INSTRUCTION MANUAL
CURRENT LOOP SUPPLY
(with square root extractor)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■■PACKAGE INCLUDES:
Signal conditioner (body + base socket)..............................(1)
■■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
MODEL
W2DNY
• The actual installation environments such as panel configurations, connected devices, connected wires, may affect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conformity.
• Install lightning surge protectors for those wires connected to remote locations.
■■POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
100 – 240V and 85 – 264V AC rating: 85 – 264V
(90 – 264V for UL), 47 – 66 Hz, approx. 5 – 7VA
24V DC rating: 24V ±10%, approx. 3W
11 – 27V DC rating: 11 – 27V, approx. 3W
110V DC rating: 85 – 150V (110V ±10% for UL), approx. 3W
■■GENERAL PRECAUTIONS
• Before you remove the unit from its base socket or mount
it, turn off the power supply and input signal for safety.
POINTS OF CAUTION
■■NONINCENDIVE APPROVAL OPTION
• This equipment is suitable for use in Class I, Div. 2,
Groups A, B, C and D or Non-Hazardous Locations only.
• WARNING! Before You Remove the Unit from Its Base
Socket or Mount It, Turn Off the Power Supply and Input
Signal for Safety.
• WARNING! – Explosion Hazard –
Substitution of Components May Impair Suitability for
Class I, Div. 2.
• WARNING! – Explosion Hazard –
Do Not Disconnect Equipment Unless Power Has Been
Switched Off or The Area is Known To Be Non-Hazardous.
• The equipment was evaluated for use in the ambient temperature and relative humidity as mentioned in ‘ENVIRONMENT’ section.
• The input and output wiring must be in accordance with
Class I, Div. 2 wiring methods and in accordance with the
authority having jurisdiction for use in these hazardous
locations.
■■CONFORMITY WITH EU DIRECTIVES OR UL
• This equipment is suitable for Pollution Degree 2 and
Installation Category II (transient voltage 2500V). Reinforced insulation (signal input or output 1 or output 2
to power input: 300V) and basic insulation (signal input
to output 1 or output 2: 300V) are maintained. Prior to
installation, check that the insulation class of this unit
satisfies the system requirements.
• Altitude up to 2000 meters.
• The equipment must be mounted inside a panel.
• The equipment must be installed such that appropriate
clearance and creepage distances are maintained to conform to CE/UL requirements. Failure to observe these
requirements may invalidate the CE/UL conformance.
■■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
• Be sure that the ventilation slits are not covered with cables, etc.
■■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■■AND ....
• The unit is designed to function as soon as power is supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
• With voltage output, do not leave the output terminals
shortcircuited for a long time. The unit is designed to
endure it without breakdown, however, it may shorten appropriate life duration.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-5524 Rev.5
P. 1 / 3
W2DNY
COMPONENT IDENTIFICATION
Body
Fixing Screw
Output 1
INSTALLATION
Base Socket
Model
Zero Adj.
Span Adj.
Connection
Diagram
ZERO
SPAN
ZERO
Output 2*
Zero Adj.
SPAN
Specifications
Span Adj.
*Provided only for dual output.
Loosen the fixing screw at the front of the unit in order to
separate the body from the base socket.
■■DIN RAIL MOUNTING
Set the base socket so that
its DIN rail adaptor is at
the bottom. Position the
upper hook at the rear side
of base socket on the DIN
rail and push in the lower.
When removing the socket,
push down the DIN rail
adaptor utilizing a minus
screwdriver and pull.
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
■■WALL MOUNTING
Refer to “EXTERNAL DIMENSIONS.”
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.
■■EXTERNAL DIMENSIONS unit: mm (inch)
6 (.23)
11–M3
SCREW
9
72 (2.83)
5 4
8 7
11 10
4
(.16)
53 (2.09)
88.5 (3.48)
2–4.2x5
(.17x.20)
MTG HOLE
6 (.24) deep
3 2 1
6
59 (2.32)
DIN RAIL
35mm wide
22 (.87)
29.5 (1.16)
21.5 (.87)
10 (.39)
84 (3.31)
114 (4.49)
[4 (.16)]
• When mounting, no extra space is needed between units.
■■CONNECTION DIAGRAM
INPUT
2-WIRE XMTR
PWR SUPPLY
–
MONITOR V
+
1 – 5V DC
+ 1
7 +
– 2
8 –
+ 5
3 +
4
6 –
OUTPUT 1
OUTPUT 2
10 U(+)
11 V(–)
POWER
The section enclosed by broken line is only with 2nd output option.
■ When Used as DC Supply
2-WIRE
TRANSMITTER
–
■ When Used as Square Root
Extractor
+ 1
+ 1
50Ω
– 2
+
+ 5
4
INPUT
– 2
50Ω
5
250Ω
4
250Ω
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-5524 Rev.5
P. 2 / 3
W2DNY
WIRING INSTRUCTIONS
MAINTENANCE
■■SCREW TERMINAL
Torque: 0.8 N·m
Regular calibration procedure is explained below:
■■SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm2 (AWG 22 to 16)
Recommended manufacturer: Japan Solderless Terminal
MFG.Co.Ltd, Nichifu Co.,ltd
6 (.24) max
3.3 (.13) max
■■CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 4%,
16%, 36%, 64% and 100% input signal. Check that the output signal for the respective input signal shows 0%, 20%,
40%, 60%, 80% and 100% within accuracy described in the
data sheet. When the output is out of tolerance, recalibrate
the unit according to the “ADJUSTMENT PROCEDURE”
explained earlier.
LIGHTNING SURGE PROTECTION
mm (inch)
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.
CHECKING
1) Terminal wiring: Check that all cables are correctly connected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
10 – 11 with a multimeter.
3) Input: Check that the input signal is within 0 – 100% of
the full-scale.
4) Output: Check that the load resistance meets the described specifications.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any calibration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■■HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 1% input and adjust output to 10%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 1% input.
4) When ZERO value is changed, repeat the above procedure 1) – 3).
5) Go through the same procedure for the Output 2.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-5524 Rev.5
P. 3 / 3
">