- Industrial & lab equipment
- Electrical equipment & supplies
- Power conditioning
- Power adapters & inverters
- Schneider Electric
- VSD 57
- User's manual
- 66 Pages
Schneider Electric VSD 57 Adjustable Speed Drive Controller User’s Manual
The VSD 57 is a microprocessor-based, keypad-programmable, variable speed AC motor drive designed for both constant and variable torque applications. It is suited for motors from 1 to 200 HP, operating on 200 to 575 VAC. The manual provides guidance on receiving, installation, configuration, and startup of the VSD 57 series.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
Adjustable Speed
Drive Controllers for
VSD 57 Series
User’s Manual
Constant and Variable Torque:
1 to 200 HP — 200 to 575 VAC
Receiving, Installation, Configuration and Startup
HAZARDOUS VOLTAGE
•
Read and understand this bulletin in its entirety before installing or operating
VSD57 drive controllers. Installation, adjustment, repair and maintenance of these drive controllers must be performed by qualified personnel
•
Disconnect all power before servicing drive controller. WAIT THREE
MINUTED until DC bus capacitors discharge. The DC bus LED is not an accurate indication of the absence of DC bus voltage.
•
DO NOT short across DC capacitors or touch unshielded components or terminal strip screw connections with voltage present. Install all covers and close the door before applying power or starting and stopping the drive controller.
•
User is responsible for conforming to all applicable code requirements with respect to grounding all equipment. For drive controller grounding points, refer to terminal connection drawings.
•
Many parts in this drive controller, including printed wire boards, operate at line voltage. DO NOT TOUCH. Use only electrically insulated tools.
Before servicing this controller:
•
Disconnect all power.
•
Place a "DO NOT TURN ON" label on drive controller disconnect.
•
Lock diconnect in open position.
Failure to observe these precautions will cause shock or burn, resulting in severe personal injury or death
COPYRIGHT NOTICE
© 1996 Schneider Canada Inc. All rights reserved. This document may not be copied in whole or in part, or transferred to any other media, without the written permission of Schneider Canada Inc.
PLEASE NOTE
Electrical equipment should be serviced only by qualified electrical maintenance personel, and this document should not be viewed as sufficient instruction for those who are not otherwise qualified to operate, service or maintain the equipment discussed. Although reasonable care has been taken to provide accurate and authoritative information in this document, no responsibility is assumed by Schneider Canada Inc. for any consequences arising out of the use of this material.
TABLE OF CONTENTS
1 General
Product Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Customer Modification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.
Theory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Description of AC Motor Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Drive Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.
Design Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.
Designation Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5.
Dimensional Data Variable Torque Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
6.
Dimensional Data Constant Torque Series . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7.
Drive Ratings - 208/240V Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
8.
Drive Ratings - 480V Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
9.
Drive Ratings - 575V Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
10. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
11. Input AC line requirements
Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
KVA ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Input Fusing and Disconnect requirements . . . . . . . . . . . . . . . . . . . . . . . . . 21
12 Voltage Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
13. Wiring
General wiring practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Input wiring precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Output wiring precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Power wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
14. Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
15. Control Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
16. Initial Power Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
17. Operating by Keypad Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
18. Monitor Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
19. Programming - Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
20. Programmable Parameter Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
21. Description of Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
22. Option: Dynamic braking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
23. Parameter Menu Index / User Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
1.
GENERAL
1.1
PRODUCT CHANGES
Schneider Canada Inc. reserves the right to discontinue or make modifications to the design of its products without prior notice, and holds no obligation to make modifications to products sold previously. Schneider
Canada Inc. also holds no liability for losses of any kind which may result from this action.
1.2
WARRANTY
Schneider Canada warrants the VSD 57 series AC motor control to be free of defects in material and workmanship for a period of twelve months from the date of shipment. Any control component, which under normal use, becomes defective, within the stated warranty time period, shall be returned to Schneider Canada
Inc., freight prepaid, for examination. Schneider Canada Inc. reserves the right to make the final determination as to the validity of a warranty claim, and sole obligation is to repair or replace only components which have been rendered defective due to faulty material or workmanship. No warranty claim will be accepted for components which have been damaged due to mis-handling, improper installation, unauthorized repair and/or alteration of the product, operation in excess of design specifications or other misuse, or improper maintenance. Schneider Canada Inc. makes no warranty that its products are compatible with any other equipment, or to any specific application, to which they may be applied and shall not be held liable for any other consequential damage or injury arising from the use of its products.
This warranty is in lieu of all other warranties, expressed or implied. No other person, firm or corporation is authorized to assume, for Schneider Canada Inc., any other liability in connection with the demonstration or sale of its products.
1.3
RECEIVING
Inspect all cartons for damage which may have occurred during shipping. Carefully unpack equipment and inspect thoroughly for damage or shortage. Report any damage to carrier and/or shortages to supplier. All major components and connections should be examined for damage and tightness, with special attention given to PC boards, plugs, knobs and switches.
1.4
CUSTOMER MODIFICATION
Schneider Canada Inc., its sales representatives and distributors, welcome the opportunity to assist our customers in applying our products. Many customizing options are available to aid in this function. Schneider
Canada Inc. cannot assume responsibility for any modifications not authorized by its engineering department.
1
2.
THEORY
DESCRIPTION OF AC MOTOR OPERATION
Three phase AC motors are comprised of two major components, the stator and the rotor. The stator is a set of three electrical windings held stationary in the motor housing. The rotor is a metal cylinder, fixed to the motor drive shaft, which rotates within the stator. The arrangement of the stator coils and the presence of three phase AC voltage give rise to a rotating magnetic field which drives the rotor. The speed at which the magnetic field rotates is known as the synchronous speed of the motor. Synchronous speed is a function of the frequency at which the voltage is alternating and the number of poles in the stator windings.
The following equation gives the relation between synchronous speed, frequency, and the number of poles:
Ss = 120 f/p
Where: Ss = Synchronous speed (rpm ), f = frequency (Hz), p = number of poles
In three phase induction motors the actual shaft speed differs from the synchronous speed as load is applied.
This difference is known as "slip". Slip is commonly expressed as a percentage of synchronous speed. Typical values are three percent at full load.
The strength of the magnetic field in the gap between the rotor and stator is proportional to the amplitude of the voltage at a given frequency. The output torque capability of the motor is, therefore, a function of the applied voltage amplitude at a given frequency. When operated below base (rated) speed, AC motors are commonly run in a mode known as "constant torque". Constant torque output is obtained by maintaining a constant ratio between voltage amplitude (volts) and frequency (hertz). For 60 hertz 230, 460, and 575 volt motors, common values for this volts to hertz ratio are 3.83, 7.66, and 9.58 respectively. Operating with these values of the volts to hertz ratio generally yields optimum torque capability. Operating at lower ratio values lowers torque and power capability, and is known as "Variable Torque" operation. Operating at higher ratio values will cause the motor to overheat.
2
If the motor’s applied frequency is increased while voltage remains constant, its torque capability will decrease as speed increases. This will cause horsepower capability of the motor to remain approximately constant.
Motors are commonly run in this mode when operated above base speed, where drive output voltage is limited by the input line voltage. This operating range is known as the "constant horsepower" range. The typical maximum range for constant horsepower is about 2.0 to 1 (60 to 120 Hz).
WARNING! Consult motor manufacturer before operating above base speed.
3
DRIVE FUNCTION DESCRIPTION
The drive is a 16 bit microprocessor based, keypad programmable, variable speed AC motor drive. There are four major sections; an input diode bridge and filter, a power board, a control board, and an output intelligent power module(s).
DRIVE OPERATION
Incoming AC line voltage is converted to a pulsating DC voltage by the input diode bridge. The DC voltage is supplied to the bus filter capacitors through a charge circuit which limits inrush current to the capacitors during power-up, and discharges the capacitors after power is removed . The pulsating DC voltage is filtered by the bus capacitors which reduces the ripple level. The filtered DC voltage enters the inverter section of the drive, composed of six output intelligent insulated gate bi-polar transistors (IGBT’s) which make up the three output legs of the drive. Each leg has one intelligent IGBT connected to the positive voltage and one connected to the negative voltage. Alternately switching on each leg, the intelligent IGBT produces an alternating voltage on each of the corresponding motor windings. By switching each output intelligent IGBT at a very high frequency (known as the carrier frequency) for varying time intervals, the inverter is able to produce a smooth, three phase, sinusoidal current wave which optimizes motor performance.
CIRCUIT DESCRIPTION
The control section consists of a control board with a 16 bit microprocessor, keypad and display. Drive programming is accomplished via the keypad or the serial communications port. During operation the drive can be controlled via the keypad, by control devices wired to the control terminal strip, or by the the serial communications port. The Power Board has the control and protection circuits which supply the six or seven output IGBT’s. The seventh output IGBT is used for the dynamic braking option, and is not available on all models. The Power Board also contains a charging and discharging circuit for the bus filter capacitors, a motor current feedback circuit, a voltage feedback circuit, and a fault signal circuit. The drive has several built in protection circuits. These include phase-to-phase and phase-to-ground short circuit protection, high and low line voltage protection, protection against excessive ambient temperature, and against continuous excessive output current. Activation of any of these circuits will cause the drive to shut down in a protection "trip".
INPUT SIGNALS
The drive allows for three speed reference signal types: a speed potentiometer (10,000 Ohm), 4-20 MA, or
0-10 VDC signals. For control by a speed pot., the wiper lead is connected to terminal 5A, and the high and low end leads are connected to terminals 6 and 2, respectively. For 4-20 MA control, wire the positive to terminal 5B and the negative to terminal 2. For 0-10 VDC control, wire the positive to terminal 5D and the negative to terminal 2.
The input impedance of terminal 5A, speed control potentiometer input is 100 K ohms, the 0-10 VDC input, terminal 5D, is 200 K ohms, and the 4-20 MA input, terminal 5B, is 100 ohms (0.4 to 2.0 VDC). Terminal 2 is circuit common (the minus connection).
The control voltage of the microprocessor control board is 24 VDC, (Isolated, referenced to circuit common
- terminal 2).
OUTPUT SIGNALS
There are four terminals with output frequency and load indicating signals; Terminal 10B can be set to indicate speed or load via 0-10 VDC or 2-10 VDC. Terminal 10D can be set to indicate speed or load via 0-20 MA or
4-20 MA. Terminal 10C has a a 12 VDC pulse train (at 6 times the output frequency) proportional to speed.
Terminal 10E can be set to indicate output frequency or load via either a 0-10 VDC or 2-10 VDC signal.
4
AUXILIARY RELAY CONTACTS / OPEN COLLECTOR OUTPUT
The control board has two sets of FORM C contacts at terminals 16 through 21. Contacts are rated 2 amps resistive at 28 VDC or 120 VAC. Each set of contacts can be programmed to indicate NO FUNCTION, RUN,
FAULT, FAULT LOCKOUT, AT SPEED, CURRENT LIMIT, FOLLOWER PRESENT, AUTO SPEED MODE,
START PENDING, OR ABOVE SET SPEED, OR MAINTENANCE TARGET.
The VSD57 Series general control wiring diagrams illustrate the relays in the de-energized state.
There is an open collector output at terminal 14 for status indication. This output can be programmed for any of the functions listed below for the auxiliary contacts. The circuit is a current sinking type, and is rated 24
VDC, 5 MA maximum.
The following choices are available with each relay or open collector output.
•
The NO FUNCTION is not a true indicator, but rather a means of disabling the relay.
•
A RUN relay energizes whenever a "START" is called for, and remains energized until a "STOP" is called for and the output frequency has decelerated to 0.5 HZ, until the drive has "tripped", or until the input voltage is removed. This is used to indicate that the drive is in the run mode, not necessarily that the motor is turning.
•
A FAULT relay energizes when input voltage is applied to the drive and remains energized until the input voltage is removed, or the drive has "tripped" into a fault condition - see the PARAMETER DE-
SCRIPTION section.
•
A FAULT LOCKOUT relay is used when the drive is programmed to automatically restart after a "trip" condition. The relay energizes when input voltage is applied to the drive and remains energized until the input voltage is removed, or the drive has "tripped" into a fault condition, and unsuccessfully attempted the number of restarts set by the RESTART LIMIT (Parameter #72).
•
An AT SPEED relay energizes when the drive reaches the commanded frequency. The frequency at which the relay energizes and de-energizes has a (+ / -) 3 HZ frequency band, from the commanded frequency.
•
CURRENT LIMIT relay energizes when the drive is operating in current limit. Once the current limit relay is energized, it remains energized for a minimum of 500 mS. If the drive is operating in and out of current limit at a period of less than 500 mS, the relay will remain energized. Otherwise at the end of the 500 mS interval, if the drive is no longer in current limit, the relay will de-energize.
•
A FOLLOWER PRESENT relay energizes when the 4-20 MA speed reference input wired to control board terminals 5B and 2 is greater than 2 MA, and de-energizes when the input signal falls below 2 MA.
•
The AUTO SPEED MODE relay energizes when in the AUTO MODE. This relay function will only be active if Parameter #67 is set to AUTO / MANUAL SPEED, or AUTO / MANUAL LOCAL. This function will energize and remain energized if Parameter #67 is programmed for AUTO SPEED. This function will not be active if Parameter #67 is programmed for MANUAL SPEED.
•
The START PENDING relay energizes when the FAULT RESTART (Parameter #72) is ENABLED, and a START PENDING condition exists. This relay will remain energized for the duration of the start pending message. The duration of the start pending message is controlled by the RESTART DELAY (Parameter #73). This relay will also energize when the DC BRAKE (Parameter #80) is set to either ON
START, or START & STOP, and a start braking sequence is active. The time period the relay will remain energized is determined by the START BRAKE (Parameter #84).
•
An ABOVE SET SPEED relay energizes when the output frequency of the drive exceeds the value corresponding to the RELAY SET SPEED (Parameter #123) value, and de-energizes when the output frequency returns to a value lower than the RELAY SET SPEED value.
•
The MAINTENANCE TARGET relay energizes after the time period value set by the MAINTENANCE
TARGET (Parameter #132) has elapsed. The relay will stay energized until a new ( Higher ) time period value has been set by Parameter #132.
If Parameter #132 is set to 0, the MAINTENANCE TARGET relay function is disabled.
5
3.
DESIGN SPECIFICATIONS
Storage Temperature
Ambient Operating
(All Voltages)
Ambient Humidity
Maximum Altitude
Input Line Voltages
Input Voltage Tolerance
Input Frequency Tolerance
Displacement Power Factor
Frequency Stability
Input Power Device
Output Power Device
Wave Form
Output Frequency
Carrier Frequency
Service Factor
Overload Current Capacity
Speed Reference Follower
Control Voltage
Ride Thru
Output Signals
0 - 10 VDC
12 VDC Pulse train
(40 - 50% duty cycle)
4 - 20 MA
0 - 10, 2 - 10 VDC
Line Reactor
-20° to 70° C
Temperature 0° - 40°C
Less than 95% (non-condensing)
3300 feet (1000 meters) above sea level
200 / 240 Vac, 400 / 480 Vac, and 480 / 590 Vac
+10%, -15%
48 to 62 Hz
Approximately 0.96
+/- 0.00006% / °C
Full Wave Bridge Rectifier
IGBT Power Module
Sine Coded Pulse Width Modulated
0-120 Hz Standard
Factory default to constant 1.5 kHz,
Adjustable to 12 kHz.
Typically greater than 96%
120% for one minute for Variable Torque
(based on drive nominal output current rating)
150% for one minute, 180% for twenty seconds for Constant Torque
(based on drive nominal output current rating)
0-10 VDC, or (10-0 VDC), 4-20 MA, or (20-4 MA)
(Isolated, referenced to circuit common - terminal 2)
24 VDC (Isolated, referenced to circuit common - terminal 2)
400 mS
Proportional to speed or load (terminal 10B)
Proportional to speed (terminal 10C)
Proportional to speed or load (terminal 10D)
Proportional to speed or load (terminal 10E)
1) At 200V & 460V standard 25 HP and above
2) At 575 Volt standard 5 HP and above
6
4.
VSD 57 SERIES MODEL DESIGNATION CODE
The model number of a VSD57 Series drive gives a full description of the basic drive unit (see example below). Options such as door interlocked disconnects, input line fuses, input line and load reactors, EMI /
RFI filter, manual and automatic transfer bypass, additional door mounted operator controls, remote stations, etc can also be provided.
EXAMPLE: VSD57VU72S66
(VSD 57 Series, 575V AC, 5 HP, TYPE 1 ENCLOSURE)
V S D 5 7 V U 7 2 S 6 6
SERIES:
SERIES VSD 57
TORQUE CAPABILITY (only for VSD 57 SERIES):
C = Constant Torque & Variable Torque
V = Variable Torque only
POWER RATING:
U18 = 1HP
U29 = 2HP
U41 = 3 HP
U72 = 5 HP
U90 = 7 1/2 HP
D12 = 10 HP
D16 = 15HP
D23 = 20 HP
D27 = 25 HP
D33 = 30 HP
D46 = 40 HP
D54 = 50 HP
D64 = 60HP
D79 = 75 HP
C10 = 100 HP
C13 = 125 HP
C15 = 150 HP
C19 = 200 HP
INPUT VOLTAGE:
M2 = 240 VAC 3 phase
N4 = 480 VAC 3 phase
S6 = 590 VAC 3 phase
ENCLOSURE TYPE:
6 = type 1 vented enclosure
8 = type 4/12 totally enclosed
9 = type 4X totally enclosed stainless steel and water-tight
7
5.
DIMENSIONAL DATA VSD57 VARIABLE TORQUE
VSD57 SERIES - VARIABLE TORQUE - CHASSIS AND TYPE 1 ENCLOSED
W D
H
P
Q
Q
Conduit holes:
If Q = 2.12", all 1-1/8" dia.
If Q = 2.50", outer = 1-3/8" dia.,
middle = 1-1/8" dia.
V
U
R
2R
T
Dia.
Mounting tab detail
N
HP Voltage
1 to 2 200/240
400/480
480/590
3 200/240
400/480
480/590
5
7.5
200/240
400/480
480/590
200/240
400/480
480/590
10
15
20
200/240
400/480
480/590
200/240
400/480
480/590
200/240
400/480
480/590
Model H
VSD57VU29M26
VSD57VU29N46
VSD57VU29S66
VSD57VU41M26
VSD57VU41N46
VSD57VU41S66
VSD57VU72M26
VSD57VU72N46
VSD57VU72S66
VSD57VU90M26
VSD57VU90N46
VSD57VU90S66
VSD57VD12M26
VSD57VD12N46
VSD57VD12S66
VSD57VD16M26
VSD57VD16N46
VSD57VD16S66
VSD57VD23M26
VSD57VD23N46
VSD57VD23S66
14.00
12.00
15.50
14.00
14.00
19.00
19.00
19.00
25.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
15.50
12.00
12.00
15.50
D
9.50
7.91
7.91
9.50
9.50
9.84
9.84
9.84
10.50
7.91
7.91
7.91
7.91
7.91
7.91
7.91
7.91
7.91
7.91
7.91
7.91
W
8.88
7.44
7.44
8.88
8.88
8.88
8.88
8.88
8.88
7.44
7.44
7.44
7.44
7.44
7.44
7.44
7.44
7.44
7.44
7.44
7.44
N
4.44
3.72
3.72
4.44
4.44
4.44
4.44
4.44
4.44
3.72
3.72
3.72
3.72
3.72
3.72
3.72
3.72
3.72
3.72
3.72
3.72
Q
2.50
2.12
2.12
2.50
2.50
2.50
2.50
2.50
2.50
2.12
2.12
2.12
2.12
2.12
2.12
2.12
2.12
2.12
2.12
2.12
2.12
P
5.75
4.75
4.75
5.75
5.75
6.13
6.13
6.13
6.50
4.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
T
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.36
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
R
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.50
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
U
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
V Wght
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
30
25
35
45
30
50
50
35
55
25
25
35
25
25
35
25
25
25
25
25
25
ALL DIMENSIONS SHOWN ARE IN INCHES - ALL WEIGHTS SHOWN ARE IN POUNDS
8
VSD57 SERIES -VARIABLE TORQUE- CHASSIS AND TYPE 1 ENCLOSED
W D
H
P
N
Q
Q
Conduit holes:
If Q = 2.50", outer = 1-3/8" dia.
middle = 1-1/8" dia.
If Q = 2.62", left = 1-1/8" dia.
middle & right = 1-3/8" dia.
If Q = 3.12", left = 1-1/8" dia.
middle & right = 1-3/4" dia.
If Q =4.50 ", left = 1-1/8" dia.
middle & right = 2-1/2" dia.
V
U
R
2R
T
Dia.
Mounting tab detail
HP Voltage
25
30
40
50
60
75
100
125
150
200
200/240
400/480
480/590
400/480
480/590
400/480
480/590
400/480
480/590
400/480
480/590
400/480
480/590
200/240
400/480
480/590
200/240
400/480
480/590
200/240
400/480
480/590
200/240
400/480
480/590
Model H
VSD57VD27M26
VSD57VD27N46
VSD57VD27S66
VSD57VD33M26
VSD57VD33N46
VSD57VD33S66
VSD57VD46M26
VSD57VD46N46
VSD57VD46S66
VSD57VD54M26
VSD57VD54N46
VSD57VD54S66
VSD57VD64M26
VSD57VD64N46
VSD57VD64S66
VSD57VD79N46
VSD57VD79S66
VSD57VC10N46
VSD57VC10S66
VSD57VC13N46
VSD57VC13S66
VSD57VC15N46
VSD57VC15S66
VSD57vC19N46
VSD57VC19S66
29.00
25.00
25.00
29.00
29.00
29.00
29.00
29.00
29.00
29.00
29.00
29.00
29.00
25.00
25.00
25.00
25.00
25.00
25.00
25.00
25.00
25.00
25.00
25.00
25.00
W D
11.85
10.50
10.50
11.85
11.85
11.85
11.85
11.85
11.85
11.85
11.85
11.85
11.85
10.50
10.50
10.50
10.50
10.50
10.50
10.50
10.50
10.50
10.50
10.50
10.50
16.64
13.00
13.00
16.64
16.64
16.64
16.64
24.42
24.42
24.42
24.42
37.00
37.00
13.00
13.00
13.00
13.00
13.00
13.00
8.88
8.88
8.88
8.88
8.88
8.88
N
7.14
5.56
5.56
7.14
7.14
7.14
7.14
11.12
11.12
11.12
11.12
11.12
11.12
5.56
5.56
5.56
5.56
5.56
5.56
4.44
4.44
4.44
4.44
4.44
4.44
P
6.88
6.50
6.50
6.88
6.88
6.88
6.88
6.50
6.50
6.50
6.50
6.50
6.50
6.50
6.50
6.50
6.50
6.50
6.50
6.50
6.50
6.50
6.50
6.50
6.50
Q R
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
3.12
2.62
2.62
3.12
3.12
4.50
4.50
4.50
4.50
4.50
4.50
4.50
4.50
2.62
2.62
2.62
2.62
2.62
2.62
2.50
2.50
2.50
2.50
2.50
2.50
T
0.44
0.36
0.36
0.44
0.44
0.44
0.44
0.44
0.44
0.44
0.44
0.44
0.44
0.36
0.36
0.36
0.36
0.36
0.36
0.36
0.36
0.36
0.36
0.36
0.36
U
0.49
0.37
0.37
0.49
0.49
0.49
0.49
0.49
0.49
0.49
0.49
0.49
0.49
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
ALL DIMENSIONS SHOWN ARE IN INCHES - ALL WEIGHTS SHOWN ARE IN POUNDS
V Wght
0.92
0.68
0.68
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
185
175
255
205
260
255
175
170
130
175
170
360
350
125
120
85
130
125
120
80
80
80
80
80
80
9
6.
DIMENSIONAL DATA VSD57 CONSTANT TORQUE (VARIABLE TORQUE)
57 SERIES - CONSTANT TORQUE- CHASSIS AND TYPE 1 ENCLOSED
W D
H
P
Q
Q
Conduit holes:
If Q = 2.12", all 1-1/8" dia.
If Q = 2.50", outer = 1-3/8" dia.,
middle = 1-1/8" dia.
V
U
R
2R
T
Dia.
Mounting tab detail
N
HP
1/4
TO 1
1.5
TO 2
3
5
7.5
10
15
20
Voltage
200/240
400/480
480/590
200/240
400/480
480/590
200/240
400/480
480/590
200/240
400/480
480/590
200/240
400/480
480/590
200/240
400/480
480/590
200/240
400/480
480/590
200/240
400/480
480/590
Model
VSD57CU18M26
VSD57CU18N46
VSD57CU18S66
VSD57CU29M26
VSD57CU29N46
VSD57CU29S66
VSD57CU41M26
VSD57CU41N46
VSD57CU41S66
VSD57CU72M26
VSD57CU72N46
VSD57CU72S66
VSD57CU90M26
VSD57CU90N46
VSD57CU90S66
VSD57CD12M26
VSD57CD12N46
VSD57CD12S66
VSD57CD16M26
VSD57CD16N46
VSD57CD16S66
VSD57CD23M26
VSD57CD23N46
VSD57CD23S66
H
12.00
12.00
15.50
14.00
12.00
15.50
14.00
14.00
19.00
14.00
14.00
19.00
19.00
19.00
25.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
D
9.50
9.50
9.84
9.50
9.50
9.84
7.91
7.91
7.91
9.50
7.91
7.91
9.84
9.84
10.50
5.91
5.91
5.91
7.91
7.91
7.91
7.91
7.91
7.91
W
8.88
8.88
8.88
8.88
8.88
8.88
7.44
7.44
7.44
8.88
7.44
7.44
8.88
8.88
8.88
7.44
7.44
7.44
7.44
7.44
7.44
7.44
7.44
7.44
N
4.44
4.44
4.44
4.44
4.44
4.44
3.72
3.72
3.72
4.44
3.72
3.72
4.44
4.44
4.44
3.72
3.72
3.72
3.72
3.72
3.72
3.72
3.72
3.72
Q
2.50
2.50
2.50
2.50
2.50
2.50
2.12
2.12
2.12
2.50
2.12
2.12
2.50
2.50
2.50
2.12
2.12
2.12
2.12
2.12
2.12
2.12
2.12
2.12
P
5.75
5.75
6.13
5.75
5.75
6.13
4.75
4.75
4.75
5.75
4.75
4.75
6.13
6.13
6.50
2.75
2.75
2.75
4.75
4.75
4.75
4.75
4.75
4.75
T
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.36
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
R
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.50
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
V
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
U
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
Wght
35
35
53
35
35
53
25
25
31
35
35
31
55
55
75
25
25
19
25
25
19
25
25
19
ALL DIMENSIONS SHOWN ARE IN INCHES - ALL WEIGHTS SHOWN ARE IN POUNDS
10
VSD57 SERIES - CONSTANT TORQUE - CHASSIS AND TYPE 1 ENCLOSED
W D
H
V
P
N
Q Q
Conduit holes:
If Q = 2.50", outer = 1-3/8" dia.
middle = 1-1/8" dia.
If Q = 2.62", left = 1-1/8" dia.
middle & right = 1-3/8" dia.
If Q = 3.12", left = 1-1/8" dia.
middle & right = 1-3/4" dia.
If Q =4.50 ", left = 1-1/8" dia.
middle & right = 2-1/2" dia.
HP Voltage
25
30
40
50
60
75
100
125
150
200/240
400/480
480/590
200/240
400/480
480/590
200/240
400/480
480/590
400/480
480/590
200/240
400/480
480/590
400/480
480/590
400/480
480/590
400/480
480/590
400/480
480/590
Model H
VSD57CD27M26
VSD57CD27N46
VSD57CD27S66
VSD57CD33M26
VSD57CD33N46
VSD57CD33S66
VSD57CD46M26
VSD57CD46N46
VSD57CD46S66
VSD57CD54N46
VSD57CD54S66
VSD57CD64M26
VSD57CD64N46
VSD57CD64S66
VSD57CD79N46
VSD57CD79S66
VSD57CC10N46
VSD57CC10S66
VSD57CC13N46
VSD57CC13S66
VSD57CC15N46
VSD57CC15S66
25.00
25.00
25.00
25.00
25.00
25.00
25.00
25.00
25.00
25.00
25.00
29.00
29.00
29.00
29.00
29.00
29.00
29.00
29.00
29.00
29.00
29.00
W D
8.88
8.88
8.88
10.50
10.50
10.50
13.00
8.88
8.88
10.50
10.50
10.50
13.00
13.00
13.00
10.50
10.50
10.50
13.00
13.00
10.50
10.50
16.64
16.64
16.64
16.64
16.64
11.85
11.85
11.85
11.85
11.85
24.42
24.42
11.85
11.85
24.42
24.42
37.00
37.00
11.85
11.85
11.85
11.85
N
4.44
4.44
4.44
5.56
4.44
4.44
5.56
5.56
5.56
5.56
5.56
7.14
7.14
7.14
7.14
7.14
11.12
11.12
11.12
11.12
11.12
11.12
P
6.50
6.50
6.50
6.50
6.50
6.50
6.50
6.50
6.50
6.50
6.50
6.88
6.88
6.88
6.88
6.88
6.50
6.50
6.50
6.50
6.50
6.50
U
R
2R
T
Dia.
Mounting tab detail
Q
2.50
2.50
2.50
2.50
2.50
2.50
2.62
2.62
2.62
2.62
2.62
3.12
3.12
3.12
3.12
3.12
4.50
4.50
4.50
4.50
4.50
4.50
R
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
T
0.36
0.36
0.36
0.36
0.36
0.36
0.36
0.36
0.36
0.36
0.36
0.44
0.44
0.44
0.44
0.44
0.44
0.44
0.44
0.44
0.44
0.44
U
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.37
0.49
0.49
0.49
0.49
0.49
0.49
0.49
0.49
0.49
0.49
0.49
V Wght
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.68
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
130
125
-
130
-
80
80
75
125
80
75
185
180
-
185
-
250
-
260
-
360
-
ALL DIMENSIONS SHOWN ARE IN INCHES - ALL WEIGHTS SHOWN ARE IN POUNDS
11
VSD57 SERIES - CONSTANT TORQUE- TYPE 4/12 AND 4X ENCLOSED
HP
1/4 TO 1
1.5 TO 2
3
5
7.5
10
15
20
25
30
Voltage
200/240
400/480
480/590
200/240
400/480
480/590
200/240
400/480
480/590
200/240
400/480
480/590
200/240
400/480
480/590
200/240
400/480
480/590
200/240
400/480
480/590
200/240
400/480
480/590
200/240
400/480
480/590
400/480
480/590
Model
VSD57CU18M28
VSD57CU18N48
VSD57CU18S68
VSD57CU29M28
VSD57CU29N48
VSD57CU29S68
VSD57CU41M28
VSD57CU41N48
VSD57CU41S68
VSD57CU72M28
VSD57CU72N48
VSD57CU72S68
VSD57CU90M28
VSD57CU90N48
VSD57CU90S68
VSD57CD12M28
VSD57CD12N48
VSD57CD12S68
VSD57CD16M28
VSD57CD16N48
VSD57CD16S68
VSD57CD23M28
VSD57CD23N48
VSD57CD23S68
VSD57CD27M28
VSD57CD27N48
VSD57CD27S68
VSD57CD33N48
VSD57CD33S68
P
5.63
5.63
5.63
5.63
5.63
5.63
4.81
4.81
4.81
5.63
4.81
4.81
3.50
3.50
3.50
4.56
3.50
3.50
4.56
4.56
4.56
5.88
5.88
5.88
7.08
5.88
5.88
7.08
7.08
D
8.83
8.83
8.83
8.83
8.83
8.83
7.50
7.50
7.50
8.83
7.50
7.50
6.19
6.19
6.19
7.25
6.19
6.19
7.25
7.25
7.25
9.78
9.78
9.78
10.98
9.78
9.78
10.98
10.98
W
9.70
9.70
9.70
11.38
9.70
9.70
11.38
11.38
11.38
11.38
11.38
11.38
7.88
7.88
7.88
7.88
7.88
7.88
7.88
7.88
7.88
11.74
11.74
11.74
11.74
11.74
11.74
11.74
11.74
H
16.00
16.00
16.00
19.00
16.00
16.50
19.00
19.00
19.00
19.00
19.00
19.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
29.00
29.00
29.00
29.00
29.00
29.00
29.00
29.00
ALL DIMENSIONS SHOWN ARE IN INCHES - ALL WEIGHTS SHOWN ARE IN POUNDS
Q
2.50
2.50
2.50
2.50
2.50
2.50
2.12
2.12
2.12
2.50
2.12
2.12
2.12
2.12
2.12
2.12
2.12
2.12
2.12
2.12
2.12
2.50
2.50
2.50
2.50
2.50
2.50
2.50
2.50
R
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
T
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.28
0.36
0.36
0.36
0.36
0.36
0.36
0.36
0.36
Wght
50
50
60
50
50
60
35
35
46
50
35
46
25
25
21
25
25
21
25
25
21
80
80
85
85
85
85
90
90
12
VSD57 SERIES - CONSTANT TORQUE - TYPE 12 ENCLOSED
HP Voltage Model H W D N P Q R T U V Y Wght
30
40
50
60
200/240 VSD57CD33M28 31.00
14.00
11.86
6.00
7.50
2.62
1.50
0.36
0.37
0.68
22.50 150
200/240 VSD57CD46M28 31.00
14.00
11.86
6.00
7.50
2.62
1.50
0.36
0.37
0.68
22.50 150
400/480 VSD57CD46N48 31.00
14.00
11.86
6.00
7.50
2.62
1.50
0.36
0.37
0.68
22.50 150
480/590 VSD57CD46S68 31.00
14.00
11.86
6.00
7.50
2.62
1.50
0.36
0.37
0.68
22.50 -
400/480 VSD57CD54N48 31.00
14.00
11.86
6.00
7.50
2.62
1.50
0.36
0.37
0.68
22.50 150
480/590 VSD57CD54S68 31.00
14.00
11.86
6.00
7.50
2.62
1.50
0.36
0.37
0.68
22.50 -
200/240 VSD57CD64M28 37.00
18.00
13.30
7.50
8.00
3.13
1.50
0.49
0.50
0.92
27.00 200
400/480 VSD57CD64N48 37.00
18.00
13.30
7.50
8.00
3.13
1.50
0.49
0.50
0.92
27.00 195
75
480/590 VSD57CD64S68 37.00
18.00
13.30
7.50
8.00
3.13
1.50
0.49
0.50
0.92
27.00 -
400/480 VSD57CD79N48 37.00
18.00
13.30
7.50
8.00
3.13
1.50
0.49
0.50
0.92
27.00 200
480/590 VSD57CD79S68 37.00
18.00
13.30
7.50
8.00
3.13
1.50
0.49
0.50
0.92
27.00 -
100 400/480 VSD57CC10N48 39.00
26.00
13.30
11.50
8.00
4.50
1.50
0.49
0.50
0.92
27.00 300
480/590 VSD57CC10S68 39.00
26.00
13.30
11.50
8.00
4.50
1.50
0.49
0.50
0.92
27.00 -
125 400/480 VSD57CC13N48 39.00
26.00
13.30
11.50
8.00
4.50
1.50
0.49
0.50
0.92
27.00 310
480/590 VSD57CC13N68 39.00
26.00
13.30
11.50
8.00
4.50
1.50
0.49
0.50
0.92
27.00 -
ALL DIMENSIONS SHOWN ARE IN INCHES - ALL WEIGHTS SHOWN ARE IN POUNDS
13
7. DRIVE RATINGS - 208 / 240 V Model
VSD57 Series ratings - Variable Torque application only
Model Number Motor Power
230 V
HP
200 V
HP
VSD57VU29M26
VSD57VU41M26
VSD57VU72M26
VSD57VU90M26
VSD57VD12M26
VSD57VD16M26
VSD57VD23M26
VSD57VD27M26
VSD57VD33M26
VSD57VD46M26
VSD57VD54M26
VSD57VD64M26
VSD57VD79M26
25
30
40
50
60
7.5
10
15
20
1.5
2
3
5
30
40
50
60
75
10
15
20
25
2
3
5
7.5
INPUT
3 Phase input only
Input Line Current
240/208V
A
8.1
11.3
17.7
25.2
31.8
47.6
61
64
76
98.6
122
145
182
Power
(240V/208V)
KVA
3.4/2.8
4.7/3.9
7.3/6.1
10.5/8.7
13.2/11.0
19.8/16.5
25.3/21.0
26.6/22.1
31.6/26.3
41/34.1
50.7/42.1
60.5/50.3
75.7/62.8
OUTPUT
Output Current
(230/200V)
A
80
104
130
154
192
28
42
54
68
6.8
9.6
15.2
22
Max Transient
Current (60s)
A
8.16
11.52
18.24
26.4
33.6
50.4
64.8
81.6
96
124.8
156
184.8
230.4
1) AC line reactor are included as standard equipment on 200/230 VAC models 25 HP through 75HP
2) Verify the nameplate current rating of the motor. It may be necessary to use a larger HP drive to meet the continous full load amp requirements.
3) See section 11, for recommended input fuse type.
14
VSD57 Series ratings - Constant Torque (& Variable Torque)
Model Number Motor Power
230 V
HP
200 V
HP
VSD57CU18M2-
VSD57CU29M2-
VSD57CU41M2-
VSD57CU72M2-
VSD57CU90M2-
VSD57CD12M2-
VSD57CD16M2-
VSD57CD23M2-
VSD57CD27M2-
VSD57CD33M2-
VSD57CD46M2-
VSD57CD64M2-
7.5
10
15
20
1
2
3
5
25
30
40
60
7.5
10
15
20
1
2
3
5
25
30
40
60
INPUT
3 Phase input only
Input Line Current
240/208V
A
4.6 / 5.5
8.1 / 9.7
11.3 / 13.6
17.7 / 21.3
25.2 / 30.3
31.8 / 38.2
47.6 / 57.2
61.0 / 73.2
64.0 / 76.8
76.0 / 91.2
98.6 / 118.4
145.0 / 174.0
Power
(240V/208V)
KVA
10.5
13.2
19.8
25.3
1.9
3.4
4.7
7.3
26.6
31.6
41
60.5
OUTPUT
Output Current
(230/200V)
A
4.0 / 4.8
6.8 / 8.1
9.6 / 11.5
15.2 / 18.0
22.0 / 26.0
28.0 / 33.0
42.0 / 49.0
54.0 / 64.0
68.0 / 78.0
80.0 / 92.0
104.0 / 120.0
154.0 / 185.0
Max Transient
Current (60s)
A
6.0/7.2
10.2 / 12.2
14.4 / 17.2
22.8 / 27.0
33.0 / 39.0
42.0 / 49.5
63.0 / 73.5
81.0 / 96.0
102.0 / 117.0
120.0 / 138.0
156.0 / 180.0
231.0 / 277.5
1) AC line reactor are included as standard equipment on 200/230 VAC models 25 HP through 60HP
2) Verify the nameplate current rating of the motor. It may be necessary to use a larger HP drive to meet the continous full load amp requirements.
3) See section 11, for recommended input fuse type.
4) - Last number of model code designates enclosure type. See section 4.
15
8. DRIVE RATINGS - 480 V Model
VSD57 Series ratings - Variable Torque application only
Model Number Motor Power
460 V
HP
380 V
KW
VSD57VU29N46
VSD57VU41N46
VSD57VU72N46
VSD57VU90N46
VSD57VD12N46
VSD57VD16N46
VSD57VD23N46
VSD57VD27N46
VSD57VD33N46
VSD57VD46N46
VSD57VD54N46
VSD57VD64N46
VSD57VD79N46
VSD57VC10N46
VSD57VC13N46
VSD57VC15N46
VSD57VC19N46
55
75
90
110
18.5
22
30
37
45
0.75
1.5
3
4
5.5
9
11
15
100
125
150
200
30
40
50
60
75
7.5
10
15
20
25
2
3
5
INPUT
3 Phase input only
Input Line Current
480/400 V
A
4
5.7
8.8
12.6
15.9
23.8
30.6
32.2
38.4
49.3
61
72.8
90.8
116
146
169
225
Power
(480V/400V)
KVA
3.4/2.8
4.7/3.9
7.3/6.1
10.5/8.7
13.2/11.0
19.8/16.5
25.3/21.0
26.6/22.1
31.6/26.3
41/34.1
50.7/42.1
60.5/50.3
75.5/62.7
96.4/80.0
121.4/100.8
140/116.2
187.1/155.3
124
156
180
240
40
52
65
77
96
11
14
21
27
34
3.4
4.8
7.6
OUTPUT
Output Current
(460V/380V)
A
Max Transient
Current (60s)
A
48
62.4
78
92.4
115.2
148.8
187.2
216
288
4.08
5.76
9.12
13.2
16.8
25.2
32.4
40.8
1) AC line reactor are included as standard equipment on 480 VAC models 25 HP and above.
2) Verify the nameplate current rating of the motor. It may be necessary to use a larger HP drive to meet the continous full load amp requirements.
3) See section 11, for recommended input fuse type.
4) For drive models VSD57VC13N46, VSD57VC15N46 and VSD57VC19N46 derate the input and ouput nominal current and power ratings by 0,90 for a 10 KHZ carrier frequency, and 0.80 for 12KHZ carrier frequency.
16
VSD57 Series ratings - Constant Torque (& Variable Torque)
Model Number Motor Power
460 V
HP
380 V
KW
VSD57CU18N4-
VSD57CU29N4-
VSD57CU41N4-
VSD57CU72N4-
VSD57CU90N4-
VSD57CD12N4-
VSD57CD16N4-
VSD57CD23N4-
VSD57CD27N4-
VSD57CD33N4-
VSD57CD46N4-
VSD57CD54N4-
VSD57CD64N4-
VSD57CD79N4-
VSD57CC10N4-
VSD57CC13N4-
VSD57CC15N4-
15
18.5
22
30
37
45
55
75
90
110
0.75
1.5
2.2
4
5.5
7.5
11
20
25
30
40
50
60
75
100
125
150
5
7.5
10
15
1
2
3
3 Phase input only
Input Line Current
480/400V
A
2.3 / 2.8
4.0 / 4.8
5.7 / 6.8
8.8 / 10.6
12.6 / 15.2
15.9 / 19.1
23.8 / 28.6
30.6 / 36.7
32.2 / 38.6
38.4 / 46.1
49.3 / 59.2
61.0 / 73.2
72.8 / 87.4
90.8 / 109.0
116.0 / 139.2
146.0 / 175.2
169.0 / 203.0
INPUT
Power
(480V/400V)
KVA
25.4
26.7
31.5
41
50.7
60.5
75.5
96.4
121.4
140
1.9
3.4
4.7
7.3
10.5
13.2
19.8
OUTPUT
Output Current
(460/380V)
A
2.0 / 2.4
3.4 / 4.1
4.8 / 5.7
7.6 / 9.0
11.0 / 13.0
14.0 / 17.0
21.0 / 25.0
27.0 / 32.0
34.0 / 40.0
40.0 / 48.0
52.0 / 62.0
65.0 / 78.0
77.0 / 92.0
96.0 / 115.0
124.0 / 148.0
156.0 / 187.0
180.0 / 216.0
Max Transient
Current (60s)
A
3.0 / 3.6
5.1 / 6.1
7.2 / 8.5
11.4 / 13.5
16.5 / 19.5
21.0 / 25.5
31.5 / 37.5
40.5 / 48.0
51.0 / 60.0
60.0 / 72.0
78.0 / 93.0
43.3 / 117.0
115.5 / 138.0
144.0 / 172.5
186.0 / 222.0
234.0 / 280.5
270.0 / 324.0
1) AC line reactor are included as standard equipment on 480 VAC models 25 HP and above.
2) Verify the nameplate current rating of the motor. It may be necessary to use a larger HP drive to meet the continous full load amp requirements.
3) See section 11, for recommended input fuse type.
4) - Last number of model code designates enclosure type. See section 4.
17
9. DRIVE RATINGS - 575 V Model
VSD57 Series ratings - Variable Torque application only
Model Number Motor Power
575 V
HP
525 V
KW
VSD57VU29S66
VSD57VU41S66
VSD57VU72S66
VSD57VU90S66
VSD57VD12S66
VSD57VD16S66
VSD57VD23S66
VSD57VD27S66
VSD57VD33S66
VSD57VD46S66
VSD57VD54S66
VSD57VD64S66
VSD57VD79S66
VSD57VC10S66
VSD57VC13S66
VSD57VC15S66
VSD57VC19S66
22
30
37
45
55
75
90
132
9
11
15
18.5
1.5
2.2
3
4
5.5
40
50
60
75
100
125
150
200
15
20
25
30
2
3
5
7.5
10
INPUT
3 Phase input only
Input Line Current
590/525V
A
3.3
4.6
5.8
8.6
10.6
16.4
20.8
26.3
30.9
39.7
50
59.6
74.1
94.5
119
137
183
Power
(590V/525V)
KVA
3.4/2.8
4.7/3.9
7.3/6.1
10.5/8.7
13.2/11.0
19.8/16.5
25.3/21.0
26.6/22.1
31.6/26.3
41/34.1
50.7/42.1
60.5/50.3
75.5/62.7
96.4/80.0
121.4/100.8
140/116.2
187/155
41
52
62
77
99
125
144
192
17
22
27
32
2.7
3.9
6.1
9
11
OUTPUT
Output Current
(575/525V)
A
Max Transient
Current (60s)
A
49.2
62.4
74.4
92.4
118.8
150
172.8
230.4
3.24
4.68
7.32
10.8
13.2
20.4
26.4
32.4
38.4
1) AC line reactor are included as standard equipment on 575 VAC models 5 HP and above.
2) Verify the nameplate current rating of the motor. It may be necessary to use a larger HP drive to meet the continous full load amp requirements.
3) See section 11, for recommended input fuse type.
4) For drive models VSD57VC13S66, VSD57VC15S66 and VSD57VC19S66 derate the input and ouput nominal current and power ratings by 0,90 for a 10 KHZ carrier frequency, and 0.80 for 12KHZ carrier frequency.
18
VSD57 Series ratings - Constant Torque (& Variable Torque)
Model Number Motor Power
575 V
HP
525 V
KW
VSD57CU18S6-
VSD57CU29S6-
VSD57CU41S6-
VSD57CU72S6-
VSD57CU90S6-
VSD57CD12S6-
VSD57CD16S6-
VSD57CD23S6-
VSD57CD27S6-
VSD57CD33S6-
VSD57CD46S6-
VSD57CD54S6-
VSD57CD64S6-
VSD57CD79S6-
VSD57CC10S6-
VSD57CC13S6-
VSD57CC15S6-
15
18.5
22
30
37
45
55
75
90
110
0.75
1.5
2.2
4
5.5
7.5
11
20
25
30
40
50
60
75
100
125
150
5
7.5
10
15
1
2
3
INPUT
3 Phase input only
Input Line Current
590/525V
A
1.8 / 1.7
3.3 / 3.2
4.6 / 4.6
5.8 / 6.6
8.6 / 8.6
10.6 / 11.0
16.4 / 18.0
20.8 / 22.8
26.3 / 28.9
30.9 / 33.9
39.7 / 43.7
50.0 / 54.0
59.6 / 64.0
74.1 / 78.0
94.5 / 100.0
119.0 / 125.0
137.0 / 150.0
Power
(590V/525V)
KVA
21.3
26.9
31.6
40.5
51.1
60.9
75.7
96.6
121.6
140
1.9
3.4
4.7
5.9
8.8
10.9
16.7
OUTPUT
Output Current
(590/525V)
A
1.6 / 1.5
2.7 / 2.6
3.9 / 3.8
6.1 / 6.5
9.0 / 9.0
11.0 / 12.0
17.0 / 18.4
22.0 / 23.0
27.0 / 28.5
32.0 / 33.0
41.0 / 45.0
52.0 / 55.0
62.0 / 65.0
77.0 / 80.0
99.0 / 105.0
125.0 / 129.0
144.0 / 156.0
Max Transient
Current (60s)
A
2.4 / 2.25
4.1 / 3.9
5.8 / 5.7
9.2 / 9.7
13.5 / 13.5
16.5 / 18.0
25.5 / 27.6
33.0 / 34.5
40.5 / 42.7
48.0 / 49.5
61.5 / 67.5
78.0 / 82.5
93.0 / 97.5
115.5 / 120.0
148.5 / 157.5
187.5 / 193.5
216.0 / 234.0
1) AC line reactor are included as standard equipment on 575 VAC models 5 HP and above.
2) Verify the nameplate current rating of the motor. It may be necessary to use a larger HP drive to meet the continous full load amp requirements.
3) See section 11, for recommended input fuse type.
4) Last number of model code designates enclosure type. See section 4.
19
10. INSTALLATION
DRIVES MUST NOT BE INSTALLED WHERE SUBJECTED TO ADVERSE
ENVIRONMENTAL CONDITIONS! DRIVES MUST NOT BE INSTALLED WHERE
SUBJECTED TO: COMBUSTIBLE, OILY, OR HAZARDOUS VAPORS OR DUST;
EXCESSIVE MOISTURE OR DIRT; STRONG VIBRATION; EXCESSIVE AMBIENT
TEMPERATURES. CONSULT SCHNEIDER CANADA FOR MORE INFORMATION
ON THE SUITABILITY OF A DRIVE TO A PARTICULAR ENVIRONMENT.
The drive should be mounted on a smooth vertical surface capable of safely supporting the unit without vibrating. The LCD display has an optimum field of view, this should be considered when determining the mounting position.
Chassis models must be installed in an electrical enclosure which will provide complete mechanical protection and maintain uniform internal temperature within the drive’s ambient operating temperature rating. All drive models MUST be mounted in a vertical position for proper heatsink cooling.
Maintain a minimum of three to four inches above and below the drive and a minimum of three inches on
either side of units rated below 20 HP. Maintain a minimum of six to eight inches above and below the drive and a minimum of four inches on either side of of units rated above 20 HP. Fans or blowers should be used to insure proper cooling in tight quarters. Do not mount drives above other drives or heat producing equipment. Note the ambient operating temperature ratings for each drive model.
If it is necessary to drill or cut the enclosure or panel, extreme care must be taken to avoid damaging drive components or contaminating the drive with metal fragments (which cause shorting of electrical circuits).
Cover drive components with a clean cloth to keep out metal chips and other debris. Use a vacuum cleaner to clean drive components after drilling, even if chips do not appear to be present. Do not attempt to use positive air pressure to blow chips out of drive, since this will lodge debris under electronic components.
Contaminating the drive with metal chips can cause drive failure and will void the warranty.
20
11. INPUT AC LINE REQUIREMENTS
HAZARDOUS VOLTAGE
Hazard of electrical shock. Disconnect incoming power and wait three minutes before servicing the drive. Capacitors retain charge after power removal.
INPUT AC POWER REQUIREMENTS
VOLTAGE:
The input voltage must match the drive’s nameplate voltage rating. Voltage fluctuation must not vary by greater than 10% overvoltage or 15% undervoltage. Note: Drives with dual rated voltage input and must be set for the proper supply voltage - see VOLTAGE SELECTION section.
The drive is suitable for use on a circuit capable of delivering not more than 18,000 rms symmetrical amperes, at the drive’s rated voltage. This is applicable only when a 3% impedance reactor and current limiting fuses are installed at the input power of VSD57 drive.
Phase to phase voltage imbalance must be less than 2.0%. Excessive phase to phase imbalance can cause severe damage to the drive’s power components.
Motor voltage should match line voltage in normal applications. The drive’s maximum output voltage will equal the input voltage. Use extreme caution when using a motor with a voltage rating which is different from the input line voltage - see BASE FREQUENCY (Parameter #100) in the DESCRIPTION OF PARAMETERS section.
kVA RATINGS:
If the kVA rating of the AC supply transformer is greater than ten times the input kVA rating of the drive, a drive isolation transformer, or a 2 to 3% input line inductor (also known as a choke or reactor) must be added.
This applies only to 200 / 240 VAC and 400 / 480 VAC models 20 hp and below, and 480 / 590 VAC models
3 hp and below, since larger units have built in line reactors.
Line Reactor 1) At 200V & 460V standard 25 HP and above
2) At 575 Volt standard 5 HP and above
INPUT FUSING AND DISCONNECT REQUIREMENTS
A circuit breaker or a disconnect switch with fuses must be provided in accordance with the National Electric
Code (NEC) or Canadian Electrical Code (CEC) and all local codes.
The VSD57 Variable Torque is capable of withstanding a 120% overload for 60 seconds. The VSD57
Constant Torque is capable of withstanding a 150% overload for 60 seconds. Select a fast actingfuse or magnetic trip circuit breaker rated at a maximum of 1.2 times the input amperage rating of the Variable Torque
Drive or select a fast acting fuse or magnetic trip circuit breaker rated at a maximum of 1.5 times the input rating of the Constant Torque Drive. Note: See the Drive Ratings Section.
Minimum voltage rating of the protection device should be; 250 VAC for 200 / 240 VAC rated drives, and 600
VAC for 400 / 480 VAC and 480 / 590 VAC drives.
All VSD57 drives require fuse protection, current limiting fuses must be used. Select fuses with low I
2
T values, rated at 200,000 AIC. Recommended fuses are Bussman type KTK-R and JJN for 200 / 240 VAC installations and KTK-R and JJS for 400 / 480 and 480 / 590 VAC drives. Similar fuses with equivalent ratings by other manufacturers may also be acceptable.
21
12. VOLTAGE SELECTION
BEFORE APPLYING INCOMING AC VOLTAGE, VERIFY THAT THE PROPER
VOLTAGE SELECTION AT (PL1, OR PL2), AND PARAMETER #94 HAS BEEN MADE.
FAILURE TO PROPERLY SELECT THE INPUT
VOLTAGE MAY RESULT IN DRIVE DAMAGE.
INPUT RATINGS
VSD57 Series drives rated for 200/240 VAC, 50-60 HZ input: with the proper voltage selection, the drives will function with input power of 208 VAC (+ 10%, - 15%) or with input power of 240 VAC (+ 10%, - 15%), at 48 to 62 HZ.
VSD57 Series drives rated for 400/480 VAC, 50-60 HZ input: with the proper voltage selection, the drives will function with input power of 400 VAC (+ 10%, - 15%) or with input power of 480 VAC (+ 10%, - 15%), at 48 to 62 HZ.
VSD57 Series drives rated for 480/590 VAC, 50-60 HZ input: with the proper voltage selection, the drives will function with input power of 480 VAC (+ 10%, - 15%) or with input power of 590 VAC (+ 10%, - 15%), at 48 to 62 HZ.
VOLTAGE SELECTION
To select the proper voltage on 1, 2, and 3 horsepower 200 / 240 VAC drives position the plug on pin header
PL1, located in the lower right corner of the power board. See figure a and figure b, below.
For all other units select the proper voltage by moving the jumper plug on pin header PL2 to the position on pin header PL2 which corresponds to the desired input voltage - middle and lower pin for 200, VAC input
(on 590V product) (figure c), and middle and upper pin for 240, 400V or 480 (on 480V product), or 590 VAC input (figure d).
NOTE: In addition to the voltage jumper selection, Parameter # 94 must also be selected for the proper voltage - see the PARAMETER DESCRIPT ION section.
2 - 3 HP, 200 / 240 VAC
MODELS
PL1
PL1
240V
208V
240V 208V
208 VAC INPUT SETTING figure a.
PL2
240 VAC INPUT SETTING figure b.
ALL OTHER UNITS
PL2
MODEL
CODE
1200
1400
1500
200V
400V
480V
240V
480V
590V
208, 400, 480 VAC
INPUT SETTING figure c.
MODEL
CODE
1200
1400
1500
200V
400V
480V
240, 480, 590 VAC
INPUT SETTING figure d.
240V
480V
590V
22
13. WIRING
Note drive input and output current ratings and check applicable electrical codes for required wire type and size, grounding requirements, over-current protection, and incoming power disconnect, before wiring the drive. Size conservatively to minimize the voltage drop.
GENERAL WIRING PRACTICES
Good wiring practices requires the seperation of controlcircuit wiring from all power (line and load) wiring.
Power wiring to the motor must have the maximum possible seperation from all other power wiring, whether from the same drive or other drives; do not run in the same conduit. This seperation reduces the possibility of coupling electircal noise between cicuits.
When wiring VSD57 Drives, follow the wiring practices required by national and local electrical codes in addition to the practices below:
•
Use metallic conduit for all drive controller wiring. Do not run control and power wiring in the same conduit. All three power output wires, from terminals T1, T2 and T3 to the motor, must be kept tightly bundled and run in a seperate conduit away from all other wiring.
•
Metallic conduits carrying power wiring or low-level control wiring must be separated by at least 4 in
(10cm)
•
Non-metallic conduits or cable trays used to carry power wiring must be separated from metallic conduit carrying low-level control wiring by at least 12 in (30.5cm).
•
Whenever power and control wiring cross, the metallic conduits and non-metallic conduits or trays must cross at right angles.
•
In some installations, conducted emissions to the line from the drive controller must be attenuated to prevent interference with telecommunication, radio and sensitive electronic equipment. In these instances, attenuating filters may be required.
INPUT WIRING PRECAUTIONS
HAZARDOUS VOLTAGE
Hazard of electrical shock. Disconnect incoming power and wait three minutes before servicing the drive. Capacitors retain charge after power removal.
Input fusing and a power disconnect switch or contactor MUST be wired in series with terminals L1, L2, and
L3. These may be supplied by Schneider Canada Inc., as an option. If one has not been supplied by
Schneider Canada Inc., a disconnect means must be wired during installation. This disconnect must be used to power down the drive when servicing, or when drive is not to be operated for a long period of time, but should not be used to start and stop the motor. Start and stop the motor with the drive run/stop circuit.
Repetitive cycling of a disconnect or input contactor (more than once every two minutes) may cause damage to the drive.
The drive is nameplated for three phase input only, wire input to terminals L1, L2, and L3.
23
OUTPUT WIRING PRECAUTIONS
DRIVE CONTOLLER DAMAGE
Drive controller will be damaged if input line voltage is applied to output terminals (U/T1, V/T2, W/T3). Check power connections before energizing drive controller.
Failure to observe this precaution can result in equipment damage, severe personal injury or death.
The drive controller is sensitive to the amount of capacitance (either phase-to-phase or phase-to-ground) present on the output power conductors. If excessive capacitance is present, the drive controller may trip.
Follow the guidlines below when selecting output cable:
•
Cable type: the cable selected must have a low capacitance phase-to phase and to ground. Do not use mineral impregnated cable because it has a very high capacitance. Immersion of cables in water increases capacitance.
•
Cable length: the longer the cable, the greater the capacitance. Cable lengths greater than 320 ft
(100m) may cause problems.
•
Proximity to output cables from other drive controllers: because of the high frequency switching and increased capacitance, the drive may fault under some conditions.
•
Do not use lightning arrestors or power factor correction capacitors on output of drive controller.
For installations where cable capacitances may be a problem, an inductor can be installed between the drive controller and the motor.
All three power output wires, from terminals T1, T2, and T3 to the motor, must be kept tightly bundled and run in a separate conduit away from all other wiring.
Do not install contactors between drive and motor without consulting Schneider Canada Inc. Representative, for more information.
24
GROUNDING
For safe , dependable operation, drive controllers must be grounded according to national and all local codes.
To ground the drive controller:
•
Connect a copper wire from the grounding terminal to the power system ground conductor. Wire size is determined by the drive controller size and by national and local codes
•
Verify resistance to ground is one ohm or less. Improper grounding causes intermittent and unreliable operation.
•
Ground equipment using screw provided.
•
Drive controller must be grounded before applying power.
•
Do not use metallic conduits or shields as a ground conductor.
Failure to observe these precautions will cause shock or burn, resulting in severe personal injury or death
25
VSD 57 SERIES POWER WIRING DIAGRAM
WARNING !
Do not connect AC incoming power to terminals T1, T2, or T3.
Severe damage to the drive will result.
GND
LED 101
T1 T2 T3 DB1 DB2 L3 L2 L1
FUSED
INPUT
VOLTAGE
GND
DISCONNECT
SWITCH
(REQUIRED)
GND
THREE PHASE
AC MOTOR
GND
INSTALL, WIRE AND GROUND IN ACCORDANCE WITH ALL APPLICABLE CODES.
NOTES:
1.) WIRE THE MOTOR FOR THE PROPER VOLTAGE PER THE OUTPUT RATING OF THE DRIVE. MO-
TOR WIRES MUST BE RUN IN A SEPARATE STEEL CONDUIT AWAY FROM CONTROL WIRING
AND INCOMING AC POWER WIRES.
2.) DO NOT INSTALL CONTACTORS BETWEEN DRIVE AND MOTOR, WITHOUT FIRST CONSULT-
ING SCHNEIDER CANADA FOR MORE INFORMATION. OPERATING CONTACTORS BETWEEN
DRIVE AND MOTOR MAY RESULT IN DRIVE DAMAGE.
3.) REMOVE ANY EXISTING, AND DO NOT INSTALL, POWER FACTOR CORRECTION CAPACITORS
BETWEEN DRIVE AND MOTOR. FAILURE TO DO SO WILL RESULT IN DRIVE DAMAGE.
4.) USE ONLY UL AND CSA LISTED AND APPROVED WIRE.
5.) WIRE MINIMUM VOLTAGE RATINGS: 300 V FOR 200 / 240 VAC SYSTEMS AND 600 V FOR 400 /
480 AND 480 / 590 VAC SYSTEMS.
6.) SELECT WIRE GAUGE BASED ON A MINIMUM OF 120% OF THE VARIABLE TORQUE DRIVE’S
AND 150% OF THE CONSTANT TORQUE DRIVE’S CONTINUOUS INPUT CURRENT RATING,
AND MINIMUM 75°C INSULATION RATING. USE COPPPER WIRE ONLY. SEE DRIVE RATINGS
FOR CURRENT RATING.
7.) WIRE AND GROUND IN ACCORDANCE WITH NEC OR CEC, AND ALL APPLICABLE LOCAL
CODES.
26
14. CONTROL WIRING
INSTALL, WIRE, AND GROUND IN ACCORDANCE WITH NEC OR CEC,
AND ALL APPLICABLE LOCAL CODES.
ALL CONTROL WIRING MUST BE WIRED WITH CLASS I WIRING OR
EQUIVALENT. USE COPPER WIRE RATED FOR A MINIMUM OF 75° C.
The drive can be controlled by the keypad or by operators wired to the control terminal strip. To run the drive from the keypad, wire the control per the instructions in the OPERATING BY KEYPAD CONTROL section.
Control wiring, when run external to the drive, MUST be in a separate conduit and away from all input and output power wiring. Use twisted wires or shielded cable grounded at drive panel ONLY.
Terminals marked 2 are the circuit common used for the start, stop, jog, fwd / rev, input select, local / remote, analog input, analog output, and E-stop functions. If necessary terminal 2 may be connected to chassis ground.
SURGE PROTECTION
Current and voltage surges and spikes in the coils of contactors, relays, and solenoids, near or connected to the drive can lead to faulty drive operation. A snubber circuit should be used on relay and contactor coils associated with the inverter. For AC loads snubbers should consist of a resistor and a capacitor in series across the coil. For DC loads a free-wheeling or flyback diode should be placed across the coil.
RUN COMMAND
Start-stop control can be accomplished by either a two wire or a three wire circuit. For two wire control, terminal 2 is connected to terminal 12A and the run contact is wired to terminals 1 and 2. For three wire control, a normally closed pushbutton is wired to terminals 1 and 2 (stop signal) and a normally open pushbutton is wired to terminals 2 and 12A (start signal).
SPEED REFERENCE SIGNAL
The drive allows for three speed reference signal types: a speed potentiometer (2.5 to 10 k Ohm), 4-20 MA, or 0-10 VDC signals. For control by a speed pot., the wiper lead is connected to terminal 5A, and the high and low end leads are connected to terminals 6 and 2, respectively. For 4-20 MA control, wire the positive to terminal 5B and the negative to terminal 2. For 0-10 VDC control, wire the positive to terminal 5D and the negative to terminal 2.
The input impedance of terminal 5A, speed control potentiometer input is 100 K ohms, the 0-10 VDC input, terminal 5D, is 200 K ohms, and the 4-20 MA input, terminal 5B, is 100 ohms (0.4 to 2.0 VDC). Terminal 2 is circuit common (the minus connection).
OUTPUT FREQUENCY / LOAD SIGNAL
The drive is equipped with output signals that are proportional to output frequency (speed) or load. These signals can be used to interface with other equipment or to operate speed or load meters. Three signals proportional to frequency are available: a 0-10 VDC voltage signal between terminals 10B and 2 (capable of sourcing 20 MA @ 10 VDC); a frequency output (40 to 50% duty cycle pulse train) between terminals 10C and 2 (12 VDC open circuit, 2200 ohm source impedance). The frequency is six times the drive output frequency; A 4-20 MA DC current signal between terminals 10D and 2; and a 0 - 10 VDC, or 2 - 10 VDC voltage signal between terminals 10E and 2, (capable of sourcing 20 MA @ 10 VDC).
Note: The output type must be selected in the case of the analog outputs - see the PARAMETER
DESCRIPTION section.
27
AUXILIARY OUTPUT CONTACTS SERIES MODELS
The control board has two auxiliary relays with form "C" contacts, and an open collector (transistor) output which can be used to indicate several different drive functions - see the PARAMETER DESCRIPTION section,
(Parameters 121, 122, and 124).
The terminals for relay number one are 16, 17, and 18. The terminals for relay number two are 19, 20, and
21. Terminals 17 and 20 are the respective commons. Contacts between 16 and 17, and 19 and 20 are normally open (N.O.). Contacts between 17 and 18, and 20 and 21 are normally closed (N.C.). Contacts are rated 2 amps at 28 VDC or 120 VAC.
The open collector output is at terminal 14. It is a current sinking type output and is rated at 24 VDC, 5 MA maximum. Control wiring diagrams show relays in the rest state (coils NOT energized)
FORWARD-REVERSE
Terminals 12B and 12C are used to select direction of motor rotation in the remote mode. Terminal 12B must be maintained closed to terminal 2 to select forward or terminal 12C must be maintained closed to terminal 2 to select reverse for the drive to start when in the remote mode.
JOG
Closing the remote jog circuit, terminal 2 to terminal 12D, will activate the remote jog mode. When the jog mode is activated, the drive will start (or continue to run if already started), ramp to the jog speed at the jog accel (or decel) rate and run at the jog speed until the jog circuit is opened.
THE JOG FUNCTION OVERRIDES THE KEYPAD
& REMOTE STOP COMMANDS.
To disable the JOG function in the REMOTE mode while the STOP command is active, wire the control terminal strip per the following diagrams:
Two Wire Start/Stop
28
Three Wire Start/Stop
SPEED REFERENCE SELECTION
A speed reference is selected by closing one of the terminals 12E through 13C to terminal 2.
Closing terminal 12E to 2 activates a pot. wired to terminals 2, 5A, and 6. Closing terminal 12F to 2 activates a 4 - 20 MA speed reference wired to terminals 2 and 5B. Closing terminal 12G to 2 activates a 0 - 10 VDC speed reference wired to terminals 2 and 5D. Closing different combinations of terminals 13A, 13B, and/or
13C to terminal 2 will activate one of the seven preset speeds. See "Parameters # 11 - 17 PRESET SPEEDS" in the DESCRIPTIONS OF PARAMETERS section.
EMERGENCY STOP ( E-Stop )
The control board has terminals to facilitate safety interlocks, and protective devices, (e.g. E-Stop pushbutton).
Opening terminals 22 to 2, will cause the drive to trip into the EMERGENCY STOP function. When the
EMERGENCY STOP condition exists, the drive will COAST TO STOP, it will not follow the NORMAL DECEL ramp. ( See the following parameters, NORMAL DECEL, (Parameter #30), COAST TO STOP, (Parameter
#65), and DYNAMIC BRAKING, Parameter #86 ).
The drive will not start unless there is Emergency Stop protective devices, or a wire jumper closing terminals
22 to 2.
29
15. VSD57 SERIES CONTROL WIRING DIAGRAM
30
16. INITIAL POWER UP
HAZARDOUS VOLTAGE
•
Hazard of electrical shock. Disconnect incoming power and wait three minutes before servicing drive. Capacitors retain charge after power is removed.
•
DC bus LED is not an accurate indication of abscence of DC bus voltage.
•
DO NOT short across capacitors or touch unsheilded components or terminal strip screw connections with voltage present
•
Many parts in this drive controller, including printed wiring boards, operate at line voltage. DO NOT TOUCH. Use only electrically insulated tools.
•
Failure to observe these precautions will cause shock or burn, resulting in severe personal injury or death.
Before attempting to operate drive, motor, and driven equipment be sure all procedures pertaining to installation and wiring have been properly followed. Before powering up the drive for the first time, wire the drive for operation via the keypad (see OPERATING BY KEYPAD CONTROL), then follow the procedures below.
Disconnect the driven load from the motor. Verify that the drive input terminals L1, L2, and L3 are wired to the proper input voltage (per the nameplate rating of the drive). Verify the voltage selection has been properly selected per the "VOLTAGE SELECTION" section.
INCOMING AC POWER MUST NOT BE WIRED TO T1, T2, OR T3!
DO NOT CYCLE INCOMING AC MORE THAN ONCE
PER TWO MINUTES!
Failure to observe these precautions will cause shock or burn, resulting in severe personal injury or death.
Energize the incoming power line. The LCD display should light and indicate the standby mode. If the display does not appear, remove the incoming power, wait three minutes, check to be sure the bus capacitors have discharged, and verify correct installation of wiring. If wiring is correct, re-apply incoming power, note display for drive status. Next follow the procedures in the "PROGRAMMING" section to properly configure the parameter values.
Power down the drive and wait for the bus capacitors to discharge, then wire the proper (correct voltage) leads of the motor to T1, T2, and T3. Reapply incoming power and then press start. If the motor rotates in the wrong direction, remove the incoming power, wait three minutes, check to be sure the bus capacitors have discharged and swap motor wires connected to T1and T2.
Rewire control wiring per directions in the CONTROL WIRING section, if required.
31
17. OPERATING BY KEYPAD CONTROL
The drive can be operated by keypad (local mode), by control devices wired to the control terminal strip
(remote mode), by serial communications (serial mode), or by a combination of the terminal strip and either the keypad or serial communications control source. Units should first be run in the keypad control mode during initial start up. For information on wiring remote operators see the CONTROL WIRING section and the DESCRIPTION OF PROGRAMMABLE PARAMETERS sections.
SETTING UP FOR CONTROL BY THE KEYPAD
To operate by keypad control first wire the control terminal strip per the diagram depicted below:
0 1 2 5A 5B 5D 6 7 10B 10C 10D 10E 12A 12B 12C 12D 12E 12F 12G 13A 13B 13C 14 16 17 18 19 20 21 2 22 23
WIRING FOR BASIC KEYPAD CONTROL
1.) 2 to 1 de-activates the remote stop. (NOTE: The remote stop function is always operational, even in the local mode).
2.) 2 to 7 to activate local (keypad) mode.
3.) 2 to 22 to de-activate E-stop.
Note : To Run in the remote mode, in addition to opening terminals 2 to 7, several terminal closures must be made: A contact closure needs to be made by closing terminal 1 to 2, and terminal 12A to 2. A direction must be selected by closing terminal 12B or 12C to 2. A speed reference type must be selected by closing terminal 12E, 12F, 12G, 13A, 13B, or 13C to terminal 2, Terminal 12D to 2, JOG, activates the jog function.
THIS CIRCUIT OVERRIDES THE START/STOP FUNCTION AND CAUSES THE DRIVE TO RUN AT THE
SPEED DETERMINED BY THE JOG SPEED PARAMETER.
KEYPAD FUNCTIONS IN LOCAL OPERATING MODE
START, STOP - Note: The keypad STOP key is always active in both the LOCAL or REMOTE modes.
SPEED CONTROL - To change the speed via the keypad press the UP ARROW and DOWN ARROW keys to scroll to the desired speed, or input the desired speed with the numerical keys, and press ENTER.
JOG - To enter the keypad jog mode, press the JOG key while holding down the STOP key, and then release both keys. "JOG" will appear in the speed reference portion of the display. The drive will now jog whenever the JOG button is pressed. Press any other key than JOG to exit the jog mode.
FORWARD/REVERSE - To change the direction of rotation press the FWD/REV key, and then press the
ENTER key. Note: Parameter #66 must be set to FWD + REV for this key to be active. (NOTE: FORWARD
ONLY is the factory default).
32
SPEED REFERENCE SELECTION (AUTO/MANUAL) - To change between keypad speed control (MAN) and some other speed reference type (AUTO) press the AUTO/MAN key, and then press ENTER. To activate a speed reference type other than keypad control, the corresponding terminal (12E, 12F, 12G, 13A, 13B, or
13C) on the control strip must be connected to terminal 2. See the control wiring section. Note: Parameter
#67 must be set to AUTO/MANUAL SPEED, or AUTO/MANUAL LOCAL for this key to be active, - see the
DESCRIPTION OF PARAMETERS section.
CLEARING MIS-KEYED INPUTS - Use the CLEAR key to clear errors made while entering data.
VIEWING A FAULT - To view the present fault condition press ENTER while in the operating mode. To view previous faults press Prog/Run and then ENTER. (Previous faults are stored in Parameter #200, see the
DESCRIPTION OF PARAMETERS section).
THE VSD57 SERIES KEYPAD DISPLAY IN THE OPERATING MODE ( NORMAL )
RUN
STATUS
COMMANDED
SPEED
SPEED
UNITS
LOAD
STOP 60.00 HZ
1% LOAD FWD KEY
LOAD
UNITS
DIRECTION
SPEED
REFERENCE
THE VSD57 SERIES KEYPAD DISPLAY IN THE OPERATING MODE - ACTUAL SPEED
(ALTERNATE ), PARAMETER #133.
ACTUAL RUN
SPEED
COMMANDED
SPEED
SPEED
UNITS
LOAD
60.00 60.00 HZ
1% LOC FWD KEY
CONTROL
MODE
DIRECTION
SPEED
REFERENCE
33
18. MONITOR MODE
The Monitor Mode has four display functions: Time Since Start, Total Run Time, Total KiloWatt Hours, and
Hours Until Maintenance Required.
Time Since Start displays the time since the drive was started. This value resets each time the START button is pressed or if power is removed from the drive.
Total Run Time displays the total elapsed run time. The value is displayed in hours and minutes. For memory purposes the value is rounded to the nearest hour and stored in non-volatile memory. This value is non-resettable.
Total Kilowatt-Hours displays the total elapsed kilowatt-hours as calculated from the total elapsed run time, motor current and voltage. This value is non-resettable.
Hours Until Maintenance Required displays the time remaining until the Maintenance Target (Parameter
#132) is reached. This parameter is usually used to indicate a time when maintenance needs to be completed on driven equipment (e.g. motor or gear box lubrication) Parameter #132 must be set to a value higher than zero for this function to be enabled.
To enter the Monitor Mode press the ENTER button while in the Operating Mode. Pressing the ENTER button once will display the Time Since Start function. Pressing the ENTER button a second time will display the
Total Run Time function. Pressing the ENTER button a third time will display the Total KiloWatt-Hour function.
Pressing the ENTER button a fourth time will display the Hours Until Maintenance Required function if
Parameter #132 is set to a value higher than zero. Pressing the ENTER button a fifth time will return the display to the Operating Mode.
Examples of the four Monitor Mode Functions:
Time Since Start Display
Total Run Time Display
TIME SINCE START
12 : 45 HR
TOTAL RUN TIME
4500 : 55 HR
Total Kilowatt-Hour Display
TOTAL KW HOURS
49345 KWH
Hours until Maintenance Display
HOURS TIL MAINT
650 HR
Parameter #132 -
34
19. PROGRAMMING - CONFIGURATION
THE VSD57 SERIES KEYPAD
The drive is programmed using the keypad to enter the program parameter menu and change parameter values. The keypad may also be used to operate the drive when in the local mode (terminal 7 closed to terminal 2). An LED to the right of the LCD display indicates when the drive is running (power is applied to the motor).
2 X 16 BACK LIT LCD
PROG
RUN
CLEAR
0
7 8 9
4
5 6
1 2 3
RUN
Variable Speed AC Drive
AUTO
MAN
FWD
REV
JOG
START
STOP
ENTER
When the drive is first powered up it will be in the operating mode in standby. The display will appear as follows:
STOP 20.00 HZ
0%LOAD FWD KEY
To program the drive, first access the program mode by pressing the PROG/RUN button. This will result in either direct entry into the program mode if password protection is disabled or the ENTER PASSWORD prompt will be displayed if password protection is enabled. If the ENTER PASSWORD: prompt is displayed
(see diagram below) input the appropriate password and press the ENTER key.
35
Pressing the ENTER key, prior to entering a password, upon initially entering the program mode will access
Parameter #200 PREVIOUS FAULTS. This parameter retains a historical log of ten previous drive protection trip conditions.
If an asterisk is showing in the upper right hand corner of the display, it is not necessary to input the password before pressing ENTER. The asterisk will appear for approximately three minutes after initial entry into the drive menu. Pressing the ENTER button when the asterisk is showing, places the drive in programming mode, at the last parameter viewed.
Upon entering the program mode the first item in the parameter list will be displayed (see below).
ENTER PASSWORD:
0000
To change the displayed parameter, scroll through the menu using the UP and DOWN keys, or move directly
1 CURRENT LIM.
180%
to the desired point by keying in a new parameter number with the numerical keys and then pressing ENTER.
To change the parameter value, press ENTER to move the "cursor" (highlighted character) from the parameter number ("1" in the above example) to the parameter value ("180%" in the above example). Then while the cursor is on the parameter value change the parameter value by scrolling to the desired value using the UP arrow and DOWN arrow keys and pressing the ENTER key. Numeric parameter values may also be changed by keying in the desired value via the numerical keys and then pressing ENTER.
See the PARAMETER MENU and PARAMETER DESCRIPTION sections for more information on programming.
36
20. PROGRAMMABLE PARAMETER MENU
54
61
62
64
65
66
67
ITEM
NUMBER
1
2
20
21-27
29
30
31-37
38
39
3
4
5
9
11-13
14-17
19
41
42
43
44
50
51
52
53
70
71
72
73
75
PARAMETER MENU
PARAMETER
NAME
VALUE LIMIT OR
MENU CHOICE
DEFAULT
SETTING
CURRENT LIMIT
THERMAL OVERLOAD
SLIP COMPENSATION
SPEED @ 4 MA / 0 VDC
SPEED @ 20 MA / 10 VDC
PRESET ACC / DEC
SPEED PRESETS #1- #3
SPEED PRESETS #4- #7
JOG SPEED
NORMAL ACCEL
PRESET #1 - #7 ACCEL
JOG ACCEL
NORMAL DECEL
PRESET #1 - #7 DECEL
TAPER DECEL
JOG DECEL
SKIP SPEED #1
SKIP SPEED #2
SKIP SPEED #3
SKIP BANDWIDTH
TB-10B / D FUNCTION
FREQUENCY OUT @ MAXIMUM
TB-10D RESISTANCE OHM
TB-10E FUNCTION
LOAD OUT AT MAXIMUM
MINIMUM FREQUENCY
MAXIMUM FREQUENCY
STABILITY
COAST TO STOP
FORWARD / REVERSE
AUTO / MANUAL SEL
AUTO START
RESTART ON FAULT
RESTART LIMIT
RESTART DELAY
RESTART DECEL
5 - 120 % (for VT) - 180% (for CT) 120 % (for VT) -
180% (for CT)
50 - 120 % (for VT) - 150% (for CT) 120 % (for VT) -
150% (for CT)
0 - 5.0 %
0.00 - 360.00 HZ
0.00 - 360.00 HZ
0.0 %
0.00 HZ
60.00 HZ
DISABLED, ENABLED
0.00 - 120.00 HZ
0.00 - 120.00 HZ
0.00 - 120.00 HZ
SEE TABLE 1
SEE TABLE 1
SEE TABLE 1
DISABLED
10.00 HZ
10.00 HZ
10.00 HZ
30.0 SEC
30.0 SEC
30.0 SEC
SEE TABLE 2
SEE TABLE 2
DISABLED, ENABLED
SEE TABLE 2
0.00 - 120.00 HZ
0.00 - 120.00 HZ
0.00 - 120.00 HZ
0.00 - 10.00 HZ
0 -10 V FREQ, 0 -10 V LOAD,
4 - 20 MA FREQ, 4 - 20 MA LOAD
1.00 - 360.00 HZ
0 - 250
30.0 SEC
30.0 SEC
DISABLED
30.0 SEC
0.00 HZ
0.00 HZ
0.00 HZ
2.00 HZ
0 - 10V FREQ
60.00 HZ
250
0 - 10V LOAD 0 - 10V FREQ, 0 -10 V LOAD,
2 -10 V FREQ, 2 -10 V LOAD,
DISABLED
10 - 200 %
0.00 - 120.00 HZ
0.00 - 120.00 HZ
NORMAL, LOW, MED, HIGH
ENABLED, DISABLED
125 %
0.50 HZ
60.00 HZ
NORMAL
ENABLED (for VT)
DISABLED (for CT)
FWD ONLY FWD ONLY, REV ONLY,
FWD + REV
AUTO SPEED, MANUAL SPEED,
AUTO / MANUAL SPEED
AUTO / MANUAL LOCAL
DISABLED, ENABLED
DISABLED, ENABLED
1 - 5
1.0 - 180.0 SEC
0.1 - 999.9 SEC
AUTO / MANUAL
SPEED
DISABLED
DISABLED
3
5.0 SEC
10.0 SEC
37
PASSWORD
LEVEL
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
91
92
93
94
82
83
84
86
90
95
100
101
ITEM
NUMBER
76
80
104
105
121
122
123
124
130
132
133
PARAMETER
NAME
RESTART
CURRENT LIMIT
DC BRAKE
DC BRAKE LOAD
STOP BRAKE
START BRAKE
DYNAMIC BRAKING
SPEED UNITS
SPEED MULTIPLIER
LOAD UNITS
LOAD MULTIPLIER
AC INPUT
SPEED DP
BASE FREQUENCY
V/HZ CURVE TYPE
AUTO V BOOST
MANUAL V BOOST
RELAY #1 FUNCTION
RELAY #2 FUNCTION
RELAY SET SPEED
TB-14 FUNCTION
DRIVE POWER
MAINTENANCE TARGET
DISPLAY FUNCTION
PARAMETER MENU
VALUE LIMIT OR
MENU CHOICE
10 - 180 %
DEFAULT
SETTING
100 %
DISABLED, CONTINUOUS,
ON START, ON STOP,
@ ZERO SPEED, START &
STOP,
ZERO SPEED & STOP
20 - 180 %
0.1 - 60.0 SEC
0.1 - 20.0 SEC
DISABLED, ENABLED
HZ, RPM, % RPM, /S, /M,
/H, #/S, #/M, #/H
0.10 - 400.00
% LOAD, AMPS
0.01 - 300.00
240 / 480 / 590
200 / 400 / 480
XXXXX, XXXX.X, XXX.XX,
XX.XXX, X.XXXX, .XXXXX
10.00 - 360.00 HZ
LINEAR - 1.0,
VAR TORQUE - 1.3,
VAR TORQUE - 1.6,
VAR TORQUE - 2.0
0.0 - 20.0 %
0.0 - 30.0 %
NO FUNCTION, RUN, FAULT,
FAULT LOCKOUT, AT SPEED,
CURRENT LIMIT, FOLLOWER
PRESENT, AUTO SPEED MODE,
START PENDING,
ABOVE SET SPEED,
MAINTENANCE TARGET
NO FUNCTION, RUN, FAULT,
FAULT LOCKOUT, AT SPEED,
CURRENT LIMIT, FOLLOWER
PRESENT, AUTO SPEED MODE,
START PENDING,
ABOVE SET SPEED,
MAINTENANCE TARGET
0.00 - 120.00 HZ
NO FUNCTION, RUN, FAULT,
FAULT LOCKOUT, AT SPEED,
CURRENT LIMIT, FOLLOWER
PRESENT, AUTO SPEED MODE,
START PENDING,
ABOVE SET SPEED,
MAINTENANCE TARGET
0 - 150 (for CT), 0 - 200 (FOR VT)
0 - 65,000 HR
NORMAL, ACTUAL SPEED
DISABLED
0 %
5.0 SEC
5.0 SEC
DISABLED
HZ
30.00
% LOAD
1.00
240 / 480 / 590
XXXXX
60.00 HZ
VAR TORQUE -
1.6 (for VT)
LINEAR - 1.0 (for
CT)
0.0 %
SEE TABLE 3
RUN
FAULT
0.50 HZ
NO FUNCTION
0
0 HR
NORMAL
PASSWORD
LEVEL
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
38
146
147
148
149
150
198
200
ITEM
NUMBER
137
141
142
144
145
PARAMETER
NAME
CARRIER FREQUENCY
SELECTION
FACTORY PARAMETERS
CLEAR HISTORY
SOFTWARE VERSION
SERIAL COMMUNICATIONS
SERIAL TIMEOUT
SERIAL ADDRESS
ENABLE PASSWORDS
LEVEL 1 PASSWORD
LEVEL 2 PASSWORD
LANGUAGE
PREVIOUS FAULT
PARAMETER MENU
VALUE LIMIT OR
MENU CHOICE
1.5 kHZ, 8 kHZ, 10 kHZ, 12 kHZ
(NOTE: DERATING
INFORMATION
IN SECTION 5.1)
DISABLED, ENABLED
DISABLED, ENABLED
213-020X
DISABLED, DETECT,
MONITOR ONLY, PROGRAM,
CONTROL,
PROGRAM & CONTROL
0 - 30 SEC
1 - 30
DISABLED, ENABLED
0000 - 9999
0000 - 9999
ENGLISH, SPANISH
THIS "PARAMETER" IS FOR
VIEWING ONLY
DEFAULT
SETTING
1.5 kHZ
DISABLED
DISABLED
213-020X
PROGRAM
8 SEC
1
ENABLED
9100
0019
ENGLISH
N/A
PASSWORD
LEVEL
2
2
2
2
2
2
2
0
2
2
2
2
39
21. DESCRIPTION OF PARAMETERS
1 - CURRENT LIMIT
The current limit setting determines the maximum value of the output current. This is usually done to limit motor torque capability. For most applications the current limit is maintained at the maximum setting.
2 - THERMAL OVERLOAD
The THERMAL OVERLOAD setting is used to protect the motor from overheating due to excess current.
The trip time for the THERMAL OVERLOAD setting is based on what is known as an "inverse I squared t" function. This circuit emulates the function of a mechanical thermal overload relay (commonly referred to as
"heaters").
Set the THERMAL OVERLOAD to a value which is equal to the ratio of the motor amp rating to the drive amp rating X 120% for V.T. or X 150% for C.T. . This will result in a trip at 120% for V.T. or 150% for C.T. of the motor rating in one minute and allow for the continuous operation at a 1.0 service factor.
Example: For a 10 Hp, 480 VAC drive operating a 7.5 Hp motor with a full load current rating of 11 amps.
Divide the motor current rating by the drive output current rating and then multiply by 120% for V.T. or 150% for C.T..
For V.T. (11.0/14.0) x 120% = 94% approx. (for one minute), and (11.0/14.0) x 100% = 79% approx.
(continuous)
For C.T. (11.0/14.0) x 150% = 118% approx. (for one minute), and (11.0/14.0) X 100% = 79% approx.
(continuous).
3 - SLIP COMPENSATION
SLIP COMPENSATION is used to compensate for changes in motor speed ("slip") which occur due to changes in load. In a standard AC induction motor, as the load on the motor increases, the motor current increases and the motor shaft speed decreases. By increasing the output frequency in response to the increased motor current, the reduction in the motor speed due to increased load is greatly reduced. Speed regulation with no load to full load fluctuations of less than 1% of base speed are attainable in most applications. SLIP COMPENSATION is often set to 3% since that is the standard slip rating of most AC induction motors. 0 Value means slip compensation is disabled.
4 - SPEED @ 4MA / 0V
5 - SPEED @ 20MA / 10V
These two parameters determine the gain in the 4 - 20 MA (or 20 - 4 MA) and 0 -10 VDC (or 10 - 0 VDC) follower circuit. The follower circuit is set to be either proportional (4 - 20 MA) or inversely proportional (20 -
4 MA) depending on which value is larger. The speed follower extremes can be set to any value at or between
0 - 360 HZ.
Example: To follow the speed of a 4 - 20 MA input signal where it is desired to have a minimum speed of 0
HZ at 4 MA and a maximum speed of 60 HZ at 12 MA; set Parameter #4 to 0 HZ, Parameter #5 to 120 HZ, and MAXIMUM FREQUENCY (Parameter #62) to 60 HZ.
Parameter #5 is set to 120 HZ since a line which passes through the points (0 HZ, 4 MA) and (120 HZ, 20
MA) also passes through point (60 HZ, 12 MA). Setting the MAXIMUM FREQUENCY to 60 HZ prevents the output frequency from rising above 60 HZ as the follower signal rises above 12 MA.
40
9 - PRESET ACC / DEC
This parameter is used to ENABLE or DISABLE the individual acceleration and deceleration rates for each of the seven speed presets. When disabled the NORMAL ACCEL (Parameter #20) and NORMAL DECEL
(Parameter #30) control the rate of acceleration and deceleration of all the presets.
11-17 - SPEED PRESETS #1- #7
Speed presets are pre-programmed speeds which are activated via contact closures between terminal 2 and terminal 13A, 13B, and/or 13C. The presets can be set to any value between the MINIMUM FREQUENCY and MAXIMUM FREQUENCY. The speed presets are activated by the multiplex scheme shown in the following tables:
PRESET NUMBER
ONE
TWO
THREE
FOUR
FIVE
SIX
SEVEN
PRESET SPEED ACTIVATION
TB-13A TO TB-2
CLOSED
OPEN
OPEN
CLOSED
CLOSED
OPEN
CLOSED
TB-13B TO TB-2
OPEN
CLOSED
OPEN
CLOSED
OPEN
CLOSED
CLOSED
TB-13C TO TB-2
OPEN
OPEN
CLOSED
OPEN
CLOSED
CLOSED
CLOSED
19 - JOG SPEED
The JOG SPEED determines the speed when a JOG is called for from the keypad (local JOG mode) or from a contact closure between terminals 2 and 12D (remote Jog mode). The JOG SPEED can be set to any value between the MINIMUM FREQUENCY and the MAXIMUM FREQUENCY.
JOG SPEED is usually set to a low value (5-10 HZ). For information on activating the JOG function see the
OPERATING FROM THE KEYPAD and CONTROL WIRING sections.
20 - NORMAL ACCEL
This parameter sets the acceleration rate when the speed is commanded from the keypad, a potentiometer,
4-20 MA, 0-5 VDC, or 0-10 VDC. It also determines the acceleration for the preset speeds if the PRESET
ACC/DEC is DISABLED. The NORMAL ACCEL does not have any effect when the speed is commanded by JOG. Minimum acceleration times vary with horsepower, SEE TABLE 1 for the NORMAL ACCEL value limit.
The ability to accelerate a given load at a particular rate will be limited by the output power capabilities of the drive/motor combination.
NOTE: All acceleration and deceleration times are based on the time to increase or decrease speed from 0
HZ to the BASE FREQUENCY (Parameter #100) value.
41
21-27 - PRESET #1 ACCEL - PRESET #7 ACCEL
These parameters set each individual acceleration rate when the speed is commanded by the corresponding preset speed (Parameters #1- #7) and PRESET ACC/DEC (Parameter #9) is set to ENABLED. Minimum acceleration times vary with horsepower, SEE TABLE 1 for the PRESET ACCEL value limit.
29 - JOG ACCEL
This parameter sets the acceleration rate for the Jog speed. Minimum acceleration times vary with horsepower, SEE TABLE 1 for the JOG ACCEL value limit.
MODELS
HORSEPOWER
1 - 15 HP
20 - 200 HP
TABLE 1
ACCELERATION TIMES
NORMAL ACCEL, (PRESET SPEEDS #1 THRU #7 ACCEL, AND JOG ACCEL)
VALUE LIMIT OR MENU CHOICE AND FACTORY DEFAULT
VSD57 230 TO 460V
VALUE LIMIT OR
MENU CHOICE
0.1 - 3600.0 SEC
1.0 - 3600.0 SEC
FACTORY
DEFAULT
30.0 SEC
30.0 SEC
MODEL
HORSEPOWER
1 - 15 HP
20 - 200 HP
VSD57 575V
VALUE LIMIT OR
MENU CHOICE
0.1 - 3600.0 SEC
1.0 - 3600.0 SEC
FACTORY
DEFAULT
30.0 SEC
30.0 SEC
30 - NORMAL DECEL
This parameter sets the deceleration rate when the speed is commanded by the keypad, potentiometer, 4
-20 MA, 0-5 VDC, 0-10 VDC, or speed presets when PRESET ACC/DEC is in the DISABLED mode. Dynamic braking may be needed to provide enough decelerating capacity to slow large inertia loads from higher speeds. See OPTIONS-DYNAMIC BRAKING. Minimum deceleration times vary with horsepower, SEE
TABLE 2 for the NORMAL DECEL value limit.
31-37 - PRESET #1 DECEL - PRESET #7 DECEL
These parameters set each individual deceleration rate when the speed is commanded by the corresponding preset speed (Parameter #1- #7) and PRESET ACC/DEC is set to ENABLED. Minimum deceleration times vary with horsepower, SEE TABLE 2 for the PRESET DECEL value limit.
38 - TAPER DECEL
Taper decel varies the decel "ramp" in order to increase stopping capacity on high inertia loads.
When this parameter is enabled, the decel ramp is altered from a linear relation to the "top half of an S-curve".
During the first part of the decel period, when rotational kinetic energy is high, the rate of decel is low. During the later part of the decel period the rate of decel increases.
39 - JOG DECEL
Jog Decel sets the deceleration rate for the Jog speed. Minimum deceleration times vary with horsepower,
SEE TABLE 2 for the JOG DECEL value limit.
42
MODELS
HORSEPOWER
1 - 7.5 HP
10 - 15 HP
20 - 40 HP
50 - 75 HP
100 -200 HP
TABLE 2
DECELERATION TIMES
NORMAL DECEL, (PRESET SPEEDS #1 THRU #7 DECEL, AND JOG DECEL)
VALUE LIMIT OR MENU CHOICE AND FACTORY DEFAULT
VSD57 230 TO 480V
VALUE LIMIT OR
MENU CHOICE
0.1 - 3600.0 SEC
FACTORY
DEFAULT
30.0 SEC
0.5 - 3600.0 SEC
2.5 - 3600.0 SEC
7.5 - 3600.0 SEC
15.0 - 3600.0 SEC
30.0 SEC
30.0 SEC
30.0 SEC
30.0 SEC
MODEL
HORSEPOWER
1 - 5 HP
7.5 - 10 HP
15 - 20 HP
25 - 40 HP
50 - 75 HP
100 - 200 HP
VSD57 575V
VALUE LIMIT OR
MENU CHOICE
0.1 - 3600.0 SEC
FACTORY
DEFAULT
30.0 SEC
0.5 - 3600.0 SEC
2.5 - 3600.0 SEC
7.5 - 3600.0 SEC
15.0 - 3600.0 SEC
30.0 SEC
30.0 SEC
30.0 SEC
30.0 SEC
25.0 - 3600.0 SEC 30.0 SEC
41 - 44 - SKIP SPEEDS
Parameters #41 through #44 are used to prevent continued operation at critical speeds. Critical speeds are speeds which cause mechanical resonance, usually causing excessive vibration in the driven equipment.
The SKIP SPEEDS (Parameters #41 - #43) and SKIP BANDWIDTH (Parameter #44) are used to define up to three speed ranges which correspond to critical speeds (speed avoidance ranges). The SKIP SPEEDS are the mid-points of each of the speed avoidance ranges. The SKIP BANDWIDTH is the width of the speed avoidance ranges.
If the commanded speed lies within the speed avoidance range, the drive output speed will not enter the range, it will settle at the boundary determined by the skip frequency and skip bandwidth parameter settings.
If the commanded speed lies on the opposite side of the speed avoidance range the output frequency will ramp thru the speed avoidance range to the value of the commanded frequency.
50 - TB-10B & TB-10D FUNCTION
This parameter selects the analog output signal at terminals 10B and 10D to be either frequency or load indicating and either 0-10VDC or 4-20 MA. This parameter determines the function of both 10B and 10D they are not independent. Set the parameter to the desired setting and wire to terminal 10B if a 0-10 VDC signal is desired or wire to 10D if a 4-20 MA signal is desired. The parameter can be set to one of four values:
0-10 V FREQ, 0-10 V LOAD, 4-20 MA FREQ, 4-20 MA LOAD.
The load at terminal 10D should be exactly 250 ohms. If the load cannot be set to 250 ohms, adding a series resistor or changing Parameter #52 (TB-10D Resistance Ohms) to the actual load resistance. Any load less than 250 ohms decreases the output signal resolution. This signal may not be used to drive signal powered
4 - 20 MA devices.
51 - FREQUENCY OUT AT MAXIMUM
This parameter scales the analog frequency indicating output signals at terminals 10B, 10D, or 10E (see
Parameters #50 and #53). Set the parameter value to the drive output frequency which is to correspond to maximum output level of the speed indicating signal (10VDC or 20 MA).
43
52 - TB-10D RESISTANCE OHMS
This parameter is used to select the output impedance of the 4-20 MA signal output from terminal 10D. The total resistance that is connected between terminal 2 and terminal 10D should equal 250 ohms. A series resistor can be added to accomplish this.When the resistance of the 4 - 20 MA device is less than 250 ohms, and a series resistor cannot be added, the actual measured resistance value needs to be entered to
Parameter #52, in order to have the proper scaling with the 4 - 20 MA output signal on terminal 10D.
53 - TB-10E FUNCTION
This parameter selects the analog output signal at terminal 10E to be either frequency indicating or load indicating and either 0-10VDC or 2-10VDC. The parameter can be set to one of five values: 0-10 V FREQ,
0-10 V LOAD, 2-10 V FREQ, 2-10 V LOAD, DISABLED.
A 4 - 20 MA signal can be derived from these signals by programming this parameter for 2 - 10 VDC, and adding a series resistor so that the total load resistance equals 500 ohms.
54 - LOAD OUT AT MAXIMUM
This parameter scales the analog load indicating output signals at terminals 10B, 10D, or 10E (see
Parameters #50 and #53). Set the parameter value to the load (%) output value which is to correspond to maximum output level of the load indicating signal (10VDC or 20 MA).
61 - MINIMUM FREQUENCY
The Minimum frequency determines the lowest output frequency (in Hertz) at which the drive will operate continuously. Note that the lowest speed at which a standard AC induction motor can produce torque is limited by the slip range, usually 3% of full speed. This means a standard motor will not produce full rated torque below 2 Hz. Note: units are always in HERTZ. The minimum frequency range is 0.0 Hz up to the MAXIMUM
FREQUENCY.
When the Minimum frequency is set to 0.0 HZ, the drive may be run in ZERO SPEED MODE (no frequency or voltage is outputted from the drive). ZERO SPEED operation is used with applications requiring the ability to start and stop the drive using only the selected speed control source.
NOTE: The drive must be initially started using any of the normal start commands.
62 - MAXIMUM FREQUENCY
The Maximum frequency determines the highest output frequency (in Hertz).
THE MAXIMUM FREQUENCY MUST BE SET LOW ENOUGH TO AVOID OVER SPEEDING
THE MOTOR AND OR DRIVEN EQUIPMENT. OVER SPEEDING THE MOTOR AND/OR
DRIVEN EQUIPMENT MAY RESULT IN DAMAGE TO EQUIPMENT AND INJURY TO
PERSONNEL! CONSULT MOTOR MANUFACTURER BEFORE OPERATING THE MOTOR
ABOVE ITS RATED SPEED!
64 - STABILITY
The STABILITY adjustment alters the drive output to compensate for differences in motor inductance, capacitance, and impedance. Certain motors may operate erratically under lightly loaded conditions. If motor operation is erratic at low load levels, adjusting the STABILITY setting to LOW COMP, MED COMP, or HIGH
COMP may give smoother operation.
44
65 - COAST TO STOP
VSD57 Series drives are shipped with the COAST TO STOP parameter in the ENABLED mode. When
ENABLED and a drive "STOP" command is given, the motor will behave as though the drive was instantaneously disconnected. If RAMP TO STOP operation is required ( COAST TO STOP parameter
DISABLED ).
Note: Dynamic braking may be needed to provide enough decelerating capacity to slow large inertia loads from higher speeds.
66 - FORWARD / REVERSE
This parameter is used to limit the motor rotation direction to forward or reverse, or to allow rotation in both directions. The parameter can be set to one of three values: FWD ONLY, REV ONLY, FWD + REV. FWD
ONLY and REV ONLY disable the FWD/REV key and corresponding drive terminals Forward (terminal 12B)
/ Reverse (terminal 12C), in the REMOTE mode. FWD + REV enables the FWD/REV key allowing the motor direction to be changed from the keypad (local mode) or terminals 12B and 12C (remote mode).
When FWD + REV is selected and the opposite direction is activated by the keypad (local mode) or the terminal strip (remote mode) to change the motor direction, the frequency will ramp down to zero speed at the decel rate and then ramp up to the set speed in the opposite direction.
Activate the forward direction in the remote mode by closing terminal 2 to 12B. Activate the reverse direction in the remote mode by closing terminal. In the local mode, activate different motor directions by first pressing the FWD/REV key and then pressing the ENTER key.
When placing the VSD57 Series models in the REMOTE mode, the appropriate direction contact must be closed in order for the drive to run.If neither or both contacts are closed, the drive will STOP if running, or will not START if stopped.
67 - AUTO / MANUAL SELECT
This parameter is used to limit function of AUTO/MAN key on the keypad. Possible settings are, AUTO
SPEED, MANUAL SPEED, AUTO / MANUAL LOCAL, or AUTO / MANUAL SPEED.
If set to MANUAL SPEED the drive’s speed reference will default to keypad control, when in the LOCAL
MODE, and the AUTO/MAN key is disabled.
If set to AUTO SPEED, the drive’s speed reference will default to whichever speed control method is activated by the terminal strip (see the Control Wiring Section), and the AUTO/MAN key is disabled.
Note: If no speed control method is activated by a terminal strip connection, the speed reference will default to keypad control even if this parameter is set AUTO SPEED.
If set to AUTO / MANUAL LOCAL, the AUTO/MAN key is active and control may be switched between the drive keypad, and the drive terminal strip, when in the LOCAL MODE only.
If set to AUTO / MANUAL SPEED, the AUTO/MAN key is active and control may be switched between the drive keypad, and the drive terminal strip in either the local or remote mode.
Note: If no speed control method is activated by a terminal strip connection, the speed reference will default to keypad control.
70 - AUTO START
This parameter is used to automatically start the drive upon application of input power. The drive must be wired for two wire start/stop control with a maintained start contact which is in the closed position. NOTE:
45
The drive output frequency will ramp up from zero (no speed search will be conducted) whenever this parameter is enabled.
In the local (keypad) or remote mode, terminal 1 and 12A must be closed to terminal 2 for this function to be active.
UNINTENDED EQUIPMENT ACTION
•
Automatic start can only be used for machines or installations that present no danger for personnel or equipment in the event of automatic restarting
•
Equipment operation must conform with national and local safety regulations
•
Failure to observe this precaution can result in equipment damage, severe personal injury, or death.
71 - RESTART ON FAULT
This parameter sets the drive to either restart after a fault or to remain tripped until it is reset by calling for a stop.
If restart is ENABLED and the drive trips, the drive will attempt to restart after a time delay set by RESTART
DELAY. If the drive is unable to restart, the drive will attempt additional restarts, each after a time delay. The number of attempted restarts is determined by the RESTART LIMIT.
The RESTART ON FAULT function is designed to restart into a coasting motor by conducting a speed search to catch the motor while it is still spinning, and then accelerate to the commanded speed.
Note: The drive can be set to conduct a speed search upon power up by setting Parameter #70 to DISABLED and Parameter #71 to ENABLED.
The speed search is conducted by first restarting the drive at MAXIMUM FREQUENCY at a reduced voltage.
The voltage is then increased and the motor current rises to a high level causing the drive to go into current limit
(based on the RESTART CURRENT LIMIT setting). The motor current rises to the current limit level because of the differential between the output frequency of the drive and the speed at which the motor is coasting. The drive output frequency then decelerates, at the RESTART DECEL rate, until the motor current drops below the current limit level (this occurs when the drive output frequency is matched to the motor speed). Once output frequency and motor speed are matched, the drive output frequency is accelerated returning the motor to the commanded speed. NOTE: The drive output frequency will ramp up from zero in the event of restart after a power outage (no speed search will be conducted) if Parameter #70, AUTO START, is enabled.
In the local (keypad) or remote mode, terminal 1 and 12A must be closed to terminal 2 for this function to be active.
UNINTENDED EQUIPMENT ACTION
•
Automatic restart can only be used for machines or installations that present no danger for personnel or equipment in the event of automatic restarting
•
Equipment operation must conform with national and local safety regulations
•
Failure to observe this precaution can result in equipment damage, severe personal injury, or death.
46
72 - RESTART LIMIT
The RESTART LIMIT determines the number of times the drive will attempt to restart after a trip. If unable to restart (fault condition persists) within the set number of attempts, the drive will display FAULT LOCKOUT and cease attempting to restart. The drive will not attempt to restart in the event of an E-stop trip or into a shorted motor without first being reset by opening the stop circuit (terminal 1 to terminal 2), or pressing the keypad stop key. This setting must be higher than the normal operating limit.
73 - RESTART DELAY
The RESTART DELAY is the time delay in between restart attempts. During this time delay the operator screen will display a warning, "WARNING! START PENDING". This parameter also determines the time period which must pass, after a fault, before the drive can be reset.
75 - RESTART DECEL
The RESTART DECEL sets the rate at which the drive lowers the output frequency during a restart speed search.
This parameter and the RESTART CURRENT LIMIT are set for a particular system by trial. The RESTART
DECEL time should be minimized to limit speed transients during the speed search. However, setting the value too low can result in high bus voltage tripping.
76 - RESTART CURRENT LIMIT
The RESTART CURRENT LIMIT determines the current limit value used during the auto restart on trip sequence.
The RESTART CURRENT LIMIT should be minimized to limit speed transients during the speed search.
However, setting the value too low can result in high bus voltage tripping. This setting must be higher than the operating current.
80 - DC BRAKE
DC injection braking provides shaft stopping torque by supplying low level DC voltage to the motor’s stator coils. DC braking can provide up to the motor’s full rated torque for short periods of time.
NO HOLDING TORQUE
•
DC injection braking does not provide holding torque at zero speed
•
DC injection braking does not function during loss of power or drive controller fault
•
When required, use separate brake function for holding torque
•
Failure to observe this precaution can result in equipment damage, severe personal injury, or death.
MOTOR OVERHEATING AND DAMAGE
•
Application of DC injection braking for long periods of time can cause motor overheating and damage. Protect motor from extended periods of DC injection braking.
47
This parameter sets the DC braking function to be either DISABLED or operational in a CONTINUOUS mode.
In the DISABLED mode, DC braking is not functional.
In the CONTINUOUS mode, DC braking energizes either when the output frequency decelerates to 0 HZ if
COAST TO STOP (Parameter #65) is DISABLED, after a short delay when a stop command is given if COAST
TO STOP (Parameter #65) is ENABLED, and remains energized until a start command is given.
In the ON START mode, DC braking energizes when a start is called for, and will remain energized until the time period determined by the START BRAKE setting (Parameter #84) has elapsed. The drive will automatically start once the START BRAKE setting time period elapses. During the START BRAKE time delay the operator screen will display START in the run status location on the drive keypad. Also, during this time, the START PENDING relay, or open collector output will energize if it has been selected.
In the ON STOP mode, DC braking energizes either when the output frequency reaches 0 HZ (COAST TO
STOP (Parameter #65) is DISABLED) or when a stop command is given (COAST TO STOP (Parameter
#65) is ENABLED), and remains energized until the time period determined by the STOP BRAKE (Parameter
#83) elapses, or until a start command is given. Executing a start command while the STOP BRAKE
(Parameter #83) is active, aborts the remaining stop time, and allows the drive to start immediately.
In the @ ZERO SPEED mode, DC braking energizes when the drive reaches zero speed (0.1HZ or less) and will remain energized until the time period determined by the STOP BRAKE (Parameter #83) has elapsed.
To avoid brake cycling due to noise, there is hysteresis incorporated to enable and disable the ZERO SPEED
BRAKE. Once active the ZERO SPEED brake will not re-enable until the command speed reaches 0.51HZ
or greater, or if the command speed goes above 0.50 HZ during an active brake, the brake time will be aborted, and the drive will start.
NOTE: ZERO SPEED operation requires MINIMUM FREQUENCY (Parameter #61) be set to 0 HZ, or the
ZERO SPEED function will not work. (See Parameter #61 for description of ZERO SPEED MODE).
In the START & STOP mode, DC braking energizes when a start or stop command is called for as described above for the individual ON START, and ON STOP modes.
In the @ ZERO & STOP mode, DC braking energizes when the drive reaches zero speed, or a stop is called for, and the drive has reached a stop condition as described under the individual ON STOP, and @ZERO
SPEED modes.
82 - DC BRAKE LOAD
This parameter sets the magnitude of the current applied to the motor by the DC braking circuit. This parameter is based on the drive’s nameplate current rating. DC BRAKE LOAD should be set to the lowest possible value which gives satisfactory operation in order to minimize motor heating.
83 - STOP BRAKE
This parameter determines the duration of time DC is applied to the motor when first coming to a stop, or with COAST TO STOP (Parameter # 65) ENABLED, shortly after the stop command. The STOP BRAKE
TIME should be set to the lowest possible value which gives satisfactory operation in order to minimize motor heating.
84 - START BRAKE
This parameter determines the duration of time DC is applied to the motor before a start operation, but after a start command. The START BRAKE TIME should be set to the lowest possible value which gives satisfactory operation in order to minimize motor heating.
48
86 - DYNAMIC BRAKING
This parameter enables the dynamic braking circuit. Set the parameter to enable only when the optional dynamic braking resistors are installed. See OPTIONS-DYNAMIC BRAKING.
90 - SPEED UNITS
SPEED UNITS sets the units of the output speed indication on the keypad display. This parameter can be set for a variety of different keypad display functions; HZ, RPM, %, /S, /M, /H, #/S, #/M, and #/H. NOTE: The intended use of "/S", "/M", "/H"; are units per second, units per minute, and units per hour.
91 - SPEED MULTIPLIER
The SPEED MULTIPLIER is a calibration constant for the output speed indication on the keypad display.
The speed multiplier is the constant which when multiplied by the frequency in Hertz, will give the desired displayed value. This parameter is used in conjunction with the SPEED UNITS (Parameter # 90) settings of
RPM, /S, /M, /H, #/S, #/M, and #/H. This parameter has no effect when the SPEED UNITS (Parameter #90), is set to HZ, or %.
92 - LOAD UNITS
LOAD UNITS sets the units of the output load indication on the keypad display.This parameter can be set to display %LOAD, or AMPS. When set to %LOAD, the load indication is configured to be a load percentage meter (this is the factory default).
93 - LOAD MULTIPLIER
The LOAD MULTIPLIER is a calibration constant for the output load indication on the keypad display. This parameter has no effect when the LOAD UNITS (Parameter #92) are set to %LOAD. Setting the LOAD UNITS to AMPS and the LOAD MULTIPLIER to the nameplate amp rating of the drive configures the load indicator as an ammeter.
94 - AC INPUT
This parameter is used to select the correct AC incoming voltage to the drive. With system input line voltages of either 200 / 208 VAC, set Parameter #94 to the 200 / 400 / 480 VAC selection. With system input line voltages of 230 / 240 VAC, 460 / 480 VAC (on 480 VAC rated drives), or 575 / 600 VAC, set Parameter #94 to the 240 / 480 / 590 setting.
95 - SPEED DECIMAL POINT
This parameter is used to move the decimal point location in the speed units display. Speed Units are selected by Parameter #90. This parameter is only active if the speed unit display functions in Parameter #90 are set to of the following values; /S, /M, /H, #/S, #/M, and #/H. This parameter will have no effect with the speed unit display if Parameter #90 is set to HZ, RPM, or %RPM.
100 - BASE FREQUENCY
The BASE FREQUENCY is the frequency at which the drive output reaches full voltage. For most applications the base frequency should be set to the motor’s rated frequency.
The BASE FREQUENCY determines the volts to hertz ratio. For example, if the drive is rated for 460 VAC and the BASE FREQUENCY is set to 60 HZ, and the V/HZ Curve Type (Parameter #101) is set to LINEAR-1.0, the drive will maintain a constant ratio of 7.66 V/HZ (except when AUTO V BOOST or MANUAL V BOOST are active).
49
101 - V/HZ CURVE TYPE
This parameter is used to change the relationship between the output voltage and frequency. Choices are;
LINEAR-1.0, VAR-TORQUE-1.3, VAR TORQUE-1.6, and VAR-TORQUE-2.0.
LINEAR-1.0 gives a linear relationship between voltage and frequency, V/HZ is a constant, yielding constant motor torque capability. The three VARIABLE TORQUE values (1.3, 1.6, 2.0) are used to gain optimum energy savings and reduce acoustical noise in variable torque applications such as pumps and fans. An infinite array of V/HZ patterns are available by adjusting the BASE FREQUENCY, V/HZ CURVE TYPE, and
MAXIMUM FREQUENCY.
104 - AUTO V BOOST
AUTO V BOOST supersedes the V/HZ setting determined by the BASE FREQUENCY and V/HZ CURVE
TYPE to increase output voltage during acceleration. In order to boost motor torque, the output voltage is increased in the amount of the AUTO V BOOST setting whenever the drive is accelerating. AUTO V BOOST is usually used in applications with high inertia loads where quick accelerations are desired.
105 - MANUAL V BOOST
The MANUAL V BOOST supersedes the V/HZ setting determined by the BASE FREQUENCY and V/HZ
CURVE TYPE and maintains a minimum voltage at lower frequency levels. MANUAL V BOOST is used in applications which require high starting torque. (e.g. conveyors, lifts and other loads which have high static friction or high inertia). MANUAL V BOOST varies with horsepower, SEE TABLE 3 for the MANUAL V BOOST value limit.
HORSEPOWER
1 HP
2 HP
3 HP
5 HP
7.5 HP
10 HP
15 HP
20 HP
25 HP
TABLE 3
MANUAL VOLTAGE BOOST FACTORY DEFAULT SETTINGS
HORSEPOWER FACTORY DEFAULT
5.3 %
4.4 %
30 HP
40 HP
4.0 %
3.5 %
50 HP
60 HP
3.2 %
3.0 %
75 HP
100 HP
2.7 %
2.6 %
125 HP
150 HP
2.5 %
200 HP
FACTORY DEFAULT
2.4 %
2.3 %
2.2 %
2.1 %
2.0 %
1.9 %
1.9 %
1.8 %
1.8 %
121, 122 - RELAY #1 FUNCTION, RELAY #2 FUNCTION
The control board has two auxiliary relays which can be programmed for a variety of functions; NO
FUNCTION, RUN, FAULT, FAULT LOCKOUT, AT SPEED, FOLLOWER PRESENT, START PENDING,
AUTO SPEED MODE, ABOVE SET SPEED, OR MAINTENANCE TARGET. - See the THEORY SECTION for relay descriptions.
Each relay has a set of FORM C contacts rated 2 amps at 28 VDC or 120 VAC. Control wiring diagrams show relays in the rest state (coils NOT energized).
50
123 - RELAY SET SPEED
This parameter sets the speed at which Relay #1 or #2 (above) will change state if either or both are programmed for the ABOVE SET SPEED function. If set in the ABOVE SET SPEED MODE, the relay energizes when the output frequency of the drive exceeds the value corresponding to the RELAY SET SPEED value and de-energizes when the output frequency returns to a value lower than the RELAY SET SPEED value. - See the THEORY SECTION for relay descriptions.
124 - TB - 14 FUNCTION
This parameter sets the function of the open collector output at terminal 14. This function can be set to a variety of functions; NO FUNCTION, RUN, FAULT, FAULT LOCKOUT, AT SPEED, CURRENT LIMIT,
FOLLOWER PRESENT, START PENDING, AUTO SPEED MODE. ABOVE SET SPEED, OR MAINTE-
NANCE TARGET. - See the THEORY SECTION for relay descriptions.
The open collector output at terminal 14 is a current sinking type, and is rated 24 VDC, 5 MA maximum.
NOTE - See the THEORY SECTION for relay descriptions.
130 - DRIVE POWER
This parameter is used to scale the kilwatt hour display. Enter the horsepower rating odf the drive (not the motor horsepower) as it appears on the drive data plate.
When this parameter is set to 0 the kilowatt hour display (see the Monitor Mode section) is disabled.
132 - MAINTENANCE TARGET
This parameter sets the time period, in hours, for the maintenance target alarm. The maintenance target alarm alerts the operator that a given amount of accumulated run time has passed. This can be used to indicate the need for maintenance on the driven equipment, or to time any other period dependent on motor run time.
After the time period set by this parameter has elapsed, a message is displayed indicating that the maintenance target has been reached. The message can be cleared by pressing any key to the keypad, but will be re-displayed each hour until a new maintenance target is set.
When this parameter is set to 0 the maintenance target display (see the MONITOR MODE SECTION) is disabled.
133 - DISPLAY FUNCTION
This parameter is used to set the drive keypad display to either a NORMAL display, or the ACTUAL SPEED
(alternate) display. See the OPERATING BY KEYPAD CONTROL section for pictorial view of both the
NORMAL and ACTUAL SPEED keypad displays.
The NORMAL display in the operating mode will display RUN STATUS, COMMANDED SPEED, SPEED
UNITS, LOAD %, LOAD UNITS, DIRECTION, and SPEED REFERENCE.
The ACTUAL SPEED display in the operating mode will display ACTUAL RUN SPEED, COMMANDED
SPEED, SPEED UNIT, LOAD %, CONTROL MODE, DIRECTION, and SPEED REFERENCE.
137 - CARRIER FREQUENCY SELECTION
This parameter determines permissible values of the carrier frequency. The carrier frequency is the switching rate of the output transistors. Higher switching rates causes less aubible noise to be emitted from the motor, but may cause the drive to run warmer. Set this parameter to the lowest value which gives acceptable sound levels, available carrier frequencies are: 1.5 kHZ, 8 kHZ, 10 kHZ, and 12 kHZ.
51
NOTE:The low carrier frequency is 1.5 kHZ up 25 HZ output frequency, and synchronized above 25 HZ. This carrier frequency is a fixed multiple of the drive output frequency.
Example: If the output frequency of the drive is set to 30 HZ, then the carrier frequency the drive is operating is 1800 HZ, (30 HZ x 60 = 1800 HZ).
The ability to operate a drive in the quiet (high carrier frequency) mode is dependent on the drive horsepower rating, driven load, drive enclosure, and the ambient temperature. Note the derating information in Section 7.
141 - FACTORY PARAMETERS
This parameter is used to reset the inverters customers usable parameters back to the factory default settings.
Setting the value to ENABLE will reset the inverter - the parameter value will immediately revert back to the
DISABLED setting.
142 - CLEAR HISTORY
This parameter is used to clear the PREVIOUS FAULTS (Parameter #200) history log. Setting the value to
ENABLE will clear the fault history log - the parameter value will immediately revert back to the DISABLED setting.
144 - SOFTWARE VERSION
This parameter displays the version number of the drive’s software. This information is useful if referring to the factory for programming or trouble shooting assistance. Since this value is a "view only" parameter, its value cannot be changed.
145 - SERIAL COMMUNICATIONS
This parameter is used with the serial communications feature. When using this feature, the inverter can communicate with a personal computer (PC), programmable logic controller (PLC), or other external device that utilizes RS-232, or RS-485 serial communications for control. The serial interface may be used to read present parameter settings (uploading to the control device), write new parameter settings (downloading from the control device), monitor present drive activity, and control current drive activity. These settings also allow use of the serial interface as a diagnostic tool.
This parameter selects the drive operations that are valid from an external control device over the serial link.
This parameter can be set to the following access levels: DISABLED, DETECT, MONITOR ONLY, PRO-
GRAM, CONTROL, PROGRAM & CONTROL. If the serial communications feature is not being used, leave this parameter set to the default setting of PROGRAM.
DISABLED -The serial port is inactive and will not respond to any requests from the external control device.
DETECT -The drive will only respond to requests for drive type identification, and software version level. This is provided to allow building a network map in an RS-485 network, and will allow the drive to be in an "OFF-LINE" mode, as far as serial communication is concerned.
MONITOR ONLY -In addition to drive type identification and software version, present drive status and the present drive parameter settings can be read. This function only allows reading information from the drive.
52
PROGRAM -The drive will accept updated parameter values from the external device.
Additionally, all MONITOR functions are available.
CONTROL -The drive will accept control commands from the external control device, and will not accept PROGRAM functions. Additionally, all MONITOR functions are available.
PROGRAM & CONTROL -All PROGRAM, CONTROL, and MONITOR functions are operable with this access level.
146 - SERIAL TIMEOUT
This parameter is used with the serial communications feature. The drive has an internal "Watchdog Timer" that is active when an external device has control of the drive via the serial interface, Parameter #145 is set to either CONTROL or PROGRAM & CONTROL, and an active control link is established. During an active control link there is control and handshake information that is passed back and forth between the control device and the drive. If the serial link is broken, for a time period exceeding the SERIAL TIMEOUT, the drive will automatically stop and return to local operation.
This parameter has an adjustable range from 0 to 30 Seconds. Setting this parameter to 0, disables the
"Watchdog Timer".
If the serial communications option is not being used, leave this parameter set to the default setting of 8
Seconds.
Though setting this parameter to 0 may be appropriate during setup,
CAUTION should be used, since a setting of 0 will allow the drive to operate via the serial link without a failsafe mechanism.
The SERIAL TIMEOUT function should always be enabled for normal serial link operation.
147 - SERIAL ADDRESS
This parameter is used with the serial communications feature, and is intended for use in a multiple drive network (RS-485). The serial link will support from 1 to 30 drives, each drive having an address in the range of 1 to 30. If the serial communications option is not being used, leave this parameter set to the default setting of 1.
148 - ENABLE PASSWORDS
This parameter sets the programming mode to be password protected when set to the ENABLED mode.
Password protection is based on a two level system. See the PARAMETER MENU for a listing of the password level for each parameter. Level one allows access to "low end" parameters which are changed more frequently. Level two allows access to all parameters which are user adjustable.
149 - LEVEL 1 PASSWORD
Level 1 - factory default value - 9100.
53
150 - LEVEL 2 PASSWORD
Level 2 - factory default value - 0019
198 - LANGUAGE
This parameter allows the language that is displayed on the drive keypad to be changed between ENGLISH and SPANISH. When the language is changed, the effect is immediate. French will be available in the near future.
The ability to change the language is also available to the operator without having to be in the program mode.
Pressing the STOP key and 0 key simultaneously, will bring up a message screen in opposite of the current default language. The selected language is the retained until changed through either Parameter #198, or by the STOP and 0 key combination.
200 - PREVIOUS FAULTS
This "parameter" stores a fault history of ten previous fault conditions. If any fault trips have occurred, the fault number and name will be stored here. View the previous faults by pressing ENTER and then scrolling through the previous faults with the UP and DOWN arrow keys. Possible values are shown in the table below.
DISPLAY
OUTPUT TRANSISTOR FAULT (1)
EMERGENCY STOP *
HIGH DC BUS
VOLTAGE
HIGH CONTROL
TEMPERATURE
CURRENT OVERLOAD
OUTPUT TRANSISTOR FAULT (2)
LOW DC BUS
VOLTAGE
START ERROR *
DC BRAKE FAULT
FAULT HISTORY DISPLAYS
DESCRIPTION (POSSIBLE CAUSE)
FAULT DETECTED AT OUTPUT TRANSISTOR -
PHASE TO PHASE OR PHASE TO GROUND
SHORT. DURING OPERATION
E-STOP CONNECTION (TERMINAL 2 TO TERMINAL 22 OPEN)
HIGH INPUT LINE VOLTAGE OR REGENERATING MOTOR
HIGH AMBIENT TEMPERATURE OR HIGH HEATSINK TEMPERATURE
HIGH MOTOR AMPERAGE DRAW (OVERLOADED MOTOR)
FAULT DETECTED AT OUTPUT TRANSISTOR - PHASE TO PHASE OR PHASE
TO GROUND SHORT.
AT START
LOW INPUT LINE VOLTAGE
INPUT POWER APPLIED WITH START CIRCUIT CLOSED
NO MOTOR CONNECTED WHEN DC BRAKE IS ACTIVATED
* Not in fault history - run time fault display only.
This parameter may be accessed without entering the password, from the operating mode, by pressing the
PROG/RUN key and then pressing ENTER.
54
22. Option - Dynamic braking
Dynamic braking principles:
When the frequency produced by the controller decreases rapidly, the motor behaves like an asynchronous generator and produces a braking torque. The motor feeds energy back to the drive controller. The amount of energey depends on the rate of deceleration, the inertia of the moving mass and the resistive torque.
Since the controller cannot feed the energy back into the supply, this causes an increase in the voltage of the filter capacitors, which limits the braking effect, potentially causing the controller to fault on overvoltage
"High CD Bus Voltage". Part of the braking energy is dissipated as losses in the motor, the corresponding corresponding braking torque varying from 10% to 35% of the rated motor torque.
Dynamic braking allows a higher braking torque to be obtained and ensures dissipation of part of the braking energy in an external resistor. Dynamic braking consists of the following major components:
•
Power transistor that switches the braking resistor across the filter capacitor terminals (Included in the controller)
•
Control electronics (Included in the controller)
•
Separately-mounted braking resistor.
The braking resistor is available from 3 HP up to 15 HP at 208 & 460 V and 20 HP at 575 V. There is no dynamic braking available as a standard for the 1 HP, 2 HP and above 20 HP models.
HAZARDOUS VOLTAGE
•
DB module power and control terminals are at line potential.
•
Ground equipment using screw provided.
•
Disconnect all power before servicing DB module.
•
Highvoltage remains after power is removed.
•
Bus capacitors do not discharge immediately
Before servicing:
•
WAIT TEN MINUTES.
•
Measure bus capacitor voltage between + and - terminals of controller to verify DC voltage is zero.
•
DO NOT short across capacitor terminals with voltage present.
•
Install all covers before applying power to DB module.
•
Use insulating tool.
•
External devices connected to DB module must be insulated for line voltage with respect to ground.
Falure to observe these precautions will cause shock or burn, resulting in severe personal injury or death!
55
Available braking torque:
Continuous braking (hold back) of 100% 9OR RATED MOTOR TORQUE) AT OUTPUT FREQUENCIES UP
TO 15 hz (25% OF THE MOTOR BASE SPEED), OR 50% AT OUTPUT FREQUENCIES UP TO 30hz (50%
OF THE MOTOR BASE SPEED ), OR 25% OF OUTPUT FREQUENCIES UP YO ^0 hz (100% MOTOR
BASE SPEED) IS POSSIBLE.
Intermittent (once per minute) braking (hold back) at 180% of the motor torque rated torque is possible for thirty seconds at the output frequencies up to 15 HZ (25% of motor base speed), fifteen seconds at output frequencies up to 30 HZ (50% of the motor base speed), or seven seconds at output frequencies up to 60HZ
(100% of the motor base speed).
The braking resistor value is not recommended for continuous cycling applications which require stopping loads greater than twice that of the motor or from 1800 rpm, more than eight (8) times, from 2500 rpm more than four (4) times, or from 3600 rpm mre than (2) times, within a one minute period.
The braking resistor is available for use with the VSD 57 series variable speed drive as a separately mounted option. The braking resistor option should be located as close to the drive as possible. Care should be taken to insure adequate ventilation.
OVERSPEED HAZARD.
•
Generation of braking torque throughout the operating speed range of the controller rquires dynamic braking be present and operating.
•
Dynamic braking resistor must be selected to generate required torque.
Failure to observe these precautions can result in severe personal injury, product damage
NO HOLDING TORQUE.
•
Dynamic braking does not provide torque at zero speed.
•
Dynamic braking does not function during loss of power or controller fault.
•
When required, use separate braking function for holding torque.
Failure to observe these precautions can result in severe personal injury, product damage or property dam or property damage
56
Installing a braking resistor kit:
HAZARDOUS VOLTAGE AND HOT COMPONENTS
Avoid accidental contact with braking resistor. Resistor operating voltage may reach 1000 VDC between terminals and its temperature may reach 752 °F (400 °C).
•
Install resistors in appropriate enclosures or restricted area.
•
Provide sufficient coling air clearance
•
Do not mount on or enclose with combustible materials.
•
Use conductors rated for expected voltage and temperature.
Failure to observe these precautions may cause shock or burn, resulting in severe personal injury or death!
When mounting the resistor and associated cables, observe the following precautions:
•
Braking Resistors must be sized and supplied by Schneider Canada.
•
Two conductors from he breaking resistor need to be connected to the drive board. These two (2) wires should be run through a piece of rigid metal conduit, and connect to terminas DB1 and DB2 on the power board (see connecrtion diagram).
•
When connecting the braking resistor to the drive controller, use conductors whose temperature and voltage ratings are suitable for the application. The conductor insiulation voltage rating must meet or excede the input line voltage rating. The conductor insulation temperature rating must be 194 °F (90 °C) or greater
•
Parameter # 86 (Dynamic Brake) needs to be programmed to ENABLED if the dynamic brake assembly is installed
•
Sufficient space and air pflow must be provided to allow for dissipation of heat produced by braking action, maintain at leat 2 inches between the resistor element and any surface. Do not mount the resistor to the combustible surfaces or house the resistor in a combustible enclosure.
57
Braking Resistor:
For VSD57 Total Wattage Total Ohmic
Value
Catalog Nbr Dimensions
H*W*D
Cabling: recommended section
At 230 V
VSD57CU41M2-
VSD57CU72M2-
VSD57CU90M2-
VSD57CD12M2-
VSD57CD16M2-
At 460 V
VSD57CU41N4-
VSD57CU72N4-
VSD57CU90N4-
VSD57CD12N4-
VSD57CD16N4-
At 575 V
VSD57CU41S6-
VSD57CU72S6-
VSD57CU90S6-
VSD57CD12S6-
VSD57CD16S6
VSD57CD23S6
350
700
1050
1200
1800
1800
350
700
1050
1600
2400
350
700
1050
1600
2400
360
180
120
90
60
56
240
120
80
56
37.33
60
30
20
14
9.33
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
C.F.
AWG 14
AWG 12
AWG12
AWG12
AWG10
AWG14
AWG12
AWG12
AWG12
AWG10
AWG14
AWG12
AWG12
AWG12
AWG10
AWG10
58
Customer connection diagram for external resistor:
59
23. PARAMETER MENU INDEX / USER SETTINGS
ITEM
NO.
PARAMETER MENU
NOTE: STANDARD DRIVES ARE SHIPPED AT DEFAULT SETTINGS
PARAMETER
NAME
VALUE LIMIT OR
MENU CHOICE
DEFAULT
SETTING
1
2
CURRENT LIMIT
THERMAL OVERLOAD
5 - 120 % (for V.T.)
- 180% (for C.T.)
50 - 120 % (for V.T.)
- 180% (for C.T.)
3
4
SLIP COMPENSATION
SPEED @ 4 MA / 0 VDC
5
SPEED @ 20 MA / 10 VDC
9
PRESET ACC / DEC
11-13
SPEED PRESETS #1- #3
14-17
SPEED PRESETS #4- #7
19
JOG SPEED
20
NORMAL ACCEL
21-27
PRESET #1 - #7 ACCEL
29
30
JOG ACCEL
NORMAL DECEL
31-37
PRESET #1 - #7 DECEL
TAPER DECEL
38
39
JOG DECEL
41
42
SKIP SPEED #1
SKIP SPEED #2
43
SKIP SPEED #3
44
50
0 - 5.0 %
0.00 - 360.00 HZ
0.00 - 360.00 HZ
DISABLED, ENABLED
0.00 - 120.00 HZ
0.00 - 120.00 HZ
0.00 - 120.00 HZ
SEE TABLE 19-1
SEE TABLE 19-1
SEE TABLE 19-1
SEE TABLE 19-2
SEE TABLE 19-2
DISABLED, ENABLED
SEE TABLE 19-2
0.00 - 120.00 HZ
0.00 - 120.00 HZ
0.00 - 120.00 HZ
SKIP BANDWIDTH 0.00 - 10.00 HZ
TB-10B / D FUNCTION 0-10 V FREQ, 0-10 V LOAD,
4-20 MA FREQ,
4-20 MA LOAD
120 %(for V.T.) -
180% (for C.T.)
120 % (for V.T.) -
180% (for C.T.)
0.0 %
0.00 HZ
60.00 HZ
DISABLED
10.00 HZ
10.00 HZ
10.00 HZ
30.0 SEC
30.0 SEC
30.0 SEC
30.0 SEC
30.0 SEC
DISABLED
30.0 SEC
0.00 HZ
0.00 HZ
0.00 HZ
2.00 HZ
0-10V FREQ
54
61
62
64
51
FREQUENCY OUT
@ MAXIMUM
1.00 - 360.00 HZ
52
TB-10D RESISTANCE OHM
53
TB-10E FUNCTION
0 - 250
0 -10 V FREQ, 0-10 V
LOAD,
2-10 V FREQ, 2-10 V LOAD
LOAD OUT AT MAXIMUM
MINIMUM FREQUENCY
MAXIMUM FREQUENCY
STABILITY
10 - 200 %
0.00 - 120.00 HZ
0.00 - 120.00 HZ
65
66
67
COAST TO STOP
FORWARD / REVERSE
AUTO / MANUAL SEL
NORMAL, LOW,
MED, HIGH
ENABLED,
DISABLED
FWD ONLY, REV ONLY,
FWD + REV
AUTO SPEED,
MANUAL SPEED,
AUTO / MANUAL SPEED,
AUTO / MANUAL LOCAL
60.00 HZ
250
0-10V LOAD
125 %
0.50 HZ
60.00 HZ
NORMAL
ENABLED (for V.T.)
DISABLED (for C.T.)
FWD ONLY
AUTO /
MANUAL
SPEED
PASSWORD
LEVEL
2
2
2
2
2
2
2
41
42
41
41
37
37
38
39
39
39
39
38
38
38
37
38
38
37
37
37
40
40
40
40
40
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
SEE
PAGE
USER
SETTING
40
40
40
40
41
60
ITEM
NO.
70
71
72
73
75
76
80
82
83
84
86
90
91
92
93
94
95
100
101
104
105
121
122
123
124
130
132
133
PARAMETER MENU
NOTE: STANDARD DRIVES ARE SHIPPED AT DEFAULT SETTINGS
PARAMETER
NAME
VALUE LIMIT OR
MENU CHOICE
DEFAULT
SETTING
PASSWORD
LEVEL
SEE
PAGE
USER
SETTING
AUTO START
RESTART ON FAULT
RESTART LIMIT
RESTART DELAY
RESTART DECEL
RESTART
CURRENT LIMIT
DC BRAKE
DISABLED, ENABLED
DISABLED, ENABLED
1 - 5
1.0 - 180.0 SEC
0.1 - 999.9 SEC
10 - 180 %
DISABLED
DISABLED
3
5.0 SEC
10.0 SEC
100 %
DC BRAKE LOAD
STOP BRAKE
START BRAKE
DYNAMIC BRAKING
SPEED UNITS
SPEED MULTIPLIER
LOAD UNITS
LOAD MULTIPLIER
AC INPUT
SPEED DP
BASE FREQUENCY
V/HZ CURVE TYPE
AUTO V BOOST
MANUAL V BOOST
RELAY #1 FUNCTION
RELAY #2 FUNCTION
RELAY SET SPEED
TB-14 FUNCTION
DRIVE POWER
MAINTENANCE TARGET
DISPLAY FUNCTION
DISABLED, CONTINUOUS
ON START, ON STOP,
@ ZERO SPEED,
START & STOP,
ZERO SPEED & STOP
20 - 180 %
0.1 - 60.0 SEC
0.1 - 20.0 SEC
DISABLED, ENABLED
HZ, RPM, % RPM, /S, /M,
/H, #/S, #/M, #/H
0.10 - 400.00
% LOAD, AMPS
0.01 - 300.00
240 / 480 / 590
200 / 400 / 480
XXXXX, XXXX.X, XXX.XX,
XX.XXX, X.XXXX, .XXXXX
10.00 - 360.00 HZ
LINEAR - 1.0,
VAR TORQUE - 1.3,
VAR TORQUE - 1.6,
VAR TORQUE - 2.0
0.0 - 20.0 %
0.0 - 30.0 %
NO FUNCTION, RUN,
FAULT, FAULT LOCKOUT,
AT SPEED,
CURRENT LIMIT,
FOLLOWER PRESENT,
AUTO SPEED MODE,
START PENDING,
ABOVE SET SPEED,
MAINTENANCE TARGET
SAME AS RELAY #1
0.00 - 120.00 HZ
SAME AS RELAY #1
0 - 200 (for V.T.)
- 0 - 150 (for C.T.)
0 - 65,000 HR
NORMAL,
ACTUAL SPEED
DISABLED
30 %
5.0 SEC
5.0 SEC
DISABLED
HZ
30.00
% LOAD
1.00
240 / 480 / 590
XXXXX
60.00 HZ
VAR TORQUE -1.6
LINEAR 1.0 (for C.T.)
0.0 %
SEE TABLE 19-3
RUN
FAULT
0.50 HZ
NO
FUNCTION
0
0 HR
NORMAL
61
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
47
48
48
47
47
47
42
43
43
43
44
44
44
48
48
45
45
45
45
46
46
46
46
46
46
46
47
ITEM
NO.
PARAMETER MENU
NOTE: STANDARD DRIVES ARE SHIPPED AT DEFAULT SETTINGS
PARAMETER
NAME
VALUE LIMIT OR
MENU CHOICE
141
142
144
145
137
146
147
148
149
150
198
200
CARRIER FREQUENCY
SELECTION
FACTORY PARAMETERS
CLEAR HISTORY
SOFTWARE VERSION
SERIAL
COMMUNICATIONS
SERIAL TIMEOUT
SERIAL ADDRESS
ENABLE PASSWORDS
LEVEL 1 PASSWORD
LEVEL 2 PASSWORD
LANGUAGE
PREVIOUS FAULT
1.5 kHZ, 8 kHZ,
10 kHZ, 12 kHZ,
DISABLED, ENABLED
DISABLED, ENABLED
213-020X
DISABLED, DETECT,
MONITOR ONLY,
PROGRAM, CONTROL,
PROGRAM & CONTROL
0 - 30 SEC
1 - 30
DISABLED, ENABLED
0000 - 9999
0000 - 9999
ENGLISH, SPANISH
THIS "PARAMETER" IS
FOR VIEWING ONLY
DEFAULT
SETTING
1.5 kHZ
DISABLED
DISABLED
213-020X
PROGRAM
8 SEC
1
ENABLED
9100
0019
ENGLISH
N/A
PASSWORD
LEVEL
2
2
2
2
2
2
2
2
2
0
2
2
SEE
PAGE
USER
SETTING
49
49
49
49
49
50
50
50
50
50
51
51
62
advertisement
Key Features
- Microprocessor-based control
- Keypad programmable
- Variable speed operation
- Constant torque and variable torque applications
- Comprehensive protection features
- Adjustable carrier frequency
- Multiple input and output signals
- Serial communications port
- Configurable auxiliary contacts
Frequently Answers and Questions
What type of applications is the VSD 57 suitable for?
What is the voltage range of the VSD 57?
How do I program the VSD 57?
What types of input signals are accepted by the VSD 57?
What types of output signals are available from the VSD 57?
What are the protection features of the VSD 57?
Related manuals
advertisement
Table of contents
- 5 Product Changes
- 5 Warranty
- 5 Receiving
- 5 Customer Modification
- 6 Theory
- 6 Description of AC Motor Operation
- 7 Drive Function Description
- 10 Design Specifications
- 11 Designation Code
- 12 Dimensional Data Variable Torque Series
- 14 Dimensional Data Constant Torque Series
- 18 Drive Ratings - 208/240V Model
- 20 Drive Ratings - 480V Model
- 22 Drive Ratings - 575V Model
- 24 10. Installation
- 25 Voltage
- 25 KVA ratings
- 25 Input Fusing and Disconnect requirements
- 26 12 Voltage Selection
- 27 General wiring practices
- 27 Input wiring precautions
- 28 Output wiring precautions
- 29 Grounding
- 30 Power wiring diagram
- 31 14. Control Wiring
- 34 15. Control Wiring Diagram
- 35 16. Initial Power Up
- 36 17. Operating by Keypad Control
- 38 18. Monitor Mode
- 39 19. Programming - Configuration
- 41 20. Programmable Parameter Menu
- 44 21. Description of Parameters
- 59 22. Option: Dynamic braking
- 64 23. Parameter Menu Index / User Settings