Thermoscreens Ecopower Installation, Operation And Maintenance Instructions

Add to My manuals
6 Pages

advertisement

Thermoscreens EcoPower Installation, Operation & Maintenance Manual | Manualzz
Controls.
EcoPower
INSTALLATION, OPERATION AND
MAINTENANCE INSTRUCTIONS
English
T9901125-1-1 UK
Page | 1
1
CONTENTS
Page
1
CONTENTS ................................................................................................................................... 2
2.
DELIVERY CONTENTS ................................................................................................................ 3
3.
REMOTE CONTROL INSTALLATION .......................................................................................... 4
4.
REMOTE CONTROL OPERATION............................................................................................... 5
Thermoscreens Ltd
St. Mary’s Road
Nuneaton
Warwickshire
England
CV11 5AU
Email: [email protected] — http://www.thermoscreens.com
Tel: +44 (0) 24 7638 4646 — Fax: +44 (0) 24 7638 8578
T9901125-1-1 UK
Page | 2
2.
DELIVERY CONTENTS
Depending on the optional controllers and air curtain model selected one of the following controllers is
supplied.
NOTE: If any parts are missing or damaged contact your place of purchase.
Ecopower Remote Control
Ecopower Plus Remote Control
(for Electric and Water Heated units)
(for Electric and Water Heated units)
OR
Supplied with 6m RJ Control Cable
Remote Control Switch
(for Ambient units)
T9901125-1-1 UK
Page | 3
3.
REMOTE CONTROL INSTALLATION
Mount the Ecopower or Ecopower Plus Remote Control in a convenient position directly to the wall or
onto a switch box. As the Remote Control has a room air temperature sensor in it, which may be
selected, avoid a location where the Remote Control would see false room temperatures such as in
direct sunlight or on a very cold wall. Seal any openings going into the wall at the rear of the control to
avoid cold draughts blowing into the control and giving false temperatures.
3.1
Step 1
Ecopower Controller Wall Mounting
Using a screwdriver undo the screw on the top of the Remote Control case and pull the back
case away (see Fig 1 and Fig 2 below).
Fig 1
Fig 2
Step 2
Feed one end of the RJ control cable through the back case,
secure it, then screw the back case to the wall using suitable
fixings (not supplied) (see Fig 3).
Step 3
Connect the RJ plug to the RJ socket on the PCB in the
Remote Control.
Step 4
Refit the front case.
3.2
Fig 3
Ecopower Plus Controller Wall Mounting
Step 1
Place a slotted screwdriver to each slot on the bottom edge of
controller (see Fig 4). Push and twist to release the top half of
the controller.
Note: dimensions of controller are 148 x 90 x 33mm (l x h x d).
Step 2
Feed one end of the RJ control cable through the back case,
secure it ensuring the back case slots are towards the bottom
and then screw the back case to the wall using suitable fixings
(not supplied).
Step 3
Connect the RJ plug to the RJ socket on the PCB in the
Remote Control.
Step 4
Refit the front case.
Fig 4
Fig 5
T9901125-1-1 UK
Page | 4
3.3
Remote Control Settings
On the back of the PCB inside the Ecopower/Ecopower Plus
Remote Control you will find four DIP switches (see Fig 6) that
provide optional features detailed in Table 1 below.
Fig 6
Table 1
DIP
1
Feature
Reset on power-up
2
Stop fan on cold
3
Never blow cold
4
Room air
temperature control
4.
4.1
Explanation
On restoring power after an
electrical interruption all Remote
Control settings are retained
Fans are switched off when
heating level is achieved (AUTO
mode only)
Air curtain always heats in
AUTO mode
Enables the room air sensor in
the Remote Control
Default
ON
Notes
WARNING! – Fans start
on their own after power
is restored
OFF
OFF
OFF
Will not go to ambient
mode
Disables all other
temperature sensors
REMOTE CONTROL OPERATION
Remote Control Switch (for Ambient units)
4
3
2
1
1 On/Off
Turns the air curtain fans On or Off.
2, 3 & 4 Fan speed
Switch fan speed between Low, Medium and High respectively.
T9901125-1-1 UK
Page | 5
4.2
Ecopower/Ecopower Plus Remote Control (for Electric and
Water Heated units)
Heating level scale
Use the Remote Control to operate the air curtain as follows:
1 On/Off
Turns the air curtain On or Off.
NOTE: If an electric heated air curtain is heating when switched off the fan will run-on for
approximately 2 minutes to dissipate excess heat.
2 Manual/Automatic
Switches between Manual and Automatic modes.
The Auto On indicator LED is lit for "Auto Mode" and unlit for "Manual Mode".
3 & 4 Heating level controls
Manual mode
Select heating level from zero, to half heat, to full heat by stepping up or down with the heating level
controls. The heating level scale shows the level selected.
Automatic mode
Heat output is controlled automatically according to:


Inlet air temperature, or
Room air temperature
This is dependent on the settings made in Section 3.3 Remote Control Settings (DIP switch 4).
5, 6 & 7 Fan speed
Switch fan speed between Low, Medium and High respectively. The appropriate LED illuminates.
NOTE: for small lobby areas, operate air curtain in automatic mode (recommended).
T9901125-1-1 UK
Page | 6

advertisement

Key Features

  • Remote Control
  • Heating Levels
  • Fan Speeds
  • Automatic Mode
  • Room Temperature Sensing

Related manuals

Frequently Answers and Questions

Can I use the EcoPower air curtain in both electric and water heated modes?
The EcoPower can be used with both electric and water heating depending on the model you purchased. Check your specific manual for confirmation.
How do I set up the EcoPower remote control?
Refer to the installation instructions in your manual for a step-by-step guide on mounting the remote control, connecting the control cable, and setting up the DIP switches for desired features.
What does the “Auto On” indicator LED mean on the EcoPower remote control?
The “Auto On” LED indicates that the air curtain is operating in Automatic mode. In this mode, the heating output adjusts automatically based on your set temperature and environmental conditions.
Download PDF

advertisement