- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- mundoclima
- Series Aerotherm V2 “Aerotherm Heat Pump”
- Installation manual
- 51 Pages
mundoclima Series Aerotherm V2 “Aerotherm Heat Pump” Installation manual
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
▼
Scroll to page 2
of
51
AEROTHERM V2 User & Installation manual www.mundoclima.com SO30140 to SO30153 English User & Installation manual Aerotherm V2 Contents 1 Instruction to Users���������������������������������������������������������������������������������1 2 Safety Considerations�����������������������������������������������������������������������������2 3 Diagram of the Operating Principle���������������������������������������������������������4 4 Operating Principle of the Unit����������������������������������������������������������������4 5 Nomenclature������������������������������������������������������������������������������������������6 6 Installation Example �����������������������������������������������������������������������������7 7 Main Components ����������������������������������������������������������������������������������9 7.1 Indoor unit�������������������������������������������������������������������������������������������������� 9 7.2 Outdoor unit ������������������������������������������������������������������������������������������� 10 8 Installation Guideline of the Unit������������������������������������������������������������12 8.1 Instruction to installation�������������������������������������������������������������������������� 12 8.2 Installation of outdoor unit����������������������������������������������������������������������� 12 9 Installation of Indoor Unit�����������������������������������������������������������������������14 9.1 Select installation location of indoor unit ������������������������������������������������ 14 9.2 Install process of indoor unit�������������������������������������������������������������������� 14 9.3 Outline dimension of indoor unit ������������������������������������������������������������ 16 9.4 Space requirements for installation��������������������������������������������������������� 16 9.5 Precautions on installation of indoor unit������������������������������������������������� 16 9.6 Water volume and pump capacity (with pump)��������������������������������������� 17 9.7 Water volume and expansion vessel pressure���������������������������������������� 17 9.8 The method of calculating the charging pressure of expansion vessel��� 18 9.9 Selection of expansion vessel����������������������������������������������������������������� 18 10 Connection of Pipeline �����������������������������������������������������������������������19 10.1 Connection of outlet pipe for indoor & outdoor unit ������������������������������ 19 10.2 Installation of protective layer on connection pipe �������������������������������� 19 User & Installation manual Aerotherm V2 11 Remote Air Temperature Sensor���������������������������������������������������������21 12 Thermostat������������������������������������������������������������������������������������������22 13 2-Ways Valve���������������������������������������������������������������������������������������23 14 3-Way Valve����������������������������������������������������������������������������������������23 15 Other Auxiliary Heat Sources �������������������������������������������������������������24 16 Remote ON/OFF (Gate-controller) ����������������������������������������������������������������������������������� 24 17 Filling of Refrigerant����������������������������������������������������������������������������25 18 Installation of Insulated Water Tank ����������������������������������������������������25 18.1 Installation measure������������������������������������������������������������������������������ 25 18.2 Connection of waterway system .......................������������������������������������ 26 18.3 Electric wiring work ������������������������������������������������������������������������������� 28 19 Wring Diagram�������������������������������������������������������������������������������������30 19.1 PCB outline�������������������������������������������������������������������������������������������� 30 19.2 Electric wiring work�������������������������������������������������������������������������������� 35 20 Debugging Operation of Unit ��������������������������������������������������������������43 20.1 Check before startup����������������������������������������������������������������������������� 43 20.2 Test run�������������������������������������������������������������������������������������������������� 44 21 Daily Operation and Maintenance ������������������������������������������������������45 22 Operation Range���������������������������������������������������������������������������������47 User & Installation manual Aerotherm V2 1 Instruction to Users Thank you for choosing our Air to water Heat Pump. Please read this manual carefully before installation and use the unit correctly according to the following procedure. ◆◆ After receipt of the unit, check it for appearance, unit model compared with your desire and attachments. ◆◆ For proper installation and future maintenance please read this Instruction and keep it carefully. ◆◆ Design and installation work of the unit must be performed by authorized personnel according to applicable laws and regulations and this Instruction. ◆◆ After installation work, the unit can not be energized unless there is not any problem in check. ◆◆ Ensure periodical clean and maintenance of the unit after normal operation of the unit for longer life and reliable operation. ◆◆ For improvement of products, there should be not additional notice of amendment of the contents. ◆◆ This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. ◆◆ Children should be supervised to ensure that they do not play with the appliance. Notice! This product must not be disposed together with the domestic waste. This product has to be disposed at an authorized place for recycling of electrical and electronic appliances. 1 User & Installation manual Aerotherm V2 2 Safety Considerations Please read the following contents carefully before operating. WARNING ■■Once abnormality like burning smell occurs, please cut off the power supply immediately and then contact with service center. If the abnormality still exists, the unit may be damaged and electric shock or fire may result. ■■Don't operate the unit with wet hand. ■■Before installation,please see if the voltage of local place accords with that on nameplate of unit and capacity of power supply, power cord or socket is suitable for input power of this unit. Otherwise, it may cause electric shock. ■■S p e c i a l c i r c u i t m u s t b e adopted for power supply to prevent fire. ■■Be sure to pull out the power plug and drain the indoor unit and water tank when unit is not in use for a long time. ■■Never damage the electric wire or use the one which is not specified. Do not use octopus multipurpose plug or mobile terminal board for wire connection. Otherwise, the accumulated dust may cause overheating,fire or freeze of water tank or coaxial heater exchanger in winter. Otherwise, it may cause overheating or fire. ■■Before cleaning please cut off the power supply. ■■The power supply must adopt special circuit with leakage switch and enough capacity. ■■User can not change power cord socket without prior consent. Wiring working must be done by professionals. Ensure good earthing and don't change earthing mode of unit. Otherwise, it may cause electric shock or damage. 2 User & Installation manual ■■Earthing: the unit must be earthed reliably ! The earthing wire should connect with special device of buildings. If not, please ask the qualified personnel to install. Furthermore, don't connect earth wire to gas pipe, water pipe, drainage pipe or any other improper places which professional does not recognize. ■■Don't step on the top of the unit or place anything on it. There is the danger of fall of things or people. ■■P l e a s e n o t e w h e t h e r t h e installation stand is firm enough or not. Aerotherm V2 ■■N e v e r i n s e r t a n y f o r e i g n matter into uint to avoid damage . And never insert your hands into the air outlet of outdoor unit. ■■Don't attempt to repair the unit by yourself. Improper repair may cause electric sh o ck o r f i re , so yo u sh o u l d contact the service center to repair. ■■Never block the air inlet and outlet of unit. ■■Keep pressurized spray, gas holder and so on away from the unit above 1m . It may reduce efficiency or cause stop of the unit and even fire. ■■Unit should be installed at the place with good ventilation to save energy. It may cause fire or explosion. ■■When there is not water in water tank, never power the unit on to run. If damaged, it may cause fall of the unit and injury of people. Notice! (1) Before installation, please check if the adopted power is accordance with that listed on nameplate, and check the safety of power. (2) Before using, please check and confirm if wires and water pipes are connected correctly to avid water leakage, electric shock or fire etc. (3) Don’t operate the unit with wet hand, and don’t allow children to operate the unit. 3 User & Installation manual Aerotherm V2 (4) The On/off in the instruction is for the operation to on and off button of PCB for users; cut off power means to stop supplying power to the unit. (5) Don’t directly expose the unit under the corrosive ambient with water or dampness. (6) Don’t operate the unit without water in water tank .The air outlet/inlet of unit can not be blocked by other objects. (7) The water in unit and pipeline should be discharged if the unit is not in use, to prevent the water tank, pipe line and water pump from frost-cracking. (8) Never press the button with sharp objects to protect manual controller. Never use other wires instead of special communication line of the unit to protect control elements. Never clean the manual controller with benzene, thinner or chemical cloth to avoid fading of surface and failure of elements. Clean the unit with the cloth soaked in neutral eradicator .Slightly clean the display screen and connecting parts to avoid fading. (9) The power cord must be separated with the communication line. If there is any question, please contact with local dealer, authorized service center, agencies or our company directly. 3 Diagram of the Operating Principle OUTDOOR UINT INDOOR UINT 3 R1T 9 8 t M 4 5 6 R2T 17 20 R5T 11 12 t 13 M M 10 19 t M 2 7 R4T t 5 1 18 R3T t t t 1 compressor 2 four-way valve 3 finned coil exchanger 4 fan motor 5 filter 6 electronic expansion valve 7 plate heat exchanger 8 pump 9 air-vent valve 14 10 electric heater 11 flow switch 12 3-way valve 13 2-way valve 14 by-pass valve 15 under-floor heating 16 radiator 17 other thermal system 18 water tank 15 R6T 16 R7T 19 expansion tank 20 safety valve R1T plate outlet temperature sensor R2T Liquid line temperature sensor R3T gas line temperature sensor R4T returning water temperature sensor R5T leaving water temperature sensor R6T water tank temperature sensor 1 R7T water tank temperature sensor 2 4 Operating Principle of the Unit DC Inverter Air to Water Heat Pump is composed of outdoor unit, indoor unit and internal-fan coil water tank. Operation functions: (1) Cooling; (2) Heating; (3) Water heating; (4) Cooling +water heating; (5) Heating+ water heating; (6) Emergency mode; (7) Quick water heating; 4 User & Installation manual Aerotherm V2 (8) Holiday mode; (9) Forced Operation Mode; (10) Silent mode; (11) Disinfection mode; (12) Weather-dependent Operation; (13) Floor debugging (14) Air removal of the water system Cooling: in cooling mode, the refrigerant is condensed in the outdoor unit and evaporated in the indoor unit. Via the heat exchange with water in the indoor unit, the temperature of water decrease and it releases heat while the refrigerant absorbs heat and evaporates. With the help of wired controller, the outflow temperature can meet the user’s requirement. Through the control of valve, the low-temperature water in the system is connected with indoor fan coil and underground pipe, and exchanges heat with the indoor air so that the indoor temperature decreases to the required range. Heating: in heating mode,the refrigerant evaporates in the outdoor unit and is condensed in the indoor unit. Via the heat exchange with water in the indoor unit, the water absorbs heat and its temperature increase while the refrigerant releases heat and is condensed. With the help of wired controller, the outflow temperature can meet the user’s requirement. Through the control of valve, the high-temperature water in the system is connected with indoor fan coil and underground pipe, and exchanges heat with the indoor air so that the indoor temperature increases to the required range. Water heating: in water heating mode: the refrigerant evaporates in the outdoor unit and is condensed in the indoor unit. Via the heat exchange with water in the indoor unit, the water absorbs heat and its temperature increase while the refrigerant releases heat and is condensed. With the help of wired controller, the outflow temperature can meet the user’s requirement. Through the control of valve, the high-temperature water in the system is connected with the coil pipe of bearing water tank, and exchanges heat with the water in the water tank so that the temperature of water tank increases to the required range. Cooling + water heating: when cooling mode exists together with the water heating mode, the user can set the priority of these two modes based on the needs. The default priority is heat pump. That is under the default setting, if cooling mode exists together with the water heating mode, the heat pump gives priority to cooling. In that case, water heating can only realized with e-heater of the water tank. Inversely, the heat pump gives priority to water heating and switches to cooling after finishing water heating. Heating+ water heating: when heating mode exists together with the water heating mode, the user can set the priority of these two modes based on the needs. The default priority is heat pump. That is under the default setting, if heating mode exists together with the water heating mode, the heat pump gives priority to heating. In that case, water heating can only realized with e-heater of the water tank. Inversely, the heat pump gives priority to water heating and switches to heating after finishing water heating. Emergency mode: this mode is only available for heating and water heating. When the outdoor unit stops due to malfunction, enter the corresponding emergency mode; as to heating mode, after entering the emergency mode, heating can only be realized through e-heater of the indoor unit. When the setting outflow temperature or indoor temperature is reached, the e-heater of indoor unit will stop running; as to water heating mode, the e-heater of indoor unit stops while the e-heater of water tank runs. When the setting temperature or water tank is reached, the e-heater will stop running. Quick water heating: in quick water heating mode, the unit runs according to the water heating control of heat pump and the e-heater of water tank runs at the same time. Forced Operation Mode: this mode is only used for refrigerant recovery and debugging for the unit. 5 User & Installation manual Aerotherm V2 Holiday mode: this mode is only available for heating mode. This mode is set to keep indoor temperature or leaving water temperature in a certain range, so as to prevent water system of the unit from freezing or protect certain indoor articles from freezing damage. When the outdoor unit stops due to malfunction, the two e-heaters of the unit will run. Disinfection mode: in this mode, the water heating system can be disinfected. When starting up the disinfection function and setting corresponding time to meet the requirement of disinfection mode, the function will start. After the setting temperature is reached, this mode will terminate. Weather-dependent Operation: this mode is only available for space heating. In Weatherdependent mode, the setting value (remote room air temperature or leaving water temperature) is detected and controlled automatically when the outdoor air temperature is changed. Silent mode: Silent mode is available in cooling, heating and water heating mode. In silent mode, the outdoor unit will reduce the running noise via automatic control. Floor commissioning: this function is intended to preheat the floor periodically for the initial use. Air removal of the water system: this function is intended to replenish water and remove air in the water system to make the equipment run at the stabilized water pressure. 5 Nomenclature CAPACITY HEATING (kW) COOLING 2 (kW) CODE DESCRIPTION S030140 S030141 S030144 S030145 S030148 S030149 S030152 S030153 OUTDOOR UNIT AEROTHERM 8 KW 1Ph MUNDOCLIMA INDOOR UNIT AEROTHERM 8 KW 1Ph MUNDOCLIMA OUTDOOR UNIT AEROTHERM 12 KW 1Ph MUNDOCLIMA INDOOR UNIT AEROTHERM 12 KW 1Ph MUNDOCLIMA OUTDOOR UNIT AEROTHERM 16 KW 1Ph MUNDOCLIMA INDOOR UNIT AEROTHERM 16 KW 1Ph MUNDOCLIMA OUTDOOR UNIT AEROTHERM 16 KW 3Ph MUNDOCLIMA INDOOR UNIT AEROTHERM 16 KW 3Ph MUNDOCLIMA 1 8,5 8,5 12,5 12,5 15,5 14,5 15,5 15,0 Note: 1 Capacities are based on the following conditions: Indoor Water Temperature 30°C/35°C,Outdoor Air Temperature 7°C DB/6°C WB; 2 Capacities are based on the following conditions: Indoor Water Temperature 23°C/18°C,Outdoor Air Temperature 35°C DB/24°C WB. 6 User & Installation manual Aerotherm V2 6 Installation Example CASE 1: Connecting Under-floor Coil for Heating and Cooling Under- floor coil Indoor Outdoor B T Shut off value T Remote room Thermostat(Field supply) By-pass value(Field supply) B Low temperature line High temperature line Note: ① Type of thermostat and specification should be complied with installation of this manual; ② By pass valve must be installed to secure enough water flow rate,and by pass valve should be installed at the collector; CASE 2: Connecting Sanitary Water Tank Under-floor coil Outdoor Indoor B 1m Sanitary water tank T Booster heater Shut off value T 3-wa y value(Field supply) Remote room Thermostat(Field suppl y) B By-pass value(Fi eld supply) High temperature line Note: Install the 3-way valve at 1m distance from the exit of the indoor unit. 7 Low temperature line User & Installation manual Aerotherm V2 Note: ① In this case, three-way valve should be installed and should be complied with installation of this manual; ② Sanitary water tank should be equipped with internal electric heater to to secure enough heat energy in the very cold days; CASE 3 : Connecting Sanitary Water Tank and Heat Emitters for Heating and Cooling Under-floor coil Outdoor Radiator Indoor B M 1m T Sanitary water tank FCU 1 FCU2 Booster heater Shut off value T Remote room Thermostat(Field suppl y) M 3-wa y valu e(Field supply) B By-p ass value(Field supply) 2-way value(Field supply) High tempe rature line temperature line Note: Install the 3-way valve at 1m distance from the exit of the indoor unit. Two-way valve is very important to prevent dew condensation on the floor and Radiator while cooling mode. 8 User & Installation manual Aerotherm V2 7 Main Components 7.1 Indoor unit SO30141 SO30145 SO30149 SO30153 External view (8 kW) (12 kW) (16 kW) (16 kW - 3 Ph) Internal view Safety Valve Air Vent Electric Heater Plate Heat Exchanger Expansion Tank Control Box Water Pump Control Panel Water Pressure Gage Flow Switch 9 User & Installation manual Aerotherm V2 7.2 Outdoor unit SO30140 (8 kW) External view Internal view Control Box DC Fan Motor Compressor 10 User & Installation manual SO30144 (12 kW) SO30148 (16 kW) SO30152 (16 kW - 3 Ph) Aerotherm V2 External view Internal view Control Box DC Fan Motor Compressor 11 User & Installation manual Aerotherm V2 8 Installation Guideline of the Unit 8.1 Instruction to installation (1) The installation of unit must be in accordance with national and local safety codes. (2) Installation quality will directly affect the normal use of air conditioner unit. The user is prohibited from installation by himself. Please contact your dealer after buying this machine. Professional installation workers will provide installation and test services according to installation manual. (3) Do not connect to power until all installation work is completed. 8.2 Installation of outdoor unit 8.2.1 Select installation location of outdoor unit (1) Outdoor unit must be installed on a firm and solid support. (2) Outdoor unit shall be installed close to the indoor unit, hence to minimize the length and bends of cooling pipe. (3) Avoid placing the outdoor unit under window or between two constructions, hence to prevent normal operating noise from entering the room. (4) Air flow at inlet and outlet shall not be blocked. (5) Install at a well-ventilated place, so that the machine can absorb and discharge sufficient air. (6) Do not install at a place where flammable or explosive goods exist or a place subject to severe dust, salty fog and polluted air. 8.2.2 Outline dimension of outdoor unit SO30140 (8 kW) 980 790 360 395 650 12 User & Installation manual Aerotherm V2 1326 1345 SO30144 (12 kW) SO30148 (16 kW) SO30152 (16 kW - 3 Ph) 340 378 412 900 572 Description: Unit: inch No. Name Remarks 1 Liquid-side Service Valve 3/8" 2 Gas-side Service Valve 5/8" 3 Handle 4 Air discharge Grill 8, 12, 16 kW & 16 kW (3-Ph) Used to cover or uncover the front case / >500 >1000 8.2.2 Space requirements for installation >2000 >500 >500 >2000 >500 13 User & Installation manual Aerotherm V2 8.2.3 Precautions on installation of outdoor unit (1) When moving outdoor unit, it is necessary to adopt 2 pieces of long enough rope to hand the unit from 4 directions. Included angle between the rope when hanging and moving must be 40°below to prevent center of the unit from moving. (2) Adopt M12 bolts components to tighten feet and under frame when installing. (3) Outdoor unit should be installed on concrete base that is 10cm height. (4) Requirements on installation space dimension of unit’s bodies are shown in following drawing. (5) Outdoor unit must be lifted by using designated lifting hole. Take care to protect the unit during lift. To avoid rusting, do not knock the metal parts. 9 Installation of Indoor Unit 9.1 Select installation location of indoor unit (1) Avoid direct sunshine. (2) Ensure the hanger rod, ceiling and building structure have sufficient strength to support the weight of air conditioner unit. (3) Drainage pipe is easy to connect out. (4) Indoor and outdoor connection pipes are easy to go outdoors (5) Do not install at a place where flammable or explosive goods exist or flammable or explosive gas might leak. (6) Do not install at a place subject to corrosive gas, severe dust, salty fog, smoke or heavy moisture. (7) Air flow at inlet and outlet air is not blocked. 9.2 Install process of indoor unit Step1:Drilling hole on the wall in the following draw. 500 463 823 900 expansion bolt hole unit outline 14 User & Installation manual Aerotherm V2 Step2:Releasing screws, detach front cover from the indoor unit. Step3: Attaching indoor unit to the wall make use of accessory expansion bolt. Expansion bolt Install wall CAUTION! ① While lifting the indoor unit, at least two persons should be joined. Weight of the indoor unit is more than 50kg. ② The indoor unit must be installed vertically to the ground and fastened securely. ③ Before commissioning, the dust-proof cap of the automatic relief valve must be loosened, other than entirely being removed away, and it can be tightened in case that it leaks. 15 User & Installation manual Aerotherm V2 9.3 Outline dimension of indoor unit 500 900 324 Description: Unit: inch No. Name Remarks 1 Leaving Water Pipe 1″Male BSP 2 Returning Water Pipe 1″Male BSP 3 Gas-side Pipe 5/8" 4 Liquid-side Pipe 3/8" 8, 12, 16 kW & 16 kW (3-Ph) 9.4 Space requirements for installation 250 200 800 1300 Service Space 9.5 Precautions on installation of indoor unit (1) Indoor unit shall be vertically mounted on the wall of the room with expansion bolt. 16 User & Installation manual Aerotherm V2 (2) Keep the indoor unit away from heat sources like heat sink and so on in the room as much as possible. (3) Keep the indoor unit as close as possible to outdoor unit. Level distance between connection pipes can not exceed 30m(8.0~16KW) or 20m(6.0kw) and vertical distance can not exceed 15m(8.0~16KW) or 10m(6.0kw). 9.6 Water volume and pump capacity (with pump) 8 maximum speed Hydraulic Head Loss(mH2O) Hydraulic Head Loss(mH2O) 8 7 6 5 4 3 2 medium speed 7 6 5 4 3 2 1 1 0 0 0 20 40 60 80 100 Water Flow Rate(l/min) 120 20 60 40 Water Flow Rate(l/min) 0 80 100 Note: ① The water pump is three speed-adjustable(maximum/medium/minimum), In most case, we strongly recommended to set speed as maximum; ② If the noise of the pump is not acceptable, we recommended change the default speed to medium speed, but to secure enough flow rate, do not set water speed as “Min”, it can lead unexpected flow rate error “EC”; Pre-pressure in expension vessel(Bar) 9.7 Water volume and expansion vessel pressure 2.5 2.0 1.5 1.0 0.5 0.0 0 50 100 150 200 250 300 350 400 Maximum total water volume(liter) Note: ① Expansion vessel is included which 10 liter and 1bar pre-pressure. ② Total water volume of 280 liter is default; If total water is changed because of installation condition, the pre-pressure should be adjusted to secure proper operation. If the indoor unit is located at the highest position, adjustment is not required; ③ Minimum total water volume is 20 liter; ④ To adjust pre-pressure, use nitrogen gas by certificated installer. 17 User & Installation manual Aerotherm V2 9.8 The method of calculating the charging pressure of expansion vessel The method of calculating the charging pressure of expansion vessel needed to be adjusted is as follows. During installation, if the volume of water system has changed, please check if the pre-set pressure of the expansion vessel needs to be adjusted according to the following formula: Bar(H ---the difference between installing location of indoor unit and the highest spot of water system.) Ensure that the volume of water system is lower than the maximum volume required in the above figure. If it exceeds the range, the expansion vessel does not meet the installing requirement. Installation height 1 difference Water volume <280L >280L <7 m Adjustment is not necessary 1. Pre-set pressure needs to be adjusted according to the above formula. 2. Check if the water volume is lower than the maximum water volume. (with help of the above figure) <7 m 1. Pre-set pressure needs to be adjusted according to the above formula. 2. Check if the water volume is lower than the maximum water volume. (with help of the above figure) The expansion vessel is too small and adjustment is not available. 1 Note:Installation height difference: the difference between installing location of indoor unit and the highest spot of water system; if the indoor unit is located at the highest point of the installation,the installation height difference is considered 0m; Example 1: The indoor unit is installed 5m below the outdoor unit and the total volume of the water system is 100L. Referring to the above figure, it is not necessary to adjust the pressure of the expansion vessel. Example 2: The indoor unit is installed on the highest spot of the water system and the total water volume is 350L. (1) As the volume of water system is higher than 280L, it is necessary to adjust the pressure of the expansion vessel be lower. (2) The formula of calculating pressure Bar (3) The maximum volume of the water system is about 410L. As the actual volume of the water system is 350L, the expansion vessel meets the installing requirement. (4) Adjust the pre-set pressure of the expansion vessel from 1.0Bar to 0.3Bar. 9.9 Selection of expansion vessel Formula: V--- Volume of expansion vessel C--- Total water volume P1--- Pre-set pressure of expansion vessel P2-- The highest pressure during running of the system (that is the action pressure of safety valve.) e---The expansion factor of water (the difference between the expansion factor of the original water temperature and that of highest water temperature.) 18 User & Installation manual Aerotherm V2 Water expansion factor in different temperature Expansion factor e Temperature(℃) 0 0.00013 4 0 10 0.00027 20 0.00177 30 0.00435 40 0.00782 45 0.0099 50 0.0121 55 0.0145 60 0.0171 65 0.0198 70 0.0227 75 0.0258 80 0.029 85 0.0324 90 0.0359 95 0.0396 100 0.0434 10 Connection of Pipeline 10.1 Connection of outlet pipe for indoor & outdoor unit (1) Align the expansion end of copper pipe with the center of threaded joint. Tighten the flaring nuts with your hands. (2) Tighten the flaring nuts with torque wrench until you hear a “click”. (3) Bend of fitting pipe shall not be too low; otherwise the fitting pipe might crack. Please use pipe bender when bending the fitting pipe. (4) When connecting outdoor and indoor unit, never pull the big and small joint of indoor unit with force, so as to prevent the tubes of indoor unit from cracking and causing leakage. (5) Connecting pipe shall be supported by a rack without transmitting its weight to other units. 10.2 Installation of protective layer on connection pipe (1) To avoid condensate dew or water leakage on connecting pipe, the air pipe and liquid pipe must be wrapped with heat preservation material and adhesive pipe for insulation from the air. 19 User & Installation manual Aerotherm V2 (2) The joints on indoor unit and outdoor unit must be wrapped with heat preservation materials and have no clearance against the wall surface of indoor unit and outdoor unit. (3) Wrap the pipe with tapes. 1). Use the adhesive tape to wrap the connecting pipe and cable into one bundle. To prevent condensate water from overflowing out of the drainpipe, the drainpipe shall be separated from connecting pipe and cable. 2). Wrap the heat preservation tape so that each ring of tape shall press half of the previous ring. 3). Fix the wrapped pipe onto the wall with pipe clamp. 4). Do not wrap the protective tape too tightly, as this will decrease the heat insulation performance. 5). After completing the protection work and wrapping the pipe properly, close the wall holes with sealing materials. No clearance Indoor unit Outdoor unit Indoor unit A A Outdoor unit B B Outdoor unit Indoor unit Oil trap A B 20 User & Installation manual Aerotherm V2 Pipe size (Diameter:Φ) gas Liquid Model Length B Elevation A Standard Max. Standard Max. Additional refrigerant 8 kW 5/8" 3/8" 5m 30m 0m 15m 50g/m 12 kW 16 kW 5/8" 3/8" 5m 30m 0m 15m 50g/m 5/8" 3/8" 5m 30m 0m 15m 50g/m 16 kW (3-Ph) 5/8" 3/8" 5m 30m 0m 15m 50g/m Aditional charge (g) = (L - 10) x 50 Note: ① No additional charge of the refrigerant is need when the pipe length is less than 10 m, if the pipe length is longer than 10m, additional charge of the refrigerant is needed according to the table. Example: If 16kW model is installed at a distance of 25m, (25-10)*50=750g refrigerant should be added; ② Rated capacity is based on standard pipe length and maximum allowable length is base on the product reliability in the operation; ③ Oil trap should be installed every 5-7 meters when the location of outdoor unit is higher than indoor unit. 11 Remote Air Temperature Sensor Front side Back side Remote Air Temperature Sensor NO YES 1.5 Meters NO 21 NO NO Doors User & Installation manual Aerotherm V2 Remote Air Environment Temp sensor CN15 15K CN1 PCB RT9 AP1 2 Electric box Note: ① Distance between the indoor unit and the remote air temperature senor should be less than 15 meter due to length of the connection cable of remote air temperature sensor; ② Height from floor is approximately 1.5 meter; ③ Remote air temperature sensor can not be located where the area may be hidden when door is open; ④ Remote air temperature sensor can not be located where external thermal influence may be applied; ⑤ Remote air temperature sensor should be installed where space heating is mainly applied; ⑥ After the Remote air temperature sensor is installed, should be set the value form “0”to“1” at the function code 1 in the control panel, so as to select remote air temperature to the control point. 12 Thermostat Installation of Thermostat is very similar to that of Remote air temperature sensor. XT3 21 Cool 22 Heat 23 24 N L (230Vac) Thermostat 25 Cool 26 Heat 27 N 28 L (24Vac) Thermostat Fig .1 How to Wire Thermostat (1) Uncover the front cover of the indoor unit and open the control box. (2) Identify the power specifcation of the thermostat, if it is 230Vac, fnd terminal block XT3 as NO.21~24 or NO.23~26; Otherwise, if it is 24Vac, find terminal block XT3 as NO.25~28 or NO.27~30; (3) If it is Heating/Cooling thermostat, please connect wire as Fig 1 ; CAUTION! ① NEVER USE 230Vac and 24Vdc Thermostat at the same time, otherwise, it will cause shortcircuit and power cut-off by circuit breaker; ② Setting temperature by Thermostat(heating or cooling) should be chosen within the setting temperature range of the product ; ③ For other constrains, please refer to previous page where constrains about remote air temperature sensor ④ Do not connect external electric loads, Wire (L) and (N) should be used only for operation Electric type thermostat. 22 User & Installation manual Aerotherm V2 ⑤ Never connect external electric loads such as valves, fan coil units, etc. If connected, PCB of the indoor unit can be seriously damaged. ⑥ Installation of Thermostat is very similar to that of Remote air temperature sensor. 13 2-Ways Valve 2-way valve is required to control water flow while cooling operation. Role of 2-way valve is to cut off water flow into under floor loop in cooling mode when fan coil unit is equipped for cooling operation. General Information Type Power NO 2-wire 230V 50Hz ~AC NC 2-wire 230V 50Hz ~AC Operating Mode Supported Closing water flow Yes Opening water flow Yes Closing water flow Yes Opening water flow Yes (1) Normal Open type. When electric power is NOT supplied, the valve is open. (When electric power is supplied, the valve is closed.) (2) Normal Closed type. When electric power is NOT supplied, the valve is closed. (When electric power is supplied, the valve is open.) How to Wire 2-Way Valve: Follow below procedures Step 1 ~ Step 2. Step 1. Uncover front cover of the indoor unit and open the control box. Step 2. Find terminal block and connect wire as below. 1 2 OFF ON NC NO 3 5 4 N OFF ON 6 N N NC N NO Reserved 2 way value WARING! ① Normal Open type should be connected to wire (NO) and wire (N)for valve closing in cooling mode. ② Normal Closed type should be connected to wire (NC) and wire (N)for valve closing in cooling mode. (NO) : Line signal (for Normal Open type) from PCB to 2-way valve (NC) : Line signal (for Normal Closed type) from PCB to 2-way valve (N) : Neutral signal from PCB to 2-way valve 14 3-Way Valve 3-way valve is required to operate sanitary water tank. Role of 3-way valve is flow switching between under floor heating loop and water tank heating loop. Note: Install the 3-way valve at 1m distance from the exit of the indoor unit. General Information Type Power SPDT 3-wire 230V 50Hz ~AC Operating Mode Supported Selecting “Flow A” between “Flow A” and “Flow B” Yes Selecting “Flow B” between “Flow B” and “Flow A” Yes 23 User & Installation manual Aerotherm V2 (1) SPDT = Single Pole Double Throw. Three wires consist of Live1 (for selecting (for selecting Flow B), and Neutral (for common). (2) Flow A means ‘water flow from the indoor unit to under floor water circuit.’ (3) Flow B means ‘water flow from the indoor unit to sanitary water tank.’ How to Wire 3-Way Valve: Follow below procedures Step 1 ~ Step 2. Step 1. Uncover front cover of the indoor unit and open the control box. Step 2. Find terminal block and connect wire as below. 7 OFF 8 ON 9 N 3 way value 1 WARING! ① 3-way valve should select water tank loop when electric power is supplied to wire (ON) and wire (N). ② 3-way valve should select under floor loop when electric power is supplied to wire (OFF) and wire (N). (ON) : Line signal (Water tank heating) from PCB to 3-way valve (OFF) : Line signal (Under floor heating) from PCB to 3-way valve (N) : Neutral signal from PCB to 3-way valve 15 Other Auxiliary Heat Sources Other auxiliary heat sources are allowed for the equipment and controlled in such a way that the mainboard will output 230V when outdoor temperature is lower than the set point for startup of the auxiliary heat source. OFF ON N 16 Remote ON / OFF (Gate-controller) If there is gate control function, pull out the leading wire 50 on terminal board(XT2) between19 and 20 or between 21 and 22, and then connect the Gate-controller . Installation Guide follow as: XT 20 19 XT 20 19 ON / OFF Mundoclima does not supply this section 24 User & Installation manual Aerotherm V2 17 Filling of Refrigerant (1) Before shipped out from manufacturer, the outdoor unit has been filled with refrigerant. Additional refrigerant may be filled when carrying out site connection of pipelines. (2) Check the liquid valve and the gas valve of the outdoor unit. The valves shall be completely shut off. (3) Connect a vacuum pump to the liquid valve and the gas valve of the outdoor unit to remove air from the inside of the indoor unit and the connecting pipe. Refer to the following figure: Pressure meter “HI”knob “Lo”knob Liquid valve Vacuum pump Connection pipe Gas valve (4) After confirming that there is no leakage from the system, when the compressor is not in operation ,charge additional R410A working fluid with specified amount to the unit through the filling opening of the liquid pipe valve of the outdoor unit. ◆◆ Be sure to charge the specified amount of refrigerant in liquid state to the liquid pipe. Since this refrigerant is a mixed refrigerant, adding it in gas form may cause the refrigerant composition to change, preventing normal operation. ◆◆ Before charging, check whether the refrigerant cylinder is equipped with a siphon tube or not; With siphon tube No siphon tube 18 Installation of Insulated Water Tank 18.1 Installation measure The insulated water tank should be installed and keep levelly within 5m and vertically within 3m from the Indoor unit. It can be installed in the room. Standing water tank must be installed vertically with the bottom on the ground, never suspended. Installation place must be firm enough and the water tank should be fixed on the wall with bolts to avoid vibration, as shown in the following figure. Weight capacity of water tank during installation should also be considered. Water tank Fix with bolts Installed on the ground and never suspended 25 User & Installation manual Aerotherm V2 The minimum clearance from the water tank to combustible surface must be 500mm. There should be water pipe, hot water joint and floor drain near the water tank in favor of water replenishment, hot water supply and drainage of water tank. Connection of inlet/outlet waterway: Connect the safety check valve attached with the unit (→ points at insulated water tank) with the water inlet of water tank with PPR pipe according to the following figure, sealing with unsintered tape. The other end of the safety check valve should connect with tap water joint. Connect the hot water pipe and water outlet of water tank with PPR pipe. Safety check valve Tap water Note: For safe use of water, water outlet/inlet of water tank must connect with a certain length of PPR pipe ,L ≥70×R2(cm, R is inside radius of the pipe). Moreover, heat preservation should be conducted and metal pipe can not be used. For the first use, water tank must be full of water before the power is on. 18.2 Connection of waterway system (1) If connection between water tank and indoor unit should be through the wall, drill a holeφ70 for pass of circulating water pipe. It is unnecessary if the hole is not needed. (2) Preparation of pipelines: Circulating water outlet/inlet pipe must be hot water pipe, PPR pipe with nominal out diameter of dn25 and S2.5 series (wall thickness of 4.2mm) being recommended. Cooling water inlet pipe and hot water outlet pipe of water tank should also be hot water pipe, PPR pipe with nominal out diameter of dn20 and S2.5 series (wall thickness of 3.4mm) being recommended. If other insulated pipes are adopted, refer to the above dimensions for out diameter and wall thickness. (3) Installation of circulating water inlet/outlet pipes: Connect the water inlet of unit with circulating outlet of water tank and water outlet of unit with circulating inlet of water tank. (4) Installation of water inlet/outlet pipes of water tank: Safety check valve (→ on the valve body points at water tank), filter and cut-off valve must be installed for water inlet pipe according to the installation sketch of unit. At least a cut-off valve is needed for the water outlet pipe. (5) Installation of blow-off pipe at the bottom of water tank: Connect a piece of PPR pipe with drainage outlet to floor drain. A cut-off valve must be installed in the middle of the drainage pipe and at the place where it is easy to be operated by the users. (6) After connection of all waterway pipelines, perform leakage test firstly (refer to debugging of the unit). After that, bind up the water pipes, water temp sensor and wires with wrapping tapes attached with the unit. (7) Refer to Installation Sketch of Unit for details. 26 User & Installation manual Aerotherm V2 Indoor Unit Other Thermal sensor (less than 5 meters) Water Tank Hot water output Other Thermal System Temp Sensor 1 Safety check Filter valve temp sensor 2 Cool Water Inlet Tap water Blow-off Outlet Power cord of booster heater Cut-off Valve Note: ① Distance between indoor unit and water tank should not exceed 5m levelly and 3m vertically. If higher, please contact with us. Water tank on lower and main unit on higher side is recommended. ② Prepare the materials according to the above joints dimension. If cut-off valve is installed outside the room, PPR pipe is recommended to avoid freeze damage. ③ Waterway pipelines can’t be installed until water heater unit is fixed. Do not let dust and other sundries enter into pipeline system during installation of connection pipes. ④ After connection of all waterway pipelines, perform leakage test firstly. After that, perform heat preservation of waterway system; meanwhile, pay more attention to valves and pipe joints. Ensure enough thickness of insulated cotton. If necessary, install heating device for pipeline to prevent the pipeline from freezing. ⑤ Hot water supplied from insulated water tank depends on pressure of water tap, so there must be supply of tap water. ⑥ During using, the cut-off valve of cooling water inlet of water tank should be kept normally on. 27 User & Installation manual Aerotherm V2 18.3 Electric wiring work 18.3.1 Wiring principle General principles ◆◆ Wires, equipment and connectors supplied for use on the site must be in compliance with provisions of regulations and engineering requirements. ◆◆ Only electricians holding qualification are allowed to perform wire connection on the site. ◆◆ Before connection work is started, the power supply must be shut off. ◆◆ Installer shall be responsible for any damage due to incorrect connection of the external circuit of the unit. Caution --- MUST use copper wires. Connection of power cable to the electric cabinet of the unit ◆ Power cables should be laid out through cabling trough, conduit tube or cable channel. ◆ Power cables to be connected into the electric cabinet must be protected with rubber or plastic to prevent scratch by edge of metal plate. ◆ Power cables close to the electric cabinet of the unit must be fixed reliably to make the power terminal in the cabinet free from an external force. ◆ Power cable must be grounded reliably. ◆ 18.4.2 Specification of power supply wire and leakage switch Power cable specifications and Leakage switch types in the following list are recommended for selection. Power Supply Leakage Switch Minimum Sectional Area of Earth Wire Minimum Sectional Area of Power Supply Wire V,Ph,Hz (A) (mm2) (mm2) SO30141 (8 kW - IDU) 50 10 3×10 SO30140 (8 kW - ODU) 25 4 3×4 50 10 3×10 32 4 3×4 SO30149 (16 kW - IDU) 50 10 3×10 SO30148 (16 kW - ODU) SO30153 (16 kW - IDU) 380-415V,3N~,50Hz SO30152 (16 kW - ODU) 32 4 3×4 20 2.5 5×2.5 16 1.5 5×1.5 Model SO30145 (12 kW - IDU) SO30144 (12 kW - ODU) 220-240V,~,50Hz Note: ① Leakage Switch is necessary for additional installation. If circuit breakers with leakage protection are in use, action response time must be less than 0.1 second, leakage circuit must be 30mA. ② The above selected power cable diameters are determined based on assumption of distance from the distribution cabinet to the unit less than 75m. If cables are laid out in a distance of 75m to 150m, diameter of power cable must be increased to a further grade. ③ The power supply must be of rated voltage of the unit and special electrical line for airconditioning. ④ All electrical installation shall be carried out by professional technicians in accordance with the local laws and regulations. ⑤ Ensure safe grounding and the grounding wire shall be connected with the special grounding equipment of the building and must be installed by professional technicians. 28 User & Installation manual Aerotherm V2 ⑥ The specifications of the breaker and power cable listed in the table above are determined based on the maximum power (maximum amps) of the unit. ⑦ The specifications of the power cable listed in the table above are applied to the conduitguarded multi-wire copper cable (like, YJV XLPE insulated power cable) used at 40℃ and resistible to 90℃(see IEC 60364-5-52). If the working condition changes, they should be modified according to the related national standard. ⑧ The specifications of the breaker listed in the table above are applied to the breaker with the working temperature at 40℃. If the working condition changes, they should be modified according to the related national standard. 29 User & Installation manual Aerotherm V2 19 Wring Diagram 19.1 PCB outline (1) SO30140 (8 kW - ODU) Silk Screen AC-L Specification Live wire input of power supply, red N Neutral wire input of power supply, white E1 Ground wire, yellow green L2-2 PFC blue inductive wire L1-1 PFC brown inductive wire L2-1 PFC yellow inductive wire L1-2 PFC white inductive wire U U-phase of compressor V V-phase of compressor W W-phase of compressor DC fan 1 pin: strong power supply; 3 pin: fan GND; 4 pin: +15V; 5 pin: control signal; 6 pin:feedback signal; 4-way valve DC_MOTOR1 4V 4V1 HEAT Electric heating tape VA-1 E-heater of chassis HPP High pressure switch LPP Low pressure switch OVC-COMP Overload protection of compressor T-SENSOR2 1, 2 hole: pipe temperature; 3, 4 hole: environment; 5, 6 hole: exhaust T-SENSOR3 1 hole: +3.3V 2 hole: detection ; suction temperature sensor CN66.CN67 Communication cable 2 pin B, 3pinA Communication cable: 1 pin earthed, 2 pin B, 3 pin A, 4 pin+12power supply; It can not be used for communication between outdoor unit and indoor unit; Pipe electric expansion valve,1-4 pin: driving impulse output; 5 pin: +12V; Signal input of pressure sensor 1 pin: GND; 2 pin: signal input; 3 pin: +5V; CN65 FA H-PRESS 30 User & Installation manual Aerotherm V2 (2) SO30144 (12 kW - ODU) SO30148 (16 kW - ODU) Specification Silk screen AC-L N live wire input of power supply, red Neutral line input of power supply(PFC blue inductive wire) blue L1-1 PFC brown inductive wire L2-1 PFC yellow inductive wire L1-2 PFC white inductive wire U U-phase of compressor V W V-phase of compressor W-phase of compressor DC fan 1 pin: strong power supply; 3 pin: fan GND; 4 pin: +15V; 5 pin:control signal; 6 pin: feedback signal; DC fan 1 pin: strong power supply; 3 pin: fan GND; 4 pin: +15V;5 pin: control signal; 6 pin: feedback signal; 4-way valve DC_MOTOR1 DC_MOTOR2 4V1 HEAT electric heating tape VA-1 e-heater of chassis HPP high pressure switch LPP low pressure switch T-SENSOR2 1, 2hole: pipe temperature; 3, 4hole: environment; 5, 6 hole: exhaust; T-SENSOR3 1 hole:+3.3V CN66, CN67 communication cable 2 pin B, 3 pin A communication cable 1 pin earthed, 2 pin B, 3 pin A, 4 pin+12 power supply It can not be used for communication between outdoor unit and indoor unit. pipe electric expansion valve 1-4 pin: driving impulse output; 5 pin: +12V; signal input of pressure sensor 1 pin: GND; 2 pin: signal input; 3 pin: +5V; CN65 FA H-PRESS 2 hole: detection: suction temperature sensor 31 User & Installation manual Aerotherm V2 (3) SO30152 (16 kW 3 Ph - ODU) Silk screen L1 L2 L3 N L U V W DC_MOTOR1 DC_MOTOR2 4V1 HEAT VA-1 HPP LPP T-SENSOR2 T-SENSOR3 CN66,CN67 CN65 FA H-PRESS Specification live wire input of power supply Neutral line input of power supply Reactor red inductive wire U-phase of compressor V-phase of compressor W-phase of compressor DC fan 1 pin:strong power supply;3 pin:fan GND;4 pin:+15V;5 pin:control signal;6 pin:feedback signal; DC fan 1 pin:strong power supply;3 pin:fan GND;4 pin:+15V;5 pin:control signal;6 pin:feedback signal; 4-way valve electric heating tape e-heater of chassis high pressure switch low pressure switch 1, 2hole:pipe temperature;3, 4hole:environment;5, 6hole:exhaust 1 hole:+3.3V 2 hole: detection: suction temperature sensor communication cable 2 pin B,3 pin A communication cable 1 pin earthed,2 pin B,3 pin A,4 pin+12 power supply It can not be used for communication between outdoor unit and indoor unit. pipe electric expansion valve 1-4 pin:driving impulse output;5 pin:+12V; signal input of pressure sensor 1 pin:GND;2 pin:signal input;3 pin:+5V 32 User & Installation manual (4) SO30141 SO30145 SO30149 SO30153 Aerotherm V2 (8 kW - IDU) (12 kW - IDU) (16 kW - IDU) (16 kW 3 Ph - IDU) HEAT2-L RUN AC_L N PUMP1 2V1_OFF HEAT1-L PUMP2 HEAT3-L ERR 2V2_OFF 2V1_ON 3V1_OFF 2V2_ON 3V1_ON Other _OFF Other _ON LED1 LED2 LED3 CN30 T-SENSOR 1 CN31 T-SENSOR 2 T-SENSOR 3 T-SENSOR 4 T-SENSOR 5 T-SENSOR 6 TR-IN TR-OUT1 TR-OUT2 COM-MANUAL OVC-HEAT1 IN-SW COM-OUT OVC-HEAT2 Specification Silk screen Location AC-L - live wire of power supply N - Neutral wire of power supply PUMP1 X13 live wire of indoor water pump PUMP2 X14 live wire of solar water pump RUN X15 running indicator HEAT3-L X16 e-heater of water tank HEAT1-L X17 e-heater of indoor unit 1 HEAT2-L X18 e-heater of indoor unit 2 ERR X19 error indicator 2V1_OFF X5 Electric magnetic 2-way valve1 is normally closed. 2V1_ON X6 Electric magnetic 2-way valve1 is normally open. 2V2_OFF X7 Electric magnetic 2-way valve2 is normally closed. 2V2_ON X8 Electric magnetic 2-way valve2 is normally open. 3V1_OFF X9 Electric magnetic 3-way valve1 is normally closed. 3V1_ON X10 Electric magnetic 3-way valve1 is normally open. Other _OFF X11 Other auxiliary is normally closed. Other _ON X12 Other auxiliary is normally open. 33 OVC-HEAT3 DOOR -C User & Installation manual Aerotherm V2 T-SENSOR1 CN10 terminal of temperature sensor1 T-SENSOR2 CN11 terminal of temperature sensor2 T-SENSOR3 CN12 terminal of temperature sensor3 T-SENSOR4 CN13 terminal of temperature sensor4 T-SENSOR5 CN14 terminal of temperature sensor5 T-SENSOR6 CN15 terminal of temperature sensor6 DOOR-C CN23 Door detection input OVC-HEAT3 CN28 e-heater of water tank adhesion-proof protection detector OVC-HEAT1 CN26 e-heater of indoor unit1 adhesion-proof protection detector OVC-HEAT2 CN27 e-heater of indoor unit2 adhesion-proof protection detector IN-SW CN25 detection input of water flow switch COM-MANUAL CN6 connect the wired controller COM-OUT CN5 connect to outdoor unit TR-OUT1 CN2 transformer output 1 TR-OUT2 CN3 transformer output 2 TR-IN CN1 220V input of transformer CN30 CN30 heavy-current interface of end controller CN31 CN31 heavy-current interface of end controller 34 User & Installation manual Aerotherm V2 19.2 Electric wiring work 19.2.1 Wiring principle (1) General principles ◆◆ Wires, equipment and connectors supplied for use on the site must be in compliance with provisions of regulations and engineering requirements. ◆◆ Only electricians holding qualification are allowed to perform wire connection on the site. ◆◆ Before connection work is started, the power supply must be shut off. ◆◆ Installer shall be responsible for any damage due to incorrect connection of the external circuit of the unit. ◆◆ Caution --- Must use copper wires. (2) Connection of power cable to the electric cabinet of the unit ◆◆ Power cables should be laid out through cabling trough, conduit tube or cable channel. ◆◆ Power cables to be connected into the electric cabinet must be protected with rubber or plastic to prevent scratch by edge of metal plate. ◆◆ Power cables close to the electric cabinet of the unit must be fixed reliably to make the power terminal in the cabinet free from an external force. ◆◆ Power cable must be grounded reliably. 19.2.2 Electric wiring design 19.2.2.1 Wiring diagram: indoor unit SO30141 (8 kW - IDU) SO30145 (12 kW - IDU) SO30149 (16 kW - IDU) 15K RT9 AP2 PE CN12 N EH2 54 HEAT 22 N 23 (230V) L 24 55 COOL 58 HEAT EH1 CN11 X6 X5 47 Thermostat 3.power supply for Thermostat:If it is 230V AC,please connect Terminal block(xt3) 21.22.23.24;If it is 24V AC, please connect Terminal block(xt3) 25.26.27.28. 49 20 XT3 21 48 KM3-4 Thermostat COOL CN10 X8 X7 45 19 50 2.The wires in the imaninal frames are connected by the consumer. 43 46 18 Gate-controller 44 56 25 59 60 KM1 XT2 AP XT3 KM2 XT1 PE PE 3 PE PE 1 KM1 17 1 18 0 KM2 19 CN13 14 OUTDOOR UNIT AP1 HT1 35 CN6 CN2 CN1 TC Display board CN3 62 Water PUMP 15 L KM3 Terminal block RT1 Plate heat exchanger water-out temp sensor RT2 Plate heat exchanger water-in temp sensor RT3 RT4 Liquid line temp sensor Gas line temp sensor Auxiliary electric heater RT5 water-out temp sensor RT6 Water-tank temp sensor2 RT7 Water-tank temp sensor1 Other thermal RT8 Water- out temp sensor 16 21 0 AC contactor Auxiliary electric heater 1,2 51 3 HT1 XT2 Client water pump M SW 25 4 1,2 AC contactor KM3 Water tank Auxiliary electric heater AC contactor XT1,2,3 0 Auxiliary electric heater KM2 RT5 13 CN5 CN66 TC KM3 Thermostat2 (WP95A-R) 20K 11 61 HT2 EH1~2 12 Communication line Thermostat1 (WP65A-R) RT4 57 26 N 27 (24V)L 28 Water flow switch 20K KM1-6 50 42 SW HT1 KM4 KM2-6 HT2 41 RT3 KM3-6 XT2 20 19 KM4 13 14 HL1 Running 15 indicating lamp 16 Error HL2 17 indicating lamp 38 39 20K CN25 Client water pump AC contactor 31 X17 Other thermal X18 BU RT2 CN26 BK Main Board KM1 RT1 20K CN27 RD 8 37 CN28 WH 6 36 30 X16 6 8 N 6 L1(OFF) 7 L2(ON) 8 N 9 L1(OFF) 10 L2(ON) 11 N 12 3-way valve1 35 X13 KM1 9 5 RT6 Water-tank NAME AP 52 20K AP 2 L2(ON) 34 4 X10 X9 4 KM2 2-way valve2 33 2 3 X12 X11 4 2 63 7 RT7 50K 32 1 X14 6 50K 53 8 XT2 X15 XT2 20 19 N L1(OFF) 5 Specification: 1.If there is gate control function, pull out the leading wire 50 on terminal boards between19 and 20 and then connect the Gate-controller . L2(ON) X19 2-way valve1 3 XT1 PE L1(OFF) 65 CN23 4 8 KM3 2 1 1 6 4 N(2) PE CN15 2 64 3 RT8 CN14 (AC-L) 1 CN30 1 N CODE 20K 17 L N 1 CN1 CN31 POWER Indoor Unit 2 4 PE Water tank Auxiliary electric heater ◆◆ 1 N 22 14 26 XT2 RT9 Remote Air temp sensor AP2 Main Board Only For RT9 TC Transformer User & Installation manual ◆◆ SO30153 Aerotherm V2 (16 kW 3 Ph - IDU) 19.2.2.2 Wiring diagram: outdoor unit ◆◆ SO30140 (8 kW - ODU) XT1 L N POWER COMMUNICATION CORD OUTDOOR UNIT W1 SYMBOL W2 W3 W7 INDOOR UNIT E1 N CN66 AC-L PE W9 W10 LP P LPP H-PRESS L1 YE L2 OVC-COMP L2-2 L1-2 θ RT33 50K θ RT 20K T-SENSOR3 θ W17 W15 TERMINAL BOARD MAIN PCB L1/L2 INDUCTANCE COMP COMPRESSOR M EH3 FAN MOTOR BAND HEATER 4-WAY VALVE ELECTRONIC INFLATE VALVE LOW PRESSURE SWITCH Pressure sensor (High side) HS W6 W5 W4 RT31 PIPE TEMP. SENSOR RT32 ENVIRONMENT TEMP. SENSOR DISCHARGE GAS TEMP. SENSOR SUCTON TEMP SENSOR RT33 RT RD BK BU P HP W19 VA-1 FA W14 EH1 AP1 EKV WH W18 HPP W16 XT1 LP W V U 20K θ RT32 15K ELECTRIC HEATER YV L BU EKV W13 EH3 BN AP1 HS RT31 L1-1 L2-1 DC_MOTOR1 AP PE T-SENSOR2 CN5 PE PE HEAT YEGN PE EH2 36 HIGH PRESSURE SWITCH HP Electric component position map U V W RD BKWH YEBU (S)(C)(R) COMP M 3 YV 4V NAME EH1 EH2 W8 YEGN PE L AP1 XT1 User & Installation manual ◆◆ Aerotherm V2 SO30144 (12 kW - ODU) SO30148 (16 kW - ODU) ◆◆ SO30152 (16 kW 3 Ph - ODU) 3 37 User & Installation manual Aerotherm V2 19.2.2.3 Wiring diagram: indoor and outdoor unit(including feld wiring) ◆◆ 8, 12, 16 kW (1-Ph) AC reserved ON / OFF Mundoclima does not supply this section Note: 1. Running indicating lamp (HL1) and Error indicating lamp (HL2) are connected or not on the basis of the clients demand. 2. Client water pump AC contactor (KM3) is back-up Pump for the future, so it is not be connect. el contactor de la bomba auxiliar y nunca para alimentar la bomba de agua de forma directa. 3. Leakage switch (LK) is necessary dor additional installation, please reference to 17.4.2 Specification of Power Supply Wire and Leakage Switch. 38 User & Installation manual ◆◆ Aerotherm V2 16 kW (3-Ph) AC reserved ON / OFF Mundoclima does not supply this section Note: 1. Running indicating lamp (HL1) and Error indicating lamp (HL2) are connected or not on the basis of the clients demand. 2. Client water pump AC contactor (KM3) is back-up Pump for the future, so it is not be connect. el contactor de la bomba auxiliar y nunca para alimentar la bomba de agua de forma directa. 3. Leakage switch (LK) is necessary dor additional installation, please reference to 17.4.2 Specification of Power Supply Wire and Leakage Switch. 39 User & Installation manual Aerotherm V2 19.2.2.4 Terminal board information ◆ 8, 12, 16 kW (1-Ph) ƹ Terminal 21 board X T3: 22 24 23 25 Thermostat 230Vac ƹ Terminal 26 27 28 Thermostat 24Vac board X T1: power supply for Water tank electric heater 12 L N 1 345678 91 01 11 21 31 41 51 61 71 81 92 0 N(2) Connecting external electric power supply for Indoor Unit ƹ Terminal Connection for Indicating lihgt board X T2: 1 2 way value 4 5 reserved 6 7 8 9 10 11 12 13 14 15 16 Connection for Client water's AC contactor 3 way value 40 Remote O N / O FF 17 18 19 20 Connection for Accident lihgt User & Installation manual ◆ Aerotherm V2 16 kW (3-Ph) ƹ Terminal board X T2: 1 4 2 way value ƹ Terminal L1 Connection for Indicating lihgt 5 6 reserved 7 8 9 10 11 12 13 14 17 18 19 15 16 Connection for Client water's AC contactor 3 way value Remote O N / O FF Connection for Accident lihgt board X T1: L2 L3 N Connecting external electric power supply for Indoor unit ƹ Terminal 21 board X T3: 22 23 24 Thermostat 230Vac 25 26 27 28 Thermostat 24Vac 41 29 30 31 power supply for water tank eletric heater 20 User & Installation manual 19.2.2.5 Control wiring design Aerotherm V2 Diplay board CN4 CN5 4 CN6 Indoor Unit Eletric box AP 3 CN66 AP1 Outdoor Unit Main board Eletric box CN5 Main board Installation Instruction : (1) Wired controller connects to terminal CN6 on mainboard of indoor unit by 4-core communication line. (2) The indoor unit connects to outdoor unit by 3-core communication line. Wiring terminal of indoor unit is CN5 and that of the outdoor unit is CN66. 42 User & Installation manual Aerotherm V2 20 Debugging Operation of Unit 20.1 Check before startup For safety of users and unit, the unit must be started up for check before debugging. The procedures are as below: The following items shall be performed by qualified repair persons. Confirm together with the sales engineer, dealer, installing contractor and customers forthe following items having been finished or to be finished. No. 1 2 3 No. 1 2 Confirmation of Installation If the contents of Application for Installation of this Unit by Installer are real. If not, debugging will be refused. If there is written notice in which amend project is shown to the installer in respect of unqualified installation. If Application for Installation of unit by Installer and Debugging list are filed together. Pre-check If appearance of the unit and internal pipeline system is ok during conveying, carrying or installation. Check the accessories attached with the unit for quantity, package and so on. √ □ □ □ √ □ □ Make sure there is drawings in terms of electricity, control, design of pipeline and so on. Check if installation of the unit is stale enough and there is enough space for operation and repair. Completely test refrigerant pressure of each unit and perform leakage detection of the unit. □ Check if water tank is installed stably and its bearing is safe upon it is full. Check if heat insulating measures for the water tank, outlet/inlet pipes and water replenishing pipe are proper. Check if nilometer of water tank, water temperature indicator, controller, manometer, pressure relief valve and automatic discharge valve etc. are installed and operate properly. Check if power supply accords with the nameplate and model of power cord conform to applicable requirements. □ 10 Check if power supply and control wiring is connect properly according to wiring diagram, earthing is safe and each terminal is stable. □ 11 Check if connection pipe, water pump, manometer, thermometer, valve etc. are installed properly. □ 12 Check if each valve in the system is open or closed according to requirements. □ 13 Confirm that the customers and inspection personnel of Part A are at site. □ 14 Installation Check-up Table is completed and ask installing contractor’s signature for consent. □ 3 4 5 6 7 8 9 □ □ □ □ □ Attention: If the items with ×, please notify the contractor .The above items are recommended. Confirmed Items after pre-checking General Evaluation: Debugging □ Amendment □ Judge the following items (if there is not any filling, qualification will be regarded.) a: Power supply and electric control system b: Loading calculation c: Heating problems of Unit d: Noise problem e: Pipeline problem f: Others Normal debugging work can’t be performed unless all installation items are qualified. If problem, it must be solved firstly. All costs will be installer’s responsibility for delay of debugging and redebugging incurred by any problem which is not solved immediately. Submit schedule of amending reports to installer. If provide written amending report to installer which should be signed after communication. Yes ( ) No ( ) 43 User & Installation manual Aerotherm V2 20.2 Test run Test run is testing whether the unit can run normally via preoperation. If the unit can not run normally, find and solve the engineering or unit problem until the test run is satisfactory. All inspection must meet the requirements before performing the test run. Test run should follow the content and steps of the table below: The following procedure should be executed by experience and qualified maintenance man. No. Start up the pretest procedure Notice: before test, ensure that all power must be cut off including far- end power switch. Otherwise, it may cause casualty. 1 Ensure that the compressor of the unit is preheated for 8h. Caution: heat the lubricating oil at least 8h in advance, to prevent the refrigerant from mixing with the lubricating oil, which may cause damage to the compressor when starting up the unit. Check whether the oil temperature of the compressor is obviously higher than the outdoor ambient temperature. Caution: if the oil temperature of the compressor is obviously higher than the outdoor ambient temperature, it means that the heating tape of compressor is damaged.In that case, the compressor will be damaged easily. Therefore, repair the heating tape Before using the unit. Check whether the phase sequence of main power supply is correct. If not, correct the phase 3 sequence according to specification. Recheck the phase sequence before start-up to avoid inversion of the compressor which may damage the unit. Apply universal electric meter to measure the insulation resistance between each 4 outdoor phase and earth as well as between phases. Caution: defective earthing may cause electric shock. 2 No. 1 Ready to start Cut off all of temporary power supply, resume all the insurance and check the electricity for the last time. Check the power supply and voltage of the control circuit; _____V must be ±10% within the range of rated operating power. No. 1 Start up the unit Check all the conditions needed to start up the unit: oil temperature, mode, required load ect. Start up the unit, and observe the operation of compressor, electric expanding valve, fan motor and water pump ect. 2 Note: the unit will be damaged under abnormal running state. Do not operate the unit in states of high pressure and high current. affixed information: Items for acceptance after debugging Estimation or suggestion on the general running situation: good, modify Identify the potential problem( no writing means the installation and debugging are in accordance with the requirements.) a. problem of power supply and electric control system: b. problem of load calculation: c. outdoor refrigerant system: d. noise problem: e. problem of indoor and piping system: h. other problems: During operation, it is needed to charge for the maintenance due to non-quality problems such as incorrect installation and maintenance. Acceptance situation: Is the user trained according to the specification? Please sign. Yes( ) No( ) 44 User & Installation manual Aerotherm V2 21 Daily Operation and Maintenance In order to avoid damage of unit, all protecting devices in the unit had been set before outgoing, so the user can never adjust or remove them. For the first startup of the unit or next startup of unit after long-period stop (above 1 day)by cutting off the power, please electrify the unit in advance to preheat the unit for more than 8hr Never put sundries on the unit and accessories. Keep dry, clean and ventilated around the unit. Remove the dust accumulated on the condenser fin timely to ensure performance of unit and to avoid stop of unit for protection. In order to avoid protection or damage of unit caused by blockage of water system, clean the filter in water system periodically and frequently check water replenishing device. In order to ensure anti-freezing protection, never cut off the power if ambient temp. is below zero in winter. In order to avoid frost crack of the unit, water in the unit and pipeline system not used for a long period should be drained. In addition, open the end cap of water tank for drainage. Never frequently make the unit on/off and close manual valve of water system during operation of unit by users. Ensure frequently check the working condition of each part to see if there is oil stain at pipeline joint and charge valve to avoid leakage of refrigerant. If malfunction of the unit is out of control of users, please timely contact with authorized service center of company. Note: The water pressure gage is installed in returning water line in the indoor unit, Please adjust the hydraulics system pressure according to next item: ① If the pressure is less than 0.5 bar, please recharge the water immediately; ② When recharging, the hydraulics system pressure should be not more than 2.5Bar. Troubleshooting Malfunctions Reasons Compressor does not start up ① ② ③ ④ High noise of fan ① ② ③ Troubleshooting ① ② ③ ④ ② Power supply has problem. Connection wire is loose. Malfunction of mainboard. Malfunction of compressor. Fixing bolt of fan is loose. Fan blade touches shell or grill. Operation of fan is unreliable. Liquid slugging happens when liquid refrigerant enters into compressor. Internal parts in compressor are broken. Water pump does not run or runs abnormally ① ② ③ Malfunction of power supply or terminal. Malfunction of relay. There is air in water pipe. ① ② ③ Compressor starts or stops frequently ① ② ③ Poor or excess refrigerant. Poor circulation of water system. Low load. The unit does not heat although compressor is running ① ② Leakage of refrigerant. Malfunction of compressor. Poor efficiency of hot water heating ① ② ③ ④ Poor heat insulation of water system. Poor heat exchange of evaporator. Poor refrigerant of unit. Blockage of heat exchanger at water side. High noise of compressor ① ① ② ③ ① ② Phase sequence is reverse. Check out and re-fix. Find out the reasons and repair. Replace compressor. Re-fix fixing bolt of fan. Find out the reasons and adjust. Replace fan. Check if expansion valve is failure and temp. sensor is loose .If that, repair it. Replace compressor. Find out the reasons and repair. Replace relay. Evacuate. ① Discharge or add part of refrigerant. ② Water system is blocked or there is air in it.Check water pump, valve and pipeline. Clean water filter or evacuate. ③ Adjust the load or add accumulating devices. ① Repair by leakage detection and add refrigerant. ② Replace compressor. ① 45 Enhance heat insulation efficiency of the system. ② Check if air in or out of unit is normal and clean evaporator of the unit. ③ Check if refrigerant of unit leaks. ④ Clean or replace heat exchanger. User & Installation manual Aerotherm V2 The table of error code Full Name Ambient temperature sensor error Condenser temperature sensor error Discharge temperature sensor error Suction temperature sensor error Outdoor fan error Compressor internal overload protection High pressure protection Low pressure protection High discharge protection Incorrect capacity DIP switch setting Communication error between indoor and outdoor unit High pressure sensor error Heat exchanger-leaving water temperature sensor error Auxiliary heater-leaving water temperature sensor error Refrigerant liquid line temperature sensor error Heat exchanger-entering water temperature sensor error Water tank water temperature sensor 1 error Water tank water temperature sensor 2 error Refrigerant gas line temperature sensor error Solar heater-leaving water temperature sensor error Room temperature sensor error Water flow swich protection Welding protection of the auxiliary heater 1 Welding protection of the auxiliary heater 2 Welding protection of the water tank heater Under-voltage DC bus or voltage drop error Over-voltage DC bus AC current protection (input side) IPM defective PFC defective Start failure Phase loss Drive module resetting Compressor over-current Overspeed Sensing circuit error or current sensor error desynchronizing Compressor stalling Communication error Radiator or IPM or PFC module overtemperature Radiator or IPM or PFC module temperature sensor error Charging circuit error Incorrect AC voltage input Drive board temperature sensor error AC contactor protection or input zero crossing error Temperature drift protection Current sensor connection protection (current sensor not connected to phase U/V) Communication error to the outdoor unit Communication error to the indoor unit Communication error to the drive Overload protection of compresor or driver error Indoor anti-frozen protection Pull-out of the remote ON/OFF (gate controller) 46 Displayed Name Ambient sensor Cond. sensor Disch. sensor Suction sensor Outdoor fan Comp. overload High pressure Low pressure Hi-discharge Capacity DIP ODU-IDU Com. Pressure sens. Temp-HELW Temp-AHLW Temp-RLL Temp-HEEW Tank sens. 1 Tank sens. 2 Temp-RGL Temp-SHLW Sensor-RT WS-protection Auxi. heater 1 Auxi. heater 2 Auxi. -WTH DC under-vol. DC over-vol. AC curr. pro. IPM defective FPC defective Start failure Phase loss Driver reset Com. over-curr. Overspeed Current sen. Desynchronize Comp. stalling drive-main com. Overtemp.-mod. T-mod. sensor Charge circuit AC voltage Temp-driver AC contactor Temp. drift Error Code F4 F6 F7 F5 EF H3 E1 E3 E4 c5 E6 FC F9 dH F1 F8 FE FL F3 dF F0 EC EH EH EH PL PH PA H5 HC LC LD P0 P5 LF PC H7 LE P6 P8 P7 PU PP PF P9 PE Sensor con. PD ODU Com. IDU Com. Driver Com. E6 E6 E6 E5 E2 dU User & Installation manual Aerotherm V2 22 Operation Range Mode Range of Outdoor Temperature( C) Heating -20~35 Cooling 10~48 Water heating -20~45 47 ASK FOR MORE INFORMATION Phone: (+34) 93 446 27 80 eMail: [email protected] TECHNICAL ASSISTANCE Phone: (+34) 93 652 53 57 www.mundoclima.com
advertisement