Below you will find brief information for Isolated Analog Output Module Compact 1769-OF4VI. This module is a Compact I/O module that is suitable for use in an industrial environment when installed in accordance with these instructions. It has four isolated differential analog outputs, and it can be used to control various actuators. The module can be mounted to a panel or a DIN rail, and it is compatible with the MicroLogix 1500 programmable controller.
Advertisement
Advertisement
Installation Instructions
Compact 1769-OF4VI Isolated Analog Output
Module
Inside
Mounting Expansion I/O ...........................................................................5
Replacing a Single Module within a System ...........................................7
Module Spare/Replacement Parts ...........................................................8
Field Wiring Connections..........................................................................8
I/O Memory Mapping .............................................................................11
Hazardous Location Considerations .......................................................19
Environnements dangereux ....................................................................20
Publication 1769-IN076A-EN-P - July 2005
2 Compact 1769-OF4VI Isolated Analog Output Module
Module Description
5a
7a
9
7b
8a
1
10a
10
10b
OK
Analog
8b
OK
Analog
7b
7a
2a
DANGER
Do Not Remove RTB Under Power
Unless Area is Non-Hazardous
N/C
N/C
V out 0 -
V out 0 +
N/C
N/C
V out 1 -
V out 1 +
N/C
N/C
V out 2 -
V out 2 +
N/C
N/C
V out 3 -
V out 3 +
N/C
N/C
Ensure Adjacent
Bus Lever is Unlatched/Latched
Before/After
Removing/Inserting Module
1769-OF4VI
2b
3
4
6
5b
3
4
Item Description
1
bus lever
(with locking function)
2a
2b
upper panel mounting tab lower panel mounting tab
5a
5b
module status LED module door with terminal identification label movable bus connector with female pins stationary bus connector with male pins
6
7a
7b
nameplate label upper tongue-and-groove slots lower tongue-and-groove slots upper DIN rail latch lower DIN rail latch
8a
8b
9
10
write-on label (user ID tag) removable terminal block (RTB) with finger-safe cover
10a
RTB upper retaining screw
10b
RTB lower retaining screw
Publication 1769-IN076A-EN-P - July 2005
Compact 1769-OF4VI Isolated Analog Output Module 3
Module Installation
Compact I/O is suitable for use in an industrial environment when installed in accordance with these instructions. Specifically, this equipment is intended for use in clean, dry environments (Pollution degree 2
(1)
) and to circuits not exceeding Over Voltage Category
II
(2)
(IEC 60664-1).
(3)
Prevent Electrostatic Discharge
ATTENTION
Electrostatic discharge can damage integrated circuits or semiconductors if you touch bus connector pins or the terminal block. Follow these guidelines when you handle the module:
• Touch a grounded object to discharge static potential.
• Wear an approved wrist-strap grounding device.
• Do not touch the bus connector or connector pins.
• Do not touch circuit components inside the module.
• If available, use a static-safe work station.
• When not in use, keep the module in its static-shield box.
Remove Power
ATTENTION
Remove power before removing or inserting this module. When you remove or insert a module with power applied, an electrical arc may occur.
An electrical arc can cause personal injury or property damage by:
• sending an erroneous signal to your system’s field devices, causing unintended machine motion
• causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance.
(1)
Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that occasionally a temporary conductivity caused by condensation shall be expected.
(2)
Over Voltage Category II is the load level section of the electrical distribution system. At this level transient voltages are controlled and do not exceed the impulse voltage capability of the product’s insulation.
(3)
Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC) designations.
Publication 1769-IN076A-EN-P - July 2005
4 Compact 1769-OF4VI Isolated Analog Output Module
System Assembly
The module can be attached to the controller or an adjacent I/O module before or after
mounting. For mounting instructions, see “Panel Mounting” on page 6, or “DIN Rail
Mounting” on page 7. To work with a system that is already mounted, see “Replacing a Single
Module within a System” on page 7.
The following procedure shows you how to assemble the Compact I/O system.
3
4
2
1
6
1
5
1. Disconnect power.
2. Check that the bus lever of the module to be installed is in the unlocked (fully right) position.
3. Use the upper and lower tongue-and-groove slots (1) to secure the modules together
(or to a controller).
4. Move the module back along the tongue-and-groove slots until the bus connectors (2) line up with each other.
5. Push the bus lever back slightly to clear the positioning tab (3). Use your fingers or a small screwdriver.
Publication 1769-IN076A-EN-P - July 2005
Compact 1769-OF4VI Isolated Analog Output Module 5
6. To allow communication between the controller and module, move the bus lever fully to the left (4) until it clicks. Ensure it is locked firmly in place.
ATTENTION
When attaching I/O modules, it is very important that the bus connectors are securely locked together to ensure proper electrical connection.
7. Attach an end cap terminator (5) to the last module in the system by using the tongue-and-groove slots as before.
8. Lock the end cap bus terminator (6).
IMPORTANT
A 1769-ECR or 1769-ECL right or left end cap must be used to terminate the end of the serial communication bus.
Mounting Expansion I/O
ATTENTION
During panel or DIN rail mounting of all devices, be sure that all debris
(metal chips, wire strands, etc.) is kept from falling into the module.
Debris that falls into the module could cause damage on power up.
Minimum Spacing
Maintain spacing from enclosure walls, wireways, adjacent equipment, etc.
Allow 50 mm (2 in.) of space on all sides for adequate ventilation, as shown:
Side
Host Controller
Top
Bottom
Side
Publication 1769-IN076A-EN-P - July 2005
6 Compact 1769-OF4VI Isolated Analog Output Module
Panel Mounting
Mount the module to a panel using two screws per module. Use M4 or #8 panhead screws.
Mounting screws are required on every module.
Panel Mounting Using the Dimensional Template
Spacing for single-wide modules 35mm (1.378 in.)
Spacing for one-and-a half-wide modules 52.5mm (2.067 in.)
Refer to host controller documentation for this dimension.
Note: Overall hole spacing tolerance:
±0.4mm (0.016 in.).
30535-M
Panel Mounting Procedure Using Modules as a Template
The following procedure allows you to use the assembled modules as a template for drilling holes in the panel. If you have sophisticated panel mounting equipment, you can use the
dimensional template provided on page 6. Due to module mounting hole tolerance, it is
important to follow these procedures:
1. On a clean work surface, assemble no more than three modules.
2. Using the assembled modules as a template, carefully mark the center of all module-mounting holes on the panel.
3. Return the assembled modules to the clean work surface, including any previously mounted modules.
4. Drill and tap the mounting holes for the recommended M4 or #8 screw.
5. Place the modules back on the panel, and check for proper hole alignment.
6. Attach the modules to the panel using the mounting screws.
TIP
If mounting more modules, mount only the last one of this group and put the others aside. This reduces remounting time during drilling and tapping of the next group.
7. Repeat steps 1 to 6 for any remaining modules.
Publication 1769-IN076A-EN-P - July 2005
Compact 1769-OF4VI Isolated Analog Output Module 7
DIN Rail Mounting
The module can be mounted using the following DIN rails: 35 x 7.5 mm (EN 50 022 - 35 x
7.5) or 35 x 15 mm (EN 50 022 - 35 x 15).
Before mounting the module on a DIN rail, close the DIN rail latches. Press the DIN rail mounting area of the module against the DIN rail. The latches will momentarily open and lock into place.
Replacing a Single Module within a System
The module can be replaced while the system is mounted to a panel (or DIN rail). Follow the steps below in order:
1. Remove power. See important note on page 3.
2. On the module to be removed, remove the upper and lower mounting screws from the module (or open the DIN latches using a flat-blade or phillips-style screwdriver).
3. Move the bus lever to the right to disconnect (unlock) the bus.
4. On the right-side adjacent module, move its bus lever to the right (unlock) to disconnect it from the module to be removed.
5. Gently slide the disconnected module forward. If you feel excessive resistance, check that the module has been disconnected from the bus, and that both mounting screws have been removed (or DIN latches opened).
TIP
It may be necessary to rock the module slightly from front to back to remove it, or, in a panel-mounted system, to loosen the screws of adjacent modules.
6. Before installing the replacement module, be sure that the bus lever on the module to be installed, and on the right-side adjacent module are in the unlocked (fully right) position.
7. Slide the replacement module into the open slot.
8. Connect the modules together by locking (fully left) the bus levers on the replacement module and the right-side adjacent module.
9. Replace the mounting screws (or snap the module onto the DIN rail).
Publication 1769-IN076A-EN-P - July 2005
8 Compact 1769-OF4VI Isolated Analog Output Module
Module Spare/Replacement Parts
• Terminal block, catalog number 1769-RTBN18
• Door, catalog number 1769-RD (2 per kit)
Field Wiring Connections
Grounding the Module
This product is intended to be mounted to a well-grounded mounting surface such as a metal panel. Additional grounding connections from the module’s mounting tabs or DIN rail (if used), are not required unless the mounting surface cannot be grounded. Refer to Industrial
Automation Wiring and Grounding Guidelines, Allen-Bradley publication 1770-4.1, for additional information.
System Wiring Guidelines
Consider the following when wiring your system:
• Channels are isolated from each other.
• Use Belden™ 8761, or equivalent, shielded wire.
• Under normal conditions, the drain wire and shield junction must be connected to earth ground, via a panel or DIN rail mounting screw at the analog I/O module end.
Keep the shield connection to ground as short as possible.
(1)
• To ensure optimum accuracy, limit overall cable impedance by keeping your cable as short as possible. Locate the I/O system as close to your sensors or actuators as your application will permit.
• Load resistance for each voltage output channel must be equal to or greater than
2K Ω.
(1)
In environments where high frequency noise may be present, it may be necessary to ground the shield via a 0.1µF capacitor at the load end and also ground the module end without a capacitor.
Publication 1769-IN076A-EN-P - July 2005
Compact 1769-OF4VI Isolated Analog Output Module 9
Wiring Output Devices
Basic wiring of output devices is shown below.
ATTENTION
• Miswiring of the module to an AC/DC source will damage the module.
• Be careful when stripping wires. Wire fragments that fall into a module could cause damage at power up. Once wiring is complete, ensure the module is free of all metal fragments.
Labeling the Terminals
A removable, write-on label is provided with the module. Remove the label from the door, mark the identification of each terminal with permanent ink, and slide the label back into the door. Your markings (ID tag) will be visible when the module door is closed.
Publication 1769-IN076A-EN-P - July 2005
10 Compact 1769-OF4VI Isolated Analog Output Module
Removing the Finger-Safe Terminal Block
To remove the terminal block, loosen the upper and lower retaining screws. The terminal block will back away from the module as you remove the screws. When replacing the terminal block, torque the retaining screws to 0.46 Nm (4.1 in-lbs).
upper retaining screw wiring the finger-safe terminal block lower retaining screw
Wiring the Finger-Safe Terminal Block
When wiring the terminal block, keep the finger-safe cover in place.
1. Loosen the terminal screws to be wired.
2. Route the wire under the terminal pressure plate. You can use the bare wire or a spade lug. The terminals will accept a 6.35 mm (0.25 in.) spade lug.
TIP
The terminal screws are non-captive. Therefore, it is possible to use a ring lug [maximum 1/4 inch o.d. with a 0.139 inch minimum i.d. (M3.5)] with the module.
3. Tighten the terminal screw making sure the pressure plate secures the wire.
Recommended torque when tightening terminal screws is 0.68 Nm (6 in-lbs).
TIP
If you need to remove the finger-safe cover, insert a screw driver into one of the square, wiring holes and gently pry the cover off. If you wire the terminal block with the finger-safe cover removed, you will not be able to put it back on the terminal block because the wires will be in the way.
Publication 1769-IN076A-EN-P - July 2005
Compact 1769-OF4VI Isolated Analog Output Module 11
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires with the following restrictions:
Solid
Stranded
Wire Type
Cu-90°C (194°F)
Cu-90°C (194°F)
Wire Size
#14 to #22 AWG
#16 to #22 AWG
Terminal Screw
Torque
0.68 Nm (6 in-lbs)
0.68 Nm (6 in-lbs)
Retaining Screw
Torque
0.46 Nm (4.1 in-lbs)
0.46 Nm (4.1 in-lbs)
I/O Memory Mapping
Output Data File
For each module, slot x, words 0-3 in the output data file contain the channel 0 through channel 3 output data. Word 4 is used to unlatch any alarm condition that has been latched.
Refer to your module’s user manual for additional details.
Bit Position
15 14 13 12 11 10 9
0 SGN
8 7 6 5
Analog Output Data Channel 0
1 SGN
2 SGN
Analog Output Data Channel 1
Analog Output Data Channel 2
4 3 2 1 0
3 SGN
4
Analog Output Data Channel 3
UU3 UO3 UU2 UO2 UU1 UO1 UU0 UO0
• SGN = Sign bit in two’s complement format.
• UU = Unlatch under-range (or low-clamp exceeded) alarm.
• UO = Unlatch over-range (or high-clamp exceeded) alarm.
Publication 1769-IN076A-EN-P - July 2005
12 Compact 1769-OF4VI Isolated Analog Output Module
Input Data File
For each module, slot x, input data file words 2-5 contain the state of the module’s output data (output data echo) file words 0-3. During normal operation, these input words represent the analog values that the outputs are directed to by the control program.
2
3
0
1
4
5
15 14 13 12 11 10 9
Bit Position
8 7 6 5 4 3 2 1 0
S3 S2 S1 S0
H0 U0 O0 H3 U3 O3 H2 U2 O2 H1 U1 O1
Channel 0 Data Value
Channel 1 Data Value
Channel 2 Data Value
Channel 3 Data Value
• S = General status (over-range, under-range, or low/high clamp exceeded).
• H = Output held bit.
• U = Under-range (or low-clamp exceeded) alarm.
• O = Over-range (or high-clamp exceeded) alarm.
IMPORTANT
The output module’s input data file reflects the analog output data echo of the module, not necessarily the electrical state of the output terminals. It does not reflect shorted or open outputs.
Publication 1769-IN076A-EN-P - July 2005
Compact 1769-OF4VI Isolated Analog Output Module 13
10
11
12
13
8
9
6
7
14
15
4
5
2
3
Word
0
1
Configuration Data File
The manipulation of the bits from this file is normally done with programming software (e.g.
RSLogix 500, RSNetworx for DeviceNet, etc.) during initial configuration of the system. In that case, graphical screens are provided by the programmer to simplify configuration.
However, some systems, like the 1769-ADN DeviceNet Adapter, also allow the bits to be altered as part of the control program, using communication rungs. In that case, it is necessary to understand the bit arrangement. The channel configuration words, the first two
words of each eight word group, are described on page 14. Refer to your module’s user
manual for additional details.
Description
Channel 0 Configuration Word 0
Channel 0 Configuration Word 1
Channel 0 Fault Value Word
Channel 0 Program Idle Mode Word
Channel 0 Low Clamp
Channel 0 High Clamp
Channel 0 Ramp Rate
Channel 0 Spare
Channel 1 Configuration Word 0
Channel 1 Configuration Word 1
Channel 1 Fault Value Word
Channel 1 Program Idle Mode Word
Channel 1 Low Clamp
Channel 1 High Clamp
Channel 1 Ramp Rate
Channel 1 Spare
26
27
28
29
22
23
24
25
30
31
18
19
20
21
Word
16
17
Description
Channel 2 Configuration Word 0
Channel 2 Configuration Word 1
Channel 2 Fault Value Word
Channel 2 Program Idle Mode Word
Channel 2 Low Clamp
Channel 2 High Clamp
Channel 2 Ramp Rate
Channel 2 Spare
Channel 3 Configuration Word 0
Channel 3 Configuration Word 1
Channel 3 Fault Value Word
Channel 3 Program Idle Mode Word
Channel 3 Low Clamp
Channel 3 High Clamp
Channel 3 Ramp Rate
Channel 3 Spare
Publication 1769-IN076A-EN-P - July 2005
14 Compact 1769-OF4VI Isolated Analog Output Module
Channel Configuration Words
Word/Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Word 0 E Reserved SIU SIO LA ER FM PM HI PFE
Word 1 Reserved Output Data
Format Select
Reserved Output
Type/Range
• E = Channel Enable: (0 = Disabled, 1 = output Enabled, process changes)
• Reserved = Set to zero
• SIU = System interrupt low clamp, under-range alarms: (0 = Disabled, 1 = Enabled)
• SIO = System interrupt high clamp, over-range alarms: (0 = Disabled, 1 = Enabled)
• LA = Latch low/high clamp, under/over-range alarms: (0 = Disabled, 1 = Enabled)
• ER = Enable ramping: (0 = Disabled, 1 = Enabled. Ramp rate limited by fault states.)
• FM = Fault mode: (0 = Hold Last State, 1 = User Defined Value)
• PM = Program mode: (0 = Hold Last State, 1 = User Defined Value)
• HI = Hold for initialization: (0 = Disabled, 1 = Enabled)
• PFE = Program/idle to fault enable: (0 = Disabled, 1 Enabled)
Publication 1769-IN076A-EN-P - July 2005
Compact 1769-OF4VI Isolated Analog Output Module 15
The first two words of each eight word group in the configuration file allow you to change the parameters of each channel independently. For example, words 8 and 9 correspond to channel
1 while words 16 and 17 correspond to channel 3.
Define Indicate this
Program
(Idle) to
Fault Enable
Program (Idle) Mode
Data Applied
(1)
Hold for
Initialization
Fault Mode Data
Disabled
Enabled
Program
(Idle) Mode
User-Defined
Value
Fault Mode Hold Last State (1)
Enable
Ramping
System
Interrupt
High Clamp
System
Interrupt
Low Clamp
Enable
Channel
User-Defined Fault
Value
Disabled
Enabled
Disabled
Disabled
Disabled
Enabled
0
1
These bit settings
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0
0
1
0
1
0
1
0
1
0
1
0
1
1
(1)
These functions are not supported by all controllers (e.g. MicroLogix 1500) using any configuration method. Refer to your controller manual for details.
Define
Output
Range
Select
Output
Data
Select
Indicate this
-10 to +10V dc
0 to 5V dc
0 to 10V dc
1 to 5V dc
Raw/Proportional
Counts
Engineering Units
Scaled for PID
Percent Range
These bit settings
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 0 0
0 0 1
0 1 0
0 1 1
0 0 0
0 0 1
0 1 0
0 1 1
Publication 1769-IN076A-EN-P - July 2005
16 Compact 1769-OF4VI Isolated Analog Output Module
Specifications
General Specifications
Specification
Dimensions
Value
118 mm (height) x 87 mm (depth) x 35 mm (width) height including mounting tabs is 138 mm
4.65 in. (height) x 3.43 in (depth) x 1.38 in (width) height including mounting tabs is 5.43 in.
270g (0.6 lbs.) Approximate Shipping Weight
(with carton)
Storage Temperature
Operating Temperature
Operating Humidity
Operating Altitude
Vibration
Shock
-40°C to +85°C (-40°F to +185°F)
0°C to +60°C (32°F to +140°F)
5% to 95% non-condensing
2000 meters (6561 feet)
Operating: 10 to 500 Hz, 5G, 0.030 in. peak-to-peak
Operating: 30G, 11 ms panel mounted
(20G, 11 ms DIN rail mounted)
Agency Certification
Hazardous Environment Class
Non-Operating: 40G panel mounted
(30G DIN rail mounted)
• C-UL certified (under CSA C22.2 No. 142)
• UL 508 listed
• CE compliant for all applicable directives
Class I, Division 2, Hazardous Location, Groups A, B, C, D (UL 1604,
C-UL under CSA C22.2 No. 213)
Radiated and Conducted Emissions EN50081-2 Class A
Electrical /EMC:
• ESD Immunity (IEC1000-4-2)
• Radiated Immunity (IEC1000-4-3)
• Fast Transient Burst (IEC1000-4-4)
• Surge Immunity (IEC1000-4-5)
• Conducted Immunity
(IEC1000-4-6)
The module has passed testing at the following levels:
• 4 kV contact, 8 kV air, 4 kV indirect
• 10 V/m, 80 to 1000 MHz, 80% amplitude modulation
• 2 kV, 5 kHz
• 1 kV galvanic gun
• 10V dc, 0.15 to 80 MHz (1)
(1)
Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to
1000 MHz.
Publication 1769-IN076A-EN-P - July 2005
Compact 1769-OF4VI Isolated Analog Output Module 17
Output Specifications
Specification
Analog Normal Operating Ranges
(1)
Full Scale Analog Ranges
Number of Outputs
Bus Current Draw (max.)
Heat Dissipation
Digital Resolution Across Full Range
1769-OF4VI
± 10V dc, 0 to 10V dc, 0 to 5V dc, 1 to 5V dc
± 10.5V dc, -0.5 to 10.5V dc, -0.5 to 5.25V dc,
0.5 to 5.25V dc
4 isolated differential
145 mA at 5V dc
75 mA at 24V dc
2.0 Total Watts (all points - 10V dc into 2 k - worst case calculated)
15 bits plus sign (bipolar)
Conversion Rate (all channels) max.
Step Response to 63%
(2)
Load Output Current
Load Range Output
Max. Capacitive Load
Field Calibration
Overall Accuracy
(3)
±10V dc: 15.89 bits, 330 µV/bit
0 to +5V dc: 13.89 bits, 330 µV/bit
0 to +10V dc: 14.89 bits, 330 µV/bit
+1 to +5V dc: 13.57 bits, 330 µV/bit
120 ms
<2.9 ms
5 mA max.
> 2K
Ω
1 µF
None required
±0.5% full scale at 25°C
(1)
The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will continue to convert the analog output up to the maximum full scale range. The flag automatically resets when within the normal operating range unless configured to latch.
(2)
Step response is the period of time between when the D/A converter was instructed to go from minimum to full range until the device is at 63% of full range.
(3)
Includes offset, gain, drift, non-linearity and repeatability error terms.
Publication 1769-IN076A-EN-P - July 2005
18 Compact 1769-OF4VI Isolated Analog Output Module
Specification
Accuracy Drift with Temperature
Output Ripple
(1) range 0 to 50 kHz
(referred to output range)
Non-linearity (in percent full scale)
Repeatability
(2)
(in percent full scale)
Output Error Over Full Temperature
Range
(0 to 60°C [+32 to +140°F])
Output Impedance
Open and Short-Circuit Protection
Short-Circuit Current
Output Overvoltage Protection
Output Response at System Power Up and Power Down
Rated Working Voltage
(3)
Output Group to Bus Isolation
1769-OF4VI
±0.0086% FS per °C
±0.05%
±0.05%
±0.05%
±0.8%
<1
Ω
Yes
35 mA typical, 42 mA max.
Yes
Power up: +1.2V dc spike for less than 0.4 ms
Power down: 1.2V dc spike for less than 21 ms
30V ac/30V dc
500V ac or 710V dc for 1 minute (qualification test)
Module OK LED
30V ac/30V dc working voltage (IEC Class 2 reinforced insulation)
On: module has power, has passed internal diagnostics, and is communicating over the bus.
Channel Diagnostics
Off: Any of the above is not true.
Over- or under-range by bit reporting
(1)
Output ripple is the amount a fixed output varies with time, assuming a constant load and temperature.
(2)
Repeatability is the ability of the output module to reproduce output readings when the same controller value is applied to it consecutively, under the same conditions and in the same direction.
(3)
Rated working voltage is the maximum continuous voltage that can be applied at the output terminal, including the output signal and the value that floats above ground potential (for example, 10V dc output signal and 20V dc potential above ground).
Publication 1769-IN076A-EN-P - July 2005
Compact 1769-OF4VI Isolated Analog Output Module 19
Specification
System Power Supply Distance
Rating
Recommended Cable
Vendor I.D. Code
Product Type Code
Product Code
Input Words
Output Words
Configuration Words
6
5
32
1769-OF4VI
The module may not be more than 8 modules away from the system power supply.
Belden 8761 (shielded)
1
10
42
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations only. The following ATTENTION statement applies to use in hazardous locations.
ATTENTION
EXPLOSION HAZARD
• Substitution of components may impair suitability for Class I,
Division 2.
• Do not replace components or disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
• Do not connect or disconnect components unless power has been switched off or the area is known to be non-hazardous.
• This product must be installed in an enclosure.
All wiring must comply with N.E.C. article 501-4(b).
Publication 1769-IN076A-EN-P - July 2005
20 Compact 1769-OF4VI Isolated Analog Output Module
Environnements dangereux
Cet équipement est conçu pour être utilisé dans des environnements de Classe 1, Division 2,
Groupes A, B, C, D ou non dangereux. La mise en garde suivante s’applique à une utilisation dans des environnements dangereux.
ATTENTION
DANGER D’EXPLOSION
• La substitution de composants peut rendre cet équipement impropre
à une utilisation en environnement de Classe 1, Division 2.
• Ne pas remplacer de composants ou déconnecter l'équipement sans s'être assuré que l'alimentation est coupée et que l'environnement est classé non dangereux.
• Ne pas connecter ou déconnecter des composants sans s'être assuré que l'alimentation est coupée ou que l'environnement est classé non dangereux.
Ce produit doit être installé dans une armoire.
Publication 1769-IN076A-EN-P - July 2005
Compact 1769-OF4VI Isolated Analog Output Module 21
For More Information
For Refer to this Document
A more detailed description of how to install and use your Compact I/O with MicroLogix 1500 programmable controller.
MicroLogix 1500 Programmable
Controllers User Manual
Detailed information on installing, programming, and troubleshooting your Compact Analog I/O modules.
Compact I/O Analog Modules User
Manual
A detailed description of how to install and use your Compact I/O with the 1769-ADN DeviceNet
Adapter.
1769-ADN DeviceNet Adapter User
Manual
An overview of the MicroLogix 1500 system, including Compact I/O.
More information on proper wiring and grounding techniques.
MicroLogix 1500 Programmable
Controller with Compact I/O for
Expansion
Industrial Automation Wiring and
Grounding Guidelines
Pub. No.
1764-UM001
1769-UM002
1769-UM001
1764-SO001
If you would like a manual, you can:
• download a free electronic version from the internet:
www.ab.com/micrologix or www.ab.com/literature
• purchase a printed manual by:
– contacting your local distributor or Rockwell Automation representative
– calling 1.800.963.9548 (USA/Canada) or 001.330.725.1574 (Outside USA/Canada)
1770-4.1
MicroLogix and Compact are trademarks of Rockwell Automation.
Belden is a trademark of Belden, Inc.
Publication 1769-IN076A-EN-P - July 2005
22 Compact 1769-OF4VI Isolated Analog Output Module
Notes:
Publication 1769-IN076A-EN-P - July 2005
Compact 1769-OF4VI Isolated Analog Output Module 23
Publication 1769-IN076A-EN-P - July 2005
Rockwell Automation Support
Rockwell Automation provides technical information on the web to assist you in using our products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com.
Installation Assistance
If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special
Customer Support number for initial help in getting your module up and running:
United States
Outside United
States
1.440.646.3223
Monday – Friday, 8am – 5pm EST
Please contact your local Rockwell Automation representative for any technical support issues.
New Product Satisfaction Return
Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned:
United States
Outside United
States
Contact your distributor. You must provide a Customer Support case number
(see phone number above to obtain one) to your distributor in order to complete the return process.
Please contact your local Rockwell Automation representative for return procedure.
Publication 1769-IN076A-EN-P - July 2005 PN 40071-205-01(1)
Copyright © 2005 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A
´H',%!¶1,¨
Advertisement
Key Features
- 4 isolated differential analog outputs
- Panel or DIN rail mounting
- Compatible with MicroLogix 1500
- Class I, Division 2, Hazardous Location, Groups A, B, C, D
- CE compliant for all applicable directives
- UL 508 listed
- C-UL certified
- Output range: ± 10V dc, 0 to 10V dc, 0 to 5V dc, 1 to 5V dc
- Resolution: 15 bits plus sign
- Conversion rate: 120 ms