Rockwell Automation Compact 16-Point AC/DC relay output module Installation Instructions
Below you will find brief information for relay output module Compact 16-Point AC/DC. The Compact™ 16-Point AC/DC Relay Output Module (Catalog Number 1769-OW16) is a 16 point relay output module that can control AC or DC loads. The module has 2 isolated groups of 8 points each. This allows you to mix both AC and DC loads on one module. It can be attached to the controller or an adjacent I/O module before or after mounting. For mounting instructions, see "Panel Mounting" on page 5, or "DIN Rail Mounting" on page 7. The module can be replaced while the system is mounted to a panel (or DIN rail). You can use the bare wire or a spade lug. The terminals will accept a 6.35 mm (0.25 in.) spade lug.
Advertisement
Advertisement
Installation Instructions
Compact™ 16-Point AC/DC Relay Output Module
(Catalog Number 1769-OW16)
Inside
Mounting Expansion I/O .......................................................................... 5
Replacing a Single Module within a System .......................................... 7
Field Wiring Connections......................................................................... 8
I/O Memory Mapping ............................................................................ 11
1769-OW16 Configuration File .............................................................. 12
Spare/Replacement Module Parts ........................................................ 13
Hazardous Location Considerations ...................................................... 17
Environnements dangereux ................................................................... 17
Publication 1769-IN062A-EN-P - December 2001
2 Compact™ 16-Point AC/DC Relay Output Module
Module Description
The 1769-OW16 is a 16 point relay output module that can control AC or DC loads.
The module has 2 isolated groups of 8 points each. This allows you to mix both AC and DC loads on one module.
5a
9
7a
8a
7b
1
10a
10b
10
8b
7b
7a
2a
DANGER
Do Not Remove RTB Under Power
Unless Area is Non-Hazardous
VAC-VDC1
Out 0
Out 1
Out 2
Out 3
Out 4
Out 5
Out 6
Out 7
VAC-VDC2
Out 8
Out 9
Out 10
Out 11
Out 12
Out 13
Out 15
Out 14
Ensure Adjacent
Bus Lever is Unlatched/Latched
Before/After Removing/Inserting Module
1769-OW16
3
4
2b
6
5b
Item Description
1
bus lever
(with locking function)
2a
upper panel mounting tab
2b
lower panel mounting tab
3
4
I/O diagnostic LEDs (Logic Side) module door with terminal identification label
5a
movable bus connector with female pins
5b
stationary bus connector with male pins
6
nameplate label
7a
upper tongue-and-groove slots
7b
lower tongue-and-groove slots
8a
upper DIN rail latch
8b
lower DIN rail latch
9
write-on label (user ID tag)
10
removable terminal block (RTB) with finger-safe cover
10a
RTB upper retaining screw
10b
RTB lower retaining screw
Publication 1769-IN062A-EN-P - December 2001
Compact™ 16-Point AC/DC Relay Output Module 3
Module Installation
Compact I/O is suitable for use in an industrial environment when installed in accordance with these instructions. Specifically, this equipment is intended for use in clean, dry environments (Pollution degree 2
(1)
) and to circuits not exceeding
Over Voltage Category II
(2)
(IEC 60664-1).
(3)
Prevent Electrostatic Discharge
ATTENTION
!
Electrostatic discharge can damage integrated circuits or semiconductors if you touch bus connector pins. Follow these guidelines when you handle the module:
•
Touch a grounded object to discharge static potential.
•
Wear an approved wrist-strap grounding device.
•
Do not touch the bus connector or connector pins.
•
Do not touch circuit components inside the module.
•
If available, use a static-safe work station.
•
When not in use, keep the module in its static-shield box.
Remove Power
ATTENTION
!
Remove power before removing or inserting this module. When you remove or insert a module with power applied, an electrical arc may occur. An electrical arc can cause personal injury or property damage by:
• sending an erroneous signal to your system’s field devices, causing unintended machine motion
• causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance.
(1) Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that occasionally a temporary conductivity caused by condensation shall be expected.
(2) Over Voltage Category II is the load level section of the electrical distribution system. At this level transient voltages are controlled and do not exceed the impulse voltage capability of the product’s insulation.
(3) Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC) designations.
Publication 1769-IN062A-EN-P - December 2001
4 Compact™ 16-Point AC/DC Relay Output Module
System Assembly
The module can be attached to the controller or an adjacent I/O module before or
after mounting. For mounting instructions, see "Panel Mounting" on page 5, or "DIN
Rail Mounting" on page 7. To work with a system that is already mounted, see
"Replacing a Single Module within a System" on page 7.
The following procedure shows you how to assemble the Compact I/O system.
3
4
2
1
6
1
5
1. Disconnect power.
2. Check that the bus lever of the module to be installed is in the unlocked
(fully right) position.
3. Use the upper and lower tongue-and-groove slots (1) to secure the modules together (or to a controller).
4. Move the module back along the tongue-and-groove slots until the bus connectors (2) line up with each other.
5. Push the bus lever back slightly to clear the positioning tab (3). Use your fingers or a small screw driver.
6. To allow communication between the controller and module, move the bus lever fully to the left (4) until it clicks. Ensure it is locked firmly in place.
ATTENTION
!
When attaching I/O modules, it is very important that the bus connectors are securely locked together to ensure proper electrical connection.
Publication 1769-IN062A-EN-P - December 2001
Compact™ 16-Point AC/DC Relay Output Module 5
7. Attach an end cap terminator (5) to the last module in the system by using the tongue-and-groove slots as before.
8. Lock the end cap bus terminator (6).
IMPORTANT
A 1769-ECR or 1769-ECL right or left end cap must be used to terminate the end of the serial communication bus.
Mounting Expansion I/O
ATTENTION
During panel or DIN rail mounting of all devices, be sure that all debris (metal chips, wire strands, etc.) is kept from falling into the module. Debris that falls into the module could cause damage on power up.
!
Minimum Spacing
Maintain spacing from enclosure walls, wireways, adjacent equipment, etc. Allow
50 mm (2 in.) of space on all sides for adequate ventilation, as shown:
Side
Host Controller
Top
Bottom
Side
Panel Mounting
Mount the module to a panel using two screws per module. Use M4 or #8 panhead screws. Mounting screws are required on every module.
Publication 1769-IN062A-EN-P - December 2001
6 Compact™ 16-Point AC/DC Relay Output Module
Panel Mounting Using the Dimensional Template
Spacing for single-wide modules 35 mm (1.378 in.)
Spacing for one-and-a half-wide modules 52.5 mm (2.067 in.)
Refer to host controller documentation for this dimension.
Note: Overall hole spacing tolerance: ±0.4 mm (0.016 in.).
Locate holes every 17.5 mm (0.689 in.) to allow for a mix of single-wide and one-and-a-half-wide modules (e.g. 1769-OA16).
Panel Mounting Procedure Using Modules as a Template
The following procedure allows you to use the assembled modules as a template for drilling holes in the panel. If you have sophisticated panel mounting equipment,
you can use the dimensional template provided on page 6. Due to module
mounting hole tolerance, it is important to follow these procedures:
1. On a clean work surface, assemble no more than three modules.
2. Using the assembled modules as a template, carefully mark the center of all module-mounting holes on the panel.
3. Return the assembled modules to the clean work surface, including any previously mounted modules.
4. Drill and tap the mounting holes for the recommended M4 or #8 screw.
5. Place the modules back on the panel, and check for proper hole alignment.
6. Attach the modules to the panel using the mounting screws.
TIP
If mounting more modules, mount only the last one of this group and put the others aside. This reduces remounting time during drilling and tapping of the next group.
7. Repeat steps 1 to 6 for any remaining modules.
Publication 1769-IN062A-EN-P - December 2001
Compact™ 16-Point AC/DC Relay Output Module 7
DIN Rail Mounting
The module can be mounted using the following DIN rails: 35 x 7.5 mm (EN 50 022
- 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15).
Before mounting the module on a DIN rail, close the DIN rail latches. Press the DIN rail mounting area of the module against the DIN rail. The latches will momentarily open and lock into place.
Replacing a Single Module within a System
The module can be replaced while the system is mounted to a panel (or DIN rail).
1. Remove power. See attention note on page 3.
2. On the module to be removed, remove the upper and lower mounting screws from the module (or open the DIN latches using a flat-blade or phillips style screw driver).
3. Move the bus lever to the right to disconnect (unlock) the bus.
4. On the right-side adjacent module, move its bus lever to the right (unlock) to disconnect it from the module to be removed.
5. Gently slide the disconnected module forward. If you feel excessive resistance, check that the module has been disconnected from the bus, and that both mounting screws have been removed (or DIN latches opened).
TIP
It may be necessary to rock the module slightly from front to back to remove it, or, in a panel-mounted system, to loosen the screws of adjacent modules.
6. Before installing the replacement module, be sure that the bus lever on the module to be installed, and on the right-side adjacent module are in the unlocked (fully right) position.
7. Slide the replacement module into the open slot.
8. Connect the modules together by locking (fully left) the bus levers on the replacement module and the right-side adjacent module.
9. Replace the mounting screws (or snap the module onto the DIN rail).
Publication 1769-IN062A-EN-P - December 2001
8 Compact™ 16-Point AC/DC Relay Output Module
Field Wiring Connections
Grounding the Module
This product is intended to be mounted to a well-grounded mounting surface such as a metal panel. Additional grounding connections from the module’s mounting tabs or DIN rail (if used), are not required unless the mounting surface cannot be grounded. Refer to Industrial Automation Wiring and Grounding Guidelines,
Allen-Bradley publication 1770-4.1, for additional information. \
Output Wiring
Basic wiring
(1)
of output devices to the 1769-OW16 is shown below.
ATTENTION
Be careful when stripping wires. Wire fragments that fall into a module could cause damage at power up. Once wiring is complete, ensure the module is free of all metal fragments.
!
L1 or +DC
CR
CR
OUT 0
VAC-VDC
1
OUT 1
OUT 2
OUT 3
OUT 4
OUT 5
OUT 6
OUT 7
CR
CR
CR
CR
CR
VAC-VDC
2
OUT 8
OUT 9
OUT 11
OUT 10
OUT 13
OUT 12
OUT 14
OUT 15
CR
CR
CR
L1 or +DC
L2 or -DC
L2 or -DC
(1) Surge Suppression - Connecting surge suppressors across your external inductive load will extend the life of the relay contacts. For additional details, refer to
Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication
1770-4.1.
Publication 1769-IN062A-EN-P - December 2001
Compact™ 16-Point AC/DC Relay Output Module 9
A removable, write-on label, (see page 2, item 9) is provided with the module.
Remove the label from the door, mark the identification of each terminal with permanent ink, and slide the label back into the door. Your markings (ID tag) will be visible when the module door is closed.
Removing the Finger-Safe Terminal Block
When wiring field devices to the module, it is not necessary to remove the terminal block. If you remove the terminal block, use the write-on label on the side of the terminal block to identify the module slot location and type.
SLOT # _____
MODULE TYPE ______
To remove the terminal block, loosen the upper and lower retaining screws. The terminal block will back away from the module as you remove the screws. When replacing the terminal block, torque the retaining screws to 0.46 Nm (4.1 in-lbs).
Wiring the Finger-Safe Terminal Block
upper retaining screw wiring the finger-safe terminal block lower retaining screw
When wiring the terminal block, keep the finger-safe cover in place.
1. Loosen the terminal screws to be wired.
Publication 1769-IN062A-EN-P - December 2001
10 Compact™ 16-Point AC/DC Relay Output Module
2. Route the wire under the terminal pressure plate. You can use the bare wire or a spade lug. The terminals will accept a 6.35 mm (0.25 in.) spade lug.
TIP
The terminal screws are non-captive. Therefore, it is possible to use a ring lug [maximum 1/4 inch o.d. with a 0.139 inch minimum i.d. (M3.5)] with the module.
3. Tighten the terminal screw making sure the pressure plate secures the wire.
Recommended torque when tightening terminal screws is 0.68 Nm (6 in-lbs).
TIP
If you need to remove the finger-safe cover, insert a screw driver into one of the square, wiring holes and gently pry the cover off. If you wire the terminal block with the finger-safe cover removed, you will not be able to put it back on the terminal block because the wires will be in the way.
Simplified Output Circuit Diagram
+24V
VAC - VDC
OUT
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires with the following restrictions:
Wire Type
Solid Cu-90°C (194°F)
Stranded Cu-90°C (194°F)
Wire Size
#14 to #22 AWG
#16 to #22 AWG
Terminal Screw
Torque
0.68 Nm (6 in-lbs)
0.68 Nm (6 in-lbs)
Retaining Screw
Torque
0.46 Nm (4.1 in-lbs)
0.46 Nm (4.1 in-lbs)
Publication 1769-IN062A-EN-P - December 2001
Compact™ 16-Point AC/DC Relay Output Module 11
I/O Memory Mapping
Output Data File
Data output bits are turned on or off using the bit positions in Word 0.
1 = output on
0 = output off
Example: To turn on bit position 12, type 1 in Word 0, Bit 12.
For each module, slot x, word 0 in the output data file contains the control program’s directed state of the discrete output points.
Bit Position
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 w w w w w w w w w w w w w w w w w = write only
Output Module’s Input Data File
For each module, slot x, input data file word 0 contains the state of the module’s output data (output data echo) file word 0. During normal operation, these input bits represent the logic state that the outputs are directed to by the control program.
They are also dependent upon the:
•
Program Mode configuration (if supported by the controller)
•
The Fault Mode configuration (if supported by the controller).
15 14 13 12 11 10 9
r r r r r r r
Bit Position
r
8 7
r r
6
0 r = read only r
5
r
4
r
3
r
2
r
1
r
0
IMPORTANT
The output module’s input data file reflects the output data echo of the module, not necessarily the electrical state of the output terminals. It does not reflect shorted or open outputs.
It is important to use this input word if the controller adapter supports the Program Mode or Fault Mode function, and if it is configured to use them.
Publication 1769-IN062A-EN-P - December 2001
12 Compact™ 16-Point AC/DC Relay Output Module
1769-OW16 Configuration File
The read/writable configuration data file allows the setup of the hold last state and user-defined safe state conditions.
The manipulation of the bits from this file is normally done with programming software (e.g. RSLogix 500, RSNetworx for DeviceNet, etc.) during initial configuration of the system. In that case, graphical screens are provided via the programmer to simplify configuration. However, some systems (e.g. 1769-ADN
DeviceNet Adapter) also allow the bits to be altered as part of the control program using communication rungs. In that case, it is necessary to understand the bit arrangement.
2
3
0
1
4
15 14 13 12 11 10 9
0 0 0 0 0 0 0
Bit Position
8
0
7
0
6
0
5
0
Program State for Output Array Word 0
Program Value for Output Array Word 0
Fault State for Output Array Word 0
Fault Value for Output Array Word 0
4
0
3
0
2
0
1 0
0 PFE
Program State Word
Word 1, the program state word, selects the hold last state or user-defined safe state condition for each individual output on a system transition from Run to Program.
Condition Bit Setting
User-defined Safe State 0
Hold Last State 1
Program Value Word
The program value word, word 2, is used to program the user-defined safe state value (0=Off,
1=On). Each output is individually configurable for on or off.
Value
Off
On
Bit Setting
0
1
Fault State Word
Word 3, the fault state word, selects the hold last state or user-defined safe state condition for each individual output on a system transition from Run to Fault.
Condition Bit Setting
User-defined Safe State 0
Hold Last State 1
Publication 1769-IN062A-EN-P - December 2001
Compact™ 16-Point AC/DC Relay Output Module 13
Fault Value Word
The fault value word, word 4, is used to program the fault state value (0=Off, 1=On). Each output is individually configurable for on or off.
Value
Off
On
Program to Fault Enable Bit (PFE)
Word 0, bit 0, allows the selection of which data value, the program or fault value, to apply to the output if a system in Program mode undergoes a system fault, resulting in a change to the Fault mode.
Value Applied
Program
Fault
Module Default Condition
Bit Setting
0
1
Bit Setting
0
1
The modules default condition is all zeros, programming the conditions shown below.
Word or Bit Affected
Word 0, Bit 0:
Word 1:
Word 2:
Word 3:
Word 4:
Program-to-Fault Enable
Program State
Program Value
Fault State
Fault Value
Condition Applied
Program Value
User-defined Safe State
Off
User-defined Safe State
Off
Spare/Replacement Module Parts
•
Terminal Block:1769-RTBN18 (1 per kit)
Publication 1769-IN062A-EN-P - December 2001
14 Compact™ 16-Point AC/DC Relay Output Module
Specifications
General Specifications
Specification
Dimensions
Value
118 mm (height) x 87 mm (depth) x 52.5 mm (width) height including mounting tabs is 138 mm
4.65 in. (height) x 3.43 in (depth) x 2.07 in (width) height including mounting tabs is 5.43 in.
450g (0.99 lbs.) Approximate Shipping Weight
(with carton)
Storage Temperature
Operating Temperature
Operating Humidity
Operating Altitude
Vibration
-40°C to +85°C (-40°F to +185°F)
0°C to +60°C (32°F to +140°F)
5% to 95% non-condensing
2000 meters (6561 feet)
(1)
Operating: 10 to 500 Hz, 5G, 0.030 inches maximum peak-to-peak
Relay Operation: 2.0G
Shock
Agency Certification
Hazardous Environment Class
•
•
•
Operating: 30G panel mounted (20G DIN rail mounted)
Relay Operation: 10G panel mounted (5G DIN rail mounted)
Non-Operating: 40G panel mounted (30G DIN rail mounted)
C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE and C-Tick compliant for all applicable directives
Class I, Division 2, Hazardous Location, Groups A, B, C, D (UL 1604,
C-UL under CSA C22.2 No. 213)
Radiated and Conducted Emissions EN50081-2 Class A
Electrical /EMC: The module has passed testing at the following levels:
ESD Immunity (IEC61000-4-2)
•
4kV contact, 8 kV air, 4 kV indirect
Radiated Immunity (IEC61000-4-3)
•
10 V/m, 80 to 1000 MHz, 80% amplitude modulation, +900
MHz keyed carrier
Fast Transient Burst (IEC61000-4-4)
•
2 kV, 5 kHz
Surge Immunity (IEC61000-4-5)
•
2 kV common mode, 1 kV differential mode
Conducted Immunity (IEC61000-4-6) •
10V, 0.15 to 80 MHz
(2)
(1) For operation above 2000 meters, consult the factory.
(2) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to
1000 MHz.
Publication 1769-IN062A-EN-P - December 2001
Compact™ 16-Point AC/DC Relay Output Module 15
Output Specifications
Specification
Voltage Category
Operating Voltage Range
Number of Outputs
Bus Current Draw (max.)
Heat Dissipation
Signal Delay (max.) – resistive load
Off-State Leakage (max.)
On-State Current (min.)
Continuous Current per Point (max.)
Continuous Current per Common (max.)
Continuous Current per Module (max.)
Power Supply Distance Rating
Output Point to Bus Isolation
Isolated Groups
Output Group to Output Group Isolation
Vendor I.D. Code
Product Type Code
Product Code
1769-OW16
AC/DC normally open relay
5 to 265V ac
5 to 125V dc
16
205 mA at 5V dc line
180 mA at 24V dc line
4.75 Total Watts
(The Watts per point, plus the minimum Watts, with all points energized.) turn-on = 10 ms turn-off = 10 ms
0 mA
10 mA at 5V dc
2.5A (Also see "Relay Contact Ratings" on page 16.)
10A
20A
1
7
85
8 (The module may not be more than 8 modules away from the power supply.)
Verified by one of the following dielectric tests: 1836V ac for 1 sec. or 2596V dc for 2 sec.
265V ac working voltage (IEC Class 2 reinforced insulation)
Group 1: outputs 0 to 7
Group 2: outputs 8 to 15
Verified by one of the following dielectric tests: 1836V ac for
2 sec. or 2596V dc for 2 sec.
265V ac working voltage (basic insulation)
150V ac working voltage (IEC Class 2 reinforced insulation)
Publication 1769-IN062A-EN-P - December 2001
16 Compact™ 16-Point AC/DC Relay Output Module
Relay Contact Ratings
Volts (max.)
240V ac
120V ac
125V dc
24V dc
Continuous Amps per Point (max.)
2.5A
1.0A
2.0A
(1)
Amperes
(2)
Make
7.5A
Voltamperes
Break Make
0.75A
1800 VA
Break
180 VA
15A
0.22A
(3)
1.5A
28 VA
NEMA
ICS 2-125
C300
R150
(1) The continuous current per module must be limited so the module power does not exceed 1440 VA.
(2) Surge Suppression - Connecting surge suppressors across your external inductive load will extend the life of the relay contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication
1770-4.1.
(3) For dc voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the applied dc voltage. For example, 28 VA/48V dc = 0.58A. For dc voltage applications less than 48V, the make/break ratings for relay contacts cannot exceed 2A.
Publication 1769-IN062A-EN-P - December 2001
Compact™ 16-Point AC/DC Relay Output Module 17
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations only. The following WARNING statement applies to use in hazardous locations.
WARNING
!
EXPLOSION HAZARD
•
Substitution of components may impair suitability for
Class I, Division 2.
•
Do not replace components or disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
•
Do not connect or disconnect components unless power has been switched off or the area is known to be non-hazardous.
•
This product must be installed in an enclosure.
•
All wiring must comply with N.E.C. article 501-4(b).
Environnements dangereux
Cet équipement est conçu pour être utilisé dans des environnements de Classe 1,
Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante s’applique à une utilisation dans des environnements dangereux.
AVERTISSEMENT
!
DANGER D’EXPLOSION
•
La substitution de composants peut rendre cet équipement impropre à une utilisation en environnement de Classe 1,
Division 2.
•
Ne pas remplacer de composants ou déconnecter l'équipement sans s'être assuré que l'alimentation est coupée et que l'environnement est classé non dangereux.
•
Ne pas connecter ou déconnecter des composants sans s'être assuré que l'alimentation est coupée ou que l'environnement est classé non dangereux.
•
Ce produit doit être installé dans une armoire.
Publication 1769-IN062A-EN-P - December 2001
18 Compact™ 16-Point AC/DC Relay Output Module
For More Information
For Refer to this Document
A more detailed description of how to install and use your Compact™ I/O with MicroLogix™
1200 & 1500 programmable controller.
MicroLogix 1500 Programmable
Controllers User Manual
A more detailed description of how to install and use your Compact I/O with the
CompactLogix™ System.
More information on proper wiring and grounding techniques.
Pub. No.
1764-UM001B-US-P
CompactLogix System User Manual 1769-UM007C-EN-P
Industrial Automation Wiring and
Grounding Guidelines
1770-4.1
If you would like a manual, you can:
• download a free electronic version from the internet:
www.ab.com/micrologix or www.theautomationbookstore.com
• purchase a printed manual by:
– contacting your local distributor or Rockwell Automation representative
– visiting www.theautomationbookstore.com and placing your order
– calling 1.800.963.9548 (USA/Canada) or 001.330.725.1574 (Outside USA/Canada)
Publication 1769-IN062A-EN-P - December 2001
Compact™ 16-Point AC/DC Relay Output Module 19
Publication 1769-IN062A-EN-P - December 2001
Compact, MicroLogix, CompactLogix, RSLogix and RSNetworx are trademarks of Rockwell Automation.
DeviceNet is a trademark of Open DeviceNet Vendor Association (ODVA).
Publication 1769-IN062A-EN-P - December 2001 PN 40072-119-01 (1)
© 2001 Rockwell International Corporation. Printed in the U.S.A.