- No category
advertisement
VAM I/O units
Publication version: VIOen M/A001
User manual
Trace back information:
Workspace Main version a5
Checked in 2012-10-18
Skribenta version 803
3
Contents VAM I/O units
Contents
1 This document .........................................................................
Legal notice ......................................................................
Safety information ............................................................
Related documents ..........................................................
Abbreviations and symbols ..............................................
2 Introduction .............................................................................
Purpose ............................................................................
Main properties ................................................................
3 User interface ..........................................................................
VAM 3L ............................................................................
VAM 3LX ..........................................................................
VAM 10L ..........................................................................
VAM 10LD ........................................................................
VAM 12L ..........................................................................
VAM 12LD ........................................................................
VAM 4C ............................................................................
VAM 4CD .........................................................................
VAMP 4R .........................................................................
4 Programming switches ...........................................................
Switches for arc sensor I/O units .....................................
Switches for current I/O units ...........................................
5 Adjusting the overcurrent setting ..........................................
6 BI/BO connection ....................................................................
7 Connection examples .............................................................
VAM 3L / VAM 3LX interfaces ..........................................
VAM 10L interfaces ..........................................................
VAM 10LD interfaces .......................................................
VAM 12L interfaces ..........................................................
VAM 12LD ........................................................................
VAM 4C interfaces ...........................................................
VAM 4CD interfaces .........................................................
Multiplying relay VAMP 4R ...............................................
8 Technical data ..........................................................................
Connections .....................................................................
Auxiliary power supply ........................................
Digital inputs (BI/O bus) ......................................
Trip contacts ........................................................
Test and environmental conditions ..................................
Environmental conditions ....................................
VIOen M/A001
VAM I/O units Contents
Casing .................................................................
Package ..............................................................
9 Construction ............................................................................
Dimensional drawings ......................................................
VAM 3L / 3LX Din rail mounting ..........................
VAM 10L Din rail mounting ..................................
VAM 10LD Flush mounting .................................
VAM 12L Din rail mounting ..................................
VAM 12LD Flush mounting .................................
VAM 4C Din rail mounting ...................................
VAM 4CD Flush mounting ...................................
VAMP 4R Din rail mounting .................................
VA 1 DA ...............................................................
9.1.10 VA 1 EH ...............................................................
9.1.11 VYX 001 ..............................................................
9.1.12 VYX 002 ..............................................................
I/O unit mounting and wiring ............................................
VAM 3L, VAMP 3LX, VAM 10L, VAM 12L, VAM
4C ........................................................................
VAM 10LD, VAM 12LD, VAM 4CD ......................
Wiring of the I/O units ......................................................
Wiring the secondary circuits of the current transformers
(VAM 4C / VAM 4CD only) ...............................................
Wiring the trip circuits of the circuit breakers ...................
Wiring between the central unit and the I/O unit ..............
Wiring separate auxiliary supplies ...................................
VAMP 4R .........................................................................
Wiring multiple central units .............................................
9.10 Arc sensors ......................................................................
10 Order information ....................................................................
11 Glossary ...................................................................................
VIOen M/A001 4
5
1
1.1
1.2
1 This document VAM I/O units
This document
Legal notice
Copyright
©Schneider Electric 2012. All rights reserved.
Disclaimer
No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this document. This document is not intended as an instruction manual for untrained persons. This document gives instructions on device installation, commissioning and operation. However, the manual cannot cover all conceivable circumstances or include detailed information on all topics. In the event of questions or specific problems, do not take any action without proper authorization. Contact Schneider Electric and request the necessary information.
Contact information
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00 www.schneider-electric.com
Safety information
• Failure to follow these instructions will result in death or serious injury
• Only qualified personnel should install this equipment. Such work should be performed only after reading this entire set of instructions.
• Turn off all power supplying this equipment before starting the installation work.
• Ensure the protective grounding is connected.
• Before performing visual inspections, commissioning, or maintenance on this equipment, disconnect all sources of electric power.
VIOen M/A001
VAM I/O units
1.3
1 This document 1.3 Related documents
• Assume that all circuits are live until they have been completely de-energised, tested and tagged. Pay particular attention to the design of the power system. Consider all sources of power, including the possibility of backfeeding.
• Beware of potential hazards, wear personal protective equipment, carefully inspect the work area for tools and objects that may have been used during commissioning or maintenance.
• Neglecting fundamental installation requirements can lead to personal injury as well as damage to electrical equipment or other property.
• Handling this equipment requires relevant expertise in the field of protection of electrical networks. Only competent people who have this expertise are allowed to configure and set up this equipment.
• Before performing dielectric (Hi-Pot) testing on any equipment in which the IED is installed, disconnect all input and output wires to the IED. High voltage testing can damage electronic components contained in the unit.
• Always use a properly rated voltage sensing device to confirm that all power is off.
• The successful operation of this equipment depends upon proper handling, installation, and operation.
Related documents
Table 1.1: Related documents
Document
VAMP Mounting and Commissioning Instructions
VAMP Arc I/O units user manual
VAMP Arc Flash Protection Testing Manual
VAMPSET Setting and Configuration Tool User Manual
*) xxxx = revision number
Identification* )
VARC_MC_xxxx
VIO_EN_M_xxxx
VARCTEST_EN_M_xxx
VVAMPSET_EN_M_xxxx
Download the latest documents and software at www.vamp.fi.
VIOen M/A001 6
7
1.4 Abbreviations and symbols
1.4
1 This document VAM I/O units
Abbreviations and symbols
Table 1.2: Symbols
Symbol Description
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
Addresses practices not related to personal injury.
Table 1.3: Abbreviations
ANSI
CB
CBFP
Dead band
DI
DO
DSR
DST
DTR
FFT
Hysteresis
IEC
IEEE
IEC-101
IEC-103
LAN
Latching
NTP
PT pu
SNTP
TCS
THD
American National Standards Institute. A standardization organisation.
Circuit breaker
Circuit breaker failure protection
See hysteresis.
Digital input
Digital output, output relay
Data set ready. An RS232 signal. Input in front panel port of VAMP relays to disable rear panel local port.
Daylight saving time. Adjusting the official local time forward by one hour for summer time.
Data terminal ready. An RS232 signal. Output and always true (+8
Vdc) in front panel port of VAMP relays.
Fast Fourier transform. Algorithm to convert time domain signals to frequency domain or to phasors.
I.e. dead band. Used to avoid oscillation when comparing two near by values.
International Electrotechnical Commission. An international standardization organisation.
Institute of Electrical and Electronics Engineers
Abbreviation for communication protocol defined in standard IEC
60870-5-101
Abbreviation for communication protocol defined in standard IEC
60870-5-103
Local area network. Ethernet based network for computers and relays.
Output relays and indication LEDs can be latched, which means that they are not released when the control signal is releasing.
Releasing of lathed devices is done with a separate action.
Network time protocol for LAN and WWW
See VT
Per unit. Depending of the context the per unit refers to any nominal value. For example for overcurrent setting 1 pu = 1xI mode
.
Simple Network Time Protocol for LAN and WWW
Trip circuit supervision
Total harmonic distortion
VIOen M/A001
VAM I/O units
U
0sec
U a
U b
U c
U n
UTC
VT
VT pri
VT sec
WWW
1 This document 1.4 Abbreviations and symbols
Voltage at input U c at zero ohm earth fault. (Used in voltage measurement mode “2LL+Uo”)
Voltage input for U
12 mode or U
L1 depending of the voltage measurement
Voltage input for U
23 mode or U
L2 depending of the voltage measurement
Voltage input for U
31 mode or U
0 depending of the voltage measurement
Nominal voltage. Rating of VT primary or secondary
Coordinated Universal Time (used to be called GMT = Greenwich
Mean Time)
Voltage transformer i.e. potential transformer PT
Nominal primary value of voltage transformer
Nominal secondary value of voltage transformer
World wide web (internet)
VIOen M/A001 8
9
2
2.1
2.2
2 Introduction VAM I/O units
Introduction
This User’s Manual contains a functional description of the VAM I/O units and technical data.
Purpose
The main purpose of the VAM I/O units is to detect arc light or short circuit current and deliver this information (zone information) to the arc protection central unit and the other VAM I/O units. Additionally
VAM I/O units can be used for tripping appropriate circuit breakers.
Main properties
Arc flash protection system is a modular system consisting of a central unit, I/O units and arc sensors.
Due to its modularity, the system is suitable for a range of arc protection applications, from simple systems with one central unit and one I/O unit to more complex solutions comprising several central units used for selective arc protection.
The I/O unit VAM 10L / VAM 10LD, VAM 12L / VAM 12LD serves as link between the system’s point sensors and the central unit. Each
I/O unit has connections for ten arc sensors, one portable pin sensor and one trip output.
The I/O unit VAM 3L/VAM3LX serves as link between the system’s fibre sensors and the central unit. Each I/O unit has connections for three arc sensors, one pin sensor and one trip output.
The I/O unit VAM 4C / VAM 4CD serves as link between the system’s current inputs and the central unit. Each I/O unit has connections for three current transformers and one trip output.
The arc sensor VA 1 DA is activated by strong light. The sensor transforms the light information into the current signal, which is forwarded through the I/O unit to the central unit. The arc sensor VA
1 EH also operates on the same principle.
The pin sensor VA 1 DP has the same functions as an arc sensor but can be temporarily connected to an I/O unit. The sensor can be fixed to the breast pocket of a technician to improve safety when working with live switchgear.
The door mounted VAM I/O units with the letter D in the type designations VAM 10LD, VAM 12LD and VAM 4CD are door mounted versions for the corresponding VAM 10L, VAM 12 L and VAM 4C units. The functionality is exactly the same.
VIOen M/A001
VAM I/O units
3
3.1
VIOen M/A001
3 User interface
User interface
Usually, there is no need to touch the front panel during normal operation, since all the necessary information can be read from the central unit display. However, after a new installation or a system expand you will need to program certain functions (zone/address, trip output) in the I/O unit.
If you unfasten the terminal blocks during installation, remember to tighten the fixing screws after installation! Also tighten the screws even if you did not unfasten the blocks.
VAM 3L
12
VAM 3L
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X2
COM 1
6
COM 2
1
2
BI/O
Latch
L+I / L
Zone
Addr.
6
7
4
5
8
2
3
OFF
1
SW1
ON
SENSOR
OK
ACT
9
10
TRIP
11
7
CH1
SENSOR INPUTS
CH2 CH3
3
4
5
POWER
COM
ERROR
R1 T1 R2 T2 R3 T3
VAM3 L
8
Figure 3.1: Arc fibre sensor I/O unit VAM 3L front panel
1. Connection for portable arc sensor (VA 1 DP)
2. Programming switches
3. POWER indicator light, indicates that the supply voltages of each component are in order.
4. COM indicator light, lit when the central units and I/O units are communicating.
5. ERROR indicator light, indicates an internal fault detected by the component’s self-diagnostics. Such faults include faulty arc sensor or changes in the amount of sensors.
6. Connector sockets for the VX001 modular cables
7. LED lights indicating sensor activation
10
3.1 VAM 3L 3 User interface VAM I/O units
8. Terminals for three fibre sensors
9. Portable arc sensor VA 1 DP connected and operational
10. Portable arc sensor activated
11. I/O unit trip relay activated
12. Terminal block for external communication and BI/O channels and trip signal
11 VIOen M/A001
VAM I/O units
3.2
3 User interface 3.2 VAM 3LX
VAM 3LX
12
16 15 14 13 12 11 10 9
VAM 3LX
8 7 6 5 4 3 2 1
COM 1
X2
6
COM 2
1
2
BI/O
Latch
L+I / L
Zone
Addr.
6
7
8
4
5
OFF
1
2
3
SW1
ON
SENSOR
OK
ACT
9
10
TRIP
11
7
CH1
SENSOR INPUTS
CH2 CH3
3
4
5
POWER
COM
ERROR
R1 T1 R2 T2
8
R3 T3
CH1
Adj
CH2
Adj
CH3
Adj
13
Min. Max. Min. Max. Min. Max.
VAM 3LX
Figure 3.2: Arc fibre sensor I/O unit VAM 3LX front panel
1. Connection for portable arc sensor (VA 1 DP)
2. Programming switches
3. POWER indicator light, indicates that the supply voltages of each component are in order.
4. COM indicator light, lit when the central units and I/O units are communicating.
5. ERROR indicator light, indicates an internal fault detected by the component’s self-diagnostics. Such faults include faulty arc sensor or changes in the amount of sensors.
6. Connector sockets for the VX001 modular cables
7. LED lights indicating sensor activation
8. Terminals for three fibre sensors
9. Portable arc sensor VA 1 DP connected and operational
10. Portable arc sensor activated
11. I/O unit trip relay activated
12. Terminal block for external communication and BI/O channels and trip signal
13. Sensitivity adjustments for each fibre sensor channels
VIOen M/A001 12
3.3 VAM 10L
3.3
3 User interface VAM I/O units
VAM 10L
12
VAM 10L
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X2
COM 1
6
COM 2 M
OELLER
1
2
L> ext/int
Latch
L+I / L
Zone
Addr.
5
6
7
8
3
4
OFF
1
2
SW1
ON
SENSOR
OK
9
ACT
10
TRIP 11
3
4
5
POWER
COM
ERROR
1 2 3
7
4
SENSOR INPUTS
5 6 7 8 9 10
X1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
8
VAM10L
Figure 3.3: Arc sensor I/O unit VAM 10L front panel
1. Connection for portable arc sensor (VA 1 DP)
2. Programming switches
3. POWER indicator light, indicates that the supply voltages of each component are in order.
4. COM indicator light, lit when the central unit and I/O units are communicating.
5. ERROR indicator light, indicates an internal fault detected by the component’s self-diagnostics. Such faults include faulty arc sensor or changes in the amount of sensors.
6. Connector sockets for the VX001 modular cables
7. LED lights indicating sensor activation
8. Terminal block for ten arc sensors
9. Portable arc sensor VA 1 DP connected and operational
10. Portable arc sensor activated
11. I/O unit trip relay activated
12. Terminal block for external communication and BI/O channels and trip signal
VIOen M/A001 13
VAM I/O units
3.4
3 User interface
VAM 10LD
VAM 10LD
Arc Protection I/O-UNIT
M
1 2 3 4
7
SENSOR CHANNELS
5 6 7 8 9 10
13
ADDRESS NR 10
1. BB FEEDER 7
2. CB FEEDER 7
3. CC FEEDER 7
4. BB FEEDER 8
5. CB FEEDER 8
6. CC FEEDER 8
7. BB FEEDER 9
8. BB FEEDER 9
9. BB FEEDER 9
10. TIE BREAKER ID
TRIP
11
5
4
3
ERROR
COM
POWER
FRONT PANEL
3.4 VAM 10LD
VIOen M/A001
8
COM 2
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
SENSOR INPUTS
X1
1
SENSOR
2
SW1
6
COM 1
10 ACT
9 OK
Addr.
Zone
L/L+I
Latch
L> Int/
Ext
OELLER BACK PANEL
X2
12
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
M
VAM10LD
Figure 3.4: Arc sensor I/O unit VAMP 10LD front and back panels
1. Connection for portable arc sensor (VA 1 DP)
2. Programming switches
3. POWER indicator light, indicates that the supply voltages of each component are in order.
4. COM indicator light, lit when the central unit and I/O units are communicating.
5. ERROR indicator light, indicates an internal fault detected by the component’s self-diagnostics. Such faults include faulty arc sensor or changes in the amount of sensors.
6. Connector sockets for the VX001 modular cables
7. LED lights indicating sensor activation
8. Terminal block for ten arc sensors
14
3.5 VAM 12L
3.5
3 User interface VAM I/O units
9. Portable arc sensor VA 1 DP connected and operational
10. Portable arc sensor activated
11. I/O unit trip relay activated
12. Terminal block for external communication and BI/O channels and trip signal
13. Text pocket for sensor specific labels.
VAM 12L
VAM 12L is primary design for selective feeder trip applications. The unit comprises 3 electromechanical trip normally open contacts and one trip alarm change over contact.
The unit has 10 Arc sensor inputs. Tree sensors (of the ten) inputs are dedicated, and are controlling their own trip relay. The unit is ideal for selective trip of cable compartment in case of an ARC fault.
VAM 12L can selectively handle 3 feeders. The rest of the sensors can then supervise the busbar and breaker compartments and will operate in the zone selected by the unit address switches.
12
VAM 12L
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X2
COM 1
6
COM 2 M
OELLER
1
2
L> ext/int
Latch
L+I / L
Zone
Addr.
5
6
3
4
7
8
OFF
1
2
SW1
ON
SENSOR
OK
9
ACT
10
TRIP
11
3
4
5
POWER
COM
ERROR
1 2 3
7
4
SENSOR INPUTS
5 6 7 8 9 10
X1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
8
VAM12L
Figure 3.5: Arc sensor I/O unit 12L
1. Connection for portable arc sensor (VA 1 DP)
2. Programming switches
3. POWER indicator light, indicates that the supply voltages of each component are in order.
4. COM indicator light, lit when the central unit and I/O units are communicating.
VIOen M/A001 15
VAM I/O units 3 User interface 3.5 VAM 12L
5. ERROR indicator light, indicates an internal fault detected by the component’s self-diagnostics. Such faults include faulty arc sensor or changes in the amount of sensors.
6. Connector sockets for the VX001 modular cables
7. LED lights indicating sensor activation
8. Terminal block for ten arc sensors
9. Portable arc sensor VA 1 DP connected and operational
10. Portable arc sensor activated
11. I/O unit trip relays activated
12. Terminal block for output relay
VIOen M/A001 16
3.6 VAM 12LD
3.6
3 User interface
VAM 12LD
VAM 12LD
Arc Protection I/O-UNIT
M
1 2 3 4
7
SENSOR CHANNELS
5 6 7 8 9 10
13
ADDRESS NR 10
1. BB FEEDER 7
2. CB FEEDER 7
3. CC FEEDER 7
4. BB FEEDER 8
5. CB FEEDER 8
6. CC FEEDER 8
7. BB FEEDER 9
8. BB FEEDER 9
9. BB FEEDER 9
10. TIE BREAKER ID
TRIP
11
5
4
3
ERROR
COM
POWER
FRONT PANEL
VAM I/O units
8
COM 2
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
SENSOR INPUTS
X1
1
SENSOR
2
SW1
6
COM 1
10 ACT
9 OK
Addr.
Zone
L/L+I
Latch
L> Int/
Ext
OELLER BACK PANEL
X2
12
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
M
VAM12LD
Figure 3.6: Arc sensor I/O unit VAM 12LD front and back panels
1. Connection for portable arc sensor (VA 1 DP)
2. Programming switches
3. POWER indicator light, indicates that the supply voltages of each component are in order.
4. COM indicator light, lit when the central unit and I/O units are communicating.
5. ERROR indicator light, indicates an internal fault detected by the component’s self-diagnostics. Such faults include faulty arc sensor or changes in the amount of sensors.
6. Connector sockets for the VX001 modular cables
7. LED lights indicating sensor activation
8. Terminal block for ten arc sensors
VIOen M/A001 17
VAM I/O units 3 User interface 3.6 VAM 12LD
9. Portable arc sensor VA 1 DP connected and operational
10. Portable arc sensor activated
11. I/O unit trip relays activated
12. Terminal block for output relays
13. Text pocket for sensor specific labels.
VIOen M/A001 18
3.7 VAM 4C
3.7
3 User interface VAM I/O units
VAM 4C
12
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
VAM 4C
X2
COM 1
5
COM 2
1
Zone1
Zone2
Zone3
Zone4
Addr.
6
7
4
5
8
2
3
OFF
1
SW1
ON
TRIP
11
6
CURRENT TRANSFORMER
L1 L2 L3
13 x In
4.0
2.0
1.0
0.5
0.1
POWER
COM
ERROR
2
3
4
X1
1 2 3 4 5 6 7 8 9 10 11 12
7
L1/L3 L2/Io
SW2
ON
1 2 3 4
6
3
L1,L3
0.5
5
1.0
L2/Io
0.05
x In
8 9 10
VAM4c
Figure 3.7: Current I/O unit VAM 4C front panel
1. Programming switches
2. POWER indicator light, indicates the supply voltages of each component are in order.
3. COM indicator light, lit when the central units and I/O units are communicating.
4. ERROR indicator light, indicates an internal fault detected by the component’s self-diagnostics. Such faults include faulty current transformer or phase current unbalance.
5. Connector sockets for the VX001 modular cables
6. LED lights indicating that I> stage has started
7. Terminals for three current transformers
8. Current transformer programming switches
9. Overcurrent setting knob (I
L1
, I
L3
), setting range 0.5…6xI
N
10. Overcurrent setting knob (I
L1
, I
0
), setting range 0.05…5xI
N
11. I/O unit trip relay activated
12. Terminal block for external communication and BI/O channels and trip signal
13. Indicator leds for current setting
VIOen M/A001 19
VAM I/O units
3.8
3 User interface
VAM 4CD
VAM 4CD
Arc Protection I/O-UNIT
M
14
FEEDER:
ADDRESS:
F06
33
ZONE: 1 & 2
I> PICK -UP: 2 X In
OTHER : I > EXT ON
1
6
- - - CURRENT TRANSFORMER - - -
2 3
TRIP
11
4
3
2
FRONT PANEL
ERROR
COM
POWER
3.8 VAM 4CD
VIOen M/A001
10 9 8
L2/Io L1/L3 SW2
4.0
2.0
1.0
0.5
0.1
13 x In
COM 2 5 COM 1
12 11 10 9 8 7
7
6 5 4 3 2 1
X1
SW1 1
Addr.
Zone4
Zone3
Zone2
Zone1
OELLER
M
BACK PANEL
12
X2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
VAM 4 CD
Figure 3.8: Current I/O unit VAM 4CD front and back panel
1. Programming switches
2. POWER indicator light, indicates the supply voltages of each component are in order.
3. COM indicator light, lit when the central units and I/O units are communicating.
4. ERROR indicator light, indicates an internal fault detected by the component’s self-diagnostics. Such faults include faulty current transformer or phase current unbalance.
5. Connector sockets for the VX001 modular cables
6. LED lights indicating that I> stage has started
7. Terminals for three current transformers
8. Current transformer programming switches
20
3.8 VAM 4CD 3 User interface VAM I/O units
9. Overcurrent setting knob (I
L1
, I
L3
), setting range 0.5…6xI
N
10. Overcurrent setting knob (I
L1
, I
0
), setting range 0.05…5xI
N
11. I/O unit trip relay activated
12. Terminal block for external communication and BI/O channels and trip signal
13. Indicator leds for current setting
14. Text pocket
21 VIOen M/A001
VAM I/O units
3.9
3 User interface
VAMP 4R
VAMP 4R
Power
Trip 1
Trip 2
12 11 9 8 6 5 4 3 2 1 X2
TRIP 1 TRIP 2
18...265Vac/dc
-
INPUTS
+ +
24Vdc
+
3.9 VAMP 4R
TRIP GROUP 1
NO NC NO
OUTPUT
TRIP GROUP 2
NC NO NC NO NC
SF ALARM
NO
COM
NC
X1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
VAMP 4R frontplate
Figure 3.9: Multiplying relay VAMP 4R
1. POWER LED, indicates that the external operating voltage of
+24 Vdc is connected.
2. Terminals for external operating voltage (+24 Vdc). Can be supplied by central units or I/O units.
3. Terminals for incoming trip signal (e.g. 24 Vdc from VAM I/O unit binary output, 2 groups). Control voltage range is 18 … 265
Vad/dc.
4. Terminals for outgoing trip signals (8 potential-free contacts, 4 normally open, 4 normally closed).
VIOen M/A001 22
4
4.1
4 Programming switches VAM I/O units
Programming switches
Before system implementation, check the positions of the programming switches in accordance with the following basic principles:
• Each I/O unit connected to the communication bus has its own address (each I/O unit have an unique address).
• Set the programming switches before connecting the supply voltage.
• If you have to change the switch positions once the supply voltage has been connected, disconnect the supply voltage to the unit in question for the duration of the programming and re-configure the system.
• If position of the switch is changed, re-install the system again in the central unit.
Switches for arc sensor I/O units
The programming switches of the I/O units are used to determine the unit address and trip relay function.
The system accommodates up to 16 I/O units. Eight addresses are reserved for each protection zone:
• Zone 1 addresses 0…7
• Zone 2 addresses 8…15
• Zone 3 addresses 16…23
• Zone 4 addresses 24…31
The programming switches have different weight factors. To create an address for the I/O unit, turn switches with different values to the
ON position and calculate the sum of their weight factors. The following table shows the weight factors of each programming switch.
Table 4.1: Programming switch weight factors, *) VAM 3L and VAM 3LX, VAM
10L / VAM 10LD, VAM 12L / VAM 12LD only
Switch No.
8
7
6
5
4 *)
Weight factor
1
2
4
8
16
Note the position of the VAM 12LD, VAM 10LD and VAM 4CD dip switches.
VIOen M/A001 23
VAM I/O units 4 Programming switches 4.1 Switches for arc sensor I/O units
VAM 3L / VAM 3LX
VAM 12LD / VAM 10LD
ACT
OK
SENSOR
6
5
4
3
2
1
ON
8
7
SW1
OFF
Addr.
Zone
L / L+I
Latch
L> ext/int
BI/O
Latch
L+I / L
Zone
Addr.
4
5
6
7
8
OFF
1
2
3
SW1
ON
SENSOR
OK
ACT
TRIP
M
VAM 10L / VAM 12L
M
L> ext/int
Latch
L+I / L
OFF
1
2
3
4
Zone
5
6
Addr.
7
8
SW1
ON
SENSOR
OK
ACT
TRIP
VAM3L/VAM3LX, VAM10L/VAM10LD, VAM12L/VAM12LD dips
Figure 4.1: Programming switches for VAM 3L, VAM 3LX, VAM 10L, VAM 10LD, VAM
12L and VAM 12LD
VAM 3L / VAM 3LX, VAM 10L / VAM 10LD
Switch 1 determines which light activation activates the arc stage.
When the switch position is ON, the arc stage only activates on the light information provided by the unit's own sensors. In OFF position the arc stage activates on the light information received from any unit in the same protection zone.
Switch 2 determines the trip relay latch. When the switch is in ON position the trip relay remains engaged after the arc trip until the fault is acknowledged at the central unit’s panel. In the OFF position the trip relay follows the arc fault.
Switch 3 determines the arc trip criteria. When the switch is in ON position the trip is based on light information only; in OFF position both fault currents exceeding the current limit and light information are required.
VIOen M/A001 24
4.2 Switches for current I/O units 4 Programming switches
4.2
VAM I/O units
VAM 12L / VAM 12LD
When the L>ext/int DIP switch is in “L>int” position, the output relays are only activated by dedicated sensors.
SENSOR 1 activates T1.
SENSOR 2 activates T2.
SENSOR 3 activates T3.
SENSORS 4 to 10 are normally sending light information to system according to zone setting.
If the switch is in “L>ext” position, all output relays are also controlled by the selected zone information. This activation source can be any sensor channel 4 to 10 or from an external I/O unit configured to the same zone.
Switches for current I/O units
The address range for current I/O units is (32),33…46. Do not use address 32, because in this case the current I/O unit operates in
CENTRAL UNIT mode and the actual central unit must be set to
SUB-UNIT mode. To determine the address of a current I/O unit, add the sum of the weight factors to 32 (for example, programming switch values total 7, address of the current I/O unit 32 + 7 = 39).
Do not use 32 as the unit address if system have central unit.
Other programming switches have different functions in different units, as described below.
VAM 4C / VAM 4CD
VAM 4C
Zone1
Zone2
Zone3
Zone4
Addr.
7
8
5
6
3
4
OFF
1
2
SW1
ON
TRIP
11 12
SW2
ON
1 2 3 4
6
3
L1,L3
0.5
5
1.0
L2/Io
0.05
x In
VAM4C_dips
VAM 4CD
2
1
6
5
4
3
ON
8
7
SW1
OFF
Addr.
Zone4
Zone3
Zone2
Zone1
11 12
SW2
ON
1 2 3 4
6
3
M
0.5
5
1.0
L2/Io
0.05
x In
VAM4CD_dips
Figure 4.2: Programming switches of VAM 4C / VAM 4CD
25 VIOen M/A001
VAM I/O units 4 Programming switches 4.2 Switches for current I/O units
Table 4.2: VAM4C dipswitches weight factors
SW NO:
8
7
6
5
7
8
4
5
6
2
3
Switch
1
SW1 switch settings
Definition
Zone 1
Zone 2
Zone 3
Zone 4
Addr
Addr
Addr
Addr
Weight factor
1
2
4
8
Description
System operating zone 1 (light information)
System operating zone 2 (light information)
System operating zone 3 (light information)
System operating zone 4 (light information)
Address weighting coefficient 8
Address weighting coefficient 4
Address weighting coefficient 2
Address weighting coefficient 1
VIOen M/A001 26
4.2 Switches for current I/O units 4 Programming switches
SW2 switch settings
Switch
1
Definition
Latch
2
3
4
1A / 5A *
I> out
I> in
VAM I/O units
Description
Position ”0” (switch down): trip relay is only operational while the protection is activated
Position ”1” (switch up): trip relay changes to latching status after trip
Position ”0” (switch down): rated secondary current of the current transformer is 1 A
Position ”1” (switch up): rated secondary current of the current transformer is 5 A
Position ”0” (switch down): unit does not transmit the current criteria to other units
Position ”1” (switch up): unit transmits the current criteria to other units
Position ”0” (switch down): unit does not receive the current criteria from other units
Position ”1” (switch up): unit receives the current criteria from other units
*) As in CT
27 VIOen M/A001
VAM I/O units
5
5 Adjusting the overcurrent setting
Adjusting the overcurrent setting
The principles for changing the current setting in VAM 4C units are the same as for the central unit. You can see the estimated current setting from the led bar on the right side of the unit.
The most accurate way of setting the current limit for the unit is as follows:
• Turn the potentiometer to the maximum value.
• Feed a test current corresponding to the required setting using a testing device.
• Lower the setting until the current activation indicator led of the
I/O unit and the I>ext indicator led in the central unit are lit.
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
VAM 4C
Zone1
Zone2
Zone3
Zone4
Addr.
SW1
TRIP
COM 1 x In
4.0
2.0
1.0
0.5
0.1
CURRENT TRANSFORMER
L1 L2 L3
X2
COM 2
POWER
COM
ERROR
L1/L3 L2/Io X1
VAM4c conn
Figure 5.1: Adjusting the current setting in VAM 4C
VIOen M/A001 28
6
6 BI/BO connection VAM I/O units
BI/BO connection
Each I/O unit also has a BI/O bus. The light I/O units (VAM 3L / VAM
3LX, VAM 10L / VAM 10LD, VAM 12L / VAM 12LD) can transmit trip signal to the central unit or current I/O unit. The current I/O unit (VAM
4C / VAM 4CD) can receive the light information and send the current information either to other I/O units or the multiplying relay.
The DI/DO on the VAM units are fast BI/BO signals.
The following DI and DO connections are included in the standard delivery of VAM 3L / VAM 3LX and VAM 10L units:
Zone shift 1(2, 2(1, 3(4, 4(3 DI
GND
Trip out
GND
X2-8
X2-7
X2-10
X2-9
Trip signal, 24 V dc
Trip signal earth
The following DI and DO connections are included in the standard delivery of VAM 4C units:
L>in
GND
Trip out
GND
X2-8
X2-7
X2-10
GND
Light input, 24-48 V dc
Light input earth
Trip signal
Trip signal earth
29 VIOen M/A001
VAM I/O units
7
7.1
VIOen M/A001
7 Connection examples
Connection examples
VAM 3L / VAM 3LX interfaces
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
VAM 3L / 3LX
COM 1
X2
COM 2
BI/O
Latch
L+I / L
Zone
Addr.
SW1
SENSOR
OK
ACT
TRIP
CH1
SENSOR INPUTS
CH2 CH3
POWER
COM
ERROR
X2-9:
X2-10:
X2-11:
X2-12:
X2-13:
X2-14:
X2-15:
X2-16:
X1-R1:
X1-T1:
X1-R2:
X1-T2:
X1-R3:
X1-T3:
X2-1:
X2-2:
X2-3:
X2-4:
X2-5:
X2-6:
X2-7:
X2-8
R1 T1 R2 T2 R3 T3
VAM3L/VAM 3LX conn
Fiber receiver connection
Fiber transmitter connection
Fiber receiver connection
Fiber transmitter connection
Fiber receiver connection
Fiber transmitter connection
Channel 1
Channel 2
Channel 3
+24V supply from master unit or external power supply
GND
CAN-L
CAN-H
Serial B
Serial A
DI GND
DI (24-48Vdc)
DO GND
DO +24Vdc
+ Temp sensor
- Temp sensor
Zone information
(L>, I>) master slave com
Zone change
(1 -> 2; 2 -> 1;
3 -> 4; 4 -> 3)
Trip signal
(DI&DO)
Not in use
= COM1, COM2
Trip relay (NO)
Trip relay (NO)
30
7.2 VAM 10L interfaces
7.2
7 Connection examples
VAM 10L interfaces
VAM 10L
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
M
OELLER
COM 1
X2
COM 2
L> ext/int
Latch
L+I / L
Zone
Addr.
SW1
SENSOR
OK
ACT
TRIP
1 2 3 4
SENSOR INPUTS
5 6 7 8 9 10
POWER
COM
ERROR
X1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
X2-2:
X2-3:
X2-4:
X2-5:
X2-6:
X2-7:
X2-8:
X2-9:
X2-10:
X2-11:
X2-12:
X2-13:
X2-14:
X2-15:
X2-16:
X1-1,2:
X1-3,4:
X1-5,6:
X1-7,8:
X1-9,10:
X1-11,12:
X1-13,14:
X1-15,16:
X1-17,18:
X1-19,20:
X2-1:
VAM10L conn arc sensor channel 1 arc sensor channel 2 arc sensor channel 3 arc sensor channel 4 arc sensor channel 5 arc sensor channel 6 arc sensor channel 7 arc sensor channel 8 arc sensor channel 9 arc sensor channel 10
+24V supply from masterunit or external power supply
GND
CAN-L
CAN-H
Serial B
Serial A
DI GND
DI (24-48Vdc)
Zone information
(L>, I>)
Master slave com
Zone change
(1 -> 2; 2 ->1;
3 -> 4; 4 -> 3)
DO GND
DO +24Vdc
+ Temp sensor
- Temp sensor
Trip signal
Not in use
=COM1, COM2
Trip relay (NO)
Trip relay (NO)
VIOen M/A001 31
VAM I/O units
VAM I/O units
7.3
VIOen M/A001
7 Connection examples
VAM 10LD interfaces
7.3 VAM 10LD interfaces
COM 2
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
SENSOR INPUTS
COM 1
X1
ACT
OK
SENSOR
SW1
Addr.
Zone
L/L+I
Latch
L> Int/
Ext
OELLER
M
X2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
X2-2:
X2-3:
X2-4:
X2-5:
X2-6:
X2-7:
X2-8:
X2-9:
X2-10:
X2-11:
X2-12:
X2-13:
X2-14:
X2-15:
X2-16:
X1-1,2:
X1-3,4:
X1-5,6:
X1-7,8:
X1-9,10:
X1-11,12:
X1-13,14:
X1-15,16:
X1-17,18:
X1-19,20:
X2-1:
VAM10LD conn arc sensor channel 1 arc sensor channel 2 arc sensor channel 3 arc sensor channel 4 arc sensor channel 5 arc sensor channel 6 arc sensor channel 7 arc sensor channel 8 arc sensor channel 9 arc sensor channel 10
+24V supply from masterunit or external power supply
GND
CAN-L
CAN-H
Serial B
Serial A
DI GND
DI (24-48Vdc)
Zone information
(L>, I>)
Master slave com
Zone change
(1 -> 2; 2 ->1;
3 -> 4; 4 -> 3)
DO GND
DO +24Vdc
+ Temp sensor
- Temp sensor
Trip signal
Not in use
=COM1, COM2
Trip relay (NO)
Trip relay (NO)
32
7.4 VAM 12L interfaces
7.4
7 Connection examples
VAM 12L interfaces
VAM 12L
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
COM 1
X2
M
OELLER
COM 2
L> ext/int
Latch
L+I / L
Zone
Addr.
6
7
4
5
2
3
OFF
1
8
SW1
ON
SENSOR
OK
ACT
TRIP
1 2 3 4
SENSOR INPUTS
5 6 7 8 9 10
POWER
COM
ERROR
X1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
VAM I/O units
VAM12L conn
X2-2:
X2-3:
X2-4:
X2-5:
X2-6:
X2-7:
X2-8:
X2-9:
X2-10:
X2-11:
X2-12:
X2-13:
X2-14:
X2-15:
X2-16:
X1-1,2:
X1-3,4:
X1-5,6:
X1-7,8:
X1-9,10:
X1-11,12:
X1-13,14:
X1-15,16:
X1-17,18:
X1-19,20:
X2-1: arc sensor channel 1 arc sensor channel 2 arc sensor channel 3 arc sensor channel 4 arc sensor channel 5 arc sensor channel 6 arc sensor channel 7 arc sensor channel 8 arc sensor channel 9 arc sensor channel 10
+24v supply from masterunit or external power supply
GND
COM
NO
NC
Trip relay 3 (NO)
Trip relay 3 (NO)
Trip relay 2 (NO)
Trip relay 2 (NO)
Trip relay 1 (NO)
Trip relay 1 (NO)
Alarm
VIOen M/A001 33
VAM I/O units
7.5
VIOen M/A001
7 Connection examples
VAM 12LD
COM 2
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
SENSOR INPUTS
COM 1
X1
ACT
OK
SENSOR
SW1
Addr.
Zone
L/L+I
Latch
L> Int/
Ext
OELLER
M
X2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
VAM12LD conn
X2-2:
X2-3:
X2-4:
X2-5:
X2-6:
X2-7:
X2-8:
X2-9:
X2-10:
X2-11:
X2-12:
X2-13:
X2-14:
X2-15:
X2-16:
X1-1,2:
X1-3,4:
X1-5,6:
X1-7,8:
X1-9,10:
X1-11,12:
X1-13,14:
X1-15,16:
X1-17,18:
X1-19,20:
X2-1: arc sensor channel 1 arc sensor channel 2 arc sensor channel 3 arc sensor channel 4 arc sensor channel 5 arc sensor channel 6 arc sensor channel 7 arc sensor channel 8 arc sensor channel 9 arc sensor channel 10
+24v supply from masterunit or external power supply
GND
COM
NO
NC
Trip relay 3 (NO)
Trip relay 3 (NO)
Trip relay 2 (NO)
Trip relay 2 (NO)
Trip relay 1 (NO)
Trip relay 1 (NO)
Alarm
7.5 VAM 12LD
34
7.6 VAM 4C interfaces
7.6
7 Connection examples
VAM 4C interfaces
VAM I/O units
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
VAM 4C
Zone1
Zone2
Zone3
Zone4
Addr.
SW1
TRIP
COM 1 x In
4.0
2.0
1.0
0.5
0.1
CURRENT TRANSFORMER
L1 L2 L3
X2
COM 2
POWER
COM
ERROR
X1
X1-1,3:
X1-5,7:
X1-9,11.
X2-1:
X2-2:
X2-3:
X2-4:
X2-5:
X2-6:
X2-7:
X2-8:
X2-9:
X2-10:
X2-11:
X2-12:
X2-13:
X2-14:
X2-15:
X2-16:
Trip relay (NO)
Trip relay (NO)
L1/L3 L2/Io
VAM4c conn
Current input IL1
Current input IL2 / Io
Current input IL3
+24V supply from master unit or external power supply
GND
CAN-L
Zone information
(L>, I>)
CAN-H
Serial B master slave com
Serial A
DI GND
L>
DI (24-48Vdc)
DO GND
TRIP
DO +24Vdc
= COM1, COM2
35 VIOen M/A001
VAM I/O units
7.7
7 Connection examples
VAM 4CD interfaces
7.7 VAM 4CD interfaces
L2/Io L1/L3 SW2
COM 2
4.0
2.0
1.0
0.5
0.1
x In
COM 1
12 11 10 9 8 7 6 5 4 3 2 1
X1
OELLER
SW1
Addr.
Zone4
Zone3
Zone2
Zone1
M
X2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
VAM4CD conn
X1-1,3:
X1-5,7:
X1-9,11.
X2-1:
X2-10:
X2-11:
X2-12:
X2-13:
X2-14:
X2-15:
X2-16:
X2-2:
X2-3:
X2-4:
X2-5:
X2-6:
X2-7:
X2-8:
X2-9:
Current input IL1
Current input IL2 / Io
Current input IL3
+24V supply from master unit or external power supply
GND
CAN-L
Zone information
(L>, I>)
CAN-H
Serial B master slave com
Serial A
DI GND
L>
DI (24-48Vdc)
DO GND
TRIP
DO +24Vdc
= COM1, COM2
Trip relay (NO)
Trip relay (NO)
VIOen M/A001 36
7.8 Multiplying relay VAMP 4R
7.8
7 Connection examples
Multiplying relay VAMP 4R
VAMP 4R
Power
Trip 1
Trip 2
12 11 9 8 6 5 4 3 2 1 X2
TRIP 1 TRIP 2
18...265Vac/dc
-
INPUTS
+ +
24Vdc
+
TRIP GROUP 1
NO NC NO
OUTPUT
TRIP GROUP 2
NC NO NC NO NC
SF ALARM
NO
COM
NC
X1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
VAMP 4R frontplate
X1-1,2:
X1-3,4:
X1-5,6:
X1-7,8:
X1-9,10:
X1-11,12:
X1-13,14:
X1-15,16:
X1-17:
X1-18:
X1-19:
X1-20:
X2-1:
X2-2:
X2-3:
X2-4:
X2-5:
X2-6:
X2-7:
X2-8:
X2-9:
X2-10:
X2-11:
X2-12:
Trip relay (NO), Trip group 1.
Trip relay (NC), Trip group 1.
Trip relay (NO), Trip group 1.
Trip relay (NC), Trip group 1.
Trip relay (NO), Trip group 2.
Trip relay (NC), Trip group 2.
Trip relay (NO), Trip group 2.
Trip relay (NC), Trip group 2.
NO
COM
NC
Aux voltage supply +24Vdc
GND
Aux voltage supply +24Vdc
GND
Aux voltage supply +24Vdc
GND
TRIP 2. Input 18...265Vac/dc
TRIP 2. Input 18...265Vac/dc
TRIP 1. Input 18...265Vac/dc
TRIP 1. Input 18...265Vac/dc
SF Alarm relay
Trip group 2.
Trip group 1.
VAM I/O units
VIOen M/A001 37
VAM I/O units
8
8.1
VIOen M/A001
8 Technical data
Technical data
Connections
VAM 3L
Sensor connections 3 fibre loop sensors (type ARC-SLx)
1 portable arc sensor (type VA 1 DP)
VAM 3LX
Sensor connections 3 fibre loop sensors (type ARC-SLx)
- sensitivity adjust range compared to 3L
0,5 (max) … 1,5 (min)
1 portable arc sensor (type VA 1 DP)
VAM 10L, VAM 10LD, VAM 12L, VAM 12LD
Sensor connections
Terminal:
- Phoenix MVSTBW or similar
10 arc sensors (type VA 1 DA or
VA 1 EH)
1 portable arc sensor (type VA 1 DP)
Maximum cross-section area of wire
2.5 mm 2 (13-14 AWG)
VAM 4C, VAM 4CD
Rated current L1 / L3
- current measuring zone
- thermal withstand capability
- power consumption
Rated current L2 / I
0
- current measuring zone
- thermal withstand capability
- power consumption
Terminal:
- single or multi-strand wire
1 or 5 A (optional) 50/60Hz
0 … 6 A (0 … 6*I
N
[I
N
=1A]);
0 … 30 A (0 … 6* I
N
[I
N
=5A])
300 A (for 1s)
100 A (for 10s)
20 A (continuous)
<0.3 VA
1 or 5 A (optional) 50/60Hz
0 … 6 A (0 … 6*I
N
[I
N
=1A]);
0 … 30 A (0 … 6* I
N
[I
N
=5A])
300 A (for 1s)
100 A (for 10s)
20 A (continuous)
<0.3 VA
Maximum cross-section area of wire
4 mm 2 (10-12 AWG)
38
8.1 Connections
8.1.1
8.1.2
39
8 Technical data VAM I/O units
Auxiliary power supply
VAM 3L, VAM 3LX, VAM 10L, VAM 10LD, VAM 12L, VAM 12LD,
VAM 4C, VAM 4CD
Rated voltage U
AUX
Power consumption
Terminal:
- Phoenix MVSTBW or similar
( RJ 45 when supply from central unit)
24 V dc
< 1 W (in normal mode)
< 1.5 W (output relays activated)
Maximum cross-section area of wire
2.5 mm 2 (13-14 AWG)
VAR 4CE
Rated voltage U
AUX
Power consumption
Terminal:
- fixed terminal
24 V dc
< 0.5 W (in normal mode)
< 4.5 W (output relays activated)
Maximum cross-section area of wire
2.5 mm 2 (13-14 AWG)
VAMP 4R
Rated voltage U
AUX
Current consumption
- one relay group activated
- both relay groups activated
VA 1 DA, VA 1 EH, VA 1 DP
Rated voltage U
AUX
Power consumption
24 V dc
20 mA stby
80 mA
180 mA
12 V dc (from I/O unit)
< 35 mW (in normal mode)
< 450 mW (activated)
Digital inputs (BI/O bus)
No digital inputs available in VAM 12L and VAM 12LD
VAM 3L, VAM 3LX, VAM 10L, VAM 10LD
Number of inputs
Internal operating voltage
Load capacity (max.)
Terminal:
- Phoenix MVSTBW or similar
1 pcs I> in
1 arc fault trip out
24…48 V dc (BIO in)
24 V dc (BIO out)
5 mA
Maximum cross-section area of wire
2.5 mm 2 (13-14 AWG)
VIOen M/A001
VAM I/O units
8.1.3
8 Technical data 8.1 Connections
VAM 4C
Number of inputs
Internal operating voltage
Load capacity (max.)
Terminal:
- Phoenix MVSTBW or similar
VAMP 4R
Operating voltage
Current consumption
1 pcs L> in
1 pcs I> out
24…48 V dc (BIO in)
24 V dc (BIO out)
5 mA
Maximum cross-section area of wire
2.5 mm 2 (13-14 AWG)
18…265 V ac/dc
2 mA
Trip contacts
VAM 3L, VAM 3LX, VAM 10L, VAM 10LD, VAM 12L, VAM 12LD,
VAM 4C, VAM 4CD
1 closing contact (relay T1) Number of contacts for VAM 10L, VAM 10LD, VAM 3L, VAM
3LX, VAM 4C, VAM 4CD
Number of contacts for VAM 12L, VAM 12LD
Rated voltage
Continuous withstand capacity
Make and carry for 0.5s
Make and carry for 3s
Breaking capacity, dc(L/R=40 ms)
At 48 V dc:
At 110 V dc:
At 220 V dc:
Relay material
Terminal:
- Phoenix MVSTBW or similar
3 closing contacts (relay T1)
250 V ac/dc
5 A
30 A
15 A
1 A
0.44 A
0.22 A
AgNi 90/10
Maximum cross-section area of wire
2.5 mm 2 (13-14 AWG)
VIOen M/A001 40
8.2 Test and environmental conditions
8 Technical data
VAMP 4R
4N/O / 4N/C rated voltage
Continuous withstand capacity
Make and carry for 0.5s
Make and carry for 3s
N/O breaking capacity dc
(L/R=40ms)
At 48 V dc
At 110 V dc
At 220 V dc
Contact material
Terminal:
- Phoenix MVSTBW or similar
250V ac/dc
5A
30A
15A
VAM I/O units
1A
0.44A
0.22A
AgNi 90/10
Maximum cross-section area of wire
2.5 mm 2 (13-14 AWG)
8.2
Test and environmental conditions
8.2.1
Environmental conditions
Operating temperature range
Transport and storage temperature range
- VAM I/O units
- ARC SLm, VA 1 xx sensors
Relative air humidity
Operation altitude
-10 … +55°C
-40 … +70°C
-40 … +85°C
<75% (1 year, average)
<90% (30 days per year, condensation not allowed)
2000 m
8.2.2
Casing
VAM 3L, VAM 3LX, VAM 10L, VAM 4C, VAMP 4R
Housing class (IEC 60529)
Dimensions (WxHxD)
Material
Weight
Colour code
IP21
157x92x25 mm
1mm steel plate
0.52 kg
RAL 7032 (housing) / RAL 70035
(back plate)
VIOen M/A001 41
VAM I/O units
8.2.3
8 Technical data 8.2 Test and environmental conditions
VAM 10LD, VAM 12LD, VAM 4CD
Door mounted (IEC 60529)
Dimensions (WxHxD)
Material
Weight
Colour code
IP64
185x120x25 mm
1mm steel plate
0.60 kg
RAL 7032 (housing) / RAL 70035
(back plate)
VA 1 DA, VA 1 EH, VA 1 DP
Housing class (IEC 60529)
Dimensions (WxHxD)
Material
Weight
Cable length
IP21
25x55x14 mm (VA 1 DA)
Φ11x62 mm (VA 1 EH)
Φ40x7 mm (VA 1 DP)
Plastic
0.01 kg
6 m or 20 m
(VA 1 DP 5 m)
Package
Dimensions (WxHxD)
Weight (unit, box and user instructions)
VAMP 4R: 157 x 92 x 25 mm
VAM 10L: 157 x 92 x 25 mm
VAM 3L: 157 x 92 x 25 mm
VAM 3LX: 157 x 92 x 25 mm
VAM 4C: 157 x 92 x 25 mm
VAMP 4R: 0.62 kg
VAM 10L: 0.62 kg
VAM 3L: 0.62 kg
VAM 3LX: 0.62 kg
VAM 4C: 0.62 kg
VIOen M/A001 42
9
9.1
9.1.1
9 Construction
Construction
Dimensional drawings
VAM 3L / 3LX Din rail mounting
VAM
3L /
3LX
VAM I/O units mm in
92
3.62
112
4.41
VAM
3L /
3LX
157
6.18
25
0.98
T max. 0.5...0.6Nm
4.4...5.3 lb.in
V A M
3 L /
3 L X
EN 50022
VAM
3L /
3LX
35 mm
1.38 in
43 VIOen M/A001
VAM I/O units
9.1.2
9 Construction
VAM 10L Din rail mounting
mm in
9.1 Dimensional drawings
157
6.18
92
3.62
112
4.41
25
0.98
T max. 0.5...0.6Nm
4.4...5.3 lb.in
EN 50022
35 mm
1.38 in
VIOen M/A001 44
9.1 Dimensional drawings
9.1.3
9 Construction
VAM 10LD Flush mounting
mm in
105
4.13
ø4.5
0.18
1.0
0.0
- 3
4-
.0
0.1
2
170
6.69
157
6.18
92
3.62
VAM I/O units
T max. 0.5...0.6Nm
4.4...5.3 lb.in
90
3.54
27.6
1.09
min. 2.5mm
2
120
4.72
185
7.28
45 VIOen M/A001
VAM I/O units
9.1.4
9 Construction
VAM 12L Din rail mounting
mm in
92
3.62
112
4.41
9.1 Dimensional drawings
157
6.18
25
0.98
T max. 0.5...0.6Nm
4.4...5.3 lb.in
EN 50022
35 mm
1.38 in
VIOen M/A001 46
9.1 Dimensional drawings
9.1.5
9 Construction
VAM 12LD Flush mounting
mm in
105
4.13
ø4.5
0.18
1.0
0.0
- 3
4-
.0
0.1
2
170
6.69
157
6.18
MP
121
D
92
3.62
VAM I/O units
T max. 0.5...0.6Nm
4.4...5.3 lb.in
VA
MP
121
D
90
3.54
27.6
1.09
MP
121
D min. 2.5mm
2
120
4.72
185
7.28
47 VIOen M/A001
VAM I/O units
9.1.6
9 Construction
VAM 4C Din rail mounting
9.1 Dimensional drawings mm in
92
3.62
112
4.41
157
6.18
25
0.98
T max. 0.5...0.6Nm
4.4...5.3 lb.in
EN 50022
35 mm
1.38 in
VIOen M/A001 48
9.1 Dimensional drawings
9.1.7
9 Construction VAM I/O units
VAM 4CD Flush mounting
mm in
2
105
4.13
ø4.5
0.18
1.0
0.0
- 3
4-
.0
0.1
2
170
6.69
157
6.18
T max. 0.5...0.6Nm
4.4...5.3 lb.in
1
92
3.62
D I P
O N
1
2
3 4
VAM
4C otec
Arc Pr tion
D
I/O
-UNIT
---CURRENT
TRANSFORMER---
L3
L2
L1
TRIP
ERRO
R
CO
M
PO
WER
3
O N
D I
1
2
P
3
4
VAM
4C
Arc Pr otec tion
D
I/O
-UNIT
---CURRENT
TRANSFORMER---
L3
L2
L1
TRIP
ER
RO
R
CO
M
PO
WER min. 2.5mm
2
90
3.54
27.6
1.09
O N
D I P
2 3
1
4
VAM
D
Arc Pr otec tion
I/O
-UNIT
---CURRENT
TRANSFORMER---
L3
L2
L1
TRIP
ERRO
R
CO
M
PO
WER
120
4.72
185
7.28
49 VIOen M/A001
VAM I/O units
9.1.8
9 Construction
VAMP 4R Din rail mounting
mm in
92
3.62
112
4.41
9.1 Dimensional drawings
157
6.18
25
0.98
T max. 0.5...0.6Nm
4.4...5.3 lb.in
EN 50022
35 mm
1.38 in
VIOen M/A001 50
9.1 Dimensional drawings
9.1.9
9 Construction
VA 1 DA
mm in
22.2
0.83
14
0.55
9.1.10
VA 1 EH
mm in
VAM I/O units
20
0.79
62
2.44
25
0.98
4.2
0.17
VA1DA_mittakuva
8
0.31
VA1EH_mittakuva
51 VIOen M/A001
VAM I/O units
9.1.11
9 Construction
VYX 001
mm in
15
0.59
50
1.97
0.3
10
9
0
.1
2
.5
50
1.97
15
0.59
9.1 Dimensional drawings
25
0.98
51
2.0
VYX001_mittakuva
VIOen M/A001 52
9.1 Dimensional drawings
9.1.12
9 Construction
VYX 002
mm in 1
0
0
.3
9
15
0.59
30
1.18
0
.1
2
3
15
0.59
VAM I/O units
30
1.18
VYX002
53 VIOen M/A001
VAM I/O units
9.2
9.2.1
9.2.2
VIOen M/A001
9 Construction 9.2 I/O unit mounting and wiring
I/O unit mounting and wiring
Read this User's Manual carefully before undertaking any installation or wiring work.
Safety instructions
Always observe the national electrical safety regulations when working under live conditions. The unit manufacturer is not liable for damage due to incorrect working methods or failure to observe safety instructions.
The correct handling of the unit under all mounting and operating conditions forms the foundation for its safe use.
Any separately marked notes and warnings must be observed.
The wiring work must be performed according to national standards and any requirements specified by the customer.
Do not connect the auxiliary supply voltage until the installation has been completed.
Before installation
Before installation, make sure the environmental conditions comply with the requirements specified in Chapter 7.
The unit contains components liable to damage if exposed to an electrostatic discharge (ESD).
Do not open the unit unless you have taken appropriate protective measures against ESD.
The manufacturer cannot guarantee operational safety in environments that do not satisfy the specified environmental conditions.
VAM 3L, VAMP 3LX, VAM 10L, VAM 12L, VAM
4C
The units are designed for mounting on a DIN rail. Mount the units on the rail in such a way that the indicator lights on the front panel are visible and the sensor wiring can be made as easily as possible.
VAM 10LD, VAM 12LD, VAM 4CD
The units are designed for mounting on a door. Hence all indicators are clearly visible in normal operation.
54
9.3 Wiring of the I/O units
9.3
9.4
9.5
55
9 Construction VAM I/O units
Wiring of the I/O units
The I/O units can be connected to the following:
• secondary circuits of the current transformers of the switchgear
(VAM 4C only)
• the trip circuits of the circuit breakers
• external auxiliary supply circuits
• connections to the central unit or other I/O units (data communication and auxiliary supply)
• connections to other central units or protection relays (DI or DO bus)
Wiring the secondary circuits of the current transformers (VAM 4C / VAM
4CD only)
Connect the secondary circuits of the current transformers to the following screw connectors:
• X1-1, X1-3 (L1)
• X1-5, X1-7 (L2/I0)
• X1-9, X1-11 (L3)
The arc protection system can also be single or two-phase connected.
Three-phase connection is nevertheless recommended for optimal operating speed.
The current measuring channels L1 and L3 must be used in connection with two-phase current measuring. Single-phase current or earth-fault current must always be connected to the current measuring channel L2/I0; otherwise, an unbalance error will occur.
The specified operating time of 7ms can only be guaranteed for three-phase current measurement.
Wiring the trip circuits of the circuit breakers
Connect the circuit breaker’s trip circuit to the following terminals:
TRIP1: X2-15, X2-16 (fast)
In the event of an arc fault, the output contact will close at 7 ms when three-phase current measurement is used.
VIOen M/A001
VAM I/O units
9.6
9.7
9 Construction 9.6 Wiring between the central unit and the I/O unit
The output trip relay of the light I/O units (VAM 10L and VAM 3 L) operates during faults in its own zone. In the current I/O unit (VAM
4 C), select the protection zone controlling the I/O unit using the programming switches.
If several trips are required, the multiplying relay VAMP 4R can be used.
Wiring between the central unit and the
I/O unit
Connect the central unit to the I/O units with a modular cable of type
VX001. The modular cable carries all information between the central unit and I/O units, including data in serial form, arc fault messages and operating supply to the I/O units.
• Connect the VX001 cable to the arc I/O COM interface of the central units.
• Connect the cable to COM1 or COM2 on the first I/O unit.
• Route the cable from COM1 or COM2 on the first I/O unit to
COM1 or COM2 in the next unit, etc.
All the COM1 and COM2 interfaces are identical, i.e. the cable can always be connected to either interface. The maximum total length of the modular cable, taking into account all the I/O units connected to the central unit, is 100 m.
Use only star connection for I/O units. Closed loop will cause communication errors.
Wiring separate auxiliary supplies
When routing modular cables over long distances or when the system contains several I/O units, you should preferably use a separate auxiliary supply parallel with the modular cable.
Connect the auxiliary supply to the 24 V terminals of the central unit to the 24 V terminals in the I/O units. Alternatively, you can also use a separate external voltage supply 3P004.
Pay particular attention to the polarity of the cable connections.
VIOen M/A001 56
9.8 VAMP 4R
9.8
9 Construction
VAMP 4R
18...265 V ac/dc
12 11 9 8
+ 24 Vdc
+ + +
6 5 4 3 2 1 :X2
VAMP 4R
Group 1 Group 2
Self supervision alarm
VAM I/O units
X1: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 19 20 18
VAMP4R Block diagram
Figure 9.1: VAMP 4R block diagram
The multiplying relay VAMP 4R can be used when additional trip outputs are needed.
VAMP 4R comprises 4 N/O contacts and 4 N/C contacts. They are divided into two separate groups which can be independently controlled by e.g. the binary output of the I/O units or the central unit.
• Attach the VAMP 4R unit to a DIN rail.
• Connect the auxiliary voltage ( +24V ) to terminal X2-1 (+) and
X2-2 (-). Terminals X2-3 and X2-5 are parallel inputs to X2-1(+).
Terminals X2-4 and X2-6 are parallel inputs to X2-2(1). The auxiliary voltage ( +24V ) can be supplied from the central unit or nearest slave ( X2-1 (+), X2-2 (-)).
• Connect the required signal (18-265 V ad/dc) to the trip control inputs.
• Input “TRIP 1” ( X2-11, X2-12 ) is controlling the trip group 1.
Input “TRIP 2” ( X2-8, X2-9 ) is controlling the trip group 2.
• There are 2xN/C + 2xN/O contacts per trip group.
If necessary, input TRIP 1 and 2 can be connected in parallel. Then all trip relays will operate simultaneously.
57 VIOen M/A001
VAM I/O units
9.9
9 Construction 9.9 Wiring multiple central units
Wiring multiple central units
A maximum of three central units can be connected to one communication bus. In this case, the units can operate on a maximum of four protection zones (depending on their programming switches).
The light and current signals given by the I/O units, including address information, are transferred to each central unit.
If more than one central unit is to be connected to the same communication bus, one central unit must be in central unit mode and the other central units in sub-unit mode.
In applications with multiple central units the central units can be interconnected also via BI/O connections (binary input/output). In this case, each part of the system can control four protection zones per system communication bus. In this case, arc and overcurrent information is transferred between the central units without address information.
When configurating arc protection system with multiple central units, disconnect I/O-units from central units in slave mode during their installation procedure.
VIOen M/A001 58
9.10 Arc sensors
9.10
9 Construction VAM I/O units
Arc sensors
Mount the sensors on the switchgear in such a way that they cover the protection zone as completely as possible. The line of sight must be free between the sensor and the supervised area.
If point sensors are used in open compartments (such as bus-bar sections), there should be a sensor approximately every 5 meters.
Due to the wide detection range of the sensors and the light reflection inside the switchgear, the mounting position is not critical.
Connecting sensors VA 1 DA and VA 1 EH to the I/O units
The sensors are delivered with 6-metre standard cables or 20-metre shielded cables (to be specified in the order).
After mounting the sensors, connect them to the I/O units as follows:
• Draw the wire to the nearest I/O unit using the shortest route possible and cut it to a suitable length.
• Connect the arc sensors to the screw terminals X1-1…20. The polarity of the arc sensor cables is not critical.
Connecting the ARC-SLx sensors to the I/O units
The sensors are delivered in standard lengths (to be specified in the order) equipped with terminals compatible with VAM 3L units.
After mounting the sensors, connect them to the I/O units as follows:
• Draw each end of the sensor to the I/O unit and carefully form a loop of the extra fibre.
Do not shorten the extra sensor fibre unless you have appropriate terminal connectors.
• Connect the arc sensors to plug-in terminals X1-R1, T1…R3,
T3. While the polarity of the arc sensors is not critical, you must connect each end of the fibre to the same channels.
59 VIOen M/A001
VAM I/O units 9 Construction 9.10 Arc sensors
VA 1 DA
You can be install the arc sensor onto the switchgear wall from the outside. Press the active part of the sensor through the 10-mm hole in the wall and fix it using a 4-mm screw.
VIOen M/A001
VA1DA_asennus
Figure 9.2: Mounting the arc sensor VA 1 DA
1. Active part of the sensor
2. Cable clamp
3. Fastening screw 4x15 mm
4. Cable of sensor
You can also surface mount the sensor to the wall using the mounting plates VYX01 or VYX02, available as additional parts.
The sensor must not be exposed to direct sunlight or other strong light. Do not mount the sensor directly under a light source.
60
9.10 Arc sensors 9 Construction VAM I/O units
Figure 9.3: Arc sensor VA 1 DA
Figure 9.4: Sensitivity of the arc sensor VA
1 DA
VA 1 EH
You can be install the arc sensor onto the switchgear wall from the outside. Press the active part of the sensor through the 10.5-mm hole in the wall.
You can also surface mount the sensor. To do this, push the sensor into a plastic mounting tube and fix it with heat shrink tubing.
The sensor must not be exposed to direct sunlight or other strong light. Do not mount the sensor directly under a light source.
61
Figure 9.5: Arc sensor VA 1 EH
ARC-SLx
ARC-SLx is an fibre sensor that can be mounted on the switchgear to monitor several compartments simultaneously (various bus-bar compartmets, etc.).
The fibre must not touch any live parts of the switchgear or other hot components, since too high temperatures may destroy the fibre.
VIOen M/A001
VAM I/O units 9 Construction 9.10 Arc sensors
When mounting the sensor on the switchgear, ensure that the bending radius is long enough (min. 80 mm) and that it is safe from the sharp edges of the switchgear.
The sensor must not be exposed to direct sunlight or other strong light. Do not mount the sensor directly under a light source.
To avoid false tripping, cover any unused channels of the I/O unit.
Figure 9.6: ARC-SLx
VA 1 DP
The portable pin sensor can be temporarily connected to the I/O units. It is used to improve safety when working with live switchgear, for example, Attach the sensor close to the working area, for example in the breast pocket of the maintenance man.
A pin sensor operates in the same way as a fixed arc sensor. The only difference is free mobility within the limits of the connecting cable.
VIOen M/A001
Figure 9.7: Pin sensor VA 1 DP
To avoid faulty tripping, disconnect the pin sensor from the system immediately after use.
62
10
10 Order information VAM I/O units
Order information
Order code
VAM 3LSE
VAM3LXSE
VAM4CSE
VAM4CDSE
VAM10LSE
VAM10LDSE
VAM12LSE
VAM12LDSE
VAMP4RSE
VA 1 DA-6
VA 1 DA-20
VA 1 DT-6
VA 1 DP-5
VA 1 DP-5D
VA 1 EH-6
VA 1 EH-20
ARC SLm-x
VX001-xx
VX031-5
VX052-3
VX054-3
VYX001
VYX002
VSE001PP
VSE002
VPA3CG
Explanation Note
Fiber sensor I/O unit (VAMP221) 3 fiber loops, 1 trip relay
Fiber sensor I/O unit (VAMP221) 3 fiber loops, 1 trip relay, adjustable sensitivity
Current I/O unit (VAMP221)
Current I/O unit (VAMP221)
3 current inputs, 1 trip relay
3 current inputs, 1 trip relay, flush mounting
Point sensor I/O unit (VAMP221) 10 sensor inputs, 1 trip relay
Point sensor I/O unit (VAMP221) 10 sensor inputs, 1 trip relay, flush mounting
Point sensor I/O unit (VAMP221) 10 sensor inputs, 3 trip relays
Point sensor I/O unit (VAMP221) 10 sensor inputs, 3 trip relays, flush mounting
Trip multiplier relay
Arc Sensor
4 x NO, 4 x NC, 2 groups
Cable length 6m
Arc Sensor
Temperature sensor
Portable arc sensor
Portable arc sensor
Cable length 20m
Cable length 6m
Cable length 5m
Cable length 5m
Arc sensor (pipe type)
Arc sensor (pipe type)
Fiber sensor, 8000 lx
Cable length 6m
Cable length 20m x= fiber length (2
Modular cable VAM <-> VAM
(xx= cable length [m]
Extension cable for VA1 DP-5D
USB programming cable
(VAMPSET)
Interface cable to VPA 3CG
(Profibus module) for RS-232
Surface mounting plate for sensors
Surface mounting plate for sensors
Fiber optic interface module
(plastic - plastic)
RS485 interface module
Profibus interface module
Preferred cable lengths (3
Cable length 5m
Cable length 3m
Cable length 3m
Z-shaped
L-shaped
RS-232 mode only
RS-232 mode only
Note 2: Fiber lengths 1 , 5, 10, 15, 20, 25, 30, 35, 40, 50 or 70 m
Note 3: Cable lengths 1, 3, 5, 7, 10, 15, 20, 25 & 30 m
VIOen M/A001 63
VAM I/O units
11
11 Glossary
Glossary
Term
BI
BO
Document file
FPGA
HMI
IED
LCD
LED
Local HMI
PC
VAMPSET
Description
Binary input
Binary output
Stores information about the IED settings, events and fault logs.
Field-programmable gate array
Human-machine interface
Intelligent electronic device
Liquid crystal display
Light-emitting diode
IED front panel with display and push-buttons
Personal computer
Configuration tool for VAMP protection devices
VIOen M/A001 64
We reserve the right to changes without prior notice
VAMP Ltd.
Street address:
Post address:
Yrittäjänkatu 15
P.O. Box 810
FI-65101 Vaasa
Phone:
Fax:
Internet: email:
+358 20 753 3200
+358 20 753 3205 www.vamp.fi
Customer Care Centre
http://www.schneider-electric.com/CCC
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00 www.schneider-electric.com
Publication version: VIOen M/A001
Publishing: Schneider Electric
10/2012
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project