Softing ROCK OLC 485 Instructions

Softing ROCK OLC 485 Instructions

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Manual
Softing ROCK OLC 485 Instructions | Manualzz

SPECIAL FACTORY CONFICURATION

Fiber Optic Module Number OLC-485-85-D-ST has been configured at the factory to provide general purpose

RS-485 communication. All Network Baud Rate and Diagnostic Select switch settings are identical to OLC-

DSL switch designations, which are given in Tables 8 and 25 in the attached Users Manual. Connector wiring information and pin definitions are given below:

J1 Connector

Pin Number (1)

1

2

3

4

5

Signal Name

RxD+ Input (2)

RxD- Input (2)

TxD+ Output (2)

TxD- Output (2)

Shield (3)

6

7

8

Chassis Ground

External +5VDC

External +5VDC Return

J1 CONNECTOR DEVICE

INTERFACE PIN DEFINITIONS

(1) Orientation – Top to bottom on front of module (Pins 1 thru 8 respectively). (Note: All unused connector screw terminals should be fully seated.)

(2) All RS-485 devices on the hardwire network stub must be interconnected for either 2 wire or 4 wire operation. For 2 wire operation jumper OLC J1 pin # 1 to 3 (TxD+ to RxD+) and pin # 4 to 2 (TxD- to

RxD-), and interconnect all devices on the hardwire network stub “Tx/Rx+” to “Tx/Rx+”, and “Tx/Rx-”to

“Tx/Rx-”. A 120 ohm resistor (supplied with every OLC) must be located at each end of the hardwire segment. For 4 wire operation all of the devices on the hardwire network stub must be interconnected

“Tx+” to “Tx+” and “Tx-” to “Tx-” (Transmit Outputs), and these lines should be connected to OLC “Rx+” and “Rx-”, respectively (Receive inputs). Similarly, the receive data inputs must be interconnected “Rx+” to “Rx+” and “Rx-”to “Rx-”, among the RS-485 devices on the hardwire network segment, and should be connected to the OLC “Tx+” and “Tx-”transmit outputs, respectively. A 120 ohm termination resistor must be connected across “Rx+” and “Rx-” on each OLC (pin #s 1 and 2), and “Rx+” and “Rx-” at the device on the opposite end of each hardwire network stub… for 4 wire operation.

(3) All of the devices on the multi-drop RS-485 network stub (including the OCM) should have their Shield signals interconnected via the shielded cable drain wire… but only one device at one end of the hardwire

RS-485 network stub should have Shield and Chassis Ground jumpered together. (To connect Shield to

Chassis Ground at the OLC, J1 Pin 5 should be wired to the nearest Earth Ground/Chassis Ground connection.)

If the OLC is not connected to any RS-485 devices (i.e. used as a fiber optic repeater on the network) it should have the J1 Connector Local Interface Disabled. See Interactive Diagnostics in Section 1.3.3 of

Users Manual for more information.

advertisement

Related manuals

Download PDF

advertisement