WarmlyYours Slab Heating Installation Manual
বিজ্ঞাপন
বিজ্ঞাপন
Installation Manual for
Slab Heating Systems
24/7 Installation Support • Lifetime Technical Assistance • Free Design Service • www.WarmlyYours.com • (800) 875-5285
CONTENTS PAGE
1.0 Product Specifications ............................................................................. 1
2.0 Selection of the Heating System ................................................................ 2
3.0 Important Instructions before Installing the System................................... 2
4.0 Installation for Slab Heating ....................................................................... 3
4.1 Thermostat & Sensor.......................................................................... 3
4.2 Electrical Provisions for the System ................................................... 3
4.3 Pre-Installation Preparations .............................................................. 4
4.4 Installation for Concrete Embedded Applications .............................. 4
4.5 Operating Tips .................................................................................... 5
4.6 Installation under Concrete ................................................................ 6
4.7 Installation of Slab Heating Mat ......................................................... 6
5.0. Testing the Mats and Cable ....................................................................... 7
5.1 Test One: Total Cable Resistance ....................................................... 7
5.2 Test Two & Three: Insulation Resistance ............................................ 7
6.0 Warranty ..................................................................................................... 7
7.0 Appendix
Appendix A: Slab Heating Mats ............................................................... 8
Appendix B: Slab Heating Cables ............................................................ 8
Appendix C: Cross-section of indoor slab Heating Cable in concrete
(With NO floor covering) ........................................................................... 9
Appendix D: Cross-section of indoor slab Heating Cable in concrete
(With floor covering) ................................................................................. 9
8.0 Troublshooting ............................................................................................ 12
9.0 Warranty ..................................................................................................... 14
Warranty Registration ............................................................................... 15
1.0 PRODUCT SPECIFICATIONS
WarmlyYours Heating Cable is designed for new concrete slab floors. It is well suited for large areas like basements, garages and additions.
The Heating Cable is comprised of a dual, multistrand heating element with a primary insulation of Fluoropolymer. The insulated core is then protected with a woven metal braid and an outer jacket of PVC, EPR or Zero Halogen Polyolefin based compound to make it sturdier and to provide corrosion protection. These cables are terminated with 20’ (6.1m) long standard cold leads. The hot and cold junction is uniquely designed to make it durable and flexible.
Available in a wide range of lengths and sizes to suit your requirements, the Slab
Heating Mats and Heating Cables are identified as indicated below.
Item Number: AAAA-BBB-CCCC
Ex: Item Number: WSHM-240-0250
(product type) (voltage) (width & length = 2’x50’)
• AAAA = WSHM for Slab Heating Mat, WSHC for Slab Heating Cable
• BBB = Operating Voltage available in 120V and 240V
• CCCC = Mat width in ft. (first two digits) and Mat length in ft. (third and fourth digits) for Slab Heating Mat, Cable length in ft. for Slab Heat Cable
The available lengths of Slab Heating Mats are shown in Appendix A. The available lengths of Slab Heating Cables are shown in Appendix B. Both Appendices include the following attributes for each Item Number.
• Product Type
• Operating Voltage
• Cable Length
• Mat Width and Length
• Total Ohms
• Total Watts
• Watts/Ft for Cable or Watts/Sq Ft for Mats
• Amps
1
2” (5 cm)
Level of heating cable
2” (5 cm)
3” (7.6 cm)
4 in (10) or 6 in (15) square 10 gauge wire mesh cable
3” (7.6 cm)
2.0 SELECTION OF THE HEATING SYSTEM
Selection of your Heating System will depend on the application. The following can be taken as a general guide:
INSTALL CHART
Application
Indoor Slab Heating
Watts per Sq.Ft. (per Sq.M.)
- Cable spacing inches (mm)
20 W/ft2 (161 to 215 W/m2)
Recommended spacing 3” to 3.5” (76 to 89mm).
Multiplier at given spacing
4 at 3” (76mm)
3.5 at 3.5” (89mm)
3 at 4” (102mm)
2.4 at 5” (127mm)
Formula: Area of Application x Multiplier at given cable spacing = Heated Cable
Length required
Example 1 (English): 100 sq.ft of Slab Heating x 4.0 at 3” spacing = 400 feet of
Heated Cable required
Example 2 (Metric): 9.3 sq.m of Slab Heating x 4.0 at 76mm spacing = 122m of
Heated Cable required
Note: For normal plain bare slabs, stained or stamped use 3” spacing. For application when the slab also has a floor covering like tile or wood, use 5” spacing for a maximum of 15w/sq ft. to meet code requirements.
Please note the above-indicated values are meant as a general guide. Your values may vary depending on a number of factors. Please consult your Account Manager for assistance.
over cable. Duct tape the ends of shovels. Do NOT saw expansion joints, without having lines marked off clearly with spray paint, where installer has verified that
Heating Cables will not be cut. Do NOT damage Cables with heavy equipment, machinery or vehicles.
6. Heating Cables should be separated from other heat sources such as luminaries, and fireplaces.
7. Do not install the Heating Cable below 5˚ F (-15˚ C) ambient temperature.
8. Minimum bending radius of the Heating Cable shall not be less than 10 times its diameter.
9. Minimum spacing of Cables is 3” (76 mm) and maximum spacing of Cables is 5”
(127mm).
10. Twin Conductor Heating Cable has a ground braid (metal sheath) to be connected to ground and 2 conductors which are to be connected to the power supply.
11. Double check the voltage and wattage of the Heating Cable received against the project specifications on your custom installation plan. These are marked on the CSA label of the product. A qualified electrician should connect the Heating
System.
12. Check the conductor, resistance and insulation resistance of the Heating Cable before installing and also after installing. Resistance value should match the value shown in Appendix A and Appendix B. A tolerance of -5% to +10% is allowed.
Insulation resistance must be infinite (500 VDC megger meter required to test).
13. Keep high voltage power wires in a separate conduit from the low voltage sensor wire.
14. Allow sufficient drying or curing period of the slab after installing the Heating
System before energizing the Heating System. (7 day minimum)
15. For easy reference, fix a label at the power distribution board indicating the location of the heating units installed.
3.0 IMPORTANT INSTRUCTIONS BEFORE INSTALLING THE SYSTEM
1. Heating Cable must not cross or overlap itself at any point. Do not install cable runs any closer than 3” on center. This could cause the Cable to overheat, requiring replacement.
2. The Heating Cable length should not be cut or altered under any circumstances. This may cause over heating resulting in damage to the Cable.
3. All heated portion (blue) and factory splice must end up buried completely in the concrete. Ensure none of the heated portion (blue) or the splice (look for heatshrink) enter into any conduit.
Control joint
4. The cold lead can be cut /extended with a conventional splice, inside of an accessible junction box (weatherproof if outdoors).
8”-12” crushed rock aggregate
2
WARNING
16. The Cable must NOT be shortened or cut in any manner or subjected to strain at the factory splice joint.
17. NEVER power up Heating Cables prior to being buried in concrete, (even for testing purposes). This will prevent premature failure of the Heating Cable.
Right hot/cold joints 3 in (7.6 cm) apart and 6 in (15 cm) from slab edge hot/cold joints installed on slab cold joints stalle slab edge hot/cold joints bunched
Concrete
Control joint
Right hot/cold joints 3 in (7.6 cm) apart and 6 in (15 cm) from slab edge
3” hot/cold joints installed on slab cold joints stalle slab edge hot/cold joints bunched
Plastic tie wrap
Heating cable secured to rebar with plastic tie wraps
3”
3” concrete wall
Junction box mounted on inside wall
Cable identification tag
(within 3 in (7.5cm) of NPT connector)
Cold lead
Expansion joint
Heating cable
Hot/Cold joint
4 in (10) or 6 in (15) square 10 gauge wire mesh concrete wall
Junction box mounted on inside wall
Cable identification tag
Conduit
Cold lead
Expansion joint
Heated Slab
Heating cable
Hot/Cold joint Conduit
Conduit
Steel bar
Steel bar
Dimension A must not exceed 3 in (7.5 cm)
A
Dimension B must not exceed 6 in (15 cm)
B
Heating cable secured to rebar with plastic tie wraps maximum thickness
Topping 2 in (5.0 cm) minimum, to 3 in (7.5 cm) maximum thickness
Dimension B must not exceed 6 in (15 cm)
C
Dimension A must not B
A Cold leads protected with 1-1/2in (3.8cm)
Heated Slab where they emerge from slab
Splice
C
If dimension C exceeds 3 in(10 cm) an additional run of cable must be used
Cold leads protected with 1-1/2in (3.8cm) minimum nonmetallic conduit where they emerge from slab
Splice
Lip edge rounded off to prevent cable damage
1.2 in (1.3 cm) wide steel prepunched strapping
Cable must be at least 4 in
(10 cm) from edge
Cable must be at least 4 in
(10 cm) from rail post
1.2 in (1.3 cm) wide steel prepunched strapping
Cable must be at least 4 in
(10 cm) from rail post
Lip edge rounded off to prevent cable damage
Cable must be at least 4 in
(10 cm) from edge
Pavers - No lip overhang
Pavers - No lip overhang
Length 5’ (152cm) min 50’ (1524cm) max
2’ (61cm) or
3’ (91cm)
3"
(8cm)
SENSOR
1/4” (6mm)
Twin-conductor
Heating Cable 20’ (610cm)
Cold Lead
4.0 INSTALLATION FOR INDOOR SLAB HEATING
4.1 TEMPERATURE CONTROLLER & SENSOR
We recommend a standard Programmable Thermostat with a temperature sensor specially designed for control of the Heating System.
WARNING
Length 5’ (152cm) min 50’ (1524cm) max
In case the GFCI in our thermostat trips during normal operation, and cannot be reset, there is likely a fault in the Cable. No attempt should be made to re-energize the system. The GFCI must not be bypassed under any circumstances. Consult a qualified electrician.
The sensor normally comes with a 2 conductor lead wire of 15 feet (4.5m) in length. Thermostat sensor location shall be centered between two adjacent runs of
Heating Cable within metal pipe or conduit to allow for replacement. Do not position
240 VAC
PANEL be routed to the Thermostat located in the wall at suitable operating height. Do not allow any other Heating Cable to overlap with the sensor cable.
20’ (610cm)
Cold Lead
DIAGRAM A
2’ (61cm) or
3’ (91cm)
The details of the thermostats and installation guidelines are given in the instruction manual provided with the Thermostat.
4.2 ELECTRICAL PROVISIONS FOR THE SYSTEMS
THERMOSTAT
120 VAC or use along with the Heating Cables are listed below:
FLOOR
HEATING
CABLE
CONTROL
RELAY
PANEL
T-Stat
2-3”
Probe type sensor at the end of 15’ 2 conductor
20AWG wire.
Code and any applicable local codes. Controls and accessories recommended for
CONCRETE SLAB
SLAB
4-6”
SENSOR WIRE SENSOR CAPPED 3/4”
METAL CONDUIT
120V / 240V VAC SUPPLY
110V / 230V AC SUPPLY
THERMOSTAT
HEATING SYSTEM
THERMOSTAT
SENSOR WIRE
CAPPED
CONDUIT
FLOOR
HEATING
CABLE
10"
(251mm)
SENSOR WIRE
3"
(8cm)
CAPPED
CONDUIT
20’ (610cm) Cold Lead
FLOOR
HEATING
CABLE
Polyester Sheath
Outer Sheath PVC/Pololefin
• Dedicated Circuit Breaker(s) for all heater circuits. GFCI (5mA trip) or GFPE (30mA trip) may be required - check local and national code.
SNOW MELT MAT
SLAB HEATING SYSTEM
The location of the Thermostat junction box shall be about 4’ (1.2m) high from the floor for easy access. The floor sensor wire and the Heating Cable cold leads shall be routed to the Thermostat / power connection box in separate conduits.
If the Heating System has a load below 1,750W at 120V or 3,500W at 240V based on thermostat power rating, it may be connected directly to an electronic thermostat as shown in Diagram A which gives a typical scheme of the electrical system. If the
Heating System has a load more than the thermostat power rating, consult your
WarmlyYours Account Manager. (you’ll likely need a relay panel)
10"
(251mm)
20’ (610cm) Cold Lead
Heating Conductor (Solid/Multistrand)
Primary Insulation (Fluoropolymer)
Metal Sheath (Copper/Galvanised Steel/Cladded Steel)
Polyester Sheath
Outer Sheath PVC/Pololefin
3
Length 5’ (152cm) min 50’ (1524cm) max
4.3 PRE-INSTALLATION PREPARATIONS
1. Review the custom installation plan for the area requiring the Heating System and verify dimensions listed against your actual field dimensions to ensure they match.
2. Confirm the location of the power supply box/Thermostat and sensor against the plan.
3. Select Heating Cable(s) and ensure that the procured Cable is correct according to the requirements in the following section.
4. Check the Slab Heating Cable in the box visually and make sure that it is not damaged. Check voltage, wattage, resistance values from the factory test record and verify that they match the required specifications.
10. Check the resistance and insulation resistance value after laying out Cables.
Check to see if these values are consistent with the pre-install values. Record values in the warranty card on page 13.
11. At this point, the concrete can be poured.
5. Check resistance of the conductor and its insulation resistance with a multimeter/ megohmmeter as soon as it is removed from its packing. Resistance value of the Heating Cable shall match to the value shown in Appendix A or Appendix B.
A tolerance of -5% to +10% is allowed. Insulation resistance should be infinite.
Record it on the warranty card located on page 13 of this manual.
6. The Heating Cable is now ready for installation.
8. Heating Cable should be laid so that the Cables are equally spaced. The distance between two Heating Cable passes should be according to the spacing calculation determined by WarmlyYours (3” to 5” range).
9. Route the power leads through a conduit from the floor to the connection box. If multiple cables are being used, route all power leads through a conduit from the floor to the connection box in the wall. Ensure hot section and factory splice do
NOT get into the conduit
12. Pour the concrete and spread evenly on the reinforcement mesh / grid. The concrete floor or slab thickness shall be about 2” (51 mm) on top of the Heating
Cable. Typical 4” to 6” slabs will have cable located in middle (2” to 3” from finished surface).
13. Ensure the entire Heating Cable, factory splices and thermostat sensor (in metal conduit) are embedded in the cement mortar. The choice and application of building materials should be in accordance with the building material manufacturer’s instructions. (see diagram B)
4.4 INSTALLATION FOR INDOOR CONCRETE SLAB APPLICATION
1. 2” thick polystyrene insulation (or better) should be installed below slab and around perimeter edges.
SNOW MELT MAT
2. Reinforcement mesh on the floor or slab should be strong enough to walk on and not sag or bend.
14. Ensure the correct curing time for drying of construction materials is followed before powering ON the Heating Cables (7 day minimum).
15. Check the continuity, resistance and insulation resistance values after the concrete or mortar is poured. They should be consistent with the values recorded previously.
Record values on the warranty card on page 13 of this manual.
3. Reinforcement mesh should be properly positioned and supported so that it does not get disturbed during the concrete pour. Ensure the Heating Cable is on the reinforcement mesh a minimum of 2” (51mm) below the finished concrete/slab surface.
P N E
4. Surface preparation of the floor is very important. The floor must be completely free of all debris including all nails, sharp metallic objects, wood and construction debris.
Make absolutely sure that there are no objects on the floor that might damage the
Heating Cable.
FLOOR
5. Start installing Heating Cable from the location of power connection box.
SENSOR
6. Roll out the Heating Cable. Secure it to the reinforcement mesh or grid using plastic zip ties (supplied by installer).
HEATING
CABLE
16. Never use 500 VAC megger while personal are standing in, or touching the wet cement. Wait until personal are out of the wet concrete.
T-Stat
2-3”
DIAGRAM B
CONCRETE SLAB
SENSOR WIRE SENSOR
SLAB
4-6”
CAPPED 3/4”
METAL CONDUIT
110V / 230V AC SUPPLY
THERMOSTAT
HEATING SYSTEM
SENSOR WIRE
CAPPED
CONDUIT
FLOOR
HEATING
CABLE
4
2’ (61cm) or
3’ (91cm)
3"
(8cm)
10"
(251mm)
20’ (610cm) Cold Lead
Heating Conductor (Solid/Multistrand)
Primary Insulation (Fluoropolymer)
Metal Sheath (Copper/Galvanised Steel/Cladded Steel)
Polyester Sheath
Outer Sheath PVC/Pololefin
4.5 OPERATING TIPS
1. Energy consumption will vary depending on ambient temperature and building insulation. For lower energy consumption, use a 7-day Programmable Thermostat control.
2. Energy consumption can be minimized by turning the system OFF when heating is not required, but extra time will be required for the floor to warm up once the system is turned ON again.
3. Avoid placing objects like thick mats, rugs, floor level furniture and mattresses on the heated floor, especially in the area where the floor temperature sensor is located. These restrict the transfer of heat away from the Cables and result in the floor area beneath them being warmer than other areas.
4. Avoid Mats with rubber or vinyl type backing as these may decompose with heat and could stain flooring.
4a. For Two-Pour Installations: The concrete installer pours the first 2” to 3” (51mm to 76mm) of concrete. While this first pour is still wet, rebar or wire-mesh should be placed on top of the first pour. The cables should be attached to the rebar
/ mesh with plastic zip ties, using 3” to 5” (76mm to 127mm) spacing for freeform type cable. At this time, the electrician must route the cold lead(s) thru rigid metal conduit(s) to get back to an accessible junction box(es). Care must be taken by the electrician so that none of the heated section nor the factory splice enters any conduit. This is the best time for sensor placement. Separate conduit should be used to protect the low voltage sensor wire and must NOT be shared with any high voltage cold lead from the Heating Cables / Mats. Once conduits
& sensor(s) are placed, the topping pour of concrete can be finished. Again, the concrete installer(s) must take care not to walk on the hot-cold splice point, and to avoid damaging the Heating Cables with shovels and rakes. Taping up the shovel blades helps make them less sharp. It’s recommended that Mats be placed so the mesh faces up, keeping the wire-side-down to help protect it from the shovels.
4.6 INSTALLATION UNDER CONCRETE
1. Ensure that the concrete contractor has installed a solid base of 4” to 8” (102 mm to 203mm) of crushed rock aggregate base and that it is tamped down and ready for the concrete pour.
2 . It is extremely important that the concrete installer does NOT use any heavy equipment, machinery, or vehicles over the exposed Heating Cable. During concrete pours, it is recommended that care be taken to avoid stepping on the factory splice portion of cable, where the hot section (blue) meets the cold section
(black). This is the location of the factory splice. During this process of installing the heating product and pouring concrete, it is the responsibility of the electrician to use a 500 VDC megohmmeter and a multi-meter to keep checking on the
Heating Cables that are currently being worked on top of, to ensure they have not been damaged, and will be ready for action once the concrete slab has cured.
* Do NOT use 500 VDC megger while personal are still in contact with the wet cement.
3. For installations in basements and warehouses that will include building posts, it is strongly recommended that the concrete installer pre-sleeve for the posts to avoid any and all drilling of the concrete. The Heating Cable must be routed around these sleeves or posts to avoid any direct contact with them. Heating
Cables or Mats must not be allowed to pass thru expansion joint locations. It is recommended that lines are spray painted on the finished concrete surface by the electrician to mark off exactly where expansion joints may be located.
It is the responsibility of the electrician and the concrete installer to coordinate their efforts so they avoid saw-cutting or drilling thru Heating Cables that are no longer visible beneath the concrete. Following the proposed installation plan from
WarmlyYours will help to ensure this process goes smoothly.
5
4b. For Single-Pour Installations: The wire mesh or rebar is first placed by the concrete installer or electrician. The electrician then must attach the Heating Cable to the rebar / mesh with plastic zip ties using 3” to 5” (51mm to 127mm) spacing for free-form type cable. Then the rebar / mesh must be propped up with concrete rubble, wire chairs, or brick pavers to the appropriate depth so that Heating
Cable / Mat ends up 2” to 3” (51mm to 76mm) from finished surface and no deeper. Once rebar / mesh / Heating Cable is all propped up, the electrician must route the cold leads(s) thru rigid metal conduit(s) to get back to an accessible junction box (es). Care must be taken so that none of heated section or factory splice enters any conduit. If a slab-mounted sensor will be used, this is the best time for placement. It should be located in an open area, between 2 runs of cable. Separate conduit should be used to protect the low voltage sensor wire and must NOT be shared with any high voltage cold lead from the Heating
Cables / Mats. Once conduits & sensor(s) are placed, the pour of the concrete can be finished in one step. The concrete installer(s) must take care not to walk on the hot-cold splice and to avoid damaging the Heating Cables with shovels and rakes. Mats should be placed mesh facing up, keeping the wire-side-down, to help protect it from the shovels and rakes.
5. The electrician needs to complete final testing of all the Heating Cables / Mats with a multi-meter and a megohmmeter to verify and record that each Heating
Cable has survived the pour of concrete and is ready for action once the concrete is cured. (7 day minimum)
Length 5’ (152cm) min 50’ (1524cm) max
2’ (61cm) or
3’ (91cm)
3"
(8cm)
1/4” (6mm)
Twin-conductor
Heating Cable 20’ (610cm)
Cold Lead
110V / 230V AC SUPPLY
THERMOSTAT
4.7 INSTALLATION OF SLAB HEATING MAT
Use scissors to cut the Mat. NEVER cut the Heating Cable
SENSOR
FLOOR
HEATING
CABLE
SENSOR
HEATING SYSTEM
110V / 230V AC SUPPLY
P N E
THERMOSTAT
Flip / Turn the
Mat suitably
For 90 Degree Turn
FLOOR
HEATING
CABLE
Maintain 3” gap between all cable and mat passes
90˚
3”
Flip the
Mat Reverse
SNOW MELT MAT
Maintain 3” gap between all cable and mat passes
3”
For 180 Degree Turn
Turn the Mat
180˚
For other shapes, detach Cable from Mat to required length and lay only Cable.
Means of attachment may vary project to project.
Maintain same spacing 3” to 5”
3”
Maintain 3” gap between all cable and mat passes
6
10"
(251mm)
20’ (610cm) Cold Lead
Primary Insulation (Fluoropolymer)
Metal Sheath (Copper/Galvanised Steel/Cladded Steel)
Polyester Sheath
Outer Sheath PVC/Pololefin
Heating Conductor (Solid/Multistrand)
5.0 TESTING THE MATS AND CABLE
5.1 TEST ONE: TOTAL CABLE RESISTANCE
(MULTI-METER REQUIRED)
1. Connect one meter clamp to one cold lead (pigtail) inner conductor and the other meter clamp to the other cold lead (pigtail) inner conductor.
2. Test in accordance with the meter manufacturer’s instructions and record this ohm value on the warranty card on last page.
3. Total nominal cable resistance information is found on the CSA label, the bill of materials and Appendix A and Appendix B, or can be obtained by calling your
WarmlyYours Account Manager. Actual reading should be within 10% of the cable resistance.
4. Record measured values on the warranty card on last page. Perform this test before, during and after installation of the Heating Cables.
5. Please be sure that you write in the full part number of the Cable or Mat next to your results.
5.2 TEST TWO & THREE: INSULATION RESISTANCE
(MEGOHMMETER REQUIRED)
1. Connect one meter clamp to the cold lead (pigtail) inner conductor and the other meter clamp to the yellow/green (ground) of the Heating Cable.
2. Test in accordance with the meter manufacturer’s instructions. Recommended meter is a 500 VDC megohmmeter.
3. Megohmmeter reading should read “infinite”.
4. Record measured values on the warranty card on last page. Perform this test before, during and after installation of the Heating Cables.
5. Duplicate test using inner conductor.
6.0 WARRANTY
WarmlyYours provide a warranty for the Heating Cables for a period of 10 years from date of purchase, for the material and workmanship under normal operating conditions.
In case of defective material, WarmlyYours obligation will be limited to the repair or supply of new material, free of charge to the customer.
The warranty does not cover installations made by unqualified persons or faults caused by incorrect design by others / misuse / damage caused by others / damage in transit / incorrect installation and any other subsequent damage that may occur. Costs related to repair / replacement will be fully chargeable to the customer if the damage is due to of any of the above reasons.
WarmlyYours is under no circumstances liable for consequential damages or losses including without limitations the loss or profit arising from any cause whatsoever. The guarantee is a material warranty only and does not cover field labor.
The warranty is void if there is any payment default and if data is not filled in attached warranty card.
TEST #1
Ohms Test with
Multimeter
Core
Core
TEST #2
Insulation Ohms with
500 VDC megger
(Infinite is good value)
Ground
Core
TEST #3
Insulation Ohms with
500 VDC megger
(Infinite is good value)
Ground Core
WARNING
Heating cable may hold a charge after the 500 VDC tests. Allow time for charge to dissipate before handling the heating cable afterward.
Ground Black
Yellow or Red
Yellow or Red
7
7.0 APPENDIX A:
WARMLYYOURS SLAB HEATING MATS (SUITABLE FOR CONCRETE)
Part #
WSHM-120-15011
WSHM-120-15016
WSHM-120-15022
WSHM-120-03017
WSHM-120-15036
WSHM-120-15040
WSHM-120-03021
WSHM-120-03025
WSHM-120-15056
WSHM-120-03029
WSHM-240-15064
WSHM-240-15070
WSHM-240-03040
WSHM-240-15085
WSHM-240-03044
WSHM-240-15095
WSHM-240-03048
WSHM-240-03052
WSHM-240-15112
WSHM-240-03056
WSHC-120-00057
WSHC-120-00082
WSHC-120-00112
WSHC-120-00172
WSHC-120-00182
WSHC-120-00202
WSHC-120-00252
WSHC-240-00323
WSHC-240-00353
WSHC-240-00402
WSHC-240-00443
WSHC-240-00483
WSHC-240-00523
WSHC-240-00563
Size (ft/m)
1.5' X 11' (0.46 x 3.35m)
1.5' X 16' (0.46 x 4.88m)
1.5' X 22' (0.46 x 6.71m)
3.0' X 17' (0.91 x 5.18m)
1.5' X 36' (0.46 x 10.97m)
1.5' X 40' (0.46 x 12.19m)
3.0' X 21' (0.91 x 6.40m)
3.0' X 25' (0.91 x 7.62m)
1.5' X 56' (0.46 x 17.07m)
3.0' X 29' (0.91 x 8.84m)
1.5' X 64' (0.46 x 19.51m)
1.5' X 70' (0.46 x 21.34m)
3.0' X 40' (0.91 x 12.19m)
1.'5 X 85' (0.46 x 25.91m)
3.0' X 44' (0.91 x 13.41m)
1.5' X 95' (0.46 x 28.96m)
3.0' x 48' (0.91 x 14.63m)
3.0' x 52' (0.91 x 15.85m)
1.5' X 112' (0.46 x 34.14m)
3.0' X 56' (0.91 x 17.07m)
120
240
240
240
240
120
240
240
240
120
120
120
120
120
Voltage
120
120
120
120
120
240
240
120
120
120
120
120
240
240
240
240
240
240
240
240
57' (17m)
82' (25m)
112' (34m)
172' (53m)
182' (56m)
202' (62m)
252' (77m)
323' (98m)
353' (108m)
402' (123m)
443' (135m)
483' (147m)
523' (159m)
563' (172m)
Area (ft 2 /m 2 )
16.5 (1.53m
2 )
24.0 (2.23m
2 )
33.0 (3.07m
2 )
51.0 (4.73m
2 )
54.0 (5.02m
2 )
60.0 (5.57m
2 )
63.0 (5.85m
2 )
75.0 (6.97m
2 )
84.0 (7.80m
2 )
87.0 (8.09m
2 )
96.0 (8.92m
2 )
105.0 (9.75m
2 )
120.0 (11.15m
2 )
127.5 (11.85m
2 )
132 (12.26m
2 )
142.5 (13.24m
2 )
144.0 (13.38m
2 )
156.0 (14.49m
2 )
168 (15.61m
2 )
168.0 (15.61m
2 )
APPENDIX B:
WARMLYYOURS SLAB HEATING CABLES (SUITABLE FOR CONCRETE)
Part # Voltage Cable Length Total Ohms
43.64
30.00
21.82
14.12
13.33
12.00
9.60
30.00
27.43
24.00
21.82
20.00
18.46
17.14
Cable Length (ft/m)
57.15 (17.42m)
82.22 (25.06m)
112.27 (34.22m)
172.24 (52.50m)
182.45 (55.61m)
202.49 (61.72m)
212.30 (64.71m)
252.36 (76.92m)
282.71 (86.17m)
292.42 (89.13m)
322.80 (98.39m)
352.89 (107.56m)
402.59 (122.71m)
428.08 (130.48m)
442.65 (134.92m)
478.22 (145.76m)
482.71 (147.13m)
522.77 (159.34m)
563.42 (171.73m)
562.83 (171.55m)
Total Watts
330
480
660
1,020
1,080
1,200
1,500
1,920
2,100
2,400
2,640
2,880
3,120
3,360
Total Ohms
43.64
30.00
21.82
14.12
13.33
12.00
11.43
9.60
8.57
8.28
30.00
27.43
24.00
22.59
21.82
20.21
20.00
18.46
17.14
17.14
Watts/Ft
5.79 (19W/m)
5.85 (19W/m)
5.89 (19W/m)
5.93 (19W/m)
5.93 (19W/m)
5.94 (19W/m)
5.95 (20W/m)
5.94 (19W/m)
5.95 (20W/m)
5.97 (20W/m)
5.96 (20W/m)
5.96 (20W/m)
5.97 (20W/m)
5.97 (20W/m)
Total Watts
330
480
660
1,020
1,080
1,200
1,260
1,500
1,680
1,740
1,920
2,100
2,400
2,550
2,640
2,850
2,880
3,120
3,360
3,360
8
Amps
2.75
4.00
5.50
8.50
9.00
10.00
12.50
8.00
8.75
10.00
11.00
12.00
13.00
14.00
Watts/ft 2 (W/m 2 )
20 (215W/m2)
20 (215W/m2)
20 (215W/m2)
20 (215W/m2)
20 (215W/m2)
20 (215W/m2)
20 (215W/m2)
20 (215W/m2)
20 (215W/m2)
20 (215W/m2)
20 (215W/m2)
20 (215W/m2)
20 (215W/m2)
20 (215W/m2)
20 (215W/m2)
20 (215W/m2)
20 (215W/m2)
20 (215W/m2)
20 (215W/m2)
20 (215W/m2)
Amps
10.00
10.50
12.50
14.00
14.50
8.00
8.75
2.75
4.00
5.50
8.50
9.00
10.00
10.63
11.00
11.88
12.00
13.00
14.00
14.00
WHCA heater run
2” to 3”(51mm to 76mm) of finished asphalt.
Wire mesh above or below Heating Cables
1.5” to 2” (38mm to 51mm) of base/primer asphalt
WHCA heater run
2” to 3”(51mm to 76mm) of finished asphalt.
4” to 8” (102mm to 203mm) of crushed aggregate
Wire mesh above or below Heating Cables
3” (76mm)
Spacing
1.5” to 2” (38mm to 51mm) of base/primer asphalt
APPENDIX C:
4” to 8” (102mm to 203mm) of crushed aggregate
CROSS-SECTION OF INDOOR SLAB HEATING CABLE IN CONCRETE (WITH NO FLOOR COVERING)
3” (76mm)
Spacing
Slab heater run
3” (76mm)
Spacing
Slab heater run
Concrete Block or Metal Chairs
3” (76mm)
Spacing
Heating Cable run (tied to the rebar or wire mesh with zip ties)
2” to 3” (51mm to 76mm) of finished concrete
Rebar or wire mesh supported by bricks or metal chairs
2” to 3” (51mm to 76mm) of concrete
2” insulation ( polystyrene or better ) must be added on top
Rebar or wire mesh supported by bricks or metal chairs
2” insulation ( polystyrene or better ) must be added on top before the base concrete layer.
Concrete Block or Metal Chairs
8” to 12” (203mm to 305mm) of crushed rock aggregate base
APPENDIX D:
Slab heater run
5” (127mm)
Spacing
Slab heater run
Concrete Block or Metal Chairs
5” (127mm)
Spacing
Concrete Block or Metal Chairs
2” to 3” (51mm to 76mm) of finished concrete
Rebar or wire mesh supported by bricks or metal chairs
2” to 3” (51mm to 76mm) of base/concrete
2” insulation ( polystyrene or better ) must be added on top of the sand layer, before the base concrete layer.
2” to 3” (51mm to 76mm) of finished concrete
Rebar or wire mesh supported by bricks or metal chairs
2” insulation ( polystyrene or better ) must be added on top of the sand layer, before the base concrete layer.
8” to 12” (203mm to 305mm) of crushed rock aggregate base
WHCA heater run
WHCA heater run
Brick and Stone Pavers must NOT be any thicker than 2.5” (63.5mm).
1” to 2” (51mm to 76mm) of finished mortar
9
Rebar or wire mesh staked to aggregrate base
Brick and Stone Pavers must NOT be any thicker than 2.5” (63.5mm).
1” to 2” (51mm to 76mm) of finished mortar
4” to 8” (102mm to 203mm) of crushed rock aggregate base
Rebar or wire mesh staked to aggregrate base
3” (76mm)
Spacing
4” to 8” (102mm to 203mm) of crushed rock aggregate base
3” (76mm)
Spacing
10
2.5” in (6.3cm) maximum thickness brick or concrete paver
1.5” sand, stone dust or mortar
2” (5 cm) 2.5” in (6.3cm) maximum thickness brick or concrete paver
1.5” sand, stone dust or mortar
8”-12” crushed rock aggregate
2” (5 cm)
Level of heating cable
3” (7.6 cm)
Plastic tie wrap
4 in (10) or 6 in (15) square 10 gauge wire mesh
Level of heating cable
3” (7.6 cm) concrete wall
Junction box mounted on
4 in (10) or 6 in (15) square 10 gauge wire mesh connector)
Cold lead
Expansion joint concrete wall
Junction box mounted on inside wall connector) cable
Hot/Cold
Cable identification tag joint
(within 3 in (7.5cm) of NPT
Cold lead
Expansion joint
Conduit
Heating cable
Hot/Cold joint
Heated Slab
Conduit
8”-12” crushed
APPENDIX E:
Plastic tie wrap
Conduit
Conduit
APPENDIX F:
3” gap
3” gap
Right hot/cold joints 6 in (15 cm) apart and 6 in (15 cm) from slab edge
Right hot/cold joints 6 in (15 cm) apart
End hot/cold joints installed on slab cold joints stalle slab edge hot/cold joints installed on slab cold joints stalle slab edge hot/cold joints bunched
Wrong hot/cold joints bunched
End
Cold lead is in the conduit
Thermostat / Relay / or splice box
J
4” of cold lead shall be buried directly in concrete
Factory splice buried in concrete
Thermostat / Relay / or splice box
J
4” of cold lead shall be buried directly in concrete
Factory splice buried in concrete
All Blue section of cable on mesh is buried in concrete
Cold leads protected with 1-1/2in (3.8cm) minimum nonmetallic conduit where they emerge from slab
2” to 3” (51mm to 76mm) of finished concrete
Wire mesh with heating cable
2” to 3” (51mm to 76mm) of concrete
2” polystyrene insulation
Corner rounded off to prevent cable damage
Cold leads protected with 1-1/2in (3.8cm) minimum nonmetallic conduit where they emerge from slab
Conduit for slab temperature sensor
Corner rounded off to prevent cable damage
1.2 in (1.3 cm) wide steel prepunched strapping
Cable must be at least 4 in
(10 cm) from rail post
Cable must be at least 4 in
(10 cm) from edge
Factory Splice
Conduit for heating cable cold lead protrudes into bottom of slab only
10
2” to 3” (51mm to 76mm) of finished concrete
8” to 12” (203mm to 305mm) of crushed rock aggregate base
Wire mesh with heating cable
2” to 3” (51mm to 76mm) of concrete
2” polystyrene insulation
4” thick sand over crushed rock aggregate
8” to 12” (203mm to 305mm) of crushed rock aggregate base
Factory Splice
Conduit for heating cable cold lead protrudes into bottom of slab only
1.2 in (1.3 cm) wide steel prepunched strapping
Cable must be at least 4 in
(10 cm) from rail post
Cable must be at least 4 in
(10 cm) from edge
APPENDIX G:
WIRING DIAGRAM
For 120V & 240V Slab Heating Products with nSpire Touch Wi-Fi (UWG4), nSpire Touch (UDG4), nHance (UDG), nTrust (UTN4), nJoin (USG)
(CONDUIT SIZE AS PER INSTALLER)
120/240 VAC
BREAKER PANEL
120/240V 120V/240V
THERMOSTAT
15 AMPS MAX
120/240V CIRCUITS
J-BOX
120/240V CIRCUITS
HEATER CABLE PIGTAIL COLD LEADS TO BE TAKEN
THROUGH 3/4” (19MM) RIGID METAL CONDUIT, OR
OTHER APPROVED MEANS, BACK TO J-BOXES.
LOW VOLTAGE
REAR OF THE BASE or
YELLOW 120V
HOUSE GROUND
HOT (240V) or
NEUTRAL (120V)
HOT
HEATER MAT/CABLE
HEATER MAT/CABLE
HEATER MAT/CABLE
SLAB TEMP SENSOR PROBE TO BE
ENCLOSED IN METAL CONDUIT THAT IS
CAPPED OFF, BETWEEN TWO PASSES OF
HEAT CABLE.
FRONT OF THE BASE MATS OR CABLES THAT
TOTAL LESS THAN 15 AMPS
SLAB TEMP SENSOR PROBE TO BE
ENCLOSED IN METAL CONDUIT THAT IS
CAPPED OFF, BETWEEN TWO PASSES OF
HEAT CABLE.
ENSURE THE SYSTEM
IS GROUNDED
Installation Support • (800) 875-5285 • www.WarmlyYours.com
11
1. MAT/CABLE HAS NO POLARITY
2. DO NOT CUT THE HEATING WIRE
3. ALWAYS TEST OHMS OF HEATING
PRODUCT BEFORE, DURING AND AFTER
INSTALLATION
4. ALWAYS TEST SENSOR AND VERIFY
8-15 K OHM RESISTANCE
5. NEVER INSTALL ELECTRIC FLOOR
HEATING UNDER PERMANENT FIXTURES
6. THE INSTALLATION MUST COMPLY WITH ALL
NATIONAL AND LOCAL ELECTRICAL AND
BUILDING CODES, INCLUDING AUTHORITY
HAVING JURISDICTION.
C
LISTED
US
12
Slab Heat Troubleshooting Guide
SYSTEM NOT WARMING
1. Do an amp draw test on the cables to verify proper operation.
2. Thermostat/control set at too low of a temperature. Adjust to higher temperature.
Because of the nature of slab heat, any changes in slab temperature will take time to accomplish. Slab heat has a much slower reaction time that floor surface heating.
3. Severe Weather.
a. Extreme outdoor conditions may affect slab temperature. Depending on the insulation values under the slab and around the perimeter of the slab, extreme outdoor temperatures can adversely affect the final temperature of the slab.
4. Insufficient watt density. Verify spacing of product vs the design plan.
a. The more distance between the heating wire, the lower the watts per square foot.
The lower the watts per foot, the less satisfactory the performance. This type of system will have to run longer amounts of time, and may not reach desired temperature.
5. Wrong voltage is being supplied to heating cable. a. Is 120V being supplied to a 240V cable?
b. Is the installed product drawing the correct number of amps?
6. Test ohms of heating product a. Verify proper ohms per roll/cable b. Verify no shorts or open circuits
7. Inspect breaker/reset
8. Inspect wiring and connections inside any junction boxes
9. Test ohms of sensor. Call WarmlyYours to verify value.
NO POWER TO HEATING PRODUCT
1. Test ohms of heating cables/rolls a. Verify proper ohms per roll/cable b. Verify no shorts c. Verify no open circuits
2. Inspect breaker/reset a. Verify proper operation b. Verify proper amperage rating per install plan. Recalculate amp load.
c. Verify proper mA rating of breaker d. Replace defective breaker e. Verify use of dual pole breakers for 240V heaters
3. Inspect Relay panel (if present) a. Inspect/replace any faulty wiring b. Inspect/redo/replace any faulty wiring terminals c. Inspect/replace relay d. Verify proper trigger voltage entering relay panel/trigger relay
4. Inoperative Thermostat a. Verify proper connections and power to controller b. Verify proper voltage to controller c. Verify voltage going into controller equals voltage exiting controller d. Verify voltage of heating product matches that supplied to controller.
e. Verify proper setup/programming of controller f. Test/inspect sensor/s for proper operation (see troubleshooting guide for controller) g. Replace defective controller or sensor
5. Wrong voltage is being supplied to heating cable. a. Has 240V been supplied to a 120V product? If so, test ohms of heating product.
b. Do the ohms match the data sheet for installed product?
c. Repair/replace damaged heating product.
6. Inspect wiring between breaker box and control, between control and sensor/s, control and relay panel (if present), and between relay panel and any junction box/es.
7. Inspect heater connections inside all junction boxes.
12
Slab Heat Troubleshooting Guide
MEGA-OHM INSULATION READINGS LOWER THAN SPEC
1. Rain or high humidity present a. Dry wires at test point b. Check for water ingress at junction boxes c. Dry connections and re-test.
2. Physical damage to cold lead, splice, or heating product a. Inspect installation area. Has any work been done in area by trade personnel? Is there visible damage to the concrete slab?
b. Use troubleshooting kit and thermal camera to locate damage c. Repair damaged area of cable d. Replace damaged heating product c. Use troubleshooting kit and thermal camera to locate damage d. Repair damaged area of lead e. Replace damaged heating product
HEATING PRODUCT RESISTANCE INFINITE
1. Open circuit a. Use troubleshooting kit (from conductor to conductor) and thermal camera to locate fault b. Repair damaged area of heating product
HEATING PRODUCT RESISTANCE LOWER THAN SPECIFICATION
1. Conductor shorted to ground somewhere in heating cable a. Test for ohms across conductors to ground and compare to spec for that product b. Use troubleshooting kit (from conductor to ground) and thermal camera to locate fault c. Repair damaged area of heating product
2. Both conductors shorted together somewhere in heating cable a. Test for ohms across conductors and compare to spec for that product b. Use troubleshooting kit (from conductor to conductor) and thermal camera to locate fault c. Repair damaged area of heating product
HEATING PRODUCT RESISTANCE HIGHER THAN SPECIFICATION
1. Conductor shorted to ground somewhere in heating cable a. Test for ohms across conductors to ground and compare to spec for that product b. Use troubleshooting kit (from conductor to ground) and thermal camera to locate fault c. Repair damaged area of heating product
2. Both conductors shorted together somewhere in heating cable a. Test for ohms across conductors and compare to spec for that product b. Use troubleshooting kit (from conductor to conductor) and thermal camera to locate fault c. Repair damaged area of heating product
3. Cold lead damaged a. Inspect exposed coldlead b. Inspect installation area. Has any work been done in area by trade personnel?
Is there visible damage to the concrete, slab, or pavers?
13
HEATING PRODUCT RESISTANCE ZERO
1. Conductor/s shorted to ground at factory splice a. Use troubleshooting kit and thermal camera to locate fault b. Remove factory splice and repair damaged area of heating product c. Contact WarmlyYours for instructions on returning Factory Splice for inspection
RESETTING CIRCUIT BREAKER
1.Test ohms of heating cables/rolls a. Verify proper ohms per roll/cable b. Verify no shorts c. Verify no open circuits d. Use troubleshooting kit and camera to locate fault e. Repair fault
2.Inspect breaker/reset a. Verify proper operation b. Verify proper amperage rating per install plan (re-calculate circuit load) c. Verify proper mA rating of breaker (30 mA GFEP breaker required by code) d. Replace defective breaker e. Verify use of dual pole breakers for 208 & 240V heaters
3.Inspect all connections a. Correct any incorrect wiring at all connections in the power feed
4.Inspect Junction Box/es a. Install drains in boxes if required b. Dry connections and re-connect c. Replace any faulty junction boxes
WarmlyYours Slab Heating Warranty
WarmlyYours, Inc. warrants the WarmlyYours slab heating cables and mats (“the Product”) to be free from defects in materials and workmanship for ten years from the date of purchase, provided that the Product is installed in accordance with the WarmlyYours product installation guide, any special written or oral design or installation guidelines provided by WarmlyYours for the specific project that the Product is intended, the provisions of the National Electric
Code (NEC), and all applicable local building and electrical codes. If the Product is determined to be defective in materials and workmanship, and has not been damaged as a result of misuse, misapplication or improper installation, WarmlyYours will replace the Product or refund the original cost of the Product.
Controls sold under the WarmlyYours name are warranted for two years from date of purchase. Should the control be defective or malfunction, return the control to WarmlyYours and it will be repaired or replaced (at WarmlyYours’ option). The warranty does not cover removal or reinstallation costs. See entire warranty in packaging. Other controls carry their manufacturer’s warranty.
WarmlyYours Inc. assumes no responsibility under this warranty for any damage to the Product prior to or during installation by anyone, including, but not limited to trades people or visitors to the job site, or damage caused as a result of post installation work. Call our toll free number, (800) 875-5285, if you have any questions about installation. The Limited Warranty is null and void if the Product owner or his representative attempts to repair the Product without receiving authorization. Upon notification of an actual or possible problem, WarmlyYours will issue an Authorization to Proceed under the terms of the Limited
Warranty. WarmlyYours reseves the right to void said warranty, if the product owner repairs any heating wire, for any reason.
Warranty Subject to the Following Conditions: 1. The warranty of the slab heating system must be registered by completing and returning the attached
‘WarmlyYours Warranty Registration’ card to WarmlyYours, Inc. within thirty days of date of purchase. Please keep your invoice, as proof of date of purchase will be required in the event of a claim. 2. The slab heating cables or mats must be installed properly under concrete, asphalt or in mortar under pavers 3.
The slab heating system must be electrically grounded and protected by a GFI (Ground Fault Interrupter). 4. The installation must comply with all national and local electrical and building codes, as well as any other applicable statutory requirements. 5. The manufacturer hereby reserves the right to inspect the installation site at any reasonable time. 6. The warranty is not automatically transferred with change of ownership, but the manufacturer may, on application, transfer the warranty for the period remaining. This transfer is solely at the discretion of the manufacturer. 7. The slab heating system should be used strictly in accordance with the following: 7a. Hard wire the slab heating cables and mats to a dedicated circuit. The voltage of the circuit should match the voltage of the slab heating system, and the size of the circuit should be such that the system does not occupy more than 80% of the circuit capacity. 7b. Should you feel no warmth from the surface that the system is installed within 60 minutes, verify that there is power to the control or thermostat. Contact WarmlyYours after verifying that there is power to the system. Under no circumstances should you or anyone else tamper with or attempt to repair the snow melt or slab heating system - this will render the warranty null and void. 7c. Switch the system on and off as you would any conventional electric heater, although timers or thermostats may be used if preferred. 7d. Use reasonable care in the operation of the system. Do not drop heavy articles, pierce or cut the surface that the heating system is installed. 7e. All restrictions and warnings detailed in the installation guide must be strictly followed.
WARMLYYOURS, INC. DISCLAIMS ANY WARRANTY NOT PROVIDED HEREIN, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR
IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. WARMLYYOURS FURTHER DISCLAIMS ANY RESPONSIBILITY FOR SPECIAL,
INDIRECT, SECONDARY, INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARISING FROM OWNERSHIP OR USE OF THIS PRODUCT, INCLUDING
INCONVENIENCE OR LOSS OF USE. THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE FACE OF THIS DOCUMENT. NO AGENT
OR REPRESENTATIVE OF WARMLYYOURS HAS ANY AUTHORITY TO EXTEND OR MODIFY THIS WARRANTY UNLESS SUCH EXTENSION OR
MODIFICATION IS MADE IN WRITING BY A CORPORATE OFFICER.
WarmlyYours Slab Heat Warranty Registration
Thank you for purchasing your new WarmlyYours Slab Heating System. Once the report form is completed, please copy the form and attach a copy to the main breaker box, or give to the homeowner or business owner. Please send a copy to WarmlyYours via mail, FAX at (800) 408-1100, or scan and send via e-mail to: [email protected]
.
HOMEOWNER/JOB LOCATION INFORMATION
Name
Address
City
Order Number
ELECTRICIAN INFORMATION
Company Name
Address
City
Installer Name
State
Phone
ZIP
Phone
State
Job Name
ZIP
PAVING/CONCRETE INSTALLER INFORMATION
Company Name
Address
City
Installer Name
State
Phone
ZIP
Install Date: Installed Under: q Concrete q Asphalt q Pavers q Other If Pavers, thickness of the Paver:___________________ [2.5” (64mm) Max]
Material Depth Below Cable [2” (51mm) Min.]: Material Depth Above Cable [1.5” (38mm) Min.]:
Cable/Mat 1 Cable/Mat 2 Cable/Mat 3 Cable/Mat 4 Cable/Mat 5 Cable/Mat 6
Zone ID
OHM Reading 1 - Before Install
*MegOHM Reading 1 - Before Install
OHM Reading 2 - During Install
*MegOHM Reading 2 - During Install
OHM Reading 3 - After Install
*MegOHM Reading 3 - After Install
PART #
Serial Number - Internal Use Only
QC MEGOHM - Internal Use Only
QC OHM - Internal Use Only
Megohms readings are done across the assembly’s green, ground wire to each conductor separately. Remember to keep a copy of this form with your warranty.
*If at any time a value does not read infinite, please halt installation and contact WarmlyYours at (800) 875-5285.
Installation Support • (800) 875-5285 • www.WarmlyYours.com
ডাউনলোড
বিজ্ঞাপন