User Manual

Add to my manuals
16 Pages

advertisement

User Manual | Manualzz
MODELS:
GS10
GS10-R
NEMA 4X SCR
MOTOR CONTROLS
User’s Manual
GS10 Series
Safety Warnings
SHOCK
HAZARD
AVOID
HEAT
KEEP
DRY
Contents
AVOID
VIBRATION
• This symbol
denotes an important safety tip or warning.
Please read these instructions carefully before performing any
of the procedures contained in this manual.
• DO NOT INSTALL, REMOVE, OR REWIRE THIS
EQUIPMENT WITH POWER APPLIED. Have a qualified
electrical technician install, adjust and service this equipment.
Follow the National Electrical Code and all other applicable
electrical and safety codes, including the provisions of the
Occupational Safety and Health Act (OSHA), when installing
equipment.
• Reduce the chance of an electrical fire, shock, or explosion by
proper grounding, over-current protection, thermal protection,
and enclosure. Follow sound maintenance procedures.
WARNING
It is possible for a drive to run at full speed as
a result of a component failure. Manufacturer
strongly recommends the installation of a master
switch in the main power input to stop the drive in an
emergency.
Circuit potentials are at 115 VAC or 230 VAC above
Earth ground. Avoid direct contact with the printed
circuit board or with circuit elements to prevent the
risk of serious injury or fatality. Use a non-metallic
screwdriver for adjusting the calibration trimpots.
Use approved personal protective equipment and
insulated tools if working on this drive with power
applied.
2
Safety Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Removing the plastic cover . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Line fusing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Field Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Voltage Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Calibration procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
MINIMUM SPEED (MIN SPD) . . . . . . . . . . . . . . . . . . . . . . . 6
MAXIMUM SPEED (MAX SPD) . . . . . . . . . . . . . . . . . . . . . . 6
REGULATION (IR COMP) . . . . . . . . . . . . . . . . . . . . . . . . . . 6
TORQUE LIMIT (TORQUE) . . . . . . . . . . . . . . . . . . . . . . . . . 6
ACCELERATION (ACCEL) . . . . . . . . . . . . . . . . . . . . . . . . . 7
DECELERATION (DECEL) . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Calibration procedure conclusion . . . . . . . . . . . . . . . . . . . . . 7
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Before applying power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
GS-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
GS-10-R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Application Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Inhibit circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Decelerating to minimum speed . . . . . . . . . . . . . . . . . . . . . 10
Dynamic braking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Multiple fixed speeds . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Adjustable speeds using potentiometers in series . . . . . . .10
Independent adjustable speeds . . . . . . . . . . . . . . . . . . . . . 10
RUN/JOG switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
RUN/JOG option #1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
RUN/JOG option #2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Leader-follower application. . . . . . . . . . . . . . . . . . . . . . . . . 12
Single speed potentiometer control of multiple drives . . . . 12
Reversing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Before troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Power and current limit LEDs . . . . . . . . . . . . . . . . . . . . . . . 13
GoldSpec™ User’s Manual
Specifications
Illustrations
Figure 1. GS10 Series Dimensions . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 2. Cover removal for terminal strip access . . . . . . . . . . . . 5
Figure 3. Drive connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 4. Voltage Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 5. Calibration Trimpot Layout . . . . . . . . . . . . . . . . . . . . . . 6
Figure 6. Recommended TORQUE and IR COMP
Settings for GS10 Series Controls . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 7. Inhibit Plug with Run/Coast to Minimum Speed . . . . . . 9
Figure 8. Run/Decelerate to Minimum Speed Switch . . . . . . . . 10
Figure 9. Dynamic Brake Connection . . . . . . . . . . . . . . . . . . . . 10
Figure 10. Multiple Fixed Speeds . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 11. Adjustable Fixed Speeds using
Potentiometers in Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 12. Independent Adjustable Speeds . . . . . . . . . . . . . . . 11
Figure 13. RUN/JOG Switch Option #1 . . . . . . . . . . . . . . . . . . . 11
Figure 14. RUN/JOG Switch Option #2 . . . . . . . . . . . . . . . . . . . 11
Figure 15. Leader-Follwer Application . . . . . . . . . . . . . . . . . . . . 11
Figure 16. Single Speed Potentiometer
Control of Multiple Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 17. Reversing Circuit Connection . . . . . . . . . . . . . . . . . . 12
Figure 18. Current Limit LED . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Model
Max.
Armature
Current
(Amps DC)
GS10
SERIES
10
AC Line Voltage
HP Range
HP Range
Current with Current
with
115 VAC
230 VAC
Applied
Applied
1/8–1
1/4–2
Table 1. Recommended Line Fuse Sizes . . . . . . . . . . . . . . . . . . 4
Table 2. Field Output Connections. . . . . . . . . . . . . . . . . . . . . . . . 5
NEMA 4X
115/230 VAC ±10%, 50/60 Hz, single phase
Armature Voltage (115 VAC Input)
0–90 VDC
Armature Voltage (230 VAC Input)
0–180 VDC
Form Factor
Field Voltage (115 VAC Input)
1.37 at base speed
50 VDC (F1 to L1); 100 VDC (F1 to F2)
Field Voltage (230 VAC Input) 100 VDC (F1 to L1); 200 VDC (F1 to F2)
Max. Field Current
1 ADC
Decel. Time Range:
for 0-90 VDC Armature Voltage
for 0–180 VDC Armature Voltage
1 - 15 seconds
1 - 15 seconds
Decel. Time Range:
for 0-90 VDC Armature Voltage
for 0–180 VDC Armature Voltage
coast to a stop–13 seconds
coast to a stop–25 seconds
Analog Input Voltage Range (signal must be isolated; S1 to S2):
for 0–90 VDC Armature Voltage
for 0–180 VDC Armature Voltage
0–1.4 VDC
0–2.8 VDC
Current Limit Range:
for 0-90 VDC Armature Voltage
for 0–180 VDC Armature Voltage
Tables
Style
Input Impedance (S1 to S2)
Load Regulation
0 - 14 A
0 - 13.5 A
3M ohms
1% base speed or better
Vibration
1G max (0–50 Hz)
Ambient Temp. Range (cased drive)
GS10 Series
10°C–40°C
3
Dimensions
Dimensions
Installation
Mounting
5.63 [143]
5.16 [ 131]
POWER
ON

0.19 [5.00]
SLOTTED HOLES
4 PLACES
OFF
5
6
3
4
2
7
1
8
9
0
1 0
7.50 [191]
SPEED
5.50 [140]
ADJUSTABLE SPEED
DC MOTOR CONTROL
Removing the Plastic Cover
BOTTOM PLATE
0.73 [18.5]
CONDUIT HOLES
2 PLACES
GS10 Series drives may be vertically wall mounted using
the four 0.19 inch (5 mm) slotted holes on the attached
heat sink (see Figure 1, Page 2). For motor loads less than
5 ADC, the drive may be bench mounted horizontally, or
operated without mounting.
Connections, calibration, and other settings must be made
internally. After mounting, use the following procedure to
remove the plastic cover and configure the control:
1.Remove the six (6) phillips screws on the front cover.
NOTE: The two shorter screws (#6 - 32 x 2 1/2) are for
the two lower holes on the front of the cover (see Figure
2, page 5).
4.56 [116]
2.12 [53.8]
2.Remove the five (5) phillips screws on the bottom plate
(see Figure 2, page 5). NOTE: DO NOT remove the 3
screws securing the bottom plate to the heatsink.
2.20
[55.9]
3.40
[86.4]
ALL DIMENSIONS IN INCHES [MILLIMETERS]
Line fusing
Figure 1. MC10 Series Dimensions
Figure 1. GS10 Series Dimensions
Overview
The following is an overview of the steps taken to set
up a GS10 Series control. For more detailed installation
information, read the Installation and Calibration sections of
this manual.
1.Mount the control using the 4 slotted holes on the heat
sink. The slotted holes are 0.19 inches [5 mm]
(see Figure 1).
2.Remove the plastic cover by unscrewing the 6 screws on
the front cover and 5 screws on the bottom plate. NOTE:
Do not remove the 3 screws securing the bottom plate to
the heatsink.
3.Change the line fuse if necessary. If the horsepower
rating of the motor being used is less than the maximum
HP rating of the drive, the line fuse may have to be
replaced with a lower rated one.
Line fuses are preinstalled on all GS10 Series drives. If
the current rating of the motor be­ing used is less than the
maximum current rating of the drive, the line fuse may have
to be replaced with a lower rated one. Refer to Table 1 for
recommended line fuse sizes.
Table 1. Recommended Line Fuse Sizes
MOTOR HP
FUSE SIZE (AMPS)
@ 115 VAC INPUT
FUSE SIZE (AMPS)
@ 230 VAC INPUT
1/4
5
3
1/3
8
3
1/2
8
5
3/4
10
8
1
15
8
1½
–
10
2
–
15
4.Wire the control through the conduit holes, or optional
aluminum hardware. NOTE: Do not connect the control
while power is applied.
5.Assure that settings on voltage switches are correct
(SW501 & SW502).
6.Apply power to the drive.
7.Calibrate the trimmer pots, if necessary.
8.Re-install the plastic cover.
4
GoldSpec™ User’s Manual
Installation
MOV502
MOV501
WARNING
Do not connect this equipment with power
applied. Failure to heed this directive may result in
fire or serious injury.
F502
1
A2 FRM SW A1
A1
A2
L1
L2-230
Installation
A2 TO SW A1
L2 TO SW L1
TB501
F2
F1
2.Connect external wiring to the terminal block as shown in
Figure 3.
L2 FRM SW L1
F501
MOV503
L2-115
1.Install conduit hardware through the two 0.73 inch (18.5
mm) conduit holes or by using aluminum cord connectors
attached to the line seal plate on the bottom of the case.
2
+
POWER
230 VAC
ON

D
OFF
115 VAC
1
7 8 9
2 3
4 5 6
EARTH GROUND
(GREEN SCREW)
0
R502
Connections
3
4
SPEED
6
5
MOTOR
ARMATURE
The field output is for shunt wound motors only. Do not make any
The field
output
shunt
motors
connections
to F1 is
andfor
F2 when
usingwound
a permanent
magnet motor.
For field
connections,
see Table 2 on
only. Do not make
any
connections
toPage
F18.and F2
when using a Figure
permanent
magnet motor.
3. Drive connections
For field connections, see Table 2.
REMOVE THE SIX (6)
PHILLIPS SCREWS ON
THE FRONT CASE.
NOTE: THE TWO SHORTER
SCREWS (#6 - 32 x 2 ½) ON
THE FRONT CASE ARE USED
AT HOLE LOCATIONS 5 & 6.
LINE VOLTAGE INPUT
(115 or 230 VAC)
FIELDD
OUTPUT
CONNECTIONS
FIELD OUTPUT
CONNECTIONS D
ADJUSTABLE SPEED
DC MOTOR CONTROL
STEP #1
FIELD
OUTPUT
Figure 3. Drive connections
OPTIONAL
ALUMINUM CORD
CONNECTORS (2)
PART #: 155-0081
1
STEP #2
REMOVE THE FIVE (5)
PHILLIPS SCREWS ON
THE BOTTOM PLATE.
2
Field Output
BOTTOM PLATE
The field output is for shunt wound motors only. Do
not make any connections to F1 and F2 when using a
permanent magnet motor. Use 18 AWG wire to connect the
field output to a shunt wound motor. Table 2 lists the field
output connections.
3
OPTIONAL ALUMINUM
CORD CONNECTORS
4
5
MOTOR HP
FUSE SIZE (AMPS)
@ 115 VAC INPUT
FUSE SIZE (AMPS)
@ 230 VAC INPUT
1/4
5
3
DO NOT REMOVE
THE THREE (3) SCREWS SECURING
THE BOTTOM PLATE TO THE HEATSINK
Figure 2. Cover removal for terminal strip access
Figure 2. Cover removal for terminal strip access
1/3
8
3
1/2
8
5
3/4
10
8
1
15
8
1½
–
10
2
–
15
Table 2. Field Output Connections
GS10 Series
5
Installation (Continued)
Calibration
Voltage Switches
WARNING
Dangerous voltages exist on the drive when it is
powered. When possible, disconnect the voltage
input from the drive before adjusting the trimpots.
If the trimpots must be adjusted with power applied,
use insulated tools and the appropriate personal
protec­tion equipment. BE ALERT. High voltages
can cause serious or fatal injury.
• Set voltage switch SW501 to either 115 or 230 to match
the AC line voltage (see Figure 4).
• Set voltage switch SW502 to either 90 or 180Installation
to match the
maximum motor armature voltage (see Figure 4).
IL502
IC501
CURRENT
LIMIT
IL501
SO501
SW502 (90 or 180 VDC)
TQ LIMIT
ACCEL
DECEL
IR COMP
MIN SPD
MAX SPD
T501
R501
230 - 115
SO502
SW501
90 - 180 SW502 INHIBIT
IC502
MAX ARMATURE VOLTAGE SWITCH
S3 S2 S1
C501
C504
POWER
C502
AC LINE VOLTAGE SWITCH
MOV501
C503
MOV502
R502
SW501 (115 or 230 VAC)
All drives have six user-adjustable trimpots: Torque Limit
(TORQUE), Acceleration (ACCEL), Deceleration (DECEL),
Regulation (IR COMP), Minimum Speed (MIN SPD),
and Maximum Speed (MAX SPD). Each drive is factory
calibrated to its maximum current rating. Readjust the
calibration trimpot settings to accommodate lower current
rated motors.
All adjustments increase with CW rotation, and decrease
with CCW rotation. Use a non-metallic screwdriver for
calibration. Each trimpot is identified on the printed circuit
board. Refer to Figure 5 for trimpot locations and Figure 6 (page 8) for typical TORQUE LIMIT and IR COMP settings.
F502
A2 TO SW A1
L2 TO SW L1
A2 FRM SW A1
F501
L1
A2
C501
A1
C504
L2-230
IC502
Figure 4. Voltage Switches
TQ LIMIT
Figure 4. Voltage Switches
ACCEL
DECEL
MOV502
MOV501
IR COMP
R502
R501
230-115
MIN SPD
MAX SPD
TRIMMER POTS
TORQUE LIMIT (TQ LIMIT)
ACCELERATION (ACCEL)
DECELERATION (DECEL)
REGULATION (IR COMP)
MINIMUM SPEED (MIN SPD)
MAXIMUM SPEED (MAX SPD)
C503
SW501
SO502
T501
90 - 180 SW502 INHIBIT
L2-115
CURRENT
LIMIT
IL501
SO501
F2
IL502
IC501
C502
S3 S2 S1
TB501
POWER
MOV503
F1
L2 FRM SW L1
F502
A2 TO SW A1
L2 TO SW L1
A2 FRM SW A1
F501
MOV503
F1
L2 FRM SW L1
TB501
F2
L2-115 L2-230 L1
A2
A1
Figure 5. Calibration Trimpot Layout
Figure 5. Calibration Trimpot Layout
6
GoldSpec™ User’s Manual
Calibration procedure
REGULATION (IR COMP)
The IR COMP setting determines the degree to which motor
speed is held constant as the motor load changes. It is
factory set for optimum motor regulation.
Calibrate the drive using the following procedure:
1.Set the MIN SPD, IR COMP, ACCEL and DECEL trimpots
to zero (full CCW).
Recalibrate the IR COMP setting when using a lower
horsepower motor. Refer to the recommended IR COMP
settings in Figure 6 (page 8), or recalibrate using the
following procedure:
2.Set the TORQUE trimpot to maximum (full CW).
3.Set the MAX SPD trimpot to midrange (approximate 12
o’clock position).
If the motor does not maintain set speed as the load
changes, gradually rotate the IR COMP trimpot CW. If the
motor oscillates (overcompensation), the IR COMP trimpot
may be set too high. Turn the IR COMP trimpot CCW to
stabilize the motor.
4.Turn the speed adjust potentiometer on front cover to
zero.
5.Apply power to the drive.
6.Calibrate the trimpots as follows:
TORQUE LIMIT (TORQUE)
MINIMUM SPEED (MIN SPD)
WARNING
The MIN SPD setting determines the motor speed when the
speed adjust potentiometer is turned full CCW or reference
signal is at its minimum. It is factory set to zero speed.
Although TORQUE is set to 150% of drive
nameplate current rating, continuous opera­tion
beyond that rating may damage the motor. If you
intend to operate beyond the rating, contact your
Applied Industrial Technologies representative for
assistance.
To calibrate, turn the speed adjust potentiometer full CCW
or reference signal is at its minimum. Adjust the MIN SPD
trimpot until the motor has stopped, or is running at the
desired minimum speed.
The TORQUE setting determines the maximum torque for
accelerating and driving the motor. TORQUE is factory set
at 150% of maximum drive current. You must recalibrate
the TORQUE setting if using a lower current rated motor.
See Figure 6 (page 8) for typical TORQUE and IR COMP
settings.
MAXIMUM SPEED (MAX SPD)
The MAX SPD setting determines the motor speed
when the speed adjust potentiometer is turned full CW
or reference signal is at its maximum. It is factory set for
maximum rated speed.
1.With no power applied to the drive, connect a DC
ammeter in series with the motor armature.
2.Set the TORQUE trimpot to full CCW.
To calibrate, set the MAX SPD trimpot full CCW. Turn the
speed adjust potentiometer full CW or reference signal is at
its maximum. Adjust the MAX SPD trimpot until the desired
maximum motor speed is reached.
3.Carefully lock the motor armature. Ensure that the motor
is firmly mounted.
4.Apply line power. The motor should be stopped.
Note: Check the MIN SPD and MAX SPD adjustments after
recalibrating to verify that the motor runs at the desired
minimum and maximum speed.
5.Set the speed potentiometer or reference signal to
maximum speed. The motor should remain stopped.
6.Slowly rotate the TORQUE trimpot clockwise (CW) until
the ammeter reads 150% of maximum motor armature
current.
7.Set the speed adjust potentiometer or reference signal to
zero speed.
8.Remove power from the drive.
9.Remove the lock from the motor shaft.
10.Remove the ammeter in series with the motor armature.
GS10 Series
7
Calibration (continued)
Operation
ACCELERATION (ACCEL)
WARNING
Change voltage switch settings only when the drive
is disconnected from AC line voltage. Make sure
both switches are set to their correct position. If
the switches are improperly set to a lower voltage
position, the motor will not run at full voltage. If the
switches are improperly set to a higher voltage
position, the motor will overspeed, which may cause
motor damage.
The ACCEL setting determines the time the motor takes
to ramp to a higher speed. See Specifications on page 3
for approximate acceleration times. The ACCEL setting is
factory set to its minimum value (full CCW).
Turn the ACCEL trimpot CW to increase the acceleration
time, and CCW to decrease the acceleration time.
DECELERATION (DECEL)
Before applying power
The DECEL setting determines the time the motor takes
to ramp to a lower speed. See Specifications on page 3
for approximate decelerating times. The DECEL setting is
factory set to its minimum value (full CCW).
Calibration
Turn the DECEL trimpot CW to increase the deceleration
time, and CCW to decrease the deceleration time.
Calibration procedure conclusion
This concludes the calibration procedure. The control
should now be calibrated for optimum operation.
TORQUE
TORQUE
TORQUE
IR COMP
IR COMP
IR COMP
1 HP
90 VDC
1750 RPM
10 AMPS
1/2 HP
90 VDC
1750 RPM
5 AMPS
1/4 HP
90 VDC
1750 RPM
2.7 AMPS
TORQUE
TORQUE
TORQUE
IR COMP
IR COMP
IR COMP
2 HP
180 VDC
1750 RPM
9.2 AMPS
• Set voltage switch SW501 to either 115 or 230 to match
the AC line voltage (see Figure 4, page 6).
• Set voltage switch SW502 to either 90 or 180 to match the
maximum armature voltage (see Figure 4, page 6).
• Verify that no conductive material is present on the
printed circuit board.
• If using a 90 VDC or 130 VDC motor with 230 VAC line
voltage, derate the nameplate motor torque by at least
30%.
Startup
GS10
1 HP
180 VDC
1750 RPM
5 AMPS
WARNING
If the motor or drive does not perform as described
in this section, disconnect the AC line voltage
immediately. Refer to the Troubleshooting section for
further assistance.
1/2 HP
180 VDC
1750 RPM
1.3 AMPS
Figure 6. Recommended TORQUE and IR COMP
Figure 6. Recommended TORQUE and IR COMP Settings for MC10 Series Controls
Settings for GS10 Series Controls
1.Set the speed adjust potentiometer (SPEED dial) to “0”,
or full CCW.
2.Apply AC line voltage.
3.Set the POWER switch to the ON position.
4.Slowly advance the speed adjust potentiometer CW.
The motor slowly accelerates as the potentiometer is
turned CW. Likewise, the motor slowly decelerates as the
potenti­ometer is turned CCW. Continue until the desired
speed is reached.
5.To bring the motor to a stop, turn the speed adjust
potentiometer to “0” or set the POWER switch to the
OFF position.
8
GoldSpec™ User’s Manual
Application Notes
GS10-R
WARNING
WARNING
Do not change the motor direction while the motor
is running. The motor must come to a complete stop
before reversing. Changing motor direction before
allowing the motor to completely stop will cause
excessively high current to flow in the armature
circuit, and may damage the drive and/or motor.
Decelerating to minimum speed, inhibit operation,
or coasting to a stop is recom­mended for frequent
starts and stops. Do not use any of these methods
for emer­gency stopping. They may not stop a drive
that is malfunctioning. Removing the AC line power
(both L1 and L2) is the only acceptable method for
emergency stopping.
1.Set the FORWARD/OFF/REVERSE switch to the OFF
position.
Inhibit circuit
2.Set the speed adjust potentiometer (SPEED dial) to “0”, or
full CCW.
Maintianing a connection between the inhibit pins
(Figure 7) causes the motor to coast to minimum speed.
Removing the connection between the inhibit pins allow the
motor to accelerate to the speed set by the speed adjust
potentiometer.
3.Apply AC line voltage.
4.Set the FORWARD/OFF/REVERSE switch to the desired
direction of rotation.
5.Slowly advance the speed adjust potentiometer CW.
The motor slowly accelerates as the potentiometer is turned CW. Likewise, the motor slowly decelerates as the
potenti­ometer is turned CCW. Continue until the desired
speed is reached.
GoldSpec™ offers two accessory plug harnesses for
connecting to the INHIBIT terminals: part number GS2010024 [inhibit
Application
Notesplug with 18 inches (46 cm) leads]; and part
number GS201-0079 [inhibit plug with 36 inches (91 cm)
leads].
Twist inhibit wires and separate them from other powercarrying wires or sources of electrical noise. Use shielded
cable if the inhibit wires are longer than 18 inches (46 cm). If
shielded cable is used, ground only one end of the shield to
Earth ground. Do not ground both ends of the shield.
6.To bring the motor to a stop, turn the speed adjust
potentiometer to “0” or set the FORWARD/OFF/
REVERSE switch to the OFF position.
7.To reverse direction:
a.Set the FORWARD/OFF/REVERSE switch to the
OFF position.
b.After the motor comes to a complete stop, set the FORWARD/OFF/REVERSE switch to the
desired direction of rotation.
RUN
COAST TO
MIN SPEED
Signal Operation Calibration
IN
H
IB
IT
1.Set the Signal/Manual Switch located on the enclosure to
the SIGNAL position.
2.Apply the AC line voltage.
3.Set the POWER switch to the ON position.
SO501 SO501
2-PIN2-PIN
HEADER
HEADER
accessory plug
harness
201-0024 or
UseUse
accessory
plug
harness
201-0079 to mate with 2-pin header
to mate
with 2-pin header
(SO501) on control board.
(SO501) on control board
Figure 7. Inhibit Plug with Run/Coast to Minimum Speed
4.Apply minimum current or voltage signal. Adjust the SIG
MIN trimpot to achieve the desired minimum motor speed.
Figure 7. Inhibit Plug with Run/Coast to Minimum Speed
5.Apply the maximum current or voltage signal. Adjust the
SIG MAX trimpot to achieve the desired maximum motor
speed.
6.Application Notes
GS10 Series
9
Replace the speed adjust potentiometer with series resistors with a total series resistance
of 10K ohms (Figure 10). Add a single-pole, multi-position switch with the correct number
of positions for the desired number of fixed speeds.
Application Notes (continued)
Application Notes
Replace the speed adjust potentiometer with series
resistors with a total series resistance of 10K ohms (Figure
10). Add a single-pole, multi-position switch with the correct
number of positions for the desired number of fixed speeds.
The
switch shown
in Figure speed
8 may be used to decelerate a
Decelerating
to minimum
motor to minimum speed. Closing the switch between S1
and S2 decelerates the motor from set speed to minimum
The switch shown in Figure 8 may be used to decelerate a motor to minimum speed.
speed
determined
MIN
SPD trimpot
setting.
If the
Closing the
switch betweenby
S1 the
and S2
decelerates
the motor from
set speed
to minimum
speed determined by the MIN SPD trimpot setting. If the MIN SPD trimpot is set full CCW,
MIN
SPD
trimpot
is
set
full
CCW,
the
motor
decelerates
to
the motor decelerates to zero speed when the switch between S1 and S2 is closed. The
zero
when
the switch
between
and
S2 is closed.
DECELspeed
trimpot setting
determines
the rate
at which theS1
drive
decelerates.
By opening
the switch, the motor accelerates to set speed at a rate determined by the ACCEL trimpot
The
DECEL trimpot setting determines the rate at which
setting.
the drive decelerates. By opening the switch, the motor
accelerates to set speed at a rate determined by the ACCEL
trimpot setting.
R4
R3
R2
TOTAL SERIES
RESISTANCE
10K OHMS
50
2
R1
S3
S2
S0
S1
Decelerating to minimum speed
Multiple Fixed Speeds
RUN
Application Notes
Figure 10. Multiple Fixed Speeds
CLOSE TO
DECEL TO
MIN SPEED
Adjustable speeds using potentiometers in series
10K OHM
SPEED ADJUST
POTENTIOMETER
Adjustable
speeds using
Replace the speed adjust ptentiometer with a single-pole, multi-position switch, and two or
more
potentiometers
in series, with
series resistance of 10K ohms. Figure 11 shows
potentiometers
ina total
series
a connection for fixed high and low speed adjust potentiometers.
Figure 10. Multiple Fixed Speeds
Replace the speed adjust ptentiometer with a single-pole,
multi-position switch, and two or more potentiometers in
series, with a total series resistance of 10K ohms. Figure
11 shows a connection for fixed high and low speed adjust
potentiometers.
S3
S2
S0
S1
50
2
CW
Figure 8. Run/Decelerate to Minimum Speed Switch
Dynamic Braking
5K
OHM
WARNING
Sizing the dynamic brake resistor depends on load inertia,
motor voltage, and braking time. Use a lower-value, higherApplication Notes
wattage dynamic brake resistor to stop a motor more rapidly.
A2
RUN
MOTOR
DYNAMIC BRAKE
RESISTOR
BRAKE
CW
HIGH
SPEED
5K
OHM
CW
S1
50
S3
S2
S0
Dynamic braking may be used to rapidly stop a motor
(Figure 9). For the RUN/BRAKE switch, use a two-pole,
two-position switch rated for at least the maximum DC
armature voltage and maximum braking current. For the
dynamic brake resistor; use a 40 watt minimum, high power,
wirewound resistor.
LOW
SPEED
2
Wait forFigure
the motor
to completly stop before swtiching
8. Run/Decelerate to Minimum Speed Switch
it back to the RUN position. This will prevent high
armature currents from damaging the motor or drive.
A1
Figure
11. Adjustable Fixed Speeds Using
Application
Notes
Potentiometers in Series
Independent adjustable speeds
Independent adjustable speeds
Replace the speed adjust potentiometer with a single pole, multiposition switch, and two
or more potentiometers in parallel, with a total prallel resistance of 10K ohms. Figure
12 shows the connection of two independent speed adjust potentiometers that can be
mounted at two separate
operating
stations.
Figure 11.
Adjustable
Fixed Speeds Using Potentiometers in Series
Replace the speed adjust potentiometer with a single
pole, multiposition switch, and two or more potentiometers
in parallel, with a total prallel resistance of 10K ohms.
Figure 12 shows the connection of two independent speed
adjust potentiometers that can be mounted at two separate
operating stations.
SPEED 1
DYNAMIC BRAKE RESISTOR
15 ohm for 90 VDC motors
30 ohm for 180 VDC motors
20K
OHM
CW
CW
S1
S2
SO501 2-PIN HEADER
SO501 2-PIN HEADER
Figure 9. Dynamic Brake Connection
S3
Use
accessory
plug
harness 201-0024 or
Use
accessory
plug
harness
201-0079
to mate
with 2-pin header
to mate
with 2-pin
header
(SO501)
control board.
(SO501) on
controlon
board
10
20K
OHM
02
SPEED 2
S0
5
IBIT
INH
Figure 12. Independent Adjustable Speeds
Figure 12. Independent Adjustable Speeds
Figure 9. Dynamic Brake Connection
GoldSpec™ User’s Manual
RUN/JOG Switch
Leader-follower application
Notes
In this application, use a Process Control Application
Module (GS4)
to monitor the speed
of the leader motor (Figure 15). The
Leader-follower
application
GS4 isolates the leader motor from the follower drive, and
In this application, use a Process Control Module (PCM4) to monitor the speed of the
outputs a voltage proportional to the leader motor armature
leader motor (Figure 15). The PCM4 isolates the leader motor from the follower drive, and
outputs
a voltage
the leader
motor
armature
voltage.
The follower drive
voltage.
Theproportional
followertodrive
uses
this
voltage
reference
uses this voltage reference to set the speed of the follower motor. An optional ratio
to set themay
speed
motor.
An optional ratio
potentiomter
be usedoftothe
scalefollower
the PCM output
voltage.
potentiomter may be used to scale the GS4 output voltage.
Using a RUN/JOG switch is recommended in applications
where quick stopping is not needed and frequent
Applicationjogging
Notes is
required. Use a single pole, two position switch for the RUN/
RUN/JOG
Switch
JOG switch,
and a single pole, normally closed, momentary
operated
for theinJOG
pushbutton.
Using
a RUN/JOGpushbutton
switch is recommended
applications
where quick stopping is not
needed and frequent jogging is required. Use a single pole, two position switch for the
RUN/JOG switch, and a single pole, normally closed, momentary operated pushbutton for
the JOG pushbutton.
RUN/JOG option #1
RUN/JOG
option
In the first
wiring#1
option, connect the RUN/JOG switch and
In JOG
the firstpushbutton
wiring option, connect
theinhibit
RUN/JOGplug
switchas
andshown
JOG pushbutton
to the inhibit
to the
in Figure
13.
plug as shown in Figure 13. The motor coasts to minimum speed when the RUN/JOG
The
motor
coasts
to
minimum
speed
when
the
RUN/JOG
switch is set to JOG. Press the JOG pushbutton to jog the motor. Return the RUN/JOG
switch
to RUN
normal
operation.
switch
isforset
to JOG.
Press the JOG pushbutton to jog
RUN
INH
0
TB502
7 (-)
A2
S2
(-) 1
S1
Follower
Drive
10K Ohm
(optional)
Figure 15. Leader-Follower Application
Application Notes
Single speed potentiometer
Single speed potentiometer control of multiple drives
control
of multiple drives
Multiple drives can be controlled with a single speed adjust potentiometer using a Process
Control Module (PCM4) at the input of each drive to provide isolation (Figure 16). Optional
ratio potentiometers
can becan
used to
the PCM output
voltage,
allowing
independent
Multiple drives
bescale
controlled
with
a single
speed
adjust
control of each drive.
potentiometer using a Process Control Module (GS4) at the
input of each drive to provide isolation (Figure 16). Optional
ratio potentiometers can be used to scale the GS output
voltage, allowing independent control of each drive.
SO501 2-PIN HEADER
SO501 2-PIN HEADER
Use accessory plug harness 201-0024 or
Use accessory plug harness
201-0079 to mate with 2-pin header
to mate with
2-pinon
header
(SO501)
control board.
(SO501) on control board
2
6
Figure 13. RUN/JOG Switch Option #1
Application Notes
10K Ohms
Figure 13. RUN/JOG Switch Option #1
RUN/JOG
option option
#2
RUN/JOG
GS4
PCM4
Figure 15. Leader-Follower Application
JOG
IBIT
8
MOTOR
TB501
the motor. Return the RUN/JOG switch to RUN for normal
operation.
JOG
PUSHBUTTON
(+) 2
9 (+)
A1
Leader
Drive
8
TB501
In the second wiring option, connect the RUN/JOG switch and the JOG pushbutton as
shown in Figure 14. When the RUN/JOG switch is set to JOG, the motor decelerates to
In the second wiring option, connect the RUN/JOG switch
minimum speed (minimum speed is determined by the MIN SPD trimpot setting). Press the
JOG pushbutton
the motor.
Return the as
RUN/JOG
switch
RUN for normal
operation.
and theto jog
JOG
pushbutton
shown
intoFigure
14. When
the RUN/JOG switch is set to JOG, the motor decelerates
to minimum speed (minimum speed is determined by the
MIN SPD trimpot setting). Press the JOG pushbutton to jog
the motor. Return the RUN/JOG switch to RUN for normal
operation.
7
TB501
Drive
A
S1
1
A1
Motor
A
A2
TB502
6
8
S2
PCM4
GS4
7
#2
ratio pot A
(optional)
10K Ohms
2
ratio pot B
(optional)
10K Ohms
A1
S2
PCM4
GS4
1
S1
Drive
B
Motor
B
A2
TB502
Figure 16. Single Speed Potentiometer
Control of Multiple Drives
Figure 16. Single Speed Potentiometer Control of Multiple Drives
JOG
PUSHBUTTON
RUN
JOG
10K OHM
SPEED ADJUST
POTENTIOMETER
S3
S2
S0
S1
50
2
CW
Figure 14. RUN/JOG Switch Option #2
Figure 14. RUN/JOG Switch Option #2
GS10 Series
11
Application Notes (continued)
Troubleshooting
Reversing
WARNING
A dynamic brake may be used when reversing the motor
direction (Figure 17). Use a three-pole, three-position
Application Notes
switch rated for at least the maximum DC armature voltage
Reversing
and maxi­mum braking current. Wait for the motor to stop
completely
before
it the
to motor
either
the forward
A dynamic
brake may
be usedswitching
when reversing
direction
(Figure 17).or
Use a threepole, three-position switch rated for at least the maximum DC armature voltage and maxireverse
direction.
See
the
dynamic
braking
section,
page
mum braking current. Wait for the motor to stop completely before switching it to either the
10, for
recommended
dynamic
brake
resistor
sizes.
NOTE:
forward
or reverse
direction. See the
dynamic braking
section,
page 24,
for recommended
dynamic brake resistor sizes. NOTE: Model MC10-R is equipped with the reversing feature,
Model GS10-R is equipped with the reversing feature, but
but not the dynamic brake feature.
not the dynamic brake feature.
A1
Dangerous voltages exist on the drive when it is
powered. When possible, disconnect the drive while
troubleshooting. High voltages can cause serious or
fatal injury.
Before troubleshooting
• Perform the following steps before starting any procedure
in this section:
• Disconnect AC line voltage from the drive.
• Check the drive closely for damaged components.
A2
• Check that no conductive or other foreign material has
become lodged on the printed circuit board.
DYNAMIC
BRAKE
RESISTOR
MOTOR
• Verify that every connection is correct and in good
condition.
FWD
• Verify that there are no short circuits or grounded
connections.
BRAKE
REV
SO501 2-PIN HEADER
SO501 2-PIN HEADER
Use
plug harness
harness201-0024
to
Useaccessory
accessory plug
or
mate201-0079
with 2-pin
(SO501)
to header
mate with
2-pin header
(SO501)
control board.
on
controlon
board
• Check that the voltage switch settings match the AC line
and maximum armature output voltages.
• Check that the drive’s rated armature outputs are
consistent with the motor ratings.
IN
HI
BI
T
Power and Current Limit LEDs
Figure 17. Reversing Circuit Connection
Patriot Series drives are equipped with a green,
PCB-mounted power LED and a red, PCB-mounted
current limit LED.
Figure 17. Reversing Circuit Connection
Troubleshooting
POWER LED (IL502)
Power
andpower
CurrentLED
Limitturns
LEDs on when AC line voltage is
The
green
Patriot Series
drives drive.
are equipped with a green, PCB-mounted power LED and a red, PCBapplied
to the
mounted current limit LED.
POWER LED (IL502)
CURRENT
(IL501)
The green powerLIMIT
LED turns on
when AC line voltage is applied to the drive.
TheCURRENT
red current
LIMIT (IL501)limit LED turns on when the drive reaches
The red current limit LED turns on when the drive reaches current limit and turns off whencurrent
and
turns
off when­
ever the drive is not in
ever the limit
drive is not
in current
limit (normal
operation).
current limit (normal operation).
POWER LED (IL502)
IL502
IC501
CURRENT
LIMIT
IL501
DECEL
IR COMP
MIN SPD
MAX SPD
90-180
ACCEL
230-115
R501
C503
SW501
SO502
T501
S3 S2 S1
TQ LIMIT
SW502 INHIBIT
IC502
SO501
C501
C504
POWER
C502
CURRENT LIMIT LED (IL501)
Figure 18. Current Limit LEDs
MOV502
MOV501
R502
Figure 18. Current Limit LEDs
F502
12
GoldSpec™ User’s Manual
MOV503
F501
TB501
L2 FRM SW L1
A2 TO SW A1
L2 TO SW L1
A2 FRM SW A1
Problem
Line fuse blows.
Possible
Causes
1. Line fuse is the wrong
size.
2. Motor cable or
armature is shorted to
ground.
Suggested
Solutions
1. Check that the line fuse
is correct for the motor
size.
2. Check motor cable and
armature for shorts.
3. Nuisance tripping
3. Add a blower to cool
caused by a
the drive components;
combination of ambient
decrease TORQUE
conditions and highsettings, or resize
current spikes (i.e.
motor and drive for
reversing).
actual load demand,
or check for incorrectly
aligned mechanical
components or
“jams”. See page 7
for information on
adjusting the TORQUE
trimpot.
Line fuse does not blow
or circuit breaker does
not trip, but the motor
does not run
1. Reference signal or
speed adjust pot is set
to zero speed.
1. Increase reference
signal or speed adjust
potentiometer setting.
2. Reference signal
or speed adjust
potentiometer
connections are open.
2. Check that the
reference signal
or speed adjust
potentiometer
connections are not
open.
3. Drive is in current limit.
4. Drive is not receiving
AC line voltage.
5. Motor is not
connected.
3. Verify that the motor is
not jammed. Increase
TORQUE setting
(page 7).
4. Apply AC line voltage
to L1 and L2.
5. Connect motor to A1
and A2.
Problem
Possible
Causes
Suggested
Solutions
Motor runs too fast at
maximum speed setting.
1. MIN SPD and MAX
1. Recalibrate MIN SPD
SPD are not calibrated.
(page 7) and MAX
SPD (page 7).
Motor runs too slow or
too fast.
1. MIN SPD and MAX
1. Recalibrate MIN SPD
SPD are not calibrated.
(page 7) and MAX
SPD (page 7).
Motor will not reach the
desired speed.
1. MAX SPD setting is
too low.
1. Increase MAX SPD
setting (page 7).
2. IR COMP setting is
too low.
2. Increase IR COMP
setting
3. Motor is overloaded.
3. (page 7).
4. Check motor load.
Resize the motor or
drive if necessary.
Motor pulsates or surges
under load.
1. R COMP is set too
high.
2. Control is in current
limit mode.
1. Adjust the IR COMP
setting slightly CCW
until the motor speed
stabilizes (page 7).
2. Check that motor is of
sufficient horsepower
and amperage.
On non-reversing
drives, motor runs in the
opposite direction.
1. Reverse connections
to the motor armature.
1. Reverse connections
to the motor armature.
Motor will not stop
when the speed adjust
potentiometer or
reference signal is set to
zero speed.
1. MIN SPD trimpot is not 1. Slowly rotate the MIN
adjusted properly.
SPD trimpot until the
motor stops.
GS10 Series
13
NOTES
14
GoldSpec™ User’s Manual
NOTES
GS600 Series
15
Corporate Headquarters
1 Applied Plaza, Cleveland, Ohio 44115
Toll Free Phone: 1-877-279-2799
Applied.com
© 2009 Applied Industrial Technologies, Inc. All Rights Reserved. C-0609-11-5450
GoldSpec™ is a registered trademark of Applied Industrial Technologies.
GoldSpec™ User’s Manual

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement