NS-Series Programmable Terminals HOST CONNECTION MANUAL

Cat. No. V085-E1-07
NS-Series
NS15-TX01[]-V2
NS12-TS0[](B)-V1/V2
NS10-TV0[](B)-V1/V2
NS8-TV0[](B)-V1/V2
NS8-TV1[](B)-V1
NS5-SQ0[](B)-V1/V2, NS5-SQ1[](B)-V2
NS5-TQ0[](B)-V2, NS5-TQ1[](B)-V2
NS5-MQ0[](B)-V2, NS5-MQ1[](B)-V2
Programmable Terminals
HOST CONNECTION MANUAL
Notice
OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual.
Always heed the information provided with them. Failure to heed precautions can result in injury to people or damage to property.
! DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
! WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
! Caution
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury, or property damage.
OMRON Product References
All OMRON products are capitalized in this manual. The word "Unit" is also capitalized when it refers to an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation "Ch," which appears in some displays and on some OMRON products, often means "word" and is abbreviated "Wd" in documentation in this sense.
The abbreviation "PLC" means Programmable Controller.
The abbreviation “host” means a controller, such as an IBM PC/AT or compatible computer, that controls a PT (Programmable Terminal).
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of information.
Note
Reference
Indicates information of particular interest for efficient and convenient operation of the product.
Indicates supplementary information on related topics that may be of interest to the user.
1, 2, 3...
1. Indicates lists of one sort or another, such as procedures, checklists, etc.
CS1G-CPU
[ ] [ ] -VI Boxes in model numbers indicate variable characters. For example, "CS1G-CPU
[ ] [ ] -EV1" indicates the following models: CS1G-CPU42-EV1,
CS1G-CPU43-EV1, CS1G-CPU44-EV1, and CS1G-CPU45-EV1.
© OMRON, 2008
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
1
Contents
Notice ......................................................................................................................... 1
About this Manual .......................................................................................................... 3
Related Manuals ............................................................................................................ 4
Terminology ................................................................................................................... 5
Introduction .................................................................................................................... 6
Section 1 Possible Combinations
1-1List of combinations
1-2CX-Designer and System Program version
Section 2 Connection of Temperature Controller
2-1Outline
2-2Possible combinations
2-3Configuration
2-4Setting projects
2-5Monitor variables area in temperature controller
2-6Operation of temperature controller
2-7Functional restrictions
Section 3 Connection via Memory Link
3-1How does Memory Link work
3-2Settings
3-3Communications procedures
3-4What has been changed since NT31/631
2
About this Manual
Section 1 Possible Combinations
This section provides information of possible combination of CX-Designer and system program when making connection with PT and host other than OMRON PLCs.
Section 2 Connection of Temperature Controller
This section provides information on connection methods and communications setting in connecting NS-series PTs with a Temperature Controller by serial port. It also provides information Temperature Controller which can be connected to the PT.
Section 3 Connection via Memory Link
This section describes information on connection methods and communication setting in connecting NS-series PTs with a host by Memory Link.
WARNING
Failure to read and understand the information provided in this manual may result in personal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given.
3
Related Manuals
The following manuals are used for NS-series PTs. (The boxes at the end of the catalog numbers indicate the revision code.)
NS Series -V1/-V2 Host Connection Manual .............................. V085-E1-
[]
Provides information on NS Series V1/V2 models (i.e., NS15- V2, NS12-V1/V2,
NS10-V1/V2, NS8-V1/V2, and NS5-V1/V2).
Describes how to connect the PT to the host and peripheral devices, methods to setup communications and operation, and procedures for maintenance.
Refer to the NS Series Programming Manual (V073-E1-
[]) for information on PT functions and specific operating procedures.
NS Series -V1/-V2 Setup Manual ..................................................... V083-E1-
[]
Provides information on NS Series V1/V2 models (i.e., NS15- V2, NS12-V1/V2,
NS10-V1/V2, NS8-V1/V2, and NS5-V1/V2).
Describes how to connect the PT to the host and peripheral devices, methods to setup communications and operation, and procedures for maintenance.
Refer to the NS Series Programming Manual (V073-E1-
[]) or CX-Designer Online Help for information on PT functions and specific operating procedures.
NS Series Setup Manual……………………………………………..V072-E1-
[]
Provides information on existing NS Series models (i.e., NS12, NS10, and NS7).
Describes how to connect the PT to the host and peripheral devices, methods to setup communications and operation, and procedures for maintenance.
Refer to the NS Series Programming Manual (V073-E1-
[]) for information on PT functions and specific operating procedures.
NS Series Programming Manual................................................. V073-E1-
[]
Describes the screen configurations, object functions, and host communications for the
PT.
4
Terminology
The following terminology is used in this manual.
PT
NS Series
PLC
In this manual, indicates an NS-series Programmable Terminal.
Indicates products in the OMRON NS
[ ] [ ] Series of Programmable Terminals.
Indicates a Programmable Controller in the OMRON SYSMAC CS/CJ, C, or
CVM1/CV Series of Programmable Controllers.
CS/CJ Series Indicates Programmable Controllers in the OMRON SYSMAC CS/CJ Series of
Programmable Controllers: CS1G, CS1H, CS1G-H, CS1H-H, CJ1G, CJ1M, CJ2H,
CJ2M.
C Series
CVM1/CV Series
In this manual, “CJ1H-H” indicates the CJ1H-CPU[][]H-R and CJ1H-CPU[][]H
CPU Units. “CJ1H-H-R” is used to indicate only the CJ1H-CPU [][]H-R CPU
Units.
Indicates products in the OMRON SYSMAC C Series of Programmable Controllers:
C200HS, C200HX(-Z), C200HG(-Z), C200HE(-Z), CQM1, CQM1H, CPM1A,
CPM2A, CPM2C.
Indicates products in the OMRON SYSMAC CVM1/ CV Series of Programmable
Controllers: CV500, CV1000, CV2000, CVM1
Serial Communications Unit Indicates a Serial Communications Unit for an OMRON CS/CJ-series PLC.
Serial Communications Board Indicates a Serial Communications Board for an OMRON CS-series or CQM1H
PLC.
Communications Board Indicates a Communications Board for an OMRON C200HX/HG/HE(-Z) PLC.
CPU Unit
CX-Designer
Host
Programming Manual
Indicates a CPU Unit in the OMRON SYSMAC CS/CJ, C, or CVM1/CV Series of
Programmable Controllers.
Indicates the OMRON CX-Designer (NS-CXDC1-V
[ ] ).
Indicates the PLC, IBM PC/AT or compatible computer, or personal computer functioning as the control device and interfaced with the NS-series PT.
Indicates the NS Series Programming Manual (V073-E1-
[]).
5
Introduction
• Intended Audience
This manual is intended for the following personnel, who must also have knowledge of electrical systems (an electrical engineer or the equivalent).
• Personnel in charge of introducing FA systems into production facilities.
• Personnel in charge of designing FA systems.
• Personnel in charge of installing and connecting FA systems.
• Personnel in charge of managing FA systems and facilities.
• General Precautions
• The user must operate the product according to the performance specifications described in the operation manuals.
• Do not use the PT touch switch input functions for applications where danger to human life or serious property damage is possible, or for emergency switch applications.
• Before using the product under conditions which are not described in the manual or applying the product to nuclear control systems, railroad systems, aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, and other systems, machines and equipment that may have a serious influence on lives and property if used improperly, consult your OMRON representative.
• Make sure that the ratings and performance characteristics of the product are sufficient for the systems, machines, and equipment, and be sure to provide the systems, machines, and equipment with double safety mechanisms.
• This manual provides information for connecting and setting up an NS-series PT. Be sure to read this manual before attempting to use the PT and keep this manual close at hand for reference during installation and operation.
• Safety Precautions
Do not attempt to take the Unit apart and do not touch any internal parts while the power is being supplied. Doing either of these may result in electrical shock.
• Operating Environment Precautions
1. Do not install the Unit in the following places:
• Locations subject to direct sunlight
• Locations subject to temperatures or humidity outside the range specified in the specifications
• Locations subject to condensation as the result of severe changes in temperature
• Locations subject to corrosive or flammable gases
• Locations subject to dust (especially iron dust) or salts
• Locations subject to exposure to water, oil, or chemicals
• Locations subject to shock or vibration
2. Take appropriate and sufficient countermeasures when installing systems in the following
6
locations:
• Locations subject to static electricity or other forms of noise
• Locations subject to strong electromagnetic fields
• Locations subject to possible exposure to radioactivity
• Locations close to power supplies
• Application Precautions
1. When unpacking the Units, check carefully for any external scratches or other damage.
Also, shake the Units gently and check for any abnormal sound.
2. The mounting panel must be between 1.6 and 4.8 mm thick. Tighten the Mounting
Brackets evenly to a torque of between 0.5 and 0.6 N
⋅m to maintain water and dust resistance. Make sure the panel is not dirty or warped and that it is strong enough to hold the Units.
3. Do not let metal particles enter the Units when preparing the panel.
4. If conformance to EC Directives (Low Voltage Directive) is required, use reinforced insulation for the power supplies.
5. Do not connect an AC power supply to the power terminals.
6. Use a DC power supply with minimal fluctuation voltage.
Rated power supply voltage: 24 VDC
(Allowable range: 20.4 to 27.6 VDC)
Capacity: 25 W min.
7. Do not perform a dielectric voltage test.
8. Use a twisted-pair cable with a cross-sectional area of at least 2 mm
2 to connect to the power terminals and always use M3.5 crimp terminals. Tighten the terminal screws to a torque of 0.8 N
⋅m. Make sure the screws are properly tightened.
9. Ground the Unit correctly to prevent operational errors caused by noise.
10. Do not touch the surface of the circuit board or the components mounted on it with your bare hands. Discharge any static electricity from your body before handling the board.
11. Confirm that the current capacity of the connected device is 250 mA or less before using the 5-V power supply from pin 6 of the serial port A, B connectors. The 5-V output of the
PT is 250 mA max. at 5 V
±5%.
12. Turn OFF the power supply before connecting or disconnecting cables.
13. Always tighten the connector screws after connecting communications cables.
14. The maximum tensile load for cables is 30 N. Do not apply loads greater than this.
15. Confirm the safety of the system before turning ON or OFF the power supply or before pressing the reset button.
16. The whole system may stop depending on how the power supply is turned ON or OFF.
Turn ON or OFF the power supply according to the specified procedure.
17. Start actual system application only after sufficiently checking screen data. macros, and the operation of the program in the PC (host).
18. Always reset the power supply after changing switch settings.
19. After changing the settings of the DIP switch, always turn the power supply OFF and ON or reset the PT.
20. Do not perform the following operations while the Memory Card is being accessed:
• Turning OFF the power supply to the PT
• Pressing the PT’s reset switch
• Removing the Memory Card
Always following the specified procedure when removing the Memory Card.
21. Do not press the touch switch with a force greater than 30 N.
22. Confirm the safety of the system before pressing touch switches.
23. Do not accidentally press touch switches when the backlight is not lit or when the display does not appear.
24. Signals from the touch switches may not be input if the switches are pressed
7
consecutively at high speed. Confirm each input before proceeding to the next one.
25. Before initializing screen data, confirm that existing data is backed up at the CX-Designer.
26. When changing the password with the system menu, do not reset or turn OFF the power supply until writing is finished (i.e., until the Write Button returns to its original condition). It may become impossible to manipulate screens if the password is not set correctly.
27. When using the device monitor, confirm the safety of the system before performing the following operations.
• Changing monitor data
• Changing operation modes
• Forced setting or resetting
• Changing present values or set values
28. Do not use benzene, paint thinner, or other volatile solvents, and do not use chemically treated cloths.
29. Dispose of any battery that has been dropped on the floor or otherwise subjected to excessive shock.
30. Do not attempt to disassemble, repair, or modify the Unit in any way.
31. Dispose of the Units and batteries according to local ordinances as they apply.
32. To ensure system safety, incorporate a program that periodically calls PT operation bits from the host side to check that the PT is properly operating.
33. Do not connect an USB connector to any device that is not applicable.
34. Before connecting an USB connector to a device, make sure that the device is free of damage.
35. When mounting the Battery, be sure to use the correct Battery and mount it correctly.
8
Section 1
Possible combinations
This section explains in general how to connect hosts other than NS-V1/V2 Series Omron PLC and which models to connect.
1-1List of combinations
1-2CX-Designer and System Program version
9
1-1 List of combinations
This explains the configuration when host is other than Omron PLCs.
1-1-1 Connection of temperature controller
Communicates with Omron temperature controller via RS-485.
Connect RS-422 converter CJ1W-CIF11 to serial port A or B and set communication mode to RS-485.
For details, refer to ‘Chapter 2: connection of temperature controller’.
1-1-2 Connection with memory link
When host other than PLC such as board-controller and personal computer is used, connection via memory link is possible. Use serial port A or B to connect host equipment. For details, refer to ‘chapter 3: connection via memory
link’.
10
1-2 CX-Designer and System Program versions
1-2-1 CX-Designer versions
With CX-Designer Ver.1.0 or later version, you can create and edit projects for Temperature Controller connections and Memory Link connections.
1-2-2 System Program versions
System program Ver.5.0 or later.
A copy of this version is included CX-Designer.
NS Series V1/V2 models (NS15 –V2, NS12/10/8/5 –V1/V2), and NSJ Series (NSJ12/10/8/5) are supported for those connections.
NS without –V1/V2 suffix models are not supported.
When system program version is earlier than Ver.5.0, you need to upgrade. For details on how to upgrade, refer to the manual (PDF)(How To RecoverUpdate the system) in CX-Designer.
11
Section 2
Connection of temperature controller
This section explains how to connect Omron temperature controllers (E5□N) and digital controllers
(E5AR/ER) and which models to connect.
2-1Outline
2-2Possible combinations
2-3Configuration
2-4Setting projects
2-5Monitor variables area in temperature controller
2-6Operation of temperature controller
2-7Functional restrictions
12
2-1 Outline
This explains how to connect temperature controllers.
Connectable are temperature controllers with a RS-485 port.
Use NS serial port A or B (either one), use converter to transform to RS-485.
1 serial port can accommodate max. 31 temperature controllers.
NS-series PT
Temp. controller
Temp. controller
Serial port A or B converter
CJ1W-CIF11
RS-485
(max. extension:50m)
By using another communications port, you can simultaneously connect temperature controllers and a host.
With one more serial port, NS can connect PLC, barcode reader, Memory Link and can communicate with
CX-Designer.
If NS is equipped with Ethernet port, communications with Omron PLC via Ethernet is possible.
If equipped with Controller Link I/F, communication with Omron PLC via Controller Link is possible.
13
2-2 Possible combinations
2-2-1 Connectable temperature controller
Only models with RS-485 communications port that support CompoWay/F can be used.
The following models are connectable:
Name Series Model
Temperature controller
Digital temperature controller
E5ZN
E5AN
E5EN
E5CN
E5GN
E5AR
E5ER
E5ZN-SCT24S (terminal unit)
E5AN-□□□03□-FLK
E5EN-□□□03□-FLK
E5CN-□□□03□-FLK
E5GN-□□□03□-FLK
E5AR-QC43DB-FLK
E5AR-QQ43DW-FLK
E5AR-CC43DWW-FLK
E5ER-QC43B-FLK
E5ER-PRQ43F-FLK
E5ER-QT3DW-FLK
E5ER-CT3DW-FLK
2-2-2 Temperature controller Manuals
Manual name Catalog No.
E5CN/CN-U User’s manual
E5GN User’s manual
E5□N User’s manual Communications functions
E5EN User’s manual
E5AN User’s manual
E5AR/ER User’s manual
H100-E1
H101-E1
H102-E1
H111-E1
H112-E1
Z182-E1
14
2-3 Configurations
2-3-1 Necessary parts
■RS-422A Converter
CJ1W-CIF11
■Crimp terminal
●CJ1W-CIF11side communications path terminator
Phoenix Contact AI Series
AI-0.5-8WH-B
ZA3
(serial No. 3201369)
Crimp tool (serial No. 1201882)
●CJ1W-CIF11 side other than communications path terminator
(serial No. 3200933) Phoenix Contact
Crimp tool
●Temperature controller side
AI series
AI-TWIN2×0.5-8WH
UD6 (serial No. 1204436) screw size
E5CN
E5GN
E5EN
E5AN
E5ZN
E5ER/AR
15
2-3-2 Wiring diagram
NS side
CJ1W-CIF11
SDB(+) terminal
Temperature controller side
E5ZN
E5AN
E5EN
E5CN
E5GN E5ER E5AR
Terminal number
B(+) 23 11 5 C1 F1
SDA(-)
FG
A(-) 24 12 6 C2 F2
To next temperature controller
■ Connection: 1:1 or 1:N. If 1:N, max. 32 units (NS and temperature controllers combined) can be connected.
(in case of E5ZN, the maximum is 16 units).
■ Cable length: In total max. 50 m
■ Use shielded twist pair cables (min. size AWG28)
■ Connect terminating resistance (100 to 125 Ω (1/2W) to both ends of the communications path.
Furthermore, combined resistance must be 54Ω min.
16
2-3-3 Temperature controller communications settings
This summarizes temperature controller communications settings.
For more details on settings and operation procedure of setting specifications, refer to the relevant temperature controller manual.
■ E5ZN
Setup Switch on E5ZN panel
Unit number
Baud rate
0 to 15
When using multiple E5ZN units, be careful not the use the same number twice.
0 4800 bps
1 9600 bps
2 19200 bps
Communications setting level
Data bits
Stop bits
C3 0013 or
C3 0113
C3 0014 or
C3 0114
Parity
Response
Waiting time
C3 0015 or
C3 0115
C3 0016 or
C3 0116
0 to 270FH
( 0 t o 9999)
In ms
■ E5GN/E5AN/E5EN/E5CN/E5ER/E5AR
Adjustment level L.Adj writing
Communications setting level L.S
Baud rate bPS on enable
OFF disable
Data bits
Stop bits
LEn
Sbit
2.4
4.8
9.6
19.2
38.4
7
2
In kbps
Set all communicating temperature controllers to match parameters of NS
E5ER/AR: choose between
9.6/19.2/38.4
E5□N: 38.4 cannot be selected.
7 bits
2 bits
Response
Waiting time
Communications
Unit No.
Protocol select
SdWt
U-no
PSEL
0 to 270FH
( 0 to 9999 )
0 to 31
CyF
In ms
E5AR/ER range: 0 to 63H(0 to 99)
E5AR/ER only
Compoway/F (E5AR/ER only)
17
2-3-4 CJ1W-CIF11 setting
Dip switch setting
Pin No.
1
2
3
Function
Terminal resistance select ON/OFF
Switch between 2/4 line system
Switch between 2/4 line system setting
ON Terminating resistance (on both ends of the communications path)
OFF No terminating resistance (other than both ends of the communications path)
ON
ON
2 line system
-
5
RD control by RS select ON/OFF
OFF
SD control by RS ON RS control function ON
6
Select ON/OFF
2-3-5 NS setting
Before you can connect temperature controllers, you need to store the required project in the NS. For project setting, refer to ‘2-4 setting project’.
With communications settings under system menu, you can set the speed of communications.
Baud rate 2400 / 4800 / 9600 / 19200 / 38400 / 57600 /115200 bps
Of these values, 57600 / 115200 are for future use.
Present temperature controllers cannot operate at these rates.
Set PT unit and temperature controller baud rate values to match each other.
18
2-4 Setting Project
With this function, you set projects needed to connect temperature controllers.
Select PT - Communication Setting. The Comm. Setting dialogue appears.
1. Select Serial Port A (or Serial Port B) in the left pane, and select Temperature Controller from the pull down menu for Serial Port.
2. Define temperature controller model to be connected from the pull down menu for Type. Selectable models are:
E5ZN, E5A/E/C/GN, or E5A/ER.
3. Select baud rate from the pull down menu for Comm. Speed.
Selectable baud rate values are:
2400 / 4800 / 9600 / 19200 / 38400 / 57600 / 115200 (in bps).
Baud rates 57600 / 115200 are for future use. Present temperature controllers cannot operate at these rates.
1
2
3
19
2-5 Monitor variables area in temperature controller
2-5-1 Variables area in temperature controller
Data stored in variable area of the temperature controller are: Present Value, SP, Heater burnout alarm status and such.
By reading/writing these data from PT, you can monitor temperature controller status.
Values of variables you can display on PT screen as numbers and you can create save the changes of those as log data.
Temperature controller status (variable C0, address 0001) is information on bit level. You can show status by
ON/OFF lamp and you can display/save the history log that shows status changes.
Address of variable are in a Temperature Controller should be assigned to the lamps, numeral display and input object, or graphs before monitoring the variable area.
Accessible address ranges vary with temperature controller models.
For details on accessible address ranges and definitions of settable address ranges, numerical values and contact status, refer to the following manuals.
E5AN E5EN E5CN E5GN
E5ZN
H102-E1
H112-E1
3
5, 5.10 Variables area map
E5AR E5ER Z182-E1 Appendix Settings list
CX-Designer shows accessible address range in accordance with the model specified in the Register
Host dialog so that user can set an appropriate communication address.
20
You can also manually enter a communications address, which is not listed without opening Address
Setting dialog. In this case, enter the desired address directly to the field shown in the property dialog.
21
2-5-2 Address notation in CX-Designer
Address notation when accessed using word (address for word communications)
<port>
:
<Communications
#
<Variable unit No..> category>
<Channel> <Address>
Address when accessed using bit (address for bit communications)
<port>
:
<communications
#
<Variable unit No.> category>
<channel> <address>
.
Item Value range & definition
<Port> SerialA
SerialB
00 to 31
Connected to serial port A
Connected to serial port B
<communications unit No. >
<Variable type>
<Channel>
<Address>
<Pit position>
C0 to D7
00 to 03 ch1 to ch4 variable category
Address range
C0 to C3 00 to 3F
C4 to CB 00 to 7F
CC to D7 00 to 3F
00 to 31
Example:
<bit position>
SerialB:17#D1036E.
PortB:Unit No.17/area D1/ch4/address6EH/bit3
3
2-5-3 Use of double word numbers
Variable area in the Temperature Controller is composed of values in double-word format(32bit length).
Negative values are expressed as the two’s complement. Therefore, select DINT(signed 2 words) as storage type for the variable, which the decimal value will be stored. Select UDINT(unsigned 2 words) for the variable, which the hexadecimal value will be stored.
2-5-4 Communications writing enabled/disabled
Before you can write to variable area in temperature controller, you need to go to the adjustment level and set Communications writing on Enabled: ON. (Default setting is Disabled: OFF).
For monitoring only, so when no writing is carried out, the setting can be either Disabled: OFF or
Enabled: ON.
Use either the panel on the Temperature Controller or Setting Tool to set “Communications Writing” parameter. It can be also set with Smart Active Parts in the PT.
22
2-6 Operation of Temperature Controller
The use of Smart Active Parts, allows you to operate PT screen to change Temperature Controller running conditions and to disable/enable communications writing.
2-6-1 How to create a Smart Active Parts part
In CX-Designer, you open the arrange Smart Active Parts screen.
When you select Tools - Library , the Library dialogue opens.
Under list of categories, tree of selectable libraries is shown.
Smart Active Parts for temperature controller you can find under Library -> SAP -> Smart Active Parts_E ->
Temperature Controller.
Temperature controller is grouped by model, channel and broadcast. For each operation instruction, a Smart
Active Parts part is available.
There are 2 categories: Instructions to the unit itself and broadcast .
When same instruction is given to all units, no results response is sent. For that reason error judgment is omitted.
23
Selectable Smart Active Parts are shown in the preview box on the right. Title of the selected Smart Active Parts is shown below it.
Select appropriate Smart Active Parts and drag & drop it to the screen.
By doing so, the selected Smart Active Parts is pasted onto the screen that is being edited.
Then, double click the Smart Active Parts and set communications parameters.
24
Destination port name of commands
Destination Unit No.
SERIALA :when connected to serial port A
SERIALB :when connected to serial port B
0 31 :Communications unit No. of the temperature controller you want to operate.
With broadcast to all parts, this parameter is not used. Keep default value 0.
Use the following table for serial connection.
SCU
Unit No.
Port Destination Unit No.
SCU
Unit No.
Port Destination Unit No.
When you want to change the label and color setting of the Smart Active Parts, select and right click on a Smart
Active Parts, and select Edit Smart Active Parts. It is now in Smart Active Parts edit mode. Double click on the desired object to open the property dialog and the settings can be changed.
Do not change the communications address when editing the settings. Once it has been changed, the Smart Active Parts will not function properly anymore.
Furthermore, when it is in Smart Active Parts edit mode, you cannot set Smart Active Parts communications settings. So when you want to modify the communications settings, click any area except the Smart Active parts to exit from the edit mode.
25
2-6-2 Smart Active Parts Operations
Smart Active Parts for Temperature Controllers are grouped by Temperature Controller model, channel, instruction to single unit/broadcast, control details.
Smart Active Parts title indicates the operating instruction to be executed.
■Communications writing enabled/disabled
You can either enable or disable the writing of set values from communications.
When communications writing is disabled, the writing of set values from communications and the execution of certain instructions is prohibited.
Default setting is set as Disable.
By executing Smart Active Parts Enable communications writing/Disable communications writing, you can switch between enabled/disabled.
If communications writing is not enabled before writing set values with numeral display & input object or word button, an error occurs.
Furthermore, by disabling communications writing, you can avoid that set values are being changed by accident.
A summary of executable/non executable instructions when communications writing is disabled, is given in table ‘2-6-3 Smart Active Parts list’.
■Setting area 0/setting area 1
Temperature controller communications has 2 operation modes: setting area 0 and setting area 1.
In setting area 0, control operations are conducted. You cannot modify any set values that negatively affect the control operations. When power supply is turned on, this mode is selected.
In Setting area 1, the control operations are stopped. You can modify the set values protected in Setting area 0.
You can switch to Setting area 1 by executing Smart Active Parts part ‘Move to setting area 1’.
To change from Setting area 1 to Setting area 0, you can either turn the power off and then back ON again or you can execute Smart Active Parts part: “ Software Reset”.
Executable operating instructions vary depending on which mode is selected: setting area 0 or 1.
Non executable in setting
Area 0
Initialize set values
Non executable in setting
Area 1
AT execute/cancel
Move to protect level
Auto/manual
PV hold
26
■Confirm command results
Under certain conditions e.g. communications writing disabled, it can happen that a selected Smart Active
Parts instruction cannot be executed.
But, when performing the broadcast, no response is given. In that case there is no check as to whether the action was completed successfully or not.
Theref,ore adopt a method that checks if the operation was carried out properly, e.g. lamp indication.
Model
Title
(operating instruction)
Communications writing disabled
Communications writing enabled
Addresses to be monitored ch1 CO0001.25 ch 2 CO 0101.25
Common stop
AT execute
AT cancel
Writing mode: back-up
Writing mode: RAM
Move to setup area 1 ch 2 ch1 ch 2 ch1 ch 2
CO 0101.24
CO 0001.23
CO 0101.23
CO 0001.20
CO 0101.20 ch 2 CO 0101.22
E5ZN
E5□R
Cancel alarm 1 latch
Cancel alarm 2 latch
Cancel alarm 3 latch
Cancel all alarm latches
Cancel alarm latch
SP mode: local SP
SP mode: remote SP
Select bank: 0 to 7
AT execute
(confirm executing PID group No.) ch1 ch2
*1
C00001.12 to 15
C00101.12 to 15 ch1 ch 2 ch 3 ch 4
*1 ch1 ch 2 ch 1 ch 2 ch 3 ch 4
C00001.12 to 15
C00101.12 to 15
C00201.12 to 15
C00301.12 to 15
C00001.27
C00101.27
C40408
C41408
C42408
C43408 ch 1 ch 2
C4040A
C4140A ch 3 C4240A ch4 C4340A
*1 Confirm that alarm output has become OFF.
Attention: Under certain conditions such as PV that an alarm might be output, you cannot confirm because alarm output remains high even when the latch is cancelled
27
28
For more information on each Smart Active Parts’ functions and usage, refer to Smart Active Parts Library manuals: Temperature Controller (CJ1W-TC), Temperature Controller (E5xN), Temperature Controller (E5xR),
Temperature Controller (E5CN), Temperature Controller (E5ZN), and Temperature Controller (from Ver5 or earlier).
2-7 Restrictions
2-7-1 The behavior of 2 word number in the CX-Designer test function
In the temperature controller, a value equivalent to 2 words (32 bits) is stored for each communications address, but in the test function, the first 16 bits and the last 16 bits behave as one and the same value. For that reason, test function will not operate successfully when 2 word numbers are designated.
2-7-2 Address display when address error occurs
When faulty device is set to communications address set in functional object, this communications address is displayed in the device setting error dialogue.
If the communications address is allocated to the temperature controller, not the address for the temperature controller set with the CX-Designer, but the address in the PLC address format is displayed. Addresses will be converted as shown below.
<Device>
Address displayed when faulty device is set to communications address
0000 to 7FFF 00 to 15
Word address Bit position
10 6 5 4 3 2 1
Unit No.
0 to 31
0
Ch
0-3
<variable>
0 to F
<address>
0000 to 007F
0 7 6 5 4 3 2 1 0
0 0 0 0
Bit position
0 to 31
CH address of temperature controller
<Device>
DM
EM
EM8_
EM9_
EMA_
EMB_
EMC_
WR
0
2
20
22
24
26
28
30
Unit
No.
1
3
21
23
25
27
29
31
Temp
<Variable > controller
<Address>
Variable
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
C0 C1 0000 to 003F
C2 C3
C4
0040 to 007F
C5
C6
C7
C8
0000 to 007F
C9
CA
CB
CC CD
CE CF
D0 D1
D2 D3
D4 D5
D6 D7
0040 to 007F
0000 to 003F
0040 to 007F
0000 to 003F
0040 to 007F
0000 to 003F
29
Device setting errors are not likely to occur. This because, setting is done using the method by which a selection is made from a list of accessible addresses for each temperature controller model.
However, in below cases in which the address is not selected from the list of accessible addresses an invalid address may have been assigned. In such a case, a device setting error may occur. z
Communications address set when functional object was copied using repeat command when index was assigned. z
Communications address set by ‘Allocate Addresses Automatically ’ in the frame property. z
Communications address set by using the macro function.
Furthermore, z
Writing to read-only area z
Writing while communications writing was prohibited cause device setting errors to occur.
2-7-3 Communications address set when functional part was copied
using repeat command
In CX-Designer, you can select functional object and when you then execute ‘repeat’ , you can copy while communications addresses are being added.
The temperature controller’s address is a double word address. To increment a double word address by 1, you need to increment a single word address by 2.
Address in CX-Designer is expressed as a 1 word address. When repeat command is used to copy functional object, 1 word is added to 1 word address.
For that reason, when communications address offset width is 1 while repeat command is used, part with the same communications address is copied twice.
Actual address Internal address
Double word
+0
Single word
+0 Address originally set for functional object
Omit figures below decimal0.5->0 +0 (0.5) +1
+1 +2
+1 (1.5) +3 Omit figures below decimal 0.5->0
For that reason, set always offset in multiples of 2 to specify communications address with single word access.
30
Section 3
Connection via Memory Link
This chapter explains the Memory Link function and how to use it to connect host computer.
3-1How does Memory Link work
3-2Settings
3-3Communications procedures
3-4What has been changed since NT31/631
31
3-1 How does Memory Link work
3-1-1 PT memory
With Memory Link you assign objects word and bit to PT memory. PT memory is an imaginary PLC area inside the NS. NS performs read/write operations to internal PT memory. Host reads/writes PT memory as required and so controls and monitors NS.
PT memory consists of 2 territories: Bit ($B) and Word ($W).
Host reads/writes internal holding memory($HB/$HW) can be used in the following combination:
NS system program Ver. 6.2 and later versions
System Ver.6.2 and later projects
PT memory can be also used to store functional object display character strings or as data area for the macro function.
3-1-2 Command and response
With Memory Link, the following commands enable data transmission between host and PT.
- Read-out command / response
This is the command for reading out PT memory of PT.
When host gives command, PT responds the contents of the designated data.
There are 4 commands that vary with the type of PT memory.
Command Title
Read out PT ($W) memory
RM
Action
Read out $W data in PT memory
RB
RD
Read out PT ($B) memory
Read out PT ($HW) memory
Read out $B data in PT memory
Read out $HW data in PT memory
RH Read out PT ($HB) memory Read out $HB data in PT memory
- Write command/response
This is the command to write designated data to PT memory area in PT.
Host gives command. PT responds whether or not the writing was completed successfully.
The successful completion response may be omitted by particular setting the Response parameter in the communications conditions menu.
The following 8 commands can be given:
Command Title
Write to PT memory ($W)
WM
Action
Write data to PT memory $W
WB
WD
Write to PT memory ($B)
Write to PT memory ($HW)
Write data to PT memory $B
Write data to PT memory $HW
WH
FM
Write to PT memory ($HB)
FILL PT memory ($W)
Write data to PT memory $HB
Write designated data to multiple
PT memory $W
32
FB
FD
FH
FILL PT memory ($B)
FILL PT memory ($HW)
FILL PT memory ($HB)
Write designated data (0 or 1) to
Multiple PT memory $B.
Write designated data to multiple
PT memory $HW
Write designated data (0 or 1) to
Multiple PT memory $HB.
- Notify Command
This is the command to communicate the results of PT operations to host.
PT gives command. For that reason, there is no response.
The following 4 commands can be given.
command Title Action
PT memory ($W) change notice Notify host of PT memory $W changes.
SM
SB
SD
PT memory ($B) change notice Notify host of PT memory $B changes.
PT memory ($HW) change notice Notify host of PT memory $HW changes.
SH changes.
- Error response
Response from PT when the received command is an invalid one.
Command Title
Error response
ER
Action
Notify host of command error
33
3-1-3 Action when command is used
There are 3 flows of communications between host and PT, depending on the type of command and Response
Settings in Communications conditions.
- Write data command while [response: OFF]
[Host] [PT]
Write data command
Send command Receive command
- Write Data command while [response: ON]
- Read-out data command
- Invalid command
Send command Receive command receive response
- PT to host communications
Send response
[Host] [PT]
Receive change notice command.
Communicate command
Change PT memory
Send change notice command
34
3-1-4 Notify Command Behavior
When anything has changed in the PT memory, by e.g. touch switch operation on PT, numerical input or character string input, PT sends change notice command to host.
In addition to Memory Link connection, PT memory serves other purposes as well. If all changes would be communicated to host, the host would be burdened more than is needed. For that reason, PT communicates only changes from a designated number and up. Changes in PT memory areas with a lower number are not communicated.
Set the number in Communications conditions -> Notice Start $B, Notice Start $W, Notice Start $HB, and
Notice Start $HW.
$W
$W0 no notice
PT operati on
Number input
Notice start
$W notify command
Number input
Only changes from specified $W number and up are communicated to host using the change notice Command.
3-1-5 Flow control
When too many commands are sent, PT cannot process timely. Communications buffer overflows. Commands and command sequence get lost. Memory Link connection in NS Series -V1/-V2 models do not support flow control.
For that reason, set Communications conditions Response to ON when PT to host command interval frequency becomes high.
35
3-2 Settings
3-2-1 Making settings for the Project
The Memory Link can be used in combination with
NS system program Ver. 5.0 and later versions
System Ver.5.0 and later projects
With CX-Designer, you can create and edit project developed by System Ver.5.0 and later projects.
A project created with System Ver.4.0 or earlier can be opened with CX-Designer and converted to data of Ver.5.0 and later.
Open a project created with System Ver.5.0 using CX-Designer, and select PT - Communication Setting. The
Comm. Setting dialogue appears. Select Serial Port A (or Serial Port B) in the left pane, and select Memory Link from the pull down menu for
Serial Port.
36
You cannot simultaneously set Serial Port A and B to Memory Link.
37
3-2-2 Communications conditions setting
In CX-Designer, select Serial Port A (or Serial Port B) in the Comm. Setting dialog box, and set to the following communications conditions. With System Ver.6.2 and later projects, you can set Notice start $HB and Notice start $HW.
Parameter
Baud rate
Data bits
Stop bits
Parity response
Notice start $B
Notice start $W
Notice start $HB
Notice start $HW
Set value
9600bps / 19200bps / 38400bps
7 / 8
1 / 2
None / Even / Odd
OFF / ON
0 to 32767
0 to 32767
0 to 8191
0 to 8191
Default value
9600bps
7
1
Even
OFF
16384
16384
4096
4096
3-2-3 NS system menu operation
You can also use the NS system menu to set the communications conditions for the Memory Link connection.
Under system menu, click tab Communications Setting.
By pressing the key beside the Serial Port A or Serial Port B, you can switch between communications methods.
unused
↓
NT Link 1:1
↓
NT Link 1:N
↓
Bar code reader
↓
↓
Memory Link
↓
↓
Modem
After you have thus set communications to Memory Link, use the Details key to set the communications conditions for the Memory Link connection (for details, refer to section 2.2). However, with system menu you cannot set the Notice start $B, Notice start $W, Notice start $HB, and Notice start $HW.
Set values are not saved until you press the Write key. Also, setting changes will be effective when you turn the power OFF and then ON again.
38
3-2-4 Connection Diagram
Use either NS Serial Port A or B to connect host computer via Memory Link.
You cannot simultaneously set Serial Port A and B to Memory Link.
The connecting cable varies with the specifications of the host computer communications port.
Below is a typical example, which shows the wiring diagram when DOS/V PC is connected.
9pin
Dsub(Female)
3 SD
2 RD
7 RS
8 CS
5 SG
DOS/V PC
9pin
Dsub(Male)
SD
RD
2
3
RS 4
CS
SG
5
9
NS-series PT
Above wiring is identical with the NS to and from CX-Designer wiring.
If the cable length is conform, you can use the following cable with connector.
Cable length 2m, 9 pin⇔9 pin
39
3-3 Communications procedures
3-3-1 Memory Link Commands
Command/response formats are as mentioned below.
• Read/write/change notify command
ESC command *S *A *L *D SUM CR
• Read/write command (In above-mentioned format, the *L is regarded as 1 (fixed))
ESC command *S *A *D SUM CR
• Write all (FILL) command
ESC command *S *A *B *D
• Read type command normal completion response format
ESC command *A *L *D SUM
SUM CR
CR
ESC command *D SUM CR
*A
*B
*L
*D
ESC
SUM
CR
($1B) Initial Command: ESC($1B) fixed characters
1 English capital letters which display the type of command
Designates SUM omission and *L omission. In some cases, specifies write to memory attributes as well. character
SUM OFF: SUM computing by host can be omitted.
SUM ON: enables judgment if command is invalid as a result of noise interference.
Hexadecimal
4 digits
Initial read/write address
Hexadecimal
4 digits
Last Write all (FILL) address
BCD 2 digits
Variable length
2 characters
(may be abbreviated)
($0D)
Number of read/write elements
Data section
The checksum of the command response is the 2 digit code in hexadecimal which is indicated using lower one-byte of the total sum from the ESC to the *D. It can be abbreviated by specifying *S. Be sure that it is added when PT is transmitting.
Command end: CR($0D) fixed
40
Memory Link commands are as follows:
Command
RM
RB
RD
RH
WM
WB
WD
WH
Command title
Read PT memory ($W)
Read PT memory ($B)
Read PT memory ($HW)
Read PT memory ($HB)
Write PT memory ($W)
Write PT memory ($B)
Write PT memory ($HW)
Write PT memory ($HB)
Fill PT memory ($W)
FM
Fill PT memory ($B)
FB
Fill PT memory ($HW)
FD
Fill PT memory ($HB)
FH
SM
SB
SD
SH
PT memory ($W) change notice
PT memory ($B) change notice
PT memory ($HW) change notice
PT memory ($HB) change notice
Action
Read contents of $W data
Read contents of $B data
Read contents of $HW data
Read contents of $HB data
Write to $W data
Write to $B data
Write to $HW data
Write to $HB data
Fill multiple sequential $W with the same value
Fill multiple sequential $B with the same value.
Fill multiple sequential $HW with the same value
Fill multiple sequential $HB with the same value.
Communicate $W changes to host
Communicate $B changes to host
Communicate $HW changes to host
Communicate $HB changes to host
41
RM Read PT memory ($W)
Read $W data in PT memory.
Per command, a maximum of 100 words can be read.
Response is up to 50 words per response.
When requesting command is parameter 2: number of words exceeds 51, then the response is split into two.
The first response sends 50 words, the second response sends the remaining channels.
When entries were made on NS in between the first and second response, change notice command is not sent until after the second response has been sent.
ESC command *S *A
$1B
R
M
*L SUM CR
$0D
[Settings]
*S
0 OFF
1 ON
*A
*L
0000 to 7FFF
00 to 99
Initial address No. (hexadecimal 4 digits)
Number of read-out words (BCD 2 digits)
00 indicates 100.
• Successful completion response format
ESC command
*A
*L *D SUM CR
$0D
[Settings]
*A
0000 to 7FFF Initial address No. (hexadecimal 4 digits)
*L
*D
01 to 50
0 to FFFF
“,”
Number of read-out words (BCD 2 digits)
Word data (zero suppressed hexadecimal 1 to 4 digits)
From 2 nd
word onward, enter comma “, “($2C) before the next data.
42
RB Read PT memory ($B)
Read $B data in PT memory.
Per command, a maximum of 100 bits can be read.
After reading, bit data are displayed and returned per 8 bits as 8 bit value.
ESC command
*S
$0D
[Settings]
*A
*L
*S
0 OFF
1 ON
8 OFF
Number of tables: 1 (fixed). Omit Parameter2.
9 ON
0000 to 7FFF Initial address No. (hexadecimal 4 digits)
00 to 99 Read-out bit number (BCD 2 digits)
00 indicates 100.
ESC command *A
$1B
R
*L *D
B Variable length
SUM CR
$0D
[Settings]
*A
0000 to 7FFF Initial address No. (hexadecimal 4 digits)
*L
*D
00 to 99
00 to FF
Number of bits (BCD 2 digits)
00 indicates 100.
Bit data (hexadecimal 2 digit value of 8 bits each)
0:OFF, 1: ON
Fills addresses in ascending order starting with first digit. Turns 8 bits into a binary 8 digit value and displays this as a hexadecimal 2 digit value. The next hexadecimal 2 digit value continues with the following 8 bits.
Fills any of the last 8 bits that does not actually have a valid read-out data with 0.
[example] from $B10 6 bits have read-out value
$B10 11 12 13 14 15 * *
1 0 1 0 1 1 0 0 → AC (converted to hexadecimal form)
43
RD Read PT memory ($HW)
Read $HW data in PT memory.
Per command, a maximum of 100 words can be read.
Response is up to 50 words per response.
When requesting command is parameter 2: number of words exceeds 51, then the response is split into two.
The first response sends 50 words, the second response sends the remaining channels.
When entries were made on NS in between the first and second response, change notice command is not sent until after the second response has been sent.
ESC command *S *A
$1B
R
D
*L SUM CR
$0D
[Settings]
*S
0 OFF
1 ON
*A
*L
0000 to 1FFF Initial address No. (hexadecimal 4 digits)
00 to 99 Number of read-out words (BCD 2 digits)
00 indicates 100.
• Successful completion response format
ESC command
*A
*L *D SUM CR
$0D
[Settings]
*A
0000 to 1FFF Initial address No. (hexadecimal 4 digits)
*L 01 to 50
*D 0 to FFFF
“,”
Number of read-out words (BCD 2 digits)
Word data (zero suppressed hexadecimal 1 to 4 digits)
From 2 nd
word onward, enter comma “, “($2C) before the next data.
44
RH Read PT memory ($HB)
Read $HB data in PT memory.
Per command, a maximum of 100 bits can be read.
After reading, bit data are displayed and returned per 8 bits as 8 bit value.
ESC command
*S
$0D
[Settings]
*A
*L
*S
0 OFF
1 ON
8 OFF
Number of tables: 1 (fixed). Omit Parameter2.
9 ON
0000 to 1FFF Initial address No. (hexadecimal 4 digits)
00 to 99 Read-out bit number (BCD 2 digits)
00 indicates 100.
ESC command *A
$1B
R
*L *D
H Variable length
SUM CR
$0D
[Settings]
*A
0000 to 1FFF Initial address No. (hexadecimal 4 digits)
*L
*D
00 to 99
00 to FF
Number of bits (BCD 2 digits)
00 indicates 100.
Bit data (hexadecimal 2 digit value of 8 bits each)
0:OFF, 1: ON
Fills addresses in ascending order starting with first digit. Turns 8 bits into a binary 8 digit value and displays this as a hexadecimal 2 digit value. The next hexadecimal 2 digit value continues with the following 8 bits.
Fills any of the last 8 bits that does not actually have a valid read-out data with 0.
[example] from $HB10 6 bits have read-out value
$HB10 11 12 13 14 15 * *
1 0 1 0 1 1 0 0 → AC (converted to hexadecimal form)
45
WM Write to PT memory ($W)
Write to $W data in PT memory.
Per command, a maximum of 50 words can be written.
As writing attribute you can select SET, AND, OR, or XOR.
ESC command CR
*S
$0D length
[Settings]
*S
BCD1digit
SUM Writing attribute
0 OFF
Writes designated value just as it is.
2 OFF
AND
3 ON
4 OFF
OR
5 ON
6 OFF
XOR
7 ON
Ands present value of destination with designated value and writes outcome.
Ors present value of destination with designated value and writes outcome
Xors present value of destination with designated value and writes outcome.
8 OFF Omits *L .
Number of destination words : 1
(fixed)
*A
*L
0000 to 7FFF
01to 50
*D 0000 to FFFF
“,”
Initial address number (hexadecimal 4 digits)
Number of destination words (BCD 2 digits)
Word data (zero suppressed hexadecimal, 1 to 4 digits)
From 2 nd
word on, enter comma [,] ($2C) before next data.
Data ending with comma cause error.
• Normal completion response format (only when response under communications conditions is ON).
ESC command SUM CR
$0D
[Settings]
*D
00 fixed. Indicates successful completion.
46
WB Write PT memory ($B)
Write to $B data in PT memory.
Per command, a maximum of 100 bits can be written.
ESC command
*S
CR
$0D length
[Settings]
*A
*L
*D
*S
BCD1 digit SUM value
0 OFF
1 ON
8 OFF
Bit number: 1 fixed. Parameter 2 omitted.
9 ON
0000 to 7FFF Initial address number (hexadecimal 4 digits)
00 to 99
00 to FF
Entry bit number (BCD 2 digits)
When 00, 100 is meant.
Bit data (hexadecimal 1 digit value for 4 bits each)
0: OFF, 1: ON
Fills data in descending order starting with first digit. Turns 4 bits into a binary 4 digit value and displays this as a hexadecimal 1 digit value. The next hexadecimal 1 digit value continues with the following 4 bits.
Fills any of the last 4 bits that does not actually have a valid read-out data with 0.
[example] from $B10, 6 bits have read-out value
$B10 11 12 13 14 15 * *
1 0 1 0 1 1 0 0 → AC (converted to hexadecimal form)
• Normal completion response format (only when response under communications conditions is ON).
ESC command
*D
SUM CR
$1B W B 0
0
$0D
[Settings]
47
*D
00 fixed. Indicates normal completion.
48
WD Write to PT memory ($HW)
Write to $HW data in PT memory.
Per command, a maximum of 50 words can be written.
As writing attribute you can select SET, AND, OR, or XOR.
ESC command CR
*S
$0D length
[Settings]
*S
BCD1digit
SUM Writing attribute
0 OFF
SET
1 ON
2 OFF
AND
3 ON
4 OFF
OR
5 ON
6 OFF
XOR
7 ON
8 OFF
Writes designated value just as it is.
Ands present value of destination with designated value and writes outcome.
Ors present value of destination with designated value and writes outcome
Xors present value of destination with designated value and writes outcome.
Omits *L .
Number of destination words : 1
(fixed)
*A
*L
0000 to 1FFF
01to 50
*D 0000 to FFFF
“,”
Initial address number (hexadecimal 4 digits)
Number of destination words (BCD 2 digits)
Word data (zero suppressed hexadecimal, 1 to 4 digits)
From 2 nd
word on, enter comma [,] ($2C) before next data.
Data ending with comma cause error.
• Normal completion response format (only when response under communications conditions is ON).
ESC command SUM CR
$0D
[Settings]
*D
00 fixed. Indicates successful completion.
49
WH Write PT memory ($HB)
Write to $HB data in PT memory.
Per command, a maximum of 100 bits can be written.
ESC command
*S
CR
$0D length
[Settings]
*A
*L
*D
*S
BCD1 digit SUM value
0 OFF
1 ON
8 OFF
Bit number: 1 fixed. Parameter 2 omitted.
9 ON
0000 to 1FFF Initial address number (hexadecimal 4 digits)
00 to 99
00 to FF
Entry bit number (BCD 2 digits)
When 00, 100 is meant.
Bit data (hexadecimal 1 digit value for 4 bits each)
0: OFF, 1: ON
Fills data in descending order starting with first digit. Turns 4 bits into a binary 4 digit value and displays this as a hexadecimal 1 digit value. The next hexadecimal 1 digit value continues with the following 4 bits.
Fills any of the last 4 bits that does not actually have a valid read-out data with 0.
[example] from $HB10, 6 bits have read-out value
$HB10 11 12 13 14 15 * *
1 0 1 0 1 1 0 0 → AC (converted to hexadecimal form)
• Normal completion response format (only when response under communications conditions is ON).
ESC command
*D
SUM CR
$1B W H 0
0
$0D
[Settings]
50
*D
00 fixed. Indicates normal completion.
51
FM Fill PT memory ($W)
Fills PT memory $W with the same word data. Range: first to last address number.
ESC command
*S
*A *B *D SUM CR
$1B F M $0D
[Settings]
*A
*B
*D
*S
BCD1 digit
SUM value
0 OFF
1 ON
0000 to 7FFF First address number (hexadecimal 4 digits)
0000 to 7FFF Last address number (hexadecimal 4 digits)
0 to FFFF Word data (zero suppressed hexadecimal 1 to 4 digits)
• Normal completion response format (only when response under communications conditions is ON).
ESC command
*D
SUM CR
0 E $0D
[Settings]
*D
00 fixed. Indicates normal completion.
52
FB Fill PT memory ($B)
Fills PT memory $B with the same bit data. Range: first to last address number.
ESC command
*S
$1B F B $0D
[Settings]
*A
*B
*S
BCD1 digit
SUM value
0 OFF
1 ON
0000 to 7FFF Initial address number (hexadecimal 4 digits)
0000 to 7FFF Last address number (hexadecimal 4 digits)
Bit data (hexadecimal 1 digit)
1: ON
• Normal completion response format (only when response under communications conditions is ON).
ESC command
*D
SUM CR
$0D
[Settings]
*D
00 fixed. Indicates normal completion.
53
FD Fill PT memory ($HW)
Fills PT memory $HW with the same word data. Range: first to last address number.
ESC command
*S
*A *B *D SUM CR
$1B F D $0D
[Settings]
*A
*B
*D
*S
BCD1 digit
SUM value
0 OFF
1 ON
0000 to 1FFF First address number (hexadecimal 4 digits)
0000 to 1FFF Last address number (hexadecimal 4 digits)
0 to FFFF Word data (zero suppressed hexadecimal 1 to 4 digits)
• Normal completion response format (only when response under communications conditions is ON).
ESC command
*D
SUM CR
0 E $0D
[Settings]
*D
00 fixed. Indicates normal completion.
54
FH Fill PT memory ($HB)
Fills PT memory $HB with the same bit data. Range: first to last address number.
ESC command
*S
$1B F H $0D
[Settings]
*A
*B
*S
BCD1 digit
SUM value
0 OFF
1 ON
0000 to 1FFF Initial address number (hexadecimal 4 digits)
0000 to 1FFF Last address number (hexadecimal 4 digits)
Bit data (hexadecimal 1 digit)
1: ON
• Normal completion response format (only when response under communications conditions is ON).
ESC command
*D
SUM CR
$0D
[Settings]
*D
00 fixed. Indicates normal completion.
55
SM PT memory ($W) change notice
When PT memory $W changed as a result of PT operation and when this $W address is higher than the address designated with Notice start $W in the communications settings menu, this command is sent from PT to host.
Response from host to PT is not needed.
When sent from host to PT, illegal command error occurs.
ESC command
*A
*L *D SUM CR
$1B S M Variable length
$0D
SB
[Settings]
*A
0000 to 7FFF Changed address number (hexadecimal 4 digits)
*L
*D
01 to 50
0000 to FFFF
“,”
Number of changed words (BCD 2 digits)
Word data (zero suppressed hexadecimal 1 to 4 digits)
Divide multiple word data by comma [,] ($2C).
Data ending with comma cause error.
PT memory ($B) change notice
When PT memory $B changed as a result of PT operation and when this $B address is higher than the address designated with Notice start $B in the communications settings menu, this command is sent from PT to host.
Response from host to PT is not needed.
When sent from host to PT, illegal command error occurs.
ESC command CR
*A
$0D
[Settings]
*A
*B
0000 to 7FFF Changed address number (hexadecimal 4 digits)
01 fixed Number of changed bits (hexadecimal 2 digits)
Bit data (hexadecimal 1 digit)
1: ON
56
SD PT memory ($HW) change notice
When PT memory $HW changed as a result of PT operation and when this $HW address is higher than the address designated with Notice start $HW in the communications settings menu, this command is sent from PT to host.
Response from host to PT is not needed.
When sent from host to PT, illegal command error occurs.
ESC command
*A
*L *D SUM CR
$1B S D Variable length
$0D
SH
[Settings]
*A
0000 to 1FFF Changed address number (hexadecimal 4 digits)
*L
*D
01 to 50
0000 to FFFF
“,”
Number of changed words (BCD 2 digits)
Word data (zero suppressed hexadecimal 1 to 4 digits)
Divide multiple word data by comma [,] ($2C).
Data ending with comma cause error.
PT memory ($HB) change notice
When PT memory $HB changed as a result of PT operation and when this $HB address is higher than the address designated with Notice start $HB in the communications settings menu, this command is sent from PT to host.
Response from host to PT is not needed.
When sent from host to PT, illegal command error occurs.
ESC command CR
*A
$0D
[Settings]
*A
*B
0000 to 1FFF Changed address number (hexadecimal 4 digits)
01 fixed Number of changed bits (hexadecimal 2 digits)
Bit data (hexadecimal 1 digit)
1: ON
57
ESC command
*D
SUM CR
$1B E R $0D
[Settings]
*D
Error codes listed below (hexadecimal 2 digits)
Error code
Error contents
01 Illegal command
02
03
05
10
12
Command length error
Boundary value error
Command format error
SUM value error
Reception timeout error cause
Command contents lie outside the supported range
Length of received command is illegal for that command.
• Value set to parameter lies outside the supported range.
• Parameter in BCD format includes others than 0 to 9
Sum information Set value lies outside the effective range.
$W/$B command; Data section includes characters other than 0 to F and “,”.
$W command; data section ends with “,”.
Command with sum value ON. Computed sum value and the one in the command do not match.
After the initial ESC was received, the interval in between receiving one byte after the other until command end [CR] exceeded timeout monitoring time.
These commands are sent from NS to host when the host sent an invalid command and when a communications error occurred.
58
3-4 What has been changed since NT31/631
3-4-1 Memory Link Commands
This summarizes the points that need to be given attention when switching over from NT31/631 series to NS series Memory Link.
Memory structure inside PT differs, so the structure of Memory Link commands has changed as well.
■Memory structure inside PT
PT memory
Memory table
NT31/631 series
Contact point channel common
0000 to 9999
Number memory table
Character string memory table bit memory table
NS series
Contact point
$B0 to 65535 $HB0 to 8191 channel $W0 to 65535 $HW0 to 8191 none
Battery backup
Is performed Is not performed Is performed
■Memory Link command
CB
ST
SN
SS
PM
SM
SB
MC
RM
RB
RN
RS
WM
WB
FR
PT
WN
WS
FM
FB
CN
CS
ER
RD
NT31/631 series
Read-out PT memory
NS series
Read-out PT memory ($W)
Read-out bit memory table
Read-out number memory table
Read-out character string memory table
Write to PT memory
Write to bit memory table
Read-out display data comment
Read-out PT memory ($B)
-
-
Read-out system conditions
Write to number memory table
Write to character string memory table
Fill PT memory
-
Clear number memory table
Clear character string memory table
Clear bit memory table
Fill PT memory ($W)
Fill PT memory ($B)
-
-
Touch switch input notice
Number input notice
Character string input notice
-
-
-
-
-
-
-
Write to PT memory ($W)
Write to PT memory ($B)
-
Direct area change notice
PT memory change notice
-
Switch PT operating mode
Error response
-
-
PT memory ($W) change notice
PT memory ($B) change notice
-
-
Error response
Read-out PT memory ($HW)
59
RH
WD
WH
FD
FH
SD
SH
-
-
-
-
-
-
-
Read-out PT memory ($HB)
Write to PT memory ($HW)
Write to PT memory ($HB)
Fill PT memory ($HW)
Fill PT memory ($HB)
PT memory ($HW) change notice
PT memory ($HB) change notice
■Execution of contact notice to $W
While NT31/631 performs contact point change notice and channel change notice in the same PT memory, the
NS splits it into $B and $W
There, the use of a macro, enables the contact point notice to $W.
E.g. Momentary switch sending notice to 5 th
bit in $W1000
•
Create ON/OFF button
•
Designate $B address that is not specified for any other purpose.
Destination address may be blank, but in that case the button does not light when it is being pressed down.
•
Edit macro (touch ON)
$W1000 = $W1000 | H10;
•
Edit macro (touch OFF)
$W1000 = $W1000 & to H10;
■PT memory hold
Battery backup in NT31/631 ensures that PT memory and memory table values are kept as they were when the power goes off.
Because NS’s battery backup holds PT memories($HB/$HW), the values in these memories are kept as they were when the power goes off. Host reads/writes internal holding memory($HB/$HW) is only available in the following combination:
NS system program ver.6.2 and later versions
System ver.6.2 and later projects
NS cannot react to an unexpected power fall out, but there is a possibility to store values before the power is turned OFF.
You can save a copy of PT memory $W by saving the contents of this memory as a file on a compact flash card.
Then removes this card.
As it is a file reading/writing operation to a compact flash card, it cannot be done frequently. In addition, you cannot save a copy of the PT memory $B.
E.g. Manually save the PT memory $W contents.
•
Create a command button
•
Set function selection to No processing
60
•
Edit macro (touch ON)
WRITECF($W16384,16384,”PTMEM.DAT”,0);
E.g. Recover PT memory $W contents from saved file when PT is started up.
•
Edit macro when project is started up
READCF($W16384,16384,”PTMEM.DAT”,0);
61
Revision History
A manual revision code appears as a suffix to the catalog number on the cover of the manual.
Man.No. V085-E1-[]
Revision code
The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version.
Revision code
01
02
03
04
05
06
07
Date Revised content
October 2003 Original production
July 2004 Addition of information related to NS-Designer Ver.6.0 upgrade
February 2005 Addition of information related to NS-Designer Ver.6.2 upgrade
July 2006
July 2007
Addition of information related to CX-Designer release
Addition of information related to CJ1H-CPU[][]H-R release
June 2008 Addition of information related to NS5-[][]1[][] release
October 2010 Addition of information related to CX-Designer release
OMRON Corporation
Industrial Automation Company
Tokyo, JAPAN
Contact: www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg,
IL 60173-5302 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
Authorized Distributor:
© OMRON Corporation 2009 All Rights Reserved.
In the interest of product improvement, specifications are subject to change without notice.
Cat. No. V085-E1-07
1010
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project