Heat Mat 6mm Red In-screed Heating Cables, 7mm Black Outdoor Heating Cables Heating Cables Fitting Guide
Below you will find brief information for Heating Cables 6mm Red In-screed Heating Cables, Heating Cables 7mm Black Outdoor Heating Cables. The Heat Mat 6mm and 7mm Heating Cables are compatible with...Thermostats, Thermal insulation boards, Levelling compound, Ice & Snow Systems, Cable safe accessory. You can use the cables to set up your own indoor or outdoor heating system. There is a basic wiring diagram for you to follow. Before you begin installation, please check you have the correct heater for your chosen area.
Advertisement
Advertisement
Robust, 17 th Edition and
Part L Compliant
6mm Red In-screed Heating Cables
7mm Black Outdoor Heating Cables
Fitting Guide – Version 3
Call 01444 247020 for Technical Support
CO
MPLIANT
C
OM
P LIAN
T
Please ensure you read this guide completely before commencing installation of the underfloor heating.
If you are unsure of any aspect of the installation please call Heat Mat’s Technical
Support helpline on 01444 247020.
Before commencing your installation, please check that you have the correct heater or combination of heaters for your chosen area.
Heat Mat 6mm and 7mm Heating Cables are compatible with...
Thermostats
Thermal insulation boards
Levelling compound
Contents
Do’s and don’ts
.............................................................................................
3
Basic wiring diagram and warning label
..........
4
Technical specification
.....................................................................
5
Cable spacing information
.........................................................
7
Installation instructions
...................................................................
8
Ice & Snow
Systems
Cable safe accessory
Ice & Snow Melting Systems
............................................
14
Driveway Heating Mats
...............................................................
15
Ice & Snow Melting Systems for Roofs
..........
17
Ice & Snow Melting Systems for Gutters
.....
18
Warranty information
......................................................................
19
Heat Mat Limited accept no liability, either express or implied, for any consequential losses incurred as a result of a Heat Mat system installation that does not conform to the following installation instructions.
Do’s and Don’ts for internal heating systems
Important - Always calculate the cable spacing for each room before starting to lay the heating cable. See Page 7
Do thoroughly read this guide before commencing installation.
Do space the cables evenly across the floor for a uniform heat output.
Do ensure that all heating wire (including joints) is fitted beneath the floor covering. The cable can never be shortened.
Do use a multi-meter to test the cable, before, during and after covering.
Do connect multiple cables in parallel.
Do consider thermally insulating your sub-floor before installing the underfloor heating system.
Do use a Heat Mat thermostat to control your system.
Do ensure that all electrical works conform to Part ‘P’ of the Building Regulations and current IEE Wiring Regulations.
Do ensure the system is protected by a suitable
RCD device (30mA).
Do ensure that all heating cable and connections are covered with a cementaceous screed of at least 50mm (min 65mm for Part L compliance) or 15mm of flexible self-levelling compound.
Do log on to www.heatmat.co.uk to ensure that you are using the most recent instructions.
Do ensure all heating cables are at least 60mm away from each other.
Always calculate the cable spacing for each room yourself referring to the actual cables you will be fitting (see page 7). Heat Mat provide a cable spacing guide but this distance must always be tailored to the individual rooms.
Don’t cut, shorten, strain or cross the heating cables.
Don’t bend the joint between the element and cold tail.
Don’t supply power to the heater until the cable has been fully encased and the wet trade has been allowed to fully dry out.
Don’t lay cables closer than 60mm to conductive parts.
Don’t lay cables at an output greater than
160W if covering with wood, vinyl or carpet.
Don’t install heating cables if the ambient temperature is below 5ºC as they can become less flexible.
Don’t install the heating cable at an output higher than 270W/sqm unless approval has been received for this application from
Heat Mat.
Don’t install the heating cables in walls or ceilings.
Don’t install the floor sensor close to other heat sources e.g. hot water pipes.
Don’t begin covering with cementaceous screed or levelling compound until the system is in place and has been tested with a multimeter.
Don’t leave any sections of the heating cable or connections in the open air or beneath fixtures and fittings when installation is completed.
Don’t use the heating system to help to dry out the wet trade.
For support please call 01444 247020 3
Basic wiring diagram and warning label
Typical Wiring System
Fused Spur
Power supplied through an RCD S
E
F
U
Please see the back page of this fitting guide for the required information label for the distribution board. It is a legal requirement that this label is completed and the required
Thermostat information is displayed near the relevant distribution board.
11:05 Thu
18ºC
Comfort Menu Manual
1.3m above floor
Floor
Floor Sensor
• All electrical works must be carried out by a certified electrician.
• A suitable RCD protection must be incorporated in this system.
• If the ampage of the thermostat is exceeded by your chosen system, a contactor or similar device will be required. All thermostats used must be of a two-pole design with a minimum opening between the contacts of 3mm.
• The heating cables must not be cut or cross each other or other wiring.
• The cold tail joint must be kept straight and located beneath the final floor covering and must be thoroughly encased in tile adhesive or levelling compound.
• Please consult your electrician to discuss your individual requirements.
To check that you have the latest set of instructions please follow this link www.heatmat.co.uk/frequently-asked-questions/instruction-downloads.html
4 Please visit our website www.heatmat.co.uk for further information
6mm Red In-screed Heating Cable 22W/m technical specification
– not suitable for external use
Product code
Length in meters
Output Resistance
175W/m 2 c-c 12.5cm
150W/m 2 c-c 15.0cm
PKC-6.0-0120
PKC-6.0-0220
PKC-6.0-0330
PKC-6.0-0440
PKC-6.0-0550
PKC-6.0-0640
PKC-6.0-0750
PKC-6.0-0950
PKC-6.0-1070
PKC-6.0-1380
PKC-6.0-1530
PKC-6.0-1800
5.8m
10.0 m
15.0 m
20.0 m
25.0 m
30.0 m
36.0 m
44.0 m
50.0 m
64.0 m
71.0 m
84.0 m
120W
220 W
330 W
440 W
550 W
640 W
750 W
950 W
1070 W
1380 W
1530 W
1800 W
0.7 m
1.3 m
1.9 m
2
2
2
2.5 m 2
3.1 m 2
3.6 m
4.3 m
5.4 m
6.1 m
7.8 m 2
8.7 m 2
10.2 m
2
2
2
2
2
0.8 m 2
1.5 m 2
2.2 m 2
3.0 m 2
3.7 m 2
4.4 m 2
5.1 m
6.5 m
7.3 m
2
9.4 m 2
10.4 m 2
12.2 m
2
2
2
PKC-6.0-2190
PKC-6.0-2770
101.0 m
130.0 m
2190 W
2770 W
26 Ω
21 Ω
12.4 m
15.7 m
2
2
14.9 m
18.8 m
2
2
PKC-6.0-3530 163.0 m 3530 W 16 Ω 20.1 m 2 24.0 m 2
PRA-111-0002 25m Cable fixing band – For rectangular or square rooms over 5m 2 roughly 1.5m of fixing strip is required for every m 2 of floor.
For all other rooms approximately 2.0m of fixing strip is required for every m 2 of floor.
HCA-111-0008 25m Double-sided tape – for securing fixing bands
Test your heating cable with a multi-meter before unwrapping to confirm you have received it in working order.
The black cold tail is double insulated and carries an earth screen (silver braid), live and neutral wires.
Exposing the ends of these wires will allow the continuity tests to be carried out with a functional multi-meter.
This test should also be done before, during and after covering with screed or levelling compound.
At no point should any cable be connected to a power supply to test it.
Tests
• Live to neutral = ohms value as listed above
• Live to earth and neutral to earth = both infinity
If your tests do not conform to the expected results please contact Heat Mat’s Technical Support Team.
125W/m 2 c-c 17.5cm
6.0 m 2
7.6 m 2
8.6 m 2
11.0 m 2
12.2 m 2
14.4 m 2
1.0 m 2
1.8 m 2
2.6 m 2
3.5 m 2
4.4 m 2
5.1 m 2
17.5 m 2
22.2 m 2
28.2 m 2
Technical Data:
General Construction: Dual conductor wire with earth
Voltage: 240 Vac – 50Hz
Maximum Load: 22 W/m
Maximum Cable Temperature: 90ºC
Approvals: CE marked
Wire Thickness: 6mm
Cable Flexibility: Minimum allowable cable radius is 50mm
Power Range: 210W-3530W
UV Resistance: Not UV resistant or suitable for outdoor use
Approved in accordance with: EN60335-2-96, EN60800 M1
IP Rating: IPX7 as required by the 17th Edition IEE Wiring Regulations
Construction:
Thermal Conductor: 2 x resistance 7 stranded wires insulated with flouropolymer
Additional Internal Insulation: Polyester sheath
Insulation Shield: Aluminium foil shield
Outer Insulation: PVC (105) UV resistant, tested to 90ºC
Reinforcement Materials: Fibreglass strands
Fixing Materials: Fix onto reinforcement fabric or Heat Fix metal bands can be used
CO
MPLIANT
PART L
OM
P LIAN
T
Part L
Compliant
17 th Edition
Compliant
Certified
EMC safe
Manufactured in a
BEAB approved factory
For support please call 01444 247020
CE
Marked
5
7mm In-screed Heating Cable 20W/m technical specification
– suitable for external use
Product code
Length in meters
Output Resistance
270W/m 2 c-c 7.5cm
200W/m 2 c-c 10.0cm
PKC-7.0-0210
PKC-7.0-0417
PKC-7.0-0504
PKC-7.0-0627
PKC-7.0-0837
PKC-7.0-1022
PKC-7.0-1246
10.5 m
21.0 m
26.0 m
32.0 m
42.0 m
50.0 m
62.0 m
210 W
417 W
504 W
627 W
837 W
1022 W
1246 W
0.8 m 2
1.5 m 2
1.9 m 2
2.3 m 2
3.1 m 2
3.8 m 2
4.6 m 2
PKC-7.0-1381
PKC-7.0-1774
PKC-7.0-2144
69.0 m
89.0 m
105.0 m
1381 W
1774 W
2144 W
5.1 m 2
6.6 m 2
7.9 m 2
6.9 m 2
8.9 m 2
10.7 m 2
PKC-7.0-2458
PKC-7.0-3067
123.0 m
150.0 m
2458 W
3067 W
9.1 m 2
11.4 m 2
12.3 m 2
15.3 m 2
PRA-111-0002 25m Cable fixing band – For rectangular or square rooms over 5m 2 roughly 1.5m of fixing strip is required for every m 2 of floor.
For all other rooms approximately 2.0m of fixing strip is required for every m 2 of floor.
HCA-111-0008 25m Double-sided tape – for securing fixing bands
1.1 m 2
2.1 m 2
2.5 m 2
3.1 m 2
4.2 m 2
5.1 m 2
6.2 m 2
Test your heating cable with a multi-meter before unwrapping to confirm you have received it in working order.
The black cold tail is double insulated and carries an earth screen (silver braid), live and neutral wires.
Exposing the ends of these wires will allow the continuity tests to be carried out with a functional multi-meter.
This test should also be done before, during and after covering with screed or levelling compound.
At no point should any cable be connected to a power supply to test it.
Tests
• Live to neutral = ohms value as listed above
• Live to earth and neutral to earth = both infinity
If your tests do not conform to the expected results please contact Heat Mat’s Technical Support Team.
160W/m 2 c-c 12.5cm
1.3 m 2
2.6 m 2
3.2 m 2
3.9 m 2
5.2 m 2
6.4 m 2
7.8 m 2
8.6 m 2
11.1 m 2
13.4 m 2
15.4 m 2
19.2 m 2
Technical Data:
General Construction: VDE approved dual conductor wire with earth
Voltage: 230 Vac – 50Hz
Maximum Load: 21 W/m
Maximum Cable Temperature: 90ºC
Approvals: CE marked
Wire Thickness: 6.8mm to 7.2mm depending on Ohm Value
Cable Flexibility: Minimum allowable cable radius is 50mm
Power Range: 210W-3067W
UV Resistance: Confirmed UV Resistant by VDE test institute
Approved in accordance with: EN 60335-1:1998,
EN60335-2-17:1999, IEC 60730
IP Rating: IPX7 as required by the 17th Edition IEE Wiring Regulations
Construction:
Thermal Conductor: 2 x resistance 7 stranded wires insulated with 0.8mm silicon rubber (2G)
Additional Internal Insulation: Polyester sheath
Insulation Shield: Aluminium foil shield
Outer Insulation: PVC (105) UV resistant, tested to 90ºC
Reinforcement Materials: Fibreglass wire
Fixing Materials: Heat Fix metal bands can be used
For full fitting instructions please see our website www.heatmat.co.uk or contact us for advice.
CO
MPLIANT
PART L
C
OM
P LIAN
T
Part L
Compliant
6
17 th Edition
Compliant
Certified
EMC safe
Please visit our website www.heatmat.co.uk for further information
Manufactured in a
BEAB approved factory
CE
Marked
Choosing the correct cable spacing (c-c)
Calculate the total m 2 of floor area you have in your room, and then deduct any areas where underfloor heating should not be laid, such as any floor fixed furniture including baths, shower trays, kitchen units, central islands etc. We also recommend leaving a 60mm margin unheated around the perimeter of the room.
This will give you your free floor area.
To calculate the wattage output per m 2 you will have, divide the wattage listed for your cable/s by the m 2 free floor area that you have to heat i.e.
2,144W
–––––––––
11m 2
= an output of 195W/m 2
Now you must calculate the cable to cable (c-c) distance you will lay your heating cable at. Divide the free floor area multiplied by 100 by the total length of the cables you have to lay i.e.
11m 2 x 100
–––––––––
105m
= 10.5cm
You should therefore, in this circumstance, lay all of the cables in runs roughly 10.5cm apart.
The 6mm and 7mm cable tables on pages 5 and 6 can be used as a guide to the approximate m 2 coverage of each cable when laying at various outputs. You should always confirm the actual coverage required using the calculation above.
As a guide to confirming the wattage per square metre
(W/m 2 ) that you require, please use the following advice.
Very well insulated rooms – 100W/m 2 to
130W/m 2
In very well insulated properties this output can provide a full heating system as long as the system is installed above significant sub-floor insulation.
Standard rooms – 140W/m 2 to 160W/m 2
In properties up to the current insulation standards this output is sufficient to provide a full heating system and will react faster than a lower powered installation.
The system must be laid above sub-floor insulation.
High heat loss rooms – 170W/m 2 to 200W/m 2
In high heat loss rooms such as conservatories or older properties with low insulation values a more powerful system should still be able to provide a full heating system if laid above sub-floor insulation.
Although 100% coverage is achievable, a border of roughly
60mm is recommended around the perimeter of the room as the heating cables should not touch the walls, kickboards etc.
We would recommend planning your installation before starting to lay your cable, and also that you photograph your cable layout before tiling for future reference.
The thermal resistance (insulation) between the top of the heated screed and the room must not have an insulation value higher than 0.125 m²K/W. Some typical insulation values for common floor coverings are listed below:
Tiled, stone and thin vinyl floors
Linoleum floors and thick vinyl floors
Hessian backed carpets with low Tog underlays
Parquet and laminate floors up to 18mm thick
Wood fibre floors and rubber backed carpets
Up to 0.035 m²K/W
Up to 0.040 m²K/W
Up to 0.125 m²K/W
Up to 0.125 m²K/W
Up to 0.175 m²K/W
The material used to cover the heating cable must have a density of 1,500kg/m3 and a minimum heat transmission of 1W/m K, all normal tile adhesives, levelling compounds and screeds conform to this standard.
* Insulation within the floor base minimises downward heat loss allowing your underfloor heating to run more efficiently.
Insulation laid directly beneath the underfloor heating will provide the largest benefit, and the further down in the floor build the insulation is
(such as beneath a screed) the less benefit it will offer. Systems laid onto very badly insulated floor bases may not meet your expectations.
For support please call 01444 247020 7
Installation instructions for 6mm Red and 7mm Black Heating Cables indoors
Floor preparation
The sub-floor should be solid, level and reasonably dust free as would normally be required before pouring a screed. Cables should always be laid above an insulation layer and this should be either foil faced (such as Cellotex TM
FF4000) or concrete faced (such as Heat Mat underfloor heating insulation boards).
If a damp-proofing membrane is being installed this must be placed beneath the heating cables. We would also recommend that the entire floor base is of the same construction to ensure the system performs evenly.
It is acceptable to lay cables directly onto an existing well insulated concrete base or tiled floor, however in these circumstances we still recommend considering installing an additional layer of insulation, such as
Heat Mat underfloor heating insulation boards.
Underfloor heating cables must not be installed directly onto a layer of soft insulation, it must have a layer of concrete or foil to facilitate an even heat spread.
Any areas containing expansion joints must be clearly marked ahead of installation and the cables must not cross these joints.
Installing the Heating Cable System
Test each cable with a multi-meter before unpacking to ensure you have received your product in full working order. (See bottom of pages 5 and 6 for testing instructions)
Before starting to lay the heating cable/s it is vital that you calculate the cable spacing for the area in question.
Even if you have already been provided with a suggested cable spacing it is important that you verify that this is suitable for your area; if the cable is not spaced correctly you may end up with excess cable or not enough to cover the area correctly.
Refer to page 7 for details of how to calculate the cable spacing for each area and remember to take into account any perimeter that you may be leaving unheated.
The cables would normally be laid backwards and forwards along the longest dimension of the room and you should start to lay the cables running away from the site where the electrical connections will be made.
The heating cable can be secured in place via two methods; either loosely cable-tied to reinforcement fabric/reinforcement mesh or fixed to the floor using
Heat Mat’s metallic fixing strips.
8 Please visit our website www.heatmat.co.uk for further information
Installation instructions for 6mm Red and 7mm Black Heating Cables indoors
Installation with reinforcement fabric/ reinforcement mesh
In most circumstances and particularly in large areas the recommended method of installation is fitting the cables onto reinforcement fabric. This method ensures the cables are held slightly above any insulation layer and is particularly suited to installation onto a damp-proof membrane (DPM).
The reinforcement fabric should be laid onto the base above the insulation and any DPM. The fabric should be sufficiently strong to prevent it bending while people are walking above it and we recommend 6mm thick A142 or
A142m reinforcement fabric which should be firmly cable tied together to hold it in place. The fabric must be free from sharp edges and you should pay particular attention to any sections which have been trimmed with a bolt cutter.
It is preferable to fix the cables to the top reinforcement bars, so where possible these should be placed at 90 degrees to the direction the cable will be laid. If this is not possible it is still straightforward to fix the cable to the bottom bar, although it takes slightly longer. The cables should be loosely fixed in place using 2.5mm x 203mm cable ties and these should be tightened enough to hold the cable in place, but should not be over-tightened which could damage the cable. The cable should still be able to run backwards and forwards even when held in place by the cable tie. This method of installation is suitable for damp or wet conditions.
The cable should be secured either side of the room approximately 0.2m from the wall, with the second fixing 1.0m in from the wall.
Further cable ties should be used every 1.2m to
1.5m across the room. The cables should be spaced evenly over the room at the appropriate distance to provide 100% coverage.
The free floor area of each room should be verified before laying the cables and referring to page
7 of the installation guide you should calculate the precise cable spacing for that room.
Once the cable spacing has been decided upon we recommend using liquid Tipp-ex TM with a brush
(the bottles contain a small brush) to mark out the cable spacing on the 6mm metalwork on either side of the room.
The speediest method of installation is for a team of two installers to mark out the cable spacing and then stretch the cable across the room with one installer on either side of the room. The cable can then be safely secured close to the wall and then the next run can be laid.
This is repeated across the room until the cable covers the whole area. Once this is done the team can move onto the next area and the cable can be secured at the additional points by one person. Under no circumstances can the cables be cut to shorten them, or joined together to lengthen them.
For support please call 01444 247020 9
Installation instructions for 6mm Red and 7mm Black Heating Cables indoors
All cable including the coldtail connection and end termination must be completely encapsulated within the screed. It is important that the cables are started close to where the thermostat, connection box or contactor will be placed to allow simple connection.
All cable, coldtail connections and end terminations must be placed where they will be fully covered with screed and must not be taped down or pushed into the insulation.
Cables must not cross each other and must never be closer than 60mm to other cables or conductive parts.
Installation with Heat Mat metallic fixing strips
Heat Mat metallic fixing strips can be used in installations where the heating cables are being laid directly onto a firm concrete or tiled base or a rigid insulation layer such as concrete faced insulation boards or Celotex FF4000 or similar with a metallic facing. It is possible to use fixing strips to install onto a DPM above a rigid insulation layer if the DPM is fully secured in place and taught.
Heat Mat’s recommendation though is using reinforcement fabric for the installation directly above a DPM.
Metallic fixing strips are held to the base using double-sided tape, adhesive or they can be nail gunned into place (nail gunning is not suitable when used on top of a damp-proof membrane and is only recommended on concrete floors).
The fixing strips should be placed on the floor in runs at a 90 degree angle to the direction you wish to lay the heating cable. The first run of fixing strip should be placed approximately 0.2m from the walls with a further fixing strip 1m out. They should then be spaced every 1.2m to 1.5m across the room.
If the fixing strip is being secured with double sided tape the surface must be dry and free from dust. If the fixing strip is being secured with a nail gun the installation can be carried out in damp conditions.
The free floor area of each room should be verified before laying the cables and referring to page 7 of the installation guide you should calculate the precise cable spacing for that room. The fixing strip has pre-spaced cable fittings at 2.5cm intervals, and if your calculated spacing is at
10cm or 12.5cm intervals then simply fix the cables in the appropriate slots.
10 Please visit our website www.heatmat.co.uk for further information
Installation instructions for 6mm Red and 7mm Black Heating Cables indoors
Multiple cables can be installed in one room but must be connected in parallel (they do not join together).
Up to 2 cables can be physically wired into the back of the thermostat. More than 2 cables will require a connection box. If your system exceeds the Ampage rating of your chosen thermostat, your electrician can install a contactor or similar device to allow the heating system to operate safely through a single thermostat for ease of control.
Test the heater/s with a multi-meter again prior to covering.
If covering is not going to happen straight away restrict any traffic above the cable to a minimum.
Covering the Heating Cable System
Wear soft soled shoes and do not allow any unnecessary traffic across the cabled area until the floor covering is completed. Do not stack or cut tiles across the cabled area and take care to avoid dropping sharp objects or tiles onto the cables as this can crush or cut into them.
Check the resistance and continuity of the cable with a multi-meter regularly during installation. If the resistance changes, or the cable goes to open circuit, the cable has been damaged. In this case, please contact Heat Mat’s
Technical Support line on 01444 247020.
Even a small nick in or scratch to the outer insulation can lead to system failure when powered up over a period of time.
If the system is being covered with a cementaceous screed this should be carefully poured over the heating cables to an even depth of at least 50mm, and at least
65mm for Part L compliance. Any material used to cover the heating cables must have a density of at least
1,500kg/m 3 and a minimum heat transmission of 1W/m K.
The screed must be allowed to dry before laying further floor coverings and the heating cables must not be used to ‘dry out’ the screed, as this could lead to the screed cracking or the cable failing. If Heat Mat’s flexible levelling compound is being used to cover the heating cables then a layer of at least 15mm must be used.
In normal circumstances this levelling compound will dry within 24 hours, and as with screed the heating cables must not be used to ‘dry it out’.
The floor sensor should be positioned in the finished screed layer or levelling compound as close to the top of this layer as possible. The floor sensor should extend roughly 400mm into the room and if using a levelling compound rather than a screed, it must be located equidistant between two heating cables.
If using the system as a night storage heater then the floor sensor can be laid at the same level as the heating cables, and again it must be placed equidistant between two heating cables.
For support please call 01444 247020 11
Installation instructions for 6mm Red and 7mm Black Heating Cables indoors
The sensor cable can be extended if required up to 50m using a twin sheathed high temperature PVC cable and the connection between the two wires must be waterproof and fully insulated.
The floor sensor should not be fitted in areas affected by other heat sources, such as hot water pipes and radiators, or in an area that will be covered at a later date with items such as rugs or flat bottomed furniture, as this will prevent the system from operating correctly.
If using one of Heat Mat’s infra-red wall mounted floor sensors you are not required to include an additional floor sensor within the floor construction. Once the screed or levelling compound has fully dried the final floor covering can be laid.
If laying a tiled floor flexible tile adhesive and grout must be used to ensure compatibility with the underfloor heating.
With floating laminate or engineered board floors it is essential that the flooring is no more than 18mm thick to ensure a good movement of heat through the covering, and with these floors any layer of soft insulation laid beneath the flooring must be compatible with installation on top of an underfloor heating system.
For carpeted floors rubber backed carpets should not be used and the Tog rating of the carpet must be no more than 2.0 Tog and of the underlay 0.8 Tog.
To check that you have the latest set of instructions please follow this link www.heatmat.co.uk/ frequently-asked-questions/ instruction-downloads.html
12 Please visit our website www.heatmat.co.uk for further information
Installation instructions
(Continued)
Electrical connections
Wiring can now be completed but no power should be applied to the system until the adhesive, grout and/or levelling compound or screed is completely dry.
All work must comply with current IEE wiring regulations and installations must comply with Part ‘P’ of the Building
Regulations. Consult your Local Authority Building Control department regarding their requirements for certification or check with an electrician qualified to issue Part ‘P’ certification regarding your individual installation.
The heating cable has to be wired into a thermostat with floor temperature limitation. Please see the separate instructions in your Heat Mat thermostat box.
Run the cold tail connection and floor sensor cable in separate plastic conduit or trunking from your heated floor to the thermostat position.
Up to 2 heating cables can be wired straight into the thermostat. A connection box will be required if installing
3 or more heating cables. Ensure that multiple cables are wired in parallel, not in series.
The mains power supply must be protected by a suitable
RCD (30mA and up to 4.8kW).
The thermostat should be connected to the power supply via a suitably rated fused spur or circuit breaker.
Should the total loading from a combination of heating cables exceed the Ampage rating of your chosen thermostat, the system will require the installation of a suitable rated contactor which will allow the heating system to be run through a single thermostat for ease of control.
Some Heat Mat thermostats are IP21 rated, which means that they can be installed within some bathrooms if there is a suitable area.
If the thermostat is placed outside the room to be heated, or inside a cupboard, the thermostat will have to be re-programmed (when first switched on) to only monitor the floor sensor that has been placed into the heated floor space.
Remember:
If you are unsure how to proceed at any stage of the installation process, please contact Heat
Mat Technical Support on 01444 247020 for guidance.
Living with your Underfloor Heating System
To ensure that your system works to its full capacity for the lifetime of the flooring, please ensure that thermal blocking is avoided above the heating system.
Thermal blocking occurs when the heat produced by the system warms the floor surface but is then trapped and has no way of escaping from the surface of the floor. This can happen beneath beanbags, rubber backed mats, furniture without an air gap beneath it or kitchen units.
This can cause the system to overheat in the thermally blocked area and, in extreme cases, affect the integrity of the floor covering and heating system.
Thermal blocking is not usually a problem within floors where the system has been covered with levelling compound or tile adhesive and tiles, as these coverings are efficient transmitters of heat themselves and will spread the heat around any thermal block. Thermal blocking has a greater chance of occurring in situations with a carpeted, wooden or laminate floor finish that do not utilise a levelling compound as these coverings do not transmit heat as effectively.
Heat Mat’s thermostats are IP21 rated, and the heating mats are IPX7 rated, which means systems can be installed in bathrooms and other ‘wet areas’ and if a suitable zone is available the thermostat can also be placed in the bathroom.
For support please call 01444 247020 13
Heat Mat external
Ice & Snow Melting Systems
Heat Mat offer a wide range of Scandinavian designed outdoor de-icing systems for roofs, gutters, driveways and walkways. In most circumstances these systems will be based around the 7mm black cable system which has specifically been designed to be robust enough for external use and is fully UV protected. The 6mm Red cable system is not suitable for external use.
The majority of external heating systems are controlled using one of our range of proprietary ice and snow melting thermostats and these have a range of temperature sensors to monitor ambient or ground temperature. In addition to temperature sensors our higher end ice and snow melting thermostats also include the option of a moisture detector which ensures that the system will only operate when it is cold and there is moisture present.
Moisture sensors would normally cut the running costs of a system by around 80%, as it is often very cold, but if there is no moisture present there is no risk of ice or snow, so the system does not need to be powered up.
Particular care should be taken when deciding where to place the temperature and moisture sensors and we recommend that you thoroughly read the instructions that are supplied with the thermostats and, if you are unclear on any points, please contact Heat Mat.
Installing the heating cables for external use is much the same as with general installation instructions for beneath a screed, however the covering over the cable (in the case of driveway or walkway heating) is obviously different and the three most common installation methods are noted overleaf. For roof and gutter heating systems there are a number of alternative ways to install the heating cables and these are briefly described in the following pages.
For additional installation information for external systems please speak to Heat Mat’s
Technical Team on 01444 247020.
14 Please visit our website www.heatmat.co.uk for further information
Driveway Heating Mats
Outdoor Heating Mat - 7mm Heating Mat 300W/m 2
Driveway heating mats are perfect for situations where you only need to heat tyre tracks rather than the entire driveway, and their high 300W/sqm output ensures any snow or ice melts quickly. The cable is pre-spaced on a fibreglass mesh for speedy installation and the mats can either be laid into sand or affixed to hard bases using an appropriate fixing to hold down the mesh.
In most circumstances a 400mm wide mat will be sufficient to heat the tyre tracks.
800mm mats are available if a wider protected track is required, for instance for larger vehicles, however these are a special order item and please speak to your distributor for delivery timescales.
For large industrial applications mats are available in 410V specification and again, these are a special order item.
Product code
ICE-040-0600
ICE-040-0800
ICE-040-1000
ICE-040-1200
ICE-040-1400
ICE-040-1600
ICE-040-1800
ICE-040-2000
Length
6m
8m
10m
12m
14m
16m
18m
20m
Width
0.4m
0.4m
0.4m
0.4m
0.4m
0.4m
0.4m
0.4m
Area
2.4m
3.2m
4.0m
4.8m
5.6m
6.4m
7.2m
8.0m
Output
720W
960W
1200W
1440W
1680W
1920W
2160W
2400W
Technical Data
Voltage: 230 V - 50 Hz
Maximum load: 21W/m
Max. cable temperature: 70 o C
Wire Thickness: 6.8mm-7.2mm depending on
Ohm value
Cable flexibility: Minimum allowable cable radius
50mm
Power range: 720W-2400W
Approvals: CE marked, EN60800
IP Rating: IPX7 as required by 17 th Edition IEE wiring insulated with fluropolymer
Construction Data
Resistance
General Construction: Dual conductor wire with earth
Thermal conductor: 2 x resistance stranded wires insulated with flouropolymer
Additional Internal Insulation: Polyester sheath
Insulation Shield: Tinner copper shield
Outer Insulation: PVC
Reinforcement Mesh: Fibreglass
For support please call 01444 247020 15
Driveway, walkway and loading ramp heating
Choice of output
For normal installations we recommend an output of around
270W/sqm which provides a good balance between speed of operation and power requirements. Often the limiting factor to the size of area which can be heated is the available power supply on site, and with restricted power supplies it is often possible to specify a lower powered system which will still clear the ice and snow.
Tyre track heating
Where a long driveway requires heating it is quite acceptable to simply heat two tyre tracks leaving other areas unheated. This saves on the power requirements and installation and running costs and it allows longer driveways to be heated than would otherwise be possible.
Drainage channel heating
When heating a driveway or path area it is vital to ensure that the water can safely run away, and does not become pooled to then refreeze. When heating a driveway area we recommend that trace heating cables are installed into the drainage channels to ensure complete clearance.
Installation methods
There are a number of different installation methods, although all of them involve fixing down outdoor heating cable to Heat Fix metal bands or zip-tying it onto reinforcement mesh fabric or rebar. A rough overview of the three most popular installation methods is detailed below; please contact Heat Mat technical support for more details on 01444 247020.
Asphalt
The main issue to consider when installing heating cables beneath asphalt is to ensure that the heating cables do not come into contact with hot asphalt. The normal method of installation would be to level the current surface. If the surface is concrete or similar Heat Fix strips can be nail-gunned to the base and the cable installed onto these or alternatively reinforcement fabric can be laid. If the surface is not concrete or similar a layer of 30mm of sand or finely crushed stone should be laid with a reinforcement fabric placed on top of this, and the cables zip-tied in place. A minimum of a 10mm layer of sand should then be laid on top of the cables. The asphalt should be allowed to cool to approximately 100ºC, before laying it over the sand, to ensure the cables are not damaged. The asphalt layer should be at least
55mm thick. Heat Mat supply specialist hot-asphalt cables which can be used directly beneath hot asphalt which often simplifies the installation. Please contact
Technical Support for more information.
Block paving
Care must be taken not to drop any paving slabs onto the cable during the installation process as it could damage the heating system. The normal method of installation would be to level the current surface, lay a 60mm layer of sand/grit and compact this as required. A reinforcement fabric would then be laid on top and the heating cables zip-tied in place. A further 40-50mm layer of sand/grit would then be laid on top and this would be compacted by hand to ensure no damage to the heating cables.
The block paving could then be laid, to achieve the greatest benefit from the heating system the blocks should be between 50 and 80mm thick.
Concrete
Heating cables are often installed into concrete bases as concrete is particularly prone to damage from rock salt and freeze/thaw activity. The standard installation method would be to level the existing base before covering it with a support layer of sand/grit 30-40mm deep. A reinforcement fabric should then be laid and the cables can be zip-tied in place on this, before placing a layer of sand on top to protect the cables; this should be a minimum of 10mm thick.
The concrete can now be poured and it should form a layer with a minimum depth of 50mm, and the concrete mix must not include sharp stones as these could damage the cables.
16 Please visit our website www.heatmat.co.uk for further information
Ice & Snow Melting
Systems for Roofs
For roof heating there is no ‘standard’ output of heating that is required and Heat Mat specify the required output based on a wide variety of parameters including the pitch of the roof, its insulation level, the aims of the system and the buildings location. There are a number of ways of securing heating cables to the roof, however the main methods are either to use our standard fixing strips held down onto the roof using an external grade adhesive, or to use our specialist roof fixing.
These fixings have been designed to allow the cable to be secured onto virtually any type of roof, and the normal installation method for these is as follows.
The spacing of the fixings will have been specified by Heat
Mat and it is vital that this spacing is followed. To install the fixing plates you should first remove any loose material from the surface and then clean the area where the fixing will be placed using a solvent based de-greasing rag.
The adhesive that you will have been supplied with will normally come in 295ml dispensers and these are suitable for approximately 30 fixings. The glue must not be used in damp conditions or in temperatures below 10ºC.
A measure of adhesive roughly the same size as the fixing should be placed on the roof, and the fixing should be pushed into this adhesive with a slight forwards and backwards twisting movement to ensure that is firmly held.
Although a small amount of adhesive should be forced through the holes in the fixing, the adhesive should not be allowed to come through the fixing to the extent that it will prevent the cable from sitting between the two saddles on the fixing. The glue should be allowed to dry for 72 hours before installing the cables.
Once the glue has hardened the cables can be run out through the saddles and should then be cable tied into place by passing the cable tie around the cable and the two saddles. Care should be taken not to over tighten the cable tie, as the cables must be allowed to move slightly as they warm up and cool down. It is also vital that the cable ties supplied by Heat Mat are used as they are specifically selected for the appropriateness for this application, and normal ‘UV stable’ cable ties would have a very short life expectancy.
For support please call 01444 247020 17
Ice & Snow
Melting Systems for Gutters
As with roof heating systems, each gutter heating system is individually specified taking into account the local conditions. As a general rule, however, in a normal 125mm gutter we would recommend a double run of 7mm cable
(providing a total output of 40W per meter) to ensure that the gutter is kept clear of ice and snow.
It is important to heat the downpipes of any gutter heating system and in normal circumstances we recommend heating the first 1/3rd of the downpipe with two runs of the heating cable. In circumstances where air temperatures are expected to fall below -10ºC for a significant period of time we recommend heating the downpipe all the way down to ground level.
Heat Mat offer a variety of gutter heating cable fixing accessories including spacers for the cable within the gutters, and suspension beams, chains and cable guides to allow cables to be safely run in downpipes.
Gutter cable guides should be used to space the two runs of cable apart in the gutter to ensure that they do not touch, and these guides can be easily clipped over the side of the gutter and held in place with silicon sealant if required. The guides should be spaced roughly every 1m, and if possible we recommend installing the heating cables along the side of the gutter resting against the property.
Where the heating cable is going to pass down a downpipe it is essential to use a suspension beam to ensure that the cable does not have to support its own weight.
The suspension beam is placed above the downpipe in the gutter and the gutter protector is used to protect the gutter from excess heating as the cable passes into and then back out of the gutter. The plastic downpipe chain is fixed to the suspension beam, and the cable is held onto this chain using downpipe guides spaced at roughly
25cm intervals.
FRO-GUT-GUID
Cable guides for heating cable in standard gutters
FRO-GUT-CHAI
1m Chain for downpipe heating cable
FRO-GUT-DOWN
Cable guide for downpipe heating cable
FRO-GUT-BEAM
Suspension beam for downpipe chain
FRO-GUT-PROT
Cable protector for gutters and downpipes
18 Please visit our website www.heatmat.co.uk for further information
Heat Mat
Extended Warranty
Congratulations on your purchase of a
Heat Mat electric underfloor heating system.
The ultra-thin heating cable has been manufactured and supplied in the European Union by Heat-Com a/s/Heat Mat
Limited, and the following Warranty is supplied in accordance with the general product liability rules, as stated in Directive 85/374/CEE, and all relevant national laws. You are provided with a ten year warranty on the heating cable for eventual defects in material. Details and evidence of defects has to be presented to Heat-Com, Heat
Mat or an authorised UK or Ireland distributor for approval.
When your warranty is invoked, your damaged product will either be repaired or replaced free of charge to yourself.
Your warranty does not cover the following:
• Any faults caused by misuse.
• A system which has not been installed in accordance with the manufacturer’s guidelines.
• Any other subsequential or consequential damages.
To provide clarification, these damages could include the cost of repairs to walls, floors, tiles; professional fees; utility expenses. We would however pay for any reasonable damages which are a foreseeable consequence of Heat Mat’s negligence.
• Any system that had not been paid for in full.
• Heat-Com a/s/Heat Mat Limited are covered by an international insurance covering warranty payments.
In addition to the above warranty, Heat Mat offer a
5 year extension to the above warranty on your heating cable. To be covered by this extra warranty in addition to the above stipulations you must also:
• Register your product at www.heatmat.co.uk/
warrantyregistration within 90 days of purchase.
• Be able to provide your proof of purchase of the system, a normal retail invoice/receipt is sufficient for this purpose.
• Ensure the system has been installed in accordance with
Heat Mat’s installation guidelines and it must be protected by a suitable RCD.
• Ensure that all installation work is compliant with current
IEE wiring regulations and installations must comply with
Part ‘P’ of the Building Regulations. You should retain your Part ‘P’ certificate as proof of this.
If the above stipulations have been followed, Heat Mat will provide a five year warranty once the original ten year warranty expires for the heating cable. This warranty runs for the life of the floor covering above the original installation. This warranty covers manufacturing defects in the heating cable supplied. Details and evidence of defects has to be presented to Heat Mat or an authorised
UK or Ireland distributor for approval. When your warranty is invoked, your damaged product will either be repaired or replaced free of charge to yourself.
The repair or replacement of your system is the only remedy available to you under these warranties.
None of the above warranties affect your statutory rights. Heat-Com a/s and Heat Mat Limited will in no event be liable for consequential losses or secondary charges including, but not restricted to, the cost of replacing or repairing floor coverings, any costs associated with utility expenses or running costs, professional fees relating to trades peoples’ subsequent work or any other damage caused to material items.
Heat Mat Limited,
Ashwyn Business Centre,
Marchants Way,
Burgess Hill. RH15 8QY
T 01444 247020
F 01444 247121 www.heatmat.co.uk
For support please call 01444 247020 19
Please complete and display at your distribution board.
Warning
This building is fitted with Heat Mat 100% earth shielded electric underfloor heating utilising a
230Vac supply.
Do NOT pierce the floors above the system with nails, screws or other fasteners.
(see installer diagram for heater positioning)
Do NOT expose the floor to thermal blocking or attempt to reduce the size of the heated floor area.
(check suitability of floor covering with manufacturer & that furniture has 10mm (min) air void beneath it.)
In the event of flooding or when carrying out any repairs or alterations disconnect the Under Floor Heating and contact your electrician or
Heat Mat for advice
Details of Installation:
Electricians Name: Signature:
Company Name:
& Address:
Date:
Room with heating Installed:
Total Wattage of system:
Please list the product code and test results of each element after installation (compare to install guide for rated resistance)
Product Code Resistance Rating Insulation Test Passed
Heat Mat Ltd - Tel No: 01444 247020 see .www.heatmat.co.uk for more under floor heating solutions
This warranty card should be left with the thermostat user manual, Heat Mat system installation guide and the installer's heater layout & wiring diagrams to meet IEE Wiring regulations (17th Edition - section 753). These items should be permanently fixed near the relevant distribution board.
Art No. 02000053
Art No. 02000053
Heat Mat Limited, Ashwyn Business Centre,
Marchants Way, Burgess Hill. RH15 8QY
www.heatmat.co.uk
www.heatmat.co.uk
Reproduction of part or all of the contents of this fitting guide in any form is prohibited
Reproduction of part or all of the contents of this fitting guide in any form is prohibited other than with the express written permission of Heat Mat Limited.

Public link updated
The public link to your chat has been updated.
Advertisement
Key features
- Robust, 17th Edition and Part L Compliant
- 6mm Red In-screed Heating Cables
- 7mm Black Outdoor Heating Cables
- Ice & Snow Melting Systems
- Driveway Heating Mats
- Ice & Snow Melting Systems for Roofs
- Ice & Snow Melting Systems for Gutters
- For internal heating systems
- For external heating systems