ASI Doors 135 Owner's Manual
Advertisement
Advertisement
OWNER’S MANUAL
Single and Paired Swing Doors
MODELS 120/125, 130/135, 220/225, 230/235
MANUAL PART #: 17A144
GENERAL INFORMATION
. . . . . . . . . . . . . . . . . . . . . . . 3-6
Safety Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Warranty Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Crates and Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
INSTALLATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-16
Storage at Building Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Door Frame Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Power Operator Reinforcement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Slip-On Frame Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Welded/Knockdown Frame Install . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Door Hardware and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Door Hardware: Wall Anchors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Door Hardware: Gasketing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Door Hardware: MagLock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Door Hardware: Manual Closers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Power Operator Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Operator Handing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
ELECTRICAL CONTROLS
. . . . . . . . . . . . . . . . . . . . . . 19-40
Safety Warnings & Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Electrical Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Modes of Door Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Programming with the FCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Teach-In Process, Single Swing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Teach-In Process, Paired Swing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Programming Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Troubleshooting Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Control Connections, Single . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Control Connections, Paired Primary . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Control Connections, Paired Secondary . . . . . . . . . . . . . . . . . . . . . . . . . 37
Electric Schematic, Single . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Electric Schematic, Paired Primary . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Electric Schematic, Paired Secondary . . . . . . . . . . . . . . . . . . . . . . . . . . 40
REPLACEMENT PARTS
. . . . . . . . . . . . . . . . . . . . . . . 41-46
Instructions for Ordering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Door Assembly, Single . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Door Assembly, Paired . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Door Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Operator and Shroud . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
2
Manual last updated on: November 7, 2022 3:08 PM
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Safety Practices
This is a safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION used without a safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage.
NOTE
NOTE explains general information.
3
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Warning read these safety practices before installing, operating or servicing the SLIDING door. Failure to follow these safety practices could result in property damage, death or serious injury.
READ AND UNDERSTAND ALL WARNING LABELS AND OPERATING INSTRUCTIONS IN THIS
MANUAL BEFORE OPERATING THE SLIDING DOOR. If you do not understand the instructions, ask your supervisor to teach you how to use the SLIDING door.
Safety Practices
(cont’d)
1. Do not operate the door while under the influence of drugs or alcohol.
2. Do not use the door if it looks broken or does not seem to work properly. Advise your supervisor at once.
3. Stay clear of the door when it is moving
4. Keep hands, feet and head clear of the door at all times.
5. Do not operate the door with equipment, material or people directly inside door opening.
6. Disconnect power before performing any electrical or mechanical service, cleaning or other maintenance on the door. OSHA requires disconnect to be properly tagged and locked out during all maintenance or service of equipment. With the power supply disconnected, always verify using a volt meter.
7. All electrical troubleshooting or service must be completed by a qualified electrician or service person and must meet all applicable local, state, federal, international and other governing agency codes.
8. When it is necessary to service the control box with power on, USE EXTREME CAUTION. Do not place fingers or uninsulated tools inside the control box. Touching wires or other parts inside the enclosure may cause electrical shock, serious injury or death.
9. It is your responsibility to keep all warning labels and instructional literature legible, intact and kept with the door. Replacement labels and literature are available from ASI Doors, Inc. or its representatives.
10. If you have any questions, contact your supervisor or your local ASI Doors, Inc. representative for assistance.
11. Train all service and personnel using or near door on intended use(s) and operation of the door.
12. Failure to operate the door as intended, as described, or heed any warning may result in equipment damage, property damage, serious bodily injury or death.
4
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Warranty Policy
ASI Doors (herein called “ASI”) warrants solely for the benefit of its customer that each door system manufactured by ASI (each a “Door System”) will be free from defects in material and manufacture for a period of one (1) year from the date of original shipment by ASI. The following models receive a similar two (2) years from date of shipment warranty: 109, 209, 120-125, 1240-125-, 1240SS-1250SS, 1260-1270,
1260SS-1270SS, 130-135, 140-150, 160-170, 220-225, 220SS-225SS, 230-235, 230SS-235SS. In all instances warranty labor is covered for a period of one (1) year from the date of original shipment.
The foregoing limited warranty shall not apply to defects that result from improper installation, abuse, misuse, alteration, modification, or failure to maintain the Door System in accordance with the ASI
Owner’s Manual. Periodic maintenance and adjustment of the Door System as described in the ASI
Owner’s Manual are the sole responsibility of the customer. All claims for defects must be made to
ASI within thirty (30) days aft er the defect is discovered or should, with reasonable care, have been discovered. THE FOREGOING LIMITED WARRANTY CONSTITUTES THE EXCLUSIVE WARRANTY OF ASI
WITH RESPECT TO THE DOOR SYSTEM. ASI EXPRESSLY DISCLAIMS ALL OTHER GUARANTEES OR
WARRANTIES—WHETHER EXPRESSED, IMPLIED, OR STATUTORY, INCLUDING BUT NOT LIMITED TO
ANY IMPLIED WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
If a Door System does not comply with the foregoing limited warranty, and a claim is made by customer within the warranty period, ASI will, at the option of ASI, either repair or replace any defective equipment or parts free of charge and pay the reasonable labor costs to repair or replace the defective equipment or parts if within the defined warranty period. The remedy of repair or replacement shall be the exclusive and sole remedy for any breach of the foregoing limited warranty.
ASI SHALL NOT IN ANY EVENT BE LIABLE FOR ANY INCIDENTAL, INDIRECT, SPECIAL, EXEMPLARY OR
CONSEQUENTIAL DAMAGES OF ANY KIND, INCLUDING WITHOUT LIMITATION ANY LOST PROFITS,
ARISING FROM THE SALE OR USE OF THE DOOR SYSTEM, OR FROM ANY OTHER CAUSE WHATSOEVER,
WHETHER THE CLAIM GIVING RISE TO SUCH DAMAGES IS BASED UPON BREACH OF WARRANTY
(EXPRESSED OR IMPLIED) BREACH OF CONTRACT, TORT, STRICT LIABILITY OR ANY OTHER THEORY
OF LIABILITY, EVEN IF A PARTY HAS BEEN ADVISED OF THE POSSIBILITY THEREOF, AND REGARDLESS
OF ANY ADVISE OR REPRESENTATION THAT MAY HAVE BEEN RENDERED BY ASI CONCERNING THE
SALE OR USE OF THE DOOR SYSTEM.
At ASI’s request, customer shall return to ASI for inspection any Door System for which a warranty claim has been made, F.O.B. ASI’s facility with freight prepaid. The customer is responsible for any removal costs.
The customer shall comply with the following procedures in filing a warranty claim with ASI:
1. Notify ASI of any and all defects in writing with photographic evidence. ASI will review the warranty request and issue a Returns Merchandise Authorization (RMA) form if the defective parts need to be returned to ASI for inspection and verification. The RMA form must accompany any materials returned for warranty consideration.
2. All replacement parts or equipment will be invoiced to the customer. Upon verification by ASI that the
Door System is defective, ASI will issue a full credit to customer for the replacement parts or equipment.
3. If outside labor is needed to install the replacement parts or equipment, ASI requires a written estimate of the labor charges in advance so ASI may approve the labor charges and issue a purchase order. ASI will not accept any labor charges unless previously approved in writing and accompanied by the ASI purchase order number.
(Rev 12/21)
5
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Crates and Contents
Single Swing Paired Swing
Upon receipt of the shipment, check that you have received the correct number of pieces as shown in (Figure 1).
Crate one will contain the door panel(s). Crate two will contain the frame, operator and loose parts. For your protection, note any damages or shortages on the carrier’s bill of lading before signing the bill for receipt.
The installation of this door will require at least a two man crew and a fork lift . Select a fork lift with lift ing height based upon the height of the door plus a minimum additional two feet.
NOTE
NOTE DO NOT remove door sections from crate until you encounter the step in which they are to be installed.
NOTE Unless specifically called out as “Provided by ASI”, installer is to provide all necessary mounting hardware, anchors, inserts, hangers, supports and equipment needed to install door in accordance with final shop drawings and manufacturer’s instructions.
6
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Storage at Building Site
1. Frames shall be stored under cover on the Building site on 4” wood sills or on floors in a manner that will prevent rust and damage. Avoid the use of non-vented plastic or canvas shelters which create a humidity chamber (Figure 2).
2. Assembled frames shall be stored in a vertical positions, five units maximum in a stack. Provide a 1/4” space between frames to promote air circulation (Figure 3).
3. Doors shall be stored in an upright position at the building site, under cover. Place the units on at least 4” wood sills or on floors in a manner that will prevent rust and damage. Avoid the use of non-vented plastic or canvas shelters which create a humidity chamber. Provide a 1/4” space between frames to promote air circulation.
STORE UNDER COVER
(AVOID CREATING A HUMIDITY
CHAMBER BY NOT VENTING)
1 /
4
" SPACERS
4" WOOD SILL
STORE UNDER COVER,
STACK VERTICALLY
5 UNITS MAXIMUM
1 /
4
" SPACERS
4" WOOD SILL
Figure 2: Storage of Knocked Down Frames
Door Frame Measurements
Figure 3: Storage of Assembled Frames
1. The detailed description of frame installation techniques that follow speak of plumbing, squaring and aligning the frame. The details in Figure 4 indicate the maximum allowable tolerance in this area.
SQUARENESS ALIGNMENT
1 / " 1 / "
1 / "
HINGE
JAMB
STRIKE
JAMB
M AXIM UM / " ALL
1 / "
HINGE
JAMB
PLUM BNESS
HEAD LEVEL HEAD LEVEL
STRIKE
JAMB
1 / "
TWIST
1 / "
7
HINGE OR
STRIKE
JAMB
BOTTOM
ASI DOORS, INC.
(800) 558-7068
HINGE OR
STRIKE
JAMB
BOTTOM Figure 4: Installation Tolerances asidoors.com
Power Operator Reinforcement
For Swing Doors with Power Operator Option
1. When using a power door operator, the wall must have adequate reinforcement to support the operator(s).
For stud walls, 7 gage plate steel 8” high, starting at rough opening and extending 1 stud past each side of frame is the minimum requirement. For masonry walls, fastening the operator directly to the wall is suff icient.
Slip-On Frame Installation
1. Size Opening (Figure 5) DW-Series frames are designed for installation aft er the studs and drywall are completed. Install double steel studs at all jambs. See Figure 10 for recommended practice at head and jamb stud intersections. It is important to ensure that the rough stud opening for double rabbet profiles is sized as follows: a. Rough Stud Opening Width
RSOW = Door width + 1 1 /
2
” (+ 1 /
4
/ –0) b. Rough Stud Opening Height
RSOH = Door height + 3 /
4
” (+ 1 /
4
/ –0)
2. Install Head (Figure 6) a. For fire rated pairs only, install snap-in anchors in each face at the center line of the head. See
Figures 7, 8 & 9 for installation of anchors.
b. Slide head into position in center of rough stud
opening (wedges may be used to temporarily
hold head in position).
RS
OH
RS
OW
Figure 5: Size Opening Figure 6: Install Head
RETR
ANCHOR
Figure 8: Drywall Tension Anchor
3 /
4
" at HJ and HD 1 1 / "
1 1 /
8
" at S
5 /
8
" 5 /
8
"
Figure 7: Anchorage at Base of Frame
TIGHTEN SCREW
UPPER HEAD RUNNER
AND SCREW FIXED
Figure 9: Snap-In Anchor
Figure 10: Head and Jamb Stud Intersections
8
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Slip-On Frame Installation
Continued
3. Install Hinge Jamb (Figure 11) a. Retract tension anchor at top of jamb by turning screw clockwise.
b. Insert the integral soff it tab on the jamb slot in the head. Pivot jamb into place over the wall.
c. Insert screws into top corners of the head. Do not fully tighten at this time.
4. Install Strike (or 2nd hinge) Jamb (Figure 12) a. For fire rated singles only, install snap-in anchor in each face of strike jamb immediately above strike reinforcing.
b. Repeat Steps 3a through 3c.
5. Anchor Frame (Figure 13) a. Place a temporary wooden spreader between jambs at the floor to ensure the correct frame rabbet width at the base of the frame. The spreader must be square, at least 1” thick, almost Figure 11: Install Hinge Jamb as wide as the frame jamb depth with clearance notches for the frame stops.
b. Shim the bottom of the jambs to the same elevation so head will be level.
c. Secure the bottom of the frame through the dimpled holes at the base of each jamb with standard drywall screws into the stud sill plate/ runner. (Both jamb rabbets must be parallel)
6. Set Frame (Figure 14) a. Plumb and square-up frame by adjusting tension anchors at the top of each jamb ensuring that anchors press tightly against studs.
b. On fire rated frames, secure snap-in anchors at strike jamb or head to studs with 2 standard drywall screws per anchor.
c. Tighten screws at corners of the head.
d. Remove temporary wooden spreader.
Figure 12: Install Strike Jamb
Figure 13: Anchor Frame
Figure 14: Set Frame
9
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Welded or Knocked-Down Frame Installation
NOTE
Note for knock-down frames, start at step 1.
For welded frames, start at step 2.
1. Assemble Frame (Figure 15) a. Insert jamb corner clip tabs into 2 slots at each end of head. Insert screws into frame at 2 corners at each end of head.
b. Ensure that face miters on jambs and head are tight and corners are square.
c. Bend the tabs at each head rabbet slot downwards away from door opening and tighten 2 screws at each corner of head.
2. Remove Temporary Spreaders (Figure 16) a. Welded frames are provided with temporary steel spreaders to maintain alignment and minimize other damage during shipping and handling. They are not intended to be used during installation and must be removed.
Figure 15: Assemble Frame
NOTE
Note for new unit masonry or steel stud partitions, proceed to step 3. For existing unit masonry or poured concrete walls proceed to step 7.
Figure 16: Remove Temporary Spreaders
3. Place and Anchor to Floor (Figure 17) a. Stand frame in position.
b. Place a wooden spreader between the jambs at the floor. The spreader must be square, at least 1” thick, almost as wide as the frame jamb depth with clearance notches for the frame stops.
c. Level the frame head, placing shims under the jamb base anchors as necessary.
d. Adjust frame for alignment and twist. Rabbets must be parallel.
e. Fasten jambs to the floor through the floor anchors.
Spreaders
Figure 17: Place and Anchor to Floor
10
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Welded or Knocked-Down Frame Installation
Continued
4. Set Frame (Figure 18) a. Brace frame as shown. Do not brace in the direction of the adjacent wall.
b. Install a second wooden spreader at the mid height of the frame to maintain correct frame rabbet width and to prevent bowing of the jambs.
5. New Unit Masonry Wall Anchorage (Figure 19) a. As wall is laid up, embed wire, T-stop or masonry fire anchors in mortar coursing immediately above or below hinges and directly opposite on strike jamb.
b. Although not mandatory, even for fire rated frames, grouting of the jambs is recommended in all units to endure a more secure and stable installation.
6. Steel Stud Partition Anchorage (Figure 20) a. Where loose combination stud anchors are provided, install in frame throat opening.
b. Remove or bend legs of combination stud anchors back inside frame profile.
c. Place and secure fl oor and ceiling
steel runners.
d. Place, plumb and secure first vertical steel stud inside floor and ceiling runners with stud fitting snug against wall anchors in each jamb. Open webs of studs should be facing away from the frame.
standard
2
” long pan head sheet metal screws, secure studs to each anchor.
f. Check plumb and square of frame, alignment and twist of jambs.
g. Place and secure a second vertical steel stud inside floor and ceiling runners with stud returns abutting the first steel stud returns.
h. Install and secure steel lintel runners at head of frame.
SECOND
WOODEN
SPREADER
2" × 4"
SUPPORTS
Figure 18: Set Frame
T-STRAP OR
MASONRY ANCHOR
2" × 4"
BRACES
GROUTING
THE JAMB
Figure 19: New Unit Masonry Wall Anchorage
ANCHOR
FIRST HHRTICAH
STUDS
SHHHT MHTAH
SCRHWS
SHHHT MHTAH
SCRHWS
SHCOND HHRTICAH
STUDS
2 PIHCH COMBINATION
STUD ANCHOR (CSA) SHOWN
(1 PIHCH CSA SIMIHAR)
HH” THPH
STUD ANCHOR
Figure 20: Steel Stud Partition Anchorage
11
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Door Hardware and Accessories
7. Existing Masonry or Poured Concrete Wall Anchorage
(Figure 21) a. Set the assembled frame centered in the completed opening.
b. Place wooden spreaders between the jambs at the floor and at mid height of the frame.
c. Level the head by placing shims under the jambs as necessary.
d. Adjust the frame for plumb, square, alignment and twist. Rabbets must be parallel.
e. Mark the wall through the dimpled holes in the jamb soff its to locate the anchor points.
f. Drill the wall for appropriate holes at the marks.
g. Install sleeve or expansion shell anchors in the wall holes.
h. Insert anchor bolts through the dimpled holes into the wall sleeve anchors.
i. Place shims snugly between the frame and the wall, above each anchor bolt.
j. Tighten bolts, checking plumb, square, alignment and twist.
a. The door is shipped with all hinges mounted on door frame.
b. Match door panel with correct frame.
c. Line door hinges up with frame cutouts and secure hinges with supplied fasteners.
2. Sweep Gasket: (Figure 23) a. Position sweep gasket at the door bottom of desired side such that gasket will just touch the floor through full range of door travel. Positioning gasket too close to floor will wear gasket out prematurely.
b. Trim length as needed.
c. Mark holes on panel and secure with supplied #6-32 screws.
HIHHES
EXPANSION
ANCHOR
SHIM
Figure 21: Existing Masonry or
Poured Concrete Wall Anchorage
Figure 22: Panel Installation
FRAME
CHTHHTS
Figure 23: Sweep Gasket Installation
12
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Door Hardware and Accessories
Continued
3. Frame Gasket: (Figure 25) a. Remove adhesive backing and adhere gasket to frame.
4. Astragal Gasket: (Figure 24 a. Position gaskets on pull side of panel such that the (2) gaskets just touch in the center of the gap between the panels, the full height of the panels.
b. Trim as needed.
c. Mark holes on panel and secure with supplied #6-32 screws.
-
13
SCREWS
ASTRAGAL
GASKET
Figure 24: Astragal Gasket Installation
ASI DOORS, INC.
(800) 558-7068
Figure 25: Frame Gasket Installation asidoors.com
Door Hardware and Accessories
Continued
MagLock
Figure 26 shows detail of MagLock installation. Refer to the manufactures instructions and mounting templates supplied with MagLock when mounting to door and frame.
Figure 26: MagLock Installation
NOTE
Note do not thru-bolt Maglock hardware.
Manual Door Closers
The following figures show 3 types of closers available:
• Regular pull side mount
• Parallel arm push side mount
• Top jamb push side mount
Refer to the manufactureres instruction and mounting templates supplied with closer when mounting these closers.
NOTE
Note do not thru-bolt any door closer hardware
14
Figure 27: Regular Pull Side Closer
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Door Hardware and Accessories
Continued
Figure 28: Parallel Arm Push Side Closer
Figure 29: Top Jamb Push Side Closer
Power Operator Installation
1. Remove material from packages and check contents:
Remove all contents from the crate. Check all items to ensure you have the material you need before beginning the actual installation.
2. Remove access panel from header housing assembly:
Carefully remove the header housing assembly from the crate. Using a Phillips screwdriver, remove the two
access panel retaining screws.
Remove all decals, paperwork and parts bag from inside header and set to one side.
Determine door handing and match with corresponding operator.....
5. Operator:
• Determine swing type and arm type.
• Position operator per figures #31-34.
• Secure operator to wall with appropriate fasteners.
• If required, fill gap between finished wall and operator with shim material.
(Note position of door arm shoe on door panel before proceeding with next step)
• Position and secure arms / tracks to door panel.
CAUTION do not tighten arm shaft to operator until told to do so during start-up/programming!
15
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Power Operator Installation
Continued
Operator Handing
Left Hand (LH) Inswing
Inswing Track
90° Max
Inswing Arm
90° Max
Right Hand (RH) Inswing
Exterior
Left Hand (LH) Outswing
Right Hand (LH) Outswing
90° Max 90° Max
Arm Mounting
Bracket
Exterior
Outswing Arm
Figure 30: Operator Handing Options
Consult end user and follow provided installation instructions and templates for desired mounting style.
16
Figure 31: 1301 Outswing Operator, W/Aluminum Arm
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Power Operator Installation
Continued
Figure 32: 1301 Inswing Operator, W/Aluminum Arm
17
ASI DOORS, INC.
(800) 558-7068
Figure 33: 1301 Outswing Operator, W/SS Arm asidoors.com
Power Operator Installation
Continued
Figure 34: 1301 Inswing Operator, W/SS Arm
18
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Electrical Controls
Continued
Safety/Warning Symbols
NOTE indicates important information specific to the process or steps being performed.
ELECTRICAL VOLTAGE indicates that electrical voltage is present and that caution should be taken to prevent injury or property damage.
CAUTION indicates failure to follow instructions may result in personal injury and/ or property damage.
OPTIONAL COMPONENTS indicates components that are not installed in all systems.
WARNING failure to observe the information in this manual may result in personal Injury or damage to equipment. To reduce the risk of injury of persons use this operator only with pedestrian swing doors. Save these instructions for future reference.
Installation and Service
Any and all equipment must be installed, serviced and inspected by an AAADM Certified technician, to meet the current ANSI A156.10 and/ or ANSI A156.19 standard and any local or state building codes.
The person responsible for the daily operation and maintenance of the system is referred to as “End-User”.
It is the technicians responsibility to:
1. Review the functions of the equipment with the end-user. Failure to do so, may lead to the improper use, could cause injury to persons and/ or damage to the equipment.
2. Familiarize the end-user with the Daily Safety Check Decal and how to perform the walk test procedures.
3. Illustrate to the end-user how to place the door out of service (turn off power or place in P mode or OFF mode of operation), if the equipment does not perform as described in the Daily Safety Check Decal.
4. Recommend to the end-user to have their equipment inspected annually by an AAADM certified technician.
ANSI/ BHMA A156.10, A156.19 standards - Knowing Act Switch
Doors activated by a manual switch must have the switch installed in a location from which the operation of the door can be observed by the person operating the switch. Refer to the latest revision of ANSI/ BHMA A156.10 or
A156.19 for location of Knowing Act switch and time delays.
Electrical Requirements for Installation Personnel
Have a licensed electrician:
Make all mains primary power connections in accordance to federal, state and local regulations. Route mains primary power from power distribution panel (10 amp circuit breaker minimum per operator) to the operator. Install a service switch or emergency shut OFF switch, if required by customer or per regulations.
This is in addition to the mains circuit breaker to interrupt power, switch must be rated @ 10 amp minimum.
Mains Connection
Connection: N + L1 + PE protected on site with 10 AT, protective earth necessary
Power rating: 1 x 230 / 1 x 115 V AC (+5 %/ – 10 %) 50– 60 Hz, max. 250 W
Supply cable: Type H05VV-F, H05RR-F or flexible cord of type S, SO, SJ, SJO, ST, STO, SJT, SJTO or AFS
19
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Electrical Controls
Continued
Before beginning the work described below, check that the mains primary power is switched off . If required place “Out of Service” tag on circuit breaker or service switch.
• Route the mains connection to the operator along the side of the power supply.
• The edges must be rounded off on all bushings for the mains connection.
• Loosen power supply bar (3) and pull out power supply.
• Route mains cable either through the header end cap or through header back plate.
• Use only cable bushings made from synthetic materials. Metallic bushings must be grounded.
• Connect mains cable to terminal (1) as shown in the illustration.
• Check the correct setting of the voltage selector switch (2). Re-insert power supply and tighten screw.
• Secure mains cable with a cable strap at a synthetic lug on the base plate.
• Do not apply power to the door until ready for commissioning.
• A system switch (FCP or 3-position switch) must be on site.
Figure 35: Main Power Connection
Make sure that the mains cable is secured properly to prevent it from getting into the moving parts of the operator or door system.
The commissioning of the system may only take place through a qualified person and under consideration of the required documents for commissioning and examination!
Modes of Door Operation
Modes of operation can be selected with the 6 position Functional Control Panel (FCP). The technician will review the appropriate mode switch with the end-user.
1) OFF Mode
2) AUTOMATIC Mode
3) REDUCED OPEN Mode
4) EXIT Mode
5) HOLD OPEN Mode
KEY 1
Electric Door Lock LED Indicator
KEY 2 Figure 36: Functional
Control Panel (FCP)
LED Indicates Current
Operating Mode
#6 (P) MANUAL Mode
20
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Electrical Controls
Continued
1. OFF - The interior and exterior activators are inhibited aft er the door reached the fully closed position, if an electric lock is present it will be activated. Door will cycle open, if a signal is sent to the key switch input.
2. AUTOMATIC - Typical setting for normal 2-way traff ic operation with interior and exterior activators, key switch input and safety devices operating the door.
3. REDUCED OPERATING - Allows the door to open with a reduced opening width. Activators and safety devices operate the same as automatic mode.
4. EXIT - (1-way traff ic) Allows interior activator and key switch inputs to operate the door. The exterior activator input is inhibited from opening the door while the door is closed. When the door is opened/ closing the exterior activator becomes operational and will re-open a closing door.
5. HOLD OPEN - Hold and maintains the door in the open position.
6. (P) MANUAL OPERATION - Allows the door to be used manually without the use of sensors. Push and pull motion applied to the door to open and close the door.
1) OFF Mode
2) AUTOMATIC Mode
3) REDUCED OPEN Mode
4) EXIT Mode
5) HOLD OPEN Mode
Figure 37: Operation of FCP Control Panel
Key (1) increase value of code (0 - 9)
OR
Selects programming mode
Electric Lock Out-put Indicator
Mode P
Manual Operation
Key (2) confirm code digit OR
Selects programming mode
21
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Electrical Controls
Continued
Button 1 - The value of the number / letter is increased by one (0 - 9,a,b,c,...back to 0) Button 2 - Displayed character is confirmed / sent to control
1) Start Access Code
Indication of Operating Mode
Letter "C" is shown (= Code)
Press Button 1 and 2 simultaneously until “C” appears
Press Button 2 to
Confirm "0" Will
Display
2) Entering Access Code 111
A. Select the number “1” with button 1, confirm with button 2.
B. Repeat this step two more times entering the code 1-1-1.
Note: Access code “C111” is not required upon initial power-up.
Zero appears, ready for code entry
Select first digit with button 1
Confirm digit with button 2
3) Start Programming Level
A. Press button 1 and 2 simultaneously until “P” appears.
B. Confirm with button 2.
"P" is shown, ready for programming
Confirm with button 2
3) Entering Parameter Code
A. Select the number “1” with button 1, confirm with button 2.
B. Select and confirm the 2nd and 3rd code digits using the same sequence shown in step 2.
Note: Aft er confirming the 2nd number, the 3rd number will be blinking, indicating the setting of the function.
Zero appears, ready for code entry
Select the first code digit with button 1
Confirm digit with button 2
Figure 38: Entering codes on the FCP Control Panel
Time out occurs if no input is made during 10 seconds, the FCP reverts back to displaying “P”, and then displays the operating mode.
22
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Electrical Controls
Continued
Programming with the FCP
Example 1: Enter access code 111
Example 2: Enter access code 103 to adjust the hold open time for 2 seconds
Within 10 minutes you can enter the programming mode by pressing both keys simultaneously and P will display. If no further adjustments are made aft er 10 minutes the FCP will time out and require access code re-entry. Repeat example 1.
Aft er the 2nd code digit has been confirmed, the flashing digit show set value of the parameter
(= 3rd digit of the parameter code). If the value is confirmed the FCP will rapidly flash for 1 second then display “P” again.
Quickly pressing and releasing both buttons simultaneously the FCP will return to displaying the mode of operation.
23
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Electrical Controls
Continued
Customer/Installer Start Up Procedure
Operator set up
(If unfamiliar with key pad programming, please review “programming with FCP page” below)
1. Enter door weight per installation manual
For 27-36 inch wide door panels enter the code P072
For 37-42 inch wide door panels enter the code P073
For 43-48 inch wide door panels enter the code P074
2a. Pre-load arm for Out-Swing doors
Enter code P092 then select hold open mode (white circle on key pad). NOTE, motor will rotate 20 degrees then stop.
Place the arm to the configuration illustrated, while the door is in the full closed position. Tighten the shaft
6mm bolt to 25 ft . lbs. Enter code P090 to terminate the preload procedure.
OR
2b. Pre-load arms for in-swings arms
Enter code P091 then select hold open mode (white circle on key pad). NOTE, motor will rotate 20 degrees
Place the arm to the configuration illustrated, while the door is in the full closed position. Tighten the shaft
6mm bolt to 25 ft . lbs. Enter code P090 to terminate the preload procedure.
3. Begin Automatic Configuration
Enter code P021. Change the operating mode on FCP to park (Letter "P") mode.
24
ASI DOORS, INC.
(800) 558-7068
Figure 39: FCP “Park” Mode asidoors.com
Electrical Controls
Continued
Teach-In Process, Single Swing
1. Door stop adjustment a. Adjust the internal door stop as shown in Figure x to achieve 90 door angle. The door arm should not pass
beyond 90.
Figure 40: Set Door stop (90° Maximum) b. Change the operating mode on FCP to Automatic (solid green circle on keypad) as shown below.
Figure 41: FCP “Automatic” Mode c. Momentarily press and release SW2 switch on the control see figure 42. The first cycle will be slow as the door
will look for a positive full open door stop. Continue to activate the door with the SW2 button until an audible
tone and the learning code (H66) is no longer displayed on FCP. Learning procedure lasts between 5-14 cycles.
25
ASI DOORS, INC.
(800) 558-7068
Figure 42: “SW2” switch on Control asidoors.com
Electrical Controls
Continued
Primary / Secondary Function
The purpose of this wiring is to synchronize a pair of 1301 or 1302 operators. The door leaves open at the same time when an activation signal is given (interior & exterior sensors or key switch) or by push- pull on the primary. If the door leaves overlap, the secondary drive (Overlapped leaf) should have a delay (See programming table).
• The hold open time of both the operators is determined by the primary.
• The mode of operation is selected by the FCP connected to the primary.
• The opening and closing speeds are adjusted individually to prevent interference between doors with an astragal (overlap).
• During the loss of primary power, closing speeds are controlled by the spring.
ASI Doors, customer/installer start up procedure.
Primary Operator set up
(If unfamiliar with key pad programming, please review “programming with FCP page” below)
Note: Insert FCP Keypad cable into primary operator port.
1. Enter Door Weight per installation manual a. For 27-36 inch wide door panels enter the code P072 b. For 37-42 inch wide door panels enter the code P073 c. For 43-48 inch wide door panels enter the code P074
2a. Pre-load arm for Out-Swing doors a. Enter Code P092 then select Hold Open mode (white circle on key pad). NOTE, motor will rotate 20 degrees then stop.
b. Place the arm to the configuration illustrated, while the door is in the full closed position.
c. Tighten the shaft 6mm bolt to 25 ft . lbs.
d. Enter Code P090 to terminate the Preload procedure.
OR
2b.Pre-load arms for In-Swing arms a. Enter Code P091 then select Hold Open mode (white circle on key pad). NOTE, motor will rotate 20 degrees then
stop.
b. Place the arm to the configuration illustrated, while the door is in the full closed position.
c. Tighten the shaft 6mm bolt to 25 ft . lbs.
d. Enter Code P090 to terminate the Preload procedure.
3. Begin Automatic Configuration a. Enter Code P021 b. Change the operating mode on FCP to Park (Letter “P”) mode.
26
ASI DOORS, INC.
(800) 558-7068
Figure 43: FCP “Park” Mode asidoors.com
Electrical Controls
Continued
Secondary Operator Set Up
Note: Insert FCP Keypad cable into secondary operator port.
1. Enter Door Weight per installation manual a. For 27-36 inch wide door panels enter the code P072 b. For 37-42 inch wide door panels enter the code P073 c. For 43-48 inch wide door panels enter the code P074
2a. Pre-load arm for Out-Swing doors a. Enter Code P092 then select Hold Open mode (white circle on key pad). NOTE, motor will rotate 20 degrees
then stop.
b. Place the arm to the configuration illustrated, while the door is in the full closed position.
c. Tighten the shaft 6mm bolt to 25 ft . lbs.
d. Enter Code P090 to terminate the Preload procedure.
OR
2b. Pre-load arms for In-Swing arms a. Enter Code P091 then select Hold Open mode (white circle on key pad). NOTE, motor will rotate 20 degrees
then stop. b. Place the arm to the configuration illustrated, while the door is in the full closed position.
c. Tighten the shaft 6mm bolt to 25 ft . lbs.
d. Enter Code P090 to terminate the Preload procedure.
3. Begin Automatic Configuration a. Enter Code P021 b. Change the operating mode on FCP to Park (Letter “P”) mode.
Figure 44: FCP “Park” Mode
27
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Electrical Controls
Continued
Teach-In Process, Paired Swing
1. Door stop adjustment a. Adjust the internal door stop as shown in Figure 45 to achieve 90 door angle. The door arm should not pass beyond 90. Adjust both operators.
Figure 45: Set both Door Stops (90° Maximum) b. Change the operating mode on FCP to Automatic (solid green circle on keypad) as shown below. Do this for
both operators.
Figure 46: FCP “Automatic” mode (both Operators) c. On the primary controller, momentarily touch a jumper wire between terminals C1 and C2. The first cycle will
be slow as the door will look for a positive full open door stop. Continue to activate the door with the jumper
between C1 and C2 until an audible tone and the learning code (H66) is no longer displayed on FCP. Learning
procedure lasts between 5-14 cycles.
d. See programming table for other functions or parameters as required.
e. Set Hold Open timer on Primary controller only. Secondary controller Hold Open timer should be set to 0.
28
ASI DOORS, INC.
(800) 558-7068 asidoors.com
29
Programming Parameter Codes
Continued
Most common parameters used are highlighted. *Indicates Default Value
Note Code
01 5
Function
Door operator type iMotion 1301 / 1302
02 1
02 3
02 4
03 0
03 1
Automatic configuration (SW2: till 1. beep)
Start Teach-In 1 (AUTO 1)
Start Teach-In 2 (AUTO 2)
--Delete and restart "Reference run" or "Teach-In 1 & 2"
--Detecting and storing of safety facilities 1-4 (SW2: till 3.sign)
03 2 --Detecting and storing MCU Lock Module 1
03 3 --Detecting and storing of MCU Battery Module
03 4
03 5
--Detecting and storing of MCU I/O- Module 1+2
--Detecting and storing of MCU Power supply Module
03 7
03 8
03 9
04 0
--Detecting and storing of MCU User interface 2
Terminal Module: Detecting, storing "in 1-4" (NO,NC,100Hz)
I/O Module 1: Detecting, storing of "in 1-4" (NO, NC)
Reset
04 2
04 3
04 4
Firmware version
Number of cycles
Number of operating hours
04 5
04 6
Delete fault protocol
Address of control unit for network
07 0...9
--Door mass
09 0 End procedure "Spring preload"
09 1
09 2
Spring closing, sliding lever, preload 10°
Spring closing, standard linkage, preload 30°
Performs functions 030, 031,032,...7
Safety inactive
Only with code 572, Check coding on module
Check coding on module
Check coding on module
Pulse generators inactive
Pulse generators inactive
Soft ware reset - Starts program with calibration run
Example: r06_00 = V06.00
Example: c10_302 = 10'302 cycles (max. 99?999?999)
Example: h4_002 = 4002 hours (max.99'999'999)
Example: A1 = address no. 1
End with code 090
End with code 090
Code Function
10 0...F
Hold open time of activator in mode of op AUTO1
0
0
Note
1 2* 3 4 5 6 7 8 9 A b C d E F code
0.5
1 2 3 5 7.5
10 12.5
15 17.5
20 25 30 45 60 sec.
11 0...F
12 0...F
13 0...9
14 0...9
15 0...9
0
0
Hold open time of activator in mode of op. AUTO2
0
0
1 2* 3 4* 5 6 7 8 9 A b C d E F code
0.5
1 2 3 5 7.5
10 12.5
15 17.5
20 25 30 45 60 sec.
Hold open time of key switch
0 1 2 3 4* 5 6 7 8 9 A b C d E F code
0
1
0 0.5
1 2 3 5 7.5
10 12.5
15 17.5
20 25 30 45 60 sec.
Delay time Mode of op. OFF
1
3
2*
5
3
7.5
4
10
5
15
6
20
7
30
8
45
9
60 code sec.
Bell active time
0
=imp
1
0.5
2*
1
Bell intermission
3
2
4
3
5
4
6
5
7
6
8
8
9
10
0 = Duration identical to trigger duration code sec.
1 2 3 4 5 6* 7 8
0.5
1 2 3 4 5 6 8
9
10 code sec.
ASI DOORS, INC.
(800) 558-7068 asidoors.com
30
Electrical Controls
Continued
Most common parameters used are highlighted. *Indicates Default Value
Code
17 0...9
18 0...9
19 0...9
20 0...9
21 0...9
22 0...9
23 0...9 2*
24 0...9 0*
26 0...9 2*
28 0...9 4*
30 0...9
31 0...9
33 0...9
35 0...9 5*
36 0...9 5*
37 0...9 7*
39 0...9 5*
41 0...9
42 0...9
43 1...F
44 1...F
Function
Runtime Battery in mode of op. 2-6
Note
Door opens aft er switch-off battery
0 1 2 3* 4 5 6 7 8 9 code
10s 1 5 10 30 60 120 240 360 480 sec./min.
Runtime Battery in mode of op. OFF
0* 1 2 3 4 5 6 7 8 9
10s 1 5 10 30 60 120 240 360 480 sec./min.
Airlock timeout 0 = No timeout for airlock function
0* 1 2 3 4 5 6 7 8 9 code
-10 15 20 25 30 45 60 90 120 sec.
Opening Speed 0 = No timeout for airlock function
0 1 2 3 4* 5 6 7 8 9 code
10 20 30 40 50 60 70 80 90 100 degree/s
Closing Speed Limitation only valid for "Teach-In 1 + 2"
0 1 2 3 4* 5 6 7 8 9 code
8 16 24 32 40 48 56 64 72 80
Close check speed
0* 1 2 3 4 5 6
2 3 5 8 12 17 23
7
30
8
38
9
47
Manual opening speed limit
Manual closing speed limit
Braking distance opening degree/s
Angle see 42x code degree/s
0=Limitation according to course of movement, 1-9=slow-fast
0=Limitation according to course of movement, 1-9=slow-fast
Non-applicable aft er Teach, 0 = short
0
5
Braking distance closing
Motor force opening
1 2 3 4 5 6 7* 8 9
Non-applicable aft er Teach
Net force on door edge code
11 22 33 44 55 66 77 88 100 %
Motor force closing
0
5
1* 2 3 4 5 6 7 8 9
Net force on door edge code
11 22 33 44 55 66 77 88 100 %
Motor holding closed force
0*
0
1 2 3 4 5 6 7 8 9
1 2 3 5 8 12 18 25 35 incl. discharge electric strike together with code 58x code
Reversing sensitivity opening
Reversing sensitivity closing
Push-and-Go sensitivity
Travel distance tolerances (60..300%)
Opening width reduced
0 1 2 3 4 5 6* 7 8 9
Nm
9 = max
9 = max
9 = max, 0 = off
New Teach-In required
Non-applicable aft er Teach code
10 20 30 40 50 60 70 80 90 100 %
Close check angle
0*
0
1 2 3 4 5 6 7 8 9
1 2 3 5 7 10 15 20 30
Crossing angle master
Crossing angle slave
Close check speed see 22x code degree
Application see T-1319
Application see T-1319
ASI DOORS, INC.
(800) 558-7068 asidoors.com
31
Electrical Controls
Continued
51 7
55 0
55 1
55 2*
57 0
57 1
57 2
57 3
58 0...9
60 0
60 1
60 2
60 3*
60 4
60 5
60 6
60 7
60 8
60 9
61 0...9 4*
62 0...9 5*
63 0...9 0*
64 0
64 1*
64 2
64 3
64 4
64 5
64 6
64 7
64 8
64 9
64 a
64 b
64 c
Most common parameters used are highlighted. *Indicates Default Value
Code
46 0...9 0*
51 1...6
Function
Opening width scaling up 0...+9%
Operating mode return to last setting on user interface
1 2 3 4 5 6
Note
Non-applicable aft er Teach
Aft er terminal operating mode code
59 0...6
OFF AUT1 AUT2 EXIT OPEN Man.
No operating mode return
Locks in operating mode OFF
Locks in operating mode OFF, EXIT
Locks in operating mode OFF, AUTO 1+2, EXIT, P
Electric strike: current-free locked (Fail secure)
Electric strike: current-free unlocked (Fail safe)
Without electric strike
Mode of operation
Aft er terminal operating mode
Only for electric strike with 100% duty ratio
Only for electric strike with 100% duty ratio
Only for electric strike with 100% duty ratio
Electric strike switch-on range 100%, until door is closed
Delay time to open
0* 1
0 0.2
2
0.4
3
0.8
4
1.2
5 6 7 8
Only for electric strike with 100% duty ratio
Independent adjustment only with skipper
9 code
1.6
2.0
2.5
3.0
4.0
sec.
Tension "pwm out" with connection to terminal 40V or 24V**
0
6
1
9
2
12
3 4*
15 24 in1: Operation mode OFF in1: Operation mode MANUAL in1: Operation mode OPEN in1: Activator inside in1: Activator outside in1: Key switch
5 6
12** 24** in1: Emergency opening except in OFF in1: Emergency opening in all modes of op.
in1: Emergency closing (with locking) in1: Operation mode EXIT in2: Same choice of functions as on "in1" in3: Same choice of functions as on "in1" in4: Same choice of functions as on "in1" sf1: Safety opening 1 with stop function sf1: Safety opening 1 with creeping function sf1: Safety closing 1 with reversing function sf1: Safety closing 1 with creeping function sf1: Safety swing area sf1: Safety stop sf1: Emergency opening except in OFF sf1: Emergency opening in all modes of op.
sf1: Emergency closing (with locking) sf1: Mode of op. MANUAL / Break out sf1: Safety opening 2 with stop function sf1: Safety opening 2 with creeping function sf1: Safety closing 2 with reverse function code
V DC
Contact NO. NC detect with code 038
Contact NO. NC detect with code 038
Contact NO. NC detect with code 038
Contact NO. NC, 100Hz detect with code 038
Contact NO. NC, 100Hz detect with code 038
Contact NO. NC, 100Hz detect with code 038
Contact NO. NC, 100Hz detect with code 038
Contact NO. NC, 100Hz detect with code 038
Contact NO. NC, 100Hz detect with code 038
Contact NO. NC detect with code 038
Contact type detect with code 038
Contact type detect with code 038
Contact type detect with code 038
Type of connection NO,NC,test detect with code 031
Type of connection NO,NC,test detect with code 031
Type of connection NO,NC,test detect with code 031
Type of connection NO,NC,test detect with code 031
Type of connection NO,NC,test detect with code 031
Type of connection NO,NC,test detect with code 031
Contact NO. NC detect with code 031
Contact NO. NC detect with code 031
Contact NO. NC detect with code 031
Contact NO. NC detect with code 031
Type of connection NO,NC,test detect with code 031
Type of connection NO,NC,test detect with code 031
Type of connection NO,NC,test detect with code 031
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Electrical Controls
Continued
Most common parameters used are highlighted. *Indicates Default Value
Code
64 d
74 0*
74 1
74 2
74 3
74 4
74 5
74 6
74 7
70 3
70 4
70 5
70 6
70 7
71 0...7 0*
72 0...7 0*
73 0...7 0*
64 e
65 0...E 2*
66 0...E 4*
67 0...E 5*
68 0
68 1
68 2
68 3
68 4*
68 5
68 7
68 9
69 0...9 2*
70 0*
70 1
70 2
74 8
74 9
75 0...9 0*
76 0...9 0*
77 0...9 0*
78 0
78 1*
78 2
78 3
78 4
78 5
Function sf1: Safety closing 2 with creeping function sf1: Inhibit switch sf2: Same choice of functions as on "sf1" sf3: Same choice of functions as on "sf1" sf4: Same choice of functions as on "sf1" out1: Message "door closed" out1: Message “door closed and locked” out1: Message “door open” out1: Message “General fault” out1: Bell out1: Message “Mode of operation OFF” out1: Battery in service out1: Message “door is opening or open” out2: Same choice of functions as on "out1"
I/O Module 1: in1: No function
I/O Module 1: in1: Operating mode OFF
I/O Module 1: in1: Operating mode AUTOMATIC 1
I/O Module 1: in1: Operating mode AUTOMATIC 2
I/O Module 1: in1: Operating mode EXIT
I/O Module 1: in1: Operating mode OPEN
I/O Module 1: in1: Operating mode MANUAL
I/O Module 1: in1: Inhibit switch
I/O Module 1: in2: Same choice of functions as on I/O Module 1: in1
I/O Module 1: in3: Same choice of functions as on I/O Module 1: in1
I/O Module 1: in4: Same choice of functions as on I/O Module 1: in1
I/O Module 1: out1: No function
I/O Module 1: out1: Operating mode OFF
I/O Module 1: out1: Operating mode AUTOMATIC 1
I/O Module 1: out1: Operating mode AUTOMATIC 2
I/O Module 1: out1: Operating mode EXIT
I/O Module 1: out1: Operating mode OPEN
I/O Module 1: out1: Operating mode MANUAL
I/O Module 1: out1: "Door is opening"
I/O Module 1: out1: “Door is opening or open”
I/O Module 1: out1: "Door is closing"
I/O Module 1: out2: Same choice of functions as on I/O Module 1: out1
I/O Module 1: out3: Same choice of functions as on I/O Module 1: out1
I/O Module 1: out4: Same choice of functions as on I/O Module 1: out1
User Interface 1: in1: No function
User Interface 1: in1: User interface lock
User Interface 1: in1: Operating mode OFF
User Interface 1: in1: Operating mode AUTOMATIC 2
User Interface 1: in1: Operating mode EXIT
User Interface 1: in1: Operating mode OPEN
Note
Type of connection NO,NC,test detect with code 031
Type of connection NO,NC,test detect with code 031
Type of connection detect with code 031
Type of connection detect with code 031
Type of connection detect with code 031
Function visible aft er 1 door-opening cycle
Contact NO. NC detect with code 039
Contact NO. NC detect with code 039
Contact NO. NC detect with code 039
Contact NO. NC detect with code 039
Contact NO. NC detect with code 039
Contact NO. NC detect with code 039
Contact NO. NC detect with code 039
Contact NO. NC detect with code 039
Contact NO. NC detect with code 039
Contact NO. NC detect with code 039
Contact NO. Use User Interface from V1.07!
Contact NO. Use User Interface from V1.07!
Contact NO. Use User Interface from V1.07!
Contact NO. Use User Interface from V1.07!
Contact NO. Use User Interface from V1.07!
32
ASI DOORS, INC.
(800) 558-7068 asidoors.com
33
Electrical Controls
Continued
Most common parameters used are highlighted. *Indicates Default Value
Code
78 6
80 4
82 0*
82 1
82 2
82 3
83 0*
83 1
83 2
78 7
78 8
78 9
79 0...9 0*
80 0
80 1
80 2*
80 3
83 3
83 4
85 0*
85 1
85 2
Function
User Interface 1: in1: Operating mode MANUAL
User Interface 1: in1: Emergency closing
User Interface 1: in1: Emergency opening in all op. modes
User Interface 1: in1: Key switch
User Interface 1: in2: Same choice as on User Interface 1: in1
Bell trigger: Safety closing 1
Bell trigger: Safety closing 2
Bell trigger: Activator inside
Bell trigger: Activator outside
Bell trigger: Key switch
No step-by-step control
Step-by-step control only for key switch
Step-by-step control only for activator inside and outside
Step-by-step control for activator inside, outside and key switch
Single door
Primary drive, double leaf door, type A
Secondary drive, double leaf door type A
Primary drive, double leaf door, nurse & bed passage
Secondary drive, double leaf door, nurse & bed passage
No airlock function
Airlock function for inner door
Airlock function for outer door
Note
Contact NO. Use User Interface from V1.07!
Contact NO. Use User Interface from V1.07!
Contact NO. Use User Interface from V1.07!
Contact NO. Use User Interface from V1.07!
Contact NO. Use User Interface from V1.07!
Application see T-1319
Application see T-1319
Application see T-1572
Application see T-1572
Application see T-1304
Application see T-1304
Trouble Shooting Codes - *E = Error - H = Hint
E35
E36
E37
E38
E39
E40
E31
E32
E33
E34
E0x
E21
E22
E23
*No.
Fault
E00 Firmware incompatible to MCU version /D
Internal test negative
LIN to User Interface 1 USIN interrupted
LIN to User Interface 2 USIN interrupted
LIN to s I/O-Module 1 INOU interrupted
E24
E25
E26
E30
LIN to s I/O-Module 2 INOU interrupted
LIN to Lock Unit 1 LOCU interrupted
LIN to Lock Unit 2 LOCU interrupted
Safety close. creep 2 >1min. active, test neg.
Safety open 1 >1min. active, test neg.
Safety op. creep 1 >1min. active, test neg.
Safety closing 1 >1min. active, test neg.
Safety close. creep 1 >1min. active, test neg.
Safety swing area >1min. active, test neg.
Safety stop >1min. active, test neg.
Safety open 2 >1min. active, test neg.
Safety op. creep 2 >1min. active, test neg.
Safety closing 2 >1min. active, test neg.
User-defined input > 1min. active
Behavior of System
Safety operating mode or only display
Safety operating mode or only display
Last mode of operation remains
Last mode of operation remains
Programmed function will be inactive
Programmed function will be inactive
Last status remains
Last status remains
According safety function
According safety function
According safety function
According safety function
According safety function
According safety function
According safety function
According safety function
According safety function
According safety function
(Door remains open)
Reset
Reset, new version MCU32-BASE
Reset
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
ASI DOORS, INC.
(800) 558-7068 asidoors.com
34
Electrical Controls
Continued
Trouble Shooting Codes - *E = Error - H = Hint
E31
E32
E33
E34
H13
H14
H18
H21
E67
E8x
H11
H12
E63
E64
E65
E66
E55
E56
E61
E62
E49
E51
E53
E54
E43
E46
E47
E48
E39
E40
E41
E42
E35
E36
E37
E38
*No.
Fault
E00 Firmware incompatible to MCU version /D
E0x
E21
E22
E23
E24
E25
E26
E30
Behavior of System
Safety operating mode or only display
Internal test negative
LIN to User Interface 1 USIN interrupted
LIN to User Interface 2 USIN interrupted
Safety operating mode or only display
Last mode of operation remains
Last mode of operation remains
Programmed function will be inactive
LIN to s I/O-Module 1 INOU interrupted
LIN to s I/O-Module 2 INOU interrupted
LIN to Lock Unit 1 LOCU interrupted
LIN to Lock Unit 2 LOCU interrupted
Programmed function will be inactive
Last status remains
Last status remains
Safety close. creep 2 >1min. active, test neg.
Safety open 1 >1min. active, test neg.
Safety op. creep 1 >1min. active, test neg.
Safety closing 1 >1min. active, test neg.
According safety function
According safety function
According safety function
According safety function
According safety function
Safety close. creep 1 >1min. active, test neg.
Safety swing area >1min. active, test neg.
Safety stop >1min. active, test neg.
Safety open 2 >1min. active, test neg.
Safety op. creep 2 >1min. active, test neg.
Safety closing 2 >1min. active, test neg.
User-defined input > 1min. active
Activator inside > 1min. active
Activator outside > 1min. active
Key switch > 1min. active
Emergency open >10min. active
Emergency close >10min. active
Wake up or Push button SW2 > 1min. active
Inhibit switch> 1min. active
Encoder not working
Calibration run diff erent from reference
Driveway in op. longer than reference
Position drift . Shaft displacing
Door blocked
Voltage 40V outside of admissible range
Power Supply 24V (Limit U, I)
Current in power supply 40V to high
According safety function
According safety function
According safety function
According safety function
According safety function
(Door remains open)
Door remains open
Door remains open
Door remains open
Door remains open
Door closes and remains closed
Door remains open
Door stand still
Safety operating mode
Safety operating mode
Safety operating mode
Only display, auto-correction stops
Safety operation mode
Safety operation mode
Safety op. mode
Safety operating mode
Motor temperature > 90 ° C, cable interrupted Safety operating mode
Control end stage > 100 ° C
Motor control faulty in MCU32-BASE
Motor current to high in long-term
Memory or processor test negative
Operator type not defined
Door mass not defined
Linkage type not defined
Automatic configuration not executed
Configuration error in trajectory
Teach-In: Door moves >15s before start
Safety operating mode
Safety operating mode
Normal operation
Safety operating mode
Safety operating mode
Safety operating mode
Safety operating mode
Safety operating mode
Safety operating mode
Abort Teach-In
Reset
Reset, new version MCU32-BASE
Reset
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Automatically if OK
Reset
Reset >automatic configuration
Automatically if OK / Reset
Reset
Automatically if OK
Automatically if OK
Automatically if OK
Automatically aft er cooling down
Automatically aft er cooling down
Reset
Automatically if OK
Reset
Program operator type
Program door mass
Configuration 09x and 090
Program 021
New Teach-In
New Teach-In
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Electrical Controls
Continued
Trouble Shooting Codes - *E = Error - H = Hint
*No.
Fault
H22 Teach-In: No start within 15s
H73
H91
H92
H93
H94
H64
H66
H67
H71
H27
H29
H62
H63
H23
H24
H25
H26
Teach-In: Opening movement >15s
Teach-In: Hold open time >60s
Teach-In: Closing movement >15s
Teach-In: Wrong direction at closing
Teach-In: Diff ering close position
Teach-In: Request
Calibration run in closing direction
Reference run opening
Reference run closing
Learn mode (Force detection)
Absolute position not found yet
Battery mode
Motor current in closed position to high
Obstacle detection at opening
Obstacle detected at closing
Permanent obstacle at opening
Permanent obstacle at closing
Control Connection Diagram - Single Swing
Behavior of System
Abort Teach-In
Abort Teach-In
Abort Teach-In
Abort Teach-In
Abort Teach-In
Abort Teach-In
Abort Teach-In
Searches closed position
Measures reference run length
Searches closed position
Normal operation
Slow opening movement
Door moves slowly
Normal operation
Door reverses
Door reverses
Reset aft er 5 reversing's
Reset aft er 5 reversing's
Reset
New Teach-In
New Teach-In
New Teach-In
New Teach-In
New Teach-In
New Teach-In
Execute Teach-In
At the end of movement
At the end of movement
At the end of movement
Aft er max. 20 full opening cycles
Aft er max. 20 full opening cycles
Reset, reduce 33x
Automatically, Display 20s.
Automatically, Display 20s.
Automatically, Display 20s.
Automatically, Display 20s
All inputs and outputs are programmable, see programming table
Safety Slow -
Will slow the door while opening.
Reactivation -
Will reactivate the door when activated and will inhibit aft er door is fully closed.
Safety Swing Area -
Will prevent the door from moving when fully open or fully closed.
TE: Test signal for SMR sensors
(Superscan, Quadscans)
35
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Electrical Controls
Continued
Activator inside - Activation Signal
Activator outside -
Activation Signal - Inhibits when FCP is in 1-way mode and the door is fully closed.
Key switch -
Activates the door open in all modes, except (P) Manual mode
Off -
Inside and Outside sensors are inhibited unless door is activated by Key switch input.
Figure 47: Single Swing Inputs & Outputs
Electric lock -
Can power up a magnetic lock or electric strike, 1A max output. Has selectable output voltages.
Power output to Sensor is 0.75 amps Max.
Power output to Lock output is 1.00 amp Max.
Outputs 1, 2 -
See programming table.
Control Connection Diagram - Paired Swing, Primary Leaf
All inputs and outputs are programmable, see programming table
Safety Slow -
Will slow the door while opening.
Reactivation -
Will reactivate the door when activated and will inhibit aft er door is fully closed.
Safety Swing Area -
Will prevent the door from moving when fully open or fully closed.
TE: Test signal for SMR sensors
(Superscan, Quadscans)
36
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Electrical Controls
Continued
Activator inside - Activation Signal
Activator outside -
Activation Signal - Inhibits when FCP is in 1-way mode and the door is fully closed.
Key switch -
Activates the door open in all modes, except (P) Manual mode
Off -
Inside and Outside sensors are inhibited unless door is activated by Key switch input.
Figure 48: Paired Swing Primary Leaf Inputs & Outputs
Electric lock -
Can power up a magnetic lock or electric strike, 1A max output. Has selectable output voltages.
Power output to Sensor is 0.75 amps Max.
Power output to Lock output is 1.00 amp Max.
Outputs 1, 2 -
See programming table.
Control Connection Diagram - Paired Swing, Secondary Leaf
All inputs and outputs are programmable, see programming table
Safety Slow -
Will slow the door while opening.
Reactivation -
Will reactivate the door when activated and will inhibit aft er door is fully closed.
Safety Swing Area -
Will prevent the door from moving when fully open or fully closed.
TE: Test signal for SMR sensors
(Superscan, Quadscans)
37
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Electrical Controls
Continued
Figure 49: Paired Swing Secondary Leaf Inputs & Outputs
Power output to Sensor is 0.75 amps Max.
Power output to Lock output is 1.00 amp Max.
Schematic Diagram - Single Swing
Activator inside - Activation Signal
Activator outside -
Activation Signal - Inhibits when FCP is in 1-way mode and the door is fully closed.
Key switch -
Activates the door open in all modes, except (P) Manual mode
Off -
Inside and Outside sensors are inhibited unless door is activated by Key switch input.
Electric lock -
Can power up a magnetic lock or electric strike, 1A max output. Has selectable output voltages.
Outputs 1, 2 -
See programming table.
38
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Electrical Controls
Continued
Schematic Diagram - Paired Swing, Primary Leaf
39
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Electrical Controls
Continued
Schematic Diagram - Paired Swing, Secondary Leaf
40
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Instructions for Ordering
This parts manual is intended to assist in the correct identification of the more commonly replaced parts; covering, generally, all models and styles off ered within the marathon pharm. Line. The manual will also help identify obsolete parts, part design changes and current production parts. For more specific parts information, please contact an authorized representative or consult the factory’s customer service or engineering departments. Asi doors reserves the right to discontinue any part and make design changes without notice.
General Instructions for Ordering Door Parts
Accurate information is always necessary to serve you correctly and promptly. Several steps should be followed to determine exactly the parts that are needed.
Refer to the information tag on your door and record the:
1. Door model number
Use part numbers referenced in this manual.
If the item is not found in the manual, the product code on the back of the item is helpful.
If your door has no information label, the approximate purchase date is helpful.
Call
1-800-558-7068 or visit asidoors.com/parts to order parts
41
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Door Assembly, Single
All Single Doors, Manual & Power
Power Operator (RH/LH)
Shroud, Power, Operators
(RH/LH) (0 º, 30 º)
Door Frame
(Welded or Knockdown)
1
Manual Closers and
Covers (RH/LH)
42
Description PART#
Door Panel Assembly, LH/RH Consult Factory
Consult Factory Gasket, Sweep (L = WIC)
Gasket, Perimeter (L = 2* HIC
+WIC)
Gasket, Perimeter (L = 2* HIC
+WIC)
Consult Factory
Consult Factory
ITEM#
1
2
3
4
When ordering parts, specify
Job Number, Door Number and
Manufacture Date
ASI DOORS, INC.
(800) 558-7068
4
1
2 asidoors.com
Door Assembly, Paired
All Paired Doors, Manual & Power
Power Operator (RH/LH)
Shroud, Power, Operators
(RH/LH) (0 º, 30 º)
Door Frame
(Welded or Knockdown)
Manual Closers and
Covers (RH/LH)
4
Description PART#
Door Panel Assembly, RH Consult Factory
Door Panel Assembly, LH
Gasket Sweep (L=WIC/2)
Gasket, Perimeter (L = 2* HIC
+WIC)
Hinge
Consult Factory
Consult Factory
Consult Factory
Consult Factory
ITEM#
1
2
3
4
5
43
When ordering parts, specify
Job Number, Door Number and
Manufacture Date
ASI DOORS, INC.
(800) 558-7068
1
5
1
2
2 asidoors.com
Door Panel
1
4B
2
4A
3
3
4B
12
5
6
44
ASI DOORS, INC.
(800) 558-7068
4B
2 asidoors.com
Header Assembly
11
11
6
10
10
9
8
7
Description PART#
Door Panel Assembly, RH Consult Factory
Door Panel Assembly, LH
Capping, Panel, Top/Bottom ( As Required)
Capping, Panel, Side ( As Required)
Consult Factory
Consult Factory
Consult Factory
Screw, #10-24 x 1.00, PH FH MS, S/S (Hinge Side)
Screw, #10-24 x 1.00, PH FH SMS, S/S (Non-Hinge Side)
Hinge
Screw, #12-24 x 1.00, PHL FHMS, S/S
41A199
41A794
Consult Factory
41A656
Push Plate, W/ Handle (Optional, Pre-2010)
Push Plate (Optional, Pre-2010)
Handle, Stainless (STD)
Push Plate, Stainless (STD)
Screw, #6-32 x 0.75, PHL FHMS, S/S
Window Asm, 1-3/4”, Pharm Panel (Optional)
Window Asm, 1-3/4”, Cleanview (Optional)
16B017
16B016
16B0085NN
16B022
41A655
55B575
55B400
When ordering parts, specify
Job Number, Door Number and
Manufacture Date
9
10
7
8
11
12
12
ITEM#
1
1
2
3
4A
4B
5
6
45
ASI DOORS, INC.
(800) 558-7068 asidoors.com
4
5
4
5
Operator and Shroud
3
3
3
3
1
1
4
5
4
2
5
46
ASI DOORS, INC.
(800) 558-7068 asidoors.com
Operator and Shroud
Description PART#
Asm, Operator, Inswing, Single, LH 30D0040LV
Asm, Operator, Inswing, Single, RH
Asm, Operator, Outswing, Single, LH
30D0040RV
30D0041LV
Asm, Operator, Outswing, Single, RH
Asm, Operator, Inswing, Paired
30D0041RV
30D0042NV
Asm, Operator, Outswing, Paired 30D0043NV
Operator, 1301
Outswing Arm Assembly, Aluminum
23B0147
16B0094NN
Outswing Arm Assembly, 0"- 4", Stainless
Outswing Arm Assembly, 4"- 10", Stainless
Inswing Arm & Track Assembly, Aluminum
Inswing Arm & Track Assembly, Stainless
Manual Closer, RH/LH
16B0097NN
16B0098NN
16B0095NN
16B0096NN
Consult Factory
Closer Cover, S/S
Screw, 10-24 x 1/2”, PH, PHMS, S/S
Consult Factory
41A618
Bracket, Shroud, Power Swing, 304 / 316 Stainless 13B2485NN20 / 25
Asm, Single RJ12 Connector 24B0725
Asm, Paired RJ12 Connectors 24B0726
Cable, LIN BUS, 7 FT 23A0371NN
Programming Keypad (Loose) 23A0363
Shroud, 30°, Single Swing
Shroud, 30°, Paired Swing
Shroud, 0°, Single Swing
Shroud, 0°, Paired Swing
55B0125
55B0126
55B0127
55B0128
2
3
1
2
4
ITEM#
1
1
1
8
9
10
11
12
6
7
5
5
4
4
13
14
15
16
17
NOTE
Note sloped shrouds shown for reference. Shrouds are also available in flat top design. Consult factory for specific
Shroud P/N’s.
When ordering parts, specify
Job Number, Door Number and
Manufacture Date
6
8
6
7
8
7
14
9
9
47
ASI DOORS, INC.
(800) 558-7068
10
9
15
11
9 asidoors.com
asidoors.com
ASI DOORS, INC. 5848 North 95th Court, Milwaukee, WI 53225 (800) 558-7068

Public link updated
The public link to your chat has been updated.
Advertisement