GT27 General Description

Add to my manuals
2 Pages

advertisement

GT27 General Description | Manualzz

GT27 General Description

GT2715-XTBA

GT2712-STBD

GT2710-VTBA

GT2708-STBA

GT2715-XTBD

GT2712-STWD

GT2710-VTWA

GT2708-STBD

GT2712-STBA

GT2710-STBA

GT2710-VTBD

GT2708-VTBA

Thank you for purchasing the GOT2000 Series.

GT2712-STWA

GT2710-STBD

GT2710-VTWD

GT2708-VTBD

Prior to use, please read both this manual and the detailed manual thoroughly to fully understand the product.

MODEL

Model code

GT27-U-GD-E

1D7MI3

IB(NA)-0800502ENG-D(1404)MEE

 SAFETY PRECAUTIONS

(Always read these precautions before using this equipment.)

Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay full attention to safety to handle the product correctly.

The precautions given in this manual are concerned with this product.

In this manual, the safety precautions are ranked as "WARNING" and "CAUTION".

WARNING

CAUTION

Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.

Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight personal injury or physical damage.

Note that the CAUTION level may lead to a serious accident according to the circumstances.

Always follow the instructions of both levels because they are important to personal safety.

Please save this manual to make it accessible when required and always forward it to the end user.

[DESIGN PRECAUTIONS]

WARNING

 Some failures of the GOT, communication unit or cable may keep the outputs on or off.

Some failures of a touch panel may cause malfunction of the input objects such as a touch switch.

An external monitoring circuit should be provided to check for output signals which may lead to a serious accident.

Not doing so can cause an accident due to false output or malfunction.

 Do not use the GOT as the warning device that may cause a serious accident.

An independent and redundant hardware or mechanical interlock is required to configure the device that displays and outputs serious warning.

Failure to observe this instruction may result in an accident due to incorrect output or malfunction.

 The GOT backlight failure disables the operation on the touch switch(s).

When the GOT backlight has a failure, the POWER LED blinks (orange/blue) and the display section dims. In such a case, the input by the touch switch(s) is disabled.

 The display section of the GOT is an analog-resistive type touch panel. The

GOT is multi-touch compliant; however, do not touch three points or more simultaneously on the display section. Doing so may cause an accident due to incorrect output or malfunction.

 When programs or parameters of the controller (such as a PLC) that is monitored by the GOT are changed, be sure to reset the GOT, or turn on the unit again after shutting off the power as soon as possible.

Not doing so can cause an accident due to false output or malfunction.

 If a communication fault (including cable disconnection) occurs during monitoring on the GOT, communication between the GOT and PLC CPU is suspended and the GOT becomes inoperative.

For bus connection : The CPU becomes faulty and the GOT becomes inoperative.

For other than bus connection : The GOT becomes inoperative.

A system where the GOT is used should be configured to perform any significant operation to the system by using the switches of a device other than the GOT on the assumption that a GOT communication fault will occur.

Not doing so can cause an accident due to false output or malfunction.

7

8

5

6

9

0

3

4

1

2

7

8

5

6

9

0

3

4

1

2

[DESIGN PRECAUTIONS]

CAUTION

 Do not bundle the control and communication cables with main-circuit, power or other wiring.

Run the above cables separately from such wiring and keep them a minimum of 100mm apart.

Not doing so noise can cause a malfunction.

 Do not press the GOT display section with a pointed material as a pen or driver.

Doing so can result in a damage or failure of the display section.

 When the GOT is connected to the Ethernet network, the available IP address is restricted according to the system configuration.

• When multiple GOTs are connected to the Ethernet network :

Do not set the IP address (192.168.3.18) for the GOTs and the controllers in

the network.

• When a single GOT is connected to the Ethernet network :

Do not set the IP address (192.168.3.18) for the controllers except the GOT

in the network.

Doing so can cause the IP address duplication. The duplication can negatively affect the communication of the device with the IP address

(192.168.3.18).

The operation at the IP address duplication depends on the devices and the system.

 Turn on the controllers and the network devices to be ready for communication before they communicate with the GOT.

Failure to do so can cause a communication error on the GOT.

 When the GOT is subject to shock or vibration, or some colors appear on the screen of the GOT, the screen of the GOT might flicker.

[MOUNTING PRECAUTIONS]

WARNING

 Be sure to shut off all phases of the external power supply used by the system before mounting or removing the GOT main unit to/from the panel.

Not doing so can cause the unit to fail or malfunction.

 Be sure to shut off all phases of the external power supply used by the system before mounting or removing the option unit onto/from the GOT.

CAUTION

 Use the GOT in the environment that satisfies the general specifications described in this manual.

Not doing so can cause an electric shock, fire, malfunction or product damage or deterioration.

 When mounting the GOT to the control panel, tighten the mounting screws in the specified torque range (0.36 N•m to 0.48 N•m) with a Phillips-head screwdriver No.2.

Undertightening can cause the GOT to drop, short circuit or malfunction.

Overtightening can cause a drop, short circuit or malfunction due to the damage of the screws or the GOT.

 When mounting a unit on the GOT, tighten the mounting screws in the following specified torque range.

When loading the communication unit or option unit other than wireless LAN unit to the GOT, fit it to the connection interface of the GOT and tighten the mounting screws in the specified torque range (0.36 N•m to 0.48 N•m) with a

Phillips-head screwdriver No.2.

When loading the wireless LAN unit to the GOT, fit it to the side interface of

GOT and tighten the mounting screws in the specified torque range (0.10

N•m to 0.14 N•m) with a Phillips-head screwdriver No.1.

Under tightening can cause the GOT to drop, short circuit or malfunction.

Overtightening can cause a drop, failure or malfunction due to the damage of the screws or unit.

 When closing the USB environmental protection cover, fix the cover to the

GOT by pushing the [PUSH] mark on the latch firmly to comply with the protective structure.

 Remove the protective film of the GOT.

When the user continues using the GOT with the protective film, the film may not be removed.In addition, for the models equipped with the human sensor function, using the GOT with the protective film may cause the human sensor not to function properly

 Operate and store the GOT in environments without direct sunlight, high temperature, dust, humidity, and vibrations.

 When using the GOT in the environment of oil or chemicals, use the protective cover for oil.Failure to do so may cause failure or malfunction due to the oil or chemical entering into the GOT.

[WIRING PRECAUTIONS]

WARNING

 Be sure to shut off all phases of the external power supply used by the system before wiring.

Failure to do so may result in an electric shock, product damage or malfunctions.

CAUTION

 Make sure to ground the FG terminal and LG terminal of the GOT power supply section to the protective ground conductors dedicated to the GOT with a ground resistance of 100 Ω or less.

 When tightening the terminal screws, use a Phillips-head screwdriver No.2.

 Terminal screws which are not to be used must be tightened always at torque

0.5 N•m to 0.8 N•m.

Otherwise there will be a danger of short circuit against the solderless terminals.

 Use applicable solderless terminals and tighten them with the specified torque. If any solderless spade terminal is used, it may be disconnected when the terminal screw comes loose, resulting in failure.

 Correctly wire the GOT power supply section after confirming the rated voltage and terminal arrangement of the product.

Not doing so can cause a fire or failure.

[WIRING PRECAUTIONS]

CAUTION

 Tighten the terminal screws of the GOT power supply section in the specified torque range (0.5 N•m to 0.8 N•m). Undertightening can cause a short circuit or malfunction.Overtightening can cause a short circuit or malfunction due to the damage of the screws or the GOT.

 Exercise care to avoid foreign matter such as chips and wire offcuts entering the GOT. Not doing so can cause a fire, failure or malfunction.

 The module has an ingress prevention label on its top to prevent foreign matter, such as wire offcuts, from entering the module during wiring.

Do not peel this label during wiring.Before starting system operation, be sure to peel this label because of heat dissipation.

 Plug the communication cable into the GOT interface or the connector of the connected unit, and tighten the mounting screws and the terminal screws in the specified torque range.Undertightening can cause a short circuit or malfunction.Overtightening can cause a short circuit or malfunction due to the damage of the screws or unit.

 Plug the QnA/ACPU/Motion controller(A series) bus connection cable by inserting it into the connector of the connected unit until it "clicks".

After plugging, check that it has been inserted snugly.

Not doing so can cause a malfunction due to a contact fault.

[TEST OPERATION PRECAUTIONS]

WARNING

 Before performing the test operations of the user creation monitor screen

(such as turning ON or OFF bit device, changing the word device current value, changing the settings or current values of the timer or counter, and changing the buffer memory current value), read through the manual carefully and make yourself familiar with the operation method.

During test operation, never change the data of the devices which are used to perform significant operation for the system.

False output or malfunction can cause an accident.

[STARTUP/MAINTENANCE PRECAUTIONS]

WARNING

 When power is on, do not touch the terminals.

Doing so can cause an electric shock or malfunction.

 Correctly connect the battery connector.Do not charge, disassemble, heat, short-circuit, solder, or throw the battery into the fire.Doing so will cause the battery to produce heat, explode, or ignite, resulting in injury and fire.

 Before starting cleaning or terminal screw retightening, always switch off the power externally in all phases.Not switching the power off in all phases can cause a unit failure or malfunction.Undertightening can cause a short circuit or malfunction.Overtightening can cause a short circuit or malfunction due to the damage of the screws or unit.

CAUTION

 Do not disassemble or modify the unit.

Doing so can cause a failure, malfunction, injury or fire.

 Do not touch the conductive and electronic parts of the unit directly.

Doing so can cause a unit malfunction or failure.

 The cables connected to the unit must be run in ducts or clamped.

Not doing so can cause the unit or cable to be damaged due to the dangling, motion or accidental pulling of the cables or can cause a malfunction due to a cable connection fault.

 When unplugging the cable connected to the unit, do not hold and pull from the cable portion.Doing so can cause the unit or cable to be damaged or can cause a malfunction due to a cable connection fault.

 Do not drop the module or subject it to strong shock. A module damage may result.

 Do not drop or give an impact to the battery mounted to the unit.

Doing so may damage the battery, causing the battery fluid to leak inside the battery.If the battery is dropped or given an impact, dispose of it without using.

 Before touching the unit, always touch grounded metals, etc. to discharge static electricity from human body, etc.

Not doing so can cause the unit to fail or malfunction.

 Use the battery manufactured by Mitsubishi Electric Corporation.

Use of other batteries may cause a risk of fire or explosion.

 Dispose of used battery promptly.

Keep away from children.Do not disassemble and do not dispose of in fire.

 Be sure to shut off all phases of the external power supply before replacing the battery or using the dip switch of the terminating resistor.Not doing so can cause the unit to fail or malfunction by static electricity.

[TOUCH PANEL PRECAUTIONS]

CAUTION

 For the analog-resistive film type touch panels, normally the adjustment is not required.

However, the difference between a touched position and the object position may occur as the period of use elapses.

When any difference between a touched position and the object position occurs, execute the touch panel calibration.

 When any difference between a touched position and the object position occurs, other object may be activated.

This may cause an unexpected operation due to incorrect output or malfunction.

[PRECAUTIONS WHEN THE DATA STORAGE IS IN

USE]

WARNING

 If the SD card mounted on drive A of the GOT is removed while the GOT is accessed, processing for the GOT might be interrupted about for 20 seconds.The GOT cannot be operated during this period. The functions that run in the background including a screen updating, alarm, logging, scripts, and others are also interrupted.Since this interruption makes an impact to the system operation, it might cause failure.After checking the light off of SD card access LED, remove the SD card.

CAUTION

 If the data storage mounted on the GOT is removed while the GOT is accessed, the data storage and files are damaged.To remove the data storage from the GOT, check that the access to the data storage in SD card access LED, the system signal, and others is not performed.

 When inserting a SD card into the GOT, make sure to close the SD card cover. Failure to do so causes the data not to be read or written.

 When removing the SD card from the GOT, make sure to support the SD card by hand as it may pop out.Failure to do so may cause the SD card to drop from the GOT, resulting in a failure or break.

 When inserting a USB device into a USB interface of the GOT, make sure to insert the device into the interface firmly.Failure to do so may cause the USB device to drop from the GOT, resulting in a failure or break

 Before removing the USB device from the GOT, follow the procedure for removal on the utility screen of the GOT. After the successful completion dialog is displayed, remove the USB device by hand carefully.Failure to do so may cause the USB device to drop from the GOT, resulting in a failure or break.

[DISPOSAL PRECAUTIONS]

CAUTION

 When disposing of this product, treat it as industrial waste.

When disposing of batteries, separate them from other wastes according to the local regulations.

(Refer to the GOT2000 Series User’s Manual (Hardware) for details of the battery directive in the EU member states.)

[TRANSPORTATION PRECAUTIONS]

CAUTION

 When transporting lithium batteries, make sure to treat them based on the transport regulations.

(Refer to the GOT2000 Series User’s Manual (Hardware) for details of the regulated models.)

 Make sure to transport the GOT main unit and/or relevant unit(s) in the manner they will not be exposed to the impact exceeding the impact resistance described in the general specifications of this manual, as they are precision devices.

Failure to do so may cause the unit to fail.

Check if the unit operates correctly after transportation.

 When fumigants that contain halogen materials such as fluorine, chlorine, bromine, and iodine are used for disinfecting and protecting wooden packaging from insects, they cause malfunction when entering our products.

Please take necessary precautions to ensure that remaining materials from fumigant do not enter our products, or treat packaging with methods other than fumigation (heat method).

Additionally, disinfect and protect wood from insects before packing products.

Manual

The following shows manuals relevant to this product.

Detailed Manual

Manual name

GOT2000 Series User’s Manual

(Hardware)

GOT2000 Series User’s Manual (Utility)

Manual number

(Model code)

SH-081194ENG-A

(1D7MJ5)

SH-081195ENG-A

(1D7MJ6)

For detailed manuals, refer to the PDF manuals stored in the DVD-ROM for the drawing software used.

Relevant Manuals

For relevant manuals, refer to the Help or the PDF manuals stored in the DVD-

ROM for the drawing software used.

The latest manuals are also available from MITSUBISHI ELECTRIC FA Global

Website (http://www.MitsubishiElectric.co.jp/fa/).

© 2013MITSUBISHI ELECTRIC CORPORATION

Before using the GOT

Connect the connector of the GOT to the connector of the battery.

Refer to the GOT2000 Series User’s Manual (Hardware) for the connection instructions.

For details on the GOT specifications, installing instructions, wiring, maintenance and inspection, or checking procedure for the version and the compatible standard, refer to the GOT2000 Series User’s Manual (Hardware).

Packing List

The GOT product package includes the following:

Description

GT27

Battery (GT11-50BAT) (Attached to the GOT)

Installation fitting

GT27 General Description (This manual)

GT27 本体概要説明書

Quantity

1

1

4,

8(Only GT2715)

1

1

1. FEATURES

(1) Abundant standard equipment

• Variety of connection with FA devices

• SD card interface compatible with the SDHC card having a large capacity and allowing high-speed communication

• Connection with various peripheral devices with the USB host

(2) Improved usability

• Abundant troubleshooting

• Easy and clear screen creation

• PC-like operation screen

• Multi-touch function, Gesture function

(3) Enhanced compatibility with Mitsubishi FA devices

(4) Easy replacement]

(5) LED backlight

(6) External controllers including multimedia and video supported

(7) Various extended functions supported

2. Part Names and Settings

The following shows the part names for GT2715, GT2712, GT2710 and GT2708.

GT2715 1) 2) 7) 7) 7) 8) 9) 7)

6)

5)

3)4)

10)

11) 12)

7)

13)

14)

15)

16)

7) 7) 19) 18)

17)

7)

GT2712

23)

22)

21)

20)

1)2)

6)

5)

3)4)

7) 8) 7) 9)

10)

11)

12)

13)

14)

15)

16)

7) 19) 18) 17) 7)

24) 23) 22)21) 20)

GT2710

5)

3)4)

5)

3)4)

24)

GT2708

1)2)

23)22)21) 20)

1)2)

7)

7)

8) 7) 9)

10)

11)

12)

13)

14)

15)

16)

19) 18)

17)

7)

7) 8) 7) 9)

10)

11)12)13)

14)

15)

7) 19) 18) 7)

17)

16) 23)22)21) 20)

No.

1)

2)

3)

4)

5)

6)

7)

8)

9)

16)

17)

Name

Display screen

Touch Pane

USB interface

(Host/Front face)

USB interface (Device

/Front face)

POWER LED

Human sensor

Unit installation fitting

Reset switch

Installation switch

10) SD card access LED

11) SD card interface

12) SD card cover

13) Battery holder

14) Side interface

15)

USB interface

(Host/Back face)

Hole for attaching a cable clamp

Terminating resistor setting switch

(Inside cover)

Description

Displays the utility and the user-created screen.

For operating the touch switches in the utility and the usercreated screen

For connecting a USB mouse, connecting a USB keyboard, data transfer, and data storage

(connector type: TYPE-A)

(Only GT2715-XTBA/D, GT2712-STBA/D, GT2710-STBA/

D, GT2710-VTBA/D, GT2708-STBA/D, GT2708-VTBA/D)

For connecting a personal computer (connector type: Mini-

B)

(Only GT2715-XTBA/D, GT2712-STBA/D, GT2710-STBA/

D, GT2710-VTBA/D, GT2708-STBA/D, GT2708-VTBA/D)

Lit in blue

Lit in orange

: Power is properly supplied.

: Screen saving

Blinks in orange/blue : Backlight failure

Not lit : Power is not supplied

Detects human movement.(Only GT2715, GT2712)

Mounting fixtures for fixing the GOT to the control panel

Hardware reset switch

Used for OS installations at the GOT startup

Lit: SD card mounted

Blinking: SC card accessed

No lit: SD card not mounted or SD card mounted

(removable)

For installing a SD card

With a switching function for accepting and stopping the access to the SD card

When the cover is opened : Access is prohibited

When the cover is closed : Access is allowed

Houses the battery

For installing a communication unit

For connecting a USB mouse, connecting a USB keyboard, data transfer, and data storage

(connector type: TYPE-A)

Hole for attaching a cable clamp for preventing USB cable from being pulled out

(Recommended product: RSG-130-V0 made by

KITAGAWA INDUSTRIES CO.,LTD)

For switching on and off of the terminating resistor for the

RS-422/485 communication port (Default (Off))

19) Extension interface

20) Power terminal

21) Ethernet interface

22) RS-232 interface

23) RS-422/485 interface

24)

USB interface (Device/

Back face)

For installing an option unit

For installing a communication unit or an option unit

Power input terminal, LG terminal, FG terminal

For communicating with a controller or connecting a personal computer (connector type: RJ-45 (modular jack))

For communicating with a controller (Connector type: D sub

9-pin (male))

For communicating with a controller (Connector type: D sub

9-pin (female))

For connecting personal computers (connector type: Mini-B)

(Only GT2712-STWA/D,GT2710-VTWA/D)

3. Specifications

3.1 General Specifications

Item

Operating ambient temperature *1

Température ambiante de fonctionnement *1

Storage ambient temperature

Operating ambient humidity

Storage ambient humidity

Vibration resistance

Shock resistance

Operating atmosphere

Operating altitude *3

Installation location

Overvoltage category *4

Pollution degree *5

Cooling method

Grounding

Specifications

0 to 55

0 à 55

-20 to 60

*2

*2

10 to 90% RH, non-condensing

10 to 90% RH, non-condensing

Frequency Acceleration

Halfamplitude

Sweep count

Complian t with JIS

B 3502 and IEC

61131-2

Under intermitten t vibration

Under continuou s vibration

5 to 8.4Hz

8.4 to150Hz

5 to 8.4Hz

8.4 to 150Hz

-

9.8m/s

-

4.9m/s

2

2

3.5mm

-

-

1.75mm

10 times each in X,

Y and Z directions

-

Compliant with JIS B 3502 and IEC 61131-2 147 m/s

3 times each in X, Y and Z directions

2 (15G),

No greasy fumes, corrosive gas, flammable gas, excessive conductive dust, and direct sunlight (Same as storage atmosphere)

2000 m (6562 ft) max.

Inside control panel

II or less

2 or less

Self-cooling

Type D grounding (100Ω or less).

Connect to panel if unable to ground.

*1: The operating ambient temperature includes the temperature inside the enclosure of the control panel to which the GOT is installed.

La température ambiante de fonctionnement inclut la température à l'intérieur du boîtier du tableau de commande sur lequel le GOT est installé.

*2: When mounting a multimedia unit (GT27-MMR-Z), MELSECNET/H communication unit (GT15-J71LP23-25, GT15-J71BR13), or CC-Link communication unit (GT15-J61BT13), the operating ambient temperature must be reduced 5 against the maximum values described in general specifications.

Lors du montage d'un module multimédia (GT27-MMR-Z), du module de communication MELSECNET/H (GT15-J71LP23-25, GT15-J71BR13) ou du module de communication CC-Link (GT15-J61BT13), la température ambiante de fonctionnement doit être réduite de 5 par rapport aux valeurs maximales décrites dans les spécifications générales.

*3: Do not use or store the GOT under pressure higher than the atmospheric pressure of altitude 0m (0ft.).

Failure to observe this instruction may cause a malfunction.

When an air purge is made inside the control panel by adding pressure, there may be a clearance between the surface sheet and the screen making it difficult to use the touch panel, or the sheet may come off.

*4: This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within the premises.

Category II applies to equipment for which electrical power is supplied from fixed facilities.

The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V.

*5: This index indicates the degree to which conductive material is generated in the environment where the equipment is used.

In pollution degree 2, only non-conductive pollution occurs but temporary conductivity may be produced due to condensation.

Point

Refer to the GOT2000 Series User’s Manual (Hardware) for details on the performance specifications of each GOT.

3.2 Power Supply Specifications

The following indicates the power supply specifications for GT27 .

Note

Operation at momentary failure

• If an instantaneous power failure occurs in the power supply and continues for more than the permissible period, the GOT will be reset.

• Make sure to power on the unit more than 5 seconds after power-off.

3.2.1 For GOTs powered from the 100 to 240VAC power supply

Item

Power supply voltage

Power frequency

Max. apparent power maximum load

Power consum ption

Stand alone

Stand alone with backlight off

GT2715-XTBA

Specifications

GT2712-

STBA

GT2712-

STWA

GT2710-

STBA

GT2710-

VTBA

GT2710-

VTWA

GT2708-

STBA

GT2708-

VTBA

AC100 to 240VAC (+10%, -15%)

50/60Hz 5%

140VA

51W or less

25W

44W or less

19W

100VA

41W or less

17W 15W

10W

Inrush current

40A or less (3ms, operating ambient temperature 25, maximum load)

60A or less (2ms, operating ambient temperature 25, maximum load)

Allowable momentary power failure time

20 ms or less (100VAC or more)

Noise immunity

Dielectric withstand voltage

Insulation resistance

Applicable wire size

Applicable solderless terminal

Applicable tightening torque

(Terminal block terminal screw)

1,500Vp-p noise voltage, 1 s noise width (when measuring with a noise simulator under 25 to 60Hz noise frequency)

1500VAC for 1 minute across power terminals and earth

10M or more across power terminals and earth by a

500V DC insulation resistance tester

0.75[mm 2 ] to 2[mm 2 ]

Solderless terminal for M3 screw RAV1.25-3, V2-S3.3,

V2-N3A, FV2-N3A

0.5[N•m] to 0.8[N•m]

3.2.2 For GOTs powered from the 24VDC power supply

Item

Power supply voltage maximum load

Power consum ption

Stand alone

Stand alone with backlight off

GT2715-

XTBD

Specifications

GT2712-

STBD,

GT2712-

STWD

GT2710-

STBD,

GT2710-

VTBD,

GT2710-

VTWD

GT2708-

STBD,

GT2708-

VTBD

DC24V (+25%, -20%)

48W or less 45W or less 42W or less 39W or less

23W 18W 15W 13W

8W

Inrush current

5A or less (20ms, operating ambient temperature 25, maximum load)

Allowable momentary power failure time

10 ms or less

Noise immunity

Dielectric withstand voltage

Insulation resistance

Applicable wire size

Applicable solderless terminal

500Vp-p noise voltage, 1 s noise width (when measuring with a noise simulator under 25 to 60Hz noise frequency)

350VAC for 1 minute across power terminals and earth

10M or more across power terminals and earth by a

500V DC insulation resistance tester

0.75[mm 2 ] to 2[mm 2 ]

Solderless terminal for M3 screw RAV1.25-3, V2-S3.3,

V2-N3A, FV2-N3A

Applicable tightening torque

(Terminal block terminal screw)

0.5[N•m] to 0.8[N•m]

3.3 External Dimensions

GT2715 GT2712

397(15.63)

322(12.68)

316 (12.44)

241 (9.49)

10

(0.39)

GT2710

322(12.68)

382(15.04)

303 (11.93)

208 (8.19)

10

(0.39)

GT2708

241 (9.49)

301 (11.85)

241 (9.49)

166 (6.54) 37.5

(1.48)

228 (8.98)

288 (11.34)

171.6

(6.76)

37.5

(1.48)

226 (8.90)

Unit : mm (inch)

4. EMC AND LOW VOLTAGE DIRECTIVE

For the products sold in European countries, the conformance to the

EMC Directive, which is one of the European Directives, has been a legal obligation since 1996. Also, conformance to the Low Voltage.

Directive, another European Directives, has been a legal obligation since

1997.

Manufacturers who recognize their products must conform to the EMC and Low Voltage Directive are required to declare that their products conform to these Directives and put a "CE mark" on their products.

• Authorized representative in Europe

Authorized representative in Europe is shown below.

Name :Mitsubishi Electric Europe BV

Address :Gothaer strase 8, 40880 Ratingen, Germany

4.1 Requirements to Meet EMC Directive

EMC Directives are those which require "any strong electromagnetic force is not output to the external.:Emission (electromagnetic interference)" and "It is not influenced by the electromagnetic wave from the external.: Immunity (electromagnetic sensitivity)".

Items4.1.1 through4.1.3 summarize the precautions to use GOT and

configure the mechanical unit in order to match the EMC directives.

Though the data described herein are produced with our best on the basis of the requirement items and standards of the restrictions gathered by Mitsubishi, they do not completely guaranteed that all mechanical unit manufactured according to the data do not always match the above.

4.1.1 EMC directive

The standards of the EMC Directive are shown below.

Applied standard

Test standard Test details Standard value

EN61131-2

: 2007

CISPR16-2-3

Radiated noise

*1

CISPR16-2-1

Conducted noise *1

IEC61000-4-2

Electrostatic immunity *1

IEC61000-4-3

Radiated electromagnetic field AM modulation

IEC61000-4-4

Fast transient burst noise *1

IEC61000-4-5

Surge immunity

*1

Electromagnetic emissions from the product are measured.

Electromagnetic emissions from the product to the power line is measured.

Immunity test in which static electricity is applied to the cabinet of the equipment.

Immunity test in which field is irradiated to the product.

Immunity test in which burst noise is applied to the power line and signal lines.

Immunity test in which lightening surge is applied to the product.

30M-230MHz QP:

30dB V/m (30m in measurement range) *2, *3

230M-1000MHz QP:

37dB V/m(30m in measurement range) *2, *3

150k-500kHz QP:79dB,

Mean: 66dB *2

500k-30MHz QP:73dB,

Mean: 60dB

*2

4kV Contact discharge

8kV Aerial discharge

80-1000MHz:10V/m

1.4-2GHz:3V/m

2.0-2.7GHz:1V/m

80%AM modulation@1kHz

Power line:2kV

Digital I/O(24V or higher): 1kV

(Digital I/O(24V or less))> 250V

(Analog I/O, signal lines)> 250V

AC power type

Power line (between line and ground): 2kV

Power line (between lines)

: 1kV

Data communication port

: 1kV

DC power type

Power line (between line and ground) : 0.5kV

Power line (between lines)

: 0.5kV

Data communication port

: 1kV

IEC61000-4-6

Conducted RF immunity

*1

IEC61000-4-8

Power supply frequency magnetic field immunity

Immunity test in which a noise inducted on the power and signal lines is applied.

Test for checking normal operations under the circumstance exposed to the ferromagnetic field noise of the power supply frequency

(50/60Hz).

Power line: 10V

Data communication port: 10V

30 A/m

IEC61000-4-11

Instantaneous power failure and voltage dips immunity

Test for checking normal operations at instantaneous power failure.

AC power type

0.5 cycle 0% (interval 1 to 10s)

250/300 cycle 0%

10/12 cycle 40%

25/30 cycle 70%

*1: The GOT is an open type device (device installed to another device) and must be installed in a conductive control panel.

The above test items are conducted in the condition where the GOT is installed on the conductive control panel and combined with the Mitsubishi PLC.

*2: QP (Quasi-Peak): Quasi-peak value, Mean: Average value

*3: The above test items are conducted in the following conditions.

30M-230MHz QP : 40dB V/m (10m in measurement range)

230M-1000MHz QP : 47dB V/m (10m in measurement range)

4.1.2 Control panel

The GOT is an open type device (device installed to another device) and must be installed in a conductive control panel.

It not only assure the safety but also has a large effect to shut down the noise generated from GOT, on the control panel.

(1) Control Panel

(a) The control panel must be conductive.

(b) When fixing a top or bottom plate of the control panel with bolts, do not coat the plate and bolt surfaces so that they will come into contact.

And connect the door and box using a thick grounding cable in order to ensure the low impedance under high frequency.

(c) When using an inner plate to ensure electric conductivity with the control panel, do not coat the fixing bolt area of the inner plate and control panel to ensure conductivity in the largest area as possible.

(d) Ground the control panel using a thick grounding cable in order to ensure the low impedance under high frequency.

(e) The diameter of cable holes in the control panel must be 10cm

(3.94in.). In order to reduce the chance of radio waves leaking out, ensure that the space between the control panel and its door is small as possible.

Paste the EMI gasket directly on the painted surface to seal the space so that the leak of electric wave can be suppressed.

Our test has been carried out on a panel having the damping characteristics of 37dB max. and 30dB mean (measured by 3m method with 30 to 300MHz).

(2) Connection of power and ground wires

Ground and power supply wires for the GOT must be connected as described below.

(a) Provide a grounding point near the GOT. Short-circuit the LG and

FG terminals of the GOT (LG: line ground, FG: frame ground) and ground them with the thickest and shortest wire possible

(The wire length must be 30cm (11.81in.) or shorter.)

The LG and FG terminals function is to pass the noise generated in the PC system to the ground, so an impedance that is as low as possible must be ensured. As the wires are used to relieve the noise, the wire itself carries a large noise content and thus short wiring means that the wire is prevented from acting as an antenna.

Note) A long conductor will become a more efficient antenna at high frequency.

(b) The earth wire led from the earthing point must be twisted with the power supply wires.

By twisting with the earthing wire, noise flowing from the power supply wires can be relieved to the earthing. However, if a filter is installed on the power supply wires, the wires and the earthing wire may not need to be twisted.

4.1.3 Noise filter (power supply line filter)

The noise filter (power supply line filter) is a device effective to reduce conducted noise. Except some models, installation of a noise filter onto the power supply lines is not necessary. However conducted noise can be reduced if it is installed. (The noise filter is generally effective for reducing conducted noise in the band of 10MHz or less.) Usage of the following filters is recommended.

Model name

Manufacturer

Rated current

Rated voltage

FN343-3/05

SCHAFFNER

3A

FN660-6/06

SCHAFFNER

6A

250V

RSHN-2003

TDK

3A

The precautions required when installing a noise filter are described below.

(1) Do not install the input and output cables of the noise filter together to prevent the output side noise will be inducted into the input side cable where noise has been eliminated by the noise filer.

Input side

(power supply side)

Input side

(power supply side)

Induction

Filter Filter

Output side

(device side)

Output side

(device side)

• Installing the input and output cables together will cause noise induction.

• Separate the input cable from the output cable.

(2) Connect the noise filter's ground terminal to the control panel with the shortest cable as possible (approx. 10cm (3.94 in.) or less).

4.2 Requirements for Compliance with the Low

Voltage Directive

The Low Voltage Directive requires each device which operates with power supply ranging from 50VAC to 1000V and 75VDC to 1500V to satisfy necessary safety items.

In the Sections from 4.2.1 to 4.2.5, cautions on installation and wiring of

the GOT to conform to the Low Voltage Directive requires are described.

We have put the maximum effort to develop this material based on the requirements and standards of the Directive that we have collected.

However, compatibility of the devices which are fabricated according to the contents of this manual to the above Directive is not guaranteed.

Each manufacturer who fabricates such device should make the final judgement about the application method of the Low Voltage Directive and the product compatibility.

4.2.1 Standard subject to GOT

Standard applied to GOT : EN61131-2 Programmable controllers - Equipment requirements and tests

EN60950-1 Safety of Information Technology Equipment

4.2.2 Power supply

The insulation specification of the GOT was designed assuming installation category II. Be sure to use the installation category II power supply to the GOT.

The installation category indicates the durability level against surge voltage generated by lightning strike.

Category I has the lowest durability; category IV has the highest durability.

Category IV Category III Category II Category I

Installation category

Category II indicates a power supply whose voltage has been reduced by two or more levels of isolating transformers from the public power distribution.

4.2.3 Control panel

Because the GOT is open type equipment (device designed to be stored within another device), be sure to use it only when installed in a control panel.

(1) Shock Protection

In order to prevent those who are unfamiliar with power facility, e.g., an operator, from getting a shock, make sure to take the following measures on the control panel.

(a) Store the GOT within the control panel locked, and allow only those who are familiar with power facility to unlock the panel.

(b) Build the structure in order that the power supply will be shut off when the control panel is opened.

(2) Dustproof and waterproof features

The control panel also provides protection from dust, water and other substances. Insufficient ingression protection may lower the insulation withstand voltage, resulting in insulation destruction.

The insulation in the GOT is designed to cope with the pollution level 2, so use in an environment with pollustion level 2 or better.

Pollution level 1: An environment where the air is dry and conductive dust does not exist.

Pollution level 2: An environment where conductive dust does not usually exist, but occasional temporary conductivity occurs due to the accumulated dust.

Generally, this is the level for inside the control panel equivalent a control room or on the floor of a typical factory.

Pollution level 3: An environment where conductive dust exits and conductivity may be generated due to the accumulated dust.

An environment for a typical factory floor.

Pollution level 4: Continuous conductivity may occur due to rain, snow, etc. An outdoor environment.

4.2.4 Grounding

The following are applicable ground terminals. Use them in the grounded state.

Be sure to ground the GOT for ensuring the safety and complying with the EMC Directive.

Functional grounding : Improves the noise resistance.

4.2.5 External wiring

(1) External devices

When a device with a hazardous voltage circuit is externally connected to the GOT, select a model which complies with the

Low Voltage Directive's requirements for isolation between the primary and secondary circuits.

(2) Insulation requirements

Dielectric withstand voltages are shown in the following table.

Reinforced Insulation Withstand Voltage

(Installation Category II, source : IEC664)

Rated voltage of hazardous voltage area

150 VAC or below

300 VAC or below

2500V

4000V

Surge withstand voltage (1.2/50 s)

5. INSTALLATION

5.1 Control Panel Inside Dimensions for

Mounting GOT

Install the GOT on the control panel out of the way for the equipment inside the control panel. Do not install the GOT and the unit in prohibited areas for the installation.

Point

Applicable cable

Some cables may need to be longer than the specified dimensions when connecting to the

GOT. Therefore, consider the connector dimensions and bending radius of the cable as well for installation.

5.2 Panel Cutting Dimensions

A

*Panel thickness : 1.6 to 4 mm

(0.06 to 0.16 inch)

GOT

GT2715

A

383.5 (15.10)

+2 (0.08)

0 (0)

B

282.5 (11.12)

+2 (0.08)

0 (0)

GT2712

GT2710

GT2708

302 (11.89)

+2 (0.08)

0 (0)

289 (11.38)

+2 (0.08)

0 (0)

227 (8.94)

+2 (0.08)

0 (0)

228 (8.98)

+2 (0.08)

0 (0)

200 (7.87)

+2 (0.08)

0 (0)

176 (6.93)

+2 (0.08)

0 (0)

Unit: mm (inch)

5.3 Mounting Position

When mounting the GOT, the following clearances must be maintained from other structures and devices.

Some cables may need to be longer than the specified dimensions when connecting to the GOT.

Therefore, consider the connector dimensions and bending radius of the cable as well for installation.

For the lead-in allowance for cables at the bottom of the GOT, refer to the GOT2000 Series User’s Manual (Hardware) .

C D E

Panel thickness: 1.6 to 4mm

(0.06 to 0.16 inch)

According to the dimensions in the following table, leave clearances between the GOT and the other devices. The values enclosed in square brackets apply to the case where no other equipment generating radiated noise (such as a contactor) or heat is installed near the GOT. However, keep the ambient temperature of the GOT to 55°C or lower.

Serial connection unit is fitted

CC-Link communication unit

(GT15-J61BT13) fitted

MELSECNET/H communication unit (coaxial) fitted

*1

MELSECNET/H communication

unit(optical) fitted *2

CC-Link IE Controller Network communication unit fitted

CC-Link IE Field Network communication unit fitted

A

Video input unit fitted

*1

B

C

D

E*4

GOT only

Item

Bus connection unit is fitted

RGB input unit fitted *3

Video/RGB input unit fitted

*1*3

RGB output unit fitted *3

Multimedia unit fitted

*1

Printer unit fitted

External I/O unit fitted

Sound output unit fitted

When the SD card is used

When the SD card is not used

GT2715 GT2712

Unit : mm(inch)

GT2710 GT2708

48(1.89) or more

[18(0.71) or more]

48(1.89) or more

[18(0.71) or more]

23(0.91) or more

[29(1.14) or more]

48(1.89) or more

[18(0.71) or more]

48(1.89) or more

[18(0.71) or more]

48(1.89) or more

[18(0.71) or more]

48(1.89) or more

[18(0.71) or more]

48(1.89) or more

[18(0.71) or more]

48(1.89) or more

[38(1.50) or more]

48(1.89) or more

[45(1.77) or more]

48(1.89) or more

[18(0.71) or more]

48(1.89) or more

[18(0.71) or more]

48(1.89) or more

[18(0.71) or more]

48(1.89) or more

[38(1.50) or more]

48(1.89) or more

[45(1.77) or more]

48(1.89) or more

[18(0.71) or more]

48(1.89) or more

[38(1.50) or more]

48(1.89) or more

[45(1.77) or more]

48(1.89) or more

[18(0.71) or more]

48(1.89) or more

[18(0.71) or more]

48(1.89) or more

[38(1.50) or more]

48(1.89) or more

[45(1.77) or more]

48(1.89) or more

[18(0.71) or more]

48(1.89) or more

[18(0.71) or more]

48(1.89) or more

[18(0.71) or more]

78(3.07) or more

[18(0.71) or more]

50(1.97)or more

[20(0.79) or more]

50(1.97) or more

[20(0.79) or more]

50(1.97) or more

[20(0.79) or more]

100(3.94) or more

[20(0.79) or more]

67(2.64) or more

67(2.64) or more

67(2.64) or more

67(2.64) or more

50(1.97) or more

*1: This value is for use of the coaxial cable 3C-2V (JIS C 3501).

For specifications of the cable, refer to the GOT2000 Series Connection

Manual for a controller used.

*2: This value differs depending on the cable used.

*3: This value differs depending on the cable used.

If the bending radius of the cable used is greater than the value specified above, apply the value of the cable used.

*4: When opening or closing the battery cover: 72(2.83) or more

5.4 Control Panel Inside Temperature and

Installation Angle

When installing the GOT to a panel, set the display section as shown below.Using the GOT with the installation angle other than the following deteriorates the GOT earlier.

When installing the GOT with the installation angle between 60 to 105

°, the temperature inside the control panel must be within 55 °C.

When installing the GOT with the installation angle other than between

60 to 105 °, the temperature inside the control panel must be within 40

°C.

Display section

GOT

105°

60°

Panel or others

5. INSTALLATION

5.1 Dimensions intérieures du tableau de commande pour le montage du GOT

Installez le GOT sur le tableau de commande en laissant de l'espace pour le dispositif à l'intérieur du tableau de commande. N'installez pas le GOT et le module dans des zones où l'installation est interdite.

Point

Câble applicable

Certains câbles peuvent être plus longs que les dimensions spécifiées lors de la connexion au GOT. Par conséquent, prenez également en compte les dimensions du connecteur et le rayon de courbure du câble pour l'installation.

5.2 Cotes de découpe du panneau

A

*Épaisseur du panneau : 1,6 à 4mm

(0,06 à 0,16 pouce)

GOT

GT2715

GT2712

A B

383,5 (15,10) 282,5 (11,12)

+2 (0,08)

0 (0)

+2 (0,08)

0 (0)

302 (11,89)

+2 (0,08)

0 (0)

228 (8,98)

+2 (0,08)

0 (0)

GT2710

GT2708

289 (11,38)

+2 (0,08)

0 (0)

227 (8,94)

+2 (0,08)

0 (0)

200 (7,87)

+2 (0,08)

0 (0)

176 (6,93)

+2 (0,08)

0 (0)

Unité : mm (pouce)

5.3 Position de montage

Lors du montage du GOT, laissez les espaces suivants pour les autres structures et dispositifs.

Certains câbles peuvent être plus longs que les dimensions spécifiées lors de la connexion au GOT.

Par conséquent, prenez également en compte les dimensions du connecteur et le rayon de courbure du câble pour l'installation.

Pour connaître l'espace à laisser pour les câbles sous le GOT, référezvous au manuel GOT2000 Series User’s Manual (Hardware).

C D E

Épaisseur du panneau : 1,6 à 4mm

(0,06 à 0,16 pouce)

Laissez les espaces entre le GOT et les autres dispositifs en fonction des dimensions contenues dans le tableau suivant. Les valeurs entre parenthèses s'appliquent au cas où aucun dispositif générant des

émissions sonores (comme un contacteur) ou de la chaleur n'est installé près du GOT.

Toutefois, maintenez la température ambiante du GOT à 55°C ou moins.

Unité : mm (pouce)

Article GT2715 GT2712 GT2710 GT2708

GOT uniquement

48 (1,89) ou plus

[18 (0,71) ou plus]

Unité de connexion de bus encastrée

48 (1,89) ou plus

[18 (0,71) ou plus]

23 (0,91) ou plus

[29 (1,14) ou plus]

A

Unité de connexion série encastrée

Module de communication CC-

Link (GT15-J61BT13) encastré

Module de communication

MELSECNET/H (coaxial) encastré *1

48(1,89) or more

[18(0,71) or more]

48 (1,89) ou plus

[18 (0,71) ou plus]

48 (1,89) ou plus

[18 (0,71) ou plus]

48 (1,89) ou plus

[38 (1,50) ou plus]

48 (1,89) ou plus

[45 (1,77) ou plus]

67 (2,64) ou plus

Module de communication

MELSECNET/H (optique) encastré *2

Module de communication réseau de contrôleur CC-Link IE encastré

Module de communication réseau de champ CC-Link IE encastré

48 (1,89) ou plus

[18 (0,71) ou plus]

48 (1,89) ou plus

[18 (0,71) ou plus]

48 (1,89) ou plus

[18 (0,71) ou plus]

A

B

C

D

Article

Module d'entrée vidéo encastré *1

Module d'entrée RGB encastré

*3

Module d'entrée vidéo/RGB encastré *1*3

Module de sortie RGB encastré

*3

Module multimédia encastré *1

Imprimante encastrée

Module d'E/S externe encastré

Module de sortie acoustique encastré

Quand la carte SD est utilisée

Quand la carte SD n'est pas utilisée

E*4

GT2715 GT2712

48(1,89) or more

[18(0,71) or more]

48 (1,89) ou plus

[38 (1,50) ou plus]

48(1,89) or more

[18(0,71) or more]

48(1,89) or more

[18(0,71) or more]

GT2710

48 (1,89) ou plus

[45 (1,77) ou plus]

48 (1,89) ou plus

[18 (0,71) ou plus]

48 (1,89) ou plus

[38 (1,50) ou plus]

48 (1,89) ou plus

[45 (1,77) ou plus]

48 (1,89) ou plus

[18 (0,71) ou plus]

48 (1,89) ou plus

[38 (1,50) ou plus]

48 (1,89) ou plus

[45 (1,77) ou plus]

48 (1,89) ou plus

[18 (0,71) ou plus]

48 (1,89) ou plus

[18 (0,71) ou plus]

48 (1,89) ou plus

[18 (0,71) ou plus]

78 (3,07) ou plus

[18 (0,71) ou plus]

50 (1,97) ou plus

[20 (0,79) ou plus]

50 (1,97) ou plus

[20 (0,79) ou plus]

50 (1,97) ou plus

[20 (0,79) ou plus]

100 (3,94) ou plus

[20 (0,79) ou plus]

GT2708

67 (2,64) ou plus

67 (2,64) ou plus

67 (2,64) ou plus

50 (1,97) ou plus

*1 : Cette valeur est utilisée pour le câble coaxial 3C-2V (JIS C 3501).

Pour connaître les spécifications du câble, référez-vous au manuel

GOT2000 Series Connection Manual for a controller used.

*2 : Cette valeur diffère selon le câble utilisé.

*3 : Cette valeur diffère selon le câble utilisé.

Si le rayon de courbure du câble utilisé est supérieur à la valeur spécifiée ci-dessus, appliquez la valeur du câble utilisé.

*4 : Pour ouvrir ou fermer le couvercle de la batterie : 72 (2,83) ou plus

5.4 Température intérieure et angle d'installation du tableau de commande

Lors de l'installation du GOT sur un panneau, réglez la zone d'affichage comme indiqué ci-dessous.

Si l'angle d'installation est différent de celui indiqué, le GOT se détériore plus tôt.

Lors de l'installation du GOT avec un angle d'installation compris entre

60 et 105°, la température à l'intérieur du tableau de commande doit

être d'environ 55°C.

Lors de l'installation du GOT avec un angle d'installation non compris entre 60 et 105°, la température à l'intérieur du tableau de commande doit être d'environ 40°C.

Zone d'affichage

GOT

105°

60°

Tableau ou autres

6. MAINTENANCE AND INSPECTION

Refer to the GOT2000 Series User’s Manual (Hardware) for maintenance and inspection for the GOT.

Warranty

Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi products; damage, secondary damage, accident compensation caused by special factors unpredictable by Mitsubishi; damages to products other than

Mitsubishi products; and to other duties.

For safe use

• This product has been manufactured as a general-purpose part for general industries, and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life.

• Before using the product for special purposes such as nuclear power, electric power, aerospace, medicine or passenger movement vehicles, consult with Mitsubishi.

• This product has been manufactured under strict quality control.

However, when installing the product where major accidents or losses could occur if the product fails, install appropriate backup or failsafe functions in the system.

Country/Region Sales office/Tel

U.S.A

Brazil

Germany

U.K

Italy

Spain

France

Mitsubishi Electric Automation Inc.

500 Corporate Woods Parkway Vernon Hills, IL 60061, U.S.A.

Tel : +1-847-478-2100

MELCO-TEC Rep. Com.e Assessoria Tecnica Ltda.

Rua Correia Dias, 184, Edificio Paraiso Trade Center-8 andar

Paraiso, Sao Paulo, SP Brazil

Tel : +55-11-5908-8331

Mitsubishi Electric Europe B.V. German Branch

Gothaer Strasse 8 D-40880 Ratingen, GERMANY

Tel : +49-2102-486-0

Mitsubishi Electric Europe B.V. UK Branch

Travellers Lane, Hatfield, Hertfordshire., AL10 8XB, U.K.

Tel : +44-1707-276100

Mitsubishi Electric Europe B.V. Italian Branch

Centro Dir. Colleoni, Pal. Perseo-Ingr.2

Via Paracelso 12, I-20041 Agrate Brianza., Milano, Italy

Tel : +39-039-60531

Mitsubishi Electric Europe B.V. Spanish Branch

Carretera de Rubi 76-80,

E-08190 Sant Cugat del Valles, Barcelona, Spain

Tel : +34-93-565-3131

Mitsubishi Electric Europe B.V. French Branch

South Africa

Hong Kong

China

25, Boulevard des Bouvets, F-92741 Nanterre Cedex, France

Tel : +33-1-5568-5568

Circuit Breaker Industries Ltd.

Private Bag 2016, ZA-1600 Isando, South Africa

Tel : +27-11-928-2000

Mitsubishi Electric Automation (Hong Kong) Ltd.

10th Floor, Manulife Tower, 169 Electric

Road, North Point, Hong Kong

Tel : +852-2887-8870

Mitsubishi Electric Automation (China) Ltd.

Taiwan

4/F Zhi Fu Plazz, No.80 Xin Chang Road,

Shanghai 200003, China

Tel : +86-21-6120-0808

Setsuyo Enterprise Co., Ltd.

6F No.105 Wu-Kung 3rd.Rd, Wu-Ku Hsiang,

Korea

Taipei Hsine, Taiwan

Tel : +886-2-2299-2499

Mitsubishi Electric Automation Korea Co., Ltd.

1480-6, Gayang-dong, Gangseo-ku Seoul

Korea

Singapore

Thailand

Indonesia

Tel : +82-2-3660-9552

Mitsubishi Electric Asia Pte, Ltd.

307 Alexandra Road #05-01/02,

Mitsubishi Electric Building, Singapore 159943

Tel : +65-6470-2460

Mitsubishi Electric Automation (Thailand) Co., Ltd.

Bang-Chan Industrial Estate No.111 Moo 4, Serithai Rd,

T.Kannayao, A.Kannayao, Bangkok 10230 Thailand

Tel : +66-2-517-1326

P.T. Autoteknindo Sumber Makmur

India

Muara Karang Selatan, Block A/Utara

No.1 Kav. No.11 Kawasan Industri Pergudangan

Jakarta - Utara 14440, P.O.Box 5045 Jakarta, 11050 Indonesia

Tel : +62-21-6630833

Messung Systems Pvt, Ltd.

Electronic Sadan NO:III Unit No15, M.I.D.C Bhosari,

India

Tel : +91-20-2712-3130

Australia Mitsubishi Electric Australia Pty. Ltd.

348 Victoria Road, Rydalmere, N.S.W 2116, Australia

Tel : +61-2-9684-7777

HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

NAGOYA WORKS : 1-14, YADA-MINAMI 5-CHOME, HIGASHI-KU, NAGOYA, JAPAN

When exported from Japan, this manual does not require application to the Ministry of Economy, Trade and Industry for service transaction permission.

Specifications subject to change without notice.

Printed in Japan, April 2014.