Air Circuit Breakers BT2 Series

Add to My manuals
64 Pages

advertisement

Air Circuit Breakers BT2 Series | Manualzz

Air Circuit Breakers BT2 Series

5-7, Nihonbashi Odemma-cho, Chuo-ku, Tokyo, 103-0011, Japan

URL http://www.fujielectric.co.jp/fcs/eng

Information in this catalog is subject to change without notice.

Printed in Japan 2012-1 Ed5 FOLS EEH606

EEH606

Air Circuit Breakers

BT2 Series 1600 to 6300A

Contents

Features .................................................................... 3

Type number nomenclature ........................................ 6

Specifications ............................................................. 7

Appearance ................................................................ 8

Intelligent controller (OCR) ......................................... 9

Communication ......................................................... 14

Characteristics curve ................................................ 16

Accessories .............................................................. 23

Technical data ........................................................... 28

Dimensions and mounting ........................................ 30

Wiring diagram ......................................................... 54

Ordering form ........................................................... 62

Ordering notice ......................................................... 63

Air Circuit Breakers

BT2 series

Features

Selection guide

Series BT2 series

Frame size

No. of poles

Installation

Closing Mechanism

Tripping Mechanism

Protection function

Fixed

Draw-out

1600, 2000, 2500, 4000, 6300

3, 4

Available

Available

Manual spring or motor spring

Shunt trip, Under-voltage trip

Long time delay, Short time delay, Instantaneous, Ground fault, etc.

Breaking Capacity

Icu is equal to Ics up to 120kA at maximum and Icw is up to 100kA at maximum under 400VAC distribution.

3

产 品 特 点

优异的升级换代性能

CW2-2000断 路 器 , 可 直 接 替 换 原 CW1-

Air Circuit Breakers

BT2 series

Features

CW2-2000 can directly substitute for CW1-

2000 without changing copper bar and aperture dimensions on the panel sheet.

产 品 特 点

优异的升级换代性能

CW2-2000断 路 器 , 可 直 接 替 换 原 CW1-

2000断路器,无需改变母排和柜门的开孔尺寸。

Compact size

BT2 series, Air Circuit Breakers, have five framesize and four physical dimension sizes.

Ampere frame

1600 2000 2500

Outsta ding upgrade performance

4000

Appearance

CW2-2000 can directly substitute for CW1-

2000 without changing copper bar and aperture

6300

简便安装、节约成本

CW2系列断路器具有更简单的安装方式,可以

简便实现

水平连接

垂直连接

混合连接

Simply installed、cost-saving

CW2 Series Circuit Breakers can be simply installed as follows:

Horizontal connection

Vertical connection

Composite connection

CW2系列断路器具有更简单的安装方式,可以

简便实现

水平连接

垂直连接

混合连接

Width 401mm

CW2 Series Circuit Breakers can be simply installed as follows:

Horizontal connection

Vertical connection

Composite connection

• Vertical connection

• Composite connection

先进可靠的安全性能

CW2系列断路器具有可靠的:

抽屉座三位置锁定和自动解锁装置,安全

确认“连接”、“试验”、“分离”三个位置。

Advanced and reliable safety performance

CW2 Series Circuit Breakers are reliable by the following aspects:

Reliable assurance of the three positions: connected、 test、 separated by the locked and automatically unlocked mechanism at the draw-out socket.

767mm

Safety performance

BT2 series, Air Circuit Breakers, are reliable by the following aspects:

• Reliable assurance of the three positions:

Connected

Test

Separated by the locked and automatically unlocked mechanism at the draw-out socket.

Clear indication of ready-for-switching-on to ensure safe manipulation and reliable operation.

Indication of ready-forswitching-on:"ok"

先进可靠的安全性能

CW2系列断路器具有可靠的:

抽屉座三位置锁定和自动解锁装置,安全

确认“连接”、“试验”、“分离”三个位置。

Advanced and reliable safety performance

CW2 Series Circuit Breakers are reliable by the following aspects:

Reliable assurance of the three positions: connected、 test、 separated by the locked and automatically unlocked mechanism at the draw-out socket.

5

More reliable safety protection with seconday terminals of protection grade IP30

4

5

Air Circuit Breakers

BT2 series

Features

Protection and selection

BT2 Series, Air Circuit Breakers, can implement selective interlock of ZSI Region to ensure comprehensive selection of various protection and reduce the copper bar's bearing of thermodynamic.

21

22

23

24

21

22

23

24

21

22

23

24

Intelligent controller (OCR)

Selecting OCR's, it can be classified into six types

Type L25

Option

M25

Standard

Pic

L25 Intelligent Controller M25 Intelligent Controller

M26

Option

M26 Intelligent Controller

H26

Option

H26 Intelligent Controller

21

22

23

24

P25

Option

P25 Intelligent Controller

P26

Option

P26 Intelligent Controller

Display/setting Light columnar indication LED digtal indication LED digtal indication LED digtal indication LCD indication

Dial setting by knob Consecutive Consecutive Consecutive Consecutive parameter setting parameter setting parameter setting parameter setting

Protection/ function t t t t t t t t t t t t t t t t t t t

LCD indication

Consecutive parameter setting t

I

I I

I I

I I

I t t t t

I I I

I

I

I I

I t t t t

I I I

I

I

I

I

I

I I t

I t

I

5

I

I

Air Circuit Breakers

BT2 series

Type number nomenclature

6

Type number nomenclature

BT2-2500P / 32500E

Basic type

Frame size

1600, 2000, 2500, 4000, 6300

Installation

P: Fixed type

X: Draw-out type

Number of poles

3: 3 poles

4: 4 poles

Rated current

1600AF: 0200, 0400, 0630, 0800, 1000, 1250, 1600

2000AF: 0630, 0800, 1000, 1250, 1600, 2000

2500AF: 1250, 1600, 2000, 2500

4000AF: 2000, 25000, 2900, 3200, 3600, 4000

6300AF: 4000, 5000, 6300

CE version

P25

P26

OCR type or Additional accessories

• OCR type (note: M25 is standard), See page 9

Type

L25

Code

L5A

Remarks

M25

H26

– (None)

H6A

P5A

P5B

P5C

P5D

P6A

P6B

P6C

P6D w harmonic analysis function w communication function w alarm of current-imbalance w harmonic analysis function w communication function w alarm of current-imbalance

• Accessories

Type

LED indicator of Voltage

Load-monitoring function

ZSI function

(Zone selective interlock function)

Under voltage release

Code

C1

C2

C3

Remarks

Switching OFF lock device

Mechanical interlock device

(Two sets of ACB's)

Mechanical interlock device

(Three sets of ACB's)

Current transformer for neutral line N connected externally

N3

N4

N6

MB4

N1

N1

N2

D1

R1

R2

Q1

Q2

Q3

MW1

MB1

MW2

MB2

MB3

Instananeous

Time delay

One lock and one key

Two lock and one key

Three lock and two key

Steel lock interlock

Link rod interlock (0,6m)

Cable type interlock

Pattern one of rod interlock

Pattern two of rod interlock

Pattern three of rod interlock

1600AF L

・M・H Controller

1600AF P Controller

2000AF

2500AF

4000AF

6300AF

Electrical mechanism for the indication of draw out socket's position

Separator plate between phases B3

B4

RFS

3P

4P

Electrical module for indication of ready-for-switching-on

"Button" Locking device

Counter

Communication function choice of accessories

DC power supply module

AC power supply module

Automatic transfer switch (ATS)

(included automatic controller, connector and 1.8m cable)

PD2

PD3

PA1

PA2

AS1

AS2

L

CM

S1

S2

S3

S4

PD1

AS3

Components of draw-out socket communication module

Ready-for-switching-on signal

Under-voltage signal

Fault-trip signal

24VDC

110VDC

220VDC

230VAC

400VAC

R type

S type

F type

Air Circuit Breakers

BT2 series

Specifications

Specifications

Frame size 1600A

Basic type

No. of poles

Rated current (A)

BT2-1600

3 4

200, 400, 630, 800,

1000, 1250, 1600

100% In Rated current of the neutral pole

(IN)

Rated insulation voltage (Ui) 1000

Rated operational volage (Ue) 690

Rated ultimate short-circuit 690VAC *

1

40 breaking capacity (Icu kA, sym)

Rated service short-circuit breaking capacity (Ics kA,

400VAC 50

690VAC *

1

25

400VAC 50 sym)

Rated making current

(kA, peak)

Rated short time withstand current (Icw) (kA, rms)

690VAC *

1

84

400VAC 105

690VAC *

1

25 (0.5s)

400VAC 42 (0.5s)

Rated impulse withstand voltage

(Uimp) (kV)

12

Installations

Fixed P

Draw-out X

Main circuit terminal connection

Fixed Horizontal

Vertical

Dimensions

Draw-out Horizontal

Vertical

Fixed W

H

D

Draw-out W

H

D

254

320

197

248

351.5

297

324

320

197

318

351.5

297

Note: *

1

Cannot be used for an IT distribution system.

Available

1000

690

50

80

50

80

362

395

290

347

438

390

2000A

BT2-2000

3 4

630, 800, 1000,

1250, 1600, 2000

100% In

105

176

40 (1s)

60 (1s)

12

457

395

290

442

438

390

362

395

290

347

438

390

2500A

BT2-2500

3 4

1250, 1600, 2000,

2500

100% In

4000A

BT2-4000

3 4

2000, 2500, 2900,

3200, 3600, 4000

100% In

1000

690

50

85

50

85

105

187

50 (1s)

65 (1s)

12

1000

690

75

100

75

100

165

220

75 (1s)

85 (1s)

12

1000

690

85

120

85

120

6300A

BT2-6300

3 4

4000, 5000, 6300

100% In

187

264

85 (1s)

100 (1s)

12

457

395

290

442

438

390

414

395

290

401

438

395

527

395

290

514

438

395

782

395

290

767

475.5

395

1008

395

290

993

475.5

395

7

Air Circuit Breakers

BT2 series

Appearance

Appearance

• Fixed • Draw-out

6

7

10

11

8

9

12

<Common>

6: Terminals of sencondary circuit (fixed)

7: Off lock mechanism

9: Inteligent controller (OCR)

10: OFF button

11: Indications of "ON" and "OFF"

8: Release indication and resetting button

12: Indication of ready-for-switching-on ("OK")

1: Name plate

2: Indications of energy-storage and energy-release

3: ON button

4: Manual energy-storage handle

5: Brand

• Draw-out cradle

The cradle has the back plate for isolating the copper bar of the main circuit, which take the role of safety protection when the ACB is drawn out.

6

5

4

3

2

1

11

12

13

14

7

8

9

10

17

16

15

<For Draw-out>

13: "Unlock button" of the three positions

("Separated", "test" and "connected") *1,2

14: Safety padlock mechanism

15: Racking shaft operating hole

16: Racking shaft storage hole

17: Indications of the three position

("Separated", "test" and "connected")

Note: *

1

"Separated": Indicates that main circuit and secondary circuit are both in isolation."Test": Indicates that main circuit is in isolation and secondary circuit is in connection."Connected": Indicates that main circuit and

*

2 secondary circuit are both in connection.

The ACB can be automatically locked (racking shaft can not be turned at the point) when its main part is at the position of "separated","test" or "connected" by turning the racking shaft, and can be unlocked by pushing "unlock button" to the left side.

5

4

3

2

1

21

22

23

20

19

18

24

18: Installation hole

19: Safety back plate

20: Wiring terminals of secondary circuit

21: Side plate

22: Copper bar of the main cirucit

23: Draw-out socket

24: Earthing point at draw-out socket

8

Air Circuit Breakers

BT2 series

Intelligent controller

Intelligent controller (OCR)

Selecting OCR's, it can be classified into six types

Type L25

Option

M25

Standard

M26

Option

Overcurrent protection

(Long-time, Short-time, insantaneous)

Ground-fault protection

Load monitor function

Indication

Power, electric energy, power-factor, frequency indication

Alarm function (pre-trip alarm, overload alarm)

Test function

Contact Welding indication

Self-diagnosis function

MCR funciton

Fault-memory funciton

Current-imbalance indication

Thermo-analogue function

Harmonic analysis function

ZSI function

Communication function

Light Columnar LED

– –

LED

Note: Reprensents fundamental functions, Represents selective functions, – Represent no such functions

H26

Option

LED

P25

Option

LCD

P26

Option

LCD

Function

Over-current protection

• The over-current protection is composed of phase and neutral line protection (Four pole breaker and three pole breaker with current transformer linking externally to neutral N) from over-current.

• The parameters of current and time of phase line over-current protection can be set by the company in terms of the requirements of users (can be set by customers themselves); the parameters of current and time of neutral line over-current protection will be set according to the setting of the phase line, all these mainly divided into the following two situations:

Three pole breaker with the neutral connected eaternally

• To type L25, M26, H26 intelligent controller, when ordering the goods the neutral line setting current customers should have to confirm the protecting data, it has two type of 50%In and 100%In.

• To type P25, P26 intelligent controller, the customers can setup into four types from menu:turn off, 50%In, 100%In, 200%In. When

200%In neutral line protecting (if it has a high triple frequency harmonic), the neutral line cross section should be double leg of a circuit cross section in the electrical power distribution system. But to

BT2-6300 three circuit breaker, there is no neutral line protecting.

Four pole breaker

• To type L25, M25, M26, H26 intelligent controller, the customers should have to confirm the protecting data, it has two types of 50%In and 100%In.

• To type P25, P26 intelligent controller, the customers can setup into three types from menu:turn off, 50%In, 100%In.

Overload protection

• Inverse long-time delay overload protection, and its setting current Ir1 can be adjusted.

• The delay time t1 of overload long-time delay can be adjusted.

• The long-time delay overload characteristic of the type P25, P26, the curves can be adjusted. There have common type (I2t), uncommon inverse-time type (It), high-voltage fuse concert type (I4t) can be adjusted, which can matching higher-up and lower-lever's overload protection'needs. The long-time delay overload characteristic ofthe type L25, M25, M26, H26, its running according to the common type (I2t) curves,current Ir1, time t1 can beadjusted.

Short-time short circuit protection (can be OFF)

• Inverse short-time delay short circuit protection (I2t ON), and its setting current Ir2 can be adjusted.

• Definite short-time delay short circuit protection (I2t OFF), and its setting current Ir2 can be adjusted.

• The delay time t2 of short circuit short-time delay can be adjusted.

Instantaneous short circuit protection

• The setting current Ir3 of instantaneous short circuit (can be OFF) can be adjusted.

t

Delay time of overload long-time delay adjustable

Definite short-time delay short circuit(I

2 t OFF)

Setting current Ir

1

of overload long-time delay

Setting delay time t

1

of overload long-time delay

Setting current Ir

2

of short-time circuit short-time delay

Inverse short-time delay short circuit (I

2 t ON)

Setting delay time t

2

of short circuit short-time delay

Setting current Ir

3

of instantaneous short circuit

Long-time delay, short-time delay, instantaneous protection

I

9

Air Circuit Breakers

BT2 series

Intelligent controller

Ground-fault protection

• Definite ground-fault protection, and its setting current Ir4 can be adjusted

• Delay time t4 can be adjusted

• Alarm but not break after being off t

Setting current Ir

4

of ground-fault

Setting current t

4

of ground-fault

I

• TN-C, TN-C-S, or TN-S, power distribution system

without additional current transformer of neutral

Transformer

BT2 circuit breaker with three poles

Current transformer

L

1

L

2

L

3

PEN

Intelligent controller

• TN-S, power distribution system, 4 poles

Transformer

BT2 circut breaking with four poles

Current transformer

L

L

L

2

1

3

N

PE

• TN-S, power distribution system, 3 poles

Transformer

BT2 circut breaking with three poles

Current transformer

L

1

L

2

L

N

3

Intelligent controller

Intelligent controller

For exmple : TN-C system

PE

Load monitoring function

• To monitor the down stream load so as to ensure power supply of main system

• There are two patterns of load monitoring from which users t can choose one. The setting value of load-monitoring current are I

LC1

and I

LC2

, normally I

LC1

is larger than or equal to I

• Inverse characteristic of load-monitoring is the same of

LC2 inverse long-time delay overload characteristic.

t t

Setting current I

LC2

of load monitoring (Limiting load)

Setting current I

LC1

of load monitoring (Limitiong load)

Setting delay time t c1

of load monitoring

I

Setting delay time t c2

of load monitoring

I

Acting characteristic of two kinds of ultimate setting load

Setting current I

LC2

of load monitoring (reload)

Setting current I

LC1

of load monitoring (Limiting load)

For example: TN-S system

N line current transformer connected externally

For example: TN-S system

• Pattern 1: Two circuits of down stream load can be controlled.

When the operating current of the main circuit rises over the setting value of I

LC1

and I

LC2 after time durations of t

C1

, contact signal will be sent out

and t

C2

repectively. Then this two circuits with monitored load are broken off by receiving the instructions from the intelligent controller.

• Pattern 2: Only one circuit with down stream load can be controlled. When the operating current of the main circuit rises over the setting value of I out after time duration of t

LC1

, contact signal will be sent

C1

, and this circuit is broken off by receiving the instructions from the intelligent controller. If the operating current of the main circuit decreases lower than the setting value of I

LC2

after this circuit is broken off, the signal will be sent out again after time duration of t supply of this circuit is restored.

C2

for the open loading circuit to be closed (reloaded) and so the power

• Load monitoring signals"(1)" and "(2)" corresponding to I

LC1 and I

LC2

respectively are transmitted into contact signals via the wiring terminals 13, 14 and 15, 16 of the secondary circuit. There will be LED indication at the time when signals are transmitted. (The load monitoring signals from the intelligent controller will be cut off in half second after the signal of contact closing is transmitted, and the capacity of contact is AC230V 5A) t

Setting delay time t c2

of load monitoring

10

Setting delay time t c2

of load monitoring (definite)

I

Acting characteristic of ultimate setting value of load and reload

I

Air Circuit Breakers

BT2 series

Intelligent controller

Indication and measurement function

• For L25, M25, M26 and H26

Item

Current

Voltage

Type of OCR's

L25

M25

M26, H26

M25, M26 as optional

H26 as standard

• For P25 and P26

Item

Current

Display

LCD

Display Content

Light columnar Indication I

1

, I

2

, I

3

, I

N

LED I

1

, I

2

, I

3

, I

N

, I max

I

1

, I

2

, I

3

, I

N

, I

G

, I max

LED U

12

, U

23

, U

31

, U min

Voltage

Power

Power-factor

Electric energy

Frequency

Fundamental current

Fundamental line voltage

Fundamental phase voltage

Fundamental power

Harmonic ratio

Total harmonic distortion

(THD)

Content

I

1

, I

2

, I3, I

N

I

G

Line Voltage: U

12

, U

23

, U

31

Phase Voltage: U

1N

, U

2N

, U

Three-phase active power

3N

Three-phase reactive power

Three-phase apparent power

Power-factor

Three-phase active electric energy

Three-phase reactive electric energy

Three-phase apparent electric energy f

I

1-1

, I

2-1

, I

3-1

, I

N-1

U

12-1

, U

23-1

, U

31-1

U

1N-1

, U

2N-1

, U

P1

3N-1

Q1

S1

Current

Voltage

Current

Voltage

Indication and measurement range

(0.1In to 2In) A

Accuracy

± 5%

30V to 690V ± 3%

Indication and measurement range

(0.1In to 2In) A

0.1In to 2000A

30V to 690V

-120MW to +120MW

-120Mvar to +120Mvar

-120MVA to +120MVA

-1.00 to +1,00

-10

10

GWh to +10

10

GWh

-10

10

Gvarh to +10

10

Gvarh

-10

10

GVAh to +10

10

GVAh

45 to 65Hz

(0.1In to 2In) A

30V to 690V

-120MW to +120MW

-120Mvar to +120Mvar

-120MVA to +120MVA

0 to 1000%

Accuracy

± 1.5%

± 2.5%

± 0.5%

± 2.5%

± 2.5%

± 2.5%

± 0.1Hz

± 1.5%

± 0.5%

± 2.5%

± 5%

Alarm and fault functions

Over-current alarm

Type L25

Type M25

Type M26, H26

Type P25, P26

Fault indication Type L25

Type M25

Type M26, H26

Type P25, P26

Corresponding LED on the panel will be "ON"

Corresponding LED on the panel will be "ON"

Indication of fault phase, current and time

Type M25,

M26, H26

Indication

Type P25, P26 Indication

Alarm and release indication lights will be on after the circuit breaker's being overloaded or released (yellow or red)

After the circuit breaker's being released by long-time delay overload, short-time delay short circuit and instantaneous short circuit, indication lights of corresponding alarm will be on.

After the circuit breaker's being released by long-time delay overload, short-time delay short circuit, instantaneous short circuit and ground-fault, indication lights of corresponding alarm will be on.

After the circuit breaker's being released by long-time delay overload, short-time delay short circuit and instantaneous short circuit, indication lights of corresponding alarm will be on.

After the circuit breaker's being released by long-time delay overload, short-time short circuit and instantaneous short circuit, indication lights of corresponding fault type will be on.

After the circuit breaker's being released by long-time delay overload, short-time short circuit and instantaneous short circuit, indication lights of corresponding fault type will be on.

After the circuit breaker's being released by long-time delay overload, short-time delay short circuit, instantaneous short circuit, instantaneous short circuit and ground-fault, indication lights of corresponding fault type will be on.

After the circuit breaker's being released by long-time delay overload, short-time delay short circuit and instantaneous short circuit, indication lights of corresponding alarm will be on.

Indication of faulty phase, breaking value of fault current and breaking time

It can indicate the latest ten times fault categories and occurrence time, faulty phase, breaking value of fault current and breaking time.

11

Air Circuit Breakers

BT2 series

Intelligent controller

Test functions

Panel button Type L25, M25, M26,

H26, P25, P26

Type M25, M26, H26,

P25, P26

Release

Non-release

Inspeciton of T-I characteristic of the OCR and the conditions of operating mechanism

Inspeciton of T-I characteristic of the OCR

• Contact wearing indication (for M25, M26, H26, P25 and P26)

The intelligent controller has the function of contact wearing indication. Accordingly, the percentage of the equivalent to wearing times of main contact to electrical life-span times of the circuit breaker can be indicated by pushing the button of

"wearing indication".

• Self-diagnosis function (for M25, M26, H26, P25 and P26)

When the microprocessor of the intelligent controller breaks down or the ambient temperature of the microprocessor rises over 80°C±5, alarm signals can be sent out immediately.

• MCR function

When the circuit breaker is on or the controller is initially electrified, the circuit breaker would trip instantly if short-time short circuit fault occurred.

• Fault-memory function (for M25, M26, H26, P25 and P26)

The types and phases of fault, value of faulty current and breaking time would be indicated on the intelligent controller if the circuit breaker broke off as a result of faults.

• Current disequilibrium display (selective function for P25 and P26)

The intelligent controller can sent out and display, when the three phases current disequilibrium level reached the setting value (20%-80%).

Note: the three phases current disequilibrium=

Imax-Imin

Imax

×100%

• Harmonic analysis function (for P25 and P26)

P25 or P26 intelligent controller with harmonic analysis function can measure fundamental current, fundamental line voltage, fundamental phase voltage, fundamental power, odd harmonic current ratio (HRIh) from the third to thirty-first, harmonic voltage ratio (HRUh), total harmonic distortion of current (THDi, thdi) and total harmonic distortion of voltage

(THDu, thdu).

• Harmonic ratio (HR)

The ratio of RMS of hth harmonic component in the periodical alternating quantum to RMS of fundamental component (express by percent).

• Harmonic current ratio of hth expresses HRI h

.

HRI h

= I h

I

1-1

×100%

Note: I h

-harmonic current of hth of phase A (RMS)

• Harmonic voltage ratio of hth expresses HRU h

.

U h

HRU h

=

U

12-1

×100%

Note: Uh -harmonic line voltage of hth between phase A and B.

• Total harmonic distortion (THD)

• The ratio of harmonic content in the periodical alternating quantum to RMS of fundamental component

(THD)(express by percent).

THD i

=

I

1-1

I

2 h

×100%

THD u

=

U

2 h

U

12-1

×100%

Note: I

U h h

-harmonic current of hth of phase A (RMS)

-harmonic line voltage of hth between phase A and B (RMS)

• The ratio of harmonic component in the periodical alternating quantum to RMS of periodical alternating quantum(thd) (express by percent).

thd i

=

I

1-1

I

2 h

×100%

thd u

=

U

2 h

U

12-1

×100%

Ntoe: I h

-harmonic current of hth of phase A (RMS)

U h

-harmonic line voltage of hth between phase A and B (RMS)

12

Air Circuit Breakers

BT2 series

Intelligent controller

Zone selective interlock

Zone selective interlock (ZSI function) (for M25, M26, H26, P25 and P26, optional)

Busbar

Zone1

Control line

Control line

Busbar

Zone2

Control line

Control line

Busbar

Zone3

Circuit breaker at higher level

21

22

23

24

21

22

23

24

21

22

23

24

Fault

Down stream circuit breaker

Release delay t

2

21

22

23

24

Release delay t

2

Note: 21,22,23,24 serve as the wiring teminals of secondary circuit.

When pieces of circuit breakers are linked together up and down, zone selective interlock (ZSI) can ensure fully-selective protection of circuit breakers at higher or lower level so as to reduce the range of action by fault and the breaking time of circuit breakers. This function serves for short-time delay short circuit (I

2 t OFF) and ground-fault protection of circuit breakers.

As the sketch shown above, control lines can interlock with pieces of circuit breakers.

After detecting the fault, the intelligent controller (zone 2) will send out a signal to circuit breakers (zone1) at higher level and check whether the signal of circuit breakers (zone 3) at lower level arrives. If circuit breakers at lower level send out a signal, the circuit breaker will be on at the time duration of release delay; if circuit breakers at lower level don't send out a signal, the circuit breaker will break off instantly no matter whether the release has the protection of delay.

Note: The end 23 and 24 should be shortcircuited.

13

Air Circuit Breakers

BT2 series

Communication

Communicative

To achieve the function of "four kinds of remote operation" at long distance by communication interface of the circuit breaker, namely, remote control, remote communication, remote adjustment and remote detection.

• Communication protocol : The application of Modbus-RTU mode

• Communication interface

• Standard interface: RS-485.

• Baud rate: 19200bps (in favour of 1200, 2400, 4800, 9600, 38400bps)

• Communication address:1-119.

• Byte format: First bit as start bit, eighth bit as data bit, second bit as stop bit, even check (in favour of non-check, odd check .)

• Network characteristic

• Twisted-pair shielded cables serve as communication lines.

• One line can link up 32 pieces of communicative circuit breakers at the same time (16 pieces of circuit breakers with components of draw-out socket communication module).

• Wiring distance is 1200m at maximum but the distance of communication can be extended by equipping with repeaters additionally.

Communication cable

Blue

White

One group

Shielding layer

Standard twisted-pair shielded cable

Note: please use the type of communication cable with the shielding layer and approach to circuits with strong electricity should be avoided as far as possible when wiring in the cabinet.

Communication data

• Real-time current, voltage fundamental current, fundamental voltage, power, power factor, electric energy, harmonic current or voltage ratio and total distortion of current or voltage.

• State data of circuit breakers such as alarm, fault, energy-storage, undervoltage, ready-for-switching-on, and the positions of switching-on and switching-off etc.

• The position of main body of the circuit breaker (components of communication module of draw-out socket for BT2 need to be purchased).

• The fetching and modification of the setting values of circuit breakers.

• Recorded data of fault last time.

• Outline data such as serial numbers and the type etc of circuit breakers.

• Long-distance operation if switching-on and switching-off.

• Circuit breakers can be switched on or off in the long-distance.

• Wiring terminals for communication.

Colour

Blue

White

Shielding layer

Signal

DATA+

DATA−

GND

Funation

Receive/transmit data

Receive/transmit data

Grounding

As the above diagram shows, a group of twisted-pair lines in the standard communication cable is employed as the communication line of 485 and the sheilding layer is grounded.

The actual practice should be possibly different such as the application of the colour of the twisted-pair line. Users could define the ways of cable's usage by themselves but the definition of the signal of each line in the cable should be made clear in advance.

8 1 0 1 2 1 4

7 9 1 1 1 3

Terminal

8

10

12

Signal

DATA+(A+)

DATA-(B-)

SH

Function

Receive/transmit data

Receive/transmit data

In connection with shielded layer of communication line

14

Linking diagram of communication system

Monitoring computer

RS232

RS485

RS232/RS485

Converter

DATA+

DATA−

Draw-out socket communication module

Modbus

BT2

BT2

Note: As the accessory of selective purchase, the draw-out socket communication module should be selected into use when users need read the location of main body in the long distance by the choice of draw-out circuit breakers.

BT2

BT2

Air Circuit Breakers

BT2 series

Communication

15

Air Circuit Breakers

BT2 series

Characteristic curve

Characteristic curve of general l

2

• BT2-1600~BT2-6300 t

T/I (time / current) curve of type L25 intelligent controllers (OCR)

10000

I r1

1000 t

1

100 long-time delay curve

Illustrational curve

The range of long-time delay

I r1 t

1

=(0.65~1)In

=15s~480s t

I

The range of short-time delay

2 r2

=(1.5~10)I

=0.1s~0.4s

r2

+OFF

I

Instantaneous range r3

=(3~15)I r1

+OFF

I

2

T ON

I r2 t (s)

10

0.02

0.01

1

0.4

0.3

0.2

0.1

Short-time delay curve

I 2 T OFF

0.4

1

Instantaneous curve

1.5

3

Ir1

Instantaneous range

10 15 t

2

16

Air Circuit Breakers

BT2 series

Characteristic curve

• T/I (time / current) curve of type M25, M26, H26, P25 and P26 intelligent controllers (OCR)

10000

Illustrational curve

I r1

I

The range of long-time delay r1

=(0.4~I)In t

1

=10s~120s

1000

The range of short-time delay

I r2 t

2

=(0.4~15)In+OFF

=0.1s~0.4s

t

1

Instantaneous range

I r3

= 1.6kA~35kA+OFF BT2-1600

2kA~50kA+OFF BT2-2000

2.5kA~50kA+OFF BT2-2500

4kA~65kA+OFF BT2-4000

6.3kA~80kA+OFF BT2-6300

100 long-time delay curve t (s)

10

I 2 T ON

I r2

Short-time delay curve

I

2

T OFF t

2

0.02

0.01

1

0.4

0.3

0.2

0.1

I r1

Instantaneous curve

0.4

1 1.6

Instantaneous range

10 15 kA

80

17

Air Circuit Breakers

BT2 series

Characteristic curve

Characteristic curve of inverse time delay special It

• T/I (time / current) curve of type 25 and 26 intelligent controllers (OCR)

10000

I r1

1000

100 t

1

Illustrational curve

The range of long-time delay

I r1 t

1

=(0.4~1)In

=10s~120s t

I

The range of short-time delay

2 r2

=(0.4~15)In+OFF

=0.1s~0.4s

Instantaneous range

I r3

= 1.6kA~35kA+OFF BT2-1600

2kA~50kA+OFF BT2-2000

2.5kA~50kA+OFF BT2-25

4kA~65kA+OFF BT2-4000

6.3kA~80kA+OFF BT2-6300 long-time delay curve

I

2

T ON

I r2 t (s)

10

Short-time delay curve

I

2

T OFF t

2

0.02

0.01

1

0.4

0.3

0.2

0.1

Instantaneous curve

0.4

1

I r1

1.6

Instantaneous range

10

15 kA

80

18

Air Circuit Breakers

BT2 series

Characteristic curve

Characteristic curve of high-voltage fuse I

4 t

• T/I (time / current) curve of type 25 and 26 intelligent controllers (OCR)

100000

10000

1000

100

I

2

T ON

I r1 t

1

Illustrational curve

The range of long-time delay

I r1 t

1

=(0.4~1)In

=60s~1440s

I

The range of short-time delay r2

=(0.4~15)In+OFF t

2

=0.1s~0.4s

Instantaneous range

I r3

= 1.6kA~35kA+OFF BT2-1600

2kA~50kA+OFF BT2-2000

2.5kA~50kA+OFF BT2-2500

4kA~65kA+OFF BT2-4000

6.3kA~80kA+OFF BT2-6300 long-time delay curve

I r2 t (s)

10

Short-time delay curve

1

0.4

0.3

0.2

0.1

I

2

T OFF t

2

0.01

0.001

I r1

Instantaneous curve

0.4

1

1.6

Instantaneous range

10 kA

15

80

19

Air Circuit Breakers

BT2 series

Characteristic curve

• T/I (time / current) curve of type M26, H26 and P26 intelligent controllers (OCR) for ground-fault protection

1000

100

Grounding current t

4

I r4

I

I

I r4

I r4 r4 r4

=(0.4~0.8)In(BT2-1600)

=(0.2~0.8)In(BT2-2000, BT2-2500)

=(0.2~0.6)In(BT2-4000)

=(0.2~0.5)In(BT2-6300)

=0.1s~0.4s four steps

Maximum 1000A (For BT2-1600)

Maximum 1200A (For BT2-2000, BT2-2500)

Maximum 1600A (For BT2-4000)

Maximum 2000A (For BT2-6300)

Maximum

10 t (s)

1

0.4

0.3

0.2

0.1

0.01

0.2

0.8

1

In

10 100

20

Air Circuit Breakers

BT2 series

Characteristic curve

• T/I (time / current) curve of type M25, M26, H26, P25 and P26 intelligent controllers (OCR) for load-monitoring pattern one.

10000 t

I

LC1

=(0.2~1)In

C1

=t

1

/2(t

1

=15, 30, 60, 120, 240, 480s)

I

LC2

I

LC2

=(0.2~1)In t

C2

I

LC2

=t

1

/4(t

1

≤I

LC1

=15, 30, 60, 120, 240, 480s)

1000

I

LC1

200

100 t

C2 t

C1 t (s)

10

1

0.1

0.2

0.8

1

In

10 100

21

Air Circuit Breakers

BT2 series

Characteristic curve

• T/I (time / current) curve of type M25, M26, H26, P25 and P26 intelligent controllers (OCR) for load-monitoring pattern two.

10000

I

LC1 t

C1

=(0.2~1)In

=t

1

/2(t

1

=15, 30, 60, 120, 240, 480s)

I

LC2

I

LC2

=(0.2~1)In t

C2

=60s

1000 t (s)

100

60

10 t

C2

I

LC1 t

C1

1

0.1

0.2

0.4

0.8

1

In

10 100

22

12.0 COMMON FAULT AND SOLUTION

No.

9

10

12.0 COMMON FAULT AND SOLUTION

● Communication cable

1. Check whether the communication doesn't connect well with cables connect well with wiring

Technical problems

9

● Communication cable doesn't connect well with

Inspection and solution

2. Check whether terminals A and B of the communication cable are inversely wired. If so, make the correction;

3. Check whether communication

Communication error for Type H26、

P25、P26 Intelligent controller

10 inversely wired

● Errors for the setting of

● Communication distance and wiring ways can't meet the requirements

● Errors for the setting of communication address intelligent controller displays

3. Check whether communication requirements; distance and wiring ways can meet the requirements;

4. Check whether the setting of

Air Circuit Breakers without conflict

BT2 series

Accessories

The screen on the intelligent around the controller

To reduce the ambient temperature controller displays

13.0 ACCESSORIES

“ERR9”

Accessories

Supplied accessories

13.1 NECESSARY ACCESSORIES

Following accessories are come with each ACB's as standard supplied.

• Shunt trip device

To break the ACB by remote control.

Rated voltage of control

○ Closing electro-magnet

○ Shunt Release

400VAC 230VAC 220VDC 110VDC power supply

1.3

1.3

2.4

For BT2-1600 Circuit Breaker For BT2 with frame current of 2000A and above

Operating voltage (V) (0.7 to 1.1) Us

Instantaneous current (A) 0.7

Breaking time (ms) No more than 30

▲ Switch the breaker off by remote control

▲ Features

13.0 ACCESSORIES

AC400 DC220

• Charge Coil

13.0 ACCESSORIES

After the ACB's ends up its energy storage, the closing electromagnet will make the energy storing spring to release its energy instantly, then to close the count ACB quickly.

Rated voltage of control power supply

▲ After the circuit breaker is charged, the closing electro-magnet will make the energy-charging

400VAC 230VAC 220VDC 110VDC

Operational Voltage(V)

Operational Voltage(V)

○ Auxiliary Switch

AC400

Breaking Time(ms)

AC230

0.7

DC220

(0.7~1.1)Us

(0.85~1.1)Us

1.3

(0.7~1.1)Us

1.3

DC110

No more than 30

(0.85~1.1)Us

DC110

2.4

DC110

Operating voltage (V) (0.85 to 1.1) Us

Instantaneous current (A) 0.7

1.3

0.7

1.3

1.3

0.7

0.7

For BT2-1600 Circuit Breaker

1.3

1.3

2.4

2.4

1.3

2.4

Switching-on time (ms) No more than 70

Switching-on Time(ms)

Drive unit

Rated voltage of control power supply

After the circuit breaker is charged, the closing electro-magnet will make the energy-charging

For BT2-1600 Circuit Breaker

For BT2 with frame current of 2000A and above

ACB has the functions of drive energy storage and automatic energy-restoring.

▲ Features

The energy storage can also be done manually.

400VAC 230VAC 220VDC 110VDC

Rated Control supply voltage Us(V)

Rated Current

AC230

AC400

DC220

AC230 DC220 DC110

Operating voltage (V)

Power consumption

(0.85 to 1.1) Us

192VA

Operational Voltage(V)

Instantaneous Current(A)

Rated operational Voltage(V)

1.3

1.3

1.3

1.3

2.4

Conventional thermal current Ith(A)

Rated capacity

Energy storage time (s) No more than 5

13.0 ACCESSORIES

230 13.0 ACCESSORIES changeover contacts; for the special type of auxiliary switch, there are four

Power Consumption close contacts (NC), or 6 pieces of NO and 2 pieces of NC, or 2 pieces of

NO and 6 pieces of NC.

For BT2-1600 Circuit Breaker

AC

192VA

○ Safety padlock mechanism at the position of “separated”

For BT2 with frame current of 2000A and above

300VA

Auxiliary Switches

Rated voltage (V)

○ Auxiliary Switch discharging.

AC 230

6

DC

400

220

110

DC

400

220

6

60W

▲ Features

Note: For the standard type of auxiliary switch, there are four pairs of changeover contacts; for the special type,

60W

Rated Control supply voltage Us(V)

Rated Control supply voltage Us(V) AC400 AC230

AC400 AC230 DC220 DC110

DC220 DC110 or 6 pieces of NO and 2 pieces of NC, or 2 pieces of NO and 6 pieces of NC.

Operational Voltage(V)

(0.85~1.1)Us

(0.85~1.1)Us

192W

For BT2 with frame current of 2000A and above

Safety padlock mechanism at the position of “separated” discharging.

Rated Current

“of separated”, the locking stick can be locked with padlock after being pulled out so that the rocker of the circuit breaker can not be turned to the position of “test” or “connected”.

Padlock should be provided by users themselves.

AC

DC

400

220

Operational Voltage(V)

Power Consumption

·66·

AC230

Rated operational Voltage(V)

AC

AC230

230

400

220

Conventional thermal current Ith(A)

DC220

Rated capacity

300VA

60W

6

Power Consumption

300VA

(0.85~1.1)Us

192VA 192W or 6 pieces of NO and 2 pieces of NC, or 2 pieces of NO and 6 pieces of NC.

Charging Time(s)

192VA

60W

Safety padlock mechanism at the position of “separated” or 6 pieces of NO and 2 pieces of NC, or 2 pieces of NO and 6 pieces of NC.

○ Safety padlock mechanism at the position of “separated”

·66·

·66·

○ Safety padlock mechanism at the position of “separated”

can be locked with padlock after being pulled out so that the rocker of the circuit breaker can not be turned to the position of “test” or “connected”.

Safety padlock mechanism at the position of “separated”

▲ Padlock should be provided by users themselves.

Safety padlock mechanism at the position of “separated”

·67·

▲ When the draw-out circuit breaker is at the position of “separated”, the locking stick can be locked with padlock after being pulled out so that the rocker of the circuit breaker can not be turned to the position of “test” or “connected”.

▲ Padlock should be provided by users themselves.

·67·

▲ When the draw-out circuit breaker is at the position of “separated”, the locking stick can be locked with padlock after being pulled out so that the rocker of the circuit breaker can not be turned to the position of “test” or “connected”.

▲ Padlock should be provided by users themselves.

·67·

13.0 ACCESSORIES

13.2 SELECTIVE ACCESSORIES

13.0 ACCESSORIES

▲ When the power voltage of the intelligent controller is DC24V, AC230V or AC400V, it can be

Air Circuit Breakers

BT2 series

Accessories

Caution: Voltage input to secondary terminals 1 and 2 of BT2-1600 must be

DC24V.

▲ When the power voltage of the intelligent controller is DC24V, AC230V or AC400V, it can be cabinet.

Caution: Voltage input to secondary terminals 1 and 2 of BT2-1600 must be

DC24V.

▲ The module is stuck into the standard slideway of 35mm in width inside the switchgear cabinet.

Optional accessories

• Special power module

When the power voltage of BT2-1600 circuit breaker's intelligent control is AC230 or AC400V, it can be transformed into DC24 by this power module for power module for power supply of the OCR.

Note: The input of voltage to 1 and 2 terminals of the secondary circuit must be

DC24V.

This module is installed by getting stuck into the standard slideway with

35mm in width inside the switchgear cabinet.

• DC24V power module

○ DC Power Module intelligent control is DC24V, it can be transformed into DC24V by this power module for power supply of the OCR.

This module is installed by getting stuck into the standard slideway with 35mm in width inside the switchgear cabinet.

○ DC Power Module

• DC power supply module

When power supply of the secondary circuit is DC220V,

110V, it should be transformed into DC24V by this module for power supply of the OCR.

• Under-voltage release

The under-voltage release consists of release coil and control unit.

The under-voltage release works in two ways: operating instantaneously and operating in time delay.

13.0 ACCESSORIES consult with the manufacturer in the light of their order about special time-delay specifications as from 3s and above up to

9s. The time delay accurary is ±10%.

13.0 ACCESSORIES

▲ When the main body of the draw-out circuit breaker and the draw-out socket are at the with the time-delay module which is installed by getting stuck into the standard slideway with 35mm in width.The module input terminals connect with main circuit,the output terminals connect with terminal 31, 32 of the breaker.

▲ Features

Rated operational Voltage Ue(V)

○ Under-voltage release

For BT2-1600 Circuit Breaker

230

AC230V

0.5s

Fuju Electric FA

·68· delay release for BT2-1600

In connection with the main circuit

In connection with the terminals of

31 and 32 in the secondary circuit

Choice of communicate accessories

• Components of draw-out socket communication module

10

• Under-voltage signal

Rated Operational current Ie(A) module consists of the draw-out socket communication module outside of the circuit breaker and the draw-out

○Components of draw-out socket communication module inside of the draw-out socket to provide the status signals of

1.5

that the circuit breaker is tripping operation under-voltage.

• Fault-trip signal

You can achieve the information through the upper device that the circuit breaker is tripping operation because of over

▲ The components of draw-out socket communication

.module consists of the draw-out socket communication module outside of the circuit breaker and the draw-out socket out socket. The draw-out socket communication module, which can provide the function of reading the address of the circuit breaker and display the status indication of the socket communication parts are installed inside of the draw-out socket to provide the status signals of such three positions as is installed by getting stuck into the standard slideway the draw-out circuit breaker and the draw-out socket.The drawout socket communication module, which can provide the

BT2 with frame current of 2000A and above function of reading the address of the circuit breaker and display the status indication of the main body and three positions of the that the circuit breaker is ready for switching-on.

output

24

cabinet. The two parts of the draw-out socket communication module are connected with soft conducting lines.

▲ Features

A; B to RS485 B; S to RS485 SH; - to cathode of DC24V; + to anode of DC24V; A

’ to 8, B

’ to 10,

S ’ to 12; for BT2-1600, T1 to 61, T2 to 62, T3 to 63, T4 to 64; for BT2-2000 or above, T1 to Y5,

T2 to Y6, T3 to Y7, T4 to Y8.

Reliable Switching-on Voltage(V) save the communication address and the address will be changed accordingly. If users want to save

AC400

(0.35~0.7)Us

(0.85~1.1)Us

≤0.35Us

12VA

AC230 light on when DC24V power supply is given to the module. The communication lamp will light on

·69·

·70·

Air Circuit Breakers

BT2 series

Accessories

Choice of mechanical interlock accessories

• Two sets of circuit breakers put horizontally and interlocked with steel cable or stacked and interlocked with connecting rods

(the style of interlock between two sets of circuit breakers with connecting rods and aperture dimensions of their bases see the counterpart of three sets of circuit breakers)

2m (max)

Wiring diagram

1QF 2QF

Possible operation pattern

1QF 2QF

0

0

1

0

1

0

Circuit breaker 1 Circuit breaker 2

• Three sets of circuit breakers stacked and interlocked with connecting rods or three sets of circuit breakers put horizontally and interlocked with steel cable (without BT2-

1600).

• Stacked and interlocked

Wiring diagram Possible operation Pattern

Pattern one: three sets of power supply can only close one sets of circuit breaker

Pattern two: two sets of common power supply plus one sets of standly power supply

Pattern three: two sets of power supply plus a piece of coupling busbar

25

Air Circuit Breakers

BT2 series

Accessories

Steel cable interlocked

13.0 ACCESSORIES interlock between two sets of circuit breakers. The maximal distance of two circuit breakers is 2m.

○ Under-voltage release

Current transformer with neutral line N connected externally

• This current transformer, which is used together with circuit breakers with three poles in the power distribution system

Wiring diagram

In connection with the main circuit

Pattern three:Two sets of power supply plus a input far from the installation point.

• Characteristics

Under-voltageTime-delayModule

AC230V output

Rated working voltage

Acting voltage

Ue (V) AC400

(V) (0.35~0.7) Us

Reliable switching voltage (V) (0.85~1.1) Us

Reliable switching resistant voltage (V)

≤0.35Us

0.5s

Power consumption 12VA

AC230

For BT2-1600 Circuit Breaker

OUTPUT

Delay Module of Under-voltage

In connection with the terminals of

31 and 32 in the secondary circuit voltage-lowering. Generally, delay time, which is selective by users , is 0.5s,

1s, 2s and 3s.

delay release for BT2-1600

BT2 with frame current of 2000A and above

▲ The under-voltage release operates in two ways: operate instantaneously and operate in time delay;

Electrical mechanism for the indication of draw-out

▲ There are four specifications of time delay for the under-voltage time delay release: 0.5s, 1s,

2s and 3s. Users should consult with the manufacturer in the light of their order about special timeand “connected” respectively, three electrical mechanisms delay specifications as from 3s and above up to 9s. The time delay accurary is ±10%;

▲ The delay module should be additionally equipped for the under-voltage delay release. The module input connects with the main circuit, and the output connects with the wiring terminals of 31 and 32 in the secondary circuit;

▲ If the voltage of power supply returns to 85% Us and above in half of the delay time, the

Ith (A) 10

AC230

Operational Voltage(V)

Power Consumption

Convertional thermal current

Rated working current

·69·

Ue (V) 230

Ith (A) 10

Ie (A) 1.5

≤0.35Us

12VA

26

附 件

附 件

ACCESSORIES

附 件

ACCESSORIES

“分闸”锁定装置

“Break” lock mechanism

“Break” lock mechanism

“Break” lock mechanism

“分闸”锁定装置

Air Circuit Breakers

按下置上,此时,断路器将不能闭合。

用户选装后,工厂提供锁和钥匙。

BT2 series

Accessories

一台断路器配一把锁和一把钥匙;

二台断路器配二把相同的锁和一把钥匙;

二台断路器配二把相同的锁和一把钥匙;

三台断路器配三把相同的锁和二把钥匙。

“Break” lock mechanism

按下置上,此时,断路器将不能闭合。 button of the circuit breaker on the pressed position. As a result, the circuit breaker can not be switched on.

After this lock mechanism was chosen by users, the manufacturer would provide lock and key.

One set of circuit breaker is outfitted with one lock and one key.

Two sets of circuit breakers are outfitted with two same locks and one key.

Three sets of circuit breakers are outfitted with three

• “Button”locking device

• When installed “Button”locking device, it can prevented

钮。

钮。 somebody from operating button of switching-on or switching

按钮锁定装置

• Padlock should be provided by users themselves.

挂锁用户自备。

挂锁用户自备。 same locks and two keys.

prevented somebody from operating button of switching-on or prevented somebody from operating button of switching-on or switching off by mistake.

钮。

然。

然。

Padlock should be provided by users themselves.

计数器

计数器累计断路器机械操作的次数,用户一目了

“Button” locking device

Counter

The counter can count mechanical operation times

计数器

相间隔板加强母排间绝缘,为断路器选择件,用

户需要时可配置。

Separator plate between phases

Separator plates between phases which strengthen insulation between bus-bars are optional and will be

相间隔板加强母排间绝缘,为断路器选择件,用

户需要时可配置。

45

Separator plate between phases

Separator plates between phases which strengthen insulation between bus-bars are optional and will be equipped as needed by users.

45

27

Air Circuit Breakers

BT2 series

Technical data

Power consumption and derating coefficient

• Power consumption (Environment temperature +40°C)

Power consumption is the overall consumption measured under with the circuit breaker is electrified with current below frame current.

Type

BT2-1600

BT2-2000

BT2-2500

BT2-4000

BT2-6300

Three poles/four poles (W)

Fixed type

152

203.6

356.8

648.96

1050.1

• Derating coefficient

The following table shows continual current-loading capacity of circuit breakers at different ambient environment temperature and under the conditions of the satisfaction of conventional heating in IEC60947-2

Ambient Environment temperature

Continual current-loading capacity

Inm=1600A

Inm=2000A

Inm=2500A

Inm=4000A

Inm=6300A

+40°C

1Inm

1Inm

1Inm

1Inm

1Inm

+45°C

0.99Inm

0.97Inm

0.96Inm

0.95Inm

0.93Inm

Derating for high-elevation

If elevation exceeds work environment 2000m, electric property of circuit breaker can correct according to following table: elevation (m)

Power-frequency withstand voltage (V)

Correction factor of operational current

Correction factor of short-circuit breaking capacity

1

1

2000

3500

3000

3150

0.93

0.83

Draw-out type

408

382.8

823.4

897.6

1200.2

+50°C

0.96Inm

0.91Inm

0.90Inm

0.89Inm

0.87Inm

+55°C

0.90Inm

0.87Inm

0.86Inm

0.85Inm

0.82Inm

+60°C

0.87Inm

0.82Inm

0.80Inm

0.78Inm

0.75Inm

4000

2500

0.88

0.71

5000

2000

0.82

0.63

28

Air Circuit Breakers

BT2 series

Technical data

Reference table of main circuit wiring copper bar for draw-out circuit breaders

Rated frame current (A)

1600

2000

2500

4000

6300

Rated current (A)

800

1000

1250

1600

2000

1250

1600

2000

200

400

630

800

1000

1250

1600

630

2500

2000

2500

2900

3200

3600

4000

4000

5000

6300

Specifications of copper bars

Number

1

1

2

2

3

4

2

2

2

2

3

2

3

3

2

3

4

3

4

3

4

4

5

5

6

8

Size (mm×mm)

20×5

50×5

40×5

50×5

40×5

40×5

50×10

50×5

60×5

60×5

60×5

60×10

60×10

60×5

60×10

60×10

60×10

100×5

100×5

100×10

100×10

100×10

100×10

100×10

100×10

100×10

The specifications of copper bars in the above table are introduced under which the circuit breakers by open installation are at maximum ambient environment temperature of 40°C and satisfy conventional heating in IEC60947-2.

29

Air Circuit Breakers

BT2 series

Dimensions and mounting

Dimensions and mounting, mm

BT2-1600 Air Circuit Breaker with three poles (draw-out type)

Current specifications

800A, 1000A, 1250A, 1600A

200A, 400A, 630A

L (mm)

15

10

Outside of the cabinet doo

Direction A

Base point

“Separated”position

Horizontal (back set)

Direction D

Outside of the cabinet door

Base point

“Separated”position

Vertical (back set)

Direction C

30

Air Circuit Breakers

BT2 series

Dimensions and mounting

Dimensions and mounting, mm

BT2-1600 Air Circuit Breaker with four poles (draw-out type)

Current specifications

800A, 1000A, 1250A, 1600A

200A, 400A, 630A

L (mm)

15

10

70

Direction A

70 70

16ø11

25

N pole

50

Outside of the cabinet door

51

A

46

Base point

72.5

77.5

102.5

297

“Separated”position

Horizontal (back set)

D

Direction D

2ø 6.5

2-6.5x8.5

Outside of the cabinet door

57

102

201

46

Base point

72.5

77.5

102.5

297

“Separated”position

Vertical (back set)

N pole

L

Direction C

70 70 70

60

C

51

15

16ø 11

31

Air Circuit Breakers

BT2 series

Dimensions and mounting

Dimensions and mounting, mm

BT2-1600 Air Circuit Breaker with three poles (fixed type)

Current specifications

800A, 1000A, 1250A, 1600A

200A, 400A, 630A

L (mm)

15

10

50

25

Direction A

12ø11

70 70

Outside of the cabinet door

32

A

4ø6.5

Base point

4ø6.5

100

192

197

38.5 50.6

Horizontal (back set)

244

10 234 10

4ø6.5

214

234

Breaker base

Aperture dimensions of the back plate at the time of hanging type installation

Outside of the cabinet door

32

C

15

Base point

4-

ø6.5

100

192

197

38.5 50.6

Vertical (back set)

Direction C

L

70 70

32

Air Circuit Breakers

BT2 series

Dimensions and mounting

Dimensions and mounting, mm

BT2-1600 Air Circuit Breaker with four poles (fixed type)

Current specifications

800A, 1000A, 1250A, 1600A

200A, 400A, 630A

L (mm)

15

10

25

50

Direction A

N pole

70 70 70

16ø11

Outside of the cabinet door

32

A

4ø6.5

Base point

4ø6.5

100

192

197

38.5 50.6

Horizontal (back set)

314

10 304 10

4ø6.5

Breaker base

284

304

Aperture dimensions of the back plate at the time of hanging type installation

Outside of the cabinet door

32

C

15

Base point

4ø6.5

100

192

197

38.5 50.6

Vertical (back set)

L

Direction C

N pole

70 70 70

33

Air Circuit Breakers

BT2 series

Dimensions and mounting

Dimensions and mounting, mm

BT2-2000 Air Circuit Breaker with three poles (draw-out type)

Current specifications

2000A

630A, 800A, 1000A,

1250A, 1600A

L (mm)

20

15

H (mm)

20

15

A (mm)

30

25

Outside of the cabinet door

61

A

Direction A

95 95

24ø 11

30 70

10

47

Base point

97

102

175

390

“Separated”position

Horizontal (back set)

D

41 265 41

Direction D

2ø 14

11x17

ø 11

Outside of the cabinet door

15

60

C

15

Base point

24-

47

10

97

102

175

390

“Separated”position

Vertical (back set)

ø

11

66

Direction C

95 95

60

30

10

34

Air Circuit Breakers

BT2 series

Dimensions and mounting

Dimensions and mounting, mm

BT2-2000 Air Circuit Breaker with four poles (draw-out type)

Current specifications

2000A

630A, 800A, 1000A,

1250A, 1600A

L (mm)

20

15

H (mm)

20

15

A (mm)

30

25

Outside of the cabinet door

61

A

95

Direction A

95 95

32-

ø11

N pole

30 70

Base point

47

10

97

102

175

390

“Separated”position

Horizontal (back set)

D

Direction D

2ø14

11 x 17

ø11

41 360 41

Outside of the cabinet door

30

60

C

15

Base point

47

10

97

102

175

390

“Separated”position

Vertical (back set)

32ø11

66

95

Direction C

95 95

N pole

60

30

10

35

Air Circuit Breakers

BT2 series

Dimensions and mounting

Dimensions and mounting, mm

BT2-2000 Air Circuit Breaker with three poles (fixed type)

Current specifications L (mm) A (mm) W (mm) B (mm)

2000A 20 269 20 13

630A, 800A, 1000A,

1250A, 1600A

15 264 15 3

Outside of the cabinet door

61

A

30

Direction A

95 95

24ø11

60

Base point

150

285

290

Horizontal (back set)

4ø12

69.5

11 340

Base point

11

Direction C

95 95

60

30

10

Outside of the cabinet door

C

60

Base point

24-

150

285

Vertical (back set)

69.5

15

94

30

ø11

36

Air Circuit Breakers

BT2 series

Dimensions and mounting

Dimensions and mounting, mm

BT2-2000 Air Circuit Breaker with four poles (fixed type)

Current specifications L (mm) A (mm) W (mm) B (mm)

2000A 20 269 20 13

630A, 800A, 1000A,

1250A, 1600A

15 264 15 3

Outside of the cabinet door

61

A

95

Direction A

95 95

32-

ø

11

N pole 30 60

Base point

4ø 12

150

285

290

Horizontal (back set)

69.5

11 435

Base point

11

95

Direction C

95 95

N pole 60

30

10

Outside of the cabinet door

60

C

Base point

32-

150

285

Horizontal (back set)

15

69.5

94

30

ø 11

37

Air Circuit Breakers

BT2 series

Dimensions and mounting

Dimensions and mounting, mm

BT2-2500 Air Circuit Breaker with three poles (draw-out type)

Current specifications

2000A, 2500A

1250A, 1600A

L (mm)

20

15

Outside of the cabinet door

62

A

10

47

Base point

97

102

175

390

“Separated”position

Horizontal (back set)

D

Direction A

95 95

24ø11

30 70

41 265 41

Direction D

2ø14

Outside of the cabinet door

C

62

24ø11

11x17

ø11

Base point

47

10

97

102

175

390

“Separated”position

Vertical (back set)

Direction C

95 95

L

38

Air Circuit Breakers

BT2 series

Dimensions and mounting

Dimensions and mounting, mm

BT2-2500 Air Circuit Breaker with four poles (draw-out type)

Current specifications

2000A, 2500A

1250A, 1600A

L (mm)

20

15

Outside of the cabinet door

62

A

95

Direction A

95 95

32ø11

30

N pole

70

Base point

47

10

97

102

175

390

“Separated”position

Horizontal (back set)

D

41 360 41

Direction D

2ø14

11x17

ø 11

Outside of the cabinet door

Base point

47

10

97

102

175

390

“Separated”position

Vertical (back set)

L

N pole

95

Direction C

95 95

C

62

32ø11

39

Air Circuit Breakers

BT2 series

Dimensions and mounting

Dimensions and mounting, mm

BT2-2500 Air Circuit Breaker with three poles (fixed type)

Current specifications

2000A, 2500A

1250A, 1600A

L (mm)

20

15

C (mm)

132

134.5

Outside of the cabinet door

61

61

A

A

30

30

95

95

95

60

60

24-

ø11

24ø11

Base

285

290

Horizontal (back set)

4ø12

4ø12

69.5

69.5

BT2-2500 Air Circuit Breaker with four poles (fixed type)

Current specifications

2000A, 2500A

1250A, 1600A

L (mm)

20

15

C (mm)

132

134.5

11

11

340

340

Base

point

11

11

95

Direction A

95 95

95 95 95

N pole

30

30

60

60

32ø11

32ø11

Outside of the cabinet door

61

61

A

A

Base point

150

285

150

4-

ø12

4-

ø12

69.5

69.5

11

11

435

435

Base

point

11

11

40

Air Circuit Breakers

BT2 series

Dimensions and mounting

Dimensions and mounting, mm

BT2-4000 Air Circuit Breaker with three poles (draw-out type)

Direction A

130 130

24ø17

50 100

Outside of the cabinet door

104

A

47

10

Base point

97 175

102

395

“Separated”position

Horizontal (back set)

B

Direction B

ø11

Outside of the cabinet door

37 327

37

C

104

50 25

11x17

2-

ø14

Base point

10

47

Base point

97

102

175

395

“Separated”position

Horizontal (back set)

24-

ø17

Direction C

113 113

10

30

41

Air Circuit Breakers

BT2 series

Dimensions and mounting

Dimensions and mounting, mm

BT2-4000 Air Circuit Breaker with four poles (draw-out type)

130

Direction A

130 130

32ø17

N pole

50 100

Outside of the cabinet door

104

A

Base point

47

10

97

102

175

395

“Separated”position

Horizontal (back set)

Direction B

ø11

B

Outside of the cabinet door

37 440 37

C

104

50

25

11x17

2ø14

Base point 10

47

Base point

97

102

175

395

“Separated”position

Vertical (back set)

32ø17

113

Direction C

113 113

N pole

10

30

42

Air Circuit Breakers

BT2 series

Dimensions and mounting

Dimensions and mounting, mm

BT2-4000 Air Circuit Breaker with three poles (fixed type)

Direction A

24-

ø13

Outside of the cabinet door

Base point

4ø12

Horizontal (back set)

BT2-4000 Air Circuit Breaker with four poles (fixed type)

Base point

N pole

Direction A

32ø13

Outside of the cabinet door

Base point

4ø12

Horizontal (back set)

Base point

43

Air Circuit Breakers

BT2 series

Dimensions and mounting

Dimensions and mounting, mm

BT2-6300 Air Circuit Breaker with three poles (draw-out type)

113 126.5

Direction A

130 126.5

113

48ø17

50

100

183

Outside of the cabinet door

104

A

Base point

10

47

77

82

258

395

“Separated”position

Horizontal (back set)

6-

ø11

Current specifications:

In=4000A, 5000A

Base point

693

767

113 126.5

Direction C

113 126.5

113

10

30

Outside of the cabinet door

48ø17

Base point

6ø11

10

47

77

82

258

395

“Separated”position

Vertically (back set)

Current specifications:

In=4000A, 5000A, 6300A

C

104

50

25

44

Air Circuit Breakers

BT2 series

Dimensions and mounting

Dimensions and mounting, mm

BT2-6300 Air Circuit Breaker with four poles (draw-out type)

113 130 113

Direction A

123 113 130 113

64ø 17

N pole

50

100

Outside of the cabinet door

104

A

239.5

Base point

6-

ø

11

10

47

77

82

258

395

“Separated”position

Horizontal (back set)

Current specifications:

In=4000A, 5000A

Base point

95

919

993

113 113 113

Direction C

140

113 113 113

N pole

10

30

Outside of the cabinet door

Base point

64ø 17

8ø 11

10

47

77

82

258

395

“Separated”position

Vertical (back set)

Current specifications:

In=4000A, 5000A, 6300A

C

104

50 25

45

Air Circuit Breakers

BT2 series

Dimensions and mounting

Dimensions and mounting, mm

BT2-6300 Air Circuit Breaker with three poles (fixed type)

205

205

50 55 50

Direction A

239.5

239.5

239.5

239.5

Outside of the cabinet door

134

134

A

A

Base point

4-

4-

ø12

ø12

150

150

290

290

Horizontal (back set)

69.5

69.5

BT2-6300 Air Circuit Breaker with four poles (fixed type)

11

11

205

205

50 55

50

50

N pole

226

226

Outside of the cabinet door

134

134

A

A

760

760

Direction A

253

253

226

226

Base point

11

11

Base point

4ø12

4-

ø12

150

150

290

290

Horizontal (back set)

69.5

69.5

11

11

986

986

Base point

11

11

46

Air Circuit Breakers

BT2 series

Dimensions and mounting

Door frame dimensions, mm

BT2-1600 door frame

BT2-1600 Air Circuit Breakers with three poles (draw-out)

The drawing of aperture dimensions for mounting cover of door frame

Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 227mm

BT2-1600 Air Circuit Breakers with four poles (draw-out)

The drawing of aperture dimensions for mounting front cover of door frame

Distance from the panel center of the Circuit Breaker to the right hinge of cabinet door should be at least 262mm

10-

ø

6

Breaker base

216

254

10-

ø

6

Breaker base

286

324

BT2-1600 Air Circuit Breakers with three poles (fixed type)

The drawing of aperture dimensions for mounting cover of door frame

Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 227mm

BT2-1600 Air Circuit Breakers with four poles (fixed type)

The drawing of aperture dimensions for mounting front cover of door frame

Distance from the panel center of the Circuit Breaker to the right hinge of cabinet door should be at least 262mm

Breaker base

216

254

10-

ø

6

10ø 6

Breaker base

286

324

47

Air Circuit Breakers

BT2 series

Dimensions and mounting

Door frame dimensions, mm

Aperture Dimension of BT2-2000 door frame

BT2-2000 Air Circuit Breakers with three poles (draw-out)

The drawing of Aperture Dimensions for mounting front cover of cabubet door

Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 256mm

BT2-2000 Air Circuit Breakers with four poles (draw-out)

The drawing of Aperture Dimensions for mounting front cover of cabinut door

Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 303.5mm

Breaker base

11-ø6

175

258

312

175

Breaker base

14-ø6

100

353

407

445

BT2-2000 Air Circuit Breakers with three poles (fixed)

The drawing of Aperture Dimensions for mounting front cover of cabunet door

Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 256mm

BT2-2000 Air Circuit Breakers with four poles (fixed)

The drawing of Aperture Dimensions for mounting front cover of cabinut door

Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 303.5mm

48

Breaker base

8-ø6

175

312

175

Breaker base

10-ø6

100

407

445

Air Circuit Breakers

BT2 series

Dimensions and mounting

Door frame dimensions, mm

Aperture Dimension of BT2-2500 door frame

BT2-2500 Air Circuit Breakers with three poles (draw-out)

The drawing of Aperture Dimensions for mounting cover of door frame

Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 256mm

BT2-2500 Air Circuit Breakers with four poles (draw-out)

The drawing of Aperture Dimensions for mounting cover of door frame

Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 303.5mm

Breaker base

11-ø6

175

258

312

175

Breaker base

14-ø6

100

353

407

445

BT2-2500 Air Circuit Breakers with three poles (fixed)

The drawing of Aperture Dimensions for mounting cover of door frame

Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 256mm

BT2-2500 Air Circuit Breakers with four poles (fixed)

The drawing of Aperture Dimensions for mounting cover of door frame

Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 303.5mm

Breaker base

8-ø6

175

312

175

Breaker base

10-ø6

100

407

445

49

Air Circuit Breakers

BT2 series

Dimensions and mounting

Door frame dimensions, mm

Aperture Dimension of BT2-4000 door frame

BT2-4000 Air Circuit Breakers with three poles (draw-out)

The drawing of Aperture Dimensions for mounting cover of door frame

Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 264mm

BT2-4000 Air Circuit Breakers with four poles (draw-out)

The drawing of Aperture Dimensions for mounting cover of door frame

Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 320.5mm

Breaker base

11-ø6

Breaker base

14-ø6

312

328

366

100

425

441

479

BT2-4000 Air Circuit Breakers with three poles (fixed)

The drawing of Aperture Dimensions for mounting cover of door frame

Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 264mm

BT2-4000 Air Circuit Breakers with four poles (fixed)

The drawing of Aperture Dimensions for mounting cover of door frame

Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 320.5mm

50

Breaker base

8-ø6

328

366

Breaker base

10-ø6

100

441

479

Air Circuit Breakers

BT2 series

Dimensions and mounting

Door frame dimensions, mm

Aperture Dimension of BT2-6300 door frame

BT2-6300 Air Circuit Breakers with three poles (draw-out)

The drawing of Aperture Dimensions for mounting cover of door frame

Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 264mm

BT2-6300 Air Circuit Breakers with four poles (draw-out)

The drawing of Aperture Dimensions for mounting cover of door frame

Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 320.5mm

Breaker base

11-ø6

312

328

366

Breaker base

14-ø6

100

425

441

479

BT2-6300 Air Circuit Breakers with three poles (fixed)

The drawing of Aperture Dimensions for mounting cover of door frame

Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 264mm

BT2-6300 Air Circuit Breakers with four poles (fixed)

The drawing of Aperture Dimensions for mounting cover of door frame

Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 320.5mm

Breaker base

8-ø6

328

366

Breaker base

10-ø6

100

441

479

51

Air Circuit Breakers

BT2 series

Dimensions and mounting

Mounting safety clearance

Draw-out breaker

Minimum distance between breaker with switchboard wall or live part.

d1 (note) (mm) d2 (mm)

Switchboard wall Live part

0 60

0 60

Fixed breaker

Minimum distance between breaker with switchboard wall or live part.

d1 (note) (mm) d2 (mm)

Switchboard wall Live part

0

0

60

60

Note:secondary circuit wiring must be considered for safety clearance.

52

Air Circuit Breakers

BT2 series

Dimensions and mounting

自动电源转换系统外形尺寸及安装尺寸

自动电源转换系统外形尺寸及安装尺寸

OUTLINE DIMENSIONS AND MOUNTING DIMENSIONS

OFAUTOMATIC POWER SUPPLYSWITCH SYSTEM

OFAUTOMATIC POWER SUPPLYSWITCH SYSTEM

转接器

转接器

The switching unit

Φ6.5

R、S型自动转换控制器

R、S型自动转换控制器

Type R and S Automatic transfer controller

R

U

N

N ormal s upply

C lose

O pen

O pen

Power genera ting

M alfuncti on

Power genera ting

Norm al supp ly

Stop

Auto matic

U

R

Stand by Pow er

Close

Open

Open

Malfu nction

1

2

0.5

4 8 16

1

0.5

24

32

64

32

64 Norm al

Sta nding

1

2

0.5

4 8 16

24

32

64

1

0.5

U =I

32

64

Stop

143

143

F型自动转换控制器

F型自动转换控制器

Type F automatic transfer controller

Under- voltage vol tage

Under- voltage vol tage

Norma l power supply

Under- voltage vol tage

Under- voltage vol tage

Under- voltage vol tage

Sta nding p ower su pply

Under- voltage vol tage

Switching unit

146

Norm al powe r supply

Standin g power supply

90

96

96

U

N

R

No rmal sup ply

Clo se

Op en

Op en

Autom a tic

N ormal supply

Stop

Autom a tic

Stop

U

U

R

1

2

1

0.5

0.5

2

1

0.5

4 8 16

24

32

4 8 16

32

64

24

32

U =I 120

64

32

18 0

18 0

120

64

32

240 300

360

480

600

360

480

600

O pen

M alfunctio n

1

2

1

0.5

0.5

2

1

0.5

U =0

4 8 16

32

64

24

32

N

64

8

4

1

U =1

96

120

8

16 32 64 180

4

1

120

180

U =I

2

0.5

4

2

0.5

8 16

3

32

64

32

64

120

240

U =0

1

2

0.5

2

4 8 16

4

1

0.5

24

32

24

32

64

Changshu Sw itchge ar Mfg. Co., Ltd. (Former Changshu S witchg ear Plant)

143

143

90

96

96

75

75

66.5

136

136

53

Air Circuit Breakers

BT2 series

Wiring diagram

断路器二次回路接线图

WIRING DIAGRAM OF SECONDARY CIRCUIT

Wiring diagram of secondary circuit

Tes t ind ication

Connec tion indication

54

76

Air Circuit Breakers

BT2 series

Wiring diagram

断路器二次回路接线图

WIRING DIAGRAM OF SECONDARY CIRCUIT

n tio ion ica art n n tion tio tio ica nec d ica t ind

Con in

Tes ind

Sep n tio on ica arti ind

Sep

77

55

Air Circuit Breakers

BT2 series

Wiring diagram

断路器二次回路接线图

WIRING DIAGRAM OF SECONDARY CIRCUIT

n tio n n tio tio ica nec ica t ind

Tes ind

Con t n tio ata

Tes

Sep n tio nec Con

56

78

Air Circuit Breakers

BT2 series

Wiring diagram

断路器二次回路接线图

WIRING DIAGRAM OF SECONDARY CIRCUIT

on n ati tio par dic n on ati tion tio ica nec dic st in

Te ind

Con in

Se n tio ion ica art ind

Sep

79

57

Air Circuit Breakers

BT2 series

Wiring diagram

自动电源转换系统电气线路图

1 2 3 4 5 6 7 8 9

10111213141516171819

58

80

自动电源转换系统电气线路图

Air Circuit Breakers

BT2 series

Wiring diagram

1 2 3 4 5 6 7 8 9

10111213141516171819

81

59

Air Circuit Breakers

BT2 series

Wiring diagram

自动电源转换系统电气线路图

1 2 3 4 5 6 7 8 9

1011121314151617 1819

60

82

自动电源转换系统电气线路图

Air Circuit Breakers

BT2 series

Wiring diagram

1 2 3 4 5 6 7 8 9

1011121314 1516 1718 19

83

61

Air Circuit Breakers

BT2 series

Ordering form

Ordering form

1. Users should make sure of their detailed acquaintance of the products’ technological materials and make order by the

2. The company would configure by“Factory's setting values of the intelligent release” if users had no requirements of

“ordering form”in terms of future applicable situations of the circuit breakers.

Ordering form

Ordering form

(Please fill numbers in or mark

√ in )

Customer name

Order quantity Date

Type BT2- / E Rated voltage AC400V AC690V

Use Standard Humid tropical (TH) Rated current

Connection Fixed Horizontal (Rear connection) Vertical (Rear connection)

In= A

Draw-out Horizontal (Rear connection) Vertical (Rear connection)

Type selection

Basic function

Type L25 Type M25 Type M26 Type H26 Type P26 Type P25

Current indication

LED current indication

LED current indication and communication function

LCD current indication and wattmeter function

Long-time delay overload protection Short-time delay short circuit protection Instantaneous short circuit protection

Selective function

Ir

1

t

1

Ir

2

t

2

Ir

3

Ground-fault protection Ir

4

Long-time delay overload protection

General inverse time delay (I 2 t)

t

4

Long-time delay overload protection

General inverse time delay (I

2 t)

Special inverse time delay (It)

High-voltage fuse type (I

4 t)

50%In 100%In

(Select setting current of N line)

Test function MCR function Thermo-analogue function Alarm and fault indication

Contact wearing indication Fault memory Self-diagnosis

Indication of voltage

OFF 50%In 100%In 200%In

(200% In for three-pole breaker + neutral line transformer BT2-6300 except)

Voltage of the intelligent controller

ZSI function Load-monitoring function: Pattern one Pattern two

Communication function

Harmonic meter Current-imbalace display

BT2-2000 and above

BT2-1600

AC230V AC400V

DC24V

Need be selectively equipped with DC24V power supply module

AC230V AC400V

Need be selectively equipped power supply module

DC220V DC110V

Need to use with DC power supply module

AC230V AC400V DC110V DC220V

AC230V AC400V DC110V DC220V

AC230V AC400V DC110V DC220V

Shunt release

Closing coil

Power-driven operation mechanism

Auxiliary switch

Under-voltage release

Lock in “OFF” mechanism

Standard pattern 4 changeover contacts

Special pattern

4NO + 4NC

6NO + 2NC

2NO + 6NC

AC230V AC400V

Under-voltage instantaneous release

One set of circuit breaker

Two sets of circuit breakers

Under-voltage time delay release 0.5s 1s 2s 3s

One lock and one key

Two locks and one key

Mechanical interlock

Three sets of circuit breakers

Two sets of circuit breakers

Cable type interlock

Three locks and two keys

Rod type interlock

Cable type interlock Pattern one of Rod type interlock Pattern two of Rod type interlock Pattern three of Rod type interlock

Connection of external CT for neutral Draw out position indication Interphase barrier

Ready to close indication

Communication accessories

Push button locking device

Components of draw-out socket communication module

Counter

Signal of ready-for-switching on Signal of under-voltage Signal of fault release

DC power supply module DC220V DC110V

Automatic transfer switch (ATS)

DC24V power supply module

Automatic transfer switch (ATS) R type S type F type

62

Air Circuit Breakers

BT2 series

Ordering notice

Ordering notice

Factory's setting values of intelligent controller

Overload long-time delay Setting values of current I r1

Setting values of delay time t

1

Overload long-time delay of P25 and P26

Short circuit short-time delay Setting values of current I r2

I

In

480s

2

6I t r1

Setting values of delay time

0.2s

t

2

Setting values of short circuit instantaneous current

I r3

Ground-fault

(Not for L25, M25, P25)

Setting values of current

Setting values of delay time

I t r4

4

15In (for In

≤ 1000A)

12In (for In = 1250A, 1600A)

10In (for In

≥ 2000A)

BT2-1600 BT2-2000

BT2-2500

0.8In or 1000A

To select the minimum

0.4s

0.8In or 1200A

To select the minimum

Load-monitoring

(Not for type L25, optional for type M25, M26, H26,

P25 and P26)

Monitoring current

Monitoring current

I

I

LC1

LC2

In

In

BT2-4000

0.8In or 1600A

To select the minimum

BT2-6300

2000A

63

Catalog Disclaimer

The information contained in this catalog does not constitute an express or implied warranty of quality, any warranty of merchantability of fitness for a particular purpose is hereby disclaimed.

Since the user's product information, specific use application, and conditions of use are all outside of Fuji Electric FA

Components & Systems'control, it shall be the responsibility of the user to determine the suitability of any of the

products mentioned for the user's application.

One Year Limited Warranty

The products identified in this catalog shall be sold pursuant to the terms and conditions identified in the

"Conditions of Sale" issued by Fuji Electric FA with each order confirmation.

Except to the extent otherwise provided for in the Conditions of Sale issued by Fuji Electric FA, Fuji Electric FA warrants that the Fuji Electric FA products identified in this catalog shall be free from significant defects in materials and workmanship provided the product has not been: 1) repaired or altered by others than Fuji Electric FA; 2) subjected to negligence, accident, misuse, or damage by circumstances beyond Fuji Electric FA's control; 3) improperly operated, maintained or stored; or 4) used in other than normal use or service. This warranty shall apply only to defects appearing within one (1) year from the date of shipment by Fuji Electric FA, and in such case, only if such defects are reported to Fuji Electric FA within thirty (30) days of discovery by purchaser. Such notice should be submitted in writing to Fuji

Electric FA at 5-7, Nihonbashi Odemma-cho, Chuo-ku, Tokyo, Japan. The sole and exclusive remedy with respected to the above warranty whether such claim is based on warranty, contract, negligence, strict liability or any other theory, is limited to the repair or replacement of such product or, at Fuji Electric FA's option reimbursement by Fuji Electric

FA of the purchase price paid to Fuji Electric FA for the particular product. Fuji Electric FA does not make any other

representations or warranties, whether oral or in writing, expressed or implied, including but not limited to any

warranty regarding merchantability or fitness for a particular purpose. Except as provided in the Conditions of

Sale, no agent or representative of Fuji Electric FA is authorized to modify the terms of this warranty in writing or orally.

In no event shall Fuji Electric FA be liable for special, indirect or consequential damages, including but not limited to, loss of use of the product, other equipment, plant and power system which is installed with the product, loss of profits or revenues, cost of capital, or claims against the purchaser or user of the product by its customers resulting from the use of information, recommendations and descriptions contained herein. The purchaser agrees to pass on to its customers and users, in writing at the time inquiries and orders are received by buyer, Fuji Electric FA's warranty as set forth above.

Safety Considerations

• Operate (keep) in the environment specified in the operating instructions and manual. High temperature, high humidity, condensation, dust, corrosive gases, oil, organic solvents, excessive vibration or shock might cause electric shock, fire, erratic operation or failure.

• For safe operation, before using the product read the instruction manual or user manual that comes with the product carefully or consult the Fuji sales representative from which you purchased the product.

• Products introduced in this catalog have not been designed or manufactured for such applications in a system or equipment that will affect human bodies or lives.

• Customers, who want to use the products introduced in this catalog for special systems or devices such as for atomic-energy control, aerospace use, medical use, passenger vehicle, and traffic control, are requested to consult with Fuji Electric FA.

• Customers are requested to prepare safety measures when they apply the products introduced in this catalog to such systems or facilities that will affect human lives or cause severe damage to property if the products become faulty.

• For safe operation, wiring should be conducted only by qualified engineers who have sufficient technical knowledge about electrical work or wiring.

• Follow the regulations of industrial wastes when the product is to be discarded.

• For further questions, please contact your Fuji sales representative or Fuji Electric FA.