Evolis: versatility
Evolis circuit breakers are used to protect and control public or industrial medium voltage electrical distribution networks.
Evolis is indoor switchgear that is particularly suited to the production and renovation of HV/MV, MV/MV and MV/LV sub-stations.
It is suitable for the protection of all types of application: cables, lines, motors, capacitors, transformers, bus sectioning of sources, etc
Schneider Electric
2 versions adapt to your fixed or withdrawable installation:
Full version
withdrawable with cradle
Modular version
basic circuit breaker with kits delivered in separate
MV catalogue Merlin Gerin
7
Evolis: performance
What does Evolis offer you?
The electrical characteristics are given in the circuit breaker designation
c
3 rated voltages
v
7.2 kV index 7 v 12 kV index 17 v 17.5 kV index 17.
c
3 breaking capacities
v
25 kA index P1 v 31.5 kA index P2 v 40 kA index P3.
c
4 rated currents
630, 1250, 1600, 2500 A.
c
The rating plates on the front of the circuit breaker also show the breaking capacity: v yellow: 25 kA v blue: 31.5 kA v red: 40 kA.
Full version
P3 : 40 kA
Rated breaking current
P2 : 31,5 kA
P1 : 25 kA
630 A
2500 A
1250 A
Rated current
2500 A
1250 A
2500 A
17,5 kV
Modular version
P3 : 40 kA
Rated voltage
7,2 kV
17,5 kV
Rated breaking current
P2 : 31,5 kA
P1 : 25 kA
Rated current
630 A
2500 A
1250 A
2500 A
1600 A
2500 A
1250 A
2500 A
1250 A
1250 A
8
MV catalogue Merlin Gerin
Schneider Electric
Evolis: heavy duty and innovative
How does Evolis eliminate faults?
Electrical endurance
A magnetic field is applied along the axis of the vacuum interrupter contacts.
This process maintains the arc in a diffuse mode even at high current values.
It ensures optimum distribution of the energy over the contact surface thus avoiding localised hot spots.
c
The advantages of this technique: v a very compact vacuum interrupter v
low dissipation of arcing energy in the bulbs.
Evolis is in conformity with highest electrical endurance class
(IEC 60 056: class E2).
Mechanical endurance
c This magnetic field is generated by a patented external coil which surrounds the contact zone. This solution provides many advantages: v
a simplified and therefore reliable vacuum interrupter v heavy duty contacts which do not distort during repeated switching operations v considerable reduction in control mechanism energy.
c For the first time, a low voltage device control mechanism has been integrated in a medium voltage circuit breaker. The Masterpact control mechanism used on
Evolis provides the benefits of a system that has proven itself for over 10 years on hundreds of thousands of installations.
Evolis is in conformity with most demanding mechanical endurance class
(IEC 60 056: class M2)
An integrated protection chain
The Sepam 1000
+
protection unit integrated with Evolis together with innovative current sensors, provide you with a comprehensive metering, protection and energy management chain.
c A high performance and economical solution v Sepam 1000
+
, through its modular offer, proposes a cost effective solution adapted to every requirement v one single sensor reference covers the circuit breaker's full operating range.
c
Easy to control and to install
v all components in the protection chain are catalogued and delivered quickly v
current sensors, developed in the circuit breaker environment, are simply mounted on the busducts v the operation of the entire protection chain with the Evolis circuit breaker has been extensively tested.
c
The power of a multifunctional digital unit
Sepam 1000
+
is not a simple protection relay, it is a multifunctional unit notably providing: v circuit breaker diagnosis functions (number and time of switching operations, rearming time, cumulated switched A
2
) v
direct circuit breaker control whatever release unit type v remote equipment operation through the Modbus communication option.
Schneider Electric MV catalogue Merlin Gerin
9
Evolis: tailored to your requirements
What does Evolis offer you?
Circuit breakers that combine simplicity of selection and richness of offer.
c
2 versions are proposed:
v
fullversion comprising the withdrawable circuit breaker and its cradle
v
modular version comprising separately delivered kits.
c
"Universal" accessories can be added to either version.
E.g:
coil, contact, motor, connection, inter-locking systems, etc
Full version: a fully assembled and tested unit
c
As standard, the circuit breaker is equiped with all the components required for "ready to use" withdrawable installation in metal clad cubicles.
This unit is easy to integrate in a cubicle environment, all it needs is mechanically fixing in place. An installation guide explains the required operations in detail.
c
This version provides the guarantees of a highly reliable unit, whose components function in perfect harmony. Critical points such as inter-locking systems, dielectric withstand and temperature rise have been checked thoroughly during design.
It is a system that is fully integrated and tested by the manufacturer, in conformity with IEC standards 60 298 and 60 056.
10
MV catalogue Merlin Gerin
Schneider Electric
Modular version: high added value accessories
c The circuit beaker is proposed in its most simple configuration.
In this case it can be combined with additional functions, to satisfy various requirements.
c This version offers maximum flexibility to adapt to constraints in existing cubicles or to operating specifications: v retrofit: fixed and withdrawable installation v block-type cubicle or fenced sub-station: fixed or removable installation v compartmented cubicle: fixed and withdrawable installation.
c The panel builder chooses the components he needs for a "customised" solution tailor made to his know-how.
Build your own version…
Schneider Electric MV catalogue Merlin Gerin
11
Evolis: the commitment of a major manufacturer
What guarantees does Evolis provide?
Conformity with standards
ccccc Conformity with standards is a guarantee of suitability for the required function, the very basis of the contract between the supplier and the customer: vvvvv dependability vvvvv operator safety.
It allows specifications to be fully satisfied whilst complying with local contraints.
During its design phase, Evolis was subjected to a series of tests which confirmed excellent performance levels, beyond the standards requirements.
ccccc Type testing: vvvvv dielectric tests vvvvv temperature rise vvvvv breaking capacity vvvvv thermal withstand vvvvv mechanical endurance vvvvv electrical endurance.
ccccc Specific testing: vvvvv ageing vvvvv transport and storage
N.B.:
IEC 60 694: common specifications for high voltage switchgear and controlgear standards
IEC 60 056: high voltage alternating current circuit breakers
IEC 60 298: A.C metal-enclosed switchgear between 1 kV and 52 kV.
Comment: for more information, consult the IEC organisation site: www.iec.ch.
Guaranteed quality
Schneider Electric integrates a functional organisation in each of its units with the main mission of checking quality and overseeing compliance with standards.
The quality system, for the design and manufacture of Evolis circuit breakers, is certified to be in conformity with the requirements of ISO 9001 and ISO 9002 quality assurance standards.
c
ISO 9001: quality system for design/production and installation c ISO 9002: quality system for production and installation c IQNET: international certification network.
Systematic control
During manufacture, each circuit breaker is subjected to routine systematic testing, with the aim of checking both quality and conformity.
c
Control of vacuum interrupters
Each bulb, sealed and airtight, is checked for the quality of the vacuum obtained.
This pressure measurement is based on the proven "magnetron discharge" method.
Using this sophisticated procedure, measurement is very precise and does not require access to the inside of the bulb, thus not affecting the airtight seal.
c
Control of the circuit breaker
A rigorous set of tests and measurements is carried out on each circuit breaker.
The results obtained are reported on and signed off by the quality control department on the test certificate for each device, thereby guaranteeing product traceability.
Respecting the environment
c
Schneider Electric sets itself the goal of
v actively participating in environmental protection, from a circuit breaker's design right through to its end of life v
complying with the environmental requirements of both its customers and end users of its products.
c
For Evolis circuit breakers
v development teams integrated the product's end-of-life right from the design stage. The product is easy to dismantle, all the materials used are recyclable and non-polluting v plastic parts are marked to identify the material v the circuit breakers are produced in factories which respect the environment.
Our subsidiary at Aubenas, France has been awarded the ISO 14001 standard certification (environmental management system).
Comment: for more information, consult the ISO organisation site: www.ISO.CH
Schneider Electric MV catalogue Merlin Gerin
13
Presentation
Evolis: simplicity and rapidity
How Evolis makes your life easier?
Choice
Evolis circuit breakers offer a comprehensive and rational range: c 3 operating voltages (7.2 kV - 12 kV - 17.5 kV) c 3 breaking capacities (25 kA - 31.5 kA - 40 kA) c
4 current ratings (630 - 1250 - 1600 - 2500 A) c 1 common range of accessories and auxiliaries c 2 versions: complete and modular.
Ordering and delivery
c You can order v the cradle before the circuit breaker v a specific release unit, at the last moment, that you will easily be able to install yourself.
c Due to delayed locally implemented customising, you are delivered quicker.
Installation
Evolis is easy to incorporate in cubicles.
c
3 phase to phase distances (145 - 185 - 240 mm) c Optimisation of volumes: one single height and depth throughout the range c Electrical auxiliaries are interchangeable throughout the range c Adjustable device height in the cubicle c Variable phase to phase connection points.
Operation
Increased safety
Evolis has been designed and industrialised to provide maximum safety for operators whilst guaranteeing the simplicity and rapidity of operations.
c Protective metal shutters c Safety interlocking systems to avoid operator errors when racking in or out c Racking in/out possible with the door closed.
Reduced maintenance
c
No preventive maintenance (lubricating, calibrating) before 10,000 switching cycles at the rated current c
Contact wear diagnosis is possible through a measurement on the pole unit c Electrical auxiliairies are easily mounted on site (all you need is a screwdriver) c Common stock of replacement parts with the
Masterpact
circuit breaker c
Diagnosis of the circuit breaker's functional chain using Sepam 1000
+
.
Evolis circuit breaker
Masterpact circuit breaker
14
MV catalogue Merlin Gerin
Schneider Electric
From pre-engineering to switchboard composition, a "toolkit" exists for panel builders to highlight their know-how and optimise their work around Evolis.
Tools to partner your know-how
Design guide
This document provides you with all the technical recommendations you require for your calculations when designing cubicles and incorporating equipment in conformity with IEC standard 60 298.
E.g.: v
defining the switchgear v dielectric strength v busbar calculation v
temperature rise calculation v definition of IP protection index.
Electronic catalogue
This "electronic" selection guide will rapidly become an everyday tool.
Several access points are proposed to discover the offer. It automatically provides the price of the device and an order form once you have selected your Evolis version.
Installation guide
This document provides you with all the information and recommendations you need to incorporate the circuit breaker and its accessories in a cubicle.
E.g.: v dimensions and space requirements v
mechanical interface v power circuit connection v auxiliary connection v
layout diagrams.
AUTOCAD library
For easier and more reliable integration of Evolis in a cubicle environment, an extensive library of dimensional drawings and electrical layout diagrams is available in AUTOCAD format (format DXF/DWg/WMF).
Schneider Electric
Internet site
Missing a certificate? Lost a technical manual?
Connect up to our web site where you can download all of our technical documentation.
MV catalogue Merlin Gerin
15
Circuit breaker
This chapter provides useful information in selecting the performance levels of your
Evolis circuit breaker.
It also describes all the functions associated to each versions.
Panorama
Full version
Performance tables
Power circuit
Sensors
Racking in
Support frame
Modular version
Performance tables
Connecting the power circuit
Power circuit
Sensors
Racking in
Support frame
Fitted accessories
Opening circuit
Remote control
Indication
Locking
Dimensions
Full version
Modular version
33
33
35
37
38
39
39
40
26
26
28
29
30
31
32
18
20
20
22
23
24
25
Schneider Electric
MV catalogue Merlin Gerin
17
Panorama
"Ready to close" contact
DV2
Ue (V)
220/440
525
690
Icu
(kA)
100
100
85
Icw
85kA/1s cat.B
Ics = 100% Icu
50/6 0Hz
IEC 947-
EN 6
UTE
0947
VDE
2
-2
CEI UNE
AS NEMA
BS
C.b. "open position" pad locking
C.b. "open position key locking
Push button disabling
Bloc of 4 o/c position contacts closing release
Opening shunt trip release
18
COM
UC1
UC2
UC3
UC4
M2C
SDE2
/RES
Low energy release
00399
Operation counter
MV catalogue Merlin Gerin
Charging motor and mechanism
Schneider Electric
Panorama
Schneider Electric
Shutter
LVsensors
Bushing
Finger
Cluster
Arm
Cradle base
1 contact for
"racked in confirmation"
Bloc of 4 racked in/out position contacts
DV2
Ue (V)
220/
440
525
690
Icu (kA)
100
100
85 cat.B
100
Ics =
Icw
85kA
/1s
% Ic u
IEC
947-
-2
EN 6
0947
2
UTE VDE
BS CEI
50/6 0Hz
UNE AS N
EMA
Circuit breaker
C
C
Racking truck
MV catalogue Merlin Gerin
Support frame
19
Full version
Performance tables
7P
1
1250 to 17P
3
2500
Common characteristics according to IEC 60 056
rated frequency short-time withstand current rated peak withstand current rated short circuit making current operating sequence operating times mechanical endurance electrical endurance capacitive current braking opening breaking closing class number of operations with maintenance class number of operations
fr
Ik for tk = 3 s
Ip
(Hz)
(kA) rms peak (kA) peak (kA) ms ms ms
25 kA
31.5 kA
40 kA
50 & 60
Ik = Isc
Ip = 2.5 & 2.6 Ik
= 2.5 & 2.6 Isc
O - 3 mn - CO - 3 mn - CO
O - 0.3 s - CO - 3 mn - CO
O - 0.3 s - CO - 15 s - CO
< 50
< 60
< 65
M2
25000
E2
100
70
50
C1 class
Characteristics according to IEC 60 056
rated voltage rated insulation level rated short-circuit breaking current rated normal current (-25
°
C,+40
°
C) climatic version
Ur
Ud
Up
(kV) rms
(kV) rms
(kV) peak
Isc
(kA) rms
Ir
(A) rms
-25
°
C + 40
°
C
Installation and connections
phase distance between poles between MV connections on the cradle dimensions breaker and cradle (mm) mass breaker and cradle
(mm)
(mm)
Width (W)
Depth (D)
Height (H)
(kg)
7P1-1250
7.2
20
60
25
1250 c
7P2-1250
7.2
20
60
31.5
1250 c
7P2-2500
7.2
20
60
31.5
2500 c
7P3-2500
7.2
20
60
40
2500 c
17P1-630
17.5
38
95
25
630 c
17P1-1250
17.5
38
95
25
1250 c
145 & 185
145…170
185…210
592 & 700
1140
960
118 & 123
185
185…210
700
1140
960
128
240
240…265
880
1140
960
194
240
240…265
880
1140
960
194
145 & 185
145…170
185…210
592 & 700
1140
960
118 & 123
145 & 185
145…170
185…210
592 & 700
1140
960
118 & 123
20
MV catalogue Merlin Gerin Schneider Electric
Full version
145 145
H
W
185 185
W
H
240 240
W
H
17P1-2500
17.5
38
95
25
2500 c
17P2-630
17.5
38
95
31.5
630 c
17P2-1250
17.5
38
95
31.5
1250 c
17P2-2500
17.5
38
95
31.5
2500 c
240
240…265
880
1140
960
194
185
185…210
700
1140
960
128
185
185…210
700
1140
960
128
240
240…265
880
1140
960
194
17P3-1250
17.5
38
95
40
1250 c
17P3-2500
17.5
38
95
40
2500 c
240
240…265
880
1140
960
194
240
240…265
880
1140
960
194
Schneider Electric MV catalogue Merlin Gerin
21
Full version
Power circuit
Power circuit
Composition
c The power circuit comprises: v mobile contacts made up of disconnecting clusters and arms mounted on the circuit breaker v fingers located on the cradle and insulated by bushings and metal shutters.
c This unit gives perfect control of dielectric and temperature rise considerations and has been validated by testing.
c
Customer connection is easily achieved outside the cradle: v on vertical copper terminals integrated in the bushing v through a set of connectors, also used on the basic circuit breaker unit.
Connection variants described on page 28 are possible.
Comments:
c The dielectric withstand values shown in the performance tables are guaranteed without the use of these connectors.
c The panel builder should check the overall cubicle connection configuration; typical examples are given in the installation guide.
3 sets of connectors
22
MV catalogue Merlin Gerin Schneider Electric
Full version
Sensor CVv120
Sensor CVv200
Sensors
Function
These low power sensors provide accurate current measurement to the protection function when the Evolis circuit breaker is associated with the Sepam1000
+
.
Composition
The sensor is delivered ready to be directly plugged to the Sepam unit.
Mechanical characteristics
c Mounted directly on the Evolis withdrawable circuit breaker cradle.
The sensors are simply located on the bushings and fixed using a screw.
Each sensor covers the full operating range of the corresponding circuit breaker.
c Connection to the Sepam 1000
+
is achieved using an armoured cable which is attached to each sensor.
Electrical characteristics
c In conformity with standard IEC 60044-8, defining voltage output current sensors c Usable for nominal currents of 25 A to 3150 A c Class 0.5 over the range 100 - 4000 A c The choice of sensor is solely based on the phase to phase distance of the cradle: v 120 mm diameter for phase to phase distances of 145 and 185 mm v 200 mm diameter for phase to phase distances of 240 mm c Current sensors deliver a voltage output at a ratio of 100 A / 22.5 mV.
Operation
An input terminal is provided on the Sepam 1000
+
for testing and maintenance purposes. A test cabinet interface can be ordered to check the correct operation of sensors.
Schneider Electric MV catalogue Merlin Gerin
23
Full version
Shutters
Auxiliary contacts
Crank system
24
Racking in
Composition
The "racking in" function is provided by: c The racking truck supporting the circuit breaker (mobile part).
c The cradle (fixed part).
Operating procedure
c The circuit breaker moves through 3 stable states: v service: circuit breaker racked in and locked in place; low voltage connected v test: circuit breaker racked out and locked in place; low voltage connected v
extracted: the circuit breaker can be unlocked and extracted from the cubicle, with no interlocking.
300 service test extracted
Functions
c Interlocking between circuit breaker control and cradle position makes operation safer: racking in or out only when the circuit breaker is open.
c Interlocking is also provided between the low voltage connector and the circuit breaker.
Racking in is only possible when the low voltage connector is connected.
c Earthing is automatically achieved throughout the whole racking in operation.
c Protective shutters placed on the cradle, prevent access to the racking fingers when the device is extracted (protection index: IP2X).
c For maintenance operations, it is possible to: v padlock the shutters in the closed position.
v unlock the shutters mechanism to access the racking fingers.
c
An inter-cubicle fool-proof system avoid racking in by mistake a circuit breaker with a different I n rating. This system is mounted on the racking base.
Part of it has to be assembled by the panel builder on the cubicle floor.
Accessories
c A set of auxiliary contacts: v 4 racked in/racked out position contacts v 1 contact indicating that the cradle is locked in the racked in position.
c
A propulsive system combined with a crank makes racking in and racking out easier. It allows the operation to be carried out with the door closed. Interlocking prevents to insert the crank until the racking base selector has been positioned to the "racked out" position.
c
Additional earthing for the base can be provided by a copper brush.
c
A key locking system (Ronis or Profalux) for the racked out position on the circuit breaker will provide increased safety when working downstream of the circuit breaker. This system is combined with an earthing disconnector (refer to page 66).
MV catalogue Merlin Gerin Schneider Electric
Full version
Support frame
Function
c The support frame allows: v A "cassette" type circuit breaker to be transformed into a "roll on the floor" type circuit breaker by adding an intermediary structure v this structure can be positioned at a variable height according to your cubicle
Support frame
Composition
c A roller kit will be provided with a drawing to allow the panel builder to adapt the height to its need inside his cubicle.
Schneider Electric MV catalogue Merlin Gerin
25
Modular version
Performance tables
12P
1
630 at 17P
3
2500
Common characteristics according to IEC 60 056
rated frequency short-time withstand current rated peak withstand current rated short circuit making current operating sequence operating times mechanical endurance electrical endurance capacitive current breaking opening breaking closing class number of operations with maintenance class number of operations
fr
Ik for tk = 3 s
Ip
(Hz)
(kA) rms peak (kA) peak (kA) ms ms ms
25 kA
31.5 kA
40 kA
50 & 60
Ik = Isc
Ip = 2.5 & 2.6 Ik
= 2.5 & 2.6 Isc
O - 3 mn - CO - 3 mn - CO
O - 0.3 s - CO - 3 mn - CO
O - 0.3 s - CO - 15 s - CO
< 50
< 60
< 65
M2
25000
E2
100
70
50
C1 class
Characteristics according to IEC 60 056
rated voltage rated insulation level rated short-circuit breaking current rated normal current (-25
°
C,+40
°
C) climatic version
Ur
(kV) rms
Ud
(kV) rms
Up
(kV) peak
Isc
(kA) rms
Ir
(A) rms
-25
°
C + 40
°
C
Installation and connections
phase distance without MV connections with MV connections
(mm)
(mm) dimensions (mm) mass
Width (W)
Depth (D)
Height (H)
(kg)
7P1-1250
7.2
20
60
25
1250 c
145 & 185
145…170
185…210
470 & 550
429
530
50
7P2-1250
7.2
20
60
31.5
1250 c
7P2-2500
7.2
20
60
31.5
2500 c
7P3-2500
7.2
20
60
40
2500 c
185
185…210
550
429
530
50
240
240…265
660
429
530
70
240
240…265
660
429
530
70
17P1-630
17.5
38
95
25
630 c
17P1-1250
17.5
38
95
25
1250 c
145 & 185
145…170
185…210
470 & 550
429
530
50
145 & 185
145…170
185…210
470 & 550
429
530
50
26
MV catalogue Merlin Gerin Schneider Electric
Modular version
145 145
H
W
185 185
W
H
240 240
W
H
17P1-1600 17P1-2500
17.5
38
95
25
1600 c
17.5
38
95
25
2500 c
17P2-630
17.5
38
95
31.5
630 c
17P2-1250
17.5
38
95
31.5
1250 c
17P2-1600
17.5
38
95
31.5
1600 c
17P2-2500
17.5
38
95
31.5
2500 c
17P3-1250
17.5
38
95
40
1250 c
17P3-2500
17.5
38
95
40
2500 c
145 & 185
145…170
185…210
470 & 550
429
530
50
240
240…265
660
429
530
70
185
185…210
550
429
530
55
185
185…210
550
429
530
55
185
185…210
550
429
530
55
240
240…265
660
429
530
70
240
240…265
660
429
530
70
240
240…265
660
429
530
70
Schneider Electric MV catalogue Merlin Gerin
27
Modular version
Terminal
3 sets of connectors
Connecting the power circuit
Composition
c The basic circuit breaker unit is equipped with copper, drilled connection terminals, located at the top and bottom of the breaking poles c
Connectors are mounted on these terminals using the associated bolt work.
They enable several connection variants.
The same connectors can be also mounted on the bushing connection terminals
(see page 22).
Fixed connectors
horizontal connectors (H) vertical connectors (V) mixed connectors
A horizontal connector becomes a vertical connector by a 90
°
rotation.
Variable distance connectors
horizontal spreading connectors (H) vertical spreading connectors (V)
The spreading connector enables the connecting distance to be increased by
0 to 25 mm.
Combined solution
example
Comments:
c The dielectric withstand values shown in the performance tables are guaranteed without the use of these Evolis connectors.
c These connectors may be fitted with either bare copper, tin plated copper or tin plated aluminium conductors without any particular protection.
c The dimensions and shapes of these conductors should be determined by the panel builder according to the required dielectric and temperature rise characteristics of the full connection system; typical examples are given in the installation guide.
28
MV catalogue Merlin Gerin Schneider Electric
Modular version
Cluster and finger
Arm, finger, bushing and cluster
Power circuit
Composition
The panel builder produces the power circuit himself. He has the possibility of integrating one of these two highly technical units.
c Clusters and fingers c
Arms, clusters, fingers and bushings
Cluster and finger
c The tulip type cluster has a shape which provides maximum contact surface whilst optimising heat dissipation. Moreover, in the case of short-circuit, it offers good compensation characteristics for electrodynamic forces.
Its degrees of freedom avoid the use of an interchangeability testing tool; a simple adjustment guide is all that is required.
c The finger is a component designed specifically for the cluster, regarding its shape, tolerances and materials. Contact between the finger and the cluster is guaranteed by type testing: 1000 racking in-out operations.
Arm, cluster, finger and bushing
c The choice of a cylindrical shape for the arm optimises the dielectric withstand and eliminates the need for additional insulation.
c
The cylindrical shape of the bushing provides excellent dielectric withstand.
c
It includes a connection terminal that can be fitted with the connectors described on page 22.
Comment:
c Performances of the overall unit shall be controlled by the panel builder.
c Conditions of installation for both units described above are given in the installation guide.
Schneider Electric MV catalogue Merlin Gerin
29
Modular version
Sensor CVv120
Sensor CVv200
Sensors
Function
These low power sensors provide accurate current measurement to the protection function when the Evolis circuit breaker is associated with the Sepam1000
+
.
Composition
The sensor is delivered ready to be directly plugged to the Sepam unit.
Mechanical characteristics
c Mounted directly on the bushings.
The sensors are simply located on the bushings and fixed using a screw. Each sensor covers the full operating range of the corresponding circuit breaker.
c Connection to the Sepam 1000
+
is achieved using an armoured cable which is attached to each sensor.
Electrical characteristics
c In conformity with standard IEC 60044-8, defining voltage output current sensors c
Usable for nominal currents of 25 A to 3150 A c Class 0.5 over the range 100 - 4000 A c
The choice of sensor is solely based on the phase to phase distance of the cradle: v
120 mm diameter for phase to phase distances of 145 and 185 mm v 200 mm diameter for phase to phase distances of 240 mm c Current sensors deliver a voltage output at a ratio of 100 A / 22.5 mV.
Operation
An input terminal is provided on the Sepam 1000
+
for testing and maintenance purposes. A test cabinet interface can be ordered to check the correct operation of sensors.
30
MV catalogue Merlin Gerin Schneider Electric
Modular version
Racking in
Cradle base
○
○
○
○
○
○
○
○
Racking truck
l Composition
The "racking in" function is provided by: c The racking truck supporting the circuit breaker (mobile part).
c
The cradle base (fixed part).
Operating procedure
c The circuit breaker moves through 3 stable states: v service: circuit breaker racked in and locked in place; low voltage connected v
test: circuit breaker racked out and locked in place; low voltage connected v extracted: the circuit breaker can be unlocked and extracted from the cubicle, with no interlocking.
300
Auxiliary contacts
Service position Test position Extracted position
Functions
c
Interlocking between circuit breaker control and cradle position makes operation safer: racking in or out only when the circuit breaker is open.
c
Interlocking is also provided between the low voltage connector and the circuit breaker.
Racking in is only possible when the low voltage connector is connected.
c Earthing is automatically achieved throughout the whole racking in operation.
c An inter-cubicle fool-proof system avoid racking by mistake in a circuit breaker with a different I n rating. This system is mounted on the racking base. Part of it has to be assembled by the panel builder on the cubicle floor.
Accessories
c A set of auxiliary contacts: v
4 racked in/racked out position contacts v 1 contact indicating that the cradle is locked in the racked in position.
c A propulsive system combined with a crank makes racking in and racking out easier. It allows the operation to be carried out with the door closed. Interlocking prevents to insert the crank until the racking base selector has been positioned to the "racked out" position.
c Additional earthing for the base can be provided by a copper brush.
c A key locking system (Ronis or Profalux) for the racked out position on the circuit breaker will provide increased safety when working downstream of the circuit breaker. This system is combined with an earthing disconnector
(refer to page 66).
Crank system
Schneider Electric MV catalogue Merlin Gerin
31
Modular version
Support frame
Function
Fixed installation
c
The support frame enables: v a fixing support to be produced for the circuit breaker. Fixing to the ground is achieved using a roller kit. A drawing enables the interface to be produced between the rolling channel and the circuit breaker.
v
the "roller" function to be provided using the integrated rollers.
Support frame
Withdrawable installation
c The support frame allows: v a "cassette" type circuit beaker to be transformed into a "roller" type circuit breaker by adding an intermediary structure v this structure to be positioned at a variable height according to the cubicle.
32
MV catalogue Merlin Gerin Schneider Electric
Fitted
Accessories
Opening circuit
PF
MCH
MX1
XF
Composition
The basic circuit breaker equipment includes a shunt trip release unit (MX).
c It may also include the following options: v a second MX release v
or an under voltage shunt trip release (MN) v or an under voltage shunt trip release with time delay (MN + time delay unit) v and a low energy release (MITOP).
Opening mechanism circuit diagram
Circuit breaker equipped with an opening release ordre de déclenchement
MX ordre de déclenchement
MN ordre de déclenchement retardé retardateur ordre de déclenchement instantané
MN
COM
UC1
UC2
UC3
UC4
M2C
SDE2
/RES
SDE1
MITOP low energy release
Low energy release (MITOP)
This specific coil actuates the opening mechanism of the poles to trip the circuit breaker. It comprises a low energy consumption electromagnet.
Characteristics supply threshold response time of the circuit breaker at Un
direct current
0.6 A < I < 3 A
11 ms
Any tripping caused by the Mitop release is indicated momentarily by an SDE type changeover contact. This Release Unit also includes a coil enabling the remote rearming of the SDE contact.
Comment
To use the MITOP release requires the adjustment of a time delay to be set by the protection relay in order to ensure a circuit breaker operating time of 45-50ms.
Schneider Electric MV catalogue Merlin Gerin
33
Fitted
Accessories
MN undervoltage release
Time delay unit for MN
MX shunt trip release
Opening circuit
Undervoltage shunt trip release (MN)
This release causes the instant opening of the circuit breaker when its supply voltage drops below a value of between 35 and 70% of its rated voltage. If the release is not energised, closing the circuit breaker (manually or electrically) is impossible. Any attempt to close causes no movement of the main contacts.
Closing is authorised when the supply voltage of the release reaches 85% of its rated voltage.
Characteristics supply threshold
V AC 50/60 Hz
V DC opening closing
consumption (VA or W) response time of the circuit breaker at Un
24/30
24/30
0.35 to 0.7 Un
0.85 Un
20
90 ms
±
5
48/60
48/60
100/130
100/130
200/250
200/250
Time delay unit for MN
To eliminate spurious tripping of the circuit breaker during momentary voltage drops MN's action is time-delayed. This function is achieved by adding an external time delay to the MN release circuit (delay is ajustable).
This unit is placed outside of the circuit breaker and can be inhibited by an emergency stop button to obtain instant opening.
Characteristics supply threshold
V CA 50/60 Hz
V CC opening closing
consumption (VA or W) response time of the circuit breaker at Un
48/60
48/60
0.35 to 0.7 Un
0.85 Un
200
0.5 s - 0.9 s - 1.5 s - 3 s
100/130
100/130
200/250
200/250
Shunt trip release (MX)
This causes instant opening of the circuit breaker when energised.
Permanent energising of the MX locks the circuit breaker in the "open" position.
Characteristics supply
V CA 50/60 Hz
V CC
threshold consumption (VA or W) response time of the circuit breaker at Un
24/30
24/30
0.7 to 1.1 Un pickup: 200 latched: 4.5
50 ms
±
10
48/60
48/60
100/130
100/130
200/250
200/250
34
MV catalogue Merlin Gerin Schneider Electric
Fitted
Accessories
MN
MX2
MX1
XF
PF
MCH
MX1
XF push O
FF push
ON d i s c h a r g e d
O OFF
I ON
Circuit breaker equipped with remote control
Remote control
Function
c The remote control enables remote opening and closing of the circuit breaker.
c In the case of continuous opening and closing orders, the remote control unit blocks the device in the open position as standard: the anti-pumping function.
This function gives absolute priority to the opening order, but and also it stops closing and thus avoids the device being locked in an indefinite opening-closing cycle: v the opening and closing coils may be fed power on a constant basis to achieve an electrical type locking: there is no self-breaking contact inside the device.
v
the interlocking between the opening and closing orders, whatever their causes, is achieved as standard within the device's control mechanism.
Remote control circuit diagram
ressorts armés ordre d'ouverture ordre de fermeture prêt
à fermer fermé
CH
MCH
MX XF
PF OF OF
OF
Composition
c
The remote control comprises: v charging motor and associated mechanism (MCH) equipped with a "springloaded" limit switch (CH) v
two shunt trip releases:
- a closing release (XF)
- an opening release (MX).
c It can be added to by: v
a "ready to close" contact PF v a second block of 4 contacts for indication of the O/C position of the device.
Schneider Electric MV catalogue Merlin Gerin
35
Fitted
Accessories
Shunt trip release XF/MX
Remote Control
Charging motor and associated mechanism (MCH)
The MCH unit arms and rearms the energy storage springs as soon as the circuit breaker is closed. This enables instant reclosing of the device after opening.
The arming lever is only used as back up control in the absence of an auxiliary voltage.
The MCH is equipped as standard with a CH limit switch. This contact indicates the
"armed" position of the mechanism (spring armed).
Characteristics supply
V AC 50/60 Hz
V DC
threshold consumption (VA or W) motor overcurrent arming time switching rate mechanical endurance
CH contact
24/30
0.85 to 1.1 Un
48/60
48/60
100/130
100/125
180
2 to 3 In during 0.1 s
4 s. max.
3 cycles per minute max.
10000 remote controlled opening operations for Evolis P1 and P2
5000 remote controlled opening operations for Evolis P3
10 A at 240 V
200/240
200/250
Shunt trip Release (XF) and (MX)
Closing release (XF)
This causes the remote closing of the circuit breaker when the control mechanism is armed.
Opening release (MX)
This causes the instant opening of the circuit breaker when energised and can be permanently energised or temporarily energised.
XF characteristics supply
V AC 50/60 Hz
V DC
threshold consumption (VA or W) response time of circuit breaker at Un
24/30
24/30
0.85 to 1.1 Un
48/60
48/60 pickup: 200 latched: 4.5
70 ms
±
10 for Evolis P1 and P2
80 ms
±
10 for Evolis P3
100/300
100/130
200/250
200/250
MX Characteristics supply
V CA 50/60 Hz
V CC
threshold consumption (VA orW) response time of circuit breaker at Un
24/30
24/30
0.7 to1.1 Un pickup: 200 latched: 4.5
50 ms
±
10 ms
48/60
48/60
100/300
100/130
200/250
200/250
36
MV catalogue Merlin Gerin Schneider Electric
Fitted assessories
00399
Operation counter
Rotary type O/C position contacts
Ready to close contacts PF
Indication
Operation counter (CDM)
The operation counter is visible from the front face. It totalises the number of switching cycles that the device performs.
"Open/closed" position contacts (OF )
These contacts indicate the "open" or "closed" position of the circuit breaker.
c Rotary type change over contacts directly driven by the circuit breaker mechanism.
c Indicator contacts proposed v
in standard version for a relaying application v in low level version for control of plc's or electronic circuits. This version is compatible with the Sepam 1000
+ unit.
Characteristics delivered as standard maximum quantity breaking capacity (A)
cos ø : 0.3
AC12/DC12 standard
V AC
V DC
240/380
480
690
24/48
125
250 low level
V AC
V DC
24/48
240
380
24/48
125
250
3
11 min. load: 10 mA/24 V
6
6
6
2.5
10/6
10/6
6
10/6
0.5
0.3
10/6
3 min. load: 1 mA/4 V
5
5
5/2.5
0.5
0.3
10/6
3
10/6
10/6
3
"Ready to close" contact (PF)
c
The "ready to close" position of the circuit breaker is indicated by a mechanical indicator and a changeover contact PF.
c
This information simultaneously indicates that: v the circuit breaker is open v the stored energy springs are armed v there is no permanent closing order v there is no permanent opening order:
- safety opening order (2nd MX or MN)
- device locked in the open position with a key lock.
Characteristics delivered as standard max. quantity breaking capacity (A)
cos
ϕ
: 0.3
AC12/DC12 standard
0
V AC 240/380 5
480 5
1 minimum load: 10 mA/24 V
690
V DC 24/48
125
250
3
3
0.3
0.15
Schneider Electric MV catalogue Merlin Gerin
37
Fitted assessories
Locking
Push button disabling
Padlocking in the circuit breaker
"open" position
DV2
Icu (kA)
220/
440
525
100
100
85
690
Icw
85kA /1s cat.B
100
Ics =
% Icu
0Hz
50/6
IEC
EN 6
0947
UTE
947-
VDE
2
-2
BS
CEI UNE
EMA
Locking in the "open" position
Opening button
Closing button
Spring position indicator
Push button disabling
Main contact position indicator
Operation counter
Disarming the control springs
This feature guarantees operator safety when removing the circuit breaker front cover.
The auxiliary support located at the top of the control mechanism is then accessible when the springs are disarmed.
Push button disabling
This transparent screen prevents access to the circuit breaker opening and closing push buttons.
The device enables independent locking of the opening or closing button, it is often associated with an electrical motor (MCH).
c Locking is achieved either by: v 2 screws v
3 padlocks, not supplied v sealing.
Padlocking Sealing
Locking of the circuit breaker in the "open" position.
c The circuit breaker is locked in the "open" position by blocking the opening push button in the "pushed-in position": v using padlocks: 1 to 3 padlocks not supplied v using key locks: 1 or 2 different key locks supplied.
c
The key locks are of Profalux or Ronis type captive key, that becomes free once locked, and are offered according to the options, either: v 1 single key lock v 1 single key lock mounted on the device + 1 identical one delivered separately for interlocking with another device v
2 different key locks for double locking.
c Profalux and Ronis key locks are inter-compatible.
Key locking in the circuit breaker
"open" position
RONIS
38
MV catalogue Merlin Gerin Schneider Electric
Dimensions
Circuit breakers:
7 P1 - 1250
17 P1 - 630
17 P1 - 1250
Circuit breakers:
7 P1 - 1250
7 P2 - 1250
17 P1 - 630
17 P1 - 1250
17 P2 - 630
17 P2 - 1250
Circuit breakers:
7 P2- 2500
7 P3 - 2500
17 P1 - 2500
17 P2 - 2500
17 P3 - 1250
17 P3 - 2500
Schneider Electric
Full version
145 145 123
576
960
370
295
240
839
1142
300
185 185 155
686
960
370
295
240
839
1142
300
240 240 190
960
370
295
240
839
1142
866
300
MV catalogue Merlin Gerin
39
Dimensions
Circuit breakers:
7 P1- 1250
17 P1 - 630
17 P1 - 1250
17 P1 - 1600
Modular version
145 145 90
530
470
429
Circuit breakers:
7 P1- 1250
7 P2 - 1250
17 P1 - 630
17 P1 - 1250
17 P1 - 1600
17 P2 - 630
17 P2 - 1250
17 P2 - 1600
Circuit breakers:
7 P2- 2500
7 P3 - 2500
17 P1 - 2500
17 P2 - 2500
17 P3 - 1250
17 P3 - 2500
40
240 240 90
530
660
429
185 185 90
530
550
429
MV catalogue Merlin Gerin Schneider Electric
Schneider Electric MV catalogue Merlin Gerin
41
Protection, monitoring control and metering
Presentation
An integrated protection chain
Sepam 1000
+
Sepam Unit
Protection and metering
Sensors
Monitoring and control
Communication
Software
Powerlogic
Metering device
Dimensions
Sepam 1000
+
51
52
53
54
54
55
55
44
44
46
46
47
50
Schneider Electric MV catalogue Merlin Gerin-Telemecanique
43
Presentation
The Sepam 1000
+
protection unit combined with innovative current sensors, provides a full chain for metering, protection, monitoring and control.
An integrated protection chain
44
c A high performance and economical solution v Sepam 1000
+
, due to its modular offer, provides a cost-effective solution adapted to every requirement v
one single reference of sensors covers a large range of currents, from 100 to 3150A.
c
Easy to order and install
v all the components of the protection chain are referenced and deliverable very rapidly v
the current sensors, developed in the circuit breaker environment are simply mounted onto the bushings, v the functioning of the protection chain integrated in the Evolis circuit breaker has been fully tested and certified.
c
The power of a multi-functional digital unit
Sepam 1000
+
is not a simple protection relay, it is a multi-functional unit notably providing: v
circuit breaker diagnosis functions (number of switching operations, operating time, charging time, cumulative breaking current) v direct circuit breaker control whatever type of release v remote operation of the equipment through the Modbus communication option.
MV catalogue Merlin Gerin Schneider Electric
Presentation
An integrated protection chain
Sepam 1000
+
is a range of protection and metering units that is simple and reliable, intended to operate machines and electrical distribution networks in industrial installations and utility sub-stations.
More solutions
Sepam 1000
+
provides solutions adapted to each application providing an optimum cost/function ratio.
c Protection of sub-station incomers and feeders c
Protection of transformers c Protection of motors c Voltage protection for busbars.
More performances
Protections
c Protection against phase to phase and phase to earth short-circuits, with logic discrimination management c Earth fault protection that is insensitive to transformer switching c Detection of phase unbalance c RMS thermal protection capable of taking account of ambient temperature and different ventilation configurations.
Communication
Fully compatible with the Modbus standard, it enables remote operation of equipment: c Reading of all available information (measurements, logical states, settings, etc) c
Circuit breaker remote control.
Diagnosis
c Network diagnosis: trip currents, unbalance ratio, disturbance recording, etc.
c Circuit breaker diagnosis: number of switching operations, operating and charging time, cumulative A
2 broken, etc.
c Protection unit diagnosis: permanent self-testing, watchdog function, etc.
Monitoring and control
Circuit breaker control and indication logic programmed without auxiliary relays or additional cabling.
More modularity
c Optional modules can be easily added at any time: v
logic inputs/outputs v communication v temperature sensor module v analogic output module.
More simplicity
Easy cubicle installation
c
Compact basic unit, depth of less than 100 mm.
v flush-mounted on the front panel v or mounted inside the control compartment, the user-machine interface (UMI) can then be placed in the best position for operation purposes.
c Low power consumption limiting the size of auxiliary supply batteries.
User-friendly
c All information is accessible on the advanced UMI c Operator language of the advanced UMI can be customised c Direct setting of real values using manufacturer's data c Setting and operation software enabling the uploading and downloading of settings files amongst other things.
Schneider Electric MV catalogue Merlin Gerin
45
Sepam 1000
+
Sepam unit
2 Sepam units are available.
They can be distinguished by their type of user-machine interface (UMI)
With the "basic" UMI
c This basic unit offers a cost-effective response for: v installations not requiring local operation (control from a remote control and monitoring system) v replacement of electromechanical or analogic electronic protection devices.
c Its UMI only includes: v 11 signal lamps v 1 "reset" key to clear faults and to reset v 1 connection port for the RS232 link with the PC.
Remote advanced UMI module (DSM 303)
c Thinner and offering the functional features of the advanced UMI, it allows convenient installation on the front panel of the cubicle in the most effective position for operation.
c
This module is connected to the basic Sepam 1000
+
unit using a prefabricated
2m (CCA 772) or 4m (CCA 774) cable.
c A mounting plate is available to mount the basic Sepam 1000
+
at the back of the cubicle control compartment (AMT 840).
Unit with basic UMI
With the "advanced" UMI
This unit is an optimum response for local operation.
c Its easy-to-read UMI includes: v 11 signal lamps v A "graphic" LCD display, enabling display of metering values, parameter settings and alarm and operation messages v a 9 key pad with 2 usage modes:
- white keys for current operation: displaying measurements, diagnosis information and alarms
- blue keys for parameter and protection setting:
Access to device parameters and protection settings. Modification protected by password v 1 connection port for the RS232 link with the PC.
Unit with basic UMI and remote advanced UMI module
General characteristics
Supply voltage
48 to 250 VDC and 110 to 240 VAC
24 VDC
Operating conditions according to IEC 60 068
from -25
°
C to +70
°
C
Operating language
English/French
English/Spanish
English/Italian
English/local language
range
-20/+10%
-20/+50%
Unit with advanced UMI
46
MV catalogue Merlin Gerin Schneider Electric
Sepam 1000
+
Protection and metering
4 applications are available
Functions
Protection
phase overcurrent earth fault (or neutral) unbalance/negative sequence thermal overload phase undercurrent excessive starting time, locked rotor starts per hour undervoltage remanent undervoltage phase to phase undervoltage phase to phase overvoltage neutral voltage displacement overfrequency underfrequency recloser (4 cycles) thermostat / Buchholz temperature monitoring
(2)
Metering
phase current I1, I2, I3 RMS residual current Io average current I1, I2, I3 peak demand line phase current IM1, IM2, IM3 voltage U21, U32, U13 voltage V1, V2, V3 residual voltage Vo positive sequence voltage Vd/rotation direction frequency temperature measurement
(2)
Network diagnosis
tripping current I1, I2, I3, Io unbalance ratio / negative sequence current running hours counter termal capacity used operation duration remaining before overload tripping waiting time after overload tripping starting current and time start inhibit time delay, number of starts before inhibition disturbance recording
Switchgear diagnosis
cumulative breaking current
2 trip circuit supervision number of operations operating time charging time
Self-diagnosis
watchdog output relay test
(3)
Control and monitoring
circuit breaker / contactor control logic discrimination
4 addressable logical outputs
Additional modules
8 temperature sensor inputs
1 low-level analogue output
4 inputs/4 outputs or 10 inputs/4 outputs
RS485 communication interface c basic, v
according to parameter settings and input/output module options
(2)
with probe option,
(3)
with advanced MMI option.
ANSI Code
27
59
59N
81H
81L
79
50/51
50N/51N
46
49 RMS
37
48/51LR
66
27D/47
27R
38/49T v c c c c c c c v v c v v c v v v c v v v
Type of Sepam sub-station
S20
c c c
transformer
T20
c c c c c c c c v v v c c c c c c v v v v v v c c v v c v v c v v c c c c
M20
c c c c c c c
motor busbars
B20
c c c c c c c c c c c c v v c v v c v v c c c c c c c c c v v v v v v c c v v c c v v v v
Schneider Electric MV catalogue Merlin Gerin
47
Sepam 1000
+
Protection and metering
Metering
c Display of operational measurements on the UMI display.
c This information can be obtained remotely: v
by adding the analogue output MSA 141 together with the factory-built cables v by adding the communication function.
Temperature sensor input
Analog output
Protection
Phase overcurrent (ANSI 50/51)
4 three-phase protection functions against faults, set independently.
c Adjustable timer hold, for detection of restriking faults.
c
Switching function between 2 sets of settings.
Earth fault (ANSI 50N/51N or 50G/51G)
4 protection functions against earth faults, set independently.
c Adjustable timer hold time, for detection of restrike faults.
c
2 nd
harmonic restraint, for stability on transformer closing.
c Switching function between 2 sets of settings.
Unbalance / negative sequence (ANSI 46)
Protection against phase unbalance.
Thermal overload (ANSI 49)
c 2 protection functions against thermal damage due to an overload, to take account of: v changes in ventilation state of transformers v start-up and reacceleration phases of motors c The calculation of equipment heat rise takes account of: v the RMS value of currents and the negative sequence current v
ambient temperature v heating and cooling curves.
c Each function includes 2 thresholds: v 1 adjustable threshold for tripping v 1 adjustable threshold for alarm.
Phase undercurrent (ANSI 37)
Protection of pump motors against working with no load, pump not primed.
Excessive starting time / locked rotor (ANSI 48/51LR)
c Checking the duration of motor starting time.
c
Detecting locked rotor in steady state.
Start per hour (ANSI 66)
Blocking motor start-up in the case of too frequent start-ups, to avoid temperature rise.
Recloser (ANSI 79)
Automatic control to reclose a circuit breaker after tripping on a spurious fault on a line (4 reclosing cycles can be set).
Thermostat, Buchholz
Protection of transformers against internal faults detected by integrated devices.
Temperature monitoring (ANSI 38/49T)
Protection of transformers and motors equipped with temperature sensors.
1 alarm threshold and 1 tripping threshold on each of 8 temperatures measured by sensors.
c This protection requires the 8 inputs MET 148 module c The module is connected to the Sepam unit by a cable of length 0.6 m, 2 m, or 4 m (CCA 770 - CCA 772 - CCA 774).
Overvoltage (ANSI 59) and Undervoltage (ANSI 27)
2 protection functions against variations in nominal voltage, to monitor quality of power supply. Can be used for automatic functions (transfer, load shedding).
Positive sequence undervoltage (ANSI 27D/47)
c Protection of motors against incorrect operation due to insufficient or unbalanced voltage.
c Detection of phase rotation .
Remanent undervoltage (ANSI 27R)
Monitoring the disappearance of remanent voltages provided by rotating machine after circuit opening.
Neutal voltage displacement (ANSI 59N)
2 protection functions against earth faults on an isolated network, by measurement of neutral voltage displacement.
Overfrequency (ANSI 81 H) and underfrequency (ANSI 81 L)
Detection of variances with respect to the rated frequency, to monitor the quality of supply.
MV catalogue Merlin Gerin Schneider Electric
48
Sepam 1000
+
Protection and metering
Setting ranges
Functions
Phase overcurrent
(1)
rated current (In) curve definite time
IDMT
Earth fault
(1)
rated current (Ino) curve definite time
IDMT
Settings
1 A to 6 250 A
DT, SIT, VIT, LTI, EIT, UIT, RI
0.3 to 24 In
0.3 to 2.4 In
1 A to 6 250 A
DT, SIT, VIT, LTI, EIT, UIT, RI
0.1 to 15 Ino
0.2 to 30 A
2 to 300 A
0.1 to 15 Ino
0.1 to 1 Ino
0.2 to 2 A
2 to 20 A
0.1 to 1 Ino
Negative sequence unbalance
definite time
IDMT
Thermal overload
0.1 to 5 Ib
0.1 to 0.5 Ib alarm; tripping cold curve change factor rate change condition max. equipment temperature
Phase undercurrent
0.15 to 1 Ib
Excessive starting time / locked rotor
0.5 Ib to 5 Ib
Starts per hour
negative sequence factor time constant
1 to 60 start-ups per period
1 to 60 successive start-ups
0 to 180
°
C (or 32 to 356
°
F)
Temperature (sensors)
2 thresholds / sensor
Overvoltage
2 thresholds
Undervoltage
2 thresholds
Positive sequence undervoltage
2 thresholds
Remanent undervoltage
1 threshold
Neutral voltage displacement
1 threshold
Overfrequency
1 threshold
Underfrequency
2 thresholds
50 to 150% Unp
5 to 100% Unp
30 to 100% Vnp (Unp/
5 to 100% Unp
2 to 80% Unp e )
50 to 53 Hz or 60 to 63 Hz
45 to 50 Hz or 55 to 60 Hz
Time delays
Inst; 0.05 s to 300 s
0.1 s to 12.5 s at 10 Is
type of sensor
Σ
3I ph
CSH cal 2 A
Inst; 0.05 s at 300 s
CSH cal 20 A
CT 1 / 5 A or zero sequence core balance CT
(2)
Σ
3I ph 0.1 s to 12.5 s at 10 Iso
CSH 2 A rating
CSH 20 A rating
CT 1 / 5 A or core balance CT
(2)
0.1 s to 300 s
0.1 s to 1 s
rate 1
0 - 2.25 - 4.5 - 9 heat rise cooling
50 to 300% of rated thermal capacity used
0 to 100% by IS setting 0.25 to 8 Ib (motor) by logic input I26 (transformer)
60 to 200
°
C
T1: 5 to 120 mn
T2: 5 to 600 mn
ST start time
LT time delay
0.05 s to 300 s
0.5 s to 300 s
0.05 s to 300 s
period
inter-start-up T 1 to 90 min
rate 2
T1: 5 to 120 mn
T2: 5 to 600 mn
0.05 s to 300 s
0.05 s to 300 s
0.05 s to 300 s
0.05 s to 300 s
0.05 s to 300 s
0.05 s to 300 s
0.05 s to 300 s
Reminder:
The current In, the rated voltage Unp and the current Ino are general settings that are set when commissioning Sepam 1000
+
.
They are expressed in terms of values at the primary of metering transformers.
In is the rated current of current sensors (CT rating) (adjustable from 1A to 6250 A).
Unp is the rated phase to phase voltage of the voltage sensor primary (adjustable from 220 V to 250 kV).
Ino is the rating of the residual current sensors.
Ib is the current corresponding to the equipment's rated power, adjustable from 0.4 to 1.3 In.
The setting of current, voltage and frequency values is carried out by directly inputting the value; (resolution: 1A, 1V, 0.1 hz, 1
°
C or F).
(1)
adjustable timerhold define time 0.05 to 300s.
(2)
with adapter core balance CT ACE 990 for core balance CT with a ratio of n between 50 and 1500 turns.
Schneider Electric MV catalogue Merlin Gerin
49
Sepam 1000
+
Sensors
2 types of sensors can be connected to
Sepam 1000
+
to measure current:
Low power current sensors
Zero sequence core balance
CT's
Low power current sensors
These are part of the integrated protection chain associated with Sepam 1000
+ and the Evolis circuit breaker providing current measurement.
Function
These low power current sensors measure current to provide the protection function when associated with Sepam 1000
+
and the Evolis circuit breaker.
Composition
The sensor is delivered with 5 m of cable and a connector that allows direct connection to the Sepam unit.
Mechanical characteristics
c Mounted directly on the Evolis withdrawable circuit breaker chassis.
The sensors are simply positioned by being fitted over the bushings and attached using a screw. Each sensor covers the full operating range of the corresponding circuit breaker.
c Connection to Sepam 1000
+
using the shielded cable and connector supplied with the sensor.
Electrical characteristics
c In conformity with IEC standard 60044-8, defining voltage output current sensors c Usable for rated currents of between 100 A and 3150 A c Class 0.5
c
The choice of sensor is based solely on the phase-phase distance of the chassis: v diameter 120 mm for phase-phase distances of between 145 and 185 mm v diameter 200 mm phase-phase distances of 240 mm c Current sensors are voltage output measurement adapters with a ratio of
100 A / 22.5 mV.
Operation
An input terminal is available on the Sepam 1000
+
unit for testing and maintenance operations. A test equipment interface can be order to check the correct operation of sensors (ACE 917).
Zero sequence core balance CT's
These enable direct measurement of residual current.
Electrical characteristics
c Maximum permissible current: 20 kA/1 s c Transformation ratio: 1/470 c
Accuracy:
±
5% 0 20
°
C c Rating of 2 A input: adjustable threshold from 0.2A to 30 A c Rating of 20 A input: adjustable threshold from 2A to 300 A.
Mechanical characteristics
c they are mounted on the Medium Voltage cables c Several versions are available according to the internal diameter: v 120 mm CSH 120 v
200 mm CSH 200.
c
An adapter is available to connect core balance CT's with ratios of between
50 and 1500 turns or current transformers to be supplied by the panel builder.
Other compatible sensors
c Sepam 1000
+
also functions with 1 A/5 A current and voltage sensors to be provided by the panel builder.
c Sepam 1000
+
B20 functions with voltage transformers (primary voltage from
220V to 250 kV), to be provided by the panel builder.
c Connection is carried out using a connector which can be unplugged when energised: v CCA 630 for current transformers v CCT 640 for voltage transformers.
50
MV catalogue Merlin Gerin Schneider Electric
Sepam 1000
+
Monitoring and control
Composition
The basic Sepam 1000
+
unit has 4 relay outputs.
c The extension of input/output resources for Sepam 1000
+
uses an additional module, available in 2 versions: v
4 logic inputs/4 relay outputs: MES 108 v 10 logic inputs/4 relay outputs: MES 114.
This module is installed on the rear panel of the basic unit.
Functions
The availability of the following functions depends on the type of Sepam 1000
+
unit and on its logic input/output resources.
Circuit breaker control
c Opening, closing and inhibit closing (ANSI 69) of circuit breaker equipped with undervoltage release coil or shunt trip coil logic discrimination according to information: v from the protection functions and the re-closer v
from remote control system v from switchgear diagnosis.
Position contacts discrepancy (SSL) (ANSI 68)
Quick and selective tripping of phase overcurrent protection and earth fault protection by logical blocking of upstream protection by the downstream protection.
A safeguard device ensures the functioning of the protection device in the case of failure of the blocking link.
Latching / acknowledgement (ANSI 86)
Latching of output relays can be set. The latched closing orders are stored in memory and must be acknowledged before the device is put back in service.
Annunciation (ANSI 30)
c
Alarms detected and indicated: v by lights on the front panel v by messages on the display v
by relay outputs according to parameter settings v remotely by the communication interface.
Watchdog
Output relay testing
Characteristics
Logic inputs
c
Independent inputs, free of voltage.
c Direct input voltage: 24 to 250 Vdc.
c Consumption: 3 mA typically.
Relay outputs
c Direct or alternating voltage: 24 to 220 Vdc and 100 Vac at 240 Vac.
c 3 control outputs: continuous rating 8 A.
c 5 indication outputs: continuous rating 2 A.
Schneider Electric MV catalogue Merlin Gerin
51
Sepam 1000
+
Communication interface
Communication
Function
Via the remote control and monitoring system, this allows the remote operation of equipment, with a Modbus protocol.
Remote monitoring by reading data
c Metering c
Value of protection settings c Status of protections and Sepam 1000
+ c Status of "logic" inputs functions c Time tagged events c Disturbance recordings.
Remote control
c Opening and closing of the switchgear from the supervisor workstation c Activating of Sepam 1000
+
functions c
Two modes are available: v "direct" or v
"select before operate".
Remote setting of protections
Characteristics
Type of transmission
Protocol
Rate
Electrical interface
Maximum distance
Number of bus supplied
Sepam units on one line
Number of masters
Response time asynchronous serial
Modbus slave
4800, 9600, 19200, 38400 bauds
2 wire differential, standard EIA RS 485
250 m
25
1 less than 15 ms
Setting up the Modbus network
c
This is achieved by connecting: v the communication interface module ACE 949 to the
Sepam 1000
+
via its connection cable of length 3 m (CCA 612) v RS 485 / RS 232 (ACE 909-2) or RS 485 / RS 485 (ACE 919) converter.
Amongst other things this provides power to the interface module. A maximum of 25 modules can be connected to it v cabling between these elements must be provided with a shielded cable which is not supplied including 2 twisted pairs.
Network example
MV catalogue Merlin Gerin Schneider Electric
52
Sepam 1000
+
Software
Expert User Machine Interface Software
The SFT2841 software gives access to all Sepam 1000
+ functions, with all the user friendliness and comfort offered by a Windows type environment.
Operation
c 2 modes are available: v not connected to Sepam 1000
+
for initial preparation of parameters and protection settings v connected to Sepam 1000
+
, to get optimum use of its resources and have all the functions available in disconnected mode and additional local operation functions.
Parameter and protection settings
The creation of files containing all parameters and protection settings for Sepam
1000
+
is possible without being connected to the unit.
c
Amongst other things the software enables: v the full setting of Sepam 1000
+
and adjustment of protection functions v customising of the control logic v customising of identification labels for lsignal lamps v management of parameters and settings files: saving, comparison, printing
Local operation
c Connected, the software enables access to the following information: v all metering and diagnosis values v parameters and settings protection v past history of alarms with time of occurrence v
logical states of inputs, outputs and signal lamps c And the following operations: v uploading and downloading parameters and settings files v recovery and saving of disturbance recordings v acknowledgement of active alarms and resetting of Sepam 1000
+ after tripping.
Implementing
c
Required configuration
v Microsoft Windows 95/98/NT4.0
v PC compatible computer with Pentium 133 MHz processor or greater v 32 Mb of RAM and 4 Mb on hard disk.
c
Available in kit form comprising
v 1 CD-ROM including:
- The SFT 2841 software for configuring Sepam 1000
+
- The SFT 2826 software for recovery of disturbance recordings v 1 RS232 series link cable PC / Sepam 1000
+
.
Disturbance recording display software
SFT 2826 software combined with the SFT 2841 software enables recovery of disturbance recording files and their visualisation.
Schneider Electric MV catalogue Merlin Gerin
53
Powerlogic
Metering device
The Power Meter can replace analogue metering devices.
It calculates electrical magnitudes: average values, harmonic distortion rates, etc.
The information it provides allows a reduction in both energy and maintenance costs.
It can be integrated in the "Power Logic
System".
Function
In addition to its metering functions, the Power Meter range has advanced functions such as: c Power quality
Harmonic distortion level in both current and voltage terms.
c Memorisation of minimum and maximum values
Used for define preventive maintenance.
c Alarm/relay functions
The PM-650 has on-board alarms. These alarms are triggered when a voltage, current, frequency and phase threshold is exceeded. Moreover, they can also trigger a relay.
c Event logging
When an alarm appears, the event is logged into the memory (non volatile).
These events are called up on the PC screen.
c Data recording
This data is saved to the local memory and can then be read on a PC. The user can select the metering data acquisition frequency.
Characteristics
Economical metering
c One single device replaces a large number of analogue metering instruments.
c
Class 0.2 accuracy for voltage current metering acquisition.
c Accuracy of RMS values for metering of voltage and current harmonic distortion up to the 31st harmonic.
c
Harmonic distortion rate reading for voltage and current in each phase to give an indication as a percentage of the quality of the waveform.
c
Neutral current monitoring to detect overloading.
c High speed sampling to monitor, for example current demand peaks.
c Load monitoring for preventive maintenance.
c
Reallocation of energy costs.
c Remote input of data provided by the devices through the RS-485 communication port and a PC.
Easy installation
c It is possible to separate the metering device and the optional screen for very flexible installation.
c Easy to incorporate in the energy management system.
c Compact dimensions 114 x 114.
Standard sensors
c
Connection to conventional CT's.
c Does not require PT up to 600 V.
Communication options
c
Modbus communication.
c Power impulse output.
Two-line LCD screen
c Back to back or next to the central device, connected using a cable of maximum length 15 metres.
c Possible to use as a portable setting tool for Power Meter.
c Simultaneous display of phase 1.2.3. measurements.
Conformity with standards
c
Conformity with standards UL. NOM. and CSA c CE marking c Tested according to standard IEC 1000 c In conformity with FCC (class A) c Vibration and temperature tests.
The optional Power Meter display takes the same space as a conventional analogue metering device and can be connected to the Power Meter module using a communications cable.
Additional function
c Other multi-functional metering devices in the Power Logic range propose among others: v magnitudes and angles of the 31 harmonics v
detection and recording of voltage and current peaks v wave form capture…
For more information, please contact us.
54
MV catalogue Merlin Gerin Schneider Electric
Dimensions
Sepam unit with advanced UMI interface
Sepam 1000
+
176
222
101
129
Remote advanced UMI module
162
117
25
Zero sequence core balance CT
CSH 30
Ø30
82
60 29
Schneider Electric MV catalogue Merlin Gerin
55
Earthing switch
Earthing
Indication and interlocking
58
59
Schneider Electric MV catalogue Merlin Gerin-Telemecanique
57
Earthing Switch
Operating mechanism
Earthing
Function
This device is used to earth and short circuit the cable ends before work is performed on the cable compartment.
Composition
c The earthing switch includes: v an operating mechanism box to be mounted on the front face of the cubicle v a power circuit unit with a fast acting closing mechanism independent of the operator.
c The link between the 2 devices will have a length depending of the depth of the cubicle. A drawing will define this rod to be manufactured and installed by the panel builder.
Power circuit unit c Mechanical interlock with the circuit breaker to prevent: v
to draw in the circuit breaker if the earthing switch is closed v to close the earthing switch if the circuit breaker is not opened and drawn out v this interlock is realised with Profalux or Ronis key v a drawing is showing the mechanical link to be manufactured and installed by the panel builder.
c Mechanical interlock with the front and rear plate of the cable compartment to prevent access to the cables under voltage v a drawing is showing the mechanical link to be manufactured and installed by the panel builder.
Characteristics according to IEC 60 129
Ur
Ik for tk = 1s
kV kA
12
Ik for tk = 3s phase distance
kA mm
31.5
160
17.5
50
31.5
200
17.5
50
31.5
240
MV catalogue Merlin Gerin Schneider Electric
58
Earthing switch
L1
L2
L3
Voltage Presence Indicator unit
Key locking
Operating lever
Indication
Interlocking
Voltage Presence Indicator System
c
This system combined with the Iso-capacitors integrated as standard in the earthing system provides an indication of the voltage in the phases of the main circuit.
c It is mounted on the front of the earthing operating mechanism.
c It is available for two voltage ranges, in conformity with standard IEC 61 958: v 3.2 to 7.2 kV v 7.2 to17.5 kV.
Open/closed contacts
A series of 6 auxiliary contacts indicates the open/closed position of the earthing switch.
Characteristics delivered as standard maximum quantity breaking capacity(A)
cos ø : 0,3
V AC
V DC
4
11
240
380
480
600
48
125
250
500
15
10
10
6
3
0,5
Mechanical earthing switch locking
This function enables the earthing switch to be locked in its open or closed position by adding 1 or 2 key locks.
c Several configurations are available: v locked closed by 1 key lock + locked open by 1 key lock.
v
locked closed by 2 key locks v locked open by 2 key locks.
A mechanical adaptation kit is delivered to fit the various key locks which are not supplied.
Electromechanical interlocking of the earthing switch
This function is achieved using a coil which blocks switching operation when it is not supplied power. When energised it releases the earthing switch which can then be closed.
The system is available in several versions according to the supply voltage: 24
VDC - 48 VDC - 110 VDC - 220 VDC.
Earthing switch operating lever
This is identical to the one supplied for the circuit breaker racking truck. It allows the earthing switch to be operated.
Schneider Electric MV catalogue Merlin Gerin
59
Switchboard components
Switchboard components
Panorama
Operation
Cubicle components
Indication, support, heating
Protection
62
62
63
65
65
66
Schneider Electric MV catalogue Merlin Gerin
61
Current sensor
Support insulator
Surge arrester
Earthing switch
Heating resistance
Switchboard components
Busbar connection cover
Panorama
L1
L2
L3
Terminal block connector
Multi 9 circuit breaker
Sepam 1000+
Lamp
Push button
Voltage presence indicator
Door handle
Earthing switch operating mechanism
Extraction table
62
MV catalogue Merlin Gerin Schneider Electric
Switchboard components
Fixed coupling link
Drawout coupling link
Operation
Fixed coupling link
Allows a standard incomer/feeder cubicle to be transformed into a busbar riser cubicle by short circuiting the top and bottom terminals of the cradle.
c This offer is exclusively available in the form of drawings proposed in the installation manual.
c This unit comprises 1 bridge/phase and is easily installable by the operator on the cradle bushing fingers.
Ir
Electrical characteristics
Ik
A kA
1250
31.5
2500
40
Drawout coupling link
Enables bridging in an existing cubicle of the upstream and downstream circuit in the cubicle. It is installed in place of the withdrawable circuit breaker in the cradle.
c It includes: v
a device to lock in the racked-in position using padlocks.
v an auxiliary PAF contact delivered separately for installation on the cradle : it indicates that the truck is well mechanically racked in.
Electrical characteristics
Ik tk
Ir phase distance
kA
S
A mm
25
3
1250
145
31.5
3
1250
185
40
3
3150
240
Busbar earthing truck
This device is a safety accessory used in place of the withdrawable breaker in order to earth the busbars.
c
Possibility of locking by padlocks in the draw-in position.
Electrical characteristics
Ur
Ik t k phase distance
kV kA
S mm
17.5
25
3
145
17.5
31.5
3
185
17.5
40
3
240
Busbar earthing truck
Schneider Electric MV catalogue Merlin Gerin
63
Switchboard components
Extraction table
Operating handle
Operation
Extraction table
Enables the circuit breaker to be taken out of the cubicle and to handle it during maintenance operations or during cubicle manufacturing.
c A height adjustment device using screw/bolts allows the height to be adjusted to
- 20 mm/ + 200 mm.
c A latching device is provided between the extraction table and the cradle.
Operating handle
This enables all operations to be carried out on the circuit breaker racking truck as well as on the earthing switch.
Busbar connection cover
This set of 3 insulating covers enables improved dielectric withstand at the busbar connections in the cubicle.
Busbar connection cover
64
MV catalogue Merlin Gerin Schneider Electric
Cubicle components
Capacitive divider insulator
Door handle
Heating element
Indication
Support
Heating
Capacitive divider insulator set
c
This Voltage Presence Indicator System (VPIS) includes: v the insulators themselves providing mechanical support and insulation up to
17.5 kV; these insulators also integrate capacitors capable of supplying a voltage potential signal.
v a voltage indication unit with light to indicate the voltage presence on the front panel covering 2 voltage ranges:
- 3.2 to 7.2 kV
- 7.2 to 17.5 kV
Support insulator
c This enables mechanical support and voltage insulation at 12 and 17.5 kV c Application for busbar and cable fixing and support.
Door handle
c Enables the front panel door of the cubicle to be closed.
Several versions are available: v
with triangular key lock v with Ronis or Profalux type key lock.
Heating element
c This can be used for 2 reasons: v heating the cubicle when the ambient temperature is too low v avoiding the formation of condensation.
c
Delivered with its support and without a thermostat.
c Power: 150 W at 220 V.
Schneider Electric MV catalogue Merlin Gerin
65
Cubicle components
Protection
Surge arresters
Silicone rubber housed metal-oxide surge arresters are intended for over voltage protection of distribution networks : they offer ad-hoc protection against overvoltage from various origins (lighting, switching…).
The VARISIL range is ideal for the various voltage covered by Evolis circuit breakers.
c Our recommendation when using with Evolis: v
Ur = 7.2 kV : HD 09 v Ur = 12 kV : HD 12 v Ur = 17.5 kV : HD 18
Surge arrestor
Common characteristics according to IEC 60 099-4
rated discharge current In (with 8/20 wave) line discharge class short time withstand current, twice rectangular withstand current, duration 2000
µ s
(with 4/10 wave) short circuit withstand
(kA peak)
I
10
(kA peak) 100
(A peak)(withstand 18 times min.) 300
(kA RMS - for 0.2 s) 31.5
Characteristics according to IEC 60 099-4
rated voltage maximum continuous service voltage rated residual voltage rated creepage distance mass - option "no"
Ur (kA RMS)
Uc (kV RMS)
In (10 kA)
(mm)
(kg)
HD06 HD09 HD12 HD15 HD18 HD24 HD30 HD36 HD42
6 9 12 15 18 24 30 36 42
5
18
380
1.5
8
28
380
1.6
10
42
380
1.8
12
45
380
1.8
15
56
610
2.5
20
72
610
2.7
24
89
910
3.5
28.8
106
910
3.6
33.6
120
910
3.6
66
MV catalogue Merlin Gerin Schneider Electric
Schneider Electric MV catalogue Merlin Gerin
67
AC/DC Protection circuit
Multi 9 circuit breakers
1 pole
2 poles
3 poles
70
Function
Control and protection of circuits against overloads and short-circuits for AC and DC applications.
Description
Technical data
c Ratings: 6 to 63 A set at 30
°
C.
c Voltage rating: 230/400 V AC and 48 V DC.
Electrical characteristics
Ratings
(A)
6 to 63
Type
1P
2.3
Voltage
(V) AC
230/400
400
Break.Cap.
(A)
3000 to 10000
3000 to 10000
Ratings
(A)
1 to 32
Type
1, 2, 3
Voltage
(V) DC
48
Break.Cap.
(A) up to 15000 c Number of operating cycles (O-C): 20 000.
c Tripping curves: v B curve: the magnetic trip units operate between 3 and 5 In v
C curve: the magnetic trip units operate between 5 and 10 In.
c Tropicalisation: treatment 2 (relative humidity 95% at 55
°
C).
c Connection: tunnel terminals for cables up to 25 mm
2
.
Electrical auxiliaries
The electrical auxiliaries enable the remote tripping or indication of the Multi 9 circuit-breakers: c On the left of the circuit breaker for the indication auxiliaries.
c On the right of the circuit breaker for the trip units.
+
+ +
or
OF auxiliary contact
SD fault indicating switch c
Combining the auxiliaries
Multi 9 circuit-breaker
MX or
MN
OF or
SD
OF or
SD v i g i
OF or
SD
SD or
OF
Shunt release g i v i
OF or
SD
Undervoltage release
MX or
MN
OF or
SD
SD or
OF
MX or
MN c
Remote tripping of Multi 9 circuit breaker
This can be carried out with an MX shunt release or MN undervoltage release fixed on the right of the circuit breaker.
For more information please refer to ART documentation...
MV catalogue Merlin Gerin Schneider Electric
AC/DC Protection circuit
Multi 9 circuit breakers
Remote indication
c OF auxiliary contact
Fixed on the left of the circuit breaker or another auxiliary contact, it enables the indication or control according to the "open" or "closed" position of the circuit breaker.
c
SD fault indicating switch
Fixed on the left of the circuit-breaker, it enables the indication or control according to the "fault tripped" position of the circuit-breaker.
Visualisation of the fault on the front face by mechanical indicator.
c Connection: screw clamp terminals for: v 2 x 1.5 mm
2 cables or 1 x 2.5 mm
2 cable.
Technical data of the auxiliaries
Voltage
(V AC or DC)
380-415 V AC
220-240 V AC
250 V DC
125 V DC
48 V DC
24 V DC
Breaking Capacity (cos Ø = 0,6)
(A)
3
6
2
6
0.4
1
Accessories
Padlocking facility
Enables the locking of the single or two-pole Multi 9 control toggle, in the "open" or "closed" position (by an 8 mm max. padlock, not supplied).
Single or double dividable mounting plate
Possibility to lock the mounting plate by an 8 mm ø padlock (not supplied), with the circuit breaker in the isolated position.
Comb busbars
c Current permissible at 40
°
C: v
100 A with a central supply point, v 125 A with two supply points.
c Rated insulation voltage: 500 V (according to IEC 664).
c
Short-circuit withstand compatible with the Multi 9 breaking capacity.
c Connection: v the supply is possible:
- by 16 mm
2
semi-rigid cable directly in the device enclosure
- by 25 mm
2
semi-rigid cable using the specific connector.
Terminal shields
c Degree of protection: IP 305.
Sealable terminal shield
Enables to install the entire multi 9 on a panel: terminal shield composed of a base with a symmetrical rail and a cover to be screwed (sealable combination).
Passage of the wiring by punched out openings on the sides and the base.
Schneider Electric
For more information please refer to ART documentation...
MV catalogue Merlin Gerin
71
Control and indication
Applications
Harmony Push Buttons and
Indicator Lights
Specific Features
Mounting Hole
Range description
Connection
Protection Index according to IEC 529 and NFC 20-010
Type of device
Modular product
With metal collar chrome plated or black
Rounded head
Plastic collar
Rounded or square head
Plastic collar
Rounded, square or rectangular head
Metal collar chrome plated
Hexagonal head
Ø 22
Push Buttons
Emergency stop buttons
Rotary buttons
Luminous buttons
Indicator lights
By screw terminals
By connector
By adaptor for printed circuit board
IP 65
IP 66 (capped push button heads)
Ø 16 Ø 30
By faston cable terminal
By pins for printed circuit board
By captive screw terminals
IP 65
Harmony style 4 Harmony style 5 Harmony style 6 Harmony style 9
XB4 XB5 XB6
72
For more information please refer to ART documentation
MV catalogue Merlin Gerin Schneider Electric
Control and indication
Harmony Push Button and
Indicator Lights
Digital displays Profil front panels
Non adaptable product
Plastic collar
Rounded head
Compact, low consumption
Rounded head
Ø 22 and Ø 25 Ø 8 and Ø 12
LED
7 segments + decimal point
Aluminium front panel for mounting in control and indication units Ø 22
Ø 22 –
Push buttons
Emergency stop buttons
Rotary buttons
Indicator lights
LED indicator lights
By captive screw terminals Clip connector
2.8 x 0.5 or screw connector
IP 40 IP 54 IP 40
IP 65 (with seal)
Harmony style 7
XB7 XB7
"Series E" "Series P"
XVL-A
Displays to be made up: body + 1 digit head
3 sizes of front panel for mounting of 4, 8 or 12 control and indication units Ø 22
By connector
IP 65
ZA2-VA
–
IP 65
KT i
Schneider Electric
For more information, please refer to ART documentation…
MV catalogue Merlin Gerin
73
Connection
Terminal blocks
Applications
(connection)
"Screw-screw" "Spring-spring"
Nominal cross-section
(mm 2 )
Number of poles
Snapped in place on
& ( '
&
&
'
(
(
'
Snapped in place on
15 mm rail
References
2.5 to16 2.5/4 35 70 150 4
1 1 1 1 1 25 or 10
6
2 or 3
10 and 35 2,5
1 1 or 2
–
–
–
●
– – – –
– ● ● ●
– – – –
– – – –
–
AB1-VV
●
– – –
–
–
●
–
–
DB6-
CD
–
–
●
–
–
–
●
–
– –
DB6DB6-
DD ED/FD
–
–
●
–
–
AB1-RR
4
1
–
–
●
–
–
Applications
(connection + functions)
Trifunctional with protection conductor
Screw-clips For supported diode
Fixed Removable
For supported fuse
Fixed Removable
Nominal cross-section
(mm 2 )
Number of poles
Snapped in place on
& ( '
&
&
'
( '
(
Display
"Screw-screw"
"Spring-spring"
References
–
–
●
–
–
2.5
2.5
1 neutral disconnectable
1 link V/V 2 linksV/V
–
–
●
–
●
●
–
●
–
AB1AB1-
TRS
TRP/TRN
4
1
4
2
4
1
10
1
4
1
4
1
–
–
–
●
–
●
–
AB1-
FV/FC
–
–
–
●
–
–
–
–
●
●
●
–
AB1-
D11
●
–
AB1-
SF/SV
–
–
–
●
●
–
–
–
●
●
–
–
●
–
●
●
–
AB1-FU AB1-SF
●
–
–
●
AB1-
RRSF
F
74
For more information, please refer to ART documentation …
MV catalogue Merlin Gerin Schneider Electric
Connection
Junction blocks
"Bolt-bolt" "Bolt-connector" "Screw-screw" conductor : protection type
"Screw-screw" for neutral typeprotection conductor
–
–
●
●
–
95, 185 and 240
1
AB1-BB
–
–
●
●
–
95, 150 and 240
1
AB1-BC
–
–
–
–
●
2.5-4
1
AB1-TP
–
–
–
●
–
4 to 35
1
–
●
–
●
–
–
–
●
–
4 to 16
1
AB1-NEN
–
–
●
–
–
2.5
1 or 2
4
1
–
–
●
–
–
AB1-RRTP
For 3-wire proximity detectors
Without PE With PE
Disconnectable
Blade type Fuse type
Staged Withdrawable
From side From front
Not Marking
withdrawable accessories
2.5
3
2.5
4
4
1
–
–
–
●
●
–
–
●
–
●
●
–
AB1-DDP
235U
●●
●
–
AB1-DDP
235T
●●
–
–
–
●
–
●
●
–
●
–
AB1-SC AB1-
FUSE
4
2
–
–
–
●
●
●
–
AB1-ET
2,5
5
–
–
–
●
–
●
–
AB1-BD
–
–
–
–
2,5
10
–
–
–
●
–
1,5
10
–
–
–
●
2,5
For flat, 20 pole cable
–
–
–
●
–
2.5
10
–
–
–
–
–
–
–
●
–
AB1-DV/
DVM
●
–
–
–
AB1-BCP AB1-BV AB1-B/R
AB1-G/S
Schneider Electric
For more information, please refer to ART documentation …
MV catalogue Merlin Gerin
75
Circuit breaker
Order form
Full version
Function p.20/21
Withdrawable circuit breaker
Composed of:
- 1 bloc of 4 O/C position contacts,
- 1 racking truck,
- 6 arms with clusters.
p.24
Type of racking
Designation kV kA A Evolis
phase distance
7.2
25
12 25
12 25
7.2
25
17.5
25
17.5
25
1250 7P1.1250
630 17P1.630
1250 17P1.1250
1250 7P1.1250
630 17P1.630
1250 17P1.1250
7.2
31.5
1250 7P2.1250
17.5
31.5
630 17P2.630
17.5
31.5
1250 17P2.1250
7.2
31.5
2500 7P2.2500
17.5
25 2500 17P1.2500
17.5
31.5
2500 17P2.2500
References
145 mm
59000
v
59001
v
59002
v start
185 mm
59004
v
59005
v
59006
v
59008
v
59009
v
59010
v
240 mm
59012
v
59014
v
59015
v manual screw / shaft
59301
v
59450
v
59301
v
59450
v
59450
v
Price
Lead
Time p.24
Operating shaft
(1 per switchboard) operating shaft
59449
v
59449
v
59449
v
p.24
Cradle, phase distance
1 cradle / 145 mm
1 cradle / 185 mm
1 cradle / 240 mm cradle
59292
v
59293
v
59294
v
p.23
Low powered CTs for Sepam 1000
+
3 CVV120
3 CVV200
25-3150 A
25-3150 A
p.24
Draw in/out position signaling
4 AC + 1 AC PAF
59390
v
59390
v
59391
v
59170
v
59170
v
59170
v
Schneider Electric MV catalogue Merlin Gerin
79
Circuit breaker
Order form
Full version
Function Designation p.24
Additional earthing device
Composed of:
- 1 CB sliding contact,
- 1 cubicle copper bar.
earthing sliding contact
References
options
59451
v
p.25
CB footing
Composed of:
- a roller kit,
- a drawing.
support
p.24
Adaptation kit in case of application with SE earthing switch
see drawings in the "installation guide"
59050
v fitted accessories are mandatory
Price
Lead
Time
80
MV catalogue Merlin Gerin Schneider Electric
Circuit breaker
Order form modular version
Function p.26/27
Basic breaker
Composed of:
1 bloc of 4 O/C position contacts.
Designation kV kA A Evolis
phase distance
7.2
25
12 25
12
12
25
25
7.2
25
17.5
25
17.5
25
17.5
25
1250 7P1.1250
630 17P1.630
1250 17P1.1250
1600 17P1.1600
1250 7P1.1250
630 17P1.630
1250 17P1.1250
1600 17P1.1600
7.2
31,5 1250 7P2.1250
17.5
31.5
630 17P2.630
17.5
31.5
1250 17P2.1250
17.5
31.5
1600 17P2.1600
7.2
31.5
2500 7P2.2500
17.5
25 2500 17P1.2500
17.5
31.5
2500 17P2.2500
References
145 mm
59026
v
59027
v
59028
v
59029
v
p.28
Type of upstream fixed connection to be mounted on basic CB or bushings
Variable V* Variable H*
3 fixed distance H or V 630-1600A
3 variable distance H 630-1600A
3 variable distance V 630-1600A
3 fixed distance H or V 1250-2500A
3 variable distance H 1250-2500A
3 variable distance V 1250-2500A
Fixed
p.28
Type of downstream fixed connection to be mounted on basic CB or bushings
3 fixed distance H or V 630-1600A
Variable V*
Variable H*
3 variable distance H 630-1600A
3 variable distance V 630-1600A
3 fixed distance H or V 1250-2500A
3 variable distance H 1250-2500A
3 variable distance V 1250-2500A
Fixed
p.29
Type of withdrawable connections
6 clusters/fingers
630-1250A
1 cluster 1 finger
6 bushings/arms&clusters
630-1250A
6 clusters/fingers
1250-2500A
6 bushings/arms&clusters
1250-2500A
1 bushing
1 arm
V*: vertical, H*: horizontal
59400
v
59401
v
59402
v
59400
v
59401
v
59402
v
59373
v
59374
v start
185 mm 240 mm
59030
v
59031
v
59032
v
59033
v
59034
v
59035
v
59036
v
59037
v
MV connections
59038
v
59040
v
59041
v
59403
v
59404
v
59405
v
59403
v
59404
v
59405
v
59375
v
59376
v
Price
Schneider Electric MV catalogue Merlin Gerin
Lead
Time
81
Circuit breaker
Order form modular version
Function Designation p.30
Low powered CTs for Sepam 1000
+
3 CVV 120
3 CVV 200
25-3150 A
25-3150 A
References
59390
v fixed & d/o options
p.31
LV terminal blocks
fixed CB terminal blocks
59081
v
59391
v
Price
Lead
Time p.31
Type of racking
manual screw / shaft mandatory for 240 mm phase distance
p.31
Operating shaft
(1 per switchboard) operating shaft
59301
v
59450
v
59449
v
p.31
Additional earthing device
earthing sliding contact
p.31
Racking base
racking base
59451
v cradle
59300
v
82
MV catalogue Merlin Gerin Schneider Electric
Circuit breaker
Function Designation p.31
Draw in/out position signaling
4 AC + 1 AC PAF
Order form modular version
References
59170
v
p.32
CB footing
composed of:
- a roller kit,
- a drawing.
support others
59050
v
Price
Lead
Time p.31
Adaptation kit in case of application with SE earthing switch
see drawings in the "installation guide" fitted accessories are mandatory
Schneider Electric MV catalogue Merlin Gerin
83
Circuit breaker
Order form
Fitted accessories
p.34
Function Designation
MX opening shunt trip voltage
24…30V
48…60V
100…130V
200…250V
DC 50/60 Hz
DC 50/60 Hz
DC 50/60 Hz
DC 50/60 Hz
References
remote control start
59133
v
59134
v
59135
v
59136
v
p.34
Additional MX opening shunt trip voltage
24…30V DC 50/60 Hz
48…60V
100…130V
DC 50/60 Hz
DC 50/60 Hz
200…250V DC 50/60 Hz
p.34
MN undervoltage shunt trip voltage
24…30V DC 50/60 Hz
48…60V
100…130V
200…250V
DC 50/60 Hz
DC 50/60 Hz
DC 50/60 Hz
p.34
Time delay unit for MN, MN time setting
48…60V DC 50/60 Hz
100…130V DC 50/60 Hz
200…250V DC 50/60 Hz
59137
v
59138
v
59139
v
59140
v
59150
v
59151
v
59152
v
59153
v
33680
v
33681
v
33682 v
Price
Lead
Time p.33
MITOP low energy release
mitop 200-250 V AC 50/60 Hz
COM
UC1
UC2
UC3
UC4 M2C
SDE2
/RES
SDE 1
59160
v
p.36
MCH motor voltage
24…30V
48…60V
100…125V
200…250V
100…130V
200…240V
p.36
XF closing coil release
24…30V
48…60V
100…130V
200…250V
DC
DC 50/60 Hz
DC
DC
AC 50/60 Hz
AC 50/60 Hz
DC 50/60 Hz
DC 50/60 Hz
DC 50/60 Hz
DC 50/60 Hz
84
MV catalogue Merlin Gerin
59162
v
59163
v
59164
v
59165
v
59166
v
59167
v
59145
v
59146
v
59147
v
59148
v
Schneider Electric
Circuit breaker
Function Designation p.37
Operation counter
operation counter
00399
p.37
Additional auxiliary contacts
4 AC "silver"
Order form
Fitted accessories
References
59085
v signaling
59090
v
Price
Lead
Time p.37
Indication of CB ready to close PF p.38
1 AC PF
Open position CB interlocking
for lock & key for padlock supplied by client
59091
v interlocking systems
59336
v
59337
v
p.38
Lock & key configuration
with one lock
RONIS with 2 idem locks
RONIS with 2 differents locks
RONIS with one lock
PROFALUX with 2 idem locks
PROFALUX with 2 differents locks
PROFALUX
p.38
Padlocking of O/C push button
for padlock supplied by client
59338
v
59339
v
59341
v
59340
v
59343
v
59342
v
59344
v end
Schneider Electric MV catalogue Merlin Gerin
85
Protection, monitoring control and metering
Order form:
Sepam 1000
+
Function Designation p.47
Application type
Substation
Transformer
Motor
Busbar
Busbar
S20
T20
M20
B21
B22
p.50
Line sensors type
1/5A CT current connector CCA630
LPCTcurrent input connector
CCA670
VT voltage input connector
CCT640
CCA630 CCT640
p.48
8 inputs temperature module
8 temperature sensors
MET148 module
References
start
59620
v
59621
v
59622
v
59624
v
59625
v
59630
v
59631
v
59630
v
59631
v
59632
v
Price
Lead
Time
59640
v
p.46
Remote modules cord
L = 0.6 m
CCA770
L = 2 m
CCA772
L = 4 m
CCA774
p.46
Operating language
English / French
English / Italian
English / Spanish
English / Polish
English / Swedish
English / Local
p.46
User Machine Interface
Basic UMI on
Trip
I>51 b>5 1n
b>> 51n ext
SF6 O of
I off
Advanced UMI
UX
59660
v
59661
v
59662
v
59609
v
59610
v
59611
v
59612
v
59613
v v
UD
MV catalogue Merlin Gerin Schneider Electric
86
Protection, monitoring control and metering
Order form:
Sepam 1000
+
Function p.46
Remote advanced
UMI module
Designation
DSM303
p.46
Remote modules cord
L = 0.6 m
CCA770
L = 2 m
CCA772
L = 4 m
CCA774
p.46
Mounting accessorie
Mounting plate
AMT840
p.46
Power supply
Sepam/basic
UMI/24V/70
°
C
UMI/48-250V/70
°
C
Sepam/advanced
UMI/24V/70
°
C
UMI/48-250V/70
°
C
S10 UX xxx J xx xAT
S10 UX xxx J xx xUT
S10 UD xxx J xx xAT
S10 UD xxx J xx xUT
p.46
Power supply connector
Screw type connector
CCA620
Ring lug connector
CCA622
p.51
Input/Output module
4 inputs + 4 outputs module MES108
10 inputs + 4 outputs module MES114
References
59608
v
59660
v
59661
v
59662
v
59670
v
59602
v
59603
v
59668
v
59669
v
59645
v
59646
v
59606
v
59607
v
Price
Lead
Time p.52
Communication interface
RS485 network interface
2 wires
ACE949-2
ACE959
4 wires
p.52
Communication Cord
L = 3 m
CCA612
59642
v
59643
v
59663
v
Schneider Electric MV catalogue Merlin Gerin
87
Protection, monitoring control and metering
Order form:
Sepam 1000
+
References Function Designation p.51
Analog output module
MSA141
p.51
Remote modules cord
L = 0.6 m
CCA720
L = 2 m
CCA772
L = 4 m CCA774
p.50
Core balance
Residual current sensor d=120 CSH120
Residual current sensor d=200 CSH200
Interposing ring CT for Io
Core balance CT interface
CSH30
ACE990
E1E2
E3E4
E5
S1S2
ACE
990
59647
v
59660
v
59661
v
59662
v
59635
v
59636
v
59634
v
59672
v end
Price
Lead
Time
88
MV catalogue Merlin Gerin Schneider Electric
Protection, monitoring control and metering
Order form: accessories Sepam 1000
+
References Function Designation p.51
8 inputs temperature module
8 temperature sensors module
MET148
p.51
Remote modules cord
L = 0.6 m
CCA770
L = 2 m CCA772
L = 4 m CCA774
p.51
Analog output module
MSA141
p.51
Input/Output module
4 inputs + 4 outputs module
MES108
10 inputs + 4 outputs module
MES114
p.52
Communication interface
RS485 network interface
2 wires
ACE949-2
4 wires
ACE959
p.52
Communication Cord
L = 3 m
CCA612
p.50
Core balance
Residual current sensor d=120
CSH120
Residual current sensor d=200
CSH200
Interposing ring CT for Io
CSH30
Core balance CT interface
ACE990
E1E2
E3E4
E5
S1S2
p.46
Mounting accessory
Mounting plate
AMT840
59640
v
59660
v
59661
v
59662
v
59647
v
59645
v
59646
v
59642
v
59643
v
59663
v
59635
v
59636
v
59634
v
59672
v
59670
v
Price
Lead
Time
Schneider Electric MV catalogue Merlin Gerin
89
Protection, monitoring control and metering
Order form: accessories Sepam 1000
+
References Function Designation p.52
Communication accessories
RS485/RS232 converter
ACE909-2
RS485/RS485 interface (AC)
ACE919 AC
RS485/RS485 interface (DC)
ACE919 DC
ACE
909
-2
p.53
Configuration software
PC configuration software kit kit SFT2841
Connectors
2 sets of spare connectors
PC connection cord
LPCT test plug
LPCT injection adaptor
User's manual in French
User's manual in English
KIT 2640
CCA783
CCA613
ACE917
PCRED399040FR
PCRED399040EN
59648
v
59649
v
59650
v
59671
v
59676
v
59664
v
59666
v
59667
v
59674
v
59675
v
Price
90
MV catalogue Merlin Gerin Schneider Electric
Earthing switch
Function Designation
Order form: earthing switch (ES) voltage presence indicator system (VPIS) d/o circuit breaker interlocking
References Price
Lead
Time
start
Cubicle functions
incomer or feeder busbar metering d/o bus section d/o CB or truck with ES d/o CB or truck without ES direct incomer without ES with ES without ES
p.58
Earthing switch (ES):
Power circuit
12kV 160mm 31.5kA-3s
17.5kV 200mm 31.5kA-3s & 50kA-1s
17.5kV 240mm 31.5kA-3s & 50kA-1s
(phase distance in mm)
59490
v
59491
v
59492
v
Earthing switch and VPIS
59490
v
59491
v
3 insulators mounted on a support
160 mm
200 mm
240 mm
p.58
Operating mechanism
box with mechanism box with voltage indication
0 p.59
Voltage indication
3.2 - 7.2 kV
7.2 - 17.5 kV
L1
L2
L3
p.59
Auxiliary contact
6 AC (3NO 3NC)
p.59
Interloking for O/C position (without locks)
for 1 lock O & 1 lock C for 2 locks O for 2 locks C
p.59
Electromagnetic interlocking for
E.S O/C position
24V DC
48V DC
110V DC
220V DC
59502
v
59506
v
59508
v
59509
v
59513
v
59514
v
59515
v
59516
v
59487
v
59487
v
59488
v
59488
v
59489
v
59489
v
59502
v
59506
v
59508
v
59508
v
59513
v
59514
v
59515
v
59516
v
59487
v
59488
v
59489
v
59496
v
59497
v
59497
v
59496
v
59497
v
59498
v
59498
v
59498
v
59498
vv
59498
v
59499
v
59499
v
59499
v
59499
vv
59499
v
Schneider Electric MV catalogue Merlin Gerin
91
Earthing switch
Function Designation p.59
d/o CB position locking
d/o CB interlocking
Order form: earthing switch (ES) voltage presence indicator system (VPIS) d/o circuit breaker interlocking
Lead
Time
References
59521
v
Circuit breaker interlocking
59521
v
Price p.59
Electromagnetic interlocking for CB O/C position
24V DC
48V DC
110V DC
220V DC
p.59
Interlocking by lock (lock not supplied)
Ronis / Profalux keylock
p.59
Operating shaft = 1 per switchboard
switchboard accessories
59526
v
59527
v
59528
v
59529
v
59523
v
59526
v
59527
v
59528
v
59529
v
59523
v
End
92
MV catalogue Merlin Gerin Schneider Electric
Switchboard components
Order form: switchboard components
Function Designation p.63
Fixed coupling link
go to installation notice: drawings
References
switchboard components
p.63
Withdrawable coupling link: phase-distance, Ith, Ir
145 mm 25 kA 1250 A
185 mm 31.5 kA 1250 A
240 mm 40 kA 3150 A
59440
v
59441
v
59442
v
p.63
Busbar earthing truck
145 mm 17.5 kV 25 kA 3 s
185 mm 17.5 kV 31.5 kA 3 s
240 mm 17.5 kV 40 kA 3 s
59470
v
59471
v
59472
v
p.64
CB extraction table
upper table + complete device drawing complete extraction table
59084
v
59132
v
Price
Lead
Time p.64
Operation shaft common to earthing switch & CB racking
operating shaft
59449
v
p.64
Busbar connection
busbar cover
59420
v
Schneider Electric MV catalogue Merlin Gerin
93
Switchboard components
Function Designation p.59
Voltage indication
box 3.2 - 7.2 kV box 7.2 - 17.5 kV
L1
L2
L3
Phase comparator
phase comparator
Order form: switchboard components
References
cubicle components
59498
v
59499
v
59448
v
Price
Lead
Time p.65
Voltage indicator insulator
3 voltage insulators
59430
v
p.65
Insulator support
3 standard insulators
p.65
Cubicle compartement handles
handles handle with key
59431
v
59270
v
59271
v
p.65
Heating resistor
heating resistance
59280
v
jig for CB/cradle changeability & wiring tool & set for arm fixation
jig mandatory for each partner & wiring tool & fixation set
AMEG
tools for partners
59310
v
94
MV catalogue Merlin Gerin Schneider Electric
Separate accessories
Order form: separate accessories
Function Designation p.24
Cradle, phase distance
cradle / 145 mm cradle / 185 mm cradle / 240 mm
References
for full CB version
59292
v
59293
v
59294
v
p.30
Low powered CTs for Sepam 1000
+ mounted on lower cradle bushings
3 CVV120 25-3150 A
3 CVV200 25-3150 A
59390
v
59391
v
p.24
Draw in/out position signaling
4 AC + 1 AC PAF
59170
v
Price
Lead
Time p.24
Additional earthing device
earthing sliding contact
59451
v
p.32
CB footing
support
59050
v
p.28
Type of fixed connection (3 units), Ir to be mounted on basic
CB or bushings
fixed distance H or V 630-1600 A variable distance H 630-1600 A variable distance V 630-1600 A fixed distance H or V 1250-2500 A variable distance H 1250-2500 A variable distance V 1250-2500 A
59400
v
59401
v
59402
v
59403
v
59404
v
59405
v
Schneider Electric
V*: vertical, H*: horizontal
MV catalogue Merlin Gerin
95
Separate accessories
Order form: separate accessories
Function Designation p.29
Type of withdrawable connections
3 clusters/fingers
3 clusters/fingers
630-1250A
1250-2500A
3 bushings/arms&clusters
630-1250A
1 cluster
1 finger
3 bushings/arms&clusters
1250-2500A
1 bushing 1 arm
3 arms
630-1250A
1250-2500A
3 arms
3 bushings without fingers
630-1250A
3 bushings without fingers
1250-2500A
p.30
Low powered CTs for Sepam 1000
+
3 CVV120
3 CVV200
25-3150 A
25-3150 A
References
for modular CB version
59369
v
59371
v
59370
v
59372
v
59396
v
59397
v
59406
v
59407
v
59390
v
59391
v
p.24
Additional earthing device
earthing sliding contact
59451
v
Price
Lead
Time p.31
Racking base
racking base
59300
v
p.31
Draw in/out position signaling
4 AC + 1 AC PAF
59170
v
p.32
CB footing
support
59050
v
96
MV catalogue Merlin Gerin Schneider Electric
Separate accessories
Order form: separate accessories
Function
Loose CB cover
Designation
loose CB cover
User manual
User manual
Unit LV terminal block for drawout installation
1 drawout CB terminal block
Unit LV terminal block for fixed installation
1 fixed CB terminal block
p.34
MX1, MX2, XF coil voltage
24…30V
48…60V
100…130V
200…250V
DC 50/60 Hz
DC 50/60 Hz
DC 50/60 Hz
DC 50/60 Hz
p.34
MN undervoltage shunt trip voltage
24…30V DC 50/60 Hz
48…60V
100…130V
200…250V
DC 50/60 Hz
DC 50/60 Hz
DC 50/60 Hz
p.34
MN time setting (0.5 - 0.9 - 1.5 - 3s) voltage
48…60V DC 50/60 Hz
100…130V DC 50/60 Hz
200…250V DC 50/60 Hz
References
for CB mechanism
59078
v
59077
v
47849
v
47074
v
59141
v
59142
v
59143
v
59144
v
33668
v
33669
v
33670
v
33671
v
33680
v
33681
v
33682
v
p.33
MITOP
COM
UC1 UC2
UC3
UC4
SDE2 SDE
1
M2C /RES mitop 200-250 V AC 50/60 Hz
59160
v
Price
Lead
Time
Schneider Electric MV catalogue Merlin Gerin
97
Separate accessories
Order form: separate accessories
Function Designation p.36
MCH motor voltage
24…30V
48…60V
100…125V
200…250V
48…60V
100…130V
200…240V
p.37
CDM operating counter
operation counter
DC
DC
DC
DC
DC 50/60 Hz
DC 50/60 Hz
DC 50/60 Hz
References
47888
v
47889
v
47890
v
47891
v
47889
v
47893
v
47894
v
48535
v
00399
p.37
Aditionnal auxiliary contacts
4 AC "sliver"
47887
v
p.37
Indication of CB ready to close PF
1 AC PF
47080
v
p.38
Open position CB interlocking
for lock & key for padlock supplied by client
p.38
RONIS lock & key configuration
with one lock with 2 idem locks with 2 different locks
p.38
PROFALUX lock & key configuration
with one lock with 2 idem locks with 2 different locks
98
MV catalogue Merlin Gerin
48541
v
48539
v
41940
v
41950
v
59341
v
42888
v
42878
v
59342
v
Price
Lead
Time
Schneider Electric
Separate accessories
Order form: separate accessories
Function Designation p.39
Padlocking of O/C push button
for padlock supplied by client
References
48536
v
3 MV connectors shield, Ir
630-1250 A
2500 A
Labels kit for Push Button & indicator (O/C)
ANSI labels green red
Auto discharge device
auto discharge
59435
v
59436
v
59100
v
59080
v
Price
Lead
Time
Schneider Electric MV catalogue Merlin Gerin
99
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 1 Evolis - intrerupatorul automat cu vid
- 3 Game si capacitati de rupere a arcului electric
- 5 Varianta completa
- 6 Versiunea modulara
- 10 Suport electronic
- 12 Panorama
- 14 Varianta completa - performante
- 20 Varianta modulara - performante
- 22 Conectare
- 24 Senzori de curent
- 25 Montaj
- 26 Suportul pentru varianta debrosabila
- 27 Circuit de deschidere
- 29 Comanda la distanta
- 31 Contacte de semnalizare
- 32 Blocare
- 33 Dimensiuni
- 37 Protectie, monitorizare, control si masura
- 38 Sepam 1000 +
- 40 Functii
- 41 Protectie
- 42 Game de reglaje
- 43 Senzori de curent
- 44 Control si monitorizare
- 45 Comunicare
- 46 Soft
- 47 Masura
- 48 Dimensiuni
- 50 Separator de punere la pamant
- 51 Interblocare
- 53 Componentele tabloului
- 56 Componentele celulei
- 59 Componentele compartimentului de control
- 59 Circuit de protectie CA/CC
- 61 Semnalizare si control
- 63 Blocuri terminale
- 65 Cum se comanda
- 65 Varianta completa
- 67 Varianta modulara
- 70 Accesorii
- 72 Sepam 1000+
- 75 Accessorii Sepam 1000 +
- 77 Separator de punere la pamant, indicator de prezenta tensiunii, interblocaje
- 79 Componentele tabloului
- 81 Accesorii separate