Functions Modicon TSX Micro automation platform

Functions Modicon TSX Micro automation platform
Modicon TSX Micro
automation platform
Presentation
0
Ethernet network and TCP/IP Modem serial link
TSX Micro platforms connect to the Ethernet TCP/IP network via 2 external and
autonomous TSX ETZ 410/510 modules. These modules are also used to link to an
external modem.
Ethernet TCP/IP TSX ETZ 410 module
The TSX ETZ 410 module includes:
b A Modbus/Uni-TE TCP/IP communication profile on Ethernet 10/100 Mbits/s or
TCP/IP via RS232 serial link connected to an external 56K bit/s modem.
b The integrated Web server function. The integrated Web server provides
access to:
v the module configuration,
v the PLC diagnostics system function, “Rack Viewer”,
v the communication diagnostics function,
v the access function to the PLC data and variables, “Data Editor”,
v and accepts the scanned input/output function; the TSX ETZ 410 can be scanned
by a device which supports the exchange of I/O Scanning input/outputs.
Ethernet TCP/IP TSX ETZ 510 module
The Ethernet TSX ETZ 510 uses all the functions of the TSX ETZ 410 module, and
in addition, the following functions on the level of the integrated Web server function.
b Graphic object editor function to assist in creating Web user pages.
b Configuration tool for the integrated WEB server.
Integration into structures
The Ethernet TSX ETZ 410/510 modules communicate with the Micro
TSX 37 10/21/22 PLCs, which are equipped with the operating system version
IE u 2.0. They connect:
b
v
v
v
Via the:
TSX 37 10/21/22 PLC terminal port (TER),
TSX 37 21/22 PLC auxiliary port (AUX),
TSX SCP114 serial link PCMCIA card inserted into the TSX 37 21/22 PLC.
b On a Uni-Telway bus, via the TSX SCA 50 derivation box or the TSX P ACC 01
isolation box.
The Ethernet TSX ETZ 410/510 modules are configured with the assistance of a
standard browser using:
b The Ethernet network.
b RS 232C serial link (PPP protocol).
The Ethernet TSX ETZ 410/510 modules ensure that the TSX Micro PLC TER port
is duplicated; the PLC connected to the TSX ETZ 410/510 module via this TER port
can be accessed locally by a programming terminal equipped with PL7 TSX Micro/
Junior/Pro software.
Functions:
pages 43312/4 to 43312/8
43312-EN_Ver1.1.fm/2
Description:
page 43312/9
Characteristics:
page 43312/10
References:
page 43312/11
Dimensions:
page 43312/11
Modicon TSX Micro
automation platform
Structure
0
Ethernet network and TCP/IP Modem serial link
TCP/IP profile on Ethernet and on the serial link by modem
Summary of the OSI structure
OSI model
Ethernet TCP/IP profile
Modem serial link
7
Application
Uni-TE Modbus
Uni-TE Modbus
6
Presentation
5
Session
4
Transport
TCP
TCP
3
Network
IP
IP
2
Link
Ethernet II or LLC IEEE 802.2
MAC IEEE 802.3
PPP
1
Physical
CSMA-CD IEEE 802.3
RS 232 point to point
The distributed automation applications can use a unique communication network
which meet:
b The needs of real-time workshop performance.
b The open access requirements for the monitoring/commanding software based
upon products using standard communication protocols or applications using
Internet technology.
Ethernet and the point to point protocol (PPP) via serial link respond to different
requirements in terms of data rate, capacity for open access on TCP/IP and flexibility
in terms of topology.
Ethernet communication affects essentially the following applications:
b Co-ordination between programmable PLCs.
b Local or centralized supervision.
b Communication with production information management.
b Communication with remote inputs/outputs.
The various services offered are as follows:
b The TCP/IP protocol standard permits communication with:
v the Quantum platforms in the Modbus messaging, with the 140 NOE 771 pp
module,
v the M1E CPUs associated with the Momentum inputs/outputs I/O base in Modbus
messaging,
v the Premium platforms with TSX ETY 110 module (outside of Ethway profile) or
TSX ETY 410p/510p module,
v a PC terminal, which supports a standard browser for the Ethernet network,
v a PC terminal, with a modem which supports a standard browser for the serial link,
v all Uni-TE/Modbus TCP/IP devices (ATV 58 drive, Magelis terminals, etc.).
b The SNMP V1 network agent function. All Ethernet modules integrate the MIB II
standard (Management Information Base RFC 1213) and the Ethernet
Transparent Ready private MIB. These are compatible with the main network
administration software available on the market.
Functions:
pages 43312/4 to 43312/8
Description:
page 43312/9
Characteristics:
page 43312/10
References:
page 43312/11
Dimensions:
page 43312/11
43312-EN_Ver1.1.fm/3
Modicon TSX Micro
automation platform
Functions
0
Ethernet network and TCP/IP Modem serial link
Ethernet link
PC + Internet browser
Quantum
c
3
1
5
Premium
2
Premium
3
a
a
2
b
TSX Micro
5
TSX Micro
b
3
3
Momentum
ATV 58
Device
T XBT F Magelis
Modem link
1
1
2
4
6
2
4
5
6
b
5
2
b
6
1, 2, 3, 4, 5 and 6 See functions on page 43312/5.
a Premium Ethernet TSX ETY 410p/510p module.
b TSX Micro Ethernet TSX ETZ 410/510 module.
c Quantum Ethernet 140 NOE 711 pp module.
Presentation:
page 43312/2
43312-EN_Ver1.1.fm/4
Description:
page 43312/9
Characteristics:
page 43312/10
References:
page 43312/11
Dimensions:
page 43312/11
TSX
Micro
Functions (continued)
Modicon TSX Micro
automation platform
0
Ethernet network and TCP/IP Modem serial link
Services linked to Ethernet applications
The TSX ETZ 410/510 modules integrate the services linked to the
Ethernet applications:
1 Integrated Web server services:
v IP configuration for the TSX ETZ 410/510 via standard browser on the Ethernet
network or locally,
v Access security,
v PLC diagnostics system Function “RackViewer”,
v Communication diagnostics function,
v Access function to the PLC data and variables, “Data Editor”,
v Download of Uni-TE PL7 applications,
v Graphic object editor (only on TSX ETZ 510),
v display of predefined Web pages,
v User Web pages (only on TSX ETZ 510).
2 Scanned inputs/outputs service performed from the Premium or Quantum PLC
(I/O Scanning function).
3 Uni-TE messaging in TCP/IP in Client/Server mode:
v Remote terminal: Terminal transparence (see page 43301/3).
4 Un-TE messaging in TCP/IP in Client/Server mode:
v Conversion of Modbus requests to Uni-TE requests going to the TSX Micro PLC
and vice versa for the reply.
5 TCP/IP messaging gateway to Uni-TE.
6 API calling/called (only for Modem link).
Standard Ethernet services for TSX ETZ 410/510
The TSX ETZ 410/510 modules conform to the following standard protocols:
b BOOTP: attribution of IP address via a server (also for addressing by default
or from a PC equipped with a standard browser).
b DHCP (1): automatic reconfiguration by replacing a faulty module (FDR function).
b SNMP (2): network management protocol. The TSX ETZ 410/510 modules
integrate the standard MIB II and the private Ethernet Transparent Ready MIB.
(1) Only for Ethernet link:
Bootstrap Protocol: protocol for starting up terminals or stations without a disk via
centralized management of network parameters.
Dynamic Host Configuration Protocol: protocol, which allows a station connected to
a network to dynamically obtain its configuration.
(2) Simple Network Management Protocol: Network management protocol which is used to
monitor a remote network by requesting the status of the stations and modifying their
configuration, performing security checks and observing various information linked to data
transmission. It can also be used to manage remote data bases and software.
Presentation:
page 43312/2
Description:
page 43312/9
Characteristics:
page 43312/10
References:
page 43312/11
Dimensions:
page 43312/11
43312-EN_Ver1.1.fm/5
Functions (continued)
Modicon TSX Micro
automation platform
0
Ethernet network and TCP/IP Modem serial link
Scanned inputs/outputs service
The Ethernet ETZ 410/510 modules for the TSX Micro PLC accept the scanned
I/O service, which is performed by the Premium or Quantum modules using the
I/O Scanning service (TSX ETY 410p/510p, 140 NOE 771 pp).
Flow chart
%MW word table
Read
Write
Momentum
Premium
TSX Micro
ATV 58
Premium
Magelis
TSX Micro
This service is used to manage the exchange of remote inputs/outputs on the
Ethernet network after a simple configuration and without the need for specific
programming.
Inputs/outputs are scanned transparently with the assistance of read/write requests
according to the Modbus protocol on the TCP/IP profile. This principle of scanning
via a standard protocol is used to communicate with any device supporting a Modbus
server on TCP/IP or with a built-in Modbus/Uni-TE converter on TCP/IP.
Integrated Web server
The Ethernet TSX ETZ 410/510 modules have an integrated Web server. On a
TSX Micro PLC level, the functions of the Web server allow:
v
v
v
v
v
v
configuration,
diagnostics,
access to variables,
graphic editing,
display of predefined Web pages and
use of a Web page configuration tool.
This server is a PLC real-time data server. All TSX Micro PLC CPU data which
support one of these modules are presented in the form of standard HTML-web
pages and can also be accessed by all standard browsers capable of embedded
Java or by FactoryCast software (supplied on CD-Rom with each Ethernet module).
All functions from the Web server do not require any configuration or programming,
either on the level of the TSX Micro PLC, or on the level of the compatible PC which
supports the Internet browser. Furthermore, this module can be used in an existing
configuration without any modification to the current program.
Presentation:
page 43312/2
43312-EN_Ver1.1.fm/6
Description:
page 43312/9
Characteristics:
page 43312/10
References:
page 43312/11
Dimensions:
page 43312/11
Functions (continued)
Modicon TSX Micro
automation platform
0
Ethernet network and TCP/IP Modem serial link
Configuration function
The configuration function for the module is a predefined function. It allows:
b
b
b
b
b
b
Altering the user name and password for access to the secure page.
Configuration of the TCP/IP parameters.
Configuration of the Uni-Telway parameters.
Automatic re-configuration.
Configuration of the SNMP parameters.
The module reset.
“Rack Viewer” function, TSX Micro PLC diagnostics
The predefined “Rack Viewer” function (display of PLC rack) is used to diagnose the
TSX Micro PLC connected to the network via the Ethernet module. This is a
predefined secure function (accessed using a password) which allows real-time
display from a standard browser:
b The status of the LEDs on the front panel of the PLC.
b The version type of the PLC.
b The hardware configuration of the PLC with the status of the system words
and bits.
b The detailed diagnostics of each I/O module or application share this
configuration.
Communication diagnostics function
The communication diagnostics function is a predefined secure function (accessed
using a password) which allows real-time display from a standard browser:
b The Ethernet network statistics.
b The Uni-Telway bus statistics.
b The RS 232 Modem serial link diagnostics.
“Data Editor” function, access to the PLC data and variables
The access to the variables function is a predefined and secure function (accessible
by password) allowing the creation of an events table to access the list of PLC
variables in read or write.
The variables to be displayed can be entered and displayed as:
b Address (%MW99) for the TSX ETZ 410 module.
b Symbol (S_Pump 234) or address (%MW99) for the TSX ETZ 510 module.
In order to be able to write a value in a variable, you will need to enter and confirm
a second password. The animation tables created by the operator can be saved in
the Ethernet TSX ETZ 410/510 module.
Presentation:
page 43312/2
Description:
page 43312/9
Characteristics:
page 43312/10
References:
page 43312/11
Dimensions:
page 43312/11
43312-EN_Ver1.1.fm/7
Functions (continued)
Modicon TSX Micro
automation platform
0
Ethernet network and TCP/IP Modem serial link
Graphic object editor function
(available on the TSX ETZ 510 module)
The graphic object editor function enables you to create graphic designs, including
animated graphic objects, linked to PLC variables.
These customized designs can be used in user Web pages created with FactoryCast
software.
These designs are created using simple cut/paste operations and the objects are
set according to the needs of the user (color, PLC variables, label…). Once the
designs have been created, they can be saved in a transparent way in the
Ethernet TSX ETZ 510 module.
Display of predefined Web pages
(available on the TSX ETZ 510 module)
The TSX ETZ 510 module also has an 8 M bytes (1) Flash EPROM type memory,
which is accessible as a hard disk and permits the reception (hosting) of Web pages
defined by the user.
These Web pages can be created using any standard tool that lets you create and
edit in HTML format. Eight pages can be enhanced by inserting animated graphic
objects provided by the graphic object editor.
Once created, these Web pages allow you to:
b Display all PLC variables in real time.
b Insert hyperlinks to external servers (documentation, suppliers…).
This function is particularly useful for creating graphics and images intended for:
b Display, monitoring, diagnostics.
b Development of real time production reports.
b Maintenance assistance.
b User guides.
FactoryCast configuration tool for the integrated WEB server
(only available on the TSX ETZ 510 module)
The FactoryCast software, version > 2.2.1 (supplied on the CD-Rom with the
TSX ETZ 510 module), allows you to configure and administer the Web server
embedded in the module. It is common to the TSX Micro, Premium and Quantum
automation platforms.
It provides the following functions:
b Access security.
b Definition of the User names and associated passwords to access the Web pages.
b Definition of the access to the variables authorized in modification.
b Access to the PL7 application and to the TSX Micro PLC data.
b Save/restore a complete Web site.
b Transfer of Web pages created in local mode by the user on a PC-compatible
workstation to the TSX ETZ 510 module and vice versa.
(1) Memory that is insensitive to power outages and to PLC resets.
Presentation:
page 43312/2
43312-EN_Ver1.1.fm/8
Description:
page 43312/9
Characteristics:
page 43312/10
References:
page 43312/11
Dimensions:
page 43312/11
Modicon TSX Micro
automation platform
Description
0
Ethernet network and TCP/IP Modem serial link
Description of the TSX ETY 410/510 modules
The Ethernet TSX ETZ 410/510 modules are autonomous and thus do not fit into a
TSX Micro PLC rack, but fix onto a DIN profile or on AM1-PA perforated mounting
plate.
1
2
3
4
The front of the TSX ETZ 410/510 modules are arranged as follows:
5
1 Three display LEDs indicating the module status (RUN, ERR, RX/TX).
2 A screened-on label indicating the module's MAC address (default address set in
the M bit).
3 A mini DIN connector for terminal port (TER address).
4 An RJ45 connector for Uni-Telway auxiliary port RS 485 serial link
(RS 485 address).
5 An RJ45 normalized connector for connecting to the Ethernet network
(10/100BASE-T address).
6 A 9 pin male SUB-D connector for RS 232 serial link (Modem).
7 A screw terminal block for connecting to the external power supply c 24 V.
8 A support plate enabling it to be fixed to the module.
6
7
8
Wiring system
The TSX ETZ 410/510 modules support two kinds of exclusive TCP/IP connections:
b By Ethernet network via 10BASE-T/100BASE-TX (RJ45) interface, see
page 48190/7 for accessories and connection cables.
b By Modem via RS 232 serial link, see page 43606/2 for accessories and
connection cables.
The TSX ETZ 410/510 modules are connected to the TSX Micro PLCs
TSX 37 10/21/22 via:
b The terminal port (TER) or the auxiliary port (AUX).
b The PCMCIA RS 485 TSX SCP114 serial link.
Flow chart
The wiring chart opposite corresponds to one of the methods of connection.
The TSX ETZ 410/510 module is attached to the TSX Micro PLC via its terminal port
(TER or AUX).
1 TSX PCU 1031: Uni-Telway connection cable between a compatible PC and the
TER port of the TSX ETZ 410/510 module.
TSX ETZ 410/510
TSX Micro
1
2
3
Presentation:
page 43312/2
3 490 NTW 000pp: shielded twisted pair cable connection right of the module
(rep. 10BASE-T/100BASE-TX) to Ethernet via hub (see page 48190/7). Length
from 2...80 m.
4
Modem
Ethernet
2 TSX ETZ CDN 003: connection cable (0.35 m cable, supplied with the
TSX ETZ 410/510 module) between the module (rep. RS 485) and the TER/AUX
port of the TSX Micro PLC. The TSX CX 100 cable authorizes a connection with
longer lengths (up to 10 m).
4 RS 232 cable between the SUB-D 9 connector contacts of the module
(rep. RS 232) and the Modem.
5
5 Connection for external power supply c 24 V (see Phaseo power supply
page 14055/3).
Functions:
pages 43312/4 to 43312/8
Characteristics:
page 43312/10
References:
page 43312/11
Dimensions:
page 43312/11
43312-EN_Ver1.1.fm/9
Modicon TSX Micro
automation platform
Characteristics
0
Ethernet network and TCP/IP Modem serial link
Characteristics of the TSX ETY 410/510 modules
Type of link
Structure
Nature
Topology
Physical interface
Protocol
Transmission
Mode
Binary data rate
Medium
Configuration
Number of stations
Length
Ethernet
Serial link by Modem
Local industrial heterogeneous network which
conforms to the IEEE 802.3 standard
Star-shaped or tree-structure network
–
–
Telephone line (1)
Manchester-type baseband
10/100 M bit/s with automatic recognition
10BASE-T, double shielded twisted pair of type
STP, impedance 100 Ω ± 15 Ω
100BASE-T, Ethernet cable category 5
conforms to standard EIA/TIA 568A
Point-to-point connection (via normalized RJ45
connector) enabling a star-shaped network to
be formed (the stations are linked to hubs or
switches). 64 stations max. per network
100 m max. between terminal device and hubs
Half or full duplex
RS 232 link to 56 K bit/s max
Shielded RS 232 cable (crossover DTE/DTE)
–
RTC Link
Point-to-point protocol
2 (point to point link)
–
Services and functions supported by the module
Shared services
Different shared services:
- scanned inputs/outputs service performed from the Premium/Quantum PLC with
the I/O Scanning function
- inter-PLC communication in Uni-TE or Modbus TCP/IP
- download of Uni-TE PL7 applications
- diagnostics module
- remote terminal: Terminal transparence (see page 43301/3)
- adjustment, debugging and modifications to the program
TCP/IP services
in Uni-TE:
- client/server mode (32 simultaneous connections)
- 128 byte client/server requests (synchronous mode)
- 1Kbyte client/server requests (asynchronous mode)
In Modbus:
- client/server mode (32 simultaneous connections)
- 128 byte synchronous requests
Integrated Web server
function (2)
Different Integrated Web server services:
- maximum simultaneous connection of 8 standard browsers
- IP configuration for TSX ETZ 410/510 module via standard browser
- PLC diagnostics system function “RackViewer”
- communication diagnostics function
- access function to the PLC data and variables “Data Editor”
- graphic objects editor (3)
- Web pages defined by the user (8 Mb available) (3)
Electrical specifications
Supply voltage
Nominal
Limits
c
c
Wave rate
24
19.2…30
5% max.
Accepted micro-cuts
ms
1
Permitted overvoltage
c
34 max. (for 1 hour in 24)
mA
mA
100
50…200
W
2.4 (4 max.) without consumption on terminal port
Power consumption
Nominal
Limits
Power dissipation
Environment
Conforming to standards
The TSX ETZ 410/510 modules conform to the TSX Micro PLC requirements (see
page 43050/11), which meet the following standards: ISO/IEC 8802-3, ANSI/IEEE Std 802.3
(4th edition 1993-07-08), conforming to the FCC-B rule for radiated emissions (50082-1)
(1) Transmission via Modem can also be by radio or satellite.
(2) Requires a standard browser on the PC (i.e. Internet Explorer version 4, Netscape version
4.05 or other) which is capable of executing Java code.
(3) Services available on the TSX ETY 510 module.
Presentation:
page 43312/2
43312-EN_Ver1.1.fm/10
Description:
page 43312/9
Functions:
pages 43312/4 to 43312/8
References:
page 43312/11
Dimensions:
page 43312/11
Modicon TSX Micro
automation platform
References,
dimensions
0
Ethernet network and TCP/IP Modem serial link
Ethernet TCP/IP network modules
Designation
Ethernet modules
for Micro
TSX 37 10/21/22
PLC
(1), (2)
Data rate and communication profile Integrated Web Server
References
Diagnostics
Web user
pages
Ethernet 10/100 Mbps or
yes
–
TSX ETZ 410
Modem 56 Kbps
yes
8 Mb available TSX ETZ 510
Uni-TE on TCP/IP or Modbus
on TCP/IP
Weight
kg
0.280
0.280
Connection cables and accessories
Designation
Ethernet twisted
shielded cables
(3)
From
To
Use
Length
TSX ETZ 410/510 Ethernet Hub (RJ45 Link to Ethernet
module
connector)
network
(RJ45 connector See page 48190/7
add. ETH)
TSX ETZ 410/510
TSX P ACC 01
2m
5m
12 m
40 m
80 m
References
(3)
490 NTW 000 02
490 NTW 000 05
490 NTW 000 12
490 NTW 000 40
490 NTW 000 80
RS 485 Uni-Telway TSX ETZ 410/510 Compatible PC
cables
module
(female SUB-D
(mini DIN
9 pin connector)
connector add.
TER)
TSX SCA 50
connection box
Uni-Telway bus link
via terminal port
2.5 m
TSX PCU 1031
Uni-Telway bus link
via terminal port
10 m (4) (5)
TSX CX 100
Terminal port
(TER) connection
box
Weight
kg
–
–
–
–
–
0.140
–
Uni-Telway
derivation bus
TSX ETZ 410/510
module or TSX
Micro PLC
(mini DIN connector
add. TER)
Uni-Telway bus
1 m (TER port TSX P ACC 01
isolation signals for
link cable)
buses > 10m in length,
end of line adaptation,
bus cable derivation
0.690
Passive derivation Uni-Telway
box
derivation bus
TSX ETZ 410/510
module
(mini DIN connector
add. TER)
Derivation and
prolonging of bus
cable, end of line
adaptation
0.520
TSX SCA 50
–
TSX SCA 50
(1) Requires a TSX 37 10/20/21 PLC with a version u 2.0 operating system, supplied with a
TSX ETZ CDN 003 link cable (0.35 m in length). These modules should be supplied with
c 24 V. (See supply process page 14055/3).
(2) Supplied with CD-Rom including the FactoryCast V2.2.1 software, the Ethernet
Transparent Ready Part A, the user manual for the Ethernet TSX ETZ 410/510 modules.
(3) Add the letter U to the end of the reference for CSA 22.1, NFPA 70 and UL approved cables
(flame-retardant).
(4) Free wire on the side of the TSX SCA 50 connection box.
(5) If the 0.35 m of TSX ETZ CDN 003 cable, supplied with the TSX ETZ 410/510 modules, is not
suitable, it is possible to use the TSX CX 100 cable (10 m in length). In this case, attach an
8 pin RJ45 connector (category 5) to the end of the free wire.
Dimensions, mounting
TSX ETZ 410/510 modules
16
5,4
Mounting on profiled AM1 DE200
or AM1 DP200 or on AM1 PA mounting plate
88,9
140
143,7 (1)
132,7 (2)
34,63
39,83
5,15
116,7
30,7
58,55
150
151,5
4
(1) 136.2 mm with profiled AM1 DP200
(2) Assembly on AM1 PA mounting plate
Presentation:
page 43312/2
Description:
page 43312/9
Functions:
pages 43312/4 to 43312/8
Characteristics:
page 43312/10
43312-EN_Ver1.1.fm/11