- Industrial & lab equipment
- Electrical equipment & supplies
- Power conditioning
- Uninterruptible power supplies (UPSs)
- Allen-Bradley
- 1609-D
- User manual
advertisement
User Manual
Bulletin 1609 Uninterruptible Power Supply
Catalog Numbers 1609-D and 1609-B
Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1
available from your local Rockwell Automation® sales office or online at http://www.rockwellautomation.com/literature/ ) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and Figures in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and Figures.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
IMPORTANT
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
WARNING: This is a category C2 UPS product. In a residential environment, this product may cause radio interference, in which case the user may be required to take additional measures.
Additional Resources
Preface
These documents contain additional information concerning related products from Rockwell Automation
Resource
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Product Certifications website, http://www.ab.com
Publication Number:
1609-UM007_-EN-P
Publication Number:
1609-UM008_-EN-P
Publication Number:
1609-IN012_-EN-P
Publication Number:
1609-IN013_-EN-P
Publication Number:
1609-IN014_-EN-P
Publication Number:
1609-IN015_-EN-P
Description
Provides general guidelines for installing a Rockwell
Automation industrial system.
Provides declarations of conformity, certificates, and other certification details.
Bulletin 1609 UPS Management Software
User Manual
Network Management Card - Cat. No. 1609-ENET
User Manual
Bulletin 1609-D
Installation Instructions
Bulletin 1609-B
Installation Instructions
Surge Protective Device (Cat. No. 1609-SPD)
Installation Instructions
Network Management Card (Cat. No. 1609-ENET)
Installation Instructions
You can view or download publications at http:/www.rockwellautomation.com/literature/ . To order paper copies of technical documentation, contact your local Allen-Bradley distributor or
Rockwell Automation sales representative.
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
3
Preface
Notes:
4
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Table of Contents
Bul. 1609-D Installation Instructions
Battery Wiring and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Mount the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Hardwire UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Selection of Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Connect Power and Equipment to the UPS . . . . . . . . . . . . . . . . . . . . . . . . . 10
Bul. 1609-D Block Figure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Bul. 1609-B Installation Instructions
Battery Wiring and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Mount the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Hardwire UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Selection of Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Connect Power and Equipment to the UPS . . . . . . . . . . . . . . . . . . . . . . . . . 14
1609-B Block Figure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Bul. 1609-EXBAT Installation
Instructions
Battery Wiring and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Mount the 1609-EXBAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Selection of Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Connect the 1609-EXBAT to the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
General Information 1609-D and
1609-B
Recommended Battery for use with the UPS . . . . . . . . . . . . . . . . . . . . . . . . 19
Dry I/O Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
USB Communication Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Manual or Remote Enable/Disable of UPS Output Selection . . . . . . . . . 20
Manual Enable/Disable/Self-test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Remote Enable/Disable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Display LED Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Troubleshooting
UPS LED Fault Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Output Short Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Output Overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Over Temperature from the Heatsink . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Over Ambient Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Over Voltage from The DC/DC Converter of Inverter . . . . . . . . . . 23
Over Voltage from The Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Under Voltage from The Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Over Voltage from the Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Under Voltage from the Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Fan Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Charger Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
TMOV Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Missing Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Replace Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
5
Table of Contents
Troubleshooting (continued)
Specifications
Dimensions
Service Instructions
UPS Management Software Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . .25
UPS Network Managemenr Card Troubleshooting . . . . . . . . . . . . . . . . . .26
Bul. 1609-D Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Bul. 1609-B Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Bul. 1609-D Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Bul. 1609-B Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Bul. 1609-EXBAT Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Bul. 1609-BRK Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Service Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
6
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Battery Wiring and
Installation
-Bulletin 1609-D Installation Instructions
ATTENTION: Do not service the 1609-SPD without disconnecting the power sources due to electric shock hazard for risk of severe injury or death.
1. To access the battery compartment remove the three screws and the battery door.
2. Remove the battery container, jumpers, and wire harness from the battery compartment. Place the battery container and batteries onto a flat surface.
Use the provided jumper wires to connect the batteries in series. Connect the positive terminal (red) of the battery to the negative terminal (black) of another battery. See photo below for details.
3. Connect the red wire of the harness to the positive terminal (top red) and the black wire of the harness to the negative terminal (bottom black). See photo below for details.
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
7
Bulletin 1609 UPS
Battery Wiring and
Installation (cont.)
4. Fold the battery container and seal it with tape.
5. To connect the batteries to the UPS, insert the batteries into the battery compartment, open the white connector retainer and connect the two cables together as shown in the photo below.
6. To complete the battery installation, close the white connector retainer and reattach the battery door with the three screws
(torque of 8.7+/-1.7 lb-in).
8
Mount the UPS
The UPS-D is designed to mount on the back of the panel or to the floor of the enclosure. The UPS mounts to a bracket assembly (1609-BRK) that allows it to mount to either the panel or floor (see Figure 1 below).
Figure 1 - Mounting the UPS
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Hardwire UPS
Selection of Cables
Bulletin 1609 UPS
Wiring of the UPS should be performed by a qualified electrician using the appropriate wire gauges.
Table 1 - AC Main Input/Output Wiring for UPS:
Item Specification
Wire Size 14 AWG
Minimum temperature
Wire conductor material
Tightening torque for terminals
75 °C
Copper only
4.4 lb-in.
Table 2 - DC Input / Output Wiring for External Battery Cabinet:
Item Specification
Wire Size 10 AWG
Minimum temperature
Wire conductor material
Tightening torque for terminals
75 °C
Copper only
12 lb-in.
WARNING: To reduce the risk of fire, connect only to a circuit with 20 amperes maximum branch circuit overcurrent protection in accordance with the National
Electric Code, ANSI/NFPA 70.
A disconnect switch shall be provided by others for AC output circuit.
To reduce the risk of fire, connect only to a circuit with branch circuit overcurrent protection for 20 amperes rating in accordance with the National Electric Code,
ANSI/NFPA 70.
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
9
Bulletin 1609 UPS
Connect Power and
Equipment to the UPS
WARNING: This UPS features Surge Protection Device (SPD) is located on the left front of the unit. Disconnect all power sources before servicing due to Electric Shock Hazard for risk of severe injury or death.
1. Connect the appropriate input power to the UPS's input (Line, Neutral and Ground) terminals (see Figure 2).
2. Connect the specified equipment to the UPS's output (Line, Neutral and
Ground) terminals (see Figure 2).
Figure 2 - System Wiring
1609-D Block Figure
3. Connect any additional optional accessories (1609-ENET card).
L
AC
Input
E
Breaker
N
Input
Filter
Backfeed
Relay
AVR
AC to DC
Backfeed
Relay
AC to AC Inverter
Relay
+
-
DC to DC DC to AC
L
E
AC
Output
N
10
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Battery Wiring and Installation
Bulletin 1609 UPS
1609-B Installation Instructions
ATTENTION: Disconnect the 1609-SPD before servicing, due to electric shock hazard for risk of severe injury or death.
Note: Batteries are not included with the 1609-B UPS
1. To access the battery compartment remove the three screws and the battery door.
2. Remove the battery container, jumpers, and wire harness from the battery compartment. Place the battery container and batteries onto a flat surface.
Use the provided jumper wires to connect the batteries in series. Connect the positive terminal (red) of the battery to the negative terminal (black) of another battery. Connect the red wire of the harness to the positive terminal (top red) and the black wire of the harness to the negative terminal (bottom black). See photo below for details.
3. Fold the battery container and seal it with tape.
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
11
Bulletin 1609 UPS
Battery Wiring and Installation (cont.)
4. To connect the batteries to the UPS, insert the batteries into the battery compartment, open the white connector retainer and connect the two cables together as shown in the photo below.
5. To complete the battery installation, close the white connector retainer and reattach the battery door with the three screws (torque of 8.7+/-1.7 lb-in).
12
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Mount the UPS
Bulletin 1609 UPS
The 1609-B UPS products are designed to mount to a heavy duty DIN-rail
(see Figure 3 below). The 1609-B UPS products are also designed with an optional bracket assembly (Cat 1609-BRK) that allows it to mount to either the panel or floor (see Figure 4 below).
Figure 3 - Standard DIN-Rail Mount
Figure 4 - Optional Panel or Floor Mount
Hardwire UPS
Selection of Cables
Wiring of the UPS should be performed by a qualified electrician using the appropriate wire gauges.
Table 3 - AC Main Input / Output Wiring for UPS
Item
Wire Size
Minimum Temperature
Wire Conductor Material
Specification
14 AWG
75 °C
Copper only
Tightening Torque for Terminals 4.4 lb - in.
WARNING: To reduce the risk of fire, connect only to a circuit with 20 amperes maximum branch circuit overcurrent protection in accordance with the National
Electric Code, ANSI/NFPA 70.
A disconnect switch shall be provided by others for AC output circuit.
To reduce the risk of fire, connect only to a circuit with branch circuit overcurrent protection for 20 amperes rating in accordance with the National Electric Code,
ANSI/NFPA 70.
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
13
Bulletin 1609 UPS
Connect Power and
Equipment to the UPS
WARNING: This UPS features Surge Protective Device (SPD) located on the top of the unit. Please disconnect all power sources before servicing due to Electric
Shock Hazard for risk of severe injury or death.
1. Connect the appropriate input power to the UPS's input (Line, Neutral and Ground) terminals (see Figure 5).
2. Connect the specified equipment to the UPS's output (Line, Neutral and
Ground) terminals (see Figure 5).
Figure 5 - System Wiring
1609-B Block Figure
L
INPUT
N G L
OUTPUT
N G
L
AC
Input E
N
AC Input
AC Output
Input
Filter
Backfeed
Relay
Backfeed
Relay
Inverter
Relay
+
-
AC to DC (Charger) DC to DC DC to AC (Step Wave)
L
E
AC
Output
N
14
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Battery Wiring and Installation
Bulletin 1609 UPS
1609-EXBAT Installation Instructions
Only use battery wires that have been provided with the 1609-EXBAT.
WARNING: A disconnect switch shall be provided by others for DC output circuit. To reduce the risk of fire, connect only to a circuit with branch circuit overcurrent protection for 35 amperes rating in accordance with the National
Electric Code, ANSI/NFPA 70.
Before connecting a battery pack to UPS, the emergent disconnecting device shall be provided between the UPS and battery pack.
1. To access the battery compartment remove the six screws and the battery door.
2. Remove the battery container, jumpers and wire harness from the battery compartment. Place the battery container and batteries onto a flat surface.
Use the provided jumper wires to connect the batteries in series. Connect the positive terminal (red) of the battery to the negative terminal (black) of another battery. See photo below for details.
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
15
Bulletin 1609 UPS
Battery Wiring and Installation (cont.)
3. Connect the shorter set of red and black wires of the harness to the top terminals (red - to - red and black - to - black). Connect the longer set of red and black wires of the harness to the bottom terminals (red - to - red and black - to - black) and route the wires through the cut-out hole. See photo below for details.
4. Fold the battery container and seal it with tape.
5. Insert the batteries into the battery compartment in the orientation as shown in the photo below.
6. Open the white connector retainer and connect the two cables together as shown in the photo below.
16
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Battery Wiring and Installation (cont.)
Bulletin 1609 UPS
7. To complete the battery installation, insert the surplus wire harness into the free space, close the white connector retainer and reattach the battery door with the six screws (torque of 8.7+/-1.7 lb-in).
Mount the 1609-EXBAT
The 1609-D UPS can be used with the External Battery Unit (1609-EXBAT).
The 1609-EXBAT unit is designed to mount to a heavy duty DIN-rail (see
Figure 6) or the optional mounting bracket assembly (1609-BRK) which allows it to mount to either the panel or floor (see Figure 7).
Figure 6 - Heavy Duty DIN Rail Mount
Figure 7 - Panel or Floor Mount
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
17
Bulletin 1609 UPS
Selection of Cables
Connect 1609-EXBAT to the UPS
Table 4 - DC Input/Output Wiring for External Battery Cabinet
Item Specification
Wire Size 10 AWG
Minimum temperature
Wire conductor material
Tightening torque for terminals
75 °C
Copper only
12 lb-in.
To install the 1609-EXBAT unit with the 1609-D UPS, connect the three 10
AWG wires from the 1609-EXBAT terminals to the 1609-D UPS terminals marked as ‘EXTERNAL BATT PACK (36V)’. (See Figure 8)
Dispose of used batteries according to the battery instructions.
Figure 8 - System Wiring
18
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Recommended Battery for Use with the UPS and 1609-EXBAT
Bulletin 1609 UPS
General Information 1609-D and 1609-B UPS Units
Rockwell Automation battery catalog numbers 1609-SBAT and 1609-HBAT consist of the battery manufacturers listed below:
Manufacturer
B & B Battery (USA)
GS Yuasa International Ltd.
Shenzhen Center Power Tech Co., Ltd.
Shenzhen Ritar Power Co., Ltd.
CSB Battery Co., Ltd.
MH Number
MH19884
MH12970
MH25860
MH28539
MH14533
Type
HRLS 5.5-12
BP 5-12
HR 5.5-12
SHR7-12
NPH5-12
CP1250
RT1250
HR1221W
Rating
12V DC, 2.75 Ah
12V DC, 5.0 Ah
12V DC, 2.75 Ah
12V DC, 3.375 Ah
12V DC, 5.0 Ah
12V DC, 5.0 Ah
12V DC, 5.0 Ah
12V DC, 5.25 Ah
Not for use in a computer room as defined in the Standard for the Protection of Electronic Computer/Data Processing Equipment, ANSI/NFPA 75.
Dispose of used batteries according to the battery instructions.
Dry I/O Contacts
There is one Remote Enable/Disable Switch connection and 3 Dry I/O Contacts available on the front of the UPS. Do not apply external power to the Remote
Enable/Disable Switch; however, the 3 sets of Dry Contacts require external power supplies (Contacts Rating is 1A/24V DC). Each of the dry contacts is used to provide a remote status indication of the UPS, as follows:
8 7 6 5 4 3 2 1
•1 and 2 On Battery Contact (NO)
•3 and 4 Low Battery Contact (NO)
•5 and 6 Fault (Indicates UPS has faulted see trouble shooting section)
•7 and 8 Remote On/O (Shorted (closed) for ON, Open for OFF)
USB Communication Port
The UPS supports a USB communication port for the end user to connect with a computer. The user may monitor all the UPS status through the USB port if the 1609 UPS Management
Software is installed in the computer. The software is stored in the CD and can be found in the accessory bag.
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
19
Bulletin 1609 UPS
Manual or Remote
Enable/Disable of UPS Output Selection
The 1609 UPS output is designed to be manually or remotely enabled or disabled. User is required to enable or disable the remote function switch on the front panel.
REMOTE FUNCTION
Manual Enable/Disable/
Self-test
Remote Enable/Disable
DISABLE ENABLE
• Selected 'DISABLE' for Manual Enable/Disable the UPS's Output.
• Selected 'ENABLE' for Remote Enable/Disable the UPS's Output.
The Power Button on the front of the UPS is used to manually enable or disable the output of the 1609-D UPS.
To enable the 1609-D UPS, press and hold the power button until one beep is heard.
To disable the 1609-D UPS, press and hold the power button until three beeps are heard, then release immediately (takes approximately 3 seconds).
To perform a self-test, press and hold the power button until two beeps are heard, then release immediately. (The UPS must operate for at least 4 hours before executing this function)
An external switch connected to the Dry I/O terminals 7 and 8 is required to remotely Enable or Disable the UPS output.
8 7 6 5 4 3 2 1
To enable the UPS, close the switch that is connected to the Dry I/O terminals 7 and 8.
SW
24 Vdc
To Disable the UPS, open the switch that is connected to the
Dry I/O terminals 7 and 8.
20
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Display LED Indicators
Bulletin 1609 UPS
Indicator LED Indicator Title
Online
AVR Trim ➊
AVR Boost ➊
On Battery
Description
The UPS is supplying utility power to the connected equipment
(see Troubleshooting).
The UPS is compensating for a high utility voltage
(see Troubleshooting).
The UPS is compensating for a low utility voltage
(see Troubleshooting).
The UPS is supplying battery power to the connected equipment.
Overload The connected equipment is drawing more than the UPS power rating allows (see Troubleshooting).
Replace Battery/Disconnect The battery is disconnected or must be replaced
(see Troubleshooting).
➊ Applies to 1609-D only
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
21
Bulletin 1609 UPS
Troubleshooting
Button Function
UPS Output Enable
UPS Output Disable
Self-Test
Explanation
Press and hold the button until one beep is heard, then release immediately
Press and hold the button until three beeps are heard, then release immediately
Press and hold the button until two beeps are heard, then release immediately (The UPS must operate for at least 4 hours before executing this function)
Problem
No LED illuminates /
No alarm
No UPS output
UPS Operates on battery although input utility voltage exists
Input line utility power circuit breaker trip
Possible Cause
UPS output is disabled or input utility power is not present
The UPS has not been enabled
Solution
Have qualified electrician trouble shoot the input utility power system and make the necessary corrections.
Manually Enable - Make sure the Remote Function selector switch is in the Disable position, then press and hold the UPS Power button until one beep is heard and release immediately.
Remotely Enable - Make sure the Remote Function selector switch is in the Enable position and verify that there is an adequate connection to the remote on/off dry
I/O connection (terminals 7 & 8)
The system may experience high, low or distorted input utility voltage
Reduce the UPS sensitivity by using the 1609 UPS
Management software.
If the problem persists, move or connect the UPS with a known good quality utility power source.
The system may have experienced an overload
Verify that the circuit breaker is sized properly.
Verify the load connected to the output of the UPS. Ensure that the load does not exceed the output rating of the UPS.
FAULT LED illuminates
ONLINE LED illuminates, but no UPS output is available
An internal fault has been detected Refer to the UPS LED Fault Indicators below to identify the specific fault that occurred and possible resolution.
The UPS output connection may not be connected properly
Disable the UPS output and have qualified electrician troubleshoot the output connection system and make the necessary corrections.
The battery did not provide expected runtime
The batteries might be weak or the lifespan is due
No communication between the
UPS and your PC
Wrong cable
The connection cable is not firmly connected
Charge the batteries for 8 hours and retest the runtime.
If the runtime is still less than expected after charging, replace the batteries even if the Replace Battery LED doesn’t illuminate.
Verify cable used.
Reconnect the communication cable firmly.
PC Communication Port may have been used by another process or is defective
There is interference on the connection cable
Check if there is other software or service accessing the
Communication Port on your PC, or connect it to a different communication port.
Lay the cable differently or away from other cables and reconnect the cable.
22
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Bulletin 1609 UPS
UPS LED Fault Indicators
No.
Fault
1 Output Short Circuit
GRN
RED
General Clear Fault Procedure
Press and hold the button until three beeps are heard then release immediately to turn the UPS off then press and hold the button again until one beep is heard then release to enable the output.
Description
The UPS has detected a short circuit on the Output of the UPS and disabled its output.
Solution
Have a qualified electrician troubleshoot the load connected to the output to the UPS and remove the short circuit if present.
2 Output Overload
GRN
RED
3 Over Temperature from the
Heatsink
GRN
RED
The UPS has detected an overload and disabled its output.
To clear fault, follow the General Clear Fault Procedure described above. If the problem persists, contact
Technical Support.
Verify the load connected to the output of the UPS. Ensure that the load does not exceed the output rating of the UPS. If the load exceeds the rating of the UPS please remove excess load or select the appropriate size UPS. If the problem persists, contact Technical Support.
To clear fault, follow the General Clear Fault Procedure described above.
The UPS has detected an over temperature of the heatsink and disabled its output.
Have a qualified electrician checked the ambient temperature to make sure that it does not exceed 40 °C
(1609-SBAT) or 50 °C (1609-HBAT). If it is over temperature, make the necessary correction to the system. This issue may be corrected by improving the room ambient temperature (add ventilation or provide air conditioning).
To clear fault, follow the General Clear Fault Procedure described above.
4 Over Ambient Temperature
RED
GRN
The UPS has detected an over ambient temperature and disabled its output.
Have a qualified electrician checked the ambient temperature to make sure that it does not exceed 40 °C
(1609SBAT) or 50 °C (1609-HBAT). If it is over temperature, make the necessary correction to the system. This issue may be corrected by improving the room ambient temperature (add ventilation or provide air conditioning).
To clear fault, follow the General Clear Fault Procedure described above.
5 Over Voltage from The DC/DC
Converter of Inverter
The UPS has detected an over voltage of the DC/DC
Converter and disabled its output.
Have a qualified electrician verify that the quality of utility voltage is within specification.
To clear the fault, follow the General Clear Fault Procedure described above.
If the fault is still present after attempting to clear fault, contact Technical Support.
RED
6
GRN
Over Voltage from The Inverter
RED
GRN
The UPS has detected high voltage on the inverter and disabled its output.
Have a qualified electrician verify that the quality of utility voltage is within specification.
To clear fault, follow the General Clear Fault Procedure described above.
If the fault is still present after attempting to clear fault, contact Technical Support.
7 Under Voltage from The Inverter The UPS has detected low voltage on the inverter and disabled its output.
RED
GRN
Have a qualified electrician verify that the quality of utility voltage is within specification.
To clear fault, follow the General Clear Fault Procedure described above.
If the fault is still present after attempting to clear fault, contact Technical Support.
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
23
Bulletin 1609 UPS
No.
Fault
8 Over Voltage from The Output of AVR
Description
The UPS has detected an over voltage on the output of AVR and disabled its output.
Solution
Have qualified electrician verify that the quality of the output voltage and the input utility voltage are within its specification.
To clear fault, follow the General Clear Fault Procedure described above and if the problem persists, contact Technical Support.
RED
BLINK
GRN
9 Under Voltage from The Output of AVR
The UPS has detected low voltage on the output of
AVR and disabled its output.
Have qualified electrician verify that the quality of the output voltage and the input utility voltage are within its specification.
To clear fault, follow the General Clear Fault Procedure described above and if the problem persists, contact Technical Support.
RED
BLINK
GRN
10 Fan Failure
RED
GRN
11 Charger Failure
The UPS has detected that the fan of the UPS has failed and disabled its output.
To clear fault, follow the General Clear Fault Procedure described above and if the Fan Failure persists, contact Technical Support.
The UPS has detected that the battery charger circuit has failed; however, the
UPS will continue running.
Clear this fault by removing the input utility voltage and batteries then plug the batteries back in place and turn the input utility voltage back on. Enable the UPS output to verify the fault.
If the Charger Failure persists, contact Technical Support.
12 TMOV Failure
GRN
BLINK
GRN
GRN
BLINK
GRN
13 Missing Battery
GRN
BLINK
RED
14 Replace Batteries
GRN RED
The UPS has detected that the MOV circuit has failed; however, the UPS will continue enabling the output.
Schedule to have a qualified electrician replace the MOV board (1609-SPD).
Remove the input utility power before service on this 1609-SPD due to risk of electrical shock.
The UPS has detected that the batteries are missing; however, the UPS will continue enabling the output.
Have a qualified electrician verify the battery connection for good contact and charge the batteries for
24 hours.
To clear fault, follow the General Clear Fault Procedure described above. If the battery status still indicates Missing Battery, new batteries are required.
The UPS has detected that the batteries are bad; however, the UPS will continue running.
Have a qualified electrician verify the battery connection for good contact and charge the batteries for
24 hours.
To clear fault, follow the General Clear Fault Procedure described above. If the battery status still indicates Replace Battery, new batteries are required.
24
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Bulletin 1609 UPS
Bulletin 1609 UPS
Management Software
Troubleshooting
General Clear Fault Procedure
Press and hold the button until three beeps are heard then release immediately to turn the UPS off then press and hold the button again until one beep is heard then release to enable the output.
Status Indications Indication Description
Buzzer Alarm The UPS has detected a fault and generate a buzzer alarm.
Test In Progress
UPS Fault
Battery Low
The UPS is currently in a test mode.
Solution
Verify the type of fault from the Status Indicators or the LEDs on the UPS for further troubleshooting.
Do not interrupt the UPS testing. The UPS is doing battery test.
The UPS has detected a fault and disabled its output.
Verify the type of fault from the Status Indicators or the LEDs on the UPS for further troubleshooting.
To clear fault, follow the General Clear Fault Procedure described above and if the fault persists, contact Technical Support.
The UPS has detected that the batteries are low.
The batteries must be charged for 24 hours and re-verify the battery status. If the batteries still indicate to be low, replace the batteries.
Power Failed
Overheat
Overload
The UPS has detected that the input utility voltage has failed.
The ambient temperature is greater than 60 °C, or some internal components are over temperature.
The UPS has detected that output load of UPS is greater than 110%.
Verify that the input utility voltage is within the UPS’s input specification.
If it is not, make the necessary correction to the input utility power system.
Have a qualified electrician checked the ambient temperature to make sure that it does not exceed
40 °C(1609-SBAT) or 50 °C (1609-HBAT). If the temperature exceeds the UPS rating, make the necessary correction to the system. This issue may be corrected by improving the room ambient temperature (add ventilation or provide air conditioning).
To clear fault, follow the General Clear Fault Procedure described above and if the fault persists, contact Technical Support.
Verify that the load does not exceed the load specification. If it is, remove the excess load from the
UPS’s output and clear its fault. If the problem persists, have a qualified electrician troubleshoot the UPS Load System and make the necessary corrections or select the appropriate size of UPS. If the problem persists, contact Technical Support.
Load Warning
Load Severity
UPS Disconnect
Output Abnormal
The output load over the warning threshold.
The output load over the severity threshold.
The UPS has detected a communication loss between the UPS and the computer.
To indicate the output voltage is abnormal.
Verify the output load. If it is close to 100% load, remove the excess load or select the appropriate size of UPS.
Verify the output load. If it is actually at 100% load, remove some of the non-essential load or select the appropriate size of UPS.
Please check the USB cable between computer and UPS for secure connection or replace the cable with a known good cable.
If communication is established, re-open the UPS Management software. If the problem persists, contact Technical Support.
Have qualified electrician verify that the quality of the output voltage and the input utility voltage are within its specification.
To clear fault, follow the General Clear Fault Procedure described above and if the problem persists, contact Technical Support.
Output Off
UPS System Off
The UPS is operating in standby mode, or UPS is faulted.
The UPS system is in the standby state.
If it is identified as the UPS fault shutdown then turn the UPS off, and then turn UPS on again to reset the fault. If the fault persists, contact Technical Support.
If it is identified as the UPS fault shutdown then turn the UPS off. Turn UPS on again to reset the fault. If the fault persists, contact Technical Support.
Apply the input utility voltage to the UPS.
Awaiting Power
Battery Need Replace
Battery Depleted
The battery is depleted and the UPS awaits the return of input utility voltage.
The UPS has detected that the battery is bad or opened.
Have a qualified electrician verify the battery connection for good contact and charge the batteries for 24 hours.
To clear fault, follow the General Clear Fault Procedure described above. If the battery status still indicates Battery Need Replace, new batteries are required.
The UPS has detected that the batteries are depleted.
Have a qualified electrician verify the battery connection for good contact and charge the batteries for 24 hours.
To clear fault, follow the General Clear Fault Procedure described above. If the battery status still indicates Battery Depleted, new batteries are required.
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
25
Bulletin 1609 UPS
Bulletin 1609
Network Management Card
Troubleshooting
Status Indications
UPS Disconnect
Buzzer Alarm
Input Out Of Range
Battery Low
Battery Depleted
Battery Need Replace
Test In Progress
Test Fail
Output Off
UPS System Off
UPS Shutdown
Output Over Voltage
Output Under Voltage
Overload
Over Temperature
Fan Abnormal
Inverter Abnormal
Charger Abnormal
General Clear Fault Procedure
Press and hold the button until three beeps are heard then release immediately to turn the UPS off then press and hold the button again until one beep is heard then release to enable the output.
Indication Description
The communication between UPS and the 1609-ENET card has been disconnected.
Solution
Check the 1609-ENET LEDs for the communication status and the operation of UPS.
If the UPS is operating normal but the LEDs of the 1609-ENET card are not working properly, make sure the cable is securely connected from the 1609-ENET card to the computer.
If the LEDs of the 1609-ENET card is still not working properly, apply a known good 1609-ENET card to verify whether the failure is on the UPS or the 1609-ENET.
Please verify the type of fault from the Status Indicators or the LEDs on the UPS for further troubleshooting.
The UPS has detected a fault and generated a buzzer alarm.
The UPS has detected that the input utility voltage is out of range.
The UPS has detected that the batteries are low.
The UPS has detected that the batteries are depleted.
The UPS has detected that the battery is bad or opened.
The UPS is currently in a test mode.
The UPS has detected that the battery is bad.
The UPS is operating in standby mode or fault shutdown.
Have a qualified electrician verify the battery connection for good contact and charge the batteries for 24 hours.
To clear fault, follow the General Clear Fault Procedure described above. If the battery status still indicates
Battery Need Replace, new batteries are required.
Do not interrupt the UPS testing.
Verify that the battery is not disconnected or replace the batteries with a brand new set of batteries. Ensure the UPS ran for at least 4 hours before test.
If it is identified as the UPS fault shutdown then turn the UPS off, and then turn UPS on again to reset the fault
If the fault persists, contact Technical Support.
The UPS system is in the standby state.
If it is identified as the UPS fault shutdown then turn the UPS off, and then turn UPS on again to reset the fault. If the fault persists, contact Technical Support.
The UPS was commanded to shut down or fault shutdown.
If it is identified as the UPS fault shutdown then turn the UPS off, and then turn UPS on again to reset the fault. If the fault persists, contact Technical Support.
The UPS has detected that the output voltage is above the UPS’s output specification.
The UPS has detected that the output voltage is below the UPS’s output specification.
Have qualified electrician verify that the quality of the output voltage and the input utility voltage are within its specification.
To clear fault, follow the General Clear Fault Procedure described above and if the problem persists, contact
Technical Support.
Have qualified electrician verify that the quality of the output voltage and the input utility voltage are within its specification.
To clear fault, follow the General Clear Fault Procedure described above and if the problem persists, contact
Technical Support.
The UPS has detected that the UPS’s output load is greater than 110%.
The UPS has detected that the ambient temperature is greater than
60 °C, or some of the internal components are over temperature.
Verify that the load does not exceed the load specification.
If it is, remove the excess load from the UPS’s output and clear the fault. If the problem persists, have a qualified electrician troubleshoot the UPS Load System and make the necessary corrections or select the appropriate size of UPS. If the problem persists, contact Technical Support.
Have a qualified electrician check the ambient temperature to make sure that it does not exceed 40°C (1609-
SBAT) or 50°C (1609-HBAT). If it is over, make the necessary correction to the system. This issue may be corrected by improving the room ambient temperature (add ventilation or provide air conditioning).
Following the General Clear Fault Procedure to clear this fault.
The UPS has detected that the UPS’s fan has failed.
The UPS has detected that the UPS inverter circuit has failed.
The UPS has detected that the UPS battery charger circuit has failed.
Verify that the input utility voltage is within the UPS’s input specification.
If it is not, makes the necessary correction to the input utility power system.
The batteries must be charged for 24 hours. After charging batteries verify the battery status. If the batteries still indicate that they are low, replace the batteries.
Have a qualified electrician verify the battery connection for good contact and charge the batteries for 24 hours.
To clear fault, follow the General Clear Fault Procedure described above. If the battery status still indicates
Battery Depleted, new batteries are required.
To clear fault, follow the General Clear Fault Procedure described above and if the Fan Failure persists, contact
Technical Support.
Have a qualified electrician verify that the quality of utility voltage is within specification.
To clear fault, follow the General Clear Fault Procedure described above and if the Inverter Failure persists, contact Technical Support.
Clear this fault by removing the input utility voltage and batteries. Plug the batteries back in place and turn the input utility voltage back on. Enable the UPS output to verify the fault.
If the Charger Failure persists, contact Technical Support.
26
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Bulletin 1609 UPS
Bul. 1609-D Specifications
Input
Output
Online
On Battery
Short Circuit Protection
Efficiency
V nom.
Capacity
Voltage Range, default
Voltage Range, widest online
Current nom.
Capacity Frequency
PFC
V nom.
Capacity
Output Voltage Range, default
Output Voltage Range, widest online
Transfer Point Accuracy
V nom
Frequency
THD
Crest Factor
On Battery (Typical with resistive load)
1609-D600N
120V
600 VA (390 W)
90...145V
90...145V
5.5 A
50/60 Hz ± 3 Hz
1609-D1000N
120V
1000 VA (650 W)
90...145V
90...145V
8.8 A
None None
120V
600 VA (390 W)
108...132 V
108...132 V
± 3 %
120V (sine wave)
50/60 Hz ± 0.5Hz
≤ 10% Full Linear Load
2.2:1
75%
Online - Typical with resistive load excluding AVR mode) 86%
50/60 Hz ± 3 Hz
1000 VA (650 W)
94%
Protection Surge
Overload (Shutdown after 10 s)
380 Joules
> 110...130%
Regulatory
Overload (Shutdown immediately)
Output Short Online/Battery
Thermal Protection
Safety
130%
Premises branch circuit over-current protection/Shutdown
UPS inside temperature ≥ 60 ºC
UL1778, CSA C22.2 No. 107.3, EN/IEC62040-1
Battery Pack
Environment
EMC
Markings
Run Time
Type
Voltage
Charger
Recharger Time
Lifetime
Temperature
FCC & CE (EN 62040-2)
UL, cULus, FCC, CE, C-Tick
≥5 min (at 25 °C, full R load) ≥3.5 min (25 °C, full R load)
1609-D1500N
120V
1500 VA (980 W)
90...145V
90...145V
13 A
50/60 Hz ± 3 Hz
None
1500 VA (980 W)
95%
≥2.5 min (at 25 °C, full R load)
Sealed Lead Acid Battery 12V/5Ah (for 0...40 °C B.B. BP5-12) 12V/5.5Ah (for 0...50 °CB.B. HRL5.5-12)
36V
Current limited, constant voltage float charger
Less than 8 hr to 90% capacity after discharge with full load
2...3 years at 25 °C ambient temperature
Operating Standard Battery 0...+40 °C (+32...+104 °F) Hi-Temperature Battery 0...+50 °C (+32...+122 °F)
Non-operating/Storage -15...+45 °C (+5...+113 °F)
Altitude
Humidity
Heat Output
Operating 0...6600 feet (0... 2000 meters)
Operating/Storage 5...95% RH (Non-condensing)
On Line, Full load: 217 BTU/hr
On Line, Full load, Charging:
296 BTU per hour
On Battery: Full Load: 1331 BTU per hour
On Line, Full load: 142BTU/hr
On Line, Full load, Charging:
221 BTU per hour
On Battery: Full Load: 2218BTU per hour
On Line, Full load: 176BTU/hr
On Line, Full load, Charging:
256BTU per hour
On Battery: Full Load: 3344BTU per hour
Mechanical
Audible Noise
Approximate Dimensions L*W*H In. (mm)
Approximate Weight lbs (kg)
< 50 dBA @ Front Side 1 Meter
8.66 x 16.14 x 10.24 (220 x 410 x 260)
29.7 (13.5) 30.1 (13.7) 31 (14.1)
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
27
Bulletin 1609 UPS
Bul. 1609-B Specifications
Input V nom.
Capacity
Voltage Range, default
Voltage Range, widest online
Current nom.
Capacity Frequency
1609-B600N
120V
600 VA (360 W)
96...138V
1609-B1000N
120V
1000 VA (600 W)
96...138V
5.4 A
50/60 Hz ± 3 Hz
8.9 A
50/60 Hz ± 3 Hz
None None
Output
Online
On Battery
Short Circuit Protection
Efficiency
PFC
V nom.
Capacity
Output Voltage Range, default
Output Voltage Range, widest online
Transfer Point Accuracy
V nom
Frequency
THD
Crest Factor
On Battery (Typical with resistive load)
120V
600 VA (360 W)
96...138V
96...138V
± 3%
120V (step wave)
50/60 Hz ± 1 Hz
47.5% (step wave)
2.5:1
80% Typical with resistive load
Online - Typical with resistive load excluding AVR mode) 94% Typical with resistive load
1000 VA (600 W)
47.6% (step wave)
Protection Surge
Overload (Shutdown after 10 s)
380 Joules (Total performance rated with 10*1000 μ s pulse)
> 110...130% - shutdown after 5 sec
Overload (Shutdown immediately)
Output Short: Online
Output Short: Battery
Thermal Protection
130% shutdown immediately
Premises branch circuit over-current protection
Shutdown
UPS inside temperature ≥ 70 °C
Regulatory
Battery Pack
Safety
EMC
Markings
Run Time
Type
UL1778, CSA C22.2 No. 107.3-05, EN/IEC62040-1
FCC & CE (Class A)
UL, cULus, FCC, CE, C-Tick
≥5 min (at 25 °C, full load = 360W, PF = 0.6...0.75)
Sealed Lead Acid Battery
12V/5Ah (for 0...40 °C: B.B. BP5...12)
12V/5.5 Ah (for 0...50 °C: B.B. HRL5.5...12)
24V
≥2 min (at 25 °C, full load = 600W, PF = 0.6...0.75)
Environment
Voltage
Charger
Recharger Time
Lifetime
Temperature
Current limited, constant voltage float charger
Less than 12 hrs to 90% capacity after discharge with full load
2...3 years at 25 °C ambient temperature
Operating Standard Battery 0...+40 °C (+32...+104 °F) Hi-Temperature Battery 0...+50 °C (+32...+122 °F)
Non-operating/Storage -15...+45 °C (+5...+113 °F)
Mechanical
Altitude
Humidity
Heat Output
Audible Noise
Approximate Dimensions L*W*H In. (mm)
Approximate Weight lbs (kg)
Operating 0...6600 feet (0... 2000 meters)
Operating/Storage 5...95% RH (Non-condensing)
On Line, Full load: 107 BTU/hr
On Line, Full load, Charging: 160 BTU per hour
On Battery: Full Load: 1228 BTU per hour
< 45 dBA @ Front Side 1 Meter
6.1 x 11 x 7.09 (155 x 300 x 180)
14.5 (6.6)
On Line, Full load: 178 BTU/hr
On Line, Full load, Charging: 231 BTU per hour
On Battery: Full Load: 2047 BTU per hour
14.7 (6.7)
28
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Appendix
A
1609 UPS Dimensions
1609-D UPS Dimensions
375
U N I N T E R R U P T I B L E
P O W E R S U P P LY
1 6 0 9 - D
200
257
220
1609-B UPS Dimensions
339
300
196
U N I N T E R R U P T I B L E
P O W E R S U P P LY
1 6 0 9 - B
140
1609-EXBAT Unit Dimensions
339
300
140
196
178
178
197
140 140
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
187
170
160
187
170
160
29
Appendix A 1609 UPS Dimensions
1609-BRK Dimensions
(1609-D orientation)
1609-BRK Dimensions
(1609-B orientation)
40 227
382
302
7
110
175
33
30
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
125
Service Instructions
1609 UPS Dimensions Appendix A
If the UPS requires service, do not return it to the distributor. Follow these steps:
1. Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
2. When replacing batteries, replace with the same number of the 1609 battery packs supplied by Rockwell Automation.
WARNING: Do not dispose of battery in a fire. The battery may explode. Do not open or mutilate the battery or batteries. Released electrolytes are harmful to the skin and eyes. It may be toxic. A battery can present a risk of electrical shock and high short circuit current.
3. Review the problems discussed in the Troubleshooting section of this manual to eliminate common problems.
4. If the problem persists, contact Rockwell Automation Customer Support at 440-646-5800.
5. Pack the UPS in its original packaging.
– Pack the UPS properly to avoid damage in transit. Never use Styrofoam beads for packaging.
– Damage sustained in transit is not covered under warranty.
ATTENTION: Always disconnect the battery(s) before shipping, in compliance with U.S. Department of Transportation (DOT) and IATA regulations. The battery(s) may remain in the UPS.
The following precautions should be observed when working on batteries:
• Remove watches, rings, or other metal objects.
• Use tools with insulated handles.
• Do not lay tools or metal parts on top of batteries.
• Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance.
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
31
Appendix A 1609 UPS Dimensions
32
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products.
At http://www.rockwellautomation.com/support , you can find technical manuals, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. You can also visit our Knowledgebase at http://www.rockwellautomation.com/knowledgebase for FAQs, technical information, support chat and forums, software updates, and to sign up for product notification updates.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer
TechConnect SM support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/ .
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or Canada Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html
, or contact your local Rockwell
Automation representative.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States
Outside United States
Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process.
Please contact your local Rockwell Automation representative for the return procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002 , available at http://www.rockwellautomation.com/literature/ .
Publication 1609-UM009A-EN-P - January 2013
Copyright © 2013 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 2 Important User Information
- 3 Preface
- 3 Additional Resources
- 4 Notes:
- 5 Table of Contents
- 5 Bul. 1609-D Installation Instructions
- 5 Bul. 1609-B Installation Instructions
- 5 Bul. 1609-EXBAT Installation Instructions
- 5 General Information 1609-D and 1609-B
- 5 Troubleshooting
- 6 Troubleshooting (continued)
- 6 Specifications
- 6 Dimensions
- 6 Service Instructions
- 7 -Bulletin 1609-D Installation Instructions
- 7 Battery Wiring and Installation
- 7 1. To access the battery compartment remove the three screws and the battery door.
- 7 2. Remove the battery container, jumpers, and wire harness from the battery compartment. Place the battery container and batteries onto a flat surface. Use the provided jumper wires to connect the batteries in series. Connect the positive terminal (r...
- 7 3. Connect the red wire of the harness to the positive terminal (top red) and the black wire of the harness to the negative terminal (bottom black). See photo below for details.
- 8 Battery Wiring and Installation (cont.)
- 8 4. Fold the battery container and seal it with tape.
- 8 5. To connect the batteries to the UPS, insert the batteries into the battery compartment, open the white connector retainer and connect the two cables together as shown in the photo below.
- 8 6. To complete the battery installation, close the white connector retainer and reattach the battery door with the three screws (torque of 8.7+/-1.7 lb-in).
- 8 Mount the UPS
- 8 Figure 1 - Mounting the UPS
- 9 Hardwire UPS
- 9 Selection of Cables
- 9 Table 1 - AC Main Input/Output Wiring for UPS:
- 9 Table 2 - DC Input / Output Wiring for External Battery Cabinet:
- 10 Connect Power and Equipment to the UPS
- 10 1. Connect the appropriate input power to the UPS's input (Line, Neutral and Ground) terminals (see Figure 2).
- 10 2. Connect the specified equipment to the UPS's output (Line, Neutral and Ground) terminals (see Figure 2).
- 10 Figure 2 - System Wiring
- 10 3. Connect any additional optional accessories (1609-ENET card).
- 10 1609-D Block Figure
- 11 1609-B Installation Instructions
- 11 Battery Wiring and Installation
- 11 1. To access the battery compartment remove the three screws and the battery door.
- 11 2. Remove the battery container, jumpers, and wire harness from the battery compartment. Place the battery container and batteries onto a flat surface. Use the provided jumper wires to connect the batteries in series. Connect the positive terminal (r...
- 11 3. Fold the battery container and seal it with tape.
- 12 Battery Wiring and Installation (cont.)
- 12 4. To connect the batteries to the UPS, insert the batteries into the battery compartment, open the white connector retainer and connect the two cables together as shown in the photo below.
- 12 5. To complete the battery installation, close the white connector retainer and reattach the battery door with the three screws (torque of 8.7+/-1.7 lb-in).
- 13 Mount the UPS
- 13 Figure 3 - Standard DIN-Rail Mount
- 13 Figure 4 - Optional Panel or Floor Mount
- 13 Hardwire UPS
- 13 Selection of Cables
- 13 Table 3 - AC Main Input / Output Wiring for UPS
- 14 Connect Power and Equipment to the UPS
- 14 1. Connect the appropriate input power to the UPS's input (Line, Neutral and Ground) terminals (see Figure 5).
- 14 2. Connect the specified equipment to the UPS's output (Line, Neutral and Ground) terminals (see Figure 5).
- 14 Figure 5 - System Wiring
- 14 1609-B Block Figure
- 15 1609-EXBAT Installation Instructions
- 15 Battery Wiring and Installation
- 15 1. To access the battery compartment remove the six screws and the battery door.
- 15 2. Remove the battery container, jumpers and wire harness from the battery compartment. Place the battery container and batteries onto a flat surface. Use the provided jumper wires to connect the batteries in series. Connect the positive terminal (re...
- 16 Battery Wiring and Installation (cont.)
- 16 3. Connect the shorter set of red and black wires of the harness to the top terminals (red - to - red and black - to - black). Connect the longer set of red and black wires of the harness to the bottom terminals (red - to - red and black - to - black...
- 16 4. Fold the battery container and seal it with tape.
- 16 5. Insert the batteries into the battery compartment in the orientation as shown in the photo below.
- 16 6. Open the white connector retainer and connect the two cables together as shown in the photo below.
- 17 Battery Wiring and Installation (cont.)
- 17 7. To complete the battery installation, insert the surplus wire harness into the free space, close the white connector retainer and reattach the battery door with the six screws (torque of 8.7+/-1.7 lb-in).
- 17 Mount the 1609-EXBAT
- 17 Figure 6 - Heavy Duty DIN Rail Mount
- 17 Figure 7 - Panel or Floor Mount
- 18 Selection of Cables
- 18 Table 4 - DC Input/Output Wiring for External Battery Cabinet
- 18 Connect 1609-EXBAT to the UPS
- 18 Figure 8 - System Wiring
- 19 General Information 1609-D and 1609-B UPS Units
- 19 Recommended Battery for Use with the UPS and 1609-EXBAT
- 19 Dry I/O Contacts
- 19 USB Communication Port
- 20 Manual or Remote Enable/Disable of UPS Output Selection
- 20 Manual Enable/Disable/ Self-test
- 20 Remote Enable/Disable
- 21 Display LED Indicators
- 22 Troubleshooting
- 23 UPS LED Fault Indicators
- 25 Bulletin 1609 UPS Management Software Troubleshooting
- 26 Bulletin 1609 Network Management Card Troubleshooting
- 27 Bul. 1609-D Specifications
- 28 Bul. 1609-B Specifications
- 29 Appendix A
- 29 1609 UPS Dimensions
- 29 1609-D UPS Dimensions
- 29 1609-B UPS Dimensions
- 29 1609-EXBAT Unit Dimensions
- 30 1609-BRK Dimensions (1609-D orientation)
- 30 1609-BRK Dimensions (1609-B orientation)
- 31 Service Instructions
- 31 1. Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
- 31 2. When replacing batteries, replace with the same number of the 1609 battery packs supplied by Rockwell Automation.
- 31 3. Review the problems discussed in the Troubleshooting section of this manual to eliminate common problems.
- 31 4. If the problem persists, contact Rockwell Automation Customer Support at 440-646-5800.
- 31 5. Pack the UPS in its original packaging.