- Industrial & lab equipment
- Electrical equipment & supplies
- Power conditioning
- Electrical relays
- ABB
- CO-9
- User manual
ABB CO, CO-8, CO-9 Instruction Leaflet
Add to My manuals32 Pages
ABB CO-9 is a single-phase, non-directional time overcurrent relay used for sensing current levels above a set point. It's ideal for applications requiring coordination with fuses, reclosers, cold load pickup, motor starting, or fixed-time operations. The CO-9 relay offers very inverse time characteristics for reliable protection against overcurrents, particularly in scenarios involving transformer inrush or motor protection with limited locked rotor time.
advertisement
▼
Scroll to page 2
of
32
Instruction Leaflet ABB Power T&D Company Inc. Power Automation & Protection Division Coral Springs, FL 33065 Effective : January 1997 Supersedes 41-100I, Dated January 1990 41-100J Type CO (HI-LO) Overcurrent Relay ( | ) Denotes Change Since Previous Issue File No. E103204 1. ! CAUTION Before putting relays into service, remove all blocking which may have been inserted for the purpose of securing the parts during shipment, make sure that all moving parts operate freely, inspect the contacts to see that they are clean and close properly, and operate the relay to check the settings and electrical connections. APPLICATION The CO Relay is a single phase non-directional time overcurrent device. It is used to sense current level above the setting and normally is used to trip a circuit breaker to clear faults. A wide range of characteristics permit applications involving coordination with fuses, reclosers, cold load pickup, motor starting, or essentially fixed time applications. AC trip applications are described, but they are not recommended except in applications where a fault will not reduce the ac voltage below a level at which tripping will be reliable. The following describes typical applications of the CO Relay: RELAY TYPE TIME CURVE TYPICAL APPLICATIONS CO-2 Short 1) Differential protection where saturation of current transformers is not expected, or where delayed tripping is permissible. 2) Overcurrent protection, phase or ground, where coordination with downstream devices is not involved and 2 to 60 cycle tripping is allowable. CO-5 Long Motor locked rotor protection where allowable locked rotor time is approximately between 10 and 70 seconds. CO-6 Definite CO-7 Moderately Inverse CO-8 Inverse CO-9 Very Inverse CO-11 Extremely Inverse Overcurrent protection where coordination with downstream devices is not involved and CO-2 is too fast. The operating time of this relay does not vary greatly as current level varies. 1) Overcurrent protection where coordination with other divices are required, and generation varies. 2) Backup protection for relay on other circuits. 1) Motor Protection where allowable locked rotor time is less than 10 sec. 2) Overcurrent protection where coordination with fuses and reclosers is involved, or where cold load pickup or trnsformer inrush are factors. All possible contingencies which may arise during installation, operation or maintenance, and all details and variations of this equipment do not purport to be covered by these instructions. If further information is desired by purchaser regarding this particular installation, operation of maintenance of this equipment, the local Asea Brown Boveri representative should be contacted. Courtesy of NationalSwitchgear.com I.L 40-100J 2. CONSTRUCTION AND OPERATION The type CO relays consist of an overcurrent unit (CO), either an Indicating Switch (ICS) or an ac Auxiliary Switch (ACS) and an Indicating Instantaneous Trip unit (IIT) when required. 2.1 Electromagnet The electromagnets for the types CO-5, CO-6, CO7, CO-8 and CO-9 relays have a main tapped coil located on the center leg of an "E" type laminated structure that produces a flux which divides and returns through the outer legs. A shading coil causes the flux through the left leg to lag the main pole flux. The out-of-phase fluxes thus produced in the air gap cause a contact closing torque. The electromagnets for the types CO-2 and CO-11 relays have a main coil consisting of a tapped primary winding and a secondary winding. Two identical coils on the outer legs of the lamination structure are connected to the main coil secondary in a manner so that the combination of all the fluxes produced by the electromagnet result in out-of-phase fluxes in the air gap. The out-of-phase air gap fluxes produced cause a contact closing torque. 2.2 so, during the operation, two fingers on the armature deflect a spring located on the front of the switch which allows the operation indicator target to drop. A core screw accessible from the top of the switch provides the adjustable pickup range. 2.4 Indicating Instantaneous Trip Unit (IIT) The instantaneous trip unit is a small ac operated clapper type device. A magnetic armature, to which leaf-spring mounted contacts are attached, is attracted to the magnetic core upon energization of the switch. When the switch closes, the moving contacts bridge two stationary contacts completing the trip circuit. Also, during the operation, two fingers on the armature deflect a spring located on the front of the switch which allows the operation indicator target to drop. A core screw accessible from the top of the switch and taps on the coil provide the adjustable pickup range. 3. CHARACTERISTICS The relays are generally available in the following current ranges: Indicating Contactor Switch Unit (ICS) Range The dc indicating contactor switch is a small clapper type device. A magnetic armature, to which-spring mounted contacts are attached, is attracted to the magnetic core upon energization of the switch. When the switch closes, the moving contacts bridge two stationary contacts, completing the trip circuit. Also during this operation two fingers on the armature deflect a spring located on the front of the switch, which allows the operation indicator target to drop. The front spring, in addition to holding the target, provides restraint for the armature and thus controls the pickup value of the switch. 2.3 AC Auxiliary Switch (ACS) The ac auxiliary switch is a small ac operated clapper device. A magnetic armature, to which leafspring mounted contacts are attached, is attracted to the magnetic core upon energization of the switch. When the switch closes, the moving contacts bridge two stationary contacts completing the trip circuit. Al2 Courtesy of NationalSwitchgear.com Taps .5 - 2.5 0.5, 0.6, 0.8, 1.0, 1.5, 2.0, 2.5 1 - 12 1.0, 1.2, 1.5, 2.0, 2.5, 3.0, 3.5, 4.0, 5.0, 6.0, 7.0, 8.0, 10.0, 12.0 These relays may have either single or double circuit closing contacts for tripping either one or two circuit breakers. The relays are wired per the internal schematics of Figure 1 to 9. The time vs. current characteristics are shown in Figures 10 to 16. These characteristics give the contact closing time for the various time dial settings when the indicated multiples of tap value current are applied to the relay. 3.1 Trip Circuit The main contacts will close 30 amperes at 250 volts dc and the seal-in contacts of either the indicating contactor switch or the ac auxiliary switch will carry this current long enough to trip a circuit breaker. I.L. 41-100J The indicating instantaneous trip contacts will close 30 amperes at 250 volts dc and will carry this current long enough to trip a breaker. 3.2 Indicating Contactor Switch (ICS) a. The indicating contactor switch has two taps that provide a pickup setting of 0.2 or 2 amperes. To change taps requires connecting the lead located in front of the tap block to the desired setting by means of a screw connection. b. Trip Circuit Constants 0.2 amperes tap. . . . . . . 6.5 ohms dc resistance 2.0 amperes tap. . . . . . . 0.15 ohms dc resistance 3.3 ac Auxiliary Switch (ACS) a. Each of the following ACS units is available in the Hi-Lo Line of relays. 4. INSTALLATION The relays should be mounted on switchboard panels or their equivalent in a location free from dirt, moisture, excessive vibration and heat. Mount the relay vertically by means of the mounting stud for projection mounting or by means of the four mounting holes on the flange for the semiflush mounting. ACS UNIT CURRENT RANGE ASC/VOLTAGE DROP RANGE (1) 0.15 0.5 1.0 0.2-0.38 0.75-1.5 1.5-3.0 40-76 14-27 6.8-14 MINIMUM RECOMMENDED SUPPLY VOLTAGE (2) – 208 120 Notes: (1) This is the voltage range which will operate the ACS coil only. (2) When connected as a current switch in series with a full rated voltage relay or trip coil. Energy Requirements ACS UNIT 0.15 0.5 1.0 BURDEN IN VOLT-AMPERES AT MINIMUM SETTINGS 4.5 4.5 4.5 THERMAL CAPACITY AMPERE RATING (COIL) 1 SECOND CONTINUOUS 4.5 18.0 44.0 0.16 0.63 1.60 Either the stud or the mounting screws may be utilized for grounding the relay. The electrical connections may be made directly to the terminals by means of screws for steel panel mounting or to the terminal stud furnished with the relay for thick panel mounting. The terminal stud may be easily removed or inserted by locking two nuts on the stud and then turning the proper nut with a wrench. For detail information on the FT case refer to I.L. 41-076. 5. SETTINGS 5.1 CO Unit The overcurrent unit setting can be defined by tap setting and time dial position or by tap setting and a specified time of operation at some current multiple of the tap setting (e.g. 4 tap setting, 2 time dial position or 4 tap setting, 0.6 seconds at 6 times tap value current). The tap setting is the minimum current required to make the disc move. To provide selective circuit breaker operation, a minimum coordinating time of 0.3 seconds plus circuit breaker time is recommended between the relay being set and the relays with which coordination is to be effected. The screw on the terminal plate above the time dial makes connections to various turns on the operating coil. By placing this screw in the various terminal plate holes, the relay will respond to multiples of tap value currents in accordance with the various typical time-current curves. ! CAUTION Since the tap block screw on both the CO unit and IIT unit carries operating current, be sure that the screws are turned tight. In order to avoid opening current transformer circuits when changing taps under load, the relay must be first removed from the case. Chassis operating shorting switches on the case will short the secondary of the current transformer. The taps should then be changed with the relay outside of the case and then re-inserted into the case. 3 Courtesy of NationalSwitchgear.com I.L 40-100J 5.2 Instantaneous Reclosing 5.5 ac Auxiliary Switch (ACS) The factory adjustment of the CO unit contacts provides a contact follow. Where circuit breaker reclosing will be initiated immediately after a trip by the CO contact, the time of the opening of the contacts should be a minimum. This condition is obtained by loosening the stationary contact mounting screw, removing the contact plate and then replacing the plate with the bent end resting against the contact spring. The core screw must be adjusted to the value of pickup current desired. For double trip relays, the upper stationary contact is adjusted such that the contact spring rests solidly against the back stop. The lower stationary contact is then adjusted such that both stationary contacts make contacts simultaneously with their respective moving contact. For relays which include an indicating instantaneous trip unit (IIT), the junction of the induction and indicating instantaneous trip coils is brought out to switch jaw #3. With this arrangement the overcurrent units can be tested separately. 5.3 The following check is recommended to verify that the relay is in proper working order: Indicating Contactor Switch (ICS) The only setting required on the ICS unit is the selection of the 0.2 or 2.0 amperes tap setting. This selection is made by connecting the lead located in front of the tap block to the desired setting by means of the connecting screw. When the relay energizes a 125 or 250 volt dc type WL relay switch, or equivalent, use the 0.2 ampere tap; for 48 volt dc applications, use the 2.0 ampere tap and use a type WL relay with a Style #304C209G01 coil, or equivalent. The relay is shipped set for 2.0 tap. 5.4 Indicating Instantaneous Trip (IIT) The IIT setting is the level of ac current at which it will pickup. It should be set to coordinate with other devices so it will never operate for a fault in a protective zone where tripping should be produced by other devices. The transient reach will not exceed 130% for an 80o circuit angle or 108% for a 60o circuit. The proper tap must be selected and the core screw must be adjusted to the value of pick-up current desired. The nameplate data will furnish the actual current range that may be obtained from the IIT unit. It is recommended that the IIT be set on the higher tap where there is a choice of tap settings. For example,, for a 20 amperes setting use the 20 to 40 tap rather than the 6 to 20 tap. 4 Courtesy of NationalSwitchgear.com 6. ADJUSTMENTS & MAINTENANCE The proper adjustments to insure correct operation of this relay have been made at the factory. Upon receipt of the relay no customer adjustments, other than those covered under "SETTINGS" should be required. Performance Check 6.1 Contact The index mark on the movement frame will coincide with the "0" mark on the time dial when the stationary contact has moved through approximately one-half of its normal deflection. Therefore, with the stationary contact resting against the backstop, the index mark is offset to the right of the "0" mark by approximately .020". The placement of the various time dial positions in line with the index mark will give operating times as shown on the respective time-current curves. For double trip relays, the follow on the stationary contacts should be approximately 1/32". 6.2 Minimum Trip Current Set the time dial to position 6 using the lowest tap setting, alternately apply tap value current plus 3% and tap value current minus 3%. The moving contacts should leave the backstop at tap value current plus 3% and should return to the backstop at tap value current minus 3%. 6.3 Time Curve Table I shows the time curve calibration points for the various types of relays. With the time dial set to the indicated position apply the currents specified by Table I, (e.g. for the CO-8, 2 and 20 times tap value current) and measure the operating time of the relay. I.L. 41-100J The .5 to 2.5 amp relay and all CO-2 relays should be set on the lowest tap. The 1 to 12 amp relay should be set on the 2 amp tap with the exception of 1-12 amp. CO-2 relay which should be set on 1 amp tap. The operating times should equal those of Table I plus or minus 5%. For type CO-11 relay only, the 1.30 times tap value operating time from the number 6 time dial position is 54.9 ± 5% seconds and should be checked first. It is important that the 1.30 times tap value current be maintained accurately. The maintaining of this current accurately is necessary because of the steepness of the slope of the time-current characteristic (Figure 16). A slight variation, ± 1%, in the 1.3 times tap value current (including measuring instrument deviation) will change the timing tolerance to ± 10% and the effects of different taps can make the total variations appear to be ±15%. 6.4 Indicating Instantaneous Trip Unit (IIT) The core screw which is adjustable from the top of the trip unit and the tap located on the top of the IIT determines the pickup value. The trip unit has a nominal ratio of adjustment of 1 to 24. The making of the contacts and target indication should occur at approximately the same instant. Position the stationary contact for a minimum of 1/32" wipe. The bridging moving contact should touch both stationary contacts simultaneously. Apply sufficient current to operate the IIT. The operation indicator target should drop freely. 6.5 Indicating Contactor Switch (ICS) Close the main relay contacts and pass sufficient dc current through the trip circuit to close the contacts of the ICS. This value of current should be not greater than the particular ICS tap setting being used. The operation indicator target drop freely. The contact follow will be approximately 1/64" to 3/ 64". The bridging moving contact should touch both stationary contacts simultaneously. at approximately the same instant. Position the stationary contact for a minimum of 1/32" wipe. The bridging moving contact should touch both stationary contacts simultaneously. Apply sufficient current to operate the ACS. The operation indicator target should drop freely. Routine Maintenance All relays should be inspected and checked periodically to assure proper operation. Generally a visual inspection should call attention to any noticeable changes. A minimum suggested check on the relay system is to close the contacts manually to assure that the breaker trips and the target drops. Then release the contacts and observe that the reset is smooth and positive. If an additional time check is desired, pass secondary current through the relay and check the time of operation. It is preferable to make this at several times pick-up current at an expected operating point for the particular application. For the .5 to 2.5 amperes range CO-5 and CO-6 induction unit use the alternative test circuit in Fig. 19 as these relays are affected by a distorted waveform. With this connection the 25/5 amperes current transformers should be worked well below the knee of the saturation (i.e. use 10L50 or better). All contacts should be periodically cleaned. A contact burnisher #182A836H01 is recommended for this purpose.. The use of abrasive material for cleaning contacts is not recommended because of the danger of embedding small particles in the face of the soft silver and thus impairing the contact. 7. Use the following procedure for calibrating the relay if the relay has been taken apart for repairs or the adjustments disturbed. This procedure should not be used until it is apparent that the relay is not in proper working order. (See "Performance Check"). CO Unit 7.1 6.6 ac Auxiliary Switch (ACS) The core screw which is adjustable from the top of the ACS unit determines the pickup value. The making of the contacts and target indication should occur CALIBRATION Contact The index mark on the movement frame will coincide with the "0" mark on the time dial when the stationary contact has moved through approximately one-half of its normal deflection. Therefore, 5 Courtesy of NationalSwitchgear.com I.L 40-100J with the stationary contact resting against the backstop, the index mark is offset to the right of the "0" mark by approximately .020". The placement of the various time dial positions in line with the index mark will give operating times as shown on the respective time-current curves. For double trip relays, the follow on the stationary contacts should be approximately 1/32". 7.2 Minimum Trip Current The adjustment of the spring tension in setting the minimum trip current value of the relay is most conveniently made with the damping magnet removed. With the time dial set on "0", wind up the spiral spring by means of the spring adjuster until approximately 6-3/4 convolutions show. Set the .5-2.5 amp relay and all CO-2 relays on the minimum tap setting. With the exception of CO-2 relay, set the 1-2 amp relay on the 2 amp tap setting. Set the 1-12 amp CO-2 on the 1 amp tap. Set time dial position 6 on all relays. Adjust the control spring tension no that the moving contact will leave the backstop at tap value current +1.0% and will return to the backstop at tap value current -1.0%. 7.3 Time Curve Calibration Install the permanent magnet. Apply the indicated current per Table I for permanent magnet adjustment (e.g. CO-8, 2 times tap value) and measure the operating time. Adjust the permanent magnet keeper until the operating time corresponds to the value of Table I. For type CO-11 relay only, the 1.30 times tap value operating time from the number 6 time dial position is 54.9 ±5% seconds. It is important that the 1.30 times tap value current be maintained accurately. The maintaining of this current accurately is necessary because of the steepness of the slope of the time-current characteristic (Figure 16). A slight variation, ±1%, in the 1.3 times tap value current (including measuring instrument deviation) will change the timing tolerance to _ 10% and the effect of different taps can make the total variations appear to be ±15%. If the operating time at 1.3 times tap value is not within these limits, a minor adjustment of the 6 Courtesy of NationalSwitchgear.com control spring will give the correct operating time without any undue effect on the minimum pick-up of the relay. This check is to be made after the 2 times tap value adjustment has been made. Apply the indicated current per Table I for the electromagnet plug adjustment (e.g. CO-8, 20 times tap value) and measure the operating time. Adjust the proper plug until the operating time corresponds to the value in Table I. (Withdrawing the left hand plug, front view, increases the operation time withdrawing the right hand plug, front view, decreases the time.). In adjusting the plugs, one plug should be screwed in completely and the other plug run in or out until the proper operating time has been obtained. Recheck the permanent magnet adjustment. If the operating time for this calibration point has changed, readjust the permanent magnet and then recheck the electromagnet plug adjustment. 7.4 Indicating Contactor Switch (ICS) Close the main relay contacts and pass sufficient dc current through the trip circuit to close the contacts of the ICS. This value of current should be not greater than the particular ICS tap setting being used. The operation indicator target should drop freely. For proper contact adjustment, insert a .030" feeler guage between the core pin and the armature. Hold the armature closed against the core pin and guage and adjust the stationary contacts such that they just make with the moving contact. Both stationary contacts should make at approximately the same time. The contact follow will be approximately 1/64" to 3/ 64". 7.5 ac Auxiliary Switch (ACS) The core screw must be adjusted to the value of pickup current desired. The nameplate data of the ACS will furnish the actual current range that may be obtained from the ACS unit. 7.6 Indicating Instantaneous Trip Unit (IIT) The proper tap must be selected and the core screw adjusted tothe value of pickup currentdesired. The nameplate data and tap plate of the IIT will furnish the actual current range that may be obtained from the IIT unit. I.L. 41-100J TABLE 1 TIME CURVE CALIBRATION DATA 50 AND 60 Hertz PERMANENT MAGNET ADJUSTMENT RELAY TYPE TIME DIAL POSITION CURRENT (MULTIPLES OF TAP VALUE) OPERATING TIME SECONDS CO-2 CO-5 CO-6 CO-7 CO-8 CO-9 CO-11 6 6 6 6 6 6 6 3 2 2 2 2 2 2 0.57 37.80 2.46 4.27 13.35 8..87 11.27 8. RENEWAL PARTS Repair work can be done most satisfactorily at the factory. However, interchangeable parts can be furnished to the customers who are equipped for doing repair work. When ordering parts always give the complete nameplate data. ELECTROMAGNET PLUGS CO-2 CO-5 CO-6 CO-7 CO-8 CO-9 CO-11 ∆ 6 6 6 6 6 6 6 20 10 20 20 20 20 20 0.22 14.30 1.19 1.11 1.11 0.65 0.24 ∆ For 50 Hz. CO-11 relay 20 times operating time limits are 0.24 + 20% -5%. 7 Courtesy of NationalSwitchgear.com I.L 40-100J 8 Courtesy of NationalSwitchgear.com I.L. 41-100J ENERGY REQUIREMENTS INSTANTANEOUS TRIP UN IT(IIT) 60 HERTZ BURDEN (NOTE 1 FOR 50 HZ) TYPE OF IIT UNIT RANGES AVAILABLE WITH CORE ADJUSTMENT 2-48 6-144 2-7 7-14 14-48 6-20 20-40 40-144 AT PICKUP TAP SETTING MINIUM PICKUP 2-7 7-14 14-48 6-20 20-40 40-144 2 7 14 6 20 40 R .68 .076 .032 108 .016 .007 XL Z .42 .048 .012 .067 .008 .002 .8 .09 .035 .127 .018 .007 3 TIMES PICKUP .72 .086 .035 .125 .018 .007 OHMS 10 TIMES PICKUP .67 .075 .035 .125 .018 .007 20 TIMES PICKUP CONT. RATING AMPS 1 SECO ND RATING AMPS 2.5 7 10 7 16 25 70 140 185 88 280 460 .67 .075 .035 .100 .018 .007 NOTE 1. 50 Hz values for Z and OHMS are 96% to 100% of 60 Hz Values. CO-2 SHORT TIME RELAY 60 HERTZ VOLT AMPERES**(x∆ FOR 50 HZ) AMPERE RANGE TAP 0.5/2.5 1/12 0.5 0.6 0.8 1.0 1.5 2.0 2.5 1.0 1.2 1.5 2.0 2.5 3.0 3.5 4.0 5.0 6.0 7.0 8.0 10.0 12.0 AT CONTINUOUS ONE SECOND POWER TAP VALUE RATING RATING FACTOR CURRENT (AMPERES) (AMPERES) ANGLE ø (∆ = 0.86) 0.91 0.96 1.18 1.37 1.95 2.24 2.50 1.65 1.90 2.20 3.30 4.00 5.00 5.50 6.50 7.10 8.80 9.50 10.50 12.00 13.00 28 28 28 28 28 28 28 28 28 28 28 56 56 56 56 230 230 230 230 230 230 58 57 53 50 40 36 29 55 54 53 54 56 55 54 53 53 50 48 46 40 35 4.8 4.9 5.0 5.3 6.2 7.2 7.9 4.6 4.6 4.8 4.8 4.7 4.9 4.9 4.8 5.1 5.2 5.7 6.2 6.8 7.8 AT 3 TIMES TAP VALUE CURRENT (∆ = 0.88) 39.6 39.8 42.7 45.4 54.4 65.4 73.6 37.3 38.0 40.0 40.5 39.2 40.2 41.0 41.0 42.7 44.0 48.5 53.0 61.0 0 AT 10 TIMES AT 20 TIMES TAP VALUE TAP VALUE CURRENT CURRENT (∆ = 0.9) (∆ = 0.91) 256 270 308 348 435 580 700 266 280 310 315 282 295 312 325 330 360 390 475 565 680 790 851 1024 1220 1740 2280 285 895 1000 1150 1180 970 1050 1125 1150 1200 1350 1600 1800 2500 3300 Thermal capacities for short times other than one second may be calculated on the basis of times being inversely proportional to the square of the current ø Degrees current lags voltage at tap value current ** Voltages taken with Rector type voltmeter 9 Courtesy of NationalSwitchgear.com I.L 40-100J ENERGY REQUIREMENTS CO-5 LONG TIME AND CO-6 DEFINITE MINIMUM TIME RELAYS 60 HERTZ VOLT AMPERES**(x∆ FOR 50 HZ) RANGE 0.5/2.5 1/12 TAP RATING (AMPERES) RATING (AMPERES) FACTOR ANGLE ø 0.5 2.7 88 69 0.6 0.8 1.0 1.5 2.0 2.5 1.0 1.2 1.5 2.0 2.5 3.0 3.5 4.0 5.0 6.0 7.0 8.0 10.0 12.0 3.1 3.7 4.1 5.7 6.8 7.7 4.5 5.5 6.0 7.7 9.5 10.0 12.0 13.5 15.0 17.5 20.5 22.5 23.5 26.5 88 88 88 88 88 88 88 88 88 88 88 230 230 230 230 460 460 460 460 460 68 67 66 62 60 58 69 68 67 66 65 65 65 64 61 60 57 53 48 42 AT TAP VALUE CURRENT (∆ = 0.86) AT 3 TIMES TAP VALUE CURRENT (∆ = 0.88) AT 10 TIMES TAP VALUE CURRENT (∆ = 0.9) AT 20 TIMES TAP VALUE CURRENT (∆ = 0.91) 3.93 20.6 103 270 3.96 3.96 4.07 4.19 4.30 4.37 3.98 3.98 4.00 3.98 3.98 4.02 4.06 4.12 4.18 4.35 4.44 4.54 4.80 5.34 20.7 21 21.4 23.2 24.9 26.2 21.0 21.3 21.8 21.9 22.2 22.5 23.2 23.5 24.6 25.8 27.0 28.6 32.5 37.9 106 114 122 147 168 180 100 103 109 115 122 125 132 137 150 165 185 211 266 325 288 325 360 462 548 630 265 282 308 340 363 366 402 420 500 570 630 736 940 1152 103 107 114 122 148 174 185 100 104 110 117 123 127 131 136 153 165 189 206 250 342 278 288 320 356 459 552 640 265 270 300 312 360 390 413 420 490 528 630 732 970 1224 CO-7 MODERATELY INVERSE TIME RELAY 0.5/2.5 1/12 0.5 0.6 0.8 1.0 1.5 2.0 2.5 1.0 1.2 1.5 2.0 2.5 3.0 3.5 4.0 5.0 6.0 7.0 8.0 10.0 12.0 2.7 3.1 3.7 4.1 5.7 6.8 7.7 4.5 5.5 6.0 7.7 9.5 10.0 12.0 13.5 15.0 17.5 20.5 22.5 23.5 26.5 88 88 88 88 88 88 88 88 88 88 88 88 230 230 230 230 460 460 460 460 460 68 67 66 64 61 58 56 68 67 66 65 64 63 63 63 60 58 54 50 46 42 3.88 3.93 3.93 4.00 4.08 4.24 4.38 3.86 3.82 3.92 3.90 3.90 3.92 3.97 4.02 4.11 4.29 4.43 4.50 4.81 5.04 20.7 20.9 21.1 21.6 22.9 24.8 25.9 20.6 20.4 21.2 21.8 21.8 22.5 22.7 22.9 24.1 25.5 27.3 30.8 32.6 36.9 Thermal capacities for short times other than one second may be calculated on the basis of time being inversely proportional to the square of the current. øDegrees current lags voltage at tap value current 10 * * Voltages taken with Tectox type voltmeter Courtesy of NationalSwitchgear.com I.L. 41-100J ENERGY REQUIREMENTS CO-8 INVERSE TIME AND CO-9 VERY INVERSE TIME RELAYS 60 HERTZ VOLT AMPERES**(x∆ FOR 50 HZ) AMPERE RANGE 0.5/2.5 1/12 TAP CONTINUOUS RATING (AMPERES) 0.5 0.6 0.8 1.0 1.5 2.0 2.5 1.0 1.2 1.5 2.0 2.5 3.0 3.5 4.0 5.0 6.0 7.0 8.0 10.0 12.0 2.7 3.1 3.7 4.1 5.7 6.8 7.7 4.5 5.5 6.0 7.7 9.5 10.0 12.0 13.5 15.0 17.5 20.5 22.5 23.5 26.5 0.5 0.6 0.8 1.0 1.5 2.0 2.5 1.0 1.2 1.5 2.0 2.5 3.0 3.5 4.0 5.0 6.0 7.0 8.0 10.0 12.0 1.7 1.9 2.2 2.5 3.0 3.5 3.8 3.5 4.0 5.5 8.5 10.0 12.5 14.0 15.0 17.0 18.5 20.0 21.5 25.0 28.0 ONE SECOND POWER RATING FACTOR (AMPERES) (AMPERES) 88 88 88 88 88 88 88 88 88 88 88 88 230 230 230 230 460 460 460 460 460 72 71 69 67 62 57 53 73 73 72 69 68 67 66 65 63 60 57 55 48 45 AT TAP VALUE CURRENT (∆ = 0.86) 3.38 2.38 2.40 2.42 2.51 2.65 2.74 2.33 2.33 2.35 2.35 2.36 2.37 2.38 2.40 2.40 2.47 2.51 2.52 2.77 2.94 AT 3 TIMES TAP VALUE CURRENT (∆ = 0.88) 21 21 21.1 21.2 22 23.5 24.8 20 20 20.1 20.2 20.3 20.4 20.9 21.0 21.0 21.6 21.8 22.2 24.5 25.4 AT 10 TIMES TAP VALUE CURRENT (∆ = 0.9) AT 20 TIMES TAP VALUE CURRENT (∆ = 0.91) 132 134 142 150 170 200 228 135 135 142 145 146 149 153 157 164 170 180 192 230 258 350 365 400 440 530 675 800 347 361 383 412 415 420 450 460 500 525 600 672 830 960 71.8 75.0 84.0 93.1 115.5 136.3 160.0 82 87 93 96 96 88 88 96 110 120 135 160 210 276 250 267 298 330 411 502 610 300 324 350 380 377 340 340 366 435 478 560 648 900 120 CO-11 EXTREMELY INVERSE TIME RELAY 0.5/2.5 1/12 56 56 56 56 56 56 56 56 56 56 56 56 230 230 230 230 460 460 460 460 460 36 34 30 27 22 17 16 30 29 26 25 24 33 31 29 25 22 20 19 14 10 0.72 0.75 0.81 0.89 1.13 1.30 1.48 0.82 0.90 0.97 1.00 1.10 0.87 0.88 0.94 1.10 1.25 1.40 1.50 1.9 2.4 6.54 6.80 7.46 8.30 10.04 11.95 13.95 7.4 8.0 8.6 8.9 9.0 8.0 8.2 8.7 10.0 11.5 12.3 14.0 18.3 23.8 Thermal capacities for short times other than one second may be calculated on the basis of times being inversely proportional to the square of the current øDegrees current lags voltage at tap value current * * Voltages taken with Rector type voltmeter Courtesy of NationalSwitchgear.com 11 I.L 40-100J INDICATING CONTACTOR SWITCH INDUCTION UNIT ICS RED HANDLE TEST SWITCH CURRENT TEST JACK CHASSIS OPERATED SHORTING SWITCH TERMINAL Sub 3 57D4524 Figure 1. Internal Schematic of the Double Trip Relay Without IIT 12 Courtesy of NationalSwitchgear.com I.L. 41-100J Sub 1 3498A03 Figure 2. Internal Schematic of the Double Trip Relay With IIT 13 Courtesy of NationalSwitchgear.com I.L 40-100J Sub 3 57D4523 Figure 3. Internal Schematic of the Single Trip Relay Without IIT 14 Courtesy of NationalSwitchgear.com I.L. 41-100J Sub 1 3498A02 Figure 4. Internal Schematic of the Single Trip Relay With IIT 15 Courtesy of NationalSwitchgear.com I.L 40-100J Sub 1 3508A73 Figure 5. Internal Schematic of Double Trip Relay With ITT to Separate Terminals 16 Courtesy of NationalSwitchgear.com I.L. 41-100J Sub 2 3516A07 Figure 6. Internal Schematic of the Single Trip Relay With ITT Contacts Wired to Two Separate Terminals 17 Courtesy of NationalSwitchgear.com I.L 40-100J Sub 6 183A608 Figure 7. Internal Schematic of the Single Trip Relay With an ACS Unit 18 Courtesy of NationalSwitchgear.com I.L. 41-100J Sub 4 3515A06 Figure 8. Internal Schematic of the Single Trip Relay With an ACS Unit and IIT 19 Courtesy of NationalSwitchgear.com I.L 40-100J Sub 1 3524A37 Figure 9. Internal Schematic of the Single Trip Relay With an ACS Unit and with IIT Contacts Wired to Two Separate Terminals 20 Courtesy of NationalSwitchgear.com I.L. 41-100J MULTIPLES OF TAP VALUE Curve 619584 Figure 10. Typical Time Curve of the Type CO-2 Relay 21 Courtesy of NationalSwitchgear.com I.L 40-100J Curve 418245 Figure 11. Typical Time Curve of the Type CO-5 Relay 22 Courtesy of NationalSwitchgear.com I.L. 41-100J Curve 418246 Figure 12. Typical Time Curve of the Type CO-6 Relay 23 Courtesy of NationalSwitchgear.com I.L 40-100J Curve 418247 Figure 13. Typical Time Curve of the Type CO-7 Relay 24 Courtesy of NationalSwitchgear.com I.L. 41-100J Curve 418248 Figure 14. Typical Time Curve of the Type CO-8 Relay 25 Courtesy of NationalSwitchgear.com I.L 40-100J Curve 418249 Figure 15. Typical Time Curve of the Type CO-9 Relay 26 Courtesy of NationalSwitchgear.com I.L. 41-100J Sub 2 288B655 Figure 16. Typical Time Curve of the Type CO-11 Relay 27 Courtesy of NationalSwitchgear.com I.L 40-100J NEG. OR POS. ICS ICS DEVICE NUMBER CHART 51 - OVERCURRENT RELAY, TYPE CO 51-N - GROUND OVERCURRENT TELAY, TYPE CO 52 - POWER CIRCUIT BREAKER 52A - BREAKER AUXILIARY CONTACT ICS - INDICATING CONTACTOR SWITCH TC - BREAKER TRIP COIL NEG. OR POS. Sub 3 182A755 Figure 17. External Schematic of HiLo CO Relay for Phase and Ground Overcurrent Protection on a Three Phase System Sub 1 3527A93 Figure 18. External Schematic of HiLo CO Relay with ACS Unit for Phase and Ground Protection on a Three Phase System 28 Courtesy of NationalSwitchgear.com I.L. 41-100J Sub 3 3503A43 Figure 19. Siagram of Test Connections for the Type CO Relay 29 Courtesy of NationalSwitchgear.com I.L 40-100J RELAY TYPE FIRST 7 DIGITS OF STYLE NO. C0-2 CO-5 CO-6 CO-7 CO-8 CO-9 CO-11 LAST THREE DIGITS OF STYLE NUMBER RANGE CO 265C195 264C897 264C898 264C899 264C900 264C901 265C047 RANGE IIT DESCRIPTION SCHEMATIC 60 HZ 50 HZ A01 A21 .5-2.5 --- SINGLE TRIP A02 A22 .5-2.5 --- DOUBLE TRIP A03 A23 .5-2.5 2-48 SINGLE TRIP A04 A24 .5-2.5 2-48 DOUBLE TRIP A05 A25 1-12 --- SINGLE TRIP A06 A26 1-12 --- DOUBLE TRIP A07 A27 1-12 6-144 SINGLE TRIP A08 A28 1-12 6-144 DOUBLE TRIP A09 A29 .5-2.5 6-144 SINGLE TRIP A10 A30 .5-2.5 6-144 DOUBLE TRIP A11 A31 1-12 2-48 SINGLE TRIP A12 A32 1-12 2-48 DOUBLE TRIP A13 A33 .5-2.5 2-48 DOUBLE TRIP A14 A34 1-12 6-144 DOUBLE TRIP A15 A35 .5-2.5 6-144 DOUBLE TRIP A16 A36 1-12 2-48 DOUBLE TRIP A17 --- .5-2.5 2-48 SINGLE TRIP A18 A38 1-12 6-144 SINGLE TRIP A19 --- .5-2.5 6-144 SINGLE TRIP A20 A40 1-12 2-48 SINGLE TRIP WITH IIT CONTACTS WIRED TO SEPARATE TERMINALS WITH IIT CONTACTS WIRED TO SEPARATE TERMINALS WITH IIT CONTACTS WIRED TO SEPARATE TERMINALS WITH IIT CONTACTS WIRED TO SEPARATE TERMINALS WITH IIT CONTACTS WIRED TO TWO SEPARATE TERMINALS WITH IIT CONTACTS WIRED TO TWO SEPARATE TERMINALS WITH IIT CONTACTS WIRED TO TWO SEPARATE TERMINALS WITH IIT CONTACTS WIRED TO TWO SEPARATE TERMINALS 57D4523 (FIG. 3) 57D4524 (FIG.1) 3498A02 (FIG.4) 3498A03 (FIG.2) 57D4523 (FIG. 3) 57D4524 (FIG.1) 3498A02 (FIG.4) 3498A03 (FIG.2) 3498A02 (FIG.4) 3498A03 (FIG.2) 3498A02 (FIG.4) 3498A03 (FIG.2) 3508A73 (FIG.5) 3508A73 (FIG.5) 3508A73 (FIG.5) 3508A73 (FIG.5) 3516A07 3516A07 3516A07 3516A07 Sub 60 775B349 Figure 20. Style Descriptions of CO Relay with ICS Unit. 30 Courtesy of NationalSwitchgear.com I.L. 41-100J LAST THREE DIGITS OF STYLE NO. 60 HZ 50 HZ RELAY TYPE RANGE CO A01 C0-11 A02 ACS UNITS IN AMPS RANGE IIT 1-12 .5 - SINGLE TRIP 183A680 CO-11 1-12 1.0 - SINGLE TRIP 183A680 A03 CO-8 1-12 1.0 - SINGLE TRIP 183A680 A04 CO-5 1-12 1.0 - SINGLE TRIP 183A680 A05 CO-5 1-12 1.0 6-144 SINGLE TRIP 3515A06 A06 CO-9 1-12 1.0 6-144 SINGLE TRIP 3515A06 A07 CO-11 1-12 0.5 6-144 SINGLE TRIP 3515A06 A08 CO-9 1-12 1.0 - SINGLE TRIP 183A680 A09 CO-9 1-12 0.5 - SINGLE TRIP 183A680 A10 CO-9 1-12 0.5 6-144 SINGLE TRIP 3515A06 A11 CO-2 1-12 0.5 6-144 SINGLE TRIP 3515A06 A12 CO-5 .5-2.5 0.5 - SINGLE TRIP 183A680 A13 CO-2 1-12 1.0 6-144 SINGLE TRIP 3515A06 A14 CO-9 .5-2.5 1.0 2-48 SINGLE TRIP 3515A06 CO-8 1-12 1.0 6-144 SINGLE TRIP 3515A06 A16 CO-11 1-12 1-0 6-144 SINGLE TRIP 3515A06 A18 CO-8 1-12 ,5 6-144 SINGLE TRIP 3515A06 A19 CO-11 .5-2.5 .5 - SINGLE TRIP 183A680 A20 CO-7 1-12 1.0 - SINGLE TRIP 183A680 A23 CO-8 .5-2.5 1.0 - SINGLE TRIP 183A680 A24 CO-5 .5-2.5 1.0 - SINGLE TRIP 183A680 A25 CO-11 1-12 .15 6-144 SINGLE TRIP 3515A06 A26 CO-8 .5-2.5 .15 2-48 SINGLE TRIP 3515A06 A27 CO-5 1-12 .15 - SINGLE TRIP 183A680 A28 CO-8 1-12 0.5 2-48 SINGLE TRIP 3515A06 A29 CO-6 1-12 1.0 - SINGLE TRIP 183A680 A30 CO-8 1-12 1.0 SINGLE TRIP 3524A37 A31 CO-9 .5-2.5 0.5 - SINGLE TRIP 183A680 A32 CO-11 .5-2.5 1.0 - SINGLE TRIP 183A680 A33 CO-11 .5-2.5 1.0 2-48 SINGLE TRIP 3515A06 A17 A15 6-144 DESCRIPTION Figure 21. Style Description of CO Relays with ACS Units SCHEMATIC Sub 60 775B349 31 Courtesy of NationalSwitchgear.com I.L 40-100J * Sub 20 57D7900 Figure 22. Outline and Drilling Plan for the Type CO Relay *Denotes Change Since Previous Issue 32 Courtesy of NationalSwitchgear.com
advertisement
Key Features
- Single-Phase
- Non-Directional
- Very Inverse Time
- Coordination with Fuses/Reclosers
- Cold Load Pickup
- Motor Starting
- Transformer Inrush
Related manuals
Frequently Answers and Questions
What type of time curve does the CO-9 relay have?
The CO-9 relay has a very inverse time curve, which means the tripping time decreases rapidly as the current increases.
What are some common applications for the CO-9 relay?
Common uses include motor protection with limited locked rotor time, overcurrent protection with coordination with fuses and reclosers, and handling cold load pickup inrush.
How does the CO-9 relay coordinate with other devices?
The relay's very inverse time curve allows it to coordinate with downstream protective devices, ensuring selective tripping in case of a fault.