Product sheet (PDF/204 kB)
Grid measurement module
GMP232/x Grid measurement and
protection module
The GMP232/x module enables the safe, reliable
and fast measuring of all relevant values for threephase electrical networks. It also provides a number
of monitoring functions for generator and grid
protection. Up to two circuit-breakers/trip circuits are
triggered by the module directly via relay outputs.
The continuous monitoring of grid harmonics up to
the 50th harmonic can be used for direct responses
as well as for evaluating the power quality.
Item
1 A
5 A
GMP232/1
00025962-00
GMP232/1 CC
00025966-00
GMP232/3
00025964-00
GMP232/3 CC
00025968-00
e
r
690 V
1 A
5 A
GMP232/2
p
00025961-00
GMP232/2 CC
00025965-00
GMP232/4
00025963-00
GMP232/4 CC
In preparation:
00025967-00
a
n
The module is provided with an integrated real-time
data recorder for the high-precision recording of up
to 24 measuring channels during alarm/protection
events. Error events are recorded continuously and
stored permanently with a high resolution time
entry. The internal time base of the module can
be synchronized to an external time source (e.g.
IEEE 1588 Precision Time Protocol), which supports
the analysis of the data from spatially separated
measurement and protection devices.
i
m
i
l
Item no.
120 V
y
r
The GMP232/x is fully integrated in the Bachmann
SolutionCenter. Configurations can be created simply
and stored for later reuse. Both the measured
channel values and also the derived values are made
available directly in the user interface. Commissioning
and fault analysis are simplified with tabular, vector
and time sequence displays. Event logs and recorded
time sequences can be exported in CSV or COMTRADE
format. The integrated simulation function simplifies
the configuration of protection and monitoring
functions.
•Measurement of current, voltage, frequency, power,
power factor, phase angle
• True RMS and fundamental RMS, symmetrical
components
•Measurement of grid harmonics up to the 50th
(power quality)
•Monitoring functions for grid and generator
protection
•Direct relay outputs for circuit-breaker/trip circuits
•Integrated real-time data recorder
•Integrated event logging
•4Q energy counter
•Measured value simulation
•Integrated average value
7
System Overview • Bachmann electronic GmbH • 02/2016 • Specification subject to change –
the product’s characteristics are exclusively governed by the data of the respective user manual.
Grid measurement module
GMP232 – Grid measurement
Current/voltage measurement
Measuring method
• True RMS (incl. harmonics up to 3 kHz)
• Fundamental RMS (only fundamental)
• Symmetrical components
Sampling rate
Network frequency-independent, approx. 100 µs (10 kHz)
Measurement interval (RMS values)
Phase synchronized with each
zero crossing (T/6)
50 Hz: 3.3 ms
60 Hz: 2.7 ms
Individual sampling values
Intervals that can be called via function calls in the user application:
100 µs, 200 µs, 400 µs, 800 µs, 1.6 ms (via block access)
floating:
50 Hz: 0.1 ms
60 Hz: 0.1 ms
y
r
Voltage measurement
Type
1, 3
Number
3
Rated voltage
UL-L, RMS: 120 Vrms
UL-N, RMS: 70 Vrms
Voltage measuring range
UL-L, RMS: 3.6 to 340 Vrms
UL-N, RMS: 2 to 196 Vrms
Accuracy*
±0.1 % in relation to URated
Short-term overload
(10x1 s, interval 10 s)
Input impedance
2, 4
UL-L, RMS: 1035 Vrms
Current measurement
Type
1, 2
e
r
3
UL-L, RMS: 690 Vrms
UL-N, RMS: 400 Vrms
i
m
i
l
> 2 MΩ
Number
a
n
3
UL-L, RMS: 17.3 to 1173 Vrms
UL-N, RMS: 10 to 677 Vrms
±0.1 % in relation to URated
UL-L, RMS: 1385 Vrms
> 2 MΩ
3, 4
3
Current transformer rated current
1 Arms
5 Arms
Current measuring range
2 mArms to 4 Arms
10 mArms to 15 Arms
≤ ±0.1 % in relation to URated
≤ ±0.1 % in relation to URated
Accuracy*
p
Short-term overload (10x1 s, interval 100 s)
50 Arms
100 Arms
Load
10 mVA
250 mVA
Frequency measurement
Rated frequency
Measuring range
50/60 Hz
10 to 75 Hz
Measured variables
Frequenzy (f), frequenzy with suppression of dynamic events (f2),
mean frequency over definable duration or number (fAVG)
Accuracy*
≤ ±0.001 Hz
Measurement interval
Refresh with every zero voltage crossing (T/12) (string voltage and
line-to-line voltage), if no voltage present, the current is used for the
calculation
1-conductor system:
50 Hz: 10 ms
60 Hz: 8.3 ms
3-conductor system:
50 Hz: 1.667 ms
60 Hz: 1.389 ms
Frequency change measurement
ROCOF
Up to 10 Hz/s
* Accuracy values as a percentage of the nominal value at 25 °C and under reference conditions
8
System Overview • Bachmann electronic GmbH • 02/2016 • Specification subject to change –
the product’s characteristics are exclusively governed by the data of the respective user manual.
Grid measurement module
GMP232 – Grid measurement
Power measurement – active, reactive and apparent power
Measured values
P, Q, S per phase and as total
Calculation methods
DIN 40110-2 (incl. harmonics up to 3 kHz),
IEC 61400-21 (only fundamental)
Measurement interval
Phase synchronized with each
zero crossing (T/6)
50 Hz: 3.3 ms
60 Hz: 2.7 ms
floating:
50 Hz: 0.1 ms
60 Hz: 0.1 ms
y
r
Energy count
Number
2 (separate measuring for TRMS and FRMS)
Resolution
1 Ws
Active energy
Supplied (positive), drawn (negative)
Reactive energy
Inductive (positive), capacitive (negative)
Type of memory
Nonvolatile (on the module)
Measurement interval
Refresh at every voltage zero crossing
i
1-conductor system:
50 Hz: 10 ms
60 Hz: 8.3 ms
m
i
l
Power quality
Parameter harmonics
p
Calculation method
Measurement interval
3-conductor system:
50 Hz: 3.3 ms
60 Hz: 2.8 ms
Total harmonic distortion (THD) and Total demand distortion (TDD)
for current and voltage per phase, reference set to nominal value or
fundamental harmonic
e
r
Voltage harmonics
Current harmonics
a
n
Amplitudes of harmonics up to 50th harmonic per phase
Amplitudes of harmonics up to 50th harmonic per phase
EN 61000-4-7
50 Hz: Calculation over 10 periods
60 Hz: Calculation over 12 periods
Digital relay outputs
Number/type
2 changeover contacts
Signal rated voltages
230 VAC, 48 VDC, 24 VDC (not mixed)
Output current max.
Nominal
Nominal
Nominal
Nominal
Status display (LED)
Green
0.5
0.5
1A
2A
A at +24 VDC, DC-13
A at +24 VDC, resistive load
at 230 VAC, AC-15
at 230 VAC, resistive load
* Precision values as a percentage of the nominal value at 25 °C and under reference conditions
9
System Overview • Bachmann electronic GmbH • 02/2016 • Specification subject to change –
the product’s characteristics are exclusively governed by the data of the respective user manual.
Grid measurement module
GMP232 – Monitoring functions
General
Delay
0 to 600 s configurable for time-independent monitoring function
Action
Configurable: generating an alarm, triggering of relais 1, relais 2 or
both, Trigger for real-time data recorder (fault recorder)
Triggering and suggestion are logged as an event and can be read or
viewed.
Time-independent overcurrent protection (ANSI 50TD)
Resolution
0.1 % of IRated
Protection elements
I>; I>>; I>>>
y
r
Directional overcurrent protection (ANSI 67)
Description
Directional monitoring of IactIN, with which the sign depends on the
direction of active power.
Protection elements
I Dir >; I Dir >>
Unbalanced load / current asymmetry monitoring (ANSI 46)
Description
i
a
n
EN 50160: Asymmetry is defined as the ratio of negative sequence
components to positive sequence components. The reference value is
the current basic oscillation component.
m
i
l
Undervoltage/overvoltage protection (ANSI 27/59)
Input variable
Phase voltage (ULN) or mesh voltage (ULL)
e
r
Protection elements
U<; U<<; U<<<
U>; U>>; U>>>
Time-dependent undervoltage/overvoltage protection (VFRT)
Description
p
Time-dependent voltage monitoring is triggered if one of the three
phase voltages falls below or above a curve U(t) configured via
interpolation points. Up to 10 time/voltage pairs are available to
calculate a grid-code dependent limit curve.
Four separate protection functions can be used with different
parameter sets. (LVRT, HVRT)
Voltage asymmetry monitoring (ANSI 47)
Description
EN 50160: Asymmetry is defined as the ratio of negative sequence
components to positive sequence components. The reference value is
the actual fundamental component.
10
System Overview • Bachmann electronic GmbH • 02/2016 • Specification subject to change –
the product’s characteristics are exclusively governed by the data of the respective user manual.
Grid measurement module
GMP232 – Monitoring functions
Frequency protection (ANSI 81 U/O)
Protection elements
f<; f<<; f<<<
f>; f>>; f>>>
Input variable
Frequenzy (f) or frequenzy with phase shift suppression (f2)
Configuration option
Blockage at undervoltage/overvoltage
Change of frequency protection ROCOF (Rate of change of frequency) (ANSI 81 R)
Input variable
Frequenzy (f) or frequenzy with phase shift suppression (f2)
Configuration option
Calculation dialog for ROCOF with relation to duration or number
y
r
Phase shift monitoring (VectorJump) (ANSI 78)
Description
Monitoring of sudden phase shifts for detection of sudden load
changes or islanding.
a
n
Time-dependent frequency monitoring – FRT (Fault Ride Through)
Description
Time-dependent frequency monitoring is triggered if the frequency
falls below or above a curve f(t) configured via interpolation points.
Up to 10 time/frequency pairs are available to calculate a grid-code
dependent limit curve.
Two separate protection functions can be used with different
parameter sets.
i
m
i
l
Power quality monitoring – PQM
e
r
Description
Monitors voltage and current harmonics up to the 50th harmonic.
Trips if one of the pre-defined limits is exceeded (evaluation per
phase).
Protection elements
p
THD
TDD
H2 bis H50
H2 bis H50
Total harmonic distortion
Total demand distortion
Individual amplitudes of voltage harmonics
Individual amplitudes of current harmonics
Forward power protection (ANSI 32)
Description
Protection elements
Protective tripping on exceeding a 3-phase maximum active power
according to IEC 61400-21, i.e. fundamental positive sequence
power
P>; P>>
Reverse power protection (ANSI 32R)
Description
Directional monitoring of Pact/PN. Monitoring can be implemented
either in all 3 phases together (Ptotal) or in one of any of the
3 phases.
Protection elements
P Dir >; P Dir >>
Undervoltage reactive power protection Q(U)
Description
Voltage dependent directional reactive power protection. Used to
support the voltage during grid faults. Trips if all three evaluated
voltages are below a certain limit (e.g. 0.85 URated) and inductive
reactive power is drawn from the power supply grid.
Two separate protection functions can be used with different
parameter sets.
11
System Overview • Bachmann electronic GmbH • 02/2016 • Specification subject to change –
the product’s characteristics are exclusively governed by the data of the respective user manual.
Grid measurement module
GMP232 – Monitoring functions
Time synchronization
Basic principle
The GMP module is synchronized automatically with the real-time
clock of the PLC-CPU. This can be time synchronized via the network.
Physical medium
Ethernet (CPU)
Protocols
Precision Time Protocol (PTP – IEEE 1588)
SNTP (Simple Network Time Protocol)
Event logging with real-time stamp – SER (sequence of events recorder)
Description
Monitoring events (configured alarm/protection functions) are stored
with a precise time reference when they occur.
Type of memory
nonvolatile (on the module)
Size
2048 entries
y
r
Real-time data recorder / digital fault recorder – DFR
Description
A high resolution time sequence recording can be started
automatically when a monitoring function is triggered.
Number of channels
24 channels (measured values, digital I/O, calculated values)
Memory depth per channel
61440 sampling values (6 s at approx. 100 µs sampling rate)
Recording time
6, 12, 24, 48, 96 seconds
Pre-trigger
Yes
Input variable
i
m
i
l
Average value
a
n
Average value 1 and 2: effective value of current and voltage,
frequenzy, angle, powers, power factors, symmetrical components,
THD, TDD
Average value 3: Harmonic of the current and voltage
e
r
Configuration option
p
Average value 1: Update 0.2 to 60 s
Average value 2: Update 60 s to 15 min
Average value 3: Update 3 s to 15 min
12
System Overview • Bachmann electronic GmbH • 02/2016 • Specification subject to change –
the product’s characteristics are exclusively governed by the data of the respective user manual.
Grid measurement module
GMP232 – Module properties
Electrical safety
Product standard
IEC/EN 61131-2
Generic standard
IEC/EN 60664-1
Pollution degree
2
Overvoltage category
III
Test surge voltage
6 kV
Protection class
2
y
r
Approvals / certificates
General
CE, UL/cUL, CCC
Medium voltage directive
In preparation: BDEW:2008, FGW TR3:2011 (Rev. 22), FGW
TR8:2011 (Rev. 5)
Marine
In preparation: GL, DNV, LR, ABS, BV
Others
In preparation: ENA ER G59/3:2013, IEEE Std. C37.90:2005
Standard
Operating temperature
m
i
l
Rel. air humidity, operation
e
r
Maximum operating height
Power supply
Via backplane
p
External on the module
System requirements
Hardware
Software
ColdClimate ( )
-30 to +60 °C
5 to 95 % no condensation
Storage temperature
Rel. air humidity, storage
a
n
i
Ambient conditions
5 to 95 % with condensation
-40 to +85 °C
5 to 95% with temporary
condensation
5 to 95 % with condensation
2,000 m above sea level (operation up to 4,500 m on request)
+5 V | ≤ 260 mA, +15 V | ≤ 20 mA, -15 V | ≤ 16 mA
24 V | ≤ 87 mA
All M1 CPU families apart from ME203, SK1 backplane not required
M-Base 4.00 or higher
13
System Overview • Bachmann electronic GmbH • 02/2016 • Specification subject to change –
the product’s characteristics are exclusively governed by the data of the respective user manual.
Grid measurement module
Order codes
Item
Item no.
Description
GMP232/1
00025962-00
Grid measurement and monitoring module; 3x Un 120 V, 3x In
1 A; 2x Out relay 24/48 VDC, 230 VAC; U, I, P, Q, f measurement;
4Q energy metering, integrated monitoring/protection functions,
harmonics analysis, integrated real-time data recorder
(24 channels); Event logging with real-time stamp
GMP232/1 CC
00025966-00
Like GMP232/1; ColdClimate ( )
GMP232/2
00025961-00
Grid measurement and monitoring module; 3x Un 690 V, 3x In
1A; 2x Out relay 24/48 VDC, 230 VAC; U, I, P, Q, f measurement;
4Q energy metering, integrated monitoring/protection functions,
harmonics analysis, integrated real-time data recorder
(24 channels); Event logging with real-time stamp
GMP232/2 CC
00025965-00
Like GMP232/2; ColdClimate ( )
GMP232/3
00025964-00
Grid measurement and monitoring module; 3x Un 120 V, 3x In
5 A; 2x Out relay 24/48 VDC, 230 VAC; U, I, P, Q, f measurement;
4Q energy metering, integrated monitoring/protection functions,
harmonics analysis, integrated real-time data recorder
(24 channels); Event logging with real-time stamp
GMP232/3 CC
00025968-00
Like GMP232/3; ColdClimate ( )
GMP232/4
00025963-00
Grid measurement and monitoring module; 3x Un 690 V, 3x In
5 A; 2x Out relay 24/48 VDC, 230 VAC; U, I, P, Q, f measurement;
4Q energy metering, integrated monitoring/protection functions,
harmonics analysis, integrated real-time data recorder
(24 channels); Event logging with real-time stamp
GMP232/4 CC
00025967-00
Like GMP232/4; ColdClimate ( )
e
r
p
Accessories for GMP232/x
a
n
i
m
i
l
y
r
Item
Item no.
SS-GMP232/x B
00027474-00
Description
Terminal set Phoenix screw side (1x SS 51/03; 1x SS 51/06; 1x SS
76/06; 1x SS 76/06 inv) with labeling strips
14
System Overview • Bachmann electronic GmbH • 02/2016 • Specification subject to change –