- No category
advertisement
GT27 General Description
GT2715-XTBA
GT2712-STBD
GT2710-VTBA
GT2708-STBA
GT2715-XTBD
GT2712-STWD
GT2710-VTWA
GT2708-STBD
GT2712-STBA
GT2710-STBA
GT2710-VTBD
GT2708-VTBA
Thank you for purchasing the GOT2000 Series.
GT2712-STWA
GT2710-STBD
GT2710-VTWD
GT2708-VTBD
Prior to use, please read both this manual and the detailed manual thoroughly to fully understand the product.
MODEL
Model code
GT27-U-GD-E
1D7MI3
IB(NA)-0800502ENG-D(1404)MEE
SAFETY PRECAUTIONS
(Always read these precautions before using this equipment.)
Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay full attention to safety to handle the product correctly.
The precautions given in this manual are concerned with this product.
In this manual, the safety precautions are ranked as "WARNING" and "CAUTION".
WARNING
CAUTION
Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight personal injury or physical damage.
Note that the CAUTION level may lead to a serious accident according to the circumstances.
Always follow the instructions of both levels because they are important to personal safety.
Please save this manual to make it accessible when required and always forward it to the end user.
[DESIGN PRECAUTIONS]
WARNING
Some failures of the GOT, communication unit or cable may keep the outputs on or off.
Some failures of a touch panel may cause malfunction of the input objects such as a touch switch.
An external monitoring circuit should be provided to check for output signals which may lead to a serious accident.
Not doing so can cause an accident due to false output or malfunction.
Do not use the GOT as the warning device that may cause a serious accident.
An independent and redundant hardware or mechanical interlock is required to configure the device that displays and outputs serious warning.
Failure to observe this instruction may result in an accident due to incorrect output or malfunction.
The GOT backlight failure disables the operation on the touch switch(s).
When the GOT backlight has a failure, the POWER LED blinks (orange/blue) and the display section dims. In such a case, the input by the touch switch(s) is disabled.
The display section of the GOT is an analog-resistive type touch panel. The
GOT is multi-touch compliant; however, do not touch three points or more simultaneously on the display section. Doing so may cause an accident due to incorrect output or malfunction.
When programs or parameters of the controller (such as a PLC) that is monitored by the GOT are changed, be sure to reset the GOT, or turn on the unit again after shutting off the power as soon as possible.
Not doing so can cause an accident due to false output or malfunction.
If a communication fault (including cable disconnection) occurs during monitoring on the GOT, communication between the GOT and PLC CPU is suspended and the GOT becomes inoperative.
For bus connection : The CPU becomes faulty and the GOT becomes inoperative.
For other than bus connection : The GOT becomes inoperative.
A system where the GOT is used should be configured to perform any significant operation to the system by using the switches of a device other than the GOT on the assumption that a GOT communication fault will occur.
Not doing so can cause an accident due to false output or malfunction.
7
8
5
6
9
0
3
4
1
2
7
8
5
6
9
0
3
4
1
2
[DESIGN PRECAUTIONS]
CAUTION
Do not bundle the control and communication cables with main-circuit, power or other wiring.
Run the above cables separately from such wiring and keep them a minimum of 100mm apart.
Not doing so noise can cause a malfunction.
Do not press the GOT display section with a pointed material as a pen or driver.
Doing so can result in a damage or failure of the display section.
When the GOT is connected to the Ethernet network, the available IP address is restricted according to the system configuration.
• When multiple GOTs are connected to the Ethernet network :
Do not set the IP address (192.168.3.18) for the GOTs and the controllers in
the network.
• When a single GOT is connected to the Ethernet network :
Do not set the IP address (192.168.3.18) for the controllers except the GOT
in the network.
Doing so can cause the IP address duplication. The duplication can negatively affect the communication of the device with the IP address
(192.168.3.18).
The operation at the IP address duplication depends on the devices and the system.
Turn on the controllers and the network devices to be ready for communication before they communicate with the GOT.
Failure to do so can cause a communication error on the GOT.
When the GOT is subject to shock or vibration, or some colors appear on the screen of the GOT, the screen of the GOT might flicker.
[MOUNTING PRECAUTIONS]
WARNING
Be sure to shut off all phases of the external power supply used by the system before mounting or removing the GOT main unit to/from the panel.
Not doing so can cause the unit to fail or malfunction.
Be sure to shut off all phases of the external power supply used by the system before mounting or removing the option unit onto/from the GOT.
CAUTION
Use the GOT in the environment that satisfies the general specifications described in this manual.
Not doing so can cause an electric shock, fire, malfunction or product damage or deterioration.
When mounting the GOT to the control panel, tighten the mounting screws in the specified torque range (0.36 N•m to 0.48 N•m) with a Phillips-head screwdriver No.2.
Undertightening can cause the GOT to drop, short circuit or malfunction.
Overtightening can cause a drop, short circuit or malfunction due to the damage of the screws or the GOT.
When mounting a unit on the GOT, tighten the mounting screws in the following specified torque range.
When loading the communication unit or option unit other than wireless LAN unit to the GOT, fit it to the connection interface of the GOT and tighten the mounting screws in the specified torque range (0.36 N•m to 0.48 N•m) with a
Phillips-head screwdriver No.2.
When loading the wireless LAN unit to the GOT, fit it to the side interface of
GOT and tighten the mounting screws in the specified torque range (0.10
N•m to 0.14 N•m) with a Phillips-head screwdriver No.1.
Under tightening can cause the GOT to drop, short circuit or malfunction.
Overtightening can cause a drop, failure or malfunction due to the damage of the screws or unit.
When closing the USB environmental protection cover, fix the cover to the
GOT by pushing the [PUSH] mark on the latch firmly to comply with the protective structure.
Remove the protective film of the GOT.
When the user continues using the GOT with the protective film, the film may not be removed.In addition, for the models equipped with the human sensor function, using the GOT with the protective film may cause the human sensor not to function properly
Operate and store the GOT in environments without direct sunlight, high temperature, dust, humidity, and vibrations.
When using the GOT in the environment of oil or chemicals, use the protective cover for oil.Failure to do so may cause failure or malfunction due to the oil or chemical entering into the GOT.
[WIRING PRECAUTIONS]
WARNING
Be sure to shut off all phases of the external power supply used by the system before wiring.
Failure to do so may result in an electric shock, product damage or malfunctions.
CAUTION
Make sure to ground the FG terminal and LG terminal of the GOT power supply section to the protective ground conductors dedicated to the GOT with a ground resistance of 100 Ω or less.
When tightening the terminal screws, use a Phillips-head screwdriver No.2.
Terminal screws which are not to be used must be tightened always at torque
0.5 N•m to 0.8 N•m.
Otherwise there will be a danger of short circuit against the solderless terminals.
Use applicable solderless terminals and tighten them with the specified torque. If any solderless spade terminal is used, it may be disconnected when the terminal screw comes loose, resulting in failure.
Correctly wire the GOT power supply section after confirming the rated voltage and terminal arrangement of the product.
Not doing so can cause a fire or failure.
[WIRING PRECAUTIONS]
CAUTION
Tighten the terminal screws of the GOT power supply section in the specified torque range (0.5 N•m to 0.8 N•m). Undertightening can cause a short circuit or malfunction.Overtightening can cause a short circuit or malfunction due to the damage of the screws or the GOT.
Exercise care to avoid foreign matter such as chips and wire offcuts entering the GOT. Not doing so can cause a fire, failure or malfunction.
The module has an ingress prevention label on its top to prevent foreign matter, such as wire offcuts, from entering the module during wiring.
Do not peel this label during wiring.Before starting system operation, be sure to peel this label because of heat dissipation.
Plug the communication cable into the GOT interface or the connector of the connected unit, and tighten the mounting screws and the terminal screws in the specified torque range.Undertightening can cause a short circuit or malfunction.Overtightening can cause a short circuit or malfunction due to the damage of the screws or unit.
Plug the QnA/ACPU/Motion controller(A series) bus connection cable by inserting it into the connector of the connected unit until it "clicks".
After plugging, check that it has been inserted snugly.
Not doing so can cause a malfunction due to a contact fault.
[TEST OPERATION PRECAUTIONS]
WARNING
Before performing the test operations of the user creation monitor screen
(such as turning ON or OFF bit device, changing the word device current value, changing the settings or current values of the timer or counter, and changing the buffer memory current value), read through the manual carefully and make yourself familiar with the operation method.
During test operation, never change the data of the devices which are used to perform significant operation for the system.
False output or malfunction can cause an accident.
[STARTUP/MAINTENANCE PRECAUTIONS]
WARNING
When power is on, do not touch the terminals.
Doing so can cause an electric shock or malfunction.
Correctly connect the battery connector.Do not charge, disassemble, heat, short-circuit, solder, or throw the battery into the fire.Doing so will cause the battery to produce heat, explode, or ignite, resulting in injury and fire.
Before starting cleaning or terminal screw retightening, always switch off the power externally in all phases.Not switching the power off in all phases can cause a unit failure or malfunction.Undertightening can cause a short circuit or malfunction.Overtightening can cause a short circuit or malfunction due to the damage of the screws or unit.
CAUTION
Do not disassemble or modify the unit.
Doing so can cause a failure, malfunction, injury or fire.
Do not touch the conductive and electronic parts of the unit directly.
Doing so can cause a unit malfunction or failure.
The cables connected to the unit must be run in ducts or clamped.
Not doing so can cause the unit or cable to be damaged due to the dangling, motion or accidental pulling of the cables or can cause a malfunction due to a cable connection fault.
When unplugging the cable connected to the unit, do not hold and pull from the cable portion.Doing so can cause the unit or cable to be damaged or can cause a malfunction due to a cable connection fault.
Do not drop the module or subject it to strong shock. A module damage may result.
Do not drop or give an impact to the battery mounted to the unit.
Doing so may damage the battery, causing the battery fluid to leak inside the battery.If the battery is dropped or given an impact, dispose of it without using.
Before touching the unit, always touch grounded metals, etc. to discharge static electricity from human body, etc.
Not doing so can cause the unit to fail or malfunction.
Use the battery manufactured by Mitsubishi Electric Corporation.
Use of other batteries may cause a risk of fire or explosion.
Dispose of used battery promptly.
Keep away from children.Do not disassemble and do not dispose of in fire.
Be sure to shut off all phases of the external power supply before replacing the battery or using the dip switch of the terminating resistor.Not doing so can cause the unit to fail or malfunction by static electricity.
[TOUCH PANEL PRECAUTIONS]
CAUTION
For the analog-resistive film type touch panels, normally the adjustment is not required.
However, the difference between a touched position and the object position may occur as the period of use elapses.
When any difference between a touched position and the object position occurs, execute the touch panel calibration.
When any difference between a touched position and the object position occurs, other object may be activated.
This may cause an unexpected operation due to incorrect output or malfunction.
[PRECAUTIONS WHEN THE DATA STORAGE IS IN
USE]
WARNING
If the SD card mounted on drive A of the GOT is removed while the GOT is accessed, processing for the GOT might be interrupted about for 20 seconds.The GOT cannot be operated during this period. The functions that run in the background including a screen updating, alarm, logging, scripts, and others are also interrupted.Since this interruption makes an impact to the system operation, it might cause failure.After checking the light off of SD card access LED, remove the SD card.
CAUTION
If the data storage mounted on the GOT is removed while the GOT is accessed, the data storage and files are damaged.To remove the data storage from the GOT, check that the access to the data storage in SD card access LED, the system signal, and others is not performed.
When inserting a SD card into the GOT, make sure to close the SD card cover. Failure to do so causes the data not to be read or written.
When removing the SD card from the GOT, make sure to support the SD card by hand as it may pop out.Failure to do so may cause the SD card to drop from the GOT, resulting in a failure or break.
When inserting a USB device into a USB interface of the GOT, make sure to insert the device into the interface firmly.Failure to do so may cause the USB device to drop from the GOT, resulting in a failure or break
Before removing the USB device from the GOT, follow the procedure for removal on the utility screen of the GOT. After the successful completion dialog is displayed, remove the USB device by hand carefully.Failure to do so may cause the USB device to drop from the GOT, resulting in a failure or break.
[DISPOSAL PRECAUTIONS]
CAUTION
When disposing of this product, treat it as industrial waste.
When disposing of batteries, separate them from other wastes according to the local regulations.
(Refer to the GOT2000 Series User’s Manual (Hardware) for details of the battery directive in the EU member states.)
[TRANSPORTATION PRECAUTIONS]
CAUTION
When transporting lithium batteries, make sure to treat them based on the transport regulations.
(Refer to the GOT2000 Series User’s Manual (Hardware) for details of the regulated models.)
Make sure to transport the GOT main unit and/or relevant unit(s) in the manner they will not be exposed to the impact exceeding the impact resistance described in the general specifications of this manual, as they are precision devices.
Failure to do so may cause the unit to fail.
Check if the unit operates correctly after transportation.
When fumigants that contain halogen materials such as fluorine, chlorine, bromine, and iodine are used for disinfecting and protecting wooden packaging from insects, they cause malfunction when entering our products.
Please take necessary precautions to ensure that remaining materials from fumigant do not enter our products, or treat packaging with methods other than fumigation (heat method).
Additionally, disinfect and protect wood from insects before packing products.
Manual
The following shows manuals relevant to this product.
Detailed Manual
Manual name
GOT2000 Series User’s Manual
(Hardware)
GOT2000 Series User’s Manual (Utility)
Manual number
(Model code)
SH-081194ENG-A
(1D7MJ5)
SH-081195ENG-A
(1D7MJ6)
For detailed manuals, refer to the PDF manuals stored in the DVD-ROM for the drawing software used.
Relevant Manuals
For relevant manuals, refer to the Help or the PDF manuals stored in the DVD-
ROM for the drawing software used.
The latest manuals are also available from MITSUBISHI ELECTRIC FA Global
Website (http://www.MitsubishiElectric.co.jp/fa/).
© 2013MITSUBISHI ELECTRIC CORPORATION
Before using the GOT
Connect the connector of the GOT to the connector of the battery.
Refer to the GOT2000 Series User’s Manual (Hardware) for the connection instructions.
For details on the GOT specifications, installing instructions, wiring, maintenance and inspection, or checking procedure for the version and the compatible standard, refer to the GOT2000 Series User’s Manual (Hardware).
Packing List
The GOT product package includes the following:
Description
GT27
Battery (GT11-50BAT) (Attached to the GOT)
Installation fitting
GT27 General Description (This manual)
GT27 本体概要説明書
Quantity
1
1
4,
8(Only GT2715)
1
1
1. FEATURES
(1) Abundant standard equipment
• Variety of connection with FA devices
• SD card interface compatible with the SDHC card having a large capacity and allowing high-speed communication
• Connection with various peripheral devices with the USB host
(2) Improved usability
• Abundant troubleshooting
• Easy and clear screen creation
• PC-like operation screen
• Multi-touch function, Gesture function
(3) Enhanced compatibility with Mitsubishi FA devices
(4) Easy replacement]
(5) LED backlight
(6) External controllers including multimedia and video supported
(7) Various extended functions supported
2. Part Names and Settings
The following shows the part names for GT2715, GT2712, GT2710 and GT2708.
GT2715 1) 2) 7) 7) 7) 8) 9) 7)
6)
5)
3)4)
10)
11) 12)
7)
13)
14)
15)
16)
7) 7) 19) 18)
17)
7)
GT2712
23)
22)
21)
20)
1)2)
6)
5)
3)4)
7) 8) 7) 9)
10)
11)
12)
13)
14)
15)
16)
7) 19) 18) 17) 7)
24) 23) 22)21) 20)
GT2710
5)
3)4)
5)
3)4)
24)
GT2708
1)2)
23)22)21) 20)
1)2)
7)
7)
8) 7) 9)
10)
11)
12)
13)
14)
15)
16)
19) 18)
17)
7)
7) 8) 7) 9)
10)
11)12)13)
14)
15)
7) 19) 18) 7)
17)
16) 23)22)21) 20)
No.
1)
2)
3)
4)
5)
6)
7)
8)
9)
16)
17)
Name
Display screen
Touch Pane
USB interface
(Host/Front face)
USB interface (Device
/Front face)
POWER LED
Human sensor
Unit installation fitting
Reset switch
Installation switch
10) SD card access LED
11) SD card interface
12) SD card cover
13) Battery holder
14) Side interface
15)
USB interface
(Host/Back face)
Hole for attaching a cable clamp
Terminating resistor setting switch
(Inside cover)
Description
Displays the utility and the user-created screen.
For operating the touch switches in the utility and the usercreated screen
For connecting a USB mouse, connecting a USB keyboard, data transfer, and data storage
(connector type: TYPE-A)
(Only GT2715-XTBA/D, GT2712-STBA/D, GT2710-STBA/
D, GT2710-VTBA/D, GT2708-STBA/D, GT2708-VTBA/D)
For connecting a personal computer (connector type: Mini-
B)
(Only GT2715-XTBA/D, GT2712-STBA/D, GT2710-STBA/
D, GT2710-VTBA/D, GT2708-STBA/D, GT2708-VTBA/D)
Lit in blue
Lit in orange
: Power is properly supplied.
: Screen saving
Blinks in orange/blue : Backlight failure
Not lit : Power is not supplied
Detects human movement.(Only GT2715, GT2712)
Mounting fixtures for fixing the GOT to the control panel
Hardware reset switch
Used for OS installations at the GOT startup
Lit: SD card mounted
Blinking: SC card accessed
No lit: SD card not mounted or SD card mounted
(removable)
For installing a SD card
With a switching function for accepting and stopping the access to the SD card
When the cover is opened : Access is prohibited
When the cover is closed : Access is allowed
Houses the battery
For installing a communication unit
For connecting a USB mouse, connecting a USB keyboard, data transfer, and data storage
(connector type: TYPE-A)
Hole for attaching a cable clamp for preventing USB cable from being pulled out
(Recommended product: RSG-130-V0 made by
KITAGAWA INDUSTRIES CO.,LTD)
For switching on and off of the terminating resistor for the
RS-422/485 communication port (Default (Off))
19) Extension interface
20) Power terminal
21) Ethernet interface
22) RS-232 interface
23) RS-422/485 interface
24)
USB interface (Device/
Back face)
For installing an option unit
For installing a communication unit or an option unit
Power input terminal, LG terminal, FG terminal
For communicating with a controller or connecting a personal computer (connector type: RJ-45 (modular jack))
For communicating with a controller (Connector type: D sub
9-pin (male))
For communicating with a controller (Connector type: D sub
9-pin (female))
For connecting personal computers (connector type: Mini-B)
(Only GT2712-STWA/D,GT2710-VTWA/D)
3. Specifications
3.1 General Specifications
Item
Operating ambient temperature *1
Température ambiante de fonctionnement *1
Storage ambient temperature
Operating ambient humidity
Storage ambient humidity
Vibration resistance
Shock resistance
Operating atmosphere
Operating altitude *3
Installation location
Overvoltage category *4
Pollution degree *5
Cooling method
Grounding
Specifications
0 to 55
0 à 55
-20 to 60
*2
*2
10 to 90% RH, non-condensing
10 to 90% RH, non-condensing
Frequency Acceleration
Halfamplitude
Sweep count
Complian t with JIS
B 3502 and IEC
61131-2
Under intermitten t vibration
Under continuou s vibration
5 to 8.4Hz
8.4 to150Hz
5 to 8.4Hz
8.4 to 150Hz
-
9.8m/s
-
4.9m/s
2
2
3.5mm
-
-
1.75mm
10 times each in X,
Y and Z directions
-
Compliant with JIS B 3502 and IEC 61131-2 147 m/s
3 times each in X, Y and Z directions
2 (15G),
No greasy fumes, corrosive gas, flammable gas, excessive conductive dust, and direct sunlight (Same as storage atmosphere)
2000 m (6562 ft) max.
Inside control panel
II or less
2 or less
Self-cooling
Type D grounding (100Ω or less).
Connect to panel if unable to ground.
*1: The operating ambient temperature includes the temperature inside the enclosure of the control panel to which the GOT is installed.
La température ambiante de fonctionnement inclut la température à l'intérieur du boîtier du tableau de commande sur lequel le GOT est installé.
*2: When mounting a multimedia unit (GT27-MMR-Z), MELSECNET/H communication unit (GT15-J71LP23-25, GT15-J71BR13), or CC-Link communication unit (GT15-J61BT13), the operating ambient temperature must be reduced 5 against the maximum values described in general specifications.
Lors du montage d'un module multimédia (GT27-MMR-Z), du module de communication MELSECNET/H (GT15-J71LP23-25, GT15-J71BR13) ou du module de communication CC-Link (GT15-J61BT13), la température ambiante de fonctionnement doit être réduite de 5 par rapport aux valeurs maximales décrites dans les spécifications générales.
*3: Do not use or store the GOT under pressure higher than the atmospheric pressure of altitude 0m (0ft.).
Failure to observe this instruction may cause a malfunction.
When an air purge is made inside the control panel by adding pressure, there may be a clearance between the surface sheet and the screen making it difficult to use the touch panel, or the sheet may come off.
*4: This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within the premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities.
The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V.
*5: This index indicates the degree to which conductive material is generated in the environment where the equipment is used.
In pollution degree 2, only non-conductive pollution occurs but temporary conductivity may be produced due to condensation.
Point
Refer to the GOT2000 Series User’s Manual (Hardware) for details on the performance specifications of each GOT.
3.2 Power Supply Specifications
The following indicates the power supply specifications for GT27 .
Note
Operation at momentary failure
• If an instantaneous power failure occurs in the power supply and continues for more than the permissible period, the GOT will be reset.
• Make sure to power on the unit more than 5 seconds after power-off.
3.2.1 For GOTs powered from the 100 to 240VAC power supply
Item
Power supply voltage
Power frequency
Max. apparent power maximum load
Power consum ption
Stand alone
Stand alone with backlight off
GT2715-XTBA
Specifications
GT2712-
STBA
GT2712-
STWA
GT2710-
STBA
GT2710-
VTBA
GT2710-
VTWA
GT2708-
STBA
GT2708-
VTBA
AC100 to 240VAC (+10%, -15%)
50/60Hz 5%
140VA
51W or less
25W
44W or less
19W
100VA
41W or less
17W 15W
10W
Inrush current
40A or less (3ms, operating ambient temperature 25, maximum load)
60A or less (2ms, operating ambient temperature 25, maximum load)
Allowable momentary power failure time
20 ms or less (100VAC or more)
Noise immunity
Dielectric withstand voltage
Insulation resistance
Applicable wire size
Applicable solderless terminal
Applicable tightening torque
(Terminal block terminal screw)
1,500Vp-p noise voltage, 1 s noise width (when measuring with a noise simulator under 25 to 60Hz noise frequency)
1500VAC for 1 minute across power terminals and earth
10M or more across power terminals and earth by a
500V DC insulation resistance tester
0.75[mm 2 ] to 2[mm 2 ]
Solderless terminal for M3 screw RAV1.25-3, V2-S3.3,
V2-N3A, FV2-N3A
0.5[N•m] to 0.8[N•m]
3.2.2 For GOTs powered from the 24VDC power supply
Item
Power supply voltage maximum load
Power consum ption
Stand alone
Stand alone with backlight off
GT2715-
XTBD
Specifications
GT2712-
STBD,
GT2712-
STWD
GT2710-
STBD,
GT2710-
VTBD,
GT2710-
VTWD
GT2708-
STBD,
GT2708-
VTBD
DC24V (+25%, -20%)
48W or less 45W or less 42W or less 39W or less
23W 18W 15W 13W
8W
Inrush current
5A or less (20ms, operating ambient temperature 25, maximum load)
Allowable momentary power failure time
10 ms or less
Noise immunity
Dielectric withstand voltage
Insulation resistance
Applicable wire size
Applicable solderless terminal
500Vp-p noise voltage, 1 s noise width (when measuring with a noise simulator under 25 to 60Hz noise frequency)
350VAC for 1 minute across power terminals and earth
10M or more across power terminals and earth by a
500V DC insulation resistance tester
0.75[mm 2 ] to 2[mm 2 ]
Solderless terminal for M3 screw RAV1.25-3, V2-S3.3,
V2-N3A, FV2-N3A
Applicable tightening torque
(Terminal block terminal screw)
0.5[N•m] to 0.8[N•m]
3.3 External Dimensions
GT2715 GT2712
397(15.63)
322(12.68)
316 (12.44)
241 (9.49)
10
(0.39)
GT2710
322(12.68)
382(15.04)
303 (11.93)
208 (8.19)
10
(0.39)
GT2708
241 (9.49)
301 (11.85)
241 (9.49)
166 (6.54) 37.5
(1.48)
228 (8.98)
288 (11.34)
171.6
(6.76)
37.5
(1.48)
226 (8.90)
Unit : mm (inch)
4. EMC AND LOW VOLTAGE DIRECTIVE
For the products sold in European countries, the conformance to the
EMC Directive, which is one of the European Directives, has been a legal obligation since 1996. Also, conformance to the Low Voltage.
Directive, another European Directives, has been a legal obligation since
1997.
Manufacturers who recognize their products must conform to the EMC and Low Voltage Directive are required to declare that their products conform to these Directives and put a "CE mark" on their products.
• Authorized representative in Europe
Authorized representative in Europe is shown below.
Name :Mitsubishi Electric Europe BV
Address :Gothaer strase 8, 40880 Ratingen, Germany
4.1 Requirements to Meet EMC Directive
EMC Directives are those which require "any strong electromagnetic force is not output to the external.:Emission (electromagnetic interference)" and "It is not influenced by the electromagnetic wave from the external.: Immunity (electromagnetic sensitivity)".
Items4.1.1 through4.1.3 summarize the precautions to use GOT and
configure the mechanical unit in order to match the EMC directives.
Though the data described herein are produced with our best on the basis of the requirement items and standards of the restrictions gathered by Mitsubishi, they do not completely guaranteed that all mechanical unit manufactured according to the data do not always match the above.
4.1.1 EMC directive
The standards of the EMC Directive are shown below.
Applied standard
Test standard Test details Standard value
EN61131-2
: 2007
CISPR16-2-3
Radiated noise
*1
CISPR16-2-1
Conducted noise *1
IEC61000-4-2
Electrostatic immunity *1
IEC61000-4-3
Radiated electromagnetic field AM modulation
IEC61000-4-4
Fast transient burst noise *1
IEC61000-4-5
Surge immunity
*1
Electromagnetic emissions from the product are measured.
Electromagnetic emissions from the product to the power line is measured.
Immunity test in which static electricity is applied to the cabinet of the equipment.
Immunity test in which field is irradiated to the product.
Immunity test in which burst noise is applied to the power line and signal lines.
Immunity test in which lightening surge is applied to the product.
30M-230MHz QP:
30dB V/m (30m in measurement range) *2, *3
230M-1000MHz QP:
37dB V/m(30m in measurement range) *2, *3
150k-500kHz QP:79dB,
Mean: 66dB *2
500k-30MHz QP:73dB,
Mean: 60dB
*2
4kV Contact discharge
8kV Aerial discharge
80-1000MHz:10V/m
1.4-2GHz:3V/m
2.0-2.7GHz:1V/m
80%AM modulation@1kHz
Power line:2kV
Digital I/O(24V or higher): 1kV
(Digital I/O(24V or less))> 250V
(Analog I/O, signal lines)> 250V
AC power type
Power line (between line and ground): 2kV
Power line (between lines)
: 1kV
Data communication port
: 1kV
DC power type
Power line (between line and ground) : 0.5kV
Power line (between lines)
: 0.5kV
Data communication port
: 1kV
IEC61000-4-6
Conducted RF immunity
*1
IEC61000-4-8
Power supply frequency magnetic field immunity
Immunity test in which a noise inducted on the power and signal lines is applied.
Test for checking normal operations under the circumstance exposed to the ferromagnetic field noise of the power supply frequency
(50/60Hz).
Power line: 10V
Data communication port: 10V
30 A/m
IEC61000-4-11
Instantaneous power failure and voltage dips immunity
Test for checking normal operations at instantaneous power failure.
AC power type
0.5 cycle 0% (interval 1 to 10s)
250/300 cycle 0%
10/12 cycle 40%
25/30 cycle 70%
*1: The GOT is an open type device (device installed to another device) and must be installed in a conductive control panel.
The above test items are conducted in the condition where the GOT is installed on the conductive control panel and combined with the Mitsubishi PLC.
*2: QP (Quasi-Peak): Quasi-peak value, Mean: Average value
*3: The above test items are conducted in the following conditions.
30M-230MHz QP : 40dB V/m (10m in measurement range)
230M-1000MHz QP : 47dB V/m (10m in measurement range)
4.1.2 Control panel
The GOT is an open type device (device installed to another device) and must be installed in a conductive control panel.
It not only assure the safety but also has a large effect to shut down the noise generated from GOT, on the control panel.
(1) Control Panel
(a) The control panel must be conductive.
(b) When fixing a top or bottom plate of the control panel with bolts, do not coat the plate and bolt surfaces so that they will come into contact.
And connect the door and box using a thick grounding cable in order to ensure the low impedance under high frequency.
(c) When using an inner plate to ensure electric conductivity with the control panel, do not coat the fixing bolt area of the inner plate and control panel to ensure conductivity in the largest area as possible.
(d) Ground the control panel using a thick grounding cable in order to ensure the low impedance under high frequency.
(e) The diameter of cable holes in the control panel must be 10cm
(3.94in.). In order to reduce the chance of radio waves leaking out, ensure that the space between the control panel and its door is small as possible.
Paste the EMI gasket directly on the painted surface to seal the space so that the leak of electric wave can be suppressed.
Our test has been carried out on a panel having the damping characteristics of 37dB max. and 30dB mean (measured by 3m method with 30 to 300MHz).
(2) Connection of power and ground wires
Ground and power supply wires for the GOT must be connected as described below.
(a) Provide a grounding point near the GOT. Short-circuit the LG and
FG terminals of the GOT (LG: line ground, FG: frame ground) and ground them with the thickest and shortest wire possible
(The wire length must be 30cm (11.81in.) or shorter.)
The LG and FG terminals function is to pass the noise generated in the PC system to the ground, so an impedance that is as low as possible must be ensured. As the wires are used to relieve the noise, the wire itself carries a large noise content and thus short wiring means that the wire is prevented from acting as an antenna.
Note) A long conductor will become a more efficient antenna at high frequency.
(b) The earth wire led from the earthing point must be twisted with the power supply wires.
By twisting with the earthing wire, noise flowing from the power supply wires can be relieved to the earthing. However, if a filter is installed on the power supply wires, the wires and the earthing wire may not need to be twisted.
4.1.3 Noise filter (power supply line filter)
The noise filter (power supply line filter) is a device effective to reduce conducted noise. Except some models, installation of a noise filter onto the power supply lines is not necessary. However conducted noise can be reduced if it is installed. (The noise filter is generally effective for reducing conducted noise in the band of 10MHz or less.) Usage of the following filters is recommended.
Model name
Manufacturer
Rated current
Rated voltage
FN343-3/05
SCHAFFNER
3A
FN660-6/06
SCHAFFNER
6A
250V
RSHN-2003
TDK
3A
The precautions required when installing a noise filter are described below.
(1) Do not install the input and output cables of the noise filter together to prevent the output side noise will be inducted into the input side cable where noise has been eliminated by the noise filer.
Input side
(power supply side)
Input side
(power supply side)
Induction
Filter Filter
Output side
(device side)
Output side
(device side)
• Installing the input and output cables together will cause noise induction.
• Separate the input cable from the output cable.
(2) Connect the noise filter's ground terminal to the control panel with the shortest cable as possible (approx. 10cm (3.94 in.) or less).
4.2 Requirements for Compliance with the Low
Voltage Directive
The Low Voltage Directive requires each device which operates with power supply ranging from 50VAC to 1000V and 75VDC to 1500V to satisfy necessary safety items.
In the Sections from 4.2.1 to 4.2.5, cautions on installation and wiring of
the GOT to conform to the Low Voltage Directive requires are described.
We have put the maximum effort to develop this material based on the requirements and standards of the Directive that we have collected.
However, compatibility of the devices which are fabricated according to the contents of this manual to the above Directive is not guaranteed.
Each manufacturer who fabricates such device should make the final judgement about the application method of the Low Voltage Directive and the product compatibility.
4.2.1 Standard subject to GOT
Standard applied to GOT : EN61131-2 Programmable controllers - Equipment requirements and tests
EN60950-1 Safety of Information Technology Equipment
4.2.2 Power supply
The insulation specification of the GOT was designed assuming installation category II. Be sure to use the installation category II power supply to the GOT.
The installation category indicates the durability level against surge voltage generated by lightning strike.
Category I has the lowest durability; category IV has the highest durability.
Category IV Category III Category II Category I
Installation category
Category II indicates a power supply whose voltage has been reduced by two or more levels of isolating transformers from the public power distribution.
4.2.3 Control panel
Because the GOT is open type equipment (device designed to be stored within another device), be sure to use it only when installed in a control panel.
(1) Shock Protection
In order to prevent those who are unfamiliar with power facility, e.g., an operator, from getting a shock, make sure to take the following measures on the control panel.
(a) Store the GOT within the control panel locked, and allow only those who are familiar with power facility to unlock the panel.
(b) Build the structure in order that the power supply will be shut off when the control panel is opened.
(2) Dustproof and waterproof features
The control panel also provides protection from dust, water and other substances. Insufficient ingression protection may lower the insulation withstand voltage, resulting in insulation destruction.
The insulation in the GOT is designed to cope with the pollution level 2, so use in an environment with pollustion level 2 or better.
Pollution level 1: An environment where the air is dry and conductive dust does not exist.
Pollution level 2: An environment where conductive dust does not usually exist, but occasional temporary conductivity occurs due to the accumulated dust.
Generally, this is the level for inside the control panel equivalent a control room or on the floor of a typical factory.
Pollution level 3: An environment where conductive dust exits and conductivity may be generated due to the accumulated dust.
An environment for a typical factory floor.
Pollution level 4: Continuous conductivity may occur due to rain, snow, etc. An outdoor environment.
4.2.4 Grounding
The following are applicable ground terminals. Use them in the grounded state.
Be sure to ground the GOT for ensuring the safety and complying with the EMC Directive.
Functional grounding : Improves the noise resistance.
4.2.5 External wiring
(1) External devices
When a device with a hazardous voltage circuit is externally connected to the GOT, select a model which complies with the
Low Voltage Directive's requirements for isolation between the primary and secondary circuits.
(2) Insulation requirements
Dielectric withstand voltages are shown in the following table.
Reinforced Insulation Withstand Voltage
(Installation Category II, source : IEC664)
Rated voltage of hazardous voltage area
150 VAC or below
300 VAC or below
2500V
4000V
Surge withstand voltage (1.2/50 s)
5. INSTALLATION
5.1 Control Panel Inside Dimensions for
Mounting GOT
Install the GOT on the control panel out of the way for the equipment inside the control panel. Do not install the GOT and the unit in prohibited areas for the installation.
Point
Applicable cable
Some cables may need to be longer than the specified dimensions when connecting to the
GOT. Therefore, consider the connector dimensions and bending radius of the cable as well for installation.
5.2 Panel Cutting Dimensions
A
*Panel thickness : 1.6 to 4 mm
(0.06 to 0.16 inch)
GOT
GT2715
A
383.5 (15.10)
+2 (0.08)
0 (0)
B
282.5 (11.12)
+2 (0.08)
0 (0)
GT2712
GT2710
GT2708
302 (11.89)
+2 (0.08)
0 (0)
289 (11.38)
+2 (0.08)
0 (0)
227 (8.94)
+2 (0.08)
0 (0)
228 (8.98)
+2 (0.08)
0 (0)
200 (7.87)
+2 (0.08)
0 (0)
176 (6.93)
+2 (0.08)
0 (0)
Unit: mm (inch)
5.3 Mounting Position
When mounting the GOT, the following clearances must be maintained from other structures and devices.
Some cables may need to be longer than the specified dimensions when connecting to the GOT.
Therefore, consider the connector dimensions and bending radius of the cable as well for installation.
For the lead-in allowance for cables at the bottom of the GOT, refer to the GOT2000 Series User’s Manual (Hardware) .
C D E
Panel thickness: 1.6 to 4mm
(0.06 to 0.16 inch)
According to the dimensions in the following table, leave clearances between the GOT and the other devices. The values enclosed in square brackets apply to the case where no other equipment generating radiated noise (such as a contactor) or heat is installed near the GOT. However, keep the ambient temperature of the GOT to 55°C or lower.
Serial connection unit is fitted
CC-Link communication unit
(GT15-J61BT13) fitted
MELSECNET/H communication unit (coaxial) fitted
*1
MELSECNET/H communication
unit(optical) fitted *2
CC-Link IE Controller Network communication unit fitted
CC-Link IE Field Network communication unit fitted
A
Video input unit fitted
*1
B
C
D
E*4
GOT only
Item
Bus connection unit is fitted
RGB input unit fitted *3
Video/RGB input unit fitted
*1*3
RGB output unit fitted *3
Multimedia unit fitted
*1
Printer unit fitted
External I/O unit fitted
Sound output unit fitted
When the SD card is used
When the SD card is not used
GT2715 GT2712
Unit : mm(inch)
GT2710 GT2708
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[18(0.71) or more]
23(0.91) or more
[29(1.14) or more]
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[38(1.50) or more]
48(1.89) or more
[45(1.77) or more]
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[38(1.50) or more]
48(1.89) or more
[45(1.77) or more]
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[38(1.50) or more]
48(1.89) or more
[45(1.77) or more]
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[38(1.50) or more]
48(1.89) or more
[45(1.77) or more]
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[18(0.71) or more]
78(3.07) or more
[18(0.71) or more]
50(1.97)or more
[20(0.79) or more]
50(1.97) or more
[20(0.79) or more]
50(1.97) or more
[20(0.79) or more]
100(3.94) or more
[20(0.79) or more]
67(2.64) or more
67(2.64) or more
67(2.64) or more
67(2.64) or more
50(1.97) or more
*1: This value is for use of the coaxial cable 3C-2V (JIS C 3501).
For specifications of the cable, refer to the GOT2000 Series Connection
Manual for a controller used.
*2: This value differs depending on the cable used.
*3: This value differs depending on the cable used.
If the bending radius of the cable used is greater than the value specified above, apply the value of the cable used.
*4: When opening or closing the battery cover: 72(2.83) or more
5.4 Control Panel Inside Temperature and
Installation Angle
When installing the GOT to a panel, set the display section as shown below.Using the GOT with the installation angle other than the following deteriorates the GOT earlier.
When installing the GOT with the installation angle between 60 to 105
°, the temperature inside the control panel must be within 55 °C.
When installing the GOT with the installation angle other than between
60 to 105 °, the temperature inside the control panel must be within 40
°C.
Display section
GOT
105°
60°
Panel or others
5. INSTALLATION
5.1 Dimensions intérieures du tableau de commande pour le montage du GOT
Installez le GOT sur le tableau de commande en laissant de l'espace pour le dispositif à l'intérieur du tableau de commande. N'installez pas le GOT et le module dans des zones où l'installation est interdite.
Point
Câble applicable
Certains câbles peuvent être plus longs que les dimensions spécifiées lors de la connexion au GOT. Par conséquent, prenez également en compte les dimensions du connecteur et le rayon de courbure du câble pour l'installation.
5.2 Cotes de découpe du panneau
A
*Épaisseur du panneau : 1,6 à 4mm
(0,06 à 0,16 pouce)
GOT
GT2715
GT2712
A B
383,5 (15,10) 282,5 (11,12)
+2 (0,08)
0 (0)
+2 (0,08)
0 (0)
302 (11,89)
+2 (0,08)
0 (0)
228 (8,98)
+2 (0,08)
0 (0)
GT2710
GT2708
289 (11,38)
+2 (0,08)
0 (0)
227 (8,94)
+2 (0,08)
0 (0)
200 (7,87)
+2 (0,08)
0 (0)
176 (6,93)
+2 (0,08)
0 (0)
Unité : mm (pouce)
5.3 Position de montage
Lors du montage du GOT, laissez les espaces suivants pour les autres structures et dispositifs.
Certains câbles peuvent être plus longs que les dimensions spécifiées lors de la connexion au GOT.
Par conséquent, prenez également en compte les dimensions du connecteur et le rayon de courbure du câble pour l'installation.
Pour connaître l'espace à laisser pour les câbles sous le GOT, référezvous au manuel GOT2000 Series User’s Manual (Hardware).
C D E
Épaisseur du panneau : 1,6 à 4mm
(0,06 à 0,16 pouce)
Laissez les espaces entre le GOT et les autres dispositifs en fonction des dimensions contenues dans le tableau suivant. Les valeurs entre parenthèses s'appliquent au cas où aucun dispositif générant des
émissions sonores (comme un contacteur) ou de la chaleur n'est installé près du GOT.
Toutefois, maintenez la température ambiante du GOT à 55°C ou moins.
Unité : mm (pouce)
Article GT2715 GT2712 GT2710 GT2708
GOT uniquement
48 (1,89) ou plus
[18 (0,71) ou plus]
Unité de connexion de bus encastrée
48 (1,89) ou plus
[18 (0,71) ou plus]
23 (0,91) ou plus
[29 (1,14) ou plus]
A
Unité de connexion série encastrée
Module de communication CC-
Link (GT15-J61BT13) encastré
Module de communication
MELSECNET/H (coaxial) encastré *1
48(1,89) or more
[18(0,71) or more]
48 (1,89) ou plus
[18 (0,71) ou plus]
48 (1,89) ou plus
[18 (0,71) ou plus]
48 (1,89) ou plus
[38 (1,50) ou plus]
48 (1,89) ou plus
[45 (1,77) ou plus]
67 (2,64) ou plus
Module de communication
MELSECNET/H (optique) encastré *2
Module de communication réseau de contrôleur CC-Link IE encastré
Module de communication réseau de champ CC-Link IE encastré
48 (1,89) ou plus
[18 (0,71) ou plus]
48 (1,89) ou plus
[18 (0,71) ou plus]
48 (1,89) ou plus
[18 (0,71) ou plus]
A
B
C
D
Article
Module d'entrée vidéo encastré *1
Module d'entrée RGB encastré
*3
Module d'entrée vidéo/RGB encastré *1*3
Module de sortie RGB encastré
*3
Module multimédia encastré *1
Imprimante encastrée
Module d'E/S externe encastré
Module de sortie acoustique encastré
Quand la carte SD est utilisée
Quand la carte SD n'est pas utilisée
E*4
GT2715 GT2712
48(1,89) or more
[18(0,71) or more]
48 (1,89) ou plus
[38 (1,50) ou plus]
48(1,89) or more
[18(0,71) or more]
48(1,89) or more
[18(0,71) or more]
GT2710
48 (1,89) ou plus
[45 (1,77) ou plus]
48 (1,89) ou plus
[18 (0,71) ou plus]
48 (1,89) ou plus
[38 (1,50) ou plus]
48 (1,89) ou plus
[45 (1,77) ou plus]
48 (1,89) ou plus
[18 (0,71) ou plus]
48 (1,89) ou plus
[38 (1,50) ou plus]
48 (1,89) ou plus
[45 (1,77) ou plus]
48 (1,89) ou plus
[18 (0,71) ou plus]
48 (1,89) ou plus
[18 (0,71) ou plus]
48 (1,89) ou plus
[18 (0,71) ou plus]
78 (3,07) ou plus
[18 (0,71) ou plus]
50 (1,97) ou plus
[20 (0,79) ou plus]
50 (1,97) ou plus
[20 (0,79) ou plus]
50 (1,97) ou plus
[20 (0,79) ou plus]
100 (3,94) ou plus
[20 (0,79) ou plus]
GT2708
67 (2,64) ou plus
67 (2,64) ou plus
67 (2,64) ou plus
50 (1,97) ou plus
*1 : Cette valeur est utilisée pour le câble coaxial 3C-2V (JIS C 3501).
Pour connaître les spécifications du câble, référez-vous au manuel
GOT2000 Series Connection Manual for a controller used.
*2 : Cette valeur diffère selon le câble utilisé.
*3 : Cette valeur diffère selon le câble utilisé.
Si le rayon de courbure du câble utilisé est supérieur à la valeur spécifiée ci-dessus, appliquez la valeur du câble utilisé.
*4 : Pour ouvrir ou fermer le couvercle de la batterie : 72 (2,83) ou plus
5.4 Température intérieure et angle d'installation du tableau de commande
Lors de l'installation du GOT sur un panneau, réglez la zone d'affichage comme indiqué ci-dessous.
Si l'angle d'installation est différent de celui indiqué, le GOT se détériore plus tôt.
Lors de l'installation du GOT avec un angle d'installation compris entre
60 et 105°, la température à l'intérieur du tableau de commande doit
être d'environ 55°C.
Lors de l'installation du GOT avec un angle d'installation non compris entre 60 et 105°, la température à l'intérieur du tableau de commande doit être d'environ 40°C.
Zone d'affichage
GOT
105°
60°
Tableau ou autres
6. MAINTENANCE AND INSPECTION
Refer to the GOT2000 Series User’s Manual (Hardware) for maintenance and inspection for the GOT.
Warranty
Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi products; damage, secondary damage, accident compensation caused by special factors unpredictable by Mitsubishi; damages to products other than
Mitsubishi products; and to other duties.
For safe use
• This product has been manufactured as a general-purpose part for general industries, and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life.
• Before using the product for special purposes such as nuclear power, electric power, aerospace, medicine or passenger movement vehicles, consult with Mitsubishi.
• This product has been manufactured under strict quality control.
However, when installing the product where major accidents or losses could occur if the product fails, install appropriate backup or failsafe functions in the system.
Country/Region Sales office/Tel
U.S.A
Brazil
Germany
U.K
Italy
Spain
France
Mitsubishi Electric Automation Inc.
500 Corporate Woods Parkway Vernon Hills, IL 60061, U.S.A.
Tel : +1-847-478-2100
MELCO-TEC Rep. Com.e Assessoria Tecnica Ltda.
Rua Correia Dias, 184, Edificio Paraiso Trade Center-8 andar
Paraiso, Sao Paulo, SP Brazil
Tel : +55-11-5908-8331
Mitsubishi Electric Europe B.V. German Branch
Gothaer Strasse 8 D-40880 Ratingen, GERMANY
Tel : +49-2102-486-0
Mitsubishi Electric Europe B.V. UK Branch
Travellers Lane, Hatfield, Hertfordshire., AL10 8XB, U.K.
Tel : +44-1707-276100
Mitsubishi Electric Europe B.V. Italian Branch
Centro Dir. Colleoni, Pal. Perseo-Ingr.2
Via Paracelso 12, I-20041 Agrate Brianza., Milano, Italy
Tel : +39-039-60531
Mitsubishi Electric Europe B.V. Spanish Branch
Carretera de Rubi 76-80,
E-08190 Sant Cugat del Valles, Barcelona, Spain
Tel : +34-93-565-3131
Mitsubishi Electric Europe B.V. French Branch
South Africa
Hong Kong
China
25, Boulevard des Bouvets, F-92741 Nanterre Cedex, France
Tel : +33-1-5568-5568
Circuit Breaker Industries Ltd.
Private Bag 2016, ZA-1600 Isando, South Africa
Tel : +27-11-928-2000
Mitsubishi Electric Automation (Hong Kong) Ltd.
10th Floor, Manulife Tower, 169 Electric
Road, North Point, Hong Kong
Tel : +852-2887-8870
Mitsubishi Electric Automation (China) Ltd.
Taiwan
4/F Zhi Fu Plazz, No.80 Xin Chang Road,
Shanghai 200003, China
Tel : +86-21-6120-0808
Setsuyo Enterprise Co., Ltd.
6F No.105 Wu-Kung 3rd.Rd, Wu-Ku Hsiang,
Korea
Taipei Hsine, Taiwan
Tel : +886-2-2299-2499
Mitsubishi Electric Automation Korea Co., Ltd.
1480-6, Gayang-dong, Gangseo-ku Seoul
Korea
Singapore
Thailand
Indonesia
Tel : +82-2-3660-9552
Mitsubishi Electric Asia Pte, Ltd.
307 Alexandra Road #05-01/02,
Mitsubishi Electric Building, Singapore 159943
Tel : +65-6470-2460
Mitsubishi Electric Automation (Thailand) Co., Ltd.
Bang-Chan Industrial Estate No.111 Moo 4, Serithai Rd,
T.Kannayao, A.Kannayao, Bangkok 10230 Thailand
Tel : +66-2-517-1326
P.T. Autoteknindo Sumber Makmur
India
Muara Karang Selatan, Block A/Utara
No.1 Kav. No.11 Kawasan Industri Pergudangan
Jakarta - Utara 14440, P.O.Box 5045 Jakarta, 11050 Indonesia
Tel : +62-21-6630833
Messung Systems Pvt, Ltd.
Electronic Sadan NO:III Unit No15, M.I.D.C Bhosari,
India
Tel : +91-20-2712-3130
Australia Mitsubishi Electric Australia Pty. Ltd.
348 Victoria Road, Rydalmere, N.S.W 2116, Australia
Tel : +61-2-9684-7777
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
NAGOYA WORKS : 1-14, YADA-MINAMI 5-CHOME, HIGASHI-KU, NAGOYA, JAPAN
When exported from Japan, this manual does not require application to the Ministry of Economy, Trade and Industry for service transaction permission.
Specifications subject to change without notice.
Printed in Japan, April 2014.