- Home
- Domestic appliances
- Sewing & ironing
- Sewing machines
- Rational
- SelfCookingCenter® 5Senses 6x1/1 GN
- Installation manual
- 44 Pages
RATIONAL SelfCookingCenter® 5Senses 6x1/1 GN, 6x2/1 GN, 10x1/1 GN, 10x2/1 GN, 20x1/1 GN, 20x2/1 GN oven Installation Manual
Below you will find brief information for SelfCookingCenter® 5Senses 6x1/1 GN, SelfCookingCenter® 5Senses 6x2/1 GN, SelfCookingCenter® 5Senses 10x1/1 GN. This manual describes the steps you need to take to install your oven. The manual also provides information about the unit's technical data, including its weight, heat emission, and noise emission level.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
Original
Installation Manual
Safety instructions
Explanations of the icon's
Danger!
Immediate dangerous situation, that can endanger severe injury or death
Warning!
Possibly dangerous situation, that possibly can endanger severe injury or death.
Caution!
Possibly dangerous situation, that can endanger minor injury.
Corrosive substances
Attention: Inobservance can cause material damages.
Fire hazard!
Tips and tricks for installation
Danger of burning!
Danger!
High voltage.
Caution danger of life
Inobservance can endanger severe injury or death.
V-09 05/2014 - 2 -
Safety instructions
WARNING
Wrong installation, service, maintenance or cleaning as well as unauthorized changes on the unit can cause damages, injuries or even death. Read the installation manual carefully before installing the unit.
This unit may only be used for preparing food in commercial kitchens. Every other usage is against definition and therefore dangerous.
WARNING
Only gas units
Waste gases!
- If the unit is installed underneath an extraction hood, it must be made sure that the hood is switched on during operation of the unit
Fire hazard!
- If the gas unit is connected to a chimney, it must be made sure that the exhaust line will be cleaned on a regular basis subject to local regulations (For this purpose also contact the installer)
- Don't put any material on the exhaust pipes of the unit
- The area underneath the unit may not be blocked or closed by any material
- The unit may only be operated in a calm environment
DANGER
Danger of explosion
Safety measures in case of smell of gas:
- Immediately close the gas supply.
- Don't touch any electrical switching element
- ventilation of the room.
- Avoid open flame or sparks
- Use an external telephone and inform your local gas authority (in case the local gas authority can not be reached inform the operation centre of the fire brigade).
- 3 - V-09 05/2014
Dear customer
The warranty excludes glass damage, light bulbs and sealing material as well as damage caused by improper use, installation, maintenance, repair by untrained/unqualified personnel and scaling of components
We reserve the right to make technical changes in the interest of progress!
© 2011 Rational Technical Services. All rights reserved. Please note that any technical information concerning Rational products must NOT be forwarded to any third party.
Dealer
Quote in the event of a query:
Appliance model:
Installer
Appliance no.:
______________________________________
Set to gas type:
______________________________________
Your appliance was checked by:
______________________________________
Safety stickers „Max. rack height for containers with liquid“ are in the Starter Kit.
After Installation of the unit, this sticker has to be fixed to the unit in a height of 1600 mm (see examples)
WARNING
Risk of scalding!
To avoid scalding, do not use loaded containers with liquids or cooking goods which becomes fluid by heating in higher levels than those which can easily be monitored. (DIN: IEC 60335-2-42)
V-09 05/2014 - 4 -
Installation instructions / Changing air filter
Attention:
The named standards are valid for Germany. In all other countries follow the local standards and valid instructions. Damages based on installation not complying with the directives given hereunder are not covered by warranty terms.
The requisite connections (water, electricity, gas) must only be carried out by suitably qualified technicians in compliance with local regulations.
Liability
Installation and repair works, not carried out by qualified personnel or not using original spare parts, as well as every technical change on the unit which were not authorised by the manufacturer will lead to an expiration of the warranty and the liability of the manufacturer.
The conformity of the unit references to the complete appliance at the time of shipment.
In case function extension and/or connection of additional functions are made the user is responsible for an extended conformity.
Australian Supplement to Gas Installation
- To be installed only by authorised person in accordance with AS 5601, local authority, gas, electricity, any applicable statutory regulations and manufacturer requirements.
- Particular attention should be given to relevant requirements regarding ventilation.
- This appliance is not suitable for use in marine environment.
Check for any transport damage.
Should there be any signs of transport damage, inform your dealer/freight forwarder immediately!
Cleaning of the unit body after installation:
With the cleaning cloth, attached to the door handle, the body of the unit can be cleaned.
As the cleaning cloth is soaked with cleaning agent it can not be used for cleaning of the door glass pane and the operator surface (also follow the hint on the packaging of the cleaning cloth).
Dumping of old units.
At the end of its service life, the unit must not be disposed of with the general waste and must not be placed in the recycling containers at local authority collection points.
We will be happy to help you with the disposal of your unit.
Changing air filter
In case the unit detects a polluted air filter, a message is shown that prompts the operator to change the filter.
When changing the filter the following procedure has to be observed:
Units 6x1/1GN, 6x2/1GN, 10x1/1GN and 10x2/1GN
Air filter article number: 40.03.461
The filter may be changed by the operator. The operator is responsible that the new filter is set in place correctly and that it is not allowed to run the unit without filter. For changing the filter follow the instruction in the operator manual.
Units 20x1/1GN and 20x2/1GN
The filter may only be changed by qualified technical personal
Attention, the hose water protection of 20x1/1GN and 20x2/1GN units is only ensured with correct installed air filter and protective cover.
- 5 - V-09 05/2014
First time commissioning
When commissioning your new unit for the first time, you will be asked to start an automatic self test. The duration of the self test is approximately 45 minutes and is necessary to adapt the unit to the specific environmental conditions.
- Remove packing material from the interior cabinet. Check air baffle and racks for correct positioning and fixing.
- Units 6X1/1, 10X1/1, 6X2/1 and 10X2/1 put a GN container (e.g. 20 mm deep) upside down into the center rail of the racks.
- Units 20X1/1 respec. 20X2/1 GN two containers have to be put into the mobile trolley of the unit. One container each upside down to the center in front of each fan wheel.
- Cabinet door must not be opened during the complete self test
6X1/1 / 10X1/1 / 6X2/1 / 10X2/1 GN
CAUTION
Start
45:00
Fire hazard!
Remove packing material, starter kit as well as containers and grids from interior cabinet.
close cabinet door
V-09 05/2014 - 6 -
20X1/1 / 20X2/1 GN
44:59
Start
Press Start-key, Self test is running, remaining running time is shown
Table of content
Installation Manual
Safety instructions
Dear customer
Installation instructions / Changing air filter
First time commissioning
Table of content
Transport of units
Recommended minimum clearance
Installation type 6x1/1, 6x2/1, 10x1/1, 10x2/1 GN
Installation Type 20x1/1 GN, 20x2/1 GN
Levelling mobile oven racks 20x1/1 and 20x2/1 GN
Electrical connection
Water connection
Selection of water filter
Gas connection
Gas exhaust connection
Gas connection / Gas consumption
Drain connection
Ventilation, technical data, heat emission
Option 26
Connected loads in accordance to VDE Guideline
Conversion tables
Schematic drawing 6x1/1 GN Electric
Schematic drawing 6x1/1 GN Gas
29
30
32
33
8
9
6
7
10
4
5
1
2
20
21
23
24
25
12
13
14
16
18
Schematic drawing 6x2/1 GN Electric
Schematic drawing 6x2/1 GN Gas
Schematic drawing 10x1/1 GN Electric
Schematic drawing 10x1/1 GN Gas
Schematic drawing 10x2/1 GN Electric
Schematic drawing 10x2/1 GN Gas
Schematic drawing 20x1/1 GN Electric
Schematic drawing 20x1/1 GN Gas
Schematic drawing 20x2/1 GN Electric
Schematic drawing 20x2/1 GN Gas
39
40
41
42
43
34
35
36
37
38
- 7 - V-09 05/2014
1
2
3
4
Transport of units
Center of Gravity o n t
F r o r
D o
2x2", 50x50mm
6x1/1 GN:
920mm/36 1/4"
6x2/1 GN:
1120mm/44 1/8"
10x1/1 GN:
920mm/36 1/4"
10x2/1 GN:
1120mm/44 1/8"
20x1/1 GN:
950mm/37 1/2"
20x2/1 GN:
1150mm/45 1/4"
20x1/1 GN:
920mm/36 1/4"
20x2/1 GN:
1140mm/45"
Transport of units
Transport of units using a pallet pic. 1,2
Transport of units without a pallet, 20x1/1 GN and
20x2/1 GN units only. Put a piece of wood between pallet jack and left guide rail of the trolley pic. 3, 4
CAUTION
Unit can tilt
Danger of injury
Make sure that the unit is secured against tilting, when transporting it.
Remove all containers/mobile oven racks from the cabinet. For floor model, remove corner mountings from the pallet. Take unit off the pallet.
CAUTION
Observe the weight of the units.
Danger of injury
Use carrying aid to avoid injuries.
Wear safety boots.
Weight see technical data on page 25
Observe door height pic. 5
X= Required door width when transporting units without pallet:
6x1/1GN
6x2/1GN
10x1/1GN
10x2/1GN
20x1/1GN
20x2/1GN
840 mm (33 1/8”)
1040 mm (41”)
840 mm (33 1/8”)
1040 mm (41”)
920 mm (36,1/4”)
1140-mm (45“)
5
20x1/1 GN /
20x2/1 GN:
1900mm/75"
X (6x1/1 - 20x2/1GN)
V-09 05/2014 - 8 -
Recommended minimum clearance
1
50mm/2"
Minimum clearance left/ right/ rear 50 mm (2”)
(except floor models). pic. 1
50mm/2" 50mm/2"
On floor models (20x1/1 GN and 20x2/1 GN) there must be a minimum clearance of 500 mm (approx.
20”) on the left side of the unit, for installing the power cable
Minimum clearance when there are heat sources on the left-hand side is 350 mm (14”). pic 2
2
≥ 350mm
14"
Attention:
A safety shut down can occur if the ambient temperature on the left hand side of the unit is too high.
Option:
Heat shield see page 26
3
50mm/2"
We recommend a distance of 500 mm (20”) on the left hand side of the unit for carrying out maintenance work. pic. 3
500mm/
20"
50mm/2"
4
Attention:
- Do not install deep fat fryer at the rear side of the unit.
- The units must only be installed in frost-free rooms.
- Should it not be possible to direct the exhaust air of the exhaust pipe into a ventilated ceiling or an exhaust hood an open space of 500 mm above the unit is required. This space is sufficient for installing a condensation breaker that can direct the exhaust air to an uncritical area.
(Condensation breaker see page 27) pic. 4
- 9 - V-09 05/2014
1
2
Installation type 6x1/1, 6x2/1, 10x1/1, 10x2/1 GN
Because of safety reasons table units shall only be installed on original stands of the manufacturer.
In this case the maximum rack height is 1600 mm
(63")
A 6x1/1 /10x1/1 GN: 745,5mm (29 3/8")
6x2/1 10x2/1 GN: 965,5mm (38")
A
64,5mm
2 5/8"
+_ 10mm
64,5mm
2 5/8"
If Gas units are installed on a table or on the kitchen floor (combi duo) then: a) press the retaining plates (ET-No.:12.00.519) into the lower part of the pedestal and fasten with the enclosed nuts.
b) the plate must be fitted to the surface using either screws and dowels or studs and nuts or the
special adhesive.
The retaining plates are not included in the pic. 1 scope of supply
Attention: The centre height of the drain pipes 88 mm (3 1/2”). When installing combi duo observe the drain height of the bottom unit.
3
+_ 10mm
4
5006.0213
Option:
Using 110 mm (4 3/8”) legs and height adjustable transport trolley for extended space underneath unit.
See page 26
Stands for gas appliances must be fixed to the floor using the fixing set part no.: 8700.0317 either with screws and dowels, or with the special adhesive supplied.
Fixing set is not included in the scope of supply, pic. 2
Slide the stand into the fixing brackets and level it.
Place the unit on the stand. The feet of the unit must be secured by means of the locating pins of the stand pic. 3
Ensure that the unit is level pic. 4
V-09 05/2014 - 10 -
Installation type 6x1/1, 6x2/1, 10x1/1, 10x2/1 GN
1
Attention:
If the unit is mounted on a mobile stand or base cabinet, the unit must be additionally secured against slipping by a chain or cable in order to prevent damage to the electricity, water or gas supply line. pic. 1
- 11 - V-09 05/2014
1
Installation Type 20x1/1 GN, 20x2/1 GN
Installation type 20x1/1 GN, 20x2/1 GN
Ensure that the unit is level pic. 1
2
+_ 10mm
A 20x1/1 GN: 732,5 mm / 28 7/8"
20x2/1 GN: 937,5 mm / 37"
A
64,5mm
2 5/8"
64,5mm
2 5/8"
3
5006.0213
4
Fix the floor locks, (supplied with the fixing set) to the floor with either screws and pins or with the special adhesive. pic. 2
Next slide the unit into the floor locks pic. 2
The mobile oven rack must be level when standing inside the unit pic. 3
Attention: Observe height of the drain pipe
Option:
Using leg extension for more space underneath unit.
Install height extension for mobile oven rack see page
27
For a safe storing of the trolley handle, during cooking, an angle bracket is delivered with the unit. This angle bracket has to be mounted to the left side panel of the unit. For mounting remove the left side panel and slide the angle bracket on the top edge of the panel to the middle.
Now the handle can be stored at the unit pic. 4
V-09 05/2014 - 12 -
Levelling mobile oven racks 20x1/1 and 20x2/1 GN
1
If the floor is not level, an access ramp (not supplied) will be required. The incline must not exceed 4°. pic. 1,2
WARNING
Hot cooking liquid
Risk of scalding
If the incline exceeds 4°, hot cooking liquid can slop out of the cooking containers
2
Attention:
An incorrect levelled trolley can cause malfunction during operating the unit (e. g. during Cleanjet)
Set unit legs that a height of 200 mm (7 7/8") is reached pic. 2 "A"
Valid for SCC_WE units:
Check unit door for tightness by activating cleaning program "rinse without tabs"
3
200mm
(7 7/8 “)
A
4 max 4
Option:
Access ramp see page 27
If there is a drain grill in front of the floor unit, a ramp should be placed over it to enable the mobile oven rack to be used. pic. 3
Attention:
Avoid steam sources in the ambient area of the air filter. Sucked in humidity can cause malfunction to the unit.
Because of hygienic reason and following the "NSF standard 4" respectively "DIN EN 203-3" all units
20x1/1 GN respectively 20x2/1 GN must be equipped with a cover over ball valve and care pump. pic. 4
Cover kit and corresponding installation instruction are delivered with the unit
- 13 - V-09 05/2014
1
Electrical connection
5 mm
2
L
1 L
2 L
3 N
3
4
DANGER
High voltage
Danger to life
Observe local regulations and standards during installation
General information see next page
Electrical units
• Each appliance requires an independent fused power supply line
• A permanent electrical connection must be provided for the units.
Units 6X1/1GN - 20X2/1GN
Voltage version 3NAC 400V
Units can either be connected permanent or by using a plug
• Table units (6X1/1 GN - 10X2/1 GN) are equipped with a power cable. The cable comes without plug and is approx. 2,5 m (8 ft) long.
WARNING
Wrong connection can cause electric shock
Danger to life
Observe colour coding of the wires
Attention:
Wrong connection can cause damages (e. g. fan motor)
• Colour coding of wires:
yellow/green = earth
blue = neutral
brown, grey or black = Phase L1, L2, L3
• Floor units 20X1/1 GN and 20X2/1 GN are delivered without power cable
• The main contactor (table units) and the main terminals (floor models) are located in the electrical compartment and are accessible after removing
the left side panel. pic. 1/2
V-09 05/2014 - 14 -
Electrical connection
Gas units
• We recommend an independent fused power supply line.
• A permanent electrical connection must be provided for the units.
• All units are equipped with a power cable without plug, approx. 2,5 m (8 ft) long.
• The main terminals are located in the electrical compartment and are accessible after removing
the left side panel. pic. 1/2
• Unit should be connected to a fused spur, observe local electrical regulations
• Attention!
Observe polarity of the mains!
No burner function with wrong polarity!
• The appliance is equipped with a motor with an integrated frequency converter
• On-site installation: provide accessible all-pole disconnection device with a minimum of a 3 mm contact gap.
• Electric units 10x2/1, 20x1/1 and 20x2/1GN:
The maximum electrical impedance at the mains connection point is 0,09 ohm
• Special voltages available on request.
• The cross-section of the power cables must be based on the current consumption and on local regulations.
• Applicable standards: EN 60335, IEC 335
• For electrical connection data, see page 29
• Before disconnecting or reconnecting unit. Ensure electrical supply is isolated.
• The circuit diagram is located on the inner side of the left side panel.
Danger to life
WARNING
Wrong connection can cause electric shock
Observe colour coding of the wires
For appliance connections, precise dimensions and connection points, see pages 32 and following.
motor)
Attention:
Wrong connection can cause damages (e. g. fan
• Colour coding of the power cable: yellow/green = earth, blue = Neutral brown, grey or black = Phase L1 (L2)
Gas and electrical units
The stud of the equipotential bonding is located on the bottom side, underneath the control panel. Connect the wire of the equipotential bonding to this stud pic. 3/4
General information:
• Follow the installation instructions and the information on the rating plate when connecting the unit.
• Comply with all local regulations and standards!
• We recommend an independent fused power supply line for each appliance.
• Units must be connected to an earth leakage circuit breaker.
Power cable :
• The exchange of the power cable may only be carried out by the manufacturer, his service agents or similar qualified personal
Electrical units
• Connect an H07RN-F supply cable (minimum), tighten the cable gland and the strain relief
• Connect the supply as follows:
Grey terminal: L1, L2, L3 (non-phase-sequencedependent)
Blue terminal: Neutral (only 3N AC)
Yellow/green terminal: Earth connection
Gas units:
• Units the power cable has to be exchanged a power cable with the following minimum quality has to be used:
H05 RN-F 3x2,5 mm2
- 15 - V-09 05/2014
1
Water connection
6x1/1GN - 10x2/1GN E/G
2
3
2
1
20x1/1GN - 20x2/1GN E/G
3
1 2
The appliance must be connected to water with drinking water quality. We recommend a maximum water temperature of 30°C.
pic. 1 Legend to water connections valid for :
- SelfCookingCenter® 5Senses table units
1 = Common water supply 3/4” cold water
In case of split water connection
2 = Cold water, connection 3/4” (quenching)
3 = Treated water connection 3/4”
(steam generator, moistening, cleaning, hand shower,)
Legend to water connections valid for:
- SelfCookingCenter® 5Senses floor units
1 = Common water supply 3/4” cold water
In case of split water connection pic. 2
2 = Cold water, max 30°C/86°F, connection 3/4”
(quenching)
3 = Treated water connection 3/4”
(steam generator, moistening, cleaning, hand shower,)
The appliance is to be connected to the water supply using a flexible supply hose. Possible backflow protection devices such as check valves have to be installed directly at the water tap.
The appliance must be connected to the facility water supply with a supply hose that conforms to EN 61770 resp. IEC 61770 or of similar quality.
The water supply hose must fulfil the local or standard hygiene requirements for hoses in drinking water systems.
For water connection only new supply hoses may be used. Old supply hoses must not be reused.
A water supply hose conform to EN 61770 with
DVGW drinking water approval can be ordered at
RATIONAL (# 2067.0709).
V-09 05/2014 - 16 -
Water connection
UK only:
WRAS approval IRN R160
To be carried out by the installer:
An approved double check valve or some other no less effective backflow prevention device shall be fitted at the point of connection directly to the water tap.
• Install individual shut-off valve for each appliance
• Rinse the water supply line prior to connection to the unit!
• Connected water pressure must be in the range
150 kPa - 600 kPa, recommended 300 kPa
Maximum flow rate for each unit
6x1/1, 10x 1/1: 20 l/min
6x2/1, 10x2/1, 20x1/1, 20x2/1: 25 l/min
Note:
The manufacturer recommends especially on model
CombiMaster® Plus a preventive check of your equipment 6 months after installation to determine actual scale build up. This should be done by a trained technician.
Water treatment:
For filter selection see pages 18/19
Treated water with a water hardness less than 6 °e may not be supplied, because such water can react aggressive and corrosive which can reduce the life cycle of the unit.
Connecting SelfCookingCenter® 5Senses to water with hardness less than 8,75°e:
When starting the self test (refer to page 6) the customer can choose between two different levels of water hardness. In this case select "water with hardness less than 8,75°e":
- 17 - V-09 05/2014
1
2
3/4"
Selection of water filter
30°C/86°F
300 kPa
43,5 psi
E
R
T
L
I
F
300 kPa
43,5 psi max. 30°C/86°F
30°C/86°F
300 kPa
43,5 psi
150-600kpa
21,75-87 psi
A B C D
1/2"
3/4"
R 3/4" max. 30°C max. 86°F
2
3
1/2"
R3/4"
In most cases it is not necessary to install a filter or water treatment for water supply. The integrated SCautomatic changes the water in the steam generator at regular intervals automatically.
However under certain water conditions different filter applications (A, B, C, D) might be necessary.
Please consult your local water supply board for advise on chlorine (Cl2), chloride (Cl-) and hardness of the water
A) Particle filter pic. 1/2
When the water contains sand, iron particles or suspended matter, we recommend a 5-15 µm
(micro meter) particle filter:
B) Active carbon filter pic. 1/2
When the level of chlorine (Cl2) in the water exceeds 0.2 mg/l (= ppm) (information available from the water company), an active carbon filter should be installed.
C) Complete De-Ionization pic. 1/2
When the water has a chloride Cl- concentration above 80 mg/l (= 80 ppm), a complete deionization system should be installed to avoid corrosion.
Note: Make sure a minimum conductivity of 50 µS/ cm (micro Siemens) remains in the water.
D) Water softener:
Valid for SelfCookingCenter® 5Senses pic. 1/2
These models will remove scale all by itself providing that the units are used as prescribed. This means a water softener is not needed.
Valid for CombiMaster® Plus:
A water softener is recommended when a high level of scale (not containing chloride) is experienced. Systems recommended: H
+
Ion Exchanger.
Sodium ion exchangers (as used in dishwashers) must not be used.
As a phosphate dosing system can have negative influence to the water system it must also not be used.
Treated water with a water hardness less than 6
°e may not be supplied, because such water can
V-09 05/2014 - 18 -
Selection of water filter
react aggressive and corrosive which can reduce the life cycle of the unit.
Amongst others the following filter manufacturers offer adequate filter applications:
Brita, Falk.
Important for treated water connection:
Split the water supply to standard and treated water connection for each unit to extend filter capacity!
See pictures 1/2 page 16
Remove T-connection at water inlet
Connect cold untreated water to inlet position “2”
Connect treated water to inlet position “3”
Filter capacity:
Average treated water consumption is as follows
(values excluding usage of hand shower)
6x1/1 6x2/1 10x1/1 10x2/1 20x1/1 20x2/1
3l/h 8 l/h 6,3 l/h 10,4 l/h 12,5 l/h 15 l/h
Maximum flow rate 16 l/min
Important for filter connection:
Water supply hose / pipe size 1/2” minimum
Connection to filter : 3/4”
If a combination of filters is fitted, the sequence A-B and C or D of the filters in the direction of flow must be observed pic. 2
- 19 - V-09 05/2014
Gas connection
Important!
To ensure that the burner settings made at the factory conform with the actual installation conditions, the waste gas (C0, C02) from the steam and hot-air burners must be analysed during commissioning. The corresponding values must be documented inside the unit. If the undiluted C0 values are above 1000 ppm, the burner settings must be checked and if necessary adjusted by engineers trained and certified by the company.
1
2
3
6x1/1 GN: 3/4"
6x2/1 GN: 3/4"
10x1/1 GN: 3/4"
10x2/1 GN: 3/4"
RATIONAL
! mbar
20x1/1 GN: 3/4"
20x2/1 GN: 3/4"
! mbar
WARNING
Incorrect connection can engender fire hazard!
Danger to life
Observe local regulation
Comply with local gas authority regulations!
Follow installation instructions!
• Check that the gas type supplied is suitable for the unit.
• The diameter of the pipe must comply with local regulations
• Inner thread of gas connection: pic. 1,2
• Gas stop valve supplied for each unit.
• Gas connection with gas outlet socket is possible.
• All gas supply connectors must comply with local regulations.
• The unit must be secured against movement.
• Check the gas supply and gas distribution in the
unit line for leakage. pic. 3
• For documentation of the correct installation our installation checklist can be used.
• Automatic direct ignition with ignition monitor.
Attention:
• The unit is only to be connected to the gas supply by a locally approved gas installer. It is vital to ensue that the gas connection pipes as well as the connection pipes for the associated gas metering systems match the stipulated pipe widths.
• If the flow pressure deviates from the specified flow pressure (see table), inform the gas authorities. If the flow pressure of natural gas exceeds 30 mbar
(12,04 in w. c.), the unit must not be switched on and the gas supply must be disconnected.
• Attention: The gas parts are designed for a maximum flow pressure of 65 mbar (26,09 in w. c.)
V-09 05/2014 - 20 -
Gas exhaust connection
Type A3, B13, B13BS gas unit
Comply with local gas authority regulations!
DANGER
Gaseous combustion product (CO and CO
2
)
Suffocation hazard
The rooms in which these appliances are installed must be well ventilated, in order to prevent an unacceptable build-up of harmful combustion products.
4
5
Vented hood
Vented ceiling
A3 – 6x1/1GN pic. 4
Room air-dependent gas appliance with blower before burners, without draft diverter and rated thermal load < 14 kW. It is not mandatory for the gas delivery to be released to the burners only when the exhaust system is operative.
An up draft system is not required.
When installing gas appliances type A with a total nominal heat load up to 14 kW it is sufficient, if
- the room volume of the installation site is above
2 m³/kW, or
- a door or window to the outside which can be opened is available, or
- a kitchen ventilation system with a minimum discharge volume of 15 m³/h per kW total nominal heat load is used and suitable openings for fresh air are installed.
For UK market can be used when replacing similar equipment in kitchens where installation of the air inlet/extraction was prior to September 2001 & providing there is a documented risk assessment to ensure that there will always be sufficient make-air and extraction available when running the equipment.
Please observe Current Gas Regulations.
Vented hood
Vented ceiling made sure, that the gas supply of the burner is only enabled in case the ventilation is ensured.
Required room volume see page 23
B13 pic. 6
A3 – 10x1/1, 6x2/1, 10x2/1, 20x1/1, 20x2/1 GN pic. 5
Room air-dependent gas appliance with blower before burners, without draft diverter and rated thermal load > 14 kW.
An up draft system is not required.
Flue gases must be lead to the outside using a kitchen venting system. Thereby flue gases of type
A gas appliances are blown into the kitchen air and immediate sucked out by the kitchen venting system.
By monitoring the flue gas evacuation it must be
- 21 - V-09 05/2014
Gas exhaust connection
6
7
8
400mm
6x1/1 / 10x1/1GN
180 mm
7 1/4”
Vented hood
230 mm
400mm
Vented ceiling
6x2/1, 10x2/1, 20x1/1, 20x2/1GN
180 mm
7 1/4”
320 mm
Ambient-air-dependent gas-powered cooking range with fan assisted burners with exhaust collector.
The type B13 installation must only be done using the below mentioned original exhaust collector. The exhaust collector is not shipped with the unit, but can be ordered under the following part numbers:
6x1/1 70.00.737
10x1/1 70.00.757
6x2/1 70.00.768
10x2/1 70.00.769
20x1/1 70.00.770 20x2/1 70.00.771
For installation please follow the installation instruction sheet of the exhaust collector.
Observe that in case of B13 installation an up draft system must be provided
Up draft system shall end 400 mm below the fat filter. The unit must be installed underneath a vented hood/ceiling.
By monitoring the flue gas evacuation it must be made sure, that the gas supply of the burner is only enabled in case the ventilation is ensured.
Required room volume see page 23
B13BS
Fixed connection to chimney is permissible.
pic. 7
For calculating the necessary supply and exhaust air contact your local gas or responsible authority
Gas exhaust system
• Check that gas exhaust pipes are leak proof, in accordance with local regulations
• Waste gas pipes of aluminium or other materials which are not resistant to temperatures up to
400°C should not be used because of the high waste gas temperatures!
Draft diverter needed for B13 and B13BS pic. 8
The gas exhaust system connected to the draft diverter has to be designed in such a way that a constant draft will be maintained. In case of a back flow the safety temperature limiter (set to 103°C) of the draft diverter will disengage.
V-09 05/2014 - 22 -
Gas connection / Gas consumption
Maintenance
- We recommend to service the gas units at least once a year in accordance with the specified standards.
- After maintenance or repair works the compensation hose of the gas valve has to be checked for tight fit.
- After maintenance or repair works a leak test of all gas components has to be carried out.
Gas consumption
Gas type Required flow
Wobbe index max. consumption on nominal heat load
(15°C, 1013mbar) pressure Wi Ws 6x1/1 GN
MJ/m
3
MJ/m
3
13 kW
Nat. gas H G20 18-25 mbar 45,67 50,72 1,4 m
3
/h
Nat. gas L G25 20-30 mbar 37,38 41,52 1,63 m
3
/h
MJ/m
3
MJ/m
3
14 kW
6x2/1 GN
28 kW
3,05 m
3,53 m
31 kW
3
3
/h
/h
LPG G30 25-57,5 mbar 80,58 87,33 1,22 kg/h
MJ/m
3
MJ/m
3
13 kW
LPG G31 25-57,5 mbar 74,75 81,19 1,08 kg/h
2,66 kg/h
28 kW
2,33 kg/h
Gas type
Nat. gas H G20
Nat. gas L G25
Required
18-25 mbar
20-30 mbar
Wobbe index max. consumption on nominal heat load flow pressure
(15°C, 1013mbar)
Wi Ws 10x2/1 GN
MJ/m
3
MJ/m
3
45 kW
45,67
37,38
50,72 4,87 m
3
/h
41,52 5,76 m
3
/h
20x1/1 GN
44 kW
4,77 m
5,58 m
3
3
/h
/h
MJ/m
LPG G30 25-57,5 mbar 80,58
3 MJ/m
87,33
3 50 kW
4,31 kg/h
MJ/m
3
MJ/m
3
45 kW
LPG G31 25-57,5 mbar 74,75 81,19 3,76 kg/h
48 kW
4,15 kg/h
44 kW
3,69 kg/h
10x1/1 GN
22 kW
2,35 m
3
/h
2,76 m
3
/h
24 kW
2,09 kg/h
22 kW
1,84 kg/h
20x2/1 GN
90 kW
9,86 m
3
/h
11,36 m
3
/h
100 kW
8,56 kg/h
90 kW
7,56 kg/h
Australian Supplement to Gas Installation
Unit size SCC_WE /CMP
Heat Load
Minimum inlet pressure NG
Minimum inlet pressure LPG
61 62 101 102 201 202
47 MJ/h
1.0 kPa
2.75 kPa
Note: Maximum inlet pressures for NG and LPG: 5kPa
101 MJ/h
1.0 kPa
2.75 kPa
79 MJ/h
1.0 kPa
2.75 kPa
162 MJ/h
1.0 kPa
2.75 kPa
158 MJ/h
1.0 kPa
2.75 kPa
324 MJ/h
1.0 kPa
2.75 kPa
Flue gas- and room volume (values are valid for single units)
Free ventilation = Combustion air supply through windows and doors
Permanent ventilation = Combustion air supply by two openings to the outside with a free cross section of
150 cm
2
(one opening near the ceiling, the other opening near the floor)
Attention: Data are calculated under German standards
Unit size 6x1/1GN 6x2/1GN 10x1/1GN 10x2/1GN 20x1/1GN 20x2/1GN
Room size free ventilation 52 m
3
112 m
3
88,0 m
3
180 m
3
176 m
3
360 m
3
Room size permanent ventilation 26,0 m
3
56,0 m
3
44,0 m
3
90,0 m
3
88,0 m
3
180 m
3
Combustion air supply
Flue gas volume
Flue gas temperature
19 m
38 m
3
3
/h 45 m
3
/h 108 m
/h 35 m
3
/h 78 m
3
3
/h
/h
72 m
3
180 m
/h
3
70 m
3
/h 150 m
/h
3
144 m
/h 350 m
3
3
/h
/h
- 23 - V-09 05/2014
1
2
3
Drain connection
200-300mm
(8 - 12 “)
250-300mm
(10 - 12 “)
3x45° min. 3° / 5%
Ø 50mm (2”) max. 1m
(3 ft.)
70mm
(2 3/4“) min. 3° / 5%
Ø 50mm (2”) max. 1m
(3 ft.)
• The appliance complies with the relevant regulations (EN 1717, SVGW, KIWA, WRAS)
Attention
Use pips capable of withstanding steam temperature, don't use hoses
• Drain/water connection set
Art. no.: 60.70.464
• Welding of drain pipe to the units drain is not permissible (welding can cause damages to the unit)
• DN 50 pipe with constant gradient (min. 5% or 3°); do not reduce the diameter of the pipe.
• Fixed connection with odour lock permissible; a ventilated drain line is integral to the appliance pic. 1,2
• Where there is an existing floor drain without air trap, a clear outflow of 2 cm
(1”) must be provided. pic. 3
• We recommend to connect every unit to a separate drain.
• We recommend to install a syphon in the drain system of the unit, to reach an optimized energy consumption.
• Units 6x1/1GN up to 10x2/1GN can be connected either to a wall drain or to a floor drain
• Units 20x1/1GN or 20x2/1GN can only be connected to a floor drain.
Option:
For reduction of steam escape via the ventilation pipe a condensate collector or an additional ascending pipe can be used. See pages 27/28
Option table models:
Using 110 mm (approx. 4”) legs for extended space underneath unit. Height adjustable transport trolley, see page 26
Option floor models:
Using leg extension for more space underneath unit.
Install height extension for mobile oven rack see page
27
V-09 05/2014 - 24 -
Note drainage dimensions: short-term pumped discharge volume of steam generator 0.7 l/sec (0,18 gal/sec.)
• Average waste water temperature: 65°C
• Applicable standard: DIN 1986, Part 1
Attention: The centre height drain pipe of table models is 88 mm and floor models is 70 mm.
Ventilation, technical data, heat emission
Ventilation:
An exhaust hood is not essential. If one is fitted, bear the following points in mind:
• Comply with all local regulations and standards;
• The hood should project 300-500 mm (1-1,6 ft) in front of the appliance;
• Install a grease filter in the projecting part of the hood;
• An exhaust hood is available as an option for 6x1/1 - 20x1/1 GN units.
• For installation of the hood, please follow the instruction of the corresponding installation manual
• In case the VarioSmoker is used in the unit, then the unit has to be installed under hood in accordance with local and on state jurisdictions
DANGER
Flue gases (CO and CO
2
)
Suffocation hazard
The rooms in which these appliances are installed must be well ventilated, in order to prevent an unacceptable build-up of harmful flue gases.
Technical data:
Noise emission level: <70dBA Hoseproofness: IPX5
Heat emission:
Electrical units: latent: sensible:
6x1/1 GN 6x2/1GN 10x1/1 GN 10x2/1 GN 20x1/1 GN 20x2/1 GN
2.143 kJ/h 4.167 kJ/h 3.529 kJ/h 6.667 kJ/h 7.200 kJ/h 12.500 kJ/h
2.727 kJ/h 5.000 kJ/h 4.615 kJ/h 9.474 kJ/h 9.000 kJ/h 14.286 kJ/h
Gas units: latent: sensible:
6x1/1 GN 6x2/1GN 10x1/1 GN 10x2/1 GN 20x1/1 GN 20x2/1 GN
2.143 kJ/h 4.167 kJ/h 3.529 kJ/h 6.667 kJ/h 7.200 kJ/h 11.583 kJ/H
2.571 kJ/h 5.000 kJ/h 4.286 kJ/h 9.231 kJ/h 8.780 kJ/h 13.636 kJ/H
Weight of electric units:
SCC units:
6 x 1/1 GN: 112,5 kg
10 x 1/1 GN: 132,5 kg
20 x 1/1 GN: 267,0 kg
Mobile:
20 x 1/1 GN: 275,5 kg
6 x 2/1 GN: 148,5 kg
10 x 2/1 GN: 173,0 kg
20 x 2/1 GN: 346,0 kg
20 x 2/1 GN: 352,0 kg
CM units without
6 x 1/1 GN: 105,5 kg
10 x 1/1 GN: 125,5 kg
20 x 1/1 GN: 259,0 kg
20 x 1/1 GN: 269,0 kg
6 x 2/1 GN: 141,5 kg
10 x 2/1 GN: 166,0 kg
20 x 2/1 GN: 338,0 kg
20 x 2/1 GN: 346,0 kg
Weight of gas units:
SCC units:
6 x 1/1 GN: 127,0 kg
10 x 1/1 GN: 149,5 kg
6 x 2/1 GN: 169,5 kg
10 x 2/1 GN: 203,5 kg
20 x 1/1 GN: 297,5 kg
Mobile:
20 x 1/1 GN: 303,5 kg
20 x 2/1 GN: 374,5 kg
20 x 2/1 GN: 390,5 kg
CM units without
6 x 1/1 GN: 121,0 kg
10 x 1/1 GN: 143,5 kg
20 x 1/1 GN: 288,0 kg
20 x 1/1 GN: 278,5 kg
6 x 2/1 GN: 163,5 kg
10 x 2/1 GN: 197,5 kg
20 x 2/1 GN: 364,5 kg
20 x 2/1 GN: 389,5 kg
Right of technical modifications reserved.
- 25 - V-09 05/2014
2
3
1
Option
50 mm
V-09 05/2014 - 26 -
Heat shield left and right
If the minimum required distance to heat sources on the left or right side (right side only 6x1/1 GN and
10x1/1 GN) can not be maintained a heat shield will help to reduce the heat stress to the unit
Unit size:
6x1/1GN
6x1/1GN
10x1/1GN
Art.-No.: 60.70.390 left
Art.-No.: 60.70.736 right
Art.-No.: 60.70.391 left pic 1
10x1/1GN
6x2/1GN
10x2/1GN
20x1/1GN
20x2/1GN
Art.-No.: 60.70.743 right
Art.-No.: 60.70.392
Art.-No.: 60.70.393
Art.-No.: 60.70.394
Art.-No.: 60.70.395
Height extension of table units.
(6x1/1 GN up to 10x2/1GN)
Should the distance between floor and bottom of table units be too low (e.g. when installing combi duo), then the standard lower parts of the legs can be replaced by longer legs (110 mm).
Art.-No.: 12.00.224 pic. 2
Attention: In this case the height of the upper rail in the cooking cabinet exceeds 1600 mm (63”)
When using mobile oven racks and transport trolleys the height difference can be compensated by a height adjustable transport trolley. pic. 3
Height adjustable trolley:
Unit size: Art.-No.:
6x1/1 and 10x1/1 GN 60.60.188
6x2/1 and 10x2/1 GN 60.70.160
Option
1
2
3
4
460mm
(18”)
Foot extension for floor units
Art.-No.: 60.21.179
Should the distance be too low between floor and bottom of floor units , foot extensions for floor units can be used pic 1
Attention: In this case the height of the upper rail exceeds 1600 mm (63”).
When using these foot extensions a height compensation of the mobile oven rack must be carried out by adding an additional frame. pic. 2
20x1/1GN Art.-No.: 60.21.184
20x2/1GN Art.-No.: 60.22.184
Ramp for mobile oven rack floor models
If the floor underneath the unit is not level the mobile oven rack ramp can level out this uneveness. The adjustment range of the legs is between
+/- 10 mm .
20x1/1GN Art.-No.: 60.21.080
20x2/1GN Art.-No.: 60.22.181
pic. 3
Condensation breaker
Attention:
Extending the unit's vent pipe without using a condensation breaker can cause malfunction.
By installing the condensation breaker together with the enclosed pipes it is possible to guide the steam to an uncritical area or to the suction area of a pic 4 suction system (e.g.vent ceiling)
The kits contain the following:
Condensation breaker (depends on unit size)
Elbow DN75 with 45° angle (stainless steel)
Pipe DN75, 250 mm long (stainless steel)
Unit size:
61, 101, 062:
Art. Number
60.72.591
102: 60.72.592
201, 202: 60.72.593
- 27 - V-09 05/2014
1
Option
2
8 mm
1/8"
Also for reducing the steam escape at the drain pipe an additional vent pipe can be fitted to the drain pipe. In this extra vent pipe holes must be drilled where air is sucked in and condensates the steam pic 1/2
Interfaces a) Optional all CombiMaster® Plus can be retrofitted with an Ethernet interface b) SelfCookingCenter® 5Senses are equipped with an Ethernet interface as a standard.
Show mode units (operator panel active, heating and fan motor are continuously off)
For converting units into show mode units a modification instruction is available at
RATIONAL
Output for connecting an external signal appliance (optional only electric units)
If the unit is ordered with option „external signal appliance“, in the unit (electric compartment) a 230V-output is provided. This output is controlled parallel to the loud speaker respectively buzzer of the unit. For connection of the external signal appliance the additional terminals grey (phase), blue (neutral) and yellow/green (ground) are installed in the electric compartment, also refer to wiring diagram of the unit.
Attention:
External signal appliances must not be fixed on the unit.
V-09 05/2014 - 28 -
Connected loads in accordance to VDE Guideline
SCC_WE, CM_P Electric units:
3
6x1/1 6x2/1 10x1/1 10x2/1 20x1/1 20x2/1 6x1/1 6x2/1 10x1/1 10x2/1 20x1/1 20x2/1
200V 10,1 20,7 17,2 34 34,3 62,3 29,8 59,1 49,5 97,6 99 182
AC
3
3
NAC
3
3 480V 11,2 22,3 18,6 36,7 37 67,3 13,4 26,7 22,3 44 44,7 80,9
1
240V
48.3
12 50
2 AC 230V 11,2
2 AC 240V 11,2
48.3
47
Fuse protection = A
6x1/1 6x2/1 10x1/1 10x2/1 20x1/1 20x2/1
3 AC 200V 35 63 63 100 100 200
3 AC 230V 32 63 63 100 100 200
NAC
3
NAC
3
3
1 NAC 230V 50
1 NAC 240V 50
2 AC 230V 50
2 AC 240V 50
SCC_WE, CM_P Gas units:
Power
6x1/1 6x2/1 10x1/1 10x2/1 20x1/1 20x2/1 6x1/1 6x2/1 10x1/1 10x2/1 20x1/1 20x2/1
1NAC 100V
1NAC
0,4 0,5 0,95 4 5 9,5
110V 0,4 0,5 0,95 3,7 4,5 8,7
120V 0,4 0,5 0,95 3,4 4,2 7,9
1NAC
1NAC 220V 0,4 0,77 0,5 0,8 0,95 1,6 1,8 3,5 2,3 3,7 4,3 7,3
1NAC 230V 0,4 0,77 0,5 0,8 0,95 1,6 1,74 3,35 2,17 3,48 4,13 6,96
1NAC 240V 0,4 0,77 0,5 0,8 0,95 1,6 1,66 3,21 2,1 3,33 3,96 6,66
2 AC 200V 0,4 0,77 0,5 0,8 0,95 1,6 2 3.85 2,5 4,0 4,75 8
2 AC 220V 0,4 0,77 0,5 0,8 0,95 1,6 1,8 3,5 2,3 3,7 4,3 7,3
2 AC 230V 0,4 0,77 0,5 0,8 0,95 1,6 1,74 3,35 2,17 3,48 4,13 6,96
2 AC 240V 0,4 0,77 0,5 0,8 0,95 1,6 1,66 3,21 2,1 3,33 3,96 6,66
The maximum allowable tolerance of the supply voltage (supply voltage see name plate) is in the range of -15% up to +10%
- 29 - V-09 05/2014
Conversion tables
1 °dH
°dH
1
°f
1,79
°e
1,25 ppm
17,9 mmol/l gr/gal(US) mval/kg
0,1783 1,044 0,357
1 0,56 1 0,70 10,0 0,1 0,584 0,2
1 0,8 1,43 1 14,32 0,14 0,84 0,286
1 ppm
1 mmol/l
0,056
5,6
0,1
0,001
0,07
0,0007
1
100
0,01
1
0,0584 0,02
0,00058 2
1 gr/gal (US)
1
0,96 mval/kg
1,71 1,20 17,1 0,171 1 0,342
1
1 °dH: 10,00 mg CaO/kg
(Germany) 17,86 mg CaCO
3
1 ppm :
/kg (USA)
1 °f :
7,14 mg Ca
2
+
/kg
5,60 mg CaO/kg 1 mmol/l :
(France) 10,0 mg CaCO
1 °e :
(GB)
4,00 mg Ca
2
+
3
/kg
/kg
8,01 mg CaO/kg
14,3 mg CaCO
5,72 mg Ca
2
3
/kg
+
/kg
0,56 mg CaO/kg
1,0 mg CaCO
0,40 mg Ca
2
+
3
/kg
/kg
56,00 mg CaO/kg
(chem. conz.) 100,0 mg CaCO
3
39,98 mg Ca
2
+
/kg
/kg
1 mval/kg : 28,00 mg CaO/kg
(Milliäquivalent) 50,0 mg CaCO /kg
19,99 mg Ca
2
+
3
/kg
1 gr/gal : 9,60 mg CaO/kg
(USA) 64,8 mg CaCO
3
17,11 mg CaCO
3
6,85 mg Ca
2
/gal
+
/kg
/kg
kPa mbar psi inch/wc
0,1 1 0,0147 0,4014
0,2 2 0,0294 0,8028
0,3 3 0,0441 1,2042
0,4 4 0,0588 1,6056
0,5 5 0,0735 2,0070
0,6 6 0,0882 2,4084
0,7 7 0,1029 2,8098
0,8 8 0,1176 3,2112
0,9 9 0,1323 3,6126
1 10 0,147 4,0140
1,2 12 0,1764 4,8168
1,4 14 0,2058 5,6196
1,6 16 0,2352 6,4224
1,8 18 0,2646 7,2252
2 20 0,294 8,0280
2,5 25 0,3675 10,0350
3 30 0,441 12,0420
3,5 35 0,5145 14,0490
V-09 05/2014 - 30 -
kPa mbar psi inch/wc
4 40 0,588 16,0560
4,5 45 0,6615 18,0630
5 50 0,735 20,0700
5,5 55 0,8085 22,0770
6 60 0,882 24,0840
6,5 65 0,9555 26,0910
7 70 1,029 28,0980
7,5 75 1,1025 30,1050
8 80 1,176 32,1120
8,5 85 1,2495 34,1190
9 90 1,323 36,1260
9,5 95 1,3965 38,1330
10 100 1,47 40,1400
20 200 2,94 80,2800
30 300 4,41 120,4200
40 400 5,88 160,5600
50 500 7,35 200,7000
100 1000 14,7 401,4000
- 31 - V-09 05/2014
Schematic drawing 6x1/1 GN Electric
50
V-09 05/2014
782
125
88 [3-1/2]
72 [2-7/8]
n
4 43
50 n
370
8
4 83
715
552
8 80
120
~
R531
88 n
1 2 3
120
4 400
340 [13-3/8]
~
110
R531
[ 21
]
- 32 -
Schematic drawing 6x1/1 GN Gas
50
2 88
72 [2-7/8]
782
125
88 [3-1/2]
n
107
-3/8
03 [2 n6
4 43
370
845 [3-3/8]
50 n
4 83
552
/2
88 n
8 80
120
~
R531
-1/ 4 488
120
4 400
340 [13-3/8]
~ R
531
[ 20-7/8
]
- 33 - V-09 05/2014
Schematic drawing 6x2/1 GN Electric
50
782
125
84 [3-3/8]
72 [2-7/8]
n
50
4 44 n
475
75
915
764
88 n
76
120
~
R737
8 129
2 445
385 [15-1/8]
~
110
R737
[ 29
]
V-09 05/2014 - 34 -
Schematic drawing 6x2/1 GN Gas
2 88
72 [2-7/8]
782
125
84 [3-3/8]
3 [2-3/8 n60
135
4 44
50 n
2 139
475
75
764
2
88 n
76
120
~
7
R73
50
8
425
129
2 445
385 [15-1/8]
~
110
R73
7
[ 29
]
n
- 35 - V-09 05/2014
Schematic drawing 10x1/1 GN Electric
50
V-09 05/2014
1042
8 125
88 [3-1/2]
72 [2-7/8]
n
43
50 n
370
8
83
715
552
/2
88 n
1 2 3
80
120
~
R531
120
4 400
340 [13-3/8]
~
R531[21 ]
- 36 -
Schematic drawing 10x1/1 GN Gas
50
1042
8 125
88 [3-1/2]
88
72 [2-7/8]
n
3 [2-3/8]
0 n
50 n
370
43
845 [3-3/8]
1
2
88 n
120
~
R531
-1/4
120
488
4 400
340 [13-3/8]
~
R53
1
[ 21
]
- 37 - V-09 05/2014
Schematic drawing 10x2/1 GN Electric
50
V-09 05/2014
1042
8 125
84 [3-3/8]
72 [2-7/8]
n
50 n
46
475
75
915
764
88 n
76
120
~
R737
129
445
385 [15-1/8]
~
110
R737
[ 29
]
- 38 -
Schematic drawing 10x2/1 GN Gas
56
1042
8 125
84 [3-3/8]
88
72 [2-7/8]
70 n
50 n
46
1385 [5-1/2]
475
235
2
88 n
120
~
R737
425
129
445
385 [15-1/8]
~
110
R73
7
[ 29
]
n
- 39 - V-09 05/2014
Schematic drawing 20x1/1 GN Electric
8 55
8 48
8 370
1782
4
2
145
190
71 [2-3/4]
136,5 [5-3/8]
52
715
629
34
12
0
565
158 [6-1/4]
1 2 3
152
103,5 [4-1/8] o o
V-09 05/2014 - 40 -
Schematic drawing 20x1/1 GN Gas
55
4 196
115
763
815 [3-1/4]
48
370
1782
145
190
71 [2-3/4]
137 [5-3/8]
- 41 -
158 [6-1/4]
52
715
629
8 34
12
0
565
104
152 o o
V-09 05/2014
Schematic drawing 20x2/1 GN Electric
8 49
480
136,5 [5-3/8]
8 55
1782
4
2
145
190
71 [2-3/4]
8 55
4 57
8
920
829
8 34
120
8
770
162 [6-3/8]
8
103,5 [4-1/8]
156 o o
V-09 05/2014 - 42 -
Schematic drawing 20x2/1 GN Gas
2 240
140
76,3
8
138,5 [5-1/2]
480
49
136,5 [5-3/8]
68
1782
2
145
190
71 [2-3/4]
8 55
4 57
920
829
34
12
0
8
770
162 [6-3/8]
8
103,5 [4-1/8]
156 o o
- 43 - V-09 05/2014
UK
80.05.052 · V-09 · Technical Services · Md · 05/2014
advertisement
Key Features
- Automatic direct ignition with ignition monitor
- Integrated SCautomatic that changes water in steam generator
- Hoseproofness: IPX5
- Maximum flow rate for each unit
- Room volume requirements based on ventilation type