Air Circuit Breakers BT2 Series
5-7, Nihonbashi Odemma-cho, Chuo-ku, Tokyo, 103-0011, Japan
URL http://www.fujielectric.co.jp/fcs/eng
Information in this catalog is subject to change without notice.
Printed in Japan 2012-1 Ed5 FOLS EEH606
EEH606
Air Circuit Breakers
BT2 Series 1600 to 6300A
Contents
Features .................................................................... 3
Type number nomenclature ........................................ 6
Specifications ............................................................. 7
Appearance ................................................................ 8
Intelligent controller (OCR) ......................................... 9
Communication ......................................................... 14
Characteristics curve ................................................ 16
Accessories .............................................................. 23
Technical data ........................................................... 28
Dimensions and mounting ........................................ 30
Wiring diagram ......................................................... 54
Ordering form ........................................................... 62
Ordering notice ......................................................... 63
Air Circuit Breakers
BT2 series
Features
Selection guide
Series BT2 series
Frame size
No. of poles
Installation
Closing Mechanism
Tripping Mechanism
Protection function
Fixed
Draw-out
1600, 2000, 2500, 4000, 6300
3, 4
Available
Available
Manual spring or motor spring
Shunt trip, Under-voltage trip
Long time delay, Short time delay, Instantaneous, Ground fault, etc.
Breaking Capacity
Icu is equal to Ics up to 120kA at maximum and Icw is up to 100kA at maximum under 400VAC distribution.
3
产 品 特 点
优异的升级换代性能
CW2-2000断 路 器 , 可 直 接 替 换 原 CW1-
Air Circuit Breakers
BT2 series
Features
CW2-2000 can directly substitute for CW1-
2000 without changing copper bar and aperture dimensions on the panel sheet.
产 品 特 点
优异的升级换代性能
CW2-2000断 路 器 , 可 直 接 替 换 原 CW1-
2000断路器,无需改变母排和柜门的开孔尺寸。
Compact size
BT2 series, Air Circuit Breakers, have five framesize and four physical dimension sizes.
Ampere frame
1600 2000 2500
Outsta ding upgrade performance
4000
Appearance
CW2-2000 can directly substitute for CW1-
2000 without changing copper bar and aperture
6300
简便安装、节约成本
CW2系列断路器具有更简单的安装方式,可以
简便实现
水平连接
垂直连接
混合连接
Simply installed、cost-saving
CW2 Series Circuit Breakers can be simply installed as follows:
Horizontal connection
Vertical connection
Composite connection
CW2系列断路器具有更简单的安装方式,可以
简便实现
水平连接
垂直连接
混合连接
Width 401mm
CW2 Series Circuit Breakers can be simply installed as follows:
Horizontal connection
Vertical connection
Composite connection
• Vertical connection
• Composite connection
先进可靠的安全性能
CW2系列断路器具有可靠的:
抽屉座三位置锁定和自动解锁装置,安全
确认“连接”、“试验”、“分离”三个位置。
Advanced and reliable safety performance
CW2 Series Circuit Breakers are reliable by the following aspects:
Reliable assurance of the three positions: connected、 test、 separated by the locked and automatically unlocked mechanism at the draw-out socket.
767mm
Safety performance
BT2 series, Air Circuit Breakers, are reliable by the following aspects:
• Reliable assurance of the three positions:
Connected
Test
Separated by the locked and automatically unlocked mechanism at the draw-out socket.
Clear indication of ready-for-switching-on to ensure safe manipulation and reliable operation.
Indication of ready-forswitching-on:"ok"
先进可靠的安全性能
CW2系列断路器具有可靠的:
抽屉座三位置锁定和自动解锁装置,安全
确认“连接”、“试验”、“分离”三个位置。
Advanced and reliable safety performance
CW2 Series Circuit Breakers are reliable by the following aspects:
Reliable assurance of the three positions: connected、 test、 separated by the locked and automatically unlocked mechanism at the draw-out socket.
5
More reliable safety protection with seconday terminals of protection grade IP30
4
5
Air Circuit Breakers
BT2 series
Features
Protection and selection
BT2 Series, Air Circuit Breakers, can implement selective interlock of ZSI Region to ensure comprehensive selection of various protection and reduce the copper bar's bearing of thermodynamic.
21
22
23
24
21
22
23
24
21
22
23
24
Intelligent controller (OCR)
Selecting OCR's, it can be classified into six types
Type L25
Option
M25
Standard
Pic
L25 Intelligent Controller M25 Intelligent Controller
M26
Option
M26 Intelligent Controller
H26
Option
H26 Intelligent Controller
21
22
23
24
P25
Option
P25 Intelligent Controller
P26
Option
P26 Intelligent Controller
Display/setting Light columnar indication LED digtal indication LED digtal indication LED digtal indication LCD indication
Dial setting by knob Consecutive Consecutive Consecutive Consecutive parameter setting parameter setting parameter setting parameter setting
Protection/ function t t t t t t t t t t t t t t t t t t t
LCD indication
Consecutive parameter setting t
I
I I
I I
I I
I t t t t
I I I
I
I
I I
I t t t t
I I I
I
I
I
I
I
I I t
I t
I
5
I
I
Air Circuit Breakers
BT2 series
Type number nomenclature
6
Type number nomenclature
BT2-2500P / 32500E
Basic type
Frame size
1600, 2000, 2500, 4000, 6300
Installation
P: Fixed type
X: Draw-out type
Number of poles
3: 3 poles
4: 4 poles
Rated current
1600AF: 0200, 0400, 0630, 0800, 1000, 1250, 1600
2000AF: 0630, 0800, 1000, 1250, 1600, 2000
2500AF: 1250, 1600, 2000, 2500
4000AF: 2000, 25000, 2900, 3200, 3600, 4000
6300AF: 4000, 5000, 6300
CE version
P25
P26
OCR type or Additional accessories
• OCR type (note: M25 is standard), See page 9
Type
L25
Code
L5A
Remarks
M25
H26
– (None)
H6A
P5A
P5B
P5C
P5D
P6A
P6B
P6C
P6D w harmonic analysis function w communication function w alarm of current-imbalance w harmonic analysis function w communication function w alarm of current-imbalance
• Accessories
Type
LED indicator of Voltage
Load-monitoring function
ZSI function
(Zone selective interlock function)
Under voltage release
Code
C1
C2
C3
Remarks
Switching OFF lock device
Mechanical interlock device
(Two sets of ACB's)
Mechanical interlock device
(Three sets of ACB's)
Current transformer for neutral line N connected externally
N3
N4
N6
MB4
N1
N1
N2
D1
R1
R2
Q1
Q2
Q3
MW1
MB1
MW2
MB2
MB3
Instananeous
Time delay
One lock and one key
Two lock and one key
Three lock and two key
Steel lock interlock
Link rod interlock (0,6m)
Cable type interlock
Pattern one of rod interlock
Pattern two of rod interlock
Pattern three of rod interlock
1600AF L
・M・H Controller
1600AF P Controller
2000AF
2500AF
4000AF
6300AF
Electrical mechanism for the indication of draw out socket's position
Separator plate between phases B3
B4
RFS
3P
4P
Electrical module for indication of ready-for-switching-on
"Button" Locking device
Counter
Communication function choice of accessories
DC power supply module
AC power supply module
Automatic transfer switch (ATS)
(included automatic controller, connector and 1.8m cable)
PD2
PD3
PA1
PA2
AS1
AS2
L
CM
S1
S2
S3
S4
PD1
AS3
Components of draw-out socket communication module
Ready-for-switching-on signal
Under-voltage signal
Fault-trip signal
24VDC
110VDC
220VDC
230VAC
400VAC
R type
S type
F type
Air Circuit Breakers
BT2 series
Specifications
Specifications
Frame size 1600A
Basic type
No. of poles
Rated current (A)
BT2-1600
3 4
200, 400, 630, 800,
1000, 1250, 1600
100% In Rated current of the neutral pole
(IN)
Rated insulation voltage (Ui) 1000
Rated operational volage (Ue) 690
Rated ultimate short-circuit 690VAC *
1
40 breaking capacity (Icu kA, sym)
Rated service short-circuit breaking capacity (Ics kA,
400VAC 50
690VAC *
1
25
400VAC 50 sym)
Rated making current
(kA, peak)
Rated short time withstand current (Icw) (kA, rms)
690VAC *
1
84
400VAC 105
690VAC *
1
25 (0.5s)
400VAC 42 (0.5s)
Rated impulse withstand voltage
(Uimp) (kV)
12
Installations
Fixed P
Draw-out X
Main circuit terminal connection
Fixed Horizontal
Vertical
Dimensions
Draw-out Horizontal
Vertical
Fixed W
H
D
Draw-out W
H
D
254
320
197
248
351.5
297
324
320
197
318
351.5
297
Note: *
1
Cannot be used for an IT distribution system.
Available
1000
690
50
80
50
80
362
395
290
347
438
390
2000A
BT2-2000
3 4
630, 800, 1000,
1250, 1600, 2000
100% In
105
176
40 (1s)
60 (1s)
12
457
395
290
442
438
390
–
362
395
290
347
438
390
2500A
BT2-2500
3 4
1250, 1600, 2000,
2500
100% In
4000A
BT2-4000
3 4
2000, 2500, 2900,
3200, 3600, 4000
100% In
1000
690
50
85
50
85
105
187
50 (1s)
65 (1s)
12
1000
690
75
100
75
100
165
220
75 (1s)
85 (1s)
12
1000
690
85
120
85
120
6300A
BT2-6300
3 4
4000, 5000, 6300
100% In
187
264
85 (1s)
100 (1s)
12
–
457
395
290
442
438
390
414
395
290
401
438
395
527
395
290
514
438
395
782
395
290
767
475.5
395
1008
395
290
993
475.5
395
7
Air Circuit Breakers
BT2 series
Appearance
Appearance
• Fixed • Draw-out
6
7
10
11
8
9
12
<Common>
6: Terminals of sencondary circuit (fixed)
7: Off lock mechanism
9: Inteligent controller (OCR)
10: OFF button
11: Indications of "ON" and "OFF"
8: Release indication and resetting button
12: Indication of ready-for-switching-on ("OK")
1: Name plate
2: Indications of energy-storage and energy-release
3: ON button
4: Manual energy-storage handle
5: Brand
• Draw-out cradle
The cradle has the back plate for isolating the copper bar of the main circuit, which take the role of safety protection when the ACB is drawn out.
6
5
4
3
2
1
11
12
13
14
7
8
9
10
17
16
15
<For Draw-out>
13: "Unlock button" of the three positions
("Separated", "test" and "connected") *1,2
14: Safety padlock mechanism
15: Racking shaft operating hole
16: Racking shaft storage hole
17: Indications of the three position
("Separated", "test" and "connected")
Note: *
1
"Separated": Indicates that main circuit and secondary circuit are both in isolation."Test": Indicates that main circuit is in isolation and secondary circuit is in connection."Connected": Indicates that main circuit and
*
2 secondary circuit are both in connection.
The ACB can be automatically locked (racking shaft can not be turned at the point) when its main part is at the position of "separated","test" or "connected" by turning the racking shaft, and can be unlocked by pushing "unlock button" to the left side.
5
4
3
2
1
21
22
23
20
19
18
24
18: Installation hole
19: Safety back plate
20: Wiring terminals of secondary circuit
21: Side plate
22: Copper bar of the main cirucit
23: Draw-out socket
24: Earthing point at draw-out socket
8
Air Circuit Breakers
BT2 series
Intelligent controller
Intelligent controller (OCR)
Selecting OCR's, it can be classified into six types
Type L25
Option
M25
Standard
M26
Option
Overcurrent protection
(Long-time, Short-time, insantaneous)
Ground-fault protection
Load monitor function
Indication
Power, electric energy, power-factor, frequency indication
Alarm function (pre-trip alarm, overload alarm)
Test function
Contact Welding indication
Self-diagnosis function
MCR funciton
Fault-memory funciton
Current-imbalance indication
Thermo-analogue function
Harmonic analysis function
ZSI function
Communication function
–
–
–
–
–
–
–
–
–
–
Light Columnar LED
–
– –
–
–
–
LED
–
–
–
–
Note: Reprensents fundamental functions, Represents selective functions, – Represent no such functions
H26
Option
LED
–
–
–
P25
Option
–
LCD
–
–
P26
Option
LCD
–
–
Function
Over-current protection
• The over-current protection is composed of phase and neutral line protection (Four pole breaker and three pole breaker with current transformer linking externally to neutral N) from over-current.
• The parameters of current and time of phase line over-current protection can be set by the company in terms of the requirements of users (can be set by customers themselves); the parameters of current and time of neutral line over-current protection will be set according to the setting of the phase line, all these mainly divided into the following two situations:
Three pole breaker with the neutral connected eaternally
• To type L25, M26, H26 intelligent controller, when ordering the goods the neutral line setting current customers should have to confirm the protecting data, it has two type of 50%In and 100%In.
• To type P25, P26 intelligent controller, the customers can setup into four types from menu:turn off, 50%In, 100%In, 200%In. When
200%In neutral line protecting (if it has a high triple frequency harmonic), the neutral line cross section should be double leg of a circuit cross section in the electrical power distribution system. But to
BT2-6300 three circuit breaker, there is no neutral line protecting.
Four pole breaker
• To type L25, M25, M26, H26 intelligent controller, the customers should have to confirm the protecting data, it has two types of 50%In and 100%In.
• To type P25, P26 intelligent controller, the customers can setup into three types from menu:turn off, 50%In, 100%In.
Overload protection
• Inverse long-time delay overload protection, and its setting current Ir1 can be adjusted.
• The delay time t1 of overload long-time delay can be adjusted.
• The long-time delay overload characteristic of the type P25, P26, the curves can be adjusted. There have common type (I2t), uncommon inverse-time type (It), high-voltage fuse concert type (I4t) can be adjusted, which can matching higher-up and lower-lever's overload protection'needs. The long-time delay overload characteristic ofthe type L25, M25, M26, H26, its running according to the common type (I2t) curves,current Ir1, time t1 can beadjusted.
Short-time short circuit protection (can be OFF)
• Inverse short-time delay short circuit protection (I2t ON), and its setting current Ir2 can be adjusted.
• Definite short-time delay short circuit protection (I2t OFF), and its setting current Ir2 can be adjusted.
• The delay time t2 of short circuit short-time delay can be adjusted.
Instantaneous short circuit protection
• The setting current Ir3 of instantaneous short circuit (can be OFF) can be adjusted.
t
Delay time of overload long-time delay adjustable
Definite short-time delay short circuit(I
2 t OFF)
Setting current Ir
1
of overload long-time delay
Setting delay time t
1
of overload long-time delay
Setting current Ir
2
of short-time circuit short-time delay
Inverse short-time delay short circuit (I
2 t ON)
Setting delay time t
2
of short circuit short-time delay
Setting current Ir
3
of instantaneous short circuit
Long-time delay, short-time delay, instantaneous protection
I
9
Air Circuit Breakers
BT2 series
Intelligent controller
Ground-fault protection
• Definite ground-fault protection, and its setting current Ir4 can be adjusted
• Delay time t4 can be adjusted
• Alarm but not break after being off t
Setting current Ir
4
of ground-fault
Setting current t
4
of ground-fault
I
• TN-C, TN-C-S, or TN-S, power distribution system
without additional current transformer of neutral
Transformer
BT2 circuit breaker with three poles
Current transformer
L
1
L
2
L
3
PEN
Intelligent controller
• TN-S, power distribution system, 4 poles
Transformer
BT2 circut breaking with four poles
Current transformer
L
L
L
2
1
3
N
PE
• TN-S, power distribution system, 3 poles
Transformer
BT2 circut breaking with three poles
Current transformer
L
1
L
2
L
N
3
Intelligent controller
Intelligent controller
For exmple : TN-C system
PE
Load monitoring function
• To monitor the down stream load so as to ensure power supply of main system
• There are two patterns of load monitoring from which users t can choose one. The setting value of load-monitoring current are I
LC1
and I
LC2
, normally I
LC1
is larger than or equal to I
• Inverse characteristic of load-monitoring is the same of
LC2 inverse long-time delay overload characteristic.
t t
Setting current I
LC2
of load monitoring (Limiting load)
Setting current I
LC1
of load monitoring (Limitiong load)
Setting delay time t c1
of load monitoring
I
Setting delay time t c2
of load monitoring
I
Acting characteristic of two kinds of ultimate setting load
Setting current I
LC2
of load monitoring (reload)
Setting current I
LC1
of load monitoring (Limiting load)
For example: TN-S system
N line current transformer connected externally
For example: TN-S system
• Pattern 1: Two circuits of down stream load can be controlled.
When the operating current of the main circuit rises over the setting value of I
LC1
and I
LC2 after time durations of t
C1
, contact signal will be sent out
and t
C2
repectively. Then this two circuits with monitored load are broken off by receiving the instructions from the intelligent controller.
• Pattern 2: Only one circuit with down stream load can be controlled. When the operating current of the main circuit rises over the setting value of I out after time duration of t
LC1
, contact signal will be sent
C1
, and this circuit is broken off by receiving the instructions from the intelligent controller. If the operating current of the main circuit decreases lower than the setting value of I
LC2
after this circuit is broken off, the signal will be sent out again after time duration of t supply of this circuit is restored.
C2
for the open loading circuit to be closed (reloaded) and so the power
• Load monitoring signals"(1)" and "(2)" corresponding to I
LC1 and I
LC2
respectively are transmitted into contact signals via the wiring terminals 13, 14 and 15, 16 of the secondary circuit. There will be LED indication at the time when signals are transmitted. (The load monitoring signals from the intelligent controller will be cut off in half second after the signal of contact closing is transmitted, and the capacity of contact is AC230V 5A) t
Setting delay time t c2
of load monitoring
10
Setting delay time t c2
of load monitoring (definite)
I
Acting characteristic of ultimate setting value of load and reload
I
Air Circuit Breakers
BT2 series
Intelligent controller
Indication and measurement function
• For L25, M25, M26 and H26
Item
Current
Voltage
Type of OCR's
L25
M25
M26, H26
M25, M26 as optional
H26 as standard
• For P25 and P26
Item
Current
Display
LCD
Display Content
Light columnar Indication I
1
, I
2
, I
3
, I
N
LED I
1
, I
2
, I
3
, I
N
, I max
I
1
, I
2
, I
3
, I
N
, I
G
, I max
LED U
12
, U
23
, U
31
, U min
Voltage
Power
Power-factor
Electric energy
Frequency
Fundamental current
Fundamental line voltage
Fundamental phase voltage
Fundamental power
Harmonic ratio
Total harmonic distortion
(THD)
Content
I
1
, I
2
, I3, I
N
I
G
Line Voltage: U
12
, U
23
, U
31
Phase Voltage: U
1N
, U
2N
, U
Three-phase active power
3N
Three-phase reactive power
Three-phase apparent power
Power-factor
Three-phase active electric energy
Three-phase reactive electric energy
Three-phase apparent electric energy f
I
1-1
, I
2-1
, I
3-1
, I
N-1
U
12-1
, U
23-1
, U
31-1
U
1N-1
, U
2N-1
, U
P1
3N-1
Q1
S1
Current
Voltage
Current
Voltage
Indication and measurement range
(0.1In to 2In) A
Accuracy
± 5%
30V to 690V ± 3%
Indication and measurement range
(0.1In to 2In) A
0.1In to 2000A
30V to 690V
-120MW to +120MW
-120Mvar to +120Mvar
-120MVA to +120MVA
-1.00 to +1,00
-10
10
GWh to +10
10
GWh
-10
10
Gvarh to +10
10
Gvarh
-10
10
GVAh to +10
10
GVAh
45 to 65Hz
(0.1In to 2In) A
30V to 690V
-120MW to +120MW
-120Mvar to +120Mvar
-120MVA to +120MVA
0 to 1000%
Accuracy
± 1.5%
± 2.5%
± 0.5%
± 2.5%
± 2.5%
± 2.5%
± 0.1Hz
± 1.5%
± 0.5%
± 2.5%
± 5%
Alarm and fault functions
Over-current alarm
Type L25
Type M25
Type M26, H26
Type P25, P26
Fault indication Type L25
Type M25
Type M26, H26
Type P25, P26
Corresponding LED on the panel will be "ON"
Corresponding LED on the panel will be "ON"
Indication of fault phase, current and time
Type M25,
M26, H26
Indication
Type P25, P26 Indication
Alarm and release indication lights will be on after the circuit breaker's being overloaded or released (yellow or red)
After the circuit breaker's being released by long-time delay overload, short-time delay short circuit and instantaneous short circuit, indication lights of corresponding alarm will be on.
After the circuit breaker's being released by long-time delay overload, short-time delay short circuit, instantaneous short circuit and ground-fault, indication lights of corresponding alarm will be on.
After the circuit breaker's being released by long-time delay overload, short-time delay short circuit and instantaneous short circuit, indication lights of corresponding alarm will be on.
After the circuit breaker's being released by long-time delay overload, short-time short circuit and instantaneous short circuit, indication lights of corresponding fault type will be on.
After the circuit breaker's being released by long-time delay overload, short-time short circuit and instantaneous short circuit, indication lights of corresponding fault type will be on.
After the circuit breaker's being released by long-time delay overload, short-time delay short circuit, instantaneous short circuit, instantaneous short circuit and ground-fault, indication lights of corresponding fault type will be on.
After the circuit breaker's being released by long-time delay overload, short-time delay short circuit and instantaneous short circuit, indication lights of corresponding alarm will be on.
Indication of faulty phase, breaking value of fault current and breaking time
It can indicate the latest ten times fault categories and occurrence time, faulty phase, breaking value of fault current and breaking time.
11
Air Circuit Breakers
BT2 series
Intelligent controller
Test functions
Panel button Type L25, M25, M26,
H26, P25, P26
Type M25, M26, H26,
P25, P26
Release
Non-release
Inspeciton of T-I characteristic of the OCR and the conditions of operating mechanism
Inspeciton of T-I characteristic of the OCR
• Contact wearing indication (for M25, M26, H26, P25 and P26)
The intelligent controller has the function of contact wearing indication. Accordingly, the percentage of the equivalent to wearing times of main contact to electrical life-span times of the circuit breaker can be indicated by pushing the button of
"wearing indication".
• Self-diagnosis function (for M25, M26, H26, P25 and P26)
When the microprocessor of the intelligent controller breaks down or the ambient temperature of the microprocessor rises over 80°C±5, alarm signals can be sent out immediately.
• MCR function
When the circuit breaker is on or the controller is initially electrified, the circuit breaker would trip instantly if short-time short circuit fault occurred.
• Fault-memory function (for M25, M26, H26, P25 and P26)
The types and phases of fault, value of faulty current and breaking time would be indicated on the intelligent controller if the circuit breaker broke off as a result of faults.
• Current disequilibrium display (selective function for P25 and P26)
The intelligent controller can sent out and display, when the three phases current disequilibrium level reached the setting value (20%-80%).
Note: the three phases current disequilibrium=
Imax-Imin
Imax
×100%
• Harmonic analysis function (for P25 and P26)
P25 or P26 intelligent controller with harmonic analysis function can measure fundamental current, fundamental line voltage, fundamental phase voltage, fundamental power, odd harmonic current ratio (HRIh) from the third to thirty-first, harmonic voltage ratio (HRUh), total harmonic distortion of current (THDi, thdi) and total harmonic distortion of voltage
(THDu, thdu).
• Harmonic ratio (HR)
The ratio of RMS of hth harmonic component in the periodical alternating quantum to RMS of fundamental component (express by percent).
• Harmonic current ratio of hth expresses HRI h
.
HRI h
= I h
I
1-1
×100%
Note: I h
-harmonic current of hth of phase A (RMS)
• Harmonic voltage ratio of hth expresses HRU h
.
U h
HRU h
=
U
12-1
×100%
Note: Uh -harmonic line voltage of hth between phase A and B.
• Total harmonic distortion (THD)
• The ratio of harmonic content in the periodical alternating quantum to RMS of fundamental component
(THD)(express by percent).
THD i
=
I
1-1
I
2 h
×100%
THD u
=
U
2 h
U
12-1
×100%
Note: I
U h h
-harmonic current of hth of phase A (RMS)
-harmonic line voltage of hth between phase A and B (RMS)
• The ratio of harmonic component in the periodical alternating quantum to RMS of periodical alternating quantum(thd) (express by percent).
thd i
=
I
1-1
I
2 h
×100%
thd u
=
U
2 h
U
12-1
×100%
Ntoe: I h
-harmonic current of hth of phase A (RMS)
U h
-harmonic line voltage of hth between phase A and B (RMS)
12
Air Circuit Breakers
BT2 series
Intelligent controller
Zone selective interlock
Zone selective interlock (ZSI function) (for M25, M26, H26, P25 and P26, optional)
Busbar
Zone1
Control line
Control line
Busbar
Zone2
Control line
Control line
Busbar
Zone3
Circuit breaker at higher level
21
22
23
24
21
22
23
24
21
22
23
24
Fault
Down stream circuit breaker
Release delay t
2
21
22
23
24
Release delay t
2
Note: 21,22,23,24 serve as the wiring teminals of secondary circuit.
When pieces of circuit breakers are linked together up and down, zone selective interlock (ZSI) can ensure fully-selective protection of circuit breakers at higher or lower level so as to reduce the range of action by fault and the breaking time of circuit breakers. This function serves for short-time delay short circuit (I
2 t OFF) and ground-fault protection of circuit breakers.
As the sketch shown above, control lines can interlock with pieces of circuit breakers.
After detecting the fault, the intelligent controller (zone 2) will send out a signal to circuit breakers (zone1) at higher level and check whether the signal of circuit breakers (zone 3) at lower level arrives. If circuit breakers at lower level send out a signal, the circuit breaker will be on at the time duration of release delay; if circuit breakers at lower level don't send out a signal, the circuit breaker will break off instantly no matter whether the release has the protection of delay.
Note: The end 23 and 24 should be shortcircuited.
13
Air Circuit Breakers
BT2 series
Communication
Communicative
To achieve the function of "four kinds of remote operation" at long distance by communication interface of the circuit breaker, namely, remote control, remote communication, remote adjustment and remote detection.
• Communication protocol : The application of Modbus-RTU mode
• Communication interface
• Standard interface: RS-485.
• Baud rate: 19200bps (in favour of 1200, 2400, 4800, 9600, 38400bps)
• Communication address:1-119.
• Byte format: First bit as start bit, eighth bit as data bit, second bit as stop bit, even check (in favour of non-check, odd check .)
• Network characteristic
• Twisted-pair shielded cables serve as communication lines.
• One line can link up 32 pieces of communicative circuit breakers at the same time (16 pieces of circuit breakers with components of draw-out socket communication module).
• Wiring distance is 1200m at maximum but the distance of communication can be extended by equipping with repeaters additionally.
Communication cable
Blue
White
One group
Shielding layer
Standard twisted-pair shielded cable
Note: please use the type of communication cable with the shielding layer and approach to circuits with strong electricity should be avoided as far as possible when wiring in the cabinet.
Communication data
• Real-time current, voltage fundamental current, fundamental voltage, power, power factor, electric energy, harmonic current or voltage ratio and total distortion of current or voltage.
• State data of circuit breakers such as alarm, fault, energy-storage, undervoltage, ready-for-switching-on, and the positions of switching-on and switching-off etc.
• The position of main body of the circuit breaker (components of communication module of draw-out socket for BT2 need to be purchased).
• The fetching and modification of the setting values of circuit breakers.
• Recorded data of fault last time.
• Outline data such as serial numbers and the type etc of circuit breakers.
• Long-distance operation if switching-on and switching-off.
• Circuit breakers can be switched on or off in the long-distance.
• Wiring terminals for communication.
Colour
Blue
White
Shielding layer
Signal
DATA+
DATA−
GND
Funation
Receive/transmit data
Receive/transmit data
Grounding
As the above diagram shows, a group of twisted-pair lines in the standard communication cable is employed as the communication line of 485 and the sheilding layer is grounded.
The actual practice should be possibly different such as the application of the colour of the twisted-pair line. Users could define the ways of cable's usage by themselves but the definition of the signal of each line in the cable should be made clear in advance.
8 1 0 1 2 1 4
7 9 1 1 1 3
Terminal
8
10
12
Signal
DATA+(A+)
DATA-(B-)
SH
Function
Receive/transmit data
Receive/transmit data
In connection with shielded layer of communication line
14
Linking diagram of communication system
Monitoring computer
RS232
RS485
RS232/RS485
Converter
DATA+
DATA−
Draw-out socket communication module
Modbus
BT2
BT2
Note: As the accessory of selective purchase, the draw-out socket communication module should be selected into use when users need read the location of main body in the long distance by the choice of draw-out circuit breakers.
BT2
BT2
Air Circuit Breakers
BT2 series
Communication
15
Air Circuit Breakers
BT2 series
Characteristic curve
Characteristic curve of general l
2
• BT2-1600~BT2-6300 t
T/I (time / current) curve of type L25 intelligent controllers (OCR)
10000
I r1
1000 t
1
100 long-time delay curve
Illustrational curve
The range of long-time delay
I r1 t
1
=(0.65~1)In
=15s~480s t
I
The range of short-time delay
2 r2
=(1.5~10)I
=0.1s~0.4s
r2
+OFF
I
Instantaneous range r3
=(3~15)I r1
+OFF
I
2
T ON
I r2 t (s)
10
0.02
0.01
1
0.4
0.3
0.2
0.1
Short-time delay curve
I 2 T OFF
0.4
1
Instantaneous curve
1.5
3
Ir1
Instantaneous range
10 15 t
2
16
Air Circuit Breakers
BT2 series
Characteristic curve
• T/I (time / current) curve of type M25, M26, H26, P25 and P26 intelligent controllers (OCR)
10000
Illustrational curve
I r1
I
The range of long-time delay r1
=(0.4~I)In t
1
=10s~120s
1000
The range of short-time delay
I r2 t
2
=(0.4~15)In+OFF
=0.1s~0.4s
t
1
Instantaneous range
I r3
= 1.6kA~35kA+OFF BT2-1600
2kA~50kA+OFF BT2-2000
2.5kA~50kA+OFF BT2-2500
4kA~65kA+OFF BT2-4000
6.3kA~80kA+OFF BT2-6300
100 long-time delay curve t (s)
10
I 2 T ON
I r2
Short-time delay curve
I
2
T OFF t
2
0.02
0.01
1
0.4
0.3
0.2
0.1
I r1
Instantaneous curve
0.4
1 1.6
Instantaneous range
10 15 kA
80
17
Air Circuit Breakers
BT2 series
Characteristic curve
Characteristic curve of inverse time delay special It
• T/I (time / current) curve of type 25 and 26 intelligent controllers (OCR)
10000
I r1
1000
100 t
1
Illustrational curve
The range of long-time delay
I r1 t
1
=(0.4~1)In
=10s~120s t
I
The range of short-time delay
2 r2
=(0.4~15)In+OFF
=0.1s~0.4s
Instantaneous range
I r3
= 1.6kA~35kA+OFF BT2-1600
2kA~50kA+OFF BT2-2000
2.5kA~50kA+OFF BT2-25
4kA~65kA+OFF BT2-4000
6.3kA~80kA+OFF BT2-6300 long-time delay curve
I
2
T ON
I r2 t (s)
10
Short-time delay curve
I
2
T OFF t
2
0.02
0.01
1
0.4
0.3
0.2
0.1
Instantaneous curve
0.4
1
I r1
1.6
Instantaneous range
10
15 kA
80
18
Air Circuit Breakers
BT2 series
Characteristic curve
Characteristic curve of high-voltage fuse I
4 t
• T/I (time / current) curve of type 25 and 26 intelligent controllers (OCR)
100000
10000
1000
100
I
2
T ON
I r1 t
1
Illustrational curve
The range of long-time delay
I r1 t
1
=(0.4~1)In
=60s~1440s
I
The range of short-time delay r2
=(0.4~15)In+OFF t
2
=0.1s~0.4s
Instantaneous range
I r3
= 1.6kA~35kA+OFF BT2-1600
2kA~50kA+OFF BT2-2000
2.5kA~50kA+OFF BT2-2500
4kA~65kA+OFF BT2-4000
6.3kA~80kA+OFF BT2-6300 long-time delay curve
I r2 t (s)
10
Short-time delay curve
1
0.4
0.3
0.2
0.1
I
2
T OFF t
2
0.01
0.001
I r1
Instantaneous curve
0.4
1
1.6
Instantaneous range
10 kA
15
80
19
Air Circuit Breakers
BT2 series
Characteristic curve
• T/I (time / current) curve of type M26, H26 and P26 intelligent controllers (OCR) for ground-fault protection
1000
100
Grounding current t
4
I r4
I
I
I r4
I r4 r4 r4
=(0.4~0.8)In(BT2-1600)
=(0.2~0.8)In(BT2-2000, BT2-2500)
=(0.2~0.6)In(BT2-4000)
=(0.2~0.5)In(BT2-6300)
=0.1s~0.4s four steps
Maximum 1000A (For BT2-1600)
Maximum 1200A (For BT2-2000, BT2-2500)
Maximum 1600A (For BT2-4000)
Maximum 2000A (For BT2-6300)
Maximum
10 t (s)
1
0.4
0.3
0.2
0.1
0.01
0.2
0.8
1
In
10 100
20
Air Circuit Breakers
BT2 series
Characteristic curve
• T/I (time / current) curve of type M25, M26, H26, P25 and P26 intelligent controllers (OCR) for load-monitoring pattern one.
10000 t
I
LC1
=(0.2~1)In
C1
=t
1
/2(t
1
=15, 30, 60, 120, 240, 480s)
I
LC2
I
LC2
=(0.2~1)In t
C2
I
LC2
=t
1
/4(t
1
≤I
LC1
=15, 30, 60, 120, 240, 480s)
1000
I
LC1
200
100 t
C2 t
C1 t (s)
10
1
0.1
0.2
0.8
1
In
10 100
21
Air Circuit Breakers
BT2 series
Characteristic curve
• T/I (time / current) curve of type M25, M26, H26, P25 and P26 intelligent controllers (OCR) for load-monitoring pattern two.
10000
I
LC1 t
C1
=(0.2~1)In
=t
1
/2(t
1
=15, 30, 60, 120, 240, 480s)
I
LC2
I
LC2
=(0.2~1)In t
C2
=60s
1000 t (s)
100
60
10 t
C2
I
LC1 t
C1
1
0.1
0.2
0.4
0.8
1
In
10 100
22
12.0 COMMON FAULT AND SOLUTION
No.
9
10
12.0 COMMON FAULT AND SOLUTION
● Communication cable
1. Check whether the communication doesn't connect well with cables connect well with wiring
Technical problems
9
● Communication cable doesn't connect well with
Inspection and solution
2. Check whether terminals A and B of the communication cable are inversely wired. If so, make the correction;
3. Check whether communication
Communication error for Type H26、
P25、P26 Intelligent controller
10 inversely wired
● Errors for the setting of
● Communication distance and wiring ways can't meet the requirements
● Errors for the setting of communication address intelligent controller displays
3. Check whether communication requirements; distance and wiring ways can meet the requirements;
4. Check whether the setting of
Air Circuit Breakers without conflict
BT2 series
Accessories
The screen on the intelligent around the controller
To reduce the ambient temperature controller displays
13.0 ACCESSORIES
“ERR9”
Accessories
Supplied accessories
13.1 NECESSARY ACCESSORIES
Following accessories are come with each ACB's as standard supplied.
• Shunt trip device
To break the ACB by remote control.
Rated voltage of control
○ Closing electro-magnet
○ Shunt Release
400VAC 230VAC 220VDC 110VDC power supply
1.3
1.3
2.4
For BT2-1600 Circuit Breaker For BT2 with frame current of 2000A and above
Operating voltage (V) (0.7 to 1.1) Us
Instantaneous current (A) 0.7
Breaking time (ms) No more than 30
▲ Switch the breaker off by remote control
▲ Features
13.0 ACCESSORIES
AC400 DC220
• Charge Coil
13.0 ACCESSORIES
After the ACB's ends up its energy storage, the closing electromagnet will make the energy storing spring to release its energy instantly, then to close the count ACB quickly.
Rated voltage of control power supply
▲ After the circuit breaker is charged, the closing electro-magnet will make the energy-charging
▲
400VAC 230VAC 220VDC 110VDC
Operational Voltage(V)
Operational Voltage(V)
○ Auxiliary Switch
AC400
Breaking Time(ms)
AC230
0.7
DC220
(0.7~1.1)Us
(0.85~1.1)Us
1.3
(0.7~1.1)Us
1.3
DC110
No more than 30
(0.85~1.1)Us
DC110
2.4
DC110
Operating voltage (V) (0.85 to 1.1) Us
Instantaneous current (A) 0.7
1.3
0.7
1.3
1.3
0.7
0.7
For BT2-1600 Circuit Breaker
1.3
1.3
2.4
2.4
1.3
2.4
Switching-on time (ms) No more than 70
Switching-on Time(ms)
• Drive unit
Rated voltage of control power supply
▲
After the circuit breaker is charged, the closing electro-magnet will make the energy-charging
For BT2-1600 Circuit Breaker
For BT2 with frame current of 2000A and above
ACB has the functions of drive energy storage and automatic energy-restoring.
▲ Features
The energy storage can also be done manually.
400VAC 230VAC 220VDC 110VDC
Rated Control supply voltage Us(V)
Rated Current
AC230
AC400
DC220
AC230 DC220 DC110
Operating voltage (V)
Power consumption
(0.85 to 1.1) Us
192VA
Operational Voltage(V)
Instantaneous Current(A)
Rated operational Voltage(V)
1.3
1.3
1.3
1.3
2.4
Conventional thermal current Ith(A)
Rated capacity
Energy storage time (s) No more than 5
13.0 ACCESSORIES
230 13.0 ACCESSORIES changeover contacts; for the special type of auxiliary switch, there are four
Power Consumption close contacts (NC), or 6 pieces of NO and 2 pieces of NC, or 2 pieces of
NO and 6 pieces of NC.
For BT2-1600 Circuit Breaker
AC
192VA
○ Safety padlock mechanism at the position of “separated”
For BT2 with frame current of 2000A and above
300VA
• Auxiliary Switches
Rated voltage (V)
○ Auxiliary Switch discharging.
AC 230
6
DC
400
220
110
DC
400
220
6
60W
▲ Features
Note: For the standard type of auxiliary switch, there are four pairs of changeover contacts; for the special type,
60W
Rated Control supply voltage Us(V)
Rated Control supply voltage Us(V) AC400 AC230
AC400 AC230 DC220 DC110
DC220 DC110 or 6 pieces of NO and 2 pieces of NC, or 2 pieces of NO and 6 pieces of NC.
Operational Voltage(V)
(0.85~1.1)Us
(0.85~1.1)Us
192W
For BT2 with frame current of 2000A and above
• Safety padlock mechanism at the position of “separated” discharging.
Rated Current
“of separated”, the locking stick can be locked with padlock after being pulled out so that the rocker of the circuit breaker can not be turned to the position of “test” or “connected”.
Padlock should be provided by users themselves.
AC
DC
400
220
Operational Voltage(V)
Power Consumption
·66·
AC230
Rated operational Voltage(V)
AC
AC230
230
400
220
Conventional thermal current Ith(A)
DC220
Rated capacity
300VA
60W
6
Power Consumption
300VA
(0.85~1.1)Us
192VA 192W or 6 pieces of NO and 2 pieces of NC, or 2 pieces of NO and 6 pieces of NC.
Charging Time(s)
192VA
60W
Safety padlock mechanism at the position of “separated” or 6 pieces of NO and 2 pieces of NC, or 2 pieces of NO and 6 pieces of NC.
○ Safety padlock mechanism at the position of “separated”
·66·
·66·
○ Safety padlock mechanism at the position of “separated”
can be locked with padlock after being pulled out so that the rocker of the circuit breaker can not be turned to the position of “test” or “connected”.
Safety padlock mechanism at the position of “separated”
▲ Padlock should be provided by users themselves.
Safety padlock mechanism at the position of “separated”
·67·
▲ When the draw-out circuit breaker is at the position of “separated”, the locking stick can be locked with padlock after being pulled out so that the rocker of the circuit breaker can not be turned to the position of “test” or “connected”.
▲ Padlock should be provided by users themselves.
·67·
▲ When the draw-out circuit breaker is at the position of “separated”, the locking stick can be locked with padlock after being pulled out so that the rocker of the circuit breaker can not be turned to the position of “test” or “connected”.
▲ Padlock should be provided by users themselves.
·67·
13.0 ACCESSORIES
13.2 SELECTIVE ACCESSORIES
○
13.0 ACCESSORIES
▲ When the power voltage of the intelligent controller is DC24V, AC230V or AC400V, it can be
Air Circuit Breakers
BT2 series
Accessories
○
Caution: Voltage input to secondary terminals 1 and 2 of BT2-1600 must be
DC24V.
▲ When the power voltage of the intelligent controller is DC24V, AC230V or AC400V, it can be cabinet.
Caution: Voltage input to secondary terminals 1 and 2 of BT2-1600 must be
DC24V.
▲ The module is stuck into the standard slideway of 35mm in width inside the switchgear cabinet.
Optional accessories
• Special power module
When the power voltage of BT2-1600 circuit breaker's intelligent control is AC230 or AC400V, it can be transformed into DC24 by this power module for power module for power supply of the OCR.
Note: The input of voltage to 1 and 2 terminals of the secondary circuit must be
DC24V.
This module is installed by getting stuck into the standard slideway with
35mm in width inside the switchgear cabinet.
• DC24V power module
○ DC Power Module intelligent control is DC24V, it can be transformed into DC24V by this power module for power supply of the OCR.
This module is installed by getting stuck into the standard slideway with 35mm in width inside the switchgear cabinet.
○ DC Power Module
• DC power supply module
When power supply of the secondary circuit is DC220V,
110V, it should be transformed into DC24V by this module for power supply of the OCR.
• Under-voltage release
The under-voltage release consists of release coil and control unit.
The under-voltage release works in two ways: operating instantaneously and operating in time delay.
13.0 ACCESSORIES consult with the manufacturer in the light of their order about special time-delay specifications as from 3s and above up to
9s. The time delay accurary is ±10%.
13.0 ACCESSORIES
▲ When the main body of the draw-out circuit breaker and the draw-out socket are at the with the time-delay module which is installed by getting stuck into the standard slideway with 35mm in width.The module input terminals connect with main circuit,the output terminals connect with terminal 31, 32 of the breaker.
▲ Features
Rated operational Voltage Ue(V)
○ Under-voltage release
For BT2-1600 Circuit Breaker
230
AC230V
0.5s
Fuju Electric FA
·68· delay release for BT2-1600
In connection with the main circuit
In connection with the terminals of
31 and 32 in the secondary circuit
Choice of communicate accessories
• Components of draw-out socket communication module
10
• Under-voltage signal
Rated Operational current Ie(A) module consists of the draw-out socket communication module outside of the circuit breaker and the draw-out
○Components of draw-out socket communication module inside of the draw-out socket to provide the status signals of
1.5
that the circuit breaker is tripping operation under-voltage.
• Fault-trip signal
You can achieve the information through the upper device that the circuit breaker is tripping operation because of over
▲ The components of draw-out socket communication
.module consists of the draw-out socket communication module outside of the circuit breaker and the draw-out socket out socket. The draw-out socket communication module, which can provide the function of reading the address of the circuit breaker and display the status indication of the socket communication parts are installed inside of the draw-out socket to provide the status signals of such three positions as is installed by getting stuck into the standard slideway the draw-out circuit breaker and the draw-out socket.The drawout socket communication module, which can provide the
BT2 with frame current of 2000A and above function of reading the address of the circuit breaker and display the status indication of the main body and three positions of the that the circuit breaker is ready for switching-on.
output
24
cabinet. The two parts of the draw-out socket communication module are connected with soft conducting lines.
▲ Features
▲
A; B to RS485 B; S to RS485 SH; - to cathode of DC24V; + to anode of DC24V; A
’ to 8, B
’ to 10,
S ’ to 12; for BT2-1600, T1 to 61, T2 to 62, T3 to 63, T4 to 64; for BT2-2000 or above, T1 to Y5,
T2 to Y6, T3 to Y7, T4 to Y8.
Reliable Switching-on Voltage(V) save the communication address and the address will be changed accordingly. If users want to save
AC400
(0.35~0.7)Us
(0.85~1.1)Us
≤0.35Us
12VA
AC230 light on when DC24V power supply is given to the module. The communication lamp will light on
·69·
·70·
Air Circuit Breakers
BT2 series
Accessories
Choice of mechanical interlock accessories
• Two sets of circuit breakers put horizontally and interlocked with steel cable or stacked and interlocked with connecting rods
(the style of interlock between two sets of circuit breakers with connecting rods and aperture dimensions of their bases see the counterpart of three sets of circuit breakers)
2m (max)
Wiring diagram
1QF 2QF
Possible operation pattern
1QF 2QF
0
0
1
0
1
0
Circuit breaker 1 Circuit breaker 2
• Three sets of circuit breakers stacked and interlocked with connecting rods or three sets of circuit breakers put horizontally and interlocked with steel cable (without BT2-
1600).
• Stacked and interlocked
Wiring diagram Possible operation Pattern
Pattern one: three sets of power supply can only close one sets of circuit breaker
Pattern two: two sets of common power supply plus one sets of standly power supply
Pattern three: two sets of power supply plus a piece of coupling busbar
25
Air Circuit Breakers
BT2 series
Accessories
•
Steel cable interlocked
13.0 ACCESSORIES interlock between two sets of circuit breakers. The maximal distance of two circuit breakers is 2m.
○ Under-voltage release
Current transformer with neutral line N connected externally
• This current transformer, which is used together with circuit breakers with three poles in the power distribution system
Wiring diagram
In connection with the main circuit
Pattern three:Two sets of power supply plus a input far from the installation point.
• Characteristics
Under-voltageTime-delayModule
AC230V output
Rated working voltage
Acting voltage
Ue (V) AC400
(V) (0.35~0.7) Us
Reliable switching voltage (V) (0.85~1.1) Us
Reliable switching resistant voltage (V)
≤0.35Us
0.5s
Power consumption 12VA
AC230
For BT2-1600 Circuit Breaker
OUTPUT
Delay Module of Under-voltage
In connection with the terminals of
31 and 32 in the secondary circuit voltage-lowering. Generally, delay time, which is selective by users , is 0.5s,
1s, 2s and 3s.
delay release for BT2-1600
BT2 with frame current of 2000A and above
▲ The under-voltage release operates in two ways: operate instantaneously and operate in time delay;
Electrical mechanism for the indication of draw-out
▲ There are four specifications of time delay for the under-voltage time delay release: 0.5s, 1s,
2s and 3s. Users should consult with the manufacturer in the light of their order about special timeand “connected” respectively, three electrical mechanisms delay specifications as from 3s and above up to 9s. The time delay accurary is ±10%;
▲ The delay module should be additionally equipped for the under-voltage delay release. The module input connects with the main circuit, and the output connects with the wiring terminals of 31 and 32 in the secondary circuit;
▲ If the voltage of power supply returns to 85% Us and above in half of the delay time, the
Ith (A) 10
AC230
Operational Voltage(V)
Power Consumption
Convertional thermal current
Rated working current
·69·
Ue (V) 230
Ith (A) 10
Ie (A) 1.5
≤0.35Us
12VA
26
附 件
附 件
ACCESSORIES
附 件
ACCESSORIES
“分闸”锁定装置
“Break” lock mechanism
“Break” lock mechanism
“Break” lock mechanism
“分闸”锁定装置
Air Circuit Breakers
按下置上,此时,断路器将不能闭合。
用户选装后,工厂提供锁和钥匙。
BT2 series
Accessories
一台断路器配一把锁和一把钥匙;
二台断路器配二把相同的锁和一把钥匙;
二台断路器配二把相同的锁和一把钥匙;
三台断路器配三把相同的锁和二把钥匙。
“Break” lock mechanism
按下置上,此时,断路器将不能闭合。 button of the circuit breaker on the pressed position. As a result, the circuit breaker can not be switched on.
After this lock mechanism was chosen by users, the manufacturer would provide lock and key.
One set of circuit breaker is outfitted with one lock and one key.
Two sets of circuit breakers are outfitted with two same locks and one key.
Three sets of circuit breakers are outfitted with three
• “Button”locking device
• When installed “Button”locking device, it can prevented
钮。
钮。 somebody from operating button of switching-on or switching
按钮锁定装置
• Padlock should be provided by users themselves.
挂锁用户自备。
挂锁用户自备。 same locks and two keys.
prevented somebody from operating button of switching-on or prevented somebody from operating button of switching-on or switching off by mistake.
钮。
然。
然。
Padlock should be provided by users themselves.
计数器
计数器累计断路器机械操作的次数,用户一目了
“Button” locking device
Counter
The counter can count mechanical operation times
计数器
相间隔板加强母排间绝缘,为断路器选择件,用
户需要时可配置。
Separator plate between phases
Separator plates between phases which strengthen insulation between bus-bars are optional and will be
相间隔板加强母排间绝缘,为断路器选择件,用
户需要时可配置。
45
Separator plate between phases
Separator plates between phases which strengthen insulation between bus-bars are optional and will be equipped as needed by users.
45
27
Air Circuit Breakers
BT2 series
Technical data
Power consumption and derating coefficient
• Power consumption (Environment temperature +40°C)
Power consumption is the overall consumption measured under with the circuit breaker is electrified with current below frame current.
Type
BT2-1600
BT2-2000
BT2-2500
BT2-4000
BT2-6300
Three poles/four poles (W)
Fixed type
152
203.6
356.8
648.96
1050.1
• Derating coefficient
The following table shows continual current-loading capacity of circuit breakers at different ambient environment temperature and under the conditions of the satisfaction of conventional heating in IEC60947-2
Ambient Environment temperature
Continual current-loading capacity
Inm=1600A
Inm=2000A
Inm=2500A
Inm=4000A
Inm=6300A
+40°C
1Inm
1Inm
1Inm
1Inm
1Inm
+45°C
0.99Inm
0.97Inm
0.96Inm
0.95Inm
0.93Inm
Derating for high-elevation
If elevation exceeds work environment 2000m, electric property of circuit breaker can correct according to following table: elevation (m)
Power-frequency withstand voltage (V)
Correction factor of operational current
Correction factor of short-circuit breaking capacity
1
1
2000
3500
3000
3150
0.93
0.83
Draw-out type
408
382.8
823.4
897.6
1200.2
+50°C
0.96Inm
0.91Inm
0.90Inm
0.89Inm
0.87Inm
+55°C
0.90Inm
0.87Inm
0.86Inm
0.85Inm
0.82Inm
+60°C
0.87Inm
0.82Inm
0.80Inm
0.78Inm
0.75Inm
4000
2500
0.88
0.71
5000
2000
0.82
0.63
28
Air Circuit Breakers
BT2 series
Technical data
Reference table of main circuit wiring copper bar for draw-out circuit breaders
Rated frame current (A)
1600
2000
2500
4000
6300
Rated current (A)
800
1000
1250
1600
2000
1250
1600
2000
200
400
630
800
1000
1250
1600
630
2500
2000
2500
2900
3200
3600
4000
4000
5000
6300
Specifications of copper bars
Number
1
1
2
2
3
4
2
2
2
2
3
2
3
3
2
3
4
3
4
3
4
4
5
5
6
8
Size (mm×mm)
20×5
50×5
40×5
50×5
40×5
40×5
50×10
50×5
60×5
60×5
60×5
60×10
60×10
60×5
60×10
60×10
60×10
100×5
100×5
100×10
100×10
100×10
100×10
100×10
100×10
100×10
The specifications of copper bars in the above table are introduced under which the circuit breakers by open installation are at maximum ambient environment temperature of 40°C and satisfy conventional heating in IEC60947-2.
29
Air Circuit Breakers
BT2 series
Dimensions and mounting
Dimensions and mounting, mm
BT2-1600 Air Circuit Breaker with three poles (draw-out type)
Current specifications
800A, 1000A, 1250A, 1600A
200A, 400A, 630A
L (mm)
15
10
Outside of the cabinet doo
Direction A
Base point
“Separated”position
Horizontal (back set)
Direction D
Outside of the cabinet door
Base point
“Separated”position
Vertical (back set)
Direction C
30
Air Circuit Breakers
BT2 series
Dimensions and mounting
Dimensions and mounting, mm
BT2-1600 Air Circuit Breaker with four poles (draw-out type)
Current specifications
800A, 1000A, 1250A, 1600A
200A, 400A, 630A
L (mm)
15
10
70
Direction A
70 70
16ø11
25
N pole
50
Outside of the cabinet door
51
A
46
Base point
72.5
77.5
102.5
297
“Separated”position
Horizontal (back set)
D
Direction D
2ø 6.5
2-6.5x8.5
Outside of the cabinet door
57
102
201
46
Base point
72.5
77.5
102.5
297
“Separated”position
Vertical (back set)
N pole
L
Direction C
70 70 70
60
C
51
15
16ø 11
31
Air Circuit Breakers
BT2 series
Dimensions and mounting
Dimensions and mounting, mm
BT2-1600 Air Circuit Breaker with three poles (fixed type)
Current specifications
800A, 1000A, 1250A, 1600A
200A, 400A, 630A
L (mm)
15
10
50
25
Direction A
12ø11
70 70
Outside of the cabinet door
32
A
4ø6.5
Base point
4ø6.5
100
192
197
38.5 50.6
Horizontal (back set)
244
10 234 10
4ø6.5
214
234
Breaker base
Aperture dimensions of the back plate at the time of hanging type installation
Outside of the cabinet door
32
C
15
Base point
4-
ø6.5
100
192
197
38.5 50.6
Vertical (back set)
Direction C
L
70 70
32
Air Circuit Breakers
BT2 series
Dimensions and mounting
Dimensions and mounting, mm
BT2-1600 Air Circuit Breaker with four poles (fixed type)
Current specifications
800A, 1000A, 1250A, 1600A
200A, 400A, 630A
L (mm)
15
10
25
50
Direction A
N pole
70 70 70
16ø11
Outside of the cabinet door
32
A
4ø6.5
Base point
4ø6.5
100
192
197
38.5 50.6
Horizontal (back set)
314
10 304 10
4ø6.5
Breaker base
284
304
Aperture dimensions of the back plate at the time of hanging type installation
Outside of the cabinet door
32
C
15
Base point
4ø6.5
100
192
197
38.5 50.6
Vertical (back set)
L
Direction C
N pole
70 70 70
33
Air Circuit Breakers
BT2 series
Dimensions and mounting
Dimensions and mounting, mm
BT2-2000 Air Circuit Breaker with three poles (draw-out type)
Current specifications
2000A
630A, 800A, 1000A,
1250A, 1600A
L (mm)
20
15
H (mm)
20
15
A (mm)
30
25
Outside of the cabinet door
61
A
Direction A
95 95
24ø 11
30 70
10
47
Base point
97
102
175
390
“Separated”position
Horizontal (back set)
D
41 265 41
Direction D
2ø 14
11x17
ø 11
Outside of the cabinet door
15
60
C
15
Base point
24-
47
10
97
102
175
390
“Separated”position
Vertical (back set)
ø
11
66
Direction C
95 95
60
30
10
34
Air Circuit Breakers
BT2 series
Dimensions and mounting
Dimensions and mounting, mm
BT2-2000 Air Circuit Breaker with four poles (draw-out type)
Current specifications
2000A
630A, 800A, 1000A,
1250A, 1600A
L (mm)
20
15
H (mm)
20
15
A (mm)
30
25
Outside of the cabinet door
61
A
95
Direction A
95 95
32-
ø11
N pole
30 70
Base point
47
10
97
102
175
390
“Separated”position
Horizontal (back set)
D
Direction D
2ø14
11 x 17
ø11
41 360 41
Outside of the cabinet door
30
60
C
15
Base point
47
10
97
102
175
390
“Separated”position
Vertical (back set)
32ø11
66
95
Direction C
95 95
N pole
60
30
10
35
Air Circuit Breakers
BT2 series
Dimensions and mounting
Dimensions and mounting, mm
BT2-2000 Air Circuit Breaker with three poles (fixed type)
Current specifications L (mm) A (mm) W (mm) B (mm)
2000A 20 269 20 13
630A, 800A, 1000A,
1250A, 1600A
15 264 15 3
Outside of the cabinet door
61
A
30
Direction A
95 95
24ø11
60
Base point
150
285
290
Horizontal (back set)
4ø12
69.5
11 340
Base point
11
Direction C
95 95
60
30
10
Outside of the cabinet door
C
60
Base point
24-
150
285
Vertical (back set)
69.5
15
94
30
ø11
36
Air Circuit Breakers
BT2 series
Dimensions and mounting
Dimensions and mounting, mm
BT2-2000 Air Circuit Breaker with four poles (fixed type)
Current specifications L (mm) A (mm) W (mm) B (mm)
2000A 20 269 20 13
630A, 800A, 1000A,
1250A, 1600A
15 264 15 3
Outside of the cabinet door
61
A
95
Direction A
95 95
32-
ø
11
N pole 30 60
Base point
4ø 12
150
285
290
Horizontal (back set)
69.5
11 435
Base point
11
95
Direction C
95 95
N pole 60
30
10
Outside of the cabinet door
60
C
Base point
32-
150
285
Horizontal (back set)
15
69.5
94
30
ø 11
37
Air Circuit Breakers
BT2 series
Dimensions and mounting
Dimensions and mounting, mm
BT2-2500 Air Circuit Breaker with three poles (draw-out type)
Current specifications
2000A, 2500A
1250A, 1600A
L (mm)
20
15
Outside of the cabinet door
62
A
10
47
Base point
97
102
175
390
“Separated”position
Horizontal (back set)
D
Direction A
95 95
24ø11
30 70
41 265 41
Direction D
2ø14
Outside of the cabinet door
C
62
24ø11
11x17
ø11
Base point
47
10
97
102
175
390
“Separated”position
Vertical (back set)
Direction C
95 95
L
38
Air Circuit Breakers
BT2 series
Dimensions and mounting
Dimensions and mounting, mm
BT2-2500 Air Circuit Breaker with four poles (draw-out type)
Current specifications
2000A, 2500A
1250A, 1600A
L (mm)
20
15
Outside of the cabinet door
62
A
95
Direction A
95 95
32ø11
30
N pole
70
Base point
47
10
97
102
175
390
“Separated”position
Horizontal (back set)
D
41 360 41
Direction D
2ø14
11x17
ø 11
Outside of the cabinet door
Base point
47
10
97
102
175
390
“Separated”position
Vertical (back set)
L
N pole
95
Direction C
95 95
C
62
32ø11
39
Air Circuit Breakers
BT2 series
Dimensions and mounting
Dimensions and mounting, mm
BT2-2500 Air Circuit Breaker with three poles (fixed type)
Current specifications
2000A, 2500A
1250A, 1600A
L (mm)
20
15
C (mm)
132
134.5
Outside of the cabinet door
61
61
A
A
30
30
95
95
95
60
60
24-
ø11
24ø11
Base
285
290
Horizontal (back set)
4ø12
4ø12
69.5
69.5
BT2-2500 Air Circuit Breaker with four poles (fixed type)
Current specifications
2000A, 2500A
1250A, 1600A
L (mm)
20
15
C (mm)
132
134.5
11
11
340
340
Base
point
11
11
95
Direction A
95 95
95 95 95
N pole
30
30
60
60
32ø11
32ø11
Outside of the cabinet door
61
61
A
A
Base point
150
285
150
4-
ø12
4-
ø12
69.5
69.5
11
11
435
435
Base
point
11
11
40
Air Circuit Breakers
BT2 series
Dimensions and mounting
Dimensions and mounting, mm
BT2-4000 Air Circuit Breaker with three poles (draw-out type)
Direction A
130 130
24ø17
50 100
Outside of the cabinet door
104
A
47
10
Base point
97 175
102
395
“Separated”position
Horizontal (back set)
B
Direction B
ø11
Outside of the cabinet door
37 327
37
C
104
50 25
11x17
2-
ø14
Base point
10
47
Base point
97
102
175
395
“Separated”position
Horizontal (back set)
24-
ø17
Direction C
113 113
10
30
41
Air Circuit Breakers
BT2 series
Dimensions and mounting
Dimensions and mounting, mm
BT2-4000 Air Circuit Breaker with four poles (draw-out type)
130
Direction A
130 130
32ø17
N pole
50 100
Outside of the cabinet door
104
A
Base point
47
10
97
102
175
395
“Separated”position
Horizontal (back set)
Direction B
ø11
B
Outside of the cabinet door
37 440 37
C
104
50
25
11x17
2ø14
Base point 10
47
Base point
97
102
175
395
“Separated”position
Vertical (back set)
32ø17
113
Direction C
113 113
N pole
10
30
42
Air Circuit Breakers
BT2 series
Dimensions and mounting
Dimensions and mounting, mm
BT2-4000 Air Circuit Breaker with three poles (fixed type)
Direction A
24-
ø13
Outside of the cabinet door
Base point
4ø12
Horizontal (back set)
BT2-4000 Air Circuit Breaker with four poles (fixed type)
Base point
N pole
Direction A
32ø13
Outside of the cabinet door
Base point
4ø12
Horizontal (back set)
Base point
43
Air Circuit Breakers
BT2 series
Dimensions and mounting
Dimensions and mounting, mm
BT2-6300 Air Circuit Breaker with three poles (draw-out type)
113 126.5
Direction A
130 126.5
113
48ø17
50
100
183
Outside of the cabinet door
104
A
Base point
10
47
77
82
258
395
“Separated”position
Horizontal (back set)
6-
ø11
Current specifications:
In=4000A, 5000A
Base point
693
767
113 126.5
Direction C
113 126.5
113
10
30
Outside of the cabinet door
48ø17
Base point
6ø11
10
47
77
82
258
395
“Separated”position
Vertically (back set)
Current specifications:
In=4000A, 5000A, 6300A
C
104
50
25
44
Air Circuit Breakers
BT2 series
Dimensions and mounting
Dimensions and mounting, mm
BT2-6300 Air Circuit Breaker with four poles (draw-out type)
113 130 113
Direction A
123 113 130 113
64ø 17
N pole
50
100
Outside of the cabinet door
104
A
239.5
Base point
6-
ø
11
10
47
77
82
258
395
“Separated”position
Horizontal (back set)
Current specifications:
In=4000A, 5000A
Base point
95
919
993
113 113 113
Direction C
140
113 113 113
N pole
10
30
Outside of the cabinet door
Base point
64ø 17
8ø 11
10
47
77
82
258
395
“Separated”position
Vertical (back set)
Current specifications:
In=4000A, 5000A, 6300A
C
104
50 25
45
Air Circuit Breakers
BT2 series
Dimensions and mounting
Dimensions and mounting, mm
BT2-6300 Air Circuit Breaker with three poles (fixed type)
205
205
50 55 50
Direction A
239.5
239.5
239.5
239.5
Outside of the cabinet door
134
134
A
A
Base point
4-
4-
ø12
ø12
150
150
290
290
Horizontal (back set)
69.5
69.5
BT2-6300 Air Circuit Breaker with four poles (fixed type)
11
11
205
205
50 55
50
50
N pole
226
226
Outside of the cabinet door
134
134
A
A
760
760
Direction A
253
253
226
226
Base point
11
11
Base point
4ø12
4-
ø12
150
150
290
290
Horizontal (back set)
69.5
69.5
11
11
986
986
Base point
11
11
46
Air Circuit Breakers
BT2 series
Dimensions and mounting
Door frame dimensions, mm
BT2-1600 door frame
BT2-1600 Air Circuit Breakers with three poles (draw-out)
The drawing of aperture dimensions for mounting cover of door frame
Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 227mm
BT2-1600 Air Circuit Breakers with four poles (draw-out)
The drawing of aperture dimensions for mounting front cover of door frame
Distance from the panel center of the Circuit Breaker to the right hinge of cabinet door should be at least 262mm
10-
ø
6
Breaker base
216
254
10-
ø
6
Breaker base
286
324
BT2-1600 Air Circuit Breakers with three poles (fixed type)
The drawing of aperture dimensions for mounting cover of door frame
Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 227mm
BT2-1600 Air Circuit Breakers with four poles (fixed type)
The drawing of aperture dimensions for mounting front cover of door frame
Distance from the panel center of the Circuit Breaker to the right hinge of cabinet door should be at least 262mm
Breaker base
216
254
10-
ø
6
10ø 6
Breaker base
286
324
47
Air Circuit Breakers
BT2 series
Dimensions and mounting
Door frame dimensions, mm
Aperture Dimension of BT2-2000 door frame
BT2-2000 Air Circuit Breakers with three poles (draw-out)
The drawing of Aperture Dimensions for mounting front cover of cabubet door
Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 256mm
BT2-2000 Air Circuit Breakers with four poles (draw-out)
The drawing of Aperture Dimensions for mounting front cover of cabinut door
Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 303.5mm
Breaker base
11-ø6
175
258
312
175
Breaker base
14-ø6
100
353
407
445
BT2-2000 Air Circuit Breakers with three poles (fixed)
The drawing of Aperture Dimensions for mounting front cover of cabunet door
Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 256mm
BT2-2000 Air Circuit Breakers with four poles (fixed)
The drawing of Aperture Dimensions for mounting front cover of cabinut door
Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 303.5mm
48
Breaker base
8-ø6
175
312
175
Breaker base
10-ø6
100
407
445
Air Circuit Breakers
BT2 series
Dimensions and mounting
Door frame dimensions, mm
Aperture Dimension of BT2-2500 door frame
BT2-2500 Air Circuit Breakers with three poles (draw-out)
The drawing of Aperture Dimensions for mounting cover of door frame
Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 256mm
BT2-2500 Air Circuit Breakers with four poles (draw-out)
The drawing of Aperture Dimensions for mounting cover of door frame
Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 303.5mm
Breaker base
11-ø6
175
258
312
175
Breaker base
14-ø6
100
353
407
445
BT2-2500 Air Circuit Breakers with three poles (fixed)
The drawing of Aperture Dimensions for mounting cover of door frame
Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 256mm
BT2-2500 Air Circuit Breakers with four poles (fixed)
The drawing of Aperture Dimensions for mounting cover of door frame
Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 303.5mm
Breaker base
8-ø6
175
312
175
Breaker base
10-ø6
100
407
445
49
Air Circuit Breakers
BT2 series
Dimensions and mounting
Door frame dimensions, mm
Aperture Dimension of BT2-4000 door frame
BT2-4000 Air Circuit Breakers with three poles (draw-out)
The drawing of Aperture Dimensions for mounting cover of door frame
Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 264mm
BT2-4000 Air Circuit Breakers with four poles (draw-out)
The drawing of Aperture Dimensions for mounting cover of door frame
Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 320.5mm
Breaker base
11-ø6
Breaker base
14-ø6
312
328
366
100
425
441
479
BT2-4000 Air Circuit Breakers with three poles (fixed)
The drawing of Aperture Dimensions for mounting cover of door frame
Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 264mm
BT2-4000 Air Circuit Breakers with four poles (fixed)
The drawing of Aperture Dimensions for mounting cover of door frame
Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 320.5mm
50
Breaker base
8-ø6
328
366
Breaker base
10-ø6
100
441
479
Air Circuit Breakers
BT2 series
Dimensions and mounting
Door frame dimensions, mm
Aperture Dimension of BT2-6300 door frame
BT2-6300 Air Circuit Breakers with three poles (draw-out)
The drawing of Aperture Dimensions for mounting cover of door frame
Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 264mm
BT2-6300 Air Circuit Breakers with four poles (draw-out)
The drawing of Aperture Dimensions for mounting cover of door frame
Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 320.5mm
Breaker base
11-ø6
312
328
366
Breaker base
14-ø6
100
425
441
479
BT2-6300 Air Circuit Breakers with three poles (fixed)
The drawing of Aperture Dimensions for mounting cover of door frame
Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 264mm
BT2-6300 Air Circuit Breakers with four poles (fixed)
The drawing of Aperture Dimensions for mounting cover of door frame
Distance from the panel center of the circuit breaker to the right hinge of cabinet door should be at least 320.5mm
Breaker base
8-ø6
328
366
Breaker base
10-ø6
100
441
479
51
Air Circuit Breakers
BT2 series
Dimensions and mounting
Mounting safety clearance
Draw-out breaker
Minimum distance between breaker with switchboard wall or live part.
d1 (note) (mm) d2 (mm)
Switchboard wall Live part
0 60
0 60
Fixed breaker
Minimum distance between breaker with switchboard wall or live part.
d1 (note) (mm) d2 (mm)
Switchboard wall Live part
0
0
60
60
Note:secondary circuit wiring must be considered for safety clearance.
52
Air Circuit Breakers
BT2 series
Dimensions and mounting
自动电源转换系统外形尺寸及安装尺寸
自动电源转换系统外形尺寸及安装尺寸
OUTLINE DIMENSIONS AND MOUNTING DIMENSIONS
OFAUTOMATIC POWER SUPPLYSWITCH SYSTEM
OFAUTOMATIC POWER SUPPLYSWITCH SYSTEM
转接器
转接器
The switching unit
Φ6.5
R、S型自动转换控制器
R、S型自动转换控制器
Type R and S Automatic transfer controller
R
U
N
N ormal s upply
C lose
O pen
O pen
Power genera ting
M alfuncti on
Power genera ting
Norm al supp ly
Stop
Auto matic
U
R
Stand by Pow er
Close
Open
Open
Malfu nction
1
2
0.5
4 8 16
1
0.5
24
32
64
32
64 Norm al
Sta nding
1
2
0.5
4 8 16
24
32
64
1
0.5
U =I
32
64
Stop
143
143
F型自动转换控制器
F型自动转换控制器
Type F automatic transfer controller
Under- voltage vol tage
Under- voltage vol tage
Norma l power supply
Under- voltage vol tage
Under- voltage vol tage
Under- voltage vol tage
Sta nding p ower su pply
Under- voltage vol tage
Switching unit
146
Norm al powe r supply
Standin g power supply
90
96
96
U
N
R
No rmal sup ply
Clo se
Op en
Op en
Autom a tic
N ormal supply
Stop
Autom a tic
Stop
U
U
R
1
2
1
0.5
0.5
2
1
0.5
4 8 16
24
32
4 8 16
32
64
24
32
U =I 120
64
32
18 0
18 0
120
64
32
240 300
360
480
600
360
480
600
O pen
M alfunctio n
1
2
1
0.5
0.5
2
1
0.5
U =0
4 8 16
32
64
24
32
N
64
8
4
1
U =1
96
120
8
16 32 64 180
4
1
120
180
U =I
2
0.5
4
2
0.5
8 16
3
32
64
32
64
120
240
U =0
1
2
0.5
2
4 8 16
4
1
0.5
24
32
24
32
64
Changshu Sw itchge ar Mfg. Co., Ltd. (Former Changshu S witchg ear Plant)
143
143
90
96
96
75
75
66.5
136
136
53
Air Circuit Breakers
BT2 series
Wiring diagram
断路器二次回路接线图
WIRING DIAGRAM OF SECONDARY CIRCUIT
Wiring diagram of secondary circuit
Tes t ind ication
Connec tion indication
54
76
Air Circuit Breakers
BT2 series
Wiring diagram
断路器二次回路接线图
WIRING DIAGRAM OF SECONDARY CIRCUIT
n tio ion ica art n n tion tio tio ica nec d ica t ind
Con in
Tes ind
Sep n tio on ica arti ind
Sep
77
55
Air Circuit Breakers
BT2 series
Wiring diagram
断路器二次回路接线图
WIRING DIAGRAM OF SECONDARY CIRCUIT
n tio n n tio tio ica nec ica t ind
Tes ind
Con t n tio ata
Tes
Sep n tio nec Con
56
78
Air Circuit Breakers
BT2 series
Wiring diagram
断路器二次回路接线图
WIRING DIAGRAM OF SECONDARY CIRCUIT
on n ati tio par dic n on ati tion tio ica nec dic st in
Te ind
Con in
Se n tio ion ica art ind
Sep
79
57
Air Circuit Breakers
BT2 series
Wiring diagram
自动电源转换系统电气线路图
1 2 3 4 5 6 7 8 9
10111213141516171819
58
80
自动电源转换系统电气线路图
Air Circuit Breakers
BT2 series
Wiring diagram
1 2 3 4 5 6 7 8 9
10111213141516171819
81
59
Air Circuit Breakers
BT2 series
Wiring diagram
自动电源转换系统电气线路图
1 2 3 4 5 6 7 8 9
1011121314151617 1819
60
82
自动电源转换系统电气线路图
Air Circuit Breakers
BT2 series
Wiring diagram
1 2 3 4 5 6 7 8 9
1011121314 1516 1718 19
83
61
Air Circuit Breakers
BT2 series
Ordering form
Ordering form
1. Users should make sure of their detailed acquaintance of the products’ technological materials and make order by the
2. The company would configure by“Factory's setting values of the intelligent release” if users had no requirements of
“ordering form”in terms of future applicable situations of the circuit breakers.
Ordering form
Ordering form
(Please fill numbers in or mark
√ in )
Customer name
Order quantity Date
Type BT2- / E Rated voltage AC400V AC690V
Use Standard Humid tropical (TH) Rated current
Connection Fixed Horizontal (Rear connection) Vertical (Rear connection)
In= A
Draw-out Horizontal (Rear connection) Vertical (Rear connection)
Type selection
Basic function
Type L25 Type M25 Type M26 Type H26 Type P26 Type P25
Current indication
LED current indication
LED current indication and communication function
LCD current indication and wattmeter function
Long-time delay overload protection Short-time delay short circuit protection Instantaneous short circuit protection
Selective function
Ir
1
t
1
Ir
2
t
2
Ir
3
Ground-fault protection Ir
4
Long-time delay overload protection
General inverse time delay (I 2 t)
t
4
Long-time delay overload protection
General inverse time delay (I
2 t)
Special inverse time delay (It)
High-voltage fuse type (I
4 t)
50%In 100%In
(Select setting current of N line)
Test function MCR function Thermo-analogue function Alarm and fault indication
Contact wearing indication Fault memory Self-diagnosis
Indication of voltage
OFF 50%In 100%In 200%In
(200% In for three-pole breaker + neutral line transformer BT2-6300 except)
Voltage of the intelligent controller
ZSI function Load-monitoring function: Pattern one Pattern two
Communication function
Harmonic meter Current-imbalace display
BT2-2000 and above
BT2-1600
AC230V AC400V
DC24V
Need be selectively equipped with DC24V power supply module
AC230V AC400V
Need be selectively equipped power supply module
DC220V DC110V
Need to use with DC power supply module
AC230V AC400V DC110V DC220V
AC230V AC400V DC110V DC220V
AC230V AC400V DC110V DC220V
Shunt release
Closing coil
Power-driven operation mechanism
Auxiliary switch
Under-voltage release
Lock in “OFF” mechanism
Standard pattern 4 changeover contacts
Special pattern
4NO + 4NC
6NO + 2NC
2NO + 6NC
AC230V AC400V
Under-voltage instantaneous release
One set of circuit breaker
Two sets of circuit breakers
Under-voltage time delay release 0.5s 1s 2s 3s
One lock and one key
Two locks and one key
Mechanical interlock
Three sets of circuit breakers
Two sets of circuit breakers
Cable type interlock
Three locks and two keys
Rod type interlock
Cable type interlock Pattern one of Rod type interlock Pattern two of Rod type interlock Pattern three of Rod type interlock
Connection of external CT for neutral Draw out position indication Interphase barrier
Ready to close indication
Communication accessories
Push button locking device
Components of draw-out socket communication module
Counter
Signal of ready-for-switching on Signal of under-voltage Signal of fault release
DC power supply module DC220V DC110V
Automatic transfer switch (ATS)
DC24V power supply module
Automatic transfer switch (ATS) R type S type F type
62
Air Circuit Breakers
BT2 series
Ordering notice
Ordering notice
Factory's setting values of intelligent controller
Overload long-time delay Setting values of current I r1
Setting values of delay time t
1
Overload long-time delay of P25 and P26
Short circuit short-time delay Setting values of current I r2
I
In
480s
2
6I t r1
Setting values of delay time
0.2s
t
2
Setting values of short circuit instantaneous current
I r3
Ground-fault
(Not for L25, M25, P25)
Setting values of current
Setting values of delay time
I t r4
4
15In (for In
≤ 1000A)
12In (for In = 1250A, 1600A)
10In (for In
≥ 2000A)
BT2-1600 BT2-2000
BT2-2500
0.8In or 1000A
To select the minimum
0.4s
0.8In or 1200A
To select the minimum
Load-monitoring
(Not for type L25, optional for type M25, M26, H26,
P25 and P26)
Monitoring current
Monitoring current
I
I
LC1
LC2
In
In
BT2-4000
0.8In or 1600A
To select the minimum
BT2-6300
2000A
63
Catalog Disclaimer
The information contained in this catalog does not constitute an express or implied warranty of quality, any warranty of merchantability of fitness for a particular purpose is hereby disclaimed.
Since the user's product information, specific use application, and conditions of use are all outside of Fuji Electric FA
Components & Systems'control, it shall be the responsibility of the user to determine the suitability of any of the
products mentioned for the user's application.
One Year Limited Warranty
The products identified in this catalog shall be sold pursuant to the terms and conditions identified in the
"Conditions of Sale" issued by Fuji Electric FA with each order confirmation.
Except to the extent otherwise provided for in the Conditions of Sale issued by Fuji Electric FA, Fuji Electric FA warrants that the Fuji Electric FA products identified in this catalog shall be free from significant defects in materials and workmanship provided the product has not been: 1) repaired or altered by others than Fuji Electric FA; 2) subjected to negligence, accident, misuse, or damage by circumstances beyond Fuji Electric FA's control; 3) improperly operated, maintained or stored; or 4) used in other than normal use or service. This warranty shall apply only to defects appearing within one (1) year from the date of shipment by Fuji Electric FA, and in such case, only if such defects are reported to Fuji Electric FA within thirty (30) days of discovery by purchaser. Such notice should be submitted in writing to Fuji
Electric FA at 5-7, Nihonbashi Odemma-cho, Chuo-ku, Tokyo, Japan. The sole and exclusive remedy with respected to the above warranty whether such claim is based on warranty, contract, negligence, strict liability or any other theory, is limited to the repair or replacement of such product or, at Fuji Electric FA's option reimbursement by Fuji Electric
FA of the purchase price paid to Fuji Electric FA for the particular product. Fuji Electric FA does not make any other
representations or warranties, whether oral or in writing, expressed or implied, including but not limited to any
warranty regarding merchantability or fitness for a particular purpose. Except as provided in the Conditions of
Sale, no agent or representative of Fuji Electric FA is authorized to modify the terms of this warranty in writing or orally.
In no event shall Fuji Electric FA be liable for special, indirect or consequential damages, including but not limited to, loss of use of the product, other equipment, plant and power system which is installed with the product, loss of profits or revenues, cost of capital, or claims against the purchaser or user of the product by its customers resulting from the use of information, recommendations and descriptions contained herein. The purchaser agrees to pass on to its customers and users, in writing at the time inquiries and orders are received by buyer, Fuji Electric FA's warranty as set forth above.
Safety Considerations
• Operate (keep) in the environment specified in the operating instructions and manual. High temperature, high humidity, condensation, dust, corrosive gases, oil, organic solvents, excessive vibration or shock might cause electric shock, fire, erratic operation or failure.
• For safe operation, before using the product read the instruction manual or user manual that comes with the product carefully or consult the Fuji sales representative from which you purchased the product.
• Products introduced in this catalog have not been designed or manufactured for such applications in a system or equipment that will affect human bodies or lives.
• Customers, who want to use the products introduced in this catalog for special systems or devices such as for atomic-energy control, aerospace use, medical use, passenger vehicle, and traffic control, are requested to consult with Fuji Electric FA.
• Customers are requested to prepare safety measures when they apply the products introduced in this catalog to such systems or facilities that will affect human lives or cause severe damage to property if the products become faulty.
• For safe operation, wiring should be conducted only by qualified engineers who have sufficient technical knowledge about electrical work or wiring.
• Follow the regulations of industrial wastes when the product is to be discarded.
• For further questions, please contact your Fuji sales representative or Fuji Electric FA.