NHT 25, NJT 30, NJT 40, NJT 50 air conditioner, MACZ 50A evaporator coil Installation manual
The NHT25, NJT30, NJT40, and NJT50 air conditioners are designed for indoor use only. They are part of a split-system air conditioning system that requires specific application considerations with regard to the air handling system, duct design, condensing unit, refrigerant piping, and control scheme. The NHT25, NJT30, and NJT40 units consist of an evaporator coil section and a blower section that are factory assembled and shipped as shown in Figures 20 thru 25. These sections may be rearranged in the field for other air discharge patterns as shown in Figures 1 and 2. NJT50 units consist of a blower section only and must be matched with an MACZ-50 evaporator coil as shown in Figures 27 thru 28. These units are shipped separately and must be field assembled as shown in Figure 28. These sections may be rearranged for other air discharge patterns as shown in Figure 3. It's important to ensure TXV bulbs are not crossed between systems, as undesirable performance and possible compressor damage may occur.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
R-410A MODELS: NHT25, 2-Pipe NJT30 Thru T50, 4-Pipe 25 - 50 Ton, 60 Hertz TABLE OF CONTENTS General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Agency Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Unit Application Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Physical Data Indoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . Unit Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Air Discharge Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . Unit Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2 2 2 2 3 3 4 5 5 5 5 5 8 Refrigerant Mains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Expansion Valve Bulb Installation . . . . . . . . . . . . . . . . . . . Duct Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Connections Air Handlers with Contactor . . . . . NJT50 Bearing Alignment: . . . . . . . . . . . . . . . . . . . . . . . . ............................................. Air System Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . Twin Belt Drive Adjustment . . . . . . . . . . . . . . . . . . . . . . . . Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . Start-Up Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 14 14 16 17 19 21 21 21 22 35 36 41 LIST OF TABLES 1 2 3 4 5 6 7 8 Unit Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Physical Data Indoor Unit . . . . . . . . . . . . . . . . . . . . . . . . 4 Unit Mounting Dimensions . . . . . . . . . . . . . . . . . . . . . . . 11 Corner Weights & Center of Gravity NH/NJ Units . . . . . 11 Accessory Operating Weight Distribution (Lbs) . . . . . . . 12 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Overload Relay Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Overload Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 1 2 3 4 NHT25 and NJT30/T40 Vertical Airflow Arrangements . . 6 NHT25 and NJT30/T40 Horizontal Airflow Arrangements 6 NJT50 & MACZ-50 Airflow Arrangements . . . . . . . . . . . . 7 NHT25/NJT30/NJT40 Weight Distribution With Suspension Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 NHT25/NJT30/NJT40 Details For Securing Suspension Channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 NJT50 & MACZ-50 Weight Distribution With Suspension Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Figure 7: NJT50 & MACZ-50 Details For Securing Suspension Channels . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Figure 8: Recommended Drain Piping . . . . . . . . . . . . . . 12 Figure 9: Suggested Method For Connecting Ductwork 15 Figure 10: NHT25/NJT30/NJT40 Motor Arrangements As Seen In Figures 1 and 2 . . . . . . . . . . . . . . . . . . . . . . . . . 19 NJT50 Factory Motor Mounting Position . . . . . . . . . . . . 20 Figure 11: NJT50 Center Bearing . . . . . . . . . . . . . . . . . 20 Figure 13: NJT50 Motor Mount Plate . . . . . . . . . . . . . . 20 Figure 14: Double Groove Pulley . . . . . . . . . . . . . . . . . 21 Figure 15: Hole Locations For Reading Coil Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Figure 16: NHT25 - Pressure Drop Vs. Cfm Across Dry Indoor Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Figure 17: NJT30 - Pressure Drop Vs. Cfm Across Dry Indoor Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Figure 19: NJT50 & MACZ-50 - Pressure Drop Vs. Cfm Across Dry Indoor Coil . . . . . . . . . . . . . . . . . . . . . . . . . . 25 9 10 11 12 13 14 15 Unit Blower Motor Data . . . . . . . . . . . . . . . . . . . . . . . . . Unit Drive Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fan Performance Data - 25 Ton . . . . . . . . . . . . . . . . . . Fan Performance Data - 30 Ton . . . . . . . . . . . . . . . . . . Fan Performance Data - 40 Ton . . . . . . . . . . . . . . . . . . Fan Performance Data - 50 Ton . . . . . . . . . . . . . . . . . . Unit Connection Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . 18 21 22 22 22 23 35 LIST OF FIGURES 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Figure 18: NJT40 - Pressure Drop Vs. Cfm Across Dry Indoor Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 20 Figure 20: NHT25 Unit Dimensions . . . . . . . . . . . . . . . 26 21 Figure 21: NHT25 Unit Dimensions (Continued) . . . . . . 27 22 Figure 22: NJT30 Unit Dimensions . . . . . . . . . . . . . . . . 28 23 Figure 23: NJT30 Unit Dimensions (Continued) . . . . . . 29 24 Figure 24: NJT40 Unit Dimensions . . . . . . . . . . . . . . . . 30 25 Figure 25: NJT40 Unit Dimensions (Continued) . . . . . . 31 26 Figure 26: NJT50 Unit Dimensions . . . . . . . . . . . . . . . . 32 27 Figure 27: MACZ-50 Evaporator Section Dimensions . . 33 28 Figure 28: NJT50 Air handler & MACZ-50 Evaporator Coil Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 29 Figure 29: Typical NC300 Indoor Unit Wiring Diagram (Contactor) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 30 Figure 30: Typical ND360, 480 & 600 Indoor Unit Wiring Diagram (Contactor) . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 31 Figure 31: Typical Field Wiring Diagram - NHT25 Evaporator Unit with YHT25 Condenser Unit . . . . . . . . 38 32 Figure 32: Typical NHT25 Liquid Line Solenoid Wiring . 38 33 Figure 33: Typical Field Wiring Diagram NJT30/T40 Evaporator Units, NJT50 Air Handler and MACZ-50A Evaporator Coil when Matched with YJ-30/T40/T50 Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 34 Figure 34: Typical NJT30/T40 & MACZ-50A Liquid Line Solenoid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 35 Figure 35: Typical Liquid Line Solenoid Wiring . . . . . . . 40 5121846-TIM-A-0515 5121846-TIM-A-0515 General Reference The NH/NJ Series evaporator units are designed to match with YH/YJ Series condensing units. When matched, these units meet ASHRE 90.1 standards. This instruction covers the installation and operation of evaporator blower units. For information on the operation of matching condensing units, refer to Installation Manual for cooling units. NHT25, NJT30 and NJT40 units consist of an evaporator coil section and a blower section that are factory assembled and shipped as shown in Figures 20 thru 25. These sections may be rearranged in the field for other air discharge patterns as shown in Figures 1 and 2. Additional information on the design, installation, operation and service of this equipment is available in the following Technical Guides Model No. YHT25/NHT25 Technical Guide-5123379, Model No.YJ-30 thru T50 Technical Guide-5123384 and Model No. NJT30 thru T50 Technical Guide-5123383. NJT50 units consist of a blower section only and must be matched with an MACZ-50 evaporator coil as shown in Figures 27 thru 28. These units are shipped separately and must be field assembled as shown in Figure 28. These sections may be rearranged for other air discharge patterns as shown in Figure 3. Renewal Parts The NH/NJ evaporator coils have 24 volt normally closed solenoid valves, that when matched with the YH/YJ condensing units Simplicity® controls provide capacity staging and pump out for higher efficiencies and product reliability. Design certified by CSA as follows: Safety Considerations Inspection Installer should pay particular attention to the words: NOTE, CAUTION, and WARNING. Notes are intended to clarify or make the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury and/or equipment damage may result if installation procedure is not handled properly. As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier’s freight bill. A separate request for inspection by the carrier’s agent should be made in writing. Improper installation may create a condition where the operation of the product could cause personal injury or property damage. Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for assistance or for additional information, consult a qualified contractor, installer or service agency. Contact your local Source 1 parts distribution center for authorized replacement parts. Agency Approvals 1. For use as a cooling coil. 2. For indoor installation only. This product must be installed in strict compliance with the enclosed installation instructions and any applicable local, state and national codes including, but not limited to, building, electrical, and mechanical codes. Wear safety glasses and gloves when handling refrigerants. Failure to follow this warning can cause serious personal injury. This system uses R-410A Refrigerant which operates at higher pressures than R-22. No other refrigerant may be used in this system. Gage sets, hoses, refrigerant containers and recovery systems must be designed to handle R-410A. If you are unsure, consult the equipment manufacturer. Failure to use R-410A compatible servicing equipment may result in property damage or injury. 2 Johnson Controls Unitary Products 5121846-TIM-A-0515 Nomenclature Configured Split Air Handler Model Number Nomenclature N J T30 C00 N 6 A AA 1 Product Category N = Split System, Air Handler, AC, R-410A Product Generation 1 = First Generation Product Identifier J = Standard Efficiency, 4-Pipe, R-410A (30-50T) Product Options1 AA = No Options Installed EJ = E-Coat Evap Coil (See Note 1.) Nominal Cooling Capacity - MBH 1. NJT50C00N*AAA1 airhandler does not include evaporator coil. Customer must order MACZ-50A Standard Coil. T30 = 30 Ton T40 = 40 Ton T50 = 50 Ton Installation Options Heat Type & Nominal Heat Capacity A = None C00 = Cooling Only Voltage 6 = 208/230/460-3-60 5 = 575-3-60 Airflow2 N = None (Motor Drive Kit Req)* 2. Motors, drives and overloads are not shipped with 30 - 50 ton Air Handler Units. Unit Application Data Table 1: Model NHT25 NJT30 NJT40 NJT50 Unit Application Data Power Supply Voltage 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 Voltage Variation Min. 187 414 540 187 414 540 187 414 540 187 414 540 Max. 253 506 630 253 506 630 253 506 630 253 506 630 Supply Air Range CFM Min. 8,000 8,000 8,000 10,000 10,000 10,000 12,800 12,800 12,800 16,000 16,000 16,000 Max. 12,000 12,000 12,000 14,000 14,000 14,000 19,200 19,200 19,200 24,000 24,000 24,000 Entering Air Temperature Degrees °F Cooling Heating DB1 DB/WB Min. Max. Min. Max. 65/57 95/72 40 77 65/57 95/72 40 77 65/57 95/72 40 77 65/57 95/72 40 77 65/57 95/72 40 77 65/57 95/72 40 77 65/57 95/72 40 77 65/57 95/72 40 77 65/57 95/72 40 77 65/57 95/72 40 77 65/57 95/72 40 77 65/57 95/72 40 77 1. Heating Min/Max temperatures apply to steam and hot water coils. NOTE: Do not apply steam to hot water coils. Johnson Controls Unitary Products 3 5121846-TIM-A-0515 Physical Data Indoor Unit Table 2: Physical Data Indoor Unit Component NHT25 25 Nominal Tonnage DIMENSIONS (inches) Length Width Height Models NJT30 NJT40 30 40 NJT501 50 100.1 38.1 74.6 100.1 38.1 74.6 103.1 45.4 89.4 105.1 53.7 99.0 1067 1122 1246 1684 1130 1157 ----- 1184 1208 1224 --- --1348 1364 --- ----1742 1859 18 X 18 2 18 X 18 2 18 X 18 2 20 x 18 2 WEIGHTS2 (lb) Unit Shipping Unit Operating With 5 hp Motor and Drive 7.5 hp Motor and Drive 10 hp Motor and Drive 15 hp Motor and Drive INDOOR BLOWER Diameter x Width Qty. INDOOR COIL Face area (Sq. Ft.) Rows Fins per inch Tube diameter Circuitry Type Refrigerant Control 25.8 25.8 33.3 41.3 4 4 4 4 16 16 16 16 3/8 3/8 3/8 3/8 Interlaced Interlaced Interlaced Interlaced TEV TEV TEV TEV SYSTEM DATA No. Refrigeration Circuits Suction Line OD (in.) Liquid Line OD (in.) 1 2 1/8 7/8 2 1 1/8 7/8 2 1 3/8 7/8 2 2 1/8 7/8 --------10 --34.7 --------10 --34.7 6 3 ----6 --42.6 ------6 3 6 53.1 21.2 2 12 1/2 1 3/8 150 21.2 2 12 1/2 1 3/8 150 27.2 2 12 1/2 1 5/8 190 27.2 2 8 1/2 1 5/8 190 18.2 1 8 1 18.2 1 8 1 --------- --------- 2 1-1/2 160 2 1-1/2 160 ------- ------- FILTERS Size and Quantity Per Model (In.) Face area (Sq. Ft.) 16 x 20 x 2 20 x 20 x 2 20 x 22 x 2 16 x 25 x 2 20 x 25 x 2 25 x 25 x 2 ACCESSORY HOT WATER COIL DATA Face area (Sq. Ft.) Rows Fins per inch Tube diameter (Copper) OD (In.) Connections (Supply and Return) OD (In.) Weight (lb) STEAM COIL DATA Face area (Sq. Ft.) Rows Fins per inch Tube diameter (Copper) (In.) Connection, (NPTE) (In.) Inlet Outlet Weight (lb) 1. NJT50 and MACZ-50A Combined 2. Motor, Motor Drive and Motor Overload Kits must be ordered separately, The Motor, Motor Drive and Overload Kits are to be field installed. 4 Johnson Controls Unitary Products 5121846-TIM-A-0515 Unit Installation on one end of the unit if the blower shaft or evaporator coil is to be replaced without moving the unit. Location Air Discharge Conversion The evaporator blowers are not designed for outdoor installation. They must be located inside the building structure, either inside or outside the conditioned space where they are protected from rain and other such moisture. The unit should be located as close to the condensing unit as practical and positioned to minimize bends in the refrigerant piping. Units being installed vertically or horizontally can be set directly on a floor or platform, or supported by metal or wooden beams. NHT25/NJT30/NJT40 Air Discharge These units are shipped for upflow operation, but may be converted for any of the illustrated air discharge patterns shown in Figures 1 and 2. Convert as follows: 1. Remove the (blower section) panels. 2. Remove the Phillips machine screws located inside casing corner angles that hold the evaporator and blower sections together. 3. Rotate the blower section for the desired air discharge orientation. Units being installed horizontally can be suspended from above as shown in Figures 4 and 6. Rigging Care must be taken when moving the unit. Do not remove any packaging until the unit is near the place of installation. SPREADER BARS SHOULD BE USED BETWEEN THE SLINGS TO PREVENT CRUSHING THE UNIT FRAME OR PANELS. When preparing to move the unit, always determine the center of gravity of the unit in order to equally distribute the weight. Rig the unit by attaching chain or cable slings around the bottom skid. A lift truck may be used to raise a unit to a suspended location. Refer to Table 2 for the total unit operating weight. NOTE: Before proceeding to step 4, see the section on the blower motor mounting locations and mount the blower motor in the desired position. 4. If accessory heating coils are used, mount heating coil between evaporator and blower sections. Screw fastening locations are the same for all sections and heating accessories. If heating coils are not used, fasten evaporator section to blower section with machine screws removed in step 2. Clearances 5. See duct and drain connections. 6. Replace panels. A 25-inch clearance is required on the end with the piping connections and the supply air blower motor to properly service and maintain the unit and to replace the filters. Some clearance will also be required for the duct and power wire connections. A clearance equal to the unit width is required Johnson Controls Unitary Products 5 5121846-TIM-A-0515 1 AIR BLOWER 3 2 AIR AIR AIR EVAPORATOR COIL AIR AIR 4 5 6 AIR AIR AIR AIR AIR Figure 1: NHT25 and NJT30/T40 Vertical Airflow Arrangements 7 AIR NOTE: *If required, some air can be returned through the bottom of the evaporator section 8 9 AIR AIR AIR AIR 11 AIR AIR AIR AIR 10 12 AIR AIR AIR Figure 2: NHT25 and NJT30/T40 Horizontal Airflow Arrangements 6 Johnson Controls Unitary Products 5121846-TIM-A-0515 NJT50 Air Discharge When arranged horizontally, the evaporator section can be set directly on the floor, but a 9" support is required under the blower section for stability. The support should extend the full width of the blower section and be located under the edge away from the evaporator section. The NJT50 blower and MACZ-50 evaporator sections are shipped separately and must be joined together in the field. The blower section can be mounted either above the evaporator for a vertical positioning or beside the coil for horizontal positioning. Both vertical and horizontal positions can be arranged for upward, downward, or horizontal air discharge. The evaporator and blower sections may be assembled together as shown in Figure 3. All arrangements are possible by rearranging the panels as shown. NOTE: Ductwork should never be used to support the blower section. Refer to duct connection for more information. When arranged vertically, the NJT50 can set directly on any floor or platform that is capable of supporting its weight. . 1 2 3 VERTICAL AIRFLOW ARRANGEMENTS 4 5 6 7 HORIZONTAL AIRFLOW ARRANGEMENTS Figure 3: NJT50 & MACZ-50 Airflow Arrangements Johnson Controls Unitary Products 7 5121846-TIM-A-0515 Unit Mounting accessories include three suspension channels and hardware. The channels extend across the evaporator section, the heating section (if included) and the blower section. Each channel is to be bolted to both sections as shown in Figures 4 thru 6. Refer to Table 3 for mounting details and Tables 4 and 5 for unit weight distribution. The NH/NJ Series evaporator units may be suspended from joists with isolation type hangers or hooks. Suspension accessories 1HH0403 (NHT25 and NJT30), 1HH0404 (NJT40) and 1HH0405 (NJT50 Air Handler with MACZ-50 Evaporator Section) may be ordered separately. All Suspension HORIZONTAL UNIT SUSPENDED FROM ABOVE 3 AX D BX C E BX VERTICAL UNIT SUPPORTED FROM BELOW 3 BLOWER SECTION F 1-1/2 EVAP . COIL SECTION U3 O U B BLOWER SECTION A EVAP. COIL SECTION A HEATING COIL 2 F SUSPENSION ANGLES 1 E C D CX 4 B BX BX 1 The same channels can be used in either position. When used to support a vertical unit, these channels should be cut to match the bottom dimension of the evaporator section. 2 The suspension channels have two sets of mounting holes to accommodate horizontal units with or without a heating coil. On a horizontal unit without a heating coil, the suspension channels will extend 3” beyond both ends of the unit. 3 The same channels can be used to support a horizontal, floor- mounted unit from below. 4 After these bottom channels are cut per Note 1, a new hole will have to be drilled at the cut end if the unit is to be mounted on isolators. Figure 4: NHT25/NJT30/NJT40 Weight Distribution With Suspension Application 8 Johnson Controls Unitary Products 5121846-TIM-A-0515 NOTE: The following illustration shows how the channels should be secured to the unit using the hardware provided with the suspension accessory. (2) 9/16 HOLES FOR 1/2 HANGER RODS SUSPENSION CHANNEL 5/16 NUT, FLATWASHER 5/16 NUT, LOCKWASHER, FLATWASHER 3 3/8 NUT (USED AS SPACER) UNIT PANEL 5/16 BOLT, FLAT-WASHER SIDE PANEL UNIT ANGLE Figure 5: NHT25/NJT30/NJT40 Details For Securing Suspension Channels BX BX AX D C E B F A Figure 6: NJT50 & MACZ-50 Weight Distribution With Suspension Application Johnson Controls Unitary Products 9 5121846-TIM-A-0515 NJT50 Mounting When arranged horizontally (Figure 6), the NJT50 air handler and MACZ-50 evaporator coil can be suspended from joists with hanger rods using a suspension accessory. The suspension channels require no drilling or cutting. Each channel has enough holes in its bottom flange for: 1. Four bolted connections to the evaporator coil section. (Only two are used on the outside supports) 2. One bolted connection to the heating coil section. 3. Four bolted connections to the blower section. (Only two are used on the outside supports) See Figure 7 details for securing suspension channels. When the heating section is not included, each channel will extend 3" beyond the front and the rear of the unit. Bolt holes in the bottom flange of each channel will still align with the holes provided in the top framework of the evaporator section and the blower section. For both outside channels and for the Point 1 locations on the center channel, the bolted connections are to be made where the top sheet metal panels are attached to the unit framework. The ¼” screws and cage nuts must be removed and may be discarded. For the Point 2 locations on the center channel, the bolted connections are to be made through the knockouts in the top sheet metal panels. 5/16” cage nuts are provided in the unit framework under these knockout locations. Note that these cage nuts are part of the basic unit. They are not supplied with the suspension accessory. . CENTER CHANNEL (Location “1” Figure 13) CENTER CHANNEL (Location “2” Figure 13) Figure 7: NJT50 & MACZ-50 Details For Securing Suspension Channels 10 Johnson Controls Unitary Products 5121846-TIM-A-0515 Table 3: Unit Mounting Dimensions DIMENSIONS, INCHES UNIT NHT25 AX 69-1/4 BX 49-1/16 CX 26-5/8 NJT30 69-1/4 49-1/16 26-5/8 NJT40 84 50-9/16 34 NJT50 87 51-1/2 ~ Table 4: Model Corner Weights & Center of Gravity NH/NJ Units Evaporator Blower Drive Center of 4 Point Load Location (lbs.) 6 Point Load Location (lbs.) Weight (lbs.) Section Section Section Gravity Drive HP Cabinet Cabinet Cabinet Shipp Opera CG X CG Y A B C D A B C D E F Wt (lb) Wt (lb) Wt (lb) ing ting Vertical Airflow NHT25 NJT30 NJT40 NJT50 MACZ-50 5 7.5 5.0 7.5 10 7.5 10 10 15 ~ 539 539 567 567 567 654 654 ~ ~ ~ 463 463 490 490 490 527 527 645 645 ~ 111 138 110 134 150 141 157 155 272 ~ 463 463 490 490 490 527 527 645 645 ~ 111 137.8 110.2 134 150 140.7 156.9 154.9 271.7 ~ 1067 1130 1067 1157 1122 1184 1122 1208 1122 1224 1246 1348 1246 1364 705 17421 705 18591 979 ~ 19.0 19.3 20.1 20.3 20.5 24.6 24.8 31.4 32.4 ~ 45.5 45.1 44.3 44.0 43.8 45.1 44.9 46.1 45.0 ~ 296 301 297 301 304 334 336 393 408 ~ 321 335 363 376 385 424 434 570 639 ~ 267 274 288 295 299 330 334 461 496 ~ 247 246 236 236 236 260 259 318 318 ~ 204 206 200 202 203 223 224 267 272 ~ 220 229 244 252 257 283 288 387 426 ~ 194 202 215 222 226 249 254 341 376 ~ 172 179 191 197 201 221 226 303 333 ~ 159 161 157 158 159 174 175 209 213 ~ 180 181 176 178 179 196 197 235 240 ~ 1067 1067 1122 1122 1122 1246 1246 705 705 979 35.2 35.4 36.4 36.5 36.6 43.1 43.2 52.1 52.5 ~ 45.5 45.1 44.3 44.0 43.8 45.1 44.9 46.1 45.0 ~ 320 329 332 339 345 387 392 446 480 ~ 297 307 328 338 344 371 378 517 567 ~ 247 252 260 265 268 288 291 418 440 ~ 266 269 264 266 268 301 303 361 373 ~ 220 225 224 227 230 258 261 303 320 ~ 204 210 221 226 230 248 251 351 378 ~ 180 185 195 199 202 218 221 309 333 ~ 160 164 173 177 180 194 196 275 296 ~ 172 176 175 178 180 202 204 237 250 ~ 194 198 197 200 203 228 230 267 282 ~ Horizontal Airflow NHT25 NJT30 NJT40 NJT50 MACZ-50 5 7.5 5.0 7.5 10 7.5 10 10 15 ~ 539 539 567 567 567 654 654 908.5 908.5 ~ 1130 1157 1184 1208 1224 1348 1364 17421 18591 ~ 1. Operating weight includes NJT50 Air handler and MACZ-50 Evaporator Coil Combined. Y (D) C CG (F) (C) A (A) (B) B Vertical Johnson Controls Unitary Products Y (D) C CG (F) X MOTOR X D (E) (C) MOTOR D (E) A (A) (B) B Horizontal 11 5121846-TIM-A-0515 Table 5: Accessory Operating Weight Distribution (Lbs)1 ACCESSORY BASE2 HOT WATER COIL STEAM COIL 1 ROW NHT25 25 35 30 NJT30 25 35 30 NJT40 30 45 ~ NJT50 ~ 35 ~ 1. These weights should be added to each point load in Table 4. 2. This accessory can only be applied on units installed in the vertical position. Drain Connections Refrigerant Mains All drain lines MUST be trapped and located so they will not be exposed to freezing temperatures. The evaporator blower has 7/8” OD steel condensate stub at each end of a single drain pan. Both ends are closed with plastic caps. A plastic or rubber ell can be used. (Field supplied) Attach the ell to the desired end and run a full size 7/8” drain line to the nearest drain facility. Seal the cap at the unused end with suitable mastic. This Split-System (Air Condensing / Heat Pump / Air Handling) unit is one component of an entire system. As such it requires specific application considerations with regard to the rest of the system (air handling unit, duct design, condensing unit, refrigerant piping and control scheme). Failure to properly apply this equipment with the rest of the system may result in premature failure and/or reduced performance / increased costs. Warranty coverage specifically excludes failures due to improper application and Unitary Products specifically disclaims any liability resulting from improper application. Drain piping should be constructed as shown in Figure 8. The 3-inch dimension must equal or exceed the negative static pressure developed by the supply air blowers. If it does not, the condensate will not drain properly and may overflow the drain pan. The trap must be at least 2-inches deep to maintain a water seal under all operating conditions, especially when the blowers are starting. Please refer to the equipment Technical Guide, Installation Manual and the piping applications bulletin 247077 or call the applications department for Unitary Products @ 1-877-UPG-SERV for guidance. Line Sizing When sizing refrigerant pipe for a split-system air conditioner, check the following: Figure 8: Recommended Drain Piping 12 1. Suction line pressure drop due to friction. 2. Liquid line pressure drop due to friction. 3. Suction line velocity for oil return. 4. Liquid line pressure drop due to vertical rise. For certain piping arrangements, different sizes of suction line pipe may have to be used. The velocity of the refrigerant vapor must always be great enough to carry the oil back to the compressor. 5. Evaporator Located Below Condenser - On a split system where the evaporator blower is located below the condenser, the suction line must be sized for both pressure drop and for oil return. 6. Condenser Located Below Evaporator - When the condenser is located below the evaporator blower, the liquid line must be designed for the pressure drop due to both friction loss and vertical rise. If the pressure drop due to vertical rise and friction exceeds 60 psi, some refrigerant will flash before it reaches the thermal expansion valve. Johnson Controls Unitary Products 5121846-TIM-A-0515 Flash gas: 1. Increases the liquid line pressure loss due to friction that in turn causes further flashing. 2. Reduces the capacity of the refrigerant control device which starves the evaporator. 3. Erodes the seat of the refrigerant control device. 4. Causes erratic control of the refrigerant entering the evaporator. Take Adequate Precautions Many service problems can be avoided by taking adequate precautions to provide an internally clean and dry system and by using procedures and materials that conform to established standards. Use hard drawn copper tubing where no appreciable amount of bending around pipes or other obstructions is necessary. If soft copper is used, care should be taken to avoid sharp bends that may cause a restriction. Pack fiberglass insulation and a sealing material such as permagum around refrigerant lines where they penetrate a wall to reduce vibrations and to retain some flexibility. Support all tubing at minimum intervals with suitable hangers, brackets or clamps. Braze all copper-to-copper joints with Silfos-5 or equivalent brazing material. Do not use soft solder. Insulate all suction lines with a minimum of 1/2" ARMAFLEX or equivalent that meets local codes. Liquid lines exposed to direct sunlight and/ or high temperatures must also be insulated. Never solder suction and liquid lines together. They can be taped together for convenience and support purposes, but they must be completely insulated from each other. Before beginning installation of the main lines, be sure that the evaporator section has not developed a leak in transit. Check pressure at the Schrader valve located on the header of each coil. If pressure still exists in the system, it can be assumed to be leak free. If pressure DOES NOT exist the section will need to be repaired before evacuation and charging is performed. A filter-drier MUST be field-installed in the liquid line of every system to prevent dirt and moisture from damaging the system. Properly sized filter-driers are shipped with each condensing section. NOTE: Installing a filter-drier does not eliminate the need for the proper evacuation of a system before it is charged. A field-installed moisture indicating sight-glass should be installed in the liquid line(s) between the filter-drier and the evaporator coil. The moisture indicating sight-glass can be used to check for excess moisture in the system . The evaporator coil has copper sealing disks brazed over the ends of the liquid and suction connections. The temperature required to make or break a brazed joint is high enough to cause oxidation of the copper unless an inert atmosphere is provided. Johnson Controls Unitary Products NOTE: Dry Nitrogen should flow through the system at all times when heat is being applied and until the joint has cooled. The flow of Nitrogen will prevent oxidation of the copper lines during installation. Always punch a small hole in sealing disks before unbrazing to prevent line pressure from blowing them off. Do not use a drill as copper shavings can enter system. NOTE: Solenoid and hot gas bypass valves (if used) should be opened manually or electrically during brazing or evacuating. NOTE: Schrader valves located on service valves should have their stems removed during brazing to prevent damaging to the valves. Line Installation Start Installation of main lines at the condenser unit. Verify the service valves are fully seated by screwing the stem of both valves down into the valve body until it stops. Remove the Schraded valve stem and connect a low-pressure nitrogen source to the service port on the suction line valve body. Punch a small hole in the sealing disk; the flow of Nitrogen will prevent any debris from entering the system. Wrap the valve body with a wet rag to prevent overheating during the brazing process. Overheating the valve will damage the valve seals. Unbraze the sealing disk, cool the valve body and prepare the joint for connections of the main lines. Repeat for the liquid line valve body. Never remove a cap from an access port unless the valve is fully back-seated with its valve stem in the maximum counter-clockwise position because the refrigerant charge will be lost. Always use a refrigeration valve wrench to open and close these service valves. Connect the main liquid line to the liquid line connection on the condenser unit, while maintaining a flow of Nitrogen. Cool the valve body and replace the Schraded valve stem on the service port of the liquid line service valve. Install the liquid line from the condenser unit to the evaporator liquid connection, maintaining a flow of nitrogen during all brazing operations. The filter-drier and sight glass must be located in this line, leaving the O.D. unit. Connect a low-pressure nitrogen source to the Schrader valve located on the evaporator section coil headers. Punch a small hole in the sealing disks, the flow of Nitrogen will prevent any debris from entering the system. Unbraze both liquid and suction sealing disks and prepare the joints for connections of the main lines. Connect the main liquid line to the liquid line connection on the evaporator section, while maintaining a flow of Nitrogen. 13 5121846-TIM-A-0515 Make the suction line connection at the evaporator and run the line to the condenser unit. Connect the main suction line to the suction line connection on the condenser unit, while maintaining a flow of nitrogen. Cool the valve body and replace the Schrader valve stem on the service port of the liquid line service valve. Once the brazing process is complete, leak testing should be done on all interconnecting piping and the evaporator before proper evacuation to 500 microns is performed. Once the line set and evaporator section is properly evacuated the service valves can be opened and the condensing unit is now ready to charge with the appropriate weight of refrigerant. This system uses R-410A Refrigerant which operates at higher pressures than R-22. No other refrigerant may be used in this system. Gage sets, hoses, refrigerant containers and recovery systems must be designed to handle R-410A. If you are unsure, consult the equipment manufacturer. Failure to use R-410A compatible servicing equipment may result in property damage or injury. NOTE: Ensure TXV bulbs are not crossed between systems. Undesirable performance and possible compressor damage may occur. Liquid Line Solenoids The unit is shipped with factory installed, normally closed, liquid line solenoid valves. When the solenoid coil is energized with a 24-volt signal, the valve will open. During brazing operations, the valves should be placed in the OPEN position by removing the stem cap with a 9/16” wrench, then rotating the exposed valve stem inward (CLOCKWISE) approximately 10-12 full turns (from the fully CLOSED position) using a 4” adjustable wrench. The valve stems should be returned to the CLOSED (COUNTER-CLOCKWISE) position prior to unit operation. The “Pump-out” procedure is detailed in the following section. The sequence of operation applies to the YH/YJ condensing units and NH/NJ air handlers when applied as a matched system. Non-matched systems will have to be field wired to operate in a similar fashion as described on page 38. NOTE: See Liquid Line Solenoid Wiring on pages 37, 38. Pump Out Wear safety glasses and gloves when handling refrigerants. Failure to follow this warning can cause serious personal injury. This instruction covers the installation and operation of the basic air handling unit. For refrigerant piping installation instructions refer to document 247077 "Application Data General Piping Recommendations for Split System Air Conditioning and Heat Pumps". Expansion Valve Bulb Installation NHT25 Thermal expansion valve bulbs are not factory-installed in their final locations. They must be fastened in a 4 o'clock and 8 o'clock position to the common suction line of the evaporator coil after piping connections are made. Use the bulb clamps from the bag taped to the suction connection inside the blower unit. NJT30/NJT40/NJT50 With MACZ-50 Thermal expansion valve bulbs are not factory-installed in their final locations. The bulb for System #1 must be fastened in a 4 o'clock or 8 o'clock position to the System #1 suction line leaving the evaporator coil after piping connections are made. Repeat the procedure for System #2, locating the bulb in a 4 o'clock or 8 o'clock position to the System #2 suction line. Use the bulb clamps from the bag taped to the suction connection inside the blower unit. 14 The pump out function is a standard feature on the 25 to 50 ton systems. The pump out circuit is activated each time the first and third compressor stage is called for by the thermostat. As such, it’s a “Pump Out On Start Up” design. A normally closed solenoid valve (POS1, 2, 3 or 4) is placed in the liquid line, just prior to the expansion valve. When cooling is not being called for by the thermostat, the pump out solenoid (POS) is not energized, so it’s in the closed position. When the Simplicity™ control receives a call for cooling, it energizes a compressor. With the POS being closed, it causes the pressure on the low side of the system to begin falling. When the low pressure switch (LPS) opens, the control board energizes its on-board pump out relay, providing a 24 vac output to an external relay used to energized the pump out solenoid. The refrigeration circuit being controlled is not in normal operating mode. If the low pressure switch is already open on a call for cooling, the pump out relay is energized immediately. If the LPS does not open after 5 minutes, the pump out relay is energized. Duct Connections Ductwork should always be suspended with hangers or supported by legs. It should never be fastened directly to the building structure. Allow clearance around ducts for safety in the handling of heated air and for insulation when required. Johnson Controls Unitary Products 5121846-TIM-A-0515 Insulation Supply Air Ducts Ductwork insulation should meet the following criteria: See Figure 9 for suggested method of connecting supply air ductwork. Non-flammable material collars should be used to minimize the transmission of noise and/or vibration. Be used when ducts pass through an unconditioned space in the cooling season or through an unheated space during the heating season. Include a vapor barrier around the outside to prevent the absorption of moisture. Be no less than 2 inches thick with the weatherproof coating when applied to ducts exposed to outdoor conditions. Return Air Duct Angles Return air duct angles are shipped turned in. They are intended to be unscrewed and turned for connection of ductwork. The return air grille accessory attaches in the same manner as the panels. DUCT TRANSITION NON-FLAMMABLE COLLAR DUCT 24" AIR OUTLET BLOWER GASKETS (BY INSTALLER) FLANGED DUCT CONNECTION (FIELD FABRICATED) Figure 9: Suggested Method For Connecting Ductwork Johnson Controls Unitary Products 15 5121846-TIM-A-0515 Electrical Data Table 6: UNIT MODEL Electrical Data HP 5 NHT25 7.5 5.0 NJT30 7.5 10 7.5 NJT40 10 10 NJT50 15 16 FLA VOLTAGE (3PH-60HZ) MIN CIRCUIT AMPACITY MAX. FUSE SIZE (Amps) 16.7 15.2 7.6 6.1 24.2 22 11 9 16.7 15.2 7.6 6.1 24.2 22 11 9 30.8 28 14 11 24.2 22 11 9 30.8 28 14 11 30.8 28 14 11 46.2 42 21 17 208 230 460 575 208 230 460 575 208 230 460 575 208 230 460 575 208 230 460 575 208 230 460 575 208 230 460 575 208 230 460 575 208 230 460 575 21 19 10 8 30 28 14 11 21 19 10 8 30 28 14 11 39 35 18 14 30 28 14 11 39 35 18 14 39 35 18 14 58 53 26 21 35 30 15 15 50 45 20 20 35 30 15 15 50 45 20 20 60 60 30 20 50 45 20 20 60 60 30 20 60 60 30 20 100 90 45 35 Johnson Controls Unitary Products 5121846-TIM-A-0515 Table 7: Overload Relay Kit VOLTAGE MOTOR HP 5 7.5 10 15 Table 8: 208/230V 460V OVERLOAD KIT 2MP04708300 2MP04708400 2MP04708500 2MP04708700 2MP04708500 2MP04708700 2MP04708900 2MP04709000 575V 2MP04708300 2MP04708300 2MP04708400 2MP04708500 Overload Setting VOLTAGE MOTOR HP 5 7.5 10 15 208/230V 460V 575V 14/13 21/20 26/25 38/36 OVERLOAD SETTING (Full Load Amps)12 6.5 9.5 13 18 5 7.5 10 15 1. Motors with Service Factor of 1.15 or Greater: Adjust overload relay dial to the motor nameplate Full Load Amps (FLA). 2. Motors with Service Factor Less Than 1.15: Adjust overload relay dial based on the formula: Motor nameplate FLA x 0.90 = relay setting Electrical Connections Air Handlers with Contactor 50 Ton Replacement Motor Contactor Installation The electric box ships complete with motor contactor, transformers, relays and terminal block for making field connections. Install a power supply to meet the requirements listed in Table 6. All 25 - 50 ton split-system indoor units come equipped with a 40 amp motor contactor. However, 50 ton units with a field installed 15 hp motor used in a 208 or 230 Volt application require a 60 amp motor contactor. In these cases, the 40 amp contactor must be replaced in the field with the 60 amp contactor that is provided with the overload relay kit. Follow the instructions below to replace the factory installed 40 amp contactor with the supplied 60 amp contactor. 1. Disconnect electrical power to the unit. The unit may have more than one power source. Provide a disconnect switch and fusing as required. 2. Install interconnecting control wiring between condensing section, evaporator blower and room thermostat. The 40 amp motor contactor is located in the unit control box. Disconnect all wires to the contactor. 3. Remove the two screws mounting the top of the contactor, and loosen the one screw at the bottom. Slide out the 40 amp contactor. 4. Mount the replacement 60 amp contactor by sliding the bottom screw slot under the screw loosened in Step 3. Replace the top two screws previously removed. Tighten all three screws to fix the contactor against the control box back plate. Make sure the 60 amp contactor is now mounted in the same orientation as the 40 amp contactor removed in Step 3. 5. Install the overload relay supplied in the kit. 6. Reconnect all wires, previously disconnected in Step 2, to the new 60 amp contactor per unit wiring diagram (40 amp contactor 60 amp contactor terminals are similar). 7. Reconnect electrical power to unit. NOTE: Remember: On air handlers with factory installed pump out solenoids, wires to the solenoid must be field connected. Refer to Figures 29 thru 35 for Indoor Unit Wiring Diagrams. Air Handlers are shipped without overload relays. These must be ordered separately to match the selected motor used in the air handler. See unit's Technical Guide or price page for correct overload relay. On 50 ton units with a 15 hp motor at 208 or 230 volts, the factory installed motor contactor must be replaced with a 60 amp contactor provided with the motor overload relay kit. Refer to 50 Ton Replacement Motor Contactor Installation section. NOTE: All unit models with contactor and overload relays, the power wiring for the blower motor is supplied with the overload relay kit. Johnson Controls Unitary Products 17 5121846-TIM-A-0515 Table 9: Unit Blower Motor Data UNIT MODEL HP MOTOR KIT MODEL NUMBER FRAME SIZE 2LP04605133 5 VOLTAGE (3PH-60-HZ) 208/230/460 184 2LP04605158 575 2LP04607133 208/230/460 NHT25 7.5 213 2LP04607158 575 2LP04605133 208/230/460 5.0 NJT30 184 2LP04605158 575 2LP04607133 208/230/460 7.5 213 2LP04607158 575 2LP04610133 208/230/460 10 215 2LP04610158 575 2LP04607133 208/230/460 7.5 213 2LP04607158 575 2LP04610133 208/230/460 NJT40 10 215 2LP04610158 575 2LP04610133 208/230/460 10 215 2LP04610158 575 2LP04615133 208/230/460 NJT50 15 254 2LP04615158 Drive Packages Units are shipped from the factory without the blower motor, drives and overload relays. Blower motors, overload relays and drive kits are ordered and shipped separately for field mounting. All motors are 3-phase. Blower shafts are extended to allow the blowers to be driven from either end. Motor rotation can be reversed by changing the power supply wiring at the motor terminal box. NOTE: : All blower motors have solid bases and are not inherently protected. For proper operation, these motors require overload relays. Please see current product price pages for overloads relay kits. Motor Mounting Units are shipped with a motor mounting assembly installed as shown in Figure 10 for the NHT25, NJT30, NJT40 and Figure 12 for the NJT50. The motor mounting arrangement can be changed to allow motor access based on the airflow arrangement required. The 18 575 recommended motor location for each blower arrangement is as follows. Standard Motor Arrangement (NHT25/NJT30/NJT40) The NHT25, NJT30 and NJT40 ship from the factory with a motor mounting adapter plate for use with the 7.5 and 10 HP motors. If a 5 HP motor is used, the adapter is not necessary and should be removed and discarded. The NHT25, NJT30 and NJT40 units are shipped with the motor mount in location A as shown in Figure 10. Optional Motor Arrangements are possible by moving the entire motor mounting assembly (mounting plate, channels, etc.) to the desired location. NOTE: The blower section must be lifted off the evaporator section to gain access to the mounting channel fasteners. Since these sections have to be repositioned for the Air Flow arrangements 2 through 10 and 12 of Figures 1 and 2, the motor mounting assembly should be relocated before the two sections are rejoined. Johnson Controls Unitary Products 5121846-TIM-A-0515 AIR FLOW ARRANGEMENT 2, 6 OR 7 AIR FLOW ARRANGEMENT 1, 4, 8 OR 11 SEE NOTES A B C D SEE NOTES AIR FLOW ARRANGEMENT 3, 5 OR 10 AIR FLOW ARRANGEMENT 9 OR 12 SEE NOTES SEE NOTES C B NOTE: Since the motor mounting assembly cannot be secured to the panel with the blower openings, the motor cannot be installed in either of the normally recommended bottom positions. Figure 10: NHT25/NJT30/NJT40 Motor Arrangements As Seen In Figures 1 and 2 NJT50 Bearing Alignment: Before the drive kit is installed, turn the blower assembly by hand several times. If it doesn't rotate freely, the center bearing may have been knocked out of alignment during shipping and/ or rigging. To realign, refer to Figure 11 and the following instructions: 1. Loosen the bearing collar set screw. 2. With a drift pin in the bearing collar removal hole, loosen the bearing collar by tapping the drift pin in the direction opposite to the shaft rotation. 3. Loosen bolts “A” and “B”. 4. Remove the shim. NOTE: The bearing support angle must be horizontal to the unit and below the bearing. 5. 6. Tighten bolts “A”. 7. With a drift pin in the bearing collar removal hole, tighten the bearing collar by tapping the drift pin once in the direction of the shaft rotation. 8. Tighten the bearing collar set screw. 9. Loosen bolts “B” 10. Raise the blower shaft and re-install the shim between the bearing and the bearing support angle. 11. Tighten bolts “B”. NJT50 Motor Mounting The motor mounting plate will accommodate a 10 or 15 HP motor (Refer to Figure 13) and can be raised or lowered using Tighten bolts “B” without the shim. Johnson Controls Unitary Products 19 5121846-TIM-A-0515 NJT50 Motor Arrangements B E A R IN G C O L L A R S E T S C R E W B E A R IN G B E A R IN G C O L L A R B E A C O L R E M H O L B L O W E R S H A F T R IN G L A R O V A L E S H A F T R O T A T IO N B O L T "B " B O L T "B " The NJT50 unit is shipped with the motor mounting plate in the standard location as shown in Figure 12. The motor mounting plate can be re-located to three alternate positions: Alternate Position 1 1. Remove pivot bolts from the mounting plate. 2. Remove the mounting plate from the adjustment screws. 3. Rotate mounting plate 180°. 4. Fasten the mounting plate with pivot bolts removed in Step 1. 5. Fasten mounting plate to the adjustment screws. S H IM B E A R IN G S U P P O R T A N G L E B O L T "A " Figure 11: NJT50 Center Bearing adjustment screws to cover the complete range of pulley settings. The physical size of the 15 HP motor reduces the adjustment range of the motor mounting plate. To maximize this amount of adjustment, one set of bolt holes is provided near the adjustment screws on each end of the motor mounting plate (Refer to Figure 13). For some motor/blower wheel arrangements, however, the motor cannot be mounted because the motor terminal box will interfere with one of the blower section panels. To make these motor/blower wheel arrangements possible, a second set of bolt holes is provided near the pivot bolts on each end of the motor mounting plate (See Figure 13).The 15 HP drive package requires two different lengths of belts to vary the blower wheel RPM over the complete range of rated conditions. When the motor is mounted near the adjustment screws, the two lengths of belt are interchangeable except for the higher and lower limits of blower wheel RPM. When the motor is mounted near the pivot bolts, the shorter length of belt is recommended for the higher blower wheel RPM's and the longer length of belt is recommended for the lower blower wheel RPM's. See Figure 12 for the recommended blower motor locations. Alternate Position 2 The motor mounting plate, the pivot bolts and the adjustment screws can be moved into a position similar to the one shown as standard in Figure 13 but under the other blower scroll. The framework under each blower scroll has the same bolt hole arrangement. Alternate Position 3 The motor mounting plate, the pivot bolts and the adjustment screws can be moved into a position similar to the one detailed in alternate position one but behind the other blower scroll. The framework behind each blower scroll has the same bolt hole arrangement. 1 5 H P 1 0 H P 1 5 H P 1 5 H P A lte r n a tiv e P o s itio n 1 F o r P iv o t B o lts 1 5 H P A lte r n a te P o s itio n 3 F o r P iv o t B o lts A d ju s tm e n t S c r e w H o le s A lte r n a tiv e P o s itio n 2 F o r P iv o t B o lts 1 0 H P 1 5 H P A d ju s tm e n t S c re w (2 ) M o to r M o u n tin g P la te ( S ta n d a r d L o c a tio n a s S h ip p e d ) 1 5 H P Figure 13: NJT50 Motor Mount Plate P iv o t B o lt ( 2 ) Figure 12: NJT50 Factory Motor Mounting Position 20 Johnson Controls Unitary Products 5121846-TIM-A-0515 Table 10: Unit Drive Data UNIT MODEL NHT25 NJT30 DRIVE KIT MODEL NUMBER BLOWER RPM RANGE 1LD0440 1LD0407 ADJUSTABLE MOTOR PULLEY FIXED BLOWER PULLEY BELTS PITCH DIA. (IN.) BORE (IN.) PITCH DIA. (IN.) BORE (IN.) QTY. PITCH LENGTH (IN.) DESIGNATION 600 - 750 4.0 - 5.0 1 1/8 12.0 1 3/16 2 63.3 A62 700 - 850 4.2 - 5.2 1 3/8 11.0 1 3/16 2 63.3 A62 1LD0442 780 - 940 5.3 - 6.3 1 3/8 12.0 1 3/16 2 63.3 A62 1LD0415 636 - 795 4.0 - 5.0 1 3/8 11.0 1 3/16 2 63.3 A62 1LD0407 668 - 827 4.2 - 5.2 1 3/8 11.0 1 3/16 2 63.3 A62 1LD0408 827 - 986 5.3 - 6.3 1 3/8 11.0 1 3/16 2 59.7 A59 1LD0409 607 - 776 4.3 - 5.5 1 3/8 12.4 1 3/16 2 85.1 B84 1LD0410 776 - 917 5.4 - 6.6 1 3/8 12.4 1 3/16 2 86.8 B85 1LD0411 692 - 833 4.8 - 6.0 1 3/8 12.4 1 3/16 2 78.6 B78 1LD0412 762 - 931 5.4 - 6.6 1 5/8 12.4 1 3/16 2 76.8 B75 NJT40 NJT50 Air System Adjustment B Refer to Tables 10 thru 13 to adjust the air system. Blower motor pulleys are adjustable in 1/2 turn increments. Twin Belt Drive Adjustment A E To verify that both belts drive at the same speed, make a mark across both belts. Turn the drive several revolutions by hand. If the mark has not separated, the belts are traveling at the same speed. Twin groove blower motor pulleys should be installed with the shaft set screw (A) towards the motor (See Figure 14). To align pulleys, the housing of the twin groove motor pulley may extend 25% of its length beyond end of motor shaft. Always align twin groove pulleys using the stationary web. Check belt tension. Drive packages are supplied with fiberglass belts that must be properly tensioned at installation because Johnson Controls Unitary Products B D C C STATIONARY WEB Figure 14: Double Groove Pulley they do not stretch. The belt should deflect 3/16" per foot of belt span with a 2 or 3-pound force. Alignment of the resilient motor mount can be corrected by adjustment at the slots on the end opposite the pulleys. 21 5121846-TIM-A-0515 Airflow Performance Table 11: Fan Performance Data - 25 Ton Available External Static Pressure - IWG CFM 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Motor & Drive 7500 7.5 HP Motor & Drive 600 2.04 648 2.50 694 3.00 738 3.54 781 4.08 823 4.63 863 5.16 903 5.66 942 6.10 981 6.49 603 2.17 652 2.63 698 3.13 742 3.67 785 4.22 827 4.76 867 5.29 907 5.79 946 6.24 984 6.62 608 2.32 656 2.78 702 3.28 747 3.81 789 4.36 831 4.91 871 5.44 911 5.93 950 6.38 989 6.77 8250 613 2.48 661 2.93 707 3.44 752 3.97 795 4.52 836 5.07 877 5.60 916 6.09 955 6.54 994 6.92 8500 619 2.65 667 3.10 713 3.61 758 4.14 800 4.69 842 5.24 882 5.77 922 6.26 961 6.71 1000 7.09 7750 8000 5 HP & Field supplied Drive 8750 575 2.43 625 2.83 673 3.28 720 3.79 764 4.32 807 4.87 848 5.42 889 5.95 928 6.44 967 6.89 1006 7.27 9000 581 2.62 632 3.02 680 3.47 726 3.98 771 4.51 814 5.06 855 5.61 896 6.14 935 6.63 974 7.08 1013 7.46 9250 589 2.82 639 3.21 687 3.67 734 4.17 778 4.71 821 5.26 862 5.80 903 6.33 942 6.83 982 7.28 9500 596 3.02 647 3.42 695 3.88 741 4.38 786 4.91 829 5.46 870 6.01 910 6.54 950 7.03 989 7.48 9750 604 3.23 655 3.63 703 4.09 749 4.59 794 5.13 836 5.67 878 6.22 918 6.75 958 7.25 10000 613 3.45 663 3.85 711 4.31 758 4.81 802 5.34 845 5.89 886 6.44 927 6.97 966 7.46 10250 621 3.68 672 4.07 720 4.53 766 5.03 811 5.57 853 6.12 895 6.66 935 7.19 944 7.42 10500 630 3.9 680 4.30 729 4.76 775 5.26 819 5.80 862 6.34 904 6.89 10750 639 4.14 689 4.53 738 4.99 784 5.50 828 6.03 871 6.58 913 7.12 11000 648 4.37 699 4.77 747 5.23 793 5.73 837 6.27 880 6.82 922 7.36 11250 657 4.62 708 5.01 756 5.47 802 5.97 847 6.51 890 7.06 899 7.30 11500 667 4.86 717 5.26 766 5.71 812 6.22 856 6.75 11750 676 5.11 727 5.50 775 5.96 821 6.46 866 7.00 12000 686 5.36 737 5.75 785 6.21 831 6.71 876 7.25 12250 696 5.61 746 6.00 795 6.46 841 6.97 885 7.50 12500 706 5.86 756 6.26 805 6.72 851 7.22 High static 7.5 HP & Field Supplied Drive Table 12: Fan Performance Data - 30 Ton CFM RPM 10,000 11,000 12,000 13,000 14,000 SP BHP kW SP BHP kW SP BHP kW SP BHP kW SP BHP kW 600 0.20 3.1 2.9 0.02 3.6 3.4 - - - - - - - - - 635 0.31 3.3 3.1 0.13 3.8 3.5 - - - - - - - - - 700 0.54 3.7 3.5 0.38 4.2 3.9 0.20 4.8 4.5 0.03 5.3 5.0 - - - 775 0.85 4.4 4.1 0.70 4.8 4.5 0.54 5.3 5.0 0.39 5.8 5.5 0.20 6.4 6.0 800 0.97 4.7 4.4 0.82 5.1 4.8 0.66 5.6 5.2 0.52 6.1 5.7 0.35 6.7 6.3 875 1.34 5.6 5.2 1.19 6.0 5.7 1.04 6.6 6.2 0.93 7.1 6.6 0.77 7.7 7.2 900 1.47 5.9 5.5 1.33 6.4 6.0 1.17 7.0 6.5 1.07 7.5 7.0 0.90 8.2 7.6 940 1.70 6.5 6.1 1.55 7.0 6.6 1.40 7.7 7.2 1.31 8.3 7.8 1.09 9.0 8.4 Table 13: Fan Performance Data - 40 Ton CFM RPM 22 12,800 14,400 16,000 17,600 SP BHP kW SP BHP kW SP BHP kW SP BHP kW 600 0.84 6.0 5.2 0.63 7.2 6.2 0.40 8.4 7.2 660 1.19 7.3 6.3 1.00 8.5 7.3 0.78 9.8 8.5 0.13 9.7 8.4 0.50 11.2 700 1.42 8.2 7.1 1.25 9.4 8.1 1.03 10.7 9.7 9.2 - - 760 1.78 9.5 8.2 1.63 10.8 9.3 - - - - - - 800 2.02 10.4 9.0 1.89 11.8 10.2 - - - - - - - Johnson Controls Unitary Products 5121846-TIM-A-0515 Table 14: Fan Performance Data - 50 Ton CFM RPM 16,000 18,000 20,000 22,000 SP BHP kW SP BHP kW SP BHP kW SP 600 0.82 6.0 5.2 0.59 7.2 6.2 0.35 8.4 7.2 660 1.17 7.3 6.3 0.96 8.5 7.3 0.73 9.8 8.5 700 1.40 8.2 7.1 1.21 9.4 8.1 0.98 10.7 9.2 760 1.76 9.5 8.2 1.59 10.8 9.3 1.38 12.3 800 2.00 10.4 9.0 1.85 11.8 10.2 1.64 13.3 900 2.60 12.8 11.0 2.49 14.5 12.5 2.35 930 2.78 13.5 11.6 2.68 15.3 13.2 - To check the supply air CFM after the initial balancing has been completed: 1. Drill two (2) 5/16-inch holes in the side panel as shown in Figure 15. 2. Insert at least 8 inches of 1/4 inch tubing into each of these holes for sufficient penetration into the airflow on both sides of the evaporator coil. BHP kW 0.08 9.7 8.4 - - - 0.45 11.2 9.7 0.14 12.7 11.0 0.70 12.2 10.5 0.40 13.7 11.8 10.6 1.11 13.8 11.9 0.81 15.6 13.5 11.5 1.38 14.9 12.9 1.09 16.9 14.6 16.0 13.8 - - - - - - - - - - - - - - 4. Using an inclined manometer, determine the pressure drop across the dry evaporator coil. Since the moisture on an evaporator coil may vary greatly, measuring the pressure drop across the wet coil under field conditions would be inaccurate. To assure a dry coil, the refrigerant system should be de-activated while running the test. BHP kW 25" 5/16" HOLE EVAPORATOR COIL 22" 5/16" HOLE Knowing the pressure drop across a dry coil, the actual CFM through the unit can be determined from the curves shown in Figures 16-19. If the CFM is above or below the specified value, the supply air motor pulley may have to be readjusted. After one hour of operation, check the belt and pulleys for tightness and alignment. SP After readings are obtained, remove the tubes and seal up the drilled holes in the side panel. Dot plugs (P/N 9509) are available through normal York parts ordering procedures. 7" 3. 24,000 14" FILTERS COIL SECTION Figure 15: Hole Locations For Reading Coil Pressure Drop Failure to properly adjust the total system air quantity can result in extensive blower damage. Johnson Controls Unitary Products 23 5121846-TIM-A-0515 Pressure Drop Across Dry Indoor Coil 0.70 0.60 I.W.C. 0.50 0.40 0.30 0.20 0.10 0.00 9000 11000 13000 15000 CFM Figure 16: NHT25 - Pressure Drop Vs. Cfm Across Dry Indoor Coil Pressure Drop Across Dry Indoor Coil 0.70 0.60 I.W.C. 0.50 0.40 0.30 0.20 0.10 0.00 9000 10000 11000 12000 13000 14000 15000 CFM Figure 17: NJT30 - Pressure Drop Vs. Cfm Across Dry Indoor Coil 24 Johnson Controls Unitary Products 5121846-TIM-A-0515 Pressure Drop Across Dry Indoor Coil 0.70 0.60 I.W.C. 0.50 0.40 0.30 0.20 0.10 0.00 12000 14000 16000 18000 20000 CFM Figure 18: NJT40 - Pressure Drop Vs. Cfm Across Dry Indoor Coil Pressure Drop Across Dry Indoor Coil 0.70 0.60 I.W.C. 0.50 0.40 0.30 0.20 0.10 0.00 15000 17000 19000 21000 23000 25000 CFM Figure 19: NJT50 & MACZ-50 - Pressure Drop Vs. Cfm Across Dry Indoor Coil Johnson Controls Unitary Products 25 5121846-TIM-A-0515 TOP 22.0 62.4 22.5 5.3 22.0 5.3 2.6 9.1 3.0 19.0 SUPPLY AIR SUPPLY AIR 4X Ø.88 K0 CONTROLS CONNECTION 15.9 Ø 0.88 K0 ELECTRIC HEAT CONNECTION 57.7 FRONT SIDE 36.7 RETURN AIR RETURN AIR 74.6 Ø 1.38 KO Ø 0.88 LIQUID CONNECTION 37.3 33.2 Ø 2.13 SUCTION CONNECTION 25.0 Ø 0.88 DRAIN CONNECTION 7.6 3.5 2.4 3.4 4.1 4.2 0.1 95.6 100.1 38.1 Figure 20: NHT25 Unit Dimensions 26 Johnson Controls Unitary Products 5121846-TIM-A-0515 HORIZONTAL CONFIGURATION RETURN AIR SUPPLY AIR 73.3 74.0 Figure 21: NHT25 Unit Dimensions (Continued) Johnson Controls Unitary Products 27 5121846-TIM-A-0515 TOP 22.0 62.4 22.0 22.5 5.3 5.3 2.6 9.1 3.0 19.0 SUPPLY AIR SUPPLY AIR 4X Ø0.88 KO CONTROLS CONNECTION 15.9 Ø0.88 KO ELECTRIC HEAT CONNECTION 57.7 FRONT SIDE 36.7 RETURN AIR Ø0.88 LIQUID CONNECTION SYSTEM 1 RETURN AIR 74.7 Ø0.88 LIQUID CONNECTION SYSTEM 2 5.9 37.3 Ø1.125 SUCTION CONNECTION SYSTEM 1 33.2 23.6 Ø0.88 DRAIN CONNECTION 3.6 5.5 2.4 0.63 95.6 100.1 Ø1.125 SUCTION CONNECTION SYSTEM 2 38.1 3.4 4.1 6.1 5.1 Figure 22: NJT30 Unit Dimensions 28 Johnson Controls Unitary Products 5121846-TIM-A-0515 HORIZONTAL CONFIGURATION RETURN AIR SUPPLY AIR 73.3 74.0 Figure 23: NJT30 Unit Dimensions (Continued) Johnson Controls Unitary Products 29 5121846-TIM-A-0515 TOP 60.5 20.6 22.0 22.0 5.3 5.3 2.6 5.5 3.0 19.0 SUPPLY AIR 4X Ø0.88 KO CONTROLS CONNECTION SUPPLY AIR FRONT SIDE 44.0 RETURN AIR RETURN AIR Ø0.88 LIQUID CONNECTION SYSTEM 1 89.4 Ø0.88 LIQUID CONNECTION SYSTEM 2 10.1 44.7 40.5 Ø1.375 SUCTION CONNECTION 23.1 SYSTEM 1 3.5 2.4 0.63 98.5 103.1 105.1 Ø1.375 SUCTION CONNECTION SYSTEM 2 3.2 4.3 4.5 7.1 7.9 7.6 Ø0.88 DRAIN CONNECTION 45.4 Figure 24: NJT40 Unit Dimensions 30 Johnson Controls Unitary Products 5121846-TIM-A-0515 HORIZONTAL CONFIGURATION RETURN AIR SUPPLY AIR 88.2 88.8 Figure 25: NJT40 Unit Dimensions (Continued) Johnson Controls Unitary Products 31 5121846-TIM-A-0515 TOP 103.1 18.5 61.7 23.0 23.0 Ø0.88 KO CONTROLS CONNECTION 2.6 24.9 Ø1.13 KO CONTROLS CONNECTION SUPPLY AIR SUPPLY AIR Ø1.38 KO CONTROLS CONNECTION 7.8 9.1 6.1 4.6 6.1 DETIAL A SCALE 0.375 (2X TYP) SEE DETAIL A FRONT SUPPLY AIR SIDE SUPPLY AIR 45.4 44.0 45.5 Figure 26: NJT50 Unit Dimensions 32 Johnson Controls Unitary Products 5121846-TIM-A-0515 TOP 53.7 FRONT RETURN AIR SIDE RETURN AIR Ø0.88 LIQUID CONNECTION SYSTEM 1 Ø0.88 LIQUID CONNECTION SYSTEM 2 10.2 54.4 49.5 27.6 13.3 3.4 2.4 2.3 98.5 103.1 105.1 Ø2.13 SUCTION CONNECTION Ø2.13 SUCTION SYSTEM 1 CONNECTION SYSTEM 2 53.7 3.2 6.7 7.6 7.3 Ø.88 DRAIN CONNECTION Figure 27: MACZ-50 Evaporator Section Dimensions Johnson Controls Unitary Products 33 5121846-TIM-A-0515 VERTICAL CONFIGURATION FRONT SIDE 45.5 SUPPLY AIR SUPPLY AIR RETURN AIR RETURN AIR 99.0 97.8 54.4 103.1 53.7 105.1 HORIZONTAL CONFIGURATION NAMEPLATE RETURN AIR SUPPLY AIR 97.2 98.4 Figure 28: NJT50 Air handler & MACZ-50 Evaporator Coil Dimensions 34 Johnson Controls Unitary Products 5121846-TIM-A-0515 Table 15: Unit Connection Sizes Model Dimensions (inches) NHT25 NJT30 NJT40 NJT50 MACZ-50A Length Width Height 100.1 38.1 74.6 100.1 38.1 74.7 103.1 45.4 89.4 103.1 45.5 45.4 103.1 53.7 54.4 1 2 1/8 7/8 7/8 7/8 7/8 2 1 1/8 7/8 7/8 7/8 7/8 2 1 3/8 7/8 7/8 7/8 7/8 1 3/8 7/8 - 2 2 1/8 7/8 7/8 2 19.0 22.0 2 19.0 22.0 2 19.0 22.0 2 24.9 23.0 - 33.2 95.6 33.2 95.6 40.5 98.5 - 49.5 98.5 System Data No. Refrigeration Circuits Suction Line OD (in.) Liquid Line OD (in.) Power Wiring Knockout Control Wiring Knockout Drain Line Blower Outlet Number Width Length Return Air Inlet Width Length Maintenance Filters must be cleaned or replaced as often as necessary to assure good airflow and filtration. To remove filters through the sides of the unit, remove either the solid side panel on the piping end, or the larger side panel on the end opposite the piping. To remove the filters from the front of the unit, loosen 2 screws and raise the top filter retainer. The upper filters can be lifted over the center filter lip. Three wing nuts are provided under the center filter retainer. Remove these and a part of the center filter support, giving access to the bottom filters. Drain pan(s) should be inspected regularly to assure proper drainage. The evaporator blower bearings and blower motor bearings are permanently lubricated. Johnson Controls Unitary Products 35 5121846-TIM-A-0515 Typical Wiring Diagrams Figure 29: Typical NC300 Indoor Unit Wiring Diagram (Contactor) 36 Johnson Controls Unitary Products 5121846-TIM-A-0515 Figure 30: Typical ND360, 480 & 600 Indoor Unit Wiring Diagram (Contactor) Johnson Controls Unitary Products 37 5121846-TIM-A-0515 Figure 31: Typical Field Wiring Diagram - NHT25 Evaporator Unit with YHT25 Condenser Unit NOTE: On non NH/NJ Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit. Figure 32: Typical NHT25 Liquid Line Solenoid Wiring 38 Johnson Controls Unitary Products 5121846-TIM-A-0515 Figure 33: Typical Field Wiring Diagram NJT30/T40 Evaporator Units, NJT50 Air Handler and MACZ-50A Evaporator Coil when Matched with YJ-30/T40/T50 Condenser NOTE: On non NJ evaporator models, isolation relays must be installed to avoid overloading on 75VA transformers on the condensing unit. Figure 34: Typical NJT30/T40 & MACZ-50A Liquid Line Solenoid Johnson Controls Unitary Products 39 5121846-TIM-A-0515 Standard Terminal Block on NHT25, NJT30/T40 and NJT50 with MACZ-50A models. On non NH/NJ models isolation relays must be installed to avoid overloading on 75 VA transformer on condensing unit. Primary side of transformer connect to line side of power supply. Primary side of transformer connect to line side of power supply. Non NH/NJ units may not include any or all of the components required to wire the unit. Use the diagram as general reference only. Figure 35: Typical Liquid Line Solenoid Wiring 40 Johnson Controls Unitary Products 5121846-TIM-A-0515 Start-Up Sheet START-UP & SERVICE DATA INSTRUCTION COMMERCIAL SPLIT SYSTEMS 7.5 To 50.0 TON START-UP CHECKLIST Date: ________________________________________________________________________________________________________ Job Name: ___________________________________________________________________________________________________ Customer Name: ______________________________________________________________________________________________ Address: _____________________________________________________________________________________________________ City: ______________________________ State: ______________________________ Zip: ________________________________ Evaporator Model Number: _______________________________ Serial Number:___________________________________________ Condenser Model Number: _______________________________ Serial Number:___________________________________________ Qualified Start-up Technician: _________________________________ Signature: __________________________________________ HVAC Contractor: _________________________________________________________ Phone: ______________________________ Address: _____________________________________________________________________________________________________ Contractor’s E-mail Address: _____________________________________________________________________________________ Electrical Contractor: _________________________________________________________ Phone:___________________________ Distributor Name: ___________________________________________________________ Phone: ___________________________ WARRANTY STATEMENT Johnson Controls/UPG is confident that this equipment will operate to the owner's satisfaction if the proper procedures are followed and checks are made at initial start-up. This confidence is supported by the 30 day dealer protection coverage portion of our standard warranty policy which states that Johnson Controls/UPG will cover parts and labor on new equipment start-up failures that are caused by a defect in factory workmanship or material, for a period of 30 days from installation. Refer to current standard warranty policy and warranty manual found on UPGnet for details. In the event that communication with Johnson Controls/UPG is required regarding technical and/or warranty concerns, all parties to the discussion should have a copy of the equipment start-up sheet for reference. A copy of the original start-up sheet should be filed with the Technical Services Department. The packaged unit is available in constant or variable air volume versions with a large variety of custom options and accessories available. Therefore, some variation in the startup procedure will exist depending upon the products capacity, control system, options and accessories installed. This start-up sheet covers all startup check points common to all package equipment. In addition it covers essential startup check points for a number of common installation options. Depending upon the particular unit being started not all sections of this startup sheet will apply. Complete those sections applicable and use the notes section to record any additional information pertinent to your particular installation. Warranty claims are to be made through the distributor from whom the equipment was purchased. EQUIPMENT STARTUP Use the local LCD or Mobile Access Portal (MAP) Gateway to complete the start-up. A copy of the completed start-up sheet should be kept on file by the distributor providing the equipment and a copy sent to: Johnson Controls/UPG Technical Services Department 5005 York Drive Norman, OK 73069 1034350-UCL-B-1114 Johnson Controls Unitary Products 41 5121846-TIM-A-0515 1034350-UCL-B-1114 SAFETY WARNINGS The inspections and recording of data outlined in this procedure are required for start-up of Johnson Controls/UPG's packaged products. Industry recognized safety standards and practices must be observed at all times. General industry knowledge and experience are required to assure technician safety. It is the responsibility of the technician to assess all potential dangers and take all steps warranted to perform the work in a safe manner. By addressing those potential dangers, prior to beginning any work, the technician can perform the work in a safe manner with minimal risk of injury. Lethal voltages are present during some start-up checks. Extreme caution must be used at all times. Moving parts may be exposed during some startup checks. Extreme caution must be used at all times. NOTE: Read and review this entire document before beginning any of the startup procedures. DESIGN APPLICATION INFORMATION This information will be available from the specifying engineer who selected the equipment. If the system is a VAV system the CFM will be the airflow when the remote VAV boxes are in the full open position and the frequency drive is operating at 60 HZ. Do not proceed with the equipment start-up without the design CFM information. Design Supply Air CFM: __________________________ Design Return Air CFM:______________________________________ Design Outdoor Air CFM At Minimum Position: ________________________________________________________ Total External Static Pressure: _____________________________________________________________________ Supply Static Pressure: __________________________________________________________________________ Return Static Pressure: __________________________________________________________________________ Design Building Static Pressure: ___________________________________________________________________ ADDITIONAL APPLICATION NOTES FROM SPECIFYING ENGINEER: 2 42 Unitary Products Group Johnson Controls Unitary Products 5121846-TIM-A-0515 1034350-UCL-B-1114 REFERENCE General Inspection Completed See Notes Unit inspected for shipping, storage, or rigging damage Unit installed with proper clearances Unit installed within slope limitations Refrigeration system checked for gross leaks (presence of oil) Terminal screws and wiring connections checked for tightness Filters installed correctly and clean Condensate drain trapped properly, refer to Installation Manual All field wiring (power and control) complete Refrigerant Line Inspection Is Condenser below Evaporator? System 1 Yes No System 2 Yes No Total Line Length end to end. _______ Ft. _______ Ft. Vertical Lift in Ft. _______ Ft. _______ Ft. Vertical Fall in Ft. _______ Ft. _______ Ft. Number of Elbows? _______ Ea. _______ Ea. Liquid Line Size _______ Ea. _______ Ea. Suction Line Size _______ Ea. _______ Ea. Solenoid Valve? Yes No Yes No Check Valves? Yes No Yes No Check Valves / Solenoid arrangements installed as per UPG Piping Guide Yes No Yes No Oil Separator ? Yes No Yes No Accumulator ? Yes No Yes No TXV - Hard shutoff Yes No Yes No Heatpump Yes No Yes No Completed See Notes Alignment of drive components Air Moving Inspection Belt tension adjusted properly Blower pulleys tight on shaft, bearing set screws tight, wheel tight to shaft Pressure switch or transducer tubing installed properly Unitary Products Group Johnson Controls Unitary Products 3 43 5121846-TIM-A-0515 1034350-UCL-B-1114 Operating Measurements - Air Flow Fan operates with proper rotation ID Fans Exh. Fans Cond. Fans Pressure drop across dry evaporator coil (At maximum design CFM) 1 IWC External Static Pressure IWC Return Static Pressure IWC Supply Static Pressure IWC Supply Air CFM Using Dry Coil Chart CFM Final Adjusted Supply Air CFM2 CFM 1. Consult the proper airflow to pressure drop table to obtain the actual airflow at the measured pressure differential. 2. Was a motor pulley adjustment or change required to obtain the correct airflow? Was it necessary to increase of decrease the airflow to meet the design conditions? If the motor pulley size was changed, measure the outside diameters of the motor and blower pulleys and record those diameters here; Blower Motor HP _______________________________ FLA________ RPM________ Pulley Pitch Diameter ______________Turns Out________ Final Turns Out________ Blower Pulley Pitch Diameter ________________ Fixed Sheave_________________ ELECTRICAL DATA T1 - T2 ____________________________ Volts T2 - T3 ____________________________ Volts Control Voltage ______________________ Volts T1 - T3 ____________________________ Volts Device Measured List All Three Amperages Nameplate Supply Fan Motor1,2 AMPS AMPS Condenser Fan #1 AMPS AMPS Condenser Fan #2 (if equipped) AMPS AMPS Condenser Fan #3 (if equipped) AMPS AMPS Condenser Fan #4 (if equipped) AMPS AMPS Compressor #1 AMPS AMPS Compressor #2 (if equipped) AMPS AMPS Compressor #3 (if equipped) AMPS AMPS Compressor #4 (if equipped) AMPS AMPS 1. VAV units with heat section - simulate heat call to drive VAV boxes and VFD/IGV to maximum design airflow position. 2. VAV units without heat section - VAV boxes must be set to maximum design airflow position. Notes above apply for 3rd party application only. 4 44 Unitary Products Group Johnson Controls Unitary Products 5121846-TIM-A-0515 1034350-UCL-B-1114 OPERATING MEASUREMENTS - COOLING Discharge Pressure Stage Liquid Line Suction Discharge Pressure At Liquid Line Subcooling2 Pressure Service Temp.1 Temp. Valve Suction Temp. Superheat First3 # ° # ° ° # ° ° Second (if equipped) # ° # ° ° # ° ° Third (if equipped) # ° # ° ° # ° ° Fourth (if equipped) # ° # ° ° # ° ° Heat Pump 1st Stage # ° # ° ° # ° ° 1. Liquid line temperature should be taken before filter/drier. 2. Subtract 10 psi from discharge pressure for estimated liquid line pressure 3. If Rawal valve installed, contact Technical Service. Outside air temperature ________________ db °F ________________ wb °F ________________ RH% Return Air Temperature ________________ db °F ________________ wb °F ________________ RH% Mixed Air Temperature ________________ db °F ________________ wb °F ________________ RH% Supply Air Temperature ________________ db °F ________________ wb °F ________________ RH% REFRIGERANT SAFETIES Completed See Notes Prove Compressor Rotation (3 phase only) by guage pressure Action Prove High Pressure Safety, All Systems Prove Low Pressure Safety, All Systems OPERATING MEASUREMENTS ELECTRIC HEATING Heater kW ____________kW Heater Voltage, Nameplate ____________ Volts Heater Model Number: _______________________________ Serial Number: ______________________________________ Heater Nameplate Measured List All Three Amperages Stage 1 _________AMPS _________AMPS _________AMPS _________AMPS Stage 2 _________AMPS _________AMPS _________AMPS _________AMPS Stage 3 _________AMPS _________AMPS _________AMPS _________AMPS Stage 4 _________AMPS _________AMPS _________AMPS _________AMPS Checked Heater Limit Yes No Air Moving Switch Installed? Yes No Unitary Products Group Johnson Controls Unitary Products 5 45 OPERATIONAL MEASUREMENTS - STAGING CONTROLS Verify Proper Operation of Heating/Cooling Staging Controls Create a cooling demand at the Thermostat, BAS System or Simplicity SE Verify that cooling/economizer stages are energized. Create a heating demand at the Thermostat, BAS System or Simplicity SE Verify that heating stages are energized. Verify Proper Operation of the Variable Frequency Drive (If Required) Verify that motor speed modulates with duct pressure change. FINAL - INSPECTION Verify that all operational control set points have been set to desired value Scroll through all setpoints and change as may be necessary to suit the occupant requirements. Verify that all option parameters are correct Scroll through all option parameters and ensure that all installed options are enabled in the software and all others are disabled in the software. (Factory software settings should match the installed options) Verify that all access panels have been closed and secured OBSERVED PRODUCT DIFFICIENCIES & CONCERNS: _______________________________________________________________________________________________________ _______________________________________________________________________________________________________ _______________________________________________________________________________________________________ _______________________________________________________________________________________________________ _______________________________________________________________________________________________________ _______________________________________________________________________________________________________ _______________________________________________________________________________________________________ _______________________________________________________________________________________________________ _______________________________________________________________________________________________________ _______________________________________________________________________________________________________ _______________________________________________________________________________________________________ _______________________________________________________________________________________________________ _______________________________________________________________________________________________________ _______________________________________________________________________________________________________ _______________________________________________________________________________________________________ Subject to change without notice. Printed in U.S.A. Copyright © 2015 by Johnson Controls, Inc. All rights reserved. York International Corporation 5005 York Drive Norman, OK 73069 5121846-TIM-A-0515 Supersedes: Nothing
advertisement
Key Features
- R-410A refrigerant
- Indoor installation
- Split-system
- Evaporator coil section
- Blower section
- Multiple air discharge patterns
- Thermal expansion valve
- Liquid line solenoid
- Pump-out function
- Duct connections