GENERAL INFORMATION

The Gamewell Company thanks you for choosing the FLEXALARM 620 Conventional Control Panel to serve your monitor and control signaling needs. As with all our products we have taken great care to insure that we have provided a quality alarm control panel. To receive maximum benefit and many years of reliable service we would like to make the following recommendations:

1. Read this manual carefully and in it's entirety before proceeding with the installation of the Flex 620

Control Panel.

2. Never make any connections or perform any system programming with the power connected.

3. Gamewell spends many hours testing devices that are supplied by Gamewell to be used with it's control panels to verify compatibility. To maximize system performance, and minimize risk of damage to the equipment, we suggest using all Gamewell Components.

4. There is no substitute for proper maintenance and testing of this or any Life Safety product. Gamewell recommends testing and maintenance of your FLEX 620 system in accordance with the guidelines set forth by the National Fire Protection Association, be done on a regular basis, as a minimum.

5. This manual should be stored with the FLEX 620 Control Panel for future reference, and should not be removed.

Thank you again for choosing Gamewell. If you have any comments regarding your FLEX 620 Conventional

Control Panel, or other Gamewell products, please feel free to write us at:

The Gamewell Company

Product Marketing Department

60 Pleasant Street

Ashland, MA 01721

Phone: (508) 231-1400

Fax: (508) 231-0900

Technical Manuals Online! - http://www.tech-man.com

This page intentionally blank

Technical Manuals Online! - http://www.tech-man.com

Technical Manuals Online! - http://www.tech-man.com

This page intentionally blank

Technical Manuals Online! - http://www.tech-man.com

TABLE OF CONTENTS

S

YSTEM

O

VERVIEW

..................................................................................................................................................... 2

FLEX 620 Control Panel ..................................................................................................................................... 3

Modular Construction.......................................................................................................................................... 3

Common Control Module .................................................................................................................................... 4

S

YSTEM

I/O C

OMPONENTS

(600 S

ERIES

).................................................................................................................... 6

Initiating Module ................................................................................................................................................. 6

Indicating Module................................................................................................................................................ 6

600 Series Modules ............................................................................................................................................. 7

SYSTEM OPERATION ............................................................................................................................................... 9

C

OMMON

C

ONTROL

D

ISPLAY

- F

UNCTIONAL

D

ESCRIPTION

................................................................................... 10

CONTROLS ...................................................................................................................................................... 10

INDICATORS ................................................................................................................................................... 11

Standard Operating Display - (Legend Key Designators).................................................................................. 12

Module Displays................................................................................................................................................ 13

S

YSTEM

O

PERATING

C

HARACTERISTICS

.................................................................................................................. 14

Overview ........................................................................................................................................................... 14

Alarm Verification............................................................................................................................................. 15

And Initiating Circuit......................................................................................................................................... 16

S

YSTEM

O

PERATING

C

ONDITIONS

............................................................................................................................ 17

Default Mode..................................................................................................................................................... 17

Normal Quiescent Condition ............................................................................................................................. 17

(default) ............................................................................................................................................................. 17

Alarm Condition (default) ................................................................................................................................. 18

O

PERATING

P

ROCEDURES

......................................................................................................................................... 19

INSTALLATION........................................................................................................................................................ 24

Flex 620 System Housing .................................................................................................................................. 25

Hardware Assembly........................................................................................................................................... 26

Module Identification and Placement ................................................................................................................ 28

Main Power Supply ........................................................................................................................................... 30

Specifications..................................................................................................................................................... 30

Interconnects...................................................................................................................................................... 30

Auxiliary Power Supply..................................................................................................................................... 31

Interconnects...................................................................................................................................................... 31

Common Control Specifications........................................................................................................................ 32

Bus Driver Module ............................................................................................................................................ 35

CPU Module...................................................................................................................................................... 36

S

YSTEM

I/O C

OMPONENTS

(600 S

ERIES

).................................................................................................................. 38

Conventional Input Module .............................................................................................................................. 38

Conventional Input Module Terminal Description ............................................................................................ 39

Class "A" Adapter -Conventional Input Module - Terminal Description .......................................................... 39

Universal Signal Circuit Module ....................................................................................................................... 40

Universal Signal Circuit Module Terminal Description .................................................................................... 41

Class "A" Adapter - Universal Signal Module - Terminal Description ............................................................. 41

Technical Manuals Online! - http://www.tech-man.com

Relay Module .................................................................................................................................................... 42

Relay Module ................................................................................................................................................... 43

Relay Expansion Module................................................................................................................................... 43

Building Control Module................................................................................................................................... 44

Building Control Module................................................................................................................................... 45

City Tie Extender Module ................................................................................................................................. 46

Initial System Startup......................................................................................................................................... 47

FLEX 600 CONTROL PANEL......................................................................................................................... 48

COMPATIBLE SMOKE DETECTORS & BASES ......................................................................................... 48

FLEX 600 CONTROL PANEL......................................................................................................................... 48

COMPATIBLE AUXILIARY DEVICES ......................................................................................................... 48

FLEX 600 CONTROL PANEL......................................................................................................................... 48

COMPATIBLE INITIATING DEVICES FOR “AND“ ZONES...................................................................... 48

FLEX 600 .......................................................................................................................................................... 49

COMPATIBLE INDICATING APPLIANCES ................................................................................................ 49

FLEX 600 .......................................................................................................................................................... 50

COMPATIBLE INDICATING APPLIANCES (Cont.) .................................................................................... 50

PROGRAMMING ...................................................................................................................................................... 53

P

ROGRAMMING

O

VERVIEW

- F

LEX

A

LARM

620 ...................................................................................................... 54

Programming Options........................................................................................................................................ 55

Control By Event ............................................................................................................................................... 59

Access Levels .................................................................................................................................................... 60

Figure 4.1 Common Control Display - Operating Mode ................................................................................. 60

Password Entry .................................................................................................................................................. 60

Input Circuit - Programming.............................................................................................................................. 63

Output Circuit - Programming ........................................................................................................................... 64

Restoring Output Circuits .................................................................................................................................. 65

Programming Signal Circuit Special Functions ................................................................................................. 66

Control-By-Event - Programming...................................................................................................................... 67

C

OMPUTER

/L

APTOP

P

ROGRAMMING

O

VERVIEW

.................................................................................................... 68

Overviewof Computer Programming................................................................................................................. 68

Interconnect ....................................................................................................................................................... 68

Communication Protocol ................................................................................................................................... 68

P

ROCOMM

S

OFTWARE

............................................................................................................................................... 68

Configuration..................................................................................................................................................... 68

Line Settings ..................................................................................................................................................... 68

Setup Menu........................................................................................................................................................ 68

Terminal Setup ................................................................................................................................................. 69

General Setup ................................................................................................................................................... 69

ASCII Transfer ................................................................................................................................................. 70

S

YSTEM

M

ONITORING

& C

ONTROL

.......................................................................................................................... 70

Status Monitoring .............................................................................................................................................. 70

Access Levels .................................................................................................................................................... 70

Control Strings................................................................................................................................................... 70

S

YSTEM

P

ROGRAMMING VIA

C

OMPUTER

................................................................................................................. 71

System Menu ..................................................................................................................................................... 71

Display Menu .................................................................................................................................................... 71

Config Menu..................................................................................................................................................... 71

Display Config................................................................................................................................................... 72

Technical Manuals Online! - http://www.tech-man.com

System Configuration ........................................................................................................................................ 73

Codes Defined ................................................................................................................................................... 73

Modular Placement............................................................................................................................................ 73

Card Locations................................................................................................................................................... 73

0 through 7......................................................................................................................................................... 73

Cards # 8 - 39 .................................................................................................................................................... 73

Module Bus ....................................................................................................................................................... 73

Card ID # ........................................................................................................................................................... 73

Download Config.............................................................................................................................................. 75

Display Dict. Menu............................................................................................................................................ 75

Display Dict....................................................................................................................................................... 76

Download Dict................................................................................................................................................... 76

Display Events ................................................................................................................................................... 77

Display, Misc..................................................................................................................................................... 77

Display Pass....................................................................................................................................................... 78

Display Codes.................................................................................................................................................... 79

Display Ver........................................................................................................................................................ 80

Display Zone...................................................................................................................................................... 80

Change Menu..................................................................................................................................................... 81

Change Config ................................................................................................................................................... 81

Change Dictionary ............................................................................................................................................. 81

Change Dict.Words ........................................................................................................................................... 82

Upload Dictionary ............................................................................................................................................. 82

Dictionary File ................................................................................................................................................... 83

Change Card ...................................................................................................................................................... 84

Change Misc ...................................................................................................................................................... 84

Change Menu 1.................................................................................................................................................. 85

Change Pass....................................................................................................................................................... 85

Change Code...................................................................................................................................................... 86

Change Date ...................................................................................................................................................... 87

Change Seq ........................................................................................................................................................ 87

Change Baud...................................................................................................................................................... 88

Baud Rate Switch Settings................................................................................................................................. 88

Change Words ................................................................................................................................................... 89

Change Menu 2.................................................................................................................................................. 91

Change City ....................................................................................................................................................... 91

Change Sig Sil ................................................................................................................................................... 91

Change Ann ....................................................................................................................................................... 91

Change Trbl ....................................................................................................................................................... 92

Change Dialer .................................................................................................................................................... 92

Change Prefix .................................................................................................................................................... 92

Test Menu.......................................................................................................................................................... 93

Test Input........................................................................................................................................................... 93

Test Output ........................................................................................................................................................ 94

Test ID............................................................................................................................................................... 94

Test Gnd ............................................................................................................................................................ 95

Test Lamp .......................................................................................................................................................... 95

IDENTIFLEX 620 BATTERY CALCULATION CHART

............................................................................. 96

Technical Manuals Online! - http://www.tech-man.com

Technical Manuals Online! - http://www.tech-man.com

This page intentionally blank

Technical Manuals Online! - http://www.tech-man.com

Flex 620 System Description - Revision 5, 11/22/01

Section

1

FLEXALARM 620

System Description

System Overview

2

Technical Manuals Online! - http://www.tech-man.com

Flex 620 System Description - Revision 5, 11/22/01

FLEX 620

Control Panel

The Gamewell FlexAlarm 620 Conventional Alarm Control Panel is a limited energy fire, supervisory, alarm system consisting of a cabinet, I/O circuits, power supplies, and front panel displays. The Flex 620 is expandable to monitor, control and display up to 128 input/output circuits. It is available in two cabinet sizes, four bay and eight bay. The four bay cabinet (F624) will accommodate 4 of the 620 series modules in addition to the common control, power supply and batteries. The eight bay cabinet

(F628) will accommodate 8 of the 620 series modules in addition to the common control, power supply and batteries.

The design of the system utilizes a modular building block approach. Through selection of individual I/O modules (i.e. initiating, indicating and relay control modules, etc.) the user can customize the control panel for specific applications.

The Flex 620 control panel utilizes a unique initialization programming process,

SmartStart

. This initialization process stores the project specific system configuration in memory. Then a control-by-event table is automatically created that allows any system input to activate the system outputs. Upon completion of the initialization process the system is completely operable in a general alarm situation with the control-by-event data tables protected in non-volatile memory.

___________________________________________________________________________________________

Modular

Construction

The Flex 620 modular control panel consists of the common control section, conventional input module(s), universal signal module(s), relay module(s), building control module(s), city tie module(s), and power supplies. Other devices that can be used in conjunction with the Flex 620 system include the remote annunciators, printer interfaces and alphanumeric displays. These devices operate by means of the serial communications port which is isolated via an optional communications isolator module.

The cabinet utilizes dead front construction in either a four or eight bay arrangement.

The modules will conform to numerous system configurations that accommodate simple and complex systems.

____________________________________________________________________________________________

Technical Manuals Online! - http://www.tech-man.com

3

Flex 620 System Description - Revision 5, 11/22/01

Common

Control Module

Common

Control

Display

CPU Module

The common control module (CCM) or section consists of four modules; the common control display, the bus driver module, a relay expansion module, and the main CPU module.

The Common Control Display (CCD) is divided into two sections, the left and right displays. It provides the user with visual indicators (LED's) for status indication and guided prompts. The sixteen tactile switches are used to operate the system as well as enter data during system programming. All alarm, fault, supervisory and security status changes are annunciated by means of LED indication and the user is prompted with the proper sequence of operation. The "Power On" LED indicator is green, alarms or activated signal and city tie circuits are indicated by red LED's and faults are indicated by yellow LED's.

The CPU module (or micro processor module) contains the system operating firmware

Relay

Expansion

Module

and non-volatile memory. It provides all the processing functions and system memory as well as providing the local/remote communications interface.

The Relay Expansion Module (REM) provides 4 common relay circuits. When connected to the bus driver module this module provides

Common Alarm, Common

Trouble

and

Supervisory

Form C relay contacts. Each relay has a fused common rated at ten (10) amps. The expansion module mounts (via standoffs) to the right side of the bus driver module.

Bus Driver

Module

The Bus Driver Module (BDM) contains the circuitry that interfaces with the CPU module and the system modules. The bus driver module is equipped with two Style Y or Z, limited energy signaling circuits, a ground fault detection circuit and a city tie circuit. It has three power limited outputs, 24 Vdc auxiliary power, 12 Vdc, and resetable 24 Vdc smoke detector power. Circuitry to monitor the status of the CPU and set the system in a default mode of operation is also incorporated in the bus driver module.

___________________________________________________________________________________________

Common Control

Display

Bus Driver

Module

Relay Expansion

Module

CPU Module

620 Common Control Module

4

Technical Manuals Online! - http://www.tech-man.com

Flex 620 System Description - Revision 5, 11/22/01

Main

Power Supply

Lead Acid

Battery

Charger

Auxiliary

Power Supply

The main power supply (MPS-8) is an eight (8) amp DC supply. It provides 4 amps of regulated 5, 12, and 24 volt DC outputs and four amps of unregulated 24 volt DC power to the common control signal circuits. A battery charger and battery distribution block are incorporated into the Main Power Supply. A "Brown Out" protection circuit that will switch the main and any auxiliary power supplies to battery standby is also integrated into the supply. The main power supply mounts in the lower left hand corner of the cabinet and connects via interconnecting cables to the bus driver module.

The lead acid battery charger module is provided with the main power supply. The battery charger module is capable of charging and maintaining up to 60 AH batteries.

The auxiliary power supply (APS-8) provides eight (8) amps of unregulated 24 VDC power. Two (2), four (4) amp circuits are available from its connectors for signaling power expansion. The auxiliary power supply has provisions for receiving a signal from the main supply to switch to battery standby due to low (Brown out) or no primary input.

Main Power Supply (Left) Auxiliary Power Supply (Right)

Technical Manuals Online! - http://www.tech-man.com

5

Flex 620 System Description - Revision 5, 11/22/01

System I/O Components (600 Series)

___________________________________________________________________________________________

Initiating Module

Conventional

Input Module

CIM Display

The 600 series

Conventional Input Module

s (CIM-4 & CIM-8) are available in either

4 or 8 initiating circuits for monitoring of conventional detectors and contact type devices. Its corresponding display provides status indication and Bypass/ programming capabilities. Each zone can be programmed to meet the requirements of

NFPA Styles B (Class B). An optional Class A adapter may be used to meet the requirements of NFPA Style D if required.

The display module provides LED annunciation of

Alarm and Trouble

conditions and has one switch per zone for programming and bypass functions. The display has provisions for user defined custom labels per circuit. LED annunciation is indicated by - red - Alarm (active) and - yellow - Trouble.

___________________________________________________________________________________________

Indicating Module

Universal

Signal Module

USM Display

The Flex 600 series

universal signal modules

(USM-4 & USM-8) are a multi-function output modules available in either 4 or 8 circuit increments. These modules can be programmed to function as either notification appliance circuits, releasing circuits, speaker circuits or fireman's telephone circuits. When used as notification appliance circuits, these modules can be programmed for steady, 60PPM, 120PPM, temporal, zone coded or California UFC signaling outputs. These circuits are designed to meet the requirements of NFPA 72, Style Y notification appliance circuits. An optional

Class A adapter is available to meet the requirements of NFPA 72, Style Z notification appliance circuits.

The display module provides LED annunciation of

Alarm and Trouble

conditions and has one switch per zone for programming and bypass functions. The display has provisions for user defined custom labels per circuit. The module displays are supplied with user tactile switches per circuit. LED annunciation indication is - red -

Alarm (active) and - yellow - Trouble.

___________________________________________________________________________________________

6

Technical Manuals Online! - http://www.tech-man.com

Flex 620 System Description - Revision 5, 11/22/01

600 Series Modules

Relay Modules

The 600 series relay modules (RM-4 and RM-8) have been designed to supply 4 or 8

Form C relays for control of auxiliary functions. The relays are controlled by the main CPU and are fully field programmable. A feedback point for positive confirmation of activation has been supplied with each set of contacts. The relays are rated at 10 amps with a fused common to protect the internal circuitry.

The relay module display is provided with green (inactive) and red (active) LED's.

Relay Display

The tactile switches (per relay point) can be used to program, bypass or test the relay circuits.

___________________________________________________________________________________________

Building

Control

Module

The 600 series

building control modules

, (BC-4 & BC-8) along with their

On/Off/Auto switch display, are designed to provide an interface between the control panel and HVAC systems. The building control module is available in 4 or 8 circuit modules that are monitored and controlled by the MPU bus. Their relays are rated at

10 Amps with supervised feedback points for positive confirmation of the programmed action. Each Form A/B relay pair is programmable independently and fused on the relay common to protect the internal circuitry.

BCM Display

The building control module display provides LED annunciation (green - inactive, and red - active) indicating relay state or feedback. The display comes with tactile switches per circuit and a three position On/Off/Auto switch for manual override.

___________________________________________________________________________________________

City Tie

Module

The 600 series City Tie Module and its associated display provide 4 additional, limited energy, polarity reversal/city tie circuits to a system. Each circuit has independently programmable operation.

Module

Displays

The

city tie module displays

are supplied with red Alarm (active) and yellow Trouble

LED's with user tactile switches for programming, bypass and test per circuit.

Representative Inner Cabinet Module Assembly (USM, CIM, RM)

Technical Manuals Online! - http://www.tech-man.com

7

Technical Manuals Online! - http://www.tech-man.com

Section

2

FLEXALARM 620

System Operation

Technical Manuals Online! - http://www.tech-man.com

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

Common Control Display - Functional Description

CONTROLS

Acknowledge Switch The Acknowledge tactile switch (ACK), silences the internal buzzer of the panel. Any signal circuit, building control or relay programmed to return to the normal condition, when the "ACK" switch is depressed, will return to normal.

Should a second alarm occur, the circuits which had returned to normal will reactivate.

∆∆∆∆

WARNING !

Reset Switch

Signal Silence

Drill

Do not RESET the system until the Authority having

Jurisdiction has authorized reset.

The Reset tactile switch (RESET) removes power from the initiating circuits for a period of four (4) seconds. Power is temporarily removed from the S+ S- terminals, any devices latched into alarm should return to the normal condition

(provided the cause of alarm has been eliminated). The signal circuits, city tie, alarm relay and/or supervisory relay will restore and the panel will return to the normal quiescent condition.

The Signal Silence tactile switch (SIGNAL SILENCE ) will silence (i.e. return to normal), any signal circuit, building control point or relay that is programmed to restore on signal silence. The signal silence switch is alternating action switch. Pressing the signal silence switch will return the silenced circuits to an active state.

The Drill tactile switch (DRILL) will activate all circuits that have been programmed to sound when the Drill switch is pressed. The Drill switch is alternate acting, pressing the Drill switch again will deactivate the test.

∆∆∆∆

WARNING !

All circuits selected for WALKTEST become disable and will not Alarm the system should a real emergency occur.

WalkTest The Walktest tactile switch (WALKTEST) will provide a means for one man to test the devices in the system both silently and audibly. Walktest can only be completed in the

security access level 3 mode

. The access of the Walktest function is activated by depressing the Walktest switch and depressing the

"Enter" key. Any circuits may be selected for WalkTest. When the user has completed selecting the circuits (Initiation or Indicating i.e. signal), depress the

"Enter" key. If indicating signals were selected, these circuits will annunciate the alarm and troubles created on the initiation circuits. Should the circuit be placed in

alarm

, the signals will sound 2 short signals. Should the circuit be placed in

trouble

, the signals will sound 1 short signal. Should no signals be selected, the test will be silent. When an actual

alarm

occurs on a circuit not selected for WalkTest circuits, the system will go into full alarm sequence.

10

Technical Manuals Online! - http://www.tech-man.com

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

Bypass The Bypass tactile switch is used to disconnect a circuit that is damaged and cannot be cleared. Bypassing a circuit should only be a temporary solution to a problem and not a long term solution. Your service company should be advised immediately so full system operation may continue as soon as possible. When the Bypass switch is depressed it will illuminate the bypassed circuits LED's.

The bypass switch is an alternating action switch. Depressing the switch again will enable the bypassed circuit. Press "Enter" at the completion of the Bypass actions.

The "Enter" tactile key is used to request password access or system Enter programming and enter data while in the programming mode. It also provides the means to access system functions during WalkTest and bypass operations.

___________________________________________________________________________________________

INDICATORS

POWER ON

BATTERY FAULT

COMMON ALARM

PRE-ALARM

ANNUNCIATOR

FAULT

WALKTEST

EARTH FAULT

DRILL

ACKNOWLEDGE

SUPERVISORY

ALARM

BYPASS / ENABLE

The green "Power On" LED indicates AC line operation. When pulsing, this indicates a problem with the incoming AC line voltage, main or backup power supplies.

The yellow "Battery Fault" LED indicates a problem with the battery, or battery connections.

The common "Alarm" LED (red) indicates a common fire alarm has been activated in the system.

The common "PreAlarm" LED (red) indicates the system in a first stage alarm process.

The yellow "Annunciator" LED indicates a problem with a remote annunciator.

The yellow "WalkTest" LED indicates that part of the system is in the WalkTest mode. All zones that flash at the same rate as the WalkTest LED are in the

WalkTest mode.

The yellow "Earth Fault" LED indicates that the system's wiring is not adequately isolated from earth ground.

The Drill LED (yellow) indicates the Drill feature has been activated.

The Acknowledge LED's (yellow) illuminate to indicate the next action is to press the "ACK" switch.

The common Supervisory LED (yellow) indicates a supervisory zone has activated (alarmed).

The yellow "Bypass/Enable" LED indicates that part of the system is bypassed.

All points that flash at the same rate as the bypass/enable LED are bypassed.

11

Technical Manuals Online! - http://www.tech-man.com

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

(Indicators - continued)

CITY TIE

SIGNAL CIRCUIT 1

SIGNAL CIRCUIT 2

The City Tie LED's are red for alarm, flashing yellow for trouble and steady yellow to indicate transmission of trouble conditions.

The "Signal CIR 1" LED's are red for alarmed, yellow for trouble.

The "Signal CIR 2" LED's are red for alarmed, yellow for trouble.

RESET

TROUBLE

TROUBLE/SIL

SIGNAL SILENCE

SIGNAL SILENCE

SOUNDING

PASSWORD

REQUIRED

PASSWORD

ACCEPTED

The "Reset" LED (yellow) flashes when the reset switch is available for use.

The "Trouble" LED (yellow) indicates the system is not in the normal condition, or a fault is detected.

The yellow "Trouble/Sil" LED indicates that the system trouble has been acknowledged.

The yellow "Signal Silence" LED indicates the audible signals connected to the system are not sounding.

The yellow "Signal Silence" LED indicates the audible signals connected to the system are sounding.

The yellow "Password Required" LED indicates that the user must enter a password for further action.

The yellow "Password Accepted" indicates the password was accepted.

Standard Operating Display - (Legend Key Designators)

POWER ON

PRE-ALARM ANNUN. FAULT EARTH FAULT

FIRE

COMMON ALARM WALKTEST

DRILL

BATTERY FAULT

ACKNOWLEDGE

SUPERVISORY

SECURITY

BYPASS/

ENABLE

1

2

ALARM

CITY

TROUBLE

TIE

5

6

RESET

SIGNAL

SILENCE

COMMON TRBL.

TROUBLE

TRBL.

SILENCED

PASSWORD REQD.

ENTER

PASSWORD ACCEPT

3

4

ALARM

SIG CKT

TROUBLE

ALARM

7

SIG CKT

TROUBLE

8

Figure P-1, Standard Operating Legend

12

Technical Manuals Online! - http://www.tech-man.com

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

Module Displays

Alarm Display

(Standard)

The alarm display is a multi-purpose display module. The display module provides

LED annunciation of alarm conditions for input circuits, signal circuits, and the city tie.

The display layout is as follows; circuits 1 through 4 are fixed on the left side of the display (top to bottom). Circuits 5 through 8 are fixed on the right side of the display

(top to bottom). The display is complete with eight tactile switches, eight red LED's and eight yellow LED's. The eight "point" tactile switches, governing individual circuits, are used for programming, bypassing, and WalkTest (only zone and signal circuits can utilize the WalkTest function).

Relay Module

Display

The red LED indicates the circuit is;

!

alarm/alarmed,

!

activate/enabled.

The yellow LED (on steady) indicates;

!

trouble/fault,

!

!

off normal indication

!

or service is required

problem

!

!

check for open short or ground

The relay module display is used as a display module. The display is configured with relays 1 through 4 are fixed on the left side of the display (top to bottom). Relays 5 through 8 are fixed on the right side of the display (top to bottom). The display is complete with eight tactile switches, eight red LED's and eight green LED's. The eight

"point" tactile switches, governing individual circuits, are used for programming and bypassing the selected circuit.

The red LED (on steady) indicates;

!

alarm/alarmed,

!

activate/enabled

The green LED indicates;

!

normal

!

not

!

feedback point normal

In the programming mode, the green LED (on steady) indicates the relay is selected. If

Building

Control

Display

the green LED is flashing indicates the relay is bypassed.

The building control display is used as a control display module. Rotary switches provide for manual control of the relays. The switch is a three position

ON/OFF/AUTO. The normal position is (AUTO) and the system controls the operation of building control circuits. The other two positions are for manual control. The (ON) position activates the ON relay and (OFF) position activates the

OFF relay. The ON relays and/or OFF relays are unable to be active simultaneously on the same circuit.

The red LED (on steady) indicates;

!

alarm/alarmed,

!

activate/enabled.

The green LED indicates;

!

normal

!

not

!

feedback point normal

In the programming mode, the green LED (on steady) indicates the relay is selected.

If the green LED is flashing indicates the relay is bypassed.

13

Technical Manuals Online! - http://www.tech-man.com

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

System Operating Characteristics

Overview

The following sections briefly describe the Flex 620's operating characteristics under different general conditions. The system operation descriptions are intended as an overview to help familiarize users with the Flex 620. Careful review of this section of the manual will assist the user to understand many of the concepts and functions discussed later in this manual.

The section's titled

Fire Alarm Condition

and

Trouble Condition

describe the default operation of the Flex 620 in the Alarm and Trouble Modes. The

Supervisory

Condition

section describe general system operation for specific functions which must be programmed into your system.

Û

Note

: The following descriptions are not intended to provide detail operating information about your system. Detailed information about your Flex 620 system should be obtained from your system installer or authorized

Gamewell

distributor.

____________________________________________________________________________________________

Normal

Quiescent

Condition

When the system is in the normal quiescent condition (also referred as the Idle

Condition) the green power on LED is illuminated, indicating the system is operating from normal AC line power. All relay and building controls programmed with feedback will have the associated LED lit indicating either an active or inactive relay position. All other LEDs are extinguished, the system internal buzzer is silent, all switches are inactive (with the exception of the "

Enter

" button), and all indicating devices are inactive.

____________________________________________________________________________________________

Alarm

Condition

The Flex 620 will go into an

Alarm

condition when an initiation device activates on any alarm circuit. The associated circuit's red

Alarm

LED will light in a fast flash condition indicating the circuit where the initiation device is located. The form C common alarm relay will transfer, and the city tie circuit will be energized and will turn on its red

Alarm

LED. The common system internal buzzer will activate and can be silenced by depressing the

Acknowledge

switch. All auxiliary relay circuits will activate and illuminate the red

active

LED. All building control off relays will activate and illuminate the red "Off" LED. If feedback is connected for either the relay circuits or the building control the active LED to be lit during an

Alarm

state will be the reverse of the one that is lit during normal quiescent condition.

The

Alarm

LED(s) (slow flash for first alarm and steady for subsequent alarms) and the

Alarm

relay will remain energized, until the initiating device(s) have been cleared and the momentary reset switch is depressed. If there are multiple alarms the 1st alarm

LED will slow pulse after acknowledge, all others will go steady. The panel will remain in an alarm condition until all initiating devices are cleared and reset. At that time the panel will return to normal quiescent condition. Should the city tie be programmed for local energy master box trip, the city tie will be in trouble and box should be reset at this time.

14

Technical Manuals Online! - http://www.tech-man.com

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

Trouble

Condition

A trouble condition occurs when a fault or potential problem develops within the system, system components or system wiring connections. If a fault is detected, the system trouble LED will be illuminated on the display board with the associated fault

LED and the system trouble audible will be sounded. When the

Acknowledge

button

Supervisory

Condition

is depressed, the system trouble audible is silenced and the system trouble LED remains illuminated. Should another trouble occur the panel will return the trouble audible. When the trouble condition has been corrected the panel will extinguish the common trouble LED, returning the system to the normal quiescent condition.

A supervisory alarm condition occurs when a supervisory device activates on any supervisory alarm circuit. The associated circuit supervisory red

alarm

LED illuminates indicating the circuit where the supervisory device is located. The common system buzzer will sound, and the form C common supervisory alarm relay will transfer. Any signal, relay, city tie or building control circuit programmed to the supervisory circuit will activate. Any supervisory alarms that are cleared before the circuit is acknowledged will not latch in or need to be reset. The information will still be placed into the history log.

When the momentary Acknowledge switch is pressed, the common system buzzer will be silenced. If a subsequent supervisory alarm should occur in a different supervisory alarm circuit, the supervisory alarm LED for the new zone will illuminate, and the system trouble signal will reactivate.

The acknowledged supervisory alarm LED(s) will remain lit until the device(s) has

Acknowledged

Supervisory

Alarm

been cleared and the momentary reset switch has been depressed. If no further supervisory alarms exist in the system the panel will return to normal quiescent condition, otherwise the panel will return to supervisory alarm condition.

Should the supervisory alarm circuit be programmed to the city tie circuit, the city tie circuit that was programmed will transmit the alarm or trouble to the central station.

____________________________________________________________________________________________

Alarm

Verification

Alarm verification is used to reduce the occurrence of nuisance alarm conditions

(transient smoke etc.). Careful consideration should be taken before enabling the

Alarm Verification feature on any zone. Programming the Alarm Verification feature may delay the reporting of an actual emergency. Only those zones that are subject to conditions that require verification should be programmed with this feature.

Individual zones within the Flex 620 system may be programmed as verification zones. When this feature is enabled, all two wire automatic devices connected to the zone are subject to the alarm verification cycle.

Any two wire automatic device reporting an alarm condition, on a zone programmed for Alarm Verification., will start the pre-set verification timer (see Programming section), and the event will be recorded in the verification history log. At the expiration of the Verification Timer, the zone is automatically reset for a period of four seconds and the devices are allowed a stabilization period. After the device stabilization period a monitor cycle begins. If an alarm condition is detected during any portion of the monitor cycle the system will activate all of the associated control functions. If no other alarm conditions are reported during this period the system resumes normal operation. A short on the circuit will initiate an alarm immediately.

___________________________________________________________________________________________

15

Technical Manuals Online! - http://www.tech-man.com

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

And Initiating

Circuit

This circuit is a two-stage automatic detection zone that will operate as an

Automatic Alarm Initiating Circuit for the first two-wire smoke detector alarm reported to the panel. Should another two wire smoke detector go into alarm on the same AND circuit, a second alarm output will occur. This circuit is useful for a simple cross zone of two detectors. An example of typical application would be in an elevator lobby, where elevator capture doesn't occur until both detectors have alarmed. However, other normal alarm responses occur when the first detector activates. A short on the circuit will initiate a second stage alarm immediately.

___________________________________________________________________________________________

16

Technical Manuals Online! - http://www.tech-man.com

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

System Operating Conditions

____________________________________________________________________________________________

Default Mode

When shipped from the factory, the FlexAlarm 620 system has been initialized to a "default" configuration. In this default configuration:

1. All (input) initiating points are configured to be "Automatic Alarm" points

2. The system defaults to Security Level #2 (all features EXCEPT - programming enabled).

3. Whenever any input point(s) goes into alarm:

A. All output signaling circuits activate and produce a steady output.

B. All output relays are activated.

C. All building control "OFF" relays are activated.

D. The city-tie and common alarm relays activated.

___________________________________________________________________________________________

Normal

Quiescent

Condition

(default)

When the system is in the normal quiescent condition the green "Power On" LED is illuminated indicating the system is operating from normal AC line power. All input and output circuits are "normal" (no alarm or trouble conditions). All other

LED's and alphanumeric display are extinguished, the system internal buzzer is silent. Relay modules without feedback will indicate normal green LED “ON”.

In the normal condition, the green AC "Power-On" LED will be 'ON' - steady (upper left hand corner of the bus driver module display). Only the following keys will be active:

Enter

Password

The membrane push button switches on the building control module will be inactive.

The default for the rotary On/Off/Auto switch(es) is "AUTO". The Flex 620 system operating program controls the output.

Technical Manuals Online! - http://www.tech-man.com

17

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

Alarm

Condition

The Flex 620 will go into an ALARM state when any automatic alarm initiating points goes into an alarm condition. By default the following actions will occur:

(default)

1. The red "Alarm" LED on the bus driver module display will begin pulsing at an accelerated rate. The pulse rate is as a continuously repeating sequence of

1/4 second 'On' followed by 1/4 second 'Off'. The internal system buzzer will sound.

2. The red "Alarm" LED at the initiating point which reported the alarm will pulse at the accelerated rate. Alarm information is logged into the History

Buffer to provide a time stamped record of the event's occurrence.

3. The red Alarm LED on the bus driver module display for "City Tie" will be continually 'On' (steady) to indicate that the line-reversal city tie relay has been energized.

4. Signaling Circuits indication will be as follows;

A. The red alarm LED's on the bus driver module display for (Signal Circuit 1 and

Signal Circuit 2) will be 'On' (steady) to indicate that the signaling circuits have been energized.

B. If there are additional signal circuits in the system, each circuit's red Alarm

LED will be 'On' steady to indicate that the circuit has been energized.

5. Building Control Relay Circuits (if utilized):

A. If a building control circuit's feedback point is NOT connected, the circuit's red

LED will be 'On' steady to indicate that the "OFF" relay has been energized.

B. If a building control circuit's feedback point IS connected, the green LED is used to indicate normal (feedback point normal) and the RED active LED used to indicate an Alarm condition (feedback contacts shorted).

6. Relay Circuits:

A. If a relay circuit's feedback point is NOT connected, the circuit's red LED will be 'On' steady for each active relay point to indicate that the relay has been energized.

B. If the relay circuit's feedback point IS connected, the green LED is used to indicate normal (feedback point normal) and the RED active LED used to indicate an Alarm condition (feedback contacts shorted).

7. Both yellow LED's on the bus driver module display "acknowledge" switch will pulse at the accelerated rate. This guided prompt feature shows the user that the next expected action is to press "ACK", acknowledging the alarm condition.

___________________________________________________________________________________________

18

Technical Manuals Online! - http://www.tech-man.com

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

Operating Procedures

Acknowledging the Alarm

When the user presses the "ACK" switch to acknowledge an alarm condition, the following actions will occur:

Condition

1. The control panel's internal audible buzzer will (always) silence.

2. The acknowledge key's activation is logged into the History Buffer to provide a time stamped record of the event's occurrence.

3. The red Alarm LED on the first initiating point reporting an alarm will change from pulsing at the accelerated rate to a slower rate. The slower rate is defined as a continuously repeating sequence of 1/2 second 'On' followed by 1/2 second 'Off'.

!

If there are subsequent initiating points in alarm, the associated red Alarm

LED(s) will change from pulsing at an accelerated rate to "On' steady. All previously acknowledged point-in-alarm continue to have their red Alarm

LED's 'On' steady.

4. The two yellow LED's on the bus driver module display acknowledge "ACK" switch will stop pulsing and extinguish. Any outputs programmed to return to the normal condition upon pressing the "ACK" switch will return to normal at this time.

5. Both yellow LED's on the bus driver module display for the RESET and signal silence switches will pulse at the accelerated rate. This "guided prompt" feature notifies the user that the next expected action is to

Reset

the system or silence the signals.

___________________________________________________________________________________________

Signal Silence

If Signal Silence option is programmed, the yellow LED for the signal silence switch will pulse at an accelerated rate. This guided prompt feature notifies the user that it is possible, but not necessary, to press the SIGNAL SILENCE switch

In the

default mode

, all signal circuits will silence.

If the user presses the SIGNAL SILENCE switch, the following actions will occur:

1. The yellow LED for the SIGNAL SILENCE switch will be pulsing,.

2. All output signal circuits which have been programmed to silence when the

SIGNAL SILENCE switch is activated (which is all output circuits in the

"default" case) will silence.

19

Technical Manuals Online! - http://www.tech-man.com

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

Resound or

Return of

Signals

The signal silence switch is alternating action switch. If the user subsequently presses the SIGNAL SILENCE switch again, the signal circuits will activate.

1. The lower yellow LED for the SIGNAL SILENCE switch will extinguish.

2. The yellow LED for the SIGNAL SILENCE switch will pulse.

3. All the output signal circuits which had de-activated will re-activate returning the system status to the original alarm condition.

___________________________________________________________________________________________

Reset

After the initiating device(s) have been restored (i.e. cleared to normal condition), the momentary

Reset

switch should be depressed. When the user presses the

RESET switch the following actions will occur:

1. All signal circuits will deactivate.

2. All output relays circuits programmed for "immediate reset" will deactivate without delay (**

System default

**). The control panel will return to the normal condition.

3. If any output relay circuits are programmed for sequential reset, the highest circuit so programmed will de-activate first. Four seconds later the next highest addressed programmed will de-activate. This pattern will continue until all of the sequentially reset relays have been de-activated.

4. Power will be removed from all initiating input points for four (4) seconds to restore any latched devices.

5. The RESET key's activation is logged into the History Buffer to provide a time stamped record of the event's occurrence.

6. The control panel will re-enter into the normal quiescent condition.

20

Technical Manuals Online! - http://www.tech-man.com

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

BYPASS

Programming

Bypass is used to disable input and output circuits. To use the Bypass option, enter the proper Access level and press the Bypass key. The LED will flash at a fast rate indicating that you are in the Bypass circuit selection mode. Select the desired input and output circuits to be Bypassed and press the Bypass key again. The selected circuit(s) and Bypass LEDs should flash at the same rate indicating the circuits are

Bypassed. To deselect circuits, press the Bypass switch (Bypass LED Flashes fast)

Deselect circuits and press the Bypass switch again. Circuits deselected will extinguish.

A. Input Points Bypassed

When the Bypass is utilized it will disable an input circuit that is damaged and cannot be cleared.

B. Output Signal Circuit Bypassed

Programming any output signal circuit to Bypass will disable the circuit from activating.

C. Output Relay Circuits bypassed

Programming any output relay circuit to Bypass will disable the circuit from activating.

D. Building Control Circuits bypassed

Programming any building control circuit to Bypass will disable the circuit

WALKTEST

Programming

from activating.

E. City Tie(s) bypassed

Programming any City Tie circuit to Bypass will disable the circuit from the transmitting alarm.

WalkTest is designed to allow 1 man to test the fire alarm system. To WalkTest the system select the WalkTest switch (WalkTest LED flashes fast), select the circuits to be tested and press the WalkTest switch again. The circuits in WalkTest mode will flash at the same rate as the WalkTest LED. To deselect circuits, press the WalkTest switch (WalkTest LED Flashes fast) Deselect circuits and press the WalkTest switch again. Circuits deselected will extinguish.

A. Input Points Assigned To WalkTest

Any initiating circuits (Conventional Input Modules) may be selected for

WalkTest. Any selected Input circuits will not activate any outputs that are not selected for WalkTest. When the user has completed selecting the circuits press the "

ENTER

" key. Then select the output circuits or press enter again.

B. Output Signal Circuits Activated During WalkTest

Any indicating circuits (Universal Signal Modules) may be selected for

WalkTest. When the user has completed selecting the circuits press the

"Enter" key. The selected indicating signals will annunciate any alarm with two short outputs and troubles created will sound one short output.

21

Technical Manuals Online! - http://www.tech-man.com

Technical Manuals Online! - http://www.tech-man.com

This page intentionally blank

Technical Manuals Online! - http://www.tech-man.com

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

Section

3

FlexAlarm 620

Installation

24

Technical Manuals Online! - http://www.tech-man.com

C-W846

C-W846

C-W848

C-W848

C-W849

C-W849

C-W845

C-W846

C-W861

C-W856

C-W857

Flex 620 Installation - Revision 5, 11/22/01

___________________________________________________________________________________________

Flex 620 System

Housing

The base Flex 620 system control panel comes complete in two different size housings. The F624 model is a four bay cabinet enclosure and the F628 is an eight bay cabinet enclosure. The F624 model holds 4 of the 600 series modules in addition to the common control, power supply and batteries. When the cabinet used as an expansion unit, the cabinet accommodates 4 additional modules, an additional power supply with a battery storage area. The F628 model holds 8 of the 600 series modules in addition to the common control, power supply and battery storage. As an expansion cabinet, it can house an additional 8 modules plus a power supply with available area for battery storage.

The housings are designed with ample field wiring space and conduit knockouts mounting options. The control panel's main power supply with transformer independently mounts to the chassis. The unit's dead front design allows all operation, programming and user interface to take place without exposure of the system modules or field wiring. Field wiring terminals which the modules plug into are mounted directly to the backbox for ease of installation and servicing. Modules can be removed for servicing without disturbing field wiring. Systems are all factory assembled.

Refer to the flowing table for applicable installation wiring diagrams. Wiring diagrams are found at the end of this manual. All field wiring must be in accordance with N.F.P.A. pamphlet #70 article #760.

Drawing #

D-W1142

Issue Date

3/29/94

Part No. Title

Wiring, Minimum System Flex 620

Module Display P/N

C-W847

C-W845

C-W845

3/29/94

3/28/94

3/28/94

30879

30868-01

30868

Bus Driver Module

Initiating Module 4 Circuit (CIM-4)

Initiating Module 8 Circuit (CIM-8)

30870-02

30870-02

3/29/94

3/29/94

3/29/94

3/29/94

7/7/94

7/7/94

3/28/94

3/29/94

3/31/94

3/28/94

3/28/94

30878-01

30878

30873

30874

30871

30872

30869

30940

30875

30889

Indicating Module 4 Circuit (USM-4)

Indicating Module 8 Circuit (USM-8)

Relay Module 4 Circuit (RM-4)

Relay Expander Module (RM-4E)

Building Control Module (BC-4)

Building Control Expander (BC-4E)

Class "A" Adapter (CIM-SDA)

Class "A" Adapter (USM-SZA)

City Tie Extender Module (CTX-4)

Main Power Supply 8 Amp (MPS-8)

30890 Aux. Power Supply 8 Amps (APS-8)

Table I-1, Installation Wiring Diagrams

30870-02

30870-02

30870-03

30870-04

30870-02

Technical Manuals Online! - http://www.tech-man.com

25

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

Hardware

Assembly

Systems are all factory assembled. The 600 series modules will be positioned within a cabinet (reading left to right, top to bottom) in the following order.

Blank dress plates will be supplied for any unused module bays.

1. CIM(Conventional Input Module -

Initiating Module

)

2. USM (Universal Signal Module -

Indicating Module

)

3. RM (Relay Module)

4. BC (Building Control Module)

5. CTX (City Tie Expander)

6. APS (Auxiliary Power Supply)

Û Note: Upon receiving control panel, remove all packaging materials. Inspect for any damage that may have occurred during shipment. Notify the manufacturer immediately if damage is detected.

Flex 620

Control Panel

Mounting

Complete the following instructions to mount the Flex 620 control panel. The instructions are applicable for either the F624 or F628 housings. All control panel displays as well as the power supply are not installed and are shipped separately. Refer to drawing D-W1142, Wiring, Minimum System Flex 620.

___________________________________________________________________________________________

Cabinet Dimensions

F624 (4) Bay Cabinet

Dimensions

Battery Storage

Weight

F628 (8) Bay Cabinet

Dimensions

Battery Storage

37.2"H x 24"W x 6"D

8"H x 14.25" x 6"D approx. 65 lbs

52.25"H x 24"W x 6"D

8"H x 14.25" x 6"D

Weight approx. 75 lbs

Table I-2, Cabinet Dimensions

___________________________________________________________________________________________

26

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Installation - Revision 5, 11/22/01

___________________________________________________________________________________________

Cabinet Mounting and Assembly Procedure

1. Unlock the front panel door. Lift up and remove.

2. Remove the mounting screws securing the three horizontal cross rails.

CAUTION !

Protect all cabinet components when mounting the control panel to the foundation. Failure to cover enclosed circuit boards from debris (metal shavings, dust etc.) may damage components.

3. Secure the cabinet to the mounting foundation. Connect all conduit and secure.

4. Connect all field wiring. Reference all installation wiring diagrams as required. (All field wiring must be in accordance with N.F.P.A. pamphlet #70 article #760.) Ensure the cabinet is clean.

5. Secure the main power supply module (MPS-8 p/n 30889) to the main chassis. Plug in the battery charger card. If applicable, connect the auxiliary power supply (APS-8) in accordance with drawings D-W1142, C-W856 and C-W857.

6. Mount the three cross rails and secure (if disassembled).

7. Mount the common control display into the alignment pins of the top cross rail. Mount the two display (for initiating, indicating, building control module etc.) into alignment pins of cross rails.

8. Connect the following interconnecting cables (ribbon and power cables). Reference drawing D-W1142 all applicable wiring diagrams shown in above Table 1.

A. Ribbon cable (p/n 71157) interconnecting the bus driver module (J11) to the common control display.

B. Ribbon cable (p/n 71158) interconnecting CPU module (ISBX1) and bus driver module

(P1).

C. 4 conductor interconnecting cable (p/n 30881) from CPU module (P3) to the bus driver module (J13 - CPU power).

Note: All dual part numbers listed below refer to the correct cables for 4 and 8 bay cabinets respectively

D. Ribbon cable (p/n 71156/71161) interconnecting left display bus and the bus driver module (J6).

E. Ribbon cable (p/n 71155/71160) interconnecting left I/O module bus with the bus driver module (J5).

F. Ribbon cable (p/n 71156/71161) interconnecting right display bus and the bus driver module (J7).

G. Ribbon cable (p/n 77154/71159) interconnecting right I/O module bus with the bus driver module (J8).

H. Power cable (p/n 30883) from the power supply (J3) to bus driver module (J16).

I. Power cable (p/n 30882-01) from the power supply (J2) to bus driver module (J12).

9. Plug in battery charger card.

___________________________________________________________________________________________

Technical Manuals Online! - http://www.tech-man.com

27

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

Module Identification and Placement

Module Bus

The Module bus interconnects the I/O modules and the display modules with the bus driver module. The left I/O modules are linked (via ribbon cable) with the bus driver module at the J5 connector (labeled I/O Left). The left display modules are linked (via ribbon cable) with the bus driver module at the J6 connector (labeled

Display Left). The right I/O modules are interconnected at the J8 connector

(labeled I/O Right), and the right display modules are linked at the J6 connector

(labeled Display Right). Each I/O module and its associated display occupies one bay of the system cabinet.

___________________________________________________________________________________________

Module

Addressing

Cards # 0 - 7

Cards # 8 - 39

Circuit #

Assignments

The Flex 620 system utilizes a unique addressing scheme that allows it to monitor

card locations

and supervise the

card types

within the locations. There are 40 card locations within the Flex 620 system. Upon initialization, each card location returns a

card type

code when polled by the main CPU. Card type codes are fixed codes that are pre-assigned to each type of module. When a valid

card type

response from a

card location

is detected, a data base is created for it. The specific card type codes are defined in the programming section of this manual.

Card locations 0 through 7 are pre-assigned to the common control section of the system . These locations define the circuits present in the common control section

(operating display signal circuits, city tie, etc.).

Card locations 8 through 39 are the optional modules installed in the cabinet bays see Figure I-1. Each module (I/O module or display module) has a programmable addressing jumper which is designated as S1. This jumper must be set according to the physical placement of the module within its I/O or display bus. If the module is the first module (vertically top to bottom) within its bus, the S1 jumper should be located in position 1. If the module is the second module within the bus, its S1 jumpers should be located in position 2, and so on. This jumper placement determines the card location of the module. Each bus has four card locations preassigned to it. The left I/O bus has card locations 8-11 assigned to it. The left display bus has card locations 12 - 15, the right I/O bus has card locations 16 - 19 and the right display bus has card locations 20 - 23 assigned to them. This same sequence is repeated in the expander cabinet accounting for card locations 24 - 39.

Circuit assignments are also predefined within the system. Each cabinet bay has 8 circuits reserved for it. From Left to right, top to bottom the circuits are allocated to each bay in 8 circuit increments. Beginning with the top left bay the circuit assignments are 1 - 8. The top right bay is assigned circuits 9 - 16, and so on. The expansion cabinet’s top right bay would have circuits 65 - 72 assigned to it regardless of the main cabinet‘s size, module placement or the card types installed.

If a card does not require all 8 of the circuit assignments allocated to its bay, the lowest circuit numbers associated with that bay will be assigned to its circuits.

28

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Installation - Revision 5, 11/22/01

___________________________________________________________________________________________

FLEX 620 CABINET ASSEMBLIES - (4 Bay & 8 Bay Cabinets Shown)

Common Control Section

Cards ID# 0 - 7

L

A

Y

D

I

S

P

B

U

S

Display Module

(Left)

L

E

B

M

O

D

U

U

S

I/O Modules

(Left)

I/O Modules

(Right)

L

E

B

M

O

D

U

U

S

Display Module

(Right)

L

A

Y

B

D

I

S

P

U

S

12 jumper to 1

13 jumper to 2

14 jumper to 3

15 jumper to 4

8

Ckt. 1-8 jumper to 1

9

Ckt. 17-24

jumper to 2

10

Ckt. 33-40

jumper to 3

11

Ckt. 49-56

jumper to 4

16

Ckt. 9-16

jumper to 1

17

Ckt. 25-32

jumper to 2

18

Ckt. 41-48

jumper to 3

19

Ckt. 57-64 jumper to 4

FLEX 620

Expansion Cabinets w/Bus Extender

20 jumper to 1

21 jumper to 2

22 jumper to 3

23 jumper to 4

L

A

Y

B

D

I

S

P

U

S

Display Module

(Left)

L

E

B

M

O

D

U

U

S

I/O Modules

(Left)

I/O Modules

(Right)

L

E

B

M

O

D

U

U

S

Display Module

(Right)

L

A

Y

B

D

I

S

P

U

S

28 jumper to 1

29 jumper to 2

30 jumper to 3

31 jumper to 4

24

Ckt. 65-72

jumper to 1

25

Ckt. 81-88

jumper to 2

26

Ckt. 97-104

jumper to 3

27

Ckt. 113-120

jumper to 4

32

Ckt. 73-80

jumper to 1

33

Ckt. 89-96

jumper to 2

34

Ckt. 105-112

jumper to 3

35

Ckt. 121-128

jumper to 4

36 jumper to 1

37 jumper to 2

38 jumper to 3

39 jumper to 4

Figure 3-1, Cabinet Module Locations

29

Technical Manuals Online! - http://www.tech-man.com

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

Main Power

Supply

Installation

Diagram

The main power supply (p/n 30889) is a combination 8 amp system power supply and battery charger. It provides the system with five supplies (a 24Vdc regulated,

24Vdc unregulated, 12Vdc, 5Vdc and the battery charger). The standard battery charger is sized to maintain up to 60 AH batteries. The battery charger is designed to operate during set intervals extending the battery life of the lead acid batteries.

When installing 5 - 20 AH batteries remove R17 (both resistors) from the battery charger card (P/N 30843). When installing 21 - 40 AH batteries remove R1.

Refer to drawings C-W856 Main Power Supply and D-W1142 Wiring, Minimum

System Flex 620 for installation and cable connections. When applicable, refer to

C-W857 Aux. Power Supply.

___________________________________________________________________________________________

Specifications

Input Voltage 120 VAC 50/60 Hz 3 amps Max. (Optional 220V AC available)

Output Voltage 24 Volt DC regulated @ 4 Amps - system power, S+ S- and A+ A-

{

XE "\"Smart Start\""

}

24 Volt DC filtered @ 4 Amps - for signal circuit power

5 Volt DC regulated - supply for logic circuits

12 Volt DC regulated @ 2 Amps

Operating Temperature 0 to +49 degrees C

Humidity 85% non-condensing

Interconnects

24 VAC

C+, C-

BO

(Brown-out Output)

B+, B-

(2) secondary transformer connection

Connection (Red, Black) to Filter Capacitor

Brown Out - connects to auxiliary power supply BI

(Brown-out Input) terminal

(Red, Black) connections to Battery Distribution Block

J4 connector

J3 connector

Not used on F620 System

Interconnects to J16 on bus driver module

J2 connector Interconnects to J12 on bus driver module (5V, 12V, and

24V supervision)

___________________________________________________________________________________________

30

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Installation - Revision 5, 11/22/01

___________________________________________________________________________________________

Auxiliary Power

Supply

Auxiliary Power supply (p/n 30890) is a 8 amp auxiliary supply, which mounts into one module expansion slot. It provides the system with 24 VDC auxiliary power full wave rectified and filtered. Two 4 amp outputs are provided for signaling or auxiliary power.

Note:

Terminals Black, Red are not power limited outputs.

Interconnects

Card APS-8 Terminal

Designation

Description

OUTPUT

J1 connector

RED +24VDC auxiliary power (4 amps available for signal circuits)

J1 connector

BLK

J1 connector

J2 connector

J2 connector

J2 connector

POWER

WHT

RED

BLK

WHT

B+

B-

BO

BI

-24VDC auxiliary power (4 amps available for signal circuits)

Monitor point for AC/Battery fault

+24VDC auxiliary power (4 amps available for signal circuits)

-24VDC auxiliary power (4 amps available for signal circuits)

Monitor point for AC/Battery fault

Battery +24V Input

Battery -24V Input

Connect to next aux. power supply terminal “BI”

24VAC

From terminal "BO” of main power supply or previous aux. power supply

24VAC from transformer

24VAC 24VAC from transformer

Technical Manuals Online! - http://www.tech-man.com

31

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

Common

Control

Specifications

The specifications listed identify the interfacing modules housed in the common control section; the common control display module, the bus driver module, a relay expander card, and the CPU module.

Common Control

Input Power

Quiescent Current

Alarm Current

24VDC

275 mA

407 mA plus Signal Circuit power plus 2mA for master box or 22 mA for reverse polarity

Auxiliary Output

Smoke Detector

Power

Security Power

City Tie

1

2

3

4

5

6

7

Designation

A+

A-

S+

S-

(+)12

(-)12

M1

21 VDC, 2 Amps regulated auxiliary power*

21 VDC Common*

21 VDC @ 125mA, resetable regulated power

*

(4 second reset time)

21 VDC common *

12VDC, 2 Amps regulated power common for +12VDC

Connections for master box or line reversal option.

Line Reversal - 24VDC @ 15mA nominal

Signal Circuit 1

Signal Circuit 2

8

9

10

11

12

13

14

15

16

M2

1L1R

1L1

1L2

1L2R

2L1R

2L1

2L2

2L2R

Signal CCT#1, [email protected], Style Y or Z

Style Z (+) Return

(+) Signal Power (normal condition) **

(-) Signal Power (normal condition) **

Style Z (-) Return

Signal CCT#2, [email protected], Style Y or Z

Style Z (+) Return

(+) Signal Power (normal condition) **

(-) Signal Power (normal condition) **

Style Z (-) Return

* Note 1 : Total load of regulated power including system power, A+ A- and S+S- must not exceed 4 amps.

**Note 2 : Style Y signal circuit wiring requires 3.9K EOL resistor.

32

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Installation - Revision 5, 11/22/01

___________________________________________________________________________________________

Relay Expander

Card

The relay expansion module provides four programmable relay circuits with Form

C (normally open) contacts. When connected to the bus driver module this module provides for

Common Alarm, Common Trouble,

and

Supervisory Alarm

relay. Each relay has a fused common rated at ten (10) amps and provides

Installation

Diagram

positive feedback for status indication. Each relay on the bus driver module draws 22mA when activated. In normal operation only the trouble relay is activated.

The system initialization determines if the feedback loop is utilized. A feedback circuit must have less than 50 ohms in loop resistance. The

function of relays (K1 - K4):

Relay K1 Common Alarm

Relay K2

Relay K3

Relay K4

Common Trouble (Relay is normally energized)

Common Supervisory

AC failure when dialer is enabled or city tie trouble when

Chicago mode is enabled.

Refer to (drawing # D-W1143) for wiring the Relay Expander Card.

No switch settings are required. Card location identification number is "5".

Cable Connection & Notes

J2 Connector

F1 fuse

F2 fuse

F3 fuse

F4 fuse

Interconnection (ribbon cable) to J17 connector on the bus driver module

10 Amp overload protection K1 relay

10 Amp overload protection K2 relay

10 Amp overload protection K3 relay

10 Amp overload protection K4 relay

___________________________________________________________________________________________

Technical Manuals Online! - http://www.tech-man.com

33

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

Relay Expander Card

RELAY 1

COMMON

ALARM

Terminal # Designation Description

1 1 NO Normally open Alarm contact

2 1 NC Normally closed Alarm contact

3

4

1 C

1 M

Alarm relay common contact 10A @ 30 VDC or 220

VAC resistive, fused @ 10 amps.

Alarm relay feedback point to monitor status of controlled device

RELAY 2

COMMON

TROUBLE

Terminal # Designation * Relay is shown normally energized (normal condition)

5

6

7

8

2 NC

2 NO

2 C

2 M

Normally closed Trouble contact

Normally open Trouble contact

Trouble relay common contact 10A @ 30 VDC or

220 VAC resistive, fused @ 10 amps.

Trouble relay feedback point to monitor status of controlled device

RELAY 3

COMMON

SUPERVISORY

Terminal #

9

10

11

12

Designation

3 NO

3 NC

3 C

3 M

Description

Normally open Supervisory contact

Normally closed Supervisory contact

Supervisory relay common contact 10A @ 30 VDC or 220 VAC resistive, fused @ 10 amps.

Supervisory relay feedback point to monitor status of controlled device

RELAY 4

SPARE

Terminal #

13

14

15

16

Designation

4 NO

4 NC

4 C

4 M

Description

Note: When the City Tie is programmed in the Chicago mode the spare relay will transfer during City Tie circuit faults.

Normally open spare contact

Normally closed spare contact

Spare relay common contact 10A @ 30 VDC or 220

VAC resistive, fused @ 10 amps.

Spare relay feedback point to monitor status of controlled device

34

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Installation - Revision 5, 11/22/01

___________________________________________________________________________________________

Bus Driver

Module

The bus driver module contains the circuitry that interfaces with the CPU module and the system modules. The bus driver module is equipped with two Style Y or

Z, limited energy signaling circuits and a city tie circuit.

The bus driver module provides the system with the following :

Controls default alarm bus if the CPU fails

Monitors system modules for placement

Monitors system for ground faults

Watchdog

Programmable Signal Circuits (1 & 2)

Auxiliary Power Outputs (A+/A-, S+/S-, +/- 12VDC)

City Tie

Programming

The internal circuitry draws about 18mA from the +24V power supply with both signal circuits terminated with a 3.9K ohm resistor (with no current draw on the city tie circuit). Each relay on the bus driver module draws 22mA when activated.

In normal operation only the trouble relay is energized.

The bus driver module contains three jumpers for city tie programming (J1, J2, &

J3) located in the center of the board. These three jumpers are used to select the reverse polarity or the master box option for the city tie connection.

City Tie Programming -

Set jumpers as follows: J1

Reverse Polarity

Master Box

X = jumper installed

X

J2

X

J3

X

Installation

Diagram

Refer to drawings D-W1142, Wiring Minimum System Flex 620 and C-W847,

Bus Driver Module.

Cable Connections

P1 Connector

J5 Connector

J6 Connector

J7 Connector

J8 Connector

J9 Connector

J11 Connector

J12 Connector

J13 Connector

J16 connector

J17 Connector

Interconnect (ribbon cable) to IBX1 on the CPU module

Interconnect (ribbon cable) to Left I/O modules

Interconnect (ribbon cable) to Left Display modules

Interconnect (ribbon cable) to Right Display modules

Interconnect (ribbon cable) to Right I/O modules

Interconnect (ribbon Cable) to Cabinet Expander

Interconnect (ribbon cable) to P1 on the common control display

Cable connector to J2 - Power Supply

Cable connector to P3 - CPU module

Three conductor cable to J3 power supply

Interconnect (ribbon cable) to J2 on the Relay Expander Card

Technical Manuals Online! - http://www.tech-man.com

35

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

CPU Module

The CPU module (or micro processor module) contains the system operating firmware and non-volatile memory. It provides all the system memory and processing functions as well as providing the local/remote communications and supervision. System field programming, via a laptop PC link, is accomplished utilizing the P2 interface. The CPU module jumper settings are preset at the factory and do not require any field programming. Do not place any jumpers on the module.

The settings of DIP switch SW1 regulates the system's baud rate. The switch settings are preset at the factory; see SW1 default settings table.

The module contains a serial communications port for serial device interface

(Isolated RS-232 Card). To install, the U18 IC must be removed from its socket and replaced with the interconnecting cable from the Isolated RS-232 Card.

SW1 - Default Settings

S1 Open

S2

S3

S4

Open

Always Closed

Open

S5

S6

S7, S8 Open

S7, S8 Closed

S7 Open, S8 Closed

S7 Closed, S8 Open

Open

Open

9600 Baud Rate

4800 Baud Rate

2400 Baud Rate

1200 Baud Rate

Do Not Change

Do Not Change

Do Not Change

Do Not Change

Do Not Change

Do Not Change

DIP Switch SW1 Table

LED Indication

All four LED's "On" Hardware Reset

D1 "On" only

D2 "On" only

D3 "On" only

D4 "On" only

not used not used not used not used

Cable Connections:

IBX1 connector Interconnection (ribbon cable) to P1 connection on the bus driver module

P2 connector

P3 connector

P4 (pins 3 & 4)

U18 socket

Interconnection (ribbon cable) programming link, via laptop PC for system field

Interconnecting cable for CPU power via J13 connector on the bus driver module

System Hardware Reset (momentary short) jumper pins

Interface socket for the 16 pin ribbon cable provided for the

Isolated RS232 Card

36

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Installation - Revision 5, 11/22/01

___________________________________________________________________________________________

Common

Control

Display

The common control display (CCD) is the main interface to the system. The display

(i.e. left bus driver display and right bus driver display) provides the user with all necessary switches and annunciation points to maintain and monitor the system.

Alarm, supervisory and trouble conditions are indicated by dedicated LED's and the

Installation

Diagram

internal sounder. LED annunciation is also provided for AC power, PreAlarm, (2) signal circuits, City Tie connection and Bypass.

Refer to (drawing # D-W1142) Wiring, F620 Minimum System. The 34 pin ribbon cable (p/n 71157) interconnects the CCD to the bus driver module (J11 connector).

Power Requirements

2mA operating current

1mA for each Red LED (ON)

6mA for each Yellow or Green LED (ON)

Note: When the CIM-4 and CIM-8 circuits are programmed as AND zones types

use only Gamewell 70133,70134 and 70135 detectors.

___________________________________________________________________________________________

Technical Manuals Online! - http://www.tech-man.com

37

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

System I/O Components (600 Series)

Conventional

Input Module

Circuit

Module

Style "D"

Adapter

Display

Module

The conventional input module (CIM) consists of up to 3 assemblies. The

I/O

Circuit module

, the

Style D (Class A) adapter

, and the

Alarm Display

. To view a comprehensive listing of compatible devices with the Flex 620 control panel, refer to

Figure 3-3, Compatible Initiation Devices found at the end of this section. Also refer to Figure 3-4, Compatible Auxiliary Devices for comprehensive listing of auxiliary devices.

The circuit module provides four (CIM-4) or eight (CIM-8) conventional circuits.

All circuits operate on the Style B (Class B) mode of operation. The

End of Line

Resistor

(EOLR) required is 3.9k ohms with a maximum of 25 ohms line resistance.

Programming jumper (S1) is provided on each board for setting the vertical position/address of the card (S1-1 through S1-4). The I/O circuit module uses the lower terminal block and connects via cables to the bus driver module. The conventional input module and its display require one bay of the F620 system.

Note: When the CIM-4 and CIM-8 circuits are programmed as AND zone types use only Gamewell model 70133,70134 and 70135 detectors.

The style D adapter card (CIM-SDA) provides 4 or 8 Style D (Class A) circuits to the I/O circuit module. When the Style D adapter is used the EOLR's are not required. The style D adapter uses the upper terminal block, and is cabled to the I/O circuit module.

The display module provides eight (8) red circuit alarm LED's, eight (8) yellow circuit trouble LED's. Eight (8) circuit tactile switches are provided for

programming

,

Bypass

and

WalkTest

functions. The display module connects (via the display bus) to the bus driver module. The physical location of the display is set by the addressing jumper S1. Ensure addressing jumper is set according to its physical location in the cabinet and matches associated I/O module address jumper setting. Refer to Figure I-1, Cabinet Module Locations.

38

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Installation - Revision 5, 11/22/01

___________________________________________________________________________________________

Conventional Input Module Terminal Description

Bottom card (30868)

CIM-8

Terminal # Designation

1 1L1

Description

Initiating CCT # 1 (-)

2

3

4

5

1L2

2L1

2L2

3L1

Initiating CCT #1 (+)

Initiating CCT # 2 (-)

Initiating CCT #2 (+)

Initiating CCT # 3 (-)

6

7

8

9

10

11

12

13

14

15

16

3L2

4L1

4L2

5L1

5L2

6L1

6L2

7L1

7L2

8L1

8L2

Initiating CCT #3 (+)

Initiating CCT # 4 (-)

Initiating CCT #4 (+)

Initiating CCT # 5 (-)

Initiating CCT #5 (+)

Initiating CCT # 6 (-)

Initiating CCT #6 (+)

Initiating CCT # 7 (-)

Initiating CCT #7 (+)

Initiating CCT # 8 (-)

Initiating CCT #8 (+)

Class "A" Adapter -Conventional Input Module - Terminal Description

Top Card (30869)

(CIM-SDA)

Terminal # Designation Description

6

7

8

9

10

11

12

1

2

3

4

5

13

14

15

16

3L2

4L1

4L2

5L1

5L2

6L1

6L2

1L1

1L2

2L1

2L2

3L1

7L1

7L2

8L1

8L2

Initiating CCT #1 (-) Class "A" Return

Initiating CCT #1 (+) Class "A" Return

Initiating CCT #2 (-) Class "A" Return

Initiating CCT #2 (+) Class "A" Return

Initiating CCT #3 (-) Class "A" Return

Initiating CCT #3 (+) Class "A" Return

Initiating CCT #4 (-) Class "A" Return

Initiating CCT #4 (+) Class "A" Return

Initiating CCT #5 (-) Class "A" Return

Initiating CCT #5 (+) Class "A" Return

Initiating CCT #6 (-) Class "A" Return

Initiating CCT #6 (+) Class "A" Return

Initiating CCT #7 (-) Class "A" Return

Initiating CCT #7 (+) Class "A" Return

Initiating CCT #8 (-) Class "A" Return

Initiating CCT #8 (+) Class "A" Return

Technical Manuals Online! - http://www.tech-man.com

39

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

Universal

Signal Circuit

Module

The indicating signal circuit modules (USM-4, USM-8) consists of up to three (3) assemblies. The

I/O Signal Module

,

Style "Z" Adapter

, and the

Alarm Display Card

.

To view a comprehensive listing of compatible devices with the Flex 620 control panel, refer to Figure I-4, Compatible Indicating Appliances found at the end of this section. Also reference to Figure I-5, Wiring Guidelines Signaling Circuit Wire Sizes.

Signal Circuit

Module

Style "Z"

Adapter

Display

Module

The signal circuit module provides four (4) or eight (8), 2 amp DC, current limited analog signaling circuits. All circuits operate on the Style Y (Class B) mode of operation. The end of line resistor (EOLR) is 3.9K ohm. Programming jumper (S1) is provided on each board for setting the vertical position/address of the card (J1 through J4). The I/O signal module uses the lower terminal block and connects via cable to the bus driver module. Each universal signal module communicates via the

Module bus and requires one bay position each.

The SIGNAL I/O board has an option that allows programming of the signal circuits to be operable under Default Alarm Mode. A DIP switch (S2) is provided on the module to select which signaling circuits operate under default alarm mode. To set the circuits that are active, close their respective switch on S2. I.E.: Switch 1 for circuit 1, Switch 2 for circuit 2, through Switch 8 for circuit 8.

The Style D adapter (USM-SZA) card provides four (4) or eight (8) Style Z (Class A) circuits to the I/O signal card. When the Style Z adapter is used the EOLR's are not required. The Style Z adapter uses the upper terminal block, and is cabled to the I/O signal module.

The alarm display module provides eight (8) red zone alarmed LED's, eight (8) yellow zone trouble LED's. Eight (8) zone tactile switches are provided for

programming

,

Bypass

and

WalkTest

functions. Card slots are furnished for zone description, comments. The display module connects (via the display bus) to the bus driver module. The physical location of the display is set by the addressing jumper S1.

Ensure addressing jumper is set according to its physical location in the cabinet and matches associated I/O module address jumper setting. Refer to Figure I-1, Cabinet

Module Locations.

40

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Installation - Revision 5, 11/22/01

___________________________________________________________________________________________

Universal Signal Circuit Module Terminal Description

Bottom card (30878)

USM-8

Terminal # Designation Description

8

9

10

11

12

13

14

5

6

7

1

2

3

4

15

16

4AL2

5AL1

5AL2

6AL1

6AL2

7AL1

7AL2

1AL1

1AL2

2AL1

2AL2

3AL1

3AL2

4AL1

8AL1

8AL2

Indicating CCT #1 (+) output

Indicating CCT #1 (-) output

Indicating CCT #2 (+) output

Indicating CCT #2 (-) output

Indicating CCT #3 (+) output

Indicating CCT #3 (-) output

Indicating CCT #4 (+) output

Indicating CCT #4 (-) output

Indicating CCT #5 (+) output

Indicating CCT #5 (-) output

Indicating CCT #6 (+) output

Indicating CCT #6 (-) output

Indicating CCT #7 (+) output

Indicating CCT #7 (-) output

Indicating CCT #8 (+) output

Indicating CCT #8 (-) output

Class "A" Adapter - Universal Signal Module - Terminal Description

Top Card (30940)

(USM-SZA)

Terminal # Designation Description

1

2

3

4

1AL1

1AL2

2AL1

2AL2

Indicating CCT #1 (+) output Class "A" return

Indicating CCT #1 (-) output Class "A" return

Indicating CCT #2 (+) output Class "A" return

Indicating CCT #2 (-) output Class "A" return

9

10

11

5

6

7

8

12

13

14

15

16

3AL1

3AL2

4AL1

4AL2

5AL1

5AL2

6AL1

6AL2

7AL1

7AL2

8AL1

8AL2

Indicating CCT #3 (+) output Class "A" return

Indicating CCT #3 (-) output Class "A" return

Indicating CCT #4 (+) output Class "A" return

Indicating CCT #4 (-) output Class "A" return

Indicating CCT #5 (+) output Class "A" return

Indicating CCT #5 (-) output Class "A" return

Indicating CCT #6 (+) output Class "A" return

Indicating CCT #6 (-) output Class "A" return

Indicating CCT #7 (+) output Class "A" return

Indicating CCT #7 (-) output Class "A" return

Indicating CCT #8 (+) output Class "A" return

Indicating CCT #8 (-) output Class "A" return

Technical Manuals Online! - http://www.tech-man.com

41

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

Relay Module

Relay Circuit

Module

The relay module (RM-4, RM-8) consists of three (3) assemblies. The

I/O Relay

Module

, the

Relay Expander

, and the

Control Display

.

The relay module consists of four (4) form "C" 10 amp fused relay contacts. The module also provides four (4) feedback input points (switched negative) using 3.9K ohm resistors in parallel with an open feedback contact. If the feedback points are

Relay

Expander

Module

connected the LED's on the control display will follow the status of the feedback input point. A (-) connected directly to the feedback point will actuate the Red LED and a

(-) through the 3.9k resistor will actuate the Green LED. Otherwise the LED's on the display will follow the status of the relay. Programming jumper (S1) is provided on each board for setting the vertical position/address of the card (S1-1 through S1-4).

The relay module uses the lower terminal block and cables to the bus driver module.

Each position on the Module bus can accommodate an expanded relay module.

The relay expander provides the addition of four (4) supplementary form "C" 10 amp fused relay contacts. The module also provides four (4) feedback input points

(switched negative) using 3.9K ohm resistors in parallel with an open feedback contact. If the feedback points are connected (when the system is initialized) the

LED's on the control display will follow the status of the feedback input point.

Otherwise the LED's on the display will follow the status of the relay. The relay

Relay Display

Module

expander module uses the upper terminal block and cables to the I/O relay module.

The control display module provides eight (8) red relay activated LED's, eight (8) green relay normal LED's. Eight (8) circuit tactile switches are provided for

programming

and

Bypass

functions. Card slots are furnished for relay descriptions and comments. The display module connects (via the display bus) to the bus driver module. The physical location of the display is set by the addressing jumper S1.

Ensure addressing jumper is set according to its physical location in the cabinet and matches associated I/O module address jumper setting. Refer to Figure I-1, Cabinet

Module Locations.

___________________________________________________________________________________________

42

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Installation - Revision 5, 11/22/01

___________________________________________________________________________________________

Relay Module

RM-4

(30873)

Terminal

Number

Designator Description

9

10

11

5

6

7

8

1

2

3

4

12

13

14

15

16

1 NO

1 NC

1 C

1 M

2 NO

2 NC

2 C

2 M

3 NO

3 NC

3 C

3 M

4 NO

4 NC

4 C

4 M

Relay Expansion Module

RM-4E

(30874)

Terminal

#

1

Designator

5 NO

Form C normally open contact

Form C normally closed contact

Form C common contact 10A @ 30VDC or 220VAC resistive, fused @ 10A.

CCT #1 Relay feedback point to monitor status of controlled device

Form C normally open contact

Form C normally closed contact

Form C common contact 10A @ 30VDC or 220VAC resistive, fused @ 10A.

CCT #2 Relay feedback point to monitor status of controlled device

Form C normally open contact

Form C normally closed contact

Form C common contact 10A @ 30VDC or 220VAC resistive, fused @ 10A.

CCT #3 Relay feedback point to monitor status of controlled device

Form C normally open contact

Form C normally closed contact

Form C common contact 10A @ 30VDC or 220VAC resistive, fused @ 10A.

CCT #4 Relay feedback point to monitor status of controlled device

Description

9

10

11

12

13

14

15

6

7

8

2

3

4

5

16

7 NO

7 NC

7 C

7 M

8 NO

8 NC

8 C

5 NC

5 C

5 M

6 NO

6 NC

6 C

6 M

8 M

Form C normally open contact

Form C normally closed contact

Form C common contact 10A @ 30VDC or 220VAC resistive, fused @ 10A .

CCT #5 Relay feedback point to monitor status of controlled device

Form C normally open contact

Form C normally closed contact

Form C common contact 10A @ 30VDC or 220VAC resistive, fused @ 10A.

CCT #6 Relay feedback point to monitor status of controlled device

Form C normally open contact

Form C normally closed contact

Form C common contact 10A @ 30VDC or 220VAC resistive, fused @ 10A.

CCT #7 Relay feedback point to monitor status of controlled device

Form C normally open contact

Form C normally closed contact

Form C common contact 10A @ 30VDC or 220VAC resistive, fused @ 10A.

CCT #8 Relay feedback point to monitor status of controlled device

Technical Manuals Online! - http://www.tech-man.com

43

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

Building

Control Module

The building control module (BC) consists of three (3) assemblies. The

I/O Building

Control Module

, the

Building Control Expander,

and the

Building Control

Display/Switch Module.

Building

Control

Circuit

Module

The building control module consists of eight (8) form A/B (jumper programmable)

10 amp relays set up in four (4) "ON" relays and four (4) "OFF" relays, with a 10 amp fused common. Each relay (ON and OFF) is programmable for N/O or N/C contacts by removing the A or B jumper. Remove the A jumper for N/C contacts or the B jumper for N/O contacts. The module also provides four (4) feedback input points

(switched negative) using 3.9K ohm resistors in parallel with an open feedback contact. A (-) connected directly to the feedback point will actuate the Red LED and a

(-) through the 3.9k resistor will actuate the Green LED. Should the feedback points be connected the LED's on the building control display will follow the status of the feedback input point. Otherwise the LED's on the display will follow the status of the active relay. Programming jumper (S1) is provided on each board for setting the vertical position/address of the card (S1-1 through S1-4). The building control module uses the lower terminal block and cables to the bus driver module. The

Building

Control

Expander

Building

Control

Display/Switch

Module

building control module uses one slot in the Module bus.

The building control expander module provides an additional eight (8) form A/B

(jumper programmable) 10 amp relays set up in four (4) "ON" relays and four (4)

"OFF" relays, with a 10 amp fused common. The module functions identically as the building control module - providing four (4) feedback input points (switched negative) using 3.9k ohm resistors in parallel with an open feedback contact. The expander module mounts to the building control module (via standoffs) and uses the upper terminal block and cables to the I/O building control module.

The control display module provides eight (8) red "OFF" relay activated LED's, eight

(8) green "ON" relay activated LED's. Eight (8) three (3) position (AUTO,ON,OFF) rotary switches are provided for manual control of the I/O building control module and building control expander. Eight (8) circuit tactile switches are provided for

programming

and

Bypass

functions. Card slots are provided for building control description, comments. The building control display module mounts to the display door and is cabled to the bus driver module. The physical location of the display is set by the addressing jumper S1. Ensure addressing jumper is set according to its physical location in the cabinet and matches associated I/O module address jumper setting. Refer to Figure I-1, Cabinet Module Locations.

___________________________________________________________________________________________

A

ON

B

ON relay

COM

A

B

OFF

OFF relay

Figure 3.2 Typical building control circuit relay configuration

44

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Installation - Revision 5, 11/22/01

___________________________________________________________________________________________

Building Control Module

BC-4 (30871) Terminal # Designation Description

9

10

11

12

13

14

15

16

5

6

7

8

1

2

3

4

1 ON

1 COM

1 OFF

1 MON

2 ON

2 COM

2 OFF

2 MON

3 ON

3 COM

3 OFF

3 MON

4 ON

4 COM

4 OFF

4 MON

CCT 1 relay N/O contact - remove the W2 B Jumper

Common for CCT1 relays (terminals 1 & 3)

CCT 1 relay N/C contact - remove the W3 A Jumper

Monitor point for CCT1 (requires 3.9K resistor to (-) when used)

CCT 2 relay N/O contact - remove the W6 B Jumper

Common for CCT2 relays (terminals 5 & 7)

CCT 2 relay N/C contact - remove the W7 A Jumper

Monitor point for CCT2 (requires 3.9K resistor to (-) when used)

CCT 3 relay N/O contact - remove the W10 B Jumper

Common for CCT 3 relays (terminals 9 & 11)

CCT 3 relay N/C contact - remove the W11 A Jumper

Monitor point for CCT 3 (requires 3.9K resistor to (-) when used)

CCT 4 relay N/O contact - remove the W14 B Jumper

Common for CCT 4 relays (terminals 13 & 15)

CCT 4 relay N/C contact - remove the W15 A Jumper

Monitor point for CCT 4 (use 3.9K to (-) when req.)

BC-4E (30872) Terminal #

1

2

3

4

13

14

15

16

5

6

7

8

9

10

11

12

Designation

5 ON

5 COM

5 OFF

5 MON

6 ON

6 COM

6 OFF

6 MON

7 ON

7 COM

7 OFF

7 MON

8 ON

8 COM

8 OFF

8 MON

Description

CCT 5 relay N/O contact - remove the W2 B Jumper

Common for CCT 5 relays (terminals 1 & 3)

CCT 5 relay N/C contact - remove the W3 A Jumper

Monitor point for CCT 5 (requires 3.9K resistor to (-) when used)

CCT 6 relay N/O contact - remove the W6 B Jumper

Common for CCT6 relays (terminals 5 & 7)

CCT 6 relay N/C contact - remove the W7 A Jumper

Monitor point for CCT6 (requires 3.9K resistor to (-) when used)

CCT 7 relay N/O contact - remove the W10 B Jumper

Common for CCT 7 relays (terminals 9 & 11)

CCT 7 relay N/C contact - remove the W11 A Jumper

Monitor point for CCT 7 (requires 3.9K resistor to (-) when used)

CCT 8 relay N/O contact - remove the W14 B Jumper

Common for CCT 8 relays (terminals 13 & 15)

CCT 8 relay N/C contact - remove the W15 A Jumper

Monitor point for CCT 8 (use 3.9K to (-) when req.)

Technical Manuals Online! - http://www.tech-man.com

45

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

City Tie

Extender

The city tie extender module (CTX) consists of two (2) assemblies. These include the

I/O City Tie Extender Module

and

Alarm Display Module

.

Module

City Tie

Extender

Circuit

Module

The I/O city tie extender module provides for four (4) additional reverse polarity city tie circuits. These circuits can be programmed for multiple buildings being controlled by one panel, multiple entrances, or different types of alarms including supervisory or building notification. Each circuit transmits trouble for the zones associated to its circuit. Programming jumper (S1) is provided on each board for setting the vertical position/address of the card (S1-1 through S1-4). The city tie extender module uses

Display

Module

the lower terminal block and cables to the bus driver module. This module uses one slot in the Module bus.

The display module provides eight (8) red circuit alarm LED's, eight (8) yellow circuit trouble LED's. Eight (8) circuit tactile switches are provided for

programming

and

Bypass

functions. A card slot is furnished for circuit description and comments. The display module mounts to the display door and is cabled to the bus driver module.

The physical location of the display is set by the addressing jumper S1. Ensure addressing jumper is set according to its physical location in the cabinet and matches associated I/O module address jumper setting. Refer to Figure I-1, Cabinet Module

Locations.

City Tie Expander Module

4 Circuits (30875)

CTX-4

Terminal # Designation Description

1

2

3

4

5

6

1M1

1M2

2M1

2M2

3M1

3M2

Circuit 1 (+) line connection

Circuit 1 (-) line connection

Circuit 2 (+) line connection

Circuit 2 (-) line connection

Circuit 3 (+) line connection

Circuit 3 (-) line connection

7

8

4M1

4M2

Circuit 4 (+) line connection

Circuit 4 (-) line connection

46

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Installation - Revision 5, 11/22/01

___________________________________________________________________________________________

Initial System Startup

CAUTION !

Connect primary AC power to the system before connecting the battery/standby power source.

1. Connect primary AC supply (120VAC 50/60 Hz 3 amps).

2. Activate main power. Press the "Power On" tactile switch.

3. The "Power ON" green LED starts to pulse (15 second duration).

4. "Battery Fault" LED flashes. Connect the battery positive and negative leads.

5. At the completion of the "Power On" process, each conventional zone circuit LED will come 'On' for a four second period confirming circuit is reset during the power up sequence.

6. System is at idle, the normal quiescent condition. The "Power On" is illuminated.

___________________________________________________________________________________________

SmartStart

1. Activate main power. The "Power ON" green LED starts to pulse

(15 second duration). During this time press the "Power On" tactile switch.

2. System will commence an initialization process (i.e. SmartStart

).

The "Enter" key will begin to flash. Press "Enter" again confirming the SmartStart

initialization.

Û

Note

: If the "Enter" key is not pressed, the system will not initialize.

3. At the completion of the initialization process, each conventional zone circuit LED will come 'On' for a four second period confirming circuit is reset during the power up sequence.

4. System is initialized. "Power ON" green LED illuminated.

Technical Manuals Online! - http://www.tech-man.com

47

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

FLEX 600 CONTROL PANEL

COMPATIBLE SMOKE DETECTORS & BASES

30780-01/30780-01

30780-02/30780-02

30780-03/30780-03

30780-04/30780-04

30780-05/30780-05

71036

71086

70891 / (HB-4)

70892 /(HB-13)

70893

69121/69124

PART NUMBER

30954

30955

30069

30844

30845

Z77B

Z77D

Z77R

Z77F

STANDARD BASE F7, D9, R7, RT7

STANDARD BASE W/ REMOTE

STANDARD BASE W/ REMOTE &

RELAY

F7, D9, R7, RT7

F7, D9, R7, RT7

STANDARD BASE W/FLASH F7, D9, R7, RT7

STANDBY, REMOTE

Z77FR STANDARD BASE W/FLASH F7, D9, R7 RT7

STANDBY, REMOTE & RELAY

SERIES 60 - 4“ DETECTOR BASE

SERIES 60 - 6“ DETECTOR BASE

STANDARD BASE (SMOKE)

71033, 71034, 71035

71033, 71034, 71035

70884,70885

70886/(HD-3)

STANDARD BASE W/RELAY (SMOKE)

STANDARD BASE (HEAT DETECTOR)

70884,70885

70886/(HD-3)

70887,70888,

70889,70890

STANDARD BASE W/LATCHING LED (HEAT

DETECTOR)

70887,70888,

70889,70890

25

25

25

25

25

25

25

25

25

MAX AL.

CURRENT

100 MA

MAX AL.

CURRENT

100 MA

1 SET LINEAR BEAM SMOKE DETECTOR

Figure 3-3, Compatible Smoke Detectors

FLEX 600 CONTROL PANEL

COMPATIBLE AUXILIARY DEVICES

DESCRIPTION

4 WIRE IONIZATION DUCT DETECTOR, APOLLO

4 WIRE, PHOTOELECTRIC DUCT DETECTOR< APOLLO

END OF LINE SUPERVISORY RELAY

4 WIRE, DUCT SMOKE DETECTOR

4 WIRE, DUCT SMOKE DETECTOR

Figure 3-4, Compatible Auxiliary Devices

71036

71086

FLEX 600 CONTROL PANEL

COMPATIBLE INITIATING DEVICES FOR “AND“ ZONES

SERIES 60 - 4“ DETECTOR BASE

SERIES 60 - 6“ DETECTOR BASE

71033, 71034, 71035

71033, 71034, 71035

25

25

48

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Installation - Revision 5, 11/22/01

___________________________________________________________________________________________

PART

NUMBER

FLEX 600

COMPATIBLE INDICATING APPLIANCES

MODEL NUMBER DESCRIPTION CURRENT

70874

70875

MB-G6-24-R

MB-G10-24-R

MOTORBELL 6"

MOTORBELL 10"

.030

.030

71584

71302

71582

71303

71548

71549

70871

70873

71287

71288

71557

71631

71558

71561

71586

71587

71581

71585

68460-01

71583

71300

71301

71289

71290

71138

71573

71614

71292

71574

71295

71575

71293

RSP-2430-VFR

SRP-2475-VFR

RSP-2475-VFR

SRP-24110-HFR

CSX10-24-DC-R

CSXG10-24DC-R

CH-BF1-R

CH-CF1-W

CH-DF1-R

CH-CF1-LS-24-VFR

CH-DF1-LS-24-VFR

CH-DF1-LSM-24-VFR

CH-CF1-MS-24-CFW

CH-DF1-MS-24-VFR

CH-CF1-IS-24-CFW

CH-DF1-IS-24-VFR

SM-12/24-R

DSM-12/24-R

MIZ-24-R

MIZ-24-W

MIZ-24-LS-VFR

MIZ-24-LSM-VFR

MIZ-24-MS-VFR

MIZ-24-IS-VFR

MT-12/24-R

AMT-12/24-R

MT4-12/24-R

MT-24-LS-VFR

AMT-24-LS-VFR

MT-24-IS-VFR

AMT-24-IS-VFR

MT-24-LSM-VFR

30 Cd Strobe Adapter Red

75 Cd Strobe Adapter Red, Sync.

75 Cd Strobe Adapter Red

110 Cd Strobe Adapter Red

10” SS Exp indoor Red..

10” SS Exp outdoor Red..

Chime SS/Vib Red

Chime SS/Vib ceiling white

Chime Vibrating

Chime SS/Vib Red

Chime SS/Vib Red

Chime SS/Vib Red

Chime SS/Vib White

Chime SS/Vib Red

Chime SS/Vib White

Chime SS/Vib Red

Single Circuit Sync Module

Dual or Class A Sync Module

Mini Horn Red

Mini Horn White

Mini Horn/Strobe 15 Cd

Mini Horn/Strobe 15/75 Cd

Mini Horn/Strobe 30 Cd

Mini Horn/Strobe 75 Cd

Multi-tone Horn Red

Multi-tone Horn Red 3 Input

Multi-tone Horn Red Surface

Multi-tone Horn/Strobe Red 15 Cd

Multi-tone Horn/Strobe Red 15 Cd 3 input

Multi-tone Horn/Strobe Red 75 Cd

Multi-tone Horn/Strobe Red 75 Cd 3 input

Multi-tone Horn/Strobe Red 15/75 Cd

.155

.155

.245

.245

.025

.038

.017

.017

.092

.127

.124

.215

.200

.250

.500

.500

.020

.020

.020

.100

.100

.135

.147

.237

See DS851

See DS851

See DS851

See DS851

See DS851

See DS851

See DS851

See DS851

71576

71294

AMT-24-LSM-VFR

MT-24-MS-VFR

Multi-tone Horn/Strobe Red 15/75 Cd 3 input

Multi-tone Horn/Strobe Red 30 Cd

See DS851

See DS851

Technical Manuals Online! - http://www.tech-man.com

49

71557

71556

71558

71559

71616

71560

71561

71562

71543

71544

71545

71546

71547

71426

71427

71550

71553

71552

71551

71569

71554

71555

Flex 620 System Operation - Revision 5, 11/22/01

_______________________________________________________________________________________________

PART

NUMBER

FLEX 600

COMPATIBLE INDICATING APPLIANCES (Cont.)

MODEL NUMBER DESCRIPTION CURRENT

71140 MT-24-WM-VFR Multi-tone Horn/Strobe Red 110 Cd See DS851

MT-24-SL-VFR

MT-24-SLM-VFR

RS-2415-VFR

RS-241575-VFR

SRP-2415-VFR

SR-2415-VFR

RSP-241575-VFR

SRP-241575-VFR

SR-241575-VFR

RSP-2430-VFR

RS-2430-VFR

RSP-2475-VFR

RS-2475-VFR

SR-2475-VFR

RS-24110-HFR

SRP-24110-HFR

SR-24110-HFR

AS-2415-VFR

AS-241575-VFR

AS-2430-VFR

AS-2475-VFR

AS-24110-HFR

Multi-tone Horn/Strobe Red 15 Cd Sync

Multi-tone Horn/Strobe Red 15/75 Cd Sync

Strobe 15 Cd

Strobe 15/75 Cd

Strobe 15 Cd Plate mount Sync

Strobe 15 Cd Sync

Strobe 15/75 Cd Plate Mount

Strobe 15/75 Cd Plate Mount Sync

Strobe 15/75 Cd Sync

Strobe 30 Cd Plate mount

Strobe 30 Cd

Strobe 75 Cd Plate mount

Strobe 75 Cd

Strobe 75 Cd Sync

Strobe 110 Cd

Strobe 110 Cd Plate mount Sync

Strobe 110 Cd Sync

Horn/Strobe 15 Cd

Horn/Strobe 15/75 Cd

Horn/Strobe 30 Cd

Horn/Strobe 75 Cd

Horn/Strobe 110 Cd

Table I-2

.200

.200

.200

.200

.124

.124

.200

.200

.093

.121

.126

.239

.269

.096

.096

.100

.138

.138

See DS851

See DS851

.074

.100

50

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Installation - Revision 5, 11/22/01

___________________________________________________________________________________________

WIRING GUIDELINES

SIGNALLING CIRCUIT WIRE SIZES 24 VOLT DC PARALLEL

WIRE RESISTANCE

18 6.5

16 4.1

14 2.6

12 1.6

10 1.0

PAIR IN DISTANCE TO LAST DEVICE

(MAXIMUM LINE LOSS 10%)

1.0amp

400'

620'

1000'

1600'

2500'

200'

300'

500'

800'

1250'

1.5amp 2.0am

p

130' 100'

210' 160'

330' 250'

520' 400'

840' 620'

CIRCUIT CHARACTERISTICS

INITIATION

SIGNAL

3.9 K ohm 1/2 watt

RESISTANCE

50 ohm

3.9 K ohm

1/2 watt

4.8 ohm

@0.5a

@2.0a

Figure I-5, Wiring Guidelines

Signaling Circuit Wire Sizes

strait lay - 18 ga strait lay - 14 ga

Technical Manuals Online! - http://www.tech-man.com

51

Technical Manuals Online! - http://www.tech-man.com

Technical Manuals Online! - http://www.tech-man.com

Section

4

FlexAlarm 620

Programming

Programming Overview - FlexAlarm 620

Û

NOTE

: During all levels of programming, the system trouble relay will generate a trouble condition, indicating an 'off normal' condition.

Notify all key personnel, monitoring companies and municipalities before proceeding.

____________________________________________________________________________________________

Programming

Overview

Functional

Key Switch

Labels

Selecting

Options

Point Selection

Programming the system configuration is accomplished through the Common Control

Display (CCD) tactile switches. How the program is configured defines how the system operates and is application specific. Every programming operation has been designed to follow the same basic pattern of steps. Once one programming operation is completed, the user can apply that knowledge to all of the other programmable features.

The common control legend strips (identifying each of the display's key function designators with associated LED's) have additional programming text printed on the reverse side. The programming text identifies the function of the tactile key switches while in the programming mode. Subsequent to entering the programming mode, remove each of the 4 legend strips (pulled out from the top of the column) "reverse" each legend strip so that the back side is visible. Reinsert each strip back into its original "pocket" on the CCD. The CCD's keys are now labeled for programming mode.

1. Each labeled key function switch on the CCD has an 'Upper' and a 'Lower' LED associated with it. To choose a particular option, press the tactile key switch which is associated with the LED.

A. When the key is pressed the 1st time, the 'Upper' LED turns "On".

B. When the key is pressed the 2nd time, the 'Upper' LED turns "Off", and the 'Lower' LED turns "on".

2. Each time the key switch is pressed the LED will toggle back and forth.

3. If a completely different key is pressed , the LED which is currently "On" will turn

"Off", and the 'Upper' LED on the new key will turn "On".

4. When the desired programming option has been selected, press the "

ENTER

" key to select the choice.

Depending on the option selected, various other LED's on the input point cards, output signal cards, output relay cards and/or building control cards will turn on to indicate the inputs and outputs that are active.

A. To add new points, press the key associated with the point until its

B. corresponding LED turns "On".

To remove a point, press the key associated with the point until its

C. corresponding LED turns "Off".

When all changes to a particular option are completed, press the

D.

"

ENTER

" key to save your changes.

To program a different option, repeat the process from above steps # 1 through 4. If all programming changes are completed, press the

"ENTER" key twice to exit PROGRAM mode and return to IDLE mode.

Û

NOTE

: Reverse the display legend strips back to the "Standard Operating" labeling side after exiting the programming mode.

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Programming - Revision 5, 11/22/01

______________________________________________________________________________________________

Programming Options

The following options can be programmed from the F620 control panel keypad.

Input Circuit

Types

A. Fire Alarm Control Panel (FACP) Initiating Points

1. AUTOMATIC

The Automatic Fire Alarm Initiating Circuit is the (*System Default*). It operates as a standard fire alarm circuit, receiving alarm signals from contact closures and two wire detectors. Devices configured as automatic will activate 1st level alarm functions.

2. VERIFIED

The Verified Automatic Fire Alarm Initiating Circuit works like an

Automatic Alarm Initiating Circuit when the panel receives an alarm signal from a contact closure devices. When a (two-wire) detector initiates an alarm the panel will recognize the alarm, reset the circuit and the detector, and not take any further action while it waits for a second alarm. If, within a specified period of time, a second detector alarms or a contact device closes on the same circuit, the Alarm will be activated. If no second alarm occurs within the specified time limit the first alarm is ignored.

3. AND

The AND Fire Initiating Circuit will operate as an Automatic Alarm

Initiating Circuit for the first (two-wire) smoke detector alarm reported to the panel. Should another two wire smoke detector go into alarm on the same

AND circuit, a second alarm output will occur. This circuit is useful for a simple cross zone of two or more detectors. An example of a typical application would be in an elevator lobby where elevator capture doesn't occur until both detectors have alarmed. However, other normal alarm responses occur when the first detector activates. A short on the circuit will initiate a second stage alarm immediately.

4. SUPERVISORY

The Supervisory Alarm Circuit provides a sprinkler supervision type circuit.

When acknowledged the circuit will lock in and will need to be reset. When the Supervisory Circuit is not acknowledged, and the device causing the

Supervisory alarm clears itself or is cleared without being acknowledged, it will automatically return to normal.

B. Remote FACP switches

1. ACKNOWLEDGE

Remote Acknowledge switch causes the panel to 'acknowledge' when activated from a remote location.

2. RESET

When in alarm, the Reset switch will 'reset' the system from a remote location.

Technical Manuals Online! - http://www.tech-man.com

55

Input Circuit

Type

(continued)

3. SIGNAL SILENCE

When in alarm the Signal Silence Circuit will Signal Silence the System from a remote location. Each new alarm on the Signal Silence Circuit will switch the system between de-active and active.

4. DRILL

When activated the Drill Circuit will Drill the system from a remote location.

____________________________________________________________________________________________

Output Signal

Circuit Type

A. STEADY DC

Steady DC type signal circuit is the System Default. When Activated, any signal circuits programmed for Steady DC will provide a 24VDC uninterrupted output.

B. MARCHTIME 60

Marchtime 60 circuits, when activated, will provide a 24 VDC output on the selected circuits at a 60 pulses per minute rate with a duration of 50% on and

50% off cycle.

C. MARCHTIME 120

Marchtime 120 circuits, when activated, will provide a 24 VDC output on the selected circuits at a 120 pulses per minute rate with a duration of 50% on and 50% off cycle.

D. TEMPORAL

Temporal signaling circuits, when activated, will provide a 24 VDC output in the pattern of a Morse Code "U", this pattern is active for .25 seconds, off for .25 seconds, active for .25 seconds, off for .25 seconds, active for .75 seconds, off for .75 seconds. The pattern repeats until the circuit is returned to Idle.

E. CALIFORNIA UNIFORM FIRE CODE

California Uniform Fire Code Signal circuits, when activated, will provide a

24 VDC output in Marchtime 120 format for 10 seconds on and 5 seconds off. The pattern repeats until the circuit is returned to Idle.

F. CODED

Zone coded signaling circuits when activated will produce a 24VDC pulsed numeric code to be transmitted up to 6 times or as programmed. A separate code is usually transmitted for each input zone.

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Programming - Revision 5, 11/22/01

______________________________________________________________________________________________

Signal Circuit

Restore

A. Restore On - ACKNOWLEDGE

Any active output point programmed to restore on ACKNOWLEDGE will return to Idle whenever the Acknowledge switch is pressed. All output points that were returned to Idle will reactivate upon a subsequent alarm.

B Restore On - SIGNAL SILENCE (** System Default **)

Any active output point programmed to restore on Signal Silence will be silenced by the activation of the Signal Silence Switch and will return to Idle.

The Signal Silence Switch operates as a toggle switch. All outputs that were returned to idle will reactivate upon a subsequent alarm or by depressing the

Signal Silence Switch again. Both Signal Circuits and Relay Outputs can be programmed to restore on Signal Silence.

C. Restore On - RESET

Serves as System Default. Any active output point not programmed or deprogrammed from Restore on Acknowledge, or Restore on Signal Silence will cause the output point to restore on RESET.

Û

NOTE

: There are a few restrictions to be aware of regarding output signal circuits:

1. The two signal circuits on the Bus Driver Module (BDM) can be used for steady or pulsing DC (marchtime, temporal, etc.) and programmed separately.

2. Signal Circuit types being selected on a USM Module are always allocated in circuit pairs (an upper & lower pair). Each signal circuit has its own individual relay to control when it is activated or deactivated, but each pair of signal circuits shares a single driver transistor which is used to generate the selected type of signal output for both signal circuits.

Alarm Levels

There are three levels of alarm that can be assigned to each type of output circuit, PreAlarm, 1st Alarm or 2nd Alarm. These levels designate at which level of alarm an output circuit will activate. Output circuits assigned to 1st alarm level (system default) will activate when a first alarm is detected on its assigned input circuit(s), provided the input circuit is assigned to activate that output circuit in the CBE table. Circuits designated as PreAlarm will activate when a PreAlarm level is detected on an input circuit. Circuits requiring activation on 2nd alarm (AND zones) can be assigned to alarm level 2. An AND zone assigned to activate both 1st and 2nd alarm level output circuits will activate only those outputs assigned to level 1 during a first alarm condition. When a second alarm is detected both first and second alarm outputs will activate. A shorting device will activate both first and second alarm outputs.

Technical Manuals Online! - http://www.tech-man.com

57

Special Signal

Circuit

Functions

A. SIGNAL SILENCE INHIBIT

Silence Inhibit will prevent the operation of the Signal Silence function for a period of one (1) minute from the time the first point goes into alarm. If the panel is programmed for Silence Inhibit any activation of the Signal Silence

Switch will be ignored, allowing the output signal circuits to be active, until the one (1) minute delay has elapsed. The one (1) minute timer can be adjusted via the laptop programming.

B. AUTO SILENCE - Automatic Signal Cutoff

If an output signaling circuit is programmed for Auto Silence it will automatically silence the signal circuits ten (10) minutes from the time the first point goes into alarm. If, subsequent to its silencing, a new alarm occurs, the output signaling circuit will resound and the auto silence time-out feature will reset its timer to silence its associated outputs at ten (10) minutes past the last alarm.

C. Drillable

Any signal circuit programmed as drillable will activate when the drill feature is activated.

Restoring

Outputs

A. Restore On - ACKNOWLEDGE

Any active output point programmed to restore on ACKNOWLEDGE will return to Idle whenever the Acknowledge switch is Depressed. All output points that were returned to Idle will reactivate upon a subsequent alarm.

B. Restore On - RESET (** System Default **)

Serves as System Default. Any active output point not programmed or deprogrammed from Restore on Acknowledge, or Restore on Signal Silence will cause the output point to restore on RESET.

C. SEQUENTIAL RESTORE - Upon System Reset

The sequential restore only applies to relay outputs. Any active

Output

Control Relay

or

Building Control Relay

programmed for Sequential Restore will only restore on Reset, not on Acknowledge. Selected relays will return to Idle 4 seconds apart, starting with the highest output point and ending at the lowest point set. The restore sequence is determined by the actual wired location of the relay on the board and is not programmable.

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Programming - Revision 5, 11/22/01

______________________________________________________________________________________________

Control By Event

Control-by-Event programming allows the user to create a matrix whereby selected groups of input circuits are logically arranged to select output circuit groups. The SmartStart

feature automatically assigns all input circuit groups to select all output circuit groups.

Input Zone

(CBE)

A. Input circuit assigned to a " Group"

Control-By-Event programming allows the user to create a matrix whereby selected conventional input circuits (i.e. zones) can be logically arranged to select any combination of output groups (i.e. Signal, Relay and Building Control Circuits).

B. Signal Circuit Activation

Any combination of signal circuit(s) may be assigned to activate from an input group.

When an alarm is received from an input group, the output signal circuit(s) are activated (provided the circuits are assigned to the corresponding alarm level). System

Default activates ALL output signal circuits during a level 1 alarm.

C. Relay Circuits Activation

Any combination of relay circuit(s) may be assigned to activate from an input group.

When any member of the input group goes into alarm condition, the output relay circuit is activated (provided the circuits are assigned to the corresponding alarm level). System Default activates ALL output relays during a level 1 alarm.

D Building Control Circuits "OFF" or "ON" relays

Any output building control circuit can be assigned to a logical input point group.

When any member of the logical input group goes into alarm condition, the system may be programmed to select either the ON or OFF relay. System Default activates

ALL ”OFF” relays during a level 1 alarm.

E. City Tie Expander Circuits Activated

City Tie expander circuits can be programmed to reverse polarity for alarm and transmit trouble when any member of the assigned logical input point group goes into an alarm or fault condition. (*System Default disables all Expander Circuits*)

____________________________________________________________________________________________

Technical Manuals Online! - http://www.tech-man.com

59

Access Levels

Access Levels

:

The system has four levels of access. The levels are defined as follows:

Primary -

LEVEL 1:

User has access only to the [ACK] acknowledge function. The default password for level 1 is 1111.

Operating -

LEVEL 2:

User has access to all Level 1 functions plus the [Reset], [Signal Silence] and [Drill] functions. The default password for level 2 is 2222.

Maintenance -

LEVEL 3:

User has access to all Level 1 and Level 2 functions plus the [Bypass] and [WalkTest] functions. The default password for level 3 is 3333.

Service

- LEVEL 4:

Access to programming. Programming can only be completed using the level 4 password entry. Default password for level 4 is 4444. When this mode is entered the key switches are redefined. Reversing the front display strips will reveal the programming display functions. After a period of approximately 10 minutes of no Key action is detected, the system will automatically come out of programming mode and return to the last access level used.

____________________________________________________________________________________________

POWER ON

BATTERY FAULT

ACKNOWLEDGE

RESET

SIGNAL

SILENCE

Û

Note

: System configuration (i.e. SmartStart

) defaults to level 2 password access. When the password access level is changed, the system defaults to that level (except programming) including after power failure occurs.

PRE-ALARM

FIRE

COMMON ALARM

SUPERVISORY

SECURITY

COMMON TRBL.

TROUBLE

TRBL.

SILENCED

PASSWORD REQD.

ENTER

PASSWORD ACCEPT

ANNUN. FAULT

WALKTEST

BYPASS/

ENABLE

1

2

3

4

EARTH FAULT

DRILL

ALARM

CITY

TROUBLE

ALARM

TIE

5

6

SIG CKT

TROUBLE

ALARM

7

SIG CKT

TROUBLE

8

Figure 4.1 Common Control Display - Operating Mode

Password Entry

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Programming - Revision 5, 11/22/01

______________________________________________________________________________________________

Entering

Passwords

1. With the system in the IDLE mode, press the "ENTER" key on the CCD.

2. The 8 lower LEDs on the right display will flash to indicate that the digits 1-8 are active for entering the password.

3. Enter the password by depressing the associated numerical key. The upper LED will blink indicating that the key has been pressed. Press "

ENTER

" again to signify the end of the password

A.

Password Accepted

= The password accepted LED will flash twice when a new password is entered. This indicates that a new access level has been accepted.

B.

Password Required

= If a function is attempted from a level that does not allow access to that function (i.e. Bypass from level 2), the password required LED will flash indicating that a higher password level must be accessed to perform that function. This also occurs when a wrong password is entered.

AUTOMATIC

INITIATION

VERIFICATION

AND

INITIATION

SUPERVISORY

60 BPM

SIGNALS

120 BPM

CALIFORNIA

SIGNALS

TEMPORAL

CONTROL BY EVENT

ALARM LEVELS

ACKNOWLEDGE

RESTORE

SIGNAL SILENCE

AUTO SIL.

(10)

SIL. INHIBIT (1)

SEQ.

RESTORE

BC ALARM RELAY ACKNOWLEDGE

INITIATION

RESET

STEADY

SIGNALS

CODED DRILLABLE

SIG CKT 1

SIGNAL SILENCE

INITIATION

DRILL

ENTER SIG CKT 2

Figure 4.2 Common Control Display - Programming Mode

Technical Manuals Online! - http://www.tech-man.com

61

Entering

Programming

Mode

Selecting

Programming

Options

Circuit

Selection

Press the ENTER key. Using the right hand CCD display keys, select the programming password and press the ENTER key again. The Password Required and the Password Accepted LEDs should be illuminated steady. This indicates that the system is in the Programming Mode, ready to accept changes. Reverse the display strips.

1. Each label key function switch on the CCD has an 'Upper' and a 'Lower' LED associated with it. To choose a particular option press the tactile key which is associated with the LED.

A. When the key is pressed the 1st time, the 'Upper' LED turns "On" . Both the password required and password accepted LEDs will extinguish.

B. When the key is pressed the 2nd time, the 'Upper' LED turns "Off", and the

'Lower' LED turns "On".

2. Each time the key is pressed the LED will toggle back and forth.

3. If a completely different key is pressed , the LED which is currently "On" will turn "Off", and the 'Upper' LED on the new key will turn "On".

4. When the desired programming option has been selected, press the "

ENTER

" key. The Password Required and Password Accepted LEDs will flash twice indicating that your selection has been accepted.

Note

: If a key that is not available for selection during any phase of programming is pressed, the sonarlert will beep indicating that the selection is not valid.

Depending on the option selected, various other LEDs on the input point cards, output signal cards, output relay cards and/or building control cards will turn on to indicate the inputs and outputs that are active.

A. To add new points, press the key associated with the point until its corresponding

LED turns "On".

B. To remove a point, press the key associated with the point until its corresponding

LED turns "Off".

C. When all changes to a particular option are completed, press the "

ENTER

" key to save your changes.

D. To program a different option, repeat the process from above steps # 1 through 4.

If all programming changes are completed, press the "ENTER" key twice to exit

PROGRAM mode and return to IDLE mode.

Û

NOTE

: Reverse the display legend strips back to the "Standard

Operating" labeling side after exiting the programming mode.

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Programming - Revision 5, 11/22/01

______________________________________________________________________________________________

Input Circuit - Programming

Conventional

Input Circuit

Types

1. Enter the programming mode password. See Password Entry section. Each of the

'Input Circuit Types' are defined in the "Programming Options" section.

2. Verify the legend strips are positioned to the Programming Mode.

A. Select the desired circuit type by depressing the key associated with the circuit type legend strip until its LED is lit. The following choices are available for input circuit types:

Automatic

Verified

And

Supervisory

Acknowledge

Reset

Signal Silence

Drill

B. Once the desired circuit type LED is illuminated, press the "

ENTER

" key to select the indicated choice.

C. Select all of the input circuits that are to operate as the selected circuit

type by depressing their associated circuit switch. When all of the circuits

are selected (indicated by the circuit LED on) press the

ENTER

switch.

Note:

To deselect a circuit, press the associated circuit switch until the LED is extinguished. Any circuit deselected will default to an Automatic Zone and all control by event information will be removed.

3. If additional Input Circuit Type changes are required, repeat the procedure in step

#2.

Technical Manuals Online! - http://www.tech-man.com

63

Output Circuit - Programming

Signal Circuit

Type

1. Enter the programming mode password. See Password Entry section. Each of the 'Output Signal Circuit Types' are defined in the "Programming Options" section.

2. Verify the legend strips are positioned to the Programming Mode.

A. Select the desired output circuit type by depressing the key associated with the circuit type legend strip until its LED is lit. The following choices are available for output circuit types:

A. Steady DC (** System Default **)

B. Slow Marchtime (60 ppm)

C. Fast Marchtime (120 ppm)

D. Temporal Code

E. California Uniform Fire Code

B. Once the desired circuit type LED is illuminated, press the "

ENTER

" key to select the indicated choice.

C. Select all of the output circuits that are to operate as the selected circuit

type by depressing their associated circuit switch. When all of the circuits

are selected (indicated by the circuit LED on) press the

ENTER

switch.

Note:

To deselect a circuit, press the associated circuit switch until the LED is extinguished. Any circuit deselected will default to a steady signal and all control by event information will be removed.

3. If additional Output Circuit Types are required, repeat the procedure from step 2.

____________________________________________________________________________________________

BC Relay

Selection

The BC Relay option selects the appropriate relay (“ON” or “OFF”) of each Building

Control Module circuit to activate when an alarm condition is detected (provided the circuits are selected in Control By Event).

1. From the programming mode select the BC relay option and press the

“ENTER”

key.

2. Select all of the Relays to be activated on each Building Control Circuit by pressing the circuit key until the appropriate LED is illuminated. The GREEN

LED indicates the “ON” relay will energize and the RED led indicates the “OFF” relay will energize.

3. After all of the circuits are selected press the

“ENTER”

key.

4. If additional changes are required, repeat this procedure.

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Programming - Revision 5, 11/22/01

______________________________________________________________________________________________

Restoring Output Circuits

Signal Silence,

Acknowledge

Default restoral setting for signal circuits is signal silence and relay circuits is reset.

1. Enter the programming mode password. Verify the legend strips are positioned to the Programming Mode.

2. Select the desired output restoral option, Signal Silence or Acknowledge and press the

“ENTER”

key. Press the key once to illuminate the "Upper, Signal Silence"

LED, or twice to illuminate the "Lower, Acknowledge" LED.

3. Assign the selected Output Circuit Restore type to any combination of Signal

Circuits and/or Control Relays by depressing their associated circuit. The selected point's LED will turn "ON".

Note:

To change a signal circuit to the reset option, select the Signal Silence option,

(all Signal Circuits LED’s should be Lit in the default configuration) then deselect the desired circuit(s). This will cause the LED to extinguish. When the circuit

LED is not lit for both the Signal Silence and Acknowledge options the output circuit will restore upon system Reset.

4. When all of the desired output circuits have been selected, and any unwanted ones have been removed, press the "

ENTER

" key to save your changes.

5. If additional changes are required, repeat this procedure from step 2.

____________________________________________________________________________________________

Sequential

Restore

Sequential restoring applies to Relay and Building Control circuits only.

1. From the programming mode select the sequential restore option and press the

“ENTER”

key.

2. Select all of the Relay and Building Control circuits that should restore sequentially (from highest to lowest circuit number every four seconds).

3. After all of the circuits are selected (circuit LED’s “ON”) press the

“ENTER”

key.

4. If additional changes are required, repeat this procedure.

Technical Manuals Online! - http://www.tech-man.com

65

Programming Signal Circuit Special Functions

Silence Inhibit

The Signal Silence Inhibit feature will prevent

ALL

of the systems signal circuits from being silenced for a period of 1 minute (Default, programmable) after an initial alarm is received. This is a system wide feature and cannot be selected on a per circuit basis.

While in the programming mode select the Silence Inhibit key. It’s associated LED will illuminate. To deselect this option press the Silence Inhibit key again (LED off).

____________________________________________________________________________________________

Auto Silence

The Automatic Signal Silence feature will automatically silence any signal circuits selected for this option after a period of 10 minutes (default).

1. From the programming mode select the Auto Silence option and press the

“ENTER”

key.

2. Select all of the Signal Circuits that should automatically silence by pressing their associated circuit key.

3. After all of the circuits are selected (circuit LED’s “ON”) press the

“ENTER”

key.

4. If additional changes are required, repeat this procedure.

____________________________________________________________________________________________

Drillable

The Drillable feature determines if the Signal Circuits will activate when the drill feature is selected.

1. From the programming mode select the Drillable option and press the

“ENTER”

key.

2. Select all of the Signal Circuits that should activate when the Drill switch is pressed by pressing their associated circuit key.

3. After all of the circuits are selected (circuit LED’s “ON”) press the

“ENTER”

key.

4. If additional changes are required, repeat this procedure.

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Programming - Revision 5, 11/22/01

______________________________________________________________________________________________

Control-By-Event - Programming

Selecting CBE

Selecting Input

Circuits

1. Enter the programming mode password. See Password Entry section. Each of the

'Signal Circuit Special Function Types' are defined in the "Programming Options" section.

2. Select the Control-by-Event (CBE) by pressing the CBE key. When the associated

LED turns "ON", press the "ENTER" key.

3. Select the desired input circuit(s) by pressing the associated circuit key. Once the desired group has been selected (indicated by their associated LED’s on) press the

"ENTER" key to confirm the selection.

Û

Note

: If any previously programmed or any default point assignments are already in this group their respective LEDs will turn "ON" at this time. To deselect them press their associated circuit key.

Selecting

Output

Circuits

4. Select the desired Output Circuit(s) to activate when any of the selected inputs is alarmed. When all of the desired output circuits have been selected (indicated by the circuit LED on), press the “ENTER” key.

5. If additional circuit assignments are required, repeat the procedure from step #2.

Technical Manuals Online! - http://www.tech-man.com

67

Computer/Laptop Programming Overview

Overview of

This section describes the system communications via a computer. System monitoring,

General Control functions and system programming can only be accessed from a computer terminal with the F620. All figures shown are displayed on the computer screen.

Computer

Program ming

Interconnect

Communication

Protocol

The 14 pin ribbon cable P/N 71332, is used to connect the computer to the CPU Module port P2. If the SIM-232 card is installed use cable P/N 70703 to connect to the Com2 port of SIM-232 module. Refer to (drawing # D-W1142).

The system communicates with a computer at baud rates of 1200,2400,4800 and 9600 BPS

(see baud rate settings in CPU installation section). The standard protocol is Xon/Xoff, No

Parity, 8 Data Bits and 1 Stop Bit.

Û

Note

: Most standard communication packages for computers will allow you to set the proper protocol for the communications port of your computer.

Procomm Software

Configuration

When using PROCOMM to communicate with your FLEX 600 system the following configuration should be used. Several areas of the ProComm setup menu and the line settings menu must be accessed to configure the protocol required.

Line Settings

Setup Menu

The Line Settings option can be selected by pressing the ALT and P keys simultaneously.

From this menu select the option that your RS-232 port is set for (e.g., 2400,N,8,1 would be selected if your port speed is set to 2400 baud). The protocol is Baud Rate (port speed setting), No Parity (N), 8 Data bits (8) and 1 Stop Bit (1).

The ProComm SETUP MENU is accessed by pressing the ALT and S keys simultaneously.

The following screen should appear:

1) MODEM SETUP

2) TERMINAL SETUP

3) KERMIT SETUP

4) GENERAL SETUP

5) HOST MODE SETUP

6) ASCII TRANSFER SETUP

S) SAVE TO DISK

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Programming - Revision 5, 11/22/01

______________________________________________________________________________________________

Terminal

Setup

Select option 2 from the ProComm SETUP MENU to display the TERMINAL SETUP menu. The following options should be displayed. To change the settings select the desired number and use the up/down arrows to scroll through the selections. Press ESC to return to the SETUP MENU.

1) Terminal emulation... VT-100

2) Duplex .............. Full

3) Flow control......... XON/XOFF

4) CR translation (in).. CR

5) CR translation (out). CR

6) BS translation ...... NON-DEST

7) BS key definition.... BS

8) Line wrap ........... ON

9) Scroll .............. ON

10) Break Length (ms) .... 350

11) Inquiry (CTRL-E) ..... OFF

General

Setup

From the ProComm SETUP MENU select option 4 to display the GENERAL SETUP menu. The following settings should be displayed.

1) Editor name ..........

2) Default d/l path .....

3) Default log file ..... PROCOMM.LOG

4) Screen dump file ..... PROCOMM.IMG

5) Screen write method .. DIRECT

6) Translate table ...... OFF

7) Sound effects ........ ON

8) Alarm sound .......... ON

9) Alarm time (seconds)..... 5

10) Exploding windows .... YES

11) XMODEM mode .......... NORMAL

12) Xlat pause character .

13) Xlat CR character .... !

14) Xlat CTRL character .. ^

15) Xlat ESC character ...

|

16) Aborted downloads .... KEEP

17) Transmit pacing (ms) . 25

NOTE

: The Editor Name should be set to reflect the name of the text editor you are using. The Default D/L Path option should be set to the directory where you want to keep your downloaded Configuration and

Dictionary files. With no directory specified downloaded files will be saved in the current directory.

Technical Manuals Online! - http://www.tech-man.com

69

ASCII

Transfer

From the ASCII TRANSFER SETUP menu select option 6 to display the ASCII

TRANSFER SETUP menu. The following settings should be displayed.

ASCII UPLOAD

1) Echo locally ......... NO

2) Expand Blank Lines ... NO

3) Pace character ....... 0 (ASCII)

4) Character pacing ..... 1 (1/1000 sec)

5) Line pacing .......... 1 (1/10 sec)

6) CR translation ....... NONE

7) LF translation ....... STRIP

ASCII DOWNLOAD

8) CR translation ....... NONE

9) LF translation ....... NONE

System Monitoring & Control

Status

The computer can be used to monitor the status of the system. All status changes are transmitted from the P2 port of the CPU. The data transmitted can provide detailed

Monitoring

information on alarm, trouble and system status changes. It can also aid in troubleshooting by providing detailed information of system faults.

Access Levels

Control

Strings

System access levels may be accessed via the computer. By transmitting a Carriage Return

(Enter) to the system you will be prompted with “ ENTER PASSWORD” . By entering the proper password you may set the system to it’s various Access Levels.

Certain control strings may be transmitted to the system that provide remote control of the system from the computer. If the proper access level is enabled (see access levels) the system can be acknowledged, the signals can be silenced or the system can be reset from the computer. The following control strings provide these functions:

RESET = ^[Ox

ACKNOWLEDGE = ^[OP

SIGNAL SILENCE = ^[Or

Most software communication packages will allow the function keys to be configured for transmission of these control strings.

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Programming - Revision 5, 11/22/01

______________________________________________________________________________________________

System Programming via Computer

Programming

System programming menus may be accessed if the proper programming password is entered at the “ENTER PASSWORD:” prompt.

Û

Note

: Before proceeding, notify all personnel, monitoring companies and municipalities the system will be temporarily "out of service".

During all levels of programming, the system will be in an off-line status.

System Menu

The “System Menu” menu is displayed when the programming password is entered.

System Menu

1=Display 2=Change 3=Test

0=Exit

Display Menu

Selecting the “Display” option from the “System Menu” allows the user to display or download various system parameters. There are four options that may be selected from this menu (see Figure 5-2) and four options that may be selected from the “MISC.” menu. selection. (Figure 5-3).

Display Menu

1=Config 2=Dict 3=Events

4=Misc 0=Exit

Config Menu

The Configuration Menu allows the user to select either displaying the system module configuration or downloading the entire system configuration.

Configuration Menu

1=Display 2=Download 0=Exit

Technical Manuals Online! - http://www.tech-man.com

71

Display

Config

The system module configuration is displayed when option 1 is selected from the

Configuration Menu. This display shows the modules that are present in each card location, their associated card type code and a description of the card. The modules displayed are retrieved from the system configuration memory and are not a real time scan of the actual cards present (refer to the system test menu for a real time display).

Configuration Menu

1=Display 2=Download 0=Exit

>1

Card:0, ID:16 is CCM0: LEDs/T Switches

Card:1, ID:12 is CCM1: LEDs/T Switches

Card:2, ID:FF is Vacant

Card:3, ID:FF is Vacant

Card:4, ID:01 is CCM4: 2 Sig Ckt, Class A

Card:5, ID:02 is CCM5: 4 Rel Ckt

Card:6, ID:05 is CCM6: Misc. Ckts.

Card:7, ID:07 is CCM7: Unused

Card:8, ID:2C is Bad

Card:9, ID:0F is 4 BC Ckt

Card:10, ID:04 is 4 City Ties

Card:11, ID:2E is 8 Zone, Class B

Card:12, ID:1E is RY LEDs/T Switches

Card:13, ID:18 is RG LEDs/TR Switches

Card:14, ID:1E is RY LEDs/T Switches

Card:15, ID:1E is RY LEDs/T Switches

Card:16, ID:30 is 8 Sig Ckt, Class A

Card:17, ID:5E is 8 Rel Ckt

Card:18, ID:FF is Vacant

Card:19, ID:FF is Vacant

Card:20, ID:1E is RY LEDs/T Switches

Card:21, ID:1A is RG LEDs/T Switches

Press Enter Key To Continue

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Programming - Revision 5, 11/22/01

______________________________________________________________________________________________

System

Configuration

Codes Defined

Select this field to view the system modular placement (hardware configuration, card identification number and I/O card type assignment). The Identiflex 600 series systems utilize a fixed card placement design for identifying I/O module types (and associated displays), installed in the main cabinet as well as any

Modular

expander cabinets. The card locations are pre-defined and can not be altered.

Card numbered 0 through 7 are reserved for the various common control module

Placement

sections. These card location numbers are hardwired physical circuits. Card locations 8 - 39 are assigned to specific cards and displays utilized in Gamewell's

FlexAlarm 620 system and the IdentiFlex 650 systems. The exception is the

Card Locations

0 through 7

Cards # 8 - 39

Module Bus

Card ID #

analog addressable module which is assigned to card location number 17.

Cards numbered 0 through 7 identify the location of card types that reference the common control section of the system. Specifically, the electronic module functions are identified. These card location numbers reference hardwired physical circuits.

Card identification numbered 0 through 3 reference designated hardwired circuits interconnecting to the common control display module. Card identification numbered 4 - 7 reference designated hardwired circuits on the bus driver module.

Card numbered 8 through 39 are individual modules physically installed in cabinet bays (4 & 8 bay cabinets and 4 & 8 bay expander cabinets), see Installation Section

3, Figure 3-1 for cabinet layout. Each module (i.e. individual display or I/O module) has programmable addressing jumpers (1, 2, 3 or 4) which are designated on each module as S1. The addressing jumpers must be set according to the physical placement in the cabinet bay locations (1 through 4). Set the module addressing jumper (1 - 4) in the proper location to match the bay location (1 - 4).

The Module bus interconnects the left I/O modules and the right I/O modules with the bus driver module. The left I/O modules are linked (via ribbon cable) and interface with the bus driver module at J5 connector (labeled I/O Left). The right

I/O modules also interconnect (via ribbon cable) and interface with the bus driver module at J8 connector (labeled I/O Right). Each I/O module occupies one slot on the module bus.

The left I/O module displays are linked (via ribbon cable) and interface with the bus driver module at J6 connector (Display Left). The right I/O module displays are linked (via ribbon cable) and interface with the bus driver module at J7 connector

(Display Right). The addressing jumper of each display must match the associated

I/O module addressing jumper placement.

Each type of card is assigned a unique 8 bit code that the card transmits to the CPU when it is polled. In operation each card is periodically polled and returns its type code. The CPU detects if the card is functioning correctly, for a card type at that location. Refer to Table L4, IF650 Card ID Type.

Technical Manuals Online! - http://www.tech-man.com

73

Card

Location

00

01

Card Type

ID (Hex)

16

12

Card description

LEFT CCM 1: LEDs & T Switches

RIGHT CCM 2: LEDs & T Switches

04

05

06

01

02

05

CCM: 2 Signal Circuits, Class A

CCM: 4 Relay Circuits

CCM: City Tie, Buzzer etc

Zone Card

(CIM)

Signal Card

(USM)

Relay Card

0A

0B

0E

0F

1F

1E

1B

1A

17

16

13

12

19

18

28

29

2A & 2B

2C

2D

2E

2F

38

39

3A & 3B

3C

3D

3E

3F

5E

Analog Control Panel - Tactile SW installed

Analog Control Panel - Tactile SW missing

Building Control I/O Card - 8 circuit

Building Control I/O Card - 4 circuit

Red/Yellow LEDs, no 3 pos sw, no tactile sw (Alarm Display)

Red/Yellow LEDs, no 3 pos sw, tactile sw installed (Alarm Display)

Red/Green LEDs, no 3 pos sw, no tactile sw (Control Display)

Red/Green LEDs, no 3 pos sw, tactile sw installed (Control Display)

Combo Red/Green/Yellow LEDs no 3 pos sw, no tactile sw

(Left Control Display)

Combo Red/Green/Yellow LEDs no 3 pos sw, tactile sw installed

(Left Control Display)

Combo Red/Yellow LEDs, no 3 pos sw, no tactile sw

(Right Control Display)

Combo Red/Yellow LEDs, no 3 pos sw, tactile sw installed

(Right Control Display)

Red/Green LEDs, no 3 pos sw, no tactile sw (Fan Control )

Red/Green LEDs, no 3 pos sw, tactile sw installed (Fan Control )

Eight Circuit Class A installation

Four Circuit Class A (Alternate)

Invalid

Four Circuit Class A, plus Four circuit Class B

Four Circuit Class A

8 Circuit Class B

Four Circuit Class B

Eight Circuit Class A installation

Four Circuit Class A (Alternate)

Invalid

Four Circuit Class A, plus Four circuit Class B

Four Circuit Class A

8 Circuit Class B

Four Circuit Class B

Eight circuit

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Programming - Revision 5, 11/22/01

______________________________________________________________________________________________

Download

Config

Selecting Download from the Display Configuration Menu will prompt the system to transmit the complete system configuration file to the RS-232 port. When this is selected the system prompts the user to perform several steps. These steps are the actions required to receive an ASCII file when using PROCOMM communications software. When using alternate software packages follow the procedure required for that software to receive an

ASCII file. The next CR the system receives will start the transmission of the file.

Configuration Menu

1=Display 2=Download 0=Exit

>2

Ready to Download Configuration File.

Display Dict.

Menu

1. Press PgDn

2. Choose 7 (ASCII)

3. Enter Filename

This display option allows the user to view the contents of word dictionaries 1 - 5.

Dictionaries 1 - 4 may contain up to 128 entries and dictionary 5 may contain up to 1024 entries. By selecting this option the contents of all 5 user dictionaries are output to the laptop/computer screen.

Display Dictionary Menu

1=Display 2=Download 0=Exit

Technical Manuals Online! - http://www.tech-man.com

75

Display Dict.

Download

Dict.

The following is the format in which the dictionary will be displayed.

Start of Dictionary #1

End of Dictionary #1

Start of Dictionary #2

End of Dictionary #2

Start of Dictionary #3

End of Dictionary #3

Start of Dictionary #4

End of Dictionary #4

Start of Dictionary #5

End of Dictionary #5

Press Enter Key to Continue.

Selecting Download from the Display Dictionary Menu will prompt the system to transmit the complete set of 5 dictionaries to the RS-232 port. When this is selected the system prompts the user to perform several steps. These steps are the actions required to receive an

ASCII file when using PROCOMM communications software. When using alternate software packages follow the procedure required for that software to receive an ASCII file.

The next CR the system receives will start the transmission of the file.

Display Dictionary Menu

1=Display 2=Download 0=Exit

>2

Ready to Download Dictionary File.

1. Press PgDn

2. Choose 7 (ASCII)

3. Enter Filename

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Programming - Revision 5, 11/22/01

______________________________________________________________________________________________

Display

Events

The display events selection will prompt the CPU to output it’s complete history log to the

RS-232 port. The history log will contain all information regarding the system status changes for the previous 1000 events or since the last time the system Smart Start™ feature was invoked.

Display,

Misc.

Display Menu

1=Config 2=Dict 3=Events

4=Misc 0=Exit

>3

**** Start of Event Buffer ****

Status:NORMAL 03/27/95 15:08

Press Enter Key To Continue

When 4 (Misc) is selected from the Display menu, a sub-menu of selections is displayed.

Display Menu

1=Config 2=Dict 3=Event

4=Misc. 0=Exit

>4

Display Menu (Misc.)

1=Pass 2=Codes

3=Ver 4=Zone 0=Exit

Technical Manuals Online! - http://www.tech-man.com

77

Display Pass

Displaying the passwords allows the user to view the 10 passwords that are assigned to the system. Each password has a user ID and a security or access level assigned to it. This screen also shows the security levels that are assigned to each of the function keys. The following displays are the default settings for the Flex 600 system.

Display Menu

1=Config 2=Dict 3=Event

4=Misc 0=Exit

>4

Display Menu (Misc.)

1=Pass 2=Codes

3=Ver 4=Zone 0=Exit

>1

1. Pass:1111 User ID:USER1 Sec:1

2. Pass:2222 User ID:USER2 Sec:2

3. Pass:3333 User ID:USER3 Sec:3

4. Pass:4444 User ID:USER4 Sec:4

5. Pass:5555 User ID:USER5 Sec:1

6. Pass:6666 User ID:USER6 Sec:1

7. Pass:7777 User ID:USER7 Sec:1

8. Pass:8888 User ID:USER8 Sec:1

9. Pass:7111 User ID:USER1 Sec:1

10. Pass:7222 User ID:USER2 Sec:1

Ack:01 Rst:02 Sig:02 Drl:03

Byp:03 Wlk:03

Press Enter Key To Continue

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Programming - Revision 5, 11/22/01

______________________________________________________________________________________________

Display

Codes

Displaying the codes will allow the user to view the codes that are assigned to each of the

256 input groups. This is followed by information on the timing of the codes, number of rounds transmitted and weather the system reverts to March Time coding or silences after the coding is completed. The default setting for each code is 1,2,3,4,5,6.

Display Menu (Misc.)

1=Pass 2=Codes

3=Ver 4=Zone 0=Exit

>2

1=123456 2=123456 3=123456 4=123456

5=123456 6=123456 7=123456 8=123456

9=123456 10=123456 11=123456 12=123456

13=123456 14=123456 15=123456 16=123456

17=123456 18=123456 19=123456 20=123456

21=123456 22=123456 23=123456 24=123456

25=123456 26=123456 27=123456 28=123456

29=123456 30=123456 31=123456 32=123456

33=123456 34=123456 35=123456 36=123456

37=123456 38=123456 39=123456 40=123456

41=123456 42=123456 43=123456 44=123456

45=123456 46=123456 47=123456 48=123456

49=123456 50=123456 51=123456 52=123456

53=123456 54=123456 55=123456 56=123456

57=123456 58=123456 59=123456 60=123456

61=123456 62=123456 63=123456 64=123456

65=123456 66=123456 67=123456 68=123456

69=123456 70=123456 71=123456 72=123456

73=123456 74=123456 75=123456 76=123456

77=123456 78=123456 79=123456 80=123456

81=123456 82=123456 83=123456 84=123456

85=123456 86=123456 87=123456 88=123456

89=123456 90=123456 91=123456 92=123456

93=123456 94=123456 95=123456 96=123456

97=123456 98=123456 99=123456 100=123456

101=123456 102=123456 103=123456 104=123456

105=123456 106=123456 107=123456 108=123456

109=123456 110=123456 111=123456 112=123456

113=123456 114=123456 115=123456 116=123456

117=123456 118=123456 119=123456 120=123456

121=123456 122=123456 123=123456 124=123456

125=123456 126=123456 127=123456 128=123456

Pls:1.0Sec Cyl:04 Sig:OFF

Press Enter Key To Continue

Technical Manuals Online! - http://www.tech-man.com

79

Display Ver.

Display Zone

The version of firmware installed in the main CPU will be displayed when 3 (Ver) is selected from the Display Menu (Misc.).

Display Menu (Misc.)

1=Pass 2=Codes

3=Ver 4=Zone 0=Exit

>3

Flex 620 System, Version 1.0

Last Updated on Mar 14 1995 at 15:43:58

Press Enter Key To Continue

Displaying the zones allows the user to view the information associated with the conventional zone cards installed in the system. The card ID and description is displayed along with each associated circuit type and assigned code information.

Display Menu (Misc.)

1=Pass 2=Codes

3=Ver 4=Zone 0=Exit

>4

>>>>> Listing Zones Cards detected

Card #:0B is: 8 Zone, Class B

Ckt:38 Type:Auto Code:123456

Ckt:37 Type:Auto Code:123456

Ckt:36 Type:Auto Code:123456

Ckt:35 Type:Auto Code:123456

Ckt:34 Type:Auto Code:123456

Ckt:33 Type:Auto Code:123456

Ckt:32 Type:Auto Code:123456

Ckt:31 Type:Auto Code:123456

<<<<< End of Zones Cards detected

Press Enter Key To Continue

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Programming - Revision 5, 11/22/01

______________________________________________________________________________________________

Change

The system change menu allows the user to change various system parameters.

Menu

Change

Config

Change Menu

1=Config 2=Dict 3=Card

4=Misc 0=Exit

>

Changing the system configuration requires a previously downloaded system configuration file. When selected, the user is prompted with the sequence of keystrokes required for the

PROCOMM software package to Upload an ASCII file. When using other software packages, the keystrokes required to Upload an ASCII file should be followed. When using the PROCOMM software package the following settings should be configured.

Change Menu

1=Config 2=Dict 3=Card

4=Misc 0=Exit

>1

Ready to Upload Configuration File.

1. Press PgUp

2. Choose 7 (ASCII)

3. Enter Filename

Change

Dictionary

Changing the dictionary entries can be achieved by two means, changing the Words or

Uploading an entirely new dictionary.

Change Menu

1=Config 2=Dict 3=Card

4=Misc 0=Exit

>2

Change Dictionary Menu

1=Words 2=Upload 0=Exit

Technical Manuals Online! - http://www.tech-man.com

81

Change

Dict.Words

Upload

Dictionary

To change the Dictionary words, select 1 from the Change Dictionary Menu. The system will prompt you with the dictionary and word number to be changed. The existing word is then displayed. To change the word, type the desired text or press enter to leave the existing text and return to the word number prompt.

Change Dictionary Menu

1=Words 2=Upload 0=Exit

>1

Enter Dictionary #:1

Enter Word #:1

Overwrite Current Word:

Fire Alarm

Enter New Word:

Enter Word #:22

Word Doesn’t Exist, Append New Word

Enter New Word:

Enter Word #:

Uploading is accessed by selecting 2 from the Change Dictionary Menu. In order to upload a new dictionary, a file containing the new dictionary entries must be created using an

ASCII text editor. The SAN-RAN disk (P/N XXXXX) contains the AHED text editor that may be used to create the dictionary file. The dictionary file is comprised of a simple format that has very few restrictions ( See Dictionary File Format).

Change Dictionary Menu

1=Words 2=Upload 0=Exit

>2

Ready to Receive Dictionary File.

1. Press PgUp

2. Choose 7 (ASCII)

3. Enter Filename

Û

Note

: When changes are made to any of the dictionaries, they are appended to the existing dictionary. Therefore the entire number of added text may change when you exit the programming area. For example, if dictionary 2 has twelve entries and you add an entry as number 15, when you exit the program, the dictionary is appended and your new entry becomes number 13.

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Programming - Revision 5, 11/22/01

______________________________________________________________________________________________

Dictionary

File

The dictionary file format consists of the five dictionaries, each separated by two fore slashes (//) as delimiters. The first line of the dictionary file would contain two fore slashes indicating that it is the beginning of the file and the next line received will be word #0 of dictionary #1. This line should be left blank since each device defaults to word 0 of each dictionary. The following lines would contain the desired text entries, in numerical order, for dictionary one. When all of the entries for dictionary one have been entered, two fore slashes should be inserted on the next line to signify the end of dictionary one and the start of dictionary 2. Again the next line, word 0 dictionary 2, should be left blank for default purposes. This format is followed throughout the five dictionaries. The end of dictionary five is also signified by two fore slashes.

Some important points to keep in mind when writing the file are as follows. Dictionary one through dictionary four may contain up to 128 entries (0-127). Dictionary 5 may contain up to 1024 entries (0-1023). If all of the entries in any one dictionary are not used, the file does not need to contain blank lines before terminating the dictionary with two fore slashes.

Each dictionary entry may contain up to 40 characters. However, entries from dictionaries one and two are displayed on the third line of the alphanumeric display, and, entries from dictionaries three, four and five are displayed on the fourth line of the alphanumeric display. The total characters of dictionary entries used in conjunction with each other should not exceed 40 characters.

The file below illustrates a simple dictionary file.

//

Fire Alarm

Supervisory Alarm

//

Smoke Detector

Heat Detector

//

First Floor

Second Floor

Third Floor

//

Stairwell

Computer Room

Mechanical Room

//

Room 111

Room 112

Below Raised Floor

//

83

Technical Manuals Online! - http://www.tech-man.com

Change Card

Change Misc

The Flex 600 system allows components to be added or deleted without disturbing the programming (Control By Event, etc.) of other system components. When the Change

Card menu is selected, an Add or Delete option is then prompted. Select the desired option and enter the card number to be changed. (See system configuration in the installation section of this manual for card location information)

NOTE: When changing card types in a location the existing card should be deleted before the new card is added. This will ensure that the control by event table is

Change Menu

1=Config 2=Dict 3=Card

4=Misc 0=Exit

>3

Change Card Menu

1=Add 2=Delete 0=Exit

>1

Enter Card # To Add:

Delete Existing Card First !

Press Enter Key To Continue

Change Card Menu

1=Add 2=Delete 0=Exit

>2

Enter Card # To Delete: 1

Card Deleted From System

Press Enter Key To Continue

Change Card Menu

1=Add 2=Delete 0=Exit

Enter Card # To Add: 1

Card Added To System

Press Enter Key To Continue

The Change Misc selection accesses two sub menus, Menu1 and Menu2 These menus allow access to other change functions when selected.

Change Menu

1=Config 2=Dict 3=Card

4=Misc 0=Exit

>4

Change Card Menu

1=Menu1 2=Menu2 0=Exit

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Programming - Revision 5, 11/22/01

______________________________________________________________________________________________

Change

Menu 1

Change Menu 1 accesses menus to change Passwords, Codes, Time and Date,

Sequence Key Access levels and the Baud Rate detect function.

Change Pass

The Change Password menu is used to change the password, user name and/or the access level associated with the passwords. When this is selected from Change Menu

1, the previously programmed password information is displayed followed by a prompt requesting the password number to be changed. When the password number is entered the “Enter Password” prompt is displayed. Enter the new password (Four

Digits) or press enter to leave the existing password. This is followed with the User

ID prompt. The User ID may contain up to 8 ASCII characters. After defining the user the access level or security level (Sec:)assigned to that password is defined.

NOTE: Before changing the password # 4 (programming password) make sure that you have added a new password to access the programming (Sec: 4) area.

Change Menu (Misc.)

1=Menu1 2=Menu2

0=Exit

>1

Change Menu 1

1=Pass 2=Code 3=Date 4=Seq

5=Baud 6=Words 0=Exit

>1

1. Pass:1111 User ID:USER1 Sec:1

2. Pass:2222 User ID:USER2 Sec:2

3. Pass:3333 User ID:USER3 Sec:3

4. Pass:4444 User ID:USER4 Sec:4

5. Pass:5555 User ID:USER5 Sec:1

6. Pass:6666 User ID:USER6 Sec:1

7. Pass:7777 User ID:USER7 Sec:1

8. Pass:8888 User ID:USER8 Sec:1

9. Pass:7111 User ID:USER1 Sec:1

10. Pass:7222 User ID:USER2 Sec:1

Enter Password # To Change:1

Enter Password:1234

Enter User ID: John Doe

Enter Security level:1

1. Pass:1234 User ID:John Doe Sec:1

2. Pass:2222 User ID:USER2 Sec:2

3. Pass:3333 User ID:USER3 Sec:3

4. Pass:4444 User ID:USER4 Sec:4

5. Pass:5555 User ID:USER5 Sec:1

6. Pass:6666 User ID:USER6 Sec:1

7. Pass:7777 User ID:USER7 Sec:1

8. Pass:8888 User ID:USER8 Sec:1

9. Pass:7111 User ID:USER1 Sec:1

10. Pass:7222 User ID:USER2 Sec:1

Enter Password # To Change:

Technical Manuals Online! - http://www.tech-man.com

85

Change Code

The codes in the Flex 600 systems are assigned to the input groups. When a device within that group alarms, that code would be sounded on the signal circuits that have been programmed as coded circuits. Each input group may be assigned an individual code that contains up to 6 digits. The digits are defined in hexadecimal and range from 0-9 and A-F. When selected each digits (1-6) of the code is entered individually.

After the code has been entered a sub menu appears. This menu allows you to change the Timing, the number of Cycles and the output of the signal circuits after the code is complete, silence or March Time signal.

Change Menu 1

1=Pass 2=Code 3=Date 4=Seq

5=Baud 6=Words 0=Exit

>2

Enter Input Ckt/Group Number:1

Current Code For Ckt/Group1=123456

Enter Digit 01:656565Re-enter Input :6

Enter Digit 02:5

Enter Digit 03:4

Enter Digit 04:3

Enter Digit 05:2

Enter Digit 06:1

New Code For Ckt/Group1=654321

Enter Input Ckt/Group Number:

Change Coded Signal's Parameters

1=Timing 2=Cycles 3=Signal

0=Exit

>1

Change Coded Signal's Timing

1=0.5 2=1.0 3=1.5 4=2.0

0=Exit

>2

Enter # of Cycles (1-8):

>3

Choose Signal

1=OFF 2=March Time

0=Exit

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Programming - Revision 5, 11/22/01

______________________________________________________________________________________________

Change Date

To change the date and/or time in the Flex 600 system the Change Date Menu must be selected. This menu prompts the user with the information the system requires to enter a new time and date.

Change Seq

Change Menu 1

1=Pass 2=Code 3=Date 4=Seq

5=Baud 6=Words 0=Exit

>3

Current Date/Time

Date 03/31/95 Time 09:52:41

Enter Month :03

Enter Date :30

Enter Year :95

Enter Hour :10

Enter Minutes: 43

New Date/Time

Date 03/30/95 Time 10:43:00

Press Enter Key To Continue

The Change Sequence option allows the user to redefine the access levels associated with each of the sequence keys. Each of these keys is assigned an access level by default. The Acknowledge key is assigned to level 1 access, the Reset, Signal Silence and Drill keys are assigned to level 2 and the Detector test, WalkTest and Bypass keys are assigned to level 3.

Any of these keys may be reassigned by selecting this option, pressing the key to be reassigned and entering the access level desired. These keys may also be assigned to level 4 access (programming level). By assigning a key to level 4 access, that keys operation is inhibited.

Change Menu 1

1=Pass 2=Code 3=Date 4=Seq

5=Baud 6=Words 0=Exit

>4

Change Sequence's Security

Press A Sequence's Key

Press Enter Key To Exit

Acknowledge, Current:01 Enter New:01

Technical Manuals Online! - http://www.tech-man.com

87

Change Baud

Baud Rate

Switch

Settings

The Change Baud selection will cause the system to output a printer test pattern to the

RS-232 port. This continuous output allows the user to select the baud rate of the connected device without having to cause system abnormalities.

Change Menu 1

1=Pass 2=Code 3=Date 4=Seq

5=Baud 6=Words 0=Exit

>5

Ready To Read Dip Switch and Set

Serial Port 1's Baud Rate.

Press Enter Key To Proceed...

0123456789:;<=>[email protected][\]^_`abcdef ghijklmnopqrstuvwxyz{|}~!"#$%&'()*+,./0123456789:;<=>[email protected]

IJKLMNOPQRSTUVWXYZ[\]^_`abcdefghijklmnopqrstuvwxyz{|}~!"#$%

&'()*+,./0123456789:;<=>[email protected][\]^

_`abcdefghijklmnopqrstuvwxyz{|}~!"#$%&'()*+,./0123456789:;<=>[email protected]

CDEFGHIJKLMNOPQRSTUVWXYZ[\]^_`abcdefghijklmnopqrstuvwxyz{|

}~!"#$%&'()*+,./0123456789:;<=>[email protected]

WXYZ[\]^_`abcdefghijklmnopqrstuvwxyz{|}~!"#$%&'()*+,./0123456789:;

<=>[email protected][\]^_`abcdefghijklmnopqr stuvwxyz{|}~!"#$%&'()*+,./0123456789:;<=>[email protected]

QRSTUVWXYZ[\]^_`abcdefghijklmnopqrstuvwxyz{|}~!"#$%&'()*+,-

./0123456789:;<=>[email protected]{|}~

The baud rate is changed by setting DIP switch SW1 on the CPU module to the desired speed ( see below table). Select this option to read new setting.

SW1 - Settings

S1

S2

S3

S4

S5

S6

Note

:

S7, S8 Open

S7, S8 Closed

S7 Open, S8 Closed

S7 Closed, S8 Open

Open

Open

Do Not Change

Do Not Change

Always Closed

Open

Open

Open

Do Not Change

Do Not Change

Do Not Change

Do Not Change

P2 baud rate of is selected via S7 and S8.

Auto Detect

Baud rate is utilized for peripheral devices.

9600 Baud Rate

4800 Baud Rate

2400 Baud Rate

1200 Baud Rate

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Programming - Revision 5, 11/22/01

______________________________________________________________________________________________

Change

Words

The Change Words option allows descriptions of individual hardwired circuits to be assigned. Each circuit (input and output) may be assigned an entry from each of the five dictionaries. When selected the system prompts the user to enter the dictionary then the word number of that dictionary. Pressing the enter key twice on a blank line will exit this menu.

Change Menu 1

1=Pass 2=Code 3=Date 4=Seq

5=Baud 6=Words 0=Exit

>6

Press an I/O Ckt. or Enter Ckt. #:01

Press an I/O Ckt. or Enter Ckt. #:49

Enter Ckt.'s Word # To Change (1-5):1

Current Word:

Enter Replacement Word # (0-127):1

Fire Alarm

Enter Ckt.'s Word # To Change (1-5):2

Current Word:

Enter Replacement Word # (0-127):1

Fire Alarm Smoke Detector

Enter Ckt.'s Word # To Change (1-5):3

Current Word:

Enter Replacem1ent Word # (0-127):

Fire Alarm Smoke Detector

1st.

Enter Ckt.'s Word # To Change (1-5):4

Current Word:

Enter Replacement Word # (0-127):1

Fire Alarm Smoke Detector

1st. Floor Room Number

Enter Ckt.'s Word # To Change (1-5):5

Current Word:

Enter Replacement Word # (0-127):1

Fire Alarm Smoke Detector

1st. Floor Room Number 1

Enter Ckt.'s Word # To Change (1-5):

Press an I/O Ckt. or Enter Ckt. #:

Technical Manuals Online! - http://www.tech-man.com

89

To select word options from the faceplate of the control panel:

Prompt Description

<a1> = first lower case letter of a word or key

<a2> =

<a3> = second lower case letter of a word or key third lower case letter of a word or key

<a

#> =

<A1> =

<A2> =

<A#> etc. (sequential order)

First Upper Case letter of a word or key

Second Upper Case letter of a word or key etc. (sequential order)

Note

: The term “key” used in the above table refers to any user identifying code which is entered as a word.

1.

1.1

1.2

Press the Letters/ Numbers key on the Keypad until the proper selection is displayed. The display indicates the selection by the following means.

When assigning the first letter to a word (or key) <a1> should be displayed in the upper right hand corner of the display. To select the second letter of that word, press the Letters/ Numbers key until

<a2> is displayed. <a3> should be displayed if the third letter is desired and <#> should be displayed if the number associated with that key is desired.

The case of the letters may be changed by pressing the Caps key. The case is indicated by the case setting of the <A> within the brackets shown on the display. When the desired number or letter field is displayed press the key associated with it then go on to the next letter, number or punctuation mark. When the text entry is complete press the “

Enter

” key and go on to the next text entry to change. To exit the programming area, and save the changes made, press the “

Enter

” key.

Note

: When changes are made to any dictionaries they are appended to the existing dictionary. Therefore the entire number of added text may change when you enter the programming area. For example, if dictionary 2 has twelve entries and you add an entry as number 15, when you exit the program, the new entry becomes number 13.

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Programming - Revision 5, 11/22/01

______________________________________________________________________________________________

Change Menu 2

Change menu 2 has options to change the City Tie operation, the Automatic Signal

Silence Timer, The Annunciator Supervision, The Trouble Relay operation and the

Automatic Dialer connection.

Change City

The City Tie Circuit is designed to operate in two modes of operation. Standard mode and Chicago mode. In the standard mode alarms and troubles are transmitted over the city tie circuit. In the Chicago mode the city tie transmits all troubles and alarms with the exception of City Tie troubles. If the city tie circuit detects a trouble condition the Spare relay will transfer for use with a local indicator that indicates troubles and alarms can’t be transmitted.

Change Sig Sil

Change Ann

Change Menu (Misc.)

1=Menu1 2=Menu2

0=Exit

Change Menu 2

1=City 2=Sig Sil 3=Ann 4=Trbl

5=Dialer 6=Prefix 0=Exit

>1

Press Enter Key To Exit

Press Any Other Key To Toggle

City Tie Is In Standard Mode

City Tie Is In Chicago Mode

The Sig Sil option allows the user to set the Automatic Signal Silence timer. This is the length of time the signal circuits will operate before automatically silencing when selected.

EXAMPLE: Entry of the number 3 would equal 90 seconds (3 x 30 sec.= 90sec.)

Change Menu 2

1=City 2=Sig Sil 3=Ann 4=Trbl

5=Dialer 6=Prefix 0=Exit

>2

Sig Sil Delay Is Set To:0 Min

Delay = Entry (0-10) x 30 Sec

Enter New Sig Sil Delay (0-10):

The change Ann option allows the user to enable and disable the supervision of the supervised annunciator devices connected to the RS-232 port.

Change Menu 2

1=City 2=Sig Sil 3=Ann 4=Trbl

5=Dialer 6=Prefix 0=Exit

Press Enter Key To Exit

Press Any Other Key To Toggle

Remote Annunciator is Detached

Remote Annunciator is Attached

Technical Manuals Online! - http://www.tech-man.com

91

Change Trbl

Change

Dialer

Change

Prefix

The Change Trouble option should be in the “Troubles are Annunciated” Mode. This feature is used in Special Applications where a backup system is required. Special modules and wiring are required to utilize this option. Please consult your factory representative for applications requiring redundant system operation.

Change Menu 2

1=City 2=Sig Sil 3=Ann 4=Trbl

5=Dialer 6=Prefix 0=Exit

>4

Press Enter Key To Exit

Press Any Other Key To Toggle

I/O Troubles Are Annunciated

I/O Troubles Are Not Annunciated

This option allows the system to delay the reporting of AC failure as required by UL when the “Dialer Is Installed” is selected. Normal reporting of AC failure troubles is restored when the “Dialer Is Not Installed “ option is selected.

Change Menu 2

1=City 2=Sig Sil 3=Ann 4=Trbl

5=Dialer 6=Prefix 0=Exit

>5

Press Enter Key To Exit

Press Any Other Key To Toggle

Dialer Is Not Installed

Dialer Is Installed

This option allows the user to change the Prefix for alarm events that occur. The default setting is FIRE Alarm. If the panel were monitoring Gas detectors, for example. The Prefix could be changed to GAS and therefore display GAS Alarm during alarm conditions.

Change Menu 2

1=City 2=Sig Sil 3=Ann 4=Trbl

5=Dialer 6=Prefix 0=Exit

>6

Current Alarm Prefix is: Fire

Enter New Alarm Prefix: XXXX

Do you want to clear prefix Y/N? N

Alarm Prefix is set to! Fire

Press any key to continue

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Programming - Revision 5, 11/22/01

______________________________________________________________________________________________

Test Menu

The test menu is a useful tool when testing and troubleshooting the Flex 600 systems.

The various options allow the testing of the input and output devices a circuits, ground fault monitoring and system communications.

Test Input

The Input Test allows the user to test input circuit cards and monitor for circuit noise. This selection requires the input of the card location number (see installation section for card location numbers) to be tested. The card is continuously scanned and a “real time” value in Hexadecimal format (base 16) is returned for each of the 8 circuits (0-7) for that card location.

EXAMPLE: The normal value for a CIM card to return would be approximately 0E hex. If the circuit is open the value would drop to 00 hex . If a short circuit occurs the value returned would increase up to FF hex.

>1

Input Card Test

Test Menu

1=Input 2=Output 3=ID 4=Gnd

5=Lamp 0=Exit

Enter Input Card #:11

Press Enter Key To Exit

0=0E 1=0E 2=0E 3=0E 4=0E 5=0E 6=0E 7=0E

0=0F 1=0E 2=0E 3=0E 4=0F 5=0F 6=0E 7=0F

Technical Manuals Online! - http://www.tech-man.com

93

Test Output

Test ID

The Output Test is used to test the interaction between an input circuit and an output circuit. When selected the user is prompted to enter the output card location number to be tested. Then the input card location that is to be used to control the output card is entered. When the input circuit is activated, the corresponding output card circuit will activate.

EXAMPLE1: If card location 12 (CIM display) is selected as the output card location and card location 12 is selected as the input card location, when a switch on card 12 is pressed the corresponding LED will light.

EXAMPLE2: If output card location 17 (USM-8) is selected and input card 21

(USM-8 display) is selected, the corresponding signal circuit will activate when the display switch is pressed.

NOTE : When card 0 (main display) is selected on the 630 and 650 systems, no input card option is displayed. Pressing the front panel switches will toggle the LED’s and display the switch number pressed.

Test Menu

1=Input 2=Output 3=ID 4=Gnd

5=Lamp 0=Exit

>2

Output Card Test

Enter Output Card #:9

Enter Input (Keys) Card #:13

Press Enter Key To Exit

Selecting the Test ID option will continuously display the “real time” card readings from the system card locations. The card locations (0-39) should always equal the card type installed in that location.

Test Menu

1=Input 2=Output 3=ID 4=Gnd

5=Lamp 0=Exit

>3

00=16 01=12 02=FF 03=FF 04=01 05=02

06=05 07=07 08=2C 09=0F 10=04 11=2E

12=1E 13=18 14=1E 15=1E 16=30 17=5E

18=FF 19=FF 20=1E 21=1A 22=FF 23=FF

24=FF 25=FF 26=FF 27=FF 28=FF 29=FF

30=FF 31=FF 32=FF 33=FF 34=FF 35=FF

36=FF 37=FF 38=FF 39=FF

Technical Manuals Online! - http://www.tech-man.com

Flex 620 Programming - Revision 5, 11/22/01

______________________________________________________________________________________________

Test Gnd

The Gnd (Ground) test utilizes a unique method of ground detection. A measurement is taken from the +5 supply to earth ground and a value is displayed. Then a measurement from system common is taken and its value is displayed. The differential value between these two measurements must be greater than 142 but less than 255 for a reading of “Good”.

Note : The values displayed are derived from an A/D conversion and not displayed in actual voltages.

Test Menu

1=Input 2=Output 3=ID 4=Gnd

5=Lamp 0=Exit

>4

Ground Fault Test

Press Enter Key To Exit

142 < Diff < 255

5V=216, Gnd=1, Diff=215 : Good

Test Lamp

The Test Lamp selection will cause the system to test the LED’s on all of the modules in the system. The sounder will alternate on and off while each cards LED’s are lit in sequence.

Test Menu

1=Input 2=Output 3=ID 4=Gnd

5=Lamp 0=Exit

>5

Technical Manuals Online! - http://www.tech-man.com

95

MODULE

BDM

QTY

1

IDENTIFLEX 620 BATTERY CALCULATION CHART

NORMAL CURRENT ALARM CURRENT NORMAL

TOTAL

1

.205 .337 + signal circuit power +

.002 for master box and .022 for reverse polarity

.070

3 S+S- note

4

A+A- note

4

12VDC note

4

ALARM

TOTAL

2

CIM-4

CIN-8

.050

.090

.050 per active ckt

.050 per active ckt

CIM-4

W/CIM-SDA

CIM-8

W/CIM-SDA

USM-4

USM-8

.050

.050

.018

.018 x

.050 per active ckt

.022 per active class a relay

.050 per active ckt

.022 per active class a relay

.020 PER CKT + signal load

.020 PER CKT + signal load

USM-4

W/USM-SZA

USM-4

W/USM-SZA

CTX

RM-4

RM-8

BC-4

.018

.018

.020 PER CKT + signal load

.022 per active class a relay

.020 PER CKT + signal load

.022 per active class a relay

.020 +.005 per active ckt .020 +max .046 per active circuit

.010 +.003 for each inactive Normal +.022 per active feedback point and .006 for each circuit active

.010 +.003 for each inactive Normal +.022 per active feedback point and .006 for each circuit active

.010 +.003 for each inactive Normal +.022 per active feedback point and .006 for each circuit active

BC-8 .010 +.003 for each inactive Normal +.022 per active feedback point and .006 for each circuit active

.001 CABINET

EXPANDER

.001

ALARM PERCENT CALCULATION

0.10=10% 1.00=100%

TOTAL NORMAL

CURRENT

HOURS OF STANDBY TOTAL NORMAL

CURRENT

= NORMAL Amp Hours x

HOURS OF ALARM

5

TOTAL ALARM

CURRENT

=ALARM Amp Hours

TOTAL ALARM

CURRENT

Hours

ALARM Amp Hours

TOTAL

TOTAL X 1.25

BATTERY AH

REQUIRED

(note 6)

1

NORMAL TOTAL is figured by multiplying the number of modules times the current values for that module

2

ALARM TOTAL is figured by multiplying the number of modules/active points times the current values for that module

3

The Common Control Module consists of Bus Driver Module, CPU, Common Relays, Power Supply and Common Displays.

4

The actual loads for Normal and Alarm currents being drawn on the power terminals should be placed in the Normal Total and Alarm

Total boxes for each power output.

5

6

Minutes of alarm is figured by dividing the minutes required by 60. 5 minutes divided by 60 equals .083 minutes

Maximum of 50 AH Permitted