Fireye InSight Type 95 S1, S2 Flame Scanner User Manual
Below you will find brief information for Flame Scanner InSight Type 95 S1, Flame Scanner InSight Type 95 S2. Fireye InSight Type 95 models are micro-processor based flame scanners utilizing solid state infrared (IR) or ultraviolet (UV) or dual (IR and UV) sensors. InSight scanners incorporate an internal flame relay with adjustable ON/OFF thresholds, eliminating the need for a remote flame amplifier. They are designed to detect the presence or absence of a target flame in single or multi-burner applications.
Advertisement
Advertisement
CU-95
November 2000
TYPE 95IR/95UV/95DS
MODEL S1,S2
Integrated Flame Scanner with Internal Flame Relay
Year 2000 Compliant in accordance with BSI document DISC PD2000-I:1998
DESCRIPTION
The FIREYE InSight Type 95IR, 95UV, and 95DS flame scanners are micro-processor based flame scanners utilizing solid state infrared (IR) or ultraviolet (UV) or dual (IR and UV) sensors.
The FIREYE InSight Type 95 flame scanners incorporate an internal flame relay with adjustable
ON/OFF thresholds, thereby eliminating the need for a remote flame amplifier.
The InSight scanners incorporate elements of the FIREYE Type 45FS1 and 45UVFS1 Signature
Scanners™ as well as of the Type 45RM4 flame scanners to detect the presence or absence of a target flame in single or multi-burner applications.
The InSight scanners measure the amplitude of the modulations (the flame “flicker”) that occur within the targeted flame. During the scanner set-up procedure, the modulation frequency that yields the best flame ON/OFF discrimination is selected. The appropriate modulation frequency and sensor gain is either manually selected (S1 models), or automatically selected with manual override capability (S2 models).
The InSight 95IR, 95UV, and 95DS scanners are each available in two models differentiated by feature levels.
The Standard Model S1 has three choices of modulation frequency, adjustable sensor gain, adjustable flame relay ON/OFF thresholds, 4-20 mA analog signal strength output, fault relay, and two selectable programmable files to store setpoints (for two different fuels or firing rates).
The Expanded Model S2 adds automatic programming (AutoTune) with manual override capability,
21 choices of flame flicker frequency, a total of four selectable programmable files to store setpoints, plus adds remote communication capability via Fireye Windows 95/98/NT user software.
All FIREYE InSight scanner models are powered by 24 Vdc, have a twelve-pin electrical quick-disconnect, and contain electronic self-checking (no mechanical shutter required). The scanners contain an eight character alpha-numeric LED display and a four (4) push-button keypad to enable the user to view operating parameters and select setpoints.
1
TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
APPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INSIGHT SCANNER FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
OPERATOR INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
DIMENSIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
AGENCY APPROVALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
INSTALLATION NOTES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
INSTALLATION PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
MECHANICAL ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
ELECTRICAL ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
SCANNER WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
REMOTE FILE SELECTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
ASSEMBLY INSTRUCTIONS, QUICK DISCONNECT KIT . . . . . . . . . . . . . . 13
WIRING FOR REMOTE COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . 16
GROUNDING AND SHIELDING TECHNIQUES . . . . . . . . . . . . . . . . . . . 19
PROGRAMMING THE InSight SCANNER . . . . . . . . . . . . . . . . . . . . . . . 20
INSIGHT MENU STRUCTURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
THE STATUS MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
THE EDIT MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
FILE COPY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
ERROR MESSAGES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
THE PRE-EDIT MENU (“S1” Models only) . . . . . . . . . . . . . . . . . . . . . . . 31
MANUAL SET-UP (“S1” Models only) . . . . . . . . . . . . . . . . . . . . . . . . . . 32
THE AUTOTUNE MENU (“S2” Models only) . . . . . . . . . . . . . . . . . . . . . . 34
ORDERING INFORMATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
2
OPERATION
The InSight scanners measure the amplitude of the modulations that occur within the targeted flame.
During the scanner set-up procedure, the modulation frequency that yields the best flame ON: OFF discrimination is selected. The appropriate modulation frequency and sensor gain is either manually selected (S1models), or automatically selected with manual override capability (S2 models).
With the appropriate modulation frequency selected, the flame relay’s ON and OFF thresholds are then entered. (This selection is set automatically with S2 models). The scanner’s 4-20 mA signal strength output is at minimum (4 mA) with a signal strength of “0”, and at maximum (20 mA) at a signal strength of 100.
The
FLAME RELAY
is energized (and its normally open contacts close) when the signal strength is at or above the programmed flame ON threshold. The flame relay is de-energized when the signal strength is at or below the programmed flame OFF threshold. The flame relay contact circuit will also open upon a power interruption or the detection of an internal fault (see below).
The
FAULT RELAY
is energized when the scanner is powered (24 vdc)
and
when the scanner had successfully passed all internal self-checking routines. The Fault relay is de-energized if there is a power interruption to the scanner
or
if the scanner has detected an internal fault. A normally open
(fault relay) contact is wired in series with the flame relay contact (internally), and a normally closed contact is available for alarm indication.
APPLICATION
Type 95IR
contains an infrared flame sensor, responding to infrared radiation from 700 to 1700 nanometers wavelength. This sensor is best suited to coal and oil applications.
Type 95UV
contains an ultraviolet flame sensor, responding to ultraviolet radiation from 295 to 320 nanometers wavelength. This sensor is best suited to gas applications.
Type 95DS
(Dual sensor) contains both the infrared and ultraviolet flame sensors described above.
This sensor is best suited to multi-fuel applications.
The Standard Model S1
is best suited to the many applications that do not require the level of sophistication, or the remote communications capability of the Expanded Model S2 (e.g. single burner boilers and furnaces, duct burners, etc.)
The Expanded Model S2
is best suited to the applications that require the highest level of sophistication and flexibility (addition choices of modulation frequencies, and the time-saving AutoTune function), and remote communications capability (e.g. larger multi-burner boilers and furnaces).
InSight SCANNER FEATURES
Features
95IR S1
X
Infrared Sensor
Ultraviolet Sensor
Flame Relay
Fault Relay
4-20 mA Output
Modulation Frequency Selections
Memory Files
Communications
AutoTune
Pre-Edit
X
X
3
X
X
2
Basic Models (S1)
95UV S1
X
X
X
X
3
2
X
95DS S1
X
3
2
X
X
X
X
X
95IR S2
Expanded Models (S2)
95UV S2 95DS S2
X
4
X
X
X
21
X
X
X
X
X
X
21
4
X
X
4
X
X
21
X
X
X
X
X
3
OPERATOR INTERFACE
The InSight scanners contain an eight character alphanumeric LED display and a four (4) push-button keypad to enable the user to view operating parameters and select setpoints. For complete set-up procedure, refer to the “PROGRAMMING” section in this document.
DIMENSIONS
FIGURE 1.
TYPE 95IR/95UV/95DS SCANNER (shown with mounting flange, ordered separately)
AGENCY APPROVALS
PART
NUMBER
95IRS1-1
95UVS1-1
95DSS1-1
95IRS2-1
95UVS2-1
95DSS2-1
95IRS1E-1
95UVS1E-1
95DSS1E-1
95IRS2E-1
95UVS2E-1
95DSS2E-1
X
X
X
X
CSA
X
X
X
X
X
X
FM
X
X
AGENCY APPROVALS
DIN-DVGW CE
X
X
X
X
X
X
X
X
X
X
X
X
SPECIFICATIONS
MECHANICAL:
Housing Material:
Housing Weight:
Environmental:
4
Cast aluminum with gray polyester powder coat finish
3 1bs (1.41kg), flange additional
NEMA 4X, IP66
NOTES
Mounting:
Mounting Flange
Kit:
Requires one of two threaded mounting flanges, ordered separately
(see below).
P/N 60-2692 1" NPT female pipe mount with 3/8" NPT female cooling air connection, includes 1" NPT x 3" long heat insulating nipple
(P/N 35-127-1)
P/N 60-2693 1" BSP female pipe mount with 3/8" BSP female cooling air connection, includes 1" BSP x 3"long heat insulating nipple
(P/N 35-127-3)
Mounting Flange Weight:
0.7 lbs (0.32kg)
Cooling / Purge Air Requirements
:
Source:
Clean, dry, cool
Volume:
4 SCFM (113 l/min) at 3/8" threaded mounting flange, or 1 inch “Y” fitting, mounted on scanner sight pipe. Temperature near the upper limit of the scanner operating range and/or use with dirty/dusty fuels may require up to 15 SCFM (425 l/min).
Pressure:
Adequate to overcome furnace or windbox pressure
Temperature Rating:
Humidity:
-40° F to + 150°F (-40°C to +65°C)
0% to 95% relative humidity, non-condensing
ELECTRICAL:
Input Power:
Electrical Connection:
Relay Output
Contact Rating:
24 Vdc, +10%, -15% supply current 0.35 A, 8.5 VA
12-pin quarter-turn quick-disconnect
FLAME RELAY, SPST (N.O.)
FAULT RELAY, SPST (N.C.)
Minimum: 10 mA @ 5 Vdc
Maximum: 2 A @ 30 Vdc
2 A @ 50 Vac (CE approved models, see page 4)
2 A @ 240 Vac (FM & CSA models)
Analog Output:
4-20 mA dc current, referenced to 24Vdc, maximum connected
1oad: 750 ohms
Eight (8) character alpha-numeric LED display (scrolling capability)
Status Indication:
Operator Interface:
Four (4) pushbutton style keys
Cable Specification:
P/N 59-497:
Multi-core, 12 conductor (color coded), with foil wrap and overall braided shield
Six #18 AWG and four #22 AWG conductors, plus one #22 AWG twisted pair
Cable Jacket: Irradiated Modified Polyolefin (flame-retardant, low smoke, zero halogen)
Nominal O.D. 0.41" (10.4 mm)
Maximum O.D. 0.43" (10.9 mm)
Maximum cable length 1000 feet (305 meters)
5
INSTALLATION NOTES
The InSight flame scanners determine the presence or absence of flame by monitoring the frequency spectrum of the flame. The scanner should initially be mounted so that the primary combustion zone is within the scanner’s line of sight.
The location and sighting instructions listed in the following sections are rough guidelines for the location of the scanner. The scanner provides feedback via its LED display to assist in the adjustment and proper alignment of the flame scanner. Refer to the setpoint procedures described in this bulletin.
Note:
An acceptable scanner location must ensure the following:
Reliable main flame and/or ignitor flame detection at all air flow and furnace loads (ranges of fuel firing).
Rejection of the ignitor flame if too short or in the wrong position to ignite the main flame reliably, thus prohibiting the delivery of fuel to the burner.
Note:
Due to the microprocessor based design of the InSight scanner, the heat insulating nipple
(P/N 35-127-1 or 35-127-3) must be used to isolate the scanner from ground and to reduce conducted energy and noise. See Figure 7. The nipple is included in mounting flange kit P/N 60-2692, 60-2693.
INSTALLATION PROCEDURE
WARNING: Protective filtered lenses should be worn when viewing flame. Infrared and ultraviolet energy from the flame can be damaging to the eyes.
FIGURE 2.
1.
2.
3.
The best results are obtained when the scanner is aimed so that the scanner’s line of sight intersects the burner center at a slight angle (e.g. 5 degrees) and sees a maximum of the primary combustion zone, as shown in Figure 2. If only one scanner is used per burner, the line of sight should also intersect the igniting flame.
For installations where separate scanners are used to monitor main and ignitor flames, the main flame scanner should be sighted so it does not detect the ignitor flame.
The scanner should have an unrestricted view of flame as far as possible. Physical obstructions such as air register blades, interfering vanes, or other hardware should be cut away or notched so they do not fall within the scanner’s line of sight as shown in Figures 2 and 4.
Note:
Always check with the burner manufacturer
before
you trim the register blades.
SINGLE BURNER SCANNER SIGHTING
AIR REGISTER
BLADES
FLAME
ENVELOPE
SCANNER
LINE OF
SIGHT
BURNER
THROAT
BURNER
CENTER LINE
BASE
PRIMARY
COMBUSTION
ZONE
4.
Consideration must be given to burner secondary air rotation, some burners have clockwise (CW) air rotation and others have counterclockwise (CCW) air rotation. If combustion air enters the furnace with a rotational movement of sufficient velocity to deflect the ignitor flame in the direction of rotation, position the scanner 10 to 30 degrees downstream of the ignitor as shown in Figure 3 and close to the periphery of the burner throat (See Figure 2).
6
FIGURE 3.
FIGURE 4.
SCANNER LOCATION VS. SECONDARY AIR ROTATION
IGNITOR IGNITOR
SCANNER
SCANNER
MAIN
BURNER
MAIN
BURNER
CCW ROTATION CW ROTATION
5.
Having determined the approximate location for the sight pipe, cut a clearance hole for a 2 inch pipe through the burner plate. Look through the hole. If register vanes interfere with the desired line of sight, the interfering vane(s) should be trimmed to assure an unrestricted viewing path at all firing levels as indicated in Figures 2 and 4.
Note:
Always check with the burner manufacturer
before
you trim register vanes.
FLAME MUST COMPLETELY COVER SIGHT OPENING
NOT THIS NOT THIS BUT THIS
6.
The preferred method for mounting surface mounted scanners requires the use of a swivel mount, Part No. 60-1664-3 (NPT), shown in Figures 5, 6 and 7. Center the swivel mount over the two inch hole in the burner plate and secure using three hexed cap screws (not provided).
Install the sight pipe on the swivel mount. If a swivel is not used, insert the end of the sight pipe into the hole, align the hole to the desired viewing angle and tack weld (welding must be adequate to temporarily support the weight of the installed scanner). The sight pipe should be arranged to slant downward so that dirt and dust will not collect inside.
CAUTION: Use no more than one foot of one inch diameter sight pipe. Increase the sight pipe diameter one inch for every additional foot of sight pipe length used to avoid restricting the scanner’s field of view.
7.
8.
When a satisfactory sighting has been confirmed by operational testing, secure the swivel mount’s ball position in place by tightening the three hex head cap screws located on the swivel mount ring.
For ease of use, the scanner should be installed on the sight pipe so the LED display can easily be read.
Note:
Operation of the LED display is independent of position.
Note:
Due to the microprocessor based design of the InSight scanner, the heat insulating nipple
(P/N 35-127-1 or 35-127-3) must be used to isolate the scanner from ground and to reduce conducted energy and noise. See Figure 7.
9.
The scanner lens must be kept free of contaminants (oil, ash, soot, dirt) and the scanner housing temperature must not exceed its maximum rating of 150° F (65° C). Excessive temperatures will shorten scanner life. Both requirements will be satisfied by a continuous injection of purge air at either the 3/8" housing inlet or the 1” “Y” connection ahead of the swivel mount as shown in Figures 5 and 6.
Note:
Internal scanner temperature is available via the LED display. See “Status Menu” under
“Programming the Scanner.”
7
The scanner mounting may be made with provision for purge air through only the 3/8" opening as shown in Figure 7 or for purge air through either the 3/8" opening or the 1” “Y” connection as shown in Figure 6. In the latter arrangements, normally only one of the two connections is provided with purge air and the other connection is plugged. When a sealing union is used as shown in Figure 5, the
1" “Y” connection is used for the purge air and the 3/8" opening is plugged.
It is good practice to use the sealing union (P/N 60-1199 with NPT threads) on all installations to insure against unwanted furnace pressures from damaging the scanner lens.
Under normal conditions, with clean burning fuels and moderate ambient temperature conditions, purge air flow of approximately 4 SCFM (133l/min) is generally adequate. Up to 15 SCFM
(425 l/min) may be required for fuels that produce high levels of ash or soot, or for hot environments to maintain the scanner’s internal temperature within specification. Flexible conduit should be used to wire the scanner from a grounded service box to the scanner.
MECHANICAL ACCESSORIES
Surface Mounting Flange (Required)
P/N 60-2692
P/N 60-2693
1" NPT female pipe mount with 3/8" NPT female cooling air connection, includes locking ring and 1" NPT x 3" long heat insulating nipple
(P/N 35-127-1).
1" BSP female pipe mount with 3/8" BSP female cooling air connection, includes locking ring and 1" BSP x 3" long heat insulating nipple
(P/N 35-127-3).
Swivel Mount (Optional)
The scanner swivel mount, P/N 60-1664-3 (NPT) (see Figure 8, Item A), is used to adjust the scanner sighting angle after the scanner has been installed, The swivel mount is used as indicated in Figures
5, 6, and 7.
Heat Insulating Nipple (Required)
Heat Insulating nipple, P/N 35-127-1 (NPT), or P/N 35-127-3 (BSP) (see Figure 7, Item B), is used to prevent heat transfer from the hot sight pipe to the scanner head as well as electrically isolate the scanner from ground. The appropriate nipple (NPT or BSP) is shipped
with
the surface mounting flange.
Sealing Union with Quartz Window (Optional)
The sealing union, P/N 60-1199 (see Figure 8, Item B), is used whenever a coupling or a seal is required for scanner piping. The quartz window blocks furnace pressure, hot gases and soot from coming in contact with the scanner and contaminating the lens. The size is one inch U.S. standard taper pipe thread (Schedule 40, 1" - 11
1
/
2
NPT). When the sealing union is used, a 1 inch “Y” fitting must be used down stream of it for connection of a purge air supply (plug
3
/
8
" opening). See Figure 5 for piping with the sealing union, Item D.
ELECTRICAL ACCESSORIES
Scanner Cable, P/N 59-497
Fireye recommends P/N 59-497 multi-core, 12 conductor (color coded), foil wrap and overall braided shield cable. This cable includes six #18 AWG and four #22 AWG conductors, plus one #22 AWG twisted pair. The cable jacket is Irradiated Modified Polyolefin (flame-retardant, low smoke, zero halogen) with a maximum diameter of 0.43" (10.9 mm). The maximum cable length is 1000 feet (305 meters) per scanner. This raw stock cable requires the Quick-Disconnect Kit described below. Refer to Figure 9 for color code and connection information.
8
Quick-Disconnect Kit, P/N 129-164
A twelve-pin (male) electrical connector is factory installed on the InSight scanners. Fireye offers the mating (female) connector for field installation onto the 59-497 cable. Refer to Quick-Disconnect assembly instructions.
Scanner Cable with Factory installed Female Connector (P/N 59-497-XXX)
Fireye offers the 59-497 12-conductor cable in pre-cut lengths with the female quick-disconnect factory installed. These assemblies are offered in lengths from 10 feet (3m) to 300 feet (91m)
Wiring Harness Assembly, P/N 61-6944-XXX
If remote communication is required (Model S2 only), and the distance between the InSight scanner and the control room exceeds 200 feet (61m), then a small junction box must be installed near each scanner.
The two communications wires must be separated out of the twelve-conductor scanner cable at the junction box and wired independently in a multi-drop (“daisy-chain”) configuration to each scanner in the loop, and finally to the computer. The Fireye Wiring Harness Assembly, available in lengths from 3 to 30 feet (0.9 to 9.1m), provides a convenient method to accomplish this.
On one end, the harness has a female quick-disconnect to connect to the InSight scanner. Fireye twelve-conductor cable, P/N 59-497 is factory wired to the quick-disconnect, run through flexible conduit and connected to a terminal strip within a junction box at the other end of the harness. The terminal strip accepts up to 14 AWG wires and uses push-type cage clamp connectors for quick and secure connections.
From the junction box, the installer would connect all but two wires of a length of Fireye 59-497 twelve-conductor cable that is run to the burner management system. The two communications wires originating from the scanner would be connected from one junction box to the next, and finally to the computer using a two-conductor communications cable (Belden #8761, 22 AWG or equal).
24 Volt DC Power Supplies
Fireye offers two DIN rail mounted 24 vdc power supplies for use with the InSight Integrated flame scanner. Model 60-2685-2 (2 amp) can power up to five InSight scanners, model 60-2685-4 (4 amp) can power up to ten Insight scanners ( see note 1).
PART NUMBER
60-2685-2
60-2685-4
60-2539-12
60-2539-24
60-2539-36
DESCRIPTION
24 VDC Switching Power Supply, 50W, 100-240 vac 50/60 Hz. input, 2.1 A output at 24 vdc
Dimensions: 3.2"(82mm) high x 3.5" (90mm) wide x 3.6"(91mm) deep
1,2
NOTES
24 VDC Switching Power Supply, 100W, 120 / 240 vac 50/60 Hz. input, 4.2 A output at 24 vdc
Dimensions: 3.2"(82mm) high x 5.7" (145mm) wide x
3.6"(91mm) deep
1,2
DIN mounting rail, 12" (305mm)long 2
DIN mounting rail, 24" (610mm)long
DIN mounting rail, 36" (914mm)long
2
2
Notes:
1. Rated output is when power supply is vertically mounted, and with an ambient temperature of
122F (50C) maximum. When supply is mounted vertically, at 140F (60C) the output is de-rated 25%.
2. When mounted in a row, allow at least 0.79" (20mm) between adjacent power supplies.
9
FIGURE 5.
PART NUMBER
A. SWIVEL MOUNT
B. 1" WYE
C. 1” CLOSE NIPPLE
60-1664-3 (NPT)
60-1664-4 (BSP)
35-200 (NPT)
35-201 (NPT)
D. SEALING UNION W/QUARTZ WINDOW
60-1199 (NPT)
E. HEAT INSULATING NIPPLE 35-127-1 (NPT)
35-127-3 (BSP)
F. 3/8" PLUG 35-202 (NPT)
G. SURFACE MOUNTING
FLANGE (includes item E)
60-2692 (1”NPT)
60-2693 (1”BSP)
A
FIGURE 6.
PART NUMBER
A. SWIVEL MOUNT 60-1664-3 (NPT)
60-1664-4 (BSP)
35-200 (NPT) B. 1" WYE
C. HEAT INSULATING NIPPLE 35-127-1 (NPT)
35-127-3 (BSP)
D. 3/8" PLUG 35-202 (NPT)
E. SURFACE MOUNTING
FLANGE (includes item C)
60-2692 (1”NPT)
60-2693 (1”BSP)
A
B
B
D
23.8” (605mm)
C E
20.6” (523mm)
D
C
E
G
F
FIGURE 7.
PART NUMBER
A. SWIVEL MOUNT
B. HEAT INSULATING NIPPLE 35-127-1 (NPT)
35-127-3 (BSP)
C. 3/8" THREADED OPENING
60-1664-3 (NPT)
60-1664-4 (BSP)
D. SURFACE MOUNTING
FLANGE (includes item B)
60-2692 (1”NPT)
60-2693 (1”BSP)
A
D
B
15.3” (389mm)
C
10
FIGURE 8.
PART NUMBER
A. SWIVEL MOUNT
SWIVEL MOUNT
60-1664-3 (NPT)
60-1664-4 (BSP)
B. SEALING UNION W/QUARTZ WINDOW
60-1199 (NPT)
C. SCANNER CABLE 59-497
A
B
C
SCANNER WIRING
To reduce electrical noise interference, the scanner cable should be installed in rigid or flexible conduit. Take precautions to keep the scanner cable away from any high inductive wiring associated with high inductive loads or high voltage, high energy spark ignition systems.
CAUTION: The InSight flame scanner requires 24 Vdc power for operation. Connection to a 24 Vac or 120 Vac power source will damage the scanner. Refer to wiring diagrams.
External 2.0 Amp fuses are recommended to protect Flame Relay and Fault Relay contacts
All wiring to the scanner should be rated at 90°C. For runs less than 1000 feet, the use of
Fireye Scanner Cable, Part No. 59-497, (12 wire) is recommended. For runs in excess of
1000 feet, consult the factory.
11
FIGURE 9.
WIRING DIAGRAM, INSIGHT INTEGRATED FLAME SCANNER
TYPE 95IR/95UV/95DS
QUICK-DISCONNECT
PIN NUMBER
FIREYE CABLE 59-497
COLOR CODE
(+)
INPUT
POWER
24VDC
(-)
A
B
BLACK/RED
WHITE/BLUE
C
WHITE/BLACK
FLAME
RELAY
(Note 1)
FAULT
RELAY
(Note 2)
FAULT
RELAY
(Note 2)
D
E
F
WHITE/RED
RED
FUSE
PINK
FUSE
(+)
(-)
24 VDC
INPUT
POWER
TO BMS
INPUT
(Notes 6, 7)
TO BMS
INPUT
(Notes 6, 7)
4-20mA
OUTPUT
Referenced to Common
(+)
(-)
G
H
VIOLET
GREY/RED
TO BMS
METER
(Note 6)
REMOTE
FILE SELECT 1
J
BLUE/RED
SW1
(Note 5)
12
SW2
REMOTE
FILE SELECT 2
(Model S2 only)
REMOTE
COMMUNICATIONS
(Model S2 only)
A
B
K
L
(Note 8)
M
YELLOW
BROWN
ORANGE
(Notes 3, 4)
(Note 5)
TO
COMPUTER
6.
7.
8.
Notes:
1.
2.
3.
4.
5.
Flame relay contacts are shown in de-energized (no flame) condition.
Fault relay contacts are shown in de-energized (fault) condition.
Brown and orange wires are a twisted pair.
Cable shield not shown.
With Remote File Select programmed as “LINE”, external switches SW1/SW2 (not furnished) will select between two (S1 Models) or four (S2 Models) internal memory files, when connected to
24Vdc(-) supply.
BMS = Burner Management System (by others).
External 2.0 Amp fuses recommended.
A ground screw is provided on the scanner end plate. An external ground wire must be installed if line voltage is applied to the relay contacts.
REMOTE FILE SELECTION
The InSight scanners have more than one internal memory file. The user has the option of storing different scanner setpoints for different operating conditions (e.g. Gas / Oil, Pilot / Main, Low Fire /
High Fire, etc.) in these files. The “S1” models have two programmable files (A & B), and “S2” models have four (A,B,C, & D). With RFS selected as “LINE”, one or two external switches (supplied by user) will select between the files when the RFS1 or RFS2 wires are connected to
24 vdc (-).
RFS1 (Blue) RFS2 (Yellow) File Selected
Open
Closed
Open
Closed
(Note 1)
Open
Open
Closed
Closed
Note 1:
RFS2 function is available in the “S2” models only.
A
B
C
D
Note 2:
The user may also select RFS as “KEY” which will allow manual file selection at the scanner keypad.
Note 3:
With FM & CSA approved “S2” models, the user may also select RFS as “COMM” which will allow manual selection at a remote computer running Fireye software. This feature is not available with CE approved “S2E” models.
Note 4:
Fireye recommends the use of shielded cable for the two remote file select switches (or relays). The switch contacts should be rated for low current operation (3mA dc).
ASSEMBLY INSTRUCTIONS, QUICK DISCONNECT KIT P/N 129-164
ASSEMBLY (Refer to Figure 11)
FIGURE 10.
QUICK DISCONNECT TERMINAL
59-497 Cable Color
Black/Red
White/Blue
White /Black
White/Red
Red
Pink
Violet
Grey/Red
Blue/Red
*Yellow
*Brown
*Orange
* “S2” models only
Pin Number of Quick
Disconnect
A
B
C
F
G
D
E
K
L
H
J
M
Function
Power (+) 24 Vdc
Power (-) 24 Vdc
Flame Relay (N.O.)
Flame Relay (N.O.)
Fault Relay (N.C.)
Fault Relay (N.C.)
4-20 mA (+)
4-20 mA (-)
File Select 1
File Select 2
Communications A
Communications B
Note:
Brown and orange wires are a twisted pair.
13
FIGURE 11.
VT
PK
GY/RD
BU/RD
FOR EASE OF CONNECTOR ASSEMBLY, INSTALL ON END SHOWN
COLOR CODE:
RD
BN
OR
YL
WT/RD
WT/BK
WT/BU
BK/RD
BK = BLACK
RD = RED
WT = WHITE
PK = PINK
VT = VIOLET
GY = GREY
BU = BLUE
YL = YELLOW
BN = BROWN
OR = ORANGE
For ease of assembly, install the
129-164 connector on the 59-497 cable end where the 3 white wires are clockwise to the red wire.
FIGURE 12.
CONNECTOR ASSEMBLY INSTRUCTIONS
.87 ± .04
(22.1 ±1)
BRAID
.15 - .18
(3.8 - 4.6)
1.75 ± .04
(44.5 ±1)
Inches (mm)
CLAMP NUT
GROUNDING RING
HOUSING
CABLE SEAL
COUPLING NUT
O-RING
SUPPORT SLEEVE
CABLE GRIP
SCANNER CABLE
59-497
FEMALE CONTACTS
PLUG CONNECTOR
CONNECTOR ASSEMBLY STEPS
1.
2.
3.
4.
Select 59-497 cable end with the wire color orientation as shown in Figure 10.
Slide items along the cable as shown, including coupling nut and O-ring (discard the black thread protector and orange grommet from plug connector).
Strip cable connector end in accordance with Figure 11. Slide braid back and forth to loosen, then fold braid back over cable jacket. Cut and discard foil tape.
Solder the wires to the contacts.
14
FIGURE 13.
5.
6.
7.
Slide contacts into plug connector per wiring table until contacts lock in place.
Slide coupling nut up against plug connector flange and slide O-ring into groove on plug connector body.
Slide support sleeve back over braid and drain wire then place braid over spring elements of support sleeve. Clamp braid and drain wire by snapping on the metal grounding ring.
Screw housing onto the plug connector. Torque to 27 lb-in ± .25 lb-in, (3.05N-m ± 0.03 N-m)
.
Assemble cable seal and cable grip to the housing, screw clamp nut onto housing and tighten to 27 lb-in ± .25 lb-in, (3.05N-m ± 0.03 N-m)
.
WIRING TABLE AND PLUG CONNECTOR PIN LOCATION
PLUG CONNECTOR PIN LOCATION
(VIEWED FROM PIN INSERTION SIDE)
WIRE PIN
BLACK/RED, #18 AWG A
WHITE/BLUE, #18 AWG
WHITE/BLACK, #18 AWG
B
C
WHITE/RED, #18 AWG
RED, #18 AWG
PINK, #18 AWG
VIOLET, #22 AWG
D
E
F
G
GREY/RED, #22 AWG
BLUE/RED, #22 AWG
YELLOW, #22 AWG
BROWN, #22 AWG TWISTED
ORANGE, #22 AWG TWISTED
K
L
H
J
M
G
H
J
M
F
K
A
E
L
B
D
C
15
FIGURE 14.
WIRING HARNESS ASSEMBLY
Safety Ground
Ground Screw
Scanner Quick Disconnect
Connector and Flexible
Metal Conduit
Belden 8761 for communication to other scanners
IN
OUT
Length
3 ft.
10 ft.
15 ft.
20 ft.
30 ft.
HARNESS ASSEMBLY NO
Part No.
61-6944-003
61-6944-010
61-6944-015
61-6944-020
61-6944-030
59-497 CABLE (ordered separately)
TO BURNER
MANAGEMENT SYSTEM
EMI CONNECTOR (not included)
For FIREYE 59-497 cable
Housing Connected to Earth Ground
1
2 3
4
5 6 7 8 9 10 11 12
Prewired by Factory
WIRING FOR REMOTE COMMUNICATIONS (“S2” models only)
Remote communications with the InSight scanner uses an RS485 Interface to carry the communication signals. An IBM compatible PC running Fireye software is required to communicate with the flame scanners.
The wiring configuration for remote communications is dependent on the dis-
tance between the scanner and amplifier. For distances less than 200 feet, wire the Fireye cable
P/N 59-497 to the female quick disconnect in the manner previously described, and run the cable directly back to the burner management system.
For wiring distances greater than 200 feet, remote communications requires wiring a twisted,
shielded pair of wires in a “multi-drop” wiring configuration, and then use a terminating resistor at the scanner located farthest from the communication source. See “Using Fireye Wiring Harness.”
16
Note: The maximum distance for the communication wiring for all associated InSight scanners is
4,000 feet. The maximum number of scanners connected to the communication link is 32 scanners.
Exceeding this total wiring length or number of scanners requires the installation of bi-directional repeaters or amplifiers. Consult factory for additional information.
Using Fireye Wiring Harness (P/N 61-6944 -003, -010, -015, -020, -030).
To provide an easy method to wire the InSight scanners in a “Multi-drop” wiring configuration for remote communications, Fireye offers a wiring harness in 5 different lengths (3, 10, 15, 20 and
30 ft.). The harness has a pre-wired female quick disconnect to plug into the quick disconnect on the scanner. The other end of the wiring harness has a conduit box with a 16 connector terminal strip.
Twelve (12) connectors are pre-wired to the female quick disconnect.
Wire cable Cable Color Function
59-497
Cable
Blue/Red
Yellow
Brown
Orange
Belden 8761 Black
Clear
Belden 8761 Black
Clear
Black/Red
White/Blue
Power (+) 24 VDC
Power (-) 24 VDC
White /Black Flame Relay (N.O.)
White/Red Flame Relay (N.O.)
Red
Pink
Violet
Grey/Red
Fault Relay (N.C.)
Fault Relay (N.C.)
4-20 mA (+)
4-20 mA (-)
File Select 1
File Select 2
Communications A
Communications B
RS485 COM A
RS485 COM B
RS485 COM A
RS485 COM B
12
11
12
11
12
10
11
8
9
Wiring Harness
1
2
3
6
7
4
5
Back to Control Room
(Burner Management System)
To next flame scanner
To previous flame scanner
(or IC485 converter)
17
FIGURE 15.
RS485 communication; For each individual wiring run, connect shields together.
Connect one end of the shield circuit to ground. Tape and isolate other end. See next page for more detail.
SUGGESTED WIRING FOR COMMUNICATIONS
RS485 COMMUNICATIONS
59-497 to
Control Room
BELDEN #8761
(Twisted, shielded pair) to previous wiring harness.
1
2 3
4
5 6 7 8 9 10 11 12
59-497 to
Control Room
TO NEXT WIRING
HARNESS
1 2 3 4 5
6 7 8 9 10 11
12
Flex Conduit to Scanner
Flex Conduit to Scanner
FIGURE 16.
WIRING DIAGRAM FOR WIRING HARNESS
TO FLAME
SCANNER
(prewired by factory)
COM B — ORANGE
COM A — BROWN
RFS2— YELLOW
RFS1— BLUE/RED
4-20mA (-) — GREY/RED
4-20mA (+) — VIOLET
FAULT RELAY (N.C.) — PINK
FAULT RELAY (C) — RED
FLAME RELAY (N.O.) —WHITE/RED
FLAME RELAY (C) WHITE/BLACK
(-)24VDC — WHITE/BLUE
(+) 24VDC — BLACK/RED
CONNECT SCANNER SHIELDS
TOGETHER AND GROUND AT
BURNER MANAGEMENT
SYSTEM
59-497
1
2 3
4 5 6 7 8
9 10
11
TO CONTROL
ROOM
BLACK/RED
WHITE/BLUE
WHITE/BLACK
WHITE/RED
RED
PINK
VIOLET
GREY/RED
BLUE/RED
YELLOW
12
CLEAR
COM B
COM A
BLACK
1. CONNECT SHIELDS
TOGETHER.
2. TAPE SHIELD AT
LAST WIRING HARNESS
TO NEXT
SCANNER
BELDEN
8761
CLEAR COM B
BLACK COM A
TO PREVIOUS
SCANNER, OR
EC485 CONVERTER.
1. CONNECT SHIELDS TOGETHER
2. CONNECT SHIELD TO
EARTH GROUND AT
ORIGIN. (FIRST HARNESS OR PC)
18
FIGURE 17.
WIRING FOR REMOTE COMMUNICATIONS
1. WHEN THE DISTANCE FROM SCANNER TO CONTROL ROOM< 200 FEET.
59-497
CABLE
BELDEN 8761
59-497
CABLE
BELDEN 8761
59-497
CABLE
BELDEN 8761
BURNER
MANAGEMENT
SYSTEM
BURNER
MANAGEMENT
SYSTEM
BURNER
MANAGEMENT
SYSTEM
2. WHEN THE DISTANCE FROM SCANNER TO CONTROL ROOM >200 FEET.
RS485-RS232
CONVERTER, P/N IC485
PC WITH
FIREYE
SOFTWARE
61-6944
WIRING
HARNESS
59-497
CABLE
BURNER
MANAGEMENT
SYSTEM
BELDEN 8761
59-497
CABLE
BURNER
MANAGEMENT
SYSTEM
BELDEN 8761 BELDEN 8761
59-497
CABLE
RS485
COM A
COM B
RS485-RS232
CONVERTER, P/N IC485
BURNER
MANAGEMENT
SYSTEM
PC WITH
FIREYE
SOFTWARE
GROUNDING AND SHIELDING TECHNIQUES
FOR USE ON SCANNERS OR SCANNER CABLE LOCATED WITHIN 12" OF A HIGH ENERGY
OR HIGH VOLTAGE SOURCE.
1.
Connect a safety ground to scanner housing (Figure 13).
2.
The scanner and scanner cable (preferably within flexible conduit) MUST be located at least 12" from the ignition source.
3.
Run a ground wire from the ignition transformer chassis to the ignitor assembly.
4.
Replace all frayed, cracked, or dirty (oily) ignition wire. Ignition wire must be in good working condition.
5.
Electrically isolate the scanner from the burner using a heat insulating nipple provided with the surface mounting flange.
6.
Cooling/Purge Air must be electrically isolated from the scanner (e.g. isolated short rubber hose).
SCANNER TO CONTROL ROOM SHIELDING TECHNIQUES
Scanner with scanner cable (59-497) wired directly back to burner management system. See below for remote communications.
Attach drain wire to scanner quick disconnect as described. Use heat insulating nipple on scanner. Connect drain wire of 59-497 to earth ground at power supply.
REMOTE COMMUNICATIONS: LESS THAN 200 FEET
Scanner with scanner cable (59-497) wired directly back to control room.
Attach drain wire to scanner quick disconnect as described. Use heat insulating nipple on scanner. Connect drain wire of 59-497 to earth ground at power supply.
REMOTE COMMUNICATIONS: GREATER THAN 200 FEET
RS485 communications for scanners wired in a multidrop configuration (Belden 8761) using wiring harness or junction box.
Attach drain wire to scanner quick disconnect as described. Use heat insulating nipple on scanner. Connect drain wire of 59-497 to earth ground at power supply. Twist together and tape (to electrically isolate) drain shields from Belden 8761 cables inside each wiring harness or junction box. Connect shield drain to earth ground at RS485 source (e.g. IBM computer).
19
PROGRAMMING THE INSIGHT SCANNER
Keypad/Display:
The InSight flame scanner uses an eight (8) character alphanumeric LED Display and four (4)pushbuttons to review and program the various setpoints and operating parameters. The functions of the pushbuttons are:
UP/DOWN
The UP and DOWN buttons are used to scroll through the scanner menus. When in the EDIT menu, after selecting a setpoint to edit, (see SELECT button), the UP and DOWN buttons are used to change that setpoint.
SELECT
When in the EDIT menu, the UP / DOWN buttons are used to display the setpoints. Depressing the
SELECT button displays the stored value of the setpoint, allowing it to be changed.
PROGRAM
The PROGRAM button saves a change made to a setpoint. It is also used to execute the Auto Tune function (“S2” Models only) or Pre-Edit function (“S1” Models only).
INSIGHT MENU STRUCTURE
For ease of operation, the InSight scanner contains three menus (or loops) accessed via the keypad and viewed on the scanner’s display.
STATUS MENU
The Status menu is the default display, and appears as soon as power is applied. Use the UP and
DOWN buttons to scroll through the menu and view the current operating status. No operating parameters can be changed from the Status menu. To change any setpoint, you must enter a four digit password then enter the Edit, or Pre-Edit (“S1”) or AutoTune (“S2”) menus.
EDIT MENU
The Edit Menu contains all the user-selected setpoints for the InSight scanner. The Edit menu is entered from the Status menu after first entering a four-digit password. In the Edit menu, the user is allowed to change the setpoints to optimize the scanner performance.
PRE-EDIT MENU (“S1” Models only)
From the Pre-Edit menu, the user views the flame signal intensity and physically aims the scanner for optimum signal. The user then commands the scanner to set an appropriate internal front-end gain
(FEG) level. As with the Edit menu, the Pre-Edit menu is entered from the Status menu after first entering a four-digit password.
20
FIGURE 18.
AUTOTUNE MENU (“S2” Models Only)
From the AutoTune menu, the user views the flame signal intensity and physically aims the scanner for optimum signal.The user then commands the InSight scanner to analyze the flame ON and OFF
(background radiation) conditions, and automatically select the optimum setpoints. As with the Edit menu, the AutoTune menu is entered from the Status menu after first entering a four-digit password.
INSIGHT SCANNER MENU STRUCTURE
FQ O
NOTE 1: If the password is not entered, access to the
EDIT, PRE-EDIT and AUTO TUNE loops are denied.
Pressing the (
▲
) UP KEY advances the display directly to “FQ O”.
Note 1
AUTOTUNE (“S2”)
OR
PRE-EDIT (“S1”)
AUTOTUNE (“S2”)
OR
PRE-EDIT (“S1”)
LOOP
STATUS
LOOP
PASSWORD
EDIT
EDIT
LOOP
Note 1
21
THE STATUS MENU
FIGURE 19.
STATUS MENU LOOP
Keypad Legend
UP Key (Scrolls through menu, clockwise)
DOWN Key (Scrolls through menu, counter clockwise)
SELECT Key
FLAME OFF
PROGRAM Key
T=46C
FILE A
NOTE 1: If the password is not entered, access to the EDIT, PRE-EDIT and AUTO
TUNE loops are denied. Pressing the (
▲
) UP
KEY advances the display directly to “FQ O”.
NOTE 2: Refer to PASSWORD section for further details.
NOTE 3: Dual sensor model shown (IR &
UV).
NOTE 4: Communications available in “S2” models only.
NOTE 1
FQ 0
START HERE
AUTOTUNE (“S2”)
OR
PRE-EDIT (“S1”)
iO uO
PASSWORD
EDIT
NOTE 3
COMM 0
NOTE 4
SOFTWARE
REVISION
MAX 51C
NOTES 1 & 2
TO PRE-EDIT (“S1”)
OR AUTOTUNE (“S2”)
MENU LOOP
TO EDIT MENU LOOP
FIGURE 20.
TEXT DISPLAYED
FQ 0
FLAME OFF
T= 46C
File A i 0 u 0
COMM 0
SOFTWARE REVISION
MAX 46C
PASSWORD
THE STATUS MENU
DESCRIPTION
Flame Quality (scanner output)
Flame Relay status
Present Scanner temperature
Scanner file in operation
Signal strength, IR and UV (dual sensor models)
Communication address (“S2” models only)
Scanner software revision
Scanner Temperature, stored maximum
A Password is required to enter the EDIT, PRE-EDIT or
AutoTune menus. See PASSWORD section.
POSSIBLE VALUES
0-100
ON, OFF
+32°F to 212°F (0°C to 100°C)
A,B,C,D
0-999
0-127
-40° F to 185°F (-40°C to 85° C)
0000-9999
22
Flame Quality
The “Flame Quality” number can range from 0 to 100. It represents the scanner’s 4-20 mA analog flame signal strength OUTPUT (in percent), and is the scale by which the internal Flame Relay ON and OFF thresholds are set.
The “Flame Quality” number is determined by the input of the IR and / or UV sensor, (in dual sensor models it is the sum of the two). This sensor signal strength value can be viewed in the Status menu as “Signal Strength”, see description below.
For clarity, the “Flame Quality” number is capped at 100, while under certain firing conditions the IR or UV “signal strength” (or their sum) may normally exceed 100 (maximum of 999).
In normal burner operation after the scanner has been properly setup, “FQ 100” will be displayed with occasional movement depending on the stability of the flame.
Flame ON/Off
This item refers to the energized / de-energized status of the internal Flame relay. “Flame ON” is displayed when the flame quality rises above the relay “On Threshold” set in the Edit menu. When the flame quality drops below the relay “Off Threshold”, “Flame OFF” will be displayed.
Temperature
The scanner’s present temperature in degrees, expressed in either Fahrenheit or Centigrade depending on which was selected in the Edit menu.
File Selected
The current running file is displayed. Choices are files “A, B” for S1 Models, and files “A,B,C,D” for
S2 Models.
Signal Strength
The Signal Strength number represents the intensity of the “flame flicker”, as sensed by the IR and / or UV sensor(s), and is a function of the individual sensor “Gain” and “Bandpass” (flicker frequency) settings. The Signal Strength number is related to the Flame Quality number (see Signal Strength expanded description below).
Comm Address (“S2” Models Only)
This number refers to the remote communications address of the scanner. The address can range from 0 to 127, as selected in the Edit menu. No two scanners in a communications loop should have the same address.
Software Revision
This displays the internal software revision.
Maximum Temperature
This displays the highest scanner temperature recorded.
Password
A four-digit Password is required to enter the EDIT and AUTOTUNE menus. If a Password is not entered, pressing the UP key will advance directly to the “Flame Quality” display, pressing the
DOWN key will return to the “Maximum Temperature” display.
To enter the EDIT or AUTOTUNE menus, you must enter the four-digit Password. The following
example is for the factory installed password of 0205:
1.
With “PASSWORD” displayed, depress the SELECT key. “0xxx” will be displayed, the first digit (“0”) is adjustable. (If the factory password was changed, use the UP/DOWN keys to select the appropriate first digit).
23
24
2.
With the first digit selected (e.g. “0xxx”) depress the PROGRAM key. “00xx” will be displayed, the second digit (“0”) is adjustable. Depress the UP key twice to display “2”. (If the factory password was changed, use the UP/DOWN keys to select the appropriate second digit).
3.
With the second digit selected (e.g. “02xx”) depress the PROGRAM key. “020x” will be displayed, the third digit (“0”) is adjustable. (If the factory password was changed, use the UP/
DOWN keys to select the appropriate third digit).
4.
With the third digit selected (e.g. “020x”) depress the PROGRAM key. “0200” will be displayed, the fourth digit (“0”) is adjustable. Depress the UP key five times to display “5”. (If the factory password was changed, use the UP/DOWN keys to select the appropriate fourth digit).
5.
With all four digits selected (e.g. “0205”) depress the PROGRAM key.
If the Password was not entered correctly, the display will read “Wrong Password”. Depress the
SELECT key to re-enter the password.
If the Password was entered correctly, the display will read “Valid Password. Press SELECT to change password”. If you wish to change the password at this time, see the “Change Password” section below. Otherwise, depress the UP key to advance to the EDIT and AUTOTUNE menus.
Entering the correct Password allows the user 20 minute access to the EDIT and AUTOTUNE menus. Changing any parameter will re-start this 20 minute time-out period.
Change Password
The user may change the password (the factory set password is “0205”) to any four-digit code desired. To change the password, you first enter the current password as described above.
When the display reads “Valid Password. Press SELECT to change password”, press the SELECT key and “0xxx NEW” is displayed, the first digit (“0”) is adjustable. For example, enter a NEW password of “1357”. Use the UP/DOWN key and the PROGRAM key (as described in the above section) to enter the new password. When complete, in this example the display will now read “New password 1357”. Depress the UP/DOWN keys to return to the menu loops.
Signal Strength & Flame Quality (FQ), Expanded Description
Single sensor models (Type 95IR, 95UV): The value of Signal Strength is the same as the “Flame
Quality” number except that the Signal Strength value is allowed to exceed 100 (maximum of 999) while “Flame Quality” is capped at 100.
Dual sensor models (Type 95DS): This screen shows the individual sensor’s contribution to the
Flame Quality number. Each value is preceded by the corresponding lower case letter indicating whether it is the IR (i) or UV (u) sensor. Under most firing conditions, the sum of these individual values will exceed 100 (maximum of 999).
Important Note: The Flame Quality number is the Flame Signal number, but is capped at 100. In dual sensor (95DS) models, it is the sum of the IR + UV Signal Strength numbers, but the sum is capped at 100.
Example 1 (Single Sensor Model 95IR, infrared):
If “I 80” is displayed as signal strength, you would see a Flame Quality number of “FQ 80” displayed on the Flame Quality screen.
If “I 120” is displayed as signal strength, you would see a Flame Quality number of “FQ 100” on the
Flame Quality screen, because Flame Quality is capped at 100.
Example 2 (Dual Sensor Model 95DS):
If “i80 u15” is displayed as signal strength, you would see a Flame Quality number (the IR and UV signal sum) of “FQ 95” displayed on the Flame Quality screen.
If “i70 u 40” is displayed as signal strength, although the sum is 110, you would see a Flame Quality number of “FQ 100” on the Flame Quality screen, because Flame Quality is capped at 100.
THE EDIT MENU
FIGURE 21.
EDIT MENU LOOP
UP Key (Scrolls through menu, clockwise)
DOWN Key (Scrolls through menu, counter clockwise)
SELECT Key
PROGRAM Key
IR RANGE
IR GAIN
IR BAND
SENSORS
LANGUAGE
FILE COPY
REMOTE FILE SELECT
COMM ADDRESS
TEMPERATURE SCALE
FILE SELECT
IRR HIGH iG1/0 i 70/0
UV & IR
ENGLISH
A
RFS KEY
COMM O
SCALE C
FILE A
UV BAND
UV GAIN
UV RANGE
ON THRESHOLD
OFF THRESHOLD
FFRT
OTD
--EXIT--
P u70/0 uG1/0
UVR HIGH
ONT 40
OFFT 20
FFRT 1
OTD 1
FROM “EDIT”
ON STATUS MENU
LOOP
NOTE 1: Dual Scanner model shown. If scanner is single sensor model (IR of UV) only the appropriate parameter will be displayed (e.g.
SENSORS, BAND, GAIN, RANGE).
NOTE 2: Communications available with “S2” models only.
NOTE 3: The PROGRAM Key is used to accept a value change for all parameters except IR/UV Gain and IR/UV Band. For these parameters, the value change is accepted immediately.
25
FIGURE 22.
THE EDIT MENU
File Select
TEXT DISPLAYED
FILE A
DEPRESS ‘SELECT’ KEY, TEXT DISPLAYED
Temperature Scale
Comm address
Remote File Select
File Copy
Language
Sensors
IR Band
Scale C
COMM 0
RFS KEY
A-> (See File Copy Section)
English
UV + IR (Dual Sensor Models Only) i70/ 0 (IR Frequency selected/Signal strength)
POSSIBLE VALUES (UP/DOWN KEYS)
“S1” models: A.B
“S2” models: A.B, C, D
C, F
0-127
“S1” models: KEY, LINE
“S2” models: KEY, LINE, COMM
IR Gain
IR Range
UV Band
UV Gain
UV Range
On Threshold
Off Threshold
FFRT
OTD
--EXIT-iG1 / 0 (IR Gain selected/ Signal strength)
IRR HIGH u70/ 0 (UV Frequency selected/Signal strength) uG1 / 0 (UV Gain selected/ Signal strength)
UVR HIGH
ONT 40
OFFT 20
FFRT 1
OTD 1
Edit (Returns you to STATUS loop)
English
UV + IR, IR Only, UV Only
“S1” Models: 23, 70, 117
“S2” Models: 23, 31, 39, 46, 54, 62, 70,
78, 85, 93, 101, 109, 117, 125, 132, 140,
148, 156, 164, 171, 179 Hz
1 - 31
HIGH, LOW
“S1” Models: 23, 70, 117
“S2” Models: 23, 31, 39, 46, 54, 62, 70,
78, 85, 93, 101, 109, 117, 125, 132, 140,
148, 156, 164, 171, 179 Hz
1 - 31
HIGH, LOW
5 - 100
0 - 95
1, 2, 3, 4, 5, 6 seconds
1, 2, 3, 4, 5, 6 seconds
THE EDIT MENU
The values of the menu choices are viewed by pressing the SELECT button. (To exit the viewed value without changing it, press the SELECT button again). To change a value, press the UP /
DOWN keys until the desired value is displayed. Depress the PROGRAM button. The display will scroll “Parameter saved”, then automatically de-select the menu choice as if the SELECT button had been pressed. See important note below.
IMPORTANT NOTE:
In order to immediately see the effect of a setpoint change upon the “Signal Strength” number, some parameter values are changed and saved immediately via the UP / DOWN keys, and do not require depressing the PROGRAM key. These parameters include IR Band, UV Band, IR Gain, and UV
Gain. The “Signal Strength” number is displayed to the right of the parameter value on the same screen, providing the user instantaneous feedback.
Note: You may only Edit the File that the scanner is currently running. For example, to Edit file
“B”, you must be currently running file “B”. (See File Select section below).
Exceptions: A change made to the Temperature Scale, Comm Address, Remote File Select, and
Language parameters, can be made in any file and the new values will be automatically saved to all files.
26
File Select
The user can manually choose which file to run (and to Edit) by selecting this menu choice provided
the Remote File Select “KEY” choice is selected (see below). If the user wants to Edit the contents of a file, they must first select and run that particular file. (See “exceptions” in note above).
Temperature Scale
(Affects all files)
The scale may be selected to be Fahrenheit “F”, or Celsius “C”.
Comm Address (“S2” Models Only)
(Affects all files)
The communications address selected may range from 0 to 127. Each scanner must have a unique address. No two scanners in a communications loop can have the same address.
Remote File Select
(Affects all files)
Choices are KEY, LINE, COMM*
KEY allows the file selection to be made only at the scanner keypad
(See File Select menu choice above).
LINE allows the file selection to be made only via an external switch or relay.
COMM allows the file selection to be made only via an external computer running Fireye Software.
This feature is only available with FM & CSA approved “S2” models. This feature is not available with CE approved “S2E” models.
FileCopy
This function allows the user to copy the contents of one internal scanner file to another. “S1” Models have two user configurable files, “A,B”, plus two factory configured files, “F1, F2”. “S2” Models add two additional user files, “C, D”.
You may copy from any file to a user file. You are not allowed to copy from a user file to a factory file.
You must first enter the source file, then the destination file (Refer to FileCopy instructions at the end of this section).
The Factory Configured Files (“F1” and “F2”) contain factory default settings.
In File “F1”, the sensor gain is set at maximum (31) and the flicker frequency is set at 23 Hz. At
these settings the scanner will respond to flame but will not likely discriminate between the target flame and other nearby flames.
In File “F2”, the sensor gain is set at minimum (1) and the flicker frequency is set at 70 Hz. At
these settings the scanner will not likely respond to flame until the scanner gain is increased.
Note: As shipped, all user files (A,B,C,D) contain the same setpoints as factory file “F2”.
Language
(Affects all files)
This allows the user to select which language the menu system will use. The available choice is
“English”.
Sensors (dual sensor units only, Type 95DS)
Choices include: UV only, IR only, or UV+IR
This parameter is used to manually select which sensor(s) are used in a particular file.
IR Band
The display is broken into two halves. The left side displays the selected IR flicker frequency (bandpass). The right side displays the signal strength attributed to the IR sensor.
27
28
For example with a model “S2” scanner, “i 23 / 80” indicates that 23Hz is selected and the current signal strength is 80 (as viewed in the Status loop).
Frequency choices range from 23Hz to 179Hz (“S2” models), or from 23Hz, 70Hz, 117Hz (“S1” models). The signal strength number can range from 0-999.
Note: Remember that while the signal strength number can range to 999, the “Flame Quality” number viewed in the Status menu is capped at 100. In dual sensor models the “Flame Quality” number is the sum of the IR and UV sensor signal strengths, capped at 100.
Pressing the UP and DOWN keys changes the frequency displayed and immediately stores the value
(pressing the PROGRAM key is not required). The user will immediately see the effect on the signal strength number displayed on the right side of the display.
IR Gain
The display is broken into two halves. The left side displays the selected IR Gain. The right half displays the signal strength attributed to the IR sensor.
The IR sensor Gain is selectable from 1 (lowest) to 31 (highest). The signal strength number can range from 0-999.
Note: Remember that while the signal strength number can range to 999, the “Flame Quality” number viewed in the Status menu is capped at 100. In dual sensor models the “Flame Quality” number is the sum of the IR and UV sensor signal strengths, capped at 100.
Pressing the UP and DOWN keys changes the IR Gain displayed and immediately stores the value
(pressing the PROGRAM key is not required). The user will immediately see the effect on the signal strength number displayed on the right side of the display. See MANUAL ADJUSTMENT note at the end of this section.
IR Range
There are two selectable internal “ranges” for the IR sensor Gain, “High” and “Low”. If, when “Aiming” the scanner, a flashing IR number is observed, then the signal is over-range and the “Range” should be set to “LOW”. If, when “Aiming” the scanner, an IR number of less than 10 is observed, then the gain Range should be set to “HIGH”.
UV Band
The display is broken into two halves. The left side displays the selected UV flicker frequency (bandpass). The right side displays the signal strength attributed to the UV sensor.
For example with a model “S2” scanner, “u 23 / 80” indicates that 23Hz is selected and the current signal strength is 80 (as viewed in the Status loop).
Frequency choices range from 23Hz to 179Hz (“S2” models), or from 23Hz, 70Hz, 117Hz (“S1” models). The signal strength number can range from 0-999.
Note: Remember that while the signal strength number can range to 999, the “Flame Quality” number viewed in the Status menu is capped at 100. In dual sensor models the “Flame Quality” number is the sum of the IR and UV sensor signal strengths, capped at 100.
Pressing the UP and DOWN keys changes the frequency displayed and immediately stores the value
(pressing the PROGRAM key is not required). The user will immediately see the effect on the signal strength number displayed on the right side of the display.
UV Gain
The display is broken into two halves. The left side displays the selected UV Gain. The right half displays the signal strength attributed to the UV sensor.
The UV sensor Gain is selectable from 1(lowest) to 31(highest). The signal strength number can range from 0-999.
Note: Remember that while the signal strength number can range to 999, the “Flame Quality” number viewed in the Status menu is capped at 100. In dual sensor models the “Flame Quality” number is the sum of the IR and UV sensor signal strengths, capped at 100.
Pressing the UP and DOWN keys changes the UV Gain displayed and immediately stores the value
(pressing the PROGRAM key is not required). The user will immediately see the effect on the signal strength number displayed on the right side of the display. See MANUAL ADJUSTMENT note at the end of this section.
UV Range
There are two selectable internal “ranges” for the UV sensor Gain, “High” and “Low”. If, when
“Aiming” the scanner, a flashing UV number is observed, then the signal is over-range and the
“Range” should be set to “LOW”. If, when “Aiming” the scanner, a UV number of less than 10 is observed, then the gain Range should be set to “HIGH”.
On Threshold
This refers to the “pull-in” threshold of the internal Flame Relay, in terms of “Flame Quality”. The
ON Threshold can be set from 5 to 100. The ON Threshold must be at least 5 units higher than the
OFF Threshold.
When the Flame Quality is equal to or greater than the ON Threshold (for a time equal to the “On
Time Delay setting, see below), the flame relay will energize.
Off Threshold
This refers to the “drop-out” threshold of the internal Flame Relay, in terms of “Flame Quality”. The
OFF Threshold can be set from 0 to 95. The OFF Threshold must be at least 5 units lower than the
ON Threshold.
When the Flame Quality is equal to or less than the OFF Threshold (for a time equal to the “Flame
Failure Response Time” setting, see below), the flame relay will de-energize.
FFRT
When the Flame Quality drops to or below the Flame Relay OFF Threshold, the Flame relay will deenergize after the selected Flame Failure Response Time (FFRT). The choices range from 1 to 6 seconds. The maximum allowable FFRT setting is determined by local safety code, and is factory selected at 1 second.
OTD
When the Flame Quality rises to or above the Flame Relay ON Threshold, the Flame relay will energize after the selected On Time Delay (OTD). The choices, range from 1 to 6 seconds.
--EXIT--
Pressing the SELECT key will return the user to the “Edit” display in the Status menu.
FILE COPY INSTRUCTIONS
You may copy from any file to a user file. You are not allowed to copy from a user file to a factory file,
(refer to FileCopy description earlier in this section). You must first select the source file, then select the destination file.
With “FileCopy” displayed (EDIT menu), depress the SELECT key. The display will read “A➔” with “A” being the source file. Use the UP/DOWN keys to select a different source file if desired.
With the desired source file displayed, press the PROGRAM key. The arrow will flash and the destination file will appear (e.g. “A ➔ A”). Initially the destination is displayed is “A”. Use the UP/
DOWN keys to select the desired destination file (e.g. “A ➔ B”).
Press the PROGRAM key to copy the source file to the destination file. The display will read “File
Copied”. (Pressing the SELECT key at any time before pressing the PROGRAM key for the second time will cancel the operation.)
Press the UP/DOWN keys to scroll through the EDIT loop.
29
Manual Adjustment of IR or UV Gain
When manually adjusting the IR and / or UV “Gain” in the EDIT loop, the display will show both the selected gain (1-31), and the Signal Strength (Sensor Flame Quality) number (0-999) associated with either the IR or UV sensor, e.g. “iG30 / 80”, “uG12 / 40”. (In this case, the total Flame Quality is
“120”, and the FQ number viewed in the Status loop would be 100 [capped at 100]).
Each increment of the gain will increase the Signal Strength (Sensor Flame Quality) number for the selected sensor by 50%. In the above example, changing the UV sensor gain from 12 to 13 would increase the UV Signal Strength from 40 to 60. Decreasing the IR sensor gain from 30 to 29 would decrease the IR Signal Strength from 80 to 53. (In this case, the total Flame Quality is “103”, and the
FQ number as viewed in the Status loop would be 100 [capped at 100]).
For best scanner operation, the Flame ON Flame Quality number (IR Signal Strength + UV
Signal Strength) should be between 100 and 150 even though the Flame Quality display (Status loop) is capped at 100.
Error Messages
In the event that an internal scanner fault is detected, the scanner will turn off its output and a four digit error code will appear on the display. If the scanner’s internal temperature exceeds 80°C
(176°F), the scanner will turn off its output and “Too HOT!” will appear on the display.
To clear the error code and re-start the scanner, the 24 vdc power must be cycled off then on.
When power is applied to a scanner that had experienced a fault, the display will read “Errors” followed by several digits indicating the scanner’s error history. Pressing any key will clear this message.
30
THE PRE-EDIT MENU (“S1” Models only)
FIGURE 23.
THE PRE-EDIT MENU LOOP (“S1” Models Only)
Keypad Legend
UP Key (Scrolls through menu, clockwise)
DOWN Key (Scrolls through menu, counter clockwise)
SELECT Key
PROGRAM Key
SET FEG
RUN FLAME AT
LOWEST SETTING
AND PRESS PROGRAM
IO UO
AIM SCANNER
--EXIT--
FEG IS SET
FROM “PRE-EDIT”
ON STATUS MENU
THE PRE-EDIT MENU (“S1” Models Only) FIGURE 24.
Aim Scanner
Set FEG
--Exit--
TEXT DISPLAYED DEPRESS “SELECT” KEY
TEXT DISPLAYED
I0 U0
(Possible values 0-60)
Run flame at lowest setting and press
PROGRAM
Pre-Edit (Returns you to STATUS loop)
DEPRESS “PROGRAM” KEY
TEXT DISPLAYED
FEG is set
Pre-Edit is an automatic calibration function whereby the scanner sets an appropriate internal frontend gain (FEG) level. The appropriate choice of modulation BAND (flame flicker frequency), and sensor GAIN is later manually set up in the EDIT menu.
Pre-Edit and Manual Set-up is performed in 3 steps:
1.
In the PRE-EDIT menu, run the target flame at the low firing rate and physically aim the scanner for peak signal strength (as observed at the “Aim Scanner” prompt). Depress the Program key at the “Set FEG” prompt and the scanner will set an appropriate internal front-end gain
(FEG) level.
31
2.
In the EDIT menu, observe and record the flame ON and flame OFF sensor signal strength and stability at each of the three modulation bands. Select the modulation band that yields the greatest Flame ON to Flame OFF signal ratio and/or yields the greatest stability.
3.
Adjust the sensor GAIN and flame relay ON and OFF thresholds for reliable on/off operation.
Aim Scanner
When SELECT is depressed, “Ix Ux” is displayed (dual sensor models). The value of “x” may range from 0 to 60. The value displayed represents the flame flicker intensity of the flame for the entire
flicker frequency spectrum as individually sensed by the UV (U) sensor and/or IR (I) sensor(s).
The numbers should be at their peak (highest numerically) when the scanner is aimed at the primary combustion zone (first 1/3) of the flame. If the scanner is equipped with both an IR and UV sensor, priority should be given to maximizing the UV intensity.
Run the flame at low fire rate and observe the signal intensity.
Physically aim the scanner at the first 1/3 of the flame to maximize the intensity reading. (Allow the scanner reading to stabilize two seconds after each movement.)
If the reading is l0 or less, the intensity is marginal. Verify that the appropriate sensor “Range” parameter (IR Range or UV Range) in the Edit menu is set to “HIGH”.
If the reading is greater than 26 (the number will blink) the signal is excessive. Verify that the appropriate sensor “Range” parameter (IR Range or UV Range) in the Edit menu is set to “LOW”.
Set FEG
Run the flame at low fire and press the PROGRAM button. The scanner will set an appropriate internal front-end gain (FEG) level based upon the flame intensity (brightness) then display “FEG is set”.
--EXIT--
Pressing the SELECT key will return the user to the “Pre-Edit” menu choice of the main status menu.
Manual Set-up in Edit menu (“S1” Models only)
In the EDIT menu with the target flame ON (at low fire), observe and record the sensor signal
strength and stability at each of the three modulation BANDS: 23, 70, and 117 Hz. The signal strength display has a range of 0-999.
During set-up it may be necessary to adjust the sensor GAIN in order to keep the signal strength value on scale. If so, observe and record the sensor GAIN value (1-31) selected.
With dual sensor models, perform this step for each sensor.
In the EDIT menu with the target flame OFF (leaving other burners firing), observe and record the
sensor signal strength and stability at each of the three modulation BANDS: 23, 70, and 117 Hz. Do
not adjust the sensor GAIN at this time.
With dual sensor models, perform this step for each sensor.
At each of the three modulation frequencies, compare the recorded Flame ON signal strength
to the recorded Flame OFF signal strength. Select the modulation BAND that yielded the greatest
Flame ON to Flame OFF signal ratio and/or yielded the greatest stability.
With dual sensor models, perform this step for each sensor.
Adjust the sensor gain (1-31) so that the flame ON signal strength is well above the flame relay ON
threshold, and the flame OFF signal strength is well below the flame relay OFF threshold (see
“Flame Relay Thresholds” below).
When manually adjusting the IR and / or UV “Gain” in the EDIT loop, the display will show both the selected gain (1-31), and the Signal Strength (Sensor Flame Quality) number (0-999) associated with either the IR or UV sensor, e.g. “iG30 / 80”, “uG12 / 40”. (In this case, the total Flame Quality is
“120”, and the FQ number viewed in the Status loop would be 100 [capped at 100]).
32
Each increment of the gain will increase the Signal Strength (Sensor Flame Quality) number for the selected sensor by 50%. In the above example, changing the UV sensor gain from 12 to 13 would increase the UV Signal Strength from 40 to 60. Decreasing the IR sensor gain from 30 to 29 would decrease the IR Signal Strength from 80 to 53. (In this case, the total Flame Quality is “103”, and the
FQ number as viewed in the Status loop would be 100 [capped at 100]).
For best scanner operation, the Flame ON Flame Quality number (IR Signal Strength + UV
Signal Strength) should be between 100 and 150 even though the Flame Quality display (Status loop) is capped at 100.
Example:
At the selected BAND the Flame ON signal ranged from 800 to 999, and the Flame OFF signal ranged from 50 to 130 (a 6:1 on/off ratio).
The user must reduce the sensor gain so that flame ON signal strength is well above the flame relay
ON threshold (factory programmed at 40), and the flame OFF signal strength is well below the flame relay OFF threshold (factory programmed at 20).
In this example, the user may reduce the gain to have a flame OFF signal of 0, and a flame ON signal of 150.
Special Note for Dual Sensor Models:
With dual sensor models, the flame relay and 4-20 mA output will operate on the SUM of both the IR and UV signals. When setting the final GAIN adjustments, the user should favor the sensor (IR or
UV) which exhibited the greatest flame ON:OFF signal ratio, and/or greatest stability.
If the user chooses to use the input from only one sensor and disable the input from the other, he may do so by selecting “IR ONLY” or “UV ONLY” as Sensors in the Edit menu.
Flame Relay Thresholds
The flame relay has a factory programmed FLAME ON threshold of 40, and a FLAME OFF threshold of 20 (0-100 scale). With these settings, it is recommended that the flame ON signal normally be at least 150. Other on and off thresholds may be selected to suit particular applications.
CAUTION: After selecting Sensor TYPE, Sensor BAND, Sensor GAIN, and Flame Relay
ON & OFF Thresholds, proper flame detection and flame discrimination must be verified by starting and stopping the burner several times. The flame relay must reliably de-energize for all flame out conditions. This testing should be done with various adjacent burners on and off, and at various load levels. This is a requirement for proper operation.
33
THE AUTOTUNE MENU (“S2” Models only)
FIGURE 25.
Keypad Legend
THE AUTOTUNE MENU LOOP (“S2” Models only)
UP Key (Scrolls through menu, clockwise)
DOWN Key (Scrolls through menu, counter clockwise)
SELECT Key
PROGRAM Key
LEARN OFF
TURN FLAME OFF
AND PRESS PROGRAM
LEARN ON
AIM SCANNER
RUN FLAME AT
LOWEST SETTING
AND PRESS PROGRAM
IO UO
WAIT 128 ➔ 0
LEARN OFF
COMPLETE
WAIT 128 ➔ 0
LEARN ON
COMPLETE
--EXIT--
TO “AUTOTUNE”
ON STATUS MENU
LOOP
FIGURE 26.
THE AUTOTUNE MENU (“S2” Models Only)
Aim Scanner
TEXT DISPLAYED DEPRESS “SELECT” KEY
TEXT DISPLAYED
I 0 U 0
(Possible Values 0-60)
Run Flame at Lowest setting and press
PROGRAM
DEPRESS “PROGRAM” KEY
TEXT DISPLAYED
Learn On
LearnOff (only displayed if Learn ON had been performed)
--Exit--
Turn Flame OFF and press PROGRAM
WAIT 128 – 0
(Counts down to 0 within 20 seconds, then displays “Learn OFF complete“)
WAIT 128 – 0
(Counts down to 0 within 20 seconds, then displays “Learn OFF complete”)
AutoTune (Returns you to STATUS loop)
AutoTune is an automatic calibration function whereby the InSight scanner scans the flame flicker frequency spectrum with flame ON, and with flame OFF (background radiation present). The scanner will then select the appropriate sensor gain, bandpass frequency, and sensor range for optimum flame ON: OFF discrimination. The scanner will also select the optimum Flame Relay ON and OFF thresholds.
34
AutoTune is performed in 3 steps:
1.
Run the target flame at the low firing rate and physically aim the scanner for peak signal strength
(as observed at the “Aim Scanner” prompt).
2.
Depress the “Program” key and the scanner will memorize the flame ON condition.
3.
Turn the target flame OFF (while leaving other burners firing), and depress the “Program” key.
The scanner will memorize the flame OFF condition and select the appropriate internal setpoints.
Aim Scanner
When SELECT is depressed, “Ix Ux” is displayed (dual sensor models). The value of “x” may range from 0 to 60. The value displayed represents the flame flicker intensity of the flame for the entire
flicker frequency spectrum as individually sensed by the UV (U) sensor and/or IR (I) sensor(s).
The numbers should be at their peak (highest numerically) when the scanner is aimed at the primary combustion zone (first 1/3) of the flame. If the scanner is equipped with both an IR and UV sensor, priority should be given to maximizing the UV intensity.
Run the flame at low fire rate and observe the signal intensity.
Physically aim the scanner at the first 1/3 of the flame to maximize the intensity reading. (Allow the scanner reading to stabilize two seconds after each movement.)
If the reading is l0 or less, the intensity is marginal. Verify that the appropriate sensor “Range” parameter (IR Range or UV Range) in the Edit menu is set to “HIGH”.
If the reading is greater than 26 (the number will blink) the signal is excessive. Verify that the appropriate sensor “Range” parameter (IR Range or UV Range) in the Edit menu is set to “LOW”.
Learn ON
Run the flame at low fire and press the PROGRAM button. The scanner will display “Wait” followed by a number that will count down from 128 to 0 in about 20 seconds. This will temporarily store the spectrum of the monitored flame and the adjacent flames. The front-end gain number, used in the
ON/OFF calculation, will be stored at this time.
Learn Off
Turn off the monitored flame leaving adjacent flames operating, then press the PROGRAM button.
The scanner will display “Wait” followed by a number that will count down from 128 to 0 in about
20 seconds. This will temporarily store the spectrum of the adjacent flames.
The “ON” spectrum will then be compared to the “OFF” spectrum and the frequency and gain for optimum discrimination will be selected.
The IR and UV gain settings will be automatically selected based on the proportionality of their flame ON: OFF ratios. (On dual sensor models, the contribution of the IR and UV signal strengths to the Flame Quality is also determined at this time by the selection of their respective gain numbers.
The gain settings will be selected to yield a total “signal strength” of between 100 and 150, which would yield a Flame Quality number of 100.
The Flame relay ON and OFF thresholds will be automatically set to 40 and 20, respectively, unless the “off” signal level is exceptionally high, which usually indicates poor aiming of the scanner.
Note: If after learning flame OFF, an insufficient on/off ratio is not found in at least one sensor, the display will show, “Warning: Poor discrimination, try re-aiming scanner”.
--EXIT--
Pressing the SELECT key will return the user to the “AutoTune” menu choice of the main menu.
35
CAUTION: After selecting Sensor TYPE, Sensor BAND, Sensor GAIN, and Flame
Relay ON & OFF Thresholds, proper flame detection and flame discrimination must be verified by starting and stopping the burner several times. The flame relay must reliably de-energize for all flame out conditions. This testing should be done with various adjacent burners on and off, and at various load levels. This is a requirement for proper operation.
ORDERING INFORATION
PART NUMBER STRUCTURE
TYPE
95= Integrated (internal flame relay)
SENSOR
IR= Solid state infrared
UV= Solid state ultraviolet
MODEL
S1= Basic features, FM&CSA, 220
Vac contact rating.
S1E= Basic features, CE, 50 Vac contact rating.
HOUSING
-1= NEMA 4X/IP66 housing, 12 pin electrical connector
DS= Dual sensor, IR + UV S2= Expanded features, FM& CSA,
220 Vac contact rating, “Remote
Command” user software.
S2E= Expanded features, CE, 50
Vac contact rating, “Read Only” user Software.
Example 1
To select the Fireye equipment meeting the following specification:
“Integrated Insight scanner, dual sensor, expanded features, CSA & FM approved, surface mounted
NEMA 4X/IP66 enclosure with male electrical connector. Accessories to include 1" NPT mounting flange, 100 feet of 12-conductor cable, and female electrical connector kit”
Order the following:
1
1
100 feet
1
QUANTITY PART NUMBER
95DSS2-1
60-2692
59-497
129-164
DESCRIPTION
InSight Scanner, Dual Sensor
1" NPT mounting flange kit
12-Conductor cable
Female electrical connector kit
36
1
1
1
Example 2
To select the Fireye equipment meeting the following specification:
“Integrated Insight scanner, ultraviolet sensor, basic features, CE approved, surface mounted
NEMA 4X/IP66 enclosure with male electrical connector. Accessories to include 1" BSP mounting flange, 12-conductor cable assembly 100 feet long with factory installed female electrical connector”
Order the following:
QUANTITY PART NUMBER
95UVS1E-1
60-2693
59-497-100
DESCRIPTION
InSight Scanner, Ultraviolet
1" BSP mounting flange kit
12-Conductor cable assembly,
100 feet with installed connector
37
38
39
NOTICE
When Fireye products are combined with equipment manufactured by others and/or integrated into systems designed or manufactured by others, the Fireye warranty, as stated it its General Terms and
Conditions of Sale, pertains only to the Fireye products and not to any other equipment or to the combined system or its overall performance.
WARRANTIES
FIREYE guarantees for one year from the date of installation or 18 months from date of manufacture of its products to replace, or, at its option, to repair any product or part thereof (except lamps, electronic tubes and photocells) which is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order. THE FOREGOING
IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE MAKES NO WARRANTY OF
MERCHANTABILITY OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED. Except as
specifically stated in these general terms and conditions of sale, remedies with respect to any product or part number manufactured or sold by Fireye shall be limited exclusively to the right to replacement or repair as above provided. In no event shall Fireye be liable for consequential or special damages of any nature that may arise in connection with such product or part.
FIREYE
3 Manchester Road
Derry, New Hampshire 03038 www.fireye.com
CU-95
NOVEMBER 2000
40

Public link updated
The public link to your chat has been updated.
Advertisement
Key features
- Micro-processor based
- Solid state IR or UV or dual sensors
- Internal flame relay
- Adjustable ON/OFF thresholds
- Single or multi-burner applications
- Automatic programming
- Remote communication capability