advertisement
Realflo
Reference and User Manual
5/19/2011
The information provided in this documensstation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to help ensure compliance with documented system data, only the manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must be followed. Failure to use Schneider Electric software or approved software with our hardware products may result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2011 Schneider Electric. All rights reserved
Table of Contents
Table of Contents ...................................................................... 1
Important Safety Information ................................................. 14
About The Book ........................................................................ 1
Introduction ............................................................................... 2
Realflo Maintenance Mode Reference ................................... 19
Select Flow Computer Wizard ................................................................... 22
Read Logs and Flow History .................................................................... 127
Connections for SCADAPack Sensor Calibration ................................... 145
View and Change Configuration Wizard .................................................. 194
Document (Version #.##.#) 5/19/2011
Table of Contents
Realflo Expert Mode Reference ........................................... 202
Print Preview Command .......................................................................... 222
Print Setup Command in PEMEX Mode .................................................. 223
Custom Views Command ........................................................................ 226
Write Initial Values Command ................................................................. 240
Current Readings Command ................................................................... 243
Hourly History Command ......................................................................... 246
Hourly Gas Quality History Command ..................................................... 252
Document Revised May 19, 2011
Table of Contents
More Views Command ............................................................................ 256
Run 1 . . . Run 10 Commands ................................................................. 257
Change All Views Command ................................................................... 258
Replace Flow Computer .......................................................................... 260
Flow Computer Information ..................................................................... 278
Power Management Configuration .......................................................... 383
Gas Sampler Output Configuration.......................................................... 386
C/C++ Program Loader ........................................................................... 408
Override Flow Computer Lock ................................................................. 414
Document Revised May 19, 2011
Table of Contents
Update Readings Once ........................................................................... 460
PC Communications Settings Command ................................................ 465
Connect to Controller Command ............................................................. 524
Disconnect from Controller Command .................................................... 524
New Window Command .......................................................................... 526
Realflo Wizards ..................................................................... 528
Read Configuration From the Flow Computer ......................................... 530
Create Configuration From a Template File ............................................ 535
Create Configuration Step-by-Step.......................................................... 576
Replace Flow Computer Wizard ................................................................... 619
Read Logs and Flow History Wizard............................................................. 626
Connect to Flow Computer ...................................................................... 626
Select Flow Computer Configuration ....................................................... 628
Select Alarm and Event Logs to Read ..................................................... 628
Select Hourly and Daily History to Read ................................................. 629
Document Revised May 19, 2011
Table of Contents
Connect to Flow Computer ...................................................................... 643
Run Calibration Procedure ...................................................................... 646
MVT Calibration Procedure ..................................................................... 660
Connect to Flow Computer ...................................................................... 676
Choose Orifice Fitting Type Step ............................................................. 678
Connect to Flow Computer ...................................................................... 687
Select Run or Transmitter to Force ......................................................... 688
TeleBUS Protocol Interface .................................................. 692
Configuration Command Execution ......................................................... 709
User Account Configuration ..................................................................... 751
Flow Computer Execution Control ........................................................... 758
Document Revised May 19, 2011
Table of Contents
Flow Computer ID Configuration ............................................................. 759
Enron Modbus Time Stamp Configuration .............................................. 760
Real Time Clock Configuration ................................................................ 761
SolarPack 410 Power Management Configuration.................................. 764
SolarPack 410 Gas Sampler Output........................................................ 766
SolarPack 410 Pulse Input Accumulation ................................................ 768
Display Control Configuration .................................................................. 770
Process Input / Output Configuration ...................................................... 776
Event and Alarm Log Data ....................................................................... 798
Program Information Registers ................................................................ 812
Flow Computer Events and Alarms .............................................................. 814
Global Events and Alarms ....................................................................... 814
AGA-3 (1985) Events and Alarms ........................................................... 816
AGA-3 (1992) Events and Alarms ........................................................... 817
AGA-7 Events and Alarms ....................................................................... 818
AGA-11 Events and Alarms ..................................................................... 818
V-Cone Events and Alarms ..................................................................... 819
AGA-8 Events and Alarms ....................................................................... 820
NX-19 Events and Alarms ....................................................................... 821
Sensor Events and Alarms ...................................................................... 822
Calibration and User Defined Alarms and Events ................................... 834
AGA-3 (1985) Calculation Errors ............................................................. 836
AGA-3 (1992) Calculation Errors ............................................................. 837
AGA-11 Calculation Errors ...................................................................... 838
Flow Calculation Engine Command Errors .............................................. 840
MVT Command Errors ............................................................................. 842
Document Revised May 19, 2011
Table of Contents
AGA-3 Command Errors .......................................................................... 843
AGA-7 Command Errors .......................................................................... 843
AGA-11 Command Errors ........................................................................ 843
V-Cone Command Errors ........................................................................ 843
AGA-8 Command Errors .......................................................................... 844
NX-19 Command Errors .......................................................................... 844
Flow Computer Register Grouping ...................................... 847
Configure Register Group Location .............................................................. 849
Flow Computer Application ID ............................................. 850
Device Configuration Read Only Registers .................................................. 851
Enron Modbus Protocol Interface ........................................ 854
Flow Computer Variables ........................................................................ 856
Enron Modbus General Purpose Registers .................................................. 858
Program Information Variables ................................................................ 860
Meter Runs Configuration Variable ......................................................... 860
Real Time Clock Variables ...................................................................... 860
Flow Computer ID Variables .................................................................... 861
Hourly / Daily Archive Records ................................................................ 861
Hourly Gas Quality Archive Records ....................................................... 863
Flow Computer Events Variables ............................................................ 864
User Account Events Variables ............................................................... 864
Event/Alarm Archive Variable .................................................................. 864
Event and Alarm Log Events Variables ................................................... 864
Meter Run 1 Flow Computer Execution State Variable ........................... 867
Meter Run 1 Instantaneous and Accumulated Variables ........................ 867
Document Revised May 19, 2011
Table of Contents
Meter Run 1 Input Configuration Variables ............................................. 870
Meter Run 1 Flow Computer Execution Control Variable ........................ 873
Meter Run 1 Contract Configuration Variables ........................................ 874
Meter Run 1 AGA-3 Configuration Variables ........................................... 875
Meter Run 1 V-Cone Configuration Variables ......................................... 875
Meter Run 1 AGA-7 Configuration Variables ........................................... 876
Meter Run 1 AGA-8 Configuration Variables ........................................... 877
Meter Run 1 NX-19 Configuration Variables ........................................... 881
Plate Change Events Variables ............................................................... 881
Enron Forcing Events Variables .............................................................. 882
Meter Run 1 Flow Computer Events Variables ....................................... 883
MVT-1 Data and Configuration Variables ..................................................... 890
MVT-1 MVT Configuration Variables ....................................................... 891
MVT-2 Data and Configuration Variables ..................................................... 894
MVT-3 Data and Configuration Variables ..................................................... 895
MVT-4 Data and Configuration Variables ..................................................... 895
MVT-5 Data and Configuration Variables ..................................................... 895
MVT-6 Data and Configuration Variables ..................................................... 896
MVT-7 Data and Configuration Variables ..................................................... 896
MVT-8 Data and Configuration Variables ..................................................... 897
MVT-9 Data and Configuration Variables ..................................................... 897
MVT-10 Data and Configuration Variables ................................................... 898
Global Alarms and Events ....................................................................... 900
AGA-3 (1985) Alarms and Events ........................................................... 902
AGA-3 (1992) Alarms and Events ........................................................... 903
AGA-7 Alarms and Events ....................................................................... 904
Document Revised May 19, 2011
Table of Contents
AGA-11 Alarms and Events ..................................................................... 904
V-Cone Alarms and Events ..................................................................... 904
AGA-8 Alarms and Events ....................................................................... 905
NX-19 Alarms and Events ....................................................................... 907
MVT Alarms and Events .......................................................................... 907
Coriolis Meter Alarms and Events ........................................................... 909
Calibration and User Defined Alarms and Events ................................... 909
AGA-3 (1985) Calculation Errors ............................................................. 910
AGA-3 (1992) Calculation Errors ............................................................. 910
PEMEX Modbus Protocol Interface ..................................... 913
Meter Run 1 Instantaneous and Accumulated Variables ........................ 914
Meter Run 1 Historic Variables ................................................................ 915
Meter Run 2 Instantaneous and Accumulated Variables ........................ 915
Meter Run 2 Historic Variables ................................................................ 916
Meter Run 3 Instantaneous and Accumulated Variables ........................ 916
Meter Run 3 Historic Variables ................................................................ 917
Meter Run 4 Instantaneous and Accumulated Variables ........................ 917
Meter Run 4 Historic Variables ................................................................ 918
Gas Quality History Record Format ......................................................... 919
Gas Composition Configuration ............................................................... 920
Document Revised May 19, 2011
Table of Contents
Gas Composition Configuration ............................................................... 923
Gas Composition Configuration ............................................................... 923
AGA Calculation Method ......................................................................... 924
Global Alarms and Events ....................................................................... 925
AGA-3 (1985) Alarms and Events ........................................................... 929
AGA-3 (1992) Alarms and Events ........................................................... 929
AGA-7 Alarms and Events ....................................................................... 930
AGA-11Alarms and Events ...................................................................... 931
V-Cone Alarms and Events ..................................................................... 931
AGA-8 Alarms and Events ....................................................................... 932
NX-19 Alarms and Events ....................................................................... 933
MVT Alarms and Events .......................................................................... 934
Coriolis Meter Alarms and Events ........................................................... 935
Calibration and User Defined Alarms and Events ................................... 935
AGA-3 (1985) Calculation Errors ............................................................. 937
AGA-3 (1992) Calculation Errors ............................................................. 937
AGA-11 Calculation Errors ...................................................................... 938
Retrieval and Acknowledgment of Events and Alarms ................................. 939
Alarm or Event Record Format ................................................................ 939
Alarm Acknowledgement ......................................................................... 940
Measurement Units ............................................................... 941
Document Revised May 19, 2011
Table of Contents
Input Averaging ..................................................................... 948
Flow-Dependent Time Weighted Linear Average ......................................... 948
Creating Custom Realflo Applications ................................ 950
Building the Application for Telepace Firmware ...................................... 952
Building the Application for ISaGRAF Firmware ...................................... 952
SCADAPack 314/330/334 and SCADAPack 350 Controllers ...................... 953
Measurement Canada Approved Version ........................... 956
Flow Computer Disabled Commands ........................................................... 956
Enron Protocol Disabled Commands ............................................................ 957
Measurement Canada Lockout Cable .......................................................... 958
Document Revised May 19, 2011
Table of Contents
Measurement Canada Approved Flow Computers ....................................... 958
SCADAPack 330/334 .............................................................................. 958
SCADAPack and SCADAPack LP........................................................... 959
SCADAPack 4203 DR ............................................................................. 959
SCADAPack 4203 DS ............................................................................. 960
SCADAPack 4202 DR ............................................................................. 960
SCADAPack 4202 DS ............................................................................. 961
DNP3 Protocol User Manual ................................................. 962
Modbus Database Mapping ..................................................................... 965
SCADAPack DNP Operation Modes ....................................................... 966
How to Configure SCADAPack DNP Outstation ..................................... 967
SCADAPack DNP Master Concepts ....................................................... 973
How to Configure SCADAPack DNP Master ........................................... 977
How to Configure SCADAPack Address Mapping .................................. 981
How to Configure SCADAPack DNP Mimic Master ................................ 982
How to Configure a SCADAPack DNP Router ........................................ 983
Considerations of DNP3 Protocol and SCADAPack DNP Driver ............ 987
Typical Configuration Malpractices and Recommendations ................... 987
DNP Configuration Menu Reference ............................................................ 996
Application Layer Configuration ............................................................... 997
Data Link Layer Configuration ............................................................... 1002
Binary Inputs Configuration ................................................................... 1017
Binary Outputs Configuration ................................................................. 1020
Document Revised May 19, 2011
Table of Contents
–Bit Analog Inputs Configuration ....................................................... 1023
32-Bit Analog Inputs Configuration ........................................................ 1026
Short Floating Point Analog Inputs ........................................................ 1029
16-Bit Analog Outputs Configuration ..................................................... 1033
32-Bit Analog Outputs Configuration ..................................................... 1035
Short Floating Point Analog Outputs ..................................................... 1037
–Bit Counter Inputs Configuration ..................................................... 1040
32-Bit Counter Inputs Configuration ...................................................... 1043
DNP Master Device Profile Document ........................................................ 1055
DNP Slave Device Profile Document .......................................................... 1071
Document Revised May 19, 2011
Important Safety Information
Important Safety Information
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will
result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, can
result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can
result in minor or moderate.
CAUTION
CAUTION used without the safety alert symbol, indicates a potentially hazardous
Document Revised May 19, 2011
Important Safety Information situation which, if not avoided, can result in equipment damage..
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and the installation, and has received safety training to recognize and avoid the hazards involved.
BEFORE YOU BEGIN
Do not use this product on machinery lacking effective point-of-operation guarding. Lack of effective point-of-operation guarding on a machine can result in serious injury to the operator of that machine.
CAUTION
UNINTENDED EQUIPMENT OPERATION
Verify that all installation and set up procedures have been completed.
Before operational tests are performed, remove all blocks or other temporary holding means used for shipment from all component devices.
Remove tools, meters, and debris from equipment
Failure to follow these instructions can result in death, serious injury or equipment damage.
Follow all start-up tests recommended in the equipment documentation. Store all equipment documentation for future references.
Software testing must be done in both simulated and real environments.
Verify that the completed system is free from all short circuits and grounds, except those grounds installed according to local regulations (according to the
National Electrical Code in the U.S.A, for instance). If high-potential voltage testing is necessary, follow recommendations in equipment documentation to prevent accidental equipment damage.
Before energizing equipment:
Remove tools, meters, and debris from equipment.
Close the equipment enclosure door.
Remove ground from incoming power lines.
Perform all start-up tests recommended by the manufacturer.
Document Revised May 19, 2011
Important Safety Information
OPERATION AND ADJUSTMENTS
The following precautions are from the NEMA Standards Publication ICS 7.1-
1995 (English version prevails):
Regardless of the care exercised in the design and manufacture of equipment or in the selection and ratings of components, there are hazards that can be encountered if such equipment is improperly operated.
It is sometimes possible to misadjust the equipment and thus produce unsatisfactory or unsafe operation. Always use the manufacturer‟s instructions as a guide for functional adjustments. Personnel who have access to these adjustments should be familiar with the equipment manufacturer‟s instructions and the machinery used with the electrical equipment.
Only those operational adjustments actually required by the operator should be accessible to the operator. Access to other controls should be restricted to prevent unauthorized changes in operating characteristics.
Document Revised May 19, 2011
About The Book
About The Book
At a Glance
Document Scope
This manual describes the Realflo programming environment for
SCADAPack controllers.
Validity Notes
This document is valid for all versions of Realflo.
Product Related Information
WARNING
UNINTENDED EQUIPMENT OPERATION
The application of this product requires expertise in the design and programming of control systems. Only persons with such expertise should be allowed to program, install, alter and apply this product.
Follow all local and national safety codes and standards.
Failure to follow these instructions can result in death, serious injury or equipment damage.
User Comments
We welcome your comments about this document. You can reach us by email at [email protected].
Realflo User and Reference Manual
May 19, 2011
1
Introduction
Overview
Introduction
Realflo is a Man-Machine Interface to the Control Microsystems Gas Flow
Computer. The Gas Flow Computer runs on any of the SCADAPack controllers (4202 DR, 4202 DS, 4203 DR or 4203 DS), SCADAPack 32,
SCADAPack 300, SCADAPack, SCADAPack 100: 1024K, SCADAPack LP controllers and SolarPack 410. Realflo allows editing of the flow computer configuration parameters with configuration dialogs for process inputs, contract specifications, compressibility calculations, and flow calculations for each meter run. The operator may write configuration data to the flow computer or read it back. parameter checking is provided on user entries.
The flow computer is an electronic natural gas flow computer providing the following industry standard calculations:
AGA-3 (1992) for gas volume calculation with orifice meters;
AGA-7 for gas volume calculation with turbine meters;
AGA-11 for gas volume calculations with Coriolis meters (this calculation type is not supported on 16-bit controllers);
V-Cone for gas volume calculation with V-Cone gas flow meters;
AGA-8 Detailed calculation for gas compressibility calculation; and
NX-19 for gas compressibility calculation in legacy applications.
Realflo displays the flow computer current readings, historical logs, alarm logs, and event logs for each meter run. Realflo supports having multiple configuration and display windows open simultaneously to display data from multiple views.
Realflo can be used to configure and calibrate the SCADAPack 4000, 4202, and 4203, as well as Rosemount MVT transmitters. The gas flow computer automatically polls the MVT transmitter for sensor information used in the gas flow calculations.
Realflo generates customized reports for configuration data, historical data logs, gas quality historical data logs, event logs, alarm logs, and calibrations.
Realflo can save configuration parameters, current readings, historical data logs, and event logs to spreadsheet files in csv format or in Flow-Cal cfx format.
Realflo provides wizard-style dialogs to guide you through the configuration, maintenance and calibration procedures.
The flow computer integrates with SCADA systems using Modbuscompatible communications. You can access data, configuration, and calculation factors over a SCADA network as well as locally at the flow computer. This manual describes the configuration and operation procedures for these systems.
Realflo User and Reference Manual
May 19, 2011
2
Introduction
The flow computer supports Enron Modbus protocol. This protocol is used widely in the Oil and Gas industry to obtain data from electronic flow measurement devices. The protocol is a de-facto standard in many industries.
The flow computer supports PEMEX Modbus protocol. This protocol is used in the Oil and Gas industry to obtain data from electronic flow measurement devices.
Users may integrate the flow calculation capability with user applications written in Ladder Logic, IEC 61131-3 or C/C++.
Realflo User and Reference Manual
May 19, 2011
3
Introduction
System Requirements
Realflo 6.70 is supported on the following operating systems (32- and 64-bit platforms):
Microsoft Windows 2000 Professional
Microsoft Windows XP Professional
Microsoft Windows Vista Ultimate on 32-bit and 64-bit platforms
Microsoft Windows Vista Enterprise on 32-bit and 64-bit platforms
The Realflo program requires the following minimum system configuration.
Pentium 133MHz or better.
Minimum screen resolution supported is 1024 by 768.
Minimum 32 MB of RAM, 64MB recommended.
Mouse or compatible pointing device.
Hard disk with approximately 35 Mbytes of free disk space.
Organization of the Manual
New users should read the sections in order, to gain an understanding of underlying concepts before tackling detailed material.
The Realflo Installation Procedure section describes how to install Realflo.
The Realflo Maintenance Mode section describes how to use Realflo in the
Maintenance Mode.
The Realflo Expert Mode section describes how to use Realflo in the Expert
Mode.
The Realflo Wizards section describes how to use the configuration wizards available in Realflo.
The Measurement Units section describes the available units of measure.
The Creating Custom Realflo Applications section describes modifying the flow computer application.
The following sections describe communication with a SCADA system. If you are using Realflo alone these sections are not needed.
The TeleBUS Protocol Interface section describes interfacing the flow computer with a SCADA host.
Flow Computer Register Grouping section describes how to group commonly read data from a SolarPack 410 flow computer.
Flow Computer Application ID section describes the configuration registers that provide useful information on the flow computer, logic applications, and controller used in a Realflo application.
The Enron Modbus Protocol Interface section describes interfacing the flow computer with an Enron Modbus host.
The PEMEX Modbus Protocol Interface section describes interfacing the flow computer with a PEMEX Modbus host.
The DNP3 User Manual section describes interfacing the flow computer with a DNP host.
Realflo User and Reference Manual
May 19, 2011
4
Introduction
Additional Documentation
The Control Microsystems Hardware User Manual is a complete reference to Flow Computer and 5000 I/O modules.
The Telepace Ladder Logic Reference and User Manual describes the creation of application programs in the Ladder Logic language.
The ISaGRAF User and Reference Manual describes the creation of application programs using IEC 61131-3 languages.
The TeleBUS Protocols User Manual describes communication using
Modbus compatible protocols.
The TeleBUS DF1 Protocol User Manual describes communication using
DF1 compatible protocols.
Realflo User and Reference Manual
May 19, 2011
5
Installation
Introduction
Before using Realflo, you need to install the Realflo program on your system. The installation is automated and takes only a few minutes.
Some virus checking software may interfere with Setup. If you experience any difficulties with Setup, disable your virus checker and run Setup again.
To install Realflo, follow these steps:
(1) Insert the Realflo setup CD into CD drive. The CD loads automatically.
Realflo and Firmware Loader need to be installed.
(2) Select Install Realflo to start the Realflo install wizard.
(3) Select Install Firmware Loader to start the Firmware Loader install wizard.
(4) Select Install Adobe Reader to install the Adobe Acrobat reader.
(5) Select Control Microsystems Web Site to open the CD version of the website.
(6) Select Browse CD to open Windows Explorer and view the CD contents.
(7) Select Exit to close the Realflo install menu.
Flow computers used with Realflo need to have 1024K RAM and have the
Flow Run option enabled. Contact Control Microsystems to purchase a memory upgrade or flow run option.
Realflo User and Reference Manual
May 19, 2011
6
Introduction
Version Release Notes
New Features in Realflo 6.77
Realflo 6.77 includes the following new features and enhancements.
When restoring a configuration after a flow computer upgrade any forced values used in the configuration can be restored.
The Enron Modbus Gas Analysis history is now available. Gas Quality
History is available when the Gas Transmission option bit is enabled for the controller.
Time stamping of Enron Modbus can be defined as time leads data or time lags data for flow data.
Support for polling sensors for 10 runs in a SCADAPack 32 flow computer is added. Sensors and Coriolis meters can be polled using multiple serial ports and the flow computer manages the polling so that a 1 second poll of each sensors is achieved.
Acknowledging of Alarms and Events is now configurable so the Host
SCADA system can have control over how alarms and events are acknowledged.
The selection of forward or reverse sensing is added. The direction status register can now be configured for the On status, i.e. forward indicated by On or reverse indicated by On.
An indication of a configuration change in the flow computer density calculation is added. Registers provide the time and date of configuration changes to the AGA-8 calculation. This includes changes to the gas composition.
New Features in Realflo 6.76
AGA-11, Coriolis Mass Flow Meter Support
A new flow calculation type, AGA-11, is added to Realflo. The AGA-11 calculation supports the Endress and Hauser Promass 83 Coriolis meter.
Bi-Directional Flow Support
Realflo supports bi-directional flow. Flow direction, forward or reverse, is indicated by a value or status allowing flow rates and accumulation to be done for each flow direction.
New Features in Realflo 6.75
Windows7 Support Added
Realflo Supports for Windows 7 OS.
New Features in Realflo 6.74
Realflo 6.74 includes the following new features and enhancements.
When gas ratios are written to the flow computer using the Write
Configuration command or the Set AGA8 command the new gas ratios are updated in the Configuration Proposed registers and in the
Configuration Actual registers. This allows a Realflo user or SCADA host to immediately confirm the new ratios were written to the flow
Realflo User and Reference Manual
May 19, 2011
7
Introduction computer. The new gas ratios are not used by the flow computer until a new density calculation is started.
The writing of Real Time Clock, AGA-8 and Orifice plate configuration changes from a host to the flow computer has been simplified with the addition of the Modbus Mapping Settings. Using Modbus Mapping run configuration changes can be written to the flow computer as a single block of registers without the need of TeleBUS Command sequences.
Operator response time is significantly improved over previous versions of Realflo. This results in significant time savings when an operator first goes online with a flow computer and when monitoring online.
Measurement Canada approval for SCADAPack 4203, SCADAPack
314/330/334, SolarPack 410 and SCADAPack 32 is added.
New Features in Realflo 6.73
Wet gas correction factor is added for the two models of the V-Cone device: the V-Cone and the Wafer Cone.
New Features in Realflo 6.72
Support for the SCADAPack 314 controller is added.
New Features in Realflo 6.71
The V-Cone calculation is improved to include the Wafer Cone device. The
V-Cone configuration now includes a selection for adiabatic expansion factor type when either V-Cone or Wafer Cone devices are used.
New Features in Realflo 6.70
Realflo version 6.70 includes the following new features and enhancements:
PEMEX Modbus Protocol Support
New data columns to display the start time for the period, events logged during the period, and alarms logged during the period.
New Volume PEMEX column on the Hourly and Daily History tables displays the corrected volume for a flow when PEMEX is configured.
Realflo provides one set of base conditions for temperature and pressure as part of the contract configuration for a specific run. PEMEX
Modbus requests a second default set of base conditions (secondary conditions). The default set of base conditions is:
20°C (68°F) and 1 kg/cm2 (14.22334 psi)
The hourly history Volume PEMEX column displays the corrected volume for the flow.
New Up-Time column added to the PEMEX Hourly and Daily History tables shows the measurement time (in minutes) in the contract day.
New Average Heating Value column added to the PEMEX Hourly and
Daily History tables displays the average heating value accumulated during the contract period.
New Quality column added to the PEMEX Hourly and Daily History tables to indicate if there are alarms during the period.
New Hourly and Daily History tables to display PEMEX-specific data.
Realflo User and Reference Manual
May 19, 2011
8
Introduction
Gas Quality Control History
The Gas Quality Control History feature has been added to the View menu.
This feature includes the following:
Gas Quality History feature now provides a method to record and store the average value of natural gas components in the hourly history event log.
Flow Computer Report Quality History feature now provides a method to create, store, and print gas quality history reports for the calculations of the natural gas components in the hourly event history log.
Realflo Display Quality History feature provides a method to display gas quality history reports for the calculations of the natural gas components in the hourly event history log.
Realflo Display Quality History feature provides a method to read gas quality history reports of the natural gas components in the hourly event history log.
Realflo Display Quality History feature provides a method to export gas quality history reports of the natural gas components in the hourly event history log.
New Features in Realflo 6.51
Realflo version 6.51 includes the following new features and enhancements:
Flow Computer Register Grouping
Register grouping provides a method to group commonly read data from a
SolarPack 410 flow computer. The data that is commonly read is in scattered register locations in the flow computer. Register grouping enables the SCADA Host to read a sequential block of data in a single read command. The start address for the register group is user defined.
New Features in Realflo 6.50
Realflo version 6.50 includes the following new features and enhancements:
Support for SCADAPack 330 and SCADAPack 334 Controllers
The SCADAPack 330 and SCADAPack 334 controllers support up to four meter runs. The Flow Computer Information and Replace Flow Computer dialogs are displayed differently when the SCADAPack 330, SCADAPack
334 and SCADAPack 350 controller is used. These dialogs display the multiple C/C++ programs that can execute in the SCADAPack 330,
SCADAPack 334 and SCADAPack 350 controller.
New Features in Realflo 6.42
Realflo version 6.42 includes the following new features and enhancements:
Enron General Purpose Registers Added
Using fixed register mapping the flow computer mirrors standard Modbus registers into Enron Modbus registers. This allows the host to read and write data to Enron Modbus registers not directly associated with the flow computer.
Realflo User and Reference Manual
May 19, 2011
9
Introduction
Remove AGA-3 (1985) Flow Calculations
AGA-3 (1985) calculation type is removed for SCADAPack 5203/4,
SCADAPack LP, SCADAPack 100 and SCADAPack 4202 flow computers.
The following Modbus register commands have been removed.
351 Get AGA-3 (1985) Configuration
353 Set AGA-3 (1985) Configuration
The following changes have been made to the Enron Modbus handler.
Register 7101 and 7351: Flow calculation type 2 = AGA-3 (1985) is recognized by SCADAPack 5203/4, SCADAPack LP, SCADAPack 100 and SCADAPack 4202 flow computers up to version 6.41.
Register 7151 to 7161 and 7401 to 7411: These registers read and write configuration for AGA-3 (1985 and 1992). For flow calculation type 2 =
AGA-3 (1985) for SCADAPack 5203/4, SCADAPack LP, SCADAPack
100 and SCADAPack 4202 flow computers up to version 6.41.
New Features in Realflo 6.41
Realflo version 6.41 includes the following new features and enhancements:
Support for Application Identifier
SCADAPack and SCADAPack 32 controllers are compatible with older firmware that does not provide the application identifier feature.
Flow computers enable the register mapping feature. This is not compatible with older firmware for SCADAPack 32, SCADAPack 300, SolarPack 410, and SCADAPack 4203 controllers, or ISaGRAF applications that used these registers, for any controllers. Logic applications need to disable the mapping if they wish to use the registers for other uses.
SCADAPack 300, SCADAPack 4203, and SolarPack 410 flow computers with the application identifier feature will not load on firmware that does not support the feature. The firmware needs to be updated to a version supporting the application identifier.
New Features in Realflo 6.40
Realflo version 6.40 includes the following new features and enhancements:
Support for SolarPack 410 Controllers
The SolarPack 410 is a solar-powered one-run flow computer. This unit brings integrated solar power, intelligent battery charging and spreadspectrum communication to remote EFM installations.
New Features in Realflo 6.30
Realflo version 6.30 includes the following new features and enhancements:
Support for SCADAPack 4203 Controllers
The SCADAPack 4203 controllers (4203 DR and 4203 DS), is now supported in Realflo. These controllers support up to two meter runs, are physically identical to the SCADAPack 4202 DR and 4202 DS), but are based on a 32-bit ARM7-TDMI processor.
Realflo User and Reference Manual
May 19, 2011
10
Introduction
New Features in Realflo 6.21
Realflo version 6.21 includes the following enhancements:
Changes to the Wet Gas Meter Parameter
The Wet Gas Meter Factor can now be changed while the calculations are running. The calculations need to be stopped before any change in other the settings can be accepted.
For Realflo versions 6.01 To 6.20, changing Wet Gas Meter Factor requires a new contract day to be started, as the flow calculation has to be stopped.
For Realflo version 6.21 and later, changing the Wet Gas Meter Factor can be accomplished without stopping the flow calculations. This means that a new a new contract day does not have to be started when this parameter needs to be changed.
AGA-7 Uncorrected Flow Volume- Turbine Meter Factor
The AGA7 Uncorrected Flow Volume now has the option to include or exclude the turbine meter factor. The AGA-7 property page in Realflo includes an option to determine whether the M factor is included in the calculation of the Uncorrected Flow Volume. The default option is to include the M factor in the calculation. This option has no effect on corrected flow totals.
CSV and CSX Export Enhancements
The Export to File and Print commands now include the following parameters in the file and printed reports:
The date and time that the report was exported or printed.
The date and time of the last flow calculation update.
The orifice tap, flange or pipe location, configuration.
The lower range limit and upper range limit of the transmitter‟s sensor for each meter run input that uses a transmitter.
The calculated, or entered, relative density.
The calculated, or entered, heating value.
The wet gas meter factor.
New Features in Realflo 6.20
Realflo version 6.20 includes the following new features and enhancements:
Support for
SCADAPack 350
The SCADAPack 350 controller is now supported in Realflo. The
SCADAPack 350 controller supports up to four meter runs. The Flow
Computer Information and Replace Flow Computer dialogs are displayed differently when the SCADAPack 350 controller is used. These dialogs display the multiple C/C++ programs that can execute in the SCADAPack
350 controller.
Flow Accumulator Time Stamps
The time stamp of the flow accumulators is updated whenever the flow computer run is running, regardless of whether there is flow or not. This is
Realflo User and Reference Manual
May 19, 2011
11
Introduction so that under typical conditions that the time stamp of hourly and daily records will correspond to the end of the hour, the exception being configuration events that produce breaks in the records during the hours.
New Features in Realflo 6.00
Realflo version 6.0 included the following features and enhancements:
4000 Transmitter Display Enhancements
Custom items may now be added to the MVT display. Registers can be in the range 1 to 9999, 10001 to 19999, 30001 to 39999 and 40001 to 49999.
A seven character description string is displayed below the value for the first half of the display period. A seven character units string is displayed below the value for the second half of the display period. This string may be scrolled to allow a scaling exponent to be displayed.
Absolute / Gage Configuration of 4000 Transmitters
Realflo now provides configuration of either absolute or gage mode for the
SCADAPack transmitters. When gage mode is selected an entry is provided for the local atmospheric pressure.
AGA-8 Composition Editing for Hexane Plus Added
Realflo now allows the entering of a single value for hexane and higher components (n-Hexane, n-Heptane, n-Octane, n-Nonane, and n-Decane).
For hexane and higher components, Realflo allows entering of the percent of the combined value used for each component.
AGA-8 Heating Value and Specific Gravity
Heating value and specific gravity may be calculated, as is currently done, or they may be entered as configuration parameters.
CFX Export Enhancements
Realflo provides an option to export one record per hour, rather than one record per period measured by the by the flow computer. When this option is selected Realflo merges records produced by the flow computer within a single hour into a single record.
Realflo now provides an option to export data in a time leads data format.
The time stamp on exported records is the time at the start of the hour containing the records.
Realflo now provides an option to set the live value flags for gas analysis, energy, or gravity. The CFX file snapshot section contains four flags describing if certain values are live or static. Realflo does not provide a way to obtain live values for gas analysis, energy, or gravity and these flags are set to false in the CFX export. A user may write an application program to obtain the live values for gas analysis, energy, or gravity.
Flow-Cal cannot accept file names longer than 30 characters. Previous versions of Realflo suggested file names that were longer than 30 characters in some cases. Realflo provides a number of options for the file name. A display window shows an example of the selected file name.
Previous versions of Realflo would load the Run # (1, 2, 3, etc.) into the meter number and the Run ID was loaded into the meter name in the CFX
Realflo User and Reference Manual
May 19, 2011
12
Introduction file. Realflo now provides an option to use the Run ID for the meter number and to set the meter name to none.
CSV Export Enhancements
Realflo provides an option to export data in a time leads data format. The time stamp on exported records is the time at the start of the hour containing the records.
Maintenance Mode
Realflo Maintenance mode provides quick and easy access to commonly used functions. The Realflo application starts in Maintenance mode when first installed but can be configured to start in Expert Mode thereafter.
Flow Computer Configuration Templates
Realflo can save a configuration as a template file for new flow computers.
Files can be created from a template using the New File wizard. A template is used to create a new flow computer from a pre-set configuration. The template specifies what data is pre-set and what needs to be entered when the template is used.
Improved Flow Computer Setup Dialog
The Flow Computer Setup dialog is now divided into four separate dialogs to improve setup and information functions.
The Flow Computer Setup dialog defines the flow computer type, number of flow runs, and the Flow Computer ID.
The Flow Computer Information dialog displays information about the flow computer.
The Read Configuration dialog reads configuration from the flow computer.
The Write Configuration wizard writes configuration to the flow computer.
Forcing of Flow Calculation Inputs
Realflo allows users to force an input to a flow calculation. Realflo indicates the input is forced on the Current Readings view and shows the forced value. Realflo displays live value of the input, while it is forced, on the
Current Readings view.
Improved History Download and Archive
Realflo provides a wizard to automate the history download and archive process (Maintenance Mode only). Realflo allows the user to download new history data only. Realflo reads the information needed to archive the history, including information on the Current Readings view that is required for CFX exports.
Improved Transmitter and Run Integration
In previous versions of Realflo the MVT and Flow Run configurations were very much separate configurations. Some configuration was required to be entered in both the MVT configuration and the Run configuration.
In this version of Realflo when a MVT transmitter is selected in the Run configuration Input Type selection for Temperature, Static Pressure or
Differential Pressure the zero and full-scale entries are disabled and the
Realflo User and Reference Manual
May 19, 2011
13
Introduction values are forced to the MVT Lower Operating Limit and Upper Operating
Limit respectively.
New File Wizards
New File wizards have been added to improve the creation of new files.
Improved Plate Change Wizard Information
The plate change wizard is enhanced to work with single and dual chamber orifices and to allow Back and Cancel operations to improve usability.
Improved Process I/O Destination Restrictions
Realflo displays an error if a destination register for Process I/O is reserved.
Registers depend on the configured Flow Computer Type. SCADAPack LP,
SCADAPack 100: 1024K, and SCADAPack 4200 or 4300 transmitter types assume two flow runs. Other 16-bit SCADAPack types assume three flow runs. 32-bit SCADAPack types assume ten flow runs.
Improved Run ID length
Realflo allows a Run ID of up to 32 characters.
Improved Time Weighted Averages of DP, P, and T
Realflo provides time-weighted averages of the static pressure and temperature during low DP (or low pulse) cutoff. The differential pressure (or meter pulses) is considered zero since it is the typical reason for halting flow accumulation.
The hourly history Temperature column displays the average temperature in the period. When the Flow Time is zero, the value will be the average temperature for the entire hour or hour fragment.
The hourly history Pressure column displays the average pressure in the period. When the Flow Time is zero, the value will be the average pressure for the entire hour or hour fragment.
Calibration Reports
Realflo creates, stores, and can print a calibration report for each calibration session performed.
Current and Previous month totals
Realflo displays the accumulated flow volume and flow time for the current month and the previous month. Data is copied from the current month (This
Month) to the previous month (Last Month) at the end of the contract day at the end of the month, as measured by the real time clock.
AGA-7 uncorrected flow
Realflo displays the accumulated uncorrected flow volume for the current month and the previous month. Data is copied from the current month (This
Month) to the previous month (Last Month) at the end of the contract day at the end of the month, as measured by the real time clock.
Analog Measurement Rate
Analog input measurements are taken every second regardless the number of flow runs. For SCADAPack flow computers the flow calculations are done
Realflo User and Reference Manual
May 19, 2011
14
Introduction every second for one run and every two seconds for two runs. The average value of the analog input measurement is used for each calculation.
History Restore
When a flow computer is replaced Realflo allows the user to read the flow history and logs from the existing flow computer and then initialize the new flow computer with the flow history and data.
New I/O Module Support
5506 Analog Input module.
5505 RTD Input module.
5606 I/O module.
Wet Gas Meter Factor (Realflo 6.10 and later)
The Wet Gas Meter Factor is used when there is water in the flow. Realflo now allows an entry in the Contract Configuration for a Wet Gas Meter. This factor is used when there is water in the flow. Volume, mass and energy values will be adjusted according to this factor. For example the Wet Gas
Meter Factor would be set to 0.95 when the water content is 0.05 (5 %).
Realflo Firmware Compatibility
The following table shows the relationship between Realflo and flow computer and the required version of firmware needed for the target controller.
In the following table:
SCADAPack includes SCADAPack, SCADAPack Plus, SCADAPack Light,
SCADAPack LP, Micro16 and SCADAPack 4200 controllers.
SCADAPack 32 includes SCADAPack 32 and SCADAPack 32P controllers.
If you have any questions concerning the compatibility of Realflo applications and firmware versions, contact Control Microsystems Technical
Support at [email protected]
or phone 888-226-
6876.
Realflo and
Flow Computer
Version 2.02
Version 2.03
Version 2.05
Version 3.00
Version 3.10
Version 4.00
Version 4.10
Version 4.50
Version 4.51
Controller Firmware
SCADAPack firmware 1.40 and 1.42
SCADAPack firmware 1.43
SCADAPack firmware 1.45
SCADAPack firmware 1.45
SCADAPack firmware 1.47
SCADAPack firmware 1.47 and 1.49
SCADAPack firmware 1.50, 1.52 and 1.53
SCADAPack 32 firmware 1.10, 1.11, 1.13, 1.14 and
1.15
SCADAPack firmware 1.55
SCADAPack 32 firmware 1.16
SCADAPack firmware 1.55 and 1.56
SCADAPack 32 firmware 1.16, 1.17 and 1.18
Realflo User and Reference Manual
May 19, 2011
15
Introduction
Realflo and
Flow Computer
Version 5.01
Controller Firmware
Version 5.02
Version 5.10
Version 5.11
Version 5.12
Version 5.14
Version 5.14a
Version 5.15
Version 5.16
Version 5.20
Version 5.21
Version 5.22
Version 5.23
Version 5.24
Version 5.26
Version 5.27
Version 6.00
Version 6.01
Version 6.10
Version 6.11
Version 6.20
Version 6.21
Version 6.22
SCADAPack firmware 1.57 and 1.58
SCADAPack 32 firmware 1.19 and 1.20
SCADAPack firmware 1.58
SCADAPack 32 firmware 1.20
SCADAPack firmware 1.59
SCADAPack 32 firmware 1.21
SCADAPack firmware 1.59 and 1.60
SCADAPack 32 firmware 1.21 and 1.22
SCADAPack firmware 1.61 and 1.62
SCADAPack 32 firmware 1.23
SCADAPack firmware 1.62
SCADAPack 32 firmware 1.23
SCADAPack firmware 1.63
SCADAPack 32 firmware 1.23
SCADAPack firmware 1.63 and 1.64
SCADAPack 32 firmware 1.23
SCADAPack firmware 1.64
SCADAPack 32 firmware 1.23
SCADAPack firmware 1.64
SCADAPack 32 firmware 1.24
SCADAPack firmware 1.64
SCADAPack 32 firmware 1.24 and 1.25
SCADAPack firmware 1.64 and 1.65
SCADAPack 32 firmware 1.25
SCADAPack firmware 1.65 and 1.80
SCADAPack 32 firmware 1.31, 1.32 and 1.40
SCADAPack firmware 1.80, 1.81, 1.82 and 2.00
SCADAPack 32 firmware 1.40
SCADAPack firmware 2.00 and 2.10
SCADAPack 32 firmware 1.40
SCADAPack firmware 2.11, 2.12, 2.20 and 2.21
SCADAPack 32 firmware 1.40, 1.42, 1.50 and 1.51
SCADAPack firmware 2.21 and 2.30
SCADAPack 32 firmware 1.51 and 1.60
SCADAPack firmware 2.30
SCADAPack 32 firmware 1.60
SCADAPack firmware 2.30
SCADAPack 32 firmware 1.70 and 1.75
SCADAPack firmware 2.31
SCADAPack 32 firmware 1.79
SCADAPack firmware 2.31
SCADAPack 32 firmware 1.79
SCADAPack 350/SCADAPack 4203 firmware 1.10
SCADAPack firmware 2.31
SCADAPack 32 firmware 1.79
SCADAPack 350/SCADAPack 4203 firmware 1.10
SCADAPack firmware 2.31
SCADAPack 32 firmware 1.79
Realflo User and Reference Manual
May 19, 2011
16
Introduction
Realflo and
Flow Computer
Controller Firmware
Version 6.30
Version 6.31
Version 6.32
Version 6.33
Version 6.34
Version 6.35
Version 6.40
Version 6.41
Version 6.42
Version 6.50
Version 6.70
Version 6.71
Version 6.72
SCADAPack 350/SCADAPack 4203 firmware 1.10
SCADAPack firmware 2.31
SCADAPack 32 firmware 1.79
SCADAPack 350/SCADAPack 4203 firmware 1.20
SCADAPack firmware 2.41
SCADAPack 32 firmware 1.80
SCADAPack 350/SCADAPack 4203 firmware 1.20
SCADAPack firmware 2.41
SCADAPack 32 firmware 1.80
SCADAPack 350/SCADAPack 4203 firmware 1.21
SCADAPack firmware 2.41
SCADAPack 32 firmware 1.80
SCADAPack 350/SCADAPack 4203 firmware 1.21
SCADAPack firmware 2.41
SCADAPack 32 firmware 1.80
SCADAPack 350/SCADAPack 4203 firmware 1.21
SCADAPack firmware 2.41
SCADAPack 32 firmware 1.80
SCADAPack 350/SCADAPack 4203 firmware 1.21
SCADAPack firmware 2.43
SCADAPack 32 firmware 1.90
SCADAPack 350/SCADAPack 4203 firmware 1.24
SolarPack 410 firmware 1.30
SCADAPack firmware 2.44
SCADAPack 32 firmware 1.92
SCADAPack 350/SCADAPack 4203 firmware 1.25
SolarPack 410 firmware 1.32
SCADAPack firmware 2.44
SCADAPack 32 firmware 1.92
SCADAPack 350/SCADAPack 4203 firmware 1.25
SolarPack 410 firmware 1.32
SCADAPack firmware 2.44
SCADAPack 32 firmware 1.92
SCADAPack 350/SCADAPack 4203 firmware 1.40
SCADAPack 33x firmware 1.40
SolarPack 410 firmware 1.40
SCADAPack firmware 2.44
SCADAPack 32 firmware 2.12
SCADAPack 350/SCADAPack 4203 firmware 1.45
SCADAPack 33x firmware 1.45
SolarPack 410 firmware 1.45
SCADAPack 300, SCADAPack 4203, and SolarPack
410 flow computers require firmware 1.45 or newer.
SCADAPack 32 PEMEX and GOST flow computers require firmware 2.12 or newer.
SCADAPack 32 standard flow computers require firmware 2.10 or newer.
SCADAPack firmware 2.50
Realflo User and Reference Manual
May 19, 2011
17
Introduction
Realflo and
Flow Computer
Controller Firmware
Version 6.73
Version 6.74
SCADAPack 32 firmware 2.10
SCADAPack 314, 33x, and 350 firmware 1.47
SCADAPack 4203 firmware 1.47
SolarPack 410 firmware 1.47
SCADAPack firmware 2.50
SCADAPack 32 firmware 2.10
SCADAPack 314, 33x, and 350 firmware 1.47
SCADAPack 4203 firmware 1.47
SolarPack 410 firmware 1.47
SCADAPack firmware 2.50
SCADAPack 32 firmware 2.16
SCADAPack 314, 33x, and 350 firmware 1.51
SCADAPack 4203 firmware 1.51
SolarPack 410 firmware 1.51
Realflo User and Reference Manual
May 19, 2011
18
Realflo Maintenance Mode Reference
Realflo Maintenance Mode Reference
Realflo opens in Maintenance Mode when you start it on your computer.
Maintenance Mode provides an interface into the commonly used functions associated with the maintenance of a flow computer installation. The Realflo
Maintenance Mode main screen is shown below.
The main screen displays a number of buttons grouped into sections. The buttons in each section let you to perform typical flow computer maintenance actions such as:
Selecting or Creating a Flow Computer file.
Viewing data and reading logs and history from the flow computer.
Performing calibration and orifice plate change operations for the flow computer.
Viewing and modifying the configuration of the flow computer.
Tip: Each button on the screen has a tool tip. Moving your mouse pointer over the button will cause the tool tip to be displayed.
The maintenance actions are explained in the following sections:
Selected Flow Computer on page 21.
View Current Readings on page 121.
Read Logs and Flow History on page 127.
Change Orifice Plate on page 175.
Realflo User and Reference Manual
May 19, 2011
19
Realflo Maintenance Mode Reference
View and Change Configuration on page 194.
Switch to Expert Mode on page 201.
Realflo User Manual on page 201.
Realflo User and Reference Manual
May 19, 2011
20
Realflo Maintenance Mode Reference
Selected Flow Computer
The topmost section of the Maintenance Mode screen is the Selected Flow
Computer section. The section contains a Select Flow Computer button and display windows that will display the Flow Computer ID and the File
Name of the flow computer you select for use.
When you start Realflo, the Flow Computer ID and File Name display windows are blank as shown below.
Click the Select Flow Computer button to start the Select Flow Computer wizard. The wizard leads you through the steps to open an existing flow computer file, create new flow computer file, or to read the flow computer file from an existing flow computer.
Each step of in the wizard opens a dialog so that you can enter the parameters for that step. Each dialog contains four buttons to allow navigation through the wizard.
<Back returns to the previous step in the wizard. This button is disabled on the first step of a wizard.
Next> moves to the next step in the wizard. This button is hidden on the last step of a wizard.
Cancel cancels the operation and closes the wizard. Steps performed thus far in the wizard are cancelled. Pressing the ESC key performs the same action as Cancel.
Help opens the user manual.
Finish is displayed on the final step of a wizard in place of the Next button. It finishes the operation. This button is hidden on other steps.
Realflo User and Reference Manual
May 19, 2011
21
Realflo Maintenance Mode Reference
Select Flow Computer Wizard
The Select Flow Computer wizard starts with the following dialog.
The wizard offers two selections for selecting a file: (1) Open an existing
file or (2) Create a new file.
Select the Open an existing file option if you have a copy of the flow computer file on your PC or available on a CD or other media. See the
section below.
Select the Create a new file option if you want to read the flow computer configuration from a flow computer, create a new configuration file using a template or create a new configuration file
When you have selected an option, click Next> to move to the next step.
The wizard advances through the necessary steps depending on the option you select. The following sections describe each option.
Open an Existing File
The default option for selecting a flow computer is to Open an existing file.
When you click Next> the Open File dialog opens. You can select a local flow computer file to open using the using the Browse button or to open a recently used file from the Recently Used Files list.
Realflo User and Reference Manual
May 19, 2011
22
Realflo Maintenance Mode Reference
The Browse button opens the File Open dialog as shown below.
Use the Look in: dropdown selector to locate the flow computer file you wish to use.
When the file has been located, click on the file to highlight it. The file name will be displayed in the File name: window.
Click the Open button to close the dialog and return to the Open File dialog.
Click the Finish button to close the Open File dialog and return to the
Maintenance Mode main screen.
The Recently Used Files list contains the last 10 flow computer files that have been used.
To open one of these files:
Realflo User and Reference Manual
May 19, 2011
23
Realflo Maintenance Mode Reference
Click on the file name to highlight it. The complete file name and path are displayed in the Select File to Open edit box.
Click Finish to close the dialog and return to the Maintenance Mode main screen.
The Flow Computer ID and File Name displays now contain flow computer information as shown in the example below.
Create a New File Wizard
To create a new flow computer file, select the Create a new file radio button, click Next>. The Create New File wizard opens. The Create New File dialog offers you three choices to create a new flow computer file:
Read the configuration from the target flow computer (default selection).
Create a new configuration from a template file.
Create a new configuration step-by-step.
The Create New File dialog is shown below.
The How do you want to create a new file? selections determine how the new file is created.
Select Read Configuration from the Flow Computer to read the configuration of an existing flow computer. Realflo will connect to the flow computer, read configuration parameters, and save the file.
Follow the wizard steps described in the
section when you select this option.
Realflo User and Reference Manual
May 19, 2011
24
Realflo Maintenance Mode Reference
Create Configuration From a Template File
configuration file based on a template. A template contains pre-defined settings requiring you to fill in configuration data specific this flow computer.
Select the template file from the dropdown list. The last ten recently used templates are shown. The recently used template is selected by default.
The selection edit box is blank if no recently used templates are available.
Click Browse to choose another template file. A File Open dialog appears which allows you to select any template file.
Template files are created in the Expert Mode. When templates are created some flow computer configuration parameters are preset and are not displayed in the Create Configuration from Template wizard steps.
Follow the wizard steps described in the
Create Configuration Stepby-Step
section to configure the flow computer step by step.
Read Configuration From the Flow Computer
The Read Configuration from Flow Computer option enables you to connect to the flow computer and read the existing configuration from the flow computer. A communication link needs to exist between Realflo and the flow computer to use this option. The wizard prompts you for default communication settings or allows you to select new communication settings.
When Realflo reads configuration from a 32-bit flow computer, Realflo reads the flowing fields for each flow run:
Use Value on Sensor Fail (see section
Differential Pressure default value (see section
Static Pressure default value (see section
Temperature default value (see section
For flow computers not supporting this feature, Realflo reads the following fields for each flow run:
Use Value on Sensor Fail = Last Known Good Value (see section
Differential Pressure default value = 0 (see section
Static Pressure default value = 0 (see section
Temperature default value = 0 (see section
When the Read Configuration from Flow Computer option is selected, the
Connect to Flow Computer wizard leads you through the necessary steps.
The sequence of steps to read the configuration from a flow computer is:
Connect to Flow Computer wizard step.
Read Configuration from Flow Computer wizard step.
Save Configuration wizard step.
Open File
The Open File step lets you select the step
Realflo User and Reference Manual
May 19, 2011
25
Realflo Maintenance Mode Reference
Connect to Flow Computer
The Connect to Flow Computer step defines the communication settings for the connection between the PC running the Realflo application and the target flow computer.
The How do you want to communicate with the flow computer? prompt provides two selections.
The Use the Current Settings option sets the default communication settings for Realflo. These settings are for the PC that is running Realflo.
(The communication settings for the PC running Realflo and the communication settings in the flow computer need to match).
The default communication settings are:
COM 1 (serial port on the PC)
9600 baud, no parity
8 Data bits
1 Stop bit
The default Modbus address Realflo will connect to is station 1.
Use this selection if the serial port on your PC is COM 1 and the serial port settings for the serial port on the flow computer are set for default (9600,
8,n,1 and Modbus address 1).
Click the Next> button to begin communication with the flow computer and move to the next step in the wizard.
The Choose/View Communication Setup option opens the PC
Communication Settings dialog as shown below. This allows you to view the default settings and to change the PC communication setting for the type of connection you are using to communicate with the flow computer.
Realflo User and Reference Manual
May 19, 2011
26
Realflo Maintenance Mode Reference
See the section Communication Menu >>
in the Realflo Expert Mode Reference section of this manual for complete details on the parameter settings in this dialog.
You need to know the communication settings for the connection to the flow computer to use this step.
Once the communication settings have been selected click the OK> button to close the dialog and begin communication with the flow computer.
Read Configuration from the Flow Computer
The Read Configuration from Flow Computer step starts with the Create
New File window as shown below.
Click the Next> button to begin reading the flow computer configuration form the flow computer.
The Communication progress displays the status of the reading of the configuration.
Realflo User and Reference Manual
May 19, 2011
27
Realflo Maintenance Mode Reference
Save Configuration File
Once the configuration has been read from the flow computer the Save File dialog is opened to prompt for a file name to save the configuration to.
Select the Save to Realflo.tfc to save the configuration to the default
Realflo.tfc file. This file will be located in the folder Realflo was installed in.
Click the Next> button to save the configuration and move to the next step.
Select the Save to another file to save the file to a specified name and location. When this option is selected the Save As dialog is opened as shown below.
Realflo User and Reference Manual
May 19, 2011
28
Realflo Maintenance Mode Reference
Select the folder to save the file in the Save in: window. Use the dropdown selector to browse the available folders on your PC. Enter the file name in the File name: window. The file will automatically be saved with the Realflo
.tfc extension.
Click the Save button to save the configuration file and close the Save
As dialog.
Click the Next> button to move to the next step.
Configuration Complete
The Configuration Complete dialog is the last step in the Read Configuration from Flow Computer wizard.
Click the Finish button to complete the wizard.
Realflo User and Reference Manual
May 19, 2011
29
Realflo Maintenance Mode Reference
Create Configuration From a Template File
When you choose to configure the flow computer using a template file, the
Create New File wizard prompts you through the steps needed.
Select File >> New from the Realflo command menu.
The Create New File dialog is displayed and the wizard will lead you through the steps to create a congiuration file from a temple.
Create New File Dialog
(1) Select the Create Configuration from a Template File radio button.
(2) Do one of the following: a. Select the template file from the dropdown list. The last ten recently used templates are shown. The recently used template is selected by default. b. Click Browse to choose another template file. A File Open dialog appears which allows you to select any template file.
(3) Click Next > to continue.
Template files are created in the Expert Mode. When templates are created some flow computer configuration parameters are preset and are not displayed in the Create Configuration from Template wizard steps.
Follow the wizard steps described in the following sections to configure the flow computer using the selected template.
Flow Computer Information
Flow Computer Status Dialog
When configuring the flow computer using a template file, select No when the Flow Computer Status dialog opens. This lets you choose the hardware type and firmware type manually.
Hardware and Firmware Type Step
Realflo User and Reference Manual
May 19, 2011
30
Realflo Maintenance Mode Reference
The Hardware and Firmware Type Dialog opens when you select No in the
Flow Computer Status dialog.
First, select the Hardware Type from the dropdown list. The template selected determines the default value when creating the configuration using a template. The options from which you can select are:
Micro16
SCADAPack
SCADAPack Plus
SCADAPack Light
SCADAPack LP
SCADAPack 32
SCADAPack 32P
4202 DR
SCADAPack 100: 1024K
4202 DS
SCADAPack 314
SCADAPack 330
SCADAPack 334
SCADAPack 350
4203 DR
4203 DS
SolarPack 410
Realflo User and Reference Manual
May 19, 2011
31
I/O Module Type Step
Realflo Maintenance Mode Reference
Second, select the Firmware Type from the dropdown list. The template selected determines the default value (either Telepace or ISaGRAF).
If the firmware selected is Telepace, the I/O Module Type dialog opens, followed by the Flow Computer ID dialog. If the firmware type selected is
ISaGRAF, the Flow Computer ID dialog opens.
This step selects the I/O module to use for the selected Hardware type. The register assignment in the new file is set to the default register assignment for the selected hardware type.
Select the I/O module for the flow computer from the dropdown list.
Selections displayed in the list depend on the flow computer hardware type.
Hardware Type
Micro16
SCADAPack
SCADAPack Plus
SCADAPack Light
SCADAPack LP
SCADAPack 32
SCADAPack 32P
4202 DR
SCADAPack 100:
1024K
I/O Modules Available
Controller I/O only or Backwards compatible modules.
5601 I/O Module, 5604 I/O Module, or 5606 I/O
Module
5601 I/O Module, 5604 I/O Module, or 5606 I/O
Module
5602 I/O Module
SCADAPack LP I./O
5601 I/O Module
5604 10V/40mA I/O module
5604 5V/20mA I/O module
, 5604 I/O Module, or 5606 I/O Module
SCADAPack 32P I/O
4202 DR or 4202 DR Extended/4203 DR I/O
SCADAPack 100: 1024K I/O
Realflo User and Reference Manual
May 19, 2011
32
Realflo Maintenance Mode Reference
Hardware Type
4202 DS
SCADAPack 314
SCADAPack 330
SCADAPack 334
SCADAPack 350
4203 DR
4203 DS
SolarPack 410
I/O Modules Available
4202/4203 DS I/O
SCADAPack 314/33x I/O
SCADAPack 330 Controller.
SCADAPack 33x I/O
SCADAPack 350 10V/40mA I/O
SCADAPack 350 5V/20mA I/O
4202 DR Extended/4203 DR I/O
4202/4203 DS I/O
Flow Computer ID Step
This step sets the Flow Computer ID.
Type the Flow Computer ID string in the edit box. This unique ID stops accidental mixing of data from different flow computers. The maximum length of the Flow Computer ID is eight characters. Any characters are valid.
You can leave the Flow Computer ID edit box blank.
Number of Flow Runs Step
This step selects the number of flow runs in the flow computer. The wizard will step through the configuration of the first run and then each subsequent run if more than one run is selected.
Realflo User and Reference Manual
May 19, 2011
33
Realflo Maintenance Mode Reference
Flow Run ID Step
Select the number of flow runs with the dropdown list. Valid values depend on the hardware type and the number of flow runs enabled for the flow computer. The template determines the default value when using a template.
For Micro16, SCADAPack, SCADAPack Light and SCADAPack Plus
Flow Computers, the maximum number of meter runs is three.
The selection of three meter runs is available for older flow computers that could be enabled for three meter runs.
For SCADAPack LP and SCADAPack (4202 and 4203) Flow
Computers, the maximum number of meter runs is two.
For SCADAPack 100: 1024K and SolarPack 410 Flow Computers, the maximum number of meter runs is one.
For SCADAPack 314/330/334 and SCADAPack 350 Flow Computers the maximum number of meter runs is four.
For SCADAPack 32 and SCADAPack 32P Flow computers the maximum number of runs you can select is ten.
This step sets the Flow Run ID for the meter run. This is the first step of a flow run configuration. The wizard will step you through the flow run configuration steps for the first run and then each subsequent run if you select more than one run.
Realflo User and Reference Manual
May 19, 2011
34
Realflo Maintenance Mode Reference
Copy Run Step
The Flow Run ID helps to identify the flow run. Type a string up to 32 characters long. Any characters are valid. You can leave the Flow Run ID edit box blank.
Older flow computers allow a string up to 16 characters. See the TeleBUS
section.
This step controls how multiple runs are configured once the first run has been configured.
The Step by Step Configuration radio button selects that the run will be configured step by step as was the previous run. Parameters for each step are configured one at a time.
Realflo User and Reference Manual
May 19, 2011
35
Realflo Maintenance Mode Reference
The Copy configuration from radio button selects that the run will be configured the same as the run selected in the drop down window.
Flow Calculation Configuration
Flow and Compressibility Calculations Step
This step selects the flow and compressibility calculations for the first run.
Flow Calculation selects the type of flow calculation for the meter run. Valid values are:
AGA-3 (1985 version)
AGA-3 (1992 version)
AGA-7
AGA-11 (not available for 16-bit controllers)
V-cone calculations
The template selected determines the default value.
Compressibility Calculation selects the type of compressibility calculation for the meter run. Valid compressibility calculation values are:
AGA-8 Detailed
NX-19 (Not supported for PEMEX flow computers)
AGA-8 Detailed is the recommended calculation for new systems as it has superior performance compared to NX-19. NX-19 is provided for legacy systems. The template selected determines the default value.
Flow Direction Control selects the direction of flow indication, forward or reverse, for a meter run.
Forward by Value selection indicates the flow direction is forward when the value from a differential pressure (DP) sensor is positive or the mass flow rate value from a Coriolis meter is positive.
Realflo User and Reference Manual
May 19, 2011
36
Flow Run Units Step
Realflo Maintenance Mode Reference
Reverse by Value selection indicates the flow direction is reverse when the value from a differential pressure (DP) sensor is negative or the mass flow rate value from a Coriolis meter is negative.
Forward by Status selection indicates the flow direction is forward when the Flow Direction Register has a value of 0 (OFF).
Reverse by Status selection indicates the flow direction is reverse when the Flow Direction Register has a value of 1 (ON).
Flow Direction Register specifies which register indicates the forward or reverse flow direction status. Any valid register for the flow computer controller can be used for this setting. The default register is 1. This edit control is disabled if Flow Direction Control selection is Value. This control is hidden in GOST mode flow computers.
This step lets you select the units that are used for input measurements and contracts.
Input Units selects the units of measurement of input values for the meter run. Inputs may be measured in different units than the calculated results.
This allows you to use units that are convenient to you for measuring inputs.
A dropdown list allows the selection of the following unit types. The template selected determines the default value.
US1
US2
US3
IP
Metric1
Metric2
Metric3
Realflo User and Reference Manual
May 19, 2011
37
Realflo Maintenance Mode Reference
SI
US4
US5
US6
US7
US8
PEMEX
The reference list for the Input Units displays the parameters and units for these parameters:
DP (Differential pressure)
SP (Static pressure)
Temperature
Pipe and Orifice Diameter
Viscosity
Altitude
Heating Value
Contract Units selects the units of measurement of contract values. These units are used for the calculated results. A dropdown list allows the selection of the following unit types. The template selected determines the default value.
US1
US2
US3
IP
Metric1
Metric2
Metric3
SI
US4
US5
US6
US7
US8
PEMEX
The reference list for the Contract Units displays the parameters and units for these parameters when used for the contract. The parameters displayed depend on the contract units selected. The parameters are:
Volume
Realflo User and Reference Manual
May 19, 2011
38
Realflo Maintenance Mode Reference
Flow Run Inputs Step
This step lets you configure the flow run inputs. One of two configuration dialogs is presented based on the input type you configure.
Sensor Inputs
Analog Inputs
Sensor Inputs
Volume Rate
Energy
Energy Rate
Base Pressure
Base Temperature
Mass
Mass Flow Rate
Density
Flow Extension
Heating Value
Select Internal Sensor (4202 DR/DS or 4203DR/DS or SolarPack 410) to use a SCADAPack internal transmitter as the input device. The transmitter is the input for pressure, differential pressure, and temperature. This is the only valid selection for run 1 of a SCADAPack flow computer. Other options are disabled.
Realflo User and Reference Manual
May 19, 2011
39
Analog Inputs
Realflo Maintenance Mode Reference
Select Sensor to use a multivariable transmitter as the input device. The transmitter is the input for pressure, differential pressure, and temperature.
This is the default selection, except for run 1 of a SCADAPack controller.
The Where is sensor connected to the Flow Computer parameter enables the ability to select the serial or LAN port where the sensor is connected to the flow computer. Selections vary according to the flowcomputer type. Valid selections can include:
com1
com2
com3
com4
LAN
The What is the sensor model parameter selects the multivariable transmitter (MVT) type. The selections available are:
3095FB
4101
4102
4202 DR
4202 DS
4203 DR
4203 DS
The What value should be used if the sensor fails parameter selects the specified value in this field as the live input value when communicating with a sensor. The dropdown list lets you select:
Use Last Known Good Value
Use Default Value
When you open a file using an older file format, Realflo sets the default value of the Values on Sensor Fail field to Use Last Known Good.
When the status to a sensor changes and you select the Use Default Value option, this is added to the Event Log.
For flow computers 6.70 and later, when communication to a sensor fails and the configuration option “Use Last Known Good Value” is set to
“Use Default Value,” the flow computer needs to use the specified default value in the configuration in place of a live input value.
When communication to a sensor is restored and the configuration option for the Value on Sensor Fail field is set to use the default value, the flow computer uses the input value from the sensor as the live input value.
For flow computers prior to 6.70, the value on sensor fail is ``Use Last
Known Good Value.”
Realflo User and Reference Manual
May 19, 2011
40
Realflo Maintenance Mode Reference
Select Analog Inputs to use analog inputs to measure pressure, differential pressure, and temperature.
Valid values are:
Telepace Integer
ISaGRAF Integer
Float
Raw Float
The template selected determines the default value displayed.
For AGA-7 calculations, the value is fixed and set automatically. The value is Telepace Long if Telepace firmware is running, otherwise it is an
ISaGRAF integer if ISaGRAF firmware is running.
The next step is Differential Pressure Settings if AGA-3 or V-Cone is configured.
The next step is Turbine Settings if AGA-7 is configured.
Differential Pressure Limits Step
This step lets you configure the differential pressure input limits. One of two configuration dialogs is presented based on the input type you configure.
Sensor Inputs
Analog Inputs
Sensor Inputs
Input Type is a read-only field that identifies the sensor number for which you are setting the parameters using this dialog.
Units are the differential pressure units. Values read from the transmitter are in these units. If the transmitter has a local display, the transmitter uses these units. Valid values depend on the MVT type:
Realflo User and Reference Manual
May 19, 2011
41
Analog Inputs
Realflo Maintenance Mode Reference
For SCADAPack transmtters, valid units are: inches H2O at 68°F,
Pascal (Pa) and kiloPascal (kPa). The default is inches H2O at 68°F.
For the 3095 MVT valid units are: inches H2O at 60°F, Pascal (Pa), kiloPascal (kPa) and inches H2O at 68°F. The default is inches H2O at
60°F.
Damping is the response time of the transmitter. It is used to smooth the process variable reading when there are rapid input variations.
For SCADAPack transmitters the valid values are 0.0 (damping off), 0.5,
1.0, 2.0, 4.0, 8.0, 16.0, and 32.0 seconds. The template selected determines the default value displayed.
For the 3095 MVT the valid values are 0.108, 0.216, 0.432, 0.864, 1.728,
3.456, 6.912, 13.824 and 27.648. The default is 0.864.
Lower Operating Limit (LOL) is the lowest valid value from the sensor and needs to be less than the UOL. Alarms occur if the value is less than the
LOL. The template selected determines the default value displayed. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Upper Operating Limit (UOL) is the highest valid value from the sensor and needs to be greater than the LOL. Alarms occur if the value is greater than the UOL. The template selected determines the default value displayed. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Low DP Cutoff is the differential pressure where flow accumulation will stop and needs to be less than the UOL. The template selected determines the default value displayed. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Low DP Hysteresis is the amount by which the differential pressure needs to rise above the Low DP Cutoff for flow accumulation to start. It may be a value using the DP units or may be a percentage of the operating span. The operating span is the difference between the Upper Operating Limit and the
Lower Operating limit. Values depend on the transmitter. The flow accumulation level needs to be less than the Upper Operating Limit. The template selected determines the default value displayed.
Default Value is enabled if you configured the field using the Flow Run
Inputs dialog. Type the live input value to use when communicating with a sensor. The template selected determines the default value displayed.
If you configured sensor inputs, go to the
The dialog below opens when analog inputs are selected.
Realflo User and Reference Manual
May 19, 2011
42
Realflo Maintenance Mode Reference
Input Type is a read-only field that identifies the input type for which you are setting the parameters using this dialog.
Input Register is the register address where the input value is stored. Valid values are 30001 to 39999 or 40001 to 49999. The default is selected based on the run number so that inputs have unique registers.
Input at Zero Scale is value read from the sensor, in unscaled I/O units, when the sensor is at zero scale. Valid values depend on the input type. The template selected determines the default value displayed. This is enabled for Telepace integer, raw float and ISaGRAF integer types and disabled otherwise.
Input at Full Scale is value read from the sensor, in unscaled I/O units, when the sensor is at full scale. Valid values depend on the input type. The template selected determines the default value displayed. This is enabled for Telepace integer, raw float and ISaGRAF integer types and disabled otherwise.
DP at Zero Scale is the pressure that corresponds to the zero scale input, or if the input does not require scaling, the minimum pressure that can be read from the sensor. Valid values depend on the input type. The template selected determines the default value displayed.
DP at Full Scale is the pressure that corresponds to the full-scale input, or if the input does not require scaling, the maximum pressure that can be read from the sensor. Valid values depend on the input type. The template selected determines the default value displayed.
Low DP Cutoff is the differential pressure where flow accumulation will stop and needs to be less than the UOL. The template selected determines the default value displayed. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Low DP Hysteresis is the amount by which the differential pressure needs to rise above the Low DP Cutoff for flow accumulation to start. It may be a value using the DP units or may be a percentage of the operating span. The
Realflo User and Reference Manual
May 19, 2011
43
Realflo Maintenance Mode Reference operating span is the difference between the Upper Operating Limit and the
Lower Operating limit. Values depend on the transmitter. The flow accumulation level needs to be less than the Upper Operating Limit. The template selected determines the default value displayed.
Turbine Limits Step
This step configures the turbine input for AGA-7 calculations.
Input Register is the register address where the input value is stored. Valid values are 30001 to 39999 or 40001 to 49999. The default is selected based on the run number so that inputs have unique registers.
Low Flow Pulse Limit is the number of pulses below which a low flow alarm will occur. The template selected determines the default value displayed.
Low Flow Detect Time is the length of time the number of pulses needs to remain below the Low Flow Pulse Limit for a low flow alarm to occur. Valid values are 1 to 5 seconds. The template selected determines the default value displayed.
Static Pressure Measurement Step
This step lets you select how the static pressure is measured.
Realflo User and Reference Manual
May 19, 2011
44
Realflo Maintenance Mode Reference
The pressure tap may be upstream or downstream of the orifice plate for
AGA-3.
Select Up Stream for an upstream static pressure tap. This is the default value. The control is disabled for AGA-7 and V-Cone calculations.
Select Down Stream for a downstream static pressure tap. The control is disabled for AGA-7 and V-Cone calculations.
Static Pressure Input Limits Step
This step lets you define the limits for the static pressure input. One of two configuration dialogs is presented based on the Input Type configured for static pressure limits:
Sensor Inputs
Analog Inputs
Sensor Inputs
The dialog below is presented when sensor inputs are used.
Realflo User and Reference Manual
May 19, 2011
45
Realflo Maintenance Mode Reference
Input Type is a read-only field that identifies the sensor number for which you are setting the parameters using this dialog.
Units is the differential pressure units. Values read from the transmitter are in these units. If the transmitter has a local display it uses these units. Valid values are kiloPascal, MegaPascal, and psi (pounds per square inch). The default is psi.
Damping is the response time of the transmitter. It is used to smooth the process variable reading when there are rapid input variations.
For SCADAPack transmitters the valid values are 0.0 (damping off), 0.5,
1.0, 2.0, 4.0, 8.0, 16.0, and 32.0 seconds. The template selected determines the default value displayed.
For the 3095 MVT the valid values are 0.108, 0.216, 0.432, 0.864,
1.728, 3.456, 6.912, 13.824 and 27.648. The default is 0.864.
Lower Operating Limit (LOL) is the lowest valid value from the sensor and needs to be less than the UOL. Alarms occur if the value is less than the
LOL. The template selected determines the default value displayed. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Upper Operating Limit (UOL) is the highest valid value from the sensor and needs to be greater than the LOL. Alarms occur if the value is greater than the UOL. The template selected determines the default value displayed. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Default Value is enabled if you gage pressure using the Static Pressure
Options. Type the live input value to use when communicating with a sensor. The template selected determines the default value displayed.
The pressure sensor may measure absolute or gage pressure.
Select Absolute Pressure to measure absolute static pressure.
Select Gage Pressure to measure gage static pressure.
Realflo User and Reference Manual
May 19, 2011
46
Realflo Maintenance Mode Reference
Type the Atmospheric Pressure measured at the site. This control is disabled and set to zero if absolute pressure is selected.
The atmospheric pressure entered needs to be greater than zero. The maximum upper limits for atmospheric pressure are:
30 psi and PEMEX units for US1, US2, US3, US4, US5, US6, US7, US8,
4320
207
2.07
0.207 lbf/ft2 for IP units kPa bar
MPa for Metric1 units for Metric2 units for Metric3 units
207000 Pa for SI units
If you configured sensor inputs, see the Static Pressure Compensation
section.
Analog Inputs
The dialog below is presented when analog inputs are used.
Input Type is a read-only field that identifies the input type for which you are setting the parameters using this dialog.
Input Register is the register address where the input value is stored. Valid values are 30001 to 39999 or 40001 to 49999. The default is selected based on the run number so that inputs have unique registers.
Input at Zero Scale is value read from the sensor, in unscaled I/O units, when the sensor is at zero scale. Valid values depend on the input type. The template selected determines the default value displayed. This is enabled for Telepace integer, raw float, and ISaGRAF integer types and disabled otherwise.
Realflo User and Reference Manual
May 19, 2011
47
Realflo Maintenance Mode Reference
Input at Full Scale is value read from the sensor, in unscaled I/O units, when the sensor is at full scale. Valid values depend on the input type. The template selected determines the default value displayed. This is enabled for Telepace integer, raw float and ISaGRAF integer types and disabled otherwise.
SP at Zero Scale is the pressure that corresponds to the zero scale input, or if the input does not require scaling, the minimum pressure that can be read from the sensor. Valid values depend on the input type. The template selected determines the default value displayed.
SP at Full Scale is the pressure that corresponds to the full-scale input, or if the input does not require scaling, the maximum pressure that can be read from the sensor. Valid values depend on the input type. The template selected determines the default value displayed.
Static Pressure Compensation Step
This step selects if compensation is applied for the location where calibration was performed. If you configured sensors or analog inputs from the Static Pressure Limits dialog, this is the next step in the configuration sequence.
Select No if compensation is not required. This is the default value.
Select Yes to compensate for the altitude and latitude.
Type the Altitude of the location. Valid values are
–30000 to 30000.
The template selected determines the default value displayed. This control is disabled if No is selected.
Type the Latitude of the location. Valid values are
–90 to 90. The template selected determines the default value displayed. This control is disabled if No is selected.
Temperature Limits Step
Realflo User and Reference Manual
May 19, 2011
48
Sensor Inputs
Realflo Maintenance Mode Reference
This step defines the limits for the temperature input. One of two configuration dialogs is presented based on the Input Type configured for static pressure limits:
Sensor Inputs
Analog Inputs
The following dialog is presented when sensor (MVT) inputs are used.
Analog Inputs
Input Type is a read-only field that identifies the sensor number for which you are setting the parameters using this dialog.
Units is the differential pressure units. Values read from the transmitter are in these units. If the transmitter has a local display it uses these units. Valid values are kiloPascal, MegaPascal, and psi (pounds per square inch). The default is psi.
Lower Operating Limit (LOL) is the lowest valid value from the sensor and needs to be less than the UOL. Alarms occur if the value is less than the
LOL. The template selected determines the default value displayed. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Upper Operating Limit (UOL) is the highest valid value from the sensor and needs to be greater than the LOL. Alarms occur if the value is greater than the UOL. The template selected determines the default value displayed. Valid values depend on the transmitter; refer to the transmitter band or user manual.
The following dialog is presented when analog inputs are used.
Realflo User and Reference Manual
May 19, 2011
49
Realflo Maintenance Mode Reference
Input Type is a read-only field that identifies the input type for which you are setting the parameters using this dialog.
Input Register is the register address where the input value is stored. Valid values are 30001 to 39999 or 40001 to 49999. The default is selected based on the run number so that inputs have unique registers.
Input at Zero Scale is value read from the sensor, in unscaled I/O units, when the sensor is at zero scale. Valid values depend on the input type. The template selected determines the default value displayed. This is enabled for Telepace integer, raw float and ISaGRAF integer types and disabled otherwise.
Input at Full Scale is value read from the sensor, in unscaled I/O units, when the sensor is at full scale. Valid values depend on the input type. The template selected determines the default value displayed. This is enabled for Telepace integer, raw float and ISaGRAF integer types and disabled otherwise.
Temperature at Zero Scale is the temperature that corresponds to the zero scale input, or if the input does not require scaling, the minimum pressure that can be read from the sensor. Valid values depend on the input type.
The template selected determines the default value displayed.
Contract Settings Step
Temperature at Full Scale is the temperature that corresponds to the fullscale input, or if the input does not require scaling, the maximum pressure that can be read from the sensor. Valid values depend on the input type.
The template selected determines the default value displayed.
This step lets you set the contract settings for the run.
Realflo User and Reference Manual
May 19, 2011
50
Realflo Maintenance Mode Reference
Input Average Weighting is the weighting method of the linear inputs. This applies to the differential pressure, static pressure, and temperature. Valid
values are time-weighted or flow-weighted (see Input Averaging on page
948 for more information). The template selected determines the default
value.
Contract Hour is the hour of the day that starts a new contract day using a
24-hour clock. The contract day begins at 00 minutes and 00 seconds of the specified hour. Valid values are 0 to 23. The template selected determines the default value displayed.
Standard Base Conditions are the default Base Temperature and Base
Pressure (absolute) values.
Base Temperature is the reference temperature to which contract flow values are corrected. Valid values are
–40 to 200. The default value is given in the table below.
Base Pressure is the reference pressure to which contract flow values are corrected. The base pressure is measured as absolute pressure
(not a gauge pressure). Valid values are 0 to 32000. The default value is given in the table below.
Contract Units Standard Base
Temperature
US1
US2
US3
IP
Metric1
Metric2
Metric3
SI
60 F
60 F
60 F
60 F
15 C
15 C
15 C
288.15 K
Standard Base Pressure
14.73 psi
14.73 psi
14.73 psi
2116.2281 lbf/ft
2
101.325 kPa
1.01325 bar
0.101325 MPa
101325 Pa
Realflo User and Reference Manual
May 19, 2011
51
Realflo Maintenance Mode Reference
Contract Units Standard Base
Temperature
US4
US5
US6
US7
US8
PEMEX
60 F
60 F
60 F
60 F
60 F
60 F
Standard Base Pressure
14.73 psi
14.73 psi
14.73 psi
14.73 psi
14.73 psi
14.73 psi
Realflo for PEMEX flow computers provide a second set of base conditions.
PEMEX Base Conditions are the default Base Temperature and Base
Pressure (absolute) values when Realflo is operating in PEMEX mode.
Base Temperature is the reference temperature to which contract flow values are corrected. The default is listed in the table below for each type of contract unit.
Base Pressure is the reference pressure to which contract flow values are corrected. The base pressure is measured as absolute pressure
(not a gauge pressure). Valid values are 0 to 32000. The default values are listed in the table below for each contract unit.
Contract Units Standard Base
Temperature
US1
US2
US3
IP
Metric1
Metric2
Metric3
SI
US4
US5
US6
US7
US8
PEMEX
60 F
60 F
60 F
60 F
15 C
15 C
15 C
288.15 K
60 F
60 F
60 F
60 F
60 F
68 F
Standard Base Pressure
14.73 psi
14.73 psi
14.73 psi
2116.2281 lbf/ft
2
101.325 kPa
1.01325 bar
0.101325 MPa
101325 Pa
14.73 psi
14.73 psi
14.73 psi
14.73 psi
14.73 psi
14.73 psi
AGA-3 Settings Step
This step sets the AGA-3 calculation parameters.
Realflo User and Reference Manual
May 19, 2011
52
Realflo Maintenance Mode Reference
Orifice Material is the material from which the orifice plate for the meter run is made. Valid values are Stainless Steel, Monel, and Carbon Steel. The template selected determines the default value displayed.
Pipe Material is the material from which the meter run pipe is made. Valid values are Stainless Steel, Monel, and Carbon Steel. The template selected determines the default value displayed.
Orifice Diameter is the diameter of the meter run orifice. The template selected determines the default value displayed.
Orifice reference temperature is the temperature at which the diameter of the meter run orifice was measured. The template selected determines the default value displayed.
Pipe Diameter is the measurement of the meter run pipe inside diameter.
The template selected determines the default value displayed.
Pipe reference temperature is temperature at which the meter run pipe diameter was measured. The template selected determines the default value displayed.
Beta Ratio is the ratio of orifice diameter to pipe diameter. It is displayed for information purposes only and cannot be edited.
Realflo displays messages if the beta ratio is outside recommended limits.
Isentropic Exponent is a thermodynamic property of gas used to predict the relationships between pressure, temperature, volume and energy. If you are unsure of this value, a typical value of 1.3 is commonly used. The template selected determines the default value displayed.
Viscosity is a measure of the resistance of a measured gas to flow. Valid values are 0 to 1. The template selected determines the default value displayed.
AGA-3 Deadband Settings Step
This step sets AGA-3 calculation deadbands.
Realflo User and Reference Manual
May 19, 2011
53
Realflo Maintenance Mode Reference
Temperature Deadband is the tolerated change in the flowing temperature before temperature dependent factors in the flow calculation are recalculated. Changes in the temperature smaller than the deadband will be ignored in determining the result. The template selected determines the default value displayed. The upper limit is 7°F or 4°C.
Static Pressure Deadband is the tolerated change in the static pressure before static pressure dependent factors in the flow calculation are recalculated. Changes in the static pressure smaller than the deadband will be ignored in determining the result. A static pressure deadband setting of up to four percent of the typical static pressure level should have a small effect on the accuracy of the AGA-3 calculation. The template selected determines the default value displayed. The upper limit is 800 psi or 5500 kPa or the equivalent in other units.
Differential Pressure Deadband is the tolerated change in the differential pressure before differential pressure dependent factors in the flow calculation are recalculated. Changes in the differential pressure smaller than the deadband will be ignored in determining the result. A change of N in the differential pressure input will cause a change of 0.5 N in the calculation volume at base conditions. It is recommended that the differential pressure deadband be set to zero. The template selected determines the default value displayed. The upper limit is 4.5 inWC or 1.1 kPa or the equivalent in other units.
AGA-7 Settings Step
This step lets you define the AGA-7 settings.
Realflo User and Reference Manual
May 19, 2011
54
Realflo Maintenance Mode Reference
K Factor is the number of pulses per unit volume of the turbine meter. Valid values are 0.001 to 1000000. The template selected determines the default value displayed.
M Factor is the adjustment to the number of pulses per unit volume for the turbine meter compared to an ideal meter. Valid values are 0.001 to 1000.
The template selected determines the default value displayed.
*Uncorrected Flow Volume is the measurement of the volume of gas during the contract period.
The Uncorrected Flow Volume control is available in Realflo versions 6.20 and higher.
AGA -11 Configuration Step
AGA-11 configuration defines parameters unique to the AGA-11 calculation.
The AGA-11 calculation communicates with a Coriolis meter for the calculation. The AGA-11 configuration sets the communication parameters for communication between the Coriolis meter and the flow computer.
Realflo User and Reference Manual
May 19, 2011
55
Realflo Maintenance Mode Reference
Address
This is the Modbus address of the Coriolis Meter for serial communications.
Multiple Coriolis meters using the same serial port on the flow computer need to each have a unique Modbus address. Valid Modbus addresses are between 1 and 247. The default address is 247.
Port
This is the communication port on the flow computer that will be used to communicate with the Coriolis meter. Valid port selections depend on the type of controller the flow computer running on. The default port is the first valid port available on the controller.
Timeout
This is the time the flow computer waits for a response for Modbus read commands send to the Coriolis meter. When the timeout time is exceeded the command is unsuccessful and an alarm is added to the flow computer alarm list. Valid timeout values are from 0 to 1000 ms. The default value is
50 ms.
V-Cone Settings Step
V-Cone Configuration defines parameters unique to the V-Cone calculation.
Realflo User and Reference Manual
May 19, 2011
56
Realflo Maintenance Mode Reference
Cone Material
This is the material of the V-cone. Valid values are Carbon Steel, Stainless
304, and Stainless 316. The default value is determined by the template selected.
Pipe Material
This is the material from which the meter run pipe is made. Valid values are
Carbon Steel, Stainless 304, and Stainless 316. The default value is determined by the template selected.
Adiabatic Expansion Factor
The Adiabatic Expansion Factor drop down list selects which calculation is used for the adiabatic expansion factor of the calculation.
Select Legacy Calculation to use the older calculation method. This is the default selection. Flow computers prior to version 6.71 support only this selection.
Select V-Cone to use the V-Cone specific calculation. This selection should be used with V-Cone devices.
Select Wafer-Cone to use the Wafer-Cone specific calculation. This selection should be used with Wafer-Cone devices.
This control is disabled and forced to Legacy Calculation if the controller type is not one of SCADAPack 32, SCADAPack 32P, SCADAPack
314/330/334, SCADAPack 350 SCADAPack 4203 or SolarPack 410.
When reading from a flow computer that does not support the adiabatic expansion factor configuration, the method will be set to Legacy Calculation.
When writing to a flow computer that does not support the adiabatic expansion factor method, the configuration registers will be ignored and the expansion factor will not be written.
Cone Diameter
Realflo User and Reference Manual
May 19, 2011
57
Realflo Maintenance Mode Reference
The diameter of the meter run cone used for the flow calculation. The measurement units are displayed depending on the input units selected.
The default value is 3 inches.
Cone Measurement Temperature
This is the reference temperature at which the cone diameter for the meter run was measured. The measurement units are displayed depending on the input units selected. The default value is 59 degrees F.
Pipe Inside Diameter
This is the measurement of the meter run pipe inside diameter. The measurement units are displayed depending on the input units selected.
The default value is 5 inches.
Pipe reference temperature
The temperature at which the meter run pipe diameter was measured. The measurement units are displayed depending on the input units selected.
The default value is 59 degrees.
Isentropic Exponent
In general, this is a thermodynamic property of gas used to predict the relationships between pressure, temperature, volume and energy. If you are unsure of this value a typical value of 1.3 is commonly used. The default value is 1.3.
Viscosity
This is the viscosity of the measured gas. In general, this is the resistance of a gas or semi-fluid resistance to flow. The measurement units are displayed depending on the input units selected. Valid values are 0 to 1. The default value is 0.010268 centiPoise.
Wet Gas Correction Factor
The Wet Gas Correction Factor Method drop down list selects which calculation is used for the wet gas correction factor of the calculation.
Select Legacy Method to use the older correction method. This is the default selection. Flow computers prior to version 6.73 support only this selection.
Select V-Cone or Wafer Cone to use the V-Cone and Wafer Cone specific calculation. This selection should be used with V-Cone or Wafer
Cone devices.
This control is disabled and forced to Legacy Calculation if the controller type is not one of SCADAPack 32, SCADAPack 32P, SCADAPack
314/330/334, SCADAPack 350 SCADAPack 4203 or SolarPack 410.
The V-Cone or Wafer Cone supported Beta Ratios are:
For Fr (Froude Number) < 5 supported Beta Ratio is 0.55.
For Fr (Froude Number) < 5 supported Beta Ratio is 0.75.
For Fr (Froude Number) > 5 supported Beta Ratio is 0.75.
When V-Cone or Wafer Cone is selected and if the current Beta ratio is not supported when executing verification, a message is displayed.
Realflo User and Reference Manual
May 19, 2011
58
Realflo Maintenance Mode Reference
When V-Cone or Wafer Cone is selected, configuration of the fixed wet gas factor parameter, as set in the Contract tab, is disabled.
When Legacy Method is selected, configuration of the parameters used by the V-Cone or Wafer Cone method is disabled.
Mass Flow Rate of Liquid
The Mass flow rate of liquid at flow conditions parameter is used by the V-
Cone or Wafer Cone method and can be configured when V-Cone or Wafer
Cone is selected. This information needs to be gathered using a sampling method or a tracer method. The default is 0.
Density of Liquid
The Density of liquid at flow conditions parameter is used by the V-Cone or
Wafer Cone method and can be configured when V-Cone or Wafer Cone is selected. The default is 0.
V-Cone Coefficients
This step defines the V-Cone coefficients.
Enter the V-Cone coefficient pairs from the meter-sizing report. The default list contains one pair: Re = 1000000; Cf = 0.82.
Click Add to add a coefficient pair.
In the original McCrometer V-Cone Application Sizing sheet that is included with V-Cone meters uses the terminology Cd (discharge coefficient) rather than Cf (flow coefficient). You will need to use the Re and Cd values from the V-Cone Application Sizing sheet for the Re and Cf entries. If the Re value is the same for every entry in the table only the first pair is used.
McCrometer now supplies one value of Cd in the sizing document. You
Realflo User and Reference Manual
May 19, 2011
59
Realflo Maintenance Mode Reference need to enter one Re/Cd pair only. See the McCrometer Application Sizing sheet for the Re/Cd pair for your meter.
To edit a coefficient pair in the table:
Select a row in the list.
Click Edit to open the Add/Edit Flow Coefficient dialog.
To delete a coefficient pair in the table:
Select a row in the list.
Click Delete to delete the pair form the list.
AGA-8 Options Step
This step sets AGA-8 calculation options.
Events can be logged each time an AGA-8 gas component changes.
Select Yes to log each change to the gas composition. Use this option if the gas composition changes infrequently. This is the default selection.
Select No to skip logging changes. Use this option if you are making frequent changes to the gas composition.
The Relative Density and Heating values can be calculated from the AGA-8 calculation or determined in a laboratory.
Realflo User and Reference Manual
May 19, 2011
60
Realflo Maintenance Mode Reference
Select Calculate the Values to have AGA-8 calculate the values.
Select Use Laboratory Values to used fixed values.
Relative Density sets the real relative density of the gas. Valid values are
0.07 to 1.52. The template selected determines the default value displayed.
This control is disabled if Calculate the Values is selected.
Heating Value sets the heating value of the gas. Valid values are 0 to 1800
BTU(60)/ ft
3
or the equivalent in the selected units. The template selected determines the default value displayed. This control is disabled if Calculate
the Values is selected.
AGA-8 Hexanes+ Options
This step lets you choose to enter Hexane and higher components individually or as a single combined value.
Gas composition can be measured with individual values for hexane and higher components or use a combined value.
Select Enter Each Component to use individual values for the higher components. This is the default selection.
Select Use Combined Hexanes+ with these Ratios to use a combined value. Type the ratios of the higher components.
n-Hexane defines the percentage of the Hexanes+ contributed by n-
Hexane.
n-Heptane defines the percentage of the Hexanes+ contributed by n-
Heptane.
n-Octane defines the percentage of the Hexanes+ contributed by n-
Octane.
n-Nonane defines the percentage of the Hexanes+ contributed by n-
Nonane.
Realflo User and Reference Manual
May 19, 2011
61
Realflo Maintenance Mode Reference
n-Decane defines the percentage of the Hexanes+ contributed by n-
Decane.
The Total field displays the sum of all portions. This value cannot be edited. The total of portions needs to be 100 percent.
AGA-8 Gas Composition Step
This step lets you define the AGA-8 gas composition. One of two configuration dialogs opens based on how you elected to enter Hexane and higher components.
Individual Components
The dialog below lets you enter combined Hexanes+ composition.
NX-19 Settings
Type the gas composition according to the laboratory analysis. The total of components needs to be 100 percent.
Normalize adjusts non-zero components so that the total of components is
1.0000 (or 100.00 percent). The ratio to each other for the components remains the same.
This step defines the NX-19 calculation. NX-19 is not supported for PEMEX flow computers.
Realflo User and Reference Manual
May 19, 2011
62
Realflo Maintenance Mode Reference
Specific Gravity is the specific gravity of the gas being measured. Valid values are 0.554 to 1.000. The template selected determines the default value displayed.
Carbon Dioxide is the percent of carbon dioxide in the gas being measured. This value needs to be in the range 0 to 15. The template selected determines the default value displayed.
Nitrogen is the percent of nitrogen in the gas being measured. This value needs to be in the range 0 to 15.
Heating Value is the heating value of the gas being measured. Valid values are 0 to 1800 BTU(60)/ft
3
or the equivalent in the selected units. The template selected determines the default value displayed.
Events can be logged each time the NX-19 configuration changes.
Select Yes to log each change to the configuration. Use this option if the configuration changes infrequently. This is the default selection.
Select No to skip logging changes. Use this option if you are making frequent changes to the configuration.
Sensor Configuration
The next step is Sensor Configuration if any transmitters were used in the
input configuration. Otherwise the next step is
Sensor Configuration
This step lets you select how the transmitters are to be configured.
Realflo User and Reference Manual
May 19, 2011
63
Realflo Maintenance Mode Reference
The Flow Runs are configured to use these transmitters dialog is a table that shows each of the configured flow run numbers, the Flow Run ID for each, and the transmitter that the run uses for the differential pressure (DP), static pressure (SP), and temperature sensors. If an analog input is used for the flow run, AIN will be displayed in the coresponding DP, SP, or Temp column.
The How do you want to configure sensors? option lets you select how to continue configuring the sensors. The three options are:
Connect now and configure transmitters to connect to the flow computer and configure the attached transmitters. This selection is disabled if the flow computer configuration was selected to be completed offline in the Flow Computer Status step. If you choose this
option, go to the Configure Sensors
section to continue.
Edit sensor configuration without connecting to proceed directly to the editing pages, without connecting to the flow computer. If you
Use default sensor configuration to complete the configuration without changing the sensor configuration. Sensor configuration will be
set to default values. If you choose this option, the next step is
Configure Sensors
This step lets you select to use the Realflo configuration or the sensor‟s configuration file.
Realflo User and Reference Manual
May 19, 2011
64
Realflo Maintenance Mode Reference
Sensor Search
Select Use the configuration from Realflo to use the configuration data from the Realflo file. This is the default setting.
Select
Use the transmitter’s current configuration by reading from the
transmitter to read configuration from a pre-configured transmitter.
This step searches for sensors connected to the flow computer serial ports or LAN port.
Realflo User and Reference Manual
May 19, 2011
65
Realflo Maintenance Mode Reference
Search Serial Option
Select Search Serial to search for transmitters connected to a serial port of the flow computer.
The Port parameter selects the flow computer serial port where the sensor is attached. Valid values are com1, com2, com3, and com4. The template selected determines the default value displayed.
The Timeout parameter specifies the length of time the flow computer will wait for a response from a sensor. Valid values are 100 ms to 10000 ms.
The default is 300 ms.
Select Maximum to search for a number of MVT transmitters. The search operation will stop after finding the specified number of transmitters. The valid value is from 1 to 255. The default is 1.
Select Range to search the addresses in a specified range. The range to search for is typed in the edit boxes to the right of the radio button. The value in To edit control needs to be equal or great than the value in the first edit control. The maximum search range that can be typed is for 255 transmitters. The default range is 1 to 247.
Range Search supports addresses 1 to 255 in standard Modbus mode, and 1 to 65534 in extended address mode. The address mode of the flow computer serial port needs to be set to extended in order to search for transmitters with extended addresses.
Select All to search the addresses of transmitters connected with the serial port selected in Port. Up to 255 addresses are searched.
Click Next to start the search for sensors or 4000 transmitters. A search process dialog is displayed so that the search operation can be cancelled at any time.
Search LAN Option
Select Search LAN to search for transmitters connected to a LAN port of the flow computer.
The IP Address parameter specifies the IP address of a 4000 transmitter.
Valid entries are IP addresses in the format nnn.nnn.nnn.nnn where nnn are values between 0 and 255.
The Protocol parameter selects the type of IP protocol used to query the transmitter. Valid IP protocol selections are Modbus/TCP and Modbus RTU in UDP.
The IP port (for example port 502) for the selected protocol needs to be the same in the flow computer and the 4000 transmitter.
The Timeout parameter specifies the length of time the flow computer will wait for a response from a 4000 transmitter. Valid values are 100 to 10000 milliseconds. The default is 5000 ms.
Click Next to start the search for MVT transmitters or 4000 transmitters. A search process dialog is displayed so that the search operation can be cancelled at any time.
If no transmitters were found, then a message is displayed and the search step is displayed again.
Assign Sensors
Realflo User and Reference Manual
May 19, 2011
66
Realflo Maintenance Mode Reference
This step assigns found transmitters to flow runs.
The Available Sensors window shows the transmitters that have been configured and the transmitters that were found by the search. There may be more transmitters in the list than there are runs.
The Sensor column shows the transmitter slots that have been configured.
Transmitters that were found but not assigned are listed as Not assigned.
The Status column indicates if configuration data for the transmitter exists.
Found indicates a transmitter has been configured and the search found one with the same port, address and device type.
Missing means a transmitter has been configured but the search did not find one with the same port, address and device type.
The Port column displays the serial or LAN port the flow computer is using to communicate with the transmitter.
The Address column displays the Modbus station address or IP address of the transmitter.
The Tag column displays the Tag Name assigned to the transmitter. This column may be blank if a Tag Name has not been assigned to the transmitter.
The Device type column displays type of transmitter. Valid values are
3095FB, 4101, 4102, 4202 DR, 4202 DS, 4203 DR, or 4203 DS.
The Flow Runs window shows which MVTs are assigned to the runs.
To Change the order of the sensors:
Select a sensor in Available Sensors window.
Click Move.
The Move Sensor dialog opens:
Realflo User and Reference Manual
May 19, 2011
67
Realflo Maintenance Mode Reference
In the Move Sensor dialog, use Move To selection to select the new location
Click OK.
To delete a sensor:
Select a transmitter in Available Sensors
Click Delete.
To change the address of a Sensor:
Select a transmitter in Available Sensors
Click Change Address.
The Change Address dialog opens:
Enter a new address for the transmitter in the New Address: window.
Click OK.
Click Next when the transmitters have been moved to the correct location.
Next is disabled if there are Not Assigned transmitters still in the list.
The next step is Search for More Transmitters.
Notes
The following actions may occur when moving a Sensor.
Moving one sensor to another results in the both swapping positions.
When Use the configuration from Realflo was selected, assigning a Not
assigned transmitter to a Sensor with status Missing and device type matching will result in the sensor adopting the transmitter‟s port and address and retaining the rest of the sensor configuration. The sensor, being assigned, will disappear from the list.
When Read the configuration from the transmitter was selected, assigning a Not assigned transmitter to a sensor with status Missing and device type matching will result in the sensor adopting the transmitter‟s configuration. The transmitter, being assigned, will disappear from the list.
Assigning a Not assigned transmitter to a sensor with status Missing and device type not matching will result in the sensor adopting the
Realflo User and Reference Manual
May 19, 2011
68
Realflo Maintenance Mode Reference transmitter‟s configuration. The transmitter, being assigned, will disappear from the list.
Other assignments are not permitted.
Search for More Sensors
This step displays the current sensor assignments and asks if more searches are needed.
Proposed Sensors shows the transmitters that have been configured and the transmitters that were found by the search.
Flow Runs shows which sensors are assigned to the runs.
Select Search for more transmitters to search again. The next step is
Search for Transmitters.
Select Finish searching and review configuration to use the current settings. This is the default button.
Review Transmitters
This step displays the transmitter assignments and allows editing the transmitter configuration.
Realflo User and Reference Manual
May 19, 2011
69
Realflo Maintenance Mode Reference
The Sensors window shows the transmitters that have been configured.
The Flow Runs window shows which sensors are assigned to the runs.
Click Edit to review and modify the settings for each transmitter. Edit opens the Add/Edit Sensor Settings dialog. Changes to a transmitter address will be written to the transmitter without affecting current flow computer configuration.
Once you have configured Run 1, the Flow Run ID dialog re-opens.
Flow Computer Configuration Summary
This step displays a summary of the flow computer settings.
A summary of the flow computer configuration is shown.
Realflo User and Reference Manual
May 19, 2011
70
Review Differences
Realflo Maintenance Mode Reference
The current configuration can be compared with the configuration in the target flow computer.
Select Yes to compare the configurations. The next step is Review
Differences.
Select No to not compare the configurations. The next step is Save File.
This step displays a summary of changes in the flow computer configuration. You can select to write to the flow computer or not.
A summary of the differences is the configuration is shown.
Select Yes to write the configuration to the flow computer. The configuration is written to the flow computer. The Start Executing command will be written for each flow run. The communication progress dialog shows the stages of writing.
Select No to write the configuration to the flow computer later.
Click Next to perform the selected action.
In Flow Computer versions 6.73 and older, when AGA-8 gas ratios or NX-19 gas quality values are written to the flow computer the new gas ratios are updated in the Proposed registers. The Actual registers are not updated until a new Density calculation is started with the new values. The new values are not available to SCADA host software reading the Actual registers until a until a new Density calculation is started with the new values.
In Flow Computer versions 6.74 and newer when AGA-8 gas ratios or NX-
19 gas quality values are written to the flow computer the new gas ratios are updated in the Proposed registers and in the Actual registers. This allows a
SCADA host to immediately confirm the new values were written to the flow computer. The new gas values are not used by the flow computer until a new density calculation is started.
Realflo User and Reference Manual
May 19, 2011
71
Save File
Realflo Maintenance Mode Reference
This step selects where to save the configuration file.
Finish
Select the Save to Realflo.tfc to save the configuration file to the default file location.
Select the Save to another file to either enter a file name or use the
Browse option to open the Save As dialog.
This step is displayed at the end of the wizard.
Click Finish to close the wizard.
Notes
1. Views for extra runs are closed but new ones may be opened.
2. The history and event logs contain no information.
Realflo User and Reference Manual
May 19, 2011
72
Realflo Maintenance Mode Reference
3. The configuration data for supported runs in the file is set to usable values, so when the number of runs is changed there is useful data in the configuration.
Create Configuration Step-by-Step
When you choose to configure the flow computer step-by-step, the Create
New File Wizard prompts you through the steps needed. The dialogs displayed are dependent upon the calculations you select.
Step-by-Step Configuration Sequence for a Flow Computer
The main steps in the configuration sequence to configure flow computer step-by-step are:
Use Create New File Dialog to select how to create a new file.
Use Hardware and Firmware Type Dialog to configure the hardware and firmware you are using.
Use the I/O Module Dialog to configure your I/O module (Telepace only).
Use the Flow Computer ID Dialog to assign an ID to the flow computer.
Use the Flow Runs Dialog to configure the number of flow runs
Dialog to assign an ID to the flow run.
Flow and Compressibility Calculations
compressibility calculations for the meter run.
to configure the type of inputs for the flow
run.
pressure calibration to use for the run.
Dialog to configure your sensors to
compensate for the gravitation pull of the Earth according to altitude and latitude variations.
Flow Computer Configuration Summary
configuration settings.
to save the new configuration.
Select the Create a new file? radio button from the Select File dialog to configure the flow computer step-by-step.
Realflo User and Reference Manual
May 19, 2011
73
Create New File Dialog
Realflo Maintenance Mode Reference
(1) Select the Create Configuration Step-by-Step radio button.
(2) Click Next > to continue.
Follow the wizard steps described in the following sections to configure the flow computer.
Flow Computer Status Dialog
When configuring the flow computer step-by-step, select No when the Flow
Computer Status dialog opens. This lets you choose the hardware type and
Hardware and Firmware Type Dialog
The Hardware and Firmware Type Dialog opens when you select No in the
Flow Computer Status dialog.
First, select the Hardware Type from the dropdown list. The default value is
SCADAPack 4202 DR. The options from which you can select are:
Realflo User and Reference Manual
May 19, 2011
74
Realflo Maintenance Mode Reference
Micro16
SCADAPack
SCADAPack Plus
SCADAPack Light
SCADAPack LP
SCADAPack 32
SCADAPack 32P
4202 DR
SCADAPack 100: 1024K
4202 DS
SCADAPack 314
SCADAPack 330
SCADAPack 334
SCADAPack 350
4203 DR
4203 DS
SolarPack 410
Second, select the Firmware Type from the dropdown list. The default value is Telepace. You can select ISaGRAF from the dropdown list for the firmware type.
If the firmware selected is Telepace, the I?O Module Dialog opens, followed by the Flow Computer ID dialog. If the firmware type selected is ISaGRAF, the Flow Computer ID dialog opens.
Realflo User and Reference Manual
May 19, 2011
75
Realflo Maintenance Mode Reference
I/O Module Type Dialog
This step lets you select the I/O module to use for the selected Hardware type. The register assignment in the new file is set to the default register assignment for the selected hardware type.
Select the I/O module for the flow computer from the dropdown list. The choices displayed depend on the flow computer hardware type.
Hardware Type
Micro16
SCADAPack
SCADAPack Plus
SCADAPack Light
SCADAPack LP
SCADAPack 32
SCADAPack 32P
4202 DR
SCADAPack 100:
1024K
4202 DS
SCADAPack 314
SCADAPack 330
SCADAPack 334
SCADAPack 350
I/O Modules Available
Controller I/O only or Backwards compatible modules.
5601 I/O Module, 5604 I/O Module, or 5606 I/O
Module
5601 I/O Module, 5604 I/O Module, or 5606 I/O
Module
5602 I/O Module
SCADAPack LP I./O
5601 I/O Module,
5604 I/O 10V/40mA Module
5604 I/O 5V/20mA Module
5606 I/O Module
SCADAPack 32P I/O
4202 DR or 4202 DR Extended/4203 DR I/O
SCADAPack 100: 1024K I/O
4202/4203 DS I/O
SCADAPack 314/33x I/O
SCADAPack 330 Controller.
SCADAPack 33x I/O
SCADAPack 350 10V/40mA Module
SCADAPack 350 5V/20mA Module
SCADAPack 357 Module
Realflo User and Reference Manual
May 19, 2011
76
Hardware Type
4203 DR
4203 DS
SolarPack 410
Flow Computer ID Dialog
This step sets the Flow Computer ID.
Realflo Maintenance Mode Reference
I/O Modules Available
4202 DR Extended/4203 DR I/O
4202/4203 DS I/O
N/A
Type the Flow Computer ID string in the edit box. This unique ID stops accidental mixing of data from different flow computers. The maximum length of the Flow Computer ID is eight characters. Any character is valid.
You can leave the Flow Computer ID edit box blank. The default value is blank.
Flow Runs Dialog
This step selects the number of flow runs in the flow computer. The wizard will step through the configuration of the first run and then each subsequent run if more than one run is selected.
Realflo User and Reference Manual
May 19, 2011
77
Realflo Maintenance Mode Reference
Flow Run ID
Select the number of flow runs with the dropdown list. Valid values depend on the hardware type and the number of flow runs enabled for the flow computer. The default value is one.
For Micro16, SCADAPack, SCADAPack Light and SCADAPack Plus
Flow Computers, the maximum number of meter runs is three.
The selection of three meter runs is available for older flow computers that could be enabled for three meter runs.
For SCADAPack LP and SCADAPack (4202 and 4203) Flow
Computers, the maximum number of meter runs is two.
For SCADAPack 100: 1024K and SolarPack 410 Flow Computers, the maximum number of meter runs is one.
For SCADAPack 314/330/334 and SCADAPack 350 Flow Computers the maximum number of meter runs is four.
For SCADAPack 32 and SCADAPack 32P Flow computers the maximum number of runs you can select is ten.
This step sets the Flow Run ID for the meter run. This is the first step of a flow run configuration. The wizard will step you through the configuration of the first run and then each subsequent run if you select more than one run.
Realflo User and Reference Manual
May 19, 2011
78
Realflo Maintenance Mode Reference
The Flow Run ID helps to identify the flow run. Type a string up to 32 characters long. Any character is valid. You can leave the Flow Run ID edit box blank.
Older flow computers allow a string up to 16 characters. See the TeleBUS
section.
Realflo User and Reference Manual
May 19, 2011
79
Flow Calculations
Dialog
.
Realflo Maintenance Mode Reference
Realflo User and Reference Manual
May 19, 2011
80
Realflo Maintenance Mode Reference
Flow Calculations Dialog
This step selects the flow and compressibility calculations for the first run.
Flow Calculation selects the type of flow calculation for the meter run. Valid values are:
AGA-3 (1985 version)
AGA-3 (1992 version)
AGA-7
AGA-11 (not available for 16-bit controllers)
V-cone calculations
The template selected determines the default value.
Compressibility Calculation selects the type of compressibility calculation for the meter run. Valid compressibility calculation values are:
AGA-8 Detailed
NX-19 (Not supported for PEMEX flow computers)
AGA-8 Detailed is the recommended calculation for new systems as it has superior performance compared to NX-19. NX-19 is provided for legacy systems. The template selected determines the default value.
Flow Direction Control selects the direction of flow indication, forward or reverse, for a meter run.
Forward by Value selection indicates the flow direction is forward when the value from a differential pressure (DP) sensor is positive or the mass flow rate value from a Coriolis meter is positive.
Reverse by Value selection indicates the flow direction is reverse when the value from a differential pressure (DP) sensor is negative or the mass flow rate value from a Coriolis meter is negative.
Forward by Status selection indicates the flow direction is forward when the Flow Direction Register has a value of 0 (OFF).
Realflo User and Reference Manual
May 19, 2011
81
Realflo Maintenance Mode Reference
Reverse by Status selection indicates the flow direction is reverse when the Flow Direction Register has a value of 1 (ON).
Flow Direction Register specifies which register indicates the forward or reverse flow direction status. Any valid register for the flow computer controller can be used for this setting. The default register is 1. This edit control is disabled if Flow Direction Control selection is Value. This control is hidden in GOST mode flow computers.
Flow Run Units Dialog
This step selects the units that are used for input measurements and contracts.
Input Units selects the units of measurement of input values for the meter run. Inputs may be measured in different units than the calculated results.
This allows you to use units that are convenient to you for measuring inputs.
A dropdown box allows the selection of the following unit types. US2 is the default value.
US1
US2
US3
IP
Metric1
Metric2
Metric3
SI
US4
US5
US6
Realflo User and Reference Manual
May 19, 2011
82
Realflo Maintenance Mode Reference
US7
US8
PEMEX
The reference list for the Input Units displays the parameters and units for these parameters:
DP (Differential pressure)
SP (Static pressure)
Temperature
Pipe and Orifice Diameter
Viscosity
Altitude
Heating value
Contract Units selects the units of measurement of contract values. These units are used for the calculated results. A dropdown box allows the selection of the following unit types. The default value is US2.
US1
US2
US3
IP
Metric1
Metric2
Metric3
SI
US4
US5
US6
US7
US8
PEMEX
The reference list for the Contract Units displays the parameters and units for these parameters when used for the contract. The parameters displayed depend on the contract units selected. The parameters are:
Volume
Volume Rate
Energy
Energy Rate
Base Pressure
Realflo User and Reference Manual
May 19, 2011
83
Flow Run Inputs
Realflo Maintenance Mode Reference
Base Temperature
Mass
Mass Flow Rate
Density
Flow Extension
Heating Value
This step lets you configure the flow run inputs. One of two configuration dialogs is presented based on the input type you configure.
Sensor Inputs
Select Internal Sensor (4202 DR/DS or 4203DR/DS or SolarPack
410) to use a SCADAPack internal transmitter as the input device. The transmitter is the input for pressure, differential pressure, and temperature. This is the only valid selection for run 1of a SCADAPack flow computer. Other options are disabled.
Select Sensor to use a multivariable transmitter as the input device.
The transmitter is the input for pressure, differential pressure, and temperature. This is the default selection, except for run 1 of a
SCADAPack controller.
The Where is sensor connected to the Flow Computer parameter enables the ability to select the serial or LAN port where the sensor is
Realflo User and Reference Manual
May 19, 2011
84
Analog Inputs
Realflo Maintenance Mode Reference connected to the flow computer. Selections vary according to the flowcomputer type. The default value is com1. Valid selections can include: o com1 o com2 o com3 o com4 o LAN
The What is the sensor model parameter selects the multivariable transmitter (MVT) type. The selections available are: o 3095FB o 4101 o 4102 o 4202 DR o 4202 DS o 4203 DR o 4203 DS
The What value should be used if the sensor fails parameter selects the specified value in this field as the live input value when communicating with a sensor. The dropdown list lets you select: o Use Last Known Good Value o Use Default Value
When you open a file using an older file format, Realflo sets the default value of the Values on Sensor Fail field to Use Last Known Good.
When the status to a sensor changes and you select the Use Default Value option, this is added to the Event Log.
For flow computers 6.70 and later, when communication to a sensor fails and the configuration option “Use Last Known Good Value” is set to
“Use Default Value,” the flow computer needs to use the specified default value in the configuration in place of a live input value.
When communication to a sensor is restored and the configuration option for the Value on Sensor Fail field is set to use the default value, the flow computer uses the input value from the sensor as the live input value.
For flow computers prior to 6.70, the value on sensor fail is ``Use Last
Known Good Value.”
Select Analog Inputs to use analog inputs to measure pressure, differential pressure, and temperature.
Valid values are:
Telepace Integer
ISaGRAF Integer
Realflo User and Reference Manual
May 19, 2011
85
Realflo Maintenance Mode Reference
Float
Raw Float
The default value is Telepace integer if Telepace firmware is running and
ISaGRAF integer if ISaGRAF firmware is running.
For AGA-7 calculations, the value is fixed and set automatically. The value is Telepace Long if Telepace firmware is running and ISaGRAF integer if
ISaGRAF firmware is running.
Differential Pressure Input Limits
configured.
If AGA-7 is configured, the next step is
Differential Pressure Input Limits
This step lets you configure the differential pressure input limits. One of two configuration dialogs is presented based on the input type you configure.
Sensor Inputs
Input Type is a read-only field that identifies the sensor number for which you are setting the parameters using this dialog.
Units are the differential pressure units. Values read from the transmitter are in these units. If the transmitter has a local display, the transmitter uses these units. Valid values depend on the MVT type:
For SCADAPack transmtters, valid units are: inches H2O at 68°F,
Pascal (Pa) and kiloPascal (kPa). The default is inches H2O at 68°F.
For the 3095 MVT valid units are: inches H2O at 60°F, Pascal (Pa), kiloPascal (kPa) and inches H2O at 68°F. The default is inches H2O at
60°F.
Realflo User and Reference Manual
May 19, 2011
86
Realflo Maintenance Mode Reference
Damping is the response time of the transmitter. It is used to smooth the process variable reading when there are rapid input variations.
For SCADAPack transmitters the valid values are 0.0 (damping off), 0.5,
1.0, 2.0, 4.0, 8.0, 16.0, and 32.0 seconds. The default value is 0
(damping off).
For the 3095 MVT the valid values are 0.108, 0.216, 0.432, 0.864,
1.728, 3.456, 6.912, 13.824 and 27.648. The default is 0.864.
Lower Operating Limit (LOL) is the lowest valid value from the sensor and needs to be less than the UOL. Alarms occur if the value is less than the
LOL. The default value is 0. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Upper Operating Limit (UOL) is the highest valid value from the sensor and needs to be greater than the LOL. Alarms occur if the value is greater than the UOL. The default value is the upper range limit of the transmitter.
Valid values depend on the transmitter; refer to the transmitter band or user manual.
Low DP Cutoff is the differential pressure where flow accumulation will stop and needs to be less than the UOL. The default value is 0. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Low DP Hysteresis is the amount by which the differential pressure needs to rise above the Low DP Cutoff for flow accumulation to start. It may be a value using the DP units or may be a percentage of the operating span. The operating span is the difference between the Upper Operating Limit and the
Lower Operating limit. Values depend on the transmitter. The flow accumulation level needs to be less than the Upper Operating Limit. The default value is 0.
Default Value is enabled if you configured the field using the Flow Run
Inputs dialog. Type the live input value to use when communicating with a sensor. The default value is 0.
If you configured sensor inputs, go to the
Realflo User and Reference Manual
May 19, 2011
87
Analog Inputs
Realflo Maintenance Mode Reference
Static Pressure Options
Dialog section.
The dialog below opens when analog inputs are selected.
Input Type is a read-only field that identifies the input type for which you are setting the parameters using this dialog.
Input Register is the register address where the input value is stored. Valid values are 30001 to 39999 or 40001 to 49999. The default is selected based on the run number so that inputs have unique registers.
Input at Zero Scale is value read from the sensor, in unscaled I/O units, when the sensor is at zero scale. Valid values depend on the input type. The default value is 0. This is enabled for Telepace integer, raw float and
ISaGRAF integer types and disabled otherwise.
Input at Full Scale is value read from the sensor, in unscaled I/O units, when the sensor is at full scale. Valid values depend on the input type. The default value is 32767. This is enabled for Telepace integer, raw float and
ISaGRAF integer types and disabled otherwise.
DP at Zero Scale is the pressure that corresponds to the zero scale input, or if the input does not require scaling, the minimum pressure that can be read from the sensor. Valid values depend on the input type. The default value is 0.
DP at Full Scale is the pressure that corresponds to the full-scale input, or if the input does not require scaling, the maximum pressure that can be read from the sensor. Valid values depend on the input type. The default value is
16.
Low DP Cutoff is the differential pressure where flow accumulation will stop and needs to be less than the UOL. The default value is 0. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Low DP Hysteresis is the amount by which the differential pressure needs to rise above the Low DP Cutoff for flow accumulation to start. It may be a value using the DP units or may be a percentage of the operating span. The operating span is the difference between the Upper Operating Limit and the
Lower Operating limit. Values depend on the transmitter. The flow accumulation level needs to be less than the Upper Operating Limit. The default value is 0.
Realflo User and Reference Manual
May 19, 2011
88
Turbine Settings
Realflo Maintenance Mode Reference
This step configures the turbine input for AGA-7 calculations.
Input Register is the register address where the input value is stored. Valid values are 30001 to 39999 or 40001 to 49999. The default is selected based on the run number so that inputs have unique registers.
Low Flow Pulse Limit is the number of pulses below which a low flow alarm will occur. The default value is 10.
Low Flow Detect Time is the length of time the number of pulses needs to remain below the Low Flow Pulse Limit for a low flow alarm to occur. Valid values are 1 to 5 seconds. The default value is 5.
Realflo User and Reference Manual
May 19, 2011
89
Realflo Maintenance Mode Reference
Static Pressure Options Dialog
This step lets you select how the static pressure is measured.
The pressure tap may be upstream or downstream of the orifice plate for
AGA-3.
Select Up Stream for an upstream static pressure tap. This is the default value. The control is disabled for AGA-7 and V-Cone calculations.
Select Down Stream for a downstream static pressure tap. The control is disabled for AGA-7 and V-Cone calculations.
Static Pressure Input Limits
This step defines the limits for the temperature input. One of two configuration dialogs is presented based on the Input Type configured for static pressure limits:
Realflo User and Reference Manual
May 19, 2011
90
Sensor Inputs.
Realflo Maintenance Mode Reference
Realflo User and Reference Manual
May 19, 2011
91
Sensor Inputs
Realflo Maintenance Mode Reference
The dialog below is presented when sensor inputs are used.
Input Type is a read-only field that identifies the sensor number for which you are setting the parameters using this dialog.
Units is the differential pressure units. Values read from the transmitter are in these units. If the transmitter has a local display it uses these units. Valid values are kiloPascal, MegaPascal, and psi (pounds per square inch). The default is psi.
Damping is the response time of the transmitter. It is used to smooth the process variable reading when there are rapid input variations.
For SCADAPack transmitters the valid values are 0.0 (damping off), 0.5,
1.0, 2.0, 4.0, 8.0, 16.0, and 32.0 seconds. The default value is 0
(damping off).
For the 3095 MVT the valid values are 0.108, 0.216, 0.432, 0.864,
1.728, 3.456, 6.912, 13.824 and 27.648. The default is 0.864.
Lower Operating Limit (LOL) is the lowest valid value from the sensor and needs to be less than the UOL. Alarms occur if the value is less than the
LOL. The default value is 0. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Upper Operating Limit (UOL) is the highest valid value from the sensor and needs to be greater than the LOL. Alarms occur if the value is greater than the UOL. The default value is the upper range limit of the transmitter.
Valid values depend on the transmitter; refer to the transmitter band or user manual.
Default Value is enabled if you gage pressure using the Static Pressure
Options. Type the live input value to use when communicating with a sensor. The template selected determines the default value displayed.
The pressure sensor may measure absolute or gage pressure.
Realflo User and Reference Manual
May 19, 2011
92
Analog Inputs
Realflo Maintenance Mode Reference
Select Absolute Pressure to measure absolute static pressure. This is the default value unless the Compressibility Calculation type is set to
NX-19. The Static Pressure is set to Gage and the Atmospheric pressure is 14.7psi when NX-19 is selected.
Select Gage Pressure to measure gage static pressure.
Type the Atmospheric Pressure measured at the site. This control is disabled and set to zero if absolute pressure is selected.
The atmospheric pressure entered needs to be greater than zero. The maximum upper limits for atmospheric pressure are:
30 psi and PEMEX units for US1, US2, US3, US4, US5, US6, US7, US8,
4320
207 lbf/ft2 for IP units kPa for Metric1 units
2.07
0.207 bar for Metric2 units
MPa for Metric3 units
207000 Pa for SI units
If you configured sensor inputs, see the
section.
The dialog below is presented when analog inputs are used.
Input Type is a read-only field that identifies the input type for which you are setting the parameters using this dialog.
Input Register is the register address where the input value is stored. Valid values are 30001 to 39999 or 40001 to 49999. The default is selected based on the run number so that inputs have unique registers.
Input at Zero Scale is value read from the sensor, in unscaled I/O units, when the sensor is at zero scale. Valid values depend on the input type. The default value is 0. This is enabled for Telepace integer, raw float and
ISaGRAF integer types and disabled otherwise.
Realflo User and Reference Manual
May 19, 2011
93
Realflo Maintenance Mode Reference
Input at Full Scale is value read from the sensor, in unscaled I/O units, when the sensor is at full scale. Valid values depend on the input type. The default value is 32767. This is enabled for Telepace integer, raw float and
ISaGRAF integer types and disabled otherwise.
SP at Zero Scale is the pressure that corresponds to the zero scale input, or if the input does not require scaling, the minimum pressure that can be read from the sensor. Valid values depend on the input type. The default value is 0.
SP at Full Scale is the pressure that corresponds to the full-scale input, or if the input does not require scaling, the maximum pressure that can be read from the sensor. Valid values depend on the input type. The default value is
20000.
Static Pressure Compensation
This step selects if compensation is applied for the location where calibration was performed. If you configured sensors or analog inputs from the Static Pressure Limits dialog, this is the next step in the configuration sequence.
Select No if compensation is not required. This is the default value.
Select Yes to compensate for the altitude and latitude.
Type the Altitude of the location. Valid values are -30000 to 30000. The default value is 0. This control is disabled if No is selected.
Type the Latitude of the location. Valid values are -90 to 90. The default value is 0. This control is disabled if No is selected.
Temperature Limits
This step lets you define the limits for the temperature input. One of two configuration dialogs is presented based on the Input Type configured for static pressure limits:
Realflo User and Reference Manual
May 19, 2011
94
Sensor Inputs
Realflo Maintenance Mode Reference
Analog Inputs
The following dialog is presented when sensor (MVT) inputs are used.
Input Type is a read-only field that identifies the sensor number for which you are setting the parameters using this dialog.
Units is the differential pressure units. Values read from the transmitter are in these units. If the transmitter has a local display it uses these units. Valid values are kiloPascal, MegaPascal, and psi (pounds per square inch). The default is psi.
Lower Operating Limit (LOL) is the lowest valid value from the sensor and needs to be less than the UOL. Alarms occur if the value is less than the
LOL. The default value is 0. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Upper Operating Limit (UOL) is the highest valid value from the sensor and needs to be greater than the LOL. Alarms occur if the value is greater than the UOL. The default value is the upper range limit of the transmitter.
Valid values depend on the transmitter; refer to the transmitter band or user manual.
Realflo User and Reference Manual
May 19, 2011
95
Analog Inputs
Realflo Maintenance Mode Reference
The following dialog is presented when analog inputs are used.
Input Type is a read-only field that identifies the input type for which you are setting the parameters using this dialog.
Input Register is the register address where the input value is stored. Valid values are 30001 to 39999 or 40001 to 49999. The default is selected based on the run number so that inputs have unique registers.
Input at Zero Scale is value read from the sensor, in unscaled I/O units, when the sensor is at zero scale. Valid values depend on the input type. The default value is 0. This is enabled for Telepace integer, raw float and
ISaGRAF integer types and disabled otherwise.
Input at Full Scale is value read from the sensor, in unscaled I/O units, when the sensor is at full scale. Valid values depend on the input type. The default value is 32767. This is enabled for Telepace integer, raw float and
ISaGRAF integer types and disabled otherwise.
Temperature at Zero Scale is the temperature that corresponds to the zero scale input, or if the input does not require scaling, the minimum pressure that can be read from the sensor. Valid values depend on the input type.
The default value is
–40.
Temperature at Full Scale is the temperature that corresponds to the fullscale input, or if the input does not require scaling, the maximum pressure that can be read from the sensor. Valid values depend on the input type.
The default value is 200.
Realflo User and Reference Manual
May 19, 2011
96
Realflo Maintenance Mode Reference
Contract Settings
This step sets the contract settings for the run.
Input Average Weighting is the weighting method of the linear inputs. This applies to the differential pressure, static pressure, and temperature. Valid
values are time-weighted or flow-weighted (see Input Averaging on page
948 for more information). The default is time-weighted.
Contract Hour is the hour of the day that starts a new contract day specified using a 24-hour clock. The contract day begins at 00 minutes and
00 seconds of the specified hour. Valid values are 0 to 23. The default value is 0 (midnight).
Standard Base Conditions are the default Base Temperature and Base
Pressure (absolute) values.
Base Temperature is the reference temperature to which contract flow values are corrected. Valid values are -40 to 200. The default value is given in the table below.
Base Pressure is the reference pressure to which contract flow values are corrected. The base pressure is measured as absolute pressure
(not a gauge pressure). Valid values are 0 to 32000. The default value is given in the table below.
Contract Units Standard Base
Temperature
US1
US2
US3
IP
Metric1
Metric2
Metric3
SI
60 F
60 F
60 F
60 F
15 C
15 C
15 C
288.15 K
Standard Base
Pressure
14.73 psi
14.73 psi
14.73 psi
2116.2281 lbf/ft
2
101.325 kPa
1.01325 bar
0.101325 MPa
101325 Pa
Realflo User and Reference Manual
May 19, 2011
97
Realflo Maintenance Mode Reference
Contract Units Standard Base
Temperature
US4
US5
US6
US7
US8
PEMEX
60 F
60 F
60 F
60 F
60 F
60 F
Standard Base
Pressure
14.73 psi
14.73 psi
14.73 psi
14.73 psi
14.73 psi
14.73 psi
Realflo for PEMEX flow computers provide a second set of base conditions.
PEMEX Base Conditions are the default Base Temperature and Base
Pressure (absolute) values when Realflo is operating in PEMEX mode.
Base Temperature is the reference temperature to which contract flow values are corrected. The default is listed in the table below for each type of contract unit.
Base Pressure is the reference pressure to which contract flow values are corrected. The base pressure is measured as absolute pressure
(not a gauge pressure). Valid values are 0 to 32000. The default values are listed in the table below for each contract unit.
Contract Units Standard Base
Temperature
US1 60 F
US2
US3
IP
Metric1
Metric2
60 F
60 F
60 F
15 C
15 C
Metric3
SI
US4
US5
US6
US7
US8
PEMEX
15 C
288.15 K
60 F
60 F
60 F
60 F
60 F
68 F
Standard Base Pressure
14.73 psi
14.73 psi
14.73 psi
2116.2281 lbf/ft
2
101.325 kPa
1.01325 bar
0.101325 MPa
101325 Pa
14.73 psi
14.73 psi
14.73 psi
14.73 psi
14.73 psi
14.73 psi
Flow Calculations
When configuring a flow computer, you can configure it to use the following calculations:
AGA-Settings
AGA-3 Deadband Settings
AGA-7 Settings
AGA-11 Settings
Realflo User and Reference Manual
May 19, 2011
98
AGA-3 Settings
Realflo Maintenance Mode Reference
This step lets you set the AGA-3 calculation parameters.
Orifice Material is the material the orifice plate for the meter run is made of.
Valid values are Stainless Steel, Monel, and Carbon Steel. The default value is Stainless Steel.
Pipe Material is the material the meter run pipe is made of. Valid values are
Stainless Steel, Monel, and Carbon Steel. The default value is Carbon
Steel.
Orifice Diameter is the diameter of the meter run orifice. The default value is 3 inches.
Orifice reference temperature is the temperature at which the diameter of the meter run orifice was measured. The default value is 68°F.
Pipe Diameter is the measurement of the meter run pipe inside diameter.
The default value is 4.026 inches.
Pipe reference temperature is temperature at which the meter run pipe diameter was measured. The default value is 68°F.
Beta Ratio is the ratio of orifice diameter to pipe diameter. It is displayed for information purposes only and cannot be edited.
Realflo displays a message if the beta ratio is outside recommended limits.
Isentropic Exponent is a thermodynamic property of gas used to predict the relationships between pressure, temperature, volume and energy. If you are unsure of this value, a typical value of 1.3 is commonly used. The default value is 1.3.
Viscosity is a measure of the resistance of a measured gas to flow. Valid values are 0 to 1. The default value is 0.010268 centipoise.
Realflo User and Reference Manual
May 19, 2011
99
Realflo Maintenance Mode Reference
AGA-3 Deadband Settings
This step lets you set AGA-3 calculation deadbands.
Temperature Deadband is the tolerated change in the flowing temperature before temperature dependent factors in the flow calculation are recalculated. Changes in the temperature smaller than the deadband will be ignored in determining the result. The default value is 0. The upper limit is
7°F or 4°C.
Static Pressure Deadband is the tolerated change in the static pressure before static pressure dependent factors in the flow calculation are recalculated. Changes in the static pressure smaller than the deadband will be ignored in determining the result. A static pressure deadband setting of up to four percent of the typical static pressure level should have a small effect on the accuracy of the AGA-3 calculation. The default value is 0. The upper limit is 800 psi or 5500 kPa or the equivalent in other units.
Differential Pressure Deadband is the tolerated change in the differential pressure before differential pressure dependent factors in the flow calculation are recalculated. Changes in the differential pressure smaller than the deadband will be ignored in determining the result. A change of N in the differential pressure input will cause a change of 0.5 N in the calculation volume at base conditions. It is recommended that the differential pressure deadband be set to zero. The default value is 0. The upper limit is 4.5 inWC or 1.1 kPa or the equivalent in other units.
Realflo User and Reference Manual
May 19, 2011
100
AGA-7 Settings
Realflo Maintenance Mode Reference
This step lets you define AGA-7 settings.
AGA -11 Settings
K Factor is the number of pulses per unit volume of the turbine meter. Valid values are 0.001 to 1000000. The default value is 100.
M Factor is the adjustment to the number of pulses per unit volume for the turbine meter compared to an ideal meter. Valid values are 0.001 to 1000.
The default value is 1.
Uncorrected Flow Volume is the accumulated uncorrected flow volume at base conditions.
The Uncorrected Flow Volume control is available in Realflo versions 6.20 and higher.
AGA-11 configuration defines parameters unique to the AGA-11 calculation.
The AGA-11 calculation communicates with a Coriolis meter for the calculation. The AGA-11 configuration sets the communication parameters for communication between the Coriolis meter and the flow computer.
Realflo User and Reference Manual
May 19, 2011
101
Address
Realflo Maintenance Mode Reference
This is the Modbus address of the Coriolis Meter for serial communications.
Multiple Coriolis meters using the same serial port on the flow computer need to each have a unique Modbus address. Valid Modbus addresses are between 1 and 247. The default address is 247.
Port
This is the communication port on the flow computer that will be used to communicate with the Coriolis meter. Valid port selections depend on the type of controller the flow computer running on. The default port is the first valid port available on the controller.
Timeout
V-Cone Settings
This is the time the flow computer will wait for a response for Modbus read commands send to the Coriolis meter. When the timeout time is exceeded the command is unsuccessful and an alarm is added to the flow computer alarm list. Valid timeout values are from 0 to 1000 ms. The default value is
50 ms.
V-Cone Configuration defines parameters unique to the V-Cone calculation.
Cone Material
This is the material of the V-cone. Valid values are Carbon Steel, Stainless
304, and Stainless 316. The default value is determined by the template selected.
Pipe Material
This is the material from which the meter run pipe is made. Valid values are
Carbon Steel, Stainless 304, and Stainless 316. The default value is determined by the template selected.
Adiabatic Expansion Factor
The Adiabatic Expansion Factor drop down list selects which calculation is used for the adiabatic expansion factor of the calculation.
Realflo User and Reference Manual
May 19, 2011
102
Realflo Maintenance Mode Reference
Select Legacy Calculation to use the older calculation method. This is the default selection. Flow computers prior to version 6.71 support only this selection.
Select V-Cone to use the V-Cone specific calculation. This selection should be used with V-Cone devices.
Select Wafer-Cone to use the Wafer-Cone specific calculation. This selection should be used with Wafer-Cone devices.
This control is disabled and forced to Legacy Calculation if the controller type is not one of SCADAPack 32, SCADAPack 32P, SCADAPack
314/330/334, SCADAPack 350 SCADAPack 4203 or SolarPack 410.
When reading from a flow computer that does not support the adiabatic expansion factor configuration, the method will be set to Legacy Calculation.
When writing to a flow computer that does not support the adiabatic expansion factor method, the configuration registers will be ignored and the expansion factor will not be written.
Cone Diameter
The diameter of the meter run cone used for the flow calculation. The measurement units are displayed depending on the input units selected.
The default value is 3 inches.
Cone Measurement Temperature
This is the reference temperature at which the cone diameter for the meter run was measured. The measurement units are displayed depending on the input units selected. The default value is 59 degrees F.
Pipe Inside Diameter
This is the measurement of the meter run pipe inside diameter. The measurement units are displayed depending on the input units selected.
The default value is 5 inches.
Pipe reference temperature
The temperature at which the meter run pipe diameter was measured. The measurement units are displayed depending on the input units selected.
The default value is 59 degrees.
Isentropic Exponent
In general, this is a thermodynamic property of gas used to predict the relationships between pressure, temperature, volume and energy. If you are unsure of this value a typical value of 1.3 is commonly used. The default value is 1.3.
Viscosity
This is the viscosity of the measured gas. In general, this is the resistance of a gas or semi-fluid resistance to flow. The measurement units are displayed depending on the input units selected. Valid values are 0 to 1. The default value is 0.010268 centiPoise.
Wet Gas Correction Factor
The Wet Gas Correction Factor Method drop down list selects which calculation is used for the wet gas correction factor of the calculation.
Realflo User and Reference Manual
May 19, 2011
103
Realflo Maintenance Mode Reference
Select Legacy Method to use the older correction method. This is the default selection. Flow computers prior to version 6.73 support only this selection.
Select V-Cone or Wafer Cone to use the V-Cone and Wafer Cone specific calculation. This selection should be used with V-Cone or Wafer
Cone devices.
This control is disabled and forced to Legacy Calculation if the controller type is not one of SCADAPack 32, SCADAPack 32P, SCADAPack
314/330/334, SCADAPack 350 SCADAPack 4203 or SolarPack 410.
The V-Cone or Wafer Cone supported Beta Ratios are:
For Fr (Froude Number) < 5 supported Beta Ratio is 0.55.
For Fr (Froude Number) < 5 supported Beta Ratio is 0.75.
For Fr (Froude Number) > 5 supported Beta Ratio is 0.75.
When V-Cone or Wafer Cone is selected and if the current Beta ratio is not supported when executing verification, a message is displayed.
Density of Liquid
When V-Cone or Wafer Cone is selected, configuration of the fixed wet gas factor parameter, as set in the Contract tab, is disabled.
When Legacy Method is selected, configuration of the parameters used by the V-Cone or Wafer Cone method is disabled.
Mass Flow Rate of Liquid
The Mass flow rate of liquid at flow conditions parameter is used by the V-
Cone or Wafer Cone method and can be configured when V-Cone or Wafer
Cone is selected. This information needs to be gathered using a sampling method or a tracer method. The default is 0.
The Density of liquid at flow conditions parameter is used by the V-Cone or
Wafer Cone method and can be configured when V-Cone or Wafer Cone is selected. The default is 0.
Realflo User and Reference Manual
May 19, 2011
104
Realflo Maintenance Mode Reference
V-Cone Coefficients
This step lets you define the V-Cone coefficients.
Enter the V-Cone coefficient pairs from the meter sizing report. The default list contains one pair: Re = 1000000; Cf = 0.82.
Click Add to add a coefficient pair.
In the original McCrometer V-Cone Application Sizing sheet that is included with V-Cone meters uses the terminology Cd (discharge coefficient) rather than Cf (flow coefficient). You will need to use the Re and Cd values from the V-Cone Application Sizing sheet for the Re and Cf entries. If the Re value is the same for every entry in the table only the first pair is used.
McCrometer now supplies one value of Cd in the sizing document. You need to enter one Re/Cd pair only. See the McCrometer Application Sizing sheet for the Re/Cd pair for your meter.
To edit a coefficient pair in the table:
Select a row in the list.
Click Edit to open the Add/Edit Flow Coefficient dialog.
To delete a coefficient pair in the table:
Select a row in the list.
Click Delete to delete the pair form the list.
Realflo User and Reference Manual
May 19, 2011
105
Realflo Maintenance Mode Reference
Compressibility Calculations
When configuring a flow computer, you can configure it to use the following compressibility calculations:
AGA-8 Settings
This step sets AGA-8 calculation options.
Events can be logged each time an AGA-8 gas component changes.
Select Yes to log each change to the gas composition. Use this option if the gas composition changes infrequently. This is the default selection.
Select No to skip logging changes. Use this option if you are making frequent changes to the gas composition.
The Relative Density and Heating values can be calculated from the AGA-8 calculation or determined in a laboratory.
Select Calculate the Values to have AGA-8 calculate the values.
Select Use Laboratory Values to used fixed values.
Relative Density sets the real relative density of the gas. Valid values are 0.07 to 1.52. The default value is 0.554. This control is disabled if
Calculate the Values is selected.
Heating Value sets the heating value of the gas. Valid values are 0 to
1800 BTU(60)/ ft
3
or the equivalent in the selected units. The default value is 1014 BTU(60)/ft
3
or the equivalent in the selected units. This control is disabled if Calculate the Values is selected.
Realflo User and Reference Manual
May 19, 2011
106
Realflo Maintenance Mode Reference
AGA-8 Hexanes+ Settings
This step chooses if Hexane and higher components are entered individually or as a single combined value.
Gas composition can be measured with individual values for hexane and higher components or use a combined value.
Select Enter Each Component to use individual values for the higher components. This is the default selection.
Select Use Combined Hexanes+ with these Ratios to use a combined value. Type the ratios of the higher components.
n-Hexane defines the percentage of the Hexanes+ contributed by n-
Hexane.
n-Heptane defines the percentage of the Hexanes+ contributed by n-
Heptane.
n-Octane defines the percentage of the Hexanes+ contributed by n-
Octane.
n-Nonane defines the percentage of the Hexanes+ contributed by n-
Nonane.
n-Decane defines the percentage of the Hexanes+ contributed by n-
Decane.
The Total field displays the sum of each portion. This value cannot be edited. The total of portions needs to be 100 percent.
AGA-8 Gas Composition
This step defines the AGA-8 gas composition. One of two configuration dialogs opens based on whether Hexane and higher components are entered individually or as a single combined value.
Individual Components
Realflo User and Reference Manual
May 19, 2011
107
Realflo Maintenance Mode Reference
The dialog below lets you enter combined Hexanes+ composition.
Type the gas composition according to the laboratory analysis. The total of components needs to be 100 percent.
Normalize adjusts non-zero components so that the total of components is
1.0000 (or 100.00 percent). The ratio to each other for the components remains the same.
Realflo User and Reference Manual
May 19, 2011
108
Realflo Maintenance Mode Reference
Combined Hexanes+
The dialog below lets you enter combined Hexanes+ composition.
NX-19 Settings
Type the gas composition according to the laboratory analysis. The total of components needs to be 100 percent.
Normalize adjusts non-zero components so that the total of components is
1.0000 (or 100.00 percent). The components remain in their current ratio to each other.
This step lets you define the NX-19 calculation. NX-19 is not supported for
PEMEX flow computers.
Realflo User and Reference Manual
May 19, 2011
109
Realflo Maintenance Mode Reference
Specific Gravity is the specific gravity of the gas being measured. Valid values are 0.554 to 1.000. The default value is 0.554.
Carbon Dioxide is the percent of carbon dioxide in the gas being measured. This value needs to be in the range 0 to 15. The default value is
0.
Nitrogen is the percent of nitrogen in the gas being measured. This value needs to be in the range 0 to 15.
Heating Value is the heating value of the gas being measured. Valid values are 0 to 1800 BTU(60)/ft
3
or the equivalent in the selected units. The default value is 1014.33 BTU(60)/ft3.
Events can be logged each time the NX-19 configuration changes.
Select Yes to log each change to the configuration. Use this option if the configuration changes infrequently. This is the default selection.
Select No to skip logging changes. Use this option if you are making frequent changes to the configuration.
Sensor Configuration Parameters
The next step is MVT Configuration if any transmitters were used in the
input configuration. Otherwise the next step is
Sensor Configuration
This step selects how the transmitters are to be configured.
The Flow Runs are configured to use these transmitters window is a table that shows each of the configured flow run numbers, its Flow Run ID and the transmitter that it uses for the differential pressure (DP), static pressure (SP) and temperature sensors. If an analog input is used for the flow run AIN will be displayed in the coresponding DP, SP, or Temp column.
Realflo User and Reference Manual
May 19, 2011
110
Realflo Maintenance Mode Reference
The How do you want to configure sensors? option lets you select how to continue configuring the sensors. The three options are:
Connect now and configure transmitters to connect to the flow computer and configure the attached transmitters. This selection is disabled if the flow computer configuration was selected to be completed offline in the Flow Computer Status step. If you choose this
Configure Connected Transmitters
section to continue.
Edit sensor configuration without connecting to proceed directly to the editing pages, without connecting to the flow computer. If you
continue.
Use default sensor configuration to complete the configuration without changing the sensor configuration. Sensor configuration will be
set to default values. If you choose this option, the next step is
Configure Connected Transmitters
This step lets you select to either use the Realflo configuration data or the configuration from a pre-configured transmitter.
Sensor Search
Select Use the configuration from Realflo to use the configuration data from the Realflo file. This is the default setting.
Select Read the configuration from the transmitter to read configuration from a pre-configured transmitter.
This step searches for sensors connected to the flow computer serial ports or LAN port.
Realflo User and Reference Manual
May 19, 2011
111
Realflo Maintenance Mode Reference
Search Serial Option
Select Search Serial to search for transmitters connected to a serial port of the flow computer.
The Port parameter selects the flow computer serial port where the sensor is attached. Valid values are com1, com2, com3, and com4. The default value is com2 for a SCADAPack controller and com1 for other controllers.
The Timeout parameter specifies the length of time the flow computer will wait for a response from a sensor. Valid values are 100 ms to 10000 ms.
The default is 300 ms.
Select Maximum to search for a number of MVT transmitters. The search operation will stop after finding the specified number of transmitters. The valid value is from 1 to 255. The default is 1.
Select Range to search the addresses in a specified range. The range to search for is typed in the edit boxes to the right of the radio button. The value in To edit control needs to be equal or great than the value in the first edit control. The maximum search range that can be typed is for 255 transmitters. The default range is 1 to 247.
Range Search supports addresses 1 to 255 in standard Modbus mode, and 1 to 65534 in extended address mode. The address mode of the flow computer serial port needs to be set to extended to search for transmitters with extended addresses.
Select All to search the addresses of transmitters connected with the serial port selected in Port. Up to 255 addresses are searched.
Realflo User and Reference Manual
May 19, 2011
112
Search LAN Option
Select Search LAN to search for transmitters connected to a LAN port of the flow computer.
The IP Address parameter specifies the IP address of a 4000 transmitter.
Valid entries are IP addresses in the format nnn.nnn.nnn.nnn where nnn are values between 0 and 255.
The Protocol parameter selects the type of IP protocol that will be used to query the transmitter. Valid IP protocol selections are Modbus/TCP and
Modbus RTU in UDP.
The IP port (for example port 502) for the selected protocol needs to be the same in the flow computer and the 4000 transmitter.
The Timeout parameter specifies the length of time the flow computer will wait for a response from a 4000 transmitter. Valid values are 100 to 10000 milliseconds. The default is 5000 ms.
Click Next to start the search for MVT transmitters or 4000 transmitters. A search process dialog is displayed so that the search operation can be cancelled at any time.
If no transmitters were found, a message is displayed and the search step is displayed again.
Assign Sensors
Realflo Maintenance Mode Reference
Click Next to start the search for sensors or 4000 transmitters. A search process dialog is displayed so that the search operation can be cancelled at any time.
This step lets you assign found transmitters to flow runs.
The Available Sensors pane shows the transmitters that have been configured and the transmitters that were found by the search. There may be more transmitters in the list than there are runs.
Realflo User and Reference Manual
May 19, 2011
113
Realflo Maintenance Mode Reference
The Sensor column indicates the transmitter slots that have been configured. Transmitters that were found but not assigned are listed as Not
assigned.
The Status column indicates if configuration data for the transmitter exists.
Found indicates a transmitter has been configured and the search found one with the same port, address and device type.
Missing indicates a transmitter has been configured but the search did not find one with the same port, address, and device type.
The Port column displays the serial or LAN port the flow computer is using to communicate with the transmitter.
The Address column displays the Modbus station address or IP address of the transmitter.
The Tag column displays the Tag Name assigned to the transmitter. You can leave this column blank if a Tag Name has not been assigned to the transmitter.
The Device type column displays the transmitter type. Valid values are
3095FB, 4101, 4102, 4202 DR, 4202 DS, 4203 DR, or 4203 DS.
The Flow Runs window shows which MVTs are assigned to the runs.
To Change the order of the sensors:
Select a sensor in Available Sensors window.
Click Move.
The Move Sensor dialog opens:
In the Move Sensor dialog, use Move To selection to select the new location
Click OK.
To delete a sensor:
Select a transmitter in Available Sensors.
Click Delete.
To change the address of a Sensor:
Select a transmitter in Available Sensors.
Click Change Address.
The Change Address dialog opens:
Realflo User and Reference Manual
May 19, 2011
114
Realflo Maintenance Mode Reference
Enter a new address for the transmitter in the New Address: edit box.
Click OK.
Click Next when the transmitters have been moved to the correct location.
Next is disabled if there are Not Assigned transmitters still in the list.
Search for More Transmitters Dialog
Notes
The following actions may occur when moving a sensor.
Moving one sensor to another results in the both swapping positions.
When Use the configuration from Realflo is selected, assigning a Not assigned transmitter to a Sensor with status Missing and device type matching result in the sensor adopting the transmitter‟s port and address and retaining the rest of the sensor configuration. The sensor, being assigned, will disappear from the list.
When Read the configuration from the transmitter is selected, assigning a Not assigned transmitter to a sensor with status Missing and device type matching results in the sensor adopting the transmitter‟s configuration. The transmitter, being assigned, will disappear from the list.
Assigning a Not assigned transmitter to a sensor with status Missing and device type not matching will result in the sensor adopting the transmitter‟s configuration. The transmitter, being assigned, will disappear from the list.
Other assignments are not permitted.
Search for More Transmitters Dialog
This step displays the current sensor assignments and asks if more searches are needed.
Realflo User and Reference Manual
May 19, 2011
115
Realflo Maintenance Mode Reference
Proposed Sensors shows the transmitters that have been configured and the transmitters that were found by the search.
Flow Runs shows which sensors are assigned to which runs.
Select Search for more transmitters to search again.
Select Finish searching and review configuration to use the current settings. This is the default radio button.
Review Sensors Dialog
This step displays the transmitter assignments and allows you to edit the transmitter configuration.
Realflo User and Reference Manual
May 19, 2011
116
Realflo Maintenance Mode Reference
The Sensors pane shows the transmitters that have been configured.
The Flow Runs pane shows which sensors are assigned to the runs.
Click Edit to review and modify the settings for each transmitter. Edit opens the Add/Edit Sensor Settings dialog. Changes to a transmitter address will be written to the transmitter without affecting current flow computer configuration.
Copy Run Configuration Dialog
The Copy Run step is displayed only if you selected more than one run is selected in the Number of Flow Runs step and you have configured the first run.
The second flow run, and subsequent runs, may be configured step-by-step or by copying the configuration of a previous run.
Create Configuration Step-by-Step
to configure another run using the wizard without copying Run 1.
Flow Computer Configuration Summary
This step displays a summary of the flow computer settings.
Realflo User and Reference Manual
May 19, 2011
117
Realflo Maintenance Mode Reference
A summary of the flow computer configuration is shown.
The current configuration can be compared with the configuration in the target flow computer.
Select Yes to compare the configurations.
Select No to not compare the configurations.
Review Differences
This step displays a summary of changes in the flow computer configuration. You can select to write to the flow computer or not.
The summary shows the differences in the configuration.
Select Yes to write the configuration to the flow computer. The configuration is written to the flow computer. The Start Executing command will be written for each flow run. The communication progress dialog shows the stages of writing.
Select No to write the configuration to the flow computer later.
Realflo User and Reference Manual
May 19, 2011
118
Save File
Realflo Maintenance Mode Reference
Click Next to perform the selected action.
In Flow Computer versions 6.73 and older, when AGA-8 gas ratios or NX-19 gas quality values are written to the flow computer the new gas ratios are updated in the Proposed registers. The Actual registers are not updated until a new Density calculation is started with the new values. The new values are not available to SCADA host software reading the Actual registers until a until a new Density calculation is started with the new values.
In Flow Computer versions 6.74 and newer when AGA-8 gas ratios or NX-
19 gas quality values are written to the flow computer the new gas ratios are updated in the Proposed registers and in the Actual registers. This allows a
SCADA host to immediately confirm the new values were written to the flow computer. The new gas values are not used by the flow computer until a new density calculation is started.
This step lets you select where to save the configuration file.
Finish
Select Save to Realflo.tfc to save the configuration file to the default file location.
Select the Save to another file to either enter a file name or use the
Browse option to open the Save As dialog.
This step is displayed at the end of the wizard.
Realflo User and Reference Manual
May 19, 2011
119
Realflo Maintenance Mode Reference
Click Finish to close the wizard.
Realflo User and Reference Manual
May 19, 2011
120
Realflo Maintenance Mode Reference
View Data
The View Data section contains a View Current Readings button and a
Read Logs and Flow History button.
Click the View Current Readings button to start the View Current Readings wizard, which will lead you through the steps to connect to a flow computer and view the current readings.
Click the Read Logs and Flow History button to start the Read Logs and
Flow History wizard, which will lead you through the steps to connect to a flow computer and read the alarm and event logs and the flow history.
View Current Readings
The View Current Readings wizard will lead you through the steps to connect to a flow computer and view the current readings.
<Back returns to the previous step in the wizard. This button is disabled on the first step of a wizard.
Next> moves to the next step in the wizard. This button is hidden on the last step of a wizard.
Finish is displayed on the final step of a wizard in place of the Next button. It finishes the operation. This button is hidden on other steps.
Cancel cancels the operation and closes the wizard. Steps performed thus far in the wizard are cancelled. Pressing the ESC key performs the same action as Cancel.
Help opens the user manual.
Connect to Flow Computer
The connect to flow computer step defines the communication settings for the connection between the PC running the Realflo application and the target flow computer.
The How do you want to communicate with the flow computer? prompt provides two selections.
The Use the Current Settings option sets the default communication settings for Realflo. These settings are for the PC that is running Realflo.
Realflo User and Reference Manual
May 19, 2011
121
Realflo Maintenance Mode Reference
(The communication settings for the PC running Realflo and the communication settings in the flow computer need to match).
The default communication settings are:
COM 1 (serial port on the PC)
9600 baud, no parity
8 Data bits
1 Stop bit
The default Modbus address Realflo will connect to is station 1.
Use this selection if the serial port on your PC is COM 1 and the serial port settings for the serial port on the flow computer are set for default (9600,
8,n,1 and Modbus address 1).
Click the Next> button to begin communication with the flow computer and move to the next step in the wizard.
The Choose/View Communication Setup option opens the PC
Communication Settings dialog as shown below. This allows you to view the default settings and to change the PC communication setting for the type of connection you are using to communicate with the flow computer.
See the section Communication >> PC Communication Settings
Command in the Realflo Expert Mode Reference section of this manual for complete details on the parameter settings in this dialog.
You need to know the communication settings for the connection to the flow computer to use this step.
Once the communication settings have been selected click the OK> button to close the dialog and begin communication with the flow computer.
Current Readings View
The Current Readings view displays current measured and calculated values from the flow computer. The Current Readings view will appear differently depending on the run configuration.
Realflo User and Reference Manual
May 19, 2011
122
Realflo Maintenance Mode Reference
The view is divided into eight sections. These sections are:
Process Measurements
This section displays the live and forced values for the flow calculation process inputs. The live values show the value read from the sensor. The forced values show the inputs to the flow calculation when they are forced.
The Forced values are disabled when the input is live. The forced values are shown in red when the value is forced.
The units of measurement displayed are those in effect when the readings were made. See Measurement Units for a description of the unit types.
Process measurements not used by the flow calculation are disabled.
Forced values are not displayed for flow computers older than 6.0.
Calculated Compressibility
This section displays the results of the compressibility calculation selected in the Input Configuration property page. The time of the last compressibility calculation update and any compressibility calculation errors are also displayed in this section. The units of measurement displayed are those in
effect when the readings were made. See Measurement Units
for a description of the unit types.
Calculation Status
The Calculation Status section displays the Calculation State of the flow computer calculations for the run. Refer to the Calculation Control command in the Flow Computer menu for further information on flow calculation control.
The Calculation State Start and Stop button is disabled for users who have a read and view privileges account.
The Calculation State can be changed using the start or stop button beside the Calculation State display.
When the Current Readings are being updated and the calculation is
stopped or not set then the button is labeled Start.
When the Current Readings are being updated and the calculation is
running then the button is labeled Stop.
Realflo User and Reference Manual
May 19, 2011
123
Realflo Maintenance Mode Reference
When the Current Readings are not being updated the button is disabled and no text is displayed on it.
Click on the button to change the Calculation State.
If the calculations are stopped the following message box is displayed.
If Yes is selected the flow calculations for the run are started.
If No is selected the message box is closed and no further action is taken.
If the calculations are running the following message box is displayed.
If Yes is selected the flow calculations for the run are stopped.
If No is selected the message box is closed and no further action is taken.
The Last Flow Configuration displays the time stamp of the last time the flow configuration was changed.
The Last Density Configuration displays the time stamp of the last time the compressibility configuration was changed.
The Last Flow Configuration and Last Density Configuration values are not displayed for flow computers older than 6.0.
Pulse Input Volume
The Pulse Input Volume section is enabled when you configure a
Calculated Flow at Base Conditions
The Calculated Flow displays the instantaneous Flow Mas Rate, Standard
Flow Volume Rate, Flow Energy Rate, Flow Product, Time of last update, and Input and Flow Calculation Status. The Flow Extension is displayed when the run is configured for AGA-3 (1990) calculations. The Flow Product is displayed when the run is configured for AGA-3 (1990) calculations. The time of the last flow calculation and input and flow calculation status are also displayed. The units of measurement displayed are those in effect when the
for a description of the unit types.
Calculated Flow (PEMEX)
The Calculated Flow displays the instantaneous Flow Volume Rate,
Standard Flow Volume Rate, Flow Energy Rate, Flow Product, Time of last
Realflo User and Reference Manual
May 19, 2011
124
Realflo Maintenance Mode Reference update, and Input and Flow Calculation Status. The Flow Extension is displayed when the run is configured for AGA-3 (1990) calculations. The
Flow Product is displayed when the run is configured for AGA-3 (1990) calculations. The time of the last flow calculation and input and flow calculation status are also displayed. The units of measurement displayed
are those in effect when the readings were made. See
for a description of the unit types.
Accumulated Flow
The Accumulated Flow section displays the flow volume for the current contract day (Today) and the previous contract day (Yesterday). Data is copied from the current contract day (Today) to the previous contract day
(Yesterday) at the end of the contract day, as measured by the real time clock. Data is not copied when a new day is started for other reasons. It also displays the standard flow volume, flow energy, the number of flow calculations. The units of measurement displayed are those in effect when
for a description of the unit types.
This section also displays the accumulated flow volume and flow time for the current month and the previous month. Data is copied from the current month (This Month) to the previous month (Last Month) at the end of the contract day at the end of the month, as measured by the real time clock.
Accumulated Flow (PEMEX)
The Accumulated Flow section displays the PEMEX flow volume for the current contract day (Today) and the previous contract day (Yesterday).
Data is copied from the current contract day (Today) to the previous contract day (Yesterday) at the end of the contract day, as measured by the real time clock. Data is not copied when a new day is started for other reasons. It also displays the standard flow volume, flow energy, the number of flow calculations. The units of measurement displayed are those in effect when
for a description of the unit types.
This section also displays the accumulated flow volume and flow time for the current month and the previous month. Data is copied from the current month (This Month) to the previous month (Last Month) at the end of the contract day at the end of the month, as measured by the real time clock.
AGA-7 Calculations Only
Accumulated Uncorrected Flow
The Accumulated Uncorrected Flow section displays the total calculated uncorrected flow volume (for the current contract day, the previous contract day, the current month and the last month. The accumulator holds a number between 0 and 999,999,999,999. It rolls over when the accumulated value is equal or greater than 1,000,000,000,000.
The view is updated according to the status of the Update Readings selection in the Maintenance menu.
Realflo User and Reference Manual
May 19, 2011
125
SolarPack 410
Realflo Maintenance Mode Reference
Views specific to SolarPack 410 are described below.
Pulse Input Volume
This section displays pulse and accumulated flow volumes for the onboard counter of a SolarPack 410. This section applies only to the SolarPack 410 system.
Data displayed is as follows:
Pulses: Raw instantaneous pulse count
Today: An accumulation of today‟s total.
Yesterday: An accumulation of yesterday‟s total.
This Month: An accumulation of the totals for this month.
Last Month: An accumulation of the totals for last month.
Total: A running total volume since the beginning of this operation.
Volumes are listed in the unit selected when configuring the Pulse Input.
Battery Charger
The view has two additional sections. These sections are described below:
This section applies only to the SolarPack 410.
The Battery Status indicates the current state of the battery charger.
The Temperature Sensor indicates the current status of the battery charger temperature sensor.
Realflo User and Reference Manual
May 19, 2011
126
Realflo Maintenance Mode Reference
Read Logs and Flow History
The Read Logs and Flow History wizard will lead you through the steps to connect to a flow computer and read the alarm and event logs and the flow history.
<Back returns to the previous step in the wizard. This button is disabled on the first step of a wizard.
Next> moves to the next step in the wizard. This button is hidden on the last step of a wizard.
Finish is displayed on the final step of a wizard in place of the Next button. It finishes the operation. This button is hidden on other steps.
Cancel cancels the operation and closes the wizard. Steps performed thus far in the wizard are cancelled. Pressing the ESC key performs the same action as Cancel.
Help opens the user manual.
Connect to Flow Computer
The connect to flow computer step defines the communication settings for the connection between the PC running the Realflo application and the target flow computer.
The How do you want to communicate with the flow computer? prompt provides two selections.
The Use the Current Settings option sets the default communication settings for Realflo. These settings are for the PC that is running Realflo.
(The communication settings for the PC running Realflo and the communication settings in the flow computer need to match).
The default communication settings are:
COM 1 (serial port on the PC)
Realflo User and Reference Manual
May 19, 2011
127
Realflo Maintenance Mode Reference
9600 baud
no parity
8 Data bits
1 Stop bit
The default Modbus address Realflo will connect to is station 1.
Use this selection if the serial port on your PC is COM 1 and the serial port settings for the serial port on the flow computer are set for default (9600,
8,n,1 and Modbus address 1).
Click the Next> button to begin communication with the flow computer and move to the next step in the wizard.
The Choose/View Communication Setup option opens the PC
Communication Settings dialog as shown below. This allows you to view the default settings and to change the PC communication setting for the type of connection you are using to communicate with the flow computer.
See the section Communication >> PC Communication Settings
Command in the Realflo Expert Mode Reference section of this manual for complete details on the parameter settings in this dialog.
You need to know the communication settings for the connection to the flow computer to use this step.
Once the communication settings have been selected click the OK> button to close the dialog and begin communication with the flow computer.
Realflo User and Reference Manual
May 19, 2011
128
Realflo Maintenance Mode Reference
Select Runs to Read
This step selects the flow run or runs to read.
The Select the Flow Run or Runs to Read selection determines if data for all runs or for a single run is read.
The All Runs radio button selects reading data for all runs.
The Selected Run radio button selects reading from a single run. The drop-down list selects the run to be read.
Click the Next> button to move to the next step in the wizard.
Realflo User and Reference Manual
May 19, 2011
129
Realflo Maintenance Mode Reference
Select Flow Computer Configuration
This step selects whether to read the flow run configuration.
Select Yes to read the flow run configuration.
Select No to not read the flow run configuration.
Select Alarm and Event Logs to Read
This step selects which alarm and event logs to read.
The Which Events do you want to read? selection determines which events to read from the flow computer.
Select Just Read New Events to read unacknowledged events in the flow computer. If the operator has View, Read and Write Data or
Administrator authorization then the events will be acknowledged after
Realflo User and Reference Manual
May 19, 2011
130
Realflo Maintenance Mode Reference reading the new events. If the events in the log are not acknowledged, the event log will fill with 700 events. Operator activity will be prevented until the events are read and acknowledged. The control is grayed under the following conditions: o The event log is not selected. o The user has Read and View account privileges. o The Restrict Realflo users to reading all alarms and events option is selected in the Expert Mode Options menu.
Select Read All Events to read all events in the flow computer. This control is grayed if the Event Log control is not selected.
Select Do Not Read Any Events to skip reading of events from the flow computer.
The Which Alarms to you want to read? selection determines which alarm logs to read from the flow computer.
Select Just Read New Alarms to read unacknowledged alarms in the flow computer. If the operator has View, Read and Write Data or
Administrator authorization then the alarms will be acknowledged after reading the new events. If the events in the log are not acknowledged, the alarm log will fill with 300 events. Operator activity will be prevented until the alarms are read and acknowledged. The control is grayed under the following conditions: o The alarm log is not selected. o The user has Read and View account privileges. o The Restrict Realflo users to reading all alarms and events option is selected in the Expert Mode Options menu.
The Read All Alarms radio button selects the reading of all alarms in the controller. The control is grayed if the Alarm control is not selected.
The Do Not Read Any Alarms button selects not to read alarms from the flow computer.
Click the Next> button to move to the next step in the wizard.
Select Hourly and Daily History to Read
This step selects which hourly and daily logs to read.
Realflo User and Reference Manual
May 19, 2011
131
Realflo Maintenance Mode Reference
The Which Hourly Logs do you want to read? selection determines which hourly history is read.
Select New Hours to read hourly history for hours after the current time in the file. If the file is empty then Realflo will read hourly history stored in the flow computer. This is the default selection.
Select All Days to read hourly history for days stored in the flow computer.
Select Selected Hours to read hourly history for the range of days selected with the From and to drop-down lists. Records are read for the contract days whose first hour is within the date range. Records for the contract day are read, regardless of their calendar date. This may result in records with calendar days outside the range being added to the log.
For example, if the contract day is configured to start at 7:00 AM.
Reading hourly history for September 23 would return the records where the first record in a day was between 7:00 on the 23 the 24 th
. rd
to 6:59:59 AM on
The From control contains the oldest previous day for which the hourly history is to be read. The initial value is the current day. Change this date to avoid reading data that has previously been read into the log.
The to control contains the recent previous day for which the hourly history is to be read. The initial value is the current day. The allowed range is the same or greater than the value in the From control. Change this date when wanting to read older data only. Leaving this date at its default will result in the recent data being read.
Select the Do Not Read Hourly Logs to skip the reading of hourly logs.
The Which Daily Logs do you want to read? selection determines which hourly history is read.
Select New Days to read daily history for days after those in the current file. If the file is empty then Realflo will read all hourly history stored in the flow computer. This is the default selection.
Realflo User and Reference Manual
May 19, 2011
132
Realflo Maintenance Mode Reference
Select All Days to read daily history for all days stored in the flow computer.
Select Selected Days to read daily history for the range of days selected with the From and to drop-down lists. Records are read for the contract days whose first record is within the date range. Records for the contract day are read, regardless of their calendar date. This may result in records with calendar days outside the range being added to the log. For example, if the contract day is configured to start at 7:00
AM. Reading daily history for September 23 would return the daily records whose end time is in the range 7:00 on the 23 on the 24 th
. rd
to 6:59:59 AM
The From control contains the oldest previous day for which the daily history is to be read. The initial value is the current day. Change this date to avoid reading data that has previously been read into the log.
The to control contains the recent previous day for which the daily history is to be read. The initial value is the current day. The allowed range is the same or greater than the value in the From control. Change this date when wanting to read older data only. Leaving this date at its default will result in the recent data being read.
Select the Do Not Read Hourly Logs to skip the reading of hourly logs.
Click the Next> button to read the selected logs and history from the runs selected and move to the next step in the wizard.
The Read Logs Results page displays the results of the Read Logs and
History.
Save Data
Click the Next> button to move to the next step in the wizard.
This step selects where to save the flow run configuration, logs and flow history.
Realflo User and Reference Manual
May 19, 2011
133
Realflo Maintenance Mode Reference
Select Save to File name.tfc to save the data read to the currently opened file. The name of the current file is shown in place of file name.tfc.
Select Save to another file and enter a file name or click the Browse button to open the Save As dialog.
The following options allow you to specify the name and location of the file you're about to save:
The Save in: box lists the available folders and files.
The File name: box allows entry of a new file name to save a file with a different name. Realflo adds the extension you specify in the Save As type box.
The Save as type: box lists the types of files Realflo can save. Realflo can open flow computer (TFC) files and flow computer Template files (RTC).
Realflo User and Reference Manual
May 19, 2011
134
Realflo Maintenance Mode Reference
If the open file is a flow computer file and the Save as Type is a template file, Realflo will ask if the flow computer file should be saved before converting it to a template. This stops the missing of flow computer data when the file is converted.
The Save button saves the file to the specified location.
The Cancel button closes the dialog without saving.
Realflo User and Reference Manual
May 19, 2011
135
Export Data
Realflo Maintenance Mode Reference
This step selects whether to export the logs and history.
Select Export to CFX format file to export the logs and history to a Flow-
Cal CFX format file. This format is designed for importing into Flow-Cal.
Data is exported to the CFX file from one flow run. The file includes data from the configuration, current readings, alarm log, event log and hourly history log.
When this option is selected the Export Data to CFX dialog is opened when the Finish button is clicked.
The CFX Export Setting button opens the CFX Export Settings dialog.
The parameters for this dialog are described in the CFX Export Settings section below.
Select Export to CSV format file to export the logs and history to a CSV
(comma-separated values) format file. This format can be read by spreadsheet and database software.
When this option is selected the Export Data to CSV dialog is opened when the Finish button is clicked.
The CSV Export Setting button opens the CSV Export Settings dialog.
The parameters for this dialog are described in the CSV Export Settings section below.
Select No, Do not export to skip the Export Data step.
When this option is selected the dialog is closed and the Read Logs
Flow History wizard is ended when the Finish button is clicked.
Realflo User and Reference Manual
May 19, 2011
136
Export Data to CFX
Realflo Maintenance Mode Reference
Select All Alarms, Events and Hourly Logs to select all of the data in the flow run. This is the default button.
Select Selected Days to select the data from the contract days in the From and To dropdown lists.
The From dropdown list selects the oldest contract day. This control is enabled when the Selected Days radio button is selected.
The To dropdown list selects the recent contract day. This control is enabled when the Selected Days radio button is selected.
The Export Type dropdown list selects how export files are stored.
Select Specific File to export to a single file. A standard file save dialog opens to allow you to select the file name. The default file name is
<Realflo file name>(<FC ID>) - <Run Number> (<Run ID>).CFX.
Select Dated CFX to export one file per day to a single folder per run.
Realflo exports one file for each day. The file name is based on the time and date according to the CFX standard (YYYYMMDD.CFX).
Realflo User and Reference Manual
May 19, 2011
137
Save CFX Export
Realflo Maintenance Mode Reference
Select Save to File name.CFX to save the CFX Export data to the currently opened file. The name of the current file is shown in place of file name.CFX.
The files that that will be created are shown in the display window.
Select Save to another file to save the CFX Export data to a different file name and location. Enter the name in the window or select Browse to open the Save As dialog and select a name and location.
The Save As dialog allows you to specify the file to export the data to.
The Save button exports the data to the selected file.
The Cancel button the export command and closes the dialogs.
Click the Next> button to complete the Read Logs and Flow history wizard and close the dialog.
Realflo User and Reference Manual
May 19, 2011
138
Export Data to CSV
Realflo Maintenance Mode Reference
Save CSV Export
Select Hourly history to export the hourly history data.
Select Daily history to export the daily history data.
Select Alarm log to export the alarm log data.
Select Event log to export the event log data.
The Next> button moves to the Save CSV Export step in the wizard.
Select Save to File name.CSV to save the CSV Export data to the currently opened file. The name of the current file is shown in place of file name.CSV.
The files that that will be created are shown in the display window.
Realflo User and Reference Manual
May 19, 2011
139
Realflo Maintenance Mode Reference
Select Save to another file to save the CSV Export data to a different file name and location. Enter the name in the window or select Browse to open the Save As dialog and select a name and location.
You may change the file name to any suitable name. The suggested file name format is defined in the CSV Export Options command.
The Save As file selection dialog appears for views. The Save As dialog allows you to specify the file to export the data to.
The Save button in the Save As dialog exports the data to the selected file.
The Cancel button in the Save As dialog cancels the export command and closes dialogs.
Export PEMEX Report to CSV
This option is only available in the PEMEX version of Realflo.
Select Run number to export the history data for a specific meter run.
Select Hourly history to export the history data.
Select Data to specify the dates for which to export the history data. .
Click OK to open the Save As dialog.
Click Save to save the hourly history data.
Realflo User and Reference Manual
May 19, 2011
140
Realflo Maintenance Mode Reference
CFX Export Settings
The CFX Export Options dialog sets options for exporting to Flow-Cal CFX files. The settings in this dialog apply to files opened by Realflo. They are stored in the Windows registry.
The Hourly History section defines how records from the hourly history are exported.
Select Export Partial Hour Records to export the records as they appear in Realflo. Some hours may contain more than one record due to power cycling or configuration changes. This is the default selection.
Select Export One Record per Hour to export only one record per hour. Multiple records within an hour are merged into a single record for exporting. Hours that are not yet complete are not merged or exported.
The following hourly record fields are summed: volume, mass, energy, pulses (turbine type).
The following hourly record fields are averaged: termperature, static pressure, differential pressure (orifice types), relative density, flow product
or flow extension. See Input Averaging on page 948 for more information.
Select Time Leads Data Format to export the date and time at the start of the period. The time stamp on the record is the time at the start of the hour, even if the first record to be merged started later than that time.
Realflo User and Reference Manual
May 19, 2011
141
Realflo Maintenance Mode Reference
This option is enabled only when Export One Record per Hour is checked. This option is unchecked by default.
The File Description section defines some descriptive parameters in the
CFX file.
Meter Number defines the meter number parameter. The options are
none, Flow Computer ID, Flow Run ID and Flow Run Number. The default value is Flow Computer ID. The parameter is 17 characters long in the file.
Meter Name defines the meter name parameter. The options are none,
Flow Computer ID, Flow Run ID and Flow Run Number. The default value is Flow Run ID. The parameter is 49 characters long in the file.
Serial Number defines the meter serial number parameter in the file.
The options are none, Flow Computer ID, Flow Run ID and Flow Run
Number. The default value is Flow Run Number. The parameter is 11 characters long in the file.
The Live Inputs Flags section defines which live input flags are set by
Realflo. The CFX file contains four flags in the Live Inputs parameter.
Realflo sets the T (temperature) flag to Y (live data). The other flags are normally set to N (not live), but can be modified using the following options.
Check Set Live Gas Composition Flag when there is a program that updates the gas composition. This is flag A (analysis). This option is unchecked by default.
Check Set Live Energy Flag when there is a program that updates the energy. This is flag B (heating value). This option is unchecked by default.
Check Set Live Gravity Flag when there is a program that updates the specific gravity (relative density). This is flag G (gravity). This option is unchecked by default.
The Default Name Format section defines what file names Realflo suggests when exporting. The names are combinations of the file name;
Flow Computer ID; flow run number; and flow run ID.
Format selects the name format. The valid values are listed below. The default is to include the file name; Flow Computer ID; flow run number; and flow run ID. o file name (Flow Computer ID) - Run# (run ID) o file name (Flow Computer ID) - Run# o file name (Flow Computer ID) - run ID o file name - Run# (run ID) o file name - Run# o file name - run ID o Flow Computer ID - Run# (run ID) o Flow Computer ID - Run# o Flow Computer ID - run ID o Run# (run ID) o run ID
Realflo User and Reference Manual
May 19, 2011
142
Realflo Maintenance Mode Reference
The Example control shows the file name that will be suggested for the current file.
The Dated CFX section defines where and how CFX files are exported.
Select Use .CFX extension on folder names to create folders with a
CFX extension when exporting Dated CFX files. The data for each month is stored in its own folder when using the Dated CFX format. The folder name may have a CFX extension or not. This option is unchecked by default.
Select Export Dated CFX Files to the Folder to define a common folder for exports. Exported data is placed in this folder. The option is unchecked by default. When checked, the edit control holds the destination folder that will appear in the Save As dialog. Use Browse to search for another folder.
CSV Export Settings
The CSV Export Options command defines whether optional data is exported to CSV files. The settings in this dialog apply to files opened by
Realflo. They are stored in the Windows registry.
The Hourly and Daily Records section of the dialog defines optional data to include and how the data is time stamped.
Select the Include Uncorrected Flow in AGA-7 Export option to export the Uncorrected Data column from the Hourly History Log and
Daily History Log. This option applies to AGA-7 only. The option is unchecked by default.
Select the Export in Time Leads Data Format option to export time stamps that mark the start of the period. Uncheck the option to export time stamps that mark the end of the period (Realflo format). This applies to the the Hourly History and Daily History only. The control is unchecked by default.
The Default File Name Format section defines the file name that is suggested by Realflo when data is exported. The names are combinations of the file name; Flow Computer ID; flow run number; and flow run ID.
The Format list selects the name format. The name is made up of the identifier format and a view format. The valid values for the identifier are listed below. The default is to include the file name; Flow Computer ID; flow run number; and flow run ID.
Realflo User and Reference Manual
May 19, 2011
143
Realflo Maintenance Mode Reference o file name (Flow Computer ID) - Run# (run ID) - Type o file name (Flow Computer ID) - Run# - Type o file name (Flow Computer ID) - run ID - Type o file name - Run# (run ID) - Type o file name - Run# - Type o file name - run ID - Type o Flow Computer ID - Run# (run ID) - Type o Flow Computer ID - Run# - Type o Flow Computer ID - run ID - Type o Run# (run ID) - Type o run ID - Type
When the logs are exported the word Type is replaced by the following, according to the export selected. o Alarms o Events o Hourly Log o Daily Log o Current Readings o Custom View Name
The Example control shows the file name that will be suggested for the current file.
Realflo User and Reference Manual
May 19, 2011
144
Realflo Maintenance Mode Reference
Maintenance
The Maintenance section of the Realflo main page contains Calibrate
Inputs, Change Orifice Plate and Force Inputs buttons.
Click the Calibrate Inputs button to start the Calibrate Inputs wizard, which will lead you through the steps to connect to a flow computer and calibrate the measurement inputs.
Click the Change Orifice Plate button to start the Change Orifice Plate wizard, which will lead you through the steps to connect to a flow computer and change the orifice plate for a meter run.
Click the Force Inputs button to start the Force Inputs wizard, which will lead you through the steps to connect to a flow computer and force the inputs.
Connections for SCADAPack Sensor Calibration
It should be noted that when an Absolute (Static) Pressure calibration is performed the bypass or cross feed valve on the manifold needs to be open.
When performing a Differential Pressure calibration the bypass valve needs to be closed.
Differential Pressure Calibration Connections
Realflo User and Reference Manual
May 19, 2011
145
Absolute Pressure Calibration Connections
Realflo Maintenance Mode Reference
Calibrate Inputs
The Calibrate Inputs wizard is used to calibrate the temperature sensor, static pressure sensor, and differential pressure sensor or pulse counter input. The calibration dialogs lead you through the calibration procedure.
When more than one sensor is selected, they are forced and then the calibration cycle will be allowed for each sensor in turn. This allows multiple variable transmitters such as the MVT to be calibrated.
WARNING
The same input sensor can be used for more than one flow run. When the sensor is calibrated for one run, Realflo only forces the input value for that run. When the sensor is disconnected to do the calibration, the live input to the other run will be disconnected and the value will not be correct. The flow computer does not support forcing of inputs during calibration on more than one run.
For each step in the wizard a dialog is presented to enter the parameters for the step. Each dialog contains four buttons to allow navigation through the wizard.
<Back returns to the previous step in the wizard. This button is disabled on the first step of a wizard.
Next> moves to the next step in the wizard. This button is hidden on the last step of a wizard.
Finish is displayed on the final step of a wizard in place of the Next button. It finishes the operation. This button is hidden on other steps.
Cancel cancels the operation and closes the wizard. Steps performed thus far in the wizard are cancelled. Pressing the ESC key performs the same action as Cancel.
Help opens the user manual.
Realflo User and Reference Manual
May 19, 2011
146
Realflo Maintenance Mode Reference
Connect to Flow Computer
The connect to flow computer step defines the communication settings for the connection between the PC running the Realflo application and the target flow computer.
The How do you want to communicate with the flow computer? prompt provides two selections.
The Use the Current Settings option sets the default communication settings for Realflo. These settings are for the PC that is running Realflo.
(The communication settings for the PC running Realflo and the communication settings in the flow computer need to match).
The default communication settings are:
COM 1 (serial port on the PC)
9600 baud
no parity
8 Data bits
1 Stop bit
The default Modbus address Realflo will connect to is station 1.
Use this selection if the serial port on your PC is COM 1 and the serial port settings for the serial port on the flow computer are set for default (9600,
8,n,1 and Modbus address 1).
Click the Next> button to begin communication with the flow computer and move to the next step in the wizard.
The Choose/View Communication Setup option opens the PC
Communication Settings dialog as shown below. This allows you to view the default settings and to change the PC communication setting for the type of connection you are using to communicate with the flow computer.
Realflo User and Reference Manual
May 19, 2011
147
Realflo Maintenance Mode Reference
See the section Communication >> PC Communication Settings
Command in the Realflo Expert Mode Reference section of this manual for complete details on the parameter settings in this dialog.
You need to know the communication settings for the connection to the flow computer to use this step.
Once the communication settings have been selected click the OK> button to close the dialog and begin communication with the flow computer.
Realflo User and Reference Manual
May 19, 2011
148
Realflo Maintenance Mode Reference
Sensor Calibration
When the Calibration command is selected the Sensor Calibration dialog is displayed. The Run, or Sensor, to be calibrated is selected from this dialog.
This dialog allows the selected meter run or Sensor to be calibrated.
Select the Run radio button and then select a meter run to calibrate.
Transmitters used for the meter run may be calibrated. This section is disabled if every run is using external sensors.
Select the Sensor radio button and select one of the tags to calibrate a
Sensor or Transmitter. The tags that have been configured will be in
Sensor selection box.
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log.
The back button is not enabled on the first step since there is no previous step.
The Next> button starts the calibration procedure. After the Run, or sensor, is selected, the configuration for the run is read from the flow computer. The
Run, or sensor calibration page for the run is then displayed.
The Cancel button closes the dialog and stops the transmitter calibration.
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
Realflo User and Reference Manual
May 19, 2011
149
Realflo Maintenance Mode Reference
WARNING
Realflo uses live values from the sensor when calibration is cancelled.
Connect sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Realflo User and Reference Manual
May 19, 2011
150
Realflo Maintenance Mode Reference
Run Calibration Procedure
When the Run radio button is selected the Run Calibration dialog is displayed. The transmitters for the run are selected for calibration from this dialog.
WARNING
Realflo uses live values from the sensor when calibration is cancelled.
Connect sensors first.
The same input sensor can be used for more than one flow run. When the sensor is calibrated for one run, Realflo only forces the input value for that run. When the sensor is disconnected to do the calibration, the live input to the other run will be disconnected and the value will not be correct. The flow computer does not support forcing of inputs during calibration on more than one run.
Select the sensors to be calibrated by checking the appropriate boxes. More than one sensor may be selected for calibration.
The <Back button is not enabled as this is the initial step.
The Next> button completes the selections and opens the Step 1: Force
Value dialog.
The Cancel button closes the dialog and stops the transmitter calibration.
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
Realflo User and Reference Manual
May 19, 2011
151
Realflo Maintenance Mode Reference
WARNING
Realflo uses live values from the sensor when calibration is cancelled.
Connect sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Calibration Step 1: Force Value
The flow calculations continue to execute while calibrating sensors. The sensor value needs to be forced to either the current value or a fixed value during calibration. This dialog lets you select the current value of the input or a fixed value of your choice.
If a sensor was forced before starting the execution of a calibration, the sensor will remain in a forced state after the calibration process is completed or even if the calibration process is cancelled before completion.
When more than one sensor is selected, they need to be forced to a current or fixed value before any of the other steps are performed. A Step 1: Force
Value dialog will be presented for each sensor selected for calibration.
The input register associated with this input is displayed to aid you in determining which input you are calibrating.
Check the Current Value radio button to use the current value for the sensor.
Realflo User and Reference Manual
May 19, 2011
152
Realflo Maintenance Mode Reference
Check the Fixed Value radio button and enter a value to use for the calibration in the entry box.
The No Change radio button will be selected if the value is currently forced. (You may still select one of the other two radio buttons if desired).
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log.
When the Next> button is pressed Realflo records the start of calibration for the sensor in the event log. The sensor input is forced. The sensor may now be disconnected from the process.
The Cancel button closes the dialog and stops the transmitter calibration.
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
WARNING
Realflo uses live values from the sensor when calibration is cancelled. Be sure to connect sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Calibration Step 2: Record As Found Values
Realflo User and Reference Manual
May 19, 2011
153
Realflo Maintenance Mode Reference
As-found readings indicate how the sensor was calibrated before adjustment. These can be used to correct flow measurement errors resulting from an out of calibration sensor. Follow the procedure your company has set for taking as-found readings. You need to record at least one as-found reading.
To take as-found readings:
Apply a known signal to the sensor, or measure the signal applied to the sensor with a calibrated instrument.
Enter the applied value in the Applied Value edit box.
Check the measured value from the process in the Measured Value box. When it has settled, click on the Record button to record an asfound reading.
Repeat the process to record additional readings.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For Run Calibration the deviation is calculated as follows. The output full scale and zero scale are taken from the input configuration for the run. span = input full scale – input zero scale deviation = (measured - applied) / span
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log.
The Next> button proceeds to the next step.
The Cancel button is greyed and an as found reading needs to be recorded.
Realflo User and Reference Manual
May 19, 2011
154
Realflo Maintenance Mode Reference
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
WARNING
Realflo uses live values from the sensor when calibration is cancelled.
Connect sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Calibration Step 3: Calibration Required
The as-found readings indicate if calibration is required. Examine the list of as-found readings. If the sensor is in need of calibration, select Yes.
Otherwise select No.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The
Realflo User and Reference Manual
May 19, 2011
155
Realflo Maintenance Mode Reference measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For Run Calibration the deviation is calculated as follows. The output full scale and zero scale are taken from the input configuration for the run. span = input full scale – input zero scale deviation = (measured - applied) / span
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log.
The Next> button proceeds to the next step.
The Cancel button is greyed and an as found reading needs to be recorded.
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
WARNING
Realflo uses live values from the sensor when calibration is cancelled.
Connect sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Calibration Step 4: Calibrate Sensor
Realflo User and Reference Manual
May 19, 2011
156
Realflo Maintenance Mode Reference
This dialog aids you in calibrating a sensor by displaying the measured value from the sensor and the as-found readings.
Follow the procedure your company or the sensor supplier has set to calibrate the sensor. When the sensor calibration is complete, you may wish to check the as-left measurements that will be recorded in the next step.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For Run Calibration the deviation is calculated as follows. The output full scale and zero scale are taken from the input configuration for the run. span = input full scale – input zero scale deviation = (measured - applied) / span
Click on the Next> button when the calibration is complete.
Calibration Step 5: Record As Left Values
As-left readings indicate how the sensor was calibrated. These can be used to verify sensor calibration. Follow the procedure your company has set for taking as-left readings. You need to record at least one as-left reading.
Realflo User and Reference Manual
May 19, 2011
157
Realflo Maintenance Mode Reference
To take as-left readings:
Apply a known signal to the sensor, or measure the signal applied to the sensor with a calibrated instrument.
Enter the applied value in the Applied Value edit box.
Check the measured value from the process. When it has settled, click on the Record button to record an as-left reading.
Repeat the process to record additional readings.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For Run Calibration the deviation is calculated as follows. The output full scale and zero scale are taken from the input configuration for the run. span = input full scale – input zero scale deviation = (measured - applied) / span
When required readings are taken, click on the Next> button.
Calibration Step 6: Restore Live Input
The sensors need to be reconnected to the process and the input hardware before calibration is complete. Reconnect sensors and verify connections are correct.
Realflo User and Reference Manual
May 19, 2011
158
Realflo Maintenance Mode Reference
Click on the Next button when the sensor is connected.
WARNING
Realflo uses live values from the sensor when calibration is cancelled.
Connect sensors first.
Calibration Step 6: Calibration Report Comment
Realflo User and Reference Manual
May 19, 2011
159
Realflo Maintenance Mode Reference
Realflo creates, stores, and prints calibration reports for each calibration session performed. Comments may be added to the calibration report using the Calibration Report Comment dialog as shown below.
Enter any comments or leave the window blank.
Click the Next button when completed entering comments.
Calibration Step 7: Calibration Report
The Calibration Report dialog allows the saving of the calibration report.
Select Save Report to File to save the report.
Realflo User and Reference Manual
May 19, 2011
160
Realflo Maintenance Mode Reference
Type the name of the report in the Save Report to File window. The default location and name are specified on the Calibration Report
Options dialog.
Select Browse to select a different file name.
Check View Calibration Report After Saving the File to view the saved calibration report file. Default is checked.
Select Do not Save Report to skip saving the calibration report.
Click the Finis button to complete the calibration process.
If selected the Calibration report will be displayed as shown below.
Realflo User and Reference Manual
May 19, 2011
161
Realflo Maintenance Mode Reference
Sensor Calibration Procedure
When the Sensor radio button is selected in the Sensor Calibration dialog the Sensor Calibration dialog is displayed.
The transmitter number, transmitter tag name, the communication port and the transmitter address associated with this sensor are displayed to aid you in determining which input you are calibrating.
Check the Calibrate Temperature Sensor check box to select the temperature sensor for calibration. This will add the Temperature to the
Calibration order list box.
Check the Calibrate Static Pressure Sensor check box to select the static pressure sensor for calibration. This will add the Static Pressure to the Calibration order list box.
Check the Calibrate Differential Pressure Sensor check box to select the differential pressure sensor for calibration. This will add the Diff.
Pressure to the Calibration order list box.
The Calibration Order list displays the list of sensors to be calibrated.
Sensors are calibrated in order from the top of the list.
Select Move Up button to move the specified item in the list up. The button is disabled if highlight item is on the top of the list or the list is empty.
Select Move Down button to move the specified item in the list down.
The button is disabled if highlight item is on the bottom of the list or the list is empty.
The <Back button is not enabled as this is the initial step.
The Next> button completes the selections and opens the Step 1: Force
Value dialog.
The Cancel button closes the dialog and stops the transmitter calibration.
Realflo User and Reference Manual
May 19, 2011
162
Realflo Maintenance Mode Reference
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
WARNING
Realflo uses live values from the sensor when calibration is cancelled.
Connect sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Calibration Step 1: Force Value
The flow calculations continue to execute while calibrating sensors. The sensor value needs to be forced to either the current value or a fixed value during calibration. This dialog lets you select the current value of the input or a fixed value of your choice.
If a sensor was forced before starting the execution of a calibration, the sensor will remain in a forced state after the calibration process is completed or even if the calibration process is cancelled before completion.
When more than one sensor is selected, they need to all be forced to a current or fixed value before any of the other steps are performed.
Realflo User and Reference Manual
May 19, 2011
163
Realflo Maintenance Mode Reference
Realflo User and Reference Manual
May 19, 2011
Select the value you wish to use, for each sensor, by clicking the appropriate radio button for each sensor.
Check the Current Value radio button to use the current value for the sensor.
Check the Fixed Value radio button and enter a value to use for the calibration in the entry box.
The No Change radio button will be selected if the value is currently forced. (You may still select one of the other two radio buttons if desired).
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log.
When the Next> button is pressed Realflo records the start of calibration for the sensor in the event log. The sensor input is forced. The sensor may now be disconnected from the process.
The Cancel button closes the dialog and stops the transmitter calibration.
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
164
Realflo Maintenance Mode Reference
WARNING
Realflo uses live values from the sensor when calibration is cancelled.
Connect sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Calibration Step 2: Record As- Found Values
As-found readings indicate how the sensor was calibrated before adjustment. These can be used to correct flow measurement errors resulting from an out of calibration sensor. Follow the procedure your company has set for taking as-found readings. You need to record at least one as-found reading.
Realflo will record As Found values to the unit type selected for the meter run. If the units type for the meter run and the MVT are not the same then the MVT units are scaled to the meter run units.
To take as-found readings:
Apply a known signal to the sensor, or measure the signal applied to the sensor with a calibrated instrument.
Enter the applied value in the Applied Value edit box.
Check the measured value from the process in the Measured Value box. When it has settled, click on the Record button to record an asfound reading.
Repeat the process to record additional readings.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The
Realflo User and Reference Manual
May 19, 2011
165
Realflo Maintenance Mode Reference measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For MVT Calibration the deviation is calculated as follows. The operating limits are read from the flow computer. span = upper range limit - lower range limit deviation = (measured - applied) / span
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log.
The Next> button proceeds to the next step.
The Cancel button is greyed and an as found reading needs to be recorded.
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
WARNING
Realflo uses live values from the sensor when calibration is cancelled.
Connect sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Calibration Step 3: Calibration Required
Realflo User and Reference Manual
May 19, 2011
166
Realflo Maintenance Mode Reference
The as-found readings indicate if calibration is required. Examine the list of as-found readings. If the sensor is in need of calibration, select Yes.
Otherwise select No.
Realflo User and Reference Manual
May 19, 2011
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For Run Calibration the deviation is calculated as follows. The output full scale and zero scale are taken from the input configuration for the run. span = input full scale – input zero scale deviation = (measured - applied) / span
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log.
The Next> button proceeds to the next step.
The Cancel button is greyed and an as found reading needs to be recorded.
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
167
Realflo Maintenance Mode Reference
WARNING
Realflo uses live values from the sensor when calibration is cancelled.
Connect sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Calibration Step 4: Calibrate SCADAPack 4102, 4202, or 4203
Step three in the calibration procedure varies depending on the type of transmitter being calibrated. Use this section if you are calibrating a
SCADAPack 4102, 4202 or 4203 transmitter. Use the Calibration Step 4:
Calibrate 4101 for the SCADAPack 4101 transmitter and use Calibration
Step 4: Calibrate 3905 for the 3095 transmitter.
This dialog aids you in calibrating a sensor by displaying the measured value from the sensor and the as-found readings.
Follow the procedure your company or the sensor supplier has set to calibrate the sensor. When the sensor calibration is complete, you may wish to check the as-left measurements that will be recorded in the next step..
The Static Pressure can only have a span calibration performed if at least 5% of the rated pressure is applied.
The RTD Zero can only be adjusted +/- 1% of the RTD upper limit, typically 8.5 degrees C, relative to the settings used when a reset sensor command was last issued.
The list box displays as-found values listed in the list of Record As-Found
Values dialog.
The Measured Value displays the measured value from the sensor.
Realflo User and Reference Manual
May 19, 2011
168
Realflo Maintenance Mode Reference
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For MVT Calibration the deviation is calculated as follows. The operating limits are read from the flow computer. span = upper range limit - lower range limit deviation = (measured - applied) / span
Calibration Step 4: Calibrate SCADAPack 4101
Step three in the calibration procedure varies depending on the type of transmitter being calibrated. Use this section if you are calibrating a
SCADAPack 4101, 4202 or 4203 transmitter.
The as-found readings, for each sensor, will indicate if calibration is required for the sensor. You are prompted to use the SCADAPack 4000 Configurator application to perform the calibration. The SCADAPack 4000 Configurator software is installed from the Control Microsystems Hardware
Documentation CD.
The Next> button proceeds to the next step.
The Help button displays the online help file.
Calibration Step 4: Calibrate 3095 MVT
Realflo User and Reference Manual
May 19, 2011
169
Realflo Maintenance Mode Reference
Step four in the calibration procedure varies depending on the type of transmitter being calibrated. Use this section if you are calibrating a 3095
MVT transmitter.
This dialog aids you in calibrating a sensor by displaying the measured value from the sensor and the as-found readings.
Follow the procedure your company or the sensor supplier has set to calibrate the sensor. When the sensor calibration is complete, you may wish to check the as-left measurements that will be recorded in the next step.
The list box displays as-found values listed in the list of Record As-Found
Values dialog.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For MVT Calibration the deviation is calculated as follows. The operating limits are read from the flow computer. span = upper range limit - lower range limit deviation = (measured - applied) / span
The Calibrate Sensor section of the Calibrate Sensor dialog displays the current calibration settings and selectable radio buttons for configuring the sensor calibration.
The Radio buttons enable the changing of the zero and span for the
Temperature, Static Pressure and Differential Pressure sensors. For
Temperature sensors, an additional radio button allows the user to fix the
Temperature value in the event the temperature reading is outside the configured limits.
Select the Re-Zero radio button to enable a new entry in the Applied
Value field. This field displays the current zero value. The button is labeled Re-Zero if the Re-Zero radio button is selected. Clicking the
Re-Zero button writes the zero applied value to the transmitter immediately.
Realflo User and Reference Manual
May 19, 2011
170
Realflo Maintenance Mode Reference
Select the Calculate Span radio button to enable a new entry in the
Applied Value field. This field displays the current span value. The button is labeled Calibrate if the Calibrate Span radio button is selected. Clicking the Calibrate button writes the span applied value to the transmitter immediately.
When calibrating the temperature sensor you may select the Default
Temperature radio button to enable a new entry in the Applied Value field.
The button is labeled Set if the Default Temperature radio button is selected. The transmitter returns the fixed temperature value if the RTD is not working, or if the RTD is not connected. The valid range is
–40 to 1200
F or
–40 to 648.89
C. The default value is 60
F or 15.56
C. The new fixed temperature point is written to the transmitter immediately.
The Measured Value displays the measured value from the sensor.
Realflo records the points at which MVT calibration was performed in the event log.
Each time the Re-Zero button is clicked the following information is recorded.
Event Name
New Value
Previous Value
Target Re-zero Temperature
The applied value entered by the user
The measured value from the flow computer
Each time the Calibrate button is clicked the following information is recorded.
Event Name
New Value
Previous Value
Target Temperature Span
The applied value entered by the user
The measured value from the flow computer
Each time the Set Default button is clicked the following information is recorded.
Event Name
New Value
Previous Value
Set Default Temperature
The applied value entered by the user
The measured value from the flow computer
Calibration Step 4: Record As Left Values
Realflo User and Reference Manual
May 19, 2011
171
Realflo Maintenance Mode Reference
As-left readings indicate how the sensor was calibrated. These can be used to verify sensor calibration. Follow the procedure your company has set for taking as-left readings. You need to record at least one as-left reading.
Realflo will record As Found values to the units type selected for the meter run. If the units type for the meter run and the MVT are not the same then the MVT units are scaled to the meter run units.
To take as-left readings:
Apply a known signal to the sensor, or measure the signal applied to the sensor with a calibrated instrument.
Enter the applied value in the Applied Value edit box.
Check the measured value from the process. When it has settled, click on the Record button to record an as-left reading.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For MVT Calibration the deviation is calculated as follows. The operating limits are read from the flow computer. span = upper range limit - lower range limit deviation = (measured - applied) / span
Repeat the process to record additional readings.
When required readings are taken, click on the Next> button.
Calibration Step 5: Restore Live Input
Realflo User and Reference Manual
May 19, 2011
172
Realflo Maintenance Mode Reference
The sensors need to be reconnected to the process and the input hardware before calibration is complete. Reconnect sensors and verify connections are correct.
Click on the Finish button when the sensor is connected.
WARNING
The live value from sensors is used as soon as the Finish button is clicked.
Connect sensors first.
Calibration Step 6: Calibration Report Comment
Realflo User and Reference Manual
May 19, 2011
173
Realflo Maintenance Mode Reference
Realflo creates, stores, and prints calibration reports for each calibration session performed. Comments may be added to the calibration report using the Calibration Report Comment dialog as shown below.
Enter any comments or leave the window blank.
Click the Next button when completed entering comments.
Calibration Step 7: Calibration Report
The Calibration Report dialog allows the saving of the calibration report.
Select Save Report to File to save the report.
Realflo User and Reference Manual
May 19, 2011
174
Realflo Maintenance Mode Reference
Type the name of the report in the Save Report to File window. The default location and name are specified on the Calibration Report
Options dialog.
Select Browse to select a different file name.
Check View Calibration Report After Saving the File to view the saved calibration report file. Default is checked.
Select Do not Save Report to skip saving the calibration report.
Click the Finis button to complete the calibration process.
If selected the Calibration report will be displayed as shown below.
Change Orifice Plate
The Change Orifice Plate wizard enables the orifice plate to be changed for
AGA-3 meter runs. This wizard supports Dual Chamber Orifice fittings and
Singe Chamber Orifice fittings. This wizard will prompt you through the plate change procedure.
For each step in the wizard a dialog is presented to enter the parameters for the step. Each dialog contains four buttons to allow navigation through the wizard.
<Back returns to the previous step in the wizard. This button is disabled on the first step of a wizard.
Next> moves to the next step in the wizard. This button is hidden on the last step of a wizard.
Finish is displayed on the final step of a wizard in place of the Next button. It finishes the operation. This button is hidden on other steps.
Cancel cancels the operation and closes the wizard. Steps performed thus far in the wizard are cancelled. Pressing the ESC key performs the same action as Cancel.
Help opens the user manual.
Realflo User and Reference Manual
May 19, 2011
175
Realflo Maintenance Mode Reference
Connect to Flow Computer
The connect to flow computer step defines the communication settings for the connection between the PC running the Realflo application and the target flow computer.
The How do you want to communicate with the flow computer? prompt provides two selections.
The Use the Current Settings option sets the default communication settings for Realflo. These settings are for the PC that is running Realflo.
(The communication settings for the PC running Realflo and the communication settings in the flow computer need to match).
The default communication settings are:
COM 1 (serial port on the PC)
9600 baud
no parity
8 Data bits
1 Stop bit
The default Modbus address Realflo will connect to is station 1.
Use this selection if the serial port on your PC is COM 1 and the serial port settings for the serial port on the flow computer are set for default (9600,
8,n,1 and Modbus address 1).
Click the Next> button to begin communication with the flow computer and move to the next step in the wizard.
The Choose/View Communication Setup option opens the PC
Communication Settings dialog as shown below. This allows you to view the default settings and to change the PC communication setting for the type of connection you are using to communicate with the flow computer.
Realflo User and Reference Manual
May 19, 2011
176
Realflo Maintenance Mode Reference
See the section Communication >> PC Communication Settings
Command in the Realflo Expert Mode Reference section of this manual for complete details on the parameter settings in this dialog.
You need to know the communication settings for the connection to the flow computer to use this step.
Once the communication settings have been selected click the OK> button to close the dialog and begin communication with the flow computer.
Realflo User and Reference Manual
May 19, 2011
177
Select Meter Run
Realflo Maintenance Mode Reference
This step selects which meter run the orifice plate is to be changed.
The Run dropdown selection displays runs using AGA
–3 flow calculations.
Select the run to change or inspect the orifice plate.
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log. Realflo does not attempt to reverse the effect of a previous step when backing up. For example, backing up to the force values step does not restore the live values.
The Next> button completes the run selection and the wizard moves to the next step. This button is greyed if there are no flow runs configured to use the AGA-3 flow calculation.
The Cancel button aborts the plate change and displays the following message.
Click Yes to abort the calibration.
Click No to continue with the plate change. The default button is No.
WARNING
Realflo uses live values from the sensor when the plate change is cancelled.
Realflo User and Reference Manual
May 19, 2011
178
Realflo Maintenance Mode Reference
Connect sensors first.
Realflo does not erase any events from the flow computer when the plate change is cancelled. Realflo restores live values (ends forcing) when Cancel is clicked.
The Help button displays the online help file.
Realflo User and Reference Manual
May 19, 2011
179
Realflo Maintenance Mode Reference
Choose Orifice Fitting Type Step
This page allows the user to select the type of orifice fitting.
Select Dual Chamber Orifice Fitting if a dual chamber fitting is present.
Flow accumulation with estimated values will continue during the plate change.
Select Singe Chamber Orifice Fitting if a single chamber fitting is present.
Flow accumulation will stop during the plate change.
The Next button moves to the next step.
The next step is described in the section
dual chamber fitting is selected.
The next step is described in the section
single chamber fitting is selected.
The Cancel button closes the dialog and stops the plate change procedure.
The Help button displays the online Help file.
Realflo User and Reference Manual
May 19, 2011
180
Realflo Maintenance Mode Reference
Dual Chamber Orifice
A dual chamber orifice allows the user to change, or inspect, the orifice plate without stopping the flow. These are generally large custody transfer sites where the orifice fitting is bypassed during the change or inspection procedure.
The Change Orifice Plate Command forces the Static Pressure, Differential
Pressure and Temperature inputs to a fixed value during the orifice plate change or inspection procedure. This command is disabled if the Update
Readings command is enabled. The flow is estimated during the procedure using the fixed values.
This command allows a user to place a flow run into estimation mode to allow an orifice plate to be changed or inspected. Changing the orifice plate involves the following steps.
Set the estimated flow to be used during the orifice plate change by forcing inputs to fixed values.
Change the orifice size.
Complete the orifice plate change and resume normal flow measurement.
The Flow Computer ID is checked when the Change Orifice Plate command is selected. If the Flow Computer ID does not match the ID Realflo displays the message “ The Flow Computer ID from the flow computer does not match the Flow Computer ID from the file
.” The command is aborted.
Force Input Step
This step forces the flow run inputs. An estimated flow will be calculated while the plate change is in progress. The current values are updated every second.
Select the value you wish to use, for each sensor, by clicking the appropriate radio button for each sensor.
Realflo User and Reference Manual
May 19, 2011
181
Realflo Maintenance Mode Reference
Check the Current Value radio button to use the current value for the sensor.
Check the Fixed Value radio button and enter a value to use for the calibration in the entry box.
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log. Realflo does not attempt to reverse the effect of a previous step when backing up. For example, backing up to the force values step does not restore the live values.
The Next> button completes the force inputs step and the wizard moves to the next step. Realflo records the start of the plate change procedure in the event log and forces the sensor inputs.
The Cancel button aborts the plate change and displays the following message.
Click Yes to abort the calibration.
Click No to continue with the plate change. The default button is No.
WARNING
Realflo uses live values from the sensor when the plate change is cancelled.
Connect sensors first.
Realflo does not erase any events from the flow computer when the plate change is cancelled. Realflo restores live values (ends forcing) when Cancel is clicked.
The Help button displays the online help file.
Change Orifice Plate Step
Realflo User and Reference Manual
May 19, 2011
182
Realflo Maintenance Mode Reference
The orifice plate can now be changed. The forced inputs are used while the change is in progress. This dialog allows you to enter the new orifice plate diameter.
The Current Orifice Diameter and Current Pipe Diameter are displayed for reference.
Enter the new orifice size in the New Orifice Diameter entry box. If the diameter is not valid, Realflo displays the following a message box.
You need to enter a valid orifice diameter. Click the OK button to return to the Change Orifice dialog.
The Beta Ratio is calculated and displayed for orifice diameter changes.
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log. Realflo does not attempt to reverse the effect of a previous step when backing up. For example, backing up to the force values step does not restore the live values.
The Next> button completes the change orifice step and the wizard moves to the last step.
The Cancel button aborts the plate change and displays the following message.
Realflo User and Reference Manual
May 19, 2011
183
Realflo Maintenance Mode Reference
Click Yes to abort the calibration.
Click No to continue with the plate change. The default button is No.
WARNING
Realflo uses live values from the sensor when the plate change is cancelled.
Connect sensors first.
Realflo does not erase any events from the flow computer when the plate change is cancelled. Realflo restores live values (ends forcing) when Cancel is clicked.
The Help button displays the online help file.
Complete Orifice Plate Change
The Finish Plate Change is the last step in the Plate Change wizard.
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log. Realflo does not attempt to reverse the effect of a previous step when backing up. For example, backing up to the force values step does not restore the live values.
The Finish button completes the orifice plate change wizard and closes the dialog. Realflo restores the sensor live values
The Help button displays the online help file.
Realflo User and Reference Manual
May 19, 2011
184
Realflo Maintenance Mode Reference
Single Chamber Orifice
A single chamber orifice requires the flow be stopped while an orifice plate is changed.
The Change Orifice Plate command prompts the user to stop the flow before changing the plate and start the flow after changing the plate.
Changing the orifice plate involves the following steps.
Confirm that flow has stopped.
Change the orifice size.
Complete the orifice plate change.
The Flow Computer ID is checked when the Change Orifice Plate command is selected. If the Flow Computer ID does not match the ID Realflo displays the message “ The Flow Computer ID from the flow computer does not match the Flow Computer ID from the file.
” The command is aborted.
Stop Flow Step
This step stops the flow run. The current inputs can be monitored while the flow is stopped.
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log. Realflo does not attempt to reverse the effect of a previous step when backing up. For example, backing up to the force values step does not restore the live values.
The Next> button completes the Stop Flow step and the wizard moves to the next step. Realflo records the start of the plate change procedure in the event log and forces the sensor inputs.
The Cancel button aborts the plate change and closes the wizard.
The Help button displays the online help file.
Realflo User and Reference Manual
May 19, 2011
185
Realflo Maintenance Mode Reference
Change Orifice Plate Step
The orifice plate can now be changed. The forced inputs are used while the change is in progress. This dialog allows you to enter the new orifice plate diameter.
The Current Orifice Diameter and Current Pipe Diameter are displayed for reference.
Enter the new orifice size in the New Orifice Diameter entry box. If the diameter is not valid, Realflo displays the following a message box.
You need to enter a valid orifice diameter. Click the OK button to return to the Change Orifice dialog.
The Beta Ratio is calculated and displayed for orifice diameter changes.
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log. Realflo does not attempt to reverse the effect of a previous step when backing up.
The Next> button completes the change orifice step and the wizard moves to the last step.
The Cancel button aborts the plate change and closes the wizard.
The Help button displays the online help file.
Complete Orifice Plate Change
The Finish Plate Change is the last step in the Plate Change wizard.
Realflo User and Reference Manual
May 19, 2011
186
Realflo Maintenance Mode Reference
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log. Realflo does not attempt to reverse the effect of a previous step when backing up.
The Finish button completes the orifice plate change wizard and closes the dialog. Realflo restores the sensor live values
The Help button displays the online help file.
Force Inputs
The Force Sensor wizard allows forcing and unforcing of the value of the temperature sensor, static pressure sensor, differential pressure sensor, or pulse counter input. Flow calculations continue to execute while sensors are forced.
The flow computer ID is checked when the Force Inputs command is selected. If the flow computer ID does not match the ID in the dialog Realflo displays the error message “ The Flow Computer ID from the flow computer does not match the Flow Computer ID from the file.
” The command is aborted,
For each step in the wizard a dialog is presented to enter the parameters for the step. Each dialog contains four buttons to allow navigation through the wizard.
<Back returns to the previous step in the wizard. This button is disabled on the first step of a wizard.
Next> moves to the next step in the wizard. This button is hidden on the last step of a wizard.
Finish is displayed on the final step of a wizard in place of the Next button. It finishes the operation. This button is hidden on other steps.
Cancel cancels the operation and closes the wizard. Steps performed thus far in the wizard are cancelled. Pressing the ESC key performs the same action as Cancel.
Realflo User and Reference Manual
May 19, 2011
187
Realflo Maintenance Mode Reference
Help opens the user manual.
Connect to Flow Computer
The connect to flow computer step defines the communication settings for the connection between the PC running the Realflo application and the target flow computer.
The How do you want to communicate with the flow computer? prompt provides two selections.
The Use the Current Settings option sets the default communication settings for Realflo. These settings are for the PC that is running Realflo.
(The communication settings for the PC running Realflo and the communication settings in the flow computer need to match).
The default communication settings are:
COM 1 (serial port on the PC)
9600 baud
no parity
8 Data bits
1 Stop bit
The default Modbus address Realflo will connect to is station 1.
Use this selection if the serial port on your PC is COM 1 and the serial port settings for the serial port on the flow computer are set for default (9600,
8,n,1 and Modbus address 1).
Click the Next> button to begin communication with the flow computer and move to the next step in the wizard.
The Choose/View Communication Setup option opens the PC
Communication Settings dialog as shown below. This allows you to view the
Realflo User and Reference Manual
May 19, 2011
188
Realflo Maintenance Mode Reference default settings and to change the PC communication setting for the type of connection you are using to communicate with the flow computer.
See the section Communication >> PC Communication Settings
Command in the Realflo Expert Mode Reference section of this manual for complete details on the parameter settings in this dialog.
You need to know the communication settings for the connection to the flow computer to use this step.
Once the communication settings have been selected click the OK> button to close the dialog and begin communication with the flow computer.
Realflo User and Reference Manual
May 19, 2011
189
Realflo Maintenance Mode Reference
Select Run or Transmitter to Force
This step selects the run or transmitter to force.
Select Run to force the sensor inputs for a flow run using analog or pulse sensors. Select the run to be forced from the dropdown list. The Run controls are disabled if there are no runs using analog or pulse sensors.
below for information on forcing Run
inputs.
Select Sensor to force the inputs from an external transmitter. Select the sensor to be forced from the dropdown list beside it. The
„Sensor” control is disabled if there are no transmitters configured.
See the section Force Transmitter Sensor Inputs below for information on
forcing transmitter inputs.
The Back button is disabled, as this is the first step in the wizard.
The Next starts the force procedure.
The Cancel closes the wizard.
The Help displays the online help file.
Realflo User and Reference Manual
May 19, 2011
190
Force Run Inputs
Realflo Maintenance Mode Reference
When the Force Run is selected the Force Input Values dialog is displayed as shown below. The Force Input Values step selects the analog inputs of a flow run which will be forced or unforced. It displays the inputs that can be forced.
The Force Input Value dialog contains sections for Force Differential
Pressure Input, Force Static Pressure Input and Force Temperature Input.
When AGA-7 calculation type is used the dialog contains a section for Force
Pulse Counter Input instead of Force Differential Pressure Input.
For each input the following parameters are available:
Select Current Value to use the current value for the sensor. The current value is shown beside the control and updates continuously.
Select Fixed Value to use a fixed value. Type the value in the edit box.
Select No Change, input is already forced to leave the input in its current state. This is selected by default if the value is already forced.
This is disabled if the input is not forced.
Select Remove to remove the existing forcing. This button is disabled if the input is not forced.
The Back button moves back to the Select Run or Transmitter to Force step. Backing up does not erase events from the flow computer event log, or remove forcing from inputs previously processed.
The Finish button completes the Force Input Value process and closes the dialog.
Realflo User and Reference Manual
May 19, 2011
191
Realflo Maintenance Mode Reference
The Cancel button closes the wizard. This does not undo any changes. Any input that is already forced will remain forced.
The Help displays the online help file.
Force Sensor Inputs
This step shows the selected sensor inputs. The inputs can be forced to the current value or a fixed value, left as it is, or the forcing can be removed.
The transmitter number, transmitter tag name, the communication port and the transmitter address associated with this sensor transmitter are displayed to aid you in determining which input you are forcing.
The Sensor Values dialog contains sections for Force Differential Pressure,
Force Static Pressure and Force Temperature.
For each input the following parameters are available:
Select Current Value to use the current value for the sensor. The current value is shown beside the control and updates continuously.
Select Fixed Value to use a fixed value. Type the value in the edit box.
Select No Change, input is already forced to leave the input in its current state. This is selected by default if the value is already forced.
This is disabled if the input is not forced.
Select Remove Force to remove the existing forcing. This button is disabled if the input is not forced.
If an input on a run is not forced currently, the initial (default value of the
Fixed Value field) needs to be the default input value for the field. If the input type is a sensor and the Values on Sensor Fail field is set to use default value in the Run Configuration dialog.
Realflo User and Reference Manual
May 19, 2011
192
Realflo Maintenance Mode Reference
The Back button moves back to the Select Run or Transmitter to Force step. Backing up does not erase events from the flow computer event log, or remove forcing from inputs previously processed.
The Finish button completes the Force Input Value process and closes the dialog.
The Cancel button closes the wizard. This does not undo any changes. Any input that is already forced will remain forced.
The Help displays the online help file.
The same transmitter can be used for more than one flow run. Realflo forces the value for each run.
Realflo User and Reference Manual
May 19, 2011
193
Realflo Maintenance Mode Reference
Configuration
The Configuration section of the Realflo main page contains a View and
Change Configuration button. Click the View and Change Configuration button to start the View and Change Configuration wizard. The wizard will lead you through the steps to connect to a flow computer and view and modify the configuration.
For each step in the wizard, a dialog is presented to enter the parameters for the step. Each dialog contains four buttons to allow navigation through the wizard.
View and Change Configuration Wizard
The View and Change Configuration wizard will lead you through the steps to connect to a flow computer and view and modify the configuration.
For each step in the wizard a dialog is presented to enter the parameters for the step. Each dialog contains four buttons to allow navigation through the wizard.
<Back returns to the previous step in the wizard. This button is disabled on the first step of a wizard.
Next> moves to the next step in the wizard. This button is hidden on the last step of a wizard.
Finish is displayed on the final step of a wizard in place of the Next button. It finishes the operation. This button is hidden on other steps.
Cancel cancels the operation and closes the wizard. Steps performed thus far in the wizard are cancelled. Pressing the ESC key performs the same action as Cancel.
Help opens the user manual.
Realflo User and Reference Manual
May 19, 2011
194
Realflo Maintenance Mode Reference
Connect to Flow Computer
The connect to flow computer step defines the communication settings for the connection between the PC running the Realflo application and the target flow computer.
The How do you want to communicate with the flow computer? prompt provides two selections.
The Use the Current Settings option sets the default communication settings for Realflo. These settings are for the PC that is running Realflo.
(The communication settings for the PC running Realflo and the communication settings in the flow computer need to match).
The default communication settings are:
COM 1 (serial port on the PC)
9600 baud
no parity
8 Data bits
1 Stop bit
The default Modbus address Realflo will connect to is station 1.
Use this selection if the serial port on your PC is COM 1 and the serial port settings for the serial port on the flow computer are set for default (9600,
8,n,1 and Modbus address 1).
Click the Next> button to begin communication with the flow computer and move to the next step in the wizard.
The Choose/View Communication Setup option opens the PC
Communication Settings dialog as shown below. This allows you to view the default settings and to change the PC communication setting for the type of connection you are using to communicate with the flow computer.
See the section Communication >> PC Communication Settings
Command in the Realflo Expert Mode Reference section of this manual for complete details on the parameter settings in this dialog.
Realflo User and Reference Manual
May 19, 2011
195
Realflo Maintenance Mode Reference
You need to know the communication settings for the connection to the flow computer to use this step.
Once the communication settings have been selected click the OK> button to close the dialog and begin communication with the flow computer.
Realflo User and Reference Manual
May 19, 2011
196
Edit Configuration
Realflo Maintenance Mode Reference
The Edit Configuration dialog allows the viewing and editing of the flow computer parameters.
The Edit Configuration dialog displays parameter types associated with a flow computer in the tree structure at the right side of the dialog.
The Description field displays an overview of each of the parameter types.
Click on a parameter type and a short description of the parameter is displayed in the Description field.
The View/Edit button displays the configuration dialog for a selected parameter.
Click on a parameter type to highlight it and then click the View/Edit button to open the configuration dialog for the parameter.
Parameters in the tree are completely described in other sections of this user manual. A list of the parameters and the location of the complete description is shown below.
Flow Computer Configuration
For complete information on Flow Computer Type parameters refer to
the Realflo Expert Mode Reference>> Configuration Menu >> Setup
section.
For complete information on Serial Ports parameters refer to the
Realflo Expert Mode Reference>> Configuration Menu >> Serial
Ports section of this user manual.
For complete information on Register Assignments parameters refer
to Realflo Expert Mode Reference>> Configuration Menu
>>Register Assignment section of this user manual.
For detailed information on DNP configuration refer to the DNP section.
Realflo User and Reference Manual
May 19, 2011
197
Realflo Maintenance Mode Reference
Flow Run Configuration
For complete information on Flow Run Configuration refer to the
Realflo Expert Mode Reference>> Configuration Menu >>Flow Run
section.
Sensor and Display Configuration
For complete information on Sensor and Display Configuration refer
to the Realflo Expert Mode Reference>> Configuration Menu
Process I/O configuration
For complete information on Process I/O Configuration refer to the Realflo
Expert Mode Reference>> Configuration Menu >>Process I/O section.
Flow Computer Configuration Summary
This step displays a summary of the flow computer settings.
Review Differences
A summary of the flow computer configuration is shown.
The current configuration can be compared with the configuration in the target flow computer.
Select Yes to compare the configurations. The next step is Review
Differences.
Select No to not compare the configurations. The next step is Save File.
Realflo User and Reference Manual
May 19, 2011
198
Realflo Maintenance Mode Reference
This step displays a summary of changes in the flow computer configuration. The user may select to write to the flow computer or not
A summary of the differences is the configuration is shown.
Select Yes to write the configuration to the flow computer. The configuration is written to the flow computer. The Start Executing command will be written for each flow run. The communication progress dialog shows the stages of writing.
Select No to write the configuration to the flow computer later.
Click Next to perform the selected action.
In Flow Computer versions 6.73 and older, when AGA-8 gas ratios or NX-19 gas quality values are written to the flow computer the new gas ratios are updated in the Proposed registers. The Actual registers are not updated until a new Density calculation is started with the new values. The new values are not available to SCADA host software reading the Actual registers until a until a new Density calculation is started with the new values.
In Flow Computer versions 6.74 and newer when AGA-8 gas ratios or NX-
19 gas quality values are written to the flow computer the new gas ratios are updated in the Proposed registers and in the Actual registers. This allows a
SCADA host to immediately confirm the new values were written to the flow computer. The new gas values are not used by the flow computer until a new density calculation is started.
Realflo User and Reference Manual
May 19, 2011
199
Save File
Realflo Maintenance Mode Reference
This step selects where to save the configuration file.
Select the Save to Realflo.tfc to save the configuration file to the default file location.
Select the Save to another file to either enter a file name or use the
Browse button to open the Save As dialog.
Realflo User and Reference Manual
May 19, 2011
200
Realflo Maintenance Mode Reference
Switch to Expert Mode
The Switch to Expert Mode button closes the Maintenance Mode window and opens the Expert Mode window. Files are not closed and connections to flow computers are not lost when the Switch to Expert Mode button is selected.
Realflo User Manual
The Realflo User Manual button opens this manual.
Exit Realflo
The Exit Realflo button closes Realflo. Realflo will display a message if any files are not saved or not yet written to the flow computer.
Realflo User and Reference Manual
May 19, 2011
201
Realflo Expert Mode Reference
Realflo Expert Mode Reference
The Realflo display window is divided into the following areas. Each area is described in the following sections of this manual.
User Interface Components
The Title Bar is located along the top of the Realflo window and contains application file information and window control functions.
The Menu Bar provides access to Realflo commands. This reference contains complete information on Realflo menu commands.
The Tool Bar is located below the Menu Bar and provides quick mouse access to many Realflo functions.
The Maintenance Tool Bar is a docking toolbar and provides single button access to flow computer maintenance functions.
The Configuration Tool Bar is a docking toolbar and provides a structured tree of flow computer configuration data.
The Status Bar is displayed across the bottom of the application window and describes actions of menu items as you use the arrow keys or mouse to navigate through menus.
Realflo User and Reference Manual
May 19, 2011
202
Realflo Expert Mode Reference
Display Window
The Expert Mode display window is shown below.
Current Readings
The Current Readings view is divided into five sections:
The Process Measurements section displays the live and forced values for the flow calculation process inputs. The live values show the value read from the sensor. The forced values show the inputs to the flow calculation when they are forced. The Forced values are disabled when the input is live.
The forced values are shown in red when the value is forced.
The units of measurement displayed are those in effect when the readings were made. See Measurement Units for a description of the unit types.
Process measurements not used by the flow calculation are disabled.
Forced values are not displayed for flow computers older than 6.0.
The Calculated Compressibility section displays the results of the compressibility calculation selected in the Input Configuration property page. The time of the last compressibility calculation update and any compressibility calculation errors are also displayed in this section. The units of measurement displayed are those in effect when the readings were made. See Measurement Units for a description of the unit types.
The Calculation Status section displays the Calculation State of the flow computer calculations for the run. Refer to the Calculation Control command in the Flow Computer menu for further information on flow calculation control. The Calculation State can be changed using the start or stop button beside the Calculation State display.
When the Current Readings are being updated and the calculation is
stopped or not set then the button is labeled Start.
When the Current Readings are being updated and the calculation is
running then the button is labeled Stop.
When the Current Readings are not being updated the button is disabled and no text is displayed on it.
Realflo User and Reference Manual
May 19, 2011
203
Realflo Expert Mode Reference
Click on the button to change the Calculation State.
If the calculations are stopped the following message box is displayed.
If Yes is selected the flow calculations for the run are started.
If No is selected the message box is closed and no further action is taken.
If the calculations are running the following message box is displayed.
If Yes is selected the flow calculations for the run are stopped.
If No is selected the message box is closed and no further action is taken.
The Last Flow Configuration displays the time stamp of the last time the flow configuration was changed.
The Last Density Configuration displays the time stamp of the last time the compressibility configuration was changed.
The Last Flow Configuration and Last Density Configuration values are not displayed for flow computers older than 6.0.
The Calculated Flow at Base Conditions displays the instantaneous Flow
Volume Rate, Flow Volume Rate and Flow Energy Rate at base conditions.
The Flow Extension is displayed when the run is configured for AGA-3
(1990) calculations. The Flow Product is displayed when the run is configured for AGA-3 (1990) calculations. The Uncorrected Volume is displayed when the run is configured for AGA-7 calculations. The time of the last flow calculation and any flow calculation errors are also displayed. The units of measurement displayed are those in effect when the readings were made. See Measurement Units for a description of the unit types.
The Accumulated Flow at Base Conditions section displays the accumulated flow at base conditions for the current contract day, the number of flow calculations and the flow time for the current contract day
(Today) and the previous contract day (Yesterday). Data is copied from the current contract day (Today) to the previous contract day (Yesterday) at the end of the contract day, as measured by the real time clock. Data is not copied when a new day is started for other reasons. The units of measurement displayed are those in effect when the readings were made.
See Measurement Units for a description of the unit types.
Realflo User and Reference Manual
May 19, 2011
204
Realflo Expert Mode Reference
This section also displays the accumulated flow volume and flow time for the current month and the previous month. Data is copied from the current month (This Month) to the previous month (Last Month) at the end of the contract day at the end of the month, as measured by the real time clock.
The Total Accumulated Flow at Base Conditions section displays the total accumulated flow volume at base conditions. The accumulator holds a number between 0 and 999,999,999,999. It rolls over when the accumulated value is equal or greater than 1,000,000,000,000. The units of measurement displayed are those in effect when the readings were made. See
Measurement Units for a description of the unit types.
The Accumulated Uncorrected Flow section displays the total calculated uncorrected flow volume (AGA-7 only) for the current contract day, the previous contract day, the current month and the last month.
Title Bar
The title bar is located along the top of a window. It contains the name of the application, Realflo, and the currently opened flow computer file. The current view and meter run are displayed in brackets. The title bar provides commands for control of the opened application and the window display.
To move the window, drag the title bar. You can also move dialog boxes by dragging their title bars.
The application control menu button is the Realflo icon in the upper left corner of the Realflo window. When selected the following commands are displayed.
Use the Restore Command to return the active window to its size and position before you chose the Maximize or Minimize command.
Use the Move Command to display a four-headed arrow so you can move the active window or dialog box with the arrow keys. This command is unavailable if you maximize the window. Using the mouse drag the window title bar to location required.
Use the Size Command to display a four-headed arrow so you can size the active window with the arrow keys. This command is unavailable if you maximize the window. Use the mouse to drag the size bars at the corners or edges of the window.
Use the Minimize Command to reduce the Realflo window or the view window to an icon. Use the mouse by clicking the minimize icon on the title bar.
Use the Maximize Command to enlarge the active window to fill the available space. Use the mouse by clicking the maximize icon on the title bar; or double-click the title bar.
Use the Close Command to close the active window or dialog box. Doubleclicking a Control-menu box is the same as choosing the Close command.
If you have multiple windows open for a single document, the Close command on the document Control menu closes only one window at a time.
You can close all windows at once with the Close command on the File menu. Keyboard keys CTRL+F4 closes a document window and ALT+F4 closes the Realflo window or dialog box.
Use the Next Window Command to switch to the next open document window. Realflo determines which window is next according to the order in which you opened the windows. Use the keyboard keys CTRL+F6.
Realflo User and Reference Manual
May 19, 2011
205
Realflo Expert Mode Reference
Use the Previous Window Command to switch to the previous open document window. Realflo determines which window is previous according to the order in which you opened the windows. Use the keyboard keys
SHIFT+CTRL+F6.
Standard Toolbar
The Standard toolbar is displayed across the top of the application window, below the menu bar. The toolbar provides quick mouse access to many tools used in Realflo.
To hide or display the Toolbar, choose Toolbar from the View menu.
The following commands and functions are displayed on the Toolbar.
Create a new file
Open an existing file. Realflo displays the Open dialog box, in which you can locate and open the desired file.
Save the active file with its current name. If you have not named the document, Realflo displays the Save As dialog box.
Print data from the active view.
View data as it would be printed.
Edit Flow Computer configuration.
Edit Flow Computer configuration.
Read configuration from controller.
Write configuration to the controller.
Enable/Disable updating of Current Readings view.
Read Logs/History from Flow Computer for the meter run.
Display the Current Readings view for the meter run.
Display the Hourly History view for the meter run.
Display the Daily History view for the meter run.
Display the Hourly Gas Quality History view for the meter run.
Display the Event Log view for the meter run.
Displays the Alarm Log view for the meter run.
Show Run 1 in the current view. The view type is not changed.
Show Run 2 in the current view. The view type is not changed.
Realflo User and Reference Manual
May 19, 2011
206
Realflo Expert Mode Reference
Show Run 3 in the current view. The view type is not changed.
Show Run 4 in the current view. The view type is not changed.
Show Run 5 in the current view. The view type is not changed.
Show Run 6 in the current view. The view type is not changed.
Show Run 7 in the current view. The view type is not changed.
Show Run 8 in the current view. The view type is not changed.
Show Run 9 in the current view. The view type is not changed.
Show Run 10 in the current view. The view type is not changed.
Select whether all views or only the current view are affected by the
Run 1, Run 2 and Run 3 commands.
The toolbar may:
Remain stationary along one side of its parent window;
Be dragged and docked, or attached, by the user to any side or sides of the parent window you specify;
Be floated, or detached from the frame window, in its own mini-frame window so the user can move it around to any convenient position; and
Be re-sized while floating.
To move the toolbar, click on the background of the toolbar. Drag the toolbar to the new location and release the mouse button.
Maintenance Toolbar
The maintenance toolbar organizes the maintenance operations together.
The maintenance toolbar is a docking toolbar. Its initial position is below the main toolbar. You can move it, undock it, or hide it.
The following commands and functions are displayed on the toolbar.
The Maintenance Toolbar may:
Realflo User and Reference Manual
May 19, 2011
207
Realflo Expert Mode Reference
Remain stationary below the main toolbar;
Be dragged and docked, or attached, to either side of the parent window;
Be floated, or detached from the frame window, in its own mini-frame window so the you can move it around to any convenient position; and
Be resized while floating. The button layout automatically changes as the toolbar is resized.
To move the toolbar, click the title bar of the toolbar. Drag the toolbar to the new location and release the mouse button.
The toolbar can be enabled or disabled from the View menu. A check mark appears next to the menu item when the Maintenance Toolbar is displayed.
Configuration Toolbar
The configuration toolbar organizes configuration data in one place.
The configuration toolbar is a docking toolbar. Its initial position is on the left side of the Realflo window. You can move it, dock it, or hide it. or hidden by the user.
The configuration toolbar contains a tree of configurable items. Leaves are grouped under nodes. Double-clicking a leaf will open the dialog or property sheet for the item.
The toolbar may:
Remain stationary along one side of its parent window;
Be dragged and docked, or attached, by the user to either side of the parent window you specify;
Be floated, or detached from the frame window, in its own mini-frame window so the user can move it around to any convenient position; and
Be re-sized while floating.
Realflo User and Reference Manual
May 19, 2011
208
Status Bar
Scroll Bars
Menu Bar
Realflo Expert Mode Reference
To move the toolbar, right click anywhere in the toolbar and select Allow
Docking. The toolbar can be moved to a new location.
To close the toolbar, right click anywhere in the toolbar and select Hide.
The Status Bar is displayed across the bottom of the application window.
The left area of the status bar describes actions of menu items as you use the arrow keys to navigate through menus. It also shows messages that describe the actions of toolbar buttons as you depress them, before releasing them. If after viewing the description of the toolbar button command you wish not to execute the command, then release the mouse button while the pointer is off the toolbar button.
The Username and security level are shown at the bottom right of the Status
Bar. This provides an indication of the security level of the user. Some configuration toolbar items may be disabled depending of the security level of the user.
The right areas of the status bar indicate which of the following keys are latched down:
CAP Indicates the Caps Lock key is latched down.
NUM Indicates the Num Lock key is latched down.
SCRL Indicates the Scroll Lock key is latched down.
To hide or display the Status Bar, choose Status Bar from the View menu.
Scroll bars are displayed at the right and bottom edges of the document window. The scroll boxes inside the scroll bars indicate your vertical and horizontal location in the document. You can use the mouse to scroll to other parts of the document.
Scroll bars appear only when needed. If there is no visible data the scroll bar will not be shown.
The menu bar displays the commands for configuration, communication, monitoring, and security and file management functions available with
Realflo. Menu commands are displayed by clicking the mouse button on the menu item or by pressing the alt key and the underlined letter of the menu item.
Realflo User and Reference Manual
May 19, 2011
209
File Menu
Realflo Expert Mode Reference
The File menu contains commands to create, open and save Realflo files.
File menu commands allow data to be exported to spreadsheet (csv), Flow-
Cal (cfx) files and to be printed. User accounts are also configured using this menu.
New Command
Use this command to create a new Realflo file. When selected this command opens the New File Wizard. See the section Realflo Wizards >>
New File Wizard for complete details on using the wizard.
Open Command
Use this command to open an existing Realflo file. When the Open command is used the File Open Dialog is displayed.
The following options allow you to specify which file to open.
The Look In: box lists the available folders and files.
The File Name: box allows you to type or select the file name you want to open. This box lists files with the extension you select in the Files of Type box.
The Files of Type: box lists the types of files Realflo can open. Realflo can open flow computer (TFC) files and flow computer Template files (RTC).
When any account other than the ADMIN account has been created in the
Realflo file the user needs to log on to an account when a flow computer file
section for details.
The Open button opens the selected file and closes all views for runs that are not supported by the file that is opened.
The Cancel button closes the dialog without opening a file.
Realflo User and Reference Manual
May 19, 2011
210
Realflo Expert Mode Reference
Only one flow computer file can be open at a time in Realflo. To view data from more than one flow computer at a time, start another copy of Realflo.
Close Command
Use this command to close all Realflo windows for the flow computer.
Realflo suggests that you save changes to the flow computer file. If you close a flow computer file without saving, configuration changes made and data that has been read from the flow computer since the last time you saved it are not saved. Before closing an untitled file, Realflo displays the
Save As dialog box and suggests that you name and save the file.
Save Command
Use this command to save the flow computer file to its current name and directory. Saving a file saves the flow computer configuration, Hourly and
Daily history, and the Event and Alarm logs.
When you save a file for the first time, Realflo displays the Save As dialog box so you can name your file. If you want to change the name or directory of the file, before you save it, choose the Save As command.
Realflo 6.70 files are compatible with files saved using earlier versions of
Realflo.
Save As Command
Use this command to save and name the flow computer file. Realflo displays the Save As dialog box so you can name your file.
The following options allow you to specify the name and location of the file you're about to save:
The Save in: box lists the available folders and files.
The File name: box allows entry of a new file name to save a file with a different name. Realflo adds the extension you specify in the Save As type box.
The Save as type: box lists the types of files Realflo can save. Realflo can open flow computer (TFC) files and flow computer Template files (RTC).
Realflo User and Reference Manual
May 19, 2011
211
Realflo Expert Mode Reference
If the open file is a flow computer file and the Save as Type is a template file, Realflo will ask if the flow computer file should be saved before converting it to a template.
The Save button saves the file to the specified location.
The Cancel button closes the dialog without saving.
To save a file with its existing name and directory, use the Save command.
Flow Computer File Types
Realflo uses separate files for flow computer configuration, current reading data, daily history data, hourly history data, alarm and event log data, process I/O configuration and custom views. All files are saved with the same file name and different file extensions. The table below indicates the file types and extensions.
File Type File Contents Extension
Configuration
Daily history
Hourly history
Configuration of the Flow
Computer
Historical data for daily history view
Historical data for hourly history view
TFC
TFD
TFH
Gas Quality History Historical data for gas quality history view
Event log Historical data for event log
Alarm log
Current readings
Settings
Historical data for alarm log
Current readings data
TFG
TFE
TFA
TFR
Configuration data not relating to flow calculations
TFS
Process I/O configuration data TFP Process I/O
Custom Views
Settings
Custom Views configuration
Additional configuration data not relating to flow calculations.
Includes SolarPack settings.
TFV
TFX
Template File Types
Realflo uses separate files for templates. All files are saved with the same file name and different file extensions. The table below indicates the file types and extensions.
File Type
Configuration
Settings
Process I/O
Custom Views
File Contents
Flow Computer configuration
Configuration data not relating to flow calculations
Process I/O configuration
Flow Run and Custom Views configuration
Extension
RTC
RTS
RTP
RTV
Managing Realflo Files
When copying Realflo files from one PC to another, copy all the files for a flow computer.
If history, event or alarm logs have grown too large, move the history and log files to another directory. New files will be created the next time you read
Realflo User and Reference Manual
May 19, 2011
212
Realflo Expert Mode Reference logs from the flow computer. If you export the data first, you can have easy access to the archived data from a spreadsheet and current data from
Realflo.
If you have created a copy of a flow computer for configuration of a new unit, you can delete the hourly and daily history, event and alarm logs by deleting the files with the TFD, TFH, TFE and TFA extensions.
Export Command
The Export command is used to select the type of file format to export
Realflo data to. There are five selections:
Export to CSV
Export to CFX
CSV Export Options
CFX Export Options
Export PEMEX Report
Export to CSV
Use the Export to CSV command to export the flow computer configuration data and the data from any view. Data is exported in the CSV (commaseparated values) format. This format can be read by spreadsheet and database software.
Data is exported from the current window. Select the window containing the view you wish to export or change the view in the current window using the
View menu.
When the Export command is selected the Export data dialog appears for views that support the selection of records for exporting, such as the hourly history, daily history or event log views. For views not supporting the selection of records, for example, configuration views, the Save As dialog is opened.
The All radio button selects all the data in the current view. This is the default button if no data is selected.
The Selection radio button selects the data that is currently selected in the view. This is the default button if data is selected.
The Selected Dates radio button selects the data from the contract days in the From and To dropdown lists.
The From dropdown list selects the oldest contract day. This control is enabled when the Selected Dates radio button is selected.
Realflo User and Reference Manual
May 19, 2011
213
Realflo Expert Mode Reference
The To dropdown list selects the recent contract day. This control is enabled when the Selected Dates radio button is selected.
Clicking the Cancel button or pressing the Escape key closes the dialog.
The OK button opens the Save As file selection dialog, with the file type
CSV active. A file name is suggested for each type of file that is exported.
Export to CFX
You may change the file name to any suitable name. The suggested file name format is defined in the CSV Export Options command.
The Save As file selection dialog appears for views. The Save As dialog allows you to specify the file to export the data to.
The Save button in the Save As dialog exports the data to the selected file.
The Cancel button in the Save As dialog cancels the export command and closes dialogs.
Use the Export to CFX command to export data in the Flow-Cal CFX format.
This format is designed for importing into Flow-Cal. Data is exported to the
CFX file from one flow run. The file includes data from the configuration, current readings, alarm log, event log and hourly history log.
The Run dropdown list selects the flow run to export. The default value is the flow run of the active view.
Realflo User and Reference Manual
May 19, 2011
214
Realflo Expert Mode Reference
The All Alarms, Events and Hourly Logs radio button selects all of the data in the flow run. This is the default button.
The Selected Days radio button selects the data from the contract days in the From and To dropdown lists.
The From dropdown list selects the oldest contract day. This control is enabled when the Selected Days radio button is selected.
The To dropdown list selects the recent contract day. This control is enabled when the Selected Days radio button is selected.
The Export Type dropdown list selects how export files are stored.
Select Specific File to export to a single file. A standard file save dialog opens to allow you to select the file name. The default file name is
<Realflo file name>(<FC ID>) - <Run Number> (<Run ID>).CFX.
Select Dated CFX to export one file per day to a single folder per run.
Realflo exports one file for each day. The file name is based on the time and date according to the CFX standard (YYYYMMDD.CFX).
A separate folder is created for each run. The folder is named
<Realflo file name>(<FC ID>) - <Run Number> (<Run ID>).CFX.
CFX File Version
The Save As file selection dialog appears for views. The Save As dialog allows you to specify the file to export the data to.
The Save button in the Save As dialog exports the data to the selected file.
The Cancel button in the Save As dialog cancels the export command and closes dialogs.
Data is exported in the CFX version 5 format. This format is not supported by some older versions of Flow-Cal. An upgrade may be available from
Flow-Cal to allow older versions to read this file format. Contact Flow-Cal for details.
Realflo User and Reference Manual
May 19, 2011
215
Realflo Expert Mode Reference
CSV Export Options Dialog
The CSV Export Options command defines whether optional data is exported to CSV files. The settings in this dialog apply to files opened by
Realflo. They are stored in the Windows registry.
The Hourly and Daily Records section of the dialog defines optional data to include and how the data is time stamped.
Select the Include Uncorrected Flow in AGA-7 Export option to export the Uncorrected Data column from the Hourly History Log and
Daily History Log. This option applies to AGA-7 only. The option is unchecked by default.
Select the Export in Time Leads Data Format option to export time stamps that mark the start of the period. Uncheck the option to export time stamps that mark the end of the period (Realflo format). This applies to the the Hourly History and Daily History only. The control is unchecked by default.
The Default File Name Format section defines the file name that is suggested by Realflo when data is exported. The names are combinations of the file name; Flow Computer ID; flow run number; and flow run ID.
The Format list selects the name format. The name is made up of the identifier format and a view format. The valid values for the identifier are listed below. The default is to include all information. o file name (Flow Computer ID) - Run# (run ID) - Type o file name (Flow Computer ID) - Run# - Type o file name (Flow Computer ID) - run ID - Type o file name - Run# (run ID) - Type o file name - Run# - Type o file name - run ID - Type o Flow Computer ID - Run# (run ID) - Type
Realflo User and Reference Manual
May 19, 2011
216
Realflo Expert Mode Reference o Flow Computer ID - Run# - Type o Flow Computer ID - run ID - Type o Run# (run ID) - Type o run ID - Type
When the logs are exported the word Type is replaced by the following, according to the export selected. o Alarms o Events o Hourly Log o Daily Log o Current Readings o Custom View Name
The Example control shows the file name that will be suggested for the current file.
Realflo User and Reference Manual
May 19, 2011
217
Realflo Expert Mode Reference
CFX Export Options Dialog
The CFX Export Options dialog sets options for exporting to Flow-Cal CFX files. The settings in this dialog apply to files opened by Realflo. They are stored in the Windows registry.
The Hourly History section defines how records from the hourly history are exported.
Select Export Partial Hour Records to export the records as they appear in Realflo. Some hours may contain more than one record due to power cycling or configuration changes. This is the default selection.
Select Export One Record per Hour to export only one record per hour. Multiple records within an hour are merged into a single record for exporting. Hours that are not yet complete are not merged or exported.
The following hourly record fields are summed: volume, mass, energy, pulses (turbine type).
Realflo User and Reference Manual
May 19, 2011
218
Realflo Expert Mode Reference
The following hourly record fields are averaged: termperature, static pressure, differential pressure (orifice types), relative density, flow product
or flow extension. See Input Averaging on page 948 for more information.
Select Time Leads Data Format to export the date and time at the start of the period. The time stamp on the record is the time at the start of the hour, even if the first record to be merged started later than that time.
This option is enabled only when Export One Record per Hour is checked. This option is unchecked by default.
The File Description section defines some descriptive parameters in the
CFX file.
Meter Number defines the meter number parameter. The options are
none, Flow Computer ID, Flow Run ID and Flow Run Number. The default value is Flow Computer ID. The parameter is 17 characters long in the file.
Meter Name defines the meter name parameter. The options are none,
Flow Computer ID, Flow Run ID and Flow Run Number. The default value is Flow Run ID. The parameter is 49 characters long in the file.
Serial Number defines the meter serial number parameter in the file.
The options are none, Flow Computer ID, Flow Run ID and Flow Run
Number. The default value is Flow Run Number. The parameter is 11 characters long in the file.
The Live Inputs Flags section defines which live input flags are set by
Realflo. The CFX file contains four flags in the Live Inputs parameter.
Realflo sets the T (temperature) flag to Y (live data). The other flags are normally set to N (not live), but can be modified using the following options.
Check Set Live Gas Composition Flag when there is a program that updates the gas composition. This is flag A (analysis). This option is unchecked by default.
Check Set Live Energy Flag when there is a program that updates the energy. This is flag B (heating value). This option is unchecked by default.
Check Set Live Gravity Flag when there is a program that updates the specific gravity (relative density). This is flag G (gravity). This option is unchecked by default.
The Default Name Format section defines what file names Realflo suggests when exporting. The names are combinations of the file name;
Flow Computer ID; flow run number; and flow run ID.
Format selects the name format. The valid values are listed below. The default is to include all information. o file name (Flow Computer ID) - Run# (run ID) o file name (Flow Computer ID) - Run# o file name (Flow Computer ID) - run ID o file name - Run# (run ID) o file name - Run# o file name - run ID o Flow Computer ID - Run# (run ID)
Realflo User and Reference Manual
May 19, 2011
219
Realflo Expert Mode Reference o Flow Computer ID - Run# o Flow Computer ID - run ID o Run# (run ID) o run ID
The Example control shows the file name that will be suggested for the current file.
The Dated CFX section defines where and how CFX files are exported.
Select Use .CFX extension on folder names to create folders with a
CFX extension when exporting Dated CFX files. The data for each month is stored in its own folder when using the Dated CFX format. The folder name may have a CFX extension or not. This option is unchecked by default.
Select Export Dated CFX Files to the Folder to define a common folder for exports. Exported data will be placed in this folder. The option is unchecked by default. When checked, the edit control holds the destination folder that will appear in the Save As dialog. Use Browse to search for another folder.
Export PEMEX Report to CSV
Use the Export PEMEX Report to CSV command to export the flow computer configuration data and the data from any view. Data is exported in the CSV (comma-separated values) format. This format can be read by spreadsheet and database software.
Data is exported from the current window. Select the window containing the view you wish to export or change the view in the current window using the
View menu.
When the Export command is selected, the Export PEMEX Report to CVS dialog appears for views that support the selection of records for exporting, such as the hourly history, daily history or event log views.
This menu item is only visible if Realflo PEMEMX is launched.
Select the Run to export from the Run dropdown list.
The Type radio button lets you export hourly or daily records.
Realflo User and Reference Manual
May 19, 2011
220
Realflo Expert Mode Reference
For views not supporting the selection of records, for example, Configuration views, the Save As dialog opens.
The All radio button selects all the data in the current view. This is the default button if no data is selected.
The Selected Dates radio button selects the data from the contract days in the From and To dropdown lists.
The From dropdown list lets you select the oldest contract day. This control is enabled when the Selected Dates radio button is selected.
The To dropdown list lets you select the recent contract day. This control is enabled when the Selected Dates radio button is selected.
Clicking the Cancel button or pressing the Escape key closes the dialog.
The OK button opens the Save As file selection dialog, with the file type
CSV active. A file name is suggested for each type of file that is exported.
Print Command
You may change the file name to any suitable name. The suggested file name format is defined in the CSV Export Options command.
The Save As file selection dialog appears for views. The Save As dialog allows you to specify the file to export the data to.
The Save button in the Save As dialog exports the data to the selected file.
The Cancel button in the Save As dialog cancels the export command and closes dialogs.
Use this command to print data from the current view. Realflo displays the
Print dialog. The following options allow you to specify the printer, the print range and the number of copies.
The Name drop-down list box displays a list of configured printers.
The Properties button defines the settings for the selected printer.
The Print range radio buttons selects the data to be printed.
Realflo User and Reference Manual
May 19, 2011
221
Realflo Expert Mode Reference
The All radio button prints all the data in the current view. This is the default button if no data is selected.
The Pages radio button allows the printing of selected pages.
The Selection radio button prints the data that is currently selected in the view. This is the default button if data is selected.
The Number of copies selection indicates how many copies to print.
If the printer selected in the Name box supports collating print jobs you may select Collate, otherwise the control is grayed out.
The OK button prints the report.
Selecting the Cancel button or pressing the Escape key closes the dialog.
Print Preview Command
Use this command to see how your printed report will look. The command opens a special view that shows data as it will be printed.
To preview a report from a view select the window containing the view you wish to print or change the view in the current window using selections from the View menu.
When hourly history, daily history or log views are selected you can select records to print that interest you by left-clicking the mouse button on them.
A row of control buttons is available at the top of this view. These control buttons are described below.
The Print button prints the report as shown.
The Next Page button displays the next page. It is grayed if there are no more pages.
The Prev Page button displays the previous page. It is grayed if there are no pages before the current page.
The Two Page button changes the display to show two pages at a time. The
One Page button changes the display to show one page at a time.
The Zoom In button enlarges the page displayed so you can see details on the report.
The Zoom Out button shrinks the page displayed so you see how the page is formatted.
The Close button closes the Print Preview view.
Print Setup Command
Use this command to define how reports are printed. The font, page headings, margins, and the size of the columns on the hourly history, daily history or event log reports can be changed. Select from the options described below.
The page headings section selects what is printed in the header of each report page.
Selecting Title prints the title of the report centered on the page.
Selecting Date and Time prints the date and time in the upper left-hand corner of the page. The date and time are printed in the long time format defined from the Windows Control Panel.
Realflo User and Reference Manual
May 19, 2011
222
Realflo Expert Mode Reference
Selecting Page Numbers prints “Page” and the page number in the upper right hand corner of the page. The Start At edit box selects where the page numbers start.
The Margins section defines the page margins.
Left is the size of the left-hand margin on the page.
Right is the size of the right hand margin on the page.
Top is the size of the top margin on the page.
Bottom is the size of the bottom margin on the page.
Measurement Units is the units of measurement for the margins. It is one of Inches or mm. The units are converted into the other measurement system when this control is changed.
The selected font section defines the font used for printing reports. The currently selected font is shown.
The Change Font button opens a font selection dialog. The user may choose the font for printing reports.
The column width section defines the widths of the columns on specific reports.
The Report dropdown list selects the report to edit.
The Column dropdown list displays columns on the selected report.
The Width edit box displays the current column width and allows it to be changed.
The Reset Report button resets columns on the current report to their default widths.
Select the OK button to use the new settings.
Select the Cancel button or press the Escape key to close the dialog.
The Printer button opens the Printer dialog.
The Help button displays help for this dialog.
Print Setup Command in PEMEX Mode
Use this command to define how reports are printed when Realflo is operating in PEMEX mode. The font, page headings, margins, and the size of the columns on the hourly history, daily history or event log reports can be changed. Select from the options described below.
The page headings section selects what is printed in the header of each report page.
Selecting Title prints the title of the report centered on the page.
Selecting Date and Time prints the date and time in the upper left-hand corner of the page. The date and time are printed in the long time format defined from the Windows Control Panel.
Selecting Page Numbers prints “Page” and the page number in the upper right hand corner of the page. The Start At edit box selects where the page numbers start.
The Margins section defines the page margins.
Realflo User and Reference Manual
May 19, 2011
223
Realflo Expert Mode Reference
Left is the size of the left-hand margin on the page.
Right is the size of the right hand margin on the page.
Top is the size of the top margin on the page.
Bottom is the size of the bottom margin on the page.
Measurement Units is the units of measurement for the margins. It is one of Inches or mm. The units are converted into the other measurement system when this control is changed.
The selected font section defines the font used for printing reports. The currently selected font is shown.
The Change Font button opens a font selection dialog. The user may choose the font for printing reports.
The column width section defines the widths of the columns on specific reports.
The Report dropdown list selects the report to edit.
The Column dropdown list displays columns on the selected report.
The Width edit box displays the current column width. To print a PEMEX
Report, the default column widths need to be:
Column Width
21 Start Time and date
(regional format)
End Time and date
(regional format)
21
10 Time with active flow
(seconds)
Volume (1 st
base condition)
Energy (1 st
base condition)
Temperature
Pressure
Differential pressure/Average frequency
Relative density
Flow extension/Uncorrected volume
Number of alarms
Number of events
Up time (minutes)
Volume (2 nd
base condition)
Heating value
12
18
12
14
12
16
12
5
5
5
12
12
Realflo User and Reference Manual
May 19, 2011
224
Recent Files List
Use the numbers and file names listed at the bottom of the File menu to open the last four files you closed. Choose the number that corresponds with the file you want to open.
Exit Command
Realflo Expert Mode Reference
Column
Quality
Width
5
The Reset Report button resets columns on the current report to the required default settings when operating in PEMEX mode.
Select the OK button to use the new settings.
Select the Cancel button or press the Escape key to close the dialog.
The Printer button opens the Printer dialog.
The Help button displays help for this dialog.
Use this command to exit from Realflo. If changes have been made to the flow computer file, you will be asked if you want to save them.
Realflo User and Reference Manual
May 19, 2011
225
Realflo Expert Mode Reference
Edit Menu
The edit menu commands allow selected data to be copied to the clipboard.
The selected data is then available for use in other applications.
Copy Command
Use this command to copy selected data onto the clipboard. This command is unavailable if the view does not contain data that can be selected.
Copying data to the clipboard replaces the contents previously stored there.
Select All Command
Use this command to select all the records in the current view. This command is unavailable if the view does not contain data that can be selected.
Custom Views Command
Custom views provide a means for users to display and modify register data used in their custom applications. Custom applications include Telepace or
IEC 61131-3 and custom C or C++ programs that are running on a controller in addition to the gas flow computer application. Any register the
SCADAPack controller may be added to one or more custom views.
The Custom Views command is used to create and edit custom views.
When Custom Views are created they are assigned an Access Level for security purposes. The access levels are based on the User Account
Access levels, described in the
‟s access level, views may be viewed or edited and initial values may be written to the registers in the view.
When the Custom Views command is selected the Edit Custom Views dialog is displayed.
Realflo User and Reference Manual
May 19, 2011
226
Realflo Expert Mode Reference
The View Name list displays the views that are available to the current user.
Views that require a higher access level are not displayed. Refer to the
section for more information on Access Levels. If there are no
views created the list is blank.
Click on a view in the list to select it.
Double-click on a view in the list to edit it.
Use Ctrl-click or Shift-click to select multiple views.
Click on the column headings to sort the data. Clicking once sorts the data in ascending order. Clicking again sorts the data in descending order.
The buttons at the side of the Edit Custom Views dialog are used to create and edit Custom Views.
Click the Add button to open the Edit Table View dialog and add a new
Custom Views.
Click the Copy button to copy a selected Custom Views. The Edit Table
View dialog is opened with a copy of the selected view. This button is disabled if no view is selected or if multiple views are selected.
Click the Edit button to edit the selected Custom Views. The Edit Table
View dialog is opened and will contain the selected view. This button is disabled if no view is selected or if multiple views are selected.
Click the Delete button to delete the selected view or Custom Views.
The button is disabled if no view is selected. After deletion the next view in the list is selected, or the last view in the list is selected.
Realflo User and Reference Manual
May 19, 2011
227
Realflo Expert Mode Reference
The Update Rate edit box sets the rate, in seconds that data is polled from the flow computer to refresh the Custom Views. Valid values are 1 to 65535 seconds. The default value is 1 second.
The OK button saves changes to the Custom Views and closes the dialog.
The Cancel button closes the dialog without saving any changes to the
Custom Views.
Edit Table View Dialog
When the Edit button is selected, or a view is double clicked, in the Edit
Custom Views dialog the Edit Table View dialog is opened as shown below. The dialog contains information about the selected Custom Views.
The dialog contents are described below.
When the Add button is selected in the Edit Custom Views dialog the Edit
Table View dialog is opened as shown below. The dialog contents are described below.
Realflo User and Reference Manual
May 19, 2011
228
Realflo Expert Mode Reference
The View Name entry box contains the name of the Custom View. The View
Name may be any character string up to 16 characters in length. A view name needs to be entered and it needs to be unique.
The View Description entry box contains a description of the Custom View.
The View Description may be any character string up to 64 characters in length.
The Access Level Required dropdown menu selects the user account
access level required to display the Custom Views. See the
section for details on creating Realflo user account. Users with a lower access level than selected will not be able to see the view on menus. The menu selections are:
View and read data.
View, read and write data.
Administrator.
Access levels that are greater than the current user's access level are not available. This prevents a user from creating a view that he will not be able to edit because his access level is too low. The default value is View and read data.
The Allow Sorting dropdown menu selects whether the user can change the sort order on the Custom View. The menu selections are:
Yes
No
The default value is Yes.
The Default Sort Column dropdown menu selects the default column by which the Custom View is sorted. The menu selections are:
Tag
Description
Realflo User and Reference Manual
May 19, 2011
229
Realflo Expert Mode Reference
Address
Value
Forced
Type
Format
Writeable
Initial Value
The default value is Tag.
The Edit Table View list control displays the register data that will be included in the custom view. The register data is for each entry is displayed as a row in the list with column headings across the top of the list.
Click on the column headings to sort the data by the heading. Clicking once sorts the data in ascending order. Clicking again sorts the data in descending order.
The address and initial value columns are sorted numerically. The tag, description, type, format, and writeable columns are sorted alphanumerically.
The list is sorted by address in ascending order when the dialog is opened.
Click on a row in the list to select it.
Double-click on a row in the list to open the Edit Register on View dialog.
Use Ctrl-click or Shift-click to select multiple rows.
The OK button saves the changes to the Custom View and closes the dialog.
The Cancel button closes the dialog without saving any changes to the
Custom View.
Click the Add button to open the Add Registers dialog. This dialog is used to add registers to the Custom View.
Click the Edit button to open the Edit Registers On View dialog. This button is disabled if no register is selected or multiple registers are selected.
Click the Delete button to delete the selected register or registers. The button is disabled if no register is selected. After deletion the next register in the list is selected, or the last register in the list is selected.
Click the Columns button to open the Columns dialog. This dialog is used to select the columns that will be displayed on the Custom View.
This command does not affect the columns displayed in the Edit Table
View dialog.
Realflo User and Reference Manual
May 19, 2011
230
Realflo Expert Mode Reference
Add Registers Dialog
When the Add button is clicked in the Edit Table View dialog the Add
Registers dialog is opened. The dialog contents are described below.
The Existing Registers on All Views list displays all registers that are defined in all views. The list displays all registers, even if they are already in the view. This allows adding them more than once with different format.
Click on the column headings to sort the data. Clicking once sorts the data in ascending order. Clicking again sorts the data in descending order. The register column is sorted numerically. The tag column is sorted alphanumerically.
The list is sorted by register in ascending order when the dialog is opened.
The Registers to Add to Current View list displays registers that are to be added to the current view. Registers in the Registers to Add to Current View list are added to the current view when the OK button is clicked.
Click on the column headings to sort the data. Clicking once sorts the data in ascending order. Clicking again sorts the data in descending order. The register column is sorted numerically. The tag column is sorted alphanumerically.
The list is sorted by register in ascending order when the dialog is opened.
Registers in both lists may be selected by clicking on a row in the list or by holding down the Ctrl button and clicking on a row to select or deselect multiple rows.
The Add>> button will add the selected registers from the Existing Registers on All Views list to the Registers to Add to Current View list. This button is disabled if no registers are selected in the Existing Registers on All Views list.
The Add Copy>> button is used to add a copy of the selected register from the Existing Registers on All Views list to the Registers to Add to Current
View list. When selected this button opens the Register Properties dialog.
Realflo User and Reference Manual
May 19, 2011
231
Realflo Expert Mode Reference
The button is disabled if no register is selected in the Existing Registers on
All Views list.
The New button adds a new register to the Registers to Add to Current View list. When the button is pressed the Register Properties dialog is opened.
The Copy button adds a copy of the selected registers from the Existing
Registers on All Views list to the Registers to Add to Current View list. When the button is pressed the Register Properties dialog is opened. This button is disabled if no registers are selected in the Existing Registers on All Views list.
The Delete button deletes the selected registers from the Registers to Add to Current View list. The button is disabled if no registers are selected in the
Registers to Add to Current View list. After deletion the next register in the list is selected, or the last register in the list is selected.
The OK button adds the registers to the view and closes the dialog.
Registers of type Boolean are added using the Boolean format. All other register types are added using the decimal format.
The Cancel button closes the dialog without saving any changes.
Register Properties Dialog
The Register Properties dialog is used to edit the properties of a register object. Register objects are shared by all views. Editing these properties will affect all views that use the object. For example, if the register number is changed here, then all views that used the object will show the data from the new register.
When the Add Copy>> button or the New button are selected in the Add
Registers dialog the Register Properties dialog is opened.
Realflo User and Reference Manual
May 19, 2011
232
Realflo Expert Mode Reference
The Tag entry box contains the tag name of the register. The Tag name may be any character string up to 16 characters in length. A tag name needs to be entered and it needs to be unique.
The Description entry box contains a description of the register. The
Description may be any character string up to 64 characters in length.
The Address entry box contains the address of the register to be displayed.
Valid entries are:
00001 to 09999;
10001 to 19999;
30001 to 39999;
40001 to 49999.
The Data Type dropdown menu selects the type of register. Valid selections are:
Boolean for address from 00001 to 09999 and from 10001 to 19999
Signed Integer for address from 30001 to 39999 and from 40001 to
49999
Unsigned Integer for address from 30001 to 39999 and from 40001 to
49999
Signed Double for address from 30001 to 39999 and from 40001 to
49999
Unsigned Double for address from 30001 to 39999 and from 40001 to
49999
Realflo User and Reference Manual
May 19, 2011
233
Realflo Expert Mode Reference
Floating Point for address from 30001 to 39999 and from 40001 to
49999
ISaGRAF Integer for address from 30001 to 39999 and from 40001 to
49999
The default value is Unsigned Integer.
The Deadband entry is the amount by which the register needs to change value before Custom Views are updated. Valid entries depend on the register type selected. This control is disabled if Data Type is set to boolean.
The following table shows the minimum and maximum values for each type of register.
Type
Signed Integer
Minimum Value Maximum Value
-32768 32767
Unsigned Integer 0
Signed Double -2147483648
Unsigned Double 0
Floating Point Any
ISaGRAF Integer -2147483648
65535
2147483647
4294967295
Any
2147483647
The Writeable dropdown menu selects whether the user can write to the register. Valid selections are Yes and No.
The Use Initial Value dropdown menu selects whether an initial value is defined for the register. Valid selections are Yes and No. This control is disabled if Writeable is set to no.
The Initial Value entry is the initial value for the register. Valid values depend on the register type as shown in the table below. This control is disabled if Use Initial Value is set to No or if Writeable is set to No.
Type Minimum Value Maximum Value
Boolean
Signed Integer
OFF
-32768
Unsigned Integer 0
Signed Double -2147483648
Unsigned Double 0
Floating Point Any
ISaGRAF Integer -2147483648
ON
32767
65535
2147483647
4294967295
Any
2147483647
The Labels section displays the defined labels for a register. Labels are used in Custom Views to display text in place of values. For example a label could be used for the On / Off status of a motor. When the status is On the label could display Running and when the status is Off the label could display Stopped. When labels are defined there needs to be at least two labels.
The Value column displays the register value for which a label will be displayed.
The Label column displays the text that will be displayed for a value.
Click on a row in the list to select it.
Double-click on a row in the list to open the Edit Label dialog.
Hold down Ctrl and click on a row to select or deselect multiple rows.
Realflo User and Reference Manual
May 19, 2011
234
Edit Label Dialog
Realflo Expert Mode Reference
The Add button is used to add a label to the list. When selected the Edit
Label dialog is opened.
The Edit button is used to edit the selected label in the list. When selected the Edit Label dialog is opened. This button is disabled if no label or more than one label is selected.
The Delete button deletes the selected labels. The button is disabled if no label is selected. After deletion the next label in the list is selected, or the last label in the list is selected.
The OK button saves the changes and closes the dialog.
The Cancel button closes the dialog without saving any changes.
When the Add or Edit button is selected in the Register Properties dialog the
Edit Label dialog is opened.
The Value entry is the register value for which a label will be displayed.
Valid entries depend on the register type as shown in the table below. The value needs to be unique for each label.
Type
Boolean
Minimum Value Maximum Value
OFF ON
Signed Integer -32768
Unsigned Integer 0
Signed Double -2147483648
Unsigned Double 0
Floating Point Any
ISaGRAF Integer -2147483648
32767
65535
2147483647
4294967295
Any
2147483647
The Label entry is the text that will be displayed for a register value. The
Label may be any character string up to 8 characters in length and needs to be unique.
The OK button saves the changes and closes the dialog.
The Cancel button closes the dialog without saving any changes
Edit Register on View Dialog
The Edit Register on View dialog is used to modify a register on a Custom
View. This dialog is displayed when the Edit button in the Edit Table View is selected.
Realflo User and Reference Manual
May 19, 2011
235
Realflo Expert Mode Reference
The Register dropdown menu selects the register object that is displayed on the view. The dropdown list displays defined registers by tag and register number.
The Format dropdown menu selects how the register object will be displayed on the view. Valid selections are listed below.
Boolean - displays the register value as a Boolean. If the value is 0 then
OFF is displayed. If the value is non-zero then ON is displayed.
Decimal - displays the register value in decimal (base 10).
Hexadecimal - displays the register value in hexadecimal (base 16).
Binary - displays the register value in binary (base 2).
ASCII - displays bytes of the register value as ASCII characters. The number of characters displayed depends on the register Type.
Label - displays labels in place of the register value. The labels are defined in the register properties. This selection is not available if labels are not defined for the register.
Bit 00, Bit 01, … , Bit 31 - displays the selected bit from the register as a Boolean. If the bit is 0 then OFF is displayed. If the bit is non-zero then
ON is displayed. I the register cannot be edited from the Table View if this format is selected. Valid values are Bit 00 to Bit 31 for 32-bit data types, and Bit 00 to Bit 15 for 16-bit data types.
Realflo User and Reference Manual
May 19, 2011
236
Columns Dialog
Realflo Expert Mode Reference
The default selection value is Decimal. Changing selection doesn‟t affect the display of Register Properties. The selection will be changed to Decimal if the previous selection is no longer valid after changing register or editing register properties.
The Register Properties displays the properties of the selected register.
The properties are updated when the Register is changed.
The OK button saves the changes and closes the dialog.
The Cancel button closes the dialog without saving any changes.
The Edit button is used to edit the register object properties. When selected the Register Properties dialog is opened.
The Columns dialog is used to define the columns displayed on the Table view and the Edit Register dialog. This does not affect the columns shown in the Edit Table View dialog.
The columns to be displayed can be defined for each Access Level so different users see different information. Select the column to show it on in the Table view. Columns are enabled by default when a view is created.
Tag - selects if the register tag is shown.
Description - selects if the description is shown.
Address - selects if the register address is shown.
Value - selects if the register value is shown.
Forced - selects if the force status is shown.
Type - selects if the register type is shown.
Format - selects if the display format is shown.
Writeable - selects if the writeable status is shown.
Initial Value - selects if the initial value is shown.
Realflo User and Reference Manual
May 19, 2011
237
Realflo Expert Mode Reference
Custom View Window
The Custom View window displays the registers for a custom view in a tabular format. Each row in the table displays one register.
Editing Data
The Custom View window displays the following columns. Some columns may not appear if they are not enabled on the view.
The Tag column displays the name of the register.
The Description column displays the description of the register.
The Address column displays the register address.
The Value column displays the value of the register in the format defined for the view. If the Label format is selected and the value is not in the label list then Invalid (value) is displayed. If data is not available value shows ----.
The Forced column displays if the register value is forced. If data is not available forced shows ----.
The Type column displays the type of register.
The Format column displays the format of the value.
The Writeable column displays if the user can write to the register. A register is not writeable if the Format is set to Bit.
The Initial Value column displays the initial value for the register if one is defined, or ---- if a value is not defined.
Clicking on the column headings will sort the table, in ascending order, according to the column selected. Clicking subsequent times on the same column toggles the sort order between descending and ascending order.
Click on any row to select it. Hold down Shift and click on any row to select the range from the currently selected row to the new row. Hold down Ctrl key and click on any row to toggle the selection of that row.
To change the column width, position the cursor over the line separating the columns in the heading. The cursor changes to a vertical bar with arrows pointing left and right. Click on the line and slide the mouse left or right.
Release the mouse button when the column is the desired width.
Use the Flow Computer menu commands Update Readings or Update
Readings Once to poll the flow computer for the value and force status of registers.
There are several ways to edit registers and data in a Custom View.
Select a row and, from the Edit menu, choose the Register command to open the Edit Register Value dialog.
Double-click on a row open the Edit Register Value dialog.
Realflo User and Reference Manual
May 19, 2011
238
Realflo Expert Mode Reference
Select a row and press the Enter key to open the Edit Register Value dialog.
The above commands are disabled if the Writeable parameter of the register is set to No, if the display format is set to Bit or if the Update
Readings is not enabled.
Printing and Exporting Data
To print or export part of the data in the Custom View, select the desired rows then use the Print or Export function.
Register Command
The Register command is used to modify the value or force status of a selected register in a Custom View. This command is disabled if the Update
Readings command is turned off. When this command is selected the Edit
Register Value dialog is opened.
The dialog appears as follows for the decimal, ASCII, hexadecimal, binary and BIT formats.
The dialog appears as follows for the Boolean, and Label formats.
The Value field is the register value for decimal, ASCII, hexadecimal, binary and BIT formats. For Boolean and Label formats a dropdown menu is used to select the Value.
Realflo User and Reference Manual
May 19, 2011
239
Realflo Expert Mode Reference
Valid values depend on the register type as shown in the table below. Value initially shows the current value of the register in the format defined for the view. If the Label format is selected and the value is not in the label list then
Invalid (value) is displayed.
Type Minimum Value Maximum Value
Boolean
Signed Integer
OFF
-32768
Unsigned Integer 0
Signed Double -2147483648
Unsigned Double 0
Floating Point Any
ISaGRAF Integer -2147483648
ON
32767
65535
2147483647
4294967295
Any
2147483647
Double register variables like counters use the Unsigned Double type with
Telepace firmware and use the ISaGRAF integer type with ISaGRAF firmware.
The Forced dropdown menu selects if the register value is forced. The selections are Yes or No.
The Register, Tag, Description, Type, and Format fields display information about the register. These fields cannot be changed. Data is displayed only if the corresponding column appears in the Table View; otherwise the field is blank.
The OK button writes the value and force status to the flow computer and closes the dialog.
The Cancel button closes the dialog without any changes.
The Initial Value button sets Value to the initial value defined for the register. This button is disabled if no initial value is defined.
The Apply button writes the value and force status to the flow computer.
Write Initial Values Command
The Write Initial Values command is used to write initial values for all
Custom Views or for selected Custom Views. This command is disabled if the Update Readings command is turned off. When this command is selected the Write Initial Values dialog is opened.
Realflo User and Reference Manual
May 19, 2011
240
Realflo Expert Mode Reference
The All Views selection will write initial values to registers for all defined views. Registers with an initial value are written.
The Selected Views writes initial values to registers on the selected views only. All registers with an initial value on the selected views are written.
Click on a row in the list to select it.
Hold down Ctrl and click on a row to select or deselect multiple rows.
Hold down Shift and click on a row to select a range of rows.
The OK button writes the initial values and closes the dialog.
The Cancel button closes the dialog with no changes.
Template Steps
This command is available only when a template file is opened in Realflo. A template is used to create a new flow computer from a pre-set configuration.
The template specifies what data is pre-set and what needs to be entered when the template is used.
History, event, or alarm logs are not stored in templates. A history view can be opened in a template file, but it will be empty. This allows views to be arranged when the template is edited. The view arrangement is stored in the template.
Creating a Template File
Realflo can save a configuration as a template file for new flow computers.
New flow computer files can then be created from a template using the New
File wizard.
To create a template file:
Realflo User and Reference Manual
May 19, 2011
241
Realflo Expert Mode Reference
Open a Realflo configuration file (TFC) and use the Save As command to save the file as a Realflo Template (RTC).
Selecting Template Steps
When the Template Steps command is selected the Show Template Steps dialog is displayed as shown below. A template provides default data for many of the steps in a new file wizard. To make it easier to use a template, some steps in the New File wizard may be skipped. These steps can be configured for each flow computer template.
All template steps are selected by default. To configure the steps shown for a template:
Check the steps that should be displayed. Checking or a node automatically selects all the steps within that node.
Click OK.
Realflo User and Reference Manual
May 19, 2011
242
Realflo Expert Mode Reference
View Menu
The view menu commands select the data that is displayed in the active window. This data includes current readings, hourly history, daily history, event and alarm Logs. Each record in the displayed data file is generated in response to a predefined trigger. Refer to the section for each data file for details on the list of triggers.
The visibility of the Toolbar and Status Bar is controlled from the view menu.
Current Readings Command
Use this command to display the Current Readings view for the selected run. This view displays current measured and calculated values from the flow computer. The current readings view will appear differently depending on the run configuration. The dialog is a property sheet with tabs for each flow run configured in the flow computer. Click the Run1 tab to display run 1,
Run 2 to display run2, and so on.
The view is divided into five sections that are described below:
Process Measurements
This section displays the live and forced values for the flow calculation process inputs. The live values show the value read from the sensor. The forced values show the inputs to the flow calculation when they are forced.
The forced values are disabled when the input is live. The forced values are shown in red when the value is forced.
The units of measurement displayed are those in effect when the readings were made. See Measurement Units for a description of the unit types.
Process measurements not used by the flow calculation are disabled.
Forced values are not displayed for Flow Computers older than 6.0.
Calculated Compressibility
This section displays the results of the compressibility calculation selected in the Input Configuration property page. The time of the last compressibility calculation update and any compressibility calculation errors are also
Realflo User and Reference Manual
May 19, 2011
243
Realflo Expert Mode Reference displayed in this section. The units of measurement displayed are those in
effect when the readings were made (see
description of the unit types).
Calculation Status
The Calculation Status section displays the Calculation State of the flow computer calculations for the run. Refer to the Calculation Control command in the Flow Computer menu for further information on flow calculation control.
The Calculation State Start and Stop button is disabled for users who have a read and view privileges account.
The Calculation State can be changed using the start or stop button beside the Calculation State display.
When the Current Readings are being updated and the calculation is
stopped or not set then the button is labeled Start.
When the Current Readings are being updated and the calculation is
running then the button is labeled Stop.
When the Current Readings are not being updated the button is disabled and no text is displayed on it.
Click on the button to change the Calculation State.
If the calculations are stopped the following message box is displayed.
If Yes is selected the flow calculations for the run are started.
If No is selected the message box is closed and no further action is taken.
If the calculations are running the following message box is displayed.
If Yes is selected the flow calculations for the run are stopped.
If No is selected the message box is closed and no further action is taken.
The Last Flow Configuration displays the time stamp of the last time the flow configuration was changed.
The Last Density Configuration displays the time stamp of the last time the compressibility configuration was changed.
Realflo User and Reference Manual
May 19, 2011
244
Realflo Expert Mode Reference
The Last Flow Configuration and Last Density Configuration values are not displayed for flow computers older than 6.0.
Pulse Input Volume
This section displays pulse and accumulated flow volumes for the onboard counter of a SolarPack 410. This section applies only to the SolarPack 410 system.
Data displayed is as follows:
Pulses: Raw instantaneous pulse count
Today: An accumulation of today‟s total.
Yesterday: An accumulation of yesterday‟s total.
This Month: An accumulation of the totals for this month.
Last Month: An accumulation of the totals for last month.
Total: A running total volume since the beginning of this operation.
Volumes are listed in the unit selected when configuring the Pulse Input.
Calculated Flow at Base Condition
The Calculated Flow displays the instantaneous Flow Mass Rate, Standard
Flow Volume Rate, Flow Energy Rate, Flow Product, Time of last update, and Input and Flow Calculation Status. The Flow Extension is displayed when the run is configured for AGA-3 (1990) calculations. The Flow Product is displayed when the run is configured for AGA-3 (1990) calculations. The time of the last flow calculation and input and flow calculation status are also displayed. The units of measurement displayed are those in effect when the
for a description of the unit types.
Calculated Flow (PEMEX)
The Calculated Flow displays the instantaneous Flow Volume Rate,
Standard Flow Volume Rate, Flow Energy Rate, Flow Product, Time of last update, and Input and Flow Calculation Status. The Flow Extension is displayed when the run is configured for AGA-3 (1990) calculations. The
Flow Product is displayed when the run is configured for AGA-3 (1990) calculations. The time of the last flow calculation and input and flow calculation status are also displayed. The units of measurement displayed
are those in effect when the readings were made. See
for a description of the unit types.
Accumulated Flow Base Conditions
The Accumulated Flow section displays the flow volume for the current contract day (Today) and the previous contract day (Yesterday). Data is copied from the current contract day (Today) to the previous contract day
(Yesterday) at the end of the contract day, as measured by the real time clock. Data is not copied when a new day is started for other reasons. It also displays the standard flow volume, flow energy, the number of flow calculations. The units of measurement displayed are those in effect when
for a description of the unit types.
Realflo User and Reference Manual
May 19, 2011
245
Realflo Expert Mode Reference
This section also displays the accumulated flow volume and flow time for the current month and the previous month. Data is copied from the current month (This Month) to the previous month (Last Month) at the end of the contract day at the end of the month, as measured by the real time clock.
Accumulated Flow (PEMEX)
The Accumulated Flow section displays the PEMEX flow volume for the current contract day (Today) and the previous contract day (Yesterday).
Data is copied from the current contract day (Today) to the previous contract day (Yesterday) at the end of the contract day, as measured by the real time clock. Data is not copied when a new day is started for other reasons. It also displays the standard flow volume, flow energy, the number of flow calculations. The units of measurement displayed are those in effect when
for a full description of the unit types.
This section also displays the accumulated flow volume and flow time for the current month and the previous month. Data is copied from the current month (This Month) to the previous month (Last Month) at the end of the contract day at the end of the month, as measured by the real time clock.
Accumulated Uncorrected Flow
The Accumulated Uncorrected Flow section displays the total calculated uncorrected flow volume (AGA-7 only) for the current contract day, the previous contract day, the current month and the last month.
The view is updated according to the status of the Update Readings selection in the Maintenance menu.
Battery Charger
This section applies only to the SolarPack 410.
The Battery Status indicates the current state of the solar panel charger.
The Temperature Sensor indicates the status of the battery charger temperature sensor.
Hourly History Command
Use this command to display the Hourly History view or the Hourly Gas
Quality History view for the selected run.
Hourly History View
Select Hourly History from the View menu to view the Hourly History table.
This view shows a table of flow measurements. Each row in the table represents one period (nominally one hour) of flow history.
Data in this view is updated when Hourly History is read from the controller when you click Read Logs and History.
The units of measurement displayed are those in effect when the readings were made. See Measurement Units for a description of the unit types.
New Hour Triggers
Realflo User and Reference Manual
May 19, 2011
246
Realflo Expert Mode Reference
A break in the hourly log is made when new hour is triggered. When a new hour is triggered the current hourly record is closed and a new hourly record is created.
A new record is created and added to the hourly history when any of the following triggers occur:
Power on.
At the end of each hour.
When the clock is changed to a new time that is within the current day.
AGA-3 (1985 or 1992) configuration change.
V-Cone configuration change.
AGA-8 configuration change. An AGA-8 configuration change does not start a new hour if the flow computer is set to ignore gas quality changes.
NX-19 configuration change.
Flow calculation stopped. (Stopping calculations ends the current hour.
Starting calculations starts the new hour).
Any of the items marked with an asterisk under the Input Configuration is changed.
Contract configuration change, all parameters except the Wet Gas
Meter factor for versions 6.21 and newer.
Realflo Standard and GOST Modes Hourly History Views
The columns in the tables are listed below. Some columns are not used for some types of flow calculation.
The Start Time column displays the date and time of the start of the period.
For flow computers using earlier versions of Realflo, Realflo will display ``---
`` in the Start Time column. For flow computers using Realflo 6.70 or higher,
Realflo will display the start time for the period.
The End Time column displays the date and time of the end of the period.
The Flow Time column displays the time of flow, in seconds, for the period.
The Volume column displays the corrected flow volume at standard conditions for the period.
The Mass column displays the calculated flow mass for the period.
The Energy column displays the calculated flow energy for the period based on real heating value.
The Temperature column displays the average temperature in the period.
When the Flow Time is zero, the value will be the average temperature for the entire hour or hour fragment.
The Pressure column displays the average pressure in the period. When the Flow Time is zero, the value will be the average pressure for the entire hour or hour fragment.
The Differential Pressure column displays the average differential pressure in the period.
Realflo User and Reference Manual
May 19, 2011
247
Realflo Expert Mode Reference
The Meter Pulses column displays the number of meter pulses in the period
(AGA-7 only).
The Relative Density column displays the average relative density value for the period.
The Flow Extension column displays the average flow extension value for the period. The flow extension is calculated based on the AGA-3 calculation being used:
For AGA-3 (1985)
Flow Extension = square root of the Flow Product
Where
Flow Product = Upstream Static Pressure * Differential Pressure
For AGA-3 (1992)
Flow Extension = square root of the Flow Product
Where
Flow Product = Density of the fluid at flowing conditions * Differential
Pressure
The Uncorrected Volume column displays the calculated uncorrected flow volume for the period (AGA-7 only).
The Events column displays the number of Events if there are events in the
Event Log within the period. Zero is displayed if there are no Events within the period.
The Alarms column displays the number of Alarms if there are Alarms in the
Alarm Log within the period. Zero is displayed if there are no Alarms within the period.
For flow computers earlier than version 6.70, the events and alarms displayed will be calculated the number of events based on the event log.
For flow computers version 6.70 or higher, Realflo will read the value from the flow computer.
Realflo PEMEX Mode Hourly History View
The columns for PEMEX are listed below.
The Start Time column displays the date and time of the start of the period.
See section Historic Record Format for information on the units used in
the Daily History table.
For flow computers using earlier versions of Realflo, Realflo will display ``---
`` in the Start Time column. For flow computers using Realflo 6.70 or higher,
Realflo will display the start time for the period.
The End Time column displays the date and time of the end of the period.
The Flow Time column displays the time of flow, in seconds, for the period.
The Volume column displays the corrected flow volume at standard conditions for the period.
The Volume PEMEX column displays the corrected flow volume at secondary conditions for the period.
Realflo User and Reference Manual
May 19, 2011
248
Realflo Expert Mode Reference
The Energy column displays the calculated flow energy for the period based on real heating value.
The Temperature column displays the average temperature in the period.
When the Flow Time is zero, the value will be the average temperature for the entire hour or hour fragment.
The Pressure column displays the average pressure in the period. When the Flow Time is zero, the value will be the average pressure for the entire hour or hour fragment.
The Differential Pressure column displays the average differential pressure in the period.
The Meter Pulses column displays the number of meter pulses in the period
(AGA-7 only).
The Relative Density column displays the average relative density value for the period.
The Flow Extension column displays the average flow extension value for the period. The flow extension is calculated based on the AGA-3 calculation being used:
For AGA-3 (1985)
Flow Extension = square root of the Flow Product
Where
Flow Product = Upstream Static Pressure * Differential Pressure
For AGA-3 (1992)
Flow Extension = square root of the Flow Product
Where
Flow Product = Density of the fluid at flowing conditions * Differential
Pressure
The Uncorrected Volume column displays the calculated uncorrected flow volume (for the period (AGA-7 only).
The Events column displays Events if there are events in the Event Log within the period. None is displayed if there are no Events within the period.
The Alarms column displays Alarms if there are Alarms in the Alarm Log within the period. None is displayed if there are no Alarms within the period.
For flow computers earlier than version 6.70, the events and alarms displayed will be calculated the number of events based on the event log.
For flow computers version 6.70 or higher, Realflo will read the value from the flow computer.
The Up Time column displays the time of flow in minutes for the day.
The Heating value column displays average heating value for the period.
The Quality column indicates if there are alarms during the period. It shows
1 if alarms occurred and 0 if no alarms occurred.
Daily History Command
Select Daily History from the View menu to view the Daily History table.
Realflo User and Reference Manual
May 19, 2011
249
Realflo Expert Mode Reference
Use this command to display the Daily History view for the selected run.
This view shows a table of flow measurements. Each row in the table represents one period (nominally one day) of flow history.
Data in this view is updated when Daily History is read from the flow computer with the Read Logs and History command.
The units of measurement displayed are those in effect when the readings were made. See Measurement Units for a full description of the unit types.
New Day Triggers
A new record is added to the daily history when any of the following triggers occur:
Power on ( when contract hour passed while power was off);
Time passed contract hour;
Real time clock changed outside contract day;
Change in input configuration of these parameters: o Flow calculation type o Compressibility calculation type
Contract configuration change
All parameters except the Wet Gas Meter factor for versions 6.21 and newer.
Realflo Standard and GOST Modes Daily History Views
The Daily History table contains the following information, divided into columns in the table. The columns in the table are listed below. Some columns are not used for some types of flow calculation.
The Start Time column displays the date and time of the start of the period.
For flow computers using earlier versions of Realflo, Realflo will display ``---
`` in the Start Time column. For flow computers using Realflo 6.70 or higher,
Realflo will display the start time for the period.
The End Time column displays the date and time of the end of the period.
The Flow Time column displays the time of flow, in seconds, in the period.
The Volume column displays the corrected flow volume at standard conditions for the period.
The Mass column displays the calculated flow mass for the period.
The Energy column displays the calculated flow energy for the period based on real heating value.
The Temperature column displays the average temperature in the period.
The Pressure column displays the average pressure in the period.
The Differential Pressure column displays the average differential pressure in the period.
The Meter Pulses column displays the number of meter pulses in the period
(AGA-7 only).
The Relative Density column displays the average relative density value for the period.
Realflo User and Reference Manual
May 19, 2011
250
Realflo Expert Mode Reference
The Flow Extension column displays the average flow extension value for the period. The flow extension is calculated based on the AGA-3 calculation being used:
For AGA-3 (1985)
Flow Extension = square root of the Flow Product
Where
Flow Product = Upstream Static Pressure * Differential Pressure
For AGA-3 (1992)
Flow Extension = square root of the Flow Product
Where
Flow Product = Density of the fluid at flowing conditions * Differential
Pressure
The Uncorrected Volume column displays the calculated uncorrected flow volume for the period (AGA-7 only).
The Events column displays the number of Events if there are events in the
Event Log within the period. Zero is displayed if there are no Events within the period.
The Alarms column displays number of Alarms if there are Alarms in the
Alarm Log within the period. Zero is displayed if there are no Alarms within the period.
For flow computers earlier than version 6.70, the events and alarms displayed will be calculated the number of events based on the event log.
For flow computers version 6.70 or higher, Realflo will read the value from the flow computer.
Realflo PEMEX Mode Daily History View
The PEMEX mode Daily History table contains the following information, divided into columns in the table. The columns in the table are listed below.
Not all columns are used for all types of flow calculation.
See section Historic Record Format for information on the units used in
the Daily History table.
The Start Time column displays the date and time of the start of the period.
For flow computers using earlier versions of Realflo, Realflo will display ``---
`` in the Start Time column. For flow computers using Realflo 6.70 or higher,
Realflo will display the start time for the period.
The End Time column displays the date and time of the end of the period.
The Flow Time column displays the time of flow, in seconds, in the period.
The Volume column displays the corrected flow volume at standard conditions for the period.
The Volume PEMEX column displays the corrected flow volume at secondary conditions for the period.
The Energy column displays the calculated flow energy for the period based on real heating value.
The Temperature column displays the average temperature in the period.
Realflo User and Reference Manual
May 19, 2011
251
Realflo Expert Mode Reference
The Pressure column displays the average pressure in the period.
The Differential Pressure column displays the average differential pressure in the period.
The Meter Pulses column displays the number of meter pulses in the period
(AGA-7 only).
The Relative Density column displays the average relative density value for the period.
The Flow Extension column displays the average flow extension value for the period. The flow extension is calculated based on the AGA-3 calculation being used:
For AGA-3 (1985)
Flow Extension = square root of the Flow Product
Where
Flow Product = Upstream Static Pressure * Differential Pressure
For AGA-3 (1992)
Flow Extension = square root of the Flow Product
Where
Flow Product = Density of the fluid at flowing conditions * Differential
Pressure
The Uncorrected Volume column displays the calculated uncorrected flow volume for the period (AGA-7 only).
The Heating value column displays average heating value for the period.
The Events column displays the number of Events if there are events in the
Event Log within the period. Zero is displayed if there are no Events within the period.
The Alarms column displays number of Alarms if there are Alarms in the
Alarm Log within the period. Zero is displayed if there are no Alarms within the period.
For flow computers earlier than version 6.70, the events and alarms displayed will be calculated the number of events based on the event log.
For flow computers version 6.70 or higher, Realflo will read the value from the flow computer.
The Quality column indicates if there are alarms during the period. It shows
1 if alarms occurred and 0 if no alarms occurred.
The Up Time column displays the time of flow in minutes for the day.
Hourly Gas Quality History Command
Use this command to display the accumulated gas component values for the period since the previous gas composition message or the beginning of the hourly record (whichever has the later time stamp). At the end of the period, a maximum one hour, the average gas component values are calculated.
Select Hourly Gas Quality History from the View menu to view the
Hourly Gas Quality History table.
Realflo User and Reference Manual
May 19, 2011
252
Realflo Expert Mode Reference
This view shows a table of gas quality average values. Each row in the table represents one period (nominally one hour) of gas quality history.
Data in this view is updated when Hourly Gas Quality History is read from the controller when you click Read Logs and History.
New Hour Triggers
A break in the hourly log is made when new hour is triggered. When a new hour is triggered the current hourly record is closed and a new hourly record is created.
A new record is added to the hourly gas quality history when any of the following triggers occur:
Power on.
Time passed end of hour.
When the clock is changed to a new time that is within the current day.
V-Cone configuration change.
AGA-8 configuration change. An AGA-8 configuration change does not start a new hour if the flow computer is set to ignore gas quality changes.
AGA-7 configuration change.
AGA-385 configuration change.
AGA-392 configuration change.
Flow calculation stopped. (Stopping calculations ends the current hour.
Starting calculations starts the new hour.)
Change to input configuration.
Change to contract configuration.
Start calculations (stopping calculations ends the current hour, starting calculations starts the new hour).
Hourly Gas Quality History View
The columns in the table are listed below.
Gas Quality History Columns
The Start Time column displays the date and time of the start of the period.
The End Time column displays the date and time of the end of the period.
The Operational Time column displays the value, in seconds, how long the meter run was running during the period.
The Methane column displays the average percentage of methane in the gas composition for the period.
The Nitrogen column displays the percentage of nitrogen in the gas composition for the period.
The Carbon Dioxide column displays the average percentage of carbon dioxide in the gas composition for the period.
The Ethane column displays the average percentage of ethane in the gas composition for the period.
Realflo User and Reference Manual
May 19, 2011
253
Realflo Expert Mode Reference
The Propane column displays the average percentage of propane in the gas composition for the period.
The Water column displays the average percentage of water in gas composition for the period.
The Hydrogen Sulphide column displays the average percentage of hydrogen sulphide in the gas composition for the period.
The Hydrogen column displays the average percentage of hydrogen in the gas composition for the period.
The Carbon Monoxide column displays the average percentage of carbon monoxide in the gas composition for the period.
The Oxygen column displays the average percentage of oxygene in the gas composition for the period.
The i-Butane column displays the average percentage of i-Butane in the gas composition for the period.
The n-Butane column displays the average percentage of n-Butane in the gas composition for the period.
The i-Petane column displays the average percentage of i-Petane in the gas composition for the period.
The n-Petane column displays the average percentage of n-Petane in the gas composition for the period.
The n-Hexane column displays the average percentage of n-Hexane in the gas composition for the period.
The n-Heptane column displays the average percentage of n-Heptane in the gas composition for the period.
The n-Octane column displays the average percentage of n-Octane in the gas composition e for the period.
The n-Nonane column displays the average percentage of n-Nonane in the gas composition for the period.
The n-Decane column displays the average percentage of n-Decane in the gas composition for the period.
The Helium column displays the average percentage of helium in gas composition for the period.
The Argon column displays the average percentage of argon in the gas composition for the period.
The Relative Density column displays the average relative density value for the period.
The Heating Value column displays the average heating value in
BTU(60)/ft
3
of the gas composition for the period.
The HexanesPlus column displays the average percentage of hexaneplus in gas composition for the period.
Event Log Command
Use this command to display the Event Log view for the selected run. This view displays the event log from the flow computer. The view is a table, with
Realflo User and Reference Manual
May 19, 2011
254
Realflo Expert Mode Reference each row in the table representing one event, that being, a Realflo configuration change.
Events are numbered sequentially from 1 to 65535, with automatic rollover allowing for verification that events have been duly recorded when reviewing event history.
Data in this view is updated when Event Log is read from the flow computer with the Read Logs/History from Controller command. Data in this view is also updated when hourly history is read from the controller with the Read
Logs/History command from the Flow Computer menu. To delete the events read from the log in the flow computer, select Just Read New
Events.
If the events in the log are not purged and the event log fills with 700 events, the oldest events are lost and the lost event counter is incremented. Events are numbered sequentially from 1 to 65535, with automatic rollover allowing for verification that events have been duly recorded when reviewing alarm history.
Each event in the log contains the following information, divided into columns in the table.
The Time column displays the date and time of the event in the short format defined from the Windows Control Panel.
The Event Number column displays the unique event number for the event (module 65536) as read from the flow computer.
The Event ID column displays the code identifying the event.
The Event Type column displays the description of the Event ID code.
The New Value column displays the new data associated with the event. If a configuration parameter was changed, for example, the new value of the parameter is displayed.
The Previous Value column displays the previous data associated with the event. If a configuration parameter was changed, for example, the previous value of the parameter is displayed. Some events don‟t record a previous value. In that case a value of 0 is displayed.
The userID column displays the code identifying the user that caused the event.
The User Name column displays the account name of the user that caused the event.
Alarm Log Command
Use this command to display the Alarm Log view for the selected run. This view displays the alarm log from the flow computer. The view is a table, with each row in the table representing one alarm, that being, a dynamic change that affects the outcome of the calculations, for example, if communications are lost between the flow computer and sensor.
Alarms are numbered sequentially from 1 to 65535, with automatic rollover allowing for verification that alarms have been duly recorded when reviewing alarm history.
Data in this view is updated when Alarm Log is read from the flow computer with the Read Logs/History from Controller command. Data in this view is also updated when hourly history is read from the flow computer with the
Realflo User and Reference Manual
May 19, 2011
255
Realflo Expert Mode Reference
Read Logs/History command. To delete the alarms read from the log in the flow computer, select Just Read New Alarms.
If the alarms in the log are not acknowledged and the alarm log fills with 300 alarms, the oldest alarms are lost and the lost alarm counter is incremented.
Alarms are numbered sequentially from 1 to 65535, with automatic rollover allowing for verification that all alarms have been duly recorded when reviewing alarm history.
Each alarm in the log contains the following information, divided into columns in the table.
The Time column displays the date and time of the alarm in the short format defined from the Windows Control Panel.
The Alarm Number column displays the unique alarm number for the event (module 65536) as read from the flow computer.
The Alarm ID column displays the code identifying the alarm.
The Alarm Type column displays the description of alarm.
The New Value column displays the new data associated with the alarm.
The Previous Value column displays the previous data associated with the alarm.
Some alarms don‟t include a previous value. In that case a value of 0 is displayed.
The userID column displays the code identifying the user that caused the alarm.
The User Name column displays the account name of the user that caused the alarm.
More Views Command
Use these commands to change the Custom View. The view type is not changed. If the Change All Views option is selected, opened views are changed to the selected Custom View. Otherwise, only the current view is changed. When more than nine custom views are available the More Views command is enabled.
The Custom Views displayed will depend on the number of custom views created. The Custom Views displayed will have the format:
1 Custom View
2 Custom View
3 Custom View
4 Custom View
5 Custom View
6 Custom View
7 Custom View
8 Custom View
9 Custom View
More Views
When the More Views command is selected the Select Custom View dialog is opened.
The Select Custom View dialog displays a list of custom views. The list shows the views that are available to the current user. Views that require a
Realflo User and Reference Manual
May 19, 2011
256
Realflo Expert Mode Reference higher access level are not shown. Refer to the Accounts section for more information on Access Levels.
The views are sorted in alphabetical order.
Click on a view in the list to select it. Double click on a view in the list to show the selected view in the current window and close the dialog.
The OK button shows the selected view in the current window and closes the dialog.
The Cancel button closes the dialog
Run 1 . . . Run 10 Commands
Use these commands to change the run being viewed to the selected run.
The view type is not changed. If the Change All Views option is selected, opened views are changed to the selected run. Otherwise, only the current view is changed.
The Runs displayed are:
Run 1
Run 2
Run 3
Run 4
Run 5
Run 6
Run 7
Run 8
Run 9
Run 10
Commands for runs that are not enabled in the current file are grayed.
Realflo User and Reference Manual
May 19, 2011
257
Realflo Expert Mode Reference
Change All Views Command
Use this command to select if all views are affected by the Run commands, or if only the current view is affected. A checkmark appears to the left of the item if all views are selected.
Modifying History and Log Views
The history and log view tables may be modified using the following options.
Sorting Data
Clicking on the column headings will sort the table, in ascending order, according to the column selected. Click on the same column heading again to toggle the sort order from ascending to descending order.
Sizing Columns
Positioning the cursor over the line separating the columns in the heading can change the column widths. The cursor changes to a vertical bar with arrows pointing left and right. Click on the line then slide the mouse left or right. Release the mouse button when the column is the desired width.
Selecting Data
Click on any row to select it. Hold down Shift and click on any row to select the range from the currently selected row to the new row. Hold down Ctrl and click on any row to toggle the selection of that row.
Printing and Exporting Data
To print or export part of the data, select the desired rows then use the Print or Export function.
Toolbar Command
Use this command to display and hide the toolbars, which includes buttons for some of the common commands in Realflo. A check mark appears next
to the menu item when the toolbar is displayed. See the Standard Toolbar
section for help on using the toolbar.
Status Bar Command
Use this command to display and hide the Status Bar. The Status bar appears at the bottom of the main window. It displays information about the command selected and other status information. A check mark appears next
to the menu item when the Status Bar is displayed. See
for help on using the status bar.
Maintenance Mode
Use this command to switch to the Maintenance Mode screen in Realflo.
Click the Maintenance Mode command to switch to Maintenance
Mode.
Start in Expert Mode
Realflo starts in maintenance mode by default. Advanced users can select to have Realflo start in expert mode.
Click the Start in Expert Mode command to have Realflo start with the
Expert Mode window opened.
Realflo User and Reference Manual
May 19, 2011
258
Realflo Expert Mode Reference
A check mark is displayed beside the Start in Expert Mode command indicating the selection.
Realflo User and Reference Manual
May 19, 2011
259
Realflo Expert Mode Reference
Configuration Menu
Replace Flow Computer
The Replace Flow Computer command enables users to replace the flow computer. This is typically required only when a new version of flow computer is available.
When selected, the command starts the Replace Flow Computer wizard to
guide you through the steps to replace the flow computer (see the
section).
Collect Logs and Flow History
This step selects whether the logs and flow history are read before replacing the flow computer program and if the new flow computer is initialized with the logs and flow history from the current flow computer.
The first question, Do you want to collect the flow history and logs?
Determines if the flow history and logs are to be read from the current flow computer before it is replaced.
Select Yes to collect the logs and flow history. This is the default selection.
Select No to discard the uncollected logs and flow history.
The second question, Do you want to initialize new Flow Computer with
history values from the current Flow Computer? Selects whether the new flow computer will be initialized with the flow history and logs are read from the current flow computer once the new flow computer is written.
Select Yes to initialize the new flow computer with history values. This is the default selection.
Select No to discard the history values of the current Flow Computer.
The Next button moves to the next step. The next step is Replace Account
Codes if the current account includes some non-default account, otherwise the next step is Read Configurations if collect the logs and flow history
option is selected, otherwise the next step is Replace Flow Computer.
Realflo User and Reference Manual
May 19, 2011
260
Realflo Expert Mode Reference
The Cancel button closes the dialog and stops the wizard.
The Help button opens the on-line manual.
Replace Account Codes
The Replace Account Codes dialog is be displayed if the current Realflo file includes some non-default account codes. Selections allow for the account codes to be written to the flow computer or to have the account codes set for the default settings.
Select Yes, write to the Flow Computer to write the account codes. This is the default selection. The writing account codes will be done after writing the accumulated history in the Replace Flow Computer step.
Select No, remain the default settings to not write the account codes.
The Back button returns to the previous step.
The Next button moves to the next step.
The Cancel button closes the dialog and stops the wizard.
The Help button opens the on-line manual.
Read Configuration
This step selects whether the current configuration is read from the flow computer. Selections provide for reading configurations from the flow
computer or to not read configurations. See the
section of this manual for further information on what
information is read.
Realflo User and Reference Manual
May 19, 2011
261
Realflo Expert Mode Reference
Select Yes, read configuration from Flow Computer to read the configurations from flow computer. This is a default option.
Select No, do not read configuration from Flow Computer to skip reading configurations.
The Back button returns to the previous step.
The Next button reads the flow computer configuration, if selected, and moves to the next step, Select Alarms and Events.
The Cancel button closes the dialog and stops the wizard.
The Help button opens the on-line manual.
Realflo User and Reference Manual
May 19, 2011
262
Realflo Expert Mode Reference
Select Event and Alarm Logs
This step selects whether the alarms and events in the flow computer are read.
The Which Events do you want to read? selection determines which events to read from the flow computer.
Select Just Read New Events to read unacknowledged events in the flow computer. If the operator has View, Read and Write Data or
Administrator authorization then the events will be acknowledged after reading the new events. If the events in the log are not acknowledged, the event log will fill with 700 events. Operator activity will be prevented until the events are read and acknowledged. The control is grayed under the following conditions: o The event log is not selected. o The user has Read and View account privileges. o The Restrict Realflo users to reading all alarms and events option is selected in the Expert Mode Options menu.
Select Read All Events to read all events in the flow computer. This control is grayed if the Event Log control is not selected.
Select Do Not Read Any Events to skip reading of events from the flow computer.
The Which Alarms to you want to read? selection determines which alarm logs to read from the flow computer.
Select Just Read New Alarms to read unacknowledged alarms in the flow computer. If the operator has View, Read and Write Data or
Administrator authorization then the alarms will be acknowledged after reading the new events. If the events in the log are not acknowledged, the alarm log will fill with 300 events. Operator activity will be prevented until the alarms are read and acknowledged. The control is grayed under the following conditions:
The alarm log is not selected.
Realflo User and Reference Manual
May 19, 2011
263
Realflo Expert Mode Reference
The user has Read and View account privileges.
The Restrict Realflo users to reading all alarms and events option is selected in the Expert Mode Options menu.
The Read All Alarms radio button selects the reading of all alarms in the controller. The control is grayed if the Alarm control is not selected.
The Do Not Read Any Alarms button selects not to read alarms from the flow computer.
Click the Next> button to move to the next step in the wizard.
The Which Events do you want to read? section has the following selections.
Select Just Read New Events to read unacknowledged events in the flow computer. If the operator has Write authorization then the events will be acknowledged after reading the new events. If the events in the log are not acknowledged, the event log will fill with 700 events.
Operator activity will be stopped until the events are read and acknowledged. This is the default selection.
Select Read All Events to read all events in the flow computer. Do not acknowledge the events.
Select Do Not Read Any Events to skip reading events.
The Back button returns to the previous step.
The Next button reads the selected alarms and events and moves to the next step, Select Hourly History.
The Cancel button closes the dialog and stops the wizard.
The Help button opens the on-line manual.
Select Hourly and Daily History
This step selects which hourly and daily history logs are read from the flow computer.
The Which Hourly Logs do you want to read? section has the following selections.
Realflo User and Reference Manual
May 19, 2011
264
Realflo Expert Mode Reference
Select New Hours to read hourly history for days after those in the file.
If the file is empty then Realflo will read all hourly history stored in the flow computer. This is the default selection.
Select All Hours to read hourly history for all days stored in the flow computer.
Select Selected Hours to read hourly history for the range of days selected with the From and To drop-down lists. Records are read for the contract days whose first hour is within the date range. Records for the contract day are read, regardless of their calendar date. This may result in records with calendar days outside the range being added to the log.
For example, if the contract day is configured to start at 7:00 AM.
Reading hourly history for September 23 would return the records where the first record in a day was between 7:00 on the 23 the 24 th
. rd
to 6:59:59 AM on
Select Do Not Read Hourly Logs to skip the reading of hourly history.
The Which Daily Logs do you want to read? section has the following selections.
Select New Days to read daily history for days after those in the file. If the file is empty then Realflo will read daily history stored in the flow computer. This is the default selection.
Select All Days to read daily history for all days stored in the flow computer.
Select Selected Days to read daily history for the range of days selected with the From and To drop-down lists. Records are read for the contract days whose first record is within the date range. Records for the contract day are read, regardless of their calendar date. This may result in records with calendar days outside the range being added to the log. For example, if the contract day is configured to start at 7:00
AM. Reading daily history for September 23 would return the daily records whose end time is in the range 7:00 on the 23 rd
to 6:59:59 AM on the 24 th
.
Select Do Not Read Daily Logs to skip the reading of daily history.
The From controls contain the oldest previous day for which the hourly or daily history is to be read. The initial value is 35 days before the current day.
The control is enabled when the Selected Hours or Selected Days is selected. Change this date to avoid reading data that has previously been read into the log.
The To controls contain the recent previous day for which the hourly or daily history is to be read. The initial value is the current day. The allowed range is the same or greater than the value in the From control. The control is enabled when the Selected Hours or Selected Days is selected. Change this date when wanting to read older data only. Leaving this date at its default will result in the recent data being read.
The Back button returns to the previous step.
The Next button reads the selected logs and then moves to the next step,
Read Log Results.
The Cancel button closes the dialog and stops the wizard.
The Help button opens the on-line manual.
Realflo User and Reference Manual
May 19, 2011
265
Read Log Results
Realflo Expert Mode Reference
This step displays the results of the Read Logs and History steps.
The Back button returns to the previous step.
The Next button moves to the next step, Replace Flow Computer.
The Cancel button closes the dialog and stops the wizard.
The Help button opens the on-line manual.
Realflo User and Reference Manual
May 19, 2011
266
Realflo Expert Mode Reference
Replace Flow Computer Wizard
This step selects the flow computer file to write and writes the file to the flow computer.
Use the Replace Flow Computer dialog to select the flow computer program to write to the flow computer.
Select Flow Computer to write a basic flow computer program. Realflo selects the correct program file for the flow computer from the folder Realflo was started from, typically C:\Program Files\Control
Microsystems\Realflo.
The file selected will be Realflot v#.##.#.abs for Telepace firmware and
Realfloi v#.##.#.abs for ISaGRAF firmware on 16-bit SCADAPack controllers, where #.##.# is the flow computer version number.
This option is disabled if the controller type is a SCADAPack 32,
SCADAPack 314/330/334, SCADAPack 350, SCADAPack 4203 and
SolarPack 410.
Select Flow Computer with Enron Modbus to write a flow computer program with Enron Modbus support. Realflo selects the correct program file for the flow computer from the folder Realflo was started from, typically
C:\Program Files\Control Microsystems\Realflo.
Flow computer files available will depend on the Realflo operating mode and the controller type.
Standard Flow Computer Files
RFEnront v#.##.#.abs for Telepace firmware and RFEnroni v#.##.#.abs for ISaGRAF firmware for 16-bit SCADAPack controllers.
Realflot v#.##.#.out for Telepace SCADAPack 350 firmware and Realfloi v#.##.#.out for ISaGRAF SCADAPack 350 firmware.
Realflo33xt v#.##.#.out for Telepace SCADAPack 330/334 firmware and
Realflo33xi v#.##.#.out for ISaGRAF SCADAPack 330/334 firmware.
Realflo31xt v#.##.#.out for Telepace SCADAPack 314 firmware and
Realflo31xi v#.##.#.out for ISaGRAF SCADAPack 314 firmware.
Realflo User and Reference Manual
May 19, 2011
267
Realflo Expert Mode Reference
Realflo4203t v#.##.#.out for Telepace SCADAPack 4203 firmware and
Realflo4203i v#.##.#.out for ISaGRAF SCADAPack 4203 firmware.
Realflo410t v#.##.#.out for SolarPack 410 firmware.
Realflot v#.##.#.mot for Telepace SCADAPack 32 firmware and Realfloi v#.##.#.mot for ISaGRAF SCADAPack 32 firmware.
GOST Flow Computer Files
Realflo_GOST_t v#.##.#.abs for Telepace firmware and
Realflo_GOST_i v#.##.#.abs for ISaGRAF firmware for 16-bit
SCADAPack controllers.
Realflo_GOST_33xt v#.##.#.out for Telepace SCADAPack 330/334 firmware and Realflo_GOST_33xi v#.##.#.out for ISaGRAF
SCADAPack 330/334 firmware.
Realflo_GOST_31xt v#.##.#.out for Telepace SCADAPack 314 firmware and Realflo_GOST_31xi v#.##.#.out for ISaGRAF SCADAPack 314 firmware.
Realflo_GOST_4203t v#.##.#.out for Telepace SCADAPack 4203 firmware and Realflo_GOST_4203i v#.##.#.out for ISaGRAF
SCADAPack 4203 firmware.
Realflo_GOST_410t v#.##.#.out for SolarPack 410 firmware.
Realflot v#.##.#.mot for Telepace SCADAPack 32 firmware and Realfloi v#.##.#.mot for ISaGRAF SCADAPack 32 firmware.
PEMEX Flow Computer Files
Realflo_PEMEX_t v#.##.#.abs for Telepace firmware and
Realflo_PEMEX_i v#.##.#.abs for ISaGRAF firmware for 16-bit
SCADAPack controllers.
Realflo_PEMEX_33xt v#.##.#.out for Telepace SCADAPack 330/334 firmware and Realflo_PEMEX_33xi v#.##.#.out for ISaGRAF
SCADAPack 330/334 firmware.
Realflo_PEMEX_31xt v#.##.#.out for Telepace SCADAPack 314 firmware and Realflo_PEMEX_31xi v#.##.#.out for ISaGRAF
SCADAPack 314 firmware.
Realflo_PEMEX_4203t v#.##.#.out for Telepace SCADAPack 4203 firmware and Realflo_PEMEX_4203i v#.##.#.out for ISaGRAF
SCADAPack 4203 firmware.
Realflo_PEMEX_410t v#.##.#.out for SolarPack 410 firmware.
Realflot v#.##.#.mot for Telepace SCADAPack 32 firmware and Realfloi v#.##.#.mot for ISaGRAF SCADAPack 32 firmware.
Select Customer Flow Computer or C/C++ Program to write any C/C++ program to the flow computer. Select the file to write by:
Entering the file name in the edit box.
Selecting a recently used file by clicking the down arrow.
Using the Browse button to select a file. The Browse button opens a file open dialog. The dialog shows files of type ABS if the flow computer is a
SCADAPack. OUT, if the flow computer is a SCADAPack 314/330/334,
Realflo User and Reference Manual
May 19, 2011
268
Set Time
Realflo Expert Mode Reference
SCADAPack 350 or SCADAPack 4203, or MOT if the flow computer is a
SCADAPack 32.
The Back button returns to the previous step.
The Next button writes the flow computer file and moves to the next step,
Set Time.
The Cancel button closes the dialog and stops the wizard.
The Help button opens the on-line manual.
This step sets the time in the flow computer.
The following controls are available from the Real Time Clock dialog.
The current Flow Computer Time shows the current time and date in the flow computer. It is updated continuously while the dialog is open. The time and date are displayed in the short time format as defined in the Windows
Control Panel.
The Yes, set to PC Time radio button selects setting the controller time to match the PC time. The current PC time and date are shown to the right of the button. The time and date are displayed in the short format as defined in the Windows Control Panel.
The Yes, set to this time radio button selects setting the time and date to the values specified by the user in the Year, Month, Day, Hour, Minute and
Second controls. If the Set to User Entered Time radio button is not selected these controls are grayed.
The Back button returns to the previous step.
The Finish button writes the time and ends the wizard.
The Cancel button closes the dialog and stops the wizard.
The Help button opens the on-line manual.
Realflo User and Reference Manual
May 19, 2011
269
Realflo Expert Mode Reference
Write Flow Computer Configuration
The Write Configuration command is used to write all or selected parts of the Flow Computer Configuration. When selected the command displays the
Write Flow Computer Configuration dialog as shown below.
The All Configuration radio button, when selected, results in the writing of all configuration data from the flow computer.
The Selected Configuration radio button enables specific configuration data to be written to the flow computer.
Select Communication and I/O Settings to write the serial port, register assignment configuration information and mapping table.
Select Flow Run and MVT Configuration to write the flow run configuration and the MVT transmitter configuration.
Select Process I/O Configuration to write the Process I/O configuration.
Select Force Inputs to write the force status of any forced flow run inputs before the flow computer was updated.
Click on the OK button to write the selected items to the flow computer.
Realflo User and Reference Manual
May 19, 2011
270
Realflo Expert Mode Reference
Click the Cancel button to cancel the operation and close the dialog.
The Flow Computer ID is checked before writing. If the Flow Computer
ID does not match the ID in the dialog Realflo displays an error message.
An error occurs if Controller Configuration is selected and the flow computer type is different from the flow computer type selected in the
Controller Type dialog. An error message is displayed.
In Flow Computer versions 6.73 and older, when AGA-8 gas ratios or NX-19 gas quality values are written to the flow computer the new gas ratios are updated in the Proposed registers. The Actual registers are not updated until a new Density calculation is started with the new values. The new values are not available to SCADA host software reading the Actual registers until a until a new Density calculation is started with the new values.
In Flow Computer versions 6.74 and newer when AGA-8 gas ratios or NX-
19 gas quality values are written to the flow computer the new gas ratios are updated in the Proposed registers and in the Actual registers. This allows a
SCADA host to immediately confirm the new values were written to the flow computer. The new gas values are not used by the flow computer until a new density calculation is started.
Read Alarm and Event Logs
This step selects whether the alarms and events in the flow computer are read.
The Which Events do you want to read? section has the following selections.
Select Just Read New Events to read unacknowledged events in the flow computer. If the operator has Write authorization then the events will be acknowledged after reading the new events. If the events in the log are not acknowledged, the event log will fill with 700 events.
Realflo User and Reference Manual
May 19, 2011
271
Realflo Expert Mode Reference
Operator activity will be stopped until the events are read and acknowledged. This is the default selection.
Select Read All Events to read all events in the flow computer. Do not acknowledge the events.
Select Do Not Read Any Events to skip reading events.
The Back button returns to the previous step.
The Next button reads the selected alarms and events and moves to the next step, Select Hourly History.
The Cancel button closes the dialog and stops the wizard.
The Help button opens the on-line manual.
Bluetooth Security
If a Bluetooth connection was used to replace the flow computer in a
SolarPack 410 the last step is setting the Bluetooth security.
The Bluetooth Security Settings dialog specifies how Bluetooth security is configured in the SolarPack 410 controller. Opening the dialog reads the current settings from the controller. The dialog does not open if the settings can‟t be read.
Bluetooth Security selects if security is enabled or not. Select Use current
security settings to maintain the security settings that have already been established. Select Disable to operate the Bluetooth radio without security.
Select Enable to use authentication and encryption. Select Enable and
Change PIN to use authentication and encryption with a new PIN.
Current PIN specifies the current value of the PIN. Valid values are up to 10 alphanumeric characters (a to z, A to Z, and 0 to 9). The PIN is case sensitive. Characters entered are masked. Copy and paste are disabled (so the user needs to type the PIN). The factory default PIN is default.
New PIN specifies the new value of the PIN. This control is enabled if
Enable and Change PIN is selected. Valid values are up to 10 alphanumeric characters (a to z, A to Z, and 0 to 9). The PIN is case
Realflo User and Reference Manual
May 19, 2011
272
Realflo Expert Mode Reference sensitive. Characters entered are masked. Copy and paste are disabled (so the user needs to type the PIN).
Confirm New PIN specifies the new value of the PIN. This control is enabled if Enable and Change PIN is selected. Valid values are up to 10 alphanumeric characters (a to z, A to Z, and 0 to 9). The PIN is case sensitive. Characters entered are masked. Copy and paste are disabled (so the user needs to type the PIN).
The two values of the new PIN needs to match before any settings are written to the controller.
Click Finish to write the new settings to the controller. A message is displayed if the settings cannot be written to the controller and the dialog remains open.
Click Cancel to close the dialog without making any changes.
Initialize Command
The Initialize command erases programs in the flow computer and sets the flow computer to default settings. This command is typically used when starting a new project with a flow computer. This command is disabled if the
Update Readings command is enabled. The command opens the Initialize
Flow Computer dialog. The dialog displayed will depend on whether
Telepace or ISaGRAF firmware is used in the flow computer.
Initialize Telepace Flow Computer
Check Use Default Communication and I/O Settings to reset flow computer settings to default values and clear all registers in the I/O database. This includes the serial port settings. If you are communicating
using settings other than the default, the
will have to be changed once the command is complete.
Realflo User and Reference Manual
May 19, 2011
273
Realflo Expert Mode Reference
Check Erase Register Assignment to erase the register assignments. This command applies only if Telepace firmware is loaded in the flow computer.
The command is disabled if SCADAPack 314, SCADAPack 330,
SCADAPack 334 or SCADAPack 350 is selected as the hardware type.
Check Erase Ladder Logic to erase the Telepace Ladder Logic application in the flow computer.
Check Erase Ladder Logic Program Flash to erase the Telepace Ladder
Logic application in flash memory in the flow computer. This command applies only if Telepace firmware is loaded in the controller.
Click on the Finish button to perform the requested initializations.
Click on the Cancel button to exit without performing any action.
Initialize IEC 61131-3 Flow Computer
Check Use Default Communication and I/O Settings to reset flow computer settings to default values and clear registers in the I/O database.
This includes the serial port settings. If you are communicating using
settings other than the default, the
will have to be changed once the command is complete.
Check Erase Register Assignment to erase the register assignments. The command is disabled if ISaGRAF firmware is loaded.
Check IEC 61131-3 Program to erase the IEC 61131-3 Logic application in the flow computer.
Check Erase Ladder Logic Program Flash to erase the Telepace Ladder
Logic application in flash memory in the flow computer. This command applies only if Telepace firmware is loaded in the controller. The command is disabled if ISaGRAF firmware is loaded.
Click on the Finish button to perform the requested initializations.
Click on the Cancel button to exit without performing any action.
Realflo User and Reference Manual
May 19, 2011
274
Realflo Expert Mode Reference
Erasing Programs in Flash
Erasing the flash memory requires stopping the Logic and C programs. If either flash erase command is selected the following message is displayed.
Select OK to stop the Logic program and erase the flash memory.
Select Cancel to abort the initialization of flash memory. Other selected initializations will still be performed.
Initialize SCADAPack 4203 and SolarPack 410 Flow Computer
When a SolarPack 410 is the controller type the following dialog is displayed when the Initialize command is selected.
Check Use Default Communication and I/O Settings to reset flow computer settings to default values and clear registers in the I/O database.
This includes the serial port settings. If you are communicating using
settings other than the default, the
will have to be changed once the command is complete.
The Reset Sensor and Restore Factory Calibration check box will return the sensor to factory calibration. Note that the sensor calibration, operating limits and measurement units are reset to factory calibration.
Realflo User and Reference Manual
May 19, 2011
275
Real Time Clock
Realflo Expert Mode Reference
The Real Time Clock dialog sets the real time clock in the flow computer.
This command is disabled if the Update Readings command is enabled. The user may set the clock to the PC time, to a user specified time or adjust the clock forward or back by a number of seconds.
The following methods cannot to set the real time clock when using the flow computer.
The CNFG Real Time Clock and Alarm register assignment in
Telepace.
The setclock function in IEC 61131-3.
The Real Time Clock dialog in Telepace or IEC 61131-3.
Using any of these methods to set the Real Time Clock may result in the flow computer logging data incorrectly.
The Flow Computer clock was set at the factory. However, it may be set to the wrong time zone for your location. Set the clock before configuring the flow computer so that configuiration events are stored at the correct time.
The following controls are available from the Real Time Clock dialog.
Controller Time shows the current time and date in the controller. It is updated continuously while the dialog is open. The time and date are displayed in the short time format as defined in the Windows Control Panel.
Realflo User and Reference Manual
May 19, 2011
276
Realflo Expert Mode Reference
The Set to PC Time radio button selects setting the controller time to match the PC time. The current PC time and date are shown to the right of the button. The time and date are displayed in the short format as defined in the
Windows Control Panel.
The Set to User Entered Time radio button selects setting the time and date to the values specified by the user in the Year, Month, Day, Hour,
Minute and Second controls. If the Set to User Entered Time radio button is not selected these controls are grayed.
The Adjust Forward or Backward radio button selects adjusting the time by the number of seconds specified in the Adjust Clock by Seconds edit box. The value can be negative or positive. The edit box is grayed if the
Adjust by radio button is not selected.
This option is useful if your communication network introduces a delay between the time the command is sent and when the flow computer receives it.
The Close button closes the dialog.
The Write button writes the selected time to the flow computer.
The Help button displays the help for this dialog.
Wireless Security Settings
The Wireless Security Settings dialog specifies how wireless security is configured in the SolarPack 410 controller. Opening the dialog reads the current settings from the controller. The dialog does not open if the settings can‟t be read. The pictorial representation of the dialog and description of each field is given below. This command is available on the SolarPack 410 controllers only.
Select Disable to operate the wireless radio without security. Select Enable to use authentication and encryption. Select Enable and Change PIN to use authentication and encryption with a new PIN.
Current PIN specifies the current value of the PIN. Valid values are up to 10 alphanumeric characters (a to z, A to Z, and 0 to 9). The PIN is case sensitive. Characters entered are masked. Copy and paste are disabled (so the user needs to type the PIN).
New PIN specifies the new value of the PIN. This control is enabled if
Enable and Change PIN is selected. Valid values are up to 10 alphanumeric characters (a to z, A to Z, and 0 to 9). The PIN is case
Realflo User and Reference Manual
May 19, 2011
277
Realflo Expert Mode Reference sensitive. Characters entered are masked. Copy and paste are disabled (so the user needs to type the PIN).
Confirm New PIN specifies the new value of the PIN. This control is enabled if Enable and Change PIN is selected. Valid values are up to 10 alphanumeric characters (a to z, A to Z, and 0 to 9). The PIN is case sensitive. Characters entered are masked. Copy and paste are disabled (so the user needs to type the PIN).
The two values of the new PIN needs to match before any settings are written to the controller.
Click OK to write the new settings to the controller. An error message is displayed if the settings cannot be written to the controller and the dialog remains open.
Click Cancel to close the dialog without making any changes.
Flow Computer Information
The Flow Computer Information command is used to display information about the firmware, options, and programs installed in the flow computer.
When selected, the command opens the Flow Computer Information dialog.
The Flow Computer dialog displayed depends on the Firmware Type and
Hardware Type that is running the flow computer.
Telepace Flow Computer Information
For SCADAPack 32, SCADAPack, SCADAPack 4202 and Micro16 controllers the following dialog is displayed. The Telepace firmware Program
Status is shown in the following dialog.
Runs Available is the maximum number of runs supported by the flow computer. The runs available may differ from the number of runs licensed in options section. This is typically due to other C applications and consuming
Realflo User and Reference Manual
May 19, 2011
278
Realflo Expert Mode Reference memory in the controller. For SCADAPack 32 controllers the maximum number of runs is 4 when the Gas Transmission option is enabled.
Flow Computer Version is the version of the flow computer program.
Controller Type is the type of controller hardware.
Controller ID is the unique ID assigned to the controller at the factory.
Firmware Version is the version of the firmware in the controller.
Firmware Type is the type of firmware in the controller. It is one of
Telepace, Telepace DNP, or ISaGRAF, or ISaGRAF DNP.
Ethernet Address is the Ethernet address of the controller, if an Ethernet port is available.
I/O Version is the version number of the internal I/O controller.
Flow Computer Type is the type of flow computer licensed. You can select one of the following values for this field from the dropdown list:
None
Standard
PEMEX
GOST
If you select an unlicensed flow computer type, an error message displays telling you to purchase the appropriate license.
The Options area shows the current options enabled in the controller.
The DF1 Protocol option enables communication using the Allen-
Bradley full duplex and half-duplex protocols.
The IEC 61131-3 option enables the IEC 61131-3 run-time engine.
The DNP Protocol option enables communication using the DNP
Protocol.
The Telepace option enables communication using Telepace.
The Flow Computer option enables support for the Realflo natural gas flow computer. The valid options from the dropdown list are: o Standard o PEMEX o GOST
The Runs option displays the number of runs available for the flow computer.
The Gas Transmission checkbox enables or disables calculating hourly gas quality history.
If the Flow Computer option is set to None, the Runs Available and the
Gas Transmission options are disabled.
The Edit button opens the Edit Options Dialog.
The Ladder Logic Program Status section indicates the state of the
Ladder Logic program. A program can be loaded in RAM memory and in
Realflo User and Reference Manual
May 19, 2011
279
Realflo Expert Mode Reference
Flash memory. Only one of the programs can be running. The state will be one of No Program, Stopped, or Running.
The C/C++ Program (Flow Computer) Status section indicates the state of the C/C++ program. Usually this is the flow computer program, but it could be another program. The state will be one of No Program, Stopped, or
Running.
On a SCADAPack controller with Telepace firmware 1.65 or newer, a program can be loaded in RAM memory. The controller has operating system code in the C Program section of Flash.
On a SCADAPack controller with Telepace firmware 1.64 or older, a program can be loaded in RAM memory and in Flash memory. Only one of the programs can be running.
On a SCADAPack 32 controller a program is executed from RAM memory and saved in Flash memory.
Click Run to run the C/C++ program (flow computer). If there is a program in both RAM and Flash, the program in RAM will run.
Click Stop o stop the C/C++ program (flow computer).
Close closes the dialog.
Refresh button reads information from the flow computer.
Help button opens the user manual.
Realflo User and Reference Manual
May 19, 2011
280
Realflo Expert Mode Reference
Telepace SCADAPack 314/330/334, SCADAPack 350, SCADAPack 4203 and SolarPack 410
Flow Computer Information
For SCADAPack 314/330/334, SCADAPack 350, SCADAPack 4202 and
SolarPack 410 controllers the following dialog is displayed. The
SCADAPack 314/330/334, SCADAPack 350 and SCADAPack 4203 controllers support multiple C/C++ applications. When this controller is used the Flow Computer Information dialog allows for the stopping and running of each C/C++ application independently.
Runs Available is the maximum number of runs supported by the flow computer. The runs available may differ from the number of runs licensed in options section. This is typically due to other C applications or IEC 61131-3 applications running and consuming memory in the controller.
Flow Computer Version is the version of the flow computer program.
Controller Type is the type of controller hardware.
Controller ID is the unique ID assigned to the controller at the factory.
Firmware Version is the version of the firmware in the controller.
Firmware Type is the type of firmware in the controller. It is one of
Telepace, Telepace DNP, or ISaGRAF, or ISaGRAF DNP.
Ethernet Address is the Ethernet address of the controller, if an Ethernet port is available.
I/O Version is the version number of the internal I/O controller.
Flow Computer Type is the type of flow computer licensed. This will be one of the following types:
None
Standard
Realflo User and Reference Manual
May 19, 2011
281
Realflo Expert Mode Reference
PEMEX
GOST
If you select an unlicensed flow computer type, an error message displays telling you to purchase the appropriate license.
The Options area shows the current options enabled in the controller.
The DF1 Protocol option enables communication using the Allen-
Bradley full duplex and half-duplex protocols.
The IEC 61131-3 option enables the IEC 61131-3 run-time engine.
The DNP Protocol option enables communication using the DNP
Protocol.
The Flow Computer option enables support for the Realflo natural gas flow computer. The valid options from the dropdown list are: o Standard o PEMEX o GOST
The Runs option displays the number of runs available for the flow computer.
The Gas Transmission checkbox enables or disables calculating hourly gas quality history.
If the Flow Computer option is not set the Runs Available and the Gas
Transmission options are disabled.
The Edit button opens the Edit Options Dialog.
The Ladder Logic Program Status section indicates the state of the
Ladder Logic program. A program can be loaded in RAM memory and in
Flash memory. Only one of the programs can be running. The state will be one of No Program, Stopped, or Running.
The dialog displays the C/C++ Programs that are loaded in the controller.
The status of each program is indicated as Running or Stopped.
The Close button closes the dialog.
The Refresh button reads information from the flow computer.
The Help button opens the user manual.
The Loaded C/C++ Programs section indicates the state of the C/C++ programs currently loaded in the controllers. Usually this is the flow computer program, but it could be another program. The state will be one of
No Program, Stopped, or Running.
The Run and Stop buttons apply to the C/C++ Program selected from the list of loaded C/C++ programs. Only one C/C++ Program may be selected from the list at one time. These buttons are disabled when there are no
C/C++ Programs loaded.
The Run button stops and restarts the selected C/C++ program in the controller.
The Stop button stops the selected C/C++ program in the controller.
Realflo User and Reference Manual
May 19, 2011
282
Realflo Expert Mode Reference
IEC 61131-3 Flow Computer Information
The Flow Computer Information dialog is different for ISaGRAF firmware.
The program status section appears as follows in the Flow Computer
Information dialog.
Runs Available is the maximum number of runs supported by the flow computer. The runs available may differ from the number of runs licensed in options section. This is typically due to other C applications or IEC 61131-3 applications running and consuming memory in the controller. For
SCADAPack 32 controllers the maximum number of runs is 4 when the Gas
Transmission option is enabled.
Flow Computer Version is the version of the flow computer program.
Controller Type is the type of controller hardware.
Controller ID is the unique ID assigned to the controller at the factory.
Firmware Version is the version of the firmware in the controller.
Firmware Type is the type of firmware in the controller. It is one of
Telepace, Telepace DNP, or ISaGRAF, or ISaGRAF DNP.
Ethernet Address is the Ethernet address of the controller, if an Ethernet port is available.
I/O Version is the version number of the internal I/O controller.
Flow Computer Type is the type of flow computer licensed. This will be one of the following types:
Standard
PEMEX
GOST
Realflo User and Reference Manual
May 19, 2011
283
Realflo Expert Mode Reference
If the Flow Computer option is not set the Runs Available and the Gas
Transmission options are disabled.
The Options area shows the current options enabled in the controller.
The DF1 Protocol option enables communication using the Allen-
Bradley full duplex and half-duplex protocols.
The Flow Computer option enables support for the Realflo natural gas flow computer. The Runs window displays the number of runs available for the flow computer.
The IEC 61131-3 option enables the IEC 61131-3 run-time engine.
The DNP Protocol option enables communication using the DNP
Protocol.
The Flow Computer option enables support for the Realflo natural gas flow computer. The valid options from the dropdown list are: o None o Standard o PEMEX o GOST
The Runs option displays the number of runs available for the flow computer.
The Gas Transmission checkbox enables or disables calculating hourly gas quality history.
If the Flow Computer option is not set the Runs Available and the Gas
Transmission options are disabled.
The Edit button opens the Edit Options Dialog.
The Program Status portion of the dialog depends on the controller type and the firmware. See the sections below for details.
The IEC 61131-3 Program Status section indicates the state of the IEC
61131-3 program. The state will be one of No Program, Stopped, or
Running.
The C/C++ Program (Flow Computer) Status section indicates the state of the C/C++ program. Usually this is the flow computer program, but it could be another program. The state will be one of No Program, Stopped, or
Running.
Click on the Run button to run the C/C++ program (flow computer).
Click on the Stop button to stop the C/C++ program (flow computer).
The Close button closes the dialog.
The Refresh button reads information from the flow computer.
The Help button opens the user manual.
IEC 61131-3 SCADAPack 314/330/334, SCADAPack 350 and SCADAPack 4203 Flow Computer
Information
For SCADAPack 314/330/334, SCADAPack 350 and SCADAPack 4203 controllers the following dialog is displayed. When this controller is used the
Realflo User and Reference Manual
May 19, 2011
284
Realflo Expert Mode Reference
Flow Computer Information dialog allows for the stopping and running of each C/C++ application independently.
Runs Available is the maximum number of runs supported by the flow computer. The runs available may differ from the number of runs licensed in options section. This is typically due to other C applications or IEC 61131-3 applications running and consuming memory in the controller.
Flow Computer Version is the version of the Flow Computer program.
Controller Type is the type of controller hardware.
Controller ID is the unique ID assigned to the controller at the factory.
Firmware Version is the version of the firmware in the controller.
Firmware Type is the type of firmware in the controller. It is one of
Telepace, Telepace DNP, or ISaGRAF, or ISaGRAF DNP.
Ethernet Address is the Ethernet address of the controller, if an Ethernet port is available.
I/O Version is the version number of the internal I/O controller.
Flow Computer Type is the type of flow computer licensed. This will be one of the following types:
Standard
PEMEX
GOST
If the Flow Computer option is not set the Runs Available and the Gas
Transmission options are disabled.
The Options area shows the current options enabled in the controller.
The DF1 Protocol option enables communication using the Allen-
Bradley full duplex and half-duplex protocols.
Realflo User and Reference Manual
May 19, 2011
285
Realflo Expert Mode Reference
The IEC 61131-3 option enables the IEC 61131-3 run-time engine.
The DNP Protocol option enables communication using the DNP
Protocol.
The Flow Computer option enables support for the Realflo natural gas flow computer. The valid options from the dropdown list are: o None o Standard o PEMEX o GOST
The Runs option displays the number of runs available for the flow computer.
The Gas Transmission checkbox enables or disables calculating hourly gas quality history.
If the Flow Computer option is not set the Runs Available and the Gas
Transmission options are disabled.
The Edit button opens the Edit Options Dialog.
The Program Status portion of the dialog depends on the controller type and the firmware. See the sections below for details.
The Close button closes the dialog.
The Refresh button reads information from the flow computer.
The Help button opens the user manual.
The Loaded C/C++ Programs section indicates the state of the C/C++ programs currently loaded in the SCADAPack 314/330/334 or SCADAPack
350. Usually this is the flow computer program, but it could be another program. The state will be one of No Program, Stopped, or Running.
The Run and Stop buttons apply to the C/C++ Program selected from the list of loaded C/C++ programs. Only one C/C++ Program may be selected from the list at one time. These buttons are disabled when there are no
C/C++ Programs loaded.
The Run button stops and restarts the selected C/C++ program in the controller.
The Stop button stops the selected C/C++ program in the controller.
Edit Options Dialog
The Edit Options dialog modifies the firmware options. An activation code is required to change the options. See the Obtaining an Activation Code section below for details on obtaining an activation code. See the Applying
an Activation Code section below for details on applying the activation code.
Realflo User and Reference Manual
May 19, 2011
286
Realflo Expert Mode Reference
The Controller ID is shown at the top of the dialog. This is a unique ID for the controller and is set at the factory. It cannot be changed.
The controllers Current Options are shown on the left. These are read from the controller when the Change Options command selected.
The New Options available for the controller are shown on the right. Select the new options based on the Activation Code obtained from Control
Microsystems. See the Obtaining an Activation Code section below for details on obtaining an activation code.
The Activation Code edit box contains the activation code for the currently selected options. If you leave the activation code edit box blank, an error message displays.
The OK button accepts the options and writes them to the controller. If the activation code is correct, the options are enabled. Otherwise the current options remain in effect.
The Cancel button closes the dialog without making any changes.
The Help button opens the user manual.
Obtaining an Activation Code
The activation code needs to be obtained from Control Microsystems. To obtain activation codes:
Record the Controller ID, Current Options and New Options for each controller you wish to update.
Contact Control Microsystems sales department, or your local representative, and report the information gathered in step 1.
The sales representative will inform you of the cost of the options and arrange for payment.
The activation codes will be sent to you upon receipt of payment.
Applying an Activation Code
Enter the same New Options as in item 1 of the Obtaining an Activation
Code section.
Realflo User and Reference Manual
May 19, 2011
287
Setup
Realflo Expert Mode Reference
Enter the Activation Code received from Control Microsystems and click
OK. The options will be written to the flow computer.
Stop flow runs using the Maintenance | Calculation Control menu item.
Read logs and history using the Maintenance | Read Logs/History menu item.
Replace the flow computer using the Configuration | Replace Flow
Computer menu item.
Replace the configuration using the Configuration | Write Configuration menu item. Flow runs will be started.
The Setup command is used to display and configure basic flow computer parameters. The hardware type, firmware type, number of flow runs enables and the flow computer ID are configurable.
The Hardware Type selection sets the type hardware that the flow computer is executing on. Valid selections are Micro16, SCADAPack,
SCADAPack Plus, SCADAPack Light, SCADAPack LP, SCADAPack 100:
1024K, SCADAPack 32, SCADAPack 32P, SCADAPack 4202 DR,
SCADAPack 4202 DS, SCADAPack 4203 DR, SCADAPack 4203 DS,
SCADAPack 314, SCADAPack 330, SCADAPack 334, SCADAPack 350 and SolarPack 410.
The Firmware Type selection sets the firmware type for the flow computer.
Valid sel;ections are Telepace and ISaGRAF. The default value is Telepace for step-by-step, or the value in the template.
The Number of Runs selection sets the number of runs in the file. The number of runs available depends on the type of flow computer used.
For Micro 16, SCADAPack, SCADAPack Light and SCADAPack Plus flow computers the maximum number of runs is three.
Realflo User and Reference Manual
May 19, 2011
288
Realflo Expert Mode Reference
The selection of three meter runs is available for older flow computers that could be enabled for three meter runs.
For SCADAPack LP and SCADAPack 4202 of flow computers the maximum number of meter runs is two.
For SCADAPack 100: 1024K and SolarPack 410 Flow Computers the maximum number of meter runs is one.
For SCADAPack 314/330/334 and SCADAPack 350 Flow Computers the maximum number of meter runs is four.
For SCADAPack 32 and SCADAPack 32P the maximum number of runs available is ten without the gas transmission option enabled and four with the gas transmission option enabled.
The Flow Computer ID entry is a unique ID for the flow computer. It stops accidental mixing of data from different flow computers. The Flow Computer
ID is stored in the flow computer. Realflo will not perform operations if the ID in the flow computer and that in the configuration file are not the same.
Enter a string of up to 8 characters for the Flow Computer ID. Any character is valid and the ID may be left blank.
The Enron Timestamp selects the type of timestamp for Enron flow history logs. Realflo and flow computer versions 6.77 and higher support the selection of time leads data or time lags data for the timestamp.
Time leads data selection time stamps the data for the period at the beginning of the period.
Time lags data selection time stamps the data for the period at the end of the period.
The configuration is valid for runs of the flow computer and is applied on the
Enron Modbus enabled ports only. This control is hidden in PEMEX or
GOST application modes.
Sensor and Display
Use this command to configure the sensor parameters of external transmitters. This command is disabled if the Update Readings command is enabled and opens the Transmitter Configuration dialog as shown below, when selected.
Realflo User and Reference Manual
May 19, 2011
289
Realflo Expert Mode Reference
The Flow Runs list displays each of the configured flow runs. The list displays the Run number, Run ID and the transmitter that is used for the differential pressure (DP), static pressure (SP) and temperature sensors.
The Run values are numbered 1 to N, in order.
The Configuration list shows the transmitters that can be configured. Up to
10 transmitters can be configured, depending on number of flow runs available. The number of transmitters in the list is equal to the number of flow runs. Use the Setup dialog on the Flow Computer menu to set the number of flow runs.
The configuration list displays the transmitter; the serial port the transmitter is connected to, the transmitter Modbus address, and the transmitter tag name.
When a transmitter is used the first position in the dialog is reserved for the internal transmitter. In this case the following dialog is displayed.
The list may be sorted by clicking on the column headings. Click on the column headings once to sort the list in ascending order. Click on the column a second time to sort the list in descending order.
disabled for SCADAPack 4202 or 4203 transmitters if only one meter run is enabled.
transmitter configuration. The button is disabled if no transmitter is selected or if more than one transmitter is selected.
The Delete button deletes the configuration for selected transmitters in the list box. The button is disabled if no transmitter is selected.
The OK button saves the settings and closes the dialog.
The Cancel button closes the dialog without saving.
The Help button opens the on-line manual.
Realflo User and Reference Manual
May 19, 2011
290
Realflo Expert Mode Reference
Sensor Search Dialog
The Sensor Search dialog allows searches for Multi-Variable Transmitters connected to the flow computer. Searches can be made using a serial connection and if the flow computer supports it using a LAN connection.
The Search dialog cannot remove or replace a transmitter when the controller type is a SCADAPack.
Search Serial
The Search Serial area of the search dialog is highlighted in the picture
above. The LAN Search is described in Search LAN section below. The
following paragraphs describe the parameters of the Serial Search.
The Port drop-down list box selects the controller serial port that will communicate with the transmitter. The valid ports are COM1, COM2, COM3 and COM4 for serial connections and LAN for LAN connections.
The Timeout edit box specifies the length of time the flow computer will wait for a response from a transmitter. The valid range is from 100 ms to 10000 ms. The default is 300 ms.
The radio buttons determine for which transmitters to search.
Use the Maximum radio button to search for the specified number of transmitters. The search operation will stop after finding the specified number of transmitters. The valid value is from 1 to 247. The default is 1.
Use the Range radio button to search the addresses in specified range. The range to search for is entered in the edit boxes to the right of the radio button. The value in To edit control needs to be equal or great than the value in the first edit control. The maximum search range that can be entered is for 255 transmitters. The default range is 1 to 247.
Valid values are any range between 1 and 247 for the SCADAPack
4101 and 3095MVT.
Realflo User and Reference Manual
May 19, 2011
291
Realflo Expert Mode Reference
4000 transmitters support addresses 1 to 255 in standard Modbus mode, and 1 to 65534 in extended address mode. The address mode of the flow computer serial port needs to be set to extended to search for transmitters with extended addresses.
The SCADAPack 4202 or 4203 transmitter support 1 to 255 addresses in the standard addressing mode and 1 to 65534 addresses in the extended addressing mode. The address mode of the SCADAPack
4202 or 4203 port needs to be set to extended in order to search for transmitters with extended addresses.
Select the All radio button to search the addresses of transmitters connected with the serial port selected in Port. A maximum of 255 addresses are searched.
The Serial Search button starts the search for MVT transmitters. A search process dialog is displayed so that the search operation can be cancelled at any time. The results of the search are added to the list box at the bottom of the dialog.
The search result list box shows the transmitters that were found by the search. Additional searches may add to the list box. The list may be sorted by clicking on the column headings. Click on the column headings once to sort the list in ascending order. Click on the column a second time to sort the list in descending order.
The list box displays the following columns:
The Port column displays the serial or LAN port the controller is using to communicate with the transmitter.
The Address column displays the Modbus station address of the transmitter.
The Tag column displays the Tag Name assigned to the transmitter. This column may be blank if a Tag Name has not been assigned to the transmitter.
The Serial Number column displays the transmitter factory serial number.
The Manufacturer Code column displays the transmitter factory manufacturer code.
The Status column indicates if configuration data for the transmitter exists.
Configured indicates a transmitter with the same port, address, serial number, and factory code is in the list in the Sensor and Display
Configuration dialog.
Different means a transmitter with the same port and address is in the list in the Sensor and Display Configuration dialog. The tag, serial number, or factory code of the transmitter is different.
New means that the transmitter is not in the list of configured transmitters.
The Change button opens the Change Address Dialog to change the
Modbus station address of the serial port on the remote transmitter. This action will change the Modbus station number of the serial port on the MVT connected to a SCADAPack controller. The button is grayed if the list is empty or if more than one transmitter is selected.
Realflo User and Reference Manual
May 19, 2011
292
Search LAN
Realflo Expert Mode Reference
The Delete button removes the selected items from the list. The button is grayed if the list empty or no transmitter is selected.
The OK button saves the settings and closes the dialog. Transmitters in the result list are added to the transmitter configuration in the Sensor and
Display Configuration Dialog.
If the transmitter status is configured the list is not changed.
If the transmitter status is different the tag, serial number, and factory code in the list is updated with the new information from the transmitter.
If the transmitter status is new the transmitter is added to the list in the first available position. If there are more new transmitters than there are free positions in the list an error dialog is displayed with the message
“There are too many new transmitters. Please delete some new
transmitters from the list.”
The Cancel button closes the dialog without saving.
The Help button opens the on-line manual.
The Search LAN area of the search dialog is highlighted in the picture below. The following paragraphs describe the parameters of the Search
LAN function.
The IP Address edit box specifies the known IP address of the 4000 transmitter. Valid entries are IP addresses in the format nnn.nnn.nnn.nnn where nnn are values between 0 and 255.
The Protocol drop-down list box selects the type of IP protocol that will be used to query the transmitter. Valid IP protocol selections are Modbus/TCP and Modbus RTU in UDP.
The IP port (for example port 502) for the selected protocol needs to be the same in the flow computer and the 4000 transmitter.
The LAN Timeout edit box specifies the length of time the flow computer will wait for a response from a 4000 transmitter. The valid range is from 100 to 10000 milliseconds. The default is 5000 ms.
The Search LAN button starts the search for the 4000 transmitters. A search progress dialog is displayed and the search operation can be cancelled at any time. The result of the search is added to the search results list box at the bottom of the MVT Search dialog.
The search result list box shows the transmitters that were found by the search. Additional searches may add to the list box. The list may be sorted by clicking on the column headings. Click on the column headings once to sort the list in ascending order. Click on the column a second time to sort the list in descending order.
The Port column displays the serial or LAN port the controller is using to communicate with the transmitter.
The Address column displays the Modbus station address of the transmitter.
The Tag column displays the Tag Name assigned to the transmitter. This column may be blank if a Tag Name has not been assigned to the transmitter.
Realflo User and Reference Manual
May 19, 2011
293
Realflo Expert Mode Reference
The Serial Number column displays the transmitter factory serial number.
The Manufacturer Code column displays the transmitter factory manufacturer code.
The Status column indicates if configuration data for the transmitter exists.
Configured indicates a transmitter with the same port, address, serial number, and factory code is in the list in the Sensor and Display
Configuration dialog.
Different means a transmitter with the same port and address is in the list in the Sensor and Display Configuration dialog. The tag, serial number, or factory code of the transmitter is different.
New means that the transmitter is not in the list of configured transmitters.
The Delete button removes the selected items from the list. The button is grayed if the list empty or no transmitter is selected.
The OK button saves the settings and closes the dialog. Transmitters in the result list are added to the transmitter configuration in the Sensor and
Display Configuration Dialog.
If the transmitter status is configured the list is not changed.
If the transmitter status is different the tag, serial number, and factory code in the list is updated with the new information from the transmitter.
If the transmitter status is new the transmitter is added to the list in the first available position. If there are more new transmitters than there are free positions in the list the following message is displayed “There are too many new transmitters. Please delete some new transmitters from the list.”
The Cancel button closes the dialog without saving.
The Help button opens the on-line manual.
Change Address Dialog
The Change button opens the Change Address Dialog to change the
Modbus station address of the serial port on the remote transmitter. This action will change the Modbus station number of the serial port on the MVT connected to a SCADAPack controller. The button is grayed if the list is empty or if more than one transmitter is selected.
New SCADAPack 4101 transmitters have a default address of 99. It is recommended that transmitters be assigned an address other than 99. This will allow adding a new transmitter at any time. If a transmitter is left at address 99, then it will have to be disconnected to install a new transmitter.
The Old Address window displays the current address of the transmitter.
The New Address entry specifies the new address for the transmitter. The new address needs to be different from any existing addresses in the results
Realflo User and Reference Manual
May 19, 2011
294
Realflo Expert Mode Reference list of Sensor Search dialog. Valid values are any range between 1 and 247 for the SCADAPack 4101and 3095MVT. The SCADAPack 4202 or 4203 transmitters support 1 to 255 addresses in the standard addressing mode and 1 to 65534 addresses in the extended addressing mode.
The OK button changes the transmitter address. A communication progress dialog opens while the information is written to the transmitter. Click on the
Cancel button on the progress dialog to attempt to abort the command. This will close the progress dialog, bit the address of the transmitter already may be changed.
The Cancel button closes the dialog without changing the transmitter address.
Realflo User and Reference Manual
May 19, 2011
295
Realflo Expert Mode Reference
Edit Sensor Settings Dialog
This dialog allows the editing of settings for transmitters connected to the flow computer.
There are three selection tabs, shown at the top left corner of the dialog.
When selected, each tab will display a page of configuration parameters in the dialog. The General Page contains sets communication and transmitter information for a transmitter. The Measured Variables page configures the three process measurements, and the Display Module Page configures the display on the transmitter.
There are two columns of data on each page. The Proposed column contains the values that will be written to the controller. The Actual column contains the values that were in the controller the last time data was read from the controller. Values in the Proposed column are colored blue if they differ from the values in the Actual column; this enables the easy location of any differences.
The OK button closes the dialog and saves the settings.
The Read button reads the transmitter settings from the flow computer into the Actual column on all pages. If there is no transmitter configured in the flow computer then the flow computer will attempt to read the configuration from the Address in the Proposed column. A communication progress dialog is displayed while reading from the flow computer.
The Copy Actual to Proposed button copies settings from the Actual column to the Proposed column on both pages. The button is disabled if the
Actual column is empty.
The Print button prints the current page display settings.
The Export button exports the settings to a specified CSV file.
The Help button opens the on-line manual.
The flow computer ID is checked when the Read command is used. If the flow computer ID does not match the ID Realflo displays the message “ The
Realflo User and Reference Manual
May 19, 2011
296
General Page
Realflo Expert Mode Reference
Flow Computer ID from the flow computer does not match the Flow
Computer ID from the file.” The read is not performed.
The General page sets communication and generic information for a transmitter.
The Address edit-box specifies the Modbus address of the transmitter for serial connections and the IP address of the transmitter for LAN connections. Transmitters on the same serial port need to have a unique
Modbus address. Transmitters on the LAN port need to have a unique IP address. This edit box is disabled if the controller type is set to a
SCADAPack 4202 or 4203 transmitter.
Valid addresses are between 1 and 247 for the SCADAPack 4101and
3095MVT.
4000 transmitters support addresses 1 to 255 in standard Modbus mode, and 1 to 65534 in extended address mode.
The SCADAPack 4202 or 4203 transmitters support 1 to 255 addresses in the standard addressing mode and 1 to 65534 addresses in the extended addressing mode.
New SCADAPack 4101 transmitters have a default address of 99. It is recommended that transmitters be assigned an address other than 99. This will allow adding a new transmitter at any time. If a transmitter is left at address 99, then it will have to be disconnected to install a new transmitter.
The Port drop-down list box specifies the flow computer serial port where the MVT is connected. The valid port selections are com1, com2, com3, and com4 for serial connections and LAN for LAN connections. This edit box is disabled if the controller type is set to a member of the SCADAPack 4202 or
4203 of controllers.
Polling Sensors for SCADAPack 32 10 Runs
The SCADAPack 32 supports 10 flow runs but can poll a maximum of 6 sensors in 1 second. So that all sensors and Coriolis meters are polled for all runs in 1 second the flow computer manages the polling using multiple serial communication ports.
When using more than 5 runs on a SCADAPack 32 flow computer users need to distribute the communication for sensor and Coriolis meter data over multiple serial ports. For example if 10 runs are to be used poll for 5 sensors on one serial port and 5 sensors on another serial port.
The Timeout edit-box specifies the time the flow computer waits for a response from the transmitter before the command is unsuccessful. The valid range is from 0 to 10000 ms. The default is 1000 ms. This edit box is disabled if the controller type is set to a member of the SCADAPack 4202 or
4203 of controllers.
The flow computer polls each configured transmitter in turn. It waits for a response or timeout. If the transmitter does not respond it will take longer to poll it, than if it responded. The flow computer does not retry the transmitter.
It moves on to the next transmitter. The transmitter will be polled again in the regular cycle.
The communication failure alarm is raised if the transmitter does not respond for 3 consecutive polls.
Realflo User and Reference Manual
May 19, 2011
297
Realflo Expert Mode Reference
The Device dropdown list specifies the type of transmitter connected to the flow computer. Valid values are 3095FB, SCADAPack 4101, SCADAPack
4102 or a SCADAPack 4202 or 4203 transmitter. The default value is 4202
DR.
The Tag edit-box specifies the transmitter tag. Up to 8 characters can be entered. The default is no tag.
The Serial Number displays the serial number of the MVT transmitter. It cannot be edited. It is set when the transmitter is found using the Search feature.
The Turnaround Delay Time edit-box specifies the turnaround delay time.
The transmitter will wait this long before responding to the flow computer.
The valid range is 0 to 200 ms. The default is 50 ms.
Measured Variables Page
The Measured Variables page configures the transmitter measurements.
The MVT transmitter measures differential pressure, static pressure, and temperature. The configuration parameters for each measurement are the same.
The Units drop-down list boxes select the units used by the transmitter for the measurement. Values read from the transmitter are in these units. If the transmitter has a local display it uses these units.
For Differential Pressure the valid units displayed will depend on the transmitter used. For SCADAPack 4202, 4203 or 4000 transmitters, valid units are: inches H2O at 68 F, Pascal (Pa) and kiloPascal (kPa).
The default is inches H2O at 68°F. For the 3095 MVT valid units are: inches H2O at 60°F, Pascal (Pa), kiloPascal (kPa) and inches H2O at
60 F. The default is inches H2O at 60°F.
For Static Pressure the valid units are kiloPascal (kPa), MegaPascal
(Mpa), and pounds per square inch (psi). The default is psi.
Realflo User and Reference Manual
May 19, 2011
298
Realflo Expert Mode Reference
For Temperature the valid units are degrees Celsius (C) and degrees
Fahrenheit (F). The default is Fahrenheit (F).
The Damping edit boxes specify the response time of transmitter in order to smooth the process variable reading when there are rapid input variations.
For the SCADAPack 4202, 4203 or 4000 transmitters the valid values are
0.0 (damping off), 0.5, 1.0, 2.0, 4.0, 8.0, 16.0, and 32.0 seconds. The default value is 0 (damping off). Flow Temperature damping is disabled for the
SCADAPack 4202, 4203 and 4000 transmitters.
For the 3095 MVT the valid values are 0.108, 0.216, 0.432, 0.864, 1.728,
3.456, 6.912, 13.824 and 27.648. The default is 0.864.
The Lower Operating Limit (LOL) and Upper Operating Limit (UOL) edit boxes specify the sensor operating values. These values are set in Realflo as a method to generate an alarm in the alarm log if the measured value is outside these limits The flow computer uses these values to record when the process value has transitioned into an unexpected value based on the predicted characteristics of the users application. The valid range depends upon the transmitter. The default is 0 for lower operating limit and 65534 for upper operating limit. The LOL and UOL needs to satisfy the following conditions. The user is responsible for selecting suitable values for LOL and
UOL.
LRL <= LOL < (UOL
– URL/100)
(LOL + URL/100) <= UOL <= URL
Where LRL (Lower Range Limit) and URL (Upper Range Limit) are the upper and lower calibrated measurements for the transmitter as it is shipped from the factory. These are fixed values and not adjustable by the user.
Refer to the calibration plate on the MVT transmitter or your MVT User
Manual for calibrated LRL and URL ranges.
Re-ranging is a concept that does not apply to the 4000 digital transmitters.
The transmitters are shipped with a specific URL/LRL that defines the calibrated measurement range of the transmitter. The accuracy specifications of the transmitter are based on this calibrated range, and that range is not user adjustable.
Older analog transmitters had an analog output to indicate the pressure reading. For applications where the measurement was only expected to take place over a portion of the full transmitter measurement range, this analog output could be 're-ranged' so that the full output analog range (4-20mA) would cover only a portion of the factory calibrated range, and therefore reduce some of the error associated with the digital-to-analog (D/A) conversion.
Since there is no D/A conversion in the digital transmitters, the additional errors associated with the D/A conversion are not present and the concept of re-ranging that was done with analog transmitters no longer applies.
The Pressure Type edit box specifies whether the static pressure is measured as gage or absolute pressure. Valid values are Absolute and
Gage. The default value is Absolute. The control is enabled for the
SCADAPack 4202 or 4203 and 4102 transmitters, and is disabled for other transmitters.
The Atmospheric Pressure specifies the local atmospheric pressure. The atmospheric pressure is the weight of the atmosphere on the surface of the
Realflo User and Reference Manual
May 19, 2011
299
Realflo Expert Mode Reference
Earth. Valid values are 0 to 30 psia, or equivalent values in other units. The default value is 0 psia. The control is disabled if the Pressure Type is
Absolute. The control is enabled for the SCADAPack 4202, 4203 and 4102 transmitters, and is disabled for other transmitters.
Realflo User and Reference Manual
May 19, 2011
300
Realflo Expert Mode Reference
Display Module Page
The Display Module page sets items that will be displayed on the MVT transmitter display.
The Available Items list will contain possible items that can be displayed.
The number of available items will vary depending on how many flow runs are configured. The table below shows the available items.
Item
DP
SP
PT
Current Time
Run ID
Orifice Plate Size
Calculation State
Flow Volume Rate
Flow Mass Rate
Flow Energy Rate
Flow Time
Today‟s Flow Volume
Notes
One selection for each flow run is available
One selection for each flow run is available
One selection for each flow run is available
One selection for each flow run is available
One selection for each flow run is available
One selection for each flow run is available
One selection for each flow run is available
One selection for each flow run is available
One selection for each flow run is available
One selection for each flow run is available
One selection for each flow run is available
One selection for each flow run is available
Realflo User and Reference Manual
May 19, 2011
301
Custom Item Dialog
Realflo Expert Mode Reference
Item
Yesterday‟s Flow Volume
Pulses
Relative Density
Pipe Diameter
Atmospheric pressure
Battery Voltage
Notes
One selection for each flow run is available
One selection for each flow run is available
One selection for each flow run is available for flow computers with version 6.00 and higher.
One selection for each flow run is available
One selection for each flow run is available
This item is available for
SolarPack 410 controllers only.
The Proposed Items list contains the items are ready to be displayed. The order of the items in the list is the same as the order that the items will be shown on the display. A maximum of 12 items can be added to the
Proposed Items list. A maximum of 5 custom display registers can be added to the list. It is permitted to have the same item in the list multiple times.
Clicking on the Add button will move selected items from the Available
Items list to the Configured Items list. The Add button is disabled if there is not enough room in the Configured Items list to add the selected items, and when the Configured Items list is full. The Add button is also disabled if no items are selected in the Available Items list.
Click Add Custom to open the Add/Edit Custom Item dialog with default settings. The resulting item will be placed at the end of the Proposed Items list. The Add Custom button is disabled when the Proposed Items list is full.
A maximum of 5 custom display registers can be added.
Clicking on the Remove button will remove selected items from the
Configured Items list. Multiple items may be removed at once. The
Remove button is disabled if no items are selected in the Configured Items list.
The Display Update Interval edit-box shows the length of time that each measurement from the Configured Items list will be displayed. The valid range is from 2 to 60 seconds inclusive. The default setting is 4 seconds.
The Move Up button will move the selected item(s) in the Configured
Items list up one position each time it is clicked. The Move Up button is disabled if no item is selected in the Configured Items list or if multiple items are selected in the Configured Items list.
The Move Down button will move the selected item(s) in the Configured
Items list down one position each time it is clicked. The Move Down button is disabled if no item is selected in the Configured Items list or if multiple items are selected in the Configured Items list.
The Actual Items list contains the items that read from the controller and
Actual Display Update Rate text-box contains the display update rate that read from the controller.
Realflo User and Reference Manual
May 19, 2011
302
Realflo Expert Mode Reference
When the Add Custom button is used the Add/Edit Custom Item dialog is displayed as shown below. A maximum of 5 custom display registers can be added.
Flow Run
Type the Register number. Registers can be in the range 1 to 9999, 10001 to 19999, 30001 to 39999 and 40001 to 49999.
Select the Data Type format for the value in the register. Some data types will read two consecutive registers. The boolean data type reads a single bit.
The types are: boolean, signed, unsigned, signed double, unsigned double, floating point and ISaGRAF integer.
Type the seven character string in the Description control. This string will be displayed below the value for the first half of the display period.
Type the seven character string in the Units control. This string will be displayed below the value for the second half of the display period. This string may be scrolled to allow a scaling exponent to be displayed.
Use this command to configure the parameters for a selected meter run.
This command is disabled if the Update Readings command is enabled. The
Flow Run command opens the Select Run to Configure dialog. This dialog selects the run to be configured.
The Run drop-down list box lists the runs available. The number of runs available is set in the Flow Computer Setup dialog.
The OK button opens the Configuration - Run N dialog with the data for the selected run.
The Configuration - Run N dialog displays a maximum of eight selection tabs, depending on the flow calculation type, shown across the top of the dialog. When selected, each tab will display a page of configuration parameters in the dialog. This section provides an overview of the configuration parameters for each tab. Detailed explanations for the
configuration parameters are found in the
Realflo User and Reference Manual
May 19, 2011
303
Realflo Expert Mode Reference
To select a tab move the pointer to the tab name and click the left mouse button. The seven tabs displayed will change depending on the type of flow calculation and type of compressibility calculation selected in the Input tab.
The Inputs tab defines the type of flow calculation to be performed, the type of compressibility calculation to be performed, and the configuration of the sensor inputs.
The Static Pressure tab defines the parameters for the static pressure sensor for the meter run.
The Temperature tab defines the parameters for the temperature sensor for the meter run.
The Differential Pressure tab defines the parameters for the differential pressure sensor for the meter run.
The Contract tab defines parameters for the gas measurement contract.
These parameters define the information operation of the flow computer.
The AGA-3 tab defines parameters unique to the AGA-3 calculation.
This tab is visible only if the AGA-3 calculation is selected on the Input configuration.
The AGA-7 tab defines parameters unique to the AGA-7 calculation.
This tab is visible only if the AGA-7 calculation is selected on the Input configuration.
The V-Cone tab defines parameters unique to the V-Cone calculation.
This tab is visible only if the V-Cone calculation is selected on the Input configuration.
The AGA-11 tab defines parameters unique to the AGA-11 calculation.
This tab is visible only if the AGA-11 calculation is selected on the Input configuration. This calculation type is not available for 16-bit controllers.
The AGA-8 tab defines parameters unique to the AGA-8 Detailed calculation. This tab is visible only if the AGA-8 calculation is selected on the Input configuration.
Realflo User and Reference Manual
May 19, 2011
304
Inputs Tab
Realflo Expert Mode Reference
The AGA-8 Hexanes+ tab defines the composition of the heavier gas components being measured
The NX-19 tab defines parameters unique to the NX-19 calculation. This tab is visible only if the NX-19 calculation is selected on the Input configuration.
Tabs work in the same manner. There are two columns of data on the page.
The Proposed column contains the values that will be written to the controller. The Actual column contains the values that were in the controller the last time data was read from the controller. Values in the Proposed column are colored blue if they differ from the values in the Actual column; this lets you easily located differences.
The Run Configuration dialog has the following controls at the bottom of the dialog. These controls are available and are independent of the tab selected.
The OK button saves the modified settings and closes the Run
Configuration dialog.
The Cancel button closes the Controller Configuration dialog and discards any changes. The OK button is disabled if the user is logged on with an account that is read and view only.
The Read Actual button reads the run configuration from the flow computer. Data for all property pages is read and placed in the Actual columns on the property pages. If the flow computer ID does not match the ID in the file Realflo displays the message “ The Flow Computer ID from the flow computer does not match the Flow Computer ID from the file.”
In SCADAPack 4202 and SCADAPack 16-bit Flow Computers with multiple flow runs, the latest AGA-8 ratios may not be read back for several minutes.
In SCADAPack 4203 and SCADAPack 314/330/334, SCADAPack 350 or
SCADAPack32 Flow Computers with multiple flow runs, the latest AGA-8 ratios may not be read back for up to a minute. New gas ratio configurations may be delayed until the other flow run has completed its current AGA-8 calculation.
The Print Run button prints the configuration data for the run.
The Export Run button exports the configuration data, for the run, to a file. Refer to the Exporting section below.
The Help button displays help for the currently open property page.
Inputs Tab defines the type of flow calculation to be performed, the type of compressibility calculation to be performed, and the configuration of the sensor inputs. The contents of the page will change depending on the selections made in the Flow Calculation and Compressibility Calculation selections.
The flow calculation needs to be stopped in order to write some of the parameters on this page to the controller. These parameters are noted with
an asterisk (*) beside the parameter title. Refer to the
section for information on stopping and starting flow calculations in the flow computer.
Realflo User and Reference Manual
May 19, 2011
305
Realflo Expert Mode Reference
Realflo does not allow configuration changes if the Event Log in the flow
command to empty the Flow Computer Event Log.
Run ID
* Input Units
The configuration of parameters for the Inputs page is done using entry fields or dropdown selections for each parameter. The following edit controls are displayed.
The flow run identification string, Run ID, is used to identify the flow run.
Enter a string up to 16 characters long in the Run ID edit box. For flow computer version 6.00 or higher, type a string up to 32 characters long.
The flow run ID is displayed in the title bar of each view window beside the run number. The flow run ID is printed on report headers beside the run number.
The run ID is not supported in older flow computers. Realflo will not read or write the run ID when an older flow computer is detected.
Select the units of measurement of input values for the meter run. Inputs may be measured in different units than the calculated results. This allows you to use units that are convenient to you for measuring inputs. The flow calculation needs to be stopped in order to write this parameter to the controller. A dropdown box allows the selection of the following unit types:
US1
US2
US3
IP
Metric1
Metric2
Metric3
Realflo User and Reference Manual
May 19, 2011
306
Realflo Expert Mode Reference
SI
US4
US5
US6
US7
US8
PEMEX
section for information on unit types and how they are displayed.
* Flow Calculation
Select the type of flow calculation for the meter run. Realflo supports the
AGA-3 (1985 version) and AGA-3 (1992 version) for orifice meters the AGA-
7 calculations for turbine meters and the V-Cone calculations for v-cone meters. A dropdown box allows the selection of:
AGA-3 (1985)
AGA-3 (1992)
AGA-7
AGA-11 (not available for 16-bit controllers)
V-Cone
Notes:
The SolarPack 410 does not support AGA-7 calculations.
When a Realflo configuration file that is using AGA-11 flow calculation type is opened in a version of Realflo 6.75 or earlier the flow calculation type AGA-11 is not displayed and the window is blank. This is correct operation. When a new calculation type is entered, i.e. AGA-3(1992), the AGA-8 and AGA-8 Hexanes+ tabs are not displayed. To correct this select OK to close the Run Configuration dialog and then reopen it. The missing tabs are correctly displayed.
* Compressibility Calculation
Select the type of compressibility calculation for the meter run. AGA-8
Detailed and NX-19 compressibility calculations can be selected. AGA-8
Detailed is the recommended calculation for new systems as it has superior performance compared to NX-19. NX-19 is provided for legacy systems.
The flow calculation needs to be stopped in order to write this parameter to the controller. A dropdown box allows the selection of:
AGA-8
NX-19 (Not supported for PEMEX flow computers)
When NX-19 calculation is used the Input Units type needs to be selected such that the Static Pressure is in psi (pounds per square inch).
Low Flow Events
Select whether to log or ignore flow events that occur for the meter run.
Realflo can ignore all events or log low flow events. A dropdown box allows the selection of:
Realflo User and Reference Manual
May 19, 2011
307
Realflo Expert Mode Reference
Ignore
Log Low Flow
Select Ignore if the measured flow experiences these events as part of normal operation. Ignoring these events will keep the Alarm Log from overflowing. Flow accumulation stops when this alarm occurs.
When selected the Low Flow events are added to the Alarm log.
Value on Sensor Fail
The Value on Sensor Fail configuration option uses the specified value in this field as the live input value when communicating with a sensor. A dropdown list lets you select:
Use Last Known Good Value
Use Default Value
When the Use Default Value option is selected the default value is entered in the Differential Pressure, Static Pressure and the Temperature tabs. The entry window Default Value is activated in each tab when this selection is made.
When you open a file using an older file format, Realflo sets the default value of the Values on Sensor Fail field to Use Last Known Good.
When the status to a sensor changes and you select the Use Default Value option, this is added to the Event Log.
For flow computers 6.70 and later, when communication to a sensor fails and the configuration option “Use Last Known Good Value” is set to
“Use Default Value,” the flow computer needs to use the specified default value in the configuration in place of a live input value.
When communication to a sensor is restored and the configuration option for the Value on Sensor Fail field is set to use the default value, the flow computer uses the input value from the sensor as the live input value.
For flow computers prior to 6.70, the value on sensor fail is “Use Last
Known Good Value.”
Run Direction Control
The Run Direction Control option is used to indicate the direction of flow, forward or reverse, for a meter run. The flow computer calculates flow rates and accumulates flow volumes for one flow direction only for each flow run configured. In order to calculate flow rates and accumulate volume for another flow direction a second flow run needs to be configured, using the same run parameters but with an opposite flow direction setting.
Flow direction is indicated using either the value from a Differential Pressure sensor or Coriolis meter or a status register.
When using a value to indicate flow direction:
Forward flow direction is indicated by a positive (plus) value from a differential pressure sensor for AGA-3 and V-Cone applications and a positive (plus) mass flow rate value from a Coriolis meter.
Reverse flow direction is indicated by a negative (minus) value from a differential pressure sensor for AGA-3 and V-Cone applications and a negative (minus) mass flow rate value from a Coriolis meter.
Realflo User and Reference Manual
May 19, 2011
308
Realflo Expert Mode Reference
When using status to indicate flow direction the flow direction is indicated by a status register and the On Indicates value for the status register.
Forward flow direction is indicated by a status value of 1 or ON in the
Flow Direction Register when the On Indication is set to Forward.
Reverse flow direction is indicated by a status value of 1 or ON in the
Flow Direction Register when the On Indication is set to Reverse.
In many applications the flow direction is forward but in some applications there is a need to calculate reverse flow under certain conditions. An example of this would be a gas storage facility.
The selections available for Flow Direction Control are:
The Forward by Value selection will indicate the flow direction is forward when the value from a differential pressure (DP) sensor is positive or the mass flow rate value from a Coriolis meter is positive. When the flow direction is forward the flow computer calculates flow rates and accumulates volumes for the flow run. Using this setting when the value from a differential pressure (DP) sensor is negative or the mass flow rate value from a Coriolis meter is negative the flow computer does not calculate flow rates or accumulate volumes for the flow run.
The Reverse by Value selection will indicate the flow direction is reverse when the value from a differential pressure (DP) sensor is negative or the mass flow rate value from a Coriolis meter is negative. When the flow direction is reverse the flow computer calculates flow rates and accumulates volumes for the flow run. Using this setting when the value from a differential pressure (DP) sensor is positive or the mass flow rate value from a Coriolis meter is positive the flow computer does not calculate flow rates or accumulate volumes for the flow run.
The Forward by Status selection will indicate the flow direction is forward when the Flow Direction Register has a value of 1 (ON) and the On
Indication value is set to Forward. When the flow direction is forward the flow computer calculates flow rates and accumulates volumes for the flow run. Using this setting when the Flow Direction Register has a value of 0
(OFF) the flow computer does not calculate flow rates or accumulate volumes for the flow run.
The Reverse by Status selection will indicate the flow direction is reverse when the Flow Direction Register has a value of 1 (ON) and the On
Indication value is set to Reverse. When the flow direction is reverse the flow computer calculates flow rates and accumulates volumes for the flow run. Using this setting when the Flow Direction Register has a value of 1
(ON) the flow computer does not calculate flow rates or accumulate volumes for the flow run.
Flow Direction Register
The Flow Direction Register edit-box specifies which register indicates the forward or reverse flow direction status. Valid registers for the flow computer controller can be used for this setting. The default register is 1. This edit control is disabled if Flow Direction Control selection is Value. This control is hidden in GOST mode flow computers.
When using the flow direction register consider the following points:
When two configured runs are using the same status register one run is configured for forward direction and second run is configured for reverse direction.
Realflo User and Reference Manual
May 19, 2011
309
Realflo Expert Mode Reference
When more than two configured runs are using the same status register the configuration needs to be checked. There may be a logic application that uses a single status point for all runs.
On Indicates
The On Indicates drop-down selection list allows the selection of Forward or
Reverse for the status register value. The default is Forward. The control does not show up in GOST mode. The control is disabled if Status Register control is disabled.
Gas Quality Sources
This parameter is available for PEMEX versions of Realflo only. The Gas
Quality Sources control selects the source for the AGA-8 gas quality for
PEMEX applications. A dropdown box allows the selection of Gas Quality
Source as:
Manual
PEMEX Host
When Manual is selected AGA-8 gas quality can be written from the Realflo application to the flow computer. The Modbus Mapping table can also be written if the user has an Admin level account. The PEMEX interface
(PEMEX Host) cannot write gas quality settings when the source is set to manual. An error is returned to the PEMEX host if an attempt is made to write the settings to the flow computer.
When PEMEX Host is selected AGA-8 gas quality cannot be written from the Realflo application to the flow computer. Writing the Modbus Mapping table will return an error code if an attempt is made to write the AGA-8 settings to the flow computer. The PEMEX interface (PEMEX Host) is able to write gas quality settings when the source is set to PEMEX Host.
Hysteresis Units
The Hysteresis Units control selects how hysteresis is configured for the high and low level hysteresis in the Pressure, Temperature and Differential
Pressure tabs. A dropdown box allows the selection of:
Percent
Engineering Units
Realflo User and Reference Manual
May 19, 2011
310
Realflo Expert Mode Reference
Differential Pressure Tab
The controls in this tab are used to configure the differential pressure sensor for the meter run. The differential pressure controls are used only if the
AGA-3 or the V-Cone flow calculation is selected.
* Input Type
The configuration of parameters for the Differential Pressure page is done using entry fields or dropdown selections for each parameter. The following edit controls are displayed. Parameter ranges are determined by the selection of the Input Units.
The tap location for the orifice meter as used in the gas flow calculation by
Realflo is as follows:
For AGA-3 1985 flange taps are used.
For AGA-3 1992 flange taps are used.
For V Cone meters the tap provided with the V-Cone element is used.
The type of register used for the Input Register. A dropdown box allows the selection of:
Telepace Integer 16
–bit signed integer register.
Float Floating-point register in engineering units.
Raw Float Floating point register requiring scaling.
ISaGRAF integer 32-bit signed integer register in ISaGRAF format.
4202 DR The internal 4202DR replaces the first MVT (transmitter 1) on the MVT list when the controller type is set to 4202 DR.
4202 DS The internal 4202 DS replaces the first MVT (transmitter 1) on the MVT list when the controller type is set to 4202 DS.
4203 DR The internal 4203 DR replaces the first MVT (transmitter 1) on the MVT list when the controller type is set to 4203 DR.
4203 DS The internal 4203 DS replaces the first MVT (transmitter 1) on the MVT list when the controller type is set to 4203 DS.
Realflo User and Reference Manual
May 19, 2011
311
Realflo Expert Mode Reference
SolarPack 410 The internal SolarPack 410 replaces the first MVT
(transmitter 1) on the MVT list when the controller type is set to
SolarPack 410.
Configured MVT If there are configured MVT transmitters they are
displayed in the format number (tag name). Refer to the
section for details on configuring MVT transmitters.
Refer to the
Register Formats
section for more information and examples for register types.
* Input Register
The Input Register is the address of the register in the Flow Computer I/O database that contains the reading from the differential pressure sensor.
The I/O database register will be an input register (3xxxx) or a holding register (4xxxx). The flow calculation needs to be stopped in order to write this parameter to the controller. If an MVT or a SCADAPack 4202 or 4203 transmitter is selected in the Input Type selection this entry is disabled.
Input at Zero Scale
The value read from the sensor, in unscaled I/O units, when the sensor is at zero scale. This field is grayed if the register type does not require scaling. If an MVT or a SCADAPack 4202 or 4203 transmitter is selected in the Input
Type selection this entry is disabled.
Input at Full Scale
The value read from the sensor, in unscaled I/O units, when the sensor is at full scale. This field is grayed if the register type does not require scaling. If an MVT or a SCADAPack 4202 or 4203 transmitter is selected in the Input
Type selection this entry is disabled.
Differential Pressure at Zero Scale
The differential pressure that corresponds to the zero scale input, or if the input does not require scaling, the minimum DP that can be read from the sensor. If a MVT or a SCADAPack 4202 or 4203 transmitter is selected in the Input Type selection this entry is disabled and the value is forced to that of the MVT Lower Operating Limit.
Differential Pressure at Full Scale
The differential pressure that corresponds to the full scale input, or if the input does not require scaling, the maximum DP that can be read from the sensor. If an MVT or a SCADAPack 4202 or 4203 transmitter is selected in the Input Type selection this entry is disabled and the value is forced to that of the MVT Upper Operating Limit.
Low DP Cutoff
This is the scaled input differential pressure where flow accumulation will stop. Valid values depend on the transmitter: refer to the transmitter band or user manual. It needs to be less than the UOL. The default value is 0.
Low DP Hysteresis
This is the amount, in percent of span, that the differential pressure needs to rise above the Low DP Cutoff to clear the low alarm and allow the flow calculations to resume.
Default Value
Realflo User and Reference Manual
May 19, 2011
312
Realflo Expert Mode Reference
The Default Value edit box is enabled when the Input Type is set to a sensor and when the Values on Sensor Fail option on the Inputs tab is configured to Use Default Value.
The value you can enter in Default Value edit box needs to be a range that is checked against the sensor configuration. The actual value needs to be uploaded from the controller when you click Read Actual.
Realflo User and Reference Manual
May 19, 2011
313
Realflo Expert Mode Reference
Static Pressure Tab
The controls in this tab are used to configure the static pressure sensor for the meter run. The static pressure used in the flow calculations is either gauge pressure or absolute.
Gauge pressure is the pressure that a normal sensor would register. These sensors measure the pressure that is in excess of the atmospheric pressure. An atmospheric pressure value needs to be entered when gauge pressure sensors are used.
Absolute pressure sensors measure pressure relative to zero pressure
(vacuum). An atmospheric pressure value of zero needs to be entered when absolute pressure sensors are used.
* Input Type
The configuration of parameters for the Static Pressure page is done using entry fields or dropdown selections for each parameter. The following edit controls are displayed. Parameter ranges are determined by the selection of the Input Units.
The tap location for static pressure as used in the gas flow calculation by
Realflo is as follows:
For AGA-3 1985 flange taps are used.
For AGA-3 1992 flange taps are used.
For V Cone meters the tap provided with the V-Cone element is used.
The type of register used for the Input Register. A dropdown box allows the selection of:
Telepace Integer 16
–bit signed integer register.
Float Floating-point register in engineering units.
Raw Float Floating point register requiring scaling.
Realflo User and Reference Manual
May 19, 2011
314
Realflo Expert Mode Reference
ISaGRAF integer 32-bit signed integer register in ISaGRAF format.
4202 DR The internal 4202 DR replaces the first MVT (transmitter 1) on the MVT list when the controller type is set to 4202 DR.
4202 DS The internal 4202 DS replaces the first MVT (transmitter 1) on the MVT list when the controller type is set to 4202 DS.
4203 DR The internal 4203 DR replaces the first MVT (transmitter 1) on the MVT list when the controller type is set to 4203 DR.
4203 DS The internal 4203 DS replaces the first MVT (transmitter 1) on the MVT list when the controller type is set to 4203 DS.
SolarPack 410 The internal SolarPack 410 replaces the first MVT
(transmitter 1) on the MVT list when the controller type is set to
SolarPack 410.
Configured MVT If there are configured MVT transmitters they are
displayed in the format number (tag name). Refer to the
section for details on configuring MVT transmitters.
section for more information and examples
for register types.
* Input Register
The Input Register is the address of the register in the Flow Computer I/O database that contains the reading from the pressure sensor. The I/O database register is an input register (3xxxx) or a holding register (4xxxx).
The flow calculation needs to be stopped in order to write this parameter to the controller. If a SCADAPack 4202 or 4203 or MVT transmitter is selected in the Input Type selection this entry is disabled.
Input at Zero Scale
The value read from the sensor, in unscaled I/O units, when the sensor is at zero scale. This field is grayed if the register type does not require scaling. If a SCADAPack 4202 or 4203 or MVT transmitter is selected in the Input
Type selection this entry is disabled.
Input at Full Scale
The value read from the sensor, in unscaled I/O units, when the sensor is at full scale. This field is grayed if the register type does not require scaling. If a MVT or a SCADAPack 4202 or 4203 transmitter is selected in the Input
Type selection this entry is disabled.
Pressure at Zero Scale
The pressure that corresponds to the zero scale input, or if the input does not require scaling, the minimum pressure that can be read from the sensor.
If a SCADAPack 4202 or 4203 or MVT transmitter is selected in the Input
Type selection this entry is disabled and the value is forced to that of the
MVT Lower Operating Limit.
Pressure at Full Scale
The pressure that corresponds to the full scale input, or if the input does not require scaling, the maximum pressure that can be read from the sensor. If a MVT transmitter or a SCADAPack 4202 or 4203 transmitter is selected in the Input Type selection this entry is disabled and the value is forced to that of the MVT Upper Operating Limit.
* Tap Location
Realflo User and Reference Manual
May 19, 2011
315
Realflo Expert Mode Reference
This is the location of the static pressure pipe tap. The flow calculation needs to be stopped in order to write this parameter to the controller. A dropdown box allows the selection of:
Up
Down upstream pressure tap location. downstream pressure tap location.
Pressure Type
Atmospheric Pressure
The atmospheric pressure is the weight of the atmosphere on the surface of the Earth. At sea level this value is approximately 101.3 kPa. The value entered needs to be the local atmospheric pressure for the flow computer.
This control is disabled and forced to 0 if the Pressure Type is set to
Absolute Pressure.
The control is disabled if the Input Type is set to MVT and the MVT is a
SCADAPack 4202, 4203 or 4102. Its value is set equal to the MVT atmospheric pressure.
The control is disabled if the Compressibility Calculation type is set to
NX-19. The Static Pressure is set to Gage and the Atmospheric pressure is 14.7psi when NX-19 is selected.
The atmospheric pressure entered needs to be greater than zero. The maximum upper limits for atmospheric pressure are:
30 psi and PEMEX units for US1, US2, US3, US4, US5, US6, US7, US8,
4320 lbf/ft2 for IP units
207
2.07 bar kPa for Metric1 units for Metric2 units
0.207 MPa for Metric3 units
207000 Pa for SI units
Location
The Pressure Type selects if the static pressure is measured as gage or absolute pressure. A dropdown box allows the selection of:
Absolute Pressure
Gage Pressure
The control is disabled if the Input Type is set to MVT and the MVT is a
SCADAPack 4202, 4203 or 4102 controller. Its value is set equal to the
MVT pressure type.
The control is disabled if the Compressibility Calculation type is set to NX-
19. The Static Pressure is set to Gage and the Atmospheric pressure is
14.7psi when NX-19 is selected.
Location compensation is only to be used for cases where the static pressure is calibrated using a dead-weight tester. Location compensation adjusts for differences in the gravitational effect on the weights which is primarily dependent on latitude, and elevation. This is due to the centripetal effect of the spinning earth counteracting the effects of gravity. The compensation is not to be used when a pressure measurement is used as a reference instead of placing a specific amount of weight on a dead-weight tester to establish the reference pressure.
Realflo User and Reference Manual
May 19, 2011
316
Altitude
Latitude
Default Value
Realflo Expert Mode Reference
Measurement of the static pressure can be compensated for altitude and latitude. An algorithm is given in the Manual of Petroleum Measurement
Standards, Chapter 21, Section 2, Appendix E, published by the American
Petroleum Association. The algorithm for pressure compensation is used and the temperature compensation factor is not used.
The flow computer applies the compensation to the static pressure reading as it is input to the flow computer. The input pressure is multiplied by the compensation factor and then used by the flow computer whenever the static pressure is used or displayed.
Shown below are some calculated location compensation factors for different locations below.
Ottawa, ON: the compensation factor applied is 1.0000717 (Alt=374ft,
Lat=45deg)
Calgary, AB: the compensation factor applied is 0.994447 (Alt=3438Ft,
Lat=51deg)
Midland, TX: the compensation factor applied is 1.001445 (Alt=2800Ft,
Lat=32deg)
For example in Midland TX, an input pressure of 500psi with applied location compensation would result in:
500 psi * 1.001445 = 500.7225psi
A dropdown box allows the selection of:
Ignore
Compensate
Do not compensate for altitude and latitude.
Compensate for altitude and latitude.
Note that calibration needs to be performed at the location entered for the altitude and latitude compensation when Compensate is selected.
The Altitude is the height above sea level of the location where the sensor is located. The altitude is measured in feet for US unit sets and meters for SI unit sets. This control is disabled if the Location is set to Ignore. Valid inputs are
–30000 to 30000.
The Latitude is the latitude in decimal degrees of the location where the sensor is located. This control is disabled if the Location is set to Ignore.
Valid inputs are
–90 to 90.
The Default Value edit box is enabled when the Input Type is set to a sensor and when the Values on Sensor Fail option on the Inputs tab is configured to Use Default Value.
The value you can enter in Default Value edit box needs to be a range that is checked against the sensor configuration. The actual value needs to be uploaded from the controller when you click Read Actual.
Realflo User and Reference Manual
May 19, 2011
317
Temperature Tab
Realflo Expert Mode Reference
The controls in this tab are used to configure the flow temperature sensor for the meter run.
* Input Type
The configuration of parameters for the Temperature page is done using entry fields or dropdown selections for each parameter. The following edit controls are displayed. Parameter ranges are determined by the selection of the Input Units.
The type of register used for the Input Register. A dropdown box allows the selection of:
Telepace Integer 16
–bit signed integer register.
Float Floating-point register in engineering units.
Raw Float Floating point register requiring scaling.
ISaGRAF integer 32-bit signed integer register in ISaGRAF format.
Coriolis Meter Temperature in engineering units read from the
Coriolis meter. This selection is available only when AGA-11 is selected as the flow calculation type.
4202 DR The internal 4202 DR replaces the first MVT (transmitter 1) on the MVT list when the controller type is set to 4202 DR.
4202 DS The internal 4202 DS replaces the first MVT (transmitter 1) on the MVT list when the controller type is set to 4202 DS.
4203 DR The internal 4203 DR replaces the first MVT (transmitter 1) on the MVT list when the controller type is set to 4203 DR.
4203 DS The internal 4203 DS replaces the first MVT (transmitter 1) on the MVT list when the controller type is set to 4203 DS.
SolarPack 410 The internal SolarPack 410 replaces the first MVT
(transmitter 1) on the MVT list when the controller type is set to
SolarPack 410.
Realflo User and Reference Manual
May 19, 2011
318
Realflo Expert Mode Reference
Configured MVT If there are configured MVT transmitters they are
displayed in the format number (tag name). Refer to the
section for details on configuring MVT transmitters.
section for more information and
examples for register types.
* Input Register
The Input Register is the address of the register in the Flow Computer I/O database that contains the reading from the temperature sensor. The I/O database register will be an input register (3xxxx) or a holding register
(4xxxx). The flow calculation needs to be stopped in order to write this parameter to the controller. If an MVT or a SCADAPack 4202 or 4203 controller is selected in the Input Type selection this entry is disabled.
Input at Zero Scale
The value read from the sensor, in unscaled I/O units, when the sensor is at zero scale. This field is grayed if the register type does not require scaling. If an MVT or a SCADAPack 4202 or 4203 controller is selected in the Input
Type selection this entry is disabled.
Input at Full Scale
The value read from the sensor, in unscaled I/O units, when the sensor is at full scale. This field is grayed if the register type does not require scaling. If an MVT or a SCADAPack 4202 or 4203 controller is selected in the Input
Type selection this entry is disabled.
Temperature at Zero Scale
The temperature that corresponds to the zero scale input, or if the input does not require scaling, the minimum temperature that can be read from the sensor. If an MVT or a SCADAPack 4202 or 4203 controller is selected in the Input Type selection this entry is disabled and the value is forced to that of the MVT Lower Operating Limit.
Temperature at Full Scale
The temperature that corresponds to the full scale input, or if the input does not require scaling, the maximum temperature that can be read from the sensor. If an MVT or a SCADAPack 4202 or 4203 controller is selected in the Input Type selection this entry is disabled and the value is forced to that of the MVT Upper Operating Limit.
Default Value
The Default Value edit box is enabled when the Input Type is sset to a sensor and when the Values on Sensor Fail option on the Inputs tab is configured to Use Default Value.
The value you can enter in Default Value edit box needs to be a range that is checked against the sensor configuration. The actual value needs to be uploaded from the controller when you click Read Actual.
Realflo User and Reference Manual
May 19, 2011
319
Turbine Tab
Realflo Expert Mode Reference
The controls in this tab are used to configure the turbine input for the meter run. The turbine controls are displayed only if the AGA-7 flow calculation is selected on the Inputs property page.
The configuration of parameters for the Turbine page is done using entry fields or dropdown selections for each parameter. The following edit controls are displayed.
* Input Type
This is the type of value found in the Input Register. A dropdown box allows the selection of:
Telepace long 32-bit unsigned integer in Telepace format.
ISaGRAF integer 32-bit signed integer in ISaGRAF format.
* Input Register
The Input Register is the address of the register in the Flow Computer I/O database that contains the reading (number of pulses) from the turbine meter. The I/O database register will be an input register (3xxxx). The flow calculation needs to be stopped in order to write this parameter to the controller.
Low Flow Pulse Limit
The number of pulses below which a low flow alarm will occur. The default value is 10.
Low Flow Detect Time
The length of time the number of pulses needs to remain below the Low
Flow Pulse Limit for a low flow alarm to occur. Valid values are 1 to 5 seconds. The default value is 5.
Contract Tab
Contract Configuration defines parameters for the gas measurement contract. This is referred to as contract configuration because these parameters are often defined by a contract for selling gas.
Realflo User and Reference Manual
May 19, 2011
320
Realflo Expert Mode Reference
With Realflo versions 6.0 and newer the Input Error Action control is no longer available on the Contract tab. When the configuration is written to the flow computer and Realflo detects an older flow computer (5.28 flow computers and earlier) the Input Error Action is automatically written as Do
Not Accumulate Flow.
To enable flow accumulation for 5.28 flow computers and earlier check that the limits selected for the Differential Pressure, Static Pressure or
Temperature inputs do not result in an Input Error condition for your application.
Additional Notes:
The flow calculation needs to be stopped to write the parameters on this page to the controller.
If changes are written to the controller a new hour and day are started in the history logs.
* Contract Units
The configuration of parameters for the Contract page is done using entry fields or dropdown selections for each parameter. The following edit controls are displayed. Parameter ranges are determined by the selection of the
Contract Units.
These are the units of measurement for the contract (calculated) values.
These units are used for outputs from the flow calculations for the meter run.
This value may be different from the units used as inputs to the calculations.
A dropdown box allows the selection of:
US1
US2
US3
IP
Metric1
Realflo User and Reference Manual
May 19, 2011
321
Realflo Expert Mode Reference
Metric2
Metric3
SI
US4
US5
US6
US7
US8
PEMEX
Pemex contract units are not supported on 16-bit controllers.
section of for information on unit types
and how they are displayed.
* Base Temperature
This is the reference temperature to which contract flow values are corrected. The temperature units are displayed depending on the contract units selected.
* Base Pressure
This is the reference pressure to which contract flow values are corrected.
The base pressure is measured as absolute pressure (not a gauge pressure). The pressure units are displayed depending on the contract units selected.
Standard Conditions
The Standard Conditions button sets default values for the Base
Temperature and Base Pressure controls. The conditions are based on the
Contract Units.
Contract Units Standard Base
Temperature
US1
US2
US3
IP
Metric1
Metric2
60 F
60 F
60 F
60 F
15 C
15 C
Metric3
SI
US4
US5
US6
US7
US8
PEMEX
15 C
288.15 K
60 F
60 F
60 F
60 F
60 F
60 F
Standard Base Pressure
14.73 psi
14.73 psi
14.73 psi
2116.2281 lbf/ft
101.325 kPa
1.01325 bar
0.101325 Mpa
101325 Pa
14.73 psi
14.73 psi
14.73 psi
14.73 psi
14.73 psi
14.73 psi
2
* Contract Hour
The hour of the day that starts a new contract day. The contract day begins at 00 minutes and 00 seconds of the specified hour. The contract hour is specified using a 24-hour clock, 00 through 23 hours.
Realflo User and Reference Manual
May 19, 2011
322
Realflo Expert Mode Reference
** Wet Gas Meter Factor
This parameter is an adjustment to the volume, mass and energy values when there is water in the flow. Typically a test is conducted to determine the water content of the gas to be measured. The Wet Gas Meter Factor is applied to the volume, mass and energy values to get a corrected value. For example: if the water content is determined to be 5% then the meter factor is
0.95.
For Realflo versions 6.01 To 6.20, changing Wet Gas Meter Factor requires a new contract day to be started, as the flow calculation has to be stopped.
For Realflo version 6.21 and later, changing the Wet Gas Meter Factor can be accomplished without stopping the flow calculations. This means that a new a new contract day does not have to be started when this parameter needs to be changed.
PEMEX Base Conditions
* Base Temperature
This is the reference temperature to which contract flow values are corrected. The temperature units are displayed depending on the contract units selected.
* Base Pressure
This is the reference pressure to which contract flow values are corrected.
The base pressure is measured as absolute pressure (not a gauge pressure). The pressure units are displayed depending on the contract units selected.
PEMEX Conditions Button
The Secondary Conditions button sets default values for the secondary
Base Temperature and Base Pressure controls. The conditions are based on the Contract Units.
Standard Base Pressure Contract Units Standard Base
Temperature
US1
US2
US3
IP
Metric1
Metric2
60 F
60 F
60 F
60 F
15 C
15 C
Metric3
SI
US4
US5
US6
US7
US8
PEMEX
15 C
288.15 K
60 F
60 F
60 F
60 F
60 F
68 F
14.73 psi
14.73 psi
14.73 psi
2116.2281 lbf/ft
2
101.325 kPa
1.01325 bar
0.101325 Mpa
101325 Pa
14.73 psi
14.73 psi
14.73 psi
14.73 psi
14.73 psi
14.2233 psi
Realflo User and Reference Manual
May 19, 2011
323
Realflo Expert Mode Reference
AGA-3 Configuration
AGA-3 Configuration defines parameters unique to the AGA-3 calculation.
This tab is visible only if the AGA-3 calculation is selected on the Inputs tab for the meter run.
The Warnings area shows messages if the parameters entered are outside the bounds of the regression database used to create the AGA-3 standard.
The calculation may be used outside these bounds, but the results are extrapolated. The calculated flow may not be accurate. It is the user‟s responsibility to decide if the values used are appropriate.
There are two messages on the configuration page. These are grayed if they unless they apply.
If the orifice diameter is smaller than the specification suggests, the message
“The orifice diameter is less than 0.45 inches (11.4 mm). The calculated flow may not be accurate. The user needs to accept responsibility
for the selection.” is displayed.
If the beta ratio is larger than the specification suggests, the message
“The
ratio of orifice diameter to pipe diameter (beta ratio) is greater than 0.75.
The calculated flow may not be accurate. The user must accept responsibility for the selection
.” is displayed.
Orifice Material
The configuration of parameters for the AGA-3 page is done using entry fields or dropdown selections for each parameter. The following edit controls are displayed.
The material the orifice plate for the meter run is made of. A dropdown box allows the selection of:
Stainless Steel
Monel
Carbon Steel
Pipe Material
Realflo User and Reference Manual
May 19, 2011
324
Realflo Expert Mode Reference
The material the meter run pipe is made of. A dropdown box allows the selection of:
Stainless Steel
Monel
Carbon Steel
Orifice Diameter
The diameter of the meter run orifice used for the flow calculation. The measurement units are displayed depending on the input units selected.
Orifice reference temperature
This is the temperature at which the diameter of the meter run orifice was measured. The measurement units are displayed depending on the input units selected.
Pipe Diameter
This is the measurement of the meter run pipe inside diameter. The measurement units are displayed depending on the input units selected.
Pipe reference temperature
The temperature at which the meter run pipe diameter was measured. The measurement units are displayed depending on the input units selected.
Isentropic exponent
In general, this is a thermodynamic property of gas used to predict the relationships between pressure, temperature, volume and energy.
If you are unsure of this value a typical value of 1.3 is commonly used.
Viscosity
This is the viscosity of the measured gas. In general, this is the resistance of a gas or semi-fluid resistance to flow. The measurement units are displayed depending on the input units selected.
Temperature Deadband
The tolerated change in the flowing temperature before temperature dependent factors in the flow calculation are recalculated. Changes in the temperature smaller than the deadband will be ignored in determining the result. The default value is 0. The upper limit is 7°F or 4°C.
Static Pressure Deadband
The tolerated changes in the static pressure before static pressure dependent factors in the flow calculation are recalculated. Changes in the static pressure smaller than the deadband will be ignored in determining the result. A static pressure deadband setting of up to four per cent of the typical static pressure level should have a small effect on the accuracy of the AGA-
3 calculation. The default value is 0. The upper limit is 800 psi or 5500 kPa or equivalent in other units.
Differential Pressure Deadband
The tolerated changes in the differential pressure before differential pressure dependent factors in the flow calculation are recalculated.
Changes in the differential pressure smaller than the deadband will be ignored in determining the result. A change of N in the differential pressure input will cause a change of 0.5 N in the calculation volume at base conditions. It is recommended that the differential pressure deadband be set
Realflo User and Reference Manual
May 19, 2011
325
Realflo Expert Mode Reference to zero. The default value is 0. The upper limit is 4.5 inWC or 1.1 kPa or equivalent in other units.
Realflo User and Reference Manual
May 19, 2011
326
Realflo Expert Mode Reference
AGA-7 Configuration
AGA-7 Configuration defines parameters unique to the AGA-7 calculation.
This tab is visible only if the AGA-7 calculation is selected in the Inputs tab section for the meter run.
K Factor
M Factor
The configuration of parameters for the AGA-7 page is done using entry fields or dropdown selections for each parameter. The following edit controls are displayed.
This is the number of pulses per unit volume of the turbine meter. Valid values are 0.001 to 1000000. The default value is 100.
This is the adjustment to the number of pulses per unit volume for the turbine meter compared to an ideal meter. Valid values are 0.001 to 1000.
The default value is 1.
The SolarPack 410 does not support AGA-7 calculations.
Realflo User and Reference Manual
May 19, 2011
327
Realflo Expert Mode Reference
AGA -11 Configuration
AGA-11 configuration defines parameters unique to the AGA-11 calculation.
This tab is visible only if the AGA-11 calculation is selected in the Flow
Calculation type selection in the Inputs tab for the meter run.
The AGA-11 configuration sets the Coriolis meter Modbus address, the flow computer serial port to use and the command timeout value for messages sent to the Coriolis meter.
The flow computer communicates with one or more Coriolis meters using serial communication. When a direct connection is used, i.e. a single
Coriolis meter connected, either RS-232 or RS-485 serial communication may be used. When the flow computer is communicating with multiple
Coriolis meters, or Coriolis meters and other devices, then RS-485 communication needs to be used.
The serial communication parameters for the flow computer and the Coriolis meter need to match for successful communication to take place.
In order to use an Endress and Hauser Promass 83 Coriolis meter it needs to have the following parameters configured through the local display to match the settings that the Flow Computer will use:
Address (factory setting is 247)
Baud rate (factory setting is 19200)
Parity (factory setting is Even)
Write protection needs to be OFF (factory setting is OFF)
Transmission mode needs to be RTU (factory setting is RTU)
The flow computer serial port settings are configured from the Serial Ports
command. The serial port settings for the serial port used by the flow computer and the Coriolis meter need to match.
NOTES:
If the Promass 83 is installed in a multi-drop fashion the only permitted
Modbus master device is the Flow Computer (address 1) that is configured to poll the Promass 83. Additional master devices or a second Flow Computer polling the Promass 83 can result in communication not succeeding.
SCADAPack 4102, 4012 and 4032 transmitters and Rosemount 3095 sensors have the parity setting fixed at No parity and 1 stop bit. The
Promass 83 Coriolis meter No parity setting requires 2 stop bits. When these sensors are used by the flow computer they need to use another serial port on the flow computer.
SCADAPack 4202 and 4203 sensors may be used on the same serial port as the Promass 83 Coriolis meter.
Realflo User and Reference Manual
May 19, 2011
328
Realflo Expert Mode Reference
Address
Port
Timeout
This is the Modbus address of the Coriolis Meter for serial communications.
Multiple Coriolis meters using the same serial port on the flow computer need to each have a unique Modbus address. Valid Modbus addresses are between 1 and 247. The default address is 247.
This is the communication port on the flow computer that will be used to communicate with the Coriolis meter. Valid port selections depend on the type of controller the flow computer running on. The default port is the first valid port available on the controller.
This is the time the flow computer will wait for a response for Modbus read commands send to the Coriolis meter. When the timeout time is exceeded the command is unsuccessful and an alarm is added to the flow computer alarm list. Valid timeout values are from 0 to 1000 ms. The default value is
50 ms.
Realflo User and Reference Manual
May 19, 2011
329
Realflo Expert Mode Reference
V-Cone Configuration
V-Cone Configuration defines parameters unique to the V-Cone calculation.
This tab is visible only if the V-Cone calculation is selected in the Flow
Calculation type selection in the Inputs tab for the meter run.
Cone Material
This is the material of the V-cone. Valid values are Carbon Steel, Stainless
304, and Stainless 316. The default value is determined by the template selected.
Pipe Material
This is the material from which the meter run pipe is made. Valid values are
Carbon Steel, Stainless 304, and Stainless 316. The default value is determined by the template selected.
Adiabatic Expansion Factor
The Adiabatic Expansion Factor drop down list selects which calculation is used for the adiabatic expansion factor of the calculation.
Select Legacy Calculation to use the older calculation method. This is the default selection. Flow computers prior to version 6.71 support only this selection.
Select V-Cone to use the V-Cone specific calculation. This selection should be used with V-Cone devices.
Select Wafer-Cone to use the Wafer-Cone specific calculation. This selection should be used with Wafer-Cone devices.
This control is disabled and forced to Legacy Calculation if the controller type is not one of SCADAPack 32, SCADAPack 32P, SCADAPack
314/330/334, SCADAPack 350 SCADAPack 4203 or SolarPack 410.
When reading from a flow computer that does not support the adiabatic expansion factor configuration, the method will be set to Legacy Calculation.
When writing to a flow computer that does not support the adiabatic expansion factor method, the configuration registers will be ignored and the expansion factor will not be written.
Realflo User and Reference Manual
May 19, 2011
330
Realflo Expert Mode Reference
Cone Diameter
The diameter of the meter run cone used for the flow calculation. The measurement units are displayed depending on the input units selected.
The default value is 3 inches.
Cone Measurement Temperature
This is the reference temperature at which the cone diameter for the meter run was measured. The measurement units are displayed depending on the input units selected. The default value is 59 degrees F.
Pipe Inside Diameter
This is the measurement of the meter run pipe inside diameter. The measurement units are displayed depending on the input units selected.
The default value is 5 inches.
Pipe reference temperature
The temperature at which the meter run pipe diameter was measured. The measurement units are displayed depending on the input units selected.
The default value is 59 degrees.
Isentropic Exponent
In general, this is a thermodynamic property of gas used to predict the relationships between pressure, temperature, volume and energy. If you are unsure of this value a typical value of 1.3 is commonly used. The default value is 1.3.
Viscosity
This is the viscosity of the measured gas. In general, this is the resistance of a gas or semi-fluid resistance to flow. The measurement units are displayed depending on the input units selected. Valid values are 0 to 1. The default value is 0.010268 centiPoise.
Wet Gas Correction Factor
The Wet Gas Correction Factor Method drop down list selects which calculation is used for the wet gas correction factor of the calculation.
Select Legacy Method to use the older correction method. This is the default selection. Flow computers prior to version 6.73 support only this selection.
Select V-Cone or Wafer Cone to use the V-Cone and Wafer Cone specific calculation. This selection should be used with V-Cone or Wafer
Cone devices.
This control is disabled and forced to Legacy Calculation if the controller type is not one of SCADAPack 32, SCADAPack 32P, SCADAPack
314/330/334, SCADAPack 350 SCADAPack 4203 or SolarPack 410.
The V-Cone or Wafer Cone supported Beta Ratios are:
For Fr (Froude Number) < 5 supported Beta Ratio is 0.55.
For Fr (Froude Number) < 5 supported Beta Ratio is 0.75.
For Fr (Froude Number) > 5 supported Beta Ratio is 0.75.
When V-Cone or Wafer Cone is selected and if the current Beta ratio is not supported when executing verification, an error message is displayed.
Realflo User and Reference Manual
May 19, 2011
331
Realflo Expert Mode Reference
Mass Flow Rate of Liquid
The Mass flow rate of liquid at flow conditions parameter is used by the V-
Cone or Wafer Cone method and can be configured when V-Cone or Wafer
Cone is selected. This information needs to be gathered using a sampling method or a tracer method. The default is 0.
Density of Liquid
The Density of liquid parameter is used by the V-Cone or Wafer Cone method and can be configured when V-Cone or Wafer Cone is selected.
The default is 0.
Density of Liquid
The Density of liquid at flow conditions parameter is used by the V-Cone or
Wafer Cone method and can be configured when V-Cone or Wafer Cone is selected. The default is 0.
Flow Coefficients
When V-Cone or Wafer Cone is selected, configuration of the fixed wet gas factor parameter, as set in the Contract tab, is disabled.
When Legacy Method is selected, configuration of the parameters used by the V-Cone or Wafer Cone method is disabled.
Reynolds number and flow coefficient pairs are entered in a table editor.
The flow coefficient pairs are entered from the calibration data sheet that accompanies the V-Cone Meter. The table is a list view sorted by the
Reynolds number column. The default list contains one pair: Re = 1000000;
Cf = 0.82.
The Add button adds an entry to the table. Up to 10 pairs may be added to the table. The button is grayed if the table is full. If the Re value is the same for all entries in the table only the first pair is used.
The Edit button edits the selected entry. The button is grayed if no entry is selected.
The Delete button removes the selected entry. The button is grayed if no entry is selected.
In the original McCrometer V-Cone Application Sizing sheet that is included with V-Cone meters uses the terminology Cd (discharge coefficient) rather than Cf (flow coefficient). You will need to use the Re and Cd values from the V-Cone Application Sizing sheet for the Re and Cf entries. If the Re value is the same for all entries in the table only the first pair is used.
McCrometer now supplies one value of Cd in the sizing document. You need to enter one Re/Cd pair only. See the McCrometer Application Sizing sheet for the Re/Cd pair for your meter.
Realflo User and Reference Manual
May 19, 2011
332
Realflo Expert Mode Reference
AGA-8 Configuration
AGA-8 Configuration defines parameters unique to the AGA-8 Detailed calculation. This tab is visible only if the AGA-8 calculation is selected in the
Inputs tab for the meter run.
In Flow Computer versions 6.74 and newer when gas ratios are written to the flow computer using the Write Configuration command the new gas ratios are updated in the Configuration Proposed registers and in the
Configuration Actual registers. This allows a Realflo user or SCADA host to immediately confirm the new ratios were written to the flow computer. The new gas ratios are not used by the flow computer until a new density calculation is started.
The configuration of parameters for the AGA-8 page are entered using entry fields or dropdown selections for each parameter. The following edit controls are displayed.
The AGA-8 configuration defines the composition of the gas being measured. The gas composition can be made up of a number of components. These components are usually represented as either a percentage of the gas being measured i.e. 0 to 100% or as a fraction of the gas being measured i.e. 0 to 1.0000.
For each component listed, enter the fraction of the gas that the component represents.
See the AGA-8 Gas Component Range table below for the valid entry range of each gas component.
The value entered needs to be in the range 0 to 1.0000 if Composition
Units value is set to Mole Fractions.
The value entered needs to be in the range 0 to 100% if Composition
Units is set to Percent.
Realflo User and Reference Manual
May 19, 2011
333
Realflo Expert Mode Reference
The Total of all Components field displays the sum of all components. The total of all components needs to be 1.0000 (+/- 0.00001) if Composition
Units is set to Mole Fractions or 100% (+/- 0.00001%) if Composition
Units is set to Percent.
Hexane and higher components may be measured individually or may be combined. This affects the n-Hexane, n-Heptane, n-Octane, n-Nonane, and n-Decane components. This setting is on the AGA-8 Hexanes+ tab.
Hexanes+ is the fraction of the gas that is composed of hexane and higher components. This value is included in the total of all components. This component is visible if Combined Hexanes+ Ratios are selected, and is hidden if individual ratios are selected.
The Relative Density and Heating Value can be calculated from the AGA-
8 calculation or determined in a laboratory.
Select Calculate the Values to have AGA-8 calculate the values.
o The calculated Relative Density is displayed in the Calculated
Compressibility section of the Current Readings view. This is
the real relative density of the gas.
o The calculated Heating Value is displayed in the Calculated
Compressibility section of the Current Readings view. The
heating value is calculated for dry gas.
Select Use Laboratory Values to used fixed values. o Relative Density sets the real relative density of the gas. Valid values are 0.07 to 1.52. The default value is 0.554. This control is disabled if Calculate the Values is selected.. o Heating Value sets the heating value of the dry gas. Valid values are 0 to 1800 BTU(60)/ ft
3
or the equivalent in the selected units. The default value is 1014 BTU(60)/ft
3
or the equivalent in the selected units. This control is disabled if
Calculate the Values is selected.
The Configuration Events dropdown list control selects if the flow computer logs AGA-8 gas composition changes. The AGA-8 gas composition can be changed while the flow calculation is running. This allows an on-line gas chromatograph to provide updates to the gas composition. Frequent changes to the composition will result in the event log filling with gas composition events. When the log is full, further changes cannot be made until Realflo reads the log.
A dropdown box allows the selection of:
Log Changes
Ignore
Log all gas composition changes.
Disable logging of gas composition changes.
The default setting is Log Changes.
The Composition Units drop-down list control selects the units used to enter the AGA-8 composition.
Select Mole Fractions to enter the composition in fractions.
Select Percent to enter the composition in percent.
The default setting is Percent.
Realflo User and Reference Manual
May 19, 2011
334
Realflo Expert Mode Reference
The Normalize button adjusts all non-zero components so that the total of all components is 1.0000 (or 100.00%). The components remain in their current ratio to each other.
The Default button sets components to default values. The methane component is set to 1 (or 100%). All other components are set to 0.
AGA-8 Gas Component Ranges
The range of the fractional values of the components cannot be predetermined. The gas components are shown in the table below. There are two ranges shown for each gas component. Realflo accepts any value in the Expanded Range. Only values in the Normal Range will work in all circumstances.
The run-time error message
“Bracket derivative negative” occurs when the combination of the components at the current pressure and temperature results in an error. The AGA-8 calculation will produce a result even if the error occurs, but the accuracy of the result is not guaranteed.
Component Normal Range Expanded Range
Methane CH
4
Nitrogen
Hydrogen
Carbon Dioxide
Ethane C
2
H
6
Propane C
3
H
8
.4500 to 1.0000 0 to 1.0000
0 to 0.5000 0 to 1.0000
0 to 0.3000 0 to 1.0000
0 to 0.1000
0 to 0.0400
Water 0 to 0.0005
Hydrogen Sulfide 0 to 0.0002
0 to 0.1000
0 to 1.0000
0 to 0.1200
0 to 0.0300
0 to 1.0000
0 to 1.0000
Carbon Monoxide 0 to 0.0300
Oxygen 0
0 to 0.0100 Total Butanes
iButane
nButane
Total Pentanes
iPentane
nPentane
0 to 0.0300
0 to 0.0200 Total Hexane Plus
nHexane nHeptane
nOctane
nNonane
nDecane
Helium
Argon
0 to 0.0200
0
0 to 0.0300
0 to 0.2100
0 to 0.0600
0 to 0.0400
0 to 0.0400
0 to 0.0300
0 to 0.0100
Realflo User and Reference Manual
May 19, 2011
335
Realflo Expert Mode Reference
AGA-8 Hexanes +
AGA-8 Hexanes+ Configuration defines parameters unique to the AGA-8
Detailed calculation. This tab is visible only if the AGA-8 calculation is selected in the Inputs tab for the meter run. Settings on this tab affect settings on the AGA-8 tab.
The AGA-8 Hexanes+ configuration defines the composition of the heavier gas components being measured. There are two options.
The Individual option disables all controls on the property page and all gas components are entered on the AGA-8 tab.
The Combined option enables the edit controls for the portion of the
Hexanes+ ratio that is applied to each of the listed gas component. These portions are represented as a percentage of the gas components being measured i.e. 0 to 100%.
n-Hexane defines the percentage of the Hexanes+ contributed by n-
Hexane.
n-Heptane defines the percentage of the Hexanes+ contributed by n-
Heptane.
n-Octane defines the percentage of the Hexanes+ contributed by n-
Octane.
n-Nonane defines the percentage of the Hexanes+ contributed by n-
Nonane.
n-Decane defines the percentage of the Hexanes+ contributed by n-
Decane.
The Total field displays the sum of portions. This value cannot be edited.
The total of portions needs to be 100 percent.
The Copy Actual to Proposed button copies the values in the actual column to the proposed column.
The Normalize button adjusts non-zero portions so that the total of portions is 100.00%. The portions remain in their current ratio to each other.
Realflo User and Reference Manual
May 19, 2011
336
Realflo Expert Mode Reference
NX-19 Configuration
NX-19 Configuration defines parameters unique to the NX-19 calculation.
This tab is visible only if the NX-19 calculation is selected on the Inputs tab.
This is not supported for PEMEX flow computers.
The configuration of parameters for the NX-19 page is done using entry fields for each parameter. The following edit controls are displayed.
The Specific Gravity edit box is used to enter the specific gravity of the gas being measured.
The Fraction of Carbon Dioxide edit box is used to enter the fractional value of carbon dioxide in the gas being measured. This value needs to be in the range 0 to 0.15.
The Fraction of Nitrogen edit box is used to enter the fractional value of nitrogen in the gas being measured. This value needs to be in the range 0 to
0.15.
The Heating Value edit box is used to enter the heating value of the gas being measured. The units are displayed depending on the contract units selected.
The Configuration Events control selects if the flow computer logs NX-19 gas composition changes. The NX-19 gas composition can be changed while the flow calculation is running. This allows an on-line gas chromatograph to provide updates to the gas composition. Frequent changes to the composition will result in the event log filling with gas composition events. When the log is full, further changes cannot be made until Realflo reads the log.
A dropdown box allows the selection of:
Log Changes Log all gas composition changes.
Ignore Disable logging of gas composition changes.
The default setting is Log Changes.
Realflo User and Reference Manual
May 19, 2011
337
Register Formats
Realflo Expert Mode Reference
Select Log Changes to log all gas composition changes. Select Ignore to disable logging of gas composition changes. The default setting is Log
Changes.
Input configuration values are stored in the controller I/O database registers in the following formats.
Register Type
Telepace integer
Registers Description
1 Signed integer in the range
–32768 to 32767
Telepace long 2 Unsigned long integer in the range 0 to 4,294,967,295. The lower numbered register contains the lower
16 bits of the number. float 2 raw float
ISaGRAF integer
2
2
Floating-point value in the IEEE 754 standard. The lower numbered register contains the upper 16 bits of the number.
Floating-point value in the IEEE 754 standard. The lower numbered register contains the upper 16 bits of the number.
Signed long integer in the range
–
2,147,483,648 to 2,147,483,647. The lower numbered register contains the upper 16 bits of the number.
Telepace Long Example
The Telepace long integer 65550 is represented, in hexadecimal, as
0001000Eh. If this value is stored at register 30010 then:
register 30010 contains the lower 16 bits of the value = 14 (000Eh)
register 30011 contains the upper 16 bits of the value = 1 (0001h)
Floating Point Example
The floating-point value 1.0 is represented, in hexadecimal, as 3F800000h.
If this value is stored at register 30004 then:
register 30004 contains the upper 16 bits of the value = 16256 (3F80h)
register 30005 contains the lower 16 bits of the value = 0 (0000h)
ISaGRAF Integer Example
The ISaGRAF integer 65550 is represented, in hexadecimal, as 0001000Eh.
If this value is stored at register 30020 then:
register 30020 contains the upper 16 bits of the value = 1 (0001h)
register 30021 contains the lower 16 bits of the value = 14 (000Eh)
Process I/O
The Process I/O command configures scaling and alarms for input and output points used by your process. Input points convert integer values read from input modules into floating-point values. Output points convert floatingpoint values into integer values for output modules.
Realflo User and Reference Manual
May 19, 2011
338
Realflo Expert Mode Reference
Process I/O is normally used with I/O points that are not related to the flow runs. Use the Run Configuration command to scale inputs to flow runs.
Process I/O is available on SCADAPack 32, SCADAPack 314/330/334,
SCADAPack 350, SCADAPack 4202 or 4203 controllers and the SolarPack
410.
The Process I/O command opens the Process I/O dialog.
Number of Inputs window indicates the number of inputs in the list. On
SCADAPack, SCADAPack 4202 or 4203 controllers the maximum number of inputs is 10. For SCADAPack 32, SCADAPack 314/330/334,
SCADAPack 350 or SCADAPack 4202 or 4203 controllers and SolarPack
410 the maximum number of inputs 30.
Number of Outputs window indicates the number of outputs in the list. The maximum number of outputs is 10.
The list box displays the configured process I/O points.
Direction indicates if the point is an input or an output.
Source shows the source register for the point.
Destination shows the destination register for the point.
Low Alarm shows the low alarm output register for the point. If no alarm is configured it shows "none".
High Alarm shows the high alarm output register for the point. If no alarm is configured it shows "none".
Click on a row to select the I/O point.
Double-click on a row to edit the I/O point.
Realflo User and Reference Manual
May 19, 2011
339
Realflo Expert Mode Reference
Click on the column headings to sort the data. Clicking once sorts the data in ascending order. Clicking again sorts the data in descending order.
The OK button saves the configuration and closes the dialog. In PEMEX mode the OK button is not active if the user is not logged on with
Administrator privileges.
The Cancel button closes the dialog without saving changes.
The Add Input button adds an input point. It opens the Process Input dialog. The button is disabled if the list already contains the maximum number of inputs.
The Add Output button adds an output point. It opens the Process Output dialog. The button is disabled if the list already contains the maximum number of outputs.
The Copy button adds a copy of the selected point. The button is disabled if no point is selected, or if the list already contains the maximum number of points of the selected type.
The Edit button edits the selected point. It opens the Process Input dialog for input points and the Process Output dialog for output points. The button is disabled if no point is selected.
The Delete button deletes the selected point from the list. The button is disabled if no point is selected.
The Print button prints the Process I/O configuration.
The Help button opens the user manual.
Process Input Dialog
The Process Input dialog edits the configuration of a process input point.
Use an input point to scale a value read from a hardware input module.
Source Register is the address of the register or registers that hold the value to be scaled. Valid values are 30001 to 39999, and 40001 to 49999 if the source format is Telepace Integer and 30001 to 39998, and 40001 to
49998 if the source format is ISaGRAF integer.
Source Format is the format of the data in the register. Valid values are
Telepace Integer and ISaGRAF Integer. The default value is Telepace integer. A Telepace integer is a 16-bit signed number stored in one register.
An ISaGRAF integer is a 32-bit signed value stored in two registers.
Source Range defines the range of the source register. The zero scale is the value of the input at its lowest value. The full scale is the value of the input at its highest value. Valid values are -32768 to 32767 for Telepace
Realflo User and Reference Manual
May 19, 2011
340
Realflo Expert Mode Reference
Integer format, and
–2,147,483,648 to 2,147,483,647 for the ISaGRAF
Integer format. The default zero scale is 0. The default full scale is 32767.
Destination Register is the address of the first of two registers that hold the floating-point result. Registers used by the flow computer are not permitted to be destination registers. These depend on the flow computer type. Valid values are displayed in the table below.
Flow Computer Type
SCADAPack 4202 or 4203
SolarPack 410
Micro 16
SCADAPack
SCADAPack Light
SCADAPack Plus
SCADAPack LP
SCADAPack 100: 1024K
SCADAPack 32
SCADAPack 32P
SCADAPack 314/330/334
SCADAPack 350
Valid Register
Ranges
40500 to 43179
43800 to 46498
40001 to 43179
43800 to 45498
40001 to 43179
Destination Format is the format of the data in the destination registers.
Valid values are MSW First (most significant word first) and LSW First (least significant word first). The default value is MSW First. This is the format of floating point values used by Telepace and ISaGRAF.
Destination Range defines the range of the destination register. The zero scale is the value corresponding to the input at its lowest value. The full scale is the value corresponding to the input at its highest value. Valid values are any floating-point number.
The Destination Alarm section configures alarms for the destination register. A high and low alarm can be configured.
Alarm Point is the coil register that will be turned on if an alarm occurs.
Valid values are 0 and 00001 to 09999. Enter 0 to disable the alarm. The default value is zero.
Setpoint is the value at which the alarm occurs. The low alarm occurs when the destination register is less than the low alarm setpoint. The high alarm occurs when the destination register is greater than the high alarm setpoint.
Valid values are any floating-point number; Realflo does not check the setpoint values. The control is disabled if the corresponding alarm point is set to 0.
Hysteresis keeps minor changes from causing multiple alarms. The Low
Alarm Hysteresis is the amount above the setpoint that the value needs to rise to clear the alarm. The High Alarm Hysteresis is the amount below the setpoint that the value needs to fall to clear the alarm. Valid values are any floating-point number. The control is disabled if the corresponding alarm point is set to 0.
The OK button saves the configuration and closes the dialog. All parameters are checked against their limits. The destination registers and alarm points are checked for conflicts with any other input or output points.
The Cancel button closes the dialog without saving changes.
Realflo User and Reference Manual
May 19, 2011
341
Realflo Expert Mode Reference
Process Output Dialog
The Process Output dialog edits the configuration of a process output point. Use an output point to scale a value so it can be written to a hardware output module.
Source Register is the address of the first of two registers that hold the floating-point value to be scaled. Valid values are 30001 to 39998, and
40001 to 49998.
Source Format is format of the data in the source registers. Valid values are MSW First (most significant word first) and LSW First (least significant word first). The default value is MSW First: this is the format of floating point values used by Telepace and ISaGRAF.
Source Range defines the range of the source register. The zero scale is the value corresponding to the output at its lowest value. The full scale is the value corresponding to the output at its highest value. Valid values are any floating-point number.
Destination Register is the address of the register or registers that hold the result. Registers used by the flow computer are not permitted to be destination registers. These depend on the flow computer type. Valid values are displayed in the table below.
Flow Computer Type
SCADAPack 4202 or 4203.
SolarPack 410
The ISaGRAF Registers apply only to the SCADAPack 4203 controllers
Micro16
SCADAPack
SCADAPack Light
SCADAPack Plus
SCADAPack LP
SCADAPack 100: 1024K
SCADAPack 32
SCADAPack 32P
SCADAPack 314/330/334
SCADAPack 350
Valid Register
Ranges
ISaGRAF Integer
40500 to 43179
43800 to 46498
40001 to 43179
43800 to 45498
40001 to 43179
Valid Register
Ranges
Telepace Integer
40500 to 43179
43800 to 46499
40001 to 43179
43800 to 45499
40001 to 43179
Realflo User and Reference Manual
May 19, 2011
342
Serial Ports
Realflo Expert Mode Reference
Destination Format is format of the data in the register. Valid values are
Telepace Integer and ISaGRAF Integer. The default value is Telepace integer. A Telepace integer is a 16-bit signed number stored in one register.
An ISaGRAF integer is a 32-bit signed value stored in two registers.
Destination Range defines the range of the destination register. The zero scale is the value of the output at its lowest value. The full scale is the value in the register when the input is at its highest value. Valid values are -32768 to 32767 for Telepace Integer format, and
–2,147,483,648 to 2,147,483,647 for the ISaGRAF Integer format. The default zero scale is 0. The default full scale is 32767.
The Source Alarm section configures alarms for the source register. A high and low alarm can be configured.
Alarm Point is the coil register that will be turned on if an alarm occurs.
Valid values are 0 and 00001 to 09999. Enter 0 to disable the alarm. The default value is zero.
Setpoint is the value at which the alarm occurs. The low alarm occurs when the source register is less than the low alarm setpoint. The high alarm occurs when the source register is greater than the high alarm setpoint.
Valid values are any floating-point number; Realflo does not check the setpoint values. The control is disabled if the corresponding alarm point is set to 0.
Hysteresis keeps minor changes from causing multiple alarms. The Low
Alarm Hysteresis is the amount above the setpoint that the value needs to rise to clear the alarm. The High Alarm Hysteresis is the amount below the setpoint that the value needs to fall to clear the alarm. Valid values are any floating-point number. The control is disabled if the corresponding alarm point is set to 0.
The OK button saves the configuration and closes the dialog. All parameters are checked against their limits. The destination registers and alarm points are checked for conflicts with any other input or output points.
The Cancel button closes the dialog without saving changes.
The Serial Ports command configures the serial ports on the flow computer.
The command opens the Flow Computer Serial Port Settings dialog.
The SCADAPack 4202 controllers support Sensor protocol only on com1.
The serial port settings for com1 cannot be edited. The settings are described in the following sections.
Realflo User and Reference Manual
May 19, 2011
343
Realflo Expert Mode Reference
The Port dropdown menu selects the controller serial port to configure. The settings for the port are displayed in the Port Settings controls section of the dialog. The valid serial ports depend on the controller type. The default serial port is com1.
Controller Type com1 com2 com3 com4
Micro16
SCADAPack
SCADAPack Plus
SCADAPack Light
SCADAPack LP
SCADAPack 100
SCADAPack 32
SCADAPack 32P
X
X
SCADAPack 314 X
SCADAPack 330/334 X
SCADAPack 350 X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Realflo User and Reference Manual
May 19, 2011
344
Realflo Expert Mode Reference
Controller Type com1 com2 com3 com4
SCADAPack 4202 DR X
SCADAPack 4202 DS X
SCADAPack 4203 DR X
SCADAPack 4203 DS X
SolarPack 410 X
X
X
X
X
X
X
X
X
X
X
The Protocol dropdown menu selects the communication protocol type.
Valid protocols depend on the controller type as shown in the following table.
Controller Type
Micro16
SCADAPack
SCADAPack Plus
SCADAPack Light
SCADAPack LP
SCADAPack 100
SCADAPack 32
SCADAPack 32P
SCADAPack family of programmable controllers (4202
DR, 4202 DS,
4203 DR and
4203 DS)
SCADAPack
314/330/334
SCADAPack 350
Valid Protocols
None
Modbus RTU
Modbus ASCII
DF1 Full Duplex BCC
DF1 Full Duplex CRC
DF1 Half Duplex BCC
DF1 Half Duplex CRC
DNP
* DF1 protocols are not supported on
SCADAPack 100 controllers with firmware older than version 1.80.
None
Modbus RTU
Modbus ASCII
DF1 Full Duplex BCC
DF1 Full Duplex CRC
DF1 Half Duplex BCC
DF1 Half Duplex CRC
DNP
PPP
Com 1 fixed as Sensor.
Com 2 and Com 3:
None
Modbus RTU
Modbus ASCII
DF1 Full Duplex BCC
DF1 Full Duplex CRC
DF1 Half Duplex BCC
DF1 Half Duplex CRC
DNP
None
Modbus RTU
Modbus ASCII
DF1 Full Duplex BCC
DF1 Full Duplex CRC
Default Protocol
Modbus RTU
Modbus RTU
Com 1 fixed as Sensor.
Com 2 and Com 3 default is Modbus RTU.
Modbus RTU
Realflo User and Reference Manual
May 19, 2011
345
Realflo Expert Mode Reference
Controller Type
SolarPack 410
Valid Protocols
DF1 Half Duplex BCC
DF1 Half Duplex CRC
DNP
Com 1 fixed as Sensor.
Com 2 and Com 3:
None
Modbus RTU
Modbus ASCII
DF1 Full Duplex BCC
DF1 Full Duplex CRC
DF1 Half Duplex BCC
DF1 Half Duplex CRC
DNP
Default Protocol
Com 1 fixed as Sensor.
Com 2 and Com 3 default is Modbus RTU.
The Addressing dropdown menu selects the addressing mode for the selected protocol. The control is disabled if the protocol does not support it.
Valid addressing modes depend on the selected protocol as shown in the following table.
Protocol
Modbus RTU
Modbus ASCII
DF1 Full Duplex BCC
DF1 Full Duplex CRC
DF1 Half Duplex BCC
DF1 Half Duplex CRC
DNP
PPP
None
Valid Mode
Standard
Extended
Default Mode
Standard
Control is disabled N/A
Control is disabled N/A
Control is disabled N/A
Control is disabled N/A
The Station entry sets the station address for the selected controller serial port. Valid addresses depend on the protocol and addressing mode selected, as shown in the table below.
Protocol
Modbus RTU
Modbus ASCII
Valid Addresses
Standard addressing:
1 to 255
Extended addressing:
1 to 65534
0 to 254
Default Address
1
DF1 Full Duplex BCC
DF1 Full Duplex CRC
DF1 Half Duplex BCC
DF1 Half Duplex CRC
DNP
PPP
None
Control is disabled
Control is disabled
Control is disabled
N/A
N/A
N/A
N/A
The Duplex dropdown menu selects full or half-duplex operation for the selected Port. Valid and default duplex settings depend on the serial port
Realflo User and Reference Manual
May 19, 2011
346
Realflo Expert Mode Reference and controller type, as shown in the table below. The duplex is forced to Half if a MVT transmitter is configured on the port.
Controller Type
Micro16
SCADAPack
SCADAPack Plus
SCADAPack Light
SCADAPack LP
SCADAPack 100
SCADAPack 32
SCADAPack 32P
SCADAPack 4202 DR
SCADAPack 4202 DS
SCADAPack 4203 DR
SCADAPack 4203 DS
SCADAPack 314
SCADAPack 330/334
SCADAPack 350
SolarPack 410
com1 com2 com3 com4
Valid Def. Valid Def. Valid Def. Valid Def.
Full
Half
Full
Half
Full
Half
Full
Half
Full Full
Half
Full Full
Half
Full Full
Half
Full
Full
Full
Half
Half
Half
Half
Full
Half
Half
Full
Half Half
Full
Half
Full Full
Half
Half Half Full
Half
Full
Half
Full
Half
Full
Half
Full
Full
Full Half Half
Half
Full Full
Half
Half Full
Half
Full Full
Half
Full
Half Half Half Full
Half
Full
Full Half Half Half Half
Full
Half
Half
Half
Full
Half
Full
Half
Half Full
Half
Half Full
Half
Half Full
Half
Half Full
Half
Half
Half
Half Half Full
Half
Half Half Full
Half
Half Half
Full
Half Full
Full
Full
The Baud Rate dropdown menu selects the communication speed for the selected serial port. Valid baud rates depend on the serial port and controller type, as shown in the table below. The default value is always
9600 baud.
Baud
Rate
Controller
Micro 16
Com 1, Com 2
SCADAPack
Com 1, Com 2
X X X X X X X X
X X X X X X X X
Realflo User and Reference Manual
May 19, 2011
347
Realflo Expert Mode Reference
Baud
Rate
Controller
Com 3
SCADAPack
Plus
X X X X X X X X
Com 1, Com 2
Com 3, Com 4
SCADAPack
Light
Com 1, Com 2
X X X
X
X
X
X
X
X
X
X
X
X
X X X
X X X X X X X X
Com 4
Com 3
X X X X X X
SCADAPack LP
Com 1, Com 2 X X X X X X X X
X X
X X X X X X X X
SCADAPack 100: 1024K
Com 1, Com 2 X X X X X X X X
SCADAPack32
X X X X X X X X X X Com 1, Com 2,
Com 4
Com 3
SCADAPack32P
Com 1, Com 2,
Com 4
SCADAPack 314
X X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Com 1 and Com
2
X
SCADAPack 330/334
X X X X X X X X X
Com 1, Com 2,
Com 3
X X X X X X X X X X
SCADAPack 350
Com 1, Com2,
Com3
X X X X X
SCADAPack of Programmable Controllers
X X X X X
Com1 X
Realflo User and Reference Manual
May 19, 2011
348
Realflo Expert Mode Reference
Baud
Rate
Controller
Com2
Com3
SolarPack 410
X X X
X
X
X
X
X
X
X
X
X
X
X X X
Com1 (disabled)
Com2
X
X X X X X X X X X X
Com3 X
The Data Bits dropdown menu selects the number of data bits. Valid selections are 7 and 8 bits. This parameter is forced to 8 bits when the protocol type is Modbus RTU, PPP or any DF1 protocol. The default selection is 8 bits.
The Parity dropdown menu selects the parity for the selected port. Valid selections depend on the serial port, controller type and data bits, as shown in the table below. The default selection is none.
Controller Type com1 com2 com3
Micro16
com4
7 bits 8 bits 7 bits 8 bits
N/A N/A
SCADAPack
SCADAPack
Plus
SCADAPack
Light
None even odd
None even odd
None even odd none even odd none even odd none even odd none even odd none even odd even odd space mark even odd space mark
N/A none even odd mark none even odd mark
N/A even odd space mark even odd space mark
N/A none even odd mark none even odd mark
SCADAPack LP none even odd none even odd even odd space mark none even odd mark
Realflo User and Reference Manual
May 19, 2011
349
Realflo Expert Mode Reference
Controller Type com1 com2 com3 com4
7 bits 8 bits 7 bits 8 bits
SCADAPack
100 none even odd
SCADAPack 32 none even odd
SCADAPack
32P
SCADAPack
4202 DR
SCADAPack
4202 DS
SCADAPack
4203 DR
SCADAPack
4203 DS
SCADAPack
314 none even odd none none even odd none even odd none even odd none none even odd none even odd even odd space mark
N/A none even odd mark none even odd
N/A none even odd mark none even odd none even odd
N/A
N/A
N/A
SCADAPack
330/334
SCADAPack
350
SolarPack 410 none even odd none even odd none even odd none even odd none
N/A
N/A none none even odd none even odd
The Stop Bits dropdown menu selects the number of stop bits for the selected serial port. Valid selections are 1 and 2. Valid selection for com3 is
1 stop bit. The default selection is 1.
The Rx Flow dropdown menu selects the receiver flow control for the selected port. Valid selections depend on the protocol, controller type, and serial port, as shown in the table below. If there is only one valid value the control is disabled. If there is more than one possible value, the default selection is none.
Protocol
DF1 Full BCC
DF1 Full CRC
DF1 Half BCC
DF1 Half CRC
DNP
Controller
Micro16
SP
SP Plus
SP Light
SP LP
SP 100
SP 32
com1 com2 com3
None None N/A
None
None
None
None
None
None
None
None
None
None
None
None
None
None
N/A
None
N/A
None
com4
N/A
N/A
None
None
N/A
N/A
None
Realflo User and Reference Manual
May 19, 2011
350
Protocol
Modbus RTU
Controller
SP 32P
SCADAPack
4202 DR
SCADAPack
4202 DS
SCADAPack
4203 DR
SCADAPack
4203 DS
SCADAPack
314/330/334
SCADAPack
350
com1
None
None
None
None
SolarPack 410 None
Micro16 None
SP None
SP Plus
SP Light
SP LP
None
None
None
Realflo Expert Mode Reference
com2
None
None
None
None
None
None
com3
None
None
Ignore
CTS
None
None
None
N/A
None Modbus
RTU
None Modbus
RTU
None N/A
com4
None
N/A
N/A
N/A
N/A
N/A
N/A
Modbus
RTU
Modbus
RTU
N/A
SP 100
SP 32
SP 32P
None
Modbu s RTU
Modbu s RTU
None Modbus
RTU
None N/A
Modb us
RTU
Modb us
RTU
None
Modbus
RTU
Modbus
RTU
None
Ignore
CTS
N/A
Modbus
RTU
Modbus
RTU
N/A SCADAPack
4202 DR
SCADAPack
4202 DS
SCADAPack
4203 DR
SCADAPack
4203 DS
None
None
SCADAPack
330/334
SCADAPack
350
SCADAPack
314
None
None
SCADAPack
330/334
SCADAPack
350
None
SolarPack 410 None
None
None
None
None
None
None
None
N/A
None
None
N/A
N/A
N/A
N/A
N/A
Realflo User and Reference Manual
May 19, 2011
351
Protocol
None
Modbus ASCII
Controller
Micro16
SP
SP Plus
SP Light
SP LP
SP 100
SP 32
SP 32P
SCADAPack
4202 DR
SCADAPack
4202 DS
SCADAPack
4203 DR
SCADAPack
4203 DS
SCADAPack
330/334
SCADAPack
350
com1 com2 com3
None
Xon/Xo ff
None
Xon/X off
N/A none None
Xon/Xo ff
None
Xon/X off none None
Xon/Xo ff
None
Xon/Xo ff
None
Xon/Xo ff
None
Xon/Xo ff none
Modbu s RTU none
Modbu s RTU
None
None
None
SCOLARPack
410
SCADAPack
314
None
None
SCADAPack
330/334
SCADAPack
350
None
SolarPack 410 None
Realflo Expert Mode Reference
None
Xon/X off none
Modb us
RTU none
Modb us
RTU
None
None
Xon/X off
None
Xon/X off
None
Xon/X off
None
None
None
None
None
None
N/A none
N/A none
Modbus
RTU none
Modbus
RTU
None
Modbus
RTU
None
None
N/A
N/A
None
None
com4
N/A
N/A none none
N/A
N/A none
Modbus
RTU none
Modbus
RTU
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Realflo User and Reference Manual
May 19, 2011
352
Realflo Expert Mode Reference
Protocol
PPP
Controller
SP 32
SP 32P
com1 com2 com3
Queue d
Queu ed
com4
Queued Queued
Queue d
Queu ed
Queued Queued
The Tx Flow dropdown menu selects the transmitter flow control for the selected port. Valid selections depend on the protocol, controller type, and serial port, as shown in the table below. The default selection is none.
Protocol
Modbus RTU
DF1 Full BCC
DF1 Full CRC
DF1 Half BCC
DF1 Half CRC
DNP
None
Modbus ASCII
Controller
Micro16
SP
SP Plus
SP Light
SP LP
SP 100
SP 32
SP 32P
None
None
Ignore
CTS
None
Ignore
CTS
None SCADAPack
4202 DR
SCADAPack
4202 DS
SCADAPack
4203 DR
SCADAPack
4203 DS
SCADAPack
314
SCADAPack
330/334
SCADAPack
350
None
None
None
SolarPack 410 None
Micro16 None
Xon/Xo ff
com1 com2 com3 com4
None
None
None
None
None
None N/A
None None
Ignore
CTS
None None
Ignore
CTS
None N/A
N/A
N/A
None
Ignore
CTS
None
Ignore
CTS
N/A None None
Ignore
CTS
None N/A
None
Ignore
CTS
None
Ignore
CTS
None
Ignore
CTS
None
N/A
None
Ignore
CTS
N/A
None
Ignore
CTS
None
Ignore
CTS
N/A
None
None
None
None
None
Xon/X off
None
N/A
None
None
N/A
N/A
N/A
N/A
N/A
N/A
Realflo User and Reference Manual
May 19, 2011
353
Realflo Expert Mode Reference
Protocol
PPP
Controller
SP
SP Plus
SP Light
SP LP
SP 100
SP 32
SP 32P
None
Ignore
CTS
None
Ignore
CTS
N/A SCADAPack
4202 DR
SCADAPack
4202 DS
SCADAPack
4203 DR
SCADAPack
4203 DS
SCADAPack
314
SCADAPack
330/334
SCADAPack
350
N/A
None
None
SolarPack 410 None
SP 32 None
Ignore
CTS
SP 32P None
Ignore
CTS
None
Xon/Xo ff
None
Xon/Xo ff
None
Xon/Xo ff
None
Xon/Xo ff
None
Xon/Xo ff
com1 com2 com3 com4
None
Xon/X off
None
Xon/X off
None
Xon/X off
None
Xon/X off
None
Xon/X off
None
Ignore
CTS
None
Ignore
CTS
None
None
Ignore
CTS
None
Ignore
CTS
N/A
None
Ignore
CTS
N/A
None
Ignore
CTS
N/A
None
Ignore
CTS
N/A
None
Ignore
CTS
None
Ignore
CTS
N/A
N/A
None
Ignore
CTS
None
Ignore
CTS
N/A
None
None
None
None
None
Ignore
CTS
None
Ignore
CTS
None
N/A
None
None
None
Ignore
CTS
None
Ignore
CTS
N/A
N/A
N/A
N/A
None
Ignore
CTS
None
Ignore
CTS
The Port Type dropdown menu selects the type of serial port. Valid selections depend on the serial port and controller type as shown in the table below. The default selection is RS-232. The options are as follows:
RS-232: for a regular RS-232 connection.
RS-232 Dial-up modem: If an external dial-up modem is used on the
RS-232 connection.
Realflo User and Reference Manual
May 19, 2011
354
Realflo Expert Mode Reference
RS-232 Collision Avoidance: RS-232 connection with collision avoidance based on the CD signal is available only when the DNP protocol type is selected on the serial port, and the serial port supports handshaking.
When this flow control is enabled, the protocol uses the Carrier Detect
(CD) signal provided by the serial port to detect if the communication medium is in use. If it is, it waits until the medium is free before transmitting.
Prior to transmitting each Data Link (DL) frame, the controller will test the CD line. If it is active, a countdown equal to the DL timeout will be set and CD will be monitored every 100 ms throughout this countdown period. If the Data Link timeout is set to the minimum of 100 ms, the CD line will be tested once.
If the CD line reports inactive (line not in use), a frame will be transmitted immediately, and a new DL timeout is started as normal. On the other hand, if CD remains active during the DL timeout, the transmission attempt will be unsuccessful. If a non-zero retry is configured in the Data Link layer, the test will be repeated until the number of retries has been exhausted.
RS-232 Collision Avoidance is supported only on serial ports which support handshaking and whose protocol type is set for DNP.
RS-485: for a regular RS-485 connection.
Controller Type
Micro16
SCADAPack
SCADAPack Plus
SCADAPack Light
SCADAPack 32
SCADAPack 32P
com1
RS-232
RS-232 dial-up modem
RS-232
Collision
Avoidance
RS-485
RS-232
RS-232 dial-up modem
RS-232
Collision
Avoidance
Port type
RS-232 applies for
RS-232 or
RS-485 operation on COM1.
com2, com4
RS-232
com3
RS-232 dial-up modem
RS-232
Collision
Avoidance
RS-232
RS-232 dial-up modem com4 is available on the
SCADAPack
Light and Plus only.
RS-232 RS-232
RS-232 dial-up modem
RS-232 dial-up modem
RS-232
Collision
Avoidance
Realflo User and Reference Manual
May 19, 2011
355
Controller Type
Realflo Expert Mode Reference
com3 com1
Jumper J9 on the controller board needs to be installed to configure
COM1 for
RS-485 operation.
com2, com4
Controller Type
SCADAPack
Programmable
Controllers
(4202 DR, 4202
DS, 4203 DR and
4203 DS).
SCADAPack 100
SCADAPack LP
com1
N/A (RS-232)
RS-232
RS-232 Collision
Avoidance
Port type RS-232 applies for RS-232 or RS-485 operation on Com 1.
RS-485
SCADAPack 314 RS-232
RS-232 dial-up modem
RS-232 Collision
Avoidance
RS-485
Port type RS-232 applies for RS-232 or RS-485 operation on COM1. Jumper
J8 on the controller board needs to be installed to configure
COM1 for RS-485 operation.
com2, com3
RS-232
RS-232 Dialup Up Modem
(com 2 only)
RS-232 Port Type applies for RS-232 or RS-485 operation.
RS-232
RS-232 dial-up modem
RS-232 Collision
Avoidance
Com 3: not available
RS-232
RS-232 dial-up modem
RS-232 Collision
Avoidance
RS-232
RS-232 dial-up modem
RS-232 Collision
Avoidance
Port type RS-232 applies for RS-232 or RS-485 operation on COM2.
Jumper J10 on the controller board needs to be installed to configure
COM2 for RS-485 operation.
Realflo User and Reference Manual
May 19, 2011
356
Realflo Expert Mode Reference
Controller Type com1
SCADAPack
330/334
RS-232
RS-232 dial-up modem
RS-232 Collision
Avoidance
RS-485
Port type RS-232 applies for RS-232 or RS-485 operation on COM1. Jumper
J8 on the controller board needs to be installed to configure
COM1 for RS-485 operation.
SCADAPack 350 RS-485
SolarPack 410 RS-232
com2, com3
RS-232
RS-232 dial-up modem
RS-232 Collision
Avoidance
Port type RS-232 applies for RS-232 or RS-485 operation on COM2.
Jumper J10 on the controller board needs to be installed to configure
COM2 for RS-485 operation.
RS-232
RS-232 dial-up modem
RS-232 Collision
Avoidance
Port type RS-232 applies for RS-232 or RS-485 operation on COM2.
Jumper J13 on the controller board needs to be installed to configure
COM2 for RS-485 operation.
RS-232
The Store and Forward dropdown menu selects whether store and forward messaging is enabled for the port. Valid selections are enabled and disabled. If this option is enabled, messages will be forwarded according to the settings in the store and forward routing table. The default selection is disabled. This control is disabled when PPP protocol is selected for a serial port, or if any of the DF1 protocols are selected and for com 1 on the
SCADAPack 4202 or 4203 of controllers.
The Store and Forward menu selection changes to Routing menu selection when DNP protocol is selected for a serial port. Valid selections are enabled and disabled. Routing needs to be enabled on a serial port to enable routing of DNP messages.
The Enron Modbus or PEMEX Modbus dropdown menu lets you enable or disable Enron Modbus or PEMEX Modbus for the port. If this option is enabled, the controller, in addition to regular Modbus messages, will handle
Enron Modbus or PEMEX Modbus messages. Valid selections depend on the protocol as shown in the table below. This control is disabled when PPP protocol is selected for a serial port and for com 1 on the 4202 controllers.
Protocol
Modbus RTU
Modbus ASCII
Valid Selections
Enabled
Disabled
Default Selection
Disabled
Realflo User and Reference Manual
May 19, 2011
357
IP Command
Realflo Expert Mode Reference
Protocol
DF1 Full Duplex BCC
DF1 Full Duplex CRC
DF1 Half Duplex BCC
DF1 Half Duplex CRC
DNP
None
Valid Selections
Control is disabled
Control is disabled
Control is disabled
Default Selection
N/A
N/A
N/A
The Enron Station or PEMEX Station entry selects the Enron Modbus or
PEMEX Modbus station address for the serial port. Valid entries depend on the protocol. The station needs to be different from the Modbus station set in the Station control. This allows Enron Modbus or PEMEX Modbus and
Modbus communication can occur on the same port. This entry is greyed out if Enron Modbus or PEMEX Modbus is not enabled.
Protocol
Modbus RTU
Modbus ASCII
Valid Values
Standard addressing:
1 to 255
Extended addressing:
1 to 65534
Control is disabled DF1 Full Duplex BCC
DF1 Full Duplex CRC
DF1 Half Duplex BCC
DF1 Half Duplex CRC
DNP
None
Control is disabled
Control is disabled
Default Value
2
N/A
N/A
N/A
The OK button saves the settings for all serial ports and closes the dialog. In
PEMEX mode the OK button is not active if the user is not logged on with
Administrator privileges.
The Cancel button closes the dialog without saving.
The Default button sets the parameters for the port to their default values.
When the IP Configuration menu item is clicked under the Controller menu the IP Configuration dialog is opened. This dialog is available only when the controller type is set to SCADAPack 314/330/334, SCADAPack 350,
SCADAPack 32 or SCADAPack 32P.
The IP Configuration dialog has a tree control on the left side of the window.
Headings on the tree control are enabled or disabled depending on the controller type.
The SCADAPack 32 and SCADAPack 32P support Point-To-Point
Protocol (PPP) on the serial ports. The tree control displays headings for com 1 Port through com 4 Port and PPP Login are displayed for configuring the serial ports for PPP. PPP is not supported on
SCADAPack 314/330/334 and SCADAPack 350 the headings for com 1
Port through com 4 Port and PPP Login are not displayed.
The SCADAPack 314/330/334 and SCADAPack 350 support an FTP
(File Transfer Protocol) server. The tree control will display a heading for
Realflo User and Reference Manual
May 19, 2011
358
Realflo Expert Mode Reference
FTP when these controllers are used. FTP is not supported on
SCADAPack 32 and SCADAPack 32P.
Each of the tree control selections is explained in the following sections of this user manual.
The IP Configuration dialog has a tree control on the left side of the window.
This tree control contains headings for:
LAN Port
Modbus Common
Modbus/TCP
Modbus RTU in UDP
Modbus ASCII in UDP
DNP in TCP
DNP in UDP
Friendly IP List
When a tree control is selected by clicking the mouse on a heading, a property page is opened for the header selected. From the property page the IP configuration parameters for the selected header is displayed.
The Default button selects the default values for the current property page.
The OK button saves the configuration and closes the Controller IP
Configuration dialog. In PEMEX mode, the OK button is not active if the user is not logged on with Administrator privileges.
The Cancel button closes the Controller IP Configuration dialog without saving any changes.
Realflo User and Reference Manual
May 19, 2011
359
LAN Port
Realflo Expert Mode Reference
The LAN Port property page is selected for editing by clicking LAN Port in the tree control section of the Controller IP Configuration dialog. When selected the LAN Port property page is active.
The IP Address is the address of the controller LAN port. The IP address is statically assigned. Contact your network administrator to obtain an IP address for the controller. The default value is 0.0.0.0.
The Subnet Mask is determines the subnet on which the controller LAN port is located. The subnet mask is statically assigned. Contact your network administrator to obtain the subnet mask for the controller. The default value is 255.255.255.0.
The Gateway determines how your controller communicates with devices outside its subnet. The LAN radio button selects the gateway specified in the LAN edit box. Enter the IP address of the gateway. The gateway is located on the LAN port subnet. The gateway is statically assigned. Contact your network administrator to obtain the gateway IP address. The default value is 0.0.0.0.
The PPP radio button selects the serial port where the gateway is located.
The PPP dropdown menu displays only those serial ports currently configured for the PPP protocol. Select a serial port from this menu to select its remote IP address as the gateway. The gateway is automatically assigned to the remote IP address of the selected serial port.
SCADAPack 32 or SCADAPack 32P PPP Controls com1 Port
The com1 Port property page is selected for editing by clicking com1 Port in the tree control section of the Controller IP Configuration dialog. When selected, the com1 Port property page is active. This page configures the
IP settings for com1 when the PPP protocol is selected for this serial port.
Realflo User and Reference Manual
May 19, 2011
360
Realflo Expert Mode Reference
The Enable Auto Answer (PPP Server) checkbox enables the PPP Server on this serial port. Check this box if you want to allow a remote PPP client to connect to this port. This checkbox enables the remaining settings in the page.
The IP Address is the address of this serial port. The IP address is statically assigned. Contact your network administrator to obtain an IP address for this serial port.
The Subnet Mask determines the subnet on which this serial port is located. The subnet mask is statically assigned. Contact your network administrator to obtain the subnet mask for this serial port. In a standard
PPP configuration, a subnet mask of 255.255.255.255 is used to restrict routing on this serial port to a single host (i.e. the Remote IP Address).
If another subnet mask is used, packets on that subnet will be forwarded to this serial port. Any address on that subnet in addition to the Remote IP
Address can be used for the remote host in this case.
The Remote IP Address is the address that will be assigned to the remote
PPP client connected to this serial port. The Automatic radio button automatically selects the address to be the serial port‟s IP address + 1. The second radio button selects the address specified in the edit box. Enter the
IP address to assign to the remote client.
The Allow remote to specify its own IP address checkbox allows the remote PPP client to assign its own IP address. Check this box if you want to allow this option. The client may or may not request its own IP address. If the client does not make this request, the PPP Server will assign the IP address selected.
The Authentication determines the login protocol used at the start of every
PPP connection. The None radio button removes the login step. The PAP radio button selects the Password Authentication Protocol (PAP). The
CHAP radio button selects the Challenge-Handshake Authentication
Realflo User and Reference Manual
May 19, 2011
361
com2 Port com3 Port com4 Port
PPP Login
Realflo Expert Mode Reference
Protocol (CHAP). PAP and CHAP usernames and passwords are configured on the PPP Login page.
The Inactivity Timeout is the inactivity timeout for this serial port. If there has been no activity on an existing PPP connection for the selected number of minutes, then the connection is automatically closed. If there is a modem connected it is hung up. Setting this value to zero disables the timeout.
The com2 Port property page is selected for editing by clicking com2 Port in the tree control section of the IP Configuration dialog. When selected the com2 Port property page is active. This page configures the IP settings for com2 when the PPP protocol is selected for this serial port.
The com2 Port property page provides the same options as the com1 Port page. See the com1 Port page for a description of these options.
The com3 Port property page is selected for editing by clicking com3 Port in the tree control section of the IP Configuration dialog. When selected the com3 Port property page is active. This page configures the IP settings for com3 when the PPP protocol is selected for this serial port.
The com3 Port property page provides the same options as the com1 Port page. See the com1 Port page for a description of these options.
The com4 Port property page is selected for editing by clicking com4 Port in the tree control section of the IP Configuration dialog. When selected the com4 Port property page is active. This page configures the IP settings for com4 when the PPP protocol is selected for this serial port.
The com4 Port property page provides the same options as the com1 Port page. See the com1 Port page for a description of these options.
The PPP Login property page is selected for editing by clicking PPP Login in the tree control section of the IP Configuration dialog. When selected the
PPP Login property page is active.
This page configures the username and password list for PPP login authentication. The list is used only by those serial ports configured for the
PPP protocol using PAP or CHAP authentication.
Realflo User and Reference Manual
May 19, 2011
362
Realflo Expert Mode Reference
Select the Add button to enter a new username to the list. Selecting the Add button opens the Add PPP Username dialog.
Select the Edit button to edit the username highlighted in the list. Selecting the Edit button opens the Edit PPP Username dialog. This button is disabled if there are no entries in the list.
The Delete button removes the selected usernames from the list. This button is disabled if there are no entries in the list.
Add PPP Username dialog
This dialog selects a new PPP username and password.
The Username edit box selects the username. A username is any alphanumeric string 1 to 16 characters in length, and is case sensitive.
The Password edit box selects the password. A password is any alphanumeric string 1 to 16 characters in length, and is case sensitive.
The Verify Password edit box selects the verify password. Enter the same string entered for the password.
The Cancel button discards any changes made to this dialog and exits the dialog.
The OK button to accept changes made to this dialog and exits the dialog.
Edit PPP Username dialog
Realflo User and Reference Manual
May 19, 2011
363
Realflo Expert Mode Reference
This dialog edits a PPP username and password selected from the list.
The Username edit box selects the username. A username is any alphanumeric string 1 to 16 characters in length, and is case sensitive.
The Password edit box selects the password. A password is any alphanumeric string 1 to 16 characters in length, and is case sensitive.
The Verify Password edit box selects the verify password. Enter the same string entered for the password.
The Cancel button discards any changes made to this dialog and exits the dialog.
The OK button to accept changes made to this dialog and exits the dialog.
Modbus Common
The Modbus Common property page is selected for editing by clicking
Modbus Common in the tree control section of the IP Configuration dialog.
When selected the Modbus Common property page is active.
The Addressing menu selects standard or extended Modbus addressing.
Standard addressing allows 255 stations and is compatible with standard
Modbus devices. Extended addressing allows 65534 stations, with stations
1 to 254 compatible with standard Modbus devices. The default value is standard.
Realflo User and Reference Manual
May 19, 2011
364
Modbus/TCP
Realflo Expert Mode Reference
The Station menu sets the station number of the controller. The valid range is 1 to 255 if standard addressing is used, and 1 to 65534 if extended addressing is used. The default value is 1.
The Store and Forward selection controls forwarding of messages using IP based protocols. If this option is enabled, messages will be forwarded according to the settings in the store and forward routing table. The default value is disabled.
The Enron Modbus box selects whether or not Enron Modbus is enabled for the port. If this option is enabled, the controller, in addition to regular
Modbus messages, will handle Enron Modbus messages.
The Enron Station box selects the Enron Modbus station address. The valid range for Enron Station is 1 to 255 if the Addressing control is set to
Standard. The valid range for Enron Station is 1 to 65534 if the Addressing control is set to Extended. The Enron station needs to be different from the
Modbus station set in the Station edit box. This allows Enron Modbus and
Modbus communication to occur on the same port.
The Modbus/TCP property page is selected for editing by clicking
Modbus/TCP in the tree control section of the IP Configuration dialog. When selected the Modbus/TCP property page is active.
The Server selection selects whether the server is enabled. If this option is enabled the controller supports incoming slave messages. Disabling this option stops the controller from processing slave messages. Master messaging is always enabled.
The Master Idle Timeout determines when connections to a slave controller are closed. Setting this value to zero disables the timeout; the connection will be closed only when your program closes it. Any other value sets the timeout in seconds. The connection will be closed if no messages are sent in that time. This allows the slave device to free unused
Realflo User and Reference Manual
May 19, 2011
365
Realflo Expert Mode Reference connections. Valid timeout range is 0 to 4294967295 seconds. The default value is 10 seconds.
The Server Idle Timeout determines when connections from a remote device are closed. Setting this value to zero disables the timeout; the connection will be closed only when the remote device closes it. Any other value sets the timeout in seconds. The connection will be closed if no messages are received in that time. This allows the controller to free unused connections. Valid timeout range is 0 to 4294967295 seconds. The default value is 250 seconds.
The TCP Port sets the port used by the Modbus/TCP protocol. In all cases this should be set to 502. This is the well-known port number for
Modbus/TCP. Modbus/TCP devices use 502 by default, and on many devices the value cannot be changed. It is suggested that you change this value only if this port is used by another service on your network. Valid port number range is 1 to 65534. Consult your network administrator to obtain a port if you are not using the default.
Modbus RTU in UDP
The Modbus RTU in UDP property page is selected for editing by clicking
Modbus RTU in UDP in the tree control section of the IP Configuration dialog. When selected the Modbus RTU in UDP property page is active.
The Server selection selects whether the server is enabled. If this option is enabled the controller supports incoming slave messages. Disabling this option keeps the controller from processing slave messages. Master messaging is always enabled.
The UDP Port sets the port used by the protocol. Valid port number range is
1 to 65535. The default value is 49152. This is a recommendation only.
Consult your network administrator to obtain a port if you are not using the default.
Realflo User and Reference Manual
May 19, 2011
366
Realflo Expert Mode Reference
Modbus ASCII in UDP
The Modbus ASCII in UDP property page is selected for editing by clicking
Modbus ASCII in UDP in the tree control section of the IP Configuration dialog. When selected the Modbus ASCII in UDP property page is active.
The Server selection selects whether the server is enabled. If this option is enabled the controller supports incoming slave messages. Disabling this option keeps the controller from processing slave messages. Master messaging is always enabled.
The UDP Port sets the port used by the protocol. Valid port number range is
1 to 65534. The default value is 49153. This is a recommendation only.
Consult your network administrator to obtain a port if you are not using the default.
Realflo User and Reference Manual
May 19, 2011
367
DNP in TCP
Realflo Expert Mode Reference
The DNP in TCP property page is selected for editing by DNP in TCP in the tree control section of the IP Configuration dialog. When selected the DNP in TCP property page is active.
The Protocol selection selects whether the DNP in TCP protocol is enabled. If this option is enabled the controller supports DNP in TCP protocol. Disabling this option keeps the controller from processing DNP in
TCP protocol messages. Master messaging is always enabled. The default selection is disabled.
The Server Idle Timeout determines when connections from a remote device are closed. Setting this value to zero disables the timeout; the connection will be closed only when the remote device closes it. Any other value sets the timeout in seconds. The connection will be closed if no messages are received in that time. This allows the controller to free unused connections. Valid timeout range is 0 to 4294967295 seconds. The default value is 250 seconds.
The Master Idle Timeout determines when connections to a slave controller are closed. Setting this value to zero disables the timeout; the connection will be closed only when your program closes it. Any other value sets the timeout in seconds. The connection will be closed if no messages are sent in that time. This allows the slave device to free unused connections. Valid timeout range is 0 to 4294967295 seconds. The default value is 10 seconds.
The TCP Port sets the port used by the DNP in TCP protocol. Valid port number range is 1 to 65534. The default value is 20000. Consult your network administrator to obtain a port if you are not using the default.
Realflo User and Reference Manual
May 19, 2011
368
DNP in UDP
Realflo Expert Mode Reference
The DNP in UDP property page is selected for editing by DNP in UDP in the tree control section of the IP Configuration dialog. When selected the DNP in UDP property page is active.
Friendly IP List
The Protocol selection selects whether the DNP in UDP protocol is enabled. If this option is enabled the controller supports DNP in UDP protocol. Disabling this option keeps the controller from processing DNP in
UDP protocol messages and sending DNP in UDP master messages. The default selection is disabled.
The UDP Port sets the port used by the DNP in UDP protocol. Valid port number range is 1 to 65534. The default value is 20000. Consult your network administrator to obtain a port if you are not using the default.
The Friendly IP property page is selected for editing by Friendly IP in the tree control section of the IP Configuration dialog.
Realflo User and Reference Manual
May 19, 2011
369
Realflo Expert Mode Reference
The Enable Friendly IP List checkbox enables or disables the friendly IP list. Check this box to accept messages from only the IP addresses in the list. Uncheck this to accept message from any IP address.
Select the Add button to enter a new row in the Friendly IP list. Selecting the Add button opens the Add Friendly IP address dialog. The button is disabled if the Enable Friendly IP List control is not checked. The button is disabled if the table is full. Up to 32 entries can be added to the table.
Select the Edit button to edit range in the Friendly IP list. Selecting the Edit button opens the Edit Friendly IP address dialog. The button is disabled if the Enable Friendly IP List control is not checked.
The Delete button removes the selected rows from the list. This button is disabled if there are no entries in the list. The button is disabled if the
Enable Friendly IP List control is not checked.
Click on the column headings to sort the list by that column. Click a second time to reverse the sort order. The order is indicated by the triangle next to the text.
The settings are verified when the OK button is pressed or another settings page is selected.
A message is displayed if the friendly IP list is enabled and the list is empty.
A message is displayed if the IP address of the PC is not in the friendly
IP table.
Add Friendly IP Address Range Dialog
The Add Friendly IP Address Range dialog specifies an IP address range to add to the Friendly IP list.
Realflo User and Reference Manual
May 19, 2011
370
FTP
Realflo Expert Mode Reference
Start Address specifies the starting IP address in the range. Enter any valid
IP address.
End Address specifies the ending IP address in the range. Enter a valid IP address that is numerically greater than or equal to the IP Start Address.
This field can be left blank if only a single IP address is required.
The OK button adds the IP address range to the list and closes the dialog. A message is displayed if the address range is invalid.
The Cancel button closes the dialog without making any changes.
When the FTP tree control is selected the FTP property page becomes active allowing for the configuration of the FTP server on the controller.
FTP Server enables the FTP server in the controller. There are three selections available.
Select Disabled to disable the FTP server and stop FTP access to the file system
Select Login Required to enable the FTP server. A username and password are required to access the file system.
Select Anonymous Allowed to enable the FTP server. A username and password may be used to access the file system. The server will accept an anonymous login; it will accept any username and password.
Realflo User and Reference Manual
May 19, 2011
371
FTP Practices
Realflo Expert Mode Reference
Username specifies the username for the FTP server account. It is used when Login Required is selected. Enter a User Name of 1 to 16 characters long.
Password specifies the password for the FTP server account. It is used when Login Required is selected. Enter a password of 1 to 16 characters long.
Verify Password specifies the password a second time to confirm the value. Enter the same value as for the password.
The setftp function can be used to enable and disable the FTP server using program logic in the controller.
FTP Server functions operate at a high priority in the controller. The execution of Telepace and IEC 61131-3 logic applications is impacted during file uploads and downloads. The logic applications will slow significantly during large file uploads to the controller.
To reduce the impact on logic applications:
Use a number of small files rather than a single large file.
Use the LS (list) command rather than the DIR (directory) command.
FTP usernames and passwords are transmitted in the clear when reading/writing controller configuration. In order to minimize the possibility of reading of credentials the controller should be kept locked against programming commands except when the configuration is being read or written.
These practices should be followed to maximize the effectiveness of the
FTP feature.
Binary vs ASCII Mode
Files can be transferred via either Binary or ASCII modes. Binary file transfers are recommended because they are more efficient. FTP clients will support both types of file transfers.
File Locations
The internal file system on the SCADAPack 330/334/350/357 controllers may use either of two available drives:
The internal Controller Disk Drive is labeled /d0.
The External USB Drive is labeled /bd0.
The internal file system on the SCADAPack 314 and SCADAPack 4203 controllers has one drive:
The internal Controller Disk Drive is labeled /d0.
The controller internal flash drive d0 contains all system and user files. The system files should not be modified via FTP or user processes.
Many system files can be found in the d0/SYSTEM folder. It is strongly recommended that only system files reside in this folder to prevent accidental corruption of controller settings.
C programs can be found in the root directory d0. These programs have a suffix of “.out” and should not be modified.
Realflo User and Reference Manual
May 19, 2011
372
Realflo Expert Mode Reference
Log files created by the data log to file functionality are stored in sub-folders of d0/LOGS/. These files may be read, but writing to or deleting these files is discouraged. The data log to file functionality will manage these files as required.
Users are encouraged to create their own folders and store all files that they need to access in folders they create to minimize accidentally altering a system file. i.e. create a directory called d0/SCADA to keep files that will be modified via FTP in.
Register Assignment
The Register Assignment command is used to configure the register assignment for flow computers using Telepace firmware. When selected the command opens the Register assignment dialog and displays the current register assignment list. The user may edit the list or the entries in the list.
This feature is available only on Telepace firmware. The settings have no effect on ISaGRAF firmware.
For complete information on the Register Assignment modules available refer to the Telepace Studio User and Reference manual.
Realflo uses the following registers for flow calculation data. These registers cannot be used in any register assignment.
Configuration and Control Registers
Requested Data Registers
Meter Run 1 Data Registers
Meter Run 2 Data Registers
Meter Run 3 Data Registers
Requested Daily History Registers
Meter Run 4 Data Registers
Meter Run 5 Data Registers
Meter Run 6 Data Registers
Meter Run 7 Data Registers
Meter Run 8 Data Registers
Meter Run 9 Data Registers
Meter Run 10 Data Registers
MVT Configuration Registers
MVT Data Registers
MVT Internal Registers
49500 to 49999
48500 to 49499.
47500 to 48499
46500 to 47499
45500 to 46499
44500 to 45499.
44400 to 44499
44300 to 44399
44200 to 44299
44100 to 44199
44000 to 44099
43900 to 43999
43800 to 43899
43700 to 43799
43600 to 43689
38000 to 38999
Display Configuration Registers
Process I/O Configuration Registers
43470 to 43499
43400 to 43469
Uncorrected Accumulated Flow, runs 1 to 10 43300 to 43398
SolarPack Configuration / Accumulation
43180 to 43260
In addition to the above registers the SCADAPack 4202 and 4203 controllers use the following registers for transmitter parameters and data.
These registers cannot be used in any register assignment if a SCADAPack
4202 or 4203 controller is used.
SCADAPack 4202 and 4203 data and parameters registers
40001 to
40499
Realflo User and Reference Manual
May 19, 2011
373
Realflo Expert Mode Reference
The main portion of the dialog is a list showing the modules in the register assignment list. The module list displays the Module, Module Address, Start
Register, End Register and the number of Registers for the module.
The Module field displays the type and name of I/O modules that have been added to the Register Assignment. For modules that support more than one type of I/O, there are multiple lines in the row of the table, one for each input or output I/O type.
The Address field displays the unique module address of the physical hardware, such as a 5000 5401 Digital I/O module. Some module types have no address that can be set by the user. The address is blank for these modules.
The Start Register field displays the first register address in the I/O database where the module data is stored. A start register is required for each type of input or output on the module.
The End Register field displays the last address in the I/O database used by the module. An end register is required for each type of input or output on the module.
The Registers field displays the number of registers used by the module. A size is required for each type of input or output on the module.
The OK button updates the register assignment list and closes the dialog.
This is the default button. Pressing the ENTER key selects the OK button.
The Cancel button exits the dialog without saving changes. If changes were made, the user is prompted for confirmation before exiting. Pressing the
ESC key selects the Cancel button. If changes were made the following dialog appears.
Realflo User and Reference Manual
May 19, 2011
374
Realflo Expert Mode Reference
Selecting Yes closes the Register Assignment dialog and the register assignment list is not changed.
Selecting No returns to the Register Assignment dialog. The No button is the default selection. Pressing the Enter or ESC keys selects the No button.
The Add button adds a new module to the register assignment. The Edit
Register Assignment dialog opens.
The Add Copy button adds a copy of the selected module to the register assignment. The Edit Register Assignment dialog opens. The Address field is set to the first unused address for the currently selected module type.
Other fields are set to the values from the currently selected I/O module.
The Add Copy button is grayed if the table is empty, or I/O modules of the given type are in use (i.e. modules are already defined for possible addresses for the selected module type).
The Edit button modifies the selected module. The Edit Register
Assignment dialog opens with data from the currently selected I/O module.
The Edit button is grayed if the table is empty, or no module is selected in the table.
The Delete function removes the selected module from the register assignment. The button is grayed if the table is empty, or no module is selected in the table.
The Default button replaces the current Register Assignment with the
Default Register Assignment for the controller. The controller type is selected using the Flow Computer Setup command. The dialog displayed
is dependent on the type of controller used. See the
The I/O Module Error Indication check box determines if the controller displays I/O module communication errors. If enabled, the controller will blink the Status LED if there is an I/O error. See the DIAG Controller Status
Code diagnostic module for information on the controller status code. If disabled, the controller will not display the module communication status.
The module communication status is checked. This option controls only the indication on the Status LED.
Module Selection
Clicking anywhere in a row selects the module. Double clicking anywhere in a row selects the data for the module and invokes the Edit Register
Assignment dialog.
Sorting
Click on the column headings to sort the data. Clicking once sorts the data in ascending order. Clicking again sorts the data in descending order.
Realflo User and Reference Manual
May 19, 2011
375
Realflo Expert Mode Reference
If a module has more than one value in a column, data is sorted by the first value.
Edit Register Assignment Dialog
The Edit Register Assignment dialog modifies an entry in the register assignment. The following example shows the dialog editing a module with more than one I/O type.
The Module drop-down list box shows the current module type. The dropdown list displays available modules. Refer to the Telepace Studio
User and Reference manual for complete information on the Register
Assignment module types available.
The Address drop-down list box shows the current module address. The drop-down list displays addresses valid for the current module type that are not already used. If all addresses are in use, the list will be empty.
There are up to four type description fields. The text displays the type of the input or output register. The type descriptions are 0xxxx, 1xxxx, 3xxxx and
4xxxx.
Digital output data is read from coil (0xxxx) registers. The digital outputs are updated continuously with data read from the coil registers.
Digital input data is stored in status (1xxxx) registers. The status registers are updated continuously with data read from the digital inputs.
Analog input data is stored in input (3xxxx) registers. The input registers are updated continuously with data read from the analog inputs.
Analog output data is stored in holding (4xxxx) registers. The analog output registers are updated continuously with data read from the holding registers.
The Start edit box holds the starting register in the I/O database for the I/O type. The edit box allows any number to be entered.
The End field shows the last register used by the module for the I/O type.
The Registers field shows the number of registers in the I/O module.
The Description field displays the I/O type for multiple I/O modules.
Selecting OK checks the data entered. If the data is correct the dialog is closed and the Register Assignment dialog returns with the changes made.
An error message is displayed if any data is incorrect. Pressing the ENTER key selects the OK button.
Realflo User and Reference Manual
May 19, 2011
376
Realflo Expert Mode Reference
Selecting Cancel exits the dialog without saving changes. Pressing the ESC key selects the Cancel button.
Realflo User and Reference Manual
May 19, 2011
377
Realflo Expert Mode Reference
Default Register Assignments
SCADAPack 4202 or 4203
If the controller type is a SCADAPack 4202 or 4203 with controller board version 5 and terminal board version 6, the following dialog appears.
SCADAPack 4202 DR manufactured after July 13, 2004 may use the 4202
DS Extended I/O register assignment. The 4202-DR needs to have controller board version 5 and terminal board version 6. Previous versions of the SCADAPack 4202 DR require the 4202 DR I/O register assignment module.
If the controller type is a SCADAPack 4202 DS or 4203 DS the following dialog appears.
SCADAPack, SCADAPack Plus, SCADAPack 32
If the controller type is a SCADAPack, SCADAPack Plus, or SCADAPack 32 the default register assignment will include the supported integrated I/O modules for the controller. Clicking the Default button in the Register
Assignment opens a dialog displaying the supported integrated I/O modules.
SCADAPack 5601 I/O module
Realflo User and Reference Manual
May 19, 2011
378
SCADAPack 314
Realflo Expert Mode Reference
SCADAPack 5604 10V/40mA I/O module
SCADAPack 5604 5V/20mA I/O module
SCADAPack 5606 I/O module
If the controller type is a SCADAPack 314 the following dialog appears.
SCADAPack 330
If the controller type is a SCADAPack 330 the following dialog appears.
SCADAPack 334
If the controller type is a SCADAPack 334 the following dialog appears.
Realflo User and Reference Manual
May 19, 2011
379
Realflo Expert Mode Reference
SCADAPack 350
If the controller type is a SCADAPack 350 register assignment will include the supported integrated I/O modules for the controller. Clicking the Default button in the Register Assignment opens a dialog displaying the supported integrated I/O modules.
SCADAPack 350 10V/40mA I/O module
SCADAPack 350 5V/20mA I/O module
SCADAPack 357 Controller (SCADAPack 350 and SCADAPack 5607
I/O module).
DNP
The DNP command is used to configure the DNP protocol settings for the controller. When selected the DNP Settings window is opened.
For complete information on DNP configuration refer to the
section of this manual.
Store and Forward
The Store and Forward command configures the Store and Forward settings for a SCADAPack 32, SCADAPack 314/330/334, SCADAPack 350 controller or SolarPack 410. A controller configured for store and forward operation receives messages destined for a remote Slave Station on the
Slave Interface. The controller forwards the message on the Forward
Interface to the Forward Station.
Refer to the following diagram as a reference for the terminology used in the following Store and Forward command reference.
Realflo User and Reference Manual
May 19, 2011
380
Slave Interface
The Ethernet port is set for Modbus address 2. The local SCADAPack
32 will respond to messages received for address 2.
Messages that require forwarding cannot be addressed for station 2.
LAN
SCADAPack 32
Controller
Communication
Interfaces
COM1 COM2 COM4
Realflo Expert Mode Reference
Forward Interface
COM port 4 is set for Modbus address 2. The local SCADAPack
32 will respond to messages received for station 2. Messages that are forwarded cannot be addressed for station 2.
Message to be Forwarded
The message, from a remote master station, that is to be forwarded by the SCADAPack 32 controller.
The station address of the message needs to be in the Store and Forward table. In this example the station address cannot be 2.
Forwarded Message
The forwarded message, to the remote slave station, that is forwarded by the SCADAPack
32 controller.
The station address of the message needs to be in the Store and Forward table. In this example the station address cannot be 2.
When the Store and Forward command is selected the Store and Forward dialog appears. This dialog displays the Store and Forward table for the controller. This command is available only when the controller type is set to
SCADAPack 330/334, SCADAPack 350, SCADAPack 32, SCADAPack 32P or SolarPack 410.
The Store and Forward table displays each Store and Forward translation as a row, with column headings, in the table. The table may have up to 128 entries. A vertical scroll bar is used if the list exceeds the window size.
The Slave Interface heading displays the receiving slave interface the message is received from for each translation.
The Slave Station heading displays the Modbus station address of the slave message.
The Forward Interface heading displays the interface the message is forwarded from. When forwarding to a Modbus TCP or UDP network, the protocol type is selected for the Forward Interface. The IP Stack automatically determines the exact interface (e.g. LAN/PPP) to use when it searches the network for the Forward IP Address. If a serial port is selected for the Forward Interface, and the serial port is configured for PPP protocol, the message will not be forwarded.
The Forward Station heading displays the Modbus station address of the forwarded message.
Realflo User and Reference Manual
May 19, 2011
381
Realflo Expert Mode Reference
The Forward IP Address heading displays the IP address of the Forward
Station. This field is blank unless a TCP or UDP network is selected for
Forward Interface.
The Time Out heading displays the maximum time (in tenths of seconds) the forwarding task waits for a valid response from the Forward Station. The time out should be equal to or less than the time out set for the master message received on the Slave Interface.
The OK button saves the table data. No checking is done on the table data.
The Cancel button closes the dialog without saving changes.
Select the Add button to enter a new row in the store and forward table.
Selecting the Add button opens the Add/Edit Store and Forward dialog.
Select the Edit button to modify the selected row in the store and forward table. Selecting the Edit button opens the Add/Edit Store and Forward dialog containing the data from the selected row. This button is disabled if more than one row is selected. This button is disabled if there are no entries in the table.
The Delete button removes the selected rows from the table. This button is disabled if there are no entries in the table.
The Undo button undoes the action performed by the last button selection since the dialog was opened. This applies to the buttons Add, Edit, Delete and Undo. This button is disabled when the dialog is opened, and is enabled as soon as any of the applicable buttons are selected.
The Sorted by menu box lists each of the five column headings. The rows are sorted according to the selected heading. Headings in the table are, by default, sorted by the Slave Interface heading.
Add/Edit Store and Forward Dialog
This dialog is used to edit an entry or add a new entry in the store and forward table.
The Slave Interface is the receiving slave interface the message received from. The dropdown list allows the following selection:
com1
com2
com3
com4
Realflo User and Reference Manual
May 19, 2011
382
Realflo Expert Mode Reference
LAN/PPP
The Slave Station is the Modbus station address of the slave message.
This address needs to be different from the Modbus address assigned to the
Slave Interface. Valid range for Slave Station is:
1 to 255 when standard addressing is selected for the interface.
1 to 65534 when extended addressing is selected for the interface.
The Forward Interface is the interface the message is forwarded from. The dropdown list allows the following selection:
com1
com2
com3
com4
Modbus/TCP
Modbus RTU in UDP
Modbus ASCII in UDP
The Forward Station is the Modbus station address of the forwarded message. This address needs to be different from the Modbus address assigned to the Forward Interface. Valid range for Forward Station is:
1 to 255 when standard addressing is selected for the interface.
1 to 65534 when extended addressing is selected for the interface.
The Forward IP Address edit box is disabled and the address is forced to
“0.0.0.0“ whenever the Forward Interface is set to com1, com2, com3 or com4. The Forward IP Address edit box is enabled only when the Forward
Interface is set to a TCP or UDP network. Valid entries are 0 to 255 for each byte in the IP address.
The Time Out is the maximum time the forwarding task waits for a valid response from the Forward Station, in tenths of second. Valid entries are 0 to 65535. The time out should be equal to or less than the time out set for the master message received on the Slave Interface.
The OK button checks the data for this table entry. If the data is valid the dialog is closed. If the table data entered is invalid, a message is displayed and the dialog remains open. The table entry is invalid if any of the fields is out of range. The data is also invalid if it conflicts with another entry in the table. In PEMEX mode the OK button is not active if the user is not logged on with Administrator privileges.
The Cancel button closes the dialog without saving changes.
Power Management Configuration
The SolarPack 410 provides power management features to minimize the power consumption.
Power Management Dialog
The power management dialog appears as follows.
Realflo User and Reference Manual
May 19, 2011
383
Realflo Expert Mode Reference
The Continuous Wake Mode section specifies if the flow computer stays in the continuous power mode.
The following parameters can be configured for this mode.
Always Stay Awake specifies if the flow computer should stay awake.
Valid values are Yes and No. The default value is No.
Radio Power selects if the SCADA radio is powered. Valid values are
ON or OFF. The default value is ON.
Bluetooth Power selects if the Bluetooth radio is powered. Valid values are ON or OFF. The default value is ON.
Display selects if the display is powered. Valid values are ON or OFF.
The default value is ON.
Display Backlight selects if the display backlight is powered. Valid values are ON or OFF. The default value is ON. This control is set to
OFF when the display control is set to OFF.
The Enable Input Activation section specifies what happens when the enable input is activated. Activating the enable input places the flow computer in the continuous power mode. A power off timer starts when entering continuous power mode. The flow computer remains in this mode until the power off timer expires, then enters the power saving mode.
Realflo User and Reference Manual
May 19, 2011
384
Realflo Expert Mode Reference
The following parameters can be configured for this mode. These controls are disabled when the controller is in the continuous wake mode.
Stay Awake For specifies the number of minutes until power off. Valid values are 1 to 240. The default value is 10 minutes.
Radio Power selects if the SCADA radio is powered. Valid values are
ON or OFF. The default value is OFF.
Bluetooth Power selects if the Bluetooth radio is powered. Valid values are ON or OFF. The default value is ON.
Display selects if the display is powered. Valid values are ON or OFF.
The default value is ON.
Display Backlight selects if the display backlight is powered. Valid values are ON or OFF. The default value is OFF. This control is set to
ON when the display control is set to ON.
The Scheduled Wake Mode section specifies when the flow computer should wake up. The flow computer stays awake for a fixed period of time in this mode. The controller is in the continuous power mode for the specified duration at the specified times, then it enters the power saving mode.
The following parameters can be configured for this mode. These controls are disabled when the controller is in the continuous wake mode.
Times to Wake lists the times at which the flow computer should wake. Up to 24 times can be added. The default value is an empty list.
Stay Awake For specifies the number of minutes until power off. Valid values are 1 to 240. The default value is 20 minutes.
Radio Power selects if the SCADA radio is powered. Valid values are ON or OFF. The default value is OFF.
Bluetooth Power selects if the Bluetooth radio is powered. Valid values are
ON or OFF. The default value is OFF.
Display selects if the display is powered. Valid values are ON or OFF. The default value is OFF.
Display Backlight selects if the display backlight is powered. Valid values are ON or OFF. The default value is OFF This control is set to ON when the display control is set to ON.
Selecting Power Management Configuration
In Expert mode do one of the following:
Select the Power Management command on the Configuration menu to open the Power Management configuration dialog.
Double-click the Power Management item in the configuration tree to open the Power Management configuration dialog.
In Maintenance mode:
Select View and Change Configuration.
Advance to the Edit Configuration page.
Double-click the Power Management item in the configuration tree.
Realflo User and Reference Manual
May 19, 2011
385
Realflo Expert Mode Reference
Communication
The power management settings are written to the flow computer with the flow computer configuration. The settings are read from the flow computer with the flow computer configuration.
Pulse Input Configuration
The SolarPack 410 flow computer can accumulate pulse inputs. The flow computer counts the number of pulses, multiplies by a K factor and accumulates the results. Total volume, today‟s volume, yesterday‟s volume, this month‟s volume, and last month‟s volume accumulators are provided.
Pulse Input Configuration Dialog
The Pulse Input Configuration dialog appears as follows.
Selecting Pulse Input Configuration
Select the Pulse Input command on the Configuration menu to open the
Pulse Input configuration dialog.
Double-click on the Pulse Input item in the configuration tree to open the
Pulse Input configuration dialog.
Communication
Units specify the units for volume. Valid values are cubic feet (ft metres (m
3
3
) and cubic
), litres, and US gallons, barrels (42 US gallons). The default value is cubic feet.
K Factor specifies the factor by which the raw count is divided to obtain the volume. Valid values are any number greater than 0. The default value is
1.0. Units are pulses/volume.
The Pulse Input settings are written to the flow computer with the flow computer configuration. The settings are read from the flow computer with the flow computer configuration.
Changes to settings can generate up to three events in the event log for run
1.
Number Description
10096 Set pulse input K factor
10097 Set pulse input units
Gas Sampler Output Configuration
The gas sampler output is pulsed based on the current flow. The pulse rate is configurable with a factor based on the current volume. The pulse width is user adjustable from 0.1 seconds to 5.0 seconds.
Realflo User and Reference Manual
May 19, 2011
386
Realflo Expert Mode Reference
Gas Sampler Output Dialog
The Gas Sampler Output dialog appears as follows.
Selecting Gas Sampler Output Configuration
Select the Gas Sampler Output command on the Configuration menu to open the Gas Sampler Output configuration dialog.
Double-click on the Gas Sampler Output item in the configuration tree to open the Gas Sampler Output configuration dialog.
Communication
Volume/Pulse specifies the flow volume for each pulse output. The measurement units are the same as the contract units for run 1. Any positive value is valid. The default value is 1,000,000 ft
3
/pulse or the equivalent in the current unit set.
Pulse Width specifies the pulse width. Valid values are 0.1 to 5.0 seconds in increments of 0.1 seconds. The default value is 1.0 seconds.
The Gas Sampler Output settings are written to the flow computer with the flow computer configuration. The settings are read from the flow computer with the flow computer configuration.
Realflo User and Reference Manual
May 19, 2011
387
Realflo Expert Mode Reference
Modbus Mapping
Modbus mapping provides a simplified method for SCADA host software to make configuration changes to the gas quality ratios, orifice plate size and the real time clock settings in the flow computer. Using Modbus mapping a sequential block of registers containing the gas quality ratios and orifice plate size for a meter run can be written to the flow computer and applied to the flow computer configuration in one Modbus write from the SCADA host.
The Modbus Mapping table cannot be modified unless the user is logged on with Administrator privileges. The OK button is grayed out in the Modbus
Mapping Settings dialog if the account privileges are not at the ADMIN level.
See the Accounts section for information on creating and using accounts in
Realflo.
If an attempt is made to write a Realflo configuration that contains a Modbus
Mapping table that is different from the one in the flow computer by a user without Administration privileges a message is displayed and the Modbus
Mapping table is not written to the flow computer.
Modbus mapping may be applied to the following flow computer configurations:
The Real Time Clock Registers table requires a sequential block of 9
holding registers. These registers are described in the Real Time Clock
The Shared Read/Write Run Registers table requires a sequential block of 63 holding registers. These registers can be used to read or write to the AGA8 gas composition parameters and the orifice plate size
for any meter run. These registers are described in the Shared
Read/Write Run Data Registers section below.
The Run Read/Write Registers table requires a sequential block of 62 holding registers. These registers can be used to read or write to the
AGA8 gas composition parameters and the orifice plate size for the selected meter run. The number of meter runs displayed depends on the number of meter runs configured in the flow computer. These
registers are described in the Meter Run Data Registers section below.
The Run Read Only Registers table requires a sequential block of 60 input registers. These registers can be used to read the AGA8 gas composition parameters and the orifice plate size for the selected meter run. The number of meter runs displayed depends on the number of meter runs configured in the flow computer. These registers are
described in the Meter Run Data Registers section below.
The Modbus mapping table operates according to the following rules:
The flow computer reads the registers, for each configured run, from the mapping table on each scan. Verification is done and the status of the current mapping table is reported via the Configuration Mapping
Range status register for each table.
Only valid new settings are used to update the flow computer configuration when the Apply Request register is set to 1. The Apply
Request register is reset to zero after the request is executed.
A Timer restricts incomplete configuration settings from staying in the
Modbus mapping table forever. If changes have not been applied in a specified number minutes (default is 10 minutes), since the last change,
Realflo User and Reference Manual
May 19, 2011
388
Realflo Expert Mode Reference the mapping table is synchronized with the current flow computer settings and user mapping changes will be lost.
The Modbus Mapping registers may be set to a user defined range. The mapping table is initialized with the current flow computer configuration when the mapping range changed.
The Mapping Table registers are automatically updated when any flow computer interface (i.e. Realflo) changes the AGA-8, AGA-8 Hexanes+,
AGA-3 or Real Time Clock configuration.
The Configuration Mapping Range status register indicates the status of the Mapping Range for each configuration. A Host computer can use this register to know if other flow computer interface is updating the same configuration.
When the Modbus Mapping command is selected the Modbus Mapping
Settings dialog opens as shown below.
The Modbus mapping dialog is divided into three columns and a number of rows depending on the number of meter runs configured in the flow computer. The rows in the table list the flow computer configurations that can be assigned to Modbus Mapping.
The Real Time Clock Registers are a sequential block of 9 holding registers. The block of registers used cannot include any registers used by
the flow computer. See the TeleBUS Registers Used by the Flow
Computer section for a listing of flow computer registers.
The Shared Read/Write Run Registers are a sequential block of 63 holding registers. These registers can be used to read or write to the AGA8 gas composition parameters and the orifice plate size for any meter run. The block of registers used cannot include any registers used by the flow
computer. See the TeleBUS Registers Used by the Flow Computer
section for a listing of flow computer registers.
The Run Read/Write Registers are a sequential block of 62 holding registers. These registers can be used to read or write to the AGA8 gas composition parameters and the orifice plate size for the selected meter run.
The block of registers used cannot include any registers used by the flow
Realflo User and Reference Manual
May 19, 2011
389
Realflo Expert Mode Reference
computer. See the TeleBUS Registers Used by the Flow Computer
section for a listing of flow computer registers.
The Run Read Only Registers are a sequential block of 60 input registers.
These registers can be used to read the AGA8 gas composition parameters and the orifice plate size for the selected meter run. The block of registers used cannot include any registers used by the flow computer. See the
TeleBUS Registers Used by the Flow Computer section for a listing of
flow computer registers.
Using the Modbus Mapping Settings Table
The mapping for each configuration is enabled or disabled by clicking your mouse in the box to the left of each configuration type.
The Shared Read/Write Run Registers and the individual meter run
Read/Write Registers mapping cannot be enabled at the same time.
The Shared Read/Write Run Registers and the individual meter run
Read Only Registers mapping may be enabled at the same time.
The Real Time Clock Registers maybe used with any mapping selection.
The Modbus Mapping table uses the default Start Register and End
Register values unless the Start Register is changed. When the Start
Register is changed the End Register automatically updates to the end of the configuration range. To change the Start Register:
Click on the Start Register Modbus register.
Press the keyboard Enter key to open the window for editing.
Enter the new Start Register Modbus address and press the Enter key again.
The Modbus registers used for Modbus Mapping cannot include any
registers used by the flow computer. See the TeleBUS Registers Used by
the Flow Computer section for a listing of flow computer registers.
The Timer Interval selection is used to apply a timeout value for pending changes to a configuration table. If changes have not been applied in a specified number minutes (default is 10 minutes), since the last change, the mapping table is synchronized with the current flow computer settings and user mapping changes will be lost. The default timer interval value is 10 minutes. Any values between 1 and 1000 minutes may be entered.
The Only check for range errors when closing dialog selection is used to limit range validation errors when configuring the mapping table. Each range is validated and needs to not overlap with another range or conflict with registers used by the flow computer. Using this control the validation will only be checked when the dialog is closed.
Real Time Clock Registers
The Real Time Clock Registers are a sequential block of 9 holding registers. The block of registers used cannot include any registers used by the flow computer. The following table describes the registers. The default registers are described, when the register range is changed the registers are offset from the entered Start Register.
To write a complete Real Time Clock configuration from a Host:
Realflo User and Reference Manual
May 19, 2011
390
Realflo Expert Mode Reference
Enter the Real Time Clock values into the range of registers and enter a
1 into the Apply Request register.
Write the registers to the flow computer.
Read the Configuration Mapping Range status register to confirm the changes have been made in the flow computer
To write an incomplete Real Time Clock configuration from a Host (i.e. change the hour only):
Enter a value of 100 in the Apply Request register to read the current flow computer settings and write this register to the flow computer.
Enter the selected new Real Time Clock values into the appropriate register(s) and enter a 1 into the Apply Request register.
Write the registers to the flow computer.
Read the Configuration Mapping Range status register to confirm the changes have been made in the flow computer
Description
Years = 1997 to 2096
Months = 1 to 12
Days = 1 to 31, with exceptions
Hours = 0 to 23
Minutes = 0 to 59
Read/Write
Register
Range
42550
42551
42552
42553
42554
Seconds = 0 to 59
Seconds = -32000 to 32000, Increment /
Decrement number of seconds
Apply Request
42555
42556
42557
0 =
1 =
No operation
Apply new setting
100 = Synchronize with Flow Computer
Configuration Mapping Range status
0 = Reset and Synchronized with
Flow Computer by Apply Request
42558 commands 1 and 100.
1 = Settings have changed.
2 =
3 =
The current settings are invalid.
Reset and Synchronized with
Flow computer as a result of a timeout.
4 = The event log is full and no further change events are allowed.
5 = Invalid command
Register
Type
uint uint uint uint uint uint sint uint uint
Shared Read/Write Run Data Registers
The Shared Read/Write Run Registers are a sequential block of 63 holding registers. These registers can be used to read or write to the AGA8 gas composition parameters and the orifice plate size for any meter run. The following table describes the registers. The default registers are described, when the register range is changed the registers are offset from the entered
Start Register.
To write a complete Run Configuration from a Host:
Realflo User and Reference Manual
May 19, 2011
391
Realflo Expert Mode Reference
Enter the meter run number in the Meter Run register.
Enter the Run Configuration values into the range of registers and enter a 1 into the Apply Request register.
Write the registers to the flow computer.
Read the Configuration Mapping Range status register to confirm the changes have been made in the flow computer
To write an incomplete Run Configuration from a Host (i.e. change the orifice plate size only):
Enter the meter run in the Meter Run register.
Enter a value of 100 in the Apply Request register to read the current flow computer settings and write this register to the flow computer.
Enter the selected new Run Configuration values into the appropriate register(s) and enter a 1 into the Apply Request register.
Write the registers to the flow computer.
Read the Configuration Mapping Range status register to confirm the changes have been made in the flow computer.
Description
Shared Run Data Registers
Meter Run = 1 to 10
Methane
Nitrogen
Carbon Dioxide
Ethane
Propane
Water
Hydrogen Sulfide
Hydrogen
Carbon Monoxide
Oxygen iButane nButane iPentane nPentane
Hexane and higher components may be measured individually or may be combined.
This affects the n-Hexane, n-Heptane, n-
Octane, n-Nonane, and n-Decane components. See the Hexanes+ register for details.
The following registers are used when the
Hexane and higher components are used.
n-Hexane
This register contains the n-Hexane value when individual components are
Default
Read/Write
Register
Range
42480 to
42542
42480
42481
42483
42485
42487
42489
42491
42493
42495
42497
42499
42501
42503
42505
42507
Register
Type
float float float float float float float uint float float float float float float float
42509 float
Realflo User and Reference Manual
May 19, 2011
392
Realflo Expert Mode Reference
Description Default
Read/Write
Register
Range
Register
Type
selected.
The register contains the total
Hexanes+ when combined components are selected.
See the Hexanes+ register description. n-Heptane n-Octane n-Nonane
Helium n-Decane
Argon
Composition logging control
This register selects if the flow computer logs
AGA-8 gas composition changes. Frequent changes to the composition will result in the event log filling with gas composition events.
When the log is full, further changes cannot be made until Realflo reads the log.
0 = log composition changes
1 = do not log composition changes
Real Relative Gas Density
0 = calculate live value
A non-zero value will be interpreted by the flow computer as the Real Relative Density. This value will be used with the Heating value register. Valid range for value 0 to 1800
BTU(60)/ft3.
Heating Value
0 = calculate live value
A non-zero value will be interpreted by the flow computer as the Heating Value. This value will be used with the Real Relative Density register. Valid range for value 0.07 to 1.52
Hexanes +
The AGA-8 Hexanes+ configuration registers define the composition of the heavier gas components being measured. There are two options, individual components (selected above) or combined (selected below). The
Hexanes+ register below determines which method is used. n-Hexane portion
This register defines the percentage of the
Hexanes+ contributed by n-Hexane. n-Heptane portion
This register defines the percentage of the
Hexanes+ contributed by n- Heptane. n-Octane portion
This register defines the percentage of the
42511
42513
42515
42517
42519
42521
42522
42524
42526
42528
42530
42532 float float float float float float uint float float float float float
Realflo User and Reference Manual
May 19, 2011
393
Realflo Expert Mode Reference
Description Default
Read/Write
Register
Range
Register
Type
Hexanes+ contributed by n- Octane. n-Nonane portion
This register defines the percentage of the
Hexanes+ contributed by n- Nonane. n-Decane portion
This register defines the percentage of the
Hexanes+ contributed by n- Decane.
The Hexanes+ register determines how the
Hexanes+ values are entered.
0 = Use individual gas components
(default)
When 0 is entered for the register the
Hexane+ registers are entered using registers for n- Hexane, n-Heptane, n-Octane, n-
Nonane and n-Decane listed above (registers
42509 to 42518).
1 = Use combined value for hexane and higher components.
When 1 is entered (use registers 42528 to
42537) the portion of the Hexanes+ ratio that is applied to each of the n- Hexane, n-
Heptane, n-Octane, n-Nonane and n-Decane gas components. These portions are represented as a percentage of the gas components being measured i.e. 0 to 100%.
The total of the Hexanes+ components needs to add to 100 percent.
Orifice diameter
Apply Request
0 =
1 =
No operation
Apply new setting
100 = Synchronize with Flow Computer
Configuration Mapping Range status
0 = Reset and Synchronized with Flow
Computer by Apply Request commands 1 and
100.
1 = Settings have changed.
2 = The current settings are invalid.
3 = Reset and Synchronized with Flow computer as a result of a timeout.
4 = The event log is full and no further change events are allowed.
5 = Invalid command
42534
42536
42538
42539
42541
42542 float float uint float uint uint
Meter Run Data Registers
The Meter Run Registers Read/ Write Registers are a sequential block of
62 holding registers. These registers can be used to read or write to the
AGA8 gas composition parameters and the orifice plate size for the selected
Realflo User and Reference Manual
May 19, 2011
394
Realflo Expert Mode Reference meter run. The following table describes the registers. The default registers are described, when the register range is changed the registers are offset from the entered Start Register.
To write a complete Run Configuration from a Host:
Enter the Run Configuration values into the range of registers and enter a 1 into the Apply Request register.
Write the registers to the flow computer.
Read the Configuration Mapping Range status register to confirm the changes have been made in the flow computer
To write an incomplete Run Configuration from a Host (i.e. change the orifice plate size only):
Enter a value of 100 in the Apply Request register to read the current flow computer settings and write this register to the flow computer.
Enter the selected new Run Configuration values into the appropriate register(s) and enter a 1 into the Apply Request register.
Write the registers to the flow computer.
Read the Configuration Mapping Range status register to confirm the changes have been made in the flow computer.
Register
Type
Description Default
Read/Write
Register
Range
Meter Run 1 Data Registers
42559 to
42620
Methane
Nitrogen
42559
42561
Carbon Dioxide
Ethane
Propane
Water
42563
42565
42567
42569
Hydrogen Sulfide
Hydrogen
Carbon Monoxide
Oxygen iButane nButane iPentane nPentane
Hexane and higher components may be measured individually or may be combined. This affects the n-Hexane, n-Heptane, n-
Octane, n-Nonane, and n-
Decane components. See the Hexanes+ register for details.
42571
42573
42575
42577
42579
42581
42583
42585
The following registers are used when the Hexane and
Default
Read
Register
Range
39200 to
39259
39200
39202
39204
39206
39208
39210
39212
39214
39216
39218
39220
39222
39224
39226 float float float float float float float float float float float float float float
Realflo User and Reference Manual
May 19, 2011
395
Description
higher components are used.
n-Hexane
This register contains the n-Hexane value when individual components are selected.
The register contains the total Hexanes+ when combined components are selected.
See the Hexanes+ register description. n-Heptane n-Octane
Helium
Argon n-Nonane n-Decane
Composition logging control
This register selects if the flow computer logs AGA-8 gas composition changes.
Frequent changes to the composition will result in the event log filling with gas composition events. When the log is full, further changes cannot be made until Realflo reads the log.
0 = log composition changes
1 = do not log composition changes
Real Relative Gas Density
0 = calculate live value
A non-zero value will be interpreted by the flow computer as the Real
Relative Density. This value will be used with the Heating value register. Valid range for value is 0.07 to 1.52.
Heating Value
0 = calculate live value
A non-zero value will be interpreted by the flow computer as the Heating
Value. This value will be used with the Real Relative
42587
42589
42591
42593
42595
42597
42599
42601
42602
42604
Realflo Expert Mode Reference
Default
Read/Write
Register
Range
Default
Read
Register
Range
39228
39230
39232
39234
39236
39238
39240
39242
39243
39245
Register
Type
float float float float float float float uint float float
Realflo User and Reference Manual
May 19, 2011
396
Description
Realflo Expert Mode Reference
Default
Read/Write
Register
Range
Density register. Valid range for value is 0 to 1800
BTU(60)/ft3
Hexanes +
The AGA-8 Hexanes+ configuration registers define the composition of the heavier gas components being measured. There are two options, individual components (selected above) or combined (selected below). See the Hexanes+ register below. n-Hexane portion
This register defines the percentage of the Hexanes+ contributed by n-Hexane. n-Heptane portion
This register defines the percentage of the Hexanes+ contributed by n- Heptane. n-Octane portion
This register defines the percentage of the Hexanes+ contributed by n- Octane. n-Nonane portion
This register defines the percentage of the Hexanes+ contributed by n- Nonane. n-Decane portion
This register defines the percentage of the Hexanes+ contributed by n- Decane.
The Hexanes+ register determines how the
Hexanes+ values are entered.
0 = Use individual gas components (default)
When 0 is entered for the register the Hexane+ registers are entered using registers for n- Hexane, n-
Heptane, n-Octane, n-
Nonane and n-Decane listed above (registers 42587 to
42600).
1 = Use combined value for hexane and higher
42606
42608
42610
42612
42614
42616
Default
Read
Register
Range
39247
39249
39251
39253
39255
39257
Register
Type
float float float float float uint
Realflo User and Reference Manual
May 19, 2011
397
Description Default
Read/Write
Register
Range
components.
When 1 is entered (registers
42606 to 42615)the portion of the Hexanes+ ratio that is applied to each of the n-
Hexane, n-Heptane, n-
Octane, n-Nonane and n-
Decane gas components.
These portions are represented as a percentage of the gas components being measured i.e. 0 to 100%.
The total of the Hexanes+ components needs to add to
100 percent.
Orifice diameter
Apply Request
0 = No operation
1 = Apply new setting
100 = Synchronize with
Flow Computer
Configuration Mapping
Range status
0 = Reset and
Synchronized with Flow
Computer by Apply Request commands 1 and 100.
1 = Settings have changed.
2 = The current settings are invalid.
3 = Reset and
Synchronized with Flow computer as a result of a timeout.
4 = The event log is full and no further change events are allowed.
5 = Invalid command
Meter Run 2 Data Registers
See meter run 1 details.
Meter Run 3 Data Registers
See meter run 1 details.
Meter Run 4 Data Registers
See meter run 1 details.
Meter Run 5 Data Registers
See meter run 1 details.
Meter Run 6 Data Registers
See meter run 1 details.
Meter Run 7 Data Registers
See meter run 1 details.
42617
42619
42620
42621 to
42682
42683 to
42744
42745 to
42806
42807 to
42868
42869 to
42930
42931 to
42992
Realflo Expert Mode Reference
Default
Read
Register
Range
39258
N/A
N/A
39260 to
39319
39320 to
39379
39380 to
39439
39440 to
39499
39500 to
39559
39560 to
39619
Register
Type
float uint uint
Realflo User and Reference Manual
May 19, 2011
398
Description
Meter Run 8 Data Registers
See meter run 1 details.
Meter Run 9 Data Registers
See meter run 1 details.
Meter Run 10 Data Registers
See meter run 1 details.
Realflo Expert Mode Reference
Default
Read/Write
Register
Range
42993 to
43054
43055 to
43116
43117 to
43178
Default
Read
Register
Range
39620 to
39679
39680 to
39739
39740 to
39799
Register
Type
Read Configuration
The Read Configuration command is used to read all or selected parts of the Flow Computer Configuration. When selected the command displays the
Read Flow Computer Configuration dialog as shown below.
The All Configuration radio button, when selected, results in the reading of all configuration data from the flow computer.
The Selected Configuration radio button enables specific configuration data to be read from the flow computer.
Select Communication and I/O Settings to read the serial port and register assignment configuration information.
Select Flow Run and MVT Configuration to read the flow run configuration and the MVT transmitter configuration.
Select Process I/O Configuration to read the Process I/O configuration.
Click on the OK button to read the selected items from the flow computer.
Click the Cancel button to cancel the operation and close the dialog.
The Flow Computer ID is checked before reading. If the Flow Computer ID does not match the ID in the dialog Realflo displays the following message.
Realflo User and Reference Manual
May 19, 2011
399
Realflo Expert Mode Reference
Write Configuration
The Write Configuration command is used to write all or selected parts of the Flow Computer Configuration. When selected the command displays the
Write Flow Computer Configuration dialog as shown below.
The All Configuration radio button, when selected, results in the writing of all configuration data from the flow computer.
The Selected Configuration radio button enables specific configuration data to be written to the flow computer.
Select Communication and I/O Settings to write the serial port, register assignment configuration information and mapping table.
Select Flow Run and MVT Configuration to write the flow run configuration and the MVT transmitter configuration.
Select Process I/O Configuration to write the Process I/O configuration.
Click on the OK button to write the selected items to the flow computer.
Click the Cancel button to cancel the operation and close the dialog.
The Flow Computer ID is checked before writing. If the Flow Computer
ID does not match the ID in the dialog Realflo displays a message.
An error occurs if Controller Configuration is selected and the flow computer type is different from the flow computer type selected in the
Controller Type dialog. A message is displayed.
Realflo User and Reference Manual
May 19, 2011
400
Edit Script
Realflo Expert Mode Reference
In Flow Computer versions 6.73 and older, when AGA-8 gas ratios or NX-19 gas quality values are written to the flow computer the new gas ratios are updated in the Proposed registers. The Actual registers are not updated until a new Density calculation is started with the new values. The new values are not available to SCADA host software reading the Actual registers until a until a new Density calculation is started with the new values.
In Flow Computer versions 6.74 and newer when AGA-8 gas ratios or NX-
19 gas quality values are written to the flow computer the new gas ratios are updated in the Proposed registers and in the Actual registers. This allows a
SCADA host to immediately confirm the new values were written to the flow computer. The new gas values are not used by the flow computer until a new density calculation is started.
Use this command to edit Realflo script commands. Scripts are text files that contain a list of Realflo commands. The script files can be executed either manually, (under direct control of the user) or automatically, (under control of another program).
The Edit Script command opens the Edit Script dialog.
This command edits and saves script files that can be accessed by Realflo applications. The script file is not related to the currently open Realflo application. The script command line determines which Realflo application executes which script file.
The Edit Script dialog consists of the currently opened script file name, a list of commands configured in the opened script, script configuration command buttons and Edit Script dialog command buttons.
The currently opened script file name displays the file name of the currently opened script file. The format is X:\….…\file name.aut, where X is the disk drive letter assignment, \……\ is the subdirectory or subdirectories where the script file is located, file name is the script file name and .aut is the file name extension.
Realflo User and Reference Manual
May 19, 2011
401
Realflo Expert Mode Reference
In the above example the opened script file is called Meter1 Script
File.aut and is located in the C:\Program Files\Realflo subfolder.
When the Edit Script command is selected, a script file is not yet open. The file name is displayed as [untitled file] in this case.
The configured command list displays the commands that have be configured for the open script file. These commands are configured with the
Add and Edit commands and are executed in the order that they appear in the command list. Listed commands may be acted upon by selecting the particular command, with the cursor, and then executing one of the script configuration commands.
The script configuration commands are used to configure the script file.
The Add command opens the Edit Script Command dialog for the configuring of a new script command.
The Script command field displays the currently selected script command as determined by the Command field.
The Commands dropdown menu displays the list of available commands for selection. Selecting the arrow icon with the cursor will make these commands visible for selecting. For commands the Run dropdown menu selects the meter run for the command. The commands are:
Update Readings Once. Use this command to update the Current
Readings once from the flow computer for the selected Run.
Read Event Logs. Use this command to read the event log for the selected Run. The Option selection allows for All events or New events.
Read Alarm Logs. Use this command to read the alarm log for the selected Run. The Option selection allows for All alarms or New alarms.
Read Hourly History. Use this command to read the hourly history for the selected Run. The Option selection allows for All hourly history or for a selected Period.
Read Daily History. Use this command to read the daily history for the selected Run. The Option selection allows for All daily history or for a selected Period.
Export Readings. Use this command to export the Current Readings data in the flow computer to a CSV file. Name of CSV file is: <Realflo
file name> - TFR< Run Number > <(Run ID)>.CSV
Export Event Logs. Use this command to export the Event Log data in the flow computer to a CSV file. The Option selection allows for All
Realflo User and Reference Manual
May 19, 2011
402
Realflo Expert Mode Reference alarms or for a selected Period. Name of CSV file is: <Realflo file
name> - TFE< Run Number > <(Run ID)>.CSV
Export Alarm Logs. Use this command to export the Alarm Log data, for the selected Run, from the flow computer to a CSV file. The Option selection allows for All alarms or for a selected Period. The CSV file name is: <Realflo file name>-TFA<Run Number>.CSV
Export Hourly History. Use this command to export the Hourly History data, for the selected Run, from the flow computer to a CSV file. The
Option selection allows for All alarms or for a selected Period. The CSV file name is: <Realflo file name> - TFH<Run Number> <(Run ID)>.CSV
Export Daily History. Use this command to export the Daily History data, for the selected Run, from the flow computer to a CSV file. The
Option selection allows for All alarms or for a selected Period. The CSV file name is: <Realflo file name> - TFD<Run Number> <(Run ID)>.CSV
Export Specific CFX. Use this command to export configuration, current readings, alarm log, event log and hourly history in the flow computer to a CFX file. Data are exported to a single file for each run.
The Option selection allows for All events, alarms and logs or for a selected Period. The name of the CFX file is
<Realflo file name>(<FC ID>) - <Run Number> (<Run ID>).CFX.
Export Dated CFX. Use this command to export configuration, current readings, alarm log, event log and hourly history in the flow computer to a CFX file. Each day's data is exported to a separate file. The file name is based on the time and date according to the CFX standard
(YYYYMMDD.CFX). The Option selection allows for All events, alarms and logs or for a selected Period. Files for each run are saved to a folder. The name of the folder is
<Realflo file name>(<FC ID>) - <Run Number> (<Run ID>).CFX.
Read Flow Run Configuration. Use this command to read the Flow
Run Configuration for the selected Run. The Option selection allows for
All runs to be read.
Export Flow Run Configuration. Use this command to export the Flow
Run Configuration, for the selected Run, from the flow computer to a
CSV file. The Option selection allows for All runs. The CSV file name is:
<Realflo file name> - TFC<Run Number> <(Run ID)>.CSV
Save. Use this command to save the Realflo application files.
Exit. Use this command to close Realflo.
The Option dropdown menu is used to define the limits of some of the commands. The selections available depend on the command selected.
The All selection specifies all the data for a command.
The New selection specifies only new alarms and events for the Read
Events and Read Alarms commands.
The Period selection specifies a From and To period of data for the command. For hourly data the From entry is the oldest hour and the To entry is the newest hour. For daily data the From entry is the oldest contract day and the To entry is the newest contract day. For either entry 0 is the current hour or contract day, 1 is the previous hour or contract day, etc.
Realflo User and Reference Manual
May 19, 2011
403
Realflo Expert Mode Reference
The OK button retains the settings for the current script command and closes the Edit Script Command dialog.
The Cancel button discards any new changes to the current script command and closes the Edit Script Command dialog.
The Help button displays help for the dialog.
The Edit button opens the Edit Script Command dialog to edit the currently selected command. This command will appear in both the Script command and Command fields in the Edit Script Command dialog. See the Add command for details on the Edit Script Command dialog. This command is grayed if the command list is empty.
The Delete button removes the currently selected command from the command list. This command is grayed if the command list is empty.
The Delete All button removes all commands from the command list. This command is grayed if the command list is empty.
The Move Up button moves the currently selected command up one position in the command list. This command is grayed if the command list is empty or if top command in the list is selected.
The Move Down button moves the currently selected command down one position in the command list. This command is grayed if the command list is empty or if the bottom command in the list is selected.
The edit script dialog commands are used to manage the script files for editing.
The Close button closes the Edit Script dialog. If a script file has been configured but not yet saved, a dialog will appear prompting the user to save the changes to a script file. The Save As dialog is displayed. (see the Save
As command section for more information).
The New button is used to create a new script. If changes have been made to the current script you will be asked if you wish to save the changes first.
Once the changes have been saved, or not, the Edit Script dialog is opened.
The Open button opens an existing script file for editing. If the current command list has not yet been saved to a script file, a dialog will appear prompting the user to save the changes to a script file. When the Open command is used the Open dialog is displayed. The following options allow the user to specify which file to open.
The Look in: box lists the available folders and files.
The File name: box allows you to type or select the file name you want to open. This box lists files with the script file extension “aut”.
The Files of type: box displays the only type of file that this command can open: Realflo script files, with the file extension “aut”.
The Open command opens the script file that is displayed in the File
name: box and closes the Open dialog. The commands contained in the script file are displayed in the command list.
The Cancel command cancels the Open command and closes the
Open dialog.
The Save button saves the currently open script file. This command is grayed if the script file has not been saved using the Save As command.
Realflo User and Reference Manual
May 19, 2011
404
Run Script
Realflo Expert Mode Reference
The Save As button saves the current command list to either an existing or new script file. This command is grayed if the command list is empty.
The Save As dialog is displayed with the following options to allow the user to specify the script file name.
The Save in: box lists the available folders and files.
The File name: box allows you to type or select the file name you want to save.
The Save as type: box displays the only type of file that this command can save: Realflo script file, with the file extension “aut”.
The Save command saves the current command list to the script file specified in the File name: box and closes the Save dialog.
The Cancel command cancels the Save As command and closes the
Save As dialog.
Realflo 6.70 files are compatible with files saved using earlier versions of
Realflo.
The Help button displays help for the dialog.
The Run Script command enables the user to manually execute Realflo script files. This command is disabled if the Update Readings command is enabled. The Run Script command opens the Run Script dialog.
Enter the Realflo script file name and path in the Full Path of the Script
File window or select the Browse button and find the Realflo script file.
Once a Realflo script file is entered in the Full Path of the Script File window the View button opens the View Script window. The View Script window displays the Realflo script commands.
Check the Do Not Wait for User Input to run the script without input from the user. The script will run without displaying dialog boxes to the user. This is equivalent to running a script in the No Window mode from the command line.
The OK button closes the Run Script dialog and executes the script file.
The Cancel button closes the Run Script dialog without executing the script file.
The Help button displays help for the dialog.
Log Results
The Log Results command allows the user to set if the results of the script command execution is logged or not. When the Log Results menu is checked, the results of the script-enabled Realflo operations will be written into a log file. The results are saved in a text file as Realflo file name.LOG.
Realflo User and Reference Manual
May 19, 2011
405
Realflo Expert Mode Reference
The log information consists of three parts as follows:
Time stamp Operation Result
The Time stamp indicates the date and time at the end of the operation.
The date is recorded using the short date format defined in the Control
Panel. The time is recorded using the time format defined in the Control
Panel.
The Operation indicates the script command that was executed.
The Result indicates the normal result or error message.
For example,
2001/05/28 15:20:30
– Update Readings
2001/05/28 15:20:30 -- Read Event Logs Run1
– 5 Events added, cancelled
2001/05/28 15:20:30 -- Read Alarm Logs Run2
– Error: Controller did not respond
2001/05/28 15:20:30 -- Read Hourly History Run3
– 2 Hours added, Error:
Controller did not respond
Automatic Script Execution
Automatic script execution allows the user to configure other applications to execute the Realflo script command automatically. Direct user-operation of
Realflo is not necessary in this scenario. Realflo is completely run by another application.
Applications that would typically run a Realflo script file include HMI packages and custom interface applications. Refer to the HMI or application reference material for information on executing external programs.
Applications such as WindowsNT Scheduler enable tasks such as Realflo flow scripts to be executed on a timed basis. Refer to the Help files for your
PC operating system for more information.
To run the Realflo script automatically, a command line has to be configured in the user application. The command line is in following format:
Realflo configfile.tfc /s=scriptfile.aut /NoWindow where /NoWindow is an option.
If the command line doesn‟t include the /NoWindow option, a Realflo application window will be displayed during script execution. A communication dialog will allow user to cancel current operation at any time.
If the command line includes the /NoWindow option then the Realflo application window is not displayed during script execution. The user cannot cancel script execution before it is completed. The application will exit after finishing the last script command, regardless of whether the script file includes the Exit command.
Options
The options command provides for configuration options to be set when writing flow computer configuration. Currently one option, Check if flow computer upgrade is required, is selectable.
Realflo User and Reference Manual
May 19, 2011
406
Realflo Expert Mode Reference
Select Check if Flow Computer upgrade is required to enable tests of the flow computer version when writing flow computer configuration. Each time a configuration is written to the flow computer a check is made to see if the flow computer version is older than the version available in Realflo. This option is enabled by default.
The Historic Views options determine how historic views timestamps are displayed.
Timestamp selects if start times or end times are shown on historic records.
Select Show Start Time (time leads data) to show the start time of the record. This is supported on flow computer 6.70 and later. This is the default value for PEMEX installations.
Select Show End Time (time lags data) to show the end time of the record. This is the default setting for Standard and GOST installations.
Some Flow computers do not support Start Time timestamps. If you have chosen to show start times, and the start time data is not available, you can select what timestamps are shown. These selections are disabled if end times are selected above.
Select Show the start time anyway to show the start time even if there is no data. Dashes will show in the start time column.
Select Show the end time to automatically show the end time for the record.
Select Ask me what to do to have Realflo prompt you if start time data is not supported. This is the default selection.
The Restrict Realflo Users to reading all alarms and events option defines how alarms and events are acknowledged.
Selecting this option restricts all users to only reading all alarms or all events. Reading all alarms or all events does not acknowledge the alarms or events in the flow computer. Use this option to allow only the
Host system to acknowledge alarms and events. This is the default selection.
When this option Is not selected users with View, Read and Write Data and Administrator account privileges are able to Read New Events and
Realflo User and Reference Manual
May 19, 2011
407
Realflo Expert Mode Reference
Read New Alarms. Reading new events and alarms will result in the events and alarms being acknowledged in the flow computer when they are read using Realflo.
Click OK to save the settings.
Click Cancel to discard changes and close the dialog.
C/C++ Program Loader
The C/C++ Program Loader command provides for downloading multiple
C/C++ applications to a SCADAPack 314/330/334, SCADAPack 350 or
SCADAPack 4203 controller. Each downloaded program can be individually started, stopped, erased, and loaded.
This command is only available when the SCADAPack 314/330/334,
SCADAPack 350, SCADAPack 4203 hardware type is selected from the
Setup dialog. The command is greyed out for other hardware types.
When C/C++ Program Loader command is selected, the controller type is polled by Realflo. If the controller type is a SCADAPack 314/330/334,
SCADAPack 350, SCADAPack 4203then the C/C++ Program Loader dialog is displayed as shown below.
The dialog displays the C/C++ Programs that are loaded in the SCADAPack
314/330/334, SCADAPack 350, SCADAPack 4203 controller. The status of each program is indicated as Running or Stopped.
The Close button closes the dialog.
The Add button writes a new C/C++ program to the controller. Selecting the
Add button opens the Add C/C++ Program dialog.
Only one flow computer program may be added to the C/C++ Programs list.
The Run, Stop and Delete buttons apply to the C/C++ Program selected from the list of loaded C/C++ programs. Only one C/C++ Program may be selected from the list at one time. These buttons are disabled when there are no C/C++ Programs loaded.
The Run button stops and restarts the selected C/C++ program in the controller.
The Stop button stops the selected C/C++ program in the controller.
Realflo User and Reference Manual
May 19, 2011
408
Realflo Expert Mode Reference
The Delete button stops and erases the selected C/C++ program in the controller. However, if the current selected file is a flow computer, the following error message dialog will be displayed.
The Refresh button refreshes the list of loaded programs and their status.
Click on the column headings to sort the list by that column. Click a second time to reverse the sort order.
Add C/C++ Program Dialog
The Add C++ Program dialog writes a C/C++ Program to the controller.
Only one flow computer program may be added to the C/C++ Programs list.
Accounts
File Name specifies the C/C++ Program to write to controller. The file name may be selected in a number of ways.
Click on the Browse button to open a standard file open dialog.
Use the drop-down menu to select the file from a list of previously written files.
Type the path and file name directly into the edit box.
The Write button writes the selected file to the controller. The communication progress dialog box displays information about the write in progress, and allows you to cancel the write. If the file name is loaded already a prompt to replace the file or cancel is displayed.
When using DNP communication between Realflo and the target controller the DNP Application Layer timeout may need to be increased if a large
C/C++ application is added. The default Application Layer timeout of 5 seconds may not be long enough.
The Cancel button exits the dialog without writing to the controller.
The Accounts command in Realflo defines the security settings for Realflo and access to flow computers. The account information is stored both in
Realflo and the flow computer. One user account, the ADMIN account, is automatically created. Up to 99 additional user accounts may be created.
Realflo User and Reference Manual
May 19, 2011
409
Realflo Expert Mode Reference
When a new flow computer file is created, one Administrator level account is created with no PIN. Until the PIN is set or additional accounts are created,
Realflo will automatically log on to this account.
The user account name and security level are displayed in the Status Bar of the Realflo display.
Account Information
Each Realflo account consists of the following information.
Item Description
User ID
8 characters string identifying the account
Limits
maximum
PIN
PIN used to access flow computer range 1 to 65535
Access level functions user has access to one of:
view and read data
view, read data, and configure flow computer
administrator (all of above plus administration of accounts)
Integer in
Account information is stored in the flow computer configuration file. PINs are encrypted.
The user needs to log on to an account when a flow computer file is opened.
If the account settings are not changed, then security is effectively disabled.
For security when accounts are created the default ADMIN account should be deleted and the changes written to the flow computer. This allows that only with accounts can access the flow computer.
When the Accounts command is selected the Accounts dialog is displayed as shown below.
The Accounts dialog has the following controls.
The Accounts list box displays the user ID for each defined account. The users IDs are listed in alphabetic order.
Realflo User and Reference Manual
May 19, 2011
410
Realflo Expert Mode Reference
The Close button accepts the changes and closes the dialog. If the account that was active when the dialog was opened has been deleted, the user is logged off.
The Add button opens the Add/Edit Account dialog. The button is grayed if the maximum number of accounts is reached.
The Edit button opens the Add/Edit Account dialog. Fields in the dialog are set to the values for the currently selected account in the Accounts list box. This button is grayed if no account is selected.
The Delete button removes the currently selected account in the Accounts list box. This button is grayed if the account selected is the last
Administrator level account.
The Write button writes the accounts to the flow computer. To write account information to the flow computer, a user needs to be logged on to an
Administrator level account that has a corresponding account enabled on the flow computer. This button is grayed until accounts are read from the flow computer using the Read button.
The Read button reads accounts from the flow computer. To read account information from the flow computer, a user needs to be logged on to an
Administrator level account that has a corresponding account enabled on the flow computer. Account PINs are not stored in the flow computer.
Reading an account from the flow computer that does not already exist in
Realflo will result in an account with a blank PIN.
The flow computer ID is checked when accounts are written to or read from the flow computer. If the flow computer ID does not match the ID in the dialog Realflo displays the message “ The Flow Computer ID from the flow computer does not match the Flow Computer ID from the file.”
The Help button displays the help for this dialog.
Add/Edit Account Dialog
The Add/Edit Account dialog edits information for an account. This dialog pops up when New or Edit is selected in the Accounts dialog. It has the following controls.
Realflo User and Reference Manual
May 19, 2011
411
Realflo Expert Mode Reference
The User ID edit-box lists the user ID for the account. Any combination of letters and numbers up to eight characters in length is permitted. User IDs are case sensitive. For example the user ID “ADMIN” is different from
“admin”. A corresponding User Number (used by the flow computer) is assigned to each user ID, in increasing order. The ADMIN account is User
Number 1).
The PIN edit box contains the flow computer PIN for the account. This needs to be a number in the range 0 to 65535. The data in this field is masked with asterisks so it cannot be viewed.
The Confirm PIN edit box contains a second copy of the flow computer PIN for the account. This needs to be a number in the range 0 to 65535. The data in this field is masked with asterisks so it cannot be viewed.
The Access Level dropdown list contains the access level for the account.
View and read data level users can view data in Realflo and read new data from the flow computer. Users can also view any Custom Views assigned this security level. They cannot change the configuration, start or stop the calculations, set the clock, perform calibration or replace the flow computer program.
View, read and write data level users can view data in Realflo, read new data from the flow computer, change the configuration, start or stop the calculations, set the clock and perform calibration. Users can also view and write initial values for any Custom Views assigned this security level. Users with this access level cannot create or edit Accounts or replace the flow computer program. In PEMEX mode user at this level cannot make any changes to the communication settings, Process I/O, Sensor configuration or Store and Forward settings.
Administrator level users can perform the above functions plus administration of accounts. Users can also view, edit and write initial values for any Custom Views assigned this security level. Users with this access level can create or edit Accounts or replace the flow computer program.
The OK button accepts the entries and closes the dialog. The PIN and
Confirm PIN fields need to match or a message is shown. Correct the values and press OK again.
The Cancel button discards the changes and closes the dialog.
The Help button displays the help for this dialog.
Account PINs are not stored in the flow computer. Reading an account from the flow computer that does not already exist in Realflo will result in an account with a blank PIN.
Lock Flow Computer
Locking a flow computer stops unauthorized access. Commands sent to the flow computer when it is locked will be rejected. A flow computer that is unlocked operates without restriction.
The Lock Flow Computer dialog specifies a password to be used to lock the controller and the commands that are locked.
Realflo User and Reference Manual
May 19, 2011
412
Realflo Expert Mode Reference
Enter a password in the Password edit box. Re-enter the password in the
Verify Password edit box. Any character string up to eight characters in length may be entered. Typing in these edit boxes is masked. An asterisk is shown for each character typed.
The Prevent radio buttons select the commands that are locked.
Locking the programming commands prevents modifying or viewing the program in the controller. Communication protocols can read and write the I/O database.
Locking programming and database write commands prevents modifying or viewing the program and prevents writing to the I/O database. Communication protocols can read data from the I/O database, but cannot modify any data.
Locking programming and database commands prevents modifying or viewing the program and prevents reading and writing the I/O database.
Communication protocols cannot read or write the I/O database.
The OK button verifies the passwords are the same and sends the lock controller command to the controller. The dialog is closed. If the passwords are not the same an error message is displayed. Control returns to the dialog.
The Cancel button closes the dialog without any action.
If the controller is already locked, a message indicating this is shown instead of the dialog.
Unlock Flow Computer
The Unlock Flow Computer dialog prompts the user for a password to be used to unlock the flow computer. If the flow computer is locked, the following dialog is displayed.
Enter the password that was used to lock the flow computer in the
Password edit box. Typing in this edit box is masked. An asterisk is shown for each character typed.
The Cancel button closes the dialog without any action.
Realflo User and Reference Manual
May 19, 2011
413
Realflo Expert Mode Reference
The OK button sends the Unlock Flow Computer command to the controller.
If the password is correct the flow computer will be unlocked. If the password is not correct, the flow computer will remain locked.
If you forget the controller password, the Override Flow Computer Lock command can be used to unlock the controller. It will erase programs in the controller.
Override Flow Computer Lock
The Override Flow Computer Lock dialog allows the user to unlock a flow computer without knowing the password. This can be used in the event that that the password is forgotten.
To stop unauthorized access to the information in the flow computer, the C and Logic programs are erased.
Selecting the Override Flow Computer Lock command displays the following dialog.
The Yes button unlocks the flow computer and erases programs.
The No button closes the dialog without any action.
Show Lock Status
The Show Lock Status command displays the flow computer lock state.
It opens a dialog showing one of the following states:
unlocked
locked against programming commands
locked against programming commands and database write
locked against programming commands and database read/write
The OK button closes the dialog.
Realflo User and Reference Manual
May 19, 2011
414
Realflo Expert Mode Reference
Maintenance Menu
Log On
Use this command to log on to an account. This command is disabled if the
Update Readings command is enabled. You need to enter the PIN for the account. This command is not available if there are no accounts created.
The Log On dialog has the following controls.
Enter the user ID in the User name edit box.
Enter the PIN number in the PIN edit box. Text entered in this edit box is masked (i.e. asterisks are printed instead of the text).
Click on OK button to accept the account name and PIN. If the PIN is correct, the user is given access. Otherwise the file is opened, but the user has no access to any data.
The Cancel button closes the dialog. No changes are made.
Read Logs/History
Use this command to update the history and event logs with information from the controller. This command is disabled if the Update Readings command is enabled. The Read Logs/History command opens the Read
Logs From Controller dialog.
The flow computer ID is checked when the Read Logs/History command is selected. If the flow computer ID does not match the ID in the dialog Realflo displays the message “ The Flow Computer ID from the flow computer does not match the Flow Computer ID from the file
.”
Realflo User and Reference Manual
May 19, 2011
415
Realflo Expert Mode Reference
The Flow Run Range group of controls determines if data for all runs or for a single run is read.
The All Runs radio button selects reading data for all runs.
The Selected Run radio button selects reading from a single run. The drop-down list selects the run to be read.
The Log Range group of controls determines what data is read. The controls apply to all runs selected using the Setup command.
The Event Log check box selects if the event log is read.
The Read All Events radio button selects the reading of all events in the controller. The control is grayed if the Event Log control is not selected.
Select Just Read New Events to read unacknowledged events in the flow computer. If the operator has View, Read and Write Data or
Administrator authorization then the events will be acknowledged after reading the new events. If the events in the log are not acknowledged, the event log will fill with 700 events. Operator activity will be prevented until the events are read and acknowledged. The control is grayed under the following conditions: o The event log is not selected.
Realflo User and Reference Manual
May 19, 2011
416
Realflo Expert Mode Reference o The user has Read and View account privileges. o The Restrict Realflo users to reading all alarms and events option is selected in the Expert Mode Options menu.
The Alarm Log check box selects if the alarm log is read.
Select Just Read New Alarms to read unacknowledged alarms in the flow computer. If the operator has View, Read and Write Data or
Administrator authorization then the alarms will be acknowledged after reading the new events. If the events in the log are not acknowledged, the alarm log will fill with 300 events. Operator activity will be prevented until the alarms are read and acknowledged. The control is grayed under the following conditions: o The alarm log is not selected. o The user has Read and View account privileges. o The Restrict Realflo users to reading all alarms and events option is selected in the Expert Mode Options menu.
The Hourly History check box selects if the hourly history is read.
The All Days radio button selects reading hourly history for all days stored in the controller.
The Selected Days radio button selects reading hourly history for the range of days selected with the From and to drop-down lists. All records are read for the contract days whose first hour is within the date range.
All records for the contract day are read, regardless of their calendar date. This may result in records with calendar days outside the range being added to the log. For example, if the contract day is configured to start at 7:00 AM. Reading hourly history for September 23 would return all the records where the first record in a day was between 7:00 on the
23 rd
to 6:59:59 AM on the 24 th
.
The Daily History check box selects if the daily history is read.
The All Days radio button selects reading hourly history for all days stored in the controller.
The Selected Days radio button selects reading hourly history for the range of days selected with the From and to drop-down lists. All records are read for the contract days whose first record is within the date range. All records for the contract day are read, regardless of their calendar date. This may result in records with calendar days outside the range being added to the log. For example, if the contract day is configured to start at 7:00 AM. Reading daily history for September 23 would return all the daily records whose end time is in the range 7:00 on the 23 rd
to 6:59:59 AM on the 24 th
.
The From controls contain the oldest previous day for which the hourly or daily history is to be read. The initial value is 35 days before the current day.
The control is enabled when the Hourly History or Daily History checkbox is checked and the Selected Days radio button is selected. Change this date to avoid reading data that has previously been read into the log.
The to controls contain the recent previous day for which the hourly or daily history is to be read. The initial value is the current day. The allowed range is the same or greater than the value in the From control. The control is enabled when the Hourly History or Daily History checkbox is checked
Realflo User and Reference Manual
May 19, 2011
417
Realflo Expert Mode Reference and the Selected Days radio button is selected. Change this date when wanting to read older data only. Leaving this date at its default will result in the recent data being read.
The dates are formatted using the short date style from the Date page of the Regional Settings in the Control Panel.
The OK button reads the selected logs from the controller. If no log is selected, the dialog is closed with no further action.
The Cancel button closes the dialog.
The Help button invokes the Help engine and displays the help page for this dialog.
Calibration
Use this command to calibrate the temperature sensor, static pressure sensor, and differential pressure sensor or pulse counter input. This command is disabled if the Update Readings command is enabled. The calibration dialogs lead you through the calibration procedure.
When more than one sensor is selected, they are forced and then the calibration cycle will be allowed for each sensor in turn. This allows multiple variable transmitters such as the MVT to be calibrated.
The flow computer ID is checked when the calibration command is selected.
If the flow computer ID does not match the ID in the dialog Realflo displays the message “ The Flow Computer ID from the flow computer does not match the Flow Computer ID from the file.”
WARNING
The same input sensor can be used for more than one flow run. When the sensor is calibrated for one run, Realflo only forces the input value for that run. When the sensor is disconnected to do the calibration, the live input to the other run will be disconnected and the value will not be correct. The flow computer does not support forcing of inputs during calibration on more than one run.
Inputs from an MVT may be used by more than one run. The flow computer supports calibration of an MVT that has inputs used by multiple flow runs.
After the run is selected, the configuration for the run is read from the flow computer. The calibration selection page for the run is then displayed.
Connections for SCADAPack Sensor Calibration
It should be noted that when an Absolute (Static) Pressure calibration is performed the bypass or cross feed valve on the manifold needs to be open.
When performing a Differential Pressure calibration the bypass valve needs to be closed.
Differential Pressure Calibration Connections
Realflo User and Reference Manual
May 19, 2011
418
Absolute Pressure Calibration Connections
Realflo Expert Mode Reference
Realflo User and Reference Manual
May 19, 2011
419
Realflo Expert Mode Reference
Sensor Calibration
When the Calibration command is selected the Sensor Calibration dialog is displayed. The Run, or Sensor transmitter, to be calibrated is selected from this dialog.
The Sensor Calibration dialog allows the selection meter run or MVT for calibration.
Select the Run radio button and then select a meter run to calibrate.
Transmitters used for the meter run may be calibrated. This section is disabled if runs are using MVT transmitters.
Select Sensor radio button and select one of the MVT tags to calibrate a
MVT transmitter. The MVT tags that have been configured will be in MVT selection box.
Sensor Calibration Procedure .
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log.
The back button is not enabled on the first step since there is no previous step.
The Next> button starts the calibration procedure. After the Run, or MVT, is selected, the configuration for the run is read from the flow computer. The
Run, or MVT, calibration page for the run is then displayed.
The Cancel button closes the dialog and stops the transmitter calibration.
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
Realflo User and Reference Manual
May 19, 2011
420
Realflo Expert Mode Reference
WARNING
Realflo uses live values from the sensor when calibration is cancelled. Be sure to connect all sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Realflo User and Reference Manual
May 19, 2011
421
Realflo Expert Mode Reference
Run Calibration Procedure
When the Run radio button is selected the Run Calibration dialog is displayed. The transmitters for the run are selected for calibration from this dialog.
Realflo uses live values from the sensor when calibration is cancelled, connect all sensors first.
WARNING
The same input sensor can be used for more than one flow run. When the sensor is calibrated for one run, Realflo only forces the input value for that run. When the sensor is disconnected to do the calibration, the live input to the other run will be disconnected and the value will not be correct. The flow computer does not support forcing of inputs during calibration on more than one run.
Select the sensors to be calibrated by checking the appropriate boxes. More than one sensor may be selected for calibration.
The <Back button is not enabled as this is the initial step.
The Next> button completes the selections and opens the Step 1: Force
Value dialog.
The Cancel button closes the dialog and stops the transmitter calibration.
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
Realflo User and Reference Manual
May 19, 2011
422
Realflo Expert Mode Reference
WARNING
Realflo uses live values from the sensor when calibration is cancelled. Be sure to connect all sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Calibration Step 1: Force Value
The flow calculations continue to execute while calibrating sensors. The sensor value needs to be forced to either the current value or a fixed value during calibration. This dialog lets you select the current value of the input or a fixed value of your choice.
If a sensor was forced before starting the execution of a calibration, the sensor will remain in a forced state after the calibration process is completed or even if the calibration process is cancelled before completion.
Realflo User and Reference Manual
May 19, 2011
423
Realflo Expert Mode Reference
When more than one sensor is selected, they each need to be forced to a current or fixed value before any of the other steps are performed. A Step 1:
Force Value dialog will be presented for each sensor selected for calibration.
The input register associated with this input is displayed to aid you in determining which input you are calibrating.
Check the Current Value radio button to use the current value for the sensor.
Check the Fixed Value radio button and enter a value to use for the calibration in the entry box.
The No Change radio button will be selected if the value is currently forced. (You may still select one of the other two radio buttons if desired).
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log.
When the Next> button is pressed Realflo records the start of calibration for the sensor in the event log. The sensor input is forced. The sensor may now be disconnected from the process.
The Cancel button closes the dialog and stops the transmitter calibration.
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
Realflo User and Reference Manual
May 19, 2011
424
Realflo Expert Mode Reference
WARNING
Realflo uses live values from the sensor when calibration is cancelled. Be sure to connect all sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Calibration Step 2: Record As Found Values
As-found readings indicate how the sensor was calibrated before adjustment. These can be used to correct flow measurement errors resulting from an out of calibration sensor. Follow the procedure your company has set for taking as-found readings. You need to record at least one as-found reading.
To take as-found readings:
Apply a known signal to the sensor, or measure the signal applied to the sensor with a calibrated instrument.
Enter the applied value in the Applied Value edit box.
Realflo User and Reference Manual
May 19, 2011
425
Realflo Expert Mode Reference
The measured value from the process is shown in the Measured Value box. When it has settled, click on the Record button to record an asfound reading.
Repeat the process to record additional readings.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For Run Calibration the deviation is calculated as follows. The output full scale and zero scale are taken from the input configuration for the run. span = input full scale – input zero scale deviation = (measured - applied) / span
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log.
The Next> button proceeds to the next step.
The Cancel button is greyed and an as found reading needs to be recorded.
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
WARNING
Realflo uses live values from the sensor when calibration is cancelled. Be sure to connect all sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Calibration Step 3: Calibration Required
Realflo User and Reference Manual
May 19, 2011
426
Realflo Expert Mode Reference
The as-found readings indicate if calibration is required. Examine the list of as-found readings. If the sensor is in need of calibration, select Yes.
Otherwise select No.
Realflo User and Reference Manual
May 19, 2011
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For Run Calibration the deviation is calculated as follows. The output full scale and zero scale are taken from the input configuration for the run. span = input full scale – input zero scale deviation = (measured - applied) / span
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log.
The Next> button proceeds to the next step.
The Cancel button is greyed and an as found reading needs to be recorded.
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
427
Realflo Expert Mode Reference
WARNING
Realflo uses live values from the sensor when calibration is cancelled. Be sure to connect all sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Calibration Step 4: Calibrate Sensor
This dialog aids you in calibrating a sensor by displaying the measured value from the sensor and the as-found readings.
Follow the procedure your company or the sensor supplier has set to calibrate the sensor. When the sensor calibration is complete, you may wish to check the as-left measurements that will be recorded in the next step.
This confirms that you have calibrated the sensor correctly before placing it back in service.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For Run Calibration the deviation is calculated as follows. The output full scale and zero scale are taken from the input configuration for the run. span = input full scale – input zero scale deviation = (measured - applied) / span
Click on the Next> button when the calibration is complete.
Calibration Step 5: Record As Left Values
Realflo User and Reference Manual
May 19, 2011
428
Realflo Expert Mode Reference
As-left readings indicate how the sensor was calibrated. These can be used to verify sensor calibration. Follow the procedure your company has set for taking as-left readings. You need to record at least one as-left reading.
To take as-left readings:
Apply a known signal to the sensor, or measure the signal applied to the sensor with a calibrated instrument.
Enter the applied value in the Applied Value edit box.
The measured value from the process is shown. When it has settled, click on the Record button to record an as-left reading.
Repeat the process to record additional readings.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For Run Calibration the deviation is calculated as follows. The output full scale and zero scale are taken from the input configuration for the run. span = input full scale – input zero scale deviation = (measured - applied) / span
When required readings are taken, click on the Next> button.
Calibration Step 6: Restore Live Input
The sensors need to be reconnected to the process and the input hardware before calibration is complete. Reconnect sensors and verify connections are correct.
Realflo User and Reference Manual
May 19, 2011
429
Realflo Expert Mode Reference
Click on the Next button when the sensor is connected.
WARNING
Realflo uses live values from the sensor when calibration is cancelled. Be sure to connect all sensors first.
Realflo User and Reference Manual
May 19, 2011
430
Realflo Expert Mode Reference
Calibration Step 7: Calibration Report Comment
Realflo creates, stores, and prints calibration reports for each calibration session performed. Comments may be added to the calibration report using the Calibration Report Comment dialog as shown below.
Enter any comments or leave the window blank.
Click the Next button when completed entering comments.
Calibration Step 8: Calibration Report
The Calibration Report dialog allows the saving of the calibration report.
Select Save Report to File to save the report. o Type the name of the report in the Save Report to File window.
The default location and name are specified on the Calibration
Report Options dialog. o Select Browse to select a different file name.
Realflo User and Reference Manual
May 19, 2011
431
Realflo Expert Mode Reference o Check View Calibration Report After Saving the File to view the saved calibration report file. Default is checked. o Select Do not Save Report to skip saving the calibration report. o Click the Finis button to complete the calibration process.
If selected the Calibration report will be displayed as shown below.
Realflo User and Reference Manual
May 19, 2011
432
Realflo Expert Mode Reference
Sensor Calibration Procedure
When the Sensor radio button is selected in the Sensor Calibration dialog the Sensor Calibration dialog is displayed.
The transmitter number, transmitter tag name, the communication port and the transmitter address associated with this transmitter are displayed to aid you in determining which input you are calibrating.
Check the Calibrate Temperature Sensor check box to select the temperature sensor for calibration. This will add the Temperature to the
Calibration order list box.
Check the Calibrate Static Pressure Sensor check box to select the static pressure sensor for calibration. This will add the Static Pressure to the Calibration order list box.
Check the Calibrate Differential Pressure Sensor check box to select the differential pressure sensor for calibration. This will add the Diff.
Pressure to the Calibration order list box.
The Calibration Order list displays the list of sensors to be calibrated.
Sensors are calibrated in order from the top of the list.
Select Move Up button to move the specified item in the list up. The button is disabled if highlight item is on the top of the list or the list is empty.
Select Move Down button to move the specified item in the list down.
The button is disabled if highlight item is on the bottom of the list or the list is empty.
The <Back button is not enabled as this is the initial step.
Realflo User and Reference Manual
May 19, 2011
433
Realflo Expert Mode Reference
The Next> button completes the selections and opens the Step 1: Force
Value dialog.
The Cancel button closes the dialog and stops the transmitter calibration.
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
WARNING
Realflo uses live values from the sensor when calibration is cancelled. Be sure to connect all sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Calibration Step 1: Force Value
The flow calculations continue to execute while calibrating sensors. The sensor value needs to be forced to either the current value or a fixed value during calibration. This dialog lets you select the current value of the input or a fixed value of your choice.
If a sensor was forced before starting the execution of a calibration, the sensor will remain in a forced state after the calibration process is completed or even if the calibration process is cancelled before completion.
Realflo User and Reference Manual
May 19, 2011
434
Realflo Expert Mode Reference
When more than one sensor is selected, they each need to be forced to a current or fixed value before any of the other steps are performed.
Select the value you wish to use, for each sensor, by clicking the appropriate radio button for each sensor.
Check the Current Value radio button to use the current value for the sensor.
Check the Fixed Value radio button and enter a value to use for the calibration in the entry box.
The No Change radio button will be selected if the value is currently forced. (Note: You may still select one of the other two radio buttons if desired).
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log.
When the Next> button is pressed Realflo records the start of calibration for the sensor in the event log. The sensor input is forced. The sensor can now be disconnected from the process.
The Cancel button closes the dialog and stops the transmitter calibration.
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
Realflo User and Reference Manual
May 19, 2011
435
Realflo Expert Mode Reference
WARNING
Realflo uses live values from the sensor when calibration is cancelled. Be sure to connect all sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Calibration Step 2: Record As- Found Values
As-found readings indicate how the sensor was calibrated before adjustment. These can be used to correct flow measurement errors resulting from an out of calibration sensor. Follow the procedure your company has set for taking as-found readings. You need to record at least one as-found reading.
Realflo will record As Found values to the units type selected for the meter run. If the units type for the meter run and the MVT are not the same then the MVT units are scaled to the meter run units.
To take as-found readings:
Realflo User and Reference Manual
May 19, 2011
436
Realflo Expert Mode Reference
Apply a known signal to the sensor, or measure the signal applied to the sensor with a calibrated instrument.
Enter the applied value in the Applied Value edit box.
The measured value from the process is shown in the Measured Value box. When it has settled, click on the Record button to record an asfound reading.
Repeat the process to record additional readings.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For Sensor Calibration the deviation is calculated as follows. The operating limits are read from the flow computer. span = upper range limit - lower range limit deviation = (measured - applied) / span
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log.
The Next> button proceeds to the next step.
The Cancel button is grayed and an as found reading needs to be recorded.
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
WARNING
Realflo uses live values from the sensor when calibration is cancelled. Be sure to connect all sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Calibration Step 3: Calibration Required
Realflo User and Reference Manual
May 19, 2011
437
Realflo Expert Mode Reference
The as-found readings indicate if calibration is required. Examine the list of as-found readings. If the sensor is in need of calibration, select Yes.
Otherwise select No.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For Run Calibration the deviation is calculated as follows. The output full scale and zero scale are taken from the input configuration for the run. span = input full scale – input zero scale deviation = (measured - applied) / span
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log.
The Next> button proceeds to the next step.
The Cancel button is grayed out and an
“as found reading” needs to be recorded.
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
Realflo User and Reference Manual
May 19, 2011
WARNING
438
Realflo Expert Mode Reference
Realflo uses live values from the sensor when calibration is cancelled. Be sure to connect all sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Calibration Step 4: Calibrate SCADAPack 4101, 4202 or 4203
Step four in the calibration procedure varies depending on the type of transmitter being calibrated. Use this section if you are calibrating a
SCADAPack 4101, 4202 or 4203 transmitter.
This dialog aids you in calibrating a sensor by displaying the measured value from the sensor and the as-found readings.
Follow the procedure your company or the sensor supplier has set to calibrate the sensor. When the sensor calibration is complete, you may wish to check the as-left measurements that will be recorded in the next step.
This confirms that you have calibrated the sensor correctly before placing it back in service.
The Static Pressure can only have a span calibration performed if at least
5% of the rated pressure is applied.
The RTD Zero can only be adjusted +/- 1% of the RTD upper limit, typically
8.5 degrees C, relative to the settings used when a reset sensor command was last issued.
The list box displays the as-found values listed in the list of Record As-
Found Values dialog.
The Measured Value displays the measured value from the sensor.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The
Realflo User and Reference Manual
May 19, 2011
439
Realflo Expert Mode Reference measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For MVT Calibration the deviation is calculated as follows. The operating limits are read from the flow computer. span = upper range limit - lower range limit deviation = (measured - applied) / span
Calibration Step 4: Calibrate SCADAPack 4101
Step four in the calibration procedure varies depending on the type of transmitter being calibrated. Use this section if you are calibrating a
SCADAPack 4101 transmitter.
The as-found readings, for each sensor, will indicate if calibration is required for the sensor. You are prompted to use the 4000 Configurator application to perform the calibration. The 4000 Configurator software is installed from the
Control Microsystems Hardware Documentation CD.
The Next> button proceeds to the next step.
The Help button displays the online help file.
Calibration Step 4: Calibrate 3095 Transmitter
Step four in the calibration procedure varies depending on the type of transmitter being calibrated. Use this section if you are calibrating a 3905 transmitter.
This dialog aids you in calibrating a sensor by displaying the measured value from the sensor and the as-found readings.
Follow the procedure your company or the sensor supplier has set to calibrate the sensor. When the sensor calibration is complete, you may wish to check the as-left measurements that will be recorded in the next step.
This confirms that you have calibrated the sensor correctly before placing it back in service.
Realflo User and Reference Manual
May 19, 2011
440
Realflo Expert Mode Reference
The list box displays the as-found values listed in the list of Record As-
Found Values dialog.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For Sensor Calibration the deviation is calculated as follows. The operating limits are read from the flow computer. span = upper range limit - lower range limit deviation = (measured - applied) / span
The Calibrate Sensor section of the Calibrate Sensor dialog displays the current calibration settings and selectable radio buttons for configuring the sensor calibration.
The Radio buttons enable the changing of the zero and span for the
Temperature, Static Pressure and Differential Pressure sensors. For
Temperature sensors, an additional radio button allows the user to fix the
Temperature value in the event the temperature reading is outside the configured limits.
Select the Re-Zero radio button to enable a new entry in the Applied
Value field. This field displays the current zero value. The button is labeled Re-Zero if the Re-Zero radio button is selected. Clicking the
Re-Zero button writes the zero applied value to the transmitter immediately.
Select the Calculate Span radio button to enable a new entry in the
Applied Value field. This field displays the current span value. The button is labeled Calibrate if the Calibrate Span radio button is selected. Clicking the Calibrate button writes the span applied value to the transmitter immediately.
When calibrating the temperature sensor you may select the Default
Temperature radio button to enable a new entry in the Applied Value field.
Realflo User and Reference Manual
May 19, 2011
441
Realflo Expert Mode Reference
The button is labeled Set if the Default Temperature radio button is selected. The transmitter returns the fixed temperature value if the RTD isnot working, or if the RTD is not connected. The valid range is
–40 to 1200
F or
–40 to 648.89
C. The default value is 60
F or 15.56
C. The new fixed temperature point is written to the transmitter immediately.
The Measured Value displays the measured value from the sensor.
Realflo records the points at which MVT calibration was performed in the event log.
Each time the Re-Zero button is clicked the following information is recorded.
Event Name
New Value
Previous Value
Target Re-zero Temperature
The applied value entered by the user
The measured value from the flow computer
Each time the Calibrate button is clicked the following information is recorded.
Event Name
New Value
Previous Value
Target Temperature Span
The applied value entered by the user
The measured value from the flow computer
Each time the Set Default button is clicked the following information is recorded.
Event Name
New Value
Previous Value
Set Default Temperature
The applied value entered by the user
The measured value from the flow computer
Calibration Step 4: Record As Left Values
As-left readings indicate how the sensor was calibrated. These can be used to verify sensor calibration. Follow the procedure your company has set for taking as-left readings. You need to record at least one as-left reading.
Realflo User and Reference Manual
May 19, 2011
442
Realflo Expert Mode Reference
Realflo will record the As Found values to the units type selected for the meter run. If the units type for the meter run and the transmitter are not the same then the transmitter units are scaled to the meter run units.
To take as-left readings:
Apply a known signal to the sensor, or measure the signal applied to the sensor with a calibrated instrument.
Enter the applied value in the Applied Value edit box.
The measured value from the process is shown. When it has settled, click on the Record button to record an as-left reading.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For Sensor Calibration the deviation is calculated as follows. The operating limits are read from the flow computer. span = upper range limit - lower range limit deviation = (measured - applied) / span
Repeat the process to record additional readings.
When the required readings are taken, click on the Next> button.
Calibration Step 5: Restore Live Input
The sensors need to be reconnected to the process and the input hardware before calibration is complete. Reconnect sensors and verify connections are correct.
Click on the Finish button when the sensor is connected.
WARNING
Realflo User and Reference Manual
May 19, 2011
443
Realflo Expert Mode Reference
The live value from all sensors is used as soon as the Finish button is clicked. Be sure to connect all sensors first.
Calibration Step 6: Calibration Report Comment
Realflo creates, stores, and prints calibration reports for each calibration session performed. Comments may be added to the calibration report using the Calibration Report Comment dialog as shown below.
Enter any comments or leave the window blank.
Click the Next button when completed entering comments.
Calibration Step 7: Calibration Report
Realflo User and Reference Manual
May 19, 2011
444
Realflo Expert Mode Reference
The Calibration Report dialog allows the saving of the calibration report.
Realflo User and Reference Manual
May 19, 2011
Select Save Report to File to save the report.
Type the name of the report in the Save Report to File window. The default location and name are specified on the Calibration Report
Options dialog.
Select Browse to select a different file name.
Check View Calibration Report After Saving the File to view the saved calibration report file. Default is checked.
Select Do not Save Report to skip saving the calibration report.
Click the Finis button to complete the calibration process.
If selected the Calibration report will be displayed as shown below.
445
Realflo Expert Mode Reference
Recovering From a PC Crash During Calibration
If power to the PC is disconnected or another event prevents the completion of the calibration procedure, the flow computer is left in calibration mode.
The sensor input is left at the forced value. This needs to be corrected or the proper flow measurement will not be made.
To recover, simply restart the calibration.
From the Flow Computer menu, select Calibrate.
Follow the on-screen instructions. You may have repeat steps already performed, depending on when the crash occurred.
Recovering From a Power Loss During Calibration
If power is lost to the flow computer during calibration, the calibration is aborted. The flow computer uses the live inputs from the sensors when power is restored.
If you were part way through calibration when the power was lost, you will have to restart the calibration. If possible, restore the sensor to an operating state before restoring power to the flow computer.
Replacing a Sensor
When a sensor is not working it needs to be replaced. If you have a working sensor you can replace it immediately. Replacing a sensor is similar to calibration.
At the As-Found stage it will be necessary to take at least one reading. If possible take enough readings to show how the sensor has stopped working. This may make it possible to correct previous flow readings.
Answer Yes when asked if you want to calibrate the sensor.
During the calibration step, remove the sensor and replace it with a working sensor.
Take the same As-Left readings as you would for calibration.
If a working sensor is not available, it may be possible to continue measuring flow by forcing a value for the sensor. Consult your company‟s procedures before attempting this. Forcing of input registers can be done using Telepace (see the Telepace manual for details).
Calibration Report Options
The calibration report options command specifies where the calibration report is stored when the Calibration Report Options dialog is displayed.
Realflo User and Reference Manual
May 19, 2011
446
Realflo Expert Mode Reference
Realflo suggests report file names.
The Format window selects the name format. The valid values are listed below. The default is to include all information.
file name (Flow Computer ID) - Run# (run ID)
file name (Flow Computer ID) - Run#
file name (Flow Computer ID) - run ID
file name - Run# (run ID)
file name - Run#
file name - run ID
Flow Computer ID - Run# (run ID)
Flow Computer ID - Run#
Flow Computer ID - run ID
Run# (run ID)
run ID
The Example control shows the file name that will be suggested for the current file. The text Calibration Report is appended to any suggestions.
The Report File Location window is used to select where reports are stored:
Type the folder where reports are to be stored.
Click Browse to select a folder.
These options are stored in the registry and apply to any files opened in
Realflo.
The default file name is file name (Flow Computer ID) - Run# (run ID)
The default location when Realflo is first run is the Realflo installation folder.
Change Orifice Plate
The Change Orifice Plate command allows the orifice plate to be changed for AGA-3 meter runs. This command supports Dual Chamber Orifice fittings and Singe Chamber Orifice fittings.
Realflo User and Reference Manual
May 19, 2011
447
Select Meter Run
Realflo Expert Mode Reference
When selected this command opens the Orifice Plate Change wizard is started and will prompt you through the plate change procedure.
The flow computer ID is checked when the Change Orifice Plate command is selected. If the flow computer ID does not match the ID Realflo displays the message “ The Flow Computer ID from the flow computer does not match the Flow Computer ID from the file.” The command is aborted.
When the Change Orifice command is selected the Change Orifice Plate dialog is displayed.
The Run dropdown selection displays the runs using AGA
–3 flow calculations. Select the run to change or inspect the orifice plate.
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log. Realflo does not attempt to reverse the effect of a previous step when backing up. For example, backing up to the force values step does not restore the live values.
The Next> button completes the run selection and the wizard moves to the next step. This button is grayed out if there are no flow runs configured to use the AGA-3 flow calculation.
The Cancel button aborts the plate change and displays the following message.
Click Yes to abort the calibration.
Realflo User and Reference Manual
May 19, 2011
448
Realflo Expert Mode Reference
Click No to continue with the plate change. The default button is No.
Realflo User and Reference Manual
May 19, 2011
449
Realflo Expert Mode Reference
WARNING
Realflo uses live values from the sensor when the plate change is cancelled.
Be sure to connect all sensors first.
Realflo does not erase any events from the flow computer when the plate change is cancelled. Realflo restores live values (ends forcing) when Cancel is clicked.
The Help button displays the online help file.
Choose Orifice Fitting Type Step
This page allows the users to select the type of orifice fitting.
Select Dual Chamber Orifice Fitting if a dual chamber fitting is present.
Flow accumulation with estimated values will continue during the plate change.
Select Singe Chamber Orifice Fitting if a single chamber fitting is present.
Flow accumulation will stop during the plate change.
The Next button moves to the next step.
The next step is described in the section Dual Chamber Orifice
if a dual chamber fitting is selected.
The next step is described in the section Single Chamber Orifice
if a single chamber fitting is selected.
The Cancel button closes the dialog and stops the plate change procedure.
The Help button displays the online Help file.
Dual Chamber Orifice
A dual chamber orifice allows the user to change, or inspect, the orifice plate without stopping the flow. These are generally large custody transfer sites
Realflo User and Reference Manual
May 19, 2011
450
Force Input Step
Realflo Expert Mode Reference where the orifice fitting is bypassed during the change or inspection procedure.
The Change Orifice Plate Command forces the Static Pressure, Differential
Pressure and Temperature inputs to a fixed value during the orifice plate change or inspection procedure. This command is disabled if the Update
Readings command is enabled. The flow is estimated during the procedure using the fixed values.
This command allows a user to place a flow run into estimation mode to allow an orifice plate to be changed or inspected. Changing the orifice plate involves the following steps.
Set the estimated flow to be used during the orifice plate change by forcing inputs to fixed values.
Change the orifice size.
Complete the orifice plate change and resume normal flow measurement.
The Flow Computer ID is checked when the Change Orifice Plate command is selected. If the Flow Computer ID does not match the ID Realflo displays the message “ The Flow Computer ID from the flow computer does not match the Flo w Computer ID from the file.” The command is aborted.
This step forces the flow run inputs. An estimated flow will be calculated while the plate change is in progress. The current values are updated every second.
Select the value you wish to use, for each sensor, by clicking the appropriate radio button for each sensor.
Check the Current Value radio button to use the current value for the sensor.
Check the Fixed Value radio button and enter a value to use for the calibration in the entry box.
Realflo User and Reference Manual
May 19, 2011
451
Realflo Expert Mode Reference
If an input on a run is not currently forced, the default value configured for the Values for Sensor Fail field on the Configuration Tool Bar > Run n >
Inputs tab needs to be entered for the Fixed Value The default value to use when the Value on Sensor Fail option on the Inputs tab is set to Use Default
Value field.
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log. Realflo does not attempt to reverse the effect of a previous step when backing up. For example, backing up to the force values step does not restore the live values.
The Next> button completes the force inputs step and the wizard moves to the next step. Realflo records the start of the plate change procedure in the event log and forces the sensor inputs.
The Cancel button aborts the plate change and displays the following message.
Click Yes to abort the calibration.
Click No to continue with the plate change. The default button is No.
WARNING
Realflo uses live values from the sensor when the plate change is cancelled.
Be sure to connect all sensors first.
Realflo does not erase any events from the flow computer when the plate change is cancelled. Realflo restores live values (ends forcing) when Cancel is clicked.
The Help button displays the online help file.
Change Orifice Plate Step
The orifice plate can now be changed. The forced inputs are used while the change is in progress. This dialog allows you to enter the new orifice plate diameter.
Realflo User and Reference Manual
May 19, 2011
452
Realflo Expert Mode Reference
The Current Orifice Diameter and Current Pipe Diameter are displayed for reference.
Enter the new orifice size in the New Orifice Diameter entry box. If the diameter is not valid, Realflo displays the following a message box.
You need to enter a valid orifice diameter. Click the OK button to return to the Change Orifice dialog.
The Beta Ratio is calculated and displayed for orifice diameter changes.
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log. Realflo does not attempt to reverse the effect of a previous step when backing up. For example, backing up to the force values step does not restore the live values.
The Next> button completes the change orifice step and the wizard moves to the last step.
The Cancel button aborts the plate change and displays the following message.
Realflo User and Reference Manual
May 19, 2011
453
Realflo Expert Mode Reference
Click Yes to abort the calibration.
Click No to continue with the plate change. The default button is No.
WARNING
Realflo uses live values from the sensor when the plate change is cancelled.
Be sure to connect all sensors first.
Realflo does not erase any events from the flow computer when the plate change is cancelled. Realflo restores live values (ends forcing) when Cancel is clicked.
The Help button displays the online help file.
Complete Orifice Plate Change
The Finish Plate Change is the last step in the Plate Change wizard.
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log. Realflo does not attempt to reverse the effect of a previous step when backing up. For example, backing up to the force values step does not restore the live values.
The Finish button completes the orifice plate change wizard and closes the dialog. Realflo restores the sensor live values
Realflo User and Reference Manual
May 19, 2011
454
The Help button displays the online help file.
Realflo Expert Mode Reference
Realflo User and Reference Manual
May 19, 2011
455
Realflo Expert Mode Reference
Single Chamber Orifice
A single chamber orifice requires the flow be stopped while an orifice plate is changed.
The Change Orifice Plate command prompts the user to stop the flow before changing the plate and start the flow after changing the plate.
Changing the orifice plate involves the following steps.
Confirm that flow has stopped.
Change the orifice size.
Complete the orifice plate change.
The Flow Computer ID is checked when the Change Orifice Plate command is selected. If the Flow Computer ID does not match the ID Realflo displays the message “ The Flow Computer ID from the flow computer does not match th e Flow Computer ID from the file.” The command is aborted.
Stop Flow Step
This step stops the flow run. The current inputs can be monitored while the flow is stopped.
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log. Realflo does not attempt to reverse the effect of a previous step when backing up. For example, backing up to the force values step does not restore the live values.
The Next> button completes the Stop Flow step and the wizard moves to the next step. Realflo records the start of the plate change procedure in the event log and forces the sensor inputs.
The Cancel button aborts the plate change and closes the wizard.
The Help button displays the online help file.
Change Orifice Plate Step
Realflo User and Reference Manual
May 19, 2011
456
Realflo Expert Mode Reference
The orifice plate can now be changed. The forced inputs are used while the change is in progress. This dialog allows you to enter the new orifice plate diameter.
The Current Orifice Diameter and Current Pipe Diameter are displayed for reference.
Enter the new orifice size in the New Orifice Diameter entry box. If the diameter is not valid, Realflo displays the following a message box.
You need to enter a valid orifice diameter. Click the OK button to return to the Change Orifice dialog.
The Beta Ratio is calculated and displayed for orifice diameter changes.
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log. Realflo does not attempt to reverse the effect of a previous step when backing up.
The Next> button completes the change orifice step and the wizard moves to the last step.
The Cancel button aborts the plate change and closes the wizard.
The Help button displays the online help file.
Complete Orifice Plate Change
The Finish Plate Change is the last step in the Plate Change wizard.
Realflo User and Reference Manual
May 19, 2011
457
Realflo Expert Mode Reference
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log. Realflo does not attempt to reverse the effect of a previous step when backing up.
The Finish button completes the orifice plate change wizard and closes the dialog. Realflo restores the sensor live values
The Help button displays the online help file.
Calculation Control
This command is used to control the execution of flow calculations for all meter runs in the controller. This command is disabled if the Update
Readings command is enabled. The flow calculation for each selected meter run may be running or stopped.
When the Calculation Control dialog is opened, the current state of the flow calculation is read from the controller.
The flow computer ID is checked when the Calculation Control dialog is opened. If the flow computer ID does not match the ID in the dialog Realflo displays the message “ The Flow Computer ID from the flow computer does not match the Flow Computer ID from the file.
”
When the dialog is opened, the current state of every runs is read from the controller. The dialog displays a table containing four columns.
Realflo User and Reference Manual
May 19, 2011
458
Realflo Expert Mode Reference
The Run column displays each run configured in Realflo.
The Current Status column displays the flow calculation state of each run.
Running indicates the flow calculation is executing.
Stopped indicates the flow calculation is not executing.
Not Set indicates the run state is not known.
The New Status column displays the state of the flow calculation for each run. To change the state of the flow calculation, click on the cell or move the cursor to the cell with the arrow keys and press the space bar. The setting changes as follows:
Running changes to Stopped
Stopped changes to Running
Not set changes to Running
The Interval column displays the time between calculations for the run. This value cannot be changed.
The OK button accepts the changes and writes them to the controller. When there are no changes, nothing is written to the controller.
The Cancel button closes the dialog.
The Help button displays the help page for this dialog.
Update Readings
This command is used to control updating of the Current Readings view.
This command is disabled if the Update Readings command is enabled.
When this command is selected readings are continuously updated from the flow computer. A check mark is shown next to the command when readings are updating.
The flow computer ID is checked when the Update Readings command is selected. If the flow computer ID does not match the ID in the dialog Realflo displays the message “The Flow Computer ID from the flow computer does not match the Flow Computer ID from the file
.”
Realflo User and Reference Manual
May 19, 2011
459
Realflo Expert Mode Reference
The Current Readings view is updated continuously until the Update
Readings command is selected again.
Update Readings Once
This command is used to control updating of the Current Readings view.
When this command is selected readings are updated once from the flow computer.
The flow computer ID is checked when the Update Readings Once command is selected. If the flow computer ID does not match the ID in the dialog Realflo displays the message “ The Flow Computer ID from the flow computer does not match the Flow Computer ID from the file
.”
The Current Readings view is updated once each time the Update Readings
Once command is selected.
Force Inputs
The Force Sensor command allows forcing and unforcing of the value of the temperature sensor, static pressure sensor, differential pressure sensor, or pulse counter input. When selected the command opens the Force Sensor wizard. Flow calculations continue to execute while sensors are forced.
The flow computer ID is checked when the Force Inputs command is selected. If the flow computer ID does not match the ID in the dialog Realflo displays the message “ The Flow Computer ID from the flow computer does not match the Flow Computer ID from the file.”
When the Force Inputs command is selected the Select Run or Transmitter to Force dialog is opened as shown below.
Realflo User and Reference Manual
May 19, 2011
460
Force Run Inputs
Realflo Expert Mode Reference
Select Run to force the sensor inputs for a flow run using analog or pulse sensors. Select the run to be forced from the dropdown list. The Run controls are disabled if there are no runs using analog or pulse sensors.
See the section Force Run Inputs b
elow for information on forcing Run inputs.
Select Sensor to force the inputs from a transmitter. Select the transmitter
to be forced from the dropdown list beside it. See the section
below for information on forcing transmitter
inputs.
The Back button is disabled, as this is the first step in the wizard.
The Next starts the force procedure.
The Cancel closes the wizard.
The Help displays the online help file.
When the Force Run is selected the Force Input Values dialog is displayed as shown below. The Force Input Values step selects the analog inputs of a flow run which will be forced or unforced. It displays the inputs that can be forced
.
The Force Input Value dialog contains sections for Force Differential
Pressure Input, Force Static Pressure Input and Force Temperature Input.
When AGA-7 calculation type is used the dialog contains a section for Force
Pulse Counter Input instead of Force Differential Pressure Input.
For each input the following parameters are available:
Select Current Value to use the current value for the sensor. The current value is shown beside the control and updates continuously.
Realflo User and Reference Manual
May 19, 2011
461
Realflo Expert Mode Reference
Select Fixed Value to use a fixed value. Type the value in the edit box.
Select No Change, input is already forced to leave the input in its current state. This is selected by default if the value is already forced.
This is disabled if the input is not forced.
Select Remove to remove the existing forcing. This button is disabled if the input is not forced.
If an input on a run is not currently forced, the default value configured for the Values for Sensor Fail field on the Configuration Tool Bar > Run n >
Inputs tab needs to be entered for the Fixed Value The default value to use when the Value on Sensor Fail option on the Inputs tab is set to Use Default
Value field.
The Back button moves back to the Select Run or Transmitter to Force step. Backing up does not erase the events from the flow computer event log or remove forcing from inputs previously processed.
The Finish button completes the Force Input Value process and closes the dialog.
The Cancel button closes the wizard. This does not undo any changes. Any input that is already forced will remain forced.
The Help displays the online help file.
Realflo User and Reference Manual
May 19, 2011
462
Realflo Expert Mode Reference
Force Transmitter Sensor Inputs
This step shows the selected transmitter inputs. The inputs can be forced to the current value or a fixed value, left as it is, or the forcing can be removed.
The transmitter number, transmitter tag name, the communication port and the transmitter address associated with this transmitter are displayed to aid you in determining which input you are forcing.
The Sensor Values dialog contains sections for Force Differential Pressure,
Force Static Pressure and Force Temperature.
For each input the following parameters are available:
Select Current Value to use the current value for the sensor. The current value is shown beside the control and updates continuously.
Select Fixed Value to use a fixed value. Type the value in the edit box.
Select No Change, input is already forced to leave the input in its current state. This is selected by default if the value is already forced.
This is disabled if the input is not forced.
Select Remove Force to remove the existing forcing. This button is disabled if the input is not forced.
The Back button moves back to the Select Run or Transmitter to Force step.
Realflo User and Reference Manual
May 19, 2011
463
Realflo Expert Mode Reference
Backing up does not erase events from the flow computer event log, or remove forcing from inputs previously processed.
The Finish button completes the Force Input Value process and closes the dialog.
The Cancel button closes the wizard. This does not undo any changes. Any input that is already forced will remain forced.
The Help displays the online help file.
The same transmitter can be used for more than one flow run. Realflo forces the value for each run.
Realflo User and Reference Manual
May 19, 2011
464
Realflo Expert Mode Reference
Communication Menu
The Communication menu contains the commands for configuring the communication between the flow computer and Realflo.
PC Communications Settings Command
The PC Communication Settings command defines the communication protocol and communication link to communicate between the personal computer (PC) and SCADAPack or 4202 controller.
When the command is select the Communication Protocols Configuration dialog is displayed as shown below.
The Communication Protocols dropdown list box presents available communication protocols. The default protocol is Modbus RTU. Click the dropdown list icon at the right of the window to display a list of available communication protocols.
ClearSCADA
DNP
DNP/TCP
DNP/UDP
Modbus ASCII
Modbus ASCII in TCP
Modbus ASCII in UDP
[Modbus RTU]
Modbus RTU in TCP
Modbus RTU in UDP
Modbus/TCP
Modbus/UDP
Modbus/USB
SCADAServer
The Configure button opens configuration dialog for the selected communication protocol.
Realflo User and Reference Manual
May 19, 2011
465
Realflo Expert Mode Reference
The Realflo Command Timeout edit box sets the length of time, in seconds, to wait for a response to a Realflo command. The valid range is 3 to 60 seconds and the default value is 10.
Clicking the OK button will make the selected protocol the active one.
Clicking the Cancel button abandons any and any changes made via this dialog.
ClearSCADA
The ClearSCADA protocol driver is used for communicating with a local or remote ClearSCADA server. The ClearSCADA server will then, in turn, communicate with devices as per its configuration. The ClearSCADA protocol driver communicates with the ClearSCADA server using a TCP connection.
To configure a ClearSCADA protocol connection, highlight
ClearSCADA in the Communication Protocols window and click the
Configure button. The ClearSCADA Configuration window is displayed.
To select a configured ClearSCADA protocol connection, highlight
ClearSCADA in the Communication Protocols window and click the OK button.
To close the dialog, without making a selection click the Cancel button.
General Parameters
When ClearSCADA protocol is selected for configuration the ClearSCADA
Configuration dialog is opened with the General tab selected as shown below.
The General tab component information section contains the name of
Communication Component and the author, Control Microsystems.
The Communications Settings grouping contains details necessary to establish communication to a device through a local or remote ClearSCADA installation.
Realflo User and Reference Manual
May 19, 2011
466
Realflo Expert Mode Reference
The Modbus Station entry specifies the station address of the target device. Valid values are 1 to 65534.
The Outstation Set entry specifies the ClearSCADA outstation set to which the target device is attached. The valid range is 0 to 65535. The default value is 0.
The IP Address / Name entry specifies the Ethernet IP address in dotted quad notation, or a DNS host name that can be resolved to an IP address, of the PC where the ClearSCADA server is installed. The following IP addresses are not supported and will be rejected:
0.0.0.0 through 0.255.255.255
127.0.0.0 through 127.255.255.255 (except 127.0.0.1)
224.0.0.0 through 224.255.255.255
255.0.0.0 through 255.255.255.255.
The TCP Port Number entry specifies the TCP port on the ClearSCADA server. The valid range is 0 to 65535. The default value is 49155
Click Restore Defaults to restore default values to fields on this page, except for the IP Address / Name field. The contents of this field will remain unchanged.
Advanced Parameters
Advanced parameters are used to control the message size for the protocol.
Control over message length is needed when writing large amounts of data over certain communication networks. A larger value can improve communication speed but can increase the number of missing transmissions. A smaller value can reduce the number of missing transmissions but may reduce throughput. When the Advanced tab heading is clicked the Advanced dialog is opened as shown below.
The protocol that ClearSCADA uses to communicate with the remote
SCADAPack controller needs to be taken into account when determining the message size. In ClearSCADA the Modbus tab in the Channel object sets the maximum packet size ClearSCADA uses when communicating with the remote SCADAPack controller.
Realflo User and Reference Manual
May 19, 2011
467
Realflo Expert Mode Reference
Information
The Maximum selection indicates that the host application is to package messages using the maximum size allowable by the protocol.
The Custom Value selection specifies a custom value for the message size. This value will indicate to the host application to package messages to be no larger than what is specified, if it is possible. Valid values are 2 to 264.
The default value is 264.
Click Restore Defaults to restore default values to fields on this page.
Information displays detailed driver information. When the Information tab heading is clicked the Information dialog is opened as shown below.
Realflo User and Reference Manual
May 19, 2011
468
Realflo Expert Mode Reference
Module is the physical name of the driver.
File Version is the version number of the driver.
In GAC indicates whether the module (assembly) was loaded from the
Global Assembly Cache (GAC).
Runtime is the version of the Common Language Runtime (CLR) the driver was built against.
Copyright indicates the copyright information of the protocol driver.
DNP
The DNP protocol driver is used to communicate over a serial DNP network to SCADAPack controllers configured for DNP communication.
To configure a DNP protocol connection, highlight DNP in the
Communication Protocols window and click the Configure button. The
DNP Configuration window is displayed.
To select a configured DNP protocol connection, highlight DNP in the
Communication Protocols window and click the OK button.
To close the dialog, without making a selection click the Cancel button.
General Parameters
When DNP is selected for configuration the DNP Configuration dialog is opened with the General tab selected as shown below.
Realflo User and Reference Manual
May 19, 2011
469
Realflo Expert Mode Reference
The General tab component information section contains the name of
Communication Component and the author, Control Microsystems.
The DNP Communication Settings logical grouping contains DNP specific communication settings including the DNP Station address, the timeout interval as well as the number of attempts.
The RTU Station parameter sets the target DNP station number. Valid entries are 0 to 65519. The default address is 1.
The Timeout parameter sets the length of time, in seconds, to wait for a response from the controller before retrying (see Attempts). Valid entries are
1 to 255. The default is 3.
The Attempts parameter sets number of times to send a command to the controller before giving up and reporting this to the host application. Valid entries are 1 to 20. The default is 3.
This Serial Port Settings grouping contains details directly related to the
PC‟s communication port including the port number, the baud rate, parity, and stop bit settings.
The Port parameter specifies the PC serial port to use. The DNP driver determines what serial ports are available on the PC and presents these in the drop-down menu list. The available serial ports list will include any USB to serial converters used on the PC. The default value is the first existing port found by the driver.
Realflo User and Reference Manual
May 19, 2011
470
Realflo Expert Mode Reference
The Baud parameter specifies the baud rate to use for communication. The menu list displays selections for 300, 600, 1200, 2400, 4800, 9600, 19200,
38400, and 57600. The default value is 9600.
The Parity parameter specifies the type of parity to use for communication.
The menu list displays selections for none, odd and even parity. The default value is None.
The Stop Bits parameter specifies the number of stop bits to use for communication. The menu list displays selections for 1 and 2 stop bits. The default value is 1 bit.
The Connection Type parameter specifies the serial connection type. The
DNP driver supports direct serial connection with no flow control, Requestto-send (RTS) and clear-to-send (CTS) flow control and PSTN dial-up connections. The menu list displays selections for Direct Connection,
RTS/CTS Flow Control and Dial Up Connection. The default selection is
Direct Connection.
Select Direct Connection for RS-232 for RS-485 connections not requiring the hardware control lines on the serial ports.
Select RTS/CTS Flow Control to communicate over radio or leasedline networks using modems that require RTS/CTS handshaking.
Selecting RTS/CTS Flow Control adds a new tab, Flow Control, to the
DNP Configuration dialog. Refer to the Flow Control Parameters section below for configuration details.
Select Dial Up Connection to communication over dial up modems.
Selecting Dial Up Connection adds a new tab, Dial Up, to the DNP
Configuration dialog. Refer to the Dial Up Parameters section below for configuration details.
Click Restore Defaults to restore default values to fields on this page.
Flow Control Parameters
Flow Control parameters are used to configure how RTS and CTS control is used. When RTS/CTS Flow Control is selected for Connection Type the
Flow Control tab is added to the DNP Configuration dialog. When the Flow
Control tab heading is clicked the Flow Control dialog is opened as shown below.
Realflo User and Reference Manual
May 19, 2011
471
Realflo Expert Mode Reference
RTS/CTS Flow Control
The RTS/CTS Flow Control grouping contains two mutually exclusive options, Use Hardware Control Lines and Use CTS Delay Time. These options enable the driver to communicate over radio or leased-line networks using modems that require RTS/CTS handshaking.
The Use Hardware Control Lines option specifies a half-duplex connection requiring the use of the Request to Send (RTS) and Clear to Send (CTS) hardware control lines to control the flow of data. This selection is used with radios and dedicated telephone line modems. The driver turns on the RTS signal when it wants to transmit data. The modem or other device then turns on CTS when it is ready to transmit. The driver transmits the data, and then turns off the RTS signal. This selection is mutually exclusive of the Use CTS
Delay Time selection described below. This is the default selection.
The Use CTS Delay Time option is selected if the device cannot generate a
CTS signal. The driver will assert RTS then wait the specified Delay Time, in milliseconds, before proceeding. This option is mutually exclusive with the
Use Hardware Control Lines selection described above.
The Delay Time parameter sets the time in milliseconds that the driver will wait after asserting RTS before proceeding. The value of this field needs to be smaller than the Time Out value set in the General parameters dialog.
For example, if the Timeout value is set to 3 seconds, the CTS Delay Time can be set to 2999 milliseconds or less. The minimum value for this field is 0 milliseconds. The value is initially set to 0 by default.
Realflo User and Reference Manual
May 19, 2011
472
Realflo Expert Mode Reference
The Hold Time parameter specifies the time, in milliseconds, that the driver will hold RTS after the last character is transmitted. This is useful for devices that immediately end transmission when RTS is turned off. The value of this field needs to be smaller than the Time Out value set in the General parameters dialog. For example, if the Timeout value is set to 3 seconds, the CTS Delay Time can be set to 2999 milliseconds or less. The minimum value for this field is 0 milliseconds. The value is initially set to 0 by default.
Click Restore Defaults to restore default values to fields on this page.
Dial Up Parameters
Dial Up parameters are used to configure a dial up connection. When Dial
Up is selected for Connection Type the Dial Up tab is added to the DNP
Configuration dialog. When the Dial Up tab heading is clicked the Dial Up dialog is opened as shown below.
The Dialing Prefix parameter specifies the commands sent to the modem before dialing. A maximum of 32 characters can be entered. Any character i s valid. The default value is “&F0 &K0 S0=1 &W0 &Y0”.
The Phone Number parameter specifies the telephone number of the remote controller. A maximum of 32 characters can be entered. Any character i s valid. This field‟s default value is blank.
The Dial Type parameter specifies the dialing type. Valid values are Pulse and Tone. The default value is Tone.
Realflo User and Reference Manual
May 19, 2011
473
Realflo Expert Mode Reference
The Dial Attempts parameter specifies how many dialing attempts will be made. Valid values are 1 to 10. The default value is 1.
The Connect Time parameter specifies the amount of time in seconds the modem will wait for a connection. Valid values are 6 to 300. The default value is 60.
The Pause Time parameter specifies the time in seconds between dialing attempts. Valid values are 6 to 600. The default value is 30.
Check the Inactivity Timeout check box to automatically terminate the dialup connection after a period of inactivity. The Inactivity Time edit box is enabled only if this option is checked. The default state is checked.
Enter the inactivity period, in minutes, in the Inactivity Timeout box. The dialup connection will be terminated automatically after the specified number of minutes of inactivity has lapsed. This option is only active if the Inactivity
Timeout box is checked. Valid values are from 1 to 30 minutes. The default value is 1.
Click Restore Defaults to restore default values to fields on this page, except for the Phone Number field. The content of this field will remain unchanged.
Advanced Parameters
DNP Configuration Advanced parameters set the DNP master station address and message size control. When the Advanced tab heading is clicked the Advanced dialog is opened as shown below.
Realflo User and Reference Manual
May 19, 2011
474
Information
Realflo Expert Mode Reference
The Master Station parameter is the DNP station address assumed by this communication component. When this driver sends out commands, responses from the controller will be directed to this address. The default value is 100.
The Message Size grouping parameters are used to control the message size for the protocol. Control over message length is needed when writing large amounts of data over certain communication networks. A larger value can improve communication speed but can increase the number of missing transmissions. A smaller value can reduce the number of missing transmissions but may reduce throughput.
The Maximum selection indicates that the host application is to package messages using the maximum size allowable by the protocol.
The Custom Value selection specifies a custom value for the message size. This value indicates to the host application to package messages to be no larger than what is specified, if it is possible. Valid values are 2 to 231.
The default value is 231.
Click Restore Defaults to restore default values to fields on this page.
Information displays detailed driver information. When the Information tab heading is clicked the Information dialog is opened as shown below.
Realflo User and Reference Manual
May 19, 2011
475
DNP/TCP
General Page
Realflo Expert Mode Reference
The Information grouping presents informative details concerning the executing protocol driver.
Module is the physical name of the driver.
File Version is the version number of the driver.
In GAC indicates whether the module (assembly) was loaded from the
Global Assembly Cache (GAC).
Runtime is the version of the Common Language Runtime (CLR) the driver was built against.
Copyright indicates the copyright information of the protocol driver.
The DNP/TCP protocol driver is used to communicate over an Ethernet
DNP network to SCADAPack controllers configured for DNP/TCP communication.
To configure a DNP/TCP protocol connection, highlight DNP/TCP in the
Communication Protocols window and click the Configure button. The
DNP/TCP Configuration window is displayed.
To select a configured DNP/TCP protocol connection, highlight
DNP/TCP in the Communication Protocols window and click the OK button.
To close the dialog, without making a selection click the Cancel button.
When DNP/TCP protocol is selected for configuration the DNP/TCP
Configuration dialog is opened with the General tab selected as shown below.
Realflo User and Reference Manual
May 19, 2011
476
Realflo Expert Mode Reference
The DNP Communication Settings grouping contains DNP specific communication settings including the DNP Station address, the timeout interval as well as the number of attempts.
The RTU Station parameter specifies the DNP station number of the target device. The valid range is 0 to 65519. The default is station 1.
The Timeout parameter specifies the length of time, in seconds, to wait for a response from the controller before retrying (see Attempts). Valid values are 1 to 255. The default value is 3 seconds.
The Attempts parameter specifies the number of times to send a command to the controller before giving up and reporting this to the host application.
Valid values are 1 to 20. The default value is 3 attempts.
The Host Network Details grouping contains information about the IP network including the target‟s IP address or name, and the TCP port number on which it is listening. More details on these below.
IP Address / Name
The IP Address / Name parameter specifies the Ethernet IP address of the target RTU, or a DNS name that can be resolved to an IP address. The default value is blank. The following IP addresses are not supported and will be rejected:
0.0.0.0 through 0.255.255.255
127.0.0.0 through 127.255.255.255 (except 127.0.0.1)
224.0.0.0 through 224.255.255.255
255.0.0.0 through 255.255.255.255.
The TCP Port No. field specifies the TCP port of the remote device. Valid values are 0 to 65535. The default value is 20000.
Click Restore Defaults to restore default values to fields on this page, except for the IP Address / Name field. The content of this field will remain unchanged.
Advanced Page
Advanced parameters are used to set the Master Station address and control the message size for the protocol. Control over message length is needed when writing large amounts of data over certain communication networks. A larger value can improve communication speed but can increase the number of missing transmissions. A smaller value can reduce the number of missing transmissions but may reduce throughput. When the
Advanced tab heading is clicked the Advanced dialog is opened as shown below.
Realflo User and Reference Manual
May 19, 2011
477
Realflo Expert Mode Reference
Information Page
The Master Station parameter specifies the DNP station address of the
Realflo application. When Realflo sends out commands, responses from the target controller will be directed to this address. The valid range is 0 to
65519, except that this value cannot be the same as the target RTU Station number. The default value is 100.
The Maximum selection indicates that you want the host application to package messages using the maximum size allowable by the protocol.
The Custom value selection specifies a custom value for message size.
This value indicates to the host application to package messages to be no larger than what is specified if possible. The valid range for the Custom value field is from 2 to 231. Maximum is selected by default.
Click Restore Defaults to restore default values to fields on this page.
Realflo User and Reference Manual
May 19, 2011
478
Realflo Expert Mode Reference
The Information page displays detailed driver information. When the
Information tab is clicked the Information dialog is opened as shown below.
DNP/UDP
The Information grouping presents informative details concerning the executing protocol driver.
Module is the physical name of the driver.
File Version is the version number of the driver.
In GAC indicates whether the module (assembly) was loaded from the
Global Assembly Cache (GAC).
Runtime is the version of the Common Language Runtime (CLR) the driver was built against.
Copyright indicates the copyright information of the protocol driver.
The DNP/UDP protocol driver is used to communicate over an Ethernet
DNP network to SCADAPack controllers configured for DNP/UDP communication.
Realflo User and Reference Manual
May 19, 2011
479
General Page
Realflo Expert Mode Reference
To configure a DNP/UDP protocol connection, highlight DNP/UDP in the
Communication Protocols window and click the Configure button. The
DNP/UDP Configuration window is displayed.
To select a configured DNP/UDP protocol connection, highlight
DNP/UDP in the Communication Protocols window and click the OK button.
To close the dialog, without making a selection click the Cancel button.
When DNP/UDP protocol is selected for configuration the DNP/UDP
Configuration dialog is opened with the General tab selected as shown below.
The DNP Communication Settings grouping contains DNP specific communication settings including the DNP Station address, the timeout interval as well as the number of attempts.
The RTU Station parameter specifies the DNP station number of the target device. The valid range is 0 to 65519. The default is station 1.
The Timeout parameter specifies the length of time, in seconds, to wait for a response from the controller before retrying (see Attempts). Valid values are 1 to 255. The default value is 3 seconds.
The Attempts parameter specifies the number of times to send a command to the controller before giving up and reporting this to the host application.
Valid values are 1 to 20. The default value is 3 attempts.
Realflo User and Reference Manual
May 19, 2011
480
IP Address / Name
The IP Address / Name parameter specifies the Ethernet IP address of the target RTU, or a DNS name that can be resolved to an IP address. The default value is blank. The following IP addresses are not supported and will be rejected:
0.0.0.0 through 0.255.255.255
127.0.0.0 through 127.255.255.255 (except 127.0.0.1)
224.0.0.0 through 224.255.255.255
255.0.0.0 through 255.255.255.255.
The UDP Port No. field specifies the UDP port of the remote device. Valid values are 0 to 65534. The default value is 20000.
Click Restore Defaults to restore default values to fields on this page, except for the IP Address / Name field. The content of this field will remain unchanged.
Advanced Page
Realflo Expert Mode Reference
The Host Network Details grouping contains information about the IP network including the target‟s IP address or name, and the UDP port number on which it is listening. More details on these below.
Advanced parameters are used to set the Master Station address and control the message size for the protocol. Control over message length is needed when writing large amounts of data over certain communication networks. A larger value can improve communication speed but can increase the number of missing transmissions. A smaller value can reduce the number of missing transmissions but may reduce throughput. When the
Advanced tab heading is clicked the Advanced dialog is opened as shown below.
Realflo User and Reference Manual
May 19, 2011
481
Information Page
Realflo Expert Mode Reference
The Master Station parameter specifies the DNP station address of the
Realflo application. When Realflo sends out commands, responses from the target controller will be directed to this address. The valid range is 0 to
65519, except that this value cannot be the same as the target RTU Station number. The default value is 100.
The Maximum selection indicates that you want the host application to package messages using the maximum size allowable by the protocol.
The Custom value selection specifies a custom value for message size.
This value indicates to the host application to package messages to be no larger than what is specified if possible. The valid range for the Custom value field is from 2 to 231. Maximum is selected by default.
Click Restore Defaults to restore default values to fields on this page
The Information page displays detailed driver information. When the
Information tab is clicked the Information dialog is opened as shown below.
The Information grouping presents informative details concerning the executing protocol driver.
Module is the physical name of the driver.
File Version is the version number of the driver.
In GAC indicates whether the module (assembly) was loaded from the
Global Assembly Cache (GAC).
Realflo User and Reference Manual
May 19, 2011
482
Realflo Expert Mode Reference
Runtime is the version of the Common Language Runtime (CLR) the driver was built against.
Copyright indicates the copyright information of the protocol driver.
Modbus ASCII
The Modbus ASCII protocol driver is used to communicate over a serial network, using Modbus ASCII framing, to SCADAPack controllers configured for Modbus ASCII protocol.
To configure a Modbus ASCII protocol connection, highlight Modbus
ASCII in the Communication Protocols window and click the Configure button. The Modbus ASCII Configuration window is displayed.
To select a configured Modbus ASCII protocol connection, highlight
Modbus ASCII in the Communication Protocols window and click the
OK button.
To close the dialog, without making a selection click the Cancel button.
General Parameters
When Modbus ASCII is selected for configuration the Modbus ASCII
Configuration dialog is opened with the General tab selected as shown below.
Realflo User and Reference Manual
May 19, 2011
483
Realflo Expert Mode Reference
The Modbus Communication Settings grouping contains Modbus specific communication settings including the addressing mode, the station address, the timeout interval as well as the number of attempts.
The Addressing parameter selects standard or extended Modbus addressing. Standard addressing allows 255 stations and is compatible with standard Modbus devices. Extended addressing allows 65534 stations, with stations 1 to 254 compatible with standard Modbus devices. The default is
Standard.
The Station parameter sets the target station number. The valid range is 1 to 255 if standard addressing is used, and 1 to 65534 if extended addressing is used. The default is 1.
The Timeout parameter sets the length of time, in seconds, to wait for a response from the controller before retrying (see Attempts). Valid entries are
1 to 255. The default is 3.
The Attempts parameter sets number of times to send a command to the controller before giving up and reporting this to the host application. Valid entries are 1 to 20. The default is 3.
This Serial Port Settings grouping contains details directly related to the
PC‟s communication port including the port number, the baud rate, parity, and stop bit settings.
The Port parameter specifies the PC serial port to use. The DNP driver determines what serial ports are available on the PC and presents these in the drop-down menu list. The available serial ports list will include any USB to serial converters used on the PC. The default value is the first existing port found by the driver.
The Baud parameter specifies the baud rate to use for communication. The menu list displays selections for 300, 600, 1200, 2400, 4800, 9600, 19200,
38400, and 57600. The default value is 9600.
The Parity parameter specifies the type of parity to use for communication.
The menu list displays selections for none, odd and even parity. The default value is None.
The Data Bits parameter specifies the number of data bits contained in the character frame. Valid values are for this field is 7 and 8 bits. The default value is 8 bits.
The Stop Bits parameter specifies the number of stop bits to use for communication. The menu list displays selections for 1 and 2 stop bits. The default value is 1 bit.
The Connection Type parameter specifies the serial connection type. The
Modbus ASCII driver supports direct serial connection with no flow control,
Request-to-send (RTS) and clear-to-send (CTS) flow control and PSTN dialup connections. The menu list displays selections for Direct Connection,
RTS/CTS Flow Control and Dial Up Connection. The default selection is
Direct Connection.
Select Direct Connection for RS-232 for RS-485 connections not requiring the hardware control lines on the serial ports.
Select RTS/CTS Flow Control to communicate over radio or leasedline networks using modems that require RTS/CTS handshaking.
Selecting RTS/CTS Flow Control adds a new tab, Flow Control, to the
Realflo User and Reference Manual
May 19, 2011
484
Realflo Expert Mode Reference
Modbus ASCII Configuration dialog. Refer to the Flow Control
Parameters section below for configuration details.
Select Dial Up Connection to communication over dial up modems.
Selecting Dial Up Connection adds a new tab, Dial Up, to the Modbus
ASCII Configuration dialog. Refer to the Dial Up Parameters section below for configuration details.
Click Restore Defaults to restore default values to fields on this page.
Modbus ASCII Configuration (Flow Control)
Flow Control parameters are used to configure how RTS and CTS control is used. When RTS/CTS Flow Control is selected for Connection Type the
Flow Control tab is added to the Modbus ASCII Configuration dialog. When the Flow Control tab heading is clicked the Flow Control dialog is opened as shown below.
The RTS/CTS Flow Control grouping contains two mutually exclusive options, Use Hardware Control Lines and Use CTS Delay Time. These options enable the driver to communicate over radio or leased-line networks using modems that require RTS/CTS handshaking.
The Use Hardware Control Lines option specifies a half-duplex connection requiring the use of the Request to Send (RTS) and Clear to Send (CTS) hardware control lines to control the flow of data. This selection is used with radios and dedicated telephone line modems. The driver turns on the RTS
Realflo User and Reference Manual
May 19, 2011
485
Realflo Expert Mode Reference signal when it wants to transmit data. The modem or other device then turns on CTS when it is ready to transmit. The driver transmits the data, and then turns off the RTS signal. This selection is mutually exclusive of the Use CTS
Delay Time selection described below. This is the default selection.
The Use CTS Delay Time option is selected if the device cannot generate a
CTS signal. The driver will assert RTS then wait the specified Delay Time, in milliseconds, before proceeding. This option is mutually exclusive with the
Use Hardware Control Lines selection described above.
The Delay Time parameter sets the time in milliseconds that the driver will wait after asserting RTS before proceeding. The value of this field needs to be smaller than the Time Out value set in the General parameters dialog.
For example, if the Timeout value is set to 3 seconds, the CTS Delay Time can be set to 2999 milliseconds or less. The minimum value for this field is 0 milliseconds. The value is initially set to 0 by default.
The Hold Time parameter specifies the time, in milliseconds, that the driver will hold RTS after the last character is transmitted. This is useful for devices that immediately end transmission when RTS is turned off. The value of this field needs to be smaller than the Time Out value set in the General parameters dialog. For example, if the Timeout value is set to 3 seconds, the CTS Delay Time can be set to 2999 milliseconds or less. The minimum value for this field is 0 milliseconds. The value is initially set to 0 by default.
Click Restore Defaults to restore default values to all fields on this page.
Modbus ASCII Configuration (Dial Up)
Dial Up parameters are used to configure a dial up connection. When Dial
Up is selected for Connection Type the Dial Up tab is added to the Modbus
ASCII Configuration dialog. When the Dial Up tab heading is clicked the
Dial Up dialog is opened as shown below.
Realflo User and Reference Manual
May 19, 2011
486
Realflo Expert Mode Reference
The Dialing Prefix parameter specifies the commands sent to the modem before dialing. A maximum of 32 characters can be entered. Any character is valid. The default value is “&F0 &K0 S0=1 &W0 &Y0”.
The Phone Number parameter specifies the telephone number of the remote controller. A maximum of 32 characters can be entered. Any character i s valid. This field‟s default value is blank.
The Dial Type parameter specifies the dialing type. Valid values are Pulse and Tone. The default value is Tone.
The Dial Attempts parameter specifies how many dialing attempts will be made. Valid values are 1 to 10. The default value is 1.
The Connect Time parameter specifies the amount of time in seconds the modem will wait for a connection. Valid values are 6 to 300. The default value is 60.
The Pause Time parameter specifies the time in seconds between dialing attempts. Valid values are 6 to 600. The default value is 30.
Check the Inactivity Timeout check box to automatically terminate the dialup connection after a period of inactivity. The Inactivity Time edit box is enabled only if this option is checked. The default state is checked.
Enter the inactivity period, in minutes, in the Inactivity Timeout box. The dialup connection will be terminated automatically after the specified number
Realflo User and Reference Manual
May 19, 2011
487
Realflo Expert Mode Reference of minutes of inactivity has lapsed. This option is only active if the Inactivity
Timeout box is checked. Valid values are from 1 to 30 minutes. The default value is 1.
Click Restore Defaults to restore default values to all fields on this page, except for the Phone Number field. The content of this field will remain unchanged.
Advanced Parameters
Advanced parameters are used to control the message size for the protocol.
Control over message length is needed when writing large amounts of data over certain communication networks. A larger value can improve communication speed but can increase the number of missing transmissions. A smaller value can reduce the number of missing transmissions but may reduce throughput. When the Advanced tab heading is clicked the Advanced dialog is opened as shown below.
The Message Size grouping parameters are used to control the message size for the protocol. Control over message length is needed when writing large amounts of data over certain communication networks. A larger value can improve communication speed but can increase the number of missing transmissions. A smaller value can reduce the number of missing transmissions but may reduce throughput.
Realflo User and Reference Manual
May 19, 2011
488
Information
Realflo Expert Mode Reference
The Maximum selection indicates that the host application is to package messages using the maximum size allowable by the protocol.
The Custom Value selection specifies a custom value for the message size. This value indicates to the host application to package messages to be no larger than what is specified, if it is possible. Valid values are 2 to 250 when Addressing is set to Extended and Station is 255 or higher. When
Addressing is set to Extended and Station is less than 255 valid values are
2 to 252. When Addressing is set to Standard valid values are 2 to 252.
Click Restore Defaults to restore default values to fields on this page.
Information displays detailed driver information. When the Information tab heading is clicked the Information dialog is opened as shown below.
The Information grouping presents informative details concerning the executing protocol driver.
Module is the physical name of the driver.
File Version is the version number of the driver.
In GAC indicates whether the module (assembly) was loaded from the
Global Assembly Cache (GAC).
Realflo User and Reference Manual
May 19, 2011
489
Realflo Expert Mode Reference
Runtime is the version of the Common Language Runtime (CLR) the driver was built against.
Copyright indicates the copyright information of the protocol driver.
Modbus ASCII in TCP
Modbus ASCII in TCP message format is exactly same as that of the
Modbus ASCII protocol. The main difference is that Modbus ASCII in TCP protocol communicates with a SCADAPack controller through the Internet and Modbus ASCII through the serial port. The Modbus ASCII in TCP protocol does not include a six-byte header prefix, as with the Modbus\TCP, but does include the Modbus „CRC-16‟ or „LRC‟ check fields.
To configure a Modbus ASCII in TCP protocol connection, highlight
Modbus ASCII in TCP in the Communication Protocols window and click the Configure button. The Modbus ASCII in TCP Configuration window is displayed.
To select a configured Modbus ASCII in TCP protocol connection, highlight Modbus ASCII in TCP in the Communication Protocols window and click the OK button.
To close the dialog, without making a selection click the Cancel button.
General Parameters
When Modbus ASCII in TCP is selected for configuration the Modbus ASCII in TCP Configuration dialog is opened with the General tab selected as shown below.
Realflo User and Reference Manual
May 19, 2011
490
Realflo Expert Mode Reference
The Modbus Communication Settings grouping contains Modbus specific communication settings including the addressing mode, the station address, the timeout interval as well as the number of attempts.
The Addressing parameter selects standard or extended Modbus addressing. Standard addressing allows 255 stations and is compatible with standard Modbus devices. Extended addressing allows 65534 stations, with stations 1 to 254 compatible with standard Modbus devices. The default is
Standard.
The Station parameter sets the target station number. The valid range is 1 to 255 if standard addressing is used, and 1 to 65534 if extended addressing is used. The default is 1.
The Timeout parameter sets the length of time, in seconds, to wait for a response from the controller before retrying (see Attempts). Valid entries are
1 to 255. The default is 3.
The Attempts parameter sets number of times to send a command to the controller before giving up and reporting this to the host application. Valid entries are 1 to 20. The default is 3.
The Host Network Details grouping contains entries for the host‟s IP address or name and the TCP port on which it is listening.
The IP Address / Name entry specifies the Ethernet IP address in dotted quad notation, or a DNS host name that can be resolved to an IP address, of the PC where the ClearSCADA server is installed. The following IP addresses are not supported and will be rejected:
0.0.0.0 through 0.255.255.255
127.0.0.0 through 127.255.255.255 (except 127.0.0.1)
224.0.0.0 through 224.255.255.255
255.0.0.0 through 255.255.255.255.
The TCP Port No. field specifies the TCP port of the remote device. Valid values are 0 to 65535. The default value is 49153.
Click Restore Defaults to restore default values to fields on this page, except for the IP Address / Name field. The content of this field will remain unchanged.
Advanced Parameters
Advanced parameters are used to control the message size for the protocol.
Control over message length is needed when writing large amounts of data over certain communication networks. A larger value can improve communication speed but can increase the number of missing transmissions. A smaller value can reduce the number of missing transmissions but may reduce throughput. When the Advanced tab heading is clicked the Advanced dialog is opened as shown below.
Realflo User and Reference Manual
May 19, 2011
491
Realflo Expert Mode Reference
Information
The Message Size grouping parameters are used to control the message size for the protocol. Control over message length is needed when writing large amounts of data over certain communication networks. A larger value can improve communication speed but can increase the number of missing transmissions. A smaller value can reduce the number of missing transmissions but may reduce throughput.
The Maximum selection indicates that the host application is to package messages using the maximum size allowable by the protocol.
The Custom Value selection specifies a custom value for the message size. This value indicates to the host application to package messages to be no larger than what is specified, if it is possible. Valid values are 2 to 250 when Addressing is set to Extended and Station is 255 or higher. When
Addressing is set to Extended and Station is less than 255 valid values are
2 to 252. When Addressing is set to Standard valid values are 2 to 252.
Click Restore Defaults to restore default values to all fields on this page.
Information displays detailed driver information. When the Information tab heading is clicked the Information dialog is opened as shown below.
Realflo User and Reference Manual
May 19, 2011
492
Realflo Expert Mode Reference
The Information grouping presents informative details concerning the executing protocol driver.
Module is the physical name of the driver.
File Version is the version number of the driver.
In GAC indicates whether the module (assembly) was loaded from the
Global Assembly Cache (GAC).
Runtime is the version of the Common Language Runtime (CLR) the driver was built against.
Copyright indicates the copyright information of the protocol driver.
Modbus ASCII in UDP
Modbus ASCII in UDP protocol is similar to Modbus ASCII in TCP protocol.
It has the same message format as the Modbus ASCII in TCP. The only difference between them is one uses TCP protocol and another uses UDP protocol.
To configure a Modbus ASCII in TCP protocol connection, highlight
Modbus ASCII in UDP in the Communication Protocols window and click the Configure button. The Modbus ASCII in UDP Configuration window is displayed.
Realflo User and Reference Manual
May 19, 2011
493
Realflo Expert Mode Reference
To select a configured Modbus ASCII in TCP protocol connection, highlight Modbus ASCII in UDP in the Communication Protocols window and click the OK button.
To close the dialog, without making a selection click the Cancel button.
General Parameters
When Modbus ASCII in UDP is selected for configuration the Modbus ASCII in UDP Configuration dialog is opened with the General tab selected as shown below.
The Modbus Communication Settings grouping contains Modbus specific communication settings including the addressing mode, the station address, the timeout interval as well as the number of attempts.
The Addressing parameter selects standard or extended Modbus addressing. Standard addressing allows 255 stations and is compatible with standard Modbus devices. Extended addressing allows 65534 stations, with stations 1 to 254 compatible with standard Modbus devices. The default is
Standard.
The Station parameter sets the target station number. The valid range is 1 to 255 if standard addressing is used, and 1 to 65534 if extended addressing is used. The default is 1.
The Timeout parameter sets the length of time, in seconds, to wait for a response from the controller before retrying (see Attempts). Valid entries are
1 to 255. The default is 3.
The Attempts parameter sets number of times to send a command to the controller before giving up and reporting this to the host application. Valid entries are 1 to 20. The default is 3.
Realflo User and Reference Manual
May 19, 2011
494
Realflo Expert Mode Reference
The Host Network Details grouping contains entries for the host‟s IP address or name and the TCP port on which it is listening.
The IP Address / Name entry specifies the Ethernet IP address in dotted quad notation, or a DNS host name that can be resolved to an IP address, of the PC where the ClearSCADA server is installed. The following IP addresses are not supported and will be rejected:
0.0.0.0 through 0.255.255.255
127.0.0.0 through 127.255.255.255 (except 127.0.0.1)
224.0.0.0 through 224.255.255.255
255.0.0.0 through 255.255.255.255.
The UDP Port No. field specifies the UDP port of the remote device. Valid values are 0 to 65535. The default value is 49153.
Click Restore Defaults to restore default values to fields on this page, except for the IP Address / Name field. The content of this field will remain unchanged.
Advanced Parameters
Advanced parameters are used to control the message size for the protocol.
Control over message length is needed when writing large amounts of data over certain communication networks. A larger value can improve communication speed but can increase the number of missing transmissions. A smaller value can reduce the number of missing transmissions but may reduce throughput. When the Advanced tab heading is clicked, the Advanced dialog is opened as shown below.
Realflo User and Reference Manual
May 19, 2011
495
Information
Realflo Expert Mode Reference
The Message Size grouping parameters are used to control the message size for the protocol. Control over message length is needed when writing large amounts of data over certain communication networks. A larger value can improve communication speed but can increase the number of missing transmissions. A smaller value can reduce the number of missing transmissions but may reduce throughput.
The Maximum selection indicates that the host application is to package messages using the maximum size allowable by the protocol.
The Custom Value selection specifies a custom value for the message size. This value indicates to the host application to package messages to be no larger than what is specified, if it is possible. Valid values are 2 to 250 when Addressing is set to Extended and Station is 255 or higher. When
Addressing is set to Extended and Station is less than 255 valid values are
2 to 252. When Addressing is set to Standard valid values are 2 to 252.
Click Restore Defaults to restore default values to fields on this page.
Information displays detailed driver information. When the Information tab heading is clicked the Information dialog is opened as shown below.
The Information grouping presents informative details concerning the executing protocol driver.
Realflo User and Reference Manual
May 19, 2011
496
Realflo Expert Mode Reference
Module is the physical name of the driver.
File Version is the version number of the driver.
In GAC indicates whether the module (assembly) was loaded from the
Global Assembly Cache (GAC).
Runtime is the version of the Common Language Runtime (CLR) the driver was built against.
Copyright indicates the copyright information of the protocol driver.
Modbus RTU
Introduction
The Modbus RTU protocol driver is used to communicate over a serial network, using Modbus RTU framing, to SCADAPack controllers configured for Modbus RTU protocol.
To configure a Modbus RTU protocol connection, highlight Modbus
RTU in the Communication Protocols window and click the Configure button. The Modbus RTU Configuration window is displayed.
To select a configured Modbus RTU protocol connection, highlight
Modbus RTU in the Communication Protocols window and click the OK button.
To close the dialog, without making a selection click the Cancel button.
General Parameters
When Modbus RTU is selected for configuration the Modbus RTU
Configuration dialog is opened with the General tab selected as shown below.
Realflo User and Reference Manual
May 19, 2011
497
Realflo Expert Mode Reference
The Modbus Communication Settings grouping contains Modbus specific communication settings including the addressing mode, the station address, the timeout interval as well as the number of attempts.
The Addressing parameter selects standard or extended Modbus addressing. Standard addressing allows 255 stations and is compatible with standard Modbus devices. Extended addressing allows 65534 stations, with stations 1 to 254 compatible with standard Modbus devices. The default is
Standard.
The Station parameter sets the target station number. The valid range is 1 to 255 if standard addressing is used and 1 to 65534 if extended addressing is used. The default is 1.
The Timeout parameter sets the length of time, in seconds, to wait for a response from the controller before retrying (see Attempts). Valid entries are
1 to 255. The default is 3.
The Attempts parameter sets number of times to send a command to the controller before giving up and reporting this to the host application. Valid entries are 1 to 20. The default is 3.
This Serial Port Settings grouping contains details directly related to the
PC‟s communication port including the port number, the baud rate, parity, and stop bit settings.
The Port parameter specifies the PC serial port to use. The DNP driver determines what serial ports are available on the PC and presents these in
Realflo User and Reference Manual
May 19, 2011
498
Realflo Expert Mode Reference the drop-down menu list. The available serial ports list will include any USB to serial converters used on the PC. The default value is the first existing port found by the driver.
The Baud parameter specifies the baud rate to use for communication. The menu list displays selections for 300, 600, 1200, 2400, 4800, 9600, 19200,
38400, and 57600. The default value is 9600.
The Parity parameter specifies the type of parity to use for communication.
The menu list displays selections for none, odd and even parity. The default value is None.
The Stop Bits parameter specifies the number of stop bits to use for communication. The menu list displays selections for 1 and 2 stop bits. The default value is 1 bit.
The Connection Type parameter specifies the serial connection type. The
Modbus RTU driver supports direct serial connection with no flow control,
Request-to-send (RTS) and clear-to-send (CTS) flow control and PSTN dialup connections. The menu list displays selections for Direct Connection,
RTS/CTS Flow Control and Dial Up Connection. The default selection is
Direct Connection.
Select Direct Connection for RS-232 for RS-485 connections not requiring the hardware control lines on the serial ports.
Select RTS/CTS Flow Control to communicate over radio or leasedline networks using modems that require RTS/CTS handshaking.
Selecting RTS/CTS Flow Control adds a new tab, Flow Control, to the
Modbus RTU Configuration dialog. Refer to the Flow Control
Parameters section below for configuration details.
Select Dial Up Connection to communication over dial up modems.
Selecting Dial Up Connection adds a new tab, Dial Up, to the Modbus
RTU Configuration dialog. Refer to the Dial Up Parameters section below for configuration details.
Click Restore Defaults to restore default values to fields on this page.
Modbus RTU Configuration (Flow Control)
Flow Control parameters are used to configure how RTS and CTS control is used. When RTS/CTS Flow Control is selected for Connection Type the
Flow Control tab is added to the Modbus RTU Configuration dialog. When the Flow Control tab heading is clicked the Flow Control dialog is opened as shown below.
Realflo User and Reference Manual
May 19, 2011
499
Realflo Expert Mode Reference
The RTS/CTS Flow Control grouping contains two mutually exclusive options, Use Hardware Control Lines and Use CTS Delay Time. These options enable the driver to communicate over radio or leased-line networks using modems that require RTS/CTS handshaking.
The Use Hardware Control Lines option specifies a half-duplex connection requiring the use of the Request to Send (RTS) and Clear to Send (CTS) hardware control lines to control the flow of data. This selection is used with radios and dedicated telephone line modems. The driver turns on the RTS signal when it wants to transmit data. The modem or other device then turns on CTS when it is ready to transmit. The driver transmits the data, and then turns off the RTS signal. This selection is mutually exclusive of the Use CTS
Delay Time selection described below. This is the default selection.
The Use CTS Delay Time option is selected if the device cannot generate a
CTS signal. The driver will assert RTS then wait the specified Delay Time, in milliseconds, before proceeding. This option is mutually exclusive with the
Use Hardware Control Lines selection described above.
The Delay Time parameter sets the time in milliseconds that the driver will wait after asserting RTS before proceeding. The value of this field needs to be smaller than the Time Out value set in the General parameters dialog.
For example, if the Timeout value is set to 3 seconds, the CTS Delay Time can be set to 2999 milliseconds or less. The minimum value for this field is 0 milliseconds. The value is initially set to 0 by default.
The Hold Time parameter specifies the time, in milliseconds, that the driver will hold RTS after the last character is transmitted. This is useful for devices
Realflo User and Reference Manual
May 19, 2011
500
Realflo Expert Mode Reference that immediately end transmission when RTS is turned off. The value of this field needs to be smaller than the Time Out value set in the General parameters dialog. For example, if the Timeout value is set to 3 seconds, the CTS Delay Time can be set to 2999 milliseconds or less. The minimum value for this field is 0 milliseconds. The value is initially set to 0 by default.
Click Restore Defaults to restore default values to fields on this page.
Modbus RTU Configuration (Dial Up)
Dial Up parameters are used to configure a dial up connection. When Dial
Up is selected for Connection Type the Dial Up tab is added to the Modbus
RTU Configuration dialog. When the Dial Up tab heading is clicked the Dial
Up dialog is opened as shown below.
The Dialing Prefix parameter specifies the commands sent to the modem before dialing. A maximum of 32 characters can be entered. Any characters are valid. The default value is “&F0 &K0 S0=1 &W0 &Y0”.
The Phone Number parameter specifies the telephone number of the remote controller. A maximum of 32 characters can be entered. Any characters are valid. This field‟s default value is blank.
The Dial Type parameter specifies the dialing type. Valid values are Pulse and Tone. The default value is Tone.
The Dial Attempts parameter specifies how many dialing attempts will be made. Valid values are 1 to 10. The default value is 1.
Realflo User and Reference Manual
May 19, 2011
501
Realflo Expert Mode Reference
The Connect Time parameter specifies the amount of time in seconds the modem will wait for a connection. Valid values are 6 to 300. The default value is 60.
The Pause Time parameter specifies the time in seconds between dialing attempts. Valid values are 6 to 600. The default value is 30.
Check the Inactivity Timeout check box to automatically terminate the dialup connection after a period of inactivity. The Inactivity Time edit box is enabled only if this option is checked. The default state is checked.
Enter the inactivity period, in minutes, in the Inactivity Timeout box. The dialup connection will be terminated automatically after the specified number of minutes of inactivity has lapsed. This option is only active if the Inactivity
Timeout box is checked. Valid values are from 1 to 30 minutes. The default value is 1.
Click Restore Defaults to restore default values to fields on this page, except for the Phone Number field. The content of this field will remain unchanged.
Advanced Parameters
Advanced parameters are used to control the message size for the protocol.
Control over message length is needed when writing large amounts of data over certain communication networks. A larger value can improve communication speed but can increase the number of missing transmissions. A smaller value can reduce the number of missing transmissions but may reduce throughput. When the Advanced tab heading is clicked the Advanced dialog is opened as shown below.
Realflo User and Reference Manual
May 19, 2011
502
Realflo Expert Mode Reference
Information
The Message Size grouping parameters are used to control the message size for the protocol. Control over message length is needed when writing large amounts of data over certain communication networks. A larger value can improve communication speed but can increase the number of missing transmissions. A smaller value can reduce the number of missing transmissions but may reduce throughput.
The Maximum selection indicates that the host application is to package messages using the maximum size allowable by the protocol.
The Custom Value selection specifies a custom value for the message size. This value indicates to the host application to package messages to be no larger than what is specified, if it is possible. Valid values are 2 to 250 when Addressing is set to Extended and Station is 255 or higher. When
Addressing is set to Extended and Station is less than 255 valid values are
2 to 252. When Addressing is set to Standard valid values are 2 to 252.
Click Restore Defaults to restore default values to fields on this page.
Information displays detailed driver information. When the Information tab heading is clicked the Information dialog is opened as shown below.
Realflo User and Reference Manual
May 19, 2011
503
Realflo Expert Mode Reference
The Information grouping presents informative details concerning the executing protocol driver.
Module is the physical name of the driver.
File Version is the version number of the driver.
In GAC indicates whether the module (assembly) was loaded from the
Global Assembly Cache (GAC).
Runtime is the version of the Common Language Runtime (CLR) the driver was built against.
Copyright indicates the copyright information of the protocol driver.
Modbus RTU in TCP
Modbus RTU in TCP message format is exactly same as that of the Modbus
RTU protocol. The main difference is that Modbus RTU in TCP protocol communicates with a controller through the Internet and Modbus RTU protocol through the serial port. The Modbus RTU in TCP protocol does not include a six-byte header prefix, as with the Modbus\TCP, but does include the Modbus „CRC-16‟ or „LRC‟ check fields. The Modbus RTU in TCP message format supports Modbus RTU message format.
Realflo User and Reference Manual
May 19, 2011
504
Realflo Expert Mode Reference
To configure a Modbus RTU in TCP protocol connection, highlight
Modbus RTU in TCP in the Communication Protocols window and click the Configure button. The Modbus RTU in TCP Configuration window is displayed.
To select a configured Modbus RTU in TCP protocol connection, highlight Modbus RTU in TCP in the Communication Protocols window and click the OK button.
To close the dialog, without making a selection click the Cancel button.
General Parameters
When Modbus RTU in TCP is selected for configuration the Modbus RTU in
TCP Configuration dialog is opened with the General tab selected as shown below.
The Modbus Communication Settings grouping contains Modbus specific communication settings including the addressing mode, the station address, the timeout interval as well as the number of attempts.
The Addressing parameter selects standard or extended Modbus addressing. Standard addressing allows 255 stations and is compatible with standard Modbus devices. Extended addressing allows 65534 stations, with stations 1 to 254 compatible with standard Modbus devices. The default is
Standard.
The Station parameter sets the target station number. The valid range is 1 to 255 if standard addressing is used and 1 to 65534 if extended addressing is used. The default is 1.
Realflo User and Reference Manual
May 19, 2011
505
Realflo Expert Mode Reference
The Timeout parameter sets the length of time, in seconds, to wait for a response from the controller before retrying (see Attempts). Valid entries are
1 to 255. The default is 3.
The Attempts parameter sets number of times to send a command to the controller before giving up and reporting this to the host application. Valid entries are 1 to 20. The default is 3.
The Host Network Details grouping contains entries for the host‟s IP address or name and the TCP port on which it is listening.
The IP Address / Name entry specifies the Ethernet IP address in dotted quad notation, or a DNS host name that can be resolved to an IP address, of the PC where the ClearSCADA server is installed. The following IP addresses are not supported and will be rejected:
0.0.0.0 through 0.255.255.255
127.0.0.0 through 127.255.255.255 (except 127.0.0.1)
224.0.0.0 through 224.255.255.255
255.0.0.0 through 255.255.255.255.
The TCP Port No. field specifies the TCP port of the remote device. Valid values are 0 to 65535. The default value is 49152.
Click Restore Defaults to restore default values to all fields on this page, except for the IP Address / Name field. The content of this field will remain unchanged.
Advanced Parameters
Advanced parameters are used to control the message size for the protocol.
Control over message length is needed when writing large amounts of data over certain communication networks. A larger value can improve communication speed but can increase the number of missing transmissions. A smaller value can reduce the number of missing transmissions but may reduce throughput. When the Advanced tab heading is clicked the Advanced dialog is opened as shown below.
Realflo User and Reference Manual
May 19, 2011
506
Realflo Expert Mode Reference
Information
The Message Size grouping parameters are used to control the message size for the protocol. Control over message length is needed when writing large amounts of data over certain communication networks. A larger value can improve communication speed but can increase the number of missing transmissions. A smaller value can reduce the number of missing transmissions but may reduce throughput.
The Maximum selection indicates that the host application is to package messages using the maximum size allowable by the protocol.
The Custom Value selection specifies a custom value for the message size. This value indicates to the host application to package messages to be no larger than what is specified, if it is possible. Valid values are 2 to 250 when Addressing is set to Extended and Station is 255 or higher. When
Addressing is set to Extended and Station is less than 255 valid values are
2 to 252. When Addressing is set to Standard valid values are 2 to 252.
Click Restore Defaults to restore default values to fields on this page.
Information displays detailed driver information. When the Information tab heading is clicked the Information dialog is opened as shown below.
Realflo User and Reference Manual
May 19, 2011
507
Realflo Expert Mode Reference
The Information grouping presents informative details concerning the executing protocol driver.
Module is the physical name of the driver.
File Version is the version number of the driver.
In GAC indicates whether the module (assembly) was loaded from the
Global Assembly Cache (GAC).
Runtime is the version of the Common Language Runtime (CLR) the driver was built against.
Copyright indicates the copyright information of the protocol driver.
Modbus RTU in UDP
Modbus RTU in UDP protocol is similar to Modbus RTU in TCP protocol. It has the same message format as the RTU in TCP message. The only difference between them is one uses TCP protocol and another uses UDP protocol.
To configure a Modbus RTU in UDP protocol connection, highlight
Modbus RTU in UDP in the Communication Protocols window and click the Configure button. The Modbus RTU in UDP Configuration window is displayed.
Realflo User and Reference Manual
May 19, 2011
508
Realflo Expert Mode Reference
To select a configured Modbus RTU in UDP protocol connection, highlight Modbus RTU in UDP in the Communication Protocols window and click the OK button.
To close the dialog, without making a selection click the Cancel button.
General Parameters
When Modbus RTU in UDP is selected for configuration the Modbus RTU in
UDP Configuration dialog is opened with the General tab selected as shown below.
The Modbus Communication Settings grouping contains Modbus specific communication settings including the addressing mode, the station address, the timeout interval as well as the number of attempts.
The Addressing parameter selects standard or extended Modbus addressing. Standard addressing allows 255 stations and is compatible with standard Modbus devices. Extended addressing allows 65534 stations, with stations 1 to 254 compatible with standard Modbus devices. The default is
Standard.
The Station parameter sets the target station number. The valid range is 1 to 255 if standard addressing is used and 1 to 65534 if extended addressing is used. The default is 1.
The Timeout parameter sets the length of time, in seconds, to wait for a response from the controller before retrying (see Attempts). Valid entries are
1 to 255. The default is 3.
The Attempts parameter sets number of times to send a command to the controller before giving up and reporting this to the host application. Valid entries are 1 to 20. The default is 3.
Realflo User and Reference Manual
May 19, 2011
509
Realflo Expert Mode Reference
The Host Network Details grouping contains entries for the host‟s IP address or name and the TCP port on which it is listening.
The IP Address / Name entry specifies the Ethernet IP address in dotted quad notation, or a DNS host name that can be resolved to an IP address, of the PC where the ClearSCADA server is installed. The following IP addresses are not supported and will be rejected:
0.0.0.0 through 0.255.255.255
127.0.0.0 through 127.255.255.255 (except 127.0.0.1)
224.0.0.0 through 224.255.255.255
255.0.0.0 through 255.255.255.255.
The UDP Port No. field specifies the UDP port of the remote device. Valid values are 0 to 65535. The default value is 49152.
Click Restore Defaults to restore default values to fields on this page, except for the IP Address / Name field. The content of this field will remain unchanged.
Advanced Parameters
Advanced parameters are used to control the message size for the protocol.
Control over message length is needed when writing large amounts of data over certain communication networks. A larger value can improve communication speed but can increase the number of missing transmissions. A smaller value can reduce the number of missing transmissions but may reduce throughput. When the Advanced tab heading is clicked the Advanced dialog is opened as shown below.
Realflo User and Reference Manual
May 19, 2011
510
Information
Realflo Expert Mode Reference
The Message Size grouping parameters are used to control the message size for the protocol. Control over message length is needed when writing large amounts of data over certain communication networks. A larger value can improve communication speed but can increase the number of missing transmissions. A smaller value can reduce the number of missing transmissions but may reduce throughput.
The Maximum selection indicates that the host application is to package messages using the maximum size allowable by the protocol.
The Custom Value selection specifies a custom value for the message size. This value indicates to the host application to package messages to be no larger than what is specified, if it is possible. Valid values are 2 to 250 when Addressing is set to Extended and Station is 255 or higher. When
Addressing is set to Extended and Station is less than 255 valid values are
2 to 252. When Addressing is set to Standard valid values are 2 to 252.
Click Restore Defaults to restore default values to fields on this page.
Information displays detailed driver information. When the Information tab heading is clicked the Information dialog is opened as shown below.
The Information grouping presents informative details concerning the executing protocol driver.
Module is the physical name of the driver.
File Version is the version number of the driver.
In GAC indicates whether the module (assembly) was loaded from the
Global Assembly Cache (GAC).
Realflo User and Reference Manual
May 19, 2011
511
Realflo Expert Mode Reference
Runtime is the version of the Common Language Runtime (CLR) the driver was built against.
Copyright indicates the copyright information of the protocol driver.
Modbus/TCP
Modbus/TCP is an extension of serial Modbus, which defines how Modbus messages are encoded within and transported over TCP/IP-based networks. The Modbus/TCP protocol uses a custom Modbus protocol layer on top of the TCP protocol. Its request and response messages are prefixed by six bytes. These six bytes consist of three fields: transaction ID field, protocol ID field and length field. The encapsulated Modbus message has exactly the same layout and meaning, from the function code to the end of the data portion, as other Modbus messages. The Modbus „CRC-16‟ or
„LRC‟ check fields are not used in Modbus/TCP. The TCP/IP and link layer
(e.g. Ethernet) checksum mechanisms instead are used to verify accurate delivery of the packet.
To configure a Modbus/TCP protocol connection, highlight
Modbus/TCP in the Communication Protocols window and click the
Configure button. The Modbus/TCP Configuration window is displayed.
To select a configured Modbus/TCP protocol connection, highlight
Modbus/TCP in the Communication Protocols window and click the OK button.
To close the dialog, without making a selection click the Cancel button.
General Parameters
When Modbus/TCP is selected for configuration the Modbus/TCP
Configuration dialog is opened with the General tab selected as shown below.
Realflo User and Reference Manual
May 19, 2011
512
Realflo Expert Mode Reference
The Modbus Communication Settings grouping contains Modbus specific communication settings including the addressing mode, the station address, the timeout interval as well as the number of attempts.
The Addressing parameter selects standard or extended Modbus addressing. Standard addressing allows 255 stations and is compatible with standard Modbus devices. Extended addressing allows 65534 stations, with stations 1 to 254 compatible with standard Modbus devices. The default is
Standard.
The Station parameter sets the target station number. The valid range is 1 to 255 if standard addressing is used and 1 to 65534 if extended addressing is used. The default is 1.
The Timeout parameter sets the length of time, in seconds, to wait for a response from the controller before retrying (see Attempts). Valid entries are
1 to 255. The default is 3.
The Attempts parameter sets number of times to send a command to the controller before giving up and reporting this to the host application. Valid entries are 1 to 20. The default is 3.
The Host Network Details grouping contains entries for the host‟s IP address or name and the TCP port on which it is listening.
The IP Address / Name entry specifies the Ethernet IP address in dotted quad notation, or a DNS host name that can be resolved to an IP address, of the PC where the ClearSCADA server is installed. The following IP addresses are not supported and will be rejected:
0.0.0.0 through 0.255.255.255
127.0.0.0 through 127.255.255.255 (except 127.0.0.1)
Realflo User and Reference Manual
May 19, 2011
513
Realflo Expert Mode Reference
224.0.0.0 through 224.255.255.255
255.0.0.0 through 255.255.255.255.
The TCP Port No. field specifies the UDP port of the remote device. Valid values are 0 to 65535. The default value is 502.
Click Restore Defaults to restore default values to fields on this page, except for the IP Address / Name field. The content of this field will remain unchanged.
Advanced Parameters
Advanced parameters are used to control the message size for the protocol.
Control over message length is needed when writing large amounts of data over certain communication networks. A larger value can improve communication speed but can increase the number of missing transmissions. A smaller value can reduce the number of missing transmissions but may reduce throughput. When the Advanced tab heading is clicked the Advanced dialog is opened as shown below.
The Message Size grouping parameters are used to control the message size for the protocol. Control over message length is needed when writing large amounts of data over certain communication networks. A larger value can improve communication speed but can increase the number of missing transmissions. A smaller value can reduce the number of missing transmissions but may reduce throughput.
The Maximum selection indicates that the host application is to package messages using the maximum size allowable by the protocol.
The Custom Value selection specifies a custom value for the message size. This value indicates to the host application to package messages to be
Realflo User and Reference Manual
May 19, 2011
514
Information
Realflo Expert Mode Reference no larger than what is specified, if it is possible. Valid values are 2 to 246 when Addressing is set to Extended and Station is 255 or higher. When
Addressing is set to Extended and Station is less than 255 valid values are
2 to 248. When Addressing is set to Standard valid values are 2 to 248.
Click Restore Defaults to restore default values to fields on this page.
Information displays detailed driver information. When the Information tab heading is clicked the Information dialog is opened as shown below.
The Information grouping presents informative details concerning the executing protocol driver.
Module is the physical name of the driver.
File Version is the version number of the driver.
In GAC indicates whether the module (assembly) was loaded from the
Global Assembly Cache (GAC).
Runtime is the version of the Common Language Runtime (CLR) the driver was built against.
Copyright indicates the copyright information of the protocol driver.
Realflo User and Reference Manual
May 19, 2011
515
Realflo Expert Mode Reference
Modbus/UDP
Modbus/UDP communication mode is similar to Modbus/TCP communication mode. It has the same message format with the
Modbus/TCP. The only difference between them is one uses TCP protocol and another uses UDP protocol.
To configure a Modbus/UDP protocol connection, highlight
Modbus/UDP in the Communication Protocols window and click the
Configure button. The Modbus/ UDP Configuration window is displayed.
To select a configured Modbus/UDP protocol connection, highlight
Modbus/ UDP in the Communication Protocols window and click the
OK button.
To close the dialog, without making a selection click the Cancel button.
General Parameters
When Modbus/UDP is selected for configuration the Modbus/ UDP
Configuration dialog is opened with the General tab selected as shown below.
The Modbus Communication Settings grouping contains Modbus specific communication settings including the addressing mode, the station address, the timeout interval as well as the number of attempts.
The Addressing parameter selects standard or extended Modbus addressing. Standard addressing allows 255 stations and is compatible with standard Modbus devices. Extended addressing allows 65534 stations, with stations 1 to 254 compatible with standard Modbus devices. The default is
Standard.
Realflo User and Reference Manual
May 19, 2011
516
Realflo Expert Mode Reference
The Station parameter sets the target station number. The valid range is 1 to 255 if standard addressing is used and 1 to 65534 if extended addressing is used. The default is 1.
The Timeout parameter sets the length of time, in seconds, to wait for a response from the controller before retrying (see Attempts). Valid entries are
1 to 255. The default is 3.
The Attempts parameter sets number of times to send a command to the controller before giving up and reporting this to the host application. Valid entries are 1 to 20. The default is 3.
The Host Network Details grouping contains entries for the host‟s IP address or name and the TCP port on which it is listening.
The IP Address / Name entry specifies the Ethernet IP address in dotted quad notation, or a DNS host name that can be resolved to an IP address, of the PC where the ClearSCADA server is installed. The following IP addresses are not supported and will be rejected:
0.0.0.0 through 0.255.255.255
127.0.0.0 through 127.255.255.255 (except 127.0.0.1)
224.0.0.0 through 224.255.255.255
255.0.0.0 through 255.255.255.255.
The UDP Port No. field specifies the UDP port of the remote device. Valid values are 0 to 65535. The default value is 502.
Click Restore Defaults to restore default values to fields on this page, except for the IP Address / Name field. The content of this field will remain unchanged.
Advanced Parameters
Advanced parameters are used to control the message size for the protocol.
Control over message length is needed when writing large amounts of data over certain communication networks. A larger value can improve communication speed but can increase the number of missing transmissions. A smaller value can reduce the number of missing transmissions but may reduce throughput. When the Advanced tab heading is clicked the Advanced dialog is opened as shown below.
Realflo User and Reference Manual
May 19, 2011
517
Realflo Expert Mode Reference
Information
The Message Size grouping parameters are used to control the message size for the protocol. Control over message length is needed when writing large amounts of data over certain communication networks. A larger value can improve communication speed but can increase the number of missing transmissions. A smaller value can reduce the number of missing transmissions but may reduce throughput.
The Maximum selection indicates that the host application is to package messages using the maximum size allowable by the protocol.
The Custom Value selection specifies a custom value for the message size. This value indicates to the host application to package messages to be no larger than what is specified, if it is possible. Valid values are 2 to 246 when Addressing is set to Extended and Station is 255 or higher. When
Addressing is set to Extended and Station is less than 255 valid values are
2 to 248. When Addressing is set to Standard valid values are 2 to 248.
Click Restore Defaults to restore default values to fields on this page.
Information displays detailed driver information. When the Information tab heading is clicked the Information dialog is opened as shown below.
Realflo User and Reference Manual
May 19, 2011
518
Realflo Expert Mode Reference
Modbus/USB
The Information grouping presents informative details concerning the executing protocol driver.
Module is the physical name of the driver.
File Version is the version number of the driver.
In GAC indicates whether the module (assembly) was loaded from the
Global Assembly Cache (GAC).
Runtime is the version of the Common Language Runtime (CLR) the driver was built against.
Copyright indicates the copyright information of the protocol driver.
The Modbus/USB protocol specifies a Universal Serial Bus (USB) connection between SCADAPack controllers equipped with a USB peripheral port and the PC.
Windows NT does not support USB. The Modbus/USB selection will be displayed but it will not work with Windows NT. This is a limitation of the
Windows NT operating system.
Realflo User and Reference Manual
May 19, 2011
519
Realflo Expert Mode Reference
To configure a Modbus/USB protocol connection, highlight
Modbus/USB in the Communication Protocols window and click the
Configure button. The Modbus/USB Configuration window is displayed.
To select a configured Modbus/USB protocol connection, highlight
Modbus/USB in the Communication Protocols window and click the OK button.
To close the dialog, without making a selection click the Cancel button.
General Parameters
When Modbus/USB is selected for configuration the Modbus/USB
Configuration dialog is opened with the General tab selected as shown below.
Realflo User and Reference Manual
May 19, 2011
The Connection Settings grouping presents two options for Modbus/USB connections. These options are Automatic Connection and Connect to
controller with this Controller ID.
Automatic Connection
The Automatic Connection selection enables communication with any single SCADAPack controller equipped with a USB peripheral port. A message, as shown below, is displayed when more than one SCADAPack controller is detected on the Bus.
520
Information
Realflo Expert Mode Reference
The Connect to controller with this Controller ID selection enables
Modbus/USB communication to a specific controller regardless of the existence of multiple controllers on the bus. Each SCADAPack controller is uniquely identified through its Controller ID.
The Controller ID list box will display the Controller ID for each controller on the Bus. The Controller ID may be entered in the entry window or selected from the list.
The Restore Defaults button will restore the configuration dialog to the default state. The Automatic Connection option is selected, and the Connect
to controller with this Controller ID selection will be disabled. If text was present in the Controller ID window when the button is pressed it will be displayed in grey.
Information displays detailed driver information. When the Information tab heading is clicked the Information dialog is opened as shown below.
The Information grouping presents informative details concerning the executing protocol driver.
Module is the physical name of the driver.
File Version is the version number of the driver.
In GAC indicates whether the module (assembly) was loaded from the
Global Assembly Cache (GAC).
Runtime is the version of the Common Language Runtime (CLR) the driver was built against.
Copyright indicates the copyright information of the protocol driver.
SCADAServer
The SCADAServer protocol specifies a SCADAServer Host connection.
Applications will act as an OPC client and route programming commands through the SCADAServer Host to the SCADAPack controller. The type of
Realflo User and Reference Manual
May 19, 2011
521
Realflo Expert Mode Reference connection to the field device: no flow control, hardware flow control or dialup modem is configured in the SCADAServer Host itself.
To configure a SCADAServer protocol connection, highlight
SCADAServer in the Communication Protocols window and click the
Configure button. The SCADAServer Configuration window is displayed.
To select a configured SCADAServer protocol connection, highlight
SCADAServer in the Communication Protocols window and click the
OK button.
To close the dialog, without making a selection click the Cancel button.
General Parameters
When SCADAServer is selected for configuration the SCADAServer
Configuration dialog is opened with the General tab selected as shown below.
The Communication Settings grouping contains details necessary to establish communication to a device through a local or remote
SCADAServer installation.
The Modbus Station parameter specifies the station address of the target device. The valid range is 1 to 65534. The default is station 1.
The Access Path parameter specifies the access path to a SCADAServer connection. This parameter is entered as a string with a maximum size of 16 characters. This access path was named when a connection was defined within the SCADAServer installation. If the access path is left blank, the default SCADAServer connection will be used, as defined within the
SCADAServer installation. The default for this entry is blank.
The Use a remote server check box defines whether the SCADAServer connection uses a SCADAServer installation installed on the same physical
PC as the client application or on a remote PC. If the SCADAServer installation is located on a separate machine, check this option and enter
Realflo User and Reference Manual
May 19, 2011
522
Realflo Expert Mode Reference the host name or IP address of the remote PC into the “IP Address / Name” edit box. If the SCADAServer installation is located on the same PC as the client application leave this box unchecked. The default state for this check box is unchecked.
The IP Address / Name entry specifies the Ethernet IP address in dotted quad notation, or a DNS host name that can be resolved to an IP address, of the PC where the ClearSCADA server is installed. The following IP addresses are not supported and will be rejected:
0.0.0.0 through 0.255.255.255
127.0.0.0 through 127.255.255.255 (except 127.0.0.1)
224.0.0.0 through 224.255.255.255
255.0.0.0 through 255.255.255.255.
Click Restore Defaults to restore default values to fields on this page.
Advanced Parameters
Advanced parameters are used to control the message size for the protocol.
Control over message length is needed when writing large amounts of data over certain communication networks. A larger value can improve communication speed but can increase the number of missing transmissions. A smaller value can reduce the number of missing transmissions but may reduce throughput. When the Advanced tab heading is clicked the Advanced dialog is opened as shown below.
The Message Size grouping parameters are used to control the message size for the protocol. Control over message length is needed when writing large amounts of data over certain communication networks. A larger value can improve communication speed but can increase the number of missing transmissions. A smaller value can reduce the number of missing transmissions but may reduce throughput.
The Maximum selection indicates that the host application is to package messages using the maximum size allowable by the protocol.
Realflo User and Reference Manual
May 19, 2011
523
Information
Realflo Expert Mode Reference
The Custom Value selection specifies a custom value for the message size. This value indicates to the host application to package messages to be no larger than what is specified, if it is possible. Valid values are 2 to 246.
Click Restore Defaults to restore default values to fields on this page.
Information displays detailed driver information. When the Information tab heading is clicked the Information dialog is opened as shown below.
The Information grouping presents informative details concerning the executing protocol driver.
Module is the physical name of the driver.
File Version is the version number of the driver.
In GAC indicates whether the module (assembly) was loaded from the
Global Assembly Cache (GAC).
Runtime is the version of the Common Language Runtime (CLR) the driver was built against.
Copyright indicates the copyright information of the protocol driver.
Connect to Controller Command
The Connect to Controller command starts a dial-up connection to a remote flow computer. To connect to a dial-up flow computer, select Connect to
Controller from the Communication menu. Wait for Realflo to connect to the remote flow computer.
Disconnect from Controller Command
The Disconnect from Controller command terminates a dial-up connection.
To disconnect from a dial-up flow computer select Disconnect From
Realflo User and Reference Manual
May 19, 2011
524
Realflo Expert Mode Reference
Controller from the Communication menu. Wait for Realflo to disconnect with the remote flow computer.
Communication Progress Dialog
The Communication Progress dialog is displayed whenever Realflo is communicating with the flow computer. The dialog indicates the operation being performed and the status of the communication. If a long operation is being performed, a progress bar is displayed as well.
Click on the Cancel button to abort the operation. This is useful if communication is not progressing or if you have initiated the operation in error.
Communication Failures
Communication with the flow computer may fail for one of the following reasons.
The message to the flow computer was garbled or lost by the communication network.
The response from the flow computer was garbled or lost by the communication network.
The flow computer is not connected.
The PC Serial Port Settings are not set correctly.
The flow computer did not respond or responded too late. Setting the time-out value too small in the PC Communications Settings can cause this.
If communication fails a message box appears. You have two options:
Select Retry to attempt the communication again. This is useful when an occasional message is garbled by the communication system.
Select Cancel to abort the command.
Inactive Phone Connection Dialog
The Inactive Phone Connection dialog is displayed when a dial-up phone connection has been inactive for longer than the period set in PC
Communications Settings. The dialog notifies the user that the connection will be terminated.
Click on OK to terminate the connection immediately.
Click on Cancel to stay connected.
Realflo User and Reference Manual
May 19, 2011
525
Realflo Expert Mode Reference
Window Menu
The Window menu contains the commands for opening and arranging windows used in Realflo.
New Window Command
Use this command to create a copy of the currently selected window. You can change the view in the copy of the window so you can look at more than one view at a time.
Cascade Command
Use this command to arrange open, non-minimized windows, so they stack upon each other with an offset so the title bar of each window is visible. All minimized windows are collected at the bottom of the main window.
Tile Command
Use this command to arrange open, non-minimized windows, so that they are visible. Minimized windows are collected at the bottom of the main window.
Arrange All Command
Use this command to arrange icons (minimized windows) at the bottom of the main window.
Open Window List
Use the numbers and file names listed at the bottom of the Window menu to switch to any open window. Choose the number that corresponds with the window you want to activate.
If there are more than nine open windows, the last item in the open window list will be the command More Windows. This will open a dialog with a list box showing open windows.
Realflo User and Reference Manual
May 19, 2011
526
Realflo Expert Mode Reference
Help Menu
Contents Command
Use this command to open the Realflo help file using the Windows Help program. The Contents page of the help file is displayed.
The F1 key on your keyboard will open the Realflo Help file.
The help file has a general description of how the Realflo program operates and how to use the Realflo program. It also has specific descriptions for each view, dialog and command.
About Command
The Help menu contains the commands for opening and using Realflo on line help and for viewing information about Realflo.
Use this command to display information about Realflo.
Realflo User and Reference Manual
May 19, 2011
527
Realflo Wizards
Realflo Wizards
The following sections describe the Realflo Wizards to make the tasks you need to perform easier.
Read Logs and Flow History Wizard
Navigating Wizards
The wizards display four navigation buttons until the final step of the wizard when the Finish button becomes visible. These buttons are:
<Back returns to the previous step in the wizard. This button is disabled on the first step of a wizard.
Next> moves to the next step in the wizard. This button is hidden on the last step of a wizard.
Cancel cancels the operation and closes the wizard. Steps performed thus far in the wizard are cancelled. Pressing the ESC key performs the same action as Cancel.
Help opens the on-line Realflo User and Reference Manual.
Finish is displayed on the final step of a wizard in place of the Next button. It finishes the operation. This button is hidden on other steps.
Create New File Wizard
When the File New command is selected from the Expert Mode >> File
menu >> New or when the Select Flow Computer command is selected from Maintenance Mode main screen, the New File wizard starts.
In Expert Mode, the New File wizard is used to create a new Realflo configuration file. It offers four ways to create a new file.
Read the configuration from the target flow computer.
Create a new configuration from a template file.
Create a new configuration step-by-step.
Create 1-run Configuration with Default Values. (This option is available in Expert Mode only).
When the New File Wizard starts, the Create New File dialog opens.
Realflo User and Reference Manual
May 19, 2011
528
Realflo Wizards
The How do you want to create a new file? selections determine how the new file is created.
Select Read Configuration from the Flow Computer to read the configuration of an existing flow computer. Realflo will connect to the flow computer, read configuration, and save the file.
Follow the wizard steps described in the
section below when this option is selected.
Select Create Configuration from a Template File to create a new configuration file based on a template. A template contains pre-defined settings requiring you to fill in configuration data specific this flow computer.
Select the template file from the dropdown list. The last ten recently used templates are shown. The recently used template is selected by default.
The selection edit box is blank if no recently used templates are available.
Click Browse to choose another template file. A File Open dialog appears which allows you to select any template file.
Select Create Configuration from Template file to use a congiguration
template to create the configuration. To create a template file, see
. When templates are created, some flow computer configuration
parameters are preset and are not displayed in the Create Configuration from Template wizard steps.
Follow the wizard steps described in the
section below when this option is selected.
Select Create Configuration Step-by-Step to create a new configuration file. Realflo will lead you through the steps required using a wizard. You will need to modify the default data at each step.
Follow the wizard steps described in the
Create Configuration Stepby-Step
section below when this option is selected.
Realflo User and Reference Manual
May 19, 2011
529
Realflo Wizards
Select Create 1-run Configuration with Default Values option to create a new configuration file with a default configuration. A file with configuration for a 1-run flow computer, using a 4202 DR is created. You will need to edit the configuration manually.
Once you select the radio button to create 1-run configuration with default values, do the following:
Click Next.
Click Finish.
Read Configuration From the Flow Computer
The Read Configuration from Flow Computer option enables you to connect to the flow computer and read the existing configuration from the flow computer. A communication link needs to exist between Realflo and the flow computer to use this option. The wizard prompts you for default communication settings or allows you to select new communication settings.
When Realflo reads configuration from a 32-bit flow computer, Realflo reads the flowing fields for each flow run:
Differential Pressure default value (see
section)
Static Pressure default value (see
Temperature default value (see
For flow computers not supporting this feature, Realflo reads the following fields for each flow run:
Use Value on Sensor Fail = Last Known Good Value (see
Differential Pressure default value = 0 (see
Static Pressure default value = 0 (see
Temperature default value = 0 (see
When the Read Configuration from Flow Computer option is selected, the
Connect to Flow Computer wizard leads you through the necessary steps.
The sequence of steps to read the configuration from a flow computer is as follows.
Realflo User and Reference Manual
May 19, 2011
530
Realflo Wizards
Flow Computer Status
The flow computer status step selects whether a flow computer is connected to the PC running Realflo.
Select Yes is a flow computer is connected to the PC or select No if no flow computer is connected. The Connect to Flow Computer step following is only displayed if the selection is Yes.
Connect to Flow Computer
The Connect to Flow Computer step defines the communication settings for the connection between the PC running the Realflo application and the target flow computer.
The How do you want to communicate with the flow computer? prompt provides two option.
Realflo User and Reference Manual
May 19, 2011
531
Realflo Wizards
The Use the Current Settings option sets the default communication settings for Realflo. These settings are for the PC that is running Realflo.
(The communication settings for the PC running Realflo and the communication settings in the flow computer need to match).
The default communication settings are:
COM 1 (serial port on the PC)
9600 baud, no parity
8 Data bits
1 Stop bit
The default Modbus address to which Realflo connects is station 1.
Use this selection if the serial port on your PC is COM 1 and the serial port settings for the serial port on the flow computer are set for default (9600,
8,n,1 and Modbus address 1).
Click Next> to begin communication with the flow computer and move to the next step in the wizard.
The Choose/View Communication Setup option opens the PC
Communication Settings dialog as shown below. This allows you to view the default settings and to change the PC communication setting for the type of connection you are using to communicate with the flow computer.
See the section Communication >>
in the Realflo Expert Mode Reference for complete details on
the parameter settings in this dialog.
You need to know the communication settings for the connection to the flow computer to use this step.
Once the communication settings have been selected, click OK> to close the dialog and begin communication with the flow computer.
Read Configuration from the Flow Computer
The Read Configuration from Flow Computer step starts with the Create
New File window as shown below.
Realflo User and Reference Manual
May 19, 2011
532
Realflo Wizards
Click Next> to begin reading the flow computer configuration form the flow computer.
The Communication progress displays the status of the reading of the configuration.
Save Configuration File
Once the configuration has been read from the flow computer, the Save File dialog is opened to prompt for a file name to which save the configuration.
Realflo User and Reference Manual
May 19, 2011
533
Realflo Wizards
Select the Save to Realflo.tfc to save the configuration to the default
Realflo.tfc file. This file will be located in the folder Realflo was installed in.
Click Next> to save the configuration and move to the next step.
Select the Save to another file to save the file to a specified name and location. When this option is selected the Save As dialog is opened as shown below.
Select the folder to save the file in the Save in: window. Use the dropdown selector to browse the available folders on your PC. Enter the file name in the File name: window. The file will automatically be saved with the Realflo
.tfc extension.
Click Save to save the configuration file and close the Save As dialog.
Click Next> to move to the next step.
Realflo User and Reference Manual
May 19, 2011
534
Realflo Wizards
Configuration Complete
The Configuration Complete dialog is the last step in the Read Configuration from Flow Computer wizard.
Click Finish to complete the wizard.
Create Configuration From a Template File
When you choose to configure the flow computer using a template file, the
Create New File wizard prompts you through the steps needed.
Select File >> New from the Realflo command menu.
The Create New File dialog is displayed and the wizard will lead you through the steps to create a congiuration file from a temple.
Create New File Dialog
Select the Create Configuration from a Template File radio button.
Do one of the following:
Realflo User and Reference Manual
May 19, 2011
535
Realflo Wizards o Select the template file from the dropdown list. The last ten recently used templates are shown. The recently used template is selected by default. o Click Browse to choose another template file. A File Open dialog appears which allows you to select any template file.
Click Next > to continue.
Template files are created in the Expert Mode. When templates are created some flow computer configuration parameters are preset and are not displayed in the Create Configuration from Template wizard steps.
Follow the wizard steps described in the following sections to configure the flow computer using the selected template.
Flow Computer Information
Flow Computer Status Dialog
When configuring the flow computer using a template file, select No when the Flow Computer Status dialog opens. This lets you choose the hardware type and firmware type manually.
Hardware and Firmware Type Step
The Hardware and Firmware Type Dialog opens when you select No in the
Flow Computer Status dialog.
First, select the Hardware Type from the dropdown list. The template selected determines the default value when creating the configuration using a template. The options from which you can select are:
Micro16
SCADAPack
SCADAPack Plus
SCADAPack Light
SCADAPack LP
SCADAPack 32
Realflo User and Reference Manual
May 19, 2011
536
Realflo Wizards
SCADAPack 32P
4202 DR
SCADAPack 100: 1024K
4202 DS
SCADAPack 314
SCADAPack 330
SCADAPack 334
SCADAPack 350
4203 DR
4203 DS
SolarPack 410
Second, select the Firmware Type from the dropdown list. The template selected determines the default value (either Telepace or ISaGRAF).
If the firmware selected is Telepace, the I/O Module Type dialog opens, followed by the Flow Computer ID dialog. If the firmware type selected is
ISaGRAF, the Flow Computer ID dialog opens.
I/O Module Type Step
This step selects the I/O module to use for the selected Hardware type. The register assignment in the new file is set to the default register assignment for the selected hardware type.
Select the I/O module for the flow computer from the dropdown list.
Selections displayed in the list depend on the flow computer hardware type.
Hardware Type
Micro16
I/O Modules Available
Controller I/O only or Backwards compatible
Realflo User and Reference Manual
May 19, 2011
537
Hardware Type
SCADAPack
SCADAPack Plus
SCADAPack Light
SCADAPack LP
SCADAPack 32
Realflo Wizards
I/O Modules Available
modules.
5601 I/O Module, 5604 I/O Module, or 5606 I/O
Module
5601 I/O Module, 5604 I/O Module, or 5606 I/O
Module
5602 I/O Module
SCADAPack LP I./O
5601 I/O Module
5604 10V/40mA I/O module
5604 5V/20mA I/O module
, 5604 I/O Module, or 5606 I/O Module
SCADAPack 32P I/O
4202 DR or 4202 DR Extended/4203 DR I/O
SCADAPack 100: 1024K I/O
SCADAPack 32P
4202 DR
SCADAPack 100:
1024K
4202 DS
SCADAPack 314
SCADAPack 330
SCADAPack 334
SCADAPack 350
4203 DR
4203 DS
SolarPack 410
4202/4203 DS I/O
SCADAPack 314/33x I/O
SCADAPack 330 Controller.
SCADAPack 33x I/O
SCADAPack 350 10V/40mA I/O
SCADAPack 350 5V/20mA I/O
4202 DR Extended/4203 DR I/O
4202/4203 DS I/O
Flow Computer ID Step
This step sets the Flow Computer ID.
Type the Flow Computer ID string in the edit box. This unique ID stops accidental mixing of data from different flow computers. The maximum length of the Flow Computer ID is eight characters. Any characters are valid.
You can leave the Flow Computer ID edit box blank.
Realflo User and Reference Manual
May 19, 2011
538
Realflo Wizards
Number of Flow Runs Step
This step selects the number of flow runs in the flow computer. The wizard will step through the configuration of the first run and then each subsequent run if more than one run is selected.
Flow Run ID Step
Select the number of flow runs with the dropdown list. Valid values depend on the hardware type and the number of flow runs enabled for the flow computer. The template determines the default value when using a template.
For Micro16, SCADAPack, SCADAPack Light and SCADAPack Plus
Flow Computers, the maximum number of meter runs is three.
The selection of three meter runs is available for older flow computers that could be enabled for three meter runs.
For SCADAPack LP and SCADAPack (4202 and 4203) Flow
Computers, the maximum number of meter runs is two.
For SCADAPack 100: 1024K and SolarPack 410 Flow Computers, the maximum number of meter runs is one.
For SCADAPack 314/330/334 and SCADAPack 350 Flow Computers the maximum number of meter runs is four.
For SCADAPack 32 and SCADAPack 32P Flow computers the maximum number of runs you can select is ten.
This step sets the Flow Run ID for the meter run. This is the first step of a flow run configuration. The wizard will step you through the flow run configuration steps for the first run and then each subsequent run if you select more than one run.
Realflo User and Reference Manual
May 19, 2011
539
Realflo Wizards
Copy Run Step
The Flow Run ID helps to identify the flow run. Type a string up to 32 characters long. Any characters are valid. You can leave the Flow Run ID edit box blank.
Older flow computers allow a string up to 16 characters. See the TeleBUS
section.
For run 1 the next step is Flow and Compressibility Calculations .
For subsequent runs, the next step is
This step controls how multiple runs are configured once the first run has been configured.
The Step by Step Configuration radio button selects that the run will be configured step by step as was the previous run. Parameters for each step are configured one at a time.
The Copy configuration from radio button selects that the run will be configured the same as the run selected in the drop down window.
Realflo User and Reference Manual
May 19, 2011
540
Realflo Wizards
Flow Calculation Configuration
Flow and Compressibility Calculations Step
This step selects the flow and compressibility calculations for the first run.
Flow Calculation selects the type of flow calculation for the meter run. Valid values are:
AGA-3 (1985 version)
AGA-3 (1992 version)
AGA-7
AGA-11 (not available for 16-bit controllers)
V-cone calculations
The template selected determines the default value.
Compressibility Calculation selects the type of compressibility calculation for the meter run. Valid compressibility calculation values are:
AGA-8 Detailed
NX-19 (Not supported for PEMEX flow computers)
AGA-8 Detailed is the recommended calculation for new systems as it has superior performance compared to NX-19. NX-19 is provided for legacy systems. The template selected determines the default value.
Flow Direction Control selects the direction of flow indication, forward or reverse, for a meter run.
Forward by Value selection indicates the flow direction is forward when the value from a differential pressure (DP) sensor is positive or the mass flow rate value from a Coriolis meter is positive.
Reverse by Value selection indicates the flow direction is reverse when the value from a differential pressure (DP) sensor is negative or the mass flow rate value from a Coriolis meter is negative.
Realflo User and Reference Manual
May 19, 2011
541
Realflo Wizards
Forward by Status selection indicates the flow direction is forward when the Flow Direction Register has a value of 0 (OFF).
Reverse by Status selection indicates the flow direction is reverse when the Flow Direction Register has a value of 1 (ON).
Flow Direction Register specifies which register indicates the forward or reverse flow direction status. Any valid register for the flow computer controller can be used for this setting. The default register is 1. This edit control is disabled if Flow Direction Control selection is Value. This control is hidden in GOST mode flow computers.
Flow Run Units Step
This step lets you select the units that are used for input measurements and contracts.
Input Units selects the units of measurement of input values for the meter run. Inputs may be measured in different units than the calculated results.
This allows you to use units that are convenient to you for measuring inputs.
A dropdown list allows the selection of the following unit types. The template selected determines the default value.
US1
US2
US3
IP
Metric1
Metric2
Metric3
SI
US4
US5
Realflo User and Reference Manual
May 19, 2011
542
Realflo Wizards
US6
US7
US8
PEMEX
The reference list for the Input Units displays the parameters and units for these parameters:
DP (Differential pressure)
SP (Static pressure)
Temperature
Pipe and Orifice Diameter
Viscosity
Altitude
Heating Value
Contract Units selects the units of measurement of contract values. These units are used for the calculated results. A dropdown list allows the selection of the following unit types. The template selected determines the default value.
US1
US2
US3
IP
Metric1
Metric2
Metric3
SI
US4
US5
US6
US7
US8
PEMEX
The reference list for the Contract Units displays the parameters and units for these parameters when used for the contract. The parameters displayed depend on the contract units selected. The parameters are:
Volume
Volume Rate
Energy
Energy Rate
Realflo User and Reference Manual
May 19, 2011
543
Realflo Wizards
Base Pressure
Base Temperature
Mass
Mass Flow Rate
Density
Flow Extension
Heating Value
Flow Run Inputs Step
This step lets you configure the flow run inputs. One of two configuration dialogs is presented based on the input type you configure.
Sensor Inputs
Analog Inputs
Sensor Inputs
Select Internal Sensor (4202 DR/DS or 4203DR/DS or SolarPack 410) to use a SCADAPack internal transmitter as the input device. The transmitter is the input for pressure, differential pressure, and temperature. This is the only valid selection for run 1 of a SCADAPack flow computer. Other options are disabled.
Select Sensor to use a multivariable transmitter as the input device. The transmitter is the input for pressure, differential pressure, and temperature.
This is the default selection, except for run 1 of a SCADAPack controller.
The Where is sensor connected to the Flow Computer parameter enables the ability to select the serial or LAN port where the sensor is connected to the flow computer. Selections vary according to the flowcomputer type. Valid selections can include:
com1
com2
Realflo User and Reference Manual
May 19, 2011
544
Analog Inputs
Realflo Wizards
com3
com4
LAN
The What is the sensor model parameter selects the multivariable transmitter (MVT) type. The selections available are:
3095FB
4101
4102
4202 DR
4202 DS
4203 DR
4203 DS
The What value should be used if the sensor fails parameter selects the specified value in this field as the live input value when communicating with a sensor. The dropdown list lets you select:
Use Last Known Good Value
Use Default Value
When you open a file using an older file format, Realflo sets the default value of the Values on Sensor Fail field to Use Last Known Good.
When the status to a sensor changes and you select the Use Default Value option, this is added to the Event Log.
For flow computers 6.70 and later, when communication to a sensor fails and the configuration option “Use Last Known Good Value” is set to
“Use Default Value,” the flow computer needs to use the specified default value in the configuration in place of a live input value.
When communication to a sensor is restored and the configuration option for the Value on Sensor Fail field is set to use the default value, the flow computer uses the input value from the sensor as the live input value.
For flow computers prior to 6.70, the value on sensor fail is ``Use Last
Known Good Value.”
Select Analog Inputs to use analog inputs to measure pressure, differential pressure, and temperature.
Valid values are:
Telepace Integer
ISaGRAF Integer
Float
Raw Float
The template selected determines the default value displayed.
Realflo User and Reference Manual
May 19, 2011
545
Realflo Wizards
For AGA-7 calculations, the value is fixed and set automatically. The value is Telepace Long if Telepace firmware is running, otherwise it is an
ISaGRAF integer if ISaGRAF firmware is running.
The next step is Differential Pressure Settings if AGA-3 or V-Cone is configured.
The next step is Turbine Settings if AGA-7 is configured.
Differential Pressure Limits Step
This step lets you configure the differential pressure input limits. One of two configuration dialogs is presented based on the input type you configure.
Sensor Inputs
Analog Inputs
Sensor Inputs
Input Type is a read-only field that identifies the sensor number for which you are setting the parameters using this dialog.
Units are the differential pressure units. Values read from the transmitter are in these units. If the transmitter has a local display, the transmitter uses these units. Valid values depend on the MVT type:
For SCADAPack transmtters, valid units are: inches H2O at 68°F,
Pascal (Pa) and kiloPascal (kPa). The default is inches H2O at 68°F.
For the 3095 MVT valid units are: inches H2O at 60°F, Pascal (Pa), kiloPascal (kPa) and inches H2O at 68°F. The default is inches H2O at
60°F.
Damping is the response time of the transmitter. It is used to smooth the process variable reading when there are rapid input variations.
For SCADAPack transmitters the valid values are 0.0 (damping off), 0.5,
1.0, 2.0, 4.0, 8.0, 16.0, and 32.0 seconds. The template selected determines the default value displayed.
For the 3095 MVT the valid values are 0.108, 0.216, 0.432, 0.864, 1.728,
3.456, 6.912, 13.824 and 27.648. The default is 0.864.
Realflo User and Reference Manual
May 19, 2011
546
Analog Inputs
Realflo Wizards
Lower Operating Limit (LOL) is the lowest valid value from the sensor and needs to be less than the UOL. Alarms occur if the value is less than the
LOL. The template selected determines the default value displayed. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Upper Operating Limit (UOL) is the highest valid value from the sensor and needs to be greater than the LOL. Alarms occur if the value is greater than the UOL. The template selected determines the default value displayed. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Low DP Cutoff is the differential pressure where flow accumulation will stop and needs to be less than the UOL. The template selected determines the default value displayed. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Low DP Hysteresis is the amount by which the differential pressure needs to rise above the Low DP Cutoff for flow accumulation to start. It may be a value using the DP units or may be a percentage of the operating span. The operating span is the difference between the Upper Operating Limit and the
Lower Operating limit. Values depend on the transmitter. The flow accumulation level needs to be less than the Upper Operating Limit. The template selected determines the default value displayed.
Default Value is enabled if you configured the field using the Flow Run
Inputs dialog. Type the live input value to use when communicating with a sensor. The template selected determines the default value displayed.
If you configured sensor inputs, go to the
The dialog below opens when analog inputs are selected.
Input Type is a read-only field that identifies the input type for which you are setting the parameters using this dialog.
Input Register is the register address where the input value is stored. Valid values are 30001 to 39999 or 40001 to 49999. The default is selected based on the run number so that inputs have unique registers.
Realflo User and Reference Manual
May 19, 2011
547
Realflo Wizards
Input at Zero Scale is value read from the sensor, in unscaled I/O units, when the sensor is at zero scale. Valid values depend on the input type. The template selected determines the default value displayed. This is enabled for Telepace integer, raw float and ISaGRAF integer types and disabled otherwise.
Input at Full Scale is value read from the sensor, in unscaled I/O units, when the sensor is at full scale. Valid values depend on the input type. The template selected determines the default value displayed. This is enabled for Telepace integer, raw float and ISaGRAF integer types and disabled otherwise.
DP at Zero Scale is the pressure that corresponds to the zero scale input, or if the input does not require scaling, the minimum pressure that can be read from the sensor. Valid values depend on the input type. The template selected determines the default value displayed.
DP at Full Scale is the pressure that corresponds to the full-scale input, or if the input does not require scaling, the maximum pressure that can be read from the sensor. Valid values depend on the input type. The template selected determines the default value displayed.
Low DP Cutoff is the differential pressure where flow accumulation will stop and needs to be less than the UOL. The template selected determines the default value displayed. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Low DP Hysteresis is the amount by which the differential pressure needs to rise above the Low DP Cutoff for flow accumulation to start. It may be a value using the DP units or may be a percentage of the operating span. The operating span is the difference between the Upper Operating Limit and the
Lower Operating limit. Values depend on the transmitter. The flow accumulation level needs to be less than the Upper Operating Limit. The template selected determines the default value displayed.
Turbine Limits Step
This step configures the turbine input for AGA-7 calculations.
Input Register is the register address where the input value is stored. Valid values are 30001 to 39999 or 40001 to 49999. The default is selected based on the run number so that inputs have unique registers.
Realflo User and Reference Manual
May 19, 2011
548
Realflo Wizards
Low Flow Pulse Limit is the number of pulses below which a low flow alarm will occur. The template selected determines the default value displayed.
Low Flow Detect Time is the length of time the number of pulses needs to remain below the Low Flow Pulse Limit for a low flow alarm to occur. Valid values are 1 to 5 seconds. The template selected determines the default value displayed.
Static Pressure Measurement Step
This step lets you select how the static pressure is measured.
The pressure tap may be upstream or downstream of the orifice plate for
AGA-3.
Select Up Stream for an upstream static pressure tap. This is the default value. The control is disabled for AGA-7 and V-Cone calculations.
Select Down Stream for a downstream static pressure tap. The control is disabled for AGA-7 and V-Cone calculations.
Static Pressure Input Limits Step
This step lets you define the limits for the static pressure input. One of two configuration dialogs is presented based on the Input Type configured for static pressure limits:
Sensor Inputs
Analog Inputs
Sensor Inputs
The dialog below is presented when sensor inputs are used.
Realflo User and Reference Manual
May 19, 2011
549
Realflo Wizards
Input Type is a read-only field that identifies the sensor number for which you are setting the parameters using this dialog.
Units is the differential pressure units. Values read from the transmitter are in these units. If the transmitter has a local display it uses these units. Valid values are kiloPascal, MegaPascal, and psi (pounds per square inch). The default is psi.
Damping is the response time of the transmitter. It is used to smooth the process variable reading when there are rapid input variations.
For SCADAPack transmitters the valid values are 0.0 (damping off), 0.5,
1.0, 2.0, 4.0, 8.0, 16.0, and 32.0 seconds. The template selected determines the default value displayed.
For the 3095 MVT the valid values are 0.108, 0.216, 0.432, 0.864,
1.728, 3.456, 6.912, 13.824 and 27.648. The default is 0.864.
Lower Operating Limit (LOL) is the lowest valid value from the sensor and needs to be less than the UOL. Alarms occur if the value is less than the
LOL. The template selected determines the default value displayed. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Upper Operating Limit (UOL) is the highest valid value from the sensor and needs to be greater than the LOL. Alarms occur if the value is greater than the UOL. The template selected determines the default value displayed. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Default Value is enabled if you gage pressure using the Static Pressure
Options. Type the live input value to use when communicating with a sensor. The template selected determines the default value displayed.
The pressure sensor may measure absolute or gage pressure.
Select Absolute Pressure to measure absolute static pressure.
Select Gage Pressure to measure gage static pressure.
Type the Atmospheric Pressure measured at the site. This control is disabled and set to zero if absolute pressure is selected.
Realflo User and Reference Manual
May 19, 2011
550
Realflo Wizards
The atmospheric pressure entered needs to be greater than zero. The maximum upper limits for atmospheric pressure are:
30 psi and PEMEX units
4320
207 for US1, US2, US3, US4, US5, US6, US7, US8, lbf/ft2 for IP units kPa for Metric1 units
2.07
0.207 bar for Metric2 units
MPa for Metric3 units
207000 Pa for SI units
If you configured sensor inputs, see the Static Pressure Compensation
section.
Analog Inputs
The dialog below is presented when analog inputs are used.
Input Type is a read-only field that identifies the input type for which you are setting the parameters using this dialog.
Input Register is the register address where the input value is stored. Valid values are 30001 to 39999 or 40001 to 49999. The default is selected based on the run number so that inputs have unique registers.
Input at Zero Scale is value read from the sensor, in unscaled I/O units, when the sensor is at zero scale. Valid values depend on the input type. The template selected determines the default value displayed. This is enabled for Telepace integer, raw float, and ISaGRAF integer types and disabled otherwise.
Input at Full Scale is value read from the sensor, in unscaled I/O units, when the sensor is at full scale. Valid values depend on the input type. The template selected determines the default value displayed. This is enabled for Telepace integer, raw float and ISaGRAF integer types and disabled otherwise.
SP at Zero Scale is the pressure that corresponds to the zero scale input, or if the input does not require scaling, the minimum pressure that can be
Realflo User and Reference Manual
May 19, 2011
551
Realflo Wizards read from the sensor. Valid values depend on the input type. The template selected determines the default value displayed.
SP at Full Scale is the pressure that corresponds to the full-scale input, or if the input does not require scaling, the maximum pressure that can be read from the sensor. Valid values depend on the input type. The template selected determines the default value displayed.
Static Pressure Compensation Step
This step selects if compensation is applied for the location where calibration was performed. If you configured sensors or analog inputs from the Static Pressure Limits dialog, this is the next step in the configuration sequence.
Select No if compensation is not required. This is the default value.
Select Yes to compensate for the altitude and latitude.
Type the Altitude of the location. Valid values are
–30000 to 30000.
The template selected determines the default value displayed. This control is disabled if No is selected.
Type the Latitude of the location. Valid values are
–90 to 90. The template selected determines the default value displayed. This control is disabled if No is selected.
Temperature Limits Step
This step defines the limits for the temperature input. One of two configuration dialogs is presented based on the Input Type configured for static pressure limits:
Sensor Inputs
Analog Inputs
Sensor Inputs
The following dialog is presented when sensor (MVT) inputs are used.
Realflo User and Reference Manual
May 19, 2011
552
Realflo Wizards
Analog Inputs
Input Type is a read-only field that identifies the sensor number for which you are setting the parameters using this dialog.
Units is the differential pressure units. Values read from the transmitter are in these units. If the transmitter has a local display it uses these units. Valid values are kiloPascal, MegaPascal, and psi (pounds per square inch). The default is psi.
Lower Operating Limit (LOL) is the lowest valid value from the sensor and needs to be less than the UOL. Alarms occur if the value is less than the
LOL. The template selected determines the default value displayed. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Upper Operating Limit (UOL) is the highest valid value from the sensor and needs to be greater than the LOL. Alarms occur if the value is greater than the UOL. The template selected determines the default value displayed. Valid values depend on the transmitter; refer to the transmitter band or user manual.
The following dialog is presented when analog inputs are used.
Realflo User and Reference Manual
May 19, 2011
553
Realflo Wizards
Input Type is a read-only field that identifies the input type for which you are setting the parameters using this dialog.
Input Register is the register address where the input value is stored. Valid values are 30001 to 39999 or 40001 to 49999. The default is selected based on the run number so that inputs have unique registers.
Input at Zero Scale is value read from the sensor, in unscaled I/O units, when the sensor is at zero scale. Valid values depend on the input type. The template selected determines the default value displayed. This is enabled for Telepace integer, raw float and ISaGRAF integer types and disabled otherwise.
Input at Full Scale is value read from the sensor, in unscaled I/O units, when the sensor is at full scale. Valid values depend on the input type. The template selected determines the default value displayed. This is enabled for Telepace integer, raw float and ISaGRAF integer types and disabled otherwise.
Temperature at Zero Scale is the temperature that corresponds to the zero scale input, or if the input does not require scaling, the minimum pressure that can be read from the sensor. Valid values depend on the input type.
The template selected determines the default value displayed.
Temperature at Full Scale is the temperature that corresponds to the fullscale input, or if the input does not require scaling, the maximum pressure that can be read from the sensor. Valid values depend on the input type.
The template selected determines the default value displayed.
Contract Settings Step
This step lets you set the contract settings for the run.
Realflo User and Reference Manual
May 19, 2011
554
Realflo Wizards
Input Average Weighting is the weighting method of the linear inputs. This applies to the differential pressure, static pressure, and temperature. Valid
values are time-weighted or flow-weighted (see Input Averaging on page
948 for more information). The template selected determines the default
value.
Contract Hour is the hour of the day that starts a new contract day using a
24-hour clock. The contract day begins at 00 minutes and 00 seconds of the specified hour. Valid values are 0 to 23. The template selected determines the default value displayed.
Standard Base Conditions are the default Base Temperature and Base
Pressure (absolute) values.
Base Temperature is the reference temperature to which contract flow values are corrected. Valid values are
–40 to 200. The default value is given in the table below.
Base Pressure is the reference pressure to which contract flow values are corrected. The base pressure is measured as absolute pressure
(not a gauge pressure). Valid values are 0 to 32000. The default value is given in the table below.
Contract Units Standard Base
Temperature
US1
US2
US3
IP
Metric1
Metric2
Metric3
SI
US4
US5
US6
US7
60 F
60 F
60 F
60 F
15 C
15 C
15 C
288.15 K
60 F
60 F
60 F
60 F
Standard Base
Pressure
14.73 psi
14.73 psi
14.73 psi
2116.2281 lbf/ft
2
101.325 kPa
1.01325 bar
0.101325 MPa
101325 Pa
14.73 psi
14.73 psi
14.73 psi
14.73 psi
Realflo User and Reference Manual
May 19, 2011
555
Realflo Wizards
Contract Units Standard Base
Temperature
US8
PEMEX
60 F
60 F
Standard Base
Pressure
14.73 psi
14.73 psi
Realflo for PEMEX flow computers provide a second set of base conditions.
PEMEX Base Conditions are the default Base Temperature and Base
Pressure (absolute) values when Realflo is operating in PEMEX mode.
Base Temperature is the reference temperature to which contract flow values are corrected. The default is listed in the table below for each type of contract unit.
Base Pressure is the reference pressure to which contract flow values are corrected. The base pressure is measured as absolute pressure
(not a gauge pressure). Valid values are 0 to 32000. The default values are listed in the table below for each contract unit.
Contract Units Standard Base
Temperature
US1
US2
US3
IP
Metric1
Metric2
60 F
60 F
60 F
60 F
15 C
15 C
Metric3
SI
US4
US5
US6
US7
US8
PEMEX
15 C
288.15 K
60 F
60 F
60 F
60 F
60 F
68 F
Standard Base
Pressure
14.73 psi
14.73 psi
14.73 psi
2116.2281 lbf/ft
2
101.325 kPa
1.01325 bar
0.101325 MPa
101325 Pa
14.73 psi
14.73 psi
14.73 psi
14.73 psi
14.73 psi
14.73 psi
AGA-3 Settings Step
This step sets the AGA-3 calculation parameters.
Realflo User and Reference Manual
May 19, 2011
556
Realflo Wizards
Orifice Material is the material from which the orifice plate for the meter run is made. Valid values are Stainless Steel, Monel, and Carbon Steel. The template selected determines the default value displayed.
Pipe Material is the material from which the meter run pipe is made. Valid values are Stainless Steel, Monel, and Carbon Steel. The template selected determines the default value displayed.
Orifice Diameter is the diameter of the meter run orifice. The template selected determines the default value displayed.
Orifice reference temperature is the temperature at which the diameter of the meter run orifice was measured. The template selected determines the default value displayed.
Pipe Diameter is the measurement of the meter run pipe inside diameter.
The template selected determines the default value displayed.
Pipe reference temperature is temperature at which the meter run pipe diameter was measured. The template selected determines the default value displayed.
Beta Ratio is the ratio of orifice diameter to pipe diameter. It is displayed for information purposes only and cannot be edited.
Realflo displays messages if the beta ratio is outside recommended limits.
Isentropic Exponent is a thermodynamic property of gas used to predict the relationships between pressure, temperature, volume and energy. If you are unsure of this value, a typical value of 1.3 is commonly used. The template selected determines the default value displayed.
Viscosity is a measure of the resistance of a measured gas to flow. Valid values are 0 to 1. The template selected determines the default value displayed.
AGA-3 Deadband Settings Step
This step sets AGA-3 calculation deadbands.
Realflo User and Reference Manual
May 19, 2011
557
Realflo Wizards
Temperature Deadband is the tolerated change in the flowing temperature before temperature dependent factors in the flow calculation are recalculated. Changes in the temperature smaller than the deadband will be ignored in determining the result. The template selected determines the default value displayed. The upper limit is 7°F or 4°C.
Static Pressure Deadband is the tolerated change in the static pressure before static pressure dependent factors in the flow calculation are recalculated. Changes in the static pressure smaller than the deadband will be ignored in determining the result. A static pressure deadband setting of up to four percent of the typical static pressure level should have a small effect on the accuracy of the AGA-3 calculation. The template selected determines the default value displayed. The upper limit is 800 psi or 5500 kPa or the equivalent in other units.
Differential Pressure Deadband is the tolerated change in the differential pressure before differential pressure dependent factors in the flow calculation are recalculated. Changes in the differential pressure smaller than the deadband will be ignored in determining the result. A change of N in the differential pressure input will cause a change of 0.5 N in the calculation volume at base conditions. It is recommended that the differential pressure deadband be set to zero. The template selected determines the default value displayed. The upper limit is 4.5 inWC or 1.1 kPa or the equivalent in other units.
AGA-7 Settings Step
This step lets you define the AGA-7 settings.
Realflo User and Reference Manual
May 19, 2011
558
Realflo Wizards
K Factor is the number of pulses per unit volume of the turbine meter. Valid values are 0.001 to 1000000. The template selected determines the default value displayed.
M Factor is the adjustment to the number of pulses per unit volume for the turbine meter compared to an ideal meter. Valid values are 0.001 to 1000.
The template selected determines the default value displayed.
*Uncorrected Flow Volume is the measurement of the volume of gas during the contract period.
The Uncorrected Flow Volume control is available in Realflo versions 6.20 and higher.
AGA -11 Configuration Step
AGA-11 configuration defines parameters unique to the AGA-11 calculation.
The AGA-11 calculation communicates with a Coriolis meter for the calculation. The AGA-11 configuration sets the communication parameters for communication between the Coriolis meter and the flow computer.
Address
This is the Modbus address of the Coriolis Meter for serial communications.
Multiple Coriolis meters using the same serial port on the flow computer
Realflo User and Reference Manual
May 19, 2011
559
Realflo Wizards needs to each have a unique Modbus address. Valid Modbus addresses are between 1 and 247. The default address is 247.
Port
This is the communication port on the flow computer that will be used to communicate with the Coriolis meter. Valid port selections depend on the type of controller the flow computer running on. The default port is the first valid port available on the controller.
Timeout
This is the time the flow computer will wait for a response for Modbus read commands send to the Coriolis meter. When the timeout time is exceeded the command is unsuccessful and an alarm is added to the flow computer alarm list. Valid timeout values are from 0 to 1000 ms. The default value is
50 ms.
V-Cone Settings Step
V-Cone Configuration defines parameters unique to the V-Cone calculation.
Cone Material
This is the material of the V-cone. Valid values are Carbon Steel, Stainless
304, and Stainless 316. The default value is determined by the template selected.
Pipe Material
This is the material from which the meter run pipe is made. Valid values are
Carbon Steel, Stainless 304, and Stainless 316. The default value is determined by the template selected.
Adiabatic Expansion Factor
The Adiabatic Expansion Factor drop down list selects which calculation is used for the adiabatic expansion factor of the calculation.
Select Legacy Calculation to use the older calculation method. This is the default selection. Flow computers prior to version 6.71 support only this selection.
Realflo User and Reference Manual
May 19, 2011
560
Realflo Wizards
Select V-Cone to use the V-Cone specific calculation. This selection should be used with V-Cone devices.
Select Wafer-Cone to use the Wafer-Cone specific calculation. This selection should be used with Wafer-Cone devices.
This control is disabled and forced to Legacy Calculation if the controller type is not one of SCADAPack 32, SCADAPack 32P, SCADAPack
314/330/334, SCADAPack 350 SCADAPack 4203 or SolarPack 410.
When reading from a flow computer that does not support the adiabatic expansion factor configuration, the method will be set to Legacy Calculation.
When writing to a flow computer that does not support the adiabatic expansion factor method, the configuration registers will be ignored and the expansion factor will not be written.
Cone Diameter
The diameter of the meter run cone used for the flow calculation. The measurement units are displayed depending on the input units selected.
The default value is 3 inches.
Cone Measurement Temperature
This is the reference temperature at which the cone diameter for the meter run was measured. The measurement units are displayed depending on the input units selected. The default value is 59 degrees F.
Pipe Inside Diameter
This is the measurement of the meter run pipe inside diameter. The measurement units are displayed depending on the input units selected.
The default value is 5 inches.
Pipe reference temperature
The temperature at which the meter run pipe diameter was measured. The measurement units are displayed depending on the input units selected.
The default value is 59 degrees.
Isentropic Exponent
In general, this is a thermodynamic property of gas used to predict the relationships between pressure, temperature, volume and energy. If you are unsure of this value a typical value of 1.3 is commonly used. The default value is 1.3.
Viscosity
This is the viscosity of the measured gas. In general, this is the resistance of a gas or semi-fluid resistance to flow. The measurement units are displayed depending on the input units selected. Valid values are 0 to 1. The default value is 0.010268 centiPoise.
Wet Gas Correction Factor
The Wet Gas Correction Factor Method drop down list selects which calculation is used for the wet gas correction factor of the calculation.
Select Legacy Method to use the older correction method. This is the default selection. Flow computers prior to version 6.73 support only this selection.
Realflo User and Reference Manual
May 19, 2011
561
V-Cone Coefficients
Realflo Wizards
Select V-Cone or Wafer Cone to use the V-Cone and Wafer Cone specific calculation. This selection should be used with V-Cone or Wafer
Cone devices.
This control is disabled and forced to Legacy Calculation if the controller type is not one of SCADAPack 32, SCADAPack 32P, SCADAPack
314/330/334, SCADAPack 350 SCADAPack 4203 or SolarPack 410.
The V-Cone or Wafer Cone supported Beta Ratios are:
For Fr (Froude Number) < 5 supported Beta Ratio is 0.55.
For Fr (Froude Number) < 5 supported Beta Ratio is 0.75.
For Fr (Froude Number) > 5 supported Beta Ratio is 0.75.
When V-Cone or Wafer Cone is selected and if the current Beta ratio is not supported when executing verification, a message is displayed.
When V-Cone or Wafer Cone is selected, configuration of the fixed wet gas factor parameter, as set in the Contract tab, is disabled.
When Legacy Method is selected, configuration of the parameters used by the V-Cone or Wafer Cone method is disabled.
Mass Flow Rate of Liquid
The Mass flow rate of liquid at flow conditions parameter is used by the V-
Cone or Wafer Cone method and can be configured when V-Cone or Wafer
Cone is selected. This information needs to be gathered using a sampling method or a tracer method. The default is 0.
Density of Liquid
The Density of liquid at flow conditions parameter is used by the V-Cone or
Wafer Cone method and can be configured when V-Cone or Wafer Cone is selected. The default is 0.
This step defines the V-Cone coefficients.
Enter the V-Cone coefficient pairs from the meter-sizing report. The default list contains one pair: Re = 1000000; Cf = 0.82.
Click Add to add a coefficient pair.
Realflo User and Reference Manual
May 19, 2011
562
Realflo Wizards
In the original McCrometer V-Cone Application Sizing sheet that is included with V-Cone meters uses the terminology Cd (discharge coefficient) rather than Cf (flow coefficient). You will need to use the Re and Cd values from the V-Cone Application Sizing sheet for the Re and Cf entries. If the Re value is the same for all entries in the table only the first pair is used.
McCrometer now supplies one value of Cd in the sizing document. You need to enter one Re/Cd pair only. See the McCrometer Application Sizing sheet for the Re/Cd pair for your meter.
To edit a coefficient pair in the table:
Select a row in the list.
Click Edit to open the Add/Edit Flow Coefficient dialog.
To delete a coefficient pair in the table:
Select a row in the list.
Click Delete to delete the pair form the list.
AGA-8 Options Step
This step sets AGA-8 calculation options.
Events can be logged each time an AGA-8 gas component changes.
Select Yes to log each change to the gas composition. Use this option if the gas composition changes infrequently. This is the default selection.
Select No to skip logging changes. Use this option if you are making frequent changes to the gas composition.
The Relative Density and Heating values can be calculated from the AGA-8 calculation or determined in a laboratory.
Realflo User and Reference Manual
May 19, 2011
563
Realflo Wizards
Select Calculate the Values to have AGA-8 calculate the values.
Select Use Laboratory Values to used fixed values.
Relative Density sets the real relative density of the gas. Valid values are
0.07 to 1.52. The template selected determines the default value displayed.
This control is disabled if Calculate the Values is selected.
Heating Value sets the heating value of the gas. Valid values are 0 to 1800
BTU(60)/ ft
3
or the equivalent in the selected units. The template selected determines the default value displayed. This control is disabled if Calculate
the Values is selected.
AGA-8 Hexanes+ Options
This step lets you choose to enter Hexane and higher components individually or as a single combined value.
Gas composition can be measured with individual values for hexane and higher components or use a combined value.
Select Enter Each Component to use individual values for the higher components. This is the default selection.
Select Use Combined Hexanes+ with these Ratios to use a combined value. Type the ratios of the higher components.
n-Hexane defines the percentage of the Hexanes+ contributed by n-
Hexane.
n-Heptane defines the percentage of the Hexanes+ contributed by n-
Heptane.
n-Octane defines the percentage of the Hexanes+ contributed by n-
Octane.
n-Nonane defines the percentage of the Hexanes+ contributed by n-
Nonane.
n-Decane defines the percentage of the Hexanes+ contributed by n-
Decane.
Realflo User and Reference Manual
May 19, 2011
564
Realflo Wizards
The Total field displays the sum of portions. This value cannot be edited. The total of portions needs to be 100 percent.
AGA-8 Gas Composition Step
This step lets you define the AGA-8 gas composition. One of two configuration dialogs opens based on how you elected to enter Hexane and higher components.
Individual Components
The dialog below lets you enter combined Hexanes+ composition.
NX-19 Settings
Type the gas composition according to the laboratory analysis. The total of components needs to be 100 percent.
Normalize adjusts non-zero components so that the total of components is
1.0000 (or 100.00 percent). The ratio to each other for the components remains the same.
This step defines the NX-19 calculation. This is not supported for PEMEX flow computers.
Realflo User and Reference Manual
May 19, 2011
565
Realflo Wizards
Specific Gravity is the specific gravity of the gas being measured. Valid values are 0.554 to 1.000. The template selected determines the default value displayed.
Carbon Dioxide is the percent of carbon dioxide in the gas being measured. This value needs to be in the range 0 to 15. The template selected determines the default value displayed.
Nitrogen is the percent of nitrogen in the gas being measured. This value needs to be in the range 0 to 15.
Heating Value is the heating value of the gas being measured. Valid values are 0 to 1800 BTU(60)/ft
3
or the equivalent in the selected units. The template selected determines the default value displayed.
Events can be logged each time the NX-19 configuration changes.
Select Yes to log each change to the configuration. Use this option if the configuration changes infrequently. This is the default selection.
Select No to skip logging changes. Use this option if you are making frequent changes to the configuration.
Sensor Configuration
The next step is Sensor Configuration if any transmitters were used in the
input configuration. Otherwise the next step is
Sensor Configuration
This step lets you select how the transmitters are to be configured.
Realflo User and Reference Manual
May 19, 2011
566
Realflo Wizards
The Flow Runs are configured to use these transmitters dialog is a table that shows each of the configured flow run numbers, the Flow Run ID for each, and the transmitter that the run uses for the differential pressure (DP), static pressure (SP), and temperature sensors. If an analog input is used for the flow run, AIN will be displayed in the coresponding DP, SP, or Temp column.
The How do you want to configure sensors? option lets you select how to continue configuring the sensors. The three options are:
Connect now and configure transmitters to connect to the flow computer and configure the attached transmitters. This selection is disabled if the flow computer configuration was selected to be completed offline in the Flow Computer Status step. If you choose this
option, go to the Configure Sensors
section to continue.
Edit sensor configuration without connecting to proceed directly to the editing pages, without connecting to the flow computer. If you
Use default sensor configuration to complete the configuration without changing the sensor configuration. Sensor configuration will be
set to default values. If you choose this option, the next step is
Configure Sensors
This step lets you select to use the Realflo configuration or the sensor‟s configuration file.
Realflo User and Reference Manual
May 19, 2011
567
Realflo Wizards
Sensor Search
Select Use the configuration from Realflo to use the configuration data from the Realflo file. This is the default setting.
Select
Use the transmitter’s current configuration by reading from the
transmitter to read configuration from a pre-configured transmitter.
This step searches for sensors connected to the flow computer serial ports or LAN port.
Search Serial Option
Select Search Serial to search for transmitters connected to a serial port of the flow computer.
Realflo User and Reference Manual
May 19, 2011
568
Realflo Wizards
The Port parameter selects the flow computer serial port where the sensor is attached. Valid values are com1, com2, com3, and com4. The template selected determines the default value displayed.
The Timeout parameter specifies the length of time the flow computer will wait for a response from a sensor. Valid values are 100 ms to 10000 ms.
The default is 300 ms.
Select Maximum to search for a number of MVT transmitters. The search operation will stop after finding the specified number of transmitters. The valid value is from 1 to 255. The default is 1.
Select Range to search the addresses in a specified range. The range to search for is typed in the edit boxes to the right of the radio button. The value in To edit control needs to be equal or great than the value in the first edit control. The maximum search range that can be typed is for 255 transmitters. The default range is 1 to 247.
Range Search supports addresses 1 to 255 in standard Modbus mode, and 1 to 65534 in extended address mode. The address mode of the flow computer serial port needs to be set to extended in order to search for transmitters with extended addresses.
Select All to search the addresses of all transmitters connected with the serial port selected in Port. Up to 255 addresses are searched.
Click Next to start the search for sensors or 4000 transmitters. A search process dialog is displayed so that the search operation can be cancelled at any time.
Search LAN Option
Select Search LAN to search for transmitters connected to a LAN port of the flow computer.
The IP Address parameter specifies the IP address of a 4000 transmitter.
Valid entries are IP addresses in the format nnn.nnn.nnn.nnn where nnn are values between 0 and 255.
The Protocol parameter selects the type of IP protocol that will be used to query the transmitter. Valid IP protocol selections are Modbus/TCP and
Modbus RTU in UDP.
The IP port (for example port 502) for the selected protocol needs to be the same in the flow computer and the 4000 transmitter.
The Timeout parameter specifies the length of time the flow computer will wait for a response from a 4000 transmitter. Valid values are 100 to 10000 milliseconds. The default is 5000 ms.
Click Next to start the search for MVT transmitters or 4000 transmitters. A search process dialog is displayed so that the search operation can be cancelled at any time.
If no transmitters were found, then a message is displayed and the search step is displayed again.
Assign Sensors
This step assigns found transmitters to flow runs.
Realflo User and Reference Manual
May 19, 2011
569
Realflo Wizards
The Available Sensors window shows the transmitters that have been configured and the transmitters that were found by the search. There may be more transmitters in the list than there are runs.
The Sensor column shows the transmitter slots that have been configured.
Transmitters that were found but not assigned are listed as Not assigned.
The Status column indicates if configuration data for the transmitter exists.
Found indicates a transmitter has been configured and the search found one with the same port, address and device type.
Missing means a transmitter has been configured but the search did not find one with the same port, address and device type.
The Port column displays the serial or LAN port the flow computer is using to communicate with the transmitter.
The Address column displays the Modbus station address or IP address of the transmitter.
The Tag column displays the Tag Name assigned to the transmitter. This column may be blank if a Tag Name has not been assigned to the transmitter.
The Device type column displays type of transmitter. Valid values are
3095FB, 4101, 4102, 4202 DR, 4202 DS, 4203 DR, or 4203 DS.
The Flow Runs window shows which MVTs are assigned to the runs.
To Change the order of the sensors:
Select a sensor in Available Sensors window.
Click Move.
The Move Sensor dialog opens:
Realflo User and Reference Manual
May 19, 2011
570
Realflo Wizards
In the Move Sensor dialog, use Move To selection to select the new location
Click OK.
To delete a sensor:
Select a transmitter in Available Sensors
Click Delete.
To change the address of a Sensor:
Select a transmitter in Available Sensors
Click Change Address.
The Change Address dialog opens:
Enter a new address for the transmitter in the New Address: window.
Click OK.
Click Next when the transmitters are moved to the correct location. Next is disabled if there are Not Assigned transmitters still in the list.
The next step is Search for More Transmitters.
Notes
The following actions may occur when moving a Sensor.
Moving one sensor to another results in the both swapping positions.
When Use the configuration from Realflo was selected, assigning a Not
assigned transmitter to a Sensor with status Missing and device type matching will result in the sensor adopting the transmitter‟s port and address and retaining the rest of the sensor configuration. The sensor, being assigned, will disappear from the list.
When Read the configuration from the transmitter was selected, assigning a Not assigned transmitter to a sensor with status Missing and device type matching will result in the sensor adopting the transmitter‟s configuration. The transmitter, being assigned, will disappear from the list.
Assigning a Not assigned transmitter to a sensor with status Missing and device type not matching will result in the sensor adopting the
Realflo User and Reference Manual
May 19, 2011
571
Realflo Wizards transmitter‟s configuration. The transmitter, being assigned, will disappear from the list.
Other assignments are not permitted.
Search for More Sensors
This step displays the current sensor assignments and asks if more searches are needed.
Proposed Sensors shows the transmitters that have been configured and the transmitters that were found by the search.
Flow Runs shows which sensors are assigned to the runs.
Select Search for more transmitters to search again. The next step is
Search for Transmitters.
Select Finish searching and review configuration to use the current settings. This is the default button.
Review Transmitters
This step displays the transmitter assignments and allows editing the transmitter configuration.
Realflo User and Reference Manual
May 19, 2011
572
Realflo Wizards
The Sensors window shows the transmitters that have been configured.
The Flow Runs window shows which sensors are assigned to the runs.
Click Edit to review and modify the settings for each transmitter. Edit opens the Add/Edit Sensor Settings dialog. Changes to a transmitter address will be written to the transmitter without affecting current flow computer configuration.
Once you have configured Run 1, the Flow Run ID dialog re-opens.
Flow Computer Configuration Summary
This step displays a summary of the flow computer settings.
A summary of the flow computer configuration is shown.
The current configuration can be compared with the configuration in the target flow computer.
Select Yes to compare the configurations. The next step is Review
Differences.
Realflo User and Reference Manual
May 19, 2011
573
Realflo Wizards
Select No to not compare the configurations. The next step is Save File.
Review Differences
This step displays a summary of changes in the flow computer configuration. You can select to write to the flow computer or not.
Save File
A summary of the differences is the configuration is shown.
Select Yes to write the configuration to the flow computer. The configuration is written to the flow computer. The Start Executing command will be written for each flow run. The communication progress dialog shows the stages of writing.
Select No to write the configuration to the flow computer later.
Click Next to perform the selected action.
In Flow Computer versions 6.73 and older, when AGA-8 gas ratios or NX-19 gas quality values are written to the flow computer the new gas ratios are updated in the Proposed registers. The Actual registers are not updated until a new Density calculation is started with the new values. The new values are not available to SCADA host software reading the Actual registers until a until a new Density calculation is started with the new values.
In Flow Computer versions 6.74 and newer when AGA-8 gas ratios or NX-
19 gas quality values are written to the flow computer the new gas ratios are updated in the Proposed registers and in the Actual registers. This allows a
SCADA host to immediately confirm the new values were written to the flow computer. The new gas values are not used by the flow computer until a new density calculation is started.
This step selects where to save the configuration file.
Realflo User and Reference Manual
May 19, 2011
574
Realflo Wizards
Finish
Select the Save to Realflo.tfc to save the configuration file to the default file location.
Select the Save to another file to either enter a file name or use the
Browse option to open the Save As dialog.
This step is displayed at the end of the wizard.
Click Finish to close the wizard.
Notes
Views for extra runs are closed but new ones may be opened.
The history and event logs contain no information.
The configuration data for supported runs in the file is set to usable values, so when the number of runs is changed there is useful data in the configuration.
Realflo User and Reference Manual
May 19, 2011
575
Realflo Wizards
Create Configuration Step-by-Step
When you choose to configure the flow computer step-by-step, the Create
New File Wizard prompts you through the steps needed. The dialogs displayed are dependent upon the calculations you select.
Step-by-Step Configuration Sequence for a Flow Computer
The main steps in the configuration sequence to configure flow computer step-by-step are:
Use Create New File Dialog to select how to create a new file.
Use Hardware and Firmware Type Dialog to configure the hardware and firmware you are using.
Use the I/O Module Dialog to configure your I/O module (Telepace only).
Use the Flow Computer ID Dialog to assign an ID to the flow computer.
Use the Flow Runs Dialog to configure the number of flow runs
Use the Flow Run ID Dialog to assign an ID to the flow run.
Use the Flow and Compressibility Calculations to select the flow and
compressibility calculations for the meter run.
Select the Flow Run Inputs to configure the type of inputs for the flow
run.
Select the Differential Pressure Limits to configure the differential
pressure calibration to use for the run.
Configure the Static Pressure for the run.
Configure the Static Pressure Input Limits for the run.
Use the Static Pressure dialog to configure your sensors to
compensate for the gravitation pull of the Earth according to altitude and latitude variations.
Define the Temperature Limits for the run.
Define the Contract Settings for the run.
Select the Flow Calculations Dialog for the run.
Configure the Sensor Configuration for the run.
Review the Flow Computer Configuration Summary to confirm the
configuration settings.
Use Save File to save the new configuration.
Select the Create a new file? radio button from the Select File dialog to configure the flow computer step-by-step.
Realflo User and Reference Manual
May 19, 2011
576
Create New File Dialog
Realflo Wizards
Select the Create Configuration Step-by-Step radio button.
Click Next > to continue.
Follow the wizard steps described in the following sections to configure the flow computer.
Flow Computer Status Dialog
When configuring the flow computer step-by-step, select No when the Flow
Computer Status dialog opens. This lets you choose the hardware type and
Hardware and Firmware Type Dialog
The Hardware and Firmware Type Dialog opens when you select No in the
Flow Computer Status dialog.
First, select the Hardware Type from the dropdown list. The default value is
SCADAPack 4202 DR. The options from which you can select are:
Realflo User and Reference Manual
May 19, 2011
577
Realflo Wizards
Micro16
SCADAPack
SCADAPack Plus
SCADAPack Light
SCADAPack LP
SCADAPack 32
SCADAPack 32P
4202 DR
SCADAPack 100: 1024K
4202 DS
SCADAPack 314
SCADAPack 330
SCADAPack 334
SCADAPack 350
4203 DR
4203 DS
SolarPack 410
Second, select the Firmware Type from the dropdown list. The default value is Telepace. You can select ISaGRAF from the dropdown list for the firmware type.
If the firmware selected is Telepace, the I/O Module Type Dialog opens, followed by the Flow Computer ID dialog. If the firmware type selected is
ISaGRAF, the Flow Computer ID dialog opens.
I/O Module Type Dialog
This step lets you select the I/O module to use for the selected Hardware type. The register assignment in the new file is set to the default register assignment for the selected hardware type.
Realflo User and Reference Manual
May 19, 2011
578
Realflo Wizards
Select the I/O module for the flow computer from the dropdown list. The choices displayed depend on the flow computer hardware type.
Hardware Type
Micro16
SCADAPack
SCADAPack Plus
SCADAPack Light
SCADAPack LP
SCADAPack 32
SCADAPack 32P
4202 DR
SCADAPack 100:
1024K
4202 DS
SCADAPack 314
SCADAPack 330
SCADAPack 334
SCADAPack 350
4203 DR
4203 DS
SolarPack 410
I/O Modules Available
Controller I/O only or Backwards compatible modules.
5601 I/O Module, 5604 I/O Module, or 5606 I/O
Module
5601 I/O Module, 5604 I/O Module, or 5606 I/O
Module
5602 I/O Module
SCADAPack LP I./O
5601 I/O Module,
5604 I/O 10V/40mA Module
5604 I/O 5V/20mA Module
5606 I/O Module
SCADAPack 32P I/O
4202 DR or 4202 DR Extended/4203 DR I/O
SCADAPack 100: 1024K I/O
4202/4203 DS I/O
SCADAPack 314/33x I/O
SCADAPack 330 Controller.
SCADAPack 33x I/O
SCADAPack 350 10V/40mA Module
SCADAPack 350 5V/20mA Module
SCADAPack 357 Module
4202 DR Extended/4203 DR I/O
4202/4203 DS I/O
N/A
Flow Computer ID Dialog
This step sets the Flow Computer ID.
Realflo User and Reference Manual
May 19, 2011
579
Realflo Wizards
Type the Flow Computer ID string in the edit box. This unique ID stops accidental mixing of data from different flow computers. The maximum length of the Flow Computer ID is eight characters. Any characters are valid.
You can leave the Flow Computer ID edit box blank. The default value is blank.
Flow Runs Dialog
This step selects the number of flow runs in the flow computer. The wizard will step through the configuration of the first run and then each subsequent run if more than one run is selected.
Flow Run ID
Select the number of flow runs with the dropdown list. Valid values depend on the hardware type and the number of flow runs enabled for the flow computer. The default value is one.
For Micro16, SCADAPack, SCADAPack Light and SCADAPack Plus
Flow Computers, the maximum number of meter runs is three.
The selection of three meter runs is available for older flow computers that could be enabled for three meter runs.
For SCADAPack LP and SCADAPack (4202 and 4203) Flow
Computers, the maximum number of meter runs is two.
For SCADAPack 100: 1024K and SolarPack 410 Flow Computers, the maximum number of meter runs is one.
For SCADAPack 314/330/334 and SCADAPack 350 Flow Computers the maximum number of meter runs is four.
For SCADAPack 32 and SCADAPack 32P Flow computers the maximum number of runs you can select is ten.
This step sets the Flow Run ID for the meter run. This is the first step of a flow run configuration. The wizard will step you through the configuration of the first run and then each subsequent run if you select more than one run.
Realflo User and Reference Manual
May 19, 2011
580
Realflo Wizards
The Flow Run ID helps to identify the flow run. Type a string up to 32 characters long. Any characters are valid. You can leave the Flow Run ID edit box blank.
Older flow computers allow a string up to 16 characters. See the TeleBUS
section.
For subsequent runs, the next step is
Flow Calculations Dialog
This step selects the flow and compressibility calculations for the first run.
Flow Calculation selects the type of flow calculation for the meter run. Valid values are:
AGA-3 (1985 version)
AGA-3 (1992 version)
AGA-7
Realflo User and Reference Manual
May 19, 2011
581
Realflo Wizards
AGA-11 (not available for 16-bit controllers)
V-cone calculations
The template selected determines the default value.
Compressibility Calculation selects the type of compressibility calculation for the meter run. Valid compressibility calculation values are:
AGA-8 Detailed
NX-19 (Not supported for PEMEX flow computers)
AGA-8 Detailed is the recommended calculation for new systems as it has superior performance compared to NX-19. NX-19 is provided for legacy systems. The template selected determines the default value.
Flow Direction Control selects the direction of flow indication, forward or reverse, for a meter run.
Forward by Value selection indicates the flow direction is forward when the value from a differential pressure (DP) sensor is positive or the mass flow rate value from a Coriolis meter is positive.
Reverse by Value selection indicates the flow direction is reverse when the value from a differential pressure (DP) sensor is negative or the mass flow rate value from a Coriolis meter is negative.
Forward by Status selection indicates the flow direction is forward when the Flow Direction Register has a value of 0 (OFF).
Reverse by Status selection indicates the flow direction is reverse when the Flow Direction Register has a value of 1 (ON).
Flow Direction Register specifies which register indicates the forward or reverse flow direction status. Any valid registers for the flow computer controller can be used for this setting. The default register is 1. This edit control is disabled if Flow Direction Control selection is Value. This control is hidden in GOST mode flow computers.
Flow Run Units Dialog
This step selects the units that are used for input measurements and contracts.
Realflo User and Reference Manual
May 19, 2011
582
Realflo Wizards
Input Units selects the units of measurement of input values for the meter run. Inputs may be measured in different units than the calculated results.
This allows you to use units that are convenient to you for measuring inputs.
A dropdown box allows the selection of the following unit types. US2 is the default value.
US1
US2
US3
IP
Metric1
Metric2
Metric3
SI
US4
US5
US6
US7
US8
PEMEX
The reference list for the Input Units displays the parameters and units for these parameters:
DP (Differential pressure)
SP (Static pressure)
Temperature
Pipe and Orifice Diameter
Viscosity
Altitude
Heating value
Contract Units selects the units of measurement of contract values. These units are used for the calculated results. A dropdown box allows the selection of the following unit types. The default value is US2.
US1
US2
US3
IP
Metric1
Metric2
Metric3
Realflo User and Reference Manual
May 19, 2011
583
Realflo Wizards
SI
US4
US5
US6
US7
US8
PEMEX
The reference list for the Contract Units displays the parameters and units for these parameters when used for the contract. The parameters displayed depend on the contract units selected. The parameters are:
Volume
Volume Rate
Energy
Energy Rate
Base Pressure
Base Temperature
Mass
Mass Flow Rate
Density
Flow Extension
Heating Value
Flow Run Inputs
This step lets you configure the flow run inputs. One of two configuration dialogs is presented based on the input type you configure.
Sensor Inputs
Realflo User and Reference Manual
May 19, 2011
584
Realflo Wizards
Select Internal Sensor (4202 DR/DS or 4203DR/DS or SolarPack
410) to use a SCADAPack internal transmitter as the input device. The transmitter is the input for pressure, differential pressure, and temperature. This is the only valid selection for run 1of a SCADAPack flow computer. Other options are disabled.
Select Sensor to use a multivariable transmitter as the input device.
The transmitter is the input for pressure, differential pressure, and temperature. This is the default selection, except for run 1 of a
SCADAPack controller.
The Where is sensor connected to the Flow Computer parameter enables the ability to select the serial or LAN port where the sensor is connected to the flow computer. Selections vary according to the flowcomputer type. The default value is com1. Valid selections can include: o com1 o com2 o com3 o com4 o LAN
The What is the sensor model parameter selects the multivariable transmitter (MVT) type. The selections available are: o 3095FB o 4101 o 4102 o 4202 DR o 4202 DS o 4203 DR o 4203 DS
The What value should be used if the sensor fails parameter selects the specified value in this field as the live input value when communicating with a sensor. The dropdown list lets you select:
Realflo User and Reference Manual
May 19, 2011
585
Realflo Wizards o Use Last Known Good Value o Use Default Value
When you open a file using an older file format, Realflo sets the default value of the Values on Sensor Fail field to Use Last Known Good.
When the status to a sensor changes and you select the Use Default Value option, this is added to the Event Log.
For flow computers 6.70 and later, when communication to a sensor fails and the configuration option “Use Last Known Good Value” is set to
“Use Default Value,” the flow computer needs to use the specified default value in the configuration in place of a live input value.
When communication to a sensor is restored and the configuration option for the Value on Sensor Fail field is set to use the default value, the flow computer uses the input value from the sensor as the live input value.
For flow computers prior to 6.70, the value on sensor fail is ``Ùse Last
Known
Good Value.”
Analog Inputs
Select Analog Inputs to use analog inputs to measure pressure, differential pressure, and temperature.
Valid values are:
Telepace Integer
ISaGRAF Integer
Float
Raw Float
The default value is Telepace integer if Telepace firmware is running and
ISaGRAF integer if ISaGRAF firmware is running.
For AGA-7 calculations, the value is fixed and set automatically. The value is Telepace Long if Telepace firmware is running and ISaGRAF integer if
ISaGRAF firmware is running.
Differential Pressure Input Limits
configured
If AGA-7 is configured, the next step is
Differential Pressure Input Limits
This step lets you configure the differential pressure input limits. One of two configuration dialogs is presented based on the input type you configure.
Realflo User and Reference Manual
May 19, 2011
586
Sensor Inputs
Realflo Wizards
Input Type is a read-only field that identifies the sensor number for which you are setting the parameters using this dialog.
Units are the differential pressure units. Values read from the transmitter are in these units. If the transmitter has a local display, the transmitter uses these units. Valid values depend on the MVT type:
For SCADAPack transmtters, valid units are: inches H2O at 68°F,
Pascal (Pa) and kiloPascal (kPa). The default is inches H2O at 68°F.
For the 3095 MVT valid units are: inches H2O at 60°F, Pascal (Pa), kiloPascal (kPa) and inches H2O at 68°F. The default is inches H2O at
60°F.
Damping is the response time of the transmitter. It is used to smooth the process variable reading when there are rapid input variations.
For SCADAPack transmitters the valid values are 0.0 (damping off), 0.5,
1.0, 2.0, 4.0, 8.0, 16.0, and 32.0 seconds. The default value is 0
(damping off).
For the 3095 MVT the valid values are 0.108, 0.216, 0.432, 0.864,
1.728, 3.456, 6.912, 13.824 and 27.648. The default is 0.864.
Lower Operating Limit (LOL) is the lowest valid value from the sensor and needs to be less than the UOL. Alarms occur if the value is less than the
LOL. The default value is 0. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Upper Operating Limit (UOL) is the highest valid value from the sensor and needs to be greater than the LOL. Alarms occur if the value is greater than the UOL. The default value is the upper range limit of the transmitter.
Valid values depend on the transmitter; refer to the transmitter band or user manual.
Low DP Cutoff is the differential pressure where flow accumulation will stop and needs to be less than the UOL. The default value is 0. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Low DP Hysteresis is the amount by which the differential pressure needs to rise above the Low DP Cutoff for flow accumulation to start. It may be a
Realflo User and Reference Manual
May 19, 2011
587
Analog Inputs
Realflo Wizards value using the DP units or may be a percentage of the operating span. The operating span is the difference between the Upper Operating Limit and the
Lower Operating limit. Values depend on the transmitter. The flow accumulation level needs to be less than the Upper Operating Limit. The default value is 0.
Default Value is enabled if you configured the field using the Flow Run
Inputs dialog. Type the live input value to use when communicating with a sensor. The default value is 0.
If you configured sensor inputs, go to the
Static Pressure Options Dialog
section.
The dialog below opens when analog inputs are selected.
Input Type is a read-only field that identifies the input type for which you are setting the parameters using this dialog.
Input Register is the register address where the input value is stored. Valid values are 30001 to 39999 or 40001 to 49999. The default is selected based on the run number so that inputs have unique registers.
Input at Zero Scale is value read from the sensor, in unscaled I/O units, when the sensor is at zero scale. Valid values depend on the input type. The default value is 0. This is enabled for Telepace integer, raw float and
ISaGRAF integer types and disabled otherwise.
Input at Full Scale is value read from the sensor, in unscaled I/O units, when the sensor is at full scale. Valid values depend on the input type. The default value is 32767. This is enabled for Telepace integer, raw float and
ISaGRAF integer types and disabled otherwise.
DP at Zero Scale is the pressure that corresponds to the zero scale input, or if the input does not require scaling, the minimum pressure that can be read from the sensor. Valid values depend on the input type. The default value is 0.
DP at Full Scale is the pressure that corresponds to the full-scale input, or if the input does not require scaling, the maximum pressure that can be read
Realflo User and Reference Manual
May 19, 2011
588
Realflo Wizards from the sensor. Valid values depend on the input type. The default value is
16.
Low DP Cutoff is the differential pressure where flow accumulation will stop and needs to be less than the UOL. The default value is 0. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Low DP Hysteresis is the amount by which the differential pressure needs to rise above the Low DP Cutoff for flow accumulation to start. It may be a value using the DP units or may be a percentage of the operating span. The operating span is the difference between the Upper Operating Limit and the
Lower Operating limit. Values depend on the transmitter. The flow accumulation level needs to be less than the Upper Operating Limit. The default value is 0.
Static Pressure Options Dialog
This step lets you select how the static pressure is measured.
The pressure tap may be upstream or downstream of the orifice plate for
AGA-3.
Select Up Stream for an upstream static pressure tap. This is the default value. The control is disabled for AGA-7 and V-Cone calculations.
Select Down Stream for a downstream static pressure tap. The control is disabled for AGA-7 and V-Cone calculations.
Static Pressure Input Limits
This step defines the limits for the temperature input. One of two configuration dialogs is presented based on the Input Type configured for static pressure limits:
Sensor Inputs
The dialog below is presented when sensor inputs are used.
Realflo User and Reference Manual
May 19, 2011
589
Realflo Wizards
Input Type is a read-only field that identifies the sensor number for which you are setting the parameters using this dialog.
Units is the differential pressure units. Values read from the transmitter are in these units. If the transmitter has a local display it uses these units. Valid values are kiloPascal, MegaPascal, and psi (pounds per square inch). The default is psi.
Damping is the response time of the transmitter. It is used to smooth the process variable reading when there are rapid input variations.
For SCADAPack transmitters the valid values are 0.0 (damping off), 0.5,
1.0, 2.0, 4.0, 8.0, 16.0, and 32.0 seconds. The default value is 0
(damping off).
For the 3095 MVT the valid values are 0.108, 0.216, 0.432, 0.864,
1.728, 3.456, 6.912, 13.824 and 27.648. The default is 0.864.
Lower Operating Limit (LOL) is the lowest valid value from the sensor and needs to be less than the UOL. Alarms occur if the value is less than the
LOL. The default value is 0. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Upper Operating Limit (UOL) is the highest valid value from the sensor and needs to be greater than the LOL. Alarms occur if the value is greater than the UOL. The default value is the upper range limit of the transmitter.
Valid values depend on the transmitter; refer to the transmitter band or user manual.
Default Value is enabled if you gage pressure using the Static Pressure
Options. Type the live input value to use when communicating with a sensor. The template selected determines the default value displayed.
The pressure sensor may measure absolute or gage pressure.
Select Absolute Pressure to measure absolute static pressure. This is the default value unless the Compressibility Calculation type is set to
NX-19. The Static Pressure is set to Gage and the Atmospheric pressure is 14.7psi when NX-19 is selected.
Select Gage Pressure to measure gage static pressure.
Realflo User and Reference Manual
May 19, 2011
590
Analog Inputs
Realflo Wizards
Type the Atmospheric Pressure measured at the site. This control is disabled and set to zero if absolute pressure is selected.
The atmospheric pressure entered needs to be greater than zero. The maximum upper limits for atmospheric pressure are:
30 psi and PEMEX units for US1, US2, US3, US4, US5, US6, US7, US8,
4320
207
2.07
0.207 lbf/ft2 for IP units kPa bar
MPa for Metric1 units for Metric2 units for Metric3 units
207000 Pa for SI units
If you configured sensor inputs, see the
section.
The dialog below is presented when analog inputs are used.
Input Type is a read-only field that identifies the input type for which you are setting the parameters using this dialog.
Input Register is the register address where the input value is stored. Valid values are 30001 to 39999 or 40001 to 49999. The default is selected based on the run number so that inputs have unique registers.
Input at Zero Scale is value read from the sensor, in unscaled I/O units, when the sensor is at zero scale. Valid values depend on the input type. The default value is 0. This is enabled for Telepace integer, raw float and
ISaGRAF integer types and disabled otherwise.
Input at Full Scale is value read from the sensor, in unscaled I/O units, when the sensor is at full scale. Valid values depend on the input type. The default value is 32767. This is enabled for Telepace integer, raw float and
ISaGRAF integer types and disabled otherwise.
Realflo User and Reference Manual
May 19, 2011
591
Realflo Wizards
SP at Zero Scale is the pressure that corresponds to the zero scale input, or if the input does not require scaling, the minimum pressure that can be read from the sensor. Valid values depend on the input type. The default value is 0.
SP at Full Scale is the pressure that corresponds to the full-scale input, or if the input does not require scaling, the maximum pressure that can be read from the sensor. Valid values depend on the input type. The default value is
20000.
Static Pressure Compensation
This step selects if compensation is applied for the location where calibration was performed. If you configured sensors or analog inputs from the Static Pressure Limits dialog, this is the next step in the configuration sequence.
Select No if compensation is not required. This is the default value.
Select Yes to compensate for the altitude and latitude.
Type the Altitude of the location. Valid values are -30000 to 30000. The default value is 0. This control is disabled if No is selected.
Type the Latitude of the location. Valid values are -90 to 90. The default value is 0. This control is disabled if No is selected.
Realflo User and Reference Manual
May 19, 2011
592
Turbine Settings
Realflo Wizards
This step configures the turbine input for AGA-7 calculations.
Temperature Limits
This step lets you define the limits for the temperature input. One of two configuration dialogs is presented based on the Input Type configured for static pressure limits:
Sensor Inputs
Input Register is the register address where the input value is stored. Valid values are 30001 to 39999 or 40001 to 49999. The default is selected based on the run number so that inputs have unique registers.
Low Flow Pulse Limit is the number of pulses below which a low flow alarm will occur. The default value is 10.
Low Flow Detect Time is the length of time the number of pulses needs to remain below the Low Flow Pulse Limit for a low flow alarm to occur. Valid values are 1 to 5 seconds. The default value is 5.
The following dialog is presented when sensor (MVT) inputs are used.
Realflo User and Reference Manual
May 19, 2011
593
Realflo Wizards
Analog Inputs
Input Type is a read-only field that identifies the sensor number for which you are setting the parameters using this dialog.
Units is the differential pressure units. Values read from the transmitter are in these units. If the transmitter has a local display it uses these units. Valid values are kiloPascal, MegaPascal, and psi (pounds per square inch). The default is psi.
Lower Operating Limit (LOL) is the lowest valid value from the sensor and needs to be less than the UOL. Alarms occur if the value is less than the
LOL. The default value is 0. Valid values depend on the transmitter; refer to the transmitter band or user manual.
Upper Operating Limit (UOL) is the highest valid value from the sensor and needs to be greater than the LOL. Alarms occur if the value is greater than the UOL. The default value is the upper range limit of the transmitter.
Valid values depend on the transmitter; refer to the transmitter band or user manual.
The following dialog is presented when analog inputs are used.
Realflo User and Reference Manual
May 19, 2011
594
Realflo Wizards
Input Type is a read-only field that identifies the input type for which you are setting the parameters using this dialog.
Input Register is the register address where the input value is stored. Valid values are 30001 to 39999 or 40001 to 49999. The default is selected based on the run number so that inputs have unique registers.
Input at Zero Scale is value read from the sensor, in unscaled I/O units, when the sensor is at zero scale. Valid values depend on the input type. The default value is 0. This is enabled for Telepace integer, raw float and
ISaGRAF integer types and disabled otherwise.
Input at Full Scale is value read from the sensor, in unscaled I/O units, when the sensor is at full scale. Valid values depend on the input type. The default value is 32767. This is enabled for Telepace integer, raw float and
ISaGRAF integer types and disabled otherwise.
Temperature at Zero Scale is the temperature that corresponds to the zero scale input, or if the input does not require scaling, the minimum pressure that can be read from the sensor. Valid values depend on the input type.
The default value is
–40.
Temperature at Full Scale is the temperature that corresponds to the fullscale input, or if the input does not require scaling, the maximum pressure that can be read from the sensor. Valid values depend on the input type.
The default value is 200.
Realflo User and Reference Manual
May 19, 2011
595
Contract Settings
This step sets the contract settings for the run.
Realflo Wizards
Input Average Weighting is the weighting method of the linear inputs. This applies to the differential pressure, static pressure, and temperature. Valid
values are time-weighted or flow-weighted (see Input Averaging on page
948 for more information). The default is time-weighted.
Contract Hour is the hour of the day that starts a new contract day specified using a 24-hour clock. The contract day begins at 00 minutes and
00 seconds of the specified hour. Valid values are 0 to 23. The default value is 0 (midnight).
Standard Base Conditions are the default Base Temperature and Base
Pressure (absolute) values.
Base Temperature is the reference temperature to which contract flow values are corrected. Valid values are -40 to 200. The default value is given in the table below.
Base Pressure is the reference pressure to which contract flow values are corrected. The base pressure is measured as absolute pressure
(not a gauge pressure). Valid values are 0 to 32000. The default value is given in the table below.
Contract Units Standard Base
Temperature
US1 60 F
US2
US3
IP
Metric1
Metric2
60 F
60 F
60 F
15 C
15 C
Metric3
SI
US4
US5
US6
US7
US8
15 C
288.15 K
60 F
60 F
60 F
60 F
60 F
Standard Base Pressure
14.73 psi
14.73 psi
14.73 psi
2116.2281 lbf/ft
2
101.325 kPa
1.01325 bar
0.101325 MPa
101325 Pa
14.73 psi
14.73 psi
14.73 psi
14.73 psi
14.73 psi
Realflo User and Reference Manual
May 19, 2011
596
Realflo Wizards
Contract Units Standard Base
Temperature
PEMEX 60 F
Standard Base Pressure
14.73 psi
Realflo for PEMEX flow computers provide a second set of base conditions.
PEMEX Base Conditions are the default Base Temperature and Base
Pressure (absolute) values when Realflo is operating in PEMEX mode.
Base Temperature is the reference temperature to which contract flow values are corrected. The default is listed in the table below for each type of contract unit.
Base Pressure is the reference pressure to which contract flow values are corrected. The base pressure is measured as absolute pressure
(not a gauge pressure). Valid values are 0 to 32000. The default values are listed in the table below for each contract unit.
Contract Units Standard Base
Temperature
US1 60 F
US2
US3
IP
Metric1
Metric2
60 F
60 F
60 F
15 C
15 C
Metric3
SI
US4
US5
US6
US7
US8
PEMEX
15 C
288.15 K
60 F
60 F
60 F
60 F
60 F
68 F
Standard Base Pressure
14.73 psi
14.73 psi
14.73 psi
2116.2281 lbf/ft
2
101.325 kPa
1.01325 bar
0.101325 MPa
101325 Pa
14.73 psi
14.73 psi
14.73 psi
14.73 psi
14.73 psi
14.73 psi
Flow Calculations
AGA-3 Settings
When configuring a flow computer, you can configure it to use the following calculations:
AGA-Settings
AGA-3 Deadband Settings
AGA-7 Settings
AGA-11 Settings
This step lets you set the AGA-3 calculation parameters.
Realflo User and Reference Manual
May 19, 2011
597
Realflo Wizards
Orifice Material is the material the orifice plate for the meter run is made of.
Valid values are Stainless Steel, Monel, and Carbon Steel. The default value is Stainless Steel.
Pipe Material is the material the meter run pipe is made of. Valid values are
Stainless Steel, Monel, and Carbon Steel. The default value is Carbon
Steel.
Orifice Diameter is the diameter of the meter run orifice. The default value is 3 inches.
Orifice reference temperature is the temperature at which the diameter of the meter run orifice was measured. The default value is 68°F.
Pipe Diameter is the measurement of the meter run pipe inside diameter.
The default value is 4.026 inches.
Pipe reference temperature is temperature at which the meter run pipe diameter was measured. The default value is 68°F.
Beta Ratio is the ratio of orifice diameter to pipe diameter. It is displayed for information purposes only and cannot be edited.
Realflo displays messages if the beta ratio is outside recommended limits.
Isentropic Exponent is a thermodynamic property of gas used to predict the relationships between pressure, temperature, volume and energy. If you are unsure of this value, a typical value of 1.3 is commonly used. The default value is 1.3.
Viscosity is a measure of the resistance of a measured gas to flow. Valid values are 0 to 1. The default value is 0.010268 centipoise.
AGA-3 Deadband Settings
This step lets you set AGA-3 calculation deadbands.
Realflo User and Reference Manual
May 19, 2011
598
Realflo Wizards
AGA-7 Settings
Temperature Deadband is the tolerated change in the flowing temperature before temperature dependent factors in the flow calculation are recalculated. Changes in the temperature smaller than the deadband will be ignored in determining the result. The default value is 0. The upper limit is
7°F or 4°C.
Static Pressure Deadband is the tolerated change in the static pressure before static pressure dependent factors in the flow calculation are recalculated. Changes in the static pressure smaller than the deadband will be ignored in determining the result. A static pressure deadband setting of up to four percent of the typical static pressure level should have a small effect on the accuracy of the AGA-3 calculation. The default value is 0. The upper limit is 800 psi or 5500 kPa or the equivalent in other units.
Differential Pressure Deadband is the tolerated change in the differential pressure before differential pressure dependent factors in the flow calculation are recalculated. Changes in the differential pressure smaller than the deadband will be ignored in determining the result. A change of N in the differential pressure input will cause a change of 0.5 N in the calculation volume at base conditions. It is recommended that the differential pressure deadband be set to zero. The default value is 0. The upper limit is 4.5 inWC or 1.1 kPa or the equivalent in other units.
This step lets you define AGA-7 settings.
Realflo User and Reference Manual
May 19, 2011
599
Realflo Wizards
AGA -11 Settings
K Factor is the number of pulses per unit volume of the turbine meter. Valid values are 0.001 to 1000000. The default value is 100.
M Factor is the adjustment to the number of pulses per unit volume for the turbine meter compared to an ideal meter. Valid values are 0.001 to 1000.
The default value is 1.
Uncorrected Flow Volume is the accumulated uncorrected flow volume at base conditions.
The Uncorrected Flow Volume control is available in Realflo versions 6.20 and higher.
AGA-11 configuration defines parameters unique to the AGA-11 calculation.
The AGA-11 calculation communicates with a Coriolis meter for the calculation. The AGA-11 configuration sets the communication parameters for communication between the Coriolis meter and the flow computer.
Address
This is the Modbus address of the Coriolis Meter for serial communications.
Multiple Coriolis meters using the same serial port on the flow computer
Realflo User and Reference Manual
May 19, 2011
600
Realflo Wizards needs to each have a unique Modbus address. Valid Modbus addresses are between 1 and 247. The default address is 247.
Port
Timeout
V-Cone Settings
This is the communication port on the flow computer that will be used to communicate with the Coriolis meter. Valid port selections depend on the type of controller the flow computer running on. The default port is the first valid port available on the controller.
This is the time the flow computer will wait for a response for Modbus read commands send to the Coriolis meter. When the timeout time is exceeded the command fails and an alarm is added to the flow computer alarm list.
Valid timeout values are from 0 to 1000 ms. The default value is 50 ms.
V-Cone Configuration defines parameters unique to the V-Cone calculation.
Cone Material
This is the material of the V-cone. Valid values are Carbon Steel, Stainless
304, and Stainless 316. The default value is determined by the template selected.
Pipe Material
This is the material from which the meter run pipe is made. Valid values are
Carbon Steel, Stainless 304, and Stainless 316. The default value is determined by the template selected.
Adiabatic Expansion Factor
The Adiabatic Expansion Factor drop down list selects which calculation is used for the adiabatic expansion factor of the calculation.
Select Legacy Calculation to use the older calculation method. This is the default selection. Flow computers prior to version 6.71 support only this selection.
Select V-Cone to use the V-Cone specific calculation. This selection should be used with V-Cone devices.
Realflo User and Reference Manual
May 19, 2011
601
Realflo Wizards
Select Wafer-Cone to use the Wafer-Cone specific calculation. This selection should be used with Wafer-Cone devices.
This control is disabled and forced to Legacy Calculation if the controller type is not one of SCADAPack 32, SCADAPack 32P, SCADAPack
314/330/334, SCADAPack 350 SCADAPack 4203 or SolarPack 410.
When reading from a flow computer that does not support the adiabatic expansion factor configuration, the method will be set to Legacy Calculation.
When writing to a flow computer that does not support the adiabatic expansion factor method, the configuration registers will be ignored and the expansion factor will not be written.
Cone Diameter
The diameter of the meter run cone used for the flow calculation. The measurement units are displayed depending on the input units selected.
The default value is 3 inches.
Cone Measurement Temperature
This is the reference temperature at which the cone diameter for the meter run was measured. The measurement units are displayed depending on the input units selected. The default value is 59 degrees F.
Pipe Inside Diameter
This is the measurement of the meter run pipe inside diameter. The measurement units are displayed depending on the input units selected.
The default value is 5 inches.
Pipe reference temperature
The temperature at which the meter run pipe diameter was measured. The measurement units are displayed depending on the input units selected.
The default value is 59 degrees.
Isentropic Exponent
In general, this is a thermodynamic property of gas used to predict the relationships between pressure, temperature, volume and energy. If you are unsure of this value a typical value of 1.3 is commonly used. The default value is 1.3.
Viscosity
This is the viscosity of the measured gas. In general, this is the resistance of a gas or semi-fluid resistance to flow. The measurement units are displayed depending on the input units selected. Valid values are 0 to 1. The default value is 0.010268 centiPoise.
Wet Gas Correction Factor
The Wet Gas Correction Factor Method drop down list selects which calculation is used for the wet gas correction factor of the calculation.
Select Legacy Method to use the older correction method. This is the default selection. Flow computers prior to version 6.73 support only this selection.
Select V-Cone or Wafer Cone to use the V-Cone and Wafer Cone specific calculation. This selection should be used with V-Cone or Wafer
Cone devices.
Realflo User and Reference Manual
May 19, 2011
602
Realflo Wizards
This control is disabled and forced to Legacy Calculation if the controller type is not one of SCADAPack 32, SCADAPack 32P, SCADAPack
314/330/334, SCADAPack 350 SCADAPack 4203 or SolarPack 410.
The V-Cone or Wafer Cone supported Beta Ratios are:
For Fr (Froude Number) < 5 supported Beta Ratio is 0.55.
For Fr (Froude Number) < 5 supported Beta Ratio is 0.75.
For Fr (Froude Number) > 5 supported Beta Ratio is 0.75.
When V-Cone or Wafer Cone is selected and if the current Beta ratio is not supported when executing verification, a message is displayed.
When V-Cone or Wafer Cone is selected, configuration of the fixed wet gas factor parameter, as set in the Contract tab, is disabled.
When Legacy Method is selected, configuration of the parameters used by the V-Cone or Wafer Cone method is disabled.
Mass Flow Rate of Liquid
The Mass flow rate of liquid at flow conditions parameter is used by the V-
Cone or Wafer Cone method and can be configured when V-Cone or Wafer
Cone is selected. This information needs to be gathered using a sampling method or a tracer method. The default is 0.
Density of Liquid
The Density of liquid at flow conditions parameter is used by the V-Cone or
Wafer Cone method and can be configured when V-Cone or Wafer Cone is selected. The default is 0.
V-Cone Coefficients
This step lets you define the V-Cone coefficients.
Enter the V-Cone coefficient pairs from the meter sizing report. The default list contains one pair: Re = 1000000; Cf = 0.82.
Click Add to add a coefficient pair.
Realflo User and Reference Manual
May 19, 2011
603
Realflo Wizards
In the original McCrometer V-Cone Application Sizing sheet that is included with V-Cone meters uses the terminology Cd (discharge coefficient) rather than Cf (flow coefficient). You will need to use the Re and Cd values from the V-Cone Application Sizing sheet for the Re and Cf entries. If the Re value is the same for all entries in the table only the first pair is used.
McCrometer now supplies one value of Cd in the sizing document. You need to enter one Re/Cd pair only. See the McCrometer Application Sizing sheet for the Re/Cd pair for your meter.
Compressibility Calculations
When configuring a flow computer, you can configure it to use the following compressibility calculations:
AGA-8 Settings
To edit a coefficient pair in the table:
Select a row in the list.
Click Edit to open the Add/Edit Flow Coefficient dialog.
To delete a coefficient pair in the table:
Select a row in the list.
Click Delete to delete the pair form the list.
Realflo User and Reference Manual
May 19, 2011
604
This step sets AGA-8 calculation options.
Realflo Wizards
Events can be logged each time an AGA-8 gas component changes.
Select Yes to log each change to the gas composition. Use this option if the gas composition changes infrequently. This is the default selection.
Select No to skip logging changes. Use this option if you are making frequent changes to the gas composition.
The Relative Density and Heating values can be calculated from the AGA-8 calculation or determined in a laboratory.
Select Calculate the Values to have AGA-8 calculate the values.
Select Use Laboratory Values to used fixed values.
Relative Density sets the real relative density of the gas. Valid values are 0.07 to 1.52. The default value is 0.554. This control is disabled if
Calculate the Values is selected.
Heating Value sets the heating value of the gas. Valid values are 0 to
1800 BTU(60)/ ft
3
or the equivalent in the selected units. The default value is 1014 BTU(60)/ft
3
or the equivalent in the selected units. This control is disabled if Calculate the Values is selected.
AGA-8 Hexanes+ Settings
This step chooses if Hexane and higher components are entered individually or as a single combined value.
Realflo User and Reference Manual
May 19, 2011
605
Realflo Wizards
Gas composition can be measured with individual values for hexane and higher components or use a combined value.
Select Enter Each Component to use individual values for the higher components. This is the default selection.
Select Use Combined Hexanes+ with these Ratios to use a combined value. Type the ratios of the higher components.
n-Hexane defines the percentage of the Hexanes+ contributed by n-
Hexane.
n-Heptane defines the percentage of the Hexanes+ contributed by n-
Heptane.
n-Octane defines the percentage of the Hexanes+ contributed by n-
Octane.
n-Nonane defines the percentage of the Hexanes+ contributed by n-
Nonane.
n-Decane defines the percentage of the Hexanes+ contributed by n-
Decane.
The Total field displays the sum of portions. This value cannot be edited. The total of portions needs to be 100 percent.
AGA-8 Gas Composition
This step defines the AGA-8 gas composition. One of two configuration dialogs opens based on whether Hexane and higher components are entered individually or as a single combined value.
Individual Components
The dialog below lets you enter combined Hexanes+ composition.
Realflo User and Reference Manual
May 19, 2011
606
Realflo Wizards
Type the gas composition according to the laboratory analysis. The total of components needs to be 100 percent.
Normalize adjusts non-zero components so that the total of components is
1.0000 (or 100.00 percent). The ratio to each other for the components remains the same.
Combined Hexanes+
The dialog below lets you enter combined Hexanes+ composition.
Type the gas composition according to the laboratory analysis. The total of components needs to be 100 percent.
Normalize adjusts non-zero components so that the total of components is
1.0000 (or 100.00 percent). The components remain in their current ratio to each other.
NX-19 Settings
Realflo User and Reference Manual
May 19, 2011
607
Realflo Wizards
This step lets you define the NX-19 calculation. This is not supported for
PEMEX flow computers.
Specific Gravity is the specific gravity of the gas being measured. Valid values are 0.554 to 1.000. The default value is 0.554.
Carbon Dioxide is the percent of carbon dioxide in the gas being measured. This value needs to be in the range 0 to 15. The default value is
0.
Nitrogen is the percent of nitrogen in the gas being measured. This value needs to be in the range 0 to 15.
Heating Value is the heating value of the gas being measured. Valid values are 0 to 1800 BTU(60)/ft
3
or the equivalent in the selected units. The default value is 1014.33 BTU(60)/ft3.
Events can be logged each time the NX-19 configuration changes.
Select Yes to log each change to the configuration. Use this option if the configuration changes infrequently. This is the default selection.
Select No to skip logging changes. Use this option if you are making frequent changes to the configuration.
Sensor Configuration Parameters
The next step is MVT Configuration if any transmitters were used in the
input configuration. Otherwise the next step is
Sensor Configuration
This step selects how the transmitters are to be configured.
Realflo User and Reference Manual
May 19, 2011
608
Realflo Wizards
The Flow Runs are configured to use these transmitters window is a table that shows each of the configured flow run numbers, its Flow Run ID and the transmitter that it uses for the differential pressure (DP), static pressure (SP) and temperature sensors. If an analog input is used for the flow run AIN will be displayed in the coresponding DP, SP, or Temp column.
The How do you want to configure sensors? option lets you select how to continue configuring the sensors. The three options are:
Connect now and configure transmitters to connect to the flow computer and configure the attached transmitters. This selection is disabled if the flow computer configuration was selected to be completed offline in the Flow Computer Status step. If you choose this
Configure Connected Transmitters
section to continue.
Edit sensor configuration without connecting to proceed directly to the editing pages, without connecting to the flow computer. If you
continue.
Use default sensor configuration to complete the configuration without changing the sensor configuration. Sensor configuration will be
set to default values. If you choose this option, the next step is
Configure Connected Transmitters
This step lets you select to either use the Realflo configuration data or the configuration from a pre-configured transmitter.
Realflo User and Reference Manual
May 19, 2011
609
Realflo Wizards
Sensor Search
Select Use the configuration from Realflo to use the configuration data from the Realflo file. This is the default setting.
Select Read the configuration from the transmitter to read configuration from a pre-configured transmitter.
This step searches for sensors connected to the flow computer serial ports or LAN port.
Search Serial Option
Select Search Serial to search for transmitters connected to a serial port of the flow computer.
The Port parameter selects the flow computer serial port where the sensor is attached. Valid values are com1, com2, com3, and com4. The default value is com2 for a SCADAPack controller and com1 for other controllers.
Realflo User and Reference Manual
May 19, 2011
610
Realflo Wizards
The Timeout parameter specifies the length of time the flow computer will wait for a response from a sensor. Valid values are 100 ms to 10000 ms.
The default is 300 ms.
Select Maximum to search for a number of MVT transmitters. The search operation will stop after finding the specified number of transmitters. The valid value is from 1 to 255. The default is 1.
Select Range to search the addresses in a specified range. The range to search for is typed in the edit boxes to the right of the radio button. The value in To edit control needs to be equal or great than the value in the first edit control. The maximum search range that can be typed is for 255 transmitters. The default range is 1 to 247.
Range Search supports addresses 1 to 255 in standard Modbus mode, and 1 to 65534 in extended address mode. The address mode of the flow computer serial port needs to be set to extended to search for transmitters with extended addresses.
Select All to search the addresses of all transmitters connected with the serial port selected in Port. Up to 255 addresses are searched.
Click Next to start the search for sensors or 4000 transmitters. A search process dialog is displayed so that the search operation can be cancelled at any time.
Search LAN Option
Select Search LAN to search for transmitters connected to a LAN port of the flow computer.
The IP Address parameter specifies the IP address of a 4000 transmitter.
Valid entries are IP addresses in the format nnn.nnn.nnn.nnn where nnn are values between 0 and 255.
The Protocol parameter selects the type of IP protocol that will be used to query the transmitter. Valid IP protocol selections are Modbus/TCP and
Modbus RTU in UDP.
The IP port (for example port 502) for the selected protocol needs to be the same in the flow computer and the 4000 transmitter.
The Timeout parameter specifies the length of time the flow computer will wait for a response from a 4000 transmitter. Valid values are 100 to 10000 milliseconds. The default is 5000 ms.
Click Next to start the search for MVT transmitters or 4000 transmitters. A search process dialog is displayed so that the search operation can be cancelled at any time.
If no transmitters were found, a message is displayed and the search step is displayed again.
Assign Sensors
This step lets you assign found transmitters to flow runs.
Realflo User and Reference Manual
May 19, 2011
611
Realflo Wizards
The Available Sensors pane shows the transmitters that have been configured and the transmitters that were found by the search. There may be more transmitters in the list than there are runs.
The Sensor column indicates the transmitter slots that have been configured. Transmitters that were found but not assigned are listed as Not
assigned.
The Status column indicates if configuration data for the transmitter exists.
Found indicates a transmitter has been configured and the search found one with the same port, address and device type.
Missing indicates a transmitter has been configured but the search did not find one with the same port, address, and device type.
The Port column displays the serial or LAN port the flow computer is using to communicate with the transmitter.
The Address column displays the Modbus station address or IP address of the transmitter.
The Tag column displays the Tag Name assigned to the transmitter. You can leave this column blank if a Tag Name has not been assigned to the transmitter.
The Device type column displays the transmitter type. Valid values are
3095FB, 4101, 4102, 4202 DR, 4202 DS, 4203 DR, or 4203 DS.
The Flow Runs window shows which MVTs are assigned to the runs.
To Change the order of the sensors:
Select a sensor in Available Sensors window.
Click Move.
The Move Sensor dialog opens:
Realflo User and Reference Manual
May 19, 2011
612
Realflo Wizards
In the Move Sensor dialog, use Move To selection to select the new location
Click OK.
To delete a sensor:
Select a transmitter in Available Sensors.
Click Delete.
To change the address of a Sensor:
Select a transmitter in Available Sensors.
Click Change Address.
The Change Address dialog opens:
Enter a new address for the transmitter in the New Address: edit box.
Click OK.
Click Next when the transmitters are moved to the correct location.
Next is disabled if there are Not Assigned transmitters still in the list.
Search for More Transmitters Dialog
Notes
The following actions may occur when moving a sensor.
Moving one sensor to another results in the both swapping positions.
When Use the configuration from Realflo is selected, assigning a Not assigned transmitter to a Sensor with status Missing and device type matching result in the sensor adopting the transmitter‟s port and address and retaining the rest of the sensor configuration. The sensor, being assigned, will disappear from the list.
When Read the configuration from the transmitter is selected, assigning a Not assigned transmitter to a sensor with status Missing and device type matching results in the sensor a dopting the transmitter‟s configuration. The transmitter, being assigned, will disappear from the list.
Assigning a Not assigned transmitter to a sensor with status Missing and device type not matching will result in the sensor adopting the
Realflo User and Reference Manual
May 19, 2011
613
Realflo Wizards transmitter‟s configuration. The transmitter, being assigned, will disappear from the list.
Other assignments are not permitted.
Search for More Transmitters Dialog
This step displays the current sensor assignments and asks if more searches are needed.
Proposed Sensors shows the transmitters that have been configured and the transmitters that were found by the search.
Flow Runs shows which sensors are assigned to which runs.
Select Search for more transmitters to search again.
Select Finish searching and review configuration to use the current settings. This is the default radio button.
Review Sensors Dialog
This step displays the transmitter assignments and allows you to edit the transmitter configuration.
Realflo User and Reference Manual
May 19, 2011
614
Realflo Wizards
The Sensors pane shows the transmitters that have been configured.
The Flow Runs pane shows which sensors are assigned to the runs.
Click Edit to review and modify the settings for each transmitter. Edit opens the Add/Edit Sensor Settings dialog. Changes to a transmitter address will be written to the transmitter without affecting current flow computer configuration.
Copy Run Configuration Dialog
The Copy Run step is displayed only if you selected more than one run is selected in the Number of Flow Runs step and you have configured the first run.
The second flow run, and subsequent runs, may be configured step-by-step or by copying the configuration of a previous run.
Select Set by Step configuration to configure another run using the wizard without copying Run 1.
Realflo User and Reference Manual
May 19, 2011
615
Flow Computer Configuration Summary
This step displays a summary of the flow computer settings.
Realflo Wizards
A summary of the flow computer configuration is shown.
The current configuration can be compared with the configuration in the target flow computer.
Select Yes to compare the configurations.
Select No to not compare the configurations.
Review Differences
This step displays a summary of changes in the flow computer configuration. You can select to write to the flow computer or not.
The summary shows the differences in the configuration.
Select Yes to write the configuration to the flow computer. The configuration is written to the flow computer. The Start Executing command will be written for each flow run. The communication progress dialog shows the stages of writing.
Select No to write the configuration to the flow computer later.
Realflo User and Reference Manual
May 19, 2011
616
Save File
Realflo Wizards
Click Next to perform the selected action.
In Flow Computer versions 6.73 and older, when AGA-8 gas ratios or NX-19 gas quality values are written to the flow computer the new gas ratios are updated in the Proposed registers. The Actual registers are not updated until a new Density calculation is started with the new values. The new values are not available to SCADA host software reading the Actual registers until a until a new Density calculation is started with the new values.
In Flow Computer versions 6.74 and newer when AGA-8 gas ratios or NX-
19 gas quality values are written to the flow computer the new gas ratios are updated in the Proposed registers and in the Actual registers. This allows a
SCADA host to immediately confirm the new values were written to the flow computer. The new gas values are not used by the flow computer until a new density calculation is started.
This step lets you select where to save the configuration file.
Finish
Select Save to Realflo.tfc to save the configuration file to the default file location.
Select the Save to another file to either enter a file name or use the
Browse option to open the Save As dialog.
This step is displayed at the end of the wizard.
Realflo User and Reference Manual
May 19, 2011
617
Click Finish to close the wizard.
Realflo Wizards
Realflo User and Reference Manual
May 19, 2011
618
Realflo Wizards
Replace Flow Computer Wizard
This step selects the flow computer file to write and writes the file to the flow computer.
Use the Replace Flow Computer dialog to select the flow computer program to write to the flow computer.
Select Flow Computer to write a basic flow computer program. Realflo selects the correct program file for the flow computer from the folder Realflo was started from, typically C:\Program Files\Control
Microsystems\Realflo.
The file selected will be Realflot v#.##.#.abs for Telepace firmware and
Realfloi v#.##.#.abs for ISaGRAF firmware on 16-bit SCADAPack controllers, where #.##.# is the flow computer version number.
This option is disabled if the controller type is a SCADAPack 32,
SCADAPack 314/330/334, SCADAPack 350, SCADAPack 4203 and
SolarPack 410.
Select Flow Computer with Enron Modbus to write a flow computer program with Enron Modbus support. Realflo selects the correct program file for the flow computer from the folder Realflo was started from, typically
C:\Program Files\Control Microsystems\Realflo.
Flow computer files available will depend on the Realflo operating mode and the controller type.
Standard Flow Computer Files
RFEnront v#.##.#.abs for Telepace firmware and RFEnroni
v#.##.#.abs for ISaGRAF firmware for 16-bit SCADAPack controllers.
Realflot v#.##.#.out for Telepace SCADAPack 350 firmware and
Realfloi v#.##.#.out for ISaGRAF SCADAPack 350 firmware.
Realflo33xt v#.##.#.out for Telepace SCADAPack 330/334 firmware and Realflo33xi v#.##.#.out for ISaGRAF SCADAPack 330/334 firmware.
Realflo31xt v#.##.#.out for Telepace SCADAPack 314 firmware and
Realflo31xi v#.##.#.out for ISaGRAF SCADAPack 314 firmware.
Realflo User and Reference Manual
May 19, 2011
619
Realflo Wizards
Realflo4203t v#.##.#.out for Telepace SCADAPack 4203 firmware and
Realflo4203i v#.##.#.out for ISaGRAF SCADAPack 4203 firmware.
Realflo410t v#.##.#.out for SolarPack 410 firmware.
Realflot v#.##.#.mot for Telepace SCADAPack 32 firmware and
Realfloi v#.##.#.mot for ISaGRAF SCADAPack 32 firmware.
GOST Flow Computer Files
Realflo_GOST_t v#.##.#.abs for Telepace firmware and
Realflo_GOST_i v#.##.#.abs for ISaGRAF firmware for 16-bit
SCADAPack controllers.
Realflo_GOST_33xt v#.##.#.out for Telepace SCADAPack 330/334 firmware and Realflo_GOST_33xi v#.##.#.out for ISaGRAF
SCADAPack 330/334 firmware.
Realflo_GOST_31xt v#.##.#.out for Telepace SCADAPack 330/334 firmware and Realflo_GOST_31xi v#.##.#.out for ISaGRAF
SCADAPack 330/334 firmware.
Realflo_GOST_4203t v#.##.#.out for Telepace SCADAPack 4203 firmware and Realflo_GOST_4203i v#.##.#.out for ISaGRAF
SCADAPack 4203 firmware.
Realflo_GOST_410t v#.##.#.out for SolarPack 410 firmware.
Realflot v#.##.#.mot for Telepace SCADAPack 32 firmware and Realfloi
v#.##.#.mot for ISaGRAF SCADAPack 32 firmware.
PEMEX Flow Computer Files
Realflo_PEMEX_t v#.##.#.abs for Telepace firmware and
Realflo_PEMEX_i v#.##.#.abs for ISaGRAF firmware for 16-bit
SCADAPack controllers.
Realflo_PEMEX_33xt v#.##.#.out for Telepace SCADAPack 330/334 firmware and Realflo_PEMEX_33xi v#.##.#.out for ISaGRAF
SCADAPack 330/334 firmware.
Realflo_PEMEX_31xt v#.##.#.out for Telepace SCADAPack 330/334 firmware and Realflo_PEMEX_31xi v#.##.#.out for ISaGRAF
SCADAPack 330/334 firmware.
Realflo_PEMEX_4203t v#.##.#.out for Telepace SCADAPack 4203 firmware and Realflo_PEMEX_4203i v#.##.#.out for ISaGRAF
SCADAPack 4203 firmware.
Realflo_PEMEX_410t v#.##.#.out for SolarPack 410 firmware.
Realflot v#.##.#.mot for Telepace SCADAPack 32 firmware and
Realfloi v#.##.#.mot for ISaGRAF SCADAPack 32 firmware.
Select Customer Flow Computer or C/C++ Program to write any C/C++ program to the flow computer. Select the file to write by:
Entering the file name in the edit box.
Selecting a recently used file by clicking the down arrow.
Using the Browse button to select a file. The Browse button opens a file open dialog. The dialog shows files of type ABS if the flow computer is a
SCADAPack. OUT, if the flow computer is a SCADAPack 314/330/334,
Realflo User and Reference Manual
May 19, 2011
620
Set Time
Realflo Wizards
SCADAPack 350 or SCADAPack 4203, or MOT if the flow computer is a
SCADAPack 32.
The Back button returns to the previous step.
The Next button writes the flow computer file and moves to the next step,
Set Time.
The Cancel button closes the dialog and stops the wizard.
The Help button opens the on-line manual.
This step sets the time in the flow computer. Setting the time allows that configuration events are recorded with the correct time.
The following controls are available from the Real Time Clock dialog.
The current Flow Computer Time shows the current time and date in the flow computer. It is updated continuously while the dialog is open. The time and date are displayed in the short time format as defined in the Windows
Control Panel.
The Yes, set to PC Time radio button selects setting the controller time to match the PC time. The current PC time and date are shown to the right of the button. The time and date are displayed in the short format as defined in the Windows Control Panel.
The Yes, set to this time radio button selects setting the time and date to the values specified by the user in the Year, Month, Day, Hour, Minute and
Second controls. If the Set to User Entered Time radio button is not selected these controls are grayed.
The Back button returns to the previous step.
The Finish button writes the time and ends the wizard.
The Cancel button closes the dialog and stops the wizard.
The Help button opens the on-line manual.
Realflo User and Reference Manual
May 19, 2011
621
Realflo Wizards
Write Flow Computer Configuration
The Write Configuration command is used to write all or selected parts of the Flow Computer Configuration. When selected the command displays the
Write Flow Computer Configuration dialog as shown below.
The All Configuration radio button, when selected, results in the writing of all configuration data from the flow computer.
The Selected Configuration radio button enables specific configuration data to be written to the flow computer.
Select Communication and I/O Settings to write the serial port, register assignment configuration information and mapping table.
Select Flow Run and MVT Configuration to write the flow run configuration and the MVT transmitter configuration.
Realflo User and Reference Manual
May 19, 2011
622
Realflo Wizards
Select Process I/O Configuration to write the Process I/O configuration.
Click on the OK button to write the selected items to the flow computer.
Click the Cancel button to cancel the operation and close the dialog.
The Flow Computer ID is checked before writing. If the Flow Computer
ID does not match the ID in the dialog Realflo displays a message.
An error occurs if Controller Configuration is selected and the flow computer type is different from the flow computer type selected in the
Controller Type dialog. A message is displayed.
In Flow Computer versions 6.73 and older, when AGA-8 gas ratios or NX-19 gas quality values are written to the flow computer the new gas ratios are updated in the Proposed registers. The Actual registers are not updated until a new Density calculation is started with the new values. The new values are not available to SCADA host software reading the Actual registers until a until a new Density calculation is started with the new values.
In Flow Computer versions 6.74 and newer when AGA-8 gas ratios or NX-
19 gas quality values are written to the flow computer the new gas ratios are updated in the Proposed registers and in the Actual registers. This allows a
SCADA host to immediately confirm the new values were written to the flow computer. The new gas values are not used by the flow computer until a new density calculation is started.
Read Alarm and Event Logs
This step selects whether the alarms and events in the flow computer are read.
The Which Events do you want to read? section has the following selections.
Select Just Read New Events to read unacknowledged events in the flow computer. If the operator has Write authorization then the events will be acknowledged after reading the new events. If the events in the
Realflo User and Reference Manual
May 19, 2011
623
Realflo Wizards log are not acknowledged, the event log will fill with 700 events.
Operator activity will be stopped until the events are read and acknowledged. This is the default selection.
Select Read All Events to read all events in the flow computer. Do not acknowledge the events.
Select Do Not Read Any Events to skip reading events.
The Which Alarms do you want to read? section has the following selections.
Select Just Read New Alarms to read unacknowledged alarms in the flow computer. If the operator has Write authorization then the alarms will be acknowledged after reading the new alarms. If the alarms in the log are not acknowledged, the alarm log will wrap around at 300 alarms.
This is the default selection.
Select Read All Alarms to read all alarms in the flow computer. Do not acknowledge the alarms.
Select Do Not Read Any Alarms to skip reading alarms.
The Back button returns to the previous step.
The Next button reads the selected alarms and events and moves to the next step, Select Hourly History.
The Cancel button closes the dialog and stops the wizard.
The Help button opens the on-line manual.
Bluetooth Security
If a Bluetooth connection was used to replace the flow computer in a
SolarPack 410 the last step is setting the Bluetooth security.
The Bluetooth Security Settings dialog specifies how Bluetooth security is configured in the SolarPack 410 controller. Opening the dialog reads the current settings from the controller. The dialog does not open if the settings can‟t be read.
Bluetooth Security selects if security is enabled or not. Select Use current
security settings to maintain the security settings that have already been
Realflo User and Reference Manual
May 19, 2011
624
Realflo Wizards established. Select Disable to operate the Bluetooth radio without security.
Select Enable to use authentication and encryption. Select Enable and
Change PIN to use authentication and encryption with a new PIN.
Current PIN specifies the current value of the PIN. Valid values are up to 10 alphanumeric characters (a to z, A to Z, and 0 to 9). The PIN is case sensitive. Characters entered are masked. Copy and paste are disabled (so the user needs to type the PIN). The factory default PIN is default.
New PIN specifies the new value of the PIN. This control is enabled if
Enable and Change PIN is selected. Valid values are up to 10 alphanumeric characters (a to z, A to Z, and 0 to 9). The PIN is case sensitive. Characters entered are masked. Copy and paste are disabled (so the user needs to type the PIN).
Confirm New PIN specifies the new value of the PIN. This control is enabled if Enable and Change PIN is selected. Valid values are up to 10 alphanumeric characters (a to z, A to Z, and 0 to 9). The PIN is case sensitive. Characters entered are masked. Copy and paste are disabled (so the user needs to type the PIN).
The two values of the new PIN need to match before any settings are written to the controller.
Click Finish to write the new settings to the controller. A message is displayed if the settings cannot be written to the controller and the dialog remains open.
Click Cancel to close the dialog without making any changes.
Realflo User and Reference Manual
May 19, 2011
625
Realflo Wizards
Read Logs and Flow History Wizard
The Read Logs and Flow History wizard will lead you through the steps to connect to a flow computer and read the alarm and event logs and the flow history.
<Back returns to the previous step in the wizard. This button is disabled on the first step of a wizard.
Next> moves to the next step in the wizard. This button is hidden on the last step of a wizard.
Finish is displayed on the final step of a wizard in place of the Next button. It finishes the operation. This button is hidden on other steps.
Cancel cancels the operation and closes the wizard. Steps performed thus far in the wizard are cancelled. Pressing the ESC key performs the same action as Cancel.
Help opens the user manual.
Connect to Flow Computer
This step lets you define the communication settings for the connection between the PC running the Realflo application and the target flow computer.
The How do you want to communicate with the flow computer? prompt provides two selections.
The Use the Current Settings option sets the default communication settings for Realflo. These settings are for the PC that is running Realflo.
(The communication settings for the PC running Realflo and the communication settings in the flow computer need to match).
The default communication settings are: COM 1 (serial port on the PC),
9600 baud, no parity, 8 Data bits, and 1 Stop bit. The default Modbus address Realflo will connect to is station 1.
Realflo User and Reference Manual
May 19, 2011
626
Realflo Wizards
Use this selection if the serial port on your PC is COM 1 and the serial port settings for the serial port on the flow computer are set for default (9600,
8,n,1 and Modbus address 1).
Click the Next> button to begin communication with the flow computer and move to the next step in the wizard.
The Choose/View Communication Setup option opens the PC
Communication Settings dialog as shown below. This allows you to view the default settings and to change the PC communication setting for the type of connection you are using to communicate with the flow computer.
See the section Communication >> PC Communication Settings
Command in the Realflo Expert Mode Reference section of this manual for complete details on the parameter settings in this dialog.
You need to know the communication settings for the connection to the flow computer to use this step.
Select Runs to Read
This step selects the flow run or runs to read.
The Select the Flow Run or Runs to Read selection determines if data for all runs or for a single run is read.
The All Runs radio button selects reading data for all runs.
Realflo User and Reference Manual
May 19, 2011
627
Realflo Wizards
The Selected Run radio button selects reading from a single run. The drop-down list selects the run to be read.
Click the Next> button to move to the next step in the wizard.
Select Flow Computer Configuration
This step selects whether the flow computer configuration is read from the flow computer with the logs and history.
Select Yes to read the flow run configuration.
Select No to not read the flow run configuration.
Select Alarm and Event Logs to Read
This step selects which alarms and events to read.
The Which Events do you want to read? selection determines which events to read from the flow computer.
Select Just Read New Events to read unacknowledged events in the flow computer. If the operator has View, Read and Write Data or
Administrator authorization then the events will be acknowledged after
Realflo User and Reference Manual
May 19, 2011
628
Realflo Wizards reading the new events. If the events in the log are not acknowledged, the event log will fill with 700 events. Operator activity will be prevented until the events are read and acknowledged. The control is grayed under the following conditions: o The event log is not selected. o The user has Read and View account privileges. o The Restrict Realflo users to reading all alarms and events option is selected in the Expert Mode Options menu.
Select Read All Events to read all events in the flow computer. This control is grayed if the Event Log control is not selected.
Select Do Not Read Any Events to skip reading of events from the flow computer.
The Which Alarms to you want to read? selection determines which alarm logs to read from the flow computer.
Select Just Read New Alarms to read unacknowledged alarms in the flow computer. If the operator has View, Read and Write Data or
Administrator authorization then the alarms will be acknowledged after reading the new events. If the events in the log are not acknowledged, the alarm log will fill with 300 events. Operator activity will be prevented until the alarms are read and acknowledged. The control is grayed under the following conditions:
The alarm log is not selected.
The user has Read and View account privileges.
The Restrict Realflo users to reading all alarms and events option is selected in the Expert Mode Options menu.
The Read All Alarms radio button selects the reading of all alarms in the controller. The control is grayed if the Alarm control is not selected.
The Do Not Read Any Alarms button selects not to read alarms from the flow computer.
Click the Next> button to move to the next step in the wizard.
Select Hourly and Daily History to Read
This step selects which hourly and daily logs to read.
Realflo User and Reference Manual
May 19, 2011
629
Realflo Wizards
The Which Hourly Logs do you want to read? selection determines which hourly history is read.
Select New Hours to read hourly history for hours after those current in the file. If the file is empty then Realflo will read all hourly history stored in the flow computer. This is the default selection.
Select All Days to read hourly history for all days stored in the flow computer.
Select Selected Hours to read hourly history for the range of days selected with the From and to drop-down lists. Records are read for the contract days whose first hour is within the date range. Records for the contract day are read, regardless of their calendar date. This may result in records with calendar days outside the range being added to the log.
For example, if the contract day is configured to start at 7:00 AM.
Reading hourly history for September 23 would return the records where the first record in a day was between 7:00 on the 23 the 24 th
. rd
to 6:59:59 AM on
The From control contains the oldest previous day for which the hourly history is to be read. The initial value is the current day. Change this date to avoid reading data that has previously been read into the log.
The to control contains the recent previous day for which the hourly history is to be read. The initial value is the current day. The allowed range is the same or greater than the value in the From control. Change this date when wanting to read older data only. Leaving this date at its default will result in the recent data being read.
Select the Do Not Read Hourly Logs to skip the reading of hourly logs.
The Which Daily Logs do you want to read? selection determines which hourly history is read.
Select New Days to read daily history for days after those in the current file. If the file is empty then Realflo will read hourly history stored in the flow computer. This is the default selection.
Realflo User and Reference Manual
May 19, 2011
630
Realflo Wizards
Select All Days to read daily history for all days stored in the flow computer.
Select Selected Days to read daily history for the range of days selected with the From and to drop-down lists. Records are read for the contract days whose first record is within the date range. Records for the contract day are read, regardless of their calendar date. This may result in records with calendar days outside the range being added to the log. For example, if the contract day is configured to start at 7:00
AM. Reading daily history for September 23 would return the daily records whose end time is in the range 7:00 on the 23 on the 24 th
. rd
to 6:59:59 AM
The From control contains the oldest previous day for which the daily history is to be read. The initial value is the current day. Change this date to avoid reading data that has previously been read into the log.
The to control contains the recent previous day for which the daily history is to be read. The initial value is the current day. The allowed range is the same or greater than the value in the From control. Change this date when wanting to read older data only. Leaving this date at its default will result in the recent data being read.
Select the Do Not Read Hourly Logs to skip the reading of hourly logs.
Click the Next> button to read the selected logs and history from the runs selected and move to the next step in the wizard.
The Read Logs Results page displays the results of the Read Logs and
History.
Click the Next> button to move to the next step in the wizard.
Realflo User and Reference Manual
May 19, 2011
631
Save Data
Realflo Wizards
This step saves the flow run configuration, if selected, and the logs and history.
Select Save to File name.tfc to save the data read to the currently opened file. The name of the current file is shown in place of file name.tfc.
Select Save to another file and enter a file name or click the Browse button to open the Save As dialog.
The following options allow you to specify the name and location of the file you're about to save:
The Save in: box lists the available folders and files.
The File name: box allows entry of a new file name to save a file with a different name. Realflo adds the extension you specify in the Save As type box.
The Save as type: box lists the types of files Realflo can save. Realflo can open flow computer (TFC) files and flow computer Template files (RTC).
Realflo User and Reference Manual
May 19, 2011
632
Export Data
Realflo Wizards
If the open file is a flow computer file and the Save as Type is a template file, Realflo will ask if the flow computer file should be saved before converting it to a template.
Save saves the file to the specified location.
The Cancel button closes the dialog without saving.
This step selects the file type to export data to.
Select Export to CFX format file to export the logs and history to a Flow-
Cal CFX format file. This format is designed for importing into Flow-Cal.
Data is exported to the CFX file from one flow run. The file includes data from the configuration, current readings, alarm log, event log and hourly history log.
When this option is selected the Export Data to CFX dialog is opened when the Finish button is clicked.
The CFX Export Setting button opens the CFX Export Settings dialog.
The parameters for this dialog are described in the CFX Export Settings section below.
Select Export to CSV format file to export the logs and history to a CSV
(comma-separated values) format file. This format can be read by spreadsheet and database software.
When this option is selected the Export Data to CSV dialog is opened when the Finish button is clicked.
The CSV Export Setting button opens the CSV Export Settings dialog.
The parameters for this dialog are described in the CSV Export Settings section below.
Select No, Do not export to skip the Export Data step.
When this option is selected the dialog is closed and the Read Logs
Flow History wizard is ended when the Finish button is clicked.
Export Data to CFX
This step selects what data to export to CFX.
Realflo User and Reference Manual
May 19, 2011
633
Realflo Wizards
Select All Alarms, Events and Hourly Logs to select all of the data in the flow run. This is the default button.
Select Selected Days to select the data from the contract days in the From and To dropdown lists.
The From dropdown list selects the oldest contract day. This control is enabled when the Selected Days radio button is selected.
The To dropdown list selects the recent contract day. This control is enabled when the Selected Days radio button is selected.
The Export Type dropdown list selects how export files are stored.
Select Specific File to export to a single file. A standard file save dialog opens to allow you to select the file name. The default file name is
<Realflo file name>(<FC ID>) - <Run Number> (<Run ID>).CFX.
Select Dated CFX to export one file per day to a single folder per run.
Realflo exports one file for each day. The file name is based on the time and date according to the CFX standard (YYYYMMDD.CFX).
Realflo User and Reference Manual
May 19, 2011
634
Save CFX Export
This step selects where to save the CFX export.
Realflo Wizards
Select Save to File name.CFX to save the CFX Export data to the currently opened file. The name of the current file is shown in place of file name.CFX.
The files that that will be created are shown in the display window.
Select Save to another file to save the CFX Export data to a different file name and location. Enter the name in the window or select Browse to open the Save As dialog and select a name and location.
The Save As dialog allows you to specify the file to export the data to.
Save exports the data to the selected file.
Cancel the export command and closes the dialogs.
Click the Next> button to complete the Read Logs and Flow history wizard and close the dialog.
Realflo User and Reference Manual
May 19, 2011
635
Export Data to CSV
This step selects what data to export to CSV.
Realflo Wizards
Select Hourly history to export the hourly history data.
Select Daily history to export the daily history data.
Select Alarm log to export the alarm log data.
Select Event log to export the event log data.
The Next> button moves to the Save CSV Export step in the wizard.
Realflo User and Reference Manual
May 19, 2011
636
Save CSV Export
This step selects where to save the CSV export.
Realflo Wizards
Select Save to File name.CSV to save the CSV Export data to the currently opened file. The name of the current file is shown in place of file name.CSV.
The files that that will be created are shown in the display window.
Select Save to another file to save the CSV Export data to a different file name and location. Enter the name in the window or select Browse to open the Save As dialog and select a name and location.
You may change the file name to any suitable name. The suggested file name format is defined in the CSV Export Options command.
The Save As file selection dialog appears for views. The Save As dialog allows you to specify the file to export the data to.
The Save button in the Save As dialog exports the data to the selected file.
Realflo User and Reference Manual
May 19, 2011
637
Realflo Wizards
The Cancel button in the Save As dialog cancels the export command and closes dialogs.
Realflo User and Reference Manual
May 19, 2011
638
Realflo Wizards
CFX Export Settings
The CFX Export Options dialog sets options for exporting to Flow-Cal CFX files. The settings in this dialog apply to files opened by Realflo. They are stored in the Windows registry.
The Hourly History section defines how records from the hourly history are exported.
Select Export Partial Hour Records to export of the records as they appear in Realflo. Some hours may contain more than one record due to power disconnection or configuration changes. This is the default selection.
Select Export One Record per Hour to export only one record per hour. Multiple records within an hour are merged into a single record for exporting. Hours that are not yet complete are not merged or exported.
The following hourly record fields are summed: volume, mass, energy, pulses (turbine type).
The following hourly record fields are averaged: termperature, static pressure, differential pressure (orifice types), relative density, flow product
or flow extension. See Input Averaging on page 948 for more information.
Select Time Leads Data Format to export the date and time at the start of the period. The time stamp on the record is the time at the start of the
Realflo User and Reference Manual
May 19, 2011
639
Realflo Wizards hour, even if the first record to be merged started later than that time.
This option is enabled only when Export One Record per Hour is checked. This option is unchecked by default.
The File Description section defines some descriptive parameters in the
CFX file.
Meter Number defines the meter number parameter. The options are
none, Flow Computer ID, Flow Run ID and Flow Run Number. The default value is Flow Computer ID. The parameter is 17 characters long in the file.
Meter Name defines the meter name parameter. The options are none,
Flow Computer ID, Flow Run ID and Flow Run Number. The default value is Flow Run ID. The parameter is 49 characters long in the file.
Serial Number defines the meter serial number parameter in the file.
The options are none, Flow Computer ID, Flow Run ID and Flow Run
Number. The default value is Flow Run Number. The parameter is 11 characters long in the file.
The Live Inputs Flags section defines which live input flags are set by
Realflo. The CFX file contains four flags in the Live Inputs parameter.
Realflo sets the T (temperature) flag to Y (live data). The other flags are normally set to N (not live), but can be modified using the following options.
Check Set Live Gas Composition Flag when there is a program that updates the gas composition. This is flag A (analysis). This option is unchecked by default.
Check Set Live Energy Flag when there is a program that updates the energy. This is flag B (heating value). This option is unchecked by default.
Check Set Live Gravity Flag when there is a program that updates the specific gravity (relative density). This is flag G (gravity). This option is unchecked by default.
The Default Name Format section defines what file names Realflo suggests when exporting. The names are combinations of the file name;
Flow Computer ID; flow run number; and flow run ID.
Format selects the name format. The valid values are listed below. The default is to include all information. o file name (Flow Computer ID) - Run# (run ID) o file name (Flow Computer ID) - Run# o file name (Flow Computer ID) - run ID o file name - Run# (run ID) o file name - Run# o file name - run ID o Flow Computer ID - Run# (run ID) o Flow Computer ID - Run# o Flow Computer ID - run ID o Run# (run ID)
Realflo User and Reference Manual
May 19, 2011
640
Realflo Wizards o run ID
The Example control shows the file name that will be suggested for the current file.
The Dated CFX section defines where and how CFX files are exported.
Select Use .CFX extension on folder names to create folders with a
CFX extension when exporting Dated CFX files. The data for each month is stored in its own folder when using the Dated CFX format. The folder name may have a CFX extension or not. This option is unchecked by default.
Select Export Dated CFX Files to the Folder to define a common folder for exports. Exported data will be placed in this folder. The option is unchecked by default. When checked, the edit control holds the destination folder that will appear in the Save As dialog. Use Browse to search for another folder.
Realflo User and Reference Manual
May 19, 2011
641
Realflo Wizards
CSV Export Settings
The CSV Export Options command defines whether optional data is exported to CSV files. The settings in this dialog apply to files opened by
Realflo. They are stored in the Windows registry.
The Hourly and Daily Records section of the dialog defines optional data to include and how the data is time stamped.
Select the Include Uncorrected Flow in AGA-7 Export option to export the Uncorrected Data column from the Hourly History Log and
Daily History Log. This option applies to AGA-7 only. The option is unchecked by default.
Select the Export in Time Leads Data Format option to export time stamps that mark the start of the period. Uncheck the option to export time stamps that mark the end of the period (Realflo format). This applies to the the Hourly History and Daily History only. The control is unchecked by default.
The Default File Name Format section defines the file name that is suggested by Realflo when data is exported. The names are combinations of the file name; Flow Computer ID; flow run number; and flow run ID.
The Format list selects the name format. The name is made up of the identifier format and a view format. The valid values for the identifier are listed below. The default is to include all information. o file name (Flow Computer ID) - Run# (run ID) - Type o file name (Flow Computer ID) - Run# - Type o file name (Flow Computer ID) - run ID - Type o file name - Run# (run ID) - Type o file name - Run# - Type o file name - run ID - Type o Flow Computer ID - Run# (run ID) - Type o Flow Computer ID - Run# - Type o Flow Computer ID - run ID - Type o Run# (run ID) - Type o run ID - Type
Realflo User and Reference Manual
May 19, 2011
642
Realflo Wizards
When the logs are exported the word Type is replaced by the following, according to the export selected. o Alarms o Events o Hourly Log o Daily Log o Current Readings o Custom View Name
The Example control shows the file name that will be suggested for the current file.
Calibrate Inputs Wizard
The Calibrate Inputs wizard is used to calibrate the temperature sensor, static pressure sensor, and differential pressure sensor or pulse counter input. The calibration dialogs lead you through the calibration procedure.
When more than one sensor is selected, they are each forced and then the calibration cycle will be allowed for each sensor in turn. This allows multiple variable transmitters such as the MVT to be calibrated.
WARNING
The same input sensor can be used for more than one flow run. When the sensor is calibrated for one run, Realflo only forces the input value for that run. When the sensor is disconnected to do the calibration, the live input to the other run will be disconnected and the value will not be correct. The flow computer does not support forcing of inputs during calibration on more than one run.
For each step in the wizard a dialog is presented to enter the parameters for the step. Each dialog contains four buttons to allow navigation through the wizard.
<Back returns to the previous step in the wizard. This button is disabled on the first step of a wizard.
Next> moves to the next step in the wizard. This button is hidden on the last step of a wizard.
Finish is displayed on the final step of a wizard in place of the Next button. It finishes the operation. This button is hidden on other steps.
Cancel cancels the operation and closes the wizard. All steps performed thus far in the wizard are cancelled. Pressing the ESC key performs the same action as Cancel.
Help opens the user manual.
Connect to Flow Computer
The connect to flow computer step defines the communication settings for the connection between the PC running the Realflo application and the target flow computer.
Realflo User and Reference Manual
May 19, 2011
643
Realflo Wizards
The How do you want to communicate with the flow computer? prompt provides two selections.
The Use the Current Settings option sets the default communication settings for Realflo. These settings are for the PC that is running Realflo.
(The communication settings for the PC running Realflo and the communication settings in the flow computer need to match).
The default communication settings are: COM 1 (serial port on the PC),
9600 baud, no parity, 8 Data bits, and 1 Stop bit. The default Modbus address Realflo will connect to is station 1.
Use this selection if the serial port on your PC is COM 1 and the serial port settings for the serial port on the flow computer are set for default (9600,
8,n,1 and Modbus address 1).
Click the Next> button to begin communication with the flow computer and move to the next step in the wizard.
The Choose/View Communication Setup option opens the PC
Communication Settings dialog as shown below. This allows you to view the default settings and to change the PC communication setting for the type of connection you are using to communicate with the flow computer.
See the section Communication >> PC Communication Settings
Command in the Realflo Expert Mode Reference section of this manual for complete details on the parameter settings in this dialog.
You need to know the communication settings for the connection to the flow computer to use this step.
Realflo User and Reference Manual
May 19, 2011
644
Realflo Wizards
Sensor Calibration
When the Calibration wizard is selected the Sensor Calibration dialog is displayed. The Run, or Sensor, to be calibrated is selected from this dialog.
The Sensor Calibration dialog allows the selection meter run or MVT for calibration.
Select the Run radio button and then select a meter run to calibrate.
Transmitters used for the meter run may be calibrated. This section is disabled if runs are using sensors
Select Sensor radio button and select one of the sensor tags to calibrate a sensor. Sensor tags that have been configured will be in sensor selection box.
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log.
The back button is not enabled on the first step since there is no previous step.
Realflo User and Reference Manual
May 19, 2011
645
Realflo Wizards
The Next> button starts the calibration procedure. After the Run, or sensor, is selected, the configuration for the run is read from the flow computer. The
Run, or sensor, calibration page for the run is then displayed.
The Cancel button closes the dialog and stops the transmitter calibration.
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
WARNING
Realflo uses live values from the sensor when calibration is cancelled. Be sure to connect all sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Run Calibration Procedure
When the Run radio button is selected the Run Calibration dialog is displayed. The transmitters for the run are selected for calibration from this dialog.
WARNING
The same input sensor can be used for more than one flow run. When the sensor is calibrated for one run, Realflo only forces the input value for that run. When the sensor is disconnected to do the calibration, the live input to the other run will be disconnected and the value will not be correct. The flow computer does not support forcing of inputs during calibration on more than one run.
Realflo User and Reference Manual
May 19, 2011
646
Realflo Wizards
Select the sensors to be calibrated by checking the appropriate boxes. More than one sensor may be selected for calibration.
The <Back button is not enabled as this is the initial step.
The Next> button completes the selections and opens the Step 1: Force
Value dialog.
The Cancel button closes the dialog and stops the transmitter calibration.
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
The same input sensor can be used for more than one flow run. When the sensor is calibrated for one run, Realflo only forces the input value for that run. When the sensor is disconnected to do the calibration, the live input to the other run will be disconnected and the value will not be correct. The flow computer does not support forcing of inputs during calibration on more than one run.
WARNING
Realflo uses live values from the sensor when calibration is cancelled. Be sure to connect all sensors first.
Realflo User and Reference Manual
May 19, 2011
647
Realflo Wizards
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Realflo User and Reference Manual
May 19, 2011
648
Realflo Wizards
Calibration Step 1: Force Value
The flow calculations continue to execute while calibrating sensors. The sensor value needs to be forced to either the current value or a fixed value during calibration. This dialog lets you select the current value of the input or a fixed value of your choice.
When more than one sensor is selected, they need to each be forced to a current or fixed value before any of the other steps are performed. A Step 1:
Force Value dialog will be presented for each sensor selected for calibration.
The input register associated with this input is displayed to aid you in determining which input you are calibrating.
Check the Current Value radio button to use the current value for the sensor.
Check the Fixed Value radio button and enter a value to use for the calibration in the entry box.
The No Change radio button will be selected if the value is currently forced. (You may still select one of the other two radio buttons if desired).
The <Back button returns to the previous step. Backing up does not erase events from the Flow Computer event log.
When the Next> button is pressed Realflo records the start of calibration for the sensor in the event log. The sensor input is forced. The sensor can now be removed from the process.
The Cancel button closes the dialog and stops the transmitter calibration.
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
Realflo User and Reference Manual
May 19, 2011
649
Realflo Wizards
WARNING
Realflo uses live values from the sensor when calibration is cancelled. Be sure to connect all sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Realflo User and Reference Manual
May 19, 2011
650
Realflo Wizards
Calibration Step 2: Record As Found Values
As-found readings indicate how the sensor was calibrated before adjustment. These can be used to correct flow measurement errors resulting from an out of calibration sensor. Follow the procedure your company has set for taking as-found readings. You needs to record at least one
“asfound
” reading.
To take as-found readings:
Apply a known signal to the sensor, or measure the signal applied to the sensor with a calibrated instrument.
Enter the applied value in the Applied Value edit box.
The measured value from the process in the Measured Value box.
When it has settled, click on the Record button to record an as-found reading.
Repeat the process to record additional readings.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For Run Calibration the deviation is calculated as follows. The output full scale and zero scale are taken from the input configuration for the run. span = input full scale – input zero scale deviation = (measured - applied) / span
<Back returns to the previous step. Backing up does not erase events from the flow computer event log.
Next> proceeds to the next step.
Realflo User and Reference Manual
May 19, 2011
651
Realflo Wizards
The Cancel button is greyed and an as found reading needs to be recorded.
When you click Cancel to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
WARNING
Realflo uses live values from the sensor when calibration is cancelled. Be sure to connect all sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Realflo User and Reference Manual
May 19, 2011
652
Realflo Wizards
Calibration Step 3: Calibration Required
The as-found readings indicate if calibration is required. Examine the list of as-found readings. If the sensor is in need of calibration, select Yes.
Otherwise select No.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For Run Calibration the deviation is calculated as follows. The output full scale and zero scale are taken from the input configuration for the run. span = input full scale – input zero scale deviation = (measured - applied) / span
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log.
The Next> button proceeds to the next step.
The Cancel button is grayed and an as found reading needs to be recorded.
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
WARNING
Realflo uses live values from the sensor when calibration is cancelled. Be
Realflo User and Reference Manual
May 19, 2011
653
Realflo Wizards sure to connect all sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Realflo User and Reference Manual
May 19, 2011
654
Realflo Wizards
Calibration Step 4: Calibrate Sensor
This dialog aids you in calibrating a sensor by displaying the measured value from the sensor and the as-found readings.
Follow the procedure your company or the sensor supplier has set to calibrate the sensor. When the sensor calibration is complete, you may wish to check the as-left measurements that will be recorded in the next step.
This confirms that you have calibrated the sensor correctly before placing it back in service.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For Run Calibration the deviation is calculated as follows. The output full scale and zero scale are taken from the input configuration for the run. span = input full scale – input zero scale deviation = (measured - applied) / span
Click on the Next> button when the calibration is complete.
Realflo User and Reference Manual
May 19, 2011
655
Realflo Wizards
Calibration Step 5: Record As Left Values
As-left readings indicate how the sensor was calibrated. These can be used to verify sensor calibration. Follow the procedure your company has set for taking as-left readings. You need to record at least one as-left reading.
To take as-left readings:
Apply a known signal to the sensor, or measure the signal applied to the sensor with a calibrated instrument.
Enter the applied value in the Applied Value edit box.
When the measured value from the process has settled, click on the
Record button to record an as-left reading.
Repeat the process to record additional readings.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For Run Calibration the deviation is calculated as follows. The output full scale and zero scale are taken from the input configuration for the run. span = input full scale – input zero scale deviation = (measured - applied) / span
When the required readings are taken, click on the Next> button.
Realflo User and Reference Manual
May 19, 2011
656
Realflo Wizards
Calibration Step 6: Restore Live Input
The sensors need to be reconnected to the process and the input hardware before calibration is complete. Reconnect sensors and verify connections are correct.
Click on the Next button when the sensor is connected.
WARNING
The live value from all sensors is used as soon as you click Next. Be sure to connect al sensors first.
Realflo User and Reference Manual
May 19, 2011
657
Realflo Wizards
Calibration Step 6: Calibration Report Comment
Realflo creates, stores, and prints calibration reports for each calibration session performed. Comments may be added to the calibration report using the Calibration Report Comment dialog as shown below.
Enter any comments or leave the window blank.
Click the Next button when completed entering comments.
Realflo User and Reference Manual
May 19, 2011
658
Realflo Wizards
Calibration Step 7: Calibration Report
The Calibration Report dialog allows the saving of the calibration report.
Realflo User and Reference Manual
May 19, 2011
Select Save Report to File to save the report. o Type the name of the report in the Save Report to File window.
The default location and name are specified on the Calibration
Report Options dialog. o Select Browse to select a different file name.
Check View Calibration Report After Saving the File to view the saved calibration report file. Default is checked.
Select Do not Save Report to skip saving the calibration report.
Click the Finis button to complete the calibration process.
If selected the Calibration report will be displayed as shown below.
659
Realflo Wizards
MVT Calibration Procedure
When the MVT radio button is selected in the Sensor Calibration dialog the
MVT Calibration dialog is displayed.
The transmitter number, transmitter tag name, the communication port and the transmitter address associated with this MVT transmitter are displayed to aid you in determining which input you are calibrating.
Check the Calibrate Temperature Sensor check box to select the temperature sensor for calibration. This will add the Temperature to the
Calibration order list box.
Check the Calibrate Static Pressure Sensor check box to select the static pressure sensor for calibration. This will add the Static Pressure to the Calibration order list box.
Check the Calibrate Differential Pressure Sensor check box to select the differential pressure sensor for calibration. This will add the Diff.
Pressure to the Calibration order list box.
The Calibration Order list displays the list of sensors to be calibrated.
Sensors are calibrated in order from the top of the list.
Select Move Up button to move the specified item in the list up. The button is disabled if highlight item is on the top of the list or the list is empty.
Select Move Down button to move the specified item in the list down.
The button is disabled if highlight item is on the bottom of the list or the list is empty.
The <Back button is not enabled as this is the initial step.
The Next> button completes the selections and opens the Step 1: Force
Value dialog.
The Cancel button closes the dialog and stops the transmitter calibration.
Realflo User and Reference Manual
May 19, 2011
660
Realflo Wizards
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
The live value from each sensor is used as soon as you click Next. Connect al sensors first.
WARNING
Realflo uses live values from the sensor when calibration is cancelled. Be sure to connect all sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Realflo User and Reference Manual
May 19, 2011
661
Realflo Wizards
Calibration Step 1: Force Value
The flow calculations continue to execute while calibrating sensors. The sensor value needs to be forced to either the current value or a fixed value during calibration. This dialog lets you select the current value of the input or a fixed value of your choice.
When more than one sensor is selected, they need to each be forced to a current or fixed value before any of the other steps are performed.
Select the value you wish to use, for each sensor, by clicking the appropriate radio button for each sensor.
Check the Current Value radio button to use the current value for the sensor.
Check the Fixed Value radio button and enter a value to use for the calibration in the entry box.
The No Change radio button will be selected if the value is currently forced. (You may still select one of the other two radio buttons if desired).
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log.
When the Next> button is pressed Realflo records the start of calibration for the sensor in the event log. The sensor input is forced. The sensor can now be disconnected to the process.
The Cancel button closes the dialog and stops the transmitter calibration.
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
Realflo User and Reference Manual
May 19, 2011
662
Realflo Wizards
Realflo uses live values from the sensor when calibration is cancelled.
Connect sensors first.
WARNING
Realflo uses live values from the sensor when calibration is cancelled.
Be sure to connect all sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Realflo User and Reference Manual
May 19, 2011
663
Realflo Wizards
Calibration Step 2: Record As-Found Values
As-found readings indicate how the sensor was calibrated before adjustment. These can be used to correct flow measurement errors resulting from an out of calibration sensor. Follow the procedure your company has set for taking as-found readings. You need to record at least one as-found reading.
Realflo will record As-Found values to the unit types selected for the meter run. If the units type for the meter run and the MVT are not the same then the MVT units are scaled to the meter run units.
To take as-found readings:
Apply a known signal to the sensor, or measure the signal applied to the sensor with a calibrated instrument.
Enter the applied value in the Applied Value edit box.
The measured value from the process is in the Measured Value box.
When it has settled, click on the Record button to record an as-found reading.
Repeat the process to record additional readings.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For MVT Calibration the deviation is calculated as follows. The operating limits are read from the flow computer. span = upper range limit - lower range limit deviation = (measured - applied) / span
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log.
The Next> button proceeds to the next step.
Realflo User and Reference Manual
May 19, 2011
664
Realflo Wizards
The Cancel button is grayed and an as found reading needs to be recorded.
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
WARNING
Realflo uses live values from the sensor when calibration is cancelled. Be sure to connect all sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Realflo User and Reference Manual
May 19, 2011
665
Realflo Wizards
Calibration Step 3: Calibration Required
The as-found readings indicate if calibration is required. Examine the list of as-found readings. If the sensor is in need of calibration, select Yes.
Otherwise select No.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For Run Calibration the deviation is calculated as follows. The output full scale and zero scale are taken from the input configuration for the run. span = input full scale – input zero scale deviation = (measured - applied) / span
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log.
The Next> button proceeds to the next step.
The Cancel button is grayed and an as found reading needs to be recorded.
When you click the Cancel button to abort the calibration the following message is displayed. Click Yes to abort the calibration. Click No to continue with the calibration. The default button is No.
Realflo User and Reference Manual
May 19, 2011
WARNING
666
Realflo Wizards
Realflo uses live values from the sensor when calibration is cancelled. Be sure to connect all sensors first.
Realflo does not erase any calibration events from the flow computer when canceling.
The Help button displays the online help file.
Calibration Step 4: Calibrate SCADAPack 4101, 4202 or 4203
Step four in the calibration procedure varies depending on the type of transmitter being calibrated. Use this section if you are calibrating a
SCADAPack 4102 or a SCADAPack 4202 or 4203.
This dialog aids you in calibrating a sensor by displaying the measured value from the sensor and the as-found readings.
Follow the procedure your company or the sensor supplier has set to calibrate the sensor. When the sensor calibration is complete, you may wish to check the as-left measurements that will be recorded in the next step.
This confirms that you have calibrated the sensor correctly before placing it back in service.
The Static Pressure can only have a span calibration performed if at least 5% of the rated pressure is applied.
The RTD Zero can only be adjusted +/- 1% of the RTD upper limit, typically 8.5 degrees C, relative to the settings used when a reset sensor command was last issued.
The list box displays as-found values listed in the list of Record As-Found
Values dialog.
The Measured Value displays the measured value from the sensor.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
Realflo User and Reference Manual
May 19, 2011
667
Realflo Wizards
For MVT Calibration the deviation is calculated as follows. The operating limits are read from the flow computer. span = upper range limit - lower range limit deviation = (measured - applied) / span
Realflo User and Reference Manual
May 19, 2011
668
Realflo Wizards
Calibration Step 4: Calibrate SCADAPack 4101
Step four in the calibration procedure varies depending on the type of transmitter being calibrated. Use this section if you are calibrating a
SCADAPack 4101 transmitter.
The as-found readings, for each sensor, will indicate if calibration is required for the sensor. You are prompted to use the 4000 Configurator application to perform the calibration. The 4000 Configurator software is installed from the
Control Microsystems Hardware Documentation CD.
The Next> button proceeds to the next step.
The Help button displays the online help file.
Realflo User and Reference Manual
May 19, 2011
669
Realflo Wizards
Calibration Step 4: Calibrate 3095 MVT
Step four in the calibration procedure varies depending on the type of transmitter being calibrated. Use this section if you are calibrating a 3905 transmitter.
This dialog aids you in calibrating a sensor by displaying the measured value from the sensor and the as-found readings.
Follow the procedure your company or the sensor supplier has set to calibrate the sensor. When the sensor calibration is complete, you may wish to check the as-left measurements that will be recorded in the next step.
This confirms that you have calibrated the sensor correctly before placing it back in service.
The list box displays as-found values listed in the list of Record As-Found
Values dialog.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For MVT Calibration the deviation is calculated as follows. The operating limits are read from the flow computer. span = upper range limit - lower range limit deviation = (measured - applied) / span
The Calibrate Sensor section of the Calibrate Sensor dialog displays the current calibration settings and selectable radio buttons for configuring the sensor calibration.
The Radio buttons enable the changing of the zero and span for the
Temperature, Static Pressure and Differential Pressure sensors. For
Temperature sensors, an additional radio button allows the user to fix the
Temperature value in the event the temperature reading is outside the configured limits.
Select the Re-Zero radio button to enable a new entry in the Applied
Value field. This field displays the current zero value. The button is
Realflo User and Reference Manual
May 19, 2011
670
Realflo Wizards labeled Re-Zero if the Re-Zero radio button is selected. Clicking the
Re-Zero button writes the zero applied value to the transmitter immediately.
Select the Calculate Span radio button to enable a new entry in the
Applied Value field. This field displays the current span value. The button is labeled Calibrate if the Calibrate Span radio button is selected. Clicking the Calibrate button writes the span applied value to the transmitter immediately.
When calibrating the temperature sensor you may select the Default
Temperature radio button to enable a new entry in the Applied Value field.
The button is labeled Set if the Default Temperature radio button is selected. The transmitter returns the fixed temperature value if the RTD is not working, or if the RTD is not connected. The valid range is
–40 to 1200
F or
–40 to 648.89
C. The default value is 60
F or 15.56
C. The new fixed temperature point is written to the transmitter immediately.
The Measured Value displays the measured value from the sensor.
Realflo records the points at which MVT calibration was performed in the event log.
Each time the Re-Zero button is clicked the following information is recorded.
Event Name
Current Value
Previous Value
MVT Re-zero
The applied value entered by the user
The measured value from the controller
Each time the Calibrate button is clicked the following information is recorded.
Event Name
Current Value
Previous Value
MVT Span Calibration
The applied value entered by the user
The measured value from the controller
Realflo User and Reference Manual
May 19, 2011
671
Realflo Wizards
Calibration Step 5: Record As Left Values
As-left readings indicate how the sensor was calibrated. These can be used to verify sensor calibration. Follow the procedure your company has set for taking as-left readings. You need to record at least one as-left reading.
Realflo will record all As Found values to the units type selected for the meter run. If the units type for the meter run and the MVT are not the same then the MVT units are scaled to the meter run units.
To take as-left readings:
Apply a known signal to the sensor, or measure the signal applied to the sensor with a calibrated instrument.
Enter the applied value in the Applied Value edit box.
The measured value from the process is displayed. When it has settled, click on the Record button to record an as-left reading.
As readings are recorded they are automatically entered in the record window. The applied values are listed under the Applied column. The measured values are listed under the Measured column and the deviation between the readings is listed under the Deviation column.
For MVT Calibration the deviation is calculated as follows. The operating limits are read from the flow computer. span = upper range limit - lower range limit deviation = (measured - applied) / span
Repeat the process to record additional readings.
When required readings are taken, click on the Next> button.
Realflo User and Reference Manual
May 19, 2011
672
Realflo Wizards
Calibration Step 6: Restore Live Input
The sensors need to be reconnected to the process and the input hardware before calibration is complete. Reconnect sensors and verify connections are correct.
Click on the Finish button when the sensor is connected.
WARNING
The live value from all sensors is used as soon as the Finish button is clicked. Be sure to connect all sensors first.
Realflo User and Reference Manual
May 19, 2011
673
Realflo Wizards
Calibration Step 7: Calibration Report Comment
Realflo creates, stores, and prints calibration reports for each calibration session performed. Comments may be added to the calibration report using the Calibration Report Comment dialog as shown below.
Enter any comments or leave the window blank.
Click the Next button when completed entering comments.
Realflo User and Reference Manual
May 19, 2011
674
Realflo Wizards
Calibration Step 8: Calibration Report
The Calibration Report dialog allows the saving of the calibration report.
Realflo User and Reference Manual
May 19, 2011
Select Save Report to File to save the report. o Type the name of the report in the Save Report to File window.
The default location and name are specified on the Calibration
Report Options dialog. o Select Browse to select a different file name.
Check View Calibration Report After Saving the File to view the saved calibration report file. Default is checked.
Select Do not Save Report to skip saving the calibration report.
Click the Finis button to complete the calibration process.
If selected the Calibration report will be displayed as shown below.
675
Realflo Wizards
Change Orifice Plate Wizard
The Change Orifice Plate wizard enables the orifice plate to be changed for
AGA-3 meter runs. This wizard supports Dual Chamber Orifice fittings and
Singe Chamber Orifice fittings. This wizard will prompt you through the plate change procedure.
For each step in the wizard a dialog is presented to enter the parameters for the step. Each dialog contains four buttons to allow navigation through the wizard.
<Back returns to the previous step in the wizard. This button is disabled on the first step of a wizard.
Next> moves to the next step in the wizard. This button is hidden on the last step of a wizard.
Finish is displayed on the final step of a wizard in place of the Next button. It finishes the operation. This button is hidden on other steps.
Cancel cancels the operation and closes the wizard. Steps performed thus far in the wizard are cancelled. Pressing the ESC key performs the same action as Cancel.
Help opens the user manual.
Connect to Flow Computer
The connect to flow computer step defines the communication settings for the connection between the PC running the Realflo application and the target flow computer.
The How do you want to communicate with the flow computer? prompt provides two selections.
The Use the Current Settings option sets the default communication settings for Realflo. These settings are for the PC that is running Realflo.
(The communication settings for the PC running Realflo and the communication settings in the flow computer need to match).
The default communication settings are: COM 1 (serial port on the PC),
9600 baud, no parity, 8 Data bits, and 1 Stop bit. The default Modbus address Realflo will connect to is station 1.
Realflo User and Reference Manual
May 19, 2011
676
Realflo Wizards
Use this selection if the serial port on your PC is COM 1 and the serial port settings for the serial port on the flow computer are set for default (9600,
8,n,1 and Modbus address 1).
Click the Next> button to begin communication with the flow computer and move to the next step in the wizard.
The Choose/View Communication Setup option opens the PC
Communication Settings dialog as shown below. This allows you to view the default settings and to change the PC communication setting for the type of connection you are using to communicate with the flow computer.
See the section Communication >> PC Communication Settings
Command in the Realflo Expert Mode Reference section of this manual for complete details on the parameter settings in this dialog.
You need to know the communication settings for the connection to the flow computer to use this step.
Select Meter Run
This step selects which meter run the orifice plate is to be changed.
The Run dropdown selection displays runs using AGA
–3 flow calculations.
Select the run to change or inspect the orifice plate.
Realflo User and Reference Manual
May 19, 2011
677
Realflo Wizards
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log. Realflo does not attempt to reverse the effect of a previous step when backing up. For example, backing up to the force values step does not restore the live values.
The Next> button completes the run selection and the wizard moves to the next step. This button is grayed if there are no flow runs configured to use the AGA-3 flow calculation.
The Cancel button aborts the plate change and displays the following message.
Click Yes to abort the calibration.
Click No to continue with the plate change. The default button is No.
WARNING
Realflo uses live values from the sensor when the plate change is cancelled.
Be sure to connect all sensors first.
Realflo does not erase any events from the flow computer when the plate change is cancelled. Realflo restores live values (ends forcing) when Cancel is clicked.
The Help button displays the online help file.
Choose Orifice Fitting Type Step
This page allows the user to select the type of orifice fitting.
Realflo User and Reference Manual
May 19, 2011
678
Realflo Wizards
Select Dual Chamber Orifice Fitting if a dual chamber fitting is present.
Flow accumulation with estimated values will continue during the plate change.
Select Singe Chamber Orifice Fitting if a single chamber fitting is present.
Flow accumulation will stop during the plate change.
The Next button moves to the next step.
The next step is described in the section
if a dual chamber fitting is selected.
The next step is described in the section
single chamber fitting is selected.
The Cancel button closes the dialog and stops the plate change procedure.
The Help button displays the online Help file.
Dual Chamber Orifice
A dual chamber orifice allows the user to change, or inspect, the orifice plate without stopping the flow. These are generally large custody transfer sites where the orifice fitting is bypassed during the change or inspection procedure.
The Change Orifice Plate Command forces the Static Pressure, Differential
Pressure and Temperature inputs to a fixed value during the orifice plate change or inspection procedure. This command is disabled if the Update
Readings command is enabled. The flow is estimated during the procedure using the fixed values.
This command allows a user to place a flow run into estimation mode to allow an orifice plate to be changed or inspected. Changing the orifice plate involves the following steps.
Set the estimated flow to be used during the orifice plate change by forcing inputs to fixed values.
Change the orifice size.
Complete the orifice plate change and resume normal flow measurement.
The Flow Computer ID is checked when the Change Orifice Plate command is selected. If the Flow Computer ID does not match the ID Realflo displays the message “ The Flow Computer ID from the flow computer does not match the Flow Computer ID from the file
.” The command is aborted.
Realflo User and Reference Manual
May 19, 2011
679
Force Input Step
Realflo Wizards
This step forces the flow run inputs. An estimated flow will be calculated while the plate change is in progress. The current values are updated every second.
Select the value you wish to use, for each sensor, by clicking the appropriate radio button for each sensor.
Check the Current Value radio button to use the current value for the sensor.
Check the Fixed Value radio button and enter a value to use for the calibration in the entry box.
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log. Realflo does not attempt to reverse the effect of a previous step when backing up. For example, backing up to the force values step does not restore the live values.
The Next> button completes the force inputs step and the wizard moves to the next step. Realflo records the start of the plate change procedure in the event log and forces the sensor inputs.
The Cancel button aborts the plate change and displays the following message.
Click Yes to abort the calibration.
Realflo User and Reference Manual
May 19, 2011
680
Realflo Wizards
Click No to continue with the plate change. The default button is No.
WARNING
Realflo uses live values from the sensor when the plate change is cancelled.
Be sure to connect all sensors first.
Realflo does not erase any events from the flow computer when the plate change is cancelled. Realflo restores live values (ends forcing) when Cancel is clicked.
The Help button displays the online help file.
Realflo User and Reference Manual
May 19, 2011
681
Realflo Wizards
Change Orifice Plate Step
The orifice plate can now be changed. The forced inputs are used while the change is in progress. This dialog allows you to enter the new orifice plate diameter.
The Current Orifice Diameter and Current Pipe Diameter are displayed for reference.
Enter the new orifice size in the New Orifice Diameter entry box. If the diameter is not valid, Realflo displays the following a message box.
You need to enter a valid orifice diameter. Click the OK button to return to the Change Orifice dialog.
The Beta Ratio is calculated and displayed for orifice diameter changes.
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log. Realflo does not attempt to reverse the effect of a previous step when backing up. For example, backing up to the force values step does not restore the live values.
The Next> button completes the change orifice step and the wizard moves to the last step.
The Cancel button aborts the plate change and displays the following message.
Realflo User and Reference Manual
May 19, 2011
682
Realflo Wizards
Click Yes to abort the calibration.
Click No to continue with the plate change. The default button is No.
WARNING
Realflo uses live values from the sensor when the plate change is cancelled.
Be sure to connect all sensors first.
Realflo does not erase any events from the flow computer when the plate change is cancelled. Realflo restores live values (ends forcing) when Cancel is clicked.
The Help button displays the online help file.
Realflo User and Reference Manual
May 19, 2011
683
Realflo Wizards
Complete Orifice Plate Change
The Finish Plate Change is the last step in the Plate Change wizard.
Single Chamber Orifice
A single chamber orifice requires the flow be stopped while an orifice plate is changed.
The Change Orifice Plate command prompts the user to stop the flow before changing the plate and start the flow after changing the plate.
Changing the orifice plate involves the following steps.
Confirm that flow has stopped.
Change the orifice size.
Complete the orifice plate change.
The Flow Computer ID is checked when the Change Orifice Plate command is selected. If the Flow Computer ID does not match the ID Realflo displays the message “ The Flow Computer ID from the flow computer does not match the Flow Computer ID from the file.” The command is aborted.
Stop Flow Step
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log. Realflo does not attempt to reverse the effect of a previous step when backing up. For example, backing up to the force values step does not restore the live values.
The Finish button completes the orifice plate change wizard and closes the dialog. Realflo restores the sensor live values
The Help button displays the online help file.
This step stops the flow run. The current inputs can be monitored while the flow is stopped.
Realflo User and Reference Manual
May 19, 2011
684
Realflo Wizards
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log. Realflo does not attempt to reverse the effect of a previous step when backing up. For example, backing up to the force values step does not restore the live values.
The Next> button completes the Stop Flow step and the wizard moves to the next step. Realflo records the start of the plate change procedure in the event log and forces the sensor inputs.
The Cancel button aborts the plate change and closes the wizard.
The Help button displays the online help file.
Change Orifice Plate Step
The orifice plate can now be changed. The forced inputs are used while the change is in progress. This dialog allows you to enter the new orifice plate diameter.
The Current Orifice Diameter and Current Pipe Diameter are displayed for reference.
Realflo User and Reference Manual
May 19, 2011
685
Realflo Wizards
Enter the new orifice size in the New Orifice Diameter entry box. If the diameter is not valid, Realflo displays the following a message box.
You need to enter a valid orifice diameter. Click the OK button to return to the Change Orifice dialog.
The Beta Ratio is calculated and displayed for orifice diameter changes.
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log. Realflo does not attempt to reverse the effect of a previous step when backing up.
The Next> button completes the change orifice step and the wizard moves to the last step.
The Cancel button aborts the plate change and closes the wizard.
The Help button displays the online help file.
Complete Orifice Plate Change
The Finish Plate Change is the last step in the Plate Change wizard.
The <Back button returns to the previous step. Backing up does not erase events from the flow computer event log. Realflo does not attempt to reverse the effect of a previous step when backing up.
The Finish button completes the orifice plate change wizard and closes the dialog. Realflo restores the sensor live values
The Help button displays the online help file.
Realflo User and Reference Manual
May 19, 2011
686
Realflo Wizards
Force Inputs Wizard
The Force Sensor wizard allows forcing and unforcing of the value of the temperature sensor, static pressure sensor, differential pressure sensor, or pulse counter input. Flow calculations continue to execute while sensors are forced.
The flow computer ID is checked when the Force Inputs command is selected. If the flow computer ID does not match the ID in the dialog Realflo displays the message “ The Flow Computer ID from the flow computer does not match the Flow Computer ID from the file.”
For each step in the wizard a dialog is presented to enter the parameters for the step. Each dialog contains four buttons to allow navigation through the wizard.
<Back returns to the previous step in the wizard. This button is disabled on the first step of a wizard.
Next> moves to the next step in the wizard. This button is hidden on the last step of a wizard.
Finish is displayed on the final step of a wizard in place of the Next button. It finishes the operation. This button is hidden on other steps.
Cancel cancels the operation and closes the wizard. Steps performed thus far in the wizard are cancelled. Pressing the ESC key performs the same action as Cancel.
Help opens the user manual.
Connect to Flow Computer
The connect to flow computer step defines the communication settings for the connection between the PC running the Realflo application and the target flow computer.
The How do you want to communicate with the flow computer? prompt provides two selections.
The Use the Current Settings option sets the default communication settings for Realflo. These settings are for the PC that is running Realflo.
Realflo User and Reference Manual
May 19, 2011
687
Realflo Wizards
(The communication settings for the PC running Realflo and the communication settings in the flow computer need to match).
The default communication settings are: COM 1 (serial port on the PC),
9600 baud, no parity, 8 Data bits, and 1 Stop bit. The default Modbus address Realflo will connect to is station 1.
Use this selection if the serial port on your PC is COM 1 and the serial port settings for the serial port on the flow computer are set for default (9600,
8,n,1 and Modbus address 1).
Click the Next> button to begin communication with the flow computer and move to the next step in the wizard.
The Choose/View Communication Setup option opens the PC
Communication Settings dialog as shown below. This allows you to view the default settings and to change the PC communication setting for the type of connection you are using to communicate with the flow computer.
See the section Communication >> PC Communication Settings
Command in the Realflo Expert Mode Reference section of this manual for complete details on the parameter settings in this dialog.
You need to know the communication settings for the connection to the flow computer to use this step.
Select Run or Transmitter to Force
This step selects the run or transmitter to force.
Realflo User and Reference Manual
May 19, 2011
688
Realflo Wizards
Select Run to force the sensor inputs for a flow run using analog or pulse sensors. Select the run to be forced from the dropdown list. The Run controls are disabled if there are no runs using analog or pulse sensors.
below for information on forcing Run
inputs.
Select MVT to force the inputs from an MVT. Select the MVT to be forced from the dropdown list beside it. The MVT controls are disabled if there are no transmitters configured.
Inputs below for information on
forcing MVT inputs.
The Back button is disabled, as this is the first step in the wizard.
The Next starts the force procedure.
The Cancel closes the wizard.
The Help displays the online help file.
Force Run Inputs
When the Force Run is selected the Force Input Values dialog is displayed as shown below. The Force Input Values step selects the analog inputs of a
Realflo User and Reference Manual
May 19, 2011
689
Realflo Wizards flow run which will be forced or unforced. It displays the inputs that can be forced.
The Force Input Value dialog contains sections for Force Differential
Pressure Input, Force Static Pressure Input and Force Temperature Input.
When AGA-7 calculation type is used the dialog contains a section for Force
Pulse Counter Input instead of Force Differential Pressure Input.
For each input the following parameters are available:
Select Current Value to use the current value for the sensor. The current value is shown beside the control and updates continuously.
Select Fixed Value to use a fixed value. Type the value in the edit box.
Select No Change, input is already forced to leave the input in its current state. This is selected by default if the value is already forced.
This is disabled if the input is not forced.
Select Remove to remove the existing forcing. This button is disabled if the input is not forced.
The Back button moves back to the Select Run or Transmitter to Force step.
Backing up does not erase events from the flow computer event log, or remove forcing from inputs previously processed.
The Finish button completes the Force Input Value process and closes the dialog.
The Cancel button closes the wizard. This does not undo any changes. Any input that is already forced will remain forced.
The Help displays the online help file.
Force MVT Inputs
This step shows the selected MVT inputs. The inputs can be forced to the current value or a fixed value, left as it is, or the forcing can be removed.
The transmitter number, transmitter tag name, the communication port and
Realflo User and Reference Manual
May 19, 2011
690
Realflo Wizards the transmitter address associated with this MVT transmitter are displayed to aid you in determining which input you are forcing.
The MVT Values dialog contains sections for Force Differential Pressure,
Force Static Pressure and Force Temperature.
For each input the following parameters are available:
Select Current Value to use the current value for the sensor. The current value is shown beside the control and updates continuously.
Select Fixed Value to use a fixed value. Type the value in the edit box.
Select No Change, input is already forced to leave the input in its current state. This is selected by default if the value is already forced.
This is disabled if the input is not forced.
Select Remove Force to remove the existing forcing. This button is disabled if the input is not forced.
The Back button moves back to the Select Run or Transmitter to Force step. Backing up does not erase events from the flow computer event log, or remove forcing from inputs previously processed.
The Finish button completes the Force Input Value process and closes the dialog.
The Cancel button closes the wizard. This does not undo any changes. Any input that is already forced will remain forced.
The Help displays the online help file.
The same MVT can be used for more than one flow run. Realflo forces the value for each run.
Realflo User and Reference Manual
May 19, 2011
691
TeleBUS Protocol Interface
TeleBUS Protocol Interface
This section describes communication with a SCADA system.
Data interchange, including flow history data, is accomplished using the
TeleBUS protocol. TeleBUS is fully compatible with standard Modbus drivers.
Data may be retrieved over any SCADA communications system while taking advantage of the error detection and non-proprietary nature of the
Modbus protocol.
Register Addresses
The TeleBUS protocol registers used by the flow calculation routine for configuration, display and data archiving are called holding registers.
Holding registers have a five-digit address in the range of 40001 to 49999.
The data values in these registers may be read or written to by any software package that supports the Modbus protocol.
TeleBUS Registers Used by the Flow Computer
The flow calculation routine in the flow computer uses holding registers in the ranges shown below. These registers are described in the following sections of this manual. A Telepace Ladder Logic program that may be executing simultaneously on the flow computer cannot use the registers in this range.
Configuration and Control Registers 49500 to 49999
Requested Data Registers
Meter Run 1 Data Registers
Meter Run 2 Data Registers
Meter Run 3 Data Registers
48500 to 49499.
47500 to 48499
46500 to 47499
45500 to 46499
Requested Daily History Registers
Meter Run 4 Data Registers
Meter Run 5 Data Registers
Meter Run 6 Data Registers
Meter Run 7 Data Registers
Meter Run 8 Data Registers
Meter Run 9 Data Registers
Meter Run 10 Data Registers
MVT Configuration Registers
MVT Data Registers
MVT Internal Registers
Display Configuration Registers
44500 to 45499.
44400 to 44499
44300 to 44399
44200 to 44299
44100 to 44199
44000 to 44099
43900 to 43999
43800 to 43899
43700 to 43799
43600 to 43689
38000 to 38999
43470 to 43499
Realflo User and Reference Manual
May 19, 2011
692
TeleBUS Protocol Interface
Process I/O Configuration Registers
43400 to 43469
Uncorrected Accumulated Flow, runs 1 to 10 43300 to 43398
SolarPack Configuration/Accumulation
43180 to 43260
In addition to the above registers the SCADAPack 4202 and 4203 controllers use the following registers for transmitter parameters and data.
These registers cannot be used if a SCADAPack 4202 or 4203 controller is used.
SCADAPack 4202 and 4203 data and parameters registers
40001 to
40499
Data Formats
The TeleBUS protocol interface allows for data access and configuration locally or remotely, using any software running the Modbus protocol. Data are stored in several formats in registers. Some formats take more than one register for a number. These are described in the table below.
Data
Type
sint uint slong ulong float userID runID
Registers
Required
1
1
2
2
2
4
8
Description
Signed integer in the range
–32767 to
32767.
Unsigned integer in the range 0 to 65535.
Signed long integer in the range
-2,147,483,647 to 2,147,483,647. The lower numbered register contains the higher order word.
Unsigned long integer in the range 0 to
4,294,967,295. The lower numbered register contains the higher order word.
IEEE single precision floating-point number. The lower numbered register contains the higher order word.
8-byte string packed into four registers.
The first register contains the first two characters of the string, etc. The first character is in the low order byte, the second in the high order byte.
The string is terminated with a NULL (= 0) character if it is less than 8 characters. Set the first register to 0 to indicate a NULL
(empty) string.
16-byte string packed into eight registers.
The first register contains the first two characters of the string, etc. The first character is in the low order byte, the second in the high order byte.
The string is terminated with a NULL (= 0) character if it is less than 16 characters.
Set the first register to 0 to indicate a NULL
(empty) string.
Realflo User and Reference Manual
May 19, 2011
693
TeleBUS Protocol Interface
Data
Type
RunID2
Registers
Required
16
Description
32-byte string packed into 16 registers.
The first register contains the first two characters of the string, etc. The first character is in the low order byte, the second in the high order byte.
The string is terminated with a NULL (= 0) character if it is less than 32 characters.
Set the first register to 0 to indicate a NULL
(empty) string.
Register Data Formats
The HMI or SCADA Host Software in use with the flow computer calculations needs to either support these data formats with the Modbus protocol or allow for custom scripting such that numeric data written to, or read from the flow computer, can be interpreted in these formats.
Meter Run 1 Data Registers
This section contains a of tables listing Meter Data Registers utilized by the flow computer (gas flow routines). These registers display data from each meter run. The flow computer continuously updates these registers.
The registers shown in this section are for meter run 1. Data for additional meter runs will start at lower addresses.
Execution State Registers
These registers contain the execution state of the flow calculation.
Actual
Register
47500
47501
Data
Type
uint unit
Description
Meter run = 1
Execution state:
1 = stopped
2 = running
Meter 1 Execution State Registers
Instantaneous and Accumulated Readings Registers
The instantaneous readings registers contain flow data. The values are instantaneous results. The Source column indicates the calculation that produces the value.
Values produced by the input, flow and accumulation calculations are updated once per second. Values produced by the compressibility calculation are updated each time the compressibility calculation recalculates. This time varies according to the calculation type and the changes in the inputs to the calculation (including configuration parameters).
Check the time of the last update registers to determine when the calculation was performed.
Values for the previous contract day are updated at the end of the contract day. Values for the current contact day include flow for the contract day, even if an event causes a separate day record in the hourly history.
Actual
Register
Data
Type Description Source
Realflo User and Reference Manual
May 19, 2011
694
Actual
Register
43390
Data
Type
float
43392
43394
43396
43398
47502
47504
47505
47506
47507
47508 float float float float uint uint uint uint
Uint
Uint
TeleBUS Protocol Interface
Description
Uncorrected flow volume during the current day (AGA-
7 only)
Uncorrected flow volume during the previous contract day (AGA-7 only)
Uncorrected flow volume during the current month
(AGA-7 only)
Uncorrected flow volume during the previous month
(AGA-7 only)
Source
Accumulation
Accumulation
Accumulation
Accumulation
Not used
Calibration flags
The calibration flag register indicates whether input values are forced or live.
Bit 0 = Get current temperature
Bit 1 = Get current static pressure
Bit 2 = Get current differential pressure or mass flow
Bit 3 = Get current pulse rate
Bit 4 = Temperature is forced
Bit 5 = Static pressure is forced
Bit 6 = Differential pressure is forced
Bit 7 = Pulse rate is forced
Bit 14 = Generate calibration event
Bit 15 = Generate orifice plate change event
A bit set indicates input is forced.
See also registers 47522
–
47528 and registers 47556,
47558 and 48470.
Compressibility approximated flag
0 = compressibility value is calculated result
1 = compressibility value is approximate
Input
Flow calculation
Input or flow calculation error code
Compressibility calculation error code
Flow calculation
Compressibility calculation
Temperature Input Alarm Input
Static Pressure Input Alarm Input
Realflo User and Reference Manual
May 19, 2011
695
Actual
Register
47509
47510
47512
47514
47516
47518
47520
47522
47524
47526
47528
47530
47532
47534
47536
47538
47540
47542
47544
47546
47548
TeleBUS Protocol Interface
Data
Type
Uint Differential Pressure (AGA-3 and V-Cone only)
Turbine Pulses (AGA-7 only) input Alarm ulong Turbine meter pulses (AGA-
7 only) ulong Number of flow calculations during the contract day float float
Description
Date of flow update (days since Jan 1, 1970)
Time of flow update
(seconds since 00:00:00) float float float float float float
Date of compressibility update (days since Jan 1,
1970)
Time of compressibility update (seconds since
00:00:00)
Temperature
Static pressure
Differential pressure (AGA-3 and V-Cone only)
Mass flow rate (AGA-11 only)
Flow volume rate float float float float float float float float float float
Flow mass rate
Flow energy rate
Flow extension (AGA-3 1990 only)
Flow product (AGA-3 1985 only)
Uncorrected flow volume
(AGA-7 only)
Supercompressibility
Flow calculation
Flow calculation
Flow calculation
Flow calculation
Real relative gas density
Mass density at flow conditions
Mass density at base conditions
Heating value
Duration of flow during the contract day (seconds)
Flow volume at base conditions during the contract day
Source
Input
Input
Accumulation
Flow calculation
Flow calculation
Compressibility calculation
Input
Input
Input
Compressibility calculation
Compressibility calculation
Compressibility calculation
Compressibility calculation
Density calculation
Accumulation
Accumulation
Realflo User and Reference Manual
May 19, 2011
696
TeleBUS Protocol Interface
Actual
Register
47550
47552
47554
47556
47558
48470
48472
48474
48476
48478
48490
48492
48494
48496
48498
Data
Type
float float float float float float float float float
Description
Flow mass at base conditions during the contract day
Flow energy at base conditions during the contract day
Total accumulated flow volume at base conditions
Forced Temperature
Forced Static Pressure
Forced Differential Pressure
(AGA-3 and V-Cone only)
Flow duration in current month.
Flow volume in current month
Flow duration in previous month float ulong Forced Pulse Rate (AGA-7 only) float
Flow volume in previous month
Date of last flow configuration change (days since January 1, 1970). float Time of last flow configuration change
(seconds since midnight). float float
Date of last density configuration change (days since January 1, 1970).
Time of last density configuration change
(seconds since midnight).
Source
Accumulation
Accumulation
Accumulation
Input
Input
Input
Accumulation
Accumulation
Accumulation
Accumulation
Input
Current readings
Current readings
Current readings
Current readings
Instantaneous and Accumulated Readings Registers
Actual
Register
48480
48482
48484
48486
Data
Type
float float float float
Description
Duration of flow during the previous contract day
(seconds)
Flow volume at base conditions during the previous contract day
Flow mass at base conditions during the previous contract day
Flow energy at base conditions during the previous contract day
Source
Accumulation
Accumulation
Accumulation
Accumulation
Realflo User and Reference Manual
May 19, 2011
697
Actual
Register
48488
Data
Type Description
ulong Number of flow calculations during the previous contract day
Previous Day Accumulated Readings Registers
TeleBUS Protocol Interface
Source
Accumulation
Daily Flow History Data Registers
Daily flow data registers are updated automatically at the beginning of each new contract day, and a user querry is not required to be refreshed. There are 35 days consisting of 26 History Registers each. The table Meter 1
Daily Flow History - Day 1 Registers shows the registers associated with the recent day of data only. The table Meter 1 Daily Flow History - Days 2
through 35 Registers shows the registers used for days 2 through 35. Day
1 is the recent day
Actual
Register
47560
Data
Type
float
47562
47564
47566
47568
47570
47572
47574
47576
47578
47580
47582 float float float float float float float float float float float
Description
Date at the end of the period (days since Jan 1,
1970)
Time at the end of the period (seconds since
00:00:00)
Duration of flow in the period
Flow volume at base conditions
Flow mass at base conditions
Flow energy at base conditions
Flow extension (AGA-3 1990 only)
Flow product (AGA-3 1985 only)
Uncorrected flow volume (AGA-7 only)
Average temperature
Average static pressure
Average differential pressure (AGA-3 and V-Cone only)
Average number of rotations per second (AGA-7 only)
Average real relative gas density
Realflo User and Reference Manual
May 19, 2011
698
TeleBUS Protocol Interface
Actual
Register
47584
Data
Type
float
Description
Units code = input units code + (contract units code
* 32)
The units code field indicates the units in use at the time the log entry was made. The codes for the input units and contract units are listed below. Both are combined in a single floating-point value to save space in the log.
Units Units Code
US1
US2
0
1
US3
IP
2
3
Metric1
Metric2
Metric3
SI
US4
4
5
6
7
8
US5
US6
US7
9
10
11
US8 12
Meter 1 Daily Flow History - Day 1 Registers
Actual
Register
Data Type
47586 to 47611 See Day 1 Structure
47612 to 47637 See Day 1 Structure
47638 to 47663 See Day 1 Structure
47664 to 47689 See Day 1 Structure
47690 to 47715 See Day 1 Structure
47716 to 47741 See Day 1 Structure
47742 to 47767 See Day 1 Structure
47768 to 47793 See Day 1 Structure
47794 to 47819 See Day 1 Structure
47820 to 47845 See Day 1 Structure
47846 to 47871 See Day 1 Structure
47872 to 47897 See Day 1 Structure
47898 to 47923 See Day 1 Structure
47924 to 47949 See Day 1 Structure
47950 to 47975 See Day 1 Structure
47976 to 48001 See Day 1 Structure
48002 to 48027 See Day 1 Structure
48028 to 48053 See Day 1 Structure
48054 to 48079 See Day 1 Structure
48080 to 48105 See Day 1 Structure
48106 to 48131 See Day 1 Structure
48132 to 48157 See Day 1 Structure
48158 to 48183 See Day 1 Structure
48184 to 48209 See Day 1 Structure
48210 to 48235 See Day 1 Structure
48236 to 48261 See Day 1 Structure
Description
2 nd most recent contract day
3 rd
most recent contract day
4
5 th th
most recent contract day
most recent contract day
6 th
most recent contract day
7
8 th th
most recent contract day
most recent contract day
9 th
most recent contract day
10 th
most recent contract day
11 th
most recent contract day
12
13 th th
most recent contract day
most recent contract day
14 th
most recent contract day
15
16 th th
most recent contract day
most recent contract day
17
18
19 th th th
most recent contract day
most recent contract day
most recent contract day
20
21 th st
most recent contract day most recent contract day
22 nd
most recent contract day
23 rd
most recent contract day
24 th
most recent contract day
25
26 th th
most recent contract day
most recent contract day
27 th
most recent contract day
Realflo User and Reference Manual
May 19, 2011
699
TeleBUS Protocol Interface
Actual
Register
Data Type
48262 to 48287 See Day 1 Structure
48288 to 48313 See Day 1 Structure
48314 to 48339 See Day 1 Structure
48340 to 48365 See Day 1 Structure
48366 to 48391 See Day 1 Structure
48392 to 48417 See Day 1 Structure
48418 to 48443 See Day 1 Structure
48444 to 48469 See Day 1 Structure
Description
28 th
most recent contract day
29
30
31 th th st
most recent contract day
most recent contract day
most recent contract day
32 nd
most recent contract day
33 rd
most recent contract day
34 th
most recent contract day
35 th
most recent contract day
Meter 1 Daily Flow History - Days 2 through 35 Registers
Meter Run 2 Data Registers
The registers for meter 2 are organized in the same manner as meter 1. The registers for each meter start at a different offset. The table below shows the registers used for meter run 2.
Actual
Register
Data Type
46500 to 47489 See meter run 1 Data
Structure above
43380 to 43389 See Uncorrected Flow
Accumulated Readings
Registers above
Description
Meter run 2 Data
Registers.
Meter run 2 Uncorrected
Flow Registers
Meter Run 3 Data Registers
The registers for meter 3 are organized in the same manner as meter 1. The registers for each meter start at a different offset. The table below shows the registers used for meter run 3.
Actual
Register
Data Type
45500 to 46489 See meter run 1 Data
Structure above
43370 to 43379 See Uncorrected Flow
Accumulated Readings
Registers above
Description
Meter run 3 Data
Registers.
Meter run 3 Uncorrected
Flow Registers
Meter Run 4 Data Registers
The registers for meter 4 do not contain the daily history that is provided for runs 1 to 3. The data structures for meter runs 4 to 10 do not contain the full
daily flow history to conserve register space. See the section
Meter Runs 4 to 10 Daily Flow History Registers
for daily flow history data for these
meter runs.
The tables below show the structure. The flow computer continuously updates these registers.
Execution State Registers
These registers contain the execution state of the flow calculation.
Actual
Register
44400
Data
Type
uint
Description
Meter run = 4
Realflo User and Reference Manual
May 19, 2011
700
TeleBUS Protocol Interface
Actual
Register
44401
Data
Type
uint
Description
Execution state:
1 = stopped
2 = running
Meter 4 Execution State Registers
Instantaneous and Accumulated Readings Registers
The instantaneous readings registers contain flow data. The values are instantaneous results. The Source column indicates the calculation that produces the value.
Values produced by the input, flow and accumulation calculations are updates once per second. Values produced by the compressibility calculation are updated each time the compressibility calculation recalculates. This time varies according to the calculation type and the changes in the inputs to the calculation (including configuration parameters).
Check the time of last update registers to determine when the calculation was performed.
Values for the previous contract day are updated at the end of the contract day. Values for the current contract day include flow for the contract day, even if an event causes a separate day record in the hourly history.
Actual
Register
43360
Data
Type
float
43362
43364
43366
43368
44402 float float float float uint
Description
Uncorrected flow volume during the previous month (AGA-7 only)
Uncorrected flow volume during the current month (AGA-7 only)
Uncorrected flow volume during the previous contract day
(AGA-7 only)
Uncorrected flow volume during the contract day (AGA-7 only)
Not used
Calibration flags
Bit 0 = Get current temperature
Bit 1 = Get current static pressure
Bit 2 = Get current differential pressure or mass flow
Bit 3 = Get current pulse rate
Bit 4 = Temperature is forced
Bit 5 = Static pressure is forced
Bit 6 = Differential pressure is forced
Bit 7 = Pulse rate is forced
Bit 14 = Generate calibration event
Bit 15 = Generate orifice plate change event.
Bit set indicates input is forced.
Source
Accumulation
Accumulation
Accumulation
Accumulation
Input
Realflo User and Reference Manual
May 19, 2011
701
Actual
Register
44404
44405
44406
44407
44408
44409
44410
44412
44414
44416
44418
44420
44422
44424
44426
44428
44430
44432
44434
44436
44438
44440
44442
44444
TeleBUS Protocol Interface
Data
Type
uint
Description
Compressibility approximated flag
0 = compressibility value is calculated result
1 = compressibility value is approximate uint uint uint uint
Input or flow calculation error code
Compressibility calculation error code
Temperature Input Alarm
Static Pressure Input Alarm uint Differential Pressure (AGA-3 and V-Cone only)
Turbine Pulses (AGA-7 only) input Alarm slong Turbine meter pulses (AGA-7 only) slong Number of flow calculations during the contract day float Date of flow update (days since
Jan 1, 1970) float float float
Time of flow update (seconds since 00:00:00)
Date of compressibility update
(days since Jan 1, 1970)
Time of compressibility update
(seconds since 00:00:00) float float
Temperature
Static pressure float float float float float float float float float float
Source
Flow calculation
Flow calculation
Compressibility calculation
Input
Input
Input
Input
Accumulation
Flow calculation
Flow calculation
Compressibility calculation
Input
Input
Differential pressure (AGA-3 and V-Cone only)
Mass flow rate (AGA-11 only)
Flow volume rate
Flow mass rate
Flow energy rate
Input
Flow calculation
Flow calculation
Flow calculation
Flow calculation Flow extension (AGA-3 1990 only)
Flow product (AGA-3 1985 only)
Uncorrected flow volume (AGA-
7 only)
Supercompressibility
Real relative gas density
Compressibility calculation
Compressibility calculation
Mass density at flow conditions Compressibility calculation
Mass density at base conditions Compressibility calculation
Heating value Density calculation
Realflo User and Reference Manual
May 19, 2011
702
TeleBUS Protocol Interface
Actual
Register
44446
44448
44450
44452
44454
44456
44458
44460
44462
44464
44466
44468
44470
44472
44474
44476
44478
44490
44492
44494
44496
44498
Data
Type
float float float float float float float
Description
Duration of flow during the contract day (seconds)
Flow volume at base conditions during the contract day
Flow mass at base conditions during the contract day
Flow energy at base conditions during the contract day
Total accumulated flow volume at base conditions
Duration of flow during the previous contract day (seconds)
Flow volume at base conditions during the previous contract day
Source
Accumulation
Accumulation
Accumulation
Accumulation
Accumulation
Accumulation
Accumulation float float
Flow mass at base conditions during the previous contract day
Flow energy at base conditions during the previous contract day
Accumulation
Accumulation ulong Number of flow calculations during the previous contract day float Forced Temperature float float float
Forced Static Pressure
Forced Differential Pressure
(AGA-3 and V-Cone only)
Accumulation
Input
Input
Input
Forced mass flow rate (AGA-11 only)
Flow duration in current month. Accumulation float float float
Flow volume in current month Accumulation
Flow duration in previous month Accumulation
Flow volume in previous month Accumulation
Input ulong Forced Pulse Rate (AGA-7 only) float Date of last flow configuration float change (days since January 1,
1970).
Time of last flow configuration change (seconds since midnight). float float
Date of last density configuration change (days since January 1, 1970).
Time of last density configuration change (seconds since midnight).
Current readings
Current readings
Current readings
Current readings
Instantaneous and Accumulated Readings Registers
Meter Runs 4 to 10 Daily Flow History Registers
Realflo User and Reference Manual
May 19, 2011
703
TeleBUS Protocol Interface
The data structures for meter runs 4 to 10 do not contain the full daily flow history to conserve register space.
For SCADAPack 32 and SCADAPack 330/334, SCADAPack 350 controllers only the following registers can be used to display the daily flow history for any flow run. This includes runs 1 to 3.
to load the history data into these
registers.
There are 35 days consisting of 26 History Registers each. The table Meter
1 Daily Flow History - Day 1 Registers shows the registers associated with the recent day of data only. The table Meter 1 Daily Flow History -
Days 2 through 35 Registers shows the registers used for days 2 through
35. Day 1 is the recent day.
Actual
Register
44560
44562
44564
44566
44568
44570
44572
44574
44576
44578
44580
44582
Data
Type
float float float float float float float float float float float float
Description
Date at the end of the period (days since Jan 1,
1970)
Time at the end of the period (seconds since
00:00:00)
Duration of flow in the period
Flow volume at base conditions
Flow mass at base conditions
Flow energy at base conditions
Flow extension (AGA-3 1990 only)
Flow product (AGA-3 1985 only)
Uncorrected flow volume (AGA-7 only)
Average temperature
Average static pressure
Average differential pressure (AGA-3 and V-Cone only)
Average number of rotations per second (AGA-7 only)
Average real relative gas density
Realflo User and Reference Manual
May 19, 2011
704
TeleBUS Protocol Interface
Actual
Register
44584
Data
Type
float
Description
Units code = input units code + (contract units code
* 32)
The units code field indicates the units in use at the time the log entry was made. The codes for the input units and contract units are listed below. Both are combined in a single floating point value to save space in the log.
Units Units Code
US1
US2
0
1
US3
IP
2
3
Metric1
Metric2
Metric3
SI
US4
4
5
6
7
8
US5
US6
US7
9
10
11
US8 12
Daily Flow History - Day 1 Registers
Actual Data Type
Register Description
44586 to 44611 See Day 1 Structure 2 nd
most recent contract day
44612 to 44637 See Day 1 Structure 3 rd
most recent contract day
44638 to 44663 See Day 1 Structure 4
44664 to 44689 See Day 1 Structure 5 th th
most recent contract day
most recent contract day
44690 to 44715 See Day 1 Structure 6 th
most recent contract day
44716 to 44741 See Day 1 Structure 7
44742 to 44767 See Day 1 Structure 8 th th
most recent contract day
most recent contract day
44768 to 44793 See Day 1 Structure 9 th
most recent contract day
44794 to 44819 See Day 1 Structure 10 th
most recent contract day
44820 to 44845 See Day 1 Structure 11 th
most recent contract day
44846 to 44871 See Day 1 Structure 12
44872 to 44897 See Day 1 Structure 13 th th
most recent contract day
most recent contract day
44898 to 44923 See Day 1 Structure 14 th
most recent contract day
44924 to 44949 See Day 1 Structure 15
44950 to 44975 See Day 1 Structure 16 th th
most recent contract day
most recent contract day
44976 to 45001
45002 to 45027
See Day 1 Structure
See Day 1 Structure
17
18
45028 to 45053 See Day 1 Structure 19 th th th
most recent contract day
most recent contract day
most recent contract day
45054 to 45079 See Day 1 Structure 20
45080 to 45105 See Day 1 Structure 21 th st
most recent contract day
most recent contract day
45106 to 45131 See Day 1 Structure 22 nd
most recent contract day
45132 to 45157 See Day 1 Structure 23
45158 to 45183 See Day 1 Structure 24 rd th
most recent contract day
most recent contract day
45184 to 45209 See Day 1 Structure 25
45210 to 45235 See Day 1 Structure 26 th th
most recent contract day
most recent contract day
45236 to 45261 See Day 1 Structure 27 th
most recent contract day
Realflo User and Reference Manual
May 19, 2011
705
TeleBUS Protocol Interface
Actual Data Type
Register Description
45262 to 45287 See Day 1 Structure 28 th
most recent contract day
45288 to 45313
45314 to 45339
See Day 1 Structure
See Day 1 Structure
29
30
45340 to 45365 See Day 1 Structure 31 th th st
most recent contract day
most recent contract day
most recent contract day
45366 to 45391 See Day 1 Structure 32 nd
most recent contract day
45392 to 45417 See Day 1 Structure 33 rd
most recent contract day
45418 to 45443 See Day 1 Structure 34 th
most recent contract day
45444 to 45469 See Day 1 Structure 35 th
most recent contract day
Daily Flow History - Days 2 through 35 Registers
Get Daily History Command
The daily history is comprised of 35 days worth of data that is written into a block of registers when the flow computer is queried. This command can read hourly history for any run. The history for runs 1 to 3 is also available in dedicated registers for those runs.
Only the host computer, application program, or Realflo can send commands to the flow computer at one time. Command Reply Registers
49505 and 49506 will indicate an error if more than one host sends a command at one time.
Use the following procedure to execute the command.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type Description
uint Command: 12 (Get Daily History) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the command succeeded.
Location
49505
49506
Data
Type Description
uint
Echo command or error from Flow Calculation
uint Specific to error. Meter run if the command was successful.
Read the Data Registers.
Location Data Type Description
44560 to 45469 see table Daily totals are displayed.
Meter Run 5 Data Registers
The registers for meter 5 are organized in the same manner as meter 4. The registers for each meter start at a different offset. The table below shows the registers used for meter run 5.
Actual
Register
Data Type
44300 to 44399 See meter run 4 Data
Structure above
Description
Meter run 5 Data
Registers.
Realflo User and Reference Manual
May 19, 2011
706
Actual
Register
Data Type
43350 to 43359 See Uncorrected Flow
Accumulated Readings
Registers above
TeleBUS Protocol Interface
Description
Meter run 5 Uncorrected
Flow Registers
Meter Run 6 Data Registers
The registers for meter 6 are organized in the same manner as meter 4. The registers for each meter start at a different offset. The table below shows the registers used for meter run 6.
Actual
Register
Data Type
44200 to 44299 See meter run 4 Data
Structure above
43340 to 43349 See Uncorrected Flow
Accumulated Readings
Registers above
Description
Meter run 6 Data
Registers.
Meter run 6 Uncorrected
Flow Registers
Meter Run 7 Data Registers
The registers for meter 7 are organized in the same manner as meter 4. The registers for each meter start at a different offset. The table below shows the registers used for meter run 7.
Description Actual
Register
Data Type
44100 to 44199 See meter run 4 Data
Structure above
43330 to 43339 See Uncorrected Flow
Accumulated Readings
Registers above
Meter run 7 Data
Registers.
Meter run 7 Uncorrected
Flow Registers
Meter Run 8 Data Registers
The registers for meter 8 are organized in the same manner as meter 4. The registers for each meter start at a different offset. The table below shows the registers used for meter run 8.
Description Actual
Register
Data Type
44000 to 44099 See meter run 4 Data
Structure above
43320 to 43329 See Uncorrected Flow
Accumulated Readings
Registers above
Meter run 8 Data
Registers.
Meter run 8 Uncorrected
Flow Registers
Meter Run 9 Data Registers
The registers for meter 9 are organized in the same manner as meter 4. The registers for each meter start at a different offset. The table below shows the registers used for meter run 9.
Realflo User and Reference Manual
May 19, 2011
707
Actual
Register
Data Type
43900 to 43999 See meter run 4 Data
Structure above
43310 to 43319 See Uncorrected Flow
Accumulated Readings
Registers above
TeleBUS Protocol Interface
Description
Meter run 9 Data
Registers.
Meter run 9 Uncorrected
Flow Registers
Meter Run 10 Data Registers
The registers for meter 10 are organized in the same manner as meter 4.
The registers for each meter start at a different offset. The table below shows the registers used for meter run 10.
Actual
Register
Data Type
43800 to 43899 See meter run 4 data
Structure above
43300 to 43309 See Uncorrected Flow
Accumulated Readings
Registers above
Description
Meter run 10 Data
Registers.
Meter run 8 Uncorrected
Flow Registers
TeleBUS Configuration Registers
This section of the User Manual describes the configuration of the Gas flow computer using the TeleBUS communication protocol. TeleBUS protocol is fully compatible with standard Modbus drivers.
This method of configuration is typically used in a SCADA system where the host computer is required to modify flow computer operating parameters through the SCADA communication system. Command sequences enable the modification of flow computer parameters by authorized users.
Only the host computer, application program, or Realflo can send commands to the flow computer at one time. Command reply registers
49505 and 49506 will indicate an error if more than one host sends a command at one time.
This section contains a of tables listing configuration registers utilized by the flow computer (gas flow routines). The gas flow data is updated to the tables using the various Get commands. The Set commands write data in the tables to the flow computer.
The registers labeled, as Actual Registers in the tables are the registers containing the values already in use by the flow calculation routines. The registers labeled as Config. Registers are the registers used for loading new configuration values to the flow calculation routines.
Configuration changes are not passed to the flow calculation routines until the command has been entered and verification has taken place where applicable. Configuration values already in use may be loaded into separate registers for viewing on command.
Realflo does not allow configuration changes if the Event Log in the flow computer is full. Use the Read Logs/History command to empty the flow computer Event Log.
Realflo User and Reference Manual
May 19, 2011
708
TeleBUS Protocol Interface
Configuration Command Execution
Entering a command consists of writing the appropriate command number into the Command Register and the appropriate meter number into the
Meter Run Register. To stop unauthorized command entry, and to allow for recording of user commands in the event log, a user number and PIN number needs to be specified before a command is executed.
Only the host computer, application program, or Realflo can send commands to the flow computer at one time. Command reply registers
49505 and 49506 will indicate an error if more than one host sends a command at one time.
Configuration commands are written to registers starting at location 49500.
Write to the registers starting at location 49500 and then read the Command
Register (49500) until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command number from 1 to 2203. See
command numbers.
Meter run number from 1 to 10
User number needs to correspond to the PIN number as entered in the user accounts table. The default value is 1 if no User accounts have been created in Realflo. See the
Accounts
command for more information on user number.
The PIN needs to correspond to the PIN as entered in the user accounts table. The default value is 1 if no user accounts have been created in
Realflo. See
Accounts
command for more information on PIN.
Feedback to the user is provided through a Command Reply Register, which will indicate the same command number as was requested, if the command was accepted and executed. In the event that the command could not be carried out, an error code is loaded into the Command Reply
Register indicating the reason that the command was not accepted.
The Reply Registers become valid after the Command Register is changed to zero by the flow computer.
Replies to commands are read from the registers starting at location 49505.
Successfully accepted commands return the command number in the Reply
Register (49505). Error numbers will be returned when the command was not successful.
Read from the registers starting at location 49505.
Location
49505
49506
Data
Type
uint uint
Description
Echo command number from 1 to 2203 or error reply code.
Specific to error. Usually meter run if the command
for a listing of error codes.
Realflo User and Reference Manual
May 19, 2011
709
TeleBUS Protocol Interface
Input Configuration
The flow calculation routines require a temperature transmitter input, static pressure transmitter input and a differential pressure transmitter input (AGA-
3 or V-Cone), or pulse input (AGA-7).
Input Configuration Registers
The Input Configuration Registers for each transmitter input are set to contain the source register; the minimum and maximum scaled and unscaled values and the level limits and hysteresis. The Input Configuration
Registers for the pulse input are set to contain the Source Register, the low flow minimum pulse limit and the time duration for low flow pulse limit check.
The General Input Configuration Registers are set to contain the meter run number, type of units used, and the flow and compressibility calculation types.
The registers in the Actual Registers column in these tables are the registers containing the values already in use by the flow calculation routines. The registers in the Config. Registers column are the registers used for loading new configuration values to the flow calculation routines.
The registers in these tables are read from the flow computer using the
The registers in these tables are set in the flow computer using the
Config.
Register
49510
49511
49512
49513
49514
Actual
Register
49570
49571
49572
49573
49574
Data
Type
uint uint uint uint uint
Description
Meter run: 1 to 10
Input units type:
0 = US1,
1 = US2,
2 = US3,
3 = Imperial,
4 = Metric1,
5 = Metric2,
6 = Metric3,
7 = SI,
8 = US4,
9 = US5,
10 = US6,
11 = US7
12 = US8
Flow calculation type:
2 = AGA-3 (1985)
3 = AGA-3 (1992),
7 = AGA-7,
12 = AGA-11
22 = V-Cone
Compressibility calculation type:
8 = AGA 8
19 = NX-19
Static pressure tap location:
0 = upstream,
1 = downstream
Realflo User and Reference Manual
May 19, 2011
710
Config.
Register
49515
49516
49517
49518
49519
49520
49521
49522
49523
49524
49525
49526
49527
49529
49531
49533
49535
49537
49539
49541
TeleBUS Protocol Interface
Actual
Register
49575
49576
49577
49578
49579
49580
49581
49582
49583
49584
49585
49586
49587
49589
49591
49593
49595
49597
49599
49601
Data
Type
uint uint uint uint uint uint uint
Description
Log out of range events flag
0 = ignore Out Of Range events
1 = log Out Of Range events in event queue
Temperature input register, or
MVT transmitter number (1 to 10), or
SCADAPack 4202 or 4203 transmitter number (1)
Zero scale temperature input
(used with type 0 temperature inputs)
Full scale temperature input
(used with type 0 temperature inputs)
Static pressure input register, or
MVT transmitter number (1 to 10), or
SCADAPack 4202 or 4203 transmitter number (1).
Zero scale static pressure input
(used with type 0 static pressure inputs)
Full scale static pressure input
(used with type 0 static pressure inputs)
Differential pressure input register, or uint uint
MVT transmitter number (1 to 10) or
SCADAPack 4202 or 4203 transmitter number (1).
(AGA-3 and V-Cone only)
Zero scale differential pressure input
(AGA-3 and V-Cone only)
(used with type 0 differential pressure inputs) uint uint uint
Rotation counter input register (AGA-7 only)
Time duration for low flow pulse limit check (seconds) (AGA-7 only) slong Low flow minimum pulse limit (AGA-7 only) float
Full scale differential pressure input
(AGA-3 and V-Cone only)
(used with type 0 differential pressure inputs) float float float float float float
Temperature at zero scale
(used with type 3 temperature inputs)
Temperature at full scale
(used with type 3 temperature inputs)
Temperature low level cutoff
Temperature low level hysteresis
Temperature high level hysteresis
Temperature high level cutoff
Static pressure at zero scale
(used with type 3 static pressure inputs)
Realflo User and Reference Manual
May 19, 2011
711
Config.
Register
49543
Actual
Register
49603
Data
Type
float
49545
49547
49549
49551
49553
49555
49557
49559
49561
49563
49565
49567
49568
49569
49871
49872
49873
49605
49609
49607
49611
49613
49615
49617
49619
49621
49623
49625
49627
49628
49629
49876
49877
49878 float float float float float float float float float float float uint uint uint uint uint uint
TeleBUS Protocol Interface
Description
Static pressure at full scale
(used with type 3 static pressure inputs)
Static pressure low level cutoff
Static pressure low level hysteresis
Static pressure high level hysteresis
Static pressure high level cutoff
Atmospheric pressure
Differential pressure at zero scale
(AGA-3 and V-Cone only)
(used with type 3 differential pressure inputs)
Differential pressure at full scale (AGA-
3 and V-Cone only)
(used with type 3 differential pressure inputs)
Differential pressure low level cutoff
(AGA-3 and V-Cone only)
Differential pressure low level hysteresis
(AGA-3 and V-Cone only)
Differential pressure high level hysteresis
(AGA-3 and V-Cone only)
Differential pressure high level cutoff
(AGA-3 and V-Cone only)
Static pressure altitude and latitude compensation
0 = ignore
1 = compensate
Sensor Fail Action
0 = last known value
1 = default value
Gas Quality Sources (PEMEX only)
0 = manual
1 = PEMEX host
Flow Direction Control
0 = forward indicated by value
1 = reverse indicated by value
2 = forward indicated by status
3 = reverse indicated by status
Flow Direction Register
1 to 4096
10001 to 14096
30001 to 39999
40001 to 49999
On Indicates
0 = Reverse
1 = Forward
Realflo User and Reference Manual
May 19, 2011
712
TeleBUS Protocol Interface
Config.
Register
49874
Actual
Register
49879
Data
Type
uint
Description
Time stamp for Enron Modbus history logs.
0 = time leads data
1 = time lags data
Input Configuration Registers
The Input Type Registers describe the type of data in the Input Registers for each type of input. For floating point-input registers, floating-point scaling values need to be used.
Config.
Register
49900
49901
49902
49903
49904
49906
Actual
Register
49920
49921
49922
49923
49924
49926
Data
Type Description
uint Temperature input register type
0 = Telepace integer requiring scaling
2 = float in engineering units (no scaling required)
3 = float requiring scaling
4 = MVT
5 = ISaGRAF integer
6 = SCADAPack 4202 or 4203 uint Static pressure input register type
0 = Telepace integer requiring scaling
2 = float in engineering units (no scaling required)
3 = float requiring scaling
4 = MVT
5 = ISaGRAF integer
6 = SCADAPack 4202 or 4203 uint Differential pressure input register type
0 = Telepace integer requiring scaling
2 = float in engineering units (no scaling required)
3 = float requiring scaling
4 = MVT
5 = ISaGRAF integer
6 = SCADAPack 4202 or 4203 uint Turbine input register type
1 = Telepace long
5 = ISaGRAF integer or
Mass flow input register type (AGA-11 float slong only)
7 = Coriolis source
Zero scale temperature input
(used with type 3 and 5 temperature inputs) float format with type 3 inputs slong format with type 5 inputs float slong
Full scale temperature input
(used with type 3 and 5 temperature inputs) float format with type 3 inputs slong format with type 5 inputs
Realflo User and Reference Manual
May 19, 2011
713
TeleBUS Protocol Interface
Config.
Register
49908
49910
49912
49914
49916
49918
Actual
Register
49928
49930
49932
49934
49936
49938
Data
Type
float slong float slong
Description
Zero scale static pressure input
(used with type 3 and 5 static pressure inputs) float format with type 3 inputs slong format with type 5 inputs
Full scale static pressure input
(used with type 3 and 5 static pressure inputs) float format with type 3 inputs slong format with type 5 inputs float slong
Zero scale differential pressure input
(AGA-3 and V-Cone only)
(used with type 3 and 5 differential pressure inputs) float format with type 3 inputs slong format with type 5 inputs float slong
Full scale differential pressure input
(AGA-3 and V-Cone only)
(used with type 3 and 5 differential pressure inputs) float format with type 3 inputs slong format with type 5 inputs float Altitude float Latitude in decimal degrees
Input Type Configuration Registers
Registers 49904
– 49915 and 49924 – 49935 use the float type for type 3 inputs and the ISaGRAF integer type for type 5 inputs.
Get Input Configuration Command
The Get Input Configuration command returns the Input Configuration
Registers.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command = 1 (Get Input Configuration)
Meter run = 1 to 10
User number
PIN for user
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. The run number if the command was successful.
Read the Data Registers.
Location Data Type Description
Realflo User and Reference Manual
May 19, 2011
714
Location
49920 to 49939
Data Type
49570 to 49628 Input configuration structure
Input register type configuration structure
TeleBUS Protocol Interface
Description
See the Input
Configuration
section for details on these registers.
See the
Input
Configuration
section for details on these registers.
Set Input Configuration Command
The Set Input Configuration command sets the Input Configuration registers.
Write the configuration data into the registers.
Location Data Type
49510 to 49568 Input configuration structure
49900 to 49918 Input type configuration structure
Description
See the
Input
Configuration
section for details on these registers.
See the
Input
Configuration
section for details on these registers.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command = 3 (Set Input Config)
Meter run = 1 to 3
User number
PIN for user
Read the Reply Registers to determine whether the configuration was accepted.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. The run number if the command was successful.
MVT Configuration
MVT configuration defines the operation of the MVT transmitter and the polling of the transmitter by the flow computer.
The flow computer polls each configured transmitter in turn. It waits for a response or timeout. If the transmitter does not respond it will take longer to poll it, than if it responded. The timeout is set by the user in the sensor configuration page. The flow computer does not retry the transmitter. It moves on to the next transmitter. The transmitter will be polled again in the regular cycle.
The communication failure alarm is raised if the transmitter does not respond for 3 consecutive polls.
Realflo User and Reference Manual
May 19, 2011
715
TeleBUS Protocol Interface
Configuration events for the transmitters are logged in the event logs for all runs that use a sensor from the transmitter. If no runs use the transmitter, then the events are not logged.
MVT Data Registers
The flow computer polls the MVT transmitters and updates the Data
Registers.
The sensor status values are the same for each transmitter.
0 = response OK
1 = communication failed
2 = value below operating limit
3 = transmitter configuration invalid
4 = not polled, may be disabled
5 = bad value
6 = value above operating limit
7 = sensor is off line, may be calibrating
8 = RTD open (temperature sensor only)
9 = RTD offset out of range (temperature only)
43618
43619
43620
43621
43622
43623
43624
43625
43626
43608
43609
43610
43611
43612
43613
43614
43615
43616
43617
Register Data
Type
43600 uint
43601
43602
43603
43604
43605
43606
43607 uint uint uint uint uint uint uint uint uint uint uint uint uint uint uint uint uint uint uint uint uint uint uint uint uint uint
Description
Transmitter 1: differential pressure sensor status
Transmitter 1: static pressure sensor status
Transmitter 1: temperature pressure sensor status
Transmitter 2: differential pressure sensor status
Transmitter 2: static pressure sensor status
Transmitter 2: temperature pressure sensor status
Transmitter 3: differential pressure sensor status
Transmitter 3: static pressure sensor status
Transmitter 3: temperature pressure sensor status
Transmitter 4: differential pressure sensor status
Transmitter 4: static pressure sensor status
Transmitter 4: temperature pressure sensor status
Transmitter 5: differential pressure sensor status
Transmitter 5: static pressure sensor status
Transmitter 5: temperature pressure sensor status
Transmitter 6: differential pressure sensor status
Transmitter 6: static pressure sensor status
Transmitter 6: temperature pressure sensor status
Transmitter 7: differential pressure sensor status
Transmitter 7: static pressure sensor status
Transmitter 7: temperature pressure sensor status
Transmitter 8: differential pressure sensor status
Transmitter 8: static pressure sensor status
Transmitter 8: temperature pressure sensor status
Transmitter 9: differential pressure sensor status
Transmitter 9: static pressure sensor status
Transmitter 9: temperature pressure sensor status
Realflo User and Reference Manual
May 19, 2011
716
TeleBUS Protocol Interface
43658
43660
43662
43664
43666
43668
43670
43672
43674
43676
43678
43680
43630
43632
43634
43636
43638
43640
43642
43644
43646
43648
43650
43652
43654
43656
43682
43684
43686
43688 float float float float float float float float float float float float float float float float float float float float float float float float float float float float float float
Register Data
Type
43627 uint
43628
43629 uint uint
Description
Transmitter 10: differential pressure sensor status
Transmitter 10: static pressure sensor status
Transmitter 10: temperature pressure sensor status
Transmitter 1: differential pressure
Transmitter 1: static pressure
Transmitter 1: temperature
Transmitter 2: differential pressure
Transmitter 2: static pressure
Transmitter 2: temperature
Transmitter 3: differential pressure
Transmitter 3: static pressure
Transmitter 3: temperature
Transmitter 4: differential pressure
Transmitter 4: static pressure
Transmitter 4: temperature
Transmitter 5: differential pressure
Transmitter 5: static pressure
Transmitter 5: temperature
Transmitter 6: differential pressure
Transmitter 6: static pressure
Transmitter 6: temperature
Transmitter 7: differential pressure
Transmitter 7: static pressure
Transmitter 7: temperature
Transmitter 8: differential pressure
Transmitter 8: static pressure
Transmitter 8: temperature
Transmitter 9: differential pressure
Transmitter 9: static pressure
Transmitter 9: temperature
Transmitter 10: differential pressure
Transmitter 10: static pressure
Transmitter 10: temperature
Internal Registers
The flow computer uses the following registers for communication with the
MVT transmitter. The contents are of no interest to the user. These registers cannot be used in another program.
Register Data
Type
38000
…
38999
Description
Internal data
Internal data
MVT Command Parameter Registers
The Command Parameter Registers are used by the
Realflo User and Reference Manual
May 19, 2011
717
TeleBUS Protocol Interface
Register Data
Type
43700 uint
Description
43701
43702
43703 uint uint uint
Flow Computer serial port
1 = com1
2 = com2
3 = com3
4 = com4
Timeout = 100 ms to 10000 ms
Start or current address = 1 to 65534
End or new address = 1 to 65534
MVT Transmitter Information Registers
The Transmitter Information Registers are used by the
Register Data
Type
43710
43711
43712
43714
43718 uint uint
S
Description
Address of transmitter
Manufacturer code
Serial number userID Tag uint Type code (valid for 3095FB, SCADAPack 4000 and SCADAPack 4202 or 4203)
, for SCADAPack 4000 transmitter type
code.
MVT Transmitter Type Codes
Type
Code
41020
41021
40120
40121
40122
40123
40320
40321
Model
Number
4102
4102
4012
4012
4012
4012
Description
Multivariable transmitter (Serial interface)
Multivariable transmitter (Serial and LAN interfaces)
Gauge pressure transmitter (Serial interface)
Absolute pressure transmitter (Serial interface)
Gauge pressure transmitter (Serial and LAN interfaces)
Absolute pressure transmitter (Serial and LAN interfaces)
4032 Differential pressure transmitter (Serial interface)
4032 Differential pressure transmitter (Serial and
LAN interfaces)
Unknown The transmitter is not functioning correctly 0
MVT Configuration Registers
The MVT transmitter configuration registers are defined as follows. The registers in the Actual Register column are the registers containing the values already in use by the flow computer MVT transmitter. The registers in the Config.Register column are the registers used for loading new configuration values to the flow computer and the MVT transmitter.
Realflo User and Reference Manual
May 19, 2011
718
TeleBUS Protocol Interface
The registers in this table are read using the
The registers in this table are set using the
Config.
Register
43720
43721
43722
43723
43724
43725
43726
43727
43728
43729
43731
43735
Actual
Register
43760
43761
43762
43763
43764
43765
43766
43767
43768
43769
43771
43775
Data
Type
uint
Description
uint
Transmitter polling status:
0 = disabled
1 = enabled
Serial Port:
0 = unused, for internal SCADAPack
4202 or 4203 in slot 1
1 = com1
2 = com2
3 = com3
4 = com4
100 = LAN (4102, 4000 only) uint uint uint uint uint
Address of transmitter:
0 = unused, for internal SCADAPack
4202 or 4203 in slot 1
1 to 247 (Rosemount 3095FB, 4101)
1 to 255 (SCADAPack 4000,
SCADAPack 4202 or 4203 in standard addressing mode)
1 to 65534 (SCADAPack 4000,
SCADAPack 4202 or 4203 in extended addressing mode)
Timeout:
0 = unused, for internal SCADAPack
4202 or 4203 in slot 1
10 to 10000 ms
Manufacturer code
Turnaround delay time: 0 to 200 ms
Differential pressure units:
1 = inches of water at 60 F (3095FB only)
2 = Pascal
3 = kiloPascal uint
6 = inches of water at 68°F
Static pressure units:
3 = kiloPascal
4 = MegaPascal
5 = psi uint ulong Serial number userID Tag: 1 to 8 characters float
Temperature units:
20 = Celsius
21 = Fahrenheit
Differential pressure damping:
3095FB:
0.108, 0.216, 0.432, 0.864, 1.728,
3.456, 6.912, 13.824, or 27.648
SCADAPack 4000 and SCADAPack
Realflo User and Reference Manual
May 19, 2011
719
Config.
Register
43737
43739
43741
43743
43745
43747
43749
43751
43752
43753
43754
43756
43757
TeleBUS Protocol Interface
Actual
Register
43777
43779
43781
43783
43785
43787
43789
43791
43792
43793
43794
43796
43797
Data
Type
Description
float float float float float float float float uint
4202 or 4203 :
0.0 (damping off), 0.5, 1.0, 2.0, 4.0,
8.0, 16.0, or 32.0 seconds
Differential pressure upper operating limit
Differential pressure lower operating limit
Static pressure damping:
3095FB:
0.108, 0.216, 0.432, 0.864, 1.728,
3.456, 6.912, 13.824, or 27.648
SCADAPack 4000 and SCADAPack
4202 or 4203:
0.0 (damping off), 0.5, 1.0, 2.0, 4.0,
8.0, 16.0, or 32.0 seconds
Static pressure upper operating limit
Static pressure lower operating limit
Temperature damping:
3095FB:
0.108, 0.216, 0.432, 0.864, 1.728,
3.456, 6.912, 13.824, or 27.648
SCADAPack 4000 and SCADAPack
4202 or 4203: Not supported
Temperature upper operating limit
Temperature lower operating limit
Type code (not used with SCADAPack
4101)
31 = 3095FB MVT
4102 = SCADAPack 4102
4202 = SCADAPack 4202
4203 = SCADAPack 4203. uint Type Code (not used with SCADAPack
4101)
31 = 3095FB MVT
40120 = 4012 Absolute
40121 = 4012 Gauge
41020 = 4102 Serial
41021 = 4102 Serial and LAN
4202 = 4202 DR
42021 = 4202 DS
42990 = 4203 DR
42991 = 4203 DS ulong IP Address (MSB first) (when Port is
LAN) uint IP Protocol (when Port is LAN)
0 = None
1 = Modbus/TCP
2 = Modbus RTU in UDP
Float Atmospheric pressure (used by
SCADAPack 4102 and SCADAPack
4202 or 4203)
0 = absolute pressure
>0 to 30 psia (or equivalent) = gage
Realflo User and Reference Manual
May 19, 2011
720
Config.
Register
Actual
Register
Data
Type
Description
TeleBUS Protocol Interface pressure
MVT Search Command
The flow computer can search for MVT transmitters connected to its serial ports.
Write the search parameters into the Configuration Registers.
Register Data
Type
43700
43701
43702
43703
43704
43706
Description
uint Flow Computer serial port
1 = com1
2 = com2
3 = com3
4 = com4
100 = LAN (4102, 4000 only)
Timeout = 100 ms to 10000 ms uint uint Start address = 1 to 65534
0 for LAN
End address = 1 to 65534 uint
Ulong IP Address (SCADAPack 4102 only when LAN port is available)
MSB first, representing aa.bb.cc.dd format
Uint IP Protocol (SCADAPack 4102 only when LAN port is available)
0 = None
1 = Modbus/TCP
2 = Modbus RTU in UDP
Write the command and read the Command Register until it is cleared.
Register Data
Type
49500 uint
49501
49502
49503 uint uint uint
Description
Command = 130 (Search for MVT Transmitter)
Meter run = 0
User number
PIN
Read the Reply Registers to determine if a transmitter was found. An error is returned if the command parameters are invalid.
Register Data
Type
49505 uint
Description
49506 uint
Command status:
130 = command complete
other = Error code from MVT Command Errors.
Command result:
0 = transmitter found
1 = no transmitter found
If a transmitter was found, read the search result registers to get the transmitter information.
Register Data
Type
Description
Realflo User and Reference Manual
May 19, 2011
721
TeleBUS Protocol Interface
43710
43711
43712
43714
43718 uint Address of transmitter uint Manufacturer code ulong Serial number userID Tag uint Type code (valid for 3095FB, SCADAPack 4102,
4202 and 4203
The flow computer will return the first transmitter found. Repeat the command with a different range to find additional transmitters.
MVT Change Address Command
This command changes the address of a MVT transmitter.
Write the command parameters into the Configuration Registers.
Register Data
Type
43700 uint
Description
43701
43702
43703 uint uint uint
Flow Computer serial port:
1 = com1
2 = com2
3 = com3
4 = com4
Timeout = 100 ms to 10000 ms
Current address = 1 to 247
New address = 1 to 247
Write the command and read the Command Register until it is cleared.
Register Data
Type
49500
49501
49502
49503 uint uint uint uint
Description
Command = 131 (Change MVT Address)
Meter run = 0
User number
PIN
Read the Reply Registers to determine if the transmitter address was changed. An error is returned if the command parameters are invalid.
Register Data
Type
49505 uint
Description
49506 uint
Command status:
131 = command complete
other = other = Error code from MVT Command
Command result:
0 = transmitter address changed
1 = no response from transmitter
Get MVT Configuration Command
This command reads a MVT-transmitter configuration from the transmitter and flow computer. The flow computer reads the configuration from the transmitter and returns it. If the transmitter does not respond, the current configuration from the flow computer is returned instead.
Realflo User and Reference Manual
May 19, 2011
722
TeleBUS Protocol Interface
If the transmitter is disabled in the flow computer, the current configuration from the flow computer is returned. The flow computer does not attempt to read the transmitter.
Write the command and read the Command Register until it is cleared.
Register Data
Type
49500 uint
49501
49502
49503 uint uint uint
Description
Command = 132 (Get MVT Configuration)
Transmitter number = 1 to 10
User number
PIN
Read the Reply Registers when the command is complete. An error is returned if the command parameters are invalid.
Register Data
Type
49505 uint
Description
49506 uint
Command status:
132 = command complete
other = other = Error code from MVT Command
Command result:
0 = error occurred
1 to 10 = transmitter number
If a transmitter was found, read the actual Configuration Registers.
Register
43760 to 43792
Data Type
MVT
Configuration
Structure
Description
details.
Set MVT Configuration Command
The command writes a MVT-transmitter configuration to the flow computer and the transmitter. The flow computer writes the configuration to the transmitter. If the transmitter does not respond, the configuration is still saved in the flow computer memory.
Write data into the Configuration Registers.
Register
43720 to 43752
Data Type
MVT configuration structure
Description
section for details.
Write the command and read the Command Register until it is cleared.
Register
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command = 133 (Set MVT Configuration)
Transmitter number = 1 to 10
User number
PIN
Read the Reply Registers when the command is complete. An error is returned if the configuration data are invalid.
Register Data Description
Realflo User and Reference Manual
May 19, 2011
723
TeleBUS Protocol Interface
49505
49506
Type
uint uint
Command status:
133 = command complete
other = other = Error code from MVT Command
Command result:
0 = error occurred
1 to 10 = transmitter number
Read MVT Configuration Command
This command reads a MVT-transmitter configuration from the transmitter and flow computer. The flow computer reads the configuration from the transmitter and returns it. If the transmitter does not respond, the current configuration from the flow computer is returned instead.
If the transmitter is disabled in the flow computer, the search parameters will be used to try to read the transmitter.
Write the search parameters into the Configuration Registers.
Register Data
Type
43700 uint
Description
43701
43702
43703 uint uint uint
Flow Computer serial port:
1 = com1
2 = com2
3 = com3
4 = com4
100 = LAN (SCADAPack 4000 only)
Timeout = 100 ms to 10000 ms
Station address = 1 to 247
0 for LAN
End address = 1 to 65534
Not used for LAN
43704
43706
Ulong IP Address (SCADAPack 4000 only when LAN port is available)
MSB first, representing aa.bb.cc.dd format
Uint IP Protocol (SCADAPack 4000 only when LAN port is available)
0 = None
1 = Modbus/TCP
2 = Modbus RTU in UDP
Write the command and read the Command Register until it is cleared.
Register Data
Type
49500 uint
49501
49502
49503 uint uint uint
Description
Command = 136 (Read MVT Configuration)
Transmitter number = 1 to 10
User number
PIN
Read the Reply Registers when the command is complete. An error is returned if the command parameters are invalid.
Description Register Data
Type
49505 uint Command status:
Realflo User and Reference Manual
May 19, 2011
724
TeleBUS Protocol Interface
Register Data
Type
Description
49506 uint
136 = command complete
other = other = Error code from MVT Command
Command result:
0 = error occurred
1 to 10 = transmitter number
If a transmitter was found, read the actual Configuration Registers.
Register
43760 to 43792
Data Type
MVT configuration structure
Description
section for details.
Set MVT Sensor Mode
This command writes the sensor mode to the flow computer and the transmitter.
The calibrate mode allows operation to the bottom end of the MVT. The flow computer allows writing to the MVT registers when calibrate mode is set and disallows writing when on-line mode is set. This keeps the MVT from being accessed by other sources.
Write the mode into the Configuration Registers.
Register
49990
Data
Type
uint
Description
Sensor Mode
0 = On-line
255 = Calibrate
Write the command and read the Command Register until it is cleared.
Register Data
Type
49500
49501
49502
49503 uint uint uint uint
Description
Command = 139 (Set Sensor Mode)
Transmitter number (1 to 10)
User number
PIN
Read the Reply Registers to determine if the mode was accepted. An error is returned if the command parameters were invalid.
Register Data
Type
49505 uint
49506 uint
Description
Command Status
139 = command complete
other = Error code from MVT Command Errors.
Command Result
0 = error
1 to 10 = Transmitter number
Realflo User and Reference Manual
May 19, 2011
725
TeleBUS Protocol Interface
MVT Calibration
MVT calibration changes the calibration of a transmitter. A transmitter may be calibrated while it is in use by flow runs. To do this the inputs to the flow runs needs to be forced. The procedure is as follows.
Select the MVT to calibrate.
Determine which runs take one or more inputs from this transmitter. It is possible that no runs take inputs from the transmitter. It is still possible to calibrate the transmitter, however no inputs need to be forced and no information needs to be logged in the steps that follow.
Force each input point using sensors from this transmitter to its current value or a fixed value. The value needs to be in the input units for the run, not in the transmitter units. Use the Force Inputs command appropriate for the sensor (commands 30, 31, 33, 34, 36, and 37).
Remove the transmitter from the process.
For each sensor on the transmitter that is to be calibrated.
Measure as-found readings for the sensor. Record the as-found readings in the event logs for each run that use the sensor. The values need to be in the input units for the run, not in the transmitter units. Use the Log User Defined Event command to log the appropriate events.
Read the transmitter sensor information to determine the applicable range for the transmitter calibration parameters. Use the Get MVT
Sensor Information command.
Determine the new calibration parameters.
Write the calibration parameters to the transmitter. Use the Calibrate
MVT Sensor command.
Measure as-left readings for the sensor. Record the as-left readings in the event logs for each run that use the sensor. The values need to be in the input units for the run, not in the transmitter units. Use the Log
User Defined Event command to log the appropriate events.
Reinstall the transmitter into the process.
Restore each input point using sensors from this transmitter to live values. Use the End Calibration command appropriate for the sensor
(commands 32, 35, and 38).
MVT Sensor Information Registers
The Sensor Information Registers show information about. These registers are read using the Get MVT Sensor Information command.
Register Data
Type
49980 uint
Description
49981
49983
49985 float float float
Sensor type:
1 = differential pressure
2 = static pressure
3 = flow temperature
Zero value
Span value (not available for sensor type 3 on
SCADAPack 4000 and SCADAPack 4202 or 4203.
Upper range limit
Realflo User and Reference Manual
May 19, 2011
726
TeleBUS Protocol Interface
49987 float Lower range limit
MVT Sensor Calibration Registers
The Sensor Calibration Registers contain calibration data for MVT sensors.
These registers are written using the Calibrate MVT Sensor command.
Register Data
Type
49990 uint
Description
49991 uint float
Sensor type:
1 = differential pressure
2 = static pressure
3 = flow temperature
Type of value
0 = calibration zero
1 = calibration span (not available for sensor type 3 on SCADAPack 4000 and SCADAPack 4202 or
4203).
2 = fixed temperature (for 3095FB only; for sensor type 3 only)
Value to set (depends on type of value) 49992
Get MVT Sensor Information Command
This command reads sensor information from a MVT transmitter. The flow computer reads this information from the transmitter and returns it.
Select the type of sensor for which information is needed.
Register Data
Type
49990 uint
Description
Sensor type:
1 = differential pressure
2 = static pressure
3 = flow temperature
Write the command and read the Command Register until it is cleared.
Register
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command = 134 (Get MVT Sensor Information)
Transmitter number = 1 to 10
User number
PIN
Read the Reply Registers when the command is complete. An error is returned if the sensor parameters are invalid.
Description Register Data
Type
49505 uint
49506 uint
Command status:
134 = command complete
other = other = Error code from MVT Command
Command result:
0 = error occurred
1 to 10 = transmitter number
Realflo User and Reference Manual
May 19, 2011
727
TeleBUS Protocol Interface
If a transmitter responded, read the Transmitter Information Registers.
Register
49980
Data
Type
uint
Description
49981
49983
49985
49987 float float float float
Sensor type:
1 = differential pressure
2 = static pressure
3 = flow temperature
Zero value
Span value
Upper range limit
Lower range limit
Calibrate MVT Sensor Command
This command writes sensor calibration data to a MVT transmitter. The flow computer writes the data to the sensor. This command needs to be repeated for each sensor on the transmitter.
The command will not work if span calibration or fixed temperature is selected for the SCADAPack 4000, 4200 or 4300 transmitters.
Write data into the Sensor Calibration Registers.
Register Data
Type
49990 uint
Description
49991
49992 uint float
Sensor type:
1 = differential pressure
2 = static pressure
3 = flow temperature
Type of value
0 = calibration zero
1 = calibration span
2 = fixed temperature (when sensor type is 3)
Value to set (depends on type of value)
Write the command and read the Command Register until it is cleared.
Register
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command = 135 (Calibrate MVT Sensor)
Transmitter number = 1 to 10
User number
PIN
Read the Reply Registers when the command is complete. An error is returned if the command parameters are invalid.
Description Register Data
Type
49505 uint
49506 uint
Command status:
135 = command complete
other = Error code from MVT Command Errors.
Command result:
0 = error occurred
1 to 10 = transmitter number
Realflo User and Reference Manual
May 19, 2011
728
TeleBUS Protocol Interface
Contract Configuration
The flow calculation routines require valid entries for the Contract
Configuration Registers. This is called Contract Configuration because these parameters are often defined by a contract for selling gas.
Contract Configuration Registers
The Contract Configuration Registers define parameters for the gas measurement contract.
Changes to the Contract Configuration Registers are not allowed while the flow calculation is running, except as noted below.
The registers in the Actual Registers column in these tables are the registers containing the values already in use by the flow calculation routines. The registers in the Config. Registers column are the registers used for loading new configuration values to the flow calculation routines.
The registers in this table are read from the flow computer using the
The registers in this table are set in the flow computer using the
Config.
Register
49630
49631
49632
49633
49635
49637
Actual
Register
49640
49641
49642
49643
49645
49647
Data
Type
uint uint uint float float uint
Description
Meter run number: 1 to 10
Output and log units type:
0 = US1,
1 = US2,
2 = US3,
3 = Imperial,
4 = Metric1,
5 = Metric2,
6 = Metric3,
7 = SI,
8 = US4,
9 = US5,
10 = US6,
11 = US7
12 = US8
Contract hour, 0 to 23
Base temperature
Base static pressure
For Flow Computer 6.70 and later
Input weighting average
0 = flow-dependent time-weighted linear average
2 = flow-weighted linear average
For Flow Computer 5.28 and earlier
Input error action
0 = do not accumulate flow when inputs in error
1 = accumulate flow when inputs in error
Realflo User and Reference Manual
May 19, 2011
729
TeleBUS Protocol Interface
Config.
Register
49638
Actual
Register
49648
Data
Type
49831
49833
49841
49843
Contract Configuration Registers
Description
Float Wet gas meter factor. Version 6.10 or greater.
Default value is 1.0.
The value 0.0 indicates that the parameter is not supported and that
1.0 should be substituted for it.
For version 6.21 or greater, this parameter can be changed while flow calculations are running and without starting a new contract day.
Float Pemex Base Temperature
Float Pemex Base Static Pressure
Get Contract Configuration Command
The Get Contract Configuration command returns the Contract
Configuration Registers.
Write the command and read the Command Register until it is cleared.
Location
49500
Data
Type
uint
Description
Command = 13 (Get Contract Configuration)
49501
49502 uint uint
Meter run = 1 to 10
User number
49503 uint PIN for user
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. The run number if the command was successful.
Read the Data Registers.
Location
49640 to 49646
Data Type
Contract Configuration
Structure
Description
section for details on these registers.
Set Contract Configuration Command
The Set Contract Configuration command sets the Contract Configuration
Registers.
Write the configuration data into the registers.
Location
49630 to 49636
Data Type
Contract configuration structure
Description
section for details on these registers.
Realflo User and Reference Manual
May 19, 2011
730
TeleBUS Protocol Interface
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command = 15 (Set Contract Configuration)
Meter run = 1 to 10
User number
PIN for user
Read the Reply Registers to determine whether the configuration was accepted.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. The run number if the command was successful.
AGA-3 Configuration
AGA-3 Configuration defines parameters unique to the AGA-3 calculation.
Configuration of the AGA-3 flow calculation parameters is accomplished by setting the required values into the AGA-3 Configuration Registers.
AGA-3 Configuration Registers
The registers in the Actual Registers column in these tables are the registers containing the values already in use by the flow calculation routines. The registers in the Config. Registers column are the registers used for loading new configuration values to the flow calculation routines.
The registers in these tables are read from the flow computer using the
The registers in these tables are set in the flow computer using the
Config.
Register
49650
49651
49652
49653
49655
49657
49659
49661
49663
49665
Actual
Register
49680
49681
49682
49683
49685
49687
49689
49691
49693
49695
Data
Type
uint uint uint float float float float float float float
Description
Meter run: 1 to 10
Orifice material
0 = stainless,
1 = Monel,
2 = carbon steel
Pipe material
0 = stainless,
1 = Monel,
2 = carbon steel
Orifice diameter
Reference temperature for orifice measurement
Pipe diameter
Reference temperature for pipe diameter measurement
Isentropic exponent
Viscosity
Temperature dead band
Realflo User and Reference Manual
May 19, 2011
731
TeleBUS Protocol Interface
Config.
Register
49667
49669
Actual
Register
49697
49699
Data
Type
float float
AGA-3 Configuration Registers
Description
Static pressure dead band
Differential pressure dead band
Get AGA-3 Configuration Command
The Get AGA-3 Configuration command returns the AGA-3 Configuration
Registers.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command = 301 (get AGA-3 (1992) configuration)
Command = 351 (get AGA-3 (1985) configuration)
Meter run = 1 to 10
User number
PIN for user
Read the Reply Register to determine whether the data is available.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error code from
Specific to error. The run number if the command was successful.
Read the Data Registers.
Location Data Type
49680 to 49700 AGA-3
Configuration
Structure
Description
these registers.
Set AGA-3 Configuration Command
The Set AGA-3 Configuration command sets the AGA-3 Configuration
Registers.
Write the configuration data into the registers.
Location Data Type
49650 to 49670 AGA-3 configuration structure
Description
these registers.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command = 303 (set AGA-3 (1992) configuration)
Command = 353 (set AGA-3 (1985) configuration)
Meter run = 1 to 10
User number
PIN for user
Realflo User and Reference Manual
May 19, 2011
732
TeleBUS Protocol Interface
Read the Reply Registers to determine whether the configuration was accepted.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error code from AGA-3 (1985)
Calculation Errors, AGA-3 (1992) Calculation
Errors or AGA-3 Command Errors.
Specific to error. The run number if the command was successful.
AGA-7 Configuration
AGA-7 configuration defines parameters unique to the AGA-7 calculation.
Configuration of the AGA-7 flow calculation parameters is accomplished by setting the required values into the AGA-7 Configuration Registers.
AGA-7 Configuration Registers
The registers in the Actual Registers column in these tables are the registers containing the values already in use by the flow calculation routines. The registers in the Config. Registers column are the registers used for loading new configuration values to the flow calculation routines.
The registers in these tables are read from the flow computer using the
The registers in these tables are set in the flow computer using the
Config.
Register
49710
49711
49713
49719
Actual
Register
49720
49721
49723
49729
Data
Type
uint float float unit
Description
Meter run = 1 to 10
K factor
M factor
Uncorrected Flow Volume
0 = include M factor in calculation
(default).
1 = exclude M factor from calculation.
AGA-7 Configuration Registers
Get AGA-7 Configuration Command
The Get AGA-7 Configuration command returns the AGA-7 Configuration
Registers.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command = 701 (Get AGA-7 configuration)
Meter run = 1 to 10
User number
PIN for user
Read the Reply Registers to determine whether the data is available.
Location
Data
Type Description
Realflo User and Reference Manual
May 19, 2011
733
TeleBUS Protocol Interface
Location
49505
49506
Data
Type
uint uint
Description
Command = 701 or error code from
Specific to error. The run number if the command was successful.
Read the Data Registers.
Location Data Type
49720 to 49729 AGA-7
Configuration
Structure
Description
these registers.
Set AGA-7 Configuration Command
The Set AGA-7 Configuration command sets the AGA-7 Configuration
Registers.
Write the configuration data into the registers.
Location
49710 to 49714,
49719
Data Type
AGA-7
Configuration
Structure
Description
these registers.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type Description
uint Command = 703 (Set AGA-7 Configuration) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the configuration was accepted.
Location
49505
49506
Data
Type Description
uint
Command = 701 or error code from AGA-7
Calculation Errors or AGA-7 Command Errors.
uint Specific to error. The run number if the command was successful.
Coriolis Meter Configuration
Coriolis meter configuration defines parameters unique to the Coriolis meter used for AGA-11 calculations. Configuration of the Coriolis parameters is accomplished by setting the required values into the Coriolis Meter
Configuration Registers.
Coriolis Meter Configuration Registers
The registers in the Actual Registers column in these tables are the registers containing the values already in use by the flow calculation routines. The registers in the Config. Registers column are the registers used for loading new configuration values to the flow calculation routines.
Realflo User and Reference Manual
May 19, 2011
734
TeleBUS Protocol Interface
The registers in these tables are read from the flow computer using the
Coriolis Meter Configuration Command
The registers in these tables are set in the flow computer using the
Coriolis Meter Configuration Command
Config.
Register
49650
49651
49652
49653
49654
Actual
Register
49680
49681
49682
49683
49684
Data
Type
uint float float unit uint
Description
Coriolis Meter: 1 to 10
(Meter number is linked to Meter Run number)
Address: 1 to 247
Serial port:
0 = Com1,
1 = Com2,
2 = Com3,
3 = Com4
Timeout: 1 to 1000
Device code
0 = E&H Promass 83
Coriolis Meter Configuration Registers
Get Coriolis Meter Configuration Command
The Get Coriolis Meter Configuration command returns the Coriolis Meter
Configuration Registers.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command = 112 (get Coriolis Meter configuration)
Coriolis Meter number = 1 to 10 (Meter number is linked to Meter Run number)
User number
PIN for user
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type
uint uint
Description
Command = 112 or error code from
Specific to error. Coriolis meter number if the command was successful. (Meter number is linked to Meter Run number)
Read the Data Registers.
Location Data Type
49680 to 49684 Coriolis Meter
Configuration
Structure
Description
for details on these registers.
Set Coriolis Meter Configuration Command
The Set Coriolis Meter Configuration command sets the Coriolis Meter
Configuration Registers.
Realflo User and Reference Manual
May 19, 2011
735
TeleBUS Protocol Interface
Write the configuration data into the registers.
Location Data Type
49650 to 49654 Coriolis Meter
Configuration
Structure
Description
for details on these registers.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type Description
uint Command = 113 (set Coriolis Meter configuration) uint Coriolis Meter number = 1 to 10 (Meter number is linked to Meter Run number) uint User number uint PIN for user
Read the Reply Registers to determine whether the configuration was accepted.
Location
49505
49506
Data
Type Description
uint
Command = 113 or error code from
uint Specific to error. Coriolis meter number if the command was successful. (Meter number is linked to Meter Run number)
V-Cone Configuration
V-Cone configuration defines parameters unique to the V-Cone calculation.
Configuration of the V-Cone flow calculation parameters is accomplished by setting the required values into the V-Cone Configuration Registers.
In the original McCrometer V-Cone Application Sizing sheet that is included with V-Cone meters uses the terminology Cd (discharge coefficient) rather than Cf (flow coefficient). You will need to use the Re and Cd values from the V-Cone Application Sizing sheet for the Re and Cf entries. If the Re value is the same for all entries in the table only the first pair is used.
McCrometer now supplies one value of Cd in the sizing document. You need to enter one Re/Cd pair only. See the McCrometer Application Sizing sheet for the Re/Cd pair for your meter.
V-Cone Configuration Registers
The registers in the Actual Registers column in these tables are the registers containing the values already in use by the flow calculation routines. The registers in the Config. Registers column are the registers used for loading new configuration values to the flow calculation routines.
The registers in these tables are read from the flow computer using the
The registers in these tables are set in the flow computer using the
Config.
Register
Actual
Register
Data
Type Description
Realflo User and Reference Manual
May 19, 2011
736
TeleBUS Protocol Interface
Config.
Register
49650
49651
49652
49653
49655
49657
49659
49661
49663
49665
49667
49669
49671
49673
49675
49677
49679
49711
49713
49715
49717
49830
Actual
Register
49680
49681
49682
49683
49685
49687
49689
49691
49693
49695
49697
49699
49701
49703
49705
49707
49709
49721
49723
49725
49727
49840
Data
Type
uint uint uint float float float float float float float float float float float float float uint float float float float uint
49831
49833
49940
49942
49944
49946
49948
49950
49952
49954
49956
49958
49841
49843
49960
49962
49964
49966
49968
49970
49972
49974
49976
49978
V-Cone Configuration Registers
float float float float float float float float float float float float
Description
Meter run = 1 to 10
V-Cone material
2 = carbon steel,
3 = stainless 304,
4 = stainless 316
Pipe material
2 = carbon steel,
3 = stainless 304,
4 = stainless 316
Cone diameter
Reference temperature for cone diameter measurement.
Inside meter diameter
Reference temperature for inside meter diameter measurement
Isentropic exponent
Viscosity
Number of points: 1 to 10
Point 1 Reynold‟s number
Point 1 Coefficient
Point 2 Reynold‟s number
Point 2 Coefficient
Point 3 Reynold‟s number
Point 3 Coefficient
Adiabatic Expansion Factor Method
0 = Legacy
1 = V-Cone
2 = Wafer Cone
Point 4 Reynold‟s number
Point 4 Coefficient
Point 5 Reynold‟s number
Point 5 Coefficient
Wet Gas Correction Factor Method
0 = Legacy Method
1 = V-Cone or Wafer Cone
Mass flow rate of liquid at flow
Density of liquid at flow conditions
Point 6 Reynold‟s number
Point 6 Coefficient
Point 7 Reynold‟s number
Point 7 Coefficient
Point 8 Reynold‟s number
Point 8 Coefficient
Point 9 Reynold‟s number
Point 9 Coefficient
Point 10 Reynold‟s number
Point 10 Coefficient
Realflo User and Reference Manual
May 19, 2011
737
TeleBUS Protocol Interface
Get V-Cone Configuration
The Get V-Cone Configuration command returns the V-Cone
Configuration Registers.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command = 2201 (get V-Cone configuration)
Meter run = 1 to 10
User number
PIN for user
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error code from
Specific to error. The run number if the command was successful.
Read the Data Registers.
Location
49680 to 49708,
49721 to 49728,
49840 to 49844
49960 to 49979
Data Type
V-Cone
Configuration
Structure
Description
these registers.
Set V-Cone Configuration
The Set V-Cone Configuration command sets the V-Cone Configuration
Registers.
Write the configuration data into the registers.
Location
49650 to 49678,
49711 to 49718,
49830 to 79834,
49940 to 49959
Data Type
V-Cone
Configuration
Structure
Description
these registers.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command = 2203 (Set V-Cone Configuration)
Meter run = 1 to 10
User number
PIN for user
Read the Reply Registers to determine whether the configuration was accepted.
Location
49505
Data
Type
uint
Description
Echo command or error code from
Realflo User and Reference Manual
May 19, 2011
738
49506 uint
TeleBUS Protocol Interface
Specific to error. The run number if the command was successful.
AGA-8 Configuration
Configuration of the AGA-8 calculation parameters is accomplished by setting the required values into the AGA-8 Configuration Registers. AGA-8 configuration defines parameters unique to the AGA-8 calculation.
The AGA-8 Configuration Registers define the composition of the gas being measured. The gas composition can be made up of a number of components. These components are usually represented as either a percentage of the gas being measured i.e. 0 to 100% or as a fraction of the gas being measured i.e. 0 to 1.0000. The flow computer uses fractional values for gas composition components, 0 to 1.0000.
The range of the fractional values of the components cannot be predetermined. The valid gas components are shown below. There are two ranges shown for each gas component. Realflo accepts any value in the
Expanded Range. Only values in the Normal Range will work in every circumstances.
Component Normal Range Expanded Range
Methane CH
4
Nitrogen
Hydrogen
Carbon Dioxide
Ethane C
2
H
6
Propane C
3
H
8
.4500 to 1.0000 0 to 1.0000
0 to 0.5000 0 to 1.0000
0 to 0.3000 0 to 1.0000
0 to 0.1000
0 to 0.0400
Water 0 to 0.0005
Hydrogen Sulfide 0 to 0.0002
0 to 0.1000
0 to 1.0000
0 to 0.1200
0 to 0.0300
0 to 1.0000
0 to 1.0000
Carbon Monoxide 0 to 0.0300
Oxygen 0
0 to 0.0100 Total Butanes
iButane
nButane
Total Pentanes
iPentane
nPentane
0 to 0.0300
0 to 0.0200 Total Hexane Plus
nHexane nHeptane
nOctane
nNonane
nDecane
Helium
Argon
0 to 0.0200
0
0 to 0.0300
0 to 0.2100
0 to 0.0600
0 to 0.0400
0 to 0.0400
0 to 0.0300
0 to 0.0100
AGA-8 Configuration Registers
The registers in the Actual Registers column in these tables are the registers containing the values already in use by the flow calculation routines. The registers in the
Config. Registers’ column are the registers used for loading new configuration values to the flow calculation routines.
The AGA-8 gas composition can be changed while the flow calculation is running. This allows an on-line gas chromatograph to provide updates to the
Realflo User and Reference Manual
May 19, 2011
739
TeleBUS Protocol Interface
Config.
Register
49730
49731
49733
49735
49737
49739
49741
49743
49745
49747
49749
49751
49753
49755
49757
49759 gas composition. Frequent changes to the composition will result in the event log filling with gas composition events. When the log is full, further changes cannot be made until Realflo reads the log. Use the Composition
Logging Control register to not log changes if this occurs.
Realflo checks the validity of the entered components using the following limits:
Individual components are in the ranges listed in the table above.
The Total of all Components field displays the sum of components. The total of components needs to be 1.0000 (+/- 0.00001) if Composition
Units is set to Mole Fractions or 100% (+/- 0.00001%) if Composition
Units is set to Percent.
The registers in these tables are read from the flow computer using the
The registers in these tables are set in the flow computer using the
49761
49763
49765
49767
49769
49771
49773
49774
49776
Actual
Register
49780
49781
49783
49785
49787
49789
49791
49793
49795
49797
49799
49801
49803
49805
49807
49809
49811
49813
49815
49817
49819
49821
49823
49824
49826
Data
Type
uint float float float float float float float float float float float float float float float float float float float float float uint float float
Description
Meter run = 1 to 10
Methane
Nitrogen
Carbon Dioxide
Ethane
Propane
Water
Hydrogen Sulfide
Hydrogen
Carbon Monoxide
Oxygen iButane nButane iPentane nPentane n-Hexane (when individual components selected) n-Heptane n-Octane n-Nonane n-Decane
Helium
Hexanes+
(when combined component s selected)
N/A
N/A
N/A
N/A
Argon
Composition logging control
0 = log composition changes
1 = do not log composition changes
Real Relative Gas Density
0 = calculate live value
Heating Value (for dry gas)
0 = calculate live value
Realflo User and Reference Manual
May 19, 2011
740
TeleBUS Protocol Interface
AGA-8 Configuration Registers
Get AGA-8 Gas Ratios Command
The Get AGA-8 Gas Ratios command returns the AGA-8 Configuration
Registers.
In Flow Computer versions 6.73 and older, when gas ratios are written to the flow computer using the Set AGA-8 Gas Ratios the new gas ratios are updated in the Configuration Config registers. The Configuration Actual registers are not updated until a new Density calculation is started with the new values. The new gas ratios are not available to SCADA host software reading the Configuration Actual registers until a new Density calculation is started with the new values.
In Flow Computer versions 6.74 and newer when gas ratios are written to the flow computer using the Set AGA-8 Gas Ratios the new gas ratios are updated in the Configuration Config registers and in the Configuration Actual registers. This allows a SCADA host to immediately confirm the new ratios were written to the flow computer. The new gas ratios are not used by the flow computer until a new density calculation is started.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type Description
uint Command = 801 (Get AGA-8 gas ratios) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type Description
uint
Command = 801 or error code from
uint Specific to error. The run number if the command was successful.
Read the Data Registers.
Location Data Type
49780 to 49827 Get AGA-8 Gas
Fractions
Configuration
Structure
Description
these registers.
Set AGA-8 Gas Ratios Command
The Set AGA-8 Gas Ratios command sets the AGA-8 Configuration
Registers.
Write the configuration data into the registers.
Location Data Type Description
Realflo User and Reference Manual
May 19, 2011
741
TeleBUS Protocol Interface
49730 to 49777 AGA-8 Gas
Fractions
Configuration
Structure
these registers.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type Description
uint Command = 803 (Set AGA-8 Gas Ratios) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the configuration was accepted.
Location
49505
49506
Data
Type Description
uint
Command = 801 or error code from AGA-8
Calculation Errors or AGA-8 Command Errors.
uint Specific to error. The run number if the command was successful.
AGA-8 Hexanes+ Configuration Registers
The registers in the Actual Registers column in these tables are the registers containing the values already in use by the flow calculation routines. The registers in the
Proposed Registers’ column are the registers used for loading new configuration values to the flow calculation routines.
The AGA-8 Hexanes+ gas portions can be changed while the flow calculation is running. This allows an on-line gas chromatograph to provide updates to the gas composition. Frequent changes to the composition will result in the event log filling with gas composition events. When the log is full, further changes cannot be made until Realflo reads the log.
The AGA-8 Hexanes+ configuration allows a single value to be used for the heavy gas components (n-Hexane through n-Decane). These ratios are applied to the Hexanes+ ratio to determine the true ratio for those components.
The registers in these tables are read from the flow computer using the Get
AGA-8 Hexanes+ Ratios Command.
The registers in these tables are set in the flow computer using the Set
AGA-8 Hexanes+ Ratios Command.
If individual gas components are selected, the values of portions will be 0.
If combined value for hexane and higher components is selected, the values of portions from n-Hexane to n-Decane needs to sum to 100.000.
Proposed
Registers
49730
49759
49761
49763
49765
Actual
Registers
49780
49809
49811
49813
49815
Data
Type
Uint
Float
Float float float
Description
Meter run = 1 to 10 n-Hexane portion n-Heptane portion n-Octane portion n-Nonane portion
Realflo User and Reference Manual
May 19, 2011
742
TeleBUS Protocol Interface
49767
49773
49817
49823 float uint n-Decane portion
0 = Use individual gas components (default)
1 = Use combined value for hexane and higher components.
AGA-8 Hexanes+ Configuration Registers
Get AGA-8 Hexanes+ Gas Ratios
The Get AGA-8 Hexanes+ Gas Ratios command returns the AGA-8
Hexanes+ Configuration Registers.
In Flow Computer versions 6.73 and older, when AGA-8 Hexanes+ gas ratios are written to the flow computer using the Set AGA-8 Hexanes+ Gas
Ratios the new gas ratios are updated in the Proposed Registers. The
Actual Registers are not updated until a new Density calculation is started with the new values. The new gas ratios are not available to SCADA host software reading the Actual Registers until a until a new Density calculation is started with the new values.
In Flow Computer versions 6.74 and newer when AGA-8 Hexanes+ gas ratios are written to the flow computer using the Set AGA-8 Hexanes+ Gas
Ratios the new gas ratios are updated in the Proposed Registers and in the
Actual Registers. This allows a SCADA host to immediately confirm the new ratios were written to the flow computer. The new gas ratios are not used by the flow computer until a new density calculation is started.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type Description
uint Command = 802 (Get AGA-8 Hexanes+ gas ratios) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type Description
uint
Command = 802 or error code from
uint Specific to error. The run number if the command was successful.
Read the Data Registers.
Location
49780, 49809 to
49818, 49823
Data Type
Get AGA-8
Hexanes+ Gas
Fractions
Configuration
Structure
Description
See the AGA-8 Hexanes+
Configuration Registers section for details on these registers.
Set AGA-8 Hexanes+ Gas Ratios
The Set AGA-8 Hexanes+ Gas Ratios command sets the AGA-8
Hexanes+ Configuration Registers.
Write the configuration data into the registers.
Realflo User and Reference Manual
May 19, 2011
743
TeleBUS Protocol Interface
Location
49730, 49759 to 49768, 49773
Data Type
AGA-8
Hexanes+ Gas
Fractions
Configuration
Structure
Description
See the AGA-8 Hexanes+
Configuration Registers section for details on these registers.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type Description
uint Command = 804 (Set AGA-8 Hexanes+ Gas Ratios) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the configuration was accepted.
Location
49505
49506
Data
Type Description
uint
Command = 802 or error code from AGA-8
Calculation Errors or AGA-8 Command Errors.
uint Specific to error. The run number if the command was successful.
NX-19 Configuration
Configuration of the NX-19 flow calculation parameters is accomplished by setting the required values into the NX-19 Configuration Registers. This is not supported for PEMEX flow computers.
NX-19 Configuration Registers
The registers in the Actual Registers column in these tables are the registers containing the values already in use by the flow calculation routines. The registers in the Config. Registers column are the registers used for loading new configuration values to the flow calculation routines.
The NX-19 gas composition can be changed while the flow calculation is running. This allows an on-line gas chromatograph to provide updates to the gas composition. Frequent changes to the composition will result in the event log filling with gas composition events. When the log is full, further changes cannot be made until Realflo reads the log.
The registers in these tables are read from the flow computer using the
The registers in these tables are set in the flow computer using the
Config.
Register
49830
49831
49833
49835
49837
Actual
Register
49840
49841
49843
49845
49847
Data
Type
uint float float float float
Description
Meter run = 1 to 10
Specific gravity
Fraction of carbon dioxide
Fraction of nitrogen
Heating value (valid range: 0.07 to
1.52)
Realflo User and Reference Manual
May 19, 2011
744
Config.
Register
49839
Actual
Register
49849
Data
Type
uint
TeleBUS Protocol Interface
Description
Composition logging control
0 = log composition changes
1 = do not log composition changes
NX-19 Configuration Registers
Get NX-19 Gas Ratios Command
The Get NX-19 Gas Ratios command returns the NX-19 Configuration
Registers.
In Flow Computer versions 6.73 and older, when gas ratios are written to the flow computer using the Set NX-19 Gas Ratios command the new gas ratios are updated in the Configuration Config registers. The Configuration
Actual registers are not updated until a new Density calculation is started with the new values. The new gas ratios are not available to SCADA host software reading the Configuration Actual registers until a until a new
Density calculation is started with the new values.
In Flow Computer versions 6.74 and newer when gas ratios are written to the flow computer using the Set NX-19 Gas Ratios command the new gas ratios are updated in the Configuration Config registers and in the
Configuration Actual registers. This allows a SCADA host to immediately confirm the new ratios were written to the flow computer. The new gas ratios are not used by the flow computer until a new density calculation is started.
Write the Get NX-19 Gas Ratios command and read the Command
Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type Description
integer Command = 1901 (Get NX19 Gas Ratios) integer Meter run = 1 to 10 integer User number uint PIN for user
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type Description
integer
Command = 1901 or error code from
integer Specific to error. The run number if the command was successful.
Read the Data Registers.
Location Data Type
49840 to 49848 NX-19 Gas
Fractions
Configuration
Structure
Description
these registers.
Set NX-19 Gas Ratios Command
The Set NX-19 Gas Ratios command sets the NX-19 Configuration
Registers.
Realflo User and Reference Manual
May 19, 2011
745
TeleBUS Protocol Interface
Write the configuration data into the registers.
Location Data Type
49830 to 49838 NX-19 gas fractions configuration structure
Description
these registers.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type Description
uint Command = 1903 (Set NX-19 Gas Ratios) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the configuration was accepted.
49505
49506
Data
Type
uint uint
Description
Command = 1901 or error code from NX-19
Calculation Errors or NX-19 Command Errors.
Specific to error. The run number if the command was successful.
Orifice Plate Change
Changing the orifice plate requires forcing inputs and changing the AGA-3 configuration. Use the following commands to force the inputs before making a change to the AGA-3 configuration. Refer to the AGA-3
Configuration section for commands to change the orifice plate.
Start Plate Change: Temperature Input Commands
A plate change requires that the temperature, static pressure, and differential pressure inputs to a run be forced. These commands affect the temperature input. These commands need to be used with the Start Plate
Change: Static Pressure Input commands and the Start Plate Change:
Differential Pressure Input commands.
These commands force the temperature input to either the current temperature or to a fixed value. The flow computer will use the forced value during the plate change process.
Write the information required for the request.
Location
48690
48691
Data
Type Description
integer Meter run to calibrate: 1 to 10 float Forced manual value for temperature. This register is required only if calibration is done using a forced manual value. This register is not used if a forced recent value is used.
Write the command and read the Command Register until it is cleared.
Realflo User and Reference Manual
May 19, 2011
746
TeleBUS Protocol Interface
Location
49500
49501
49502
49503
Location
48690
48695
Data
Type
uint uint uint uint
Description
Command: 40 = (Start plate change: force current temp.)
41 = (Start plate change: force fixed temp.)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Read the Calibration Data Registers for the temperature value being used by the flow computer.
Data
Type
uint float
Description
Meter run = 1 to 10
Value for temperature while calibrating.
End Plate Change: Temperature Input Command
Ending a plate change requires that the temperature, static pressure, and differential pressure input to a run be returned to live values. This command needs to be used with the End Plate Change: Static Pressure command and the End Plate Change: Differential Pressure command.
This command ends a plate change by restoring the live input for temperature.
Write the information required for the request.
Location
48690
Data
Type Description
integer Meter run number: 1 to 10
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 42 = (End plate change: temperature)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Realflo User and Reference Manual
May 19, 2011
747
Location
49505
49506
Data
Type
uint uint
TeleBUS Protocol Interface
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Start Plate Change: Static Pressure Input Commands
A plate change requires that the temperature, static pressure, and differential pressure inputs to a run be forced. These commands affect the static pressure input. These commands needs to be used with the Start
Plate Change: Temperature Input commands and the Start Plate
Change: Differential Pressure Input commands.
These commands force the static pressure input to either the current static pressure or to a fixed value. The flow computer will use the forced value during the plate change process.
Write the information required for the request.
Location
48690
48691
Data
Type Description
integer Meter run to calibrate: 1 to 10 float Forced manual value for static pressure. This register is required only if calibration is done using a forced manual value. This register is not used if a forced recent value is used.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 43 = (Start plate change: force current pressure)
44 = (Start plate change: force fixed pressure)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Read the Calibration Data Registers for the static pressure value being used by the flow computer.
Realflo User and Reference Manual
May 19, 2011
748
Location
48690
48695
Data
Type
uint float
Description
Meter run = 1 to 10
TeleBUS Protocol Interface
Value for static pressure while calibrating.
End Plate Change: Static Pressure Input Command
Ending a plate change requires that the temperature, static pressure, and differential pressure input to a run be returned to live values. This command needs to be used with the End Plate Change: Temperature command and the End Plate Change: Differential Pressure command.
This command ends a plate change by restoring the live input for static pressure.
Write the information required for the request.
Location
48690
Data
Type Description
integer Meter run number: 1 to 10
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 45 = (End plate change: static pressure)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Start Plate Change: Differential Pressure Input Commands
A plate change requires that the temperature, static pressure, and differential pressure inputs to a run be forced. These commands affect the differential pressure input. These commands need to be used with the Start
Plate Change: Temperature Input commands and the Start Plate
Change: Static Pressure Input commands.
These commands force the differential pressure input to either the current differential pressure or to a fixed value. The flow computer will use the forced value during the plate change process.
Write the information required for the request.
Realflo User and Reference Manual
May 19, 2011
749
TeleBUS Protocol Interface
Location
48690
48691
Data
Type Description
integer Meter run to calibrate: 1 to 10 float Forced manual value for differential pressure. This register is required only if calibration is done using a forced manual value. This register is not used if a forced recent value is used.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 46 = (Start plate change: force current DP)
47 = (Start plate change: force fixed DP)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Read the Calibration Data Registers for the differential pressure value being used by the flow computer.
Location
48690
48695
Data
Type
uint float
Description
Meter run = 1 to 10
Value for differential pressure while calibrating.
End Plate Change: Differential Pressure Input Command
Ending a plate change requires that the temperature, static pressure, and differential pressure input to a run be returned to live values. This command needs to be used with the End Plate Change: Temperature command and the End Plate Change: Static Pressure command.
This command ends a plate change by restoring the live input for differential pressure.
Write the information required for the request.
Location
48690
Data
Type Description
integer Meter run number: 1 to 10
Write the command and read the Command Register until it is cleared.
Realflo User and Reference Manual
May 19, 2011
750
TeleBUS Protocol Interface
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 48 = (End plate change: differential pressure)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
User Account Configuration
User Accounts are manipulated using the commands Lookup User
Number, Lookup userID, Read Next Account, Delete Account and
Update Account.
User Account Configuration Registers
Data for these commands is written into the Configuration Registers shown below. Not all commands use all of the registers. Any value may be entered in the Unused Registers.
Config.
Register
49850
49851
49852
49853
Actual
Register
49860
49861
49862
49863
Data
Type
uint uint uint
Description
User number
Personal Identification Number (PIN)
Authorization level userID userID string
User Account Configuration Registers
Lookup User Number Command
The Lookup User Number command returns the user number corresponding to a userID. First, write the userID into the user account
Configuration Registers. Only the registers shown are used.
Location
49853
Data
Type Description
userID userID string (8 byte string packed into four registers, null terminated if less that 8 characters).
Write the Lookup User Number command and read the Command
Register until it is cleared.
Realflo User and Reference Manual
May 19, 2011
751
TeleBUS Protocol Interface
Location
49500
49501
49502
49503
Data
Type Description
uint Command = 100 (Lookup User Number) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type Description
uint
Echo command or error from Flow Calculation Engine
uint Specific to error. The run number if the command was successful.
Read the user account Reply Registers to determine the user number.
Location
49860
Data
Type Description
uint User number
Lookup User ID Command
The Lookup userID command returns the userID corresponding to a user number. First, write the user number into the user account configuration registers. Only the registers shown are used.
Location
49850
Data
Type
uint
Description
User number
Write the Lookup userID command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type Description
uint Command = 101 (Lookup userID) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type Description
uint
Echo command or error from Flow Calculation Engine
uint Specific to error. The run number if the command was successful.
Read the Reply Register to determine the user number.
Realflo User and Reference Manual
May 19, 2011
752
Location
49863
TeleBUS Protocol Interface
Data
Type Description
userID userID string (8 byte string packed into four registers, null terminated if less that 8 characters).
Delete Account Command
The Delete Account command removes an account from the flow computer. First, write the userID into the user account Configuration
Registers. Only the registers shown are used.
Location
49853
Data
Type Description
userID userID string (8 byte string packed into four registers, null terminated if less that 8 characters).
Write the Delete Account command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type Description
uint Command = 102 (Delete Account) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine if the account was deleted.
Location
49505
49506
Data
Type Description
uint
Echo command or error from Flow Calculation Engine
uint Specific to error. The run number if the command was successful.
Update Account Command
The Update Account command creates or updates an account. First, write the userID, PIN and authorization level into the user account configuration registers. Only the registers shown are used.
Location
49851
49852
49853
Data
Type
uint
Description
PIN uint Authorization level userID userID string (8 byte string packed into four registers, null terminated if less that 8 characters).
Write the Update Account command and read the Command Register until it is cleared.
Realflo User and Reference Manual
May 19, 2011
753
TeleBUS Protocol Interface
Location
49500
49501
49502
49503
Data
Type Description
uint Command = 103 (Update Account) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type Description
uint
Echo command or error from Flow Calculation Engine
uint Specific to error. The run number if the command was successful.
Read the user account Reply Registers to determine the user number (if needed).
Location
49860
Data
Type Description
uint User number
Read Next Account Command
The Read Next Account command is used to read account information from the flow computer. The command is repeated until the user accounts have been read.
First, write zero into the user number Configuration Register. User number zero is reserved for the flow computer. Retrieving the next user returns the first valid user account.
Location
49850
Data
Type Description
uint User number
Write the Read Next Account command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type Description
uint Command = 104 (Read Next Account) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type
uint
Description
uint
Echo command or error from Flow Calculation Engine
0
Read the user account Reply Registers to determine account information.
Location
Data
Type Description
Realflo User and Reference Manual
May 19, 2011
754
TeleBUS Protocol Interface
49860
49861
49862
49863 uint User number uint uint
PIN
Authorization level userID userID string
If the user number is non-zero, this is a valid account. If the user number is zero, this indicates that no more accounts can be found.
Repeat the process above, using the user number returned as the starting point. Repeat until the user number returned is zero.
Meter Runs Configuration
Meter Runs Configuration Registers
The Run Configuration Registers determine how many meter runs are active. The value is written into the Configuration Register.
Config.
Register
49870
Actual
Register
49875
Data
Type
uint
Description
Number of meter runs in use.
Set Number of Meter Runs Command
This command sets the number of active runs. The number of active runs determines the flow calculation period.
Write the configuration data into the register.
Location Type Description
49870 uint Number of runs to use: 1 to 10
Write the command 16 (Set Number of Runs) and read the Command
Register until it is cleared.
Location Type Description
49500
49501
49502
49503 uint uint uint uint
Command = 16 (Set Number of Runs)
Unused
User number
PIN for user
Read the Reply Registers to determine whether the configuration was accepted.
Location Type Description
49505
49506 uint uint
Echo command or error from Flow Calculation Engine
Unused
Flow Run Identification
The Run Identifier (runID) aids in identifying each flow run. The runID is a
16-character string. The runID string is stored in registers in the runID format.
For older flow computers the Run ID is a 16-character string. The Run ID string is stored in registers in the runID format. See the Run ID
Configuration Registers section.
Realflo User and Reference Manual
May 19, 2011
755
TeleBUS Protocol Interface
For version 6 or greater, the Run ID is a 32-character string. The Run ID string is stored in registers in the runID2 format. See the Long Run ID
Configuration Registers section.
Run ID Configuration Registers
The runID is set using the command Set runID. Data for the command is written into the ID Configuration Registers.
These registers overlap the Flow Computer ID registers, but use a different layout.
Config.
Register
49880
Actual
Register
49890
Data
Type Description
runID runID string.
Set Run ID Command
Write the configuration data into the registers.
Location
49880
Data
Type
runID
Description
runID string.
Write the command 19 (Set runID) and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command = 19 (Set runID)
Meter run = 1 to 10
User number
PIN for user
Read the Reply Registers to determine whether the configuration was accepted.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation Engine
Specific to error. The run number if the command was successful.
The flow computer will log a Set runID event, in the event log, for the run when the ID is set.
The command will not work if there is not enough room in the log for an event. If this occurs the flow runID will not be changed.
Get Run ID Command
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
Data
Type
uint uint uint
Description
Command = 20 (Get Run ID)
Meter run = 1 to 10
User number
Realflo User and Reference Manual
May 19, 2011
756
TeleBUS Protocol Interface
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation Engine
Specific to error. The run number if the command was successful.
Read the Data Registers.
Location
49890
Data
Type
runID
Description
runID string
Long Run ID Configuration Registers
The runID is set using the command Set Long Run ID. Data for the command is written into the ID Configuration Registers.
These registers overlap the Flow Computer ID registers and the Run ID registers, but use a different layout.
Proposed
Register
49880
Actual
Register
49880
Data
Type
RunI
D2
Description
RunID string.
Set Long Run ID Command
Write the configuration data into the registers.
Location Data
Type
49880
Description
runID2 runID string.
Write the command 21 (Set Long Run ID) and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command = 21 (Set Long Run ID)
Meter run = 1 to 10
User number
PIN for user
Read the Reply Registers to determine whether the configuration was accepted.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation Engine
Specific to error. The run number if the command was successful.
The flow computer will log a Set Run ID event, in the event log, for the run when the ID is set.
Realflo User and Reference Manual
May 19, 2011
757
TeleBUS Protocol Interface
The command will not work if there is not enough room in the log for an event. If this occurs the flow runID will not be changed.
Get Long Run ID Command
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
Data
Type
uint uint uint
Description
Command = 22 (Get Long Run ID)
Meter run = 1 to 10
User number
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation Engine
Specific to error. The run number if the command was successful.
Read the Data Registers.
Location Data
Type
49880
Description
RunID2 runID string
Flow Computer Execution Control
The execution Control Registers control the state of the flow routine execution for the selected meter run. The state of the flow routine execution is selected as either run or stop. Some commands, such as Contract
Configuration Commands, are not allowed when the flow calculation is running.
Execution Control Registers
Config.
Register
48500
48501
48502
Data
Type
uint uint uint
Description
Meter run = 1 to 10
Execution state: 1: stop, 2: run
Flow calculation interval (reserved but not used)
Execution Control Registers
Set Execution State Command
Write the desired execution state into the registers.
Location
48500
48501
Data
Type Description
uint Meter run = 1 to 10 uint Execution state:
1 for stopped state
2 for running state
Write the command and read the Command Register until it is cleared.
Realflo User and Reference Manual
May 19, 2011
758
TeleBUS Protocol Interface
Location
49500
49501
49502
49503
Data
Type Description
uint Command: 8 (Set Execute) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the execution state was accepted.
Location
49505
49506
Data
Type Description
uint
Echo command or error from Flow Calculation Engine
uint Specific to error. Meter run if the command was successful.
Read the current execution state from the registers shown in the following table. These registers always show the current execution status for the meter run.
Location
47501
46501
45601
Data
Type Description
uint Meter run 1 execution state:
1 when stopped
2 when running uint Meter run 2 execution state:
1 when stopped
2 when running uint Meter run 3 execution state:
1 when stopped
2 when running
Flow Computer ID Configuration
The Flow Computer Identifier allows Realflo to keep from mixing data from different flow computers. The ID is an eight-character string. The ID string is stored in registers using the same format as the existing userID data type.
Flow Computer Identifier Configuration Registers
The Flow Computer ID is set using the command Set Flow Computer ID.
Data for the command is written into the ID Configuration Registers.
Config.
Register
49880
Actual
Register
49885
Data
Type Description
userID Flow Computer ID string.
Set Flow Computer ID Command
The Flow Computer ID provides for a unique identification of each gas flow computer. This unique ID stops accidental mixing of data from different flow computers.
Write the configuration data into the registers.
Location Data
Type
49880
Description
userID Flow Computer ID string.
Realflo User and Reference Manual
May 19, 2011
759
TeleBUS Protocol Interface
Write the command 17 (Set Flow Computer ID) and read the Command
Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command = 17 (Set Flow Computer ID)
Meter run = 1 to 10
User number
PIN for user
Read the Reply Registers to determine whether the configuration was accepted.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation Engine
Specific to error. The run number if the command was successful.
Get Flow Computer ID Command
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
Data
Type
uint uint uint
Description
Command = 18 (Get Flow Computer ID)
Meter run = 1 to 10
User number
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation Engine
Specific to error. The run number if the command was successful.
Read the Data Registers.
Location Data
Type
49885
Description
userID Flow Computer ID string
Enron Modbus Time Stamp Configuration
The Enron Timestamp selects the type of timestamp for Enron flow history logs. Realflo and flow computer versions 6.77 and higher support the selection of time leads data or time lags data for the timestamp.
Time leads data selection time stamps the data for the period at the beginning of the period.
Time lags data selection time stamps the data for the period at the end of the period.
The configuration is valid for each run of the flow computer and is applied on the Enron Modbus enabled ports only. This control is hidden in PEMEX or
GOST application modes.
Realflo User and Reference Manual
May 19, 2011
760
TeleBUS Protocol Interface
Following registers determine how the Enron Modbus time stamp is defined.
The value is written into the Configuration Register.
Type Description Config.
Register
49874
Actual
Register
49879 uint Time stamp in Enron Modbus
0 = time leads data
1 = time lags data
Set Enron Modbus Time Stamp Command
This command sets the definition of the Enron Modbus time stamp.
Write the configuration data into the register.
Register
49874
Type
uint
Description
Time stamp in Enron Modbus
0 = time leads data
1 = time lags data
Write the command 23 (Set Enron Modbus Time Stamp Command) and read the Command Register until it is zero.
Register
49500
49501
49502
Type
uint uint uint
Description
Command = 23 (Set Enron Modbus Time Stamp)
Unused
User number
49503
Read the Reply Registers to determine whether the configuration was accepted.
Register
49505 uint
Type
Uint
Pass code for user
Description
Command status:
23 = command complete
Other = error code
49506 uint Command result: meter run if successful
Real Time Clock Configuration
The Real Time Clock is fully adjustable using the configuration registers.
The RTC is configured using the Set Real Time Clock or the Adjust Real
Time Clock commands.
The following methods cannot be used to set the real time clock when using the flow computer.
The CNFG Real Time Clock and Alarm register assignment in Telepace.
Realflo User and Reference Manual
May 19, 2011
761
TeleBUS Protocol Interface
The setclock function in ISaGRAF.
The Real Time Clock dialog in Telepace or ISaGRAF.
Using any of these methods to set the Real Time Clock may result in the flow computer logging data incorrectly.
Real Time Clock Configuration Registers
The registers in these tables are read from the flow computer using the command.
Config.
Register
48503
48504
48505
48506
48507
48508
Data
Type
uint uint uint uint uint uint
Description
Years, 1997 to 2096
Months, 1 to 12
Days, 1 to 31, with exceptions
Hours, 0 to 23
Minutes, 0 to 59
Seconds, 0 to 59
Real Time Clock Settings Registers
Config.
Register
48509
Data
Type
sint
Description
Seconds, -32000 to 32000, Increment / Decrement number of seconds
Real Time Clock Adjustment Registers
The actual registers in the table below are updated on each execution of the gas flow engine.
Actual
Register
48510
48511
48512
48513
48514
48515
48516
48517
48518
48519
48520
Data
Type
uint uint uint uint uint uint uint uint uint uint uint
Description
Real Time Clock Hour, 0 to 23
Real Time Clock Minute, 0 to 59
Real Time Clock Second, 0 to 59
Real Time Clock Year, 0 to 99
Real Time Clock Month, 1 to 12
Real Time Clock Day, 1 to 31
Reserved but unused
Reserved but unused
Reserved but unused
Reserved but unused
Reserved but unused
Real Time Clock Actual Value Registers
Read Real Time Clock
One Real Time Clock is configured for the flow computer.
Location
48510
48511
48512
Data
Type
uint uint uint
Description
Hour: 0 to 23
Minute: 0 to 59
Second: 0 to 59
Realflo User and Reference Manual
May 19, 2011
762
Location
48513
Data
Type
uint
TeleBUS Protocol Interface
Description
Year: (19)97 to 99, (20)00 to 96. This register contains one or two digits only, not the entire four digit year.
Month: 1 to 12
Day: 1 to 31
Other RTC Configuration data
48514
48515
48516 to 48520 uint uint
Set Real Time Clock Command
Write the new time into the registers.
Location
48503
48504
48505
48506
48507
48508
Data
Type
uint uint uint
Description
uint Year: (19) 97 to 99, (20) 00 to 96. The complete four digit year needs to be entered. uint Month : 1 to 12 uint
Day : 1 to 31
Hour : 0 to 23
Minute : 0 to 59
Second : 0 to 59
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type Description
uint Command: 6 (Set Real Time Clock) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the time was accepted.
Location
49505
49506
Data
Type Description
uint
Echo command or error from Flow Calculation Engine
uint Specific to error. 0 if the command was successful.
Adjust Real Time Clock Command
Write the time adjustment into the registers.
Location
48509
Data
Type Description
integer Seconds, -32000 to 32000
Write the command 9 (Adjust Real Time Clock) and read the Command
Register until it is cleared.
Location
49500
49502
49503
Data
Type Description
uint Command: 9 (Adjust Real Time Clock) uint User number uint PIN for user
Realflo User and Reference Manual
May 19, 2011
763
TeleBUS Protocol Interface
Read the Reply Registers to determine whether the time adjustment was accepted.
Location
49505
49506
Data
Type Description
uint
Echo command or error from Flow Calculation Engine
uint Specific to error. 0 if the command was successful.
SolarPack 410 Power Management Configuration
The SolarPack 410 Power Management configuration is fully adjustable using the configuration registers. The SolarPack 410 Power Management is configured using the Set Power Management or the Get Power
Management commands.
SolarPack 410 Power Management Configuration Registers
Power management is configured using the following registers.
The Power Management Configuration Registers are defined as follows.
The registers in the Register column are the registers containing the values already in use by the flow computer or are the registers used for loading new configuration values to the flow computer.
The registers in this table are read using the
The registers in this table are set using the
Register
43180
Data
Type
uint
Description
43181
43182
43183
43184
43185
43186
43187
43188
43189
43190
43191
43192
43193
43194
43195
43196
43197
43198 uint uint uint uint uint uint uint uint uint uint uint uint uint uint uint uint uint uint
Enable Input: Time in minutes until power off (1 to
240)
Enable Input: Radio power 0=off, 1=on
Enable Input: Bluetooth power 0=off, 1=on
Enable Input: Display backlight 0=off, 1=on
Enable input: Display 0=off, 1=on
Continuous wake: enable 0=off, 1=on
Continuous wake: Radio power 0=off, 1=on
Continuous wake: Bluetooth power 0=off, 1=on
Continuous wake: Display backlight 0=off, 1=on
Continuous wake: Display 0=off, 1=on
Scheduled Wake: Time in minutes until power off (1 to 240)
Scheduled Wake: Radio power 0=off, 1=on
Scheduled Wake: Bluetooth power 0=off, 1=on
Scheduled Wake: Display backlight 0=off, 1=on
Scheduled Wake: Display 0=off, 1=on
Scheduled Wake: Number of times to wake (0 to 24)
Scheduled Wake: Time 1 to wake (minutes since
00:00)
Scheduled Wake: Time 2 to wake (minutes since
00:00)
Scheduled Wake: Time 3 to wake (minutes since
00:00)
Realflo User and Reference Manual
May 19, 2011
764
TeleBUS Protocol Interface
Register Data
Type
uint
Description
43199
43200
43201
43202
43203
43204
43205
43206
43207
43208
43209
43210
43211
43212
43213
43214
43215
43216
43217
43218
43219 uint uint uint uint uint uint uint uint uint uint uint uint uint uint uint uint uint uint uint uint
Scheduled Wake: Time 4 to wake (minutes since
00:00)
Scheduled Wake: Time 5 to wake (minutes since
00:00)
Scheduled Wake: Time 6 to wake (minutes since
00:00)
Scheduled Wake: Time 7 to wake (minutes since
00:00)
Scheduled Wake: Time 8 to wake (minutes since
00:00)
Scheduled Wake: Time 9 to wake (minutes since
00:00)
Scheduled Wake: Time 10 to wake (minutes since
00:00)
Scheduled Wake: Time 11 to wake (minutes since
00:00)
Scheduled Wake: Time 12 to wake (minutes since
00:00)
Scheduled Wake: Time 13 to wake (minutes since
00:00)
Scheduled Wake: Time 14 to wake (minutes since
00:00)
Scheduled Wake: Time 15 to wake (minutes since
00:00)
Scheduled Wake: Time 16 to wake (minutes since
00:00)
Scheduled Wake: Time 17 to wake (minutes since
00:00)
Scheduled Wake: Time 18 to wake (minutes since
00:00)
Scheduled Wake: Time 19 to wake (minutes since
00:00)
Scheduled Wake: Time 20 to wake (minutes since
00:00)
Scheduled Wake: Time 21 to wake (minutes since
00:00)
Scheduled Wake: Time 22 to wake (minutes since
00:00)
Scheduled Wake: Time 23 to wake (minutes since
00:00)
Scheduled Wake: Time 24 to wake (minutes since
00:00)
Set Power Management Command
This command writes the power management settings.
Write the configuration to the configuration registers.
Register Data
Type
43180 to
43219
Description
See above.
Realflo User and Reference Manual
May 19, 2011
765
TeleBUS Protocol Interface
Write the command and read the Command Register until it is cleared.
Register
49500
49502
49503
Data
Type
uint uint uint
Description
Command = 152 (Set Power Management)
User number
PIN
Read the Reply Registers when the command is complete. An error is returned if the configuration data are invalid.
Description Register Data
Type
49505 uint
49506 uint
Command status
152 = command complete
Command result:
0 = OK
1 = invalid parameters
Get Power Management Command
This command reads the power management settings.
Write the command and read the Command Register until it is cleared.
Register Data
Type
49500
49502
49503 uint uint uint
Description
Command = 153 (Get Power Management)
User number
PIN
Read the Reply Registers when the command is complete. An error is returned if the configuration data are invalid.
Register Data
Type
49505 uint
Description
49506 uint
Command status
153 = command complete other = error code
Command result:
0 = OK
1 = invalid parameters
Read the configuration from the configuration registers if successful.
Register Data
Type
43180 to
43219
Description
See above.
If the configuration is incorrect, the following error code will be returned.
Number
30140
Description
Invalid power management configuration
SolarPack 410 Gas Sampler Output
The gas sampler output is pulsed based on the current flow. The pulse rate is configurable with a factor based on the current volume. The typical
Realflo User and Reference Manual
May 19, 2011
766
TeleBUS Protocol Interface interval is once per 15 seconds to once per 2 hours. The pulse width is user adjustable from 0.1 seconds to 5.0 seconds.
Gas Sampler Configuration
The gas sampler is configured using these registers.
Register Data
Type
43230-43231 Float
43232 uint
Description
Volume/pulse using contract units for run 1.
Pulse width in multiples of 0.1 seconds (1 to 50)
Set Gas Sampler Configuration Command
This command writes the gas sampler settings.
Write the configuration to the configuration registers.
Register Data
Type
43230 to
43232
Description
See above.
Write the command and read the Command Register until it is cleared.
Register Data
Type
49500
49502
49503 uint uint uint
Description
Command = 154 (Set Gas Sampler Configuration)
User number
PIN
Read the Reply Registers when the command is complete. An error is returned if the configuration data are invalid.
Register Data
Type
49505 uint
Description
49506 uint
Command status
154 = command
Command result:
0 = OK
1 = invalid parameters
Get Gas Sampler Configuration Command
This command reads the gas sampler settings.
Write the command and read the Command Register until it is cleared.
Register Data
Type
49500
49502
49503 uint uint uint
Description
Command = 155 (Get Gas Sampler Configuration)
User number
PIN
Read the Reply Registers when the command is complete. An error is returned if the configuration data are invalid.
Register Data
Type
Description
Realflo User and Reference Manual
May 19, 2011
767
TeleBUS Protocol Interface
Register Data
Type
49505 uint
Description
49506 uint
Command status
155 = command complete
Command result:
0 = OK
1 = invalid parameters
Read the configuration from the configuration registers if successful.
Register
43230 to
43232
Data
Type
Description
See above.
If the configuration is incorrect, the following error code will be returned.
Number
30139
Description
Invalid gas sampler output configuration
SolarPack 410 Pulse Input Accumulation
The SolarPack 410 flow computer can accumulate a pulse input. The flow computer counts the number of pulses, divides by a K factor and accumulates the results. Total volume, today‟s volume, yesterday‟s volume, this month‟s volume, and last month‟s volume accumulators are provided.
Pulse Input Accumulation Configuration
The pulse input accumulation is configured using these registers.
Register
43240
Data
Type
uint
Description
43241-43242 float
43243 Uint
Counter register (30001 to 39999, 40001 to 49999)
Specifies two registers containing the count value.
These registers need to contain a 32-bit unsigned value. The value needs to increase or remain the same (i.e. it cannot decrease) except when it rolls over from the maximum 32-bit unsigned value to zero.
K factor (any value > 0) in pulses/volume
Volume Units
0 = ft
1 = m
3
3
(cubic feet)
(cubic metres)
2 = litres
3 = barrels (42 US gallons)
4 = US gallons
Pulse Input Accumulation Registers
The pulse accumulation is reported in these registers. The registers are available.
Register Data
Type
43248-43249 ulong
43250-43251 float
Description
Pulse accumulator raw total (total number of pulses)
Pulse accumulator total volume in configured units
Realflo User and Reference Manual
May 19, 2011
768
Register Data
Type
43252-43253 float
43254-43255 float
43256-43257 float
43258-43259 float
43260 Uint
TeleBUS Protocol Interface
Description
Pulse accumulator today‟s volume in configured units
Pulse accumulator yesterday‟s volume in configured units
Pulse accumulator this month‟s volume in configured units
Pulse accumulator last month‟s volume in configured units
Volume Units
0 = ft
3
1 = m
3
(cubic feet)
(cubic metres)
2 = litres
3 = barrels (42 US gallons)
4 = US gallons
Set Pulse Input Configuration Command
This command writes the pulse input settings.
Write the configuration to the configuration registers.
Register Data
Type
43240 to
43243
Description
See above.
Write the command and read the Command Register until it is cleared.
Register
49500
49502
49503
Data
Type
uint uint uint
Description
Command = 156 (Set Pulse Input Configuration)
User number
PIN
Read the Reply Registers when the command is complete. An error is returned if the configuration data are invalid. The command does not work if there isn‟t sufficient room in the run 1 event log to log changes.
Description Register Data
Type
49505 uint
49506 uint
Command status
156 = command complete
Command result:
0 = OK
1 = invalid parameters
Get Pulse Input Configuration Command
This command reads the pulse input settings.
Write the command and read the Command Register until it is cleared.
Register Data
Type
49500 uint
Description
Command = 157 (Get Pulse Input Configuration)
Realflo User and Reference Manual
May 19, 2011
769
TeleBUS Protocol Interface
Register Data
Type
49502
49503 uint uint
Description
User number
PIN
Read the Reply Registers when the command is complete. An error is returned if the configuration data are invalid.
Register Data
Type
49505 uint
Description
49506 uint
Command status
157 = command complete
Command result:
0 = OK
1 = invalid parameters
Read the configuration from the configuration registers if successful.
Register Data
Type
43240 to
43243
Description
See above.
If the configuration is incorrect, the following error code will be returned.
Number
30138
Description
Invalid pulse configuration
Display Control Configuration
Users may select the data that is displayed on the optional display module.
The data to display and the interval between the displayed items is user
defined. Data items that may be displayed are shown in the Display Item
Display Control Configuration Registers
The Display Control Configuration Registers are defined as follows. The registers in the Register column are the registers containing the values already in use by the flow computer MVT transmitter or are the registers used for loading new configuration values to the flow computer and the transmitter.
The registers in this table are read using the Get Display Control
The registers in this table are set using the Set Display Control
Register Data
Type
43470
43471 uint uint
Description
43472 uint
Display interval (2 to 60 seconds)
Display custom item 1
(Use one identifier from the list in Display Item
Identifiers)
Display custom item 2
(Use one identifier from the list in Display Item
Identifiers)
Realflo User and Reference Manual
May 19, 2011
770
TeleBUS Protocol Interface
Register Data
Type
43473 uint
Description
43474
43475
43476
43477
43478
43479
43480
43481
43482 uint uint uint uint uint uint uint uint uint
Display custom item 3
(Use one identifier from the list in Display Item
Identifiers)
Display custom item 4
(Use one identifier from the list in Display Item
Identifiers)
Display custom item 5
(Use one identifier from the list in Display Item
Identifiers)
Display custom item 6
(Use one identifier from the list in Display Item
Identifiers)
Display custom item 7
(Use one identifier from the list in Display Item
Identifiers)
Display custom item 8
(Use one identifier from the list in Display Item
Identifiers)
Display custom item 9
(Use one identifier from the list in Display Item
Identifiers)
Display custom item 10
(Use one identifier from the list in Display Item
Identifiers)
Display custom item 11
(Use one identifier from the list in Display Item
Identifiers)
Display custom item 12
(Use one identifier from the list in Display Item
Identifiers)
Display Item Identifiers
Use these values when programming the display controller.
Display Item
DP (input units)
SP (input units)
PT (input units)
Current Time runID
Orifice plate size (input units)
Calculation state (contract units)
Flow volume rate (contract units)
Flow mass rate (contract units)
Flow energy rate (contract units)
Flow Time
Today‟s flow volume (contract units)
Yesterday‟s flow volume (contract units)
Run 1
1001
1002
1003
1004
1005
1006
1007
1008
1009
1010
1011
1012
1013
Run 2
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
Run 3
3001
3002
3003
3004
3005
3006
3007
3008
3009
3010
3011
3012
3013
Run 4 Run 5
4001 5001
4002 5002
4003 5003
4004 5004
4005 5005
4006 5006
4007 5007
4008 5008
4009 5009
4010 5010
4011
4012
4013
5011
5012
5013
Realflo User and Reference Manual
May 19, 2011
771
Display Item
Pulses
Relative Density
Pipe diameter
Atmospheric pressure
Battery Voltage (SolarPack 410 only)
Custom Item 1
Custom Item 2
Custom Item 3
Custom Item 4
Custom Item 5
Display Item
DP (input units)
SP (input units)
PT (input units)
Current Time runID
Orifice plate size (input units)
Calculation state (contract units)
Flow volume rate (contract units)
Flow mass rate (contract units)
Flow energy rate (contract units)
Flow time
Today‟s flow volume (contract units)
Yesterday‟s flow volume (contract units)
Pulses
Relative Density
Pipe diameter
Atmospheric pressure
Battery Voltage
Custom Item 1
Custom Item 2
Custom Item 3
Custom Item 4
Custom Item 5
Run 1
1014
1015
1016
1017
1018
1101
1102
1103
1104
1105
Run 6
6001
6002
6003
6004
6005
6006
6007
6008
6009
6010
6011
6012
6013
6014
6015
6016
6017
6018
6101
6102
6103
6104
6105
Run 2
2014
2015
2016
2017
2018
2101
2102
2103
2104
2105
7001
7002
7003
7004
7005
7006
7007
7008
7009
7010
7011
7012
7013
7014
7015
7016
7017
7018
7101
7102
7103
7104
7105
TeleBUS Protocol Interface
Run 7
Run 3
3014
3015
3016
3017
3018
3101
3102
3103
3104
3105
Run 8
8001
8002
8003
8004
8005
8006
8007
8008
8009
8010
8011
8012
8013
8014
8015
8016
8017
8018
8101
8102
8103
8104
8105
Run 4
4014
4015
4016
4017
4018
4101
4102
4103
4104
4105
Run 9
9001
9002
9003
9004
9005
9006
9007
9008
9009
9010
9011
9012
9013
9014
9015
9016
9017
9018
9101
9102
9103
9104
9105
Run 5
5014
5015
5016
5017
5018
5101
5102
5103
5104
5105
Run 10
Get Display Control Configuration Command
This command reads a display control configuration from the flow computer.
Write the command and read the Command Register until it is cleared.
Register Data Description
10001
10002
10003
10004
10005
10006
10007
10008
10009
10010
10011
10012
10013
10014
10015
10016
10017
10018
10101
10102
10103
10104
10105
Realflo User and Reference Manual
May 19, 2011
772
TeleBUS Protocol Interface
49500
49501
49502
49503
Type
uint uint uint uint
Command = 137 (Get Display Control
Configuration)
Transmitter number = 1 to 10
User number
PIN
Read the Reply Registers when the command is complete. An error is returned if the command parameters are invalid.
Description Register Data
Type
49505 uint
49506 uint
Command status:
137 = command complete
Other = error code
Command result:
0 = error occurred
1 to 10 = transmitter number
If a transmitter was found, read the actual Configuration Registers.
Register
43470 to 43482
Data Type
Display
Control
Configuration
Structure
Description
See the Display Control
Configuration Registers section for details.
Set Display Control Configuration Command
The command writes a display control configuration to the flow computer.
The flow computer writes the configuration and data to the transmitter. If the transmitter does not respond, the configuration is still saved in the flow computer memory.
Write data into the Configuration Registers.
Register
43470 to 43482
Data Type
Display control configuration structure
Description
See the Display Control
Configuration Registers section for details.
Write the command and read the Command Register until it is cleared.
Register
49500
Data
Type
uint
Description
49501
49502
49503 uint uint uint
Command = 138 (Set Display Control
Configuration)
Transmitter number = 1 to 10
User number
PIN
Read the Reply Registers when the command is complete. An error is returned if the configuration data are invalid.
Description Register Data
Type
49505 uint Command status:
138 = command complete
Realflo User and Reference Manual
May 19, 2011
773
TeleBUS Protocol Interface
Register Data
Type
Description
49506 uint
Other = error code
Command result:
0 = error occurred
1 to 10 = transmitter number
Get Display Control Custom Configuration Command
This command reads a display control custom configuration from the flow computer.
Write the index number of the custom configuration to get from the flow computer.
Register Data
Type
43483 uint
Configuration
Number of the custom configuration for the flow run.
1 to 5.
Write the command and read the command register until it is cleared.
Register
49500
Data
Type
uint
Configuration
49501
49502
49503
Uint
Uint
Uint
Command = 150 (Get Display Controller Custom
Configuration)
Transmitter number = 1 to 10
User number
PIN
Read the Reply Registers when the command is complete. An error is returned if the configuration data are invalid.
Register Data
Type
49505 uint
Configuration
49506 Uint
Command status
150 = command complete
Other = error code
Command result:
0 = error occurred
1 to 10 = Transmitter number
If a transmitter was found, read the actual Custom Configuration record.
Register Data
Type
43483 uint
Configuration
43484
43485
Uint
Uint
Index number of the custom configuration for the flow run.
1 to 5
Register to display: 00001 to 09999, 10001 to
19999, 30001 to 39999, 40001 to 49999.
0 = not used
Display type
1 = Boolean
2 = Signed integer
3 = Unsigned integer
4 = Signed double
Realflo User and Reference Manual
May 19, 2011
774
TeleBUS Protocol Interface
Register Data
Type
43486 to
43489
43490 to
43493
Configuration
5 = Unsigned double
6 = ISaGRAF integer
7 = Floating point
Chars Item description string. Seven character string packed into four registers. The first character is in the low order byte. The second character is in the high order byte.
Chars Units string. Seven character string packed into four registers. The first character is in the low order byte. The second character is in the high order byte.
Set Display Control Custom Configuration Command
This command reads a display control custom configuration from the flow computer.
Write the data for one custom configuration index number to the flow computer.
Register Data
Type
43483
43484
43485
43486 to
43489
43490 to
43493
Configuration
uint
Uint
Uint
Index number of the custom configuration for the flow run.
1 to 5
Register to display: 00001 to 09999, 10001 to
19999, 30001 to 39999, 40001 to 49999.
0 = not used
Display type
1 = Boolean
2 = Signed integer
3 = Unsigned integer
4 = Signed double
5 = Unsigned double
6 = ISaGRAF integer
7 = Floating point
Chars Item description string. Seven character string packed into four registers. The first character is in the low order byte. The second character is in the high order byte.
Chars Units string. Seven character string packed into four registers. The first character is in the low order byte. The second character is in the high order byte.
Write the command and read the command register until it is cleared.
Register
49500
Data
Type
uint
Configuration
49501
49502
49503
Uint
Uint
Uint
Command = 151 (Set Display Controller Custom
Configuration)
Transmitter number = 1 to 10
User number
PIN
Realflo User and Reference Manual
May 19, 2011
775
TeleBUS Protocol Interface
Read the Reply Registers when the command is complete. An error is returned if the configuration data are invalid.
Configuration Register Data
Type
49505 uint
49506 Uint
Command status
151 = command complete
Other = error code
Command result:
0 = error occurred
1 to 10 = Transmitter number
Process Input / Output Configuration
Process I/O defines scaling and alarms for input and output points used by your process. Input points convert integer values read from input modules into floating-point values. Output points convert floating-point values into integer values for output modules.
Process I/O is normally used with I/O points that are not related to the flow runs. Use the run configuration to scale inputs to flow runs.
Process I/O is not available on SCADAPack Flow Computers with ISaGRAF firmware. Use an ISaGRAF program to scale I/O values.
The Process I/O configuration registers are defined as follows. The registers in the Actual Register column are the registers containing the values already in use by the flow computer. The registers in the Config. Register column are the registers used for loading new configuration values to the flow computer.
Process I/Os Configuration Registers
Config.
Register
43400
Actual
Register
43405
43401 43406
Data
Type
uint
Description
Number of process inputs
On SCADAPack Flow Computers the maximum number of inputs is 10.
On SCADAPack 32, SCADAPack
314/330/334 and SCADAPack 350
Flow Computers the maximum number of inputs 30. uint Number of process outputs
The maximum number of outputs is 10.
Process Input Configuration Registers
The Process Input configuration are used with the process I/O commands.
Config.
Register
43410
Actual
Register
43440
Data
Type
uint
Description
43411
43412
43441
43442 uint uint
Process input status
0 = disabled
1 = enabled
Source format
0 = Telepace Integer
5 = ISaGRAF Integer
Source register:
Realflo User and Reference Manual
May 19, 2011
776
Description
TeleBUS Protocol Interface
Config.
Register
Actual
Register
Data
Type
43413
43414
43415
43416
43417
43419
43421
43423
43425
43427
43429
43431
43443
43444
43445
43446
43447
43449
43451
43453
43455
43457
43459
43461 uint uint uint uint long long float float float float float float
30001 to 39999, 40001 to 49999
Low alarm point:
0 = disabled
00001 to 09999 = address of coil
High alarm point:
0 = disabled
00001 to 09999 = address of coil
Destination format
0 = Most Significant Word First (MSW
First)
1 = Least Significant Word First (LSW
First)
Destination register:
40001 to 49999
Source range zero scale:
Source format 0:
–32768 to 32767
Source format 5:
–2,147,483,648 to
2,147,483,647
Source range full scale:
Source format 0:
–32768 to 32767
Source format 5:
–2,147,483,648 to
2,147,483,647
Destination range zero scale
Destination range full scale
Low alarm setpoint
Low alarm hysteresis
High alarm setpoint
High alarm hysteresis
Process Output Configuration Registers
The Process Output Configuration Registers are used with the process I/O commands.
Config.
Register
43410
Actual
Register
43440
Data
Type
uint
Description
43411
43412
43413
43414
43415
43441
43442
43443
43444
43445 uint uint uint uint uint
Process output status
0 = disabled
1 = enabled
Source format
0 = Most Significant Word First (MSW
First)
1 = Least Significant Word First (LSW
First)
Source register: 40001 to 49999
Low alarm point:
0 = disabled
00001 to 09999 = address of coil
High alarm point:
0 = disabled
00001 to 09999 = address of coil
Destination format
0 = Telepace Integer
Realflo User and Reference Manual
May 19, 2011
777
Description
TeleBUS Protocol Interface
Config.
Register
Actual
Register
Data
Type
43416
43417
43419
43421
43423
43425
43427
43429
43431
43446
43447
43449
43451
43453
43455
43457
43459
43461 uint long long float float float float float float
5 = ISaGRAF Integer
Destination register: 40001 to 49999
Destination range zero scale:
Destination format 0:
–32768 to 32767
Destination format 5:
–2,147,483,648 to 2,147,483,647
Destination range full scale:
Destination format 0:
–32768 to 32767
Destination format 5:
–2,147,483,648 to 2,147,483,647
Source range zero scale
Source range full scale
Low alarm setpoint
Low alarm hysteresis
High alarm setpoint
High alarm hysteresis
Get Number of Process Inputs Command
This command reads the maximum number of process inputs from the flow computer.
Write the command and read the Command Register until it is cleared.
Register Data
Type
49500
49501
49502
49503 uint uint uint uint
Description
Command = 140 (Get Number of Process Inputs)
0
User number
PIN
Read the Reply Registers when the command is complete. An error is returned if the command parameters are invalid.
Register Data
Type
49505 uint
Description
49506 uint
Echo command or error from Flow Calculation
Specific to error. 0 if the command was successful.
Read the Actual Configuration Registers.
Register
43405
Data
Type
uint
Description
Process I/Os Configuration Registers
section for details.
Get Process Input Command
This command reads one Process Input configuration from the flow computer.
Write the command and read the Command Register until it is cleared.
Register Data
Type
Description
Realflo User and Reference Manual
May 19, 2011
778
TeleBUS Protocol Interface
49500
49501
49502
49503 uint uint uint uint
Command = 142 (Get Process Input)
Process Input Number
1 to 10 for SCADAPack Flow Computers
1 to 30 for SCADAPack 32, SCADAPack
314/330/334 and SCADAPack 350 Flow
Computers
User number
PIN
Read the Reply Registers when the command is complete. An error is returned if the command parameters are invalid.
Description Register Data
Type
49505 uint
49506 uint
Echo command or error from Flow Calculation
Process Input Number. 0 if the command was unsuccessful.
Read the Actual Configuration Registers.
Register
43440 to 43462
Data Type
mixed
Description
section for details.
Set Process Input Command
This command writes one Process Input configuration to the flow computer.
Write the Configuration Registers.
Register
43410 to 43432
Data Type
mixed
Description
section for details.
Write the command and read the Command Register until it is cleared.
Register Data
Type
49500
49501 uint uint
49502
49503 uint uint
Description
Command = 143 (Set Process Input)
Process Input Number
1 to 10 for SCADAPack Flow Computers
1 to 30 for SCADAPack 32, SCADAPack
314/330/334 and SCADAPack 350 Flow
Computers
User number
PIN
Read the Reply Registers when the command is complete. An error is returned if the command parameters are invalid.
Register Data
Type
49505 uint
Description
49506 uint
Echo command or error from Flow Calculation
Process Input Number. 0 if the command was
Realflo User and Reference Manual
May 19, 2011
779
TeleBUS Protocol Interface unsuccessful.
Get Number of Process Outputs Command
This command reads the maximum number of Process Outputs from the flow computer.
Write the command and read the Command Register until it is cleared.
Register Data
Type
49500 uint
49501
49502
49503 uint uint uint
Description
Command = 144 (Get Number of Process Outputs)
0
User number
PIN
Read the Reply Registers when the command is complete. An error is returned if the command parameters are invalid.
Description Register Data
Type
49505 uint
49506 uint
Echo command or error from Flow Calculation
Specific to error. 0 if the command was successful.
Read the Actual Configuration Registers.
Register
43406
Data Type
uint
Description
section for details.
Get Process Output Command
This command reads one Process Output configuration from the flow computer.
Write the command and read the Command Register until it is cleared.
Register Data
Type
49500
49501 uint uint
49502
49503 uint uint
Description
Command = 146 (Get Process Output)
Process Output Number
1 to 10 for SCADAPack Flow Computers
1 to 10 for SCADAPack 32, SCADAPack
314/330/334 and SCADAPack 350 Flow
Computers
User number
PIN
Read the Reply Registers when the command is complete. An error is returned if the command parameters are invalid.
Description Register Data
Type
49505 uint
49506 uint
Echo command or error from Flow Calculation
Process Output Number. 0 if the command was unsuccessful.
Realflo User and Reference Manual
May 19, 2011
780
TeleBUS Protocol Interface
Read the Actual Configuration Registers.
Register
43440 to 43462
Data Type
mixed
Description
section for details.
Set Process Output Command
This command writes one Process Output configuration to the flow computer.
Write the Configuration Registers.
Register
43410 to 43432
Data Type
mixed
Description
section for details.
Write the command and read the Command Register until it is cleared.
Register Data
Type
49500
49501 uint uint
49502
49503 uint uint
Description
Command = 147 (Set Process Output)
Process Output Number
1 to 10 for SCADAPack Flow Computers
1 to 10 for SCADAPack 32, SCADAPack
314/330/334 and SCADAPack 350 Flow
Computers
User number
PIN
Read the Reply Registers when the command is complete. An error is returned if the command parameters are invalid.
Description Register Data
Type
49505 uint
49506 uint
Echo command or error from Flow Calculation
Process Output Number. 0 if the command was unsuccessful.
Calibration Registers
The flow calculations continue to execute while sensors are being calibrated. The sensor value needs to be forced to a fixed value during calibration. The current value of the input or a fixed value of your choice may be used.
Calibration Registers
The Calibration Settings registers hold the forced value for the device currently being calibrated. These registers are used when the calibration commands are sent to the flow computer.
Actual
Register
48690
48691
Data
Type
uint float
Description
Meter run = 1 to 10
Forced temperature, static pressure or differential pressure.
Realflo User and Reference Manual
May 19, 2011
781
TeleBUS Protocol Interface
Actual
Register
48693
Data
Type Description
ulong Forced change in pulse counts
Calibration Settings Registers
The Calibration Data registers hold the live measured values from the device being calibrated. Data in these registers is updated while calibration is in process.
Actual
Register
48695
48697
Data
Type Description
float Temperature, static pressure or differential pressure during calibration. ulong Change in pulse counts during calibration (AGA-7 only).
Calibration Data Registers
Force Temperature Input Commands
Start temperature input calibration by forcing either the recent temperature input or a manual forced value. The flow computer will use the forced value during the calibration process.
Write the information required for the request.
Location
48690
48691
Data
Type Description
integer Meter run to calibrate: 1 to 10 float Forced manual value for temperature. This register is required only if calibration is done using a forced manual value. This register is not used if a forced recent value is used.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 30 = (Force Recent Temperature)
31 = (Force Manual Temperature)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Read the Calibration Data Registers for the Temperature value being used by the flow computer.
Location
48690
Data
Type
uint
Description
Meter run = 1 to 10
Realflo User and Reference Manual
May 19, 2011
782
Location
48695
Data
Type
float
TeleBUS Protocol Interface
Description
Value for temperature while calibrating.
End Temperature Calibration Command
End temperature input calibration by restoring the live input for temperature.
Write the information required for the request.
Location
48690
Data
Type Description
integer Meter run number: 1 to 10
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 32 = (End Temperature Calibration)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Force Static Pressure Input Commands
Start static pressure input calibration by forcing either the recent pressure input or a manual forced value. The flow computer will use the forced value during the calibration process.
Write the information required for the request.
Location
48690
48691
Data
Type Description
integer Meter run to calibrate: 1 to 10 float Forced manual value for static pressure. This register is required only if calibration is done using a forced manual value. This register is not used if a forced recent value is used.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 33 = (Force Recent Pressure)
34 = (Force Manual Pressure)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Realflo User and Reference Manual
May 19, 2011
783
TeleBUS Protocol Interface
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Read the Calibration Data Registers for the Static Pressure value being used by the flow computer.
Location
48690
48695
Data
Type
uint float
Description
Meter run = 1 to 10
Value for static pressure while calibrating.
End Static Pressure Calibration Command
End Static Pressure input calibration by restoring the live input for pressure.
Write the information required for the request.
Location
48690
Data
Type Description
integer Meter run number: 1 to 10
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 35 = (End Pressure Calibration)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Force Differential Pressure Input Commands
Start differential pressure input calibration by forcing either the recent differential pressure input or a manual forced value. The flow computer will use the forced value during the calibration process.
Write the information required for the request.
Location
48690
48691
Data
Type Description
integer Meter run to calibrate: 1 to 10 float Forced manual value for differential pressure. This register is required only if calibration is done using a forced manual value. This register is not used if a forced recent value is used.
Realflo User and Reference Manual
May 19, 2011
784
TeleBUS Protocol Interface
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 36 = (Force Recent DP)
37 = (Force Manual DP)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Read the Calibration Data Registers for the Differential Pressure value being used by the flow computer.
Location
48690
48695
Data
Type
uint float
Description
Meter run = 1 to 10
Value for differential pressure while calibrating.
End Differential Pressure Calibration Command
End Differential Pressure input calibration by restoring the live input for differential pressure.
Write the information required for the request.
Location
48690
Data
Type Description
integer Meter run number: 1 to 10
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 38 = (End DP Calibration)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Realflo User and Reference Manual
May 19, 2011
785
TeleBUS Protocol Interface
Force Turbine Counts Commands
Start turbine input calibration by forcing either the recent turbine counts or a manual forced value. The flow computer will use the forced value during the calibration process.
Write the information required for the request.
Location
48690
48693
Data
Type Description
integer Meter run to calibrate: 1 to 10 ulong Forced manual value for turbine counts. This register is required only if calibration is done using a forced manual value. This register is not used if a forced recent value is used.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 75 = (Force Recent Turbine
Counts)
76 = (Force Manual Turbine
Counts)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Read the Calibration Data Registers for the Differential Pressure value being used by the flow computer.
Location
48690
48697
Data
Type
uint ulong
Description
Meter run = 1 to 10
Value for turbine counts while calibrating.
End Turbine Counts Calibration Command
End Differential Pressure input calibration by restoring the live input for differential pressure.
Write the information required for the request.
Location
48690
Data
Type Description
integer Meter run number: 1 to 10
Write the command and read the Command Register until it is cleared.
Location
Data
Type Description
Realflo User and Reference Manual
May 19, 2011
786
TeleBUS Protocol Interface
49500
49501
49502
49503 uint uint uint uint
Command: 77 = (End Turbine Counts Calibration)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Force Mass Flow Rate Calibration Commands
Start Mass Flow Rate calibration by forcing either the current Mass Flow
Rate or a manual forced value. The flow computer will use the forced value during the calibration process.
Write the information required for the request.
Location
48690
48693
Data
Type Description
integer Meter run to calibrate: 1 to 10 ulong Forced manual value for Mass Flow Rate. This register is required only if calibration is done using a forced manual value. This register is not used if a forced recent value is used.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 93 = (Force Current Mass Flow
Rate)
94 = (Force Manual Mass Flow
Rate)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Read the Calibration Data Registers for the Mass Flow Rate being used by the flow computer.
Location
48690
48697
Data
Type
uint ulong
Description
Meter run = 1 to 10
Value for mass flow rate while calibrating.
Realflo User and Reference Manual
May 19, 2011
787
TeleBUS Protocol Interface
End Mass Flow Rate Calibration Command
End Mass Flow Rate calibration by restoring the live input for differential pressure.
Write the information required for the request.
Location
48690
Data
Type Description
integer Meter run number: 1 to 10
Write the command and read the Command Register until it is cleared.
Location
Data
Type Description
49500
49501
49502
49503 uint uint uint uint
Command:95 = (End Mass Flow Rate Calibration)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Force Inputs Registers
The flow calculations continue to execute while sensors are being forced to either the recent value or a fixed value.
Force Inputs Registers
The Force Inputs registers hold the forced value for the inputs being forced.
These registers are used when the force commands are sent to the flow computer.
Actual
Register
48690
48691
Data
Type Description
uint float
Meter run = 1 to 10
Forced temperature, static pressure or differential pressure. ulong Forced change in pulse counts 48693
The Force Inputs Data registers hold the live measured values from the input being forced. Data in these registers is updated while the inputs are forced.
Actual
Register
48695
48697
Data
Type Description
float Temperature, static pressure or differential pressure during forcing. ulong Change in pulse counts during forcing (AGA-7 only).
Realflo User and Reference Manual
May 19, 2011
788
TeleBUS Protocol Interface
Force Current Temperature Command
The force current temperature command forces the temperature input to the current value. The flow computer uses the forced value when the input is forced.
Write the information required for the request.
Location
48690
48691
Data
Type Description
integer Meter run to calibrate: 1 to 10 float Forced fixed value for temperature. This register is required only if forcing is done using a forced fixed value. This register is not used if a forced current value is used.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 78 = (Force Current Temperature)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Read the Calibration Data Registers for the Temperature value being used by the flow computer.
Location
48690
48695
Data
Type
uint float
Description
Meter run = 1 to 10
Value for temperature while forcing.
Force Fixed Temperature Command
The force fixed temperature command forces the temperature input to a user entered fixed value. The flow computer uses the forced value when the input is forced.
Write the information required for the request.
Location
48690
48691
Data
Type Description
integer Meter run to calibrate: 1 to 10 float Forced fixed value for temperature. This register is required only if forcing is done using a forced fixed value. This register is not used if a forced current value is used.
Write the command and read the Command Register until it is cleared.
Realflo User and Reference Manual
May 19, 2011
789
TeleBUS Protocol Interface
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 79 = (Force Fixed Temperature)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Read the Calibration Data Registers for the Temperature value being used by the flow computer.
Location
48690
48691
Data
Type
uint float
Description
Meter run = 1 to 10
Value for temperature while forcing.
Restore Live Temperature Command
This command restores the live input for temperature.
Write the information required for the request.
Location
48690
Data
Type Description
integer Meter run number: 1 to 10
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 80 = (Restore Live Temperature Input)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Force Current Static Pressure Input Command
The force current static pressure command forces the static pressure input to the current value. The flow computer uses the forced value when the input is forced.
Write the information required for the request.
Realflo User and Reference Manual
May 19, 2011
790
TeleBUS Protocol Interface
Location
48690
48691
Data
Type Description
integer Meter run to calibrate: 1 to 10 float Forced fixed value for static pressure. This register is required only if forcing is done using a forced fixed value. This register is not used if a forced current value is used.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command:
Pressure)
81 = (Force Current Static
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Read the Calibration Data Registers for the Static Pressure value being used by the flow computer.
Location
48690
48695
Data
Type
uint float
Description
Meter run = 1 to 10
Value for static pressure while forcing.
Force Fixed Static Pressure Input Command
The force fixed static pressure command forces the static pressure input to a user entered fixed value. The flow computer uses the forced value when the input is forced.
Write the information required for the request.
Location
48690
48691
Data
Type Description
integer Meter run to calibrate: 1 to 10 float Forced fixed value for static pressure. This register is required only if forcing is done using a forced fixed value. This register is not used if a forced current value is used.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
Data
Type
Uint
Uint
Description
Command: 82 = (Force Fixed Static
Pressure)
Meter run = 1 to 10
Realflo User and Reference Manual
May 19, 2011
791
TeleBUS Protocol Interface
49502
49503
Uint
Uint
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
Uint
Uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Read the Calibration Data Registers for the Static Pressure value being used by the flow computer.
Location
48690
48695
Data
Type
Uint float
Description
Meter run = 1 to 10
Value for static pressure while forcing.
Restore Live Static Pressure Command
This command restores the live input for Static Pressure input.
Write the information required for the request.
Location
48690
Data
Type Description
integer Meter run number: 1 to 10
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 83 = (Restore Live Static Pressure)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Force Current Differential Pressure Input Command
The force current differential pressure command forces the differential pressure input to the current value. The flow computer uses the forced value when the input is forced.
Write the information required for the request.
Location
48690
Data
Type Description
integer Meter run to calibrate: 1 to 10
Realflo User and Reference Manual
May 19, 2011
792
TeleBUS Protocol Interface
48691 float Forced fixed value for differential pressure. This register is required only if forcing is done using a forced manual value. This register is not used if a forced current value is used.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 84 = (Force Current DP)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Read the Current Forced Data Registers for the Differential Pressure value being used by the flow computer.
Location
48690
48695
Data
Type
uint float
Description
Meter run = 1 to 10
Value for differential pressure while forcing.
Force Fixed Differential Pressure Input Command
The force fixed differential pressure command forces the differential pressure input to a user entered fixed value. The flow computer uses the forced value when the input is forced.
Write the information required for the request.
Location
48690
48691
Data
Type Description
integer Meter run to calibrate: 1 to 10
Float Forced fixed value for differential pressure. This register is required only if forcing is done using a forced manual value. This register is not used if a forced current value is used.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
Uint
Uint
Uint
Uint
Description
Command: 85 = (Force Fixed DP)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Data
Realflo User and Reference Manual
May 19, 2011
793
TeleBUS Protocol Interface
Location
49505
49506
Type
Uint
Uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Read the Calibration Data Registers for the Differential Pressure value being used by the flow computer.
Location
48690
48695
Data
Type
Uint
Float
Description
Meter run = 1 to 10
Value for differential pressure while forcing.
Restore Live Differential Pressure Input Command
This command restores the live input for Differential Pressure input.
Write the information required for the request.
Location
48690
Data
Type Description
integer Meter run number: 1 to 10
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 86 = (Restore Live DP Input)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Echo command or error from Flow Calculation
Specific to error. Meter run number if the command was successful.
Force Current Turbine Pulse Rate Command
The force current turbine pulse rate command forces the turbine pulse rate input to the current value. The flow computer uses the forced value when the input is forced.
Write the information required for the request.
Location
48690
48693
Data
Type Description
integer Meter run to calibrate: 1 to 10 ulong Forced fixed value for turbine pulses. This register is required only if forcing is done using a forced manual value. This register is not used if a forced current value is used.
Realflo User and Reference Manual
May 19, 2011
794
TeleBUS Protocol Interface
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 87 = (Force Current Turbine
Pulse Rate)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Specific to error. Meter run number if the command was successful.
Read the Calibration Data Registers for the Differential Pressure value being used by the flow computer.
Location
48690
48697
Data
Type
uint ulong
Description
Meter run = 1 to 10
Value for turbine counts while forcing.
Force Fixed Turbine Pulse Rate Command
The force current turbine pulse rate command forces the turbine pulse rate input to the user selected value. The flow computer uses the forced value when the input is forced.
Write the information required for the request.
Location
48690
48693
Data
Type Description
integer Meter run to calibrate: 1 to 10 ulong Forced fixed value for turbine pulses. This register is required only if forcing is done using a forced manual value. This register is not used if a forced current value is used.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 88 = (Force Fixed Turbine Pulse
Rate)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
Data
Type
uint
Description
Realflo User and Reference Manual
May 19, 2011
795
TeleBUS Protocol Interface
49506 uint Specific to error. Meter run number if the command was successful.
Read the Calibration Data Registers for the Differential Pressure value being used by the flow computer.
Location
48690
48697
Data
Type
uint ulong
Description
Meter run = 1 to 10
Value for turbine counts while forcing.
Restore Live Turbine Pulse Rate Command
This command restores the live input for the turbine pulse rate.
Write the information required for the request.
Location
48690
Data
Type Description
integer Meter run number: 1 to 10
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 89 = (Restore Live Turbine Pulse
Rate)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Specific to error. Meter run number if the command was successful.
Force Current Mass Flow Rate Command
The force current mass flow rate command forces the mass flow rate input to the current value. The flow computer uses the forced value when the input is forced.
Write the information required for the request.
Location
48690
48691
Data
Type Description
integer Meter run to calibrate: 1 to 10 ulong Forced fixed value for mass flow rate. This register is required only if forcing is done using a forced manual value. This register is not used if a forced current value is used.
Write the command and read the Command Register until it is cleared.
Location
Data
Type Description
Realflo User and Reference Manual
May 19, 2011
796
TeleBUS Protocol Interface
49500
49501
49502
49503 uint uint uint uint
Command: 90 = (Force Current Mass Flow
Rate)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Specific to error. Meter run number if the command was successful.
Read the Calibration Data Registers for the Mass Flow Rate value being used by the flow computer.
Location
48690
48697
Data
Type
uint ulong
Description
Meter run = 1 to 10
Value for Mass Flow Rate while forcing.
Force Fixed Mass Flow Rate Command
The force current mass flow rate command forces the mass flow rate input to the user selected value. The flow computer uses the forced value when the input is forced.
Write the information required for the request.
Location
48690
48693
Data
Type Description
integer Meter run to calibrate: 1 to 10 ulong Forced fixed value for mass flow rate. This register is required only if forcing is done using a forced manual value. This register is not used if a forced current value is used.
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 91 = (Force Fixed Mass Flow
Rate)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Specific to error. Meter run number if the command was successful.
Realflo User and Reference Manual
May 19, 2011
797
TeleBUS Protocol Interface
Read the Calibration Data Registers for the Differential Pressure value being used by the flow computer.
Location
48690
48697
Data
Type
uint ulong
Description
Meter run = 1 to 10
Value for Mass Flow Rate while forcing.
Restore Live Mass Flow Rate Command
This command restores the live input for the mass flow rate.
Write the information required for the request.
Location
48690
Data
Type Description
integer Meter run number: 1 to 10
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 92 = (Restore Live Mass Flow Rate)
Meter run = 1 to 10
User number
PIN
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type
uint uint
Description
Specific to error. Meter run number if the command was successful.
Event and Alarm Log Data
The flow computer stores up to 700 events and 300 alarms in the Alarm and
Event logs. This data is made available for retrieval and viewing on the basis of data for maximum of 10 events or alarms at a time.
The same Command Registers and Data Registers are used to read the event and alarm logs. Only the commands used to read the events differ.
If the events in the log are not acknowledged and the event log fills, the oldest events are lost and the lost event counter is incremented. Events are numbered sequentially from 1 to 700, with automatic rollover allowing for verification that events have been duly recorded when reviewing event history. The flow computer will not allow the execution of a command that would cause the event log to fill, so this should not occur.
If the alarms in the log are not acknowledged and the alarm log fills, the oldest alarms are lost and the lost alarm counter is incremented. Alarms are numbered sequentially from 1 to 300, with automatic rollover allowing for verification that alarms have been duly recorded when reviewing alarm history.
Alarm and event numbers are independent. Therefore it is possible to have an alarm and an event with the same number.
Realflo User and Reference Manual
May 19, 2011
798
TeleBUS Protocol Interface
Event and Alarm Log Data Registers
Actual
Register
48530
48531
48532
48533
Data
Type
uint uint uint uint
Description
Meter run number: 1 to 10
First event to display 1
– 700 or,
First alarm to display 1 - 300
No of events or alarms to load in display registers:
1
– 10
Number of events or alarms to delete starting at oldest:
Alarms 1
– 300
Events 1
– 700
Log Query Registers
The Header Registers describe the alarm and event data in the Data Set
Register groups.
Actual
Register
48535
48536
48537
48538
48539
Data
Type
uint uint uint uint uint
Log Header Registers
Description
Meter run: 1 to 10
Number of events or alarms shown
First event or alarm number shown
Number of events or alarms in the log
Number of events or alarms lost
A total of 10 sets of event or Alarm Data Display Registers are provided.
Each event or alarm consists of 11 registers.
Actual
Register
48540
48541
48542
48543
48545
48547
48549
Data
Type
uint uint uint float float float float
Description
Event ID
Sequential event (1 to 700) or alarm (1 to 300) number.
User number
Date of event or alarm (days since January 1,
1970)
Time of event or alarm (seconds since 00:00:00)
New data associated with the event or alarm, if any
Previous data associated with the event or alarm, if any
Log Data Set 1 Registers
Actual Register Data Type
48551 to 48561 See above
48562 to 48572 See above
48573 to 48583 See above
48584 to 48594 See above
48595 to 48605 See above
48606 to 48616 See above
48617 to 48627 See above
48628 to 48638 See above
48639 to 48649 See above
Description
Event or alarm log display set 2
Event or alarm log display set 3
Event or alarm log display set 4
Event or alarm log display set 5
Event or alarm log display set 6
Event or alarm log display set 7
Event or alarm log display set 8
Event or alarm log display set 9
Event or alarm log display set 10
Realflo User and Reference Manual
May 19, 2011
799
TeleBUS Protocol Interface
Log Data Sets 2 through 10 Registers
Get Number of New Events Command
To query the number of new events in the log execute the Get Number of
New Events command.
Write the information required for the request.
Location
48530
Data
Type Description
uint Meter run number: 1 to 10
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type Description
uint Command: 50 (Get Number Of New Events) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type Description
uint
Echo command or error from Flow Calculation
uint Specific to error. The run number if the command was successful.
Read the Data Registers.
Location
48535
48538
48539
Data
Type Description
uint Meter run = 1 to 10 uint Number of new events in the log uint The number of events that were lost because the queue was full.
Get Requested New Events Command
To query specific new event data for loading into the Display Registers, the meter run number, the number of the first new event to display and the number of new events need to be placed in the Event Query Registers before executing the Get Requested New Events command.
Write the information required for the request.
Location
48530
48531
48532
Data
Type Description
uint Meter run number: 1 to 10 uint First new event to display: 1
– 700 uint Number of new events to load in display registers: 1
– 10
Write the command and read the Command Register until it is cleared.
Location
Data
Type Description
Realflo User and Reference Manual
May 19, 2011
800
TeleBUS Protocol Interface
49500
49501
49502
49503 uint Command: 51 (Get Requested New Events) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type Description
uint
Echo command or error from Flow Calculation
uint Specific to error. The run number if the command was successful.
Read the Data Registers to determine which parts of the log are available.
Location
48535
48536
48537
48538
48539
Data
Type Description
uint Meter run = 1 to 10 uint Number of new events shown uint First new event number shown uint Number of new events in the event log uint Number of new events lost
Read the events.
Location Data Type
48540 to 48548 Event
Structure
48549 to 48629 Event
Structures
Description
First new event in the group.
The rest of the new events in the group.
Get Number of All Events Command
To query the total number of events in the log, execute the Get Number of
All Events command.
Write the information required for the request.
Location
48530
Data
Type Description
uint Meter run number: 1 to 10
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type Description
uint Command: 55 (Get Number Of All Events) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type Description
uint
Echo command or error from Flow Calculation
uint Specific to error. The run number if the command
Realflo User and Reference Manual
May 19, 2011
801
TeleBUS Protocol Interface was successful.
Read the Data Registers.
Location
48535
48538
48539
Data
Type
uint uint uint
Description
Meter run = 1 to 10
Number of events in the log
The number of events that were lost because the queue was full.
Get Requested All Events Command
To query specific event data for loading into the Display Registers, the meter run number, the number of the first event to display and the number of events need to be placed in the Event Query Registers before executing the Get Requested All Events command.
Write the information required for the request.
Location
48530
48531
48532
Data
Type Description
uint Meter run number: 1 to 10 uint First event to display: 1
– 700 uint Number of events to load in display registers: 1
– 10
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type Description
uint Command: 56 (Get Requested All Events) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type Description
uint
Echo command or error from Flow Calculation
uint Specific to error. The run number if the command was successful.
Read the Data Registers to determine which parts of the log are available.
Location
48535
48536
48537
48538
48539
Data
Type Description
uint Meter run = 1 to 10 uint Number of events shown uint Oldest event number shown uint Number of events in the event log uint Number of events lost
Read the events.
Location Data Type
48540 to 48548 Event
Structure
Description
First event in the group.
Realflo User and Reference Manual
May 19, 2011
802
48549 to 48629 Event
Structures
TeleBUS Protocol Interface
The rest of the events in the group.
Get Recent Events Command
To query the recent event data execute the Get Recent Events command.
The „first event to display‟ register is ignored when this command is used.
Command 50, Get Number of New Events, needs to first be run immediately before each instance of this command.
Write the information required for the request.
Location
48530
48532
Data
Type Description
uint Meter run number: 1 to 10 uint No of events/alarms to load in display registers: 1
–
10
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type
uint uint uint uint
Description
Command: 52 (Get Recent Events)
Meter run = 1 to 10
User number
PIN for user
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type Description
uint
Echo command or error from Flow Calculation
uint Specific to error. The run number if the command was successful.
Read the Data Registers to determine which parts of the log are available.
Location
48535
48536
48537
48538
48539
Read the events.
Data
Type Description
uint Meter run = 1 to 10 uint Number of events/alarms shown uint First event/alarm number shown uint Number of events/alarms in the log uint Number of events/alarms lost
Location Data Type
48540 to 48548 Event
Structure
48549 to 48629 Event
Structures
Description
First event in the group.
The rest of the events in the group.
Acknowledge Events Command
To acknowledge the oldest events in the log the number of events to
Acknowledge Register needs to be specified before executing the
Realflo User and Reference Manual
May 19, 2011
803
TeleBUS Protocol Interface
Acknowledge Events command. If there were any lost events then a Lost
Events event is generated and stored in the log.
Write the information required for the request.
Location
48530
48533
Data
Type Description
uint Meter run number: 1 to 10 uint Number of events to acknowledge starting at oldest:
1
– 700
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type Description
uint Command: 53 (Acknowledge Events) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type Description
uint
Echo command or error from Flow Calculation
uint Specific to error. The run number if the command was successful.
Get Number of New Alarms Command
To query the number of new alarms in the alarm log execute the Get
Number of New Alarms command.
Write the information required for the request.
Location
48530
Data
Type Description
uint Meter run number: 1 to 10
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type Description
uint Command: 60 (Get Number Of New Alarms) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type Description
uint
Echo command or error from Flow Calculation
uint Specific to error. The run number if the command was successful.
Read the Data Registers.
Realflo User and Reference Manual
May 19, 2011
804
Location
48535
48538
48539
TeleBUS Protocol Interface
Data
Type Description
uint Meter run = 1 to 10 uint Number of new alarms in the log uint The number of new alarms that were lost because the queue was full.
Get Requested New Alarms Command
To query specific alarm data for loading into the Display Registers, the meter run number, the number of the first new alarm to display and the number of new alarms need to be placed in the Alarm Query Registers before executing the Get Requested New Alarms command.
Write the information required for the request.
Location
48530
48531
48532
Data
Type Description
uint Meter run number: 1 to 10 uint First new alarm to display: 1
– 300 uint Number of new alarms to load in display registers: 1
– 10
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type Description
uint Command: 61 (Get Requested New Alarms) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type Description
uint
Echo command or error from Flow Calculation
uint Specific to error. The run number if the command was successful.
Read the Data Registers to determine which parts of the log are available.
Location
48535
48536
48537
48538
48539
Data
Type Description
uint Meter run = 1 to 10 uint Number of new alarms shown uint First alarm number shown uint Number of alarms in the log uint Number of alarms lost
Read the alarms.
Location Data Type
48540 to 48548 Event
Structure
48549 to 48629 Event
Structures
Description
First new alarm in the request.
The rest of the new alarms in the request.
Realflo User and Reference Manual
May 19, 2011
805
TeleBUS Protocol Interface
Get Number of All Alarms Command
To query the total number of alarms in the alarm log, execute the Get
Number of All Alarms command.
Write the information required for the request.
Location
48530
Data
Type Description
uint Meter run number: 1 to 10
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type Description
uint Command: 64 (Get Number Of All Alarms) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type Description
uint
Echo command or error from Flow Calculation
uint Specific to error. The run number if the command was successful.
Read the Data Registers.
Location
48535
48538
48539
Data
Type Description
uint Meter run = 1 to 10 uint Number of alarms in the log uint The number of alarms that were lost because the queue was full.
Get Requested All Alarms Command
To query specific alarm data for loading into the Display Registers, the meter run number, the number of the first alarm to display and the number of alarms need to be placed in the Alarm Query registers before executing the Get Requested All Alarms command.
Write the information required for the request.
Location
48530
48531
48532
Data
Type Description
uint Meter run number: 1 to 10 uint First new alarm to display: 1
– 300 uint Number of new alarms to load in display registers: 1
– 10
Write the command and read the Command Register until it is cleared.
Location
49500
49501
Data
Type
uint uint
Description
Command: 65 (Get Requested All Alarms)
Meter run = 1 to 10
Realflo User and Reference Manual
May 19, 2011
806
TeleBUS Protocol Interface
49502
49503 uint uint
User number
PIN for user
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type Description
uint
Echo command or error from Flow Calculation
uint Specific to error. The run number if the command was successful.
Read the Data Registers to determine which parts of the log are available.
Location
48535
48536
48537
48538
48539
Data
Type Description
uint Meter run = 1 to 10 uint Number of alarms shown uint First number shown uint Number of alarms in the log uint Number of alarms lost
Read the alarms.
Location Data Type
48540 to 48548 Event
Structure
48549 to 48629 Event
Structures
Description
First new alarm in the request.
The rest of the new alarms in the request.
Get Recent Alarms Command
To query the recent alarm data execute the Get Recent Alarms command.
The first alarm to Display Register is ignored when this command is used.
Write the information required for the request.
Location
48530
48532
Data
Type Description
uint Meter run number: 1 to 10 uint No of events/alarms to load in Display Registers: 1
– 10
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type Description
uint Command: 62 (Get Recent Alarms) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type Description
uint
Echo command or error from Flow Calculation
uint Specific to error. The run number if the command
Realflo User and Reference Manual
May 19, 2011
807
TeleBUS Protocol Interface was successful.
Read the Data Registers to determine which parts of the log are available.
Location
48535
48536
48537
48538
48539
Data
Type
uint uint uint uint uint
Read the alarms.
Description
Meter run = 1 to 10
Number of alarms shown
First alarm number shown
Number of alarms in the log
Number of alarms lost
Location Data Type
48540 to 48548 Event
Structure
48549 to 48629 Event
Structures
Description
First alarm in the group.
The rest of the alarms in the group.
Acknowledge Alarms Command
To acknowledge the oldest alarms in the log the number of alarms,
Acknowledge Register needs to be specified before executing the
Acknowledge Alarms command. If there were any lost alarms then a Lost
Alarms alarm is generated and stored in the log.
Write the information required for the request.
Location
48530
48533
Data
Type Description
uint Meter run number: 1 to 10 uint Number of alarms to acknowledge starting at oldest:
1
– 300
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type Description
uint Command: 63 (Acknowledge Alarms) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type Description
uint
Echo command or error from Flow Calculation
uint Specific to error. The run number if the command was successful.
Log User Defined Events
Additional events, defined by the user, may be recorded in the event log.
Executing the Log User Event command (command 54) will store the event and values defined in the following table.
Realflo User and Reference Manual
May 19, 2011
808
TeleBUS Protocol Interface
Actual
Register
48680
48681
48683
Data
Type
uint float float
Log Event Registers
Description
Event ID to be recorded (19000 to 19999)
Value to be recorded as the previous value
Value to be recorded as the new value
The event is stored in the event log for the meter that is defined in the
Command Registers.
The event is time stamped by the flow computer when it is recorded.
The event ID needs to be in the range 19000 to 19999. An event ID out of this range will result in the command not working and an event being logged indicating an out of range event ID was specified. This feature keeps users from faking real events.
The previous value and new value are recorded in the event log. The user defines the use of these values.
Log User Event Command
Additional events, defined by the user, may be recorded in the event log.
Executing the Log User Event command will store the event and values.
Write the information required for the request.
Location
48680
48681
48683
Data
Type Description
uint Event ID to be recorded (19000 to 19999) float Value to be recorded as the previous value float Value to be recorded as the new value
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
49503
Data
Type Description
uint Command: 54 (Log User Event) uint Meter run = 1 to 10 uint User number uint PIN for user
Read the Reply Registers to determine whether the action was performed.
Location
49505
49506
Data
Type Description
uint
Echo command or error from Flow Calculation
uint Specific to error. The run number if the command was successful.
Hourly History Data
There are a total of 30 periods of hourly History Data Registers. Each period is nominally an hour long, but may be shorter. Each period consists of 26 registers. The registers for the first (recent) period of history are shown in the Hourly History Data - Period 1 Registers table. The registers for hours
2 through 30 are shown in the Hourly History Data - Periods 2 to 30
Registers table.
Realflo User and Reference Manual
May 19, 2011
809
TeleBUS Protocol Interface
Hourly History Query and Data Registers
The units code field indicates the units in use at the time the log entry was made.
Actual
Register
48704
48706
48708
48710
48712
48714
48716
48718
48720
48722
48724
48726
48728
Data
Type
float float float float float float float float float float float float float
Description
Date at the end of the period (days since Jan 1,
1970)
Time at the end of the period (seconds since
00:00:00)
Duration of flow in the period in seconds
Flow volume at base conditions
Flow mass at base conditions
Flow energy at base conditions
Flow extension (AGA-3 1990 only)
Flow product (AGA-3 1985 only)
Uncorrected flow volume (AGA-7 only)
Average temperature
Average static pressure
Average differential pressure
(AGA-3 only)
Average number of rotations per second (AGA-7 only)
Average real relative gas density
Units code = input units code + (contract units code
* 32)
The units code field indicates the units in use at the time the log entry was made. The codes for the input units and contract units are listed below. Both are combined in a single floating point value to save space in the log.
Units
US1
US2
US3
IP
Units Code
0
1
2
3
Metric1
Metric2
Metric3
SI
US4
US5
US6
9
10
US7 11
US8 12
4
5
6
7
8
Hourly History Data - Period 1 Registers
Actual Register Data Type
48730 to 48755
48756 to 48781
48782 to 48807
48808 to 48833
48834 to 48859 see above see above see above see above see above
Description
2 nd
most recent period
3 rd
most recent period
4 th
most recent period
5
6 th th
most recent period
most recent period
Realflo User and Reference Manual
May 19, 2011
810
TeleBUS Protocol Interface
Actual Register
48860 to 48885
Data Type
see above
48886 to 48911 see above
48912 to 48937 see above
48938 to 48963 see above
48964 to 48989 see above
48990 to 49015 see above
49016 to 49041 see above
49042 to 49067 see above
49068 to 49093 see above
49094 to 49119 see above
49120 to 49145 see above
49146 to 49171 see above
49172 to 49197 see above
49198 to 49223 see above
49224 to 49249 see above
49250 to 49275 see above
49276 to 49301 see above
49302 to 49327 see above
49328 to 49353 see above
49354 to 49379 see above
49380 to 49405 see above
49406 to 49431 see above
49432 to 49457 see above
49458 to 49483 see above
Description
7 th
most recent period
8
9 th th
10
most recent period
most recent period th
most recent period
11
12 th th
most recent period
most recent period
13 th
most recent period
14
15 th th
most recent period
most recent period
16 th
most recent period
17
18 th th
most recent period
most recent period
19
20 th th
most recent period
most recent period
21 st
most recent period
22 nd
most recent period
23 rd
most recent period
24
25
26 th th th
most recent period
most recent period
most recent period
27
28 th th
most recent period
most recent period
29 th
most recent period
30 th
most recent period
Hourly History Data - Periods 2 to 30 Registers
Get Hourly History Command
The hourly history is comprised of 30 days worth of data that is written into a block of registers one-day at a time when the flow computer is queried.
The meter and day are written starting at location 48702. The data is made up of 780 registers starting at 48704. The internal arrangement is 30-hour segments by 26 registers.
In order to specify which day of data is to be loaded into the Display
Registers, the meter run number and day requested need to be placed in the Query registers prior to executing the Get Hourly History command
(11).
Write the day request:
Actual
Register
48700
48701
Data
Type
uint uint
Description
Meter run = 1 to 10
Day to query: 0 for today, 1 to 35 for previous days
Write the command and read the Command Register until it is cleared.
Location
49500
49501
49502
Data
Type Description
uint Command: 11 (Get Hourly History) uint Meter run = 1 to 10 uint User number
Realflo User and Reference Manual
May 19, 2011
811
TeleBUS Protocol Interface
Location
49503
Data
Type Description
uint PIN for user
Read the Reply Registers to determine whether the data is available.
Location
49505
49506
Data
Type Description
uint
Echo command or error from Flow Calculation
uint Specific to error. Meter run if the command was successful.
Read the Data Register to determine which day is available.
Actual
Register
48702
48703
Data
Type
uint uint
Description
Meter run = 1 to 10
Day to query: 0 for today, 1 to 35 for previous days
Read the Data Registers.
Location Data Type
48704 to 48728 Hourly History
Log
48730 to 49483 Hourly History
Log
Description
Most recent hour totals are displayed.
The rest of the hours in the day are displayed.
Program Information Registers
The Program Information Registers describe the flow computer program in the flow computer
Actual
Register
48525
48526
Data
Type
uint uint
Description
Firmware version
The value of register 48525 divided by 100 is the version information, for example a value of 147 indicates major version 1, minor version 47
Controller type
The Controller type value is stored in the lower 8bits of the register.
0 = unknown type
2 = Micro16
5 = SCADAPack
6 = SCADAPack Light
7 = SCADAPack Plus
8 = Boot Loader
9 = SCADAPack 32P
10 = SCADAPack 32
11 = Boot Loader 32
12 = SCADAPack LP
13 = SCADAPack 100 (small memory)
14 = SCADAPack 4202
15 = SCADAPack 4102
16 = SCADAPack 4012 Absolute
Realflo User and Reference Manual
May 19, 2011
812
TeleBUS Protocol Interface
Actual
Register
48527
48528
48529
Data
Type
uint uint uint
Description
17 = SCADAPack 4012 Gauge
18 = SCADAPack 4022 Absolute
19 = SCADAPack 4022 Gauge
20 = SCADAPack 4032
21 = SCADAPack 4052
22 = SCADAPack 4062
23 = SCADAPack Boot Loader
24 = IMV25-M
25 = SCADAPack 100 (large memory)
26 = SCADAPack 4202 DS
27 = SCADAPack 350
28 = Neptune Boot Loader
29 = SCADAPack 4203 DR
30 = SCADAPack 4203 DS
31 = SCADAPack 4203 Boot Loader
32 = SolarPack 410
33 = SCADAPack 330
34 = SCADAPack 334
35 = Pump Controller
36 = SCADAPack 314
255 = 4000 with unsupported sensor
Gas Flow Application Version
Gas Flow Application Build Number
Number of flow runs available (not the number currently in use).
Program Information Registers
Realflo User and Reference Manual
May 19, 2011
813
TeleBUS Protocol Interface
Flow Computer Events and Alarms
This section contains tables of the event and alarm codes that are created by the flow computer.
Up to 700 events and 300 alarms are stored in the event log by the flow computation routines. This event log is made available for retrieval and viewing using the Event Log Data and Query registers. Refer to the event log documentation for further information on the Event Log.
Global Events and Alarms
The gas flow computation engine creates these events and alarms.
Number Description
10001
10002
10003
10004
10005
10006
10007
10008
10009
10010
10011
10012
10013
10014
10015
10016
10017
10018
10019
10020
10021
10022
10023
10024
10025
10026
10027
10028
10029
10030
10031
10032
10033
10034
10035
10036
10037
Power On - Cold Boot
Power On
– Warm Boot
Lost Events
Recovered from Input Error
Set Input: Units Type
Set Input: Flow Calculation Type
Event
Set Input: Compressibility Calculation
Type
Set Input: Temperature Register
Set Input: Temperature Input at Zero
Scale
√
√
Set Input: Temperature Input at Full
√
Scale
Set Input: Temperature at Zero Scale
Set Input: Temperature at Full Scale
√
√
Set Input: Pressure Register
√
Set Input: Pressure Input at Zero Scale
√
Set Input: Pressure Input at Full Scale
Set Input: Pressure at Zero Scale
Set Input: Pressure at Full Scale
Set Input: DP Register
Set Input: DP Input at Zero Scale
√
√
√
√
√
Set Input: DP Input at Full Scale
Set Input: DP at Zero Scale
Set Input: DP at Full Scale
Set Contract: Units Type
Set Contract: Base Temperature
Set Contract: Base Pressure
Set Contract: Atmospheric Pressure
√
Set Input: Static Pressure Tap Location
√
Set Contract: Contract Hour
√
Change Execution State
Set RTC Year
√
√
√
√
√
√
√
√
Set RTC Month
Set RTC Day
Set RTC Hour
Set RTC Minute
Set RTC Second
√
√
Set Input: Temperature Low Level Cutoff
√
Set Input: Temperature Low Level
√
√
√
√
√
√
√
√
√
Alarm
√
√
Realflo User and Reference Manual
May 19, 2011
814
Number Description
10038
10039
10040
10041
10042
10043
10044
10046
10047
10048
10049
10050
10051
10052
10053
10054
10055
10056
10057
10058
10059
10060
10061
10062
10063
10064
10065
10066
10067
10068
10069
10071
10072
10073
10074
10075
10076
10077
10078
TeleBUS Protocol Interface
Event
Hysteresis
Set Input: Temperature High Level Cutoff
√
Set Input: Temperature High Level
√
Hysteresis
Set Input: Pressure Low Level Cutoff
Set Input: Pressure Low Level
Hysteresis
√
√
Set Input: Pressure High Level Cutoff
Set Input: Pressure High Level
√
√
Hysteresis
Set Input: Save Low/High Flow Events
√
Invalid User Event
√
Starting Calibration: Forced temperature
√ input
Ending Calibration: Restored live temperature input
√
Starting Calibration: Forced SP input
Ending Calibration: Restored live SP input
√
√
Starting Calibration: Forced DP input
Ending Calibration: Restored live DP input
√
√
Starting Calibration: Forced pulse count rate
√
Ending Calibration: Restored live pulse count rate
End Plate Change: Restored live
√
Set User Number
Set User Security Level
Set Input: Temperature Register Type
Set Input: Pressure Register Type
Set Input: DP Register Type
Set Input: Temperature Input at Zero
Scale
Set Input: Temperature Input at Full
Start Plate Change: Forced temperature input
√
Scale
Set Input: Pressure Input at Zero Scale
√
Set Input: Pressure Input at Full Scale
√
Set Input: DP Input at Zero Scale
Set Input: DP Input at Full Scale
√
√
Set Input: Pulse Counter Register
√
Set Input: Pulse Counter Register Type
√
Set Active Runs
√
Lost Alarms
Firmware Version
√
√
Application Version
Set Flow Computer ID
Contract In Err Action
Set runID
√
√
√
√
Power Off
√
√
√
√
√
√
√
√
Alarm
√
Realflo User and Reference Manual
May 19, 2011
815
10095
10096
10097
10099
10100
10101
10102
10103
10104
10105
10106
10107
10108
10109
10084
10085
10086
10087
10088
10089
10090
10091
10092
10093
10094
Number Description
10079
10080
10081
10082
10083
10110
10111
Event
temperature input
Start Plate Change: Forced static
√ pressure input
End Plate Change: Restored live static pressure input
√
Start Plate Change: Forced differential pressure input
√
End Plate Change: Restored live differential pressure input
√
Set Input: Altitude and Latitude
√
Compensation
Set Input: Altitude
Set Input: Latitude
Forced temperature input
Restored live temperature input
Forced static pressure input
√
√
Restored live static pressure input
Forced differential pressure input
√
√
Restored live differential pressure input
√
√
√
√
Forced pulse count rate
Restored live pulse count rate
Set Contract: Wet Gas Meter Factor
Set pulse input counter register
Set pulse input K factor
Set pulse input units
Set Contract: Input averaging
Set input: sensor fail action
Set input: default temperature
Set input: default static pressure
Set input: default differential pressure
Set gas quality source (Pemex only)
Set Input: Flow Direction Control
Set Input: Flow Direction Register
Forced mass flow input
Restored live mass flow input
Starting Calibration: Forced mass flow
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√ rate input
Ending Calibration: Restored live mass
√ flow rate input
Set Input: Mass Flow Rate Register Type
√
Global Alarms and Events Description
TeleBUS Protocol Interface
Alarm
AGA-3 (1985) Events and Alarms
These events and alarms are specific to the AGA-3 (1985) calculation.
Number Description
10201
10202
10203
Failed To Create AGA-3 (1985) Data
Structure
Created AGA-3 (1985) with Execution
Stopped
Created AGA-3 (1985) with Execution
Running
Event
√
Alarm
√
√
Realflo User and Reference Manual
May 19, 2011
816
TeleBUS Protocol Interface
Number Description
10204
Event
Destroyed AGA-3 (1985) Data Structure
√
10205
10206
10207
10208
10209
10210
10211
10212
10213
10214
10215
10216
10217
10218
Recovered from AGA-3 (1985) error
Set AGA-3 (1985): Input Units Type
Set AGA-3 (1985): Orifice Material
Set AGA-3 (1985): Pipe Material
Set AGA-3 (1985): Static Pressure Tap
Location
Set AGA-3 (1985): Orifice Diameter
Set AGA-3 (1985): Orifice Measurement
Reference Temperature
√
√
Set AGA-3 (1985): Pipe Diameter
Set AGA-3 (1985): Pipe Diameter
Measurement Reference Temperature
Set AGA-3 (1985): Isentropic Exponent
√
Set AGA-3 (1985): Viscosity
√
Set AGA-3 (1985): Base Temperature
√
Set AGA-3 (1985): Base Pressure
Set AGA-3 (1985): Atmospheric
√
√
Pressure
√
√
√
√
√
√
10219
10220
10221
10222
10223
Failed To Set AGA-3 (1985)
Configuration
Set AGA-3 (1985): Contract Units Type
√
Set AGA-3 (1985): Temperature
√ deadband
Set AGA-3 (1985): Static Pressure deadband
√
Set AGA-3 (1985): Differential Pressure deadband
√
AGA-3 (1985) Alarms and Events Description
Alarm
√
√
AGA-3 (1992) Events and Alarms
These events and alarms are specific to the AGA-3 (1992) calculation.
Number Description
10301
10302
10303
10304
10305
10306
10307
10308
10309
10310
10311
10312
10313
Failed To Create AGA-3 (1992) Data
Structure
Event
Created AGA-3 (1992) with Execution
Stopped
Created AGA-3 (1992) with Execution
√
Running
Destroyed AGA-3 (1992) Data Structure
√
Restored from AGA-3 (1992) error
Set AGA-3 (1992): Input Units Type
Set AGA-3 (1992): Orifice Material
Set AGA-3 (1992): Pipe Material
Set AGA-3 (1992): Static Pressure Tap
√
√
√
√
√
Location
Set AGA-3 (1992): Orifice Diameter
Set AGA-3 (1992): Orifice reference temperature
√
√
Set AGA-3 (1992): Pipe Diameter
Set AGA-3 (1992): Pipe Diameter
√
√
Alarm
√
√
Realflo User and Reference Manual
May 19, 2011
817
Number Description
10314
10315
10316
10317
10318
10319
10320
10321
10322
10323
10324
10325
10326
10327
AGA-3 (1992) Alarms and Events Description
TeleBUS Protocol Interface
Event
Measurement Temperature
Set AGA-3 (1992): Isentropic Exponent
√
Set AGA-3 (1992): Viscosity
√
Set AGA-3 (1992): Base Temperature
√
Set AGA-3 (1992): Base Pressure
Set AGA-3 (1992): Atmospheric
√
√
Pressure
Failed To Set AGA-3 (1992)
√
Configuration
Set Input: DP Low Level Cutoff
√
Set Input: DP Low Level Hysteresis
Set Input: DP High Level Cutoff
Set Input: DP High Level Hysteresis
Set AGA-3 (1992): Contract Units Type
√
Set AGA-3 (1992): Temperature
√
√
√
√
Deadband
Set AGA-3 (1992): Static Pressure
Deadband
√
Set AGA-3 (1992): Differential Pressure
Deadband
√
Alarm
AGA-7 Events and Alarms
These events and alarms are specific to the AGA-7 calculation.
10701
10702
10703
10704
10705
10706
10707
10708
10709
10710
10711
10712
10713
10714
10715
10716
Number Description Event
Failed To Create AGA-7 Data Structure
Created AGA-7 with Execution Stopped
√
Created AGA-7 with Execution Running
Destroyed AGA-7 Data Structure
√
Recovered from AGA-7 error
Set AGA-7: Input Units Type
Set AGA-7: K Factor
Set AGA-7: M Factor
Set AGA-7: Atmospheric Pressure
Set AGA-7: Base Pressure
√
√
Set AGA-7: Base Temperature
Failed To Set AGA-7 Configuration
√
√
Set Input: Turbine Low Flow Pulse Limit
√
√
√
√
Set Input: Turbine Low Flow Detect Time
√
Set AGA-7: Contract Units Type
√
Set ABA-7: Volume Option
√
AGA-7 Alarms and Events Description
AGA-11 Events and Alarms
These events and alarms are specific to the AGA-11 calculation.
Number Description
11101
11102
11103
Event
Failed To Create AGA-11 Data Structure
Created AGA-11 with Execution Stopped
√
Created AGA-11 with Execution Running
Alarm
√
√
Alarm
√
√
√
Realflo User and Reference Manual
May 19, 2011
818
Number Description
11104
11105
11106
11107
11108
11109
11110
14001
14002
14003
14004
14005
14006
14007
14008
Destroy AGA-11 Data Structure
Recovered from AGA-11 error
TeleBUS Protocol Interface
Change in AGA-11 units configuration
Change in AGA-11 contract units config
Change in AGA-11 base temperature
Coriolis Meter: Not Polled
Coriolis Meter: protocol error in response message.
The first byte returned from the meter was not the byte order.
The byte order returned from the meter was not known.
The units code returned from the meter was not known.
The meter has an unexpected configuration
.
Event
√
Change in AGA-11 base pressure
Failed To Set AGA-11 Configuration
Failed To Set Coriolis Meter
Set Coriolis Meter: Meter Address
Set Coriolis Meter: Meter Port
Set Coriolis Meter: Meter Timeout
Coriolis Meter: Lost Communication
Coriolis Meter: Communication Restored
√
√
√
√
√
√
√
Alarm
√
√
√
√
√
√
√
V-Cone Events and Alarms
These events and alarms are specific to the V-Cone calculation.
Number Description
12201
12202
12203
12204
12205
Failed To Create V-Cone Date Structure
Created V-Cone with Execution Stopped
Event
√
Created V-Cone with Execution Running
Destroyed V-Cone Data Structure
√
Recovered from V-Cone Error
12206
12207
12208
12209
12210
12211
12212
12213
12214
12215
12216
12217
12218
12219
12220
12221
12222
Failed To Set V-Cone Configuration
/* reserved */
Set V-Cone Input Units Type
Set V-Cone Contract Units Type
Set V-Cone Cone Material
Set V-Cone Pipe Material
Set V-Cone Cone Diameter
Set V-Cone Inside Pipe Diameter
√
Set V-Cone Pipe reference temperature
√
√
√
√
√
√
Set V-Cone Isentropic Exponent
Set V-Cone Viscosity
Set V-Cone Base Temperature
Set V-Cone Base Pressure
Set V-Cone Atmospheric Pressure
Set Table Point 1 Reynolds Number
Set Table Point 2 Reynolds Number
Set Table Point 3 Reynolds Number
√
√
√
√
√
√
√
√
√
√
Alarm
√
√
Realflo User and Reference Manual
May 19, 2011
819
Number
12223
12224
12225
12226
12227
12228
12229
12230
12231
12232
12233
12234
12235
12236
12237
12238
12239
12240
12241
12242
12243
Description
Set Table Point 4 Reynolds Number
Set Table Point 5 Reynolds Number
Set Table Point 6 Reynolds Number
Set Table Point 7 Reynolds Number
Set Table Point 8 Reynolds Number
Set Table Point 9 Reynolds Number
Set Table Point 10 Reynolds Number
Set Table Point 1 Flow Coefficient
Set Table Point 2 Flow Coefficient
Set Table Point 3 Flow Coefficient
Set Table Point 4 Flow Coefficient
Set Table Point 5 Flow Coefficient
Set Table Point 6 Flow Coefficient
Set Table Point 7 Flow Coefficient
Set Table Point 8 Flow Coefficient
Set Table Point 9 Flow Coefficient
Set Table Point 10 Flow Coefficient
Set Adiabatic Expansion Factor Method
√
Set Wet Gas Correction Factor Method
√
Set Density of liquid at flow conditions
Set Mass flow rate of liquid at flow
√
√
√
√
√
√
√
√
√
√
√ conditions
Event
√
√
√
√
√
√
√
√
V-Cone Alarms and Events Description
TeleBUS Protocol Interface
Alarm
AGA-8 Events and Alarms
These events and alarms are specific to the AGA-8 calculation.
Number Description
10801
10802
10804
10805
10806
10807
10808
10809
10810
10811
10812
10813
10814
10815
10816
10817
10818
10819
10820
10821
10822
10823
Failed To Create AGA-8 Data Structure
Created AGA-8 with Execution Stopped
Event
√
Created AGA-8 with Execution Running
Destroyed AGA-8 Data Structure
√
Set AGA-8 Gas: Change Gas Fractions
√
Set AGA-8 Gas: Methane (CH4)
√
Set AGA-8 Gas: Nitrogen
√
Set AGA-8 Gas: Carbon Dioxide (CO2)
√
Set AGA-8 Gas: Ethane (C2H6)
√
Set AGA-8 Gas: Propane (C3H8)
Set AGA-8 Gas: Water
√
√
Set AGA-8 Gas: Hydrogen Sulfide (H2S)
√
Set AGA-8 Gas: Hydrogen
√
Set AGA-8 Gas: Carbon Monoxide (CO)
√
Set AGA-8 Gas: Oxygen
Set AGA-8 Gas: iButane
Set AGA-8 Gas: nButane
√
√
√
Set AGA-8 Gas: iPentane
Set AGA-8 Gas: nPentane
Set AGA-8 Gas: nHexane
Set AGA-8 Gas: nHeptane
Set AGA-8 Gas: nOctane
Set AGA-8 Gas: nNonane
√
√
√
√
√
√
Alarm
√
√
Realflo User and Reference Manual
May 19, 2011
820
Number
10824
10825
10826
10827
10828
10829
10830
10831
10832
10833
10834
10835
Description
Set AGA-8 Gas: nDecane
Set AGA-8 Gas: Helium
Set AGA-8 Gas: Argon
Set AGA-8 Gas: Failed To Set
Failed To Set AGA-8 Configuration
Set AGA-8: Input Units Type
Set AGA-8: Base Temperature
Set AGA-8: Base Pressure
Set AGA-8: Atmospheric Pressure
√
√
Set AGA-8: Static Pressure Tap Location
√
Set AGA-8: Contract Units Type
√
√
√
Event
√
√
√
√
10836
10837
10838
10839
10840
10841
10842
10843
Clear Compressibility Error
Set AGA-8: Gas Composition Logging
Set AGA-8 Gas: Use combined Hexane
+ components
Set AGA-8 Hexane + Ratio for n-hexane
√
Set AGA-8 Hexane + Ratio for n-heptane
√
Set AGA-8 Hexane + Ratio for n-octane
√
Set AGA-8 Hexane + Ratio for n-nonane
√
Set AGA-8 Hexane + Ratio for n-decane
√
Set AGA-8: Set Laboratory Real Relative
√
√
√
10844
Density
Set AGA-8: Set Laboratory Forces
Heating Value
AGA-8 Alarms and Events Description
TeleBUS Protocol Interface
Alarm
√
√
√
NX-19 Events and Alarms
These events and alarms are specific to the NX-19 calculation.
Number
11901
11902
Description
Failed to Create NX-19 Data Structure
Events Alarm s
√
Created NX-19 with Execution Stopped
√
11903
11904
Created NX-19 with Execution Running
Destroyed NX-19 Data Structure
√
√
11905
√
11906
11907
11908
11909
11910
11911
11912
11913
11914
Restored from NX-19 error
Set NX-19: Calculation Method
Set NX-19: Specific Gravity
Set NX-19: Gas: Carbon Dioxide
Set NX-19: Gas: Methane
Set NX-19: Gas: Nitrogen
Set NX-19: Heating Value
√
Set NX-19: Static Pressure Tap Location
√
Set NX-19: Base Pressure
√
Set NX-19: Base Temperature
√
√
√
√
√
√
11915
11916
Failed to set NX-19 Gas Components
Failed to set NX-19 Contract
√
√
11917
11918
11919
Configuration
Set NX-19: Contract Units Type
Clear Compressibility Error
Set NX-19: Gas Composition Logging
√
√
√
Realflo User and Reference Manual
May 19, 2011
821
TeleBUS Protocol Interface
NX-19 Alarms and Events Description
Sensor Events and Alarms
These events and alarms are specific to the sensor.
Number Description
13100
13101
13102
13103
13104
13105
13106
13107
13108
13109
13110
13111
Event
Set Sensor 1: Polling Status
Set Sensor 1: Serial Port
Set Sensor 1: Address of Transmitter
Set Sensor 1: Timeout
Set Sensor 1: Manufacturer Code
Set Sensor 1: Turnaround Delay Time
√
Set Sensor 1: Differential Pressure Units
√
Set Sensor 1: Static Pressure Units
√
√
√
√
√
√
Set Sensor 1: Temperature Units
Set Sensor 1: Serial Number
Set Sensor 1: Tag
Set Sensor 1: Differential Pressure
√
√
√
√
13112
13113
13114
13115
13116
13117
13118
Damping
Set Sensor 1: Differential Pressure
Upper Operating Limit
Set Sensor 1: Static Pressure Lower
√
Set Sensor 1: Differential Pressure
√
Lower Operating Limit
Set Sensor 1: Static Pressure Damping
√
Set Sensor 1: Static Pressure Upper
√
Operating Limit
√
Operating Limit
Set Sensor 1: Temperature Damping
Set Sensor 1: Temperature Upper
√
√
Operating Limit
13119 Set Sensor 1: Temperature Lower
Operating Limit
√
13120
13121
Sensor 1: Lost Communication
Sensor 1: Transmitter Configuration
Incorrect
√
√
13122 Sensor 1: Temperature Sensor Out of
Range
√
13123 Sensor 1: Static Pressure Sensor Out of
Range
√
13124 Sensor 1: Differential Pressure Sensor
Out of Range
√
13125 Sensor 1: Not Polled
13126
13127
13128
13129
Set Sensor 1: Type Code
Set Sensor 1: IP Address
Set Sensor 1: IP Protocol
Sensor 1: Temperature Sensor has bad data
√
√
√
13130
13131
13132
Sensor 1: Static Pressure Sensor has bad data
Sensor 1: Differential Pressure Sensor has bad data
Set Sensor 1: Set Pressure Type and
√
√
√
√
Alarm
Realflo User and Reference Manual
May 19, 2011
822
Number Description
13133
13134
13135
13136
13137
13138
13139
13140
13141
13142
13150
13151
13152
13153
13154
13155
13156
13157
13158
13159
13160
13161
13162
13163
13164
13165
13166
13167
13168
13169
13170
13171
13172
13173
13174
13175
TeleBUS Protocol Interface
Event
Atmospheric Pressure
Sensor 1: Communication Restored
Sensor 1: Alarms Restored
Sensor 1: Sensors Offline
Sensor 1: RTD Disconnected
Sensor 1: Temperature Sensor Above
Range
Sensor 1: Static Sensor Above Range
Sensor 1: Differential Pressure Above
Range
Sensor 1: Temperature Sensor Below
Range
Sensor 1: Static Sensor Below Range
Sensor 1: Differential Pressure Below
Range
Set Sensor 2: Polling Status
Set Sensor 2: Serial Port
Set Sensor 2: Address of transmitter
Set Sensor 2: Timeout
Set Sensor 2: Manufacturer Code
Set Sensor 2: Turnaround Delay Time
Set Sensor 2: Differential Pressure Units
√
Set Sensor 2: Static Pressure Units
√
Set Sensor 2: Temperature Units
√
√
√
√
√
√
√
Set Sensor 2: Serial Number
Set Sensor 2: Tag
Set Sensor 2: Differential Pressure
√
√
√
Damping
Set Sensor 2: Differential Pressure
Upper Operating Limit
√
Set Sensor 2: Differential Pressure
√
Lower Operating Limit
Set Sensor 2: Static Pressure Damping
√
Set Sensor 2: Static Pressure Upper
√
Operating Limit
Set Sensor 2: Static Pressure Lower
√
Operating Limit
Set Sensor 2: Temperature Damping
Set Sensor 2: Temperature Upper
Operating Limit
Set Sensor 2: Temperature Lower
Operating Limit
Sensor 2: Lost Communication
√
√
√
Sensor 2: Transmitter Configuration
Incorrect
Sensor 2: Temperature Sensor Out of
Range
Sensor 2: Static Pressure Sensor Out of
Range
Sensor 2: Differential Pressure Sensor
Out of Range
Sensor 2: Not Polled
Alarm
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
Realflo User and Reference Manual
May 19, 2011
823
TeleBUS Protocol Interface
Number
13176
13177
13178
13179
13180
13181
13182
13183
13184
13185
13186
13187
13188
13189
13190
13191
13192
13200
13201
13202
13203
13204
13205
13206
13207
13208
13209
13210
13211
13212
13213
13214
13215
13216
13217
13218
13219
Description
Set Sensor 2: Type Code
Set Sensor 2: IP Address
Set Sensor 2: IP Protocol
Sensor 2: Temperature Sensor has bad data
Sensor 2: Static Pressure Sensor has bad data
Sensor 2: Differential Pressure Sensor has bad data
Set Sensor 2: Set Pressure Type and
Atmospheric Pressure
Sensor 2: Communication Restored
Sensor 2: Alarms Restored
Sensor 2: Sensors Offline
√
Sensor 2: RTD Disconnected
Sensor 2: Temperature Sensor Above
Range
Sensor 2: Static Sensor Above Range
Sensor 2: Differential Pressure Above
Range
Sensor 2: Temperature Sensor Below
Range
Sensor 2: Static Sensor Below Range
Sensor 2: Differential Pressure Below
Range
Set Sensor 3: Polling Status
Set Sensor 3: Serial Port
Set Sensor 3: Address of Transmitter
Set Sensor 3: Timeout
Set Sensor 3: Manufacturer Code
Set Sensor 3: Turnaround Delay Time
Set Sensor 3: Differential Pressure units
√
Set Sensor 3: Static Pressure units
√
√
√
√
√
√
√
Set Sensor 3: Temperature units
Set Sensor 3: Serial number
Set Sensor 3: Tag
Set Sensor 3: Differential Pressure
√
√
√
√
Damping
Set Sensor 3: Differential Pressure
√
Upper Operating Limit
Set Sensor 3: Differential Pressure
√
Lower Operating Limit
Set Sensor 3: Static Pressure Damping
√
Set Sensor 3: Static Pressure Upper
√
Operating Limit
Set Sensor 3: Static Pressure Lower
√
Operating Limit
Set Sensor 3: Temperature Damping
Set Sensor 3: Temperature Upper
√
√
Operating Limit
Set Sensor 3: Temperature Lower
Operating Limit
√
Event
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
Alarm
√
Realflo User and Reference Manual
May 19, 2011
824
Number Description
13220
13221
13222
13223
13224
13225
13226
13227
13228
13229
13230
13231
13232
13233
13234
13235
13236
13237
13238
13239
13240
13241
13242
13250
13251
13252
13253
13254
13255
13256
13257
13258
13259
13260
13261
13262
13263
Sensor 3: Lost Communication
TeleBUS Protocol Interface
Sensor 3: Transmitter Configuration
Incorrect
Sensor 3: Temperature Sensor Out of
Range
Sensor 3: Static Pressure Sensor Out of
Range
Sensor 3: Differential Pressure Sensor
Out of Range
Sensor 3: Not Polled
Set Sensor 3: Type Code
Set Sensor 3: IP Address
Set Sensor 3: IP Protocol
Sensor 3: Temperature Sensor has bad data
Sensor 3: Static Pressure Sensor has bad data
Event
Sensor 3: Differential Pressure Sensor has bad data
Set Sensor 3: Set Pressure Type and
Atmospheric Pressure
Sensor 3: Communication Restored
Sensor 3: Alarms Restored
Sensor 3: Sensors Offline
Sensor 3: RTD Disconnected
Sensor 3: Temperature Sensor Above
Range
Sensor 3: Static Sensor Above Range
Sensor 3: Differential Pressure Above
Range
Sensor 3: Temperature Sensor Below
Range
Sensor 3: Static Sensor Below Range
Sensor 3: Differential Pressure Below
Range
Set Sensor 4: Polling Status
Set Sensor 4: Serial Port
Set Sensor 4: Address of Transmitter
Set Sensor 4: Timeout
Set Sensor 4: Manufacturer Code
Set Sensor 4: Turnaround Delay Time
√
Set Sensor 4: Differential Pressure Units
√
Set Sensor 4: Static Pressure Units
√
√
√
√
√
√
Set Sensor 4: Temperature Units
Set Sensor 4: Serial Number
Set Sensor 4: Tag
Set Sensor 4: Differential Pressure
√
√
√
√
Damping
Set Sensor 4: Differential Pressure
√
Upper Operating Limit
Set Sensor 4: Differential Pressure
Lower Operating Limit
√
√
√
√
Alarm
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
Realflo User and Reference Manual
May 19, 2011
825
TeleBUS Protocol Interface
Number Description
13264
13265
Event
Set Sensor 4: Static Pressure Damping
√
Set Sensor 4: Static Pressure Upper
√
Operating Limit
13266 Set Sensor 4: Static Pressure Lower
Operating Limit
√
13267
13268
Set Sensor 4: Temperature Damping
Set Sensor 4: Temperature Upper
Operating Limit
√
√
13269 Set Sensor 4: Temperature Lower
Operating Limit
√
13270 Sensor 4: Lost Communication
13271
13272
Sensor 4: Transmitter Configuration
Incorrect
Sensor 4: Temperature Sensor Out of
Range
13273
13274
13275
13276
13277
13278
13279
13280
Sensor 4: Static Pressure Sensor Out of
Range
Sensor 4: Differential Pressure Sensor
Out of Range
Sensor 4: Not Polled
Set Sensor 4: Type Code
Set Sensor 4: IP Address
Set Sensor 4: IP Protocol
Sensor 4: Temperature Sensor has bad data
Sensor 4: Static Pressure Sensor has bad data
√
√
√
13281
13282
13283
13284
13285
13286
13287
13288
13289
13290
13291
13292
13300
13301
13302
13303
13304
13305
13306
Sensor 4: Differential Pressure Sensor has bad data
Set Sensor 4: Set Pressure Type and
Atmospheric Pressure
Sensor 4: Communication Restored
Sensor 4: Alarms Restored
Sensor 4: Sensors Offline
Sensor 4: RTD Disconnected
Sensor 4: Temperature Sensor Above
Range
Sensor 4: Static Sensor Above Range
Sensor 4: Differential Pressure Above
Range
Sensor 4: Temperature Sensor Below
Range
√
Sensor 4: Static Sensor Below Range
Sensor 4: Differential Pressure Below
Range
Set Sensor 5: Polling Status
√
Set Sensor 5: Serial Port
Set Sensor 5: Address of Transmitter
Set Sensor 5: Timeout
Set Sensor 5: Manufacturer Code
Set Sensor 5: Turnaround Delay Time
√
√
Set Sensor 5: Differential Pressure Units
√
√
√
√
Alarm
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
Realflo User and Reference Manual
May 19, 2011
826
TeleBUS Protocol Interface
Number
13307
13308
13309
13310
13311
13312
13313
13314
13315
13316
13317
13318
Description
Set Sensor 5: Static Pressure Units
Set Sensor 5: Temperature Units
Set Sensor 5: Serial Number
Set Sensor 5: Tag
Set Sensor 5: Differential Pressure
Damping
Set Sensor 5: Differential Pressure
Upper Operating Limit
Set Sensor 5: Static Pressure Lower
√
Set Sensor 5: Differential Pressure
√
Lower Operating Limit
Set Sensor 5: Static Pressure Damping
√
Set Sensor 5: Static Pressure Upper
√
Operating Limit
√
Operating Limit
Set Sensor 5: Temperature Damping
Set Sensor 5: Temperature Upper
√
√
Operating Limit
Event
√
√
√
√
√
13319 Set Sensor 5: Temperature Lower
Operating Limit
√
13320
13321
Sensor 5: Lost Communication
Sensor 5: Transmitter Configuration
Incorrect
13322
13323
13324
Sensor 5: Temperature Sensor Out of
Range
Sensor 5: Static Pressure Sensor Out of
Range
Sensor 5: Differential Pressure Sensor
Out of Range
Sensor 5: Not Polled 13325
13326
13327
13328
13329
13330
13331
Set Sensor 5: Type Code
Set Sensor 5: IP Address
Set Sensor 5: IP Protocol
Sensor 5: Temperature Sensor has bad data
Sensor 5: Static Pressure Sensor has bad data
Sensor 5: Differential Pressure Sensor has bad data
√
√
√
13332
√
13333
13334
13335
Set Sensor 5: Set Pressure Type and
Atmospheric Pressure
Sensor 5: Communication Restored
Sensor 5: Alarms Restored
Sensor 5: Sensors Offline
13336
13337
13338
13339
13340
Sensor 5: RTD Disconnected
Sensor 5: Temperature Sensor Above
Range
Sensor 5: Static Sensor Above Range
Sensor 5: Differential Pressure Above
Range
Sensor 5: Temperature Sensor Below
Range
Alarm
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
Realflo User and Reference Manual
May 19, 2011
827
Number Description
13341
13342
13350
13351
13352
13353
13354
13355
13356
13357
13358
13359
13360
13361
13362
13363
13364
13365
13366
13367
13368
13369
13370
13371
13372
13373
13374
13375
13376
13377
13378
13379
13380
13381
13382
13383
TeleBUS Protocol Interface
Sensor 5: Static Sensor Below Range
Sensor 5: Differential Pressure Below
Event
Range
Set Sensor 6: Polling Status
Set Sensor 6: Serial Port
Set Sensor 6: Address of Transmitter
Set Sensor 6: Timeout
Set Sensor 6: Manufacturer Code
Set Sensor 6: Turnaround Delay Time
Set Sensor 6: Differential Pressure Units
√
Set Sensor 6: Static Pressure Units
√
Set Sensor 6: Temperature Units
√
√
√
√
√
√
√
Set Sensor 6: Serial Number
Set Sensor 6: Tag
Set Sensor 6: Differential Pressure
√
√
√
Damping
Set Sensor 6: Differential Pressure
Upper Operating Limit
Set Sensor 6: Temperature Damping
Set Sensor 6: Temperature Upper
Operating Limit
√
Set Sensor 6: Differential Pressure
√
Lower Operating Limit
Set Sensor 6: Static Pressure Damping
√
Set Sensor 6: Static Pressure Upper
√
Operating Limit
Set Sensor 6: Static Pressure Lower
Operating limit
√
√
√
Set Sensor 6: Temperature Lower
Operating Limit
√
Sensor 6: Lost Communication
Sensor 6: Transmitter Configuration
Incorrect
Sensor 6: Temperature Sensor Out of
Range
Sensor 6: Static Pressure Sensor Out of
Range
Sensor 6: Differential Pressure Sensor
Out of Range
Sensor 6: Not Polled
Set Sensor 6: Type Code
Set Sensor 6: IP Address
Set Sensor 6: IP Protocol
Sensor 6: Temperature Sensor has bad data
Sensor 6: Static Pressure Sensor has bad data
Sensor 6: Differential Pressure Sensor has bad data
Set Sensor 6: Set Pressure Type and
Atmospheric Pressure
Sensor 6: Communication Restored
√
√
√
√
Alarm
√
√
√
√
√
√
√
√
√
√
√
√
Realflo User and Reference Manual
May 19, 2011
828
Number Description
13384
13385
13386
13387
13388
13389
13390
13391
13392
13400
13401
13402
13403
13404
13405
13406
13407
13408
13409
13410
13411
13412
13413
13414
13415
13416
13417
13418
13419
13420
13421
13422
13423
13424
13425
13426
13427
Sensor 6: Alarms Restored
Sensor 6: Sensors Offline
Sensor 6: RTD Disconnected
TeleBUS Protocol Interface
Sensor 6: Temperature Sensor Above
Range
Event
Sensor 6: Static Sensor Above Range
Sensor 6: Differential Pressure Above
Range
Sensor 6: Temperature Sensor Below
Range
Sensor 6: Static Sensor Below Range
Sensor 6: Differential Pressure Below
Range
Set Sensor 7: Polling Status
Set Sensor 7: Serial Port
Set Sensor 7: Address of Transmitter
Set Sensor 7: Timeout
Set Sensor 7: Manufacturer Code
Set Sensor 7: Turnaround Delay Time
Set Sensor 7: Differential Pressure Units
√
Set Sensor 7: Static Pressure Units
√
√
√
√
√
√
√
Set Sensor 7: Temperature Units
Set Sensor 7: Serial Number
Set Sensor 7: Tag
Set Sensor 7: Differential Pressure
√
√
√
√
Damping
Set Sensor 7: Differential Pressure
Upper Operating Limit
Set Sensor 7: Static Pressure Lower
Operating Limit
√
Set Sensor 7: Differential Pressure
√
Lower Operating Limit
Set Sensor 7: Static Pressure Damping
√
Set Sensor 7: Static Pressure Upper
√
Operating Limit
√
Set Sensor 7: Temperature Damping
Set Sensor 7: Temperature Upper
Operating Limit
√
√
Set Sensor 7: Temperature Lower
Operating Limit
√
Sensor 7: Lost Communication
Sensor 7: Transmitter Configuration
Incorrect
Sensor 7: Temperature Sensor Out of
Range
Sensor 7: Static Pressure Sensor Out of
Range
Sensor 7: Differential Pressure Sensor
Out of Range
Sensor 7: Not Polled
Set Sensor 7: Type Code
Set Sensor 7: IP Address
√
√
Alarm
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
Realflo User and Reference Manual
May 19, 2011
829
Realflo User and Reference Manual
May 19, 2011
830
Number Description
13472
13473
13474
13475
13476
13477
13478
13479
13480
13481
13482
13483
13484
13485
13486
13487
13488
13489
13490
13491
13492
13500
13501
13502
13503
13504
13505
13506
13507
13508
13509
13510
13511
13512
13513
13514
13515
TeleBUS Protocol Interface
Event
Incorrect
Sensor 8: Temperature Sensor Out of
Range
Sensor 8: Static Pressure Sensor Out of
Range
Sensor 8: Differential Pressure Sensor
Out of Range
Sensor 8: Not Polled
Set Sensor 8: Type Code
Set Sensor 8: IP Address
Set Sensor 8: IP Protocol
Sensor 8: Temperature Sensor has bad data
Sensor 8: Static Pressure Sensor has bad data
Sensor 8: Differential Pressure Sensor has bad data
Set Sensor 8: Set Pressure Type and
Atmospheric Pressure
Sensor 8: Communication Restored
√
Sensor 8: Alarms Restored
Sensor 8: Sensors Offline
Sensor 8: RTD Disconnected
Sensor 8: Temperature Sensor Above
Range
Sensor 8: Static Sensor Above Range
Sensor 8: Differential Pressure Above
Range
Sensor 8: Temperature Sensor Below
Range
Sensor 8: Static Sensor Below Range
Sensor 8: Differential Pressure Below
Range
Set Sensor 9: Polling Status
√
Set Sensor 9: Serial Port
Set Sensor 9: Address of Transmitter
Set Sensor 9: Timeout
Set Sensor 9: Manufacturer Code
Set Sensor 9: Turnaround Delay Time
√
√
Set Sensor 9: Differential Pressure Units
√
√
√
√
Set Sensor 9: Static Pressure Units
Set Sensor 9: Temperature Units
Set Sensor 9: Serial Number
Set Sensor 9: Tag
Set Sensor 9: Differential Pressure
√
√
√
√
√
Damping
Set Sensor 9: Differential Pressure
Upper Operating Limit
√
Set Sensor 9: Differential Pressure
√
Lower Operating Limit
Set Sensor 9: Static Pressure Damping
√
Set Sensor 9: Static Pressure Upper
√
√
√
√
Alarm
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
Realflo User and Reference Manual
May 19, 2011
831
Number Description
13516
13517
13518
13519
13520
13521
13522
13523
13524
13525
13526
13527
13528
13529
13530
13531
13532
13533
13534
13535
13536
13537
13538
13539
13540
13541
13542
13550
13551
13552
13553
13554
13555
13556
13557
TeleBUS Protocol Interface
Event
Operating Limit
Set Sensor 9: Static Pressure Lower
Operating Limit
Set Sensor 9: Temperature Damping
Set Sensor 9: Temperature Upper
Operating Limit
Set Sensor 9: Temperature Lower
Operating Limit
Sensor 9: Lost Communication
Sensor 9: Transmitter Configuration
Incorrect
Sensor 9: Temperature Sensor Out of
Range
Sensor 9: Static Pressure Sensor Out of
Range
√
√
√
√
Sensor 9: Differential Pressure Sensor
Out of Range
Sensor 9: Not Polled
Set Sensor 9: Type Code
Set Sensor 9: IP Address
Set Sensor 9: IP Protocol
Sensor 9: Temperature Sensor has bad data
Sensor 9: Static Pressure Sensor has bad data
Sensor 9: Differential Pressure Sensor has bad data
Set Sensor 9: Set Pressure Type and
Atmospheric Pressure
Sensor 9: Communication Restored
Sensor 9: Alarms Restored
Sensor 9: Sensors Offline
Sensor 9: RTD Disconnected
Sensor 9: Temperature Sensor Above
Range
Sensor 9: Static Sensor Above Range
√
Sensor 9: Differential Pressure Above
Range
Sensor 9: Temperature Sensor Below
Range
Sensor 9: Static Sensor Below Range
Sensor 9: Differential Pressure Below
Range
Set Sensor 10: Polling Status
Set Sensor 10: Serial Port
Set Sensor 10: Address of Transmitter
Set Sensor 10: Timeout
Set Sensor 10: Manufacturer Code
√
√
Set Sensor 10: Turnaround Delay Time
√
Set Sensor 10: Differential Pressure
√
√
√
√
Units
Set Sensor 10: Static Pressure Units
√
√
√
√
Alarm
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
Realflo User and Reference Manual
May 19, 2011
832
TeleBUS Protocol Interface
Number Description
13558
13559
13560
13561
13562
13563
13564
13565
13566
13567
13568
13569
Event
Set Sensor 10: Temperature Units
Set Sensor 10: Serial Number
Set Sensor 10: Tag
Set Sensor 10: Differential Pressure
Damping
Set Sensor 10: Differential Pressure
Upper Operating Limit
Set Sensor 10: Temperature Damping
Set Sensor 10: Temperature Upper
Operating Limit
√
Set Sensor 10: Differential Pressure
√
Lower Operating Limit
Set Sensor 10: Static Pressure Damping
√
Set Sensor 10: Static Pressure Upper
√
Operating Limit
Set Sensor 10: Static Pressure Lower
Operating Limit
√
√
√
Set Sensor 10: Temperature Lower
Operating Limit
√
√
√
√
√
13570 Sensor 10: Lost Communication
13571
13572
Sensor 10: Transmitter Configuration
Incorrect
Sensor 10: Temperature Sensor Out of
Range
13573
13574
13575
13576
13577
13578
13579
13580
Sensor 10: Static Pressure Sensor Out of Range
Sensor 10: Differential Pressure Sensor
Out of Range
Sensor 10: Not Polled
Set Sensor 10: Type Code
Set Sensor 10: IP Address
Set Sensor 10: IP Protocol
Sensor 10: Temperature Sensor has bad data
Sensor 10: Static Pressure Sensor has bad data
√
√
√
13581
13582
13583
13584
13585
13586
13587
13588
13589
13590
13591
Sensor 10: Differential Pressure Sensor has bad data
Set Sensor 10: Set Pressure Type and
Atmospheric Pressure
Sensor 10: Communication Restored
Sensor 10: Alarms Restored
Sensor 10: Sensors Offline
Sensor 10: RTD Disconnected
Sensor 10: Temperature Sensor Above
Range
Sensor 10: Static Sensor Above Range
Sensor 10: Differential Pressure Above
Range
Sensor 10: Temperature Sensor Below
Range
√
Sensor 10: Static Sensor Below Range
Alarm
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
Realflo User and Reference Manual
May 19, 2011
833
TeleBUS Protocol Interface
Number Description
13592 Sensor 10: Differential Pressure Below
Range
Event Alarm
√
A configuration change will usually cause a created CALC with Execution stopped, for example, 10202, created AGA-3 (1985), with execution stopped; or a Destroyed CALC, for example, 10204, Destroyed AGA-3
(1985 Data Structure), event to be logged as an event unless the meter was running before power was removed. In such cases, this change will be logged as an alarm when power is restored.
A configuration change where there is insufficient memory for the meter variables results in a Failed to Create CALC, for example, 10201 Failed to
Create AGA-3 (1985) Data Structure, to be logged as an event unless there is insufficient memory for the meter variables on power up. In such cases, this change is logged as an alarm.
Calibration and User Defined Alarms and Events
Realflo generates these events when performing calibration (not by the flow computer). User-defined events can also be created in the range 19000 to
19999. Refer to the Log User Event command for details.
Number Description
19001 Start Temperature Calibration
19016
19018
19019
19021
19022
19023
19024
19025
19026
19028
19029
19002
19003
19004
19005
19006
19007
19008
19009
19011
19012
19013
19014
19015
19031
19032
19033
19034
19039
Continue Temperature Calibration
As-Found Temperature
As-Left Temperature
Target Re-Zero Temperature
Target Temperature Span
Set Default Temperature
After Re-Zero Temperature
After Calibrate Temperature Span
Start Static Press Calibration
Continue Static Pressure Calibration
As-Found Static Pressure
As-Left Static Pressure
Target Re-Zero Static Pressure
Target Static Pressure Span
After Re-Zero Static Pressure
After Calibrate Static Pressure Span
Start Differential Pressure Calibration
Continue Differential Pressure Calibration
As-Found Differential Pressure
As-Left Differential Pressure
Target Re-Zero Differential Pressure
Target Differential Pressure Span
After Re-Zero Differential Pressure
After Calibrate Differential Pressure Span
Start Pulse Count Calibration
Continue Pulse Count Calibration
As-Found Pulse Count
As-Left Pulse Count
End Pulse Count Calibration
Realflo User and Reference Manual
May 19, 2011
834
TeleBUS Protocol Interface
Calibration and User Defined Alarms and Events Description
Realflo User and Reference Manual
May 19, 2011
835
TeleBUS Protocol Interface
Flow Computer Error Codes
This section contains tables of the error codes that are created by the flow computer.
Calculation Engine Errors
The flow calculation engine generates these errors.
Number Description
20001 Meter control structure not found
20002
20003
20004
20005
20006
Inputs have not been configured
Temperature input is below zero scale
Temperature input is above full scale
Static pressure input is below zero scale
Static pressure input is above full scale
20007
20008
20010
20011
20050
Differential pressure input is below zero scale
Differential pressure input is above full scale
Forced input register
Removed forced from input register
Restore from temperature input low alarm
20051
20052
20053
Restore from temperature input high alarm
Restore from static pressure input low alarm
Restore from static pressure input high alarm
20054
20055
20056
20057
Restore from differential pressure input low alarm
Restore from differential pressure input high alarm
Restore from low pulse input alarm
Restore from input alarm
Calculation Engine Errors Description
AGA-3 (1985) Calculation Errors
Number Description
20201
20202
20203
20204
20205
20206
20207
20208
20209
20210
AGA-3 (1985) - Input Units system is invalid
AGA-3 (1985) - Pipe diameter is too small
AGA-3 (1985) - Orifice diameter is too small
AGA-3 (1985) - Orifice diameter is larger than the pipe diameter
AGA-3 (1985) - Base pressure is zero or negative
AGA-3 (1985) - Base temperature is at or below absolute zero
AGA-3 (1985) - Relative density is zero or negative
AGA-3 (1985) - Supercompressibility is zero or negative
20211
20214
20221
20222
20223
20227
20228
AGA-3 (1985) - Viscosity is zero or negative
AGA-3 (1985) - Flowing temperature is at or below absolute zero
AGA-3 (1985) - Flow extension is zero or negative
AGA-3 (1985) - Invalid isentropic exponent
AGA-3 (1985) - Invalid pipe material
AGA-3 (1985) - Invalid orifice material
AGA-3 (1985) - Invalid static pressure tap location
AGA-3 (1985) - Differential pressure is zero or negative
AGA-3 (1985) - Configuration flag not set
Realflo User and Reference Manual
May 19, 2011
836
TeleBUS Protocol Interface
Number Description
20229
20230
20231
20234
AGA-3 (1985) - Ratios from AGA-8 or NX-19 were not available
AGA-3 (1985)
– Static Pressure Below Differential Pressure
AGA-3 (1985)
– Static Pressure Negative or Zero
AGA-3 (1985)
– Bad Calculation
AGA-3 (1985) Calculation Errors Description
AGA-3 (1992) Calculation Errors
These errors are generated by the AGA-3 calculation.
20311
20312
20313
20314
20315
20316
20317
20318
20319
20320
20321
20322
20323
20324
20325
Number Description
20301 AGA-3 (1992) - Input Units system is invalid
20302
20303
20304
20305
20306
AGA-3 (1992) - Pipe diameter is too small
AGA-3 (1992) - Orifice diameter is too small
AGA-3 (1992) - Orifice diameter is larger than the pipe diameter
AGA-3 (1992) - Base pressure is zero or negative
20307
20308
AGA-3 (1992) - Base temperature is at or below absolute zero
AGA-3 (1992) - Relative density is zero or negative
AGA-3 (1992) - Supercompressibility is zero or negative
20309
20310
20326
20327
20328
20329
20330
20331
20334
AGA-3 (1992) - Viscosity is zero or negative
AGA-3 (1992) - Flowing temperature is at or below absolute zero
AGA-3 (1992) - Flow extension is zero or negative
AGA-3 (1992) - Compressibility is negative at base conditions
AGA-3 (1992) - Compressibility is negative at flow conditions
AGA-3 (1992) - Invalid isentropic exponent
AGA-3 (1992) - Ratio of orifice to pipe diameter is small
AGA-3 (1992) - Ratio of orifice to pipe diameter is large
AGA-3 (1992) - Ratio of orifice to pipe diameter is too small
AGA-3 (1992) - Ratio of orifice to pipe diameter is too large
AGA-3 (1992) - Reynolds number is too small
AGA-3 (1992) - Reynolds number is too large
AGA-3 (1992) - Invalid pipe material
AGA-3 (1992) - Invalid orifice material
AGA-3 (1992) - Invalid static pressure tap location
AGA-3 (1992) - The discharge coefficient was not calculated
AGA-3 (1992) - Too many iterations to calculate the discharge coefficient
AGA-3 (1992) - The atmospheric pressure is invalid
AGA-3 (1992) - unused error code
AGA-3 (1992) - Configuration flag not set
AGA-3 (1992) - Ratios from AGA-8 or NX-19 were not available
AGA-3 (1992) - Static Pressure Below Differential Pressure
AGA-3 (1992) - Static Pressure Negative or Zero
AGA-3 (1992)
– Bad Calculation
AGA-3 (1992) Calculation Errors Description
Realflo User and Reference Manual
May 19, 2011
837
TeleBUS Protocol Interface
AGA-7 Calculation Errors
These errors are generated by the AGA-7 calculation.
20710
20711
20712
20713
20714
20715
20716
20717
20718
20719
20720
Number Description
20701
20702
AGA-7 - Failed to create
AGA-7 - Unused error code
20703
20704
20705
20706
20707
20708
20709
AGA-7 - Input Units system is invalid
AGA-7 - Base pressure is low
AGA-7 - Base temperature is at or below absolute zero
AGA-7 - K factor is negative or zero
AGA-7 - M factor is negative or zero
AGA-7 - Atmospheric pressure is negative
AGA-7 - Supercompressibility is zero or negative
AGA-7 - Compressibility is negative at base conditions
AGA-7 - Pulse count is negative
AGA-7 - Flow temperature is low
AGA-7 - Flow pressure is low
AGA-7 - Pulse count is low
AGA-7 - Configuration flag not set
AGA-7 - Ratios from AGA-8 or NX-19 are not available
AGA-7 - Input values are not available
AGA-7 - Contract Units system is invalid
AGA-7
– Volume Option is Invalid
AGA-7
– Bad Calculation
AGA-7 Calculation Errors Description
AGA-11 Calculation Errors
These errors are generated by the AGA-11 calculation.
Number Description
21101
21102
21103
21104
21105
21106
21107
21108
AGA-11 - Bad units
AGA-11 - Bad contract units
AGA-11 - Base Pressure negative or zero
AGA-11 - Base Temperature negative or zero
AGA-11 - Bad calculation
AGA-11 - Configuration flag not set
AGA-11 - Ratios from AGA-8 were not available
AGA-11
– Input not available
AGA-11 Calculation Errors Description
V-Cone Calculation Errors
These errors are generated by the V-Cone calculation.
Number Description
22201 V-Cone - Input Units system is invalid
22202
22203
22204
V-Cone - Contract units system is invalid
V-Cone - Invalid pipe material
V-Cone - Invalid cone material
22205
22206
22207
22208
V-Cone - Pipe diameter is too small
V-Cone - Cone diameter is too small
V-Cone - cone diameter is larger than the pipe diameter
V-Cone - Base pressure is zero or negative
Realflo User and Reference Manual
May 19, 2011
838
TeleBUS Protocol Interface
Number Description
22219
22220
22221
22222
22223
22224
22225
22226
22227
22209
22210
22211
22212
22213
22214
22215
22216
22217
22218
22228
22229
22230
22232
22233
V-Cone - Base temperature is zero or negative
V-Cone - Viscosity is zero or negative
V-Cone - Invalid isentropic exponent
V-Cone - The atmospheric pressure is invalid
V-Cone - Reynolds/coefficient table length is invalid
V-Cone - First Reynolds/coefficient point is invalid
V-Cone - A Reynolds/coefficient point is invalid
V-Cone - Reynolds number lower than previous point
V-Cone - Coefficient lower than previous point
V-Cone - Supercompressibility is zero or negative
V-Cone - Compressibility is negative at base conditions
V-Cone - Compressibility is negative at flow conditions
V-Cone - Flow temperature is at or below absolute zero
V-Cone - Configuration flag not set
V-Cone - Ratios from AGA-8 or NX-19 were not available
V-Cone - Input values were not available
V-Cone - Calculated Reynolds number is too small
V-Cone - Calculated Reynolds number is too large
V-Cone - Too many iterations for the Reynolds number to converge
V-Cone
– Static Pressure Below Differential Pressure
V-Cone
– Static Pressure Negative or Zero
V-Cone
– Bad Calculation
V-Cone
– Invalid Adiabatic Expansion Factor Setting.
Froude number invalid
– wet gas correction cannot be done.
V-Cone Calculation Errors Description
AGA-8 Calculation Errors
These errors are generated by the AGA-8 calculation.
Number Description
20801
20802
AGA-8 - Failed to create
AGA-8 - Input Units system is invalid
20803
20804
20805
20806
20807
AGA-8 - Bad gas component
AGA-8 - Components do not sum to 1.000
AGA-8 - Base temperature is out of range
AGA-8 - Heating-value temperature is out of range
AGA-8 - Base pressure is high
20808
20809
20810
20811
20812
20813
20814
20815
20816
20817
20818
20819
20820
AGA-8 - Invalid static pressure tap location
AGA-8 - Flow temperature is low
AGA-8 - Flow temperature is high
AGA-8 - Flow pressure is low
AGA-8 - Flow pressure is high
AGA-8 - Invalid calculation code
AGA-8 - Not configured
AGA-8 - Bracket exceed iterates
AGA-8 - Bracket negative derivative
AGA-8 - Not running
AGA-8 - Atmospheric pressure is invalid
AGA-8 - No gas components
AGA-8 - No inputs received
Realflo User and Reference Manual
May 19, 2011
839
TeleBUS Protocol Interface
Number Description
20821
20822
20823
20824
20825
20826
20827
AGA-8 - Contract Units system is invalid
AGA-8 - Bad log option
AGA-8 Bad Hexanes+ option
AGA-8 Bad Hexanes+ ratio
AGA-8 Hexanes+ ratios to not sum to 100
AGA-8
– Bad laboratory real relative density
AGA-8
– Bad laboratory heating value
AGA-8 Calculation Errors Description
NX-19 Calculation Errors
These errors are generated by the NX-19 calculation.
Number Description
21901 NX-19 - Failed to create
21902
21903
21904
21905
21906
NX-19 - Input Units system is invalid
NX-19 - Base temperature is out of range
NX-19 - Base pressure is high
NX-19 - Invalid static pressure tap location
NX-19 - Bad method
21907
21908
21909
21910
21911
21912
21913
21914
21915
21916
21917
21918
21919
21920
21921
NX-19 - Gravity is out of range
NX-19 - CO2 is out of range
NX-19 - Methane is out of range
NX-19 - Nitrogen is out of range
NX-19 - Gas fractions are out of range
NX-19 - Heating value temperature is out of range
NX-19 - Temperature is out of range
NX-19 - Flow pressure is low
NX-19 - Flow pressure is high
NX-19 - Configuration flag not set
NX-19 - Gas ratios were not available
NX-19 - Input values were not available
NX-19 - Not running
NX-19 - Contract Units system is invalid
NX-19
– Density Temperature High
NX-19 Errors Description
Flow Calculation Engine Command Errors
These errors are generated by commands executed by the flow calculation engine.
Number Description
30001 Invalid meter number
30002
30003
30004
30005
30006
30007
30008
30009
Invalid user number
Illegal meter number
Illegal user number
Undefined command
Unmatched meter number
Cannot change configuration while the calculations are running
Calculation units out of range
Illegal calculation type for flow calculation
Realflo User and Reference Manual
May 19, 2011
840
TeleBUS Protocol Interface
Number Description
30020
30023
30024
30025
30026
30027
30028
30029
30030
30031
30032
30033
30034
30010
30011
30012
30013
30014
30015
30016
30017
30018
30019
30035
30036
30037
30038
30039
30040
30041
30042
30043
30044
30045
30046
30047
30048
30049
30050
30051
30052
30053
30054
30055
30056
30057
30058
30059
30064
Illegal calculation type for compressibility calculation
Failed to set the contract configuration
Failed to change the gas fractions
Invalid register address
Negative value for input scale
Full scale input less than zero scale input
Contract hour is too high
Invalid data in a time register
First event position is zero or larger than queue size
Requested number of events is zero or too large
Did not find any event data for the passed parameters
Failed to flush the event log
NX-19 calculation is not configured
Day offset is too large userID does not exist
User is not authorized to perform this function.
Flow Computer is not in calibration mode
Forced temperature is out of valid range
Calibration temperature is out of valid range
The contract is not configured
Temperature level limit not within input range
Static pressure level limit not within input range
Temperature level hysteresis is invalid
Static pressure hysteresis is invalid
No temperature range remains between hysteresis limits
No static pressure range remains between hysteresis limits
Save input events selection is invalid
Invalid static pressure tap location
Atmospheric pressure is less than zero
Atmospheric pressure is too high
Forced static pressure is invalid
Forced differential pressure is invalid
Forced pulse count is invalid
The execution state is invalid
The execution state did not change, may not be configured
The event ID is not a valid user defined event ID
The register type is invalid
Attempted to set an invalid number of active runs.
Attempted to reduce the number of active runs when one still running.
Attempted to start a valid but inactive run.
Flow computer cannot execute the command because the event log is full. Read the event log then retry the operation.
The Alarm register position is not valid.
The Alarm register size is not valid.
The Alarm register data is not valid.
Failed to acknowledge alarms.
Attempted to set an invalid altitude.
Attempted to set an invalid latitude.
Attempted to set an invalid Wet Gas Meter Factor
Flow Computer cannot execute the command because the
Realflo User and Reference Manual
May 19, 2011
841
TeleBUS Protocol Interface
Number Description
30065
30066
30067
30068
30074
Measurement Canada lockout jumper is installed.
Illegal gas quality source type
Flow Direction Control setting is invalid
Flow Direction Register setting is invalid
Forced mass flow rate is invalid
On Indicates setting is invalid
Engine Commands Errors Description
MVT Command Errors
The following new error codes are defined.
Number Description
30101 Sensor search parameters invalid
30111
30112
30113
30114
30115
30116
30117
30118
30119
30120
30121
30122
30123
30124
30102
30103
30104
30105
30106
30107
30108
30109
30110
30125
30126
30127
30128
30129
30130
30131
30132
Sensor address invalid
Invalid sensor number
Sensor did not respond
Polling status is invalid
Serial port is invalid
Address of sensor is invalid
Timeout is invalid
Turnaround delay time is invalid
Differential pressure units is invalid
Static pressure units is invalid
Temperature units is invalid
Differential pressure damping is invalid
Differential pressure upper operating limit is invalid
Differential pressure lower operating limit is invalid
Static pressure damping is invalid
Static pressure upper operating limit is invalid
Static pressure lower operating limit is invalid
Temperature damping is invalid
Temperature upper operating limit is invalid
Temperature lower operating limit is invalid
Invalid sensor type
Sensor not enabled
Invalid register type
Sensor returned function exception
Sensor returned address exception
Sensor returned value exception
Bad manufacturer or type code for internal SCADAPack 4200 or 4300
Cannot write to device: bad manufacturer, type code or identifier
Display interval is invalid
A display custom item identifier is invalid
Sensor communication error
30133
30134
30135
30136
30137
Invalid protocol type
Atmospheric pressure offset is invalid
Custom display number is invalid
Custom display data type is invalid
Custom display description string is empty.
Realflo User and Reference Manual
May 19, 2011
842
TeleBUS Protocol Interface
Coriolis Meter Errors
Number Description
33001
33002
33003
33004
33005
Coriolis Meter - Address is invalid
Coriolis Meter - Port is invalid
Coriolis Meter - Timeout is invalid
Coriolis Meter - Device code invalid
Coriolis Meter - Adding Coriolis meter failed
SolarPack 410 Errors
Number Description
30138
30139
30140
Invalid pulse configuration
Invalid gas sampler output configuration
Invalid power management configuration
AGA-3 Command Errors
These errors are generated by commands executed by the AGA-3 calculation.
Number Description
30301
30302
AGA-3 is not configured
Failed to configure AGA-3
30303
30304
30305
Differential pressure level limit is invalid
Differential pressure level hysterisis is invalid
No differential pressure range remains between hysterisis limits
AGA-3 Command Errors Description
AGA-7 Command Errors
These errors are generated by commands executed by the AGA-7 calculation.
Number Description
30701 AGA-7 is not configured
30702
30703
30704
Failed to configure AGA-7
Low flow pulse limit is invalid
Low flow pulse duration is invalid
AGA-7 Command Errors Description
AGA-11 Command Errors
These errors are generated by commands executed by the AGA-11 calculation.
Number Description
31101
31102
AGA-11 - not configured for use
AGA-11 - Failed to configure AGA-11
V-Cone Command Errors Description
V-Cone Command Errors
These errors are generated by commands executed by the V-Cone calculation.
Realflo User and Reference Manual
May 19, 2011
843
TeleBUS Protocol Interface
Number Description
32201
32202
V-Cone is not configured
Failed to configure V-Cone
V-Cone Command Errors Description
AGA-8 Command Errors
These errors are generated by the executed by the AGA-8 calculation.
Number Description
30801 AGA-8 is not configured for use
30802 Failed to configure AGA-8
AGA-8 Command Errors Description
NX-19 Command Errors
These errors are generated by the executed by the NX-19 calculation.
Number Description
31901
31902
31903
NX-19 is not configured for use
Failed to configure NX-19 contract items
Failed to configure NX-19 gas components
NX-19 Command Errors Description
Flow Computer Commands
The following table is a complete list of commands used in the command
sequence configuration of the flow computer. Refer to the
section for information on using these commands.
20
21
22
23
30
31
32
34
Command
Number
15
16
17
18
19
1
3
6
8
9
11
12
13
35
Command Description
Get input configuration
Set input configuration
Set Real Time Clock
Set execution state
Adjust Real Time Clock
Get hourly history
Get daily history
Get contract configuration
Set contract configuration
Set number of runs
Set Flow Computer ID
Get Flow Computer ID
Set runID
Get runID
Set Long Run ID
Get Long Run ID
Set Enron Modbus Time Stamp
Start Temperature Calibration: Force current temperature
Start Temperature Calibration: Force fixed temperature
End Temperature Calibration
Start Static Pressure Calibration: Force current static pressure
Start Static Pressure Calibration: Force fixed static
Realflo User and Reference Manual
May 19, 2011
844
TeleBUS Protocol Interface
60
60
61
62
63
64
65
75
52
53
54
55
56
46
47
48
50
51
40
41
42
43
44
45
81
82
83
84
85
76
77
78
79
80
86
87
88
89
90
91
92
93
Command
Number
37
38
94
Command Description
pressure
End Static Pressure Calibration
Start Differential Pressure Calibration: Force current differential pressure
Start plate change: force current temperature
Start plate change: force fixed temperature
End plate change: temperature
Start plate change: force current static pressure
Start plate change: force fixed static pressure
End plate change: static pressure
Start plate change: force current differential pressure
Start plate change: force fixed differential pressure
End plate change: differential pressure
Get number of new events
Get requested new events
Get recent events
Acknowledge events
Log user defined event
Get number of all events
Get requested all events
Get number of new alarms
Get number of new alarms
Get requested new alarms
Get recent alarms
Acknowledge alarms
Get number of all alarms
Get requested all alarms
Start Pulse Count Calibration: Force current pulse count rate
Start Pulse Count Calibration: Force fixed pulse count rate
End Pulse Count Calibration
Force current temperature
Force fixed temperature
Remove forced temperature
Force current static pressure
Force fixed static pressure
Remove forced static pressure
Force current differential pressure
Force fixed differential pressure
Remove forced differential pressure
Force current pulse count rate
Force fixed pulse count rate
Remove forced pulse count rate
Force current mass flow rate
Force fixed mass flow rate
Remove forced mass rate
Start Mass Flow Rate Calibration: Force current Mass Flow
Rate
Start Mass Flow Rate Calibration: Force fixed Mass Flow
Rate
Realflo User and Reference Manual
May 19, 2011
845
TeleBUS Protocol Interface
151
301
303
351
353
701
703
801
139
140
142
143
144
146
147
150
802
803
804
1901
1903
2201
2203
112
130
131
132
133
134
135
136
137
138
Command
Number
95
100
101
102
103
104
112
Command Description
End Mass Flow Rate Calibration
Lookup user number
Lookup userID
Delete account
Update account
Read next account
Get Coriolis meter configuration
Set Coriolis meter configuration
Search for MVT sensor
Change address of MVT sensor
Get MVT configuration
Set MVT configuration
Get MVT sensor information
Calibrate MVT sensor
Read MVT configuration
Get Display Control Configuration
Set Display Control Configuration
Set Sensor Mode
Get number of process inputs
Get process input
Set process input
Get number of process outputs
Get process output
Set process output
Get Custom Display Configuration
Set Custom Display Configuration
Get AGA-3 (1992) configuration
Set AGA-3 (1992) configuration
Get AGA-3 (1985) configuration
Set AGA-3 (1985) configuration
Get AGA-7 configuration
Set AGA-7 configuration
Get AGA-8 gas ratios
Get AGA-8 Hexanes+ Gas Ratios
Set AGA-8 gas ratios
Set AGA-8 Hexanes+ Gas Ratios
Get NX19 gas ratios
Set NX19 gas ratios
Get V-Cone configuration
Set V-Cone Configuration
Realflo User and Reference Manual
May 19, 2011
846
Flow Computer Register Grouping
Flow Computer Register Grouping
Register grouping provides a method to group commonly read data from a
SolarPack 410 flow computer. The data that is commonly read is in scattered register locations in the flow computer. Register grouping enables the SCADA Host to read a sequential block of data in a single read command. The start address for the register group is user defined.
SolarPack 410 flow computer version 6.51 or later is required for this feature.
Register Group Data
The flow computer data and the order of the register locations are shown the table below. The data is grouped in consecutive Modbus Input (30000)
or Modbus Holding (40000) registers. See the
section below for information on how to define the Start Register.
Data in the register group are floating point values with the high word in the lower numbered register. This format is common to Telepace, ISaGRAF and
Realflo and is readily accessible by SCADA Host packages. The Battery
Voltage and Contract Hour are internally converted from integer format to floating point format.
The flow computer data for each register is described in the Description column of the table.
The Units column describes the flow computer data units as defined in the flow computer Inputs and Contract configuration. These units are configured using Realflo configuration Inputs tab and Contract tab respectively.
Register Group
Start Register
Format Description
Float Battery voltage
Start Register + 1 Float
Start Register + 2 Float
Differential pressure
(AGA-3 or V-Cone) or pulse rate (AGA-7)
Static pressure
Units
volts
Input
Input
Source
Instantaneous input
Instantaneous input
Start Register + 3 Float
Start Register + 4 Float
Temperature Input
Instantaneous input
Instantaneous input
Instantaneous input
Forced inputs flags: register contains the sum of each force flag:
1 = DP or pulse rate forced
10 = SP forced
100 = Temp forced
For example if both SP and temperature are forced the value in the none
Realflo User and Reference Manual
May 19, 2011
847
Flow Computer Register Grouping
Register Group
Start Register + 5
Format Description
Float register will be 110.
Volume rate
Start Register + 6
Start Register + 7
Start Register + 8
Start Register + 9
Start Register + 10
Start Register + 11
Start Register + 12
Start Register + 13
Start Register + 14
Start Register + 15
Start Register + 16
Start Register + 17
Start Register + 18
Start Register + 19
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Units Source
Flow extension (AGA-3)
or uncorrected volume rate
(AGA-7)
Accumulated volume today
Accumulated volume yesterday
Accumulated energy today
Accumulated energy yesterday
Flow duration today
Flow duration yesterday
Accumulated mass today
Accumulated mass yesterday
Heating value
Mass density
Contract Instantaneous calculated
Contract Instantaneous calculated
Contract Instantaneous calculated
Contract Instantaneous calculated
Contract Instantaneous calculated
Contract Instantaneous calculated
Seconds Instantaneous calculated
Seconds Instantaneous calculated
Contract Instantaneous calculated
Contract Instantaneous calculated
Contract Instantaneous calculated
Contract Instantaneous calculated
Input Configured Orifice diameter (AGA-3) or
cone diameter (V-Cone)
Contract hour
Pipe diameter
None
Input
Configured
Configured
Realflo User and Reference Manual
May 19, 2011
848
Flow Computer Register Grouping
Configure Register Group Location
The register group is defined, enabled and monitored using a block of three
Modbus registers as seen in the table below.
Modbus
Register
48520
(input)
48521
(input)
48522
(output)
Format
UINT
UINT
UINT
Description
Register Group Start Register
30001 to 39760
40501 to 47460
Excluding the flow computer reserved registers 40001 to 40500,
43180 to 43799 and 47500 to 49999.
section for information on reserved
registers.
Register Group Enable Register
0 = OFF(Do not copy flow computer data to register group)
1 = ON (Copy flow computer data to register group)
Register Group Status Register
0 = OFF (Enable is OFF)
1 = ON (flow computer data is copied to register group)
2 = Invalid Start Register
3 = Overlaps flow computer reserved registers.
(40001 to 40500, 43180 to 43799, 47500 to 49999 are reserved)
4 = Overlaps Device Identifier reserved registers.
(39800 to 39999 are reserved)
To configure the register group the Register Group Start Register needs to be defined. To do this write the start register address into register 48520.
For example if you want the register group to stat at register 31000 the value 31000 needs to be written to register 48520. In this case the flow computer data is written to registers 31000 (Start Register) through 31020
(Start Register + 19)
Once the register group is configured the Register Group Enable Register is used to enable of disable the register group. The register group is enabled by writing a value of 1 into register 48521.The register group is disabled by writing a value of 0 into register 48521.
To monitor the status of the register group monitor register 48522. The status codes are shown in the table above. The Register Group Status
Register provides immediate feedback about the validity of the settings.
The register group data is copied to the registers only when the Register
Group Status Register status register has a value of 1.
The Realflo Custom View feature is used to write values to the Register
Group Start Register (48520) and the Register Group enable Register
(48521) and to read the Register Group Status Register (48522). See the
section for complete details on using the
Custom View to write and monitor the register Group registers.
Realflo User and Reference Manual
May 19, 2011
849
Flow Computer Application ID
Flow Computer Application ID
Realflo automatically enables device configuration register mapping when the flow computer is run. Device configuration registers provide useful information on the flow computer, logic applications and controller used in a
Realflo application.
Refer to the Telepace, ISaGRAF and appropriate C Tools manuals for complete information on enabling and disabling Device Configuration
Register mapping.
Flow computers set their application ID using the C API and enable the device configuration register mapping. This can be disabled from a logic application or other C applications.
Application Identifiers
Each flow computer application is identified by a unique value. See the table in the Device Configuration Read Only Registers for the actual registers used.
Description Value
Company ID 1 = Control Microsystems
Application number 1 = SCADAPack & SCADAPack 4202 Telepace
2 = SCADAPack & SCADAPack 4202 Telepace
(Enron Modbus)
3 = SCADAPack & SCADAPack 4202 ISaGRAF
4 = SCADAPack & SCADAPack 4202 ISaGRAF
(Enron Modbus)
5 = SCADAPack 32 Telepace
6 = SCADAPack 32 ISaGRAF
7 = SCADAPack 330 & 334 Telepace
8 = SCADAPack 330 & 334 ISaGRAF
9 = SCADAPack 350 Telepace
10 = SCADAPack 350 ISaGRAF
11 = SCADAPack 4203 Telepace
12 = SCADAPack 4203 ISaGRAF
13 = SolarPack 410 Telepace
14 = SolarPack 410 ISaGRAF (not implemented)
15 = Reserved
16 = Reserved
17 = SCADAPack 32 Telepace with PEMEX
18 = SCADAPack 32 ISaGRAF with PEMEX
19 = SCADAPack 330 & 334 Telepace with
PEMEX
20 = SCADAPack 330 & 334 ISaGRAF with
PEMEX
21 = SCADAPack 350 Telepace with PEMEX
22 = SCADAPack 350 ISaGRAF with PEMEX
23 = SCADAPack 4203 Telepace with PEMEX
24 = SCADAPack 4203 ISaGRAF with PEMEX
25 = SolarPack 410 Telepace with PEMEX
26 = SolarPack 410 ISaGRAF with PEMEX (not
Realflo User and Reference Manual
May 19, 2011
850
Flow Computer Application ID implemented)
27 = Reserved
28 = Reserved
29 = SCADAPack 32 Telepace with GOST (not implemented)
30 = SCADAPack 32 ISaGRAF with GOST (not implemented)
31 = SCADAPack 330 & 334 Telepace with GOST
32 = SCADAPack 330 & 334 ISaGRAF with
GOST
33 = SCADAPack 350 Telepace with GOST
34 = SCADAPack 350 ISaGRAF with GOST
35 = SCADAPack 4203 Telepace with GOST (not implemented)
36 = SCADAPack 4203 ISaGRAF with GOST (not implemented)
37 = SolarPack 410 Telepace with GOST (not implemented)
38 = SolarPack 410 ISaGRAF with GOST (not implemented)
39 = Reserved
40 = Reserved
41 = SCADAPack 314 Telepace
42 = SCADAPack 314 ISaGRAF
43 = SCADAPack 314 Telepace with PEMEX
44 = SCADAPack 314 ISaGRAF with PEMEX
45 = SCADAPack 314 Telepace with GOST
46 = SCADAPack 314 ISaGRAF with GOST
Application version Current version of the flow computer
Device Configuration Read Only Registers
The Device configuration is stored in Modbus input (3xxxx) registers as shown below. The registers are read with standard Modbus commands.
These registers cannot be written to. Device configuration registers used fixed addresses. This facilitates identifying the applications in a standard manner.
The following information is stored in the device configuration. 2 logic application identifiers are provided for compatibility with SCADAPack ES/ER controllers that provide 2 ISaGRAF applications. The second logic application identifier is not used with other controllers. 32 application identifiers are provided to accommodate C applications in SCADAPack
314/330/350 controllers.
Register Description
39800 Controller ID (ASCII value), first byte.
39801
39802
39803
Controller ID (ASCII value), second byte.
Controller ID (ASCII value), third byte.
Controller ID (ASCII value), fourth byte.
39804
39805
39806
39807
Controller ID (ASCII value), fifth byte.
Controller ID (ASCII value), sixth byte.
Controller ID (ASCII value), seventh byte.
Controller ID (ASCII value), eighth byte.
Realflo User and Reference Manual
May 19, 2011
851
Flow Computer Application ID
39859
39862
39865
39868
39871
39874
39877
39880
39883
39886
39889
39817
39820
39823
39826
39829
39832
39835
39838
39841
39844
39847
39850
39853
39856
39892
39895
39898
39901
39904
39907
Register Description
39808
39809
39810
39811
39812
39813
39814
39815
39816
Firmware version (major*100 + minor)
Firmware version build number (if applicable)
Logic Application 1 - Company ID (see below)
Logic Application 1 - Application number (0 to 65535)
Logic Application 1 - Application version (major*100 + minor)
Logic Application 2 - Company ID (see below)
Logic Application 2 - Application number (0 to 65535)
Logic Application 2 - Application version (major*100 + minor)
Number of applications identifiers used (0 to 32)
Identifiers are listed sequentially starting with identifier 1.
Unused identifiers will return 0.
Application identifier 1 (see format below)
Application identifier 2 (see format below)
Application identifier 3 (see format below)
Application identifier 4 (see format below)
Application identifier 5 (see format below)
Application identifier 6 (see format below)
Application identifier 7 (see format below)
Application identifier 8 (see format below)
Application identifier 9 (see format below)
Application identifier 10 (see format below)
Application identifier 11 (see format below)
Application identifier 12 (see format below)
Application identifier 13 (see format below)
Application identifier 14 (see format below)
Application identifier 15 (see format below)
Application identifier 16 (see format below)
Application identifier 17 (see format below)
Application identifier 18 (see format below)
Application identifier 19 (see format below)
Application identifier 20 (see format below)
Application identifier 21 (see format below)
Application identifier 22 (see format below)
Application identifier 23 (see format below)
Application identifier 24 (see format below)
Application identifier 25 (see format below)
Application identifier 26 (see format below)
Application identifier 27 (see format below)
Application identifier 28 (see format below)
Application identifier 29 (see format below)
Application identifier 30 (see format below)
Application identifier 31 (see format below)
Realflo User and Reference Manual
May 19, 2011
852
Flow Computer Application ID
Register Description
39910
39913 to
39999
Application identifier 32 (see format below)
Reserved for future expansion
Application Identifier
The application identifier is formatted as follows.
Register
Start
Start +1
Start +2
Description
Company ID (see below)
Application number (0 to 65535)
Application version (major*100 + minor)
Company Identifier
Control Microsystems maintains a list of company identifiers to keep the company ID is unique. Contact Control Microsystems for a Company ID.
Company ID 0 indicates an identifier is unused.
Company IDs 1 to 100 are reserved for Control Microsystems use.
Realflo User and Reference Manual
May 19, 2011
853
Enron Modbus Protocol Interface
Enron Modbus Protocol Interface
The Enron Modbus protocol is used widely in the Oil and Gas industry to obtain data from electronic flow measurement devices. The protocol is a defacto standard in many industries. Control Microsystems supports this protocol in our flow computer products.
The Enron Modbus protocol is based on the Modbus ASCII and RTU protocols. Message framing is identical to the Modbus protocols. However, there are many differences in message formatting and register numbering, at both the logical and protocol levels.
The document Specifications and Requirements for an Electronic Flow
Measurement Remote Terminal Unit describes the Enron Modbus protocol.
The flow computer supports Enron Modbus and standard Modbus on the same serial port. Standard Modbus will use one station address and Enron
Modbus uses a different station address.
The flow computer does not determine which format a message is using, because the station address separates the data streams. This architecture allows standard PC applications to communicate with the flow computer in the normal manner. Enron Modbus hosts can communicate at the same time.
The flow computer program processes Enron Modbus commands, sends master messages, and processes master responses. This architecture allows the Enron Modbus commands to directly access flow computer data.
Flow computer data is accessed directly when a command is processed.
When data is written to the numeric registers for configuration, the flow computer reads the existing data structures, replace the targeted fields with new data and attempts to configure the run with the new configuration. This may be repeated with other configuration items when the command message is long.
Some registers are read only. The flow computer will not allow these registers to be written by not providing a write handler for these registers.
The flow computer supports the following Enron function codes.
Command
1
3
5
6
7
15
16
Description
Read multiple boolean variables
Read multiple numeric variables
Write single boolean variable
Write single numeric variable
Read unit status
Write multiple boolean variables
Write multiple numeric variables
Realflo User and Reference Manual
May 19, 2011
854
Enron Modbus Protocol Interface
Register Addresses
The addresses in the messages refer to system addresses, not type specific addresses. The commands will return exception errors if the command refers to addresses outside the valid range for the command.
There are ranges of Enron registers to hold short integers, long integers and single precision floats. The ranges are as follows.
Range Data Type
32
701
– 720
Event/Alarm archive
Hourly/Daily archive
741 - 750 Hourly Gas Quality History
1001 - 2999 Boolean
3001 - 4999 Short integer
5001 - 6999 Long integer
7000 - 9999 Float
In general, both Numeric and Boolean function codes can be used to read and write any type of registers. Consult the Enron Modbus specification for details.
section of this document for details
on the registers allocated to the flow computer.
Variable Types
Boolean Variables
Boolean variables are accessed using commands 1, 5, and 15. These commands are similar to the corresponding standard Modbus commands.
They use the Enron Modbus addressing.
Read only registers cannot be written using commands 5 and 15.
Short Integer Variables
Short integer variables are accessed using commands 3, 6, and 16. These commands are similar to the corresponding standard Modbus commands.
They use the Enron Modbus addressing.
The size of the data fields for each variable is determined by the variable address. The read command returns two bytes for each requested register.
The write command provides two bytes for each register value.
Read only registers cannot be written using commands 6 and 16.
Long Integer and Floating Point Variables
Long integer and floating point variables are accessed using commands 3,
6, and 16. These commands are similar to the corresponding standard
Modbus commands. They use the Enron Modbus addressing.
The size of the data fields for each variable is determined by the variable address. The read command returns four bytes for each requested register.
The write command provides four bytes for each register value.
Read only registers cannot be written using commands 6 and 16.
Realflo User and Reference Manual
May 19, 2011
855
Enron Modbus Protocol Interface
Hourly/Daily History
Enron Modbus Hourly/Daily archive registers are used to read Realflo hourly and daily logs. They read the logs one record at a time.
Hourly Gas Quality History
Enron Modbus Hourly Gas Quality archive registers are used to read Realflo hourly gas quality history logs. The logs are read one record at a time.
Gas Quality History is available when the Gas Transmission option bit is enabled for the controller. Only hourly records are supported.
Flow Computer Variables
The Realflo Flow Computer provides up to ten flow runs. Flow runs are configured individually. Gas quality is set for each flow run.
The Flow computer provides up to ten MVT transmitters. Transmitters are configured individually.
Registers may be read/write or read-only. The Access column in the tables indicates the register type. Configuration registers are read/write registers.
The flow computer uses the ranges of Enron Modbus variables shown in the table below.
Purpose Hourly/
Daily
Archive
Boolean
Events/
Alarms
Log Pointers
System
Variables
Run 1 none none none none none
1001 to
1099
701 to 702 1100 to
1199
Run 2
Run 3
Run 4
Run 5
Run 6
Run 7
Run 8
Run 9
Run 10
MVT - 1
MVT - 2
703 to 704 1200 to
1299
705 to 706 1300 to
1399
707 to 708 1400 to
1499
709 to 710 1500 to
1599
711 to 712 1600 to
1699
713 to 714 1700 to
1799
715 to 716 1800 to
1899
717 to 718 1900 to
1999
719 to 720 2000 to
2099 none none none none
Integer
none none
3000 to 3099 none
3100 to 3199
4400 to 4429
3200 to 3299
4430 to 4459
3300 to 3399
4460 to 4489
3400 to 3499
4490 to 4519
3500 to 3599
4520 to 4549
3600 to 3699
4550 to 4579
3700 to 3799
4580 to 4609
3800 to 3899
4610 to 4639
3900 to 3999
4640 to 4669
4000 to 4099
4670 to 4699
4100 to 4129
4700 to 4729
4130 to 4159
4730 to 4759
Long Integer
none none
5100 to 5199
5200 to 5299
5300 to 5399
5400 to 5499
5500 to 5599
5600 to 5699
5700 to 5799
5800 to 5899
5900 to 5999
6000 to 6099
6100 to 6129
6130 to 6159
Floating
Point
7000
7001 to 7003
None
7100 to 7349
7350 to 7599
7600 to 7849
7850 to 8099
8100 to 8349
8350 to 8599
8600 to 8849
8850 to 9099
9100 to 9349
9350 to 9599
9600 to 9629
9630 to 9659
Realflo User and Reference Manual
May 19, 2011
856
Purpose
MVT - 3
MVT - 4
MVT - 5
MVT - 6
MVT - 7
MVT - 8
MVT - 9
MVT - 10
Hourly/
Daily
Archive
none none none none none none none none none none none none none none none none
Boolean Integer
Enron Modbus Protocol Interface
Long Integer Floating
Point
4160 to 4189
4760 to 4789
4190 to 4219
4790 to 4819
4220 to 4249
4820 to 4849
4250 to 4279
4850 to 4879
4280 to 4309
4880 to 4909
4310 to 4339
4910 to 4939
4340 to 4369
4940 to 4969
4370 to 4399
4970 to 4999
6160 to 6189 9660 to 9689
6190 to 6219 9690 to 9719
6220 to 6249 9720 to 9749
6250 to 6279 9750 to 9779
6280 to 6309 9780 to 9809
6310 to 6339 9810 to 9839
6340 to 6369 9840 to 9869
6370 to 6399 9870 to 9899
Realflo User and Reference Manual
May 19, 2011
857
Enron Modbus Protocol Interface
Enron Modbus General Purpose Registers
In some applications it is desirable to have the ability to map Modbus register data into Enron Modbus registers. This removes the need to have a host poll the Modbus station address for data not directly associated with the flow computer and then poll the Enron Modbus station address for flow computer data.
Using fixed register mapping the flow computer mirrors standard Modbus registers into Enron Modbus registers. This allows the host to read and write data to Enron Modbus registers not directly associated with the flow computer.
Register Mapping
Modbus registers are mapped to Enron registers. Read/write registers can be read or written using Enron Modbus. Read only registers can be read using Enron Modbus; data written to the registers is ignored.
Status and Coil Registers
Coil and status registers map to Enron Boolean registers.
Modbus Registers Enron Registers
00001 to 00100
10001 to 10099
2101 to 2200
2201 to 2299
Number Access
100
99
Read/Write
Read only
16-Bit Input Registers
– Telepace only
In Telepace firmware, 16-bit input registers map to Enron Long Integer registers. Short integer registers are not used as the short integer registers available are used by the flow computer.
Modbus Registers Enron Registers
30001 to 30100 6800 to 6899
Number
100
Access
read only
Each 16-bit Modbus register is mapped to one 32-bit Enron Modbus long integer. Modbus values are treated as 16-bit signed values and are sign extended when mapped.
16-Bit Holding Registers
– Telepace only
In Telepace firmware, 16-bit holding registers are mapped to Enron Long
Integer registers. Short integer registers are not used as the short integer registers available are used by the flow computer.
Modbus Registers Enron Registers
40500 to 40579 6900 to 6979
Number
80
Access
read/write
Each 16-bit Modbus register is mapped to one 32-bit Enron Modbus long integer. Modbus values are treated as 16-bit signed values and are sign extended when mapped. Writing a value to the Enron register that is larger than can be represented by the 16-bit Modbus register will result in only the lower order 16-bits being placed in the Modbus register.
Realflo User and Reference Manual
May 19, 2011
858
Enron Modbus Protocol Interface
32-Bit Integer Holding Registers
Long values stored in pairs of holding registers are mapped to Enron Long
Integer registers. These values are suitable for double integers and 32-bit counters.
Telepace Firmware
This mapping is used in Telepace firmware only.
Modbus Registers Enron Registers
40580 to 40619 6980 to 6999
Number Access
20 read/write
Each pair of Modbus registers is mapped to one 32-bit Enron Modbus long integer. Values are 32-bit integers; as there is an exact mapping the registers can be viewed as signed or unsigned values at the user‟s choice.
The least significant 16 bits of the number is stored in the lower numbered
Modbus register of the pair. This is the format used by Telepace applications to store double integers.
ISaGRAF Firmware
This mapping is used in ISaGRAF firmware only. It allows directly mapping
ISaGRAF variables into Enron registers.
Modbus Registers Enron Registers
40500 to 40619 6900 to 6959
Number Access
60 read/write
Each pair of Modbus registers is mapped to one 32-bit Enron Modbus long integer. Values are 32-bit integers; as there is an exact mapping the registers can be viewed as signed or unsigned values at the user‟s choice.
The least significant 16 bits of the number is stored in the higher numbered
Modbus register of the pair. This is the format used by ISaGRAF variables mapped to Modbus registers.
32-Bit Floating Point Holding Registers
Floating point values stored in pairs of holding registers are mapped to
Enron Float registers. The second range can be read using the Enron
Modbus protocol, but might not be available on some Enron Modbus hosts.
Modbus Registers Enron Registers
40620 to 40819
40820 to 41019
9900 to 9999
10000 to 10099
Number Access
100
100 read/write read/write
Each pair of Modbus registers is mapped to one Enron Modbus float register.
The most significant 16 bits of the number is stored in the lower numbered
Modbus register. This is the floating point format used by Telepace and
ISaGRAF variables.
Realflo User and Reference Manual
May 19, 2011
859
Enron Modbus Protocol Interface
Flow Computer Global Variables
The variables described in this section are not meter run specific, but common to each meter run.
Program Information Variables
Program information identifies the version of the flow computer firmware and the flow computer.
The number of runs available is determined by the flow computer options.
Register Description
3001
3002
3003
3004
3005
Firmware version
Range: 100 to 999
Controller type
2 = TeleSAFE Micro16
5 = SCADAPack
6 = SCADAPack Light
7 = SCADAPack Plus
9 = SCADAPack 32P
10 = SCADAPack 32
12 = SCADAPack LP
13 = SCADAPack 100
14 = 4202
25 = SCADAPack 100+
27 = SCADAPack 350
29 = 4202 DR
30 = 4202 DS
31 = 4203 DR
32 = 4203 DS
33 = SCADAPack 330
34 = SCADAPack 334
36 = SCADAPack 314
Flow Computer Version
Range: 100 to 999
Flow Computer Build Number
Range: 1 to 255
Number of flow runs available
Range: 0 to 10
Access
Read Only
Read Only
Read Only
Read Only
Read Only
Meter Runs Configuration Variable
This register configures the number of flow runs in the flow computer. The number of runs needs to be less than or equal to the number of runs available for the flow computer.
Register Description
3009 Number of flow runs in use
Range: 1 to 10
Access
Read / Write
Real Time Clock Variables
The real time clock can be adjusted in two ways.
To adjust the clock forward or backward by a number of seconds, write to register 3010. This is useful if the time to transmit a message to the flow computer is not known.
Realflo User and Reference Manual
May 19, 2011
860
Enron Modbus Protocol Interface
To set the clock to a specific time, write to registers 3011 to 3016.
Register Description
3010
3011
3012
3013
3014
3015
3016
Time adjustment in seconds
Range: -32000 to 32000
Year
Range: 1997 to 2096
Month
Range: 1 to 12
Day
Range: 1 to 31 with exceptions
Hour
Range: 0 to 23
Minute
Range: 0 to 59
Second
Range: 0 to 59
Access
Write Only
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Flow Computer ID Variables
The flow computer ID is a string stored in 8 consecutive integers. Printable
ASCII values, in the range specified need to be used for each character in the string.
Register Description
3020
3021
3022
3023
3024
3025
3026
3027
Flow computer ID character 1
Range: 33 to 126
Flow computer ID character 2
Range: 33 to 126
Flow computer ID character 3
Range: 33 to 126
Flow computer ID character 4
Range: 33 to 126
Flow computer ID character 5
Range: 33 to 126
Flow computer ID character 6
Range: 33 to 126
Flow computer ID character 7
Range: 33 to 126
Flow computer ID character 8
Range: 33 to 126
Access
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Hourly / Daily Archive Records
The Realflo Flow Computer provides up to 10 flow runs. Hourly and daily history records are read using the standard Enron Modbus method.
The Daily Log holds records for the previous 35 days. These can be read by using index numbers 0 through 34 or by using 1 through 35.
The Hourly Log holds record for the previous 35 days plus today. Each day is allowed 30 hours to handle calculation stops, power failures and configuration changes across multiple flow runs. These can be accessed using index numbers 1 through 1080.
Some hourly records will be used by only one run in a multiple run flow computer. The other runs will return a record with the data 030102 (March 1,
Realflo User and Reference Manual
May 19, 2011
861
Enron Modbus Protocol Interface
2002), time 00:00:00 and flow duration 0. These records should be discarded.
Hourly / Daily Record Format
Each hourly and daily record is in the following format.
Date (format: MMDDYY)
Time (format: HHMMSS)
Flow duration
Volume
Energy
Flow Extension or Flow Product or Uncorrected Flow Volume.
Temperature
Pressure
Differential Pressure or Meter Pulses
Volume * 1000
Mass
Relative Density
Archives are stored in the following registers.
Register Description
701 Meter Run 1: hourly history
702
703
Meter Run 1: daily history
Meter Run 2: hourly history
704 Meter Run 2: daily history
712
713
714
715
716
717
705
706
707
708
709
710
711
718
719
720
Meter Run 3: hourly history
Meter Run 3: daily history
Meter Run 4: hourly history
Meter Run 4: daily history
Meter Run 5: hourly history
Meter Run 5: daily history
Meter Run 6: hourly history
Meter Run 6: daily history
Meter Run 7: hourly history
Meter Run 7: daily history
Meter Run 8: hourly history
Meter Run 8: daily history
Meter Run 9: hourly history
Meter Run 9: daily history
Meter Run 10: hourly history
Meter Run 10: daily history
Access
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Pointers to the hourly and daily history records are stored in the following registers. The pointers apply to archives in the flow computer.
Register Description
7001 hourly log pointer
7002 daily log pointer
Access
Read Only
Read Only
Realflo User and Reference Manual
May 19, 2011
862
Enron Modbus Protocol Interface
Hourly Gas Quality Archive Records
742
743
744
745
746
747
The hourly gas analysis history is added for flow computer versions 6.77 and higher.
Hourly Gas Quality Record Format
Not all gas quality elements supported by the flow computer are defined in the Enron Specification. Those elements, starting with water, are added at the end of the defined stream. Gas components are in %, not in % MOLE.
Each hourly and daily record is in the following format.
Field
Date
Time
Time: split of a second
Relative Density
Heating Value
Carbon Dioxide
Nitrogen
Methane
Ethane
Propane i-butane n-Butane i-Pentane n-Pentane n-Hexane n-Heptane n-Octane n-Nonane
Hydrogen Sulfide
Hydrogen
Helium
Oxygen
Carbon Monoxide
Water n-Decane
Argon
Hexanes+
Format / Units
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
MMDDYY.0
HHMMSS.0 second
-
BTU(60)/ft
3
Archives are stored in the following registers.
Register Description
741 Meter Run 1: hourly gas quality history
Access
Read Only
Meter Run 2: hourly gas quality history
Meter Run 3: hourly gas quality history
Meter Run 4: hourly gas quality history
Meter Run 5: hourly gas quality history
Meter Run 6: hourly gas quality history
Meter Run 7: hourly gas quality history
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Realflo User and Reference Manual
May 19, 2011
863
Enron Modbus Protocol Interface
748
749
Meter Run 8: hourly gas quality history Read Only
Meter Run 9: hourly gas quality history Read Only
750 Meter Run 10: hourly gas quality history
Read Only
Pointers to the hourly and daily history records are stored in the following registers. The pointers apply to archives in the flow computer.
Register Description
7003 hourly gas quality log pointer
Access
Read Only
Flow Computer Events Variables
The Flow Computer Events variables record changes in the flow computer status. Events will be recorded for these variables when the corresponding status changes. Reading these registers will return zero. The registers exist only to provide a reference for events in the event log.
Register Description
1001
1002
1003
Power On - Cold Boot
Power On
– Warm Boot
Power Off
Access
Read Only
Read Only
Read Only
The registers in the table below apply to Run 1. Refer to the table in section
Flow Computer Variables for register ranges for other runs.
Register Description
1100
1101
Recovered from Input Error
Meter control structure not found
Access
Read Only
Read Only
User Account Events Variables
These variables record events relating to the user accounts. Events will be recorded for these variables when the user accounts are configured.
Reading these registers will return zero. The registers exist only to provide a reference for events in the event log.
Register Description
3030 Set User Number
3031 Set User Security Level
Access
Read Only
Read Only
Event/Alarm Archive Variable
This variable indicates the number of events and alarms.
Register Description
7000 Number of events and alarms
Access
Read Only
Event and Alarm Log Events Variables
These variables record events relating to the event log. Events will be recorded for these variables when the logs are accessed. Reading these registers will return zero. The registers exist only to provide a reference for events in the event log.
The registers in the table below apply to Run 1. Refer to the table in section
Flow Computer Variables for register ranges for other runs.
Realflo User and Reference Manual
May 19, 2011
864
Enron Modbus Protocol Interface
Register Description
3101
3102
3103
3104
3105
Number of lost alarms
Number of acknowledged alarms
Number of lost events
Number of acknowledged events
Invalid user event
Access
Read Only
Read Only
Read Only
Read Only
Read Only
Event Record Format
Events use the Enron Modbus record format defined in the Enron Modbus standard.
Byte
1,2
3,4
5-8
9-12
13-16
17-20
Description
Operator change bit map
Modbus register number of variable
Time (HHMMSS)
Date (MMDDYY)
80 is added to the date value to convert the RTU event log dates to the current year (see Enron Modbus specification
Appendix D).
Previous value of variable
New value of variable
Format
Uint16
Uint16
Float
Float
Float
Float
The operator change bit map is:
10
11
12
13
14
15
5
6
7
8
9
Bit
0
1
2
3
4
Description
Fixed value
Zero scale
Full scale
Operator entry work value
Boolean fixed bit
Fixed/variable flag
Table entry change
System command change
Unused
Operator change event identifier bit
LoLo limit
Lo limit
Hi limit
HiHi limit
Rate of change limit unused
Alarm Record Format
Alarms use the Enron Modbus record format defined in the Enron Modbus standard.
Byte
1,2
3,4
5-8
Description
Alarm change bit map
Modbus register number of variable
Time (HHMMSS)
Format
Uint16
Uint16
Float
Realflo User and Reference Manual
May 19, 2011
865
9-12 Date (MMDDYY)
80 is added to the date value to convert the
RTU event log dates to the current year (see
Enron Modbus specification Appendix D).
Current (alarmed) value of variable
Unused (0)
Enron Modbus Protocol Interface
Float
Float
Float
13-16
17-20
The operator change bit map is:
Bit
8
9
10
11
12
13
14
15
3
4
5
0
1
2
6
7
Description
Unused
Unused
Unused
Unused
Unused
Unused
Unused
Unused
Unused
Operator change event identifier bit
LoLo limit
Lo limit
Hi limit
HiHi limit
Rate of change limit
Set/reset Alarm (1=set, 0=reset)
Realflo User and Reference Manual
May 19, 2011
866
Enron Modbus Protocol Interface
Meter Run 1 Data Variables
Meter run 1 data variables are shown in detail in the following sections.
Meter Run 1 Flow Computer Execution State Variable
This variable displays and controls the execution of the meter run 1 flow calculation.
Register Description
3165 Execution state
0 = not set (read only)
1 = stop
2 = run
Access
Read / Write
Meter Run 1 Instantaneous and Accumulated Variables
These variables display the current state of the flow calculation for meter run
1.
Instantaneous Input Variables
The Instantaneous Input variables contain the value of the inputs at the time they were last read.
Register
7220
7221
7222
7223
Description
Temperature
Static Pressure
Differential Pressure (AGA-3 and V-cone only)
Calibration flags
Access
Read Only
Read Only
Read Only
Read Only
Register Description
5100
5157
Turbine meter pulses (AGA-7)
Forced Pulse Rate (AGA-7 only)
Access
Read Only
Read Only
Instantaneous Input Alarms
These variables are used to show the status of the Instantaneous Input
Variables.
Register Description
4400
4401
4402
Temperature input alarm
Static pressure input alarm
Flow (Differential pressure or turbine pulses) input alarm
Access
Read Only
Read Only
Read Only
Instantaneous Flow Variables
The Instantaneous Flow variables contain the results of the flow calculation.
Values are updated each time the flow calculation executes. Check the time of last update registers to determine when the calculation was performed.
Register Description
7224
7225
Date of flow update (days since Jan 1,
1970)
Time of flow update (seconds since
Access
Read Only
Read Only
Realflo User and Reference Manual
May 19, 2011
867
Register Description
7226
7227
7228
00:00:00)
Flow volume rate
Flow mass rate
Flow energy rate
7229
7230
7252
7282
7283
7284
Enron Modbus Protocol Interface
Access
Flow extension (AGA-3 1990 only)
Flow product (AGA-3 1985 only)
Uncorrected flow volume (AGA-7 only)
Input or flow calculation error code
Flow volume rate * 1000
Forced Temperature
Forced Static Pressure
Forced Differential Pressure (AGA-3 and V-
Cone only)
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Compressibility Variables
The Compressibility variables contain the results of the compressibility calculation. Values are updated each time the compressibility calculation recalculates. This time varies according to the calculation type and the changes in the inputs to the calculation (including configuration parameters).
Check the time of last update registers to determine when the calculation was performed.
Register Description
7231
7232
Date of compressibility update (days since
Jan 1, 1970)
Time of compressibility update (seconds since 00:00:00)
7233
7234
7235
7236
7237
7238
7239
Supercompressibility
Real relative gas density
Mass density at flow conditions
Mass density at base conditions
Heating value
Compressibility calculation error code
Compressibility approximated flag
0 = compressibility value is calculated result
1 = compressibility value is approximate
Access
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Accumulated Flow Variables
The Accumulated Flow variables contain the cumulative flow for the current and previous contract day and the current and previous month. Values for the current contact day include flow for the contract day, even if an event causes a separate day record in the hourly history. Values for the previous contract day are updated at the end of the contract day.
Access
Read Only
Register Description
5101
5102
Number of flow calculations during the previous contract day
Number of flow calculations during the contract day
Register Description
Read Only
Access
Realflo User and Reference Manual
May 19, 2011
868
Enron Modbus Protocol Interface
7250
7251
7285
7286
7287
7288
7289
Register Description
7240
7241
7242
7243
7244
7245
7246
7247
7248
7249
7290
7291
7292
Duration of flow during the contract day
(seconds)
Flow volume at base conditions during the contract day
Flow mass at base conditions during the contract day
Flow energy at base conditions during the contract day
Total accumulated flow volume at base conditions
Duration of flow during the previous contract day (seconds)
Flow volume at base conditions during the previous contract day
Flow mass at base conditions during the previous contract day
Flow energy at base conditions during the previous contract day
Static Pressure Altitude and Latitude compensation
0 = ignore
1 = compensate
Altitude
Latitude in decimal degrees
Flow duration in current month.
Flow volume in current month
Flow duration in previous month
Flow volume in previous month
Uncorrected flow volume during the contract day (AGA-7 only)
Uncorrected flow volume during the previous contract day (AGA-7 only)
Uncorrected flow volume during the current month (AGA-7 only)
Uncorrected flow volume during the previous month (AGA-7 only)
Access
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read/Write
Read/Write
Read/Write
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Enron Log Variables
The following registers are added to show the date of last configuration change.
Register
5103
5104
5105
5106
Description
Date of last flow configuration change (days since January 1, 1997).
Time of last flow configuration change
(seconds since midnight).
Date of last density configuration change
(days since January 1, 1997).
Time of last density configuration change
(seconds since midnight).
Access
Read Only
Read Only
Read Only
Read Only
Realflo User and Reference Manual
May 19, 2011
869
Enron Modbus Protocol Interface
Meter Run 1 Input Configuration Variables
The flow calculation routines require a temperature transmitter input, static pressure transmitter input and a differential pressure transmitter input (AGA-
3 or V-Cone), or pulse input (AGA-7).
General Input Configuration Variables
The General Input Configuration variables are set to contain the meter run number, type of units used and the flow and compressibility calculation types.
Register Description
7100
7101
7102
7103
7104
Input units type
0 = US1
3 = IP
Metric2
6 = Metric3
9 = US5
12 = US8
1 = US2
4 = Metric1
7 = SI
10 = US6
Flow calculation type
2 = AGA-3 (1985)
7 = AGA-7
22 = V-Cone
Compressibility calculation type
8 = AGA 8
19 = NX-19
Static pressure tap location
0 = upstream
1 = downstream
Log out of range events action
0= ignore Out Of Range events
1= log Out Of Range events
2 = US3
5 =
8 = US4
11 = US7
3 = AGA-3 (1992)
12 = AGA-11
Access
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Temperature Input Variables
The temperature input variables are set to contain the source register; the minimum and maximum scaled and unscaled values, and the level limits and hysteresis.
The input register type describes the type of data in the input registers. For floating-point input registers, floating-point scaling values need to be used.
For integer input registers, integer scaling values need to be used.
Register Description
7105
7106
Temperature input register type
0 = Telepace uint requiring scaling
2 = float in engineering units (no scaling required)
3 = float requiring scaling
4 = MVT
5 = ISaGRAF integer requiring scaling
6 = SCADAPack 4202 or 4203
Temperature input register
Modbus address 30001 to 39999 or 40001 to 49999 or
MVT transmitter number (1 to 10)
Access
Read / Write
Read / Write
Realflo User and Reference Manual
May 19, 2011
870
Enron Modbus Protocol Interface
Register Description
7107
7108
7109
7110
7111
7112
7113
7114
7115
7116 or use 1 for SCADAPack 4202 or 4203
Zero scale temperature input
(used with type 0 and 5 inputs) full scale temperature input
(used with type 0 and 5 inputs) zero scale temperature input (used with type 3 inputs)
Full scale temperature input (used with type
3 inputs)
Temperature at zero scale
Temperature at full scale
Temperature low level cutoff
Temperature low level hysteresis
Temperature high level hysteresis
Temperature high level cutoff
Access
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Static Pressure Input Variables
The static pressure input variables are set to contain the source register; the minimum and maximum scaled and unscaled values, and the level limits and hysteresis.
The input register type describes the type of data in the input registers. For floating-point input registers, floating-point scaling values need to be used.
For integer input registers, integer-scaling values need to be used.
Register Description
7117
7118
7119
Static pressure input register type
0 = Telepace uint requiring scaling
2 = float in engineering units (no scaling required)
3 = float requiring scaling
4 = MVT
5 = ISaGRAF integer requiring scaling
6 = SCADAPack 4202 or 4203
Static pressure input register
Modbus address 30001 to 39999 or 40001 to 49999 or
MVT transmitter number (1 to 10) or use 1 for SCADAPack 4202 or 4203
Zero scale static pressure input
(used with type 0 and 5 inputs)
7120
7121
7122
7123
7124
7125
Full scale static pressure input
(used with type 0 and 5 inputs)
Zero scale static pressure input
(used with type 3 inputs)
Full scale static pressure input
(used with type 3 inputs)
Static pressure at zero scale
Static pressure at full scale
Static pressure low level cutoff
Access
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Realflo User and Reference Manual
May 19, 2011
871
Enron Modbus Protocol Interface
Register Description
7126
7127
7128
Static pressure low level hysteresis
Static pressure high level hysteresis
Static pressure high level cutoff
Access
Read / Write
Read / Write
Read / Write
Differential Input Variables
The differential pressure input variables are set to contain the source register; the minimum and maximum scaled and unscaled values, and the level limits and hysteresis.
The input register type describes the type of data in the input registers. For floating-point input registers, floating-point scaling values need to be used.
For integer input registers, integer-scaling values need to be used.
The differential pressure input is used with AGA-3 and V-Cone calculations only.
Register Description
7129 Differential pressure input register type
0 = Telepace uint requiring scaling
2 = float in engineering units (no scaling required)
3 = float requiring scaling
4 = MVT
5 = ISaGRAF integer requiring scaling
7130
7131
6 = SCADAPack 4202 or 4203
Differential pressure input register
Modbus address 30001 to 39999 or 40001 to 49999 or
MVT transmitter number (1 to 10) or use 1 for SCADAPack 4202 or 4203 zero scale differential pressure input
(used with type 0 and 5 inputs)
7132
7133
7134
7135
7136
7137
7138
7139
7140
Full scale differential pressure input
(used with type 0 and 5 inputs) zero scale differential pressure input
(used with type 3 inputs)
Full scale differential pressure input
(used with type 3 inputs)
Differential pressure at zero scale
Differential pressure at full scale
Differential pressure low level cutoff
Differential pressure low level hysteresis
Differential pressure high level hysteresis
Differential pressure high level cutoff
Access
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Turbine Input Variables
The turbine counter input registers are set to contain the source register, the low flow minimum pulse limit and the time duration for low flow pulse limit check.
The turbine counter input is used with AGA-7 calculations only
Realflo User and Reference Manual
May 19, 2011
872
Register Description
7141 Turbine input register type
0 = Telepace ulong
7142
7143
7144
7145
7146
Enron Modbus Protocol Interface
Access
Read / Write
5 = ISaGRAF integer
Rotation counter input register
Modbus address 30001 to 39999 or 40001 to 49999
Time duration for low flow pulse limit check
(seconds)
Range: 0 to 5 seconds
Low flow minimum pulse limit
Range: 0 to 8388607
The low flow minimum pulse limit can be set to values greater than 8388607 by
Realflo.
Atmospheric pressure
Output and logs units type:
0 = US1 1 = US2
3 = IP
Metric2
4 = Metric1
6 = Metric3
9 = US5
12 = US8
7 = SI
10 = US6
2 = US3
5 =
8 = US4
11 = US7
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Meter Run 1 Flow Computer Execution Control Variable
This variable controls the execution of the flow calculations.
Register Description
3165 Execution state
0 = not set (read only)
1 = stop
2 = run
Access
Read / Write
Meter Run 1 ID Variables
The Run ID is a string stored in 32 consecutive integers. Printable ASCII values in the range specified need to be used for each character in the string. The RUNID string will be terminated with a null unless the full length of the string is used.
Register Description
3167 Run 1 ID character 1 Range: 33 to 126
Access
Read / Write
3168
3169
3170
3171
3172
3173
3174
Run 1 ID character 2
Run 1 ID character 3
Run 1 ID character 7
Run 1 ID character 8
Range: 33 to 126
Range: 33 to 126
Range: 33 to 126
Range: 33 to 126
Read / Write
Read / Write
Run 1 ID character 4 Range: 33 to 126 Read / Write
Run 1 ID character 5 Range: 33 to 126 Read / Write
Run 1 ID character 6 Range: 33 to 126 Read / Write
Read / Write
Read / Write
3175
3176
3177
3178
3179
Run 1 ID character 9 Range: 33 to 126 Read / Write
Run 1 ID character 10 Range: 33 to 126 Read / Write
Run 1 ID character 11 Range: 33 to 126 Read / Write
Run 1 ID character 12 Range: 33 to 126 Read / Write
Run 1 ID character 13 Range: 33 to 126 Read / Write
Realflo User and Reference Manual
May 19, 2011
873
Enron Modbus Protocol Interface
Register Description
3180
3181
3182
3183
Run 1 ID character 14 Range: 33 to 126
Run 1 ID character 15 Range: 33 to 126
Run 1 ID character 16 Range: 33 to 126
Run 1 ID character 17 Range: 33 to 126
Access
Read / Write
Read / Write
Read / Write
Read/Write
3184
3185
3186
3187
3188
3189
3190
3191
3192
3193
3194
3195
3196
3197
3198
Run 1 ID character 18 Range: 33 to 126 Read/Write
Run 1 ID character 19 Range: 33 to 126 Read/Write
Run 1 ID character 20 Range: 33 to 126 Read/Write
Run 1 ID character 21 Range: 33 to 126 Read/Write
Run 1 ID character 22 Range: 33 to 126 Read/Write
Run 1 ID character 23 Range: 33 to 126 Read/Write
Run 1 ID character 24 Range: 33 to 126 Read/Write
Run 1 ID character 25 Range: 33 to 126 Read/Write
Run 1 ID character 26 Range: 33 to 126 Read/Write
Run 1 ID character 27 Range: 33 to 126 Read/Write
Run 1 ID character 28 Range: 33 to 126 Read/Write
Run 1 ID character 29 Range: 33 to 126 Read/Write
Run 1 ID character 30 Range: 33 to 126 Read/Write
Run 1 ID character 31 Range: 33 to 126 Read/Write
Run 1 ID character 32 Range: 33 to 126 Read/Write
Meter Run 1 Contract Configuration Variables
The Contract Configuration variables define the gas measurement contract.
Changes to the Contract Configuration are not allowed while the flow calculation is running.
Register Description
7146
7147
7148
7149
7150
7293
Output and log units type:
0 = US1
1 = US2
2 = US3
3 = Imperial
4 = Metric1
5 = Metric2
6 = Metric3
7 = SI
8 = US4
9 = US5
10= US6
11 = US7
12= US8
Contract hour
Range: 0 to 23
Base temperature
Base static pressure
Input Error Action
0 = do not accumulate flow when inputs in error
1 = accumulate flow when inputs in error
Wet gas meter factor
Version 6.10 or greater.
Default value is 1.0.
The value 0.0 indicates that the parameter
Access
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Realflo User and Reference Manual
May 19, 2011
874
Register Description
Enron Modbus Protocol Interface
Access
is not supported and that 1.0 should be substituted for it.
Meter Run 1 AGA-3 Configuration Variables
AGA-3 configuration variables define the AGA-3 calculation.
Register Description
7151
7152
7153
7154
7155
7156
7157
7158
7159
7160
7161
Orifice material
0 = stainless,
1 = Monel,
2 = carbon steel
Pipe material
0 = stainless,
1 = Monel,
2 = carbon steel
Orifice diameter
Reference temperature for orifice measurement
Pipe diameter
Reference temperature for pipe diameter measurement
Isentropic exponent
Viscosity
Temperature dead band
Static pressure dead band
Differential pressure dead band
Access
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Meter Run 1 V-Cone Configuration Variables
V-Cone configuration variables define the V-Cone calculation.
In the original McCrometer V-Cone Application Sizing sheet that is included with V-Cone meters uses the terminology Cd (discharge coefficient) rather than Cf (flow coefficient). You will need to use the Re and Cd values from the V-Cone Application Sizing sheet for the Re and Cf entries. If the Re value is the same for each entry in the table only the first pair is used.
McCrometer now supplies one value of Cd in the sizing document. You need to enter one Re/Cd pair only. See the McCrometer Application Sizing sheet for the Re/Cd pair for your meter.
Register Description
7162
7163
7164
7165
7166
7167
V-Cone material
2 = carbon steel
3 = stainless 304
4 = stainless 316
Pipe material
2 = carbon steel
3 = stainless 304
4 = stainless 316
Cone diameter
Reference temperature for cone diameter measurement.
Inside meter diameter
Reference temperature for inside meter
Access
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Realflo User and Reference Manual
May 19, 2011
875
Register Description
7168
7169
7170
7171
7172
7173
7174
7175
7176
7177
7178
7179
7180
7181
7182
7183
7184
7185
7186
7187
7188
7189
7190 diameter measurement
Isentropic exponent
Viscosity
Number of points
Point 1 Reynolds number
Range: 0.1 to 200000000
Point 1 Coefficient
Range: 0 to 10
Point 2 Reynolds number
Range: 0.1 to 200000000
Point 2 Coefficient
Range: 0 to 10
Point 3 Reynolds number
Range: 0.1 to 200000000
Point 3 Coefficient
Range: 0 to 10
Point 4 Reynolds number
Range: 0.1 to 200000000
Point 4 Coefficient
Range: 0 to 10
Point 5 Reynolds number
Range: 0.1 to 200000000
Point 5 Coefficient
Range: 0 to 10
Point 6 Reynolds number
Range: 0.1 to 200000000
Point 6 Coefficient
Range: 0 to 10
Point 7 Reynolds number
Range: 0.1 to 200000000
Point 7 Coefficient
Range: 0 to 10
Point 8 Reynolds number
Range: 0.1 to 200000000
Point 8 Coefficient
Range: 0 to 10
Point 9 Reynolds number
Range: 0.1 to 200000000
Point 9 Coefficient
Range: 0 to 10
Point 10 Reynolds number
Range: 0.1 to 200000000
Point 10 Coefficient
Range: 0 to 10
Enron Modbus Protocol Interface
Access
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Meter Run 1 AGA-7 Configuration Variables
AGA-7 Configuration variables define the AGA-7 calculation.
Register Description
7191
7192
K factor
Range: 0.001 to 1000000
M factor
Access
Read / Write
Read / Write
Realflo User and Reference Manual
May 19, 2011
876
Register Description
Range: 0.001 to 1000
Enron Modbus Protocol Interface
Access
Meter Run 1 AGA-8 Configuration Variables
Mole Fractions
AGA-8 Configuration variables define the gas quality for each run. The gas is made up of a number of components. These components are represented as fraction values, i.e. 0 to 1.0000.
Realflo checks the validity of the entered components using the following limits:
Individual components are in the ranges listed in the table above.
The Total of all Components field displays the sum of all components.
The total of all components needs to be 1.0000 (+/- 0.00001) if
Composition Units is set to Mole Fractions or 100% (+/- 0.00001%) if
Composition Units is set to Percent.
The n-hexane register contains the fraction of hexane when individual gas components are used. The register contains the fraction of the high-carbon gases combined. The high-carbon gases are n-hexane, n-heptane, noctane, n-nonane, and n-decane. Together they are known as Hexanes+.
In Flow Computer versions 6.73 and older, when gas ratios are written to the flow computer the new gas ratios are saved in temporary memory, not the Enron Modbus registers, until a new Density calculation is started with the new values. Once a density calculation is started by the flow computer the Enron Modbus registers are then loaded with the new gas ratios. The new gas ratios are not available to SCADA host software reading the Enron
Modbus registers until a new density calculation is started with the new values.
In Flow Computer versions 6.74 and newer when gas ratios are written to the flow computer the new gas ratios are updated in the Enron Modbus registers. This allows a SCADA host to immediately confirm the new ratios were written to the flow computer. The new gas ratios are not used by the flow computer until a new density calculation is started.
Register Description
7193
7194
7195
7196
7197
7198
7199
7200
Methane below
Nitrogen below
Carbon Dioxide below
Ethane below
Propane below
Water below
Hydrogen Sulphide below
Hydrogen below
Range: see table
Range: see table
Range: see table
Range: see table
Range: see table
Range: see table
Range: see table
Range: see table
Access
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Realflo User and Reference Manual
May 19, 2011
877
Enron Modbus Protocol Interface
Register Description
7201
7202
7203
7204
7205
7206
7207
7208
7209
7210
7211
7212
7213
7219
7280
7281
Carbon Monoxide below
Oxygen below i-butane below n-butane below i-pentane below n-pentane below
Range: see table
Range: see table
Range: see table
Range: see table
Range: see table
Range: see table n-hexane (when using individual gas components) n-hexane + (when using combined value for hexane and higher components)
Range: see table n-heptane below n-octane below n-nonane below
Range: see table
Range: see table n-decane below
Helium below
Argon below
Range: see table
Range: see table
Range: see table
Composition logging control
0 = log composition changes
1 = do not log composition changes
0 = calculate real relative density
0.07 to 1.52 = use as laboratory value for real relative density
0 = calculate heating value other values = use as laboratory value for heating value
0 to 1800 BTU(60)/ft
3
0 to 67.066 MJ/m
0 to 67066 J/m
3
3
Access
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
There is no single valid range for each component. There are two ranges for each gas component in the table below. The flow computer accepts any value in the Expanded Range. Only values in the Normal Range will work in all circumstances.
The run-time error message
“Bracket derivative negative” occurs when the combination of the components at the current pressure and temperature results in an error. The AGA-8 calculation will produce a result even if the error occurs, but the accuracy of the result will be suspect.
Component
Methane CH
4
Nitrogen
Normal Range
0.4500 to 1.0000
0 to 0.5000
Expanded Range
0 to 1.0000
0 to 1.0000
Realflo User and Reference Manual
May 19, 2011
878
Component
Carbon Dioxide
Ethane C
2
H
6
Propane C
3
H
8
Water
Hydrogen Sulphide
Hydrogen
Carbon Monoxide
Oxygen
Total Butanes i-Butane n-Butane
Total Pentanes i-Pentane n-Pentane
Total Hexane to Decane n-Hexane n-Heptane n-Octane n-Nonane n-Decane
Helium
Argon
0 to 0.3000
0 to 0.1000
0 to 0.0400
0 to 0.0005
0 to 0.0002
0 to 0.1000
0 to 0.0300
0
0 to 0.0100
0 to 0.0300
0 to 0.0200
0 to 0.0200
0
Enron Modbus Protocol Interface
Normal Range Expanded Range
0 to 1.0000
0 to 1.0000
0 to 0.1200
0 to 0.0300
0 to 1.0000
0 to 1.0000
0 to 0.0300
0 to 0.2100
0 to 0.0600
0 to 0.0400
0 to 0.0400
0 to 0.0300
0 to 0.0100
Percentages
AGA-8 Configuration variables define the gas quality for each run. The gas is made up of a number of components. These components can be represented as percentage values (i.e. 0 to 100.00 %) instead of mole fractions.
The n-hexane register contains the percentage of hexane when individual gas components are used. The register contains the percentage of the highcarbon gases combined. The high-carbon gases are n-hexane, n-heptane, n-octane, n-nonane, and n-decane. Together they are known as Hexanes+.
The gas quality values are floating point numbers. The sum of the values in the gas quality needs to equal 100.
Register Description
7253
7254
7255
7256
7257
7258
7259
7260
7261
7262
7263
7264
7265
7266
Methane
Nitrogen
Carbon Dioxide Range: see table below
Ethane
Propane
Water below
Range: see table below
Range: see table below
Range: see table below
Range: see table below
Range: see table below
Hydrogen Sulphide Range: see table
Hydrogen
Carbon Monoxide below
Range: see table below
Range: see table
Oxygen i-butane n-butane i-pentane n-pentane
Range: see table below
Range: see table below
Range: see table below
Range: see table below
Range: see table below
Access
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Realflo User and Reference Manual
May 19, 2011
879
Enron Modbus Protocol Interface
7268
7269
7270
7271
7272
7273
7219
Register Description
7267 n-hexane (when using individual gas components) n-hexane + (when using combined value for hexane and higher components) n-heptane Range: see table below n-octane n-nonane n-decane
Range: see table below
Range: see table below
Range: see table below
Helium
Argon
Range: see table below
Range: see table below
Composition logging control
0 = log composition changes
1 = do not log composition changes
Component
Methane CH
4
Nitrogen
Carbon Dioxide
Ethane C
2
H
6
Propane C
3
H
8
Water
Hydrogen Sulphide
Hydrogen
Carbon Monoxide
Oxygen
Total Butanes i-Butane n-Butane
Total Pentanes i-Pentane n-Pentane
Total Hexane to Decane n-Hexane n-Heptane n-Octane n-Nonane n-Decane
Helium
Argon
Normal Range
45.00 to 100.00
0 to 50.00
0 to 30.00
0 to 10.00
0 to 4.00
0 to 0.05
0 to 0.02
0 to 10.00
0 to 3.00
0
0 to 1.00
0 to 3.00
0 to 2.00
0 to 2.00
0
Access
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
There is no single valid range for each component. There are two ranges for each gas component in the table below. The flow computer accepts any value in the Expanded Range. Only values in the Normal Range will work in all circumstances.
The run-time error message
“Bracket derivative negative” occurs when the combination of the components at the current pressure and temperature results in an error. The AGA-8 calculation will produce a result even if the error occurs, but the accuracy of the result is susspect.
Expanded Range
0 to 100.00
0 to 100.00
0 to 100.00
0 to 100.00
0 to 12.00
0 to 3.00
0 to 100.00
0 to 100.00
0 to 3.00
0 to 21.00
0 to 6.00
0 to 4.00
0 to 4.00
0 to 3.00
0 to 1.00
Hexane + Ratios Percentages
These registers control if individual or combined gas components are used, and contain the ratio of the five high-carbon gases for the combined method.
Realflo User and Reference Manual
May 19, 2011
880
Enron Modbus Protocol Interface
If combined high-carbon gases are used, the ratios of the five gases nhexane, n-heptane, n-octane, n-nonane, and n-decane needs to sum to 100 percent. The percentage of the overall gas represented by these components combined is set in register 7267.
Register Description
7274
7275
7276
7277
7278
7279
Set AGA-8 Hexane + Component method
0 = Use individual gas components (default)
1 = Use combined value for hexane and higher components.
Set AGA-8 Hexane + Ratio for n-hexane
Set AGA-8 Hexane + Ratio for n-heptane
Set AGA-8 Hexane + Ratio for n-octane
Set AGA-8 Hexane + Ratio for n-nonane
Set AGA-8 Hexane + Ratio for n-decane
Access
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Meter Run 1 NX-19 Configuration Variables
NX-19 configuration variables define the gas quality for the NX-19 calculation method.
In Flow Computer versions 6.73 and older, when NX-19 gas quality values are written to the flow computer the new values are saved in temporary memory, not the Enron Modbus registers, until a new Density calculation is started with the new values. Once a density calculation is started by the flow computer the Enron Modbus registers are then loaded with the new NX-19 gas quality values. The new values are not available to SCADA host software reading the Enron Modbus registers until a new density calculation is started with the new values.
In Flow Computer versions 6.74 and newer when NX-19 gas quality values are written to the flow computer the new NX-19 gas quality values are updated in the Enron Modbus registers. This allows a SCADA host to immediately confirm the new values were written to the flow computer. The new NX-19 gas quality values are not used by the flow computer until a new density calculation is started.
Register Description
7214
7215
7216
7217
Specific gravity
Range: 0.0 to 10.0
Fraction of Carbon Dioxide
Range: 0.0 to 1.0
Fraction of Nitrogen
Range: 0.0 to 1.0
Heating Value
7218 Composition logging control
0 = log composition changes
1 = do not log composition changes
Access
Read / Write
Read / Write
Read / Write
Read / Write
Read / Write
Plate Change Events Variables
The Plate Change Events variables record plate change events. Events are created for these variables when the plate change occurs.
Reading these registers will return zero. The registers exist only to provide a reference for events in the event log.
Realflo User and Reference Manual
May 19, 2011
881
Enron Modbus Protocol Interface
Temperature Plate Change Event Variables
The temperature calibration event variables record calibration of the temperature input. The calibration needs to be done using Realflo. Events will be recorded for these variables when the calibration occurs.
Register Description
7315
7316
Start plate change: temperature
Stop plate change: temperature
Access
Read Only
Read Only
Static Pressure Plate Change Event Variables
The static pressure calibration event variables record calibration of the static pressure input. The calibration needs to be done using Realflo. Events will be recorded for these variables when the calibration occurs.
Register Description
7317
7318
Start plate change: static pressure
Stop plate change: static pressure
Access
Read Only
Read Only
Differential Pressure Plate Change Event Variables
The DP calibration event variables record calibration of the differential pressure input. The calibration needs to be done using Realflo. Events will be recorded for these variables when the calibration occurs.
Register Description
7319 Start plate change: DP
7320 Stop plate change: DP
Access
Read Only
Read Only
Enron Forcing Events Variables
The Forcing Events variables record force events. Events are created for these variables when the plate change occurs.
Reading these registers will return zero. The registers exist only to provide a reference for events in the event log.
Temperature Force Event Variables
The temperature force event variables record force of the temperature input.
The force needs to be done using Realflo. Events will be recorded for these variables when the force occurs.
Register Description
7321
7322
Forced temperature input
Removed forced temperature input
Access
Read Only
Read Only
Static Pressure Force Event Variables
The static pressure force event variables record force of the static pressure input. The force needs to be done using Realflo. Events will be recorded for these variables when the force occurs.
Register Description
7323
7324
Forced static pressure input
Removed forced static pressure input
Access
Read Only
Read Only
Realflo User and Reference Manual
May 19, 2011
882
Enron Modbus Protocol Interface
Differential Pressure Force Event Variables
The DP force event variables record force of the differential pressure input.
The force needs to be done using Realflo. Events will be recorded for these variables when the force occurs.
Register Description
7325
7326
Forced differential pressure input
Removed forced differential pressure input
Access
Read Only
Read Only
Counter Force Event Variables
The counter force event variables record force of the counter input. The force needs to be done using Realflo. Events will be recorded for these variables when the force occurs.
Access
Read Only
Read Only
Register Description
5155
5156
Forced pulse count rate
Removed forced pulse count rate
Meter Run 1 Flow Computer Events Variables
The flow computer event and alarm logs can be read as the Enron Modbus event/alarm log. The flow computer alarms events numbers are converted to changes in the Enron Modbus Variables. The tables below show the flow computer alarms/events and the corresponding Enron Modbus Variable.
Alarms and events correspond to variables used for reporting data or settings configuration. A small number of events and alarms don't have a corresponding variable. So that they can be reported in the Enron Modbus event/alarm log, variables have been created for them. These variables are read only and return zero. They exist only so events in the log have a corresponding variable.
Input Alarms Variables
The Input Alarms variables record alarms due to out of range inputs. Alarms are created for these variables when the error occurs. Reading these registers will return zero. The registers exist only to provide a reference for events in the event log.
Access
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Register Description
3106
3107
3108
3109
3110
3111
Temperature input low
Temperature input high
Static pressure low
Static pressure high
Differential pressure low
Differential pressure high
Register Description
4403
4404
4405
4406
4407
4408
Forced input register
Removed force from input register
Restore from temperature input low alarm
Access
Read Only
Read Only
Read Only
Restore from temperature input high alarm Read Only
Restore from static pressure input low alarm Read Only
Restore from static pressure input high Read Only
Realflo User and Reference Manual
May 19, 2011
883
Register Description
4409
4410
4411
4412
Enron Modbus Protocol Interface
Access
alarm
Restore from differential pressure input low alarm
Restore from differential pressure input high alarm
Restore from low pulse input alarm
Restore from input alarm
Read Only
Read Only
Read Only
Read Only
Compressibility Events Variables
The Compressibility Events variables record errors with the compressibility calculation. Events are created for these variables when the error occurs.
Reading these registers will return zero. The registers exist only to provide a reference for events in the event log.
Register Description
3112
Compressibility calculation inputs invalid
Access
Read Only
AGA-8 Variables
These compressibility event variables refer to the AGA-8 calculation only.
Reading these registers will return zero. The registers exist only to provide a reference for events in the event log.
Register Description
3113
3114
3115
3116
3117
3118
3119
3120
3121
3166
4413
4414
4416
Failed To Create AGA-8 Data Structure
Created AGA-8 with Execution Stopped
Created AGA-8 with Execution Running
Destroyed AGA-8 Data Structure
Clear Compressibility Error
Failed To Set AGA-8 Gas Fractions
Failed To Set AGA-8 Configuration
AGA-8 - Not configured
AGA-8 - No gas components
AGA-8
– Flow Pressure is Low
Density temperature low alarm
Density temperature high alarm
Density pressure high alarm
Access
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
NX-19 Variables
These compressibility event variables refer to the NX-19 calculation only.
Reading these registers will return zero. The registers exist only to provide a reference for events in the event log.
Register Description
3122
3123
3124
3125
3126
3127
3128
3129
3130
Failed to Create NX-19 Data Structure
Created NX-19 with Execution Stopped
Created NX-19 with Execution Running
Destroyed NX-19 Data Structure
Clear Compressibility Error
Access
Read Only
Read Only
Read Only
Read Only
Read Only
Failed to set NX-19 Gas Components Read Only
Failed to set NX-19 Contract Configuration Read Only
NX-19 - Configuration flag not set Read Only
NX-19 - Gas ratios were not available Read Only
Realflo User and Reference Manual
May 19, 2011
884
Enron Modbus Protocol Interface
Register Description
4413
4414
4415
4416
Density temperature low alarm
Density temperature high alarm
Density pressure low alarm
Density pressure high alarm
Access
Read Only
Read Only
Read Only
Read Only
Flow Events Variables
The Flow Events variables record errors with the flow calculation. Events are created for these variables when the error occurs.
Reading these registers will return zero. The registers exist only to provide a reference for events in the event log.
AGA-3 (1985) Variables
These compressibility event variables refer to the AGA-3 (1985) calculation only.
Register Description
3131
3132
Failed To Create AGA-3 (1985) Data
Structure
Created AGA-3 (1985) with Execution
Stopped
3133
3134
3135
3136
3137
3138
3139
4417
Created AGA-3 (1985) with Execution
Running
Destroyed AGA-3 (1985) Data Structure
Recovered from AGA-3 (1985) error
Failed To Set AGA-3 (1985) Configuration
AGA-3 (1985) - Ratios from AGA-8 or NX-19 were not available
AGA-3 (1985) - Static pressure below differential
AGA-3 (1985) - Static pressure zero or negative
Flow temperature low alarm
Access
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
AGA-3 (1992) Variables
These compressibility event variables refer to the AGA-3 (1992) calculation only.
Register
3140
3141
3142
3143
3144
3145
3146
3147
3148
Description
Failed To Create AGA-3 (1992) Data
Structure
Created AGA-3 (1992) with Execution
Stopped
Created AGA-3 (1992) with Execution
Running
Destroyed AGA-3 (1992) Data Structure
Restored from AGA-3 (1992) error
Failed To Set AGA-3 (1992) Configuration
AGA-3 (1992)
– Ratios from AGA-8 or NX-
19 were not available
AGA-3 (1992) - Static pressure below differential
AGA-3 (1992) - Static pressure zero or negative
Access
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Realflo User and Reference Manual
May 19, 2011
885
Register Description
4417 Flow temperature low alarm
Enron Modbus Protocol Interface
Access
Read Only
AGA-7 Variables
These compressibility event variables refer to the AGA-7 calculation only.
Register Description
3149
3150
3151
3152
3153
3154
3155
3156
4417
4418
Failed To Create AGA-7 Data Structure
Created AGA-7 with Execution Stopped
Created AGA-7 with Execution Running
Destroyed AGA-7 Data Structure
Restored from AGA-7 error
Failed To Set AGA-7 Configuration
AGA-7 - Low pulse rate
AGA-7 - Ratios from AGA-8 or NX-19 are not available
Flow temperature low alarm
Flow pressure low alarm
Access
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
V-Cone Variables
These compressibility event variables refer to the V-Cone calculation only.
Register Description
3157
3158
3159
3160
3161
3162
3163
3164
3199
4417
Failed To Create V-Cone Date Structure
Created V-Cone with Execution Stopped
Created V-Cone with Execution Running
Destroyed V-Cone Data Structure
Restored from V-Cone Error
Failed To Set V-Cone Configuration
V-Cone
– Ratios from AGA-8 or NX-19 were not available
V-Cone
– Static pressure below differential pressure
V-Cone
– Static pressure zero or negative
Flow temperature low alarm
Access
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Calibration Events Variables
Temperature Calibration Event Variables
The temperature calibration event variables record calibration of the temperature input. The calibration needs to be done using Realflo. Events will be recorded for these variables when the calibration occurs.
Register Description
7300 Start temperature calibration
7301
7302
7303
7304
Continue temperature calibration
Temperature as found
Temperature as left
Stop temperature calibration
Access
Read Only
Read Only
Read Only
Read Only
Read Only
Static Pressure Calibration Event Variables
The static pressure calibration event variables record calibration of the static pressure input. The calibration needs to be done using Realflo. Events will be recorded for these variables when the calibration occurs.
Realflo User and Reference Manual
May 19, 2011
886
Enron Modbus Protocol Interface
Register Description
7305
7306
7307
7308
7309
Start static pressure calibration
Continue static pressure calibration
Static pressure as found
Static pressure as left
Stop static pressure calibration
Access
Read Only
Read Only
Read Only
Read Only
Read Only
Differential Pressure Calibration Event Variables
The DP calibration event variables record calibration of the differential pressure input. The calibration needs to be done using Realflo. Events will be recorded for these variables when the calibration occurs.
Register Description
7310
7311
7312
7313
7314
Start DP calibration
Continue DP calibration
Differential pressure as found
Differential pressure as left
Stop DP calibration
Access
Read Only
Read Only
Read Only
Read Only
Read Only
Counter Calibration Event Variables
The counter calibration event variables record calibration of the counter input. The calibration needs to be done using Realflo. Events will be recorded for these variables when the calibration occurs.
Register Description
5150 Start counter calibration
5151
5152
5153
5154
Continue counter calibration
Counter as found
Counter as left
Stop counter calibration
Access
Read Only
Read Only
Read Only
Read Only
Read Only
Meter Run 2 Data Variables
Meter run 2 data variables use the same structure as Meter run 1 data variables described above. Meter run 2 variables are offset from Meter run 1 variables according to the following table.
Range Data Type Description
3200 - 3299 Short integer Meter Run 2 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 100
5200 - 5299 Long integer Meter Run 2 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 100
7350 - 7599 Float Meter Run 2 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 250
Meter Run 3 Data Variables
Meter run 3 data variables use the same structure as Meter run 1 data variables described above. Meter run 3 variables are offset from Meter run 1 variables according to the following table.
Realflo User and Reference Manual
May 19, 2011
887
Enron Modbus Protocol Interface
Range Data Type Description
3300 - 3399 Short integer Meter Run 3 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 200
5300 - 5399 Long integer Meter Run 3 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 200
7600
– 7849
Float Meter Run 3 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 500
Meter Run 4 Data Variables
Meter run 4 data variables use the same structure as Meter run 1 data variables described above. Meter run 4 variables are offset from Meter run 1 variables according to the following table.
Range Data Type Description
3400 - 3499 Short integer Meter Run 4 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 300
5400 - 5499 Long integer Meter Run 4 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 300
7850 - 8099 Float Meter Run 2 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 750
Meter Run 5 Data Variables
Meter run 5 data variables use the same structure as Meter run 1 data variables described above. Meter run 5 variables are offset from Meter run 1 variables according to the following table.
Range Data Type Description
3500 - 3599 Short integer Meter Run 5 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 400
5500 - 5599 Long integer Meter Run 5 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 400
8100 - 8349 Float Meter Run 5 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 1000
Realflo User and Reference Manual
May 19, 2011
888
Enron Modbus Protocol Interface
Meter Run 6 Data Variables
Meter run 6 data variables use the same structure as Meter run 1 data variables described above. Meter run 6 variables are offset from Meter run 1 variables according to the following table.
Range Data Type Description
3600 - 3699 Short integer Meter Run 6 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 500
5600 - 5699 Long integer Meter Run 6 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 500
8350 - 8599 Float Meter Run 6 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 1250
Meter Run 7 Data Variables
Meter run 7 data variables use the same structure as Meter run 1 data variables described above. Meter run 7 variables are offset from Meter run 1 variables according to the following table.
Range Data Type Description
3700 - 3799 Short integer Meter Run 7 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 600
5200 - 5299 Long integer Meter Run 7 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 600
8600 - 8849 Float Meter Run 7 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 1500
Meter Run 8 Data Variables
Meter run 8 data variables use the same structure as Meter run 1 data variables described above. Meter run 8 variables are offset from Meter run 1 variables according to the following table.
Range Data Type Description
3800 - 3899 Short integer Meter Run 8 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 700
5800 - 5899 Long integer Meter Run 8 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 700
Realflo User and Reference Manual
May 19, 2011
889
Range Data Type
8850 - 9099 Float
Enron Modbus Protocol Interface
Description
Meter Run 8 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 1750
Meter Run 9 Data Variables
Meter run 9 data variables use the same structure as Meter run 1 data variables described above. Meter run 9 variables are offset from Meter run 1 variables according to the following table.
Range Data Type Description
3900 - 3999 Short integer Meter Run 9 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 800
5900 - 5999 Long integer Meter Run 9 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 800
9100
– 9349
Float Meter Run 9 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 2000
Meter Run 10 Data Variables
Meter run 10 data variables use the same structure as Meter run 1 data variables described above. Meter run 10 variables are offset from Meter run
1 variables according to the following table.
Range Data Type Description
4000
– 4099
Short integer Meter Run 10 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 900
6000
– 6099
Long integer Meter Run 10 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 900
9350
– 9599
Float Meter Run 10 Data Variables
Identical structure to Meter Run 1
Data Variables.
Offset by value of 2250
MVT-1 Data and Configuration Variables
The flow computer polls the MVT transmitters and updates the data registers.
The sensor status values are the same for each transmitter.
0 = response OK
1 = communication failed
2 = value below operating limit
Realflo User and Reference Manual
May 19, 2011
890
Enron Modbus Protocol Interface
3 = transmitter configuration invalid
4 = not polled, may be disabled
5 = bad value
6 = value above operating limit
7 = sensor is off line, may be calibrating
8 = RTD cut (temperature sensor only)
Register Description
4100
4101
4102
Transmitter 1: differential pressure sensor status
Transmitter 1: static pressure sensor status
Transmitter 1: temperature pressure sensor status
Access
Read Only
Read Only
Read Only
These registers show the current inputs.
Register Description
9600
9601
Transmitter 1: differential pressure
Transmitter 1: static pressure
9602 Transmitter 1: temperature
Access
Read Only
Read Only
Read Only
MVT-1 MVT Configuration Variables
MVT configuration defines the operation of the MVT transmitter and polling by the flow computer.
Register Description
9603
9604
Transmitter polling status
0 = disabled
1 = enabled
Serial Port:
0 = unused, for internal SCADAPack 4202 or 4203 in slot 1
1 = com1
2 = com2
3 = com3
4 = com4
100 = LAN (4102, 4000 only)
9605
9606
Address of transmitter:
0 = unused, for internal SCADAPack 4202 or 4203 in slot 1
1 to 247 (Rosemount 3095FB, 4101)
1 to 255 (4102, SCADAPack 4202 or 4203 standard mode)
1 to 65534 (SCADAPack 4000,
SCADAPack 4202 or 4203 extended mode)
Timeout:
0 = unused, for internal SCADAPack 4202 or 4203 in slot 1
10 to 10000 ms
Access
Read / Write
Read / Write
Read / Write
Read / Write
Realflo User and Reference Manual
May 19, 2011
891
Enron Modbus Protocol Interface
Register Description
9607
9608
9609
9610
9611
9612
9613
9614
9615
9616
9617
9618
9619
9620
Manufacturer Code
Turnaround Delay Time: 0 to 200 ms
(3095FB only)
Differential Pressure units:
1 = inches of water at 60°F (3095FB only)
2 = Pascal
3 = kiloPascal
6 = inches of water at 68°F
Static Pressure units:
3 = kiloPascal
4 = megaPascal
5 = psi
Access
Read / Write
Read / Write
Read / Write
Read / Write
Temperature units:
20 = Celsius
21 = Fahrenheit
Differential Pressure damping:
3095FB:
0.108, 0.216, 0.432, 0.864, 1.728, 3.456,
6.912, 13.824, or 27.648
SCADAPack 4000 and SCADAPack 4202 or 4203:
0.0 (damping off), 0.5, 1.0, 2.0, 4.0, 8.0,
16.0, or 32.0 seconds
Read / Write
Read / Write
Differential Pressure upper operating limit Read / Write
Differential Pressure lower operating limit Read / Write
Read / Write Static Pressure damping:
3095FB:
0.108, 0.216, 0.432, 0.864, 1.728, 3.456,
6.912, 13.824, or 27.648
SCADAPack 4000 and SCADAPack 4202 or 4203:
0.0 (damping off), 0.5, 1.0, 2.0, 4.0, 8.0,
16.0, or 32.0 seconds
Read / Write
Read / Write
Read / Write
Static Pressure upper operating limit
Static Pressure lower operating limit
Temperature damping:
3095FB:
0.108, 0.216, 0.432, 0.864, 1.728, 3.456,
6.912, 13.824, or 27.648
SCADAPack 4000 and SCADAPack 4202 or 4203:
Not supported
Temperature upper operating limit
Temperature lower operating limit
Read / Write
Read / Write
Realflo User and Reference Manual
May 19, 2011
892
Register Description
9621
9622
Type Code (not used with SCADAPack
4101)
31 = 3095FB MVT
Enron Modbus Protocol Interface
Type Code (not used with SCADAPack
4101)
31 = 3095FB MVT
40120 = 4012 Absolute
40121 = 4012 Gauge
40320 = 4032
41020 = 4102 Serial
41021 = 4102 Serial and LAN
4202 = 4202 DR
42021 = 4202 DS
42990 = 4203 DR
42991 = 4203 DS
Atmospheric pressure (used by
SCADAPack 4102 and SCADAPack 4202 or 4203)
0 = absolute pressure
>0 to 30 psia (or equivalent) = gage pressure
Register Description
6100
6101
Serial number (3095FB only)
IP Address (SCADAPack 4000 and
SCADAPack 4202 or 4203 only)
Access
Read / Write
Read/Write
Access
Read
Read / Write
Register Description
4103
4104
4105
4106
4107
4108
4109
4110
Tag character 1
Tag character 2
Tag character 3
Tag character 4
Tag character 5
Tag character 6
Tag character 7
Tag character 8
Access
Range: 32 to 126 Read / Write
Range: 32 to 126 Read / Write
Range: 32 to 126 Read / Write
Range: 32 to 126 Read / Write
Range: 32 to 126 Read / Write
Range: 32 to 126 Read / Write
Range: 32 to 126 Read / Write
Range: 32 to 126 Read / Write
MVT-1 Events Variables
The MVT Events variables record changes in the MVT configuration. Events will be recorded for these variables when the corresponding status changes.
Reading these registers will return zero. The registers exist only to provide a reference for events in the event log.
Register Description
4111
4112
4113
4114 recovered from MVT error
MVT Transmitter 1: lost communication
MVT Transmitter 1: transmitter configuration incorrect
MVT Transmitter 1: temperature sensor out of range
Access
Read Only
Read Only
Read Only
Read Only
Realflo User and Reference Manual
May 19, 2011
893
Enron Modbus Protocol Interface
Register Description
4115
4116
4117
4118
4119
4120
4121
4122
4123
4124
MVT Transmitter 1: static pressure sensor out of range
MVT Transmitter 1: differential pressure sensor out of range
MVT Transmitter 1: not polled
Manufacture date:
This is stored as bits in the format
YYYYYYYMMMMDDDDD, where these bits correspond to Year+1986/Month/Day.
(SCADAPack 4101 or 4102 and
SCADAPack 4202 or 4203 only)
Core number (SCADAPack 4101 or 4102 and SCADAPack 4202 or 4203 only)
Access
Read Only
Read Only
Read Only
Read Only
Read Only
IP Protocol (SCADAPack 4102, 4000 only) Read / Write
Bad temperature sensor value Read Only
Bad static pressure sensor value
Bad differential pressure value
Restore for all communication alarms
Read Only
Read Only
Read Only
4125 Restore for all alarms Read Only
4126
4127
4700
4701
4702
4703
Sensors are Off Line
RTD Disconnected
Temperature sensor above range
Static Pressure sensor above range
Read Only
Read Only
Read Only
Read Only
Differential Pressure sensor above range Read Only
4704
4705
Temperature sensor below range
Static Pressure sensor below range
Read Only
Read Only
Differential Pressure sensor below range Read Only
MVT-2 Data and Configuration Variables
MVT-2 Data Variables use the same structure as MVT-1 Data Variables described above. MVT-2 Data Variables are offset from MVT-1 Data
Variables according to the following table.
Range Data Type Description
4130
– 4159
Short integer MVT-2 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 30
4730 - 4735 Short integer MVT-2 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 30
6130
– 6159
Long integer MVT-2 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 30
9630
– 9659
Float MVT-2 Data Variables
Identical structure MVT-1 Data
Variables.
Offset by value of 30
Realflo User and Reference Manual
May 19, 2011
894
Enron Modbus Protocol Interface
MVT-3 Data and Configuration Variables
MVT-3 Data Variables use the same structure as MVT-1 Data Variables described above. MVT-3 Data Variables are offset from MVT-1 Data
Variables according to the following table.
Range Data Type Description
4160
– 4189
Short integer MVT-3 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 60
4760 - 4765 Short integer MVT-2 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 30
6160
– 6159
Long integer MVT-3 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 60
9660
– 9689
Float MVT-3 Data Variables
Identical structure MVT-1 Data
Variables.
Offset by value of 60
MVT-4 Data and Configuration Variables
MVT-4 Data Variables use the same structure as MVT-1 Data Variables described above. MVT-4 Data Variables are offset from MVT-1 Data
Variables according to the following table.
Range Data Type Description
4190
– 4219
Short integer MVT-4 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 90
4790 - 4795 Short integer MVT-2 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 30
6190
– 6219
Long integer MVT-4 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 90
9690
– 9719
Float MVT-4 Data Variables
Identical structure MVT-1 Data
Variables.
Offset by value of 90
MVT-5 Data and Configuration Variables
MVT-5 Data Variables use the same structure as MVT-1 Data Variables described above. MVT-5 Data Variables are offset from MVT-1 Data
Variables according to the following table.
Range Data Type Description
4220
– 4249
Short integer MVT-5 Data Variables
Realflo User and Reference Manual
May 19, 2011
895
Enron Modbus Protocol Interface
Range Data Type Description
Identical structure to MVT-1 Data
Variables.
Offset by value of 120
4820 - 4825 Short integer MVT-2 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 30
6220
– 6249
Long integer MVT-5 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 120
9720
– 9749
Float MVT-5 Data Variables
Identical structure MVT-1 Data
Variables.
Offset by value of 120
MVT-6 Data and Configuration Variables
MVT-6 Data Variables use the same structure as MVT-1 Data Variables described above. MVT-6 Data Variables are offset from MVT-1 Data
Variables according to the following table.
Range Data Type Description
4250
– 4279
Short integer MVT-6 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 150
4850 - 4855 Short integer MVT-2 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 30
6250
– 6279
Long integer MVT-6 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 150
9750
– 9779
Float MVT-6 Data Variables
Identical structure MVT-1 Data
Variables.
Offset by value of 150
MVT-7 Data and Configuration Variables
MVT-7 Data Variables use the same structure as MVT-1 Data Variables described above. MVT-7 Data Variables are offset from MVT-1 Data
Variables according to the following table.
Range Data Type Description
4280
– 4309
Short integer MVT-7 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 180
4890 - 4895 Short integer MVT-2 Data Variables
Identical structure to MVT-1 Data
Variables.
Realflo User and Reference Manual
May 19, 2011
896
Enron Modbus Protocol Interface
Range Data Type Description
Offset by value of 30
6280
– 6309
Long integer MVT-7 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 180
9780
– 9809
Float MVT-7 Data Variables
Identical structure MVT-1 Data
Variables.
Offset by value of 180
MVT-8 Data and Configuration Variables
MVT-8 Data Variables use the same structure as MVT-1 Data Variables described above. MVT-8 Data Variables are offset from MVT-1 Data
Variables according to the following table.
Range Data Type Description
4310
– 4339
Short integer MVT-8 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 210
4920 - 4925 Short integer MVT-2 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 30
6310
– 6339
Long integer MVT-8 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 210
9810
– 9839
Float MVT-8 Data Variables
Identical structure MVT-1 Data
Variables.
Offset by value of 210
MVT-9 Data and Configuration Variables
MVT-9 Data Variables use the same structure as MVT-1 Data Variables described above. MVT-9 Data Variables are offset from MVT-1 Data
Variables according to the following table.
Range Data Type Description
4340
– 4369
Short integer MVT-9 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 240
4950 - 4955 Short integer MVT-2 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 30
6340
– 6369
Long integer MVT-9 Data Variables
Identical structure to MVT-1 Data
9840
– 9869
Float
Variables.
Offset by value of 240
MVT-9 Data Variables
Realflo User and Reference Manual
May 19, 2011
897
Range
Enron Modbus Protocol Interface
Data Type Description
Identical structure MVT-1 Data
Variables.
Offset by value of 240
MVT-10 Data and Configuration Variables
MVT-10 Data Variables use the same structure as MVT-1 Data Variables described above. MVT-10 Data Variables are offset from MVT-1 Data
Variables according to the following table.
Range Data Type Description
4370
– 4399
Short integer MVT-10 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 270
4980 - 4985 Short integer MVT-2 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 30
6370
– 6399
Long integer MVT-10 Data Variables
Identical structure to MVT-1 Data
Variables.
Offset by value of 270
9870
– 9899
Float MVT-10 Data Variables
Identical structure MVT-1 Data
Variables.
Offset by value of 270
Realflo User and Reference Manual
May 19, 2011
898
Enron Modbus Protocol Interface
Event and Alarm Log
The flow computer event and alarm logs can be read as the Enron Modbus event/alarm log. The flow computer alarms events numbers are converted to changes in the Enron Modbus Variables. The tables below show the flow computer alarms/events and the corresponding Enron Modbus Variable.
Alarms and events correspond to variables used for reporting data or settings configuration. A small number of events and alarms don't have a corresponding variable. So that they can be reported in the Enron Modbus event/alarm log, variables have been created for them. These variables are read only and return zero. They exist only so events in the log have a corresponding variable.
In the following tables, some variables are described with an offset. The offset is determined by the flow run.
Run
6
7
8
9
10
1
2
3
4
5
Short Integer
Offset
0
100
200
300
400
500
600
700
800
900
Long Integer
Offset
0
100
200
300
400
500
600
700
800
900
Float Offset
0
250
500
750
1000
1250
1500
1750
2000
2250
The flow computer logs contain information that needs to be mapped into the Enron Modbus event format.
The Event ID is mapped into the change bit map and the register number.
The Sequential event or alarm number is not reported.
The User number is not reported directly, as there is no field. There is a bit indicating the source of the alarm or event as the operator or the flow computer. The user number is mapped into this.
The date of event or alarm is converted to the Enron date format.
The time of event or alarm is converted to the Enron time format.
The new data associated with the event or alarm is reported in the alarm/event.
The previous data associated with the event or alarm is reported in the alarm/event.
The Enron interface assumes that there is one log for all of the flow runs. It contains alarms and events. Alarms and events have similar but not identical formats. Alarms and events are returned in the same response to a command.
Alarms and events cannot be read after they have been acknowledged. This happens immediately after they are read from the flow computer.
Realflo User and Reference Manual
May 19, 2011
899
Enron Modbus Protocol Interface
Enron and Realflo are not expected to work together. However they will coexist if the Read All Events option is selected when reading events using
Realflo. This allows alarms and events can be read by Enron Modbus correctly.
The existing alarm and event logs will be enhanced to support the Enron functionality and interface. This will include new data items and new access functions. The changes need to still permit alarms and events to be read via
Enron and by Realflo without losing any. The logs will mark the read records as inaccessible, to the Enron interface, when the log is acknowledged.
Global Alarms and Events
The gas flow computation engine creates these events.
10014
10015
10016
10017
10018
10019
10020
10021
10022
10023
10024
10001
10002
10003
10004
10005
10006
10007
10008
10009
10010
10011
10012
10013
10025
10026
10027
10028
10029
10030
10031
10032
10033
10034
10035
10036
10037
Number Description Enron
Variable
Power On - Cold Boot
Power On
– Warm Boot
Lost Events
Recovered from Input Error
Set Input: Units Type
1001
1002
3103 + offset
1100 + offset
7100 + offset
Set Input: Flow Calculation Type 7101 + offset
Set Input: Compressibility Calculation Type 7102 + offset
Set Input: Temperature Register 7106 + offset
Set Input: Temperature Input at Zero Scale 7107 + offset
Set Input: Temperature Input at Full Scale 7108 + offset
Set Input: Temperature at Zero Scale 7111 + offset
Set Input: Temperature at Full Scale
Set Input: Pressure Register
7112 + offset
7118 + offset
Set Input: Pressure Input at Zero Scale
Set Input: Pressure Input at Full Scale
Set Input: Pressure at Zero Scale
Set Input: Pressure at Full Scale
Set Input: DP Register
Set Input: DP Input at Zero Scale
Set Input: DP Input at Full Scale
Set Input: DP at Zero Scale
Set Input: DP at Full Scale
Set Contract: Units Type
Set Contract: Base Temperature
7119 + offset
7120 + offset
7123 + offset
7124 + offset
7130 + offset
7131 + offset
7132 + offset
7135 + offset
7136 + offset
7146 + offset
7148 + offset
Set Contract: Base Pressure
Set Input: Atmospheric Pressure
Set Input: Static Pressure Tap Location
Set Contract: Contract Hour
Change Execution State
Set RTC Year
Set RTC Month
Set RTC Day
Set RTC Hour
Set RTC Minute
Set RTC Second
Set Input: Temperature Low Level Cutoff
Set Input: Temperature Low Level hysteresis
7149 + offset
7145 + offset
7103 + offset
7147 + offset
3165 + offset
3011
3012
3013
3014
3015
3016
7113 + offset
7114 + offset
Realflo User and Reference Manual
May 19, 2011
900
Enron Modbus Protocol Interface
10066
10067
10068
10069
10071
10072
10073
10074
10076
10077
10055
10056
10057
10058
10059
10060
10061
10062
10063
10064
10065
Number
10038
10039
10040
10041
10042
10043
10044
10046
10047
10048
10049
10050
10051
10052
10053
10054
10078
10079
Description Enron
Variable
Set Input: Temperature High Level Cutoff
Set Input: Temperature High Level
Hysteresis
Set Input: Pressure Low Level Cutoff
7115 + offset
7116 + offset
7125 + offset
Set Input: Pressure Low Level Hysteresis
Set Input: Pressure High Level Cutoff
7126 + offset
7127 + offset
Set Input: Pressure High Level Hysteresis 7128 + offset
7104 + offset
3105 + offset
7300 + offset
Set Input: Save Low/High Flow Events
Invalid User Event
Start Temperature Calibration: Forced temperature input
End Temperature Calibration: Removed forced temperature input
Start Static Pressure Calibration: Forced SP input
End Static Pressure Calibration: Removed forced SP input
Start Differential Pressure Calibration:
Forced DP input
7304 + offset
7305 + offset
7309 + offset
7310 + offset
End Differential Pressure Calibration:
Removed forced DP input
Start Pulse Counter Calibration: Forced pulse count rate
End Pulse Counter Calibration: Removed forced pulse count rate
Set User Number
Set User Security Level
Set Input: Temperature Register Type
7314 + offset
5150 + offset
5154 + offset
3030
3031
7105 + offset
Set Input: Pressure Register Type
Set Input: DP Register Type
7117 + offset
7129 + offset
Set Input: Temperature Input at Zero Scale 7109 + offset
Set Input: Temperature Input at Full Scale 7110 + offset
Set Input: Pressure Input at Zero Scale 7121 + offset
Set Input: Pressure Input at Full Scale 7122 + offset
Set Input: DP Input at Zero Scale
Set Input: DP Input at Full Scale
7133 + offset
7134 + offset
Set Input: Pulse Counter Register
Set Input: Pulse Counter Register Type
Set Active Runs
Lost Alarms
Firmware Version
Application Version
Set Flow Computer ID
Set Contract: Input Err Action
Power Off
Start Plate Change: Forced temperature input
End Plate Change: Removed forced temperature input
Start Plate Change: Forced static pressure input
7142 + offset
7141 + offset
3009
3101 + offset
3001
3003
3020
7150 + offset
1003
7315 + offset
7316 + offset
7317 + offset
Realflo User and Reference Manual
May 19, 2011
901
Enron Modbus Protocol Interface
10084
10085
10086
10087
10088
10089
10090
10091
10092
10093
10094
10105
10106
10107
10108
10109
Number
10080
10081
10082
10083
10110
10111
10114
Description Enron
Variable
End Plate Change: Removed forced static pressure input
Start Plate Change: Forced differential pressure input
End Plate Change: Removed forced differential pressure input
Set Input: altitude and latitude compensation
Set Input: altitude
Set Input: latitude
Forced temperature input
Removed forced temperature input
Forced static pressure input
7318 + offset
7319 + offset
7320 + offset
7249 + offset
7250 + offset
7251 + offset
7321 + offset
7322 + offset
7323 + offset
Removed forced static pressure input
Forced differential pressure input
7324 + offset
7325 + offset
Removed forced differential pressure input 7326 + offset
Forced pulse count rate
Removed forced pulse count rate
Set Contract: wet gas meter factor
Set Input: Flow Direction Control
Set Input: Flow Direction Register
5155 + offset
5156 + offset
7293 + offset
10100 + offset
10101 + offset
Forced mass flow input
Restored live mass flow input
Starting Calibration: Forced mass flow rate input
Ending Calibration: Restored live mass flow rate input
Set Input: Mass Flow Rate Register Type
Set Input: On Indicates
10102 + offset
10103 + offset
10104 + offset
10105 + offset
10106 + offset
10107 + offset
AGA-3 (1985) Alarms and Events
These events are specific to the AGA-3 (1985) calculation.
Number Description
10201
Enron
Variable
3131 + offset
10202
10203
10204
10205
10206
10207
10208
10209
10210
10211
Failed To Create AGA-3 (1985) Data
Structure
Created AGA-3 (1985) with Execution
Stopped
Created AGA-3 (1985) with Execution
Running
Destroyed AGA-3 (1985) Data Structure
Recovered from AGA-3 (1985) error
Set AGA-3 (1985): Input Units Type
Set AGA-3 (1985): Orifice Material
Set AGA-3 (1985): Pipe Material
Set AGA-3 (1985): Static Pressure Tap
Location
Set AGA-3 (1985): Orifice Diameter
Set AGA-3 (1985): Orifice Measurement
Reference Temperature
3132 + offset
3133 + offset
3134 + offset
3135 + offset
7100 + offset
7151 + offset
7152 + offset
7103 + offset
7153 + offset
7154 + offset
Realflo User and Reference Manual
May 19, 2011
902
Enron Modbus Protocol Interface
10214
10215
10216
10217
10218
10219
10220
10221
10222
Number
10212
10213
10223
Description Enron
Variable
Set AGA-3 (1985): Pipe Diameter
Set AGA-3 (1985): Pipe Diameter
Measurement Reference Temperature
Set AGA-3 (1985): Isentropic Exponent
7155 + offset
7156 + offset
Set AGA-3 (1985): Viscosity
Set AGA-3 (1985): Base Temperature
Set AGA-3 (1985): Base Pressure
7157 + offset
7158 + offset
7148 + offset
7149 + offset
Set AGA-3 (1985): Atmospheric Pressure 7145 + offset
Failed To Set AGA-3 (1985) Configuration 3136 + offset
Set AGA-3 (1985): Contract Units Type 7146 + offset
Set AGA-3 (1985): Temperature deadband 7159 + offset
Set AGA-3 (1985): Static Pressure deadband
7160 + offset
Set AGA-3 (1985): Differential Pressure deadband
7161 + offset
AGA-3 (1992) Alarms and Events
These events are specific to the AGA-3 (1992) calculation.
10314
10315
10316
10317
10318
10319
10320
10321
10322
10323
Number
10301
10302
10303
10304
10305
10306
10307
10308
10309
10310
10311
10312
10313
Description Enron
Variable
Failed To Create AGA-3 (1992) Data
Structure
3140 + offset
Created AGA-3 (1992) with Execution
Stopped
Created AGA-3 (1992) with Execution
Running
Destroyed AGA-3 (1992) Data Structure
Restored from AGA-3 (1992) error
Set AGA-3 (1992): Input Units Type
Set AGA-3 (1992): Orifice Material
Set AGA-3 (1992): Pipe Material
3141 + offset
3142 + offset
3143 + offset
3144 + offset
7100 + offset
7151 + offset
7152 + offset
7103 + offset Set AGA-3 (1992): Static Pressure Tap
Location
Set AGA-3 (1992): Orifice Diameter
Set AGA-3 (1992): Orifice reference temperature
Set AGA-3 (1992): Pipe Diameter
7153 + offset
7154 + offset
Set AGA-3 (1992): Pipe Diameter
Measurement Temperature
Set AGA-3 (1992): Isentropic Exponent
Set AGA-3 (1992): Viscosity
Set AGA-3 (1992): Base Temperature
Set AGA-3 (1992): Base Pressure
7155 + offset
7156 + offset
7157 + offset
7158 + offset
7148 + offset
7149 + offset
Set AGA-3 (1992): Atmospheric Pressure 7145 + offset
Failed To Set AGA-3 (1992) Configuration 3145 + offset
Set Input: DP Low Level Cutoff
Set Input: DP Low Level Hysteresis
Set Input: DP High Level Cutoff
Set Input: DP High Level Hysteresis
7137 + offset
7138 + offset
7139 + offset
7140 + offset
Realflo User and Reference Manual
May 19, 2011
903
Enron Modbus Protocol Interface
Number
10324
10325
10326
10327
Description Enron
Variable
Set AGA-3 (1992): Contract Units Type
Set AGA-3 (1992): Differential Pressure deadband
7146 + offset
Set AGA-3 (1992): Temperature deadband 7159 + offset
Set AGA-3 (1992): Static Pressure deadband
7160 + offset
7161 + offset
AGA-7 Alarms and Events
These events are specific to the AGA-7 calculation.
Number Description
10701
10702
10703
10704
10705
10706
10707
10708
10709
10710
10711
10712
10713
10714
10715
Failed To Create AGA-7 Data Structure
Created AGA-7 with Execution Stopped
Created AGA-7 with Execution Running
Destroyed AGA-7 Data Structure
Restored from AGA-7 error
Set AGA-7: Input Units Type
Set AGA-7: K factor
Set AGA-7: M factor
Set AGA-7: Atmospheric Pressure
Set AGA-7: Base Pressure
Set AGA-7: Base Temperature
Failed To Set AGA-7 Configuration
Set Input: Turbine Low Flow Pulse Limit
Set Input: Turbine Low Flow Detect Time
Set AGA-7: Contract Units Type
Enron
Variable
3149 + offset
3150 + offset
3151 + offset
3152 + offset
3153 + offset
7100 + offset
7191 + offset
7192 + offset
7145 + offset
7149 + offset
7148 + offset
3154 + offset
7143 + offset
7144 + offset
7146 + offset
AGA-11 Alarms and Events
These events are specific to the AGA-11 calculation.
Number Description
11101
11102
11103
11104
11105
11106
11107
11108
11109
11110
Failed To Create AGA-11 Data Structure
Created AGA-11 with Execution Stopped
Created AGA-11 with Execution Running
Destroy AGA-11 Data Structure
Recovered from AGA-11 error
Change in AGA-11 units configuration
Change in AGA-11 contract units config
Change in AGA-11 base temperature
Change in AGA-11 base pressure
Failed To Set AGA-11 Configuration
V-Cone Alarms and Events
These events are specific to the V-Cone calculation.
Number Description
Enron
Variable
10110 + offset
10111 + offset
10112 + offset
10113 + offset
10114 + offset
10115 + offset
10116 + offset
10117 + offset
10118 + offset
10119 + offset
12201 Failed To Create V-Cone Date Structure
Enron
Variable
3157 + offset
Realflo User and Reference Manual
May 19, 2011
904
12214
12215
12216
12217
12218
12219
12220
12221
12222
12223
12224
12225
12226
12202
12203
12204
12205
12206
12207
12208
12209
12210
12211
12212
12213
12227
12228
12229
12230
12231
12232
12233
12234
12235
12236
12237
12238
12239
12240
12241
12242
12243
Number Description
Created V-Cone with Execution Stopped
Created V-Cone with Execution Running
Destroyed V-Cone Data Structure
Restored from V-Cone Error
Failed To Set V-Cone Configuration
/* reserved */
Set V-Cone Input Units Type
Set V-Cone Contract Units Type
Set V-Cone Cone Material
Set V-Cone Pipe Material
Set V-Cone Cone Diameter
Set V-Cone Inside Pipe Diameter
Set V-Cone Pipe reference temperature
Set V-Cone Isentropic Exponent
Set V-Cone Viscosity
Set V-Cone Base Temperature
Set V-Cone Base Pressure
Set V-Cone Atmospheric Pressure
Set Table Point 1 Reynolds Number
Set Table Point 2 Reynolds Number
Set Table Point 3 Reynolds Number
Set Table Point 4 Reynolds Number
Set Table Point 5 Reynolds Number
Set Table Point 6 Reynolds Number
Set Table Point 7 Reynolds Number
Set Table Point 8 Reynolds Number
Set Table Point 9 Reynolds Number
Set Table Point 10 Reynolds Number
Set Table Point 1 Flow Coefficient
Set Table Point 2 Flow Coefficient
Set Table Point 3 Flow Coefficient
Set Table Point 4 Flow Coefficient
Set Table Point 5 Flow Coefficient
Set Table Point 6 Flow Coefficient
Set Table Point 7 Flow Coefficient
Set Table Point 8 Flow Coefficient
Set Table Point 9 Flow Coefficient
Set Table Point 10 Flow Coefficient
Set Adiabatic Expansion Factor Method
Set Wet Gas Correction Factor Method
Set Density of liquid at flow conditions
Set Mass flow rate of liquid at flow conditions
Enron Modbus Protocol Interface
Enron
Variable
3158 + offset
3159 + offset
3160 + offset
3161 + offset
3162 + offset none
7100 + offset
7146 + offset
7162 + offset
7163 + offset
7164 + offset
7166 + offset
7167 + offset
7168 + offset
7169 + offset
7148 + offset
7149 + offset
7145 + offset
7171 + offset
7173 + offset
7175 + offset
7177 + offset
7179 + offset
7181 + offset
7183 + offset
7185 + offset
7187 + offset
7189 + offset
7172 + offset
7174 + offset
7176 + offset
7178 + offset
7180 + offset
7182 + offset
7184 + offset
7186 + offset
7188 + offset
7190 + offset
7295 + offset
7296 + offset
7297 + offset
7298 + offset
AGA-8 Alarms and Events
These events are specific to the AGA-8 calculation.
Number Description
10801 Failed To Create AGA-8 Data Structure
Enron
Variable
3113 + offset
Realflo User and Reference Manual
May 19, 2011
905
Enron Modbus Protocol Interface
10802
10803
10804
10805
10806
10807
10808
10809
10810
10811
10812
10813
10814
10815
10816
10817
10818
10819
10820
10833
10834
10835
10836
10837
10838
10839
10840
10841
10842
10843
10821
10822
10823
10824
10825
10826
10827
10828
10829
10830
10831
10832
Number
10844
Description Enron
Variable
Created AGA-8 with Execution Stopped
Created AGA-8 with Execution Running
Destroyed AGA-8 Data Structure
Set AGA-8 Gas: Change Gas Fractions
3114 + offset
3115 + offset
3116 + offset
Set AGA-8 Gas: Methane (CH4)
Set AGA-8 Gas: Nitrogen
Set AGA-8 Gas: Carbon Dioxide (CO2)
Set AGA-8 Gas: Ethane (C2H6)
Set AGA-8 Gas: Propane (C3H8)
Set AGA-8 Gas: Water
7193 + offset
7194 + offset
7195 + offset
7196 + offset
7197 + offset
7198 + offset
Set AGA-8 Gas: Hydrogen Sulphide (H2S) 7199 + offset
Set AGA-8 Gas: Hydrogen 7200 + offset
Set AGA-8 Gas: Carbon Monoxide (CO)
Set AGA-8 Gas: Oxygen
Set AGA-8 Gas: I-Butane
Set AGA-8 Gas: n-Butane
Set AGA-8 Gas: I-Pentane
Set AGA-8 Gas: n-Pentane
Set AGA-8 Gas: n-hexane (when using individual gas components)
Set AGA-8 Gas: n-hexane + (when using combined value for hexane and higher components)
Set AGA-8 Gas: n-Heptane
7201 + offset
7202 + offset
7203 + offset
7204 + offset
7205 + offset
7206 + offset
7207 + offset
Set AGA-8 Gas: n-Octane
Set AGA-8 Gas: n-Nonane
Set AGA-8 Gas: n-Decane
Set AGA-8 Gas: Helium
Set AGA-8 Gas: Argon
Set AGA-8 Gas: Failed To Set
Failed To Set AGA-8 Configuration
Set AGA-8: Input Units Type
Set AGA-8: Base Temperature
Set AGA-8: Base Pressure
Set AGA-8: Atmospheric Pressure
7208 + offset
7209 + offset
7210 + offset
7211 + offset
7212 + offset
7213 + offset
3118 + offset
3119 + offset
7100 + offset
7148 + offset
7149 + offset
7145 + offset
Set AGA-8: Static Pressure Tap Location
Set AGA-8: Contract Units Type
Clear Compressibility Error
Set AGA-8: gas composition logging
Set AGA-8 Gas: Use Hexanes+
Set AGA-8 Hexane + Ratio for n-hexane
Set AGA-8 Hexane + Ratio for n-heptane
Set AGA-8 Hexane + Ratio for n-octane
Set AGA-8 Hexane + Ratio for n-nonane
Set AGA-8 Hexane + Ratio for n-decane
Set AGA-8 Laboratory real relative density
0 = calculate value
0.07 to 1.52 = use value
Set AGA-8 Laboratory heating value:
0 = calculate value
0 to 1800 = use value
7103 + offset
7146 + offset
3117 + offset
7219 + offset
7274 + offset
7275 + offset
7276 + offset
7277 + offset
7278 + offset
7279 + offset
7280 + offset
7281 + offset
Realflo User and Reference Manual
May 19, 2011
906
Enron Modbus Protocol Interface
NX-19 Alarms and Events
These events are specific to the NX-19 calculation.
11901
11902
11903
11904
11905
11906
11907
11908
11909
11910
11911
Number
11912
11913
11914
11915
11916
11917
11918
11919
Description
Failed to Create NX-19 Data Structure
Created NX-19 with Execution Stopped
Created NX-19 with Execution Running
Destroyed NX-19 Data Structure
Restored from NX-19 error
Set NX-19: Calculation Method
Set NX-19: Specific Gravity
Set NX-19: Gas: Carbon Dioxide
Set NX-19: Gas: Methane
Set NX-19: Gas: Nitrogen
Set NX-19: Heating Value
Enron
Variable
3122 + offset
3123 + offset
3124 + offset
3125 + offset
3126 + offset
7214 + offset
7215 + offset
7216 + offset
7217 + offset
Set NX-19: Static Pressure Tap Location
Set NX-19: Base Pressure
Set NX-19: Base Temperature
Clear Compressibility Error
Set NX-19: gas composition logging disabled
7103 + offset
7149 + offset
7148 + offset
Failed to set NX-19 Gas Components 3127 + offset
Failed to set NX-19 Contract Configuration 3128 + offset
Set NX-19: Contract Units Type 7146 + offset
3126 + offset
7218 + offset
MVT Alarms and Events
These events are specific to the MVT transmitter.
Number
13100
13101
13102
13103
13104
13105
13106
Description
Set MVT Transmitter 1: polling status
Set MVT Transmitter 1: serial port
Set MVT Transmitter 1: Address of transmitter
Enron
Variable
9603 + offset
9604 + offset
9605 + offset
Set MVT Transmitter 1: Timeout 9606 + offset
Set MVT Transmitter 1: Manufacturer Code 9607 + offset
Set MVT Transmitter 1: Turnaround Delay
Time
9608 + offset
Set MVT Transmitter 1: Differential
Pressure units
9609 + offset
13107
13108
13109
13110
13111
13112
13113
Set MVT Transmitter 1: Static Pressure units
9610 + offset
Set MVT Transmitter 1: Temperature units 9611 + offset
Set MVT Transmitter 1: Serial number
Set MVT Transmitter 1: Tag
6100 + offset
4103 + offset
9612 + offset Set MVT Transmitter 1: Differential
Pressure damping
Set MVT Transmitter 1: Differential
Pressure upper operating limit
9613 + offset
Set MVT Transmitter 1: Differential
Pressure lower operating limit
9614 + offset
Realflo User and Reference Manual
May 19, 2011
907
Enron Modbus Protocol Interface
Number
13114
13115
13116
13117
13118
13119
13120
13121
13122
13123
13124
13125
13126
13127
13128
13129
13130
13131
13132
13133
13134
13135
13136
13137
13138
13139
13140
13141
13142
Description
Set MVT Transmitter 1: Static Pressure damping
Set MVT Transmitter 1: Static Pressure upper operating limit
Set MVT Transmitter 1: Static Pressure lower operating limit
Set MVT Transmitter 1: Temperature damping
Set MVT Transmitter 1: Temperature upper operating limit
Set MVT Transmitter 1: Temperature lower operating limit
MVT Transmitter 1: lost communication
MVT Transmitter 1: transmitter configuration incorrect
MVT Transmitter 1: temperature sensor out of range
MVT Transmitter 1: static pressure sensor out of range
MVT Transmitter 1: differential pressure sensor out of range
MVT Transmitter 1: not polled
Set MVT Transmitter 1: Type Code
Set MVT Transmitter 1: IP Address
Set MVT Transmitter 1: IP Protocol
MVT Transmitter 1: temperature sensor value is bad
MVT Transmitter 1: static pressure sensor value is bad
MVT Transmitter 1: differential pressure sensor value is bad
Set MVT Transmitter 1: Atmospheric
Pressure Offset
MVT Transmitter 1: Restore for all communication alarms
MVT Transmitter 1: Restore for all alarms
MVT Transmitter 1: Sensors are Off Line
MVT Transmitter 1: RTD is disconnected
MVT Transmitter 1: Temperature Sensor
Above Range
MVT Transmitter 1: Static Pressure Above
Range
MVT Transmitter 1: Differential Pressure
Above Range
MVT Transmitter 1: Temperature Sensor
Below Range
MVT Transmitter 1: Static Pressure Below
Range
MVT Transmitter 1: Differential Pressure
Below Range
Enron
Variable
9615 + offset
9616 + offset
9617 + offset
9618 + offset
9619 + offset
9620 + offset
4112 + offset
4113 + offset
4114 + offset
4115 + offset
4116 + offset
4117 + offset
9621 + offset
6101 + offset
4120 + offset
4121 + offset
4122 + offset
4123 + offset
9622 + offset
4124 + offset
4125 + offset
4126 + offset
4127 + offset
4127 + offset
4127 + offset
4127 + offset
4127 + offset
4127 + offset
4127 + offset
Realflo User and Reference Manual
May 19, 2011
908
Enron Modbus Protocol Interface
Coriolis Meter Alarms and Events
These events are specific to the Coriolis meter.
Number Description
14001
14002
14003
14004
14005
14006
14007
14008
Failed To Set Coriolis Meter
Set Coriolis Meter: Meter Address
Set Coriolis Meter: Meter Port
Set Coriolis Meter: Meter Timeout
Coriolis Meter: Lost Communication
Coriolis Meter: Communication Restored
Coriolis Meter: Not Polled
Coriolis Meter: Coriolis Meter has bad response
Enron
Variable
10200 + offset
10201 + offset
10202 + offset
10203 + offset
10204 + offset
10205 + offset
10206 + offset
10207 + offset
Calibration and User Defined Alarms and Events
Realflo generates these events when performing calibration (not by the flow computer). User defined events can also be created in the range 19000 to
19999. Refer to the Log User Event command for details.
19003
19004
19005
19006
19007
19008
19009
19013
19014
19015
19016
19018
19019
19023
19024
19025
19026
19028
19029
19032
19033
19034
19039
Number Description
As-Found Temperature
As-Left Temperature
Target Re-Zero Temperature
Target Temperature Span
Set Default Temperature
Temperature After ReZero
Temperature After Span Calibration
As-Found Static Pressure
Enron
Variable
7302 + offset
7303 + offset
7333 + offset
7334 + offset
7335 + offset
7327 + offset
7328 + offset
7307 + offset
As-Left Static Pressure
Target Re-Zero Static Pressure
Target Static Pressure Span
Static Pressure After ReZero
Static Pressure After Span Calibration
As-Found Differential Pressure
As-Left Differential Pressure
Target Re-Zero Differential Pressure
7308 + offset
7336 + offset
7337 + offset
7329 + offset
7330 + offset
7312 + offset
7331 + offset
7338 + offset
Target Differential Pressure Span
Differential Pressure After ReZero
7339 + offset
7332 + offset
Differential Pressure After Span Calibration 7314 + offset
Continue Pulse Count Calibration
As-Found Pulse Count
As-Left Pulse Count
End Pulse Count Calibration
5151 + offset
5152 + offset
5153 + offset
5154 + offset
Calculation Engine Errors
The flow calculation engine generates these errors.
Number Description
20001
20003
Meter control structure not found
Temperature input is below zero scale
Enron
Variable
1101 + offset
3106 + offset
Realflo User and Reference Manual
May 19, 2011
909
Enron Modbus Protocol Interface
Number
20004
20005
20006
20007
20008
20009
20010
20011
20050
Description
Temperature input is above full scale 3107 + offset
Static pressure input is below zero scale
Static pressure input is above full scale
Differential pressure input is below zero scale
3108 + offset
3109 + offset
3110 + offset
Differential pressure input is above full scale 3111 + offset
Compressibility calculation inputs invalid 3112 + offset
Forced input register 4403 + offset
Removed force from input register
Restore from temperature input low alarm
Enron
Variable
4404 + offset
4405 + offset
20051
20052
20053
20054
20055
20056
20057
Restore from temperature input high alarm
Restore from static pressure input low alarm 4407 + offset
Restore from static pressure input high alarm
Restore from differential pressure input low alarm
Restore from differential pressure input high alarm
Restore from low pulse input alarm
Restore from input alarm
4406 + offset
4408 + offset
4409 + offset
4410 + offset
4411 + offset
4412 + offset
AGA-3 (1985) Calculation Errors
These errors are generated by the AGA-3 (1985) calculation.
Number Description
20210
Enron
Variable
4417 + offset
20229
20232
20233
20234
AGA-3 (1985)
– Flowing temperature is at or below absolute zero
AGA-3 (1985) - Ratios from AGA-8 or NX-19 were not available
AGA-3 (1985) - Static pressure below differential
AGA-3 (1985) - Static pressure zero or negative
AGA-3 (1985)
– Bad Calculation
3137 + offset
3138 + offset
3139 + offset
4419 + offset
AGA-3 (1992) Calculation Errors
These errors are generated by the AGA-3 (1992) calculation.
Number
20310
20325
20329
20332
20333
Description
AGA-3 (1992)
– Flowing temperature is at or below absolute zero
AGA-3 (1992)
– Too many Iterations
AGA-3 (1992)
– Ratios from AGA-8 or NX-19 were not available
AGA-3 (1992) - Static pressure below differential
AGA-3 (1992) - Static pressure zero or negative
Enron
Variable
4417 + offset
4420 + offset
3146 + offset
3147 + offset
3148 + offset
Realflo User and Reference Manual
May 19, 2011
910
Number
20334
Description
AGA-3 (1992)
Enron Modbus Protocol Interface
– Bad Calculation
Enron
Variable
4419 + offset
AGA-7 Calculation Errors
These errors are generated by the AGA-7 calculation.
Number
20712
20713
20714
20716
20720
Description
AGA-7 - Temperature low
AGA-7
– Static pressure zero or negative
AGA-7 - Low pulse rate
AGA-7 - Ratios from AGA-8 or NX-19 are not available
AGA-7
– Bad Calculation
Enron
Variable
4417 + offset
4418 + offset
3155 + offset
3156 + offset
4419 + offset
V-Cone Calculation Errors
These errors are generated by the V-Cone calculation.
Number Description
22221
22223
22227
22228
22229
22230
V-Cone
– Temperature low
V-Cone
– Ratios from AGA-8 or NX-19 were not available
V-Cone
– Too many Iterations
V-Cone
– Static pressure below differential pressure
V-Cone
– Static pressure zero or negative
V-Cone
– Bad Calculation
Enron
Variable
4417 + offset
3163 + offset
4420 + offset
3164 + offset
3199 + offset
4419 + offset
AGA-8 Calculation Errors
These errors are generated by the AGA-8 calculation.
Number Description
20809
20810
20811
20812
20814
20819
AGA-8
– Flow Temperature is Low
AGA-8
– Flow Temperature is High
AGA-8
– Flow Pressure is Low
AGA-8
–Flow Press is High
AGA-8 - Not configured
AGA-8 - No gas components
NX-19 Errors
These errors are generated by the NX-19 calculation.
Number Description
21913
21914
21915
21916
21917
NX-19
– Flow Temperature is Low
NX-19
– Flow Pressure is Low
NX-19
–Flow Press is High
NX-19 - Configuration flag not set
NX-19 - Gas ratios were not available
Enron
Variable
4413 + offset
4414 + offset
3166 + offset
4416 + offset
3120 + offset
3121 + offset
Enron
Variable
4413 + offset
4415 + offset
4416 + offset
3129 + offset
3130 + offset
Realflo User and Reference Manual
May 19, 2011
911
Number Description
NX-19
Enron Modbus Protocol Interface
– Flow Temperature is High
Enron
Variable
4414 + offset 21921
Realflo User and Reference Manual
May 19, 2011
912
PEMEX Modbus Protocol Interface
PEMEX Modbus Protocol Interface
The PEMEX Modbus protocol is used in the Oil and Gas industry to obtain data from electronic flow measurement devices. Control Microsystems supports this protocol in our flow computer products.
The PEMEX Modbus protocol is an extension of standard Modicon Modbus that supports a subset of Modbus function codes for historical and flow data.
Message framing is identical to the Enron Modbus protocol. However, register mapping differs for PEMEX Modbus.
The flow computer supports PEMEX Modbus and standard Modbus on the same serial port. Standard Modbus uses one station address and PEMEX
Modbus uses a different station address.
The flow computer does not determine which format a message is using because the station address separates the data streams. This architecture allows standard PC applications to communicate with the flow computer in the normal manner. PEMEX Modbus hosts can communicate at the same time.
The flow computer program processes PEMEX Modbus commands, sends master messages, and processes master responses. This architecture allows the PEMEX Modbus commands to directly access flow computer data.
Flow computer data is accessed directly when a command is processed.
When data is written to the numeric registers for configuration, the flow computer reads the existing data structures, replaces the targeted fields with new data and attempts to configure the run with the new configuration. This may be repeated with other configuration items when the command message is long.
Some registers are read only, as listed in the Access column in the tables below. Changes made to read only registers are not accepted by the flow computer.
The flow computer supports the following PEMEX function codes.
Command
1
2
3
4
5
6
15
16
Description
Read coil status
Read input status
Read holding registers
Read input registers
Force single coil
Preset single register
Force multiple coils
Preset multiple registers
Register Addresses
The addresses in the messages refer to system addresses, not type specific addresses. The commands will return exception errors if the command refers to addresses outside the valid range for the command.
Realflo User and Reference Manual
May 19, 2011
913
PEMEX Modbus Protocol Interface
The ranges are as follows:
Range Data Type
0001
– 1000
Hourly/Daily archive
Alarm/Event retrieval (0032)
1001
– 2000
Real-time status
2001
– 3000
Not used
3001 - 4000 Not used
4001 - 5000 Not used
5001
– 6000
Not used
6001
– 7000
Pointers to current historic archive (6100
– 6300 approx.)
Number of events not retrieved (6301)
7001
– 7599
Real-time floating-point data
7600
– 7999
Events
8001
– 9000
Upload or download data (quality of gas and AGA configuration)
9999
– 10000 Time synchronization
Refer to the Flow Computer Variables section of this document for details on
the registers allocated to the flow computer.
Meter Run 1 Data Variables
Meter run 1 data variables are show in detail in the following sections.
Meter Run 1 Instantaneous and Accumulated Variables
These variables display the current state of the flow calculation for meter run
1.
Register Description
7001
7002
Static pressure
Differential pressure / Pulse count
7003
7004
7005
7006
7007
7008
7009
7010
Temperature
Corrected flow (2 nd
base conditions)
Corrected flow (1 st
base conditions)
Hourly volume (2 nd
base conditions)
Hourly volume (1 st
base conditions)
Daily volume (2 nd
base conditions)
Daily volume (1 st
base conditions)
Previous hourly volume (2 nd base conditions)
°
PEMEX Units
psi
F
Access
Read Only inches H
2
O / Hz Read Only
MSCM/D
MSCF/D
MSCM
MSCF
MSCM
MSCF
MSCM
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Realflo User and Reference Manual
May 19, 2011
914
PEMEX Modbus Protocol Interface
Register Description
7011
Previous hourly volume (1 st
7012 base conditions)
Previous daily volume (2 nd
7013 base conditions)
Previous daily volume (1 st base conditions)
7014 Energy flow rate
7015
7016
7017
7018
Hourly energy
Daily energy
Previous hourly energy
Previous daily energy
PEMEX Units
MSCF
MSCM
MSCF
Access
Read Only
Read Only
Read Only
Giga calories/D Read Only
Giga calories Read Only
Giga calories
Giga calories
Giga calories
Read Only
Read Only
Read Only
Meter Run 1 Historic Variables
These registers are used to retrieve the historic information for meter run 1.
The host first retrieves the history index value. The host then retrieves the relevant historic records based on the value of the history index. The host can specify which historic record to retrieve by s etting the “Number of
Registers” in the request. See section Historic Data Variables for more
information.
Register Description
701
721
741
6101
6121
6201
Daily history records
Hourly history records
Hourly gas quality history records
Daily history index
Hourly history index
Hourly gas quality history index
Access
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Meter Run 2 Data Variables
Meter run 2 data variables are show in detail in the following sections.
Meter Run 2 Instantaneous and Accumulated Variables
These variables display the current state of the flow calculation for meter run
2.
Register
7031
7032
7033
7034
7035
7036
7037
7038
Description
Static pressure
Differential pressure / Pulse count
Temperature
Corrected flow (2 nd
base conditions)
Corrected flow (1 st
base conditions)
Hourly volume (2 nd
base conditions)
Hourly volume (1 st
base conditions)
Daily volume (2 nd
base conditions)
PEMEX Units
psi
Access
Read Only inches H
2
O / Hz Read Only
°
F
MSCM/D
MSCF/D
MSCM
MSCF
MSCM
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Realflo User and Reference Manual
May 19, 2011
915
PEMEX Modbus Protocol Interface
Register Description
7039
Daily volume (1 st
base
7040 conditions)
Previous hourly volume (2 nd
7041 base conditions)
Previous hourly volume (1 st
7042 base conditions)
Previous daily volume (2 nd
7043 base conditions)
Previous daily volume (1 st base conditions)
7044 Energy flow rate
7045
7046
7047
7048
Hourly energy
Daily energy
Previous hourly energy
Previous daily energy
PEMEX Units
MSCF
MSCM
MSCF
MSCM
MSCF
Giga calories/D
Giga calories
Giga calories
Giga calories
Giga calories
Access
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Meter Run 2 Historic Variables
These registers are used to retrieve the historic information for meter run 2.
The host first retrieves the history index value. The host then retrieves the relevant historic records based on the value of the history index. The host can specify which historic r ecord to retrieve by setting the “Number of
Registers” in the request. See section Historic Data Variables for more
information.
Register Description
702
722
742
6102
6122
6202
Daily history records
Hourly history records
Hourly gas quality history records
Daily history index
Hourly history index
Hourly gas quality history index
Access
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Meter Run 3 Data Variables
Meter run 3 data variables are show in detail in the following sections.
Meter Run 3 Instantaneous and Accumulated Variables
These variables display the current state of the flow calculation for meter run
3.
Register
7061
7062
7063
7064
7065
7066
Description
Static pressure
Differential pressure / Pulse count
Temperature
Corrected flow (2 nd
base conditions)
Corrected flow (1 st
base conditions)
Hourly volume (2 nd
base
PEMEX Units
psi
Access
Read Only inches H
2
O / Hz Read Only
°
F
MSCM/D
MSCF/D
MSCM
Read Only
Read Only
Read Only
Read Only
Realflo User and Reference Manual
May 19, 2011
916
7067
7068
7069
7070
7071
7072
PEMEX Modbus Protocol Interface conditions)
Hourly volume (1 st
base conditions)
Daily volume (2 nd
base conditions)
Daily volume (1 st
base conditions)
Previous hourly volume (2 nd base conditions)
Previous hourly volume (1 st base conditions)
Previous daily volume (2 nd base conditions)
Previous daily volume (1 st base conditions)
Energy flow rate
Hourly energy
Daily energy
Previous hourly energy
Previous daily energy
MSCF
MSCM
MSCF
MSCM
MSCF
MSCM
MSCF
Giga calories/D
Giga calories
Giga calories
Giga calories
Giga calories
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
7073
7074
7075
7076
7077
7078
Meter Run 3 Historic Variables
These registers are used to retrieve the historic information for meter run 3.
The host first retrieves the history index value. The host then retrieves the relevant historic records based on the value of the history index. The host can specify which historic record to retrieve by setting the “Number of
Registers” in the request. See section Historic Data Variables for more
information.
Register Description
703
723
743
6103
6123
6203
Daily history records
Hourly history records
Hourly gas quality history records
Daily history index
Hourly history index
Hourly gas quality history index
Access
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Meter Run 4 Data Variables
Meter run 4 data variables are show in detail in the following sections.
Meter Run 4 Instantaneous and Accumulated Variables
These variables display the current state of the flow calculation for meter run
4.
Register Description
7091
7092
Static pressure
Differential pressure / Pulse count
7093
7094
Temperature
Corrected flow (2 nd
base
°
PEMEX Units
psi
F
MSCM/D
Access
Read Only inches H
2
O / Hz Read Only
Read Only
Read Only
Realflo User and Reference Manual
May 19, 2011
917
7095
7096
7097
7098
7109
7100
7101
7102
7103
7104
7105
7106
7107
7108
PEMEX Modbus Protocol Interface conditions)
Corrected flow (1 st
base conditions)
Hourly volume (2 nd
base conditions)
Hourly volume (1 st
base conditions)
Daily volume (2 nd
base conditions)
Daily volume (1 st
base conditions)
Previous hourly volume (2 nd base conditions)
Previous hourly volume (1 st base conditions)
Previous daily volume (2 nd base conditions)
Previous daily volume (1 st base conditions)
Energy flow rate
Hourly energy
Daily energy
Previous hourly energy
Previous daily energy
MSCF/D
MSCM
MSCF
MSCM
MSCF
MSCM
MSCF
MSCM
MSCF
Giga calories/D
Giga calories
Giga calories
Giga calories
Giga calories
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Meter Run 4 Historic Variables
These registers are used to retrieve the historic information for meter run 1.
The host first retrieves the history index value. The host then retrieves the relevant historic records based on the value of the history index. The host can specify which historic record to retrieve by setting the “Number of
Registers” in the request. See section Historic Data Variables for more
information.
Register Description
704
724
744
6104
6124
6204
Daily history records
Hourly history records
Hourly gas quality history records
Daily history index
Hourly history index
Hourly gas quality history index
Access
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Historic Data Variables
PEMEX Modbus Hourly/Daily archive registers are used to read Realflo hourly and daily logs. The registers read the logs record by record.
The Daily Log holds records for the previous 35 days. These can be read by using index numbers one through 35.
The Hourly Log holds records for the previous 841 hours. These can be read using index numbers one through 841.
The Gas Composition Log holds (hourly) records for the previous 841 hours.
These can be read using index numbers one through 841.
Realflo User and Reference Manual
May 19, 2011
918
PEMEX Modbus Protocol Interface
An index of 0 implies that a log has not yet occurred. Polling for index 0 will result in an illegal data address response in PEMEX Modbus.
Historic Record Format
Each hourly and daily record is in the following format.
Felds are in floating-point format.
Field PEMEX Units
Date (at the start of the period)
Time (at the start of the period)
MMDDYY.0
HHMMSS.0
Duration of flow in period Minutes
Up-time (in contract day) Minutes
Average differential pressure/ Average Frequency inches H
2
0 / Hz
Average static pressure psia
Average temperature
°
F
Average relative density
Average heating value
Average flow extension
Volume (2 nd
base conditions)
Energy
Number of events
Number of alarms
Meter ID
Quality
Volume (1 st
base conditions)
Total energy in period
-
BTU(60)/SCF
-
MCF
Mega calories
-
-
-
-
MCF
Giga calories
Gas Quality History Record Format
Each gas quality history record is in the following format.
Gas components are in %, not in mole fractions.
Field
Date
Time
Methane
Nitrogen
Carbon Dioxide
Ethane
Propane
Water
Hydrogen Sulfide
Hydrogen
Carbon Monoxide
Oxygen i-butane n-Butane i-Pentane n-Pentane n-Hexane
Format / Units Notes
%
%
%
%
%
%
%
%
%
%
%
MMDDYY.0
HHMMSS.0
%
%
%
%
Realflo User and Reference Manual
May 19, 2011
919
Field
n-Heptane n-Octane n-Nonane n-Decane
Helium
Argon
Hexanes+
Relative Density
Heating Value
PEMEX Modbus Protocol Interface
Format / Units Notes
%
%
%
%
%
%
%
-
BTU(60)/ft
3
Not used
Meter Run 1 Configuration
AGA Configuration
These registers are used to configure the AGA configuration for meter run 1.
8601
8602
8603
8604
8605
8606
8607
8608
8609
8610
8611
8612
Register Field
Atmospheric pressure
Base pressure
Base temperature
Contract hour
Low flow cut-off mark
Meter ID
Run enable
Calculated compressibility
Tap location
Pipe diameter
Orifice diameter
AGA calculation method
PEMEX Units
kg/cm
2
ABS kg/cm
2
°
C
- inches H
2
O
-
inches inches
Gas Composition Configuration
These registers configure the gas composition for stream 1. Stream 1 values are used by each flow run.
Realflo checks the validity of the entered components using the following limits:
Individual components are in the ranges listed in the table below.
The Total of all Components field displays the sum of all components.
The total of all components needs to be 1.0000 (+/- 0.00001) if
Composition Units is set to Mole Fractions or 100% (+/- 0.00001%) if
Composition Units is set to Percent.
Register Field
8031
8032
8033
8034
Methane
Nitrogen
Carbon Dioxide
Ethane
Format / Units
%
%
%
%
Realflo User and Reference Manual
May 19, 2011
920
8045
8046
8047
8048
8049
8050
8051
8052
8053
8054
8035
8036
8037
8038
8039
8040
8041
8042
8043
8044
Propane
Water
Hydrogen Sulphide
Hydrogen
Carbon Monoxide
Oxygen i-Butane n-Butane i-Pentane n-Pentane n-Hexane n-Heptane n-Octane n-Nonane n-Decane
Helium
Argon unused
Relative Density
Heating Value
PEMEX Modbus Protocol Interface
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
-
BTU(60)/ft
3
Gas Component Ranges
The range of the fractional values of the components cannot be predetermined. The valid gas components are shown below. There are two ranges shown for each gas component. Realflo accepts any value in the
Expanded Range. Only values in the Normal Range will work in all circumstances.
Component Normal Range Expanded Range
Methane CH
4
Nitrogen
.4500 to 1.0000 0 to 1.0000
0 to 0.5000 0 to 1.0000
Carbon Dioxide
Ethane C
2
H
6
Propane C
3
H
8
Water
0 to 0.3000
0 to 0.1000
0 to 0.0400
0 to 0.0005
Hydrogen Sulfide 0 to 0.0002
0 to 1.0000
0 to 1.0000
0 to 0.1200
0 to 0.0300
0 to 1.0000
Hydrogen 0 to 0.1000
Carbon Monoxide 0 to 0.0300
Oxygen 0
0 to 0.0100 Total Butanes
iButane
nButane
Total Pentanes
iPentane
0 to 0.0300
0 to 1.0000
0 to 0.0300
0 to 0.2100
0 to 0.0600
0 to 0.0400
Realflo User and Reference Manual
May 19, 2011
921
PEMEX Modbus Protocol Interface
Component
nPentane
Total Hexane Plus
nHexane
nHeptane
nOctane
nNonane
nDecane
Helium
Argon
Normal Range Expanded Range
0 to 0.0200
0 to 0.0200
0
0 to 0.0400
0 to 0.0300
0 to 0.0100
Meter Run 2 Configuration
AGA Configuration
These registers are used to configure the AGA configuration for meter run 1.
8621
8622
8623
8624
8625
8626
8627
Register Field
8628
8629
8630
8631
8632
PEMEX Units
Atmospheric pressure
Base pressure kg/cm
2
ABS kg/cm
2
Base temperature
°
C
Contract hour
Low flow cut-off mark
Meter ID
Run enable
- inches H
-
2
O
Calculated compressibility
Tap location
Pipe diameter
inches
Orifice diameter inches
AGA calculation method
Gas Composition Configuration
Gas composition configuration is shared with run 1 in registers 8031 to
8054.
Meter Run 3 Configuration
AGA Configuration
These registers are used to configure the AGA configuration for meter run 1.
Register Field
8641
8642
8643
Atmospheric pressure
Base pressure
Base temperature
PEMEX Units
kg/cm
2
ABS kg/cm
2
°
C
Realflo User and Reference Manual
May 19, 2011
922
8644
8645
8646
8647
8648
8649
8650
8651
8652
PEMEX Modbus Protocol Interface
Contract hour
Low flow cut-off mark
- inches H
2
O
- Meter ID
Run enable
Calculated compressibility
Tap location
Pipe diameter
Orifice diameter inches inches
AGA calculation method
Gas Composition Configuration
Gas composition configuration is shared with run 1 in registers 8031 to
8054.
Meter Run 4 Configuration
AGA Configuration
These registers are used to configure the AGA configuration for meter run 1.
Gas Composition Configuration
Gas composition configuration is shared with run 1 in registers 8031 to
8054.
Configuration Values
Calculated Compressibility
The values used for the Calculated Compressibility field are specified below.
Value
5.0
Calculated Compressibility
AGA-8 1992 Detailed
Tap Location
8661
8662
8663
8664
8665
8666
8667
Register Field
8668
8669
8670
8671
8672
PEMEX Units
Atmospheric pressure
Base pressure
Base temperature kg/cm
2
ABS kg/cm
2
°
C
Contract hour
Low flow cut-off mark
Meter ID
Run enable
Calculated compressibility
- inches H
2
O
-
Tap location
Pipe diameter
inches
Orifice diameter inches
AGA calculation method
The values used for the Tap Location field are specified below.
Value Tap Location
Realflo User and Reference Manual
May 19, 2011
923
PEMEX Modbus Protocol Interface
0.0
1.0
Tap upstream
Tap downstream
Run Enable
The values used for the Run Enable field are specified below.
Value
0.0
1.0
Run Enable
Inhibit
Enable
AGA Calculation Method
The values used for the AGA Calculation Method field are specified below.
Value
0.0
1.0
2.0
3.0
AGA Calculation Method
AGA-3 1985
AGA-7 1985
AGA-3 1992
V-Cone
Time Synchronization
Time synchronization registers are in floating point format.
The Modbus registers for time synchronization are downloaded using function code 16 (hex 10).
The Modbus registers for time synchronization are uploaded using function code 3.
The configuration request (upload/download) uses 2 registers and 8 bytes.
Modbus Register
9999
10000
Description Format
Date
Time
MMDDYY.0
HHMMSS.0
Access
Read / Write
Read / Write
Event and Alarm Log
The Flow Computer event and alarm logs can be read as the PEMEX
Modbus event/alarm log. The Flow Computer alarms events numbers are converted to changes in the PEMEX Modbus Variables. The tables below show the Flow Computer alarms/events and the corresponding PEMEX
Modbus item number.
A large number of events and alarms don't have a corresponding item number in the PEMEX Modbus specification. So that they can be reported in the PEMEX Modbus event/alarm log, item numbers have been created for them. These item numbers begin at 8001.
In the following tables, some variables are described with an offset. The offset is determined by the flow run.
Run
1
2
3
4
5
Poffset
0
18
36
54
72
Noffset
0
1000
2000
3000
4000
Realflo User and Reference Manual
May 19, 2011
924
Run
6
7
Poffset
90
108
PEMEX Modbus Protocol Interface
Noffset
5000
6000
The Flow Computer logs contain information that needs to be mapped into the PEMEX Modbus event format.
The Event ID is mapped into the change bit map and the register number.
The Sequential event or alarm number is not reported.
The User number is not reported directly, as there is no field. There is a bit indicating the source of the alarm or event as the operator or the flow computer. The user number is mapped into this.
The date of event or alarm is converted to the PEMEX date format.
The time of event or alarm is converted to the PEMEX time format.
The new data associated with the event or alarm is reported in the alarm/event.
The previous data associated with the event or alarm is reported in the alarm/event.
The PEMEX interface assumes that there is one log for all of the flow runs.
It contains alarms and events. Alarms and events have similar but not identical formats. Alarms and events are returned in the same response to a command.
Alarms and events cannot be read after they have been acknowledged. This happens immediately after they are read from the flow computer.
When using Realflo to retrieve events or flow history, the read all events selection needs to be used, otherwise the events will be acknowledged as being read, and the host will not have direct access to that data.
Global Alarms and Events
The gas flow computation engine creates these events.
Realflo
Number
10001
10002
10003
10004
10005
10006
10007
10008
10009
10010
10011
10012
10013
10014
10015
Description Pemex Item
Power On - Cold Boot
Power On
– Warm Boot
Lost Events
Recovered from Input Error
8001
8002
9001 + Noffset
9002 + Noffset
Set Input: Units Type
Set Input: Flow Calculation Type
9003 + Noffset
9004 + Noffset
Set Input: Compressibility Calculation Type 7616 + Poffset
Set Input: Temperature Register 9005 + Noffset
Set Input: Temperature Input at Zero Scale 9006 + Noffset
Set Input: Temperature Input at Full Scale 9007 + Noffset
Set Input: Temperature at Zero Scale
Set Input: Temperature at Full Scale
9008 + Noffset
9009 + Noffset
Set Input: Pressure Register
Set Input: Pressure Input at Zero Scale
Set Input: Pressure Input at Full Scale
9010 + Noffset
9011 + Noffset
9012 + Noffset
Realflo User and Reference Manual
May 19, 2011
925
PEMEX Modbus Protocol Interface
Realflo
Number
10028
10029
10030
10031
10032
10033
10034
10035
10036
10037
10016
10017
10018
10019
10020
10021
10022
10023
10024
10025
10026
10027
10038
10039
10040
10041
10042
10043
10044
10046
10047
10048
10049
10050
10051
10052
10053
10054
10055
10056
10057
Description Pemex Item
Set Input: Pressure at Zero Scale
Set Input: Pressure at Full Scale
Set Input: DP Register
Set Input: DP Input at Zero Scale
Set Input: DP Input at Full Scale
Set Input: DP at Zero Scale
Set Input: DP at Full Scale
Set Contract: Units Type
Set Contract: Base Temperature
Set Contract: Base Pressure
Set Input: Atmospheric Pressure
Set Input: Static Pressure Tap Location
9013 + Noffset
9014 + Noffset
9015 + Noffset
9016 + Noffset
9017 + Noffset
9018 + Noffset
9019 + Noffset
9020 + Noffset
7622 + Poffset
7621 + Poffset
7623 + Poffset
7615 + Poffset
Set Contract: Contract Hour
Change Execution State
Set RTC Year
Set RTC Month
Set RTC Day
7624 + Poffset
7612 + Poffset
8003
8004
8005
Set RTC Hour
Set RTC Minute
Set RTC Second
8006
8007
8008
Set Input: Temperature Low Level Cutoff 9021 + Noffset
Set Input: Temperature Low Level hysteresis
9022 + Noffset
Set Input: Temperature High Level Cutoff 9023 + Noffset
Set Input: Temperature High Level
Hysteresis
9024 + Noffset
Set Input: Pressure Low Level Cutoff 9025 + Noffset
Set Input: Pressure Low Level Hysteresis 9026 + Noffset
Set Input: Pressure High Level Cutoff 9027 + Noffset
Set Input: Pressure High Level Hysteresis 9028 + Noffset
Set Input: Save Low/High Flow Events 9029 + Noffset
Invalid User Event 9031 + Noffset
9032 + Noffset Start Temperature Calibration: Forced temperature input
End Temperature Calibration: Removed forced temperature input
Start Static Pressure Calibration: Forced
SP input
9033 + Noffset
9034 + Noffset
9035 + Noffset End Static Pressure Calibration: Removed forced SP input
Start Differential Pressure Calibration:
Forced DP input
End Differential Pressure Calibration:
Removed forced DP input
Start Pulse Counter Calibration: Forced pulse count rate
End Pulse Counter Calibration: Removed forced pulse count rate
Set User Number
Set User Security Level
Set Input: Temperature Register Type
9036 + Noffset
9037 + Noffset
9038 + Noffset
9039 + Noffset
8009
8010
9040 + Noffset
Realflo User and Reference Manual
May 19, 2011
926
PEMEX Modbus Protocol Interface
10093
10094
10095
10096
10097
10098
10099
10100
10101
10102
10084
10085
10086
10087
10088
10089
10090
10091
10092
Realflo
Number
10058
10059
10060
10061
10062
10063
10064
10065
10066
10067
10068
10069
10071
10072
10073
10074
10075
10076
10077
10078
10079
10080
10081
10082
10083
Description Pemex Item
Set Input: Pressure Register Type 9041 + Noffset
Set Input: DP Register Type 9042 + Noffset
Set Input: Temperature Input at Zero Scale 9043 + Noffset
Set Input: Temperature Input at Full Scale 9044 + Noffset
Set Input: Pressure Input at Zero Scale
Set Input: Pressure Input at Full Scale
Set Input: DP Input at Zero Scale
Set Input: DP Input at Full Scale
Set Input: Pulse Counter Register
Set Input: Pulse Counter Register Type
Set Active Runs
Lost Alarms
9045 + Noffset
9046 + Noffset
9047 + Noffset
9048 + Noffset
9049 + Noffset
9050 + Noffset
7604
9051 + Noffset
Firmware Version
Application Version
Set Flow Computer ID
Set Contract: Input Err Action
Set Run ID
Power Off
Start Plate Change: Forced temperature input
8011
8012
7603
9053 + Noffset
7611 + Poffset
8013
9054 + Noffset
End Plate Change: Removed forced temperature input
Start Plate Change: Forced static pressure input
End Plate Change: Removed forced static pressure input
Start Plate Change: Forced differential pressure input
End Plate Change: Removed forced differential pressure input
Set Input: altitude and latitude compensation
Set Input: altitude
Set Input: latitude
Forced temperature input
9055 + Noffset
9056 + Noffset
9057 + Noffset
9058 + Noffset
9059 + Noffset
9060 + Noffset
9061 + Noffset
9062 + Noffset
7628 + Poffset
Removed forced temperature input
Forced static pressure input
Removed forced static pressure input
7628 + Poffset
7627 + Poffset
7627 + Poffset
Forced differential pressure input 7625 + Poffset
Removed forced differential pressure input 7625 + Poffset
Forced pulse count rate 7626 + Poffset
Removed forced pulse count rate
Set Contract: wet gas meter factor
Set Input: Pulse Counter Register
Set Input: Pulse K Factor
Set Input: Pulse Units
Set Input: Base Compressibility Calc
Set Input: Averaging Type
Set Input: Default Input Type
Set Input: Default Temperature
Set Input: Default Static Pressure
7626 + Poffset
9063 + Noffset
9064 + Noffset
9065 + Noffset
9066 + Noffset
9067 + Noffset
9068 + Noffset
9069 + Noffset
9070 + Noffset
9071 + Noffset
Realflo User and Reference Manual
May 19, 2011
927
PEMEX Modbus Protocol Interface
Realflo
Number
10103
10104
10105
10106
10107
10108
10109
10110
10111
10114
Description Pemex Item
Set Input: Default Differential Pressure
Set gas quality source (Pemex only)
Set Input: Flow Direction Control
Set Input: Flow Direction Register
9072 + Noffset
9073 + Noffset
9074 + Noffset
9075 + Noffset
Forced mass flow input
Restored live mass flow input
Starting Calibration: Forced mass flow rate input
Ending Calibration: Restored live mass flow rate input
9076 + Noffset
9077 + Noffset
9078 + Noffset
9079 + Noffset
Set Input: Mass Flow Rate Register Type 9080 + Noffset
Set Input: On Indicates 9081 + Noffset
Realflo User and Reference Manual
May 19, 2011
928
PEMEX Modbus Protocol Interface
AGA-3 (1985) Alarms and Events
These events are specific to the AGA-3 (1985) calculation.
Realflo
Number
10201
10202
10203
10204
10205
10206
10207
10208
10209
10210
10211
10212
10213
10214
10215
10216
10217
10218
10219
10220
10221
10222
10223
Description PEMEX Item
Failed To Create AGA-3 (1985) Data
Structure
Created AGA-3 (1985) with Execution
Stopped
9101 + Noffset
9102 + Noffset
Created AGA-3 (1985) with Execution
Running
9103 + Noffset
Destroyed AGA-3 (1985) Data Structure 9104 + Noffset
Recovered from AGA-3 (1985) error
Set AGA-3 (1985): Input Units Type
Set AGA-3 (1985): Orifice Material
Set AGA-3 (1985): Pipe Material
Set AGA-3 (1985): Static Pressure Tap
Location
Set AGA-3 (1985): Orifice Diameter
Set AGA-3 (1985): Orifice Measurement
Reference Temperature
9105 + Noffset
9106 + Noffset
9107 + Noffset
9108 + Noffset
7615 + Poffset
7618 + Poffset
9109 + Noffset
Set AGA-3 (1985): Pipe Diameter
Set AGA-3 (1985): Pipe Diameter
Measurement Reference Temperature
Set AGA-3 (1985): Isentropic Exponent
Set AGA-3 (1985): Viscosity
Set AGA-3 (1985): Base Temperature
7617 + Poffset
9110 + Noffset
9111 + Noffset
9112 + Noffset
7622 + Poffset
Set AGA-3 (1985): Base Pressure 7621 + Poffset
Set AGA-3 (1985): Atmospheric Pressure 7623 + Poffset
Failed To Set AGA-3 (1985) Configuration 9113 + Noffset
Set AGA-3 (1985): Contract Units Type 9114 + Noffset
Set AGA-3 (1985): Temperature deadband
9115 + Noffset
Set AGA-3 (1985): Static Pressure deadband
9116 + Noffset
Set AGA-3 (1985): Differential Pressure deadband
9117 + Noffset
AGA-3 (1992) Alarms and Events
These events are specific to the AGA-3 (1992) calculation.
Realflo
Number
10301
10302
10303
10304
10305
10306
Description PEMEX Item
Failed To Create AGA-3 (1992) Data
Structure
Created AGA-3 (1992) with Execution
Stopped
Created AGA-3 (1992) with Execution
Running
9151 + Noffset
9152 + Noffset
9153 + Noffset
Destroyed AGA-3 (1992) Data Structure 9154 + Noffset
Restored from AGA-3 (1992) error 9155 + Noffset
Set AGA-3 (1992): Input Units Type 9156 + Noffset
Realflo User and Reference Manual
May 19, 2011
929
PEMEX Modbus Protocol Interface
10314
10315
10316
10317
10318
10319
10320
10321
10322
10323
10324
10325
Realflo
Number
10307
10308
10309
10310
10311
10312
10313
10326
10327
Description PEMEX Item
Set AGA-3 (1992): Orifice Material
Set AGA-3 (1992): Pipe Material
Set AGA-3 (1992): Static Pressure Tap
Location
Set AGA-3 (1992): Orifice Diameter
Set AGA-3 (1992): Orifice reference temperature
Set AGA-3 (1992): Pipe Diameter
Set AGA-3 (1992): Pipe Diameter
Measurement Temperature
9157 + Noffset
9158 + Noffset
7615 + Poffset
7618 + Poffset
9159 + Noffset
7617 + Poffset
9160 + Noffset
Set AGA-3 (1992): Isentropic Exponent
Set AGA-3 (1992): Viscosity
Set AGA-3 (1992): Base Temperature
9161 + Noffset
9162 + Noffset
7622 + Poffset
Set AGA-3 (1992): Base Pressure 7621 + Poffset
Set AGA-3 (1992): Atmospheric Pressure 7623 + Poffset
Failed To Set AGA-3 (1992) Configuration 9163 + Noffset
Set Input: DP Low Level Cutoff
Set Input: DP Low Level Hysteresis
7619 + Poffset
9164 + Noffset
Set Input: DP High Level Cutoff
Set Input: DP High Level Hysteresis
Set AGA-3 (1992): Contract Units Type
Set AGA-3 (1992): Temperature deadband
Set AGA-3 (1992): Static Pressure deadband
Set AGA-3 (1992): Differential Pressure deadband
9165 + Noffset
9166 + Noffset
9167 + Noffset
9168 + Noffset
9169 + Noffset
9170 + Noffset
AGA-7 Alarms and Events
These events are specific to the AGA-7 calculation.
Realflo
Number
10701
10702
10703
10704
10705
10706
10707
10708
10709
10710
10711
10712
10713
10714
10715
10716
Description PEMEX Item
Failed To Create AGA-7 Data Structure 9201 + Noffset
Created AGA-7 with Execution Stopped 9202 + Noffset
Created AGA-7 with Execution Running 9203 + Noffset
Destroyed AGA-7 Data Structure 9204 + Noffset
Restored from AGA-7 error 9205 + Noffset
Set AGA-7: Input Units Type
Set AGA-7: K factor
Set AGA-7: M factor
Set AGA-7: Atmospheric Pressure
Set AGA-7: Base Pressure
Set AGA-7: Base Temperature
Failed To Set AGA-7 Configuration
9206 + Noffset
7620 + Poffset
9207 + Noffset
7623 + Poffset
7621 + Poffset
7622 + Poffset
9208 + Noffset
Set Input: Turbine Low Flow Pulse Limit 9209 + Noffset
Set Input: Turbine Low Flow Detect Time 9210 + Noffset
Set AGA-7: Contract Units Type 9211 + Noffset
Set AGA-7: Volume Option 9212 + Noffset
Realflo User and Reference Manual
May 19, 2011
930
PEMEX Modbus Protocol Interface
AGA-11Alarms and Events
These events are specific to the AGA-11calculation.
Realflo
Number
11101
11102
11103
11104
11105
11106
11107
11108
11109
11110
Description PEMEX Item
Failed To Create AGA-11 Data Structure 9401 + Noffset
Created AGA-11 with Execution Stopped 9402 + Noffset
Created AGA-11 with Execution Running 9403+ Noffset
Destroy AGA-11 Data Structure
Recovered from AGA-11 error
Change in AGA-11 units configuration
9404+ Noffset
9405 + Noffset
9406+ Noffset
Change in AGA-11 contract units config
Change in AGA-11 base temperature
Change in AGA-11 base pressure
Failed To Set AGA-11 Configuration
9407+ Noffset
9408+ Noffset
9409+ Noffset
9410+ Noffset
V-Cone Alarms and Events
These events are specific to the V-Cone calculation.
12221
12222
12223
12224
12225
12226
12227
12228
12229
12208
12209
12210
12211
12212
12213
12214
12215
12216
12217
12218
12219
12220
Realflo
Number
12201
12202
12203
12204
12205
12206
12207
Description PEMEX Item
Failed To Create V-Cone Date Structure 9251 + Noffset
Created V-Cone with Execution Stopped 9252 + Noffset
Created V-Cone with Execution Running 9253 + Noffset
Destroyed V-Cone Data Structure
Restored from V-Cone Error
Failed To Set V-Cone Configuration
Set V-Cone Cone Measurement
Temperature
9254 + Noffset
9255 + Noffset
9256 + Noffset
9257 + Noffset
Set V-Cone Input Units Type
Set V-Cone Contract Units Type
Set V-Cone Cone Material
Set V-Cone Pipe Material
Set V-Cone Cone Diameter
9258 + Noffset
9259 + Noffset
9260 + Noffset
9261 + Noffset
9262 + Noffset
Set V-Cone Inside Pipe Diameter 9263 + Noffset
Set V-Cone Pipe reference temperature 9264 + Noffset
Set V-Cone Isentropic Exponent 9265 + Noffset
Set V-Cone Viscosity
Set V-Cone Base Temperature
Set V-Cone Base Pressure
Set V-Cone Atmospheric Pressure
Set Table Point 1 Reynolds Number
9266 + Noffset
7622 + Poffset
7621 + Poffset
7623 + Poffset
9267 + Noffset
Set Table Point 2 Reynolds Number
Set Table Point 3 Reynolds Number
Set Table Point 4 Reynolds Number
Set Table Point 5 Reynolds Number
Set Table Point 6 Reynolds Number
Set Table Point 7 Reynolds Number
Set Table Point 8 Reynolds Number
Set Table Point 9 Reynolds Number
Set Table Point 10 Reynolds Number
9268 + Noffset
9269 + Noffset
9270 + Noffset
9271 + Noffset
9272 + Noffset
9273 + Noffset
9274 + Noffset
9275 + Noffset
9276 + Noffset
Realflo User and Reference Manual
May 19, 2011
931
PEMEX Modbus Protocol Interface
Realflo
Number
12230
12231
12232
12233
12234
12235
12236
12237
12238
12239
12241
12242
12243
Description
Set Table Point 1 Flow Coefficient
Set Table Point 2 Flow Coefficient
Set Table Point 3 Flow Coefficient
Set Table Point 4 Flow Coefficient
Set Table Point 5 Flow Coefficient
Set Table Point 6 Flow Coefficient
Set Table Point 7 Flow Coefficient
Set Table Point 8 Flow Coefficient
Set Table Point 9 Flow Coefficient
Set Table Point 10 Flow Coefficient
Set Wet Gas Correction Factor Method
Set Density of liquid at flow conditions
Set Mass flow rate of liquid at flow conditions
PEMEX Item
9277 + Noffset
9278 + Noffset
9279 + Noffset
9280 + Noffset
9281 + Noffset
9282 + Noffset
9283 + Noffset
9284 + Noffset
9285 + Noffset
9286 + Noffset
9287 + Noffset
9288 + Noffset
9289 + Noffset
AGA-8 Alarms and Events
These events are specific to the AGA-8 calculation.
Realflo
Number
10801
10802
10803
10804
10805
10806
10807
10808
10809
10810
10811
10812
10813
10814
10815
10816
10817
10818
10819
10820
10821
10822
10823
10824
10825
10826
Description PEMEX Item
Failed To Create AGA-8 Data Structure 9301 + Noffset
Created AGA-8 with Execution Stopped 9302 + Noffset
Created AGA-8 with Execution Running 9303 + Noffset
Destroyed AGA-8 Data Structure
Set AGA-8 Gas: Change Gas Fractions
9304 + Noffset
9305 + Noffset
Set AGA-8 Gas: Methane (CH4)
Set AGA-8 Gas: Nitrogen
Set AGA-8 Gas: Carbon Dioxide (CO2)
Set AGA-8 Gas: Ethane (C2H6)
Set AGA-8 Gas: Propane (C3H8)
Set AGA-8 Gas: Water
Set AGA-8 Gas: Hydrogen Sulphide
(H2S)
7719
7720
7721
7722
7723
7724
7725
Set AGA-8 Gas: Hydrogen 7726
Set AGA-8 Gas: Carbon Monoxide (CO) 7727
Set AGA-8 Gas: Oxygen 7728
Set AGA-8 Gas: I-Butane
Set AGA-8 Gas: n-Butane
Set AGA-8 Gas: I-Pentane
7729
7730
7731
Set AGA-8 Gas: n-Pentane
Set AGA-8 Gas: n-hexane (when using individual gas components)
Set AGA-8 Gas: n-hexane + (when using combined value for hexane and higher components)
7732
7733
Set AGA-8 Gas: n-Heptane
Set AGA-8 Gas: n-Octane
Set AGA-8 Gas: n-Nonane
Set AGA-8 Gas: n-Decane
Set AGA-8 Gas: Helium
Set AGA-8 Gas: Argon
7734
7735
7736
7737
7738
7739
Realflo User and Reference Manual
May 19, 2011
932
PEMEX Modbus Protocol Interface
Realflo
Number
10827
10828
10829
10830
10831
10832
10833
10834
10835
10836
10837
10838
10839
10840
10841
10842
10843
10844
Description PEMEX Item
Set AGA-8 Gas: Failed To Set
Failed To Set AGA-8 Configuration
Set AGA-8: Input Units Type
Set AGA-8: Base Temperature
9306 + Noffset
9307 + Noffset
9308 + Noffset
7622 + Poffset
Set AGA-8: Base Pressure
Set AGA-8: Atmospheric Pressure
7621 + Poffset
7623 + Poffset
Set AGA-8: Static Pressure Tap Location 7615 + Poffset
Set AGA-8: Contract Units Type
Clear Compressibility Error
Set AGA-8: gas composition logging
9309 + Noffset
9310 + Noffset
9311 + Noffset
Set AGA-8 Gas: Use Hexanes+ 9312 + Noffset
Set AGA-8 Hexane + Ratio for n-hexane 9313 + Noffset
Set AGA-8 Hexane + Ratio for n-heptane 9314 + Noffset
Set AGA-8 Hexane + Ratio for n-octane 9315 + Noffset
Set AGA-8 Hexane + Ratio for n-nonane 9316 + Noffset
Set AGA-8 Hexane + Ratio for n-decane 9317 + Noffset
Set AGA-8 Laboratory real relative density
7740
0 = calculate value
0.07 to 1.52 = use value
Set AGA-8 Laboratory heating value:
0 = calculate value
0 to 1800 = use value
7741
NX-19 Alarms and Events
These events are specific to the NX-19 calculation.
Realflo
Number
11901
11902
11903
11904
11905
11906
11907
11908
11909
11910
11911
11912
11913
11914
11915
11916
11917
11918
11919
Description PEMEX Item
Failed to Create NX-19 Data Structure
Created NX-19 with Execution Stopped
Created NX-19 with Execution Running
Destroyed NX-19 Data Structure
Restored from NX-19 error
Set NX-19: Calculation Method
Set NX-19: Specific Gravity
Set NX-19: Gas: Carbon Dioxide
Set NX-19: Gas: Methane
9351 + Noffset
9352 + Noffset
9353 + Noffset
9354 + Noffset
9355 + Noffset
9356 + Noffset
7740
7721
7719
Set NX-19: Gas: Nitrogen
Set NX-19: Heating Value
7720
7741
Set NX-19: Static Pressure Tap Location 7615 + Poffset
Set NX-19: Base Pressure
Set NX-19: Base Temperature
Failed to set NX-19 Gas Components
Failed to set NX-19 Contract
Configuration
7621 + Poffset
7622 + Poffset
9357 + Noffset
9358 + Noffset
Set NX-19: Contract Units Type
Clear Compressibility Error
Set NX-19: gas composition logging disabled
9359 + Noffset
9360 + Noffset
9361 + Noffset
Realflo User and Reference Manual
May 19, 2011
933
PEMEX Modbus Protocol Interface
MVT Alarms and Events
These events are specific to the MVT transmitter.
Realflo
Number
13100
13101
13102
13103
13104
13105
13106
13107
13108
13109
13110
13111
13112
13113
13114
13115
13116
13117
13118
13119
13120
13121
13122
13123
13124
13125
13126
13127
13128
Description
Set MVT Transmitter 1: polling status
Set MVT Transmitter 1: serial port
Set MVT Transmitter 1: Address of transmitter
Set MVT Transmitter 1: Timeout
Set MVT Transmitter 1: Manufacturer
Code
Set MVT Transmitter 1: Turnaround Delay
Time
Set MVT Transmitter 1: Differential
Pressure units
Set MVT Transmitter 1: Static Pressure units
Set MVT Transmitter 1: Temperature units
Set MVT Transmitter 1: Serial number
Set MVT Transmitter 1: Tag
Set MVT Transmitter 1: Differential
Pressure damping
Set MVT Transmitter 1: Differential
Pressure upper operating limit
Set MVT Transmitter 1: Differential
Pressure lower operating limit
Set MVT Transmitter 1: Static Pressure damping
Set MVT Transmitter 1: Static Pressure upper operating limit
Set MVT Transmitter 1: Static Pressure lower operating limit
Set MVT Transmitter 1: Temperature damping
Set MVT Transmitter 1: Temperature upper operating limit
Set MVT Transmitter 1: Temperature lower operating limit
MVT Transmitter 1: lost communication
MVT Transmitter 1: transmitter configuration incorrect
MVT Transmitter 1: temperature sensor out of range
MVT Transmitter 1: static pressure sensor out of range
MVT Transmitter 1: differential pressure sensor out of range
MVT Transmitter 1: not polled
Set MVT Transmitter 1: Type Code
Set MVT Transmitter 1: IP Address
Set MVT Transmitter 1: IP Protocol
PEMEX Item
9601 + Noffset
9602 + Noffset
9603 + Noffset
9604 + Noffset
9605 + Noffset
9606 + Noffset
9607 + Noffset
9608 + Noffset
9609 + Noffset
9610 + Noffset
9611 + Noffset
9612 + Noffset
9613 + Noffset
9614 + Noffset
9615 + Noffset
9616 + Noffset
9617 + Noffset
9618 + Noffset
9619 + Noffset
9620 + Noffset
9621 + Noffset
9622 + Noffset
9623 + Noffset
9624 + Noffset
9625 + Noffset
9626 + Noffset
9627 + Noffset
9628 + Noffset
9629 + Noffset
Realflo User and Reference Manual
May 19, 2011
934
PEMEX Modbus Protocol Interface
Realflo
Number
13129
13130
13131
13132
13133
13134
13135
13136
13137
13138
13139
13140
13141
13142
Description PEMEX Item
MVT Transmitter 1: temperature sensor value is bad
MVT Transmitter 1: static pressure sensor value is bad
MVT Transmitter 1: differential pressure sensor value is bad
Set MVT Transmitter 1: Atmospheric
Pressure Offset
9630 + Noffset
9631 + Noffset
9632 + Noffset
9633 + Noffset
MVT Transmitter 1: Restore for all communication alarms
9634 + Noffset
MVT Transmitter 1: Restore for all alarms 9635 + Noffset
MVT Transmitter 1: Sensors are Off Line 9636 + Noffset
MVT Transmitter 1: RTD is disconnected 9637 + Noffset
MVT Transmitter 1: Temperature Sensor
Above Range
MVT Transmitter 1: Static Pressure
Above Range
MVT Transmitter 1: Differential Pressure
Above Range
MVT Transmitter 1: Temperature Sensor
Below Range
MVT Transmitter 1: Static Pressure Below
Range
MVT Transmitter 1: Differential Pressure
Below Range
9638 + Noffset
9639 + Noffset
9640 + Noffset
9641 + Noffset
9642 + Noffset
9643 + Noffset
Coriolis Meter Alarms and Events
Realflo
Number
14001
14002
14003
14004
14005
14006
14007
14008
Description PEMEX Item
Failed To Set Coriolis Meter
Set Coriolis Meter: Meter Address
Set Coriolis Meter: Meter Port
Set Coriolis Meter: Meter Timeout
Coriolis Meter: Lost Communication
9651 + Noffset
9652 + Noffset
9653 + Noffset
9654 + Noffset
9655 + Noffset
Coriolis Meter: Communication Restored 9656 + Noffset
Coriolis Meter: Not Polled 9657 + Noffset
Coriolis Meter: Coriolis Meter has bad response
9658 + Noffset
Calibration and User Defined Alarms and Events
Realflo generates these events when performing calibration (not by the flow computer).
Realflo
Number
19003
19004
19005
19006
19007
Description
As-Found Temperature
As-Left Temperature
Target Re-Zero Temperature
Target Temperature Span
Set Default Temperature
PEMEX Item
9703 + Noffset
9704 + Noffset
9705 + Noffset
9706 + Noffset
9707 + Noffset
Realflo User and Reference Manual
May 19, 2011
935
PEMEX Modbus Protocol Interface
Realflo
Number
19008
19009
19013
19014
19015
19016
19018
19019
19023
19024
19025
19026
19028
19029
19033
19034
Description PEMEX Item
After Re-Zero Temperature
After Calibrate Temperature Span
As-Found Static Pressure
As-Left Static Pressure
Target Re-Zero Static Pressure
Target Static Pressure Span
After Re-Zero Static Pressure
After Calibrate Static Pressure Span
As-Found Differential Pressure
As-Left Differential Pressure
Target Re-Zero Differential Pressure
Target Differential Pressure Span
9708 + Noffset
9709 + Noffset
9713 + Noffset
9714 + Noffset
9715 + Noffset
9716 + Noffset
9718 + Noffset
9719 + Noffset
9723 + Noffset
9724 + Noffset
9725 + Noffset
9726 + Noffset
After Re-Zero Differential Pressure 9728 + Noffset
After Calibrate Differential Pressure Span 9729 + Noffset
As-Found Pulse Count 9733 + Noffset
As-Left Pulse Count 9734 + Noffset
Calculation Engine Errors
The flow calculation engine generates these errors.
Realflo
Number
20001
20003
20004
20005
20006
20007
20008
20009
20010
20011
20012
20050
20051
20052
20053
20054
20055
20056
20057
Description PEMEX Item
Meter control structure not found
Temperature input is below zero scale
Temperature input is above full scale
9751 + Noffset
9752 + Noffset
9753 + Noffset
Static pressure input is below zero scale 9754 + Noffset
Static pressure input is above full scale 9755 + Noffset
Differential pressure input is below zero scale
9756 + Noffset
Differential pressure input is above full scale
9757 + Noffset
Compressibility calculation inputs invalid 9758 + Noffset
Forced input register 9759 + Noffset
Removed force from input register
Low battery alarm
9760 + Noffset
9761 + Noffset
Restore from temperature input low alarm 9762 + Noffset
Restore from temperature input high alarm
Restore from static pressure input low alarm
Restore from static pressure input high alarm
Restore from differential pressure input low alarm
Restore from differential pressure input high alarm
Restore from low pulse input alarm
Restore from input alarm
9763 + Noffset
9764 + Noffset
9765 + Noffset
9766 + Noffset
9767 + Noffset
9768 + Noffset
9769 + Noffset
Realflo User and Reference Manual
May 19, 2011
936
PEMEX Modbus Protocol Interface
AGA-3 (1985) Calculation Errors
These errors are generated by the AGA-3 (1985) calculation.
Realflo
Number
20210
20229
20232
20233
20234
20227
Description
AGA-3 (1985)
– Flowing temperature is at or below absolute zero
AGA-3 (1985) - Ratios from AGA-8 or NX-
19 were not available
AGA-3 (1985) - Static pressure below differential
AGA-3 (1985) - Static pressure zero or negative
AGA-3 (1985)
– Bad Calculation
AGA-3 (1985)
– Differential Pressure Neg or Zero
PEMEX Item
9801 + Noffset
9802 + Noffset
9803 + Noffset
9804 + Noffset
9805 + Noffset
9806 + Noffset
AGA-3 (1992) Calculation Errors
These errors are generated by the AGA-3 (1992) calculation.
Realflo
Number
20310
20325
20329
20332
20333
20334
20335
Description
AGA-3 (1992)
– Flowing temperature is at or below absolute zero
AGA-3 (1992)
– Too many Iterations
AGA-3 (1992)
– Ratios from AGA-8 or
NX-19 were not available
AGA-3 (1992) - Static pressure below differential
AGA-3 (1992) - Static pressure zero or negative
AGA-3 (1992)
– Bad Calculation
AGA-3 (1992)
– Differential Pressure Neg or Zero
PEMEX Item
9834 + Noffset
9836 + Noffset
9831 + Noffset
9832 + Noffset
9833 + Noffset
9835 + Noffset
9837 + Noffset
AGA-7 Calculation Errors
These errors are generated by the AGA-7 calculation.
Realflo
Number
20712
20713
20714
20716
20720
Description PEMEX Item
AGA-7 - Temperature low 9891 + Noffset
AGA-7
– Static pressure zero or negative
9892 + Noffset
AGA-7 - Low pulse rate 9893 + Noffset
AGA-7 - Ratios from AGA-8 or NX-19 are not available
AGA-7
– Bad Calculation
9894 + Noffset
9895 + Noffset
Realflo User and Reference Manual
May 19, 2011
937
PEMEX Modbus Protocol Interface
AGA-11 Calculation Errors
These errors are generated by the AGA-11 calculation.
Realflo
Number
21101
21102
21103
21104
21105
21107
Description PEMEX Item
AGA-11 - Bad units 9861 + Noffset
AGA-11 - Bad contract units 9862 + Noffset
AGA-11 - Base Pressure negative or zero 9863 + Noffset
AGA-11 - Base Temperature negative or zero
9864 + Noffset
AGA-11 - Bad calculation
AGA-11 - Ratios from AGA-8 were not available
9865 + Noffset
9866 + Noffset
V-Cone Calculation Errors
These errors are generated by the V-Cone calculation.
Realflo
Number
22221
22223
22227
22228
22229
22230
22231
Description PEMEX Item
V-Cone
– Temperature low
V-Cone
– Ratios from AGA-8 or NX-19 were not available
V-Cone
– Too many Iterations
V-Cone
– Static pressure below
9921 + Noffset
9922 + Noffset
9923 + Noffset
9924 + Noffset differential pressure
V-Cone
– Static pressure zero or negative 9925 + Noffset
V-Cone
– Bad Calculation
9926 + Noffset
V-Cone
– Differential Pressure Neg or
Zero
9927 + Noffset
AGA-8 Calculation Errors
These errors are generated by the AGA-8 calculation.
Realflo
Number
20809
20810
20811
20812
20814
20819
Description
AGA-8
– Flow Temperature is Low
AGA-8
– Flow Temperature is High
AGA-8
– Flow Pressure is Low
AGA-8
–Flow Press is High
AGA-8 - Not configured
AGA-8 - No gas components
NX-19 Errors
These errors are generated by the NX-19 calculation.
Realflo
Number
21913
21914
21915
21916
21917
21921
Description
NX-19
– Flow Temperature is Low
NX-19
– Flow Pressure is Low
NX-19
–Flow Press is High
NX-19 - Configuration flag not set
NX-19 - Gas ratios were not available
NX-19
– Flow Temperature is High
PEMEX Item
9951 + Noffset
9952 + Noffset
9953 + Noffset
9954 + Noffset
9955 + Noffset
9956 + Noffset
PEMEX Item
9981 + Noffset
9982 + Noffset
9983 + Noffset
9984 + Noffset
9985 + Noffset
9986 + Noffset
Realflo User and Reference Manual
May 19, 2011
938
PEMEX Modbus Protocol Interface
Retrieval and Acknowledgment of Events and Alarms
The field device is capable of storing 256 events or alarms.
Events and alarms can be retrieved using Modbus function code 3, to read register 32 (20 hex). The number of records in the host poll (request) will be ignored by the field device. The field device will return up to 12 alarms or events for each poll (alarm/event size is 20 bytes, the maximum Modbus message size is 156 bytes).
Alarm or Event Record Format
The format of the 20-byte record is as follows:
Byte Contents
1
– 2
3
– 4
5
– 8
9
– 12
Status bits
Event record number
Time of event/alarm
Date of event/alarm
13
– 16
Previous value
17
– 20
Current value
Format
See below
16-bit integer
HHMMSS.0 (32-bit float)
MMDDYY.0 (32-bit float)
32-bit float
32-bit float
If bit 9 of the status bits field is 1, then the record is an event. If bit 9 of the status bits field is 0, then the record is an alarm.
Event Status Bits
The status bits for events are as follows.
7
8
9
10
11
12
13
14
15
3
4
5
6
Bit
0
1
2
Byte 2, Bit 0
Byte 2, Bit 1
Byte 2, Bit 2
Byte 2, Bit 3
Byte 2, Bit 4
Byte 2, Bit 5
Byte 2, Bit 6
Byte 2, Bit 7
Byte 1, Bit 0
Byte 1, Bit 1
Byte 1, Bit 2
Byte 1, Bit 3
Byte 1, Bit 4
Byte 1, Bit 5
Byte 1, Bit 6
Byte 1, Bit 7
Description
Fixed value
Zero scale
Full scale
Operator value
Fixed Bit
Fixed/Variable flag
Change to table entry
Change to command system
Unused
Always 1 (event)
Low low limit
Low limit
High limit
High high limit
Rate of change limit
Unused
Alarm Status Bits
The status bits for alarms are as follows.
Bit
0
1
2
3
4
Byte 2, Bit 0
Byte 2, Bit 1
Byte 2, Bit 2
Byte 2, Bit 3
Byte 2, Bit 4
Description
Unused (0)
Unused (0)
Unused (0)
Unused (0)
Unused (0)
Realflo User and Reference Manual
May 19, 2011
939
Bit
5
6
7
8
9
10
11
12
13
14
15
Byte 2, Bit 5
Byte 2, Bit 6
Byte 2, Bit 7
Byte 1, Bit 0
Byte 1, Bit 1
Byte 1, Bit 2
Byte 1, Bit 3
Byte 1, Bit 4
Byte 1, Bit 5
Byte 1, Bit 6
Byte 1, Bit 7
PEMEX Modbus Protocol Interface
Description
Unused (0)
Unused (0)
Unused (0)
Unused (0)
0 (alarm)
Low low limit
Low limit
High limit
High high limit
Unused (0)
1 if the variable entered the alarm state.
0 if the variable returned to normal (in this case, the bits are set to 0)
Alarm Acknowledgement
To acknowledge alarms/events, the server will use Modbus function code 5 to “write” to register 32 (hex 20). The data in the message should be 1.
When the field device receives this request, only records that have been transmitted to the server will be deleted. Alarms/events that were not retrieved or occurred after the alarm/event retrieval will not be deleted.
Realflo User and Reference Manual
May 19, 2011
940
Measurement Units
Measurement Units
Definitions
Realflo supports twelve different systems of measurement. The tables below show the measurement units for each type of parameter. The Units column shows the measurement units. The Realflo Display column shows how these units are displayed on the screen and in printed reports.
The following are standard units used in the United States unit sets. The prefix M in units stands for thousands. The prefix MM in units stands for millions.
MCF is thousands of cubic feet (i.e. 10
3
ft
3
).
MMCF is millions of cubic feet (i.e. 10
6
ft
3
).
MBTU is thousands of BTU (i.e. 10
3
BTU).
MMBTU is millions of BTU (i.e. 10
6
BTU).
M in metric and SI unit sets stands for 10
6
(i.e. millions).
US1 Units
Parameters and Values
Pipe and Orifice Diameters
Static, Base and Atmospheric
Pressure
Differential Pressure
Flowing and Base Temperature
Viscosity
Density
Mass
Mass Flow Rate
Volume
Volume Flow Rate
Heating Value
Energy
Energy Flow Rate
Flow Extension
Turbine Rate
Altitude
Units
inches psi psi
°F centipoise lbm/ft
3 lbm lbm/hr ft
3 ft
3
/hr
BTU(60)/ft
3
BTU(60)
BTU(60)/hr kg/m
3 s pulses/ft
3 feet
Realflo
Display
inches psi psi
F cP lbm/ft3 lbm lbm/hr ft3 ft3/hr
BTU/ft3
BTU
BTU/hr kg/m3s pulses/ft3 feet
US2 Units
Parameters and Values Units
Pipe and Orifice Diameters inches
Static, Base and Atmospheric Pressure psi
Differential Pressure inches H at 60 °F
2
O
Flowing and Base Temperature °F
Realflo
Display
inches psi in H2O at 60F
F
Realflo User and Reference Manual
May 19, 2011
941
Parameters and Values
Viscosity
Density
Mass
Mass Flow Rate
Volume
Volume Flow Rate
Heating Value
Energy
Energy Flow Rate
Flow Extension
Turbine Rate
Altitude
Measurement Units
Units Realflo
Display
centipoise lbm/ft
3 lbm lbm/hr
MMCF
MMCF/day
BTU(60)/ft
3 cP lbm/ft3 lbm lbm/hr
MMCF
MMCF/day
BTU/ft3
MMBTU(60) MMBTU
MMBTU(60)/ day kg/m
3 s pulses/ft
3
MMBTU/day kg/m3s pulses/ft3 feet feet
US3 Units
Parameters and Values Units Realflo
Display
Pipe and Orifice Diameters inches
Static, Base and Atmospheric Pressure psi
Differential Pressure
Flowing and Base Temperature inches H
2
O at 68 °F
°F
Viscosity
Density
Mass
Mass Flow Rate
Volume
Volume Flow Rate
Heating Value
Energy
Energy Flow Rate
Flow Extension
Turbine Rate
Altitude inches psi in H2O at 68F centipoise lbm/ft
3 lbm
F cP lbm/ft3 lbm lbm/hr
MMCF
MMCF/day
BTU(60)/ft
3 lbm/hr
MMCF
MMCF/day
BTU/ft3
MMBTU(60) MMBTU
MMBTU(60)/ MMBTU/day day kg/m
3 s pulses/ft
3 kg/m3s pulses/ft3 feet feet
US4 Units
Parameters and Values Units
Pipe and Orifice Diameters
Mass
Mass Flow Rate
Volume inches
Static, Base and Atmospheric Pressure psi
Differential Pressure inches H at 60 °F
2
O
Flowing and Base Temperature
Viscosity
Density
°F centipoise lbm/ft
3 lbm lbm/hr
MCF
Realflo
Display
inches psi in H2O at 60F
F cP lbm/ft3 lbm lbm/hr
MCF
Realflo User and Reference Manual
May 19, 2011
942
Parameters and Values
Volume Flow Rate
Heating Value
Energy
Energy Flow Rate
Flow Extension
Turbine Rate
Altitude
Measurement Units
Units Realflo
Display
MCF/hr
BTU(60)/ft
3
MCF/hr
BTU/ft3
MBTU MBTU(60)
MBTU(60)/hr MBTU/hr kg/m
3 s pulses/ft
3 kg/m3s pulses/ft3 feet feet
US5 Units
Parameters and Values Units
Pipe and Orifice Diameters inches
Static, Base and Atmospheric Pressure psi
Differential Pressure
Flowing and Base Temperature
Viscosity inches H
2
O at 60 °F
°F
Density
Mass centipoise lbm/ft
3 lbm
Mass Flow Rate
Volume
Volume Flow Rate
Heating Value
Energy
Energy Flow Rate
Flow Extension
Turbine Rate
Altitude lbm/day
MCF feet
MCF/day
BTU(60)/ft
3
MBTU(60)
MBTU(60)/d ay kg/m
3 s pulses/ft
3 kg/m3s pulses/ft3 feet
Realflo
Display
inches psi in H2O at 60F
F cP lbm/ft3 lbm lbm/day
MCF
MCF/day
BTU/ft3
MBTU
MBTU/day
US6 Units
Parameters and Values Units Realflo
Display
Pipe and Orifice Diameters inches
Static, Base and Atmospheric Pressure psi
Differential Pressure
Flowing and Base Temperature
Viscosity
Density inches H
2
O at 60 °F
°F centipoise lbm/ft
3
Mass
Mass Flow Rate
Volume
Volume Flow Rate
Heating Value
Energy
Energy Flow Rate
Flow Extension inches psi in H2O at 60F
F cP lbm/ft3 lbm lbm/hr
MMCF
MMBTU(60)/ hr kg/m
3 s lbm lbm/hr
MMCF
MMCF/hr
BTU(60)/ft
3
MMCF/hr
BTU/ft3
MMBTU(60) MMBTU
MMBTU/hr kg/m3s
Realflo User and Reference Manual
May 19, 2011
943
Parameters and Values
Turbine Rate
Altitude
Units
pulses/ft
3 feet
Measurement Units
Realflo
Display
pulses/ft3 feet
US7 Units
Parameters and Values Units Realflo
Display
Pipe and Orifice Diameters inches
Static, Base and Atmospheric Pressure psi
Differential Pressure
Flowing and Base Temperature
Viscosity inches H
2
O at 60 °F
°F
Density
Mass centipoise lbm/ft
3 lbm
Mass Flow Rate
Volume
Volume Flow Rate
Heating Value
Energy
Energy Flow Rate
Flow Extension
Turbine Rate
Altitude inches psi in H2O at 60F
F cP lbm/ft3 lbm lbm/day
MMCF
MMCF/day
BTU(60)/ft
3 lbm/day
MMCF
MMCF/day
BTU/ft3
MMBTU(60) MMBTU
MMBTU/day MMBTU(60)/ day kg/m
3 s pulses/ft
3 feet kg/m3s pulses/ft3 feet
US8 Units
Parameters and Values Units Realflo
Display
Pipe and Orifice Diameters inches
Static, Base and Atmospheric Pressure psi
Differential Pressure
Flowing and Base Temperature
Viscosity
Density inches H
2
O at 60 °F
°F centipoise lbm/ft
3
Mass
Mass Flow Rate
Volume lbm lbm/hr
MCF
Volume Flow Rate
Heating Value
Energy
Energy Flow Rate
Flow Extension
Turbine Rate
Altitude
MCF/day
BTU(60)/ft day kg/m3s pulses/ft
3 feet
3
MMBTU(60)
MMBTU(60)/ inches psi in H2O at 60F
F cP lbm/ft3 lbm lbm/hr
MCF
MCF/day
BTU/ft3
MMBTU
MMBTU/day kg/m3s pulses/ft3 feet
PEMEX Units
Parameters and Values
Realflo User and Reference Manual
May 19, 2011
Units Realflo Display
944
Measurement Units
Parameters and Values Units Realflo Display
Pipe and Orifice Diameters inches
Static, Base and Atmospheric Pressure psi
Differential Pressure
Flowing and Base Temperature inches H2O at 60°F
°F
Viscosity
Density
Mass centipoise lbm/ft3 lbm lbm/hr
MMCF
Mass Flow Rate
Volume (standard and secondary conditions)
Volume Flow Rate (standard and secondary conditions)
Heating Value
Energy
MMCF/day inches psi in H2O at 60F
F
CP lbm/ft3 lbm lbm/hr
MMCF
MMCF/day
Energy Flow Rate
Flow Extension
Turbine Rate
Altitude
BTU(60)/ft3 BTU/ft3
Giga calories
Giga calories/day kg/m3s pulses/ft3
Giga calories
Giga calories/day kg/m3s pulses/ft3 feet feet
IP Units
Parameters and Values Units Realflo Display
Pipe and Orifice Diameters
Static, Base and Atmospheric Pressure
Differential Pressure feet lbf/ft
2 lbf/ft
2
Flowing and Base Temperature °F
Viscosity
Density
Mass lbm/ft-s lbm/ft
3 lbm
Mass Flow Rate
Volume
Volume Flow Rate
Heating Value
Energy
Energy Flow Rate
Flow Extension
Turbine Rate
Altitude ft lbf/ft2 lbf/ft2
F lbm/ft-s lbm/ft3 lbm lbm/hr ft ft
3
3
/hr
BTU(60)/ft
3 lbm/hr ft3 ft3/hr
BTU/ft3
BTU BTU(60)
BTU(60)/hr BTU/hr kg/m
3 s pulses/ft
3 kg/m3s pulses/ft3 feet feet
Metric1 Units
Parameters and Values Units Realflo Display
Pipe and Orifice Diameters Mm
Static, Base and Atmospheric Pressure kPa
Differential Pressure
Flowing and Base Temperature
Viscosity kPa
°C mm kPa kPa
C centipoise cP
Realflo User and Reference Manual
May 19, 2011
945
Metric2 Units
Metric3 Units
Parameters and Values
Density
Mass
Mass Flow Rate
Volume
Volume Flow Rate
Heating Value
Energy
Energy Flow Rate
Flow Extension
Turbine Rate
Altitude
Measurement Units
Units
kg/m
3 kg
Realflo Display
kg/m3 kg kg/s
10
3 m
3 kg/s
E3m3
10
3 m
3
/day E3m3/day
MJ/m
3
MJ/m3
GJ GJ
GJ/day kg/m
3 s
GJ/day kg/m3s pulses/m
3 pulses/m3 meters m
Parameters and Values Units Realflo Display
Pipe and Orifice Diameters mm
Static, Base and Atmospheric Pressure bar
Differential Pressure millibar
Flowing and Base Temperature
Viscosity
Density
Mass
Mass Flow Rate
Volume
Volume Flow Rate
Heating Value
Energy
Energy Flow Rate
Flow Extension
Turbine Rate
Altitude
°C mm bar millibar centipoise cP kg/m kg
3 kg/hr m
3 m
3
/hr
MJ/m
3
C kg/m3 kg kg/hr
M3
M3/hr
MJ/m3
MJ MJ
MJ/hour MJ/hour kg/m
3 s pulses/m
3 kg/m3s pulses/m3 meters m
Parameters and Values Units Realflo Display
Pipe and Orifice Diameters mm
Static, Base and Atmospheric Pressure MPa
Differential Pressure kPa
Flowing and Base Temperature °C
Viscosity
Density
Mass
Mass Flow Rate
Volume
Volume Flow Rate
Heating Value
Energy
Energy Flow Rate
Flow Extension
Turbine Rate
Altitude mm
MPa kPa
C centipoise cP kg/m
3 kg/m3 kg kg kg/s
10
3 m
3 kg/s
E3m3
10
3 m
3
/day E3m3/day
MJ/m
3
MJ/m3
GJ GJ
GJ/day kg/m
3 s
GJ/day kg/m3s pulses/m
3 pulses/m3 meters m
Realflo User and Reference Manual
May 19, 2011
946
SI Units
Measurement Units
Parameters and Values Units Realflo Display
Pipe and Orifice Diameters m
Static, Base and Atmospheric Pressure Pa
Differential Pressure Pa
Flowing and Base Temperature
Viscosity
Density
Mass
Mass Flow Rate
Volume
Volume Flow Rate
Heating Value
Energy
Energy Flow Rate
Flow Extension
Turbine Rate
Altitude m
Pa
Pa
°K
Pa-s kg/m
3 kg kg/s m
3 m
3
/s
J/m
3
K
Pa-s kg/m3 kg kg/s m3 m3/s
J/m3
J J
W W kg/m
3 s pulses/m
3 kg/m3s pulses/m3 meters m
Realflo User and Reference Manual
May 19, 2011
947
Input Averaging
Input Averaging
Realflo averages differential pressure, static pressure, and temperature using time-weighted or flow-weighted methods. The method is configured by the user. These methods comply with API 21.1.
Flow-Dependent Time Weighted Linear Average
Time weighted averaging can be selected for differential pressure, static pressure, and temperature inputs.
Each sample is a product of the input value (or rate) and the time interval.
Each input accumulation is the sum of the samples in the time period (an hour or less). The flow duration is the sum of the time intervals in the period.
The time weighted linear average is the accumulation divided by the flow duration.
The average for the period will be for all of the time intervals with flow or all of the intervals when there is no flow. 𝑝 𝑓
= 𝑘
1 𝑡 𝑓
𝑝 𝑖 𝑡 𝑖
𝐹 𝑖 𝑖=1 𝑘 𝑡 𝑓
= 𝑡 𝑖
𝐹 𝑖 𝑖=1
Where p f
is the average input variable during periods of flow. t i is the time interval for sampling i. t f is the total time with flow
.
F i
is the flow dependency factor. Zero if no flow at sample period i, and one if flow at sample period
i.
Flow Weighted Linear Average
Flow weighted averaging can be selected for differential pressure, static pressure, and temperature inputs.
Each sample is a product of the input value (or rate), the time interval and the flow weighting. Each input accumulation is the sum of the samples in the time period (an hour or less). The flow duration factor for the period is the sum of the product of the time intervals and the flow weighting. The flow weighted linear average is the accumulation divided by the flow duration factor.
The average for the period will be for all of the time intervals with flow or all of the intervals when there is no flow.
For differential pressure meters the flow weighting is the square root of the differential pressure.
Realflo User and Reference Manual
May 19, 2011
948
Input Averaging
For turbine meters, the flow weighting is one (i.e. there is no weighting) as the flow is linearly related to the pulse rate. 𝑝 𝑓
=
1 𝑡 𝑧 𝑘
𝑝 𝑖 𝑡 𝑖
𝑊 𝑖 𝑖=1 𝑘 𝑡 𝑧
= 𝑡 𝑖
𝑊 𝑖 𝑖=1
Where p f
is the average input variable during periods of flow. t i
is the time interval for sampling i. t z
is the total time with weighting
.
W i
is the flow weighting factor. This would typically be the square root of the differential pressure for an orifice meter
.
No Flow Linear Average
If there is no flow for an entire period, then a linear average of the differential pressure, static pressure, and temperature inputs is used for the entire period.
Each sample is a product of the input value (or rate) and the time interval.
Each input accumulation is the sum of the samples in the time period (an hour or less). The duration factor for the period is the sum of the time intervals. 𝑝 𝑛
=
1 𝑡 𝑘 𝑘
𝑝 𝑖 𝑡 𝑖 𝑖=1 𝑘 𝑡 𝑘
= 𝑡 𝑖 𝑖=1
Where p n is the average input variable during periods of no flow. t i is the time interval for sampling i. t k
is the total time with no flow
.
Realflo User and Reference Manual
May 19, 2011
949
Creating Custom Realflo Applications
Creating Custom Realflo Applications
SCADAPack Controllers
The Telepace C Tools, version 2.13 or newer, are required to modify the flow computer for Telepace firmware. The ISaGRAF C Tools, version 2.13 or newer, are required to modify the flow computer for ISaGRAF firmware.
The following files are found in the Custom Applications folder. gasmain.c is source code for the flow calculation main loop. Users add their source code to this file. appstart.c is the application program start-up routine. Refer to the C
Tools manual for a complete description of this file.
Telepace Files:
Realflot.lib is the object library for the flow calculation on Telepace standard firmware. This library is linked with the compiled gasmain.c to form a gas calculation application.
Realflot.cmd is a linker command file for creation of executable code for
Telepace standard firmware. rfenront.lib is the object library for the flow calculation on Telepace
Enron Modbus firmware. This library is linked with the compiled gasmain.c to form a gas calculation application. rfenront.cmd is a linker command file for creation of executable code for
Telepace Enron Modbus firmware.
ISaGRAF Files:
The flow computer program was developed using the C Tools for both
Telepace and ISaGRAF firmware in SCADAPack controllers and C++ Tools for SCADAPack 32 controllers. User written code can be added to the Flow computer program. An object library and a source file are provided for this purpose.
The size of the custom application is limited to the application memory space available in the controller being used. The amount of memory available will depend on the controller type, SCADAPack or SCADAPack
32, the flow computer type and the run configuration. The application memory space available typically ranges from 2KB to 80KB.
If you are considering creating a custom Realflo application consult the factory for advice on the application memory available for your controller and run configuration combination.
Realfloi.lib is the object library for the flow calculation on ISaGRAF standard firmware. This library is linked with the compiled gasmain.c to form a gas calculation application.
Realfloi.cmd is a linker command file for creation of executable code for
ISaGRAF standard firmware.
Realflo User and Reference Manual
May 19, 2011
950
Creating Custom Realflo Applications rfenroni.lib is the object library for the flow calculation on ISaGRAF
Enron Modbus firmware. This library is linked with the compiled gasmain.c to form a gas calculation application. rfenroni.cmd is a linker command file for creation of executable code for
ISaGRAF Enron Modbus firmware
Modifying the Application
The file gasmain.c contains the main function of the C program. The function is listed below. void main(void)
{
TASKINFO taskStatus;
/* create gas flow computer tasks */
create_task(gasTaskScheduler, 4, APPLICATION,
2);
create_task(gasFlowTask, 2, APPLICATION, 8);
/* add user application code here */
/* end execution of this task */
taskStatus = getTaskInfo(0);
end_task(taskStatus.taskID);
}
The function creates two tasks for the flow computer. Do not modify the following lines. Doing so may interfere with the proper operation of the flow computer.
create_task(gasTaskScheduler, 4, APPLICATION,
2);
create_task(gasFlowTask, 2, APPLICATION, 8);
User code may be added at the point indicated by the comment:
/* add user application code here */
User code normally takes the form of an infinite loop that performs the required functions. It is important that the user's code properly uses the
IO_SYSTEM resource and that it releases the processor. The code fragment below shows the typical form of the loop. while (TRUE)
{
/* code placed here does not use the I/O system*/
/* obtain exclusive use of the I/O system */
request_resource(IO_SYSTEM);
/* code placed here uses the I/O system */
/* allow other tasks to use the I/O system */
release_resource(IO_SYSTEM);
Realflo User and Reference Manual
May 19, 2011
951
Creating Custom Realflo Applications
/* allow other priority 1 tasks to execute */
release_processor();
}
If the code is not an infinite loop, it is executed once only. This form can be used for initialization or for creation of other tasks. Once the one-time code is executed, the lines below end the main task.
/* end execution of this task */ taskStatus = getTaskInfo(0); end_task(taskStatus.taskID);
Refer to the C Tools User Manual for a description of rules and guidelines for C programs.
Building the Application for Telepace Firmware
Execute the following commands to build the flow computer program. The first two lines compile the standard files for the Realflo Flow Computer application. The next line links the object files with the rest of the Realflo application. The executable file will be named Realflot.abs.
For standard Telepace: mccm77 -v -nQ -Ml -g -c -Ic:\Telepace\ctools\520x appstart.c mccm77 -v -nQ -Ml -g -c -Ic:\Telepace\ctools\520x gasmain.c lnkm77 -M -c Realflot.cmd
For Enron Modbus Telepace: mccm77 -v -nQ -Ml -g -c -Ic:\Telepace\ctools\520x appstart.c mccm77 -v -nQ -Ml -g -c -Ic:\Telepace\ctools\520x gasmain.c lnkm77 -M -c rfenront.cmd
You can write a batch file to execute the commands or use a make utility to control the compilation of the program.
If you add additional files compile them in the manner shown above. Add the files to the linker command file Realflot.cmd. Refer to the Telepace C Tools
User Manual for details.
Building the Application for ISaGRAF Firmware
Execute the following commands to build the flow computer program. The first two lines compile the standard files for the Realflo Flow Computer application. The next line links the object files with the rest of the Realflo application. The executable file will be named Realfloi.abs.
For standard ISaGRAF: mccm77 -v -nQ -Ml -g -c -Ic:\Telepace\ctools\isagraf appstart.c mccm77 -v -nQ -Ml -g -c -Ic:\Telepace\ctools\isagraf gasmain.c lnkm77 -M -c Realfloi.cmd
For Enron Modbus ISaGRAF: mccm77 -v -nQ -Ml -g -c -Ic:\Telepace\ctools\isagraf appstart.c mccm77 -v -nQ -Ml -g -c -Ic:\Telepace\ctools\isagraf gasmain.c lnkm77 -M -c rfenroni.cmd
Realflo User and Reference Manual
May 19, 2011
952
SCADAPack 314/330/334 and SCADAPack 350 Controllers
The SCADAPack 314/330/334 and SCADAPack 350 controllers support multiple C/C++ programs running in the controller.
See the SCADAPack 350 C/C++ Tools User manual for complete information.
SCADAPack 32 Controllers
The following files and folders are found in the SCADAPack 32 Flow
Computer folder.
SCADAPack32FlowComputer.hws The Hitachi Workspace file. Refer to the SCADAPack 32 C++ Tools manual for a complete description of this file.
SCADAPack32FlowComputer.hww The Hitachi Workspace Session file. Refer to the Hitachi Help in the Hitachi
Embedded Workshop.
Realfloi Files
Creating Custom Realflo Applications
You can write a batch file to execute the commands or use a make utility to control the compilation of the program. If you add additional files compile them in the manner shown above. Add the files to the linker command file
Realfloi.cmd. Refer to the ISaGRAF C Tools User Manual for details. appsettings.src appstart.cpp gasmain.cpp is the application program start-up settings. Refer to the SCADAPack 32 C++ Tools manual for a complete description of this file. is the application program start-up routine. Refer to the SCADAPack 32 C++ Tools manual for a complete description of this file. is source code for the flow calculation main loop.
Users add their source code to this file.
Realfloi.hwp is the Workspace project file.
ISaGRAF_Realflo.lib is the object library for the flow calculation on
ISaGRAF firmware. This library is linked with the compiled gasmain.c to form a gas calculation application.
Debug Application.hdc is the Hitachi debugger file.
Realflot Files
appsettings.src appstart.cpp gasmain.cpp
Realflot.hwp is the application program start-up settings. Refer to the SCADAPack 32 C++ Tools manual for a complete description of this file. is the application program start-up routine. Refer to the SCADAPack 32 C++ Tools manual for a complete description of this file. is source code for the flow calculation main loop.
Users add their source code to this file. is the Workspace project file.
Realflo User and Reference Manual
May 19, 2011
953
Creating Custom Realflo Applications
Telepace_Realflo.lib is the object library for the flow calculation on
Telepace firmware. This library is linked with the compiled gasmain.c to form a gas calculation application.
Debug Application.hdc is the Hitachi debugger file.
Modifying the Application
The file gasmain.cpp contains the main function of the C++ program. The function is listed below.
/* ----------------------------------------------------------------
gasmain.cpp
Gas Flow Computer Start-Up Routine
Copyright 1997-2001, Control Microsystems Inc
copied from newApp.cpp
SCADAPack 32 C++ Application Main Program
Copyright 2001, Control Microsystems Inc.
-------------------------------------------------------------- */
#include <ctools.h>
/* ----------------------------------------------------------------
Function Prototypes
-------------------------------------------------------------- */
#ifdef __cplusplus extern "C"
{
#endif extern void main(void); extern void gasTaskScheduler(void); extern void gasFlowTask(void);
#ifdef __cplusplus
}
#endif
/* -----------------------------------------------------------------
main
This routine is the main application loop.
-------------------------------------------------------------- */ void main(void)
{
TASKINFO taskStatus;
/* create gas flow computer tasks */ create_task(gasTaskScheduler, 4, APPLICATION, 2); create_task(gasFlowTask, 2, APPLICATION, 6);
/* add user application code here */
/* end execution of this task */ getTaskInfo(0, &taskStatus); end_task(taskStatus.taskID);
Realflo User and Reference Manual
May 19, 2011
954
Creating Custom Realflo Applications
}
The function creates two tasks for the flow computer. Do not modify the following lines. Doing so may interfere with the proper operation of the flow computer.
create_task(gasTaskScheduler, 4, APPLICATION, 2);
create_task(gasFlowTask, 2, APPLICATION, 8);
User code may be added at the point indicated by the comment:
/* add user application code here */
User code normally takes the form of an infinite loop that performs the required functions. If the code is not an infinite loop, it is executed once only.
This form can be used for initialization or for creation of other tasks. Once the one-time code is executed, the lines below end the main task.
/* end execution of this task */ taskStatus = getTaskInfo(0); end_task(taskStatus.taskID);
Refer to the SCADAPack 32 C++ Tools User Manual for a description of rules and guidelines for C++ programs.
Building the Application
Once the editing of the project is completed the application needs to be compiled and linked. This process results in an executable file that can be loaded into the SCADAPack 32 controller.
To compile and link the project:
Select Build All from the HEW Build menu.
The HEW Output window will show the progress of the compiling and linking process.
The application is successfully built if there are no Errors or Warnings displayed in the Output window. The following should appear in the Output window when the application is build successfully:
Build Finished
0 Errors, 0 Warnings
Realflo User and Reference Manual
May 19, 2011
955
Measurement Canada Approved Version
Measurement Canada Approved Version
Customers with measurement sites that require Measurement Canada custody transfer approval for natural gas flow measurement, can take advantage of the cost effective and flexible SCADAPack solution. The
Measurement Canada version utilizes the same flow calculations as other
Realflo related installations, but comes with the specific software and hardware required to meet the Measurement Canada requirements for sealing and inspection by Measurement Canada. The approved flow computers may be used with AGA-3 (orifice plate flow measurement), AGA-
7 (turbine flow measurement), or Vcone flow elements.
Three standard enclosure configurations are available for Measurement
Canada approved versions. Selection of enclosure size can be made based on the equipment required within the approved cabinet. Each cabinet meets
NEMA4X specifications and includes a windowed door for controller diagnostic LED viewing.
Measurement Canada approval depends on meeting requirements for locking out program changes and firmware changes. This is accomplished by disabling certain commands in the flow computer.
Flow Computer Disabled Commands
The Realflo commands listed in the table below are disabled when the lockout device is installed. Error code 30064 is returned when these commands are attempted when the lockout device is installed.
40
41
42
43
44
21
30
31
32
34
Command
Number
3
6
9
15
16
17
19
35
37
38
Command Description
Set input configuration
Set Real Time Clock
Adjust Real Time Clock
Set contract configuration
Set number of runs
Set Flow Computer ID
Set Run ID
Set Long Run ID
Start Temperature Calibration: Force current temperature
Start Temperature Calibration: Force fixed temperature
End Temperature Calibration
Start Static Pressure Calibration: Force current static pressure
Start Static Pressure Calibration: Force fixed static pressure
End Static Pressure Calibration
Start Differential Pressure Calibration: Force current differential pressure
Start plate change: force current temperature
Start plate change: force fixed temperature
End plate change: temperature
Start plate change: force current static pressure
Start plate change: force fixed static pressure
Realflo User and Reference Manual
May 19, 2011
956
130
131
133
135
138
139
151
303
353
703
803
804
1903
2203
84
85
86
87
88
89
102
103
77
78
79
80
81
82
83
Command
Number
45
46
47
48
75
76
Measurement Canada Approved Version
Command Description
End plate change: static pressure
Start plate change: force current differential pressure
Start plate change: force fixed differential pressure
End plate change: differential pressure
Start Pulse Count Calibration: Force current pulse count rate
Start Pulse Count Calibration: Force fixed pulse count rate
End Pulse Count Calibration
Force current temperature
Force fixed temperature
Remove forced temperature
Force current static pressure
Force fixed static pressure
Remove forced static pressure
Force current differential pressure
Force fixed differential pressure
Remove forced differential pressure
Force current pulse count rate
Force fixed pulse count rate
Remove forced pulse count rate
Delete account
Update account
Search for MVT sensor
Change address of MVT sensor
Set MVT configuration
Calibrate MVT sensor
Set Display Control Configuration
Set Sensor Mode
Set Custom Display Configuration
Set AGA-3 (1992) configuration
Set AGA-3 (1985) configuration
Set AGA-7 configuration
Set AGA-8 gas ratios
Set AGA-8 Hexanes+ Gas Ratios
Set NX19 gas ratios
Set V-Cone Configuration
Enron Protocol Disabled Commands
The Enron Protocol commands listed in the table below are disabled when the lockout device is installed. The flow computer will return an exception response, with exception code 1, when these commands are attempted when the lockout device is installed.
Command
Number
5
6
15
16
Command Description
Force Boolean state
Force numeric register
Load multiple states
Load multiple registers
Realflo User and Reference Manual
May 19, 2011
957
Measurement Canada Approved Version
Measurement Canada Lockout Cable
The Measurement Canada lockout cable is use with SCADAPack,
SCADAPack LP, SCADAPack 32 and SCADAPack 314/330/334 flow computers. The cable is a standard IMC cable with a jumper between the
/SELECT line and ground on the cable. The cable can be inserted anywhere on the I
2
C bus. The cable and side view are shown below.
Measurement Canada Approved Flow Computers
In order for a flow computer to be Measurement Canada approved it needs to meet measurement accuracy and performance standards. The approved flow computers require that a specific firmware version and flow computer version be used. In addition the flow computer requires a lockout device so that changes cannot be made to the firmware or meter run configuration.
The requirements for each approved flow computer type is described below.
SCADAPack 32
The lockout device is a special cable attached to the I
2
C bus. The cable pulls the /SELECT line low. If the flow computer option is enabled and the
select line is low the commands listed in the Flow Computer Disabled
Commands section are disabled.
SCADAPack 32 firmware version 2.16 (Telepace or ISaGRAF) is required for Measurement Canada operation.
Flow computer version 6.74 is is required for Measurement Canada operation.
SCADAPack 314
The lockout device is a special cable attached to the I
2
C bus. The cable pulls the /SELECT line low. If the flow computer option is enabled and the
select line is low the commands listed in the Flow Computer Disabled
Commands section are disabled.
SCADAPack 314 firmware version 1.51 (Telepace or ISaGRAF) is required for Measurement Canada operation.
Flow computer version 6.74 is is required for Measurement Canada operation.
SCADAPack 330/334
The lockout device is a special cable attached to the I
2
C bus. The cable pulls the /SELECT line low. If the flow computer option is enabled and the
select line is low the commands listed in the Flow Computer Disabled
Commands section are disabled.
Realflo User and Reference Manual
May 19, 2011
958
Measurement Canada Approved Version
SCADAPack 330/334 firmware version 1.51 (Telepace or ISaGRAF) is required for Measurement Canada operation.
Flow computer version 6.74 is is required for Measurement Canada operation.
SCADAPack and SCADAPack LP
The lockout device is a special cable attached to the I
2
C bus. The cable pulls the /SELECT line low. If the flow computer option is enabled and the
select line is low the commands listed in the Flow Computer Disabled
Commands section are disabled.
SCADAPack firmware version 2.30 (Telepace or ISaGRAF) is required for Measurement Canada operation.
Flow computer version 6.10 is is required for Measurement Canada operation.
SolarPack 410
The SolarPack 410 security jumper is used to enable or disable programming commands and firmware uploads.
When in the SECURITY ON position:
Realflo cannot make changes to the SolarPack 410 flow computer
configuration. The commands listed in the Flow Computer Disabled
Commands section are disabled.
Host and HMI systems cannot make changes to the SolarPack 410 flow computer configuration using the TeleBUS Command sequence.
New firmware cannot be loaded into the SolarPack 410
When in the SECURITY OFF position security is effectively disabled. Realflo and HMI commands are processed by the SolarPack 410. New firmware can be loaded into the SolarPack 410.
Refer to the figure below for the position of the header and jumper link labeled J3.
SolarPack firmware version 1.51 (Telepace or ISaGRAF) is required for
Measurement Canada operation.
Flow computer version 6.74 is is required for Measurement Canada operation.
SCADAPack 4203 DR
The SCADAPack 4203DR controller does not have an I
2
C bus. Jumper J4 at the left side of the Display connector on the 4203 is used to enable or disable the Measurement Canada lock out. If the flow computer option is
enabled and jumper J1 is removed the commands listed in the Flow
Computer Disabled Commands section are disabled.
Realflo User and Reference Manual
May 19, 2011
959
Measurement Canada Approved Version
Display
Connector
J1
J2
J3
J4
J1 - System Jumper, Required
J2 - System Jumper, Required
J3 - Not Used
J4 - Remove for Measurement
Canada
SCADAPack firmware version 1.51 (Telepace or ISaGRAF) is required for Measurement Canada operation.
Flow computer version 6.74 is is required for Measurement Canada operation.
SCADAPack 4203 DS
The SCADAPack 4203DS controller does not have an I
2
C bus. Jumper J4 at the left side of the Display connector on the 4203 is used to enable or disable the Measurement Canada lock out. If the flow computer option is
enabled and jumper J1 is removed the commands listed in the Flow
Computer Disabled Commands section are disabled.
Display
Connector
J1
J2
J3
J4
J1 - System Jumper, Required
J2 - System Jumper, Required
J3 - Not Used
J4 - Remove for Measurement
Canada
SCADAPack firmware version 1.51 (Telepace or ISaGRAF) is required for Measurement Canada operation.
Flow computer version 6.74 is is required for Measurement Canada operation.
SCADAPack 4202 DR
The SCADAPack 4202DR controller does not have an I
2
C bus. The lockout is implemented using digital input 0. To allow this input to be used to lock out the programming features custom firmware is required. This firmware is installed only for Measurement Canada flow computer installations. Digital input 0 will not be available for other uses when the custom firmware is installed.
If digital input 0 is connected to ground (COM) and the flow computer option is enabled the command are disabled.
SCADAPack firmware version 2.30 (Telepace or ISaGRAF) is required for Measurement Canada operation.
Flow computer version 6.10 is is required for Measurement Canada operation.
Realflo User and Reference Manual
May 19, 2011
960
Measurement Canada Approved Version
DC Power (+)
DC Power ( )
COM 2 TX / A+
COM 2 RX / B
–
COM 2 com
COM 2 (232 / 485)
COM 3 (232 / 485)
COM 3 TX / A
COM 3 RX / B
COM 3 com
P1
P2
P5
AOUT
CTR 1
COM
CTR0/DIN/DOUT
I
R
R
IRET
RTD
Connections
Lockout Jumper
P3
P4
SCADAPack 4202 DS
The SCADAPack 4202DS controller does not have an I
2
C bus. The lockout is implemented using digital input 0. To allow this input to be used to lock out the programming features custom firmware is required. This firmware is installed only for Measurement Canada flow computer installations. Digital input 0 will not be available for other uses when the custom firmware is installed.
If digital input 0 is connected to ground (COM) and the flow computer option is enabled the command are disabled.
SCADAPack firmware version 2.30 (Telepace or ISaGRAF) is required for Measurement Canada operation.
Flow computer version 6.10 is is required for Measurement Canada operation.
DC Power (+)
DC Power (-)
COM 2 TX / A+
COM 2 RX / B
–
COM 2 com
COM 2 (232 / 485)
COM 3 (232 / 485)
COM 3 TX / A
COM 3 RX / B
COM 3 com
P1
S
E
F
U
P5
Status
LED
Analog Input 0
Analog Input 1
Common
CTR/DIN/DOUT0
CTR/DOUT1
P2
P3
RTD+
RTD+
P4
Cold Boot
Switch
RET
Lockout Jumper
Realflo User and Reference Manual
May 19, 2011
961
DNP3 Protocol User Manual
DNP3 Protocol User Manual
DNP, the Distributed Network Protocol, is a standards-based communications protocol developed to achieve interoperability among systems in the electric utility, oil & gas, water/waste water and security industries. This robust, flexible non-proprietary protocol is based on existing open standards to work within a variety of networks.
DNP offers flexibility and functionality that go far beyond conventional communications protocols. Among its robust and flexible features DNP 3.0 includes:
Multiple data types (Data Objects) may be included in both request and response messages.
Multiple master stations are supported for outstations.
Unsolicited responses
1
may be initiated from outstations to master stations.
Data types (Objects) may be assigned priorities (Class) and be requested based on the priority.
Addressing for over 65,000 devices on a single link.
Time synchronization and time-stamped events.
Broadcast messages.
Data link and application layer confirmation
Internal indications that report the health of a device and results of last request.
Select-Before-Operate which is the ability to choose extra reliability when operating outputs.
DNP Overview
DNP Architecture
Object Library
DNP is a layered protocol that is based on the Open System Connection
(OSI) 7-layer protocol. DNP supports the physical, data link and application layers only and terms this the Enhanced Performance Architecture (EPA). In addition to these three layers an additional layer, the pseudo-transport layer, is added to allow for larger application layer messages to be broken down into smaller frames for the data link layer to transmit.
The data objects (Binary Inputs, Binary Outputs, and Analog
Inputs etc.) that reside in the master or outstation.
Application Layer Application tasks for sending of solicited requests (master messages) to outstations or sending of unsolicited responses from outstations. These request and response messages are referred to as fragments in DNP.
1
Unsolicited responses are also known as unsolicited messages
Realflo User and Reference Manual
May 19, 2011
962
DNP3 Protocol User Manual
Pseudo-Transport Layer Breaks the application layer messages into smaller packets that can be handled by the data link layer. These packets are referred to as frames in DNP.
Data Link Layer
Physical Layer
Handles the transmission and reception of data frames across the physical layer.
This is the physical media, such as serial or Ethernet, which
DNP communicates.
These layers are described in the following sections of this manual.
Object Library
The data types that are used in DNP are broadly grouped together into
Object Groups such as Binary Input Objects and Analog Input Objects etc.
Individual data points, or objects within each group, are further defined using
Object Variations such as Binary Input Change with Time and 16-Bit Analog
Inputs for example.
In general there are two categories of data within each data type, static objects and event objects. Static objects contain the current value of the field point or software point. Event objects are generated as a result of the data changing.
In addition to the object group and variation data objects can be assigned to classes. In DNP there are four object classes, Class 0, Class 1, Class 2 and
Class 3. Class 0 contains static data. Classes 1, 2 and 3 provide a method to assign priority to event objects. While there is no fixed rule for assigning classes to data objects typically class 1 is assigned to the highest priority data and class 3 is assigned to the lowest priority data.
This object library structure enables the efficient transfer of data between master stations and outstations. The master station can poll for high priority data (class 1) more often than it polls for low priority data (class 3). As the data objects assigned to classes is event data when the master polls for a class only the changed, or event data, is returned by the outstation. For data in an outstation that is not assigned a class the master uses a class 0 poll to retrieve static data from the outstation.
DNP allows outstations to report data to one or more master stations using unsolicited responses (report by exception) for event data objects. The outstation reports data based on the assigned class of the data. For example the outstation can be configured to only report high priority class 1 data.
Internal Indication (IIN) Flags
The Internal Indication (IIN) flags are set by a slave station to indicate internal states and diagnostic results. The following tables show the IIN flags supported by SCADAPack controllers. Bits except Device Restarted and
Time Synchronization required are cleared when the slave station receives any poll or read data command.
The IIN is set as a 16 bit word divided into two octets of 8 bits. The order of the two octets is:
First Octet
IIN First Octet
Second Octet
Realflo User and Reference Manual
May 19, 2011
963
Application Layer
DNP3 Protocol User Manual
7
0
1
2
3
4
5
6
First
Octet
Bit
6 5 4 3 2 1 0
Description
Bit Number last received message was a broadcast message
Class 1 data available
Class 2 data available
Class 3 data available
Time Synchronization required not used (returns 0)
Device trouble
Indicates memory allocation error in the slave, or
For master in mimic mode indicates communication failure with the slave device.
7 Device restarted (set on a power cycle)
IIN Second Octet
7 6 5 4 3 2 1 0
Second
Octet
Bit
0
1
Description
2
3
4
5
6
7
Bit Number
Function Code not implemented
Requested object unknown or there were errors in the application data
Parameters out of range
Event buffer overflowed
Indicates event buffer overflow in the slave or master. The slave will set this bit if the event buffer in the slave is overflowed. The master will set this bit if the event buffer in the master has overflowed with events read from the slave.
Confirm the event buffer size, in the master and slave, is set to a value that will not cause the buffer to overflow and avoid that events are lost. not used (returns 0) not used (returns 0) not used (returns 0) not used (returns 0)
The application layer in DNP is responsible for the processing of complete messages for requesting, or responding to requests, for data.
The following shows the sequence of Application Layer messages between one master and one outstation.
Realflo User and Reference Manual
May 19, 2011
964
DNP3 Protocol User Manual
Master Outstation
Send Request ------------> Accept request and process
<------------ Optional Application Confirmation
Accept response <------------- Send Response
Optional Application
Confirmation ------------->
Change detected
Accept response <-------------- Send Unsolicited Response
Optional Application
Confirmation -------------->
The complete messages are received from and passed to the pseudotransport layer. Application layer messages are broken into fragments with each fragment size usually a maximum of 2048 bytes. An application layer message may be one or more fragments in size and it is the responsibility of the application layer to keep the fragments are properly sequenced.
Application layer fragments are sent with or without a confirmation request.
When a confirmation is requested the receiving device replies with a confirmation indicating the message was received and parsed without any errors.
Pseudo-Transport Layer
The pseudo-transport layer formats the larger application layer messages into smaller packets that can be handled by the data link layer. These packets are referred to as frames in DNP. The pseudo-transport layer inserts a single byte of information in the message header of each frame.
This byte contains information such as whether the frame is the first or last frame of a message as well as a sequence number for the frame.
Data Link Layer
The data link layer handles the transmission and reception of data frames across the physical layer. Each data link frame contains a source and destination address so the receiving device knows where to send the response. For data integrity data link layer frames contain two CRC bytes every 16 bytes.
Data link layer frames are sent with or without a confirmation request. When a confirmation is requested the receiving device replies with a confirmation indicating the message was received and the CRC checks passed.
Physical Layer
The physical layer handles the physical media, such as serial or Ethernet, which DNP communicates.
Modbus Database Mapping
In SCADAPack controllers static DNP objects such as binary input, analog input, binary counter and analog output are associated with Modbus registers. Whenever a DNP object is created an associated Modbus register(s) is also assigned. Application programs executing in the
SCADAPack controller, C or logic, are able to assign physical I/O to Modbus
Realflo User and Reference Manual
May 19, 2011
965
DNP3 Protocol User Manual registers using the Telepace Register Assignment or the ISaGRAF I/O
Connection and these physical I/O points can then be assigned to DNP objects. User application data such as runtimes, flow totals and others can also be assigned to DNP objects.
This architecture enables DNP master stations and outstations to pass not only physical data points between them but also to monitor and control user applications executing in the SCADAPack controller. For example a master station can monitor a level in an outstation and then, based on the application program, send a setpoint value to another outstation to control the level.
SCADAPack DNP Operation Modes
Within a DNP network, a SCADAPack controller can operate as a:
DNP Outstation (Slave)
DNP Master or Mimic Master or
DNP Router
DNP Master Mimic and DNP Router are incompatible and mutuallyexclusive modes of operation.
A DNP outstation forms the basic class of any DNP node in a network.
Other operational modes derive from a DNP Outstation. A DNP outstation responds to requests from one or more DNP master stations on a network.
Also, a DNP Outstation is able to initiate unsolicited responses (messages) based on event data to a master station.
A DNP Master is capable of polling for data, accepting and processing unsolicited messages, and sending control commands to an outstation.
Note that a DNP Master can also act perform the duties of a DNP
Outstation.
A SCADAPack controller acting as a DNP Router is simply acting a pass through, basically redirecting messages from one DNP node to another.
Similarly to a DNP Master, a DNP Router can also perform all the duties of a
DNP Outstation.
DNP Network topologies comprise several combinations of DNP Masters,
DNP Routers, and DNP Outstations. Typical configurations possible with
SCADAPack controllers are:
DNP Master and single DNP Outstation
DNP Master and multi-dropped DNP Outstations
DNP SCADA Host, Data Concentrator (Mimic Master) and multidropped DNP Outstations
DNP SCADA Host, DNP Router and multi-dropped DNP Outstations
Major SCADAPack DNP operation modes are covered in the next chapters.
SCADAPack DNP Outstation
A DNP3 Outstation can be considered the base class of terminal nodes on a
DNP network. Other DNP3 configuration modes, such as Master, Mimic
Master or Router, as implemented by the Control Microsystems DNP driver, inherit their properties from the outstation base class. In other words, a
Realflo User and Reference Manual
May 19, 2011
966
DNP3 Protocol User Manual
SCADAPack controller can simultaneously take on any other operation mode, in addition to being a DNP outstation.
When configured as a DNP outstation a SCADAPack controller is able to:
Map physical I/O data to DNP points.
Define DNP points as Class 0 (Static or None), Class 1, Class 2 or
Class 3 data types.
Respond to requests from one or more master stations such as a
SCADA hosts or other SCADAPack controllers capable of operating as
DNP Masters.
Initiate unsolicited responses to one or more master stations.
„Unsolicited responses‟ are also known as „unsolicited messages‟.
„Unsolicited messages‟ will be used predominantly in this document.
One distinguishing feature of a DNP outstation is this ability to trigger unsolicited messages to a master, upon event accumulation. Events are accumulated when the state of a DNP point changes or an analog values exceeds a threshold. Dead bands can be used to filter out noise from being reported as event data.
After accumulating a certain number of DNP events, or if a certain time period has expired, a DNP outstation will trigger an unsolicited message to its configured master DNP stations, reporting event data. As defined by the
DNP specification, an outstation that triggers an unsolicited message expects a confirmation from the targeted masters (or peers). If an acknowledgement is not received with a configured Application Layer timeout, the outstation will retransmit the initial unsolicited message. If no response is received within the Application Layer timeout, the outstation will retransmit again. This process continues until the outstation has retransmitted the message a number of times as configured by its
Application Layer Retries parameter.
If retry attempts are not sucessful, this message is discarded from the transmit buffer. As of this writing, re-transmission of the message will only resume after a new event occurs within the appropriate buffer. Future releases of the SCADAPack DNP driver will re-attempt a DNP transaction after a random period of time has expired. Retransmissions will be attempted until the messages are eventually received by the master.
Application Layer messages that are larger than 249 bytes are broken down into Data Link frames. The DNP protocol allows one to configure acknowledgements of individual Data Link frames, this enhancing network robustness, especially under noisy environments. When the underlying network structure is noise free (wired or networks for instance), enabling
Application and Data Link confirmations are not necessary.
How to Configure SCADAPack DNP Outstation
In this exercise, we will configure a DNP outstation with address 10. We will also configure the station with digital input points associated with Class 1 and Class 2 events. The station will be configured to trigger unsolicited messages to Master station 200, when Class 1 and Class 2 events occur on these digital inputs.
After this exercise, you should be able to:
Enable the DNP protocol on a serial port.
Realflo User and Reference Manual
May 19, 2011
967
DNP3 Protocol User Manual
Configure the DNP Application and Data Link Layers
Configure Class Events Generation and Transmission
Configure a DNP Routing table
Configure DNP points.
We will map two digital inputs mapped to Modbus registers 10001 and
10002 to DNP Addresses 1 and 2.
Tasks to Complete
Enable DNP Protocol on communication interface.
Configure a DNP Outstation with station address.
Configure DNP points and assign them to Class objects.
Configure outstation to be able to trigger unsolicited messages.
Enable DNP on Communication Interface
The first step recommended in configuration the DNP driver on a
SCADAPack controller is to enable DNP on the communication interface.
To enable the DNP protocol on com2,
From the Controller menu in either Telepace or ISaGRAF, select Serial
Ports.
Select COM2 from the Port dropdown list.
Set the Protocol type to DNP.
Click on OK.
If using an Ethernet equipped controller, enable DNP in TCP or DNP in
UDP from the Controller IP configuration dialog.
Configure DNP Outstation
From the Controller Menu in either Telepace or ISaGRAF, select DNP
Configuration to launch the DNP Configuration dialog.
The Application Layer configuration panel is displayed by default.
Under the Communication group box, change the Retries parameter to
2.
Leave other parameters under the Communication group box at default values.
TIP: It is not necessary to enable the Application Layer confirmation as unsolicited events, by their nature, request for an Application Layer confirmation.
Set Time Synchronization to None.
TIP: It is recommended that a DNP3 master initiate time synchronization.
Enable Unsolicited Class 1 events.
For Class 1 Events, set a Hold Time of 5 seconds and a Hold Count of
100.
TIP: On systems with multiple outstations that could potentially transmit unsolicited messages to a master at the same time, it is recommended to
Realflo User and Reference Manual
May 19, 2011
968
DNP3 Protocol User Manual use a combination of the Hold Time and Hold Count parameters to avoid multiple stations from transmitting at the same time.
Enable Unsolicited Class 2 events.
For Class 2 Events, set a Hold Time of 3600 seconds and a Hold Count of 10.
TIP : Class 2 events are typically of less importance than Class 1 events and may not need to be reported immediately to the master
Other parameters can be left at their default values. The completed
Application Layer Configuration panel should look like this:
Clicking on OK closes the DNP Configuration dialog. Click on OK only after you have completed the DNP configuration.
From the DNP Configuration panel, select the Data Link Layer tree node.
Click on the Edit button and change the Master Station Address to
200.
Change the RTU Station Address to 10.
Leave other parameters at their default values. The completed dialog should look like this:
Realflo User and Reference Manual
May 19, 2011
969
DNP3 Protocol User Manual
TIP: It may be necessary to enable the Data Link confirmation on noisy networks. However, if the Maximum Application Fragment Length is reduced to 249 bytes, it is not necessary to enable the Data Link confirmation, as each data link packet is in essence an Application Layer fragment.
From the DNP Configuration panel, select the Routing tree node.
Click on the Add button to begin a new routing table entry.
From the Add/Edit Route dialog, o Enter 200 for the destination Station. o Set the Port to COM2. o Leave default values for other parameters. o The completed dialog should look like this:
The Data Link Timeout in this dialog takes precedence over the Data Link
Timeout in the Data Link Layer configuration panel.
TIP: Even though a SCADAPack outstation will respond successfully to master request, without is routing entry to the master, it is a good practice to define such a routing entry from an outstation to its master. Moreover,
Realflo User and Reference Manual
May 19, 2011
970
DNP3 Protocol User Manual without a routing entry defined to the master, the outstation will not know which port to send out unsolicited messages, if configured, to the master.
Click on OK to add this entry to the routing table and return to the
Routing dialog.
The completed routing table should look like this:
This next step assumes you have digital inputs mapped to Modbus registers
10001 and 10002.
From the DNP Configuration Panel, click on the Binary Inputs tree node.
Set the Starting DNP Address to 1.
Set the Event Report Method to Log All Events.
If you want to log all events and not only the most recent, you need to set the Event Reporting Method to Log all Events.
Set the Event Buffer Size to 100. The completed panel should look like this:
Click on Add to create a new DNP3 binary input point. Observe that a new binary input point is now visible under the Binary Input tree node with DNP Address 1 (Starting Address)
Leave the default associating Modbus Address as 10001.
Leave the default Event Object as Class 1.
Set the Debounce property to 10.
TIP: It is a good idea to set a non- zero Debounce on unfiltered inputs, to avoid noise being collected as Class events. The same applies for analog inputs. A non-zero Deadband will keep noise from being collected as Class events.
Set the Debounce property to 10.
Click on Add to submit this point to the database and start configuration for the next point. A new point has been added under the Binary Inputs tree node in the DNP Configuration panel.
Change the associating Modbus Address to 10002.
Change the Event Object to Class 2.
Set the Debounce appropriately.
Realflo User and Reference Manual
May 19, 2011
971
DNP3 Protocol User Manual
Click on Add to submit this point to the database and start configuration for the next point.
Repeat the previous two steps to add more points if desired.
Follow a similar procedure to configure other types of DNP3 objects.
Confirm Successful Configuration
To confirm that the DNP driver has been properly configured,
From the Controller menu, select DNP Status. You will be presented with the following dialog.
Check that the DNP Status field within this dialog displays 07: enabled, configured, running
You can also monitor the current state of the defined DNP binary input points from the Binary-In tab.
Toggle the state of digital input 1 configured earlier in this exercise and observe the event buffer for Binary Inputs increment on each change of state. After 5 seconds has elapsed, an unsolicited DNP message is triggered to master station 200. Given that DNP master station 200 is not yet configured and connected, a response to the unsolicited message will not be received and the 5000ms Application layer timeout period will expire. The unsolicited message transmission will subsequently retransmitted and will be aborted after 3 retry attempts have been made. This confirms that your outstation is properly setup and unsolicited messages are being generated and sent. At the time of this implementation, the events will be re-attempted only after a new event occurs.
Also observe the Internal Indications show that Class 1 events are available as indicated in the figure below.
Realflo User and Reference Manual
May 19, 2011
972
DNP3 Protocol User Manual
For additional information on the any of the dialogs referenced in the above
exercise, refer to the DNP Configuration Menu Reference towards the end
this booklet.
SCADAPack DNP Master
DNP master modes currently apply only to the SCADAPack 32,
SCADAPack 314/330/334, SCADAPack 350 and SCADAPack 4203 controllers.
As a master, a SCADAPack controller can be a regular Master or Mimic master.
SCADAPack DNP Master Concepts
A DNP Master station inherits the characteristics of a DNP Outstation. In addition, a DNP Master station is able to:
Poll DNP outstations for static (Class 0) data and Class 1, 2 and 3 event data.
Accept and process unsolicited response messages from polled outstations.
This configuration of a DNP Master (Client) and DNP Outstation (Server) forms the basis of a DNP3 Network. The SCADAPack DNP Master may be configured to periodically poll a SCADAPack DNP Outstation for Class 0, 1,
2, and 3 data objects and receive unsolicited responses from the outstation.
The outstation may be configured to report change event data to the master station using unsolicited responses.
The arrowed line between the master and outstation in the diagram below represents a communication path connecting the two stations. This communication medium may be any type that is supported by both controllers, such as direct serial, leased line modem, dial-up modem and radio for example.
Realflo User and Reference Manual
May 19, 2011
973
DNP3 Protocol User Manual
SCADAPack
DNP Master
SCADAPack
DNP Outstation
Figure 0-1: Simple SCADAPack Master-Outstation DNP Network
An extension of a simple DNP Master and single outstation network, involves a SCADAPack DNP Master connected to a number of outstations over a multi-drop communication channel. The DNP Master may be configured to periodically poll each SCADAPack DNP Outstation for Class
0, 1, 2, and 3 data objects and receive unsolicited responses from the outstations. The outstations may be configured to report change event data to the master station using unsolicited responses.
The arrowed line between the master and outstations, in the diagram below, represents the communication path connecting the stations. This communication path may be any multi-dropped type that is supported by the controllers, such as leased line modem, dial-up modem and radio for example.
SCADAPack
DNP Master
SCADAPack
DNP Outstation A
SCADAPack
DNP Outstation A
SCADAPack
DNP Outstation A
Figure 0-2: SCADAPack DNP Master and multi-dropped DNP
Outstations
The DNP Master feature is limited to a SCADAPack32, SCADAPack
314/330/334, SCADAPack 350 and SCADAPack 4203
SCADAPack DNP Mimic Master
In a typical DNP network a SCADA Host master communicates with a number of outstations. The SCADA Host will poll each outstation for data and may receive change event data in the form of unsolicited responses from the outstations. This type of DNP network is shown in the following diagram.
DNP SCADA Host
SCADAPack
DNP Outstation A
SCADAPack
DNP Outstation B
Figure 0-3: DNP SCADA Host and multi-dropped DNP Outstations
In the above configuration the SCADA Host manages the communication path with each outstation. When the communication path is slow, such as with dial-up communication, or subject to high error rates, such as with some radio communication, the data update rate at the SCADA host can become very slow.
Adding a SCADAPack controller configured for Master Mimic Mode, allows for the SCADA Host to poll the SCADAPack (Mimic Master) for outstation data instead. In essence, the SCADAPack Mimic Master is acting as a Data
Concentrator, reporting on behalf of the outstations currently configured in its routing table. The following diagram shows the addition of the
SCADAPack Mimic Master.
Realflo User and Reference Manual
May 19, 2011
974
DNP3 Protocol User Manual
DNP SCADA Host
SCADAPack Mimic
Slave Master
SCADAPack
DNP Outstation A
SCADAPack
DNP Outstation B
Figure 0-4: SCADAPack Mimic Master and multi-dropped DNP
Outstations
In this configuration the outstation side of the network has been decoupled from the host side of the network, as the SCADAPack mimic master now manages the communication with the outstations.
The SCADA Host and outstations will typically be connected to different communication ports of the SCADAPack Mimic Master. The mimic will respond to the following DNP messages on behalf of the targeted station:
Read messages (this includes class polls as well as individual point reads) from SCADA Host
Write messages from SCADA Host
Unsolicited messages from an outstation
Direct operate messages from SCADA Host
The following DNP messages cannot be mimicked (Mimic does not respond on behalf of target DNP station), and are routed directly to the target outstation by the Mimic:
Select and Operate messages
Data Link Layer messages (e.g. get link status, reset link status, etc)
Enable/Disable Unsolicited Message commands (FC 20 and 21)
Other control messages
Routing for those messages that cannot be mimicked is subjected to the following rule: if (a message is received which needs to be retransmitted to someone else)
if (the message target is configured in our routing table)
if (the destination port is different from the incoming port)
or (routing is enabled on the incoming port)
then retransmit the message
In order to provide current outstation data to the SCADA Host, the
SCADAPack mimicking master independently communicates with each outstation to update a local copy of its database with data from the outstations. This communication may be initiated by the SCADAPack mimicking master, either by polling each outstation in turn using solicited messages; or the outstations could initiate unsolicited messages back to the mimicking master. There could also be a combination of solicited and unsolicited messages between the mimicking master and the outstations.
Realflo User and Reference Manual
May 19, 2011
975
DNP3 Protocol User Manual
In the Mimic mode diagram above the SCADAPack mimic master polls each outstation, A and B, for data and holds images of this data in its memory.
When the SCADA Host poll outstations A and B for data, the mimic master replies from its own images of the outstations. The SCADA Host can also poll the SCADAPack master for its own local data.
Typically the messaging strategy chosen will depend on the relative importance of the data, and the required maximum end-to-end delays for data being transferred through the network. If the requirement is for a reasonably short end-to-end delay for data points, a round-robin polling scheme is optimum, without any unsolicited messages. If there are some data points, which are higher priority and need to be transferred as fast as possible, unsolicited messages should be used.
The advantage of having the SCADA system communicating with the
SCADAPack 32 mimic, instead of direct communication to the outstations is that communication delays and high error rates are effectively removed. The physical connection between the SCADA system and mimic master
SCADAPack is typically a direct high-speed connection and message transactions are fast. Outstations may often be connected via slow PSTN or radio links, and therefore message transactions are subject to substantial delays. They may also be unreliable communication links subject to high error rates.
By having a multiple-level network the communication between the
SCADAPack master and outstations is separated from communication between SCADA system and the SCADAPack master. The delays and error rates, which may be inherent in the outstation communication paths, can be isolated from communications with the SCADA system, thereby increasing overall system performance.
One particular advantage of Mimic Mode is that the master SCADAPack does not need to know, or be configured with, any details of the DNP points configured in the outstations. This makes it relatively simple to insert such a
SCADAPack master into any existing DNP network. The SCADAPack master in Mimic Mode behaves transparently to the higher-level SCADA system, and can easily be configured with communication paths and polling instructions for each connected outstation.
This feature is limited to the SCADAPack 32, 350 and SCADAPack 4203 controllers.
SCADAPack DNP Address Mapping
Address mapping provides a direct link between an outstation‟s DNP points and local Modbus registers within the SCADAPack DNP master. These remote DNP points are now mapped into specific regions of the DNP master‟s Modbus database.
When DNP data points are received from an outstation, a cross reference to the address mapping table is made, and if a match is found, the DNP data will be written to the corresponding local Modbus register. 'Input' DNP object types from the outstation are mapped to the master‟s local input
Modbus register space 1xxxx or 3xxxx. These local Modbus registers are updated after the corresponding DNP point gets updated; usually by a class poll to the outstation, or if the outstation issues an unsolicited response based on a change of value or state on these points.
„Output' DNP object types from the outstation are mapped to the master‟s local output Modbus register space 0xxxx or 4xxxx. Changes made to the
Realflo User and Reference Manual
May 19, 2011
976
DNP3 Protocol User Manual local Modbus register will trigger a DNP Write message, with the current point value, to the outstation. DNP Write implemented in SCADAPack controllers requires an Application Layer confirmation from the target outstation.
By configuring the Address Mapping table, outstation DNP points are therefore mapped to local Modbus registers. As mapped local Modbus points, the data is available for use in application programs such as
Telepace and ISaGRAF. In addition a Modbus SCADA Host can poll the
SCADAPack master for these points.
The following diagram shows a simple DNP Address Mapping network.
SCADA Host
Modbus Master
SCADAPack 32
Modbus DNP3
Slave Master
SCADAPack
Outstation A
SCADAPack
Outstation B
Figure 0-5: SCADAPack Address Mapping
In this network the SCADAPack master updates is local database with mapped outstation data. The manner and frequency with which the
SCADAPack master updates the local Modbus registers, depends on the number and type of I/O object types the registers are mapped to.
This feature is limited to the SCADAPack 32, 350 and SCADAPack 4203 controllers.
Mapping numerous local Modbus output registers (0xxxx and 4xxxx), to a remote DNP device may cause frequent communications between the master and the slave, if the associated registers are being changed frequently in the master. On limited bandwidth or radio networks network capacity needs to handle the traffic that will be generated from these local changes.
How to Configure SCADAPack DNP Master
In this exercise, we will configure a SCADAPack DNP Master to poll a DNP outstation with address 10. The DNP master will be communicating to the outstation by requesting for Class event data and acknowledging receipt of unsolicited responses through com1.
After this exercise, you should be able to:
Configure a DNP Master to poll for Static (Class 0) and Class 1 event data.
Configure a DNP Master to accept and respond to unsolicited messages
Tasks to Complete
Enable DNP communication on com1 of the SCADAPack controller.
Configure a DNP Master with station address of 200, for example.
Configure the DNP master to issue class polls to the outstation created in the previous exercise.
Map outstation DNP points to local DNP points.
Realflo User and Reference Manual
May 19, 2011
977
DNP3 Protocol User Manual
Configuration Steps
Use the same procedure of the previous exercise to enable the DNP protocol on com1.
From the Controller menu, launch the DNP Configuration panel.
From the Application Layer configuration panel, o Check that the Application Layer Confirmation is Disabled.
TIP: A master should not have to request for an Application Layer
Confirmation, as an Application Layer response is implied in master requests. o Set the Application Timeout to 3000 seconds. o Set Time Synchronization to none.
TIP: Master time synchronization to an outstation is configured in the
Add/Edit Master Poll dialog. o Other parameters can be left at their default values. The completed Application Layer Configuration panel should look like this:
From the DNP Configuration dialog, click on the Data Link Layer tree node. o Leave the Master Station Address at the default value of 100. o Change the RTU Station Address to 200.
Realflo User and Reference Manual
May 19, 2011
978
DNP3 Protocol User Manual
Click on the Master tree node from the DNP Settings dialog. o Set the Base Poll Interval to 1s. o Check that Mimic Mode is Disabled.
TIP: A small Base Poll interval provides better granularity.
Click on the Master Poll tree node from the DNP Configuration panel. o Set the Base Poll Interval to 1s. o Ensure Mimic Mode is Disabled. o Click on the Add button within the Master Poll panel to create a new master poll schedule. o In the Add/Edit Master Poll dialog, do the following:
Set Station to 10
Under Class 0 Polling group box, set the Interval to
3600 base poll intervals (1 hour).
Leave the Poll Offset at the default of 0 base poll intervals.
TIP: Static (Class 0) comprise current values of DNP3 points in the I/O database. Due to the sheer size of this data, it is recommended to reduce the frequency of static polls. Urgent data will be updated at the master via
Class polls or unsolicited messages.
Under Class 1 Polling group box, set the Interval to 10 base poll intervals (10 seconds).
Set the Poll Offset to 1 base poll intervals.
Leave the Limit Maximum Events checkbox unchecked.
Under Class 2 Polling group box, set the Interval to
600 base poll intervals (10 minutes).
Set the Poll Offset to 2 base poll intervals.
Leave the Limit Maximum Events checkbox unchecked.
Under the Time Synchronization group box, set the
Interval to 21600 base poll intervals (6 hours).
Set the Poll Offset to 3 base poll intervals.
TIP: Polling intervals on Master request for time synchronization are configured in this dialog. If possible, set this to a daily frequency.
Realflo User and Reference Manual
May 19, 2011
979
DNP3 Protocol User Manual
A small base poll interval limits that maximum poll interval to 32767 seconds. Daily polls (every 86400 seconds) are, therefore, not possible when the base poll interval is set for 1 second.
Under Unsolicited Response group box, leave fields at default. The completed dialog should look like this:
From the DNP Configuration panel, select the Routing tree node. o Click on the Add button to begin a new routing table entry. o From the Add/Edit Route dialog,
Enter 10 for the destination Station.
Set the Port to COM1.
Leave default values for other parameters.
Confirm Successful DNP Master Configuration
With this configuration and a valid communication link between com1 of the
DNP Master and com2 of the DNP outstation, you can use the DNP Master
Status dialog to see communication activity between the two devices.
Confirm that you have communication activity between the master and outstation as indicated in the screen capture below.
If the All Stations tab indicates successful message transmission between the Master and Outstation, congratulate yourself on completing the exercise.
For additional information on the aforementioned configuration parameters,
referenced in the previous two exercises, refer to Chapter
Realflo User and Reference Manual
May 19, 2011
980
DNP3 Protocol User Manual
How to Configure SCADAPack Address Mapping
At this stage in your configuration, the DNP master is able to poll for outstation points. After a successful poll, you can verify the status of current value of outstation DNP points from the various data point type tabs available across the DNP Status Window.
The figure below shows the status of DNP digital input points 0, 1 and 2 on outstation 10.
The Modbus Address column is blank as these remote DNP points have not been mapped to any local Modbus registers.
While this data is available in the DNP Address space of the master, it is not available for use within a local program. To render DNP data available to a local program, you would have to perform an Address Map. To map DNP binary input data from outstation 10 to this master‟s local DNP database, do the following:
From the Controller menu, select DNP Configuration
Click on the Address Map tree node.
From the Address Mapping configuration panel o Click on the Add button to launch the Add/Edit Address
Mapping dialog. o Enter 10 for Station. o Select Binary Input for Object Type. o Enter a value of 1 for First Point. This is the DNP Address of the first Binary Input point in Station 10. o Enter 3 for Number of points to map. o Enter 11001 for First Register (First Modbus Register) address.
Modbus address 11000 needs to exist the in your controller database.
The completed dialog should look like this:
Realflo User and Reference Manual
May 19, 2011
981
DNP3 Protocol User Manual
Click on OK to add this entry to the Address Mapping table.
Use the DNP Master Status dialog, to confirm that remote points are being mapped to local Modbus registers as shown below:
You can also confirm that remote points are being mapped to Modbus registers by monitoring the status of Modbus registers 11001, 11002 and
11003.
How to Configure SCADAPack DNP Mimic Master
In addition to the configuration procedures for a DNP Master, following the steps below to enable the DNP Mimic master.
From the Controller menu, select DNP Configuration
Follow the steps in the
Click on the Master tree node.
Enable Mimic Mode.
SCADAPack DNP Router
SCADAPack controllers can be configured as a DNP Router. A unique characteristic of a SCADAPack DNP router is the ability to:
Route (or forward) DNP messages not destined to this station, using rules defined within a routing table.
Otherwise, a SCADAPack controller not configured for DNP routing will simply discard a message whose DNP destination address does not match that of the controller.
A DNP router is typically used when a direct communication link between the DNP master and outstation cannot be established, typically due to different physical layers on the two network segments. For instance, the physical network between the DNP SCADA Host and the router could be an
Ethernet connection, while the physical layer between the router and outstations could be a multi-drop serial RS-485 or even an RS-232 radio connection. Given that messages are routed directly from the DNP SCADA
Host to the outstations, bandwidth limitations are dictated by the speed of the serial multi-drop connection. On the contrary, there is no bandwidth limitation within a DNP Mimic architecture, as the Mimic Master immediately responds to the DNP SCADA Host on behalf of the targeted outstation. Of course, the side effect of the DNP Mimic architecture is that polled data obtained by the DNP SCADA Host may not be very current. In either case, careful design considerations based on these tradeoffs should be exercised.
As mentioned above, the SCADA Host has only one connection to a
SCADAPack DNP Router. Target outstations of the SCADA Host are connected downstream of the DNP Router as illustrated in the figure below.
Realflo User and Reference Manual
May 19, 2011
982
DNP SCADA Host
SCADAPack
DNP Router
DNP3 Protocol User Manual
SCADAPack
DNP Outstation B
SCADAPack
DNP Outstation C
Ethernet Multi-drop Serial RS-485 or RS-232 data radio
Figure 0-6: SCADAPack DNP Router and multi-dropped DNP
Outstations
In the above configuration the SCADAPack DNP Router (Outstation A above) manages the communication with the outstations. The SCADAPack
DNP router receives messages from the SCADA Host for each outstation and route or forwards the messages to the outstations, based on routing rules established with the DNP Routing table.
DNP Messages are routed based on the following logic: if (a message is received which needs to be retransmitted to someone else)
if (the message target is configured in our routing table)
if (the destination port is different from the incoming port)
or (routing is enabled on the incoming port)
then retransmit the message
Change event data in the form of unsolicited responses from the outstations are routed directly to the DNP SCADA Host, by the SCADAPack DNP router.
A DNP Router is different from a Mimic in that a router forwards messages directly to the outstations, whereas the mimic responds to some messages on behalf of the outstations. Therefore, both operation modes have the advantage of delegating the task of DNP Routing of multiple outstations to this intermediate unit. The SCADAPack DNP router handles communications paths to outstations, including such tasks as dial-up radio communication. In contrast to Mimic mode, however, the SCADA Host system still has to handle the long delays and high error rates that may be present on the communications links to the outstations.
Mimic Master and Routing are incompatible modes that should not be used together.
How to Configure a SCADAPack DNP Router
In this exercise, we will configure a SCADAPack 32 controller to route DNP messages received from DNP Master 32001 on its Ethernet port, out through com2. This message is destined for outstation 20. .This exercise assumes a valid Ethernet connection between your PC or laptop and the
SCADAPack 32.
After this exercise, you should be able to:
Configure DNP/TCP on an Ethernet port
Configure a SCADAPack DNP Router to route messages from a
SCADA DNP Host to an outstation.
Realflo User and Reference Manual
May 19, 2011
983
DNP3 Protocol User Manual
Tasks to Complete
Enable the DNP protocol communication on the communication interfaces involved in routing.
Enable routing on the communication interface.
Setup the forward and return entries in the DNP routing table.
Configuration Steps
From the Controller menu, click on Serial Ports.
In the Controller Serial Ports dialog, set the Protocol on COM2 to DNP.
In the Controller Serial Ports dialog, Enable Routing.
The completed dialog should look like this:
Click on OK to close this dialog and save your settings.
From the Controller menu, click on IP Configuration.
Select the DNP/TCP tree node from the Controller IP Configuration dialog.
Enable the protocol and leave other settings at default values.
This exercise assumes that you have a valid IP Address, Subnet Mask and
Default Gateway properly configured.
The completed dialog would look like this:
Realflo User and Reference Manual
May 19, 2011
984
DNP3 Protocol User Manual
TIP:
In this configuration, the SCADAPack DNP Router is acting as a DNP
Server on the Ethernet port. The Server Idle Timeout parameter will be used to determine how long this connection will be kept open from time of last communication activity. For a Server Idle Timeout default value of 4 minutes, and an Application Layer Timeout default value of 5 minutes, there is the possibility that the IP port will be closed, if the router is experiencing communication difficulties with the outstations. In this case, it is a good idea to increase the Server Idle Timeout to at least 2x the DNP configuration Application Layer Timeout. Or, simply reduce the Application
Layer timeout to a value less than 2x the Server Idle Timeout.
From the DNP Configuration panel, select the Routing tree node. o Click on the Add button to begin a new routing table entry. o From the Add/Edit Route dialog,
Add the route to Station 20:
Enter 20 for the Station.
Set the Port to COM2.
Leave default values for other parameters.
Click on OK to add this entry to the routing table and return to the
Routing dialog.
Add the Return route from Station 20:
Enter 32001 for the Station.
Set the Port to DNP in TCP.
Enter the IP Address of your DNP Master. In this case, the IP Address of my PC running a DNP SCADA Host software is 10.10.10.141.
Leave default values for other parameters.
The completed dialog should look like this:
Realflo User and Reference Manual
May 19, 2011
985
DNP3 Protocol User Manual
Click on OK to add this entry to the routing table and return to the
Routing dialog.
The completed routing table should look like this:
For proper operation of the router, there needs to be two routing entries in the routing table for each outstation; An entry specifying how the communication path from this router to the outstation and another communication path from the router to the SCADA DNP Master.
Design Considerations
The strength of DNP lies in its ability to offer time-stamped data, scheduled polling of data from multiple outstations and time synchronization, event data buffering and reporting by exception.
DNP was originally design to be used over a serial point-to-point (RS-232) link. As such, the protocol implements certain measures against data corruption and missing data in its Application and Data Link layers. Such measures include timeouts, retries, and checksums.
These data recovery mechanisms provided by the protocol, can be counterproductive when not properly configured over an underlying communication medium, such as Ethernet, that already provides robust measures. In such cases, the recovery mechanisms offered by DNP need to be turned off. Such considerations together with good engineering judgment, therefore, need to be practiced before one embarks on the design of a large DNP network.
This chapter outlines special considerations of the DNP protocol and implications within the SCADAPack DNP driver that should be considered when designing large networks. We also list common malpractices and a list of Frequently Asked Questions (FAQs) that arise during the course of network design.
Realflo User and Reference Manual
May 19, 2011
986
DNP3 Protocol User Manual
Considerations of DNP3 Protocol and SCADAPack DNP Driver
To allow consistent network performance, even under worse case scenarios, the following DNP specification rules should be considered when designing a DNP network using SCADAPack as the main nodes.
Unsolicited Messages always request for a Confirmation
An outstation will request for an Application Layer confirmation when it sends an unsolicited message, even if the Application Layer confirmation field is not enabled. If no response is received within an Application Layer timeout, the outstation will retry the message a number of times as determined by the Application Layer Retry parameter.
Master shall never request for Application Layer Confirmation
A Master request is accompanied by a response message from an outstation. Hence, the Application Layer confirmation on the master RTU should not be enabled.
DNP Write Messages always request for a Confirmation
As implemented in the SCADAPack DNP driver, a DNP Write request (FC
02) requires an Application Layer response from the outstation. If an acknowledgement is not received within the configured Application Layer timeout interval, the message is retried a number of times as determined by the Application Layer retry parameter.
Only one DNP3 transaction can be pending at a time
A SCADAPack DNP station will not initiate or process another DNP transaction, as long as one is outstanding. Thus, once a SCADAPack has initiated a DNP transaction, subsequent DNP3 messages received but not related to the original transaction are buffered.
SCADAPack controllers buffer 3 DNP messages
A SCADAPack serial port receive buffer can hold a maximum of 3 DNP messages or Data Link frames. If an additional DNP message is received when the buffer is full, the oldest message in the buffer is replaced with the newest one.
Output points in DNP Address Mapping issue DNP Write
Digital and analog output points contained within the DNP Address Mapping of a SCADAPack controller automatically issue DNP Write messages when their value or state changes.
Typical Configuration Malpractices and Recommendations
DNP is a capable protocol that effectively transfers some of the system engineering effort from designing a sophisticated logic program, to configuring and tuning the system using parameters. However, DNP does not remove the need to properly evaluate and engineer the communication media to support the performance expectations of the system, especially under worse case scenarios.
DNP networks can be designed around polling or report-by-exception. In a polling environment, each master request can be viewed as an invitation for an outstation device to transmit data on the shared communications medium. The master controls which device can transmit, thereby keeping collisions from occurring, as the timing of responses is predictable. In addition, masters can ask again if a response is not received, thus providing
Realflo User and Reference Manual
May 19, 2011
987
DNP3 Protocol User Manual an opportunity for the outstation to re-send lost data. Using this strategy, a master effectively manages media access thereby stopping contention with those outstations unexpectedly transmitting on their own.
DNP networks can also be designed around unsolicited communications. In this case, the outstations transmit events to the master as they occur.
When using this strategy, the communications media needs to be evaluated carefully in regards to the need for collision detection and prevention, if consistent network performance is to be expected.
Given that typical systems are designed using a combination of both strategies, is a good idea to start by configuring the network for poll mode, as it can be easily tuned to cater for unsolicited messaging, when system characteristics under worst case conditions become known. Below are several requirements of DNP system architecture that require careful engineering judgment .
Multiple high priority unsolicited messages configured in outstation.
System with multiple outstations, each containing numerous Class 1 events, configured with a Class 1 Hold Count of 1.
Relying on unsolicited messaging to get event data to master. System not designed around master polling for events.
Multiple masters with poor communication link.
Insufficient use of Deadband and debounce to curb event generation.
Master RTU has Application Layer confirmation enabled.
Enabling both the Application and Data Link Layer confirmations.
Setting very high Application Layer timeout values over high speed networks.
DNP Address mapping contains multiple analog and digital output points that change rapidly.
The aforementioned statements and recommendations are provided below.
These recommendations are for consistent performance under worse case situations, and are based on the special considerations provided in the previous section.
Multiple High Priority Unsolicited Messages
A common configuration malpractice is to enable numerous high priority events objects within an outstation, and configure the outstation to trigger an unsolicited message to the master each time a new event occurs. In a
SCADAPack controller, this is accomplished by configuring numerous Class
1 event objects, and enabling Class 1 Unsolicited Responses (Messaging) with a Hold Count or Hold Time of 1.
A Hold Count of 1 and Hold Time of 60 seconds specified for Class 1 events, imply that the controller will immediately trigger an unsolicited event as one occurs. If this outstation and others have a multitude of Class 1 event objects, visualize the worst-case scenario as a burst of messages being transmitted to the master at the same time. Given that a
SCADAPack serial port buffer can only handle three DNP Data Link frames at any given time, some messages might get lost, especially if the master is required to immediately retransmit this message to some other node in return.
Realflo User and Reference Manual
May 19, 2011
988
DNP3 Protocol User Manual
Such a system is designed around unsolicited messaging and is, therefore, far more susceptible to network collisions if proper management of bandwidth it not exercised. Given that a SCADAPack controller can only process one DNP transaction at a time, there is also a good chance that the serial port receive buffer will overflow, adding to the cost of lost messages.
Recommendations:
In general, bandwidth is used more efficiently in a large DNP system if the master is designed to poll for event data more frequently and static data less regularly.
Recommended practice is also to reserve unsolicited messaging for a small number of data. If possible no more than 3 messages are sent to the master at exactly the same time, under the worst-case scenario, as some event data may be lost if the master is currently busy processing another transaction, unless random retry intervals are put in place.
If unsolicited messaging is the predominant data transfer method, an approach to manage network usage, could be to configure a group of three or less outstations with a Hold Time that is unique within the group.
The table below shows an example configuration for Hold Time and Hold
Counts for Class 1 events across six outstations.
Table 0-1: Hold Time and Hold Count Setup in for Six DNP Outstations
DNP
Outstation
Address
Hold Time
(seconds)
Hold Count
11
12
13
14
15
1
1
1
2
2
100
100
100
100
100
16 2 100
Master not polling frequently causing event buffer overflows
An outstation does not discard the events within its buffer until all its configured masters have acknowledged receipt of these events. This means that an outstation event buffer may eventually fill up and overflow leading to missing events. Buffer overflows typically indicate a poorly configured system.
When the system is designed around unsolicited messaging, there is a good likelihood of media contention causing buffer overflows. On the contrary, if the system is designed around frequent master poll for event data, there will be fewer chances of buffers overflowing causing missing event data.
As stated earlier, immediate reporting of events using unsolicited messaging should be reserved for those absolutely rare occurring events. This is because unsoliciting these messages back to the master will be reliable only if there is a substantial amount of unused bandwidth on the communication
Realflo User and Reference Manual
May 19, 2011
989
DNP3 Protocol User Manual media. A good rule of thumb is to have 50% or more of unused bandwidth available, evenly distributed over a time frame.
Recommendation:
Design the system around frequent master poll of class events and less regular integrity polls. Reserve unsolicited messaging for infrequent high priority events. If network traffic is predominated by unsolicited messaging, allocate 50% or more unused bandwidth as quiet time.
Outstation reports to Multiple Masters with Poor Communications Link
A poor communications link to one of an outstation‟s multiple masters will keep the outstation‟s event buffer from being emptied, as events cannot be reported to the master. This could lead to buffer overflow situations and loss of event data.
Recommendation:
Check that the communication path to masters of an outstation is robust.
Insufficient Use of Input Deadband or Debounce
Event generation on a DNP analog input is controlled by a Deadband parameter. On a digital input, event generation is controlled by a debounce parameter. Default settings of zero for these parameters are typically overly aggressive and may lead to events being generated due to noise.
Recommendation:
Set the analog Deadband and debounce parameters appropriately to non-zero values.
Master Confirmation and Retries
Application or Data Link Layer confirmations should never be enabled on a master as:
Master requests typically will fit within a single Application Layer fragment hence there is need for Data Link Layer confirmations.
Master request typically require a response, hence no need for
Application Layer confirmations.
Thus, enabling the Application Layer Confirmation on a DNP master is obsolete practice and may instead reduce system performance.
Recommendation:
Disable the Application Layer Confirmation in a master
SCADAPack controller. Typical retry values for Application Layer retries lie between 1 and 3. Lengthy retries may instead burden the communication medium
Outstation Confirmations and Retries
Confirmations on an outstation serve two useful purposes:
Check that a master received unsolicited responses from the outstation.
To confirm that a master correctly received responses to its request
Unsolicited messages will request for an Application Layer confirmation, whether or not the Application Layer Confirmation is enabled on the outstation. If network traffic is predominantly unsolicited messaging, the
Application Layer confirmation does not need to be enabled.
When the master is configured, as recommended, to frequently poll the outstation for event data using read request, while imposing a limit on the number of events the outstation should include in its response, the outstation still needs to know if the master received its replies so that it can:
Realflo User and Reference Manual
May 19, 2011
990
Recommendation:
DNP3 Protocol User Manual
Remove these events from its buffer
Know what to transmit next.
To cater for confirmations to read responses, Application Layer Confirmation in the outstation typically needs to be enabled.
The Data Link Layer breaks down Application Layer fragments into smaller frames. Smaller packet sizes reduce bit error in noisy environments. While it is better to accept the overhead of confirming each Data Link Layer frame of a multi-frame message, and re-transmit corrupted frames, than to re-send an entire Application Layer fragment, a viable alternative is to reduce the
Application Layer fragment size and use only Application Layer confirmations. When fragments are reduced to the size of a Data Link Layer frame, the overhead of Application Layer confirmations, and the probability of noise corrupting those confirmation messages, is nearly the same as for
Data Link Layer confirmations.
Enabling the Data Link layer confirmation on the outstation, therefore, is not required when the communication medium is not robust. For example, certain data radios, e.g., FreeWave 9000 MHz spread spectrum radios, implement a robust mechanism to ensure that a data packet make it to their desired destination; TCP/IP incorporates robust mechanisms to stop missing data; a local serial link between stations is also very robust. In these cases, it is not necessary to enable the Data Link Layer confirmations.
If, however, physical medium quality if below par, such as in the case of noisy radio networks, or a shaky PSTN connections, then one should enable the Data Link Layer confirmation only, or as mentioned earlier, reduce the
Application Layer maximum fragment length below 249 bytes.
If either the Application or Data Link Layer Confirmation is enabled, retries should be configured to a low non-zero value. Typical retry values lie between 1 and 3. Lengthy retries may instead burden the communication medium
Application and Data Link
Layer confirmations in an outstation can be set according to the following table:
Data
Acquisition
Configuration master polls outstation frequently for event data (also limits number of events in read response)
Communication Medium
High
Reliability
Low
Enable
Application
Layer
Confirmation
Disable
Application Layer
Confirmation
Disable Data
Link Layer
Confirmation
Enable Data Link
Layer
Confirmation master Enable Application Disable
Realflo User and Reference Manual
May 19, 2011
991
DNP3 Protocol User Manual does not poll frequently enough and outstation generates lot of unsolicited messages
Regardless of the data acquisition strategy, if the Max
Application
Layer fragment is set to a values less than 249
Layer
Confirmation
Disable Data Link
Layer
Confirmation
Enable Application
Layer
Confirmation
Disable Data Link
Layer
Confirmation
Application
Layer
Confirmation
Enable Data
Link Layer
Confirmation
Enable
Application
Layer
Confirmation
Disable Data
Link Layer
Confirmation
It is not required to enable BOTH the Application and Data Link Layer
Confirmations.
Setting relatively large Application Layer timeouts
On a high speed link, such as Ethernet, configuring a high Application Layer timeout does not increase network reliability. Instead this reduces system performance, as there will be a significant portion of time within the timeout period, after which the IP transaction may have been terminated.
Typically, an Ethernet transaction is completed in the order of a millisecond and a DNP master SCADAPack controller, by default, closes its DNP TCP port within 10 seconds of no activity. A DNP SCADAPack controller acting as an outstation closes its port by default in about 4 minutes.
Under these default conditions, if the application layer timeout on a
SCADAPack DNP master is set for 15 seconds, for instance, the port may have closed 10 seconds after last activity, but the application may still be waiting for a timeout.
If a message is somehow lost, and the timeout is set for 5 seconds, for instance, the application will still be waiting for a response even though the
IP transaction has terminated. This results to wasted bandwidth.
Recommendation:
When operating over high speed links, make
Application Layer timeouts as small as possible.
DNP Address mapping contains multiple output points
The DNP Address Mapping table allows local Modbus registers in the
SCADAPack DNP master to be mapped to DNP points in an outstation.
Realflo User and Reference Manual
May 19, 2011
992
DNP3 Protocol User Manual
Each time an output register defined within the DNP Address Mapping table changes, a DNP Write message (FC 2) is immediately issued to update the corresponding DNP point in the outstation.
If numerous output registers that change frequently, are listed in the
Address Mapping table, the network will be overburdened with a multitude of
DNP Write messages.
Recommendation:
Reserve Address Mapping only for mapping of outstation DNP data that needs to be used by the master Modbus database, or to segregate points from different outstations in the master. If numerous points are being mapped from the outstation to the master, the system is not designed properly. In this case, it may be worthwhile to consider transferring application logic from the master to the outstation.
Configuration FAQ
Complimentary commonly asked questions and answers are given below.
When configuring a routing entry in the DNP Routing table of a
SCADAPack, one has to specify the Data Link Layer Timeout and Retries.
Do these fields take precedence over the same fields found under the Data
Link Layer configuration panel?
Yes.
In a master-outstation architecture, how do you recommend we setup time synchronization?
Recommended practice is to configure the master to initiate time synchronization to the outstations.
DNP3 provides 4 data classes; Class 0 (Static or None), Class 1, Class 2 and Class 3. How does I decide which class to assign any given I/O point?
In a SCADAPack controller, configured DNP points by nature, are members of the Class 0 type. Class 0 data is the current value or state of a DNP point. So, when a master does a Class 0 poll to an outstation, the current value or state of DNP points within the database are returned.
Value or state changes on a point are captured as Class 1, Class 2 or Class
3 event data. Typically, highest priority events are assigned to Class 1 and the lowest priority event to Class 3.
What does Class of „None‟ mean?
Class None is Class 0 or Static.
Why does this setting do: Enable Unsolicited Responses On Startup?
This setting enables unsolicited response (or unsolicited message) transmission, when power to an RTU is cycled or when its configuration is changed. In this case, the RTU does not have to wait for Function Code 20 or 0x14 (Enable Unsolicited Responses) from the master before is starts sending any collected events.
This field should be set to No, to allow a master control when an outstation is able to send unsolicited messages. Recommended practice is to allow a master to enable unsolicited message transmission on outstations.
Why would I ever need to change the Application Layer Maximum Fragment
Length?
Realflo User and Reference Manual
May 19, 2011
993
DNP3 Protocol User Manual
Define DNP I/O points
Enable Application
Layer Confirmation
Should I Initiate
Time synchronization?
The Application Layer Maximum Fragment Length determines the maximum amount of memory that is reserved for each application layer fragment.
The default is 2048 bytes on SCADAPack controllers although outstations need to be prepared to receive fragments sizes of at least 249 bytes.
When communicating with those devices with insufficient memory it is necessary to limit the maximum application layer fragment length to what the outstation can handle. In addition, limiting the application layer fragment size beyond 249 also reduces the maximum Data Link layer frame length.
Certain data radios may give better efficiency when transmitting data packets less than the maximum data link fragment size of 249 bytes. With these radios, it is necessary to reduce the application layer‟s maximum fragment size below 249 bytes as required by the radio.
Other types of data radios, such as FreeWave‟s 900 MHz Spread Spectrum radios, provide configuration options to optimize efficiency by changing the maximum packet size. In this case, it is not necessary to reduce the application layer maximum fragment size.
In addition, when the communication medium is noisy, it is typically more efficient to transmit smaller packets than larger packets. In this case, setting small Application Layer fragments would force smaller data link frames, which is a better strategy in a noisy environment.
Limiting the application layer fragment size reduces the rate at which event data is retrieved from the buffers, thus increasing the possibility of event buffer overflows, if the event data is not being retrieved in a timely fashion.
Reducing the maximum application layer fragment size, increases network traffic and also reduced data throughput as an Application Layer
Confirmation is required for each fragment of a multi-fragment message.
Why would I ever want to „Limit that maximum number of events in a read response?”
This is another strategy that can be used to limit the Application Layer fragment of an outstations‟ response message. This strategy could be used under noisy environments.
Also, this could be used to keep an outstation with a large collection of event data from holding the communication media captive while transmitting all its events.
What behavior should we expect from a SCADAPack when the event logs are full?
When a new event is collected and the SCADAPack DNP event buffer is full, the oldest event is deleted and the newest event added into the buffer.
What is the main difference between SCADAPack DNP driver configuration modes?
DNP Master DNP Mimic Master Address Mapping Router Outstation
Not necessary
No
Not necessary
No
Not necessary
No
Not necessary
No.
Yes
Yes No. No. No.
Not necessary.
No.
Realflo User and Reference Manual
May 19, 2011
994
Poll for Class DNP static and Class data?
Initiates Unsolicited messages?
Router Messages not destined to this station?
When to use
Yes
No
No
Yes
No
Some
Master in a Point to Multipoint network
Data Concentrator with many outstations that will take a while to configure. When outstation data does not need to be available to logic in this node.
Yes
No
No
When remote
DNP data is needed by local program
DNP3 Protocol User Manual
No. No
No
Yes
Strictly
Repeater
Yes
No
Forms basic node in DNP network.
Realflo User and Reference Manual
May 19, 2011
995
DNP3 Protocol User Manual
DNP Configuration Menu Reference
This section of the manual details the SCADAPack DNP3 driver configuration parameters. The DNP Configuration panel is accessed from the Controller | DNP Configuration menu from either Telepace or
ISaGRAF. Browse through this chapter to familiarize yourself with some key DNP3 concepts and their implementation in a SCADAPack controller.
When selected the DNP Settings window is opened, as shown below.
The DNP Settings window has a tree control on the left side of the window.
The tree control appears differently depending on the controller type selected. The SCADAPack 314/330/334, SCADAPack 350, SCADAPack 32 and SCADAPack 32P controllers support DNP master and include the bolded items in the following list. SCADAPack controllers not supporting
DNP master the bolded items are not included. This tree control contains headings for:
Application Layer
Data Link Layer
Master
Master Poll
Address Mapping
Routing
Binary Inputs
Binary Outputs
16-Bit Analog Inputs
32-Bit Analog Inputs
Realflo User and Reference Manual
May 19, 2011
996
DNP3 Protocol User Manual
Short Floating Point Analog Inputs
16-Bit Analog Outputs
32-Bit Analog Outputs
Short Floating Point Analog Outputs
16-Bit Counter Inputs
32-Bit Counter Inputs
When a tree control is selected by clicking the mouse on a heading a property page is opened for the header selected. From the property page the DNP configuration parameters for the selected header is displayed.
As DNP objects are defined they are added as leaves to the object branch of the tree control. When an object is defined the object branch will display a collapse / expand control to the left of the branch.
The Allow Duplicate Modbus Addresses checkbox (in the bottom left corner) determines if the Modbus I/O database addresses assigned to the
DNP data points need to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Uncheck the box if you want to be notified about duplicate addresses. If an attempt is made to use a Modbus address that has already been used for another DNP point the following message is displayed.
Application Layer Configuration
The Application Layer property page is selected for editing by clicking
Application Layer in the tree control section of the DNP Settings window.
When selected the Application Link Layer property page is active.
Realflo User and Reference Manual
May 19, 2011
997
DNP3 Protocol User Manual
Application Layer parameters are set in this property page. Each parameter is described in the following paragraphs.
The Communication section of the dialog contains the configurable application layer communication parameters.
When the Application Confirmation feature is enabled, the SCADAPack controller requests a confirmation from the master station for any data transmitted. When it is disabled, the controller does not request a confirmation from the master station and assumes that the master receives the data it sends successfully. However if the data includes event data
(including unsolicited messages), the controller requests a confirmation from the master regardless of whether this feature is enabled or disabled. Valid selections for this parameter are:
Enabled
Disabled
The Maximum Fragment Length is maximum size of a single response fragment that the RTU will send. If the complete response message is too large to fit within a single fragment, then the SCADAPack controller will send the response in multiple fragments. Valid values are between 100 and 2048 bytes.
This parameter is adjustable to allow for interoperability with simple DNP3 devices that require smaller application layer fragments. Devices with limited memory may restrict the application layer fragment size to as low as
249 bytes.
The Maximum Fragment Length parameter applies to responses from read commands only. It does not affect unsolicited responses.
Realflo User and Reference Manual
May 19, 2011
998
DNP3 Protocol User Manual
The Retries entry maximum number of times the application layer will retry sending a response or an unsolicited response to the master station. This does not include any retries performed by the data link layer. Valid values are between 0 and 255.
Using application layer Confirmation and Retries is inherently more efficient than using data link layer Confirmation and Retries. Each fragment sent by the Application layer may require as many as 10 data link layer frames to be sent, each with its own confirmation message. The application layer is typically preferred for message confirmation for this reason.
The Application Timeout is the expected time duration (in milliseconds) that the master station's application layer requires to process and respond to a response from the SCADAPack controller. This SCADAPack controller uses this value in setting its time-out interval for master station responses.
This value should be large enough to avoid response time-outs. The value needs to be kept small enough so as not to slow system throughput. The value of this element is dependent on the master station. Valid values are between 100 and 60000 milliseconds.
The Time Synchronization section of the dialog defines when and how often the SCADAPack outstation prompts the master station to synchronize the SCADAPack controller time. Messages need to be sent between the
Master and Remote stations for Time Synchronization to work. Valid selections for this parameter are:
The None selection will cause the SCADAPack controller to not request
Time Synchronization.
The At Start Up Only selection will cause the SCADAPack controller to request Time Synchronization at startup only.
The Interval selection will cause the SCADAPack controller to request
Time Synchronization at startup and then every Interval minutes after receiving a time synchronization from the master. Valid entries for
Interval are between 1 and 32767 minutes. The default value is 60 minutes.
Time Synchronization may instead be initiated by the Master for each
Outstation. This may be selected in the Add/Edit Master Poll dialog. It is not required to enable Time Synchronization at both the Master and the
Outstation.
The Unsolicited Response section of the dialog defines which class objects are enabled or disabled from generating report by exception responses. Unsolicited responses are individually configured for Class 1,
Class 2, and Class 3 data.
The Enable Unsolicited controls enables or disables the generation of unsolicited events for Class 1, Class 2 or Class 3 data. If unsolicited responses are disabled for a Class the controller will not generate unsolicited events for that Class. If unsolicited responses are enabled the controller generates unsolicited events for that Class if its value or state exceeds a defined threshold. Valid selections are:
Enabled
Disabled
The controller does not transmit collected unsolicited messages (or responses) to a master, even after the Hold Time or Hold Count conditions
Realflo User and Reference Manual
May 19, 2011
999
DNP3 Protocol User Manual have been met, unless its 'Enable Unsolicited Responses on Start Up' field is set to 'Yes' or the master triggers this transmission.
To configure a master to control unsolicited message transmission from a remote, see the Master Poll configuration panel.
The Hold Time parameter is used only when unsolicited responses are enabled for a Class. This parameter defines the maximum period (in seconds) the RTU will be allowed to hold its events before reporting them to the DNP master station. When the hold time has elapsed since the first event occurred, the RTU will report to the DNP master station events accumulated up to then. This parameter is used in conjunction with the Hold
Count parameter in customizing the unsolicited event reporting characteristics. The value used for the Hold Time depends on the frequency of event generation, topology and performance characteristics of the system. The valid values for this parameter are 0 - 65535. The default value is 60 seconds.
The Hold Count parameter is used only when unsolicited responses are enabled for a Class. This parameter defines the maximum number of events the RTU will be allowed to hold before reporting them to the DNP master station. When the hold count threshold is reached, the RTU will report to the master, events accumulated up to that point. This parameter is used in conjunction with the Hold Time in customizing the unsolicited event reporting characteristics. So that an unsolicited response is sent as soon as an event occurs, set the Hold Count parameter to 1. The valid values for this parameter are 1 - 65535. The default value is 10.
The Enable Unsolicited Responses on Start Up parameter enables or disables unsolicited responses on startup. This affects the default controller behaviour after a start-up or restart. Some hosts require devices to start up with unsolicited responses enabled. It should be noted this is nonconforming behaviour according to the DNP standard. Valid selections are:
Yes
No
The default selection is Yes.
The Send Initial Unsolicited Response on Startup parameter enables or disables Send Initial unsolicited responses on startup. This parameter controls whether an initial unsolicited response with null data is sent after a start-up or restart. Valid selections are:
Yes
No
The default selection is No.
The Resend unreported events after parameter enables or disables the retransmission of events after every attempt to report the events have not succeeded.
Many communications networks experience occasional communications failures. In such networks, even when message retries are used, there is a chance that some messages will not be sucessful
– meaning there is a chance some unsolicited messages will be unsuccessful and change events will not be reported to the master station. The events remain in the outstation buffers until polled or additional events are generated.
Realflo User and Reference Manual
May 19, 2011
1000
DNP3 Protocol User Manual
To address this the Resend unreported events after parameter is added to the DNP configuration. This parameter controls a timer for retrying the transmission of unsolicited messages.
Whenever a DNP unsolicited message is unsucessful, including its retries, then instead of just retiring the message, an unsolicited resend timer is initiated. After the configured time delay has passed, the unsolicited message will be sent again, including the configured retries. This process will be repeated continuously until the unsolicited message is successfully sent and acknowledged. In the case of multiple masters the unsolicited resend timer is uninitiated after the retries are expired for the last master in the polling list.
SCADAPack firmware 2.44 (and later), SCADAPack 32 Firmware 1.92 (and later), SCADAPack 314/330/334, SCADAPack 350/SCADAPack firmware
1.25 (and later) and SolarPack 410 firmware 1.32 (and Later) support this feature.
Valid values are 1 to 65535 seconds. The default value is 0 seconds. The control is unselected by default.
If Resend unreported events is not selected, the controller will not resend unreported events after attempts are unsucessful, until polled or until additional events are generated and their reporting threshold is reached.
The Resend unreported events control can be selected even when no classes are enabled. This allows the feature to be used in a mimic controller that is being used to pass outstations events to a host.
The Dial Up section of the dialog defines modem parameters used when a dial up modem is used to communicate with stations that use dial up communication. The phone numbers for the stations are defined in the
Routing table.
The Modem Initialization is the string that will be sent to the modem prior to each call. This is an ASCII null-terminated string. The maximum length of the string is 64 characters, including the null terminator.
The Attempts controls the maximum number of dial attempts that will be made to establish a Dial Up connection. The valid values for this parameter are 1
– 10. The default value is 2.
The Dial Type parameter controls whether tone or pulse dialing will be used for the call. Valid values are Tone dialing or Pulse dialing. The default value is Tone dialing.
The Connect Timeout controls the maximum time (in seconds) after initiating a dial sequence that the firmware will wait for a carrier signal before hanging up. The valid values for this parameter are 1
– 65535. The default value is 45.
The Inactivity Timeout controls the maximum time after message activity that a connection will be left open before hanging up. The valid values for this parameter are 1
– 65535 seconds. The default value is 45 seconds.
The Pause Time controls the delay time (in seconds) between dial events, to allow time for incoming calls. The valid values for this parameter are 1
–
65535. The default value is 10.
The Operate Timeout parameter specifies the timeout interval between a
Select and Operate request from the Master. If after receiving a valid Select control output request from the master, the RTU does not receive the
Realflo User and Reference Manual
May 19, 2011
1001
DNP3 Protocol User Manual corresponding Operate request within this time-out interval, the control output request is unsucessful. The value of this parameter, expressed in seconds, is dependent on the master station, the data link and physical layer. Valid values are 1 to 6500 seconds. The default value is 15 seconds.
The Master needs to have the Select/Operate functionally in order to use this feature.
The Report only Level 2 Compliant Objects in Class Polls parameter affects how Short Float Analog Input, Short Float Analog Output, and 32-bit
Analog Output objects are reported. These objects are converted to 32-bit
Analog Input and 16-bit Analog Output objects when this parameter is selected. Valid selections are:
Yes
No
The default selection is No.
The Limit Maximum Events in Read Response parameter allows limiting the number of events in a read response. Select the checkbox to enable the limit. Valid values are 1 to 65535. The default value is disabled.
The Maximum Events parameter applies to responses from read commands only. It does not affect unsolicited responses.
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points need to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Click the OK button to accept the configuration changes and close the
DNP Settings dialog.
Click the Cancel button to close the dialog without saving any changes.
Data Link Layer Configuration
The Data Link Layer property page is selected for editing by clicking Data
Link Layer in the tree control section of the DNP Settings window. When selected the Data Link Layer property page is active.
Realflo User and Reference Manual
May 19, 2011
1002
DNP3 Protocol User Manual
Data Link Layer parameters are set in this property page. Each parameter is described in the following paragraphs.
The Master Station Addresses list box contains a list of Master station addresses that the SCADAPack controller will respond to. The default list contains one master address of 100. This address may be edited, or changed, and up to 8 master stations may be added to the list. Valid entries for Master Station Addresses are 0 to 65519.
When a master station polls for event data, the controller will respond with any events that have not yet been reported to that master station.
When an unsolicited response becomes due, it will be sent to each configured master station in turn. A complete unsolicited response message transaction, including retries, will be sent to the first configured master station. When this transaction has finished, a complete unsolicited response message transaction including retries will be sent to the next configured master station, and so on for the configured master stations.
Change events will be retained in the event buffer until they have been successfully reported to configured master stations.
Select the Add button to enter a new address to the Master Station Address list. Selecting the Add button opens the Add Master Station Address dialog. Up to 8 entries can be added to the table. An error message is displayed if the table is full.
Select the Edit button to edit address in the Master Station Address list.
Selecting the Edit button opens the Edit Master Station Address dialog.
The button is disabled if there are no entries in the list.
Realflo User and Reference Manual
May 19, 2011
1003
DNP3 Protocol User Manual
The Master Station Address edit box specifies the Master Station Address.
Enter any valid Station address from 0 to 65519.
The OK button adds the Master Station Address to the list and closes the dialog. An error is displayed if the Master Station Address is invalid, if the address is already in the list, or if the address conflicts with the
RTU station address.
The Cancel button closes the dialog without making any changes.
The RTU Station Address parameter specifies the address of this RTU. It is the source address used by this DNP driver when communicating with a master station. Each DNP station in a network needs to have a unique address, including the Master station. Valid entries for RTU Station Address are 0 to 65519.
The Data Link Confirmation parameter specifies whether or not the RTU requests the underlying data link transmitting its response to use a high quality service, which generally means that the data link requires the receiving data link to confirm receipt of messages.
The Retries parameter specifies the maximum number of times the data link layer will retry sending a message to the master station. This parameter is only used when responding to a request from a Master station, when there is no corresponding entry in the Routing dialog for that station. This is independent of the application layer retries. The valid values for this parameter are 0 - 255. Setting the value to 0 disables sending retries.
Using data link layer Confirmation and Retries is inherently less efficient than application layer Confirmation and Retries. Each fragment sent by the
Application layer may require as many as 10 data link layer frames to be sent, each with its own confirmation message. The data link layer is typically not used for message confirmation for this reason.
The Data Link Timeout parameter specifies the expected time duration that the master station's data link layer requires to process and respond to a message from the RTUs data link layer. It is used by the RTU in setting its time-out interval for master station responses. This value should be large enough to avoid response time-outs. The value needs to be kept small enough so as not to slow system throughput. The value of this element is dependent on the master station. It is expressed in milliseconds. Valid values are 10 to 60000 milliseconds. The default value is 500 milliseconds.
Click the OK button to accept the configuration changes and close the
DNP Settings dialog.
Click the Cancel button to close the dialog without saving any changes.
Click the Delete button to remove the selected rows from the list. This button is disabled if there are no entries in the list.
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points needs to
Realflo User and Reference Manual
May 19, 2011
1004
Master
DNP3 Protocol User Manual be unique. Check this box if you want to allow more than one point to use the same Modbus address.
The Master property page is selected for editing by clicking Master in the tree control section of the DNP Settings window. This selection is only visible if the controller type is SCADAPack 314/330/334, SCADAPack 350,
SCADAPack 32 or SCADAPack 32P. These controllers support DNP
Master. When selected the Master Application Link Layer property page is active.
Master parameters are set in this property page. Each parameter is described in the following paragraphs.
The Mimic Mode parameter specifies the DNP Mimic Mode. The valid selections are Enable or Disable. When DNP Mimic Mode is enabled the controller will intercept DNP messages destined for a remote DNP station address, and will respond directly, as though the controller were the designated target. For read commands, the controller will respond with data from its Remote DNP Objects corresponding with the target address. For write commands, the controller will write data into its Remote DNP Objects, and issue a direct response to acknowledge the command. It will then issue a new command to write the data to the designated target. The default selection is Disabled.
The Base Poll Interval parameter is the base interval (in seconds) for polling slave devices. The poll rates and issuing time synchronisation will be configured in multiples of the base poll interval. The slave devices with the same poll rates will be polled in the order they appear in the poll table. The valid values for this parameter are 1 to 65535. The default value is 10 seconds.
Realflo User and Reference Manual
May 19, 2011
1005
Master Poll
DNP3 Protocol User Manual
The Master Poll property page is selected for editing by clicking Master Poll in the tree control section of the DNP Settings window. This selection is only visible if the controller type is a SCADAPack 314/330/334, SCADAPack
350, SCADAPack 32 or SCADAPack 32P. These controllers support DNP
Master. When selected the Master Poll property page is active and button
Copy is renamed to Edit.
The Master Poll displays slave devices to be polled by this master station as a row, with column headings, in the table. The table may have up to 1000 entries. A vertical scroll bar is used if the list exceeds the window size.
Slave devices in the Master Poll table need to be added to the Routing table.
The Station column displays the address of the DNP slave device to be polled. Each entry in the table should have unique DNP Station Address.
The Class 0 Rate column displays the rate of polling for Class 0 data, as a multiple of the base poll interval.
The Class 1 Rate column displays the rate of polling for Class 1 data, as a multiple of the base poll interval.
The Class 2 Rate column displays the rate of polling for Class 2 data, as a multiple of the base poll interval.
The Class 3 Rate column displays the rate of polling for Class 3 data, as a multiple of the base poll interval.
The OK button saves the table data and closes the DNP Settings dialog.
The Cancel button closes the dialog without saving changes.
Select the Add button to enter a new row in the Master Poll. Selecting the
Add button opens the Add/Edit Master Poll dialog.
Realflo User and Reference Manual
May 19, 2011
1006
DNP3 Protocol User Manual
Select the Edit button to modify the selected row in the Master Poll.
Selecting the Edit button opens the Add/Edit Master Poll dialog containing the data from the selected row. This button is disabled if more than one row is selected or if there are no entries in the table.
The Delete button removes the selected rows from the table. This button is disabled if there are no entries in the table.
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points need to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Click on the column headings to sort the data. Clicking once sorts the data in ascending order. Clicking again sorts the data in descending order.
Add/Edit Master Poll Dialog
This dialog is used to edit an entry or add a new entry in the Master Poll.
The Station edit control displays the address of the DNP slave device to be polled. Valid values are 0 to 65519.
The Class 0 Polling section of the dialog specifies the type and rate of polling for Class 0 data.
The None selection disables class 0 polling for the slave station. This is the default selection.
The At Start Up Only selection will cause the master to poll the slave station at startup only.
The Interval selection will cause the master to poll the slave station at startup and then every Interval of the base poll interval. For example if the base poll interval is 60 seconds and the Interval parameter is set to
60 then the master will poll the slave station every hour. Valid values are
1 to 32767. The default value is 60.
The Poll Offset parameter is used to distribute the load on the communication network. The Poll Offset is entered in multiples of the base poll interval. Valid values for this parameter are 0 to the Poll
Interval value minus 1. Any non-zero value delays the start of polling for
Realflo User and Reference Manual
May 19, 2011
1007
DNP3 Protocol User Manual the specified objects by that amount. The default value is 0. This control is disabled when None is selected, and enabled otherwise. For an example of using the Poll Offset parameter see the Poll Offset
Example at the end of this section.
The Class 1 Polling section of the dialog specifies the type and rate of polling for Class 1 data.
The None selection disables class 1 polling for the slave station. This is the default selection.
The At Start Up Only selection will cause the master to poll the slave station at startup only.
The Interval selection will cause the master to poll the slave station at startup and then every Interval of the base poll interval. For example if the base poll interval is 60 seconds and the Interval parameter is set to
60 then the master will poll the slave station every hour. Valid values are
1 to 32767. The default value is 60.
The Poll Offset parameter is used to distribute the load on the communication network. The Poll Offset is entered in multiples of the base poll interval. Valid values for this parameter are 0 to the Poll
Interval value minus 1. Any non-zero value delays the start of polling for the specified objects by that amount. The default value is 0. This control is disabled when None is selected, and enabled otherwise. For an example of using the Poll Offset parameter see the Poll Offset
Example at the end of this section.
Limit Maximum Events allows limiting the number of events in poll responses for Class 1/2/3 data. The checkbox is not checked by default, meaning there is no limit on the number of events. Select the checkbox to specify a limit. The valid values for this parameter are 1 to 65535. The default value is 65535. This control is disabled when None is selected, and enabled otherwise.
The Maximum Events parameter can be used to manage communication load on a system.
Consider the example of a master polling some data logging remotes, and the case where one of the remotes has been offline for a long time.
The remote will have built up a large number of buffered events. If the master polled it for every event, the reply might take a long time, and cause an unwanted delay in the master's polling cycle. However if the master limits the number of events returned, the reply message duration will be more deterministic and the master can keep its poll loop timing maintained. In this case, the event retrieval from the data logger will be distributed over a number of poll cycles.
The Class 2 Polling section of the dialog specifies the type and rate of polling for Class 2 data.
The None selection disables class 1 polling for the slave station. This is the default selection.
The At Start Up Only selection will cause the master to poll the slave station at startup only.
The Interval selection will cause the master to poll the slave station at startup and then every Interval of the base poll interval. For example if the base poll interval is 60 seconds and the Interval parameter is set to
Realflo User and Reference Manual
May 19, 2011
1008
DNP3 Protocol User Manual
60 then the master will poll the slave station every hour. Valid values are
1 to 32767. The default value is 60.
The Poll Offset parameter is used to distribute the load on the communication network. The Poll Offset is entered in multiples of the base poll interval. Valid values for this parameter are 0 to the Poll Interval value minus 1. Any non-zero value delays the start of polling for the specified objects by that amount. The default value is 0. This control is disabled when
None is selected, and enabled otherwise. For an example of using the Poll
Offset parameter see the Poll Offset Example at the end of this section.
Limit Maximum Events allows limiting the number of events in poll responses for Class 1/2/3 data. The checkbox is not checked by default, meaning there is no limit on the number of events. Select the checkbox to specify a limit. The valid values for this parameter are 1 to 65535. The default value is 65535. This control is disabled when None is selected, and enabled otherwise.
The Maximum Events parameter can be used to manage communication load on a system. Consider the example of a master polling some data logging remotes, and the case where one of the remotes has been offline for a long time. The remote will have built up a large number of buffered events.
If the master polled it for every event, the reply might take a long time, and cause an unwanted delay in the master's polling cycle. However if the master limits the number of events returned, the reply message duration will be more deterministic and the master can keep its poll loop timing maintained. In this case, the event retrieval from the data logger will be distributed over a number of poll cycles.
The Class 3 Polling section of the dialog specifies the type and rate of polling for Class 3 data.
The None selection disables class 1 polling for the slave station. This is the default selection.
The At Start Up Only selection will cause the master to poll the slave station at startup only.
The Interval selection will cause the master to poll the slave station at startup and then every Interval of the base poll interval. For example if the base poll interval is 60 seconds and the Interval parameter is set to
60 then the master will poll the slave station every hour. Valid values are
1 to 32767. The default value is 60.
The Poll Offset parameter is used to distribute the load on the communication network. The Poll Offset is entered in multiples of the base poll interval. Valid values for this parameter are 0 to the Poll
Interval value minus 1. Any non-zero value delays the start of polling for the specified objects by that amount. The default value is 0. This control is disabled when None is selected, and enabled otherwise. For an example of using the Poll Offset parameter see the Poll Offset
Example at the end of this section.
Limit Maximum Events allows limiting the number of events in poll responses for Class 1/2/3 data. The checkbox is not checked by default, meaning there is no limit on the number of events. Select the checkbox to specify a limit. The valid values for this parameter are 1 to 65535. The default value is 65535. This control is disabled when None is selected, and enabled otherwise.
Realflo User and Reference Manual
May 19, 2011
1009
DNP3 Protocol User Manual
The Maximum Events parameter can be used to manage communication load on a system. Consider the example of a master polling some data logging remotes, and the case where one of the remotes has been offline for a long time. The remote will have built up a large number of buffered events.
If the master polled it for every event, the reply might take a long time, and cause an unwanted delay in the master's polling cycle. However if the master limits the number of events returned, the reply message duration will be more deterministic and the master can maintain its poll loop timing maintained. In this case, the event retrieval from the data logger will be distributed over a number of poll cycles.
The Time Synchronization Rate section of the dialog specifies the rate of issuing a time synchronization to this device, as a multiple of the base poll interval. Valid selections for this parameter are:
The None selection will disable issuing a time sync to this device. This is the default selection.
The At Start Up Only selection will cause issuing a time synchronization at startup only.
The Interval selection will cause the RTU to issue a time synchronization at startup and then every Interval of the base poll interval seconds. Valid entries for Interval are between 1 and 32767 the base poll interval seconds. The default value is 60.
The Unsolicited Responses section is used in conjunction with the Enable
Unsolicited Responses on Start Up parameter on the Application Layer page. Certain non-SCADAPack slave devices are designed to start with their Enable Unsolicited Responses on Start Up parameter set to No.
Selecting Enabled for any class causes the master to (after it detects the slave come online) send a command allowing the slave to begin sending
Unsolicited Responses of that class.
With SCADAPack slaves the Enable Unsolicited Responses on Start Up parameter may be set to Yes, and the Accept Class parameters may be left at Disabled.
The Accept Class 1 selection displays the enable/disable status of unsolicited responses from the slave device for Class 1 events. The default selection is disabled.
The Accept Class 2 selection displays the enable/disable status of unsolicited responses from the slave device for Class 1 events. The default selection is disabled.
The Accept Class 3 selection displays the enable/disable status of unsolicited responses from the slave device for Class 1 events. The default selection is disabled.
The Save IIN Flags checkbox enables storing the IIN (Internal Indications) flags from the slave station in a Modbus database register. When this parameter is checked the IIN flags are saved to the entered Modbus register address. Valid entries are Modbus register addresses 30001 to 39999 and
40001 to 49999. The default value is 0.
The IIN flags are set by the slave to indicate the events in the following table. The events are bit mapped to the Modbus register. Bits except Device
Restarted and Time Synchronization required are cleared when the slave station receives any poll or read data command. The master will write to bits
5 and 11 depending on the local conditions in the master.
Realflo User and Reference Manual
May 19, 2011
1010
Poll Offset Example
DNP3 Protocol User Manual
Bit Description
0
1
2
3
4
5
6
7
8
9 last received message was a broadcast message
Class 1 data available
Class 2 data available
Class 3 data available
Time Synchronization required not used (returns 0)
Device trouble
Indicates memory allocation error in the slave, or
For master in mimic mode indicates communication failure with the slave device.
Device restarted (set on a power cycle)
Function Code not implemented
Requested object unknown or there were errors in the application data
10
11
Parameters out of range
Event buffer overflowed
Indicates event buffer overflow in the slave or master. The slave will set this bit if the event buffer in the slave is overflowed. The master will set this bit if the event buffer in the master has overflowed with events read from the slave. Check that the event buffer size, in the master and slave, is set to a value that will keep the buffer from overflowing and losing events. not used (returns 0) not used (returns 0)
12
13
14
15 not used (returns 0) not used (returns 0)
The OK button checks the data for this table entry. If the data is valid the dialog is closed. If the table data entered is invalid, an error message is displayed and the dialog remains open. The table entry is invalid if any of the fields is out of range. The data is also invalid if it conflicts with another entry in the table. Such conflict occurs when the station number is not unique.
The Cancel button closes the dialog without saving changes.
The Poll Offset parameter enhances the control over timing of master poll messages, by allowing master poll messages to be staggered.
For example, a master station may have 10 slaves to poll, and needs to poll them every hour. If these are included in the poll table without any poll offset, they will be polled in quick succession on the hour
– resulting in a large burst of communication activity once per hour. On some types of communications networks (particularly radio) it is desirable to distribute communication load more evenly, to minimize the chance of collisions and to avoid the possibility of consuming bandwidth continuously for an extended period of time.
The poll offset parameter enables you to distribute the communication load evenly. In the above example, it is possible to stagger the master polls so slave stations are polled at 6-minute intervals. To do this, set the base poll
Realflo User and Reference Manual
May 19, 2011
1011
DNP3 Protocol User Manual interval to 10 seconds, and for each slave station set the poll rate and poll offset parameters as follows:
Base Poll (seconds) Poll Rate (seconds)
10
10
10
10
10
10
10
10
10
10
360
360
360
360
360
360
360
360
360
360
Poll Offset (seconds)
0
36
72
108
144
180
216
252
288
324
Address Mapping
The Address Mapping property page is selected for editing by clicking
Address Mapping in the tree control section of the DNP Settings window.
This selection is only visible if the controller type is a SCADAPack
314/330/334, SCADAPack 350, SCADAPack 32 or SCADAPack 32P.
These controllers support DNP Master.
The Address Mapping contains a set of mapping rules, which will allow the
Remote DNP Objects to be mapped into local Modbus registers. This makes the data accessible locally, to be read and/or written locally in logic. It is also possible to perform data concentration
– to map the remote DNP Objects into the local DNP address space
– by defining local DNP objects and then mapping the remote DNP objects to the same Modbus registers. Change events can also be mapped in the same way - there is a configuration option to allow mapping of change events from a remote DNP slave into the local
DNP change event buffer. The table may have up to 1000 entries. A vertical scroll bar is used if the list exceeds the window size.
The Station column displays the address of the remote DNP station.
The Object Type column displays the DNP data object type.
Realflo User and Reference Manual
May 19, 2011
1012
DNP3 Protocol User Manual
The First Point column displays the starting address of the remote DNP data points.
The Number column displays the number of remote points to be mapped.
The First Register column displays the starting address of local Modbus register where the remote data points are to be mapped.
The Map Change Events combo box enables or disables mapping of change events from a remote DNP slave into the local DNP change event buffer. Mapped change events may trigger an Unsolicited message to be sent, after the Hold Count or Hold Time is reached. It may be desired instead to map only static (live) values into local Modbus registers .
The default selection is Disabled.
The default selection is Disabled.
The OK button saves the table data. No error checking is done on the table data.
The Cancel button closes the dialog without saving changes.
Select the Add button to enter a new row in the Address Mapping. Selecting the Add button opens the Add/Edit Address Mapping dialog.
Select the Edit button to modify the selected row in the Address Mapping.
Selecting the Edit button opens the Add/Edit Address Mapping dialog containing the data from the selected row. This button is disabled if more than one row is selected. This button is disabled if there are no entries in the table.
The Delete button removes the selected rows from the table. This button is disabled if there are no entries in the table.
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points need to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Click on the column headings to sort the data. Clicking once sorts the data in ascending order. Clicking again sorts the data in descending order.
Add/Edit Address Mapping Dialog
This dialog is used to edit an entry or add a new entry in the Address
Mapping.
The Station edit control displays the address of the remote DNP station.
Valid values for this field are from 0 to 65519.
Realflo User and Reference Manual
May 19, 2011
1013
Routing
DNP3 Protocol User Manual
The Object Type combo box displays the DNP data Object Type. The list of available types includes: Binary Input, Binary Output, 16-bit Analog Input,
32-bit Analog Input, Short Floating Point Analog Input, 16-bit Analog Output,
32-bit Analog Output, Short Floating Point Analog Output, 16-bit Counter
Input, 32-bit Counter Input. The Default selection is Binary Input.
The First Point edit control displays the starting address of the remote DNP data points. Valid values are from 0 to 65519.
The Number edit control displays the number of remote points to be mapped. Valid values for this field are from 1 to 9999.
The First Register edit control displays the starting address of local
Modbus register where the remote data points are to be mapped. Valid values depend on the selection of DNP Object Type and are as follows:
For Binary Inputs valid range is from 10001 to 14096.
For Binary Outputs valid range is from 00001 to 04096.
For Analog Inputs and Counter Inputs valid range is from 30001 to 39999.
For Analog Outputs valid range is from 40001 to 49999.
The OK button checks the data for this table entry. If the data is valid the dialog is closed. If the table data entered is invalid, an error message is displayed and the dialog remains open. The table entry is invalid if any of the fields is out of range. The data is also invalid if it conflicts with another entry in the table. Such conflict occurs when the combination of station number, object type, and object address is not unique.
The Cancel button closes the dialog without saving changes.
In a typical application the SCADAPack controller, configured for DNP, will act as a DNP slave station in a network. The SCADA system will communicate directly with the DNP slave stations in the SCADA system.
DNP routing is a method for routing, or forwarding, of messages received from the SCADA system, through the SCADAPack controller, to a remote
DNP slave station. The SCADAPack DNP slave station will respond to messages sent to it from the SCADA system, as well as broadcast messages. When it receives a message that is not sent to it the message is sent on the serial port defined in the routing table.
The advantage of this routing ability is that the SCADA system can communicate directly with the SCADAPack controller and the SCADAPack controller can handle the communication to remote DNP slave stations.
The DNP Routing table displays each routing translation as a row, with column headings, in the table. Entries may be added, edited or deleted using the button selections on the table. The table will hold a maximum of
128 entries.
The DNP Routing property page is selected for editing by clicking DNP
Routing in the tree control section of the DNP Settings window. When selected the DNP Routing property page is displayed.
Notes:
Routing needs to be enabled for the controller serial port in order to enable DNP routing.
Realflo User and Reference Manual
May 19, 2011
1014
DNP3 Protocol User Manual
Telepace version 2.63 cannot open files created with version 2.64, unless the Routing table is empty.
Telepace version 2.64 cannot open files created with version 2.65, unless the Routing table is empty.
The Station column displays the address of the remote DNP station.
The Port column displays the serial communications port, which should be used to communicate with this DNP station.
The Retries column displays the maximum number of Data Link retries, which should be used for this DNP station in the case of communication errors.
The Timeout column displays the maximum time (in milliseconds) to wait for a Data Link response before retrying the message.
The IP Address column displays the IP address of the remote DNP station.
The OK button saves the table data. No error checking is done on the table data.
The Cancel button closes the dialog without saving changes.
Select the Add button to enter a new row in the DNP Routing table.
Selecting the Add button opens the Add/Edit DNP Route dialog.
Select the Edit button to modify the selected row in the DNP Routing table.
Selecting the Edit button opens the Add/Edit DNP Route dialog containing the data from the selected row. This button is disabled if more than one row is selected. This button is disabled if there are no entries in the table.
The Delete button removes the selected rows from the table. This button is disabled if there are no entries in the table.
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points need to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Realflo User and Reference Manual
May 19, 2011
1015
DNP3 Protocol User Manual
Click on the column headings to sort the data. Clicking once sorts the data in ascending order. Clicking again sorts the data in descending order.
Add/Edit DNP Route Dialog
This dialog is used to edit an entry or add a new entry in the DNP Routing table.
The Station edit control displays the address of the remote DNP station.
Valid values for this field are from 0 to 65519.
The Port combo box displays the communications port, which should be used to communicate with the remote DNP station. This combo box contains list of the valid communications ports, which will depend on the type of controller. For SCADAPack 330/334, SCADAPack 350, SCADAPack
32 and SCADAPack 32P controllers the list will contain DNP in TCP and
DNP in UDP in addition to the serial port designations, COM1, COM2 etc.
The IP Address edit control is only enabled if the controller type is a
SCADAPack 330/334, SCADAPack 350, SCADAPack 32 or SCADAPack
32P. Enter the IP address of the remote DNP station.
The Data Link Retries edit control displays the maximum number of Data
Link retries which should be used for this DNP station in the case of communication errors. This field overrides the Data Link Retries field in the global DNP parameters set in the Data Link Layer configuration. Valid values for this field are 0 to 255.
The Data Link Timeout edit control displays the maximum time (in milliseconds) to wait for a Data Link response before retrying the message.
This field overrides the Data Link Timeout field in the global DNP parameters in the Data Link Layer configuration. Valid values for this field are 100 to 60000, in multiples of 100.
The phone number parameters allow automatic dialing for stations that use dial-up ports. The Phone Number parameters are enabled only when the
Port selected is a serial port.
The Primary Phone Number is the dialing string that will be used for the primary connection to the station. The controller will make 1 or more attempts, as configured in the Application layer, to connect using this number. If this connection does not work then the Secondary Phone
Number will be dialed, if it is entered.
Realflo User and Reference Manual
May 19, 2011
1016
DNP3 Protocol User Manual
Valid values are any ASCII string. The maximum length is 32 characters.
Leave this blank if you are not using a dial-up connection. The default value is blank. The serial port type needs to be set to RS-232 Modem for dial-up operation.
The Secondary Phone Number is the dialing string that will be used for the secondary connection to the station. The controller will make 1 or more attempts, as configured in the Application layer, to connect using this number. This number is used after the primary connection does not work.
Valid values are any ASCII string. The maximum length is 32 characters.
Leave this blank if you are not using a dial-up connection. The default value is blank. The serial port type needs to be set to RS-232 Modem for dial-up operation.
The OK button checks the data for this table entry. If the data is valid the dialog is closed. If the table data entered is invalid, an error message is displayed and the dialog remains open. The table entry is invalid if any of the fields is out of range. The data is also invalid if it conflicts with another entry in the table.
The Cancel button closes the dialog without saving changes.
Dynamic Routing
In addition to the configured routing table, there is an internal dynamic routing entry. This entry is not shown in the routing table. The dynamic routing entry listens to incoming messages and learns the address of the remote station and the communication port used for communicating with it.
If there is no entry in the routing table, the RTU will use the dynamic routing entry to respond to a message on the same communication port as the incoming message.
The dynamic routing entry is not cleared on initialization. This is deliberate for controllers that need to be remotely reconfigured. In this case the host can initialize the controller without losing the communications link.
Dynamic routing should not be used in a master station. Configure slave stations in the routing table.
Binary Inputs Configuration
The Binary Inputs property page is selected for editing by clicking Binary
Inputs in the tree control section of the DNP Settings window. When selected the Binary Inputs property page is active.
Realflo User and Reference Manual
May 19, 2011
1017
DNP3 Protocol User Manual
Binary Inputs parameters are set in this property page. Each parameter is described in the following paragraphs.
The Number of Points displays number of binary inputs reported by this
RTU. This value will increment with the addition of each configured Binary
Input point. The maximum number of points is 9999. The maximum number of actual points will depend on the memory available in the controller.
The Starting Address parameter specifies the starting DNP address of the first Binary Input point.
The Event Reporting Method selection specifies how binary input events are reported. A Change Of State event is an event object, without time, that is generated when the point changes state. Only one event is retained in the buffer for each point. If a subsequent event occurs for a point, the previous event object will be overwritten. The main purpose of this mode is to allow a master station to efficiently poll for changed data. A Log All Events is event object with absolute time will be generated when the point changes state. All events will be retained. The main purpose of this mode is to allow a master station to obtain a complete historical data log. The selections are:
Change of State
Log All Events
The Event Buffer Size parameter specifies the maximum number of binary input change events buffered by the RTU. The buffer holds binary input change events, regardless of the class to which they are assigned. If the buffer is completely full the RTU will lose the oldest events and retain the newest; the „Event Buffer Overflowed‟ IIN flag will also be set to indicate that the buffer has overflowed. The Event Buffer size should be at least equivalent to the number of binary inputs defined as Change of State type.
This will allow binary inputs to change simultaneously without losing any events. The value of this parameter depends on how often binary input change events occur and the rate at which the events are reported to the master station. The valid values for this parameter are 0 - 65535. Default value is 16.
Realflo User and Reference Manual
May 19, 2011
1018
DNP3 Protocol User Manual
SCADAPack 32, SCADAPack 32P, and SCADAPack 314, SCADAPack
330/334, SCADAPack 350/357 and SCADAPack controllers attempt to process DNP points every 100ms. If there are more DNP points than the controller can scan in 100ms the controller will respond by slowing the DNP scan rate. The DNP scan rate is backed off in multiples of 100ms until there is sufficient time to execute non-DNP functions (logic programs, C programs and communication). In the event the overload is transitory the DNP scan rate will return to the original scan rate of 100ms.
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points needs to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Adding Binary Inputs
Binary Inputs are added to the DNP configuration using the Binary Input property page. To add a Binary Input:
Select Binary Inputs in the tree control section of the DNP Settings window.
Click the Add button in the Binary Inputs property page.
The Binary Input property page is now displayed.
Edit the Binary Input parameters as required and then click the Add button.
As Binary Inputs are defined they are added as leaves to the Binary Inputs branch of the tree control. When Binary Inputs are defined the Binary Inputs branch will display a collapse / expand control to the left of the branch. Click this control to display defined Binary Inputs.
The Binary Input parameters are described in the following paragraphs.
The DNP Address window displays the DNP Binary Input address of the point. Each Binary Input is assigned a DNP address as they are defined.
Realflo User and Reference Manual
May 19, 2011
1019
DNP3 Protocol User Manual
The DNP point address starts at the value defined in the Binary Inputs configuration dialog and increments by one with each defined Input.
The Modbus Address parameter specifies the Modbus address of the
Binary Input assigned to the DNP Address. The SCADAPack and Micro16 controllers use Modbus addressing for digital inputs. Refer to the I/O
Database Registers section of the Telepace Ladder Logic Reference and
User Manual for complete information on digital input addressing in the
SCADAPack and Micro16 controllers. Valid Modbus addresses are:
00001 through 09999
10001 through 19999
The Class of Event Object parameter specifies the event object class the
Binary Input is assigned. The selections are:
None
Class 1
Class 2
Class 3
The Debounce parameter limits the frequency of change events. The input needs to remain in the same state for the debounce time for a change of state to be detected. The input is sampled every 0.1s. Changes shorter than the sample time cannot be detected. Valid values are 0 to 65535 tenths of seconds. The value 0 means no debounce. The default value is 0.
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points need to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Click the OK button to accept the Binary Input parameters and close the
DNP Settings dialog.
Click the Cancel button to close the dialog without saving any changes.
Click the Add button to add the current Binary Input to the DNP configuration.
Click the Copy button to copy the current Binary Input parameters to the next DNP Address.
Click the Delete button to delete the current Binary Input.
Click the Move Up button to move the current Binary Input up one position in the tree control branch.
Click the Move Down button to move the current Binary Input down one position in the tree control branch.
Binary Outputs Configuration
The Binary Outputs property page is selected for editing by clicking Binary
Outputs in the tree control section of the DNP Settings window. When selected the Binary Outputs property page is active.
Realflo User and Reference Manual
May 19, 2011
1020
DNP3 Protocol User Manual
Binary Outputs parameters are viewed in this property page.
The Number of Points displays the number of binary outputs reported by this RTU. This value will increment with the addition of each configured
Binary Output point. The maximum number of points is 9999. The maximum number of actual points will depend on the memory available in the controller.
The Starting Address parameter specifies the starting DNP address of the first Binary Output point.
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points need to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Adding Binary Outputs
Binary Outputs are added to the DNP configuration using the Binary Output property page. To add a Binary Output:
Select Binary Outputs in the tree control section of the DNP Settings window.
Click the Add button in the Binary Outputs property page.
The Binary Output property page is now displayed.
Edit the Binary Output parameters as required and then click the Add button.
As Binary Outputs are defined they are added as leaves to the Binary
Outputs branch of the tree control. When Binary Outputs are defined the
Binary Outputs branch will display a collapse / expand control to the left of the branch. Click this control to display defined Binary Outputs.
Realflo User and Reference Manual
May 19, 2011
1021
DNP3 Protocol User Manual
The Binary Output parameters are described in the following paragraphs.
The DNP Address window displays the DNP Binary Output address of the point. Each Binary Output is assigned a DNP address as they are defined.
The DNP point address starts at the value defined in the Binary Outputs dialog and increments by one with each defined Output.
The Modbus Address 1 parameter specifies the Modbus address of the
Binary Output assigned to the DNP Address. The SCADAPack and Micro16 controllers use Modbus addressing for digital outputs. Refer to the I/O
Database Registers section of the Telepace Ladder Logic Reference
Manual for complete information on digital output addressing in the
SCADAPack and Micro16 controllers. Valid Modbus addresses are:
00001 through 09999
The Modbus Address 2 parameter specifies the second Modbus address of the second Binary Output assigned to the DNP Address when the Paired control type is selected. This selection is not active when the control type is
Not Paired. Valid Modbus addresses are:
00001 through 09999
The Control Type parameter specifies whether the Binary Output is a paired control or not. If it is a paired control, i.e. trip/close output type, this means that the DNP address is associated to two physical control outputs and requires two Modbus addresses per DNP address. Control type selections are:
Paired
Not Paired
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points need to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Click the OK button to accept the Binary Output parameters and close the
DNP Settings dialog.
Realflo User and Reference Manual
May 19, 2011
1022
DNP3 Protocol User Manual
Click the Cancel button to close the dialog without saving any changes.
Click the Add button to add the current Binary Output to the DNP configuration.
Click the Copy button to copy the current Binary Output parameters to the next DNP Address.
Click the Delete button to delete the current Binary Output.
Click the Move Up button to move the current Binary Output up one position in the tree control branch.
Click the Move Down button to move the current Binary Output down one position in the tree control branch.
16
–Bit Analog Inputs Configuration
The 16-Bit Analog Inputs property page is selected for editing by clicking 16-
Bit Analog Inputs in the tree control section of the DNP Settings window.
When selected the 16-Bit Analog Inputs property page is active.
16-Bit Analog Inputs parameters are set in this property page. Each parameter is described in the following paragraphs.
The Number of Points displays the number of 16 bit analog inputs reported by the RTU. This value will increment with the addition of each configured
16-Bit Analog Input point. The maximum number of points is 9999. The maximum number of actual points will depend on the memory available in the controller.
The Starting Address parameter specifies the DNP address of the first 16bit Analog Input point.
The Event Reporting Method selection specifies how 16-bit Analog Input events are reported. A Change Of State event is an event object, without time, that is generated when the point changes state. Only one event is retained in the buffer for each point. If a subsequent event occurs for a point, the previous event object will be overwritten. The main purpose of this mode is to allow a master station to efficiently poll for changed data. A Log
All Events event object with absolute time will be generated when the point changes state. All events will be retained. The main purpose of this mode is
Realflo User and Reference Manual
May 19, 2011
1023
DNP3 Protocol User Manual to allow a master station to obtain a complete historical data log. The selections are:
Change of State
Log All Events
The Event Buffer Size parameter specifies the maximum number of 16-Bit
Analog Input change events buffered by the RTU. The buffer holds 16-Bit
Analog Input events, regardless of the class to which they are assigned. If the buffer is completely full the RTU will lose the oldest events and retain the newest; the „Event Buffer Overflowed‟ IIN flag will also be set to indicate that the buffer has overflowed. The Event Buffer size should be at least equivalent to the number of 16-Bit Analog Inputs defined as Change of State type. That will allow 16-Bit Analog Inputs to exceed the deadband simultaneously without losing any events. The value of this parameter is dependent on how often 16-Bit Analog Input events occur and the rate at which the events are reported to the master station. The valid values for this parameter are 0 - 65535. Default value is 16.
For SCADAPack 32 and SCADAPack 32P controllers analog input events are processed by the DNP driver at a rate of 100 events every 100 ms. If more than 100 analog input events need to be processed they are processed sequentially in blocks of 100 until all events are processed. This allows the processing of 1000 analog input events per second.
SCADAPack 32, SCADAPack 32P, and SCADAPack 314, SCADAPack
330/334, SCADAPack 350/357 and SCADAPack controllers attempt to process DNP points every 100ms. If there are more DNP points than the controller can scan in 100ms the controller will respond by slowing the DNP scan rate. The DNP scan rate is backed off in multiples of 100ms until there is sufficient time to execute non-DNP functions (logic programs, C programs and communication). In the event the overload is transitory the DNP scan rate will return to the original scan rate of 100ms.
For SCADAPack controllers, SCADAPack 100, SCADAPack LP,
SCADAPack and Micro16 controllers analog input events are processed by the DNP driver at a rate of 20 events every 100 ms. If more than 20 analog input events need to be processed they are processed sequentially in blocks of 20 until all events are processed. This allows the processing of 200 analog input events per second.
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points need to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Adding 16-Bit Analog Inputs
16-Bit Analog Inputs are added to the DNP configuration using the 16-Bit
Analog Input property page. To add a 16-Bit Analog Input:
Select 16-Bit Analog Inputs in the tree control section of the DNP
Settings window.
Click the Add button in the 16-Bit Analog Inputs property page.
The 16-Bit Analog Input property page is now displayed.
Edit the 16-Bit Analog Input parameters as required and then click the
Add button.
Realflo User and Reference Manual
May 19, 2011
1024
DNP3 Protocol User Manual
As 16-Bit Analog Inputs are defined they are added as leaves to the 16-Bit
Analog Inputs branch of the tree control. When 16-Bit Analog Inputs are defined the 16-Bit Analog Inputs branch will display a collapse / expand control to the left of the branch. Click this control to display defined 16-Bit
Analog Inputs.
The 16-Bit Analog Input parameters are described in the following paragraphs.
The DNP Address window displays the DNP 16-Bit Analog Input address of the point. Each 16-Bit Analog Input is assigned a DNP address as they are defined. The DNP point address starts at the value set in the 16-bit Analog
Input configuration dialog and increments by one with each defined 16-Bit
Analog Input.
The Modbus Address parameter specifies the Modbus address of the 16-
Bit Analog Input assigned to the DNP Address. The SCADAPack and
Micro16 controllers use Modbus addressing for analog inputs. Refer to the
I/O Database Registers section of the Telepace Ladder Logic Reference
and User Manual for complete information on analog input addressing in the SCADAPack and Micro16 controllers. Valid Modbus addresses are:
30001 through 39999
40001 through 49999
The Class of Event Object parameter specifies the event object class assigned to the 16-Bit Analog Input is assigned. If Unsolicited reporting is not required for a point, it is recommended to set its Class to None. Data points automatically become members of Class 0 or None (static data).
The selections are:
None
Class 1
Class 2
Class 3
Realflo User and Reference Manual
May 19, 2011
1025
DNP3 Protocol User Manual
The Deadband parameter specifies whether the RTU generates events.
The value entered is the minimum number of counts that the 16-Bit Analog
Input needs to change in order to generate an event. Valid deadband values are 0 to 65535. A deadband value of 0 will cause any change to create an event.
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points need to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Click the OK button to accept the 16-Bit Analog Input parameters and close the DNP Settings dialog.
Click the Cancel button to close the dialog without saving any changes.
Click the Add button to add the current 16-Bit Analog Input to the DNP configuration.
Click the Copy button to copy the current 16-Bit Analog Input parameters to the next DNP Address.
Click the Delete button to delete the current 16-Bit Analog Input.
Click the Move Up button to move the current 16-Bit Analog Input up one position in the tree control branch.
Click the Move Down button to move the current 16-Bit Analog Input down one position in the tree control branch.
32-Bit Analog Inputs Configuration
The 32-Bit Analog Inputs property page is selected for editing by clicking 32-
Bit Analog Inputs in the tree control section of the DNP Settings window.
When selected the 32-Bit Analog Inputs property page is active.
32-Bit Analog Inputs parameters are set in this property page. Each parameter is described in the following paragraphs.
The Number of Points displays the number of 32- bit analog inputs reported by the RTU. This value will increment with the addition of each configured 32-Bit Analog Input point. The maximum number of points is
Realflo User and Reference Manual
May 19, 2011
1026
DNP3 Protocol User Manual
9999. The maximum number of actual points will depend on the memory available in the controller.
The Starting Address parameter specifies the DNP address of the first 32bit Analog Input point.
The Event Reporting Method selection specifies how 32-bit Analog Input events are reported. A Change Of State event is an event object, without time, that is generated when the point changes state. Only one event is retained in the buffer for each point. If a subsequent event occurs for a point, the previous event object will be overwritten. The main purpose of this mode is to allow a master station to efficiently poll for changed data. A Log
All Events is event object with absolute time will be generated when the point changes state. All events will be retained. The main purpose of this mode is to allow a master station to obtain a complete historical data log.
The selections are:
Change of State
Log All Events
The Event Buffer Size parameter specifies the maximum number of 32-Bit
Analog Input change events buffered by the RTU. The buffer holds 32-Bit
Analog Input events, regardless of the class to which they are assigned. If the buffer is completely full the RTU will lose the oldest events and retain the newest; the „Event Buffer Overflowed‟ IIN flag will also be set to indicate that the buffer has overflowed. The Event Buffer size should be at least equivalent to the number of 32-Bit Analog Inputs defined as Change of State type. That will allow 32-Bit Analog Inputs to exceed the deadband simultaneously without losing any events. The value of this parameter is dependent on how often 32-Bit Analog Input events occur and the rate at which the events are reported to the master station. The valid values for this parameter are 0 - 65535. Default value is 16.
For SCADAPack 32 and SCADAPack 32P controllers analog input events are processed by the DNP driver at a rate of 100 events every 100 ms. If more than 100 analog input events need to be processed they are processed sequentially in blocks of 100 until all events are processed. This allows the processing of 1000 analog input events per second.
SCADAPack 32, SCADAPack 32P, and SCADAPack 314, SCADAPack
330/334, SCADAPack 350/357 and SCADAPack controllers attempt to process DNP points every 100ms. If there are more DNP points than the controller can scan in 100ms the controller will respond by slowing the DNP scan rate. The DNP scan rate is backed off in multiples of 100ms until there is sufficient time to execute non-DNP functions (logic programs, C programs and communication). In the event the overload is transitory the DNP scan rate will return to the original scan rate of 100ms.
For SCADAPack controllers, SCADAPack 100, SCADAPack LP,
SCADAPack and Micro16 controllers analog input events are processed by the DNP driver at a rate of 20 events every 100 ms. If more than 20 analog input events need to be processed they are processed sequentially in blocks of 20 until all events are processed. This allows the processing of 200 analog input events per second.
The Word Order selection specifies the word order of the 32-bit value. The selections are:
Telepace Least Significant Word in first register.
Realflo User and Reference Manual
May 19, 2011
1027
DNP3 Protocol User Manual
ISaGRAF Most Significant Word in first register.
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points need to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Adding 32-Bit Analog Inputs
32-Bit Analog Inputs are added to the DNP configuration using the 16-Bit
Analog Input property page. To add a 32-Bit Analog Input:
Select 32-Bit Analog Inputs in the tree control section of the DNP
Settings window.
Click the Add button in the 32-Bit Analog Inputs property page.
The 32-Bit Analog Input property page is now displayed.
Edit the 32-Bit Analog Input parameters as required and then click the
Add button.
As 32-Bit Analog Inputs are defined they are added as leaves to the 32-Bit
Analog Inputs branch of the tree control. When 32-Bit Analog Inputs are defined the 32-Bit Analog Inputs branch will display a collapse / expand control to the left of the branch. Click this control to display defined 32-Bit
Analog Inputs.
The 32-Bit Analog Input parameters are described in the following paragraphs.
The DNP Address window displays the DNP 32-Bit Analog Input address of the point. Each 32-Bit Analog Input is assigned a DNP address as they are defined. The DNP point address starts at the value set in the 32-bit Analog
Input configuration dialog and increments by one with each defined 32-Bit
Analog Input.
The Modbus Address parameter specifies the Modbus addresses of the
32-Bit Analog Input assigned to the DNP Address. 32-Bit Analog Inputs use two consecutive Modbus registers for each assigned DNP Address, the address that is entered in this box and the next consecutive Modbus
Realflo User and Reference Manual
May 19, 2011
1028
DNP3 Protocol User Manual register. The SCADAPack and Micro16 controllers use Modbus addressing for analog inputs. Refer to the I/O Database Registers section of the
Telepace Ladder Logic Reference and User Manual for complete information on analog input addressing in the SCADAPack and Micro16 controllers. Valid Modbus addresses are:
30001 through 39998
40001 through 49998
The Class of Event Object parameter specifies the event object class the
32-Bit Analog Input is assigned. If Unsolicited reporting is not required for a
DNP point, it is recommended to set its Class 0 or None. Data points automatically become members of Class 0 or None (static data).The selections are:
None
Class 1
Class 2
Class 3
The Deadband parameter specifies whether the RTU generates events.
The value entered is the minimum number of counts that the 32-Bit Analog
Input needs to change in order to generate an event. Valid deadband values are 0 to 4,294,967,295. A deadband value of 0 will cause any change to create an event.
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points need to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Click the OK button to accept the 32-Bit Analog Input parameters and close the DNP Settings dialog.
Click the Cancel button to close the dialog without saving any changes.
Click the Add button to add the current 32-Bit Analog Input to the DNP configuration.
Click the Copy button to copy the current 32-Bit Analog Input parameters to the next DNP Address.
Click the Delete button to delete the current 32-Bit Analog Input.
Click the Move Up button to move the current 32-Bit Analog Input up one position in the tree control branch.
Click the Move Down button to move the current 32-Bit Analog Input down one position in the tree control branch.
Short Floating Point Analog Inputs
The Short Floating Point Analog Inputs property page is selected for editing by clicking Short Floating Point Analog Inputs in the tree control section of the DNP Settings window. When selected the Short Floating Point Analog
Inputs property page is active.
Realflo User and Reference Manual
May 19, 2011
1029
DNP3 Protocol User Manual
Short Floating Point Analog Input parameters are set in this property page.
Each parameter is described in the following paragraphs.
The Number of Points displays the number of Short Floating Point Analog
Inputs reported by the RTU. This value will increment with the addition of each configured Short Floating Point Analog Input point. The maximum number of points is 9999. The maximum number of actual points will depend on the memory available in the controller.
The Starting Address parameter specifies the DNP address of the first
Short Floating Point Analog Input point.
The Event Reporting Method selection specifies how Short Floating Point
Analog Input events are reported. A Change Of State event is an event object, without time, that is generated when the point changes state. Only one event is retained in the buffer for each point. If a subsequent event occurs for a point, the previous event object will be overwritten. The main purpose of this mode is to allow a master station to efficiently poll for changed data. A Log All Events is event object with absolute time will be generated when the point changes state. All events will be retained. The main purpose of this mode is to allow a master station to obtain a complete historical data log. The selections are:
Change of State
Log All Events
The Event Buffer Size parameter specifies the maximum number of Short
Floating Point Analog Input change events buffered by the RTU. The buffer holds Short Floating Point analog input events, regardless of the class to which they are assigned. If the buffer is completely full the RTU will lose the oldest events and retain the newest; the „Event Buffer Overflowed‟ IIN flag will also be set to indicate that the buffer has overflowed. The Event Buffer size should be at least equivalent to the number of Short Floating point analog inputs defined as Change of State type. That will allow Short Floating
Analog Point Inputs to exceed the deadband simultaneously without losing any events. The value of this parameter is dependent on how often Short
Floating Point Analog Input events occur and the rate at which the events
Realflo User and Reference Manual
May 19, 2011
1030
DNP3 Protocol User Manual are reported to the master station. The valid values for this parameter are 0
- 65535. Default value is 16.
For SCADAPack 32 and SCADAPack 32P controllers analog input events are processed by the DNP driver at a rate of 100 events every 100 ms. If more than 100 analog input events need to be processed they are processed sequentially in blocks of 100 until all events are processed. This allows the processing of 1000 analog input events per second.
SCADAPack 32, SCADAPack 32P, and SCADAPack 314, SCADAPack
330/334, SCADAPack 350/357 and SCADAPack controllers attempt to process all DNP points every 100ms. If there are more DNP points than the controller can scan in 100ms the controller will respond by slowing the DNP scan rate. The DNP scan rate is backed off in multiples of 100ms until there is sufficient time to execute non-DNP functions (logic programs, C programs and communication). In the event the overload is transitory the DNP scan rate will return to the original scan rate of 100ms.
For SCADAPack controllers, SCADAPack 100, SCADAPack LP,
SCADAPack and Micro16 controllers analog input events are processed by the DNP driver at a rate of 20 events every 100 ms. If more than 20 analog input events need to be processed they are processed sequentially in blocks of 20 until all events are processed. This allows the processing of 200 analog input events per second.
The Word Order selection specifies the word order of the 32-bit value. The selections are:
Telepace / ISaGRAF (MSW First) Most Significant Word in first register.
Reverse (LSW First) first register.
Least Significant Word in
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points need to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Adding Short Floating Point Analog Inputs
Short Floating Point Analog Inputs are added to the DNP configuration using the 16-Bit Analog Input property page. To add a Short Floating Point Analog
Input:
Select Short Floating Point Analog Input in the tree control section of the DNP Settings window.
Click the Add button in the Short Floating Point Analog Inputs property page.
The Short Floating Point Analog Input property page is now displayed.
Edit the Short Floating Point Analog Input parameters as required and then click the Add button.
As Short Floating Point Analog Inputs are defined they are added as leaves to the Short Floating Point Analog Inputs branch of the tree control. When
Short Floating Point Analog Inputs are defined the Short Floating Point
Analog Inputs branch will display a collapse / expand control to the left of
Realflo User and Reference Manual
May 19, 2011
1031
DNP3 Protocol User Manual the branch. Click this control to display defined Short Floating Point Analog
Inputs.
The Short Floating Point Analog Input parameters are described in the following paragraphs.
The DNP Address window displays the DNP Short Floating Point Analog
Input address of the point. Each Short Floating Point Analog Input is assigned a DNP address as they are defined. The DNP point address starts at the value set in the Short Floating Point Analog Input configuration dialog and increments by one with each defined Short Floating Point Analog Input.
The Modbus Address parameter specifies the Modbus addresses of the
Short Floating Point Analog Input assigned to the DNP Address. Short
Floating Point Analog Inputs use two consecutive Modbus registers for each assigned DNP Address, the address that is entered in this box and the next consecutive Modbus register. The SCADAPack and Micro16 controllers use
Modbus addressing for analog inputs. Refer to the I/O Database Registers section of the Telepace Ladder Logic Reference and User Manual for complete information on analog input addressing in the SCADAPack and
Micro16 controllers. Valid Modbus addresses are:
30001 through 39998
40001 through 49998
The Class of Event Object parameter specifies the event object class the
Short Floating Point Analog Input is assigned. If Unsolicited reporting is not required for a DNP point, it is recommended to set its Class 0 or None. The selections are:
None
Class 1
Class 2
Class 3
Realflo User and Reference Manual
May 19, 2011
1032
DNP3 Protocol User Manual
The Deadband parameter specifies whether the RTU generates events.
The value entered is the minimum number of counts that the Short Floating
Point Analog Input needs to change in order to generate an event. A deadband value of 0 will cause any change to create an event.
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points need to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Click the OK button to accept the Short Floating Point Analog Input parameters and close the DNP Settings dialog.
Click the Cancel button to close the dialog without saving any changes.
Click the Add button to add the current Short Floating Point Analog Input to the DNP configuration.
Click the Copy button to copy the current Short Floating Point Analog Input parameters to the next DNP Address.
Click the Delete button to delete the current Short Floating Point Analog
Input.
Click the Move Up button to move the current Short Floating Point Analog
Input up one position in the tree control branch.
Click the Move Down button to move the current Short Floating Point
Analog Input down one position in the tree control branch.
16-Bit Analog Outputs Configuration
The 16-Bit Analog Outputs property page is selected for editing by clicking
16-Bit Analog Outputs in the tree control section of the DNP Settings window. When selected the 16-Bit Analog Outputs property page is active.
16-Bit Analog Outputs parameters are viewed in this property page.
The Number of Points displays the number of 16-Bit Analog Outputs reported by this RTU. This value will increment with the addition of each configured 16-Bit Analog Input point. The maximum number of points is
Realflo User and Reference Manual
May 19, 2011
1033
DNP3 Protocol User Manual
9999. The maximum number of actual points will depend on the memory available in the controller.
The Starting Address parameter specifies the DNP address of the first 16bit Analog Output point.
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points need to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Adding 16-Bit Analog Outputs
16-Bit Analog Outputs are added to the DNP configuration using the 16-Bit
Analog Outputs property page. To add a 16-Bit Analog Output:
Select 16-Bit Analog Outputs in the tree control section of the DNP
Settings window.
Click the Add button in the 16-Bit Analog Outputs property page.
The 16-Bit Analog Output property page is now displayed.
Edit the 16-Bit Analog Outputs parameters as required and then click the Add button.
As 16-Bit Analog Outputs are defined they are added as leaves to the 16-Bit
Analog Output branch of the tree control. When 16-Bit Analog Outputs are defined the 16-Bit Analog Outputs branch will display a collapse / expand control to the left of the branch. Click this control to display defined 16-Bit
Analog Outputs.
The 16-Bit Analog Outputs parameters are described in the following paragraphs.
The DNP Address window displays the DNP 16-Bit Analog Output address of the point. Each 16-Bit Analog Output is assigned a DNP address as they are defined. The DNP point address starts at the value set in the 16-bit
Analog Output configuration dialog and increments by one with each defined
16-Bit Analog Output.
Realflo User and Reference Manual
May 19, 2011
1034
DNP3 Protocol User Manual
The Modbus Address parameter specifies the Modbus address of the 16-
Bit Analog Output assigned to the DNP Address. The SCADAPack and
Micro16 controllers use Modbus addressing for analog outputs. Refer to the
I/O Database Registers section of the Telepace Ladder Logic Reference
and User Manual for complete information on analog output addressing in the SCADAPack and Micro16 controllers. Valid Modbus addresses are:
40001 through 49999
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points need to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Click the OK button to accept the 16-Bit Analog Output parameters and close the DNP Settings dialog.
Click the Cancel button to close the dialog without saving any changes.
Click the Add button to add the current 16-Bit Analog Output to the DNP configuration.
Click the Copy button to copy the current 16-Bit Analog Output parameters to the next DNP Address.
Click the Delete button to delete the current 16-Bit Analog Output.
Click the Move Up button to move the current 16-Bit Analog Output up one position in the tree control branch.
Click the Move Down button to move the current 16-Bit Analog Output down one position in the tree control branch.
32-Bit Analog Outputs Configuration
The 32-Bit Analog Outputs property page is selected for editing by clicking
32-Bit Analog Outputs in the tree control section of the DNP Settings window. When selected the 32-Bit Analog Outputs property page is active.
32-Bit Analog Outputs parameters are viewed in this property page.
The Number of Points displays the number of 32-Bit Analog Outputs reported by this RTU. This value will increment with the addition of each
Realflo User and Reference Manual
May 19, 2011
1035
DNP3 Protocol User Manual configured 32-Bit Analog Output point. The maximum number of points is
9999. The maximum number of actual points will depend on the memory available in the controller.
The Starting Address parameter specifies the DNP address of the first 16bit Analog Output point.
The Word Order selection specifies the word order of the 32-bit value. The selections are:
Telepace Least Significant Word in first register.
ISaGRAF Most Significant Word in first register.
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points need to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Adding 32-Bit Analog Outputs
32-Bit Analog Outputs are added to the DNP configuration using the 32-Bit
Analog Outputs property page. To add a 32-Bit Analog Output:
Select 32-Bit Analog Outputs in the tree control section of the DNP
Settings window.
Click the Add button in the 16-Bit Analog Outputs property page.
The 32-Bit Analog Output property page is now displayed.
Edit the 32-Bit Analog Outputs parameters as required and then click the Add button.
As 32-Bit Analog Outputs are defined they are added as leaves to the
Binary Inputs branch of the tree control. When 32-Bit Analog Outputs are defined the 32-Bit Analog Outputs branch will display a collapse / expand control to the left of the branch. Click this control to display defined 32-Bit
Analog Outputs.
The 32-Bit Analog Outputs parameters are described in the following paragraphs.
Realflo User and Reference Manual
May 19, 2011
1036
DNP3 Protocol User Manual
The DNP Address window displays the DNP 32-Bit Analog Output address of the point. Each 16-Bit Analog Output is assigned a DNP address s they are defined. The DNP point address starts at the value set in the 32-bit
Analog Output configuration dialog and increments by one with each defined
32-Bit Analog Output.
The Modbus Address parameter specifies the Modbus address of the 32-
Bit Analog Output assigned to the DNP Address. 32-Bit Analog Outputs use two consecutive Modbus registers for each assigned DNP Address, the address that is entered in this box and the next consecutive Modbus register. The SCADAPack and Micro16 controllers use Modbus addressing for analog outputs. Refer to the I/O Database Registers section of the
Telepace Ladder Logic Reference and User Manual for complete information on analog output addressing in the SCADAPack and Micro16 controllers. Valid Modbus addresses are:
40001 through 49998
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points need to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Click the OK button to accept the 16-Bit Analog Output parameters and close the DNP Settings dialog.
Click the Cancel button to close the dialog without saving any changes.
Click the Add button to add the current 32-Bit Analog Output to the DNP configuration.
Click the Copy button to copy the current 32-Bit Analog Output parameters to the next DNP Address.
Click the Delete button to delete the current 32-Bit Analog Output.
Click the Move Up button to move the current 32-Bit Analog Output up one position in the tree control branch.
Click the Move Down button to move the current 32-Bit Analog Output down one position in the tree control branch.
Short Floating Point Analog Outputs
The Short Floating Point Analog Outputs property page is selected for editing by clicking Short Floating Point Analog Outputs in the tree control section of the DNP Settings window. When selected the Short Floating Point
Analog Outputs property page is active.
Realflo User and Reference Manual
May 19, 2011
1037
DNP3 Protocol User Manual
Short Floating Point Analog Output parameters are set in this property page.
Each parameter is described in the following paragraphs.
The Number of Points displays the number of Short Floating Point Analog
Outputs reported by the RTU. This value will increment with the addition of each configured Short Floating Point Analog Input point. The maximum number of points is 9999. The maximum number of actual points will depend on the memory available in the controller.
The Starting Address parameter specifies the DNP address of the first
Short Floating Point Analog Output point.
The Word Order selection specifies the word order of the 32-bit value. The selections are:
Telepace / ISaGRAF (MSW First) Most Significant Word in first register.
Reverse (LSW First) first register.
Least Significant Word in
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points need to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Adding Short Floating Point Analog Outputs
Short Floating Point Analog Outputs are added to the DNP configuration using the Short Floating Point Analog Output property page. To add a Short
Floating Point Analog Output:
Select Short Floating Point Analog Output in the tree control section of the DNP Settings window.
Click the Add button in the Short Floating Point Analog Inputs property page.
The Short Floating Point Analog Output property page is now displayed.
Edit the Short Floating Point Analog Output parameters as required and then click the Add button.
Realflo User and Reference Manual
May 19, 2011
1038
DNP3 Protocol User Manual
As Short Floating Point Analog Outputs are defined they are added as leaves to the Short Floating Point Analog Outputs branch of the tree control.
When Short Floating Point Analog Outputs are defined the Short Floating
Point Analog Outputs branch will display a collapse / expand control to the left of the branch. Click this control to display defined Short Floating Point
Analog Outputs.
The Short Floating Point Analog Output parameters are described in the following paragraphs.
The DNP Address window displays the DNP Short Floating Point Analog
Output address of the point. Each Short Floating Point Analog Output is assigned a DNP address as they are defined. The DNP point address starts at the value set in the Short Floating Point Analog Output configuration dialog and increments by one with each defined Short Floating Point Analog
Output.
The Modbus Address parameter specifies the Modbus addresses of the
Short Floating Point Analog Output assigned to the DNP Address. Short
Floating Point Analog Outputs use two consecutive Modbus registers for each assigned DNP Address, the address that is entered in this box and the next consecutive Modbus register. The SCADAPack and Micro16 controllers use Modbus addressing for analog inputs. Refer to the I/O Database
Registers section of the Telepace Ladder Logic Reference and User
Manual for complete information on analog input addressing in the
SCADAPack and Micro16 controllers. Valid Modbus addresses are:
30001 through 39998
40001 through 49998
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points need to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Click the OK button to accept the Short Floating Point Analog Input parameters and close the DNP Settings dialog.
Click the Cancel button to close the dialog without saving any changes.
Realflo User and Reference Manual
May 19, 2011
1039
DNP3 Protocol User Manual
Click the Add button to add the current Short Floating Point Analog Input to the DNP configuration.
Click the Copy button to copy the current Short Floating Point Analog Input parameters to the next DNP Address.
Click the Delete button to delete the current Short Floating Point Analog
Input.
Click the Move Up button to move the current Short Floating Point Analog
Input up one position in the tree control branch.
Click the Move Down button to move the current Short Floating Point
Analog Input down one position in the tree control branch.
16
–Bit Counter Inputs Configuration
The 16-Bit Counter Inputs property page is selected for editing by clicking
16-Bit Counter Inputs in the tree control section of the DNP Settings window. When selected the 16-Bit Counter Inputs property page is active.
16-Bit Counter Inputs parameters are set in this property page. Each parameter is described in the following paragraphs.
The Number of Points displays the number of 16-Bit Counter Inputs reported by the RTU. This value will increment with the addition of each configured 16-Bit Counter Inputs point. The maximum number of points is
9999. The maximum number of actual points will depend on the memory available in the controller.
The Starting Address parameter specifies the DNP address of the first 16-
Bit Counter Input point.
The Event Reporting Method selection specifies how 16-Bit Counter Input events are reported. A Change Of State event is an event object, without time, that is generated when the point changes state. Only one event is retained in the buffer for each point. If a subsequent event occurs for a point, the previous event object will be overwritten. The main purpose of this mode is to allow a master station to efficiently poll for changed data. A Log
All Events is event object with absolute time will be generated when the point changes state. All events will be retained. The main purpose of this mode is to allow a master station to obtain a complete historical data log.
The selections are:
Realflo User and Reference Manual
May 19, 2011
1040
DNP3 Protocol User Manual
Change of State
Log All Events
The Event Buffer Size parameter specifies the maximum number of 16-Bit
Counter Input change without time events buffered by the RTU. The buffer holds 16-Bit Counter Input events, regardless of the class to which they are assigned. If the buffer fills to 90 percent the RTU will send a buffer overflow event to the master station. If the buffer is completely full the RTU will lose the oldest events and retain the newest. The Event Buffer size should be at least equivalent to the number of 16-Bit Analog Inputs defined as Change of
State type. That will allow all 16-Bit Counter Inputs to exceed the threshold simultaneously without losing any events. The value of this parameter is dependent on how often 16-Bit Counter Input events occur and the rate at which the events are reported to the master station. The valid values for this parameter are 0 - 65535. Default value is 16.
For SCADAPack 32 and SCADAPack 32P controllers counter input events are processed by the DNP driver at a rate of 100 events every 100 ms. If more than 100 counter input events need to be processed they are processed sequentially in blocks of 100 until all events are processed. This allows the processing of 1000 counter input events per second.
SCADAPack 32, SCADAPack 32P, and SCADAPack 314, SCADAPack
330/334, SCADAPack 350/357 and SCADAPack controllers attempt to process all DNP points every 100ms. If there are more DNP points than the controller can scan in 100ms the controller will respond by slowing the DNP scan rate. The DNP scan rate is backed off in multiples of 100ms until there is sufficient time to execute non-DNP functions (logic programs, C programs and communication). In the event the overload is transitory the DNP scan rate will return to the original scan rate of 100ms.
For SCADAPack controllers, SCADAPack 100, SCADAPack LP,
SCADAPack and Micro16 controllers counter input events are processed by the DNP driver at a rate of 20 events every 100 ms. If more than 20 counter input events need to be processed they are processed sequentially in blocks of 20 until all events are processed. This allows the processing of 200 counter input events per second.
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points need to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Adding 16-Bit Counter Inputs
16-Bit Counter Inputs are added to the DNP configuration using the 16-Bit
Counter Inputs property page. To add a 16-Bit Counter Input:
Select 16-Bit Counter Inputs in the tree control section of the DNP
Settings window.
Click the Add button in the 16-Bit Counter Inputs property page.
The 16-Bit Counter Input property page is now displayed.
Edit the 16-Bit Counter Inputs parameters as required and then click the
Add button.
As 16-Bit Counter Inputs are defined they are added as leaves to the 16-Bit
Counter Inputs branch of the tree control. When 16-Bit Counter Inputs are defined the 16-Bit Counter Inputs branch will display a collapse / expand
Realflo User and Reference Manual
May 19, 2011
1041
DNP3 Protocol User Manual control to the left of the branch. Click this control to display defined 16-Bit
Counter Inputs.
The 16-Bit Counter Input parameters are described in the following paragraphs.
The DNP Address window displays the DNP 16-Bit Counter Input address of the point. Each 16-Bit Counter Input is assigned a DNP address s they are defined. The DNP point address starts at the value set in the 16-Bit
Counter Input configuration dialog and increments by one with each defined
16-Bit Counter Input.
The Modbus Address parameter specifies the Modbus address of the 16-
Bit Counter Input assigned to the DNP Address. The SCADAPack and
Micro16 controllers use Modbus addressing for counter inputs. Refer to the
I/O Database Registers section of the Telepace Ladder Logic Reference
and User Manual for complete information on analog input addressing in the SCADAPack and Micro16 controllers. Valid Modbus addresses are:
30001 through 39999
40001 through 49999
The Class of Event Object parameter specifies the event object class the
16-Bit Counter Input is assigned.
If Unsolicited reporting is not required for a DNP point, it is recommended to set its Class 0 or None
. The selections are:
None
Class 1
Class 2
Class 3
The Threshold parameter specifies whether the RTU generates events.
The value entered is the minimum number of counts that the 16-Bit Counter
Input needs to change since it was last reported. Setting this value to zero disables generating events for the 16-Bit Counter Input point. Valid deadband values are 0 to 65535.
Realflo User and Reference Manual
May 19, 2011
1042
DNP3 Protocol User Manual
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points need to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Click the OK button to accept the 16-Bit Analog Counter parameters and close the DNP Settings dialog.
Click the Cancel button to close the dialog without saving any changes.
Click the Add button to add the current 16-Bit Analog Input to the DNP configuration.
Click the Copy button to copy the current 16-Bit Analog Input parameters to the next DNP Address.
Click the Delete button to delete the current 16-Bit Analog Input.
Click the Move Up button to move the current 16-Bit Analog Input up one position in the tree control branch.
Click the Move Down button to move the current 16-Bit Analog Input down one position in the tree control branch.
32-Bit Counter Inputs Configuration
The 32-Bit Counter Inputs property page is selected for editing by clicking
32-Bit Counter Inputs in the tree control section of the DNP Settings window. When selected the 32-Bit Counter Inputs property page is active.
32-Bit Counter Inputs parameters are set in this property page. Each parameter is described in the following paragraphs.
The Number of Points displays the number of 32-Bit Counter Inputs reported by the RTU. This value will increment with the addition of each configured 32-Bit Counter Inputs point. The maximum number of points is
9999. The maximum number of actual points will depend on the memory available in the controller.
The Starting Address parameter specifies the DNP address of the first 32-
Bit Counter Input point.
Realflo User and Reference Manual
May 19, 2011
1043
DNP3 Protocol User Manual
The Event Reporting Method selection specifies how 32-Bit Counter Input events are reported. A Change Of State event is an event object, without time, that is generated when the point changes state. Only one event is retained in the buffer for each point. If a subsequent event occurs for a point, the previous event object will be overwritten. The main purpose of this mode is to allow a master station to efficiently poll for changed data. A Log
All Events is event object with absolute time will be generated when the point changes state. All events will be retained. The main purpose of this mode is to allow a master station to obtain a complete historical data log.
The selections are:
Change of State
Log All Events
The Event Buffer Size parameter specifies the maximum number of 32-Bit
Counter Input change events buffered by the RTU. The buffer holds all 32-
Bt Counter Input events, regardless of the class to which they are assigned.
If the buffer is completely full the RTU will lose the oldest events and retain the newest; the „Event Buffer Overflowed‟ IIN flag will also be set to indicate that the buffer has overflowed. The Event Buffer size should be at least equivalent to the number of 32-Bit Counter Inputs defined as Change of
State type. That will allow all 32-Bit Counter Inputs to exceed the deadband simultaneously without losing any events. The value of this parameter is dependent on how often 32-Bit Counter Input events occur and the rate at which the events are reported to the master station. The valid values for this parameter are 0 - 65535. Default value is 16.
For SCADAPack 32 and SCADAPack 32P controllers counter input events are processed by the DNP driver at a rate of 100 events every 100 ms. If more than 100 counter input events need to be processed they are processed sequentially in blocks of 100 until all events are processed. This allows the processing of 1000 counter input events per second.
SCADAPack 32, SCADAPack 32P, and SCADAPack 314, SCADAPack
330/334, SCADAPack 350/357 and SCADAPack controllers attempt to process all DNP points every 100ms. If there are more DNP points than the controller can scan in 100ms the controller will respond by slowing the DNP scan rate. The DNP scan rate is backed off in multiples of 100ms until there is sufficient time to execute non-DNP functions (logic programs, C programs and communication). In the event the overload is transitory the DNP scan rate will return to the original scan rate of 100ms.
For SCADAPack controllers, SCADAPack 100, SCADAPack LP,
SCADAPack and Micro16 controllers counter input events are processed by the DNP driver at a rate of 20 events every 100 ms. If more than 20 counter input events need to be processed they are processed sequentially in blocks of 20 until all events are processed. This allows the processing of 200 counter input events per second.
The Word Order selection specifies the word order of the 32-bit value. The selections are:
Telepace Least Significant Word in first register.
ISaGRAF Most Significant Word in first register.
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points need to
Realflo User and Reference Manual
May 19, 2011
1044
DNP3 Protocol User Manual be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Adding 32-Bit Counter Inputs
32-Bit Counter Inputs are added to the DNP configuration using the 16-Bit
Counter Input property page. To add a 32-Bit Analog Input:
Select 32-Bit Counter Inputs in the tree control section of the DNP
Settings window.
Click the Add button in the 32-Bit Counter Inputs property page.
The 32-Bit Counter Input property page is now displayed.
Edit the 32-Bit Counter Input parameters as required and then click the
Add button.
As 32-Bit Counter Inputs are defined they are added as leaves to the 32-Bit
Counter Inputs branch of the tree control. When 32-Bit Counter Inputs are defined the 32-Bit Counter Inputs branch will display a collapse / expand control to the left of the branch. Click this control to display defined 32-Bit
Counter Inputs.
The 32-Bit Counter Input parameters are described in the following paragraphs.
The DNP Address window displays the DNP 32-Bit Counter Input address of the point. Each 32-Bit Counter Input is assigned a DNP address as they are defined. The DNP point address starts at the value set in the 32-Bit
Counter Input configuration dialog and increments by one with each defined
32-Bit Counter Input.
The Modbus Address parameter specifies the Modbus addresses of the
32-Bit Counter Input assigned to the DNP Address. 32-Bit Counter Inputs use two consecutive Modbus registers for each assigned DNP Address, the address that is entered in this box and the next consecutive Modbus register. The SCADAPack and Micro16 controllers use Modbus addressing for counter inputs. Refer to the I/O Database Registers section of the
Telepace Ladder Logic Reference and User Manual for complete
Realflo User and Reference Manual
May 19, 2011
1045
DNP Diagnostics
DNP3 Protocol User Manual information on analog input addressing in the SCADAPack and Micro16 controllers. Valid Modbus addresses are:
30001 through 39998
40001 through 49998
The Class of Event Object parameter specifies the event object class the
32-Bit Counter Input is assigned.
If Unsolicited reporting is not required for a DNP point, it is recommended to set its Class 0 or None
. The selections are:
None
Class 1
Class 2
Class 3
The Threshold parameter specifies whether the RTU generates events.
The value entered is the minimum number of counts that the 32-Bit Counter
Input needs to change since it was last reported. Setting this value to zero disables generating events for the 32-Bit Counter Input point. Valid threshold values are 0 to 4,294,967,295.
The Allow Duplicate Modbus Addresses checkbox determines if the
Modbus I/O database addresses assigned to the DNP data points need to be unique. Check this box if you want to allow more than one point to use the same Modbus address.
Click the OK button to accept the parameters and close the DNP Settings dialog. In PEMEX mode the OK button is not active if the user is not logged on with Administrator privileges.
Click the Cancel button to close the dialog without saving any changes.
Click the Add button to add the current 32-Bit Counter Input to the DNP configuration.
Click the Copy button to copy the current 32-Bit Counter Input parameters to the next DNP Address.
Click the Delete button to delete the current 32-Bit Counter Input.
Click the Move Up button to move the current 32-Bit Counter Input up one position in the tree control branch.
Click the Move Down button to move the current 32-Bit Counter Input down one position in the tree control branch.
DNP Diagnostics provide Master station and Outstation DNP diagnostics.
The diagnostics provide detailed information on the status of DNP communication and DNP data points.
DNP diagnostics are available for local DNP information using the DNP
Status command.
For Telepace applications select Controller >> DNP Status from the menu bar.
For ISaGRAF applications select Tools >> Controller >> DNP Status from the program window menu bar.
Realflo User and Reference Manual
May 19, 2011
1046
DNP3 Protocol User Manual
SCADAPack 32 controllers support DNP master operations. DNP diagnostics are available for master stations using the DNP Master Status command.
For Telepace applications select Controller >> DNP Master Status
from the menu bar. See section
for information on DNP Master Status
diagnostics.
For ISaGRAF applications select Tools >> Controller >> DNP Master
Status from the program window menu bar.
DNP Diagnostics require firmware version 2.20 or newer for SCADAPack controllers and firmware version 1.50 or newer for SCADAPack 32 controllers. When an attempt is made to select the DNP Status or DNP
Master Status command for controllers with firmware that does not support the commands an error message is displayed. An example of the error message is shown below.
DNP Status
To enable the use of DNP diagnostics you will need to upgrade the firmware in the controller to the newer version.
When the DNP Status command is selected the DNP Status dialog is displayed. This dialog shows the run-time DNP diagnostics and current data values for the local DNP points.
The DNP Status dialog has a number of selectable tabs and opens with the
Overview tab selected. The following tabs are displayed.
Overview
Binary In (binary inputs information)
Binary Out (binary outputs information)
AIN-16 (16-bit analog inputs information)
AIN-32 (32-bit analog inputs information)
AIN-Float (short float analog inputs information)
AOUT-16 (16-bit analog outputs information)
AOUT-32 (32-bit analog outputs information)
AOUT-Float (short float analog outputs information)
Counter-16 (16-bit counter inputs information)
Counter-32 (32-bit counter inputs information)
Clicking on any tab opens the tab and displays the selected information.
Realflo User and Reference Manual
May 19, 2011
1047
Overview Tab
DNP3 Protocol User Manual
The Overview Tab displays the run-time diagnostics for the local DNP station. The Overview display is divided into five areas of diagnostic information: DNP Status, Internal Indications, Communication Statistics,
Last Message and Event Buffer. Each of these is explained in the following paragraphs.
The DNP Status window provides information on the status of the DNP protocol running in the controller. Depending on the status the window may contain the following text.
Enabled or Disabled indicates whether the controller firmware supports
DNP protocol.
Configured or Not Configured indicates whether the controller has been configured with DNP protocol on at least one communications port.
Running or Not Running indicates whether the DNP tasks are running in the controller.
The Internal Indications window displays the current state of the DNP internal indications (IIN) flags in the controller. Bits 0
– 7 (the first octet) are displayed on the left, then bits 8 - 15 (second octet) on the right.
The Communication Statistics window displays the message statistics for each DNP communication port. The statistics include the total number of messages transmitted and received and the total number of successes, failures, and failures since last success (which will only be updated for messages sent by this controller) for each communication port. The counters increment whenever a new DNP message is sent or received on the port, and roll over after 65535 messages.
Click the Reset button to reset the counters to zero.
The Last Message window displays information about the recent DNP message. The information is updated each time a new message is received or transmitted. The Last Message window contains the following information.
Direction displays whether the message was received or transmitted.
Realflo User and Reference Manual
May 19, 2011
1048
Point Status Tabs
DNP3 Protocol User Manual
Time displays the time at which the message was received or sent.
Port displays which communication port was used for the message.
Source displays the source DNP station address for the message.
Dest displays the destination DNP station address for the message.
Length displays the message length in bytes.
Link Func displays the Link Layer function code.
Appl Func displays the Application Layer function code.
IIN displays the Internal indications received with the last message
The Event Buffers window displays the number of events in each type of event buffer and the allocated buffer size. The event buffers displayed are:
Binary In (binary inputs)
AIN-16 (16-bit analog inputs)
AIN-32 (32-bit analog inputs)
AIN-Float (floating point analog inputs)
Counter-16 (16-bit counter inputs)
Counter-32 (32-bit counter inputs)
Class 1 (class 1 events)
Class 2 (class 2 events)
Class 3 (class 3 events)
The point status tabs display the state of each point of the selected type in the controller. The following tabs are displayed.
Binary In (binary inputs information)
Binary Out (binary outputs information)
AIN-16 (16-bit analog inputs information)
AIN-32 (32-bit analog inputs information)
AIN-Float (short float analog inputs information)
AOUT-16 (16-bit analog outputs information)
AOUT-32 (32-bit analog outputs information)
AOUT-Float (short float analog outputs information)
Counter-16 (16-bit counter inputs information)
Counter-32 (32-bit counter inputs information)
Each of the tabs displays information in the same format. The example below shows the appearance of the binary input page.
Realflo User and Reference Manual
May 19, 2011
1049
DNP3 Protocol User Manual
The DNP Address column shows the DNP address of the point.
The Modbus Address column shows the Modbus register address of the point.
The Value column shows the value of the point. Binary points are shown as
OFF or ON. Numeric points show the numeric value of the point.
DNP Master Status
When the DNP Master Status command is selected the DNP Master Status dialog is displayed. This dialog shows the run-time DNP diagnostics and status of the DNP outstations and current data values for the DNP points in these outstations.
The DNP Master Status dialog has a number of selectable tabs and opens with the All Stations tab selected. The following tabs are displayed.
All Stations
Remote Overview
Binary In (binary inputs information)
Binary Out (binary outputs information)
AIN-16 (16-bit analog inputs information)
AIN-32 (32-bit analog inputs information)
AIN-Float (short float analog inputs information)
AOUT-16 (16-bit analog outputs information)
AOUT-32 (32-bit analog outputs information)
AOUT-Float (short float analog outputs information)
Counter-16 (16-bit counter inputs information)
Counter-32 (32-bit counter inputs information)
Realflo User and Reference Manual
May 19, 2011
1050
All Stations Tab
DNP3 Protocol User Manual
The All Stations tab displays the run-time communications diagnostics for all outstations polled by the master or outstations reporting unsolicited data to the master.
The Communication Statistics window displays a list of all outstations and the communication statistics for each station in the list. The statistics counters increment whenever a new DNP message is sent or received, and roll over after 65535 messages. The following statistics are displayed.
DNP Address displays the DNP address of the outstation.
Successes display the number of successful message transactions between this master and the corresponding remote station. This number includes master polls to the remote station and unsolicited responses from the outstation.
Fails displays the number of failed message transactions between this master and the corresponding remote station. This counter increments by 1 for a failed message transaction irrespective of the number of application layer retries.
FailsNew displays the number failed message transactions between this master and the corresponding remote station since the last successful poll.
Msgs Rx displays the number of DNP packets (frames) received from the outstation station. This number includes frames containing unsolicited responses from the outstation.
Last Rx Msg Time displays the time the last DNP packet (frame) was received from the outstation.
Msgs Tx displays the number of DNP packets (frames) sent to the outstation.
Last Tx Msg Time displays the time the last DNP packet (frame) was sent to the outstation.
The Msgs Tx and Msgs Rx counters could be greater than or equal to the
Successes and Fails counters.
Realflo User and Reference Manual
May 19, 2011
1051
DNP3 Protocol User Manual
Remote Overview Tab
The Remote Overview tab displays the run-time diagnostics and current data values for a selected remote station. The data shown is from the image of the data in the master station.
The Remote Station window is where the DNP address of the remote station is entered. When the Remote station field is changed data fields on this tab and the following I/O tabs are updated with the values for the newly selected Remote Station.
The Internal Indications window displays the current state of the DNP internal indications (IIN) flags for the selected remote station.
The Communication Statistics window displays communication statistics for the remote station selected. The statistics counters increment whenever a new DNP message is sent or received, and roll over after 65535 messages. The following statistics are displayed.
Successes displays the number of successful messages received in response to master polls sent to the station. This number includes unsolicited responses from the outstation.
Fails displays the number of failed or no responses to master polls sent to the outstation.
FailsNew displays the number failed or no responses to master polls sent to the outstation since the last successful poll.
Msgs Rx displays the number of messages received from the outstation station. This number includes unsolicited responses from the outstation.
Last Rx Msg Time displays the time the last message was received from the outstation.
Msgs Tx displays the number of messages sent to the outstation station.
Last Tx Msg Time displays the time the last message was sent to the outstation.
Click Reset to reset the counters to zero.
Event Buffers shows the number of events in each type of event buffer and the allocated buffer size. The buffers shown are for binary inputs, 16-bit
Realflo User and Reference Manual
May 19, 2011
1052
DNP3 Protocol User Manual analog inputs, 32-bit analog inputs, Floating point analog inputs, 16-bit counter inputs, and 32-bit counter inputs, and Class 1, 2, and 3 events.
The Event Buffers window displays the number of events in each type of event buffer and the allocated buffer size for the selected remote station.
The event buffers displayed are:
Binary In (binary inputs)
AIN-16 (16-bit analog inputs)
AIN-32 (32-bit analog inputs)
AIN-Float (floating point analog inputs)
Counter-16 (16-bit counter inputs)
Counter-32 (32-bit counter inputs)
Class 1 (class 1 events)
Class 2 (class 2 events)
Class 3 (class 3 events)
Due to a limitation of the DNP3 protocol, an Unsolicited message from an outstation is not capable of including information stating which data class generated the message. As a result, Unsolicited events when received by the master will be counted as Class 1 events. Events which are polled by the master, however, do contain class information and will be counted in the
Event Buffer for the appropriate class.
Remote Point Status Tabs
The point status tabs show the state of each point of the selected type in the remote station selected on the Remote Overview tab. The values shown are from the image of the remote station in the master station.
Class 0 polling of an outstation needs to be enabled in the master in order to allow that outstation‟s DNP points to be listed on these tabs. This is the only way for the master to retrieve a complete list of points in an outstation.
The example below shows the appearance of the Binary In tab.
The DNP Address column shows the DNP address of the point.
Realflo User and Reference Manual
May 19, 2011
1053
DNP3 Protocol User Manual
The Modbus Address column shows the Modbus register address of the point. This is only relevant for points that have an address mapping in the master station. For points that have an address mapping, this will show the
Modbus register address of the point. For points not having an address mapping, this will show „---„.
The Value column shows the value of the point. Binary points are shows as
OFF or ON. Numeric points show the numeric value of the point.
Realflo User and Reference Manual
May 19, 2011
1054
DNP3 Protocol User Manual
DNP Master Device Profile Document
DNP v3.00
DEVICE PROFILE DOCUMENT
Vendor Name: Control Microsystems Inc.
Device Name: SCADAPack controllers
Highest DNP Level Supported:
For Requests 2
For Responses 2
Device Function:
Master Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels
Supported (the complete list is described in the attached table):
Function code 14 (warm restart)
Function code 20 (Enable Unsolicited Messages) for class 1, 2, 3 objects only.
Function code 21 (Disable Unsolicited Messages) for class 1, 2, 3 objects only.
Object 41, variation 1 (32-bit analog output block)
Realflo User and Reference Manual
May 19, 2011
1055
DNP3 Protocol User Manual
Maximum Data Link Frame Size (octets):
Transmitted 292
Received (must be 292)
Maximum Data Link Re-tries:
None
Fixed at
Configurable, range 0 to 255
Requires Data Link Layer Confirmation:
Never
Always
Sometimes
If 'Sometimes', when?
Configurable for Always or Never
Requires Application Layer Confirmation:
Never
Always (not recommended)
Maximum Application Fragment Size (octets):
Transmitted
Received
2048
2048
Maximum Application Layer Re-tries:
None
Configurable, range 0 to 255
Realflo User and Reference Manual
May 19, 2011
1056
DNP3 Protocol User Manual
When reporting Event Data (Slave devices only)
When sending multi-fragment responses (Slave devices only)
Sometimes
If 'Sometimes', when?
______________________________________________
Configurable for always or only when Reporting Event Data and Unsolicited Messages
Timeouts while waiting for:
Data Link Confirm
Complete Appl. Fragment
Application Confirm
None Fixed at _________ Variable
None Fixed at _________ Variable
None Fixed at _________ Variable
None Fixed at _________ Variable
Configurable
Configurable
Configurable
Configurable
Complete Appl. Response
Others __________________________________________________________________________
Sends/Executes Control Operations:
WRITE Binary Outputs
SELECT/OPERATE
DIRECT OPERATE
Never
Never
Never
DIRECT OPERATE - NO ACK Never
Count > 1
Pulse On
Pulse Off
Latch On
Latch Off
Never
Never
Never
Never
Never
Queue
Clear Queue
Never
Never
Always
Always
Always
Always
Always
Always
Always
Always
Always
Always
Always
Sometimes
Sometimes
Sometimes
Sometimes
Sometimes
Sometimes
Sometimes
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
Sometimes Configurable
Sometimes Configurable
Configurable
Sometimes Configurable
Sometimes Configurable
Realflo User and Reference Manual
May 19, 2011
1057
DNP3 Protocol User Manual
FILL OUT THE FOLLOWING ITEM FOR MASTER DEVICES ONLY:
Expects Binary Input Change Events:
Either time-tagged or non-time-tagged for a single event
Both time-tagged and non-time-tagged for a single event
Configurable (attach explanation)
FILL OUT THE FOLLOWING ITEMS FOR SLAVE DEVICES ONLY:
Reports Binary Input Change Events when no specific variation requested:
Never
Only time-tagged
Only non-time-tagged
Configurable to send both, one or the other (attach explanation)
Reports time-tagged Binary Input Change Events when no specific variation requested:
Never
Binary Input Change With Time
Binary Input Change With Relative Time
Configurable (attach explanation)
Sends Unsolicited Responses:
Never
Configurable by class
Only certain objects
Sometimes (attach explanation)
ENABLE/DISABLE UNSOLICITED
Default Counter Object/Variation:
No Counters Reported
Configurable (attach explanation)
Sends Static Data in Unsolicited Responses:
Never
When Device Restarts
When Status Flags Change
No other options are permitted.
Counters Roll Over at:
No Counters Reported
Configurable (attach explanation)
Realflo User and Reference Manual
May 19, 2011
1058
Default Object 20
Default Variation 05
Point-by-point list attached
Sends Multi-Fragment Responses:
Yes No
DNP3 Protocol User Manual
16 Bits
32 Bits
16 Bits for 16-bit counters
32 Bits for 32-bit counters
Point-by-point list attached
Realflo User and Reference Manual
May 19, 2011
1059
DNP3 Protocol User Manual
2
3
0
1
2
0
1
1
1
2
2
2
2
10
10
10
12
0
1
2
0
1
DNP V3.00
DEVICE PROFILE DOCUMENT
IMPLEMENTATION OBJECT
This table describes the objects, function codes and qualifiers used in the device:
Obj Var
OBJECT
Description
Binary Input - All Variations
Binary Input
Binary Input with Status
Binary Input Change - All Variations
Binary Input Change without Time 1
1
1
REQUEST
(slave must parse)
Func
Codes
(dec)
Qual
Codes
(hex)
06
06,07,08
06,07,08
Binary Input Change with Time
Binary Input Change with Relative Time
Binary Output - All Variations
Binary Output
Binary Output Status
Control Block - All Variations
1
1
1
06
06,07,08
06,07,08
129, 130
129, 130
129, 130
RESPONSE
(master must parse)
Func
Codes
Qual
Codes
(hex)
129, 130
129, 130
129, 130
00, 01
00, 01
17, 28
17, 28
17, 28
00, 01
Realflo User and Reference Manual
May 19, 2011
1060
DNP3 Protocol User Manual
20
20
20
20
20
20
20
20
1
2
3
4
5
6
7
8
DNP V3.00
DEVICE PROFILE DOCUMENT
IMPLEMENTATION OBJECT
This table describes the objects, function codes and qualifiers used in the device:
Obj
12
12
12
20
Var
1
2
3
0
OBJECT
Description
Control Relay Output Block
Pattern Control Block
Pattern Mask
Binary Counter - All Variations
32-Bit Binary Counter
16-Bit Binary Counter
32-Bit Delta Counter
16-Bit Delta Counter
32-Bit Binary Counter without Flag
16-Bit Binary Counter without Flag
32-Bit Delta Counter without Flag
16-Bit Delta Counter without Flag
1, 7, 8,
9, 10
REQUEST
(slave must parse)
Func
Codes
(dec)
Qual
Codes
(hex)
3, 4, 5,
6
17, 28
06
RESPONSE
(master must parse)
Func
Codes
Qual
Codes
(hex)
129 echo of request
129, 130
129, 130
129, 130
129, 130
00, 01
00, 01
00, 01
00, 01
Realflo User and Reference Manual
May 19, 2011
1061
DNP3 Protocol User Manual
Obj
21
21
21
21
21
21
21
21
DNP V3.00
DEVICE PROFILE DOCUMENT
IMPLEMENTATION OBJECT
This table describes the objects, function codes and qualifiers used in the device:
21
21
21
21
Var
0
1
2
3
4
5
6
7
8
9
10
11
OBJECT
Description
Frozen Counter - All Variations
32-Bit Frozen Counter
16-Bit Frozen Counter
32-Bit Frozen Delta Counter
16-Bit Frozen Delta Counter
32-Bit Frozen Counter with Time of Freeze
16-Bit Frozen Counter with Time of Freeze
32-Bit Frozen Delta Counter with Time of
Freeze
16-Bit Frozen Delta Counter with Time of
Freeze
32-Bit Frozen Counter without Flag
16-Bit Frozen Counter without Flag
32-Bit Frozen Delta Counter without Flag
1
REQUEST
(slave must parse)
Func
Codes
(dec)
Qual
Codes
(hex)
06
RESPONSE
(master must parse)
Func
Codes
Qual
Codes
(hex)
129, 130
129, 130
00, 01
00, 01
129, 130
129, 130
00, 01
00, 01
Realflo User and Reference Manual
May 19, 2011
1062
DNP3 Protocol User Manual
21
22
22
22
22
22
22
22
22
22
23
23
5
6
7
8
0
1
DNP V3.00
DEVICE PROFILE DOCUMENT
IMPLEMENTATION OBJECT
This table describes the objects, function codes and qualifiers used in the device:
Obj Var
12
0
1
2
3
4
OBJECT
Description
16-Bit Frozen Delta Counter without Flag
Counter Change Event - All Variations
32-Bit Counter Change Event without Time
16-Bit Counter Change Event without Time
32-Bit Delta Counter Change Event without
Time
16-Bit Delta Counter Change Event without
Time
32-Bit Counter Change Event with Time
16-Bit Counter Change Event with Time
32-Bit Delta Counter Change Event with Time
16-Bit Delta Counter Change Event with Time
Frozen Counter Event - All Variations
32-Bit Frozen Counter Event without Time
1
REQUEST
(slave must parse)
Func
Codes
(dec)
Qual
Codes
(hex)
06,07,08
RESPONSE
(master must parse)
Func
Codes
Qual
Codes
(hex)
129, 130
129, 130
17, 28
17, 28
Realflo User and Reference Manual
May 19, 2011
1063
DNP3 Protocol User Manual
23
23
23
23
23
23
23
30
30
30
30
30
30
2
3
4
5
6
7
8
0
1
2
3
4
5
DNP V3.00
DEVICE PROFILE DOCUMENT
IMPLEMENTATION OBJECT
This table describes the objects, function codes and qualifiers used in the device:
Obj Var
OBJECT
Description
16-Bit Frozen Counter Event without Time
32-Bit Frozen Delta Counter Event without Time
16-Bit Frozen Delta Counter Event without Time
32-Bit Frozen Counter Event with Time
16-Bit Frozen Counter Event with Time
32-Bit Frozen Delta Counter Event with Time
16-Bit Frozen Delta Counter Event with Time
Analog Input - All Variations
32-Bit Analog Input
16-Bit Analog Input
32-Bit Analog Input without Flag
16-Bit Analog Input without Flag
Short Floating Point Analog Input
1
REQUEST
(slave must parse)
Func
Codes
(dec)
Qual
Codes
(hex)
06
RESPONSE
(master must parse)
Func
Codes
Qual
Codes
(hex)
129, 130
129, 130
129, 130
129, 130
129, 130
00, 01
00, 01
00, 01
00, 01
00, 01
Realflo User and Reference Manual
May 19, 2011
1064
DNP3 Protocol User Manual
31
31
31
31
31
31
31
32
32
32
32
32
0
1
2
3
4
5
6
0
1
2
3
4
DNP V3.00
DEVICE PROFILE DOCUMENT
IMPLEMENTATION OBJECT
This table describes the objects, function codes and qualifiers used in the device:
Obj Var
OBJECT
Description
Frozen Analog Input - All Variations
32-Bit Frozen Analog Input
16-Bit Frozen Analog Input
32-Bit Frozen Analog Input with Time of Freeze
16-Bit Frozen Analog Input with Time of Freeze
32-Bit Frozen Analog Input without Flag
16-Bit Frozen Analog Input without Flag
Analog Change Event - All Variations
32-Bit Analog Change Event without Time
16-Bit Analog Change Event without Time
32-Bit Analog Change Event with Time
16-Bit Analog Change Event with Time
1
REQUEST
(slave must parse)
Func
Codes
(dec)
Qual
Codes
(hex)
06,07,08
RESPONSE
(master must parse)
Func
Codes
Qual
Codes
(hex)
129,130
129,130
129,130
129,130
17,28
17,28
17,28
17,28
Realflo User and Reference Manual
May 19, 2011
1065
DNP3 Protocol User Manual
33
33
33
33
33
40
40
40
40
41
41
DNP V3.00
DEVICE PROFILE DOCUMENT
IMPLEMENTATION OBJECT
This table describes the objects, function codes and qualifiers used in the device:
Obj
32
Var
5
0
1
2
3
4
0
1
2
3
0
1
OBJECT
Description
Short Floating Point Analog Change Event without Time
Frozen Analog Event - All Variations
32-Bit Frozen Analog Event without Time
16-Bit Frozen Analog Event without Time
32-Bit Frozen Analog Event with Time
16-Bit Frozen Analog Event with Time
Analog Output Status - All Variations
32-Bit Analog Output Status
16-Bit Analog Output Status
Short Floating Point Analog Output Status
Analog Output Block - All Variations
32-Bit Analog Output Block
1
3, 4, 5,
6
REQUEST
(slave must parse)
Func
Codes
(dec)
Qual
Codes
(hex)
06
17, 28
129, 130
129
129, 130
129, 130
RESPONSE
(master must parse)
Func
Codes
Qual
Codes
(hex)
129,130 17,28
00, 01
00, 01
00, 01 echo of request
Realflo User and Reference Manual
May 19, 2011
1066
DNP3 Protocol User Manual
52
52
50
50
50
51
51
DNP V3.00
DEVICE PROFILE DOCUMENT
IMPLEMENTATION OBJECT
This table describes the objects, function codes and qualifiers used in the device:
Obj
41
41
Var
2
3
0
1
2
0
1
OBJECT
Description
16-Bit Analog Output Block
Short Floating Point Analog Output Block
Time and Date - All Variations
Time and Date
Time and Date with Interval
Time and Date CTO - All Variations
Time and Date CTO
3, 4, 5,
6
3, 4, 5,
6
2 (see
4.14)
REQUEST
(slave must parse)
Func
Codes
(dec)
Qual
Codes
(hex)
17, 28
17, 28
07 where quantity = 1
129, 130
RESPONSE
(master must parse)
Func
Codes
Qual
Codes
(hex)
129
129 echo of request echo of request
51
52
2
0
1
2
Unsynchronized Time and Date CTO
Time Delay - All Variations
Time Delay Coarse
Time Delay Fine
129, 130
129
129
07, quantity=1
07, quantity=1
07, quantity=1
07, quantity=1
Realflo User and Reference Manual
May 19, 2011
1067
DNP3 Protocol User Manual
Obj
60
60
70
80
60
60
60
81
82
83
83
DNP V3.00
DEVICE PROFILE DOCUMENT
IMPLEMENTATION OBJECT
This table describes the objects, function codes and qualifiers used in the device:
Var
1
1
1
2
0
1
2
3
4
1
1
OBJECT
Class 0 Data
Class 1 Data
Class 2 Data
Class 3 Data
Description
File Identifier
Internal Indications
Storage Object
Device Profile
Private Registration Object
Private Registration Object Descriptor
1
2
1
20,21
1
20,21
1
20,21
REQUEST
(slave must parse)
Func
Codes
(dec)
Qual
Codes
(hex)
00 index=7
06
06,07,08
06
06,07,08
06
06,07,08
06
RESPONSE
(master must parse)
Func
Codes
Qual
Codes
(hex)
Realflo User and Reference Manual
May 19, 2011
1068
DNP3 Protocol User Manual
1
1
2
3
1
2
3
Obj
101
101
101
90
100
100
100
DNP V3.00
DEVICE PROFILE DOCUMENT
IMPLEMENTATION OBJECT
This table describes the objects, function codes and qualifiers used in the device:
Var
OBJECT
Description
Application Identifier
Short Floating Point
Long Floating Point
Extended Floating Point
Small Packed Binary-Coded Decimal
Medium Packed Binary-Coded Decimal
Large Packed Binary-Coded Decimal
No Object
No Object
No Object
REQUEST
(slave must parse)
Func
Codes
(dec)
Qual
Codes
(hex)
14
23
(see
4.14)
13
RESPONSE
(master must parse)
Func
Codes
Qual
Codes
(hex)
Realflo User and Reference Manual
May 19, 2011
1069
DNP3 Protocol User Manual
DNP V3.00
TIME SYNCHRONISATION PARAMETERS
This table describes the worst-case time parameters relating to time synchronization, as required by DNP Level 2 Certification Procedure section 8.7
PARAMETER
VALUE
Time base drift +/- 1 minute/month at 25°C
+1 / -3 minutes/month 0 to 50°C
Time base drift over a 10-minute interval +/- 14 milliseconds at 25°C
+14 / -42 milliseconds 0 to 50°C
Maximum delay measurement error +/- 100 milliseconds
Maximum internal time reference error when set from the protocol
+/- 100 milliseconds
Maximum response time 100 milliseconds
Realflo User and Reference Manual
May 19, 2011
1070
DNP3 Protocol User Manual
DNP Slave Device Profile Document
DNP v3.00
DEVICE PROFILE DOCUMENT
Vendor Name: Control Microsystems Inc.
Device Name: SCADAPack controllers
Highest DNP Level Supported:
For Requests 2
For Responses 2
Device Function:
Master
Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels
Supported (the complete list is described in the attached table):
Function code 14 (warm restart)
Function code 20 (Enable Unsolicited Messages) for class 1, 2, 3 objects only.
Function code 21 (Disable Unsolicited Messages) for class 1, 2, 3 objects only.
Object 41, variation 1 (32-bit analog output block)
Realflo User and Reference Manual
May 19, 2011
1071
DNP3 Protocol User Manual
Maximum Data Link Frame Size (octets):
Transmitted 292
Received (must be 292)
Maximum Data Link Re-tries:
None
Fixed at
Configurable, range 0 to 255
Requires Data Link Layer Confirmation:
Never
Always
Sometimes
If 'Sometimes', when?
Configurable for Always or Never
Maximum Application Fragment Size (octets):
Transmitted
Received
2048
2048
Maximum Application Layer Re-tries:
None
Configurable, range 0 to 255
Requires Application Layer Confirmation:
Never
Always (not recommended)
When reporting Event Data (Slave devices only)
When sending multi-fragment responses (Slave devices only)
Sometimes
If 'Sometimes', when?
______________________________________________
Configurable for always or only when Reporting Event Data and Unsolicited Messages
Realflo User and Reference Manual
May 19, 2011
1072
DNP3 Protocol User Manual
Timeouts while waiting for:
Data Link Confirm
Configurable
None Fixed at _________ Variable
Complete Appl. Fragment
Application Confirm
None Fixed at _________ Variable
None Fixed at _________ Variable
None Fixed at _________ Variable
Configurable
Configurable
Configurable
Complete Appl. Response
Others __________________________________________________________________________
Sends/Executes Control Operations:
WRITE Binary Outputs
SELECT/OPERATE
DIRECT OPERATE
Never
Never
Never
DIRECT OPERATE - NO ACK Never
Count > 1
Pulse On
Pulse Off
Latch On
Latch Off
Never
Never
Never
Never
Never
Queue
Clear Queue
Never
Never
Always
Always
Always
Always
Always
Always
Always
Always
Always
Always
Always
Sometimes
Configurable
Sometimes
Configurable
Sometimes
Sometimes
Sometimes
Sometimes
Sometimes
Sometimes
Sometimes
Sometimes Configurable
Sometimes Configurable
FILL OUT THE FOLLOWING ITEM FOR MASTER DEVICES ONLY:
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
Expects Binary Input Change Events:
Either time-tagged or non-time-tagged for a single event
Both time-tagged and non-time-tagged for a single event
Realflo User and Reference Manual
May 19, 2011
1073
DNP3 Protocol User Manual
Configurable (attach explanation)
FILL OUT THE FOLLOWING ITEMS FOR SLAVE DEVICES ONLY:
Reports Binary Input Change Events when no specific variation requested:
Never
Only time-tagged
Only non-time-tagged
Configurable to send both, one or the other (attach explanation)
Reports time-tagged Binary Input Change Events when no specific variation requested:
Never
Binary Input Change With Time
Binary Input Change With Relative Time
Configurable (attach explanation)
Sends Unsolicited Responses:
Never
Configurable by class
Only certain objects
Sometimes (attach explanation)
ENABLE/DISABLE UNSOLICITED
Default Counter Object/Variation:
No Counters Reported
Configurable (attach explanation)
Default Object 20
Default Variation 05
Point-by-point list attached
Sends Static Data in Unsolicited Responses:
Never
When Device Restarts
When Status Flags Change
No other options are permitted.
Counters Roll Over at:
No Counters Reported
Configurable (attach explanation)
16 Bits
32 Bits
16 Bits for 16-bit counters
32 Bits for 32-bit counters
Point-by-point list attached
Sends Multi-Fragment Responses:
Yes No
Realflo User and Reference Manual
May 19, 2011
1074
DNP3 Protocol User Manual
Realflo User and Reference Manual
May 19, 2011
1075
DNP3 Protocol User Manual
2
3
0
1
2
0
1
1
1
2
2
2
2
10
10
10
12
0
1
2
0
1
DNP V3.00
DEVICE PROFILE DOCUMENT
IMPLEMENTATION OBJECT
This table describes the objects, function codes and qualifiers used in the device:
Obj Var
OBJECT
Description
Binary Input - All Variations
Binary Input
Binary Input with Status
Binary Input Change - All Variations
Binary Input Change without Time 1
1
1
REQUEST
(slave must parse)
Func
Codes
(dec)
Qual
Codes
(hex)
06
06,07,08
06,07,08
Binary Input Change with Time
Binary Input Change with Relative Time
Binary Output - All Variations
Binary Output
Binary Output Status
Control Block - All Variations
1
1
1
06
06,07,08
06,07,08
129, 130
129, 130
129, 130
RESPONSE
(master must parse)
Func
Codes
Qual
Codes
(hex)
129, 130
129, 130
129, 130
00, 01
00, 01
17, 28
17, 28
17, 28
00, 01
Realflo User and Reference Manual
May 19, 2011
1076
DNP3 Protocol User Manual
20
20
20
20
20
20
20
20
1
2
3
4
5
6
7
8
DNP V3.00
DEVICE PROFILE DOCUMENT
IMPLEMENTATION OBJECT
This table describes the objects, function codes and qualifiers used in the device:
Obj
12
12
12
20
Var
1
2
3
0
OBJECT
Description
Control Relay Output Block
Pattern Control Block
Pattern Mask
Binary Counter - All Variations
32-Bit Binary Counter
16-Bit Binary Counter
32-Bit Delta Counter
16-Bit Delta Counter
32-Bit Binary Counter without Flag
16-Bit Binary Counter without Flag
32-Bit Delta Counter without Flag
16-Bit Delta Counter without Flag
1, 7, 8,
9, 10
REQUEST
(slave must parse)
Func
Codes
(dec)
Qual
Codes
(hex)
3, 4, 5,
6
17, 28
06
RESPONSE
(master must parse)
Func
Codes
Qual
Codes
(hex)
129 echo of request
129, 130
129, 130
129, 130
129, 130
00, 01
00, 01
00, 01
00, 01
Realflo User and Reference Manual
May 19, 2011
1077
DNP3 Protocol User Manual
Obj
21
21
21
21
21
21
21
21
DNP V3.00
DEVICE PROFILE DOCUMENT
IMPLEMENTATION OBJECT
This table describes the objects, function codes and qualifiers used in the device:
21
21
21
21
Var
0
1
2
3
4
5
6
7
8
9
10
11
OBJECT
Description
Frozen Counter - All Variations
32-Bit Frozen Counter
16-Bit Frozen Counter
32-Bit Frozen Delta Counter
16-Bit Frozen Delta Counter
32-Bit Frozen Counter with Time of Freeze
16-Bit Frozen Counter with Time of Freeze
32-Bit Frozen Delta Counter with Time of
Freeze
16-Bit Frozen Delta Counter with Time of
Freeze
32-Bit Frozen Counter without Flag
16-Bit Frozen Counter without Flag
32-Bit Frozen Delta Counter without Flag
1
REQUEST
(slave must parse)
Func
Codes
(dec)
Qual
Codes
(hex)
06
RESPONSE
(master must parse)
Func
Codes
Qual
Codes
(hex)
129, 130
129, 130
00, 01
00, 01
129, 130
129, 130
00, 01
00, 01
Realflo User and Reference Manual
May 19, 2011
1078
DNP3 Protocol User Manual
21
22
22
22
22
22
22
22
22
22
23
23
5
6
7
8
0
1
DNP V3.00
DEVICE PROFILE DOCUMENT
IMPLEMENTATION OBJECT
This table describes the objects, function codes and qualifiers used in the device:
Obj Var
12
0
1
2
3
4
OBJECT
Description
16-Bit Frozen Delta Counter without Flag
Counter Change Event - All Variations
32-Bit Counter Change Event without Time
16-Bit Counter Change Event without Time
32-Bit Delta Counter Change Event without
Time
16-Bit Delta Counter Change Event without
Time
32-Bit Counter Change Event with Time
16-Bit Counter Change Event with Time
32-Bit Delta Counter Change Event with Time
16-Bit Delta Counter Change Event with Time
Frozen Counter Event - All Variations
32-Bit Frozen Counter Event without Time
1
REQUEST
(slave must parse)
Func
Codes
(dec)
Qual
Codes
(hex)
06,07,08
RESPONSE
(master must parse)
Func
Codes
Qual
Codes
(hex)
129, 130
129, 130
17, 28
17, 28
Realflo User and Reference Manual
May 19, 2011
1079
DNP3 Protocol User Manual
23
23
23
23
23
23
23
30
30
30
30
30
30
2
3
4
5
6
7
8
0
1
2
3
4
5
DNP V3.00
DEVICE PROFILE DOCUMENT
IMPLEMENTATION OBJECT
This table describes the objects, function codes and qualifiers used in the device:
Obj Var
OBJECT
Description
16-Bit Frozen Counter Event without Time
32-Bit Frozen Delta Counter Event without Time
16-Bit Frozen Delta Counter Event without Time
32-Bit Frozen Counter Event with Time
16-Bit Frozen Counter Event with Time
32-Bit Frozen Delta Counter Event with Time
16-Bit Frozen Delta Counter Event with Time
Analog Input - All Variations
32-Bit Analog Input
16-Bit Analog Input
32-Bit Analog Input without Flag
16-Bit Analog Input without Flag
Short Floating Point Analog Input
1
REQUEST
(slave must parse)
Func
Codes
(dec)
Qual
Codes
(hex)
06
RESPONSE
(master must parse)
Func
Codes
Qual
Codes
(hex)
129, 130
129, 130
129, 130
129, 130
129, 130
00, 01
00, 01
00, 01
00, 01
00, 01
Realflo User and Reference Manual
May 19, 2011
1080
DNP3 Protocol User Manual
31
31
31
31
31
31
31
32
32
32
32
32
0
1
2
3
4
5
6
0
1
2
3
4
DNP V3.00
DEVICE PROFILE DOCUMENT
IMPLEMENTATION OBJECT
This table describes the objects, function codes and qualifiers used in the device:
Obj Var
OBJECT
Description
Frozen Analog Input - All Variations
32-Bit Frozen Analog Input
16-Bit Frozen Analog Input
32-Bit Frozen Analog Input with Time of Freeze
16-Bit Frozen Analog Input with Time of Freeze
32-Bit Frozen Analog Input without Flag
16-Bit Frozen Analog Input without Flag
Analog Change Event - All Variations
32-Bit Analog Change Event without Time
16-Bit Analog Change Event without Time
32-Bit Analog Change Event with Time
16-Bit Analog Change Event with Time
1
REQUEST
(slave must parse)
Func
Codes
(dec)
Qual
Codes
(hex)
06,07,08
RESPONSE
(master must parse)
Func
Codes
Qual
Codes
(hex)
129,130
129,130
129,130
129,130
17,28
17,28
17,28
17,28
Realflo User and Reference Manual
May 19, 2011
1081
DNP3 Protocol User Manual
33
33
33
33
33
40
40
40
40
41
41
DNP V3.00
DEVICE PROFILE DOCUMENT
IMPLEMENTATION OBJECT
This table describes the objects, function codes and qualifiers used in the device:
Obj
32
Var
5
0
1
2
3
4
0
1
2
3
0
1
OBJECT
Description
Short Floating Point Analog Change Event without Time
Frozen Analog Event - All Variations
32-Bit Frozen Analog Event without Time
16-Bit Frozen Analog Event without Time
32-Bit Frozen Analog Event with Time
16-Bit Frozen Analog Event with Time
Analog Output Status - All Variations
32-Bit Analog Output Status
16-Bit Analog Output Status
Short Floating Point Analog Output Status
Analog Output Block - All Variations
32-Bit Analog Output Block
1
3, 4, 5,
6
REQUEST
(slave must parse)
Func
Codes
(dec)
Qual
Codes
(hex)
06
17, 28
129, 130
129
129, 130
129, 130
RESPONSE
(master must parse)
Func
Codes
Qual
Codes
(hex)
129,130 17,28
00, 01
00, 01
00, 01 echo of request
Realflo User and Reference Manual
May 19, 2011
1082
DNP3 Protocol User Manual
52
52
50
50
50
51
51
DNP V3.00
DEVICE PROFILE DOCUMENT
IMPLEMENTATION OBJECT
This table describes the objects, function codes and qualifiers used in the device:
Obj
41
41
Var
2
3
0
1
2
0
1
OBJECT
Description
16-Bit Analog Output Block
Short Floating Point Analog Output Block
Time and Date - All Variations
Time and Date
Time and Date with Interval
Time and Date CTO - All Variations
Time and Date CTO
3, 4, 5,
6
3, 4, 5,
6
2 (see
4.14)
REQUEST
(slave must parse)
Func
Codes
(dec)
Qual
Codes
(hex)
17, 28
17, 28
07 where quantity = 1
129, 130
RESPONSE
(master must parse)
Func
Codes
Qual
Codes
(hex)
129
129 echo of request echo of request
51
52
2
0
1
2
Unsynchronized Time and Date CTO
Time Delay - All Variations
Time Delay Coarse
Time Delay Fine
129, 130
129
129
07, quantity=1
07, quantity=1
07, quantity=1
07, quantity=1
Realflo User and Reference Manual
May 19, 2011
1083
DNP3 Protocol User Manual
Obj
60
60
70
80
60
60
60
81
82
83
83
DNP V3.00
DEVICE PROFILE DOCUMENT
IMPLEMENTATION OBJECT
This table describes the objects, function codes and qualifiers used in the device:
Var
1
1
1
2
0
1
2
3
4
1
1
OBJECT
Class 0 Data
Class 1 Data
Class 2 Data
Class 3 Data
Description
File Identifier
Internal Indications
Storage Object
Device Profile
Private Registration Object
Private Registration Object Descriptor
1
2
1
20,21
1
20,21
1
20,21
REQUEST
(slave must parse)
Func
Codes
(dec)
Qual
Codes
(hex)
00 index=7
06
06,07,08
06
06,07,08
06
06,07,08
06
RESPONSE
(master must parse)
Func
Codes
Qual
Codes
(hex)
Realflo User and Reference Manual
May 19, 2011
1084
DNP3 Protocol User Manual
1
1
2
3
1
2
3
Obj
101
101
101
90
100
100
100
DNP V3.00
DEVICE PROFILE DOCUMENT
IMPLEMENTATION OBJECT
This table describes the objects, function codes and qualifiers used in the device:
Var
OBJECT
Description
Application Identifier
Short Floating Point
Long Floating Point
Extended Floating Point
Small Packed Binary-Coded Decimal
Medium Packed Binary-Coded Decimal
Large Packed Binary-Coded Decimal
No Object
No Object
No Object
REQUEST
(slave must parse)
Func
Codes
(dec)
Qual
Codes
(hex)
14
23
(see
4.14)
13
RESPONSE
(master must parse)
Func
Codes
Qual
Codes
(hex)
Realflo User and Reference Manual
May 19, 2011
1085
DNP3 Protocol User Manual
DNP V3.00
TIME SYNCHRONISATION PARAMETERS
This table describes the worst-case time parameters relating to time synchronization, as required by DNP Level 2 Certification Procedure section 8.7
PARAMETER
VALUE
Time base drift +/- 1 minute/month at 25°C
+1 / -3 minutes/month 0 to 50°C
Time base drift over a 10-minute interval +/- 14 milliseconds at 25°C
+14 / -42 milliseconds 0 to 50°C
Maximum delay measurement error +/- 100 milliseconds
Maximum internal time reference error when set from the protocol
+/- 100 milliseconds
Maximum response time 100 milliseconds
Realflo User and Reference Manual
May 19, 2011
1086
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 3 Table of Contents
- 16 Important Safety Information
- 19 About The Book
- 20 Introduction
- 20 Overview
- 22 System Requirements
- 22 Organization of the Manual
- 23 Additional Documentation
- 24 Installation
- 25 Version Release Notes
- 25 AGA-11, Coriolis Mass Flow Meter Support
- 25 Bi-Directional Flow Support
- 25 Windows7 Support Added
- 26 PEMEX Modbus Protocol Support
- 27 Gas Quality Control History
- 27 Flow Computer Register Grouping
- 27 Support for SCADAPack 330 and SCADAPack 334 Controllers
- 27 Enron General Purpose Registers Added
- 28 Remove AGA-3 (1985) Flow Calculations
- 28 Support for Application Identifier
- 28 Support for SolarPack 410 Controllers
- 28 Support for SCADAPack 4203 Controllers
- 29 Changes to the Wet Gas Meter Parameter
- 29 AGA-7 Uncorrected Flow Volume- Turbine Meter Factor
- 29 CSV and CSX Export Enhancements
- 29 Support for SCADAPack 350
- 29 Flow Accumulator Time Stamps
- 30 4000 Transmitter Display Enhancements
- 30 Absolute / Gage Configuration of 4000 Transmitters
- 30 AGA-8 Composition Editing for Hexane Plus Added
- 30 AGA-8 Heating Value and Specific Gravity
- 30 CFX Export Enhancements
- 31 CSV Export Enhancements
- 31 Maintenance Mode
- 31 Flow Computer Configuration Templates
- 31 Improved Flow Computer Setup Dialog
- 31 Forcing of Flow Calculation Inputs
- 31 Improved History Download and Archive
- 31 Improved Transmitter and Run Integration
- 32 New File Wizards
- 32 Improved Plate Change Wizard Information
- 32 Improved Process I/O Destination Restrictions
- 32 Improved Run ID length
- 32 Improved Time Weighted Averages of DP, P, and T
- 32 Calibration Reports
- 32 Current and Previous month totals
- 32 AGA-7 uncorrected flow
- 32 Analog Measurement Rate
- 33 History Restore
- 33 New I/O Module Support
- 33 Wet Gas Meter Factor (Realflo 6.10 and later)
- 33 Realflo Firmware Compatibility
- 37 Realflo Maintenance Mode Reference
- 39 Selected Flow Computer
- 40 Select Flow Computer Wizard
- 40 Open an Existing File
- 42 Create a New File Wizard
- 43 Read Configuration From the Flow Computer
- 43 Open File
- 44 Connect to Flow Computer
- 45 Read Configuration from the Flow Computer
- 46 Save Configuration File
- 47 Configuration Complete
- 48 Create Configuration From a Template File
- 48 Create New File Dialog
- 48 Flow Computer Information
- 48 Flow Computer Status Dialog
- 48 Hardware and Firmware Type Step
- 50 I/O Module Type Step
- 51 Flow Computer ID Step
- 51 Number of Flow Runs Step
- 52 Flow Run ID Step
- 53 Copy Run Step
- 54 Flow Calculation Configuration
- 54 Flow and Compressibility Calculations Step
- 55 Flow Run Units Step
- 57 Flow Run Inputs Step
- 57 Sensor Inputs
- 58 Analog Inputs
- 59 Differential Pressure Limits Step
- 59 Sensor Inputs
- 60 Analog Inputs
- 62 Turbine Limits Step
- 62 Static Pressure Measurement Step
- 63 Static Pressure Input Limits Step
- 66 Static Pressure Compensation Step
- 66 Temperature Limits Step
- 67 Sensor Inputs
- 67 Analog Inputs
- 68 Contract Settings Step
- 70 AGA-3 Settings Step
- 71 AGA-3 Deadband Settings Step
- 72 AGA-7 Settings Step
- 73 AGA -11 Configuration Step
- 74 Address
- 74 Port
- 74 Timeout
- 74 V-Cone Settings Step
- 77 V-Cone Coefficients
- 78 AGA-8 Options Step
- 79 AGA-8 Hexanes+ Options
- 80 AGA-8 Gas Composition Step
- 80 Individual Components
- 80 NX-19 Settings
- 81 Sensor Configuration
- 81 Sensor Configuration
- 82 Configure Sensors
- 83 Sensor Search
- 84 Search Serial Option
- 84 Search LAN Option
- 84 Assign Sensors
- 87 Search for More Sensors
- 87 Review Transmitters
- 88 Flow Computer Configuration Summary
- 89 Review Differences
- 90 Save File
- 90 Finish
- 91 Create Configuration Step-by-Step
- 91 Step-by-Step Configuration Sequence for a Flow Computer
- 92 Create New File Dialog
- 92 Flow Computer Status Dialog
- 92 Hardware and Firmware Type Dialog
- 94 I/O Module Type Dialog
- 95 Flow Computer ID Dialog
- 95 Flow Runs Dialog
- 96 Flow Run ID
- 99 Flow Calculations Dialog
- 100 Flow Run Units Dialog
- 102 Flow Run Inputs
- 102 Sensor Inputs
- 103 Analog Inputs
- 104 Differential Pressure Input Limits
- 104 Sensor Inputs
- 106 Analog Inputs
- 107 Turbine Settings
- 108 Static Pressure Options Dialog
- 108 Static Pressure Input Limits
- 110 Sensor Inputs
- 111 Analog Inputs
- 112 Static Pressure Compensation
- 112 Temperature Limits
- 113 Sensor Inputs
- 114 Analog Inputs
- 115 Contract Settings
- 116 Flow Calculations
- 117 AGA-3 Settings
- 118 AGA-3 Deadband Settings
- 119 AGA-7 Settings
- 119 AGA -11 Settings
- 120 Address
- 120 Port
- 120 Timeout
- 120 V-Cone Settings
- 122 Density of Liquid
- 123 V-Cone Coefficients
- 124 Compressibility Calculations
- 124 AGA-8 Settings
- 125 AGA-8 Hexanes+ Settings
- 125 AGA-8 Gas Composition
- 125 Individual Components
- 127 Combined Hexanes+
- 127 NX-19 Settings
- 128 Sensor Configuration Parameters
- 128 Sensor Configuration
- 129 Configure Connected Transmitters
- 129 Sensor Search
- 130 Search Serial Option
- 131 Search LAN Option
- 131 Assign Sensors
- 133 Search for More Transmitters Dialog
- 134 Review Sensors Dialog
- 135 Copy Run Configuration Dialog
- 135 Flow Computer Configuration Summary
- 136 Review Differences
- 137 Save File
- 137 Finish
- 139 View Data
- 139 View Current Readings
- 139 Connect to Flow Computer
- 140 Current Readings View
- 141 Process Measurements
- 141 Calculated Compressibility
- 141 Calculation Status
- 142 Pulse Input Volume
- 142 Calculated Flow at Base Conditions
- 142 Calculated Flow (PEMEX)
- 143 Accumulated Flow
- 143 Accumulated Flow (PEMEX)
- 143 AGA-7 Calculations Only
- 143 Accumulated Uncorrected Flow
- 144 SolarPack 410
- 144 Pulse Input Volume
- 144 Battery Charger
- 145 Read Logs and Flow History
- 145 Connect to Flow Computer
- 147 Select Runs to Read
- 148 Select Flow Computer Configuration
- 148 Select Alarm and Event Logs to Read
- 149 Select Hourly and Daily History to Read
- 151 Save Data
- 154 Export Data
- 155 Export Data to CFX
- 156 Save CFX Export
- 157 Export Data to CSV
- 157 Save CSV Export
- 158 Export PEMEX Report to CSV
- 159 CFX Export Settings
- 161 CSV Export Settings
- 163 Maintenance
- 163 Connections for SCADAPack Sensor Calibration
- 163 Differential Pressure Calibration Connections
- 164 Absolute Pressure Calibration Connections
- 164 Calibrate Inputs
- 165 Connect to Flow Computer
- 167 Sensor Calibration
- 169 Run Calibration Procedure
- 170 Calibration Step 1: Force Value
- 171 Calibration Step 2: Record As Found Values
- 173 Calibration Step 3: Calibration Required
- 174 Calibration Step 4: Calibrate Sensor
- 175 Calibration Step 5: Record As Left Values
- 176 Calibration Step 6: Restore Live Input
- 177 Calibration Step 6: Calibration Report Comment
- 178 Calibration Step 7: Calibration Report
- 180 Sensor Calibration Procedure
- 181 Calibration Step 1: Force Value
- 183 Calibration Step 2: Record As- Found Values
- 184 Calibration Step 3: Calibration Required
- 186 Calibration Step 4: Calibrate SCADAPack 4102, 4202, or 4203
- 187 Calibration Step 4: Calibrate SCADAPack 4101
- 187 Calibration Step 4: Calibrate 3095 MVT
- 189 Calibration Step 4: Record As Left Values
- 190 Calibration Step 5: Restore Live Input
- 191 Calibration Step 6: Calibration Report Comment
- 192 Calibration Step 7: Calibration Report
- 193 Change Orifice Plate
- 194 Connect to Flow Computer
- 196 Select Meter Run
- 198 Choose Orifice Fitting Type Step
- 199 Dual Chamber Orifice
- 199 Force Input Step
- 200 Change Orifice Plate Step
- 202 Complete Orifice Plate Change
- 203 Single Chamber Orifice
- 203 Stop Flow Step
- 204 Change Orifice Plate Step
- 204 Complete Orifice Plate Change
- 205 Force Inputs
- 206 Connect to Flow Computer
- 208 Select Run or Transmitter to Force
- 209 Force Run Inputs
- 210 Force Sensor Inputs
- 212 Configuration
- 212 View and Change Configuration Wizard
- 213 Connect to Flow Computer
- 215 Edit Configuration
- 215 Flow Computer Configuration
- 216 Flow Run Configuration
- 216 Sensor and Display Configuration
- 216 Process I/O configuration
- 216 Flow Computer Configuration Summary
- 216 Review Differences
- 218 Save File
- 219 Switch to Expert Mode
- 219 Realflo User Manual
- 219 Exit Realflo
- 220 Realflo Expert Mode Reference
- 220 User Interface Components
- 221 Display Window
- 221 Current Readings
- 223 Title Bar
- 224 Standard Toolbar
- 225 Maintenance Toolbar
- 226 Configuration Toolbar
- 227 Status Bar
- 227 Scroll Bars
- 227 Menu Bar
- 228 File Menu
- 228 New Command
- 228 Open Command
- 229 Close Command
- 229 Save Command
- 229 Save As Command
- 230 Flow Computer File Types
- 230 Template File Types
- 230 Managing Realflo Files
- 231 Export Command
- 231 Export to CSV
- 232 Export to CFX
- 233 CFX File Version
- 234 CSV Export Options Dialog
- 236 CFX Export Options Dialog
- 238 Export PEMEX Report to CSV
- 239 Print Command
- 240 Print Preview Command
- 240 Print Setup Command
- 241 Print Setup Command in PEMEX Mode
- 243 Recent Files List
- 243 Exit Command
- 244 Edit Menu
- 244 Copy Command
- 244 Select All Command
- 244 Custom Views Command
- 246 Edit Table View Dialog
- 249 Add Registers Dialog
- 250 Register Properties Dialog
- 253 Edit Label Dialog
- 253 Edit Register on View Dialog
- 255 Columns Dialog
- 256 Custom View Window
- 256 Editing Data
- 257 Printing and Exporting Data
- 257 Register Command
- 258 Write Initial Values Command
- 259 Template Steps
- 259 Creating a Template File
- 260 Selecting Template Steps
- 261 View Menu
- 261 Current Readings Command
- 261 Process Measurements
- 261 Calculated Compressibility
- 262 Calculation Status
- 263 Pulse Input Volume
- 263 Calculated Flow at Base Condition
- 263 Calculated Flow (PEMEX)
- 263 Accumulated Flow Base Conditions
- 264 Accumulated Flow (PEMEX)
- 264 Accumulated Uncorrected Flow
- 264 Battery Charger
- 264 Hourly History Command
- 264 Hourly History View
- 264 New Hour Triggers
- 265 Realflo Standard and GOST Modes Hourly History Views
- 266 Realflo PEMEX Mode Hourly History View
- 267 Daily History Command
- 268 New Day Triggers
- 268 Realflo Standard and GOST Modes Daily History Views
- 269 Realflo PEMEX Mode Daily History View
- 270 Hourly Gas Quality History Command
- 271 New Hour Triggers
- 271 Hourly Gas Quality History View
- 272 Event Log Command
- 273 Alarm Log Command
- 274 More Views Command
- 275 Run 1 . . . Run 10 Commands
- 276 Change All Views Command
- 276 Modifying History and Log Views
- 276 Sorting Data
- 276 Sizing Columns
- 276 Selecting Data
- 276 Printing and Exporting Data
- 276 Toolbar Command
- 276 Status Bar Command
- 276 Maintenance Mode
- 276 Start in Expert Mode
- 278 Configuration Menu
- 278 Replace Flow Computer
- 278 Collect Logs and Flow History
- 279 Replace Account Codes
- 279 Read Configuration
- 281 Select Event and Alarm Logs
- 282 Select Hourly and Daily History
- 284 Read Log Results
- 285 Replace Flow Computer Wizard
- 285 Standard Flow Computer Files
- 286 GOST Flow Computer Files
- 286 PEMEX Flow Computer Files
- 287 Set Time
- 288 Write Flow Computer Configuration
- 289 Read Alarm and Event Logs
- 290 Bluetooth Security
- 291 Initialize Command
- 291 Initialize Telepace Flow Computer
- 292 Initialize IEC 61131-3 Flow Computer
- 293 Erasing Programs in Flash
- 293 Initialize SCADAPack 4203 and SolarPack 410 Flow Computer
- 294 Real Time Clock
- 295 Wireless Security Settings
- 296 Flow Computer Information
- 296 Telepace Flow Computer Information
- 299 Telepace SCADAPack 314/330/334, SCADAPack 350, SCADAPack 4203 and SolarPack 410 Flow Computer Information
- 301 IEC 61131-3 Flow Computer Information
- 302 IEC 61131-3 SCADAPack 314/330/334, SCADAPack 350 and SCADAPack 4203 Flow Computer Information
- 304 Edit Options Dialog
- 305 Obtaining an Activation Code
- 305 Applying an Activation Code
- 306 Setup
- 307 Sensor and Display
- 309 Sensor Search Dialog
- 309 Search Serial
- 311 Search LAN
- 312 Change Address Dialog
- 314 Edit Sensor Settings Dialog
- 315 General Page
- 316 Measured Variables Page
- 319 Display Module Page
- 320 Custom Item Dialog
- 321 Flow Run
- 323 Inputs Tab
- 324 Run ID
- 324 * Input Units
- 325 * Flow Calculation
- 325 * Compressibility Calculation
- 325 Low Flow Events
- 326 Value on Sensor Fail
- 326 Run Direction Control
- 327 Flow Direction Register
- 328 On Indicates
- 328 Gas Quality Sources
- 328 Hysteresis Units
- 329 Differential Pressure Tab
- 329 * Input Type
- 330 * Input Register
- 330 Input at Zero Scale
- 330 Input at Full Scale
- 330 Differential Pressure at Zero Scale
- 330 Differential Pressure at Full Scale
- 330 Low DP Cutoff
- 330 Low DP Hysteresis
- 330 Default Value
- 332 Static Pressure Tab
- 332 * Input Type
- 333 * Input Register
- 333 Input at Zero Scale
- 333 Input at Full Scale
- 333 Pressure at Zero Scale
- 333 Pressure at Full Scale
- 333 * Tap Location
- 334 Pressure Type
- 334 Atmospheric Pressure
- 334 Location
- 335 Altitude
- 335 Latitude
- 335 Default Value
- 336 Temperature Tab
- 336 * Input Type
- 337 * Input Register
- 337 Input at Zero Scale
- 337 Input at Full Scale
- 337 Temperature at Zero Scale
- 337 Temperature at Full Scale
- 337 Default Value
- 338 Turbine Tab
- 338 * Input Type
- 338 * Input Register
- 338 Low Flow Pulse Limit
- 338 Low Flow Detect Time
- 338 Contract Tab
- 339 * Contract Units
- 340 * Base Temperature
- 340 * Base Pressure
- 340 Standard Conditions
- 340 * Contract Hour
- 341 ** Wet Gas Meter Factor
- 341 PEMEX Base Conditions
- 341 * Base Temperature
- 341 * Base Pressure
- 341 PEMEX Conditions Button
- 342 AGA-3 Configuration
- 342 Orifice Material
- 342 Pipe Material
- 343 Orifice Diameter
- 343 Orifice reference temperature
- 343 Pipe Diameter
- 343 Pipe reference temperature
- 343 Isentropic exponent
- 343 Viscosity
- 343 Temperature Deadband
- 343 Static Pressure Deadband
- 343 Differential Pressure Deadband
- 345 AGA-7 Configuration
- 345 K Factor
- 345 M Factor
- 346 AGA -11 Configuration
- 347 Address
- 347 Port
- 347 Timeout
- 348 V-Cone Configuration
- 348 Cone Material
- 348 Pipe Material
- 348 Adiabatic Expansion Factor
- 349 Cone Diameter
- 349 Cone Measurement Temperature
- 349 Pipe Inside Diameter
- 349 Pipe reference temperature
- 349 Isentropic Exponent
- 349 Viscosity
- 349 Wet Gas Correction Factor
- 350 Mass Flow Rate of Liquid
- 350 Density of Liquid
- 350 Flow Coefficients
- 351 AGA-8 Configuration
- 353 AGA-8 Gas Component Ranges
- 354 AGA-8 Hexanes +
- 355 NX-19 Configuration
- 356 Register Formats
- 356 Process I/O
- 358 Process Input Dialog
- 360 Process Output Dialog
- 361 Serial Ports
- 376 IP Command
- 378 LAN Port
- 378 SCADAPack 32 or SCADAPack 32P PPP Controls
- 378 com1 Port
- 380 com2 Port
- 380 com3 Port
- 380 com4 Port
- 380 PPP Login
- 381 Add PPP Username dialog
- 381 Edit PPP Username dialog
- 382 Modbus Common
- 383 Modbus/TCP
- 384 Modbus RTU in UDP
- 385 Modbus ASCII in UDP
- 386 DNP in TCP
- 387 DNP in UDP
- 387 Friendly IP List
- 388 Add Friendly IP Address Range Dialog
- 389 FTP
- 390 FTP Practices
- 391 Register Assignment
- 396 Default Register Assignments
- 396 SCADAPack 4202 or 4203
- 396 SCADAPack, SCADAPack Plus, SCADAPack 32
- 397 SCADAPack 314
- 397 SCADAPack 330
- 397 SCADAPack 334
- 398 SCADAPack 350
- 398 DNP
- 398 Store and Forward
- 400 Add/Edit Store and Forward Dialog
- 401 Power Management Configuration
- 401 Power Management Dialog
- 403 Selecting Power Management Configuration
- 404 Communication
- 404 Pulse Input Configuration
- 404 Pulse Input Configuration Dialog
- 404 Selecting Pulse Input Configuration
- 404 Communication
- 404 Gas Sampler Output Configuration
- 405 Gas Sampler Output Dialog
- 405 Selecting Gas Sampler Output Configuration
- 405 Communication
- 406 Modbus Mapping
- 408 Using the Modbus Mapping Settings Table
- 408 Real Time Clock Registers
- 409 Shared Read/Write Run Data Registers
- 412 Meter Run Data Registers
- 417 Read Configuration
- 418 Write Configuration
- 419 Edit Script
- 423 Run Script
- 423 Log Results
- 424 Automatic Script Execution
- 424 Options
- 426 C/C++ Program Loader
- 427 Add C/C++ Program Dialog
- 427 Accounts
- 428 Account Information
- 429 Add/Edit Account Dialog
- 430 Lock Flow Computer
- 431 Unlock Flow Computer
- 432 Override Flow Computer Lock
- 432 Show Lock Status
- 433 Maintenance Menu
- 433 Log On
- 433 Read Logs/History
- 436 Calibration
- 436 Connections for SCADAPack Sensor Calibration
- 436 Differential Pressure Calibration Connections
- 437 Absolute Pressure Calibration Connections
- 438 Sensor Calibration
- 440 Run Calibration Procedure
- 441 Calibration Step 1: Force Value
- 443 Calibration Step 2: Record As Found Values
- 444 Calibration Step 3: Calibration Required
- 446 Calibration Step 4: Calibrate Sensor
- 446 Calibration Step 5: Record As Left Values
- 447 Calibration Step 6: Restore Live Input
- 449 Calibration Step 7: Calibration Report Comment
- 449 Calibration Step 8: Calibration Report
- 451 Sensor Calibration Procedure
- 452 Calibration Step 1: Force Value
- 454 Calibration Step 2: Record As- Found Values
- 455 Calibration Step 3: Calibration Required
- 457 Calibration Step 4: Calibrate SCADAPack 4101, 4202 or 4203
- 458 Calibration Step 4: Calibrate SCADAPack 4101
- 458 Calibration Step 4: Calibrate 3095 Transmitter
- 460 Calibration Step 4: Record As Left Values
- 461 Calibration Step 5: Restore Live Input
- 462 Calibration Step 6: Calibration Report Comment
- 462 Calibration Step 7: Calibration Report
- 464 Recovering From a PC Crash During Calibration
- 464 Recovering From a Power Loss During Calibration
- 464 Replacing a Sensor
- 464 Calibration Report Options
- 465 Change Orifice Plate
- 466 Select Meter Run
- 468 Choose Orifice Fitting Type Step
- 468 Dual Chamber Orifice
- 469 Force Input Step
- 470 Change Orifice Plate Step
- 472 Complete Orifice Plate Change
- 474 Single Chamber Orifice
- 474 Stop Flow Step
- 474 Change Orifice Plate Step
- 475 Complete Orifice Plate Change
- 476 Calculation Control
- 477 Update Readings
- 478 Update Readings Once
- 478 Force Inputs
- 479 Force Run Inputs
- 481 Force Transmitter Sensor Inputs
- 483 Communication Menu
- 483 PC Communications Settings Command
- 484 ClearSCADA
- 484 General Parameters
- 485 Advanced Parameters
- 486 Information
- 487 DNP
- 487 General Parameters
- 489 Flow Control Parameters
- 490 RTS/CTS Flow Control
- 491 Dial Up Parameters
- 492 Advanced Parameters
- 493 Information
- 494 DNP/TCP
- 494 General Page
- 495 IP Address / Name
- 495 Advanced Page
- 496 Information Page
- 497 DNP/UDP
- 498 General Page
- 499 IP Address / Name
- 499 Advanced Page
- 500 Information Page
- 501 Modbus ASCII
- 501 General Parameters
- 503 Modbus ASCII Configuration (Flow Control)
- 504 Modbus ASCII Configuration (Dial Up)
- 506 Advanced Parameters
- 507 Information
- 508 Modbus ASCII in TCP
- 508 General Parameters
- 509 Advanced Parameters
- 510 Information
- 511 Modbus ASCII in UDP
- 512 General Parameters
- 513 Advanced Parameters
- 514 Information
- 515 Modbus RTU
- 515 Introduction
- 515 General Parameters
- 517 Modbus RTU Configuration (Flow Control)
- 519 Modbus RTU Configuration (Dial Up)
- 520 Advanced Parameters
- 521 Information
- 522 Modbus RTU in TCP
- 523 General Parameters
- 524 Advanced Parameters
- 525 Information
- 526 Modbus RTU in UDP
- 527 General Parameters
- 528 Advanced Parameters
- 529 Information
- 530 Modbus/TCP
- 530 General Parameters
- 532 Advanced Parameters
- 533 Information
- 534 Modbus/UDP
- 534 General Parameters
- 535 Advanced Parameters
- 536 Information
- 537 Modbus/USB
- 538 General Parameters
- 539 Information
- 539 SCADAServer
- 540 General Parameters
- 541 Advanced Parameters
- 542 Information
- 542 Connect to Controller Command
- 542 Disconnect from Controller Command
- 543 Communication Progress Dialog
- 543 Communication Failures
- 543 Inactive Phone Connection Dialog
- 544 Window Menu
- 544 New Window Command
- 544 Cascade Command
- 544 Tile Command
- 544 Arrange All Command
- 544 Open Window List
- 545 Help Menu
- 545 Contents Command
- 545 About Command
- 546 Realflo Wizards
- 546 Navigating Wizards
- 546 Create New File Wizard
- 548 Read Configuration From the Flow Computer
- 549 Flow Computer Status
- 549 Connect to Flow Computer
- 550 Read Configuration from the Flow Computer
- 551 Save Configuration File
- 553 Configuration Complete
- 553 Create Configuration From a Template File
- 553 Create New File Dialog
- 554 Flow Computer Information
- 554 Flow Computer Status Dialog
- 554 Hardware and Firmware Type Step
- 555 I/O Module Type Step
- 556 Flow Computer ID Step
- 557 Number of Flow Runs Step
- 557 Flow Run ID Step
- 558 Copy Run Step
- 559 Flow Calculation Configuration
- 559 Flow and Compressibility Calculations Step
- 560 Flow Run Units Step
- 562 Flow Run Inputs Step
- 562 Sensor Inputs
- 563 Analog Inputs
- 564 Differential Pressure Limits Step
- 564 Sensor Inputs
- 565 Analog Inputs
- 566 Turbine Limits Step
- 567 Static Pressure Measurement Step
- 567 Static Pressure Input Limits Step
- 570 Static Pressure Compensation Step
- 570 Temperature Limits Step
- 570 Sensor Inputs
- 571 Analog Inputs
- 572 Contract Settings Step
- 574 AGA-3 Settings Step
- 575 AGA-3 Deadband Settings Step
- 576 AGA-7 Settings Step
- 577 AGA -11 Configuration Step
- 577 Address
- 578 Port
- 578 Timeout
- 578 V-Cone Settings Step
- 580 V-Cone Coefficients
- 581 AGA-8 Options Step
- 582 AGA-8 Hexanes+ Options
- 583 AGA-8 Gas Composition Step
- 583 Individual Components
- 583 NX-19 Settings
- 584 Sensor Configuration
- 584 Sensor Configuration
- 585 Configure Sensors
- 586 Sensor Search
- 586 Search Serial Option
- 587 Search LAN Option
- 587 Assign Sensors
- 590 Search for More Sensors
- 590 Review Transmitters
- 591 Flow Computer Configuration Summary
- 592 Review Differences
- 592 Save File
- 593 Finish
- 594 Create Configuration Step-by-Step
- 594 Step-by-Step Configuration Sequence for a Flow Computer
- 595 Create New File Dialog
- 595 Flow Computer Status Dialog
- 595 Hardware and Firmware Type Dialog
- 596 I/O Module Type Dialog
- 597 Flow Computer ID Dialog
- 598 Flow Runs Dialog
- 598 Flow Run ID
- 599 Flow Calculations Dialog
- 600 Flow Run Units Dialog
- 602 Flow Run Inputs
- 602 Sensor Inputs
- 604 Analog Inputs
- 604 Differential Pressure Input Limits
- 605 Sensor Inputs
- 606 Analog Inputs
- 607 Static Pressure Options Dialog
- 607 Static Pressure Input Limits
- 609 Analog Inputs
- 610 Static Pressure Compensation
- 611 Turbine Settings
- 611 Temperature Limits
- 611 Sensor Inputs
- 612 Analog Inputs
- 614 Contract Settings
- 615 Flow Calculations
- 615 AGA-3 Settings
- 616 AGA-3 Deadband Settings
- 617 AGA-7 Settings
- 618 AGA -11 Settings
- 618 Address
- 619 Port
- 619 Timeout
- 619 V-Cone Settings
- 621 Density of Liquid
- 621 V-Cone Coefficients
- 622 Compressibility Calculations
- 622 AGA-8 Settings
- 623 AGA-8 Hexanes+ Settings
- 624 AGA-8 Gas Composition
- 624 Individual Components
- 625 Combined Hexanes+
- 625 NX-19 Settings
- 626 Sensor Configuration Parameters
- 626 Sensor Configuration
- 627 Configure Connected Transmitters
- 628 Sensor Search
- 628 Search Serial Option
- 629 Search LAN Option
- 629 Assign Sensors
- 632 Search for More Transmitters Dialog
- 632 Review Sensors Dialog
- 633 Copy Run Configuration Dialog
- 634 Flow Computer Configuration Summary
- 634 Review Differences
- 635 Save File
- 635 Finish
- 637 Replace Flow Computer Wizard
- 639 Set Time
- 640 Write Flow Computer Configuration
- 641 Read Alarm and Event Logs
- 642 Bluetooth Security
- 644 Read Logs and Flow History Wizard
- 644 Connect to Flow Computer
- 645 Select Runs to Read
- 646 Select Flow Computer Configuration
- 646 Select Alarm and Event Logs to Read
- 647 Select Hourly and Daily History to Read
- 650 Save Data
- 651 Export Data
- 651 Export Data to CFX
- 653 Save CFX Export
- 654 Export Data to CSV
- 655 Save CSV Export
- 657 CFX Export Settings
- 660 CSV Export Settings
- 661 Calibrate Inputs Wizard
- 661 Connect to Flow Computer
- 663 Sensor Calibration
- 664 Run Calibration Procedure
- 667 Calibration Step 1: Force Value
- 669 Calibration Step 2: Record As Found Values
- 671 Calibration Step 3: Calibration Required
- 673 Calibration Step 4: Calibrate Sensor
- 674 Calibration Step 5: Record As Left Values
- 675 Calibration Step 6: Restore Live Input
- 676 Calibration Step 6: Calibration Report Comment
- 677 Calibration Step 7: Calibration Report
- 678 MVT Calibration Procedure
- 680 Calibration Step 1: Force Value
- 682 Calibration Step 2: Record As-Found Values
- 684 Calibration Step 3: Calibration Required
- 685 Calibration Step 4: Calibrate SCADAPack 4101, 4202 or 4203
- 687 Calibration Step 4: Calibrate SCADAPack 4101
- 688 Calibration Step 4: Calibrate 3095 MVT
- 690 Calibration Step 5: Record As Left Values
- 691 Calibration Step 6: Restore Live Input
- 692 Calibration Step 7: Calibration Report Comment
- 693 Calibration Step 8: Calibration Report
- 694 Change Orifice Plate Wizard
- 694 Connect to Flow Computer
- 695 Select Meter Run
- 696 Choose Orifice Fitting Type Step
- 697 Dual Chamber Orifice
- 698 Force Input Step
- 700 Change Orifice Plate Step
- 702 Complete Orifice Plate Change
- 702 Single Chamber Orifice
- 702 Stop Flow Step
- 703 Change Orifice Plate Step
- 704 Complete Orifice Plate Change
- 705 Force Inputs Wizard
- 705 Connect to Flow Computer
- 706 Select Run or Transmitter to Force
- 707 Force Run Inputs
- 708 Force MVT Inputs
- 710 TeleBUS Protocol Interface
- 710 Register Addresses
- 710 TeleBUS Registers Used by the Flow Computer
- 712 Meter Run 1 Data Registers
- 712 Execution State Registers
- 712 Instantaneous and Accumulated Readings Registers
- 716 Daily Flow History Data Registers
- 718 Meter Run 2 Data Registers
- 718 Meter Run 3 Data Registers
- 718 Meter Run 4 Data Registers
- 718 Execution State Registers
- 719 Instantaneous and Accumulated Readings Registers
- 721 Meter Runs 4 to 10 Daily Flow History Registers
- 724 Get Daily History Command
- 724 Meter Run 5 Data Registers
- 725 Meter Run 6 Data Registers
- 725 Meter Run 7 Data Registers
- 725 Meter Run 8 Data Registers
- 725 Meter Run 9 Data Registers
- 726 Meter Run 10 Data Registers
- 726 TeleBUS Configuration Registers
- 727 Configuration Command Execution
- 728 Input Configuration
- 728 Input Configuration Registers
- 732 Get Input Configuration Command
- 733 Set Input Configuration Command
- 733 MVT Configuration
- 734 MVT Data Registers
- 735 MVT Command Parameter Registers
- 736 MVT Transmitter Information Registers
- 736 MVT Transmitter Type Codes
- 736 MVT Configuration Registers
- 739 MVT Search Command
- 740 MVT Change Address Command
- 740 Get MVT Configuration Command
- 741 Set MVT Configuration Command
- 742 Read MVT Configuration Command
- 743 Set MVT Sensor Mode
- 744 MVT Calibration
- 744 MVT Sensor Information Registers
- 745 MVT Sensor Calibration Registers
- 745 Get MVT Sensor Information Command
- 746 Calibrate MVT Sensor Command
- 747 Contract Configuration
- 747 Contract Configuration Registers
- 748 Get Contract Configuration Command
- 748 Set Contract Configuration Command
- 749 AGA-3 Configuration
- 749 AGA-3 Configuration Registers
- 750 Get AGA-3 Configuration Command
- 750 Set AGA-3 Configuration Command
- 751 AGA-7 Configuration
- 751 AGA-7 Configuration Registers
- 751 Get AGA-7 Configuration Command
- 752 Set AGA-7 Configuration Command
- 752 Coriolis Meter Configuration
- 752 Coriolis Meter Configuration Registers
- 753 Get Coriolis Meter Configuration Command
- 753 Set Coriolis Meter Configuration Command
- 754 V-Cone Configuration
- 754 V-Cone Configuration Registers
- 756 Get V-Cone Configuration
- 756 Set V-Cone Configuration
- 757 AGA-8 Configuration
- 757 AGA-8 Configuration Registers
- 759 Get AGA-8 Gas Ratios Command
- 759 Set AGA-8 Gas Ratios Command
- 760 AGA-8 Hexanes+ Configuration Registers
- 761 Get AGA-8 Hexanes+ Gas Ratios
- 761 Set AGA-8 Hexanes+ Gas Ratios
- 762 NX-19 Configuration
- 762 NX-19 Configuration Registers
- 763 Get NX-19 Gas Ratios Command
- 763 Set NX-19 Gas Ratios Command
- 764 Orifice Plate Change
- 764 Start Plate Change: Temperature Input Commands
- 765 End Plate Change: Temperature Input Command
- 766 Start Plate Change: Static Pressure Input Commands
- 767 End Plate Change: Static Pressure Input Command
- 767 Start Plate Change: Differential Pressure Input Commands
- 768 End Plate Change: Differential Pressure Input Command
- 769 User Account Configuration
- 769 User Account Configuration Registers
- 769 Lookup User Number Command
- 770 Lookup User ID Command
- 771 Delete Account Command
- 771 Update Account Command
- 772 Read Next Account Command
- 773 Meter Runs Configuration
- 773 Meter Runs Configuration Registers
- 773 Set Number of Meter Runs Command
- 773 Flow Run Identification
- 774 Run ID Configuration Registers
- 774 Set Run ID Command
- 774 Get Run ID Command
- 775 Long Run ID Configuration Registers
- 775 Set Long Run ID Command
- 776 Get Long Run ID Command
- 776 Flow Computer Execution Control
- 776 Execution Control Registers
- 776 Set Execution State Command
- 777 Flow Computer ID Configuration
- 777 Flow Computer Identifier Configuration Registers
- 777 Set Flow Computer ID Command
- 778 Get Flow Computer ID Command
- 778 Enron Modbus Time Stamp Configuration
- 779 Set Enron Modbus Time Stamp Command
- 779 Real Time Clock Configuration
- 780 Real Time Clock Configuration Registers
- 780 Read Real Time Clock
- 781 Set Real Time Clock Command
- 781 Adjust Real Time Clock Command
- 782 SolarPack 410 Power Management Configuration
- 782 SolarPack 410 Power Management Configuration Registers
- 783 Set Power Management Command
- 784 Get Power Management Command
- 784 SolarPack 410 Gas Sampler Output
- 785 Gas Sampler Configuration
- 785 Set Gas Sampler Configuration Command
- 785 Get Gas Sampler Configuration Command
- 786 SolarPack 410 Pulse Input Accumulation
- 786 Pulse Input Accumulation Configuration
- 786 Pulse Input Accumulation Registers
- 787 Set Pulse Input Configuration Command
- 787 Get Pulse Input Configuration Command
- 788 Display Control Configuration
- 788 Display Control Configuration Registers
- 789 Display Item Identifiers
- 790 Get Display Control Configuration Command
- 791 Set Display Control Configuration Command
- 792 Get Display Control Custom Configuration Command
- 793 Set Display Control Custom Configuration Command
- 794 Process Input / Output Configuration
- 794 Process I/Os Configuration Registers
- 794 Process Input Configuration Registers
- 795 Process Output Configuration Registers
- 796 Get Number of Process Inputs Command
- 796 Get Process Input Command
- 797 Set Process Input Command
- 798 Get Number of Process Outputs Command
- 798 Get Process Output Command
- 799 Set Process Output Command
- 799 Calibration Registers
- 799 Calibration Registers
- 800 Force Temperature Input Commands
- 801 End Temperature Calibration Command
- 801 Force Static Pressure Input Commands
- 802 End Static Pressure Calibration Command
- 802 Force Differential Pressure Input Commands
- 803 End Differential Pressure Calibration Command
- 804 Force Turbine Counts Commands
- 804 End Turbine Counts Calibration Command
- 805 Force Mass Flow Rate Calibration Commands
- 806 End Mass Flow Rate Calibration Command
- 806 Force Inputs Registers
- 806 Force Inputs Registers
- 807 Force Current Temperature Command
- 807 Force Fixed Temperature Command
- 808 Restore Live Temperature Command
- 808 Force Current Static Pressure Input Command
- 809 Force Fixed Static Pressure Input Command
- 810 Restore Live Static Pressure Command
- 810 Force Current Differential Pressure Input Command
- 811 Force Fixed Differential Pressure Input Command
- 812 Restore Live Differential Pressure Input Command
- 812 Force Current Turbine Pulse Rate Command
- 813 Force Fixed Turbine Pulse Rate Command
- 814 Restore Live Turbine Pulse Rate Command
- 814 Force Current Mass Flow Rate Command
- 815 Force Fixed Mass Flow Rate Command
- 816 Restore Live Mass Flow Rate Command
- 816 Event and Alarm Log Data
- 817 Event and Alarm Log Data Registers
- 818 Get Number of New Events Command
- 818 Get Requested New Events Command
- 819 Get Number of All Events Command
- 820 Get Requested All Events Command
- 821 Get Recent Events Command
- 821 Acknowledge Events Command
- 822 Get Number of New Alarms Command
- 823 Get Requested New Alarms Command
- 824 Get Number of All Alarms Command
- 824 Get Requested All Alarms Command
- 825 Get Recent Alarms Command
- 826 Acknowledge Alarms Command
- 826 Log User Defined Events
- 827 Log User Event Command
- 827 Hourly History Data
- 828 Hourly History Query and Data Registers
- 829 Get Hourly History Command
- 830 Program Information Registers
- 832 Flow Computer Events and Alarms
- 832 Global Events and Alarms
- 834 AGA-3 (1985) Events and Alarms
- 835 AGA-3 (1992) Events and Alarms
- 836 AGA-7 Events and Alarms
- 836 AGA-11 Events and Alarms
- 837 V-Cone Events and Alarms
- 838 AGA-8 Events and Alarms
- 839 NX-19 Events and Alarms
- 840 Sensor Events and Alarms
- 852 Calibration and User Defined Alarms and Events
- 854 Flow Computer Error Codes
- 854 Calculation Engine Errors
- 854 AGA-3 (1985) Calculation Errors
- 855 AGA-3 (1992) Calculation Errors
- 856 AGA-7 Calculation Errors
- 856 AGA-11 Calculation Errors
- 856 V-Cone Calculation Errors
- 857 AGA-8 Calculation Errors
- 858 NX-19 Calculation Errors
- 858 Flow Calculation Engine Command Errors
- 860 MVT Command Errors
- 861 Coriolis Meter Errors
- 861 SolarPack 410 Errors
- 861 AGA-3 Command Errors
- 861 AGA-7 Command Errors
- 861 AGA-11 Command Errors
- 861 V-Cone Command Errors
- 862 AGA-8 Command Errors
- 862 NX-19 Command Errors
- 862 Flow Computer Commands
- 865 Flow Computer Register Grouping
- 865 Register Group Data
- 867 Configure Register Group Location
- 868 Flow Computer Application ID
- 868 Application Identifiers
- 869 Device Configuration Read Only Registers
- 871 Application Identifier
- 871 Company Identifier
- 872 Enron Modbus Protocol Interface
- 873 Register Addresses
- 873 Variable Types
- 873 Boolean Variables
- 873 Short Integer Variables
- 873 Long Integer and Floating Point Variables
- 874 Hourly/Daily History
- 874 Hourly Gas Quality History
- 874 Flow Computer Variables
- 876 Enron Modbus General Purpose Registers
- 876 Register Mapping
- 876 Status and Coil Registers
- 876 16-Bit Input Registers – Telepace only
- 876 16-Bit Holding Registers – Telepace only
- 877 32-Bit Integer Holding Registers
- 877 Telepace Firmware
- 877 ISaGRAF Firmware
- 877 32-Bit Floating Point Holding Registers
- 878 Flow Computer Global Variables
- 878 Program Information Variables
- 878 Meter Runs Configuration Variable
- 878 Real Time Clock Variables
- 879 Flow Computer ID Variables
- 879 Hourly / Daily Archive Records
- 880 Hourly / Daily Record Format
- 881 Hourly Gas Quality Archive Records
- 882 Flow Computer Events Variables
- 882 User Account Events Variables
- 882 Event/Alarm Archive Variable
- 882 Event and Alarm Log Events Variables
- 883 Event Record Format
- 883 Alarm Record Format
- 885 Meter Run 1 Data Variables
- 885 Meter Run 1 Flow Computer Execution State Variable
- 885 Meter Run 1 Instantaneous and Accumulated Variables
- 885 Instantaneous Input Variables
- 885 Instantaneous Input Alarms
- 885 Instantaneous Flow Variables
- 886 Compressibility Variables
- 886 Accumulated Flow Variables
- 887 Enron Log Variables
- 888 Meter Run 1 Input Configuration Variables
- 888 General Input Configuration Variables
- 888 Temperature Input Variables
- 889 Static Pressure Input Variables
- 890 Differential Input Variables
- 890 Turbine Input Variables
- 891 Meter Run 1 Flow Computer Execution Control Variable
- 891 Meter Run 1 ID Variables
- 892 Meter Run 1 Contract Configuration Variables
- 893 Meter Run 1 AGA-3 Configuration Variables
- 893 Meter Run 1 V-Cone Configuration Variables
- 894 Meter Run 1 AGA-7 Configuration Variables
- 895 Meter Run 1 AGA-8 Configuration Variables
- 895 Mole Fractions
- 897 Percentages
- 898 Hexane + Ratios Percentages
- 899 Meter Run 1 NX-19 Configuration Variables
- 899 Plate Change Events Variables
- 900 Temperature Plate Change Event Variables
- 900 Static Pressure Plate Change Event Variables
- 900 Differential Pressure Plate Change Event Variables
- 900 Enron Forcing Events Variables
- 900 Temperature Force Event Variables
- 900 Static Pressure Force Event Variables
- 901 Differential Pressure Force Event Variables
- 901 Counter Force Event Variables
- 901 Meter Run 1 Flow Computer Events Variables
- 901 Input Alarms Variables
- 902 Compressibility Events Variables
- 902 AGA-8 Variables
- 902 NX-19 Variables
- 903 Flow Events Variables
- 903 AGA-3 (1985) Variables
- 903 AGA-3 (1992) Variables
- 904 AGA-7 Variables
- 904 V-Cone Variables
- 904 Calibration Events Variables
- 904 Temperature Calibration Event Variables
- 904 Static Pressure Calibration Event Variables
- 905 Differential Pressure Calibration Event Variables
- 905 Counter Calibration Event Variables
- 905 Meter Run 2 Data Variables
- 905 Meter Run 3 Data Variables
- 906 Meter Run 4 Data Variables
- 906 Meter Run 5 Data Variables
- 907 Meter Run 6 Data Variables
- 907 Meter Run 7 Data Variables
- 907 Meter Run 8 Data Variables
- 908 Meter Run 9 Data Variables
- 908 Meter Run 10 Data Variables
- 908 MVT-1 Data and Configuration Variables
- 909 MVT-1 MVT Configuration Variables
- 911 MVT-1 Events Variables
- 912 MVT-2 Data and Configuration Variables
- 913 MVT-3 Data and Configuration Variables
- 913 MVT-4 Data and Configuration Variables
- 913 MVT-5 Data and Configuration Variables
- 914 MVT-6 Data and Configuration Variables
- 914 MVT-7 Data and Configuration Variables
- 915 MVT-8 Data and Configuration Variables
- 915 MVT-9 Data and Configuration Variables
- 916 MVT-10 Data and Configuration Variables
- 917 Event and Alarm Log
- 918 Global Alarms and Events
- 920 AGA-3 (1985) Alarms and Events
- 921 AGA-3 (1992) Alarms and Events
- 922 AGA-7 Alarms and Events
- 922 AGA-11 Alarms and Events
- 922 V-Cone Alarms and Events
- 923 AGA-8 Alarms and Events
- 925 NX-19 Alarms and Events
- 925 MVT Alarms and Events
- 927 Coriolis Meter Alarms and Events
- 927 Calibration and User Defined Alarms and Events
- 927 Calculation Engine Errors
- 928 AGA-3 (1985) Calculation Errors
- 928 AGA-3 (1992) Calculation Errors
- 929 AGA-7 Calculation Errors
- 929 V-Cone Calculation Errors
- 929 AGA-8 Calculation Errors
- 929 NX-19 Errors
- 931 PEMEX Modbus Protocol Interface
- 931 Register Addresses
- 932 Meter Run 1 Data Variables
- 932 Meter Run 1 Instantaneous and Accumulated Variables
- 933 Meter Run 1 Historic Variables
- 933 Meter Run 2 Data Variables
- 933 Meter Run 2 Instantaneous and Accumulated Variables
- 934 Meter Run 2 Historic Variables
- 934 Meter Run 3 Data Variables
- 934 Meter Run 3 Instantaneous and Accumulated Variables
- 935 Meter Run 3 Historic Variables
- 935 Meter Run 4 Data Variables
- 935 Meter Run 4 Instantaneous and Accumulated Variables
- 936 Meter Run 4 Historic Variables
- 936 Historic Data Variables
- 937 Historic Record Format
- 937 Gas Quality History Record Format
- 938 Meter Run 1 Configuration
- 938 AGA Configuration
- 938 Gas Composition Configuration
- 939 Gas Component Ranges
- 940 Meter Run 2 Configuration
- 940 AGA Configuration
- 940 Gas Composition Configuration
- 940 Meter Run 3 Configuration
- 940 AGA Configuration
- 941 Gas Composition Configuration
- 941 Meter Run 4 Configuration
- 941 AGA Configuration
- 941 Gas Composition Configuration
- 941 Configuration Values
- 941 Calculated Compressibility
- 941 Tap Location
- 942 Run Enable
- 942 AGA Calculation Method
- 942 Time Synchronization
- 942 Event and Alarm Log
- 943 Global Alarms and Events
- 947 AGA-3 (1985) Alarms and Events
- 947 AGA-3 (1992) Alarms and Events
- 948 AGA-7 Alarms and Events
- 949 AGA-11Alarms and Events
- 949 V-Cone Alarms and Events
- 950 AGA-8 Alarms and Events
- 951 NX-19 Alarms and Events
- 952 MVT Alarms and Events
- 953 Coriolis Meter Alarms and Events
- 953 Calibration and User Defined Alarms and Events
- 954 Calculation Engine Errors
- 955 AGA-3 (1985) Calculation Errors
- 955 AGA-3 (1992) Calculation Errors
- 955 AGA-7 Calculation Errors
- 956 AGA-11 Calculation Errors
- 956 V-Cone Calculation Errors
- 956 AGA-8 Calculation Errors
- 956 NX-19 Errors
- 957 Retrieval and Acknowledgment of Events and Alarms
- 957 Alarm or Event Record Format
- 957 Event Status Bits
- 957 Alarm Status Bits
- 958 Alarm Acknowledgement
- 959 Measurement Units
- 959 US1 Units
- 959 US2 Units
- 960 US3 Units
- 960 US4 Units
- 961 US5 Units
- 961 US6 Units
- 962 US7 Units
- 962 US8 Units
- 962 PEMEX Units
- 963 IP Units
- 963 Metric1 Units
- 964 Metric2 Units
- 964 Metric3 Units
- 965 SI Units
- 966 Input Averaging
- 966 Flow-Dependent Time Weighted Linear Average
- 966 Flow Weighted Linear Average
- 967 No Flow Linear Average
- 968 Creating Custom Realflo Applications
- 968 SCADAPack Controllers
- 968 Telepace Files:
- 968 ISaGRAF Files:
- 969 Modifying the Application
- 970 Building the Application for Telepace Firmware
- 970 Building the Application for ISaGRAF Firmware
- 971 SCADAPack 314/330/334 and SCADAPack 350 Controllers
- 971 SCADAPack 32 Controllers
- 971 Realfloi Files
- 971 Realflot Files
- 972 Modifying the Application
- 973 Building the Application
- 974 Measurement Canada Approved Version
- 974 Flow Computer Disabled Commands
- 975 Enron Protocol Disabled Commands
- 976 Measurement Canada Lockout Cable
- 976 Measurement Canada Approved Flow Computers
- 976 SCADAPack 32
- 976 SCADAPack 314
- 976 SCADAPack 330/334
- 977 SCADAPack and SCADAPack LP
- 977 SolarPack 410
- 977 SCADAPack 4203 DR
- 978 SCADAPack 4203 DS
- 978 SCADAPack 4202 DR
- 979 SCADAPack 4202 DS
- 980 DNP3 Protocol User Manual
- 980 DNP Overview
- 980 DNP Architecture
- 981 Object Library
- 981 Internal Indication (IIN) Flags
- 982 Application Layer
- 983 Pseudo-Transport Layer
- 983 Data Link Layer
- 983 Physical Layer
- 983 Modbus Database Mapping
- 984 SCADAPack DNP Operation Modes
- 984 SCADAPack DNP Outstation
- 985 How to Configure SCADAPack DNP Outstation
- 986 Tasks to Complete
- 986 Enable DNP on Communication Interface
- 986 Configure DNP Outstation
- 990 Confirm Successful Configuration
- 991 SCADAPack DNP Master
- 991 SCADAPack DNP Master Concepts
- 992 SCADAPack DNP Mimic Master
- 994 SCADAPack DNP Address Mapping
- 995 How to Configure SCADAPack DNP Master
- 995 Tasks to Complete
- 996 Configuration Steps
- 998 Confirm Successful DNP Master Configuration
- 999 How to Configure SCADAPack Address Mapping
- 1000 How to Configure SCADAPack DNP Mimic Master
- 1000 SCADAPack DNP Router
- 1001 How to Configure a SCADAPack DNP Router
- 1002 Tasks to Complete
- 1002 Configuration Steps
- 1004 Design Considerations
- 1005 Considerations of DNP3 Protocol and SCADAPack DNP Driver
- 1005 Unsolicited Messages always request for a Confirmation
- 1005 Master shall never request for Application Layer Confirmation
- 1005 DNP Write Messages always request for a Confirmation
- 1005 Only one DNP3 transaction can be pending at a time
- 1005 SCADAPack controllers buffer 3 DNP messages
- 1005 Output points in DNP Address Mapping issue DNP Write
- 1005 Typical Configuration Malpractices and Recommendations
- 1006 Multiple High Priority Unsolicited Messages
- 1007 Recommendations:
- 1007 Master not polling frequently causing event buffer overflows
- 1008 Outstation reports to Multiple Masters with Poor Communications Link
- 1008 Insufficient Use of Input Deadband or Debounce
- 1008 Master Confirmation and Retries
- 1008 Outstation Confirmations and Retries
- 1010 Setting relatively large Application Layer timeouts
- 1010 DNP Address mapping contains multiple output points
- 1011 Configuration FAQ
- 1014 DNP Configuration Menu Reference
- 1015 Application Layer Configuration
- 1020 Data Link Layer Configuration
- 1023 Master
- 1024 Master Poll
- 1025 Add/Edit Master Poll Dialog
- 1029 Poll Offset Example
- 1030 Address Mapping
- 1031 Add/Edit Address Mapping Dialog
- 1032 Routing
- 1034 Add/Edit DNP Route Dialog
- 1035 Dynamic Routing
- 1035 Binary Inputs Configuration
- 1037 Adding Binary Inputs
- 1038 Binary Outputs Configuration
- 1039 Adding Binary Outputs
- 1041 16–Bit Analog Inputs Configuration
- 1042 Adding 16-Bit Analog Inputs
- 1044 32-Bit Analog Inputs Configuration
- 1046 Adding 32-Bit Analog Inputs
- 1047 Short Floating Point Analog Inputs
- 1049 Adding Short Floating Point Analog Inputs
- 1051 16-Bit Analog Outputs Configuration
- 1052 Adding 16-Bit Analog Outputs
- 1053 32-Bit Analog Outputs Configuration
- 1054 Adding 32-Bit Analog Outputs
- 1055 Short Floating Point Analog Outputs
- 1056 Adding Short Floating Point Analog Outputs
- 1058 16–Bit Counter Inputs Configuration
- 1059 Adding 16-Bit Counter Inputs
- 1061 32-Bit Counter Inputs Configuration
- 1063 Adding 32-Bit Counter Inputs
- 1064 DNP Diagnostics
- 1065 DNP Status
- 1066 Overview Tab
- 1067 Point Status Tabs
- 1068 DNP Master Status
- 1069 All Stations Tab
- 1070 Remote Overview Tab
- 1071 Remote Point Status Tabs
- 1073 DNP Master Device Profile Document
- 1089 DNP Slave Device Profile Document