Sunny Scout BASIC fs Installation & Service Manual
Sunny Scout BASIC fs is a powerful microprocessor appliance for the accurate control of solar systems. It is suitable for most types of south facing solar thermal systems and can be used in residential, business, or industrial premises. The device comes with the following capabilities:
- Intuitive menu-conducted operation with graphic symbols and four operating keys
- Temperature differential regulation - digitally adjustable values
- Operating hour meter for storage tank charging
- Pump speed modulation & manual switch control of solar circulation pump
- Continual system monitoring with error and failure display through symbols
Advertisement
Advertisement
Installation & Service manual
Sunny Scout BASIC fs
Micro-processor controller for solar thermal systems
Explanation of graphic symbols used in the manual
Attention!
Symbol advise possible dangers and errors
Attention 230V~ voltage!
Symbol displays the danger of high voltages.
Information tabs
Please read carefully!
Operational information / characteristic features
Other Information or procedure
Testing / checking
Table of content
1 Application / characteristics and features
1.1 Description and application
1.2 Controller characteristics
2 Safety instructions
3 Controller installation
3.1 Opening the controller
3.2 Wall installation
3.3 Electrical connection - overview
3.4 Sensors connection
4 Operation / Display
4.1 Display graphics
4.2 Button function
5 Operating menus
5.1 "Info" Menu
5.2 "Programming" Menu
5.3 "Manual operation" Menu
5.4 "Basic adjustment" Menu
6 System diagram
Controller functions
7.1 General controller functions
7.1.2 Pump speed modulation
7.2 Protection functions
7.2.1 Collector protection
7.2.2 Re-cooling (Holiday function)
7.2.3 System protection
7.2.4 Anti-freeze protection
8 System monitoring
8.1 Sensor monitoring
8.2 Flow monitoring
9 Failure repair
9.1 Failures with an error messages
9.2 Failures without error messages
10 Technical data
11 Resistance table PT1000
12 Terms of guarantee
13 Declaration of conformity
6
7
7
8
9
10
10
11
11
11
10
10
10
10
5
6
6
5
5
4
4
5
3
3
3
3
4
12
13
14
11
11
12
14
15
15
2
1 Application / characteristics and features
1.1 Description and application
The Sunny Scout BASIC fs controllers are powerful microprocessor appliances for the accurate control of solar systems. They are suitable for most types of south facing solar thermal systems
These solar controllers are for use in either residential, business or industrial premises and should be mounted in dry spaces.
The installer should ensure that the controller meets all necessary regulations and is suitable for the application prior to installation.
1.2 Controller characteristics
◼
◼
◼
◼
◼
The SOLAREG II generation of controllers is equipped with the following features:
◼ Intuitive menu-conducted operation with graphic symbols and four operating keys
Temperature differential regulation - digitally adjustable values
Operating hour meter for storage tank charging
Pump speed modulation & manual switch control of solar circulation pump
Continual system monitoring with error and failure display through symbols
All adjusted values are stored even in the case of any longer mains voltagebreakdown.
◼ Various protective functions, such as system protection, collector protection, recooling and flow monitoring
◼ Large wiring space
Available accessories:
◼
◼
◼
Temperature sensor PT1000
Sensor connection box
Immersion sleeves
2 Safety instructions
◼ Disconnect all appliances from the mains operating voltage completely before any installation or wiring work is commenced. Ensure that mains voltage is not connected into the ‘low voltage terminals’ (see page 10). Destruction and extremely dangerous voltages will occur in the controller, connected sensors and other system components if this is NOT complied with.
◼ Solar systems can absorb extremely high temperatures. There is a danger and risk of burning! Be careful during the installation of all temperature sensors!
◼ Mount the solar controller in a position to ensure that inadmissible operating temperatures (>50°C) are not experienced e.g. through other sources of heat.For safety the system can remain in a ‘manual only’ state for testing purposes. In this operating mode maximum temperatures or sensor functions are not monitored.
If any damage is seen in/on the controller, wiring cable or connected pumps and valves the system must not be started.
All installation and wiring work must only be carried out on the controller when the device is disconnected from the power supply.
The Sunny Scout BASIC fs must only be connected and commissioned by qualified personnel. In doing so, the applicable safety regulations must be observed.
3
4
The controller MUST be installed only in dry, non explosive locations. Installation should NOT be made onto combustible materials.
3 Controller installation
3.1 Opening the controller
Prior to opening the device, make sure to disconnect the power supply and ensure that it cannot be switched back on again.
The top cover is held in place by two catches on the base which can be unlocked by pulling apart the sides of the top cover (see the picture).
Hinge open the top cover upwards until it is latched into position.
You can now freely install and wire the controller.
Prior to powering up the controller ensure that the top cover is securely latched back into place
3.2 Wall installation
The device is mounted on the marked points. A drilling template is provided with the device. Insert the "Quick Info" card provided with the device into the pocket provided on the back of the device. The "Quick Info" card provides the user with an overview of the functions to facilitate rapid device operation.
3.3 Electrical connection - overview
For 230V~ connections please note the following points:
◼ I The mains supply voltage to the controller should be provided by a switched
FCU with a 3 amp rated fuse.
◼ Controllers are intended use with 230V~ /50Hz mains. All pumps and valves should be similarly rated.
◼
◼
◼
All earthed wires must be connected to terminals marked with PE.
Neutral terminals (N) are electrically connected and are not switched!
The switching output (A1) is 230V~ closer. If potential-free contacts are needed, appropriate accessories are available.
3.4 Sensors connection
The SOLAREG II BASIC controllers work with precise platinum-temperature sensors type PT1000. 2 sensors are required, the third sensor is optional.
Installation / cabling of the temperature sensors:
◼ Mount the sensors into the collector and storage tank. Ensure proper heat transfer and use heat-conducting paste if necessary.
◼ Cross-sections for cable extensions:
- up to 15m 2 x 0.5mm
2 ,
- up to 50m 2 x 0.75mm
2 .
If shielded - the shield must be connected to the earth (PE)
◼ Connect the temperature sensors according the systems design and functionality required. Polarity may be ignored as they will operate when fitted into either pole of the terminal.
◼ Temperature sensor cables MUST be run separately from 230V~wires.
◼ It is recommended that the external collector sensor can be additionally protected by a ‘Collector Sensor Protection Box’ which will protect the system from over-voltage caused by a lightning strike.
4 Operation / Display
4.1 Display graphics
During actual operation, the symbols appear in differing parts of the menu dependant upon the functionality that is being set or programmed.
Display symbols
All symbols which may appear on the graphic display:
◂ Active menu dTmin max start stop F
%
◂ Measured values, e.g.: 59.6C°.
◂ Measuring points assignment ok?
◂ Status indication
5
6
4.2 Button function
The Sunny Scout BASIC fs controller is operated by means of the 4 buttons. Use of these allows:
◼
◼ recall of all display values carry out controller function adjustments
Graphic symbols seen on the display lead you simply through the operating menu structure and show clearly the current menu points, display values or parameters.
The operating buttons have the following functions:
Button Function
“Scroll up"
„+“
"Scroll left"
"Exit"
"Break-off"
"Enter"
"Scroll down"
"-"
"Scroll right"
"Choice"
"Confirmation"
Description
◼ Menu rolls upwards
Value change: increase of the indicated value by 1, if held down the values rise constantly
◼
◼
◼
◼
Main menu scroll left
Exit menu
Exit menu point
Break-off value change without storing
◼ Call up of main menu, menu rolls downwards
◼ Value change: decrease of the indicated value by 1, if held down the values fall constantly
◼
◼
◼
Main menu scroll right
Choosing one menu point
Confirmation of value change to save amendment
The symbols appear in differing parts of the menu dependant upon the functionality that is being set or programmed
5 Operating menus
5.1 "Info" Menu
In this mode all measuring values and operating states are shown:
52 °C min
40°C max
67 °C
60 °C
Indication e.g.
75 °C min
12 °C max
105 °C
1234 h
Meaning
Indication of current collector temperature
Indication of minimum collector temperature can be “reset” to current temperature
Indication of maximum collector temperature can be “reset” to current temperature
Indication of current temperature within the storage tank
Indication of minimum storage tank temperature. Can be “reset” to current temperature
Indication of maximum storage tank temperature. Can be “reset” to current temperature
Indication of current temperature - S3
Operating hours for charging storage tank
Can be “reset” to 0 h
Reset possible
No
Yes
Yes
No
Yes
Yes
No
Yes
5.2 "Programming" Menu
All changeable parameters can be checked in this menu and, if necessary, altered.
Factory programmed default values are set which, as a rule, guarantee problem free function of the system.
Indication e.g.
max
65 °C dT max
7K dT min
3K min
100 12
Meaning
Value range
Typical adjustment
Storage tank:
Permissible maximum temperature
Storage tank: switchon difference
Storage tank: switchoff difference
Adjustment of minimum pump speed modulation
100% = rotational speed regulation off
15 –95°C
3 –40K
2 –35K
65°C
7K
3K
30% – 100% 100%
Current adjustment
5.3 "Manual operation" Menu
Automatic operation is switched off during manual operation. The outputs can be manually switched on and off for servicing and testing purposes.
Once the menu has been exited or after 8 hours, automatic operation is reactivated.
Display Meaning Value range
Manual switching “on / off” output A1 (solar circulation pump)
0 = Off
1 = On
Adjustments and changes within this menu MUST be carried out only by a specialist installer or competent staff.
Incorrect settings will effect the function of the controller and solar system..
7
8
Adjustments and changes within this menu MUST be carried out only by a specialist installer or competent staff.
Incorrect settings will effect the function of the controller and solar system..
5.4 "Basic adjustment" Menu
The hydraulic diagrams and additional functions are displayed in the Basic Setup menu. Adjustments MUST be carried out only by a specialist installer or competent staff. Settings may only be adjusted in the menu: a) within one minute after switching on the controller or b) after simultaneously pressing the buttons:
Current adjustment
Display
Line Value
0
1
2
3
Meaning
0
120 °C
0
40°C
Collector protection function: switching on or off
Collector protection function: activation temp.
Re-cooling function
(only if the collector protection is on)
Temperature to which the storage tank is re-cooled after activating the collector protection function
4 0 Anti-freeze function
5 3
Anti-freeze function
Start temperature
0 = Off
1 = On
0 = Off
110 –150°C 120°C
0 = Off
1 = On
30 –90°C
0 = Off
1 = On
0 = Off
40°C
0
-20°C ... +7°C 3°C
6 System diagram
1 collector array, 1 storage tank
S1
A1
S3
S2
PE
L
N
A1
N
Fuse
230V connections
L Live from mains supply
N Neutral from mains and outputs
A1 Live switch output 1 (solar circuit pump)
Sensor connections
S1
S2
Temp.-sensor collector
Temp.-sensor storage tank
S3 General temperature point
S3
S2
S1
9
10
Controller functions
7.1 General controller functions
The storage tank is charged through the pump on output A1 up to its adjusted maximum temperature as long as the collector temperature is higher by a pre-set temperature than the storage tank temperature. Monitoring and protection functions ensure safe operation.
7.1.2 Pump speed modulation
The output A1 can be operated either in switch mode or can be set to operate with a modulated pump speed.
„Programming“ menu
Indication min
100
Meaning Value range Typical adjustment
Adjustment of minimum pump speed modulation
100% = rotational speed regulation off
30% – 100% 100%
Adjustments and changes within this menu MUST be carried out only by a specialist installer or competent staff.
Incorrect settings will effect the function of the controller and solar system..
7.2 Protection functions
The controller is equipped with the following protective functions.
7.2.1 Collector protection
If the storage tank is charged to the maximum temperature and the collector temperature exceeds the adjusted collector protection temperature, the solar circuit pump is turned on. The solar circuit pump is switched off once the collector temperature is 10K below the adjusted value.
In this case, the storage tank is charged up to 95°C regardless of it’s adjusted maximum temperature.
7.2.2 Re-cooling (Holiday function)
The collector protection function is only effective if the storage tank temperature is below the temperature limit (95°). Therefore, during the holiday period, for example, the storage tank is discharged at night to the adjusted recooling temperature.
"Basic adjustment" menu
Indication Meaning
Line Value
0
1
2
3
0
120°C
0
40°C
Collector protection function: switching on or off
Collector protection function: activation temp.
Re-cooling function
(only if the collector protection is on)
Temperature to which the storage tank is re-cooled after activating the collector protection function
Value range Factory set-up
0 = Off
1 = On
0 = Off
110 –150°C 120°C
0 = Off
1 = On
0 = Off
30 –90°C 40°C
7.2.3 System protection
If the collector temperature exceeds the collector protection temperature (see
7.2.2) by 10K, the solar circuit pump is turned off to protect the system components. As soon as the temperature falls below this value the system is started again.
This function comes into effect no matter if the collector protection is activated or not.
7.2.4 Anti-freeze protection
This function must be activated if the water or glycol mixture can freeze.
If the temperature at the anti-freeze sensor (S1) drops below the set value, the solar circuit pump is activated and heats the solar circuit using the heat exchanger in the storage tank.
"Basic Setup" menu
Display Meaning
Line Value
4
5
0
3
Switches on or off the anti-freeze function
Temperature at which the anti-freeze function is activated
Value range Factory setting
0 = Off
1 = On
0
-20°C – +7°C 3°C
Settings and changes in this menu must only be carried out by a specialised technician. Incorrect settings can damage or adversely affect the function of the solar power system.
8 System monitoring
In the case of an error the flashing symbol is shown.
8.1 Sensor monitoring
The sensors necessary for the control functions and their connecting cables are monitored to show breaks or short circuits. If a faulty sensor or installation is recorded by the software, the symbol is shown . By scrolling up and down you can quickly find the error source.
8.2 Flow monitoring
The controller checks the flow rate when the pump is switched on. If after 15 minutes no flow is recorded an error message will be shown. The error message is automatically reset after fault correcting.
This message, however, does not switch off the pump.
"Basic adjustment" Menu
Indication
+
Meaning
A fault with the fluid circulation within the solar system
11
12
9 Failure repair
There are two different categories of system failures to be found:
◼ failures which can be recognised and indicated by the controller itself by displaying an error
◼ failures which cannot be recognised by the controller
9.1 Failures with an error messages
Error representation on display
Possible reasons
◼
◼
Sensor cable broken
Sensor defect
Flashing
Flashing
◼
◼
Short circuit in sensor cable
Sensor defect
Measures
Check the cable
Check sensor resistance if necessary replace the sensor
Check the cable
Circulation error:
No flow detected
+
Flashing
◼
◼
◼
◼
◼
Error in pump connection
Pump defect
Air in the system
Sensor cable broken
Sensor defect
Check sensor resistance and replace sensor if necessary
Check the wiring
Replace pump
Bleed the system
Check the cable
Check sensor resistance and replace sensor if necessary
9.2 Failures without error messages
If the system doesn’t work but there is no error message on the display of the controller follow the schedule in the table below.
Possible reasons Measures Error presentation
No display function
◼ 230V mains not connected or broken
◼ Internal fuse blown
Switch on or connect the controller
Check the fuse of the power supply circuit
Check the fuse, replace it if necessary, use type 2A/T
Check the 230V~ components for shortcircuits
Contact the supplier
Exit menu "Hand".
Controller does not operate the system
"Pump" symbol rotates, but pump does not work
◼
◼
◼
Controller is defective
Controller is in manual operation
Switch-on condition is not present.
◼
◼
◼
Pump connection faulty
Pump is seized or blocked.
No voltage on the output.
Wait until switch-on condition is reached.
Check the cable to pump
Bleed the pump
Contact the supplier.
Temperature display shows large variances in a short time interval
◼
◼
◼
Sensor cables are installed too close to the 230V~ cable
Sensor cable extentions used without shielding
Controller is defective
Separate sensor cables from the power supply or shield sensor cables
Shield sensor cables
Contact the supplier
Having checked the issues listed but the system is still not working please contact the supplier or manufacturer for specialist advice.
Failures that affect the
230V~ power supply must only be must be remedied only by a competent and trained electrician.
13
14
The right is reserved to change these specifications for technical purposes
10 Technical data
Housing
Material
Dimensions L x W x D in mm,
Weight
System of protection
Electrical values
Operating voltage
Interference grade
Max. conductor cross-section
230V~connections
Temperature sensor
Measuring range
Testing voltage
Switching voltage
Capability per one switching output
Fuse protection
Miscellaneous
Operating temperature
Storing temperature
Humidity
100% recyclable ABS-housing for wall installation
175 x 134 x 56; approx 360 g
IP20 according to DIN 40050, EN 60529
AC 230~ Volt, 50Hz, -10 ...+15%
N according to VDE 0875
2.5 mm² fine-strand/single-wire
PT1000 , 1 kΩ at 0°C
-30°C ... +250°C
4 kV 1 min according to EN 60730, IEC 60664
230V~
1A / approx. 230VA for cos φ = 0,7-1,0
Fine-wire fuse 5 x 20mm, 2A/T
(2 amperes, slow)
0 ... 50°C
-10 ... +65°C max. 60 %
11 Resistance table PT1000
Correct function of temperature sensors can be checked by using the following temperature resistance table in conjunction with suitable resistance measuring equipment:
Temperature in °C
-30
-20
-10
0
10
20
30
40
50
Resistance in Ohm
882
921
960
1000
1039
1077
1116
1155
1194
Temperature in °C
60
70
80
90
100
120
140
200
Resistance in Ohm
1232
1271
1309
1347
1385
1461
1535
1758
12 Terms of guarantee
The Sunny Scout BASIC fs controllers are carefully manufactured and tested as part of their production. Should any failures occur, check first for any operational, adjustment or system errors, as part of this investigation the solar pump and temperature sensor connections must also be checked.
PROZEDA GmbH provides a guarantee according to the following terms for 24 months commencing from the date of purchase.
a) The guarantee is only effective in the event of an existing material defect of the purchased goods. If the defect is due to an operating error, exceeding the permissible technical values, incorrect wiring, unauthorised technical changes made within the controller by the customer or other company other than the controller manufacturer then the guarantee will be void..
b) To claim under the guarantee notification in writing is required which describes the defect in detail, a copy of the customer´s invoice showing date of purchase must also be supplied. The manufacturers agents reserve the absolute right under the guarantee to either repair, replace or deliver a functioning spare part to correct the defect.
The maximum repair period is 1 month with effect from receipt of the controller by the manufacturers agents.
If two repair attempts fail then the customer has the right to the claim delivery of a functioning spare part. In the case of delivery of a spare part a new guarantee meeting these terms comes into effect.
c) Any further warranty (exchange, price reduction) is excluded. The guarantee is not transferable.
In the case of defects within the guarantee period....in the first instance contact the controller supplier or system installer. In the case of any return you must enclose a written description of the error or defect, together with details of the controllers programmed functionality and wiring details to allow a full and accurate assessment to take place.
13 Declaration of conformity
We, Prozeda GmbH, hereby declare in sole responsibility that the product Sunny
Scout BASIC fs Type 1316 complies with the following directives:
• Electromagnetic compatibility (2004/108/EC )
• Electrical equipment designed for use within certain voltage limits (2006/95/EC)
• CE marking (93/68/EEC).
Standards that were used:
• DIN EN 60730-1
• DIN EN 61326-1
• DIN EN 61326-2-2.
15
16
Operating manual for Sunny Scout BASIC fs 1316BED100-10B-E, 02/2012