VAM I/O units

Add to my manuals
66 Pages

advertisement

VAM I/O units | Manualzz

VAM I/O units

Publication version: VIOen M/A001

User manual

Trace back information:

Workspace Main version a5

Checked in 2012-10-18

Skribenta version 803

3

Contents VAM I/O units

Contents

1 This document .........................................................................

1.1

Legal notice ......................................................................

1.2

Safety information ............................................................

1.3

Related documents ..........................................................

1.4

Abbreviations and symbols ..............................................

5

5

5

6

7

2 Introduction .............................................................................

9

2.1

Purpose ............................................................................

2.2

Main properties ................................................................

9

9

3 User interface ..........................................................................

10

3.1

VAM 3L ............................................................................

10

3.2

VAM 3LX ..........................................................................

12

3.3

VAM 10L ..........................................................................

13

3.4

VAM 10LD ........................................................................

14

3.5

VAM 12L ..........................................................................

15

3.6

VAM 12LD ........................................................................

17

3.7

VAM 4C ............................................................................

19

3.8

VAM 4CD .........................................................................

20

3.9

VAMP 4R .........................................................................

22

4 Programming switches ...........................................................

23

4.1

Switches for arc sensor I/O units .....................................

23

4.2

Switches for current I/O units ...........................................

25

5 Adjusting the overcurrent setting ..........................................

28

6 BI/BO connection ....................................................................

29

7 Connection examples .............................................................

30

7.1

VAM 3L / VAM 3LX interfaces ..........................................

30

7.2

VAM 10L interfaces ..........................................................

31

7.3

VAM 10LD interfaces .......................................................

32

7.4

VAM 12L interfaces ..........................................................

33

7.5

VAM 12LD ........................................................................

34

7.6

VAM 4C interfaces ...........................................................

35

7.7

VAM 4CD interfaces .........................................................

36

7.8

Multiplying relay VAMP 4R ...............................................

37

8 Technical data ..........................................................................

38

8.1

Connections .....................................................................

38

8.1.1

Auxiliary power supply ........................................

39

8.1.2

Digital inputs (BI/O bus) ......................................

8.1.3

Trip contacts ........................................................

8.2

Test and environmental conditions ..................................

8.2.1

Environmental conditions ....................................

39

40

41

41

VIOen M/A001

VAM I/O units Contents

8.2.2

Casing .................................................................

41

8.2.3

Package ..............................................................

42

9 Construction ............................................................................

43

9.1

Dimensional drawings ......................................................

43

9.1.1

VAM 3L / 3LX Din rail mounting ..........................

43

9.1.2

VAM 10L Din rail mounting ..................................

9.1.3

VAM 10LD Flush mounting .................................

9.1.4

VAM 12L Din rail mounting ..................................

44

45

46

9.1.5

9.1.6

9.1.7

9.1.8

VAM 12LD Flush mounting .................................

VAM 4C Din rail mounting ...................................

VAM 4CD Flush mounting ...................................

VAMP 4R Din rail mounting .................................

47

48

49

50

9.1.9

VA 1 DA ...............................................................

51

9.1.10 VA 1 EH ...............................................................

51

9.1.11 VYX 001 ..............................................................

52

9.1.12 VYX 002 ..............................................................

53

9.2

I/O unit mounting and wiring ............................................

54

9.2.1

VAM 3L, VAMP 3LX, VAM 10L, VAM 12L, VAM

4C ........................................................................

9.2.2

VAM 10LD, VAM 12LD, VAM 4CD ......................

54

54

9.3

Wiring of the I/O units ......................................................

55

9.4

Wiring the secondary circuits of the current transformers

(VAM 4C / VAM 4CD only) ...............................................

55

9.5

Wiring the trip circuits of the circuit breakers ...................

9.6

Wiring between the central unit and the I/O unit ..............

55

56

9.7

Wiring separate auxiliary supplies ...................................

9.8

VAMP 4R .........................................................................

56

57

9.9

Wiring multiple central units .............................................

58

9.10 Arc sensors ......................................................................

59

10 Order information ....................................................................

63

11 Glossary ...................................................................................

64

VIOen M/A001 4

5

1

1.1

1.2

1 This document VAM I/O units

This document

Legal notice

Copyright

©Schneider Electric 2012. All rights reserved.

Disclaimer

No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this document. This document is not intended as an instruction manual for untrained persons. This document gives instructions on device installation, commissioning and operation. However, the manual cannot cover all conceivable circumstances or include detailed information on all topics. In the event of questions or specific problems, do not take any action without proper authorization. Contact Schneider Electric and request the necessary information.

Contact information

35 rue Joseph Monier

92506 Rueil-Malmaison

FRANCE

Phone: +33 (0) 1 41 29 70 00

Fax: +33 (0) 1 41 29 71 00 www.schneider-electric.com

Safety information

• Failure to follow these instructions will result in death or serious injury

• Only qualified personnel should install this equipment. Such work should be performed only after reading this entire set of instructions.

• Turn off all power supplying this equipment before starting the installation work.

• Ensure the protective grounding is connected.

• Before performing visual inspections, commissioning, or maintenance on this equipment, disconnect all sources of electric power.

VIOen M/A001

VAM I/O units

1.3

1 This document 1.3 Related documents

• Assume that all circuits are live until they have been completely de-energised, tested and tagged. Pay particular attention to the design of the power system. Consider all sources of power, including the possibility of backfeeding.

• Beware of potential hazards, wear personal protective equipment, carefully inspect the work area for tools and objects that may have been used during commissioning or maintenance.

• Neglecting fundamental installation requirements can lead to personal injury as well as damage to electrical equipment or other property.

• Handling this equipment requires relevant expertise in the field of protection of electrical networks. Only competent people who have this expertise are allowed to configure and set up this equipment.

• Before performing dielectric (Hi-Pot) testing on any equipment in which the IED is installed, disconnect all input and output wires to the IED. High voltage testing can damage electronic components contained in the unit.

• Always use a properly rated voltage sensing device to confirm that all power is off.

• The successful operation of this equipment depends upon proper handling, installation, and operation.

Related documents

Table 1.1: Related documents

Document

VAMP Mounting and Commissioning Instructions

VAMP Arc I/O units user manual

VAMP Arc Flash Protection Testing Manual

VAMPSET Setting and Configuration Tool User Manual

*) xxxx = revision number

Identification* )

VARC_MC_xxxx

VIO_EN_M_xxxx

VARCTEST_EN_M_xxx

VVAMPSET_EN_M_xxxx

Download the latest documents and software at www.vamp.fi.

VIOen M/A001 6

7

1.4 Abbreviations and symbols

1.4

1 This document VAM I/O units

Abbreviations and symbols

Table 1.2: Symbols

Symbol Description

Indicates a hazardous situation which, if not avoided, will result in death or serious injury.

Indicates a hazardous situation which, if not avoided, could result in death or serious injury.

Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.

Addresses practices not related to personal injury.

Table 1.3: Abbreviations

ANSI

CB

CBFP

Dead band

DI

DO

DSR

DST

DTR

FFT

Hysteresis

IEC

IEEE

IEC-101

IEC-103

LAN

Latching

NTP

PT pu

SNTP

TCS

THD

American National Standards Institute. A standardization organisation.

Circuit breaker

Circuit breaker failure protection

See hysteresis.

Digital input

Digital output, output relay

Data set ready. An RS232 signal. Input in front panel port of VAMP relays to disable rear panel local port.

Daylight saving time. Adjusting the official local time forward by one hour for summer time.

Data terminal ready. An RS232 signal. Output and always true (+8

Vdc) in front panel port of VAMP relays.

Fast Fourier transform. Algorithm to convert time domain signals to frequency domain or to phasors.

I.e. dead band. Used to avoid oscillation when comparing two near by values.

International Electrotechnical Commission. An international standardization organisation.

Institute of Electrical and Electronics Engineers

Abbreviation for communication protocol defined in standard IEC

60870-5-101

Abbreviation for communication protocol defined in standard IEC

60870-5-103

Local area network. Ethernet based network for computers and relays.

Output relays and indication LEDs can be latched, which means that they are not released when the control signal is releasing.

Releasing of lathed devices is done with a separate action.

Network time protocol for LAN and WWW

See VT

Per unit. Depending of the context the per unit refers to any nominal value. For example for overcurrent setting 1 pu = 1xI mode

.

Simple Network Time Protocol for LAN and WWW

Trip circuit supervision

Total harmonic distortion

VIOen M/A001

VAM I/O units

U

0sec

U a

U b

U c

U n

UTC

VT

VT pri

VT sec

WWW

1 This document 1.4 Abbreviations and symbols

Voltage at input U c at zero ohm earth fault. (Used in voltage measurement mode “2LL+Uo”)

Voltage input for U

12 mode or U

L1 depending of the voltage measurement

Voltage input for U

23 mode or U

L2 depending of the voltage measurement

Voltage input for U

31 mode or U

0 depending of the voltage measurement

Nominal voltage. Rating of VT primary or secondary

Coordinated Universal Time (used to be called GMT = Greenwich

Mean Time)

Voltage transformer i.e. potential transformer PT

Nominal primary value of voltage transformer

Nominal secondary value of voltage transformer

World wide web (internet)

VIOen M/A001 8

9

2

2.1

2.2

2 Introduction VAM I/O units

Introduction

This User’s Manual contains a functional description of the VAM I/O units and technical data.

Purpose

The main purpose of the VAM I/O units is to detect arc light or short circuit current and deliver this information (zone information) to the arc protection central unit and the other VAM I/O units. Additionally

VAM I/O units can be used for tripping appropriate circuit breakers.

Main properties

Arc flash protection system is a modular system consisting of a central unit, I/O units and arc sensors.

Due to its modularity, the system is suitable for a range of arc protection applications, from simple systems with one central unit and one I/O unit to more complex solutions comprising several central units used for selective arc protection.

The I/O unit VAM 10L / VAM 10LD, VAM 12L / VAM 12LD serves as link between the system’s point sensors and the central unit. Each

I/O unit has connections for ten arc sensors, one portable pin sensor and one trip output.

The I/O unit VAM 3L/VAM3LX serves as link between the system’s fibre sensors and the central unit. Each I/O unit has connections for three arc sensors, one pin sensor and one trip output.

The I/O unit VAM 4C / VAM 4CD serves as link between the system’s current inputs and the central unit. Each I/O unit has connections for three current transformers and one trip output.

The arc sensor VA 1 DA is activated by strong light. The sensor transforms the light information into the current signal, which is forwarded through the I/O unit to the central unit. The arc sensor VA

1 EH also operates on the same principle.

The pin sensor VA 1 DP has the same functions as an arc sensor but can be temporarily connected to an I/O unit. The sensor can be fixed to the breast pocket of a technician to improve safety when working with live switchgear.

The door mounted VAM I/O units with the letter D in the type designations VAM 10LD, VAM 12LD and VAM 4CD are door mounted versions for the corresponding VAM 10L, VAM 12 L and VAM 4C units. The functionality is exactly the same.

VIOen M/A001

VAM I/O units

3

3.1

VIOen M/A001

3 User interface

User interface

Usually, there is no need to touch the front panel during normal operation, since all the necessary information can be read from the central unit display. However, after a new installation or a system expand you will need to program certain functions (zone/address, trip output) in the I/O unit.

If you unfasten the terminal blocks during installation, remember to tighten the fixing screws after installation! Also tighten the screws even if you did not unfasten the blocks.

VAM 3L

12

VAM 3L

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X2

COM 1

6

COM 2

1

2

BI/O

Latch

L+I / L

Zone

Addr.

6

7

4

5

8

2

3

OFF

1

SW1

ON

SENSOR

OK

ACT

9

10

TRIP

11

7

CH1

SENSOR INPUTS

CH2 CH3

3

4

5

POWER

COM

ERROR

R1 T1 R2 T2 R3 T3

VAM3 L

8

Figure 3.1: Arc fibre sensor I/O unit VAM 3L front panel

1. Connection for portable arc sensor (VA 1 DP)

2. Programming switches

3. POWER indicator light, indicates that the supply voltages of each component are in order.

4. COM indicator light, lit when the central units and I/O units are communicating.

5. ERROR indicator light, indicates an internal fault detected by the component’s self-diagnostics. Such faults include faulty arc sensor or changes in the amount of sensors.

6. Connector sockets for the VX001 modular cables

7. LED lights indicating sensor activation

10

3.1 VAM 3L 3 User interface VAM I/O units

8. Terminals for three fibre sensors

9. Portable arc sensor VA 1 DP connected and operational

10. Portable arc sensor activated

11. I/O unit trip relay activated

12. Terminal block for external communication and BI/O channels and trip signal

11 VIOen M/A001

VAM I/O units

3.2

3 User interface 3.2 VAM 3LX

VAM 3LX

12

16 15 14 13 12 11 10 9

VAM 3LX

8 7 6 5 4 3 2 1

COM 1

X2

6

COM 2

1

2

BI/O

Latch

L+I / L

Zone

Addr.

6

7

8

4

5

OFF

1

2

3

SW1

ON

SENSOR

OK

ACT

9

10

TRIP

11

7

CH1

SENSOR INPUTS

CH2 CH3

3

4

5

POWER

COM

ERROR

R1 T1 R2 T2

8

R3 T3

CH1

Adj

CH2

Adj

CH3

Adj

13

Min. Max. Min. Max. Min. Max.

VAM 3LX

Figure 3.2: Arc fibre sensor I/O unit VAM 3LX front panel

1. Connection for portable arc sensor (VA 1 DP)

2. Programming switches

3. POWER indicator light, indicates that the supply voltages of each component are in order.

4. COM indicator light, lit when the central units and I/O units are communicating.

5. ERROR indicator light, indicates an internal fault detected by the component’s self-diagnostics. Such faults include faulty arc sensor or changes in the amount of sensors.

6. Connector sockets for the VX001 modular cables

7. LED lights indicating sensor activation

8. Terminals for three fibre sensors

9. Portable arc sensor VA 1 DP connected and operational

10. Portable arc sensor activated

11. I/O unit trip relay activated

12. Terminal block for external communication and BI/O channels and trip signal

13. Sensitivity adjustments for each fibre sensor channels

VIOen M/A001 12

3.3 VAM 10L

3.3

3 User interface VAM I/O units

VAM 10L

12

VAM 10L

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X2

COM 1

6

COM 2 M

OELLER

1

2

L> ext/int

Latch

L+I / L

Zone

Addr.

5

6

7

8

3

4

OFF

1

2

SW1

ON

SENSOR

OK

9

ACT

10

TRIP 11

3

4

5

POWER

COM

ERROR

1 2 3

7

4

SENSOR INPUTS

5 6 7 8 9 10

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

8

VAM10L

Figure 3.3: Arc sensor I/O unit VAM 10L front panel

1. Connection for portable arc sensor (VA 1 DP)

2. Programming switches

3. POWER indicator light, indicates that the supply voltages of each component are in order.

4. COM indicator light, lit when the central unit and I/O units are communicating.

5. ERROR indicator light, indicates an internal fault detected by the component’s self-diagnostics. Such faults include faulty arc sensor or changes in the amount of sensors.

6. Connector sockets for the VX001 modular cables

7. LED lights indicating sensor activation

8. Terminal block for ten arc sensors

9. Portable arc sensor VA 1 DP connected and operational

10. Portable arc sensor activated

11. I/O unit trip relay activated

12. Terminal block for external communication and BI/O channels and trip signal

VIOen M/A001 13

VAM I/O units

3.4

3 User interface

VAM 10LD

VAM 10LD

Arc Protection I/O-UNIT

M

1 2 3 4

7

SENSOR CHANNELS

5 6 7 8 9 10

13

ADDRESS NR 10

1. BB FEEDER 7

2. CB FEEDER 7

3. CC FEEDER 7

4. BB FEEDER 8

5. CB FEEDER 8

6. CC FEEDER 8

7. BB FEEDER 9

8. BB FEEDER 9

9. BB FEEDER 9

10. TIE BREAKER ID

TRIP

11

5

4

3

ERROR

COM

POWER

FRONT PANEL

3.4 VAM 10LD

VIOen M/A001

8

COM 2

20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

SENSOR INPUTS

X1

1

SENSOR

2

SW1

6

COM 1

10 ACT

9 OK

Addr.

Zone

L/L+I

Latch

L> Int/

Ext

OELLER BACK PANEL

X2

12

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

M

VAM10LD

Figure 3.4: Arc sensor I/O unit VAMP 10LD front and back panels

1. Connection for portable arc sensor (VA 1 DP)

2. Programming switches

3. POWER indicator light, indicates that the supply voltages of each component are in order.

4. COM indicator light, lit when the central unit and I/O units are communicating.

5. ERROR indicator light, indicates an internal fault detected by the component’s self-diagnostics. Such faults include faulty arc sensor or changes in the amount of sensors.

6. Connector sockets for the VX001 modular cables

7. LED lights indicating sensor activation

8. Terminal block for ten arc sensors

14

3.5 VAM 12L

3.5

3 User interface VAM I/O units

9. Portable arc sensor VA 1 DP connected and operational

10. Portable arc sensor activated

11. I/O unit trip relay activated

12. Terminal block for external communication and BI/O channels and trip signal

13. Text pocket for sensor specific labels.

VAM 12L

VAM 12L is primary design for selective feeder trip applications. The unit comprises 3 electromechanical trip normally open contacts and one trip alarm change over contact.

The unit has 10 Arc sensor inputs. Tree sensors (of the ten) inputs are dedicated, and are controlling their own trip relay. The unit is ideal for selective trip of cable compartment in case of an ARC fault.

VAM 12L can selectively handle 3 feeders. The rest of the sensors can then supervise the busbar and breaker compartments and will operate in the zone selected by the unit address switches.

12

VAM 12L

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X2

COM 1

6

COM 2 M

OELLER

1

2

L> ext/int

Latch

L+I / L

Zone

Addr.

5

6

3

4

7

8

OFF

1

2

SW1

ON

SENSOR

OK

9

ACT

10

TRIP

11

3

4

5

POWER

COM

ERROR

1 2 3

7

4

SENSOR INPUTS

5 6 7 8 9 10

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

8

VAM12L

Figure 3.5: Arc sensor I/O unit 12L

1. Connection for portable arc sensor (VA 1 DP)

2. Programming switches

3. POWER indicator light, indicates that the supply voltages of each component are in order.

4. COM indicator light, lit when the central unit and I/O units are communicating.

VIOen M/A001 15

VAM I/O units 3 User interface 3.5 VAM 12L

5. ERROR indicator light, indicates an internal fault detected by the component’s self-diagnostics. Such faults include faulty arc sensor or changes in the amount of sensors.

6. Connector sockets for the VX001 modular cables

7. LED lights indicating sensor activation

8. Terminal block for ten arc sensors

9. Portable arc sensor VA 1 DP connected and operational

10. Portable arc sensor activated

11. I/O unit trip relays activated

12. Terminal block for output relay

VIOen M/A001 16

3.6 VAM 12LD

3.6

3 User interface

VAM 12LD

VAM 12LD

Arc Protection I/O-UNIT

M

1 2 3 4

7

SENSOR CHANNELS

5 6 7 8 9 10

13

ADDRESS NR 10

1. BB FEEDER 7

2. CB FEEDER 7

3. CC FEEDER 7

4. BB FEEDER 8

5. CB FEEDER 8

6. CC FEEDER 8

7. BB FEEDER 9

8. BB FEEDER 9

9. BB FEEDER 9

10. TIE BREAKER ID

TRIP

11

5

4

3

ERROR

COM

POWER

FRONT PANEL

VAM I/O units

8

COM 2

20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

SENSOR INPUTS

X1

1

SENSOR

2

SW1

6

COM 1

10 ACT

9 OK

Addr.

Zone

L/L+I

Latch

L> Int/

Ext

OELLER BACK PANEL

X2

12

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

M

VAM12LD

Figure 3.6: Arc sensor I/O unit VAM 12LD front and back panels

1. Connection for portable arc sensor (VA 1 DP)

2. Programming switches

3. POWER indicator light, indicates that the supply voltages of each component are in order.

4. COM indicator light, lit when the central unit and I/O units are communicating.

5. ERROR indicator light, indicates an internal fault detected by the component’s self-diagnostics. Such faults include faulty arc sensor or changes in the amount of sensors.

6. Connector sockets for the VX001 modular cables

7. LED lights indicating sensor activation

8. Terminal block for ten arc sensors

VIOen M/A001 17

VAM I/O units 3 User interface 3.6 VAM 12LD

9. Portable arc sensor VA 1 DP connected and operational

10. Portable arc sensor activated

11. I/O unit trip relays activated

12. Terminal block for output relays

13. Text pocket for sensor specific labels.

VIOen M/A001 18

3.7 VAM 4C

3.7

3 User interface VAM I/O units

VAM 4C

12

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

VAM 4C

X2

COM 1

5

COM 2

1

Zone1

Zone2

Zone3

Zone4

Addr.

6

7

4

5

8

2

3

OFF

1

SW1

ON

TRIP

11

6

CURRENT TRANSFORMER

L1 L2 L3

13 x In

4.0

2.0

1.0

0.5

0.1

POWER

COM

ERROR

2

3

4

X1

1 2 3 4 5 6 7 8 9 10 11 12

7

L1/L3 L2/Io

SW2

ON

1 2 3 4

6

3

L1,L3

0.5

5

1.0

L2/Io

0.05

x In

8 9 10

VAM4c

Figure 3.7: Current I/O unit VAM 4C front panel

1. Programming switches

2. POWER indicator light, indicates the supply voltages of each component are in order.

3. COM indicator light, lit when the central units and I/O units are communicating.

4. ERROR indicator light, indicates an internal fault detected by the component’s self-diagnostics. Such faults include faulty current transformer or phase current unbalance.

5. Connector sockets for the VX001 modular cables

6. LED lights indicating that I> stage has started

7. Terminals for three current transformers

8. Current transformer programming switches

9. Overcurrent setting knob (I

L1

, I

L3

), setting range 0.5…6xI

N

10. Overcurrent setting knob (I

L1

, I

0

), setting range 0.05…5xI

N

11. I/O unit trip relay activated

12. Terminal block for external communication and BI/O channels and trip signal

13. Indicator leds for current setting

VIOen M/A001 19

VAM I/O units

3.8

3 User interface

VAM 4CD

VAM 4CD

Arc Protection I/O-UNIT

M

14

FEEDER:

ADDRESS:

F06

33

ZONE: 1 & 2

I> PICK -UP: 2 X In

OTHER : I > EXT ON

1

6

- - - CURRENT TRANSFORMER - - -

2 3

TRIP

11

4

3

2

FRONT PANEL

ERROR

COM

POWER

3.8 VAM 4CD

VIOen M/A001

10 9 8

L2/Io L1/L3 SW2

4.0

2.0

1.0

0.5

0.1

13 x In

COM 2 5 COM 1

12 11 10 9 8 7

7

6 5 4 3 2 1

X1

SW1 1

Addr.

Zone4

Zone3

Zone2

Zone1

OELLER

M

BACK PANEL

12

X2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

VAM 4 CD

Figure 3.8: Current I/O unit VAM 4CD front and back panel

1. Programming switches

2. POWER indicator light, indicates the supply voltages of each component are in order.

3. COM indicator light, lit when the central units and I/O units are communicating.

4. ERROR indicator light, indicates an internal fault detected by the component’s self-diagnostics. Such faults include faulty current transformer or phase current unbalance.

5. Connector sockets for the VX001 modular cables

6. LED lights indicating that I> stage has started

7. Terminals for three current transformers

8. Current transformer programming switches

20

3.8 VAM 4CD 3 User interface VAM I/O units

9. Overcurrent setting knob (I

L1

, I

L3

), setting range 0.5…6xI

N

10. Overcurrent setting knob (I

L1

, I

0

), setting range 0.05…5xI

N

11. I/O unit trip relay activated

12. Terminal block for external communication and BI/O channels and trip signal

13. Indicator leds for current setting

14. Text pocket

21 VIOen M/A001

VAM I/O units

3.9

3 User interface

VAMP 4R

VAMP 4R

Power



Trip 1

Trip 2

ƒ ƒ ‚

12 11 9 8 6 5 4 3 2 1 X2

TRIP 1 TRIP 2

18...265Vac/dc

-

INPUTS

+ +

24Vdc

+

3.9 VAMP 4R

TRIP GROUP 1

NO NC NO

OUTPUT

TRIP GROUP 2

NC NO NC NO NC

SF ALARM

NO

COM

NC

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

VAMP 4R frontplate

„

Figure 3.9: Multiplying relay VAMP 4R

1. POWER LED, indicates that the external operating voltage of

+24 Vdc is connected.

2. Terminals for external operating voltage (+24 Vdc). Can be supplied by central units or I/O units.

3. Terminals for incoming trip signal (e.g. 24 Vdc from VAM I/O unit binary output, 2 groups). Control voltage range is 18 … 265

Vad/dc.

4. Terminals for outgoing trip signals (8 potential-free contacts, 4 normally open, 4 normally closed).

VIOen M/A001 22

4

4.1

4 Programming switches VAM I/O units

Programming switches

Before system implementation, check the positions of the programming switches in accordance with the following basic principles:

• Each I/O unit connected to the communication bus has its own address (each I/O unit have an unique address).

• Set the programming switches before connecting the supply voltage.

• If you have to change the switch positions once the supply voltage has been connected, disconnect the supply voltage to the unit in question for the duration of the programming and re-configure the system.

• If position of the switch is changed, re-install the system again in the central unit.

Switches for arc sensor I/O units

The programming switches of the I/O units are used to determine the unit address and trip relay function.

The system accommodates up to 16 I/O units. Eight addresses are reserved for each protection zone:

Zone 1 addresses 0…7

Zone 2 addresses 8…15

Zone 3 addresses 16…23

Zone 4 addresses 24…31

The programming switches have different weight factors. To create an address for the I/O unit, turn switches with different values to the

ON position and calculate the sum of their weight factors. The following table shows the weight factors of each programming switch.

Table 4.1: Programming switch weight factors, *) VAM 3L and VAM 3LX, VAM

10L / VAM 10LD, VAM 12L / VAM 12LD only

Switch No.

8

7

6

5

4 *)

Weight factor

1

2

4

8

16

Note the position of the VAM 12LD, VAM 10LD and VAM 4CD dip switches.

VIOen M/A001 23

VAM I/O units 4 Programming switches 4.1 Switches for arc sensor I/O units

VAM 3L / VAM 3LX

VAM 12LD / VAM 10LD

ACT

OK

SENSOR

6

5

4

3

2

1

ON

8

7

SW1

OFF

Addr.

Zone

L / L+I

Latch

L> ext/int

BI/O

Latch

L+I / L

Zone

Addr.

4

5

6

7

8

OFF

1

2

3

SW1

ON

SENSOR

OK

ACT

TRIP

M

VAM 10L / VAM 12L

M

L> ext/int

Latch

L+I / L

OFF

1

2

3

4

Zone

5

6

Addr.

7

8

SW1

ON

SENSOR

OK

ACT

TRIP

VAM3L/VAM3LX, VAM10L/VAM10LD, VAM12L/VAM12LD dips

Figure 4.1: Programming switches for VAM 3L, VAM 3LX, VAM 10L, VAM 10LD, VAM

12L and VAM 12LD

VAM 3L / VAM 3LX, VAM 10L / VAM 10LD

Switch 1 determines which light activation activates the arc stage.

When the switch position is ON, the arc stage only activates on the light information provided by the unit's own sensors. In OFF position the arc stage activates on the light information received from any unit in the same protection zone.

Switch 2 determines the trip relay latch. When the switch is in ON position the trip relay remains engaged after the arc trip until the fault is acknowledged at the central unit’s panel. In the OFF position the trip relay follows the arc fault.

Switch 3 determines the arc trip criteria. When the switch is in ON position the trip is based on light information only; in OFF position both fault currents exceeding the current limit and light information are required.

VIOen M/A001 24

4.2 Switches for current I/O units 4 Programming switches

4.2

VAM I/O units

VAM 12L / VAM 12LD

When the L>ext/int DIP switch is in “L>int” position, the output relays are only activated by dedicated sensors.

SENSOR 1 activates T1.

SENSOR 2 activates T2.

SENSOR 3 activates T3.

SENSORS 4 to 10 are normally sending light information to system according to zone setting.

If the switch is in “L>ext” position, all output relays are also controlled by the selected zone information. This activation source can be any sensor channel 4 to 10 or from an external I/O unit configured to the same zone.

Switches for current I/O units

The address range for current I/O units is (32),33…46. Do not use address 32, because in this case the current I/O unit operates in

CENTRAL UNIT mode and the actual central unit must be set to

SUB-UNIT mode. To determine the address of a current I/O unit, add the sum of the weight factors to 32 (for example, programming switch values total 7, address of the current I/O unit 32 + 7 = 39).

Do not use 32 as the unit address if system have central unit.

Other programming switches have different functions in different units, as described below.

VAM 4C / VAM 4CD

VAM 4C

Zone1

Zone2

Zone3

Zone4

Addr.

7

8

5

6

3

4

OFF

1

2

SW1

ON

TRIP

11 12

SW2

ON

1 2 3 4

6

3

L1,L3

0.5

5

1.0

L2/Io

0.05

x In

VAM4C_dips

VAM 4CD

2

1

6

5

4

3

ON

8

7

SW1

OFF

Addr.

Zone4

Zone3

Zone2

Zone1

11 12

SW2

ON

1 2 3 4

6

3

M

0.5

5

1.0

L2/Io

0.05

x In

VAM4CD_dips

Figure 4.2: Programming switches of VAM 4C / VAM 4CD

25 VIOen M/A001

VAM I/O units 4 Programming switches 4.2 Switches for current I/O units

Table 4.2: VAM4C dipswitches weight factors

SW NO:

8

7

6

5

7

8

4

5

6

2

3

Switch

1

SW1 switch settings

Definition

Zone 1

Zone 2

Zone 3

Zone 4

Addr

Addr

Addr

Addr

Weight factor

1

2

4

8

Description

System operating zone 1 (light information)

System operating zone 2 (light information)

System operating zone 3 (light information)

System operating zone 4 (light information)

Address weighting coefficient 8

Address weighting coefficient 4

Address weighting coefficient 2

Address weighting coefficient 1

VIOen M/A001 26

4.2 Switches for current I/O units 4 Programming switches

SW2 switch settings

Switch

1

Definition

Latch

2

3

4

1A / 5A *

I> out

I> in

VAM I/O units

Description

Position ”0” (switch down): trip relay is only operational while the protection is activated

Position ”1” (switch up): trip relay changes to latching status after trip

Position ”0” (switch down): rated secondary current of the current transformer is 1 A

Position ”1” (switch up): rated secondary current of the current transformer is 5 A

Position ”0” (switch down): unit does not transmit the current criteria to other units

Position ”1” (switch up): unit transmits the current criteria to other units

Position ”0” (switch down): unit does not receive the current criteria from other units

Position ”1” (switch up): unit receives the current criteria from other units

*) As in CT

27 VIOen M/A001

VAM I/O units

5

5 Adjusting the overcurrent setting

Adjusting the overcurrent setting

The principles for changing the current setting in VAM 4C units are the same as for the central unit. You can see the estimated current setting from the led bar on the right side of the unit.

The most accurate way of setting the current limit for the unit is as follows:

• Turn the potentiometer to the maximum value.

• Feed a test current corresponding to the required setting using a testing device.

• Lower the setting until the current activation indicator led of the

I/O unit and the I>ext indicator led in the central unit are lit.

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

VAM 4C

Zone1

Zone2

Zone3

Zone4

Addr.

SW1

TRIP

COM 1 x In

4.0

2.0

1.0

0.5

0.1

CURRENT TRANSFORMER

L1 L2 L3

X2

COM 2

POWER

COM

ERROR

L1/L3 L2/Io X1

VAM4c conn

Figure 5.1: Adjusting the current setting in VAM 4C

VIOen M/A001 28

6

6 BI/BO connection VAM I/O units

BI/BO connection

Each I/O unit also has a BI/O bus. The light I/O units (VAM 3L / VAM

3LX, VAM 10L / VAM 10LD, VAM 12L / VAM 12LD) can transmit trip signal to the central unit or current I/O unit. The current I/O unit (VAM

4C / VAM 4CD) can receive the light information and send the current information either to other I/O units or the multiplying relay.

The DI/DO on the VAM units are fast BI/BO signals.

The following DI and DO connections are included in the standard delivery of VAM 3L / VAM 3LX and VAM 10L units:

Zone shift 1(2, 2(1, 3(4, 4(3 DI

GND

Trip out

GND

X2-8

X2-7

X2-10

X2-9

Trip signal, 24 V dc

Trip signal earth

The following DI and DO connections are included in the standard delivery of VAM 4C units:

L>in

GND

Trip out

GND

X2-8

X2-7

X2-10

GND

Light input, 24-48 V dc

Light input earth

Trip signal

Trip signal earth

29 VIOen M/A001

VAM I/O units

7

7.1

VIOen M/A001

7 Connection examples

Connection examples

VAM 3L / VAM 3LX interfaces

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

VAM 3L / 3LX

COM 1

X2

COM 2

BI/O

Latch

L+I / L

Zone

Addr.

SW1

SENSOR

OK

ACT

TRIP

CH1

SENSOR INPUTS

CH2 CH3

POWER

COM

ERROR

X2-9:

X2-10:

X2-11:

X2-12:

X2-13:

X2-14:

X2-15:

X2-16:

X1-R1:

X1-T1:

X1-R2:

X1-T2:

X1-R3:

X1-T3:

X2-1:

X2-2:

X2-3:

X2-4:

X2-5:

X2-6:

X2-7:

X2-8

R1 T1 R2 T2 R3 T3

VAM3L/VAM 3LX conn

Fiber receiver connection

Fiber transmitter connection

Fiber receiver connection

Fiber transmitter connection

Fiber receiver connection

Fiber transmitter connection

Channel 1

Channel 2

Channel 3

+24V supply from master unit or external power supply

GND

CAN-L

CAN-H

Serial B

Serial A

DI GND

DI (24-48Vdc)

DO GND

DO +24Vdc

+ Temp sensor

- Temp sensor

Zone information

(L>, I>) master slave com

Zone change

(1 -> 2; 2 -> 1;

3 -> 4; 4 -> 3)

Trip signal

(DI&DO)

Not in use

= COM1, COM2

Trip relay (NO)

Trip relay (NO)

30

7.2 VAM 10L interfaces

7.2

7 Connection examples

VAM 10L interfaces

VAM 10L

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

M

OELLER

COM 1

X2

COM 2

L> ext/int

Latch

L+I / L

Zone

Addr.

SW1

SENSOR

OK

ACT

TRIP

1 2 3 4

SENSOR INPUTS

5 6 7 8 9 10

POWER

COM

ERROR

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

X2-2:

X2-3:

X2-4:

X2-5:

X2-6:

X2-7:

X2-8:

X2-9:

X2-10:

X2-11:

X2-12:

X2-13:

X2-14:

X2-15:

X2-16:

X1-1,2:

X1-3,4:

X1-5,6:

X1-7,8:

X1-9,10:

X1-11,12:

X1-13,14:

X1-15,16:

X1-17,18:

X1-19,20:

X2-1:

VAM10L conn arc sensor channel 1 arc sensor channel 2 arc sensor channel 3 arc sensor channel 4 arc sensor channel 5 arc sensor channel 6 arc sensor channel 7 arc sensor channel 8 arc sensor channel 9 arc sensor channel 10

+24V supply from masterunit or external power supply

GND

CAN-L

CAN-H

Serial B

Serial A

DI GND

DI (24-48Vdc)

Zone information

(L>, I>)

Master slave com

Zone change

(1 -> 2; 2 ->1;

3 -> 4; 4 -> 3)

DO GND

DO +24Vdc

+ Temp sensor

- Temp sensor

Trip signal

Not in use

=COM1, COM2

Trip relay (NO)

Trip relay (NO)

VIOen M/A001 31

VAM I/O units

VAM I/O units

7.3

VIOen M/A001

7 Connection examples

VAM 10LD interfaces

7.3 VAM 10LD interfaces

COM 2

20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

SENSOR INPUTS

COM 1

X1

ACT

OK

SENSOR

SW1

Addr.

Zone

L/L+I

Latch

L> Int/

Ext

OELLER

M

X2

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

X2-2:

X2-3:

X2-4:

X2-5:

X2-6:

X2-7:

X2-8:

X2-9:

X2-10:

X2-11:

X2-12:

X2-13:

X2-14:

X2-15:

X2-16:

X1-1,2:

X1-3,4:

X1-5,6:

X1-7,8:

X1-9,10:

X1-11,12:

X1-13,14:

X1-15,16:

X1-17,18:

X1-19,20:

X2-1:

VAM10LD conn arc sensor channel 1 arc sensor channel 2 arc sensor channel 3 arc sensor channel 4 arc sensor channel 5 arc sensor channel 6 arc sensor channel 7 arc sensor channel 8 arc sensor channel 9 arc sensor channel 10

+24V supply from masterunit or external power supply

GND

CAN-L

CAN-H

Serial B

Serial A

DI GND

DI (24-48Vdc)

Zone information

(L>, I>)

Master slave com

Zone change

(1 -> 2; 2 ->1;

3 -> 4; 4 -> 3)

DO GND

DO +24Vdc

+ Temp sensor

- Temp sensor

Trip signal

Not in use

=COM1, COM2

Trip relay (NO)

Trip relay (NO)

32

7.4 VAM 12L interfaces

7.4

7 Connection examples

VAM 12L interfaces

VAM 12L

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

COM 1

X2

M

OELLER

COM 2

L> ext/int

Latch

L+I / L

Zone

Addr.

6

7

4

5

2

3

OFF

1

8

SW1

ON

SENSOR

OK

ACT

TRIP

1 2 3 4

SENSOR INPUTS

5 6 7 8 9 10

POWER

COM

ERROR

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

VAM I/O units

VAM12L conn

X2-2:

X2-3:

X2-4:

X2-5:

X2-6:

X2-7:

X2-8:

X2-9:

X2-10:

X2-11:

X2-12:

X2-13:

X2-14:

X2-15:

X2-16:

X1-1,2:

X1-3,4:

X1-5,6:

X1-7,8:

X1-9,10:

X1-11,12:

X1-13,14:

X1-15,16:

X1-17,18:

X1-19,20:

X2-1: arc sensor channel 1 arc sensor channel 2 arc sensor channel 3 arc sensor channel 4 arc sensor channel 5 arc sensor channel 6 arc sensor channel 7 arc sensor channel 8 arc sensor channel 9 arc sensor channel 10

+24v supply from masterunit or external power supply

GND

COM

NO

NC

Trip relay 3 (NO)

Trip relay 3 (NO)

Trip relay 2 (NO)

Trip relay 2 (NO)

Trip relay 1 (NO)

Trip relay 1 (NO)

Alarm

VIOen M/A001 33

VAM I/O units

7.5

VIOen M/A001

7 Connection examples

VAM 12LD

COM 2

20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

SENSOR INPUTS

COM 1

X1

ACT

OK

SENSOR

SW1

Addr.

Zone

L/L+I

Latch

L> Int/

Ext

OELLER

M

X2

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

VAM12LD conn

X2-2:

X2-3:

X2-4:

X2-5:

X2-6:

X2-7:

X2-8:

X2-9:

X2-10:

X2-11:

X2-12:

X2-13:

X2-14:

X2-15:

X2-16:

X1-1,2:

X1-3,4:

X1-5,6:

X1-7,8:

X1-9,10:

X1-11,12:

X1-13,14:

X1-15,16:

X1-17,18:

X1-19,20:

X2-1: arc sensor channel 1 arc sensor channel 2 arc sensor channel 3 arc sensor channel 4 arc sensor channel 5 arc sensor channel 6 arc sensor channel 7 arc sensor channel 8 arc sensor channel 9 arc sensor channel 10

+24v supply from masterunit or external power supply

GND

COM

NO

NC

Trip relay 3 (NO)

Trip relay 3 (NO)

Trip relay 2 (NO)

Trip relay 2 (NO)

Trip relay 1 (NO)

Trip relay 1 (NO)

Alarm

7.5 VAM 12LD

34

7.6 VAM 4C interfaces

7.6

7 Connection examples

VAM 4C interfaces

VAM I/O units

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

VAM 4C

Zone1

Zone2

Zone3

Zone4

Addr.

SW1

TRIP

COM 1 x In

4.0

2.0

1.0

0.5

0.1

CURRENT TRANSFORMER

L1 L2 L3

X2

COM 2

POWER

COM

ERROR

X1

X1-1,3:

X1-5,7:

X1-9,11.

X2-1:

X2-2:

X2-3:

X2-4:

X2-5:

X2-6:

X2-7:

X2-8:

X2-9:

X2-10:

X2-11:

X2-12:

X2-13:

X2-14:

X2-15:

X2-16:

Trip relay (NO)

Trip relay (NO)

L1/L3 L2/Io

VAM4c conn

Current input IL1

Current input IL2 / Io

Current input IL3

+24V supply from master unit or external power supply

GND

CAN-L

Zone information

(L>, I>)

CAN-H

Serial B master slave com

Serial A

DI GND

L>

DI (24-48Vdc)

DO GND

TRIP

DO +24Vdc

= COM1, COM2

35 VIOen M/A001

VAM I/O units

7.7

7 Connection examples

VAM 4CD interfaces

7.7 VAM 4CD interfaces

L2/Io L1/L3 SW2

COM 2

4.0

2.0

1.0

0.5

0.1

x In

COM 1

12 11 10 9 8 7 6 5 4 3 2 1

X1

OELLER

SW1

Addr.

Zone4

Zone3

Zone2

Zone1

M

X2

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

VAM4CD conn

X1-1,3:

X1-5,7:

X1-9,11.

X2-1:

X2-10:

X2-11:

X2-12:

X2-13:

X2-14:

X2-15:

X2-16:

X2-2:

X2-3:

X2-4:

X2-5:

X2-6:

X2-7:

X2-8:

X2-9:

Current input IL1

Current input IL2 / Io

Current input IL3

+24V supply from master unit or external power supply

GND

CAN-L

Zone information

(L>, I>)

CAN-H

Serial B master slave com

Serial A

DI GND

L>

DI (24-48Vdc)

DO GND

TRIP

DO +24Vdc

= COM1, COM2

Trip relay (NO)

Trip relay (NO)

VIOen M/A001 36

7.8 Multiplying relay VAMP 4R

7.8

7 Connection examples

Multiplying relay VAMP 4R

VAMP 4R

Power

Trip 1

Trip 2

12 11 9 8 6 5 4 3 2 1 X2

TRIP 1 TRIP 2

18...265Vac/dc

-

INPUTS

+ +

24Vdc

+

TRIP GROUP 1

NO NC NO

OUTPUT

TRIP GROUP 2

NC NO NC NO NC

SF ALARM

NO

COM

NC

X1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

VAMP 4R frontplate

X1-1,2:

X1-3,4:

X1-5,6:

X1-7,8:

X1-9,10:

X1-11,12:

X1-13,14:

X1-15,16:

X1-17:

X1-18:

X1-19:

X1-20:

X2-1:

X2-2:

X2-3:

X2-4:

X2-5:

X2-6:

X2-7:

X2-8:

X2-9:

X2-10:

X2-11:

X2-12:

Trip relay (NO), Trip group 1.

Trip relay (NC), Trip group 1.

Trip relay (NO), Trip group 1.

Trip relay (NC), Trip group 1.

Trip relay (NO), Trip group 2.

Trip relay (NC), Trip group 2.

Trip relay (NO), Trip group 2.

Trip relay (NC), Trip group 2.

NO

COM

NC

Aux voltage supply +24Vdc

GND

Aux voltage supply +24Vdc

GND

Aux voltage supply +24Vdc

GND

TRIP 2. Input 18...265Vac/dc

TRIP 2. Input 18...265Vac/dc

TRIP 1. Input 18...265Vac/dc

TRIP 1. Input 18...265Vac/dc

SF Alarm relay

Trip group 2.

Trip group 1.

VAM I/O units

VIOen M/A001 37

VAM I/O units

8

8.1

VIOen M/A001

8 Technical data

Technical data

Connections

VAM 3L

Sensor connections 3 fibre loop sensors (type ARC-SLx)

1 portable arc sensor (type VA 1 DP)

VAM 3LX

Sensor connections 3 fibre loop sensors (type ARC-SLx)

- sensitivity adjust range compared to 3L

0,5 (max) … 1,5 (min)

1 portable arc sensor (type VA 1 DP)

VAM 10L, VAM 10LD, VAM 12L, VAM 12LD

Sensor connections

Terminal:

- Phoenix MVSTBW or similar

10 arc sensors (type VA 1 DA or

VA 1 EH)

1 portable arc sensor (type VA 1 DP)

Maximum cross-section area of wire

2.5 mm 2 (13-14 AWG)

VAM 4C, VAM 4CD

Rated current L1 / L3

- current measuring zone

- thermal withstand capability

- power consumption

Rated current L2 / I

0

- current measuring zone

- thermal withstand capability

- power consumption

Terminal:

- single or multi-strand wire

1 or 5 A (optional) 50/60Hz

0 … 6 A (0 … 6*I

N

[I

N

=1A]);

0 … 30 A (0 … 6* I

N

[I

N

=5A])

300 A (for 1s)

100 A (for 10s)

20 A (continuous)

<0.3 VA

1 or 5 A (optional) 50/60Hz

0 … 6 A (0 … 6*I

N

[I

N

=1A]);

0 … 30 A (0 … 6* I

N

[I

N

=5A])

300 A (for 1s)

100 A (for 10s)

20 A (continuous)

<0.3 VA

Maximum cross-section area of wire

4 mm 2 (10-12 AWG)

38

8.1 Connections

8.1.1

8.1.2

39

8 Technical data VAM I/O units

Auxiliary power supply

VAM 3L, VAM 3LX, VAM 10L, VAM 10LD, VAM 12L, VAM 12LD,

VAM 4C, VAM 4CD

Rated voltage U

AUX

Power consumption

Terminal:

- Phoenix MVSTBW or similar

( RJ 45 when supply from central unit)

24 V dc

< 1 W (in normal mode)

< 1.5 W (output relays activated)

Maximum cross-section area of wire

2.5 mm 2 (13-14 AWG)

VAR 4CE

Rated voltage U

AUX

Power consumption

Terminal:

- fixed terminal

24 V dc

< 0.5 W (in normal mode)

< 4.5 W (output relays activated)

Maximum cross-section area of wire

2.5 mm 2 (13-14 AWG)

VAMP 4R

Rated voltage U

AUX

Current consumption

- one relay group activated

- both relay groups activated

VA 1 DA, VA 1 EH, VA 1 DP

Rated voltage U

AUX

Power consumption

24 V dc

20 mA stby

80 mA

180 mA

12 V dc (from I/O unit)

< 35 mW (in normal mode)

< 450 mW (activated)

Digital inputs (BI/O bus)

No digital inputs available in VAM 12L and VAM 12LD

VAM 3L, VAM 3LX, VAM 10L, VAM 10LD

Number of inputs

Internal operating voltage

Load capacity (max.)

Terminal:

- Phoenix MVSTBW or similar

1 pcs I> in

1 arc fault trip out

24…48 V dc (BIO in)

24 V dc (BIO out)

5 mA

Maximum cross-section area of wire

2.5 mm 2 (13-14 AWG)

VIOen M/A001

VAM I/O units

8.1.3

8 Technical data 8.1 Connections

VAM 4C

Number of inputs

Internal operating voltage

Load capacity (max.)

Terminal:

- Phoenix MVSTBW or similar

VAMP 4R

Operating voltage

Current consumption

1 pcs L> in

1 pcs I> out

24…48 V dc (BIO in)

24 V dc (BIO out)

5 mA

Maximum cross-section area of wire

2.5 mm 2 (13-14 AWG)

18…265 V ac/dc

2 mA

Trip contacts

VAM 3L, VAM 3LX, VAM 10L, VAM 10LD, VAM 12L, VAM 12LD,

VAM 4C, VAM 4CD

1 closing contact (relay T1) Number of contacts for VAM 10L, VAM 10LD, VAM 3L, VAM

3LX, VAM 4C, VAM 4CD

Number of contacts for VAM 12L, VAM 12LD

Rated voltage

Continuous withstand capacity

Make and carry for 0.5s

Make and carry for 3s

Breaking capacity, dc(L/R=40 ms)

At 48 V dc:

At 110 V dc:

At 220 V dc:

Relay material

Terminal:

- Phoenix MVSTBW or similar

3 closing contacts (relay T1)

250 V ac/dc

5 A

30 A

15 A

1 A

0.44 A

0.22 A

AgNi 90/10

Maximum cross-section area of wire

2.5 mm 2 (13-14 AWG)

VIOen M/A001 40

8.2 Test and environmental conditions

8 Technical data

VAMP 4R

4N/O / 4N/C rated voltage

Continuous withstand capacity

Make and carry for 0.5s

Make and carry for 3s

N/O breaking capacity dc

(L/R=40ms)

At 48 V dc

At 110 V dc

At 220 V dc

Contact material

Terminal:

- Phoenix MVSTBW or similar

250V ac/dc

5A

30A

15A

VAM I/O units

1A

0.44A

0.22A

AgNi 90/10

Maximum cross-section area of wire

2.5 mm 2 (13-14 AWG)

8.2

Test and environmental conditions

8.2.1

Environmental conditions

Operating temperature range

Transport and storage temperature range

- VAM I/O units

- ARC SLm, VA 1 xx sensors

Relative air humidity

Operation altitude

-10 … +55°C

-40 … +70°C

-40 … +85°C

<75% (1 year, average)

<90% (30 days per year, condensation not allowed)

2000 m

8.2.2

Casing

VAM 3L, VAM 3LX, VAM 10L, VAM 4C, VAMP 4R

Housing class (IEC 60529)

Dimensions (WxHxD)

Material

Weight

Colour code

IP21

157x92x25 mm

1mm steel plate

0.52 kg

RAL 7032 (housing) / RAL 70035

(back plate)

VIOen M/A001 41

VAM I/O units

8.2.3

8 Technical data 8.2 Test and environmental conditions

VAM 10LD, VAM 12LD, VAM 4CD

Door mounted (IEC 60529)

Dimensions (WxHxD)

Material

Weight

Colour code

IP64

185x120x25 mm

1mm steel plate

0.60 kg

RAL 7032 (housing) / RAL 70035

(back plate)

VA 1 DA, VA 1 EH, VA 1 DP

Housing class (IEC 60529)

Dimensions (WxHxD)

Material

Weight

Cable length

IP21

25x55x14 mm (VA 1 DA)

Φ11x62 mm (VA 1 EH)

Φ40x7 mm (VA 1 DP)

Plastic

0.01 kg

6 m or 20 m

(VA 1 DP 5 m)

Package

Dimensions (WxHxD)

Weight (unit, box and user instructions)

VAMP 4R: 157 x 92 x 25 mm

VAM 10L: 157 x 92 x 25 mm

VAM 3L: 157 x 92 x 25 mm

VAM 3LX: 157 x 92 x 25 mm

VAM 4C: 157 x 92 x 25 mm

VAMP 4R: 0.62 kg

VAM 10L: 0.62 kg

VAM 3L: 0.62 kg

VAM 3LX: 0.62 kg

VAM 4C: 0.62 kg

VIOen M/A001 42

9

9.1

9.1.1

9 Construction

Construction

Dimensional drawings

VAM 3L / 3LX Din rail mounting

VAM

3L /

3LX

VAM I/O units mm in

92

3.62

112

4.41

VAM

3L /

3LX

157

6.18

25

0.98

T max. 0.5...0.6Nm

4.4...5.3 lb.in

V A M

3 L /

3 L X

EN 50022

VAM

3L /

3LX

35 mm

1.38 in

43 VIOen M/A001

VAM I/O units

9.1.2

9 Construction

VAM 10L Din rail mounting

mm in

9.1 Dimensional drawings

157

6.18

92

3.62

112

4.41

25

0.98

T max. 0.5...0.6Nm

4.4...5.3 lb.in

EN 50022

35 mm

1.38 in

VIOen M/A001 44

9.1 Dimensional drawings

9.1.3

9 Construction

VAM 10LD Flush mounting

mm in

105

4.13

ø4.5

0.18

1.0

0.0

- 3

4-

.0

0.1

2

170

6.69

157

6.18

92

3.62

VAM I/O units

T max. 0.5...0.6Nm

4.4...5.3 lb.in

90

3.54

27.6

1.09

min. 2.5mm

2

120

4.72

185

7.28

45 VIOen M/A001

VAM I/O units

9.1.4

9 Construction

VAM 12L Din rail mounting

mm in

92

3.62

112

4.41

9.1 Dimensional drawings

157

6.18

25

0.98

T max. 0.5...0.6Nm

4.4...5.3 lb.in

EN 50022

35 mm

1.38 in

VIOen M/A001 46

9.1 Dimensional drawings

9.1.5

9 Construction

VAM 12LD Flush mounting

mm in

105

4.13

ø4.5

0.18

1.0

0.0

- 3

4-

.0

0.1

2

170

6.69

157

6.18

MP

121

D

92

3.62

VAM I/O units

T max. 0.5...0.6Nm

4.4...5.3 lb.in

VA

MP

121

D

90

3.54

27.6

1.09

MP

121

D min. 2.5mm

2

120

4.72

185

7.28

47 VIOen M/A001

VAM I/O units

9.1.6

9 Construction

VAM 4C Din rail mounting

9.1 Dimensional drawings mm in

92

3.62

112

4.41

157

6.18

25

0.98

T max. 0.5...0.6Nm

4.4...5.3 lb.in

EN 50022

35 mm

1.38 in

VIOen M/A001 48

9.1 Dimensional drawings

9.1.7

9 Construction VAM I/O units

VAM 4CD Flush mounting

mm in

2

105

4.13

ø4.5

0.18

1.0

0.0

- 3

4-

.0

0.1

2

170

6.69

157

6.18

T max. 0.5...0.6Nm

4.4...5.3 lb.in

1

92

3.62

D I P

O N

1

2

3 4

VAM

4C otec

Arc Pr tion

D

I/O

-UNIT

---CURRENT

TRANSFORMER---

L3

L2

L1

TRIP

ERRO

R

CO

M

PO

WER

3

O N

D I

1

2

P

3

4

VAM

4C

Arc Pr otec tion

D

I/O

-UNIT

---CURRENT

TRANSFORMER---

L3

L2

L1

TRIP

ER

RO

R

CO

M

PO

WER min. 2.5mm

2

90

3.54

27.6

1.09

O N

D I P

2 3

1

4

VAM

D

Arc Pr otec tion

I/O

-UNIT

---CURRENT

TRANSFORMER---

L3

L2

L1

TRIP

ERRO

R

CO

M

PO

WER

120

4.72

185

7.28

49 VIOen M/A001

VAM I/O units

9.1.8

9 Construction

VAMP 4R Din rail mounting

mm in

92

3.62

112

4.41

9.1 Dimensional drawings

157

6.18

25

0.98

T max. 0.5...0.6Nm

4.4...5.3 lb.in

EN 50022

35 mm

1.38 in

VIOen M/A001 50

9.1 Dimensional drawings

9.1.9

9 Construction

VA 1 DA

mm in

22.2

0.83

14

0.55

9.1.10

VA 1 EH

mm in

VAM I/O units

20

0.79

62

2.44

25

0.98

4.2

0.17

VA1DA_mittakuva

8

0.31

VA1EH_mittakuva

51 VIOen M/A001

VAM I/O units

9.1.11

9 Construction

VYX 001

mm in

15

0.59

50

1.97

0.3

10

9

0

.1

2

.5

50

1.97

15

0.59

9.1 Dimensional drawings

25

0.98

51

2.0

VYX001_mittakuva

VIOen M/A001 52

9.1 Dimensional drawings

9.1.12

9 Construction

VYX 002

mm in 1

0

0

.3

9

15

0.59

30

1.18

0

.1

2

3

15

0.59

VAM I/O units

30

1.18

VYX002

53 VIOen M/A001

VAM I/O units

9.2

9.2.1

9.2.2

VIOen M/A001

9 Construction 9.2 I/O unit mounting and wiring

I/O unit mounting and wiring

Read this User's Manual carefully before undertaking any installation or wiring work.

Safety instructions

Always observe the national electrical safety regulations when working under live conditions. The unit manufacturer is not liable for damage due to incorrect working methods or failure to observe safety instructions.

The correct handling of the unit under all mounting and operating conditions forms the foundation for its safe use.

Any separately marked notes and warnings must be observed.

The wiring work must be performed according to national standards and any requirements specified by the customer.

Do not connect the auxiliary supply voltage until the installation has been completed.

Before installation

Before installation, make sure the environmental conditions comply with the requirements specified in Chapter 7.

The unit contains components liable to damage if exposed to an electrostatic discharge (ESD).

Do not open the unit unless you have taken appropriate protective measures against ESD.

The manufacturer cannot guarantee operational safety in environments that do not satisfy the specified environmental conditions.

VAM 3L, VAMP 3LX, VAM 10L, VAM 12L, VAM

4C

The units are designed for mounting on a DIN rail. Mount the units on the rail in such a way that the indicator lights on the front panel are visible and the sensor wiring can be made as easily as possible.

VAM 10LD, VAM 12LD, VAM 4CD

The units are designed for mounting on a door. Hence all indicators are clearly visible in normal operation.

54

9.3 Wiring of the I/O units

9.3

9.4

9.5

55

9 Construction VAM I/O units

Wiring of the I/O units

The I/O units can be connected to the following:

• secondary circuits of the current transformers of the switchgear

(VAM 4C only)

• the trip circuits of the circuit breakers

• external auxiliary supply circuits

• connections to the central unit or other I/O units (data communication and auxiliary supply)

• connections to other central units or protection relays (DI or DO bus)

Wiring the secondary circuits of the current transformers (VAM 4C / VAM

4CD only)

Connect the secondary circuits of the current transformers to the following screw connectors:

• X1-1, X1-3 (L1)

• X1-5, X1-7 (L2/I0)

• X1-9, X1-11 (L3)

The arc protection system can also be single or two-phase connected.

Three-phase connection is nevertheless recommended for optimal operating speed.

The current measuring channels L1 and L3 must be used in connection with two-phase current measuring. Single-phase current or earth-fault current must always be connected to the current measuring channel L2/I0; otherwise, an unbalance error will occur.

The specified operating time of 7ms can only be guaranteed for three-phase current measurement.

Wiring the trip circuits of the circuit breakers

Connect the circuit breaker’s trip circuit to the following terminals:

TRIP1: X2-15, X2-16 (fast)

In the event of an arc fault, the output contact will close at 7 ms when three-phase current measurement is used.

VIOen M/A001

VAM I/O units

9.6

9.7

9 Construction 9.6 Wiring between the central unit and the I/O unit

The output trip relay of the light I/O units (VAM 10L and VAM 3 L) operates during faults in its own zone. In the current I/O unit (VAM

4 C), select the protection zone controlling the I/O unit using the programming switches.

If several trips are required, the multiplying relay VAMP 4R can be used.

Wiring between the central unit and the

I/O unit

Connect the central unit to the I/O units with a modular cable of type

VX001. The modular cable carries all information between the central unit and I/O units, including data in serial form, arc fault messages and operating supply to the I/O units.

• Connect the VX001 cable to the arc I/O COM interface of the central units.

• Connect the cable to COM1 or COM2 on the first I/O unit.

• Route the cable from COM1 or COM2 on the first I/O unit to

COM1 or COM2 in the next unit, etc.

All the COM1 and COM2 interfaces are identical, i.e. the cable can always be connected to either interface. The maximum total length of the modular cable, taking into account all the I/O units connected to the central unit, is 100 m.

Use only star connection for I/O units. Closed loop will cause communication errors.

Wiring separate auxiliary supplies

When routing modular cables over long distances or when the system contains several I/O units, you should preferably use a separate auxiliary supply parallel with the modular cable.

Connect the auxiliary supply to the 24 V terminals of the central unit to the 24 V terminals in the I/O units. Alternatively, you can also use a separate external voltage supply 3P004.

Pay particular attention to the polarity of the cable connections.

VIOen M/A001 56

9.8 VAMP 4R

9.8

9 Construction

VAMP 4R

18...265 V ac/dc

12 11 9 8

+ 24 Vdc

+ + +

6 5 4 3 2 1 :X2

VAMP 4R

Group 1 Group 2

Self supervision alarm

VAM I/O units

X1: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 19 20 18

VAMP4R Block diagram

Figure 9.1: VAMP 4R block diagram

The multiplying relay VAMP 4R can be used when additional trip outputs are needed.

VAMP 4R comprises 4 N/O contacts and 4 N/C contacts. They are divided into two separate groups which can be independently controlled by e.g. the binary output of the I/O units or the central unit.

• Attach the VAMP 4R unit to a DIN rail.

• Connect the auxiliary voltage ( +24V ) to terminal X2-1 (+) and

X2-2 (-). Terminals X2-3 and X2-5 are parallel inputs to X2-1(+).

Terminals X2-4 and X2-6 are parallel inputs to X2-2(1). The auxiliary voltage ( +24V ) can be supplied from the central unit or nearest slave ( X2-1 (+), X2-2 (-)).

• Connect the required signal (18-265 V ad/dc) to the trip control inputs.

• Input “TRIP 1” ( X2-11, X2-12 ) is controlling the trip group 1.

Input “TRIP 2” ( X2-8, X2-9 ) is controlling the trip group 2.

• There are 2xN/C + 2xN/O contacts per trip group.

If necessary, input TRIP 1 and 2 can be connected in parallel. Then all trip relays will operate simultaneously.

57 VIOen M/A001

VAM I/O units

9.9

9 Construction 9.9 Wiring multiple central units

Wiring multiple central units

A maximum of three central units can be connected to one communication bus. In this case, the units can operate on a maximum of four protection zones (depending on their programming switches).

The light and current signals given by the I/O units, including address information, are transferred to each central unit.

If more than one central unit is to be connected to the same communication bus, one central unit must be in central unit mode and the other central units in sub-unit mode.

In applications with multiple central units the central units can be interconnected also via BI/O connections (binary input/output). In this case, each part of the system can control four protection zones per system communication bus. In this case, arc and overcurrent information is transferred between the central units without address information.

When configurating arc protection system with multiple central units, disconnect I/O-units from central units in slave mode during their installation procedure.

VIOen M/A001 58

9.10 Arc sensors

9.10

9 Construction VAM I/O units

Arc sensors

Mount the sensors on the switchgear in such a way that they cover the protection zone as completely as possible. The line of sight must be free between the sensor and the supervised area.

If point sensors are used in open compartments (such as bus-bar sections), there should be a sensor approximately every 5 meters.

Due to the wide detection range of the sensors and the light reflection inside the switchgear, the mounting position is not critical.

Connecting sensors VA 1 DA and VA 1 EH to the I/O units

The sensors are delivered with 6-metre standard cables or 20-metre shielded cables (to be specified in the order).

After mounting the sensors, connect them to the I/O units as follows:

• Draw the wire to the nearest I/O unit using the shortest route possible and cut it to a suitable length.

• Connect the arc sensors to the screw terminals X1-1…20. The polarity of the arc sensor cables is not critical.

Connecting the ARC-SLx sensors to the I/O units

The sensors are delivered in standard lengths (to be specified in the order) equipped with terminals compatible with VAM 3L units.

After mounting the sensors, connect them to the I/O units as follows:

• Draw each end of the sensor to the I/O unit and carefully form a loop of the extra fibre.

Do not shorten the extra sensor fibre unless you have appropriate terminal connectors.

• Connect the arc sensors to plug-in terminals X1-R1, T1…R3,

T3. While the polarity of the arc sensors is not critical, you must connect each end of the fibre to the same channels.

59 VIOen M/A001

VAM I/O units 9 Construction 9.10 Arc sensors

VA 1 DA

You can be install the arc sensor onto the switchgear wall from the outside. Press the active part of the sensor through the 10-mm hole in the wall and fix it using a 4-mm screw.

VIOen M/A001

VA1DA_asennus

Figure 9.2: Mounting the arc sensor VA 1 DA

1. Active part of the sensor

2. Cable clamp

3. Fastening screw 4x15 mm

4. Cable of sensor

You can also surface mount the sensor to the wall using the mounting plates VYX01 or VYX02, available as additional parts.

The sensor must not be exposed to direct sunlight or other strong light. Do not mount the sensor directly under a light source.

60

9.10 Arc sensors 9 Construction VAM I/O units

Figure 9.3: Arc sensor VA 1 DA

Figure 9.4: Sensitivity of the arc sensor VA

1 DA

VA 1 EH

You can be install the arc sensor onto the switchgear wall from the outside. Press the active part of the sensor through the 10.5-mm hole in the wall.

You can also surface mount the sensor. To do this, push the sensor into a plastic mounting tube and fix it with heat shrink tubing.

The sensor must not be exposed to direct sunlight or other strong light. Do not mount the sensor directly under a light source.

61

Figure 9.5: Arc sensor VA 1 EH

ARC-SLx

ARC-SLx is an fibre sensor that can be mounted on the switchgear to monitor several compartments simultaneously (various bus-bar compartmets, etc.).

The fibre must not touch any live parts of the switchgear or other hot components, since too high temperatures may destroy the fibre.

VIOen M/A001

VAM I/O units 9 Construction 9.10 Arc sensors

When mounting the sensor on the switchgear, ensure that the bending radius is long enough (min. 80 mm) and that it is safe from the sharp edges of the switchgear.

The sensor must not be exposed to direct sunlight or other strong light. Do not mount the sensor directly under a light source.

To avoid false tripping, cover any unused channels of the I/O unit.

Figure 9.6: ARC-SLx

VA 1 DP

The portable pin sensor can be temporarily connected to the I/O units. It is used to improve safety when working with live switchgear, for example, Attach the sensor close to the working area, for example in the breast pocket of the maintenance man.

A pin sensor operates in the same way as a fixed arc sensor. The only difference is free mobility within the limits of the connecting cable.

VIOen M/A001

Figure 9.7: Pin sensor VA 1 DP

To avoid faulty tripping, disconnect the pin sensor from the system immediately after use.

62

10

10 Order information VAM I/O units

Order information

Order code

VAM 3LSE

VAM3LXSE

VAM4CSE

VAM4CDSE

VAM10LSE

VAM10LDSE

VAM12LSE

VAM12LDSE

VAMP4RSE

VA 1 DA-6

VA 1 DA-20

VA 1 DT-6

VA 1 DP-5

VA 1 DP-5D

VA 1 EH-6

VA 1 EH-20

ARC SLm-x

VX001-xx

VX031-5

VX052-3

VX054-3

VYX001

VYX002

VSE001PP

VSE002

VPA3CG

Explanation Note

Fiber sensor I/O unit (VAMP221) 3 fiber loops, 1 trip relay

Fiber sensor I/O unit (VAMP221) 3 fiber loops, 1 trip relay, adjustable sensitivity

Current I/O unit (VAMP221)

Current I/O unit (VAMP221)

3 current inputs, 1 trip relay

3 current inputs, 1 trip relay, flush mounting

Point sensor I/O unit (VAMP221) 10 sensor inputs, 1 trip relay

Point sensor I/O unit (VAMP221) 10 sensor inputs, 1 trip relay, flush mounting

Point sensor I/O unit (VAMP221) 10 sensor inputs, 3 trip relays

Point sensor I/O unit (VAMP221) 10 sensor inputs, 3 trip relays, flush mounting

Trip multiplier relay

Arc Sensor

4 x NO, 4 x NC, 2 groups

Cable length 6m

Arc Sensor

Temperature sensor

Portable arc sensor

Portable arc sensor

Cable length 20m

Cable length 6m

Cable length 5m

Cable length 5m

Arc sensor (pipe type)

Arc sensor (pipe type)

Fiber sensor, 8000 lx

Cable length 6m

Cable length 20m x= fiber length (2

Modular cable VAM <-> VAM

(xx= cable length [m]

Extension cable for VA1 DP-5D

USB programming cable

(VAMPSET)

Interface cable to VPA 3CG

(Profibus module) for RS-232

Surface mounting plate for sensors

Surface mounting plate for sensors

Fiber optic interface module

(plastic - plastic)

RS485 interface module

Profibus interface module

Preferred cable lengths (3

Cable length 5m

Cable length 3m

Cable length 3m

Z-shaped

L-shaped

RS-232 mode only

RS-232 mode only

Note 2: Fiber lengths 1 , 5, 10, 15, 20, 25, 30, 35, 40, 50 or 70 m

Note 3: Cable lengths 1, 3, 5, 7, 10, 15, 20, 25 & 30 m

VIOen M/A001 63

VAM I/O units

11

11 Glossary

Glossary

Term

BI

BO

Document file

FPGA

HMI

IED

LCD

LED

Local HMI

PC

VAMPSET

Description

Binary input

Binary output

Stores information about the IED settings, events and fault logs.

Field-programmable gate array

Human-machine interface

Intelligent electronic device

Liquid crystal display

Light-emitting diode

IED front panel with display and push-buttons

Personal computer

Configuration tool for VAMP protection devices

VIOen M/A001 64

We reserve the right to changes without prior notice

VAMP Ltd.

Street address:

Post address:

Yrittäjänkatu 15

P.O. Box 810

FI-65101 Vaasa

Phone:

Fax:

Internet: email:

+358 20 753 3200

+358 20 753 3205 www.vamp.fi

[email protected]

Customer Care Centre

http://www.schneider-electric.com/CCC

Schneider Electric

35 rue Joseph Monier

92506 Rueil-Malmaison

FRANCE

Phone: +33 (0) 1 41 29 70 00

Fax: +33 (0) 1 41 29 71 00 www.schneider-electric.com

Publication version: VIOen M/A001

Publishing: Schneider Electric

10/2012

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement