Beckett CG4 Gas Burner Guide to Power
Beckett CG4 Gas Burner is a versatile and reliable device designed to provide efficient and controlled heating solutions for various applications. With its advanced features and capabilities, it offers precise temperature control, improved fuel efficiency, and enhanced safety measures. Whether you're looking to heat your home, business, or industrial space, the CG4 burner delivers exceptional performance and ease of use.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
FOR
THE
HEATING
PROFESSIONAL
Guide
to
Power Gas
Burners
Table of Contents
5 — Safety Check-off List
5 — Recommendations
5 — When Converting from Oil to Gas
6 — Installation
6 — Flue Pipe
8 — Thermal Safety Switch
8 — Draft Regulator
8 — Stack Temperature & Carbon Monoxide
8 — Carbon Monoxide Signs & Symptoms
10 — Combustion Air Requirements
10 — Indoor Combustion Air
10 — Outdoor Combustion Air
10 — Gas Piping Installation
11 — Gas Supply Piping
13 — Propane Installations
16 — Wiring with the Beckett GeniSys 7590
17 — 7590 to AquaSmart 7600A & Thermal Safety Switch
18 — 7590 to Honeywell L4006 (or similar) & Thermal Safety Switch
19 — 7590 to Honeywell Pressure Switch & McDonnell/Miller 67 (or similar) Low Water Cut-off & Thermal Safety Switch
20 — 7590 to Hydrolevel Safeguard Low Water Cut-off & Honeywell Pressure Switch & Thermal Safety Switch
21 — 7590 to McDonnell & Miller Probe Low Water Cut-off & Honeywell Pressure Switch & Thermal Safety Switch
22 — 7590 to HydroStat & Thermal Safety Switch
23 — 7590 to Honeywell L7224U & Thermal Safety Switch
24 — 7590 to Honeywell L8124A & Thermal Safety Switch
25 — 7590 to Honeywell L8148A & Thermal Safety Switch
26 — Placing the Burner in Service
26 — Starting a Burner for the First Time
27 — Verify the Firing Rate
28 — Check Operation and Safety Controls
28 — Setting Combustion
29 — Recommended Combustion Adjustment Procedure
2
Before Calling a Manufacturer’s Tech Service . . .
Before contacting us about your burner, you must have a completely filled out copy of the
Contractor Start-Up Form (Located inside of last page). This information is crucial for troubleshooting and obtaining the correct replacement parts.
Please refer to the latest edition of the Beckett CG4 gas burner manual for complete specifications and installation instructions regarding the Beckett CG4 burner. The procedures in this document should be used as a supplement to the equipment manufacturer’s recommended installation and service instructions and do not preclude other accepted guideline documents on good industry practice.
This is a guide to power gas burners; it is not intended to supersede the appliance or burner manufacturer’s published specifications. Always follow the appliance or burner manufacturer’s published instructions, wiring diagrams and recommendations.
For technical assistance please call 1-800-645-2876 (8:00am - 5:00pm EST, Mon-Fri)
Guide to Power Gas Burners
3
ANSI Z21.17 Gas Conversion Burner Standard, requires specific warnings to be placed on the cover of all instruction manuals for gas conversion burners.
Below are examples of these types of warnings which must be understood and followed.
Fire, Explosion or
Carbon Monoxide
Poisoning Hazard
Fire or Explosion Hazard
Can cause severe injury, death or property damage
If the information in these instructions is not followed exactly, a fire or explosion may result causing personal injury, death or property damage.
─ Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
─ WHAT TO DO IF YOU SMELL GAS y Do not try to light any appliance y Do not touch any electrical switch; do not use any phone in your building.
y Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
y If you cannot reach your gas supplier, call the fire department.
─ Installation and service must be performed by a qualified installer, service agency or the gas supplier.
This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. (In Canada, in accordance with the requirements of the CAN/CGA-B149 Installation Codes.) If the information in these instructions is not followed exactly, a fire, explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life. The qualified service agency is responsible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer’s instructions supplied with the kit.
4
Safety Check-off List
Recommendations
Follow installation manual instructions.
Verify incoming gas pressure.
Verify the BTU rating of gas meter.
Verify that the pipe size meets the input BTU rating of the appliance (Reference Tables 4,5,6 & 7 in following pages).
Verify combustion air supply meets code requirements (consult local authorities for prevailing codes).
Verify area around appliance is free of lint or pet hair.
Verify condition and size of chimney and venting. Venting must comply with code, including construction, size and liner requirements.
Verify condition and routing of smoke pipe. Total length should be as short as possible (Note the quantity of ells, tees and location of draft regulators).
Verify type of draft regulator.
Verify clearances to combustibles, including chimney connector, burner, and appliance.
NOTICE: A manometer and combustion analyzer are required tools for proper installation and adjustment.
When Converting from Oil to Gas
Thoroughly clean heat exchanger of appliance.
Replace chamber kit.
Seal up boiler sections, clean out plates and boiler mounting plate.
Install double action draft regulator.
Install thermal safety switch (Ex. Field Controls GSK-3 or similar).
Adjust burner to operate at no less than 90% of input of the appliance rating plate (GPH x 140,000 x .9 = lowest
BTU firing rate).
Stack temperature must be set for a minimum of 325°F or appliance manufacturer’s recommended setting.
Failure to maintain proper stack temperature could result in flue gas condensing and cause chimney damage which could result in CO leakage into dwelling.
Guide to Power Gas Burners
5
Installation
Flue Pipe
The flue pipe should be same size as the breech connection on the appliance. For modern units this should cause no problem in sizing the flue pipe.
• Please reference appliance instruction for chimney size.
• Chimney liners may be required by local code.
Figure 1 - Venting Single Appliance with Power Gas Burner
BEST
Barometric Draft Control
Flue Pipe
Heating Unit
Chimney
Chimney Liner
6
Poor location for Draft
Regulator, due to combustion noise
Barometric
Draft Control
Draft Regulator should not be installed in a bullheaded tee.
Strongly recommend ells or 45°.
Barometric
Draft Control
Figure 2 - Venting Multiple Appliances with Power Gas Burners
BEST
7”
Flue Pipe (all pipe must be round)
Chimney Liner
Chimney
10” Manifold
7” 6”
12” Manifold
45° Entry
Barometric
Draft Controls
Heating
Units
This arrangement may cause resonance.
7” 7”
12” Manifold
6”
Guide to Power Gas Burners
7
Thermal Safety Switch
Some local codes and gas utilities require the installation of a thermal safety switch on the doubleacting draft regulator, or draft hood. This is a recommended practice and provides the following protection:
The thermal safety switch senses flue gas spillage caused by blocked flue exhaust, prolonged down-draft, or insufficient draft. The safety is wired in series with the burner control circuit. When the spillage of hot flue gases is detected it will shut off the burner.
For thermal safety switch application details, go to www.fieldcontrols.com
.
See wiring section of this Guide Book for sample wiring locations of a Thermal Safety Switch.
Draft Regulator
When converting from oil to gas, the draft regulator must either be replaced or newly installed. It shall be a double-acting type, agency recognized for use with gas vent systems, such as Field Controls MG-1, or equivalent. (ANSI 21.8 “Installation of Gas Conversion
Burner”)
Stack Temperature & Carbon
Monoxide
stack temperature could result in flue gas condensing and cause chimney damage which could result in CO leakage into dwelling.
◦ The above warning regarding stack temperature is one that you will find throughout instruction manuals for gas appliances or gas burners. Installation and adjustment of a gas burner has critical steps that
must not be taken lightly. Each year thousands of people are affected by carbon monoxide (CO) poisoning.
◦ High CO readings are the result of improper application, lack of combustion air, and/or improper ratio of air to fuel. Merely adjusting a fire “by eye”
is not acceptable. A properly maintained, calibrated electronic combustion analyzer must be used to make final adjustments.
◦ Dew point is another factor in combustion which must be considered while finalizing adjustments (some combustion analyzers can calculate this). Flue gases will condense below the dew point. Dew points are inversely proportional to the percentage of excess air.
As an example, the dew point of natural gas at 6%
O2/40% EA is approximately 130°F. Flue gases may condense within the flueways when heat exchanger temperatures are at or below the calculated dew point.
Chimneys and connectors may also be subjected to condensation.
◦ Figure 3 shows that gas fuels have higher dew points than oil or coal, so greater care must be taken with them to avoid condensation.
◦ Please see charts on the following page.
Carbon Monoxide Signs & Symptoms
Carbon monoxide is toxic to all aerobic forms of life.
It is easily absorbed through the lungs. Inhaling even relatively small amounts of the gas can lead to hypoxic injury, neurological damage, and even death. Different people and populations may have a different carbon monoxide tolerance levels. On average, exposures at
100 ppm or greater is dangerous to human health. In the United States, the OSHA limits long-term workplace exposure levels to less than 50 ppm averaged over an
8-hour period; in addition, employees are to be removed from any confined space if an upper limit (“ceiling”) of 100 ppm is reached. Carbon monoxide exposure may lead to a significantly shorter life span due to heart damage. The carbon monoxide tolerance level for any person is altered by several factors, including activity level, rate of ventilation, a pre-existing cerebral or cardiovascular disease, cardiac output, anemia, sickle cell disease and other hematological disorders, barometric pressure, and metabolic rate.
The acute effects produced by carbon monoxide in relation to ambient concentration in parts per million are listed in Table 2.
8
Figure 3
Flue Gases
Average Dew Point for Typical Fuels
150
140
130
120
110
100
90
0 10 20 30 40 50 60
Excess Air (%)
70 80 90 100
Manufactured Gas
Natural Gas
Oil
Table 1 - Combustion Efficiency (%) for Natural Gas*
Air
9.5
15.0
28.1
44.9
Excess %
Oxygen
2
3
5
7
200
85.4
85.2
84.7
84.1
300
Net Stack Temperature (°F)
400
83.1
80.8
500
78.4
82.8
82.1
81.2
80.4
79.5
78.2
77.9
76.7
75.2
*This is typical data. Results will vary with air and fuel properties.
600
76.0
75.4
74.0
72.1
Table 2 - Carbon Monoxide Effect on Human Body
Concentration Symptoms
35 ppm (0.0035%) Headache and dizziness within six to eight hours of constant exposure
100 ppm (0.01%) Slight headache in two to three hours
200 ppm (0.02%) Slight headache within two to three hours; loss of judgment
400 ppm (0.04%) Frontal headache within one to two hours
800 ppm (0.08%) Dizziness, nausea, and convulsions within 45 min; insensible within 2 hours
1,600 ppm (0.16%) Headache, tachycardia, dizziness, and nausea within 20 min; death in less than 2 hours
3,200 ppm (0.32%) Headache, dizziness and nausea in five to ten minutes. Death within 30 minutes.
6,400 ppm (0.64%) Headache and dizziness in one to two minutes. Convulsions, respiratory arrest, and death in less than 20 minutes.
12,800 ppm (1.28%) Unconsciousness after 2–3 breaths. Death in less than three minutes.
Guide to Power Gas Burners
9
Combustion Air Requirements
Indoor Combustion Air
In many cases, a burner operating in an indoor space of a conventional frame, brick or stone building will receive adequate air supply from leakage in the building itself. The standard method for determining the required indoor room volume is 50 cu.ft. per 1000 Btu/hr for the total input rating of all appliances in that space (in accordance with NFPA 54).
EXAMPLE: A basement has a 90,000 Btu/hr gas burner and a 30,000 Btu/hr water heater. The total input is
120,000 Btu/hr. The required space is:
1,000 Btu/hr
= 6,000 cu. ft.
The volume calculation above may include adjacent rooms provided the room is connected by 2 openings
(not furnished with doors). One opening must be within
12 inches from the top, and one opening 12 inches from the bottom of the enclosure. Each opening must have a minimum free area of 1 sq. in. per 1000 Btu/hr, but not less than 100 sq. in.
From the previous example: The total input rate for all air using appliances was 120,000 Btu/hr. The opening size must be:
120,000 Btu/hr
1,000 Btu/hr
1 sq.in. = 120 sq.in.
Each opening should be 120 sq. in.
For the Known Air Infiltration Rate Method or combining spaces on different levels, refer to NFPA 54.
Outdoor Combustion Air
If the burner is located in a tightly constructed building where there is inadequate outside air infiltration, outside combustion air must be supplied by some other means.
One method to accomplish this is through 2 permanent openings in an exterior wall. The openings must begin
12 inches from the top, and one opening 12 inches from the bottom of the enclosure. If directly connecting to the outdoors, or through vertical ducts, each opening must have a free area of 1 sq.in. / 4,000 Btu/hr of the total input rating of all appliances in the space. For horizontal ducts connecting to the outdoors, each opening must have a free area of 1 sq.in. / 2,000 Btu/hr of total input ratings for the space.
10
Another method is to supply outside air directly to the gas burner through round, smooth duct work (see
Figure 4). Some manufacturers offer accessories which allow outside combustion air duct work to be coupled to the gas burner. These kits must meet the Engineered
Installation requirements of NFPA 54 and be approved by authorities having jurisdiction. It is important that you comply strictly with the manufacturer’s instructions.
Refer to NFPA 54 for additional methods such as One
Permanent Opening (Outdoor) Method, Combination
Indoor/Outdoor Method, and Mechanical Air Supply
Method.
Gas Piping Installation
Below is an example of a warning that will be in a gas burner installation manual.
Install a Drip Leg in Gas
Supply Piping
Foreign matter could lodge in gas valve cutoff seals, resulting in gas leak-through, explosion or fire.
Install a full-size drip leg or dirt pocket in the piping directly ahead of the main shutoff valve to capture foreign matter.
When installing gas piping to a conversion gas burner or gas appliance, a drip leg is required to help keep particles/grit from getting in the gas valve. Please see
Figure 5 for the proper location of a drip leg.
Gas Supply Piping
Figure 5 - Typical Gas Piping Layout
TC
DL
MSC TEE U GV
Abbrev.
MSC
TC
U
GV
DL
KEY
Item Description
Main Shutoff Cock
Test Cock
Union
Gas Valve
Drip Leg
BURNER
Table 3. Natural Gas Supply Piping Capacity
◦ Schedule 40 metallic pipe with 0.50 psi or less inlet pressure and 0.30” W.C. pressure drop
◦ Maximum capacity in cubic feet of gas per hour (CFH). Natural gas with 0.60 specific gravity.
Pipe Length (ft.)
100
110
120
150
70
80
90
10
20
30
40
50
60
1/2
”
132
38
34
31
28
46
43
40
92
73
63
56
50
3/4
”
278
79
72
64
59
96
90
84
190
152
130
115
105
Pipe Size (inches)
1
”
520
180
170
160
150
130
120
110
350
285
245
215
195
11/4
”
1050
370
350
320
305
275
250
225
730
590
500
440
400
Guide to Power Gas Burners
11/2
”
1600
560
530
490
460
410
380
350
1100
890
760
670
610
11
12
Figure 6 - Natural Gas Piping
Sizing must consider the full load.
Size Section A/B for total of 1+2+3+4
Size Section B/C for total of 2+3+4
B
3
Range
45,000 BTU/hr input
C D A
House Gas
Meter
1
Clothes Dryer
30,000 BTU/hr input
2
Boiler
140,000 BTU/hr input
4
Water Heater
55,000 BTU/hr input
This is an example of the Longest Length Method (Reference “ Table 3. Natural Gas Supply Piping Capacity” on page 11, 90’ pipe length row):
◦ Consider that the longest length is 85 feet.
◦ Add BTU input for all appliances in the system to determine maximum load.
◦ Section A-B = 270,000 BTU/hr input. The 320 value listed in the table will cover the 270,000 load on this segment. Following this column to the top, 1.25” will be the correct pipe size.
◦ Section B-C carries 240,000 BTU/hr after we subtract the Clothes Dryer. The 320 value listed in the table is still needed to cover this load and following this column to the top, 1.25” will again be the correct pipe size.
◦ Section C-D carries 100,000 BTU/hr after subtracting the Boiler. The 160 value is needed to cover this load and following the column to the top, 1.0” will be the correct pipe size.
◦ Sizing each branch to the 90’ pipe length, Branch 1 (30,000 BTU/hr) will be 0.5”. Branch 2 (80,000 BTU/hr) will be 0.75”. Branch 3 (45,000 BTU/hr) will be .75” pipe and Branch 4 will need .75” pipe.
The methods used above and additional information can be found in NFPA 54,
National Fuel Gas Code.
Propane Installations
To convert the burner to propane simply purchase the proper sized restrictor and follow the instructions.
Pressures and set up are exactly the same once the restrictor is installed.
Make certain that supply piping is properly sized. There are two supply sizes to consider with propane, the line from first to second stage regulator and then from the second stage regulator to the burner gas valve.
Regulators, tank and line sizes must be correct. If in doubt consult the propane supplier for assistance.
Use the charts below for line sizes. Additional information can be found in NFPA 58, Liquefied
Petroleum Gas Code.
Table 4 - First Stage Pipe Sizing (Between First and Second Stage Regulators)
10 PSIG inlet with a 1 PSIG Pressure Drop, maximum capacity of pipe or tubing in thousand of BTU/hr for LP-Gas
Size of Pipe or
Copper Tubing,
Inches
3/8
1/2
5/8
3/4
1/2
3/4
1
1-1/4
1-1/2
2
10
558
1,387
2,360
3,993
3,339
6,982
13,153
27,004
40,461
77,924
20
383
870
1622
2,475
2,295
4,799
9,040
18,560
27,809
53,556
30
309
700
1,303
2,205
1,843
3,854
7,259
14,904
22,331
43,008
40
265
599
1,115
1,887
1,577
3,298
6,213
12,756
19,113
36,809
Length of Pipe or Tubing, Feet
50
235
531
988
1,672
1,398
2,923
5,507
11,306
16,939
32,623
60
213
481
896
1,515
1,267
2,649
4,989
10,244
15,348
29,559
70
196
443
824
1,394
1,165
2,437
4,590
9,424
14,120
27,194
80
182
412
767
1,297
1,084
2,267
4,270
8,767
13,136
25,299
90
171
386
719
1,217
1,017
2,127
4,007
8,226
12,325
23,737
100
161
365
679
1,149
961
2,009
3,785
7,770
11,642
22,422
Size of Pipe or
Copper Tubing,
Inches
3/8
1/2
5/8
3/4
1/2
3/4
1
1-1/4
1-1/2
2
125
142
323
601
1,018
852
1,780
3,354
6,887
10,318
19,871
150
130
293
546
923
772
1,613
3,039
6,240
9,349
18,005
175
118
269
502
843
710
1,484
2,796
5,741
8,601
16,564
200
111
251
467
790
660
1,381
2,601
5,340
8,002
15,410
Length of Pipe or Tubing, Feet
225
104
235
438
740
619
1,296
2,441
5,011
7,508
14,459
250
90
222
414
700
585
1,224
2,305
4,733
7,092
13,658
275
89
211
393
664
556
1,162
2,190
4,495
6,735
12,971
300
89
201
375
634
530
1,109
2,089
4,289
6,426
12,375
350
82
185
345
584
488
1,020
1,922
3,945
5,911
11,385
400
76
172
321
543
454
949
1,788
3,670
5,499
10,591
Note:
1. For allowable pressure drops other than 1 psi, calculate the adjusted demand and then use capacities from the table.
Adjusted demand (BTU/hr.) = Actual Demand (BTU/hr.)
Table Press Drop (1 psi)
Desired Press Drop (psi)
Guide to Power Gas Burners
13
Table 5 - First Stage Polyethylene Plastic Tubing Sizing
10 PSIG Inlet with a 1 PSIG Pressure Drop
Maximum capacity of plastic tubing in thousands of BTU/hr of LP-Gas
Size of Plastic Tubing
NPS
1/2 CTS
1/2
3/4
1 CTS
1
1-1/4
1-1/2
2
SDR
7.00
9.33
11.00
11.00
11.00
10.00
11.00
11.00
10
1,387
3,901
7,811
9,510
14,094
24,416 n/a
66,251
20
954
2,681
5,369
6,536
9,687
16,781 n/a
45,534
30
762
2,143
4,292
5,225
7,744
13,416
20,260
36,402
40
653
1,835
3,673
4,472
6,628
11,482
17,340
31,155
Length of Pipe or Tubing, Feet
50
578
1,626
3,256
3,864
5,874
10,106
15,368
27,612
60
524
1,473
2,950
3,591
5,322
9,220
13,924
25,019
70
482
1,355
2,714
3,304
4,896
8,433
12,810
23,017
Size of Plastic Tubing
NPS
1/2 CTS
1/2
3/4
1 CTS
1
1-1/4
1-1/2
2
SDR
7.00
9.33
11.00
11.00
11.00
10.00
11.00
11.00
125
352
990
1,963
2,414
3,578
6,199
9,361
16,820
150
319
897
1,797
2,188
3,242
5,616
8,482
15,240
CTS = Copper Tube Size, SDR=Standard Dimension Ratio
175
294
826
1,653
2,013
2,983
5,167
7,803
14,020
200
273
778
1,539
1,872
2,775
4,807
7,259
13,043
Length of Pipe or Tubing, Feet
225
256
721
1,443
1,757
2,603
4,510
6,811
12,236
250
242
681
1,363
1,659
2,459
4,260
6,434
11,560
275
230
646
1,294
1,576
2,336
4,046
6,111
10,979
300
219
617
1,235
1,503
2,228
3,860
5,830
10,474
80
448
1,261
2,525
3,074
4,555
7,891
11,918
21,413
90
421
1,183
2,369
2,884
4,274
7,404
11,182
20,091
350
202
567
1,136
1,383
2,050
3,551
5,363
9,636
100
397
1,117
2,238
2,724
4,037
6,994
10,562
18,978
400
188
528
1,057
1,287
1,907
3,304
4,989
8,965
Table 6 - Second Stage or Integral Twin Stage Pipe Sizing
11 Inches Water Column Inlet with a 1/2 inch Water Column Drop.
Maximum capacity of pipe or tubing in thousands of BTU/hr of LP-Gas
Size of Pipe or
Copper Tubing,
Inches
7/8
1/2
3/4
1
3/8
1/2
5/8
3/4
1-1/4
1-1/2
2
10
49
110
206
348
536
291
608
1,146
2,353
3,525
6,789
20
34
76
141
239
368
200
418
788
1,617
2,423
4,666
30
27
61
114
192
296
161
336
632
1,299
1,946
3,747
40
23
52
97
164
253
137
287
541
1,111
1,665
3,207
Length of Pipe or Tubing, Feet
50
20
46
86
146
224
122
255
480
985
1,476
2,842
60
19
42
78
132
203
110
231
435
892
1,337
2,575
70 n/a
38
71
120
185
102
212
400
821
1,230
2,369
Size of Pipe or
Copper Tubing,
Inches
7/8
1/2
3/4
1
3/8
1/2
5/8
3/4
1-1/4
1-1/2
2
125
12
28
52
89
137
74
155
292
600
899
1,731
150
80
124
67
141
265
544
815
1,569
11
26
48
175 n/a n/a n/a n/a n/a
62
129
244
500
749
1,443
200
69
106
58
120
227
465
697
1,343
10
22
41
Length of Pipe or Tubing, Feet
225 n/a n/a n/a n/a n/a
54
113
213
437
654
1,260
250
61
94
51
107
201
412
618
1,190
9
19
36
275 n/a n/a n/a n/a n/a
48
101
191
392
587
1,130
80
16
36
67
113
174
94
198
372
764
1,144
2,204
90 n/a
33
62
105
161
87
185
349
717
1,074
2,068
100
14
32
59
100
154
84
175
330
677
1,014
1,954
300
8
18
33
182
374
560
1,078
55
85
46
97
350
167
344
515
992
51
78
43
89
7
16
30
400
156
320
479
923
47
73
40
83
7
15
28
14
Figure 7 - Propane Line Sizes
Sizing must consider the full load.
Propane
Tank
A
(First Stage
Regulator)
2 PSI
Pressure
Drop
50 ft.
(Second Stage
Regulator)
B
C
1
Clothes Dryer
30,000 Btu/hr
D
30 ft.
2
Furnace
100,000 Btu/hr
3
Range
70,000 BTU/hr
E
4
Water Heater
55,000 Btu/hr input
First Stage:
Section A-B = 255,000 Btu/hr demand and 2 psi allowable pressure drop. Use Table 4 to determine the copper tubing size. Calculate adjusted demand: 255,000 Btu/hr x 0.707 = 180,312 Btu/hr (see
Table 4, Note 1 on Pg. 13). In the 50ft. length column, choose a capacity that exceeds the adjusted demand. The capacity of 235,000 Btu/hr will meet the (adjusted) demand of 180,312 Btu/hr.
This corresponds to 3/8” copper tubing.
Second Stage: Using Table 6 and only the 30 ft. column (longest length method)
Section B-C = 255,000 Btu/hr demand requires 7/8” copper tubing or 3/4” pipe.
Section C-D = 225,000 Btu/hr demand requires 7/8” copper tubing or 3/4” pipe.
Section D-E = 125,000 Btu/hr demand requires 3/4” copper tubing or 1/2” pipe.
Section C-1 = 30,000 Btu/hr demand requires 1/2” copper tubing or 1/2” pipe.
Section D-2 = 100,000 Btu/hr demand requires 5/8” copper tubing or 1/2” pipe.
Section E-3 = 70,000 Btu/hr demand requires 5/8” copper tubing or 1/2” pipe.
Section E-4 = 55,000 Btu/hr demand requires 1/2” copper tubing or 1/2” pipe.
Guide to Power Gas Burners
15
This section of wiring diagrams is not intended to supersede the control/limits manufacturer’s published specifications. Always follow the appliance manufacturer’s published instructions, wiring diagrams and recommendations.
The below warning is typically found in instruction manuals of gas controls and gas appliances and must be understood and followed.
Electrical Shock, Fire,
Explosion and Burn Hazards
into operation only by a trained, licensed, qualified professional or service agency in accordance with the latest revision of the National Electric Code ANSI/ authorities having jurisdiction.
y Follow the appliance manufacturer’s wiring diagrams and note all safety controls.
y Typical safety controls include high temperature or pressure limits, low water cut-offs, anti-scald valves, pressure relief valves and water feed valves.
y Verify all limits and safety controls are installed and functioning correctly, as specified by the appliance manufacturer, applicable safety standards, codes and all authorities having jurisdiction.
y Provide ground wiring to the appliance, burner and controls.
Wiring with the Beckett GeniSys 7590
Figure 8 - Beckett GeniSys 7590 Control
Flame Rod 1/4” Terminal Connection
1/4” Terminal Connections
Status/Reset
Button
Communication
Port #1
Gas Valve & Transformer
Plug connection
16
Air Proving Switch
Plug Connection
LEDs T-T Terminals
7590 to AquaSmart 7600A & Thermal Safety Switch
Thermal Safety Switch
(GSK-3)
LOW Voltage
Guide to Power Gas Burners
Thermal
Safety Switch
(FTS-4)
LINE Voltage
17
7590 to Honeywell L4006 (or similar) & Thermal Safety Switch
Please carefully follow Honeywell’s manufacturer directions regarding installation, wiring, & service.
Thermal Safety Switch
(GSK-3)
LOW Voltage
Thermal Safety
Switch
(FTS-4)
LINE Voltage
18
7590 to Honeywell Pressure Switch & McDonnell/Miller 67 (or similar) Low
Water Cut-off & Thermal Safety Switch
Please carefully follow McDonnell/Miller’s manufacturer directions regarding installation, wiring, & service.
Thermal Safety Switch
(GSK-3)
LOW Voltage
Guide to Power Gas Burners
Thermal
Safety Switch
(FTS-4)
LINE Voltage
19
7590 to Hydrolevel Safeguard Low Water Cut-off & Honeywell Pressure
Switch & Thermal Safety Switch
Please carefully follow Hydrolevel’s and Honeywell’s manufacturer directions regarding installation, wiring, & service.
Thermal Safety Switch
(GSK-3)
LOW Voltage
20
Thermal Safety
Switch
(FTS-4)
LINE Voltage
7590 to McDonnell & Miller Probe Low Water Cut-off & Honeywell Pressure
Switch & Thermal Safety Switch
Please carefully follow McDonnel/Miller’s and Honeywell’s manufacturer directions regarding installation, wiring, & service.
Thermal Safety Switch
(GSK-3)
LOW Voltage
Guide to Power Gas Burners
Thermal Safety
Switch
(FTS-4)
LINE Voltage
21
7590 to HydroStat & Thermal Safety Switch
Please carefully follow HydroStat’s manufacturer directions regarding installation, wiring, & service.
Thermal Safety
Switch (GSK-3)
LOW Voltage
22
Thermal Safety Switch
(FTS-4)
LINE Voltage
7590 to Honeywell L7224U & Thermal Safety Switch
Please carefully follow
Honeywell’s manufacturer directions regarding installation, wiring, & service.
Thermal Safety
Switch (GSK-3)
LOW Voltage
Guide to Power Gas Burners
Thermal Safety Switch
(FTS-4)
LINE Voltage
23
7590 to Honeywell L8124A & Thermal Safety Switch
Please carefully follow Honeywell’s manufacturer directions regarding installation, wiring, & service.
Thermal Safety Switch
(GSK-3)
LOW Voltage
24
Thermal Safety Switch
(FTS-4)
LINE Voltage
7590 to Honeywell L8148A & Thermal Safety Switch
Please carefully follow Honeywell’s manufacturer directions regarding installation, wiring, & service.
Thermal Safety Switch
(GSK-3)
LOW Voltage
Guide to Power Gas Burners
Thermal Safety Switch
(FTS-4)
LINE Voltage
25
Placing the Burner in
Service
The gas burner must be installed and prepared for startup by a qualified service technician. After the burner installation is complete prepare the appliance for testing.
The following calibrated test equipment is required to properly install the appliance. Whether these are included in one kit or are individual test components, they should be calibrated and in good working order.
◦ A combustion analyzer capable of measuring oxygen (or carbon dioxide), carbon monoxide, stack temperature, ambient temperature, and appliance efficiency.
◦ Electrical multi-meter capable of measuring voltage, ohms, amps, and DC micro-amps for measuring the flame signal. These could be included in one meter or separate meters, but should be calibrated and accurate.
◦ Calibrated manometers and gauges capable of measuring all pressure ranges in the gas supply and appliance draft. This could typically range from a few
PSI to 0.1” W.C.
◦ Gas Leak detection equipment.
Attach a gas pressure manometer to the gas valve after purging air from the gas lines. Thoroughly leakcheck all fittings when purging is complete and after commissioning the burner.
Starting a Burner for the First Time
Before you start a burner for the first time, or re-start it after work has been done that would modify its electrical or fuel-handling systems it is important that you verify that it is safe to operate.
1. With the power and main gas supply to the burner turned off, make sure gas has not accumulated in the boiler or flues.
2. Examine the boiler room and make sure that there is an adequate supply of fresh air, that the appliance’s vent system is not obstructed and that stack connections do not show open leakage paths.
3. Examine the appliance and its wiring, piping, fuel supply, venting and water level (if applicable) to assure that they meet the appliance manufacturers requirements for operation.
26
4. Examine the fuel supply system and make sure that its connections are secure, that the gas pressure supplied to the gas train does not exceed the rating of the valves, and that the manual valve has the fuel shut off.
5. Examine the burner and make sure that its piping connections are secure, that any rate-establishing components (nozzles and orifices) are correctly installed and that air handling adjustments (shutter and band) are set to recommended initial settings
6. With the main shutoff cock closed, set the limit or controller to call for heat then apply power to start the burner.
7. In order to check the function of each component
(i.e.: control sequence, airflow proving switch, ignition transformer, gas valves, safety lockout timing, etc.), with the main shutoff cock closed, monitor a complete burner run sequence. Note the control will lock out. (see control instructions for sequence & how to reset).
8. If control operation sequence and fuction is correct turn off power and remove sensor wire from control.
9. Turn on power and fuel and initiate call for heat.
Verify that burner fires up and the gas valve closes.
After control locks out, flame shall go off.
10. Turn power off and reattach sensor wire. Turn power back on. Control should reset. Initiate Call for Heat.
11. After you have observed main flame for a brief time, press the reset button on the control for
1 second to shut down and re-start the burner.
Monitor the flame and safety shutoff valves to assure that shutdown is controlled by the valves and that they operate properly. With this test passed, you may safely initiate automatic start-ups on subsequent cycles.
12. While the burner is firing, examine the vent system for evidence of leaks, obstructions, and for correct function of the barometric draft control. Leak test all gas piping from the burner to the utility supply piping. If leaks are found, correct them immediately.
13. The burner is now ready to proceed to rate and combustion adjustments.
Verify the Firing Rate
The primary method for verifying the burner’s firing rate, for either natural gas or propane, is to assure that the correct fuel orifice is properly installed and that the gas valve outlet pressure is accurately set to 3.5” water column.
1. Turn off electrical power to the burner and close the main shutoff cock supplying gas to the burner.
2. Remove the plug from the outlet pressure tap on the outlet end of the gas valve ( Figure 9) and install a hose barb fitting and manometer.
3. Turn on system power and gas supply and initiate a call for heat to light the burner.
4. The manometer should show 3.5” water column pressure. If it does, turn off the burner and skip ahead to step 6. If it doesn’t, let the burner continue to run and adjust the gas valve pressure regulator in the following steps.
5. Remove the regulator cover screw (see Figure
9) from the regulator adjustment tower and turn the regulator adjust screw clockwise to increase pressure or counterclockwise to decrease pressure. Set the regulator to produce a 3.5” water column reading in the manometer. Check the appliance breech or draft setting and adjust if necessary as it can affect the setting. Replace the regulator cover screw.
6. Turn off the burner and turn off all electrical power to the system.
7. Remove the manometer hose and barb fitting from the gas valve outlet pressure tap.
8. Replace the outlet pressure tap plug and tighten
(clockwise 40 – 60 in-lbs.).
9. Turn on system power and start the burner.
10. Check for leaks at the gas valve outlet pressure tap plug using a leak detection solution or soapsuds.
Bubbles forming indicate a leak. SHUT OFF GAS
AND FIX ALL LEAKS IMMEDIATELY.
If the burner is firing natural gas it may be possible to verify the firing rate by “clocking” the gas meter:
1. Locate the gas meter and examine its display to be sure that you can determine a 1 cubic foot usage of gas and that the meter is temperature compensated. ( Figure 10)
2. Contact the gas utility to find the heating value of the gas. It can vary from about 950 BTU/ft 3 to about 1,100 BTU/ft 3 .
Guide to Power Gas Burners
3. Examine the gas piping to know of any other gas appliances connected to it. Turn them off so that only this burner is using gas from the meter.
4. Start the burner and use a stopwatch to measure the number of timed seconds it takes for the burner to fire 1 cubic foot of gas.
5. Calculate the firing rate in BTU/Hr. using the following equation:
Firing rate BTU/Hr. = Heating value (BTU/Ft 3
3,600 ÷ Timed seconds
) x
For example, if the heating value is 1,050 BTU/Ft 3 and you timed 1 cubic foot of gas at 42 seconds then firing rate BTU/Hr = 1050 x 3,600 ÷ 42 which calculates to 90,000 BTU/Hr.
If the burner is firing LP gas, a meter is usually not available. Contact your LP supplier for recommendations.
Figure 9 – Gas Valve Pressure Adjustment
Regulator
Cover Screw
Regulator
Adjust Screw
Gas Valve Outlet Pressure Tap
Figure 10 – Typical Gas Meter Layout
2
3
1 M
ILLION
1
4
0 9
8
5
6
7
10
0 TH
OUSAN
8
7
9
6
0 1
2
3
D
5
4
10
THOUSAND
2
3
1
4
0 9
8
5
6
7
8
7
1 T
HOUSAND
9
6
0 1
2
5
4
3
HAL
F FOOT
ON
E FOOT
27
Check Operation and Safety Controls
The testing of operating and safety controls requires technical training and experience with power gas burners and appliances.
Carefully follow the manufacturer’s instructions supplied with the appliance and the controls.
Verify the correct function of all operating and safety controls used in the installation.
If instructions are not available, use the following recommended procedures and record all results in a start-up log.
1. High limit/ Pressure Control – To check the High
Limit, raise the temperature or pressure of the operating control to a higher level and lower the limit to a setting less than the operating control.
Run the burner until the high limit opens and shuts the burner off. Adjust the controls back to the desired settings.
2. Operating control – Run the burner until the operating control shuts it off. If necessary, make adjustments to ensure the control cycles the burner in the desired temperature or pressure range.
3. Low water cutoff (LWCO) – With the burner firing, open the blow down valve on the low water cutoff, if applicable. As the water level drops, the LWCO switch contacts open and shut the burner off. When the water level rises, the LWCO contacts close and restart the burner. Monitor the LWCO switch operation in relation to the water level in the sightglass for synchronization.
number of firing cycles that the burner runs.
High cycling rates increase the possibility of light-off lock outs.
Operating controls should be set to minimize the
Setting Combustion
Always use calibrated test instruments to set combustion levels. Verify that test instruments are calibrated and in good working condition. If not already provided, drill test access holes in the flue pipe near the breech (or upstream of the boiler breech damper, if applicable) and in the front mounting plate area for firebox pressure. Be careful not to damage any water-backed surface.
Verify that all boiler sections, canopy, and access plates or doors are fully equipped with gaskets and sealed against any leakage, which could affect the combustion test results. Before making these tests, operate the burner to allow the heating system temperature to stabilize or nearly reach steady-state levels. Record all results in the start-up log for future reference.
◦ Draft – Set the stack or over-fire draft to the level specified by the appliance manufacturer.
◦ Natural Draft Applications – Typically over-fire draft is -0.01” or -0.02” W.C.
◦ Direct Venting – Typically may not require draft adjustment.
◦ High Efficiency/Positive Pressure Appliances –
(see manufacturer’s recommendations).
◦ Oxygen – It is recommended that you measure the oxygen (O2) early in the test sequence because high levels of carbon monoxide can be created at very low or even very high O2 levels. The typical operating range is between 3% – 5%.
◦ Carbon monoxide (CO) – An operating range of 0
-50 PPM is recommended for the CG4 burner. The maximum carbon monoxide (CO) level permitted in the flue gas by the UL 795 Standard is 400 PPM
(.04%).
◦ Stack Temperature – The stack temperature must be within the range specified by the appliance manufacturer. Generally a 325°F stack temperature is high enough to avoid corrosive condensation in the vent system, however a large cross sectional flow area chimney or a very tall chimney may require a higher temperature. See ANSI Z 223.1/NFPA 54 for design requirements.
28
Recommended Combustion
Adjustment Procedure
1. Initiate a call for heat.
2. Adjust the draft or breech pressure to the appliance manufacturer’s recommended level after flame has stabilized. A breech pressure that does not exceed
-0.04 to -0.06”W.C. is generally acceptable.
3. Measure the carbon monoxide level and adjust air settings, if necessary, to temporarily raise CO to about 50 PPM for a test point.
4. Measure the O2 or CO2 at the 50 PPM CO level.
For this discussion, assume the O2 is 1.5% (11%
CO2).
5. Open the air adjustment until the O2 level is increased by at least 1% or to 3% O2 (whichever is higher). This should reduce the CO level and provide a margin of reserve air to accommodate variable conditions.
6. Sample the CO level again. It should be in the 0 to
20 PPM range.
7. Check the draft to ensure it still meets specifications. If a major change in draft is required, repeat the above steps.
8. Check draft regulator for spillage. Confirm the condition of the chimney if spillage is present.
9. Verify stack temperature meets appliance manufacturer’s recommendations.
10. Perform any final adjustments and lock the air settings securely. Run the burner through several cycles to verify prompt ignition and stable burner operation.
11. Record the combustion performance readings, burner settings and appliance data on the start-up form in the back of this manual and on the startup tag. If the burner is firing LP gas you must also record set-up information on the propane conversion label and attach it to the appliance.
12. Hang the start-up tag in a prominent, safe location on or near the burner for future reference.
Notes
Guide to Power Gas Burners
29
30
Notes
Contractor Start-Up Form
Installation Name:_________________________________________ Installation Date:___________________
Installation Address:_________________________________________________________________________
Start-Up Contractor’s Name_________________________________ Phone:__________________________
Name of Technician_________________________________________________________________________
■ Appliance
(Below information can be obtained from appliance name plate)
Manufacturer:______________________________________________________________________________
Type (circle one): [ Boiler / Furnace / Other ] Model #:_______________ Serial #:____________________
Input MBH:_______________ Original Appliance Designed for (circle one): [ Oil / Natural Gas / Propane ]
Output MBH:______________
Limit Model No.
(Indicate n/a if not required by the appliance manuf.)
Limits
Temperature
Pressure
LWCO
Other Limits
Operation Verified
YES / NO
YES / NO
YES / NO
YES / NO / n/a
■ Burner
Fuel: [ Natural Gas / Propane ] Model #:________________ Serial #:_________________________
Combustion Head: [ F3G / F4G / F6G ] Fuel Orifice Size:________ Air Shutter Setting:____________
Air Band Setting:____________ [ or Blank Band Installed ] Baffle: [ Installed / Not Required ]
■ Chimney/Smoke Pipe
Chimney Type:[ Masonry / Metal Vent / Direct Vent ] Location (circle one): [ Inside / Outside ]
Chimney Height:_____________ Flue Pipe Size:______________ Flue Pipe Length:________________
Number of Elbows:____________ Confirm Double Acting Draft Regulator Installed: [ Yes / No ]
Thermal Safety Switch Installed [ Yes / No ] Voltage: [ 120V / 24V ]
Gas Supply Piping
Pipe Diameter:________ Length of Pipe from Burner to Meter:_________ Number of Elbows:__________
Gas Pressure to Burner Gas Valve While Burner is Operating ____________ Inches W.C.
■ Combustion Readings
O
2 :
_________% CO:__________ PPM CO
2 :
_________% Stack Temperature (325°F MIN.):__________°F
Manifold Gas Pressure:______________ (Inches W.C.) Draft at Breech___________________________W.C.
Guide to Power Gas Burners
31
Limited Warranty Information
The R. W. BECKETT CORPORATION (“Beckett”) warrants to persons who purchase its “Products” from
Beckett for resale, or for incorporation into a product for resale (“Customers”), that its equipment is free from defects in material and workmanship. To qualify for warranty benefits, products must be installed by a qualified service agency in full compliance with all codes and authorities having jurisdiction, and used within the tolerances of Beckett’s defined product specifications.
To review the complete warranty policy and duration of coverage for a specific product, or obtain a written copy of warranty form 61545, please choose one of the following options:
1. Visit our website at: www.beckettcorp.com/warranty
2. Email your request to: [email protected]
3. Write to: R. W. Beckett Corporation, P. O. Box 1289, Elyria, OH 44036
NOTE: Beckett is not responsible for any labor cost for removal and replacement of equipment.
THIS WARRANTY IS LIMITED TO THE PRECISE TERMS SET FORTH ABOVE, AND PROVIDES
EXCLUSIVE REMEDIES EXPRESSLY IN LIEU OF ALL OTHER REMEDIES, AND IN PARTICULAR
THERE SHALL BE EXCLUDED THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS
FOR A PARTICULAR PURPOSE. IN NO EVENT WILL BECKETT BE LIABLE FOR ANY INCIDENTAL OR
CONSEQUENTIAL DAMAGE OF ANY NATURE. Beckett neither assumes, nor authorizes any person to assume for Beckett, any other liability or obligation in connection with the sale of this equipment. Beckett’s liability and Customer’s exclusive remedy is limited to the cost of the product.
USA: P.O. Box 1289
●
Elyria, Ohio 44036
Canada: R.W. Beckett Canada, Ltd.
●
Unit #3, 430 Laird Road
●
Guelph, Ontario N1G 3X7 www.beckettcorp.com * 1-800-Oilburn (645-2876)
Part Number 61934-001 R01, Printed in the U.S.A. 09/14
advertisement