1. Operation If the pre set temperature is enabled when you return home: 1.1 Manual Operation These functions allow manipulating the temperature without changing the programme. Manual operation can be carried out in two ways: 1. Press b The temperature of the current switching time appears for a few seconds. The arrow is by the current switching time. 2. Press Z or a to set the temperature (if required) 3. Press b to confirm. Otherwise after 5 sec here will be a auto-accept. Temporary temperature change 1. Press key Z or a till needed temperature is displayed. (To check temperature without changing exit by pressing b) 2. Press b to confirm. Otherwise after 5 sec here will be a auto-accept. The current temperature is displayed again. This temperature will be used until the next programming step. This procedure is valid only when the Weekly programme k, the Daily programme j or the Party/Boost programme l is enabled. 1.3 Weekly programme k This programme allows you to repeat the same programme every week. 1 2 3 4 5 6 7 d W the value is 1, the function will end at 12.00 a.m. and the d 1 2 3 4 5 6 7 1.2 Going out/Returning home function k j l ß 1. Press Y and select j. The daily programme is enabled. The current temperature and the time of day are displayed. The arrows indicate the daily programme j, the current time range (n | r } ~ M) and the setpoint temperature range ( v u t ). 1.5 Party/Boost programme l To override the programmed temperature for a period of 3 hours. After 3 hours the room thermostat will return to the weekly programme. Operating elements 1 2 3 4 5 6 7 Early morning Morning Noon Afternoon Evening Night Comfort temperature Standard temperature Setback temperature Radio-control enabled 4 Use Heating is active 5 Features 6 Function Description 6.1 Setting controller features 6.2 Performance Instat 868-r… 6.3 Setting the programmes 6.4 Setting no. of switching times per day 6.5 Control type 6.6 PWM or ON/OFF Control 6.7 Optimum Start 6.8 Valve protection 6.9 Temperature display 6.10 Temperature display offset 6.11 Change-over between heating and cooling 6.12 Manually switching on/off the output 6.13 Displaying room or setpoint temperature 6.14 Displaying operation hours 6.15 Erase/Reset 6.16 Display the symbol U 6.17 Learn mode I Temperature Time Chart 2 3 1 2 Use these keys to change the blinking feature (arrow or digit). 5. Press b. The switching time digits blink. 6. Press Z or a to set the digit. 7. Repeat steps 5 and 6 for each digit. After pressing b to confirm the minutes, the arrow will blink by v u t so that you can set the temperatures. 8. Press Z or a to set one of the three available temperatures v u t. 9. Press b to confirm. The arrow blinks by n | r } ~ M. 10. Repeat steps from 4 on to programme additional switching times. 11. If the arrow blinks on the last icon by s, by pressing a you can go to the setting of the next day. If the arrow blinks on the first icon n , by pressing Z you can go to the setting of the next day. 12. Press Y to exit programming mode. To exit setting mode press Y . Pressing and holding down Z or a will cause the corresponding digits to quickly scroll, for example when inputting the time. Press Y or don't press any key for about 1 min. to exit the current setting, without storing the new value. The weekly programme is turned on. 3 4 5 23 22 21 6 2 19 18 17 16 1 2 3 To change the programme follow steps 1 and 2 4 3 15 14 6 Switching times P1 15 14 4 6 8 10 12 14 16 18 20 22 4 Switching times P2 0 24 Uhrzeit 2 4 6 8 10 12 14 16 18 20 22 Setting the time Select/Set Mon…Fri Working days Sat...Sun Weekends Mon...Sun All days Setting is carried out as described in above step 2. Press Z or a until the required range blinks. If only few days are different from the other days of the week, you can programme the whole week first by means of the Mon...Sun block (all days). Then you can change the different days. To set 6, switching times b) The unit digit of minutes cannot be set, –>Resolution = 10 Minutes. c) Switching off times do not need to be entered separately. The next start time is automatically set as the previous switch-off time. d) If several switching times use the same temperature: Set all these switching times to the same temperature e) The night switching time s can also be set after midnight (until 5:50 a.m.), for example. switching time = 2:30; the temperature will be decreased at 2:30 a.m. To set 8, temperatures f) It is possible to select among three pre-set temperatures, which can be changed as discussed under section 2.4 "Setting temperatures". Setting of temperatures and switching times are independent. If one of the Temperatures v u t is changed, such change will affect all settings the corresponding temperature was assigned to as explained under 2.3.8. Setting switching times for the extra daily programme The daily programme is repeated on a day by day basis. Select j as described above, under section 2.3 step 2. Carry out the above procedure, with the exception of item 11. In this way, weekly programme settings won't be affected. Checking switching times To determine which switching times are set: 1. Select the required day of the week, or the extra daily programme j (the blocks can only be checked as individual days). 2. Press Z or a to select the desired switching time (n| r} ~ M). (don't press b) 3. Press Y to exit. 2.4 Setting temperatures y Here you can set the temperatures. These temperatures can be assigned to the respective times (see II Switching Times Table, 2.3 "Setting Switching Times"). 1 2 3 1. Press Y and select y. The arrow blinks in the temperature group v u t. 2. Press Z or a to select one of the three available temperatures. The corresponding temperature is displayed. 3. Press b The temperature blinks. 4. Press Z or a to set the temperature. 5. Press b The arrow blinks in the temperature group. 6. To program more temperatures repeat steps from 2 on 7. Press Y to exit programming mode. Note: Setting of temperatures and switching times are independent. If one of the temperatures v u t is changed, this change will affect any setting which the corresponding temperature was assigned to, as described under 2.3 „Setting switching times". Confirm Checking temperatures Function: time setting see 2.2 Mode Carry out steps 1 and 2 above to determine which temperatures are set. Press Y to exit. °C 24 Uhrzeit 23 Comfort 1 22 1 Optimum Start The device automatically determines the time when the heating process must begin in order to reach the required room temperature within the set time, for example, it may start heating already at 5:00 a.m. instead of 6:00 a.m. Illustration of daily temperature behaviour with 2, 4, 6 switching times per day 2 1 20 19 18 2 17 9. Dimensions 2 Switching times P5 16 15 10. Technical Data 3 14 0 Only sections 1, 2 and 3 are intended for users. All other remaining sections are for the installer. 2 4 6 8 10 12 14 16 18 20 22 II Table of Programmes and Switching Times Programme Switching Times P1 P2 P3 P4 P5 Standardprogramme The standard programmes are factory set. They should make programming easier. Refer to Table II for specific temperatures and switching times of each programme. 6 4 4 4 2 u2 t3 21°C 21°C 28°C 21°C 21°C 18°C 18°C 18°C 18°C 18°C 15°C 15°C 18°C 18°C 18°C When you select a programme, the previously set "Number of Switching Times" and temperatures will be overwritten with the new settings of this programme. The switching times will remain unchanged. Temperature P1,P2 P3, P4,P5 16 15 14 0 4 2 6 8 10 12 14 16 18 20 22 24 Time Start Time j Temperature P1,P2 P3, P4,P5 n Early morn. 6.00 6.00 21°C 28°C 21°C 7.00 7.00 21°C 28°C 21°C 7.00 21°C 28°C 21°C o Morning 8.30 8.30 18°C 18°C 18°C 10.00 10.00 18°C 18°C 18°C 10.00 18°C 18°C 18°C r Noon 12.00 12.00 21°C 12.00 12.00 21°C 12.00 21°C } Afternoon 14.00 14.00 18°C 14.00 14.00 21°C 14.00 21°C ~ Evening 17.00 17.00 21°C 28°C 21°C 17.00 17.00 21°C 28°C 21°C 17.00 21°C 28°C 21°C s Night 22.00 23.00 15°C 18°C 18°C 23.00 22.00 15°C 18°C 15°C 23.00 15°C 18°C 18°C Set the time + 1st Step 2nd Step: OK Set the switching times See 2.3 For ex. switching time 12.00 is the beginning of time range “Noon“ Set the temperature See 2.4 Function: setting switching times see 2.3 Mode w Back to weekly programme Select/Set d 1 2 3 4 5 6 7 1 2 3 4 5 6 7 This protection prevents control settings from being changed. It can be enabled only if the control is in one of the operating modes (k j A l ß). Confirm Function: setting temperatures see 2.4 Mode 1 2 3 4 5 6 7 Single days Daily programme Day-block: Mon…Sun Day-block: Mon…Fri Day-block: Sat…Sun OK No. Switching times 6 4 2 • • • • • • • • • Morning Forenoon Noon Afternoon Evening Night + Scroll the menu upwards or downwards to set other days + OK 1 Comfort Temperature 2 Standard Temperature 3 Setback Temperature + Set temperature value O OK + 2 3 Comfort Temperatur Standard Temperature OK Select temperature Mode Setback Temperature O OK Select next switching time or • Mode Select temperature range OK Set start time + 1 • • Select day time range using keys + and – Exit 2.6 Reset Reset: When unexpected results occur, the reset key should be pressed. All data are maintained, except for the time and day of the week. To activate Reset: Use a pointed object to press the hole between the x keys. After that, you should enter the time and day again. 2.7 Access protection Step 2 Setting temperatures Confirm Programme selection see 6.3 Daily programme Start Time (Sa) (So) OK 17 + Weekly programme k Temperature P1,P2 P3, P4,P5 18 Setback 3 Select/Set v1 Select a day 1= Monday … 7=Sunday 19 Standard 2 Step 1 Setting switching times 24 Uhrzeit 12 3 4 5 6 7 + 21 20 23 22 21 8 Start-up Day Z bzw. a Temperatur 7 Installation Start Time (Mon,Tue,Wed,Thu) (Fri) If only 2 or 4 Switching Times are set, some switching times are skipped. 1 20 20 19 18 17 16 2 Afternoon Evening Night Temperatur 23 22 21 0 Early morning } Morning ~ Noon M 2.5. Brief introduction (for standard programmes Mon...Sun) Temperatur 1 n | r Press this key untill the required function is selected. The arrow blinks at the feature. k . Enabling the party function 1. Press Y and select l The evening temperature will now remain enabled for 3 hours. 2. Press Z or a to set the temperature (if required). 3. Press b to confirm. Otherwise after 5 sec here will be a auto-accept. The current temperature is displayed again. OK key ON/OFF + key Reset – key Mode key Indicator in icon Lern Mode/ Access protection Cooling mode 3 Tips, Tricks, Troubleshooting 1 2 3 Temperature Ranges Group Batteries need replacing m y the following procedure Setting weekly programme switching times The weekly programme is repeated week by week. See also 2.5 Brief Tutorial 1. Press Y and select m. The arrow blinks by number 1 = Monday. 2. Press Z or a to set the day. 3. Press b. The arrow will blink in the switching time group, by n (Early morning). The switching time and temperature set until that moment are displayed. 4. Press Z or a to select the desired switching time (n | r } ~ M). Y Use this key to confirm the value. The arrow blinks by the next feature During programming, this sequence is often repeated: Press Z or a to change, then confirm with b . If you have finished setting a certain function, the arrow is on Switching Times Group (Time ranges) Time setting Switching times setting Temperature setting 2.1 General programming function For settable functions 3 applies: b extra daily programme Weekly programme Daily programme Manual operation Party/Boost programme Holiday Programming allows setting the following: • Time 3 Time setting of controls equipped with RF clock is automatic. • Switching Times m (times when the set temperature should be reached) • Temperatures y (desired room temperature) • Other Functions d Days (1=Mon, 2=Tue, 3=Wed, 4=Thu, 5=Fri, 6=Sat, 7=Sun) 3 m y The switching times and temperatures should be programmed only if you need to vary the factory-set standard programme. (See Table II) Night 2 Programming 2.1 General programming function 2.2 Setting time/day 2.3 Setting switching times 2.4 Setting temperature 2.5 Brief Introduction 2.6 Reset 2.7 Access protection 2.8 ON / OFF function 2.9 Changing the batteries 2.10 RF clock 2.11 Cleaning If you need to change the standard programme, here you can set 2, 4 or 6 switching times per day. One of the 3 available temperatures can be assigned to these time ranges (see Switching times table II or 2.4 “Setting temperatures”). Night A mode. Evening Table of Contents II Programmes and Switching times table 1 Operation 1.1 Manual operation 1.2 Going out/Returning home 1.3 Weekly Programme 1.4 Daily Programme 1.5 Party/Boost programme 1.6 Holiday Function 1 2 3 Key b can be used as Going out/returning home key. If you leave the house it is possible to decrease the temperature by pressing this key. If you press it again, the control will switch back to the automatic programme. This function has to be previously set up. (See 6.1). It is enabled only in operating modes k and j. The Night temperature t3 is always used as setback temperature. The setback temperature is enabled until: – key b or Y is pressed again, or – switching time n (06.00 a.m.) of the following day. Then the automatic programme will take over again. To terminate this function earlier, select another operating d d 1 2 3 weekly programme will be enabled. 2. Programming This program allows you to repeat the same daily programme j on a day by day basis. 1. Press Y and select A 2. Press Z or a to set the temperature. 3. Press b to confirm. Otherwise after 5 sec here will be a auto-accept. The current temperature is displayed again. I Temperature Time Chart d The day counter will decrease by 1 at 12.00 a.m. daily. When 1. Press Y and select k. Now, the weekly programme is enabled. The current temperature and the time are displayed. The arrows indicate the day (1..7), the current time range (n | r } q M) and the setpoint temperature range ( v u t ). 1 2 3 INSTAT 868… with optional RF clock 2.3 Setting switching times m (changing the standard programme) number of days you have set. 1.4 Daily Programme j Versions: Here you can set the time and day of the week. 1. Press Y and select 3. 2. Press Z or a to select the current day (1...7). 3. Press b. An hour digit blinks. 4. Press Z or a to set the hour. 5. Repeat steps 3 and 4 to set hours and minutes. Controls equipped with RF clock won't allow you to enter the time and day, see 2.10. 1 2 3 4 5 6 7 The set temperature is permanently maintained. You can exit this mode by selecting another operation mode k j l ß. Note : The Instat 868 (868 MHz) could not be used with the receivers of the INSTAT 6 (433 MHz) series. 1 2 3 4 5 6 7 The selected temperature is enabled immediately for the 1 2 3 Temperature can be permanently changed by programming manual operation A 1 2 3 4 5 6 7 1. Press Y and select ß. The pre-set number of days is displayed, e.g 1 (1 day). 2. Press Z or. a to change the day counter. 3. Press b The temperature blinks. 4. Press Z or a to change the temperature (if required). 5. Press b to confirm. Otherwise after 5 sec here will be a auto-accept. The number of set days is displayed. Afternoon INSTAT 868-r Weekly Programme Daily Programme Manual operation Party/Boost Holiday Noon k j A l ß This function allows the selction of a temperature (5 ... 40°C) for a certain number of days (1 ... 199). Once such period has elapsed, the control will switch to the weekly programme at 12.00 a.m. of the last day. Morning User's and Installation Manual 1. Press b The set-back temperature is displayed for a few seconds. The arrow is by s 2. Press Z or a to set the temperature (if required) 3. Press b to confirm. Otherwise after 5 sec here will be a auto-accept. Additional Programming Details a) In addition to single days of the week, you can also set blocks of days. All the days in a block are set to the same switching times and temperatures. The following blocks are available: (the arrow blinks by all these days) 2.2 Setting time/day 3 1.6 Holiday Function ß When you leave the house and the automatic programme is enabled The following operating modes can be selected by pressing Y: Early Morn. 468 931 002 948 Exit Enabling the protection: 1. Press and hold down key b then press also Z. Release Z first, then b. 2. z is displayed. Now the values can not be changed any more. Disabling the protection: 1. Press and hold down key b then press also a. Release a first, then b. 2. z disappears. Now you can enter values again. 2.8 ON / OFF function By pressing b for 5 Sec. the INSTAT 868-r can be switched ON and OFF. ISwitching OFF Press b for 5 Sec. OFF will be displayed instead of the time Switching ON Press b for 5 Sec. The time will be displayed instead of OFF . 4. Use 2.9 Changing the batteries When the icon appears, the batteries should be replaced within the next days. Insert the new batteries in the battery compartment on the back of the housing. Check for correct polarity. Use only the batteries indicated under item 10 "Specifications”. After changing the batteries, the time and day should be adjusted again (this is automatic in those controls equipped with an RF clock); all the remaining settings are maintained. Dispose of the batteries in compliance with the relevant regulations in force. 2.10 RF clock It is not necessary to enter the time and day for the controls equipped with an RF clock. The control will automatically switch from summer to winter. After energising the control, the time will be acquired by radio signal. The icon {. will appear on the lower right side of the display. The current time is displayed after ~3 minutes. If the RF clock is enabled (icon { displayed on the screen), it is not possible to enter the time and day manually. The time will be adjusted every day at 3 o'clock by radio signal. If the time cannot be automatically acquired, the { icon will disappear after ~10 minutes. The display will show 0:00, and now the time can be set manually. Every 3 hours the radio control will try to automatically update the time. 2.11 Cleaning Use a soft, damp cloth and a mild detergent. 3. Tips, Tricks, Troubleshooting If certain days don't fit the regular setting of the weekly programme: Use the separate daily programme j. There you can programme the switching times and temperatures required for this specific day. If you leave the house during these days, press Y to switch to the daily programme j. You would like to go on holidays and ensure the highest possible energy saving during this period. Use the Holiday function, see 1.6. You would like to keep the temperature at a certain value till further notice. Use the Manual operation, see 1.1. You would like to change the temperature for a limited period of 3 hours. Use the Party function, see 1.5. You leave the house and would like that the temperature returns to your usual values at the next programmed time. Use the Manual operation, see 1.1. You would like to go out in the evening The function Going out/Returning home allows an immediate temperature setback, see 1.2. 1. 2. 3. 4. 5. 6. 5. Features • Fuzzy-Control, with PWM output (Pulse-WidthModulation) • Optimum Start (the desired temperature is reached within the set time), can be disabled. • 5 Pre-set programmes (with 2, 4, 6 switching times) • 3 adjustable temperatures (comfort, standard, night) • 2, 4, 6 selectable times per day, (each time can be assigned one of the 3 available temperatures), blocks of days can be used • An extra daily programme (for special cases, such as public holidays or when you go on holidays) in addition to the weekly programme • Manual Operation that enables: – changing the temperature until the next programme step – permanently changing the temperature • Going out/Returning home function for a quick temperature setback • ON/OFF function • Access protection • Holiday function (a certain temperature can be selected for a settable number of days) • Party/Boost function (to override the programmed temperature for a period of 3 hours) with manual temperature change • Operation hours counter (1 through 9999 hours, the heating requirement time is recorded) • It can be also used as an ON/OFF Controller (e.g. for oil or gas fired burners) • Pump/Valve protection (the output is enabled for 3 minutes daily), can be disabled • It can be used to set-back other simple roomstats with a set-back input • Room or setpoint temperature display, selectable • Temperature display can be offset (to meet individual needs) • Output can be manually switched on/off (for a quick functional check) • Changeover between heating and cooling (for floor cooling systems, there is no Optimum Start for cooling mode) • LCD-Display with clear, simultaneous indication of Room Temperature, Time, Day, Operating Mode, Time Zone, Temperature Zone • Menu-driven operation through 4 keys • Elegant design 6. Function Description Troubleshooting: 1. 2. 3. 4. 5. It gets warm too late: a) Do the programmed switching time and clock time agree? b) Is the Optimum Start Function enabled? See 6.7 c) Did the control have enough time (a few days) to acquire data on the room? d) Is the previous switching time sufficiently far to allow the warm-up time? The device won't accept any data input: Is the Access protection switched off? See 2.7 If need be, activate Reset, see 2.6 Reset all switching times and temperature to the factory-set values. see 6.15 "Erase" The display shows o o o or u u u . The temperature has exceeded the display range. The display will show z Learn Mode was not terminated, see 6.16. The Access protection is enabled, see 2.7 Enter the set values here Position 1 Position 3 Position 2 Position 4 k 6.2 Performance Instat 868-r... The electronic Room Temperature Control INSTAT 868 can be used to control the room temperature via: • Actuators for floor and convector heating systems • Oil and gas fired hot water heating systems • Circulating pumps • Heat pumps • Electric space heaters 1 j 3 5 The INSTAT 868 performs the remote control of actuators. Temperature can be acquired at the best location, as far as sensing is concerned, in the room. This makes additional energy savings possible. The actuators can be easily controlled from anywhere in the room or in the house. No wiring is required between transmitter and receiver. Power is supplied by two "long-lasting" batteries. The controller features a timer transmission signal. The builtin timer allows radio-controlling the temperature setback function of additional controllers by means of a RF receiver. Several receivers can be controlled by a single transmitter. The transmitter-receiver co-ordination is automatic, through the "Learn Mode" feature. Through the Learn Mode see 6.17, the transmitter and the receiver are syncronized. In this way, the influence of other INSTAT 868 controls is ruled out. The transmission frequency used is intended for these applications all over Europe. Transmission safety is ensured by special test procedures and repetitions. Transmission power is very low. It is much lower than that of a mobile phone. In addition, the transmitter will only be active every 10 minutes. This device requires one of the INSTAT 868 a1, a4 or a6 RFreceivers to control the user units. The INSTAT 868-rd is equipped with a DCF77 radio-controlled clock. 6.3 Setting the programmes The INSTAT 868 features 5 programmes, see table II. Programme Table The user can select one of these programmes to suit his or her lifestyle. If required, the switching times, temperatures and "number of switching times" can be adjusted. When you select a programme, the previously set "Number of Switching Times" and temperatures will be overwritten with the new settings of this programme. The switching times will remain unchanged. To select it, choose menu k, position 2 6.4 Setting no. of switching times According to the user's lifestyle, 2, 4, 6 Switching Times per day can be set. If, for example. P1 with 6 switching times is selected, the number of switching times can be adjusted, if required. 2 switching times per day (only the switching times for n and s are used). 4 switching times per day (the switching times for r and } are not used). 6 switching times per day (all switching times are used) When programming the switching times, the unavailable switching times will not be displayed. To select it, choose menu k , position 3 6.5 Control action 6.1 Setting controller features The controller features can be set through menu items. To access a menu, select one of the operating modes (k j A l ß). The relevant features are shown in Table III. Note: Record the selected settings on the chart below, for later tests. Hand over the instructions together with these records to your customer. Checking the features: Call the menu by: 1 Press Y and select the required icon (k j A l ß). See Table III. 2. Press and hold down key b, then press also Y . Release Y, first, then b . The currently valid settings are displayed (see Table III). 3. Press Y to exit. Changing the settings: Call the menu by: 1. Press Y and select the required icon. (k j A l ß). See Table III. 2. Press and hold down key b then press also Y . Release Y, first, then b . 3. The currently valid settings are displayed (see Table III). The first position in the menu blinks. Record these values on the chart left side (if not already done) 4. Press b to move to the required position, re-adjust the previous values, if required 5. Press Z or a to set the desired digit. 6. Press b until you exit the menu. If you exit the menu by pressing Y, the settings will not be stored. For PWM (setting: j position 1 = 0, see 6.1) The control calculates a control value from the difference between setpoint and actual temperature, according to an intelligent control algorithm. This value is output as variable Pulse/Pause ratio (Pulse-Width-Modulation). The control algorithm used tries to keep room temperature constant. For that purpose, a reduced amount of heat needs to be supplied even after the setpoint temperature has already been reached. The sum of Pulse and Pause times is constant and equal to 10 minutes. If temperature difference is greater, the control is permanently switched on or off, for example for temperature setback. Behaviour of Puls-Pause-Ratio according to Temperature Pulse-Pause-Ratio 100% continuously on Note: a) The maximum limit up to which the controller can extend the pre-heating time is the previous switching time. b) At the first start-up, after the function "Erase or MasterReset" or at the beginning of the heating period, the control still does not have any valid parameters. For this reason, it is possible that during the first pre-heating stage the setpoint temperature is not reached within the programmed time. Adjusting to the specific room conditions can take several days Note: Vale protection is active even if the controller is switched off via function 2.8. 6.9 Temperature display If the temperature exceeds the high or low limit of the display range, the writing "ooo" or "u u u" respectively will be displayed". Temperature is measured and displayed every 10 minutes. For quick measuring purposes, after a key is pressed the temperature will be updated every 15 seconds for 10 minutes. If the temperature displayed by the control does not meet the expectations, it can be adjusted according to the relevant environmental conditions. (see 6.10) 6.10 Temperature display offset A variation in steps of 0.1 degrees for -4.0 ...+15 degrees is possible. Set-up procedure: 1. Make sure the controller has been operating for at least 1 hour. 2. Measure room temperature using a thermometer you trust (directly nearby the INSTAT 868, ~1 cm away from the wall). 3. Set the INSTAT 868 temperature to the measured temperature by: 3.1 Select menu l, set position 3 to 1 (See 6.1). 3.2 Press key b Room temperature is displayed and blinks. 3.3 Press Z or a to set the desired temperature. 3.4 Press b to confirm. The modified room temperature is displayed. To cancel the change: 1. Activate Reset, see 6.15 2. While only the above row is displayed (no temperature), set position 3 in Menu l to 1, see 6.1. 3. Press b to confirm. The temperature display disappears. After ~2 minutes, the unchanged temperature will be displayed. 6.11 Switching between heating and cooling The INSTAT 868 can also be used for cooling (for example, for floor cooling) (only cooling). The Optimum Start and the temperature limiting function are not available in this case. Setting: menu A , position 3, see 6.1 P is displayed permanently indicating that cooling mode is active. 6.12 Switching the output on and off manually To carry out a quick test, the output relay can be manually switched on/off by pressing a key. Setting: menu l , position 4, see 6.1 After ~15 seconds the output returns to normal operation. 6.13 Displaying room or setpoint temp. 0% Setpoint Temperature Output signal 10 min 10 min 10 min 10 min You can select if room or setpoint temperature should be permanently displayed. Setting: menu A, position 2, see 6.1 6.14 Displaying operation hours For ON/OFF control setting see: j position 1 = 1, see 6.1 If the setpoint temperature is not reached, the output switches on, if the setpoint temperature is exceeded, the output switches off again. This change-over occurs at least every 10 minutes (if room temperature is constant). On This display allows reading the number of hours during which heat was requested by the control. Inquiry: menu ß, see 6.1 The hours will be displayed for as long as the keys are pressed. The hours are counted starting from the last "Erase" see 6.15. The counter is not affected by the display function! Entire hours are displayed, for example 010 = 10 hours. 6.15 Erase/Reset III. Controller features Off Feature Menu Position Default Value Fixed Programme k k 1 2 Room P1 Switching times per day Valve protection k 3 6 k 4 On Control action display U j 1 PWM j 2 don't show U free j 3,4 – 1 1 3 5 2 6 0 1 0 1 0 1 – = = = = = = = = = = = = Room P1, 2 = P2 P3, 4 = P4 P5 2 sw. times, 4= 4 sw. times 6 sw. times Off On PWM, On/Off dont show U show U Number Setpoint Temperature 1 2 6.6 PWM or ON/OFF Control 3 4 5 6 Pulse-Width-Modulation is the best procedure, since it allows reaching a "quasi constant" behaviour of the controlled system. PWM is specially suitable for electric heating, pump control or when electrothermal actuators are used. In those cases where a frequent switching of the actuating element is to be avoided, such as direct burner control, or in those applications where the fact of exceeding or falling below a temperature is reported, the ON/OFF control should be used. 7 6.7 Optimum Start Optimum Start A 1 On Room or Setpoint temp. display Heating/Cooling change-over b key as going out/ret. home A 2 Room temperature A 3 Heating A 4 disabled Learn Mode l 1 - 1 = automatic address 2 = manual address free Temperature offset Relay on/off l l 2 3 – l 4 – 1 0 1 0 Operation hours counter ß – 0 1 0 1 0 1 0 1 = = = = = = = = = = = = Off On Room temperature Setpoint temperature Heating Cooling disabled enabled offset no offset Relay on, Relay off is displayed as long b is pressed 8 9 10 11 12 13 14 15 16 The device automatically determines the time when the heating process must begin in order to reach the required room temperature within the set time. Setting: menu A , position 1, see 6.1 The control calculates the pre-heating time from the time of the last heating-up based on the current temperature difference (see notes a, b). The Optimum Start applies only to the heating-up stage. The device is switched off (in the lower temperature direction) at the programmed moment. For PWM: During the heating-up stage, 100% heat is required. Immediately before reaching the setpoint temperature, the control changes to proportional heat demand. For ON/OFF control: 100% heat is supplied until the setpoint temperature is reached. After that, heating is switched off. 9. Common Data Ordering name EDP Number Operating voltage 6.16 Display the symbol U It can be selected if the symbol is displayed or not. In mode heating, the symbol U shows the state of the relay. If “control action” = PWM, the symbol may change each 10 Min. To select: choose menu j position 2 see 6.1 Battery life expectancy Transmission frequency Radio permits Aerial Additional Antenna Transmission interval 6.8 Valve protection The valve protection function prevents the valve from sticking (due to deposits of particles), for example during summertime. Such function will be enabled every day at 10.00 a.m. The valve will be turned on for ~3 min. (heating) or 7 min. (cooling). This function is active also during the normal heating operation. This function should be switched off if electric heating is used. Setting: menu k, position 4, see 6.1 control value continuously off Master Reset: To reset everything to the initial state, carry out an operating mode reset first and then an erase procedure. Reset: When unexplained results occur, the reset key should be pressed. All data is maintained, except for the time and day of the week. To activate Reset: Using a pointed object press the button in the hole between the x keys. After Reset, you must enter the time and day again. Erase : Used to restore the factory-set switching time and temperature settings. The following settings are affected: – Operation hours counter = 0 – Switching times and temperatures = standard values – time, day = 0:00, Mon – Optimum Start parameters = standard values 6.17 Learn mode This function allows making the radio connection between the transmitter and the receiver (for the relevant details, refer to the description of the receiver). 1. Setting through menu l see 6.1 - position 1 = 1: with automatic address TheINSTAT 868-r auto assigns the address - position 1 = 2: with manual address input The address can be manually entered 2. Press b to confirm. The display will show the icon z. Learn Mode is enabled now. 3. Only if the radio connection has been made successfully (see receiver) 4. Press b to exit. Only one transmitter at a time can be in Learn mode. Typical range Setpoint temperature setting Actual temperature display range Operating temperature Storage temperature Control algorithm Output signal PWM cycle duration Holiday function Timer Display Setting the address manually When selecting position 1 = 2, the last entered address will be displayed Press Z or a to set the desired address, digit by digit, and press b to confirm each digit. After the last digit has been entered the z icon will appear on the display. Carry out steps 3 and 4 above. Display size Digit size INSTAT 868-r INSTAT 868-rd 0536 20… 0536 25… Batteries: 2 LR6-size alkaline batteries, 1.5V each, total=3V ~5 years 868,95 MHz see below internal ZA 193 771 < 10 Minutes (data are sent repeatedly) 100 m in fee air or 1 ceilings or 3 walls 5...40°C, in steps of 0.5 K 0 … 60°C, in steps of 0.1 K 0…40°C –20…60°C Fuzzy (similar to PID) / ON/OFF Pulse-width-modulated (PWM)/ ON/OFF ~10 min (sum of on and off time of Pulse-Width Modulation PWM) 5...40°C, in 0.5° steps settable 1 to199 days LCD display with simultaneous indication of: Time, Room Temperature, Day, Operating Mode, Time Zone and Temperature Zone 41 x 32 mm (b x h) 12 mm for Temperature, 9 mm for Time Clock Display mode 24-hour, 1-minute steps Precision <10 min/year (at 20°C), RF clock: atomic precision (DCF 77) minimum swtich. time 10 minutes Temperature sensor NTC (built-in), Operation hours counter 1 to 9999 hours Housing protection rating IP 40 Device protection class III Humidity class keep away from dew Weight (without batteries) ~100g Choose a unique number as address (room number) that is not repeated throughout the whole building. Write this number on the rating plate located on the back of the control. 7 Installation Mounting The control should be mounted in a location of the room that: • is readily accessible for operation purposes • is free from curtains, cabinets, shelves, etc. • allows free air circulation • is not subject to direct sun radiation • is not subject to air currents (for example window/door opening) • is not directly affected by heat sources • is not on an external wall • is located at ~1.5 m above the ground • is not close to e.g. radio, television, or other radio equipment 10 Dimensions To fix it, use the wall support and secure it on the wall by using either screws or adhesive tape. If you use adhesive tape, make sure the wall surface is smooth and free from dust and grease. It is not possible to open the control. 8 Start-up 1. 2. 3. 4. Install the control, see 7. Remove the covering strip of the batteries Set the time, see 2.2 (for controls with RF clock see 2.10) Make the radio connection, see 6.17 (see also the instructions of the receiver) 5. Set the remaining features, see Table III. 6. Customise the programme (if required) see 2. Wall support The control is now ready to operate It will work according to the standard programme P1 see table II. Note: a) The room temperature will be displayed after about 1 minute. The exact room temperature is displayed after ~half an hour. b) For controls equipped with an RF clock, see 2.10. Note : The Instat 868 (868 MHz) could not be used with the receivers of the INSTAT 6 (433 MHz) series. A radio authorisation is available for the following countries: Germany, France, England, Belgium, Holland, Luxembourg, Norway, Denmark, Sweden, Switzerland, Finland, Spain, Italy, Austria, Ireland, Iceland, Portugal. Attention: A completely noise-free operation of the radio communication cannot always be guaranteed at the present state of the art. We therefore recommend checking the proper operation of the device in the specific installation location. Application examples for INSTAT 868-r Four independent heating circuits are controlled by 4 thermostats and one INSTAT 868 a4 or -a6 receiver. Heating distributor Thermostat Thermostat 230 V Thermostat Receiver Thermostat To activate the erase function: 1. Using a pointed object press the button in the hole between the x keys, and the b button simultaneously, 2. release x and after ~2 seconds release b. Now you must enter the time and day again Operating mode reset: Warning: This command will reset the "Control mode" feature to PWM. If required, set it to On/Off control. All functions described in Table III - Features, are reset to the pre set values To activate this function: 1. Press Y, Z and x simultaneously 2. Release x first and, after ~2 seconds the Y and Z buttons, Now, all icons on the display are active. 3. Press x. 230 V Two separate INSTAT 868-a1 receivers are controlled by one thermostat. Thermostat Receiver Receiver 2 3 0 V
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
advertisement