Spectrum Controls 1794 IRT8I RTD/Thermocouple Module User's Manual
Below you will find brief information for RTD/Thermocouple Module 1794 IRT8I. The 1794 IRT8I is an isolated universal input module that supports current, voltage, RTD, resistance, thermocouple, and millivolt type inputs. The module digitally converts and stores analog data from any combination mentioned above. Each input channel is individually configured via software for a specific input device, data format, filter frequency, and provides open-circuit, over-range, under-range detection and indication.
Advertisement
Advertisement
User's Manual Pub.
0300242 ‐ 01 Rev.
A
1794 Isolated
RTD/Thermocouple Module
Catalog Number: 1794sc-IRT8I
ii Flex™ IO Isolated RTD/Thermocouple Module
Important Notes
1.
Please read all the information in this owner’s guide before installing the product.
2.
The information in this owner's guide applies to hardware Series A and firmware version 1.0 or later.
3.
This guide assumes that the reader has a full working knowledge of the relevant processor.
Notice
The products and services described in this owner's guide are useful in a wide variety of applications. Therefore, the user and others responsible for applying the products and services described herein are responsible for determining their acceptability for each application. While efforts have been made to provide accurate information within this owner's guide, Spectrum Controls assumes no responsibility for the accuracy, completeness, or usefulness of the information herein.
Under no circumstances will Spectrum Controls be responsible or liable for any damages or losses, including indirect or consequential damages or losses, arising out of either the use of any information within this owner's guide or the use of any product or service referenced herein.
No patent liability is assumed by Spectrum Controls with respect to the use of any of the information, products, circuits, programming, or services referenced herein.
The information in this owner's guide is subject to change without notice.
Limited Warranty
Spectrum Controls warrants that its products are free from defects in material and workmanship under normal use and service, as described in Spectrum Controls literature covering this product, for a period of 1 year. The obligations of Spectrum Controls under this warranty are limited to replacing or repairing, at its option, at its factory or facility, any product which shall, in the applicable period after shipment, be returned to the
Spectrum Controls facility, transportation charges prepaid, and which after examination is determined, to the satisfaction of Spectrum Controls, to be thus defective.
This warranty shall not apply to any such equipment which shall have been repaired or altered except by Spectrum Controls or which shall have been subject to misuse, neglect, or accident. In no case shall the liability of Spectrum Controls exceed the purchase price.
The aforementioned provisions do not extend the original warranty period of any product which has either been repaired or replaced by Spectrum Controls.
User's Manual Pub.
0300242 ‐ 01 Rev.
A
iii
Table of Contents
IMPORTANT NOTES ............................................................................................................................................
II
NOTICE ..............................................................................................................................................................
II
LIMITED WARRANTY ..........................................................................................................................................
II
CHAPTER 1 MODULE OVERVIEW .....................................................................................................................
1 ‐ 1
S
ECTION
1.1
G
ENERAL
D
ESCRIPTION
..............................................................................................................................
1 ‐ 1
S
ECTION
1.2
I
NPUT
T
YPES AND
R
ANGES
.........................................................................................................................
1 ‐ 1
S
ECTION
1.3
D
ATA
F
ORMATS
.......................................................................................................................................
1 ‐ 2
S
ECTION
1.4
F
ILTER
F
REQUENCIES
................................................................................................................................
1 ‐ 2
S
ECTION
1.5
H
ARDWARE
F
EATURES
..............................................................................................................................
1 ‐ 2
S
ECTION
1.6
S
YSTEM
O
VERVIEW
...................................................................................................................................
1 ‐ 3
1.6.1
Module Power ‐ up .....................................................................................................................................
1 ‐ 3
S
ECTION
1.7
M
ODULE
O
PERATION
................................................................................................................................
1 ‐ 3
CHAPTER 2 INSTALLATION AND WIRING ..........................................................................................................
2 ‐ 1
S
ECTION
2.1
C
OMPLIANCE TO
E
UROPEAN
U
NION
D
IRECTIVES
.............................................................................................
2 ‐ 1
2.1.1
EMC Directive ............................................................................................................................................
2 ‐ 1
2.1.2
Low Voltage Directive ...............................................................................................................................
2 ‐ 1
S
ECTION
2.2
G
ENERAL
C
ONSIDERATIONS
........................................................................................................................
2 ‐ 2
2.2.1
Hazardous Location Considerations ..........................................................................................................
2 ‐ 2
2.2.2
Prevent Electrostatic Discharge ................................................................................................................
2 ‐ 2
2.2.3
Remove Power ..........................................................................................................................................
2 ‐ 3
2.2.4
Selecting a Location ..................................................................................................................................
2 ‐ 3
S
ECTION
2.3
P
OWER
R
EQUIREMENTS
............................................................................................................................
2 ‐ 3
2.3.1
Wiring the Terminal Base Units (1794 ‐ TB3G shown) ................................................................................
2 ‐ 4
S
ECTION
2.4
I
NSTALLING THE
M
ODULE
...........................................................................................................................
2 ‐ 5
2.4.1
Mounting the Terminal Base Unit on a DIN Rail .......................................................................................
2 ‐ 5
2.4.2
Panel/Wall Mounting ...............................................................................................................................
2 ‐ 7
2.4.3
Mounting the IRT8I Module on the Terminal Base Unit ...........................................................................
2 ‐ 9
S
ECTION
2.5
F
IELD
W
IRING
C
ONNECTIONS
....................................................................................................................
2 ‐ 10
2.5.1
Field Wiring using a 1794 ‐ TB3G and TB3GS Terminal Base ....................................................................
2 ‐ 10
S
ECTION
2.6
M
ODULE
I
NDICATORS
..............................................................................................................................
2 ‐ 15
CHAPTER 3 CONFIGURING THE 1794SC ‐ IRT8I USING RSLOGIX 5000 ..................................................................
3 ‐ 1
S
ECTION
3.1
T
HINGS
Y
OU
S
HOULD
K
NOW
......................................................................................................................
3 ‐ 1
S
ECTION
3.2
M
ODULE
M
EMORY
M
AP
...........................................................................................................................
3 ‐ 1
S
ECTION
3.3
C
ONFIGURE
G
ENERIC
P
ROFILE
.....................................................................................................................
3 ‐ 2
3.3.1
Add a Local Ethernet Bridge Module ........................................................................................................
3 ‐ 3
3.3.2
Add a Remote Ethernet Flex Adapter ........................................................................................................
3 ‐ 4
3.3.3
Add the Generic Flex Module ....................................................................................................................
3 ‐ 6
S
ECTION
3.4
M
ODULE
C
ONFIGURATION
.........................................................................................................................
3 ‐ 7
3.4.1
Fault Mode [Word 0 (Bits 2,3,4,5,10,11,12,13)] .......................................................................................
3 ‐ 9
3.4.2
Input Type [Words 1 – 8 (Bits 0 to 4)] .......................................................................................................
3 ‐ 9
3.4.3
Input Filter [Words 1 – 8 (Bits 5 to 7) ......................................................................................................
3 ‐ 10
3.4.4
Data Format [Words 1 – 8 (Bits 8 to 10) .................................................................................................
3 ‐ 10
3.4.5
Open Circuit Mode [Words 1 – 8 (Bits 12 & 13)] .....................................................................................
3 ‐ 12
3.4.6
Disable CJC [Words 1 – 8 (Bit 14)] ...........................................................................................................
3 ‐ 12
3.4.7
Temperature Units [Words 1 – 8 (Bit 15)] ...............................................................................................
3 ‐ 12
3.4.8
Low Alarm Threshold [Words 9,12,15,18,21,24,27,30] ..........................................................................
3 ‐ 12
3.4.9
High Alarm Threshold [Words 10,13,16,19,22,25,28,31] .......................................................................
3 ‐ 12
3.4.10
User Alarm Deadband [Words 11,14,17,20,23,26,29,32] .....................................................................
3 ‐ 12
S
ECTION
3.5
R
EAD
I
NPUT
&
S
TATUS
D
ATA
....................................................................................................................
3 ‐ 13
User's Manual Pub.
0300242 ‐ 01 Rev.
A
iv Flex™ IO Isolated RTD/Thermocouple Module
3.5.1
Input Data [Words 0 to 7] .......................................................................................................................
3 ‐ 15
3.5.2
UnderRange Alarms [Word 8 (Bits 0 to 7)] .............................................................................................
3 ‐ 15
3.5.3
OverRange Alarm [Word 8 (Bits 8 to 15)] ...............................................................................................
3 ‐ 15
3.5.4
User Low Alarm [Word 9 (Bits 0 to 7)] ....................................................................................................
3 ‐ 15
3.5.5
User High Alarm [Word 9 (Bits 8 to 15)] .................................................................................................
3 ‐ 15
3.5.6
Open Circuit Alarm [Word 10 (Bits 0 to 7)] .............................................................................................
3 ‐ 15
3.5.7
CJC Alarm [Word 10 (Bits 8 & 9)] ............................................................................................................
3 ‐ 16
3.5.8
Diagnostics [Word 11 (Bits 0 to 7)] .........................................................................................................
3 ‐ 16
APPENDIX A MODULE SPECIFICATIONS ............................................................................................................
A ‐ 1
User's Manual Pub.
0300242 ‐ 01 Rev.
A
PREFACE
v
Who Should
Use This Manual
Use this manual if you are responsible for designing, installing, programming, or troubleshooting control systems that use Allen-Bradley I/O and/or compatible controllers, such as MicroLogix, CompactLogix, ControlLogix, SLC 500 or PLC 5.
How to Use
This Manual
Read this preface to familiarize yourself with the rest of the manual. This preface covers the following topics:
•
Who should use this manual
•
How to use this manual
•
Related
•
Conventions used in this manual
•
Rockwell Automation support
As much as possible, we organized this manual to explain, in a task-by-task manner, how to install, configure, program, operate and troubleshoot a control system using the
1794sc-IRT8I.
Related
Documentation
The table below provides a listing of publications that contain important information about Allen-Bradley PLC systems.
Document Title
1794 Flex IO Product Data
CompactLogix System Overview
ControlLogix System User Manual
ControlNet Modules in Logix5000 Control Systems
User Manual
EtherNet/IP Modules in Logix5000 Control Systems
User Manual
Allen-Bradley Programmable Controller
Grounding and Wiring Guidelines
Document Number
1794-2.1
1769-SO001A-EN-P
1756-6.5.13-SEP99
CNET-UM001C-EN-P
ENET-UM001G-EN-P
1770-4.1
If you would like a manual, you can:
•
Download a free electronic version from the internet at www.theautomationbookstore.com
•
Purchase a printed manual by: o
Contacting your local distributor or Rockwell Automation representative o
Visiting www.theautomationbookstore.com and placing your order o
Calling 1.800.963.9548 (USA/Canada) or 001.330.725.1574
(Outside USA/Canada)
User's Manual Pub.
0300242 ‐ 01 Rev.
A
vi Flex™ IO Isolated RTD/Thermocouple Module
Conventions
Used in This
Manual
The following conventions are used throughout this manual:
•
Bulleted lists (like this one) provide information not procedural steps.
•
Numbered lists provide sequential steps or hierarchical information.
•
Italic
type is used for emphasis
•
Bold
type identifies headings and sub-headings
•
!
Attention
Are used to identify critical information to the reader
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Chapter 1
Module Overview
This chapter describes the 1794sc-IRT8I Isolated Universal input module and explains how the module reads current, voltage, RTD, resistance and thermocouple/millivolt analog input data. Included is information about:
•
General description
•
Input types and ranges
•
Data Formats and filter frequencies
•
Hardware Features
•
System overview and module operation
•
Auto-calibration
Section 1.1
General
Description
The isolated RTD/Thermocouple module supports current, voltage, RTD, resistance, thermocouple and millivolt type inputs. The module digitally converts and stores analog data from any combination mentioned above. Each input channel is individually configured via software for a specific input device, data format, filter frequency, and provides open-circuit, over-range, under-range detection and indication.
Section 1.2
Input Types and Ranges
The tables below list the input types and their associated ranges.
Input Type Range
B Type Thermocouple 300 to 1820 ˚ C (572 to 3308 ˚ F)
C Type Thermocouple 0 to 2315 ˚ C (32 to 4199 ˚ F)
E Type Thermocouple -270 to 1000 ˚ C (-454 to 1832 ˚ F)
J Type Thermocouple -210 to 1200 ˚ C (-346 to 2192 ˚ F)
K Type Thermocouple -270 to 1370 ˚ C (-454 to 2498 ˚ F)
N Type Thermocouple -210 to 1300 ˚ C (-346 to 2372 ˚ F)
R Type Thermocouple 0 to 1768 ˚ C (32 to 3214 ˚ F)
S Type Thermocouple 0 to 1768 ˚ C
T Type Thermocouple -270 to 400 ˚ C
(32 to 3214
(-270 to 752
˚
˚
F)
F)
100 Ω Pt α 0.385
200 Ω Pt α 0.385
500 Ω Pt α 0.385
1000 Ω Pt α 0.385
-200 to 850
-200 to 850
-200 to 850
-200 to 850
˚
˚
˚
˚
C
C
C
C
(-328 to 1562
(-328 to 1562
(-328 to 1562
(-328 to 1562
˚
˚
˚
˚
F)
F)
F)
F)
100 Ω Pt α 0.3916
200 Ω Pt α 0.3916
500 Ω Pt α 0.3916
1000 Ω Pt α 0.3916
10 Ω Cu α 0.426
100 Ω Ni α 0.618
-200 to 630 ˚ C
-200 to 630 ˚ C
-200 to 630 ˚ C
-200 to 630 ˚ C
-100 to 260 ˚ C
-100 to 260 ˚ C
(-328 to 1166 ˚ F)
(-328 to 1166 ˚ F)
(-328 to 1166 ˚ F)
(-328 to 1166 ˚ F)
(-148 to 500 ˚ F)
(-148 to 500 ˚ F)
User's Manual Pub.
0300242 ‐ 01 Rev.
A
1-2 Flex™ IO Isolated RTD/Thermocouple Module
Input Type
120 Ω Ni α 0.672
604 Ω NiFe α 0.518
Resistance
Voltage
Range
-80 to 260 ˚ C
-100 to 200 ˚ C
0 to 150 Ω
0 to 1000 Ω
0 to 3000 Ω
+/- 50 mV
+/- 100 mV
(-112 to 500 ˚ F)
(-148 to 392 ˚ F)
Section 1.3
Data Formats
For each module the data can be configured for:
•
Engineering units x 1
•
Engineering units x 10
•
Scaled-for-PID
•
Percent of full-scale
•
Raw/proportional data
•
CJC Engineering Units
•
CJC scaled-for-PID
•
CJC percent of full range
Section 1.4
Filter
Frequencies
The module uses a digital filter that provides high frequency noise rejection for each input signal. The filter for each channel is programmable allowing you to select from six different filter frequencies:
•
4.17 Hz
•
10 Hz
•
16.7 Hz
•
19.6 Hz
•
62 Hz
•
470 Hz
Section 1.5
Hardware
Features
Each module requires a terminal base unit. Terminal base units are connected together to form the backplane for the system. Each base unit contains terminals for field terminations. Field terminations are wired as differential inputs with the exception of
RTD and resistance type inputs. Two cold junction compensation (CJC) sensors can be added to the terminal base unit to enable accurate readings when using thermocouple input types. Each CJC sensor compensates for offset voltages introduced into the input signal as a result of the cold-junction where the thermocouple wires come into contact with the base unit. Module configuration is accomplished using the controller’s programming software. In addition, some controllers support configuration via the user
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Chapter 1: Module Overview 1-3 program. In either case, the module configuration is stored in the memory of the controller. Refer to your controller’s user manual for more information. The illustration below shows the module’s hardware features.
Figure 1-1
1
2
Item Description
4
2 Module key-switch position
3
Section 1.6
System
Overview
The module communicates to the controller through the base unit bus interface. The module also receives 5 and 24V dc power through the bus interface.
Note: An external power supply is required for all 2-wire transmitters.
1.6.1
Module Power-up
At power-up, the module performs a check of its internal circuits, memory and basic functions. After power-up checks are complete, the module waits for valid channel configuration data. If an invalid configuration is detected, the module generates a configuration error. Once a channel is properly configured and enabled, it continuously converts the input data to a digital value within the currently selected data range. Each time a channel is read by the input module, that data value is tested by the module for an over-range, under-range, or open-circuit condition. If such a condition is detected, a unique bit is set in the channel status word. The channel status word is described in the
Input Data File in Chapter 3. Using the module image table, the controller reads the two’s complement binary converted input data from the module. This typically occurs at the end of the program scan or when commanded by the control program. If the controller and the module determine that the data transfer has been made without error, the data is made available to the control program.
Section 1.7
Module
Operation
The module measures each analog signal using a dedicated A/D converter for each
User's Manual Pub.
0300242 ‐ 01 Rev.
A
1-4 Flex™ IO Isolated RTD/Thermocouple Module channel. The converter reads the signal and converts it as required for the type of input selected. If thermocouples are being utilized, the module continuously samples each CJC sensor and compensates for temperature changes at the terminal base cold junction, between the thermocouple wire and the input terminal. See the block diagram below.
Isolation
Barrier
1794 FLEX
Terminal Base Unit
8 Channels &
24VDC PWR
Signal
Conditioning
MUX
1 of 8
ΣΔ
ADC
+ FLTR
8 of 8
MICRO-
CNTRLR
Isolated PWR Supply
24 VDC
Backplane
COMMS
The module is designed to support up to 8 isolated channels of RTD, resistance, voltage, current, or thermocouple.
Thermocouple measurements utilize two cold junction compensation sensors placed at two different locations on the terminal base unit. The location of each CJC sensor was chosen to calculate the overall CJC error accurately for each channel. Thermocouple support includes types J, K, T, E, R, S, B, N, and C. In thermocouple mode the 1794sc-
IRT8I will measure thermocouple and CJC voltages and convert the results to a linearized temperature reading.
RTD support includes types Pt 385, Pt 3916, Ni 618, Ni 672, Cu 426, and NiFe 518. In
RTD and resistance mode the module will inject a constant current through the RTD or resistor, measure the voltage across the resistance and convert to a linearized temperature or resistance reading. The IFIU supports 2 and 3 wired RTD inputs.
When configured for current or voltage type inputs, the module converts the analog values directly into digital counts.
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Chapter 2
Installation and Wiring
This chapter will cover:
•
Compliance to European union directives
•
General considerations
•
Power requirements
•
Installing the module
•
Field wiring connections
Section 2.1
Compliance to
European
Union Directives
This product is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
2.1.1
EMC Directive
The 1794sc-IRT8I module is tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file:
•
EN 61000-6-4EMC – Generic Emission Standard, Part 2 - Industrial
Environment
•
EN 61000-6-2EMC – Generic Immunity Standard, Part 2 - Industrial
Environment
This product is intended for use in an industrial environment.
2.1.2
Low Voltage Directive
This product is tested to meet Council Directive 2006/99/EC Low Voltage, by applying the safety requirements of EN 61131-2Programmable Controllers, Part 2 – Equipment
Requirements and Tests. For specific information required by EN61131-2, see the appropriate sections in this publication, as well as the following Allen-Bradley publications:
•
Industrial Automation, Wiring and Grounding Guidelines for Noise Immunity
, publication 1770-4.1
•
Automation Systems Catalog
, publication B113
User's Manual Pub.
0300242 ‐ 01 Rev.
A
2-2 Flex™ IO Isolated RTD/Thermocouple Module
Section 2.2
General
Considerations
Flex I/O is suitable for use in an industrial environment when installed in accordance with these instructions. Specifically, this equipment is intended for use in clean, dry environments Pollution degree 2
1
II
2
(IEC 60664-1)
3
.
and to circuits not exceeding Over Voltage Category
2.2.1
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or nonhazardous locations only. The following WARNING statement applies to use in hazardous locations.
!
Attention
EXPLOSION HAZARD
•
Substitution of components may impair suitability for Class I,
Division 2.
•
Do not replace components or disconnect equipment unless power has been switched off or the area is known to be nonhazardous.
•
Do not connect or disconnect components unless power has been switched off or the area is known to be non-hazardous.
•
This product must be installed in an enclosure.
•
All wiring must comply with N.E.C. article 501-4(b).
2.2.2
Prevent Electrostatic Discharge
!
Attention
Electrostatic discharge can damage integrated circuits or semiconductors if you touch analog I/O module bus connector pins or the terminal block on the input module. Follow these guidelines when you handle the module:
•
Touch a grounded object to discharge static potential.
•
Wear an approved wrist-strap grounding device.
•
Do not touch the bus connector or connector pins.
•
Do not touch circuit components inside the module.
•
If available, use a static-safe work station.
•
When it is not in use, keep the module in its static-shield bag.
1
Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that
2 occasionally a temporary conductivity caused by condensation shall be expected.
Over Voltage Category II is the load level section of the electrical distribution system. At this level transient voltages are controlled and do not exceed the impulse voltage capability of the product’s
3 insulation.
Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC) designations.
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Chapter 2: Installation and Wiring 2-3
2.2.3
Remove Power
!
Attention
Remove power before removing or inserting this module. When you remove or insert a module with power applied, an electrical arc may occur. An electrical arc can cause personal injury or property damage by:
•
Sending an erroneous signal to your system’s field devices, causing unintended machine motion
•
Causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the module and its mating connector and may lead to premature failure.
2.2.4
Selecting a Location
Reducing Noise
Most applications require installation in an industrial enclosure to reduce the effects of electrical interference. Analog inputs are highly susceptible to electrical noise. Electrical noise coupled to the analog inputs will reduce the performance (accuracy) of the module.
Group your modules to minimize adverse effects from radiated electrical noise and heat.
Consider the following conditions when selecting a location for the analog module.
Position the module:
•
Away from sources of electrical noise such as hard-contact switches, relays, and
AC motor drives
•
Away from modules which generate significant radiated heat, such as the 1794-
OB32. Refer to the module’s heat dissipation specification.
In addition, route shielded, twisted-pair analog input wiring away from any high voltage
I/O wiring.
Section 2.3
Power
Requirements
The module receives power through the bus interface from the +5V dc/+24V dc system power supply. The maximum current drawn by the module is shown in the table below.
5 VDC 24 VDC
80 mA 240 mA
The wiring of the terminal base unit is determined by the current draw through the terminal base. Make certain that the current draw does not exceed 10A.
!
Attention
Total current draw through the terminal base unit is limited to 10A.
Separate power connections may be necessary.
Methods of wiring the terminal base units are shown in the illustration below.
User's Manual Pub.
0300242 ‐ 01 Rev.
A
2-4 Flex™ IO Isolated RTD/Thermocouple Module
2.3.1
Wiring the Terminal Base Units (1794-TB3G shown)
!
Attention
Daisy-chaining
Do not daisy chain power or ground from the terminal base unit to any ac or dc digital module terminal base unit.
Power
IF8u
Module
IF8u
Module
Frequency Input
Module
24 VDC
Note: All modules must be frequency or IRT8I modules for this configuration.
Wiring when total current draw is less than 10A
Individual
Power
Digital Input
Module
IF8u
Module
Digital Input
Module
24 VDC
24 VDC
24 VDC
Note: Use this configuration if using any “noisy” dc digital I/O modules in your system.
IRT8I module wiring separate from digital wiring
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Chapter 2: Installation and Wiring
Combination
Wiring when total current draw is greater than 10A
Power
Frequency Input
Module
IF8u
Module
2-5
Frequency Input
Module
24 VDC
Section 2.4
Installing the
Module
24 VDC
Note: All modules powered by the same power supply must be frequency or IRT8I modules for this configuration.
Total current draw through any base unit must not be greater than
10A
Installation of the analog module consists of:
•
Mounting the terminal base unit
•
Installing the IRT8I module into the terminal base unit
•
Installing the connecting wiring to the terminal base unit
If you are installing your module into a terminal base unit that is already installed, proceed to “Mounting the IRT8I Module on the Terminal Base Unit” on page 2-9.
2.4.1
Mounting the Terminal Base Unit on a DIN Rail
!
Attention
Do not remove or replace a terminal base unit when power is applied.
Interruption of the flexbus can result in unintended operation or machine motion.
1) Remove the cover plug (if used) in the male connector of the unit to which you are connecting this terminal base unit.
2) Check to make sure that the 16 pins in the male connector on the adjacent device are straight and in line so that the mating female connector on this terminal base unit will mate correctly.
User's Manual Pub.
0300242 ‐ 01 Rev.
A
2-6 Flex™ IO Isolated RTD/Thermocouple Module
3) Position the terminal base on the 35 x 7.5mm DIN rail A (A-B pt.no. 199-DR1;
46277-3) at a slight angle with hook B on the left side of the terminal base hooked into the right side of the unit on the left. Proceed as follows:
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Chapter 2: Installation and Wiring 2-7
4) Repeat the above steps to install the next terminal base.
2.4.2
Panel/Wall Mounting
Installation on a wall or panel consists of:
•
Laying out the drilling points on the wall or panel
•
Drilling the pilot holes for the mounting screws
•
Mounting the adapter mounting plate
•
Installing the terminal base units and securing them to the wall or panel
If you are installing your module into a terminal base unit that is already installed, proceed to “Mounting the IRT8I Module on the Terminal Base Unit” on page 2-9.
Use the mounting kit Cat. No. 1794-NM1 for panel/wall mounting.
User's Manual Pub.
0300242 ‐ 01 Rev.
A
2-8 Flex™ IO Isolated RTD/Thermocouple Module
To install the mounting plate on a wall or panel:
1) Lay out the required points on the wall/panel as shown in the drilling dimension drawing.
Drilling Dimensions for Panel/Wall Mounting of Flex IO
2) Drill the necessary holes for the #6 self-tapping mounting screws.
3) Mount the mounting plate (1) for the adapter module using two#6 self-tapping screws (18 included for mounting up to 8 modules and the adapter).
!
Attention
Make certain that the mounting plate is properly grounded to the panel. Refer to “Industrial Automation Wiring and Grounding
Guidelines,” publication1770-4.1.
4) Hold the adapter (2) at a slight angle and engage the top of the mounting plate in the indention on the rear of the adapter module.
5) Press the adapter down flush with the panel until the locking lever locks.
6) Position the terminal base unit up against the adapter and push the female bus connector into the adapter.
7) Secure to the wall with two #6 self-tapping screws.
8) Repeat for each remaining terminal base unit.
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Chapter 2: Installation and Wiring 2-9
Note: The adapter is capable of addressing eight modules. Do not exceed a maximum of eight terminal base units in your system.
2.4.3
Mounting the IRT8I Module on the Terminal Base Unit
The IRT8I isolated input module mounts on a 1794-TB3G or TB3GS terminal base unit.
1) Rotate the key-switch (1) on the terminal base unit (2) clockwise to position 3 as required for the IRT8I module.
2) Make certain the flexbus connector (3) is pushed all the way to the left to connect with the neighboring terminal base/adapter.
You cannot install the module unless the connector is fully extended.
3) Make sure that the pins on the bottom of the module are straight so they will align properly with the connector in the terminal base unit.
!
Attention
This module is UL listed only when used with listed Allen-Bradley catalog numbers 1794-TB3G or TB3GS terminal base units.
!
Attention
Remove field-side power before removing or inserting the module.
This module is designed so you can remove and insert it under backplane power. When you remove or insert a module with field-side power applied, an electrical arc may occur. An electrical arc can cause personal injury or property damage by:
•
sending an erroneous signal to your system’s field devices causing unintended machine motion
•
causing an explosion in a hazardous environment
Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance.
4) Position the module (4) with its alignment bar (5) aligned with the groove (6) on the terminal base.
5) Press firmly and evenly to seat the module in the terminal base unit. The module
User's Manual Pub.
0300242 ‐ 01 Rev.
A
2-10 Flex™ IO Isolated RTD/Thermocouple Module is seated when the latching mechanism (7) is locked into the module.
6) Repeat the above steps to install the next module in its terminal base unit.
Section 2.5
Field Wiring
Connections
Wiring to the IRT8I module is made through the terminal base unit on which the module mounts. Compatible terminal base units are:
1794sc-IRT8I Yes Yes
2.5.1
Field Wiring using a 1794-TB3G and TB3GS Terminal Base
1) Connect the individual signal wiring to numbered terminals on the 0–15 row (A) and 17–32 row(B) on the terminal base unit. Connect the input devices as shown in the wiring table on page 2-11 .
2) Terminate shields: to terminals 16 or 33 on row B, or 40 through 45 on row C.
3) Connect +24V dc to terminal 34 on the 34-51 row (C), and 24V common to terminal 35 on the 34-51 row (C).
!
Attention
To reduce susceptibility to noise, power IRT8I modules and digital modules from separate power supplies. Do not exceed a length of 33ft
(10m) for dc power cabling.
4) If daisy chaining the +24V dc power to the next base unit, connect a jumper from terminal 50 (+24V) on this base unit to terminal 34 and from terminal 51
(24V dc common) to terminal 35 on the next base unit.
!
Attention
Do not daisy chain power or ground from the IRT8I terminal base unit to any ac or dc digital module terminal base unit.
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Chapter 2: Installation and Wiring 2-11
!
Attention
The IRT8I module does not receive power from the backplane. +24V dc power must be applied to your module before operation. If power is not applied, the module position will appear to the adapter as an empty slot in your chassis. If the adapter does not recognize your module after installation is completed, cycle power to the adapter.
!
Attention
Use supply wire for 10˚C above surrounding ambient.
Figure 2-1
Table 2-1
Type of Input
RTD/Res 2-wire
Connect The Following
R IN+ IN- I Shield
1
1 2
Millivolt
1
Shield can be connected to chassis ground terminals 16, 33, and 40…45.
2
User's Manual Pub.
0300242 ‐ 01 Rev.
A
2-12 Flex™ IO Isolated RTD/Thermocouple Module
RTD/Resistance
2-wire
Jumper
1
3-wire
1
0
2
0
2
Thermocouple
+
1
1
2
-
mV Source
1
+ mV
-
2
Table 2-2
Numbers 0, 1, 2, and 3 are wiring numbers of the sensor used. For terminal numbers corresponding to
R, IN+, IN-, I, refer to Terminal Base Unit Wiring
Connections below.
+ Chassis
CJC1 C37
Ground
C38
- CJC
Tail
1
C39 A1
1
CJC2 C-46 C-47 C-48 B31
Terminals 37, 38, and 39, and 46, 47, and 48 are for cold junction compensation (with 38 and 47 chassis GND). Connect the tail of CJC 1 to terminal 1 and CJC2 to terminal 31 if channels 0…3 or 0…7 are configured for thermocouples.
Table 2-3
Channel Number
1794-TB3G and 1794-TB3GS Terminal Base Units
Signal Return (R) Input + Input I Return
(IN+) (-) (-)
1Terminals 16, 33, and 40…45 are chassis ground.
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Chapter 2: Installation and Wiring 2-13
!
Attention
Total current draw through the terminal base unit is limited to 10A.
Separate power connections to the terminal base unit may be necessary.
The following examples show how to wire the IF8U using the tables and diagrams listed above.
Figure 2-2 (RTD & Resistance Wiring Diagram)
R
User's Manual Pub.
0300242 ‐ 01 Rev.
A
2-14 Flex™ IO Isolated RTD/Thermocouple Module
Figure 2-3 (Thermocouple Wiring Diagram)
Figure 2-4 (Millivolt Wiring Diagram)
!
Attention
Digital and analog power must be supplied by an Isolated Secondary
Limited Energy Low Voltage source.
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Chapter 2: Installation and Wiring 2-15
Section 2.6
Module Indicators
The IRT8I module has one status indicator (OK) that is on when power is applied and no hardware faults are present. See figure below.
Figure 2-5
1
2
Item Description
4
2 Module key-switch position
3
Table 2-4 (Module Status LED)
Module
State
New
Not
Config
Idle
Active
Fault
Fatal
Fault
Power up initialized complete and passed Self-Test. Loads stored configuration, if it exist. Read Module Information Block. (see notes)
Module has not received configuration from Master. It can Set and
Get attributes. (see notes)
Controller in Program mode.
Communications normal
Controller in Run mode & Communication Is normal
FlexIO Comm. Fault or PU bit is one and /Fault=0
Module fails self tests or detects illegal state transition
State
RED, blink
@1 Hz
GREEN, blink @1 Hz
GREEN, solid
GREEN, solid
GREEN, solid
RED, solid
User's Manual Pub.
0300242 ‐ 01 Rev.
A
2-16 Flex™ IO Isolated RTD/Thermocouple Module
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Chapter 3
Configuring the 1794sc-IRT8I
Using RSLogix 5000
This chapter covers the following subjects:
•
Things you should know
•
Module memory map
•
Configure generic profile
•
Module configuration
•
Reading input/status data
Section 3.1
Things You
Should Know
This chapter describes how to configure the IRT8I module for the ControlLogix and
CompactLogix system. In the examples below, the Control Net adapter and/or Ethernet adapter were used for communication between the Logix processor and the Flex IO bus.
Note: Refer to the associated I/O scanner documentation if using a SLC controller with Control Net.
Note: If using a PLC 5 controller, refer to the PLC 5 controller documentation for Control Net configuration information.
!
Attention
The Remote I/O and Device Net adapters do not support the 1794sc-
IRT8I module. The IRT8I module is supported only by the Control Net and Ethernet adapters.
Section 3.2
Module Memory
Map
The following figure describes the data mapping for the module. The configuration image is written to the module using tags generated by the “generic Flex module” profile used to represent the IRT8I within RSLogix 5000. See section 3.3.3 for more details.
Input data and status data can be read from the module using the input image and status image. Again, tags generated by the “generic Flex module” profile will be used to read the input and status image data.
User's Manual Pub.
0300242 ‐ 01 Rev.
A
3-2 Flex™ IO Isolated RTD/Thermocouple Module
Figure 3-1 (Module Memory Map)
Read
Input Image
I:0 to I:7( 8 words)
(Input Data)
Read
Status Image
S:0 to S:3 (4 Words)
(Status Data)
Write
Configuration Image
C:0 to C:32 (33 words)
(Configuration Data)
1794sc-IRT8I
Section 3.3
Configure
Generic Profile
The generic Flex module profile is used to represent the IRT8I module within RSLogix
5000 since there’s no custom profile available. Before the generic profile can be added to the IO configuration, the proper communication module needs to be added to the IO configuration first. Follow the procedure below to add a communication module to
RSLogix 5000.
1.
Add the new local communication module to your project.
2.
Configure the local module, including: a.
Naming the module b.
Choosing a Communication Format c.
Setting the Revision level d.
Setting the module location as necessary such as the slot number for a
1756-CNB module e.
Choosing an Electronic Keying method
3.
Add the new remote module to your project, such as a Flex Control Net adapter or Ethernet Adapter (i.e. 1794-ACN15 or 1794-AENT, respectively).
4.
Configure the remote module similarly to the local module
5.
Download the configuration to the controller
Note: If you are using Control Net, you must schedule the network using
“RSNetworks for Control Net” after adding the local and remote communication modules.
Note: When you create a new RSLogix 5000 project with the CompactLogix
1769-L32C or L35CR controller, The Controller Organizer creates a Control
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Chapter 3: Configuring the 1794sc-IRT8I for ControlLogix/CompactLogix 3-3
Net port in the local chassis. In this case, you don’t need to add a separate local communication module.
Note: When you create a new RSLogix 5000 project with the CompactLogix
1769-L23E, 1769-L32E or L35E controller, The Controller Organizer creates a Ethernet port in the local chassis. In this case, you don’t need to add a separate local communication module.
3.3.1
Add a Local Ethernet Bridge Module
After you have started RSLogix 5000 software and created a controller project, you can add Ethernet communication modules. A local Ethernet communication module is a module that resides in the same chassis as the controller.
1.
Select a New Module for the I/O Configuration.
Right-click on I/O
Configuration
Select New Module
2.
Select the module type from the Select Module Type pop-up. The example below uses a 1756-ENBT module.
Select the local Ethernet bridge module
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Click OK
3-4
Name the module
Flex™ IO Isolated RTD/Thermocouple Module
3.
Configure the local Ethernet bridge module.
Enter IP address of ENBT
Select the module’s slot number
Select the module’s revision level
Select electronic keying level
Click OK
3.3.2
Add a Remote Ethernet Flex Adapter
After you have added the local Ethernet communication module, you must add remote
Ethernet communication modules. A remote Ethernet module is a module that resides in a separate chassis from the controller.
!
Attention
If you plan to use the Flex Control Net adapter, you will need to install the 1794sc-IRT8I EDS file before scheduling the network. The latest
EDS files can be found at (www.spectrumcontrols.com).
1.
Select a New Module for the I/O Configuration.
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Chapter 3: Configuring the 1794sc-IRT8I for ControlLogix/CompactLogix 3-5
Right-click on the local communication module
Select New Module
2.
Select the module type from the Select Module Type pop-up.
Select the remote Ethernet communication module.
3.
Configure the remote Ethernet communication module.
Click OK
User's Manual Pub.
0300242 ‐ 01 Rev.
A
3-6 Flex™ IO Isolated RTD/Thermocouple Module
Name the module
Enter IP address of ENBT
Select the comm. format
Select the chassis size
Select the module revision level
Select electronic keying level
Click OK
3.3.3
Add the Generic Flex Module
After adding the remote Ethernet communication module, the Generic Flex Module must be added. The Generic Flex Module is required because there is no custom profile for the
1794sc-IRT8I module. The following steps must be followed to add the Generic Flex
Module.
1.
Select a New Module for the I/O Configuration.
Right-click on the local communication module
Select New Module
2.
Select the module type from the Select Module Type pop-up.
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Chapter 3: Configuring the 1794sc-IRT8I for ControlLogix/CompactLogix 3-7
Select Generic Flex
Module
Click OK
3.
Configure the Generic Flex Module (i.e. 1794sc-IRT8I)
Name the module
Enter “Input Data – INT” for
Comm. Format
Enter module slot #
Enter the input size
(Always 8 for the IRT8I)
Enter the config. size
(Always 49 for the IRT8I)
Enter the status size
(Always 4 for the IRT8I)
Click OK
Section 3.4
Module
Configuration
The addition of the Generic Flex Module profile makes it possible to enter the configuration data for the IRT8I module. The configuration tags for the IRT8I are located under the controller tags. The following figure describes the tag structure allocated by the Generic Flex Module profile.
User's Manual Pub.
0300242 ‐ 01 Rev.
A
3-8 Flex™ IO Isolated RTD/Thermocouple Module
[Name of remote communication module]:e:x.Data[0 to 184] e = IRT8I slot number x = Image Type (i.e. C, I, or O)
Note: 185 words are allocated by the Generic Flex Module profile, but only
49 are actually used by the IRT8I module for configuration.
In the example above, the configuration tags for the first IRT8I module would appear as shown in the image below.
Figure 3-2 (Configuration Tags Example)
Note: The slot number is “0” and the Image type is “C” for configuration.
The following table describes the configuration settings for the 1794sc-IRT8I module.
Table 3-1 (Configuration Table)
Usage (16 bit words):
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
C:0 R
1
R
1
F7 F6 F5 F4 R
1
R
1
R
1
F3 F2 F1 F0 R
C:1 Temp
Units
Ch0
Disable
CJC
Ch0
Open
Circuit
Ch0
R
1
Data
Format
Ch0
Input
Filter
Ch0
Input
Type
CH0
C:2 Temp
Units
Ch1
C:3 Temp
Units
Ch2
C:4 Temp
Units
Ch3
C:5 Temp
Units
Ch4
C:6 Temp
Units
Ch5
Disable
CJC
Ch1
Disable
CJC
Ch2
Disable
CJC
Ch3
Disable
CJC
Ch4
Disable
CJC
Ch5
Open
Circuit
Ch1
Open
Circuit
Ch2
Open
Circuit
Ch3
Open
Circuit
Ch4
Open
Circuit
Ch5
R
R
R
R
R
1
1
1
1
1
Data
Format
Ch1
Data
Format
Ch2
Data
Format
Ch3
Data
Format
Ch4
Data
Format
Ch5
Input
Filter
Ch1
Input
Filter
Ch2
Input
Filter
Ch3
Input
Filter
Ch4
Input
Filter
Ch5
Input
Type
CH1
Input
Type
CH2
Input
Type
CH3
Input
Type
CH4
Input
Type
CH5
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Chapter 3: Configuring the 1794sc-IRT8I for ControlLogix/CompactLogix 3-9
Usage (16 bit words):
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
C:7 Temp Disable Open Data Input Input
Units
Ch6
CJC
Ch6
Circuit
Ch6
R
1
Format
Ch6
Filter
Ch6
Type
CH6
C:8 Temp
Units
Ch7
Disable
CJC
Ch7
Open
Circuit
Ch7
R
1
Data
Format
Ch7
Input
Filter
Ch7
Input
Type
CH7
C:9 CH0 User Low Alarm Threshold
C:10 CH0 User High Alarm Threshold
C:11 CH0 User Alarm Deadband
C:12 CH1 User Low Alarm Threshold
C:13 CH1 User High Alarm Threshold
C:14 CH1 User Alarm Deadband
C:15 CH2 User Low Alarm Threshold
C:16 CH2 User High Alarm Threshold
C:17 CH2 User Alarm Deadband
C:18 CH3 User Low Alarm Threshold
C:19 CH3 User High Alarm Threshold
C:20 CH3 User Alarm Deadband
C:21 CH4 User Low Alarm Threshold
C:22 CH4 User High Alarm Threshold
C:23 CH4 User Alarm Deadband
C:24 CH5 User Low Alarm Threshold
C:25 CH5 User High Alarm Threshold
C:26 CH5 User Alarm Deadband
C:27 CH6 User Low Alarm Threshold
C:28 CH6 User High Alarm Threshold
C:29 CH6 User Alarm Deadband
C:30 CH7 User Low Alarm Threshold
C:31 CH7 User High Alarm Threshold
1
C:32 CH7 User Alarm Deadband
Reserved set to zero
3.4.1
Fault Mode [Word 0 (Bits 2,3,4,5,10,11,12,13)]
The fault mode bits are used to enable or disable “broken wire detection”. See table below.
Table 3-2 (Fault Mode)
State Function
0 Disabled
1 Enable Broken Wire Detection
3.4.2
Input Type [Words 1 – 8 (Bits 0 to 4)]
Use the table below to select the input type for each channel.
Table 3-3 (Input Type)
Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Range:
0 0 0 0 0 B Thermocouple
0 0 0 0 1 C Thermocouple
0 0 0 1 0 E Thermocouple
0 0 0 1 1 J Thermocouple
User's Manual Pub.
0300242 ‐ 01 Rev.
A
3-10 Flex™ IO Isolated RTD/Thermocouple Module
Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Range:
0 0 1 0 0 K
0 0 1 0 1 N Thermocouple
0 0 1 1 0 R Thermocouple
0 0 1 1 1 S Thermocouple
0 1 0 0 0 T Thermocouple
0 1 0 0 1 100 α 0.385
0 1 0 1 0 200 α 0.385
0 1 0 1 1 500 α 0.385
0 1 1 0 0 1000 α 0.385
0 1 1 0 1 100 α 0.3916
0 1 1 1 0 200 α 0.3916
0 1 1 1 1 500 α 0.3916
1 0 0 0 0 1000 α 0.3916
1 0 0 0 1 10 α 0.426
1 0 0 1 0 100 α 0.618
1 0 0 1 1 120 α 0.672
1 0 1 0 0 604 α 0.518 to to Ω to Ω
3.4.3
Input Filter [Words 1 – 8 (Bits 5 to 7)
Use the table below to select the appropriate filter for each channel.
Table 3-4 (Filter Settings)
Bit 7 Bit 6 Bit 5 ADC Filter:
1 1 0 *Unused
1 1 1 *Unused
3.4.4
Data Format [Words 1 – 8 (Bits 8 to 10)
Select the appropriate data type for each channel using the table below. Refer to Table
3-6 for data type ranges.
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Chapter 3: Configuring the 1794sc-IRT8I for ControlLogix/CompactLogix 3-11
Table 3-5 (Data Format)
Bit 10 Bit9 Bit 8 Format:
0 0 1 Engineering Units X10
1 0 0
1
Percent of Full Scale
1
0
CJC EU
1
CJC Scaled for PID
CJC Percent of Full Scale
1
If selected, the CJC format will override all ranges/formats and report the indicated CJC value for this channel. Channel zero will report CJC0 directly. Channel 7 will report CJC1 directly.
All others will be distributed values between CJC0 and CJC1 based on channel position.
Table 3-6 (Data Ranges)
Input Type
B Type Thermocouple
Range
300 to 1820 ˚ C
(572 to 3308 ˚ F)
C Type Thermocouple
E Type Thermocouple
J Type Thermocouple
K Type Thermocouple
N Type Thermocouple
R Type Thermocouple
S Type Thermocouple
T Type Thermocouple
100 Ω Pt α 0.385
200 Ω Pt α 0.385
500 Ω Pt α 0.385
1000 Ω Pt α 0.385
100 Ω Pt α 0.3916
200 Ω Pt α 0.3916
500 Ω Pt α 0.3916
1000 Ω Pt α 0.3916
10 Ω Cu α 0.426
100 Ω Ni α 0.618
120 Ω Ni α 0.672
604 Ω NiFe α 0.518
Resistance
0 to 2315 ˚ C
(32 to 4199 ˚ F)
-270 to 1000 ˚ C
(-454 to 1832 ˚ F)
-210 to 1200 ˚ C
(-346 to 2192 ˚ F)
-270 to 1370 ˚ C
(-454 to 2498 ˚ F)
-210 to 1300 ˚ C
(-346 to 2372 ˚ F)
0 to 1768 ˚ C
(32 to 3214 ˚ F)
0 to 1768 ˚ C
(32 to 3214 ˚ F)
-270 to 400 ˚ C
(-270 to 752 ˚ F)
-200 to 850 ˚ C
(-328 to 1562 ˚ F)
-200 to 850 ˚ C
(-328 to 1562 ˚ F)
-200 to 850 ˚ C
(-328 to 1562 ˚ F)
-200 to 850 ˚ C
(-328 to 1562 ˚ F)
-200 to 630 ˚ C
(-328 to 1166 ˚ F)
-200 to 630 ˚ C
(-328 to 1166 ˚ F)
-200 to 630 ˚ C
(-328 to 1166 ˚ F)
-200 to 630 ˚ C
(-328 to 1166 ˚ F)
-100 to 260 ˚ C
(-148 to 500 ˚ F)
-100 to 260 ˚ C
(-148 to 500 ˚ F)
-80 to 260 ˚ C
(-112 to 500 ˚ F)
-100 to 200 ˚ C
(-148 to 392 ˚ F)
0 to 150 Ω
0 to 1000 Ω
0 to 3000 Ω
Eng. Units
3000 to 18200
(5720 to 33080)
0 to 23150
(320 to 41990)
-2700 to 10000
(-4540 to 18320)
-2100 to 12000
(-3460 to 21920)
-2700 to 13700
(-4540 to 24980)
-2100 to 13000
(-3460 to 23720)
0 to 17680
(320 to 32140)
0 to 17680
(320 to 32140)
-2700 to 4000
(-2700 to 7520)
-2000 to 8500
(-3280 to 15620)
-2000 to 8500
(-3280 to 15620)
-2000 to 8500
(-3280 to 15620)
-2000 to 8500
(-3280 to 15620)
-2000 to 6300
(-3280 to 11660)
-2000 to 6300
(-3280 to 11660)
-2000 to 6300
(-3280 to 11660)
-2000 to 6300
(-3280 to 11660)
-1000 to 2600
(-1480 to 5000)
-1000 to 2600
(-1480 to 5000)
-800 to 2600
(-1120 to 5000)
-1000 to 2000
(-1480 to 3920)
0 to 15000
0 to 10000
0 to 30000
Eng Units X10 Raw/Prop
300 to 1820 -32768 to 32767
PID
0 to 16383
Percent
0 to 10000
(572 to 3308)
-32768 to 32767 0 to 16383 0 to 10000 0 to 2315
(32 to 4199)
-270 to 1000
(-454 to 1832)
-210 to 1200
(-346 to 2192)
-32768 to 32767
-32768 to 32767
0 to 16383
0 to 16383
0 to 10000
0 to 10000
-32768 to 32767 0 to 16383 0 to 10000 -270 to 1370
(-454 to 2498)
-210 to 1300
(-346 to 2372)
0 to 1768
(32 to 3214)
0 to 1768
(32 to 3214)
-270 to 400
(-270 to 752)
-200 to 850
(-328 to 1562)
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
0 to 16383
0 to 16383
0 to 16383
0 to 16383
0 to 16383
0 to 10000
0 to 10000
0 to 10000
0 to 10000
0 to 10000
-32768 to 32767 0 to 16383 0 to 10000 -200 to 850
(-328 to 1562)
-200 to 850
(-328 to 1562)
-200 to 850
(-328 to 1562)
-200 to 630
(-328 to 1166)
-200 to 630
(-328 to 1166)
-200 to 630
(-328 to 1166)
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
0 to 16383
0 to 16383
0 to 16383
0 to 16383
0 to 16383
0 to 10000
0 to 10000
0 to 10000
0 to 10000
0 to 10000
-200 to 630
(-328 to 1166)
-100 to 260
(-148 to 500)
-100 to 260
(-148 to 500)
-80 to 260
(-112 to 500)
-100 to 200
(-148 to 392)
0 to 1500
0 to 1000
0 to 3000
-32768 to 32767 0 to 16383 0 to 10000
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
-32768 to 32767
0 to 16383
0 to 16383
0 to 16383
0 to 16383
0 to 16383
0 to 16383
0 to 16383
0 to 10000
0 to 10000
0 to 10000
0 to 10000
0 to 10000
0 to 10000
0 to 10000
User's Manual Pub.
0300242 ‐ 01 Rev.
A
3-12 Flex™ IO Isolated RTD/Thermocouple Module
3.4.5
Open Circuit Mode [Words 1 – 8 (Bits 12 & 13)]
The open circuit mode determines the fail-safe data value each channel is to default to in the event of an open circuit condition. The table below lists the available options.
Table 3-7 (Open Circuit Mode)
Bit 13 Bit 12 Open Circuit Mode:
0 0 Zero analog value on broken input.
0
1
1
0
Set analog value to Max scale on broken input.
Set analog value to Min scale on broken input.
3.4.6
Disable CJC [Words 1 – 8 (Bit 14)]
This bit is used to disable CJC compensation for the associated channel.
Table 3-8 (Disable CJC)
State Function
0 CJCs
1
1
Disabled
1
This field is only used if the input type is a thermocouple and the format is not a CJC format. No compensation is performed on the thermocouple when disabled.
3.4.7
Temperature Units [Words 1 – 8 (Bit 15)]
This bit enables Celsius or Fahrenheit for the associated channel.
Note: If the associated channel is not configured for an RTD or thermocouple, the temperature units have no effect.
Table 3-9 (Temperature Units)
State Function
3.4.8
Low Alarm Threshold [Words 9,12,15,18,21,24,27,30]
Low alarm threshold setting for channels 0 through 7, respectively.
Note: The data range is determined by the data format selected.
3.4.9
High Alarm Threshold [Words 10,13,16,19,22,25,28,31]
High alarm threshold setting for channels 0 through 7, respectively.
Note: The data range is determined by the data format selected.
3.4.10
User Alarm Deadband [Words 11,14,17,20,23,26,29,32]
The deadband is a range through which the measured input may be varied without initiating and alarm response. The deadband setting must adhere to the following rules:
•
The deadband must be greater or equal to zero.
•
The deadband cannot exceed 25% of full scale.
•
The alarm limits including deadband may not exceed the user range limits.
•
The low alarm including deadband may not overlap the high alarm including
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Chapter 3: Configuring the 1794sc-IRT8I for ControlLogix/CompactLogix 3-13 deadband.
If any of these rules are violated, a configuration error is declared, and the alarm is disabled. The notable exception is when the “low” is equal to the “high” and both are set to zero. In this case, user alarms are disabled, the deadband is ignored, and no fault is declared.
Note: The data range is determined by the data format selected.
The alarm deadband allows the user to define hysteresis for alarms. The alarm set threshold may differ from the alarm clear threshold, depending on the deadband, as illustrated below. A value must transition through the indicated threshold (see dashed arrows) to have the indicated effect.
If a CJC format is selected, the alarm limits apply to that CJC format, not to that channel’s analog input.
Figure 3-3 (Alarm DeadBand)
Low Alarm Threshold (Set)
High Alarm Threshold (Set)
Low Alarm Dead Band Normal Dead Band High Alarm
Low Alarm Threshold + deadband
(Clear)
High Alarm Threshold – deadband
(Clear)
Section 3.5
Read Input
& Status Data
Input and status data is read for each channel, converted to a scaled digital value, and stored in the controller tags. The following figure describes the tag structure allocated by the Generic Flex Module profile.
[Name of remote communication module]:e:x.Data[0 to 184] e = IRT8I slot number x = Image Type (i.e. C, I, or O)
Using the remote Ethernet adapter example, the input/status tags would appear under the controller tags as shown in the figure below.
User's Manual Pub.
0300242 ‐ 01 Rev.
A
3-14 Flex™ IO Isolated RTD/Thermocouple Module
Figure 3-4 (Input/Status Tags)
Note: The slot number is “0” and the image type is “I”.
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Chapter 3: Configuring the 1794sc-IRT8I for ControlLogix/CompactLogix 3-15
The table below describes the input and status mapping.
Table 3-10 (Input & Status)
Usage (16 bit words):
I:0 Channel 0 input Data.
I:1 Channel 1 input Data.
I:2 Channel 2 input Data.
I:3 Channel 3 input Data.
I:4 Channel 4 input Data.
I:5 Channel 5 input Data.
I:6 Channel 6 input Data.
I:7 Channel 7 input Data.
S:2 Reserved
9 8 7 6 5 4 3 2 1 0
S:0 OverRange (CH0/Bit 8, CH1/Bit 9, …)
S:1
5
User HI Alarms (CH0/Bit8, CH1/Bit9, …)
CJC
Alarm
4
5
UnderRange (CH0/Bit 0, CH1/Bit 1, …)
User LO Alarms(CH0/Bit0, CH1/Bit1, …)
6,
4
Open Circuit Alarms (CH0/Bit0,
CH1/Bit1, …)
S:3 Reserved Diagnostic Code (See )
3.5.1
Input Data [Words 0 to 7]
Words 0 through 7 display the digital value for channel inputs 0 through 7, respectively.
Scaling/range is determined by the data format selected. See 3.4.4 for more details.
3.5.2
UnderRange Alarms [Word 8 (Bits 0 to 7)]
The under range flag is set for the associated channel when the channel data value is below the minimum scale for the selected range.
3.5.3
OverRange Alarm [Word 8 (Bits 8 to 15)]
The over range flag is set for the associated channel when the channel data value is above the maximum scale for the selected range.
3.5.4
User Low Alarm [Word 9 (Bits 0 to 7)]
The user low alarm flag is set for the associated channel when the channel data value is below the user low alarm threshold.
3.5.5
User High Alarm [Word 9 (Bits 8 to 15)]
The user high alarm flag is set for the associated channel when the channel data value is above the user high alarm threshold.
3.5.6
Open Circuit Alarm [Word 10 (Bits 0 to 7)]
If set, the associated channel has detected a shorted or open circuit condition.
4
For the 0 to 20 mA range, a zero reading is valid. Therefore, under range will not trigger at the low terminus of zero, but will instead trigger when the signal goes negative at or below %2.5 of full scale. 20 –
0 = 20. -0.025 X 20 = -0.5mA.
6
5
Channel specific range alarms will apply to CJC values if a CJC format is selected for that channel.
Channel specific open circuit alarm will not be set if a CJC format is selected for that channel.
User's Manual Pub.
0300242 ‐ 01 Rev.
A
3-16 Flex™ IO Isolated RTD/Thermocouple Module
3.5.7
CJC Alarm [Word 10 (Bits 8 & 9)]
The CJC alarm indicates a broken wire condition for both CJC sensors. Refer to the table below.
Table 3-11 (CJC Alarms)
Bit 9 Bit 8 CJC Alarm:
1 1 Both CJC1 and CJC2 are broken.
3.5.8
Diagnostics [Word 11 (Bits 0 to 7)]
The diagnostic byte is used to indicate module faults. Refer to the table below for more information.
Table 3-12 (Diagnostics)
Hex Error Code: Diagnostic:
0x00 NO_ERRORS
0x10 CH0_RANGE_CFG_ERROR
0x11 CH1_RANGE_CFG_ERROR
0x12 CH2_RANGE_CFG_ERROR
0x13 CH3_RANGE_CFG_ERROR
0x14 CH4_RANGE_CFG_ERROR
0x15 CH5_RANGE_CFG_ERROR
0x16 CH6_RANGE_CFG_ERROR
0x17 CH7_RANGE_CFG_ERROR
0x20 CH0_FORMAT_CFG_ERROR
0x21 CH1_FORMAT_CFG_ERROR
0x22 CH2_FORMAT_CFG_ERROR
0x23 CH3_FORMAT_CFG_ERROR
0x24 CH4_FORMAT_CFG_ERROR
0x25 CH5_FORMAT_CFG_ERROR
0x26 CH6_FORMAT_CFG_ERROR
0x27 CH7_FORMAT_CFG_ERROR
0x30 CH0_FILTER_CFG_ERROR
0x31 CH1_FILTER_CFG_ERROR
0x32 CH2_FILTER_CFG_ERROR
0x33 CH3_FILTER_CFG_ERROR
0x34 CH4_FILTER_CFG_ERROR
0x35 CH5_FILTER_CFG_ERROR
0x36 CH6_FILTER_CFG_ERROR
0x37 CH7_FILTER_CFG_ERROR
0x40 CH0_HI_LO_ALARM_CFG_ERROR
0x41 CH1_HI_LO_ALARM_CFG_ERROR
0x42 CH2_HI_LO_ALARM_CFG_ERROR
0x43 CH3_HI_LO_ALARM_CFG_ERROR
0x44 CH4_HI_LO_ALARM_CFG_ERROR
0x45 CH5_HI_LO_ALARM_CFG_ERROR
0x46 CH6_HI_LO_ALARM_CFG_ERROR
0x47 CH7_HI_LO_ALARM_CFG_ERROR
0x50 CH0_OUT_OF_RANGE_ERROR
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Chapter 3: Configuring the 1794sc-IRT8I for ControlLogix/CompactLogix
Hex Error Code: Diagnostic:
0x51 CH1_OUT_OF_RANGE_ERROR
0x52 CH2_OUT_OF_RANGE_ERROR
0x53 CH3_OUT_OF_RANGE_ERROR
0x54 CH4_OUT_OF_RANGE_ERROR
0x55 CH5_OUT_OF_RANGE_ERROR
0x56 CH6_OUT_OF_RANGE_ERROR
0x57 CH7_OUT_OF_RANGE_ERROR
0x59 Unused module cfg bits set
0x5F MODULE_NOT_CONFIGURED
0x60
0x61
CH0 Cal Offset CFG Error
CH1 Cal Offset CFG Error
0x62
0x63
0x64
0x65
CH2 Cal Offset CFG Error
CH3 Cal Offset CFG Error
CH4 Cal Offset CFG Error
CH5 Cal Offset CFG Error
0x66
0x67
0x70
0x71
0x72
0x73
0x74
0x75
CH6 Cal Offset CFG Error
CH7 Cal Offset CFG Error
CH0 CJC Offset CFG Error
CH1 CJC Offset CFG Error
CH2 CJC Offset CFG Error
CH3 CJC Offset CFG Error
CH4 CJC Offset CFG Error
CH5 CJC Offset CFG Error
0x76
0x77
CH6 CJC Offset CFG Error
CH7 CJC Offset CFG Error
0x80 FIELD_PWR_FAULT
0x90 CH0_CAL_ERROR
0x91 CH1_CAL_ERROR
0x92 CH2_CAL_ERROR
0x93 CH3_CAL_ERROR
0x94 CH4_CAL_ERROR
0x95 CH5_CAL_ERROR
0x96 CH6_CAL_ERROR
0x97 CH7_CAL_ERROR
0xA0 CH0_IOCOMM_FAILED
0xA1 CH1_IOCOMM_FAILED
0xA2 CH2_IOCOMM_FAILED
0xA3 CH3_IOCOMM_FAILED
0xA4 CH4_IOCOMM_FAILED
0xA5 CH5_IOCOMM_FAILED
0xA6 CH6_IOCOMM_FAILED
0xA7 CH7_IOCOMM_FAILED
0xB0 CH0_BROKEN_INPUT
0xB1 CH1_BROKEN_INPUT
0xB2 CH2_BROKEN_INPUT
0xB3 CH3_BROKEN_INPUT
0xB4 CH4_BROKEN_INPUT
0xB5 CH5_BROKEN_INPUT
0xB6 CH6_BROKEN_INPUT
0xB7 CH7_BROKEN_INPUT
0xC0 CJC0_BROKEN_INPUT
0xC1 CJC1_BROKEN_INPUT
0xC2 CJC_BOTH_BROKEN_INPUT
User's Manual Pub.
0300242 ‐ 01 Rev.
A
3-17
3-18 Flex™ IO Isolated RTD/Thermocouple Module
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Appendix A
Module Specifications
Number of inputs
Module Location
Nominal input voltage ranges
Supported thermocouple types
Supported RTD/Resistance types
8 channels
Cat. No. 1794-TB3G, 1794-TB3GS
Terminal Base Units
±50 mV, ±100 mV
Type °C Range °F Range
B 300…1820 °C (572…3308 °F)
C 0…2315 °C (32…4199 °F)
E -270…1000 °C (-454…1832 °F)
J -210…1200 °C (-346…2192 °F)
K -270…1370 °C (-454…2498 °F)
N -210…1300 °C (-346…2372 °F)
R 0…1768 °C (32…3214 °F)
S 0…1768 °C (32…3214 °F)
T -270…400 °C (-454…752 °F)
RTD
100 Ω Pt α = 0.385
-200…850 °C (-328…1562 °F)
200 Ω Pt α = 0.385
-200…850 °C (-328…1562 °F)
500 Ω Pt α = 0.385
-200…850 °C (-328…1562 °F)
1000 Ω Pt α = 0.385
-200…850 °C (-328…1562 °F)
100 Ω Pt α = 0.392
-200…630 °C (-328…1166 °F)
200 Ω Pt α = 0.392
-200…630 °C (-328…1166 °F)
500 Ω Pt α = 0.392
-200…630 °C (-328…1166 °F)
1000 Ω Pt α = 0.392
-200…630 °C (-328…1166 °F)
10 Ω Cu α = 0.426
-100…260 °C (-148…500 °F)
100 Ω Ni α = 0.618
-100…260 °C (-148…500 °F)
120 Ω Ni α = 0.672
-80…260 °C (-112…500 °F)
604 Ω NiFe α = 0.518
-100…200 °C (-148…392 °F)
Resistance
0…150 Ω
0…1000 Ω
0…3000 Ω
User's Manual Pub.
0300242 ‐ 01 Rev.
A
A-2 Flex™ IO Isolated RTD/Thermocouple Module
Data format
Input Impedance
Common mode rejection
Isolation voltage (continuous voltage withstand rating)
Open circuit protection
Engineering Units X1
Engineering Units X10
Raw/Proportional Counts
Scaled for PID
Percent of full scale
>1 M ohms for voltage, thermocouple, RTD and resistance inputs
60 db @ 5V peak-to-peak, 50…60 Hz
User power to Backplane:24 VDC continuous
Channel to Backplane: 24 VDC continuous
Channel to Channel: 24 VDC continuous.
Channel to User power: 24 VDC continuous
Open circuit detection bias <1 uA with
ON/OFF capability
Overvoltage capability
Cold junction compensation Range
Cold junction compensator
Flexbus current
Power dissipation
Thermal dissipation
Keyswitch position
Module Accuracy
Voltage mode ± 24 VDC continuous (ten minutes)
-20…100 °C
A-B catalog number 1794-CJC2
80 mA
7.25 W max @ 31.2V dc
Max 10.2 BTU/hr @ 31.2V dc
3
Thermocouple Accuracy with 4.17 Hz filter using Linearization per ITS-90
Type J (-50 ˚ C to 1200 ˚ C):
Type J (-210 ˚ C to -50 ˚ C):
Type N (-80 ˚ C to 1300 ˚ C):
Type N (-250 ˚ C to -80 ˚ C):
Type T (-180 ˚ C to 400 ˚ C):
Type T (-270 ˚ C to -180 ˚ C):
Type K (-180 ˚ C to 1370 ˚ C):
Type K (-270 ˚ C to -180 ˚ C):
Type E (-130 ˚ C to 1000 ˚ C):
Type E (-270 ˚ C to -130 ˚ C):
Type C (0 ˚ C to 2315 ˚ C):
Type B (600 ˚ C to 1800 ˚ C):
Type B (300 ˚ C to 600 ˚ C):
Type S (140 ˚ C to -1760 ˚ C):
Type S (0 ˚ C to 140 ˚ C):
Type R (280 ˚ C to -1760 ˚ C):
Type R (0 ˚ C to 280 ˚ C):
CJC accuracy
Voltage Accuracy with 4.17 Hz filter
Accuracy Accuracy
25°C 55°C
Repeatability
Limit
Filter Filter
± 0.6 °C ± 2.3 °C
± 0.8 °C ± 3.3 °C
± 1.0 °C ± 1.5 °C
± 1.2 °C ± 3.0 °C
± 1.0 °C ± 1.5 °C
± 5.4 °C ± 8.5 °C
Hz filter
± 0.17 °C
± 0.25 °C
± 0.3 °C
± 1.9 °C
± 0.2 °C
± 1.5 °C
± 1.0 °C ± 1.5°C ± 0.3 °C
± 7.5 °C ± 11.5 °C ± 3.6 °C
± 0.5 °C ± 1.5 °C ± 0.1°C
± 4.2 °C ± 7.3 °C
± 1.8 °C ± 3.5 °C
± 3.0 °C ± 4.0 °C
± 3.0 °C ± 8.0 °C
± 1.7 °C ± 2.6 °C
± 1.2 °C
± 0.9 °C
± 1°C
± 2°C
± 0.55 °C
± 1.7 °C ± 5.0 °C
± 1.7 °C ± 2.6 °C
± 1.7 °C ± 5.0 °C
± 1.0 °C 3.0 °C
± 1.0 °C
± 0.4 °C
± 1.0 °C
± 0.8 °C
Repeatability
Accuracy
°25C
Accuracy
°55C
Limit
At °25C & 4.17
Hz filter
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Appendix A: Module Specifications A-3
±50 mV range
±100 mV range
±20uV
±40uV
24V dc nom
±35uV
±60uV
240 mA @ 24V dc
94 x 94 x 69 mm
(3.7 x 3.7 x 2.7 in.)
±10uV
±13uV
Resistance Accuracy with 4.17 Hz filter
Accuracy
°25C
±0.15
Accuracy
°55C
Repeatability
Limit
At °25C & 4.17
Hz filter
0-150 ohms range
0-1000 ohms range
0-3000 ohms range
±1.0 ohms ±2.0 ohms ±100 milliohms
±1.5 ohms ±2.5 ohms ±100 milliohms
Accuracy
°C
Accuracy
°C
RTD Accuracy
With 4.17 Hz filters
Platinum 385 (100, 200, 500 and 1000 ohms) (IEC751 1983, Amend 2 1995;
JISC 1604 1997)
0°55C
Platinum 3916 (100, 200, 500 and 1000 ohms) (JISC 1604: 1981) ± 0.6 °C ± 1.1 °C
Nickel 618 (100 ohms) (DIN 43760
Sept. 1987) ± 0.3 °C ± 0.5 °C
Nickel 672(120 ohms) (DIN 43760
Sept. 1987) ± 0.3 °C ± 0.5 °C
Nickel-Iron (518) (MINCO Application
Aid #18,Date 5/90)
Copper 426 (10 ohms) (SAMA RC21-4-
1966)
°25C
± 0.7 °C ± 1.2 °C
± 0.4 °C
± 2.4 °C
± 0.7 °C
± 2.8 °C
Repeatability
Limit
Hz filter
± 0.1 °C
± 0.1 °C
± 0.1 °C
± 0.1 °C
± 0.1 °C
± 0.1 °C
General Specifications
Voltage range
Supply current
Dimensions (with module installed in base)
HxWxD approx.
Environmental Conditions
Temperature, operating
Temperature, storage
Relative humidity
Vibration
Shock
Operating
Non-operating
Emissions
ESD immunity
0…55 °C (-32…131 °F)
–40…85 °C (–40…185 °F)
IEC 60068-2-30
5…95% non-condensing
IEC60068-2-6:
5 g @ 10…500Hz
IEC60068-2-27:
20 g
25 g
IEC61000-6-4
CISPR 11:
Group 1, Class A (with appropriate enclosure)
IEC 61000-6-2:
6 kV contact discharges
8 kV air discharges
User's Manual Pub.
0300242 ‐ 01 Rev.
A
A-4 Flex™ IO Isolated RTD/Thermocouple Module
Radiated RF immunity
EFT/B immunity
Surge transient immunity
Conducted RF immunity
Enclosure type rating
Signal conductors
Thermocouple
Millivolt
Category
7
Power conductors
Wire size Category
7
Terminal screw torque for cage-clamp terminal base
IEC 61000-6-2:
10 V/m with 1 kHz sine-wave 80% AM from
30…2000 MHz
10 V/m with 200 Hz 50% Pulse 100% AM at
900 MHz
10 V/m with 200 Hz 50% Pulse 100% AM at
1890 MHz
IEC 61000-6-2:
±2 kV at 5 kHz on signal ports
IEC 61000-6-2:
±2 kV line-earth (CM) on shielded ports
IEC 61000-6-4:
10V rms with 1 kHz sine-wave 80% AM from
150 kHz…80 MHz
None (open-style)
Use appropriate shielded thermocouple wire
8
Belden 8761 2 - on signal ports
0.34…2.5 mm2 (22…12 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater
1.2 mm (3/64 in.) insulation max
3 - on power ports
0.8 Nm (7 lb-in.)
7
Use this category information for planning conductor routing as described in the Industrial Automation
Wiring and Grounding Guidelines, Allen-Bradley publication 1770-4.1.
8
Refer to the thermocouple manufacturer for proper thermocouple extension wire.
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Certifications (when product is marked)
Appendix A: Module Specifications A-5
UL
Listed for Class I, Division 2 Group
A,B,C,D Hazardous
Locations, certified for U.S. and Canada. See
UL File
E180101.
UL
Listed Industrial Control Equipment, certified for U.S. and Canada. See UL File E140954.
EEx
European Union 94/9/EEC ATEX
Directive, compliant with:
EN 60079-15; Potentially Explosive
Atmospheres,
Protection “nA” (Zone 2)
CE
European Union 89/336/EEC EMC
Directive, compliant with:
EN 61000-6-4; Industrial Emissions
EN 61326; Meas./Control/Lab., Industrial
Requirements
EN 61000-6-2; Industrial Immunity
EN 61131-2; Programmable Controllers
(Clause 8, Zone A & B)
User's Manual Pub.
0300242 ‐ 01 Rev.
A
A-6 Flex™ IO Isolated RTD/Thermocouple Module
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Index
1
1794 ‐ TB3G ∙ 2 ‐ 10
1794 ‐ TB3GS ∙ 2 ‐ 10
A
A/D converter ∙ 1 ‐ 3
B
Base Unit ∙ 2 ‐ 3 block diagram ∙ 1 ‐ 4
Broken Input Alarm ∙ 3 ‐ 15
Broken Input Mode ∙ 3 ‐ 12
C
CJC ∙ 2 ‐ 12, 3 ‐ 12
Configuration ∙ 3 ‐ 7
D
Data Format ∙ 1 ‐ 2, 3 ‐ 10
Data Ranges ∙ 3 ‐ 11
Deadband
User Alarm Deadband ∙ 3 ‐ 12
Diagnostics ∙ 3 ‐ 16
DIN Rail ∙ 2 ‐ 5
Drilling Dimensions ∙ 2 ‐ 8
E
EMC Directive ∙ 2 ‐ 1
Ethernet Bridge
Local ∙ 3 ‐ 3
F
Fault Mode ∙ 3 ‐ 9
Filter Frequencies ∙ 1 ‐ 2
G
Generic Profile ∙ 3 ‐ 2
User's Manual Pub.
0300242 ‐ 01 Rev.
A
H
Hazardous Location ∙ 2 ‐ 2
I
Input Data ∙ 3 ‐ 15
Input Filter ∙ 3 ‐ 10
Input Type ∙ 1 ‐ 1, 3 ‐ 9
Installation ∙ 2 ‐ 5
K
key ‐ switch ∙ 1 ‐ 3, 2 ‐ 15
L
LED
Module Status ∙ 2 ‐ 15
Low Voltage Directive ∙ 2 ‐ 1
M
Memory Map ∙ 3 ‐ 1
N
Noise ∙ 2 ‐ 3
O
Over Range ∙ 3 ‐ 15
P
Panel/Wall Mounting ∙ 2 ‐ 7
Power Requirements ∙ 2 ‐ 3 power ‐ up ∙ 1 ‐ 3
R
Read
Input data ∙ 3 ‐ 13
Remote Ethernet
Ethernet Flex Adapter ∙ 3 ‐ 4
S
Slot Number ∙ 3 ‐ 8, 3 ‐ 13
T
Temperature Units ∙ 3 ‐ 12
U
Under Range ∙ 3 ‐ 15
User High Alarm ∙ 3 ‐ 12, 3 ‐ 15
User Low Alarm ∙ 3 ‐ 12, 3 ‐ 15
W
Wiring ∙ 2 ‐ 10
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Getting Technical
Assistance
Note that your module contains electronic components which are susceptible to damage from electrostatic discharge (ESD). An electrostatic charge can accumulate on the surface of ordinary plastic wrapping or cushioning material
. In the unlikely event that the module should need to be returned to Spectrum Controls, please ensure that the unit is enclosed in approved ESD packaging (such as static-shielding / metalized bag or black conductive container).
Spectrum Controls reserves the right to void the warranty on any unit that is improperly packaged for shipment.
RMA (Return Merchandise Authorization) form required for all product returns.
For further information or assistance, please contact your local distributor, or call the
Spectrum Controls technical Support at:
USA - 425-746-9481
Declaration of
Conformity
Available upon request
User's Manual Pub.
0300242 ‐ 01 Rev.
A
©2009, Spectrum Controls, Inc. All rights reserved. Specifications subject to change without notice.
The Encompass logo and ControlLogix are trademarks of Rockwell Automation.
Corporate Headquarters
Spectrum Controls Inc.
P.O. Box 5533
Bellevue, WA 98006 USA
Fax: 425-641-9473
Tel: 425-746-9481
Web Site: www.spectrumcontrols.com
E-mail: [email protected]
User's Manual Pub.
0300242 ‐ 01 Rev.
A
Advertisement
Key Features
- 8 isolated channels
- Support for current, voltage, RTD, resistance, thermocouple, and millivolt type inputs
- Digital conversion and storage of analog data
- Individual channel configuration
- Open-circuit, over-range, and under-range detection
- Support for 2 and 3 wired RTD inputs
- Cold junction compensation
- Digital filter for noise rejection