Below you will find brief information for Current Probe Set PQ34-12. The PQ34-12 is a set of three 1200A current probes designed to be used with the Extech PQ3450 or PQ3470 Power Analyzers. These probes are shipped fully tested and calibrated and, with proper use, will provide years of reliable service.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Current Probe Set PQ34-12 User's Guide | Manualzz

User's Guide

1200A Current Probe Set

Model PQ34-12

2

3

Introduction

Congratulations on your purchase of this Extech Current Probe Set. A set of three 1200A current probes designed to be used with the Extech PQ3450 or PQ3470 Power Analyzers. These probes are shipped fully tested and calibrated and, with proper use, will provide years of reliable service.

Safety

This symbol, adjacent to another symbol or terminal, indicates the user must refer to the manual for further information.

This symbol, adjacent to a terminal, indicates that, under normal use, hazardous voltages may be present

Double insulation

Cautions

 Read and understand this user manual before operating the meter.

 Improper use of this meter can cause damage, shock, injury or death.

 Inspect the condition of the leads and the meter itself for any damage before operating the meter.

 Use great care when making measurements if the voltages are greater than 25VAC rms or

35VDC. These voltages are considered a shock hazard.

 Do not attempt to measure Current that exceeds specified limits

 Do not operate this instrument in wet or dusty environments.

 Do not operate this instrument in the presence of combustible or explosive gas

 Do not touch exposed metal parts or unused terminals.

 Use protective gloves near high current or voltage circuits.

 If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

2 PQ-12-EU-EN V1.0 01/12

Probe Description

1. Current Sensing Jaws

2. Jaw Trigger

3. 1200A-200A-20A range switch

4. Signal output plug ( +, red )

5. Signal output plug ( -, black )

6. DCV power plug

Operation

1. Connect the “A1” signal output cables to the matching input sockets on the top of the analyzer.

2. Connect the “A1” power cable to the matching power socket on the top of the analyzer.

3. Set the "1200A-200A-20A” range switch to the range appropriate for the application.

Note: Make sure the range set on the clamp matches the range set in the analyzer.

4. Connect the “A2” and “A3” clamps as above, if needed.

5. Press the "Trigger" to open the jaws and clamp around a single conductor.

6. Power on the power analyzer

1

2

3

6

3 PQ-12-EU-EN V1.0 01/12

Specifications

Measurement ranges

Output sensitivity

Output coupling

Accuracy (50/60Hz)

Frequency range

Phase error (50/60Hz)

Minimum load

Enclosure material

Safety

Power Supply

Max. Jaw Open Size

Operating Temperature

Operating Humidity

Dimension

Cable length :

DC plug size :

Weight

Safety

20A, 200A and 1200A, switch selectable

10mV/A on the 20A range

1mV/A on the 200A range

0.1mV/A on the 1200A range

AC coupled.

± 1% F.S. @ 23 ± 5°C

45 to 400 Hz.

< ± 1°

100 K ohm for specified accuracy

UL 94-V0 rated

IEC 1010, Category III 600V

8V± 1V (supplied from meter)

50 mm (2.0 inch) Dia.

0°C to 50°C (32°F to 122°F)

Less than 80% RH

210 x 64 x 33 mm. (8.3 X 2.5 X 1.3”inch )

4 meters (13.17 feet)

5.5 mm x 2.5 mm DIA.

490 g (1.08 LB)

For indoor use and in accordance with the requirements for indoor use, double insulation to IEC1010-1 (2001):

EN61010-1 (2001) Overvoltage Category III 600V,, Pollution

Degree 2. www.extech.com

4 PQ-12-EU-EN V1.0 01/12

advertisement

Key Features

  • Measurement ranges 20A, 200A, and 1200A, switch selectable
  • Output sensitivity 10mV/A on the 20A range, 1mV/A on the 200A range, 0.1mV/A on the 1200A range.
  • Output coupling AC coupled.
  • Accuracy ± 1% F.S. @ 23 ± 5°C
  • Frequency range 45 to 400 Hz.
  • Safety IEC 1010, Category III 600V

Frequently Answers and Questions

What are the measurement ranges of the probes?
The probes have three selectable ranges: 20A, 200A, and 1200A.
How do I connect the probes to the power analyzer?
Connect the signal output cables to the matching input sockets on the top of the analyzer. Connect the power cable to the matching power socket on the top of the analyzer.
What is the accuracy of the probes?
The accuracy of the probes is ± 1% F.S. at 23 ± 5°C.
What is the frequency range of the probes?
The frequency range of the probes is 45 to 400 Hz.