- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- Carrier
- Series 120 58PHA/PHX
- User manual
- 52 Pages
Carrier Series 120 58PHA/PHX gas furnace Installation, Start-up, Operating and Service and Maintenance Instructions
Below you will find brief information for Series 120 58PHA/PHX. This gas furnace is designed for use with natural gas, but can be converted for use with propane gas. It features a 4-way multipoise design, allowing for upflow, downflow, or horizontal installation. The furnace also features a high-efficiency induced combustion design, which provides for greater energy savings than traditional furnaces. You can easily control the desired temperature with the thermostat.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
58PHA/PHX Performance Boost 80
4---Way Multipoise
Induced---Combustion Gas Furnace
Input Capacities: 45,000 thru 135,000 Btuh
Series 120
Installation, Start---up, Operating and
Service and Maintenance Instructions
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . .
2 Electrical Controls and Wiring . . . . . . . . . . . . . . . . . . . . .
41
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CODES AND STANDARDS . . . . . . . . . . . . . . . . . . . . . . . . . .
3
4
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Combustion and Ventilation Air . . . . . . . . . . . . . . . . . . . . .
5
5
5
Duct Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Acoustical Lining and Fibrous Glass Duct . . . . . . . . . . . . .
5
5
Gas Piping and Gas Pipe Pressure Testing
Electrical Connections
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ELECTROSTATIC DISCHARGE PRECAUTIONS
PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
5
5
5
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
10
Upflow Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10
Downflow Installation
Horizontal Installation
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
11
13
Filter Arrangement
Air Ducts
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13
14
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . .
16
20
115--V Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20
J--Box Relocation
24 Volt Wiring
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20
21
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VENTING
General
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
21
25
25
Masonry Chimney Requirements . . . . . . . . . . . . . . . . . . .
Appliance Application Requirements . . . . . . . . . . . . . . . .
25
26
Additional Venting Requirements . . . . . . . . . . . . . . . . . . .
Sidewall Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
START--UP, ADJUSTMENT, AND SAFETY CHECK . . . . .
28
28
32
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start--up Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
32
32
Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Check Safety Controls . . . . . . . . . . . . . . . . . . . . . . . . . . .
32
34
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
36
SERVICE AND MAINTENANCE PROCEDURES
Introduction
. . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
41
41
Care and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cleaning and/or Replacing Filter . . . . . . . . . . . . . . . . . . .
42
43
Blower Motor and Wheel
Cleaning Heat Exchanger
Sequence of Operation
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
43
44
45
Wiring Diagrams
Troubleshooting
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
47
47
REPLACEMENT INFORMATION GUIDE . . . . . . . . . . . . .
51
Always Ask For
Use of the AHRI Certified
TM
Mark indicates a manufacturer’s participation in the program. For verification of certification for individual products, go to www.ahridirectory.org.
NOTE: Read the entire instruction manual before starting the installation.
Portions of the text and tables are reprinted from NFPA 54/ANSI
Z223.1--2012E, with permission of National Fire Protection
Association, Quincy, MA 02269 and American Gas Association,
Washington DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI on the referenced subject, which is represented only by the standard in its entirety.
SAFETY CONSIDERATIONS
!
WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in dangerous operation, serious injury, death, or property damage.
Improper installation, adjustment, alteration, service, maintenance, or use could cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified service agency must use only factory--authorized and listed kits or accessories when modifying this product.
!
CAUTION
FURNACE RELIABILITY HAZARD
Improper installation or misapplication of furnace may require excessive servicing or cause premature component failure.
Application of this furnace should be indoors with special attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing.
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions include in literature and attached to the unit. Consult local building codes, the current editions of the National Fuel Gas
Code (NFGC) NFPA 54/ANSI Z223.1 and the National
Electrical Code (NEC) NFPA 70.
Recognize safety information. This is the safety--alert symbol .
When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing furnaces.
2
1. Use only with type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as specified in the “Location” section of these instructions.
3. Provide adequate combustion and ventilation air to the furnace space as specified in “Air for Combustion and
Ventilation” section.
4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in the “Venting” section of these instructions.
5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in the “Gas Piping” section.
6. Always install furnace to operate within the furnace’s intended temperature--rise range with a duct system which has an external static pressure within the allowable range, as specified in the “Start--Up, Adjustments, and Safety
Check” section. See furnace rating plate.
7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. See “Air Ducts” section.
8. A gas--fired furnace for installation in a residential garage must be installed as specified in the warning box in the
“Location” section.
9. The furnace may be used for construction heat provided that the furnace installation and operation complies with the first CAUTION in the LOCATION section of these instructions.
10. These Multipoise Gas--Fired Furnaces are CSA (formerly
A.G.A. and C.G.A). design--certified for use with natural and propane gases (see furnace rating plate) and for installation in alcoves, attics, basements, closets, utility rooms, crawlspaces, and garages. The furnace is factory--shipped for use with natural gas. A CSA listed accessory gas conversion kit is required to convert furnace for use with propane gas.
11. See Fig. 2 for required clearances to combustible construction.
12. Maintain a 1--in. (25 mm) clearance from combustible materials to supply air ductwork for a distance of 36 inches
(914 mm) horizontally from the furnace. See NFPA 90B or local code for further requirements.
13. These furnaces SHALL NOT be installed directly on carpeting, tile, or any other combustible material other than wood flooring. In downflow installations, factory accessory floor base MUST be used when installed on combustible materials and wood flooring. Special base is not required when this furnace is installed on manufacturer’s
Coil Assembly Part No. CAR, CAP, CNRV, and CNPV, or when Coil Box Part No. KCAKC is used. See Fig. 2 for clearance to combustible construction information.
INTRODUCTION
Series 120/C 4--way multipoise Category I fan--assisted furnace is
CSA design--certified. A Category I fan--assisted furnace is an appliance equipped with an integral mechanical means to either draw or force products of combustion through the combustion chamber and/or heat exchanger. The furnace is factory--shipped for use with natural gas.
This furnace is not approved for installation in mobile homes, recreational vehicles, or outdoors. This furnace is designed for minimum continuous return--air temperature of 60_F (16_C)db or intermittent operation down to 55_F (13_C) db such as when
used with a night setback thermostat. Return--air temperature must not exceed 85_F (29_C) db. Failure to follow these return--air temperature limits may affect reliability of heat exchangers, motors, and controls. (See Fig. 3).
5.1
[130.5]
2 1/16
[51.6]
1.7
[43.5]
C
For accessory installation details, refer to the applicable instruction literature.
NOTE: Remove all shipping brackets and materials before operating the furnace.
Ø7/8
[22.2]
9 7/8
[250.7]
8 7/16
[213.5]
5 15/16
[150.7]
5 1/2
[140.3]
Ø7/8
[22.2]
1 15/16
[49.2]
3 7/16
[86.8]
5 7/8
[148.5]
2 5/16
[59]
Ø7/8
[22.2]
JUNCTION BOX
LOCATION
B
AA
29 9/16
[750.7]
27 3/4
[704.7]
6 13/16
[172.3]
5 7/8
5 5/8
[143.3]
5 7/16
[138.5]
1 15/16
[49.2]
9 9/16
[243.3]
4 13/16
[122.2]
Ø7/8
[22.2]
Ø7/8
[22.2]
8 5/8
[219]
Ø1/2
[12.7]
Ø1 3/4
[44.5]
19
[481.7]
7 13/16
[197.8]
9 11/16
[245.4]
11 7/16
[290.7]
33 1/4
[843.9]
27 3/4
[704.7]
Ø1/2
[12.7]
Ø1 3/4
[44.5]
Ø7/8
[22.2]
14 7/8
[337.3]
Ø7/8
[22.2]
21.6
[549.5]
28.39
[721.2]
29
[736.9]
6.1
[155.7]
D
BOTTOM RETURN
WIDTH
3/4
[19.1]
KNOCK OUTS FOR
VENTING(5
22 1/16
[560]
SIDE INLET
(BOTH SIDES)
1
[25.4]
1 1/4
[31.8]
A10290
NOTES:
1. Two additional 7/8---in. (22 mm) diameter holes are located in the top plate.
2. Minimum return---air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer’s recommendations for equivalent diameters.
a. For 800 CFM---16---in. (406 mm) round or 14 1/2 x 12---in. (368 x 305 mm) rectangle.
b. For 1200 CFM---20---in. (508 mm) round or 14 1/2 x 19 1/2---in. (368 x 495 mm) rectangle.
c. For 1600 CFM---22---in. (559 mm) round or 14 1/2 x 22 1/16---in. (368 x 560mm) rectangle.
d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets, a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.
Fig. 1 -- Dimensional Drawing
Table 1 – Dimensions
FURNACE SIZE
045---08/024045
070---16/048070
090---16/048090
A
CABINET
WIDTH
B
OUTLET
WIDTH
14---3/16 (360) 12---9/16 (319)
17---1/2 (445) 15---7/8 (403)
21 (533) 19---3/8 (492)
C
TOP AND
BOTTOM FLUE
COLLAR
9---5/16 (237)
11---9/16 (294)
13---5/16 (338)
D
BOTTOM
INLET WIDTH
12---11/16 (322)
16 (406)
19---1/2 (495)
VENT
CONNECTION
SIZE
4 (102)
4 (102)
4 (102)
SHIP WT.
LB. (KG)
104 (47)
126 (57)
140 (64)
ACCESSORY
FILTER
MEDIA
CABINET SIZE
IN. (MM)
16 (406)
16 (406)
20 (508)
110---20/060110
135---20/060135
21 (533)
24---1/2 (622)
19---3/8 (492)
22---7/8 (581)
13---5/16 (338)
15---1/16 (383)
19---1/2 (495)
23 (584)
4 (102)
4 (102)*
152 (69)
163 (74)
20 (508)
24 (610)
*135 and 155 size furnaces require a 5 or 6---in. (127 or 152 mm) vent. Use a vent adapter between furnace and vent stack. See Installation Instructions for complete installation requirements.
3
Fig. 2 -- Clearances to Combustibles
A10269
4
A02055
Fig. 3 -- Return Air Temperature
CODES AND STANDARDS
Follow all national and local codes and standards in addition to these instructions. The installation must comply with regulations of the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply with the national codes listed below and all authorities having jurisdiction.
In the United States, follow all codes and standards for the following:
Safety
S USA: National Fuel Gas Code (NFGC) NFPA
54--2012/ANSI Z223.1--2012 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B
General Installation
S Current edition of the NFGC and the NFPA 90B. For copies, contact the National Fire Protection Association
Inc., Batterymarch Park, Quincy, MA 02269;
(www.NFPA.org) or for only the NFGC, contact the
American Gas Association, 400 N. Capitol Street,
N.W., Washington, DC 20001 (www.AGA.org).
Combustion and Ventilation Air
S NFGC NFPA54/ANSI Z223.1--2012 Section 9.3, Air for Combustion and Ventilation.
Duct Systems
S Air Conditioning Contractors Association (ACCA)
Manual D, Sheet Metal and Air Conditioning Contractors National Association (SMACNA), or American
Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 2005 Fundamentals Handbook Chapter 35 or 2004 HVAC Systems and Equipment Handbook Chapters 9 and 16.
Acoustical Lining and Fibrous Glass Duct
S Current edition of SMACNA and NFPA 90B as tested by UL Standard 181 for Class I Rigid Air Ducts
Gas Piping and Gas Pipe Pressure Testing
S NFGC NFPA54/ANSI Z223.1--2012; chapters 5, 6, 7, and 8 and National Plumbing Codes.
Electrical Connections
S
National Electrical Code (NEC) ANSI/NFPA 70--2011.
Venting
S NFGC NFPA 54 / ANSI Z223.1--2012; Chapters 12 and 13.
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS PROCEDURE
!
CAUTION
FURNACE RELIABILITY HAZARD
Improper installation or service of furnace may cause premature furnace component failure.
Electrostatic discharge can affect electronic components.
Follow the Electrostatic Discharge Precautions Procedure listed below during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential.
1. Disconnect all power to the furnace. Multiple disconnects maybe required. DO NOT TOUCH THE CONTROL OR
ANY WIRE CONNECTED TO THE CONTROL PRIOR
TO DISCHARGING YOUR
ELECTROSTATIC CHARGE TO GROUND.
BODY’S
2. Firmly touch the clean, unpainted, metal surface of the furnace chassis which is close to the control. Firmly touch the clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily discharged.
3. After touching the chassis, you may proceed to service the control or connecting wires as long as you do nothing to recharge your body with static electricity (for example;
DO NOT move or shuffle your feet, do not touch ungrounded objects, etc.).
4. If you touch ungrounded objects (and recharge your body with static electricity), firmly touch a clean, unpainted metal surface of the furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (ungrounded) furnaces.
6. Before removing a new control from its container, discharge your body’s electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 4 before bringing the control or yourself in contact with the furnace. Put all used and new controls into containers before touching ungrounded objects.
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
5
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED UPWARD.
THE BLOWER IS LOCATED
TO THE RIGHT OF THE
BURNER SECTION, AND
AIR CONDITIONED AIR IS
DISCHARGED TO THE LEFT.
THE BLOWER IS
LOCATED ABOVE THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED DOWNWARD
THE BLOWER IS
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDITIONED AIR IS
DISCHARGED TO THE RIGHT.
A02097
Fig. 4 -- Multipoise Orientations
LOCATION
GENERAL
This multipoise furnace is shipped in packaged configuration.
Some assembly and modifications are required when used in any of the four applications shown in Fig. 4.
This furnace must:
S be installed so the electrical components are protected from water.
S not be installed directly on any combustible material other than wood flooring for upflow applications.
Downflow installations require use of a factory--approved floor base or coil assembly when installed on combustible materials or wood flooring (refer to
SAFETY CONSIDERATIONS).
S be located as close to the chimney or vent and attached to an air distribution system. Refer to Air Ducts section.
S be provided ample space for servicing and cleaning.
Always comply with minimum fire protection clearances shown on the furnace clearance to combustible label.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death, and unit component damage.
Corrosive or contaminated air may cause failure of parts containing flue gas, which could leak into the living space.
Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products. Do not install furnace in a corrosive or contaminated atmosphere. Make sure all combustion and circulating air requirements are met, in addition to all local codes and ordinances.
The following types of furnace installations may require
OUTDOOR AIR for combustion due to chemical exposures:
S Commercial buildings
S Buildings with indoor pools
S Laundry rooms
S Hobby or craft rooms, and
S Chemical storage areas
If air is exposed to the following substances, it should not be used for combustion air, and outdoor air may be required for combustion:
S Permanent wave solutions
S Chlorinated waxes and cleaners
S Chlorine based swimming pool chemicals
S Water softening chemicals
S De--icing salts or chemicals
S Carbon tetrachloride
S Halogen type refrigerants
S Cleaning solvents (such as perchloroethylene)
S Printing inks, paint removers, varnishes, etc.
S Hydrochloric acid
S Cements and glues
S Antistatic fabric softeners for clothes dryers
S Masonry acid washing materials
6
All fuel--burning equipment must be supplied with air for fuel combustion. Sufficient air must be provided to avoid negative pressure in the equipment room or space. A positive seal must be made between the furnace cabinet and the return--air duct to prevent pulling air from the burner area and from draft safeguard opening.
18-IN. (457.2 mm)
MINIMUM TO BURNERS
A93044
Fig. 5 -- Installation in a Garage
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
When the furnace is installed in a residential garage, the burners and ignition sources must be located at least 18 inches above the floor. The furnace must be located or protected to avoid damage by vehicles. When the furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, the furnace must be installed in accordance with the NFGC.
!
CAUTION
PERSONAL INJURY AND/OR PROPERTY
DAMAGE HAZARD
Improper use or installation of this furnace may cause premature furnace component failure.
This gas furnace may be used for heating buildings under construction provided that:
--The furnace is permanently installed with all electrical wiring, piping, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure.
--The furnace is controlled by a thermostat. It may not be
“hot wired” to provide heat continuously to the structure without thermostatic control.
--Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
--The temperature of the return air to the furnace is maintained between 55_F (13_C) and 80_F (27_C), with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per our installation instructions.
--The air temperature rise is within the rated rise range on the furnace rating plate, and the gas input rate has been set to the nameplate value.
--The filters used to clean the circulating air during the construction process must be either changed or thoroughly cleaned prior to occupancy.
--The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all
HVAC system components after construction is completed.
--Verify proper furnace operating conditions including ignition, gas input rate, air temperature rise, and venting according to these installation instructions.
FURNACE
INPUT
(BTUH)
44,000
66,000
88,000
110,000
132,000
Table 2 – Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors
TWO HORIZONTAL DUCTS
(1 SQ. IN./2,000 BTUH)
(1,100 SQ. MM/KW)
Free Area of Opening and Duct
(sq. in. / sq. mm)
22 (14193)
33 (21290)
44 (28387)
55 (35484)
66 (42581)
Round Duct
Diameter
(in./mm)
6 (152)
7 (178)
8 (203)
9 (229)
10 (254)
SINGLE DUCT OR OPENING
(1 SQ. IN./3,000 BTUH)
(734 SQ. MM/KW)
Free Area of Opening and Duct
(sq. In. / sq. mm)
14.7 (9484)
22 (14193)
29.3 (18903)
36.7 (23677)
44 (28387)
Round Duct
Diameter
(in. / mm)
5 (127)
6 (152)
7 (178)
7 (178)
8 (203)
TWO OPENINGS OR VERTICAL
DUCTS
(1 SQ. IN./4,000 BTUH)
(550 SQ. MM/KW)
Free Area of
Opening and Duct
(sq. In. / sq. mm)
Round Duct
Diameter
(In./mm)
11 (7097)
16.5 (10645)
22 (14193)
27.5 (17742)
33 (21290)
4 (102)
5 (127)
6 (152)
6 (152)
7 (178)
FURNACE
110,000
66,000
88,000
+
+
+
WATER HEATER
30,000
40,000
30,000
EXAMPLES: Determining Free Area
TOTAL INPUT
= (140,000 divided by 4,000)
= (106,000 divided by 3,000)
= (118,000 divided by 2,000)
= 35.0 Sq. In. for each two Vertical Ducts or Openings
= 35.3 Sq. In. for a Single Duct or Opening
= 59.0 Sq. In. for each of two Horizontal Ducts
7
ACH*
0.60
0.50
0.40
1,050
1,260
1,575
0.30
0.20
2,100
3,150
0.10
6,300
0.00
*Air Changes/Hour
NP
Table 3 – Minimum Space volumes for 100% combustion, Ventilation, and Dilution from Indoors
30
OTHER THAN FAN---ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE
40 50
FAN---ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
66 88 110
1,400
1,680
2,100
2,800
4,200
8,400
NP
1,750
2,100
2,625
3,500
5,250
10,500
NP
44
Space Volume (ft.
3
)
1,100
1,320
1,650
2,200
3,300
6,600
NP
1,650
1,980
2,475
3,300
4,950
9,900
NP
2,200
2,640
3,300
4,400
6,600
13,200
NP
2,750
3,300
4,125
5,500
8,250
16,500
NP
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected. Never connect return--air ducts to the back of the furnace. (See Fig. 6.)
132
3,300
3,960
4,950
6,600
9,900
19,800
NP
AIR FOR COMBUSTION AND
VENTILATION
Provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with:
S U.S. installations: Section 9.3 of the NFGC
NFPA54/ANSI Z223.1--2012, Air for Combustion and
Ventilation, and applicable provisions of the local building codes.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
The operation of exhaust fans, kitchen ventilation fans, clothes dryers, attic exhaust fans or fireplaces could create a
NEGATIVE PRESSURE CONDITION at the furnace.
Make--up air MUST be provided for the ventilation devices, in addition to that required by the furnace. Refer to Carbon
Monoxide Poisoning Hazard warning in venting section of these instructions to determine if an adequate amount of make--up air is available.
A02054
Fig. 6 -- Prohibit Installation on Back
!
CAUTION
FURNACE CORROSION HAZARD
Failure to follow this caution may result in furnace damage.
Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.
LOCATION RELATIVE TO COOLING EQUIPMENT
The cooling coil must be installed parallel with, or on the downstream side of the unit to avoid condensation in the heat exchangers. When installed parallel with the furnace, dampers or other flow control must prevent chilled air from entering the furnace. If the dampers are manually operated, they must be equipped with means to prevent operation of either unit unless the damper is in the full--heat or full--cool position.
The requirements for combustion and ventilation air depend upon whether or not the furnace is located in a space having a volume of at least 50 cubic feet per 1,000 Btuh input rating for all gas appliances installed in the space.
S Spaces having less than 50 cubic feet per 1,000 Btuh require the OUTDOOR COMBUSTION AIR
METHOD.
S Spaces having at least 50 cubic feet per 1,000 Btuh may use the INDOOR COMBUSTION AIR,
STANDARD or KNOWN AIR INFILTRATION
METHOD.
Outdoor Combustion Air Method
1. Provide the space with sufficient air for proper combustion, ventilation, and dilution of flue gases using permanent horizontal or vertical duct(s) or opening(s) directly communicating with the outdoors or spaces that freely communicate with the outdoors.
2. Fig. 7 illustrates how to provide TWO OUTDOOR
OPENINGS, one inlet and one outlet combustion and ventilation air opening, to the outdoors.
e. One opening MUST commence within 12--in. (300 mm) of the ceiling and the second opening MUST commence within 12--in. (300 mm) of the floor.
f. Size openings and ducts per Fig. 7 and Table 2.
8
1 SQ IN.
PER 4000
BTUH*
CIRCULATING AIR
DUCTS
VENT THROUGH ROOF
DUCTS
TO
O UTDOORS
(305mm)
12
″ MAX
1 SQ IN.
PER 2000
BTUH*
B
D
VENT
THR OUGH
R OOF
″
MAX
(305mm)
F
1 SQ IN .
PER
4000
BTUH*
DUCT S
TO
OUTDOORS
1 SQ IN .
PER
4000
BTUH*
1 SQ IN.
PER 2000
BTUH*
(305mm)
A
E
G
C
″
MAX
(305mm)
(305mm)
CIRCULA TING AIR DUCT S
DUCT
TO
OUTDOORS
1 SQ IN.
PER 4000
BTUH*
*Minimum dimensions of 3 in. (76 mm).
NOTE: Use any of the following combinations of openings:
A&B, C&D, D&E, F&G
A03174
Fig. 7 -- Air for Combustion, Ventilation, and Dilution from
Outdoors
g. TWO HORIZONTAL DUCTS require 1 square inch of free area per 2,000 Btuh (1,100 mm
2
/kW) of combined input for all gas appliances in the space per Fig. 7 and
Table 2.
h. TWO OPENINGS OR VERTICAL DUCTS require 1 square inch of free area per 4,000 Btuh (550 mm
2
/kW) for combined input of all gas appliances in the space per
Fig. 7 and Table 2.
3. ONE OUTDOOR OPENING requires: a. 1 square inch of free area per 3,000 Btuh (734 mm
2
/kW) for combined input of all gas appliances in the space per
Table 2 and b. Not less than the sum of the areas of all vent connectors in the space.
The opening shall commence within 12” (300 mm) of the ceiling.
Appliances in the space shall have clearances of at least 1” (25 mm) from the sides and back and 6” (150 mm) from the front.
The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
Indoor Combustion Air -- NFPA & AGA
Standard and Known--Air--Infiltration Rate Methods
Indoor air is permitted for combustion, ventilation, and dilution, if the Standard or Known--Air--Infiltration Method is used.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in death and/or personal injury.
Many homes require air to be supplied from outdoors for furnace combustion, ventilation, and dilution of flue gases.
The furnace combustion air supply must be provided in accordance with this instruction manual.
INTERIOR
HEATED
SPACE
12" MAX
(305mm)
1 SQ IN.
PER 1000
BTUH* IN DOOR
WALL
UNCONFINED
SPACE
6" MIN (152mm)
(FRONT)
Ü
1 SQ IN.
PER 1000
BTUH* IN DOOR
WALL
12" MA X (305mm)
CIRCULATING AIR DUCTS
*Minimum opening size is 100 in.
2 mm).
with minimum dimensions of 3 in. (76
*Minimum of 3 in. (76 mm), when type ---B1 vent is used.
A03175
Fig. 8 -- Air for Combustion, Ventilation, and Dilution from
Indoors
The Standard Method:
1. The space has no less volume than 50 cubic feet per 1,000
Btuh of the maximum input ratings for all gas appliances installed in the space and
2. The air infiltration rate is not known to be less than 0.40
air changes per hour (ACH).
The Known Air Infiltration Rate Method shall be used, if the infiltration rate is known to be:
1. Less than 0.40 ACH and
2. Equal to or greater than 0.10 ACH
Infiltration rates greater than 0.60 ACH shall not be used. The minimum required volume of the space varies with the number of
ACH and shall be determined per Table 3 or Equations 1 and 2.
Determine the minimum required volume for each appliance in the space and add the volumes together to get the total minimum required volume for the space.
Table 3 -- Minimum Space Volumes were determined by using the following equations from the National Fuel Gas Code ANSI
Z223.1--2012/NFPA 54--2012, 9.3.2.2:
1. For other than fan--assisted appliances, such as a draft hood--equipped water heater:
Volume
Other
3
I
other
1000 Btu/hr
2. For fan--assisted appliances such as this furnace:
Volume
Fan
3
I
fan
1000 Btu/hr
A04002
9
A004003
If:
Iother = combined input of all other than fan--assisted appliances in Btuh/hr
Ifan = combined input of all fan--assisted appliances in Btuh/hr
ACH = air changes per hour (ACH shall not exceed 0.60.)
The following requirements apply to the Standard Method and to the Known Air Infiltration Rate Method.
1. Adjoining rooms can be considered part of a space if: a. There are no closeable doors between rooms.
b. Combining spaces on same floor level. Each opening shall have free area of at least 1 in.
2
/1,000 Btuh (2,000 mm
2
/kW) of the total input rating of all gas appliances in the space, but not less than 100 in.
2
(0.06 m
2
). One opening shall commence within 12” (300 mm) of the ceiling and the second opening shall commence within 12”
(300 mm) of the floor. The minimum dimension of air openings shall be at least 3 in. (80 mm). (See Fig. 8.) c. Combining space on different floor levels. The volumes of spaces on different floor levels shall be considered as communicating spaces if connected by one or more permanent openings in doors or floors having free area of at least 2 in.
2
/1,000 Btuh (4,400 mm rating of all gas appliances.
2
/kW) of total input
2. An attic or crawlspace may be considered a space that freely communicates with the outdoors provided there are adequate permanent ventilation openings directly to outdoors having free area of at least 1--in.
2
/4,000 Btuh of total input rating for all gas appliances in the space.
3. In spaces that use the Indoor Combustion Air Method, infiltration should be adequate to provide air for combustion, permanent ventilation and dilution of flue gases.
However, in buildings with unusually tight construction, additional air MUST be provided using the methods described in the Outdoor Combustion Air Method section.
Unusually tight construction is defined as construction with: a. Walls and ceilings exposed to the outdoors have a continuous, sealed vapor barrier. Openings are gasketed or sealed and b. Doors and openable windows are weatherstripped and c. Other openings are caulked or sealed. These include joints around window and door frames, between sole plates and floors, between wall--ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines, etc.
Combination of Indoor and Outdoor Air
1. Indoor openings shall comply with the Indoor Combustion Air Method below and,
2. Outdoor openings shall be located as required in the Out-
door Combustion Air Method mentioned previously and,
3. Outdoor openings shall be sized as follows: a. Calculate the Ratio of all Indoor Space volume divided by required volume for Indoor Combustion Air Method below.
b. Outdoor opening size reduction Factor is 1 minus the Ratio in a. above.
c. Minimum size of Outdoor openings shall be the size required in Outdoor Combustion Air Method above multiplied by reduction Factor in b. above. The minimum dimension of air openings shall be not less than 3 in. (80 mm).
INSTALLATION
UPFLOW INSTALLATION
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove two screws holding bottom filler panel. (See Fig. 9.)
Bottom
Closure Panel
Bottom Filler Panel
Fig. 9 -- Removing Bottom Closure Panel
A10273
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. This panel MUST be in place when only side return air is used.
NOTE: Side return--air openings can be used in UPFLOW and most HORIZONTAL configurations. Do not use side return--air openings in DOWNFLOW configuration.
Leveling Legs (If Desired)
In upflow position with side return inlet(s), leveling legs may be used. (See Fig. 10.) Install field--supplied, 5/16 x 1--1/2 in. (8 x
38 mm) (max) corrosion--resistant machine bolts, washers and nuts.
NOTE: Bottom closure must be used when leveling legs are used. It may be necessary to remove and reinstall bottom closure panel to install leveling legs. To remove bottom closure panel, see
Item 1. in Bottom Return Air Inlet section.
To install leveling legs:
1. Position furnace on its back. Locate and drill a hole in each bottom corner of furnace. (See Fig. 10.)
2. For each leg, install nut on bolt and then install bolt and nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat washer if desired.)
10
5/
16
(8mm)
(8mm)
5/
16
1 3 /
(44mm)
1 3 /
(44mm)
(8mm)
5 /
16
(8mm)
5/
16
(44mm) 1 3/
4
(44mm)
1 3/
4
A89014
Fig. 10 -- Leveling Legs
4. Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement.
5. Reinstall bottom closure panel if removed.
DOWNFLOW INSTALLATION
NOTE: For downflow applications, this furnace is approved for use on combustible flooring when any one of the following 3 accessories are used:
S Special Base, KGASB
S Cased Coil Assembly Part No. CNPV, CNRV, CAP, or
CAR
S Coil Box Part No. KCAKC
1. Determine application being installed from Table 4.
2. Construct hole in floor per Table 4 and Fig. 11.
3. Construct plenum to dimensions specified in Table 4 and
Fig. 11.
4. If downflow subbase KGASB is used, install as shown in
Fig. 12. If Coil Assembly Part No. CNPV, CNRV, CAP and CNR or Coil Box Part No. KCAKC is used, install as shown in Fig. 13.
NOTE: It is recommended that the perforated supply--air duct flanges be completely folded over or removed from furnace when installing the furnace on a factory--supplied cased coil or coil box.
To remove the supply--air duct flange, use wide duct pliers or hand seamers to bend flange back and forth until it breaks off. Be careful of sharp edges. (See Fig. 14.)
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove two screws holding bottom filler panel. (See Fig. 9.)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws
B
A
PLENUM
OPENING
D
C
FLOOR
OPENING
Fig. 11 -- Floor and Plenum Opening Dimensions
A96283
FURNACE
(OR COIL CASING
WHEN USED)
COMBUSTIBLE
FLOORING
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
Fig. 12 -- Furnace, Plenum, and Subbase Installed on a Combustible Floor
A96285
11
FURNACE
APPROVED
COIL ASSEMBLY
OR
COIL BOX
COMBUSTIBLE
FLOORING
SHEET METAL
PLENUM
FLOOR
OPENING
A08556
Fig. 13 -- Furnace, Plenum, and Coil Assembly or
Coil Box Installed on a Combustible Floor
FURNACE
CASING
WIDTH
14–3/16
(360)
17–1/2
(445)
21
(533)
24---1/2
(622)
Table 4 – Opening Dimensions -- In. (mm)
APPLICATION
Upflow Applications on Combustible or Noncombustible Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring (KGASB subbase not required)
Downflow applications on combustible flooring (KGASB subbase required)
Downflow Applications on Combustible Flooring with CNPV,
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box
(KGASB subbase not required)
Upflow Applications on Combustible or Noncombustible Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring (KGASB subbase not required)
Downflow applications on combustible flooring (KGASB subbase required)
Downflow Applications on Combustible Flooring with CNPV,
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box
(KGASB subbase not required)
Upflow Applications on Combustible or Noncombustible Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring (KGASB subbase not required)
Downflow applications on combustible flooring (KGASB subbase required)
Downflow Applications on Combustible Flooring with CNPV,
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box
(KGASB subbase not required)
Upflow Applications on Combustible or Noncombustible Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring (KGASB subbase not required)
Downflow applications on Combustible flooring (KGASB subbase required)
Downflow Applications on Combustible Flooring with CNPV,
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box
(KGASB subbase not required)
19
(483)
23
(584)
22---7/8
(581)
22---1/8
(562)
22---1/2
(572)
16
(406)
15---7/8
(403)
15---1/8
(384)
15---1/2
(394)
19---1/2
(495)
19---3/8
(492)
18---5/8
(473)
PLENUM OPENING
A
12---11/16
(322)
12---9/16
(319)
11---13/16
(284)
12---5/16
(313)
B
21---5/8
(549)
19
(483)
19
(483)
19
(483)
19
(483)
21---1/8
(537)
19
(483)
19
(483)
19
(483)
21---5/8
(549)
19
(483)
19
(483)
19
(483)
21---5/8
(549)
19
(483)
19
(483)
20
(508)
23---5/8
(600)
23---1/2
(597)
23---3/4
(603)
23---1/2
(597)
16---5/8
(422)
16---1/2
(419)
16---3/4
(425)
16---1/2
(419)
20---1/8
(511)
20
(508)
20---1/4
(514)
FLOOR OPENING
C
13---5/16
(338)
13---3/16
(335)
13---7/16
(341)
13---5/16
(338)
D
22---1/4
(565)
19---5/8
(498)
20---5/8
(600)
20
(508)
20
(508)
22---1/4
(565)
19---5/8
(498)
20---5/8
(600)
20
(508)
22---1/4
(565)
19---5/8
(498)
20---5/8
(600)
20
(508)
22---1/4
(565)
19---5/8
(498)
20---5/8
(600)
12
HORIZONTAL INSTALLATION
!
WARNING
FIRE, EXPLOSION, AND CARBON MONOXIDE
POISONING HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Do not install the furnace on its back or hang furnace with control compartment facing downward.
Safety control operation will be adversely affected.
Never connect return--air ducts to the back of the furnace.
The furnace can be installed horizontally in an attic or crawl space on either the left--hand (LH) or right--hand (RH) side. The furnace can be hung from floor joists, rafters or trusses or installed on a non--combustible platform, blocks, bricks or pad.
Suspended Furnace Support
The furnace may be supported under each end with threaded rod, angle iron or metal plumber’s strap as shown. (See Fig. 15 and
16.) Secure angle iron to bottom of furnace as shown.
Heavy--gauge sheet metal straps (plumber’s straps) may be used to suspend the furnace from each bottom corner. To prevent screws from pulling out, use 2 #8 x 3/4--in. (19 mm) screws into the side and 2 #8 x 3/4--in. (19 mm) screws in the bottom of the furnace casing for each strap. (See Fig. 15 and 16.) If the screws are attached to ONLY the furnace sides and not the bottom, the straps must be vertical against the furnace sides and not pull away from the furnace sides, so that the strap attachment screws are not in tension (are loaded in shear) for reliable support.
Platform Furnace Support
Construct working platform at location where all required furnace clearances are met. (See Fig. 2 and 17.) For furnaces with 1--in.
(25 mm) clearance requirement on side, set furnace on noncombustible blocks, bricks or angle iron. For crawl space installations, if the furnace is not suspended from the floor joists, the ground underneath furnace must be level and the furnace set on blocks or bricks.
Roll--Out Protection
Provide a minimum 17--3/4 in. x 22 in. (451 mm x 559 mm) piece of sheet metal for flame roll--out protection in front of burner area for furnaces closer than 12 inches (305 mm) above the combustible deck or suspended furnaces closer than 12 inches
(305 mm) to joists. The sheet metal MUST extend underneath the furnace casing by 1 in. (25 mm) with the door removed.
The bottom closure panel on furnaces of widths 17--1/2 in. (445 mm) and larger may be used for flame roll--out protection when bottom of furnace is used for return air connection. See Fig. 17 for proper orientation of roll--out shield.
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove two screws holding bottom filler panel. (See Fig. 9.)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws. Side Return Air
Inlet
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. This panel MUST be in place when side return air inlet(s) is used without a bottom return air inlet.
Not all horizontal furnaces are approved for side return air connections. (See Fig. 20).
FILTER ARRANGEMENT
!
WARNING
CARBON MONOXIDE AND POISONING
HAZARD
Failure to follow this warning could result in personal injury, or death.
Never operate a furnace without a filter or with filter access door removed.
13
There are no provisions for an internal filter rack in these furnaces.
A field--supplied accessory external filter is required.
Refer to the instructions supplied with the external filter rack for assembly and installation options.
AIR DUCTS
General Requirements
The duct system should be designed and sized according to accepted national standards such as those published by: Air
Conditioning Contractors Association (ACCA), Sheet Metal and
Air Conditioning Contractors National Association (SMACNA) or American Society of Heating, Refrigerating and Air
Conditioning Engineers (ASHRAE) or consult The Air Systems
Design Guidelines reference tables available from your local distributor. The duct system should be sized to handle the required system design CFM at the design external static pressure.
The furnace airflow rates are provided in Table 5 -- AIR
DELIVERY--CFM (With Filter).
When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
Secure ductwork with proper fasteners for type of ductwork used.
Seal supply-- and return--duct connections to furnace with code approved tape or duct sealer.
NOTE: Flexible connections should be used between ductwork and furnace to prevent transmission of vibration. Ductwork passing through unconditioned space should be insulated and sealed to enhance system performance. When air conditioning is used, a vapor barrier is recommended.
Maintain a 1--in. (25 mm) clearance from combustible materials to supply air ductwork for a distance of 36 in. (914 mm) horizontally from the furnace. See NFPA 90B or local code for further requirements.
Ductwork Acoustical Treatment
NOTE: Metal duct systems that do not have a 90 degree elbow and 10 ft. (3 M) of main duct to the first branch take--off may require internal acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with NFPA 90B as tested by UL Standard 181 for
Class 1 Rigid air ducts.
Supply Air Connections
For a furnace not equipped with a cooling coil, the outlet duct shall be provided with a removable access panel. This opening shall be accessible when the furnace is installed and shall be of such a size that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for sampling the airstream. The cover attachment shall prevent leaks.
Upflow and Horizontal Furnaces
Connect supply--air duct to flanges on furnace supply--air outlet.
Bend flange upward to 90_ with wide duct pliers. (See Fig. 14.)
The supply--air duct must be connected to ONLY the furnace supply--outlet--air duct flanges or air conditioning coil casing
(when used). DO NOT cut main furnace casing side to attach supply air duct, humidifier, or other accessories. All accessories
MUST be connected to duct external to furnace main casing.
NOTE: For horizontal applications, the top--most flange may be bent past 90 degrees to allow the evaporator coil to hang on the flange temporarily while the remaining attachment and sealing of the coil are performed.
UPFLOW DOWNFLOW
Downflow Furnaces
Connect supply--air duct to supply--air outlet on furnace. Bend flange inward past 90_ with wide duct pliers. (See Fig. 14.) The supply--air duct must be connected to ONLY the furnace supply outlet or air conditioning coil casing (when used). When installed on combustible material, supply--air duct must be connected to
ONLY the factory--approved accessory subbase or a factory-approved air conditioning coil casing. DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected to duct external to furnace casing.
HORIZONTAL
90 90
YES
YES
YES
120
MIN
YES
120
MIN
YES
120
MIN
YES
NO
NO
Fig. 14 -- Duct Flanges
1
/
4
" (6mm) THREADED ROD
4 REQ.
NO
A02020
OUTER DOOR
A S SEMBLY
8" (203mm) MIN
FOR DOOR REMOVAL
SECURE ANGLE
IRON TO BOTTOM
OF FURNACE WITH
3 #8 x
3
/
4
" (19mm) SCREWS
TYPICAL FOR 2 SUPPORTS
1” (25mm) SQUARE, 1-1/4”x1-1/4”x1/8” (32x32x3mm)
ANGLE IRON OR UNI-STRUT MAY BE USED
(2) HEX NUTS, (2) WASHERS & (2) LOCK WASHERS
REQ. PER ROD
Fig. 15 -- Horizontal Unit Suspension
14
A10130
METHOD 2
USE (4) #8 x 3/4 (19 mm) SHEET
METAL SCREWS FOR EACH
STRAP. THE STRAPS
SHOULD BE VERTICAL
AGAINST THE FURNACE
SIDES AND NOT PULL AWAY
FROM THE FURNACE
SIDES.
METHOD 1
FOLD ALL STRAPS UNDER
FURNACE AND SECURE WTH
(4) #8 x 3/4 (19 mm) SHEET METAL SCREWS
(2 SCREWS IN SIDE AND 2 SCREWS
IN BOTTOM).
Fig. 16 -- Horizontal Suspension with Straps
A10131
LINE CONT A CT ONL Y PERMISSIBLE BETWEEN
LINES FORMED BY INTERSECTIONS OF
THE T OP AND TW O SIDES OF THE FURNA CE
JA CKET AND BUILDING JOISTS ,
STUDS , OR FRAMING.
17
4
3
3
/
4
″ (451mm)OVERALL
/
4
″ (121mm) UNDER DOOR
1
″ (25mm) UNDER FURNACE
GAS
ENTR Y
TYPE-B
VENT
EXTEND OUT 12
″ (305mm)
FR OM FA CE OF DOOR
6 ″ M
IN *
(152mm)
30-IN . (762mm)
MIN WORK AREA
* WHEN USED W ITH
SINGLE W ALL VEN T
CONNECTIONS
17
3
/
4
″
(451mm)
SHEET
MET AL
22
″
(559mm)
EQUIPMENT MANU AL
SHUT -OFF GAS VA LV E
SEDIMENT
TRAP
UNION
A10164
Fig. 17 -- Typical Attic Installation
15
Return Air Connections
!
WARNING
FIRE HAZARD
Failure to follow this warning could cause personal injury, death and/or property damage.
Never connect return--air ducts to the back of the furnace.
Follow instructions below
Downflow Furnaces
The return--air duct must be connected to return--air opening
(bottom inlet) as shown in Fig. 20. DO NOT cut into casing sides
(left or right). Side opening is permitted for only upflow and most horizontal furnaces. (See Fig. 20.) Bypass humidifier connections should be made at ductwork or coil casing sides exterior to furnace.
Upflow and Horizontal Furnaces
The return--air duct must be connected to bottom, sides (left or right), or a combination of bottom and side(s) of main furnace casing as shown in Fig. 19 and 21. Bypass humidifier may be attached into unused return air side of the furnace casing. (See
Fig. 19 and 21.)
Not all horizontal furnaces are approved for side return air connections. (See Fig. 21.)
GAS PIPING
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections.
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury,death, and/or property damage.
Use proper length of pipe to avoid stress on gas control manifold and a gas leak.
!
CAUTION
FURNACE OVERHEAT HAZARD
Failure to follow this caution may result in property damage.
Connect gas pipe to gas valve using a backup wrench to avoid damaging gas controls and burner misalignment.
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
If local codes allow the use of a flexible gas appliance connector, always use a new listed connector. Do not use a connector which has previously served another gas appliance. Black iron pipe shall be installed at the furnace gas control valve and extend a minimum of 2 in.(51 mm) outside the furnace.
Gas piping must be installed in accordance with national and local codes. Refer to current edition of NFGC.
Installations must be made in accordance with all authorities having jurisdiction. If possible, the gas supply line should be a separate line running directly from meter to furnace.
NOTE: In the state of Massachusetts:
1. Gas supply connections MUST be performed by a licensed plumber or gas fitter.
2. When flexible connectors are used, the maximum length shall not exceed 36 inches (915 mm).
3. When lever handle type manual equipment shutoff valves are used, they shall be T--handle valves.
4. The use of copper tubing for gas piping is NOT approved by the state of Massachusetts.
Refer to Table 6 for recommended gas pipe sizing. Risers must be used to connect to furnace and to meter. Support all gas piping with appropriate straps, hangers, etc. Use a minimum of 1 hanger every 6 ft. (2 M). Joint compound (pipe dope) should be applied sparingly and only to male threads of joints. Pipe dope must be resistant to the action of propane gas.
An accessible manual equipment shutoff valve MUST be installed external to furnace casing and within 6 ft. (2 M) of furnace. A 1/8--in. (3 mm) NPT plugged tapping, accessible for test gauge connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual equipment shutoff valve.
NOTE: The furnace gas control valve inlet pressure tap connection is suitable to use as test gauge connection providing test pressure DOES NOT exceed maximum 0.5 psig (14--In.
W.C.) stated on gas control valve. (See Fig. 47.)
Some installations require gas entry on right side of furnace (as viewed in upflow.) (See Fig. 22.)
Install a sediment trap in riser leading to furnace as shown in Fig.
18. Connect a capped nipple into lower end of tee. Capped nipple should extend below level of furnace gas controls. Place a ground joint union between furnace gas control valve and exterior manual equipment gas shutoff valve. A 1/8--in. (3 mm) NPT plugged tapping, accessible for test gauge connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual equipment shutoff valve.
16
Table 5 – Air Delivery -- CFM (With Filter)*
UNIT SIZE
045---08/
024045
070---16/
048070
090---16/
048090
110---20/
060110
135---20/
060135
COLOR
Orange
Red
Gray
Yellow
Blue
Orange
Red
Gray
Yellow
Blue
Orange
Red
Gray
Yellow
Blue
Orange
Red
Gray
Yellow
Blue
Orange
Red
Gray
Yellow
Blue
SPEED
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
0.1
1185
920
735
820
650
1625
1405
1240
1190
1035
1845
1590
1365
1225
1100
2255
1600
1945
1420
1280
2295
1725
1910
1630
1430
0.2
1145
880
685
765
595
1585
1360
1200
1140
985
1800
1545
1320
1160
1030
2205
1525
1890
1340
1205
2240
1660
1865
1575
1355
0.3
1115
835
625
725
535
1535
EXTERNAL STATIC PRESSURE (In. W.C.)
0.4
0.5
0.6
0.7
1075
800
585
670
490
1495
1035
755
530
630
430
1460
980
720
490
580
390
1415
905
680
435
545
330
1365
1320
1155
1095
930
1755
1500
1270
1140
2185
1605
1800
1510
1285
1110
960
2150
1465
1830
1280
1280
1110
1050
885
1710
1455
1215
1060
875
2100
1400
1770
1200
1055
2125
1545
1745
1435
1200
1240
1065
1000
835
1665
1410
1170
1010
805
2040
1335
1715
1140
990
2070
1460
1685
1365
1125
1195
1020
955
785
1595
1365
1125
950
730
1985
1275
1655
1065
910
2005
1395
1610
1300
1075
1155
975
915
745
1500
1315
1070
840
1925
1340
1545
1245
1015
895
645
1920
1210
1600
1005
0.8
820
645
395
490
280
1295
1115
935
870
695
1400
1270
1025
830
570
1835
1150
1545
925
760
1805
1285
1485
1185
945
*A filter is required for each return---air inlet. Airflow performance included 3/4---in. (19 mm) washable filter media such as contained in factory---authorized accessory filter rack. To determine airflow performance without this filter, assume an additional 0.1 In. W.C. available external static pressure.
1070
895
830
650
1275
1180
955
0.9
720
605
345
455
235
1220
695
1670
1230
1435
1130
855
770
505
1735
1080
1480
865
1030
850
790
600
1105
1000
900
1
580
540
295
405
--- ---
1125
630
1545
1170
1380
1065
800
710
425
1615
1015
1430
790
--- --- Indicates unstable operating conditions.
Table 6 – Maximum Capacity of Pipe*
NOMINAL IRON
PIPE
INTERNAL
DIAMETER
LENGTH OF PIPE --- FT. (M)
SIZE IN. (mm)
1/2 (13)
3/4 (19)
1 (25)
1---1/4 (32)
1---1/2 (38)
In. (mm)
0.622 (16)
0.824 (21)
1.049 (27)
1.380 (35)
1.610 (41)
10
175 (53)
360 (110)
680 (207)
1400 (427)
2100 (640)
20
120 (37)
250 (76)
465 (142)
950 (290)
1460 (445)
30
97 (30)
200 (61)
375 (114)
770 (235)
1180 (360)
40
82 (25)
170 (52)
320 (98)
660 (201)
990 (301)
* Cubic ft. of natural gas per hr for gas pressures of 0.5 psig (14---In. W.C.) or less and a pressure drop of 0.5---In. W.C. (based on a 0.60 specific gravity gas). Ref: Chapter 6 ANSI Z223---2012/NFPA 54---2012.
50
73 (22)
151 (46)
285 (87)
580 (177)
900 (274)
Piping should be pressure and leak tested in accordance with
NFGC in the United States, local, and national plumbing and gas codes before the furnace has been connected. After all connections have been made, purge lines and check for leakage at furnace prior to operating furnace.
If pressure exceeds 0.5 psig (14--In. W.C.), gas supply pipe must be disconnected from furnace and capped before and during supply pipe pressure test. If test pressure is equal to or less than
0.5 psig (14--In. W.C.), turn off electric shutoff switch located on furnace gas control valve and accessible manual equipment shutoff valve before and during supply pipe pressure test. After all connections have been made, purge lines and check for leakage at furnace prior to operating furnace.
The gas supply pressure shall be within the maximum and minimum inlet supply pressures marked on the rating plate with the furnace burners ON and OFF.
GAS
SUPPLY
MANUAL
SHUTOFF
VALVE
(REQUIRED)
SEDIMENT
TRAP
UNION
A02035
Fig. 18 -- Typical Gas Pipe Arrangement
17
Fig. 19 -- Upflow Return Air Configurations and Restrictions
A02075
Fig. 20 -- Downflow Return Air Configurations and Restrictions
A02163
18
Fig. 21 -- Horizontal Return Air Configurations and Restrictions
A02162
2” (51mm)
Street Elbow
Fig. 22 -- Burner and Manifold
A08551
19
Table 7 – Electrical Data
FURNACE MODEL
045-08 / 024045
070-16 / 048070
090-16 / 048090
VOLTS-
HERTZ-
PHASE
115 - 60 - 1
115 - 60 - 1
115 - 60 - 1
OPERATING
VOLTAGE*
(VOLTS)
MAX
127
127
127
MIN
104
104
104
MAX UNIT
(AMPS)
8.1
10.8
11.4
110-20 / 060110
135-20 / 060135
115 - 60 - 1
115 - 60 - 1
127
127
104
104
14.2
14.2
* Permissible limits of the voltage range at which the unit operates satisfactorily.
UNIT
AMPACITY#
(AMPS)
10.9
14.2
14.8
18.2
18.2
MAX WIRE
LENGTH‡
FT. (M)
34 (10)
26 (8)
25 (7)
31 (9)
31 (9)
MAX FUSE/
CKT BKR†
(AMPS)
15
15
15
20
20
MIN
WIRE
GAGE
14
14
14
12
12
# Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier, etc.) full load amps.
{
Time---delay type is recommended.
}
Length shown is as measured one way along wire path between unit and service panel for maximum 2 percent voltage drop.
ELECTRICAL CONNECTIONS
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Blower access panel door switch opens 115--v power to control. No component operation can occur. Do not bypass or close switch with panel removed.
equipment. Refer to rating plate or Table 7 for equipment electrical specifications.
Make all electrical connections in accordance with National
Electrical Code (NEC) ANSI/NFPA 70--2011 and any local codes or ordinances that might apply.
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire.
See Fig. 25 for field wiring diagram showing typical field 115--v wiring. Check all factory and field electrical connections for tightness.
Field--supplied wiring shall conform with the limitations of 63_F
(35_C) rise.
!
WARNING
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
The cabinet MUST have an uninterrupted or unbroken ground according to NEC ANSI/NFPA 70--2011 or local codes to minimize personal injury if an electrical fault should occur. This may consist of electrical wire, conduit approved for electrical ground or a listed, grounded power cord (where permitted by local code) when installed in accordance with existing electrical codes. Refer to the power cord manufacturer’s ratings for proper wire gauge.
Do not use gas piping as an electrical ground.
!
CAUTION
FURNACE MAY NOT OPERATE
Failure to follow this caution may result in intermittent furnace operation.
Furnace control must be grounded for proper operation or else control will lock out. Control must remain grounded through green/yellow wire routed to gas valve and manifold bracket screw.
Use a separate, fused branch electrical circuit with a properly sized fuse or circuit breaker for this furnace. See Table 7 for wire size and fuse specifications. A readily accessible means of electrical disconnect must be located within sight of the furnace.
NOTE: Proper polarity must be maintained for 115--v wiring. If polarity is incorrect, control LED status indicator light will flash rapidly and furnace will NOT operate.
J--BOX RELOCATION
NOTE: If factory location of J--Box is acceptable, go to next section (ELECTRICAL CONNECTION TO J--BOX).
NOTE: On 14--in. (356 mm) wide casing models, the J--Box shall not be relocated to other side of furnace casing when the vent pipe is routed within the casing.
1. Remove and save two screws holding J--Box.
NOTE: The J--Box cover need not be removed from the J--Box in order to move the J--Box. Do NOT remove green ground screw inside J--Box.
2. Cut wire tie on loop in furnace wires attached to J--box.
3. Move J--Box to desired location.
4. Fasten J--Box to casing with two screws removed in Step
1.
5. Route J--Box wires within furnace away from sharp edges, rotating parts and hot surfaces.
115--V WIRING
Verify that the voltage, frequency, and phase correspond to that specified on unit rating plate. Also, check to be sure that service provided by utility is sufficient to handle load imposed by this
20
ELECTRICAL CONNECTION TO J--BOX
Electrical Box on Furnace Casing Side
!
WARNING
FIRE OR ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
If field--supplied manual disconnect switch is to be mounted on furnace casing side, select a location where a drill or fastener cannot damage electrical or gas components.
1. Select and remove a hole knockout in the casing where the electrical box is to be installed.
NOTE: Check that duct on side of furnace will not interfere with installed electrical box.
2. Remove the desired electrical box hole knockout and position the hole in the electrical box over the hole in the furnace casing.
3. Fasten the electrical box to casing by driving two field supplied screws from inside electrical box into casing steel.
4. Remove and save two screws holding J--Box.
5. Pull furnace power wires out of 1/2--in. (12 mm) diameter hole in J--Box. Do not loosen wires from strain--relief wire--tie on outside of J--Box.
6. Route furnace power wires through holes in casing and electrical box and into electrical box.
7. Pull field power wires into electrical box.
8. Remove cover from furnace J--Box.
9. Route field ground wire through holes in electrical box and casing, and into furnace J--Box.
10. Reattach furnace J--Box to furnace casing with screws removed in Step 4.
11. Secure field ground wire to J--Box green ground screw.
12. Complete electrical box wiring and installation. Connect line voltage leads as shown in Fig. 25. Use best practices
(NEC in U.S. for wire bushings, strain relief, etc.
13. Reinstall cover to J--Box. Do not pinch wires between cover and bracket.
POWER CORD INSTALLATION IN FURNACE J--BOX
NOTE: Power cords must be able to handle the electrical requirements listed in Table 7. Refer to power cord manufacturer’s listings.
1. Remove cover from J--Box.
2. Route listed power cord through 7/8--in. (22 mm) diameter hole in J--Box.
3. Secure power cord to J--Box bracket with a strain relief bushing or a connector approved for the type of cord used.
4. Secure field ground wire to green ground screw on J--Box bracket.
5. Connect line voltage leads as shown in Fig. 25.
6. Reinstall cover to J--Box. Do not pinch wires between cover and bracket.
BX CABLE INSTALLATION IN FURNACE J--BOX
1. Remove cover from J--Box.
2. Route BX cable into 7/8--inch diameter hole in J--Box.
3. Secure BX cable to J--Box bracket with connectors approved for the type of cable used.
4. Secure field ground wire to green ground screw on J--Box bracket.
21
A10141
Fig. 23 -- Field--Supplied Electrical Box on Furnace Casing
5. Connect line voltage leads as shown in Fig. 25 .
6. Reinstall cover to J--Box. Do not pinch wires between cover and bracket.
24--V WIRING
Make field 24--v connections at the 24--v terminal strip. (See Fig.
23.) Connect terminal Y/Y2 as shown in Fig. 24 for proper cooling operation. Use only AWG No. 18, color--coded, copper thermostat wire.
The 24--v circuit contains an automotive--type, 3--amp. fuse located on the control. Any direct shorts during installation, service, or maintenance could cause this fuse to blow. If fuse replacement is required, use ONLY a 3--amp. fuse of identical size.
ACCESSORIES
1. Electronic Air Cleaner (EAC)
Connect an accessory Electronic Air Cleaner (if used) using 1/4--in female quick connect terminals to the two male
1/4--in quick--connect terminals on the control board marked EAC--1 and EAC--2. The terminals are rated for
115 VAC, 1.0 amps maximum and are energized during blower motor operation. (See Fig. 24.)
2. Humidifier (HUM)
Connect an accessory 24 VAC, 0.5 amp. maximum humidifier (if used) to the 1/4--in male quick--connect HUM terminal and COM--24V screw terminal on the control board thermostat strip. The HUM terminal is energized when gas valve relay (GVR) is energized. (See Fig. 24.)
NOTE: A field--supplied, 115--v controlled relay connected to
EAC terminals may be added if humidifier operation is desired during blower operation.
NOTE: DO NOT connect furnace control HUM terminal to
HUM (humidifier) terminal on Thermidistatt, Zone Controller or similar device. See Thermidistat, Zone Controller, thermostat, or controller manufacturer’s instructions for proper connection.
BLOWER OFF-DELAY
TWINNING AND/OR
COMPONENT TEST
TERMINAL
24-V THERMOSTAT
TERMINALS
HUMIDIFIER TERMINAL
(24-VAC 0.5 AMP. MAX)
3-AMP FUSE
LED OPERATION
& DIAGNOSTIC
LIGHT
BLOWER SPEED
SELECTION
TERMINALS
HEAT
COOL
FAN
SPARE 2
SPARE 1
TRANSFORMER
24-VAC CONNECTIONS
PL1-LOW VOLTAGE
DRAIN HARNESS
CONNECTOR
115-VAC (L2)
NEUTRAL
CONNECTIONS
115-VAC (L1)
NEUTRAL
CONNECTIONS
EAC-1 TERMINAL
(115-VAC 1.0 AMP. MAX.)
PL2-HOT SURFACE
IGNITER & INDUCER
MOTOR CONNECTOR
A08063
Fig. 24 -- Furnace Control
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING
FIVE WIRE
THREE-WIRE
HEATING-ONLY
BLOWER DOOR SWITCH
BLK
WHT
BLK
WHT
GND
115-V FIELD-
SUPPLIED
DISCONNECT
GND
AUXILIARY
J-BOX
NOTE 2
W
R
O
L
C
O
N
T
R
G
COM
Y/Y2
W C R
NOTES:
1.
2.
3.
G Y
THERMOSTAT
TERMINALS
FIELD-SUPPLIED
DISCONNECT
GND
208/230- OR
460-V
THREE
PHASE
208/230-V
SINGLE
PHASE
24-V
TERMINAL
BLOCK
FURNACE
NOTE 1
TWO
WIRE
CONDENSING
UNIT
Connect Y-terminal in furnace as shown for proper blower operation.
Some thermostats require a "C" terminal connection as shown.
If any of the original wire, as supplied, must be replaced, use same type or equivalent wire.
A99440
Fig. 25 -- Heating and Cooling Application Wiring Diagram with 1--Stage Thermostat
22
See notes 2,5,7, and 10 on the page following these figures.
A04215
Fig. 26 -- Single--Stage Furnace with Single--Speed Air
Conditioner
See notes 1, 2, 4, 6, 7, 9, 10 and 12 on the page following these figures.
A04217
Fig. 28 -- Single--Stage Furnace with Single--Speed Heat
Pump (Dual Fuel)
See notes 2,5,8, and 10 on the page following these figures.
A04216
Fig. 27 -- Single Stage Furnace with Two--Speed Air Conditioner
See notes 1, 2, 3, 4, 6, 8, 9, 10 and 12 on the page following these figures.
A04218
Fig. 29 -- Single--Stage Furnace with Two--Speed heat Pump
(Dual Fuel)
23
HUMIDFIER
(24VAC)
See notes 1, 2, 4, 11, 12, and 13 on the page following these figures.
A04219
Fig. 30 -- Dual Fuel Thermostat with Single--Stage Furnace and Single--Speed Heat Pump
HUMIDFIER
(24VAC)
See notes 1, 2, 3, 4, 11, 12, and 14 on the page following these figures.
A04220
Fig. 31 -- Dual Fuel Thermostat with Single--Stage Furnace and Two--Speed Heat Pump
See note 2 on the page following these figures.
HUMIDFIER
(24VAC)
A04221
Fig. 32 -- Two Stage Thermostat with Single--Stage Furnace and Two--Speed Air Conditioner
NOTES FOR FIGURES 26 -- 32
1. Heat pump MUST have a high pressure switch for dual fuel applications.
2. Refer to outdoor equipment Installation Instructions for additional information and setup procedure.
3. Outdoor Air Temperature Sensor must be attached in all dual fuel applications.
4. Dip switch No. 1 on Thermidistat should be set in OFF position for air conditioner installations. This is factory default.
5. Dip switch No. 1 on Thermidistat should be set in ON position for heat pump installations.
6. Dip switch No. 2 on Thermidistat should be set in OFF position for single--speed compressor operation. This is factory default.
7. Dip switch No. 2 on Thermidistat should be set in ON position for two--speed compressor operation.
8. Configuration Option No. 10 “Dual Fuel Selection” must be turned ON in all dual fuel applications.
9. NO connection should be made to the furnace HUM terminal when using a Thermidistat.
10. The RVS Sensing terminal “L” should not be connected. This is internally used to sense defrost operation.
11. DO NOT SELECT the “FURNACE INTERFACE” or “BALANCE POINT” option on the two--speed heat pump control board. This is controlled internally by the Thermidistat/Dual Fuel Thermostat.
12. Dip switch D on Dual Fuel Thermostat should be set in OFF position for single--speed compressor operation. This is factory default.
13. Dip switch D on Dual Fuel Thermostat should be set in ON position for two--speed compressor operation.
24
VENTING
The furnace shall be connected to a listed factory built chimney or vent, or a clay--tile lined masonry or concrete chimney. Venting into an unlined masonry chimney or concrete chimney is prohibited.
When an existing Category I furnace is removed or replaced, the original venting system may no longer be sized to properly vent the attached appliances. An improperly sized Category I venting system could cause the formation of condensate in the furnace and vent, leakage of condensate and combustion products, and spillage of combustion products into the living space.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death. The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies, which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed.
Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI
Z223.1/NFPA 54.
9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas--fired burning appliance to their previous conditions of use.
Vent system or vent connectors may need to be resized. Vent systems or vent connectors, must be sized to approach minimum size as determined using appropriate table found in the NFGC.
GENERAL VENTING REQUIREMENTS
Follow all safety codes for proper vent sizing and installation requirements, including local building codes, the National Fuel
Gas Code ANSI Z223.1--2012/NFPA 54--2012 (NFGC), Parts 12 and 13, the local building codes, and furnace and vent manufacturers’ instructions.
These furnaces are design--certified as Category I furnaces in accordance with ANSI Z21.47--2012/CSA 2.3--2012 and operate with a non--positive vent static pressure to minimize the potential for vent gas leakage. Category I furnaces operate with a flue loss not less than 17 percent to minimize the potential for condensation in the venting system. These furnaces are approved for common venting and multistory venting with other fan assisted or draft hood equipped appliances in accordance with the
NFGC, the local building codes, and furnace and vent manufacturers’ instructions. The following information and warning must be considered in addition to the requirements defined in the NFGC.
1. If a vent (common or dedicated) becomes blocked, the furnace will be shut off by the draft safeguard switch located on the vent elbow.
2. Do not vent this Category I furnace into a single--wall dedicated or common vent. The dedicated or common vent is considered to be the vertical portion of the vent system that terminates outdoors.
3. Vent connectors serving Category I furnaces shall not be connected into any portion of a mechanical draft system operating under positive pressure.
4. Do not vent this appliance with any solid fuel burning appliance.
5. Category I furnaces must be vented vertically or nearly vertically unless equipped with a listed power venter.
6. Do not vent this appliance into an unlined masonry chimney. Refer to Chimney Inspection Chart, Fig. 33.
MASONRY CHIMNEY REQUIREMENTS
NOTE: These furnaces are CSA design--certified for use in exterior tile--lined masonry chimneys with a factory accessory
Chimney Adapter Kit. Refer to the furnace rating plate for correct kit usage. The Chimney Adapter Kits are for use with ONLY furnaces having a Chimney Adapter Kit numbers marked on the furnace rating plate.
If a clay tile--lined masonry chimney is being used and it is exposed to the outdoors below the roof line, relining might be required. Chimneys shall conform to the Standard for Chimneys,
Fireplaces, Vents, and Solid Fuel Burning Appliances
ANSI/NFPA 211--2012 and must be in good condition.
U.S.A.--Refer to Sections 13.1.8 and 13.2.20 of the NFGC
NFPA54/ANSI Z223.1--2012 or the authority having jurisdiction to determine whether relining is required. If relining is required, use a properly sized listed metal liner, Type--B vent, or a listed alternative venting design.
NOTE: See the NFPA54/ANSI Z223.1--2012, 13.1.8 and
13.2.20 regarding alternative venting design and the Exception, which cover installations such as the Chimney Adapter Kits, which are listed for use with these furnaces. See Product Data
Sheet for accessory listing.
The Chimney Adapter Kit is listed alternative venting system for these furnaces. See the kit instructions for complete details.
25
This furnace is permitted to be vented into a clay tile--lined masonry chimney that is exposed to the outdoors below the roof line, provided:
1. Vent connector is Type--B double--wall, and
2. This furnace is common vented with at least 1 draft hood equipped appliance, and
3. The combined appliance input rating is less than the maximum capacity given in Table 8, and
4. The input rating of each space heating appliance is greater than the minimum input rating given in Table 9 for the local 99% Winter Design Temperature. Chimneys having internal areas greater than 38 square inches require furnace input ratings greater than the input ratings of these furnaces. See footnote at bottom of Table 9, and
5. The authority having jurisdiction approves.
If all of these conditions cannot be met, an alternative venting design shall be used, such as the listed chimney adapter kit with these furnaces, which are listed for use with the kit, a listed chimney--lining system, or a Type--B common vent.
Inspections before the sale and at the time of installation will determine the acceptability of the chimney or the need for repair and/or (re)lining. Refer to the Fig. 33 to perform a chimney inspection. If the inspection of a previously used tile--lined chimney: a. Shows signs of vent gas condensation, the chimney should be relined in accordance with local codes and the authority having jurisdiction. The chimney should be relined with a listed metal liner, Type--B vent, or a listed chimney adapter kit shall be used to reduce condensation.
If a condensate drain is required by local code, refer to the NFGC NFPA54/ANSI Z223.1--2012, Section 12.10
for additional information on condensate drains.
b. Indicates the chimney exceeds the maximum permissible size in the tables, the chimney should be rebuilt or relined to conform to the requirements of the equipment being installed and the authority having jurisdiction.
A chimney without a clay tile liner, which is otherwise in good condition, shall be rebuilt to conform to ANSI/NFPA 211 or be lined with a UL listed metal liner or UL listed Type--B vent.
Relining with a listed metal liner or Type--B vent is considered to be a vent--in--a--chase.
If a metal liner or Type--B vent is used to line a chimney, no other appliance shall be vented into the annular space between the chimney and the metal liner.
Exterior Masonry Chimney FAN + NAT
Installations with Type--B Double Wall Vent
Connectors NFPA & AGA
Table 8 – Combined Appliance Maximum Input Rating in
Thousands of BTUH per Hour
VENT HEIGHT
FT. (M)
6 (1.8)
8 (2.4)
10 (3.0)
15 (4.5)
20 (6.0)
30 (9.1)
INTERNAL AREA OF CHIMNEY
IN
2
(MM
2
)
12
(7741)
19
(12258)
28
(18064)
38
(24516)
74
80
84
NR
NR
NR
119
130
138
152
NR
NR
178
193
207
233
250
NR
257
279
299
334
368
404
Table 9 – Minimum Allowable Input Rating of Space--Heating Appliance in Thousands of BTUH per Hour
VENT HEIGHT
FT (M)
INTERNAL AREA OF CHIMNEY
12
(7741)
IN . (MM
19
(12258)
)
28
(18064)
Local 99% Winter Design
Temperature: 17 to 26_F (---8 to ---3_C)
38
(24516)
6 (1.8)
8 (2.4)
0
52
55
74
99
111
10 (3.0)
15 (4.6)
20 (6.1)
30 (9.1)
NR
NR
NR
NR
90
NR
NR
NR
125
167
212
NR
Local 99% Winter Design
Temperature: 5 to 16_F* (---15 to ---9_C)
141
154
169
212
258
362
6 (1.8)
8 (2.4)
10 (3.0)
NR
NR
NR
78
94
111
121
135
149
15 (4.6)
20 (6.1)
NR
NR
NR
NR
193
NR
30 (9.1) NR NR NR
Local 99% Winter Design
Temperature: ---10 to 4_F* (---23 to ---16_C)
166
182
198
247
293
377
6 (1.8)
8 (2.4)
10 (3.0)
15 (4.6)
NR
NR
NR
NR
NR
NR
NR
NR
145
159
175
NR
20 (6.1)
30 (9.1)
NR
NR
NR
NR
NR
NR
Local 99% Winter Design
Temperature: ---11_F (---24_C) or lower
Not recommended for any vent configuration.
196
213
231
283
333
NR
*The 99.6% heating db temperatures found in the 1997 or 2001 ASHRAE
Fundamentals Handbook, Climatic Design Information chapter, Table 1A
(United States) or the 2005 ASHRAE Fundamentals handbook, Climatic
Design Information chapter, and the CD---ROM included with the 2005
ASHRAE Fundamentals Handbook.
APPLIANCE APPLICATION REQUIREMENTS
Appliance operation has a significant impact on the performance of the venting system. If the appliances are sized, installed, adjusted, and operated properly, the venting system and/or the appliances should not suffer from condensation and corrosion.
The venting system and all appliances shall be installed in accordance with applicable listings, standards, and codes.
The furnace should be sized to provide 100 percent of the design heating load requirement plus any margin that occurs because of furnace model size capacity increments. Heating load estimates can be made using approved methods available from Air
Conditioning Contractors of America (Manual J); American
Society of Heating, Refrigerating, and Air--Conditioning
Engineers; or other approved engineering methods. Excessive oversizing of the furnace could cause the furnace and/or vent to fail prematurely. When a metal vent or metal liner is used, the vent must be in good condition and be installed in accordance with the vent manufacturer’s instructions.
26
CHIMNEY INSPECTION CHART
For additional requirements refer to the National Fuel Gas Code NFPA 54/ANSI Z223.1 and ANSI/NFPA 211
Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances
Crown condition:
Missing mortar or brick?
No
Yes
Rebuild crown.
Is chimney property lined with clay tile liner?
No
Yes
Is liner and top seal in good condition?
Yes
No
Repair liner or top seal or reline chimney as necessary.
Reline
Repair
Debris in cleanout?
Mortar, tile, metal vent, fuel oil residue?
Yes
No
Remove metal vent or liner.
Mortar or tile debris?
No
Yes Remove mortar and tile debris
Clay tile misalignment, missing sections, gaps?
Yes
No
Condensate drainage at bottom of chimney?
No
Chimney exposed to outdoors below roof line?
No
Yes
Yes
No
Is chimney lined with properly
Consult
Part B of chimney adapter venting instructions for application suitability.
Suitable sized, listed liner or
Yes
Type-B vent?
Yes
Not Suitable
Install chimney adapter per instructions.
Not Suitable
Is chimney to be dedicated to a single furnace?
No
Line chimney with property sized, listed flexible metal liner or Type-B vent per
NFGC Vent
Sizing Tables and liner or vent manufacturer’s
Installation instructions.
Consult
Part C of chimney adapter venting instructions for application suitability
Suitable
Install chimney adapter per instructions.
Chimney is acceptable for use.
Fig. 33 -- Chimney Inspection Chart
A10133
27
To prevent condensation in the furnace and vent system, the following precautions must be observed:
1. The return--air temperature must be at least 60_F
(16_C)db except for brief periods of time during warm--up from setback at no lower than 55_F (13_C) db or during initial start--up from a standby condition.
2. Adjust the gas input rate per the installation instructions.
Low gas input rate causes low vent gas temperatures, causing condensation and corrosion in the furnace and/or venting system. Derating is permitted only for altitudes above
2000 ft. (610 M).
3. Adjust the air temperature rise to the midpoint of the rise range or slightly above. Low air temperature rise can cause low vent gas temperature and potential for condensation problems.
4. Set the thermostat heat anticipator or cycle rate to reduce short cycling.
Air for combustion must not be contaminated by halogen compounds which include chlorides, fluorides, bromides, and iodides. These compounds are found in many common home products such as detergent, paint, glue, aerosol spray, bleach, cleaning solvent, salt, and air freshener, and can cause corrosion of furnaces and vents. Avoid using such products in the combustion--air supply. Furnace use during construction of the building could cause the furnace to be exposed to halogen compounds, causing premature failure of the furnace or venting system due to corrosion.
Vent dampers on any appliance connected to the common vent can cause condensation and corrosion in the venting system. Do not use vent dampers on appliances common vented with this furnace.
ADDITIONAL VENTING REQUIREMENTS
A 4” (101 mm) round vent elbow is supplied with the furnace. A
5--inch (127 mm) or 6-- inch (152 mm) vent connector may be required for some model furnaces.
A field--supplied
4--inch--to--5--inch (101 -- 127 mm) or 4--inch--to--6--inch (101 --
152 mm) sheet metal increaser fitting is required when 5--inch
(127 mm) or 6--inch (152 mm) vent connector is used. See Fig.
34 -- 46 Venting Orientation for approved vent configurations.
NOTE: Vent connector length for connector sizing starts at furnace vent elbow. The 4--inch vent elbow is shipped for upflow configuration and may be rotated for other positions. Remove the
3 screws that secure vent elbow to furnace, rotate furnace vent elbow to position desired, reinstall screws. The factory--supplied vent elbow does NOT count as part of the number of vent connector elbows.
The vent connector can exit the furnace through one of 5 locations on the casing.
1. Attach the single wall vent connector to the furnace vent elbow, and fasten the vent connector to the vent elbow with at least two field--supplied, corrosion--resistant, sheet metal screws located 180_ apart.
NOTE: An accessory flue extension is available to extend from the furnace elbow to outside the furnace casing. See Product Data
Sheet for accessory listing. If flue extension is used, fasten the flue extension to the vent elbow with at least two field--supplied, corrosion--resistant, sheet metal screws located 180_ apart. Fasten the vent connector to the flue extension with at least two field--supplied, corrosion resistant sheet metal screws located
180_ apart.
2. Vent the furnace with the appropriate connector as shown in Fig. 34 -- 46.
3. Determine the correct location of the knockout to be removed.
4. Use a hammer and screwdriver to strike a sharp blow between the tie points and work the slug back and forth until the slug breaks free.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing furnaces.
!
CAUTION
BURN HAZARD
Failure to follow this caution may cause personal injury.
Hot vent pipe is within reach of small children when installed in downflow position. See the following instruction.
An accessory Vent Guard Kit is REQUIRED for downflow applications where the vent exits through the lower portion of the furnace casing. See Fig. 38 and Product Data Sheet for accessory listing. Refer to the Vent Guard Kit Instructions for complete details.
The horizontal portion of the venting system shall slope upwards not less than 1/4--in. per linear ft. (21 mm/M) from the furnace to the vent and shall be rigidly supported every 5 ft. (2 M) or less with metal hangers or straps to ensure there is no movement after installation.
SIDEWALL VENTING
This furnace is not approved for direct sidewall horizontal venting.
Per section 12.4.3 of the NFPA54/ANSI Z223.1--2012, any listed mechanical venter may be used, when approved by the authority having jurisdiction.
Select the listed mechanical venter to match the Btuh input of the furnace being vented. Follow all manufacturer’s installation requirements for venting and termination included with the listed mechanical venter.
28
Caution!! For the following applications, use the minimum vertical vent heights as specified below. For all other applications, follow exclusively the National Fuel Gas Code.
FURNACE
ORIENTATION
VENT ORIENTATION
FURNACE INPUT
(BTUH/HR)
Downflow Vent elbow left, then up Fig.
38
132,000
Horizontal Left
Horizontal Left
Vent elbow right, then up Fig.
Vent elbow right Fig.
42
41
132,000
132,000
NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFGC
*4 in. (102 mm) inside casing or vent guard
**Including 4 in. (102 mm) vent section(s)
MIN. VENT
DIAMETER
IN (MM)*
5 (127 )
5 (127 )
5 (127 )
MIN. VERTICAL VENT
HEIGHT
FT. (M)**
12 (4)
7 (2)
7 (2)
SEE NOTES: 1,2,4,7,8,9 on the page following these figures
Fig. 34 -- Upflow Application--Vent Elbow Up
A03208
SEE NOTES:1,2,3,4,5,7,8,9 on the page following these figures
A03210
Fig. 36 -- Downflow Application--Vent Elbow Up then Left
SEE NOTES: 1,2,3,4,7,8,9 on the pages following these figures
Fig. 35 -- Upflow Application--Vent Elbow Right
A03209
29
SEE NOTES: 1,2,4,5,7,8,9 on the page following these figures
Fig. 37 -- Downflow Application--Vent Elbow Up
A03211
SEE NOTES: 1,2,4,7,8,9 on the page following these figures
SEE NOTES: 1,2,4,5,6,7,8,9 on the page following these figures
A03207
Fig. 38 -- Downflow Application--Vent Elbow Left then Up
A03213
Fig. 40 -- Horizontal Left Application--Vent Elbow Left
SEE NOTES:1,2,3,4,5,7,8,9 on the page following these figures.
A03212
Fig. 39 -- Downflow Application--Vent Elbow Up then Right
SEE NOTES: 1,2,4,5,7,8,9 on the page following these figures
A03214
Fig. 41 -- Horizontal Left Application--Vent Elbow Right then Up
30
SEE NOTES: 1,2,4,7,8,9 on the page following these figures
A03214
Fig. 42 -- Horizontal Right Application--Vent Elbow Right
SEE NOTES: 1,2,4,5,7,8,9 on the page following these figures
A03219
Fig. 44 -- Horizontal Right Application--Vent Elbow Left then Up
SEE NOTES: 1,2,4,5,7,8,9 on the page following these figures
A03215
Fig. 43 -- Horizontal Left Application--Vent Elbow Up
SEE NOTES: 1,2,4,5,7,8,9 on the page following these figures
A03216
Fig. 45 -- Horizontal Left Application--Vent Elbow Right
SEE NOTES: 1,2,4,5,7,8,9
A02068
Fig. 46 -- Horizontal Right Application--Vent Elbow Left
VENTING NOTES FOR FIGURES 34 -- 46
1. For common vent, vent connector sizing and vent material: United States----use the NFGC.
2. Immediately increase to 5--inch (127 mm) or 6--inch (152 mm) vent connector outside furnace casing when 5--inch (127 mm) vent connector is required, refer to Note 1 above.
3. Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace, except when factory--authorized, Downflow Vent
Guard Kit, is used in the downflow position. See Product Data Sheet for accessory listing.
4. Type--B vent where required, refer to Note 1 above.
5. Four--inch single--wall (26 ga. min.) vent must be used inside furnace casing and when the Downflow Vent Guard Kit is used external to the furnace. See Table NO TAG for accessory listing.
6. Factory--authorized accessory Downflow Vent Guard Kit required in downflow installations with lower vent configuration. See Product Data Sheet for accessory listing.
7. Chimney Adapter Kit may be required for exterior masonry chimney applications. Refer to Chimney Adapter Kit for sizing and complete application details. See
Product Data Sheet for accessory listing.
8. Secure vent connector to furnace elbow with (2) corrosion--resistant sheet metal screws, spaced approximately 180_ apart.
9. Secure all other single wall vent connector joints with (3) corrosion resistant screws spaced approximately 120_ apart. Secure Type--B vent connectors per vent connector manufacturer’s recommendations.
31
START--UP, ADJUSTMENT, AND SAFETY
CHECK
General
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
This furnace is equipped with manual reset limit switches in the gas control area. The switches open and shut off power to the gas valve if a flame rollout or overheating condition occurs in the gas control area. DO NOT bypass the switches. Correct inadequate combustion air supply problem before resetting the switches.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing furnaces.
1. Maintain 115--v wiring and ground. Improper polarity will result in rapid flashing LED and no furnace operation.
2. Make thermostat wire connections at the 24--v terminal block on the furnace control. Failure to make proper connections will result in improper operation. (See Fig. 25.)
3. Gas supply pressure to the furnace must be greater than
4.5--In. W.C. (0.16 psig ) but not exceed 14--In. W.C. (0.5
psig).
4. Check all manual--reset switches for continuity.
5. Install blower compartment door. Door must be in place to operate furnace.
6. Replace outer door.
Start--Up Procedures
!
WARNING
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could cause personal injury, death and/or property damage.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections.
1. Purge gas lines after all connections have been made.
2. Check gas lines for leaks.
3. To Begin Component Self--Test:
Remove blower access door. Disconnect the thermostat R lead from the furnace control board. Manually close the blower door switch closed. Short (jumper) the COM--24v terminal on control to the TEST/TWIN 3/16--inch quick connect terminal on control until LED goes out (approximately 2 sec). Gas valve and humidifier will not be turned on. (See Fig. 24.)
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, or death.
Blower access door switch opens 115--v power to control.
No component operation can occur unless switch is closed.
Caution must be taken when manually closing this switch for service purposes.
NOTE: The furnace control allows all components, except the gas valve, to be run for short period of time. This feature helps diagnose a system problem in case of a component failure.
Component test feature will not operate if any thermostat signal is present at the control.
Component test sequence is as follows:
Refer to service label attached to furnace or see Fig. 50.
a. LED will display previous status code 4 times.
b. Inducer motor starts and continues to run until Step f of component test sequence.
c. Hot surface igniter is energized for 15 sec., then off.
d. Blower motor operates on HEAT speed for 10 sec.
e. Blower motor operates on COOL speed for 10 sec.
f. Inducer motor stops.
g. Reconnect R lead to furnace control board, release blower door switch and re--install blower door.
4. Operate furnace per instruction on door.
5. Verify furnace shut down by lowering thermostat setting below room temperature.
6. Verify furnace restarts by raising thermostat setting above room temperature.
Adjustments
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in injury, death and/or property damage.
DO NOT bottom out gas valve regulator adjusting screw.
This can result in unregulated manifold pressure and result in excess overfire and heat exchanger failures.
!
CAUTION
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace life.
DO NOT redrill orifices. Improper drilling (burrs, out--of--round holes, etc.) can cause excessive burner noise and misdirection of burner flames. This can result in flame impingement of heat exchangers, causing failures. (See Fig.
48.)
32
Furnace gas input rate on rating plate is for installations at altitudes up to 2000 ft. (610 M). Furnace input rate must be within +/--2 percent of furnace rating plate input. For altitudes above 5500 ft. (1676 M), a field--supplied high altitude pressure switch is required.
1. Determine the correct gas input rate.
The input rating for altitudes above 2,000 ft. (610 M) must
be reduced by 4 percent for each 1,000 ft. (305 M) above sea level. For installations below 2000 ft. (610 M), refer to the unit rating plate. For installations above 2000 ft. (610
M), multiply the input on the rating plate by the de--rate multiplier in Table 8 for the correct input rate.
2. Determine the correct orifice and manifold pressure adjustment. There are two different orifice and manifold adjustment tables. All models in all positions, except Low NOx models in downflow or horizontal positions, use Table 12
(22,000 Btuh/Burner).
Low NOx models in the downflow or horizontal positions must use Table 13 (21,000 Btuh/Burner). See input listed on rating plate.
a. Obtain average yearly gas heat value (at installed altitude) from local gas supplier.
b. Obtain average yearly gas specific gravity from local gas supplier.
c. Find installation altitude in Table 12 or 13.
d. Find closest natural gas heat value and specific gravity in Table 12 or 13.
e. Follow heat value and specific gravity lines to point of intersection to find orifice size and manifold pressure settings for proper operation.
f. Check and verify burner orifice size in furnace. NEVER
ASSUME ORIFICE SIZE. ALWAYS CHECK AND
VERIFY.
g. Replace orifice with correct size if required by Table 10,
11, 12 and 13. Use only factory--supplied orifices. See
EXAMPLE 1.
Table 10 – Altitude Derate Multiplier for U.S.A.
ALTITUDE
(FT. / M)
0–2000 (0---610)
2001–3000 (610---914)
3001–4000 (914---1219)
4001–5000 (1219---1524)
5001–6000 (1524---1829)
6001–7000 (1829---2134)
7001–8000 (2134---2438)
8001–9000 (2438---2743)
9001–10,000 (2743---3048)
PERCENT
OF
DERATE
0
8–12
12–16
16–20
20–24
24–28
28–32
32–36
36–40
DERATE
MULTIPLIER
FACTOR*
1.00
0.90
0.86
0.82
0.78
0.74
0.70
0.66
0.62
* Derate multiplier factors are based on midpoint altitude for altitude range.
EXAMPLE 1: (0 to 2000 ft. (0 to 610 M) altitude)
For 22,000 Btuh per burner application use Table 12 .
Heating value = 1000 Btuh/cu ft.
Specific gravity = 0.62
Therefore: Orifice No. 43*
Manifold pressure: 3.7--In. W.C.
*Furnace is shipped with No. 43 orifices.
In this example all main burner orifices are the correct size and do not need to be changed to obtain proper input rate.
3. Adjust manifold pressure to obtain correct input rate.
a. Turn gas valve ON/OFF switch to OFF.
b. Remove manifold pressure tap plug from gas valve. (See
Fig. 47.) c. Connect a water column manometer or similar device to manifold pressure tap.
d. Turn gas valve ON/OFF switch to ON.
e. Manually close blower door switch.
33 f. Set thermostat to call for heat.
g. Remove regulator seal cap and turn regulator adjusting screw counterclockwise (out) to decrease input rate of clockwise (in) to increase input rate.
h. Install regulator seal cap.
i. Leave manometer or similar device connected and proceed to Step 4.
NOTE: DO NOT set manifold pressure less than 3.2--In. W.C. or more than 3.8--In. W.C. for natural gas at sea level. If manifold pressure is outside this range, change main burner orifices. Refer to Table 10, 11, 12 and 13.
NOTE: If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orifice. A burr--free and squarely aligned orifice hole is essential for proper flame characteristics.
4. Verify natural gas input rate by clocking meter.
NOTE: Gas valve regulator adjustment cap must be in place for proper input to be clocked.
a. Turn off all other gas appliances and pilots served by the meter.
b. Run furnace for 3 minutes in heating operation.
c. Measure time (in sec) for gas meter to complete 1 revolution and note reading. The 2 or 5 cubic feet dial provides a more accurate measurement of gas flow.
d. Refer to Table 12 for cubic ft. of gas per hr.
e. Multiply gas rate (cu ft./hr) by heating value (Btuh/cu ft.) to obtain input.
If clocked rate does not match required input from Step 1, increase manifold pressure to increase input or decrease manifold pressure to decrease input. Repeat steps b through e until correct input is achieved. Reinstall regulator seal cap on gas valve.
5. Set temperature rise. The furnace must operate within the temperature rise ranges specified on the furnace rating plate. Do not exceed temperature rise range specified on unit rating plate. Determine the temperature rise as follows:
NOTE: Blower access door must be installed when taking temperature rise reading. Leaving blower access door off will result in incorrect temperature measurements.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect 115--v electrical power and install lockout tag before changing speed tap.
a. Place thermometers in return and supply ducts as close to furnace as possible. Be sure thermometers do not see radiant heat from heat exchangers. Radiant heat affects temperature rise readings. This practice is particularly important with straight--run ducts.
b. When thermometer readings stabilize, subtract return--air temperature from supply--air temperature to determine air temperature rise.
NOTE: If the temperature rise is outside this range, first check:
(1.) Gas input for heating operation.
(2.) Derate for altitude if applicable.
(3.) Return and supply ducts for excessive restrictions causing static pressures greater than 0.50--In. W.C.
c. Adjust air temperature rise by adjusting blower speed. Increase blower speed to reduce temperature rise. Decrease blower speed to increase temperature rise d. Turn thermostat down below room temperature and remove blower access door.
e. To change motor speed selection for heating, remove blower motor lead from control HEAT terminal (See Fig.
24.) Select desired blower motor speed lead from one of the other terminals and relocate it to the HEAT terminal
(See Table 5 for lead color identification). Reconnect original lead to SPARE terminal.
f. Repeat steps a through e.
g. When correct input rate and temperature rise is achieved, turn gas valve ON/OFF switch to OFF.
h. Remove manometer or similar device from gas valve.
i. Reinstall manifold pressure tap plug in gas valve.
Fig. 47 -- Gas Control Valve
Fig. 48 -- Orifice Hole
BURNER
ORIFICE
A06666
A93059
34
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Reinstall manifold pressure tap plug in gas valve to prevent gas leak.
!
CAUTION
FURNACE OVERHEATING HAZARD
Failure to follow this caution may result in reduced furnace life.
Recheck temperature rise. It must be within limits specified on the rating plate.
Recommended operation is at the mid--point of rise range or slightly above.
6. Set thermostat heat anticipator.
a. Mechanical thermostat -- Set thermostat heat anticipator to match the amp. draw of the electrical components in the R--W circuit. Accurate amp. draw readings can be obtained at the wires normally connected to thermostat subbase terminals, R and W. The thermostat anticipator should NOT be in the circuit while measuring current.
(1.) Remove thermostat from subbase or from wall.
(2.) Connect an amp. meter as shown in Fig. 49 across the R and W subbase terminals or R and W wires at wall.
(3.) Record amp. draw across terminals when furnace is in heating and after blower starts.
(4.) Set heat anticipator on thermostat per thermostat instructions and install on subbase or wall.
b. Electronic thermostat: Set cycle rate for 4 cycles per hr.
7. Adjust blower off delay The blower off delay has 4 adjustable settings from 90 sec to 180 sec. The blower off delay jumpers are located on the furnace control board.
(See Fig. 24.)
To change the blower off delay setting, move the jumper from one set of pins on the control to the pins used for the selected blower off delay. Factory off delay setting is 120 sec.
8. Set airflow CFM for cooling
Select the desired blower motor speed lead for cooling airflow. See Table 5--Air Delivery--CFM (With Filter) for lead color identification.
Check Safety Controls
The flame sensor, gas valve, and pressure switch were all checked in the Start--up procedure section as part of normal operation.
1. Check Main Limit Switch(es)
This control shuts off combustion control system and energizes air--circulating blower motor, if furnace overheats.
By using this method to check limit control, it can be established that limit is functioning properly and will operate if there is a restricted duct system or motor failure. If limit control does not function during this test, cause must be determined and corrected.
a. Run furnace for at least 5 minutes.
b. Gradually block off return air with a piece of cardboard or sheet metal until the limit trips.
c. Unblock return air to permit normal circulation.
d. Burners will re--light when furnace cools down.
2. Check draft safeguard switch.
The purpose of this control is to cause the safe shutdown of the furnace during certain blocked vent conditions.
a. Verify vent pipe is cool to the touch.
b. Disconnect power to furnace and remove vent connector from furnace vent elbow.
c. Restore power to furnace and set room thermostat above room temperature.
d. After normal start--up, allow furnace to operate for 2 minutes, then block vent elbow in furnace 80 percent of vent area with a piece of flat sheet metal.
e. Furnace should cycle off within 2 minutes. If gas does not shut off within 2 minutes, determine reason draft safeguard switch did not function properly and correct condition.
f. Remove blockage from furnace vent elbow.
g. Switch will auto--reset when it cools.
h. Re--install vent connector.
NOTE: Should switch remain open longer than 3 minutes, furnace control board will lockout the furnace for 3 hours. To reset furnace control board, turn thermostat below room temperature or from HEAT to OFF and turn 115v power OFF, then back ON.
3. Check Pressure Switch
This control proves operation of the draft inducer blower.
a. Turn off 115--v power to furnace.
b. Disconnect inducer motor lead wires from wire harness.
c. Turn on 115--v power to furnace.
d. Set thermostat to “call for heat” and wait 1 minute. When pressure switch is functioning properly, hot surface igniter should NOT glow and control diagnostic light flashes a status code 32. If hot surface igniter glows when inducer motor is disconnected, shut down furnace immediately.
e. Determine reason pressure switch did not function properly and correct condition.
f. Turn off 115--v power to furnace.
g. Reconnect inducer motor wires, replace outer door, and turn on 115--v power.
h. Blower will run for 90 sec before beginning the call for heat again.
i. Furnace should ignite normally.
THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
(ANITICIPATOR, CLOCK, ETC.,
MUST BE OUT OF CIRCUIT.)
HOOK-AROUND
AMMETER
R Y W G
10 TURNS
FROM UNIT 24-V
CONTROL TERMINALS
= 0.5 AMPS FOR THERMOSTAT
Fig. 49 -- Amp. Draw Check with Ammeter
A96316
35
SECONDS
FOR 1 REVOLUTION
44
45
46
47
48
39
40
41
42
43
49
34
35
36
37
38
29
30
31
32
33
24
25
26
27
28
19
20
21
22
23
14
15
16
17
18
10
11
12
13
Checklist
1. Put away tools and instruments. Clean up debris.
2. Verify that blower OFF--DELAY time is selected as desired.
3. Verify that blower and burner access doors are properly installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturer’s instructions.
6. Review User’s Guide with owner.
7. Attach literature packet to furnace.
92
90
88
86
84
106
103
100
97
95
124
120
116
113
109
150
144
138
133
129
82
80
78
76
75
73
189
180
171
164
157
257
240
225
212
200
1
Cu Ft.
360
327
300
277
Table 11 – Gas Rate (Cu Ft./Hr.)
SIZE OF TEST DIAL
2 Cu Ft.
5 Cu Ft.
SECONDS
FOR 1 REVOLUTION
164
160
157
153
150
185
180
176
172
167
147
212
206
200
195
189
248
240
232
225
218
300
288
277
267
257
379
360
343
327
313
720
655
600
555
514
480
450
424
400
409
400
391
383
375
462
450
439
429
419
367
529
514
500
486
474
621
600
581
563
545
750
720
692
667
643
947
900
857
818
783
1800
1636
1500
1385
1286
1200
1125
1059
1000
108
110
112
116
120
98
100
102
104
106
88
90
92
94
96
78
80
82
84
86
68
70
72
74
76
59
60
62
64
66
54
55
56
57
58
50
51
52
53
1 Cu Ft.
33
33
32
31
30
37
36
35
35
34
41
40
39
38
38
46
45
44
43
42
53
51
50
48
47
61
60
58
56
54
67
65
64
63
62
72
71
69
68
SIZE OF TEST DIAL
2 Cu Ft.
67
65
64
62
60
74
72
71
69
68
82
80
78
76
75
92
90
88
86
84
106
103
100
97
95
122
120
116
112
109
144
141
138
136
133
131
129
126
124
5 Cu Ft.
167
164
161
155
150
184
180
178
173
170
205
200
196
192
188
231
225
220
214
209
265
257
250
243
237
305
300
290
281
273
360
355
346
340
333
327
321
316
310
36
Table 12 – Orifice Size* and Manifold Pressure (In. W.C.) for Gas Input Rate
37
A10180
Table 12 -- Orifice Size* and Manifold Pressure (In. W.C.) for Gas Input Rate (CONT)
A10180A
38
Table 13 – Orifice Size* And Manifold Pressure (In. W.C.) For Gas Input Rate
39
A10181
Table 13-- Orifice Size* And Manifold Pressure (In. W.C.) For Gas Input Rate (CONT)
A10181A
40
SERVICE AND MAINTENANCE
PROCEDURES
!
WARNING
FIRE, INJURY, OR DEATH HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
The ability to properly perform maintenance on this equipment requires certain knowledge, mechanical skills, tools, and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment other than those procedures recommended in the User’s
Manual.
!
WARNING
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position and install a lockout tag.
There may be more than one disconnect switch. Lock out and tag switch with a suitable warning label. Verify proper operation after servicing.
!
CAUTION
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in improper furnace operation or failure of furnace.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
INTRODUCTION
GENERAL
These instructions are written as if the furnace is installed in an upflow application. An upflow furnace application is where the blower is located below the combustion and controls section of the furnace, and conditioned air is discharged upward. Since this furnace can be installed in any of the 4 positions shown in Fig. 4, you must revise your orientation to component location accordingly.
ELECTRICAL CONTROLS AND WIRING
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
There may be more than one electrical supply to the furnace. Check accessories and cooling unit for additional electrical supplies that must be shut off during furnace servicing. Lock out and tag switch with a suitable warning label.
The electrical ground and polarity for 115--v wiring must be properly maintained. Refer to Fig. 25 for field wiring information and to Fig. 54 for furnace wiring information.
NOTE: If the polarity is not correct, the STATUS LED on the control will flash rapidly and prevent the furnace from heating.
The control system also requires an earth ground for proper operation of the control and flame--sensing electrode.
The 24--v circuit contains an automotive--type, 3--amp. fuse located on the control. (See Fig. 24.) Any shorts of the 24--v wiring during installation, service, or maintenance will cause this fuse to blow. If fuse replacement is required, use ONLY a 3--amp.
fuse. The control LED will display status code 24 when fuse needs to be replaced.
Proper instrumentation is required to service electrical controls.
The control in this furnace is equipped with a Status Code LED
(Light--Emitting Diode) to aid in installation, servicing, and troubleshooting. Status codes can be viewed at the sight glass in blower access door. The furnace control LED is either ON continuously, rapid flashing, or a code composed of 2 digits. The first digit is the number of short flashes, the second digit is the number of long flashes.
For an explanation of status codes, refer to service label located on blower access door or Fig. 50 and the troubleshooting guide which can be obtained from your distributor.
See Fig. 55 for a brief Troubleshooting Guide.
For Controls With an Amber LED
The stored status code will not be erased from the control memory, if 115-- or 24--v power is interrupted.
1. To retrieve status code, proceed with the following:
NOTE: NO thermostat signal may be present at control, and all blower--OFF delays must be completed.
a. Leave 115--v power to furnace turned on.
b. Remove outer access door.
c. Look into blower access door sight glass for current LED status.
d. BRIEFLY remove insulated terminal wire from the draft safeguard (DSS) switch until LED goes out, then reconnect it.
NOTE: If wire to LS or DSS is disconnected longer than 4 sec, main blower starts, and retrieval request is ignored.
2. When above items have been completed, the LED flashes status code 4 times. Record this status code for further troubleshooting.
3. Check LED status. If no previous faults in history, control will flash status code 11.
41
SERVICE
If status code recall is needed, briefly remove then reconnect one main limit wire to display stored status code. On RED LED boards do not remove power or blower door before initiating status code recall. After status code recall is completed component test will occur.
LED CODE STATUS
CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2.
CONTINUOUS ON - Control has 24VAC power.
RAPID FLASHING - Line voltage (115VAC) polarity reversed. If twinned, refer to twinning kit instructions.
EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUMBER OF LONG FLASHES.
11 NO PREVIOUS CODE - Stored status code is erased automatically after 72 hours. On
RED LED boards stored status codes can also be erased when power
(115 VAC or 24 VAC) to control is interrupted.
12 BLOWER ON AFTER POWER UP (115 VAC or 24 VAC) -Blower runs for 90 seconds, if unit is powered up during a call for heat (R-W closed) or R-W opens during blower on-delay.
13 LIMIT CIRCUIT LOCKOUT - Lockout occurs if the limit, draft safeguard, flame rollout, or blocked vent switch (if used) is open longer than 3 minutes.
- Control will auto reset after three hours. - Refer to #33.
14 IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34.
21 GAS HEATING LOCKOUT - Control will NOT auto reset.
Check for: - Mis-wired gas valve -Defective control (valve relay)
22 ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is deenergized. Inducer will run until fault is cleared. Check for: - Leaky gas valve
- Stuck-open gas valve
23 PRESSURE SWITCH DID NOT OPEN Check for:
- Obstructed pressure tubing. - Pressure switch stuck closed.
24 SECONDARY VOLTAGE FUSE IS OPEN Check for:
- Short circuit in secondary voltage (24VAC) wiring.
COMPONENT TEST
To initiate the component test sequence, shut OFF the room thermostat or disconnect the "R" thermostat lead. Briefly short the TEST/TWIN terminal to the "Com 24V" terminal. Status LED will flash code and then turn ON the inducer motor. The inducer motor will run for the entire component test. The hot surface ignitor, blower motor fan speed (on AMBER LED boards only) blower motor-heat speed, and blower motor-cool speed will be turned ON for 10-15 seconds each. Gas Valve and Humidifier will not be turned on.
31
PRESSURE SWITCH DID NOT CLOSE OR REOPENED - If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Excessive wind
- Proper vent sizing - Defective inducer motor
- Low inducer voltage (115VAC) - Defective pressure switch
- Inadequate combustion air supply - Disconnected or obstructed pressure tubing
- Low inlet gas pressure (if LGPS used) - Restricted vent
If it opens during blower on-delay period, blower will come on for the selected blower off-delay.
33 LIMIT CIRCUIT FAULT - Indicates a limit, draft safeguard, flame rollout, or blocked vent switch (if used) is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13.
If open less than 3 minutes status code #33 continues to flash until blower shuts off.
Flame rollout switch and BVSS require manual reset. Check for: - Restricted vent
- Proper vent sizing - Loose blower wheel. - Excessive wind
- Dirty filter or restricted duct system.
- Defective blower motor or capacitor. - Defective switch or connections.
- Inadequate combustion air supply (Flame Roll-out Switch open).
34 IGNITION PROVING FAILURE - Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Flame sensor must not be grounded
- Oxide buildup on flame sensor (clean with fine steel wool).
- Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal).
- Gas valve defective or gas valve turned off - Manual valve shut-off
- Defective Hot Surface Ignitor - Control ground continuity
- Low inlet gas pressure - Inadequate flame carryover or rough ignition
- Green/Yellow wire MUST be connected to furnace sheet metal
45 CONTROL CIRCUITRY LOCKOUT Auto-reset after one hour lockout due to;
- Gas valve relay stuck open - Flame sense circuit failure - Software check error
Reset power to clear lockout. Replace control if status code repeats.
327596-101 REV. B
A04223
Fig. 50 -- Service Label
CARE AND MAINTENANCE
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Never store anything on, near, or in contact with the furnace, such as:
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners, or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning compounds, plastic or plastic containers, gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids, or other volatile fluids.
3. Paint thinners and other painting compounds, paper bags, or other paper products.
!
WARNING
CARBON MONOXIDE POISONING AND
FIRE HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Never operate unit without a filter or with filter access door removed.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing furnaces.
For continuing high performance and to minimize possible equipment failure, periodic maintenance must be performed on this equipment. Consult your local dealer about proper frequency of maintenance and the availability of a maintenance contract.
!
WARNING
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury, death or property damage.
Turn off the gas and electrical supplies to the unit and install lockout tag before performing any maintenance or service. Follow the operating instructions on the label attached to the furnace.
The minimum maintenance on this furnace is as follows:
1. Check and clean/replace air filter each month or more frequently if required. Replace if torn.
2. Check blower motor and wheel for cleanliness each heating and cooling season. Clean as necessary.
3. Check electrical connections for tightness and controls for proper operation each heating season. Service as necessary.
4. Inspect burner compartment before each heating season for rust, corrosion, soot or excessive dust. If necessary, have furnace and burner serviced by a qualified service agency.
5. Inspect the vent pipe/vent system before each heating season for rust, corrosion, water leakage, sagging pipes or broken fittings. Have vent pipes/vent system serviced by a qualified service agency.
42
6. Inspect any accessories attached to the furnace such as a humidifier or electronic air cleaner. Perform any service or maintenance to the accessories as recommended in the accessory instructions.
CLEANING AND/OR REPLACING AIR FILTER
The air filter arrangement will vary depending on the application.
The filter is exterior to the furnace casing.
NOTE: If the filter has an airflow direction arrow, the arrow must point towards the blower.
Table 14 – Filter Size Information (In. / mm)
FURNACE
CASING
WIDTH
In. (mm)
14---1/2
(368)
17---1/2
(445)
21 (533)
24 (610)
FILTER SIZE (In. / mm)
Side Return
16 x 25 x 3/4
(406 x 635 x 19)
16 X 25 X 3/4
(406 x 635 x 19)
16 x 25 x 3/4
(406 x 635 x 19)
16 x 25 x 3/4
(406 x 635 x 19)
Bottom Return
FILTER TYPE
Washable*
Washable*
Washable*
Washable*
* Recommended
Media cabinet filter procedures :
1. Turn off electrical supply to furnace before removing filter access door.
2. Remove filter cabinet door.
3. Slide filter out of cabinet.
14 x 25 x 3/4
(356 x 635 x 19)
16 X 25 X 3/4
(406 x 635 x 19)
20 X 25 X 3/4
(508 x 635 x 19)
24 X 25 X 3/4
(610 x 635 x 19)
4. If equipped with permanent, washable 3/4--in. (19 mm) filter, clean filter by spraying cold tap water through filter in opposite direction of airflow. Rinse filter and let dry. Oiling or coating of the filter is not recommended. See Table
14 for size information.
5. If equipped with factory--specified disposable media filter, replace only with media filter having the same part number and size. For expandable replacement media, refer to the instructions included with the replacement media.
6. Slide filter into cabinet.
7. Replace filter cabinet door.
8. Turn on electrical supply to furnace.
BLOWER MOTOR AND WHEEL
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Blower access door switch opens 115--v power to control.
No component operation can occur unless switch is closed.
Caution must be taken when manually closing this switch for service purposes.
NOTE: The blower wheel should not be dropped or bent as balance will be affected. The following steps should be performed by a qualified service agency.
To ensure long life and high efficiency, clean accumulated dirt and grease from blower wheel and motor annually.
The inducer and blower motors are pre--lubricated and require no additional lubrication. These motors can be identified by the absence of oil ports on each end of the motor.
Clean blower motor and wheel as follows:
1. Turn off electrical supply to furnace.
2. Remove outer door.
43
3. For downflow or horizontal furnaces having vent pipes within the furnace that pass in front of the blower access door: a. Disconnect vent connector from furnace vent elbow.
b. Disconnect and remove short piece of vent pipe from within furnace.
4. Remove two screws from blower access door and remove blower access door.
5. All factory wires can be left connected, but field thermostat connections may need to be disconnected depending on their length and routing.
6. Remove two screws holding blower assembly to blower deck and slide blower assembly out of furnace.
7. Clean blower wheel and motor using a vacuum with soft brush attachment. Blower wheel blades may be cleaned with a small paint or flux brush. Do not remove or disturb balance weights (clips) on blower wheel blades.
8. Vacuum any loose dust from blower housing, wheel and motor.
9. If a greasy residue is present on blower wheel, remove wheel from the blower housing and wash it with an appropriate degreaser. To remove wheel:
NOTE: Before disassembly, mark blower motor, and blower housing so motor and each arm is positioned at the same location during reassembly.
a. Disconnect power choke wires (if used) and ground wire attached to blower housing.
b. Remove screws securing cutoff plate and remove cutoff plate from housing.
c. Loosen set screw holding blower wheel on motor shaft
(160+/--20 in.--lb. when reassembling).
d. Remove bolts holding motor to blower housing and slide motor out of wheel (40+/--10 in.--lb. when reassembling).
e. Remove blower wheel from housing.
f. Clean wheel and housing.
10. Reassemble motor and blower by reversing steps 11f through 11a, finishing with 11a. Be sure to reattach ground wire to the blower housing.
11. Verify that blower wheel is centered in blower housing and set screw contacts the flat portion of the motor shaft.
Loosen set screw on blower wheel and reposition if necessary.
12. Spin the blower wheel by hand to verify that the wheel does not rub on the housing.
13. Reinstall blower assembly in furnace.
14. Reinstall two screws securing blower assembly to blower deck.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in shortened heat exchanger life.
Heating fan speed(s) MUST be adjusted to provide proper air temperature rise as specified on the rating plate.
Recommended operation is at the midpoint of the rise range or slightly above. Refer to “SET TEMPERATURE RISE” under START--UP, ADJUSTMENT, and SAFETY
CHECK.
NOTE: Refer to Table 5 for motor speed lead relocation if leads were not identified before disconnection.
15. Refer to furnace wiring diagram, and connect thermostat leads if previously disconnected.
16. To check blower for proper rotation: a. Turn on electrical supply.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, or death.
Blower access door switch opens 115--v power to furnace control. No component operation can occur unless switch is closed. Exercise caution to avoid electrical shock from exposed electrical components when manually closing this switch for service purposes.
b. Manually close blower access door switch.
NOTE: If thermostat terminals are jumpered at the time blower access door switch is closed, blower will run for 90 sec before beginning a heating or cooling cycle.
c. Perform component self--test as shown at the bottom of the SERVICE label, located on the front of blower access door.
d. Verify blower is rotating in the correct direction.
17. If furnace is operating properly, RELEASE BLOWER
ACCESS DOOR SWITCH. Remove any jumpers or reconnect any disconnected thermostat leads. Replace blower access door.
18. Downflow or horizontal furnaces with vent pipe through furnace only: a. Install and connect short piece of vent pipe inside furnace to existing vent.
b. Connect vent connector to vent elbow.
19. Reinstall outer door.
20. Cycle furnace through one complete heating and cooling cycle. Verify the furnace temperature rise as shown in
“Adjustments” Section. Adjust temperature rise as shown in “Adjustments” Section. If outdoor temperature is below
70_F, (21_C) turn off circuit breaker to outdoor unit before running furnace in the cooling cycle. Turn outdoor circuit breaker on after completing cooling cycle.
CLEANING HEAT EXCHANGER
The following steps should be performed by a qualified service agency:
NOTE: If the heat exchangers get a heavy accumulation of soot and carbon, they should be replaced rather than trying to clean them thoroughly. A heavy build--up of soot and carbon indicates that a problem exists which needs to be corrected, such as improper adjustment of manifold pressure, insufficient or poor quality combustion air, incorrect size or damaged manifold orifice( s), improper gas, or a restricted heat exchanger. Action must be taken to correct the problem.
If it becomes necessary to clean the heat exchangers because of dust or corrosion, proceed as follows:
1. Turn OFF gas and electrical power to furnace.
2. Remove outer access door.
3. Disconnect vent connector from furnace vent elbow.
4. For downflow or horizontal furnace having an internal vent pipe, remove internal vent pipe within the casing.
5. Disconnect wires to the following components. Mark wires to aid in reconnection of (be careful when disconnecting wires from switches because damage may occur): a. Draft safeguard switch.
b. Inducer motor.
c. Pressure switch(es).
d. Limit over--temperature switch.
e. Gas valve.
f. Hot surface igniter.
g. Flame--sensing electrode.
h. Flame rollout switches.
6. Remove screws that fasten the collector box assembly to the cell panel. Be careful not to damage the collector box.
Inducer assembly and elbow need not be removed from collector box.
7. Disconnect gas line from gas manifold.
8. Remove the 5 screws that attach the burner assembly to the cell panel. The gas valve and individual burners need not be removed from support assembly. Remove NOx baffles if installed.
NOTE: Be very careful when removing burner assembly to avoid breaking igniter. See Fig. 51 and 52 for correct igniter location.
9. Using field--provided 25--caliber rifle cleaning brush,
36--in. (914 mm) long, 1/4” (6 mm) diameter steel spring cable, a variable speed, reversible electric drill, and vacuum cleaner, clean cells as follows: a. Remove metal screw fitting from wire brush to allow insertion into cable.
b. Insert the twisted wire end of brush into end of spring cable, and crimp tight with crimping tool or crimp by striking with ball--peen hammer. TIGHTNESS IS VERY
IMPORTANT.
9/32”
7.1mm
5/16”
7.9mm
Fig. 51 -- Igniter Position--Side View
A05025
1-7/8
47.6 mm
Fig. 52 -- Igniter Position--Top View
A05026
44
NOTE: The materials needed in item 9 can usually be purchased at local hardware stores.
(1.) Attach variable--speed, reversible drill to the end of spring cable (end opposite brush).
(2.) Insert brush end of cable into the outlet opening of cell and slowly rotate with drill. DO NOT force cable. Gradually insert cable into upper pass of cell.
(See Fig. 53 .)
(3.) Work cable in and out of cell 3 or 4 times to obtain sufficient cleaning. DO NOT pull cable with great force. Reverse drill and gradually work cable out.
(4.) Insert brush end of cable in burner inlet opening of cell, and proceed to clean 2 lower passes of cell in same manner as upper pass.
(5.) Repeat foregoing procedures until each cell in furnace has been cleaned.
(6.) Using vacuum cleaner, remove residue from each cell.
(7.) Using vacuum cleaner with soft brush attachment, clean burner assembly.
(8.) Clean flame sensor with fine steel wool.
(9.) Install NOx baffles (if removed).
(10.) Reinstall burner assembly. Center burners in cell openings.
10. Remove old sealant from cell panel and collector box flange.
11. Spray releasing agent on the heat exchanger cell panel where collector box assembly contacts cell panel.
NOTE: A releasing agent such as cooking spray or equivalent
(must not contain corn or canola oil, aromatic or halogenated hydrocarbons or inadequate seal may occur) and RTV sealant
(G.E. 162, 6702, or Dow--Corning 738) are needed before starting installation. DO NOT substitute any other type of RTV sealant. G.E. 162 (P771--9003) is available through RCD in 3--oz.
tubes.
12. Apply new sealant to flange of collector box and attach to cell panel using existing screws, making sure all screws are secure.
13. Reconnect wires to the following components. (Use connection diagram on wiring label, if wires were not marked for reconnection locations.): a. Draft safeguard switch.
b. Inducer motor.
c. Pressure switch(es).
d. Limit over--temperature switch.
e. Gas valve.
f. Hot surface igniter.
g. Flame--sensing electrode.
h. Flame rollout switches.
i. Install NOx baffles (if removed).
14. Reinstall internal vent pipe, if applicable.
15. Reinstall vent connector on furnace vent elbow. Securely fasten vent connector to vent elbow with 2 field--supplied, corrosion--resistant, sheet metal screws located 180_ apart.
16. Replace blower access door only, if it was removed.
17. Set thermostat above room temperature and check furnace for proper operation.
18. Verify blower airflow and speed changes between heating and cooling.
19. Check for gas leaks.
20. Replace outer access door.
A91252
Fig. 53 -- Cleaning Heat Exchanger Cell
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections.
45
Sequence of Operation
NOTE: Furnace control must be grounded for proper operation or control will lock out. Control is grounded through green/yellow wire routed to gas valve and manifold bracket screw. Using the schematic diagram in Fig. 54, follow the sequence of operation through the different modes. Read and follow the wiring diagram very carefully.
NOTE: If a power interruption occurs during a call for heat (W), the control will start a 90--second blower--only ON period two seconds after power is restored, if the thermostat is still calling for gas heating. The Amber LED light will flash code 12 during the
90--second period, after which the LED will be ON continuous, as long as no faults are detected. After the 90--second period, the furnace will respond to the thermostat normally.
The blower door must be installed for power to be conducted through the blower door interlock switch ILK to the furnace control CPU, transformer TRAN, inducer motor IDM, blower motor BLWM, hot--surface igniter HSI, and gas valve GV.
1. Heating
(See Fig. 25 for thermostat connections.)
The wall thermostat “calls for heat,” closing the R--to--W circuit. The furnace control performs a self--check, verifies the pressure switch contacts PRS are open, and starts the inducer motor IDM.
a. Inducer Prepurge Period-- As the inducer motor IDM comes up to speed, the pressure switch contacts PRS close to begin a 15--second prepurge period.
b. Igniter Warm--Up-- At the end of the prepurge period, the Hot--Surface igniter HSI is energized for a 17--second igniter warm--up period.
c. Trial--for--Ignition Sequence-- When the igniter warm-up period is completed, the main gas valve relay contacts
GVR close to energize the gas valve GV, the gas valve opens, and 24 vac power is supplied for a field--installed humidifier at the HUM terminal. The gas valve GV permits gas flow to the burners where it is ignited by the HSI.
Five seconds after the GVR closes, a 2--second flame proving period begins. The HSI igniter will remain ener-
gized until the flame is sensed or until the 2--second flame proving period begins.
d. Flame--Proving-- When the burner flame is proved at the flame--proving sensor electrode FSE, the furnace control
CPU begins the blower--ON delay period and continues to hold the gas valve GV open. If the burner flame is not proved within two seconds, the control CPU will close the gas valve GV, and the control CPU will repeat the ignition sequence for up to three more Trials--For--Ignition before going to Ignition--Lockout. Lockout will be reset automatically after three hours or by momentarily interrupting 115 vac power to the furnace, or by interrupting
24 vac power at SEC1 or SEC2 to the furnace control
CPU (not at W, G, R, etc.).
If flame is proved when flame should not be present, the furnace control CPU will lock out of Gas--Heating mode and operate the inducer motor IDM until flame is no longer proved.
e. Blower--On Delay-- If the burner flame is proven, the blower motor is energized on HEAT speed 25 seconds after the gas valve GV is energized.
Simultaneously, the electronic air cleaner terminal
EAC--1 is energized and remains energized as long as the blower motor BLWM is energized.
f. Blower--Off Delay-- When the thermostat is satisfied, the
R--to--W circuit is opened, de--energizing the gas valve
GV, stopping gas flow to the burners, and de--energizing the humidifier terminal HUM. The inducer motor IDM will remain energized for a 5--second post--purge period.
The blower motor BLWM and air cleaner terminal
EAC--1 will remain energized for 90, 120, 150, or 180 seconds (depending on the blower--OFF delay selection).
The furnace control CPU is factory--set for a 120--second blower--OFF delay.
2. Cooling Mode
The thermostat “calls for cooling.” a. Single--Speed Cooling
(See Fig. 25 -- 32 for thermostat connections)
The thermostat closes the R--to--G--and--Y circuits. The
R--to-- Y circuit starts the outdoor unit, and the R--to--
G--and--Y/Y2 circuits start the furnace blower motor
BLWM on COOL speed.
The electronic air cleaner terminal EAC--1 is energized with 115 vac when the blower motor BLWM is operating.
When the thermostat is satisfied, the R--to--G--and--Y circuits are opened. The outdoor unit will stop, and the furnace blower motor BLWM will continue operating on the
COOL speed for an additional 90 seconds. Jumper Y/Y2 to DHUM to reduce the cooling off--delay to 5 seconds.
(See Fig. 24.) b. Two--Speed Cooling
(See Fig. 25 -- 32 for thermostat connections.)
The thermostat closes the R--to--G--and--Y1 circuits for low--cooling or closes the R--to--G--and--Y1--and--Y2 circuits for high--cooling. The R--to--Y1 circuit starts the outdoor unit on low--cooling speed, and the R--to--
G--and--Y1 circuit starts the furnace blower motor
BLWM on low--cool speed (same speed as FAN). The
R--to--Y1--and--Y2 circuits start the outdoor unit on high-cooling speed, and the R--to--G and-- Y/Y2 circuits start the furnace blower motor BLWM on COOL speed.
The electronic air cleaner terminal EAC--1 is energized with 115 vac whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R--to--G--and--Y1 or
R--to--G--and--Y1 and Y2 circuits are opened. The outdoor unit stops, and the furnace blower BLWM and electronic air cleaner terminal EAC--1 will remain energized
46 for an additional 90 seconds. Jumper Y1 to DHUM to reduce the cooling off--delay to 5 seconds. (See Fig. 24.)
3. Thermidistat Mode
(See Fig. 26 -- 29 for Thermidistat connections.)
The dehumidification output, DHUM on the Thermidistat should be connected to the furnace control thermostat terminal DHUM. When there is a dehumidify demand, the
DHUM input is activated, which means 24 vac signal is removed from the DHUM input terminal. In other words, the DHUM input logic is reversed. The DHUM input is turned ON when no dehumidify demand exists. Once 24 vac is detected by the furnace control on the DHUM input, the furnace control operates in Thermidistat mode. If the
DHUM input is low for more than 48 hours, the furnace control reverts back to non--Thermidistat mode.
The cooling operation described in item 2. above also applies to operation with a Thermidistat. The exceptions are listed below: a. When the R--to--G--and--Y1 circuit is closed and there is a demand for dehumidification, the furnace blower motor
BLWM will continue running at low--cool speed (same speed as FAN).
b. When the R--to--G--and--Y/Y2 circuit is closed and there is a demand for dehumidification, the furnace blower motor BLWM will drop the blower speed from COOL to
HEAT for a maximum of 10 minutes before reverting back to COOL speed. If there is still a demand for dehumidification after 20 minutes, the furnace control CPU will drop the blower speed back to HEAT speed. This alternating 10-- minute cycle will continue as long as there is a call for cooling.
c. When the “call for cooling” is satisfied and there is a demand for dehumidification, the cooling blower--off delay is decreased from 90 seconds to 5 seconds.
4. Continuous Blower Mode
When the R--to--G circuit is closed by the thermostat, the blower motor BLWM will operate on continuous--blower speed (can be adjusted to FAN, HEAT, or COOL speed) at the thermostat. Factory default is FAN speed. Terminal
EAC--1 is energized as long as the blower motor BLWM is energized. During a call for heat, the blower BLWM will stop during igniter warm--up (17 seconds), ignition (7 seconds), and blower--ON delay (25 seconds), allowing the furnace heat exchangers to heat up more quickly, then restarts at the end of the blower--ON delay period at HEAT speed.
In heating, the furnace control CPU will hold the blower motor BLWM at HEAT speed during the selected blower--
OFF delay period before reverting to continuous--blower speed. When the thermostat “calls for low--cooling,” the blower motor BLWM will switch to operate at low--cool speed (same speed as FAN). When the thermostat is satisfied, the blower motor BLWM will operate an additional
90 seconds on low--cool speed (same speed as FAN) before reverting back to continuous--blower speed.
When the thermostat “calls for high--cooling”, the blower motor BLWM will operate at COOL speed. When the thermostat is satisfied, the blower motor BLWM will operate an additional 90 seconds on COOL speed before reverting back to continuous--blower speed.
When the R--to--G circuit is opened, the blower motor
BLWM will continue operating for an additional 5 seconds, if no other function requires blower motor
BLWM operation.
Continuous Blower Speed Selection from Thermostat
--To select different continuous--blower speeds from the room thermostat, momentarily turn off the FAN switch or push button on the room thermostat for 1--3 seconds after
the blower motor BLWM is operating. The furnace control
CPU will shift the continuous--blower speed from the factory setting of FAN to HEAT speed. Momentarily turning off the FAN switch again at the thermostat will shift the continuous--blower speed from HEAT to COOL. Repeating the procedure will shift the continuous--blower speed from COOL to FAN speed. The selection can be changed as many times as desired and is stored in the memory to be automatically used following a power interruption.
5. Heat pump
(See Fig. 25 -- 32 for thermostat connections.) When installed with a heat pump, the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles. When the R--to--
W--and--Y1 or R--to--W--and--Y1--and--G circuits are energized the furnace control CPU will switch to or turn on the blower motor BLWM at HEAT speed, and begin a heating cycle. The blower motor BLWM will remain on until the end of the prepurge period, then shut off for 24 seconds then come back on at HEAT speed. When the W input signal disappears, the furnace control begins a normal inducer post--purge period and the blower remains running at
HEAT speed for the selected blower--OFF delay period then switches to low--cool speed (same speed as FAN). If the R--to--W--and--Y1--and--G signals disappear at the same time, the blower motor BLWM will remain on for the selected blower--OFF delay period. If the R--to--
W--and--Y1 signals disappear, leaving the G signal, the blower motor BLWM will remain on for the selected blower--OFF delay period then switch to continuous-blower speed. When the R--to--W--and--Y/Y2, R--to--
W--and--Y/Y2--and--G, R--to--W--and--Y1--and-- Y/Y2, or
R--to--W-- and--Y1--and--Y/Y2--and--G circuits are energized the furnace control CPU will switch to or turn on the blower motor BLWM at HEAT speed, and begin a heating cycle. The blower motor BLWM will remain on until the end of the prepurge period, then shut off for 24 seconds then come back on at HEAT speed. When the W input signal disappears, the furnace control begins a normal inducer post--purge period and the blower switches to COOL speed after a 3 second delay. If the R--to--W--and--
Y/Y2--and--G or R--to--W--and--Y1--and --Y/Y2--and--G signals disappear at the same time, the blower motor
BLWM will remain on for the selected blower--OFF delay period. If the R--to--W--and--Y/Y2 or R--to--W--and--
Y1--and--Y/Y2 signals disappear, leaving the G signal, the blower motor BLWM will remain on for the selected blower--OFF delay period then switch to continuous blower speed.
Wiring Diagrams
Refer to Fig. 54 for wiring diagram.
Troubleshooting
Refer to the service label. (See Fig. 50.) The Troubleshooting
Guide (See Fig. 55) can be a useful tool in isolating furnace operation problems. Beginning with the word “Start,” answer each question and follow the appropriate arrow to the next item.
The Guide will help to identify the problem or failed component.
After replacing any component, verify correct operation sequence.
47
Fig. 54 -- Wiring Diagram
48
A11289
Fig. 55 -- Troubleshooting Guide
49
A02106A
another component test sequence
Clean flame sensor with fine steel wool and
OR REOPENED – If open longer than
NO PREVIOUS CODE – Stored codes boards stored status codes can also be
Control will auto-reset after 3 hours
50 lame sensor must not be grounded.
the control and initiate the component
A05032
PARTS REPLACEMENT INFORMATION GUIDE
CASING GROUP
Outer door
Blower door
Top filler plate
Bottom filler plate
Bottom enclosure
ELECTRICAL GROUP
Control bracket
Junction box
Limit switch(es)
Circuit board
Door switch
Transformer
Wiring harness 115v
Wiring harness 24v
BLOWER GROUP
Blower housing
Blower cutoff
Blower motor
Blower wheel
Capacitor (where used)
Capacitor strap (where used)
Grommet
Power choke (where used)
GAS CONTROL GROUP
Manifold
Burner assembly
Orifice
Flame sensor
Hot surface igniter
Gas valve
Manual reset limit switches
Burner support assembly
HEAT EXCHANGER GROUP
Heat exchanger cell
Cell panel
Lox NOx baffle (California models only)
INDUCER GROUP
Housing assembly
Pressure switch
Inducer motor
Inducer wheel
Vent elbow assembly
Draft safeguard switch
TO OBTAIN INFORMATION ON PARTS: Consult your installing dealer or classified section of your local telephone directory under
“Heating Equipment” or “Air Conditioning Contractors and Systems” headings for dealer listing by brand name or contact:
CARRIER CORPORATION
Consumer Relations Department
P.O. Box 4808
Syracuse, New York 13221--4808
1--800--CARRIER
Have available the model number, series number, and serial number located on the unit rating plate to ensure correct replacement part.
Example of Model Number
MODEL
HEATING
SIZE
135
VARIATION VOLTAGE SERIES PACKAGING
COOLING
AIRFLOW
(CFM)
20 58PHA --1 1 1
WARNING: Improper installation, adjustment, alteration, service, or maintenance can cause personal injury, property damage, or death.
Consult a qualified installer, service agency, or your local gas supplier for information or assistance. The qualified installer or service agency must use only factory--authorized replacement parts, kits, or accessories when modifying this product.
51
Copyright 2013 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Edition Date: 08/13
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
52
Catalog No: 58PHA---06SI
Replaces: 58PHA--05SI
advertisement
Key Features
- 4-way multipoise design
- induced combustion design
- high efficiency
- natural gas use
- propane gas conversion
- thermostat control
- upflow, downflow, or horizontal installation
- CSA design certification
- Easy to install and maintain