SELECTION AND INSTALLATION INSTRUCTIONS
Conversion to natural or propane gas and high altitude operation
models IPT
WARNING
This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. The qualified service agency performing this work assumes responsibility for the proper conversion of this appliance with this kit.
AVERTISSEMENT
Cet ensemble de conversion ne doit etre installé que par le représentant d’un orgasnisme qualifié et conformément aux instructions du fabricant et à tous les codes et exigences applicables de l’autorité compétente. Quiconque ne respecte pas
à la lettre les instructions dans le présent manuel risque de déclencher un incendie ou une explosion entrainent des dommages matériels, des lésions corporelles ou la perte de vies humaines. L’organisme qualifié qui effectue les travaux est responsable de la conversion correcte de ce générateur d’air chaud à l’aide de cet ensemble.
IMPORTANT
This kit must be used in conjunction with literature number 9-511, latest revision, unit installation and service manual.
The kits described in this manual provide the components and instructions required for field-converting any natural gas or propane gas unit to any model size, at any listed elevation.
For Units being Converted to Natural Gas or Propane
Gas at High Altitude Concurrently
Since each kit described in this manual contains a conversion regulator kit, a separate fuel conversion kit is not necessary.
For Units being Converted from Propane Gas to
Another Propane Gas Model Size and/or Altitude
Concurrently
Follow the propane conversion instructions in this manual, discarding the propane conversion regulator kit and primary air shutter, since the original unit is already equipped with these components.
For Units Being Converted to High Altitude Operation
Gas-fired equipment ratings in the United States are certified for elevations above 2000 feet to meet ANSI Z223.1, which requires ratings to be reduced 4% for each 1000 feet above sea level. Certification in Canada requires ratings to be reduced
10% for elevations above 2000 feet. All of the high altitude kits described in this manual comply with these requirements.
To accommodate high altitude operation (over 2000 feet elevation), please follow the instructions as explained in this manual.
All gas-fired products produced by Modine Manufacturing
Company are rated at 600 feet above sea level using gas values of either 1040 Btu/ft3 for natural gas or 2500 Btu/ft3 for propane gas. Since gas values vary from location to location, be sure to account for the local gas value when sizing and selecting these products.
THIS MANUAL IS THE PROPERTY OF THE OWNER. PLEASE BE SURE
TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
2
MANIFOLD PRESSURE ADJUSTMENT
Manifold Pressure Adjustment
The unit manifold pressure is factory set for operation at elevations up to 2,000 feet as follows:
• For Natural Gas units, 3.5" W.C. based on a gas heating value of 1,050 BTU/ft ³ .
• For Propane Gas units, 10.0" W.C. based on a gas heating value of 2,500 BTU/ft ³ .
For higher elevations, some utility companies may derate the
BTU content (heating value) of the gas provided at altitude to a lower value to allow vertain heating appliances to be used with no manifold pressure adjustments. For this reason it is necessary that the supplying utility be contacted for detailed information about the gas type and BTU content (heating value) before operating any heater. Table 2.1 show the standard derated heating values of natural and propane gases at various elevations.
Table 2.1 - Gas Heating Values at Altitude (Btu/ft ³)①②⑤
Altitude (ft)
0-2,000
2,001-3,000
3,001-4,000
4,001-4,500
4,501-5,000
5,001-6,000
6,001-7,000
7,001-8,000
8,001-9,000
9,001-10,000
Natural Gas
1,050
929 ③
892 ③
874 ③
856
822
789
757
727
698
Propane
2,500
2,212 ④
2,123 ④
2,080 ④
2,038
1,957
1,879
1,803
1,731
1,662
① Values shown are for 3.5" W.C. manifold pressure for Natural Gas and 10.0" W.C. for Propane Gas. If the local utility supplies gas with a different Btu/ft ³ value, use Equation 2.2 to calculate the required manifold pressure.
② Gas Heating values shown are derated 4% per 1,000' of elevation
(10% between 2,000' and 4,500' elevation in Canada) in accordance with ANSI Z223.1 and CSA-B149, respectively.
③ 945 Btu/ft ³ for Canada
④ 2,250 Btu/ft ³ for Canada
⑤ When installed at altitudes above 2,000', a pressure switch may need to be changed. Refer to Tables 3.1 and 4.1.
If the heating value of the gas being supplied is different than the values shown in Table 2.1, use the following equation to determine the appropriate manifold pressure for the altitude and gas heating value being supplied.
Equation 2.2 - Manifold Pressure for Gas Heating
Values Different Than Shown in Table 2.1
Where:
MP
ELEV
= Manifold Pressure ("W.C.) at installed elevation
BTU
TBL
= BTU/ft ³ content of gas from table 2.1
BTU
ACT
= BTU/ft company
³ content of gas obtained from the utility
MP
SL
= Manifold Pressure (in. W.C.), at Sea Level (use
3.5" W.C. for Natural Gas and 10.0" W.C. for Propane)
NOTE: Only the primary Manifold Pressure should be adjusted on units equipped with two-stage or modulating gas controls.
No adjustments to the Low Fire Manifold Pressure are necessary on these units.
Selection of the Proper High Altitude Kit
All units installed at elevations greater than 2,000 feet above sea level require a kit, in addition to potential manifold pressure adjustment outlined in the previous step. In some instances, the combustion air proving (pressure) switch may need to be changed. To determine the proper kit to use, refer to Table
3.1 and 4.1. An example is shown as a guide to the proper selection of the kit and whether a pressure switch change is required.
75-538
MODEL IDENTIFICATION / NATURAL GAS TO PROPANE GAS CONVERSION
Table 3.1 - Convert to Natural Gas
Model Size
Altitude Range (FT)
Kit Item Code
Kit Part Number
Gas Orifice Drill Size
Air Restrictor Plate Label
50
0-2000
77823
60
0-2000
77824
75
0-6500
77825
100
0-7500
77826
125
0-7500
77827
150
0-7500
77828
175
0-7500
77829
200
0-7500
77830
3H037840-1 3H037840-2 3H037840-3 3H037840-4 3H037840-5 3H037840-6 3H037840-7 3H037840-8
3.3 mm 27 22 11 3 B F L
"50" "60" "75" "100" "125" "150N" "175" "200"
Pressure Switch /Label Color
Primary Air Plate Diameter
Regulator Kit for WR 36J Valve
Conversion Label
5H081908-5
Orange
5H081908-1
Violet
5H081908-9
Tan
5H081908-9
Tan
5H081908-4
Yellow
5H081908-1
Violet
5H081908-1
Violet
5H081908-6
Aqua
None None 0.875
0.875
0.875
92-0656 92-0656 92-0656 92-0656 92-0656
5H086014 5H086014 5H086014 5H086014 5H086014
0.875
92-0656
None
92-0656
None
92-0656
5H086014 5H086014 5H086014
Model Size
Altitude Range (FT)
Kit Item Code
Kit Part Number
Gas Orifice Drill Size
Air Restrictor Plate Label
Pressure Switch /Label Color
Primary Air Plate Diameter
Regulator Kit for WR 36J Valve
Conversion Label
50 60 75
2001-5000 2001-3500 6501-7500
77831 77832 77837
3H037840-9 3H037840-10 3H037840-15
3.3 mm 27 22
"50" "60" "75"
5H081908-1
Violet
5H081908-6
Aqua
5H081908-4
Yellow
None
92-0656
None
92-0656
0.875
92-0656
5H086014 5H086014 5H086014
Model Size
Altitude Range (FT)
Kit Item Code
Kit Part Number
Gas Orifice Drill Size
Air Restrictor Plate Label
Pressure Switch /Label Color
Primary Air Plate Diameter
Regulator Kit for WR 36J Valve
Conversion Label
50 60
5001-7500 3501-6000
77836 77834
3H037840-14 3H037840-12
3.3 mm
"50"
27
"60"
5H081908-6
Aqua
5H081908-8
Sungold
None
92-0656
None
92-0656
5H086014 5H086014
Model Size
Altitude Range (FT)
Kit Item Code
Kit Part Number
Gas Orifice Drill Size
Air Restrictor Plate Label
Pressure Switch /Label Color
Primary Air Plate Diameter
Regulator Kit for WR 36J Valve
Conversion Label
60
6001-7500
77838
3H037840-16
27
"60"
5H081908-7
Grey
None
92-0656
5H086014
75-538 3
4
MODEL IDENTIFICATION / PROPANE GAS TO NATURAL GAS CONVERSION
Table 4.1 - Convert to Propane
Model Size
Altitude Range (FT)
Kit Item Code
Kit Part Number
Gas Orifice Drill Size
Air Restrictor Plate Label
50
0-2000
77839
60
0-5000
77840
75
0-5000
77841
100
0-5000
77842
125
0-7500
77843
150
0-7500
77844
175
0-7500
77845
200
0-6000
77846
3H037841-1 3H037841-2 3H037841-3 3H037841-4 3H037841-5 3H037841-6 3H037841-7 3H037841-8
2.0 mm 43 38 32 30 28 23 18
"50" "60" "75" "100" Yes "150P" "175" "200"
Pressure Switch /Label Color
Primary Air Plate Diameter
Primary Air Shutter
Regulator Kit for WR 36J Valve
Conversion Label
5H081908-5
Orange
5H081908-1
Violet
5H081908-3
White
5H081908-9
Tan
5H081908-4
Yellow
5H081908-1
Violet
5H081908-1
Violet
5H081908-5
Orange
None
Yes
None
Yes
0.875
Yes
0.875
Yes
0.875
Yes
0.875
Yes
None
Yes
None
Yes
92-0659 92-0659 92-0659 92-0659 92-0659 92-0659 92-0659 92-0659
5H086014 5H086014 5H086014 5H086014 5H086014 5H086014 5H086014 5H086014
Model Size
Altitude Range (FT)
Kit Item Code
Kit Part Number
Gas Orifice Drill Size
Air Restrictor Plate Label
Pressure Switch /Label Color
Primary Air Plate Diameter
Primary Air Shutter
Regulator Kit for WR 36J Valve
Conversion Label
50 60 75 100 200
2001-5000 5001-6000 5001-7500 5001-7500 6001-7500
77847 77851 77852 77853 77855
3H037841-9 3H037841-13 3H037841-14 3H037841-15 3H037841-17
2.0 mm 43 38 32 18
"50" "60" "75" "100" "200"
5H081908-1
Violet
5H081908-8
Sungold
5H081908-2
Pink
5H081908-4
Yellow
5H081908-6
Aqua
None
Yes
92-0659
None
Yes
92-0659
0.875
Yes
92-0659
0.875
Yes
92-0659
None
Yes
92-0659
5H086014 5H086014 5H086014 5H086014 5H086014
Model Size
Altitude Range (FT)
Kit Item Code
Kit Part Number
Gas Orifice Drill Size
Air Restrictor Plate Label
Pressure Switch /Label Color
Primary Air Plate Diameter
Primary Air Shutter
Regulator Kit for WR 36J Valve
Conversion Label
50 60
5001-7500 6001-7500
77850 77854
3H037841-12 3H037841-16
2.0 mm 43
"50" "60"
5H081908-6
Aqua
5H081908-7
Grey
None
Yes
None
Yes
92-0659 92-0659
5H086014 5H086014
75-538
G
H
SELECTION
Identifying the Model and Control Code
Figure 5.1 explains the unit model number found on the unit's serial plate. Markings pertinent to verifying correct application of the coversion kits are identified and explained in detail. All of the following prerequisites must be satisfied before the unit is deemed convertible.
D
E
F
A
B
C
1. The first character in the model number must be IPT.
1
Figure 5.1
5 6 7
DIGIT SEQUENCE 1, 2, 3 4, 5, 6 7 8, 9 10, 11
MODEL NUMBER
IPT 200 S 01 11
MODEL PREFIX:
IMPROVED PRESSURE TUBE: IPT
CONTROL CODE:
11: SINGLE STAGE, NATURAL GAS
MODEL SIZE:
MBH INPUT: 50, 60, 75, 100, 125, 150, 175, 200
IGNITION TYPE:
S: DIRECT SPARK
21: SINGLE STAGE, PROPANE GAS
POWER CODE:
01: 115V/60HZ/1PH
8
Selection of the Proper Kit
DIGIT SEQUENCE 1 17, 18, 19, 20, 21
SERIAL NUMBER
2, 3 3, 4 5, 6 7, 8 9, 10 11, 12 13, 14, 15, 16
IMPORTANT
This kit must be used in conjunction with literature number 9-511, latest revision, unit installation and service manual.
SPO NUMBER
SEQUENTIAL NUMBER
NUMBER VARIES FROM 0000 TO 9999.
UNIT SERIES:
00: ORIGINAL, 01: MODIFIED
CONTROL SUPPLIER:
01: ROBERTSHAW, 09: WHITE ROGERS,
05: HONEYWELL, 17: UNITED TECH, 08: FENWAL
EACH UNIT WITHIN SAME WEEK OF
MANUFACTURE IS TO HAVE UNIQUE NUMBER
YEAR OF MANUFACTURE
WEEK OF MANUFACTURE
SAME AS REQUIREMENTS
PLANNING SHOP CALENDER
Referring to the model number on the unit serial plate, select the appropriate kit from Tables 3.1 - 4.1.
Example:
To convert a IPT 75AS0111 to propane gas operation at 6000 feet, select Item Code #77852. (The new IPT 75AS0121 requires tube system lengths of either 20 or 30 feet.)
1 3 4 5 6 7
To convert a IPT 75AS0111 to 150 MBH on propane gas at
5000 feet, select Item Code # 77844. (The new IPT 150AS0121 requires tube system lengths of either 50 or 60 feet.)
8
Note:
For BTU conversions - 50 and 60 can only be converted to 50 or 60K BTU. 75-200 can only be converted between 75-200
BTU sizes.
9 10 11 12
A
B
C
D
E
F
.
REVISION
.
DESCRIPTION
MODINE MANUFACTURING COMPANY
1500 DE KOVEN AVENUE
RACINE, WISCONSIN 53403-2552
.
BY
.
DATE
.
.
CO NUMBER FIELD
THIS PRINT AND ITS CONTENTS ARE THE PROPERTY OF MODINE AND MUST NOT BE USED
FOR ANY PURPOSE NOT AUTHORIZED BY MODINE. DO NOT DISCLOSE, REPRODUCE OR
OTHERWISE USE THIS PRINT OR ITS CONTENTS IN ANY MANNER DETRIMENTAL TO THE
INTEREST OF MODINE WITHOUT MODINE'S PRIOR WRITTEN CONSENT. MODINE RESERVES
ALL RIGHTS OF DESIGN AND INVENTION TO THE EXTENT PERMITTED BY LAW.
CORE CODE NUMBER MATERIAL SURFACE
TEXTURE
GENERAL TOLERANCE
UNLESS NOTED
AUTHOR
CHECKED
APPROVED
STANDARD
DATE
19Jun15
28Feb14 CPG aingle
28Feb14 CPG BRS
1ST ANGLE
3RD ANGLE
SIMILAR TO: N/A
DEP
CPG aingle
NAME
CAD SYSTEM
SOLID EDGE
SCALE
UNITS
IN
DRAWING NUMBER
8H0075610000
DESCRIPTION
FORMAT
A2
REPLACES: N/A CAD MODEL NUMBER:
UNLESS OTHERWISE SPECIFIED: ALL DIMENSIONS ARE IN INCHES.
8H0075610000.dft
2 PLC = u.03
3 PLC = u.005
ANGLES = u1v
SERIAL PLATE MARKING SHEET
IPT, LOW INTENSITY INFRARED
PAGE OF 1
G
H
75-538 5
6
INSTALLATION
Installation of Kit
Conversion of any unit is the responsibility of, and the risk of the person making the conversion.
CAUTION
Gas supply shall be shut off prior to disconnecting the electrical power, before proceeding with the conversion.
Failure to do so could result in fire, explosion or electrical shock.
Figure 6.2 - Propane Gas Air Shutter and Orifice
Air Shutter
General
1. Ensure gas supply and electrical power disconnections have been made.
2. Remove burner box side access panel (two screws).
3. Remove burner enclosure panel.
4. Remove the single screw and discard the primary air plate shown in Figure 6.1. Models 50-60 and 175-200 NG and LP units do not have a primary air plate.
Figure 6.1 - Natural Gas Primary Air Plate
Primary Air
Plate
Orifice
8. Insert propane gas orifice into manifold. Refer to Tables 3.1
- 4.1 for correct gas orifice drill size. Tighten propane gas orifice using a wrench and ensure that it is gas-tight.
9. Tighten the burner support bracket and replace the burner enclosure panel.
10. Remove the air intake restrictor plate from teh combustion blower inlet by removing four screws. Refer to Figure 6.3 for location of restrictor plate.
Figure 6.3 - Air Restrictor Plate
Air
Restrictor
Plate
Single Screw
Burner Support
Bracket
Burner
Enclosure
5. Loosen the screws for the burner support bracket (see
Figure 6.1) to make clearance for the natural gas orifice removal.
6. Remove original gas orifice from the manifold and discard.
7. Slip the propane gas air shutter over the propane gas orifice and tighten. The air shutter flat side should be flush with the end of the propane gas orifice, as shown in Figure
6.2. Propane air shutters are only used on 75-200 models.
Combustion
Blower
11. Install propane intake air restrictor plate. The air restrictor plate number is stamped onto the restrictor plate. Refer to
Table 3.1 - 4.1 to verify the correct restrictor plate.
75-538
INSTALLATION
12. Remove the unit's pressure switch by removing the pressure hose, the two wire leads, and two mounting screws. See Figure 7.1.
Figure 7.1 - Pressure Switch
Hose
A
1
Figure 7.3
2
Conversion Rating Plate
B
3
Primary Air
Plate
C
D
13. Install the new pressure switch. Ensure that the hose and two wire leads are properly connected to the pressure switch. Refer to Tables 3.1 - 4.1 to verify the correct pressure switch part number and label color.
E
If the original unit is a natural gas model, proceed to #14 below.
If the original unit is a propane gas model, proceed to #16 below.
14. Modify the combination gas control to use propane gas by following the instructions in the regulator kit. Some conversion kits will have more than one regulator kit, specific to the manufacturer of hte combination gas control
F
(i.e. Honeywell, Robertshaw, etc.). Check the conversion kit parts list, Tables 3.1 - 4.1, for application of the correct regulator kit. A second check can be made by finding the model number on the combination gas control and matching it with the correct kit. Do not attempt to substitute one regulator kit for another.
15. Affix the appropriate propane conversion label (see
Figure 7.2) to the gas valve. This label is supplied with the regulator conversion kit.
Figure 7.2
Typical Combination Gas Control Conversion
ATTENTION
THIS VALVE HAS BEEN
CONVERTED FOR USE
WITH
LP GAS
ATTENTION
Cette soupage a
été convertie pour l’ usage de gaz L.P.
16. Affix the propane conversion rating plate (see Figure 7.3) adjacent to the unit's original rating plate.
75-538
1 2 3
4
4
5 6 7 8
1. Made from 8H0704200002 label stock and 8H0704300000. Marking system described below. Label stock is 3.94" width X 8.50" height.
2. Label design and marking printed directly by Modine using Printronix
T5308 printer and system consisting of the following two elements:
a) Unprinted polyester film coated on on side with pressure sensitive adhesive protected by a release liner (8H070420002) b) Resin ribbon, black.
3. Label design based on artworks from this print. Layouts to be stored as
Loftware files to be used by batch printing applications.
4. Pressure sensitive marking system: BLM 229.
5. All artwork to be imported to Loftware directly from electronic file.
Preferred format is *.pcx, 300dpi, monocrome.
6. Label shown is scanned from original label. Two labels can be printed on
3.94" W X 8.50" h label stock. Loftware design file must be updated when this file is updated.
7. Variable fields are shown in blocks.
8. Print file saved in \\raciwi-u1\loftware$\labels directory.
Image file saved in \\raciwi-u\loftware$\images directory.
A
B
C
D
.
REVISION
.
DESCRIPTION
.
BY
.
DATE
.
.
CO NUMBER FIELD
MODINE MANUFACTURING COMPANY
RACINE, WISCONSIN 53403-2552
AUTHOR
CHECKED
APPROVED
STANDARD
DATE DEP NAME
27Aug15
27Aug15
27Aug15
BHVAC DLC
BHVAC DLC
BHVAC ANI
1ST ANGLE
CAD SYSTEM
SOLID EDGE
SCALE
UNITS
IN
FORMAT
THIS PRINT AND ITS CONTENTS ARE THE PROPERTY OF MODINE AND MUST NOT BE USED
FOR ANY PURPOSE NOT AUTHORIZED BY MODINE. DO NOT DISCLOSE, REPRODUCE OR
OTHERWISE USE THIS PRINT OR ITS CONTENTS IN ANY MANNER DETRIMENTAL TO THE
INTEREST OF MODINE WITHOUT MODINE'S PRIOR WRITTEN CONSENT. MODINE RESERVES
ALL RIGHTS OF DESIGN AND INVENTION TO THE EXTENT PERMITTED BY LAW.
CORE CODE NUMBER MATERIAL SURFACE
TEXTURE
GENERAL TOLERANCE
UNLESS NOTED
SEE NOTE
DRAWING NUMBER
2 PLC = u.03
3 PLC = u.005
5H0860140000
DESCRIPTION
3RD ANGLE
SIMILAR TO: N/A
A3
REPLACES: N/A CAD MODEL NUMBER:
UNLESS OTHERWISE SPECIFIED: ALL DIMENSIONS ARE IN INCHES.
5H0860140000.dft
ANGLES = u1v
CONVERSION KIT RATING PLATE
PAGE
8
1 OF 1
E
F
7
8
INSTALLATION / CHECK-OUT PROCEDURE
17. Verify that all controls and wiring have not been damaged, then replace the burner box side access panel.
WARNING
Radiant tube baffle must be properly selected from Table 8.1 according to fuel type, burner input and tube system length. It must also be properly assembled and installed.
Figure 8.2 - Baffle Insertion
Reflector
Last Tube
18. The last section of radiant tube includes a turbulating baffle, which must be assembled from the three identical sections provided with the tubes. Select the appropriate number of sections from Table 8.1 - noting that some models have different numbers of sections for natural and propane gas and fasten them together end-to-end as shown in Figure
8.1. Insert the assembled baffle into the last tube section, flush with the end of the tube closest to the vent as shown in Figure 8.2, and discard any unused baffle sections.
19. Continue with the following Check-Out Procedure.
50
60
75
100
125
150
175
200
Input
MBH
LP
NG
LP
NG
LP
NG
LP
Nat
Prop
NG
LP
NG
LP
NG
LP
NG
Table 8.1 - Baffle Section Quantity Determination
-
-
-
4
-
1
3
20
2
3
4
-
-
-
-
-
-
-
-
-
-
-
-
4
-
-
2
4
1
1
1
2
Tube System Length (ft.)
30
2
40
-
50
-
60
-
-
0
0
2
-
-
-
-
-
-
-
3
3
4
-
3
-
2
3
-
2
-
2
1
-
-
-
-
-
-
-
-
3
3
3
3
4
4
2
2
2
2
2
2
-
-
-
-
-
-
-
70
-
-
-
-
-
2
0
0
0
Figure 8.1 - Baffle Section Fastening Detail
Tabs
Baffle
Check-Out Procedure
This is an abbreviated check-out procedure. For additional detail, please see applicable installation and service manual for the appropriate unit.
1. Place pressure taps on both the inlet and outlet pressure taps of the gas valve.
2. Connect a pressure-measuring device capable of reading inches of water column on both the inlet and outlet pressure taps.
3. Restore both the fuel supply and the electrical supply to the unit. Verify the proper ignition sequence. The inlet pressure must be 12"-14" water column. The manifold pressure must be 10" water column.
4. No adjustments can be made to the burner flame. Some yellow in the flame is acceptable as long as no carbon
(black soot) is being formed.
5. Verify the input rate by checking the correct main burner orifice sie and manifold pressure. This information is presented on the conversion kit rating plate.
6. Turn the unit off and replace the inlet and outlet pressure tap plugs.
7. Turn the unit on.
8. Check for leaks at all joints, pressure tap plugs, and connections in the gas lines. This is most easily done with a soap and water solution. Simply brush or spray some of the solution on a joint or connection, and look for bubble formation.
9. If additional information is required, please refer to applicable installation and service manual for the specific infrared model.
Slots
75-538
Modine Manufacturing Company • 1500 DeKoven Avenue • Racine, Wisconsin 53403-2552
Tel: 1.800.828.4328 (HEAT) • www.modine.com
© Modine Manufacturing Company 2015
75-538
5/03 - Litho in USA
9
advertisement