170 ENT 110 00

Ethernet Communication Adapter

User Guide

870 USE 112 00

Rev.: 1.0

07/98

Data, Illustrations, Alterations

Data and illustrations are not binding. We reserve the right to alter products in line with our policy of continuous product development. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us using the form on one of the last pages of this publication.

Training

Schneider Automation offers suitable further training on the system.

Hotline

See addresses for the Technical Support Centers at the end of this publication.

Trademarks

All terms used in this publication to denote Schneider Automation products are trademarks of Schneider Automation Incorporated.

All other terms used in this publication to denote products may be registered trademarks and/or trademarks of the corresponding corporations.

Microsoft and MS-DOS are registered trademarks of Microsoft Corporation,

Windows is a brandname of Microsoft Corporation in the USA and other countries.

IBM is a registered trademark of International Business Machines Corporation.

Intel is a registered trademark of Intel Corporation.

Copyright

All rights are reserved. No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, including copying, processing or by online file transfer, without permission in writing by Schneider

Automation Incorporated. You are not authorized to translate this document into any other language.

ã 1998 Schneider Automation Incorporated. All rights reserved.

870--USE--112--00

Contents

Contents

TSX Momentum

Ethernet Communication Adapter

170 ENT 110 00 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.1

Product Overview

1.1.1

Function

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.1.2

Physical Structure

1.1.3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Operating Voltages and Error Control

1.1.4

Mapping Data to I/O Base Field Terminals

1.1.5

Managing Throughput to I/O Bases

1.1.6

Specifications

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2

Example: Data Turnaround Time

1.3

Status Indicators

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.4

Connecting to the Network

1.4.1

Network Connector

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.4.2

1.5

Network Labels: Global Address and IP Address

Placing the Adapter into Service

1.5.1

Initialization and Self--Tests

. . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5.2

Assigning an Ethernet IP Address

1.5.3

Identifying the I/O Base

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5.4

Storing the IP Address in the Adapter

1.6

Replacing an Adapter

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.6.1

Erase the Stored IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.6.2

Remove Operating Power and Disconnect the Adapter . . . . . . . . . . . . . . . . . .

1.6.3

Install the New Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Communicating With the Adapter . . . . . . . . . . . . . . . . . . . . . . .

2.1

Communication Access Registers

2.1.1

Data Registers

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1.2

Configuration Registers

2.1.3

Status Registers

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Test Program: Source Code . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1

Source: response.java

3.2

Source: test1.txt

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

9

10

8

9

10

10

10

7

8

8

7

7

4

6

3

3

3

2

2

2

2

11

12

13

13

15

19

20

28 i

Breite: 178 mm

Höhe: 216 mm

TSX Momentum

Ethernet Communication Adapter

170 ENT 110 00

1

This Communication Adapter can be connected to any TSX Momentum I/O base to create a functional I/O module. It provides direct connection to the Ethernet network, enabling an Ethernet host to communicate with field devices wired to the

I/O base terminals.

Figure 1 shows the layout of a typical adapter and I/O base.

Figure 1 Communication Adapter with TSX Momentum I/O Base

Side

View

Communication

Adapter

I/O Base

Front

View

Ethernet network port

Communication

Adapter

I/O Base

This chapter describes:

H

Product Overview

H

Example: Data Turnaround Time

H

Status Indicators

H

Connecting to the Network

H

Placing the Adapter into Service

H

Replacing an Adapter

1

2

Ethernet Communication Adapter

1.1

1.1.1

1.1.2

1.1.3

Product Overview

Function

This adapter is installed on any TSX Momentum I/O base to form a complete I/O module that communicates on an Ethernet network. A programmable controller or other host device on the network can then read from the input terminals and write to the output terminals of the I/O base.

The adapter communicates with host devices using Modbus Application Protocol with TCP/IP packets. It supports both Ethernet II and IEEE 802.3 framing.

For information about using Modbus Application Protocol with TCP/IP, refer to the

Ethernet TCP/IP Module User Guide, part number 840 USE 107. Details of the

Modbus protocol are provided in the Modbus Protocol Reference Guide, part number PI--MBUS--300.

For information about the application and field wiring of I/O bases, refer to the TSX

Momentum I/O Bases User Manual, part number 870 USE 002.

Physical Structure

Each adapter connects to the internal communication connector of its I/O base.

Clips lock the adapter in place and can be released with a common screwdriver to remove the adapter. The user can fill out the front panel wiring label (supplied with the I/O base) to identify the wiring connections at the I/O base terminals.

The adapter is considered open equipment and must be mounted in an enclosure that is approved for the site at which it is installed.

Operating Voltages and Error Control

Power for the adapter and I/O base is provided by the user at the field location.

The adapter receives its operating voltage through its I/O base internal connection.

The adapter monitors its voltage and goes offline to the network if the voltage is not within tolerance.

Ethernet Communication Adapter

1.1.4

1.1.5

1.1.6

Mapping Data to I/O Base Field Terminals

Data is mapped between the application and I/O base field terminals in the IEC format. Refer to the TSX Momentum I/O Bases User Manual, 870 USE 002 for the mapping diagrams for the I/O bases.

Managing Throughput to I/O Bases

To ensure deterministic timing of I/O messages, you should design your network to include only your application host and your I/O base communication adapters.

Adding other kinds of devices, such as user interfaces or programmers, can cause variables in I/O message timing when those devices access the network.

Specifications

Table 1 Network Specification

Description

Ethernet interface

Specification

Compliant with the STP or UTP 100 ohm connection.

Table 2 Agency Approval

Agency

UL 508

CAN/CSA C22.2NO.142

CE Mark

Status

Approved

Approved

Approved

3

4

Ethernet Communication Adapter

1.2

Example: Data Turnaround Time

Figure 2 shows an example of a control loop constructed to measure the data turnaround time at the field terminals of a pair of I/O bases.

A host PC running the test program is connected by Ethernet to two adapters with discrete I/O bases. The field output terminals of the output base are wired directly to the field input terminals of the input base. An oscilloscope is used to time the switching of the field signals.

Figure 2 Example: Data Turnaround Time

Host PC running

Test

Program

Ethernet

Adapter with

Discrete

Input

Terminals

Field

Wiring

Oscilloscope

Adapter with

Discrete

Output

Terminals

The test program is a Java loop that performs this sequence:

1. Continuously reads the input terminals of the input base module.

2. Writes an output terminal to a new (ON or OFF) condition.

3. When a changed state is received from the inputs, toggles the outputs.

The oscilloscope measures the time duration of the ON state of the outputs.

Figure 3 Data Turnaround Time Measurement

Time measured here

ON

OFF

Ethernet Communication Adapter

Tests were conducted on two separate NT workstations with these configurations:

H

200 MHz, 96 MB RAM

H

100 MHz, 32 MB RAM

Table 3 shows the measured data turnaround times. The results indicate that the major factor affecting data timing is the speed of the loop execution in the host.

Table 3 Results: Data Turnaround Time

Networked

Devices

2

2

2

64

64

64

64

64

64

Network

Loading

10%

40%

70%

10%

40%

70%

10%

40%

70%

Minimum

Time

5 ms

5 ms

6 ms

6 ms

6 ms

6 ms

25 ms

25 ms

26 ms

Maximum

Time

9 ms

9 ms

9 ms

8 ms

12 ms

13 ms

30 ms

30 ms

30 ms

Average

Time

Host CPU

Speed and RAM

6.2 ms 200 MHz 96 MB

6.2 ms 200 MHz 96 MB

6.3 ms 200 MHz 96 MB

6.8 ms 200 MHz 96 MB

8.4 ms 200 MHz 96 MB

8.2 ms 200 MHz 96 MB

26.7 ms 100 MHz 32 MB

26.7 ms 100 MHz 32 MB

27.0 ms 100 MHz 32 MB

Java source code for the test program is reproduced in Chapter 3.

5

6

Ethernet Communication Adapter

1.3

Status Indicators

The adapter has two front panel indicators showing its operating status.

Figure 4 Indicators

Adapter

Status

Network

Activity

Table 4 RUN Indicator: Adapter Status

Indicator State

On (steady)

3 Flashes, long Off

4 Flashes, long Off

5 Flashes, long Off

6 Flashes, long Off

7 Flashes, long Off

8 Flashes, long Off

Flashing constantly

Status

Normal operation: power is present from I/O base, and the adapter is ready for network communication.

No Link: The network cable is not connected or is defective.

No MAC Address: The adapter’s MAC address is not set.

Internal hardware problem.

No IP Address: The adapter is attempting to obtain an IP

Address from a BOOTP server.

The adapter’s internal executive program has started, but cannot initialize the I/O base.

The adapter has obtained an IP address, but does not have a valid executive program.

The adapter’s executive program has failed during execution.

Adapter is downloading its executive program.

Table 5 LAN ACT Indicator: Network Activity

Indicator State

Flashing

Off

Status

Normal operation: Adapter detects network activity.

Flashing rate indicates the amount of activity.

May appear steadily On if network activity is high.

Adapter is not detecting any network activity.

Ethernet Communication Adapter

1.4

1.4.1

1.4.2

Connecting to the Network

Network Connector

The adapter has one RJ--45 connector for a 10Base--T UTP/STP (Unshielded or

Shielded Twisted Pair) cable. The adapter should be cabled directly to the

Ethernet hub.

Figure 5 Network Connector

RJ--45

10Base--

T for

Unshielded or Shielded

Twisted Pair (UTP/STP) cable

Network Labels: Global Address and IP Address

The adapter has two labels mounted on its end panels. One label identifies the adapter’s IEEE Global Address (MAC address). The other identifies its Internet

Protocol address (IP address).

The installer records the Global Address and gives it to the network administrator for use in establishing an IP address for the adapter during the BOOTP process at startup. When the IP address has been assigned, the administrator gives this address to the installer who writes it onto the adapter’s IP address label.

Figure 6 Adapter Labels: Global Address and IP Address

Labels on end panels

Adapter’s Global Address Adapter’s IP Address

7

8

Ethernet Communication Adapter

1.5

1.5.1

1.5.2

Placing the Adapter into Service

Initialization and Self--Tests

When the adapter receives its initial operating power from its I/O base, it performs internal initialization and self--tests. If the tests fail, the RUN indicator flashes to indicate the failure reason, if possible, and the adapter remains offline. If the tests are successful, the adapter attempts to obtain its Ethernet IP address.

Assigning an Ethernet IP Address

Overview: Address Assignment

A BOOTP server is required to assign a new IP address to the adapter. After the server assigns the IP address, the server application can issue a command to the adapter to cause it to store the address internally.

If the adapter has stored its address and is re--initialized (for example, following a power loss), the adapter will again issue requests for an address from a BOOTP server. If a server responds with an address, the adapter will use it that address.

If a server does not respond, the adapter will revert to its stored address.

Requesting the IP Address

After completing its initialization, the adapter requests its Ethernet IP address from a BOOTP server. The adapter uses its MAC address with the BOOTP protocol over the Ethernet network.

Receiving the Server Response

The adapter will wait ten seconds for a BOOTP server to respond with the adapter’s IP address. If the server response is received, the adapter will use that address as long as power remains applied to the adapter.

Warning

DUPLICATE ADDRESS HAZARD Having two or more devices with the same IP address can cause unpredictable operation of your network.

Ensure that this device will receive a unique IP address. Failure to observe this precaution can result in injury or equipment damage.

Retries to the Server

If a BOOTP server response is not received, the adapter will retry the request six times: three times using the Ethernet II framing type, and three times using the

802.3 framing type.

Ethernet Communication Adapter

1.5.3

1.5.4

Server Response Not Received (IP Address Previously Stored)

If the adapter receives no response to any of its attempts to obtain an IP address, and if an address has been previously stored by a Modbus Write command from the application, the adapter will then use that stored address.

Server Response Not Received (IP Address Not Stored)

If the adapter receives no response to any of its attempts to obtain an IP address, and if it does not have any stored address, the adapter will continue to retry the

BOOTP request every 30 seconds. During this time it will flash its RUN indicator in the ‘requesting’ pattern (a sequence of five flashes).

Identifying the I/O Base

After the adapter receives its IP address, it runs an internal procedure to identify its I/O base. If the procedure fails, the adapter’s RUN indicator flashes a failure pattern (six flashes) and will remain offline.

If the I/O base is successfully identified, the adapter is ready to communicate using the Modbus protocol over TCP/IP.

Storing the IP Address in the Adapter

The adapter has a non--volatile RAM area for storing its assigned IP address.

If the application requires the adapter to retain its current IP address, the application must issue a Modbus Write command to write a boolean value into a specific register in the adapter to cause the address to be stored. The adapter’s default state is to not store the address.

Section 2.1 describes how to store the IP address and how to determine if an address has been previously stored.

9

Ethernet Communication Adapter

1.6

1.6.1

1.6.2

1.6.3

Replacing an Adapter

Erase the Stored IP Address

Before removing any adapter from service, you should clear its IP address.

The adapter has a non--volatile RAM area for storing its assigned IP parameters.

The parameters are retained when power is removed from the adapter, and will remain permanently in the adapter when it is removed from service. If the adapter is subsequently returned to service it would be possible for it to cause unspecified activity on your network. You should therefore erase the current parameters before removing the adapter from service.

The adapter has an internal register which defines the boolean state (saved or not saved) of its IP parameters. The register can be read by the application, and it can be written into to cause the adapter to clear the parameters.

Warning

DUPLICATE ADDRESS HAZARD Having two or more devices with the same IP address can cause unpredictable operation of your network.

Before removing any adapter from service, you should first write a logical 0

(zero) into the parameter storage register to clear the adapter’s stored parameters. This will rreduce the possibility of a duplicate IP address appearing on your network if the adapter is later restored to service.

Failure to observe this precaution can result in injury or equipment damage. Refer to Section 2.1 for a description of the adapter’s registers, including how to clear its stored parameters.

Remove Operating Power and Disconnect the Adapter

Before removing the adapter, remove the operating power from the I/O base.

Then disconnect the Ethernet cable, and remove the adapter from the base.

Install the New Adapter

Mount the new adapter onto the I/O base, following the instructions supplied with the new adapter. Record the new adapter’s IEEE Global Address (MAC address), and use it to configure an Internet Protocol address (IP address) for the adapter.

Section 1.5 describes how to place the new adapter into service using the

Ethernet BOOTP protocol.

10

Communicating With the Adapter

2

H

Communication Access Registers

H

Data Registers

H

Configuration Registers

H

Status Registers

11

Communicating With the Adapter

2.1

Communication Access Registers

Each adapter contains three groups of registers that enable the application to communicate with the I/O base module. The application accesses the registers to transfer input or output data at the I/O base module’s field terminals, to set or retrieve the module’s configuration, or to monitor its status.

All of the registers can be accessed as 4XXXX references by MSTR function blocks in the application program.

Figure 7 Communication Adapter Access Registers

ETHERNET

NETWORK

STARTING

REFERENCE

(Hex / Decimal)

LENGTH

(16-Bit Words)

DATA REGISTERS

DATA INPUT

(Read Only)

DATA OUTPUT

(Write Only)

40001 / 400001

40001 / 400001

Module dependent

Module dependent

CONFIGURATION REGISTERS

MODULE TIMEOUT

(Read or Write)

4F001 / 461441

MODULE OWNERSHIP

(Read or Write)

4F401 / 462465

1

6

IP ADDRESS SAVED

(Read or Write)

STATUS REGISTERS

MODULE STATUS

(Read Only)

MODULE ASCII HEADER

(Read Only)

4F411 / 462481

4F801 / 463489

4FC01 / 464513

1 on Write

2 on Read

13

Module dependent

12

Communicating With the Adapter

2.1.1

2.1.2

Data Registers

40001 hex ---- Data Input or Output

Starting reference 40001 is used to address input data from field inputs and output data to field outputs. Data is transferred in the IEC format. Mapping between the controller’s data registers and I/O base field terminals is unique to each base, and is described in the TSX Momentum I/O Bases User Manual, 870 USE 002 00.

Configuration Registers

4F001 hex ---- Outputs Holdup Timeout Value

Reference 4F001 specifies the amount of time that outputs will be held in their current state, if they are not updated by a new Modbus Write command. If the module’s holdup time expires before a new write command is received, all outputs are set to logical 0 (zero).

The field length is one word. The timeout value is expressed in units of 10 milliseconds, with a minimum register value of 30 (300 milliseconds) and maximum value of 6000 (60 seconds). The default value is 100 (1 second).

The register’s contents can be read using a Modbus Read command.

4F401 hex ---- Ownership of Write Privilege

When the adapter first receives power, it will give sole write privilege to the first node that writes to it using the Modbus Write command. The adapter maintains an internal 60--second timer for handling the write privilege, and will reserve sole privilege to that node as long at the node continues to write within 60--second intervals to the adapter.

Starting reference 4F401 specifies the IP addresses of up to three more nodes which may concurrently own write privilege to the adapter. A node which currently owns the write privilege may write up to three IP addresses (2 words per address) to the adapter starting at 4F401. With those addresses stored, any of those three nodes may then write to the adapter in addition to the original privileged node.

This allows up to four nodes to concurrently own write privilege to the adapter.

If writes continue to occur within the 60--second interval from any of the three privileged nodes, no other node may write to the adapter. If the timer is allowed to expire, any node may write to the adapter.

Note that this 60-second Write Privilege timer is separate from the Outputs Holdup timer, and applies only to the write privilege. The 60--second time is a fixed value and is not accessible to the application.

Any node may read the input data or status information from the adapter.

13

Communicating With the Adapter

4F411 hex ---- IP Address Saved

This reference serves a dual purpose, depending on whether the application issues a Modbus Write command or a Modbus Read command.

Modbus Write Command: Save or Clear IP Address For a Modbus Write command the reference is treated as a one--word register, with the application writing one word of data. The Modbus Write data may consist of a 1 or 0 (zero), which causes the adapter to save or clear its current IP address.

If a data 1 is written to the reference, the adapter will save its currently assigned IP address in its non--volatile RAM. If a new initialization occurs and the adapter cannot find a BOOTP server, the adapter will use this saved address.

If a data 0 is written to the reference, the current IP address will be erased.

Warning

DUPLICATE ADDRESS HAZARD Having two or more devices with the same IP address can cause unpredictable operation of your network.

Before removing any adapter from service, you must first write a logical 0

(zero) into register 4F411 to clear the adapter’s stored address. This will reduce the possibility of a duplicate IP address appearing on your network if the adapter is later restored to service. Failure to observe this precaution can result in injury or equipment damage.

Warning

THE ADAPTER INITIALIZES WHEN THESE CONTENTS CHANGE Any change of state of this reference’s contents will cause the adapter to re--initialize.

Modbus Read Command: Get Current IP Address For a Modbus Read command the reference is treated as a two--word register, with the application reading two words of data. If the adapter has IP parameters saved in its non--volatile RAM, it will return its current IP address to the Modbus Read command, indicating that it has stored parameters. If IP parameters are not currently saved, the adapter returns all ones (FFFFFFFF hex) to the Read.

14

Communicating With the Adapter

2.1.3

Status Registers

4F801 hex ---- Module Status Block

These registers provide information about the module’s revision level and current operating parameters.

The block’s length is 13 words. The registers can be read by the application, but cannot be written into.

Table 6 Module Status Block Layout

Reference (hex) Purpose

4F801 Length of status block (words)

4F802

4F803

4F804

4F805

4F806

4F807

4F808

4F809

4F80A

4F80B

4F80C

4F80D

I/O module quantity of input words

I/O module quantity of output words

I/O module ID number

Communication Adapter revision number

Contents

13 decimal

Module dependent

Module dependent

Module dependent

Format: XR where:

X = upper 4 bits, always 0000

R = lower 12 bits, defining the revision as 3 hex characters.

Example:

100 hex = Rev. 1..00

200 hex = Rev. 2.00

ASCII header block length (words)

Last IP address to communicate with this adapter in most recent Modbus transaction (low word of 2 words -- see

4F80D)

Module dependent

Node address dependent

Remaining ownership reservation time milliseconds

Remaining outputs holdup time

I/O module health

I/O module last error value

I/O module error counter

Last IP address to communicate with this adapter in most recent Modbus transaction (high word of 2 words -- see

4F807) milliseconds

8000 hex = healthy

0000 hex = not healthy

Module dependent

Error count 0000 ... FFFF hex

Node address dependent

15

Communicating With the Adapter

4FC01 hex ---- Module ASCII Header Block

These registers contain an ASCII text description of the module. The registers can be read by the application, but cannot be written into.

The block length depends upon the type of I/O base to which the adapter is connected. The maximum length is 64 bytes of ASCII characters, corresponding to a length of 8 ... 32 words as specified in word 6 of the Module Status Block (at reference 4F806).

The block contains labels to identify the quantities of input and output words, and the ID code of the I/O base. You can parse the block contents to extract this information into your application.

Table 7 ASCII Header Block Layout

ASCII Characters

ETHERNET

20 hex (32 decimal)

IEC

20 hex (32 decimal)

DIG:

EXP:

ANA:

20 hex (32 decimal) inlen=

n

20 hex (32 decimal) outlen=

n

20 hex (32 decimal)

ID=0x

nnnn

Meaning

Identifies Ethernet Communication Adapter space

Data is transferred with I/O base in IEC format space

Digital module (ID range: XX00 ... XX7F hex)

Expert module (ID range: XX80 ... XXBF hex)

Analog module (ID range: XXC0 ... XXFE hex) space

Input words (n = quantity of words, decimal) space

Output words (n = quantity of words, decimal) space

Module ID code (nnnn = ID code, hex)

Figure 8 shows examples of the ASCII Header Block contents for two I/O bases.

16

Communicating With the Adapter

Figure 8 Examples: ASCII Header Block

170 ADM 350 00 (Discrete 16--Point Input, 16--Point Output Module)

ETHERNET IEC DIG: inlen=1 outlen=1 ID=0x0002

Data bits transferred in IEC format

Module ID

Digital module

Input words: 1

Output words: 1

170 AAO 120 00 (Analog 4--Channel Output Module)

ETHERNET IEC ANA: inlen=0 outlen=5 ID=0x01C3

Data bits transferred in IEC format

Module ID

Analog module

Input words: 0

Output words: 5

(includes 1 parameter word)

17

Test Program: Source Code

3

H

Source: response.java

H

Source: test1.txt

19

Test Program: Source Code

3.1

Source: response.java

This Java program furnishes the looping for data throughput testing as described in Chapter 1.

It reads the text file test1.txt to get the target addresses and Modbus commands for communicating with the input and output communication adapters.

The file’s contents follow:

// response.java, 6/17/98. This is a variation of mbtest.java. This code

// will send a (write) command to one address and a separate command (read)

// to the second address. It will loop performing the read each time, but

// only doing the write when the read command detects a change in the input

// that was read. The loop counter is set as a constant. An improvement

// would be to pass it in the command line. The purpose of this program

// is to use an oscilloscope to measure the time elapsed between the input

// going high, and the output responding to it. The IP addresses of the IO

// modules, and the write and read commands are read from a text file.

//--------------------------------------------------------------------------

// mbtest.java 4/26/96

// minimal application to communicate and do performance measurement

// to the Quantum Ethernet module using ASA registered TCP port and

// MODBUS_ENCODING PDU format

// variant 5/14/96 to allow comparison of responses to the same request from 2 targets

// variant 5/24/96 to allow specification of independent addresses on the 2 targets

//

// and to allow time delay in script

11/11/97 generate ’usage:’ and handle blank lines as comment import java.io.* ; import java.net.* ; class mbtest { public static void main(String argv[]) { if (argv.length<1) {

System.out.println(”usage: java mbtest scriptfile > reportfile\n”+

”eg.

java mbtest script.txt > result.txt”);

} else try {

20

Test Program: Source Code int dolog = 1; int keybuf; long skipcnt; int ioCount; byte expect; int first;

DataInputStream di = new DataInputStream(new FileInputStream(argv[0]));

String cmd;

// analyse ’target’ lines. Note must be followed by ’address’

// note this version of the program requires that the ’target’

// lines be the first 1 or 2 lines of the script

String target;

Socket es=null;

OutputStream os=null;

FilterInputStream is=null; cmd = di.readLine().trim(); if (cmd.startsWith(”target”)) { target = cmd.substring(6).trim();

System.out.println(”mbtest: connecting to ”+target); es = new Socket(target,502); os= es.getOutputStream(); is = new BufferedInputStream(es.getInputStream()); cmd = di.readLine().trim();

}

String target2;

Socket es2=null;

OutputStream os2=null;

FilterInputStream is2=null; if (cmd.startsWith(”target”)) { target2 = cmd.substring(6).trim();

System.out.println(”mbtest: connecting to ”+target2); es2 = new Socket(target2,502); os2= es2.getOutputStream(); is2 = new BufferedInputStream(es2.getInputStream()); cmd = di.readLine().trim();

} int address = 1; int address2 = 1; byte obuf[] = new byte[261]; byte obuf2[] = new byte[261]; byte ibuf[] = new byte[261];

21

Test Program: Source Code byte ibuf2[] = new byte[261]; obuf[0] = 0; obuf[1] = 0; obuf[2] = 0; obuf[3] = 0; obuf[4] = 0; obuf2[0] = 0; obuf2[1] = 0; obuf2[2] = 0; obuf2[3] = 0; obuf2[4] = 0; for (;;) { if (cmd.startsWith(”;”)) {

System.out.println(cmd); cmd = di.readLine().trim(); continue;

} if (cmd.startsWith(”address2”)) { address2 = Integer.parseInt(cmd.substring(9)); cmd = di.readLine().trim(); continue;

} if (cmd.startsWith(”address”)) { address = Integer.parseInt(cmd.substring(8)); address2 = address; cmd = di.readLine().trim(); continue;

} if (cmd.startsWith(”quit”)) break;

// handle script delay if (cmd.startsWith(”wait”)) { int delayTime = Integer.parseInt(cmd.substring(5)); if (delayTime < 0 || delayTime > 30000) {

System.out.println(”mbtest: warning: invalid delay time - ”+delayTime+”

- ignoring”);

} else {

Thread.sleep(delayTime);

} cmd = di.readLine().trim(); continue;

}

22

Test Program: Source Code if (os == null || os2 == null ) {

System.out.println(”mbtestt: abort: no connection established to target”); break;

}

// now convert to a byte string

// assume format is hex separated by whitespace int ix = 0; // output index = number of bytes found int sx = 0; // input index = substring position int l = cmd.length(); while (sx < l) { int ex; ex = cmd.indexOf(’ ’,sx); if (ex<0) ex = l; int bval = Integer.parseInt(cmd.substring(sx,ex), 16); obuf[7+ix++] = (byte) bval; sx = ex+1;

} if (ix == 0) {

// handle blank line as comment

System.out.println(cmd); cmd = di.readLine().trim(); continue;

} obuf[5] = (byte) (ix + 1); obuf[6] = (byte) address;

//----------------------------------------------------------------

// read the command for the second target

//---------------------------------------------------------------cmd = di.readLine().trim(); ix = 0; // output index = number of bytes found sx = 0; // input index = substring position l = cmd.length(); while (sx < l) { int ex; ex = cmd.indexOf(’ ’,sx); if (ex<0) ex = l; int bval = Integer.parseInt(cmd.substring(sx,ex), 16); obuf2[7+ix++] = (byte) bval; sx = ex+1;

}

23

Test Program: Source Code

//

// if (ix == 0) {

// handle blank line as comment

System.out.println(cmd); cmd = di.readLine().trim(); continue;

} obuf2[5] = (byte) (ix + 1); obuf2[6] = (byte) address; cmd = di.readLine().trim();

} // end of FOR loop reading the input text

// purge the key buffer

//for( ; ; ) {

//keybuf = System.in.available();

//if( keybuf == 0 )

//break;

//keybuf = System.in.read();

//} keybuf = System.in.available(); if( keybuf > 1 ) { skipcnt = keybuf;

System.out.println(”skip: ”+keybuf ); do {

System.in.read(); keybuf--;

} while( keybuf > 1 );

}

System.out.println(”Press any key to stop”); expect = 0x40; first = 1;

// Now loop performing the IO for( ; ; ) { // loop doing IO

//for( ioCount=0; ioCount < 500; ioCount++ ) { // loop doing IO int c = 0; int c2 = 0; int ix; keybuf = System.in.available(); if( dolog == 1 )

System.out.println(”keybuf = ”+keybuf ); if( keybuf >= 1 ) { keybuf = System.in.read();

24

Test Program: Source Code break;

} ix = (int)obuf[5] - 1; os.write(obuf,0,ix+7); c = is.read(ibuf,0,261); if (c<=0) {

System.out.println(”mbtest: abort: detected unexpected close of channel”); break;

} while (c<7 || c<(6 + (0xff & (int)(ibuf[5])))) {

System.out.println(”mbtest: warning: response appears fragmented”); int cx = is.read(ibuf,c,261-c); if (cx<=0) {

System.out.println(”mbtest: warning: response incomplete”); break;

} c += cx;

}

// verify input length against fragmentation if (((int)(ibuf[5])&0xff) != (c-6)) {

System.out.println(”mbtest: warning: response length mismatch”);

} if( dolog == 1 ) { log_buf(obuf, ix+7, ”>”); log_buf(ibuf, c, ”<”);

}

// write to the second target, using the 2nd buffer

// wait until the input has changed if ( first == 1 || ( ibuf[12] & 0x40 ) == expect ) { first = 0; ix = (int)obuf2[5] - 1;

// if input bit 0x40 is on, turn on output bit 0x01 if( expect == 0x40 ) { expect = 0; obuf2[16] = (byte) (obuf2[16] & 0xbf); // bit 40 off obuf2[16] = (byte) (obuf2[16] | 0x01); // bit 01 on

} else { expect = 0x40; obuf2[16] = (byte) (obuf2[16] | 0x40); // bit 40 on obuf2[16] = (byte) (obuf2[16] & 0xfe); // bit 01 off

25

Test Program: Source Code

} os2.write(obuf2,0,ix+7); channel”); break;

} while (c2<7 || c2<(6 + (0xff & (int)(ibuf2[5])))) {

System.out.println(”mbtest: warning: response appears fragmented”); int cx2 = is2.read(ibuf2,c2,261-c2); if (cx2<=0) {

System.out.println(”mbtest: warning: response incomplete”); break;

} c2 += cx2;

} if (((int)(ibuf2[5])&0xff) != (c2-6)) {

System.out.println(”mbtest: warning: response length mismatch”);

} if( dolog == 1 ) { log_buf(obuf2, ix+7, ”>”); log_buf(ibuf2, c2, ”<”);

}

// check only the modbus response for equality (ignore address)

//if (buf_diff(c, ibuf, c2, ibuf2)) {

//System.out.println(”************* different”);

//}

} if( dolog == 1 )

System.out.println();

} // end of FOR loop doing IO

} catch (Exception e) { System.out.println(”mbtest: unexpected exception:”+e); }

} c2 = is2.read(ibuf2,0,261); if (c2<=0) {

System.out.println(”mbtest: abort: detected unexpected close of static boolean buf_diff(int c1, byte [] b1, int c2, byte [] b2) {

// check only the modbus response for equality (ignore address) if (c1 != c2) return true; int i; for (i=7; i<c1; i++) { if (b1[i] != b2[i]) return true;

26

Test Program: Source Code

}

} return false;

} public static void log_buf(byte buf[], int len, String prefix) {

System.out.print(prefix); int i; for (i=0; i<len; i++) {

System.out.print(” ”+Integer.toString((buf[i]>>4)&0xf, 16)+

Integer.toString(buf[i]&0xf, 16));

}

System.out.println();

}

27

Test Program: Source Code

3.2

Source: test1.txt

This file contains the target addresses of the input and output communication adapters used in the test loop. The host server must resolve these to the IP addresses of the adapters.

The file also contains the input and output Modbus commands to the adapters for reading the base module inputs and writing the base module outputs.

The file’s contents follow: target eio4 target eio2

; input command followed by output command

3 0 0 0 2

10 0 0 0 2 4 00 00 00 40 quit

28