Carrier 40MBD Series Installation Instructions Manual

Carrier 40MBD Series Installation Instructions Manual

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Manual
Carrier 40MBD Series Installation Instructions Manual | Manualzz

Installation Instructions

................

ii.................

NOTE: Read the entire instruction manual before starting the installation.

TABLE

OF CONTENTS

SAFETYCONSIDERATIONS .........................

SYSTEMREQUIREMENTS ..........................

MODEL NUMBER NOMENCLATURE .................

SAFETY PRECAUTIONS ............................

INSTALLATION INFORMATION .....................

ATTACHED FITTINGS .............................

INSPECTING AND HANDLING THE UNIT ............

INDOOR UNIT INSTALLATION .....................

OUTDOOR UNIT INSTALLATION ...................

INSTALL THE CONNECTING PIPE ..................

REFRIGERANT PIPE ...............................

REFRIGERANT PIPE CONNECTION .................

CONNECT THE DRAIN PIPE ........................

FRESH AIR DUCT INSTALLATION ..................

CONTROL ........................................

WIRING ..........................................

TEST OPERATION .................................

SAFETY PRECAUTIONS ............................

INSTALLATION ACCESSORY .......................

INSTALLATION METHOD ..........................

PAGE

2

6

7

7

2

3

4

5

20

21

24

25

26

17

18

19

20

13

15

16

SAFETY

CONSIDERATIONS

Installing,

starting

up, and

servicing air-conditioning

equipment

can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.).

Only trained, qualified installers and

service

mechanics should install, start-up, and service this equipment.

Untrained personnel can perform basic maintenance functions such

as cleaning cots.

All

other operations should be performed by trained service personnel.

When working

on

the equipment, observe precautions literature and on tags,

stickers,

and labels

attached

in the to the equipment.

Follow all safety codes. Wear safety glasses and work gloves.

Keep quenching cloth and fire extinguisher nearby when brazing.

Use

care in handling, rigging, and setting bulky equipment.

Read these insWactions thoroughly and follow all warnings or cautions included in literature and attached to the unit.

Consult

local

building codes and National Electrical Code (NEC)

for

special requirements.

Recognize safety information.

This is the safety-alert symbol/_k.

Whan you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.Understand

these signal words:

DANGER,

WARNING, and

CAUTION.

These words are used with the s_ffety-alert symbol.

DANGER identifies the most serious hazards which will result in severe personal injury or death.

WARNING signifies hazards which could result in personal injury or death.

CAUTION is used to identify unsafe practices which may result in minor

personal

injury or product and property damage.

NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or

operation.

ELECTRICAL SHOCK

HAZARD

Failure to follow this warning could result in personal injury or death.

Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position.

There may be more than 1 disconnect switch.

Lock out and tag switch with a suitable warning label.

EXPLOSION

HAZARD

Failure to follow this warning could result in death, serious personal injury, and/or property damage.

Never use air or gases containing oxygen for leak

testing

or operating refrigerant compressors.

Pressurized mixtures of air or gases containing oxygen can lead to an explosion.

EQUIPMENT

DAMAGE

HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Do not bury more than 36 in. (914 ram) of refrigerant pipe in the ground. If any section of pipe is buried, there must be a 6 in. (152 ram) vertical rise to the vane connections on the outdoor units. If more than the recommended length is buried, refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causes refrigerant slugging and could possibly damage the compressor at start-up.

SYSTEM REQUIREMENTS

Allow

sufficient space for airflow and servicing unit.

Recommended

......

ence_

Power

W_mg:

Connection

Method

_ for Power and Communi-

" "O _ " t -

The main power is supplied to the outdoor unit. The field supplied connecting cable from the outdoor unit to indoor unit consists of three (3) wires and provides the power for the indoor unit.

Two wires are high voltage AC power and one is a ground wire.

Consult

your

local building codes and the NEC (National

Electrical Code) or CEC (Canadian Electrieal Code) for special requirements.

All wires must be sized per NEC or CEC and local codes.

Use

Electrical Data table MCA (minimum

circuit

amps) and MOCP

(maximum over current protection) to correctly size the wires and the disconnect fuse or breakers respectively.

Per caution note, only copper conductors with a minimum 300 volt rating and 2/64-inch thick insulation must be used.

Communication

Wiring:

A separate shielded

copper conductor only, with a minimum 300

volt rating and 2/64-inch communication thick insulation, wire from the outdoor

must be used

unit to the indoor unit.

as the

To minimize voltage drop of the control wire, use the following wire size and maximum lengths shown in the chart below:

Wire Size

18 AWG

16 AWG

Length ft (m)

50 (15)

50 (15) to 100 (30)

EQUIPMENT DAMAGE HAZARD

Failure to fo!low

this caution may result in equipment damage or improper operation.

* Wires should be sized based on NEC and local codes.

.

Use copper conductors only with a minimum 300 volt rating and 2/64 inch thick insulation.

2

[] If used as MULTI unit, please refer to the Installation & operation manuals packed with outdoor unit.

Model Numbers

9,000

12,000

18,000

24,000

36,000

48,000

208/230-1

208/230-1

208/230-1

208/230-1

208/230-1

208!230-1

40MBQB09D--3

40MBQB12D--3

40MBQB18D--3

40MBQB24D--3

40MBQB36D--3

40MBQB48D--3

Model number Nemenclature

40 MA Q B 09 B

I

3

Digit 12 indicates voltage

1 = 115/I/60

3 = 208-230-!-60Hz

Digits 10, 11 - blank

Digit 9- indoor Fan Coil Unit Type

B = High-Wall

C = Cassette

D = Ducted

F = Console

G = Underceiling

H = High Wall Color Variation

- = Outdoor

Digits 7, 8 indicate the system's capacity in 1000

BTU/Hr

Example: 09 = 9000 BTU/Hr

Maximum Number of fan coil units connected to the outdoor unit

B=1:1

Digit 5 indicates the system's type"

C = Cooling only;

Q = Heat pump

Digits 3 and 4 represent the model

The first two digits indicate the equipment type.

40 = Indoor unit;

38 = Outdoor uni

3

1. SAFETYPRECAUTIONS

Keep this manual where the operator can easily find them.

Read this manual closely before starting up the units.

For safety reasons the operator must read the following cautions carefully.

Installation must be performed in accordance with the requirement of NEC and CEC by authorized personnel only.

(Applicable to the North American area only)

The safty precautions listed here are divided into two categories.

WARNING

If you do not follow these instrutions exactly, the unit may cause property damage, personal injury or loss of life.

,_

CAUTION

If you do not follow these instrutions exactly, the unit may cause minor or moderate property damage, personal injury.

After completing the installation, make sure that the unit operates properly during the start-up operation.

Please instruct the customers on how to operate the unit and keep it maintained.Also, inform customers that they should store this installation manual along with the owner's manual for future reference.

WARNING

Be sure only trained and qualified

service

personnel to install, repair or service the equipment.

Improper installation, repair, and maintenance may result in electric shocks, short-circuit, leaks, fire or other damage to the equipment.

Install according to this installation instructions

strictly.

If installation is defective, it will cause water leakage, electrical shock and fire.

When

installing

the unit in a small room,

take measures

against to keep refrigerant concentration from exceeding allowable safety limits in the event of refrigerant leakage.

Contact the place of purchase for more information.

Excessive refrigerant in a closed ambient can lead to oxygen deficiency.

Use the attached accessories

parts and specified

parts

for installation.

otherwise, it will cause electrical shock and fire.

the set to fall, water leakage,

Install

at a strong

and

firm

location

which

is able to

withstand the set' s weight.

If the strength is not enough or installation is not properly done, the set will drop to cause injury.

The appliance must be installed 7.5ft / 2.3m above floor.

The appliance shall not be installed in the laundry.

Before obtaining access to terminals, all supply circuits must be disconnected.

The appliance must be positioned accessible.

so that the plug is

The enclosure of the appliance shall be marked by word, or by symbols, with the direction of the fluid flow.

For

electrical

work, follow the local national wiring standard, regulation and this installation instructions.

An independent circuit and single outlet must be used.

If electrical circuit capacity is not enough or defect in electrical work, it will cause electrical shock or fire.

Use the specified cable and connect tightly and clamp the cable so that no external force will be acted on the terminal.

If connection or fixing is not perfect, it will cause heat-up or fire at the connection.

Wiring routing must be properly arranged so that control board cover is fixed properly.

If control board cover is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electrical shock.

If the supply cord is damaged, it must be replaced by the manufacture or its service agent or a similarly qualified person in order to avoid a hazard.

An all-pole

disconnection switch

with a contact separation of at least 0.118in/3mm in all poles should be connected in fixed wiring.

When carrying out piping connection, take care not to let air substances go into refrigeration cycle.

Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury.

Do not modify the length of the power supply cord or use of extension cord, and do not share the single outlet with other electrical appliances.

Otherwise, it will cause fire or electrical shock.

Carry out the specified installation work after taking into account strong winds, typhoons or earthquakes.

Improper installation work may result in the equipment falling and causing accidents.

4

If the refrigerant leaks during installation, ventilate the area immediately.

Toxic gas may be produced if the refrigerant comes into the place contacting with fire.

The temperature of refrigerant circuit will be high, please keep tube.

the interconnection cable away

from

the copper

After completing the installation work, check that the refrigerant does not leak.

Toxic gas may be produced if the refrigerant leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker.

The appliance shall be installed in accordance with national wiring regulations.

Do not operate your air conditioner in a wet room such as a bathroom or laundry room.

An all-pole disconnection device which has at least 3mm clearances in all poles , and has a leakage current that may exceed 10mA, the residual current device (RCD) has a rated residual operating current not exceeding 30mA, and disconnection must be incorporated in the

fixed

wiring in accordance with the wiring rules.

CAUTION

Ground the air conditioner.

Do not connect the ground wire to gas or water pipes, lightning rod or a telephone ground wire.

Inappropriate grounding may result in electric shocks.

Be sure to install an earth leakage breaker.

Failure to install an earth leakage breaker may result in electric shocks.

Connect the outdoor unit wires, then connect the indoor unit wires.

You are not allowed to connect the air conditioner with the power supply until the wiring and piping is done.

While following

the

instructions in

this

installation manual, install drain piping in order to ensure proper drainage and insulate condensation.

piping in order to prevent

Improper drain piping may result in water leakage and property damage.

Install the indoor and outdoor units, power supply wiring and connecting wires should be at least 3.28ft/1m away

from

televisions or radios in order to prevent image interference or noise.

Depending on the radio waves, a distance of 3.28ft/1m may not be sufficient enough to eliminate the noise.

The appliance is not intended for use by young children or infirm persons without supervision.

Don't install the air conditioner circumstance: in

There is petroleum nearby.

• There is salty air nearby (near the coast).

• There is caustic gas (sulfide, for example) in the air (near a hot spring).

The volt vibrates violently (in the factories).

In buses or cabinets.

In kitchen where it is full of oil gas.

There is strong electromagnetic wave.

There are inflammable materials or gas.

There is acid or alkaline liquid evaporating.

Other special conditions.

the

following

2.

INSTALLATION

• To install

properly,

please read this installation first.

manual

at

The air conditioner must be installed by qualified persons.

When installing the indoor unit or its tubing, please follow this manual closely.

If the air conditioner

is installed on a metal

part of the building, it must be electrically insulated according to the relevant standards to electrical appliances.

When all the installation

work

is finished,

please turn on

the power only after a thorough check.

INSTALLATION ORDER

Select the location.

Install the indoor unit.

• Install the outdoor unit.

• Install the connecting pipe.

• Connect the drain pipe.

• Wiring.

• Test operation.

5

3.

ATTACHED

Determine whether the following fittings are in full scope. If there are spare fittings, please restore them carefully.

Table 3-1

® )

1. Soundproof / insulation sheath

2. Binding tape

3.Seal sponge

4.Orifice

5. Drain joint

6. Seal ring

7. Remote controller

(on some models)

2

1

1

1

(on some models)

1

1

CCD

1

(on some models)

2

2

1

1

8. Frame

9.Mounting

screw(ST2.9x

10-C-H)

10.Alkaline dry batteries (AM4)

11. Remote controller manual

12. Wire controller

13. Magnetic ring

(twist the electirc wires L and N around the magnetic ring to five circles)

14. Owner's manual

15. Installation manual

16 .Transfer connector(C,0.375in-C,0.5in)/

(¢9.52-¢12.7)

(Packed with the indoor unit, used for multi-type models only )

(NOTE: Pipe size differs from appliance to appliance.To

meet different pipe size requirements, sometimes the pipe connections need the transfer connector to install on the outdoor unit .)

17. Connecting wire for display (6.56ft/2M)

18. Cord protection rubber ring z

1

1

1

(on some models)

1

(on some models)

1

(on some models)

6

3

4

4.

INSPECTINGAND HANDLINGTHE UNIT

At delivery, the package should be checked and any damage should be reported immediately to the service agent.

When handling the unit, take into account the following:

Fragile, handle the unit with care.

[_ Keep the unit upright in order to avoid compressor damage.

Decide before hand the path which the unit is to be brought in.

Move the unit in the original package if possible.

When lifting the unit , always use protectors to prevent belt damage and pay attention to the position of the unit's centre of gravity.

5.

INDOORUNITINSTALLATION

5.1

Installation place

The indoor unit should be installed

in a location that meets

the following

requirements:

• There is enough room for installation and maintenance.

• The ceiling is horizontal, and its structure can endure the

weight of the indoor unit.

• The outlet and the inlet are not impeded, and the influence of external air is minimal.

• The air flow can reach throughout the room.

• The connecting pipe and drainpipe could be extracted easily.

• There is no direct radiation from heaters.

Maintenance roomage

./

/

/

/

/

/

/

/

/

/

/

/,

/

/

/

./

/

_ 7.874in/200mm or more

11.811in/300mm or more

23.622inX23.622in/600mmX600mm checking orifice

CAUTION

Keep indoor unit, outdoor unit, power supply

wiring

and transmission wiring at least 3.28ft/1m away from televisions and radios. This is to prevent image interference and noise in those electrical appliances.

(Noise may be generated depending on the conditions under which the electric wave is generated, even if 3.28ft/1m is kept.)

5.2

Install the main body

1

Installing

[] bolts.

00.394in/010

Please refer to the following

hanging screw bolts.

figures for positioning

(4 bolts)

4 screw

Evaluate the ceiling construction and please install with

00.394in/010 hanging screw bolts.

Consult the construction personnels for the specific procedures.

Keepv the ceiling flat. Consolidate the roof beam to avoid possible vibration.

Carry out the pipe and line operation in the ceiling after finishing the installation of the main body. While choosing where to start the operation, determine the direction of the pipes to be drawn out. Especially in case there is a ceiling, position the refrigerant pipes, drain pipes,indoor & outdoor lines to the connection places before hanging up the machine.

[]

The installation of hanging screw bolts.

• Cut off the roof beam.

• Strengthen the place that has been cut off, and consolidate the roof beam.

[]

After the selection of installation location, position the refrigerant pipes, drain pipes, indoor and outdoor wires to the connection places before hanging up the machine.

[] The installation of hanging screw bolts.

NOTE

Confirm the minimum drain tilt is 1/100 or more

5.2.1

Wooden

construction

Put the square timber traversely over the roof beam, then install the hanging screw bolts. (Refer to Fig.5-2)

Timber over the beam

Fig.5-1

L-L_

._ZZT77_

L[ L_ ROOfbeam

\ i_ _ _ _eiling

Hanging screw bolts

Fig. 5- 2

7

5.2.2

New concrete bricks

Inlaying or embedding the screw bolts. (Refer to Fig. 5-3)

(Blade shape insertion) (Slide insertion)

Fig.5-3

5.2.3

For Original concrete bricks

Use embedding screw bold, crock and stick harness.

(Refer to Fig.5-4)

_-_._

,-_,_'_ Steel bar

Embedding screw bolt

(Pipe hanging and embedding screw bolt)

Fig.5-4

5.2.4

Steel roof beam structure

Install and use the supporting angle steel. (Refer to Fig.5-5)

Hanging screw bolt

3.

Air inlet and air outlet duct should be apart far enough to avoid air passage short-circuit.

4.

Recommended duct connection.

Canvas tie-in Canvas tie-in

Air outlet

Isolation booth

Isolation booth

Air inlet

Air dust filter

Fig.5-7

5.

Please refer to the following static pressure table to install.

Table.5-1

[_, .,_,4ar_gU.n_gbelg\ Su__i÷!g

Fig. 5-5

2

Overhanging

the indoor unit

(1)

(2)

Overhang the indoor unit onto the hanging screw bolts witha block.

Position the indoor unit in a flat level by using the level indicator, unless it may cause leakage.

Screw nut

Shockproof cushion

\

Overhang part

Washer

Hanging bolt

Fig.5-6

0 _

30

30

70

70

80

100

Note: The above static pressure ratings are in Turbo mode.

NOTE

1. Do not put the connecting duct weight on the indoor unit.

2. When connecting duct, use inflammable canvas tie-in to prevent vibrating.

3. Insulation foam should be wrapped outside the duct to avoid condensation and internal duct underlayer shall be added to reduce the noise for special requirement.

5.3

Duct and accessories installation

1. Install the filter(optional) according to air inlet size.

2. Install the canvas tie-in between the body and duct.

8

The positioning

of ceiling hole, indoor unit and hanging screw bolts

Dimension and air outlet size co

E

I

Air inlet size

F

A

.

.

i

I

Position

size of descensional ventilation

opening

I

BI

BI

J

3

3

Air filter

Air filter i m D

Electric control box

Size of mounted hook

D

C

Unit: in/ram

Z

Z

3 m

7

L

Electric control box o o

o

L o

Fig.5-8

9

Table.5-2 in/mm

A B C D E F G H I J K L M

27.6/700 8.3/210 25/635 22.4/570 2.6/65 19.4/493 1.4/35 4.7/119 23.4/595 7.9/200 3.2/80 29.1/740 13.8/350

8.3/210 25/635 22.4/570 2.6/65 28.1/713 1.4/35 4.7/119 32.1/815 7.9/200 3.2/80 37.8/960 13.8/350

10.6/270 25/635 22.4/570 2.6/65 28.1/713 1.4/35 7/179 32.1/815 10.2/260 0.8/20 37.8/960 13.8/350

10.6/270 30.5/775 28/710 2.6/65 36.7/933 1.4/35

11.8/300 34.1/865 31.5/800 3.2/80 38.1/968 0.4/40

7/179 40.711035 10.2/260 1.8/45 48.811240 19.7/500

8/204 43.111094 11.3/288 1.8/45 48.811240 19.7/500

(in=mm/25.4)

How to adjust the air inlet direction? (From rear side to under=side.)

Take off ventilation panel and flange, cut off the staples at side rail.

2.

Stick the attached seal sponge as per the indicating place in the following fig, and then change the mounting positions of air return panel and air return flange.

Air return flange

Dentilation panel

3.

When installing the filter mesh, please plug it into flange inclined from air return opening, and then push up.

Side'rail

Seal sponge/

4.

The installation is complete, after the filter mesh which holds the fixing blocks have been inserted into the flange positional holes.

NOTE

All the figures in this manual are for illustration purposes only. They may differ slightly from the air

conditioner you purchased.

10

Fig,5-9

5.9

Fan performances

Static pressure curve(middle static pressure duct)

12K

70

_

= o

&

6O

50

E 4O w

3O

20

10

Pa

9O

8O

\ \\ \,.

'_ _i "\ \, E ,lper hic!h spee(

, _ \ \,-_1 I I

i i

, i

\ \ _' _aigh speed

\ _ _*"

,

i i

_kMld speed

\

177 235

/300 /400

\ .._ ""lkL_w:sp ,eec

\

'.x-

.

\

.A/kl

I

\ _./\1 I_1 I

€"

, "1111

294 353 412

/500' /600 /700

471

/800

530

/900

Air volume(CFM/m3/h)

24K

"_ 50

_ 4o

Ill

3O

20

10

Pa

9O

8O

70

60

412 471 530 589 647

/700 /800 /900 /1000/1100

706 765 824

/1200 /1300/1400

Air volume(CFM/m/h)

3

883

/1500

18K

80

70 e

_, 60

S_ o

O3

50

E 40 d3

LU

30

Pa

90

\

\ \

\ \

\, '\

\

\

\

\

\

\

\

\

\

\

\

\

\

\

,j

\ \

\ \

/

Vlid

2O \\ , .Low

.'

10

\

\

118 117 235 294 353 412 471 530 589 647 706

/200 /300 /400 /500 /600 /700 /800 /900 /1000/1100 /1200

Air volume(CFM/m3/h)

30K

Pa

90

8O

70 o

_, 6o

50

_ 40

\ \ "\

\,\\\

\

\ x\

\ ,, v"

'\

\ '\ "\

3O

2O

10

706 824 942

/1200 /1400/1600

1059

/1800

1177

Air volume(CFM/m/h)

3

1295

/2000/2200

1413

/2400

]!

36K

Pa

90 '\

80

70

60

B_

._.9.

-_ 50

_ 40 nl

3O

20

10

'\

\

\

\ \

\

"\

',I\

\

\

\ \ \,

IIIII

IIIII

IIIII

IIIII

IIIII

IIIII

_r high speed k k

\

'\\\ \

\

'\ \

\

\

\

"\

\

f

I

Low speed_

IIII

IIII

IIII

IIII

IIII

\

!

\

I

647 706 824 942 1059 1177 1295 1413

/1100 /1200 /1400/1600 /1800 /2000/2200 /2400

Air volume(CFM/m3/h)

60K

P8

120

80

70

_ 60

110

100

90

-_ 5O w

E 4O

3O

20

10

'\',\

'\

\

\, ,\\, \,

\

\ \ ", \

\ ',, \

\ \ \ ,

\

\

'\

'"

i \' x \

/

589

765 942 1118 1295 1471 1648 1825 2001

/1000/1300 /1600/1900 /2200 /2500/2800 /3100 /3400

48K

P8

120 e

110

\\\ k \\\

100

90

\,\

'\ \,\,

\

\

\

80

70

60

50

\

\

\ ' X"

\

\ \

" IIII

\

,_ _ High speed

', \

\

,\

\

\ \'\

\g

\ k

E 4O

\

80

\

20 lO i

589 785 942 1118 1295 1471 1648 1825

/1000 /1300 /1800/1900 /2200 /2500/2800 /8100

Air volume(CFM/m_/h)

]2

6.

OUTDOOR

6.1

Installation Place

The outdoor unit should be installed in the location that

meets the following

requiements:

There is enough room for installation and maintenance.

"

The air outlet and the air inlet are not impeded, and can not be reached by strong wind.

It must be a dry and well ventilating place.

• The support is flat and horizontal and can stand the

weight

of the outdoor unit. And will no additional noise or vibration.

Your neighborhood will not feel uncomfortable with the noise or expelled air.

It is easy to install the connecting pipes or cables.

Determine the air outlet direction where the discharged air is not blocked.

There is no danger of fire due to leakage of inflammable gas.

The piping length between the outdoor unit and the indoor unit may not exceed the allowable piping length.

In the case that the installation place is exposed to strong

wind such as a seaside, ensure the fan operates properly by putting the unit lengthwise along the wall or using a dust shield.(Refer

to Fig.6-1)

If possible, do not install the unit where it is exposed to direct sunlight.

If necessary, install a blind that does not interfere with the air flow.

During the heating mode, the

water

drained off the outdoor unit ,the condensate should drain well away by the drain hole to an appropriate.

Select the position

where

it will not be subject to snow drifts, accumulation of leaves or other seasonal debris.

If unavoidable, please cover it with a shelter.

Locate the outdoor unit as close to the indoor unit as possible.

If possible, please remove the obstacles nearby to prevent the performance from being impeded by air circulation.

The minimum distance between the outdoor unit and obstacles described in the installation chart does not mean that the same is applicable to the situation of an airtight room.

Leave open two of the three directions

(L1 ,L2) (Refer to Fig.6-4)

e.2 Figure

of body

size

1. Split type outdoor unit

/

i

I w

W

• v

Fig. 6-2

Fig. 6-3

0 X

Fig.6-1

NOTE

All the figures in this manual are for illustration purposes only.

They may be slightly different from the air conditioner you purchased.

13

!

.... i--

1_o_-I

-J"

Air outlet_

Fig. 6-4

Table 6-1

Model

9K/12K

18K

24K

36K

48K

(in=mm/25.4)

W in (mm)

31.89

(810)

33.27

(845)

37.20

(945)

37.20

(945)

36.93

(938)

6.3

Space of installation and maintenance

1. Split type outdoor unit

(Wall or obstacle)

D in (mm)

12.2 (310)

12.60

(320)

15.55

(395)

15.55

(395)

15.90

(404)

J >11.81i/]/30cm

Air inlet m

@ m

H in (mm)

21.97

(558)

27.56

(700)

31.89

(810)

31.89

(810)

53.90

(1369)

L1 in (mm)

20.9 (530)

21.1 (560)

25.1 (640)

31.89(810)

24.96(634)

JJJJJJJJJ

Unit:in/turn

L2 in (mm)

11.4 (290)

13.2 (335)

15.9 (405)

31.89

(810)

17.63

(448)

Fig.6-6

Airinlet _ [_ _

_d_|M \/ Airoutlet l , ,M2i3nt61innch ....

,

Fig. 6-5

NOTE

All the figures in this manual are for illustration purposes only. They may differ slightly from the air conditioner you purchased.

6.4

Available configuration type outdoor unit for centrifugal fan

NOTE

Keep in mind that fan unit weight is aprox 1058oz/30kg ,the unit

as well as relevant equipment covered with the vinyl cover during installation work.

®

®

® o

6.5

Moving

and installation

Since the gravity center of the unit is not at its physical center, be careful when lifting it with a sling.

Never hold the inlet of the outdoor unit to prevent it from deforming.

Do not touch the fan with hands or other objects.

Do not lean it more than 45_ and do not lay it sidelong.

Make concrete foundation accoding to the specifications of the outdoor units.(Refer

to Fig.6-11)

Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong wind.(Refer

to

Fig.6-11)

[] Concrete Foundation

1. The foundation could be flat ground and is recommended be

3.94-11.81 in/100-300mm higher than ground level.

2Jnstall a drainage around the foundation for smooth drain.

3.When installing the outdoor unit fix the unit by anchor bolts of M10.

4.When installing the unit on a roof or a veranda, drain water sometimes turns to ice in cold weather. Therefore, avoid draining in an area that people often use because it is slippery.

.c

_o ooo t o

._-o

Fig.6-7

]4

Table 6-2

(_

(_

Outdoor Unit

Vibration-proof rubber

Anchor Bolt M 10

Drainage (Wide 3.94in/100×Depth 5.9in/150)

Drainage

Mortar Hole (¢3.94in100×Depth 5.9in/150)

NOTE: Make sure 3-4 degree of angel is kept between the unit and the floor when the unit is installed in the low temperauture and humid environment.

Make sure the ice on the chassis of the outdoor unit can be dealt with when the unit is installed in the low temperature and humid enviroment.

The outdoor unit should be installed in amounting rack 11.81in

/30cm high.The enviroment temperature should be above

0 °"

The machine must be installed indoor.

7.

INSTALLTHECONNECTING

7.1

Preparation

and Caution

Before installation

make sure the height difference, the length of refrigerant pipe, and the number of the bends between the indoor unit and outdoor unit meet the following requirements:

Table 7-1 unit: ft/m

° NOTE:the table above refers to the liquid tube.

° NOTE:The number of bends is up to the length of the max height drop.Usually

for each 32.8ft/10m need a bend.

_I_ CAUTION

All

field refrigeration

piping must technician

be and

provided

relevant local and national codes.

must

by a licensed comply

with the

Prevent air, dust, or other impurities

from entering

in the

pipe system during installation.

Insulation

pipe shall be used to the gas piping and the liquid piping.

Otherwise, condensation may occur.

7.2

The Procedure of Connecting

Pipes

1 Measure the required length of the connecting pipe, then create

it per the following

steps.

[]

Connect the indoor unit first, then the outdoor unit.

Bend the tubing in a proper way. Do not twist the pipe.

Bend the pipe with thumb

32.8ft/10

82.02ft/25

82.02ft/25

164.04ft/50

16.4ft/,'

39.37ft112

49.21ftP

82.02ft/25

I

I min-radius 3.94in/100mm

Fig. 7-1

Put some refrigerant oil on the surfaces of the flare pipe and the joint nuts then wrench it for 3~4 rounds with your hands before you fasten the flare nuts.(Refer to chart 16)

Use frozen oit i-

Fig.7-2

Be sure to use two wrenches simultaneously when you connect or disconnect the pipes.

_ Make the ends straight

Fig.7-3

The outdoor unit is charged with rating refrigerant amount

in

the factory.Additional

charges refer to the table below:

Table 7-2

Piping

System size

9K

12K

18K

24K

36K

48K

Additional refrigerant charge(between standard-Max piping length)

Oz/ft(g/m)

0.16(15)

0.16(15)

0.16(15)

0.32(30)

0.32(30)

0.32(30)

Gas Pipe(size-connection in(mm)

3/8(9.52)

1/2(12.7)

1/2(12.7)

5/8(16)

5/8(16)

5/8(16) type Liquid Pipe(size-connection in(mm)

1/4(6.35)

1/4(6.35)

1/4(6.35)

3/8(9.52)

3/8(9.52)

3/8(9.52) type

]5

[]

The service valves of the outdoor unit should be completely closed(as original status).Every

time you connect,first loosen the nuts, then connect the flare pipes within 5 minutes.

If the nuts have been loosened for a long time, dusts and other impurities may enter the pipe system and may cause a malfunction.So

please expel the air out of the pipe

with

refrigerant before connection.

[]

[]

Expel the air(refer to the "8.1")after connecting the refrigerant pipe with the indoor unit and the outdoor unit.

Then fasten the nuts at the service valves.

Bend the connecting pipe of small wall thickness.

• Cut out a proper insulating pipe.

concave at the bending part of the

Then expose the pipe(cover it with tape after bending).

• To prevent twisting, please bend the pipe at a proper radius.

NOTE

The bending angle should not exceed 90. o

The bending position is preferably in the middle of the bendable pipe.

Do not bend the pipe more than three times.

Be sure to use the same insulating materials when you buy the brass pipe. (More than 0.35in/9mm thick)

2.

[]

[]

[]

Place The Pipe

Drill a hole in the wall (suitable just for the size of the wall sleeve), then set the fittings such as the wall sleeve

and its

cover.

Bind the connecting pipe and the cables together tightly with binding tapes.

Pass the bound connecting pipe through the wall sleeve from outside.

Make sure the pipe allocation does not damage the copper tubes.

3

Connect

the pipes.

4 Expel the air with a vacuum pump or refrigerant.

5 Open the service valves of the outdoor unit.

6 Check the refrigerant leakage.

Check all the joints with the leak detector or soap water.

7 Cover the joints of the connecting pipe with the

insulation foam, and bind them well with the tape to

prevent potential leakage.

=

twinsfunction)

8.1

Length and drop height permitted of the

refrigerant

piping

Note: Reduced length of the branching

/0,5mof

the equivalent length of the pipe,

Table.8-1

tube is the 1.64ft

98.42ft/30m

164.04ft/50m

49.21ft/15m

32.8ft/10m

65.8fti20m

L+LI+L2

L1,L2

L1-L2

HI

1.64fti0.5m

H2 t t Outdoor unit

'

¢---

/

The line branch pipe

L2

L1

Indoor unit oC

0

o

c_ cq

0

-o

_=-_

0

Fig.8-1

]6

Table.8-3

Note: All used branch pipe must be produced by Midea,

otherwise the unit will malfunction.

The indoor units should

be installed

equivalently

at both sides

of the U type branch pipe.

8.2

Size of joint pipes

Table.8-2 Size of joint pipes for 410A

¢0.375in/9.5

¢0.5in/12.7

¢0.626in!15.9

¢0.25in/6.35

¢0.25in/6.35

¢0.375in!9.5

CE-FQZHN-01C

CE-FQZHN-01C

CE-FQZHN-01C

8.3

Vacuum with vacuum pump

1

Use the vacuum pump with the vacuum level lower than

-14.5PSi!-0.1MPa

1.4CFM!40L/min.

and the air discharge capacity above

2)

It is not necessary to vacuum the outdoor unit. Don't open the outdoor unit gas and liquid pipe shut-off valves.

3)

Make sure the vacuum pump registers as -14.5PSi/-0.1MPa or below after 2 hours or longer operation.

If the pump operated 3 hours or above can not achieve -14.5PSi!-0.1MPa

or below, please check whether there is a water mix or gas leak inside of the pipe.

Connect with vacuum pump

.0.

I Perform the pump (last for 2 hrs or above)

,,_

When get the vacuum level

I

-0.1MPa

the pump should run for 2()-60 mins

,_

/

/

I1. Close-off the valve of I vacuum meter

• I

2. Cut off the connection I

J between pressure meter and vacuum pump.

3. Close the vacuum I

[ vacuum pump

.G

Place the vacuum state unused (1 hrs or above)l

I

I

Fig.8-2

,_

CAUTION

Don't mix up the different refrigerants or abuse the tools and measurements which directly contact with refrigerants.

Don't adopt refrigerant gas for air vacuuming.

If vacuum level could not get to -14.5PSi/-0.1MPa, please check whether resulted by leakage and confirm the leakage site.If no leakage, please operate the vacuum pump again 1 or 2 hrs.

8.4

Refrigerant amount to be added

Calculate the added refrigerant according to the diameter and the length of the liquid side pipe of the outdoor/indoor unit connection.

The refrigerant is R410A.

17

¢0.25in/6.35

¢0.375in/9.52

0.0331b/0.015kg

0.0661b/0.030kg

1) The branching pipe must be installed horizontally, error angle of it should not large than 10 °. Otherwise, a malfunction will occur.

U-shaped branching pipe

I A

!

A direction view

Wrong Correct

Horizontal surface

Fig.8-3

9.

REFRIGERANTPIPE CONNECTION

9.1

Expel The Air

1 Flaring

• Cut a pipe with a pipe cutter. (Refer to Fig.9-1)

O× X X

2

/__

9_ _Lean eludj_ bull_

Fig.9-1

I I I

• Insert a flare nut into a pipe and flare the pipe.

Fasten the nut

• Put the connecting pipes at the proper position, wrench the nuts with hands then fasten it with two wrenches simultaneously.

(Refer to Fig.9-2)

__

Fig.9-2

CAUTION

Too much torque will harm the bellmouthing and too little will cause leakage.

Table 9-1.

Please determine the torque according to

Table 9-1

144_-- 176 kgf.cm

(14.2 -_17.2 N.m)

333---407 kgf.cm

(32.7 -_39.9 N.m)

0.327in/8.3

0.472in/12.0

0.343in/8.7

0.488in/12.4

504 -_616 kgf.cm

(49.5"---60.3 N.m)

630--_770 kgf.cm

(61.8"--_75.4 N.m)

0.606in/15.4

0.622in/15.8

0.732in/18.6

0.748in/19.0

90°i4

Expel the air with a vacuum pump(Refer to Fig.9-3)

(Please refer to its manual for the method of using the manifold valve)

Loosen and remove the nuts of service valves A and B, and connect the charge hose of the manifold valve with the maintenance terminator of service valve A. (Be sure that service valves A and B are both closed)

• Connect the joint of the charge hose with the vacuum pump.

• Open the Lo-lever of the manifold valve completely.

Turn on the vacuum pump. At the beginning of pumping, loosen the nut of service valve B a little to check whether the air comes in (the sound of the pump changes, and the indicator of compound meter turns below zero). Then fasten the nut.

When the pumping has finished, close the Lo-lever of the manifold valve completely and turn off the vacuum pump.

When you have pumped for over 15 minutes, please confirm that the indicator of multimeter is on -1.0X10-_Pa

(-76cmHg)

Loosen and remove the nuts of service valves A and B to open service valve A andB completely, then fasten nuts.

Disassemble the charge hose of service valve A, and fasten the nut.

ManifoEd va(ve

MultFmeter Pressure meter

-76 cmHg

Lo-lever

Charge hosem=,.-

HHever

Charge hose

_ Vacuum pump

Fig.9-3

_L CAUTION

Both service valves should be open before test operation.

Each air conditioner has two service valves of different sizes.(Refer to Fig.8-4) Flare nut

Stopper

Cap

Valve body

Valve stern

Fig.9-4

9.2

Check

the Leakage

Check all the joints with the leak detector or soap water. (Refer

Fig.9-5 as a reference illustration) in the chart

A ...... Lo-stop valve

B...... Hi-stop valve

C,D..Joints

of the connecting pipe to the indoor unit.

Check-point of indoor unit _C

Check-point of out!!or

uni_J

Fig.9-5

9.3

Insulation

Be sure to completely insulate all the exposed parts of the flare pipes.

Incomplete insulation may cause condensation.

10.

CONNECT

• Install

the drainpipe of the indoor unit

Use a polyethylene tube as the drainpipe (out-dia.1.14-1.22in

/29-31mm,

in-dia.0.984in/25mm).

When extending the drainpipe,tighten water-proof tape to prevent leakage.

the connector with

Lean the drainpipe down toward outdoor (outlet-side) at a degree of over 1/ 50 to keep water from flowing back. And please Avoid any bulge.

Do not drag the drainpipe roughly. One support point should be set every 3.28~4.92ft/1~1.5m

to prevent the drainpipe from yielding. Or tie the drainpipe with the connecting pipe to fix it.

If the outlet of the drainpipe is higher than the body's pump joint, the pipe should be arranged as vertically as possible.

And the lift distance must be less than 21.65in!550mm, otherwise the water can not be lifted completely and may cause overflow.(Only available for the unit with a pump.)

The end of the drainpipe should be over 1.969in/50mm higher than the ground , and do not immerse it in water.

If you discharge the water directly into sewage, be sure to make a

U-form aqua seal by bending the pipe up to keep the foul gas entering the house through the drain pipe.

]8

The drain pipe installation for the unit with pump.

............................................................

3,28;4_2_..........

iI i

, , I/1-1.5m

]L .......

FJg.lO-1

The drain pipe installation for the unit without pump.

1/50

2

3

[]

Operate the air conditioner in "COOLING" mode. The sound of the drain pump should be noticeable.

Check whether the water is discharged well (1 min lag is possible, according to the length of the drain pipe), and check whether the water leaks from the joints.

Power off the air conditioner and recover the cap.

The unit without

pump.

Fig. 10-2

[]

1

[] Drainage test

• Check whether the drainpipe is unhindered,

• New ly built houses should have this test done before paving the ceiling.

The unit with pump,

Remove the test cover, and stow about 2000ml

water

in the

water pan.

stowtuL

Fig. 10-5

Stow 2000ml water in the water pan through the stow tube,check whether the drainpipe is unhindered.

Install the drain joint of the outdoor unit

(For Heat Pump

Models)

Fit the seal into the drain joint, then insert the drain joint into the base pan hole of outdoor, rotate 90 ° to securely assemble them.

Connect the drain joint with an extension drain hose (Locally purchased)to avoid condensate from draining off the outdoor unit during the heating mode.

Test cap

Fig. 10-3

Seal

Base pan

,__DD Seal rain joint

Fig.

10-6

NOTE

All the figures in this manual are for illustration purposes only.

They may differ slightly from the air conditioner you purchased.

11. FRESHAIRDUCTINSTALLATION

Dimension •

Duct joint for fresh air

, ,o _o

O4.92in/125mm_ e

_

\

O6.3in/160mm

"_oj"

Fig. 11-1

Fig. 10-4

]9

Table 12-2

11.1Motor

and drain pump maintenance

(Use rear ventilated as example)

Motor maintain:

1.

Take off the ventilated panel.

2.

Take off the blower housing.

3.

Take off the motor.

-Ventilated panel

+

+

1

Fig.11-1

Pump maintainance:

1.

2.

3.

Screw off four screws from drain pump.

Plug off pump power supply and water level switch cable.

Take off _

Mofor

12.

CONTROL(ONLYFOR INVERTERUNITS)

• The capacity of the system and the network address of the air-conditioner can be set by the switches on the indoor Main Control Board,

Before setting, turn off the power, After setting,

restart the unit,

Setting is not allowed when the unit is power on,

12.1 Horsepower code setting

Table 12-1

The capacity of the indoor unit has been set in the

factory

according to the below table,

Horsepower code

POWER $

%

ENC1

8

9

A

10.5

14.0

16.0

12.2

Network address set

Every air-conditioner in the network has only one network address to distinguish each other. The address code of air-conditioner in LAN is set by code switches $1 & $2 on the Main

Control Board of the indoor unit, and the set range is 0-63.

13.

WIRING

The appliance shall be installed in accordance national wiring regulations, with

The air conditioner should use a separate power supply with rated voltage,

The external power supply to the air conditioner should be grounded, which is linked to the ground wiring of the indoor and outdoor unit,

The wiring work should be done by qualified persons according to the wiring diagram,

A circuit breaker and a residual current device (RCD) with

10mAor above rating shall be installed in the power circuit according to the national rule,

Be sure to locate the power wiring and the signal wiring well to avoid cross-disturbance,

Do not turn on the power until you have confirmed proper wiring,

The power cord type is H07RN-F,

NOTE

Refer to EMC Directive 2004/108/EC

To prevent flicker impressions during the start of the compressor, the following installation conditions apply.

1 The power connection for the air conditioner has to be done at the main power distribution.

The distribution has to be of a low impedance, normally the required impedance reaches at a 32 A fusing point.

2

No other equipment line.

has to be connected with this power

3

For detailed installation acceptance please refer to your power supplier, to verifyif restrictions apply for products like

washing

machines, air conditioners or electrical ovens.

4

For power details of the air conditioner refer to the rating nameplate of the product.

5

13.1

For any questions contact your local dealer.

Connect

the cable

Disassemble the cover.0f there isn't a cover on the outdoor

unit, disassemble the screw from the maintenance

board, and

pull it in the direction of the arrow to remove the protection

board.)

Connect the cables to the terminals

correspondingly.

Re-install the cover or the protection board.

13.2 The Specification of Power

(Refer to Table14-1~14-3)

13.3 Wiring figure

(Refer to Fig. 13-3-Fig. 13-6)

1.split type outdoor unit

Cover

Fig. 13-1

Protection board

2O

1

2

NOTE

All the figures in this manual are for illustration purposes only.

They may differ slightly from the air conditioner you purchased(depend on model).

14. TESTOPERATION

The test operation must be carried out after the entire installation.

Please confirm the following points before the test operation:

• The indoor unit and outdoor unit are installed properly.

• Tubing and wiring are correctly completed.

• The refrigerant pipe system is leakage-checked.

• The drainage is unimpeded.

• The heating insulation works well.

• The ground wiring is connected correctly.

• The length of the tubing and additional charge amount have been recorded.

• The power voltage matches rated the voltage of the air conditioner.

• There is no obstacle at the outlet and inlet of the outdoor and indoor units.

• The gas-side and liquid-side service valves are both completely open.

• The air conditioner is pre-heated by turning on the power.

3

[]

Test operation

Set the air conditioner to the cooling mode with the remote controller, and check the following points.

If there is any malfunction, please resolve it according to the chapter

"Troubleshooting" in the "Owner's Manual".

• 1) The indoor unit a. Whether the buttons on the remote controller

works well.

b. Whether the air flow louver move normally.

c. Whether the room temperature is well adjusted.

d. Whether the indicator lights normally.

e. Whether the temporary switch on the unit works well. f. Whether the drainage is normal.

g. Whether there is abnormal vibration or noise during operation.

h. Whether the air conditioner

works well

in heating mode(heat pump model).

• 2) The outdoor unit a. Whether there is abnormal vibration and noise during operation.

b. Whether the exhaust air, noise, or condensation influence your neighborhood.

c.

Whether there is any refrigerant operation.

leakage during

_k CAUTION

A 3 minute delay is normal when restarting the unit for

compressor protection.

The Specification

[] Table 13-1

of Power(indoor power

supply)

The Specification

[] Table 13-2

1Phase

208/230V

15

1Phase

208/230V

15

of Power(outdoor power

supply)

1Phase

208/230V

15

1Phase

208/230V

15

1Phase

208/230V

15

1Phase

208/230V

20

1Phase

208/230V

15~20

1Phase

208/230V

25

The specification of power

for the invert type air conditioner(independence l!

Table 13-3

1Phase

208/230V

50

1Phase

208/230V

55

power

supply)

B

1Phase

220/230V

15

1Phase

208/230V

20~15

1Phase

220/230V

15

1Phase

208/230V

20

2!

1Phase

220/230V

15

1Phase

208/230V

25

1Phase

220/230V

15

1Phase

208/230V

50

1Phase

220/230V

15

1Phase

208/230V

55

CAUTION

The power supply is included in the power supply above mentioned can be applied to the table.

Before obtaining access to terminals, all supply circuits must be disconnected.

[] Wiring figure

[] Fig.14-3

Power supply

Switch/Fuse

(Available locally)

Power wiring (indoor)

Power linking wiring (Outdoor)

Indoor

Unit

Ground wiring

Ground wiring

Strong elec-signal link wiring

Weak elec-signal link wiring

® Ground the air conditioner properly in case to affect its anti=interference function

[] Fig.14-4

Power supply l_

(Available locally)

Switch/Fuse

Indoor

Unit l

J

Power linking wiring (indoor)

/

Power wiring (outdoor)

Outdoor

Unit

Ground wiring

m m

Ground wiring

Strong etec-signal link wiring

Weak eiec-signal link wiring

® Ground the air conditioner properly in case to affect its anti=interference function

22

[] Fig.14-5

Indoor

Unit

Power supply Power supply

Switch/Fuse

(Available locally)

Powerwiring

Powerlinking

(indoor) wiring (Outdoor)

Outdoor

Unit

-_ Ground wiring

Weak dec-signal link wiring

Switch/Fuse

(Available locally)

Indoor

Unit

Ground wiring _

[

L'

I

]

I

]

o Ground the air conditioner properly.

[]

Fig.14-6

Indoor !

Ground wiring _ "_

.,,, o Ground the air conditioner

properly.

Outdoor

Unit

Power supply

I

_

E

Switch/Fuse

(Available locally)

Power wiring (outdoor)

/

1----J

/

G.....dw ring

Strong eIec-signal link wiring

Weak elec-signal link wiring

CAUTION

A disconnection incorporated device having an air gap contact separation in all active in the fixed wiring according to the National Wiring Regulation.

conductors should be

When wiring, please choose the corresponding chart, or it may cause damage.The

signs of the indoor terminal block in the some of following figures may be replaced by L N LI N1.

23

15. SAFETYPRECAUTIONS

Read the safety precautions carefully before installing the unit.

m Stated below are important safety issues that must be obeyed.

_WARNING Means improper handling may lead to personal death or severe injury.

CAUTION Means improper handling may lead to personal

injury or property

loss.

.........

Please entrust the distributor or professionals to install the unit.

Installation by other persons may lead to imperfect

installation,

lectric shock or fire.

Adhere to this installation manual.

Imporper installation may lead to electric shock or fire.

Reinstallation must be performed by professionals.

improper

installation may lead to electric

shock or fire.

Do not uninstall the unit randomly.

Random uninstalling may lead to abnormal operation, heating or fire of the air condition.

NOTE

(_ Do not install the unit in a place vulnerable to leakage of flammable gases.Once

flammable gases are leaked and left around the wire controller, fire may occure.

(_) Do not operate with wet hands or let water enter the wire controller.

Otherwise, electric shock may occur.

Q The wiring should adapt to the wire controller current.

Otherwise, electric leakage or heating may occur and result in fire.

Q The specified cables shall be applied

in the wiring.

No external force may be applied to the terminal.

Otherwise, wire cut and heating may occur and result in fire.

24

Select the installation |ocation

Don't install at the place where cover with heavy oil, vapor or sulfureted gas, otherwise, this product would be deformed that would lead to system malfunction.

Preparation before installation

1. Please confirm that all the following parts you have been supply.

Wire controller

Installation and owner's manual

Screws

Wall plugs

Screws

Plastic screw bars

The connective wires group

2. Prepare the following assemblies on the site.

3

3

2

2

1

1

1

M4X20

(For Mounting on the Wall)

For Mounting on the Wall

M4X25

(For Mounting on switch box)

For fixing on switch box

Optional

Switch box

Wiring Tube(Insulating

Sleeve and Tightening

Screw)

1

1

25

Precaution of install the wire controller

1. This manual provides the installation method of wire controller.

Please refer to the wiring diagram of this installation manual to wire the wire controller with indoor unit.

2. The wire controller working

in low voltage

loop circuit. Forbid to directly contact the cable of 220Vcommercial electricity or of 380V high voltage, and don't wire this kind of wire in the said loop; wiring clearance between configured tubes should at the range of 300NSOOmm or above.

3. The Shielded wire of the wire controller must be grounded reliable.

4. Upon finish the wire controller connection, do not employed tramegger to detect the

insulation.

5. The connective cable of wire controller should not be longer than 20 meters.

26

1.Wired remote controller structure size figure

4.7/120

0.8/21

0.5/13.1

_"q. t

(:3

04

o_

i m

I i i

U

J

I

50

Fig 17-1

2.Wiring

Principle Sketch:

5 o o

.'=

Wire Joint, 5p [

'\

"\1 i

I

Infraed Pipe

A

C

D

',

A --

--

...............................

C

I

]--

I

I --

' D

--

I

T"-

_ g

--

5-Core Shield Cable, the length I

is decided by installation i

I

J

1

,

1

I

I

'

',NUN

+5V

1

GND

',Indoor Unit Switch Board

', Indoor Unit

L ..............................

Fig 17-2 oo

I

co

I

27

f

3.Wiring figure

/

5-core wire

The connective wires group

\ display board

"_ Fig 17-3

J

• Connect the female joint of wires group from the mainboard with the male joint of connective wires group.

(See Fig 17-3)

• Please connect the other side of connective wires group with the male joint of wires group leads from wire controller.

(See Fig 17-3)

4.Remove

the upper part of wire controller

• Insert a slot screwdriver into the slots in the lower part of the wire controller (2 places), and remove the upper part of the wire controller.

(Fig 17-4)

NOTICE

The PCB is mounted in the upper part of the wire controller.

Be careful not to damage the board with the slot screwdriver.

Slots

Fig 17-4

28

4. Fasten the back plate of the wire controller

e For exposed mounting, fasten the back plate on the wall with the 3 screws (M4x20) and plugs. (Fig 17-5)

Back plate

Screws (M4x20)

Fig 17-5

For flush-mounting, fasten the back plate on the switch box with 2 screws (M4x25) and fasten it on the wall with 1 screw (M4x20).

(Fig 17-6)

Switch box

Back plate

Screw (M4x20)

Screws (M4x25) __

Fig 17-6

NOTICE

Put on a flat surface. Be careful not to distort the back plate of the wire controller by overtightening the mounting screws.

29

17. INSTALLATIONMETHOD

5. Battery installation

Fig 17-7

Put the battery into the installationsite and make sure the positive side of the battery is in accordance with the positive side of installationsite.(See Fig 17-7)

Please set the time corrected on the first time operation.

Batteries in the wire controller can timing under power failure which ensure the time keep right. When the power restores, if the time displayed is not correct, it means the battery is dead and replace the battery.

3O

6. Wiring

Top side wire outlet

Left side Right side wire outlet I L /

__! o c:::::Do

7 o c:::D o

I o o wire outlet

Bottom side wire outlet

A. For exposed mounting, four outletting positions.

There are three need cutting.

1

%'

Cutting place of right side wire outlet

Cutting place of top side wire outlet

Cutting place of left side wire outlet

Fig 17-8

Embedded switch box wiring

&Shielded wiring

Wiring through the wall

Putty__

\ Trap

"/,4mF////.

/AIV////

7.4mF///A

I/JmV///i

/_z.4,r!_/_//_

Putty r/A

/i

"Trap

Wiring hole

Fig 17-9

Wall hole and wiring hole

Diameterof wall hole: ¢20mm

Fig 17-10

CAUTION

Avoid the water enter into the wired remote controller, use trap and putty to seal the connectors of wires during wiring installation.(Fig 17-10)

When under installation, reserve certain length of the connecting wire for convenient to take down the wired remote controller while during maintenance.

Trap

3!

7.Reattach

the upper part of the wire controller

• After adjusting the upper case and then buckle the upper case; avoid clamping the wiring during installation.

(Fig 17-11 )

Fig 17-11 f

AII the pictures in this may be slightly different

.The

purpose only.

shall prevail.

32

Copyr ght 2014 Carr er Corporat on 7310 W Morr s St •nd anapo s, N 46231

Manufacturer reserves

the right to change, at any time, specifications and designs without

Edition Date: 11/14

notice and without

obligations,

Catalog No: 40M BD=01SI

Replaces: New

advertisement

Related manuals

Download PDF

advertisement