Allen-Bradley ControlNet PCI 1784-PCICS Installation Instructions Manual
Advertisement
Advertisement
ControlNet
Universal PCI
Communication
Interface Card
1784-PCIC, 1784-PCICS
Series B
Installation
Instructions
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment.
Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication
SGI-1.1, available from your local Rockwell Automation sales office or online at http://www.literature.rockwellautomation.com)
describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc. is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT
ATTENTION
SHOCK HAZARD
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you:
• identify a hazard
• avoid a hazard
• recognize the consequence
Labels may be located on or inside the drive to alert people that dangerous voltage may be present.
BURN HAZARD
Labels may be located on or inside the drive to alert people that surfaces may be dangerous temperatures.
Chapter 1
Install the 1784-PCIC or 1784-PCICS Communication Interface
Card
European Hazardous Location Approval (1784-PCIC only) . . . . . 1-3
European Zone 2 Certification. . . . . . . . . . . . . . . . . . . . . . . 1-3
North American Hazardous Location Approval . . . . . . . . . . . . . 1-4
Access the Computer’s PCI Local Bus Expansion Slots . . . . . . . . 1-5
Insert the Card Into the Computer. . . . . . . . . . . . . . . . . . . . . . . 1-6
Connect to the Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
Connect the Card Directly to the ControlNet Network . . . . . . . . 1-9
Connect to a Device on the ControlNet Network . . . . . . . . . . . 1-10
Chapter 2
Install the Driver in Windows XP
Install the Driver in Windows XP for the First Time . . . . . . . . . 2-1
Update the Existing Driver in Windows XP . . . . . . . . . . . . . . . . 2-3
Chapter 3
Install the Driver in Windows 2000
Install the Driver in Windows 2000 for the First Time. . . . . . . . . 3-1
Update the Existing Driver in Windows 2000. . . . . . . . . . . . . . . 3-4
Chapter 4
Install the Driver in Windows 98/Me
Install the Driver in Windows 98/Me for the First Time . . . . . . . 4-1
Install the Virtual Backplane Driver . . . . . . . . . . . . . . . . . . . . . . 4-3
Update the Existing Driver in Windows 98/Me . . . . . . . . . . . . . 4-5
Publication 1784-IN003D-EN-P - January 2006
ii Table of Contents
Chapter 5
Once You Have Completed the Installation
Register the EDS File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Connect a SoftLogix Controller to the ControlNet Network . . . . . 5-4
Go Online With RSNetWorx for ControlNet Software . . . . . . . . . 5-7
Interpret the LED Indicators
Chapter 6
Chapter 7
Specifications
Index
Publication 1784-IN003D-EN-P - January 2006
Chapter
1
Install the 1784-PCIC or 1784-PCICS
Communication Interface Card
For Information On This Topic
Access the Computer’s PCI Local Bus Expansion Slots
Insert the Card Into the Computer
Connect the Card Directly to the ControlNet Network
Connect to a Device on the ControlNet Network
See Page
Before you install the card, be certain that you:
• know how to install hardware in your computer.
• consult your computer’s documentation for hardware installation instructions.
TIP
Installation instructions for both the 1784-PCIC and 1784-PCICS cards are exactly the same. In most illustrations, the 1784-PCIC card is shown.
Refer to the following publications for more information:
•
ControlNet Coax Media Planning and Installation, publication CNET-IN002
•
ControlNet Communication Modules in Logix5000 Control Systems, publication CNET-UM001
•
SoftLogix5800 System User Manual, publication 1789-UM002
Publication 1784-IN003D-EN-P - January 2006
1-2 Install the 1784-PCIC or 1784-PCICS Communication Interface Card
ATTENTION
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as open type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
NOTE: See NEMA Standards publication 250 and IEC publication
60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. Also, see the appropriate sections in this publication, as well as the Industrial Automation
Wiring and Grounding Guidelines, Allen-Bradley publication
1770-4.1, for additional installation requirements pertaining to this equipment.
ATTENTION
Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
•
Touch a grounded object to discharge potential static
•
Wear an approved grounding wriststrap
•
Do not touch connectors or pins on component boards
•
Do not touch circuit components inside the equipment
•
Use a static-safe workstation, if available
•
Store the equipment in appropriate static-safe packaging when not in use.
Publication 1784-IN003D-EN-P - January 2006
Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-3
European Hazardous Location Approval (1784-PCIC only)
European Zone 2 Certification
The following applies when the product bears the EEx Marking:
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC.
The LCIE (Laboratoire Central des Industries Electriques) certifies that this equipment has been found to comply with the Essential Health and Safety
Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres, given in Annex II to this
Directive. The examination and test results are recorded in confidential report No.
28 682 010.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 50021.
IMPORTANT
This equipment is not resistant to sunlight or other sources of UV radiation.
The secondary of a current transformer shall not be open-circuited when applied in Class I, Zone 2 environments.
Equipment of lesser Enclosure Type Rating must be installed in an enclosure providing at least IP54 protection when applied in Class
I, Zone 2 environments.
This equipment shall be used within its specified ratings defined by Allen-Bradley.
Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40% when applied in Class I, Zone 2 environments.
Publication 1784-IN003D-EN-P - January 2006
1-4 Install the 1784-PCIC or 1784-PCICS Communication Interface Card
North American Hazardous Location Approval
The following information applies when operating this equipment in hazardous locations:
Informations sur l’utilisation de cet équipement en environnements dangereux:
Products marked CL I, DIV 2, GP A, B, C, D are suitable for use in Class I Division 2 Groups A, B, C, D,
Hazardous Locations and nonhazardous locations only.
Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest T number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
Les produits marqués CL I, DIV 2, GP A, B, C, D ne conviennent qu’à une utilisation en environnements de
Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d’identification qui indiquent le code de température pour les environnements dangereux.
Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable
(code de température le plus faible) peut être utilisé pour déterminer le code de température global du système.
Les combinaisons d’équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l’installation.
AVERTISSEMENT
RISQUE D’EXPLOSION
WARNING
EXPLOSION HAZARD
•
Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
•
Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous.
Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
•
Substitution of components may impair suitability for
Class I, Division 2.
•
If this product contains batteries, they must be changed only in an area known to be nonhazardous.
•
Couper le courant ou s’assurer que l’environnement est classé non dangereux avant de débrancher l'équipement.
•
Couper le courant ou s'assurer que l’environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
•
La substitution de composants peut rendre cet équipement inadapté
à une utilisation en environnement de Classe
I, Division 2.
•
S’assurer que l’environnement est classé non dangereux avant de changer les piles.
Publication 1784-IN003D-EN-P - January 2006
Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-5
To install the card, you need to:
• access the computer’s expansion slots.
• insert the card into the computer.
IMPORTANT
The card’s dimensions are shown below.
6.5 in.
16.5 cm
4.2 in.
10.7 cm
31474-M
Access the Computer’s PCI Local Bus Expansion Slots
To install the card, you must access the computer’s PCI local bus expansion slots.
Follow these general steps, or refer to your computer’s user guide for further instructions.
1. Shut down the host computer.
2. Remove the computer’s cover.
3. Select a vacant PCI local bus expansion slot.
4. Loosen the screw (if present) on the back (rear bracket) of the computer.
5. Remove the slot’s expansion cover.
Publication 1784-IN003D-EN-P - January 2006
1-6 Install the 1784-PCIC or 1784-PCICS Communication Interface Card
Insert the Card Into the Computer
WARNING
When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes.
If you insert or remove the card while host power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
1. Handle the card so that you prevent electrostatic discharge.
Refer to the Preface of this manual for more information.
2. Insert the card into the edge connector and tighten the expansion slot screw
(if present).
3. Replace the computer cover.
4. Turn on the computer to be certain that it comes up correctly.
If the Computer
Turns on
Hangs up
Then
Go to to the next section, Connect to the Network
Either the card is not seated correctly in the PCI slot or you have a memory or I/O conflict. You should:
•
remove and reinsert the card into the same PCI slot and try again
• remove and reinsert the card into a different PCI slot and try again
•
remove all other non-essential cards and try again
If you continue to experience difficulty, contact your local
Rockwell Automation sales representative or distributor, or call
Rockwell Automation Technical Support at 440.646.5800.
Publication 1784-IN003D-EN-P - January 2006
Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-7
Connect to the Network
WARNING
When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes.
If you connect or disconnect the ControlNet cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
After you have installed the card, you can connect it:
•
directly to a ControlNet network, which requires a tap (page 1-9).
•
to a device already connected to the ControlNet network (page 1-10).
See Figure 1.1 on page 1-8 for the connectors and indicators.
Publication 1784-IN003D-EN-P - January 2006
1-8 Install the 1784-PCIC or 1784-PCICS Communication Interface Card
Figure 1.1 1784-PCIC or 1784-PCICS Card (1784-PCIC Card Shown)
Diagnostic Status
Indicators
!
Network Access Port (NAP)
RJ-45 connector for connecting programming terminals to devices on a ControlNet network
Channel A
BNC connectors for connecting directly to
ControlNet network
Redundant Media
BNC Connectors
!
A
!
B
Allen-Bradley
1784-PCIC
ControlNet
!
Channel B
Do not connect more than one
ControlNet network to this card.
42281
ATTENTION
Do not connect different ControlNet networks to this card. If you attempt to connect a second network to this card, your communication system will operate erratically.
Publication 1784-IN003D-EN-P - January 2006
Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-9
Connect the Card Directly to the ControlNet Network
To connect the card directly to a ControlNet network, follow the instructions in these publications:
•
ControlNet Coax Tap Installation Instructions, publication 1786-IN007
•
ControlNet Coax Media Planning and Installation Manual, publication
CNET-IN002
Figure 1.2 Connect the Card Directly to the ControlNet Network
1784-PCIC or
1784-PCICS
Desktop Host
Computer
1786-TPR, -TPS, -TPYR, or -TPYS Tap
ControlNet Network
42200
ATTENTION
If you connect the product to a cable system that does not support redundant media, connect the tap dropline to the BNC connector labeled channel A. Channel B is left unconnected.
If the cable system is redundant, connect the product so that all devices on the network use the same cable for the same channel. That is, all channel A connectors connect to one cable; all channel B connectors connect to the other cable.
TIP
If you use a non-redundant cable system, all ControlNet devices must be on the same channel, channel A.
Publication 1784-IN003D-EN-P - January 2006
1-10 Install the 1784-PCIC or 1784-PCICS Communication Interface Card
Connect to a Device on the ControlNet Network
The 1786-CP cable (Figure 1.3) connects a host computer to another ControlNet device. It has two RJ-45 8-pin connectors.
Figure 1.3 1786-CP cable
RJ-45 8-pin Connectors
Connector 1
Connector 2
1786-CP Cable
ATTENTION
30124-m
Use only the 1786-CP cable when you connect a programming terminal to the network through the Network
Acces Port (NAP). If you use a different cable, it could result in possible network failures or product damage.
See Tables 1.1 and 1.2 for the wiring for the 1786-CP cable.
Table 1.1 Wiring For 1786-CP Cable (Connector 1)
5
6
3
4
7
8
Wire Number
1
2
Connector 1
Signal Mnemonic
ISO-GND
N.C.
PTTX-H
PTTX-L
PTRX-L
PTRX-H
N.C.
ISO-GND
Signal Name
Isolated Ground
No Connection
Transmit Data High
Transmit Data Low
Receive Data Low
Receive Data High
No Connection
Isolated Ground
Publication 1784-IN003D-EN-P - January 2006
Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-11
Table 1.2 Wiring For 1786-CP Cable (Connector 2)
6
7
4
5
8
2
3
Wire Number
1
Connector 2
Signal Mnemonic
ISO-GND
N.C.
PTRX-H
PTRX-L
PTTX-L
PTTX-H
N.C.
ISO-GND
Signal Name
Isolated Ground
No Connection
Receive Data High
Receive Data Low
Transmit Data Low
Transmit Data High
No Connection
Isolated Ground
When you use the RJ-45 connector, you can connect the card to a ControlNet network without a tap through the Network Access Port (or NAP) of a programmable controller, I/O adapter, or other ControlNet compliant devices.
See Figure 1.4 and Figure 1.5.
Publication 1784-IN003D-EN-P - January 2006
1-12 Install the 1784-PCIC or 1784-PCICS Communication Interface Card
Figure 1.4 Connect a Programming Terminal to a ControlNet Network Through
Another ControlNet Device
Programming
Terminal
1784-PCIC or
1784-PCICS
1786-CP Cable
1
ControlNet Network
ControlNet
Product
42199
1 The 1786-CP cable can be plugged into any ControlNet product’s NAP to provide programming capability on the ControlNet network. When you connect a programming terminal through this cable, it is counted as a node and must have a unique address.
ATTENTION
If a SoftLogix5800 processor is running on the computer containing the 1784-PCIC or 1784-PCICS card, do not use the
1786-CP cable to connect the card to the ControlNet network.
Instead, connect the card directly to the ControlNet network as shown in Figure 1.2.
Figure 1.5 Connect a Portable Host Computer to the ControlNet Network Through the 1784-PCIC or 1784-PCICS Card
Portable Host
Computer
1784-PCC
1784-PCIC or
1784-PCICS
Desktop Host
Computer
1784-PCC1 Cable
ControlNet Network
Publication 1784-IN003D-EN-P - January 2006
42198
Chapter
2
Install the Driver in Windows XP
For Information On This Topic
Install the Driver in Windows XP for the First Time
Update the Existing Driver in Windows XP
See Page
Install the Driver in Windows XP for the First Time
Follow these steps to install the driver for the first time on a personal computer running Windows XP.
1. Shut down the computer.
2. Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot.
Refer to Chapter 1 for installation information.
3. Restart the computer.
Publication 1784-IN003D-EN-P - January 2006
2-2 Install the Driver in Windows XP
After the computer restarts, the operating system detects the new PCI card and displays the Found New Hardware Wizard.
4. Select the Install from a list or specific location (Advanced) radio button.
5. Click Next.
6. On the screen that appears, click the Search for the best driver in these locations radio button.
7. Check the Include this location in the search checkbox.
8. Uncheck the remaining checkboxes.
Publication 1784-IN003D-EN-P - January 2006
Install the Driver in Windows XP 2-3
9. Click Browse.
10. Navigate to the folder that contains the installation files.
The installation files can be found in the \Drivers\Win2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM.
11. Click OK.
12. Click Next.
IMPORTANT
If prompted to overwrite existing files, click Yes.
13. Click Finish.
The driver is now ready to use. Go on to Chapter 5.
Update the Existing Driver in Windows XP
Follow these steps to update the existing device driver on a personal computer running Windows XP.
IMPORTANT
During the update procedure, communication through the card will be disrupted.
1. If you are browsing with RSLinx software, close RSWho.
2. Right-click My Computer.
Publication 1784-IN003D-EN-P - January 2006
2-4 Install the Driver in Windows XP
3. Click Manage.
4. In the left window pane, click the + to the left of System Tools to open it.
5. Under System Tools, click Device Manager.
6. In the right window pane, click the + to the left of A-B Virtual Backplane to expand it.
7. Right-click A-B 1784-PCIC(S).
TIP
If you see more than one A-B 1784-PCIC(S) entry, perform the update on only one of the entries.
8. Click Update Driver.
Publication 1784-IN003D-EN-P - January 2006
The Hardware Update Wizard appears.
Install the Driver in Windows XP 2-5
9. Select the Install from a list or specific location (Advanced) radio button.
10. Click Next.
11. On the screen that appears, click the Don’t search. I will choose the best driver to install radio button.
12. Click Next.
13. Click Have Disk.
14. Click Browse.
Publication 1784-IN003D-EN-P - January 2006
2-6 Install the Driver in Windows XP
15. Navigate to the folder that contains the installation files.
The installation files can be found in the \Drivers\Win2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM.
16. Click Open.
17. Click OK.
18. Select A-B 1784-PCIC(S) to highlight it.
19. Click Next.
IMPORTANT
If prompted to overwrite existing files, click Yes.
20. Click Finish.
21. Close the Device Manager screen.
22. Shut down and restart the computer.
The driver is now ready to use. Go on to Chapter 5.
Publication 1784-IN003D-EN-P - January 2006
Chapter
3
Install the Driver in Windows 2000
For Information On This Topic
Install the Driver in Windows 2000 for the First Time
Update the Existing Driver in Windows 2000
See Page
Install the Driver in Windows 2000 for the First Time
Follow these steps to install the driver for the first time on a personal computer running Windows 2000.
1. Shut down the computer.
2. Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot.
Refer to Chapter 1 for installation information.
3. Restart the computer.
After the computer restarts, the operating system detects the new PCI card and displays the Found New Hardware Wizard.
Publication 1784-IN003D-EN-P - January 2006
3-2 Install the Driver in Windows 2000
4. Click Next.
.
5. Click the Search for a suitable driver for my device (recommended) radio button.
6. Click Next.
7. Check the Specify a location checkbox and uncheck the remaining checkboxes.
Publication 1784-IN003D-EN-P - January 2006
Install the Driver in Windows 2000 3-3
8. Click Next.
9. Click Browse and navigate to the folder that contains the installation files.
The installation files can be found in the \Drivers\Win2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM.
10. Click Open.
11. Click OK.
12. Click Next to install the new driver.
IMPORTANT
If prompted to overwrite existing files, click Yes.
13. Click Finish to close the Found New Hardware Wizard.
The driver is now ready to use. Go on to Chapter 5.
Publication 1784-IN003D-EN-P - January 2006
3-4 Install the Driver in Windows 2000
Update the Existing Driver in Windows 2000
Follow these steps to update the existing device driver on a personal computer running Windows 2000.
IMPORTANT
During the update procedure, communication through the card will be disrupted.
1. If you are browsing with RSLinx software, close RSWho.
2. Right-click My Computer.
3. Click Manage.
4. In the left window pane, click the + to the left of System Tools to open it.
5. Under System Tools, click Device Manager.
6. In the right window pane, click the + to the left of A-B Virtual Backplane to expand it.
7. Right-click A-B 1784-PCIC(S).
TIP
If you see more than one A-B 1784-PCIC(S) entry, perform the update on only one of the entries.
8. Click Properties.
Publication 1784-IN003D-EN-P - January 2006
9. Click the Driver tab.
Install the Driver in Windows 2000 3-5
10. Click Update Driver.
The Upgrade Device Driver Wizard appears.
11. Click Next.
12. Click the Display a list of the known drivers for this device so I can choose a specific driver radio button
Publication 1784-IN003D-EN-P - January 2006
3-6 Install the Driver in Windows 2000
13. Click Next.
14. Click Have Disk.
15. Click Browse.
16. Navigate to the folder that contains the installation files.
The installation files can be found in the \Drivers\Win2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM.
17. Click Open.
18. Click OK.
19. Select A-B 1784-PCIC(S) to highlight it.
Publication 1784-IN003D-EN-P - January 2006
Install the Driver in Windows 2000 3-7
20. Click Next.
21. Click Next to install the new driver.
IMPORTANT
If prompted to overwrite existing files, click Yes.
22. Click Finish.
23. Close the A-B 1784-PCIC(S) Properties screen.
24. Close the Device Manager screen.
25. Shut down and restart the computer.
The driver is now ready to use. Go on to Chapter 5.
Publication 1784-IN003D-EN-P - January 2006
3-8 Install the Driver in Windows 2000
Notes:
Publication 1784-IN003D-EN-P - January 2006
Chapter
4
Install the Driver in Windows 98/Me
For Information On This Topic
Install the Driver in Windows 98/Me for the First Time
Install the Virtual Backplane Driver
Update the Existing Driver in Windows 98/Me
See Page
Install the Driver in Windows 98/Me for the First Time
Follow these steps to install the driver for the first time on a personal computer running Windows 98/Me.
1. Shut down the computer.
2. Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot.
Refer to Chapter 1 for installation information.
3. Restart the computer.
After the computer restarts, the operating system detects the new PCI card and displays the Add New Hardware wizard.
Publication 1784-IN003D-EN-P - January 2006
4-2 Install the Driver in Windows 98/Me
4. Click Next.
5. Click the Search for the best driver for your device (Recommended) radio button.
6. Click Next.
7. Check the Specify a location checkbox and uncheck the remaining checkboxes.
8. Click Browse and navigate to the folder that contains the installation files.
The installation files can be found in the \Drivers\Win98 folder on the
1784-PCIC(S) Driver CD-ROM.
Publication 1784-IN003D-EN-P - January 2006
Install the Driver in Windows 98/Me 4-3
9. Click OK.
10. Click Next.
11. Click Next.
IMPORTANT
If prompted to overwrite existing files, click Yes.
12. Click Finish.
Install the Virtual Backplane Driver
So that the 1784-PCICS drivers work properly after you install them for the first time, you must install the Virtual Backplane Driver. Follow this procedure to install the Virtual Backplane Driver.
1. Select Start
⇒Settings ⇒Control Panel.
2. Double-click Add New Hardware.
You see the Add New Hardware Wizard.
3. Click Next.
Windows searches for the new Plug and Play devices.
4. Click Next.
Publication 1784-IN003D-EN-P - January 2006
4-4 Install the Driver in Windows 98/Me
5. Click the No, I want to select the hardware from a list radio button.
6. Click Next.
7. Select A-B Virtual Backplane from the list of hardware types.
8. Click Next.
9. Select A-B Virtual Backplane from the list of models.
10. Click Next.
11. Click Finish.
The driver is now ready to use. Go on to Chapter 5.
Publication 1784-IN003D-EN-P - January 2006
Install the Driver in Windows 98/Me 4-5
Update the Existing Driver in Windows 98/Me
Follow these steps to update the existing device driver on a personal computer running Windows 98/Me.
IMPORTANT
During the update procedure, communication through the card will be disrupted.
1. If you are browsing with RSLinx software, close RSWho.
2. Right-click My Computer.
3. Click on the Device Manager tab.
4. In the left window pane, click the + to the left of A-B Virtual Backplane to expand it.
5. Right-click on A-B 1784-PCIC(S).
TIP
If you see more than one A-B 1784-PCIC(S) entry, perform the update on only one of the entries.
6. Click Properties.
Publication 1784-IN003D-EN-P - January 2006
4-6 Install the Driver in Windows 98/Me
7. Click the Driver tab.
8. Click Update Driver.
9. Click Next.
10. Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button.
Publication 1784-IN003D-EN-P - January 2006
11. Click Next.
Install the Driver in Windows 98/Me 4-7
12. Click Have Disk.
13. Click Browse, then navigate to the folder that contains the installation files.
The installation files can be found in the \Drivers\Win98 folder on the
1784-PCIC(S) Driver CD-ROM.
14. Click OK.
15. Click OK.
16. Select A-B 1784-PCIC(S) to highlight it.
17. Click Next.
18. Click Next.
19. Click Next.
IMPORTANT
If prompted to overwrite existing files, click Yes.
20. Click Finish.
Publication 1784-IN003D-EN-P - January 2006
4-8 Install the Driver in Windows 98/Me
21. Close the A-B 1784-PCIC(S) Properties screen.
22. Close the System Properties screen.
23. Shut down and restart the computer.
The driver is now ready to use. Go on to Chapter 5.
Publication 1784-IN003D-EN-P - January 2006
Once You Have Completed the Installation
Chapter
5
Once you have installed the drivers, you can do the following:
For Information On This Topic
See Page
Configure the ControlNet Communications Driver in RSLinx Software 5-2
Connect a SoftLogix Controller to the ControlNet Network 5-4
Go Online With RSNetWorx for ControlNet Software 5-7
Register the EDS File
The EDS files can be found in the \EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from http://www.ab.com/networks/eds/.
Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card:
Catalog Number
1784-PCIC
1784-PCICS
EDS File
0001000C00490400.eds
0001000C003F0400.eds
•
In Windows, select Start
⇒Programs ⇒Rockwell Software ⇒RSLinx Tools
⇒EDS Hardware Installation Tool.
•
In RSNetWorx for ControlNet software, select Tools
⇒EDS Wizard.
Publication 1784-IN003D-EN-P - January 2006
5-2 Once You Have Completed the Installation
Configure the ControlNet Communications Driver in RSLinx
Software
Follow this procedure to configure the ControlNet communication driver.
IMPORTANT
Do not use these steps to configure a ControlNet communication driver for any application that uses a
SoftLogix5800 controller. For information on configuring the
ControlNet card for use with SoftLogix5800 controllers, refer
1. Install RSLinx software, version 2.42.00 or later, on your computer.
2. In RSLinx software, select Configure Drivers.
A. Click Communications.
B. Click Configure Drivers.
3. Select a driver for ControlNet devices.
Publication 1784-IN003D-EN-P - January 2006
Once You Have Completed the Installation 5-3
In the example below, we chose the 1784-PCICS card.
A. Use the pull-down menu to select the ControlNet driver.
B. Click Add New.
4. Name the new ControlNet driver.
A. Name the driver.
This example shows the default name (AB_PCIC-1) that RSLinx software uses.
B. Click OK.
Publication 1784-IN003D-EN-P - January 2006
5-4 Once You Have Completed the Installation
5. After you create the driver, configure it to correspond to the ControlNet module within your computer.
A. If multiple cards are located in your computer, choose the correct one.
B. Make sure you use the correct Network Address.
C. Click OK.
The driver is now available in RSLinx software. You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card.
Connect a SoftLogix Controller to the ControlNet Network
The SoftLogix5800 controller is a soft control solution that runs in a Microsoft
Windows 2000 or Windows XP environment. When using this controller, you must install the SoftLogix5800 Chassis monitor, a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers.
Before you can connect the SoftLogix system to the ControlNet network, you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis.
1. In the SoftLogix chassis monitor, create a New Module.
A. Click Slot.
B. Click Create Module.
Publication 1784-IN003D-EN-P - January 2006
Once You Have Completed the Installation 5-5
2. Select the 1784-PCIC or 1784-PCICS card.
A. Select the ControlNet card.
B. Specify the virtual backplane slot number.
C. Click OK.
3. Select the serial number of the 1784-PCIC or 1784-PCICS card you want.
If you previously configured the card that you selected by serial number, the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot).
A. If multiple cards are located in your computer, choose the serial number of the correct one.
B. Click Next.
4. Configure the card.
A. Specify the node address on the
ControlNet network.
B. Enter the label name for the card
(this is the name you wrote on the label of the card to help you identify the card from others in the same computer).
C. Click Finish.
Publication 1784-IN003D-EN-P - January 2006
5-6 Once You Have Completed the Installation
You can specify any slot number greater than 0 for the communication card. RSLinx software resides in slot 0.
By creating the card in the virtual chassis, you configure the communication driver information needed by the SoftLogix controller. Do not use RSLinx software to install the ControlNet communication driver to the same card; installation through
RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor.
Instead, configure a Virtual Backplane driver in RSLinx software:
5. Select Communications
⇒Configure Drivers...
6. Under Available Driver Types, select Virtual Backplane (SoftLogix 58xx).
7. Click Add New.
8. Enter a name for the driver.
9. Click OK.
10. Click on Close.
The Virtual Backplane driver is now ready to use.
After you add the card to the chassis monitor and configure a Virtual Backplane driver, you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card. Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver.
Publication 1784-IN003D-EN-P - January 2006
Once You Have Completed the Installation 5-7
Go Online With RSNetWorx for ControlNet Software
When going online with RSNetWorx for ControlNet software via the 1784-PCIC or
1784-PCICS card, select Port A, ControlNet under the card in the Virtual Chassis.
Do not select AB-PCIC-1, ControlNet.
Publication 1784-IN003D-EN-P - January 2006
5-8 Once You Have Completed the Installation
Notes:
Publication 1784-IN003D-EN-P - January 2006
Chapter
6
Interpret the LED Indicators
The LED indicators on the card give you information about the card and the network when you’re connected via the BNC connectors. Table 6.1 outlines the states and explains what each state means to you and the action you should take, if any, to correct that state.
Diagnostic Status
Indicators
Redundant Media
BNC Connectors
!
!
A
!
B
42281
IMPORTANT
When you connect the module to a ControlNet network using only the Network Acces Port (NAP), the LEDs are meaningless.
Publication 1784-IN003D-EN-P - January 2006
6-2 Interpret the LED Indicators
•
Steady - indicator is on continuously in the defined state.
•
Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together). The two indicators are always in opposite states, out of phase.
•
Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other). If both indicators flash, they must flash together, in phase.
Table 6.1 ControlNet status interpretation
Cause Action
A and
B
Off
•
No power
•
1784-PCIC or
1784-PCICS driver not started
•
Faulted card
•
None or apply power to the personal computer
•
Start RSLinx software
•
Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software
•
Check operating system event log for details of fault (if the personal computer’s operating system supports an event log)
•
Cycle power to the computer
•
Verify that you have firmly inserted the
1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened
•
If fault persists, contact your Rockwell
Automation representative or distributor
Publication 1784-IN003D-EN-P - January 2006
Interpret the LED Indicators 6-3
Table 6.1 ControlNet status interpretation
Cause Action
A and
B
Steady red
•
Faulted card
Alternating red/green
Alternating red/off
•
Self-test
•
Incorrect channel configuration
•
Incorrect node configuration
•
Duplicate
ControlNet node address
•
Check operating system event log for details of fault (if the personal computer’s operating system supports an event log)
•
Cycle power to the computer
•
Verify that you have firmly inserted the
1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened
•
If fault persists, contact your Rockwell
Automation representative or distributor
•
None
•
Verify that the ControlNet network is connected to the correct channel of the
1784-PCIC or 1784-PCICS card (for example, if the ControlNet network is configured for channel A only, then the card must be connected to the network via channel A)
•
Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters
Off
A or B
Steady green
Flashing green/off
Flashing red/off
Cause
•
Channel disabled
Action
•
Normal operation
•
Temporary network errors
•
Media fault
•
Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media, if required
•
None
•
Check media for broken cables, loose connectors, or missing terminators
•
If condition persists, refer to the ControlNet
Media Planning and Installation Manual, publication CNET-IN002
•
Check media for broken cables, loose connectors, or missing terminators
•
If condition persists, refer to the ControlNet
Media Planning and Installation Manual, publication CNET-IN002
Publication 1784-IN003D-EN-P - January 2006
6-4 Interpret the LED Indicators
Cause Action
A or B
Flashing red/off
Flashing red/green
•
No other nodes present on network
•
•
Incorrect node address
Incorrect network configuration
•
Add other nodes to the network
•
Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to
UMAX
(1)
•
Stop and restart the 1784-PCIC or
1784-PCICS driver in RSLinx software
•
Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that
is greater than or equal to the
1784-PCIC or 1784-PCICS node address
(1)
UMAX is the highest node address on a ControlNet network that can transmit data.
Publication 1784-IN003D-EN-P - January 2006
Chapter
7
Specifications
Storage temperature
Relative humidity
Vibration
Operating shock
Non-operating shock
Emissions
ESD immunity
Radiated RF immunity
PCI local bus
Mechanical form factor, H x L
Driver compatibility
Software compatibility
Operational temperature
Compliant to PCI revision 2.2.
The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 3.3V PCI slots, 32-bit and 64-bit PCI slots, and PCI-X slots.
Attention: The 1784-PCIC and 1784-PCICS cards are not compatible with PCI
Express and should not be inserted into a PCI Express slot.
Universal PCI 32-bit short card
10.7 cm (4.2 in.) x 16.5 cm (6.5 in.) L
Microsoft Windows XP with Service Pack 1 or higher
Microsoft Windows 2000 with Service Pack 4 or higher
Microsoft Windows 98
Microsoft Windows Me
Rockwell Software RSLinx software, version 2.42.00 or later
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0...55 C (32...131 F)
The operating parameters describe the environment within the PCI slot.
Refer to the documentation for your computer for environmental requirements. This card should not exceed those specifications.
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40...85 C (-40...185 F)
IEC 60068-2-30 (Test Db, Un-packaged Nonoperating Damp Heat):
5...95% noncondensing
IEC 60068-2-6 (Test Fc, Operating):
2g @ 10...500Hz
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
CISPR 11:
Group 1, Class A
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
IEC 61000-4-3:
10V/m with 1 k Hz sine-wave 80%AM from 80 MHz...2000 MHz
10V/m with 200 Hz 50% pulse 100%AM at 900 MHz
10V/m with 200 Hz 50% pulse 100%AM at 1890 MHz
Publication 1784-IN003D-EN-P - January 2006
7-2 Specifications
EFT/B immunity
Surge transient immunity
Conducted RF immunity
Enclosure type rating
Power requirements
Power dissipation
Isolation voltage (continuous-voltage withstand rating)
Wiring category
(1)
Certifications (when product is marked)
(2)
IEC 61000-4-4:
± 2 kV at 5 kHz on communications ports
IEC 61000-4-5:
± 2 kV line-earth (CM) on communications ports
IEC 61000-4-6:
10Vrms with 1 kH sine-wave 80% AM from 150kHz...80MHz
None (open-style)
In US, this equipment must be powered from UL Listed Information
Technology Equipment or UL Listed Industrial Control Equipment. In Canada, this equipment must be powered by an SELV source, CSA Certified
Information Technology Equipment, or CSA Certified Process Control
Equipment.
5V dc, 700 mA max., Class 2
3.5 W
50V continuous
Tested to withstand 600V for 60 s
2 - on communications ports
UR UL Recognized Component Industrial Control Equipment
CSA CSA Accepted Component for Process Control Equipment
CSA Accepted Component for Process Control Equipment in Class
I, Division 2 Group A,B,C,D Hazardous Locations
CE European Union 89/336/EEC EMC Directive, compliant with:
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
C-tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
EEx (1784-PCIC only) European Union 94/9/EC ATEX Directive,
compliant with:
EN 50021; Potentially Explosive Atmospheres, Protection “n”
(Zone 2)
CI ControlNet International conformance tested to ControlNet
specifications
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1.
(2)
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Publication 1784-IN003D-EN-P - January 2006
Index
C
card, install
configure ControlNet communications driver
in RSLinx
connect
a SoftLogix controller to the ControlNet network
the card directly to the ControlNet network
to a device on the ControlNet network
ControlNet network
connect to
connect to a device on
install the driver
in Windows 2000
in Windows 98/Me
in Windows XP
install the Virtual Backplane Driver
L
LEDs
status indicator
D
driver
install in Windows 2000 for the first time
install in Windows 98/Me
install in Windows 98/Me for the first time
install in Windows XP
install in Windows XP for the first time
update the existing driver in Windows 2000
update the existing driver in Windows 98/Me
update the existing driver in Windows XP
R
RSLinx
configure ControlNet communications driver
S
specifications
status indicator LEDs
U
update the existing driver
in Windows 2000
in Windows 98/Me
in Windows XP
I
install the 1784-PCIC and 1784-PCICS
Communication Interface Cards
V
Virtual Backplane Driver
install
Publication 1784-IN003D-EN-P - January 2006
2 Index
Notes:
Publication 1784-IN003D-EN-P - January 2006
How Are We Doing?
Your comments on our technical publications will help us serve you better in the future.
Thank you for taking the time to provide us feedback.
You can complete this form and mail (or fax) it back to us or email us at
Pub. Title/Type ControlNet Universal PCI Communication Interface Card
Cat. No.
1784-PCIC,
1784-PCICS,
Series B
Pub. No.
1784-IN003D-EN-P Pub. Date January 2006 Part No. 953002-33
Where applicable, please rank the feature (1=needs improvement, 2=satisfactory, 3=outstanding).
Overall Usefulness 1 2 3 How can we make this publication more useful for you?
Completeness
(all necessary information is provided)
1 2 3
Can we add more information to help you?
procedure/step example explanation illustration guideline definition feature other
Technical Accuracy
(all information is correct)
1 2 3 Can we be more accurate?
text illustration
Clarity
(all information is easy to understand)
1 2 3 How can we make things clearer?
Other Comments You can add additional comments on the back of this form.
Your Name
Your Title/Function
Location/Phone
Would you like us to contact you regarding your comments?
___No, there is no need to contact me
___Yes, please call me
___Yes, please email me at __________________________
___Yes, please contact me via ________________________
Return this form to:Rockwell Automation Technical Communications, 1 Allen-Bradley Dr., Mayfield Hts., OH 44124-9705
Fax: 440-646-3525 Email: [email protected]
Publication CIG-CO521C-EN-P – May 2003 PN 957782-91
Other Comments
PLEASE FASTEN HERE (DO NOT STAPLE)
PLEASE FOLD HERE
BUSINESS REPLY MAIL
FIRST-CLASS MAIL PERMIT NO. 18235 CLEVELAND OH
POSTAGE WILL BE PAID BY THE ADDRESSEE
1 ALLEN-BRADLEY DR
MAYFIELD HEIGHTS OH 44124-9705
1 ALLEN-BRADLEY DR
NO POSTAGE
NECESSARY
IF MAILED
IN THE
UNITED STATES
Rockwell Automation Support
Rockwell Automation provides technical information on the web to assist you in using our products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com.
Installation Assistance
If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running:
United States
Outside United
States
1.440.646.3223
Monday – Friday, 8am – 5pm EST
Please contact your local Rockwell Automation representative for any technical support issues.
New Product Satisfaction Return
Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned:
United States
Outside United
States
Contact your distributor. You must provide a Customer Support case number
(see phone number above to obtain one) to your distributor in order to complete the return process.
Please contact your local Rockwell Automation representative for return procedure.
Publication 1784-IN003D-EN-P - January 2006
Supersedes Publication 1784-IN003C-EN-P - October 2004
PN 953002-33
Copyright © 2006 Rockwell Automation, Inc. All rights reserved. Printed in USA