advertisement
Order No. MAC0412062C2
Air Conditioner
CS-V7DKE CU-V7DKE
CS-V9DKE CU-V9DKE
CS-V12DKE CU-V12DKE
CONTENTS
Page
6
7
7
4
5
3
4
Page
14
15
16
9
11
13
13
© 2004 Panasonic HA Air-Conditioning (M) Sdn Bhd
(11969-T). All rights reserved. Unauthorized copying and distribution is a violation of law.
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
8.10. Quiet Operation
8.11. Ionizer Operation
8.12. Timer Control
8.13. Random Auto Restart Control
8.14. Remote Control Signal Receiving Sound
10 Installation Instructions
10.1. Safety Precautions
10.2. Indoor Unit
10.3. Outdoor Unit
11 Installation And Servicing Air Conditioner Using R410A
11.1. Outline
11.2. Tools For Installing/Servicing Refrigerant Piping
11.3. Refrigerant Piping Work
11.4. Installation, Transferring, Servicing
12 Servicing Information 56
12.1. Distinction Of Lead Free (PbF) Printed Circuit Board 56
12.2. Indoor Electronic Controllers Removal Procedures 56
35
35
38
42
45
45
46
50
52
25
25
27
28
28
28
29
22
24
24
25
17
18
18
19
20
20
12.3. Indoor Fan Motor And Cross Flow Fan Removal
Procedures
12.4. Remote Control Reset
12.5. Auto OFF/ON Button
13 Troubleshooting Guide
13.1. Refrigeration Cycle System
13.2. Relationship Between The Condition Of The Air
Conditioner And Pressure And Electric Current
13.3. Diagnosis Methods Of A Malfunction Of A Compressor
61
61
14 Technical Data
14.1. Thermostat Characteristics
14.2. Sensible Capacity Chart
14.3. Operation Characteristics
15 Exploded View (Indoor Unit)
15.1. CS-V7DKE CS-V9DKE CS-V12DKE
16 Replacement Parts List (Indoor Unit)
65
65
66
62
62
62
63
57
58
59
60
60
16.1. CS-V7DKE CS-V9DKE CS-V12DKE
17 Exploded View (Outdoor Unit)
17.1. CU-V7DKE
17.2. CU-V9DKE CU-V12DKE
18 Replacement Parts List (Outdoor Unit)
18.1. CU-V7DKE
18.2. CU-V9DKE CU-V12DKE
19 Electronic Circuit Diagram
19.1. Indoor Unit & Outdoor Unit
19.2. Remote Control
19.3. Print Pattern Indoor Unit Printed Circuit Board
77
78
19.4. Print Pattern Indicator & Receiver Printed Circuit Board
80
66
67
67
68
69
69
70
71
71
2
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
1 Features
• High efficiency.
• Compact design.
• Wider range of horizontal discharge air.
• Air Filter with function to reduce dust and smoke.
• Long installation piping up to 15 meter (CS/CU-V12DKE),
10 meter (CS/CU-V7DKE & CS/CU-V9DKE).
• Supersonic Air Purifying System with Super Alleru-Buster.
− Inactive various harmful airbone elements including allergens, viruses and bacteria.
− Generated supersonic waves enhance the ability to collect dust and dirt in the air.
• Operation Improvement
− Quiet mode to provide quiet operation.
− Powerful mode to reach the desired room temperature quickly.
− Ionizer control for generating negative ion in discharge air.
− 24-hour timer setting.
• Serviceability Improvement
− Removable and washable Front Panel.
• Quality Improvement
− Random auto restart after power failure for safety restart operation.
− Gas leakage detection.
− Prevent Compressor reverse cycle.
− OLP to protect Compressor.
− Noise prevention during soft dry operation.
− Blue coated Condenser for high resistance to corrosion.
− Anti-dew formation control (Cooling & Soft Dry).
• Environmental Friendly
− R410A, which does not contain chlorine, is used as its refrigerant, so there is no danger of damage to the ozone layer in Stratosphere.
3
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
2 Functions
2.1. Remote Control
AUTO
COOL
DRY
FAN
SPEED
AIR
SWING
OFF
TIMER
ON
TIMER
MODE
OFF/ON
POWERFUL FAN SPEED
QUIET
TEMP
AIR SWING
TIMER
ON
1
OFF
2
SET
3
CLOCK RESET
OFF / ON
I
Operation Start / Stop
MODE
Operation Mode Selection
•
AUTO
•
COOL
•
DRY
Automatic Operation
Cooling Operation
Soft Dry Operation
FAN SPEED
Indoor Fan Speed Selection
•
•
•
•
AUTO
Low Fan Speed
Medium Fan Speed
High Fan Speed
Automatic Fan Speed
AIR SWING
Vertical Airflow Direction Control
•
•
AUTO
Automatic Vertical Airflow
Control.
Manual Vertical Airflow
Control (5 stages of adjustment).
POWERFUL
Powerful Operation Start / Stop
QUIET
Quiet Operation Start / Stop
TEMP.
Room Temperature Setting
Cooling, Soft Dry Operation.
• Increase or decrease set temperature
(16°C to 30°C)
•
•
•
Automatic Operation
Operation with 2°C higher than standard temperature.
Operation with standard temperature.
Operation with 2°C lower than standard temperature.
ON-TIMER
OFF-TIMER
Timer Operation Selection
• 24-hour, OFF / ON Real Timer Setting.
▲
▼
Time / Timer Setting
• Hours and minutes setting.
SET
CANCEL
Timer Operation Set / Cancel
• ON Timer and OFF Timer setting and cancellation.
CLOCK
Clock Setting
• Current time setting.
Ionizer Operation Start / Stop
4
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
2.2. Indoor Unit
AUTO
OFF / ON
Automatic Operation Button
• Press for < 5 second to operate Automatic operation mode. Used when the remote control cannot be used.
• Press for
≥ 5 second to operate Cooling operation mode and compressor force to on
(“beep” sound will heard). Used when test running or servicing.
• Within 20 second of Cooling operation, press continuously for 5 second to enter various setting mode. “beep, beep” sound will be heard.
(Used to toggle remote control signal receiving sound or select remote control transmission code).
Operation Indication Lamps (LED)
•
POWER
(Green) ............. Lights up in operation, blinks in Automatic
Operation judging.
•
TIMER
(Orange) ............ Lights up in Timer
Setting.
•
QUIET
(Orange) ............. Lights up in Quiet
Operation.
•
POWERFUL (Orange) ...... Lights up in Powerful
Operation.
•
ION
(Green) .................. Lights up in Ionizer
Operation.
•
SUPER
ALLERU-BUSTER
(Blue) ... Lights up in operation.
Operation Mode
• Cooling, Soft Dry and Automatic Operation.
Powerful Operation
• Reaches the desired room temperature quickly.
Timer Operation
• Delay OFF/ON Timer control.
Quiet Operation
• To provide quiet operation.
Ionizer Operation
• Generate and discharge negative ion.
Random Auto Restart Control
• Unit will be restarted, when resume from power failure, at previous setting.
Indoor Fan Speed Control
• Manual control fan speed (High, Medium and
Low).
• Automatic fan speed.
Airflow Direction Control
• Vertical airflow control can be adjusted automatically or manually by remote control.
• Horizontal airflow can be manually adjusted by hand.
Anti-Freezing Control
• To prevent indoor heat exchanger from freezing.
Starting Current Control
• To reduce the starting current.
Time Delay Safety Control
• Restarting is inhibited for appro. 3 minutes.
7 Minutes Time Save Control
• To reduce the built up humidity inside the room.
Anti-Dew Formation Control
• Anti-Dew Formation Control for indoor unit discharge area.
5
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
2.3. Outdoor Unit
Compressor Reverse Rotation
Protection Control
• To protect compressor from reverse rotation when there is a instantaneous power failure.
Overload Protector
• OLP to protect the compressor. Overload
Protector will trip when
– Temperature of compressor increases to 120°C.
– High temperature or high current flows to compressor.
(Refer circuit diagram for OLP characteristic)
60 Secs. Forced Operation Control
• Once the compressor is activated, it does not stop within the first 60 secs.
However, it stops immediately with remote control stop signal.
Outdoor Fan Operation Control
• Temperature Fuse.
6
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
3 Product Specifications
3.1. CS-V7DKE CU-V7DKE
Cooling Capacity
Moisture Removal
Power Source
Airflow Method
Phase
Voltage
Cycle
Unit
kW (kcal/h)
BTU/h l/h (Pint/h)
ø
V
Hz
OUTLET
INTAKE
CS-V7DKE
2.40 (2,060)
8,180
1.5 (3.2)
Single
230
50
SIDE VIEW
CU-V7DKE
TOP VIEW
Air Volume
Noise Level
Lo
Me
Hi
SHi
Electrical Data Input
Running Current
EER
Power Cord Length
Number of core-wire
Dimensions
Starting Current
Piping Connection Port
(Flare piping)
Pipe Size
(Flare piping)
Drain
Hose
Inner diameter
Length
Height
Width
Depth
Net Weight
Compressor Description
Motor
Rated
Type
Output m
3
/min (cfm) m
3
/min (cfm) m
3
/min (cfm) m
3
/min (cfm) dB (A)
Power level dB
W
A
W/W (BTU/hW)
A inch inch inch inch mm mm m inch (mm) inch (mm) inch (mm) lb (kg)
W
Cooling; 5.8 (200)
Cooling; 6.7 (240)
Cooling; 7.8 (280)
—
—
Cooling; 26.0 (920)
Cooling; 8.5 (300)
Cooling; High 33, Low 26
—
Cooling; High 46
Cooling; High 46 Cooling; High 61
Cooling; 740
Cooling; 3.4
Cooling; 3.24 (11.1)
12.0
G ; Half Union 3/8”
L ; Half Union 1/4”
G ; (gas side) 3/8”
L ; (liquid side) 1/4”
12
650
1.9
3 (1.5 mm
2
)
11 - 1/32 (280)
31 - 15/32 (799)
G ; 3-way valve 3/8”
L ; 2-way valve 1/4”
G ; (gas side) 3/8”
L ; (liquid side) 1/4”
—
—
—
—
20 - 3/32 (510)
25 - 19/32 (650)
7 - 7/32 (183)
20 (9.0)
—
—
—
9 - 1/16 (230)
55 (25)
Rotary (1 cylinder) rolling piston type
Induction (2-poles)
600
7
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
Air Circulation
Heat Exchanger
Description
Material
Motor
Rated
Fan Speed
Description
Tube material
Fin material
Fin Type
Row / Stage
Type
Input
Output
Low
Medium
High
SuperHigh
FPI
Size (W × H × L)
Refrigerant Control Device
Refrigeration Oil
Refrigerant (R-410A)
Thermostat
Protection Device
Capillary Tube
Air Filter
Length
Flow Rate
Inner Diameter
Material
Style
Capacity Control
Compressor Capacitor
Fan Motor Capacitor
Unit
W
W rpm rpm rpm rpm mm
(cm
3
) g (oz) mm l/min mm
µF, VAC
µF, VAC
CS-V7DKE
Cross-flow Fan
ASG20k1
Induction (4-poles)
47
15
CU-V7DKE
Propeller Fan
PP Resin
Induction (6-poles)
63
30
Cooling; 780
Cooling; 900
Cooling; 1,050
Cooling; 1,140
Evaporator
—
—
—
795
—
Condenser
Copper
Aluminium (Pre Coat)
Copper
Aluminium (Blue Coat)
Slit Fin Corrugate Fin
(Plate fin configuration, forced draft)
2 × 15 2 × 20
21
610 × 315 × 25.4
594.7
574.7
17
× 483 × 25.4
Capillary Tube
—
—
Electronic Control
—
—
—
—
P.P.
Honeycomb
FV50S (300)
890 (31.4)
—
Overload Protector
Cooling; 570
Cooling; 6.5
Cooling; 1.2
—
Capillary Tube
—
1.5 µF, 440VAC
20 µF, 400VAC
2.0 µF, 440VAC
• Specifications are subject to change without notice for further improvement.
8
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
3.2. CS-V9DKE CU-V9DKE
Cooling Capacity
Moisture Removal
Power Source
Airflow Method
Phase
Voltage
Cycle
Unit
kW (kcal/h)
BTU/h l/h (Pint/h)
ø
V
Hz
OUTLET
INTAKE
CS-V9DKE
SIDE VIEW
3.00 (2,580)
10,230
1.7 (3.6)
Single
230
50
CU-V9DKE
TOP VIEW
Air Volume
Noise Level
Lo
Me
Hi
SHi
Electrical Data Input
Running Current
EER
Starting Current
Piping Connection Port
(Flare piping)
Pipe Size
(Flare piping)
Drain
Hose
Inner diameter
Length
Power Cord Length
Number of core-wire
Dimensions Height
Width
Depth
Net Weight
Compressor Description
Motor
Rated
Type
Output m
3
/min (cfm) m
3
/min (cfm) m
3
/min (cfm) m
3
/min (cfm) dB (A)
Cooling; 5.7 (200)
Cooling; 7.2 (250)
Cooling; 8.5 (300)
—
—
Cooling; 33.0 (1,160)
Power level (dB)
W
A
W/W (BTU/hW)
A inch inch inch inch mm mm m inch (mm) inch (mm) inch (mm) lb (kg)
W
Cooling; 9.6 (340)
Cooling; High 35, Low 26
—
Cooling; High 48
Cooling; High 48 Cooling; High 63
Cooling; 935
Cooling; 4.2
G ; Half Union 3/8”
L ; Half Union 1/4”
G ; (gas side) 3/8”
L ; (liquid side) 1/4”
12
650
1.9
3 (1.5 mm
2
)
11 - 1/32 (280)
31 - 15/32 (799)
7 - 7/32 (183)
20 (9.0)
—
Cooling; 3.21 (10.9)
20.3
—
—
G ; 3-way valve 3/8”
L ; 2-way valve 1/4”
G ; (gas side) 3/8”
L ; (liquid side) 1/4”
—
—
—
—
21 - 1/4 (540)
30 - 23/32 (780)
11 - 3/8 (289)
68 (31)
Rotary (1 cylinder) rolling piston type
Induction (2-poles)
750
9
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
Air Circulation
Heat Exchanger
Description
Material
Motor
Rated
Type
Input
Output
Fan Speed Low
Medium
High
SuperHigh
Description
Tube material
Fin material
Fin Type
Row / Stage
Refrigerant Control Device
Refrigeration Oil
Refrigerant (R-410A)
FPI
Size (W × H × L)
Thermostat
Protection Device
Capillary Tube Length
Flow Rate
Inner Diameter
Air Filter Material
Style
Capacity Control
Compressor Capacitor
Fan Motor Capacitor
Unit
W
W rpm rpm rpm rpm mm
(cm
3
) g (oz) mm l/min mm
µF, VAC
µF, VAC
CS-V9DKE
Cross-flow Fan
ASG20k1
Induction (4-poles)
47
15
CU-V9DKE
Propeller Fan
PP Resin
Induction (6-poles)
69
30
Cooling; 780
Cooling; 980
Cooling; 1,160
Cooling; 1,310
Evaporator
—
—
830
—
Condenser
Copper
Aluminium (Pre Coat)
Copper
Aluminium (Blue Coat)
Slit Fin Corrugate Fin
(Plate fin configuration, forced draft)
2 × 15 1 × 20
21
610 × 315 × 25.4
—
—
—
Electronic Control
—
—
—
—
P.P.
Honeycomb
17
835.1 × 508 × 22
Capillary Tube
FV50S (350)
930 (32.8)
—
Overload Protector
Cooling; 675
Cooling; 9.0
Cooling; 1.4
—
Capillary Tube
—
1.5 µF, 440VAC
25 µF, 370VAC
2.0 µF, 440VAC
• Specifications are subject to change without notice for further improvement.
10
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
3.3. CS-V12DKE CU-V12DKE
Cooling Capacity
Moisture Removal
Power Source
Airflow Method
Phase
Voltage
Cycle
Unit
kW (kcal/h)
BTU/h l/h (Pint/h)
ø
V
Hz
OUTLET
INTAKE
CS-V12DKE
SIDE VIEW
3.68 (3,160)
12,550
2.1 (4.4)
Single
230
50
CU-V12DKE
TOP VIEW
Air Volume
Noise Level
Lo
Me
Hi
SHi
Electrical Data Input
Running Current
EER
Starting Current
Piping Connection Port
(Flare piping)
Pipe Size
(Flare piping)
Drain
Hose
Inner diameter
Length
Power Cord Length
Number of core-wire
Dimensions Height
Width
Depth
Net Weight
Compressor Description
Motor
Rated
Type
Output m
3
/min (cfm) m
3
/min (cfm) m
3
/min (cfm) m
3
/min (cfm) dB (A)
Cooling; 6.5 (230)
Cooling; 8.0 (280)
Cooling; 9.5 (340)
—
—
Cooling; 30.8 (1,090)
Power level (dB) kW
A
W/W (BTU/hW)
A inch inch inch inch mm mm m inch (mm) inch (mm) inch (mm) lb (kg)
W
Cooling; 9.7 (343)
Cooling; High 39, Low 29
—
Cooling; High 49
Cooling; High 52 Cooling; High 64
Cooling; 1.14
Cooling; 5.3
G ; Half Union 1/2”
L ; Half Union 1/4”
G ; (gas side) 1/2”
L ; (liquid side) 1/4”
12
650
1.9
3 (1.5 mm
2
)
11 - 1/32 (280)
31 - 15/32 (799)
7 - 7/32 (183)
20 (9.0)
—
Cooling; 3.23 (11.0)
22.0
—
—
G ; 3-way valve 1/2”
L ; 2-way valve 1/4”
G ; (gas side) 1/2”
L ; (liquid side) 1/4”
—
—
—
—
21 - 1/4 (540)
30 - 23/32 (780)
11 - 3/8 (289)
73 (33)
Rotary (1 cylinder) rolling piston type
Induction (2-poles)
900
11
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
Air Circulation
Heat Exchanger
Description
Material
Motor
Rated
Fan Speed
Description
Tube material
Fin material
Fin Type
Row / Stage
Type
Input
Output
Low
Medium
High
SuperHigh
FPI
Size (W × H × L)
Refrigerant Control Device
Refrigeration Oil
Refrigerant (R-410A)
Thermostat
Protection Device
Capillary Tube
Air Filter
Length
Flow Rate
Inner Diameter
Material
Style
Capacity Control
Compressor Capacitor
Fan Motor Capacitor
Unit
W
W rpm rpm rpm rpm mm
(cm
3
) g (oz) mm l/min mm
µF, VAC
µF, VAC
CS-V12DKE
Cross-flow Fan
ASG20k1
Induction (4-poles)
47
15
CU-V12DKE
Propeller Fan
PP Resin
Induction (6-poles)
74
35
Cooling; 870
Cooling; 1,080
Cooling; 1,280
Cooling; 1,310
Evaporator
—
—
—
840
—
Condenser
Copper
Aluminium (Pre Coat)
Copper
Aluminium (Blue Coat)
Slit Fin Corrugate Fin
(Plate fin configuration, forced draft)
2 × 15 2 × 24
21
610 × 315 × 25.4
17
707.5
727.5
× 504 × 25.4
Capillary Tube
—
—
Electronic Control
—
—
—
—
P.P.
Honeycomb
FV50S (350)
1,050 (37.1)
—
Overload Protector
Cooling; 1,276
Cooling; 11.3
Cooling; 1.7
—
Capillary Tube
—
1.5 µF, 440VAC
25 µF, 370VAC
2.0 µF, 440VAC
• Specifications are subject to change without notice for further improvement.
12
4 Dimensions
4.1. Indoor Unit & Remote Control
4.1.1. CS-V7DKE CS-V9DKE CS-V12DKE
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
13
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
4.2. Outdoor Unit
4.2.1. CU-V7DKE
4.2.2. CU-V9DKE CU-V12DKE
14
5 Refrigeration Cycle Diagram
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
15
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
6 Block Diagram
16
7 Wiring Diagram
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
17
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
8 Operation Details
8.1. Cooling Operation
• Cooling operation can be set using remote control.
• This operation is applied to cool down the room temperature reaches the setting temperature set on the remote control.
• The remote control setting temperature, which takes the reading of intake air temperature sensor, can be adjusted from 16°C to 30°C.
• During cooling operation, the compressor will stop running and restart as shown in below figure.
8.1.1. Cooling Operation Time Diagram
18
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
8.2. Soft Dry Operation
• Soft Dry operation can be set using remote control.
• Soft Dry operation is applied to dehumidify and to perform a gentle cooling to the room.
• This operation starts when the intake air temperature sensor reaches the setting temperature on the remote control.
• When operation begins, Soft Dry will be switched “ON” for a maximum 10 minutes, then Soft Dry operation will be turned “OFF” for a minimum 6 minutes. After that, the Soft Dry operation will be “ON” and “OFF” based on the setting temperature as shown in below figure.
• However after 3 minutes of compressor off, during Soft Dry “OFF” (within 6 minutes Soft Dry restart control), the indoor unit will start to operate at normal Cooling mode if the intake temperature is higher than Cooling “ON” point.
8.2.1. Soft Dry Operation Time Diagram
19
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
8.3. Automatic Operation
• Automatic operation can be set using remote control.
• This operation starts to operate with indoor fan at SLo speed for 20 seconds to judge the intake air temperature.
• After judged the temperature, the operation mode is determined by referring to the below standard.
• Then, the unit start to operate at determined operation mode, until it is switched off using remote control, with the setting temperature as shown in below table.
• The setting temperature for all the operations can be changed one level up or one level down from the standard temperature as shown in below table by pressing on the temperature up or temperature down button at remote control.
Operation
Cooling
Soft Dry
Hi
(+2°C)
27°C
24°C
(Standard)
(±0°C)
25°C
22°C
Lo
(-2°C)
23°C
20°C
• The operation mode judging temperature and standard setting temperature can be increased by 2°C permanently, by open the circuit of JX1 at indoor electronic controller.
8.4. Operation Control
8.4.1. Restart Control (Time Delay Safety Control)
• When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-
− Cooling operation - the compressor stops for 3 minutes (minimum) before resume operation.
− Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.
• If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation stop, although the unit is turn on again within the period.
• This phenomenon is to balance the pressure inside the refrigerant cycle.
8.4.2. 60 Seconds Forced Operation
• Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation although the intake air temperature has reached the thermo-off temperature. However, force stop by pressing the OFF/ON operation button at the remote control is permitted.
• The reason for the compressor to force operate at minimum 60 seconds is to allow the refrigerant oil run in a full cycle and return back to the outdoor unit.
20
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
8.4.3. 7 Minutes Time Save Control
• The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls between the compressor ON temperature (A) and compressor OFF temperature (B) during the period.
• This phenomenon is to reduce the built up humidity inside a room.
8.4.4. Anti-Freezing Control
• If the temperature of the indoor heat exchanger falls below 2°C continuously for 4 minutes or more, the compressor turns off.
The fan speed setting remains the same.
• This phenomenon is to protect the indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid form returning to the compressor.
• Compressor will restart again when the indoor heat exchanger temperature rises to 10°C (Recovery).
• Restart control (Time Delay Safety Control) will be applied in this Control if the recovery time is too short.
8.4.5. Compressor Reverse Rotation Protection Control
• If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and indoor heat exchanger is 2.5°C (cooling mode) or less for continuous 2 minutes, compressor will stop and restart automatically.
• Time Delay Safety Control is activated before the compressor restart.
▲ T = Intake air temperature - Indoor heat exchanger temperature
• This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
8.4.6. Starting Current Control
• When the compressor, outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will start to operate at 1.6 second later.
• The reason of the difference is to reduce the starting current flow.
21
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
8.4.7. Anti-Dew Formation Control
• Purpose is to prevent dew formation on indoor unit air discharge area.
• When room temperature is constant (±1°C) the following conditions occur for 30 minutes continuously, anti-dew formation will activate:
− Remote Control setting temperature is less than 25°C.
− Compressor is on.
− Cooling operation mode.
− Indoor Fan motor operate at Low fan speed (CLo, Lo- or QLo).
• This control is cancelled immediately when above condition is changed, or Powerful button is pressed.
• Anti-Dew formation is control by:
1. CLo fan is changed to HLo fan.
2. QLo fan is changed to HLo fan.
8.5. Indoor Fan Speed Control
• Indoor Fan Speed can be set using remote control.
8.5.1. Fan Speed Rotation Chart
Fan Speed (rpm)
S Hi
Hi
Me
H Lo
C Lo
Lo-
S Lo
SS Lo
Q S Hi
Q Hi
Q Me
Q H Lo
Q Lo
CS-V7DKE
1140
1050
900
850
780
750
710
-
-
950
800
-
680
CS-V9DKE
1250
1140
940
840
750
750
710
-
-
1040
840
-
650
CS-V12DKE
1310
1280
1080
960
870
850
820
-
-
1180
980
-
770
22
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
8.5.2. Automatic Fan Speed Control
• When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table.
− Fan speed rotates in the range of Hi, Me and Lo-.
− Deodorizing Control will be activated.
− Auto Fan Speed during cooling operation:
1. Indoor fan will rotate alternately between off and on as shown in below diagram.
2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose.
3. For the first time the compressor operate, indoor fan will be switched to Hi fan speed from Lo- after 70 seconds from the start of compressor. This cause the room temperature to achieve the setting temperature quickly.
4. During compressor stop, indoor fan will operate at Lo- for the beginning 20 seconds to prevent higher volume of refrigerant in liquid form returning to the compressor.
5. After the compressor at turn off condition for 3 minutes, indoor fan will start to operate at Lo- to circulate the air in the room. This is to obtain the actual reading of the intake air temperature.
6. When the compressor resume operation, indoor fan will operate at Me fan speed (after 70 seconds from the restart of compressor) to provide comfort and lesser noise environment.
23
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
• Auto Fan Speed during Soft Dry operation:
1. Indoor fan will rotate alternately between off and Lo-.
2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose.
3. When compressor at turn off condition for 6 minutes, indoor fan will start fan speed at Lo- to circulate the air in the room.
This is to obtain the actual reading of intake air temperature.
8.5.3. Manual Fan Speed Control
• Manual fan speed adjustment can be carried out by using the Fan Speed selection button at the remote control.
• There are 3 types of fan speed settings: Lo, Me, Hi.
8.6. Outdoor Fan Speed Control
• There is only one speed for outdoor fan motor.
• When the air conditioner is turned on, the compressor and the outdoor fan will operate simultaneously.
• Likewise, both compressor and outdoor fan will stop at the same time if the unit is turned off.
8.7. Vertical Airflow Direction Control
8.7.1. Auto Control
• When the vertical airflow direction is set to Auto using the remote control, the louver swings up and down as shown in the diagram.
• When stop operation using the remote control, the discharge vent is reset, and stop at the closing position.
• During Cooling operation or Soft Dry operation, indoor fan motor may stop to rotate at certain periods. At that condition, the louver will stop swinging and rest at the upper limit.
• During Anti-dew condensation prevention, Airflow Direction
Auto-control angle change from 0°-32° to 20°-30° under
Cooling and Soft Dry operation mode.
Cooling and Soft Dry Operation
24
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
8.7.2. Manual Control
• When the vertical airflow direction is set to Manual using the remote control, the automatic airflow is released and the airflow direction louver move up and down in the range shown in the diagram.
• The louver can be adjusted by pressing the button to the desired louver position.
• When stop operation using the remote control, the discharge vent is reset, and stop at the closing position.
• During Anti-dew condensation prevention, Airflow Direction
Manual control angle change from 10°, 15°, 20°, 26°, 32° to
22°, 24°, 26°, 28°, 30° under Cooling and Soft Dry operation mode.
Cooling and Soft Dry Operation
8.8. Horizontal Airflow Direction Control
• The horizontal airflow direction louvers can be adjusted manually by hand.
8.9. Powerful Operation
• The Powerful operation is to achieve the setting temperature quickly.
• When Powerful operation is set, the setting temperature will be automatically decreased 3°C internally against the present setting temperature (Lower temperature limit: 16°C).
• This operation automatically will be running under SHi Fan Speed (Cooling).
• Vertical Airflow Direction:-
- In “Manual” setting, the vane will automatically shift down 10° lower than previous.
- In “Auto” setting, the vane will automatically swing up and down. However the lower limit will be shifted 10° downward.
• Powerful operation stops when:-
− Powerful operation has operate for 15 minutes.
− Powerful button is pressed again.
− Quiet button is pressed.
− Stopped by OFF/ON operation button.
− Timer OFF activates.
− Operating mode is changed.
8.10. Quiet Operation
• The Quiet operation is to provide quiet cooling operation condition compare to normal operation.
(Cooling and Soft Dry Operation condition)
• Once the Quiet Mode is set at the remote control, Quiet Mode LED illuminates. The sound level will reduce either around
2 dB(A) for Lo fan speed or 3 dB(A) for Hi/Me fan speed against the present sound level operation.
• Dew formation become severe at Quiet Lo cool, therefore Quiet Lo cool is operated only 1hr 30 min (1hr QLo, 30 min QLo
+ 80 rpm). After that, it goes back to QLo+160 (However Quiet LED remains on).
25
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
• Manual Fan Speed:-
− RPM control during Lo cool
− RPM control during Hi & Me cool
• Auto Fan Speed:-
− Cooling operation
− Soft Dry operation
• Quiet operation stops when:-
− Quiet button is pressed again.
− Powerful button is pressed.
− Stopped by OFF/ON operation button.
− Timer OFF activates.
26
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
8.11. Ionizer Operation
• The Ionizer operation is to provide fresh air effect to user by producing minus ion in discharge air.
8.11.1. Operation Control
1. Ionizer individual operation
a. When air-conditioner unit is at “OFF” condition (standby) and ION operation button at the remote control is pressed, the
Ionizer and indoor fan operations will turn on. Only ION LED will illuminates. Power LED maintain off. (1
→ 2)
b. Ionizer individual operation can be turned off by pressing the ION button again. (2
→ 1)
d. Vertical airflow direction can be adjusted using remote control during Ionizer individual operation.
e. During Ionizer individual operation, operated mode (Auto, Cool, Dry) can be activated by turning on the OFF/ON operation button. (2
→ 4)
g. When the Ionizer circuit feedback process error occur for 24 times (about 11hr 30 min.), Ionizer and Air Circulation operations will turn off with ION LED blinks continuously.
(For details, please refer to Ionizer Error detection control)
2. Operation mode & Ionizer operation.
a. When air-conditioner unit is at “ON” condition and ION operation button at the remote control is pressed, the Ionizer operation will turn on. ION & Power LED will illuminate. (3
→ 4)
b. Ionizer operation stops when:
• ION operation button is press again.
• Stopped by OFF/ON operation button.
• Timer OFF activates.
• Ionizer circuit feedback signal shows error.
without ionizer operation when it is turned on again. However, if power failure occurs during Ionizer operation together with
Cooling operation, air-conditioner will start to operate at Cooling operation with Ionizer operation when the power is resumed.
27
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
8.11.2. Error Detection Control
• The error detection control is to inform user that error occurs at ionizer system and repairing job will be needed.
• There are two types of error detection control: a. When Ionizer is ON
− If ionizer feedback = Lo for 24 times within 11hr 30min, ION LED blinks continuously.
b. When ionizer is OFF
− If ionizer feedback = Hi, ION LED blinks continuously.
• During ionizer at breakdown condition, if ionizer feedback voltage = Lo (become normal), ION LED will stop blinking.
• The error detection control can be reset by: i) Pressing the OFF/ON operation button to switch the operation OFF.
ii) Pressing the Auto Operation button to force the operation OFF.
iii) Setting the OFF Timer to stop the operation (Not applicable when ionizer is OFF).
8.12. Timer Control
• There are 2 types of timer, ON and OFF timer.
• Both ON and OFF timer can be set by pressing ON or OFF button respectively.
• By pressing ON/OFF operation button, ON Timer or OFF Timer will not be cancelled.
• To cancel the previous timer setting, press CANCEL button.
• To activate the previous timer setting, press SET button once again.
• If main power supply is switched off, the timer setting will be cancelled.
8.12.1. ON Timer
• When ON Timer is set by using the remote control, the unit will start to operate slightly before the set time, so that the room will reach nearly to the set temperature by the set time.
• For Cooling and Soft Dry operation, the operation will start 15 minutes before the set time.
• For Automatic operation, the indoor fan will operate at SLo speed for 20 seconds, 30 minutes before the set time to detect the intake air temperature to determine the operation mode. The operation indication lamp will blink at this time.
8.12.2. OFF Timer
• When OFF Timer is set by using the remote control, the unit will stop operate according to the desired setting.
8.13. Random Auto Restart Control
• If there is a power failure during operation, the air conditioner will automatically restart after 3 to 4 minutes when the power is resumed.
• It will start with previous operation mode and airflow direction.
• If there are more than one air conditioner unit in operation and power failure occur, restart time for each unit to operate will be decided randomly using 4 parameters:- intake air temperature, setting temperature, fan speed and air swing louver position.
• This Random Auto Restart Control is not available when Timer is set.
• This control can be omitted by open the circuit of JX2. (Refer Circuit Diagram)
8.14. Remote Control Signal Receiving Sound
• Long beep sound will be heard when:-
− Stopping the air conditioner using OFF/ON operation button.
− Stopping the Quiet Mode.
− Stopping the Powerful Mode.
− Stopping the Ion Mode.
• Short beep sound will be heard for others setting.
28
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
9 Operating Instructions
Thank you for purchasing Panasonic Air Conditioner
SAFETY PRECAUTIONS
■ Definition
To prevent personal injury, injury to others and property damage, the following instructions must be followed.
Incorrect operation due to failure to follow instructions will cause harm or damage, the seriousness of which is classifi ed as below:
Warning
Do not install, remove and reinstall the unit by yourself.
• Improper installation will cause leakage, electric shock or fi re. Please consult an authorized dealer or specialist for the installation work.
Warning
This sign warns of death or serious injury.
Caution
• This air conditioner must be earthed. Improper grounding will cause electric shock.
• Ensure that the drainage piping is connected properly. Otherwise, water will leak.
• Current leakage protection equipment must be installed. Otherwise, electric shock or fi re may occur.
• Do not install the unit in a potentially explosive atmosphere.
Caution
This sign warns of injury or damage to property.
The instructions to be followed are classifi ed by the following symbols:
This symbol denotes an action that is
PROHIBITED.
• Do not share power outlet.
• Do not modify power cord.
• Do not use an extension cord.
• Do not operate with wet hands.
• Do not operate or stop the unit by inserting or pulling out the power plug.
• Do not insert fi nger or other objects into the indoor or outdoor unit.
• Do not attempt to repair the unit by yourself.
• Do not use rechargeable (Ni-Cd) batteries.
• Keep the remote control away from infants and small children to prevent them from accidentally swallowing the batteries.
Warning
• Insert the power plug properly.
• Use specifi ed supply cord.
• If the supply cord is damaged or needed to be replaced, it must be replaced by the manufacturer or its service agent or a similarly qualifi ed person in order to avoid a hazard.
• Remove the batteries if the unit is not going to be use for a long period of time.
• New batteries of the same type must be inserted following the polarity stated to prevent malfunction of the remote control.
• In case of emergency or abnormal condition (burnt, smell, etc) occurs, turn off the power supply and unplug.
These symbols denote actions that are
COMPULSORY.
Safety Regulation
• Do not pull the cord to disconnect the plug.
• Do not wash the unit with water, benzene, thinner or scouring powder.
• Do not use for other purposes such as preservation of food.
• Do not use any combustible equipment at airfl ow direction.
• Do not sit or place anything on the indoor or outdoor unit.
• Do not expose directly to cold air for a long period.
The appliance is not intended for use by young children or infi rm person without supervision. Young children should be supervised to ensure that they do not play with the appliance.
Replacement or installation of power plugs shall be performed by authorized/qualifi ed personnel only. The wires in this mains lead are coloured in accordance with the following code:
(GB Standard)
Caution
• Ventilate the room regularly.
• Pay attention as to whether the installation rack is damaged after long period of usage.
• Switch off the power supply and unplug before cleaning or servicing.
• Turn off the power supply and unplug if the unit is not used for a long period of time.
Operation Condition ( O C)
Use this air conditioner under the following temperature range.
DBT: Dry Bulb Temperature
WBT: Wet Bulb Temperature
Maximum Temperature
Minimum Temperature
Indoor Outdoor
DBT WBT DBT WBT
32 23 43 26
16 11 16 11
Different countries may have different colour coding for the wires.
29
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
Note: The illustrations in this manual are for explanation purposes only and may differ from the actual unit. It is subjected to change without notice for future improvement.
PRODUCT OVERVIEW
Air intake
■ About
Remote Control Preparation
1. Pull out
OPE
N
Front panel
Supersonic air purifying device
Auto OFF/ON button
2. Insert batteries
(AAA or R03)
3. Press CLOCK button
Air filter
POWER TIMER
QUIET POWERFUL ION
Receiver
4. Set current time
Discharged air
Air inlet
Airflow direction louver
(side)
Air inlet
LCD display
Operation mode
Powerful operation
Quiet operation
Timer setting
Clock setting
(rear)
Ionizer
Do not touch during operation
Air outlet
AUTO
COOL
DRY
OFF
TIMER
MODE
OFF/ON
POWERFUL
QUIET
FANSPEED
TEMP
AIR SWING
FAN
SPEED
AIR
SWING
1
OFF
2
SET
3
CLOCK
RESET
Troubleshooting
● Operation delayed for few minutes after restart.
● Sound like water fl owing during operation.
● Mist emerges from indoor unit.
● Noisy during operations.
● Remote control/display does not work.
● The unit cannot operate.
● Outdoor unit emits water/steam.
POWER TIMER QUIET POWERFUL ION
Transmitter
Off/On
Indicator
Ion operation
Temperature setting
Fan speed selection
Airflow direction adjustment
Memory reset
5. Press again to confi rm
• Timer operation will be based on current time set.
• The batteries can be used for approximately 1 year.
• The batteries must be recycled or disposed of properly.
Remote Control Signal
• Make sure it is not obstructed.
• Maximum distances: 10m.
• Certain fluorescent lights may interfere with signal transmission.
Consult your dealer.
Auto OFF/ON Button
• To operate the unit if the remote control is misplaced or malfunctioning.
Action
Press once
Press until “beep” sound
Operation mode
Automatic
Operation
Cooling
Operation
• To OFF, press again the Auto OFF/
ON button.
• To switch the remote control signal receiving sound off or on.
1. Press until “beep” sound and release.
2. Press again until “beep-beep” sound and release.
3. Press to switch the sound off or on.
(Long “beep” - OFF; short “beep”
- ON)
➤
This is a normal self protection control.
➤
Caused by refrigerant fl ow inside.
➤
Condensation effect due to cooling process.
➤
Installation work could be slanted or front panel didn’t close properly.
➤
Check whether batteries are correctly inserted or need replacement.
➤
Check either circuit breaker is tripped, power plug is inserted correctly or timer is used correctly.
➤
Condensation or evaporation happens at piping surface.
30
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
HOW TO OPERATE
■ Operation Details
AUTO - Automatic Operation
• The unit will automatically select the operation mode according to the room temperature.
• Once the operation mode is selected, the unit will operate at the standard setting temperature as shown:
Room temperature
Operation mode
23°C & above Cool
Standard setting temperature
25°C
Below 23°C Dry 22°C
• You may press or button to change the standard setting temperature to “HI” or “LO” as shown:
Operation mode
Cool
Dry
HI
27°C
24°C
LO
23°C
20°C
COOL - Cooling Operation
• Enables you to enjoy the cooling effect at your preferred setting temperature.
• The range of temperature can be selected from 16°C ~ 30°C.
DRY - Soft Dry Operation
• Enables you to set the desired temperature at low fan speed which provides you with the dehumidifying surroundings.
• The range of temperature can be selected from 16°C ~ 30°C.
Select the desired operation.
Start the operation.
Set the temperature.
● Supersonic air purifying device (super alleru-buster) operates automatically while the air conditioner is switched on.
● Powerful, Quiet and Ion operations could be activated in all operation modes.
● Press
OFF/ON
button again to stop the operation.
Hint
● To save electricity, close the curtains when using air conditioner to prevent sunlight and heat from coming in.
Troubleshooting
● The room has a peculiar odour.
● Air conditioner does not cool effi ciently.
➤
This may be a damp smell emitted by the wall, carpet, furniture or clothing in the room.
➤
Ensure the temperature has been set correctly.
➤
Ensure windows and doors have been closed properly.
➤
Ensure fi lters are cleaned or replaced when necessary.
➤
Ensure inlet and outlet vents of the units have not been obstructed.
31
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
HOW TO OPERATE
Enables powerful operation.
Enables quiet operation.
IO N
Enables ion operation.
■ Operations Details
POWERFUL
• To achieve setting temperature quickly. It will operate for 15 minutes and return to the previous setting.
QUIET
• To provide a quiet environment.
ION
• To provide fresh air effect by producing negative ions.
FA N SPEED
Select fan speed.
FAN SPEED
• To provide you with the various fan speed selections.
• There are 3 levels of fan speed in addition to automatic fan speed.
• Automatic fan speed:
The speed of the indoor fan is automatically adjusted according to the operation.
AIR SWI NG
Adjust the vertical airfl ow direction louver.
AIR SWING
• To ventilate air in the room.
• There are 5 selections in addition to automatic vertical air fl ow direction.
• If automatic vertical airfl ow direction has been set, the louver swings up and down automatically.
• Please do not adjust the vertical airfl ow direction louver manually.
• Horizontal airfl ow direction louver could be adjusted manually.
● Ion operation could be activated independently.
● Powerful and Quiet operations could not be activated at the same time.
● Powerful, Quiet and Ion operations could be cancelled by pressing the respective button again.
Hints
● If you wish to have the cool air blowing directly on you, set the airfl ow direction downward but not for an excessive length of time, as it may harm your health.
● Approximately 10% of electricity can be saved if you set the temperature 1°C higher than the desired temperature during cooling operation.
Troubleshooting
● ION indicator on the indoor unit is blinking.
● Indoor fan stops occasionally during Automatic Fan
Speed setting.
➤
Press ION button twice. If the indicator is still blinking, please consult the dealer.
➤
This is an advanced feature that helps to remove smell from the surrounding area during operation.
32
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
HOW TO OPERATE
■ Operation Details
TIMER
• Use the ON timer to turn on the air conditioner at the desired time. This will give you a cooling environment, e.g. when you return from work or wake up.
• When the ON timer is set, operation will start 15 minutes before the actual set time.
• Use the OFF timer to stop the air conditioner operation at the desired time. This can save electricity while you are going out or sleeping.
• The set timer will repeat daily once it is set.
• If there is a power failure, you can press SET button to restore the previous setting once the power is resumed.
• If the timer is cancelled, you can restore the previous setting by pressing SET button.
Select ON or
OFF timer.
Set the desired time.
Confi rm the setting.
CA NCEL
Cancel the selected timer.
● Ensure the clock on the remote control has been set correctly.
● You could use the ON and OFF timers at the same time.
● To cancel either the ON or OFF timer, press
or , then press .
Hint
● Press CLOCK more than 10 seconds to change the time format from 24 hours to AM/PM format.
● For your convenience, you could set the air conditioner to operate automatically by using both ON and OFF timer.
Troubleshooting
● TIMER indicator always on.
● POWER indicator is blinking 15 minutes before ON timer is activated.
➤
Timer is activated and the setting will repeat itself daily.
➤
The unit is determining the operation mode by sensing the room temperature. This happens when it has been set to AUTO operation mode.
33
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
CARE & CLEANING
Vacuum, wash and dry.
Remove
SUPERSO NIC AIR
PURIFYI NG DEVICE
Vacuum the super alleru-buster fi lter.
Remove
FRO
Raise and Pull to remove.
Wash and dry.
Remove
IO
NT PANEL
POWER
TIMER QUIET POWERFUL ION
I NDOOR UNIT
Wipe gently.
NIZER
Clean with cotton bud.
■ Washing Instructions
• Do not use benzene, thinner or scouring powder.
• Use soaps or neutral household detergent (
≃
pH7) only.
• Do not use water with temperature higher than 40°C.
INDOOR UNIT
• Wipe the unit gently with a soft, dry cloth.
AIR FILTER
• It is recommended to clean the air fi lters once every 2 weeks.
• Purchase the replacement fi lter if it is damaged.
Part no.: CWD001144
SUPER ALLERU-BUSTER
• It is recommended to clean the fi lter every 6 months.
• Replace the fi lter every 3 years or purchase the replacement fi lter if it is damaged.
Part no.: CZ-SA13P
IONIZER
• It is recommended to clean the ionizer every 6 months.
■ Preparation for extended
Non-operation
• Operate the unit for 2~3 hours using ion operation to dry the internal parts.
• Turn off the power supply and unplug.
• Remove the remote control batteries.
■ Pre-season Inspection
• This inspection is recommended before operating the air conditioner at every season.
• Check if the remote control batteries needed to be replaced.
• Ensure there is no obstruction at all air intake and outlet vents.
• After the start of operation for 15 minutes, it is normal if the temperature differences between air intake and outlet vents at indoor unit is:-
Operation
Cooling
Temperature
8°C
Vacuum, wash and dry the frame.
Hints
● Clean the fi lter regularly as dirty fi lters will cause unpurifi ed air, low cooling or heating capacity, unpleasant smells and higher energy consumption.
● The unit will become dirty and the performance of the unit will decrease after used for several seasons. Please consult an authorized dealer to perform seasonal inspections in addition to regular cleaning.
● This air conditioner is equipped with a built-in surge protective device. However, in order to further protect your air conditioner from being damaged by abnormally strong lightning activity, you may switch off the power supply.
34
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
10 Installation Instructions
1.
Philips screw driver
2.
Level gauge
5.
Spanner
Required tools for Installation Works
9.
Gas leak detector
6.
Pipe cutter 10. Measuring tape
13. Multimeter
14. Torque wrench
18 N.m (1.8 kgf.m)
42 N.m (4.2 kgf.m)
55 N.m (5.5 kgf.m)
15. Vacuum pump 3.
Electric drill, hole core drill
(ø70 mm)
7.
Reamer
4.
Hexagonal wrench (4 mm) 8.
Knife
11. Thermometer
12. Megameter 16. Gauge manifold
10.1. Safety Precautions
• Read the following “SAFETY PRECAUTIONS” carefully before installation.
• Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model to be installed.
• The caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below. Incorrect installation due to ignoring of the instruction will cause harm or damage, and the seriousness is classified by the following indications.
WARNING
CAUTION
This indication shows the possibility of causing death or serious injury.
This indication shows the possibility of causing injury or damage to properties only.
The items to be followed are classified by the symbols:
Symbol with background white denotes item that is PROHIBITED from doing.
• Carry out test running to confirm that no abnormality occurs after the installation. Then, explain to user the operation, care and maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.
WARNING
1.
Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage, electrical shock or fire.
2.
Install according to this installation instruction strictly. If installation is defective, it will cause water leakage, electrical shock or fire.
3.
Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water leakage, fire or electrical shock.
4.
Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly done, the set will drop and cause injury.
5.
For electrical work, follow the local national wiring standard, regulation and this installation instruction. An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.
6.
Use the specified cable (1.5 mm
2
) and connect tightly for indoor/outdoor connection. Connect tightly and clamp the cable so that no external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
7.
Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electrical shock.
8.
When carrying out piping connection, take care not to let air substances other than the specified refrigerant go into refrigeration cycle. Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury.
9.
When connecting the piping, do not allow air or any substances other than the specified refrigerant (R410A) to enter the refrigeration cycle. Otherwise, this may lower the capacity, cause abnormally high pressure in the refrigeration cycle, and possibly result in explosion and injury.
10.
• When connecting the piping, do not use any existing (R22) pipes and flare nuts. Using such same may cause abnormally high pressure in the refrigeration cycle (piping), and possibly result in explosion and injury. Use only
R410A materials.
• Thickness of copper pipes used with R410A must be more than 0.8 mm. Never use copper pipes thinner than 0.8
mm.
• It is desirable that the amount of residual oil is less than 40 mg/10 m.
11. Do not modify the length of the power supply cord or use of the extension cord, and do not share the single outlet with other electrical appliances. Otherwise, it will cause fire or electrical shock.
35
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
CAUTION
1.
The equipment must be earthed. It may cause electrical shock if grounding is not perfect.
2.
Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fire.
3.
Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture.
ATTENTION
1. Selection of the installation location.
Select a installation location which is rigid and strong enough to support or hold the unit, and select a location for easy maintenance.
2.
Power supply connection to the room air conditioner.
Connect the power supply cord of the room air conditioner to the mains using one of the following method.
Power supply point shall be the place where there is ease for access for the power disconnection in case of emergency.
In some countries, permanent connection of this room air conditioner to the power supply is prohibited.
Use an approved 10A power plug with earth pin for the connection to the socket..
connection. It must be a double pole switch with a minimum 3.5 mm contact gap.
3.
Do not release refrigerant.
Do not release refrigerant during piping work for installation, reinstallation and during repairing a refrigeration parts. Take care of the liquid refrigerant, it may cause frostbite.
4.
Installation work.
It may need two people to carry out the installation work.
5.
Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
36
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
Attached accessories
Indoor/outdoor Unit Installation Diagram
Applicable piping kit
CZ-3F5, 7BP (V7DK, V9DK, W7DK, W9DK)
CZ-4F5, 7, 10BP (V12DK, W12DK)
Select the best location
INDOOR UNIT
• There should not be any heat source or steam near the unit.
• There should not be any obstacles blocking the air circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
• Recommended installation height for indoor unit shall be at least 2.3 m.
OUTDOOR UNIT
• If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the condenser is not obstructed.
• There should not be any animal or plant which could be affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.
• Do not place any obstacles which may cause a short circuit of the discharged air.
• If piping length is over the rated length, additional refrigerant should be added as shown in the table.
• This illustration is for explanation purposes only.
The indoor unit will actually face a different way.
37
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
10.2. Indoor Unit
10.2.1. SELECT THE BEST LOCATION
(Refer to “Select the best location” section)
10.2.3. TO DRILL A HOLE IN THE WALL
AND INSTALL A SLEEVE OF
PIPING
10.2.2. HOW TO FIX INSTALLATION
PLATE
The mounting wall is strong and solid enough to prevent it from the vibration.
1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes about 15 mm from the wall.
Caution
When the wall is hollow, please be sure to use the sleeve for tube ass’y to prevent dangers caused by mice biting the connecting cable.
4. Finish by sealing the sleeve with putty or caulking compound at the final stage.
The centre of installation plate should be at more than 450 mm at right and left of the wall.
The distance from installation plate edge to ceiling should more than 67 mm.
From installation plate left edge to unit’s left side is 74 mm.
From installation plate right edge to unit’s right is 94 mm.
:
:
:
For left side piping, piping connection for liquid should be about 15 mm from this line.
For left side piping, piping connection for gas should be about 45 mm from this line.
For left side piping, piping connection cable should be about 800 mm from this line
10.2.4. INDOOR UNIT INSTALLATION
1. For the right rear piping
1. Mount the installation plate on the wall with 5 screws or more.
(If mounting the unit on the concrete wall consider using anchor bolts.)
• Always mount the installation plate horizontally by aligning the marking-off line with the thread and using a level gauge.
2. Drill the piping plate hole with ø70 mm hole-core drill.
• Line according to the arrows marked on the lower left and right side of the installation plate. The meeting point of the extended line is the centre of the hole. Another method is by putting measuring tape at position as shown in the diagram above. The hole centre is obtained by measuring the distance namely 150 mm and 125 mm for left and right hole respectively.
• Drill the piping hole at either the right or the left and the hole should be slightly slanted to the outdoor side.
2. For the right and right bottom piping
38
3. For the embedded piping
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
39
(This can be used for left rear piping & left bottom piping also.)
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
10.2.5. CONNECT THE CABLE TO THE
INDOOR UNIT
1. The inside and outside connecting cable can be connected without removing the front grille.
2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 3 (V7DK,
V9DK, V12DK) or 5 (W7DK, W9DK, W12DK) × 1.5 mm
2 flexible cord, type designation 245 IEC 57 or heavier cord.
• Ensure the color of wires of outdoor unit and the terminal Nos. are the same to the indoor’s respectively.
• Earth lead wire shall be longer than the other lead wires as shown in the figure for the electrical safety in case of the slipping out of the cord from the anchorage.
• Secure the cable onto the control board with the holder
(clamper).
40
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
INSTALLATION OF SUPER ALLERU-BUSTER FILTER
1. Open the front panel.
2. Remove the air filter.
3. Remove Supersonic air purifying device.
4. Open the Supersonic air purifying device frame.
5. Insert the super alleru-buster filter and close the Supersonic air purifying device frame as show in illustration at right.
HOW TO TAKE OUT FRONT GRILLE
Please follow the steps below to take out front grille if necessary such as when servicing.
1. Open the intake grille and remove the screw at the front of the front grille.
2. Set the vertical airflow direction louvers to the horizontal position.
3. Slide down the 2 caps on the front grille as shown in the illustration below, and then remove the 2 mounting screws.
4. Pull the lower section of the front grille towards you to remove the front grille.
When reinstalling the front grille, first set the vertical airflow direction louver to the horizontal position and then carry out above steps 2 - 3 in the reverse order.
AUTO SWITCH OPERATION
The below operations will be performed by pressing the “AUTO” switch.
1. AUTO OPERATION MODE
The Auto operation will be activated immediately once the Auto Switch is pressed.
2. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE)
The Test Run operation will be activated if the Auto Switch is pressed continuously for more than 5 sec. A “beep” sound will occur at the fifth sec., in order to identify the starting of Test Run operation
3. REMOTE CONTROLLER RECEIVING SOUND ON/OFF
The ON/OFF of remote controller receiving sound can be change over by pressing the following step:
a. Release the Auto Switch after Test Run operation is activated.
b. Then, within 20 sec., after a., press Auto Switch for more than 5 sec.
A “beep” “beep” sound will occur at the fifth sec., then release the Auto Switch.
controller receiving sound status will be reversed between ON and OFF.
Long “beep” sound indicates that remote controller receiving sound is OFF.
Short “beep” sound indicates that remote controller receiving sound is ON.
41
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
10.3. Outdoor Unit
10.3.1. SELECT THE BEST LOCATION
(Refer to “Select the best location” section)
10.3.2. INSTALL THE OUTDOOR UNIT
• After selecting the best location, start installation according to Indoor/Outdoor Unit Installation Diagram.
1. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut. (ø10 mm).
2. When installing at roof, please consider strong wind and earthquake. Please fasten the installation stand firmly with bolt or nails.
MODEL
V7DK, V9DK, W7DK, W9DK
V12DK, W12DK
A
474
570
B
87
105
C
18.5
18.5
D
261
320
10.3.3. CONNECTING THE PIPING
Connecting The Piping To Indoor Unit
Please make flare after inserting flare nut (locate at joint portion of tube assembly) onto the copper pipe. (In case of using long piping)
Connect the piping
• Align the center of piping and sufficiently tighten the flare nut with fingers.
• Further tighten the flare nut with torque wrench in specified torque as stated in the table.
MODEL
V7DK, V9DK, W7DK, W9DK
V12DK, W12DK
Piping size (Torque)
Gas
3/8” (42 N.m)
1/2” (55 N.m)
Liquid
1/4” (18 N.m)
1/4” (18 N.m)
Connecting The Piping To Outdoor Unit
Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge. Make flare after inserting the flare nut
(located at valve) onto the copper pipe.
Align center of piping to valves and then tighten with torque wrench to the specified torque as stated in the table.
CUTTING AND FLARING THE PIPING
1. Please cut using pipe cutter and then remove the burrs.
2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder entering the pipe.
3. Please make flare after inserting the flare nut onto the copper pipes.
42
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
10.3.4. EVACUATION OF THE EQUIPMENT
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure.
1. Connect a charging hose with a push pin to the Low and High side of a charging set and the service port of the 3-way valve.
• Be sure to connect the end of the charging hose with the push pin to the service port.
2. Connect the center hose of the charging set to a vacuum pump with check valve, or vacuum pump and vacuum pump adaptor.
3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 cmHg (0 MPa) to
-76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4. Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not move after approximately five minutes.
Note: BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valve at torque of 18 N.m with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” using a hexagonal wrench (4 mm).
8. Mount valve caps onto the 2-way valve and the 3-way valve.
• Be sure to check for gas leakage.
CAUTION
• If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure:
• If the leak stops when the piping connections are tightened further, continue working from step 3.
• If the leak does not stop when the connections are retightened, repair the location of leak.
• Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may cause frostbite.
10.3.5. CONNECT THE CABLE TO THE OUTDOOR UNIT
1. Remove the control board cover from the unit by loosening the screw.
2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 3 (V7DK, V9DK, V12DK) or 5 (W7DK, W9DK, W12DK) × 1.5 mm
2 flexible cord, type designation 245 IEC 57 or heavier cord.
3. Secure the cable onto the control board with the holder (clamper).
4. Attach the control board cover back to the original position with the screw.
43
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
10.3.6. PIPE INSULATION
1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap the insulated piping end to prevent water from going inside the piping.
2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM with thickness 6 mm or above.
DISPOSAL OF OUTDOOR UNIT DRAIN WATER
• If a drain elbow is used, the unit should be placed on a stand which is taller than 3 cm.
• If the unit is used in an area where temperature falls below
0°C for 2 or 3 days in succession, it is recommended not to use a drain elbow, for the drain water freezes and the fan will not rotate.
NOTE:
These equipment shall be connected to a suitable mains network with a main impedance less than the following:
CHECK THE DRAINAGE
• Open front panel and remove air filters.
(Drainage checking can be carried out without removing the front grille.)
• Pour a glass of water into the drain tray-styrofoam.
• Ensure that water flows out from drain hose of the indoor unit.
CHECK ITEMS
Is there any gas leakage at flare nut connections?
Has the heat insulation been carried out at flare nut connection?
Is the connecting cable being fixed to terminal board firmly?
Is the connecting cable being clamped firmly?
Is the drainage OK?
(Refer to “Check the drainage” section)
Is the earth wire connection properly done?
Is the indoor unit properly hooked to the installation plate?
Is the power supply voltage complied with rated value?
Is there any abnormal sound?
Is the cooling operation normal?
Is the thermostat operation normal?
Is the remote control’s LCD operation normal?
Is the super alleru-buster filter is installed??
EVALUATION OF THE PERFORMANCE
• Operate the unit at cooling operation mode for fifteen minutes or more.
• Measure the temperature of the intake and discharge air.
• Ensure the difference between the intake temperature and the discharge is more than 8°C.
44
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
11 Installation And Servicing Air Conditioner Using R410A
11.1. Outline
11.1.1. About R410A Refrigerant
1. Converting air conditioners to R410A
Since it was declared in1974 that chlorofluorocarbons (CFC), hydro chlorofluorocarbons (HCFC) and other substances pose a destructive danger to the ozone layer in the earth´s upper stratosphere (20 to 40 km above the earth), measures have been taken around the world to prevent this destruction.
The R22 refrigerant which has conventionally been used in ACs is an HCFC refrigerant and, therefore, possesses this ozonedestroying potential. International regulations (the Montreal Protocol on Ozone-Damaging Substances) and the domestic laws of various countries call for the early substitution of R22 by a refrigerant which will not harm the ozone layer.
• In ACs, the HFC refrigerant which has become the mainstream alternative is called R410A.Compared with R22, the pressure of R410A is approximately 1.6 times as high at the same refrigerant temperature, but the energy efficiency is about the same. Consisting of hydrogen (H), fluorine (F) and carbon (C), R410A is an HFC refrigerant. Another typical HFC refrigerant is R407C. While the energy efficiency of R407C is somewhat inferior to that of R410A, it offers the advantage of having pressure characteristics which are about the same as those of R22, and is used mainly in packaged ACs.
2. The characteristics of HFC (R410A) refrigerants
a. Chemical characteristics
The chemical characteristics of R410A are similar to those of R22 in that both are chemically stable, non-flammable refrigerants with low toxicity.
However, just like R22, the specific gravity of R410A gas is heavier than that of air. Because of this, it can cause an oxygen deficiency if it leaks into a closed room since it collects in the lower area of the room. It also generates toxic gas when it is directly exposed to a flame, so it must be used in a well ventilated environment where it will not collect.
Composition (wt%)
Boiling point (°C)
Vaporizing pressure (25°C)
Saturated vapor density
Flammability
Ozone-destroying point (ODP)
Global-warming point (GWP)
Table 1 Physical comparison of R410A and R22
R410A
R32/R125 (50/50)
-51.4
1.56 Mpa (15.9 kgf/cm
2
)
64.0 kg/m
3
Non-flammable
0
1730
R22
R22 (100)
-40.8
0.94 Mpa (9.6 kgf/cm
2
)
44.4 kg/m
3
Non-flammable
0.055
1700
b. Compositional change (pseudo-azeotropic characteristics)
R410A is a pseudo-azeotropic mixture comprising the two components R32 and R125. Multi-component refrigerants with these chemical characteristics exhibit little compositional change even from phase changes due to vaporization (or condensation), which means that there is little change in the circulating refrigerant composition even when the refrigerant leaks from the gaseous section of the piping.
Accordingly, R410A can be handled in almost the same manner as the single-component refrigerant R22. However, when charging, because there is a slight change in composition between the gas phase and the liquid phase inside a cylinder or other container, charging should basically begin with the liquid side.
As seen in Table 2, the gas pressure of R410A is approximately 1.6 times as high as that of R22 at the same refrigerant temperature, which means that special R410A tools and materials with high-pressure specifications must be used for all refrigerant piping work and servicing.
Refrigerant Temperature (°C)
-20
0
20
40
60
65
Table 2 Comparison of R410A and R22 saturated vapor density
Unit: MPa
R410A
0.30
0.70
1.35
2.32
3.73
4.15
R22
0.14
0.40
0.81
1.43
2.33
2.60
45
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
d. R410A refrigerating machine oil
Conventionally, mineral oil or a synthetic oil such as alkylbenzene has been used for R22 refrigerating machine oil. Because of the poor compatibility between R410A and conventional oils like mineral oil, however, there is a tendency for the refrigerating machine oil to collect in the refrigerating cycle. For this reason, polyester and other synthetic oils which have a high compatibility with R410A are used as refrigerating machine oil.
Because of the high hygroscopic property of synthetic oil, more care must be taken in its handling than was necessary with conventional refrigerating machine oils. Also, these synthetic oils will degrade if mixed with mineral oil or alkylbenzene, causing clogging in capillary tubes or compressor malfunction. Do not mix them under any circumstances.
11.1.2. Safety Measures When Installing/Servicing Refrigerant Piping
Cause the gas pressure of R410A is approximately 1.6 times as high as that of R22, a mistake in installation or servicing could result in a major accident. It is essential that you use R410A tools and materials, and that you observe the following precautions to ensure safety.
1. Do not use any refrigerant other than R410A in ACs that have been used with R410A.
2. If any refrigerant gas leaks while you are working, ventilate the room. Toxic gas may be generated if refrigerant gas is exposed to a direct flame.
3. When installing or transferring an AC, do not allow any air or substance other than R410A to mix into the refrigeration cycle. If it does, the pressure in the refrigeration cycle can become abnormally high, possibly causing an explosion and/or injury.
4. After finishing the installation, check to make sure there is no refrigerant gas leaking.
5. When installing or transferring an AC, follow the instructions in the installation instructions carefully. Incorrect installation can result in an abnormal refrigeration cycle or water leakage, electric shock, fire, etc.
6. Do not perform any alterations on the AC unit under any circumstances. Have all repair work done by a specialist. Incorrect repairs can result in an water leakage, electric shock, fire, etc.
11.2. Tools For Installing/Servicing Refrigerant Piping
11.2.1. Necessary Tools
In order to prevent an R410A AC from mistakenly being charged with any other refrigerant, the diameter of the 3-way valve service port on the outdoor unit has been changed. Also, to increase its ability to withstand pressure, the opposing dimensions have been changed for the refrigerant pipe flaring size and flare nut. Accordingly, when installing or servicing refrigerant piping, you must have both the R410A and ordinary tools listed below.
Flaring
Bending, connecting pipes
Air purging
Type of work
Gas leak inspection
Table 3 Tools for installation, transferring or replacement
Ordinary tools
Flaring tool (clutch type), pipe cutter, reamer
R410A tools
Copper pipe gauge for clearance
Adjustment, flaring tool (clutch type)*1)
Torque wrench (nominal diameter 1/4,
3/8,1/2). Fixed spanner (opposing sides
12 mm, 17 mm, 19 mm). Adjustable wrench, Spring bender
Vacuum pump. Hexagonal wrench
(opposing sides 4 mm)
Manifold gauge, charging hose, vacuum pump adaptor
Gas leak inspection fluid or soapy water Electric gas leak detector for HFC refrigerant*2)
*1) You can use the conventional (R22) flaring tool. If you need to buy a new tool, buy the R410A type.
*2) Use when it is necessary to detect small gas leaks.
For other installation work, you should have the usual tools, such as screwdrivers (+,-), a metal-cutting saw, an electrical drill, a hole core drill (65 or 70 dia.), a tape measure, a level, a thermometer, a clamp meter, an insulation tester, a voltmeter, etc.
Type of work
Refrigerant charging
Table 4 Tools for serving
Ordinary tools R410A tools
Electronic scale for refrigerant charging.
Refrigerant cylinder. Charging orifice and packing for refrigerant cylinder
Brazing (Replacing refrigerating cycle part*1)
Nitrogen blow set (be sure to use nitrogen blowing for all brazing), and brazing machine
*1) Always replace the dryer of the outdoor unit at the same time. The replacement dryer is wrapped in a vacuum pack. Replace it last among the refrigerating cycle parts. Start brazing as soon as you have opened the vacuum pack, and begin the vacuuming operation within 2 hours.
46
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
11.2.2. R410A Tools
1. Copper tube gauge for clearance adjustment
(used when flaring with the conventional flaring tool (clutch type))
• This gauge makes it easy to set the clearance for the copper tube to 1.0-1.5 mm from the clamp bar of the flaring tool.
2. Flaring tool (clutch type)
• In the R410A flaring tool, the receiving hole for the clamp bar is enlarged so the clearance from the clamp bar can be set to 0-0.5 mm, and the spring inside the tool is strengthened to increase the strength of the pipeexpanding torque. This flaring tools can also be used with R22 piping, so we recommend that you select it if you are buying a new flaring tool.
Fig. 1 Copper tube gauge for clearance adjustment
Fig. 2 Flaring tool (clutch type)
3. Torque wrenches
Fig. 3 Torque wrenches
For 1/4 (opposite side x torque)
For 3/8 (opposite side x torque)
For 1/2 (opposite side x torque)
Table 5
Conventional wrenches
17 mm x 18 N.m (180 kgf.cm)
22 mm x 42 N.m (420 kgf.cm)
24 mm x 55 N.m (550 kgf.cm)
R410A wrenches
17 mm x 18 N.m (180 kgf.cm)
22 mm x 42 N.m (420 kgf.cm)
26 mm x 55 N.m (550 kgf.cm)
4. Manifold gauge
• Because the pressure is higher for the R410A type, the conventional type cannot be used.
Table 6 Difference between R410A and conventional high / low-pressure gauges
Conventional gauges R410A gauges
High-pressure gauge (red)
Low-pressure gauge (blue)
-76 cmHg - 35 kgf/cm
3
-76 cmHg - 17 kgf/cm
3
-0.1 - 5.3 Mpa -76 cmHg - 53 kgf/cm
-0.1 - 3.8 Mpa -76 cmHg - 38 kgf/cm
3
3
• The shape of the manifold ports has been changed to prevent the possibility of mistakenly charging with another type of refrigerant.
Port size
Table 7 Difference between R410A and conventional manifold port size
Conventional gauges R410A gauges
7/16 UNF 20 threads 1/2 UNF 20 threads
47
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
5. Charging hose
• The pressure resistance of the charging hose has been raised to match the higher pressure of R410A. The hose material has also been changed to suit HFC use, and the size of the fitting has been changed to match the manifold ports.
Pressure resistance
Material
Fig. 4 Manifold gauge charging hose
Table 8 Difference between R410A and conventional charging hoses
Working pressure
Bursting pressure
Conventional hoses
3.4 MPa (35 kgf/cm
3
)
17.2 MPa (175 kgf/cm
3
)
NBR rubber
R410A hoses
5.1 MPa (52 kgf/cm
3
)
27.4 MPa (280 kgf/cm
3
)
HNBR rubber Nylon coating inside
6. Vacuum pump adaptor
• When using a vacuum pump for R410A, it is necessary to install an electromagnetic valve to prevent the vacuum pump oil from flowing back into the charging hose. The vacuum pump adaptor is installed for that purpose. if the vacuum pump oil (mineral oil) becomes mixed with R410A, it will damage the unit.
Fig. 5 Vacuum pump adaptor
7. Electric gas leak detector for HFC refrigerant
• The leak detector and halide torch that were used with
CFC and HCFC cannot be used with R410A (because there is no chlorine in the refrigerant).
• The present R134a leak detector can be used, but the detection sensitivity will be lower (setting the sensitivity for R134a at 1, the level for R410A will drop to 0.6).
• For detecting small amounts of gas leakage, use the electric gas leak detector for HFC refrigerant. (Detection sensitivity with R410A is about 23 g/year).
Fig. 6 Electric gas leak detector for HFC refrigerant
48
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
8. Electronic scale for refrigerant charging
• Because of the high pressure and fast vaporizing speed of R410A, the refrigerant cannot be held in a liquid phase inside the charging cylinder when charging is done using the charging cylinder method, causing bubbles to form in the measurement scale glass and making it difficult to see the reading. (Naturally, the conventional R22 charging cylinder cannot be used because of the differences in the pressure resistance, scale gradation, connecting port size, etc.)
• The electronic scale has been strengthened by using a structure in which the weight detector for the refrigerant cylinder is held by four supports. It is also equipped with two connection ports, one for R22 (7/16 UNF, 20 threads) and one for R410A (1/2 UNF, 20 threads), so it can also be used for conventional refrigerant charging.
• There are two types of electronic scales, one for 10-kg cylinders and one for 20-kg cylinders. (The 10-kg cylinder is recommended.)
Refrigerant charging is done manually by opening and closing the valve.
9. Refrigerant cylinders
• The R410A cylinders are labeled with the refrigerant name, and the coating color of the cylinder protector is pink, which is the color stipulated by ARI of the U.S.
• Cylinders equipped with a siphon tube are available to allow the cylinder to stand upright for liquid refrigerant charging.
Fig. 7 Electronic scale for refrigerant charging
Fig. 8 Refrigerant cylinders
10. Charging orifice and packing for refrigerant cylinders
• The charging orifice must match the size of the charging hose fitting (1/2 UNF, 20 threads).
• The packing must also be made of an HFC-resistant material.
Fig. 9 Charging orifice and packing
11.2.3. R410A Tools Which Are Usable for R22 Models
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
Copper tube gauge for clearance adjustment
Flaring tool (clutch type)
Table 9 R410A tools which are usable for R22 models
R410A tools Usable for R22 models
OK
OK
Manifold gauge
Charging hose
Vacuum pump adaptor
Electric gas leak detector for HFC refrigerant
Electronic scale for refrigerant charging
Refrigerant cylinder
Charging orifice and packing for refrigerant cylinder
NG
NG
OK
NG
OK
NG
NG
49
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
11.3. Refrigerant Piping Work
11.3.1. Piping Materials
It is recommended that you use copper and copper alloy jointless pipes with a maximum oil adherence of 40 mg/10m. Do not use pipes that are crushed, deformed, or discolored (especially the inside surface). If these inferior pipes are used, impurities may clog the expansion valves or capillaries.
Because the pressure of ACs using R410A is higher than those using R22, it is essential that you select materials that are appropriate for these standards.
The thickness of the copper tubing used for R410A is shown in Table 10. Please be aware that tubing with a thickness of only 0.7
mm is also available on the market, but this should never be used.
Nominal diameter
1/4
3/8
1/2
Table 10 Copper tube thickness (mm)
Soft pipe
Outside diameter (mm)
6.35
9.52
12.7
R410A
0.80
0.80
0.80
Thickness (mm)
(Reference) R22
0.80
0.80
0.80
11.3.2. Processing and Connecting Piping Materials
When working with refrigerant piping, the following points must be carefully observed: no moisture od dust must be allowed to enter the piping, and there must be no refrigerant leaks.
1. Procedure and precautions for flaring work
a. Cut the pipe
Use a pipe cutter, and cut slowly so the pipe will not be deformed.
b. Remove burrs and clean shavings from the cut surface
If the shape of the pipe end is poor after removing burrs, or if shavings adhere to the flared area, it may lead to refrigerant leaks.
To prevent this, turn the cut surface downward and remove burrs, then clean the surface, carefully.
used on the AC unit)
d. Flaring
Check the clamp bar and the cleanliness of the copper pipe.
Be sure to use the clamp bar to do the flaring with accuracy. Use either an R410A flaring tool, or a conventional flaring tool. flaring tools come in different sizes, so be sure to check the size before using. When using a conventional flaring tool, use the copper pipe gauge for clearance adjustment, etc., to ensure the correct A dimension (see Fig. 10)
Fig. 10 Flaring dimensions
Fig. 11 Relation between the flare nut structure and flaring tool end
50
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
Nominal diameter
1/4
3/8
1/2
Nominal diameter
1/4
3/8
1/2
Nominal diameter
1/4
3/8
1/2
Nominal diameter
1/4
3/8
1/2
Outside diameter
(mm)
6.35
9.52
12.70
Table 11 R410A flaring dimensions
Wall thickness
(mm)
R410A flaring tool, clutch type
0.8
0.8
0.8
0 - 0.5
0 - 0.5
0 - 0.5
A (mm)
Conventional flaring tool
Clutch type
1.0 - 1.5
1.0 - 1.5
1.0 - 1.5
Wing-nut type
1.5 - 2.0
1.5 - 2.0
2.0 - 2.5
Outside diameter
(mm)
6.35
9.52
12.70
Table 12 R22 flaring dimensions
Wall thickness
(mm)
R410A flaring tool, clutch type
0.8
0.8
0.8
0 - 0.5
0 - 0.5
0 - 0.5
A (mm)
Conventional flaring tool
Clutch type Wing-nut type
0.5 - 1.0
0.5 - 1.0
0.5 - 1.0
1.0 - 1.5
1.0 - 1.5
1.5 - 2.0
Outside diameter (mm)
6.35
9.52
12.70
Table 13 R410A flare and flare nut dimensions Unit: mm
Wall thickness
(mm)
A +0, -0.4
B dimension
C dimension
0.8
9.1
9.2
6.5
0.8
0.8
13.2
16.6
13.5
16.0
9.7
12.9
D dimension
13
20
23
Flare nut width
17
22
26
Outside diameter (mm)
6.35
9.52
12.70
Table 14 R22 flare and flare nut dimensions Unit: mm
Wall thickness
(mm)
A +0, -0.4
B dimension
C dimension
0.8
9.0
9.2
6.5
0.8
0.8
13.0
16.2
13.5
16.0
9.7
12.9
D dimension
13
20
20
Flare nut width
17
22
24
2. Procedure and precautions for flare connection
a. Check to make sure there is no scratches, dust, etc., on the flare and union.
b. Align the flared surface with the axial center of the union.
torque value for R22. Be careful, because if the torque is too weak, it may lead to a gas leak. If it is too strong, it may split the flare nut or make it impossible to remove the flare nut.
Nominal diameter
1/4
3/8
1/2
Table 15 R410A tightening torque
Outside diameter (mm)
Tightening torque
N.m (kgf.cm)
6.35
14 - 18 (140 - 180)
9.52
12.70
33 - 42 (330 -420)
55 (550)
Torque wrench tightening torque
N.m (kgf.cm)
18 (180)
42 (420)
55 (550)
11.3.3. Storing and Managing Piping Materials
1. Types of piping and their storage
The following is a general classification of the refrigerant pipe materials used for ACs.
Because the gas pressure of R410A is approximately 1.6 times as high as that of R22, copper pipes with the thickness shown in Table 10, and with minimal impurities must be used. Care must also be taken during storage to ensure that pipes are not crushed, deformed, or scratched, and that no dust, moisture or other substance enters the pipe interior. When storing sheathed copper pipes or plain copper pipes, seal the openings by pinching or taping them securely.
2. Makings and management
a. Sheathed copper pipes and copper-element pipes
When using these pipes, check to make sure that they are the stipulated thickness. For flare nuts, be sure to used the same nut that is used on the AC unit.
51
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
b. Copper pipes
Use only copper pipes with the thickness given in table 10, and with minimal impurities. Because the surface of the pipe is exposed, you should take special care, and also take measures such as marking the pipes to make sure they are easily distinguished from other piping materials, to prevent mistaken use.
3. Precautions during refrigerant piping work
Take the following precautions on-site when connecting pipes. (Keep in mind that the need to control the entry of moisture and dust is even more important that in conventional piping).
a. Keep the open ends of all pipes sealed until connection with AC equipment is complete.
b. Take special care when doing piping work on rainy days. The entering of moisture will degrade the refrigerating machine oil, and lead to malfunctions in the equipment.
the seal, it must be thoroughly purged with nitrogen, or dried with a vacuum pump.
11.4. Installation, Transferring, Servicing
11.4.1. Inspecting Gas Leaks with a Vacuum Pump for New Installations (Using New
Refrigerant Piping)
1. From the viewpoint of protecting the global environment, please do not release refrigerant into the atmosphere.
a. Connect the projecting side (pin-pushing side) of the charging hose for the manifold gauge to the service port of the 3-way valve. (1)
b. Fully open the handle Lo of the manifold gauge and run the vacuum pump. (2) (If the needle of the low-pressure gauge instantly reaches vacuum, re-check step a).)
MPa (-76 cmHg). Once the vacuum process has finished, fully close the handle Lo of the manifold gauge and stop the vacuum pump operation, then remove the charging hose that is connected to the vacuum pump adaptor. (Leave the unit in that condition for 1-2 minutes, and make sure that the needle of the manifold gauge does not return.) (2) and (3)
d. Turn the valve stem of the 2-way valve 90° counter-clockwise to open it, then, after 10 seconds, close it and inspect for a gas leak (4)
e. Remove the charging hose from the 3-way valve service port, then open both the 2-way valve and 3-way valve. (1) (4) (Turn the valve stem in the counter-clockwise direction until it gently makes contact. Do not turn it forcefully).
caps with a torque wrench (42 N.m (4.2 kgf.m)) or (55 N.m (5.5 kgf.m)). (6)
g. After attaching each of the caps, inspect for a gas leak around the cap area. (5) (6)
Precautions
• Be sure to read the instructions for the vacuum pump, vacuum pump adaptor and manifold gauge prior to use, and follow the instructions carefully.
• Make sure that the vacuum pump is filled with oil up to the designated line on the oil gauge.
• The gas pressure back flow prevention valve on the charging hose is generally open during use. When you are removing the charging hose from the service port, it will come off more easily if you close this valve.
52
Fig. 12 Vacuum pump air purging configuration
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
11.4.2. Transferring (Using New Refrigerant Piping)
1. Removing the unit
a. Collecting the refrigerant into the outdoor unit by pumping down
The refrigerant can be collected into the outdoor unit (pumping down) by pressing the TEST RUN button, even when the temperature of the room is low.
• Check to make sure that the valve stems of the 2-way valve and 3-way valve have been opened by turning them counterclockwise. (Remove the valve stem caps and check to see that the valve stems are fully opened position. Always use a hex wrench (with 4-mm opposing sides) to operate the valve stems.)
• Press the TEST RUN button on the indoor unit, and allow preliminary operation for 5-6 minutes. (TEST RUN mode)
• After stopping the operation, let the unit sit for about 3 minutes, then close the 2-way valve by turning the valve stem in the clockwise direction.
• Press the TEST RUN button on the indoor unit again, and after 2-3 minutes of operation, turn the valve stem of the 3way valve quickly in the clockwise direction to close it, then stop the operation.
• Tighten the caps of the 2-way valve and 3-way valve to the stipulated torque.
• Remove the connection pipes (liquid side and gas side).
b. Removing the indoor and outdoor units.
• Disconnect the pipes and connecting electric cables from between the indoor and outdoor units.
• Put capped flare nuts onto all of the pipe connections of the indoor and outdoor units, to make sure no dust or other foreign matter enters.
• Remove the indoor and outdoor units.
2. Installing the unit
Install the unit using new refrigerant piping. Follow the instructions in section 4.1 to evacuate the pipes connecting the indoor and outdoor units, and the pipes of the indoor unit, and check for gas leaks.
11.4.3. AC Units Replacement (Using Existing Refrigerant Piping)
When replacing an R410A AC unit with another R410A AC unit, you should re-flare the refrigerant piping. Even though the replacement AC unit uses the R410A, problems occur when, for example, either the AC unit maker or the refrigerating machine oil is different.
When replacing an R22 AC unit with an R410A AC unit, the following checks and cleaning procedures are necessary but are difficult to do because of the chemical characteristics of the refrigerating machine oil (as described in items c) and d) of section
About R410A Refrigerant). In this case, you should use new refrigerant piping rather than the existing piping.
1. Piping check
Because of the different pressure characteristics of R22 and R410A, the design pressure for the equipment is 1.6 times different. the wall thickness of the piping must comply with that shown in Table 10, but this is not easy to check. Also, even if the thickness is correct, there may be flattened or bent portions midway through the piping due to sharp curves. Buried sections of the piping also cannot be checked.
2. Pipe cleaning
A large quantity of refrigerating machine oil (mineral oil) adheres to existing pipes due to the refrigeration cycle circulation. If the pipes are used just as they are for the R410A cycle, the capacity will be lowered due to the incompatibility of this oil with the
R410A, or irregularities may occur in the refrigeration cycle. For this reason, the piping must be thoroughly cleaned, but this is difficult with the present technology.
11.4.4. Refrigerant Compatibility (Using R410A Refrigerant in R22 ACs and Vice Versa)
Do not operate an existing R22 AC with the new R410A refrigerant. Doing so would result in improper functioning of the equipment or malfunction, and might lead to a major accident such as an explosion in the refrigeration cycle. Similarly, do not operate an
R410A AC with R22 refrigerant. The chemical reaction between the refrigerating machine oil used in R410A ACs and the chlorine that is contained in R22 would cause the refrigerating machine oil to degrade and lead to malfunction.
53
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
11.4.5. Recharging Refrigerant During Servicing
When recharging is necessary, insert the specified amount of new refrigerant in accordance with the following procedure.
1. Connect the charging hose to the service port of the outdoor unit.
2. Connect the charging hose to the vacuum pump adaptor. At this time, fully open the 2-way valve and 3-way valve.
3. Fully open the handle Lo of the manifold gauge, turn on the power of the vacuum pump and continue the vacuum process for at least one hour.
4. Confirm that the low pressure gauge shows a reading of -0.1 Mpa (-76 cmHg), then fully close the handle Lo, and turn off the vacuum pump. Wait for 1-2 minutes, then check to make sure that the needle of the Low pressure gauge has not returned. See
Fig. 13 for the remaining steps of this procedure.
5. Set the refrigerant cylinder onto the electronic scale, then connect the hose the cylinder and to the connection port for the electronic scale. (1)(2)
Precaution:
Be sure to set up the cylinder for liquid charging. If you use a cylinder equipped with a siphon tube, you can charge the liquid without having to turn the cylinder around
6. Remove the charging hose of the manifold gauge from the vacuum pump adaptor, and connect it to the connection port of the electronic scale. (2)(3)
7. Open the valve of the refrigerant cylinder, then open the charging valve slightly and close it. Next, press the check valve of the manifold gauge and purge the air. (2)(4) (Watch the liquid refrigerant closely at this point.)
8. After adjusting the electronic scale to zero, open the charging valve, then open the valve Lo of the manifold gauge and charge with the liquid refrigerant. (2)(5) (Be sure to read the operating instructions for the electronic scale.)
9. If you cannot charge the stipulated amount, operate the unit in the cooling mode while charging a little of the liquid at a time
(about 150 g/time as a guideline). If the charging amount is insufficient from one operation, wait about one minute, then use the same procedure to do the liquid charging again.
Precaution:
Never use the gas side to allow a larger amount of liquid refrigerant to be charged while operating the unit.
10. Close the charging valve, and after charging the liquid refrigerant inside the charging hose, fully close the valve Lo of the manifold gauge, and stop the operation of the unit. (2)(5)
11. Quickly remove the charging hose from the service port. (6) If you stop midway through, the refrigerant that is in the cycle will be discharged.
12. After putting on the caps for the service port and operating valve, inspect around the caps for a gas leak. (6)(7)
Fig. 13 Re-charging refrigerant
54
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
11.4.6. Brazing
As brazing requires sophisticated techniques and experiences, it must be performed by a qualified person.
In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry nitrogen gas (N
2
) flow.
<Brazing Method for Preventing Oxidation>
1. Attach a reducing valve to the nitrogen gas cylinder.
2. Apply a seal onto the clearance between the piping and inserted pipe for the nitrogen gas in order to prevent the nitrogen gas from flowing backward.
3. When the nitrogen gas is flowing, be sure to keep the piping end open.
4. Adjust the flow rate of nitrogen gas so that it is lower than 0.05 m
3
/h, or 0.02 MPa (0.2 kgf/cm
2
) by means of the reducing valve.
5. After taking the steps above, keep the nitrogen gas flowing until the piping cools down to a certain extent (i.e. temperature at which pipes are touchable with finger).
6. Completely remove the flux after brazing.
Fig. 14 Prevention of Oxidation during Brazing
Cautions during brazing
1. General Cautions
a. The brazing strength should be high as required.
b. After operation, airtightness should be kept under pressurized condition.
d. The refrigerant pipe work should not become blocked with scale or flux.
e. The brazed part should not restrict the flow in the refrigerant circuit.
2. Prevention of Overheating
Due to heating, the interior and exterior surfaces of treated metal may oxidize. Especially, when the interior of the refrigerant circuit oxidizes due to overheating, scale occurs and stays in the circuit as dust, thus exerting a fatally adverse effect. So, make brazing at adequate brazing temperature and with minimum of heating area.
3. Overheating Protection
In order to prevent components near the brazed part from overheating damage or quality deterioration due to flame or heat, take adequate steps for protection such as (1) by shielding with a metal plate, (2) by using a wet cloth, and (3) by means of heat absorbent.
4. Movement during Brazing
Eliminate all vibration during brazing to protect brazed joints from cracking and breakage.
5. Oxidation Preventative
In order to improve the brazing efficiency, various types of antioxidant are available on the market. However, the constituents of these are widely varied, and some are anticipated to corrode the piping materials, or adversely affect HFC refrigerant, lubricating oil, etc. Exercise care when using an oxidation preventive.
11.4.7. Servicing Tips
The drier must also be replaced whenever replacing the refrigerant cycle parts. Replacing the refrigerant cycle parts first before replacing the drier. The drier is supplied in a vacuum pack. Perform brazing immediately after opening the vacuum pack, and then start the vacuum within two hours. In addition, the drier also needs to be replaced when the refrigerant has leaked completely. (Applicable for drier models only)
55
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
12 Servicing Information
12.1. Distinction Of Lead Free (PbF) Printed Circuit Board
• Printed circuit boards (manufactured) using lead free solder will have a PbF stamp on the Printed Circuit board.
CAUTION
• Pb free solder has a higher melting point than standard solder; typically the melting point is 50 - 70°F (30 - 40°C) higher.
Please use a high temperature solder iron and set it to 700 ± 20°F (370 ± 10°C).
• Pb free solder will tend to splash when heated too high (about 1100°F/600°C).
• If you must use Pb solder, please completely remove all of the Pb free solder on the pin or solder area before applying Pb solder. If this is not practical, be sure to heat the Pb free solder until it melts, before applying Pb solder.
12.2. Indoor Electronic Controllers Removal Procedures
• Electronic controller and Display Complete unit can be seen by following the below removal procedures.
Fig. 1
− Remove the 2 caps and 2 screws at the bottom of the
Front Grille. (Fig. 1)
Fig. 3
− Release the taps on top and on the right side of metal plate cover. (Fig. 3)
− Then remove the metal plate cover. (Fig. 3)
− Remove the indicator complete screw, and then remove the indicator complete. (Fig. 3)
Fig. 2
− Remove the Front Grille Complete. (Fig. 2)
56
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
Fig. 4
− To remove the electronic controller.
− Release CN-FM connectors. (Fig. 4)
− Release CN-Sonic connector. (Fig. 4)
− Release CN-FB connector. (Fig. 4)
− Release CN-ION connector. (Fig. 4)
− Release CN-TH connector. (Fig. 4)
− Release CN-STM connector. (Fig. 4)
− Release CN-REC/DISP connector. (Fig. 4)
Fig. 5
− Press the hook to the right then take out the PCB. (Fig.
5)
− Release Ry-Pwr connector (black and brown) and Ac-
Wht connector from the PCB. (Fig. 5)
12.3. Indoor Fan Motor And Cross Flow Fan Removal Procedures
• Remove Control Board Cover
Fig. 6
− Remove the screw on the left of the unit. (Fig. 6)
− Pull the hook to the left and lift up the evaporator.
(Fig. 6)
− Pull down the Discharge Grille Complete. (Fig. 6)
Fig. 7
57
Fig. 8
− Remove indoor pipe sensor and air intake sensor from the evaporator. (Fig. 7)
− Remove the earth wire from the evaporator. (Fig. 7)
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
− Release the generator complete wire (green and red).
(Fig. 8)
− Remove 2 screws on the right and 1 screw at the left side of the control board. (Fig. 7)
− Press down the hook on the left side of control board.
(Fig. 7)
− Then pull out the Control Board Complete from the unit.
(Fig. 7)
Fig. 10
− Push up the evaporator and remove cross flow fan by pulling both cross flow fan and fan motor. (Fig. 10)
Fig. 9
− Remove the cross flow fan bushing from the chassis.
(Fig. 9)
− Loosen the fan boss screw at the cross flow fan. (Fig. 9)
12.4. Remote Control Reset
• When the batteries are inserted for the first time or the batteries are replaced, you may notice the indications at remote control’s display screen blink continuously and not functionable. If this condition happens, try to reset the remote control by pushing the reset terminal with a pointing device.
• You may also do the reset to erase the setting at remote control and restore back the default setting.
58
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
12.5. Auto OFF/ON Button
• The “Auto OFF/ON Button” (behind the front grille) is used to operate the air conditioner if remote control is misplaced or mulfunctioning.
• Forced cooling operation is possible by pressing the “Auto OFF/ON Button” for more than 5s where “beep” sound is heard then release the button.
• User able to select remote control transmission code and toggle remote control signal receiving sound under various setting mode.
• To enter various setting mode:
− Press the “Auto OFF/ON Button” continuously for 5s (“beep” sound is heard) and release.
− Within 20s, press the “Auto OFF/ON Button” continuously for 5s again (2 “beep” sound is heard) and release.
− Various setting mode has limit up to 20s. Then return to normal operation.
12.5.1. Toggle Remote Control Signal Receiving Sound
• Under various setting mode, press the “Auto OFF/ON Button” to toggle the remote control sound.
− Short “beep”: Turn ON remote control signal receiving sound.
− Long “beep”: Turn OFF remote control signal receiving sound.
• After “Auto OFF/ON Button” is pressed, the 20s counter for various setting mode is restarted.
12.5.2. Select Remote Control Transmission Code
• There are 4 types of remote control transmission code could be selected and stored in EEPROM of indoor unit. The indoor unit will only operate when received signal with same transmission code from remote control. This could prevent signal interference when there are 2 or more indoor unit installed nearby together.
• To change remote control transmission code, short or open jumpers at the remote control printed circuit board.
• Under various setting mode, after select the transmission code combination of remote control, press any button of remote control to transmit a signal to indoor unit. The transmission code will be stored in EEPROM.
• After signal is received, the various setting mode is cancelled and return to normal operation.
59
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
13 Troubleshooting Guide
13.1. Refrigeration Cycle System
In order to diagnose malfunctions, make sure that there are no electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the power source, malfunction of a compressor and a fan.
The normal outlet air temperature and pressure of the refrigeration cycle depends on various conditions, the standard values for them are shown in the table to the right.
60
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
13.2. Relationship Between The Condition Of The Air Conditioner And
Pressure And Electric Current
Cooling Mode
Condition of the air conditoner Low Pressure High Pressure Electric current during operation
Insufficient refrigerant (gas leakage)
Clogged capillary tube or Strainer
Short circuit in the indoor unit
Heat radiation deficiency of the outdoor unit
Inefficient compression
• Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
13.3. Diagnosis Methods Of A Malfunction Of A Compressor
Nature of fault Symptom
• Electric current during operation becomes approximately 20% lower than the normal value.
Insufficient compressing of a compressor
• The discharge tube of the compressor becomes abnormally hot (normally 70 to 90°C).
• The difference between high pressure and low pressure becomes almost zero.
Locked compressor
• Electric current reaches a high level abnormally, and the value exceeds the limit of an ammeter. In some cases, a breaker turns off.
• The compressor is a humming sound.
61
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
14 Technical Data
14.1. Thermostat Characteristics
14.1.1. CS-V7DKE CS-V9DKE CS-V12DKE
14.2. Sensible Capacity Chart
14.2.1.
● CS-V7DKE
230V
Indoor wet bulb temp.
17.0°C
19.0°C
19.5°C
22.0°C
TC
2.38
2.61
2.85
30
SHC
1.80
1.89
1.96
IP
0.68
0.69
0.70
TC
2.22
2.40
2.44
2.66
14.2.2.
● CS-V9DKE
230V
Indoor wet bulb temp.
17.0°C
19.0°C
19.5°C
22.0°C
TC
2.98
3.27
3.56
30
SHC
2.26
2.36
2.45
14.2.3.
● CS-V12DKE
230V
Indoor wet bulb temp.
17.0°C
19.0°C
19.5°C
22.0°C
TC
3.65
4.01
4.37
30
SHC
2.77
2.90
3.01
IP
0.86
0.88
0.89
IP
1.04
1.06
1.08
TC
2.78
3.00
3.05
3.33
TC
3.41
3.68
3.75
4.08
TC - Total Cooling Capacity (kW)
SHC - Sensible Heat Capacity (kW)
IP - Input Power (kW)
35
SHC
1.73
1.82
1.88
Outdoor Temp. (°C)
IP
0.73
0.74
0.74
0.76
TC
2.07
2.27
2.48
40
SHC
1.66
1.75
1.82
IP
0.78
0.79
0.81
35
SHC
2.16
2.27
2.36
Outdoor Temp. (°C)
IP
0.93
0.94
0.94
0.96
TC
2.59
2.84
3.10
40
SHC
2.08
2.18
2.27
IP
0.99
1.01
1.03
35
SHC
2.65
2.78
2.89
Outdoor Temp. (°C)
IP
1.12
1.14
1.14
1.17
TC
3.17
3.48
3.80
40
SHC
2.55
2.68
2.79
IP
1.20
1.22
1.25
TC
1.88
2.07
2.25
46
SHC
1.58
1.66
1.73
IP
0.84
0.86
0.87
TC
2.35
2.58
2.81
46
SHC
1.98
2.08
2.17
IP
1.07
1.09
1.11
TC
2.89
46
SHC
2.42
IP
1.30
3.17
3.45
2.55
2.66
1.32
1.34
Indoor 27°C/19°C
Outdoor 35°C/24°C
62
14.3. Operation Characteristics
14.3.1. CS-V7DKE CU-V7DKE
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
14.3.2. CS-V9DKE CU-V9DKE
63
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
14.3.3. CS-V12DKE CU-V12DKE
64
15 Exploded View (Indoor Unit)
15.1. CS-V7DKE CS-V9DKE CS-V12DKE
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
Note:
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
65
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
16 Replacement Parts List (Indoor Unit)
16.1. CS-V7DKE CS-V9DKE CS-V12DKE
25
26
27
28
29
30
20
21
22
24
31
32
33
34
13
14
15
16
17
18
19
REF. NO.
1
2
3
4
5
8
9
6
7
10
11
12
41
42
43
44
45
46
47
48
49
35
36
37
38
39
40
PART NAME & DESCRIPTION
CHASSY COMPLETE
FAN MOTOR
CROSS FLOW FAN COMPLETE
BEARING ASS’Y
SCREW - CROSS FLOW FAN
EVAPORATOR
FLARE NUT
FLARE NUT
HOLDER SENSOR
DISCHARGE GRILLE COMPLETE
VERTICAL VANE
CONNECTING BAR
CONNECTING BAR
AIR SWING MOTOR
LEAD WIRE - AIR SWING MOTOR
CAP - DRAIN TRAY
HORIZONTAL VANE
BACK COVER CHASSIS
CONTROL BOARD CASING
TERMINAL BOARD COMPLETE
POWER SUPPLY CORD
ELECTRONIC CONTROLLER - MAIN
SENSOR COMPLETE
CONTROL BOARD FRONT COVER
INDICATOR COMPLETE
INDICATOR HOLDER
INDICATOR HOLDER
CONTROL BOARD TOP COVER
REMOTE CONTROL COMPLETE
FRONT GRILLE COMPLETE
INTAKE GRILLE
GRILLE DOOR
AIR FILTER
SCREW - FRONT GRILLE
CAP - FRONT GRILLE
DRAIN HOSE
INSTALLATION PLATE
BAG COMPLETE - INSTALLATION SCREW
FULCRUM
ELECTRONIC CONTROLLER - IONIZER
CASING - IONIZER
CASING - IONIZER
ION GENERATOR
SUPERSONIC AIR PURIFYING DEVICE
ELECTRONIC CONTROLLER SUPERSONIC
SUPER ALLERU BUSTER FILTER
FRAME FR AIR FILTER SUPERSONIC
FRAME FR AIR FILTER SUPERSONIC
CS-V7DKE
CWD50C1377
CWA921181
CWH02C1031
CWH64K007
CWH4580304
CWB30C1599
CWT25086(1/4”)
CWT25087 (3/8”)
CWH32143
CWE20C2366
CWE241150
CWE261066
CWE261070
CWA98260
CWA67C3977
CWH521096
CWE241173
CWD932454
CWH102259
CWA28C2073
CWA20C2159
CWA743659
CWA50C2122
CWH131195
CWE39C1115
CWD932429
CWD932430
CWH131207
CWA75C2600
CWE11C3125
CWE22C1154
CWE141073
CWD001144
XTT4+16C
CWH521109
CWH851063
CWH361067
CWH82C067
CWH621046
CWA743675
CWD932464
CWD932431
CWH94C0001
CWH91C1013
CWA743874
CWD00C1133
CWD011026
CWD011027
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
9
1
QTY.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
(Note)
• All parts are supplied from PHAAM, Malaysia (Vendor Code: 061).
• “O” marked parts are recommended to be kept in stock.
CWA743660
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
CS-V9DKE
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
CS-V12DKE
←
←
←
←
←
CWB30C1583
←
CWT25096 (1/2”)
←
←
←
←
←
←
←
←
←
←
←
CWA28C2075
←
CWA743553
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
REMARKS
0
0
0
0
0
0
0
0
0
0
66
17 Exploded View (Outdoor Unit)
17.1. CU-V7DKE
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
Note:
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
67
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
17.2. CU-V9DKE CU-V12DKE
Note:
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
68
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
18 Replacement Parts List (Outdoor Unit)
18.1. CU-V7DKE
REF. NO.
1
2
3
4
8
9
10
11
5
6
7
12
13
14
15
16
17
18
19
20
22
23
PART NAME & DESCRIPTION
CHASSY ASS’Y
SOUND PROOF MATERIAL
FAN MOTOR BRACKET
SCREW - FAN MOTOR BRACKET
FAN MOTOR
SCREW - FAN MOTOR MOUNT
PROPELLER FAN ASS’Y
NUT - PROPELLER FAN
COMPRESSOR
ANTI - VIBRATION BUSHING
NUT - COMPRESSOR MOUNT
CONDENSER
CAPILLARY TUBE ASS’Y
STRAINER
HOLDER COUPLING ASS’Y
2-WAY VALVE (LIQUID)
3-WAY VALVE (GAS)
TERMINAL COVER
NUT - TERMINAL COVER
SOUND PROOF BOARD
TERMINAL BOARD ASS’Y
CAPACITOR - COMPRESSOR
24
25
HOLDER CAPACITOR
CAPACITOR - FAN MOTOR
26
27
28
29
30
32
34
35
36
37
38
39
40
41
CABINET SIDE PLATE (L)
CABINET SIDE PLATE (R)
CABINET FRONT PLATE
WIRE NET
CABINET TOP PLATE
CONTROL BOARD COVER
OPERATION INSTRUCTIONS (ENG., ESP., ITA., NED., POR.,
GRE., BUL.)
INSTALLATION INSTRUCTIONS (ENG., FRA., ESP. & DEU.)
OVERLOAD PROTECTOR
HOLDER O.L.P.
CHECK VALVE COMPLETE
OPERATION INSTRUCTIONS (FRA., DEU., SWE., NOR.)
INSTALLATION INSTRUCTIONS (ITA., NED., POR. & GRE.)
INSTALLATION INSTRUCTIONS (BUL.)
(Note)
• All parts are supplied from PHAAM, Malaysia (Vendor Code: 061).
• “O” marked parts are recommended to be kept in stock.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
3
1
1
1
3
1
1
1
1
QTY.
1
1
1
2
1
1
1
1
1
1
1
1
CU-V7DKE
CWD50K2107
CWG302292
CWD541074
CWH551060
CWA951392
CWH55406
CWH03K1020
CWH56053
5RS084DAB21
CWH50077
CWH56000
CWB32C1495
CWB15K1145
CWB11025
CWH351047
CWB021233
CWB011275
CWH171011
CWH7080300
CWH151074
CWA28K1064
CWA312074
(20µF, 400VAC)
CWH301038
DS441125BPQD
(2.0µF, 440VAC)
CWE041110A
CWE04C1042
CWE06K1052
CWD041057A
CWE031041A
CWH131193
CWF564472
CWF612663
CWA121066
CWH7041200
CWB03C1024
CWF564473
CWF612664
CWF612679
REMARKS
0
0
0
0
0
0
0
69
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
18.2. CU-V9DKE CU-V12DKE
11
12
13
14
15
16
17
18
19
20
21
22
23
REF. NO.
1
2
3
4
8
9
10
5
6
7
PART NAME & DESCRIPTION
CHASSY ASS’Y
SOUND PROOF MATERIAL
FAN MOTOR BRACKET
SCREW - FAN MOTOR BRACKET
FAN MOTOR
SCREW - FAN MOTOR MOUNT
PROPELLER FAN ASS’Y
NUT - PROPELLER FAN
COMPRESSOR
ANTI - VIBRATION BUSHING
NUT - COMPRESSOR MOUNT
CONDENSER
CAPILLARY TUBE ASS’Y
STRAINER
HOLDER COUPLING ASS’Y
2-WAY VALVE (LIQUID)
3-WAY VALVE (GAS)
TERMINAL COVER
NUT - TERMINAL COVER
SOUND PROOF BOARD
CONTROL BOARD CASING
TERMINAL BOARD ASS’Y
CAPACITOR - COMPRESSOR
24
25
HOLDER CAPACITOR
CAPACITOR - FAN MOTOR
1
1
1
1
3
1
1
1
1
1
1
1
1
1
1
3
1
3
1
QTY.
1
1
1
2
1
1
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
CABINET SIDE PLATE (L)
CABINET SIDE PLATE (R)
CABINET FRONT PLATE
WIRE NET
CABINET TOP PLATE
PLATE - C. B. COVER
CONTROL BOARD COVER
HANDLE
OPERATION INSTRUCTIONS (ENG., ESP., ITA.,
NED., POR., GRE., BUL.)
INSTALLATION INSTRUCTIONS (ENG., ESP., FRA.,
DEU.)
OVERLOAD PROTECTOR
CHECK VALVE COMPLETE
OPERATION INSTRUCTIONS (FRA., DEU., SWE.,
NOR.)
INSTALLATION INSTRUCTIONS (NED., GRE., ITA.,
POR.)
INSTALLATION INSTRUCTIONS (BUL.)
HOLDER O.L.P.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
(Note)
• All parts are supplied from PHAAM, Malaysia (Vendor Code: 061).
• “O” marked parts are recommended to be kept in stock.
CU-V9DKE
CWD50K2071
CWG302088
CWD541030
CWH551059
CWA951114
CWH55406
CWH03K1006
CWH56053
5PS112DAG21
CWH50077
CWH56000
CWB32C1561
CWB15K1138
CWB11025
CWH351023
CWB021058
CWB011063
CWH171011
CWH7080300
CWH151022
CWH102202
CWA28K1064
DS371256CPNA
(25µF, 370VAC)
CWH30057
DS441205NPQA
(2.0µF, 440VAC)
CWE041031A
CWE041036A
CWE06K1034
CWD04C1007
CWE031014A
CWH131088
CWH13C1065
CWE161010
CWF564472
CWF612663
CWA121221
CWB03C1027
CWF564473
CWF612664
CWF612679
CWH7041200
CU-V12DKE
←
←
←
←
CWA951116
←
←
←
5PS132DAG21
←
CWH4582065
CWB32C1562
CWB15K1133
CWB111011
←
←
CWB011062
←
←
CWH151023
←
←
←
←
←
←
CWE041037A
←
CWD04C1008
←
←
←
←
←
←
CWA121214
CWB03C1026
←
←
←
-
REMARKS
0
0
0
0
0
0
0
0
70
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
19 Electronic Circuit Diagram
19.1. Indoor Unit & Outdoor Unit
SCHEMATIC DIAGRAM 1/4
ELECTRONIC CONTROL UNIT
Auto
SW
SW01
2
1
R11
1k
C01
0.01
µ
R07
10k
SUPERSONIC COMPLETE
R603
1M
C601
0.1
µ
X601
IC601
R602
5.1k
R601
1k
1
2
3
CN-SONIC
1
2
3
CN-SONIC
R78
10k c
R55
1k
BZ
BZ01 e
R12
1k
C02
0.01
µ
R88
5.1k
b
Q01
C143XKTX
DISPLAY COMPLETE
IC401
1
2
3
R401 47
Ω
TIMER/AIR SW(ORG)
POWER(GRN)
+
C401
47
µ
6.3V
D402
D401
POWERFUL(ORG)
QUIET(ORG)
ION(GRN)
D403
D404
D405
D406
SUPERSONIC(BLU)
7
6
5
4
3
2
1
10
9
8
CN-DISP
CN-DISP
4
5
6
7
8
9
10
1
2
3
C24 0.01
µ
C25 0.01
µ
C26 0.01
µ
R15
180
Ω
C28
0.01
µ
C27
0.01
µ
C35
0.01
µ
C29
0.1
µ
R27 220
Ω
R17
220
Ω
R73
3.3k
Ω
R13 220
Ω
R14 220
Ω c e
R68
100
Ω b
Q09
R31
1k
R56
1k
CN-HA
4
3
2
1
C22
0.01
µ
R58
10k
R59 1k
JP5
C23
0.01
µ
R60
10k
71
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
SCHEMATIC DIAGRAM 2/4
C39
R75 1k
R76 1k
R74 1k
R77 1k
R06 24k
R18
R19
R20
R21
R22
R23
R24
R25
C38
1000p
R10
10k
D12
D11
D10
D09
D08
D07
D06
D05
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
1
P50
2
P51
3
P52
4
P53
5
P54
6
P55
7
P56
8 P57
9
Vss0
10 VDD0
11
P30
12
P31
13
P32
14
P33
15
P34
16
P35
RY-PWR DRIVE SIGNAL
DISPLAY
AUTO RESTART
STEPPING
MOTOR
DRIVE
SIGNAL
BUZZER
IC01
INTAKE AIR TEMP
PIPE TEMP
GROUND
AUTO OPERATION
TEST RUN
REMOTE CONTROL
SOUND
POWER CLOCK INPUT
REMOTE-CONTROL
COMMAND INPUT
OSC
RESET
POWER
TIMER SHORTEN
P71
48
TOD
47
P03
46
INTP2
45
INTP1
44
INTP0
43
Vss1
42
X1
41
X2
40
IC(VPP)
39
XT1
38
XT2 37
RESET
36
AVDD
35
AVref
34
AN10
33
JP2
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
4
5
6
1
2
3
7
8
16
15
14
13
12
11
10
9
IC05
B1HBGGF00013
RY-PWR
R05
43
Ω
1/2W
R04
43
Ω
1/2W
5 4 3 2 1
CN-STM1
5 4 3 2 1 (ZH5)
VERTICAL
6
7
4
5
1
2
3
8 16
15
14
13
12
11
10
9
IC06
B1HBGGF00013
R09
10k
JX2
5
6
DI
DO
SK
4
CS 3
7 GND Vcc 2
8 RS
R/B
1
C05
0.1
µ
16V
IC02
C3EBDG000021
C04
0.1
µ
16V
R30
20k
R33
15k
C08
0.1
µ
16V
(PH)
CN-TH
PIPE TEMP. SENSOR
(20k 3950)
4 3 2 1
(RED)
AIR TEMP. SENSOR
(15k 3950)
72
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
SCHEMATIC DIAGRAM 3/4
R66
5
2
T01
8
R48
13
IC04
REGULATOR
DB01
~
+
~
C17
3300
µ
35V
I 12V O
G
IC03
REGULATOR
C14
470
µ
25V
I
5V
G
O
C11
100
µ
16V
Q02
C143XKTX b
4.7k c
SSR02
10k e
Q03
C143XKTX b 4.7k c
SSR01
10k e
R32
150k
R41
1k
X01
C16
0.01
µ
R44
1k
ZNR01 c e b
R03 1.3k
R29
1.6k
C07
0.1
µ
16V
D16
R57 12k
D15
R47 12k
C19
0.047
µ
L01
125
µH
FUSE
T 2A L 250V
C03
0.047
µ
RY-PWR
AC-WHT
L
P
TEMPERATURE
FUSE
1
2
TO OUTDOOR
4.096 MHz
(47pF X 2)
JP3
C18
0.1
µ
16V
R49 1k
R50
100k
C36
C10
0.1
µ
16V
R38
C15
0.01
µ
R43
R79
10k
JP4
JX1
C37
0.01
µ
R37
10k
R02 1k
R01
10k
1
TEST
2 c e b
Q05
C2412KTX
R51
10k c
Q06
C2412KTX b e
R54
6.2k
R53
10k
Z01
7.5V
R52
6.2k
C21
10
µ
50V
C12
0.1
µ
16V
R36
1k
R67
R62
R61
10k c
Q08 b e
R64
6.2k
R63
6.2k
Q07 c b e
C31
0.01
µ
D01
C32
0.01
µ
CN-FM
C-FM
1.5
µ
CN-FB
1
2
3
1
2
3
4
5
FAN MOTOR
2
1
4
3
CN-ION
73
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
SCHEMATIC DIAGRAM 4/4
1
2
TO INDOOR
B
CAPACITOR
B
R
COMPRESSOR
Y
OVER LOAD
PROTECTOR
1 2 3
OR
1
OVER LOAD
PROTECTOR
4
GR
V7/12DK
V9DK
B B
Y
FAN
MOTOR
R
HIGH VOLTAGE IONIZER
EH-4P
2
1
4
3
CH1
VIN
GND
ERR
F1
C2
R2 R3
Q1 c b e
C1 c
Q2 b e
C3 R4
R5
D2
R6
C8 c
Q4 b
D1 e
Q5 b
4.7k
10k c
D3 e
R13
R14
R9
R15
D5
Z02
C5
C6
D4
Z01
R10
T1
D101
R101
R102
CN2
HV
D102
C101
R12
C7
-4.2kV
CN3
GND
74
75
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
How to use electronic circuit diagram
TIMER TABLE
Name
Real Timer
Time Delay Safety Control
Forced Operation
Time Save Control
Anti-Freezing
Auto Mode Judgement
Soft Dry OFF
ON
Cooling
Deodorizing Control
Soft Dry
Comp. Reverse Rotation Detection
Comp./ Fan Motor Delay Timer
Powerful Mode Operation
Random Auto Restart Control
Time
1 hr.
10 min.
1 min.
2 min. 58 sec.
60 sec.
7 min.
4 min.
20 sec.
6 min.
10 min.
40 sec.
70 sec.
20 sec.
180 sec.
40 sec.
360 sec.
5 min.
2 min.
1.6 sec.
15 min.
0 ~ 62 sec.
Test Mode
(When test point
Short-circuited)
1 min.
10 sec.
1 sec.
0 sec.
0 sec.
4.2 sec.
0 sec.
0 sec.
36 sec.
60 sec.
4 sec.
7 sec.
2 sec.
18 sec.
4 sec.
36 sec.
30 sec.
0 sec.
0 sec.
15 sec.
0 ~ 6.2 sec.
Remarks
Soft Dry: 10 min. operation
Comp. ON 5 min. and above
76
19.2. Remote Control
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
77
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
19.3. Print Pattern
Indoor Unit Printed Circuit Board
BOTTOM VIEW
78
TOP VIEW
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
79
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DKE
19.4. Print Pattern
Indicator & Receiver Printed Circuit Board
BOTTOM VIEW
TOP VIEW
80 [PHAAM] Printed in Malaysia
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project