and repair it.
3.2 Installation warnings
• Check that all the material to be used is in excellent condition and suitable for use.
• Before proceeding with the installation, check the environmental class of the products in the
"technical specifications" chapter.
• Check, by comparing with the values shown in the paragraph "technical specifications".
• Do not place the system components close to heat sources as they could be damaged.
• Each product has its own operating principle: check the instructions for choosing the right position
in the respective instruction manual.
ADEBUS
5
POLITEC | INSTALLATION MANUAL - VER.2.1
4.Main components list
4.1 The control unit
The box contains the following components and accessories.
When opening the package, check that everything has been included.
4
5
2
3
7
1
6
N
o.
COMPONENT CODE
DESCRIPTION
1
ADEBUS
Adebus motherboard
2
ADEBUS ESP
Expansion board with 16
relay outputs
3
ADEBUS S2 BOARD
4
TRANSF LAR22S
18/24 Vac transformer
5
ALPO2B
Power supply board
6
BATTERY (not included)
17 Ah Battery
compartment
7
ADEBUS
TAMPER
6
POLITEC | INSTALLATION MANUAL - VER.2.1
5.Board Description
5.1 ADEBUS SC - Adebus motherboard.
Control board, to which RS485 is connected for barriers, Adebus Esp and LAN port
4
3
8
2
1
7
5
6
ADEBUS
No
.
COMPONENT
1
Serial input line COM0
2
Serial input line COM1
3
0-12 Vdc input
4
LAN socket
5
Relay outputs block
6
Inputs
7
Relay expansion connection
8
RS485 Adebus S2 board
7
POLITEC | INSTALLATION MANUAL - VER.2.1
5.2 ADEBUS ESP - Adebus ESP Relay board
Interface board between configured relay outputs and universal alarm control unit
6
1
5
4
2
3
ADEBUS
No.
COMPONENT
1
0-12 Vdc input
2
Relay outputs block 1-8
3
Output connector to next
expansion board
4
Relay outputs block 9-16
5
Input connector from CA 230
motherboard
6
Input connector from previous
expansion board
8
POLITEC | INSTALLATION MANUAL - VER.2.1
5.3 ALPO2B - Power supply board.
2
1
7
3
4
8
5
6
ADEBUS
No
.
COMPONENT
1
18 Vac input
2
24 Vac input
3
24 Vac output
4
0-13.8 Vdc outputs
5
Battery 12V - 17Ah output
6
Signalling outputs
7
10 A fuse (24 Vac)
8
3 A fuse (12 Vac)
9
POLITEC | INSTALLATION MANUAL - VER.2.1
6.Preparation for installation
6.1 Preparing the components before installation
Since the communication between the barriers and the monitoring control unit takes place by wire, it
is advisable to firstly check that all the parts of the control unit and sensors and any accessories are
present before beginning the installation.
6.2 It is advisable to carry out in the following ORDER:
•
•
•
•
•
•
•
•
•
The installation of the control unit application on a PC
The assembly and wiring of the barriers on the perimeters to be protected;
Alignment and functional verification of all barriers in the field without the use of software;
Taking note of the serial numbers of the individual barriers;
Site creation from Adebus Explorer software;
Barrier addressing;
System start-up via WEB page, System Configuration menu and individual column flags;
Adebus output configuration;
Barrier configuration;
Before proceeding with the installation, it is necessary to check the integrity of the product, the
adequacy of the model chosen and the suitability of the environment intended for installation:
• Check that all conditions of use fall within the "limits of use" and in the "Technical specifications of
the product".
• Check that the environment chosen for the installation is compatible with the total footprint of the
product.
• Check that the surface chosen for the installation of the product is solid so as to ensure stable fixing
and that it is adequately protected from possible impacts or atmospheric agents.
ADEBUS
10
POLITEC | INSTALLATION MANUAL - VER.2.1
7.Connections
7.1 Adebus internal connections
It is necessary to make the power supply connections for all the boards present, Adebus SC and
Adebus ESP respecting the polarity.Also check the connection between the Adebus board and Adebus
ESP
+12Vdc
7.2 Adebus- barrier connections
Connect the columns to the Adebus SC board using the dedicated shielded double twisted cable.It is
mandatory to connect the synchronism cables between one column and another for the barrier to
work correctly.
MES9C board Barrier 1
MES9C board Barrier 2
In
the
example,
synchronism
is
connected via a redblack cable, the BUS
signal on a green-white
cable,
the
braids
positioned
in
the
negative
ADEBUS
Red
Black
Braid
Green
White
11
Adebus board
POLITEC | INSTALLATION MANUAL - VER.2.1
7.3 Examples of cable connection
Up to 2 branches of serial bus can be used.The RS485 bus must not be connected in a star-shaped
manner and the loop must never be closed.Synchronism will be a closed loop if and only if the barriers
form a closed perimeter protection.
synchronism
bus
RS485 CABLE MANA SMA
E.g.Synchronism
connects all the
columns in a
loop.Bus connects
Adebus and all
the columns
ADEBUS
ADEBUS
ADEBUS
ADEBUS
ADEBUS
ADEBUS
ADEBUS
12
E.g.Synchronism
connects all the
columns.Bus
connects Adebus
and all the
columns
E.g.Synchronism
connects all the
columns.Bus
connects Adebus
and all the
columns
POLITEC | INSTALLATION MANUAL - VER.2.1
8.Installation and first access - DEFAULT STATIC IP 192.168.1.222
8.1.Access via Ethernet port.
The ADEBUS system is managed via a LAN port with a static IP address.The system can be accessed
remotely by activating the public IP address and opening the dedicated ports (port forwarding).For full
use of the system it is necessary to use the Adebus Explorer software and the web page located on
ports 8000 and 80 respectively.
8.2 Factory settings.
Static IP Address:192.168.1.222
Username: admin
Password: admin
Board reset procedure:
• Short-circuit pin3-4 by means of
jumpers with the power off
• Switch on and wait a couple of
seconds
• Remove jumpers
• Switch on again
8.3 Adebus Exlporer software installation and start-up
•
•
•
ADEBUS
The software is compatible with all versions of
Windows 7 and above.Install the software via the
setup.exe file
Connect the PC to the Adebus SC board via ethernet
cable.
Set Static IP address on PC via network board
settings.E.g.192.168.1.223
13
POLITEC | INSTALLATION MANUAL - VER.2.1
8.4 Main screen
At start-up, the program presents the available functions, the use of which is illustrated below.
Proceed in the order listed by the software.
8.5 Working Path
It allows you to change the working folder of the
program where the database of events and sites
downloaded in .sdf format is created.These
folders can be edited via the Settings menu,
Working folders.
By copying the database file and the site plan
image file it is possible to manage the systems
from different PCs.
ADEBUS
14
POLITEC | INSTALLATION MANUAL - VER.2.1
8.6 Site Creation
Through the "SITE EDITOR" menu, it is possible to create\edit the installation under management
New Site:
• Site Name
• IP address
• Serial
• Site plan image (.jpg,
.png only)
ADEBUS
15
POLITEC | INSTALLATION MANUAL - VER.2.1
8.7 Configuration Mode
By selecting the site via the
drop-down menu, access the
"CONFIGURATION MODE" menu
without connecting to the site.
FILE → Configuration mode
•
•
•
Using the right
mouse button,
create the columns
to be inserted on
the map and name
them.e.g. column
3, southwest
barrier
To simplify the
display, arrows can
be created to
identify the
sections.(visual
purpose only)
Complete the
entire perimeter by
entering all the
columns present
8.8 Address Setup
It is necessary to address the
columns by associating the
serial number with the address
(1-32)
• Connect to the site via the
«Connect» button
• Via the Utility menu, select
«Address Setup»: Utility ->
Address Setup
• Select the COM port where
the column to be addressed
is connected (COM0-COM1)
• Enter the 6-digit serial
number on the base of the
column and on the
motherboard E.g. 015476
• Select the unique address
from 1 to 32
ADEBUS
16
POLITEC | INSTALLATION MANUAL - VER.2.1
8.9 System Configuration from
WEB PAGE
Access the "System
Configuration" menu via the
web page
Flag all the barriers addressed
and click on "Save Config".In
this way, you "START" the active
communication between
Adebus and barriers.
E.g.
COM0: columns 1-2-3-4
COM1: columns 5-6
Section "Sectioning columns
association", used only if you
have purchased the SECTORING
package.
8.10 Adding or replacing barrier
To add a column at a later date or replace a column\ MES9012 motherboard, before addressing it
is necessary to interrupt the communication between Adebus and the barriers.
• Remove the flags from ALL the columns using the "System Configuration" web page
• Perform new addressing via Adebus Explorer software and «ADDRESS SETUP»
• Re-activate ALL flags in System Configuration
8.11 Popup
It is possible to enable alarm\tamper\offline popups.These Popups are used only if there is a PC
always connected to the Adebus, otherwise the display of the Popups takes place for all the events
previously recorded but not yet on the PC
ADEBUS
17
POLITEC | INSTALLATION MANUAL - VER.2.1
9.Access to the columns - Adebus Explorer
Access the site via Adebus Explorer software and connect using the «Connect» button
9.1 Key
•
•
•
•
•
Green: column in rest status
Light blue: column in
tamper status
Red: column in alarm status
X: OFFLINE column
Yellow: low 12V power
supply in column.
9.2 Column Detail
Position on a column using the mouse and by double clicking you can access any online column
on the site.
Current status
read only
ADEBUS
Current configuration
read only
18
New configuration
write
POLITEC | INSTALLATION MANUAL - VER.2.1
9.3 New Configuration
The "ADMIN" user can change the configurations present in the column by acting on the flags in
the right section enabling\disabling beams, AND functions, etc.
E.g.Current status:
E.g.Configuration:
E.g. New configuration
barrier in alarm with beams
1-2-3, antimask
Alignment level good only
for beam 4.
4 beams active
Sectioning
Crossing
Management via software
Speed (Intervention time) =
50ms
enabling S.Low function
(disqualification from fog)
N.B.:Good alignment value
for beam > 5.3V
N.B.:Soft.Config is the
configuration via software
and has priority over the
dip configuration present
on the board in the column
N.B.: to send the
configuration, click on SEND
The Force HW config button restores the hardware configuration set with the DIP switches on the
barrier board.
The Copy button copies the current configuration of the barrier in the New Configuration section
and by selecting the desired options it is possible to configure the barrier
The Advanced button is dedicated to a reserved section that is not accessible
ADEBUS
19
POLITEC | INSTALLATION MANUAL - VER.2.1
9.4 Input/Output associations
It is possible to associate each recorded event to a relay output/open collector present on the
Adebus and on the Adebus ESP boards.In the Outputs item inside the "New Configuration" it is
possible to have access to these settings.
Adebus-column
communication
loss
Association of
events
recorded by
the column
Special INPUT
association
linked in
column
For Sectoring
package only
Typically single relays are used for ALARM, SIGNAL LOW outputs of each column.
While a shared relay is used for TAMPER and OFFLINE outputs for all columns.
The relays work with OR logic if a relay is associated with outputs of several columns:
the relay is energised if at least one output changes status.
OUTPUTS
DESCRIPTION
1…7
Adebus SC outputs.
101 … 116
Adebus ESP 1 expansion board outputs.
201 … 216
Adebus ESP 2 expansion board outputs.
301 … 316
Adebus ESP 3 expansion board outputs.
401 … 416
Adebus ESP 4 expansion board outputs.
501 … 516
Adebus ESP 5 expansion board outputs.
601 ... 616
Adebus ESP 6 expansion board outputs.
1001 ... 1032
Barrier outputs (1001 = barrier 1, ..., 1032 = barrier 32).
1099
All outputs of the barriers.
9.5 Polarity
It is possible to invert the polarity of each individual output present on Adebus.
ADEBUS
20
POLITEC | INSTALLATION MANUAL - VER.2.1
10.Event Archive
From the Archive menu you can access the history of events recorded on the PC.To download the
events, simply connect to the Adebus board of the site locally or remotely.Each Adebus SC board
stores a maximum of 32000 events.
The file format is downloadable and is a .sdf type
The events are recorded continuously by default.For controlled recording start, it is
necessary to act by balancing with 1K resistor on INPUT 1 of the Adebus SC board.Via the
WEB page go to the "Output Configuration" menu and flag Master Input 1 enabled
storage.The storage in this case occurs if the input is balanced.
ADEBUS
21
POLITEC | INSTALLATION MANUAL - VER.2.1
11.Appendix A - WEB page
The statuses and some configurations can be managed via the WEB page
11.1 Columns detail
Display of the status of each
column.
11.2 Columns status
Display of the communication
status between adebus and
column.Good communication is
with a ratio:GOOD COM:BAD
COMM> 300:1
ADEBUS
22
POLITEC | INSTALLATION MANUAL - VER.2.1
11.3 Output Configuration /
Output Polarity
Output and polarity
configuration of each column.
11.4 Network Configuration
It is possible to change the
Adebus address.By default the
ports are the 8000 not editable
for the software and the 80
editable for the web page.
ADEBUS
23
POLITEC | INSTALLATION MANUAL - VER.2.1
12.Appendix B - barrier configuration and statuses
Listed here are the meanings of all the statuses and configurations present inside the columns.
12.1 Status
ALARM
TAMPER
SIGNAL LOW
MASK
HEATER
ALARM LED
VIN OUT RANGE
VIN LOW
POWER LOW
BEAMS TEST
RELAY
IN 1
IN 2
IN 3
SECTIONING
RAY ALARM
RAY LOW
RAY MASK
ADEBUS
Barrier alarm status
Column tamper status
Disqualification status
Barrier antimask status
Heater status
Status of the ALARM LED on the motherboard
Input power supply out of range 10-30Vcc
Low input power supply (less than 11.4V, in this case the power supply
is via battery)
Low voltage stabilised inside the column (< 8V)
Indicates whether the barrier has remained under test for alignment
Status of the alarm relay, whose function can be changed using the RLC
command
Special Input 1 status (BEAM input of the MES9C terminal board located
on the base of each individual column).It is a balanced 15kΩ input.In
case of normal operation, its value is equal to 2.In the case of an open
status, its value is 0.If it is balanced at 30kΩ, its value is 1.For further
details, see the MANA IR barrier manual
Special Input 2 status (AND input of the MES9C terminal board located
on the base of each individual column).It is a balanced 15kΩ input.In
case of normal operation, its value is equal to 2.In the case of an open
status, its value is 0.If it is balanced at 30kΩ, its value is 1.For further
details, see the MANA IR barrier manual
Special Input 3 status (Gin input of the MES9C terminal board located
on the base of each individual column).It is normally open and its value
is 0.In an event occurs, it is short-circuited to ground and its value is
1.For further details, see the MANA IR barrier manual
If the SECTIONING function is enabled, it provides information about
the last sector crossed
From the sector closest to the column to the
1…5
furthest in ascending order
6
Crawl sector
7
All rays obscured
Status of the rays resulting in alarm
Rays in low signal area (disqualification)
Rays in masking status
24
POLITEC | INSTALLATION MANUAL - VER.2.1
12.2 Analogue Values
INPUT VOLTAGE
Column input voltage value
POWER VOLTAGE
Voltage value stabilised inside the column
CURRENT
TEMPERATURE
Current consumed by the column
Current temperature
Voltage value of the PEAK signal in reception (does not
correspond to the value measured by the multimeter
on the individual RX optic) For a good alignment V>
5.2V
RX1, RX2, RX3,
RX4 LEVEL
12.3 Configuration
MODEL
SERIAL NO
SOFT.CONFIG
RX CHANNELL
TX CHANNELL
BEAM1
BEAM12
AND RND
AND12
RX1, RX2, RX3, RX4
SIGN LOW1
RLC
SECTIONING
ADEBUS
Product Model
Serial number of the column and corresponding
motherboard
If active, the column configuration is managed using
software.It has priority over configuration via DIP
Not Implemented
Not Implemented
Exclusion of beam one of the barrier
Exclusion of beams one and two of the barrier
The system only goes into alarm if at least two RX optics
are obscured
The system goes into alarm if both RX 1 and 2 optics are
obscured or if at least one of the other optics is
interrupted
Status of individual receiver optics.Up to 3 receiver
optics can be deactivated
The barrier enters a disqualified status with AT LEAST
one of the RX optics that receives a low signal in case of
fog.If it is only the first optic to detect a low signal, but
not sufficient for the alarm, only the latter is inhibited,
maintaining the normal operating status of the barrier
Allows you to configure the alarm relay on the column
to close (or open) according to an event at your
discretion
It enables the SECTIONING function
25
POLITEC | INSTALLATION MANUAL - VER.2.1
CROSS
A.CRAWL
OPT./WIRE
SIGN LOW
BYPASS
RANDOM DELAY
ANTIMASK
RAY TEST 1, 2, 3, 4
SPEC.INP
SPEED
ADEBUS
The crossing function is enabled for which the
barrier works with crossed beams.For details, see
the MANA barrier manual
The anti-crawl function is enabled for which only
the first RX optic works with an intervention time
of 2 seconds.It has priority over other functions
such as AND12 or AND RND.In particular, the
system goes into alarm regardless of the status of
the other receiver optics
Not Implemented
It allows the disqualification status
Barrier inhibition for one minute
The system presents each time a random alarm
delay ranging from 0 to 1 sec
It allows the barrier antimask reading
It allows you to activate one transmitter optic at a
time.This function can be used to carry out
alignment checks on an individual receiver optic
It allows you to use special inputs on the terminal
board of the MES9C barrier.In particular, it is
possible, for example, to add a sensor connected
on the Special Input 1 (BEAM input of the terminal
board), one on the Special Input 2 (AND input) and
one on the Special Input 3 (Gin input).For details,
see the MANA barrier manual
It is the intervention time of the barrier expressed
in milliseconds.By default it is set to 50ms
26
POLITEC | INSTALLATION MANUAL - VER.2.1
13.Appendix C - Special Inputs
On all barriers it is possible to associate the outputs of sensors external to the infrared
barrier with special inputs.
13.1 Connection in barrier
IN1-IN2:The system reacts to a balanced input with 3 possible statuses:
STATUS 2:R balanced at 15K
STATUS 1:R balanced at 30K
STATUS 0: open circuit
MES9C board
IN3:STATUS 1: short circuit to GND
STATUS 0: open circuit
NC
R
GND
IN3:
Connect the NC
output referring to
GND of the external
sensor to terminal
14
IN1-IN2:
Connect
to
terminals 15 or 16
any alarm signal
from any external
sensor, by balancing
at 15k or 30k.
13.2 Enabling and software status
Status of the special inputs
IN1, IN2, IN3
ENABLE SPEC INP to activate
the reading function of the
external inputs
ADEBUS
27
POLITEC | INSTALLATION MANUAL - VER.2.1
13.3 Output configuration
For each input used on each column, enable the outputs configured in this way
INPUT1-INPUT2:
The set relay will change status
if the input goes from status 2
to status 0 (e.g. relay 601) or if
the input goes from status 2 to
status 1 (e.g. relay 609)
INPUT3:
The set relay will change status
if the input switches from DC to
AC with respect to GND (e.g.
relay 410)
ADEBUS
28
POLITEC | INSTALLATION MANUAL - VER.2.1
14.Appendix D - Sectioning
To use this function it is necessary to purchase the special Sectoring package which requires
special firmware inside the barrier motherboards.
This function allows you to estimate the crossing position of the barrier
14.1 Enabling in pairs - Sectioning
From the WEB page select the pairs that are working in sectoring.In the example only the pairs 12 and 5-6 work with this function.The outputs for the sectoring function in this case will be
present on column 1 and column 5.
ADEBUS
29
POLITEC | INSTALLATION MANUAL - VER.2.1
.
14.2 Area configuration - Sectioning
Using the "Sectioning
config" button on the
"System configuration"
web page, it is possible
to select the number of
sectors for each section.
It is also necessary to
indicate the length of the
section
Barrier
Number of
sectors
Special
sectors
Columns
distance
ADEBUS
Select the pair of columns that create the barrier
Number of sectors that make up the section
All beams obscured
If selected, information is provided on all the
obscured beams of the barrier
Crawling
If selected, the crawling information is provided
The distance between the columns of the barrier must be selected
30
POLITEC | INSTALLATION MANUAL - VER.2.1
14.3 Software configuration - Sectioning
In order to associate the
relay outputs for each
sector, access the
Outputs of the first
column of the barrier
and configure the sectors
concerned.
The Outputs to be
enabled for sectioning
are exclusively on the
first column of the
enabled pair.
COLUMN
2
COLUMN
1
A
B
C
COLUMN
2
COLUMN
1
A
ADEBUS
B
C
31
D
E
POLITEC | INSTALLATION MANUAL - VER.2.1
15.Technical Specifications
Enabled for product
communication
Max 32 columns:MANA IR SMA, MANA DT SMA, PARVIS
MES SMA, SANDOR PLUS SMA
Management software
Proprietary software complete with graphical user
interface with layout for column localisation and
configuration
Serial ports
2 RS485 including 1 optional
Serial bus line length
1km for each line with indicated cable
Event storage capacity
32000 exportable
Communication output
LAN
Real-time visualisation
Status of each column
Interface outputs
3 Relays + 4 Open Collector on Adebus SC
16 Relays on Adebus ESP
6 Adebus ESP
Power supply
220V with dedicated 13.8V power supply
Battery housing
12V up to 17Ah
Ingress protection rating IP
IP 44
Dimensions (HxWxD)
400 x 320 x 135 mm
16.Product Disposal
All components of the product are an integral part of the equipment and must be disposed of together with
it.Just as with installation operations, also at the end of life of these products, the dismantling operations
must be carried out by qualified personnel.These products are made up of various types of materials: some
can be recycled and others must be disposed of.Find out about available recycling or disposal systems for this
category of products governed by regulations in force in your area.
Warning!- Some parts of the products may contain polluting or dangerous substances which, if dispersed in
the environment, could result in harmful effects on the environment itself and on human health.As indicated
by the symbol on the side, it is forbidden to throw these products in domestic waste.Therefore, carry out
"separate collection" for disposal, according to the methods stipulated by the regulations in force in your area
or return the products to the seller when purchasing a new equivalent product.
Warning!- Local regulations can impose heavy penalties for incorrect disposal of these products.
For technical support, contact your security systems distributor
ADEBUS
32
POLITEC | INSTALLATION MANUAL - VER.2.1

advertisement

Key Features

  • Perimeter Protection
  • Up to 32 Columns
  • Web Interface
  • Real-time Monitoring
  • Event Archiving

Related manuals

Frequently Answers and Questions

What is the default IP address for accessing ADEBUS?
The default static IP address for ADEBUS is 192.168.1.222.
How many columns can be managed by ADEBUS?
ADEBUS can manage up to 32 columns.
What type of software is used to manage ADEBUS?
ADEBUS is managed through Adebus Explorer software and a Web interface.
How do I enable the sectioning function?
You need to purchase the special Sectoring package that includes special firmware for the barrier motherboards.
Download PDF