VSR-CR
CORROSION RESISTANT VANE TYPE
WATERFLOW ALARM SWITCH
WITH RETARD
UL, CUL and CSFM Listed, CE Marked
Service Pressure: 450 PSI (31 BAR) - UL
Flow Sensitivity Range for Signal:
4-10 GPM (15-38 LPM) - UL
Maximum Surge: 18 FPS (5.5 m/s)
Contact Ratings: Two sets of SPDT (Form C)
10.0 Amps at 125/250VAC
2.0 Amps at 30VDC Resistive
10 mAmps min. at 24VDC
Conduit Entrances: Two knockouts provided for 1/2" conduit.
Individual switch compartments suitable for dissimilar voltages.
Environmental Specifications:
• NEMA 4X/IP66 Rated Enclosure suitable for indoor or outdoor use with factory installed gasket and die-cast housing when used with appropriate conduit fitting.
• Corrosion resistant hardware of 316 stainless steel
• Corrosion resistant powder coated base and saddle
• Temperature Range: 40°F - 120°F, (4.5°C - 49°C) - UL
• Non-corrosive sleeve factory installed in saddle.
Service Use:
Automatic
National Fire Alarm Code
One or two family dwelling
Residential occupancy up to four stories
NFPA-13D
NFPA-13R
NFPA-72
Sprinkler NFPA-13
Specifications subject to change without notice.
3"
3 1/2"
4"
5"
6"
8"
Ordering Information
Nominal Pipe Size
2" DN50
2 1/2" DN65
DN80
-
DN100
-
DN150
DN200
Model
VSR-CR-2
VSR-CR- 2 1/2
VSR-CR-3
VSR-CR-3 1/2
VSR-CR-4
VSR-CR-5
VSR-CR-6
VSR-CR-8
Part Number
1144602
1144625
1144603
1144635
1144604
1144605
1144606
1144608
Optional : Optional: FSBS (Flow Switch Bypass Switch), stock no.
3001006
Cover Tamper Switch Kit, stock no. 0090148
Replaceable Components: Retard/Switch Assembly, stock no. 1029030
• Installation must be performed by qualified personnel and in
accordance with all national and local codes and ordinances.
• Shock hazard. Disconnect power source before servicing. Serious
injury or death could result.
• Risk of explosion. Not for use in hazardous locations. Serious
injury or death could result.
Waterflow switches that are monitoring wet pipe sprinkler systems shall not be used as the sole initiating device to discharge AFFF, deluge, or chemical suppression systems. Waterflow switches used for this application may result in unintended discharges caused by surges, trapped air, or short retard times.
Important: This document contains important information on the installation and operation of the VSR-CR waterflow switches. Please read all instructions carefully before beginning installation. A copy of this document is required by NFPA 72 to be maintained on site.
General Information
The Model VSR-CR is a vane type waterflow switch for use on wet sprinkler systems where external corrosion is a concern. It is UL Listed and CUL Listed for use on a steel pipe; schedules 5 through 40, sizes
2" - 6" and is UL and CUL Listed for use on steel pipe; schedules
10 through 40, sizes 2" thru 8" (50 mm thru 200 mm). See Ordering
Information chart.
The VSR-CR may also be used as a sectional waterflow detector on large systems. The VSR-CR contains two single pole, double throw, snap action switches and an adjustable, instantly recycling pneumatic retard. The switches are actuated when a flow of 10 GPM (38 LPM) or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period.
Enclosure
The VSR-CR switches and retard device are enclosed in a general purpose, die-cast housing. The cover is held in place with two tamper resistant screws which require a special key for removal. A field installable cover tamper switch is available as an option which may be used to indicate unauthorized removal of the cover. See bulletin number 5401103 for installation instructions of this switch.
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-1211/Canada 888-882-1833 • www.pottersignal.com
PRINTED IN USA MFG. #5401601 - REV A
10/20
PAGE 1 OF 4 firealarmresources.com
VSR-CR
CORROSION RESISTANT VANE TYPE
WATERFLOW ALARM SWITCH
WITH RETARD
Installation ( see Fig. 1)
These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they shall be installed on the top side of the pipe where they will be accessible. The device should not be installed within 6" (15 cm) of a fitting which changes the direction of the waterflow or within 24"
(60 cm) of a valve or drain.
NOTE : Do not leave cover off for an extended period of time.
Drain the system and drill a hole in the pipe using a hole saw in a slow speed drill (see Fig. 1). Clean the inside pipe of all growth or other material for a distance equal to the pipe diameter on either side of the hole. Roll the vane so that it may be inserted into the hole; do not bend or crease it. Insert the vane so that the arrow on the saddle points in the direction of the waterflow. Take care not to damage the non-corrosive bushing in the saddle. The bushing should fit inside the hole in the pipe. Install the saddle strap and tighten nuts alternately to required torque
(see the chart in Fig. 1). The vane must not rub the inside of the pipe or bind in any way.
Do not trim the paddle. Failure to follow these instructions may prevent the device from operating and will void the warranty. Do not obstruct or otherwise prevent the trip stem of the flow switch from moving when water flows as this could damage the flow switch and prevent an alarm. If an alarm is not desired, a Flowswitch Bypass Switch should be used (refer to Potter data sheet 5401554), or a qualified technician should disable the alarm system.
Fig. 1
DO NOT LEAVE COVER OFF FOR
AN EXTENDED PERIOD OF TIME
Retard Adjustment
The delay can be adjusted by rotating the retard adjustment knob from
0 to the max setting (60-90 seconds). The time delay should be set at the minimum required to prevent false alarms
TIGHTEN NUTS
ALTERNATELY
MOUNT ON PIPE SO
ARROW ON SADDLE
POINTS IN DIRECTION
OF WATERFLOW
Hole must be drilled perpendicular to the pipe and vertically centered.
Refer to the Compatible Pipe/Installation Requirements chart for size.
Correct Incorrect
DIRECTION OF
WATERFLOW
ROLL PADDLE IN
OPPOSITE DIRECTION
OF WATERFLOW
ADAPTER
50mm
ADAPTER
(Flowing water activates device in one direction only.)
Model
VSR-CR-2
VSR-CR-2 1/2
VSR-CR-2 1/2
VSR-CR-3
VSR-CR-3 1/2
VSR-CR-4
VSR-CR-5
VSR-CR-6
VSR-CR-8
4
5
3
3.5
6
8 inch
2
2.5
-
Nominal Pipe
Size mm
DN50
-
DN65
Nominal Pipe
O.D.
inch mm
2.375
60.3
.065
Lightwall inch mm
1.651
2.875
73.0
.084
3.000
76.1
-
DN80
-
3.500
88.9
.083
4.000 101.6
-
DN100 4.500 114.3 .084
5.563 141.3
-
DN150 6.625 168.3 .115
DN200 8.625 219.1
-
Compatible Pipe/ Installation Requirements
2.134
-
2.108
-
2.134
-
2.921
-
Pipe Wall Thickness
Schedule 10 (UL) Schedule 40 (UL) BS-1387 (LPC) inch mm inch mm inch mm
0.109
0.120
-
0.120
0.120
0.120
0.134
0.134
0.148
2.77
3.05
-
3.05
3.05
3.05
3.40
3.40
3.76
0.154
0.203
-
0.216
0.226
0.237
0.258
0.280
0.322
3.91
5.16
-
5.49
5.74
6.02
6.55
7.11
8.18
0.142
-
0.142
0.157
-
0.177
-
0.197
0.248
3.6
-
3.6
NOTE : For copper or plastic pipe use Model VSR-CF.
4.0
-
4.5
-
5.0
6.3
DWG# 1146-1F inch
Hole Size
1.25 + .125/-
.062
2.00 ± .125
mm
33.0 ± 2.0
50.8 ± 2.0
PRINTED IN USA MFG. #5401601 - REV A
10/20
20mm ±2mm MAX.
DN50 ONLY
USE (2) 5180162 ADAPTERS AS SHOWN ABOVE
U-Bolt Nuts
Torque ft-lb n-m
20 27
PAGE 2 OF 4 firealarmresources.com
VSR-CR
CORROSION RESISTANT VANE TYPE
WATERFLOW ALARM SWITCH
WITH RETARD
Fig. 2
To remove knockouts: Place screwdriver at inside edge of knockouts, not in the center.
Fig. 3
Break out thin section of cover when wiring both switches from one conduit entrance.
Fig. 4 Switch Terminal Connections Clamping
Plate Terminal
DWG 1146-4
Do not drill into the base as this creates metal shavings which can create electrical hazards and damage the device. Drilling voids the warranty.
Fig. 5 Typical Electrical Connections
Notes:
1. The Model VSR-CR has two switches, one can be used to operate a central station, proprietary or remote signaling unit, while the other contact is used to operate a local audible or visual annunciator.
2. For supervised circuits, see “Switch Terminal Connections” drawing and warning note (Fig. 4).
An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire become dislodged from under the terminal. Failure to sever the wire may render the device inoperable risking severe property damage and loss of life.
Do not strip wire beyond 3/8" of length or expose an uninsulated conductor beyond the edge of the terminal block. When using stranded wire, capture all strands under the clamping plate.
CONNECTOR
BELL
NEUTRAL FROM
BREAKER NEUTRAL FROM BELL
BREAKER
LINE FROM BREAKER
EOL (End Of Line Resistor)
NOTE:
When connecting to a UL Listed control panel, use the panel’s resistor value for circuit supervision.
Testing
The frequency of inspection and testing for the Model VSR-CR and its associated protective monitoring system shall be in accordance with applicable
NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).
If provided, the inspector’s test valve shall always be used for test purposes. If there are no provisions for testing the operation of the flow detection device on the system, application of the VSR-CR is not recommended or advisable.
A minimum flow of 10 GPM (38 LPM) is required to activate this device.
Advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing instructions.
Fig. 6 Mounting Dimensions
3.50 in
(89.0 mm)
2.00 in
(50.8 mm)
5.56 in
(141.2 mm)
Fig. 7
GREEN GROUND
SCREWS
2.34 in
(59.4 mm)
SS U-BOLT NUT
SS U-BOLT WASHER
POWDER COATEDPIPE SADDLE
PIPE DIA.
+ 5.25 in
(+ 133.4 mm)
PIPE
PLASTIC PADDLE
SS U-BOLT
PRINTED IN USA
DWG. 1146-14
NOMINAL PIPE DIA. +3.240 in (+82.3 MM) FOR DN 50 2 in
NOMINAL PIPE DIA. +2.740 in (+69.6 MM) FOR DN 65 2.5 in
NOMINAL PIPE DIA. +2.800 in (+71.1 MM) FOR DN 80 - DN 200 3-8 in
MFG. #5401601 - REV A
10/20 firealarmresources.com
DWG 1146-15
PAGE 3 OF 4
VSR-CR
CORROSION RESISTANT VANE TYPE
WATERFLOW ALARM SWITCH
WITH RETARD
Maintenance
Inspect detectors monthly. If leaks are found, replace the detector. The VSR-CR waterflow switch should provide years of trouble-free service.
The retard and switch assembly are easily field replaceable. In the unlikely event that either component does not perform properly, please order replacement retard switch assembly stock #1029030 (see Fig. 8). There is no maintenance required, only periodic testing and inspection.
Retard/Switch Assembly Replacement (See Fig. 8)
The Retard/Switch Assembly is field-replaceable without draining the system or removing the waterflow switch from the pipe
1. Make sure the fire alarm zone or circuit connected to the waterflow switch is bypassed or otherwise taken out of service.
2. Disconnect the power source for local bell (if applicable).
3. Identify and remove all wires from the waterflow switch.
4. Remove the (2) mounting screws holding retard/switch assembly to the base. Do not remove the (2) retard housing screws.
5. Remove the retard assembly by lifting it straight up over the tripstem.
6. Install the new retard assembly. Make sure the locating pins on the retard/switch assembly fit into the locating pin bosses on the base.
7. Re-install the (2) original mounting screws.
8. Reconnect all wires. Perform a flow test and place the system back in service.
Fig. 8 REMOVE (2) ORIGINAL MOUNTING
SCREWS HOLDING RETARD/SWITCH
ASSEMBLY TO BASE
BREAK OUT THIN SECTION OF COVER
WHEN WIRING BOTH SWITCHES
FROM ONE CONDUIT ENTRANCE.
(2) ORIGINAL MOUNTING
SCREWS
RETARD/SWITCH ASSEMBLY
DO NOT REMOVE
(2) RETARD HOUSING
SCREWS
(2) LOCATING PINS
(2) LOCATING PIN
BOSSES IN BASE
POWDER COATED BASE
DWG# 1146-10
Removal of Waterflow Switch
• To prevent accidental water damage, all control valves should be shut tight and the system completely drained before waterflow detectors are or
• Turn off electrical power to the detector, then disconnect wiring.
• nuts U-bolts.
• Gently lift the saddle far enough to get your fingers under it. With your fingers, roll the vane so it will fit through the hole while continuing
to lift the waterflow detector saddle.
• Lift detector clear of pipe.
PRINTED IN USA PAGE 4 OF 4 MFG. #5401601 - REV A
10/20 firealarmresources.com