- Industrial & lab equipment
- Personal safety & protection
- Fire protection
- Bosch
- B920
- Installation Guide
- 2 Pages
Bosch B920 keypad Installation Guide
Below you will find brief information for keypad B920. The B920 keypad is an SDI2 bus compatible device that displays two-line system messages, and user adjustable options such as volume and display brightness. The keypad connects to the SDI2 bus on the control panel using terminal wiring. The keypad can be programmed locally (from the control panel keypad) or remotely through Remote Programming Software (RPS).
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
1 | Overview
The B920 keypad is an SDI2 bus compatible device. Each keypad has an LCD display that shows two-line system messages, and user adjustable options such as volume and display brightness.
The keypad connects to the SDI2 bus on the control panel using terminal wiring. You can connect more than one keypad to the control panel by wiring them in parallel.
You can program, diagnose, and troubleshoot the system from the control panel keypad as well as remotely through Remote
Programming Software (RPS).
10
5
1
7
3 6 2 1
4
R Y G B
7
10
5
9
10
8
2.1 | Access the address switches
1. Unlock the keypad by turning the lock counter-clockwise.
Refer to Figure 2.1.
2. Hold the keypad by the base in one hand. With the other hand, gently push down on the keypad to remove it from the base. Refer to Figure 2.2.
3. Look at the back of the keypad, and locate the switches.
Refer to Figure 2.3
Figure 2.1: Unlocking the keypad
6 1
Figure 1.1: Keypad base overview
Callout ― Description
1 ― Wall mount holes
2 ― Single gang box holes
3 ― Double gang box holes
4 ― Wire opening
5 ― Surface mount wire openings
6 ― Gang box holes (3-4 in)
7 ― Surface mount wire channel
8 ― Bubble level
9 ― SDI2 wiring terminal block
10 ― Wire tie posts
2 3 6 5
2 | SDI2 address switches
Two switches determine the address for the keypad. The control panel uses the address for communications. Use a slotted screwdriver to set the switches.
Figure 2.2: Removing the keypad from base
1
Figure 2.3: Switches location
Callout ― Description
1 ― Address switches
2.2 | Set the address switches
Set the address switches per the control panel confi guration.
If multiple SDI2 keypads reside on the same system, each
SDI2 keypad must have a unique address. For single-digit addresses 1 through 9, set the tens switch to 0. Figure 2.4 shows the address switch setting for address 1.
3 | Installation
After you set the address switches for the proper address, mount the keypad base, wire to the control panel, and attach the keypad to the base.
Caution!
Remove all power (AC and battery) before making any connections. Failure to do so might result in personal injury and/or equipment damage.
3.1 | Mount the keypad
You can surface mount the keypad, or mount it to standard electrical boxes, including single gang boxes.
Mounting the keypad:
1. Use the base as a template to mark the desired mounting surface. Refer to Figure 1.1 for mounting hole and wiring locations.
2. Pull the wiring through the desired wire opening in the base.
3. Use the appropriate mounting hardware (supplied) to mount the base to the desired mounting surface. Refer to Figure 1.1 for mounting hole and wiring locations .
3.2 | Wire to the control panel
When you wire the keypad to a control panel, use the control panel terminals labeled R, Y, G, B (PWR, A, B, COM). Connect them to the keypad terminals labeled R, Y, G, B. Refer to
Figure 3.1.
You can connect keypads to the SDI2 data bus by parallel wire run from the control panel to each keypad, wire from keypad to keypad, or a combination of the two techniques. Refer to
Figure 3.2.
Figure 3.2: Installing multiple keypads using the SDI2 terminals
Reconnect the keypad to the base by sliding the keypad onto the base (reverse of Step 2). The keypad automatically locks onto the base. Apply power to the system.
4 | Display
You can adjust the keypad’s display brightness level, and you can turn the keypad’s nightlight feature on or off.
Adjusting the keypad display brightness:
1. Press [MENU] to open the Main menu.
2. Use [NEXT] to go to the Press 5 for Settings Menu option, or simply press [5].
3. Use [NEXT] to go to the Press 4 for Keypad Confi g option, or simply press [4].
4. Press [1] to adjust the brightness.
5. Use [PREV] or [NEXT] to adjust the brightness level. The changes apply immediately.
6. Press [ESC] to exit the menu.
Turning the keypad nightlight on or off (control panel version
2.1 or higher):
1. Press [MENU] to open the Main menu.
2. Use [NEXT] to go to the Press 5 for Settings Menu option, or simply press [5].
3. Use [NEXT] to go to the Press 4 for Keypad Confi g option, or simply press [4].
4. Use [NEXT] to go to the Press 4 for Nightlight option, or simply press [4].
5. Use [PREV] or [NEXT] to toggle between the Yes and No options.
6. Press [ENTER] while viewing the desired option to save the programming.
7. Press [ESC] to exit the menu.
Figure 3.1: Wiring the keypad to the SDI2 bus connection
(B5512 shown)
Callout ― Description
1 ― Control panel
2 ― Terminal wiring
3 ― Keypad’s wiring terminal block
.
Figure 2.4: Address switches
5 | Status indicators
You can diagnose and troubleshoot the system using the keypad’s status indicators. Refer to Table 5.1.
Status indicator
Function LED On
Ready to turn on (arm)
Turned on (armed)
GAS
System trouble
Gas alarm
AC power present
Table 5.1: Keypad status indicators
6 | Audible tones
The keypad has a built-in speaker that produces several distinct warning tones. The keypad backlight illuminates when it emits an audible tone.
Tone
Fire alarm
Description
When an area is in fi re alarm, the keypad emits a pulsed, high-pitched bell tone.
Gas alarm
User alarm
Burglary alarm When an area is in alarm, the keypad emits a steady, high pitched bell tone.
Entry delay The keypad emits an intermittent beep tone during entry delay periods to remind the user to disarm the area.
Exit delay
Invalid button buzz
Keypress
The keypad emits an intermittent beep tone during exit delay.
When an invalid button, or sequence of buttons, is pressed, the keypad emits a fl at buzz tone.
The keypad emits a muted beep tone as each button is pressed to indicate that the entry was accepted.
Trouble
Watch point fault
When a gas point activates, the keypad emits a unique high pitched tone.
When a user alarm (such as panic and medical alarms) occurs, the tone sounds for the programmed amount of time.
When a trouble event occurs, such as a service alert, the keypad emits a two-tone warble until you enter a programmed passcode with the appropriate authority.
A single clean tweedle tone alerts the user anytime a watch point is faulted.
Table 6.1: Keypad audible tones
7 | Supervision
The control panel supervises all keypads on the SDI2 bus.
If a supervised keypad fails to respond to the control panel, the control panel declares a Missing Keypad Trouble. When the control panel can again communicate with the keypad, it restores the Missing Keypad Trouble.
During a Missing Keypad Trouble, any connected keypad that maintained contact with the control panel shows the Missing
Keypad Trouble as its idle text, and shows the missing keypad’s address. The communicating keypads also sound a trouble tone. Users can silence the trouble tone. If no other troubles exist, the tone silences when the missing keypad restores.
8 | Show the fi rmware version
Showing the keypad fi rmware version:
1. Remove the keypad from the base to remove power to the keypad. Refer to Figures 2.1 and 2.2.
2. Return the keypad to the base to restore power.
The keypad shows the model number, keypad address, and fi rmware version for 10 seconds.
NOTICE!
You can also view a keypad’s fi rmware version in RPS.
9 | Keypad cleaning
Use a soft cloth and non-abrasive cleaning solution to clean your keypad (for example, microfi ber cloth and eyeglass cleaner).
Spray the cleaner onto the cloth. Do not spray cleaners directly onto the keypad.
10 | Certifi cations
Region Certifi cation
US
CA
UL 365 - Police Station Connected Burglar Alarm
Units and Systems
UL 609 - Local Burglar Alarm Units and Systems
UL 985 - Household Fire Warning System Units
UL 1023 - Household Burglar-Alarm System Units
UL 1076 - Proprietary Burglar Alarm Units and
Systems
UL 1610 - Central Station Burglar Alarm Units
CSFM - California Offi ce of The State Fire
Marshal
FCC Part 15 Class B
Canada CAN/ULC S303 - Local Burglar Alarm
Units and Systems
CAN/ULC S304 - Signal Receiving Centre and
Premise Alarm Control Units
ULC-ORD C1023 - Household Burglar Alarm
System Units
ULC-ORD C1076 - Proprietary Burglar Alarm
Units and Systems
ICES-003 - Digital Apparatus
11 | Specifi cations
Dimensions
Voltage (input)
Current
12 VDC nominal
35 mA in standby mode
70 mA in alarm mode
Operating temperature 0°C to +50°C (+32°F to +122°F)
Relative humidity
6.2 in x 4.7 in x 1 in (158 mm x
120 mm x 26 mm)
Terminal wire size
5% to 93% at +32°C (+90°F) non-condensing
12 AWG to 22 AWG (2 mm to 65 mm)
SDI2 wiring
Compatibility
Maximum distance - wire size
(unshielded wire only):
1000 ft (305 m) - 22 AWG (0.65 mm)
B9512G/B9512G-E
B8512G/B8512G-E
B5512
B4512
B3512
D9412GV4 version 2.0 and higher
D7412GV4 version 2.0 and higher
(Refer to the control panel installation document for number of supported devices.)
Copyright
This document is the intellectual property of Bosch Security
Systems, Inc. and is protected by copyright. All rights reserved.
Trademarks
All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
Bosch Security Systems, Inc. product manufacturing dates
Use the serial number located on the product label and refer to the Bosch Security Systems, Inc. website at http://www.boschsecurity.com/datecodes/.
Two-line Alphanumeric Keypad
B920
en Installation Guide
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, NY 14450
USA www.boschsecurity.com
© 2015 Bosch Security Systems, Inc. F.01U.265.450 | 04 | 2015.02
advertisement
Key Features
- SDI2 Bus compatible
- Two-line LCD display
- User adjustable options
- Remote programming capability
- Status indicators
- Audible tones
- Supervised by control panel
- Firmware version display
- UL and CSA certified