NuAire MRXBOXAB-ECO4 Installation And Maintenance Manual
Nuaire MRXBOXAB-ECO4 is a mechanical ventilation unit designed for wall mounting. It features heat recovery and heat exchanger bypass, offering efficient ventilation with minimal energy loss. The unit also includes a humidistat and frost protection for optimized performance in various climates. It's suitable for residential applications, ensuring fresh air circulation and a comfortable indoor environment.
PDF
Download
Document
Advertisement
Advertisement
MRXBOXAB-ECO4 (Standard Unit) MRXBOXAB-ECO4-OH (Opposite hand Unit) Mechanical Ventilation Units with Heat Recovery and Heat Exchanger Bypass for Wall Mounting Installation and Maintenance 1.0 Introduction The ECO4 wall mounted units are designed to provide mechanical supply and extract ventilation with heat recovery and an integral automatic HX bypass. The units also incorporate an integral humidistat and frost protection (see page 7 for details). To recover heat from the extract air the heat exchanger block is utilised. The heat exchanger can recover up to 95% of the normally wasted heat. The EMC Directive 2014/30/EU The Low Voltage Directive 2014/35/EU IMPORTANT The unit must remain switched on at all times to maintain ventilation within the dwelling. Turning the unit off will cause long term damage to the unit and building fabric. This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning the use of the appliance by a person for their safety. Children should be supervised so that they do not play with the appliance. Figure 1. Airflow through unit (Standard unit). Intake air from outside 2.0 Installation Supply air to house Exhaust air from house to outside Extract air from house Installation must be carried out by competent personnel in accordance with the appropriate authority and conforming to all statutory governing regulations. All mains wiring must be in accordance with the current I.E.E. Regulations, or the appropriate standards. Ensure that the mains supply (Voltage, Frequency and Phase) complies with the rating label. Please note a clear working space is required around the installed unit to allow the cover to be removed and provide sufficient access for maintenance such as filter change. Please allow a minimum of 480mm in front of the unit. The fan must be installed indoors, on a suitable wall away from direct sources of frost, heat and water spray or moisture generation. For a vibration-free result the unit must be mounted to a solid wall. The unit is designed for wall mounting only on a solid wall, a gypsum block or a stud wall will not suffice. Additional measures such as extra studs or double panelling using 20mm MDF is required. Figure 2. Airflow through OH unit (Opposite hand unit). Extract air from house Exhaust air from house to outside Supply air to house Intake air from outside 1. One part of the mounting bracket (supplied) should be offered up to the wall, ensuring it’s located horizontally. Mark the fixing points through the pre drilled holes in the bracket and install with screws (by others), whilst ensuring the interlock side is at the top (fig. 3). 2. Install the unit on the wall by ensuring the bracket on the unit interlocks over the wall mounted bracket (fig. 4). Ensure the mains power cable does not become trapped between the brackets during this process as this will prevent engagement and potentially damage the electrical insulation. The cable gland can be rotated through 90 degrees to assist this operation and subsequent cable routing. Note: Care must be taken to ensure the unit is installed true in all 3 dimensions. Failure to do so may result in overflow from the internal condensation drip tray. Figure 3. Fixing the mounting bracket to the wall. nuaire.co.uk 029 2085 8400 If fitting the MVHR in conjuntion with a MRXBOX-SIL4 the unit should be mounted using alternative brackets supplied under part code MRXBOX-AV4, the standard wall brackets supplied with the MVHR are not rated for the additional load. 19. 08. 19. Leaflet Number 671797 1 Installation and Maintenance 2.1 Option 1: Wall Mounting The ECO4 Wall Mounted Range of Units 2.3 Condensate Drain The MVHR unit fixed to a solid wall construction using the mounting bracket provided. Figure 4. Typical example of a cupboard mounted unit (Standard unit) fixed to a block work wall. 1. The condensate must be discharged under a water level in a U-trap drainpipe or an alternative drain method which acts as an airlock. 2. The condensate discharge drain is a 32mm male threaded connection. 3. If using a U-trap please ensure the U-trap has been filled to a suitable level of water to avoid any air locks. 4. If the condensation pipe is fitted in an unheated space the pipe should be in insulated to prevent freezing. Ducting in the ceiling void. Valve in ceiling. Nuaire recommend MVHR-DRAIN be used as the primary condensate take-off. (see figure 10 and 11). Figure 6. Wet option: Condensate pipe connection to unit and a typical example of a “U” trap drainpipe (Standard configuration only). Side view of unit mounted on the block wall in a cupboard. Min 5 o Drop MVHR-DRAIN Condensate drain, uninsulated drain pipe with min 5 o fall running to SVP. Figure 7. MVHR-DRAIN option: Condensate drain, uninsulated drain pipe with min 5° fall running to SVP. 2.2 Option 2: Wall Mounting If it is not practical to use a solid wall, the MVHR unit should be fixed to a stud partition with a 25mm minimum thickness MDF panel solidly fixed behind the plasterboard. Collar If fixing to a stud wall the MDF panel should extend, width wise, over a minimum of 3 vertical studs with centres of no more than 400mm. Add additional vertical supports if necessary. Height wise, ideally, the MDF panel should extend from floor to ceiling but as a minimum should be a least 2m high. Fix the mounting bracket to the wall (as fig. 3) and use the wall mounted bracket to mount the unit on (as shown in fig. 5). Figure 8. IMPORTANT: When using a “T” Piece to connect the CONTRAP drainage and the MVHR drain pipework the MVHR drain must always be fitted before the “T” Piece to prevent condensate from feeding back into the MVHR system. Figure 5. Typical example of a cupboard mounted unit (Standard unit) fixed to a stud partition with the MDF panel fixed behind the plaster-board. MVHR Drain To CONTRAP To unit To SVP “T” piece Ducting in the ceiling void. Valve in ceiling. Side view of unit mounted in a cupboard fixed to a stud partition with the 25mm MDF fixed behind the plasterboard. 2.4 Extract/Input Areas The unit is designed to extract air from all wet rooms e.g. bathroom, kitchen, en-suite, utility room (with sink). WC’s do not need to be ventilated if openable windows are fitted. Supply air should be to all habitable rooms e.g. bedrooms and lounge. Extract / input grilles should be adjustable valve types (not supplied). External grilles are to have a minimum free area of 12,250 sq. mm. MVHR-DRAIN Condensate drain, uninsulated drain pipe with min 5 o fall running to SVP. nuaire.co.uk 029 2085 8400 19. 08. 19. Leaflet Number 671797 2 Installation and Maintenance The ECO4 Wall Mounted Range of Units 2.5 Ducting It is recommended that rigid ducting be used it all times. Flexible ducting has a very high resistance and it is impossible to calculate how much resistance will be on a system if used. If used, the flexible ducting must be kept to a minimum and should always be pulled taut. A maximum of 300mm should be used on each leg. To prevent condensation on the exterior of the outside air inlet duct and the air outlet duct from the unit, these ducts should be insulated with material having a thermal resistance of >0.625m2 K/w. Ducting must be installed in such a way that resistance to airflow is minimised. Bends should be kept to a minimum. A minimum distance of 200mm between the appliance and any bends in ductwork is recommended. Ideally 200mm diameter or 204 x 60mm rectangular ducting should be used. Ducting joints must be sealed with silicone type sealant and shall be adequately and reliably fixed to the appliance. 2.6 Ventilation Flow Rates Table 1. ADF 2010 - Extract ventilation rates. Room Min high rate Kitchen 13 l/s Utility Room 8 l/s Bathroom 8 l/s Sanitary Accommodation 6 l/s Min low rate Total extract rate should be at least the whole dwelling ventilation rate given in table 2. The MVHR system has been sized for the winter period. Additional ventilation may be required during the warmer months and it has been assumed that the provisions for purge ventilation (e.g. openable windows) could be used. Step 1: For any design air permeability, determine the whole dwelling ventilation supply rate from Table 2. As an alternative where the design air permeability is intended to be more than (>) 5m3/(h.m2) 50 Pa, allow for infiltration for all dwelling types by subtracting from the whole dwelling ventilation supply rate from Table 2; 0.04 x gross internal volume of the dwelling heated space (m3). Step 2: Calculate the whole dwelling extract ventilation rate by summing the individual room rates for ‘minimum high rate’ from Table 1. (For sanitary accommodation only, as an alternative, the purge ventilation provisions given in ADF 2010 can be used where security is not an issue. In this case ‘minimum high extract rate’ for the sanitary accommodation should be omitted from the step 2 calculation). Step 3: The required airflow rates are as follows: •The maximum whole dwelling extract ventilation rate (e.g. boost) should be at least the greater of step 1 and step 2. Note that the maximum individual room extract rate should be at least those given in table 1. •The minimum air supply rate should be at least the whole building ventilation rate found in step 1. For Scotland refer to BRE Digest 398. For further information refer to “Domestic Ventilation Compliance Guide” www.planningportal.gov.uk/buildingregulations/approved documents/partl/compliance Table 2. Whole dwelling ventilation rates. Number of bedrooms in dwelling 1 Whole dwelling ventilation rate l/s 2.7 ADF 2010 Ventilation Calculations Design of MVHR Systems 13 2 17 3 21 4 25 5 29 1,2 Notes: 1. In addition, the minimum ventilation rate should be no less than 0.3 l/s per m2 of internal floor area. (This includes all floors, e.g. for a two-story building add the ground and first floor areas). 2. This is based on two occupants in the main bedroom and a single occupant in all other bedrooms. This should be used as the default value. If a greater level of occupancy is expected add 4 l/s per occupant. Pre Commissioning MRXBOX95 MVHR Units MRXBOX95 units are designed to ventilate the whole dwelling and must not be used during site construction or the clean-up period. Cement and plaster dust can be abrasive and can affect fan performance and reliability. Please ensure that the filters are checked prior to commissioning to ensure there is no build-up of dust or debris. While the property is drying out, very high moisture levels are likely to occur. Therefore it is advisable that if the installation and building works are complete the unit is left running. If the building works are not complete please close the air valves or cover up the air valves to prevent condensation forming in the ductwork and the MRXBOX95 unit due to natural migration of warm air. IMPORTANT Any air intake terminal MUST be installed in accordance with the appropriate regulation. As a guide, the BS5440 series of British Standards deals with this issue and currently states that an air intake must be at a minimum distance of 300mm from a gas boiler balanced flue. Installers are advised to be aware of the requirements of this standard when installing ‘through the wall’ supply air ducting. nuaire.co.uk 029 2085 8400 19. 08. 19. Leaflet Number 671797 3 Installation and Maintenance The ECO4 Wall Mounted Range of Units 3.0 Dimensions (mm) Figure 9. Unit dimensions. View from top 485 = = Ecosmart connection 290 139 4 x Spigots 180mm Internal Diameter 200mm External Diameter Front view Side view 710 Mounting Bracket AB AB Figure 10. Dimensions: MRXBOX95-3SWITCH Front view Side view 86.0 18 585 710 Figure 11. Dimensions: Unit wall mounting bracket position (viewed from the back). Volt Free Cable Main Cable Exit Point Exit Point = 23.0 = 176 86.0 200 25 25 15.0 Bracket to be fitted to the wall 40.0 CRS 40.0 CRS 534 Flush mounting face to wall or back box 5 Fixing Points 492 CRS 67 nuaire.co.uk 029 2085 8400 67 19. 08. 19. Leaflet Number 671797 4 Installation and Maintenance The ECO4 Wall Mounted Range of Units 4.0 Ducting Arrangements - Standard Configuration Figure 12. Typical ducted arrangement for a wall mounted unit using circular ducting. Exhaust air from kitchen/bathroom to outside via louvre grille. Minimum distance as specified in building regulations. *Insulated extract duct. Top of ceiling void. Air supply to lounge via Air Valve in ceilings. Intake air from outside via louvre grille. All duct between MVHR unit and atmosphere to be insulated*. *Insulated supply duct. Extract air from kitchen/ bathroom via Air Valve in ceilings. Air supply to bedrooms via Air Valve in ceilings. Nuaire wall mounted unit. MVHR-DRAIN Condensate drain, uninsulated drain pipe with min 5o fall running to SVP. Figure 13. Typical ducted arrangement for a wall mounted unit using circular ducting. *Insulated extract duct. Exhaust air from kitchen/bathroom to outside via air brick. Minimum distance as specified in building regulations. Top of ceiling void. Air supply to lounge via Air Valve in ceilings. Intake air from outside via air brick. All duct between MVHR unit and atmosphere to be insulated*. Air supply to bedrooms via Air Valve in ceilings. Extract air from kitchen/ bathroom via Air Valve in ceilings. *Insulated supply duct. Nuaire wall mounted unit. MVHR-DRAIN Condensate drain, uninsulated drain pipe with min 5o fall running to SVP. ALSO FROM NUAIRE New range of thermal ducting, an all-in-one insulated ducting system (see installation document 671780) nuaire.co.uk 029 2085 8400 19. 08. 19. Leaflet Number 671797 5 Installation and Maintenance The ECO4 Wall Mounted Range of Units 5.0 Electrical Connection Figure 14. PCB Details IMPORTANT For good EMC engineering practice, any sensor cables or switched live cables should not be placed within 50mm of other cables or on the same metal cable tray as other cables. EXTRA EXTRA CTCT FANF Please note: the electrical connection of the unit must be be carried out by a qualified electrician. Note: Wiring is for reference purposes only as the connections above are factory fitted. The unit is supplied with a flexible cord for connection to the mains supply. Electrical details:- If more than one Ecosmart sensor is required please use MRXBOX-JB and refer to leaflet No. 671700 for installation instructions. Voltage: 240V 1ph 50Hz Consumption: 2.5 Amp Fuse rating: 5 Amp NOTE This unit must be earthed. 3 FAIL The three core cable from the mains power supply should be connected to a fixed wiring installation, via a fused isolator, in accordance with current IEE wiring regulations. 2 Connection to Remote Fail Indicator Ref: MRXBOX95-RFI (optional). Supply Extract Supply Extract Supply Extract SPEED 1 SPEED 2 SPEED 3 5.1 Examples of typical wiring layouts MRXBOXAB-ECO4 Figure 15. Unit only. Disconnection from the supply mains must be incorporated within the fixed wiring in accordance with the wiring regulations and shall have a minimum contact separation of 3mm. Green/yellow MAINS 230V N 50Hz L Supply cord from unit Blue Brown Fuse 5A 2 Pole Isolator L 1 2 Black Grey 3 Position Switch Ancillary code: MRXBOX95-3SWITCH MRXBOXAB-ECO4 Figure 16. Unit serving one bathroom. MAINS 230V N 50Hz L Disconnection from the supply mains must be incorporated within the fixed wiring in accordance with the wiring regulations and shall have a minimum contact separation of 3mm. MRXBOXAB-ECO4 Figure 17. Unit serving two bathrooms. Disconnection from the supply mains must be incorporated within the fixed wiring in accordance with the wiring regulations and shall have a minimum contact separation of 3mm. nuaire.co.uk 029 2085 8400 MAINS 230V N 50Hz L Green/yellow Supply cord from unit Blue Brown Fuse 5A Light switch (Double Pole) Room light Black 3 Pole Isolator L 1 2 Grey 3 Position Switch Ancillary code: MRXBOX95-3SWITCH Green/yellow Supply cord from unit Blue Brown Fuse 5A Light switches (Double Pole) Room lights Black 3 Pole Isolator L 1 2 Grey 3 Position Switch Ancillary code: MRXBOX95-3SWITCH 19. 08. 19. Leaflet Number 671797 6 Installation and Maintenance 6.0 Switch To fix the switch to a wall or back box remove the front fascia by inserting a terminal screwdriver into the two openings along the bottom edge and prize open gently. The fixing points on the back plate can then be accessed; once the switch has been secured the front fascia can then be re-fitted. 6.1 Ecosmart controls A single Ecosmart sensor can be connected to the unit using the connector situated on the rear panel (see fig. 9). If more than one Ecosmart sensor is required please use MRXBOX-JB and refer to leaflet No. 671700 for installation instructions. Figure 18. Ecosmart sensor connector on the rear panel of the unit. The ECO4 Wall Mounted Range of Units 5. Correct commissioning is essential to ensure the ventilation air flow rates are met. It also ensures the unit is not over ventilating and causing excessive power consumption. 6. Commissioning should be carried out in accordance with building regulations document “Domestic ventilation compliance guide”. www.planningportal.gov.uk/building regulations/approved documents/partf/associated A calibrated moving vane anemometer and hood will be required to carry out commissioning. 7. Adjustment valves should be locked in place to prevent further adjustment. 8. Once commissioned the home owner / tenant should be informed that the unit should not be adjusted as it will have a detrimental effect on the indoor air quality and could result in condensation and mould growth. The clear panel covering the control has an adhesive panel which should be exposed and sealed post commissioning to prevent tampering. 7.1 Humidity adjustment. 7.0 Commissioning IMPORTANT The filters fitted inside the unit are protected with a plastic film. Prior to commissioning remove the covers (figs. 15 & 16), take off the film and replace. 1. For required air flow rates please refer to the design specification for the property, follow 2.4 or refer to building regulations ADF 2010. 2. The unit should be run for a minimum of 10 minutes to reach steady state before commencing commissioning. 3. The humidity sensor is initially set to its least sensitive position, this should be adjusted during commissioning. Depending on storage and site conditions the unit may boost due to high relative humidity levels, this will continue until the level drops below the specified set point. 4. The unit is supplied with independent control for the various speed airflows. (see fig. 19). This product contains an internal humidity sensor fitted into the airflow extracting from the wet rooms. When the unit senses that the humidity exceeds the set point the unit will boost to that set by the commissioned boost speed. The set point can be found on the front of the unit (see fig. 9) and is at its least sensitive when turned fully clockwise. Note that the sensor is measuring humidity from all the wet rooms at the same time and should not be relied on to solely boost the unit. Additional switch should be used local to the wet rooms (see wiring diagrams). 8.0 Status Indication The status of the unit is indicated by a series of LED’s on the front cover. The variants are listed below. Speed 1 Speed 2 Speed 3 Supply Fan Fault Extract Fan Fault Frost Protection Filter Change HX Bypass (AB units only) Figure 19. Detail of unit control on front panel. Note: The display on the unit control panel will not indicate when a higher speed setting has been triggered by an external source, such as an ES-PIR2 etc. 8.1 Integral automatic HX bypass (AB units only) Intake and extract temperatures are monitored at the point the airflows enter the unit, if the range falls within the set parameters the bypass damper is opened automatically to target an indoor comfort temperature all year round. Post commissioning remove adhesive backing and seal Ventilation Controls Speed 1 + - + Speed 2 - + - + Speed 3 - + - + Note: The extract temperature is an average from all wet rooms. If this exceeds 25°C the unit may go into bypass depending on outside temperatures. - Supply Extract Supply Extract Supply Extract Power Fan Failure 061021 nuaire.co.uk 029 2085 8400 19. 08. 19. Leaflet Number 671797 7 Installation and Maintenance The ECO4 Wall Mounted Range of Units 8.2 Frost Protection 11.0 Warranty In the event of the intake air temperature at the unit dropping below the predetermined set point (-5° C as standard) the supply fan will reduce to minimum speed, once the temperature rises above the set point the fan will return to its commissioned speed. The 5 year warranty starts from the day of delivery and includes parts and labour for the first year and parts only for the remaining 4 years. Please note this mode will only activate after ten days of continuous run time. If commissioning of the unit is outside of this time frame please notify the after sales department prior to site visit. 9.0 Maintenance IMPORTANT Isolation - Before commencing work make sure that the unit, switched live and Nuaire control are electrically isolated from the mains supply and switched live supply. Nuaire recommend that filters are inspected every 6 months and replaced every 12 months. A flashing LED (section 8.0) will indicate that a filter change is required. This indication repeats every 12 months and will turn off automatically after 5 Days. Remove the filter covers on the front panel of the unit by gripping the two circular tabs either end of the filter covers and pulling away from the unit. The filter can now be extracted by pulling the removal loop on the front edge of the filter. Once the filters have been inspected return or replace them as necessary. This warranty is void if the equipment is modified without authorisation, is incorrectly applied, misused, disassembled, or not installed, commissioned and maintained in accordance with the details contained in this manual and general good practice. The product warranty applies to the UK mainland and in accordance with Clause 14 of our Conditions of Sale. Customers purchasing from outside of the UK should contact Nuaire International Sales office for further details. 12.0 After Sales For technical assistance or further product information, including spare parts and replacement components, please contact the After Sales Department. Telephone 02920 858 400 [email protected] Inspect the heat exchanger every 5 years. Generally check for damage and security of components. Refit cover. Figure 20. Removing the two filter covers on the front panel of the unit. Filter covers Figure 21. The filters can be removed by pulling on the black tab on the visible end of the filters. Filter being removed Filter cover 10.0 Replacement of Parts Should any component need replacing, Nuaire keep extensive stocks for quick delivery. Ensure that the unit is electrically isolated, before carrying out any work. Note: The supply cable must be replaced by an electrically competent person. When ordering spare parts, please quote the serial number of the unit and the ARC number of the purchase, if possible. (This information will be available on the fan label). nuaire.co.uk 029 2085 8400 19. 08. 19. Leaflet Number 671797 8 ">

Public link updated
The public link to your chat has been updated.
Advertisement
Key features
- Heat Recovery
- Heat Exchanger Bypass
- Humidistat
- Frost Protection
- Wall Mount
- Supply & Extract Ventilation
Frequently asked questions
The heat exchanger bypass allows the unit to bypass the heat exchanger when necessary, ensuring optimal indoor comfort temperature year-round.
Nuaire recommends inspecting the filters every 6 months and replacing them every 12 months. A flashing LED on the unit indicates when a filter change is required.
A 5-year warranty applies, covering parts and labor for the first year and parts only for the remaining 4 years.