The Mitsubishi Electric EW-50E is a centralized controller designed to manage and monitor your air conditioning system. It allows you to operate and adjust settings for connected indoor units, outdoor units, and other equipment through a web browser interface. You can create schedules, set operation modes, change temperature and fan speed, and monitor energy usage. The EW-50E can control up to 200 indoor units when connected to an AE-200 controller, making it ideal for managing large commercial or residential systems. This controller also supports advanced features like external input/output signals for controlling operations, malfunction logs, and software updates for system maintenance.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Mitsubishi Electric EW-50E Installation And Instruction Manual | Manualzz

Air Conditioning Control System

Centralized Controller

EW-50A/EW-50E

Installation and Instructions Manual

Safety notes are marked with WARNING or

CAUTION, depending on the severity of possible consequences that may result when the instructions are not followed exactly as stated.

Proper installation is important for your safety and proper functioning of the units.

Thoroughly read the following safety precautions prior to installation.

Contents

1. Safety precautions .......................................................................2

1-1. General precautions ....................................................................................... 2

1-2. Precautions for unit installation ....................................................................... 3

1-3. Precautions for electrical wiring ...................................................................... 3

1-4. Precautions for relocating or repairing the unit ............................................... 4

1-5. Additional precautions .................................................................................... 4

2. Introduction ..................................................................................6

2-1. Part names ..................................................................................................... 6

3. Package contents .........................................................................8

4. Specifications ...............................................................................9

4-1. Product specifications ..................................................................................... 9

4-2. External dimensions ..................................................................................... 10

4-3. Product features ............................................................................................11

5. System configuration ..................................................................14

5-1. System restrictions ....................................................................................... 14

5-2. M-NET power feeding coefficient .................................................................. 15

5-3. System configuration example ..................................................................... 16

5-4. Number of connectable units ........................................................................ 20

5-5. Setting M-NET address for various devices ................................................. 21

6. Installation ..................................................................................23

6-1. Items not included ........................................................................................ 24

6-2. Items sold separately .................................................................................... 24

6-3. M-NET transmission cable length ................................................................. 25

6-4. Installation space .......................................................................................... 26

6-5. Installation procedures ................................................................................. 27

7. Wiring connections .....................................................................30

7-1. Removing/reinstalling the service cover ....................................................... 30

7-2. Connecting AC power cables and M-NET transmission cables.................... 32

7-3. Connecting the LAN cable ............................................................................ 34

7-4. Confirming the LAN transmission delay time ................................................ 34

8. Initial settings .............................................................................36

8-1. Logging in to the Web Browser for Initial Settings ........................................ 36

8-2. Initial settings on the Web browser ............................................................... 36

8-3. Quick IP address setting ............................................................................... 37

8-4. Network settings on the Web browser .......................................................... 38

9. Test run ......................................................................................39

9-1. Collective operation ON/OFF ....................................................................... 39

10. External input/output ..................................................................40

10-1. External signal input/output function ........................................................... 40

10-2. Pulse signal input function .......................................................................... 44

11. Maintenance ...............................................................................45

11-1. Inspection and maintenance ....................................................................... 45

11-2. Back up/import settings data....................................................................... 46

11-3. Software update .......................................................................................... 48

11-4. Software information ................................................................................... 51

12. Error code list .............................................................................52

12-1. M-NET errors .............................................................................................. 52

12-2. Errors between AE-200 and AE-50 (EW-50) .............................................. 54

Before installing the controller, please read this Installation Manual carefully to ensure proper operation.

Retain this manual for future reference.

1. Safety precautions

Thoroughly read the following safety precautions prior to installation.

Observe these precautions carefully to ensure safety.

After reading this manual, pass the manual on to the end user to retain for future reference.

The user should keep this manual for future reference and refer to it as necessary. This manual should be made available to those who repair or relocate the units. Make sure

that the manual is passed on to any future air conditioning system user.

All electrical work must be performed by qualified personnel.

: indicates a hazardous situation which, if not avoided, could result in death or serious injury.

: indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.

: addresses practices not related to personal injury, such as product and/or property damage.

1-1. General precautions

Do not install the controller in areas where large amounts of oil, steam, organic solvents, or corrosive gases (such as ammonia, sulfuric compounds, or acids), or areas where acidic/alkaline solutions or special chemical sprays are used frequently. These substances may significantly reduce the performance and corrode the internal parts, resulting in electric shock, malfunction, smoke, or fire.

To reduce the risk of injury, electric shock, or fire, do not alter or modify the controller.

To reduce the risk of electric shock, malfunction, smoke, or fire, do not touch the electrical parts or USB memory with wet fingers.

To reduce the risk of injury or electric shock, before spraying a chemical around the controller, stop the operation and cover the controller.

To reduce the risk of burns, do not touch the electrical parts with bare hands during and immediately after operation.

To reduce the risk of injury, keep children away while installing, inspecting, or repairing the controller.

Test runs, inspection, and service must be performed by qualified personnel in accordance with this manual. Incorrect use may result in injury, electric shock, malfunction, or fire.

If you notice any abnormality, stop the operation and turn off the controller. Continuing the operation may result in electric shock, malfunction, or fire.

Properly install all required covers to keep moisture and dust out of the controller. Dust accumulation and the presence of water may result in electric shock, smoke, or fire.

To reduce the risk of frostbite, burns, injury, or electric shock, keep the equipment out of the reach of children.

WT07417X01

2

To reduce the risk of fire or explosion, do not place flammable materials or use flammable sprays around the controller.

To reduce the risk of electric shock or malfunction, do not touch the switches or buttons with a sharp object.

To reduce the risk of injury, electric shock, or malfunction, avoid contact with the sharp edges of certain parts.

To reduce the risk of injury, wear protective gear when working on the controller.

Wear protective gear when working on the controller. High-voltage parts pose a risk of electric shock, and high-temperature parts pose a risk of burns.

1-2. Precautions for unit installation

Do not install the controller where there is a risk of flammable gas leaks. If flammable gas accumulates around the controller, it may ignite and cause a fire or explosion.

Properly dispose of the packing materials. Plastic bags pose a suffocation hazard to children.

Take appropriate safety measures against earthquakes to prevent the controller from causing injury.

To prevent injury, install the controller on a flat surface strong enough to support its weight.

To reduce the risk of short circuits, current leakage, electric shock, malfunction, smoke, or fire, do not install the controller in a place exposed to water or in a condensing environment.

The controller must be installed by qualified personnel according to the instructions detailed in this manual. Improper installation may result in electric shock or fire.

1-3. Precautions for electrical wiring

To reduce the risk of malfunction, smoke, fire, or damage to the controller, do not connect the power cable to the signal terminal block.

To reduce the risk of malfunction, smoke, fire, or damage to the controller, do not apply a power supply voltage in excess of that specified.

Properly secure the cables in place and provide adequate slack in the cables so as not to stress the terminals. Improperly connected cables may break, overheat, and cause smoke or fire.

To reduce the risk of injury or electric shock, switch off the main power before performing electrical work.

WT07417X01

3

Electrical work must be performed by qualified personnel in accordance with local regulations and the instructions provided in this manual. Only use specified cables and dedicated circuits. Inadequate power source capacity or improper electrical work will result in electric shock, malfunction, or fire.

To reduce the risk of electric shock, install an overcurrent breaker and an earth leakage breaker on the power supply. To reduce the risk of electric shock, smoke, or fire, install an overcurrent breaker for each controller.

Only use properly rated breakers (earth leakage breaker, local switch <switch + fuse that meets local electrical codes>, moulded case circuit breaker, or overcurrent breaker). The use of improperly rated breakers or the substitution of fuses with steel or copper wire may result in electric shock, malfunction, smoke, or fire.

To reduce the risk of current leakage, overheating, smoke, or fire, use properly rated cables with adequate current carrying capacity.

Proper grounding must be provided by qualified personnel. Do not connect the protective ground wire to a gas pipe, water pipe, lightning rod, or telephone wire. Improper grounding may result in electric shock, smoke, fire, or malfunction due to electrical noise interference.

To reduce the risk of short circuits, electric shock, or malfunction, keep wire pieces and sheath shavings out of the terminal block.

To reduce the risk of short circuits, current leakage, electric shock, or malfunction, keep the cables out of contact with controller edges.

To reduce the risk of electric shock, malfunction, or fire, seal the gap between the cable and the end of the conduit tube with putty.

To reduce the risk of injury, do not touch the burrs of the knockout holes.

1-4. Precautions for relocating or repairing the unit

The controller must be repaired or moved only by qualified personnel. Do not disassemble or modify the controller. Improper installation or repair may result in injury, electric shock, or fire.

To reduce the risk of short circuits, electric shock, malfunction, or fire, do not touch the circuit board with tools or with your hands, and do not allow dust to accumulate on the circuit board.

1-5. Additional precautions

To avoid damage to the controller, use appropriate tools to install, inspect, or repair the controller.

To prevent unauthorized access, always use a security device such as a VPN router when connecting to the Internet.

WT07417X01

4

Take appropriate measures against electrical noise interference when installing the controller in hospitals or radio communication facilities. Inverter, high-frequency medical, or wireless communication equipment as well as power generators may cause the air conditioning system to malfunction. The air conditioning system may also adversely affect the operation of these types of equipment by creating electrical noise.

To avoid malfunction, do not bundle power cables and signal cables together or place them in the same metallic conduit.

To avoid damage to the controller, do not overtighten the screws.

To avoid deformation and malfunction, do not install the controller in direct sunlight or where the ambient temperature may exceed 55°C (131°F) or drop below -10°C (14°F).

This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.

WT07417X01

5

2. Introduction

EW-50A/EW-50E is a total management system.

Any connected air conditioning systems can be operated or monitored on the Web browser. EW-50A/EW-50E can also be used as an expansion controller of AE-200A/AE-200E.

By connecting AE-200A/AE-200E, up to 200 indoor units and other equipment can be controlled.

Hereafter, AE-200A and AE-200E, unless otherwise specified, will be called “AE-200.”

Hereafter, AE-50A and AE-50E, unless otherwise specified, will be called “AE-50.”

Hereafter, EW-50A and EW-50E, unless otherwise specified, will be called “EW-50.”

Note: A PC is required to monitor and operate the air conditioning units.

Note: The required licenses vary, depending on the functions to be used. Consult your dealer.

Note: For how to use the Web browser, refer to the Web browser instruction books (separate volume).

2-1. Part names

USB port

(unused)

ON/OFF

Power Status

Push switch ON/OFF

Push switch Reset

LINK/ACT2

LINK/ACT1

Power

Item

Lit in green

Unlit

Lit in green

LED

ON/OFF

Status

Blink in green

Unlit

Blink in orange

Blink in blue

Blink in pink

Blink in orange

LINK/ACT1

LINK/ACT2

ON/OFF

Push switch

Reset

USB port

*1 The operation status of the other equipment are excluded.

Service cover

Description

Power ON

Power OFF

One or more air conditioning units are ON.

*1

One or more air conditioning units or other related equipment are in error.

All air conditioning units are OFF. *1

Startup error

Software update in progress

Software update failed

Data transmission in progress (LAN1)

Unused

Used to turn the connected air conditioning units and the other related equipment ON and OFF all at once.

Used to reboot the EW-50. (This will not affect the operation status of the air conditioning units.)

Unused

WT07417X01

6

* Back side with the service cover removed

SW1

LAN1

LAN2

(Unused)

CN7

CN6

(Unused)

CN4

(Unused)

CN5

CN21

TB3

TB1

Ground

SW1

LAN1

LAN2

CN7 (Pulse Input)

CN6

CN4

CN5 (External I/O)

*1

Item

*1

CN21 (M-NET power jumper)

Description

IP addresses can be easily set with SW1. Refer to section 8-3 “Quick IP

address setting” for details.

Connects to other units of equipment over the LAN via a HUB.

Unused

Connects to metering devices using the supplied connector.

Unused

Unused

Connects to an external input/output adapter PAC-YG10HA-E.

(When connecting an external input/output adapter PAC-YG10HA-E, cut out the knockout hole.)

Connects to the M-NET power jumper to supply power (default).

* If another system controller is connected to the same M-NET system and the power consumption coefficient is 1.5 or above, disconnect the M-NET power jumper to supply

power from the separately-sold power supply unit. (Refer to section 5-2 “M-NET power feeding coefficient” for details.)

TB3 (M-NET A, B, S) (M3.5)

M-NET transmission terminal block

Connects to M-NET transmission cables from the outdoor unit.

(A, B: Non-polarized, S: Shield)

TB1 (Power source AC L/L1, N/L2) (M3.5)

Ground (M4)

Connects to the power cable.

Connects to the protective ground wire.

*1 Refer to chapter 10 “External input/output” for details.

WT07417X01

7

3. Package contents

The following items are included in the package.

Package contents

(1)

EW-50

Qty.

1

(2)

Connector (CN6)

(Unused)

(3)

Connector (CN7)

(Used for pulse input)

(4)

L-fitting

(5)

DIN rail attachment

(for attaching DIN rail of 35 mm (1-7/16 in) width)

(6)

DIN rail auxiliary bracket 1

(7)

(8)

Roundhead screw (M3 × 12) *1

(for fixing DIN rail attachment)

Roundhead screw (M3 × 6) *1

(for fixing DIN rail auxiliary bracket or L-fitting)

4

4

(9)

Cable tie

4

(Two are spare.)

(10)

Installation and Instructions Manual (this manual) *2

CD-ROM *2

Installation and Instructions Manual (this manual)

Instruction Book (Web Browser for Initial Settings)

Instruction Book (Web Browser for System Maintenance Engineer)

Instruction Book (Web Browser for User)

(11)

Note

● The CD-ROM can only be played on a CD-drive or a DVD-drive. Do not attempt to play the

CD-ROM on an audio CD player as this may damage your ears and/or speakers.

● Each document is in PDF format. Viewing documents requires a computer with Adobe ®

Reader

®

or Adobe

®

Acrobat

®

installed. “Adobe

®

Reader

®

” and “Adobe

®

Acrobat

®

” are registered trademarks of Adobe Systems Incorporated.

*1 ISO metric screw thread

*2 For details about the apportioned electricity billing function, refer to the Instruction Book that comes with the “Charge” license.

1

1

Notes on the SD card installed on the EW-50

● Do not use the SD card installed on the EW-50 for any other equipment.

1

1

2

2

WT07417X01

8

4. Specifications

4-1. Product specifications

Item

Power supply

M-NET power feeding coefficient

Ambient conditions

Temperature

Operating temperature range

Storage temperature range

Humidity

Dimensions (W × H × D)

Weight

Installation conditions

Specifications

100–240 VAC ± 10%; 50/60 Hz Single-phase

1.5

-10°C – +55°C (+14°F – +131°F)

-20°C – +60°C (-4°F – +140°F)

30%–90% RH (Non-condensing)

172 × 209 × 92 mm

(6-13/16 × 8-4/16 × 3-10/16 in)

* 253 × 172 × 92 mm (10 × 6-13/16 × 3-10/16 in) when using L-fittings

1.7 kg (4 lbs)

Only in a metal control box indoors

WT07417X01

9

4-2. External dimensions

(1) When using L-fittings

L-fitting

(supplied)

L-fitting

(supplied)

100 (3-15/16)

169 (6-11/16)

172 (6-13/16)

(2) When using DIN rail

150 (5-15/16)

46 (1-13/16)

Unit: mm (in)

38

(1-8/16)

92 (3-10/16)

23 (15/16)

DIN rail

DIN rail attachment

(supplied)

DIN rail auxiliary bracket

(supplied)

WT07417X01

10

4-3. Product features

The table below summarizes the available functions and settings on the Web browser. Refer to the Web browser instruction books (separate volume) for details.

Operation *1

Function

ON/OFF

Operation mode

Set temperature

Air direction

Fan speed

Fan speed

(LOSSNAY unit)

Fan mode (HWHP unit)

Ventilation mode

(LOSSNAY unit)

Interlocked ventilator

(LOSSNAY unit)

ON/OFF

Prohibition of local remote controller operation

Filter sign reset

Schedule

The fan speed (3 speeds and Auto) can be changed.

The fan can be set to keep rotating even while the unit is stopped to avoid snow accumulation on the fan guard during the winter.

The ventilation mode can be switched.

Interlocked LOSSNAY units (if any) can be operated or stopped collectively or for each group or block.

Some operations or settings from the local remote controllers can be prohibited collectively or for each group or block.

Filter sign can be reset collectively or for each group or block.

Weekly, annual, and today’s schedules can be set collectively or for each group or block.

Schedule (Available/

Not Avail.)

Malfunction reset

Clear malfunction log

Description

The ON/OFF operation can be performed collectively or for each group or block.

The operation mode can be switched collectively or for each group or block. (The available operation modes depend on the unit model.)

The set temperature can be set collectively or for each group or block. (The available set temperatures depend on the unit model.)

The air direction can be changed collectively or for each group or block. (The available air directions depend on the unit model.)

The fan speed can be changed collectively or for each group or block. (The number of available fan speeds depend on the unit model.) Auto mode is available only on the models that support Auto mode.

The scheduled operations can be enabled or disabled.

Displayed errors can be reset.

Displayed unit errors and communication errors can be cleared.

External input

Using external contact signals, the following collective operations can be controlled:

Demand level, Emergency stop, ON/OFF operation, and Prohibit/Permit local remote controller operation.

* A separately-sold external input/output adapter (PAC-YG10HA-E) is required.

* Connect the external input/output adapter to each AE-200/AE-50/EW-50.

Displays and compares the energy-control-related status, such as electric energy consumption, operation time, and outdoor temperature, in a graph.

Displays the rankings in electric energy consumption and the fan operation time of given indoor units in a bar graph.

Sets the target electric energy consumption values for the entire system for the current year, each month, each day of the week, and each block. The set values will be displayed in the graph on the [Energy Use Status] screen and the [Ranking] screen.

Monitor *1

Energy Use Status

Ranking

Target Value Setting

Peakcut Control

Status

Condition List

Prohibition of local remote controller operation

Displays the average electric power consumption and the control level.

Displays the operation status of each group.

Displays the icon to indicate that the operation is prohibited by the EW-50.

Measurement List

Displays the readings of the temperature sensor, humidity sensor, and metering device.

WT07417X01

11

Monitor *1

Operation *1

Functions 1

Function

*1

Malfunction List

Filter sign

AHC List

Free Contact List

Malfunction Log

Send Mail Log

Outdoor unit status

External output

Date and time

License

Basic System

Groups

Interlocked

LOSSNAY

Blocks

E-Mail

Peak Cut

Measurement

Description

Displays the address of the unit in error and error code.

Indicates that the filter on the unit in a given group is due for cleaning.

Displays the input and output status of Advanced HVAC CONTROLLERs.

Displays the ON/OFF status of the indoor unit free contact.

Displays unit errors and communication errors.

Displays a list of error notification e-mail that have been sent.

Displays outdoor unit capacity value, high pressure, and low pressure of each outdoor unit.

Outputs signals (ON/OFF, Error) to an external device.

* A separately-sold external input/output adapter (PAC-YG10HA-E) is required.

* The operation status of general equipment (via a DIDO controller (PAC-YG66DCA)) will not be output.

Sets the current date/time and daylight savings time.

Registers license for optional functions.

Sets unit name, unit ID, IP address, subnet mask, gateway, display format, M-NET address, range of prohibited controllers, external input setting, and advanced setting.

Registers air conditioning units, Air To Water (PWFY) units, LOSSNAY units, general equipments, remote controllers, and sub system controllers to a group.

Interlocks the operation of indoor units and LOSSNAY units.

Registers groups to a block.

The e-mail server information, EW-50 e-mail information, and e-mail settings for the error notification e-mail function and e-mail communication function can be set.

The Peak Cut method and control settings for outdoor and indoor units can be set.

AI and PI controllers, temperature sensor, humidity sensor, and metering device can be registered. The trend data format, error notification e-mail function settings, and e-mail alarm function settings can be set.

Functions 2

*1

Energy

Management

Settings

Set Temperature

Range Limit

Night Mode

Schedule

Functions 3 *1

System-changeover

External

Temperature

Interlock

Night Setback

Control

Interlock control

AHC Port Name

Settings

The settings related to energy-use-status display can be made.

The settable temperature range can be set.

The start/end times for the Night mode (quiet operation) for outdoor units can be set.

This function switches the operation modes of the indoor units connected to the same outdoor unit between cooling and heating based on the room temperature and the set temperature. The target outdoor units and details for this function can be set.

This function adjusts the set temperature based on the temperature difference between the set temperature and the outdoor temperature. A maximum temperature value to be added to the set temperature can be set for each group.

This function performs cooling or heating operation when the room temperature goes outside of the specified temperature range. The start/end times and temperature range can be set for each group.

Interlock control between the connected devices can be performed by making various settings. Up to 150 interlocking conditions can be set.

The names of the AHC analog/digital input/output ports can be set.

Maintenance user User name and password for maintenance users can be set.

User settings

Building manager User name, password, and available functions to building managers can be set.

WT07417X01

12

Function Description

Back up settings data

Import settings data

Group setting information/

Interlocked LOSSNAY information

Malfunction log

Scheduled operations

Current date and time

CSV output

Software Update

Backed-up settings data can be restored from the PC.

Backed-up settings data can be restored from a PC.

The group setting information and interlocked LOSSNAY information are retained in the hardware, even if power is turned off.

The malfunction log is retained in the hardware, even if power is turned off.

The scheduled operations set for each group are retained in the hardware, even if power is turned off.

The current date and time are retained by the built-in capacitor when power is turned off.

The operation data, such as apportioning parameters and power consumption, can be output.

The software can be updated by inserting a CD or USB memory device in which the update file is stored to a PC.

Time synchronization

Clocks on the controllers and the units that are under the control of the main system controller are synchronized once a day (applicable only to the ones that support this function).

*1 The item and range that can be operated or monitored depend on the unit model.

WT07417X01

13

5. System configuration

5-1. System restrictions

The software version of the AE-200, AE-50, and EW-50 units in a system must be the same. For details about how

to update the software, refer to section 11-3 “Software update”.

The restrictions vary, depending on the number of the controlled units, model of the connected units, and the functions in use.

5-1-1. When not using an apportioned electricity billing function

Note: AE-200 is required when using AE-50.

(1) Controlling 50 or fewer units of equipment

1. AE-200 2. EW-50

EW-50

AE-200 City Multi system

Indoor unit

City Multi system

Indoor unit

M-NET M-NET

Outdoor unit Outdoor unit

Remote controller

Remote controller

(2) Controlling more than 50 units of equipment (with connection to an AE-200 controller)

M-NET

City Multi system

Indoor unit

AE-200

HUB

AE-50

Outdoor unit

M-NET

Remote controller

EW-50

M-NET

M-NET

5-1-2. When using an apportioned electricity billing function

Note: AE-200 is required to use a billing function.

Note: AE-200 M-NET cannot be used when a billing function is used.

Note: “Charge” license is required to use a billing function.

M-NET

AE-200

HUB

AE-50

M-NET

M-NET

Outdoor unit

EW-50

M-NET

M-NET

City Multi system

Indoor unit

Remote controller

WT07417X01

14

5-2. M-NET power feeding coefficient

The EW-50’s power feeding coefficient is 1.5.

A power supply unit is not required when the power consumption coefficient of the M-NET equipment (e.g. system controller, PI controller) that will be connected to the centralized control transmission cables is 1.5 or below.

Power feeding coefficient

Product

EW-50

Power supply unit (PAC-SC51KUA)

Power feeding coefficient

1.5

5

Power consumption coefficient

Product

DIDO controller (PAC-YG66DCA)

PI controller (PAC-YG60MCA)

AI controller (PAC-YG63MCA)

System controller

(North America: TC-24B, Europe: AT-50B)

ON/OFF remote controller (PAC-YT40ANRA)

Power consumption coefficient

1/4

1/4

1/4

1.5

1

Use a power supply unit and connect the M-NET power jumper as shown in the table below, depending on the system configuration and the power consumption coefficient of the M-NET equipment that will be connected to the centralized control transmission cables.

System with connection to a sub system controller or other related equipment

Power consumption coefficient ≤ 1.5

Power consumption coefficient > 1.5

Power supply unit

Not required

Required

M-NET power jumper (CN21)

Connect

(Connected at factory shipment)

Disconnect

* Leave the M-NET power jumper connected to CN41 on all outdoor units.

* Provide a single point ground for the shield of the centralized control transmission cable. (Provide the appropriate grounding according to

local standards.) Refer to section 7-2-2 “M-NET transmission cables (Centralized control transmission cables)” for details.

* Set the centralized control switch (SW5-1 (or SW2-1, depending on the unit model)) on the outdoor unit connected to the M-NET transmission cable to ON.

* Refer to section 2-1 “Part names” for the location of CN21.

WT07417X01

15

5-3. System configuration example

Note

● The figures in (1) through (3) below only show the transmission cable connections. Power cables are omitted.

(1) When the power consumption coefficient of the M-NET equipment that will be connected to the centralized control transmission cables is 1.5 or below

LAN

M-NET

EW-50

[000]

*1

Outdoor unit (Y)

*2

[051]

TB7 TB3

MA

ME

AHC

Indoor unit

Local remote controller (MA R/C type)

Local remote controller (ME R/C type)

Sub system controller

Advanced HVAC CONTROLLER

Group 1 Group 2

M-NET transmission cable

MA remote controller cable

LAN cable

Numbers in parentheses indicate address numbers.

[001] [002] [003] [004] [005]

MA

MA

M-NET

Outdoor unit (R2)

*2

[056]

TB7 TB3

BC controller

[057]

[006]

ME

[106]

[007]

[201]

Mr. Slim outdoor unit

*3

Group 3

[008]

Mr. Slim outdoor unit

*3

[009]

AHC [201]

LOSSNAY

[010]

[11]

M-NET adapter

[12]

MA

Group 4

MA

Group 5

*1 Leave the M-NET power jumper connected to CN21 on the EW-50.

*2 Leave the M-NET power jumper connected to CN41 on all outdoor units.

*3 An M-NET adapter (sold separately) is required to connect the Mr. Slim model of units to the M-NET.

WT07417X01

16

(2) When the power consumption coefficient of the M-NET equipment that will be connected to the centralized control transmission cables is greater than 1.5

Example: When two system controllers (North America: TC-24B, Europe: AT-50B) (power consumption coefficient: 1.5 each) are connected, the power consumption coefficient is 3. In this case, use a power supply unit.

EW-50

[000]

*1

Indoor unit

Power supply unit

PAC-SC51KUA

(sold separately)

LAN

MA

ME

Local remote controller (MA R/C type)

Local remote controller (ME R/C type)

M-NET transmission cable

MA remote controller cable

LAN cable

Sub system controller

Numbers in parentheses indicate address numbers.

M-NET

AHC

Advanced HVAC CONTROLLER

M-NET

Outdoor unit (Y)

*2

[051]

TB7 TB3

Group 1 Group 2

[001] [002] [003] [004] [005]

MA

M-NET

MA

Outdoor unit (R2)

*2

[056]

TB7 TB3

BC controller

[057]

[006]

ME [106]

[007]

Group 3

[008] [009]

AHC [201]

LOSSNAY

[010]

[201]

[202]

Mr. Slim outdoor unit

*3

[11]

M-NET adapter

Mr. Slim outdoor unit

*3

[12]

MA

Group 4

MA

Group 5

*1 Disconnect the M-NET power jumper (CN21) from the EW-50.

*2 Leave the M-NET power jumper connected to CN41 on all outdoor units.

*3 An M-NET adapter (sold separately) is required to connect the Mr. Slim model of units to the M-NET.

WT07417X01

17

(3) When connecting AE-50/EW-50 controllers (up to four controllers) to an AE-200

1. When not using an apportioned electricity billing function

Indoor unit

AE-200

*1

LAN1 IP: 192.168.1.001

[000]

M-NET

Outdoor unit (Y)

[051]

*2

TB7 TB3

Group 1

ME

AHC

Local remote controller (ME R/C type)

Advanced HVAC CONTROLLER

M-NET transmission cable

LAN cable

Numbers in parentheses indicate address numbers.

Group 2

[001] [002] [003] [004] [005]

ME

[101]

ME

[103]

LAN

Switching

HUB

LAN

Outdoor unit (R2)

[056]

*2

TB7 TB3

BC controller

[057]

[006]

ME

[106]

[007]

Group 3

[008] [009]

AHC [201]

LOSSNAY

[010]

AE-50

*1

LAN1 IP: 192.168.1.211

[000]

M-NET

Outdoor unit

[051]

*2

TB7 TB3

Group 1

[001]

ME

[101]

[002]

LAN

EW-50

*1

LAN1 IP: 192.168.1.212

[000]

M-NET

Outdoor unit

[051]

*2

TB7 TB3

Group 1

[001]

ME

[101]

[002]

LAN

EW-50

*1

LAN1 IP: 192.168.1.213

[000]

M-NET

Outdoor unit

[051] *2

TB7 TB3

Group 1

[001]

ME

[101]

[002]

*1 Leave the M-NET power jumper connected to CN21 on the AE-200 and EW-50.

*2 Leave the M-NET power jumper connected to CN41 on all outdoor units.

Group 2

[003]

ME

[103]

[004]

LOSSNAY

[005]

Group 2

[003]

ME

[103]

[004]

LOSSNAY

[005]

Group 2

[003]

ME

[103]

[004]

LOSSNAY

[005]

WT07417X01

18

2. When using an apportioned electricity billing function *1*2*3

AE-200

*4

LAN1 IP: 192.168.1.001

[000]

Outdoor unit

[051]

TB7 TB3

M-NET

[001]

ME

[101]

[002] [003]

ME

[103]

[004]

ME

AHC

Indoor unit

Local remote controller (ME R/C type)

Advanced HVAC CONTROLLER

M-NET transmission cable

LAN cable

Pulse signal

Numbers in parentheses indicate address numbers.

LAN

*5

Watt-hour meter

EW-50

LAN1 IP: 192.168.1.211

[000]

Switching

HUB

LAN

*6

Outdoor unit

*7

[051]

TB7 TB3

M-NET

Group 1

[001] [002]

ME

[101]

Group 2

[003]

ME

[103]

[004]

AHC [201]

Watt-hour meter

*8

LAN

EW-50

LAN1 IP: 192.168.1.212

[000]

*6

PI controller

[005]

Outdoor unit

*7

[051]

TB7 TB3

M-NET

[001]

Group 1

[002]

ME

[101]

Group 2

[003]

ME

[103]

[004]

Watt-hour meter

*8

LAN

EW-50

LAN1 IP: 192.168.1.213

[000]

*6

PI controller

[005]

Outdoor unit

*7

[051]

TB7 TB3

M-NET

Group 1

[001] [002]

ME

[101]

Group 2

[003]

ME

[103]

[004]

Watt-hour meter

*8

LAN

PI controller

[005]

EW-50

LAN1 IP: 192.168.1.214

[000]

*6

M-NET

Outdoor unit

*7

[051]

TB7 TB3

[001]

Group 1

[002]

ME

[101]

Watt-hour meter

Group 2

[003]

ME

[103]

[004]

*1 “Charge” license is required to use a billing function.

*2 AE-200 is required to use a billing function.

*3 Even when a billing function is not used, this system configuration can be used to extend the distance (the length of centralized control transmission cables) between the AE-200 and the air conditioning units.

*4 No air conditioning units can be connected to the AE-200 M-NET system when a billing function is used.

*5 A built-in PI controller on the AE-200 cannot be used for a billing function.

*6 A power supply unit may be required, depending on the system configuration.

*7 Leave the M-NET power jumper connected to CN41 on all outdoor units.

*8 Using a PI controller (PAC-YG60MCA) is recommended instead of a built-in PI controller on the AE-50/EW-50 when using a billing function.

(Discrepancies may occur between the built-in PI controller reading and the actual electric energy because the pulse input cannot be obtained during the AE-50/EW-50 power failure, shutoff process, and software update.)

WT07417X01

19

5-4. Number of connectable units

The table below summarizes the number of connectable units in an AE-200/AE-50/EW-50 M-NET system.

Unit type Number of connectable units

Indoor units, independent OA processing units, LOSSNAY units,

DIDO controllers (PAC-YG66DCA), Air To Water (PWFY) units,

Advanced HVAC CONTROLLERs, HWHP (CAHV, CRHV) units, AI controllers (PAC-YG63MCA), PI controllers (PAC-YG60MCA)

Up to 50 units (including the interlocked LOSSNAY units) *1*2*3

Indoor units, independent OA processing units, LOSSNAY units,

DIDO controllers (PAC-YG66DCA), Air To Water (PWFY) units,

HWHP (CAHV, CRHV) units in a group

Remote controllers in a group

System controllers in a group (EW-50 excluded)

1–16 units

(Indoor units, independent OA processing units,

LOSSNAY units, DIDO controllers (PAC-YG66DCA),

Air To Water (PWFY) units, and HWHP (CAHV,

CRHV) units cannot be combined in one group.)

0–2 units

0–4 units (Up to four remote and system controllers combined can be assigned to each group.)

0–1 unit

1 unit

Advanced HVAC CONTROLLER in a group

LOSSNAY unit that can be interlocked with each indoor unit

Indoor units that can be interlocked with each LOSSNAY unit 1–16 units

*1 The maximum number of controllable units varies, depending on the number of channels used for the DIDO controller. In a system with connection to Advanced HVAC CONTROLLERs, the number of connectable units is 60 units when using the monitoring function on the

Maintenance Tool, and 70 units when not using the monitoring function on the Maintenance Tool.

*2 Each contact of DIDO controller (PAC-YG66DCA) counts as one unit.

*3 Although the maximum settable total number of built-in PI controllers and PI controllers (PAC-YG60MCA) for each AE-200/AE-50/EW-50 is

15, the number of them in a system with connection to one or more AE-50/EW-50 controllers must be 20 or less. (Each built-in PI controller counts as one unit.)

WT07417X01

20

5-5. Setting M-NET address for various devices

Designate the address for each M-NET device. The addresses cannot be overlapped within the same M-NET system.

M-NET address

Indoor unit

Outdoor unit

Auxiliary outdoor unit

(BC controller etc.)

OA processing unit/

LOSSNAY unit

Air To Water (PWFY) unit

HWHP

(CAHV) unit

Main Box

Sub Box

Mr. Slim/M- and P-Series outdoor unit

Room air conditioner

M-NET remote controller

MA remote controller

Sub system controller

Advanced HVAC

CONTROLLER

DIDO controller

(PAC-YG66DCA)

PI controller

(PAC-YG60MCA)

AI controller

(PAC-YG63MCA)

Address setting method

Assign the lowest address to the main indoor unit in the group, and assign sequential addresses to the rest of the indoor units in the same group.

Assign an address that equals the lowest indoor unit address in the same refrigerant system plus 50.

Assign an address that equals the address of the outdoor unit in the same refrigerant system plus 1.

Assign an arbitrary but unused address to each of these units after assigning an address to all indoor units.

Assign the lowest address to the main Air To Water (PWFY) unit in the group, and assign sequential addresses to the rest of the Air To

Water (PWFY) units in the same group.

Assign the lowest address to the main unit in the Main Box in the group, and assign sequential addresses to the sub units in the same Main Box.

Assign addresses that equal the addresses of the main and sub units in the Main Box plus 50 to the units in the Sub Box.

Make the settings in the same way as with the indoor units.

Requires PAC-SF81MA-E/PAC-SF82MA-E (sold separately).

Make the settings in the same way as with the indoor units.

Requires MAC-333IF-E/MAC-399IF-E (sold separately).

Assign an address that equals the address of the main indoor unit with the lowest address in the group plus 100. Add 150 instead of

100 to set the address for a sub remote controller.

Address setting is not required.

Connection of two remote controllers requires the Main/Sub setting for each controller to be made.

Assign an address that equals the group number of the smallest controlled group plus 200.

Assign an address that equals the address of the main indoor unit with the lowest address in the group plus 200.

If the address overlaps with the Sub system controller’s address, assign an arbitrary but unused address between 201 and 250 to the

Advanced HVAC CONTROLLER.

Assign an arbitrary but unused address to the controller after completing the address setting for the units with an address between 1 and 50. The number of controllable units varies with the number of channels used.

Assign an arbitrary but unused address to the controller after completing the address setting for the units with an address between 1 and 50.

Assign an arbitrary but unused address to the controller after completing the address setting for the units with an address between 1 and 50.

1–50

51–100

52–100

1–50

1–50

1–50

51–100

1–50

1–50

101–200

201–250

201–250

1–50

1–50

1–50

WT07417X01

21

[Main and Sub system controllers (M-NET)]

Each group can be controlled by a Main system controller or a Sub system controller.

EW-50 (AE-200/AE-50) is exclusively for use as a Main system controller and cannot be used as a Sub system controller.

Main system controller

Main system controller refers to a system controller that controls all other system controllers including the units they control. If a given system has only one system controller, that controller becomes a Main system controller.

Group settings and interlock settings can be made only from a Main system controller.

Sub system controller

Sub system controller refers to a system controller that is controlled by a Main system controller.

Main system controller's (EW-50 or

AE-200/AE-50’s) control range

Sub system controller's control range

Group Group Group

The system cannot be configured as shown in the examples below.

● Groups that are not under the control of a Main system controller cannot be controlled from a Sub system controller.

Main system controller

Sub system controller

Group Group Group

● Each group cannot be placed under the control of two or more Main system controllers.

Main system controller 1

Main system controller 2

Group Group Group

● Sub system controllers cannot be placed under the control of two or more Main system controllers.

Main system controller 1

Sub system controller

Main system controller 2

Group Group Group Group

WT07417X01

22

6. Installation

Test runs, inspection, and service must be performed by qualified personnel in accordance with this manual. Incorrect use may result in injury, electric shock, malfunction, or fire.

Do not install the controller where there is a risk of flammable gas leaks. If flammable gas accumulates around the controller, it may ignite and cause a fire or explosion.

Take appropriate safety measures against earthquakes to prevent the controller from causing injury.

To prevent injury, install the controller on a flat surface strong enough to support its weight.

To reduce the risk of short circuits, current leakage, electric shock, malfunction, smoke, or fire, do not install the controller in a place exposed to water or in a condensing environment.

WT07417X01

23

6-1. Items not included

The following items are required to install the EW-50.

Items not included

Locknuts and bushing

Sleeved ring terminal

AC power cable/Protective ground wire

Transmission cable

Relay (for external input)

Relay (for external output)

Electrical wire for pulse input

Specifications

Must be suitable for the conduit tube to be used.

M3.5 ring terminal (for AC power cables (L/L1, N/L2) and M-NET transmission cables (A, B,

S))

M4 ring terminal (for protective ground wire)

Type: Sheathed cable (should not be lighter than ordinary sheathed cable IEC 60227.)

(designation 60227 IEC 53) *1

Recommended type: VCT, VVF, VVR, or its equivalent

Size: 0.75 to 2.00 mm² (ø1.0 to ø1.6 mm), AWG 18 to 14

Protective ground wire color: green/yellow

* Use a wire with an appropriate diameter so that the wire can be fixed with the cable tie below the terminal block. A diameter of 10 mm (25/64 in) is recommended.

Type: Shielded cable

● CPEVS ø1.2 to ø1.6 mm

● CVVS 1.25 to 2 mm²

* CPEVS: PE *2 insulated PVC *2 jacketed shielded communication cable

* CVVS: PVC *2 insulated PVC *2 jacketed shielded control cable

Contact rating

Rated voltage: 12 or 24 VDC

Rated current: 0.1 A or above

Minimum applied load: DC 1 mA

Operation coil

Rated voltage: 12 or 24 VDC

Power consumption: Max. 0.9 W

Type: Copper wire that is suitable for the terminal block of the EW-50

Size

● Single wire: ø0.65 to ø1.2 mm, AWG 21 to 16

● Twisted wire: 0.75 to 1.25 mm², AWG 18 to 16

Must output dry voltage contact pulse for each unit pulse.

Output pulse type: Semiconductor relay

Pulse width: 100 to 300 ms (Resting interval: Min. 100 ms)

Min. 100 ms

Watt-hour meter

100 to 300 ms

LAN cable

Switching HUB

Overcurrent breaker (fuse or circuit breaker)

Earth leakage breaker

PC

Fuse

Circuit breaker

Output pulse unit: 0.1/1.0/10/100 kWh/pulse

* An output pulse unit of 1 kWh/pulse or below is recommended.

Category 5 or above straight cable (Max. 100 m (328 ft))

A communication speed of 100 Mbps or faster is recommended.

Rated current: 3 A

* When using a fuse, use it in combination with a switch (rated current: 3 A).

Type: Bipolar (2P2E)

Contact distance: Min. 3 mm (1/8 in)

Rated current: 3 A

Type: Bipolar (2P2E)

Contact distance: Min. 3 mm (1/8 in)

Rated current: 3 A

Rated current sensitivity: 30 mA

Operation time: Max. 0.1 sec

Refer to the Web browser instruction books (separate volume) for PC requirements.

*1 For the U.S. and Canada: designation NEC (NEPA70) or CEC

*2 PE: Polyethylene, PVC: Polyvinyl chloride

6-2. Items sold separately

Items sold separately

External input/output adapter

Model name

PAC-YG10HA-E

Remarks

Required when using the external input/output function

WT07417X01

24

6-3. M-NET transmission cable length

Observe the maximum total length of M-NET transmission cables to ensure proper signal transmission to and from the connected equipment over the M-NET transmission cables. If the maximum total length is exceeded, the M-NET signals will be attenuated, resulting in communication error and control failure.

● Maximum total length of M-NET transmission cables: 500 m (1640 ft)

● Maximum total length of power feed: 200 m (656 ft)

<Example>

Centralized control transmission cables

Centralized controller

EW-50 a

Outdoor unit

Indoor-outdoor transmission cables

c d

Indoor unit Indoor unit b

Indoor unit

Outdoor unit f e

10 m (32 ft)

M-NET remote controller

Indoor unit Indoor unit

(1) Maximum total length of M-NET transmission cables

a + c + d (e)

a + b + f

≤ 500 m (1640 ft)

≤ 500 m (1640 ft)

d (e) + c + b + f ≤ 500 m (1640 ft)

(2) Maximum total length of power feed for the indoor-outdoor transmission cables

f ≤ 200 m (656 ft)

c + d (e) ≤ 200 m (656 ft)

(3) Maximum total length of power feed for the centralized control transmission cables

a ≤ 200 m (656 ft)

a + b ≤ 200 m (656 ft)

Note

● The M-NET remote controller cable length should be 10 m (32 ft) or shorter. The length that exceeds 10 m (32 ft) needs to be included in the maximum total length of M-NET transmission cables (500 m (1640 ft)) and in the maximum total length of the power feed (200 m (656 ft)).

● If the M-NET remote controller cable is shorter than 10 m (32 ft), the length does not need to be included in the maximum total length.

WT07417X01

25

6-4. Installation space

The EW-50 must be installed inside the metal control box.

Either the supplied L-fittings or DIN rail attachments can be used for the installation.

Leave a space around the EW-50 as shown in the figure below.

50 (2) 50 (2) 50 (2) 50 (2) 50 (2)

50 (2)

DIN rail

150 (6)

DIN rail

100 (4)

When using L-fittings When using DIN rail

50 (2)

Unit: mm (in)

50 (2)

150 (6)

100 (4)

WT07417X01

26

6-5. Installation procedures

Note

● Connect the necessary cables and wires before installing EW-50, referring to chapters 7 and 10.

● Do not install the unit where the unit may continuously receive vibration. The continuous vibration may cause the connectors to disconnect.

6-5-1. Method 1: Installation using L-fittings

1. Have a metal control box ready.

2. Cut screw holes on the surface on which the EW-50 will be installed as shown in the figure below, taking into consideration the installation space.

3. Attach the supplied two L-fittings to the EW-50 with the supplied roundhead screws (M3 × 6).

4. Properly install the EW-50 with the M4 screws (not supplied) inside the metal control box as shown in the figure below.

① Temporarily tighten the top M4 screws.

② Temporarily place the M4 screws through the screw holes at the top of the L-fitting.

③ Tighten the bottom M4 screws.

④ Tighten the top M4 screws.

Unit: mm (in)

100 (4)

M4 screw

(not supplied)

Roundhead screw

(M3 × 6)

(supplied)

L-fitting

(supplied)

240

(9-8/16)

①④

EW-50

M4

Inside the metal control box

Note

● The EW-50 to which the L-fittings are attached must be fixed to the metal control box with total of four M4 screws to prevent it from falling.

● The surface on which the EW-50 will be installed needs to be strong enough to support its weight (1.7 kg (4 lbs) each).

WT07417X01

27

6-5-2. Method 2: Installation using DIN rail

1. Have a metal control box ready.

2. Attach the supplied two DIN rail attachments to the EW-50 with the supplied roundhead screws (M3 × 12).

3. Attach the supplied DIN rail auxiliary bracket to the EW-50 with the supplied roundhead screws (M3 × 6).

EW-50

DIN rail attachment

(supplied)

Roundhead screw (M3 × 12)

(supplied)

DIN rail auxiliary bracket

(supplied)

Roundhead screw (M3 × 6)

(supplied)

4. Mount the DIN rail (not supplied) to the metal control box.

* Use a DIN rail of 35 mm (1-7/16 in) width.

Unit: mm (in)

Max. 200 (7-14/16)

Note

● To secure the strength, the screw pitch must be 200 mm (7-7/8 in) or less when DIN rail is mounted to the metal control box.

● The surface on which the EW-50 will be installed needs to be strong enough to support its weight (1.7 kg (4 lbs) each).

● Do not install the EW-50 where it may receive vibration.

● To avoid the contact of the DIN rail fixing screws with the DIN rail attachment, do not tighten the fixing screws at the shaded areas in the figure below.

Do not tighten the fixing screw here.

WT07417X01

28

[Mounting/removing the EW-50 on/from the DIN rail]

(1) Mounting

1. Hook the upper side of the attachments to the DIN rail.

2. Push the lower part of the EW-50 until it snaps into place.

Note

● Ensure that the DIN rail attachments are fixed securely in place to the DIN rail.

(2) Removing

1. Pull the lower part of the EW-50 toward you.

2. Remove the EW-50 from the DIN rail.

Mounting

Removing

WT07417X01

29

7. Wiring connections

To reduce the risk of malfunction, smoke, fire, or damage to the controller, do not connect the power cable to the signal terminal block.

To reduce the risk of injury or electric shock, switch off the main power before performing electrical work.

Electrical work must be performed by qualified personnel in accordance with local regulations and the instructions provided in this manual. Only use specified cables and dedicated circuits. Inadequate power source capacity or improper electrical work will result in electric shock, malfunction, or fire.

To reduce the risk of electric shock, install an overcurrent breaker and an earth leakage breaker on the power supply. To reduce the risk of electric shock, smoke, or fire, install an overcurrent breaker for each controller.

Proper grounding must be provided by qualified personnel. Do not connect the protective ground wire to a gas pipe, water pipe, lightning rod, or telephone wire. Improper grounding may result in electric shock, smoke, fire, or malfunction due to electrical noise interference.

To avoid malfunction, do not bundle power cables and signal cables together or place them in the same metallic conduit.

7-1. Removing/reinstalling the service cover

(1) Removing

1. Unscrew the two fixing screws on the service cover.

2. Remove the service cover.

Service cover

Openings on the EW-50

Fixing screws

Hooks on the service cover

WT07417X01

30

(2) Reinstalling

1. Insert the AC power cables and M-NET transmission cables into the openings, and then insert the hooks to the openings.

Note: Do not pinch the cables between the EW-50 body and the service cover.

2. Screw down the service panel with the two fixing screws.

3. Check that there are no pinched cables between the EW-50 body and the service cover.

Opening for M-NET transmission cables

Opening for AC power cables

Do not pinch the cables between the

EW-50 body and the service cover.

WT07417X01

31

7-2. Connecting AC power cables and M-NET transmission cables

EW-50

Outdoor unit

TB7

M-NET transmission cables for centralized control

Overcurrent breaker

Earth leakage breaker

100–240 VAC

AC power cables

7-2-1. AC power cables and protective ground wire

1. Attach M3.5 sleeved ring terminals to the AC power cables, and attach an M4.0 sleeved ring terminal to the protective ground wire.

2. Connect the AC power cables to the power supply terminal block, and connect the protective ground wire to the ground terminal.

Note: Thread the protective ground wire through the guides to prevent the wire from moving when it is retightened to the ground terminal.

3. Fix the cables in place with the supplied cable tie.

45 mm

(1-13/16 in) or less

Protective ground wire

AC power cable

Cable tie (supplied)

Sheath

100–240 VAC

Guide

Guide

Note

● Make the protective ground wire 25 mm (1 in) longer than the AC power cables (L/L1, N/L2).

● Tighten the terminal screws to a torque of 1.0 to 1.3 N•m.

● Properly fix the cable sheaths in place with the supplied cable ties. The distance between the sheath end and the ring terminal must be 45 mm (1-13/16 in) or less.

Cable tie (supplied)

Cable sheath

WT07417X01

32

7-2-2. M-NET transmission cables (Centralized control transmission cables)

1. Attach M3.5 sleeved ring terminals to the M-NET transmission cables (A, B, Shield).

2. Connect the M-NET transmission cables to the M-NET terminal block.

3. Fix the cables in place with the supplied cable tie.

4. When the power is supplied from the unit other than the EW-50, disconnect the M-NET power jumper from CN21. (Refer to

section 2-1 “Part names” for the location of CN21.)

CN21

M-NET transmission cables A and B

45 mm (1-13/16 in) or less

Sheath

M-NET transmission cable S (Shield)

Cable tie (supplied)

To outdoor unit

Note

● Provide a single point ground for the shield of the centralized control transmission cable. (Provide the appropriate grounding according to local standards.)

● When leaving the M-NET power jumper connected to CN21 on the AE-200/AE-50/EW-50, the M-NET S (shield) terminal of

TB3 is connected to the ground terminal block on the unit, and the ground is supplied via the protective ground wire.

● When disconnecting the M-NET power jumper from CN21 on the AE-200/AE-50/EW-50, provide a ground point at a power supply unit (PAC-SC51KUA).

● Tighten the terminal screws to a torque of 1.0 to 1.3 N•m.

● Properly fix the cable sheaths in place with the supplied cable ties. The distance between the sheath end and the ring terminal must be 45 mm (1-13/16 in) or less.

Cable tie (supplied)

Cable sheath

WT07417X01

33

7-3. Connecting the LAN cable

To prevent unauthorized access, always use a security device such as a VPN router when connecting to the Internet.

Connect the LAN cable to the LAN1 port on the EW-50. (The LAN2 port is unused.)

● The LAN cable is not supplied. Use a category 5 or above straight LAN cable.

● Use a switching HUB compatible with 100 BASE.

● The maximum distance between the switching HUB and AE-200/AE-50/EW-50 is 100 m (328 ft).

● The recommended number of connected devices such as gateway, router, layer 3 switch, or HUB between the

AE-200/AE-50/EW-50 is four or less. (Transmission round-trip delay time must not exceed one second. If the transmission

delay time is long, a communication error may be detected. Check the transmission delay time, referring to section 7-4.)

LAN1

LAN2 (Unused)

Note

● LAN must be installed before the unit installation. Route the LAN cable to the EW-50 in the same way as the M-NET transmission cables.

● When connecting the EW-50 to an existing LAN, consult the system administrator to decide the IP address.

7-4. Confirming the LAN transmission delay time

Connect a monitoring PC to a device such as HUB that is connected to the AE-200/AE-50/EW-50. Send a command from the PC to the AE-50/EW-50, and receive the response from the AE-50/EW-50. Check the time between sending and receiving on the PC display.

(1) Sample system connection

AE-200

EW-50

Switching HUB

Max.

100 m (328 ft)

Monitoring PC

Max.

100 m (328 ft)

Max. 100 m (328 ft)

WT07417X01

34

(2) Checking the transmission delay time

① Click [Start]>[Program]>[Accessories]>[Command Prompt] on the monitoring PC.

② Enter [ping (IP address of AE-200/AE-50/EW-50)], and press the Enter button.

([ping -w 1000 192.168.1.1] is entered on the sample screen below.)

③ Check that the transmission delay time that appears on the screen is 1000 ms or below.

(The transmission delay time is “Maximum = 1 ms” on the sample screen below, which is normal.)

If [Request timed out] appears or the displayed transmission delay time exceeds 1000 ms, consult the network administrator for how to decrease the number of gateway, router, layer 3 switch, or HUB or how to change the network.

Note

● The IP address of the monitoring PC should not overlap any of the addresses that are assigned to the

AE-200/AE-50/EW-50. (Refer to the Instruction Book (Web Browser for Initial Settings) for how to set the IP address of the PC.)

● When connecting to an existing LAN system, which does not use a dedicated LAN, consult the network administrator to obtain the permission to connect the monitoring PC and the temporary IP address for the PC.

Enter [ping -w 1000 192.168.1.1], and press the Enter button.

Check the transmission delay time.

The time should be 1000 ms or below.

If [Request timed out] appears, check the

LAN connection status and IP address.

WT07417X01

35

8. Initial settings

Initial settings need to be made for each EW-50 on the Web browser.

Details about the initial settings and other settings and operations are covered in the Instruction Books (Web

Browser for Initial Settings, Web Browser for System Maintenance Engineer).

8-1. Logging in to the Web Browser for Initial Settings

(1) Enter the web page address in the address field of the Web browser as follows:

http://[IP address of EW-50]/init/administrator.html

Press the [Enter] key. A login screen will appear.

Note: If the IP address of the EW-50 is [192.168.1.1], the web page address is [http://192.168.1.1/init/administrator.

html].

Note: The web page will be displayed in the same language as the operating system on the PC.

The web page can be displayed in other languages by entering the web page address as follows:

Chinese

English

French

German

Italian http://[IP address of EW-50]/init/ zh/administrator.html

http://[IP address of EW-50]/init/ en/administrator.html

http://[IP address of EW-50]/init/ fr/administrator.html

http://[IP address of EW-50]/init/ de/administrator.html

Japanese

Spanish http://[IP address of EW-50]/init/ it/administrator.html

Portuguese http://[IP address of EW-50]/init/ pt/administrator.html

Russian http://[IP address of EW-50]/init/ http://[IP address of EW-50]/init/

ja/administrator.html

ru/administrator.html

http://[IP address of EW-50]/init/ es/administrator.html

(2) Enter the following default maintenance user name and password in the login screen.

Default user name Default password initial init

8-2. Initial settings on the Web browser

Note: Initial settings for a system with connection to an AE-200 controller differ from those in a system without it. Refer to the Instruction Book (Web Browser for Initial Settings) for details.

Settings

Date and Time

Basic System

[Default network settings]

IP address: 192.168.1.1

Subnet mask: 255.255.255.0

Gateway: 0.0.0.0

Groups

Interlocked LOSSNAY

Blocks

Functions

User Settings

Utility

License registration

Current date/time, daylight saving time

Details

Unit Settings, Network Settings (IP address*, Subnet mask, Gateway), Display format, System Configuration Settings (M-NET Settings, External Input Setting,

Time Master/Sub)

* When connecting the EW-50 to an existing LAN, consult the system administrator to decide the IP address.

Group name, unit registration

Interlocked unit registration

Block name, group registration

E-Mail, Peak Cut, Measurement, Set Temperature Range Limit, Night Mode

Schedule, System-changeover, External Temperature Interlock, Night Setback

Control, Interlock control, Energy Management Settings, AHC Port Name Settings

Maintenance User, Building Manager

Back up/import settings data

License registration for optional functions

WT07417X01

36

8-3. Quick IP address setting

When connecting an EW-50 to a dedicated LAN system, IP address of the EW-50 can be easily set to an address between 192.168.1.1 and 192.168.1.15 with rotary switch SW1.

When the IP address cannot be set with rotary switch SW1 (e.g., when connecting an EW-50 to an existing LAN, when the EW-50 is used as an expansion controller of AE-200), set the IP address on the Web browser for Initial

Settings.

Set SW1 before turning on the power.

B

D

E

F

9A

0 1 2

4

3

5

78

6

SW1

D

E

F

B

C

9

A

7

8

5

6

3

4

1

2

SW1

0

* The arrow on the rotary switch indicates the current setting of the switch. Point the arrow at the desired number.

* To set the address, turn the rotary switch with a precision slotted screwdriver [2.0 mm (2/16 in) (width)] to a torque of less than 19.6 N•m.

IP address (LAN1)

Default

192.168.1.1

192.168.1.1

192.168.1.2

192.168.1.3

192.168.1.4

192.168.1.5

192.168.1.6

192.168.1.7

192.168.1.8

192.168.1.9

192.168.1.10

192.168.1.11

192.168.1.12

192.168.1.13

192.168.1.14

192.168.1.15

Subnet mask

Default

255.255.255.0

255.255.255.0

Gateway

Default

0.0.0.0

0.0.0.0

Note

● If you forget the EW-50 IP address, check the IP address that has been entered on the monitoring PC (Web browser or

TG-2000A).

● If you forget the EW-50 IP address, you can start EW-50 by changing the SW1 setting and temporarily using a certain IP address (between 192.168.1.1 and 192.168.1.15). The IP address can be changed to an arbitrary IP address by setting the IP address on the Web Browser for Initial Settings, setting the SW1 back to “0”, and rebooting the EW-50. (It is recommended to paste a label with the IP address on the EW-50, so that the IP address is available at all times.)

WT07417X01

37

8-4. Network settings on the Web browser

IP, subnet mask, and gateway addresses can be set on the Web browser. Rotary switch SW1 must be set to “0”

(default setting) to make these settings.

When connecting the EW-50 to an existing LAN, consult the system administrator to decide the IP, subnet mask, and gateway addresses.

Refer to the Instruction Book (Web Browser for Initial Settings) for how to make these settings.

WT07417X01

38

9. Test run

9-1. Collective operation ON/OFF

Confirm that the group settings and interlock settings are complete before performing a test run.

It may take approximately five minutes from power on until the local remote controllers become operable.

Refer to the indoor unit Installation Manual for details about a test run.

Note: Perform a test run in the presence of a customer.

Test run procedure

(1) Turn on the power to the EW-50 and all units.

(2) Make sure that the Power LED on the EW-50 is lit.

(3) Log in to the Web Browser for System Maintenance Engineer, and then open the [Monitor/Operation] screen.

* Click [Update] to show the most recent operation conditions.

(4) On the [Monitor/Operation] screen, click [Batch Operations], click [ON], and then click [OK]. The group of units will start an operation.

(5) On the [Monitor/Operation] screen, check the unit icons to see if the units are in operation.

(6) Check for the proper operation of each unit during the test run (e.g., check to see if cold (or warm) air comes out of the supply air outlet on each indoor unit).

(7) After confirming that all units are operating properly, click [Batch Operations] on the [Monitor/Operation] screen, click [OFF], and then click [OK] to stop the units.

WT07417X01

39

10. External input/output

10-1. External signal input/output function

To reduce the risk of injury, do not touch the burrs of the knockout holes.

To use external input/output, a separately-sold external input/output adapter (PAC-YG10HA-E) is required.

When connecting an external input/output adapter (PAC-YG10HA-E), cut out the CN5 knockout hole. (Refer to

section 2-1 “Part names” for the location of CN5.)

Note

● Connect the external input/output adapter to each AE-200/AE-50/EW-50. (External input signal to AE-200 cannot perform the collective operations (e.g., emergency stop) for AE-50/EW-50 systems.)

● Use caution not to damage the circuit board with tools when cutting out the knockout hole.

● Set the [External Input Setting] setting for each EW-50 on the [Network] screen on the Web browser for Initial Settings.

10-1-1. External signal input function

Using external contact signals (12 or 24 VDC), the following collective operations for all connected air conditioning units can be controlled: Demand level, Emergency stop, ON/OFF operation, and Prohibit/Permit local remote controller operation.

External input

M-NET

M-NET

External input

M-NET

External input

M-NET

External input

(1) External signal input function setting

Setting mode

[Demand (Level signal)/Not in use]

(Factory setting)

[Emergency Stop (Level signal)]

Description

Select this mode when inputting a demand level using a level signal, or when not using an external signal input function.

A demand signal of four different levels will be input.

Using a level signal, all the air conditioning units connected to the AE-200 or

AE-50/EW-50 will be stopped collectively in an emergency. During an emergency stop, the ON/OFF operation from the local remote controllers will be prohibited, and the ON/OFF operation and Prohibit/Permit settings on the AE-200 or AE-50/EW-50 will be prohibited.

A demand signal of three different levels will be input.

[ON/OFF (Level signal)]

[ON/OFF/Prohibit/Permit (Pulse signal)]

Using a level signal, all the air conditioning units connected to the AE-200 or

AE-50/EW-50 will be run or stopped collectively. The ON/OFF operation from the local remote controllers will be prohibited, and the ON/OFF operation and Prohibit/

Permit settings on the AE-200 or AE-50/EW-50 will be prohibited. Scheduled operations will not be performed.

Using a pulse signal, all the air conditioning units connected to the AE-200 or

AE-50/EW-50 will be run or stopped collectively, or the operation from the local remote controllers will be prohibited or permitted collectively.

* General equipment connected via a DIDO controller (PAC-YG66DCA) cannot be collectively run or stopped by using the external signal input function unless [Emergency Stop (Level signal)] is selected and relevant switches on the DIDO controller are set.

* The external input function cannot be used on HWHP (CAHV) units.

WT07417X01

40

(2) External signal input specifications

CN5

No. 9

No. 8

No. 7

No. 6

No. 5

Lead wire from

PAC-YG10HA-E

Red

Gray

Blue

Yellow

Orange

Demand

(Level signal)

Emergency Stop

(Level signal)

External power supply (+12 or +24 VDC)

Demand level 4 Demand level 4

Demand level 3

Demand level 2

Demand level 1

Demand level 3

Demand level 2

Emergency stop signal,

Normal operation signal

ON/OFF

(Level signal)

ON signal,

OFF signal

ON/OFF/Prohibit/Permit

(Pulse signal)

Permit signal

Prohibit signal

OFF signal

ON signal

(3) Level signal and pulse signal

(A) Level signal

Contact ON

Contact OFF

Normal

Emergency stop

Contact ON

Contact OFF

Normal

Stop

Run Stop

How the demand level is determined

Demand level signal specification: When higher levels’ contacts turn on, lower levels’ contacts also stay on.

CN5

No.8

No.7

No.6

No.5

Contact

ON

OFF

ON

OFF

ON

OFF

ON

OFF

*1

*1

*1

*1

Level 4

*1 Peak Cut control is performed when the demand level contact turns on. If two different demand levels’ contacts turn on at the same time, the

Peak Cut control will be performed with the higher level demand.

Level 3

Level 2

Level 1

Level 0

Demand level signal specification: Only the current levels’ contacts turn on.

CN5

No.8

No.7

No.6

No.5

Contact

ON

OFF

ON

OFF

ON

OFF

ON

OFF

*2

*2

*2

*2 The specification must be followed in the following order: ① When the level changes, the contact of the level after the change turns on.;

② The contact of the level before the change turns off.

Level 4

Level 3

Level 2

Level 1

Level 0

1. If [Emergency stop (Level signal)] is selected, the air conditioning units in normal operation will stop when the contact turns on. Even when the contact turns off, these units will remain stopped. They must be started up manually after the emergency stop is reset.

2. If [ON/OFF (Level signal)] is selected, the air conditioning units that are stopped will start operation when the contact turns on.

Conversely, the units that are in operation will stop when the contact turns off.

Note

● Even if the Peak Cut control is not performed due to unexpected problems, Mitsubishi Electric will not be responsible for exceeding the maximum power demand.

WT07417X01

41

(4) Pulse signal

(Example) ON/OFF (Example) Prohibit/Permit

0.5–1.0 second 0.5–1.0 second

(ON)

Contact ON

Contact OFF

(Prohibit)

Contact ON

Contact OFF

0.5–1.0 second 0.5–1.0 second

(OFF)

Contact ON

Contact OFF

Stop Run Stop

(Permit)

Contact ON

Contact OFF

Permit Prohibit Permit

1. If the input pulse signal is the same as the current operation status of the air conditioning units, no status change will occur. (For example, if an ON signal is input while the air conditioning units are in operation, the units will continue their operation.)

2. If the operation from the local remote controller is prohibited, ON/OFF status, operation mode, or temperature setting cannot be changed and filter sign cannot be reset from the local remote controller.

3. The pulse width (contact ON) should be between 0.5 and 1.0 second.

(5) Recommended circuit

(A) Level signal

CN5

9

8

7

6

5

1

Red

Gray

Blue

Yellow

Orange

Max.

100 m (328 ft) *2

External power supply *1 (12 or 24 VDC)

Y2

Y1

X2

X1

Y2

Y1

X2

X1

Use relays X1, X2, Y1, and Y2 that meet the following specifications.

Demand level 4

Demand level 3

Demand level 2

ON/OFF or Emergency stop

Demand level 1

Contact rating

Rated voltage: 12 or 24 VDC

Rated current: 0.1 A or above

Minimum applied load: DC 1 mA

EW-50

(B) Pulse signal

CN5

9

8

7

6

5

EW-50

1

Red

Gray

Blue

Yellow

Orange

Max.

100 m (328 ft) *2

External power supply *1 (12 or 24 VDC)

Y2

Y1

X2

X1

X1 X2 Y1 Y2

ON

OFF

Prohibit

Permit

*1 Select an external power supply suitable for the relays used. (12 or 24 VDC)

Connect the external power supply in the correct polarity to input and output the signals.

Connect ⑤–⑧ (see the figure at left) to the negative side.

*2 Take sufficient precautions against noise when the cable length is long.

Important

Be sure to use an external power supply (12 or 24 VDC) to avoid malfunctions.

Connect the external power supply in the correct polarity to avoid malfunctions.

Note

● The relays, DC power supply, and extension cables are not supplied.

● The total length of the lead wire and extension cable should not exceed 100 m (328 ft). (Use an extension cable of 0.3 mm

2 or thicker.)

● Cut the excess cable near the connector, and insulate the end of the unused cable with tape.

WT07417X01

42

10-1-2. External signal output function

An ON signal is output when one or more units are in operation, and an Error signal is output when one or more units are in error. (Operation status (On/Error) of the units that are connected to each EW-50 will be output.)

External output

(collective)

*1

External output

EW-50

M-NET

HUB

External output

EW-50

M-NET

EW-50

External output

EW-50

M-NET

EW-50

EW-50

M-NET

M-NET

M-NET

*1 Operation status of the total management system under the control of AE-200 (including units that are connected to AE-50 and EW-50) can collectively be output.

(1) External signal output specifications

CN5

No. 3

No. 2

Lead wire from

PAC-YG10HA-E

Brown

Black

Signal

Error signal, Normal signal

ON signal*, OFF signal

No. 1 Green Common ground for external output (Ground for the external power supply)

* The operation status of general equipment (via a DIDO controller (PAC-YG66DCA)) will not be output.

* The ON signal will be output even during an error.

(2) Recommended circuit

Relay-driven circuit

CN5

9

Diode *2

4

3

2

Brown

Black

Z2

Z1

External power supply *1

Z1 L1

Use relays Z1 and Z2 that meet the following specifications.

Operation coil

Rated voltage: 12 or 24 VDC

Power consumption: Max. 0.9 W

Z2 L2

EW-50

1

Green

Max.

10 m (32 ft)

L1: ON indicator

L2: Error indicator

*1 Select an external power supply suitable for the relays used. (12 or

24 VDC)

Connect the external power supply in the correct polarity to input and output the signals.

Connect ① (shown in the figure at left) to the negative side.

*2 Use a diode at both ends of the relay coils.

Important

Be sure to use an external power supply (12 or 24 VDC) to avoid malfunctions.

Connect the external power supply in the correct polarity to avoid malfunctions.

Do not connect the external power supply without relays being connected to the controller (no load).

Note

● The relays, lamps, DC power supply, diodes, and extension cables are not supplied.

● The total length of the lead wire and extension cable should not exceed 10 m (32 ft). (Use an extension cable of 0.3 mm

2

or thicker.)

● Each element will turn on during operation and when an error occurs.

WT07417X01

43

10-2. Pulse signal input function

Using pulse signals directly input from metering device such as watt-hour meter, billing data and energy management data will be obtained based on the cumulative number of pulse signal input.

Note

● To input pulse signals directly from the metering device to the EW-50, use the connector connected to the EW-50. (A precision screwdriver for M1 screws is required.).

Usability of a built-in PI controller for each function

Function

Apportioned electricity billing function (option)

Energy management

Demand function (option)

AE-200 x

*1

V

V

AE-50

V

*2

V

V

EW-50

V

*2

V

V

(V): Usable, (x): Not usable

*1 A built-in PI controller on the AE-200 cannot be used for an apportioned electricity billing function. Use a built-in PI controller on the AE-50 or

EW-50.

*2 Using a PI controller (PAC-YG60MCA) is recommended instead of a built-in PI controller on the AE-50/EW-50 when using an apportioned electricity billing function. (Discrepancies may occur between the built-in PI controller reading and the actual electric energy because the pulse input cannot be obtained during the AE-50/EW-50 power failure, shutoff process, and software update.)

(1) Pulse signal input specifications

CN7 Signal

No. 7, 8 Metering device 4 (count input)

No. 5, 6 Metering device 3 (count input)

No. 3, 4 Metering device 2 (count input)

No. 1, 2 Metering device 1 (count input)

(2) Recommended circuit

12 VDC

CN7

(4)

(3)

(2)

(1)

(8)

(7)

(6)

(5)

P4

P3

P2

P1

A voltage of 12 VDC is applied to CN7. Do not apply a power voltage from any other power source.

AE-200/AE-50/EW-50

Max.

100 m (328 ft)

Contact rating

Rated voltage: 12 VDC

Rated current: 0.1 A or above

Minimum applied load: DC 1 mA

Note

● The total length of the lead wire and extension cable should not exceed 100 m (328 ft). (Use an extension cable of 0.3 mm

2 or thicker.)

● Cut the excess cable near the connector, and insulate the end of the unused cable with tape.

● Do not run the signal input cable adjacent to the M-NET transmission and power cables. Do not let the cable form a loop.

● Peel off the sheath to 6 ±1 mm (4/16 ±1/16 in) from the end, and securely insert the cable into the terminal.

● Leave adequate slack in the cables so that the weight of them will not strain the terminal connectors. Use cable clamps or trunk terminals as necessary.

WT07417X01

44

11. Maintenance

11-1. Inspection and maintenance

Air conditioning units including EW-50 controllers may be damaged after long use, resulting in a performance drop or the units becoming a safety hazard. To use them safely and maximize their lives, it is recommended that a maintenance contract with a dealer or qualified personnel be signed. If the contract is signed, service technicians will periodically inspect the units to identify any damage at an early stage, and take appropriate measures.

<Reference> Maintenance/replacement cycle of components

Component

Controller (EW-50)

Maintenance/replacement cycle

10 years

* “Maintenance/replacement cycle” is not a warranty period.

* “Maintenance/replacement cycle” indicates the estimated cycle period in which each component should be replaced or repaired.

WT07417X01

45

11-2. Back up/import settings data

The settings data that have been made from the Web Browser for Initial Settings can be exported to an HDD as a backup.

The exported data can be imported back to the AE-200/AE-50/EW-50 to restore the previous settings after

AE-200/AE-50/EW-50 replacement.

Click [Utility] in the menu bar, and then click [Back up/import settings data] to access the Back up/import settings data screen.

Note: Back up/import settings data function is accessible only if logged in as a maintenance user.

Data import source

The path to the file to be imported will appear.

Back up settings data

Click to back up the EW-50 settings data.

Browse...

Click to browse for a file that contains the data to be imported.

Import settings data

Click to import the file specified in the “Data import source” field to the EW-50.

11-2-1. Backing up settings data

(1) To back up the data, click [Back up settings data]. The settings data will be created and the Window’s standard file download dialog will appear.

Note: It will take a few minutes to create the settings data.

Note: The name of the settings data will be “SettingData.dat”.

WT07417X01

46

11-2-2. Importing settings data

(1) Click the [Browse...] button to launch the explorer and browse for a file that contains the data to be imported.

Select the desired file, and click [Open]. The path to the file to be imported on an HDD will appear in the [Data import source] field.

(2) Click [Import settings data] to import the data from an HDD to the EW-50.

Note: It will take a few minutes to import the settings data.

(3) When the settings data has been successfully imported, the EW-50 will restart.

(4) Go back to the login screen and login again.

WT07417X01

47

11-3. Software update

The EW-50 software can be updated by using a Web browser.

EW-50

PC for update

USB

HUB

LAN

CD

11-3-1. Preparation

Follow the instructions below to change the IP address of the PC that is used for software update.

Note: When the system is connected to the existing LAN, ask the system administrator for permission before changing the

IP address settings and updating the software.

(1) Click [Control Panel] in the Start menu, and click [Network and

Sharing Center]>[Local Area Setting].

In the [Local Area Connection Status] window, click [Properties].

(2) Click [Internet Protocol Version 4 (TCP/IPv4)] to select it, and click

[Properties].

WT07417X01

48

(3) In the [Internet Protocol Version 4 (TCP/IPv4) Properties] window, check the radio button next to [Use the following IP address].

Enter [192.168.1.*] in the [IP address] field. (The number indicated with an asterisk must be different from the IP address of the EW-50 to be updated.)

Leave [255.255.255.0] in the [Subnet mask] field as it is.

Note: If the IP address of the EW-50 is [192.168.1.1], set the same 1st, 2nd, and 3rd numbers and different 4th number, such as [192.168.1.2].

Note: Default IP address of EW-50 is [192.168.1.1].

Note: When performing an update on a PC that is already connected to the existing

LAN, [255.255.255.0] may not appear in the [Subnet mask] field. When

[255.255.0.0] appears, enter the same 1st and 2nd numbers (192.168) and different 3rd or 4th number of the IP address of the EW-50 in the [IP address] field.

Caution:

Obtain an approval from the client for the following precautions as necessary.

1. The communication between EW-50 and the air conditioning units will stop while the software is being updated. Although the unit in operation may detect a communication error and an error sign may appear on the local remote controllers, the unit will continue its operation and be operable from the local remote controllers.

* Note that Mr. Slim indoor units or systems with no local remote controllers may detect a communication error and come to an abnormal stop.

2. Record the operation status of the air conditioning units immediately before updating the software. After the software update completes, check the operation status of the units, and manually operate the units as necessary.

3. Some operations and functions, such as scheduled operations, billing function, Peak Cut control, energy management function, will be disabled while the software is being updated. Check the setting details of these functions beforehand, and update the software when it does not affect these functions.

4. If the functions in the table below are used on the TG-2000A, avoid updating the software during the time period indicated in the right column.

TG-2000A function in use

Electricity charge apportioning function

Malfunction log backup

Peak Cut data backup

Measurement trend data backup

Time period in which the update is prohibited

AM 4:05 – 4:35

AM 0:05 – 0:15

AM 2:00 – 2:10

AM 1:05 – 1:15

5. CSV output data (e.g., energy management data) will lose up to 60-minute worth of data.

6. When a built-in PI controller is used, pulse signals cannot be input while the software is being updated.

WT07417X01

49

11-3-2. Update procedures

(1) Make sure that the PC that has been set in section 11-3-1 above and the EW-50 to be updated are

connected with a LAN cable.

(2) Turn on the power to the EW-50, and insert a CD or USB memory device in which the update file is stored to the PC.

(3) Enter the web page address in the address field of the Web browser as follows:

https://[IP address of each EW-50]/swupdate/Update.html

Press the [Enter] key.

Note: If the IP address of the EW-50 is [192.168.1.1], the web page address is [https://192.168.1.1/swupdate/Update.html].

(4) If the security certificate is invalid, a security certificate error page (as shown at right) will appear.

Click [Continue to this website (not recommended)].

(5) Enter the maintenance user name and the password in the login screen, and click [OK]. (Default user name: initial, Default password: init)

(6) A software update screen will appear.

(7) Click the [Browse...] button and select the update file (AExx_

FW####.dat) stored in the CD or USB memory device, and click [Start

Update].

Note: The software cannot be downgraded to an earlier version.

(8) A software update process starts.

Note: It takes about ten minutes to complete the update.

Note: Do not disconnect the LAN cable or turn off the power to the EW-50 while the software is being updated.

WT07417X01

50

(9) The EW-50 will reboot after the update is complete.

Check that the version that will appear on the screen is the same as the version of the update file. Also check that the version displayed on the Web browser (the Registration of Optional Functions screen, via the Web Browser for Initial Settings) is also the same.

If the software update did not properly complete, update the software again. If the problem persists, the EW-50 may be damaged. Consult your dealer.

11-4. Software information

Detailed information about the open source software of the AE-200/AE-50/EW-50 can be checked by accessing the following address:

https://[IP address of each AE-200, AE-50, or EW-50]/license/

* Accessible only if logged in as a maintenance user.

WT07417X01

51

12. Error code list

Error codes and their definitions are shown below. If an error occurs, note the error code and consult your dealer.

(A) indicates A-control units.

12-1. M-NET errors

0092 Version combination error

0093 System configuration change warning

0094 “Charge” license not registered

0095 Warning - possibility of damaged metering device

0097 Apportioned calculation data collection error

0100 Equipment abnormality

01*0 Equipment abnormality (PAC-YG66DCA) in system *

01** Equipment abnormality in system **

0403 Serial transmission trouble

0404 Indoor unit EEPROM error (A)

0701 Combustion circuit abnormality (A)

0702 Combustion heat exchange overheating protection (A)

0703 Accidental fire (A)

0704 Heater abnormality (A)

0705 Seismoscope malfunction (A)

0706 Flame current sensor abnormality (A)

0707 Ignition abnormality (A)

0708 Blower motor rotation abnormality (A)

0709 Oil pump circuit abnormality (A)

0900 Test run

1000 Refrigerant cycle abnormality

10*0 Refrigerant cycle abnormality in line *

1102 Discharge temperature abnormality (TH4) (A)

1108 Inner thermo (49C) operation (A)

11**

1300 Low-pressure abnormality (63L operation) (A)

13**

Refrigerant cycle temperature abnormality - Common operand: **

Refrigerant cycle pressure abnormality - Common operand: **

1500 Refrigerant cycle not operate due to overcharge

1501 Refrigerant cycle not operate due to undercharge (/compressor shell temperature abnormality)

1502 Refrigerant cycle not operate due to liquid back /Low-discharge super heat abnormality (A)

1503 Refrigerant cycle not operate due to coil frost

1504 Refrigerant cycle not operate due to overheat protection

1505 Refrigerant cycle not operate due to compressor vacuum operation protection/refrigerant low temperature abnormality

1506 Refrigerant cycle not operate due to refrigerant pump abnormality

1507 Refrigerant cycle not operate due to composition detection abnormality

1508 Refrigerant cycle not operate due to control valve fault

1509 Refrigerant cycle not operate due to high pressure abnormality (ball valve closed)

1510 Refrigerant cycle - Gas leakage

1511 Refrigerant cycle not operate due to oil slick abnormality

1512 Refrigerant cycle not operate due to a stop of freezing protection function

1513 Refrigerant cycle - Brine freezing

1559 Oil balance circuit abnormality

2000 Water system abnormality (Pump interlock abnormality)

20*0 Water system abnormality in line *

21**

23**

Water system temperature abnormality - Common operand: **

Water system pressure abnormality - Common operand: **

2500 Water system not operate due to water leak

2501 Water system not operate due to water supply suspension

2502 Water system not operate due to drain pump abnormality

2503 Water system not operate due to drain sensor abnormality/float switch function

2504 Water system not operate due to liquid level abnormality

2505 Water system not operate due to cool water valve abnormality

2506 Water system not operate due to warm water valve abnormality

2507 Water system not operate due to dew condensation prevention control activated

2600 Water system operation restricted due to water leak

2601 Water system operation restricted due to water supply suspension/humidifier water supply suspension

2602 Water system operation restricted due to drain pump abnormality

2603 Water system operation restricted due to drain sensor abnormality

2604 Water system operation restricted due to liquid level abnormality

2613 Drop in water flow rate

3152 Air system operation restricted due to inverter control box inner temperature abnormality

3182 Air system operation restricted due to housing inner temperature abnormality

3600 Air system operation restricted due to filter clogging

WT07417X01

52

3601 Air system operation restricted due to filter maintenance

3602 Air system operation restricted due to damper position detecting abnormality

37**

38**

Air system operation humidity abnormality allowance - Common operand: **

Air system operation humidity abnormality - Common operand: **

4000 Electric system abnormality

40*0 Electric system abnormality in line *

4100 Electric system not operate due to overcurrent shut-off

4101 Electric system not operate due to overcurrent protection

4102 Electric system not operate due to open phase /Open phase (T phase) (A)

4103 Electric system not operate due to reversed phase/open phase

4104 Electric system not operate due to electric leak

4105 Electric system not operate due to short circuit

4106 Electric system not operate due to self power supply OFF/power failure

4107 Electric system not operate due to overload

4108 Electric system not operate due to overload protection/OCR51C /Open phase (S phase),51CM connector open (A)

4109 Electric system not operate due to OCR51F

4110 Electric system not operate due to high voltage part

4111 Electric system not operate due to bus current

4112 Electric system not operate due to coil overheat 49°C

4113 Electric system not operate due to heater overheat

4114 Electric system not operate due to fan controller abnormality

4115 Electric system not operate due to power supply synchronism abnormality /Input circuit (board) failure

4116 Electric system not operate due to motor abnormality/speed abnormality

4117 Compressor self-protection function operation (A)

4118 Opposite phase detection circuit (board) failure (A)

4119 Open of 2 or more connectors (A)

4121 Electric system not operate due to trouble in equipment to which a measure against higher harmonics is taken

4123 Electric system not operate due to Inverter output error

4124 Electric system not operate due to damper abnormality

4125 Electric system - Rush-proof circuit abnormality

4200 Inverter abnormality

420* Inverter abnormality - Inverter No.: *

4210 Inverter overcurrent shut-off

421* Inverter overcurrent shut-off - Inverter No.: *

4220 Inverter bus voltage insufficiency / Voltage abnormality (A)

422* Inverter bus voltage insufficiency - Inverter No.: *

4230 Inverter radiating thermostat abnormality

423* Inverter radiating thermostat abnormality - Inverter No.: *

4240 Inverter overcurrent (overload) protection

424* Inverter overcurrent protection - Inverter No.: *

4250 Inverter IPM/bus voltage abnormality /Power module abnormality (A)

425* Inverter IPM abnormality *

4260 Inverter cooling fan trouble

426* Inverter cooling fan trouble - Inverter No.: *

5000 Sensor trouble

50*0 Sensor trouble in system *

51** Temperature sensor trouble - Sensor No.: **

5202 Connector (63L) open (A)

52** Pressure sensor trouble - Sensor No.: **

5300 Current sensor abnormality (A)

53**

54**

55**

56**

Current sensor trouble - Sensor No.: **

Humidity sensor trouble - Sensor No.: **

Gas sensor trouble - Sensor No.: **

Air speed sensor trouble - Sensor No.: **

57**

58**

Limit switch trouble - Switch No.: **

Sensor trouble - Sensor No.: **

59** Other sensors trouble - Sensor No.: **

6000 System abnormality

6101 System not operate due to abnormality - With response frame

6102 No answer back

6200 Controller H/W abnormality

6201 E2PROM abnormality

6202 RTC abnormality

6204 External memory read/write error

6500 Communication error

6600 Communication error - Address duplicate

6601 Communication error - Polarity unsettled

6602 Communication error - Transmission processor hardware error

6603 Communication error - Transmission line busy

6604 Communication error - No ACK (06H) (communication circuit error)

6605 Communication error - No response frame

WT07417X01

53

6606 Communication error - Transmission processor communication error

6607 Communication error - No ACK return

6608 Communication error - No return of response frame

6609 Communication error

6610 Communication error

6800 Communication error - Other communication errors

6801 Communication error - V-control communication error

6810 Communication error - UR communication error

6811 Communication error - UR communication synchronism not recover

6812 Communication error - UR communication hardware error

6813 Communication error - UR communication status bit detection error

6820 Other communication errors

6821 Other communication errors - Transmission line busy

6822 Other communication errors - No communication ACK

6823 Other communication errors - No response command

6824 Other communication errors - Receive data error

6830 Communication error - MA communication refrigerant address double setting error

6831 Communication error - No MA communication reception error

6832 Communication error - MA communication synchronism not recover

6833 Communication error - MA communication transmission/reception hardware trouble

6834 Communication error - MA communication start bit detection error

6840 Communication error - A control no indoor/outdoor communication/reception abnormality

6841 Communication error - A control indoor/outdoor communication synchronization recovery abnormal

6844 Communication error - A control indoor/outdoor communication incorrect indoor/outdoor wiring connection, excessive number of indoor units (more than five units)

6845 Communication error - A control indoor/outdoor communication incorrect indoor/outdoor wiring connection (telecommunication, disconnection)

6846 Communication error - A control indoor/outdoor communication startup time exceeded

7000 System abnormality

7100 System abnormality - Total capacity error

7101 System abnormality - Capacity code error

7102 System abnormality - Connecting unit number excess

7103 System abnormality - Piping length setting error

7104 System abnormality - Floor height setting error

7105 System abnormality - Address setting over 254

7106 System abnormality - Attribute setting error

7107 System abnormality - Distributor setting error

7108 System abnormality - Refrigerant system setting error

7109 System abnormality - Connection setting error

7110 System abnormality - Refrigerant system connection/connection data unsettled

7111 System abnormality - I/O connection equipment not connected/remote controller sensor abnormality

7112 System abnormality - I/O type setting error

7113 System abnormality - Equipment unsettled

7116 System abnormality - Replace non-wash setting error

7117 System abnormality - Model identification setting error

7130 System abnormality - Different unit model error

7131 System abnormality - Mixed cooling only H/P connection error (Facility PAC)

7132 System abnormality - Multiple entries of operation performance (Facility PAC)

7200 System abnormality - Numeric values unsettled

7201 System abnormality - Numeric values unsettled

73** System abnormality - LON system equipment abnormality

12-2. Errors between AE-200 and AE-50 (EW-50)

6920 No response error

6922 Response ID error

7901 Maximum connectable No. of units exceeded

7902 Connection lock error

7903 Unit information error

7904 System setting error

7905 Version error

WT07417X01

54

SD and SDHC Logos are trademarks of SD-3C, LLC.

Java is a registered trademark of Oracle and/or its affiliates.

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications.

However, there is no guarantee that interference will not occur in a particular installation.

If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

- Reorient or relocate the receiving antenna.

- Increase the separation between the equipment and receiver.

- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

- Consult the dealer or an experienced radio/TV technician for help.

WT07417X01

55

Bu uyarının içeriği sadece Türkiye’de geçerlidir.

• Şirketimizdeki geliştirme faaliyetlerinden dolayı ürün özelliklerinin, haber verilmeksizin değiştirilme hakkı tarafımızda saklıdır.

• Anma değerleri için TS EN 14511 / TS EN 14825 deki iklim şartları ile tarif edilen koşullar esas alınmıştır.

• İç ve dış ortam sıcaklıklarının standartlarda esas alınan değerlerin dışına çıkması durumunda klimanızın ısıtma ve soğutma kapasitelerinin etkilenmesi doğaldır.

• Ürünün üzerinde bulunan işaretlemelerde veya ürünle birlikte verilen diğer basılı dokümanlarda beyan edilen değerler, ilgili standartlara göre laboratuvar ortamında elde edilen değerlerdir. Bu değerler, ürünün kullanım ve ortam şartlarına göre değişebilir.

• Satın almış olduğunuz ürünün kullanım ömrü 10 yıldır. Bu, ürünün fonksiyonunu yerine getirebilmesi için gerekli yedek parça bulundurma süresidir.

Ürünün montajı için Mitsubishi Electric Turkey Elektrik Ürünleri A.Ş. yetkili servisine / bayisine başvurunuz.

Servis İstasyonları ve Yedek Parça Temini :

Cihazınızın bakım, onarım ve yedek parça ihtiyaçları için klimanızı satın aldığınız yetkili satıcıya başvurunuz. Yetkili Servislerimizin listesine [www.klima.mitsubishielectric.com.tr] adresinden veya 444 7 500 numaralı telefondan ulaşabilirsiniz.

Ünitenin ihtiyaç duyacağı bakım ve onarım parçaları 10 yıl boyunca üretilecektir.

İthalatcı Firma:

Mitsubishi Electric Turkey Elektrik Ürünleri A.Ş.

Şerifali Mah. Kale Sk. No: 41 34775 Ümraniye / İstanbul / Türkiye

Tel: + 90 216 66 100 66 Faks: + 90 216 661 44 47 [email protected]

www.klima.mitsubishielectric.com.tr

Merkez Ofis (Head Office)

Büyükdere Cad. Maya Akar Center C Blok No: 4/9 34394 Esentepe-Şişli, İstanbul, Türkiye

Tel: +90 212 318 90 86 www.mitsubishielectric.ae/turkey/

Üretici Firma:

Mitsubishi Electric Corporation (Head Office)

Tokyo Building 2-7-3, Marunouchi, Chiyoda-ku, Tokyo 100-8310, Japan

Tel: +81 (3) 3218-2111 www.mitsubishielectric.com

WT07417X01

56

WT07417X01

57

WT07417X01

58

WT07417X01

59

This product is designed and intended for use in the residential, commercial and light-industrial environment.

The product at hand is based on the following EU regulations:

• Low Voltage Directive 2006/95/EC

• Electromagnetic Compatibility Directive 2004/108/EC

• Restriction of Hazardous Substances 2011/65/EU

Please be sure to put the contact address/telephone number on this manual before handing it to the customer.

HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN WT07417X01

872C595A30

advertisement

Key Features

  • Web-based control
  • Up to 200 unit management
  • Energy monitoring
  • Scheduling
  • External input/output
  • Malfunction log
  • Software updates

Frequently Answers and Questions

How many indoor units can the EW-50E control?
When connected to an AE-200 controller, the EW-50E can control up to 200 indoor units.
What are the system restrictions for the EW-50E?
The software versions of all connected units (AE-200, AE-50, and EW-50) must be the same. The number of controllable units and the available functions may vary depending on the specific unit models.
Can I update the EW-50E software?
Yes, the EW-50E software can be updated using a CD or USB memory device.