- Home
- Domestic appliances
- Climate control
- Space heaters
- Detroit Radiant Products
- LD3 -20-50
- Installation manual
- 60 Pages
Detroit Radiant Products LD3 -15-40, LD3 -15-50, LD3 -20-40, LD3 -20-50, LD3 -30-50 Infrared Tube Heater Installation Manual
Below you will find brief information for LD3 LD3-15-40, LD3 LD3-15-50, LD3 LD3-20-40, LD3 LD3-20-50, LD3 LD3-30-50. This installation manual provides specific information related to the LD3 series model. The LD3 series infrared tube heater is a positive pressure, two stage radiant heater system.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
LD3 Series
Installation Manual
The LD3 Series Infrared Tube Heater is a positive pressure, two stage radiant heater system. This manual provides specific information related to the LD3 Series model. All persons involved with the installation, operation and maintenance of the heater system must read and understand the information in this manual.
!
WARNING
Improper installation, adjustment, alteration, service, or maintenance can cause property damage, injury, or death. Read the installation, operation, and maintenance instructions thoroughly before installing or servicing this equipment.
This heater must be installed and serviced by trained gas installation and service personnel only. Failure to comply could result in personal injury, asphyxiation, death, fire, or property damage.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
In locations used for the storage of combustible materials, signs
must be posted to specify the maximum permissible stacking height to maintain the required clearances from the heater to the combustibles. Signs must either be posted adjacent to the heater thermostats or in the absence of such thermostats, in a conspicuous location.
Do not use this heater in indoor living or sleeping quarters, etc.! Installation of a tube heater system in residential indoor living spaces may result in property damage, serious injury, asphyxiation, or death.
For Your Safety
If you smell gas:
• Do not try to light any appliance. • Immediately call your gas supplier from a neighbor’s phone.
• Do not touch any electrical switch. • Follow the gas supplier’s instructions.
• Do not use any phone in your building. • If you cannot reach your gas supplier, call the fire department.
INSTALLER: Present this manual to the end user.
Keep these instructions in a clean and dry place for future reference.
Model#: ___________________ Serial #: _________________________
(located on rating label)
LIOLD3-Rev. 32513
Print: 1M-12/15(CDS)
Replaces: LIOLD3-1M-3/14(CDS)
1.0
Introduction
• Table of Contents
Contents
LD3 Series
1.0 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Heater Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Safety Signs and Labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.0 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Warning Symbols. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Standards, Certifications and Government Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Clearance to Combustibles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.0 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Design Considerations and Prechecks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Recommended Mounting Heights and Coverages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Hanger Placement and Suspension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Radiant Tube Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Optional Elbow or U-Bend Accessory Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Burner Control Box Suspension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Reflector Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Final Heater Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Combustion Air Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Separated Combustion Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Combustion Air Supply - Room Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Optional Unvented Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Gas Supply Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Electrical Requirements and Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Typical Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Thermostat Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Unit Start-up (Commissioning) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
High Altitude Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
4.0 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
5.0 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Heater Components and Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Routine Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Kit Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
2
LD3 Series
1.0
Introduction
1.0
Introduction
• Overview • Heater Components • Specifications
Overview
The intent of this manual is to provide information regarding safety, design guidelines, installation, operation, and maintenance of the tube heater. You must read and understand the instructions and all safety warnings before installing the tube heater. This manual is property of the owner, and must stay with the owner or unit after the installation is complete.
Heater Components
Prior to installation, verify that the heater’s gas type and voltage (as listed on the rating plate) match that of your application. Also verify that you have received all heater contents included with your tube heater. Reference page 60 for a list of the kit contents for your model heater. Materials not included in the heater kit contents (e.g., screws, vent material, terminals, etc.) are the responsibility of the installer.
Notify your product representative or Detroit Radiant Products of any discrepancy or missing kit contents prior to installing unit.
Specifications
Chart 1.1 • LD3 Series Specifications
LD3-15-40
N or LP 40,000 28,000 16’-10”
LD3-15-50
N or LP 50,000 35,000 16’-10”
LD3-20-40
N or LP 40,000 28,000 21’-10”
LD3-20-50
N or LP 50,000 35,000 21’-10”
N/A
N/A
13’-0”
13’-0”
85 lbs.
85 lbs.
100 lbs.
100 lbs.
8’ to 13’
10’ to 15’
8’ to 13’
9’ to 15’
Titan
Titan
Titan
Titan
Alum
Alum
Alum
Alum
Yes
No
Yes
No
LD3-30-50*
N or LP 50,000 35,000 31’-7” 17’-8” 120 lbs.
9’ to 14’ Titan Alum Yes
* Model requires LV3-5EA-SUB optional accessory package when installing in a ‘U’ configuration (P/N: DB-TF1B/TF1B).
** Recommended mounting heights are provided as a guideline. Actual conditions may dictate variations from this
data. Optional protective guard (P/N: PG) is required when mounting below 8-ft.
^ Certified models may be installed in attached residential garages/workshops.
Titan = Black coated titanium stabilized aluminized steel.
Alum = Black coated aluminized treated steel.
3
1.0
Introduction
• Safety Signs and Labels
LD3 Series
!
WARNING
Read and understand all safety information and warnings in this manual before installation, operation, and maintenance of the radiant tube heater system.
Safety Signs and Labels
Product safety signs or labels should be replaced by the product user when they no longer are legible.
Contact either your local distributor or the product manufacturer for obtaining replacement signs or labels.
120V
- 120V HEATER INPUT -
F/N: LLV3EP1
HOT
NEUTRAL
EARTH
F/N: LLAC023
Combustion Air
Connector Label
3
F/N: LLV3EP14
Top Panel
Back Panel
F/N: LLTB018 (NG)
F/N: LLTB019 (LP)
!
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death.
This heater must be installed and serviced by trained gas installation and service personnel only.
This is NOT an explosion-proof heater. DO NOT install in explosive environments. Where there is the possibility of exposure to flammable vapors or dusts, consult the local fire marshall, your insurance carrier or authorities for approval of the proposed installation.
VENTING. This heater must be properly vented according to the manufacturer’s specifications.
WARNING: Operation of this heater, when not properly vented with an approved system, can result in carbon monoxide
(CO) poisoning and possible death.
This heater requires FRESH COMBUSTION AIR for safe operation and must meet all provisions of the specified combustion and ventilation requirements.
GAS CONNECTION. Allowances must be made for the system to expand. A flexible gas connection of approved type is required. Flexible stainless steel gas connectors installed in one plane, without sharp bends, kinks or twists is recommended. Consult manual for further instructions.
WARNING: Connector must be installed in a “C” configuration. Use only the connector that was furnished with the heater.
Gas Flex
Hose Gas Pipe
12”
Gas Flex Hose 45°
45°
Read and understand the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.
F/N: LLTCL006L/C/R
Clearance to Combustibles Label
Bottom Panel
F/N: LLLOGO1 Logo Label
4
LD3 Series
1.0
Introduction
• Safety Signs and Labels
SERVICE ACCESS PANEL
IGNITER & FLAME SENSE COMPARTMENT
1. Turn off gas & electricity.
2. Remove cover by lifting top
cover upward and outward.
CAUTION: HOT SURFACE.
KEEP COVER IN PLACE. REMOVE FOR SERVICE ONLY.
F/N: LLTB026
SERVICE ACCESS PANEL
F/N: LLTB024L
®
LOW-INTENSITY INFRARED HEATER
RADIATEUR À INFRAROUGE À FAIBLE INTENSITÉ
MODEL NUMBER
NUMÉRO DE MODÈLE
LD3-20-40N
MAX. HEAT INPUT
MAX. DEBIT CALORIFIQUE
MIN. HEAT INPUT
MIN. DEBIT CALORIFIQUE
TYPE OF GAS
TYPE DE GAZ
40,000
25,000
SERIAL NUMBER
NUMÉRO DE SÉRIE
VERSION
YYMMREPCSHIPPE#### 09/12
BTU/h
BTU/h
NATURAL
MANIFOLD PRESSURE
PRESSION A LA TUBULURE D'ALIMENTATION
MAXIMUM INLET PRESSURE
PRESSION D'ALIMENTATION MAXIMALE
MINIMUM INLET PRESSURE FOR PURPOSE OF ADJ.
PRESSION D'ALIMENTATION EN GAS MIN. ADMISE
SA
MP
3.5
LE
5.0
INCHES W.C.
VENT CATEGORY
ÉVENT CATÉGORIE
CATEGORY III
COMBUSTION CHAMBER
ORIFICE SIZE
DIM DE L'INJECTEUR
D.M.S.
D.M.S.
TP-26B; INCH BC ALUMINIZED
THIS DESIGN COMPLIES WITH STANDARD(S):
COMPLES DE CETTE CONCEPTION AVEC LA NORME:
ANSI Z83.20b-2011 • CSA2.34B-2011 RADIANT TUBE HEATER
AGA 7-89 RESIDENTIAL RADIANT TUBE HEATER
VOLTAGE
120
MAX. MOUNTING ANGLE
MAX. ANGLE DE SUPPORT
VAC
INCHES W.C.
INCHES W.C.
AMPS
2.4
PHASE
SINGLE
FREQUENCY
60
MIN. MOUNTING ANGLE
MIN. ANGLE DE SUPPORT
Hz
HEATER BUILD TYPE
0°
45°
C1
DETROIT RADIANT PRODUCTS COMPANY
21400 HOOVER ROAD - WARREN, MI 48089
(586) 756-0950 www.reverberray.com
FOR COMMERCIAL / INDUSTRIAL USE.
FOR INDOOR USE ONLY.
MADE IN U.S.A.
Rating Plate
SERVICE ACCESS PANEL
IGNITER & FLAME SENSE COMPARTMENT
1. Disconnect gas & electricity.
cover upward and outward.
SERVICE ACCESS PANEL
®
MODEL NUMBER
NUMÉRO DE MODÈLE
LD3-20-40N
SERIAL NUMBER
NUMÉRO DE SÉRIE
VERSION
YYMMREPCSHIPPE#### 09/12
40,000
25,000
BTU/h
BTU/h
NATURAL
49
TP-26B; INCH BC ALUMINIZED
THIS DESIGN COMPLIES WITH STANDARD(S):
COMPLES DE CETTE CONCEPTION AVEC LA NORME:
NATURAL GAS
D.M.S.
3.5
14.0
5.0
INCHES W.C.
INCHES W.C.
57
VOLTAGE
AMPS
INCHES W.C.
PHASE
D.M.S.
120
VAC
2.4
SINGLE
FREQUENCY
60
MIN. ANGLE DE SUPPORT
Hz
MAX. MOUNTING ANGLE
MAX. ANGLE DE SUPPORT
0°
45°
HEATER BUILD TYPE
C1
DETROIT RADIANT PRODUCTS COMPANY
21400 HOOVER ROAD - WARREN, MI 48089
(586) 756-0950 www.reverberray.com
FOR COMMERCIAL / INDUSTRIAL USE.
MADE IN U.S.A.
Controls Compartment
F/N: LLTB025R
!
INSTALLER
AVOID EQUIPMENT FAILURE
THIS 10 FT. TUBE IS THE
COMBUSTION CHAMBER.
The combustion chamber utilizes either 409 stainless, titanium alloy or aluminized steel - depending on the model number of your heater.
THIS TUBE MUST BE THE FIRST TUBE
FOLLOWING THE BURNER CONTROL BOX.
Rotate the tube’s welded seam to bottom.
Consult the manual(s) for further details.
F/N: LLTB004
(all heaters with 409 stainless steel tubes)
Bill of Material
LD3-20-40N
Serial No.: 1311XXXXXXXXXX 0001
Stock:
None
Add-On:
N/A
Version:
11.13
Data on this label is for the model shown on this label. If your heater has been converted, this information is not accurate. Please contact the factory for assistance.
BURNER COMPONENTS:
Gas Valve:
Circuit Board:
Wire Harness:
N.O. Switch:
N.O. VL Orifice:
N.C. Switch:
N.C. VL Orifice:
Diff Switch:
Diff VL Orifice:
Igniter:
Burner:
None
None
(Specify TP-#’s)
Two-Stage
Ignition Control
3 PCS Harness
None
None
IS22016051F5169
Grey (+ / -)
Norton
High
SA
N/A
264E
50
201B
4” Gen.
Yellow - 120V
1080
828
3140
851B
3252
N/A
Diag. Light:
Term. Block:
Transformer:
MP
Filter:
24 Volt In:
120 Volt In:
Gas In:
LE
Extra VL Orifice:
None
Fasco Lg.
50Hz - 120V
When Specified
None
120V Cord
7/8” FC Flare
None
16” Tube:
Ind. Lights:
None
None
N/A
N/A
55A
55B
N/A
N/A
334
333
83
HEATER
TYPE:
C1
Orifice Type:
Gas:
Air:
TP-204#
TP-44#
C1
3
1 1/2”
C2 C3
3
1 5/8”
1
1 5/8”
Internal Use Only:
Electric:
Tag:
LLWT038
None
Special 1:
Special 2:
17
1 7/16”
For parts replacement information, contact factory at 586-756-0950 or visit www.drp-co.com/parts.
Burner Control Box
Component Label
(located inside the center compartment lid)
16” Burner Tube
Fan
Compartment
F/N: LL01 - Clearance Safety Tag
(Affix adjacent to heater’s thermostat)
Al-Ti Combustion
Chamber
Aluminized
Radiant Tube(s)
(if applicable)
F/N: LLTCL015
Lighting Instructions
5
2.0
Safety • Warning Symbols • Applications
LD3 Series
2.0
Safety
Read and understand all safety information and warnings in this manual prior to installation, operation, and maintenance of this heater. Warnings indicate a potentially hazardous situation which, if not avoided, could result in injury or death.
!
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, serious injury or death. Read and understand, the installation, operation, and maintenance instructions thoroughly before installing or servicing this equipment. Only trained, qualified gas installation and service personnel may install or service this equipment.
Warning Symbols
Safety is the most important consideration during installation, operation and maintenance of the tube heater. You will see the following symbols and signal words when there is a hazard related to safety or property damage.
!
WARNING
Warning indicates a potentially hazardous situation which, if not avoided, could result in death or injury.
!
CAUTION
NOTICE
Caution indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury.
Notice indicates a potentially hazardous situation which, if not avoided, could result in property damage.
Applications
This is not an explosion proof heater. No tube heater may be used in a Class 1 or Class 2 Explosive environment. Consult your local fire marshal, insurance carrier and other authorities for approval if the proposed installation is in question.
6
LD3 Series
2.0
Safety
• Applications • Standards, Certifications and Regulations
Commercial / Industrial Applications
Unless otherwise indicated, tube heaters are designed and certified for use in industrial and commercial buildings, such as warehouses, manufacturing plants, aircraft hangars, and vehicle maintenance shops.
For maximum safety the building must be evaluated for potential problems before installing the heating system. A critical safety factor to consider before installation is the clearance to combustibles.
Residential Applications
Only select LD3 Series models are Design Certified under CSA Requirements for residential radiant tube heaters (No. 7-89). Not for use in the residential indoor living areas or sleeping quarters.
!
WARNING
Not For Use in Indoor Living Spaces. Installing this unit in residential indoor living spaces or sleeping quarters, such as bedrooms or basements, may result in property damage, serious injury, or death.
Standards, Certifications and Government Regulations
Installation of this tube heater must conform with all applicable local, state, and national specifications, regulations, and building codes. Contact the local building inspector and/or fire marshal for guidance.
In the absence of local codes, the installation must conform to the latest edition of:
United States: National Fuel Gas Code, ANSI Z223.1 (NFPA 54).
Canada: CAN/CGA B149.1 and .2, Canadian Electrical Code C22.1
Copies of the Standards can be viewed or purchased at www.nfpa.org or www.scc.ca.
Public Garages:
This heater must be installed in accordance with the latest edition of the Standard for Parking
Structures, ANSI/NFPA 88A or the Code for Motor Fuel Dispensing Facilities and Repair Garages ANSI/
NFPA 30A. In Canada, refer to CAN/CGA B149.1 and B149.2.
• Heaters must not be installed less than 8 ft. (2.4 m) above the floor. Minimum clearances to
combustibles must be maintained from vehicles parked below the heater.
• When installed over hoists, minimum clearances to combustibles must be maintained from the
upper most point of objects on the hoist.
Aircraft Hangars:
This heater must be installed in accordance with the latest edition of the Standard for Aircraft Hangars,
ANSI/NFPA 409. In Canada, refer to CAN/CGA B149.1 and B149.2.
• In aircraft storage and servicing areas, heaters shall be installed at least 10 ft. from above the upper
surface of wings or of the engine enclosures of the highest aircraft that may be housed in the hangar.
The measurement shall be made from the wing or engine enclosure, whichever is higher from the
floor, to the bottom of the heater.
• In areas adjoining the aircraft storage area (e.g., shops, offices) the bottom of heaters shall be
installed no less than 8 ft. (2.4 m) above the floor.
• Suspended or elevated heaters shall be located in spaces where they shall not be subject to damage
by aircraft, cranes, movable scaffolding or other objects.
Provisions shall be made to assure accessibility to suspended tube heaters for recurrent maintenance purposes.
7
2.0
Safety
• Clearance to Combustibles
LD3 Series
Clearance to Combustibles
A critical safety factor to consider before installation is the clearances to combustibles.
Clearance to
combustibles is defined as the minimum distance you must have between the tube surface, or reflector, and the combustible item. Considerations must also be made for moving objects around the tube heater.
The following is a partial list of items to maintain clearances from:
Combustible items:
• Wood
• Paper
• Fabric
• Chemicals
• Paint
• Parked vehicles
• Gasoline
• Storage racks
Moving Objects:
• Overhead doors
• Vehicle lifts
• Cranes
• Hoists
Hazards:
For maximum safety the building must be evaluated for hazards before installing the heating system.
Examples include, but are not limited to:
• Gas and electrical lines
• Combustible and explosive materials
• Chemical storage areas
• Areas of high chemical fume concentrations
• Provisions for accessibility to the heater
• Adequate clearances around air openings
• Combustion and ventilating air supply
• Vehicle parking areas
• Vehicles with lifts or cranes
• Storage areas with stacked materials
• Lights
• Sprinkler heads
• Overhead doors and tracks
• Dirty, contaminated environment
!
WARNING
Placement of explosive objects, flammable objects, liquids, and vapors close to the heater may result in explosion, fire, property damage, serious injury, or death. Do not store or use explosive objects, liquids, and vapor in the vicinity of the heater.
!
CAUTION
Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the same space as the heater.
Clothing or other flammable materials should not be hung from the heater, or placed on or near the heater.
Any guard or other protective device removed for servicing the heater must be replaced prior to operating the heater.
Installation and repair should be done by a qualified service person. The heater should be inspected before use and at least annually by a qualified service person. More frequent cleaning may be required as necessary. It is imperative that the control compartment, air passageways and burner(s) of the heater be kept clean.
When installing the tube heating system, the minimum clearances to combustibles for your Series tube heater and system configuration must be maintained. These distances are shown in Chart 2.1 on page 9 and on the burner control box. If you are unsure of the potential hazards, consult your local fire marshall, fire insurance carrier or other qualified authorities on the installation of gas fired tube heaters for approval
8
LD3 Series
2.0
Safety
• Clearance to Combustibles of the proposed installation.
In locations used for the storage of combustible materials, signs must be posted to specify the maximum permissible stacking height to maintain the required clearances from the heater to the combustibles.
Signs must either be posted adjacent to the heater’s thermostat or in a conspicuous location.
The stated clearance to combustibles represents a surface temperature of 90°F (50°C) above room temperature. Building materials with a low heat tolerance (such as plastics, vinyl siding, canvas, tri-ply, etc.) may be subject to degradation at lower temperatures. It is the installer’s responsibility to assure that adjacent materials are protected from degradation.
!
WARNING
Failure to comply with the stated clearances to combustibles may result in personal injury, property damage, and/or death.
Chart 2.1 •
Clearance to Combustibles in Inches (see Figure 2.1 for Mounting Angles)
Model Number
Mounting
Angle* Front
Sides
Behind Top Below
LD3 (15, 20) - 40 [N, P]
with 1 side shield
with 2 side shields
LD3 (15, 20, 30) - 50 [N, P]
with 1 side shield
with 2 side shields
20 ft. from burner
45°
0°
0°
0°
40,000 BTU/h MODELS
0° 15
45° 58
0°
0°
42
20
50,000 BTU/h MODELS
0° 11
39
29
16
7
15
8
8
20
11
8
8
16
7
6
10
6
6
6
10
6
6
6
45
45
45
45
48
48
48
48
30
* Heaters mounted on an angle between 0° to 45° must maintain clearances posted for 0° or 45°; whichever is greater.
NOTE: Use high BTU output when determining clearances. The minimum end clearance is 12 in.
Figure 2.1 • Mounting Angles
0° Mounting Angle
Top
45° Mounting Angle
Top
0° Mounting Angle with 1 Side Shield
(P/N: SSE)
Top
0° Mounting Angle with 2 Side Shields
(P/N: SSE)
Top
Side
Below
Side Front
Behind
Front
Below
9
Below
Behind Side
Below
Side
3.0
Installation
• Design Considerations and Prechecks
3.0
Installation
LD3 Series
!
WARNING
Improper installation, adjustment, alteration, service, or maintenance can cause property damage, serious injury, or death.
Read and understand, the installation, operation, and maintenance instructions thoroughly before installing or servicing this equipment.
Only trained, qualified gas installation and service personnel may install or service this equipment.
Design Considerations and Prechecks
Placement of infrared heaters is influenced by many factors. Aside from safety factors, considerations such as the number of heater or vent elbows that are allowed, maximum vent lengths, ducting of combustion air, and combining exhaust vents are a few examples. All installation manuals, along with national, state, provincial, and local codes, address these issues. It is critical that you read, understand, and follow all guidelines and instructions.
To ensure a properly designed heating system, a layout should be developed for the correct placement of the burner control box, tubes, vents, and combustion air intake ducts. Inspect and evaluate the mounting conditions, vent locations, gas supply, and wiring.
When designing an infrared radiant heating system, consider the following:
• Has the building’s heat loss been evaluated?
• Does the design meet the needs of the space?
• Have recommended mounting heights been observed?
• Have all clearance to combustible situations been observed?
• Is the supply (burner) end of the heater located where more heat is required?
• Is it best to offset the heaters and/or rotate the reflectors towards the heat zone?
• Are extra guards, side shields, ‘U’ or ‘L’ reflector covers required?
• Does the heater require outside fresh air for combustion?
• Is the environment harsh or contaminated (requiring outside air for combustion)?
• Are chemicals or vapors a concern (requiring outside air for combustion or additional ventilation)?
IMPORTANT: Fire sprinkler heads must be located at an appropriate distance from the heater. This distance may exceed the published clearance to combustibles as posted on the heater. Certain applications may require the use of high temperature sprinkler heads or relocation of the heaters.
Sprinkler systems containing propylene glycol or other flammable substances are not to be used in conjunction with this heater without careful consideration for and avoidance of potential fire or explosion hazards. For further information consult NFPA 13.
The effective infrared surface temperature of a person or object may be diminished with wind velocities above 5 mph. The use of adequate wind barrier(s) may be required.
10
LD3 Series
3.0
Installation • Recommended Mounting Heights
Chart 3.1 • Recommended Mounting Heights and Coverages
NOTE: This chart is provided as a guideline. Actual conditions may dictate variation from this data.
15 ft. 40,000 8’ - 13’ 20’ x 12’ N/A 10’ - 20’ 20’ - 40’ 16’
20 ft.
50,000
40,000
10’ - 15’
8’ - 13’
22’ x 15’
20’ x 13’
N/A
12’ x 12’
20’ - 30’
10’ - 20’
30’ - 50’
20’ - 40’
18’
16’
30 ft.
50,000
50,000
9’ - 15’
9’ - 14’
22’ x 15’
32’ x 15’
12’ x 12’
15’ x 15’
20’ - 30’
20’ - 30’
30’ - 50’
30’ - 50’
18’
18’
Factory recommended mounting heights are listed as a guideline. If infrared heaters are mounted too low or too high, they may result in discomfort or lack of heat. Detroit Radiant Products Company generally recommends observing the recommended mounting heights to optimize comfort conditions. However, certain applications such as spot heating, freeze protection, outdoor patio heating or very high ceilings may result in the heaters being mounted outside of the factory recommended mounting heights.
* Optional protective guard (P/N: PG) is required when mounting below 8-ft.
Figure 3.1 • Mounting Height Dimensions • see Chart 3.1 for dimensions
Dim. A
Dim. B
Dim. A
Dim. C
Dim. C
Note: Dimensions A, B & C are based upon heaters hung at the factory recommended mounting height.
11
3.0
Installation
• Hanger Placement and Suspension
Hanger Placement and Suspension
LD3 Series
!
WARNING
Improper suspension of the tube heater may result in collapse and being crushed. Always suspend from a permanent part of the building structure that can evenly support the total force and weight of the heater.
Failure to maintain minimum clearance to combustibles may result in fire and/or explosion, property damage, serious injury, or death. Always maintain minimum clearances and post clearance safety limit signs or the clearance safety tag where needed.
Suspension of the heater must conform to applicable codes referenced in the Safety section and these instructions.
1
Lay all radiant tubing out in the following order. Position tubes in approximate location (see Figure 3.2).
• 10 ft. 4” O.D. or 4” to 3” O.D. titanium treated combustion chamber.
• 3” O.D. aluminized radiant emitter tube(s) if applicable.
2
Connect the female end of the titanium combustion chamber to the 16” burner tube by using the 4” stainless steel tube clamp (TP-220).
The 10 ft. titanium alloy treated combustion chamber must be placed as the first tube downstream of the burner control box. The combustion chamber has an orange identification sticker located on the swaged end of the tube.
3
Place a 4” tube hanger (TP-19B) on the tapered titanium combustion chamber’s 4” O.D. end. The spacing between the burner control box mounting brackets and the 4” tube hanger should be 2’-4”.
4
Mark locations for hanging points.
If the available hanging points do not allow for the recommended spacing then additional hangers (P/N: TP-19B(4”) or TP-1079(3”)) may be necessary.
• The spacing between the burner control box mounting brackets and the first hanger should be
approximately 2’-4”.
• The space between the first two hangers placed on the first tube, should be approximately 8’-10”.
• The space between hangers thereafter, one per tube, should be approximately 9’-8”.
12
LD3 Series
3.0
Installation
• Hanger Placement and Suspension
Figure 3.2 • Heater Mounting Layout
NOTE: A sticker identifying the combustion chamber(s) is located on the swaged end of the tube(s).
Suspension
Point
9’ 8
”
Suspension
Point
9’ 8
”
Burner Control Box
Suspension Points
Suspension
Point
Igniter/
Sensor Box
2’ 4”
8’ 10
”
3” or 4” Tube
Clamp (TP-1077 or TP-21B)
3” O.D. Aluminized
Steel Radiant Emitter
Tube(s) (if applicable)
3” or 4” Tube Hanger
(TP-1079 or TP-19B)
10 ft. 4” to 3” O.D. Tapered or 10 Ft. 4” O.D.
Titanium Treated Combustion Chamber
4” Tube Hanger (TP-19B)
4” Stainless Steel
Tube Clamp (TP-220)
Burner
Control Box
16” Burner
Tube
Chart 3.2 • Heater Mounting Requirements and Weights
15 ft.
20 ft.
16’-10”
21’-10”
3
3
2
2
85 lbs.
100 lbs.
30 ft.
31’-7” 4 2 120 lbs.
*
Refer to page 18 for U-bend configuration dimensions.
13
5
5
6
N/A
6
7
3
3
4
N/A
2
3
3.0
Installation
• Hanger Placement and Suspension
LD3 Series
5
Prepare mounting surface, if necessary weld blocks, drill holes (see figure 3.3).
NOTE: The burner control box and radiant tubes should be in straight alignment and level.
6
Fasten beam clamp, screw hook or other type of suspension anchor to hanging point.
7
Attach and close S-hook (P/N: S-Hook) and #1 double-loop chain (P/N: THCS) to anchor. Check that it is securely attached. NOTE: Threaded rod and turnbuckles may be used.
8
Attach hangers to chains. Adjust chain lengths until radiant tubing is level and equal weight distribution is achieved. Chains must be straight up and down. Do not install chains at an angle as this can result in tube warpage or separation.
Figure 3.3 • Mounting the Hangers
5
I-Beam
5
I-Beam
6
Beam Clamp
6
Beam Clamp
7
S-Hook and
#1 Double-Loop Chain
7
Threaded Rod and Turnbuckle
8
Chain
5
Concrete Beam
6
Screw Hook
6
Screw hook
with Locknut
and Washer
8
Chain
5
Wood Beam
8
Chain
14
LD3 Series
Figure 3.4 • U-Tube Hanger Mounting Options
3.0
Installation
• Hanger Placement and Suspension
Single Mounting
Bracket
Brass Knuckle
Exhaust
End
U-Tubes can be mounted from a single suspension point using an optional Single Mounting Bracket
(P/N: SMB) with five S-hooks and #1 double-loop chains.
U-Tubes can be mounted at a 15, 30 or 45 degree angle with two suspension points, using two optional
Brass Knuckle (P/N: BK) fittings, #1 double-loop chains and S-hooks.
Figure 3.5 • Angled Hanger Mounting Options
45°
30°
15°
For 45 degree hanging angle use two
S-hooks and two #1 double-loop chains.
15
For variety of hanging angles, use an optional
Brass Knuckle (P/N: BK) fitting with a #1 doubleloop chain and S-hook.
3.0
Installation
• Radiant Tube Assembly
LD3 Series
Radiant Tube Assembly
To install the radiant tubes:
1
Place tubes in hangers with the welded seam facing downward and the swaged end of the tube towards the exhaust end of the heater system (see Figure 3.6).
Refer to page 22 for tube installation sequence.
Figure 3.6 • Attach Hangers
Swaged End
Radiant Tube
Hanger
Welded seam faces down
2
Slide tube clamps onto radiant tubes (see figure 3.7).
Figure 3.7 • Attach Tube Clamps
Concave surface
Tube Clamp
NOTE: If the tube clamp comes apart, the spacer must be re-assembled with the spacer’s concave surface facing against the radiant tube surface.
16
LD3 Series
3.0
Installation
• Optional Elbow or U-Bend Accessory Configuration
3
Slip-fit the radiant tube sections together until tightly connected (install the swaged end of each tube towards exhaust end). NOTE: If it is difficult to mate the tubes, they may be installed incorrectly.
4
Center tube clamps over the seam where two radiant tube sections connect. If necessary, rotate tube clamps so they will not interfere with the reflector end caps during expansion and contraction of the heater.
5
Tighten tube clamp bolts to secure. When proper compression is obtained (40-60 ft-lbs. torque) the tube seam will create a visible mark on the tube clamp.
NOTE: Excessive torque may damage the tube clamp.
6
Determine the location of the burner control box and note the placement of the mounting chains.
Figure 3.8 • Tube Connections
Tubes fit snuggly together and the tube clamp is centered over the seam.
The tube clamp is tight when the torque is achieved (normally when seam becomes visible).
Tubes are not fit snuggly together and the tube clamp is not centered over the seam.
Correct Tube Connection Incorrect Tube Connection
Optional Elbow or U-Bend Accessory Configuration
A 90 degree elbow or 180 degree U-bend accessory fitting may be installed in the radiant tube heating system. Refer to Chart 3.3 for minimum distance requirements from the burner control box.
When installing an Elbow or U-Bend Accessory Fitting:
• The top clearance of an uncovered (no reflector) elbow or U-bend accessory fitting to combustibles
is 18 in.
• If operating the heater un-vented, separate the intake air to the heater from its exhaust products a
minimum of 4 ft., further separation may be necessary. Combustion air may also be supplied.
• A maximum of two 90° elbows or one 180° U-bend can be installed on a heater.
Figure 3.9 • Optional Tube Connections
90 Degree 3” Elbow
(P/N: DB-E6) or
4” Elbow (P/N: E6)
17
180 Degree 3” U-Bend
(P/N: DB-TF1B) or
4” U-Bend (P/N: TF1B)
3.0
Installation
• Optional Elbow or U-Bend Accessory Configuration
Figure 3.10 • Elbow and U-Bend Clearances
Dimension A
LD3 Series
Elbow can be set
in both directions
Tube Clamp
Dimension A
Tube Clamp
U-Bend can be set in both directions
12” Tube Clamp
8”
Tube Clamp
Dimension B
Figure 3.11 • U-Bend and Elbow Dimensions
180 Degree 3” U-Bend
P/N: DB-TF1B
180 Degree 4” U-Bend
P/N: TF1B
16”
16”
6”
6”
90 Degree 3” Elbow
P/N: DB-E6
11.5”
90 Degree 4” Elbow
P/N: E6
12.5”
12.5”
15” 18”
16” 20”
11.5”
10”
20”
10”
20”
See Chart 3.6 on page 22 for tube diameters and locations.
Chart 3.3
Minimum Distance From Burner
Control Box to Elbow or U-bend
Accessory Fitting
Model BTU Range Dimension A
40,000
50,000
10 ft.
10 ft.
Chart 3.4
Overall Dimensions for Heaters Configured With U-Bend
Tube Length Dimension B
15 ft.
20 ft.
N/A
13’-0”
Notes
N/A
N/A
30 ft.
17’-8” Requires P/N: LV3-5EA-SUB *
* The LV3-5EA-SUB add-on may only be ordered at the time of
heater production.
18
LD3 Series
3.0
Installation
• Burner Control Box Suspension
Burner Control Box Suspension
Suspending the burner control box must be done in accordance with applicable codes listed in the Safety section and these instructions.
The burner control box must be in straight alignment with radiant tubes and level. Contact your local distributor or the factory to see if your application allows for the rotation of the burner control box.
1
Determine the mounting chain locations for hanging the burner control box.
2
Fasten beam clamp, screw hook or other type of suspension anchor to hanging point.
3
Attach S-hook and #1 double loop chain (P/N: THCS) to anchor. Check that it is securely connected.
4
Attach chain assemblies and S-hooks to mounting brackets on the burner control box. Adjust chain lengths until level and in straight alignment with radiant tubes. Burner sight glass will be visible from the floor.
Figure 3.12 • Burner Control Box Assembly • Side View
1
2
3
16 in. burner tube is in straight alignment with combustion chamber
4
TP-1079 3” Hanger
9.625”
12.875”
Burner
Sight Glass
16”
TP-19B
4” Hanger
TP- 220 4” Stainless
Steel Tube Clamp
TP-1077
3” Tube Clamp
Figure 3.13 • Burner Control Box showing U-Shaped Configuration • End View
15”
32.5”
11.25”
19
18.5”
4”
4.5”
8.625”
3.0
Installation
• Reflector Assembly
LD3 Series
Reflector Assembly
To install the reflectors (see Figure 3.14):
1
Attach the reflector center supports onto radiant tubes.
2
Slide each reflector section through the hangers and adjust the reflector tension spring into the
V-groove on the top of the reflector. The reflectors should overlap approximately 4 inches.
3
To prevent the reflectors from shifting, secure the reflector sections together using sheet metal screws, except at the expansion joint (see p.22).
NOTE: Installer to supply sheet metal screws.
4
Attach reflector end caps with polished finish inward to each end of the reflector run. Secure with clips.
Reflectors and reflector accessories direct infrared energy to the floor level. The reflector assembly depends on the heater configuration, proximity to combustibles, and space surrounding the heater.
Before you begin assembly, determine if the use of reflector accessories are necessary (see Chart 3.5).
Figure 3.14 • Reflector Assembly
Reflector
Reflector Center
Support
Hanger and Chain
Radiant
Tube
Mid-point of the tube
Reflector Tension
Spring
4” Overlap
Clips
Figure 3.15 • Width of Installed Reflector - Top View
VICE ONLY.
ARTMENT
ACCESS PANE
CONTROLS & GAS VA
SERVICE
KEEP COVER IN PLACE. REMOVE FOR SER
13.75”
Reflector End Cap
SERVICE ACCESS PANEL
FAN COMPARTMENT
1. Disconnect gas & electricity.
3. Remove tsix (6) 1/4” screws.
KEEP COVER IN PLACE. REMOVE FOR SERVICE ONLY.
20
LD3 Series
3.0
Installation
• Common Reflector Accessories
Chart 3.5
•
Common Optional Accessories
Reflector Accessory Description Part Number
Elbow Reflector* 90° bend, highly polished aluminum reflector elbow designed to fit atop one elbow accessory fitting.
RE
U-Reflector*
180° bend, highly polished aluminum reflector U-bend
RU designed to fit atop one U-bend accessory fitting.
Side Shield Extension** Highly polished side shield extension used to direct infrared rays downward, away from sidewalls and combustibles.
Protective Guard
Used to prevent debris or objects from becoming lodged between the radiant tube and reflector.
mounting heaters below 8 ft.
Required when
SSE
PG
* Reflectors cannot be rotated when used with a reflector elbow (RE), U-shaped reflector (RU), or side shield (SSE).
** Refer to the Clearance to Combustible chart on page 9 for minimum distances to combustibles when side shield extension(s) are used.
Additional accessory options are listed in the Detroit Radiant Products Company Tube Heater Accessory
Guide or online at www.detroitradiant.com.
Figure 3.16 • Reflector Shield Accessories
Elbow reflector (P/N: RE)
Used over a 90-degree elbow radiant tube.
U-shaped reflector (P/N: RU)
Used over a ‘U’ shaped radiant tube.
21
Side shield extension (P/N: SSE)
Directs infrared rays downward, away from sidewalls and combustibles.
3.0
Installation
• Final Heater Assembly
LD3 Series
Final Heater Assembly
Chart 3.6
•
Tube Installation Sequence and Secured Joints for Reflectors
40,000 BTU/h Models
15 Foot
A
10 Ft. Tube Section
D
5 Ft. Tube Section
NOTE: When securing joints on reflectors which are rotated on an angle from horizontal, secure joint only on top side of reflector to allow for sufficient heater expansion and contraction.
20 Foot
A
10 Ft. Tube Section
D
10 Ft. Tube Section
50,000 BTU/h Models
15 Foot
C
10 Ft. Tube Section
B
5 Ft. Tube Section
0° Mounting Angle
1 to 45° Mounting Angle
20 Foot
C
10 Ft. Tube Section
B
10 Ft. Tube Section
30 Foot
C
10 Ft. Tube Section
B
10 Ft. Tube Section
Burner Control Box w/16 in. Burner Tube
A
Expansion Joint on
Reflectors
Secured Joint on
Reflectors (see note)
Secure vent material to exchanger with three #8 sheet metal screws. Seal with high temperature silicone sealant. Do not use tube clamp.
B
C
D
Key
22
D
10 Ft. Tube Section
4” to 3” Tapered Titanium Treated
Combustion Chamber with 4” Stainless
Steel Clamp
4” to 3” Tapered Aluminized Steel
Tube Exchanger with 4” Clamp
4” Titanium Treated Combustion
Chamber with 4” Stainless Steel Clamp
3” Aluminized Radiant Tube Exchanger with 3” Clamp
LD3 Series
3.0
Installation
• Venting • Replacing Existing Equipment
Venting
The LD3 Series tube heater must be vented as described here to properly direct flue gases from the unit to the outside atmosphere. The venting can terminate vertically through the roof (up) or horizontally through a sidewall (sideways).
Follow these guidelines and all applicable codes for all models prior to installing the vent material. Local codes may vary.
In the absence of local codes:
United States: Refer to NFPA 54/ANSI Z223.1 (latest edition), National Fuel Gas Code.
Canada: Refer to CAN/CGA B149.1 and B149.2 Installation Codes for Gas Burning Appliances.
!
WARNING
Gas-fired heaters must be vented. A built in power exhauster is provided. Additional external power exhausters are not required or permitted.
Insufficient ventilation and/or improperly sealed vents may release gas into the building which could result in health problems, carbon monoxide poisoning, or death.
Improper venting may result in fire, explosion, injury, or death.
!
WARNING
Do not vent this appliance into another heater’s vents or through a masonry chimney.
Do not use dampers in the heater vent pipe.
Single Wall vent pipe must not pass through any unoccupied attic, inside wall, concealed space, or floor.
Un-insulated single wall vent pipe must not be used outdoors for venting appliances in regions where winter design temperature is below freezing.
Replacing Existing Equipment
If the heater is replacing existing equipment and using an existing vent system, inspect the venting for proper size and horizontal pitch as directed in these instructions and the latest edition of the National Fuel
Gas Code, ANSI Z223.1 (NFPA 54) or CSA B149.1 Installation Code.
Determine that there is no blockage or restriction, leakage, corrosion or other deficiencies that can cause hazards. The vent pipe should be corrosion-resistant galvanized steel of a thickness that meets the
National Fuel Gas Code. Minimum thickness for connectors varies depending on the pipe diameter. Never vent the LD3 Series with PVC or plastic pipe.
!
WARNING
If replacing an existing heater, vents may require re-sizing. Improperly sized venting systems can result in vent gas leakage or condensation. Refer to the National Fuel Gas
Code ANSI Z223.1 (NFPA 54) or CSA B149.1 - latest edition. Failure to follow these instructions can result in serious injury or death.
23
3.0
Installation
• General Venting Requirements
LD3 Series
General Venting Requirements
The venting system for LD3 Series heaters may terminate horizontally through a sidewall or vertically through the roof, and may be individually or commonly vented. Configuration of the vent termination determines the category type. All model heaters must be installed in accordance to the requirements of this section, as well as the requirements of its category determination, as described in this manual. To determine your applications category type, review ‘Vertical Venting’ (Category I) and ‘Horizontal Venting’
(Category III) sections of this manual.
All LD3 Series Model Requirements:
• Exhaust vent pipe must be 3 inch nominal size.
• Use vent pipe material that is corrosion-resistant galvanized steel of a thickness that meets the
National Fuel Gas Code.
• Do not exceed a maximum vent length of 20 feet.
• Maintain a minimum vent length of 3 feet.
• Maintain a minimum 12 inches of straight pipe from the flue outlet before any directional changes are made in the venting system.
• Have all vent pipe seams or connectors fastened together with at least three corrosion resistant sheet metal screws (field supplied).
• Maintain a 6 inch clearance around all single wall vent pipe from any combustible materials. For double wall vent pipe (type B) follow the vent manufacturer’s clearance to combustibles.
• The equivalent length for a 3 inch 90° elbow is 3 feet.
• The equivalent length for a 4 inch 90° elbow is 5 feet.
• Avoid using more than two 90° directional changes in the venting system.
• Horizontal sections of the vent pipe must be installed with an upward slope from the appliance at a pitch of ¼ inch per foot.
• Suspend and secure all horizontal runs at points no greater than 3 feet apart.
• Vent termination must maintain a minimum distance of 6 feet from any mechanical air supply inlet.
• Vent must terminate a minimum of 4 feet below, 4 feet horizontally from, or 1 foot above any window or door that may be opened or gravity air inlet into the building.
• Vent must terminate a minimum of 4 feet above grade level and must extend beyond any combustible overhang. Vents adjacent to the public walkways must terminate a minimum of 7 feet above grade level.
• The vent terminal must be installed to prevent any blockage by snow and protect building material from degradation by flue gases.
• The vent cap must be a minimum of 6 inches from the sidewall of the building.
• Vent must be a minimum of 36 inches below or extend beyond any combustible overhang.
• Consult NFPA ANSI Z223.1 Gas Vent Termination criteria for vents that terminate on a roof pitch that exceeds 9:12.
•
Canada: Vents must terminate a minimum of 3 feet from a window or door that may be opened, and a non-mechanical air supply inlet or combustion air inlet into the building.
24
LD3 Series
Figure 3.17 •
General Venting Requirements
3.0
Installation
• General Venting Requirements
Vent Cap
24 in.
Min.*
Roof*
Storm Collar
Adjustable Roof Flashing
Double-Wall B Vent 1 in. Minimum Clearance
(Use attic insulation shield if required)
Fire Stop Spacer
Heater
B to C Adapter
Clean Out Tee Fitting
Clean Out Cap
#8 Sheet Metal Screws (field supplied)
*Consult the NFPA ANSI Z223.1 Gas Vent Termination criteria if roof pitch exceeds 9:12
When possible, avoid venting through an unconditioned space. Venting through an unconditioned space promotes condensation. When venting through an unconditioned space is unavoidable, or if the unit is installed in an area that is prone to condensation, insulate venting runs greater than 5 feet to minimize the production of condensation. Inspect for leakage prior to insulating the venting and only use insulation that is non-combustible with a temperature rating of not less than 400°F. Install a tee fitting at the low point of the vent system and provide a drip leg with a clean out cap as shown in Figure 3.17.
When venting pipe passes through a combustible interior wall or floor, a metal thimble with a diameter 4 inches greater than the vent pipe diameter must be used. If there is 6 feet or more of vent pipe prior to passing through the combustible wall or floor, then the metal thimble need only be 2 inches greater than the vent pipe diameter. If a metal thimble is not used, all clearance to combustibles from the vent pipe must be 6 inches. Where permitted, type B vent may be used for the last section of vent pipe to reduce the required clearance to combustibles when passing through a combustible wall or floor. When using type B venting, follow the manufacturer’s recommended clearance to combustibles. Any material used to close or insulate the opening must be non-combustible.
25
3.0
Installation
• Vertical Venting (Category I)
LD3 Series
Vertical Venting (Category I)
An appliance that operates with a non-positive vent static pressure and with a vent gas temperature that avoids excessive condensate production in the vent is said to be ‘Category I’. The LD3 Series heater is considered a Category I appliance if the venting system meets all of the following criteria:
• The vent system terminates vertically (up).
• The length of the horizontal portion of the vent run is less than 75% of the vertical rise length. (e.g.- If the vertical vent height is 10 feet, the horizontal run is less than 7-1/2 feet).
• The vent terminates a minimum of 5 feet above the vent connection on the unit.
For vertical vent termination, the venting must comply with all parts of this section, in addition to the requirements of the general venting.
Category I (Vertical) venting is venting at a non-positive pressure. An appliance vented as a Category I is considered a fan-assisted appliance and the vent system does not have to be ‘gas tight’. It is recommended that the venting system is installed with a tee, drip leg, and clean-out cap as shown in
Figure 3.18.
Vent Locations and Clearances:
• Separate air intake duct from vent pipe by a minimum of 4 feet by placing vent pipes higher than adjacent air intake ducts.
• Utilize a listed type B vent termination cap.
• The vent terminal must extend a minimum of 2 feet above the roof.
• Vent caps should be located a minimum of 2 feet away from adjoining structures.
All vertically vented heaters that are Category I must be connected to a chimney or vent complying with a recognized Standard, or lined masonry (or concrete) chimney with a material acceptable to the authority having jurisdiction. Venting into an unlined masonry chimney is not permitted. Refer to the
National Fuel Gas Code and page 24 of this manual.
Use a listed vent terminal to reduce down drafts and moisture in the vent.
26
LD3 Series
Figure 3.18 •
Rooftop Venting - Side View
Vent Cap
3.0
Installation
• Horizontal Venting (Category III)
24 in. Min.*
Roof
Double-Wall B-Vent Pipe
Firestop Spacer
B to C Adapter
3” Single-Wall Pipe
Heater
Clean Out Tee Fitting
Clean Out Cap
*Consult the NFPA ANSI Z223.1 Gas Vent Termination criteria if roof pitch exceeds 9:12.
Horizontal Venting (Category III)
An appliance that operates with a positive vent static pressure and with a vent gas temperature that avoids excessive condensate production in the vent is said to be ‘Category III’. The LD3 Series heater is considered a Category III appliance if the venting system meets all of the following criteria:
• The vent system terminates horizontally (sideways).
• The vent terminates vertically, but the length of the horizontal portion of the vent run exceeds 75% of the vertical rise length. (e.g.- If the vertical vent height is 10 feet, the horizontal run is greater than
7-1/2 feet).
• The vent terminates below 5 feet of the vent connection on the unit.
Seal vent pipes with high temperature sealant and three (3) #8 sheet metal screws. Vent enclosed spaces and buildings according to the guidelines in this manual and applicable national, state, provincial and local codes.
You may either use an agency certified Category III venting system, or single wall vent pipe with all the seams and joints sealed with metallic tape or silicone sealant suitable for temperatures up to 400°F.
Wrap the tape two full turns around the vent pipe. For single wall vent systems, one continuous section of double wall vent pipe may be used with the vent system to pass through a wall or barrier.
All horizontal Category III vents must be terminated with a Simpson-Duravent sidewall vent cap (P/N:
SWD-4 for 4-inch venting or P/N: DB-208 for 3-inch venting).
27
3.0
Installation
•
Vent Locations and Clearances
•
Sidewall Venting Requirements
LD3 Series
Vent Locations and Clearances:
• Category III venting systems may NOT be common vented, and no other gas units are allowed to be vented into it.
• Vent must terminate a minimum of 4 feet below, 4 feet horizontally from, or 1 foot above any window or door that may be opened or gravity air inlet into the building.
• Vent must terminate a minimum of 3 feet above any forced air inlet that is located within 10 feet.
• Horizontal venting sections of the vent pipe on a Category III termination must be installed with a downward slope from the appliance at a pitch of 1/4 inch per foot. Do not pitch heater.
• The bottom of the vent terminate must be located a minimum of 12 inches above grade level and must extend beyond any combustible overhang. Vents adjacent to public walkways must terminate a minimum of 7 feet above grade level.
• The vent terminal must be installed to prevent blockage by snow and protect building materials from degradation by flue gasses.
• The vent cap must be a minimum of 6 inches from the sidewall of the building.
• Vent must be a minimum of 36 inches below or extend beyond any combustible overhang.
• Vents must terminate a minimum of 3 feet from a window or door that may be opened, and a nonmechanical air supply inlet or combustion air inlet into the building.
• Vents must terminate a minimum of 6 feet from a mechanical air supply inlet.
Never join two sections of double wall vent pipe within one horizontal vent system, as it is impossible to verify that inner pipes are completely sealed.
Figure 3.19 •
Sidewall Venting Requirements
Building Overhang*
36 in. min.*
6 in. min.*
Sidewall
3” Single-Wall Vent Pipe
B to C Adapter
Heater
Sidewall Vent Cap
Wall Thimble
Double-Wall
B-Vent
Single
Wall Vent
1/4 in. downward pitch per foot
*Vent must extend beyond any combustible overhang if the vent is less than 36 in. below the combustible overhang.
28
LD3 Series
3.0
Installation
•
Common Venting (Category I)
•
Common Rooftop Venting
Common Venting (Category I)
The common vent system and all attached appliances must be Category I.
The vent connector should be routed in the most direct route from the units to the common vent.
Where two or more vent connectors enter a common gas vent or chimney flue, the smaller connector shall enter at the highest level consistent with the available head room or clearance to combustible material.
Restrictions within the common vent such as elbows should be minimized. Each elbow installed within the common portion of the vent carrying system reduces the maximum common vent capacity by 10%. Refer to NFPA 54 IFEC tables 11.2 and 11.3 for capacity.
The vent connector capacities allow for the use of two 90° directional changes. For each additional required elbow, the vent connector capacity is reduced by 10%.
The common vent cross sectional area must be equal to or greater than the largest vent connector cross sectional area.
Figure 3.20 •
Common Rooftop Venting - Side View
Rooftop Vent Cap 24 in.
Min.**
Roof
Double-Wall B-Vent
Firestop Spacer
Heater
4” Single-Wall
Vent Pipe
Heater
Dual Exhaust Assembly 3” Single-Wall Vent Pipe
**Consult the NFPA ANSI Z223.1 Gas Vent Termination criteria if roof pitch exceeds 9:12.
29
3.0
Installation •
Combustion Air Requirements LD3 Series
Combustion Air Requirements
Combustion air may be supplied to the heater by indoor or outdoor means. Follow these guidelines and all applicable codes for all models prior to installing the combustion air duct work. Local codes may vary. In the absence of local codes, refer and comply with the National Fuel Code ANSI Z223.1 (NFPA 54) latest edition or the National Standards of Canada.
!
WARNING
Sufficient combustion air must be supplied to the appliance at all times.
Lack of combustion air may result in property damage, serious injury, or death.
This unit comes standard equipped for connection of supplied outdoor air for combustion. It is designed for outside air to be brought into the appliance from combustion intake ducts, and is referred to as a
“Separated Combustion” appliance.
This heater must operate as a separated combustion system if any of the following criteria apply:
• Chemicals such as chlorinated or fluorinated hydrocarbons (typical sources are refrigerants, solvents, adhesives, degreasers, paints, paint removers, lubricants, pesticides, etc.) are present in the atmosphere.
• High humidity.
• Contaminants such as sawdust, welding smoke, etc.
• Negative building pressure.
• Unusually tight construction where the air infiltration rate is less than 0.40 air changes per hour.
If your application does not meet any of these criteria, then room air may be used as supplying combustion air to the heater. Refer to ‘Combustion Air Supply - Room Air’ on page 32 for details on how to utilize room air for combustion.
Figure 3.21 •
Vertical Outside Air Supply for Common Intake
•
Side View
NOTE: Common intake heaters must share the same thermostat.
Roof Intake Cap
18 in. minimum
6” pipe
Air Inlet Connection
Roof
Air Inlet Connection
(Flexible boot and band clamps are recommended)
Burner
Control Box
Burner
Control Box
4” intake pipe 4” intake pipe
30
LD3 Series
3.0
Installation •
Separated Combustion Systems
Separated Combustion Systems (Outside Combustion Air)
All LD3 Series heaters come with a factory-installed combustion air adapter for attaching air intake ducts to the heater. Attach the air intake duct material to the adapter with three (3) non-corrosive sheet metal screws. If necessary, drill pilot holes prior to attaching the air intake ducts. The diameter of the intake ducts must not be smaller than the factory installed adapter.
When operating this unit as a separated combustion heater system, combustion air must be supplied to the heater by outdoor means through the factory installed vent connector. The combustion air intake duct may terminate horizontally through a sidewall or vertically through the roof. Ideally, the intake should terminate within the same pressure zone as the venting terminates, which should minimize the effects of wind.
All Separated Combustion systems must comply with the following items:
• Air intake ducts must be of galvanized steel or an equivalent corrosion-resistant material.
• Do not exceed a length of 20 feet.
• Do not exceed more than two (2) 90° directional changes (elbows) in the system.
• Seal all joints with metallic tape or silicone sealant. Wrap the tape two full turns around the vent pipe.
• Slope air intake pipe ¼ inch per foot upward or downward away from the unit.
• Do not draw air from attic space.
• Do not draw fresh air from the remaining space around a chimney liner, gas vent, special gas vent, or plastic piping installed within masonry, metal, or factory built chimney.
• Combustion air ducts may be insulated if they pass through an unconditioned space.
• A factory approved sidewall intake cap must be used when terminating the combustion air ducts horizontally through the sidewall.
• When combustion air ducts terminate vertically through the roof, a minimum of 18 inches above the roof grade must be maintained.
• Separate the air intake duct from vent pipe a minimum of 4 feet. Also, place vent pipe higher than adjacent air intake duct.
• Air intake duct must terminate a minimum of 3 feet below any forced air vent discharge that is located within 10 feet.
• The bottom of the air intake duct termination must be located a minimum of 12 inches above grade level. Air intake ducts that terminate adjacent to public walkways must be installed a minimum of 7 feet above grade level.
• The air intake duct must be installed to prevent blockage by snow, debris, or other possible obstructions.
31
3.0
Installation •
Separated Combustion Systems
•
Combustion Air Supply
Figure 3.22 •
Outside Combustion Air Vertical Intake - Side View
Combustion Air
Intake Cap
3 ft. Min.
(If X if less than 10 ft.)
18 in.
Min.
X
Storm Collar
Listed
Flashing
LD3 Series
Exhaust Vent
(from any other appliance)
Roof
Cleanout Tee
Air Inlet Connection
(Flexible boot and band clamps are recommended)
Burner
Control Box
Figure 3.23 •
Outside Combustion Air Sidewall Intake - Side View
Listed Wall Thimble
6 in.
Min.
4” Pipe Air Inlet Connection
(Flexible boot and band clamps are recommended)
Combustion Air
Intake Cap
Vent Termination
Support Brackets
1/4 in. pitch per foot
(upward or downward)
Burner
Control Box
Combustion Air Supply - Room Air
Combustion air may be supplied to the heater by indoor or outdoor means.
If using combustion air from indoors, the required volume of the space must be a minimum of 50 ft
3
per
1000 Btu/hr unless the building is of unusually tight construction. If the building is of unusually tight construction with air infiltration rates of less than 0.40 air changes per hour, outside combustion air is typically needed unless the sheer size of the building allows otherwise. Contact the factory for further determination of air infiltration rates.
32
LD3 Series
3.0
Installation •
Combustion Air Supply
•
Optional Unvented Operation
Non-contaminated outside air for combustion must be ducted to the heater if any of the following apply:
• Chemicals such as chlorinated or fluorinated hydrocarbons (typical sources are refrigerants, solvents, adhesives, degreasers, paints, paint removers, lubricants, pesticides, etc.) are present in the atmosphere.
• High humidity.
• Contaminants such as sawdust, welding smoke, etc.
• Negative building pressure.
• Unusually tight construction where there is an air infiltration rate of less than 0.40 per hour.
Optional Unvented Operation
!
WARNING
This appliance must be vented in residential installations. Unvented tube heaters in residential spaces may result in property damage, serious injury, or death. Use unvented operation in commercial and industrial installations with proper ventilation rates only.
When using an unvented configuration (commercial & industrial use only), consider the following:
• A factory vent cap/diffuser (P/N: WVE-3)
must be used.
• Where unvented heaters are used, natural or mechanical means
must be provided to
supply and exhaust a minimum of 4 cfm/1000 Btu/h input of installed heaters.
NOTE: Gravity or mechanical means may be used to accomplish the air displacement.
Local codes may require that the mechanical exhaust system be interlocked with the electrical supply line to the heaters, enabling both to function simultaneously.
• The minimum clearance between the air intake and the exhaust terminal is 4 ft.
NOTE: When installing in a U-tube configuration, use extra caution to separate vent gases from heater intake.
• Exhaust openings for removing the flue products must be located above the level of the
heater(s).
Figure 3.24 • Minimum End Clearances
12 in. Min.
All heaters
12 in. Min.
Unvented heaters
33
3.0
Installation
• Gas Supply
LD3 Series
Gas Supply Installation Instructions
The gas supply to the tube heater must be connected and tested in accordance with national, state, provincial, and local codes along with guidelines in this manual. In the United States refer to the latest edition of the ANSI Z223.1 (NFPA 54) Standard and in Canada refer to the latest edition of the CAN/
CGA B149.1 Standard.
Supply gas piping to the unit should conform with the local and national requirements for type and volume of gas handled, and pressure drop allowed in the line. Avoid pipe sizes smaller than 1/2”.
The installation must conform with local building codes or, in the absence of such codes, the National Fuel
Code (NFPA 54) and in conjunction with ANSI Z21.24/CSA 6.10 “Connectors for Gas Appliances”.
!
WARNING
Improperly connected gas lines may result in serious injury and death, explosion, poisonous fumes, toxic gases, or asphyxiation. Connect gas lines in accordance to national, state, provincial, and local codes.
Gas pressure to the appliance controls must never exceed 1/2 PSI (14” W.C.). Damage to the controls may result.
!
CAUTION
Gas lines should be purged of air as described in ANSI Z223.1 (NFPA 54) or CSA-B149.1– latest edition. Installation of the piping must also conform with the local building codes, or in the absence of local codes, with the latest edition of the National Fuel Gas Code (NFPA 54). In Canada, installation must be in accordance with CSA-B149.1
NOTICE
The total input to the appliance must fall within +/- 5% of the rated input as indicated on the rating plate. Otherwise the heat exchanger may prematurely fail.
IMPORTANT! The heating system will expand and contract during operation. Allowances for expansion
must be made between the connection to the heater and the gas supply. ZA flexible gas connection of approved type is required. Flexible stainless steel gas connectors installed in one plane, and without sharp bends, kinks or twists is recommended.
34
LD3 Series
3.0
Installation
• Gas Supply
IMPORTANT! Before connecting the gas supply to the burner control box:
• Verify that the heater’s gas type (as listed on the rating plate) matches that of your application and
the installation complies with national and local codes and requirements of the local gas company.
• Unless otherwise noted on the rating plate, this infrared heater is designed and orificed to operate
on standard BTU gas. Contact the factory if utilizing non-standard BTU gas.
• Check that the gas piping and service has the capacity to handle the total gas consumption of all
heaters being installed, as well as any other gas appliances being connected to the supply line.
• Check that the main gas supply line is of proper diameter to supply the required fuel pressures.
• If utilizing used pipe, verify that its condition is clean and comparable to a new pipe. Test all gas
supply lines in accordance with local codes.
To connect the gas:
!
WARNING
Failure to install, operate or service this appliance in the approved manner may result in property damage, injury, or death. Only trained, qualified gas installation and service personnel may install or service this equipment.
The LD3 Series heater is equipped to connect to the corrugated stainless steel tube (CSST) flexible gas connector (Included).
Do not connect the main gas line directly to the heaters gas inlet without the
use of the flexible connector. All piping must be installed in accordance with the requirements outlined in the National Fuel Gas Code ANSI/Z223.1 (latest edition) or CSA-B149.1 and B149.2. Support all gas piping with pipe hangers, metal strapping, or other suitable material. Do not rely on the heater to support the gas pipe.
When connecting piping to the unit, the use of a thread joint compound is required. The thread compound
(pipe dope) shall be resistant to the action of liquefied petroleum gas or any other chemical constituents of the gas to be conducted through piping. Use of Teflon
®
tape is not permitted.
!
WARNING
Always use two (2) opposing wrenches to tighten mating pipe connections to prevent excessive torque on the gas valve and manifold pipe. Excessive torque can damage the valve and/or misalign the orifice, resulting in fire, explosion, serious injury, or death.
Install ground joint union with a brass seat and a manual shut-off valve adjacent to the unit for emergency shut-off and easy servicing of controls. A 1/8” NPT plugged tap that is accessible for a test gauge connection is also recommended, as illustrated in Figures 3.25 & 3.26.
A sediment trap must be installed in the supply line in the lowest spot prior to connecting to the heater.
The trap length shall be at least three inches long. Ideally, the trap would be installed as close as possible to the shut-off, as shown in Figure 3.25.
35
3.0
Installation
• Gas Supply
LD3 Series
Connect the main gas supply line with an approved flexible connector or, if the authority having jurisdiction requires rigid piping, the use of approved swing joints may be used. If swing joints are utilized, the heater must be allowed to freely expand and contract without causing undue stress on the gas pipe.
The heater shall not be connected to the building piping system with rigid pipe or semi-rigid metallic tubing, including copper. When using such material, an intermediate connection device that allows for the heater expansion must be used.
The gas outlet must be in the same room as the appliance is installed, and must be accessible. It may not be concealed within or run through any wall, floor or partition. When installing the heater in a corrosive environment (or near corrosive substances), use a gas connector suitable for the environment. Do not use the gas piping to electrically ground the heater.
Installation of the Gas Line to the Heater
1
Install a sediment trap / drip leg in the supply line at the lowest spot prior to the gas ball valve. The trap length shall be at least three inches long. Ideally, the trap would be installed as close as possible to the shut off.
2
Install manual shut off ball valve with optional 1/8” NPT Test connection towards the supply line. The manual shut off ball valve must be located within 6 feet of the appliance’s service access door.
3
Install the 5/8 inch flare to ½” NPT adapter piece downstream of the gas valve as shown in Figure
3.25. This piece is typically included with the flexible gas connector, loosely installed on one of the flare nuts. NOTE: Keep flare surfaces clean and free of sealing compounds. Only the pipe threads require sealing compounds.
4
Form the stainless steel flexible connector into a smooth C-shape, allowing approximately 12 inches between the flexible connector’s end nuts (see Figure 3.25). The connector must reach from the gas supply to the appliance without stretching, kinking, or twisting.
5
Attach the flexible connector to the 5/8” flare adapter on the gas line and the other end to the 5/8” flare on the heaters inlet pipe. DO NOT connect the connector flare nuts directly to pipe threads. Use only the adapters provided.
DO NOT kink, twist or over-torque the connector when installing.
!
CAUTION
When using a stainless steel flexible gas connector, do not attach the connector nuts directly to the gas pipe supply. Connector nuts must be installed to an approved adapter.
Figure 3.25 •
Gas Connection (Flexible Gas
Connection shown)
•
Side View
Ball Valve w/
1/8” NPT Inlet Tap
5/8” O.D. Flare to
1/2” NPT Adapter
12”
3 inch minimum
Drip Leg/
Sediment Trap
2 in. max displacement
Figure 3.26 •
Gas Connection (Flexible Gas
Connection shown)
•
End View
Ball Valve w/ 1/8” NPT Inlet Tap
45°
45°
120V
- 120V HEATER INPUT -
HOT
NEUTRAL
EARTH
G W1 W2 R
Stainless Steel
Gas Connector
5/8” O.D. Flare to
1/2” NPT Adapter
Burner Control
Box Side View
Heater Movement
Burner Control Box End View
36
LD3 Series
3.0
Installation
• Gas Supply
Refer to Chart 3.7 for natural gas and Chart 3.8 for propane to determine the cubic feet per hour (CFH) required for the type of gas and size of unit to be installed. To determine the proper pipe diameter, use the
CFH value and the length of pipe necessary from Chart 3.9. In the case where several units are serviced by the same main gas line, the total capacity (CFH) and length of main must be adequate to service all appliances downstream of this main.
Chart 3.7
• Natural Gas Consumption
Model
LD3-(15,20)-40
LD3-(15,20,30)-50
Input
(High/Low)
40,000 (High)
28,000 (Low)
50,000 (High)
35,000 (Low)
Manifold
Pressure
(Inches W.C.)
3.5
2.2
3.5
2.2
Minimum Inlet
Pressure
(Inches W.C.)
5.0”
5.0
Gas
Consumption*
(CFH)
38.1
26.7
47.6
33.3
* Assumes an average heating value of 1050 BTU/SCF and a Specific Gravity of 0.60.
Orifice Size
31 DMS
29 DMS
Chart 3.8
• Propane Gas Consumption
Model
LD3-(15,20)-40
LD3-(15,20,30)-50
Input
(High/Low)
40,000 (High)
28,000 (Low)
50,000 (High)
35,000 (Low)
Manifold
Pressure
(Inches W.C.)
10.0
5.0
10.0
5.0
Minimum Inlet
Pressure
(Inches W.C.)
11.0
11.0
Gas
Consumption*
(CFH)
16.0
11.2
20.0
14.0
Gallons per Hour*
0.44
0.31
0.55
0.38
* Assumes an average heating value of 2500 BTU/SCF and a Specific Gravity of 1.53.
Orifice
Size
1.90 mm
2.15 mm
Chart 3.9 allows for a 0.3 inch W.C. pressure drop in the supply pressure from the building main to the inlet of the unit. Refer to the chart for the appropriate range of inlet pressures for each gas type. When sizing the inlet gas pipe diameter, make sure that the unit supply pressure can be met after the 0.3 inch W.C. pressure drop has been subtracted from the main pressure. If the 0.3 inch W.C. pressure drop is too high, refer to
NFPA 54 or the Gas Engineer’s Handbook for other gas pipe capacities.
37
3.0
Installation
• Leak Testing
LD3 Series
Chart 3.9
• Maximum capacity for Schedule 40 Metallic pipe, in CFH
Pipe
Length
10 feet
20 feet
30 feet
40 feet
50 feet
60 feet
70 feet
80 feet
90 feet
100 feet
125 feet
150 feet
175 feet
200 feet
73
46
43
40
38
34
63
56
50
31
28
26
1/2” 3/4” 1” 1-1/4” 1-1/2” 2”
Nat Prop Nat Prop Nat Prop Nat Prop Nat Prop Nat Prop
132 86 278 182 520 340 1050 686 1600 1046 3050 1993
92 60 190 124 350 229 730 477 1100 719 2100 1373
152
130
115
105
96
90
84
79
72
64
59
55
48
30
28
26
25
22
41
37
33
20
18
17
285
245
215
195
180
170
160
150
130
120
110
100
99
63
59
55
52
47
85
75
69
42
39
36
590
500
440
400
370
350
320
305
275
250
225
210
186
160
141
127
118
111
105
98
85
78
72
65
890
760
670
610
560
530
490
460
410
380
350
320
386
327
288
261
242
229
209
199
180
163
147
137
582 1650 1078
497 1450 948
438 1270 830
399 1150 752
366 1050 686
346 990 647
320
301
268
930
870
780
608
569
510
248
229
209
710
650
610
464
425
399
Leak Testing
!
WARNING
Testing for gas leaks with an open flame or other sources of ignition may lead to a fire or explosion and cause serious injury or death. Test in accordance with NFPA or local codes.
!
WARNING
Gas pressures to the appliance controls must never exceed 14 inches W.C. (1/2 PSI).
Supply pressures greater than 14” W.C. can damage the controls, resulting in personal injury, property damage, or death.
Use a soap solution or equivalent for leak testing. Leak testing solution must be non-corrosive, and be rinsed off immediately after the leak test. Never test for leak with an open flame. Failure to comply could result in personal injury, property damage or death.
Always leak test final gas assembly for gas leaks according to the procedures outlined in NFPA 54 and all local codes and/or Standards.
For leak testing on pressures below 1/2 PSI
Before leak testing, close the field installed manual shut off valve shown on Figure 3.25 on the supply line to isolate the gas valve from the pressure.
NOTE: All factory installed gas connections have passed an approved leak test.
For leak testing on pressures above 1/2 PSI
When leak testing with pressures above 1/2 PSI (14 inches W.C.), the unit must be isolated from the supply pipe. Close the field installed manual shut off valve, disconnect the supply line to the unit, and temporarily cap the supply line for testing purposes.
38
LD3 Series
3.0
Installation
• Electrical Requirements and Wiring Diagrams
Electrical Requirements and Wiring Diagrams
!
WARNING
Shock hazard. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.
Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rating of at least 105°C.
All field installed wiring to the tube heater must be done in accordance with the national, state, provincial, local codes and to the guidelines in this manual. In the United States, refer to the most current revisions to the Electrical Code ANSI/NFPA 70 and in Canada refer to the most current revisions to the Canadian Electrical Code CSA C22.1 Part 1. The unit must be electrically grounded according to these codes. Line polarity must be observed when making field connections.
Internal Wiring Diagrams
Before wiring this appliance, check the existing wiring; replace if necessary. If any of the original wire supplied with the appliance must be replaced, it must be replaced with copper wiring material having a rating of at least 600V, 105°C.
Figure 3.27 •
LD3 Internal Wiring Diagram
39
3.0
Installation
• Field Wiring Supply Voltage • Thermostat Connection
LD3 Series
Field Wiring Supply Voltage
Before proceeding with electrical connections, ensure that the supply voltage, frequency, phase and current capacity meet the requirements specified on the rating plate. A dedicated line voltage supply with properly sized wire should run directly from the main electrical panel to the heater. The power to the unit must be protected with a circuit breaker appropriate for the load. The unit must be electrically grounded in accordance with local codes, or in their absence, with the latest edition of the National
Electrical Code, ANSI / NFPA 70 and/or the Canadian Electrical Code CSA C22.1, latest edition.
!
CAUTION
The power supply to the heater must be within +/- 5% of the voltage rating as indicated on the rating plate of the appliance. If input power does not meet these specifications, contact your utility company.
The heater comes equipped with a supply cord to connect the main power supply. It is located at the rear of the heater’s burner box, and utilizes a grounding prong. This plug must be connected into an appropriate outlet receptacle that is properly installed and grounded in accordance to local codes and ordinances.
!
WARNING
Electric Shock Hazard
Do not force the three-prong plug into the grounded outlet, modify the plug, or use an adapter. Never operate this appliance if the cord or plug is damaged.
The grounding receptacle must be installed within 5 feet of the heater’s service panel, and located in the space occupied by the appliance. When plugging in the heater, make sure the supply cord is protected from damage, and keep all cords away from the heater’s surfaces and out of the clearance to combustible zones (see page 9). When routing the electrical supply for the unit, ensure that it does not interfere or obstruct the heater’s service panel.
Thermostat Connection
NOTE: Different thermostats operate according to their particular features. Refer to the thermostat’s specifications for details.
Prior to connecting the thermostat wire to the heater, check to make sure the wires will be long enough to allow for the heater to freely expand and contract without causing undue strain on the wires or terminal. Use 18 gauge wire (or larger) that is suitable for a NEC Class 2 rating for thermostat connections.
Each LD3 Series heater requires a two-stage thermostat rated for 24VAC to operate. The heater comes standard with a terminal strip for making the thermostatic connection, located on the back panel.
40
LD3 Series
3.0
Installation
• Thermostat Connection
The thermostat terminal designations are as follows:
R: 24VAC Power
W1: Call for Heat - Low Fire
W2: Call for Heat - High Fire
C: Common for 24VAC Power (if required for thermostat power)
24VAC is supplied from an internal 40VA transformer.
DO NOT supply 24 Volts to the terminal strip.
Figure 3.28 • Single Two-Stage Heater, Single Thermostat Connection
Two-Stage
Thermostat
R
OPTIONAL 24V COMMON
CHECK THERMOSTAT
INSTRUCTIONS TO SEE
IF NEEDED.
W1
W2
C
Controlling Multiple Heaters with a Single Control Device
When multiple heaters are operated by the same control device (for example, common vented heaters), an external relay kit (Part #ERK) must be utilized per heater. This allows the heater’s 24V supply voltage to be isolated from the external control voltage of the thermostats. The ERK is to be installed on or near the heater. Follow the instructions that accompany the accessory for more information and wiring diagrams.
Figure 3.29
• Multiple Heaters, Single Thermostat Connection with External Relay Kit
HEATER
TERMINAL
HEATER
TERMINAL
THERMOSTAT
R
W1
W2
C
OPTIONAL 24V COMMON
CHECK THERMOSTAT
INSTRUCTIONS TO SEE
IF NEEDED
TRANSFORMER
RELAY BOX
P/N: ERK
(1 PER HEATER)
C W1 W2
RELAY BOX
P/N: ERK
(1 PER HEATER)
C W1 W2
L1
L2
HEATER
TERMINAL
RELAY BOX
P/N: ERK
(1 PER HEATER)
C W1 W2
NOTE: W2 NOT USED ON SINGLE STAGE SCENARIOS
Thermostat Location
The location of the thermostat should be determined by the desired heating requirements and be mounted on an inside wall five (5) feet above the finished floor. Locate the thermostat in a conspicuous location, away from where it could be influenced by heat from the unit or other sources, as this may cause the unit to short cycle. Care should be given to locate the thermostat away from drafts or frequently opened doors. To prevent drafts inside the wall from affecting the thermostat’s performance, plug hole for the wire with insulation or suitable caulk. For further information, see the accompanying instructions with the thermostat.
41
3.0
Installation
• Unit Start-up (Commissioning) • Pre-Start Up Checks
LD3 Series
Unit Start-up (Commissioning)
!
WARNING
Improper installation, adjustment, alteration, service, or maintenance can cause property damage, serious injury, or death. This heater must be installed and serviced by a trained gas installation and service personnel only.
!
CAUTION
Shock Hazard.
Before attempting to perform any service or maintenance, turn electrical power to unit
OFF at disconnect switch.
Pre-Start Up Checks
Verify that the installation conforms to all of the specifications of the manual, as well as with local, state, national, and provincial codes. In absence of local codes, the radiant heater must be installed according to the current National Fuel Gas Code ANSI Z223.1 (NFPA 54). In Canada, the installation must conform to the current National Standard of Canada CSA-B149 Sections 1 &
2.
Prior to starting up the unit, verify that:
9
The gas type listed on the rating label matches that of your application.
9
The gas connections have been purged of air and properly leak tested.
9
The voltage type and frequency listed on the rating label matches that of your application.
9
The unit is properly grounded as per the National Electrical Code, ANSI/NFPA 70 or
Canadian Electrical code CSA C22.1 Part 1.
9
The unit is properly mounted to a permanent structure able to bear the weight of the unit.
9
The proper mounting height is observed for the application.
9
All clearance to combustible distances or service clearances are maintained.
9
The unit is properly isolated or installed to prevent excessive vibration.
9
The unit is level horizontally.
9
Venting is properly installed in accordance with this manual and any applicable codes.
9
Combustion air supply is sufficient to support proper operation at all times.
42
LD3 Series
3.0
Installation •
Verify Proper Inlet Pressure
Verify Proper Inlet Pressure
Before starting up the unit, smell all around the heater for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
When turning the gas shut off valve, only use your hand. Never use tools to turn the knobs, as it may damage the valve resulting in a fire or explosion. If the knob is stuck, do not try to repair it, contact a qualified service technician or your local gas company.
To verify the proper inlet pressures, follow the following steps:
1
Turn off the gas supply at the manual gas shut off valve.
2
Remove the inlet pressure tap plug on the gas control valve (see Figure 3.30).
3
Install a 1/8 inch NPT hose connector and connect the pressure gauge tube.
4
Turn on the gas supply at the manual gas shut off valve.
5
Turn on the electrical power to the heater.
6
To light the burner, set the room thermostat to a point above room temperature.
NOTE: This heater is equipped with an ignition device, which automatically lights the burner.
This heater cannot be lighted manually. Do not try to light the burner by hand.
Verify minimum inlet gas supply pressure:
7
Turn on all other gas appliances that are on the same supply line. If the other gas appliances
have multiple inputs, set it to the maximum rating.
8
Observe the pressure rating on the pressure gauge.
The minimum inlet gas supply pressure for:
• Natural gas is 5.0 inches W.C.
• Propane gas is 11.0 inches W.C.
Verify maximum inlet gas supply pressure:
9
Turn off all other gas appliances on the same supply line.
10
Observe the pressure reading on the pressure gauge.
The maximum inlet gas supply pressure for:
• Natural gas is 14.0 inches W.C.
• Propane gas is 14.0 inches W.C.
IMPORTANT: If the inlet gas supply pressure is not within the minimum and maximum
range as shown on the rating plate, contact your gas supplier.
Removing pressure gauge from inlet port on gas valve.
Set thermostat or other control device to the lowest set point.
11
After heater has completed the post-purge cycle, turn off the electrical power to the heater.
12
Turn off the gas supply at the manual gas shut off valve.
13
Remove the pressure gauge tube and the 1/8 inch NPT hose connector.
43
3.0
Installation •
Verifying Manifold Pressure LD3 Series
14
Replace the inlet pressure tap plug on the gas control valve.
15
Leak check the re-installed pressure tap plug using a soap solution or equivalent method
as described in ANSI Z223.1 (NFPA 54).
Figure 3.30 •
Gas Valve Shown in OFF Position
Manifold Pressure Port
High Fire
Manifold Pressure
Adjustment Screw
Low Fire
Manifold Pressure
Adjustment Screw
Inlet Pressure
Port
On/Off Switch
Verify Manifold Pressure
Before starting up the unit, smell all around the heater for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
When turning the gas shut off valve, only use your hand. Never use tools to turn the knobs, as it may damage the valve resulting in a fire or explosion. If the knob is stuck, do not try to repair it, contact a qualified service technician or your local gas company.
To verify the proper manifold pressure, follow the following steps:
1
Turn off the gas valve with the switch located on the valve body (see Figure 3.30).
2
Remove the manifold pressure tap plug on the gas control valve(see Figure 3.30).
3
Connect the pressure gauge tube and manometer.
4
Turn on the gas valve with the switch located on the valve body.
5
Turn on the electrical power to the heater.
6
To light the main burner, set the room thermostat to a point above room temperature.
NOTE: This heater is equipped with an ignition device, which automatically lights the burner.
This heater cannot be lighted manually. Do not try to light the burner by hand.
Verify manifold pressure:
7
After the unit has successfully ignited, wait five minutes prior to taking any readings. The
heater must be in a steady state of operation prior to taking a manifold pressure reading.
8
While waiting for the unit to stabilize, observe the characteristics of the flame. The flame
should be stable and should not lift from the burner. The burner color should be light blue,
and not create excessive noise.
44
LD3 Series
3.0
Installation •
Prior to Leaving the Job Site
9
After five minutes, observe the pressure rating on the pressure gauge.
The target manifold gas supply pressure for:
• Natural gas is 3.5 inches W.C.
• Propane gas is 10.0 inches W.C.
NOTE: Manifold pressure of the heater is pre-set at the factory. No adjustment should be
necessary.
During the verification process, a tolerance of
+/- 5%
of the full scale is acceptable due to varying atmospheric conditions.
If manifold pressure is outside of this tolerance, then an adjustment may be necessary.
Removing pressure gauge from manifold port on gas valve:
10
Set thermostat or other control device to the lowest set point.
11
After heater has completed the post-purge cycle, turn off the electrical power to the heater.
12
Turn off the gas valve with the switch located on the valve body (see Figure 3.30).
13
Remove the pressure gauge tube and the manometer.
14
Replace the manifold pressure tap plug on the gas control valve.
15
Leak check the re-installed pressure tap plug using a soap solution or equivalent method
as described in ANSI Z223.1 (NFPA 54).
Prior to leaving the Job Site
Prior to leaving the job site, verify that:
9 Service access door is properly secured to the unit.
9
The heater is clear of any objects that would interfere with the proper air circulation or that
violate the listed clearance to combustibles.
9 Manual gas shut off is ON.
9
Electrical power is ON.
9
Thermostat is set to desired temperature.
9 Properly dispose of all packaging materials.
9 Check to be sure you have all of your tools.
9
Leave the Installation, Operation, Maintenance and Parts Manual with the owner or end user.
Chart 3.10
• Manifold Pressure
Type of Gas
Natural
Required Manifold
Pressure
3.5 Inches W.C.
Propane 10.0 Inches W.C.
Minimum Inlet
Pressure
5.0 Inches W.C.
11.0 Inches W.C.
Maximum Inlet
Pressure
14.0 Inches W.C.
14.0 Inches W.C.
Pressure Equivalents: 1 Inch W.C. equals .058 oz/sq. in. equals 2.49 mbar.
45
3.0
Installation •
High Altitude Operation
LD3 Series
High Altitude Operation
!
WARNING
Explosion hazard. This heater must be converted by a trained gas installation and service personnel only. Failure to comply could result in personal injury, asphyxiation, death, and fire or property damage.
High altitude operation of this tube heater is approved, without modification, for elevations up to 6,000 feet
(1,829 m) above MSL (sea level) in the United States. If the heater is being installed at an elevation above
6,000 ft, the input rate will have to be de-rated to ensure proper operation. The deration is achieved by a gas orifice change. Contact the factory for installations above these elevations.
46
LD3 Series
4.0
Operation
4.0
Operation
• Operating Instructions
!
WARNING
This appliance does not have a pilot ignition. It is equipped with an ignition device which automatically lights the burner.
Do not attempt to light the system by hand.
BEFORE OPERATING, smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle to the floor. Refer to page 1 “If you smell gas” and on safety label affixed to the heater.
Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
Operating Instructions
!
WARNING
Use only your hand to turn the manual shutoff. Never use tools. If the knob will not turn by hand, don’t try to repair it; call a qualified technician.
Force or attempted repair may result in a fire or explosion.
Lighting Procedures
:
1
STOP! Read the safety information above.
2
Set the thermostat to the lowest setting.
3
Turn OFF all electrical power to the appliance.
4
Turn manual shutoff clockwise to “OFF”.
5
Wait five (5) minutes to clear out any gas. If you smell gas STOP! Follow the safety information found on page 1 “If you smell gas” and on safety label affixed to the heater. If you do not smell gas, proceed to step 6.
6
Turn manual shutoff knob counterclockwise to “ON”.
7
Turn ON all electrical power to the appliance.
8
Set thermostat to desired setting.
9
If the appliance will not operate, follow instructions below to turn OFF gas to the appliance and call your service technician or gas supplier.
Shutdown Procedures
:
1
Set the thermostat to the lowest setting.
2
Turn OFF all electrical power to the appliance if service is to be performed.
3
Turn manual shutoff knob clockwise to “OFF”.
Do not force.
47
4.0
Operation
• Sequence of Operation
LD3 Series
!
WARNING
This heater must be installed and serviced by trained gas installation and service personnel only.
Do not bypass any safety features or the heater’s built in safety mechanisms will be compromised.
Sequence of Operation
Standby: The ignition module (circuit board)continually checks for internal faults, circuit integrity and relay contact positioning.
Starting Circuit: Upon a call for heat, the control verifies that the burner and exhaust pressure switches are in their proper positions. The control energizes the fan. Once operational static pressure is achieved, the burner pressure switch will close initiating the ignition sequence. The hot surface igniter is powered and the gas valve opens after 45 seconds. If the flame is not sensed, the heater will attempt to re-ignite for a total of 3 trials for ignition before proceeding to soft lockout.
Low Fire Running Circuit: After ignition, the flame rod monitors burner flame. If sense of flame is lost, the control closes the gas valve within one second and a new trial sequence (identical to the starting sequence) is initiated. If flame sense is not established within 8.5 seconds, the heater will attempt two additional ignition sequences before proceeding to soft lockout. The control can be reset by briefly interrupting the power source.
High Fire Running Circuit: The second stage on the gas valve is powered directly from the second stage of the thermostat. In order for high fire to engage, low fire must be energized as well. The thermostat determines which stage to maintain for the desired comfort level.
Shut Down: When the thermostat is satisfied, the fan will enter a two (2) minute post-purge cycle.
Diagnostics
Lockout:
The controls will automatically lockout the heater system when an external or system fault occurs. There are two types of lockout:
Soft Lockout: The heater will attempt to light three times. In the event of a failed attempt to light, (gas pressure, valve, no flame sense etc.), the heater will enter a soft lockout period for 30 minutes and then attempt to light three more times before entering hard lockout mode.
Hard Lockout: If proof of flame is not established, a component failure occurs or blockages are evident, the heater will enter a hard lockout. If lockout occurs, the control can be reset by briefly interrupting the power source. Refer to Charts 4.1 & 4.2 for a description of LED codes.
Externally located operational indicator lights are provided to assist in troubleshooting of the heater. Refer to pages 50-53 for additional troubleshooting.
48
LD3 Series
Figure 4.1 • Operational Indicator Lights
4.0
Operation •
Diagnostics
Light 1
Indicates Pressure
Switch Closes
Light 2
Indicates Low Fire
Operation
Operational Indicator Lights
Light 3
Indicates High Fire
Operation
Chart 4.1 • LED Diagnostic Codes - Capable Controls Board
LED CODE
Initial flash (Red) on power up
FAULT STATUS
Normal operation
Steady flash (Green) during Ignition
Steady on (Green) after flame sense.
Normal operation
Normal operation
1 flash (Red)
2 flashes (Red)
3 flashes (Red)
Ignition failure
Ignitor error
Gas valve error
4 flashes (Red) Line voltage frq. error
5 flashes (Red) Internal control error
6 flashes (Red) Pressure switch error
*Some LED codes have a time delay before the LED will flash.
Chart 4.2 • LED Diagnostic Codes - Fenwal Circuit Board
LED CODE
Initial flash on power up, then steady off
FAULT STATUS
Normal operation
Steady on
1 flash
Module failure/Internal fault
Ignition failure
2 flashes
3 flashes
4 flashes
APS 1 failure
APS 2 failure
Solenoid valve fault/Leaky valve/Flame amplifier fault
No flash on 117V start-up Transformer fault
*Some LED codes have a time delay before the LED will flash.
49
FAULT CODE DELAY*
Immediate
Immediate
1 minute
3 minutes
12 seconds
FAULT CODE DELAY*
Immediate
Immediate
32 minutes
12 minutes
22 minutes
Immediate
Immediate
5.0
Maintenance •
Troubleshooting Guide
5.0
Maintenance
LD3 Series
Turn on control device for heat.
Pressure switch is stuck. Replace faulty switch.
Yes
Does the draft inducer motor turn on?
Yes
Does the pressure switch indicator light turn on?
No
No
Yes
Is the pressure switch light on?
Is the inlet or outlet of the heater obstructed, or is the vent exceeding the recommended lengths?
Remove obstruction or correct vent lengths.
Yes
No
Does the igniter warm up and glow red?
Yes
No
Replace igniter.
Is the igniter physically damaged?
Yes
No
No
Start
Question
Key
Process
Question
Corrective
Action
Does the heater have 120 VAC at the main power connection?
No
Yes
Find source of electrical problem.
Check for loose wiring or restrictions in the hose connection to the pressure switch. Are they acceptable?
Yes
Replace wiring or hose connections.
No
No
Yes
Check voltage at igniter sequence (usually 5 to
15 seconds after call for heat). Is it 120V?
Disconnect igniter and measure the resistance. Is it between 50-400
Ω?
Yes
No
Remove obstruction.
Is the inlet or the outlet of the unit plugged or obstructed?
Yes
Replace circuit board.
No
Does the valve indicator light turn on?
No
Does the gas valve turn on?
Do you see the burner in the sight glass?
Yes
Yes
No
Gas valve indicator light is burned out.
Replace light.
Correct wiring.
No
Does the gas valve turn on?
No
Yes
Continued on page 52
Check inlet pressure to the heater. Is it within the minimum and maximum allowable range as per the rating plate?
50
Yes
No
Are the wires to and from the gas valve properly connected?
Adjust inlet pressure.
Yes
LD3 Series
5.0
Maintenance •
Troubleshooting Guide
NOTICE
Bypassing any switch is intended for testing purposes only. Do not leave switch bypassed during normal operation or the heater’s built-in safety mechanisms will be compromised.
Check fuse on circuit board and internal controls transformer.
No
Is there 24
VAC across the ‘R’ and ‘C’ terminals?
Yes
Repair thermostat or thermostat wiring.
No
Is there 24
VAC across the ‘W’ and ‘C’ terminals?
Yes
Is the circuit board sending 120 VAC to the draft inducer motor?
No
After approximately 10 seconds of operation, is there a flash code for
Pressure Switch Failure?
Yes
Replace circuit board.
Check for loose wiring or restrictions in hose connections to pressure switch. Are the OK?
No
No
Replace pressure switch after verifying:
• Heater, blower, and
venting are clean and
free of obstructions.
• The allowable vent
length is not exceeded.
• There is not a negative
pressure experienced
at the area of intake
(e.g., high winds, attic
space, tightly sealed
building).
Is the pressure switch stuck in the closed position?
Yes
Pressure switch is faulty.
Replace wiring or hose connections.
Yes
*After 10-12 seconds of non-operation has passed, is there a flash code for
APS failure (2 or 3 flashes)?
Yes
No
Yes
Remove obstruction.
Yes
Is the draft inducer impeller obstructed or locked up?
No
The draft inducer motor is faulty and must be replaced.
Replace circuit board.
No
Replace circuit board.
Monitor the voltage on the gas valve terminals during trial for ignition. Is there 24 VAC present during the ignition sequence?
Yes
No
* Refer to LED diagnostic Fault Code Chart.
Gas valve is faulty. Replace.
Check for flash codes on the circuit board.
Replace the ignition module.
Continued on page 53
51
5.0
Maintenance •
Troubleshooting Guide
Continued from page 50
Does the burner light?
No
Yes
Is the gas supply valve to the heater in the ‘ON’ position?
No
Turn on gas supply line.
Yes
Were the gas lines purged of air?
No
Purge gas line.
Does the burner stay on?
No
Yes
Do the burners light and then shut off immediately
(within 1-2 seconds)?
Yes
Check inlet pressure and limit switches.
No
Does the burner stay on for approximately 8-10 seconds and then shut off?
No
Check circuit board for flash codes. Consult factory.
Does the heater stay on until the call for heat ends?
Yes
No
Troubleshooting ends.
For more information, contact your local representative or the factory for further assistance.
The heater can shut down due to:
• Improper grounding
• High winds.
• Taking combustion air from the attic.
• Dirty environment.
• Fluctuating gas pressure.
• Pressure switch opening.
LD3 Series
Yes
Yes
NOTICE
Bypassing any switch is intended for testing purposes only. Do not leave switch bypassed during normal operation or the heater’s built-in safety mechanisms will be compromised.
52
LD3 Series
5.0
Maintenance •
Troubleshooting Guide
Continued from page 51
Check to make sure gas pressure is within minimum and maximum inputs, as indicated on the heater’s rating plate.
Is the gas pressure OK?
No
Correct problem.
Yes
Replace gas valve.
Is the heater properly grounded? Is the heater’s polarity correct?
No
Yes
Replace circuit board.
Correct problem.
Sensing rod is faulty or flame is weak. Check to make sure heater is operating at proper gas pressure as indicated on heater’s rating plate and then, if needed, replace sensing rod.
With a microampmeter, check
DC amperage at flame rod. Is it greater than .07 microamps?
No
Yes
Check to make sure flame sensor wire is OK and then replace circuit board.
The heater is equipped with two safety pressure switches. The burner switch is a normally open switch and the exhaust switch is a normally closed switch. Temporarily place jumpers across the terminals of the exhaust switch (reinstall control box cover).
Does the igniter glow red?
NOTE: If normal operation does not continue after bypassing the exhaust switch, consult factory to troubleshoot the burner switch prior to continuing.
No
Yes
Replace the appropriate pressure switch
after verifying:
• There is continuity across the thermal fuse.
• Heater, fan blowers ,squirrel cage, intake and exhaust are clean and free from dirt and obstructions.
• The 4” air intake pipe does not exceed 20 ft. and/or 2 elbows.
• There is not a negative pressure experienced at the area of air intake (e.g.; high winds, attic space, tightly sealed building).
If heater does not go into high fire mode:
NOTE: To confirm that the heater is not in high fire mode, check manifold pressure.
If manifold pressure is 3.3” to 3.5” for natural gas or 9” to 10” for propane, the light is faulty and should be replaced.
When the heater is in low fire mode, manifold pressure is approximately 2.0” to 2.5” for natural gas or
5.0” to 6.5” for propane. If this is the case, the following troubleshooting steps should be followed:
On the outside of the control box, is there
24V across the ‘W2’ and ‘C’ connectors on the terminal strip?
Yes
Measure voltage across the ‘HI’ and the ‘C’ connectors on the gas valve.
Is it 24V?
No
Yes
No
Repair or replace faulty wiring or thermostat.
Replace gas valve.
Replace relay board.
53
5.0
Maintenance •
Heater Components and Parts List LD3 Series
Figure 5.1 • Burner Assembly Components
13
3094A
83
85
333
84
3002A
331
3098A
245
70
3099A
3044
3140, 3141
3008
3097A
826
331
3023
70A
204
3096A
3011
3012
3050
222
206
221
222A
383
217
321
1013
3001B
205
3094A
3005A
9C
1021
21B
3380
76
212
3252
851C
3093
3062, 3063
3161
10C
1070A
5
14
15
16
17
1325
68B 3010
3115
828
3029
3033F
31D
1428
3014
3004 3020
3003A
Figure 5.2 • Tube & Reflector Components
105
20C/D, 112
106
82, 1078
1088, 3077, 3081, 3088
105
19B
113
579
21B, 220, 1077
3076, 3082
26B
1079
1077
54
LD3 Series
5.0
Maintenance •
Heater Components and Parts List
Chart 5.1 • Tube & Reflector Components
Part No.
TP-5
TP-9C
TP-10C
TP-13
TP-14
TP-15
TP-16
TP-17
TP-19B
TP-20C
TP-20D
TP-21B
TP-26B
TP-31D
TP-68B
TP-70
TP-70A
TP-76
TP-82
Description
Flange Gasket
3/4” Conduit Coupling
4” x 3/4” Metal Conduit
#8 x 1/2" SMS - Drill Tip
Burner Sight Glass Gasket
Burner Sight Glass
Burner Sight Glass Washer
Burner Sight Glass Kit
4" Hanger w/ Reflector Spring
10 Foot Reflector, Aluminum
10 Foot Reflector, Stainless Steel
4" Tube Clamp
4" x 10' Titanium Stabilized Tube
Mounting Bracket (Qty. 2)
Cord Grip Strain Relief Bushing
Air Chamber Gasket, 1/2" x 10-5/16"
Manifold Gasket, 1" x 2-3/4"
Gas Pipe Grommet
4" Reflector Center Support
Part No.
TP-1013
Description
Igniter Cover Plate
TP-1021 Gasket, Igniter Cover Plate
TP-1070A Burner
TP-1077
TP-1078
TP-1079
3" Tube Clamp
3" Reflector Center Support
3" Hanger w/ Reflector Spring
TP-1088
TP-1325
4" to 3" (Belled) x 10' Titanium Stabilized Tube
Isolation Relay, 24VAC Coil
TP-1428 Green Indicator Light, 24VAC
TP-3001B Air Chamber Side Panel, Fan Mount
TP-3002A Plastic End Panel, Control Compartment
TP-3003A Plastic End Panel, Fan Compartment
TP-3004 Control Box
TP-3005A Plastic Top Panel, Valve Compartment
TP-3008 Gas Valve Mounting Bracket
TP-3010
TP-3011
TP-3012
TP-3014
Service Panel Hinge
Igniter Box
Igniter Box Cover
4" Plastic Air Collar w/ Screen
TP-83
TP-84
TP-85
TP-105
TP-106
TP-112
TP-113
TP-204
TP-205
TP-206
TP-212
TP-214
TP-217
24" CSST Flexible Gas Connector
1/2" Female NPT to 3/4" Flare fitting
1/2" Male NPT to 3/4" Flare Fitting
Reflector End Cap, Aluminum
Reflector End Cap Clips
5’ Reflector, Aluminum
Reflector Spring
Gas Orifice (Indicate Size)
Hot Surface Igniter Holder
Glo-Bar Holder Spring Clip
1/2" NPT Nipple, 3"
Hot Surface Igniter Wire & Plug
Pressure Switch Barb
TP-3020
TP-3023
TP-3024
Restrictor Plate (Indicate Size)
Snap-in Bushing
#8 x 1/2" SMS - Point Tip
TP-3029 Thermostat Terminal Board; Two-Stage
TP-3033F Power entry plate with hole for terminal strip; Two-Stage
TP-3044 Manifold Pipe
TP-3050 Hot Surface Igniter
TP-3062 NC Pressure Switch Tubing
TP-3063 NO Pressure Switch Tubing
TP-3076
TP-3077
3" x 5' Aluminized Tube w/ Baffle Dimples
4" to 3" (Belled) x 5' Aluminized Tube w/ Baffle Dimples
TP-3081 4" to 3" (Belled) x 10' Aluminized Tube w/ Baffle Dimples
TP-3082 3" x 10' Aluminized Tube w/ Baffle Dimples
TP-220
TP-221
4" Tube Clamp, Stainless Steel
Gasket, Hot Surface Igniter Holder
TP-3088 4" to 3" (Belled) x 10' Aluminized Tube
TP-3093 #8-32 Cage Nut (Qty. 4)
TP-222 Flame Sensor TP-3094A #8-32 x 1/2" Knurled Thumb Screw (Qty. 4)
TP-222A Flame Sensor Wire
TP-245 3/16” x 1/8” Plastic Gas Valve 90° Vent
TP-3096A Air Chamber Top Panel
TP-3097A Burner Access Cover
TP-321
TP-331
TP-333
TP-383
Gasket, Ignition Plate
#8-32 Ground Screw
Power Cord w/ 3-Prong Plug, 5 foot
Hot Surface Igniter Plate
TP-579
TP-826
4" Hanger
40VA Transformer, 120/24
TP-828 Yellow Indicator Light, 24VAC
TP-851C Ignition Control Circuit Board
TP-3098A Air Chamber Side Panel, Pressure Switch Mount
TP-3099A Component Panel
TP-3115
TP-3140
Inducer Motor Assembly
Two-Stage Gas Valve, Natural Gas
TP-3141
TP-3161
Two-Stage Gas Valve, Propane Gas
Pressure Switch Assembly
TP-3252 Wire Harness
TP-3380 Burner Tube w/ Flange and Fittings
55
5.0
Maintenance •
Routine Inspection LD3 Series
!
WARNING
Personal injury or death may result if maintenance is not performed by properly trained gas installer or service personnel. Contact the installing distributor or place of purchase for service. Do not operate heating system if repairs are necessary.
Allow heater to cool prior to servicing.
Disconnect power to heater before servicing.
Use protective glasses when maintaining the heater.
Routine Inspection:
At least once per year, the heating system should be inspected and serviced by trained gas installation and service personnel only. This inspection should be performed at the beginning of the heating season to insure that all heater components are in proper working order and that the heating system operates at peak performance. Particular attention should be paid to the following items.
• Clearance to Combustibles: Inspect the area near the unit to be sure there is no combustible material located within the minimum clearance requirements listed in this manual. Under no circumstances should combustible material be located within the clearances specified in this manual.
Failure to provide proper clearance could result in personal injury or equipment damage from fire.
• Gas Connection: Inspect the integrity of the gas connection to the heater. Check for leaks, damage, fatigue or corrosion. Do not operate if repairs are necessary and turn off gas supply to the heater.
Contact service personnel.
To check gas tightness of the safety shut-off valves, turn off the manual valve upstream of the appliance combination control. Remove the hex head plug on the inlet side of the combination control and connect a manometer to that tapping.
Turn the manual valve on to apply pressure to the combination control. Note the pressure reading on the manometer, then turn the valve off. Any loss of pressure indicates a leak. If leak is detected, use a soap solution to check all threaded connection. If no leak is found, combination control is faulty and must be replaced before putting appliance back in service.
• Blower Motor: Annual oiling of the blower motor with SAE oil will extend bearing life significantly.
Motors with sealed ball bearings (no oil ports) do not require oiling. Ensure that the squirrel cage in the blower is kept clean. If dirt becomes a problem, installation of outside air intake ducts for combustion is recommended.
Check lubrication instructions on motor. If oiling is required, add three or four drop of SAE 20 electric motor oil.
• After three years or 25,000 hours (for light-duty operation).
• Annually after three years or 8,000 hours (for medium-duty operation).
• Annually after one year or 1,500 hours (for heavy-duty operation).
NOTICE
Never over-oil the motor, or premature failure may occur.
56
LD3 Series
5.0
Maintenance •
Maintenance Checks & Log
• Vent pipe system: Check the outside termination and the connections at the heater. Inspect the vent exhausts for leakage, damage, fatigue, corrosion and obstructions. If dirt becomes a problem, installation of outside air intake ducts for combustion is recommended.
• Combustion air intake system (when applicable): Check for blockage and/or leakage. Check the outside termination and the connection at the heater.
• Heat exchangers: Check the integrity of the heat exchangers. Replace if there are signs of structural failure. Check for corrosion and/or buildup within the tube exchanger passageways.
• Burner: Check for proper ignition, burner flame and flame sense. Flame should extend directly outward from burner without floating or lifting.
• Wiring: Check electrical connections for tightness and/or corrosion. Check wires for damage.
• Gas Connection: Inspect the integrity of the gas connection to the heater. Check for leaks, damage, fatigue or corrosion. Do not operate if repairs are necessary and turn off gas supply to the heater.
Contact service personnel.
Reflectors: To maintain effective infrared heating, always keep both sides of the reflector clean.
Maintenance can vary significantly depending on the environment. Dirt and dust can be vacuumed or wiped with a soap and water solution. Use metal polish if the reflectors are severely dirty.
Contact service personnel if repairs are necessary. Do not operate unit.
Maintenance Log
Date Maintenance Performed Replacement Parts Required
57
5.0
Maintenance •
Limited Warranty LD3 Series
Limited Warranty Terms and Conditions
One-Year Limited Warranty. Radiant Tube Heaters covered in this manual, are warranted by Detroit Radiant
Products Company to the original user against defects in workmanship or materials under normal use for one year after date of purchase. Any part which is determined to be defective in material or workmanship and returned to an authorized service location, as Detroit Radiant Products Company designates, shipping costs prepaid, will be, as the exclusive remedy, repaired or replaced at Detroit Radiant Products Company’s option. For limited warranty claim procedures, see PROMPT DISPOSITION below. This limited warranty gives purchasers specific legal rights which vary from jurisdiction to jurisdiction.
Additional Limited Warranty. In addition to the above mentioned one-year warranty, Detroit Radiant Products
Company warrants the original purchaser an additional extension on the combustion chamber, radiant tubes and stainless steel burner. This extension excludes electrical/purchased components.
General Conditions. The Company will not be responsible for labor charges for the analysis of a defective condition of the heater or for the installation of replacement parts. The warranties provided herein will not apply if the input of the heater exceeds the rated input at time of manufacturing or if the heater in the judgment of the Company has been subjected to misuse, excessive dust, improper conversion, negligence, accident, corrosive atmospheres, excessive thermal shock, excessive vibration, physical damage to the heater, alterations by unauthorized service personnel, operation contrary to the Company’s instructions or if the serial number has been altered, defaced, or removed. The Company shall not be liable for any default or delay in the performance of these warranties caused by contingency beyond its control, including war, government restriction or restraints, strikes, fire, flood, short or reduced supply of raw materials, or parts.
Limitation of Liability. To the extent allowable under applicable law, Detroit Radiant Products Company’s liability for consequential and incidental damages is expressly disclaimed. Detroit Radiant Products Company’s liability in all events is limited to and shall not exceed the purchase price paid.
Warranty Disclaimer. Detroit Radiant Products Company has made a diligent effort to provide product information and illustrate the products in this literature accurately; however, such information and illustrations are for the sole purpose of identification, and do not express or imply a warranty that the products are merchantable, or fit for a particular purpose, or that the products will necessarily conform to the illustrations or descriptions. Except as provided below, no warranty or affirmation of fact, expressed or implied, other than as stated in the “LIMITED
WARRANTY” above is made or authorized by Detroit Radiant Products Company.
Product Suitability. Many jurisdictions have codes and regulations governing sales, construction, installation, and/ or use of products for certain purposes, which may vary from those in neighboring areas. While Detroit Radiant
Products Company attempts to assure that its products comply with as many codes, it cannot guarantee compliance, and cannot be responsible for how the product is installed or used. Before purchase and use of a product, review the product applications, and all applicable national and local codes and regulations, and be sure that the product, installation, and use will comply with them. Certain aspects of disclaimers are not applicable to consumer products: e.g., (a) some jurisdictions do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you: (b) also, some jurisdictions do not allow a limitation on how long an implied warranty lasts, consequently the above limitation may not apply to you: and (c) by law, during the period of this limited warranty, any implied warranties of implied merchantability or fitness for a particular purpose applicable to consumer products purchased by consumers, may not be excluded or otherwise disclaimed.
Prompt Disposition. Detroit Radiant Products Company will make a good faith effort for prompt correction or other adjustment with respect to any product which proves to be defective within limited warranty. For any product believed to be defective within limited warranty, first write or call dealer from whom the product was purchased.
Dealer will give additional directions. If unable to resolve satisfactorily, write to Detroit Radiant Products Company at address below, giving dealer’s name, address, date and number of dealer’s invoice, and describe the nature of the defect. Title and risk of loss pass to buyer on delivery to common carrier. If product was damaged in transit to you, file claim with carrier.
Registration. Register on-line at www.detroitradiant.com/warranty.
58
LD3 Series
Notes
5.0
Maintenance
59
5.0
Maintenance •
Kit Contents Check List LD3 Series
Kit Contents Check List
Chart 5.2 •
Kit Contents for LD3 Series - Reference the column for your model.
LD3 Series Kit Contents
TP-19B 4” Hanger with
Reflector Tension Spring
TP-220 4” Stainless Steel
Tube Clamp
TP-83 24” Stainless Steel
Flexible Gas Connector
TP-106 Reflector
End Cap Clips
TP-1079 3” Hanger with
Reflector Tension Spring
TP-1078 3” Reflector
Center Support (RCS)
TP-82 4” RCS
Part No. Description
TP-19B
TP-21B
TP-33B
TP-82
TP-83
LIOLD3
Filled By:
TP-21B 4” Tube Clamp
TP-1077 3” Tube Clamp
TP-105 Reflector End Cap
TP-33B 1/2” Shut-Off Valve
(Ball Valve & Inlet Tap)
LD3 Series Installation,
Operation and
Maintenance Manual
F/N: LIOLD3
LD3 Series
Installation Manual
The LD3 Series Infrared Tube Heater is a positive pressure, two stage radiant heater system. This manual provides specific information related to the LD3 Series model. All persons involved with the installation, operation and maintenance of the heater system must read and understand the information in this manual.
!
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operation and maintenance instructions thoroughly before installing or servicing this equipment.
This heater must be installed and serviced by trained gas installation and service personnel only. Failure to comply could result in personal injury, asphyxiation, death, fire or property damage.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
In locations used for the storage of combustible materials, signs must be posted to specify the maximum permissible stacking height to maintain the required clearances from the heater to the combustibles. Signs must either be posted adjacent to the heater thermostats or in the absence of such thermostats, in a conspicuous location.
Do not use this heater in indoor living or sleeping quarters, etc.! Installation of a tube heater system in residential indoor living spaces may result in property damage, serious injury, asphyxiation or death.
For Your Safety
If you smell gas:
• Do not try to light any appliance.
• Do not touch any electrical switch.
• Immediately call your gas supplier from a neighbor’s phone.
• Follow the gas supplier’s instructions.
• Do not use any phone in your building. • If you cannot reach your gas supplier, call the fire department.
INSTALLER: Present this manual to the end user.
Keep these instructions in a clean and dry place for future reference.
LIOLD3-Rev. 32513
Print: 1M-12/13 (CDS)
4" Hanger w/ Tension Spring
4" Tube Clamp
1/2” Shut-Off Valve & Inlet Tap
4" Reflector Center Support (RCS)
24" S.S. Flexible Gas Connector
TP-105 Reflector End Cap
TP-106 Reflector End Cap Clips
TP-220 4" Stainless Steel Tube Clamp
TP-1077 3" Tube Clamp
TP-1078 3" Reflector Center Support (RCS)
TP-1079 3" Hanger w/ Tension Spring
LD3 Series Installation Manual
2
8
1
0
1
LD3
15-40
1
0
1
2
1
1
1
2
8
1
1
1
LD3
15-50
2
1
1
1
1
0
0
2
8
1
0
1
LD3
20-40
1
0
1
2
1
1
2
2
8
1
1
1
LD3
20-50
2
1
1
1
1
0
1
2
8
1
1
1
LD3
30-50
2
1
1
2
1
1
2
Approvals
• ANSI Z83.20 and CSA 2.34.
• Indoor approval.
• Certain models are residentially
Certified to CSA No. 7-89.
• Outdoor approval with OD-Kit.
• Commercial approval.
Limited Warranty
• 1 year - Burner box components.
• 3 years - Combustion and radiant tubes.
• 5 years - Stainless steel burner.
• See page 58 for terms and conditions.
Printed in U. S. A.
© 2015 Detroit Radiant Products Co.
21400 Hoover Road • Warren, MI 48089
Phone: (586) 756-0950 Fax: (586) 756-2626 www.detroitradiant.com • [email protected]
60
advertisement
Key Features
- Positive pressure
- Two stage radiant heater
- Commercial/Industrial applications
- Residential applications (Select models)
- Clearance to combustibles
- Suspension
- Venting
- Gas supply
- Electrical requirements
- Operation
Frequently Answers and Questions
What is the clearance to combustibles for this heater?
Can this heater be used in a residential indoor living space?
What are the electrical requirements for this heater?
Related manuals
advertisement
Table of contents
- 3 1.0 Introduction
- 3 Overview
- 3 Heater Components
- 3 Specifications
- 4 Safety Signs and Labels
- 6 Warning Symbols
- 6 Applications
- 7 Standards, Certifications and Government Regulations
- 8 Clearance to Combustibles
- 10 Design Considerations and Prechecks
- 11 Recommended Mounting Heights and Coverages
- 12 Hanger Placement and Suspension
- 16 Radiant Tube Assembly
- 17 Optional Elbow or U-Bend Accessory Configuration
- 19 Burner Control Box Suspension
- 20 Reflector Assembly
- 22 Final Heater Assembly
- 30 Combustion Air Requirements
- 31 Separated Combustion Systems
- 32 Combustion Air Supply - Room Air
- 33 Optional Unvented Operation
- 34 Gas Supply Installation Instructions
- 39 Electrical Requirements and Wiring Diagrams
- 40 Typical Field Wiring
- 40 Thermostat Connection
- 42 Unit Start-up (Commissioning)
- 46 High Altitude Operation
- 47 Operating Instructions
- 48 Sequence of Operation
- 48 Diagnostics
- 50 Troubleshooting Guide
- 54 Heater Components and Parts List
- 56 Routine Inspection
- 58 Limited Warranty
- 60 Kit Contents