Autonics TK Series Simultaneous Heating and Cooling Output PID Temperature Controllers Instruction manual
Autonics TK Series is a range of PID temperature controllers offering precise temperature control with simultaneous heating and cooling output. With an intuitive user interface and advanced features, the TK Series is suitable for various industrial applications requiring accurate temperature regulation.
Advertisement
Advertisement
-|Transparent Guide|-
Simultaneous Heating&Cooling Output PID
Temperature Controllers
TK Series
INSTRUCTION MANUAL
TCD210240AB
Thank you for choosing our Autonics product.
Read and understand the instruction manual and manual thoroughly before using the product.
For your safety, read and follow the below safety considerations before using.
For your safety, read and follow the considerations written in the instruction manual, other manuals and Autonics website.
Keep this instruction manual in a place where you can find easily.
The specifications, dimensions, etc are subject to change without notice for product improvement Some models may be discontinued without notice.
Follow Autonics website for the latest information.
Safety Considerations
• Observe all ‘Safety Considerations’ for safe and proper operation to avoid hazards.
• symbol in dicates caution due to special circumstances in which hazards may occur.
Warning
Failure to follow instructions may result in serious injury or death
01. Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss.(e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.)
Failure to follow this instruction may result in personal injury, economic loss or fire.
02. Do not use the unit in the place where flammable/explosive/corrosive gas, high humidity, direct sunlight, radiant heat, vibration, impact or salinity may be present.
Failure to follow this instruction may result in explosion or fire.
03. Install on a device panel to use.
Failure to follow this instruction may result in electric shock.
04. Do not connect, repair, or inspect the unit while connected to a power source.
Failure to follow this instruction may result in fire or electric shock.
05. Check ‘Connections’ before wiring.
Failure to follow this instruction may result in fire.
06. Do not disassemble or modify the unit.
Failure to follow this instruction may result in fire or electric shock.
Caution
Failure to follow instructions may result in injury or product damage
01. When connecting the power input and relay output, use AWG 20 (0.50 mm 2 ) cable or over, and tighten the terminal screw with a tightening torque of 0.74 to 0.90 N m.
When connecting the sensor input and communication cable without dedicated cable, use AWG 28 to 16 cable and tighten the terminal screw with a tightening torque of 0.74 to 0.90 N m.
Failure to follow this instruction may result in fire or malfunction due to contact failure.
02. Use the unit within the rated specifications.
Failure to follow this instruction may result in fire or product damage
03. Use a dry cloth to clean the unit, and do not use water or organic solvent.
Failure to follow this instruction may result in fire or electric shock.
04. Keep the product away from metal chip, dust, and wire residue which flow into the unit.
Failure to follow this instruction may result in fire or product damage.
Cautions during Use
• Follow instructions in ‘Cautions during Use’. Otherwise, it may cause unexpected accidents.
• Check the polarity of the terminals before wiring the temperature sensor. For RTD temperature sensor, wire it as 3-wire type, using cables in same thickness and length.
For thermocouple (TC) temperature sensor, use the designated compensation wire for extending wire.
• Keep away from high voltage lines or power lines to prevent inductive noise. In case installing power line and input signal line closely, use line filter or varistor at power line and shielded wire at input signal line. Do not use near the equipment which generates strong magnetic force or high frequency noise.
• Do not apply excessive power when connecting or disconnecting the connectors of the product.
• Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the power.
• Do not use the unit for other purpose (e.g. voltmeter, ammeter), but temperature controller.
• When changing the input sensor, turn off the power first before changing. After changing the input sensor, modify the value of the corresponding parameter.
• 24 VACᜠ, 24-48 VDCᜡ power supply should be insulated and limited voltage/current or
Class 2, SELV power supply device.
• Do not overlapping communication line and power line. Use twisted pair wire for communication line and connect ferrite bead at each end of line to reduce the effect of external noise.
• Make a required space around the unit for radiation of heat. For accurate temperature measurement, warm up the unit over 20 min after turning on the power.
• Make sure that power supply voltage reaches to the rated voltage within 2 sec after supplying power.
• Do not wire to terminals which are not used.
• This unit may be used in the following environments.
- Indoors (in the environment condition rated in ‘Specifications’)
- Altitude Max. 2,000 m
- Pollution degree 2
- Installation category II
Ordering Information
This is only for reference, the actual product does not support all combinations.
For selecting the specified model, follow the Autonics website .
T K 4 ❶ - ❷ ❸ ❹ ❺
❶ Size
N: DIN W 48 × H 24 mm
SP: DIN W 48 × H 48 mm (11 pin plug type )
S: DIN W 48 × H 48 mm
M: DIN W 72 × H 72 mm
W: DIN W 96 × H 48 mm
H: DIN W 48 × H 96 mm
L: DIN W 96 × H 96 mm
❷ Option in/output
Size: N
PN OUT2
1
Normal type 01)
Function
Alarm 1 + CT input
Heating & Cooling Alarm 2
2
D
R
Normal type
Normal type
Normal type
Alarm 1 + Alarm 2
Alarm 1 + Digital input 1/2
Heating & Cooling Digital input 1/2
Alarm 1+Transmission output
Heating & Cooling Transmission output
T
Normal type
Alarm output 1 + RS485 communication
Heating & Cooling RS485 communication
Size: SP
PN Function
1 Alarm 1
❸ Power supply
2: 24 VACᜠ 50/60 Hz, 24-48 VDCᜡ
4: 100-240 VACᜠ 50/60 Hz
❹ OUT1 Control output
R: Relay
S: SSR drive
C: Selectable current or SSR drive output
❺ OUT2 Control output
N: Normal type
[No OUT2 (Heating or Cooling)]
R: Heating & Cooling type
[Relay output] 03)
C: Heating & Cooling type
[Selectable current or SSR drive output] 04)
Size: S, M, W, H, L
PN Function
1 Alarm 1
2 Alarm 1 + Alarm output 2
R Alarm 1 + Transmission output
T Alarm 1 + RS485 communication
A Alarm 1 + Alarm 2 + Transmission output
B Alarm 1 + Alarm 2 + RS485 communication
D Alarm 1 + Alarm 2 + Digital input 1/2 02)
01) The CT input model of TK4N can be selected only in the normal type model with alarm output 1. (except
TK4SP)
02) Only for TK4S-D, OUT2 output terminal is used as DI-2 input terminal.
03) When operating mode is heating or cooling control, OUT2 can be used as alarm output 3 (except TK4N).
04) When operating mode is heating or cooling control, OUT2 can be used as transmission output 2.
Manual
For proper use of the product, refer to the manuals and be sure to follow the safety considerations in the manuals.
Download the manuals from the Autonics website.
Software
Download the installation file and the manuals from the Autonics website.
■
DAQMaster
DAQMaster is comprehensive device management program. It is available for parameter setting, monitoring.
Sold Separately
• 11 pin socket: PG-11, PS-11 (N) • Current transformer (CT)
• Terminal protection cover: RSA / RMA / RHA / RLA Cover
• Communication converter: SCM Series
Specifications
Series
Power supply
Power consumption
AC type
AC/DC type -
TK4N TK4SP
100 - 240 VACᜠ 50/60 Hz ±10%
AC type
AC/DC type -
≤ 6 VA
Unit weight (packaged)
≈ 70 g
(≈ 140 g)
TK4S TK4M
24 VACᜠ 50/60 Hz ±10%, 24-48 VDCᜡ ±10%
≤ 8 VA
AC: ≤ 8 VA, DC ≤ 5W
≈ 85 g
(≈ 130 g)
≈ 105 g
(≈ 150 g)
≈ 140 g
(≈ 210 g)
Series
Power supply
Power consumption
TK4W TK4H
100 - 240 VACᜠ 50/60 Hz ±10%
TK4L
AC type
AC/DC type 24 VACᜠ 50/60 Hz ±10%, 24-48 VDCᜡ ±10%
AC type ≤ 8 VA
AC/DC type AC: ≤ 8 VA, DC ≤ 5W
Unit weight (packaged) ≈ 141 g (≈ 211 g) ≈ 141 g (≈ 211 g) ≈ 198 g (≈ 294 g)
Sampling period
Input specification
Option input
Control output
Alarm output
Vibration
Insulation resistance
Noise immunity
Memory retention
Ambient temperature
Ambient humidity
Protection structure
Accessory
Approval
CT input
Digital input
Relay
SSR
Current
Relay
Option output
Transmission
RS485 comm.
Display type
Control type
Heating, Cooling
Heating &
Cooling
Hysteresis
Proportional band (P)
Integral time (I)
Derivative time (D)
Control cycle (T)
Manual reset
Relay life cycle
Mechanical
Electrical
Dielectric strength
Insulation type
50 ms
Refer to 'Input Type and Using Range'
• 0.0-50.0 A (primary current measurement range)
• CT ratio: 1/1,000
• Measurement accuracy: ±5% F.S. ±1digit
• Contact - ON: ≤ 2 kΩ, OFF: ≥ 90 kΩ
• Non contact - residual voltage ≤ 1.0 V, leakage current ≤ 0.1 mA
• Outflow current: ≈ 0.5 mA per input
250 VACᜠ 3 A, 30 VDCᜡ 3 A 1a
11 VDCᜡ±2 V, ≤ 20 mA
DC 4-20 mA or DC 0-20 mA (parameter), Load resistance: ≤ 500 Ω
AL1, AL2: 250 VACᜠ 3 A 1a
• TK4N AL2: 250 VACᜠ 0.5 A 1a (≤ 125 VA)
DC 4 - 20 mA (Load resistance: ≤ 500 Ω, Output accuracy: ±0.3%
F.S.)
Modbus RTU
7 segment (red, green, yellow ), LED type
ON/OFF, P, PI, PD, PID Control
• Thermocouple, RTD: 1 to 100 (0.1 to 100.0) ℃/℉
• Analog: 1 to 100 digit
0.1 to 999.9 ℃/℉ (0.1 to 999.9%)
0 to 9,999 sec
0 to 9,999 sec
• Relay output, SSR
0.0 to 100.0% operations)
50/60 Hz for 1 min drive output: 0.1 to 120.0 sec
• Selectable current or SSR drive
OUT1/2: ≥ 5,000,000 operations
≥ 100,000 operations
output: 1.0 to 120.0 sec
AL1/2: ≥ 20,000,000 operations (TK4H/W/L: ≥ 5,000,000
Between power source terminal and input terminal: 2,000 VACᜠ
0.75 mm amplitude at frequency of 5 to 55 Hz (for 1 min) in each X,
Y, Z direction for 2 hours
≥ 100 MΩ (500 VDCᜡ megger)
±2 kV square shaped noise by noise simulator (pulse width: 1 ㎲ )
R-phase, S-phase
≈ 10 years (non-volatile semiconductor memory type)
-10 to 50 ℃, storage: -20 to 60 ℃ (no freezing or condensation)
35 to 85%RH, storage: 35 to 85%RH (no freezing or condensation)
IP65 (Front panel , IEC standards)
• TK4SP: IP50 (Front panel , IEC standards)
Double insulation or reinforced insulation (mark: ▱, dielectric strength between the measuring input part and the power part: 2 kV)
Bracket, Terminal protection cover (TK4N)
ᜢ ᜧ ᜫ
Communication Interface
■ RS485
Comm. protocol
Connection type
Application standard
Maximum connection
Synchronous method
Comm. Method
Comm. effective range
Comm. speed
Response time
Start bit
Data bit
Parity bit
Stop bit
EEPROM life cycle
Modbus RTU
RS485
EIA RS485 compliance with
31 units ( address : 01 to 99)
Asynchronous
Two-wire half duplex
≤ 800 m
2,400 / 4,800 / 9,600 (default) / 19,200 / 38,400 bps (parameter)
5 to 99 ms (default: 20 ms)
1 bit (fixed)
8 bit (fixed)
None (default), Odd, Even
1 bit, 2 bit (default)
≈ 1,000,000 operations (Erase / Write)
Input Type and Using Range
The setting range of some parameters is limited when using the decimal point display.
Input type
Thermo
-couple
RTD
Analog
K (CA)
J (IC)
E (CR)
T (CC)
B (PR)
R (PR)
S (PR)
N (NN)
C (TT)
G (TT)
L (IC)
U (CC)
01)
02)
Platinel II
Cu50 Ω
Cu100 Ω
JPt100 Ω
DPt50 Ω
DPt100 Ω
Nickel120 Ω 1
0 to 10 V
-
-
0.1
0.1
1
0.1
0 to 5 V
1 to 5 V
0 to 100 mV
0 to 20 mA
4 to 20 mA -
-
-
-
1
0.1
0.1
1
1
0.1
1
0.1
1
1
1
1
1
1
1
0.1
1
0.1
1
0.1
Decimal point
1
0.1
Display
KCaH
KCaL
JIcH
JIcL
ECrH
ECrL
TCcH
TCcL
B PR
R PR
S PR
N NN
C TT
G TT
LIcH
LIcL
UCcH
UCcL
PLII
CU 5
CU10
JPtH
JPtL
DPT5
DPtH
DPtL
NI12
AV1
AV2
AV3
AMV1
AMA1
AMA2
Using range (℃) Using range (℉)
-200 to 1,350
-199.9
to 999.9
-200 to 800
-199.9
to 800.0
-200 to 800
-199.9
to 800.0
-200 to 400
-199.9
to 400.0
0 to 1,800
0 to 1,750
0 to 1,750
-200 to 1,300
0 to 2,300
0 to 2,300
-200 to 900
-199.9
to 900.0
-328 to 2,463
-199.9
to 999.9
-328 to 1,472
-199.9
to 999.9
-328 to 1,472
-199.9
to 999.9
-328 to 752
-199.9
to 752.0
32 to 3,272
32 to 3,182
32 to 3,182
-328 to 2,372
32 to 4,172
32 to 4,172
-328 to 1,652
-199.9
to 999.9
-200 to 400
-199.9
to 400.0
0 to 1,390
-199.9
to 200.0
-199.9
to 200.0
-200 to 650
-199.9
to 650.0
-199.9
to 600.0
-328 to 752
-199.9
to 752.0
32 to 2,534
-199.9
to 392.0
-199.9
to 392.0
-328 to 1,202
-199.9
to 999.9
-199.9
to 999.9
-200 to 650
-199.9
to 650.0
-80 to 200
-328 to 1,202
-199.9
to 999.9
-112 to 392
0 to 10 V
0 to 5 V
1 to 5 V
0 to 100 mV
0 to 20 mA
4 to 20 mA
01) C (TT): Same as existing W5 (TT) type sensor
02) G (TT): Same as existing W (TT) type sensor
• Permissible line resistance per line: ≤ 5 Ω
■
Display accuracy
Input type Using temperature Display accuracy
(PV ±0.3% or ±1 ℃ higher one) ±1-digit
Thermo
-couple
RTD
At room temperature
(23℃ ±5 ℃)
Out of room temperature range
• Thermocouple K, J, T, N, E below -100 ℃ and L, U, PLII, RTD Cu50 Ω,
DPt50 Ω: (PV ±0.3% or ±2 ℃ higher one) ±1-digit
• Thermocouple C, G and R, S below 200 ℃:
(PV ±0.3% or ±3 ℃ higher one) ±1-digit
• Thermocouple B below 400 ℃: There is no accuracy standards
(PV ±0.5% or ±2 ℃ higher one) ±1-digit
• RTD Cu50 Ω, DPt50 Ω: (PV ±0.5% or ±3 ℃ higher one) ±1-digit
• Thermocouple R, S, B, C, G:
(PV ±0.5% or ±5 ℃ higher one) ±1-digit
• Other sensors: ≤ ±5 ℃ (≤-100 ℃)
Analog
At room temperature
(23℃ ±5 ℃)
±0.3% F.S. ±1-digit
Out of room temperature range
±0.5% F.S. ±1-digit
• In case of TK4SP Series, ±1 ℃ will be added to the degree standard.
Unit Descriptions
4
1
2
1. PV display part (Red)
• Run mode: Displays PV (Present value).
• Setting mode: Displays parameter name.
2. SV display part ( Green )
• Run mode: Displays SV (Setting value).
• Setting mode: Displays parameter setting value.
3. Input key
Display
[A/M]
[MODE]
Name
Control switching key
Mode key
[◀], [▼], [▲] Setting value control key
4. Indicator
Display Name
3
℃, %, ℉ Unit
AT
Description
Displays selected unit (parameter)
Auto tuning Flashes during auto tuning every 1 sec
Turns ON when the control output is ON
OUT1/2
Control output
• SSR output (cycle / phase control)
MV over 5% ON
• Current output
Manual control: 0% OFF, over ON
Auto control: below 2% OFF, over 3% ON
AL1/2
MAN
Alarm output
Manual control
Turns ON when the alarm output is ON
Turns ON during manual control
TK4N Series
5
Other series
SV1/2/3 Multi SV
The SV indicator is ON which is currently displayed. (When using multi SV function)
5. PC loader port:
For connecting communication converter (SCM series).
• For the details about old model, refer to the user manual. Download the manuals from the Autonics website.
-|Transparent Guide|-
Dimensions
• Unit: mm, For the detailed drawings, follow the Autonics website.
• Below is based on TK4S Series.
A C
E
D
■
Panel cut-out
G
I
Body
TK4N
TK4S
A
48
48
TK4SP 48
TK4M
TK4W
TK4H
TK4L
72
96
48
96
■
Bracket
TK4N
42
72
48
96
96
B
24
48
48
45.2
48.6
6
6
6
6
6
6
C
3
32.4
26.4
64.5
64.5
64.5
64.5
D
91.8
64.5
72.2
1.7
1.5
1.5
1.5
-
E
-
1.7
67.5
44.7
91.5
91.5
F
21.8
45
44.8
Panel cut-out
G H I
≥ 55 ≥ 37 45 + 0.6
0
≥ 65 ≥ 65 45 + 0.6
0
≥ 65 ≥ 65 45 + 0.6
0
≥ 90 ≥ 90 68 + 0.7
0
≥ 115 ≥ 65 92 + 0.8
0
≥ 65 ≥ 115 45 + 0.6
0
≥ 115 ≥ 115 92 + 0.8
0
J
22.2
+ 0.3
0
45
45
68
45
92
92
+ 0.6
0
+ 0.6
0
+ 0.7
0
+ 0.6
0
+ 0.8
0
+ 0.8
0
TK4S/SP
□49.5
30.5
Other series
46
37.5 40.5
12
23.9
10
■
Terminal protection cover
TK4N
44.6
6.2
60.3
Installation Method
■
TK4N
■
Other series
Screwdriver
After mounting the product to panel with bracket, fasten the bolts by using screwdriver.
Flathead screwdriver
Insert the unit into a panel, fasten the bracket by pushing with a flathead screwdriver.
Errors
Display Input
OPEN
HHHH
LLLL
ERR
Temperature sensor
Analog
Description
Flashes at 0.5 sec interval when input sensor is disconnected or sensor is not connected.
Flashes at 0.5 sec interval when input is over F.S. ±10%.
Output
' Sensor error,
MV' parameter setting value
' Sensor error,
MV' parameter setting value
Temperature sensor
Analog
Temperature sensor
Analog
Flashes at 0.5 sec intervals if the input value is above the input range.
Flashes at 0.5 sec intervals if the input value is over 5 to 10% of high limit or low limit value.
Flashes at 0.5 sec. intervals if the input value is below the input range.
Flashes at 0.5 sec intervals if the input value is over 5 to 10% of low limit or high limit value.
Temperature sensor
Analog
Flashes at 0.5 sec intervals if there is error for setting and it returns to the error-before screen.
-
Heating: 0%,
Cooling: 100%
Normal output
Heating: 100%,
Cooling: 0%
Normal output
Troubleshooting
Check input sensor status.
Check analog input status.
When input is within the rated input range, this display disappears.
Check setting method.
Connections
• Shaded terminals are standard model.
• Digital input is not electrically insulated from internal circuits, so it should be insulated when connecting other circuits.
■
TK4N
3
S
S
R
4
+
-
V
TC
RTD
V mA
CT Current Transformer
0.0-50.0 A
Digital Input
Contact,
Non contact Input
AL2 OUT:
RESISTIVE LOAD
SOURCE
50/60 Hz 6 VA
T
2
O
U
T
1
O
U
R
R
C
U
S
S
R
R
R
C
U
3
4
+ mA
-
11 VDCᜡ±2V
20 mA Max.
1
2
1
2
+
-
V
+ mA
-
11 VDCᜡ±2V
20 mA Max.
■
TK4S
Digital Input
Contact,
Non contact Input
DI-1 DI-1
1
2
Digital Input
Contact,
Non contact Input
OUT2: Relay
250 VACᜠ 3 A 1a
30 VDCᜡ 3 A 1a
RESISTIVE LOAD
13 7
DI-2 DI-2
14 8
9
AL1 OUT:
250 VACᜠ 3A 1a
RESISTIVE LOAD
AL2 OUT:
250 VACᜠ 3A 1a
RESISTIVE LOAD OUT1:Relay
250 VACᜠ 3 A 1a
30 VDCᜡ 3 A 1a
RESISTIVE LOAD
3
4
-
+
SOURCE
100-240 VACᜠ 50/60 Hz 8 VA
24 VACᜠ 50/60 Hz 8 VA
24-48 VDCᜡ 5 W
OUT1
SSR
3
4
+
-
V
5
6
Transfer
Output mA
DC 4-20 mA
RS485(A+)
RS485(B-)
Communication
Output
Current CT
Transformer
0.0-50.0 A
15
16
17
18
Current
3
4
+ mA
-
OUT2
SSR
13
14
+
-
V
10
11
12
A
B
B'
RTD
Current
13
14
+ mA
-
TC
V mA
■
TK4SP
OUT1: Relay
250 VACᜠ 3 A 1a
30 VDCᜡ 3 A 1a
RESISTIVE LOAD
B'
3
4
5
6
7
8
OUT2: Relay
250 VACᜠ 3 A 1a
30 VDCᜡ 3 A 1a
RESISTIVE LOAD
AL1:
Relay
250 VACᜠ 3 A 1a
RESISTIVE LOAD mA
V
TC
B
A
RTD
2
1 11
10
9
+
-
SOURCE
100-240 VACᜠ 50/60 Hz 8 VA
24 VACᜠ 50/60 Hz 8 VA
24-48 VDCᜡ 5 W
OUT1
SSR
5
4
+
-
V
11 VDCᜡ±2V
20 mA Max.
Current
5
4
+ mA
-
DC 0/4-20 mA
Load 500 Ω Max.
OUT2
SSR
6
9 +
-
V
11 VDCᜡ±2V
20 mA Max.
Current
6
9 +
mA
DC 0/4-20 mA
Load 500 Ω Max.
■
TK4M
+
-
1
2
3
4
5
6
AL1 OUT:
250 VACᜠ 3 A 1a
RESISTIVE LOAD
AL2 OUT:
250 VACᜠ 3 A 1a
RESISTIVE LOAD
19
20
21
22
10
11
12
7
8
9
OUT1
SSR
6
7
+
-
V
11 VDCᜡ±2V
20 mA Max.
OUT2: Relay
250 VACᜠ 3 A 1a
30 VDCᜡ 3 A 1a
RESISTIVE LOAD
OUT1: Relay
250 VACᜠ 3 A 1a
30 VDCᜡ 3 A 1a
RESISTIVE LOAD
SOURCE
100-240 VACᜠ
50/60 Hz 8 VA
24 VACᜠ
50/60 Hz 8 VA
24-48 VDCᜡ 5 W
23
24
25
26
27
13
14
Current
6
7
+
mA
DC 0/4-20 mA
Load 500 Ω Max.
OUT2
SSR
4
5
+
-
V
11 VDCᜡ±2V
20 mA Max.
15
16
17
18
DI-1 DI-1
Digital Input
Contact,
Non contact Input
RS485(A+)
RS485(B-)
+ mA
-
Communication output
CT
Current
Transformer
0.0-50.0 A
Transfer Output
DC 4-20 mA
A
B
B '
RTD TC
+
V
-
Current
4
5
+
mA
DC 0/4-20 mA
Load 500 Ω Max.
+ mA
-
■ TK4H / W / L
10
+
-
SOURCE
100-240 VACᜠ 50/60 Hz 8 VA
24 VACᜠ 50/60 Hz 8 VA
24-48 VDCᜡ 5 W
OUT1
SSR
11
12
9
10
+
-
V
11 VDCᜡ±2V
20 mA Max.
5
6
7
8
9
3
4
1
2
AL1 OUT:
250 VACᜠ 3 A 1a
RESISTIVE LOAD
AL2 OUT:
250 VACᜠ 3 A 1a
RESISTIVE LOAD
OUT2: Relay
250 VACᜠ 3 A 1a
30 VDCᜡ 3 A 1a
RESISTIVE LOAD
OUT1: Relay
250 VACᜠ 3 A 1a
30 VDCᜡ 3 A 1a
RESISTIVE LOAD
Current
9
10
+ mA
-
DC 0/4-20 mA
Load 500 Ω Max.
OUT2
SSR
7
8
+
-
V
11 VDCᜡ±2V
20 mA Max.
17
18
19
20
21
22
23
13
14
15
16
24
Digital Input
Contact,
Non contact Input
DI-1
DI-2
RS485(A+)
RS485(B-) -
+ mA
Communication output
CT
Current
Transformer
0.0-50.0 A
Transfer Out
DC 4-20 mA
A
B
B'
RTD TC
V mA
DI-1
DI-2
Current
7
8
+ mA
-
DC 0/4-20 mA
Load 500 Ω Max.
Crimp Terminal Specifications
• Unit: mm, Use the crimp terminal of follow shape.
≤5.8
≥3.0
Fork crimp terminal
≤5.8
≥3.0
Round crimp terminal
Initial Display When Power is ON
When power is supplied, after all display will flash for 1 sec, model name is displayed sequentially. After input sensor type will flash twice, enter into RUN mode.
1. All display
PV display part
***8
SV display part
***8
2. Model
TK4
14RN
3. Input specification
TK4
KCaH
4. Run mode
OPEN
0
Mode Setting
Auto before entering to mode
(when using password)
→
Password input
Password Key input
Pass
Fail
Auto
Entering mode
[◀], [▲], [▼] Password input
[MODE]
Selected mode
Run mode
[◀], [▲], [▼] → SV setting
Move digits: [◀]
Change value:
[▲], [▼]
Save : [MODE] or no key input over 5 sec
RUN [MODE] over 2 sec
[◀] + [▲] + [▼] over 5 sec
→
→
Parameter group
Parameter reset
[MODE] over 3 sec
Auto
[A/M]
[▲] + [▼] over 3 sec
01) →
→
Auto/Manual control switching
Digital input key
[A/M]
Auto
01) In case of TK4N / 4S / 4SP model, short press of [MODE] key replaces [A/M] key function.
→
→
→
→
→
RUN
18, Bansong-ro 513Beon-gil, Haeundae-gu, Busan, Republic of Korea, 48002 www.autonics.com | +82-2-2048-1577 | [email protected]
Parameter Setting
• Some parameters are activated/deactivated depending on the model or setting of other parameters.
• The 'Parameter mask' feature, which hide unnecessary or inactive parameters, and the 'User parameter group' feature, which quickly and easily set up certain parameters that are frequently used, can be set up in DAQMaster.
• Refer to the user manual for the details.
■
Parameter 1 group
Parameter
Control output
RUN/STOP
Multi SV selection
Heater current monitoring
Display Default
R-S
SV-N
CT-A
RUN
SV-0
)0
Alarm output1 low limit
AL!L
1550
Alarm output1 high limit AL!H
1550
Alarm output2 low limit
AL@L 1550
Alarm output2 high limit AL@H 1550
Alarm output3 low limit
AL#L 1550
Alarm output3 high limit AL#H 1550
Multi SV 0
Multi SV 1
Multi SV 2
Multi SV 3
SV-0
SV-1
SV-2
SV-3
0000
0000
0000
0000
■
Parameter
Auto tuning RUN/STOP
Heating proportional band
Cooling proportional band
Heating integral time
Cooling integral time
Heating derivative time
Cooling derivative time
Dead overlap band
Manual reset
Heating hysteresis
Heating OFF offset
Cooling hysteresis
Cooling OFF offset
MV low limit
MV high limit
Display Default
AT
H-P
C-P
H-1
C-1
H-D
C-D
DB
REST hHYS hOST cHYS cOST
L-MV
H-MV
RAMP up change rate RAMU
RAMP down change rate
RAMD
RAMP time unit rUNT
OFF
01)0
01)0
0000
0000
0000
0000
0000
05)0
002
000
002
000
`0)0
10)0
000
000
MIN
■
Parameter 2 group
Parameter 3 group
Parameter
Input specification
Temperature unit
Analog low limit
Analog high limit
Scaling decimal point
Low limit scale
High limit scale
Display unit
Input correction
Input digital filter
SV low limit
SV high limit
Control output mode
Control type
Auto tuning mode
OUT1 control output selection
OUT1 SSR drive output type
OUT1 current output range
OUT2 control output selection
OUT2 current output range
Display Default
IN-T KCaH
UNIT ><?C
L-RG 0)00
H-RG 1)00
DOT
L-SC 00)0
H-SC 10)0 dUNT >?/O
IN-B 0000
MAvF 00)1
L-SV -200
H-SV 1350
O-FT
C-MD
)0
HEAT
(Normal type)
H-C
(Heating&
Cooling type)
PID
(Normal type)
pP
(Heating&
Coolingtype)
AtT TUN1
OUT1 CURR
O!SR
STND
O!MA
4-20
OUT2 CURR
O@MA 4-20
■
Parameter 4 group
Parameter
Alarm output1 Operation mode
Alarm output1 Option
Display Default
AL-1
AL!T
Alarm output1 Hysteresis A!HY
Alarm output1 contact
A!N
DVCC
AL-A
001
NO type
Alarm output1 ON delay time
Alarm output1 OFF delay time
Alarm output2 Operation mode
Alarm output2 Option
A!ON
A!OF
AL-2
AL@T
0000
0000
]]DV
AL-A
Alarm output2 Hysteresis
A@HY
Alarm output2 contact
A@N type
Alarm output2 ON delay time
Alarm output2 OFF delay
A@ON
001
NO
0000 time
Alarm output3 Operation mode
Alarm output3 Option
A@OF
AL-3
AL#T
Alarm output3 Hysteresis A#HY
Alarm output3 contact
A#N
0000
OFF
AL-A
001
NO type
Alarm output3 ON delay time
Alarm output3 OFF delay time
LBA time
A#ON
A#OF
LBaT
0000
0000
0000
LBA band
Analog Transmission output1 Mode
Transmission output1 low limit
Transmission output1 high limit
Analog Transmission output2 Mode
Transmission output2 low limit
Transmission output2 high limit
LBaB
AoM1 PV
FsL1 -200
FsH1 1350
AoM2
FsL2
FsH2
002
( 003 )
PV
-200
1350
Communication address
ADRS 01
Communication speed
BPS 96
Comm. parity bit
Comm. stop bit
Response time
Comm. write
PRTY
STP
RSWT
COMW
NONE
2
20
EnA
■
Parameter 5 group
Parameter
Multi SV number
Digital input key
Digital input1 Terminal
Function
Digital input2 Terminal
Display Default
MtSV
DI-K
DI-1 OFF
Function DI-2 OFF
Manual control, initial MV
ItMV AUTO
Manual control, preset
MV
Sensor error MV
Control stop MV
PrMV
ErMV
StMV
00)0
00)0
00)0
Control stop alarm output
User level
SV setting lock
Parameter 1 group lock
Parameter 2 group lock
Parameter 3 group lock
Parameter 4 group lock
Parameter 5 group lock
Password setting
StAL
USER
LcSV
LcP1
LcP2
LcP3
LcP4
LcPS
PWD
1
STOP
CONT
STND
OFF
OFF
OFF
OFF
OFF
OFF
0000
Heating control cycle
Cooling control cycle
H-T
C-T
02)0
(Relay)
00@0
(SSR)

Public link updated
The public link to your chat has been updated.
Advertisement
Key features
- Simultaneous heating and cooling outputs for efficient temperature control
- PID control algorithm for precise and stable temperature regulation
- Dual display for simultaneous monitoring of process and setpoint temperature
- Alarm functions for abnormal temperature conditions
- Built-in communication capabilities for remote monitoring and control
- Compact and rugged design for space-saving and reliable operation
- User-friendly interface for easy setup and operation