Apollo Valves LC149251 LC149 Series 2-1/2 in. Cast Iron Flanged EPDM 10 Position Handle Butterfly Valve Installation Manual

Apollo Valves LC149251 LC149 Series 2-1/2 in. Cast Iron Flanged EPDM 10 Position Handle Butterfly Valve Installation Manual

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Manual
Apollo Valves LC149251 LC149 Series 2-1/2 in. Cast Iron Flanged EPDM 10 Position Handle Butterfly Valve Installation Manual | Manualzz

LC149 SERIES

BUTTERFLY VALVE

INSTALLATION,

OPERATION, &

MAINTENANCE

P.O. Box 125 /1418 S. Pearl Street Pageland, SC 29728 I980700

ECN# M14630

APOLLO

BFV INSTALLATION MANUAL - Page 2 of 12

INTRODUCTION ...................................................................... 3

DESIGN FEATURES ................................................................................................. 3

OPERATING PRESSURES ......................................................................................... 3

PRODUCT STORAGE ................................................................................................ 3

PRODUCT MARKING ................................................................................................ 3

FIGURE 1. APOLLO

BUTTERFLY VALVE INDENTIFICATION TAG ........................ 4

INSTALLATION INFORMATION ................................................ 4

INSTALLATION INSTRUCTIONS ................................................................................ 4

FIGURE 2. VALVE IN PARTIALLY OPEN POSITION ................................................ 5

FIGURE 3. VALVE IN FULL OPEN POSITION ......................................................... 5

MAINTENANCE AND REPAIR.................................................................................... 5

TABLE 1. BUTTERFLY VALVE DISC CHORD DIMENSIONS ................................... 6

TABLE 2. BOLT SPECIFICATIONS FOR LUG ......................................................... 6

FIGURE 4. FLANGE BOLT TIGHTENING SEQUENCE ............................................ 7

ASSEMBLY/DISASSEMBLY INSTRUCTIONS ........................... 7

LC149 SERIES BUTTERFLY VALVE ASSEMBLY AND DISASSEMBLY ........................ 7

TABLE 3. LC149 SERIES SEAT MATERIAL TEMPERATURE RANGES .................... 7

BUTTERFLY VALVE PART LISTS ............................................. 8

FIGURE 5. LC149 SERIES PARTS LIST ..................................................................... 8

MANUAL OPERATOR INSTALLATION ...................................... 9

LEVER HANDLE MOUNTING PROCEDURE .............................................................. 9

FIGURE 6. NOTCHPLATE INSTALLATION POSITION ............................................. 9

MANUAL GEAR OPERATOR MOUNTING PROCEDURE ............................................. 9

FIGURE 7. GEAR OPERATOR INSTALLATION POSITION ..................................... 10

INSTRUCTION FOR SETTING UP GEAR OPERATO..

……………………………...........9

AMENDMENT REGISTER ...................................................... 11

P.O. Box 125 /1418 S. Pearl Street Pageland, SC 29728 I980700

ECN# M14630

APOLLO

BFV INSTALLATION MANUAL - Page 3 of 12

INTRODUCTION

DESIGN FEATURES

LC149 SERIES

Available in lug body only.

Flange holes comply with ANSI Class 125/150 dimensions.

Cast-in top plate with ISO-5211 mounting dimensions provides for direct-mounting of

Apollo

actuators and manual operators.

All body dimensions were designed to comply with MSS SP-67 and API 609.

Through-shaft design with pinned connection from stem to disc.

Disc-to-seat interface provides bubble-tight shut-off with reduced torque and extended service life.

Equipped with a blowout-proof, phenolic-backed EPDM (food grade) cartridge seat.

Factory tested to 110% of full rated pressure in both directions before shipping.

FLANGE AND PIPE COMPATIBILITY

APOLLO

Butterfly Valves are designed to fit between the following piping flanges:

ANSI 125 Cast iron flanges (all sizes)

ANSI 150 Steel flanges, schedule 40 (all sizes)

ANSI 150 Steel flanges, schedule 80 (all sizes)

Note: When installing valves in schedule 80 piping, make sure the valve is properly centered between the pipe flanges to prevent disc edge damage since the clearance between the disc O.D. and the pipe I.D. is reduced. If there is a compatibility question, compare the minimum pipe I.D. with the disc chord dimensions in Table 1.

OPERATING PRESSURES

LC149 SERIES:

2”-12” (50mm-300mm) – 200 psig (13.78 bar)

PRODUCT STORAGE

The valves should be stored with the disc in the partially open position.

The valves should be stored indoors in a clean, dry, well-ventilated place away from corrosive materials and protected from excessive dust and dirt.

The valves should be stored on a rack or pallet off the floor and arranged to prevent damage during handling.

Keep valves out of direct sunlight and in a cool location to prolong elastomer life.

Valves should be protected to prevent damage to the flange faces, disc sealing edge and operator.

PRODUCT MARKING

All APOLLO

Butterfly Valves are equipped with an identification tag attached to the valve neck (Figure 1). This tag provides the model number, part number, size, max pressure rating, and date of manufacture.

P.O. Box 125 /1418 S. Pearl Street Pageland, SC 29728 I980700

ECN# M14630

APOLLO

BFV INSTALLATION MANUAL - Page 4 of 12

FIGURE 1: APOLLO

BUTTERFLY VALVE INDENTIFICATION TAG

INSTALLATION INFORMATION

APOLLO

butterfly valves are designed for use between the faces of ANSI Class 125 and 150 flat, raised face, slip-on or weld-neck flanges at the pressure indicated on the nameplate.

Flange gaskets should not be used. Due to the brittle nature of cast iron, consideration should be given to the proper piping alignment prior to the installation of any cast iron lug bodied valve. All APOLLO

resilient seated butterfly valves are bi-directional with the ability to control flow equally in either direction. All LC149 Series APOLLO

lug style butterfly valves may be used for dead-end service in either direction at their full pressure rating.

INSTALLATION INSTRUCTIONS

Step 1. Check to make sure that the pipe flange and valve sealing faces are clean and free from any debris (pipe scale, welding slag, etc.).

Step 2. Check the valve nameplate to ensure that the pressure and valve materials are correct for the application. See Table 3 for seat material temperature ratings.

WARNING! – Apollo butterfly valves should never be installed where service conditions could exceed the valve ratings. Failure to heed warning may result in personal injury or property damage.

Step 3. The seat sealing face on the LC149 Series butterfly valves is wider than the valve body providing a leak-proof seal when compressed between pipe flanges. Therefore, no flange gaskets are required when installing an APOLLO

butterfly valve.

Step 4. To prevent damage to the disc sealing edge during installation, position the disc in the “partially open” position (Figure 2) so that the disc is still contained within the valve body.

P.O. Box 125 /1418 S. Pearl Street Pageland, SC 29728 I980700

ECN# M14630

APOLLO

BFV INSTALLATION MANUAL - Page 5 of 12

FIGURE 2: VALVE IN PARTIALLY OPEN POSITION

Step 5. Spread the pipe flanges apart allowing the valve to be slipped easily in between the flanges.

Step 6. Center the valve between the flanges and loosely install all the flange bolts.

Consult Table 2 for correct flange bolt size and quantity.

Step 7. Slowly open the valve to the full open position (Figure 3) and back to the partially open position ensuring that the disc moves freely without any obstruction. If no obstruction is encountered, return the valve to the full open position and handtighten all flange bolts using the bolt tightening sequence shown in Figure 4.

FIGURE 3: VALVE IN FULL OPEN POSITION

Step 8. Rotate the disc from the fully open position to the fully closed position and make sure that the valve is properly centered and the disc edge does not contact the pipe

ID. Return the disc to the full open position and tighten the flange bolts following the bolt tightening sequence shown in Figure 4. However, do not fully tighten each flange bolt all at once. Tighten each bolt incrementally following the sequence in

Figure 4 several times until the flange bolts are tight. After all flange bolts are fully tightened, cycle the valve from full open to full closed to ensure that there is proper disc clearance.

MAINTENANCE AND REPAIR

APOLLO

butterfly valves are designed for extended service with minimal wear and servicing. No regular lubrication is required. Prior to any replacement or repair, the valve must be removed from the line following these precautions:

1. The pipeline on both sides of the valve must be depressurized and drained.

P.O. Box 125 /1418 S. Pearl Street Pageland, SC 29728 I980700

ECN# M14630

APOLLO

BFV INSTALLATION MANUAL - Page 6 of 12

2. Ensure that the disc is in the partially open or fully closed position before removing the valve from the line.

3. DO NOT remove an actuator or operator from the valve while the line is still pressurized.

Valve Size Disc Chord

(in) (mm)

2 50

2.5 65

3 80

4

5

6

100

125

150

(in)

1.14

1.71

2.45

3.49

4.30

5.70

8 200

10 250

12 300

7.69

9.71

11.74

TABLE 1: BUTTERFLY VALVE DISC CHORD DIMENSIONS

LUG BODY REGULAR HEX HEAD

SCREWS WITH NC THREADS

Valve Size Diameter Length Quantity

(in)

2

2.5

3

4

5

6

(mm)

50

65

80

100

125

150

(in)

5/8”

5/8”

5/8”

5/8”

3/4”

3/4”

(in)

1-1/2”

1-1/2”

1-3/4”

1-3/4”

1-3/4”

2”

4

4

4

8

8

8

8 200

10 250

12 300

3/4”

7/8”

7/8”

2-1/4”

2-1/4”

2-1/2”

8

12

12

TABLE 2: BOLT SPECIFICATIONS FOR LUG VALVES

P.O. Box 125 /1418 S. Pearl Street Pageland, SC 29728 I980700

ECN# M14630

APOLLO

BFV INSTALLATION MANUAL - Page 7 of 12

FLANGE

SIZE

BOLT

SIZE

MIN. BOLT

TORQUE

MAX BOLT

TORQUE

(FT./LBS.) (FT./LBS.)

2”-4”

5”-8”

10” AND 12”

14” AND 16”

18” AND 20”

24”-30”

32”-48”

54”-60”

5/8”

3/4”

7/8”

1”

1-1/8”

1-1/4”

1-1/2”

1-3/4”

20

30

50

70

100

140

200

350

70

120

200

240

380

520

800

1800

FIGURE 4: FLANGE BOLT TIGHTENING SEQUENCE

ASSEMBLY/DISASSEMBLY INSTRUCTIONS

LC149 SERIES BUTTERFLY VALVE ASSEMBLY AND DISASSEMBLY

The LC149 Series butterfly valves DO NOT have field replaceable parts.

Therefore, assembly or disassembly is not permitted. Once the valve is removed from the line, inspect the parts for wear. If valve parts show wear, replacement is necessary. Contact your local

APOLLO

distributor for a replacement valve.

Type Min Max

EPDM -30 °F (-34 °C) +275 °F (135 °C)

TABLE 3 : LC149 SERIES SEAT MATERIAL TEMPERATURE RANGES

P.O. Box 125 /1418 S. Pearl Street Pageland, SC 29728 I980700

ECN# M14630

A

A

APOLLO

BFV INSTALLATION MANUAL - Page 8 of 12

BUTTERFLY VALVE PART LISTS

LC149 SERIES PARTS LIST

8.88

5.88

1.25

8.46

.551

12

1

3

O

9.50

2

6

5

9

7

SECTION A-A

Figure 5: Assembly View: 3” Butterfly Valve Shown

5

8

5

5

2

8 X

O

3/4-10 UNC

4

10

11

P.O. Box 125 /1418 S. Pearl Street Pageland, SC 29728 I980700

ECN# M14630

APOLLO

BFV INSTALLATION MANUAL - Page 9 of 12

MANUAL OPERATOR INSTALLATION

LEVER HANDLE MOUNTING PROCEDURE

Step 1. First, start by loosely assembling the notch plate on the valve top plate. The notchplate should be installed with the notches in the third quadrant of the valve top plate with the stop tabs at the 6 o’clock and 9 o’clock position. The notchplate should be installed with the stop tabs pointing upward (Figure 5).

Step 2. Next, install the handle so that the lever fully engages in the notches when the lever is released and tighten the handle set screw.

Step 3. Compress the handle lever and position the disc so that the valve is in the fully closed position. Align the last notch on the notchplate at the 9 o’clock position with the handle lever and tighten the notch plate screws.

Step 4. Compress the handle lever and position the disc so that the valve is in the fully open position and release the lever. The lever should line-up with the last notch on the notchplate at the 6 o’clock position.

CI

3

FIGURE 6: NOTCHPLATE INSTALLATION POSITION

N O T E : T his dra w ing a nd t he s ub jec t m at t er dis cl os ed t h erein i s t he p rop ert y of C onb rac o I nd us tri es , I nc . a nd i s not t o be c opi ed, us ed , ap pro pria te d or dis cl os e d to o th ers w it hou t t he e xp res s ed w rit t en pe rm is si on o f C on bra co I n dus tri es , In c.

N A ME:

RE V.

CH A N G E DE S CRI P T IO N E CN NO .

BY DA T E

R

MANUAL GEAR OPERATOR MOUNTING PROCEDURE

S C A LE: DR N: E X P. NO .

DA T E:

Step 1. First, rotate the valve disc to the fully open position.

CH K D: A P P'D: NO .

RE V.

Step 2. Slide the handwheel onto the end of the gear operator shaft. Line-up the hole in the handwheel with the hole in the gear operator shaft. Install the shear pin and rotate the gear operator to the open position.

Step 3. Line-up the valve stem with the gear operator bore and slide the gear operator onto the valve with the handwheel pointing to the right of the valve when looking at the nameplate (Figure 6).

Step 4. Position the gear operator so the tapped holes in the bottom of the gear operator line-up with the valve top-plate mounting holes and install the mounting screws with lock washers.

P.O. Box 125 /1418 S. Pearl Street Pageland, SC 29728 I980700

ECN# M14630

APOLLO

BFV INSTALLATION MANUAL - Page 10 of 12

Step 5. Loosen the gear operator travel stops and rotate the handwheel until the valve is in the fully closed position. Tighten the gear operator stop on the right-hand side of the gear operator. (Note: There are two hex head set screws in tandem that represent the gear operator travel stops. Ensure that the first hex head screw is fully removed before loosening the travel stops.)

MAT'L:

Step 6. Rotate the handwheel until the valve is in the fully open position. Tighten the gear operator stop on the left-hand side of the gear operator.

ECN NO.

BY DATE

Step 7. Cycle the valve from the fully open position to the fully closed position to make sure that the stops are set correctly.

FIGURE 7: GEAR OPERATOR INSTALLATION POSITION

P.O. Box 125 /1418 S. Pearl Street Pageland, SC 29728 I980700

ECN# M14630

APOLLO

BFV INSTALLATION MANUAL - Page 11 of 12

Instructions For Setting Gear Operator

Step 1.

Mount gear operator (Item 1) on top of butterfly valve with the four bolts and washers provided with each assembly.

Step 2.

Use Allen wrench to remove locking set screws (item 2) and to adjust stops (item 3), see tools required.

Step 3.

Remove locking (short) set screw from both sides of the gear operator. (Item 2)

Step 4.

Loosen the second (longer) set screws (Item 3) approximately three to four turns on both sides of the gear operator.

Step 5.

Rotate handle to the fully open position and tighten set screw (item 3) into position.

Now, add locking set screw (item 2) and lock both into place.

Step 6.

Rotate hand wheel to the fully closed position. Note disc should be centered in the seating surface.

Step 7.

Once disc is fully closed, tighten set screw (item 3) into the stop position. Then open disc 20% and then back to closed position. Re-adjust set screw (item 3) if necessary. Add Locking set screw (item 2) and lock both into place. You have now locked both the open and closed positions into place.

Step 8.

As a quick reference, note the position of the pointer and the word CLOSE. The pointer should be near the center or close to the top of the letter “E” in the word

CLOSE. See Figure 7.

Item 3: Set Screw – Stop Pin

Item 2: Locking Set Screw

Item 1: Gear Operator with

Position Indicator

Tools Required

2" - 8" Valves 6 mm Hex Allen Wrench

Figure8: Pointer Location in Closed Position

10" - 24" Valves 8 mm Hex Allen Wrench

P.O. Box 125 /1418 S. Pearl Street Pageland, SC 29728 I980700

ECN# M14630

DATE REV

9/22/2014 A

APOLLO

BFV INSTALLATION MANUAL - Page 12 of 12

AMENDMENT REGISTER

PAGE

ALL

DESCRIPTION ECN# _

NEW RELEASE M14630

P.O. Box 125 /1418 S. Pearl Street Pageland, SC 29728 I980700

ECN# M14630

advertisement