Dossena DER3BDUAL Quick Start Manual
Dossena DER3BDUAL is a type B residual current device designed for use in low-voltage (LV) networks. This device is ideal for protecting various applications, including inverters, UPS systems, EV charging stations, machine tools, frequency converters, and photovoltaic systems. The DER3BDUAL is capable of detecting both AC and DC residual currents, offering enhanced protection against potentially hazardous situations.
PDF
Download
Document
Advertisement
Advertisement
Codice Ordinazione/ Order Code: 9DER3BDUAL/2I – 9DER3BDUAL/6D- 9DER3BDUAL/2IR- 9DER3BDUAL/6DR DER3BDUAL MU 1220 R .8 EV CARATTERISTICHE TECNICHE/ TECHNICAL CHARACTERISTICS Alimentazione ausiliaria/ Auxiliary power supply Us Tensione di alimentazione/ Auxiliary power supply 48 ÷ 400 Vca/ac -15/+10% (@50/60Hz ) Uimp Categoria sovratensione/ Overvoltage category Consumo max/ Max consumption ≤ 4VA Grado inquinamento/ Pollution degree Circuito controllato (in abbinamento a toroidi dossena) / Monitored circuit (by using Dossena toroids) Tipo di MRCD/ Type of MRCD B Norme di riferimento/ Standards Un Tensione nominale/ rated voltage <1000Vca/ac (@50/60Hz) - <1500Vcc/dc Uimp Sistema di distribuzione/ Distribution system TT, TN Icw Tipo di Misura/ Measurement type TRMS Tipo di regolazione/ Adjustment Campo di regolazione IΔn/ Adjustment range IΔn 0,05 ÷ 7A Campo di regolazione Δt/ Adjustment range Δt D35 D60 D80 D110 D160 D210 Categoria sovratensione/ Overvoltage category In Massima corrente nominale/ Maximum rated current 480A 720A 1020A 1560A 1860A 2160A Grado inquinamento/ Pollution degree Collegamenti toroide-relè/ Connections toroid-MRCD Cavi schermati twistati/ Shielded twisted cables Involucro/ Housing Classe di isolamento/ Insulation class Grado di protezione/ Protection degree Contatti uscita/ Output contacts Tipo di Interfaccia seriale/ Serial interface Terminazione linea seriale/ Serial line termination Isolamento galvanico seriale/ Serial line insulation Massima altitudine/ Maximum altitude II sul frontale/ II on the front Tenuta al fuoco/ Fire resistance IP40 frontale/ front panel IP20 morsetti/ terminals Altre caratteristiche/ Other features 2 NA-C-NC 250Vca/ac 5A (P.F.= 1)/ 30Vcc/dc 3A Sezione max morsetti/ Max. terminals section RS485 Modbus RTU Spellatura conduttori/ Cable strip 120Ω Coppia di serraggio/ Tightening torque <1kV @50Hz Temp.di funzionamento/ Operation temperature 2000m Temp. di stoccaggio/ Storage temperature 4kV CAT II 2 IEC 60947-2:2019 8kV 40kA (1s) Continua/ continuously variable Inst./ 0,06 ÷ 5sec. CAT III 2 Involucro in classe: V0 Housing class: V0 2,5mm2 7mm 0,6Nm -10 ÷ +55°C -20 ÷ +80°C Generalità: I relè differenziali di tipo B, della serie DER3BDUAL, perfettamente conformi alla normativa vigente (IEC 60947-2:2019), possono essere impiegati su reti BT in corrente continua (un polo a terra), alternata (TT,TN) o mista. La serie è consigliata per la protezione di inverter, UPS, colonnine di ricarica auto, macchine utensili, convertitori di frequenza, impianti fotovoltaici, ascensori, torni, frese ed ecc, dal momento che sono sempre più diffusi dispositivi che generano correnti disperse di tipo continuo o miste, che i normali relè differenziali in classe A, AC non rilevano. ISTRUZIONI DI INSTALLAZIONE E PRECAUZIONI DI SICUREZZA: Tutte le operazioni di installazione e manutenzione devono essere eseguite da personale qualificato in assenza di tensione ed in totale regime di sicurezza elettrica, nel rispetto delle normative vigenti. 1) Prima di alimentare l’apparecchiatura DER3BDUAL verificare di aver eseguito correttamente tutti i collegamenti necessari. 2) Installare SEMPRE il differenziale insieme ai toroidi serie B e D (DER3BDUAL + TOROIDE SERIE D + TOROIDE SERIE B). 3) La sezione dei conduttori deve essere tale che la resistenza totale di ciascuna connessione DER3BDUAL ↔ trasduttori sia inferiore a 0,5Ω. 4) Ridurre al minimo la distanza dei collegamenti tra DER3BDUAL e toroidi tenendoli il più lontano possibile da cavi di potenza; utilizzare cavi twistati (mantenere separato il circuito di misura da quello di prova) e schermato con lo schermo isolato dai conduttori interni e connesso a terra in un solo punto. 5) Alla prima messa in servizio eseguire la calibrazione dei toroidi (vedi sezione SETUP alla voce CAL). STATO DI NORMALE VIGILANZA (display verde) Pag 1: Visualizzazione in vero valore efficace (TRMS) della dispersione in corrente alternata (I∆ AC TRMS) e in corrente continua (I∆ DC TRMS) presenti in impianto, espresse in A. Pag 2: Visualizzazione in vero valore efficace (TRMS) del totale della corrente differenziale dell'impianto (I∆) e relativo valore in % della corrente dispersa in CA (corrente alternata) e CC (corrente continua). Altri parametri visibili in entrambe le pagine: ∆t= tempo limite di non intervento Istogramma istantaneo identificativo della corrente dispersa in CC (segmento pieno) e CA (segmento a righe diagonali) AL= visualizzazione grafica della soglia di allarme impostata Funzione dei pulsanti (nella versione 6D i tasti sono sulla destra): ►: Premendo questo tasto si sceglie la visualizzazione di Pag 1 (valori in TRMS) o Pag2 (valori in %). : Premere per variare il contrasto del diplay. TEST: Il test verifica l'intero sistema di protezione differenziale (DER3BDUAL+ Toroidi serie B e D + B.A.): Premere brevemente il tasto TEST per eseguire il test. In breve il display si colorerà di rosso, il relè di TRIP e il 2° relè cambieranno di stato. Compariranno lampeggianti il segnale di pericolo e la scritta TRIP. Se il riarmo è impostato su manuale (MAN), premere il tasto RESET per resettare il differenziale. Note: In seguito di forti anomalie e sollecitazioni elettromagnetiche potrebbe accadere che sul display scompaia la simbologia; in tale caso premere semplicemente il tasto ► per ritornare alla normale visualizzazione. STATO DI SETUP (display azzurro) CAL= pulsante per la calibrazione dei toroidi. Tale operazione va eseguita in totale assenza di corrente differenziale.Entrati in SETUP, premendo il tasto di SET per 3 sec. (display azzurro) sarà necessario premere due volte velocemente il tasto CAL. Il display si colora di viola e il dispositivo esegue la calibrazione automaticamente. Questa operazione è assolutamente necessaria per la messa in servizio dello strumento. Se la calibrazione va a buon fine il display ritorna blu e non sarà mai più necessario ripetere tale procedura. Non è possibile effettuare l'operazione di calibrazione in presenza di allarmi rilevati dal dispositivo (ALA – TRIP- TORO). (nella versione 6D i tasti sono sulla destra) 1- premere per almeno 3 secondi il tasto SET per entrare nel SET UP (display apparirà azzurro). 2- premere rapidamente il tasto SET per passare da un parametro all’altro in modo ciclico (il parametro in setting apparirà lampeggiante). 3- premere ▲▼per modificare il parametro selezionato. 4- premere per almeno 3 secondi SET per uscire dal SET UP, salvando i parametri impostati (display torna verde). Dopo circa 3 minuti di inattività il DER3BDUAL esce automaticamente dal SET UP, senza salvare le modifiche. Note: Nella fase di SETUP in caso di Allarme/Trip, il DER3BDUALinterverrà secondo le impostazioni del precedente SETUP. Per vederne la causa, uscire dal SETUP. PARAMETRI RANGE [DEFAULT] IΔn (A)= Soglia della corrente di dispersione nominale: valore al quale la IΔ provoca l'intervento del relè di TRIP . 0,05 ÷ 7A [0,05A] ΔT= Tempo limite di non intervento(s): ritardo entro il quale una corrente differenziale più elevata di IΔn impostata può fluire nel DER3BDUAL senza provocarne l'intervento (se = “INST” il differenziale funzionerà senza ritardo con intervento Istantaneo). 0,06 ÷ 5Sec. [0.060S] A – rappresenta il 2° relè e funziona come relè di allarme: cambio di stato al superamento della soglia di allarme impostata. T – rappresenta il 2° relè e funziona come secondo relè di TRIP: cambio di stato contemporaneamente al relè di TRIP (la bobina di apertura deve comunque essere sempre collegata al relè di TRIP). T/ A [A] N.De.= rappresenta lo stato di riposo del relè di TRIP. E’ normalmente diseccitato (N.De.) e si eccita quando la IΔ supera la IΔn. NE= rappresenta lo stato di riposo del relè di TRIP. E’ normalmente eccitato (N.E.) e si diseccita quando la IΔ supera la IΔn. Attenzione: la condizione di N.E. (sicurezza positiva) è applicata solo ed esclusivamente al relè di TRIP e non al secondo relè anche se impostato in configurazione TRIP. L'impostazione della sicurezza positiva esclude la vigilanza continua del circuito della bobina di apertura B.A. e della sua alimentazione. N.De. - N.E. [N.De.] MAN/AUTO: Modalità di funzionamento del RESET: manuale o automatico. In modalità MAN, a seguito di uno scatto per IΔ>IΔn, la scritta “SET” diventa “RESET” e permetterà quindi il RESET della condizione di TRIP (solo se IΔ<IΔn). MAN- AUTO [MAN] ◄ AL: Soglia d’allarme (% di IΔn). Al superamento di tale soglia si genera una condizione di allarme. 20% ÷ 80% [50%] <R: Valore percentuale d'isteresi rispetto alle soglie impostate. 30% ÷ 80% [80%] KCT= rapporto di trasformazione del toroide .NON VARIARE QUESTO PARAMETRO . BA AL= Se impostato su ON la continuità della bobina di apertura e la sua alimentazione sono vigilati costantemente, generando allarme in caso di anomalia. ON-OFF [ON] NODE= Nodo di rete: assegnare ad ogni singolo DER3BDUAL un numero di nodo (solo per versioni dotate di uscita seriale RS485). 1 ÷ 247 [1] BAUD= Configurazione velocità seriale (solo per versioni dotate di uscita seriale RS485). 4800 ÷ 38400 [19200] Pag 2 di 4 Introduction: The residual current device type B DER3BDUAL series, fully compliant with IEC 60947-2: 2019, can be used in LV network in DC (pole to ground), AC (TT, TN) or mixed current. The series is recommended for the use with inverter, UPS, frequency converters, photovoltaic system, production facilities on construction sites, lifts, lathes, milling machines, since these devices, that generate direct or mixed residual current, which the normal residual current devices type A-AC don't detect, are becoming more common. INSTALLATION SUGGESTIONS AND SAFETY PRECAUTION: All installation and maintenance operations must be carried out by qualified personnel in the absence of voltage and in a total electrical safety regime, in compliance with the safety regulations. 1) Before powering the DER3BDUAL, check that all connections have been executed properly. 2) ALWAYS install DER3BDUAL by using Dossena toroidal transducers B and D series (DER3BDUAL + B toroid + D toroid). 3) The cross-section of the conductors must be such that the total resistance of each DER3BDUAL ↔transducer connections does not exceed 0.5Ω. 4) Minimize the distance connections between DER3BDUAL and transducers and keep them away from power cables; use twisted shielded cables, with the shield connected to ground at one point only (keep the measurement circuit separate from test circuit). 5) At the first commissioning perform the calibration of toroids, please view section SETUP item CAL. NORMAL VIGILANCE (GREEN DISPLAY) Pag 1: The system alternating residual current (I∆ in Ampere AC TRMS) and direct residual current (I∆ in Ampere DC TRMS) are shown in this page. Pag 2: The system total residual current (I∆ in Ampere) and relative % value of residual current in AC (alternating current) and DC (direct current) are shown in this page. Others parameters in either pages: I∆n= Threshold of the nominal residual current. ∆t= Limiting non-actuating time. histogram = Instantaneous histogram that identifies residual current in DC (solid segment) and AC (diagonal stripes segment) . AL= Alarm threshold. Keys function (for 6Din version the keys are on the right side): ►: Push this button to display Pag1 (value in TRMS) or Pag 2 (% value). : Push this button to adjust the contrast. TEST: The test checks the complete protection system (DER3BDUAL+ B and D Toroids series + T.C.). Push quickly the test button to start the test. Display becomes red. TRIP relay and the 2nd relay change state. Danger signal and message “TRIP” appear flashing. Press “RESET” button to reset, if the reset mode is set as manual mode (MAN). Note: In case of strong electromagnetic disturbances the display may go blank or irregular: push the button ► to restore the normal display. SETUP (BLU DISPLAY) CAL= button for toroids calibration. This operation must be perfomed in total absence of differential current dispersion. Enter in SETUP, by pushing SET button for at least 3 sec (blue display), then pushing quickly for two times CAL button. The display appears violet and the device make the calibration automatically. This operation is absolutely necessary for commissioning of the instrument. If calibration will be good, the display backs to blue and it will no longer be necessary repeat this procedure. It's not possible make calibration if an important alarm is detected by device (ALA – TRIP - TORO). 1 -push SET button for at least 3 seconds to enter in SET UP (display becomes blue). 2- push quickly SET button to select cyclically the parameter to modify (it will appear flashing). (for 6Din version the keys are on 3- push ▲▼ buttons to modify the selected parameter. the right side) 4- push SET button for at least 3 seconds to exit from SETUP and save the parameters (display returns green). DER3BDUAL automatically exits from SETUP without saving modification, after 3 minutes of inactivity. Note: The new setup parameters will be operative only after saving. If an alarm occurs in setup, it is caused by the previously set parameters. PARAMETERS RANGE [DEFAULT] IΔn (A)= Threshold of the nominal residual current: when IΔ exceeds I∆n, the TRIP relay switches. 0,05 ÷ 7A [0,05A] ΔT= Limiting non-actuating time. If you set it to "INST", the tripping mode becomes instantaneous. 0,06 ÷ 5sec [0.060S] T – The 2nd relay is a second TRIP relay: it switches at the same time of TRIP relay (the trip coil must be always connected to TRIP relay). A – The 2nd relay is an alarm relay. It switches when set alarm threshold is exceeded. T/ A [A] N.de. = Trip relay is normally de-energized (N.De.) and it energizes when IΔ overcomes IΔn. NE= Trip relay is normally energized (N.E.) and it de-energizes when IΔ overcomes IΔn. Warning: the safety condition N.E, is applied exclusively to the TRIP relay and not to second relay, even if it is set in TRIP condition. Setting the positive security (fail safe) excludes the permanent verification of the T.C. circuit and its power. N.De. - N.E. [N.De.] MAN/AUTO: Reset mode: manual or automatic. After a trip for IΔ> IΔn, the written "SET" becomes "RESET" and will therefore allow the RESET of the TRIP condition (only if IΔ <IΔn) MAN- AUTO [MAN] ◄ AL: Threshold of Alarm (% di IΔn). When this threshold is exceeded, an alarm condition will be generated. 20% ÷ 80% [50%] <R: Hysteresis: threshold in percentage value of IΔn. 30% ÷ 80% [80%] KCT= transformation ratio of toroid DON'T CHANGE THIS PARAMETER . BA AL= When “ON” the continuity, the connections and the power supply of T.C. are continuously monitored and an alarm will be generated in case of malfunction. ON-OFF [ON] NODE= Configuration network node: assign to each DER3BDUAL a node number (only for versions equipped with serial output RS485) 1 ÷ 247 [1] BAUD= Serial baudrate configuration (only for versions equipped with serial output RS485) 4800 ÷ 38400 [19200] Pag 3 di 4 ALLARMI: Il simbolo di pericolo è sempre visibile a display/ ALARMS: the danger symbol is always visible on display MSG COLORE/ COLOR ALA lampeggiante giallo/rosso flashing yellow/red EVENTI/ EVENTS Il 2° relè cambia di stato (solo se impostato come relè di allarme). Incremento dell'istogramma. Incremento del valore di corrente I∆. CAUSA/ CAUSE Superamento soglia allarme La corrente di dispersione I∆ ha superato la soglia di allarme . Alarm thereshold exceeded: The residual current I∆ exceeds alarm threshold. The 2nd relay switches (only if it set as alarm relay). Increasing of histogram. Increasing of I∆ current value. BA lampeggiante giallo/rosso Il 2° rele cambia stato. The 2nd relay switches. flashing yellow/red TRIP rosso fisso Red Il rele di Trip e il 2° rele cambiano di stato. Incremento dell'istogramma. Blocco della visualizzazione sul valore di corrente per cui è avvenuto l'intervento. ALLARME B.A.: Possibile problema della BA (disconnessa o assenza tensione) o interruttore non armato. ATTENZIONE: Se l’impianto non fa uso della BA occorre disabilitare tale controllo. B.A. ALARM: Possible T.C. problem (disconnection, no voltage) or no armed circuit breaker. WARNING: Disable this monitoring, if no TC is used in the system. ALLARME DI TRIP La corrente di dispersione I∆ ha superato almeno l'85% della soglia I∆n. TRIP ALARM (I∆n) The residual current I∆ has exceeded at least 85% of threshold I∆n. The Trip relay and the 2nd relay change state. The increasing of histogram. The visualization is blocked on current value for which DER3BDUAL has been tripped. TORO rosso fisso Red Il rele di Trip cambia di stato. Il 2° rele cambia di stato solo se impostato come secondo relè di trip. The Trip relay switches. The 2nd relay switches only if it is set as second trip relay. TEMP rosso fisso Red ALLARME TOROIDE Problema toroidi: o manca un collegamento o possibile presenza di cortocircuiti sugli avvolgimenti. TOROID ALARM Toroids problem: either there is a disconnection or there is a short in its windings. ALLARME TEMPERATURA Eccessiva temperatura interna . TEMPERATURE ALARM Excessive internal temperature. Pag 4 di 4 ">

Public link updated
The public link to your chat has been updated.
Advertisement
Key features
- Type B residual current detection
- AC and DC current monitoring
- Adjustable trip threshold
- Selectable reset mode
- Alarm function
- Serial communication interface (RS485)
Frequently asked questions
The DER3BDUAL is a type B residual current device that protects electrical circuits and equipment from dangerous residual currents, both AC and DC.
To calibrate the DER3BDUAL, follow the instructions in the 'SETUP' section of the manual. Ensure there is no differential current flowing during the calibration process.
The DER3BDUAL can provide alarms for various conditions, including overcurrent (TRIP), alarm threshold exceeding (ALA), toroid issues (TORO), and high internal temperature (TEMP).