Omega Engineering PX2670 User's Guide
Omega PX2670 is a pressure transducer/transmitter that converts differential and gage pressure into a proportional high-level analog output. It offers both voltage (0 to 10 VDC) and current (4 to 20 mA) output models. The device operates in temperatures ranging from 0 to 150°F (-18 to 65°C) and can be mounted using two #8 screws. It features two 3/16” OD pressure fittings with a 1/4” push-on tubing for pressure signal connection. The PX2670 is factory calibrated and has accessible zero and span adjustments for fine-tuning.
Advertisement
Advertisement
User’s Guide
http://www.omega.com
email: [email protected]
MODEL PX2670
Low Pressure Tranducers and Transmitters
OMEGAnet
On-Line Service http://www.omega.com
Internet e-mail [email protected]
USA:
ISO 9001 Certified
Tel: (203) 359-1660 e-mail: [email protected]
Canada:
Laval (Quebec) H7L 5A1
Tel: (514) 856-6928 e-mail: [email protected]
Servicing North America:
One Omega Drive, Box 4047
Stamford, CT 06907-0047
FAX: (203) 359-7700
976 Bergar
FAX: (514) 856-6886
USA and Canada
Customer Service:
Engineering Service:
TELEX:996404
Mexico and Latin America:
Benelux:
Tel: (31) 20 6418405
Czech Republic
Tel: 420 (69) 6311899
France:
Tel: (33) 130-621-400
Germany/Austria:
Tel: 49 (07056) 3017
United Kingdom:
ISO 9002 Certified
For immediate techincal or application assistance:
Sales Service: 1-800-826-6342/1-800-TC-OMEGASM
1-800-622-2378/1-800-622-BESTSM
1-800-872-9436/1-800-USA-WHENSM
EASYLINK: 62968934
Tel: (95) 800-826-6342
CABLE: OMEGA
FAX: (95) 203-359-7807
En Espan ~ ol: (95) 203-359-7803 email: [email protected]
Servicing Europe:
Postbus 8034, 1180 LA Amstelveen, The Netherlands
FAX: (31) 20 6434643
Toll Free in Benelux: 0800 0993344 e-mail: [email protected]
ul. Rude armady 1868, 733 01 Karvina-Hranice
FAX: 420 (69) 611114
Toll Free: 0800-1-66342 e-mail: [email protected]
9, rue Denis Papin, 78190 Trappes
FAX: (33) 130-699-120
Toll Free in France: 0800-4-06342 e-mail: [email protected]
Daimlerstrasse 26, D-75392 Deckenpfronn, Germany
FAX: 49 (07056) 8540
Toll Free in Germany: 0130 11 21 66 e-mail: [email protected]
One Omega Drive, River Bend Technology Centre
Northbank, Irlam, Manchester
M44 5EX, England
Tel: 44 (161) 777-6611 FAX: 44 (161) 777-6622
Toll Free in the United Kingdom: 0800-488-488 e-mail: [email protected]
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply.
OMEGA is constantly pursuing certification of its products to the European New Approach Directives.
OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct, but OMEGA Engineering, Inc. accepts no liability for any errors it contains, and reserves the right to alter specifications without notice.
WARNING: These products are not designed for use in, and should not be used for, patient-connected applications.
SS2045 03/24/99 Rev.A
General Information
The PX2670 Series pressure transducers and transmitters sense differential pressure and gage (static) pressure and convert this pressure difference to a proportional high level analog output for both unidirectional and bidirectional pressure ranges. Two versions are offered: the voltage model transducer with 0 to 10 VDC output and the current model transmitter with 4 to 20 mA output.
Environmental Conditions
The PX2670 Series is designed to be operated and stored in the following environmental conditions:
Temperature - The PX2670 is designed to operate and be stored with the following temperature limitations:
Operating: 0 to 150
°
F (-18 to 65
°
C)
Storage: -65 to 180
°
F (-54 to 82
°
C)
Position Effect:
Range
0 to .1” WC
0 to 1” WC
0 to 5” WC
0 to 30” WC
Zero Offset
2.1% FS
.22% FS
.14% FS
.06% FS
Electrical Connections
Wiring is through a standard PG13.5 cable strain relief. Wiring terminations are identified on the circuit board below the terminal strip (see Figure 1). To access the terminal strip, remove the cover by unscrewing the 2 captive screws on top of the case.
Voltage Models
The voltage model is a 3-wire circuit. The standard voltage model can operate from either 24 VAC or 24 VDC excitation with a 0 to 10 VDC output. The input tolerances are as follows:
24 VAC can operate from 9 to 30 VAC
24 VDC can operate from 12 to 40 VDC
Electrical
Connections
Voltage
Zero & Span
Adjustment
+EXC GND +SIG
Span
Zero
Figure 1
Electrical
Connections
Current
Zero & Span
Adjustment
+EXC -
Span
Zero
The Model 267 voltage output is a 3-wire circuit, with three terminals available for wiring
(see Figure 1). The -Excitation and -Output are commoned on the circuit (see Figure 2A).
The 267 voltage output can operate from either AC (9-30 VAC) or DC (12-40 VDC) excitation. The 267 has a 0-10 VDC output, calibrated at the Factory.
Figure 2
Power
Supply
+
PX 2670
Transmitter
(4 to 20 mA)
+
_
+
Load
(Monitor)
_ _
Figure 2A
+
+
PX 2670
Transducer
(Voltage)
Power
Supply
_ _
_
+
Load
(Monitor)
Current Models
The current output transmitters are true 2-wire (See Figure 2), 4-20 mA current devices and deliver rated current into any external load of 0-800 ohms. The 4-20 mA current units are designed to have current flow in one direction only - please observe polarity.
The PX2670 can operate over a voltage range of 9 to 30 VDC. It has been factory calibrated at 24 VDC into a 250 ohm load. The minimum and maximum power supply must be capable of delivering these voltages to the PX2670. Thus, the minimum and maximum power supply calculation is shown and depicted in Figure 4.
MIN Supply Voltage: 9 + 0.02 x (resistance of receiver plus line)
MAX Supply Voltage: 30 + .004 x (resistance of receiver plus line)
Mounting and Pressure Fittings
Mounting
The PX2670 Series are designed to be mounted with the two holes located on the base of the housing. The holes are sized to accept a #8 screw.
Fittings
Two (2) 3/16” O.D. pressure fittings are supplied for pressure signal connection with a
1/4” push on tubing. Both positive (high) and negative (low) pressure ports are located on the bottom face side of the unit. For best results (shortest response time), 3/16” I.D.
tubing is suggested for tube lengths up to 100 feet long, 1/4” I.D. for tube lengths up to
300 feet long, and 3/8” I.D. for tubing lengths up to 900 feet. The high and low ports are labeled next to each respective port (see Figure 3).
Calibration
Figure 3
All PX2670 Series pressure transducers and transmitters are factory calibrated and should require no field adjustment. However, both zero and span adjustments are accessible under the cover of the unit (see Figure 1), below and to the right of the terminal strip. Whenever possible, any zero and span adjustments should be corrected by software in the user’s control system. Us the zero and span adjustments only if necessary. The PX2670 Series are calibrated in the vertical position at the factory
(baseplate vertical). For use in other orientations, position the unit and follow the zero adjustment procedure listed below. Pressure ranges are fixed and cannot be changed in the field. If a range change is required, contact the factory for a replacement PX2670 model with the appropriate pressure range.
Zero Adjustment - Voltage
While monitoring the voltage between the positive output (+OUT) and common (-OUT), and with both ports open to atmosphere, the zero may be adjusted. For unidirectional pressure ranges, turn the zero adjustment screw until a reading of 0.050 VDC is achieved. For bidirectional pressure ranges set to 5 VDC.
Zero Adjustment - Current
While monitoring the current output with both ports open to atmosphere, the zero may be adjusted. For unidirectional pressure ranges, turn the zero adjustment screw until a reading of 4 mA is achieved. For bidirectional pressure ranges, set the zero to 12 mA.
Span Adjustment - Voltage
Span or full scale output adjustments should only be performed by using an accurate pressure standard (electronic manometer, digital pressure gage, etc.) with at least comparable accuracy as the PX2670 Series. With full scale pressure applied to the high pressure port, adjust span for full scale electrical output of 10.05 VDC.
Example 1: Unidirectional pressure range of 0 to 1” WC and 0.05
to 10.05 VDC output. Apply 1” WC to the high pressure port and adjust span as close as practical to
10.05 VDC.
Span Adjustment - Current
Span or full scale output adjustments should only be performed by using an accurate pressure standard (electronic manometer, digital pressure gage, etc.) with at least comparable accuracy as the PX2670 Series. With full scale pressure applied to the high pressure port, adjust span for full sale electrical output of 20mA.
Example 1: Unidirectional pressure range of 0 to 1” WC
Apply 1” WC to the high pressure port and adjust span as close as practical to 20 mA.
Example 2: Bidirectional pressure range of
±
5” WC
Apply 5” WC to the high pressure port and adjust span as close as practical to 20 mA.
Apply -5” WC to the high pressure port and adjust span as close as practical to 4 mA.
Loop Power Supply vs.
Loop Resistance for 4 to 20mA Transmitters
Figure 4
Operating
Range
9
Loop Supply Voltage (Vdc)
30
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of
13 months from date of purchase. OMEGA Warranty adds an additional one (1) month grace period to the normal one
(1) year product warranty to cover handling and shipping time. This ensures that OMEGA’s customers receive maximum coverage on each product.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by
OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is
VOID if the unit shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s’s control. Components which wear are not warranted, including but not limited to contact points, fuses , and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by it will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR
REPRESENTATIONS OF ANY KIND WHATSO EVER, EXPRESS OR IMPLIED, EXCEPT THAT OF TITLE,
AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS
FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED.
LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of
OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall
OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/
DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
RETURN REQUESTS/INQUIRES
Direct all warranty and repair requests/inquires to the OMEGA Customer Service Department. BEFORE RETURN-
ING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUM-
BER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS).
The assigned AR number should then be marked on the outside of the return package and on any correspondence. The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.
FOR WARRANTY RETURNS, please have the following information available
BEFORE contacting OMEGA:
1.
Purchase Order number under which the product was PURCHASED,
2.
Model and serial number of the product under warranty, and
3.
Repair instructions and/or specific problems relative to the product.
FOR NON-WARRANTY REPAIRS, consult
OMEGA for current repair charges. Have the following information available BEFORE contacting OMEGA:
1.
Purchase Order number to cover the COST of the repair,
2.
Model and serial number of the product, and
3.
Repair instructions and/or specific problems relative to the product.
OMEGA’s policy is to make running changes, not model changes. This affords our customers the latest in technology and engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
Copyright 1999 OMEGA ENGINEERING INC. All rights reserved. This document may not be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior written consent of OMEGA ENGINEERING, INC.
Where Do I Find Everything I Need for
Process Measurement and Control?
OMEGA...Of Course!
TEMPERATURE
● Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies
● Wire: Thermocouple, RTD & Thermistor
● Calibrators & Ice Point References
● Recorders, Controllers & Process Monitors
● Infrared Pyrometers
PRESSURE, STRAIN AND FORCE
● Transducers & Strain Gauges
● Load Cells & Pressure Gauges
● Displacement Transducers
● Instrumentation & Accessories
FLOW/LEVEL
● Rotameters, Gas Mass Flowmeters & Flow Computers
● Air Velocity Indicators
● Turbine/Paddlewheel Systems
● Totalizers & Batch Controllers pH/CONDUCTIVITY
● pH Electrodes, Testers & Accessories
● Benchtop/Laboratory Meters
● Controllers, Calibrators, Simulators & Pumps
● Industrial pH & Conductivity Equipment
DATA ACQUISITION
● Data Acquisition & Engineering Software
● Communications-Based Acquisition Systems
● Plug-in Cards for Apple, IBM & Compatibles
● Datalogging Systems
● Recorders, Printers & Plotters
HEATERS
● Heating Cable
● Cartridge & Strip Heaters
● Immersion & Band Heaters
● Flexible Heaters