- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- CH
- GWHD(42)ND3EO
- Installation manual
- 23 Pages
CH GWHD(42)ND3EO Installation manual
The CH GWHD(30)ND3EO is a multizone ductless inverter heat pump that offers efficient and flexible climate control for your home. With its ability to connect with up to 5 indoor units, you can customize the temperature in different rooms or zones to suit your needs. The inverter technology allows for precise temperature control and energy savings, adjusting the compressor speed to match the cooling or heating demand. Installation is simplified with the recommended connection method for power and communication wiring, ensuring proper functionality and minimizing interference.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
MULTI DUCTLESS INVERTER HEAT PUMP OUTDOOR UNIT Installation manual Models: GWHD(30)ND3EO GWHD(36)ND3EO GWHD(42)ND3EO TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . 2 INDOOR UNITS COMBINATIONS . . . . . . . . . . .. . . . . . . . . . 3 PREFACE . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . 4 PRODUCT INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 PREPARATION BEFORE INSTALLATION . . . . . . . . . . . . . . . 8 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 THE CONDITIONS LISTED BELOW ARE NOT CLASSIFIED INTO ERRORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . 19 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . .21 SAFETY CONSIDERATIONS Installing, starting up, and servicing air--conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.). Only trained, qualified installers and service mechanics should install, start--up, and service this equipment. Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should be performed by trained service personnel. When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment. Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements. Recognize safety information. This is the safety--alert symbol !! . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation. WARNING ! ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label. ! WARNING EXPLOSION HAZARD Failure to follow this warning could result in death, serious personal injury, and/or property damage. CAUTION ! EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Do not bury more than 36 in. (914 mm) of refrigerant pipe in the ground. If any section of pipe is buried, there must be a 6 in. (152 mm) vertical rise to the valve connections on the outdoor units. If more than the recommended length is buried, refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causes refrigerant slugging and could possibly damage the compressor at start--up. SYSTEM REQUIREMENTS Allow sufficient space for airflow and servicing unit. See minimum required distances between unit and walls or ceilings. Recommended Connection Method for Power and Communication Wiring (To minimize communication wiring interference) Power Wiring: The main power is supplied to the outdoor unit. The field supplied connecting cable from the outdoor unit to indoor unit consists of three (3) wires and provides the power for the indoor unit. Two wires are high voltage AC power and one is a ground wire. Consult your local building codes and the NEC (National Electrical Code) or CEC (Canadian Electrical Code) for special requirements. All wires must be sized per NEC or CEC and local codes. Use Electrical Data table MCA (minimum circuit amps) and MOCP (maximum over current protection) to correctly size the wires and the disconnect fuse or breakers respectively. Per caution note, only copper conductors with a minimum 300 volt rating and 2/64--inch thick insulation must be used. Communication Wiring: A separate shielded copper conductor only, with a minimum 300 volt rating and 2/64--inch thick insulation, must be used as the communication wire from the outdoor unit to the indoor unit. To minimize voltage drop of the control wire, To minimize voltage drop, the factory recommended wire size is 14/3 stranded with a ground. In special cases where there is high electrical interference, please use a separate shielded 16GA stranded control wire. Never use air or gases containing oxygen for leak testing or operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion. ! CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. S Wires should be sized based on NEC and local codes. S Use copper conductors only with a minimum 300 volt rating and 2/64 inch thick insulation. 2 Specifications are subject to change without notice. INDOOR UNITS COMBINATIONS 3 Specifications are subject to change without notice. Preface Please carefully read the instructions in this manual before installation and operation. (1) For personal safety, please follow the instructions provided in this manual. (2) The total capacity of the indoor units , which run at the same time, can not exceed that of the outdoor units; otherwise, the cooling (heating) effect of each indoor unit would be poor. Model Minimum number of connectable indoor units Maximum number of connectable indoor units Minimum capacity of connectable indoor units Maximum capacity of connectable indoor units 30K 36K 42K 2 2 2 4 5 5 18KBtu 18KBtu 18KBtu 42KBtu 48KBtu 51KBtu (3) Switch the main power on eight hours before starting the unit to ensure a successful startup. (4) It is normal for the indoor unit to run 20-70 seconds after the indoor unit receives the³VWRS´ signal to make full use of the after heat function for the next operation. (5) When the running modes of the indoor and outdoor units conflict, the conflict appears on the wired controller display in five seconds and then the indoor unit will stop.In this case, they revert to the normal condition by synchronizing their running modes: the cooling mode is compatible with the dehumidifying mode and the fan mode can work with any other mode. If the supply power fails when the unit is running, the indoor unit sends the ³VWDUW´signal to the outdoor unit three minutes after power recovery. (6) Cautions for the Maintenance Personnel: During maintenance, prior to the startup of the compress, ensure the heating belt of the compressor has been powered for at least eight hours. Once the compressor starts, it must work continuously for at least 30 minutes. If not, it may be damaged. 4 Specifications are subject to change without notice. 2 Product Introduction The Multizone system adopts inverter compressor technology. According to change displacement of compressor, stepless capacity regulation within range of 15%~120% can be realized. Various product lineup is provided with capacity range from 30KBtu to 42KBtu, which can be widely used in a boarding house , a working area and especially applicable in a location with a variable load change. 2.1 Name of Main Parts ķ ĸ Ĺ Ļ ĺ NO. Name ķ Motor ĸ Fan Ĺ Electric Box ĺ Gas valve assembly Fig1 5 Specifications are subject to change without notice. Ļ Liquid valve assembly 2.2 Combinations for outdoor and indoor units High Wall Indoor Unit Duct Type Indoor Unit Cassettle Type Indoor Unit Floor Console Indoor Unit Fig 2 See Fig.2 for combinations for outdoor and indoor units. For the multizone series air conditioning system, one outdoor unit is able to drive up to five indoor units which can be cassette type, duct type, high wall or floor console type. The outdoor unit will run as long as any one indoor unit receives the running command, and all indoor units stop once the outdoor unit is turned off. Table 1 Energy Level and Capacity Code of the Indoor Indoor Unit High Wall Flooring ceiling Duct type Cassettle type Console 6 Nominal Unit Btuh 9,000 12,000 18,000 09,000 12,000 18,000 24,000 09,000 12,000 18,000 21,000 24,000 12,000 18,000 24,000 09,000 12,000 18,000 Indoor Model Number GWH09QC-D3DNA1D/I GWH12QC-D3DNA1D/I GWH18QD-D3DNA1G/I GTH(09)BA-D3DNA1A/I GTH(12)BA-D3DNA1A/I GTH(18)BA-D3DNA1A/I GTH(24)BA-D3DNA1A/I GFH(09)EA-D3DNA1A/I GFH(12)EA-D3DNA1A/I GFH(18)EA-D3DNA1A/I GFH(21)EA-D3DNA1A/I GFH(24)EA-D3DNA1A/I GKH(12)BA-D3DNA2A/I GKH(18)BA-D3DNA2A/I GKH(24)BA-D3DNA1A/I GEH(09)AA-D3DNA1C/I GEH(12)AA-D3DNA1C/I GEH(18)AA-D3DNA1C/I Specifications are subject to change without notice. Outdoor Model Number GWHD(30)ND3EO GWHD(36)ND3EO GWHD(42)ND3EO 2.3 Rated working condition Rating cooling Rating Heating Table 2 Indoor side state Dry buib temp.̧ Wet buib temp.̧ 80.06 66.92 69.98 60.08 Outdoor side state Dry buib temp.̧ Wet buib temp.̧ 95 75.02 47 43.00 NOTICE 1) The following listed cooling /heating capacity and noise is tested before shipping. 2) The parameters below are tested under a rated working condition. If there is any change to them, please refer to the nameplate. 3) The heating capacity parameters of the heat pump indoor unit excludes the auxiliary electric heating power. 2.4 The range of production working temperature Table 3 Outdoor Unit System size 7 30 36 42 Cooling Operating Range Outdoor Min - Max DB °F 0~118 0~118 0~118 Heating Operating Range Outdoor Min – Max DB °F -4~86 -4~86 -4~86 Specifications are subject to change without notice. 3 Preparation before Installation 3.1 Standard parts Please use the following standard parts included with the air conditioning units. Table 4 Outdoor Unit Parts Name Number Picture Quantity 1 Owner's manual 1 2 Tube connector subassy 8 Remark 3.2Selecting the installation site 1) Install the unit in a location that can withstand the weight of the unit and make sure the unit does not shake or fall off. 2) Never expose the unit to direct sunshine and rainfall. Install the unit at a place free of dust, typhoons and earthquakes. 3) Try to keep the unit away from combustible, inflammable and corrosive or exhaust gases. 4) Leave some space for heat exchanging and servising to guarantee the unit's normal operation. 5) Keep the indoor and outdoor units close to each other to shorten the pipe length and minimize the number of pipe bends. 6) Never allow children to approach the unit and prevent them from touching the unit. Figure 3 details the outdoor unit's required installation space when the outdoor unit is completely surrounded by walls. 1.64 1.64 19 2/3 1.64 19 2/3 3.28 6.56 78 3/4 1.64 6.56 78 3/4 unit:feet Fig 3 8 Specifications are subject to change without notice. 3.3 Piping Connection The maximum pipe length is shown in the following table. When the distance between units (piping length) is out of the range listed below, normal operation of the unit can not be guaranteed. Table 5 Connecting Pipe (inch) Max. Height Difference between Indoor Max. Pipe length(ft) Model Unit and Outdoor Unit (ft) Liquid Gas When the outdoor unit is above, 30K 3/8 229.6 Ï1/4 the maximum height difference between 36K Ï3/8 246.1 Ï1/4 the indoor and outdoor units is up to 49.2ft. When the indoor unit is above, 42K Ï1/4 Ï3/8 246.1 the maximum height difference between the indoor and outdoor units is up to 49.2ft. NOTICE 1) Use water-proof insulating pipe. 2) Wall thickness of pipe: 0.019-0.039 inch; bearing pressure: 3.0MPa 3) The longer the connection pipe is, the more the cooling and heating capacity will decrease. Outdoor Unit Refrige rant Piping System size 9 30 36 42 Min. Piping Length ft 9.84 9.84 9.84 Standard Piping Length ft 131.2 131.2 131.2 Max. outdoor-indoor height difference ft 49.2 49.2 49.2 Max. height distance between indoor and indoor ft 24.6 24.6 24.6 Max. height distance between indoor and outdoor and indoor ft 49.2 49.2 49.2 Max. height distance between indoor and outdoor and outdoor up ft 49.2 49.2 49.2 Max. equivalent piping outdoor to last indoor ft 82 82 82 Max. Piping Length with no additional refrigerant charge ft 131.2 131.2 131.2 Max. Piping Length ft 229.7 246 246 Additional refrigerant charge (between Standard – Max piping length) Oz/ft 0.2 0.2 0.2 Gas Pipe (size - connection type) in 3/8 3/8 3/8 Liquid Pipe (size - connection type) in 1/4 1/4 1/4 R-410A R-410A R-410A 6.17 8.05 8.05 Refrigerant Type Heat Pump Models Charge Amount Lbs Specifications are subject to change without notice. 4 Installation 4.1 Outline and dimension of the outdoor unit 30K Outline dimension and mounting holes 14 4/7 31 36 2/9 38 3/7 15 5/7 17 1/3 24 Unit:inch Fig 4 42K 336K, 8GJQG36---3 Outline dimension and mounting holes 14 1/4 42 1/2 17 1/3 43 3/7 40 15 3/4 24 5/6 Unit:inch Fig 5 10 Specifications are subject to change without notice. 4.2 Installation of the Connection Pipe Connecting piping for the indoor unit and outdoor unit are in the manifold mode (see the figure below). Fig 6 4.2.1 Piping between the Indoor and Outdoor Units (1) If the liquid and gas stop valves, which have the sign A , B, C, D or E , have not been connected to the indoor units, turn off the screw cap with the spanner airproof. (2) Refer to Fig.7 for the appropriate amount of torque to tighten the screws. (3) Point the flare end of the copper pipe at the screw and tighten the screw by hand. (4) Next, tighten the screw with the torque wrench until it emits a sound (as shown in Fig.7). (5) The bending degree of the pipe can not be too small; otherwise it will crack. Use a pipe tube bender to bend the pipe. (6) Wrap the exposed refrigerant pipe and the joints by sponge and then tighten them with the plastic tape. P ip e F la re N u t Pipe diameter ĭ1/4 inch ĭ3/8 inch ĭ1/2 inch ĭ5/8 inch Thickness of copper tube 0315 inch 0315 inch 0315 inch 0.0394 inch Tightening torque 11̚22 ft·lbf 26̚29 ft·lbf 33̚37 ft·lbf 44̚48 ft·lbf Spanner Fid 7 1) During the connection of the indoor unit and the refrigerant pipe, never pull the indoor unit joints forcefully, otherwise the capillary or other pipes may crack, which would result in leakage. 2) The refrigerant pipe should be supported by brackets. Do not allow the unit to support the weight of the refrigerant pipe. 3) If the piping connection size of the outdoor unit does not match the piping connection size of the indoor unit, use the piping connection dimension of the indoor unit. Use different-diameter joints which is installing on the place of the piping connection to connect the indoor unit. 4) For the Free Match system, each pipe should be labeled to indicate which system it belongs to avoid mistaken inaccurate piping. 4.2.2 Allowable pipe length and drop height among indoor and outdoor units If the total refrigerant pipe length (liquid pipe) is shorter than that listed in the table below, no additional refrigerant will be charged. Table 6 Model 30K 42K 36K Total Liquid Pipe 131.2ft 131.2ft 131.2ft Length (a+b+c+d+e) 11 Specifications are subject to change without notice. Allowable Length and Height for the Refrigerant Pipe Table 7 Allowable Value 30K 36K 42K Total length (actual length) of fitting pipe 229.6ft 246.1ft Length of farthest fitting pipe (ft) 82ft 82ft LX˄X=1ˈ2ˈ3ˈ4,5˅ 49.2ft 49.2ft H1 49.2ft 49.2ft H3 24.6ft 24.6ft H2 Outdoor unit at upper Outdoor unit at lower Height difference between indoor units (m) Outdoor unit Indoor unit Height difference between indoor units H2 Height difference between indoor unit and outdoor unit H1 Height difference between outdoor unit and indoor unit Fitting Pipe L1 +L2 +…+L M(M İ5) Equivalent length of the farthest fitting pipe Lx L1 L2 a b Indoor unit L3 L4 L5 c d e Fig 8 Total Pipe1/4 x 0.23 + Total Pipe3/8 x 0.58 ¨C 31 oz If the calculation results in a negative number no addition refrigerant is required. The maximum additional refrigerant is 28.2 oz regardless of the calculation 12 Specifications are subject to change without notice. 4.2.3 Installation of the Refrigerant Pipe Protection Layer The refrigerant refrigerant pipe should be insulated by the insulating material and plastic tape to prevent condensation and water leakage. The joints of the indoor unit should be wrapped with the insulating material.Ensure there is no gap on the joint of the indoor unit, as shown in Fig.9. The thermal insulating layer is required to be wrapped at this part. Thermal insulating pipe No gap Fig 9 After the pipe is protected, do not bend it to form a small angle; otherwise it will crack or break. (3)Wrap the Pipe with Tape˖ a. Bundle the refrigerant pipe and electric wire together with tape, and separate them from the drain pipe to prevent the condensate water from overflowing. b. Wrap the pipe from the bottom of the outdoor unit to the top of the pipe where it enters the wall. During the wrapping, the later circle should cover half of the former one. c. Fix the wrapped pipe on the wall with clamps. 1) Do not wrap the pipe too tight; otherwise the insulation effect would be weakened.Ensure drain hose is separated from the pipe. 2) Next, fill the hole on the wall with sealing material to prevent wind and rain from entering the room. 4.2.4 Support and protection for the pipeline Support should be made for hanging the connection pipe. The distance between each support can not exceed 3.3 ft (1m). 13 Specifications are subject to change without notice. 4.3 Air Purging and Refrigerant Charge 4.3.1 Air purging (1) The refrigerant in the outdoor unit was charged before shipment. Additional refrigerant needs to be charged into the refrigerant pipe during the field installation. (2) Ensure the outdoor unit's liquid and gas valves are closed completely. (3) As shown in the following figure (Fig.10), expel the gas inside the indoor unit and the refrigerant pipe with the vacuum pump. low side high side "HI"Knob "LO"Knob liquid valve Vacuum pump Connection hose Gas valve Fig 10 (4) When the compressor is not running, charge the R410A refrigerant into the refrigerant pipe from the liquid valve of the outdoor unit (do not charge from the gas valve). 4.3.2 Additional refrigerant charging (1) Refrigerant Charge in the Outdoor Unit before Shipment NOTICE 1) The outdoor unit has been charged with refrigerant prior to delivery. The refrigerant charge is not included and is an additional charge for the indoor unit and the refrigerant pipe. 2) The amount of the additional refrigerant charge depends on the diameter and length of the liquid refrigerant pipe which is determined by the actual yield installation requirement. 3) Record the additional refrigerant charge for future maintenance. (2) Calculation of the Additional Refrigerant Charge Additional Refrigerant Charge= Length of Liquid Pipe¶0.375×54+Length of Liquid Pipe¶0.25×22)-880 The largest additional refrigerant charge value is 800g.This means if the calculated value exceeds 800g, the additional refrigerant charge takes 800g, while the calculated value takes less than 800g, the additional refrigerant charge takes the calculated value. 14 Specifications are subject to change without notice. 4.4 Electric Wiring 4.4.1 Wiring precautions (1) The installation must be done in accordance with the national wiring regulations. (2) The electric installation should be by technician instructed the local laws, regulations and this manual. (3) The ground should be firm and thegroundshould be connected to the dedicated device of the building by the technician.The breaker coupled with the leakage current protection switch must be equipped and have enough capacity in both the magnetic and thermal tripping functions in case of the short circuit and overload. Table 8 !! Warning Models Power Supply 30K 36K 42K 208/230V~60Hz 208/230V~60Hz 208/230V~60Hz Capacity of the breaker A 30 30 30 GWHD(30)ND3EO OUTDOOR UNIT XT L1 L2 N( 1) 2 GND L1 L2 PE 3 3 N( 1) 2 GND N( 1) 2 GND POWER 3 PE INDOORUNIT A 3 PE GND INDOORUNIT B N( 1) 2 3 N( 1) 2 GND N( 1) 2 GND XT 4 XT3 XT2 XT1 GND 3 N( 1) 2 3 PE GND PE GND 3 N(1 ) 2 GND INDOORUNIT D INDOORUNIT C Fig 11 GWHD(36)ND3EO、GWHD(42)ND3EO OUTDOOR UNIT XT L1 L2 N( 1) 2 GND L1 L2 GND POWER 3 PE N( 1) 2 N( 1) 2 GND 3 GND INDOORUNIT A 3 PE N( 1) 2 GND N( 1) 2 3 GND INDOORUNIT B N( 1) 2 3 PE GND N( 1) 2 3 N( 1) 2 GND INDOORUNIT C N( 1) 2 3 PE GND 3 GND INDOORUNIT D Fig 12 15 XT5 XT4 XT3 XT2 XT1 Specifications are subject to change without notice. 3 PE N( 1) 2 GND 3 GND INDOORUNIT E PE 4.4.2 Grounding Requirements (1) The air conditioner is classified as a Class I appliance, so its grounding must be reliable. (2) The yellow-green line of the air conditioner is the ground and can not be used for any other purpose, cut off or fixed by the tapping screw; otherwise it would cause an electric shock. (3) A reliable ground terminal should be provided and the ground wire can not be connected to any of the following items: ķRunning water pipe ĸCoal gas pipe ĹSewage pipe ĺOther places where the professional personnel think unreliable. 4.4.3 Electrical Cable Connection 1) A mistake connecting the line will result in a malfunction. After the electrical wiring is working, ensure the wire between the connection place and the fixed place has a certain amount of space. 2) The connection piping and connection line of each indoor unit should connect well according to the instruction. 3) The electric installation should be carried out by a technician instructed in the local laws, regulations and this manual. 4) The installation location should be dry, shielded from direct sunlight or strong winds. 5) Install a breaker in the circuit that can shut off the system's main power supply. Also install an breaker coupled with the leakage current protection switch must be equipped. 4.4.4 Wiring of the Power Wire (1). Open the side plate. (2). Connect the power wire to terminals ĀL1ā, ĀL2āand the grounding screw. Next, connect the wiring terminals ĀN(1),2,3ā of the indoor unit to the corresponding outdoor unit terminals. (3). Fix the power wire with wire clips. (4). Place the power wire through the rubber ring. If the supply wire is damaged, it must be replaced by the manufacturer or its service agent or a similarly qualified person to avoid a hazard. 16 Specifications are subject to change without notice. 5 Troubleshooting 1) In the event of abnormal conditions (for example, a foul smell), shut off the main power supply immediately and contact your Service Center.Operating under abnormal conditions would damage the air conditioning unit and would cause electric shock or a fire hazard. 2) Do not attempt to repair the air conditioning.Contact a professionally skilled technician at the appointed service center. An incorrect repair would cause electric shock or a fire hazard. Check before Contacting Service Center. Check Items Has the unit been secured firmly? Have you done the gas leakage test? Does the unit have proper thermal insulation? Does the unit drain well? Is the voltage in accordance with the rated voltage specified on the nameplate? Is the electric wiring and piping connection installed correctly and securely? Has the unit been grounded securely? Is the power cord specified? Has the inlet and outlet been blocked? Table 9 Conditions Might Happen The unit may drop, shake or emit noise. It may cause insufficient cooling/heating capacity. It may cause condensation and dripping. It may cause condensation and dripping. It may cause a malfunction or damage the part. Check It may cause malfunction or damage the part. It may cause electrical leakage. It may cause malfunction or damage the part. It may cause insufficient cooling/heating capacity. NOTICE! If the air conditioner still runs abnormally after the above checks, please contact a maintenance serviceman at the local appointed service center and provide a description of the error as well as the model of the unit. 17 Specifications are subject to change without notice. 6 The conditions listed below are not classified into errors. The unit does not run The unit blows out mist The unit generates noise The unit blows out dust. The unit emits odors. Table 10 Conditions When restart the unit soon after it is stopped. Causes The overload protection switch of the unit let the startup delayed for three minutes. The unit will stand by for approximate one As soon as power is on. minute. When the cooling operation starts. The hi-humidity air indoor is cooled quickly. The unit “clatters” as soon as it It is the sound generated during the initialization of the electronic expansion valve. starts running. The unit “swishes ” during the It is the sound when the refrigerant gas runs inside the unit. cooling operation. The unit “swishes ” when it is It is the sound when the refrigerant gas stops running. started or stopped. The unit “swishes” when it is in It is the sound when the draining system is operating. and after the running. It is the sound of frication generated by the skin The unit “squeaks” when it is in plate etc which swells due to the temperature and after the running. change. When the unit restarts after it is not The dust inside the unit is blown out again. used for a long time. When the unit is running. The odors absorbed in are blown out again. NOTICE! If problem can not be solved after checking the above items, please contact C&H service center and show phenomena and models. Following circumstance are not malfunction Table 11 Malfunction Reason Unit doesn’t run When unit is started Overload protection switch makes it run after 3 minutes immediately after it is just delay turned off When power is turned on Standby operating for about 1 minute Mist comes from the Under cooling Indoor high humidity air is cooled rapidly unit Noise is emitted Slight cracking sound is heard It is noise when electronic expansion valve initialization when just turned on That's sound for gas refrigerant flowing in unit The unit blows out duct The unit emits odor There is consecutive sound when cooling There is sound when unit starts or stops There is slight and consecutive sound when unit is running or after running Cracking sound is heard when unit is operating and after operating When unit runs after no operation for a long period Operating Indoor unit still runs after switch off After every indoor unit receive "stop" signal, fan will keep Indoor fan motor will keep running 20-70s so as to take good use of excess cooling and heating and prepare for That's sound for gas refrigerant stops to flow That's sound for operation of drainage system That’s sound caused by expansion of panel and other parts due to temperature change Dust in indoor unit is blew out The room odor absorbed by the unit is blew out again 15 18 Specifications are subject to change without notice. Mode conflict 19 running next operation COOL or HEAT mode can not be operated When the indoor operating mode conflicts with that of outdoor unit, indoor fault indicator will flash and conflict will be shown on the wired controller after 5 minutes. Indoor unit stops to run and meanwhile change outdoor operating mode as the same as that of indoor unit, then the unit will go back to normal. COOL mode doesn't conflict with DRY mode. FAN mode doesn't conflict with any mode. Specifications are subject to change without notice. 7 Troubleshooting The error code will be displayed on the wired controller and the main board of the outdoor unit The meaning of each error, as shown in table 13. Table 12 The indicator display Name of malfunction Yellow light Red light Green light Compressor runs Flash once Defrost Flash twice Anti-freezing protection Flash 3 times IPM protection Flash 4 times AC over-current protection Flash 5 times Over-burden protection Flash 6 times Compressor exhaust high temperature protection Flash 7 times Compressor overload protection Flash 8 times Power protection Flash 9 times EEPROM reads and write protection Flash 11 times Low PN voltage protection Flash 12 times Over voltage protection for PN Flash 13 times PFC protection Flash 14 times PFC module temperature protection Flash 15 times Low pressure protection Flash 17 times High pressure protection Flash 18 times Limit/decline frequency(electric current) Flash 1 times Frequency limit(exhaust) Flash 2 times Frequency limit(Over-burden) Flash 3 times Outdoor ambient sensor malfunction Flash 6 times Outdoor tube sensor malfunction Flash 5 times Exhaust sensor malfunction Flash 7 times Attain the temperature of switch on Flash 8 times Frequency limit(power) Flash 13 times Outdoor fan malfunction Flash 14 times Frequency limit(PFC module temperature) Flash 15 times PFC module sensor malfunction Flash 16 times Liquid pipe temperature sensor malfunction of A Flash 17 times Gas pipe temperature sensor malfunction of A Flash 18 times Liquid pipe temperature sensor malfunction of B Flash 19 times Gas pipe temperature sensor malfunction of B Flash 20 times Liquid pipe temperature sensor malfunction of C Flash 21 times Gas pipe temperature sensor malfunction of C Flash 22 times Liquid pipe temperature sensor malfunction of D Flash 23 times Gas pipe temperature sensor malfunction of D Flash 24 times Liquid pipe temperature sensor malfunction of E Flash 25 times Gas pipe temperature sensor malfunction of E Flash 26 times Exit of the condenser tube sensor malfunction Flash 27 times Flash n times(n=indoor Correspondence is normal unit number) Often bright Communication failure between indoor unit and (indoor unit all outdoor unit Communication failure) 20 Specifications are subject to change without notice. 7 Maintenance A regular inspection, maintenance and care should be performed by professional personnel, which will prolong the unit's life span. 7.1 Outdoor heat exchanger The outdoor heat exchanger should be cleaned once every two months. Use a vacuum cleaner with a nylon brush to clean up dust and small particles on the surface of the heat exchanger. Blow away dust with compressed air, if available. Never use water to wash the heat exchanger. 7.2 Drain Pipe Regularly check if the drain pipe is clogged to drain condensate smoothly. 7.3 Notice before Seasonal Use (1) Check if the inlet/outlet of the indoor/outdoor unit is clogged. (2) Check if the ground wire is grounded correctly. (3) Check if the battery of remote wireless controller has been replaced. (4) Check if the filter screen has been set correctly. (5) After a long period of nonuse, open the main power switch 8 hours before re-operating the unit to preheat the compressor crankcase. (6) Check if the outdoor unit is installed securely. If there is anything abnormal, contact the appointed service center. 7.4 Maintenance after Seasonal Use (1) Cut off the main power supply to the unit. (2) Clean the filter screen and the indoor and outdoor units. (3) Clean the dust and small particles on the indoor and outdoor units. (4) In the event of rusting, use anti-rust paint to stop t h e spreading of rust. 7.5 Parts Replacement Purchase parts from an appointed service center or dealer if necessary. NOTICE! During the airtight and leakage test, never mix oxygen, ethyne and other dangerous gas into the refrigeration circuit. In case of hazard, it is better to use nitrogen or refrigerant to perform the test. 21 Specifications are subject to change without notice. www.cooperandhunter.us MANUFACTURER: GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI Add: West Jinji Rd, Qianshan, Zhuhai, Guangdong, China, 519070
advertisement
Key Features
- Inverter technology for precise temperature control and energy efficiency
- Multi-zone capability allows for independent temperature control in multiple rooms
- Quiet operation for minimal noise disturbance
- Compact design for easy installation in tight spaces
- Durable construction for long-lasting performance
- Advanced diagnostics for easy troubleshooting
- Wireless remote control for convenient operation