Below you will find brief information for Wall Series Hot Air Generator KX5, Wall Series Hot Air Generator KX8. These are independent, forced convection heating appliances that can work with blown air gas, or gas oil burners, designed for room heating. They are divided in 4 categories, depending on the installation system: sealed with respect to the installation room, separate combustion air suction pipe and combustion products exhaust pipe, wall outlet, roof outlet, roof outlet or flue, combustion air suction from room and combustion products exhaust through roof outlet or flue.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Wall Series Hot Air Generator KX5, KX8 User Manual | Manualzz

HEAD OFFICE :

VIA BIBAN 56 ( Z.I. )

31030 CARBONERA

TREVISO - ITALIA

TEL. ++39 0422 445363

FAX ++39 0422 398646

EMAIL = [email protected]

“K X – V” and “K X – O”

WALL SERIES HOT AIR GENERATORS

USE & MAINTENANCE HANDBOOK

K X 5 & K X 8 Models

N.B.:

THIS HANDBOOK ATTAINS TO THE GENERATOR ONLY. PLEASE ALSO REFER TO

THE BURNER’S MANUAL.

THE INSTRUCTIONS HEREIN INCLUDED APPLY ONLY TO THE COUNTRY

MARKED ON THE APPLIANCE LABEL.

1

CONFORMITY DECLARATION

We, undersigned,

B.P.S. PRODUZIONE s.r.l.

DECLARE

that the K X -V and K X -O Series Hot Air Generators have been duly manufactured in compliance with the

90/396/CEE and the 89/392/CEE gas standards and also with the European Pr EN 1020 standard of 1993 and following changes.

TECHNICAL DATA

MODEL

CE GAS CERTIFICATION

NOMINAL THERMAL INPUT

NOMINAL THERMAL OUTPUT

THERMAL EFFICIENCY

METHANE

G20 (9.45 kW)

FUEL

CONSUMPTION

FIGURES at + 15 °C

METHANE

G25 (8.12 kW)

PROPANE

G31 (12.8 kW)

BUTANE

G30(13.8 kW)

GAS OIL

(11.8 kW)

DELIVERY at +20 °C

TREATED AIR WORKING STATIC

PRESSURE

TEMP. RISE

CENTRIFUGAL FANS

ELECTRICAL SUPPLY

INSTALLED ELECTRIC POWER

SOUND LEVEL at 3 m.

IN STANDARD INSTALLATION

WEIGHT

REQUIRED AIR VOLUME FOR

COMBUSTION

SMOKES MASS DISCHARGE

* V = Vertical *O = Horizontal

COUNTRY

ITALY

FRANCE

BELGIUM

SPAIN

HOLLAND

PORTUGAL

GERMANY

GREECE

AUSTRIA

SWITZERLAND

CATEGORY

II 2H3+

11 2Er3+

I 2ErB/I3+

II 2H3+

II 2L3B/P

II 2H3+

II 2ELL3B/P

I 3+

II 2H3B/P

II 2H3B/P

Kg/h

Kg/h

Kg/h m

3

/h

Pa

°C

CE

kW kW

µ

% m

3

/h m

3

/h

N. rev/1’

Watt dB (a)

Kg. m

3

/h g./sec

G 20

20

20

20

20

20

20

20

20

K5X-V*

58

53

91.5

6.13

7.14

4.53

4.2

4.9

4150

160

39

2

900

500

56

170

85

42

K5X-O* K8X-V*

58

53

91.5

93

84.6

91

6.13

7.14

4.53

4.2

4.9

4150

160

39

2 2

900 900

220 - 240 V/AC 50-60 Hz

500

56

650

58

170

85

42

235

130

67

9.8

11.5

7.3

6.7

7.8

7200

150

35

FEEDING PRESSURE in mbar

G 25

25

20

25

25

G 30

30

30

50

28

30

28

28

28

50

50

G 31

30

37

50

37

37

37

37

37

50

50

K8X-O*

93

84.6

91

9.8

11.5

7.3

6.7

7.8

7200

150

35

2

900

650

58

235

130

67

2

K X – V

HANGING HOT AIR GENERATOR MODELS GLOBAL VIEW

MODEL

K5X-V

K8X-V

A B C D E F G H I

ØL

1250 1000 600 1380 380 700 750 300 115 120

1350 1050 700 1478 428 800 850 350 140 140

ØM

N O P Q R

150 540 149 302 330 410

150 640 184 332 371 455

Pict.1

3

K X – O

HANGING HOT AIR GENERATOR MODELS GLOBAL VIEW

MODEL

K5X-O

K8X-O

A B C D E F G H I

ØL ØM

N O P Q R S

1250 1000 600 1380 380 700 750 300 115 120 150 540 149 302 330 410 125

1350 1050 700 1478 428 800 850 350 140 150 150 640 184 332 371 455 175

Pict.2

4

INSTALLATION EXAMPLES

SHOWING EXHAUST & SUCTION DUCTS AND THEIR MAXIMUM ALLOWED LENGTHS

Pict.3

5

INSTALLATION EXAMPLES

6

Pict.4

7

Pict.5

These are independent, forced convection heating appliances, equipped with fan, that can work with blown air gas or gas oil burners, designed for room heating.

They are divided in 4 categories, depending on the installation system :

1.

“C

13

” type : sealed with respect to the installation room, separate combustion air suction pipe and combustion products exhaust pipe, wall outlet. (Pict.3)

2.

“C

33

” type : sealed with respect to the installation room, separate combustion air suction pipe and combustion products exhaust pipe, roof outlet. (Pict.3)

3.

“C

53

” type : sealed with respect to the installation room, separate combustion air suction pipe and combustion products exhaust pipe, roof outlet or flue. (Pict.3)

4.

B

23

” type : combustion air suction from room and combustion products exhaust through roof outlet or flue (Pict.3)

WARNING

Please carefully read all the instructions given in this booklet, as they’ll be all very useful for both safe installation and proper use & maintenance operations.

Installation is to be carried out always strictly complying with the current standards of the country where the appliance is going to be used and following, of course, the instructions given by the maker. Only skilled operators and Authorised

Assistance Centres will be entitled to carry out installation. Please note that, should wrong installation cause harm to people or damage things, in no way the manufacturer will be held responsible for it.

Before opening, check well packing cardboard box and its contents. If any doubt, don’t use the unit but contact the supplier first.

Always keep packing parts away from children reach, as they may be harmful.

Keep suction grids clear.

In case of breakdown or failure: turn unit off, do not try to repair it on your own, call operator.

If you are going to leave the generator off for a long time, first make sure that in no way this could cause harm to anyone in any way.

This unit was designed to be used for heating purposes only. Any different use is not allowed as it may be dangerous.

Always keep this handbook with the unit.

Should the unit work in a house where disabled people and/or children live, it must be placed safely away from their reach. Always make sure that the access door to the inside control board stay locked.

GAS ESCAPE

In case of typical gas smell, do not turn on electric switches nor use telephone or any other appliance that could produce sparkles. Quickly open doors and windows to let fresh air in, lock the gas detecting hand-valve and call for qualified operator.

PERFORMANCE

The “K X” hot air hanging generator is an appliance that heats room air by exploiting the thermal energy resulting from combustion. This thermal exchange is obtained by a no-stop air jet lapping the heat-exchanger areas. The air jet comes from a centrifugal fan, without need of intermediate fluid. Thanks to their high heat performance (> 90%), safe working, low noise level, quick setting-up, the “K X” series units are the best for industrial plants, warehouses, gyms, greenhouses, swimming pools, and so on (however they should never work in places directly subject to atmospheric conditions).

GENERAL MANUFACTURING FEATURES

HEAT EXCHANGER ( 4 SMOKES REVOLUTIONS)

Made of welded stainless steel sheet, sealed tested to meet the current European standards, easy to check for standard cleaning and maintenance operations: a) Combustion chamber made of Aisi 430 stainless steel sheet, circular section, of suitable thickness and volume. b) Wide surface exchanging elements made of low thermal load high quality stainless steel, rhomboid section, granting lower resistance to air cooling and improved thermal efficiency. c) High quality stainless steel rear smokes collector, with wide inspection door for easy checking and cleanings of the exchanger. d) High quality stainless steel front smokes collector, which opening is closed by safety disk of suitable features, acting as overpressure valve.

8

OUTER CASING

No visible panel fixing parts : this gives the machine a new fashionable look, while enabling very easy checking too. The outer casing is made of removable panels made of pre-varnished galvanised sheet, with an upper protective film.

The burner housing is totally sealed with respect to the room. Checking door.

The areas the most subject to radiant heat by the exchanger are provided with noise and heat proof insulation

Baffle for air flow direction, double range of vertical and horizontal wings, each one adjustable to improve even air flow diffusion.

VENTILATION UNIT

It is made of two low noise centrifugal fans, with built-in engine, granting great air delivery. They are provided with mesh safety panels for accident prevention.

BURNER UNIT

It’s made of:

- Hooking plate with peep-hole to check electrodes and flame.

- Certified blow type burner, gas or gas oil working (option on request).

CONTROL AND SAFETY THERMOSTATS

The generator is provided with three thermostats which are already assembled and electrically connected, as follows :

"Fan" thermostat, liquid expansion type. It starts up the fans when average air temperature is approx. 40°C, to avoid cool air getting into the room, then it turns them off when burner goes off, when the temperature raises to 40°C.

“Limit” thermostat, liquid expansion type. It stops the burner when the average air temperature gets approximately over 80°C.

“Maximum” thermostat, hand reset, liquid expansion type: it definitely stops burner in case of anomalous air overheating. If necessary, you can reset it by hand by pressing the key, however only after detecting and removing the reason of such anomalous behaviour.

OPTIC SIGNALLING UNIT

Green light, to show correct working.

Red light, it shows any electronic board blockage.

OPENING for SMOKES EXHAUST

The combustion products are exhausted outside through a round opening on the appliance, to be connected to a metal pipe in the permanent way.

This pipe must be sized as follows :

It must have wider or same diameter than the opening , with no section reduction..

Smooth inside surface. If wrinkled flex pipe was to be used, first make sure that the increased loss of load would not involve “unhealthy” combustion conditions and too much of a counter-pressure inside the combustion chamber. Please check the burner’s working field in the attached manual.

With the C13 and the C33 types the length must not exceed 4 m. (please remember that an elbow is equal to approx. 0.8-

1 m. of straight pipe).

With the C53 and the B23 types, please remember that the length must not exceed 6 m. (please remember that an elbow is equal to approx. 0.8-1 m. of straight pipe).

COMBUSTION AIR INLET

The combustion air gets in through a circular opening, protected by a net made of meshes smaller than 16 mm..

If the appliance was installed in a place with no air intakes from outside, the combustion air intake too must be connected to the outside, to grant a “sealed chamber” performance.

The same has to be done in case of an “under depression” room, or a dusty room, to avoid any anomalous working of the burner or the flooding of it.

The installation system length must not exceed 4 m. ( keeping in mind that each elbow is long about 0,8-1 Mt. of straight pipe) and should be provided with an outside protecting terminal top the obstruction section of which must not be wider than

40 cm

2

.

FLUES

All flues have to be made complying with the standards of the country where the generator is going to be used

Every appliance should be provided with its own flue.

The minimum diameter should never be under 220 cm

2

.

Every flue should be provided on the bottom with a special chamber for collecting and exhausting the liquid waste stuff.

With gas oil working appliances always remember that the flue width must never be smaller than the joint to the chimney. We recommend in fact to make the flue a 15-30% bigger, and well refined.

9

With gas working appliances, the flue diameter must be long 4 cm

2

per each installed power kW.

The flue must be insulated so that the temperature will decrease less than one degree per meter.

The chimneys openings must exceed one meter the top of roof, parapet or any obstacle standing at least 10 meters away.

OPTIONS FEATURES - upon request

To make the generators installation easier, the following options are available : ducts, elbows, windproof terminals for air

suction and smokes exhaust. Just specify required pieces and sizes when ordering.

Adapter:

made of galvanised steel sheet : by this one flue diameter and combustion air suction opening can be adjusted to fit any size available in Europe, as required by the EN 303-3 rule of 1996.

Shelves :

made of painted pressed stainless steel. Wall hooking plate.

Fireproof shutter for air recycling and delivery (REI 120 certified) : it stops the generator air delivery and suction circle, when the temperature is over than required. It is made of a rotating blade made of cardboard plaster, some blade rabbet fillets in the shut position, a control device including a set/reset lever, a return spring, a magneto-thermal switch with fuse being set at 70°, and a galvanised stainless steel supporting structure with 40 mm flanges . Ready for canalisation connection : we recommend to set a micro-switch connected online to the burner, so to open the circle when the shutter is working.

SHIPPING & PACKAGING

Our KX wall hanging appliances are delivered on pallet; accessories are packed separately.

Shipping, unloading and handling of the goods are all operations to be made very carefully in order not to damage goods : always handle the appliance from the bottom only.

INFORMATION for SKILLED INSTALLING OPERATORS

Install the appliance strictly complying with the rules in force in your country

!

When choosing the place where to install the unit please keep well in mind the following points :

The appliance must never be placed inside wall recesses

It must be fixed 2,5-3 Mts. up the floor, so that the air flow would not be shot onto the people in the heated area

Always grant easy connection to the fuel mains

Always grant easy connection between appliance and smokes exhaust and combustion air suction pipes

If required by law, make necessary ventilation holes

The working temperatures field must be between – 5°C and + 40° C

There must be no obstacles too close to the generator as this would affect the proper hot air diffusion, complying with the current laws and safety rules in gas operated thermal plants

The generator is usually placed on wall hanging shelves ( the leaning point must only be the bottom of the appliance) to be conveniently fixed to a suitable structure, keeping the minimum distances from walls and ceilings, in order to :

- grant the safe recycling of the air to be heated;

- make cleaning and maintenance operations easier;

- avoid depression that would rise in case the appliance was too close to ceiling and wall, which would inhibit the correct air cooling inside the combustion chamber.

In case holes were made across flammable walls, please note that an insulation must be provided around the smokes exhaust of the size of 5 cm at least.

Please note: - Before installing the unit, make sure with the Local Gas Supplying Agency that the maximum gas capacity is actually available for the unit, and that mains pressure and kind of gas are compatible with the data stated in our

Technical Data Table here above.

POWER CONNECTIONS (without summer ventilation)

This unit has been manufactured in compliance with the CEE 73/23 standard, working with a current of 220/230 V/AC 50-60

Hz. Connection must be made by means of a “H05 VV-F” cable, 3+4 pole or 7 pole, section not less than 2,5 mm

2

. Connect through the proper terminal box, inside the appliance (pictures 6-7) strictly attaining to the wiring diagram and the lettering printed under the box (wiring diagram on page 16).

STANDARD CONNECTION

= Compulsory earth connection (yellow-green wire)

ph = Active phase connection

N = Neuter phase connection

2 = Connection to the burner - neuter;

3 = Connection to the room thermostat and burner phase;

10

4 = Connection to the room thermostat;

5 = Connection to the blockage light.

POWER CONNECTIONS (with summer ventilation)

This unit has been manufactured in compliance with the CEE 73/23 standard, working with a current of 220/230 V/AC 50-60

Hz. Connection must be made by means of a “H05 VV-F” cable, 3+5 pole or 8 pole, section not less than 2,5 mm

2

. Connect through the proper terminal box, inside the appliance (pictures 6-7), strictly attaining to the wiring diagram and the lettering printed under the box (wiring diagram on page 17).

= Compulsory earth connection (yellow-green wire)

ph = Active phase connection

N = Neuter phase connection

1 = Connection to summer ventilation

2 = Connection to the burner - neuter

3 = Connection to the room thermostat and burner phase

4 = Connection to the room thermostat

5 = Connection to the blockage light.

WARNING : The neuter-phase connection must be absolutely correct. Any failure to observe the

correct polarity will make the appliance block up.

We recommend to make the connection preferably in the permanent way by means of a magneto/thermal switch of suitable power. The contacts should be 3 mm. open at least. The omnipolar switch or the plug (connection by means of cable and plug) must be mounted in places easy to reach.

INSTALLATION & CONNECTION OF THE REMOTE CONTROL BOARD (option)

Connect the remote control board (optional) on the special plug, on positions 1 e 2, keeping the power diagram and the numbers as printed on the same terminal panel. It has to be set in a place where there is constantly a medium temperature, between 1,5 and 1,7 Mts. from the floor.

HOW TO CHOOSE THE BURNER

To ensure proper unit working, burner’s flame pipe must be at least as long as the depth of the combustion chamber mouth

(mm.60) and the pressure value for the available combustion air must be higher than take-off and operating pressure values inside the combustion chamber (Pa 30). Before choosing it, make sure that the value is Pa 30 and attain to the pressurisation diagram as given in burner handbook.

WARNING

:

The correct adjusting of the burner thermal capacity will depend on whether this adjusting was made by a qualified installing operator or not. The maker cannot be held responsible for any direct damage resulting from wrong installing or adjusting.

FIRST START - GAS WORKING BURNER

To carry out the first start-up please follow the instructions below:

Check that the control board main switch is off.

Open gas tap and let air leak out from the pipeline, if necessary (see burner manual)

Give voltage

Remove any blockage (see burner manual)

Adjust burner to the required output (see burner manual)

Make sure that the gas consumption figure, the one you now read from the gas meter, does correspond to the one stated in the manual or on the appliance plate

When all the adjustments are made, it is compulsory to seal all adjusting devices (example : paint drop)

FIRST START - GAS OIL WORKING BURNER

To carry out the first start-up please follow the instructions below:

Check that the control board main switch is off.

Make sure that the burner nozzle output and other features were as per manual and that thermal output was as stated in the manual or on the appliance plate.

Open gas oil tap and let air leak out from the pipeline, if necessary (see burner manual)

Give voltage

Remove any blockage (see burner manual)

Adjust burner to the required output (see burner manual)

Make sure that, when burner is working, the pump pressure is as stated in the manual.

… AND NOW THE UNIT IS READY TO WORK.

11

PLEASE NOTE : THE ROOM TEMPERATURE MUST BE SET ON THE ROOM THERMOSTAT ONLY AND

NOT ON THE APPLIANCE THERMOSTAT.

STANDARD MAINTENANCE OPERATIONS

In order to grant the appliance always the best performance and upkeep, timely carry out maintenance operations at least once a year, we suggest at the end of the cold season.

All maintenance operations can be carried out only when the appliance is cold, provided the electric power is disconnected and the gas or gas oil tap shut.

CLEANING THE EXCHANGER WHEN THE WINTER SEASON IS OVER

For this operation just take the following steps:

Take burner out of its housing.

Remove rear panel from the appliance, remove inspecting door placed in front of the exchanger.

Clean exchanging elements by using a stainless steel tube brush.

By a vacuum cleaner remove any soot from combustion chamber, coming from exchanging elements.

Also clean exchanger outer areas.

If necessary, replace little inspection door gasket, in order to ensure always perfect sealing.

CLEANING THE BURNER

See burner manual.

FAN KEEPING

Check that no dirt was left on it. Clean it by a vacuum or compressed air pump.

HEATING FAN

Remove it and clean it well by a paintbrush or compressed air.

TROUBLESHOOTING - CAUSES & REMEDIES

In case of malfunctions in the hot air generator, first check the following points:

- Power must be connected.

No voltage jumps exceeding +10% / -15%.

Fuses must be in order.

There must be enough gas or gas oil available.

- Pressure and output of gas or gas oil must be exactly as stated in our technical features table.

Here below please find a troubleshooting list, where you can find possible causes of the trouble and look up suggested remedies in order to restore the correct performance of the unit.

MALFUNCTION

Fans do not start. -

POSSIBLE CAUSE

No voltage

REMEDY

Check main switch position.

Check line.

Check connections.

Check fuses.

Exchanger overheating

-

-

-

Fan thermostat being damaged

Burner providing too much heat

Air fans out of work

Replace it

Set as per plate values.

Check power connections

Fan damaged, replace it

Air suction choked

Too big choke in delivery

Remove choke

Remove choke

Burner does not start Hand reset thermostat set on Set it off

Burner setting the reset thermostat on Too big choke in air delivery, over Remove choke thermostat bulb

Burner stopping when normally working, even when room temperature lower than set by thermostat

Room thermostat being damaged, or placed in the wrong way

Remove it or place it in the correct way.

Unit working no-stop, but temperature Unit thermal power too poor to Replace unit by another one having staying lower than scheduled heat the room suitable thermal power.

12

See before Consumption lower than required Adjust it to plate figure.

Dirty exchanger

Unit producing steam and getting dirty Too short gas oil consumption

-

-

Clean it.

Adjust to plate value.

PLEASE NOTE : ALL REPAIRS MUST BE CARRIED OUT BY QUALIFIED SKILLED TECHNICAL PERSONNEL

ONLY. ONLY ORIGINAL SPARE PARTS CAN BE USED. IT IS NOT ALLOWED TO OPEN

THE UNIT OR TAMPERING WITH UNIT COMPONENTS, OTHER THAN RECOMMENDED

MAINTENANCE PARTS.

INFORMATION FOR THE USER

This appliance has been designed to be used on industrial plants, trade buildings, artisan workshops, warehouses, gyms, hothouses, pools, and many other public places, except for homes. Also, never use it in open-air.

WORKING STAGES

Put main switch on (if any).

Open gas or gas oil tap.

Schedule room thermostat at the required temperature.

The appliance now becomes automatic in all its functions.

The burner starts and, after a pre-washing time, it starts running. A few minutes after burner’s start, fan will start working too, blowing hot air into the room.

As soon as room temperature will raise to the figure scheduled on room thermostat, burner will stop and - about 4 minutes later - fan will stop too.

This full cycle will be automatically repeated from the beginning, every time room temperature goes below the temperature scheduled on the room thermostat.

STOP or TEMPORARY STOP

To stop the appliance, just turn off room thermostat switch or summer/winter switch if any.

WARNING : DON’T CUT OFF VOLTAGE WHEN THE APPLIANCE IS HOT AND THE FAN WORKING. This because the thermal energy stored inside the exchanger would activate the safety “LIMIT” thermostat, so it would become necessary to reset it by hand. Also, this wrong operation would involve overheating to the heat exchanger.

REST AT THE END OF THE COLD SEASON

When the cold season is over, take current off definitely, by depressing the main switch.

Shut gas or gas oil tap.

ASSISTANCE

You can ask for technical assistance either contacting your retailer or applying direct to: who will give you the address of the assistance service nearest to you.

13

K 5 X - V & K 8 X – V

MODELS GLOBAL VIEW

LEGENDA:

1- SMOKES EXHAUST WAY OUT

2- AIR SUCTION INLET

3- CHIMNEY COLLECTOR

4- BLOCKAGE SPY LIGHT

5- WORKING SPY- LIGHT

6- SUPPORT FOR BRACKETS

7- AIR BAFFLES

8- FIRE PLACE

9- EXCHANGER

10- NOISE/HEAT INSULATOR

11- FAN

12- HEAT INSULATOR

13- CHAMBER CHECKING PEEP-

HOLE

14- BURNER SUPPORT PLATE

15- ELECTRONIC BOARDS

SUPPORT PLATE

16- TERMINAL BOX WITH FUSE

17- BURNER THERMOSTAT

18- FAN THERMOSTAT

19- RESET THERMOSTAT

20- KEY LOCK

21- SEALING PROTECTION

22- CHAMBER BRACKET

SUPPORT

23- INSIDE AIR BAFFLE

24- DOOR FOR CHECKING AND

CLEANING

25- “FAN” BULB

26- “LIMIT” BULB

27- “RESET” BULB

Pict. 6

14

K 5 X - O & K 8 X – O

MODELS GLOBAL VIEW

LEGENDA :

1- SMOKES EXHAUST WAY OUT

2- AIR SUCTION INLET

3- CHIMNEY COLLECTOR

4- BLOCKAGE SPY LIGHT

5- WORKING SPY LIGHT

6- SUPPORT FOR BRACKETS

7- BAFFLES

8- FIRE PLACE

9- EXCHANGER

10- NOISE/HEAT INSULATOR

11- FAN

12- HEAT INSULATOR

13- CHAMBER CHECKING PEEP-

HOLE

14- BURNER SUPPORT PLATE

15- ELECTRONIC BOARDS

SUPPORT PLATE

16- TERMINAL BOX WITH FUSE

17- BURNER THERMOSTAT

18- FAN THERMOSTAT

19- RESET THERMOSTAT

20- KEY LOCK

21- SEALING PROTECTION

22- CHAMBER BRACKET

SUPPORT

23- INSIDE AIR BAFFLE

24- DOOR FOR CHECKING AND

CLEANING

25- “FAN” BULB

26- “LIMIT” BULB

27- “RESET” BULB ”

Pict. 7

15

“K X”

HANGING SERIES HOT AIR GENERATORS WIRING DIAGRAM

F = Fuse 5x20 T 3.15A

MC = Fan engine

TM = Maximum thermostat

TL = Limit thermostat

TF = Fan thermostat

MI = Fan inside terminal board

LF = Working spy light

LB = Blockage spy light

MV = Fan terminal board

MB = Burner terminal box

BR = Blow type burner

* OUTSIDE =

OPTIONS TO BE INSTALLED

BY THE CUSTOMER

* IMT = Magneto-thermal switch

* TA = Room thermostat

Pict. 8

16

“K X”

HANGING SERIES HOT AIR GENERATORS WIRING DIAGRAM

FOR APPLIANCES SET READY FOR SUMMER VENTILATION BY FAN

F = 5x20T 15A Fuse

MC = Fan engine

TM = Maximum thermostat

TL = Limit thermostat

TF = Fan thermostat

MI = Fan inside terminal board

LF = Working spy light

LB = Blockage spy light

MV = Fan terminal board

MB = Burner terminal box

BR = Blow type burner

* OUTSIDE =

OPTIONS TO BE INSTALLED BY THE

CUSTOMER

*IMT = Magneto-thermal switch

*TA = Room thermostat

*DV = Summer/winter switch

Pict. 9

17

“K X”

Hanging Series Hot Air Generators WIRING DIAGRAM Where REMOTE

CONTROL Is Used

19

advertisement

Key Features

  • Forced convection heating
  • Gas or gas oil burner operation
  • Room heating application
  • Sealed combustion chamber
  • Separate air suction and exhaust
  • High thermal efficiency

Frequently Answers and Questions

How do I start the Wall Series Hot Air Generator?
Make sure the control board main switch is off, open the gas or gas oil tap. Schedule the room thermostat at the required temperature. The appliance will then work automatically, with the burner starting, then the fan, and cycling as needed to maintain the desired temperature.
How do I clean the exchanger in the Wall Series Hot Air Generator?
Remove the burner, rear panel and inspection door. Clean the exchanging elements with a stainless steel tube brush. Vacuum any soot from the combustion chamber and clean the exchanger outer areas.
What are the possible causes of the Wall Series Hot Air Generator not starting?
Possible causes include no voltage, blown fuses, a blocked hand reset thermostat, a choked air suction, or a blocked air delivery.